Lutron Electronics PowPak FCJ-ECO Guía de instalación

Tipo
Guía de instalación

Este manual también es adecuado para

Lutron Electronics Co., Inc. 7200 Suter Road
Coopersburg, PA 18036-1299 USA
Test
Link
B
Hold the indicated button on each transmitter for 6seconds. The fixture will flash to show that wireless
transmitters have been associated. Alternatively, for Radio Powr SavrT occupancy/vacancy and daylight
sensors, the green laser pointer can be used. See Application Note #407 on www.lutron.com for more
information.
To associate another transmitter, repeat steps 2A and 2B.
A
Initiate association mode on the fixture control by shining a green laser pointer (by others) at the laser
detection hole on the sensor until the load attached to the control module starts flashing (every 2 seconds).
Alternatively, press and hold the Toggle button “ ” for 6 seconds on the fixture control to initiate
association mode.
Note: Multiple fixture controls can be placed into association mode by repeating one of the two above methods for the next
fixture control prior to moving to Step 2B.
Associate Transmitters to Fixture Control
Before beginning this step, make sure that there are no other fixture controls being set up in the building which
are currently in association mode. It is possible that wireless transmitters from other systems can be incorrectly
associated to this module.
Important Note: To optimize RF performance of the product:
Keep the lamp wiring as short as possible to reduce the radiation from
the lamp wires.
Keep the lamp wiring as far as possible from the PowPakR Wireless
Fixture Control mounting location.
See the Troubleshooting section for more details.
PowPakR Fixture Control Knockout
PowPakR Fixture Control Wiring
Lamp Wiring
Maximize Distance
Technical Assistance | 1.800.523.9466 USA, Canada, and the Caribbean | +44.(0)20.7702.0657 Europe | +1.610.282.3800 Others | www.lutron.com
Part of the Energi TriPak® Family
PowPak® Fixture Controls
Installation
Required Components
For each fixture, you will need:
PowPakR Fixture Sensor
(FC-SENSOR or
FC-VSENSOR)
(1 maximum)
PicoR Wireless
Control
(10 maximum)
6 mA maximum for the control lines. Switches up to 1 A total
(or maximum 3 ballasts or drivers). May be pre-installed in fixture.
PowPakR Wireless Fixture Control
(FCJ-010 or FCJ-ECO)
Raise
Toggle
Lower
Load
Status
LED
Consult the fixture installation guide for fixture wiring.
Start Here
English
Important Notes:
For installation by a qualified electrician in accordance with all local and
national electrical codes.
Use copper conductors only.
Check to see that the device type and rating is suitable for the application.
DO NOT install if product has any visible damage.
If moisture or condensation is evident, allow the product to dry completely
before installation.
Operate between 32 °F and 104 °F (0 °C and 40 °C), ambient.
0% to 90% humidity, non-condensing.
For indoor use only.
120 – 277 V~ 50 / 60 Hz 1 A switching
FCJ-010
0–10 V-
FCJ-ECO
Lutron®
EcoSystem®
PowPak® Wireless Fixture Control
UL 2043 Plenum Rated
Controls up to 3 ballasts or drivers (IEC 60929 Annex E.2 requires each ballast or
driver to limit the sink/source current draw to 2.0 mA maximum).
Provides IEC SELV / NECR Class 2, 12 V-, 25 mA to a PowPakR fixture sensor
(FC-SENSOR or FC-VSENSOR).
PIR Lens
Laser
Detection
Daylight Lens
Radio Powr SavrT
Occupancy/Vacancy
Sensor
(10 maximum)
Radio Powr SavrT
Daylight Sensor
(1 maximum)
Install Fixture Control and Optional Fixture Sensor
Suggested Installation Location: Close to the Fixture / Troffer.
The fixture control can be installed on a fixture/troffer, junction box or marshalling box using the conduit nut
(provided) or with mounting screws (not provided). Please consult local and national electric codes for proper
installation.
A
Ideally, mount the sensor to the ceiling tile close to the fixture using the wireform or using the adhesive strip
(included). The two communication wires from the sensor attach to the fixture control stab-in connectors. The
wires are interchangeable to eliminate miswiring.
B
Once installed, energize the control module. The fixture will turn on.
WARNING! Shock Hazard. May result in serious injury or death.
Turn off power at circuit breaker before installing the unit.
6 mA sink/source
Notes:
1. Fixture control can be used
without a fixture sensor as long
as at least one Radio Powr
SavrT sensor or PicoR wireless
control is used.
2. Only one fixture control can be
used per fixture sensor, and
only one fixture sensor can be
used per fixture control.
Pico®
wireless
control
30 ft (9 m)
maximum
PowPakR Fixture
Control
Install the fixture control directly to a fixture or
on a junction box nearest to the fixture. Install
the sensor on the ceiling near the fixture to
optimize coverage in the desired area.
Fixture
Control
Sensor
For more information, see
www.lutron.com/TechnicalDocumentLibrary/369866.pdf
Notes:
1. Control wires (Violet/Gray for FCJ-010 or Violet/Violet for FCJ-ECO) can
be run as either Class1 or Class2.
2. If hanging pendant fixtures the maximum wire length between fixture
sensor and fixture control is 12ft (3.7 m). Sensor should be mounted no
more than 2 ft (0.6 m) from the fixture.
3. To install unit inside a junction box, please see Application Note 423 on
www.lutron.com
4. The fixture control needs to be accessible for some programming steps.
Record where it is mounted so that it can be easily located later.
5. When using a Radio Powr SavrT daylight sensor in conjunction with both
a PowPakR wireless fixture control and PowPakR fixture sensor, the
Radio Powr SavrT daylight sensor will provide the daylighting input to the
control module, and the PowPakR fixture sensor daylighting input will be
ignored.
6. When using a Radio Powr SavrT occupancy sensor in conjunction with
both a PowPakR wireless fixture control and PowPakR fixture sensor,
occupancy data from both sensors is used; either one detecting
occupancy will turn the lights on, and the lights turn off only when both
sensors have gone vacant (no longer detect occupancy).
7. For more information on the PowPakR fixture sensor, see: Document
369866 or 048556 on www.lutron.com
For FC-SENSOR and FC-VSENSOR installation guide visit www.lutron.com
Wireless sensors
and controls must
be located within
60 ft (18 m) line of sight,
or 30 ft (9 m), through walls, of
the associated control module.
041485
Rev. A
04/2015
Please read before installing.
+
One Fixture Control
At least one of these transmitters (22 total allowed)
FCJ-010: At least one 0 10 V Fluorescent Ballast or LED Driver
FCJ-ECO: At least one Lutron® EcoSystem® Ballast or LED Driver
+
1
2
120 – 277 V~ 50 / 60 Hz 1A switching
14 V- 6 mA
OR
Laser Detection
Green laser specifications:
Wave output: constant
Wavelength: 532 nm
Output power: 5 mW
Note: The fixture control will automatically exit
association mode 10 minutes after the last activity.
Wireless Controls: All lights
Default Functionality
Fixture Controls
Auto On level: FC-SENSOR only
(not applicable for FC-VSENSOR)
Varies with ambient light level when occupancy is triggered
(e.g., 100% for a dark room, 10% for a bright room).
Timeout period: 15 minutes
On: 100% ; Favorite: 50%; Off: 0%
Green/Yellow
Neutral
Switched
Hot/Live
Violet
Gray
Fixture Earth
+
To additional 0 10 V fixtures
Hot (Black)
Neutral
+
NEU
HOT
Class 2
MAINS
+
NEU
HOT
Class 2
MAINS
+ Violet (both FCJ-010 and FCJ-ECO)
Gray (FCJ-010) / Violet (FCJ-ECO)
Fixture Earth
Green/Yellow
Switched Hot (Red)
Hot (Black)
Neutral (White)
Neutral
Fixture/Troffer
or Junction
Box
1/2 in (21 mm) Knockout Opening
From back
of sensor
Ballast / Driver
Conduit Nut
ALL PROGRAMMING IS OPTIONAL
Programming is not required for default functionality
Set a favorite light level
Set high-end and low-end trim for all fixtures
Lutron Electronics Co., Inc.
7200 Suter Road
Coopersburg, PA 18036-1299 USA
)Lutron, Lutron, Pico, PowPak, EcoSystem, and Energi TriPak are registered trademarks and Radio Powr Savr is a trademark of Lutron Electronics Co., Inc.
NEC is a registered trademark of the National Fire Protection Association, Quincy, Massachusetts.
©2014 – 2015 Lutron Electronics Co., Inc.
Reset Factory Defaults
Note: In some instances, it may be necessary to reset
the fi xture controls and connected devices back to
factory default settings. Before beginning, make sure
that all devices are connected and powered.
A
Rapidly tap the Toggle button “ ” on the fi xture
control three times and hold on the fourth until the
LED begins to flash slowly; release button.
B
Within 3 seconds of the start of flashing, again rapidly
tap the Toggle button “ ” three times and the LEDs
will flash rapidly indicating that the unit has been reset
to factory defaults.
Note: Any associations or programming previously set
up with the fi xture control will be erased and will need
to be re-programmed.
Raise
Lower
Favorite
FCC Information
This device complies with part 15 of the FCC Rules and Industry Canada license-exempt RSS standard(s). Operation is subject to the following two conditions: (1) This
device may not cause interference, and (2) this device must accept any interference, including interference that may cause undesired operation. Modifications not expressly
approved by Lutron Electronics Co., Inc. could void the user’s authority to operate this equipment.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed
to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not
installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not
occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off
and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Re-orient or relocate the receiving antenna.
Increase the separation between the equipment and receiver.
Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
Set a Favorite Light Level (Optional)
For Pico® wireless controls with a Favorite Button.
PowPak® Fixture Controls
Programming
Part of the Energi TriPak® Family
A
Adjust lights to desired level:
Use the Raise button “
or Lower button “ ” on
the Pico® wireless control.
041485
Rev. A
04/2015
B
Save favorite level:
Press and hold the Favorite
button for 6seconds.
The load will flash 3 times to
confirm that the Favorite level
is saved.
Limited Warranty:
http://www.lutron.com/TechnicalDocumentLibrary/369-119_Wallbox_Warranty.pdf
Low-End Trim
A
Enter low-end trim adjustment mode:
Press and hold the Lower button “ ” on the fixture control for 12 seconds.
The lights will flash and the load status LED will begin flashing.
B
Adjust the low-end trim:
Use the Raise button “ ” and Lower button “ ” on the fixture control to adjust and
set the lights to the desired low-end (1to 45%).
C
Save the low-end trim:
Press and hold the Toggle button “ ” for 6seconds to save setting.
The load status LED will begin flashing and then turn solid to indicate new level has
been saved.
High-End Trim
A
Enter high-end trim adjustment mode:
Press and hold the Raise button “ ” on the fixture control for 12seconds.
The lights will flash and the load status LED will flash.
B
Adjust the high-end trim:
Use the Raise button “ ” and Lower button “ ” on the fixture control to adjust and
set the lights to the desired high-end (55to 100%).
C
Save the high-end trim:
Press and hold the Toggle button “ ” for 6seconds to save setting.
The load status LED will begin flashing and then turn solid to indicate new level has
been saved.
Set Low-End Trim and High-End Trim (Optional)
For best results, minimize the amount of sunlight entering the room before
performing the following procedures.
Depending on the fixture manufacturer or load, low-end trim and high-end trim
may need to be adjusted.
Trim low-end to ensure a stable light level because some loads will flicker or drop
out if trimmed too low.
Be sure that you can turn on the lights to the low-end trim level without any
abnormal operation.
The factory default high-end trim is suitable for most applications but can be
adjusted as desired.
1
Troubleshooting www.lutron.com
Symptom Solution
Ballasts / drivers cannot
be controlled locally from
the fi xture control.
Ensure that the breaker(s) to the fixture control are energized.
Ensure that the fixture control switched hot lead is wired to the ballast / driver (FCJ-010).
Ensure that the fixture control control lines (FCJ-010: violet/gray, FCJ-ECO: violet/violet) are wired
to the ballast / driver.
If using FCJ-010, verify the driver/ballast is 0–10 V.
If using FCJ-ECO, use the LutronR EcoSystemR driver/ballast.
Reset to factory defaults.
Lights do not dim or turn
ON as expected.
Ensure that control lines are wired properly (FCJ-010: violet/gray-polarity-sensitive,
FCJ-ECO: violet/violet)
Ensure that the wires are connected between the fixture sensor and the fi xture control.
FCJ-010 only: Make sure that 0–10 V- fixture is at low-end (at 0 V), not OFF (at 0 V).
If OFF (at 0 V), adjust low-end trim.
FCJ-010 only: Ensure that fixture does not require an inverted signal (10 0 V- control).
FCJ-010 only: Verify that the voltage across the gray and violet wires is between 0 and 10 V-.
FCJ-ECO only: Disconnect the violet / violet wires from the fixture control. Verify that the lights go to
100%.
FCJ-010 only: Disconnect the violet / gray wires from the fixture control. Verify that the lights go to
100%. Short the violet / gray wires on the ballast / driver, verify that the lights go to low-end.
Lights do not respond to
wireless transmitter(s).
Ensure that the breaker(s) to the fixture control and ballasts / drivers are energized.
Ensure that wireless transmitters are associated to the fixture control.
Reset to factory defaults.
Wireless transmitter(s)
cannot be associated to
the fixture control.
The maximum number of wireless transmitters have been associated to the fixture control. To
remove a previously set up wireless transmitter, tap any button on the wireless transmitter three
times; on the third tap, hold for three seconds and then tap three more times.
RF range between
wireless controls is
diminished below 30 ft
(9 m).
Keep the ballast/driver wiring as short as possible and well organized to avoid excess wire being
bunched up.
Keep the first 7-12 in (20-30 cm) of the wires coming out of the fixture control knockout separated
as much as possible from any nearby ballast/driver/lamp wires.
Contact LutronR technical support for further assistance.
Lights are unstable at
low-end.
Adjust low-end trim.
Fixture sensor does not
turn the lights ON.
Check that fixture sensor wires are connected to fixture control.
FC-VSENSOR is vacancy only (it will not turn the lights on).
FCJ-ECO cannot be
addressed.
All drivers/ballasts connected to an FCJ-ECO function as a single zone. If more than one zone is
required, use RMJ-ECO32-DV-B.
For more information on the PowPakR fixture sensor, see Document 369866 or 048556 on www.lutron.com
For FC-SENSOR and FC-VSENSOR installation guide visit www.lutron.com
NOTE: High-end and low-end trim can also
be performed for a single unit or group of
units simultaneously with a PicoR wireless
control.
For more information see document 048556
on www.lutron.com.
Technical Assistance | 1.800.523.9466 USA, Canada, and the Caribbean | +44.(0)20.7702.0657 Europe | +1.610.282.3800 Others | www.lutron.com
2
Start Here
Lutron Electronics Co., Inc.7200 Suter Road
Coopersburg, PA 18036-1299 E.U.A.
Test
Link
B
Mantenga pulsado el botón indicado en cada transmisor durante 6 segundos. El artefacto destellará para
mostrar que los transmisores inalámbricos han sido asociados. Alternativamente, para los sensores de
ocupación/vacancia y luz diurna Radio Powr SavrT, puede utilizarse el puntero láser verde. Para obtener
más información consulte la Nota de aplicación Nº 407 en www.lutron.com. Para asociar otro transmisor,
repita los pasos 2A y 2B.
A
Inicie el modo de asociación en el control de artefactos haciendo brillar un puntero láser verde (de terceros)
en el orificio de detección láser del sensor hasta que la carga conectada al módulo de control comience a
destellar (cada 2 segundos).
Alternativamente, pulse y mantenga pulsado el botón Encender y Apagar ” durante 6 segundos en el
control de artefactos para iniciar el modo de asociación.
Nota: Pueden ponerse varios controles de artefactos en el modo de asociación repitiendo uno de los dos métodos
anteriores para el próximo control de artefactos antes de continuar al Paso 2B.
Asocie los transmisores al control de artefactos
Antes de comenzar este paso, asegúrese de que no haya otros controles de artefactos que estén siendo
configurados en el edificio y que se encuentren actualmente en el modo de asociación. Es posible que los
transmisores inalámbricos de otros sistemas puedan estar asociados incorrectamente a este módulo.
Tapa ciega del control de artefactos PowPakR
Cableado del control de artefactos PowPakR
Cableado de la lámpara
Maximice la distancia
Nota importante: Para optimizar el desempeño de RF del producto:
Mantenga el cableado de la lámpara lo más corto posible para reducir la
radiación de los cables.
Mantenga el cableado de las lámparas lo más alejado posible de la ubicación
de montaje del control inalámbrico de artefactos PowPakR.
Para obtener más detalles consulte la sección de Solución de Problemas.
Asistencia técnica | 1.800.523.9466 E.U.A., Canadá y el Caribe | +44.(0)20.7702.0657 Europa | +1.610.282.3800 Demás países | www.lutron.com
Parte de la familia Energi TriPak®
Módulo de Atenuación PowPak®
Instalación
Componentes requeridos
Para cada artefacto, se necesitará:
Sensor de artefactos
PowPakR (FC-SENSOR o
FC-VSENSOR)
(1 máximo)
Control
inalámbrico PicoR
(10 máximo)
6 mA máximo para las líneas de control. Conmuta hasta 1 A en
total (o un máximo de tres balastos o controladores). Puede ser
preinstalado en el artefacto.
Control inalámbrico de artefactos
PowPakR (FCJ-010 o FCJ-ECO)
Subir
Encender y
Apagar
Bajar
LED de
estado
de la
carga
Para informarse del cableado de los artefactos consulte la guía de
instalación de artefactos.
Comience aquí
Español
Notas importantes:
Para ser instalados por un electricista calificado de acuerdo con todas
las normativas eléctricas locales y nacionales.
Sólo utilice conductores de cobre.
Verifique que el tipo de dispositivo y la certificación sean adecuados para
la aplicación.
NO instale este producto si tuviera algún daño visible.
Si hubiera señales evidentes de humedad o condensación, permita que
el producto se seque por completo antes de la instalación.
Opérelo entre 0 °C y 40 °C (32 °F y 104 °F) de temperatura ambiente.
0 a 90% de humedad, sin condensación.
Sólo para uso bajo techo.
Conmutación de 120 277 V~ 50/60 Hz 1 A
FCJ-010
0–10 V-
FCJ-ECO
Lutron®
EcoSystem®
Control inalámbrico de artefactos PowPak®
Homologado UL 2043 para plenum
Controla hasta tres balastos o controladores (la norma IEC 60929 anexo E.2
requiere que cada balasto o controlador limite la corriente de fuente/drenaje a
2,0 mA como máximo).
Suministra 12 V- , 25 mA IEC SELV/NECR Clase 2 a un sensor de artefactos
PowPakR (FC-SENSOR o FC-VSENSOR).
Lente PIR
Detección
de láser
Lente de luz
diurna
Sensor de ocupación/
vacancia Radio Powr SavrT
(10 máximo)
Sensor de luz
diurna Radio Powr
SavrT
(1 máximo)
Instale el control de artefactos y el sensor de artefactos opcional
Ubicación de instalación sugerida: Cercana a un artefacto/luminaria.
El control del artefactos puede instalarse en un artefacto/luminaria, caja de conexiones o caja organizadora
utilizando la tuerca de conducto (suministrada) o con tornillos de montaje (no suministrados). Para obtener una
instalación adecuada consulte las normativas eléctricas locales y nacionales.
A
Idealmente, monte el sensor a la placa de techo cerca del artefacto utilizando el gancho de montaje o la cinta
adhesiva (incluidos). Los dos cables de comunicación del sensor se conectan a los conectores de cuchilla del
control de artefactos. Los cables son intercambiables para eliminar los defectos de cableado.
B
Una vez instalado, energice el módulo de control. Este artefacto se encenderá.
¡ADVERTENCIA! Peligro de descarga eléctrica. Podría ocasionar lesiones graves o la
muerte.Antes de instalar el equipo desconecte el suministro eléctrico en el disyuntor.
Fuente/drenaje de 6 mA
Notas:
1. El control de artefactos puede
utilizarse sin un sensor de
artefactos siempre y cuando
se utilice al menos un sensor
Radio Powr SavrT o un
control inalámbrico PicoR.
.
2. Sólo puede utilizarse un
control de artefactos por
sensor de artefactos, y sólo
puede utilizarse un sensor
de artefactos por control de
artefactos.
Control
inalámbrico
Pico®
9 m (30 pies)
como máximo
Control de
artefactos PowPakR
Instale el control de artefactos
directamente en un artefacto o en la caja de
conexiones más cercana al artefacto. Instale el
sensor en el cielorraso cerca del artefacto para
optimizar la cobertura en el área deseada.
Control
de
artefactos
Sensor
Para obtener información adicional, consulte
www.lutron.com/TechnicalDocumentLibrary/369866.pdf
Notas:
1. Los cables de control (violeta/gris para el FCJ-010 o violeta/violeta para
el FCJ-ECO) pueden ser tendidos como Clase 1 o Clase 2.
2. Con artefactos colgantes la máxima longitud de cable entre el sensor de
artefactos y el control de artefactos es de 3,7 m (12 pies). El sensor
deberá ser montado a no más de 0,6 m (2 pies) del artefacto.
3. Para instalar el equipo en el interior de una caja de conexiones, consulte
la Nota de aplicación 423 en www.lutron.com
4. El control de artefactos tiene que ser accesible para algunos pasos de
programación. Registre dónde está montado para que pueda ubicarlo
fácilmente más adelante.
5. Cuando se utilice un sensor de luz diurna Radio Powr SavrT en conjunto
con tanto un control inalámbrico de artefactos PowPakR y un sensor
de artefactos PowPakR, el sensor de luz diurna Radio Powr SavrT
proporciona la entrada de iluminación diurna al módulo de control, y la
entrada de luz diurna del sensor de artefactos PowPakR será ignorada.
6. Cuando se utilice un sensor de ocupación Radio Powr SavrT en conjunto
tanto con un control inalámbrico de artefactos PowPakR como con un
sensor de artefactos PowPakR, se utilizan los datos ocupación de ambos
sensores; cualquiera de ellos que detecte una ocupación encenderá las
luces, y éstas sólo se apagarán cuando ambos sensores pasen al modo
de vacancia (ya no detectan ocupación).
7. Para obtener más información sobre el sensor de artefactos PowPakR
consulte: Documentos 369866 o 048556 en www.lutron.com
Para obtener la guía de instalación del FC-SENSOR y FC-VSENSOR visite
www.lutron.com
Los sensores
y controles
inalámbricos deben
estar situados a
menos de 18 m (60 pies)
con línea de visión directa, o
9 m (30 pies) a través de paredes,
del módulo de control asociado.
041485
Rev. A
04/2015
Por favor lea antes de instalar.
+
Un control de artefactos
Al menos uno de estos transmisores (permitidos 22 en total)
FCJ-010: Al menos un balasto fluorescente o controlador de LED de 0 0 V
FCJ-ECO: Al menos un balasto o controlador de LED Lutron® EcoSystem®
+
1
2
Conmutación de 120 277 V~ 50/60 Hz 1 A
14 V- 6 mA
O
Detección de láser
Especificaciones del láser verde:
Salida de onda: constante
Longitud de onda: 532 nm
Potencia de salida: 5 mW
Nota: El control de artefactos saldrá automáticamente
del modo de asociación 10 minutos después de la
última actividad.
Controles inalámbricos: Todas las luces
Funcionalidad predeterminada
Controles de artefactos
Nivel Automático Activado: FC-SENSOR únicamente
(no aplicable para FC-VSENSOR)
Varía con el nivel de luz ambiental cuando se dispara la
ocupación (p. ej., 100% para una habitación oscura, 10% para
una habitación iluminada).
Intervalo de espera: 15 minutos
Encendida: 100%; Favorito: 50%; Apagada: 0%
Green/Yellow
Neutral
Switched
Hot/Live
Violet
Gray
Fixture Earth
+
To additional 0 10 V fixtures
Hot (Black)
Neutral
+
NEU
HOT
Class 2
MAINS
+
NEU
HOT
Class 2
MAINS
+ Violeta (tanto FCJ-010 como FCJ-ECO)
Gris (FCJ-010) / Violeta (FCJ-ECO)
Tierra del artefacto
Verde/Amarillo
Conmutado vivo (rojo)
Vivo (negro)
Neutro (blanco)
Neutro
Artefacto/
Luminaria
o caja de
conexiones
Abertura con tapa ciega de 21 mm (1/2 pulg)
Desde
la parte
trasera del
sensor
Balasto/Controlador
Tuerca del conducto
TODA LA PROGRAMACIÓN ES OPCIONAL
Para la funcionalidad predeterminada no se requiere
programación
• Configure un nivel de luz favorito
Configure el ajuste del intensidad mínima y el intensidad
máxima para todos los artefactos
Lutron Electronics Co., Inc.
7200 Suter Road
Coopersburg, PA 18036-1299 E.U.A.
)Lutron, Lutron, Pico, PowPak, EcoSystem y Energi TriPak son marcas comerciales registradas y Radio Powr Savr es una marca comercial de Lutron Electronics Co., Inc.
NEC es una marca comercial registrada de la National Fire Protection Association, Quincy, Massachusetts.
© 2014-2015 Lutron Electronics Co., Inc.
Restablezca los valores
predeterminados de fábrica
Nota: En algunos casos puede ser necesario restablecer
la configuración predeterminada de fábrica tanto de
los controles de artefactos como de los dispositivos
conectados. Antes de comenzar, asegúrese de que
todos los dispositivos estén conectados y energizados.
A
Pulse rápidamente tres veces el botón Encender y
Apagar en el control de artefactos y manténgalo
pulsado la cuarta vez hasta que el LED comience a
destellar lentamente; suelte el botón.
B
Dentro de los 3 segundos del comienzo del destello,
pulse de nuevo rápidamente tres veces el botón
Encender y Apagar ” y los LED destellarán
rápidamente, indicando que el equipo ha sido
restablecido a los valores predeterminados de fábrica.
Nota: Toda asociación o programación establecida con
anterioridad para el control de artefactos será borrada y
tendrá que ser reprogramada.
Subir
Bajar
Favorito
Información de la FCC
Este dispositivo satisface la parte 15 de las reglas de la FCC y las normas RSS de exención de licencia de Industry Canada. La operación está sujeta a las dos siguientes
condiciones: (1) Este dispositivo no debe causar interferencias perjudiciales y (2) este dispositivo debe aceptar cualquier interferencia, incluida la interferencia que pudiera
ocasionar una operación no deseada. Las modificaciones no aprobadas expresamente por Lutron Electronics Co., Inc. podrían invalidar la autorización del usuario para
utilizar este equipo.
NOTA: Este equipo ha sido comprobado y se lo encontró comprendido dentro de los límites para un dispositivo digital clase B, según la sección 15 de las reglas de la
FCC. Estos límites están diseñados para proporcionar una protección razonable contra las interferencias perjudiciales en una instalación residencial. Este equipo genera,
utiliza y puede irradiar energía de radiofrecuencia, y si no se lo instala y utiliza de acuerdo con las instrucciones podría ocasionar interferencias perjudiciales para las
radiocomunicaciones. Sin embargo, no hay garantía de que no ocurran interferencias en una instalación en particular. Si este equipo ocasionara interferencias perjudiciales
para la recepción de radio o televisión, lo que puede ser determinado encendiéndolo y apagándolo, se recomienda al usuario que intente corregir la interferencia
adoptando una o más de las siguientes medidas:
Reorientar o reubicar la antena receptora.
Aumentar la separación entre el equipo y el receptor.
Conectar el equipo a un tomacorriente que corresponda a un circuito diferente de aquel al cual está conectado el receptor.
Configure un nivel de luz favorito
(opcional)
Para los controles inalámbricos Pico® con un botón
Favorito.
Módulo de Atenuación PowPak®
Programación
Parte de la familia Energi TriPak®
A
Ajuste las luces al nivel
deseado:
Utilice el botón Subir
o el botón Bajar ” del
control inalámbrico Pico®.
041485
Rev. A
04/2015
B
Guarde el nivel favorito:
Pulse y mantenga pulsado el
botón Favorito durante
6 segundos.
La carga destellará tres veces
para confirmar que el nivel
favorito ha sido guardado.
Garantía limitada:
http://www.lutron.com/TechnicalDocumentLibrary/369-119_Wallbox_Warranty.pdf
Ajuste de la intensidad mínima
A
Ingrese al modo de ajuste de la intensidad mínima:
Pulse y mantenga pulsado el botón Bajar ” del control de artefactos durante
12 segundos.
Las luces destellarán y el LED del estado de la carga comenzará a destellar.
B
Ajuste la intensidad mínima:
Utilice el botón Subir ” y el botón Bajar ” del control de artefactos para ajustar y
configurar las luces al nivel de intensidad mínima deseado (1 a 45%).
C
Guarde el ajuste de la intensidad mínima:
Pulse y mantenga pulsado el botón Encender y Apagar ” durante 6 segundos
para guardar la configuración.
El LED de estado de la carga comenzará a dwestellar y luego se iluminará
continuamente para indicar que el nuevo nivel ha sido guardado.
Ajuste de la intensidad máxima
A
Ingrese al modo de ajuste de la intensidad máxima:
Pulse y mantenga pulsado el botón Subir ” del control de artefactos durante
12 segundos. Las luces destellarán y el LED del estado de la carga destellará.
B
Ajuste la intensidad máxima:
Utilice el botón Subir ” y el botón Bajar ” del control de artefactos para ajustar
y configurar las luces al nivel de intensidad máxima deseado (55 a 100%).
C
Guarde el ajuste de la intensidad máxima:
Pulse y mantenga pulsado el botón Encender y Apagar ” durante 6 segundos
para guardar la configuración.
El LED de estado de la carga comenzará a destellar y luego se iluminará
continuamente para indicar que el nuevo nivel ha sido guardado.
Configure el ajuste de las intensidades mínima y máxima (opcional)
Para obtener los mejores resultados, minimice la cantidad de luz solar que ingresa
a la habitación antes de realizar los siguientes procedimientos.
En función del fabricante del artefacto o de la carga, podría ser necesario ajustar
las intensidades máxima y mínima.
Ajuste el intensidad mínima para asegurar un nivel estable de luz porque algunas
cargas parpadearán o caerán si se las ajusta demasiado bajas.
Asegúrese de que se pueda encender las luces al nivel de ajuste de intensidad
mínima sin tener que ejecutar ninguna operación anormal.
El ajuste de intensidad máxima predeterminado de fábrica es adecuado para
la mayoría de las aplicaciones, pero puede ajustarse como se desee.
1
Solución de Problemas www.lutron.com
Síntoma Solución
Los balastos/
controladores no
pueden ser controlados
localmente desde el
control de artefactos.
Asegúrese de que los disyuntores al control de artefactos estén energizados.
Asegúrese de que el cable conmutado en caliente del control de artefactos esté conectado al
balasto/controlador (FCJ-010).
Asegúrese de que las líneas de control del control de artefactos (FCJ-010: violeta/gris, FCJ-ECO:
violeta/violeta) se conecten al balasto/controlador.
Si se utiliza el FCJ-010, verifique que el controlador/balasto sea de 010 V.
Si se utiliza FCJ-ECO, emplee el controlador/balasto LutronR EcoSystemR.
Restablezca los valores predeterminados de fábrica.
Las luces no se atenúan
o ENCIENDEN como se
esperaba.
Asegúrese de que las líneas de control estén cableadas correctamente (FCJ-010: violeta/gris
sensible a la polaridad, FCJ-ECO: violeta/violeta)
Asegúrese de que los cables estén conectados entre el sensor de artefactos y el control de
artefactos.
Sólo FCJ-010: Asegúrese de que el artefacto de 010 V- esté en la intensidad mínima (a 0 V), y
no APAGADO (a 0 V). Si está APAGADO (a 0 V), ajuste la intensidad mínima.
Sólo FCJ-010: Asegúrese de que el artefacto no requiera una señal invertida (control de 10 0 V-).
Sólo FCJ-010: Verifique que el voltaje entre los cables gris y violeta esté entre 0 y 10 V-.
FCJ-ECO únicamente: Desconecte los cables violeta/violeta del control de artefactos. Verifique que
las luces pasen al 100%.
Sólo FCJ-010: Desconecte los cables violeta/gris del control de artefactos. Verifique que las luces
pasen al 100%. Cortocircuite los cables violeta/gris en el balasto/controlador, y verifique que las
luces pasen a la intensidad mínima.
Las luces no responden
a los transmisores
inalámbricos.
Asegúrese de que los disyuntores al control de artefactos y a los balastos/controladores estén
energizados.
Asegúrese de que los transmisores inalámbricos estén asociados al control de artefactos.
Restablezca los valores predeterminados de fábrica.
Los transmisores
inalámbricos no pueden
ser asociados al control
de artefactos.
Ha sido asociado al control de artefactos el número máximo de transmisores inalámbricos. Para
eliminar un transmisor inalámbrico previamente configurado, pulse tres veces cualquier botón del
transmisor inalámbrico; la tercera vez manténgalo pulsado durante tres segundos y luego púlselo
tres veces más.
El rango de RF entre los
controles inalámbricos
está reducido por debajo
de los 9 m (30 pies).
Mantenga el cableado del balasto/controlador lo más corto posible y bien organizado para evitar
que se apretuje el exceso de cables.
Mantenga las primeras 20-30 cm (7-12 pulg) separadas lo más posible de los cables provenientes de
la tapa ciega del control de artefactos de cualquier cable de balasto/controlador/lámpara cercanos.
Para obtener asistencia adicional póngase en contacto con la asistencia técnica de LutronR.
Las luces son inestables
a la intensidad mínima.
Configure el ajuste de la intensidad mínima.
El sensor de artefactos
no ENCIENDE las luces.
Verifique que los cables del sensor de artefactos estén conectados al control del artefacto.
El FC-VSENSOR es de vacancia únicamente (no encenderá las luces).
El FCJ-ECO no puede ser
gestionado.
• Todos los controladores/balastos conectados a una función de FCJ-ECO como una zona única.
Si se requiriera más de una zona, utilice el RMJ-ECO32-DV-B.
Para obtener más información sobre el sensor de artefactos PowPakR consulte: Documentos 369866 o 048556 en www.lutron.com
Para obtener la guía de instalación del FC-SENSOR y FC-VSENSOR visite www.lutron.com
NOTA: El ajuste de intensidad mínima
e intensidad máxima también se puede
realizar para una sola unidad o grupo
de unidades simultáneamente con un
control inalámbrico PicoR. Para obtener
más información, consulte el documento
048556 en www.lutron.com.
Asistencia técnica | 1.800.523.9466 E.U.A., Canadá y el Caribe | +44.(0)20.7702.0657 Europa | +1.610.282.3800 Demás países | www.lutron.com
2
Comience aquí
Lutron Electronics Co., Inc. 7200 Suter Road,
Coopersburg, PA 18036-1299, États-Unis
Test
Link
B
Maintenez le bouton indiqué enfoncé sur chaque transmetteur pendant 6 secondes. Le luminaire clignotera
indiquant que les transmetteurs sans fil ont été associés. De façon alternative, pour les détecteurs
d’occupation/inoccupation et de lumière du jour Radio Powr SavrT, le pointeur laser vert peut être utilisé.
Voir la note d’application 407 sur www.lutron.com pour plus d'informations.
Pour associer un autre transmetteur, répétez les étapes 2A et 2B.
A
Démarrez le mode d’association sur la commande de luminaire en dirigeant un pointeur laser vert (d’un
fabricant tiers) allumé sur le trou de détection de laser du détecteur jusqu’à ce que la charge liée au module
de commande commence à clignoter (toutes les 2 secondes).
De façon alternative, appuyez et maintenez le bouton de Alterner
«
»
enfoncé pendant 6 secondes sur
la commande de luminaire pour démarrer le mode d’association.
Remarque: Plusieurs commandes de luminaires peuvent être placées en mode d’association en répétant l'une des deux
méthodes ci-dessus pour la commande de luminaire suivante avant de passer à l’étape 2B.
Associer des transmetteurs à la commande de luminaire
Avant d’entamer cette étape, veillez à ce qu’aucune autre commande de luminaire en phase de
configuration dans le bâtiment ne soit actuellement en mode d’association. Les transmetteurs sans fil
d'autres systèmes peuvent s’associer à ce module de façon incorrecte.
Remarque importante : Pour optimiser les performances de
radiofréquences du produit :
Réduisez la longueur du câblage de la lampe au maximum pour réduire le
rayonnement des fils de la lampe.
Gardez le câblage de la lampe aussi loin que possible de l’emplacement
du montage de la commande de luminaire sans fil PowPakR.
Voir la section Dépannage pour plus d’informations.
Perforation de la commande de luminaire PowPakR
Câblage de la commande de luminaire PowPakR
Câblage de lampe
Maximisez la distance
Assistance technique | 1.800.523.9466 É.-U., Canada, et les Caraïbes | +44.(0)20.7702.0657 Europe | +1.610.282.3800 Autres | www.lutron.com
Appartient à la famille Energi TriPak®
Commandes de luminaires
PowPak® : Installation
Composants requis
Pour chaque luminaire, vous aurez besoin de :
Détecteur de luminaire
PowPakR
(FC-SENSOR ou
FC-VSENSOR)
(1 maximum)
Commande sans
fil PicoR
(10 maximum)
6 mA maximum pour les lignes de commande. Commute
jusqu'à 1 A au total (ou 3 ballasts ou pilotes maximum). Peut être
préinstallé dans un luminaire.
Commande de luminaire sans fil
PowPakR (FCJ-010 ou FCJ-ECO)
Monter
Alterner
Baisser
DEL
d’état
de la
charge
Consultez le guide d'installation du luminaire pour le câblage du
luminaire.
Commencez ici
Français
Remarques importantes :
À faire installer par un électricien qualifié conformément à tous les codes
électriques en vigueur.
N'utilisez que des conducteurs en cuivre.
Veillez à ce que le type d'appareil et sa caractéristique nominale
conviennent à l'application.
Ne l'installez PAS si le produit présente des dommages visibles.
Si de l'humidité ou de la condensation est apparente, laissez le produit
sécher avant son installation.
Fonctionne de 0°C à 40°C (32°F à 104°F), température ambiante.
0 à 90 % d’humidité, sans condensation.
Utilisation à l'intérieur uniquement.
Commutation 120 277 V~ 50 / 60 Hz 1 A
FCJ-010
0–10 V-
FCJ-ECO
EcoSystem®
de Lutron®
Commande de luminaire PowPak®
Conformité plénum de la norme UL 2043
Commande jusqu'à 3 ballasts ou pilotes (la norme IEC 60929 Annexe E.2 exige que
chaque ballast ou pilote limite le courant de source/absorbé à 2,0 mA au maximum).
Fournit une alimentation IEC SELV / NECR de classe 2 de 12 V-, 25 mA à un
détecteur de luminaire PowPakR (FC-SENSOR ou FC-VSENSOR).
Lentille PIR
Détection
du laser
Lentille de
lumière du jour
Détecteur d'occupation/
inoccupation
Radio Powr SavrT
(10 maximum)
Détecteur de
lumière du jour
Radio Powr SavrT
(1 maximum)
Installer la commande de luminaire et le détecteur de luminaire optionnel
Emplacement recommandé pour l'installation : Près d'un luminaire / plafonnier.
La commande de luminaire peut être installée sur un luminaire / plafonnier, dans un boîtier de raccordement
ou un boîtier de regroupement avec l’écrou de conduit (fourni) ou des vis de montage (non fournies). Veuillez
consulter les codes électriques en vigueur pour une installation correcte.
A
Si possible, montez le détecteur sur une dalle de plafond à proximité du luminaire au moyen du fil ou de la
bande adhésive (inclus). Reliez les deux fils de communication du détecteur aux fiches de connexion de la
commande de luminaire. Les fils sont interchangeables pour éviter un mauvais câblage.
B
Une fois installé, mettez le module de commande sous tension. Le luminaire s’allumera.
AVERTISSEMENT ! Risque d'électrocution. Peut causer des blessures graves ou la
mort. Coupez l'alimentation au niveau du disjoncteur avant d'installer l'unité.
Courant de source/absorbé 6 mA
Remarques :
1. La commande de luminaire
peut être utilisée sans détecteur
de luminaire à condition qu'au
moins un détecteur Radio Powr
SavrT ou une commande sans
fil PicoR est utilisé.
2. Une seule commande de
luminaire peut être utilisée par
détecteur de luminaire et un
seul détecteur de luminaire peut
être utilisé par commande de
luminaire.
Commande
sans fil Pico®
9 m (30 pi)
maximum
Commande de
luminaire PowPakR
Installez la commande de luminaire
directement sur un luminaire ou un boîtier de
raccordement près du luminaire. Installez le détecteur
au plafond près du luminaire pour optimiser sa portée
dans la zone souhaitée.
Commande
de
luminaire
Détecteur
Pour plus d'information, consultez :
www.lutron.com/TechnicalDocumentLibrary/369866.pdf
Remarques :
1. Les fils de commande (Violet/Gris pour le FCJ-010 ou Violet/Violet pour le
FCJ-ECO) peuvent être de classe1 ou de classe2.
2. En cas d’utilisation de luminaire suspendu, la longueur maximale du fil
entre le détecteur de luminaire et la commande de luminaire est de 3,7 m
(12pi). Le détecteur doit être monté à moins de 0,6 m (2 pi) du luminaire.
3. Pour installer l’unité dans un boîtier de raccordement, veuillez consulter la
note d’application 423 sur www.lutron.com
4. La commande de luminaire doit être accessible pour certaines étapes de
programmation. Documentez où elle est montée de façon à la localiser
facilement ultérieurement.
5. En cas d’utilisation d’un détecteur de lumière du jour Radio Powr SavrT
en conjonction avec une commande de luminaire sans fil PowPakR et un
détecteur de luminaire PowPakR, le détecteur de lumière du jour Radio
Powr SavrT fournit les données de la lumière du jour au module de
commande, et les données de lumière du jour du détecteur de luminaire
PowPakR sont ignorées.
6. En cas d’utilisation d’un détecteur d’occupation Radio Powr SavrT en
conjonction avec une commande de luminaire sans fil PowPakR et un
détecteur de luminaire PowPakR, les données d’occupation des deux
détecteurs sont utilisées; toute détection d’occupation de l’un d’entre eux
allume les lumières, et les lumières s’éteignent seulement quand les deux
détecteurs sont en mode d’inoccupation (ils ne détectent plus d’occupation).
7. Pour plus d'informations concernant le détecteur de luminaire PowPakR,
consultez: Document 369866 ou 048556 sur www.lutron.com
Pour le guide d'installation du FC-SENSOR et FC-VSENSOR consultez
www.lutron.com
Les détecteurs
sans fil et les
commandes
doivent se situer
à moins de 18 m (60 pi)
en ligne directe du module de
commande associé ou à moins
de 9 m (30 pi) à travers les murs.
041485
Rév. A
04/2015
Veuillez lire avant l'installation.
+
Une commande de luminaire
Au moins un de ces transmetteurs (22 permis au total)
FCJ-010 : Au moins un ballast fluorescent ou un pilote de DEL de 0 10 V
FCJ-ECO : Au moins un pilote de DEL ou ballast EcoSystem® de Lutron®
+
1
2
Commutation 120 277 V~ 50 / 60 Hz 1A
14 V- 6 mA
OU
Détection du laser
Caractéristiques du laser vert :
Sortie d’onde : constante
Longueur d’onde : 532 nM
Puissance de sortie : 5 mW
Remarque : La commande de luminaire quitte
automatiquement le mode d’association 10 minutes
après la dernière activité.
Commandes sans fil : Toutes les lumières
Fonctionnalité par défaut
Commandes de luminaires
Niveau d’allumage automatique : FC-SENSOR seulement
(pas applicable pour le FC-VSENSOR)
Varie avec le niveau de lumière ambiante lorsque l’occupation se
déclenche (ex.: 100 % dans une pièce sombre, 10 % dans une
pièce lumineuse).
Période de délai d'extinction : 15 minutes
Allumé : 100 % ; Favori : 50 % ; Éteint : 0 %
Green/Yellow
Neutral
Switched
Hot/Live
Violet
Gray
Fixture Earth
+
To additional 0 10 V fixtures
Hot (Black)
Neutral
+
NEU
HOT
Class 2
MAINS
+
NEU
HOT
Class 2
MAINS
+ Violet (FCJ-010 et FCJ-ECO)
Gris (FCJ-010) / Violet (FCJ-ECO)
Terre de l’applique
Vert/Jaune
Conducteur commuté (Rouge)
Conducteur (Noir)
Neutre (Blanc)
Neutre
Luminaire /
plafonnier
ou boîtier de
raccordement
Entrée à perforer de 21 mm (1/2 po)
Depuis
l'arrière du
détecteur
Ballast / Pilote
Écrou de conduit
TOUTE PROGRAMMATION EST OPTIONNELLE
Le fonctionnement par défaut ne nécessite aucune
programmation
• Régler un niveau de lumière favori
• Régler les seuils hauts et bas de toutes les appliques
Lutron Electronics Co., Inc.
7200 Suter Road
Coopersburg, PA 18036-1299, États-Unis
)Lutron, Lutron, Pico, PowPak, EcoSystem et Energi TriPak sont des marques déposées et Radio Powr Savr est une marque de Lutron Electronics Co., Inc.
NEC est une marque déposée de la National Fire Protection Association, Quincy, Massachusetts.
©2014 – 2015 Lutron Electronics Co., Inc.
Restaurer les réglages d'usine
Remarque : Dans certains cas, il peut être nécessaire
de réinitialiser les commandes de luminaires et les
appareils raccordés à leurs réglages d’usine par
défaut. Avant de démarrer, vérifiez que tous les
appareils sont raccordés et alimentés.
A
Appuyez trois fois rapidement sur le bouton de
Alterner « » sur la commande de luminaire et
maintenez-le enfoncé la quatrième fois jusqu’à ce que
la DEL commence à clignoter lentement; relâchez le
bouton.
B
Après 3 secondes de clignotement, rappuyez sur
le bouton de Alterner « » trois fois rapidement et
les DEL clignoteront rapidement, indiquant que les
réglages d’usine de l’unité ont été restaurés.
Remarque : Toute association ou programmation
configurée précédemment avec la commande de
luminaire sera perdue et devra être reprogrammée.
Monter
Baisser
Favori
Informations FCC
Cet appareil est conforme à la partie 15 des règles du FCC et aux normes industrielles RSS d’exemption de licence du Canada. Le fonctionnement doit suivre les
deux conditions suivantes : (1) Cet appareil ne doit pas provoquer d’interférences, et (2) cet appareil ne doit accepter aucune interférence, y compris des interférences
qui pourraient provoquer un fonctionnement indésirable. Les modifications qui n’ont pas été expressément approuvées par Lutron Electronics Co., Inc. peuvent
annuler le pouvoir de l’utilisateur d’utiliser cet équipement.
REMARQUE : Cet équipement a été testé et est conforme aux limites d’un appareil numérique de Classe B en vertu de la partie 15 des règles de la FCC. Ces limites
sont conçues pour fournir une protection raisonnable face aux interférences nuisibles dans une installation résidentielle. Cet équipement génère, utilise et peut émettre
une énergie de fréquence radio et, s’il n’est pas installé et utilisé conformément aux instructions, il peut provoquer des interférences nuisibles aux communications
radio. Cependant, il n’y a aucune garantie que des interférences ne surviendront dans une installation particulière. Si cet équipement provoque des interférences
nuisibles pour la réception radio et télévisuelle, ce qui peut être déterminé en allumant et en éteignant l’équipement, il est recommandé que l’utilisateur tente de
corriger ces interférences en utilisant une ou plusieurs des mesures suivantes :
Réorientez ou repositionnez l’antenne réceptrice.
Augmentez la séparation entre l’équipement et le récepteur.
Connectez l’équipement à une prise électrique se trouvant sur un circuit différent de celui où le récepteur est connecté.
Définir un niveau de luminosité favori
(optionnel)
Pour les commandes sans fil Pico® avec un bouton
Favoris.
Commandes de luminaires
PowPak® : Programmation
Appartient à la famille Energi TriPak®
A
Réglez les lumières au
niveau souhaité :
Utilisez le bouton
Monter « » ou le bouton
Baisser « » sur la
commande sans fil Pico®.
041485
Rév. A
04/2015
B
Enregistrez le niveau favori :
Appuyez et maintenez le
bouton Favoris enfoncé
pendant 6 secondes
La charge clignotera 3 fois
pour confirmer la sauvegarde
du niveau favori.
Garantie limitée :
http://www.lutron.com/TechnicalDocumentLibrary/369-119_Wallbox_Warranty.pdf
Réglage du seuil bas
A
Activer le mode d’ajustement du réglage du seuil bas :
Appuyez et maintenez le bouton Baisser « » enfoncé sur la commande de
luminaire pendant 12 secondes.
Les lumières clignoteront à leur niveau et la DEL d'état de la charge commencera
à clignoter.
B
Ajuster le réglage du seuil bas :
Utilisez le bouton Monter «
» et le bouton Baisser «
» sur la commande de
luminaire pour régler les lumières au niveau de réglage du seuil bas souhaité
(de 1à 45 %).
C
Enregistrer le réglage du seuil bas :
Appuyez et maintenez le bouton de Alterner
«
»
enfoncé pendant 6secondes
pour enregistrer le réglage.
La DEL d'état de la charge commencera à clignoter puis restera allumée pour
indiquer que le nouveau niveau a été enregistré.
Réglage du seuil haut
A
Activer le mode de réglage du seuil haut :
Appuyez et maintenez le bouton Monter « » enfoncé sur la commande de
luminaire pendant 12 secondes.
Les lumières clignoteront à leur niveau et la DEL d'état de la charge commencera
à clignoter.
B
Ajuster le réglage du seuil haut :
Utilisez le bouton Monter « » et le bouton Baisser « » sur la commande de luminaire
pour régler les lumières au niveau de réglage du seuil haut souhaité (de 55à 100 %).
C
Enregistrer le réglage du seuil haut :
Appuyez et maintenez le bouton de Alterner
«
»
enfoncé pendant 6secondes
pour enregistrer le réglage.
La DEL d'état de la charge commencera à clignoter puis restera allumée pour
indiquer que le nouveau niveau a été enregistré.
Ajuster le réglage du seuil bas et le réglage du seuil haut
(optionnel)
Pour de meilleurs résultats, minimisez la quantité de lumière du soleil pénétrant
dans la pièce avant de réaliser les procédures suivantes.
Selon le fabricant de l’applique ou de la charge, il peut être nécessaire d'ajuster
les seuils haut et bas.
Réglez le seuil bas pour assurer un niveau de lumière stable car certaines
charges peuvent clignoter ou s’éteindre si le réglage est trop bas.
Vérifiez que vous pouvez régler les lumières au niveau du seuil bas sans
fonctionnement anormal.
Le réglage d’usine du seuil haut convient à la plupart des applications mais peut
être réglé comme vous le souhaitez.
1
Dépannage www.lutron.com
Symptôme Solution
Les ballasts / pilotes
ne peuvent pas être
commandés localement
depuis la commande de
luminaire.
Vérifiez que le(s) disjoncteur(s) de la commande de luminaire sont sous tension.
Vérifiez que le conducteur commuté de la commande de luminaire est raccordé au ballast / pilote (FCJ-010).
Vérifiez que les lignes de commande (FCJ-010 : violet/gris, FCJ-ECO: violet/violet) de la commande
de luminaire sont raccordées au ballast / pilote
Si vous utilisez le FCJ-010, vérifiez que le ballast / pilote est de 0–10 V.
Si vous utilisez le FCJ-ECO, utilisez le ballast / pilote EcoSystemR de LutronR.
Restaurer les réglages d'usine.
Les lumières ne se
tamisent ou ne s'allument
pas comme prévu.
Vérifiez que les lignes de commande sont raccordées correctement (FCJ-010 : violet/gris sensibles
à la polarité, FCJ-ECO : violet/violet)
Vérifiez que les fils sont raccordés entre le détecteur de luminaire et la commande de luminaire.
FCJ-010 seulement : Assurez-vous que le luminaire de 0–10 V- est au seuil bas (à 0 V), pas éteint (à 0 V).
S'il est éteint (à 0 V), réglez le seuil bas.
FCJ-010 seulement : Vérifiez que le luminaire ne nécessite pas un signal inversé (commande de 10 0 V-).
FCJ-010 seulement : Vérifiez que la tension entre les fils gris et violet se situe entre 0 et 10 V-.
FCJ-ECO seulement : Déconnectez les fils violet / violet de la commande de luminaire. Vérifiez que
les lumières vont à 100 %.
FCJ-010 seulement : Déconnectez les fils violet / gris de la commande de luminaire. Vérifiez que les
lumières vont à 100 %. Court-circuitez les fils violet / gris sur le ballast / pilote, vérifiez que les lumières
se règlent à leur seuil bas.
Les lumières ne
répondent pas au(x)
transmetteur(s) sans fil.
Vérifiez que le(s) disjoncteur(s) de la commande de luminaire et les ballasts / pilotes sont sous tension.
Vérifiez que les transmetteurs sans fil sont associés à la commande de luminaire.
Restaurer les réglages d'usine.
Les transmetteurs sans
fil ne peuvent pas être
associés à la commande
de luminaire.
Le nombre maximal de transmetteurs sans fil a été associé à la commande de luminaire. Pour
supprimer un transmetteur sans fil précédemment configuré, appuyez trois fois sur n’importe
quel bouton du transmetteur sans fil ; à la troisième pression, maintenez-le enfoncé pendant trois
secondes, puis appuyez trois fois de nouveau.
La portée des
radiofréquences entre
les commandes sans fil
est réduite en-dessous
de 9 m (30 pi).
Réduisez et organisez le câblage du ballast/pilote au maximum pour éviter l’enchevêtrement des
longueurs de fil excessives.
Veuillez à ce que les premiers 20-30 cm (7-12 po) de fils sortant de l’entrée à perforer de la commande
de luminaire soit séparés autant que possible des fils des ballasts/pilotes/lampes environnants.
Contactez l’assistance technique de LutronR pour plus d’assistance.
Les lumières sont
instables à leur seuil bas.
Ajustez le réglage du seuil bas.
Le détecteur de luminaire
n’allume pas les
lumières.
Vérifiez que les fils du détecteur de luminaire sont raccordés à la commande de luminaire.
Le FC-VSENSOR est en mode d’inoccupation seulement (il n’allume pas les lumières).
L’adresse du FCJ-ECO
est introuvable.
Tous les pilotes/ballasts connectés à un FCJ-ECO fonctionnent comme une zone unique. Si plus
d’une zone est requise, utilisez un RMJ-ECO32-DV-B.
Pour plus d’informations sur le détecteur de luminaire PowPakR, consultez les documents 369866 ou 048556 sur
www.lutron.com
Pour le guide d’installation du FC-SENSOR et du FC-VSENSOR, consultez www.lutron.com
Assistance technique | 1.800.523.9466 É.-U., Canada, et les Caraïbes | +44.(0)20.7702.0657 Europe | +1.610.282.3800 Autres | www.lutron.com
2
Commencez ici
REMARQUE : Seuils hauts et seuils
bas peuvent également être effectués
pour une seule unité ou groupe d’unités
simultanément avec une commande sans
fil PicoR. Pour plus d’informations, voir le
document 048556 sur www.lutron.com

Transcripción de documentos

PowPak Fixture Controls Installation ® Required Components Technical Assistance | 1.800.523.9466 USA, Canada, and the Caribbean | +44.(0)20.7702.0657 Europe | +1.610.282.3800 Others | www.lutron.com For each fixture, you will need: FCJ-010: At least one 0 – 10 V Fluorescent Ballast or LED Driver FCJ-ECO: At least one Lutron® EcoSystem® Ballast or LED Driver At least one of these transmitters (22 total allowed) One Fixture Control Part of the Energi TriPak® Family 041485 Rev. A 04/2015 Please read before installing. FCJ-010 0–10 V- 120 – 277 V~ 50 / 60 Hz 1 A switching 6 mA sink/source FCJ-ECO Lutron® EcoSystem® 120 – 277 V~ 50 / 60 Hz 1A switching 14 V- 6 mA PIR Lens Laser Detection Daylight Lens Raise Load Status LED Toggle + Lower PowPakR Fixture Sensor (FC-SENSOR or FC-VSENSOR) PowPakR Wireless Fixture Control (FCJ-010 or FCJ-ECO) UL 2043 Plenum Rated Controls up to 3 ballasts or drivers (IEC 60929 Annex E.2 requires each ballast or driver to limit the sink/source current draw to 2.0 mA maximum). Provides IEC SELV / NECR Class 2, 12 V-, 25 mA to a PowPakR fixture sensor (FC-SENSOR or FC-VSENSOR). • • • • • • • 2. Only one fixture control can be used per fixture sensor, and only one fixture sensor can be used per fixture control. Important Notes: For installation by a qualified electrician in accordance with all local and national electrical codes. Use copper conductors only. Check to see that the device type and rating is suitable for the application. DO NOT install if product has any visible damage. If moisture or condensation is evident, allow the product to dry completely before installation. Operate between 32 °F and 104 °F (0 °C and 40 °C), ambient. 0% to 90% humidity, non-condensing. For indoor use only. Consult the fixture installation guide for fixture wiring. + Radio Powr SavrT Occupancy/Vacancy Sensor Radio Powr SavrT Daylight Sensor (1 maximum) PicoR Wireless Control (10 maximum) (10 maximum) (1 maximum) PowPak® Wireless Fixture Control • Notes: 1. Fixture control can be used without a fixture sensor as long as at least one Radio Powr SavrT sensor or PicoR wireless control is used. 6 mA maximum for the control lines. Switches up to 1 A total (or maximum 3 ballasts or drivers). May be pre-installed in fixture. Start Here 1 Associate Transmitters to Fixture Control Install Fixture Control and Optional Fixture Sensor 2 Suggested Installation Location: Close to the Fixture / Troffer. Before beginning this step, make sure that there are no other fixture controls being set up in the building which are currently in association mode. It is possible that wireless transmitters from other systems can be incorrectly associated to this module. A Initiate association mode on the fixture control by shining a green laser pointer (by others) at the laser detection hole on the sensor until the load attached to the control module starts flashing (every 2 seconds). Alternatively, press and hold the Toggle button “ ” for 6 seconds on the fixture control to initiate association mode. WARNING! Shock Hazard. May result in serious injury or death. Turn off power at circuit breaker before installing the unit. The fixture control can be installed on a fixture/troffer, junction box or marshalling box using the conduit nut (provided) or with mounting screws (not provided). Please consult local and national electric codes for proper installation. A Ideally, mount the sensor to the ceiling tile close to the fixture using the wireform or using the adhesive strip (included). The two communication wires from the sensor attach to the fixture control stab-in connectors. The wires are interchangeable to eliminate miswiring. B Once installed, energize the control module. The fixture will turn on.  Note: Multiple fixture controls can be placed into association mode by repeating one of the two above methods for the next fixture control prior to moving to Step 2B. Hot (Black) Laser Detection Neutral Hot (Black) HOT Ballast / Driver Fixture/Troffer or Junction Box + – Gray (FCJ-010) / Violet (FCJ-ECO) – Class 2 + Violet (both FCJ-010 and FCJ-ECO) Sensor 30 ft (9 m) maximum NEU Switched Hot (Red) PowPakR Fixture Control Install the fixture control directly to a fixture or on a junction box nearest to the fixture. Install the sensor on the ceiling near the fixture to optimize coverage in the desired area. Fixture Earth Neutral (White) Neutral OR MAINS English Green/Yellow 1/2 in (21 mm) Knockout Opening Conduit Nut + Green laser specifications: • Wave output: constant • Wavelength: 532 nm • Output power: 5 mW – Note: The fixture control will automatically exit association mode 10 minutes after the last activity. Fixture Control Pico® wireless control Important Note: To optimize RF performance of the product: – Keep the lamp wiring as short as possible to reduce the radiation from the lamp wires. – Keep the lamp wiring as far as possible from the PowPakR Wireless Fixture Control mounting location. See the Troubleshooting section for more details. Wireless sensors and controls must be located within 60 ft (18 m) line of sight, or 30 ft (9 m), through walls, of the associated control module. B Hold the indicated button on each transmitter for 6 seconds. The fixture will flash to show that wireless transmitters have been associated. Alternatively, for Radio Powr SavrT occupancy/vacancy and daylight sensors, the green laser pointer can be used. See Application Note #407 on www.lutron.com for more information. To associate another transmitter, repeat steps 2A and 2B. PowPakR Fixture Control Wiring Default Functionality PowPakR Fixture Control Knockout From back of sensor Link Test Maximize Distance Wireless Controls: All lights Lamp Wiring On: 100% ; Favorite: 50%; Off: 0% Fixture Controls Auto On level: FC-SENSOR only (not applicable for FC-VSENSOR) Varies with ambient light level when occupancy is triggered (e.g., 100% for a dark room, 10% for a bright room). Timeout period: 15 minutes For more information, see www.lutron.com/TechnicalDocumentLibrary/369866.pdf Lutron Electronics Co., Inc. 7200 Suter Road Coopersburg, PA 18036-1299 USA Notes: 1. Control wires (Violet/Gray for FCJ-010 or Violet/Violet for FCJ-ECO) can be run as either Class 1 or Class 2. 2. If hanging pendant fixtures the maximum wire length between fixture sensor and fixture control is 12 ft (3.7 m). Sensor should be mounted no more than 2 ft (0.6 m) from the fixture. 3. To install unit inside a junction box, please see Application Note 423 on www.lutron.com 4. The fixture control needs to be accessible for some programming steps. Record where it is mounted so that it can be easily located later. 5. When using a Radio Powr SavrT daylight sensor in conjunction with both a PowPakR wireless fixture control and PowPakR fixture sensor, the Radio Powr SavrT daylight sensor will provide the daylighting input to the control module, and the PowPakR fixture sensor daylighting input will be ignored. 6. When using a Radio Powr SavrT occupancy sensor in conjunction with both a PowPakR wireless fixture control and PowPakR fixture sensor, occupancy data from both sensors is used; either one detecting occupancy will turn the lights on, and the lights turn off only when both sensors have gone vacant (no longer detect occupancy). 7. For more information on the PowPakR fixture sensor, see: Document 369866 or 048556 on www.lutron.com For FC-SENSOR and FC-VSENSOR installation guide visit www.lutron.com PowPak Fixture Controls Programming Technical Assistance | 1.800.523.9466 USA, Canada, and the Caribbean | +44.(0)20.7702.0657 Europe | +1.610.282.3800 Others | www.lutron.com ® 2 Set Low-End Trim and High-End Trim (Optional) For best results, minimize the amount of sunlight entering the room before performing the following procedures. Part of the Energi TriPak® Family 041485 Rev. A 04/2015 Depending on the fixture manufacturer or load, low-end trim and high-end trim may need to be adjusted. • Trim low-end to ensure a stable light level because some loads will flicker or drop out if trimmed too low. • Be sure that you can turn on the lights to the low-end trim level without any abnormal operation. • The factory default high-end trim is suitable for most applications but can be adjusted as desired. ALL PROGRAMMING IS OPTIONAL Programming is not required for default functionality • Set a favorite light level • Set high-end and low-end trim for all fixtures Reset Factory Defaults Note: In some instances, it may be necessary to reset the fixture controls and connected devices back to factory default settings. Before beginning, make sure that all devices are connected and powered. A Rapidly tap the Toggle button “ ” on the fixture control three times and hold on the fourth until the LED begins to flash slowly; release button. B Within 3 seconds of the start of flashing, again rapidly tap the Toggle button “ ” three times and the LEDs will flash rapidly indicating that the unit has been reset to factory defaults. Note: Any associations or programming previously set up with the fixture control will be erased and will need to be re‑programmed. Start Here 1 Set a Favorite Light Level (Optional) For Pico® wireless controls with a Favorite Button. A Adjust lights to desired level: Use the Raise button “ ” or Lower button “ ” on the Pico® wireless control. Raise B Save favorite level: Press and hold the Favorite Favorite button for 6 seconds. The load will flash 3 times to confirm that the Favorite level is saved. Lower NOTE: High-end and low-end trim can also be performed for a single unit or group of units simultaneously with a PicoR wireless control. For more information see document 048556 on www.lutron.com. Troubleshooting Symptom www.lutron.com Solution Ballasts / drivers cannot • Ensure that the breaker(s) to the fixture control are energized. be controlled locally from • Ensure that the fixture control switched hot lead is wired to the ballast / driver (FCJ-010). the fixture control. • Ensure that the fixture control control lines (FCJ-010: violet/gray, FCJ-ECO: violet/violet) are wired to the ballast / driver. • If using FCJ-010, verify the driver/ballast is 0–10 V. If using FCJ-ECO, use the LutronR EcoSystemR driver/ballast. Lights do not dim or turn • ON as expected. • • • • • • Reset to factory defaults. Ensure that control lines are wired properly (FCJ-010: violet/gray-polarity-sensitive, FCJ-ECO: violet/violet) Ensure that the wires are connected between the fixture sensor and the fixture control. FCJ-010 only: Make sure that 0–10 V- fixture is at low-end (at 0 V), not OFF (at 0 V). If OFF (at 0 V), adjust low-end trim. FCJ-010 only: Ensure that fixture does not require an inverted signal (10 – 0 V- control). FCJ-010 only: Verify that the voltage across the gray and violet wires is between 0 and 10 V-. FCJ-ECO only: Disconnect the violet / violet wires from the fixture control. Verify that the lights go to 100%. FCJ-010 only: Disconnect the violet / gray wires from the fixture control. Verify that the lights go to 100%. Short the violet / gray wires on the ballast / driver, verify that the lights go to low-end. Lights do not respond to • Ensure that the breaker(s) to the fixture control and ballasts / drivers are energized. wireless transmitter(s). • Ensure that wireless transmitters are associated to the fixture control. Reset to factory defaults. Wireless transmitter(s) • The maximum number of wireless transmitters have been associated to the fixture control. To cannot be associated to remove a previously set up wireless transmitter, tap any button on the wireless transmitter three the fixture control. times; on the third tap, hold for three seconds and then tap three more times. Low-End Trim A Enter low-end trim adjustment mode: Press and hold the Lower button “ ” on the fixture control for 12 seconds. The lights will flash and the load status LED will begin flashing. B Adjust the low-end trim: Use the Raise button “ ” and Lower button “ ” on the fixture control to adjust and set the lights to the desired low-end (1 to 45%). C Save the low-end trim: Press and hold the Toggle button “ ” for 6 seconds to save setting. The load status LED will begin flashing and then turn solid to indicate new level has been saved. High-End Trim A Enter high-end trim adjustment mode: Press and hold the Raise button “ ” on the fixture control for 12 seconds. The lights will flash and the load status LED will flash. B Adjust the high-end trim: Use the Raise button “ ” and Lower button “ ” on the fixture control to adjust and set the lights to the desired high-end (55 to 100%). C Save the high-end trim: Press and hold the Toggle button “ ” for 6 seconds to save setting. The load status LED will begin flashing and then turn solid to indicate new level has been saved. )Lutron, Lutron, Pico, PowPak, EcoSystem, and Energi TriPak are registered trademarks and Radio Powr Savr is a trademark of Lutron Electronics Co., Inc. NEC is a registered trademark of the National Fire Protection Association, Quincy, Massachusetts. ©2014 – 2015 Lutron Electronics Co., Inc. RF range between wireless controls is diminished below 30 ft (9 m). • Keep the ballast/driver wiring as short as possible and well organized to avoid excess wire being bunched up. • Keep the first 7-12 in (20-30 cm) of the wires coming out of the fixture control knockout separated as much as possible from any nearby ballast/driver/lamp wires. • Contact LutronR technical support for further assistance. Lights are unstable at low‑end. • Adjust low-end trim. Fixture sensor does not • Check that fixture sensor wires are connected to fixture control. turn the lights ON. • FC-VSENSOR is vacancy only (it will not turn the lights on). FCJ-ECO cannot be • All drivers/ballasts connected to an FCJ-ECO function as a single zone. If more than one zone is addressed. required, use RMJ-ECO32-DV-B. For more information on the PowPakR fixture sensor, see Document 369866 or 048556 on www.lutron.com For FC-SENSOR and FC-VSENSOR installation guide visit www.lutron.com Limited Warranty: http://www.lutron.com/TechnicalDocumentLibrary/369-119_Wallbox_Warranty.pdf FCC Information This device complies with part 15 of the FCC Rules and Industry Canada license-exempt RSS standard(s). Operation is subject to the following two conditions: (1) This device may not cause interference, and (2) this device must accept any interference, including interference that may cause undesired operation. Modifications not expressly approved by Lutron Electronics Co., Inc. could void the user’s authority to operate this equipment. NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: • Re-orient or relocate the receiving antenna. • Increase the separation between the equipment and receiver. • Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. Lutron Electronics Co., Inc. 7200 Suter Road Coopersburg, PA 18036-1299 USA Módulo de Atenuación PowPak Instalación ® Componentes requeridos Asistencia técnica | 1.800.523.9466 E.U.A., Canadá y el Caribe | +44.(0)20.7702.0657 Europa | +1.610.282.3800 Demás países | www.lutron.com Para cada artefacto, se necesitará: FCJ-010: Al menos un balasto fluorescente o controlador de LED de 0 – 0 V FCJ-ECO: Al menos un balasto o controlador de LED Lutron® EcoSystem® Al menos uno de estos transmisores (permitidos 22 en total) Un control de artefactos Parte de la familia Energi TriPak® 041485 Rev. A 04/2015 Por favor lea antes de instalar. FCJ-010 0–10 V- Conmutación de 120 – 277 V~ 50/60 Hz 1 A Fuente/drenaje de 6 mA FCJ-ECO Lutron® EcoSystem® Conmutación de 120 – 277 V~ 50/60 Hz 1 A 14 V- 6 mA Lente PIR Detección Lente de luz de láser diurna Subir LED de estado de la carga Encender y Apagar + Bajar Sensor de artefactos PowPakR (FC-SENSOR o FC-VSENSOR) Control inalámbrico de artefactos PowPakR (FCJ-010 o FCJ-ECO) (1 máximo) Control inalámbrico de artefactos PowPak® Homologado UL 2043 para plenum Controla hasta tres balastos o controladores (la norma IEC 60929 anexo E.2 requiere que cada balasto o controlador limite la corriente de fuente/drenaje a 2,0 mA como máximo). Suministra 12 V- , 25 mA IEC SELV/NECR Clase 2 a un sensor de artefactos PowPakR (FC-SENSOR o FC-VSENSOR). Notas importantes: • Para ser instalados por un electricista calificado de acuerdo con todas las normativas eléctricas locales y nacionales. • Sólo utilice conductores de cobre. • Verifique que el tipo de dispositivo y la certificación sean adecuados para la aplicación. • NO instale este producto si tuviera algún daño visible. • Si hubiera señales evidentes de humedad o condensación, permita que el producto se seque por completo antes de la instalación. • Opérelo entre 0 °C y 40 °C (32 °F y 104 °F) de temperatura ambiente. • 0 a 90% de humedad, sin condensación. • Sólo para uso bajo techo. Notas: Para informarse del cableado de los artefactos consulte la guía de instalación de artefactos. 1. El control de artefactos puede utilizarse sin un sensor de artefactos siempre y cuando se utilice al menos un sensor Radio Powr SavrT o un control inalámbrico PicoR. . 2. Sólo puede utilizarse un control de artefactos por sensor de artefactos, y sólo puede utilizarse un sensor de artefactos por control de artefactos. + Sensor de ocupación/ Sensor de luz vacancia Radio Powr SavrT diurna Radio Powr (10 máximo) SavrT Control inalámbrico PicoR (10 máximo) (1 máximo) 6 mA máximo para las líneas de control. Conmuta hasta 1 A en total (o un máximo de tres balastos o controladores). Puede ser preinstalado en el artefacto. Comience aquí 1 Asocie los transmisores al control de artefactos Instale el control de artefactos y el sensor de artefactos opcional 2 Ubicación de instalación sugerida: Cercana a un artefacto/luminaria. Antes de comenzar este paso, asegúrese de que no haya otros controles de artefactos que estén siendo configurados en el edificio y que se encuentren actualmente en el modo de asociación. Es posible que los transmisores inalámbricos de otros sistemas puedan estar asociados incorrectamente a este módulo. A Inicie el modo de asociación en el control de artefactos haciendo brillar un puntero láser verde (de terceros) en el orificio de detección láser del sensor hasta que la carga conectada al módulo de control comience a destellar (cada 2 segundos). Alternativamente, pulse y mantenga pulsado el botón Encender y Apagar “ ” durante 6 segundos en el control de artefactos para iniciar el modo de asociación. ¡ADVERTENCIA! Peligro de descarga eléctrica. Podría ocasionar lesiones graves o la muerte.Antes de instalar el equipo desconecte el suministro eléctrico en el disyuntor. El control del artefactos puede instalarse en un artefacto/luminaria, caja de conexiones o caja organizadora utilizando la tuerca de conducto (suministrada) o con tornillos de montaje (no suministrados). Para obtener una instalación adecuada consulte las normativas eléctricas locales y nacionales. A Idealmente, monte el sensor a la placa de techo cerca del artefacto utilizando el gancho de montaje o la cinta adhesiva (incluidos). Los dos cables de comunicación del sensor se conectan a los conectores de cuchilla del control de artefactos. Los cables son intercambiables para eliminar los defectos de cableado. B Una vez instalado, energice el módulo de control. Este artefacto se encenderá.  Nota: Pueden ponerse varios controles de artefactos en el modo de asociación repitiendo uno de los dos métodos anteriores para el próximo control de artefactos antes de continuar al Paso 2B. Hot (Black) Detección de láser Vivo (negro) Neutral Control de artefactos PowPakR HOT Artefacto/ Luminaria o caja de conexiones + – Gris (FCJ-010) / Violeta (FCJ-ECO) – Abertura con tapa ciega de 21 mm (1/2 pulg) Tuerca del conducto + Especificaciones del láser verde: • Salida de onda: constante • Longitud de onda: 532 nm • Potencia de salida: 5 mW – Nota: El control de artefactos saldrá automáticamente del modo de asociación 10 minutos después de la última actividad. Control de artefactos Nota importante: Para optimizar el desempeño de RF del producto: – Mantenga el cableado de la lámpara lo más corto posible para reducir la radiación de los cables. – Mantenga el cableado de las lámparas lo más alejado posible de la ubicación de montaje del control inalámbrico de artefactos PowPakR. Para obtener más detalles consulte la sección de Solución de Problemas. Control inalámbrico Pico® Los sensores y controles inalámbricos deben estar situados a menos de 18 m (60 pies) con línea de visión directa, o 9 m (30 pies) a través de paredes, del módulo de control asociado. O Balasto/Controlador + Violeta (tanto FCJ-010 como FCJ-ECO) Sensor 9 m (30 pies) como máximo NEU Conmutado vivo (rojo) Class 2 Instale el control de artefactos directamente en un artefacto o en la caja de conexiones más cercana al artefacto. Instale el sensor en el cielorraso cerca del artefacto para optimizar la cobertura en el área deseada. Tierra del artefacto Neutro (blanco) Neutro MAINS Español Verde/Amarillo B Mantenga pulsado el botón indicado en cada transmisor durante 6 segundos. El artefacto destellará para mostrar que los transmisores inalámbricos han sido asociados. Alternativamente, para los sensores de ocupación/vacancia y luz diurna Radio Powr SavrT, puede utilizarse el puntero láser verde. Para obtener más información consulte la Nota de aplicación Nº 407 en www.lutron.com. Para asociar otro transmisor, repita los pasos 2A y 2B. Cableado del control de artefactos PowPakR Funcionalidad predeterminada Controles inalámbricos: Todas las luces Desde la parte trasera del sensor Tapa ciega del control de artefactos PowPakR Link Test Maximice la distancia Cableado de la lámpara Encendida: 100%; Favorito: 50%; Apagada: 0% Controles de artefactos Nivel Automático Activado: FC-SENSOR únicamente (no aplicable para FC-VSENSOR) Varía con el nivel de luz ambiental cuando se dispara la ocupación (p. ej., 100% para una habitación oscura, 10% para una habitación iluminada). Intervalo de espera: 15 minutos Para obtener información adicional, consulte www.lutron.com/TechnicalDocumentLibrary/369866.pdf Lutron Electronics Co., Inc.7200 Suter Road Coopersburg, PA 18036-1299 E.U.A. Notas: 1. Los cables de control (violeta/gris para el FCJ-010 o violeta/violeta para el FCJ-ECO) pueden ser tendidos como Clase 1 o Clase 2. 2. Con artefactos colgantes la máxima longitud de cable entre el sensor de artefactos y el control de artefactos es de 3,7 m (12 pies). El sensor deberá ser montado a no más de 0,6 m (2 pies) del artefacto. 3. Para instalar el equipo en el interior de una caja de conexiones, consulte la Nota de aplicación 423 en www.lutron.com 4. El control de artefactos tiene que ser accesible para algunos pasos de programación. Registre dónde está montado para que pueda ubicarlo fácilmente más adelante. 5. Cuando se utilice un sensor de luz diurna Radio Powr SavrT en conjunto con tanto un control inalámbrico de artefactos PowPakR y un sensor de artefactos PowPakR, el sensor de luz diurna Radio Powr SavrT proporcionará la entrada de iluminación diurna al módulo de control, y la entrada de luz diurna del sensor de artefactos PowPakR será ignorada. 6. Cuando se utilice un sensor de ocupación Radio Powr SavrT en conjunto tanto con un control inalámbrico de artefactos PowPakR como con un sensor de artefactos PowPakR, se utilizan los datos ocupación de ambos sensores; cualquiera de ellos que detecte una ocupación encenderá las luces, y éstas sólo se apagarán cuando ambos sensores pasen al modo de vacancia (ya no detectan ocupación). 7. Para obtener más información sobre el sensor de artefactos PowPakR consulte: Documentos 369866 o 048556 en www.lutron.com Para obtener la guía de instalación del FC-SENSOR y FC-VSENSOR visite www.lutron.com Módulo de Atenuación PowPak Programación Asistencia técnica | 1.800.523.9466 E.U.A., Canadá y el Caribe | +44.(0)20.7702.0657 Europa | +1.610.282.3800 Demás países | www.lutron.com ® 041485 Rev. A 04/2015 TODA LA PROGRAMACIÓN ES OPCIONAL Para la funcionalidad predeterminada no se requiere programación • Configure un nivel de luz favorito • Configure el ajuste del intensidad mínima y el intensidad máxima para todos los artefactos  establezca los valores R predeterminados de fábrica Nota: En algunos casos puede ser necesario restablecer la configuración predeterminada de fábrica tanto de los controles de artefactos como de los dispositivos conectados. Antes de comenzar, asegúrese de que todos los dispositivos estén conectados y energizados. A Pulse rápidamente tres veces el botón Encender y Apagar “ ” en el control de artefactos y manténgalo pulsado la cuarta vez hasta que el LED comience a destellar lentamente; suelte el botón. B Dentro de los 3 segundos del comienzo del destello, pulse de nuevo rápidamente tres veces el botón Encender y Apagar “ ” y los LED destellarán rápidamente, indicando que el equipo ha sido restablecido a los valores predeterminados de fábrica. Nota: Toda asociación o programación establecida con anterioridad para el control de artefactos será borrada y tendrá que ser reprogramada. Comience aquí Configure un nivel de luz favorito (opcional) Para los controles inalámbricos Pico® con un botón Favorito. A Ajuste las luces al nivel deseado: Utilice el botón Subir “ ” o el botón Bajar “ ” del control inalámbrico Pico®. Configure el ajuste de las intensidades mínima y máxima (opcional) Solución de Problemas Para obtener los mejores resultados, minimice la cantidad de luz solar que ingresa a la habitación antes de realizar los siguientes procedimientos. Parte de la familia Energi TriPak® 1 2 Subir B Guarde el nivel favorito: Pulse y mantenga pulsado el Favorito botón Favorito durante 6 segundos. La carga destellará tres veces para confirmar que el nivel favorito ha sido guardado. Bajar En función del fabricante del artefacto o de la carga, podría ser necesario ajustar las intensidades máxima y mínima. • Ajuste el intensidad mínima para asegurar un nivel estable de luz porque algunas cargas parpadearán o caerán si se las ajusta demasiado bajas. • Asegúrese de que se pueda encender las luces al nivel de ajuste de intensidad mínima sin tener que ejecutar ninguna operación anormal. • El ajuste de intensidad máxima predeterminado de fábrica es adecuado para la mayoría de las aplicaciones, pero puede ajustarse como se desee. NOTA: El ajuste de intensidad mínima e intensidad máxima también se puede realizar para una sola unidad o grupo de unidades simultáneamente con un control inalámbrico PicoR. Para obtener más información, consulte el documento 048556 en www.lutron.com. Síntoma www.lutron.com Solución Los balastos/ controladores no pueden ser controlados localmente desde el control de artefactos. • Asegúrese de que los disyuntores al control de artefactos estén energizados. • Asegúrese de que el cable conmutado en caliente del control de artefactos esté conectado al balasto/controlador (FCJ-010). • Asegúrese de que las líneas de control del control de artefactos (FCJ-010: violeta/gris, FCJ-ECO: violeta/violeta) se conecten al balasto/controlador. • Si se utiliza el FCJ-010, verifique que el controlador/balasto sea de 0 – 10 V. Si se utiliza FCJ-ECO, emplee el controlador/balasto LutronR EcoSystemR. Restablezca los valores predeterminados de fábrica. Las luces no se atenúan • Asegúrese de que las líneas de control estén cableadas correctamente (FCJ-010: violeta/gris o ENCIENDEN como se sensible a la polaridad, FCJ-ECO: violeta/violeta) esperaba. • Asegúrese de que los cables estén conectados entre el sensor de artefactos y el control de artefactos. • Sólo FCJ-010: Asegúrese de que el artefacto de 0 – 10 V- esté en la intensidad mínima (a 0 V), y no APAGADO (a 0 V). Si está APAGADO (a 0 V), ajuste la intensidad mínima. • Sólo FCJ-010: Asegúrese de que el artefacto no requiera una señal invertida (control de 10 – 0 V-). • Sólo FCJ-010: Verifique que el voltaje entre los cables gris y violeta esté entre 0 y 10 V-. • FCJ-ECO únicamente: Desconecte los cables violeta/violeta del control de artefactos. Verifique que las luces pasen al 100%. • Sólo FCJ-010: Desconecte los cables violeta/gris del control de artefactos. Verifique que las luces pasen al 100%. Cortocircuite los cables violeta/gris en el balasto/controlador, y verifique que las luces pasen a la intensidad mínima. Las luces no responden • Asegúrese de que los disyuntores al control de artefactos y a los balastos/controladores estén a los transmisores energizados. inalámbricos. • Asegúrese de que los transmisores inalámbricos estén asociados al control de artefactos. Restablezca los valores predeterminados de fábrica. Ajuste de la intensidad mínima A Ingrese al modo de ajuste de la intensidad mínima: Pulse y mantenga pulsado el botón Bajar “ ” del control de artefactos durante 12 segundos. Las luces destellarán y el LED del estado de la carga comenzará a destellar. B Ajuste la intensidad mínima: Utilice el botón Subir “ ” y el botón Bajar “ ” del control de artefactos para ajustar y configurar las luces al nivel de intensidad mínima deseado (1 a 45%). C Guarde el ajuste de la intensidad mínima: Pulse y mantenga pulsado el botón Encender y Apagar “ ” durante 6 segundos para guardar la configuración. El LED de estado de la carga comenzará a dwestellar y luego se iluminará continuamente para indicar que el nuevo nivel ha sido guardado. Ajuste de la intensidad máxima A Ingrese al modo de ajuste de la intensidad máxima: Pulse y mantenga pulsado el botón Subir “ ” del control de artefactos durante 12 segundos. Las luces destellarán y el LED del estado de la carga destellará. B Ajuste la intensidad máxima: Utilice el botón Subir “ ” y el botón Bajar “ ” del control de artefactos para ajustar y configurar las luces al nivel de intensidad máxima deseado (55 a 100%). C Guarde el ajuste de la intensidad máxima: Pulse y mantenga pulsado el botón Encender y Apagar “ ” durante 6 segundos para guardar la configuración. El LED de estado de la carga comenzará a destellar y luego se iluminará continuamente para indicar que el nuevo nivel ha sido guardado. )Lutron, Lutron, Pico, PowPak, EcoSystem y Energi TriPak son marcas comerciales registradas y Radio Powr Savr es una marca comercial de Lutron Electronics Co., Inc. NEC es una marca comercial registrada de la National Fire Protection Association, Quincy, Massachusetts. © 2014-2015 Lutron Electronics Co., Inc. Los transmisores • Ha sido asociado al control de artefactos el número máximo de transmisores inalámbricos. Para inalámbricos no pueden eliminar un transmisor inalámbrico previamente configurado, pulse tres veces cualquier botón del ser asociados al control transmisor inalámbrico; la tercera vez manténgalo pulsado durante tres segundos y luego púlselo de artefactos. tres veces más. El rango de RF entre los • Mantenga el cableado del balasto/controlador lo más corto posible y bien organizado para evitar controles inalámbricos que se apretuje el exceso de cables. está reducido por debajo • Mantenga las primeras 20-30 cm (7-12 pulg) separadas lo más posible de los cables provenientes de de los 9 m (30 pies). la tapa ciega del control de artefactos de cualquier cable de balasto/controlador/lámpara cercanos. • Para obtener asistencia adicional póngase en contacto con la asistencia técnica de LutronR. Las luces son inestables • Configure el ajuste de la intensidad mínima. a la intensidad mínima. El sensor de artefactos • Verifique que los cables del sensor de artefactos estén conectados al control del artefacto. no ENCIENDE las luces. • El FC-VSENSOR es de vacancia únicamente (no encenderá las luces). El FCJ-ECO no puede ser • Todos los controladores/balastos conectados a una función de FCJ-ECO como una zona única. gestionado. Si se requiriera más de una zona, utilice el RMJ-ECO32-DV-B. Para obtener más información sobre el sensor de artefactos PowPakR consulte: Documentos 369866 o 048556 en www.lutron.com Para obtener la guía de instalación del FC-SENSOR y FC-VSENSOR visite www.lutron.com Garantía limitada: http://www.lutron.com/TechnicalDocumentLibrary/369-119_Wallbox_Warranty.pdf Información de la FCC Este dispositivo satisface la parte 15 de las reglas de la FCC y las normas RSS de exención de licencia de Industry Canada. La operación está sujeta a las dos siguientes condiciones: (1) Este dispositivo no debe causar interferencias perjudiciales y (2) este dispositivo debe aceptar cualquier interferencia, incluida la interferencia que pudiera ocasionar una operación no deseada. Las modificaciones no aprobadas expresamente por Lutron Electronics Co., Inc. podrían invalidar la autorización del usuario para utilizar este equipo. NOTA: Este equipo ha sido comprobado y se lo encontró comprendido dentro de los límites para un dispositivo digital clase B, según la sección 15 de las reglas de la FCC. Estos límites están diseñados para proporcionar una protección razonable contra las interferencias perjudiciales en una instalación residencial. Este equipo genera, utiliza y puede irradiar energía de radiofrecuencia, y si no se lo instala y utiliza de acuerdo con las instrucciones podría ocasionar interferencias perjudiciales para las radiocomunicaciones. Sin embargo, no hay garantía de que no ocurran interferencias en una instalación en particular. Si este equipo ocasionara interferencias perjudiciales para la recepción de radio o televisión, lo que puede ser determinado encendiéndolo y apagándolo, se recomienda al usuario que intente corregir la interferencia adoptando una o más de las siguientes medidas: • Reorientar o reubicar la antena receptora. • Aumentar la separación entre el equipo y el receptor. • Conectar el equipo a un tomacorriente que corresponda a un circuito diferente de aquel al cual está conectado el receptor. Lutron Electronics Co., Inc. 7200 Suter Road Coopersburg, PA 18036-1299 E.U.A. Commandes de luminaires PowPak : Installation ® Composants requis Assistance technique | 1.800.523.9466 É.-U., Canada, et les Caraïbes | +44.(0)20.7702.0657 Europe | +1.610.282.3800 Autres | www.lutron.com Pour chaque luminaire, vous aurez besoin de : FCJ-010 : Au moins un ballast fluorescent ou un pilote de DEL de 0 – 10 V FCJ-ECO : Au moins un pilote de DEL ou ballast EcoSystem® de Lutron® Au moins un de ces transmetteurs (22 permis au total) Une commande de luminaire Appartient à la famille Energi TriPak® 041485 Rév. A 04/2015 Veuillez lire avant l'installation. FCJ-010 0–10 V- Commutation 120 – 277 V~ 50 / 60 Hz 1 A Courant de source/absorbé 6 mA FCJ-ECO EcoSystem® de Lutron® Commutation 120 – 277 V~ 50 / 60 Hz 1A 14 V- 6 mA Lentille PIR Détection Lentille de du laser lumière du jour Monter DEL d’état de la charge Alterner + Baisser Détecteur de luminaire PowPakR (FC-SENSOR ou FC-VSENSOR) Commande de luminaire sans fil PowPakR (FCJ-010 ou FCJ-ECO) Commande de luminaire PowPak® Commande jusqu'à 3 ballasts ou pilotes (la norme IEC 60929 Annexe E.2 exige que chaque ballast ou pilote limite le courant de source/absorbé à 2,0 mA au maximum). Fournit une alimentation IEC SELV / NECR de classe 2 de 12 V-, 25 mA à un détecteur de luminaire PowPakR (FC-SENSOR ou FC-VSENSOR). • • • • • • • Consultez le guide d'installation du luminaire pour le câblage du luminaire. 2. Une seule commande de luminaire peut être utilisée par détecteur de luminaire et un seul détecteur de luminaire peut être utilisé par commande de luminaire. + Détecteur d'occupation/ inoccupation Radio Powr SavrT (10 maximum) Détecteur de lumière du jour Radio Powr SavrT Commande sans fil PicoR (10 maximum) (1 maximum) (1 maximum) Conformité plénum de la norme UL 2043 • Remarques : 1. La commande de luminaire peut être utilisée sans détecteur de luminaire à condition qu'au moins un détecteur Radio Powr SavrT ou une commande sans fil PicoR est utilisé. Remarques importantes : À faire installer par un électricien qualifié conformément à tous les codes électriques en vigueur. N'utilisez que des conducteurs en cuivre. Veillez à ce que le type d'appareil et sa caractéristique nominale conviennent à l'application. Ne l'installez PAS si le produit présente des dommages visibles. Si de l'humidité ou de la condensation est apparente, laissez le produit sécher avant son installation. Fonctionne de 0 °C à 40 °C (32 °F à 104 °F), température ambiante. 0 à 90 % d’humidité, sans condensation. Utilisation à l'intérieur uniquement. 6 mA maximum pour les lignes de commande. Commute jusqu'à 1 A au total (ou 3 ballasts ou pilotes maximum). Peut être préinstallé dans un luminaire. Commencez ici 1 Associer des transmetteurs à la commande de luminaire Installer la commande de luminaire et le détecteur de luminaire optionnel 2 Emplacement recommandé pour l'installation : Près d'un luminaire / plafonnier. Avant d’entamer cette étape, veillez à ce qu’aucune autre commande de luminaire en phase de configuration dans le bâtiment ne soit actuellement en mode d’association. Les transmetteurs sans fil d'autres systèmes peuvent s’associer à ce module de façon incorrecte. A Démarrez le mode d’association sur la commande de luminaire en dirigeant un pointeur laser vert (d’un fabricant tiers) allumé sur le trou de détection de laser du détecteur jusqu’à ce que la charge liée au module de commande commence à clignoter (toutes les 2 secondes). AVERTISSEMENT ! Risque d'électrocution. Peut causer des blessures graves ou la mort. Coupez l'alimentation au niveau du disjoncteur avant d'installer l'unité. La commande de luminaire peut être installée sur un luminaire / plafonnier, dans un boîtier de raccordement ou un boîtier de regroupement avec l’écrou de conduit (fourni) ou des vis de montage (non fournies). Veuillez consulter les codes électriques en vigueur pour une installation correcte. A Si possible, montez le détecteur sur une dalle de plafond à proximité du luminaire au moyen du fil ou de la bande adhésive (inclus). Reliez les deux fils de communication du détecteur aux fiches de connexion de la commande de luminaire. Les fils sont interchangeables pour éviter un mauvais câblage. B Une fois installé, mettez le module de commande sous tension. Le luminaire s’allumera. De façon alternative, appuyez et maintenez le bouton de Alterner « la commande de luminaire pour démarrer le mode d’association.  Remarque : Plusieurs commandes de luminaires peuvent être placées en mode d’association en répétant l'une des deux méthodes ci-dessus pour la commande de luminaire suivante avant de passer à l’étape 2B. Hot (Black) Détection du laser Neutral Conducteur (Noir) Détecteur 9 m (30 pi) maximum NEU Conducteur commuté (Rouge) HOT OU Ballast / Pilote Luminaire / plafonnier ou boîtier de raccordement + Violet (FCJ-010 et FCJ-ECO) – Gris (FCJ-010) / Violet (FCJ-ECO) Commande de luminaire + – Class 2 Installez la commande de luminaire directement sur un luminaire ou un boîtier de raccordement près du luminaire. Installez le détecteur au plafond près du luminaire pour optimiser sa portée dans la zone souhaitée. Terre de l’applique Neutre (Blanc) Neutre MAINS Français Vert/Jaune Commande de luminaire PowPakR » enfoncé pendant 6 secondes sur Entrée à perforer de 21 mm (1/2 po) Écrou de conduit + Caractéristiques du laser vert : • Sortie d’onde : constante • Longueur d’onde : 532 nM • Puissance de sortie : 5 mW – Remarque : La commande de luminaire quitte automatiquement le mode d’association 10 minutes après la dernière activité. Remarque importante : Pour optimiser les performances de radiofréquences du produit : – Réduisez la longueur du câblage de la lampe au maximum pour réduire le rayonnement des fils de la lampe. – Gardez le câblage de la lampe aussi loin que possible de l’emplacement du montage de la commande de luminaire sans fil PowPakR. Voir la section Dépannage pour plus d’informations. Commande sans fil Pico® Les détecteurs sans fil et les commandes doivent se situer à moins de 18 m (60 pi) en ligne directe du module de commande associé ou à moins de 9 m (30 pi) à travers les murs. B Maintenez le bouton indiqué enfoncé sur chaque transmetteur pendant 6 secondes. Le luminaire clignotera indiquant que les transmetteurs sans fil ont été associés. De façon alternative, pour les détecteurs d’occupation/inoccupation et de lumière du jour Radio Powr SavrT, le pointeur laser vert peut être utilisé. Voir la note d’application 407 sur www.lutron.com pour plus d'informations. Pour associer un autre transmetteur, répétez les étapes 2A et 2B. Câblage de la commande de luminaire PowPakR Fonctionnalité par défaut Commandes sans fil : Toutes les lumières Depuis l'arrière du détecteur Perforation de la commande de luminaire PowPakR Link Test Maximisez la distance Câblage de lampe Allumé : 100 % ; Favori : 50 % ; Éteint : 0 % Commandes de luminaires Niveau d’allumage automatique : FC-SENSOR seulement (pas applicable pour le FC-VSENSOR) Varie avec le niveau de lumière ambiante lorsque l’occupation se déclenche (ex. : 100 % dans une pièce sombre, 10 % dans une pièce lumineuse). Période de délai d'extinction : 15 minutes Pour plus d'information, consultez : www.lutron.com/TechnicalDocumentLibrary/369866.pdf Lutron Electronics Co., Inc. 7200 Suter Road, Coopersburg, PA 18036-1299, États-Unis Remarques : 1. Les fils de commande (Violet/Gris pour le FCJ-010 ou Violet/Violet pour le FCJ-ECO) peuvent être de classe 1 ou de classe 2. 2. En cas d’utilisation de luminaire suspendu, la longueur maximale du fil entre le détecteur de luminaire et la commande de luminaire est de 3,7 m (12 pi). Le détecteur doit être monté à moins de 0,6 m (2 pi) du luminaire. 3. Pour installer l’unité dans un boîtier de raccordement, veuillez consulter la note d’application 423 sur www.lutron.com 4. La commande de luminaire doit être accessible pour certaines étapes de programmation. Documentez où elle est montée de façon à la localiser facilement ultérieurement. 5. En cas d’utilisation d’un détecteur de lumière du jour Radio Powr SavrT en conjonction avec une commande de luminaire sans fil PowPakR et un détecteur de luminaire PowPakR, le détecteur de lumière du jour Radio Powr SavrT fournit les données de la lumière du jour au module de commande, et les données de lumière du jour du détecteur de luminaire PowPakR sont ignorées. 6. En cas d’utilisation d’un détecteur d’occupation Radio Powr SavrT en conjonction avec une commande de luminaire sans fil PowPakR et un détecteur de luminaire PowPakR, les données d’occupation des deux détecteurs sont utilisées ; toute détection d’occupation de l’un d’entre eux allume les lumières, et les lumières s’éteignent seulement quand les deux détecteurs sont en mode d’inoccupation (ils ne détectent plus d’occupation). 7. Pour plus d'informations concernant le détecteur de luminaire PowPakR, consultez: Document 369866 ou 048556 sur www.lutron.com Pour le guide d'installation du FC-SENSOR et FC-VSENSOR consultez www.lutron.com Commandes de luminaires PowPak : Programmation Assistance technique | 1.800.523.9466 É.-U., Canada, et les Caraïbes | +44.(0)20.7702.0657 Europe | +1.610.282.3800 Autres | www.lutron.com 2 ® Appartient à la famille Energi TriPak® 041485 Rév. A 04/2015 TOUTE PROGRAMMATION EST OPTIONNELLE Le fonctionnement par défaut ne nécessite aucune programmation • Régler un niveau de lumière favori • Régler les seuils hauts et bas de toutes les appliques Restaurer les réglages d'usine Remarque : Dans certains cas, il peut être nécessaire de réinitialiser les commandes de luminaires et les appareils raccordés à leurs réglages d’usine par défaut. Avant de démarrer, vérifiez que tous les appareils sont raccordés et alimentés. A Appuyez trois fois rapidement sur le bouton de Alterner « » sur la commande de luminaire et maintenez-le enfoncé la quatrième fois jusqu’à ce que la DEL commence à clignoter lentement ; relâchez le bouton. B Après 3 secondes de clignotement, rappuyez sur le bouton de Alterner « » trois fois rapidement et les DEL clignoteront rapidement, indiquant que les réglages d’usine de l’unité ont été restaurés. Remarque : Toute association ou programmation configurée précédemment avec la commande de luminaire sera perdue et devra être reprogrammée. Commencez ici 1 Définir un niveau de luminosité favori (optionnel) Pour les commandes sans fil Pico® avec un bouton Favoris. A Réglez les lumières au niveau souhaité : Utilisez le bouton Monter Monter « » ou le bouton Baisser « » sur la commande sans fil Pico®. B Enregistrez le niveau favori : Appuyez et maintenez le bouton Favoris enfoncé Favori pendant 6 secondes La charge clignotera 3 fois pour confirmer la sauvegarde du niveau favori. Baisser Ajuster le réglage du seuil bas et le réglage du seuil haut (optionnel) Pour de meilleurs résultats, minimisez la quantité de lumière du soleil pénétrant dans la pièce avant de réaliser les procédures suivantes. Selon le fabricant de l’applique ou de la charge, il peut être nécessaire d'ajuster les seuils haut et bas. • Réglez le seuil bas pour assurer un niveau de lumière stable car certaines charges peuvent clignoter ou s’éteindre si le réglage est trop bas. • Vérifiez que vous pouvez régler les lumières au niveau du seuil bas sans fonctionnement anormal. • Le réglage d’usine du seuil haut convient à la plupart des applications mais peut être réglé comme vous le souhaitez. REMARQUE : Seuils hauts et seuils bas peuvent également être effectués pour une seule unité ou groupe d’unités simultanément avec une commande sans fil PicoR. Pour plus d’informations, voir le document 048556 sur www.lutron.com Réglage du seuil bas A Activer le mode d’ajustement du réglage du seuil bas : Appuyez et maintenez le bouton Baisser « » enfoncé sur la commande de luminaire pendant 12 secondes. Les lumières clignoteront à leur niveau et la DEL d'état de la charge commencera à clignoter. B Ajuster le réglage du seuil bas :  Utilisez le bouton Monter « » et le bouton Baisser « » sur la commande de luminaire pour régler les lumières au niveau de réglage du seuil bas souhaité (de 1 à 45 %). C Enregistrer le réglage du seuil bas : Appuyez et maintenez le bouton de Alterner « » enfoncé pendant 6 secondes pour enregistrer le réglage. La DEL d'état de la charge commencera à clignoter puis restera allumée pour indiquer que le nouveau niveau a été enregistré. Dépannage www.lutron.com Symptôme Solution Les ballasts / pilotes ne peuvent pas être commandés localement depuis la commande de luminaire. • Vérifiez que le(s) disjoncteur(s) de la commande de luminaire sont sous tension. • Vérifiez que le conducteur commuté de la commande de luminaire est raccordé au ballast / pilote (FCJ-010). • Vérifiez que les lignes de commande (FCJ-010 : violet/gris, FCJ-ECO: violet/violet) de la commande de luminaire sont raccordées au ballast / pilote • Si vous utilisez le FCJ-010, vérifiez que le ballast / pilote est de 0–10 V. Si vous utilisez le FCJ-ECO, utilisez le ballast / pilote EcoSystemR de LutronR. Les lumières ne se • tamisent ou ne s'allument pas comme prévu. • • • • • • Restaurer les réglages d'usine. Vérifiez que les lignes de commande sont raccordées correctement (FCJ-010 : violet/gris sensibles à la polarité, FCJ-ECO : violet/violet) Vérifiez que les fils sont raccordés entre le détecteur de luminaire et la commande de luminaire. FCJ-010 seulement : Assurez-vous que le luminaire de 0–10 V- est au seuil bas (à 0 V), pas éteint (à 0 V). S'il est éteint (à 0 V), réglez le seuil bas. FCJ-010 seulement : Vérifiez que le luminaire ne nécessite pas un signal inversé (commande de 10 – 0 V-). FCJ-010 seulement : Vérifiez que la tension entre les fils gris et violet se situe entre 0 et 10 V-. FCJ-ECO seulement : Déconnectez les fils violet / violet de la commande de luminaire. Vérifiez que les lumières vont à 100 %. FCJ-010 seulement : Déconnectez les fils violet / gris de la commande de luminaire. Vérifiez que les lumières vont à 100 %. Court-circuitez les fils violet / gris sur le ballast / pilote, vérifiez que les lumières se règlent à leur seuil bas. Les lumières ne répondent pas au(x) transmetteur(s) sans fil. • Vérifiez que le(s) disjoncteur(s) de la commande de luminaire et les ballasts / pilotes sont sous tension. • Vérifiez que les transmetteurs sans fil sont associés à la commande de luminaire. Restaurer les réglages d'usine. Les transmetteurs sans fil ne peuvent pas être associés à la commande de luminaire. La portée des radiofréquences entre les commandes sans fil est réduite en-dessous de 9 m (30 pi). Les lumières sont instables à leur seuil bas. • Le nombre maximal de transmetteurs sans fil a été associé à la commande de luminaire. Pour supprimer un transmetteur sans fil précédemment configuré, appuyez trois fois sur n’importe quel bouton du transmetteur sans fil ; à la troisième pression, maintenez-le enfoncé pendant trois secondes, puis appuyez trois fois de nouveau. • Réduisez et organisez le câblage du ballast/pilote au maximum pour éviter l’enchevêtrement des longueurs de fil excessives. • Veuillez à ce que les premiers 20-30 cm (7-12 po) de fils sortant de l’entrée à perforer de la commande de luminaire soit séparés autant que possible des fils des ballasts/pilotes/lampes environnants. • Contactez l’assistance technique de LutronR pour plus d’assistance. • Ajustez le réglage du seuil bas. Le détecteur de luminaire • Vérifiez que les fils du détecteur de luminaire sont raccordés à la commande de luminaire. n’allume pas les • Le FC-VSENSOR est en mode d’inoccupation seulement (il n’allume pas les lumières). lumières. L’adresse du FCJ-ECO • Tous les pilotes/ballasts connectés à un FCJ-ECO fonctionnent comme une zone unique. Si plus est introuvable. d’une zone est requise, utilisez un RMJ-ECO32-DV-B. Pour plus d’informations sur le détecteur de luminaire PowPakR, consultez les documents 369866 ou 048556 sur www.lutron.com Pour le guide d’installation du FC-SENSOR et du FC-VSENSOR, consultez www.lutron.com Réglage du seuil haut A Activer le mode de réglage du seuil haut : Appuyez et maintenez le bouton Monter « » enfoncé sur la commande de luminaire pendant 12 secondes. Garantie limitée : http://www.lutron.com/TechnicalDocumentLibrary/369-119_Wallbox_Warranty.pdf Les lumières clignoteront à leur niveau et la DEL d'état de la charge commencera Informations FCC Cet appareil est conforme à la partie 15 des règles du FCC et aux normes industrielles RSS d’exemption de licence du Canada. Le fonctionnement doit suivre les à clignoter. deux conditions suivantes : (1) Cet appareil ne doit pas provoquer d’interférences, et (2) cet appareil ne doit accepter aucune interférence, y compris des interférences B Ajuster le réglage du seuil haut : qui pourraient provoquer un fonctionnement indésirable. Les modifications qui n’ont pas été expressément approuvées par Lutron Electronics Co., Inc. peuvent  Utilisez le bouton Monter « » et le bouton Baisser « » sur la commande de luminaire annuler le pouvoir de l’utilisateur d’utiliser cet équipement. REMARQUE : Cet équipement a été testé et est conforme aux limites d’un appareil numérique de Classe B en vertu de la partie 15 des règles de la FCC. Ces limites pour régler les lumières au niveau de réglage du seuil haut souhaité (de 55 à 100 %). sont conçues pour fournir une protection raisonnable face aux interférences nuisibles dans une installation résidentielle. Cet équipement génère, utilise et peut émettre C Enregistrer le réglage du seuil haut : une énergie de fréquence radio et, s’il n’est pas installé et utilisé conformément aux instructions, il peut provoquer des interférences nuisibles aux communications radio. Cependant, il n’y a aucune garantie que des interférences ne surviendront dans une installation particulière. Si cet équipement provoque des interférences Appuyez et maintenez le bouton de Alterner « » enfoncé pendant 6 secondes nuisibles pour la réception radio et télévisuelle, ce qui peut être déterminé en allumant et en éteignant l’équipement, il est recommandé que l’utilisateur tente de pour enregistrer le réglage. corriger ces interférences en utilisant une ou plusieurs des mesures suivantes : La DEL d'état de la charge commencera à clignoter puis restera allumée pour • Réorientez ou repositionnez l’antenne réceptrice. • Augmentez la séparation entre l’équipement et le récepteur. indiquer que le nouveau niveau a été enregistré. )Lutron, Lutron, Pico, PowPak, EcoSystem et Energi TriPak sont des marques déposées et Radio Powr Savr est une marque de Lutron Electronics Co., Inc. NEC est une marque déposée de la National Fire Protection Association, Quincy, Massachusetts. ©2014 – 2015 Lutron Electronics Co., Inc. • Connectez l’équipement à une prise électrique se trouvant sur un circuit différent de celui où le récepteur est connecté. Lutron Electronics Co., Inc. 7200 Suter Road Coopersburg, PA 18036-1299, États-Unis
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6

Lutron Electronics PowPak FCJ-ECO Guía de instalación

Tipo
Guía de instalación
Este manual también es adecuado para