Lutron Electronics Vive Series Guía de instalación

Tipo
Guía de instalación
N
L
Fixture Earth
Green/Yellow
Switched Line/Hot (Red)
Line/Hot (Black)
Neutral (White)
Neutral
Fixture/
Troffer or
Junction
Box
1/2 in (21 mm)
Knockout
Opening
From back of
sensor
Emergency
Driver / Ballast
Conduit Nut
N
L
Fixture Earth
Green/Yellow
Switched Line/Hot (Red)
Line/Hot (Black)
Neutral (White)
Neutral
Fixture/
Troffer or
Junction
Box
1/2 in (21 mm)
Knockout
Opening
From back of
sensor
Normal
Driver / Ballast
Conduit Nut
FCJS-010
FCJS-010-EM
0 –10 V-
FCJS-ECO
FCJS-ECO-EM
Lutron EcoSystem
PowPak Wireless Fixture Control
UL 2043 Plenum Rated
UL 924 Listed (FCJS-010-EM/ FCJS-ECO-EM)
Controls up to 3 ballasts or drivers (IEC 60929 Annex E.2 requires each ballast or
driver to limit the sink/source current draw to 2.0 mA maximum).
Provides IEC SELV / NECR Class 2, 12 V-, 25 mA to a PowPak fixture sensor
(FC-SENSOR or FC-VSENSOR).
Lutron Electronics Co., Inc. 7200 Suter Road
Coopersburg, PA 18036-1299 USA
Part of the Vive Family
PowPak Fixture Controls
Installation
Required Components
For each fixture, you will need:
PowPak Fixture Sensor
(FC-SENSOR or
FC-VSENSOR)
(1 maximum)
Pico
Remote Control
(10 maximum)
6 mA maximum for the control lines. Switches up to 1 A total (or
maximum 3 ballasts or drivers). May be pre-installed in fixture.
Note: All drivers and ballasts used with Vive wireless controls must
comply with the limits for a Class A device, pursuant to Part 15 of the
FCC rules.
PowPak Wireless Fixture Control
(FCJS-010 / FCJS-010-EM or
FCJS-ECO / FCJS-ECO-EM)
Raise
Toggle
Lower
Load
Status
LED
Consult the fixture installation guide for fixture wiring.
For mounting and wiring best practices see Lutron Application Note #620 (P/N 048620).
Start Here
English
Important Notes: Please read before installing.
For installation by a qualified electrician in accordance with all local and
national electrical codes (including periodic testing and maintenance of
emergency systems).
Use copper conductors only.
Check to see that the device type and rating is suitable for the application.
DO NOT install if product has any visible damage.
If moisture or condensation is evident, allow the product to dry completely
before installation.
Operate between 32 °F and 104 °F (0 °C and 40 °C), ambient.
0% to 90% humidity, non-condensing.
For indoor use only.
120 – 277 V~ 50 / 60 Hz 1 A switching
PIR Lens
Laser
Detection
Daylight Lens
Radio Powr Savr
Occupancy/Vacancy
Sensor
(10 maximum)
Radio Powr Savr
Daylight Sensor
(1 maximum)
6 mA sink/source
Notes:
1. Fixture control can be used
without a fixture sensor as long
as at least one Radio Powr
Savr sensor or Pico remote
control is used.
2. Only one fixture control can be
used per fixture sensor, and
only one fixture sensor can be
used per fixture control.
Pico
remote
control
30 ft (9 m)
maximum
PowPak
Fixture Control
Install the fixture control directly to
a fixture or on a junction box nearest
to the fixture. Install the sensor on the ceiling near
the fixture to optimize coverage in the desired area.
Fixture
Control
Sensor
For more information please refer to Lutron P/N 369918 at
www.lutron.com
Notes:
1. Control wires (Violet/Gray for FCJS-010 / FCJS-010-EM or
Violet/Violet for FCJS-ECO / FCJS-ECO-EM) can be run as
either Class1 or Class2.
2. If hanging pendant fixtures the maximum wire length
between fixture sensor and fixture control is 12ft (3.7 m).
Sensor should be mounted no more than 2 ft (0.6 m) from
the fixture.
3. To install unit inside a junction box, please see Lutron
Application Note #423 (P/N 048423) on www.lutron.com
4. When not using the Vive Hub, the fixture control needs to
be accessible for some programming steps. Record where
it is mounted so that it can be easily located later.
5. When using a Radio Powr Savr daylight sensor in
conjunction with both a PowPak wireless fixture control
and PowPak fixture sensor, the Radio Powr Savr daylight
sensor will provide the daylighting input to the control
module, and the PowPak fixture sensor daylighting input
will be ignored.
6. When using a Radio Powr Savr occupancy sensor in
conjunction with both a PowPak wireless fixture control
and PowPak fixture sensor, occupancy data from both
sensors is used; either one detecting occupancy will
turn the lights on, and the lights turn off only when both
sensors have gone vacant (no longer detect occupancy).
7. For more information on the PowPak fixture sensor, see:
P/N 369866 or P/N 048556 on www.lutron.com
For FC-SENSOR and FC-VSENSOR installation guide visit
www.lutron.com
+
One Fixture Control
At least one of these transmitters (22 total allowed)
FCJS-010 / FCJS-010-EM: At least one 0 –10 V- Fluorescent Ballast or LED Driver
FCJS-ECO / FCJS-ECO-EM: At least one Lutron EcoSystem Ballast or LED Driver
+
120 – 277 V~ 50 / 60 Hz 1 A switching
14 V- 6 mA
Note for Replacement:
FCJS - the "S" model can replace the non-"S" model
Reset Factory Defaults
Note: In some instances, it may be necessary to reset the fi xture
controls and connected devices back to factory default settings.
Before beginning, make sure that all devices are connected and
powered.
A
Rapidly tap the Toggle button “ u on the fi xture control three
times and hold on the fourth until the LED begins to flash slowly;
release button.
B
Within 3 seconds of the start of flashing, again rapidly tap the
Toggle button “ u three times and the LEDs will flash rapidly
indicating that the unit has been reset to factory defaults.
Note: Any associations or programming previously set up
with the fi xture control will be erased and will need to be
re-programmed.
Customer Assistance www.lutron.com/support
041645
Rev. A
03/2018
Install Fixture Control and Optional Fixture Sensor
Suggested Installation Location: Close to the Fixture / Troffer.
The fixture control can be installed on a fixture/troffer, junction box or marshalling box
using the conduit nut (provided) or with mounting screws (not provided). Product must
NOT be mounted inside a fixture - only on the exterior of a fixture. Please consult local
and national electric codes for proper installation.
A
Ideally, mount the sensor to the ceiling tile close to the fixture using the wireform or using
the adhesive strip (included). The two communication wires from the sensor attach to the
fixture control stab-in connectors. The wires are interchangeable to eliminate miswiring.
Note: For FC-SENSOR and FC-VSENSOR installation guide visit www.lutron.com
B
Once installed, energize the control module. The fixture will turn on.
WARNING! Shock Hazard. May result in serious injury or death.
Turn off power at circuit breaker before installing the unit.
1
Wireless sensors
and controls must be
located within 60 ft (18 m)
line of sight, or 30 ft (9 m), through
walls, of the associated control module.
vive.lutron.com
X
Programming with a Vive Hub
2
A
Use an iOS® or Android®
compatible device.
C
Open the app and follow the
instructions.
Note: For further information on set up,
programming, and troubleshooting with a
Vive system, please refer to the installation
instructions included with the Vive hub or
visit www.lutron.com/vive
Note: For programming the PowPak Fixture
Control Module without a Vive hub see the
reverse side.
X
Vive
B
Download the Lutron
Vive app.
Emergency
Backup Generator
Automatic
Transfer
Switch
Neutral
120 / 277 V~
Emergency Feed
Regular
Utility Power
Neutral
120 / 277 V~ Normal Feed
Neutral
120 / 277 V~ Generator /
Emergency Feed
Important Note: To optimize RF performance of the product:
Keep the lamp wiring as short as possible to reduce the
radiation from the lamp wires.
Keep the lamp wiring as far as possible from the PowPak
Wireless Fixture Control mounting location.
See the Troubleshooting section for more details.
Maximize Distance
PowPak Fixture
Control Knockout
PowPak Fixture
Control Wiring
Lamp
Wiring
Note: For periodic testing and maintanance of emergency systems, use
the toggle button of the FCJS-010-EM / FCJS-ECO-EM to ensure
proper operation. Make sure PowPak buttons remain accessible.
Note: Momentary power outages can envoke emergency mode on the
fixture controller. See Troubleshooting section for details.
FCJS-010-EM /
FCJS-ECO-EM only
FCJS-010: – (Gray), + (Violet)
FCJS-ECO: E1 (Violet), E2 (Violet)
FCJS-010-EM: – (Gray), + (Violet)
FCJS-ECO-EM: E1 (Violet), E2 (Violet)
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be
followed including the following:
READ AND FOLLOW ALL SAFETY
INSTRUCTIONS.
Do not use outdoors.
Do not mount near gas or electric heaters.
Equipment should be mounted in locations and at heights where it will not be
subjected to tampering by unauthorized personnel.
The use of accessory equipment not recommended by the manufacturer may cause
an unsafe condition.
Do not use this equipment for other than its intended use.
SAVE THESE INSTRUCTIONS
FCC / IC Information
This device complies with part 15 of the FCC Rules and Industry Canada license-exempt RSS standard(s). Operation is subject to
the following two conditions: (1) This device may not cause interference, and (2) this device must accept any interference, including
interference that may cause undesired operation. Modifications not expressly approved by Lutron Electronics Co., Inc. could void the
user’s authority to operate this equipment.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC
Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment
generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause
harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation.
If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off
and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Re-orient or relocate the receiving antenna.
Increase the separation between the equipment and receiver.
Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
PowPak Fixture Controls
Programming without a Vive Hub
Limited Warranty:
www.lutron.com/TechnicalDocumentLibrary/369-119_Wallbox_Warranty.pdf
Low-End Trim
A
Enter low-end trim adjustment mode:
Press and hold the Lower button “
Ǻ
” on the fixture control for 12 seconds.
The lights will flash and the load status LED will begin flashing.
B
Adjust the low-end trim:
Use the Raise button “
ŷ
” and Lower button “
Ǻ
” on the fixture control to adjust and set the lights to
the desired low-end (1 to 45%).
C
Save the low-end trim:
Press and hold the Toggle button “ u for 6seconds to save setting.
The load status LED will begin flashing and then turn solid to indicate new level has been saved.
High-End Trim
A
Enter high-end trim adjustment mode:
Press and hold the Raise button “
ŷ
” on the fixture control for 12seconds.
The lights will flash and the load status LED will flash.
B
Adjust the high-end trim:
Use the Raise button “
ŷ
” and Lower button “
Ǻ
” on the fixture control to adjust and set the lights to
the desired high-end (55 to 100%).
C
Save the high-end trim:
Press and hold the Toggle button “ u for 6seconds to save setting.
The load status LED will begin flashing and then turn solid to indicate new level has been saved.
Set Low-End Trim and High-End Trim (Optional)
For best results, minimize the amount of sunlight entering the room before performing the
following procedures.
Depending on the fixture manufacturer or load, low-end trim and high-end trim may need
to be adjusted.
Trim low-end to ensure a stable light level because some loads will flicker or drop out if trimmed too low.
Be sure that you can turn on the lights to the low-end trim level without any abnormal operation.
The factory default high-end trim is suitable for most applications but can be adjusted as desired.
NOTE: High-end and low-end trim can also
be performed for a single unit or group of units
simultaneously with a Pico remote control.
For more information see P/N 048556
on www.lutron.com.
Lutron, EcoSystem, Pico, PowPak, and Vive are trademarks of Lutron Electronics Co., Inc., registered in the U.S. and other countries. Radio Powr Savr is a trademark of Lutron Electronics Co., Inc. Safari is a trademark of Apple Inc., registered in the U.S. and other countries. iOS is a registered trademark of Cisco in the U.S. and other countries and is used
under license. Google is a registered trademark and Android and Chrome are trademarks of Google Inc. NEC is a registered trademark of the National Fire Protection Association, Quincy, Massachusetts. ©2014 – 2018 Lutron Electronics Co., Inc.
B
Hold the indicated button on each transmitter for 6seconds. The
fixture will flash to show that wireless transmitters have been
associated. Alternatively, for Radio Powr Savr occupancy / vacancy
and daylight sensors, the green laser pointer can be used. See Lutron
Application Note #407 (P/N 048407) on www.lutron.com for more
information. To associate another transmitter, repeat steps 1A and 1B.
Test
Link
Associate Transmitters to Fixture Control
Before beginning this step, make sure that there are no other fixture
controls being set up in the building which are currently in association
mode. It is possible that wireless transmitters from other systems can be
incorrectly associated to this module.
OR
Laser Detection
Green laser specifications:
Wave output: constant
Wavelength: 532 nm
Output power: 5 mW maximum
Note: The fixture control will automatically exit
association mode 10 minutes after the last activity.
A
Initiate association mode on the fixture control in one of two ways:
1 Press and hold the Toggle button “ u ” for 6 seconds on the fixture
control until the load attached to the fixture control starts flashing
(every 2 seconds).
2 Alternatively, shine a green laser pointer (available at hardware or
office supply stores) at the laser detection hole on the sensor until the
load attached to the fixture control starts flashing (every 2 seconds).
Note: Multiple fixture controls can be placed into association mode
by repeating one of the two above methods for the next fixture control
prior to moving to Step 1B.
!
WARNING
!
DANGER
Eye injury and/or blindness hazard; avoid direct eye exposure to laser beam.
Use of laser pointer is NOT recommended for use with Lutron products located near
reflective surfaces.
DO NOT aim or shine laser pointers at any person, pet, vehicle, or aircraft directly, or
through reflection by mirrors or other shiny surfaces. DO NOT view the laser beam through
binoculars magnifying glass, or other optical devices.
DO NOT allow children to use laser pointers.
Read and follow the laser pointer manufacturer’s instructions on safe use. In the
event of injury, get medical attention immediately.
Tes t
Link
Cal.
Calibrate the Radio Powr Savr Daylight Sensor
Daylight Sensor will control all wired fixtures equally.
Start Here
Troubleshooting www.lutron.com/support
Symptom Solution
Ballasts / drivers cannot be controlled
locally from the fi xture control.
Ensure that the breaker(s) to the fixture control are energized.
Ensure that the fixture control switched hot lead is wired to the ballast / driver (FCJS-010 / FCJS-010-EM).
Ensure that the fixture control control lines (FCJS-010 / FCJS-010-EM: violet/gray, FCJS-ECO /
FCJS-ECO-EM: violet/violet) are wired to the ballast / driver.
If using FCJS-010 / FCJS-010-EM, verify the driver/ballast is 0 –10 V-.
If using FCJS-ECO / FCJS-ECO-EM, use the Lutron EcoSystem driver/ballast.
Reset to factory defaults.
Lights do not dim or turn ON as
expected.
Ensure that control lines are wired properly (FCJS-010 / FCJS-010-EM: violet/gray-polarity-
sensitive, FCJS-ECO / FCJS-ECO-EM: violet/violet)
Ensure that the wires are connected between the fixture sensor and the fi xture control.
FCJS-010 / FCJS-010-EM only: Make sure that 0 –10 V- fixture is at low-end (at 0 V), not OFF
(at 0 V). If OFF (at 0 V), adjust low-end trim.
FCJS-010 / FCJS-010-EM only: Ensure that fixture does not require an inverted signal
(10 – 0 V- control).
FCJS-010 / FCJS-010-EM only: Verify that the voltage across the gray and violet wires is between
0 and 10 V-.
FCJS-ECO / FCJS-ECO-EM only: Disconnect the violet / violet wires from the fixture control.
Verify that the lights go to 100%.
FCJS-010 / FCJS-010-EM only: Disconnect the violet / gray wires from the fixture control. Verify
that the lights go to 100%. Short the violet / gray wires on the ballast / driver, verify that the lights
go to low-end.
Lights do not respond to wireless
transmitter(s).
Ensure that the breaker(s) to the fixture control and ballasts / drivers are energized.
Ensure that wireless transmitters are associated to the fixture control.
Reset to factory defaults.
Wireless transmitter(s) cannot be
associated to the fixture control.
The maximum number of wireless transmitters have been associated to the fixture control. To
remove a previously set up wireless transmitter, tap any button on the wireless transmitter three
times; on the third tap, hold for three seconds and then tap three more times.
RF range between wireless controls
is diminished below 30 ft (9 m).
Keep the ballast/driver wiring as short as possible and well organized to avoid excess wire being
bunched up.
Keep the first 7 in –12 in (20 cm –30 cm) of the wires coming out of the fixture control knockout
separated as much as possible from any nearby ballast/driver/lamp wires.
Contact Lutron Customer Assistance for further details.
Lights are unstable at low-end. Adjust low-end trim.
Fixture sensor does not turn the lights
ON.
Check that fixture sensor wires are connected to fixture control.
FC-VSENSOR is vacancy only (it will not turn the lights on).
Fixture control is in emergency mode
(FCJS-010-EM, FCJS-ECO-EM only).
In systems with a Vive hub: Contact Lutron Customer Assistance for further details.
In systems without a Vive hub: Wait 90 minutes for the PowPak to return to normal operation.
Fixture control will not go into
emergency mode
(FCJS-010-EM, FCJS-ECO-EM only).
• Contact Lutron Customer Assistance for further details.
For information on activating egress mode, application suggestions, and many other notes on the PowPak fixture controls, see Lutron
document 048556 or 369918 on www.lutron.com.
A
Press and release the “Cal.” button on the Daylight Sensor.
B
Set lights in room to desired light level.
C
Press and hold the “Cal.” button for 6seconds.
D
Exit room for 5 minutes to complete calibration.
Note: When calibration has completed, all lights will flash and begin to respond to daylight.
Customer Assistance | 1.844.LUTRON1 U.S.A., Canada, and the Caribbean | +44.(0)20.7680.4481 Europe | +1.610.282.3800 Others | www.lutron.com/support
Part of the Vive Family
Customer Assistance www.lutron.com/support
1
2
Raise
Lower
Favorite
Set a Favorite Light Level (Optional)
For Pico remote controls with a Favorite Button.
A
Adjust lights to desired level:
Use the Raise button “
” or Lower button “ ” on the Pico remote control.
B
Save favorite level:
Press and hold the Favorite button for 6seconds. The load will flash 3 times
to confirm that the Favorite level is saved.
3
4
Wireless Controls: All lights
Default Functionality
Fixture Controls
Auto On level: FC-SENSOR only
(not applicable for FC-VSENSOR)
Varies with ambient light level when occupancy is triggered
(e.g., 100% for a dark room, 10% for a bright room).
Timeout period: 15 minutes
On: 100% ; Favorite: 50%; Off: 0%
N
L
Terre de
l’applique
Vert/Jaune
Ligne/Phase commuté (Rouge)
Ligne / Phase (Noir)
Neutre (Blanc)
Neutre
Luminaire /
plafonnier
ou boîtier de
raccordement
Entrée à perforer
de 21 mm
(1/2 po)
Depuis l’arrière
du détecteur
Ballast / Pilote
de secours
Écrou de
conduit
N
L
Terre de
l’applique
Vert/Jaune
Ligne/Phase commuté (Rouge)
Ligne / Phase (Noir)
Neutre (Blanc)
Neutre
Luminaire /
plafonnier
ou boîtier de
raccordement
Entrée à perforer
de 21 mm
(1/2 po)
Depuis
l’arrière du
détecteur
Ballast / Pilote
Normal
Écrou de
conduit
FCJS-010
FCJS-010-EM
0 –10 V-
FCJS-ECO
FCJS-ECO-EM
EcoSystem de Lutron
Commande de luminaire PowPak
Conformité plénum de la norme UL 2043
Certifié UL924 (FCJS-010-EM / FCJS-ECO-EM)
Commande jusqu’à 3 ballasts ou pilotes (la norme IEC 60929 Annexe E.2 exige que
chaque ballast ou pilote limite le courant de source/absorbé à 2,0 mA au maximum).
Fournit une alimentation IEC SELV / NECR de classe 2 de 12 V-, 25 mA à un
détecteur de luminaire PowPak (FC-SENSOR ou FC-VSENSOR).
Lutron Electronics Co., Inc. 7200 Suter Road
Coopersburg, PA 18036-1299 É.-U.
Appartient à la famille Vive
Commandes de luminaires PowPak
Installation
Composants requis
Pour chaque luminaire, vous aurez besoin de :
Détecteur de luminaire
PowPak
(FC-SENSOR ou
FC-VSENSOR)
(1 maximum)
Télécommande
Pico
(10 maximum)
Commande de luminaire sans fil PowPak
(FCJS-010 / FCJS-010-EM ou
FCJS-ECO / FCJS-ECO-EM)
Monter
Alterner
Baisser
DEL
d’état
de la
charge
Consultez le guide d’installation du luminaire pour le câblage du luminaire.
Pour les meilleures pratiques de montage et de câblage, consultez la note d’application
620 (no de pièce048620) de Lutron.
Commencez ici
Français
Remarques importantes : Veuillez lire avant l’installation.
À faire installer par un électricien qualifié conformément à tous les codes
électriques locaux et nationaux (y compris pour le contrôle et l’entretien
périodiques des systèmes de secours).
N’utilisez que des conducteurs en cuivre.
Veillez à ce que le type d’appareil et sa caractéristique nominale
conviennent à l’application.
Ne l’installez PAS si le produit présente des dommages visibles.
Si de l’humidité ou de la condensation est apparente, laissez le produit
sécher avant son installation.
Fonctionne de 0°C à 40°C (32°F à 104°F), température ambiante.
0 à 90 % d’humidité, sans condensation.
Utilisation à l’intérieur uniquement.
Commutation 120 277 V~ 50 / 60 Hz 1 A
Lentille PIR
Détection
du laser
Lentille de
lumière du jour
Détecteur d’occupation/
inoccupation
Radio Powr Savr
(10 maximum)
Détecteur de
lumière du jour
Radio Powr Savr
(1 maximum)
Courant de source/absorbé 6 mA
Remarques :
1. La commande de luminaire
peut être utilisée sans détecteur
de luminaire à condition qu’au
moins un détecteur Radio Powr
Savr ou une télécommande
Pico est utilisé.
2. Une seule commande de
luminaire peut être utilisée par
détecteur de luminaire et un
seul détecteur de luminaire
peut être utilisé par commande
de luminaire.
Télécommande
Pico
9 m (30 pi)
maximum
Commande de
luminaire PowPak
Installez la commande de luminaire directement
sur un luminaire ou un boîtier de raccordement près du
luminaire. Installez le détecteur au plafond près du luminaire
pour optimiser sa portée dans la zone souhaitée.
Commande
de
luminaire
Détecteur
Pour plus d’informations veuillez vous reporter au n° de pièce
369918 de Lutron sur www.lutron.com
Remarques :
1. Les fils de commande (Violet/Gris pour le FCJS-010 ou
Violet/Violet pour le FCJS-ECO) peuvent être de classe1
ou de classe2.
2. En cas d’utilisation de luminaire suspendu, la longueur
maximale du fil entre le détecteur de luminaire et la
commande de luminaire est de 3,7 m (12pi). Le détecteur
doit être monté à moins de 0,6 m (2 pi) du luminaire.
3. Pour installer l’unité dans un boîtier de raccordement, veuillez
consulter la note d’application 423 (no de pièce048423) de
Lutron sur www.lutron.com
4. Si le hub Vive n’est pas utilisé, la commande de
luminaire doit être accessible pour certaines étapes de
programmation. Documentez où elle est montée de façon à la
localiser facilement ultérieurement.
5. En cas d’utilisation d’un détecteur de lumière du jour
Radio Powr Savr en conjonction avec une commande
de luminaire sans fil PowPak et un détecteur de luminaire
PowPak, le détecteur de lumière du jour Radio Powr
Savr fournit les données de la lumière du jour au module
de commande, et les données de lumière du jour du
détecteur de luminaire PowPak sont ignorées.
6. En cas d’utilisation d’un détecteur d’occupation Radio Powr
Savr en conjonction avec une commande de luminaire sans
fil PowPak et un détecteur de luminaire PowPak, les données
d’occupation des deux détecteurs sont utilisées; toute détection
d’occupation de l’un d’entre eux allume les lumières, et les
lumières séteignent seulement quand les deux détecteurs sont
en mode d’inoccupation (ils ne détectent plus d’occupation).
7. Pour plus d’informations concernant le détecteur de
luminaire PowPak, consultez: no de pièce 369866 ou no
de pièce 048556 sur www.lutron.com
Pour le guide d’installation du FC-SENSOR et FC-VSENSOR
consultez www.lutron.com
+
Une commande de luminaire
Au moins un de ces transmetteurs (22 permis au total)
FCJS-010 / FCJS-010-EM: Au moins un ballast fluorescent ou un pilote de DEL de 0 –10 V-
FCJS-ECO / FCJS-ECO-EM: Au moins un pilote de DEL ou ballast EcoSystem de Lutron
+
Commutation 120 277 V~ 50 / 60 Hz 1 A
14 V- 6 mA
Remarque pour les remplacements :
FCJS
- le modèle «S» peut remplacer le modèle non-«S»
Assistance à la clientele www.lutron.com/support
041645
Rev. A
03/2018
Installer la commande de luminaire et le détecteur
de luminaire optionnel
Emplacement recommandé pour l’installation : Près d’un luminaire / plafonnier.
La commande de luminaire peut être installée sur un luminaire / plafonnier, dans un boîtier de
raccordement ou un boîtier de regroupement avec l’écrou de conduit (fourni) ou des vis de montage
(non fournies). Le produit NE DOIT PAS être monté à l’intérieur d’un luminaire - seulement à l’extérieur
d’un luminaire. Veuillez consulter les codes électriques en vigueur pour une installation correcte.
A
Si possible, montez le détecteur sur une dalle de plafond à proximité du luminaire au moyen
du fil ou de la bande adhésive (inclus). Reliez les deux fils de communication du détecteur aux
fiches de connexion de la commande de luminaire. Les fils sont interchangeables pour éviter
un mauvais câblage. Remarque : Pour le guide d’installation du FC-SENSOR et du
FC-VSENSOR, consultez www.lutron.com
B
Une fois installé, mettez le module de commande sous tension. Le luminaire s’allumera.
AVERTISSEMENT ! Risque d’électrocution. Peut causer des blessures graves ou la mort.
Coupez l’alimentation au niveau du disjoncteur avant d’installer l’unité.
1
Les détecteurs sans
fil et les commandes
doivent se situer à moins
de 18 m (60 pi) en ligne directe
du module de commande associé ou à moins
de 9 m (30 pi) à travers les murs.
vive.lutron.com
X
Programmation avec un hub Vive
2
A
Utilisez un appareil compatible
avec iOS® ou Android®.
C
Ouvrez l’application et suivez
les instructions.
Remarque: Pour plus d’information sur
la configuration, la programmation et le
dépannage avec un système Vive, veuillez
vous reporter aux instructions d’installation
fournies avec le hub Vive ou consultez
www.lutron.com/vive
Remarque: Pour programmer le module de
commande de luminaire PowPak sans hub
Vive, consultez le verso.
X
Vive
B
Téléchargez l’application Vive
de Lutron.
Générateur de
secours
Commutateur
de transfert
automatique
Neutre
Alimentation de secours
de 120 / 277 V~
Alimentation de
service régulière
Neutre
Alimentation normale de
120 / 277 V~
Neutre
Remarque: Pour le contrôle et l’entretien périodiques des systèmes de
secours, utilisez le bouton à bascule du FCJS-010-EM /
FCJS-ECO-EM pour garantir le bon fonctionnement.
Assurez-vous que les boutons du PowPak restent accessibles.
Remarque: Les coupures de courant momentanées peuvent déclencher
le mode de secours sur la commande de luminaire. Voir la
section Dépannage pour plus d’informations.
FCJS-010: - (Gris), + (Violet)
FCJS-ECO: E1 (Violet), E2 (Violet)
FCJS-010: - (Gris), + (Violet)
FCJS-ECO: E1 (Violet), E2 (Violet)
CONSIGNES DE SÉCURITÉ IMPORTANTES
Lorsque vous utilisez des appareils électriques, il est important de toujours respecter
les consignes de sécurité élémentaires, notamment:
LISEZ ET RESPECTEZ TOUTES LES
CONSIGNES DE SÉCURITÉ.
N’utilisez pas cet équipement à l’extérieur.
Ne l’installez pas à proximité de radiateurs électriques ou au gaz.
L’équipement doit être installé dans des endroits et à des hauteurs où il ne sera pas
manipulé par des personnes non-autorisées.
L’utilisation d’accessoires non recommandés par le fabricant peut provoquer une
situation dangereuse.
N’utilisez pas cet appareil pour d’autres fins que celles prévues.
CONSERVEZ CES CONSIGNES
6 mA maximum pour les lignes de commande. Commute jusqu’à 1 A au total (ou
3 ballasts ou pilotes maximum). Peut être préinstallé dans un luminaire.
Remarque: Tous les pilotes et ballasts utilisés avec les commande Vive sans
fil doivent être conformes aux limites d’un appareil de Classe A en vertu de la
partie 15 des règles de la FCC.
Remarque importante : Pour optimiser les performances de
radiofréquences du produit :
Réduisez la longueur du câblage de la lampe au maximum pour réduire
le rayonnement des fils de la lampe.
Gardez le câblage de la lampe aussi loin que possible de l’emplacement
du montage de la commande de luminaire sans fil PowPak.
Voir la section Dépannage pour plus d’informations.
Maximisez la distance
Perforation de la
commande de
luminaire PowPak
Câblage de la
commande de
luminaire PowPak
Câblage
de lampe
FCJS-010-EM /
FCJS-ECO-EM seulement
Générateur / Alimentation de
secours de 120 / 277 V~
Restaurer les réglages d’usine
Remarque : Dans certains cas, il peut être nécessaire de
réinitialiser les commandes de luminaires et les appareils
raccordés à leurs réglages d’usine par défaut. Avant de démarrer,
vérifiez que tous les appareils sont raccordés et alimentés.
A
Appuyez trois fois rapidement sur le bouton de Alterner « u» sur
la commande de luminaire et maintenez-le enfoncé la quatrième
fois jusqu’à ce que la DEL commence à clignoter lentement;
relâchez le bouton.
B
Après 3 secondes de clignotement, rappuyez sur le bouton de
Alterner « u» trois fois rapidement et les DEL clignoteront rapidement,
indiquant que les réglages d’usine de l’unité ont été restaurés.
Remarque : Toute association ou programmation configurée
précédemment avec la commande de luminaire sera perdue et
devra être reprogrammée.
Informations FCC / IC
Cet appareil est conforme à la partie 15 des règles du FCC et aux normes industrielles RSS d’exemption de licence du Canada. Le
fonctionnement doit suivre les deux conditions suivantes : (1) Cet appareil ne doit pas provoquer d’interférences, et (2) cet appareil ne doit
accepter aucune interférence, y compris des interférences qui pourraient provoquer un fonctionnement indésirable. Les modifications qui n’ont
pas été expressément approuvées par Lutron Electronics Co., Inc. peuvent annuler le pouvoir de l’utilisateur d’utiliser cet équipement.
REMARQUE : Cet équipement a été testé et est conforme aux limites d’un appareil numérique de Classe B en vertu de la partie 15 des
règles de la FCC. Ces limites sont conçues pour fournir une protection raisonnable face aux interférences nuisibles dans une installation
résidentielle. Cet équipement génère, utilise et peut émettre une énergie de fréquence radio et, s’il n’est pas installé et utilisé conformément aux
instructions, il peut provoquer des interférences nuisibles aux communications radio. Cependant, il n’y a aucune garantie que des interférences
ne surviendront dans une installation particulière. Si cet équipement provoque des interférences nuisibles pour la réception radio et télévisuelle,
ce qui peut être déterminé en allumant et en éteignant l’équipement, il est recommandé que l’utilisateur tente de corriger ces interférences en
utilisant une ou plusieurs des mesures suivantes :
Réorientez ou repositionnez l’antenne réceptrice.
Augmentez la séparation entre l’équipement et le récepteur.
Connectez l’équipement à une prise électrique se trouvant sur un circuit différent de celui où le récepteur est connecté.
Commandes de luminaires PowPak
Programmation sans hub Vive
Garantie limitée :
www.lutron.com/TechnicalDocumentLibrary/369-119_Wallbox_Warranty.pdf
Réglage du seuil bas
A
Activer le mode d’ajustement du réglage du seuil bas :
Appuyez et maintenez le bouton Baisser «
Ǻ
» enfoncé sur la commande de luminaire pendant 12
secondes. Les lumières clignoteront à leur niveau et la DEL d’état de la charge commencera à clignoter.
B
Ajuster le réglage du seuil bas :
Utilisez le bouton Monter «
ŷ
» et le bouton Baisser
«
Ǻ
»
sur la commande de luminaire pour régler les
lumières au niveau de réglage du seuil bas souhaité
(1 à 45 %)
.
C
Enregistrer le réglage du seuil bas :
Appuyez et maintenez le bouton de Alterner
« u»
enfoncé pendant 6secondes pour enregistrer le
réglage. La DEL d’état de la charge commencera à clignoter puis restera allumée pour indiquer que le
nouveau niveau a été enregistré.
Réglage du seuil haut
A
Activer le mode de réglage du seuil haut :
Appuyez et maintenez le bouton Monter «
ŷ
» enfoncé sur la commande de luminaire pendant 12
secondes. Les lumières clignoteront à leur niveau et la DEL d’état de la charge commencera à clignoter.
B
Ajuster le réglage du seuil haut :
Utilisez le bouton Monter «
ŷ
» et le bouton Baisser
«
Ǻ
»
sur la commande de luminaire
pour régler les
lumières au niveau de réglage du seuil haut souhaité
(55 à 100 %)
.
C
Enregistrer le réglage du seuil haut :
Appuyez et maintenez le bouton de Alterner
« u»
enfoncé pendant 6secondes pour enregistrer le réglage.
La DEL d’état de la charge commencera à clignoter puis restera allumée pour indiquer que le nouveau
niveau a été enregistré.
Ajuster le réglage du seuil bas et le réglage du seuil haut (optionnel)
Pour de meilleurs résultats, minimisez la quantité de lumière du soleil pénétrant dans la
pièce avant de réaliser les procédures suivantes.
Selon le fabricant de l’applique ou de la charge, il peut être nécessaire d’ajuster les seuils haut et bas.
Réglez le seuil bas pour assurer un niveau de lumière stable car certaines charges peuvent
clignoter ou s’éteindre si le réglage est trop bas.
Vérifiez que vous pouvez régler les lumières au niveau du seuil bas sans fonctionnement anormal.
Le réglage d’usine du seuil haut convient à la plupart des applications mais peut être réglé
comme vous le souhaitez.
Lutron, EcoSystem, Pico, PowPak, et Vive sont des marques déposées de Lutron Electronics Co., Inc., enregistrées aux États-Unis et dans d’autres pays. Radio Powr Savr est une marque déposée de Lutron Electronics Co., Inc. Safari est une marque poe de Apple Inc., enregistrées aux États-Unis et dans d’autres pays. iOS est une marque
posée de Cisco aux États-Unis et dans d’autres pays, utilisée sous licence. Google est une marque déposée et Android et Chrome sont des marques de Google Inc. NEC est une marque déposée de le National Fire Protection Association, Quincy, Massachusetts. ©2014 – 2018 Lutron Electronics Co., Inc.
B
Maintenez le bouton indiqué enfoncé sur chaque transmetteur pendant 6
secondes. Le luminaire clignotera indiquant que les transmetteurs sans fil
ont été associés. De façon alternative, pour les détecteurs d’occupation/
inoccupation et de lumière du jour Radio Powr Savr, le pointeur laser vert
peut être utilisé. Voir la note d’application 407 (no de pièce048407) de
Lutron sur www.lutron.com pour plus d’informations. Pour associer un
autre transmetteur, répétez les étapes 1A et 1B.
Test
Link
Associer des transmetteurs à la commande
de luminaire
Avant d’entamer cette étape, veillez à ce qu’aucune autre commande de
luminaire en phase de configuration dans le bâtiment ne soit actuellement
en mode d’association. Les transmetteurs sans fil d’autres systèmes
peuvent s’associer à ce module de façon incorrecte.
OU
Détection du laser
Caractéristiques du laser vert :
Sortie d’onde : constante
Longueur d’onde : 532 nM
Puissance de sortie : 5 mW maximum
Remarque : La commande de luminaire quitte
automatiquement le mode d’association 10
minutes après la dernière activité.
A
Démarrez le mode d’association sur la commande de luminaire de l’une de
ces deux façons :
1 Appuyez et maintenez le bouton de Alterner « u » enfoncé pendant
6secondes sur la commande de luminaire jusqu’à ce que la charge liée au
module de commande commence à clignoter (toutes les 2 secondes).
2 De façon alternative, dirigez le pointeur laser vert (disponible dans les
magasins de bricolage ou de fournitures de bureau) allumé sur le trou de
détection de laser du détecteur jusqu’à ce que la charge liée à la commande
de luminaire commence à clignoter (toutes les 2 secondes).
Remarque: Plusieurs commandes de luminaires peuvent être placées en
mode d’association en répétant l’une des deux méthodes ci-dessus pour la
commande de luminaire suivante avant de passer à l’étape 1B.
!
AVERTISSEMENT
!
DANGER
Blessure aux yeux et/ou risque d’aveuglement ; évitez une exposition oculaire directe
au faisceau du laser.
L’utilisation d’un pointeur laser n’est PAS recommandée avec les produits Lutron situés près
de surfaces réfléchissantes.
NE PAS diriger ou faire briller les pointeurs laser vers une personne, un animal, un véhicule, ou
un avion directement ou par réflexion par le biais de miroirs ou autres surfaces brillantes. NE
PAS regarder le faisceau du laser avec des jumelles, une loupe ou tout autre appareil optique.
NE PAS autoriser les enfants à utiliser les pointeurs laser.
Lisez et suivez les instructions du fabricant du pointeur laser concernant leur
utilisation en toute sécurité.
En cas de blessure, consulter un médecin immédiatement.
Tes t
Link
Cal.
Étalonner le détecteur de lumière du jour Radio Powr Savr
Le détecteur de lumière du jour commandera toutes les appliques câblées
de façon égale.
Commencez ici
A
Appuyez et relâchez le bouton «Cal.» sur le détecteur de lumière du jour.
B
Réglez les lumières dans la pièce au niveau souhaité.
C
Appuyez et maintenez le bouton «Cal.» enfoncé pendant 6 secondes.
D
Quittez la pièce pendant 5 minutes pour effectuer l’étalonnage.
Remarque : Une fois l’étalonnage effectué, toutes les lumières clignoteront et commenceront
à réagir à la lumière du jour.
Assistance à la clientele | 1.844.LUTRON1 É.-U., Canada, et les Caraïbes | +44.(0)20.7702.0657 Europe | +1.610.282.3800 Autres | www.lutron.com/support
Appartient à la famille Vive
Assistance à la clientele www.lutron.com/support
1
2
Favoris
Définir un niveau de luminosité favori (optionnel)
Pour les télécommandes Pico avec un bouton Favoris.
A
Réglez les lumières au niveau souhaité :
Utilisez le bouton Monter «
» ou le bouton Baisser « » sur la
télécommande Pico.
B
Enregistrez le niveau favori :
Appuyez et maintenez le bouton Favoris enfoncé pendant 6 secondes.
La charge clignotera 3 fois pour confirmer la sauvegarde du niveau favori.
3
4
Commandes sans fil : Toutes les lumières
Fonctionnalité par défaut
Commandes de luminaires
Niveau d’allumage automatique : FC-SENSOR seulement
(pas applicable pour le FC-VSENSOR)
Varie avec le niveau de lumière ambiante lorsque l’occupation se déclenche
(ex.: 100 % dans une pièce sombre, 10 % dans une pièce lumineuse).
Période de délai d'extinction : 15 minutes
Allumé : 100 % ; Favori : 50 % ; Éteint : 0 %
Monter
Baisser
Dépannage www.lutron.com/support
Symptôme Solution
Les ballasts / pilotes ne peuvent pas
être commandés localement depuis
la commande de luminaire.
Vérifiez que le(s) disjoncteur(s) de la commande de luminaire sont sous tension.
Vérifiez que le conducteur commuté de la commande de luminaire est raccordé au ballast / pilote
(FCJ
S
-010
/ FCJS-010-EM).
Vérifiez que les lignes de commande (FCJS-010 / FCJS-010-EM: violet/gris FCJS-ECO /
FCJS-ECO-EM: violet/violet) de la commande de luminaire sont raccordées au ballast / pilote
Si vous utilisez le FCJS-010 / FCJS-010-EM, vérifiez que le ballast / pilote est de 0 –10 V-.
Si vous utilisez le FCJS-ECO / FCJS-ECO-EM, utilisez le ballast / pilote EcoSystem de Lutron.
Restaurer les réglages d'usine.
Les lumières ne se tamisent ou ne
s’allument pas comme prévu.
Vérifiez que les lignes de commande sont raccordées correctement (FCJS-010 / FCJS-010-EM:
violet/gris sensibles à la polarité, FCJS-ECO / FCJS-ECO-EM: violet/violet)
Vérifiez que les fils sont raccordés entre le détecteur de luminaire et la commande de luminaire.
FCJS-010 / FCJS-010-EM
seulement : Assurez-vous que le luminaire de 0 –10 V- est au seuil bas
(à 0 V), pas éteint (à 0 V).
S’il est éteint (à 0 V), réglez le seuil bas.
FCJS-010 / FCJS-010-EM
seulement : Vérifiez que le luminaire ne nécessite pas un signal inversé
(commande de 10 0 V-).
FCJS-010 / FCJS-010-EM seulement : Vérifiez que la tension entre les fils gris et violet se situe entre
0 et 10 V-.
FCJS-ECO / FCJS-ECO-EM seulement : Déconnectez les fils violet / violet de la commande de
luminaire. Vérifiez que les lumières vont à 100 %.
FCJS-010 / FCJS-010-EM seulement : Déconnectez les fils violet / gris de la commande de luminaire.
Vérifiez que les lumières vont à 100 %. Court-circuitez les fils violet / gris sur le ballast / pilote, vérifiez
que les lumières se règlent à leur seuil bas.
Les lumières ne répondent pas au(x)
transmetteur(s) sans fil.
Vérifiez que le(s) disjoncteur(s) de la commande de luminaire et les ballasts / pilotes sont sous tension.
Vérifiez que les transmetteurs sans fil sont associés à la commande de luminaire.
Restaurer les réglages d'usine.
Les transmetteurs sans fil ne peuvent
pas être associés à la commande de
luminaire.
Le nombre maximal de transmetteurs sans fil a été associé à la commande de luminaire. Pour
supprimer un transmetteur sans fil précédemment configuré, appuyez trois fois sur n’importe
quel bouton du transmetteur sans fil ; à la troisième pression, maintenez-le enfoncé pendant trois
secondes, puis appuyez trois fois de nouveau.
La portée des radiofréquences entre
les commandes sans fil est réduite
en-dessous de 9 m (30 pi).
Réduisez et organisez le câblage du ballast/pilote au maximum pour éviter l’enchevêtrement des
longueurs de fil excessives.
Veuillez à ce que les premiers 20-30 cm (7-12 po) de fils sortant de l’entrée à perforer de la commande de
luminaire soit séparés autant que possible des fils des ballasts/pilotes/lampes environnants.
Contactez l’assistance à la clientèle de Lutron pour plus de détails.
Les lumières sont instables à leur
seuil bas.
Ajustez le réglage du seuil bas.
Le détecteur de luminaire n’allume
pas les lumières.
Vérifiez que les fils du détecteur de luminaire sont raccordés à la commande de luminaire.
Le FC-VSENSOR est en mode d’inoccupation seulement (il n’allume pas les lumières).
La commande de luminaire est en
mode de secours (FCJS-010-EM,
FCJS-ECO-EM seulement).
Dans les systèmes avec un hub Vive: Contactez l’assistance à la clientèle de Lutron pour plus de détails.
Dans les systèmes sans hub Vive: Attendez 90minutes pour que le PowPak revienne au
fonctionnement normal.
La commande de luminaire ne passera
pas en mode de secours (FCJS-010-EM,
FCJS-ECO-EM seulement).
• Contactez l’assistance à la clientèle de Lutron pour plus de détails.
Pour obtenir des informations d’activation du mode de sortie au seuil bas, des suggestions d’application et bien d’autres notes sur les
commandes de luminaires PowPak, consultez le document de Lutron 048556 ou 369918 sur www.lutron.com.
REMARQUE : Seuils hauts et seuils bas
peuvent également être effectués pour une
seule unité ou groupe d’unités simultanément
avec une télécommande Pico.
Pour plus d’informations, voir le no de
pièce 048556 sur www.lutron.com
N
L
Tierra del
artefacto
Verde/Amarillo
Línea/vivo conmutada (rojo)
Línea/vivo (negro)
Neutro (Blanco)
Neutro
Artefacto/
Luminaria
o caja de
conexiones
Abertura con tapa
ciega de 21 mm
(1/2 pulg)
Desde la parte
trasera del sensor
Balasto /
Controlador
Emergencia
Tuerca del
conducto
FCJS-010
FCJS-010-EM
0 –10 V-
FCJS-ECO
FCJS-ECO-EM
Lutron EcoSystem
Control inalámbrico de artefactos PowPak
Homologado UL 2043 para plenum
Listado en UL 924 (FCJS-010-EM / FCJS-ECO-EM)
Controla hasta tres balastos o controladores (la norma IEC 60929 anexo E.2 requiere que
cada balasto o controlador limite la corriente de fuente/drenaje a 2,0 mA como máximo).
Suministra 12 V- , 25 mA IEC SELV/NECR Clase 2 a un sensor de artefactos
PowPak (FC-SENSOR o FC-VSENSOR).
Lutron Electronics Co., Inc. 7200 Suter Road
Coopersburg, PA 18036-1299 E.U.A.
Parte de la familia Vive
Módulo de Atenuación PowPak
Instalación
Componentes requeridos
Para cada artefacto, se necesitará:
Sensor de artefactos
PowPak (FC-SENSOR o
FC-VSENSOR)
(1 máximo)
Control
remoto Pico
(10 máximo)
6 mA máximo para las líneas de control. Conmuta hasta 1 A en total (o un
máximo de tres balastos o controladores). Puede ser preinstalado en el artefacto.
Nota: Todos los controladores y balastos utilizados con los controles
inalámbricos Vive deben satisfacer los límites para un dispositivo de clase A,
de conformidad con la Parte 15 de las reglas de la FCC.
Control inalámbrico de artefactos
PowPak (FCJS-010 / FCJS-010-EM o
FCJS-ECO / FCJS-ECO-EM)
Subir
Encender
y Apagar
Bajar
LED
de
estado
de la
carga
Para informarse del cableado de los artefactos consulte la guía de instalación de artefactos.
Para obtener las mejores prácticas de montaje y conexión consulte la Nota de
aplicación Nº 620 de Lutron (N/P 048620).
Comience aquí
Español
Important Notes: Please read before installing.
Para ser instalado por un electricista calificado de acuerdo con todas las
normativas eléctricas locales y nacionales (incluidos la verificación y el
mantenimiento periódicos de los sistemas de emergencia).
Sólo utilice conductores de cobre.
Verifique que el tipo de dispositivo y la certificación sean adecuados para
la aplicación.
NO instale este producto si tuviera algún daño visible.
Si hubiera señales evidentes de humedad o condensación, permita que
el producto se seque por completo antes de la instalación.
Opérelo entre 0 °C y 40 °C (32 °F y 104 °F) de temperatura ambiente.
0 a 90% de humedad, sin condensación.
Sólo para uso bajo techo.
Conmutación de 120 277 V~ 50 / 60 Hz 1 A
Lente PIR
Detección
de láser
Lente de luz
diurna
Sensor de ocupación/
vacancia
Radio Powr Savr
(10 máximo)
Sensor de luz
diurna
Radio Powr Savr
(1 máximo)
Fuente / drenaje de 6 mA
Notas:
1. El control de artefactos puede
utilizarse sin un sensor de
artefactos siempre y cuando
se utilice al menos un sensor
Radio Powr Savr o un control
inalámbrico Pico.
2. Sólo puede utilizarse un
control de artefactos por
sensor de artefactos, y sólo
puede utilizarse un sensor
de artefactos por control de
artefactos.
Control
remoto
Pico
9 m (30 pies)
máximo
Control de
artefactos PowPak
Instale el control de artefactos directamente en un
artefacto o en la caja de conexiones más cercana al
artefacto. Instale el sensor en el cielorraso cerca del
artefacto para optimizar la cobertura en el área deseada.
Control
de
artefactos
Sensor
Para obtener más información, consulte
N/P 369918 de Lutron en www.lutron.com
+
Un control de artefactos
Al menos uno de estos transmisores (permitidos 22 en total)
FCJS-010 / FCJS-010-EM: Al menos un balasto fluorescente o controlador de LED de 0 –10 V-
FCJS-ECO / FCJS-ECO-EM: Al menos un balasto o controlador de LED Lutron EcoSystem
+
Conmutación de 120 277 V~ 50 / 60 Hz 1 A
14 V- 6 mA
Nota para el reemplazo:
FCJS - el modelo “S” puede reemplazar al modelo no “S”
Asistencia al cliente www.lutron.com/support
041645
Rev. A
03/2018
Instale el control de artefactos y el sensor de
artefactos opcional
Ubicación de instalación sugerida: Cercana a un artefacto/luminaria.
El control del artefactos puede instalarse en un artefacto/luminaria, caja de conexiones o caja
organizadora utilizando la tuerca de conducto (suministrada) o con tornillos de montaje (no suministrados).
El producto NO debe montarse dentro de un dispositivo, solo en el exterior de un dispositivo. Para
obtener una instalación adecuada consulte las normativas eléctricas locales y nacionales.
A
Idealmente, monte el sensor a la placa de techo cerca del artefacto utilizando el gancho de montaje
o la cinta adhesiva (incluidos). Los dos cables de comunicación del sensor se conectan a los
conectores de cuchilla del control de artefactos. Los cables son intercambiables para eliminar los
defectos de cableado. Nota: Para obtener la guía de instalación del FC-SENSOR y FC-VSENSOR
visite www.lutron.com
B
Una vez instalado, energice el módulo de control. Este artefacto se encenderá.
ADVERTENCIA! Peligro de descarga eléctrica. Podría ocasionar lesiones graves o la
muerte. Antes de instalar el equipo desconecte la alimentación eléctrica en el disyuntor.
1
Los sensores y
controles inalámbricos
deben estar situados a
menos de 18 m (60 pies) con
línea de visión directa, o 9 m (30 pies) a
través de paredes, del módulo de control asociado.
vive.lutron.com
X
Programación con un hub Vive
2
A
Utilice un dispositivo compatible
con iOS® o Android®.
C
Abra la aplicación y siga las
instrucciones.
Nota: Para obtener información adicional
sobre la configuración, programación y
resolución de problemas con un sistema
Vive, consulte las instrucciones de
instalación incluidas con el hub Vive o visite
www.lutron.com/vive
Nota: Para programar el módulo de control
de artefactos PowPak sin un hub Vive,
consulte el dorso.
X
Vive
B
Descargue la aplicación
Vive de Lutron.
Generador de respaldo
de emergencia
Interruptor de
transferencia
automática
Neutro
Alimentación de
emergencia
de 120/277 V~
Suministro
eléctrico normal
de la red
Neutro
Alimentación normal de
120 / 277 V~
Neutro
Generador de 120/277 V~ /
Alimentación de emergencia
Nota: Para la verificación y el mantenimiento periódicos de los sistemas
de emergencia, utilice el botón de alternancia del FCJS-010-EM /
FCJS-ECO-EM para asegurar una operación adecuada. Asegúrese
de que los botones de PowPak permanezcan accesibles.
Nota: Las interrupciones momentáneas de la alimentación eléctrica
pueden invocar el modo de emergencia en el controlador de
dispositivos. Para obtener más detalles consulte la sección de
Solución de Problemas.
Sólo FCJS-010-EM /
FCJS-ECO-EM
FCJS-010: - (Gris), + (Violeta)
FCJS-ECO: E1 (Violeta), E2 (Violeta)
PRECAUCIONES IMPORTANTES
Cuando se utilicen equipos eléctricos se deberá adoptar siempre precauciones
básicas de seguridad, entre ellas las siguientes:
LEA Y SIGA TODAS LAS
INSTRUCCIONES DE SEGURIDAD.
No utilizar al aire libre.
No montar cerca de calefactores eléctricos o de gas.
El equipo deberá montarse en lugares y alturas donde no resulte accesible a la
manipulación por personal no autorizado.
El empleo de equipos accesorios no recomendados por el fabricante podría
ocasionar una condición insegura.
No utilice este equipo para otro uso que el concebido.
GUARDE ESTAS INSTRUCCIONES
Nota importante: Para optimizar el desempeño de RF del producto:
Mantenga el cableado de la lámpara lo más corto posible para reducir
la radiación de los cables.
Mantenga el cableado de las lámparas lo más alejado posible de la
ubicación de montaje del control inalámbrico de artefactos PowPak.
Para obtener más detalles consulte la sección de Solución de Problemas.
Maximice la distancia
Tapa ciega
del control de
artefactos PowPak
Cableado del
control de
artefactos PowPak
Cableado
de la
lámpara
N
L
Tierra del
artefacto
Verde/Amarillo
Línea/vivo conmutada (rojo)
Línea/vivo (negro)
Neutro (Blanco)
Neutro
Artefacto/
Luminaria
o caja de
conexiones
Abertura con tapa
ciega de 21 mm
(1/2 pulg)
Desde la parte
trasera del sensor
Balasto /
Controlador
Normal
Tuerca del
conducto
FCJS-010: -(Gris), + (Violeta)
FCJS-ECO: E1 (Violeta), E2 (Violeta)
Restablezca los valores
predeterminados de fábrica
Nota: En algunos casos puede ser necesario restablecer la
configuración predeterminada de fábrica tanto de los controles de
artefactos como de los dispositivos conectados. Antes de comenzar,
asegúrese de que todos los dispositivos estén conectados y
energizados.
A
Pulse rápidamente tres veces el botón Encender y Apagaru en el
control de artefactos y manténgalo pulsado la cuarta vez hasta que el
LED comience a destellar lentamente; suelte el botón.
B
Dentro de los 3 segundos del comienzo del destello, pulse de nuevo
rápidamente tres veces el botón Encender y Apagar u y los LED
destellarán rápidamente, indicando que el equipo ha sido restablecido
a los valores predeterminados de fábrica.
Nota: Toda asociación o programación establecida con anterioridad
para el control de artefactos será borrada y tendrá que ser
reprogramada.
Notas:
1. Los cables de control (violeta/gris para el FCJS-010 /
FCJS-010-EM o violeta/violeta para el FCJS-ECO /
FCJS-ECO-EM) pueden ser tendidos como Clase 1 o
Clase 2.
2. Con artefactos colgantes la máxima longitud de cable
entre el sensor de artefactos y el control de artefactos es
de 3,7 m (12 pies). El sensor deberá ser montado a no
más de 0,6 m (2 pies) del artefacto.
3. Para instalar el equipo en el interior de una caja de
conexiones, consulte la Nota de aplicación 423 de Lutron
(N/P 048423) en www.lutron.com
4. Cuando no se utiliza el hub Vive, el control de artefactos
debe estar accesible para algunas etapas de programación.
Registre dónde está montado para que pueda ubicarlo
fácilmente más adelante.
5. Cuando se utilice un sensor de luz diurna Radio Powr Savr
en conjunto con tanto un control inalámbrico de artefactos
PowPak y un sensor de artefactos PowPak, el sensor de
luz diurna Radio Powr Savr proporcionará la entrada de
iluminación diurna al módulo de control, y la entrada de luz
diurna del sensor de artefactos PowPak será ignorada.
6.
Cuando se utilice un sensor de ocupación Radio Powr Savr
en conjunto tanto con un control inalámbrico de artefactos
PowPak como con un sensor de artefactos PowPak, se
utilizan los datos ocupación de ambos sensores; cualquiera
de ellos que detecte una ocupación encenderá las luces, y
éstas sólo se apagarán cuando ambos sensores pasen al
modo
de vacancia (ya no detectan ocupación).
7. Para obtener más información sobre el sensor de artefactos
PowPak
consulte: N/P 369866 o N/P 048556 en
www.lutron.com Para obtener la guía de instalación del
FC-SENSOR y FC-VSENSOR visite www.lutron.com
Información de la FCC / IC
Este dispositivo satisface la parte 15 de las reglas de la FCC y las normas RSS de exención de licencia de Industry Canada. La operación
está sujeta a las dos siguientes condiciones: (1) Este dispositivo no debe causar interferencias perjudiciales y (2) este dispositivo debe
aceptar cualquier interferencia, incluida la interferencia que pudiera ocasionar una operación no deseada. Las modificaciones no aprobadas
expresamente por Lutron Electronics Co., Inc. podrían invalidar la autorización del usuario para utilizar este equipo.
NOTA: Este equipo ha sido comprobado y se lo encontró comprendido dentro de los límites para un dispositivo digital clase B, según la
sección 15 de las reglas de la FCC. Estos límites están diseñados para proporcionar una protección razonable contra las interferencias
perjudiciales en una instalación residencial. Este equipo genera, utiliza y puede irradiar energía de radiofrecuencia, y si no se lo instala y
utiliza de acuerdo con las instrucciones podría ocasionar interferencias perjudiciales para las radiocomunicaciones. Sin embargo, no hay
garantía de que no ocurran interferencias en una instalación en particular. Si este equipo ocasionara interferencias perjudiciales para la
recepción de radio o televisión, lo que puede ser determinado encendiéndolo y apagándolo, se recomienda al usuario que intente corregir
la interferencia adoptando una o más de las siguientes medidas:
Reorientar o reubicar la antena receptora.
Aumentar la separación entre el equipo y el receptor.
Conectar el equipo a un tomacorriente que corresponda a un circuito diferente de aquel al cual está conectado el receptor.
Módulo de Atenuación PowPak
Programación sin un hub Vive
Garantía limitada:
www.lutron.com/TechnicalDocumentLibrary/369-119_Wallbox_Warranty.pdf
Ajuste de la intensidad mínima
A
Ingrese al modo de ajuste de la intensidad mínima:
Pulse y mantenga pulsado el botón Bajar
Ǻ
” del control de artefactos durante 12 segundos.
Las luces destellarán y el LED del estado de la carga comenzará a destellar.
B
Ajuste la intensidad mínima:
Utilice el botón Subir
ŷ
” y el botón Bajar
Ǻ
” del control de artefactos para ajustar y configurar
las luces al nivel de intensidad mínima deseado (1 a 45%).
C
Guarde el ajuste de la intensidad mínima:
Pulse y mantenga pulsado el botón Encender y Apagaru” durante 6 segundos para guardar la
configuración.
El LED de estado de la carga comenzará a dwestellar y luego se iluminará continuamente para
indicar que el nuevo nivel ha sido guardado.
Ajuste de la intensidad máxima
A
Ingrese al modo de ajuste de la intensidad máxima:
Pulse y mantenga pulsado el botón Subir
ŷ
” del control de artefactos durante 12 segundos. Las
luces destellarán y el LED del estado de la carga destellará.
B
Ajuste la intensidad máxima:
Utilice el botón Subir
ŷ
” y el botón Bajar
Ǻ
” del control de artefactos para ajustar y configurar
las luces al nivel de intensidad máxima deseado (55 a 100%).
C
Guarde el ajuste de la intensidad máxima:
Pulse y mantenga pulsado el botón Encender y Apagaru” durante 6 segundos para guardar
la configuración. El LED de estado de la carga comenzará a destellar y luego se iluminará
continuamente para indicar que el nuevo nivel ha sido guardado.
Configure el ajuste de las intensidades mínima y máxima
(opcional)
Para obtener los mejores resultados, minimice la cantidad de luz solar que ingresa a la
habitación antes de realizar los siguientes procedimientos.
En función del fabricante del artefacto o de la carga, podría ser necesario ajustar las intensidades
máxima y mínima.
Ajuste el intensidad mínima para asegurar un nivel estable de luz porque algunas cargas
parpadearán o caerán si se las ajusta demasiado bajas.
Asegúrese de que se pueda encender las luces al nivel de ajuste de intensidad mínima sin tener que
ejecutar ninguna operación anormal.
El ajuste de intensidad máxima predeterminado de fábrica es adecuado para la mayoría de las
aplicaciones, pero puede ajustarse como se desee.
NOTA: El ajuste de intensidad mínima e
intensidad máxima también se puede realizar
para una sola unidad o grupo de unidades
simultáneamente con un control remoto Pico.
Para obtener más información,
consulte el N/P 048556 en www.lutron.com.
Lutron, EcoSystem, Pico, PowPak, y Vive son marcas comerciales de Lutron Electronics Co., Inc., registradas en E.U.A. y en otros países. Radio Powr Savr es una marca comercial de Lutron Electronics Co., Inc. Safari es una marca comercial de Apple Inc., registrada en E.U.A. y en otros países. iOS es una marca comercial registrada de Cisco en E.U.A. y
en otros países y se utiliza bajo licencia. Google es una marca comercial registrada y Android y Chrome son marcas comerciales de Google Inc. NEC es una marca comercial de el National Fire Protection Association, Quincy, Massachusetts. ©2014 – 2018 Lutron Electronics Co., Inc.
B
Mantenga pulsado el botón indicado en cada transmisor durante 6
segundos. El artefacto destellará para mostrar que los transmisores
inalámbricos han sido asociados. Alternativamente, para los sensores
de ocupación/vacancia y luz diurna Radio Powr Savr, puede utilizarse
el puntero láser verde. Para obtener más información consulte la Nota
de aplicación Nº 407 de Lutron (N/P 048407) en www.lutron.com.
Para asociar otro transmisor, repita los pasos 1A y 1B.
Test
Link
Asocie los transmisores al control de artefactos
Antes de comenzar este paso, asegúrese de que no haya otros controles
de artefactos que estén siendo configurados en el edificio y que se
encuentren actualmente en el modo de asociación. Es posible que los
transmisores inalámbricos de otros sistemas puedan estar asociados
incorrectamente a este módulo.
O
Detección de
láser
Especificaciones del láser verde:
Salida de onda: constante
Longitud de onda: 532 nm
Potencia de salida: 5 mW maximum
Nota: El control de artefactos saldrá
automáticamente del modo de asociación
10 minutos después de la última actividad.
A
Inicie el modo de asociación en el control de artefactos de una de dos
maneras:
1 Pulse y mantenga pulsado el botón Encender y Apagaru durante
6 segundos en el control del artefacto hasta que la carga conectada al
control del artefacto comience a destellar (cada 2 segundos).
2 Alternativamente, haga brillar un puntero láser verde (disponible en
ferreterías o tiendas de suministros de oficina) sobre el orificio de
detección de láser del sensor hasta que la carga conectada al control del
artefacto comience a destellar (cada 2 segundos).
Nota: Pueden ponerse varios controles de artefactos en el modo de
asociación repitiendo uno de los dos métodos anteriores para el próximo
control de artefactos antes de continuar al Paso 1B.
!
ADVERTENCIA
!
PELIGRO
Lesiones oculares y/o peligro de ceguera; evitar la exposición directa de los ojos al rayo
láser.
Un puntero láser NO se recomienda para su uso con productos Lutron ubicados cerca de
superficies reflectantes.
NO apunte o haga brillar punteros láser sobre ninguna persona, animal, vehículo o aeronave,
ya sea directamente o a través de su reflexión por espejos u otras superficies reflectantes. NO
mire el rayo láser a través de binoculares, lupa, u otros dispositivos ópticos.
NO permita que los niños utilicen punteros láser.
Lea y respete las instrucciones del fabricante del puntero láser sobre uso seguro.
En caso de lesiones, procure atención médica inmediatamente.
Tes t
Link
Cal.
Calibre el sensor de luz diurna Radio Powr Savr
El sensor de luz diurna va a controlar todos los artefactos conectados por igual.
Comience aquí
A
Pulse y suelte el botón “Cal.” del sensor de luz diurna.
B
Configure las luces de la habitación al nivel de luz deseado.
C
Pulse y mantenga pulsado el botón “Cal.” durante 6 segundos.
D
Salga de la habitación durante 5 minutos para completar la calibración.
Nota: Cuando la calibración se haya completado, todas las luces destellarán y comenzarán a responder
a la luz diurna.
Asistencia al cliente | 1.844.LUTRON1 E.U.A., Canadá y el Caribe | +44.(0)20.7702.0657 Europa | +1.610.282.3800 Demás países | www.lutron.com/support
Parte de la familia Vive
Asistencia al cliente www.lutron.com/support
1
2
Subir
Bajar
Favorito
Configure un nivel de luz favorito (opcional)
Para los controles remotos Pico con un botón Favorito.
A
Ajuste las luces al nivel deseado:
Utilice el botón Subir
” o el botón Bajar ” del control remoto Pico.
B
Guarde el nivel favorito:
Pulse y mantenga pulsado el botón Favorito durante 6 segundos.
La carga destellará tres veces para confirmar que el nivel favorito ha sido
guardado.
3
4
Controles inalámbricos: Todas las luces
Funcionalidad predeterminada
Controles de artefactos
Nivel Automático Activado: FC-SENSOR únicamente
(no aplicable para FC-VSENSOR)
Varía con el nivel de luz ambiental cuando se dispara la ocupación
(p. ej., 100% para una habitación oscura, 10% para una habitación
iluminada).
Intervalo de espera: 15 minutos
Encendida: 100%; Favorito: 50%; Apagada: 0%
Solución de Problemas www.lutron.com/support
Síntoma Solución
Los balastos/controladores no
pueden ser controlados localmente
desde el control de artefactos.
Asegúrese de que los disyuntores al control de artefactos estén energizados.
Asegúrese de que el cable conmutado en caliente del control de artefactos esté conectado al
balasto/controlador (FCJS-010 / FCJS-010-EM).
Asegúrese de que las líneas de control del control de artefactos (FCJS-010 / FCJS-010-EM:
violeta/gris, FCJS-ECO / FCJS-ECO-EM: violeta / violeta) se conecten al balasto/controlador.
Si se utiliza el FCJS-010 / FCJS-010-EM, verifique que el controlador/balasto sea de 0 –10 V-.
Si se utiliza el FCJS-ECO / FCJS-ECO-EM, emplee el controlador/balasto Lutron EcoSystem.
Restablezca los valores predeterminados de fábrica.
Las luces no se atenúan o
ENCIENDEN como se esperaba.
Asegúrese de que las líneas de control estén cableadas correctamente (FCJS-010 / FCJS-010-EM:
violeta/gris sensible a la polaridad, FCJS-ECO / FCJS-ECO-EM: violeta / violeta)
Asegúrese de que los cables estén conectados entre el sensor de artefactos y el control de artefactos.
Sólo FCJS-010 / FCJS-010-EM: Asegúrese de que el artefacto de 0 –10 V- esté en la intensidad
mínima (a 0 V), y no APAGADO (a 0 V). Si está APAGADO (a 0 V), ajuste la intensidad mínima.
Sólo FCJS-010 / FCJS-010-EM: Asegúrese de que el artefacto no requiera una señal invertida (control
de 10 0 V-).
Sólo FCJS-010 / FCJS-010-EM: Verifique que el voltaje entre los cables gris y violeta esté entre
0 y 10 V-.
Sólo FCJS-ECO / FCJS-ECO-EM: Desconecte los cables violeta/violeta del control de artefactos.
Verifique que las luces pasen al 100%.
Sólo FCJS-010 / FCJS-010-EM: Desconecte los cables violeta/gris del control de artefactos. Verifique
que las luces pasen al 100%. Cortocircuite los cables violeta/gris en el balasto/controlador, y verifique que
las luces pasen a la intensidad mínima.
Las luces no responden a los
transmisores inalámbricos.
Asegúrese de que los disyuntores al control de artefactos y a los balastos/controladores
estén energizados.
Asegúrese de que los transmisores inalámbricos estén asociados al control de artefactos.
Restablezca los valores predeterminados de fábrica.
Los transmisores inalámbricos no
pueden ser asociados al control de
artefactos.
Ha sido asociado al control de artefactos el número máximo de transmisores inalámbricos. Para eliminar
un transmisor inalámbrico previamente configurado, pulse tres veces cualquier botón del transmisor
inalámbrico; la tercera vez manténgalo pulsado durante tres segundos y luego púlselo tres veces más.
El rango de RF entre los controles
inalámbricos está reducido por
debajo de los 9 m (30 pies).
Mantenga el cableado del balasto/controlador lo más corto posible y bien organizado para evitar que
se apretuje el exceso de cables.
Mantenga las primeras 20-30 cm (7-12 pulg) separadas lo más posible de los cables provenientes de
la tapa ciega del control de artefactos de cualquier cable de balasto/controlador/lámpara cercanos.
Para obtener detalles adicionales póngase en contacto con la Asistencia al cliente de Lutron.
Las luces son inestables a la
intensidad mínima.
Configure el ajuste de la intensidad mínima.
El sensor de artefactos no
ENCIENDE las luces.
Verifique que los cables del sensor de artefactos estén conectados al control del artefacto.
El FC-VSENSOR es de vacancia únicamente (no encenderá las luces).
El control de artefactos está en el
modo de emergencia (sólo
FCJS-010-EM y FCJS-ECO-EM).
En sistemas con un hub Vive: Para obtener detalles adicionales póngase en contacto con la
Asistencia al cliente de Lutron.
En sistemas sin un hub Vive: Espere 90 minutos para que el PowPak retorne a su operación normal.
El control de dispositivos no pasará
al modo de emergencia (sólo
FCJS-010-EM, FCJS-ECO-EM).
Para obtener detalles adicionales póngase en contacto con la Asistencia al cliente de Lutron.
Para obtener información sobre cómo activar el modo de salida, sugerencias de aplicación y muchas otras notas sobre los controles de
artefactos PowPak, consulte los documentos de Lutron 048556 o 369918 en www.lutron.com.

Transcripción de documentos

Required Components PowPak Fixture Controls Installation FCJS-010 FCJS-010-EM 0 –10 V- 120 – 277 V~ 50 / 60 Hz 1 A switching FCJS-ECO FCJS-ECO-EM Lutron EcoSystem 120 – 277 V~ 50 / 60 Hz 1 A switching PIR Lens Laser Detection Daylight Lens Raise Load Status LED Toggle + 6 mA sink/source Lower 14 V- 6 mA PowPak Wireless Fixture Control UL 2043 Plenum Rated UL 924 Listed (FCJS-010-EM / FCJS-ECO-EM) Controls up to 3 ballasts or drivers (IEC 60929 Annex E.2 requires each ballast or driver to limit the sink/source current draw to 2.0 mA maximum). Provides IEC SELV / NECR Class 2, 12 V-, 25 mA to a PowPak fixture sensor (FC-SENSOR or FC-VSENSOR). PowPak Fixture Sensor (FC-SENSOR or FC-VSENSOR) PowPak Wireless Fixture Control (FCJS-010 / FCJS-010-EM or FCJS-ECO / FCJS-ECO-EM) Consult the fixture installation guide for fixture wiring. For mounting and wiring best practices see Lutron Application Note #620 (P/N 048620). Notes: 1. Fixture control can be used without a fixture sensor as long as at least one Radio Powr Savr sensor or Pico remote control is used. + 2. Only one fixture control can be used per fixture sensor, and only one fixture sensor can be used per fixture control. Radio Powr Savr Occupancy/Vacancy Sensor (1 maximum) 1 Install Fixture Control and Optional Fixture Sensor Line/Hot (Black) 1/2 in (21 mm) Knockout Opening Fixture Earth N Switched Line/Hot (Red) L Normal Driver / Ballast Conduit Nut FCJS-010: – (Gray), + (Violet) FCJS-ECO: E1 (Violet), E2 (Violet) the adhesive strip (included). The two communication wires from the sensor attach to the fixture control stab-in connectors. The wires are interchangeable to eliminate miswiring. Note: For FC-SENSOR and FC-VSENSOR installation guide visit www.lutron.com B Once installed, energize the control module. The fixture will turn on. Important Note: To optimize RF performance of the product: – Keep the lamp wiring as short as possible to reduce the radiation from the lamp wires. – Keep the lamp wiring as far as possible from the PowPak Wireless Fixture Control mounting location. See the Troubleshooting section for more details. PowPak Fixture Control Wiring Maximize Distance From back of sensor PowPak Fixture Control Knockout 6 mA maximum for the control lines. Switches up to 1 A total (or maximum 3 ballasts or drivers). May be pre-installed in fixture. Note: All drivers and ballasts used with Vive wireless controls must comply with the limits for a Class A device, pursuant to Part 15 of the FCC rules. Line/Hot (Black) Fixture Control Green/Yellow Neutral (White) Neutral Fixture/ Troffer or Junction Box 120 / 277 V~ Normal Feed Pico remote control Neutral Regular Utility Power 120 / 277 V~ Generator / Emergency Feed Wireless sensors and controls must be located within 60 ft (18 m) line of sight, or 30 ft (9 m), through walls, of the associated control module. Automatic Transfer Switch 120 / 277 V~ Emergency Feed Fixture Earth N Switched Line/Hot (Red) L Emergency Driver / Ballast 1/2 in (21 mm) Knockout Opening Neutral Conduit Nut Note: For periodic testing and maintanance of emergency systems, use the toggle button of the FCJS-010-EM / FCJS-ECO-EM to ensure proper operation. Make sure PowPak buttons remain accessible. Note: Momentary power outages can envoke emergency mode on the fixture controller. See Troubleshooting section for details. FCJS-010-EM / FCJS-ECO-EM only From back of sensor Emergency Backup Generator 2 Programming with a Vive Hub A Use an iOS® or Android® compatible device. B Download the Lutron Vive app. C Open the app and follow the instructions. vive.lutron.com Vive X 1. Control wires (Violet/Gray for FCJS-010 / FCJS-010-EM or Violet/Violet for FCJS-ECO / FCJS-ECO-EM) can be run as either Class 1 or Class 2. 2. If hanging pendant fixtures the maximum wire length between fixture sensor and fixture control is 12 ft (3.7 m). Sensor should be mounted no more than 2 ft (0.6 m) from the fixture. FCJS-010-EM: – (Gray), + (Violet) FCJS-ECO-EM: E1 (Violet), E2 (Violet) When using electrical equipment, basic safety precautions should always be followed including the following: Note: In some instances, it may be necessary to reset the fixture controls and connected devices back to factory default settings. Before beginning, make sure that all devices are connected and powered. A Rapidly tap the Toggle button “ u” on the fixture control three times and hold on the fourth until the LED begins to flash slowly; release button. B Within 3 seconds of the start of flashing, again rapidly tap the Toggle button “ u” three times and the LEDs will flash rapidly indicating that the unit has been reset to factory defaults. Note: Any associations or programming previously set up with the fixture control will be erased and will need to be re-programmed. 3. To install unit inside a junction box, please see Lutron Application Note #423 (P/N 048423) on www.lutron.com Neutral IMPORTANT SAFEGUARDS Reset Factory Defaults Notes: Lamp Wiring Sensor Lutron Electronics Co., Inc. 7200 Suter Road Coopersburg, PA 18036-1299 USA Fixture/ Troffer or Junction Box A Ideally, mount the sensor to the ceiling tile close to the fixture using the wireform or using Install the fixture control directly to a fixture or on a junction box nearest to the fixture. Install the sensor on the ceiling near the fixture to optimize coverage in the desired area. For more information please refer to Lutron P/N 369918 at www.lutron.com Green/Yellow Neutral The fixture control can be installed on a fixture/troffer, junction box or marshalling box using the conduit nut (provided) or with mounting screws (not provided). Product must NOT be mounted inside a fixture - only on the exterior of a fixture. Please consult local and national electric codes for proper installation. PowPak Fixture Control SAVE THESE INSTRUCTIONS (10 maximum) Neutral (White) WARNING! Shock Hazard. May result in serious injury or death. Turn off power at circuit breaker before installing the unit. Important Notes: Please read before installing. • Do not use outdoors. • Do not mount near gas or electric heaters. • Equipment should be mounted in locations and at heights where it will not be subjected to tampering by unauthorized personnel. • The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition. • Do not use this equipment for other than its intended use. (1 maximum) Pico Remote Control (10 maximum) Suggested Installation Location: Close to the Fixture / Troffer. • For installation by a qualified electrician in accordance with all local and national electrical codes (including periodic testing and maintenance of emergency systems). • Use copper conductors only. • Check to see that the device type and rating is suitable for the application. • DO NOT install if product has any visible damage. • If moisture or condensation is evident, allow the product to dry completely before installation. • Operate between 32 °F and 104 °F (0 °C and 40 °C), ambient. • 0% to 90% humidity, non-condensing. • For indoor use only. READ AND FOLLOW ALL SAFETY INSTRUCTIONS. Radio Powr Savr Daylight Sensor Start Here Note for Replacement: FCJS - the "S" model can replace the non-"S" model 30 ft (9 m) maximum www.lutron.com/support FCJS-010 / FCJS-010-EM: At least one 0 –10 V- Fluorescent Ballast or LED Driver FCJS-ECO / FCJS-ECO-EM: At least one Lutron EcoSystem Ballast or LED Driver At least one of these transmitters (22 total allowed) One Fixture Control 041645 Rev. A 03/2018 Part of the Vive Family English Customer Assistance For each fixture, you will need: X Note: For further information on set up, programming, and troubleshooting with a Vive system, please refer to the installation instructions included with the Vive hub or visit www.lutron.com/vive Note: For programming the PowPak Fixture Control Module without a Vive hub see the reverse side. 4. When not using the Vive Hub, the fixture control needs to be accessible for some programming steps. Record where it is mounted so that it can be easily located later. 5. When using a Radio Powr Savr daylight sensor in conjunction with both a PowPak wireless fixture control and PowPak fixture sensor, the Radio Powr Savr daylight sensor will provide the daylighting input to the control module, and the PowPak fixture sensor daylighting input will be ignored. 6. When using a Radio Powr Savr occupancy sensor in conjunction with both a PowPak wireless fixture control and PowPak fixture sensor, occupancy data from both sensors is used; either one detecting occupancy will turn the lights on, and the lights turn off only when both sensors have gone vacant (no longer detect occupancy). 7. For more information on the PowPak fixture sensor, see: P/N 369866 or P/N 048556 on www.lutron.com For FC-SENSOR and FC-VSENSOR installation guide visit www.lutron.com PowPak Fixture Controls Programming without a Vive Hub Customer Assistance 2 Part of the Vive Family Daylight Sensor will control all wired fixtures equally. Start Here 1 4 Calibrate the Radio Powr Savr Daylight Sensor A Press and release the “Cal.” button on the Daylight Sensor. Note: Multiple fixture controls can be placed into association mode by repeating one of the two above methods for the next fixture control prior to moving to Step 1B. For best results, minimize the amount of sunlight entering the room before performing the following procedures. Depending on the fixture manufacturer or load, low-end trim and high-end trim may need to be adjusted. C Press and hold the “Cal.” button for 6 seconds. Before beginning this step, make sure that there are no other fixture controls being set up in the building which are currently in association mode. It is possible that wireless transmitters from other systems can be incorrectly associated to this module. Set Low-End Trim and High-End Trim (Optional) Test B Set lights in room to desired light level. Associate Transmitters to Fixture Control A Initiate association mode on the fixture control in one of two ways: 1 Press and hold the Toggle button “ u ” for 6 seconds on the fixture control until the load attached to the fixture control starts flashing (every 2 seconds). 2 Alternatively, shine a green laser pointer (available at hardware or office supply stores) at the laser detection hole on the sensor until the load attached to the fixture control starts flashing (every 2 seconds). Cal. Link www.lutron.com/support D Exit room for 5 minutes to complete calibration. • Trim low-end to ensure a stable light level because some loads will flicker or drop out if trimmed too low. Note: When calibration has completed, all lights will flash and begin to respond to daylight. • Be sure that you can turn on the lights to the low-end trim level without any abnormal operation. • The factory default high-end trim is suitable for most applications but can be adjusted as desired. 3 Set a Favorite Light Level (Optional) For Pico remote controls with a Favorite Button. Raise Lower A Adjust lights to desired level: Use the Raise button “ ” or Lower button “ NOTE: High-end and low-end trim can also be performed for a single unit or group of units simultaneously with a Pico remote control. ” on the Pico remote control. B Save favorite level: Press and hold the Favorite button for 6 seconds. The load will flash 3 times to confirm that the Favorite level is saved. For more information see P/N 048556 on www.lutron.com. Favorite Laser Detection OR WARNING ! DANGER Eye injury and/or blindness hazard; avoid direct eye exposure to laser beam. • Use of laser pointer is NOT recommended for use with Lutron products located near reflective surfaces. • DO NOT aim or shine laser pointers at any person, pet, vehicle, or aircraft directly, or through reflection by mirrors or other shiny surfaces. DO NOT view the laser beam through binoculars magnifying glass, or other optical devices. • DO NOT allow children to use laser pointers. • Read and follow the laser pointer manufacturer’s instructions on safe use. In the event of injury, get medical attention immediately. B Hold the indicated button on each transmitter for 6 seconds. The fixture will flash to show that wireless transmitters have been associated. Alternatively, for Radio Powr Savr occupancy / vacancy and daylight sensors, the green laser pointer can be used. See Lutron Application Note #407 (P/N 048407) on www.lutron.com for more information. To associate another transmitter, repeat steps 1A and 1B. Link Test Default Functionality Wireless Controls: All lights On: 100% ; Favorite: 50%; Off: 0% Fixture Controls Auto On level: FC-SENSOR only (not applicable for FC-VSENSOR) Varies with ambient light level when occupancy is triggered (e.g., 100% for a dark room, 10% for a bright room). Timeout period: 15 minutes Solution • Ensure that the breaker(s) to the fixture control are energized. • Ensure that the fixture control switched hot lead is wired to the ballast / driver (FCJS-010 / FCJS-010-EM). • Ensure that the fixture control control lines (FCJS-010 / FCJS-010-EM: violet/gray, FCJS-ECO / Ballasts / drivers cannot be controlled FCJS-ECO-EM: violet/violet) are wired to the ballast / driver. locally from the fixture control. • If using FCJS-010 / FCJS-010-EM, verify the driver/ballast is 0 –10 V-. If using FCJS-ECO / FCJS-ECO-EM, use the Lutron EcoSystem driver/ballast. Reset to factory defaults. • Ensure that control lines are wired properly (FCJS-010 / FCJS-010-EM: violet/gray-polaritysensitive, FCJS-ECO / FCJS-ECO-EM: violet/violet) • Ensure that the wires are connected between the fixture sensor and the fixture control. • FCJS-010 / FCJS-010-EM only: Make sure that 0 –10 V- fixture is at low-end (at 0 V), not OFF (at 0 V). If OFF (at 0 V), adjust low-end trim. • FCJS-010 / FCJS-010-EM only: Ensure that fixture does not require an inverted signal Lights do not dim or turn ON as (10 – 0 V- control). • FCJS-010 / FCJS-010-EM only: Verify that the voltage across the gray and violet wires is between expected. 0 and 10 V-. • FCJS-ECO / FCJS-ECO-EM only: Disconnect the violet / violet wires from the fixture control. Verify that the lights go to 100%. • FCJS-010 / FCJS-010-EM only: Disconnect the violet / gray wires from the fixture control. Verify that the lights go to 100%. Short the violet / gray wires on the ballast / driver, verify that the lights go to low-end. • Ensure that the breaker(s) to the fixture control and ballasts / drivers are energized. Lights do not respond to wireless • Ensure that wireless transmitters are associated to the fixture control. transmitter(s). Reset to factory defaults. • The maximum number of wireless transmitters have been associated to the fixture control. To Wireless transmitter(s) cannot be remove a previously set up wireless transmitter, tap any button on the wireless transmitter three associated to the fixture control. times; on the third tap, hold for three seconds and then tap three more times. • Keep the ballast/driver wiring as short as possible and well organized to avoid excess wire being bunched up. RF range between wireless controls • Keep the first 7 in –12 in (20 cm –30 cm) of the wires coming out of the fixture control knockout is diminished below 30 ft (9 m). separated as much as possible from any nearby ballast/driver/lamp wires. • Contact Lutron Customer Assistance for further details. Lights are unstable at low-end. • Adjust low-end trim. Fixture sensor does not turn the lights • Check that fixture sensor wires are connected to fixture control. • FC-VSENSOR is vacancy only (it will not turn the lights on). ON. Fixture control is in emergency mode • In systems with a Vive hub: Contact Lutron Customer Assistance for further details. (FCJS-010-EM, FCJS-ECO-EM only). • In systems without a Vive hub: Wait 90 minutes for the PowPak to return to normal operation. • Contact Lutron Customer Assistance for further details. Fixture control will not go into emergency mode (FCJS-010-EM, FCJS-ECO-EM only). For information on activating egress mode, application suggestions, and many other notes on the PowPak fixture controls, see Lutron document 048556 or 369918 on www.lutron.com. Low-End Trim A Enter low-end trim adjustment mode: Press and hold the Lower button “ ” on the fixture control for 12 seconds. The lights will flash and the load status LED will begin flashing. B Adjust the low-end trim: Use the Raise button “ŷ” and Lower button “ ” on the fixture control to adjust and set the lights to the desired low-end (1 to 45%). C Save the low-end trim: Press and hold the Toggle button “ u” for 6 seconds to save setting. The load status LED will begin flashing and then turn solid to indicate new level has been saved. High-End Trim A Enter high-end trim adjustment mode: Press and hold the Raise button “ŷ” on the fixture control for 12 seconds. The lights will flash and the load status LED will flash. B Adjust the high-end trim: Use the Raise button “ŷ” and Lower button “ ” on the fixture control to adjust and set the lights to the desired high-end (55 to 100%). C Save the high-end trim: Press and hold the Toggle button “ u” for 6 seconds to save setting. The load status LED will begin flashing and then turn solid to indicate new level has been saved. Ǻ ! Symptom www.lutron.com/support Ǻ Note: The fixture control will automatically exit association mode 10 minutes after the last activity. Troubleshooting Ǻ Green laser specifications: • Wave output: constant • Wavelength: 532 nm • Output power: 5 mW maximum Limited Warranty: www.lutron.com/TechnicalDocumentLibrary/369-119_Wallbox_Warranty.pdf FCC / IC Information This device complies with part 15 of the FCC Rules and Industry Canada license-exempt RSS standard(s). Operation is subject to the following two conditions: (1) This device may not cause interference, and (2) this device must accept any interference, including interference that may cause undesired operation. Modifications not expressly approved by Lutron Electronics Co., Inc. could void the user’s authority to operate this equipment. NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: • Re-orient or relocate the receiving antenna. • Increase the separation between the equipment and receiver. • Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. Customer Assistance | 1.844.LUTRON1 U.S.A., Canada, and the Caribbean | +44.(0)20.7680.4481 Europe | +1.610.282.3800 Others | www.lutron.com/support Lutron, EcoSystem, Pico, PowPak, and Vive are trademarks of Lutron Electronics Co., Inc., registered in the U.S. and other countries. Radio Powr Savr is a trademark of Lutron Electronics Co., Inc. Safari is a trademark of Apple Inc., registered in the U.S. and other countries. iOS is a registered trademark of Cisco in the U.S. and other countries and is used under license. Google is a registered trademark and Android and Chrome are trademarks of Google Inc. NEC is a registered trademark of the National Fire Protection Association, Quincy, Massachusetts. ©2014 – 2018 Lutron Electronics Co., Inc. Commandes de luminaires PowPak Installation Commutation 120 – 277 V~ 50 / 60 Hz 1 A Courant de source/absorbé 6 mA Commande de luminaire PowPak Conformité plénum de la norme UL 2043 Certifié UL 924 (FCJS-010-EM / FCJS-ECO-EM) Commande jusqu’à 3 ballasts ou pilotes (la norme IEC 60929 Annexe E.2 exige que chaque ballast ou pilote limite le courant de source/absorbé à 2,0 mA au maximum). Fournit une alimentation IEC SELV / NECR de classe 2 de 12 V-, 25 mA à un détecteur de luminaire PowPak (FC-SENSOR ou FC-VSENSOR). Alterner + Détecteur de luminaire PowPak (FC-SENSOR ou FC-VSENSOR) Commande de luminaire sans fil PowPak (FCJS-010 / FCJS-010-EM ou FCJS-ECO / FCJS-ECO-EM) 1 2. Une seule commande de luminaire peut être utilisée par détecteur de luminaire et un seul détecteur de luminaire peut être utilisé par commande de luminaire. Installer la commande de luminaire et le détecteur de luminaire optionnel A B La commande de luminaire peut être installée sur un luminaire / plafonnier, dans un boîtier de raccordement ou un boîtier de regroupement avec l’écrou de conduit (fourni) ou des vis de montage (non fournies). Le produit NE DOIT PAS être monté à l’intérieur d’un luminaire - seulement à l’extérieur d’un luminaire. Veuillez consulter les codes électriques en vigueur pour une installation correcte. Si possible, montez le détecteur sur une dalle de plafond à proximité du luminaire au moyen du fil ou de la bande adhésive (inclus). Reliez les deux fils de communication du détecteur aux fiches de connexion de la commande de luminaire. Les fils sont interchangeables pour éviter un mauvais câblage. Remarque : Pour le guide d’installation du FC-SENSOR et du FC-VSENSOR, consultez www.lutron.com Une fois installé, mettez le module de commande sous tension. Le luminaire s’allumera. Remarque importante : Pour optimiser les performances de radiofréquences du produit : – Réduisez la longueur du câblage de la lampe au maximum pour réduire le rayonnement des fils de la lampe. Maximisez la distance – Gardez le câblage de la lampe aussi loin que possible de l’emplacement du montage de la commande de luminaire sans fil PowPak. Voir la section Dépannage pour plus d’informations. Commande de luminaire PowPak Installez la commande de luminaire directement sur un luminaire ou un boîtier de raccordement près du luminaire. Installez le détecteur au plafond près du luminaire pour optimiser sa portée dans la zone souhaitée. (1 maximum) Ligne / Phase (Noir) Télécommande Pico (10 maximum) Neutre (Blanc) Neutre Entrée à perforer de 21 mm (1/2 po) Luminaire / plafonnier ou boîtier de raccordement N Ligne/Phase commuté (Rouge) Générateur / Alimentation de secours de 120 / 277 V~ Commutateur de transfert automatique Neutre FCJS-010 : - (Gris), + (Violet) FCJS-ECO : E1 (Violet), E2 (Violet) Depuis l’arrière du détecteur Câblage de lampe Terre de l’applique Vert/Jaune Neutre (Blanc) Luminaire / plafonnier ou boîtier de raccordement N Ligne/Phase commuté (Rouge) L Ballast / Pilote de secours Entrée à perforer de 21 mm (1/2 po) Écrou de conduit Neutre L Ballast / Pilote Normal Écrou de conduit Perforation de la commande de luminaire PowPak Alimentation de secours de 120 / 277 V~ Neutre Alimentation de service régulière Terre de l’applique Vert/Jaune Neutre Les détecteurs sans fil et les commandes doivent se situer à moins de 18 m (60 pi) en ligne directe du module de commande associé ou à moins de 9 m (30 pi) à travers les murs. FCJS-010 : - (Gris), + (Violet) FCJS-ECO : E1 (Violet), E2 (Violet) Remarque : Pour le contrôle et l’entretien périodiques des systèmes de secours, utilisez le bouton à bascule du FCJS-010-EM / FCJS-ECO-EM pour garantir le bon fonctionnement. Assurez-vous que les boutons du PowPak restent accessibles. CONSIGNES DE SÉCURITÉ IMPORTANTES Générateur de secours 2 FCJS-010-EM / FCJS-ECO-EM seulement Remarque : Les coupures de courant momentanées peuvent déclencher le mode de secours sur la commande de luminaire. Voir la section Dépannage pour plus d’informations. Lorsque vous utilisez des appareils électriques, il est important de toujours respecter les consignes de sécurité élémentaires, notamment : Lutron Electronics Co., Inc. 7200 Suter Road Coopersburg, PA 18036-1299 É.-U. (10 maximum) Alimentation normale de 120 / 277 V~ Télécommande Pico Pour plus d’informations veuillez vous reporter au n° de pièce 369918 de Lutron sur www.lutron.com Détecteur de lumière du jour Radio Powr Savr Ligne / Phase (Noir) Commande de luminaire CONSERVEZ CES CONSIGNES Détecteur d’occupation/ inoccupation Radio Powr Savr Câblage de la commande de luminaire PowPak Détecteur • N’utilisez pas cet équipement à l’extérieur. • Ne l’installez pas à proximité de radiateurs électriques ou au gaz. • L’équipement doit être installé dans des endroits et à des hauteurs où il ne sera pas manipulé par des personnes non-autorisées. • L’utilisation d’accessoires non recommandés par le fabricant peut provoquer une situation dangereuse. • N’utilisez pas cet appareil pour d’autres fins que celles prévues. + Emplacement recommandé pour l’installation : Près d’un luminaire / plafonnier. AVERTISSEMENT ! Risque d’électrocution. Peut causer des blessures graves ou la mort. Coupez l’alimentation au niveau du disjoncteur avant d’installer l’unité. • À faire installer par un électricien qualifié conformément à tous les codes électriques locaux et nationaux (y compris pour le contrôle et l’entretien périodiques des systèmes de secours). • N’utilisez que des conducteurs en cuivre. • Veillez à ce que le type d’appareil et sa caractéristique nominale conviennent à l’application. • Ne l’installez PAS si le produit présente des dommages visibles. • Si de l’humidité ou de la condensation est apparente, laissez le produit sécher avant son installation. • Fonctionne de 0 °C à 40 °C (32 °F à 104 °F), température ambiante. • 0 à 90 % d’humidité, sans condensation. • Utilisation à l’intérieur uniquement. LISEZ ET RESPECTEZ TOUTES LES CONSIGNES DE SÉCURITÉ. Consultez le guide d’installation du luminaire pour le câblage du luminaire. Pour les meilleures pratiques de montage et de câblage, consultez la note d’application 620 (no de pièce 048620) de Lutron. Remarques : 1. La commande de luminaire peut être utilisée sans détecteur de luminaire à condition qu’au moins un détecteur Radio Powr Savr ou une télécommande Pico est utilisé. 6 mA maximum pour les lignes de commande. Commute jusqu’à 1 A au total (ou 3 ballasts ou pilotes maximum). Peut être préinstallé dans un luminaire. Remarque : Tous les pilotes et ballasts utilisés avec les commande Vive sans fil doivent être conformes aux limites d’un appareil de Classe A en vertu de la partie 15 des règles de la FCC. Commencez ici Remarques importantes : Veuillez lire avant l’installation. 9 m (30 pi) maximum FCJS-ECO / FCJS-ECO-EM: Au moins un pilote de DEL ou ballast EcoSystem de Lutron (1 maximum) Remarque pour les remplacements : FCJS - le modèle « S » peut remplacer le modèle non-« S » Français Lentille PIR Détection Lentille de du laser lumière du jour Monter DEL d’état de la charge www.lutron.com/support FCJS-010 / FCJS-010-EM: Au moins un ballast fluorescent ou un pilote de DEL de 0 –10 V- Au moins un de ces transmetteurs (22 permis au total) Une commande de luminaire Baisser FCJS-ECO Commutation 120 – 277 V~ 50 / 60 Hz 1 A FCJS-ECO-EM 14 V- 6 mA EcoSystem de Lutron Assistance à la clientele Pour chaque luminaire, vous aurez besoin de : 041645 Rev. A 03/2018 Appartient à la famille Vive FCJS-010 FCJS-010-EM 0 –10 V- Composants requis Depuis l’arrière du détecteur Programmation avec un hub Vive A Utilisez un appareil compatible avec iOS® ou Android®. B Téléchargez l’application Vive de Lutron. C Ouvrez l’application et suivez les instructions. vive.lutron.com Vive X X Remarque : Pour plus d’information sur la configuration, la programmation et le dépannage avec un système Vive, veuillez vous reporter aux instructions d’installation fournies avec le hub Vive ou consultez www.lutron.com/vive Remarque : Pour programmer le module de commande de luminaire PowPak sans hub Vive, consultez le verso. Restaurer les réglages d’usine Remarque : Dans certains cas, il peut être nécessaire de réinitialiser les commandes de luminaires et les appareils raccordés à leurs réglages d’usine par défaut. Avant de démarrer, vérifiez que tous les appareils sont raccordés et alimentés. A Appuyez trois fois rapidement sur le bouton de Alterner « u» sur la commande de luminaire et maintenez-le enfoncé la quatrième fois jusqu’à ce que la DEL commence à clignoter lentement ; relâchez le bouton. B Après 3 secondes de clignotement, rappuyez sur le bouton de Alterner «u» trois fois rapidement et les DEL clignoteront rapidement, indiquant que les réglages d’usine de l’unité ont été restaurés. Remarque : Toute association ou programmation configurée précédemment avec la commande de luminaire sera perdue et devra être reprogrammée. Remarques : 1. Les fils de commande (Violet/Gris pour le FCJS-010 ou Violet/Violet pour le FCJS-ECO) peuvent être de classe 1 ou de classe 2. 2. En cas d’utilisation de luminaire suspendu, la longueur maximale du fil entre le détecteur de luminaire et la commande de luminaire est de 3,7 m (12 pi). Le détecteur doit être monté à moins de 0,6 m (2 pi) du luminaire. 3. Pour installer l’unité dans un boîtier de raccordement, veuillez consulter la note d’application 423 (no de pièce 048423) de Lutron sur www.lutron.com 4. Si le hub Vive n’est pas utilisé, la commande de luminaire doit être accessible pour certaines étapes de programmation. Documentez où elle est montée de façon à la localiser facilement ultérieurement. 5. En cas d’utilisation d’un détecteur de lumière du jour Radio Powr Savr en conjonction avec une commande de luminaire sans fil PowPak et un détecteur de luminaire PowPak, le détecteur de lumière du jour Radio Powr Savr fournit les données de la lumière du jour au module de commande, et les données de lumière du jour du détecteur de luminaire PowPak sont ignorées. 6. En cas d’utilisation d’un détecteur d’occupation Radio Powr Savr en conjonction avec une commande de luminaire sans fil PowPak et un détecteur de luminaire PowPak, les données d’occupation des deux détecteurs sont utilisées ; toute détection d’occupation de l’un d’entre eux allume les lumières, et les lumières s’éteignent seulement quand les deux détecteurs sont en mode d’inoccupation (ils ne détectent plus d’occupation). 7. Pour plus d’informations concernant le détecteur de luminaire PowPak, consultez: no de pièce 369866 ou no de pièce 048556 sur www.lutron.com Pour le guide d’installation du FC-SENSOR et FC-VSENSOR consultez www.lutron.com Commandes de luminaires PowPak Programmation sans hub Vive Assistance à la clientele 2 4 Étalonner le détecteur de lumière du jour Radio Powr Savr Appartient à la famille Vive Le détecteur de lumière du jour commandera toutes les appliques câblées de façon égale. Commencez ici Cal. Link www.lutron.com/support Ajuster le réglage du seuil bas et le réglage du seuil haut (optionnel) Pour de meilleurs résultats, minimisez la quantité de lumière du soleil pénétrant dans la pièce avant de réaliser les procédures suivantes. Test A B C D Associer des transmetteurs à la commande de luminaire 1 Avant d’entamer cette étape, veillez à ce qu’aucune autre commande de luminaire en phase de configuration dans le bâtiment ne soit actuellement en mode d’association. Les transmetteurs sans fil d’autres systèmes peuvent s’associer à ce module de façon incorrecte. A Démarrez le mode d’association sur la commande de luminaire de l’une de ces deux façons : 1 Appuyez et maintenez le bouton de Alterner « u » enfoncé pendant 6 secondes sur la commande de luminaire jusqu’à ce que la charge liée au module de commande commence à clignoter (toutes les 2 secondes). 2 De façon alternative, dirigez le pointeur laser vert (disponible dans les magasins de bricolage ou de fournitures de bureau) allumé sur le trou de détection de laser du détecteur jusqu’à ce que la charge liée à la commande de luminaire commence à clignoter (toutes les 2 secondes). Remarque : Plusieurs commandes de luminaires peuvent être placées en mode d’association en répétant l’une des deux méthodes ci-dessus pour la commande de luminaire suivante avant de passer à l’étape 1B. 3 Appuyez et relâchez le bouton « Cal. » sur le détecteur de lumière du jour. Réglez les lumières dans la pièce au niveau souhaité. Appuyez et maintenez le bouton « Cal. » enfoncé pendant 6 secondes. Quittez la pièce pendant 5 minutes pour effectuer l’étalonnage. Remarque : Une fois l’étalonnage effectué, toutes les lumières clignoteront et commenceront à réagir à la lumière du jour. Selon le fabricant de l’applique ou de la charge, il peut être nécessaire d’ajuster les seuils haut et bas. • Réglez le seuil bas pour assurer un niveau de lumière stable car certaines charges peuvent clignoter ou s’éteindre si le réglage est trop bas. • Vérifiez que vous pouvez régler les lumières au niveau du seuil bas sans fonctionnement anormal. • Le réglage d’usine du seuil haut convient à la plupart des applications mais peut être réglé comme vous le souhaitez. Définir un niveau de luminosité favori (optionnel) Pour les télécommandes Pico avec un bouton Favoris. A Réglez les lumières au niveau souhaité : Utilisez le bouton Monter « » ou le bouton Baisser « télécommande Pico. Monter Baisser REMARQUE : Seuils hauts et seuils bas peuvent également être effectués pour une seule unité ou groupe d’unités simultanément avec une télécommande Pico. » sur la B Enregistrez le niveau favori : Appuyez et maintenez le bouton Favoris enfoncé pendant 6 secondes. La charge clignotera 3 fois pour confirmer la sauvegarde du niveau favori. Favoris Pour plus d’informations, voir le no de pièce 048556 sur www.lutron.com Détection du laser OU • • • • Blessure aux yeux et/ou risque d’aveuglement ; évitez une exposition oculaire directe au faisceau du laser. L’utilisation d’un pointeur laser n’est PAS recommandée avec les produits Lutron situés près de surfaces réfléchissantes. NE PAS diriger ou faire briller les pointeurs laser vers une personne, un animal, un véhicule, ou un avion directement ou par réflexion par le biais de miroirs ou autres surfaces brillantes. NE PAS regarder le faisceau du laser avec des jumelles, une loupe ou tout autre appareil optique. NE PAS autoriser les enfants à utiliser les pointeurs laser. Lisez et suivez les instructions du fabricant du pointeur laser concernant leur utilisation en toute sécurité. En cas de blessure, consulter un médecin immédiatement. Les ballasts / pilotes ne peuvent pas être commandés localement depuis la commande de luminaire. Link Test Fonctionnalité par défaut Commandes sans fil : Toutes les lumières Allumé : 100 % ; Favori : 50 % ; Éteint : 0 % Commandes de luminaires Niveau d’allumage automatique : FC-SENSOR seulement (pas applicable pour le FC-VSENSOR) Varie avec le niveau de lumière ambiante lorsque l’occupation se déclenche (ex. : 100 % dans une pièce sombre, 10 % dans une pièce lumineuse). Période de délai d'extinction : 15 minutes • Vérifiez que le(s) disjoncteur(s) de la commande de luminaire sont sous tension. • Vérifiez que le conducteur commuté de la commande de luminaire est raccordé au ballast/pilote (FCJS-010 / FCJS-010-EM). • Vérifiez que les lignes de commande (FCJS-010 / FCJS-010-EM: violet/gris FCJS-ECO / FCJS-ECO-EM: violet/violet) de la commande de luminaire sont raccordées au ballast / pilote • Si vous utilisez le FCJS-010 / FCJS-010-EM, vérifiez que le ballast / pilote est de 0 –10 V-. Si vous utilisez le FCJS-ECO / FCJS-ECO-EM, utilisez le ballast / pilote EcoSystem de Lutron. Restaurer les réglages d'usine. Les lumières ne se tamisent ou ne s’allument pas comme prévu. B Maintenez le bouton indiqué enfoncé sur chaque transmetteur pendant 6 secondes. Le luminaire clignotera indiquant que les transmetteurs sans fil ont été associés. De façon alternative, pour les détecteurs d’occupation/ inoccupation et de lumière du jour Radio Powr Savr, le pointeur laser vert peut être utilisé. Voir la note d’application 407 (no de pièce 048407) de Lutron sur www.lutron.com pour plus d’informations. Pour associer un autre transmetteur, répétez les étapes 1A et 1B. Solution • Vérifiez que les lignes de commande sont raccordées correctement (FCJS-010 / FCJS-010-EM: violet/gris sensibles à la polarité, FCJS-ECO / FCJS-ECO-EM: violet/violet) • Vérifiez que les fils sont raccordés entre le détecteur de luminaire et la commande de luminaire. • FCJS-010 / FCJS-010-EM seulement : Assurez-vous que le luminaire de 0 –10 V- est au seuil bas (à 0 V), pas éteint (à 0 V). S’il est éteint (à 0 V), réglez le seuil bas. • FCJS-010 / FCJS-010-EM seulement : Vérifiez que le luminaire ne nécessite pas un signal inversé (commande de 10 – 0 V-). • FCJS-010 / FCJS-010-EM seulement : Vérifiez que la tension entre les fils gris et violet se situe entre 0 et 10 V-. • FCJS-ECO / FCJS-ECO-EM seulement : Déconnectez les fils violet / violet de la commande de luminaire. Vérifiez que les lumières vont à 100 %. • FCJS-010 / FCJS-010-EM seulement : Déconnectez les fils violet / gris de la commande de luminaire. Vérifiez que les lumières vont à 100 %. Court-circuitez les fils violet / gris sur le ballast / pilote, vérifiez que les lumières se règlent à leur seuil bas. • Vérifiez que le(s) disjoncteur(s) de la commande de luminaire et les ballasts / pilotes sont sous tension. Les lumières ne répondent pas au(x) • Vérifiez que les transmetteurs sans fil sont associés à la commande de luminaire. transmetteur(s) sans fil. Restaurer les réglages d'usine. Les transmetteurs sans fil ne peuvent • Le nombre maximal de transmetteurs sans fil a été associé à la commande de luminaire. Pour supprimer un transmetteur sans fil précédemment configuré, appuyez trois fois sur n’importe pas être associés à la commande de quel bouton du transmetteur sans fil ; à la troisième pression, maintenez-le enfoncé pendant trois luminaire. secondes, puis appuyez trois fois de nouveau. Réduisez et organisez le câblage du ballast/pilote au maximum pour éviter l’enchevêtrement des La portée des radiofréquences entre longueurs de fil excessives. les commandes sans fil est réduite • Veuillez à ce que les premiers 20-30 cm (7-12 po) de fils sortant de l’entrée à perforer de la commande de en-dessous de 9 m (30 pi). luminaire soit séparés autant que possible des fils des ballasts/pilotes/lampes environnants. • Contactez l’assistance à la clientèle de Lutron pour plus de détails. Les lumières sont instables à leur seuil bas. Le détecteur de luminaire n’allume pas les lumières. La commande de luminaire est en mode de secours (FCJS-010-EM, FCJS-ECO-EM seulement). • Ajustez le réglage du seuil bas. • • • • Vérifiez que les fils du détecteur de luminaire sont raccordés à la commande de luminaire. Le FC-VSENSOR est en mode d’inoccupation seulement (il n’allume pas les lumières). Dans les systèmes avec un hub Vive : Contactez l’assistance à la clientèle de Lutron pour plus de détails. Dans les systèmes sans hub Vive : Attendez 90 minutes pour que le PowPak revienne au fonctionnement normal. La commande de luminaire ne passera pas en mode de secours (FCJS-010-EM, • Contactez l’assistance à la clientèle de Lutron pour plus de détails. FCJS-ECO-EM seulement). Pour obtenir des informations d’activation du mode de sortie au seuil bas, des suggestions d’application et bien d’autres notes sur les commandes de luminaires PowPak, consultez le document de Lutron 048556 ou 369918 sur www.lutron.com. Réglage du seuil bas A Activer le mode d’ajustement du réglage du seuil bas : Appuyez et maintenez le bouton Baisser « » enfoncé sur la commande de luminaire pendant 12 secondes. Les lumières clignoteront à leur niveau et la DEL d’état de la charge commencera à clignoter. B Ajuster le réglage du seuil bas : Utilisez le bouton Monter «ŷ» et le bouton Baisser « » sur la commande de luminaire pour régler les lumières au niveau de réglage du seuil bas souhaité (1 à 45 %). C Enregistrer le réglage du seuil bas : Appuyez et maintenez le bouton de Alterner « u» enfoncé pendant 6 secondes pour enregistrer le réglage. La DEL d’état de la charge commencera à clignoter puis restera allumée pour indiquer que le nouveau niveau a été enregistré. Réglage du seuil haut A Activer le mode de réglage du seuil haut : Appuyez et maintenez le bouton Monter «ŷ» enfoncé sur la commande de luminaire pendant 12 secondes. Les lumières clignoteront à leur niveau et la DEL d’état de la charge commencera à clignoter. B Ajuster le réglage du seuil haut : Utilisez le bouton Monter «ŷ» et le bouton Baisser « » sur la commande de luminaire pour régler les lumières au niveau de réglage du seuil haut souhaité (55 à 100 %). C Enregistrer le réglage du seuil haut : Appuyez et maintenez le bouton de Alterner «u» enfoncé pendant 6 secondes pour enregistrer le réglage. La DEL d’état de la charge commencera à clignoter puis restera allumée pour indiquer que le nouveau niveau a été enregistré. Ǻ !AVERTISSEMENT !DANGER Symptôme www.lutron.com/support Ǻ Remarque : La commande de luminaire quitte automatiquement le mode d’association 10 minutes après la dernière activité. Dépannage Ǻ Caractéristiques du laser vert : • Sortie d’onde : constante • Longueur d’onde : 532 nM • Puissance de sortie : 5 mW maximum Garantie limitée : www.lutron.com/TechnicalDocumentLibrary/369-119_Wallbox_Warranty.pdf Informations FCC / IC Cet appareil est conforme à la partie 15 des règles du FCC et aux normes industrielles RSS d’exemption de licence du Canada. Le fonctionnement doit suivre les deux conditions suivantes : (1) Cet appareil ne doit pas provoquer d’interférences, et (2) cet appareil ne doit accepter aucune interférence, y compris des interférences qui pourraient provoquer un fonctionnement indésirable. Les modifications qui n’ont pas été expressément approuvées par Lutron Electronics Co., Inc. peuvent annuler le pouvoir de l’utilisateur d’utiliser cet équipement. REMARQUE : Cet équipement a été testé et est conforme aux limites d’un appareil numérique de Classe B en vertu de la partie 15 des règles de la FCC. Ces limites sont conçues pour fournir une protection raisonnable face aux interférences nuisibles dans une installation résidentielle. Cet équipement génère, utilise et peut émettre une énergie de fréquence radio et, s’il n’est pas installé et utilisé conformément aux instructions, il peut provoquer des interférences nuisibles aux communications radio. Cependant, il n’y a aucune garantie que des interférences ne surviendront dans une installation particulière. Si cet équipement provoque des interférences nuisibles pour la réception radio et télévisuelle, ce qui peut être déterminé en allumant et en éteignant l’équipement, il est recommandé que l’utilisateur tente de corriger ces interférences en utilisant une ou plusieurs des mesures suivantes : • Réorientez ou repositionnez l’antenne réceptrice. • Augmentez la séparation entre l’équipement et le récepteur. • Connectez l’équipement à une prise électrique se trouvant sur un circuit différent de celui où le récepteur est connecté. Assistance à la clientele | 1.844.LUTRON1 É.-U., Canada, et les Caraïbes | +44.(0)20.7702.0657 Europe | +1.610.282.3800 Autres | www.lutron.com/support Lutron, EcoSystem, Pico, PowPak, et Vive sont des marques déposées de Lutron Electronics Co., Inc., enregistrées aux États-Unis et dans d’autres pays. Radio Powr Savr est une marque déposée de Lutron Electronics Co., Inc. Safari est une marque déposée de Apple Inc., enregistrées aux États-Unis et dans d’autres pays. iOS est une marque déposée de Cisco aux États-Unis et dans d’autres pays, utilisée sous licence. Google est une marque déposée et Android et Chrome sont des marques de Google Inc. NEC est une marque déposée de le National Fire Protection Association, Quincy, Massachusetts. ©2014 – 2018 Lutron Electronics Co., Inc. Componentes requeridos Módulo de Atenuación PowPak Instalación FCJS-010 FCJS-010-EM 0 –10 V- Conmutación de 120 – 277 V~ 50 / 60 Hz 1 A Fuente / drenaje de 6 mA FCJS-ECO Conmutación de 120 – 277 V~ 50 / 60 Hz 1 A FCJS-ECO-EM 14 V- 6 mA Lutron EcoSystem Control inalámbrico de artefactos PowPak Homologado UL 2043 para plenum Listado en UL 924 (FCJS-010-EM / FCJS-ECO-EM) Controla hasta tres balastos o controladores (la norma IEC 60929 anexo E.2 requiere que cada balasto o controlador limite la corriente de fuente/drenaje a 2,0 mA como máximo). Suministra 12 V- , 25 mA IEC SELV/NECR Clase 2 a un sensor de artefactos PowPak (FC-SENSOR o FC-VSENSOR). Encender y Apagar Bajar + Sensor de artefactos PowPak (FC-SENSOR o FC-VSENSOR) Control inalámbrico de artefactos PowPak (FCJS-010 / FCJS-010-EM o FCJS-ECO / FCJS-ECO-EM) (1 máximo) A B El control del artefactos puede instalarse en un artefacto/luminaria, caja de conexiones o caja organizadora utilizando la tuerca de conducto (suministrada) o con tornillos de montaje (no suministrados). El producto NO debe montarse dentro de un dispositivo, solo en el exterior de un dispositivo. Para obtener una instalación adecuada consulte las normativas eléctricas locales y nacionales. Idealmente, monte el sensor a la placa de techo cerca del artefacto utilizando el gancho de montaje o la cinta adhesiva (incluidos). Los dos cables de comunicación del sensor se conectan a los conectores de cuchilla del control de artefactos. Los cables son intercambiables para eliminar los defectos de cableado. Nota: Para obtener la guía de instalación del FC-SENSOR y FC-VSENSOR visite www.lutron.com Una vez instalado, energice el módulo de control. Este artefacto se encenderá. (1 máximo) Control remoto Pico (10 máximo) Neutro (Blanco) Abertura con tapa ciega de 21 mm (1/2 pulg) Artefacto/ Luminaria o caja de conexiones Tuerca del conducto Los sensores y controles inalámbricos deben estar situados a menos de 18 m (60 pies) con línea de visión directa, o 9 m (30 pies) a través de paredes, del módulo de control asociado. Generador de 120/277 V~ / Alimentación de emergencia Interruptor de transferencia automática Balasto / Controlador Normal FCJS-ECO: E1 (Violeta), E2 (Violeta) Desde la parte trasera del sensor Tapa ciega del control de artefactos PowPak Cableado de la lámpara Alimentación de emergencia de 120/277 V~ Neutro Suministro eléctrico normal de la red L FCJS-010: -(Gris), + (Violeta) Neutro (Blanco) Abertura con tapa ciega de 21 mm (1/2 pulg) Neutro Artefacto/ Luminaria o caja de conexiones N Línea/vivo conmutada (rojo) L Balasto / Controlador Emergencia Tuerca del conducto Neutro Tierra del artefacto Verde/Amarillo Neutro Control remoto Pico N Línea/vivo conmutada (rojo) Línea/vivo (negro) Alimentación normal de 120 / 277 V~ Tierra del artefacto Verde/Amarillo Cableado del control de artefactos PowPak – Mantenga el cableado de la lámpara lo más corto posible para reducir la radiación de los cables. Maximice la distancia – Mantenga el cableado de las lámparas lo más alejado posible de la ubicación de montaje del control inalámbrico de artefactos PowPak. Para obtener más detalles consulte la sección de Solución de Problemas. Control de artefactos FCJS-010: - (Gris), + (Violeta) FCJS-ECO: E1 (Violeta), E2 (Violeta) Nota: Para la verificación y el mantenimiento periódicos de los sistemas de emergencia, utilice el botón de alternancia del FCJS-010-EM / FCJS-ECO-EM para asegurar una operación adecuada. Asegúrese de que los botones de PowPak permanezcan accesibles. PRECAUCIONES IMPORTANTES Cuando se utilicen equipos eléctricos se deberá adoptar siempre precauciones básicas de seguridad, entre ellas las siguientes: Lutron Electronics Co., Inc. 7200 Suter Road Coopersburg, PA 18036-1299 E.U.A. (10 máximo) Neutro Sensor Para obtener más información, consulte N/P 369918 de Lutron en www.lutron.com Sensor de luz diurna Radio Powr Savr Línea/vivo (negro) Nota importante: Para optimizar el desempeño de RF del producto: Instale el control de artefactos directamente en un artefacto o en la caja de conexiones más cercana al artefacto. Instale el sensor en el cielorraso cerca del artefacto para optimizar la cobertura en el área deseada. GUARDE ESTAS INSTRUCCIONES Sensor de ocupación/ vacancia Radio Powr Savr ADVERTENCIA! Peligro de descarga eléctrica. Podría ocasionar lesiones graves o la muerte. Antes de instalar el equipo desconecte la alimentación eléctrica en el disyuntor. Control de artefactos PowPak • No utilizar al aire libre. • No montar cerca de calefactores eléctricos o de gas. • El equipo deberá montarse en lugares y alturas donde no resulte accesible a la manipulación por personal no autorizado. • El empleo de equipos accesorios no recomendados por el fabricante podría ocasionar una condición insegura. • No utilice este equipo para otro uso que el concebido. + 2. Sólo puede utilizarse un control de artefactos por sensor de artefactos, y sólo puede utilizarse un sensor de artefactos por control de artefactos. Ubicación de instalación sugerida: Cercana a un artefacto/luminaria. Important Notes: Please read before installing. LEA Y SIGA TODAS LAS INSTRUCCIONES DE SEGURIDAD. Para informarse del cableado de los artefactos consulte la guía de instalación de artefactos. Para obtener las mejores prácticas de montaje y conexión consulte la Nota de aplicación Nº 620 de Lutron (N/P 048620). Notas: 1. El control de artefactos puede utilizarse sin un sensor de artefactos siempre y cuando se utilice al menos un sensor Radio Powr Savr o un control inalámbrico Pico. Instale el control de artefactos y el sensor de artefactos opcional 1 • Para ser instalado por un electricista calificado de acuerdo con todas las normativas eléctricas locales y nacionales (incluidos la verificación y el mantenimiento periódicos de los sistemas de emergencia). • Sólo utilice conductores de cobre. • Verifique que el tipo de dispositivo y la certificación sean adecuados para la aplicación. • NO instale este producto si tuviera algún daño visible. • Si hubiera señales evidentes de humedad o condensación, permita que el producto se seque por completo antes de la instalación. • Opérelo entre 0 °C y 40 °C (32 °F y 104 °F) de temperatura ambiente. • 0 a 90% de humedad, sin condensación. • Sólo para uso bajo techo. 9 m (30 pies) máximo FCJS-ECO / FCJS-ECO-EM: Al menos un balasto o controlador de LED Lutron EcoSystem 6 mA máximo para las líneas de control. Conmuta hasta 1 A en total (o un máximo de tres balastos o controladores). Puede ser preinstalado en el artefacto. Nota: Todos los controladores y balastos utilizados con los controles inalámbricos Vive deben satisfacer los límites para un dispositivo de clase A, de conformidad con la Parte 15 de las reglas de la FCC. Comience aquí Nota para el reemplazo: FCJS - el modelo “S” puede reemplazar al modelo no “S” Español Lente PIR Detección Lente de luz de láser diurna Subir LED de estado de la carga www.lutron.com/support FCJS-010 / FCJS-010-EM: Al menos un balasto fluorescente o controlador de LED de 0 –10 V- Al menos uno de estos transmisores (permitidos 22 en total) Un control de artefactos 041645 Rev. A 03/2018 Parte de la familia Vive Asistencia al cliente Para cada artefacto, se necesitará: Generador de respaldo de emergencia 2 Sólo FCJS-010-EM / FCJS-ECO-EM Nota: Las interrupciones momentáneas de la alimentación eléctrica pueden invocar el modo de emergencia en el controlador de dispositivos. Para obtener más detalles consulte la sección de Solución de Problemas. Desde la parte trasera del sensor Programación con un hub Vive A Utilice un dispositivo compatible con iOS® o Android®. B Descargue la aplicación Vive de Lutron. C Abra la aplicación y siga las instrucciones. vive.lutron.com Vive X X Nota: Para obtener información adicional sobre la configuración, programación y resolución de problemas con un sistema Vive, consulte las instrucciones de instalación incluidas con el hub Vive o visite www.lutron.com/vive Nota: Para programar el módulo de control de artefactos PowPak sin un hub Vive, consulte el dorso. Restablezca los valores predeterminados de fábrica Nota: En algunos casos puede ser necesario restablecer la configuración predeterminada de fábrica tanto de los controles de artefactos como de los dispositivos conectados. Antes de comenzar, asegúrese de que todos los dispositivos estén conectados y energizados. A Pulse rápidamente tres veces el botón Encender y Apagar “ u” en el control de artefactos y manténgalo pulsado la cuarta vez hasta que el LED comience a destellar lentamente; suelte el botón. B Dentro de los 3 segundos del comienzo del destello, pulse de nuevo rápidamente tres veces el botón Encender y Apagar “ u” y los LED destellarán rápidamente, indicando que el equipo ha sido restablecido a los valores predeterminados de fábrica. Nota: Toda asociación o programación establecida con anterioridad para el control de artefactos será borrada y tendrá que ser reprogramada. Notas: 1. Los cables de control (violeta/gris para el FCJS-010 / FCJS-010-EM o violeta/violeta para el FCJS-ECO / FCJS-ECO-EM) pueden ser tendidos como Clase 1 o Clase 2. 2. Con artefactos colgantes la máxima longitud de cable entre el sensor de artefactos y el control de artefactos es de 3,7 m (12 pies). El sensor deberá ser montado a no más de 0,6 m (2 pies) del artefacto. 3. Para instalar el equipo en el interior de una caja de conexiones, consulte la Nota de aplicación 423 de Lutron (N/P 048423) en www.lutron.com 4. Cuando no se utiliza el hub Vive, el control de artefactos debe estar accesible para algunas etapas de programación. Registre dónde está montado para que pueda ubicarlo fácilmente más adelante. 5. Cuando se utilice un sensor de luz diurna Radio Powr Savr en conjunto con tanto un control inalámbrico de artefactos PowPak y un sensor de artefactos PowPak, el sensor de luz diurna Radio Powr Savr proporcionará la entrada de iluminación diurna al módulo de control, y la entrada de luz diurna del sensor de artefactos PowPak será ignorada. 6. Cuando se utilice un sensor de ocupación Radio Powr Savr en conjunto tanto con un control inalámbrico de artefactos PowPak como con un sensor de artefactos PowPak, se utilizan los datos ocupación de ambos sensores; cualquiera de ellos que detecte una ocupación encenderá las luces, y éstas sólo se apagarán cuando ambos sensores pasen al modo de vacancia (ya no detectan ocupación). 7. Para obtener más información sobre el sensor de artefactos PowPak consulte: N/P 369866 o N/P 048556 en www.lutron.com Para obtener la guía de instalación del FC-SENSOR y FC-VSENSOR visite www.lutron.com Módulo de Atenuación PowPak Programación sin un hub Vive Asistencia al cliente 2 Parte de la familia Vive El sensor de luz diurna va a controlar todos los artefactos conectados por igual. Comience aquí A Pulse y suelte el botón “Cal.” del sensor de luz diurna. Antes de comenzar este paso, asegúrese de que no haya otros controles de artefactos que estén siendo configurados en el edificio y que se encuentren actualmente en el modo de asociación. Es posible que los transmisores inalámbricos de otros sistemas puedan estar asociados incorrectamente a este módulo. A Inicie el modo de asociación en el control de artefactos de una de dos maneras: 1 Pulse y mantenga pulsado el botón Encender y Apagar “ u ” durante 6 segundos en el control del artefacto hasta que la carga conectada al control del artefacto comience a destellar (cada 2 segundos). 2 Alternativamente, haga brillar un puntero láser verde (disponible en ferreterías o tiendas de suministros de oficina) sobre el orificio de detección de láser del sensor hasta que la carga conectada al control del artefacto comience a destellar (cada 2 segundos). Nota: Pueden ponerse varios controles de artefactos en el modo de asociación repitiendo uno de los dos métodos anteriores para el próximo control de artefactos antes de continuar al Paso 1B. Cal. Link C Pulse y mantenga pulsado el botón “Cal.” durante 6 segundos. D Salga de la habitación durante 5 minutos para completar la calibración. Nota: Cuando la calibración se haya completado, todas las luces destellarán y comenzarán a responder a la luz diurna. 3 Configure un nivel de luz favorito (opcional) Para los controles remotos Pico con un botón Favorito. Configure el ajuste de las intensidades mínima y máxima (opcional) Para obtener los mejores resultados, minimice la cantidad de luz solar que ingresa a la habitación antes de realizar los siguientes procedimientos. Test B Configure las luces de la habitación al nivel de luz deseado. Asocie los transmisores al control de artefactos 1 4 Calibre el sensor de luz diurna Radio Powr Savr www.lutron.com/support Subir En función del fabricante del artefacto o de la carga, podría ser necesario ajustar las intensidades máxima y mínima. • Ajuste el intensidad mínima para asegurar un nivel estable de luz porque algunas cargas parpadearán o caerán si se las ajusta demasiado bajas. • Asegúrese de que se pueda encender las luces al nivel de ajuste de intensidad mínima sin tener que ejecutar ninguna operación anormal. • El ajuste de intensidad máxima predeterminado de fábrica es adecuado para la mayoría de las aplicaciones, pero puede ajustarse como se desee. Bajar A Ajuste las luces al nivel deseado: Utilice el botón Subir “ ” o el botón Bajar “ NOTA: El ajuste de intensidad mínima e intensidad máxima también se puede realizar para una sola unidad o grupo de unidades simultáneamente con un control remoto Pico. ” del control remoto Pico. B Guarde el nivel favorito: Pulse y mantenga pulsado el botón Favorito durante 6 segundos. La carga destellará tres veces para confirmar que el nivel favorito ha sido guardado. Favorito Detección de láser Para obtener más información, consulte el N/P 048556 en www.lutron.com. O • • PELIGRO Lesiones oculares y/o peligro de ceguera; evitar la exposición directa de los ojos al rayo láser. Un puntero láser NO se recomienda para su uso con productos Lutron ubicados cerca de superficies reflectantes. NO apunte o haga brillar punteros láser sobre ninguna persona, animal, vehículo o aeronave, ya sea directamente o a través de su reflexión por espejos u otras superficies reflectantes. NO mire el rayo láser a través de binoculares, lupa, u otros dispositivos ópticos. NO permita que los niños utilicen punteros láser. Lea y respete las instrucciones del fabricante del puntero láser sobre uso seguro. En caso de lesiones, procure atención médica inmediatamente. B Mantenga pulsado el botón indicado en cada transmisor durante 6 segundos. El artefacto destellará para mostrar que los transmisores inalámbricos han sido asociados. Alternativamente, para los sensores de ocupación/vacancia y luz diurna Radio Powr Savr, puede utilizarse el puntero láser verde. Para obtener más información consulte la Nota de aplicación Nº 407 de Lutron (N/P 048407) en www.lutron.com. Para asociar otro transmisor, repita los pasos 1A y 1B. Link Test Funcionalidad predeterminada Controles inalámbricos: Todas las luces Encendida: 100%; Favorito: 50%; Apagada: 0% Controles de artefactos Nivel Automático Activado: FC-SENSOR únicamente (no aplicable para FC-VSENSOR) Varía con el nivel de luz ambiental cuando se dispara la ocupación (p. ej., 100% para una habitación oscura, 10% para una habitación iluminada). Intervalo de espera: 15 minutos Solución • Asegúrese de que los disyuntores al control de artefactos estén energizados. • Asegúrese de que el cable conmutado en caliente del control de artefactos esté conectado al balasto/controlador (FCJS-010 / FCJS-010-EM). Los balastos/controladores no • Asegúrese de que las líneas de control del control de artefactos (FCJS-010 / FCJS-010-EM: pueden ser controlados localmente violeta/gris, FCJS-ECO / FCJS-ECO-EM: violeta / violeta) se conecten al balasto/controlador. desde el control de artefactos. • Si se utiliza el FCJS-010 / FCJS-010-EM, verifique que el controlador/balasto sea de 0 –10 V-. Si se utiliza el FCJS-ECO / FCJS-ECO-EM, emplee el controlador/balasto Lutron EcoSystem. Restablezca los valores predeterminados de fábrica. Las luces no se atenúan o ENCIENDEN como se esperaba. • Asegúrese de que las líneas de control estén cableadas correctamente (FCJS-010 / FCJS-010-EM: violeta/gris sensible a la polaridad, FCJS-ECO / FCJS-ECO-EM: violeta / violeta) • Asegúrese de que los cables estén conectados entre el sensor de artefactos y el control de artefactos. • Sólo FCJS-010 / FCJS-010-EM: Asegúrese de que el artefacto de 0 –10 V- esté en la intensidad mínima (a 0 V), y no APAGADO (a 0 V). Si está APAGADO (a 0 V), ajuste la intensidad mínima. • Sólo FCJS-010 / FCJS-010-EM: Asegúrese de que el artefacto no requiera una señal invertida (control de 10 – 0 V-). • Sólo FCJS-010 / FCJS-010-EM: Verifique que el voltaje entre los cables gris y violeta esté entre 0 y 10 V-. • Sólo FCJS-ECO / FCJS-ECO-EM: Desconecte los cables violeta/violeta del control de artefactos. Verifique que las luces pasen al 100%. • Sólo FCJS-010 / FCJS-010-EM: Desconecte los cables violeta/gris del control de artefactos. Verifique que las luces pasen al 100%. Cortocircuite los cables violeta/gris en el balasto/controlador, y verifique que las luces pasen a la intensidad mínima. Las luces no responden a los transmisores inalámbricos. • Asegúrese de que los disyuntores al control de artefactos y a los balastos/controladores estén energizados. • Asegúrese de que los transmisores inalámbricos estén asociados al control de artefactos. Los transmisores inalámbricos no pueden ser asociados al control de artefactos. Restablezca los valores predeterminados de fábrica. • Ha sido asociado al control de artefactos el número máximo de transmisores inalámbricos. Para eliminar un transmisor inalámbrico previamente configurado, pulse tres veces cualquier botón del transmisor inalámbrico; la tercera vez manténgalo pulsado durante tres segundos y luego púlselo tres veces más. El rango de RF entre los controles inalámbricos está reducido por debajo de los 9 m (30 pies). Las luces son inestables a la intensidad mínima. El sensor de artefactos no ENCIENDE las luces. El control de artefactos está en el modo de emergencia (sólo FCJS-010-EM y FCJS-ECO-EM). El control de dispositivos no pasará al modo de emergencia (sólo FCJS-010-EM, FCJS-ECO-EM). • Mantenga el cableado del balasto/controlador lo más corto posible y bien organizado para evitar que se apretuje el exceso de cables. • Mantenga las primeras 20-30 cm (7-12 pulg) separadas lo más posible de los cables provenientes de la tapa ciega del control de artefactos de cualquier cable de balasto/controlador/lámpara cercanos. • Para obtener detalles adicionales póngase en contacto con la Asistencia al cliente de Lutron. • Configure el ajuste de la intensidad mínima. • Verifique que los cables del sensor de artefactos estén conectados al control del artefacto. • El FC-VSENSOR es de vacancia únicamente (no encenderá las luces). • En sistemas con un hub Vive: Para obtener detalles adicionales póngase en contacto con la Asistencia al cliente de Lutron. • En sistemas sin un hub Vive: Espere 90 minutos para que el PowPak retorne a su operación normal. • Para obtener detalles adicionales póngase en contacto con la Asistencia al cliente de Lutron. Para obtener información sobre cómo activar el modo de salida, sugerencias de aplicación y muchas otras notas sobre los controles de artefactos PowPak, consulte los documentos de Lutron 048556 o 369918 en www.lutron.com. Ajuste de la intensidad mínima A Ingrese al modo de ajuste de la intensidad mínima: Pulse y mantenga pulsado el botón Bajar “ ” del control de artefactos durante 12 segundos. Las luces destellarán y el LED del estado de la carga comenzará a destellar. B Ajuste la intensidad mínima: Utilice el botón Subir “ŷ” y el botón Bajar “ ” del control de artefactos para ajustar y configurar las luces al nivel de intensidad mínima deseado (1 a 45%). C Guarde el ajuste de la intensidad mínima: Pulse y mantenga pulsado el botón Encender y Apagar “ u” durante 6 segundos para guardar la configuración. El LED de estado de la carga comenzará a dwestellar y luego se iluminará continuamente para indicar que el nuevo nivel ha sido guardado. Ajuste de la intensidad máxima A Ingrese al modo de ajuste de la intensidad máxima: Pulse y mantenga pulsado el botón Subir “ŷ” del control de artefactos durante 12 segundos. Las luces destellarán y el LED del estado de la carga destellará. B Ajuste la intensidad máxima: Utilice el botón Subir “ŷ” y el botón Bajar “ ” del control de artefactos para ajustar y configurar las luces al nivel de intensidad máxima deseado (55 a 100%). C Guarde el ajuste de la intensidad máxima: Pulse y mantenga pulsado el botón Encender y Apagar “ u” durante 6 segundos para guardar la configuración. El LED de estado de la carga comenzará a destellar y luego se iluminará continuamente para indicar que el nuevo nivel ha sido guardado. Ǻ • ! Síntoma www.lutron.com/support Ǻ • ADVERTENCIA Solución de Problemas Ǻ ! Especificaciones del láser verde: • Salida de onda: constante • Longitud de onda: 532 nm • Potencia de salida: 5 mW maximum Nota: El control de artefactos saldrá automáticamente del modo de asociación 10 minutos después de la última actividad. Garantía limitada: www.lutron.com/TechnicalDocumentLibrary/369-119_Wallbox_Warranty.pdf Información de la FCC / IC Este dispositivo satisface la parte 15 de las reglas de la FCC y las normas RSS de exención de licencia de Industry Canada. La operación está sujeta a las dos siguientes condiciones: (1) Este dispositivo no debe causar interferencias perjudiciales y (2) este dispositivo debe aceptar cualquier interferencia, incluida la interferencia que pudiera ocasionar una operación no deseada. Las modificaciones no aprobadas expresamente por Lutron Electronics Co., Inc. podrían invalidar la autorización del usuario para utilizar este equipo. NOTA: Este equipo ha sido comprobado y se lo encontró comprendido dentro de los límites para un dispositivo digital clase B, según la sección 15 de las reglas de la FCC. Estos límites están diseñados para proporcionar una protección razonable contra las interferencias perjudiciales en una instalación residencial. Este equipo genera, utiliza y puede irradiar energía de radiofrecuencia, y si no se lo instala y utiliza de acuerdo con las instrucciones podría ocasionar interferencias perjudiciales para las radiocomunicaciones. Sin embargo, no hay garantía de que no ocurran interferencias en una instalación en particular. Si este equipo ocasionara interferencias perjudiciales para la recepción de radio o televisión, lo que puede ser determinado encendiéndolo y apagándolo, se recomienda al usuario que intente corregir la interferencia adoptando una o más de las siguientes medidas: • Reorientar o reubicar la antena receptora. • Aumentar la separación entre el equipo y el receptor. • Conectar el equipo a un tomacorriente que corresponda a un circuito diferente de aquel al cual está conectado el receptor. Asistencia al cliente | 1.844.LUTRON1 E.U.A., Canadá y el Caribe | +44.(0)20.7702.0657 Europa | +1.610.282.3800 Demás países | www.lutron.com/support Lutron, EcoSystem, Pico, PowPak, y Vive son marcas comerciales de Lutron Electronics Co., Inc., registradas en E.U.A. y en otros países. Radio Powr Savr es una marca comercial de Lutron Electronics Co., Inc. Safari es una marca comercial de Apple Inc., registrada en E.U.A. y en otros países. iOS es una marca comercial registrada de Cisco en E.U.A. y en otros países y se utiliza bajo licencia. Google es una marca comercial registrada y Android y Chrome son marcas comerciales de Google Inc. NEC es una marca comercial de el National Fire Protection Association, Quincy, Massachusetts. ©2014 – 2018 Lutron Electronics Co., Inc.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6

Lutron Electronics Vive Series Guía de instalación

Tipo
Guía de instalación