Acson ALC30C Guía de instalación

Categoría
Acondicionadores de aire de sistema dividido
Tipo
Guía de instalación
WALL MOUNTED
SPLIT TYPE AIR CONDITIONER
Model: IM-WM1-0302-ACSON
WALL MOUNTED
INSTALLATION MANUAL
OUTLINE AND DIMENSIONS
All dimensions are in mm / (in)
i
Dimension A B C D E
WM071 / 101 / 151 / 1R 785,0 (30,9) 297,0 (11,7) 174,0 (6,85) 595,0 (23,4) 280,0 (11,0)
WM201 / 201R 1050,0 (41,3) 320,0 (12,6) 190,0 (7,5) 730,0 (28,7) 311,0 (12,2)
WM 251 / 251R / 301 / 311 / 301R 1200,0 (44,1) 360,0 (14,2) 200,0 (7,9) 730,0 (28,7) 347,0 (13,7)
Indoor Unit
D
INSTALLATION PLATE
E
FRONT VIEW
TOP VIEW
A
B
C
SIDE VIEW
Outdoor Unit (SL-Series)
Dimension A B C D E F G H J K L M N P Q R
07B / 07BR
740 494 270 266 233 474 47 55 65 166 92 348 318 129 482 68,5
10B / 10BR
(29,1) (19,4) (10,6) (10,5) (9,2) (18,7) (1,9) (2,2) (2,6) (6,5) (3,6) (13,7) (12,5) (5,1) (19,0) (2,7)
15B / 15BR
20B / 20BR
840 646 330 297 309 626 41 85 75 177 106 408 378 124 592 78,5
25B / 25BR
(33,1) (25,4) (13,0) (11,7) (12,2) (24,6) (1,6) (3,3) (3,0) (7,0) (4,2) (16,1) (14,9) (4,9) (23,3) (3,1)
30B / 30BR
28C / 28CR
855 750 328 303 309 730 49 116 75 187 98 392 362 126 603 164
(33,7) (29,5) (12,9) (11,9) (12,2) (28,7) (1,9) (4,6) (3,0) (7,4) (3,9) (15,4) (14,3) (5,0) (23,7) (6,5)
All dimensions are in mm / (in)
Q
N
E
15 (0,6)
39 (1,5)
A
M
P
P
840 (33,1)
D
15 (0,6)
39 (1,5)
5 (0,2)
C
20 (0,8)
20 (0,8)
2,5 (0,1)
F
B
C
5 (0,2)
160 (6,3)
H
G
141 (5,6)
K
J
(2,6)
65
L
20 (0,8)
R
Outdoor Unit (SL071 & 10/15 C/CR)
All dimensions are in mm / (in)
Dimension A B C D E F G H I J K L M N O
071 / 1R 600 (23,6) 475 (18,7) 245 (9,6) 418 (16,4) 177 (6,9) 35 (1,3) 93 (3,6) 81 (3,1) 83 (3,2) 55 (2,2) 398 (15,6) 101 (3,9) 97 (3,8) 17 (0,6) 22 (0,8)
10 / 15 C /CR 700 (27,5) 521 (20,5) 250 (9,8) 485 (19,1) 175 (6,8) 36 (1,4) 95 (3,7) 93 (3,6) 86 (3,3) 68 (2,6) 441 (17,3) 130 (5,1) 111 (4,3) 15 (0,5) 18 (0,7)
40 (1,57)
400 (15,75)
320 (12,60)
20 (0,79)
448 (17,64)
141,5 (5,57)
40 (1,57)
20 (0,79)
141,5 (5,57)
Outdoor Unit (SL30C)
ii
This product is subjected to Waste of Electrical and Electronic Equipment Regulations (WEE
E
Regulations). The waste product shall be separately collected by specific collection and treatment centre
.
P
lease refer to local authorithy for these centres. This is only applicable to European Union countries
.
Ce produit est soumis
à
la r
à
é
r
glementation concernant les
d
é
chets
d
es
é
quipements
é
lectriques e
t
é
lectroniques (r
é
r
r
é
ê
é
s
é
par
é
rr
m
ent par un centre de collect
e
é
é
é
î
î
tre ces centres. Ceci
îî
é
enne
.
Questo prodotto
è
soggetto alle disposizioni RAEE (Rifiuti di apparecchiature elettriche ed elettroniche)
.
à
à
locali. Questa disposizione
à
è
valida solamente i paes
i
d
el
l
U.
E
.
é
ctrico y Electr
ó
n
ico en materia d
e
ñ
ñ
á
í
fico
íí
de colecc
i
ó
solamente aplicable a los p
a
í
ses de la
U
n
i
ó
n
Europea
.
G
er
ä
ä
ä
tes
ää
getrennt vom Hausm
ü
ll bei Ihrer
ö
r
tlichen
M
ü
lldeponie bzw. Ihrem
ö
r
tliche
n
ä
ndiges Abfall-Amt. Dieser
ää
Hinweis gilt nur f
ü
f
f
rL
ä
nder der Europ
ää
ä
ischen Union
.
д
анног
о
п
о
и
.
,
.
Э
т
и
п
р
авил
а
Ев
р
опейског
о
.
25 (0,98)
1030 (40,55)
850 (33,46)
50 (1,97)
85 (3,35)
ii
! Осторожно
Острые края и поверхности змеевиков являются потенциальными
местами нанесения травм. Остерегайтесь контакта с этими местами.
! Cuidado
Los Bordes afilados y la superficie del serpentín pueden producir lesiones. Evite
tocarlos.
! Cautela
Per preservarsi da eventuali ferite, evitare di toccare gli spigoli afilati e la superficie
dei serpentini.
! Vorsicht
Scharfe Kanten und Wärmetauscherflächen stellen eine Gefahrenquelle dar.
Jeglicher Kontakt mit diesen Stellen ist zu vermeiden.
! Avertissement
Les bords coupants et les surfaces du refroidisseur tuulaire présentent un
risque de blessure. Mieux vaut éviter le contact avec ces endroits.
! Caution
Sharp edges and coil surfaces are potential locations which may cause
injury hazards. Avoid from being in contact with these places.
NOTICE
1-1
English
This manual provides the procedures of installation to ensure a safe and good standard of operation for the air
conditioner unit.
Special adjustment may be necessary to suit local requirements.
Before using your air conditioner, please read this instruction manual carefully and keep it for future reference.
INSTALLATION MANUAL
WALL MOUNTED SPLIT TYPE AIR CONDITIONER
MODEL
IM-WM1-0302(2)-Acson
Part No.: A08019025521
COOLING UNIT (R22)
Reference Model Model
WM301 AWM301
SL30C ALC30C
SL30B ALC30B
COOLING UNIT (R410A)
Reference Model Model
5WM311 A5WM311
5SL28C A5LC28C
HEAT PUMP UNIT (R22)
Reference Model Model
WM301R AWM301R
SL30CR ALC30CR
SL30BR ALC30BR
HEAT PUMP UNIT (R410A)
Reference Model Model
5WM301R AWM301R
5SL28CR A5LC28CR
1-2
! Caution
Please take note of the following important points when installing.
Do not install the unit where leakage of flammable gas may occur.
If gas leaks and accumulates at the surrounding of the unit, it may cause fire ignition.
Ensure that the drainage piping is connected properly.
If the drainage piping is not connected properly, it may cause water leakage which will dampen the
furniture.
Do not overcharge the unit.
This unit is factory pre-charged. Overcharge will cause over-current or damage to the compressor.
Ensure that the units panel is closed after service or installation.
Unsecured panels will cause the unit to operate noisily.
CONTENTS
- Outline and Dimensions page i-ii
- Safety Precautions page 2
- Installation Diagram page 3
- Installation of the Outdoor Unit page 3
- Installation of the Orifice Pipe page 4
- Installation of the Indoor Unit page 6
- Refrigerant Piping page 7
- Electrical Wiring Connection page 8
-
Special Precautions When Dealing With R410A Unit
page 10
- Vacuuming and Charging page 10
- Indicator Lights page 11
- Air Conditioner Unit Operation page 13
- Standard Operating Conditions page 14
- Electrostatic Filter page 14
- Service and Maintenance page 15
- Troubleshooting page 16
Before installing the air conditioner unit, please read the following safety precautions carefully.
SAFETY PRECAUTIONS
! Warning
Installation and maintenance should be performed by qualified persons who are familiar with local code and
regulation, and experienced with this type of appliance.
All field wiring must be installed in accordance with the national wiring regulation.
Ensure that the rated voltage of the unit corresponds to that of the name plate before commencing wiring work
according to the wiring diagram.
The unit must be GROUNDED to prevent possible hazard due to insulation failure.
All electrical wiring must not touch the refrigerant piping, compressor or any moving parts of the fan motors.
Confirm that the unit has been switched OFF before installing or servicing the unit.
IMPORTANT
DO NOT INSTALL OR USE THE AIR CONDITIONER UNIT IN A LAUNDRY ROOM.
1-3
English
Dimension A
Minimum
Distance, mm 300 1000
INSTALLATION DIAGRAM
Air Intake Grille
Air Discharge
Grille
Air Intake
Refrigerant Piping
Drain Hose
Front Frame
Back Housing
On/Off Switch
Air Filters
Indicator Lights
Signal Receiver
Air Discharge
Louver
Outdoor Unit
Indoor Unit
INSTALLATION OF THE OUTDOOR UNIT
Obstacle
Return Air
Discharge Air
Service Access
The outdoor unit must be installed in such a way, so as to
prevent short circuit of the hot discharged air or obstruction
to the smooth air flow. Please follow the installation clear-
ance shown in the figure. Select the coolest possible place
where intake air temperature is not greater than the outside
air temperature (maximum 45°C/113°F).
Installation clearance
Note: If there is any obstacle higher than 2m, or if there is
any obstruction at the upper part of the unit, please allow
more space than the figure indicated in the above table.
Air Discharge
Nozzle
Obstacle
Obstacle
Obstacle
Return Air
A
B
C
D
Air Intake
(in) (11.8) (39.4) (11.8) (19.7)
B C D
300
500
1-4
INSTALLATION OF ORIFICE PIPE
Orifice Pipe
1
2
34
1
2
3
4
Outdoor Unit
Indoor
Orifice
Pipe, connecting
Flare nut 3/8" (Female)
Flare joint 3/8" (Male)
! Caution
The orifice pipe must be installed in the correct direction as shown above.
Improper direction may cause failure to the operating system.
Note: This installation is only for WM301 / SL30B & WM301 / SL30C
A. Outdoor unit orifice pipe installation (where installation space is wide enough)
Orifice Pipe
Step 2
Step 1
Steps:
1. Directly connect the “Female” nut of the orifice pipe to
the liquid valve.
2. Flare the liquid pipe and connect it to the “Male” joint
of the orifice pipe.
Orifice Pipe
Liquid Pipe
1-5
English
Liquid Pipe
Brazer
C. Indoor unit orifice pipe installation
Indoor Unit
Orifice Pipe
B. Outdoor unit orifice pipe installation (where installation space is limited)
Step 4
Step 3
Step 2
Step 1
Orifice Pipe
If the orifice pipe cannot be connected directly to the liquid valve due to space constraint, it can be connected in between of the
liquid pipe.
Steps:
1. Flare the liquid pipe and connect it to the liquid valve.
2. Braze an additional “Male” joint to the liquid pipe.
3. Connect the “Female” nut of the Orifice pipe to
the“Male” joint.
4. Flare another liquid pipe and connect it to the “Male”
joint of the orifice pipe.
Steps:
1. Braze an additional “Male” joint
to the liquid pipe.
3. Flare another liquid pipe and
connect it to the “Male” joint
of the orifice pipe.
2. Connect the “Female” nut of the
Orifice pipe to the“Male” joint.
Liquid Pipe
Brazer
Liquid Pipe
Orifice Pipe
Liquid Pipe
Orifice Pipe
Liquid Pipe
Orifice Pipe
Liquid Pipe
Orifice Pipe
1-6
INSTALLATION OF THE INDOOR UNIT
Maintenance &
Servicing Space
Air Flow
Direction
Higher Than
Eye Level
The indoor unit must be installed in such a way so as to
prevent short circuit of the cool discharged air with the hot
return air. Please follow the installation clearance shown in
the figure. Do not place the indoor unit where there could be
direct sunlight shining on it. Also, this location must be
suitable for piping and drainage, and be away from doors or
windows.
Mounting installation plate
Ensure that the wall is strong enough to withstand the weight
of the unit. Otherwise, it is necessary to reinforce the wall
with plates, beams or pillars.
Use the level gauge for horizontal mounting, and fix it with
4 suitable screws.
In case the rear piping draws out, drill a hole 65mm in
diameter with a cone drill, slightly lower on the outside wall
(see figure).
Routing of piping
Remove the screw holding the front panel.
Piping routing
1
2
3
4
5
Installation plate
Marking-offline
Thread
Inside
Outside
1/50 Inclination
Right & rear side routing
The refrigerant piping can be routed to the unit in a
number of ways (left or right from the back of the unit), by
using the cut-out holes on the casing of the unit (see figure).
Bend the pipes carefully to the required position in order to
aligned it with the holes. For the right hand and rear side
out, hold the bottom of the piping and then position it to the
required direction (see figure). The condensation drain hose
can be taped to the pipes.
Mount the unit onto the installation plate
Hook the indoor unit onto the upper portion of the
installation plate (Engage the two hooks at the rear top of
the indoor unit with the upper edge of the installation plate).
Ensure that the hooks are properly seated on the
installation plate by moving it to the left and right.
End
Dipped
Into
Water
Water
Leaking
Water
Leaking
Water
Leaking
Water drainage piping
The indoor drain pipe must be in a downward gradient for
smooth drainage. Avoid situations that are likely to cause
water to leak.
Connecting cable
Drain hose
J
Wrong
J
Wrong
J
Wrong
j
Correct
50mm
50mm
50mm
50mm
50mm
50mm
Water Drainage
1-7
English
Piping length and elevation
If the pipe is too long, both the capacity and reliability of
the unit will drop. As the number of bends increases,
resistance to the flow of refrigerant system increases, thus
lowering cooling capacity. As a result the compressor may
become defective. Always choose the shortest path and
follow the recommendations as tabulated below:
Remark: The refrigerant pre-charged in the outdoor unit
is for piping length up to 7.62m/25ft.
REFRIGERANT PIPING
Outdoor unit
Indoor unit
Cutting copper tube
Piping works
Do not use contaminated or damaged copper tubing. Do not
remove plastic, rubber plugs and brass nuts from the valves,
fittings, tubings and coils until you are ready to connect
suction or liquid line into valves or fittings.
If any brazing work is required, ensure that the nitrogen gas
is passed through coil and joints while the brazing work is
being done. This will eliminate soot formation on the inside
walls of the copper tubings.
Cut the connection pipe with a pipe cutter.
Remove burrs from cut edges of the pipes with remover. Hold
the end of the pipe downwards to prevent metal chips from
entering the pipe.
Insert the flare nuts, mounted on the connection parts of both
the indoor unit and outdoor unit onto the copper pipes.
Flare the pipe with extra length above the flaring tool as shown
in the table.
The flared edge must be even and not cracked or scratched.
! Caution
An orifice is used as expansion device in WM301 cooling only unit. It is fixed in the liquid pipe in the indoor unit.
Piping connection to the units
Align the center of the piping and tighten the flare nut
sufficiently with fingers.
Finally, tighten the flare nut with the torque wrench
until the wrench clicks.
Ø Tube, D A (mm)
Inch mm Imperial Rigid
1/4" 6.35 1.3 0.7
3/8" 9.52 1.6 1.0
Spanar
Torque Wrench
Indoor Piping
Flare Nut
Flared TubeFlare Joint
L
H
Pipe Size mm / (in) Torque Nm / (Ft-lb)
12.7 (1/2) 55 (40.6)
15.88 (5/8) 65 (48.0)
6.35 (1/4) 18 (13.3)
9.53 (3/8) 42 (31.0)
1/2" 12.70 1.9 1.3
5/8" 15.88 2.2 1.7
25 Model 07/10 15 20 30
Maximum length, m (ft), L
12
(39.4)
12
(39.4)
15
(49.2)
15
(49.2)
35
(114.8)
Maximum elevation m (ft), H 5 (16.4) 5 (16.4) 8 (26.2) 8 (26.2) 15 (49.2)
Maximum number of bends 10 10 10 10 10
Liquid pipe size 1/4" 1/4" 1/4" 3/8" 3/8"
Gas pipe size 3/8" 1/2" 5/8" 5/8" 5/8"
Copper tube
Swaging block
Remove burr
1-8
L
COMP
N2
N1
N
T
COMP
L
N
S
R
COMP
N2
N1
L
COMP
N
ELECTRICAL WIRING CONNECTION
Cooling unit
IMPORTANT : * The figures shown in the table are for information purpose only. They should be checked and selected
to comply with the local/national codes of regulations. This is also subject to the type of installation
and conductors used.
** The appropriate voltage range should be checked with label data on the unit. ETL listed is only applicable to 60Hz
power supply only.
COMP
N2
N1
L
COMP
R
S
N
L
N
L
WM301 VS SL30C
WM07 / 10 / 15 / 20 / 25 / 301 VS SL07 / 10 / 15 / 20 / 25 / 30B
5WM311 VS 5SL28C
There must be a double pole
switch with a minimum 3mm
contact gap and fuse/circuit
breaker as recommended in
the fixed installation circuit.
!
Outdoor Unit
Terminal Block
Power Supply Cable
Power Supply Cable
There must be a double pole
switch with a minimum 3mm
contact gap and fuse/circuit
breaker as recommended in
the fixed installation circuit.
!
Indoor Unit
Terminal Block
Outdoor Unit
Terminal Block
Power Supply Cable
There must be a double pole
switch with a minimum 3mm
contact gap and fuse/circuit
breaker as recommended in
the fixed installation circuit.
!
WM201 / 251 VS SL20 / 25B (3 Phase)
Indoor Unit
Terminal Block
Outdoor Unit
Terminal Block
L
COMP
N2
N1
N
T
COMP
L
N
S
R
There must be a double pole
switch with a minimum 3mm
contact gap and fuse/circuit
breaker as recommended in
the fixed installation circuit.
!
Power Supply Cable
Indoor Unit
Terminal Block
Outdoor Unit
Terminal Block
WM301 VS SL30C (3 Phase)
Wire Clamp
Interconnection
Cable
All wires must be firmly connected.
All wires must not touch the refrigerant piping,
compressor or any moving parts of the fan motor.
The connecting wires between the indoor unit and the outdoor
unit must be clamped on the wire clamps as shown in the
figure.
The power supply cord must be equivalent to H05RN-F
(245IEC57) which is the minimum requirement.
Model Indoor WM 071/ 101/ 151 WM201/ 251/ 301 5WM311 WM301 WM201/ 251/ 301 WM301
Outdoor SL07/ 10/ 15B SL20/ 25/ 30B 5SL28C SL30C SL20/ 25/ 30B SL30C
Voltage range**
220V-240V/ 1Ph/ 50Hz + or 208V-230V/ 1Ph/ 60Hz + 380V-415V/ 3Ph/ 50Hz +N+
Power supply cable size* mm
2
1.5 2.5 2.5 4 1.5 1.5
Number of wires 333355
Interconnection cable size* mm
2
1.5 2.5 2.5 2.5 1.5 1.5
Number of wires 333444
Recommended fuse A 15 20 20 25 15 15
Indoor Unit
Terminal Block
1-9
English
Heat pump unit
4WV
OF
COMP
N2
N1
L
4WV
OF
COMP
N
4WV
OF
COMP
N2
N1
L
4WV
A
OF
COMP
L
N
L
N
WM301R VS SL30CR
WM07 / 10 / 15 / 20 / 25 / 301R VS SL07 / 10 / 15 / 20 / 25 / 30BR
5WM301R VS 5SL28CR
There must be a double pole
switch with a minimum 3mm
contact gap and fuse/circuit
breaker as recommended in
the fixed installation circuit.
!
Indoor Unit
Terminal Block
Outdoor Unit
Terminal Block
Power Supply Cable
Outdoor Coil Sensor Connection Wire
(8m long) attached in the indoor unit
There must be a double pole
switch with a minimum 3mm
contact gap and fuse/circuit
breaker as recommended in
the fixed installation circuit.
!
Indoor Unit
Terminal Block
Outdoor Unit
Terminal Block
Power Supply Cable
Outdoor Coil Sensor Connection Wire
(8m long) attached in the indoor unit
4WV
OF
COMP
N2
N1
L
4WV
OF
COMP
L
N
S
R
N
T
4WV
OF
COMP
N2
N1
L
4WV
OF
COMP
L
N
A
S
R
N
T
WM301R VS SL30CR (3 Phase)WM201 / 251R VS SL20 / 25BR (3 Phase)
Outdoor Coil Sensor Connection Wire
(8m long) attached in the indoor unit
Outdoor Coil Sensor Connection Wire
(8m long) attached in the indoor unit
There must be a double pole
switch with a minimum 3mm
contact gap and fuse/circuit
breaker as recommended in
the fixed installation circuit.
!
Indoor Unit
Terminal Block
Outdoor Unit
Terminal Block
Power Supply Cable
Indoor Unit
Terminal Block
Outdoor Unit
Terminal Block
There must be a double pole
switch with a minimum 3mm
contact gap and fuse/circuit
breaker as recommended in
the fixed installation circuit.
!
Power Supply Cable
IMPORTANT : * The figures shown in the table are for information purpose only. They should be checked and selected
to comply with the local/national codes of regulations. This is also subject to the type of installation
and conductors used.
** The appropriate voltage range should be checked with label data on the unit. ETL listed is only applicable to 60Hz
power supply only.
Model Indoor WM 071/ 101/ 151 R WM201/ 251/ 301 R 5WM301R WM301 R WM201/ 251/ 301 R WM301 R
Outdoor SL07/ 10/ 15BR SL20/ 25/ 30BR 5SL28CR SL30CR SL20/ 25/ 30BR SL30CR
Voltage range**
220V-240V/ 1Ph/ 50Hz + or 208V-230V/ 1Ph/ 60Hz + 380V-415V/ 3Ph/ 50Hz +N+
Power supply cable size* mm
2
1.5 2.5 2.5 4 1.5 1.5
Number of wires 3 3 3355
Interconnection cable size* mm
2
1.5 2.5 2.5 2.5 1.5 1.5
Number of wires 5 5 5664
Recommended fuse A 15 20 20 25 15 15
1-10
VACUUMING AND CHARGING
Purging the piping and the indoor unit
Except for the outdoor unit which is pre-charged with
refrigerant, the indoor unit and the refrigerant
connection pipes must be air-purged because the air
containing moisture that remains in the refrigerant cycle may
cause malfunction of the compressor.
Remove the caps from the valve and the service port.
Connect the centre of the charging gauge to the vacuum
pump.
Connect the charging gauge to the service port of the
3-way valve.
Start the vacuum pump. Evacuate for approximately 30
minutes. The evacuation time varies with different
vacuum pump capacity. Confirm that the charging gauge
needle has moved towards -76mmHg (0~76mmHg).
Caution
If the gauge needle does not move to 0~76mmHg, be
sure to check for gas leaks (using the refrigerant
detector) at flare type connection of the indoor and out-
door unit and repair the leak before proceeding to the
next step.
Close the valve of the changing gauge and stop the
vacuum pump.
On the outdoor unit, open the suction valve (3 way) and
liquid valve (2 way) (in anti-clockwise direction) with
4mm key for hexagon sacked screw.
Service Port
Outdoor Unit
3 Ways Valve
Flare Unit
Refrigerant Piping
Allen Key
Open
Indoor Unit
Outdoor Unit
Close
Close
Close
Discharge
Valve
Suction
Valve
Gas Side
Liquid Side
Vacuum
Pump
Low
Hi
SPECIAL PRECAUTIONS WHEN DEALING WITH R410A UNIT
R410A is a near azeotrope refrigerant blend of hydro fluorocarbon (HFC) which is environmental friendly. It has Zero
Ozone Depletion Potential (ODP=0) and this conforms to Montreal Protocol regulations. It has no flame propagation and
a low toxic refrigerant (rated as A1 by ARI). R410A is a mixture of R32 (50%) and R125 (50%).
POE oil is used as lubricant for R410A compressor, which is different from the mineral oil used for R22 compressor.
During installation or servicing, extra precaution must be taken not to expose the R410A system too long to moist air.
Residual POE oil in the piping and components can absorb moisture from the air.
Refrigerant R410A is more easily affected by dust of moisture compared with R22, make sure to temporarily cover the
ends of the tubing prior to installation.
No additional charge of compressor oil only is permitted.
No refrigerant other than R410A is permitted.
Tools designed specifically for R410A only.
i) Manifold gauge and charging hose
ii) Gas leak detector
iii) Refrigerant cylinder/charging cylinder
iv) Vacuum pump c/w adaptor
v) Flare tools
vi) Refrigerant recovery machine
!!
!!
! CAUTION
R410A must be charged as liquid. Usually R410A cylinder is equipped with a dip-pipe for liquid withdrawal.
If there is no dip-pipe, the cylinder should be inverted so as to withdraw liquid R410A from the valve.
Do not top-up when servicing leak, as this will reduce the unit performance. Vacuum the unit thoroughly and then
charge the unit with fresh R410A according to the amount recommended in the specification.
Do not touch the compressor or refrigerant piping when the chiller is running. If necessary wear protective gloves.
Additional charge
The refrigerant is pre-charged in the outdoor unit. If the
piping length is less than 7.62m (25 ft), then additional
charge after vacuuming is not necessary. If the piping length
is more than 7.62m (25 ft), then use the additional charge
valve as indicated in the table below.
1-11
English
IR signal receiver
When an infrared remote control operating signal has been
transmitted, the signal receiver on the indoor unit will
make a <beep> sound to confirm acceptance of the sig-
nal transmission.
INDICATOR LIGHTS
Cooling unit
The table shows the LED indicator lights for the air
conditioner unit under normal operation and fault conditions.
The LED indicator lights are located at the bottom right side
of the air conditioner unit.
LED Indicator Lights : Normal Operation And Fault Conditions For Cooling Unit
LED Indicator Lights for Cooling Unit
Power ON
Timer
Sleep mode
Dry mode
LED Indicator Lights
IR Receiver
Operation / Fault Indication Action
Timer on.
Sleep mode on.
Dry mode.
Frost prevention. Clean the filter and switch to high fan.
Room air sensor contact loose/short. Call your dealer.
Indoor coil sensor contact loose/short.
Call your dealer.
Sensor contact problem, compressor
Call your dealer.
overload protection trip or gas leak
ON or OFFON Blinking
Power Dry Timer Sleep
Continuously
once every 2 sec.
twice every 2 sec.
3 times every 2 sec.
Charge operation
This operation must be done by using a gas cylinder and a
precise weighing machine. The additional charge is topped-
up into the outdoor unit using the suction valve via the
service port.
Remove the service port cap.
Connect the low pressure side of the charging gauge to
the suction service port center of the cylinder tank and
close the high pressure side of the gauge. Purge the air
from the service hose.
Start the air conditioner unit.
Indoor Unit
Outdoor Unit
Liquid Side
Discharge
Valve
Suction
Valve
Gas Side
Close
Close
Close
Open
Check
Valve
Low Hi
Model 10 m/32.8 ft 12 m/39.4 ft 15 m/49.2 ft
071 / 101 / 151 35 65 -
201 35 65 110
251 / 301 90 165 280
071R / 101R /151R 50 90 -
201R 60 110 185
251R / 301R 120 220 370
Model 10 m/32.8 ft 12 m/39.4 ft 15 m/49.2 ft
311 80 150 255
301R 110 200 335
Additional charge in gram (R410A)
Open the gas cylinder and low pressure charging valve.
When the required refrigerant quantity is pumped into
the unit, close the low pressure side and the gas cylin-
der valve.
Disconnect the service hose from service port. Put back
the service port cap.
Additional charge in gram (R22)
1-12
LED Indicator Lights : Normal Operation And Fault Conditions For Heat Pump Unit
Cooling mode.
Dry mode.
Fan mode.
Heat mode.
Auto mode in heating operation.
Auto mode in cooling operation.
Defrost operation.
Compressor overload protection. Call your dealer.
Indoor coil sensor contact loose/short. Call your dealer.
Outdoor coil sensor contact loose/short. Call your dealer.
Room air sensor contact loose/short. Call your dealer.
If the system is in cool mode or heat mode (with the sleep function off), the sensor
may have a contact problem, compressor overload protection trip or gas leak.
Normal Operation/Fault Condition Action
Cool Dry Fan Heat Sleep
Heat pump unit
The table shows the LED indicator lights for the air
conditioner unit under normal operation and fault conditions.
The LED indicator lights are located at the bottom right
side of the air conditioner unit.
The heat pump units are equipped with an “auto” mode
sensor whereby it will provide reasonable room temperature
by switching automatically to either “cool” or “heat” mode,
according to the temperature set by the user.
LED Indicator Lights For Heat Pump Unit
Cooling mode Dry mode Heat/Fan mode Sleep mode
(red/green)
ON or OFF
ON
Blinking
1-13
English
Cooling
Dry
Horizontal
25°C/77°F
AIR CONDITIONER UNIT OPERATION
Dry mode
When the air humidity is high, the unit can operate in dry
mode. Press <MODE> button and choose <DRY>.
If the room temperature is 2°C/35.6°F higher than the set
temperature, the air conditioner will operate under cooling
mode until it reaches within the 2°C/35.6°F range of
difference compared to the set temperature before it
converts to dry mode.
If the room temperature is within the 2°C/35.6°F range of
difference compared to the set temperature, it will
directly operate under dry mode.
The unit will operate at LOW speed under dry mode.
Heat mode (for heat pump unit only)
• When the unit is switched on from cold start or
defrosting cycle, the indoor fan will start to operate only
after the coil reaches the desired temperature.
When the set temperature is achieved, the indoor fan will
operate until the coil cannot provide anymore
additional heat.
Horizontal air flow control
For more effective air circulation, you can manually adjust
the air discharge grille to the left or right.
During cool mode operation and dry mode operation, do
not direct the air discharge louver downwards for too long.
If operating continues in this way, condensation may occur
on the louver, thus resulting in drippings.
Hot Keep (for heat pump only)
During compressor cut off, the indoor fan can be switched
to
(i) ON (default) or
(ii) OFF or
(iii) Interval on and off
by setting the slide switch shown in the diagram.
The switch is located at the front frame cover (next to
the ON/OFF switch).
NOTE : When the option is selected, the power supply of
the unit need to be reset in order to activate the
function.
Overheating protection (for heat pump unit only)
In case the internal and/or the external temperature is to
high, or the filter is dirty and clogged up, the refrigerant
may be overheated. The compressor will cut out when the
condensing temperature reaches 62°C/143.6°F.
Frost prevention
When the air filter is dirty, the evaporating temperature
will decrease and eventually cause frosting.
The LED light will blink to indicate that the filter is dirty.
If the evaporating temperature reaches -2°C/28.4°F, the
unit will trip and defrost.
Fan speed and rated cooling capacity
The rated cooling capacity is provided at the maximum
fan speed.
The cooling capacity is lower when the unit is operating at
MEDIUM and LOW fan speed.
ON/OFF switch
HOT KEEP
OFF
INTERVAL
ON
1-14
! Warning
Disconnect from the main power supply before servicing the air conditioner unit.
DO NOT pull out the power cord when the power is ON. This may cause serious electrical shocks which may result
in fire hazards.
HOW TO INSTALL
DUAL ACTION ELECTROSTATIC AIR PURIFYING
AND DEODORIZING FILTER MEDIA AND FILTER FRAME
ACTION 1-
ELECTROSTATIC AIR PURIFYING FILTER
Removes microscopic dust, smoke and small invisible
particles to keep the room air clean with pre-charged
electrostatic polypropylene filter.
ELECTROSTATIC FILTER
ACTION 2-
DEODORIZING FILTER
Removes unwanted smells and odors in the air and keeps
the room air fresh with activated carbon filter.
STANDARD OPERATING CONDITIONS
Heat Pump Unit
Temperature Ts °C/°F Th °C/°F
Minimum indoor
temperature
Maximum indoor
temperature
Minimum outdoor
temperature
Maximum outdoor
temperature
Ts: Dry bulb temperature. Th: Wet bulb temperature.
Cooling unit
Temperature Ts °C/°F Th °C/°F
Minimum indoor
19.4 / 66.9 13.9 / 57.0
temperature
Maximum indoor
26.7 / 80.1 19.4 / 66.9
temperature
Minimum outdoor
19.4 / 66.9 13.9 / 57.0
temperature
Maximum outdoor
46 / 114.8 24 / 75.2
temperature
10 / 50
26.7 / 80.1
-8 / 17.6
24 / 75.2
-
-
-9 / 15.8
18 / 64.4
1-15
English
SERVICE AND MAINTENANCE
Maintenance Procedures
1. Remove any dust adhering to the filter by using a vacuum cleaner or
wash in lukewarm water (below 40°C/104°F ) with a neutral cleaning
detergent.
2. Rinse the filter well and dry before placing it back onto the unit.
3. Do not use gasoline, volatile substances or chemicals to clean the filter.
1. Clean any dirt or dust on the grille or panel by wiping it off with a soft
cloth soaked in lukewarm water (below 40°C/104°F) and a neutral
detergent solution.
2. Do not use gasoline, volatile substances or chemicals to clean the
indoor unit.
Period
At least once
every 2 weeks.
More frequently if
necessary.
At least once
every 2 weeks.
More frequently if
necessary.
Service Parts
Indoor air filter
Indoor unit
WHEN THE UNIT IS NOT USED FOR AN EXTENDED PERIOD OF TIME
Operate the unit for 2 hours
with the following setting.
Operating mode : cool
Temperature : 30°C/86°F
Remove the power plug.
If you are using an independent
electric circuit for your unit,
cut off the circuit.
Remove the batteries in the
remote control.
! Caution
Do not operate any heating apparatus too close to the air conditioner unit. This may cause the plastic panel to melt
or deform as a result of the excessive heat.
! Warning
Disconnect from the main power supply before servicing the air conditioner unit.
DO NOT pull out the power cord when the power is ON. This may cause serious electrical shocks which may
result in fire hazards.
! Caution
1. The electrostatic air purifying and deodorizing filter
should be replaced once every 6 months or when the
filter changes color to brownish, whichever is sooner.
2. Used dusty filters should be disposed and shouldn't be
reused, even if it has been cleaned and washed.
3. The filter is a consumable part which you can purchase
from your air conditioner dealer.
4. Use the new filter immediately once it has been taken
out from its sealed packing. Do not unpack the new
filter too early before it is actually used as this may
decrease its deodorizing effect.
1-16
If any malfunction of the air conditioner unit is noted, immediately switch off the power supply to the unit.
Check the following fault conditions and causes for some simple troubleshooting tips.
TROUBLESHOOTING
Causes / Action
- Protection against frequent starting. Wait for 3 to 4 minutes for
the compressor to start operating.
- Power failure, or the fuse needs to be replaced.
- The power plug is disconnected.
- It is possible that your delay timer has been set incorrectly.
- If the fault persist after all these verifications, please
contact the air conditioner unit installer.
- The air filter is dirty.
- The doors or windows are open.
- The air suction and discharge are clogged.
- The regulated temperature is not high enough.
- Odours may be caused by cigarettes, smoke particles, perfume
etc. which might have adhered onto the coil.
- This is caused by air humidity after an extended period of
operation.
- The set temperature is too low, increase the temperature setting
and operate the unit at high fan speed.
- Switch off unit and call dealer.
- Refrigerant fluid flowing into the evaporator coil.
Fault
1. The compressor does not operate 3 minutes after the air
conditioner unit is started.
2. The air conditioner unit does not operate.
3. The air flow is too low.
4. Discharge air flow has bad odour.
5. Condensation on the front air grille of the indoor unit.
6. Water flowing out from the air conditioner unit.
7. Hissing air flow sound from the air conditioner unit during
operation.
If the fault persists, please call your local dealer/serviceman.
2-1
Français
Ce manuel fournit les procédures d’installation pour assurer le bon fonctionnement et la sécurité de cet appareil.
Des ajustements peuvent être nécéssaires pour suivre les réglementations locales.
Avant d’installer et de faire fonctionner le climatiseur, lisez attentivement ce manuel et conservez le.
MANUEL D’INSTALLATION
CLIMATISEURS SPLIT SYSTEM MONTAGE MURAL
MODÈLE
IM-WM1-0302(2)-Acson
FROID SEUL (R22)
Modèle de Référence Modèle
WM301 AWM301
SL30C ALC30C
SL30B ALC30B
FROID SEUL (R410A)
Modèle de Référence Modèle
5WM311 A5WM311
5SL28C A5LC28C
POMPE À CHALEUR (R22)
Modèle de Référence Modèle
WM301R AWM301R
SL30CR ALC30CR
SL30BR ALC30BR
POMPE À CHALEUR (R410A)
Modèle de Référence Modèle
5WM301R A5WM301R
5SL28CR A5LC28CR
Part No.: A08019025521
2-2
! Avertissement
Vérifier les points suivants au cours de l’installation.
Ne pas installer l’appareil où il peut se produire des fuites de gaz inflammable.
En cas de fuite et accumulation de gaz autour de l’appareil, il y a risque d’incendie.
S’assurer que le tuyau d’évacuation du condensat est correctement branché.
Si le tuyau d’évacuation n’est pas correctement branché, les éventuelles fuites d’eau risquent de mouiller
le mobilier.
Ne pas surcharger l’unité (en fluide frigorigène).
Cet appareil est préchargé en usine. Une charge trop importante risque de provoquer une surcharge
électrique ou d’endommager le compresseur.
S’assurer que le panneau supérieur de l’appareil est remis en place après l’installation ou l’entretien.
Avec un panneau mal fixé l’appareil va fonctionner bruyamment.
IMPORTANT
NE PAS INSTALLER OU UTILISER LE CLIMATISEUR DANS UNE BUANDERIE.
! Attention
L’installation et la maintenance doivent être exécutées par une personne qualifiée qui est familiarisée avec les lois
et réglementations en vigueur, et aussi expérimentée dans ce type d’équipements.
Tous les câblages doivent répondre aux réglementations électriques nationales.
Avant de commencer le raccordement suivant le schéma électrique, s’assurer que la tension nominale de l’appareil
corresponde bien à celle indiquée sur la plaque signalétique.
L unité doit être raccordée à la TERRE pour prévenir tous les risques possibles dûes à un défaut d’isolation.
Aucun câble électrique ne doit toucher la tuyauterie du réfrigérant, le compresseur ou les pièces mobiles des moteurs
de ventilation.
Avant l’installation ou l’entretien du climatiseur, s’assurer que l’appareil est éteint (OFF).
SOMMAIRE
- Contour et Dimensions page i-ii
- Précautions de Sécurité page 2
- Diagramme D’installation page 3
- Installation de L’unité Extérieure page 3
- Installation du Tuyau D’orifice page 4
- Installation de L’unité Intérieure page 6
- Raccordements des Tuyauteries page 7
- Raccordement Électrique page 8
-
Précautions Spéciales Pour Les Appareils au R410A
page 10
- Aspiration et Chargement page 10
- L’indicateur S’allume page 11
- Opération du Climatiseur page 13
- Conditions Standard de Fonctionnement page 14
- Filtre Électrostatique page 14
- Entretien et Maintenance page 15
- Analyse des Causes de Dysfonctionnement
du Climatiseur page 16
Avant de faire fonctionner l’appreil, veuillez bien lire les précautions de sécurité suivantes.
PRÉCAUTIONS DE SÉCURITÉ
2-3
Français
DIAGRAMME D’INSTALLATION
Grilles de reprise d’air
Grilles de Ventilation
Reprise Air
Tuyauteries Frigorifiques
Tuyau D’evacuation
Cadre Avant
Chassis Arriere
Interrupteur ON/OFF
Filtre à air
Récepteur
de Signal
Led de Visualisation
Conduit de ventilation
Unité Extérieure
Unité Intérieure
INSTALLATION DE L’UNITÉ EXTÉRIEURE
Obstacle
L’unité extérieure (ou groupe de condensation) doit être
instalée dans un endroit où aucun obstacle ne doit perturber
la circulation de l’air, aussi bien à l’aspiration qu’au
refoulement du ventilateur (risque de recyclage d’air chaud).
Respecter les dégagements minimum prévus (voir tableau
ci-dessous). Choisir un emplacement le moins exposé
possible à l’ensoleillement; l’entré d’air sur l’unité extérieure
ne devra pas être supérieure à la température ambiante
(maximum 45°C/113°F).
Dégagements minimum
Remarques : En cas d’obstacles de part et d’autre de l’unité
d’une hauteur supérieure à 2 mètres ou toute obstruction d’air
sur le dessus de l’unité, augmenter sensibelment les
dégagements minimum prévus.
Obstacle
Obstacle
Obstacle
A
B
C
D
Refoulement d’air
Reprise Air
Entrée d’air
Refoulement
Entrée d’air
Accès de service
Dimension A B C D
Minimum
Distance, mm 300 1000 300
(Pouce) (11,8) (39,4) (11,8) (19,7)
500
2-4
INSTALLATION DU TUYAU D’ORIFICE
Tuyau d’orifice
1
2
34
1
2
3
4
Unité Extérieure
Intérieur
Orifice
Tuyau de raccord
Écrou évasé de 3/8 po (femelle)
Assemblage par évasement de 3/8 po (mâle)
! Avertissement
Le tuyau d’orifice doit être installé dans la bonne direction (illustration ci-dessus).
Une orientation incorrecte peut causer l’échec du système d'exploitation.
Remarque: Cette installation ne vaut que pour WM301 / SL30B et WM301 / SL30C
A. Installation de l’orifice du tuyau de l’unité extérieure (où l’espace pour l’installation est assez large)
Tuyau d’orifice
Étapes:
1. Raccorder directement l’écrou “Femelle” du tuyau
d’orifice sur le robinet de liquide.
2. Évaser le tuyau de liquide et le brancher au joint
“Mâle” du tuyau d’orifice.
Tuyau
d’orifice
Tuyau de
liquide
Étape 2
Étape 1
2-5
Français
Étape 1
Tuyau d’orifice
Étape 3
Étape 2
Étape 4
Tuyau de liquide
Braseur
C. Installation du tuyau d’orifice sur l’unité intérieure
Unité Intérieure
Tuyau d’orifice
B. Installation de l’orifice du tuyau de l’unité extérieure (où l’espace pour l’installation est limité)
Si le tuyau d’orifice ne peut pas être connecté directement au robinet de liquide à cause d’un manque d’espace, on peut
l’installer au milieu du tuyau de liquide.
Étapes:
1. Évaser le tuyau de liquide et le brancher au robinet de
liquide.
2. Braser un joint “Mâle” supplémentaire au tuyau de
liquide.
3. Raccorder l’écrou “Femelle” du tuyau d’orifice au joint
“Mâle”.
4. Évaser un autre tuyau de liquide et le brancher au joint
“Mâle” du tuyau d’orifice.
Étapes:
1. Braser un joint “Mâle”
supplémentaire au tuyau de
liquide.
3. Évaser un autre tuyau de liquide
et le brancher au joint “Mâle” du
tuyau d’orifice.
2. Raccorder l’écrou “Femelle” du
tuyau d’orifice au joint “Mâle”.
Tuyau de liquide
Braseur
Tuyau de liquide
Tuyau d’orifice
Tuyau de liquide
Tuyau d’orifice
Tuyau de liquide
Tuyau d’orifice
Tuyau de liquide
Tuyau d’orifice
2-6
50mm
50mm
50mm
INSTALLATION DE L’UNITÉ INTÉRIEURE
Espace d’entretien et
de reparation
Direction de
la circulation
d’air
Plus haut que le
niveau des yeux
Installer l’unité intérieure de traitement d’air de façon à ce
qu’il n’y ait aucun obstacle sur la circulation de l’air
(risque de recyclage de l’air refroidi au refoulement de l’unité
et l’air à l’entrée). Veuillez respecter l’écartement
d’installation illustré sur le diagramme. Ne pas exposer l’unité
intérieure à l’influence directe de l’éclairage. L’emplacement
de l’unité, doit permettre une évacuation aisée des condensats,
et permettre une evacuation aisee des condensats, et doit être
suffisamment loin des portes.
Montage de la platine support
S’assurrer que le mur de support soit suffisamment résistant,
pour supporter le poids de l’unité et éviter toutes vibrations.
Selon la composition du mur, utiliser des vis chevilles
appropriées pour la fixation de la platine support.
Utiliser la jauge à niveau pour le montage horizontal, puis la
fixer avec 4 vis appropriées.
Dans le cas de sortie arrière des tuyauteries, percer le trou
Ø 65mm pour les canalisations à l’aide d’une scie cloche. Le
trou aura une légère pente vers l’unité extérieure (Voir figure).
Orientation des tuyauteries
Retirer les vis qui retiennent le panneau de devant.
Acheminement de la tuyauterie
1
2
3
4
5
Plaque d’Installation
Le Marquage-Hors ligne
Le fil
À l’intèrieur
À l’extèrieur
Inclinaison de 1/50
Acheminement de la tuyauterie
L’unité d’évacuations des condensats de l’unité interieure
devra être, dans la mesure du possible, dirigé vers la sortie
arrière des tuyauteries à travers le mur de support (voir
figure). Avant d’orienter le tubing, déclipser le support de
tube. Cintrer les tubes frigorifiques avec précaution et les
diriger vers la sorte choisie. Ne pas oublier de passer le câble
d’alimentation électrique dans l’unité intérieure à travers le
mur en même temps que les tuyauteries. Ne pas raccorder
le câble. Laisser une longueur de câble suffisante pour
permettre la connection ultérieure. Relier ensemble les tubes
frigorifiques, le flexible d’évacuation des condensats et le
câble électrique.
Mise en place de l’unite de la platine support
Positionner dans un premier temps l’unité intérieure sur la
languette d’accrochage supérieure de support. Pour vous
assurer que les crochets sont correctement installés sur la
plaque d’installation, essayez de les faire légèrement bouger
de gauche à droite.
Evacuation
d’eau de
Condensation
plongé
dans l’eau
Fuite
d’eau
Évacuation des condensats
Le tube d’évacuation des condensats de l’unité devra être,
dans la mesure du possible, dirigé vers la sortie arriere des
tuyauteries a travers le mur de support. Evitez les
situations susceptibles de causer une fuite d’eau.
Câble de liaison
Tuyau d’evacuation
J
Incorrect
J
Incorrect
J
Incorrect
j
Correct
Fuite
d’eau
Fuite
d’eau
Drainage De L’eau
2-7
Français
Ø Tube, D A (mm)
Pouce mm Impérial Normal
1/4" 6,35 1,3 0,7
3/8" 9,52 1,6 1,0
1/2" 12,70 1,9 1,3
5/8" 15,88 2,2 1,7
Longueur des tuyauteries et différence de niveau
Pour un bon fonctionnement des unités, il est impératif de
respecter la longueur maximum des tuyauteries indiquée
dans le tableau ci-dessours, de respecter le nombre de coudes
maximum autorisé, et de ne pas dépasser la différence de
niveau entre l’unite intérieure et l’unite extérieure.
Tableau des caracteristiques valables pour les unites froid
seul et reversibles.
RACCORDEMENTS DES TUYAUTERIES
Coupe des Tubes Cuivre
Travail des tuyauteries
Ne pas utiliser de tuyauteries en cuivre encrassé ou
endommagé. Ne pas retirer les bouchons en plastique ou
caoutchouc et les écrous en laiton des vannes, raccords, tubes
et serpentins jusqu’à ce que les tuyauteries d’apiration ou de
liquide soient prêtes à être connectées aux vannes et raccords.
S’il est nécessaire de braser, s’assurer que de l’azote passe
dans les serpentins et raccords pendant le brasage, pour éviter
les dépôts de suie sur les faces intérieures des tubes de cuivre.
Couper le tuyau de raccordement avec un coupe-tube.
Ébarber les bords coupés des tuyaux à l’aide d’un alésoir. Tenir
l’extrémité du tuyau vers le bas pour empêcher la limaille
d’entrer dans le tuyau.
Relier les écrous ‘flare’ montés sur les connexions des unités
intérieure et extérieure aux tubes de cuivre.
Évaser le tuyau avec longueur supplémentaire au-dessus de
l’outil à évaser comme indiqué sur le tableau.
Le bord évasé doit être régulier et ne présenter aucune
craquelure ou éraflure.
! Attention
Dans l’unité de refroidissement WM301 on utilise un orifice, attaché à la tuyauterie d'eau de l’unité intérieure, comme
dispositif d’expansion.
Raccordement de la tuyauterie aux unités
Aligner les tubes et serrer l’écrou à la main d’abord.
Enfin, serrer l’écrou à l’aide d’une clef dynamométrique
jusqu’au clic.
Remarque: La charge complète de gaz se trouve dans l’unité
extérieure jusqe’à une longueur nominale de 7,62 mètres
/
25ft.
, aucun complément en réfrigérant n’est nécéssaire.
12,7 (1/2) 55 (40,6)
15,88 (5/8) 65 (48,0)
6,35 (1/4) 18 (13,3)
9,53 (3/8) 42 (31,0)
Ø Tuyau mm / (pouce) Couple Nm / (Ft-lb)
Clef Dynamométrique
Clef d'immobilisation
Tube de l'unité Intérieure
Ecrou
Tube avec dudgeon
Raccord à visser
Modèle 07/10 15 20 25 30
Longueur max, m (ft), L
12
(39,4)
12
(39,4)
15
(49,2)
15
(49,2)
35
(114,8)
Elevation max m (ft), H 5 (16,4) 5 (16,4) 8 (26,2) 8 (26,2) 15 (49,2)
Nombre de coude max 10 10 10 10 10
Ø racc. Tube liquide 1/4" 1/4" 1/4" 3/8" 3/8"
Ø racc. Tube aspiration 3/8" 1/2" 5/8" 5/8" 5/8"
Unité Extérieure
L
H
Unité Intérieure
Ebavurage
Tube Cuivre
Dudgeonniere
2-8
L
COMP
N2
N1
N
T
COMP
L
N
S
R
COMP
N2
N1
L
COMP
N
RACCORDEMENT ÉLECTRIQUE
Module refroidisseur
IMPORTANT : * Ces valeurs sont données à titre indicatif seulement; elles doivent être vérifiées et ajustées en fonction
des normes et de la réglementations en vigueur. Elles dépendent aussi du type d’installation et du choix
des conducteurs utilisés.
** Le voltage adéquat doit être vérifié avec les données de l’étiquette sur l’appareil. ETL n’est applicable
que pour une alimentation électrique de 60Hz.
COMP
N2
N1
L
COMP
R
S
N
L
N
L
WM301 VS SL30C
WM07 / 10 / 15 / 20 / 25 / 301 VS SL07 / 10 / 15 / 20 / 25 / 30B
5WM311 VS 5SL28C
Il doit y avoir un interrupteur à double
pôles avec un intervalle de contact de
3mm minimum et un coupe-circuit/
fusible comme recommandé dans le
circuit d’installation fixe.
!
Bornier De
L’unité Extérieure
Cordon Electrique
Cordon Electrique
Il doit y avoir un interrupteur à double
pôles avec un intervalle de contact de
3mm minimum et un coupe-circuit/
fusible comme recommandé dans le
circuit d’installation fixe.
!
Bornier De
L’unité Intérieure
Bornier De
L’unité Extérieure
Cordon Electrique
Il doit y avoir un interrupteur à double
pôles avec un intervalle de contact de
3mm minimum et un coupe-circuit/
fusible comme recommandé dans le
circuit d’installation fixe.
!
WM201 / 251 VS SL20 / 25B (3 Ph)
Bornier De
L’unité Intérieure
Bornier De
L’unité Extérieure
L
COMP
N2
N1
N
T
COMP
L
N
S
R
Il doit y avoir un interrupteur à double
pôles avec un intervalle de contact de
3mm minimum et un coupe-circuit/
fusible comme recommandé dans le
circuit d’installation fixe.
!
Cordon Electrique
Bornier De
L’unité Intérieure
Bornier De
L’unité Extérieure
WM301 VS SL30C (3 Ph)
Pince A Fil
Câble De
Liaison
Tous les fils doivent être fermement connectés.
Aucun fils ne doivent toucher les tubes frigorifiques, le
compresseur ou une autre partie mobile du moteur de ventilateur.
Le câble de liaison entre l’unité intérieure et extérieure
doit être fixé au boitier de raccordement à l’aide de
l’attache comme indiqué dans la figure ci-contre.
Le cordon électrique doit être êquivalent à H05RN-F
(245IEC57) au minimum.
Modèle Intérieure WM 071/ 101/ 151 WM201/ 251/ 301 5WM311 WM301 WM201/ 251/ 301 WM301
Extérieure SL07/ 10/ 15B SL20/ 25/ 30B 5SL28C SL30C SL20/ 25/ 30B SL30C
Tension d’alimentation**
220V-240V/ 1Ph/ 50Hz + ou 208V-230V/ 1Ph/ 60Hz + 380V-415V/ 3Ph/ 50Hz +N+
Section du câble d’alim* mm
2
1,5 2,5 2,5 4 1,5 1,5
Nombre de conducteurs 333355
Section du câble de liaison* mm
2
1,5 2,5 2,5 2,5 1,5 1,5
Nombre de conducteurs 333444
Fusible aM A 15 20 20 25 15 15
Bornier De
L’unité Intérieure
2-9
Français
Module pompe à chaleur
4WV
OF
COMP
N2
N1
L
4WV
OF
COMP
N
4WV
OF
COMP
N2
N1
L
4WV
A
OF
COMP
L
N
L
N
WM301R VS SL30CR
WM07 / 10 / 15 / 20 / 25 / 301R VS SL07 / 10 / 15 / 20 / 25 / 30BR
5WM301R VS 5SL28CR
Il doit y avoir un interrupteur à double
pôles avec un intervalle de contact de
3mm minimum et un coupe-circuit/
fusible comme recommandé dans le
circuit d’installation fixe.
!
Bornier De
L’unité Intérieure
Bornier De
L’unité Extérieure
Cordon Electrique
Câble De Liaison De La Sonde De
Température Obligatoire (longueur 8m) Fourni
Avec L’Unité Intérieure
Il doit y avoir un interrupteur à double
pôles avec un intervalle de contact de
3mm minimum et un coupe-circuit/
fusible comme recommandé dans le
circuit d’installation fixe.
!
Bornier De
L’unité Intérieure
Bornier De
L’unité Extérieure
Cordon Electrique
Câble De Liaison De La Sonde De
Température Obligatoire (longueur 8m) Fourni
Avec L’Unité Intérieure
4WV
OF
COMP
N2
N1
L
4WV
OF
COMP
L
N
S
R
N
T
4WV
OF
COMP
N2
N1
L
4WV
OF
COMP
L
N
A
S
R
N
T
WM301R VS SL30CR (3 Ph)WM201 / 251R VS SL20 / 25BR (3 Ph)
Câble De Liaison De La Sonde De
Température Obligatoire (longueur 8m) Fourni
Avec L’Unité Intérieure
Câble De Liaison De La Sonde De
Température Obligatoire (longueur 8m) Fourni
Avec L’Unité Intérieure
Il doit y avoir un interrupteur à double
pôles avec un intervalle de contact de
3mm minimum et un coupe-circuit/
fusible comme recommandé dans le
circuit d’installation fixe.
!
Bornier De
L’unité Intérieure
Bornier De
L’unité Extérieure
Cordon Electrique
Bornier De
L’unité Intérieure
Bornier De
L’unité Extérieure
Il doit y avoir un interrupteur à double
pôles avec un intervalle de contact de
3mm minimum et un coupe-circuit/
fusible comme recommandé dans le
circuit d’installation fixe.
!
Cordon Electrique
IMPORTANT : * Ces valeurs sont données à titre indicatif seulement; elles doivent être vérifiées et ajustées en fonction
des normes et de la réglementations en vigueur. Elles dépendent aussi du type d’installation et du choix
des conducteurs utilisés.
** Le voltage adéquat doit être vérifié avec les données de l’étiquette sur l’appareil. ETL n’est applicable
que pour une alimentation électrique de 60Hz.
Modèle Intérieure WM 071/ 101/ 151 R WM201/ 251/ 301 R 5WM301R WM301 R WM201/ 251/ 301 R WM301 R
Extérieure SL07/ 10/ 15BR SL20/ 25/ 30BR 5SL28CR SL30CR SL20/ 25/ 30BR SL30CR
Tension d’alimentation**
220V-240V/ 1Ph/ 50Hz + ou 208V-230V/ 1Ph/ 60Hz + 380V-415V/ 3Ph/ 50Hz +N+
Section du câble d’alim* mm
2
1,5 2,5 2,5 4 1,5 1,5
Nombre de conducteurs 3 3 3355
Section du câble de liaison* mm
2
1,5 2,5 2,5 2,5 1,5 1,5
Nombre de conducteurs 5 5 5664
Fusible aM A 15 20 20 25 15 15
2-10
ASPIRATION ET CHARGEMENT
Purge des tuyauteries et de l’unité intérieure
Excepté l’unité extérieure (groupe de condensation) qui
contient la charge complète de réfrigérant, l’unité intérieure
et les tubes des liaisons frigorifiques doivent être purgés de
l’air contenu dans le circuit.
Enlever le bouchon central, ainsi que le bouchon de la
prise de pression sur chaque vanne.
Raccorder le centre de la jauge de chargement à la pompe
à vide.
Raccorder la jauge de chargement à l’orifice de service
de la valve à trois voies.
Démarrer la pompe à vide. Évacuer pendant environ 30
minutes. La période d’évacuation varie selon la capacité
de la pompe à vide. S’assurer que l’aiguille de la jauge
de chargement se soit déplacée vers -76 mmHg
(0~76mmHg).
Avertissement
Si l'aguille de la jaudge ne se déplace pas vers 0 ~ 76mm
Hg, vérifier qu'il n'y ait pas de fuite de gaz (à l'aide d'un
détecteur de gaz) au niveau des raccordements évasés des
unités intérieures et extérieures, puis réparer la fuite avant
de passer à l'étape suivante.
Fermer la valve de la jauge de chargement et éteindre la
pompe à vide.
Sur l’unité extérieure, ouvrir la valve de succion (3 voies)
et la valve de liquide (2 voies) (dans le sens inverse des
aiguilles d’une montre) à l’aide d’une clé pour vis
hexagonales de 4mm.
PRÉCAUTIONS SPÉCIALES POUR LES APPAREILS AU R410A
Le R410A est un mélange quasi-azéotrope de frigorigène d’hydrofluorocarbure (HFC), sans danger pour l’environnement.
Il a un potentiel d’appauvrissement de l’ozone de zéro (PAO=0), ce qui est conforme aux dispositions du Protocole de
Montréal. Il est coté A1 (frigorigène peu toxique sans propagation de flamme) par l’ARI. Le R410A est un mélange de R32
(50%) et de R125 (50%).
L’huile POE est utilisé comme lubrifiant pour les compresseurs R410A, et elle est différent par rapport à l’huile minérale
utilisée pour les compresseurs R22. Lors de l’installation ou de la maintenance, des précautions supplémentaires doivent
être adoptées pour ne pas exposer le système R410A trop de temps à l’air humíde. L’huile POE résiduelle restée dans les
tuyauteries et les équipments peut absorber l’humidité de l’air.
Le réfrigérant R410A est plus facilement affecté par l’humidité par rapport à R22, s’assurer de protéger temporairement
les extrémités des tuyauteries avant l’installation.
Il n’est pas permis de rajouter de l’huile dans le compresseur.
Aucun autre réfrigérant que le R410A n'est permis.
Garder des instruments seulement pour le R410A
i) Manifold et flexible de charge
ii) Détecteur de fuite de gaz
iii) Cylindre de charge/bouteille de réfrigérant
iv) Adaptateur c/w pompe à vide
v) Chalumeau et outillage à flare
vi) Machine de récupération du réfrigérant
!!
!!
! AVERTISSEMENT
La charge du R410A doit être réalisée en phase liquide. Normalement la bouteille de R410A est équipé d’un tube
plongeur pour le prélèvement du liquide. Si la bouteille n’est pas pourvu de ce tube elle doit être inversée de façon à
prélever le liquide au moyen de la vanne.
Ne pas rajouter en cas de réparation de fuites afin de ne pas réduire les performances de l’appareil. Vidanger complètement
l’unité pour la recharger avec du R410A frais suivant le poids préconisé dans les spécifications techniques.
Ne pas toucher le compresseur ou la tuyauterie du réfrigérant lorsque le mini-chiller est en marche. Porter des gants si
besoin est.
Complément De Charge
La charge complète de gaz se trouve dans l’unité extérieure,
jusqu’à une longueur nominale de 7,62m (25 ft), aucun
complément de charge n’est nécéssaire. Si la longueur de la
liaison est supérieure à 7,62m (25 ft), utilisez alors la valve
de charge supplémentaire comme indiqué dans le tableau
ci-dessous.
Unité Intérieure
Unité Extérieure
Côté liquide
Côté
gaz
Ouvert
Fermé
Hi
Lo
Valve De
Deversement
Valve De
Succion
Fermé
Pompe a
vide
Fermé
Prise de Pression
Unité Extérieure
Vannne 3 Voies
Ecrou
Tuyauteries
Frigorifiques
Cléf Allen
2-11
Français
IR Récepteur de signal
Lorsqu’un signal d’opération à infrarouge a été transmis,
le récepteur de signal de l’unité intérieure émet un <bip>
pour confirmer l’acceptation de transmission du signal.
L’INDICATEUR S’ALLUME
Module refroidisseur
Le tableau montre que l’indicateur LED s’allume pour l’air
climatisé dans des conditions de fonctionnements normales
et par défaut. Les leds de visualisation apparaissent lorsque
le climatseur est sous tension, dans la fenêtre de couleur bleu
foncé située dans la partie inférieure droite du climatiseur.
L’indicateur LED s’allume: Conditions de fonctionnement normales et par défaut pour l’unité de refroidissement
L’indicateur LED s’allume pour l’unité de
refroidissement
Interrupteur
Minuterie
Mode de
sommeil
Mode
déshumidification
LED De Visualisation
IR Récepteur
De Signal
Opération de chargement
Cette opération nécessite impérativement l’utilisation d’un
cylindre de charge ou une balance de précision. Le
complement de charge se fait sur l’unité extérieure par la vanne
d’aspiration via la prise de pression de la vanne de service.
Enlever le bouchon de la vanne de service.
Raccorder le côté de basse pression de la jauge de
chargement à l’orifice de succion du réservoir cylindrique
et fermer le côté de haute pression de la jauge. Éliminer
l’air du tuyau de service.
Mettre le climatisateur en marche.
Modèle 10 m/32,8 ft 12 m/39,4 ft 15 m/49,2 ft
071 / 101 / 151 35 65 -
201 35 65 110
251 / 301 90 165 280
071R / 101R /151R 50 90 -
201R 60 110 185
251R / 301R 120 220 370
Modèle 10 m/32,8 ft 12 m/39,4 ft 15 m/49,2 ft
311 80 150 255
301R 110 200 335
Tableau de complément de charge en grammes (R410A)
Ouvrir le cylindre de gaz et la valve de chargement de
basse pression.
Lorsqu’une quantité suffisante de réfrigérant est injectée
dans l’unité, fermer le côté basse pression et la valve du
cylindre de gaz.
Débrancher le tuyau de service de l’orifice de service.
Remettre le bouchon de l’orifice de service.
Tableau de complément de charge en grammes (R22)
Unité Intérieure
Unité Extérieure
Côté liquide
Côté
gaz
Fermé
Hi
Lo
Valve De
Deversement
Valve De
Succion
Fermé
Fermé
Ouvert
Valve De
Contröle
LED Allumée ou ÉteinteLED Allumée LED Clignotante
Opération / Indication de panne Action
Minuterie en marche.
Mode de sommeil.
Mode déshumidification.
Risque de prise en glace.
Nettoyer le filtre puis passer en grande vitesse.
Défaut de la sonde de reprise
Contacter votre revendeur.
d’air lâchement/court.
Défaut sonde de l’unité intérieure
Contacter votre revendeur.
lâchement / court.
Détecteur de problèmes de contact, protection
Contacter votre revendeur.
de surcharge du compresseur ou fuite de gaz.
Interrupteur Déshumidi Minuterie Mode de
-fication Sommeil
Continuellement
uni fois toutes les 2
secondes
deux fois toutes les 2
secondes
trois fois toutes
les 2 secondes
2-12
Mode
de sommeil
L’indicateur LED s’allume: Conditions de fonctionnement normales et par
défaut pour l’unité de pompe à chaleur
Mode refroidissement.
Mode déshumidification.
Mode ventilation.
Mode chauffage.
Mode chauffage automatique.
Mode refroidissement automatique.
Dégivrage.
Défaut de protection thermique compresseur. Contacter votre revendeur.
Défaut sonde de l’unité intérieure
Contacter votre revendeur.
lâchement / court.
Défaut sonde de l’unité extérieure. Contacter votre revendeur.
Défaut de la sonde de reprise
Contacter votre revendeur.
d’air lâchement/court.
Si le climatiseur est en mode “froid” ou “chaud” (avec fonction “réduit de nuit” à
l’arrêt) la sonde peut avoir un problème de contact, la protection interne compresseur
HS ou une fuite de réfrigérant.
Fonctionnement normales/défaut Action
Froid shumi- Ventilation Chaleur Mode de
dification Sommeil
Module pompe à chaleur
Le tableau ci-dessous reprend en détail la visualisation par
led, des conditions normales de fonctionnement, et
conditions de défaut du climatiseur.
Les led de visualisation apparaissent lorsque le climatseur
est sous tension, dans la fenêtre de couleur bleu foncé située
dans la partie inférieure droite du climatiseur.
L’unité de pompe de chaleur est équipée d’un mode “auto”;
l’unité fournira une température ambiante raisonnable en
faisant passer l’unité automatiquement au mode
“refroidissement” ou au mode “chaleur”, selon la
température réglée par l’utilisateur.
L’indicateur LED s’allume pour l’unité de pompe
à chaleur
Mode chaleur/
ventilateur
(rouge/vert)
Mode de
déshumidification
Mode
refroidissement
LED ClignotanteLED Allumée ou Éteinte
LED Allumée
2-13
Français
Refroidissement
Déshumidification
Horizontale
25°C/77°F
OPÉRATION DU CLIMATISEUR
Déshumidification
Lorsque le taux d’humidité de l’air est élevé, le climatiseur
peut fonctionner en mode de déshumidification. Appuyer
sur la touche <MODE> et sélectionner <DRY>.
Au cas où la température de la pièce est de 2°C/35,6°F
supérieure à la température affichée, le climatiseur - avant
de passer en mode de déshumidification - fonctionnera en
mode de refroidissement jusqu’à ce que la température soit
retombée dans la limite des 2°C/35,6°F de différence par
rapport à la température affichée.
Si la température de la pièce se trouve dans la limite des
2°C/35,6°F de différence par rapport à la température
affichée, l’appareil fonctionnera directement en mode de
déshumidification.
En mode de déshumidification, l’appareil fonctionne à
faible vitesse de ventilation.
Chauffage (concerne seulement la pompe à chaleur)
Lorsque l’appareil est mis en marche à froid ou après un
cycle de dégivrage, le ventilateur intérieur se mettra à
tourner seulement une fois que le serpentin aura atteint la
température souhaitée.
Lorsque la température souhaitée est atteinte, le ventilateur
intérieur tournera jusqu’à ce que le serpentin ne puisse
plus fournir de chaleur supplémentaire.
Contrôle du débit d’air horizontal
Pour obtenir une meilleure circulation d’air, vous pouvez
ajuster la grille de refoulement d’air froid vers la gauche
ou vers la droite à la main.
Pendant le fonctionnement en mode froid ou
déshumidification, il n’y a pas un refoulement d’air froid
pendant un long moment vers le bas. Car il pourrait se
produire de la condensation sur les volets d’air suivi d'un
écoulement d’eau.
Subsitance Chaude (seulement pour la
thermopompe)
Durant la coupure du compresseur, le moteur du
ventilateur intérieur peut être mis en marche sur la
position:
(i) ON (Allume) (par défaut) ou
(ii) OFF (Eteint) ou
(iii) ON et OFF (Intervalle en Allume et Eteint)
par intermittence en réglant l’interrupteur à coulisse
comme indiqué sur le diagramme.
L'interrupteur est situé sur le cadre frontal (près de
l'interrupteur ON/OFF).
REMARQUE: Quand l’option est choisie, l’alimentation
d’énergieen nécessité d’unité d’être remis
à zéro afin d’activer la fonction.
Protection contre la surchauffe (concerne
seulement la pompe à chaleur)
Au cas où la température intérieure et/ou extérieure est
trop élevée, ou que le filtre est encrassé et bouché, le
réfrigérant risque de surchauffer. C’est pourquoi le
compresseur se coupe lorsque la température de
condensation atteint 62°C/143,6°F.
Prévention de givrage
• Quand le filtre à air est encrassé, le température
d’évaporation diminue et finit par causer la formation de
givre.
Le voyant lumineux correspondant va alors clignoter pour
signaler que le filtre est encrassé. Si la température
d’évaporation descend à -2°C/28,4°F, l’appareil se coupe
et se met en mode de dégivrage.
Vitesse de ventilation et capacité nominale de
refroidissement
La capacité nominale de refroidissement peut être atteinte
en vitesse de ventilation maximum.
La capacité de refroidissement est plus faible lorsque
l’appareil fonctionne en vitesse de ventilation moyenne
ou faible.
l'interrupteur ON/OFF
HOT KEEP
OFF
INTERVAL
ON
2-14
! Attention
Couper l’alimentation du secteur avant d’effectuer l’entretien du climatiseur.
NE PAS DÉBRANCHER le cordon électrique lorsqu’il y a du courant. Ceci pourrait provoquer des décharges
électriques avec pour résultat des risques d’incendie.
INSTALLATION
CADRE A FILTRE ET MATÉRIEL DE FILTRE ÉLECTROSTATIQUE DOUBLE ACTION
PURIFICATEUR D’AIR ET DÉSODORISANT
ACTION 1-
FILTRE PURIFICATEUR D’AIR
ELECTROSTATIQUE
Otez la poussière microscopique, la fumée et les petites
particules invisibles à l’aide d’un filtre polypropylène
électrostatique pour garder l’air de la pièce proper.
FILTRE ÉLECTROSTATIQUE
ACTION 2-
FILTRE DESODORISANT
Débarrassez l’air des odeurs gênantes et conservez l’air de
la pièce frais à l’aide du filtre de carbone activé.
CONDITIONS STANDARD DE FONCTIONNEMENT
Module pompe à chaleur
Module refroidisseur
Température Ts °C/°F Th °C/°F
Température
intérieure minimum
Température
intérieure maximum
Température
-9 / 15,8
extérieure minimum
Température
18 / 64,4
extérieure maximum
Température Ts °C/°F Th °C/°F
Température
19,4 / 66,9 13,9 / 57,0
intérieure minimum
Température
26,7 / 80,1 19,4 / 66,9
intérieure maximum
Température
19,4 / 66,9 13,9 / 57,0
extérieure minimum
Température
46 / 114,8 24 / 75,2
extérieure maximum
Ts: Température au thermomètre sec.
Th: Température au thermomètre mouillé.
10 / 50
26,7 / 80,1
-8 / 17,6
24 / 75,2
Ouverzle le
grillage du
cadre avant.
Sortez les filtres
d'origine en les
faisant glisser.
Inserez dans la fente
les filtres a double
action electrostatique
et desodorisant.
Replacez le filtre d'origine.
2-15
Français
ENTRETIEN ET MAINTENANCE
Procédure D’Entretien
1. Enlever la poussière du filtre à l’aide d’un aspirateur ou en lavant
le filtre à l’eau tiède (moins de 40°C/104°F) avec un détergent
neutre.
2. Bien rincer et sécher le filtre avant de le remettre en place.
3. Ne pas utiliser de gasoil, de substances volatiles ou autres produits
chimiques pour nettoyer le filtre.
1. Nettoyer la grille et le panneau en les essuyant avec un chiffon
doux mouillé à l’eau tiède (moins de 40°C/104°F) et un détergent
neutre.
2. Ne pas utiliser de gasoil, de substances volatiles ou autres produits
chimiques pour nettoyer l’unité intérieure.
Périodicité
Au moins une fois
toutes les 2
semaines.
Plus souvent si
nécessaire.
Au moins une fois
toutes les 2
semaines.
Plus souvent si
nécessaire.
Pieces A Entretenir
Filtre à air intérieur
Unité intérieure
! Avertissement
Ne pas utiliser d’appareil de chauffage à proximité du climatiseur. La chaleur excessive pourrait faire fondre
ou déformer le panneau en plastique.
MISE A L’ARRÊT PROLONGUE DU CLIMATISEUR
Faites fonctionner l’unité
pendant 2 heures sur les
réglages suivants:
Mode de fonctionnement :
froid
Température : 30˚C/86˚F
Retirer la prise du secteur.
Si vous utilisez un circuit
électrique unique pour le
climatiseur, coupez le circuit.
Enlever les piles de la
télécommande.
! Attention
Couper l’alimentation du secteur avant d’effectuer l’entretien du climatiseur.
NE PAS DÉBRANCHER le cordon électrique lorsqu’il y a du courant. Ceci pourrait provoquer des décharges
électriques avec pour résultat des risques d’incendie.
! Avertissement
1. Le filtre désodorisant et purificateur d’air électrostatique
doit être remplacé tous les 6 mois ou quand la couleur
du filtre devient marron, suivant ce qui se produit en
premier.
2. Les filtres usagés poussiéreux doivent être jetés et ne
peuvent être réutilisés, même si le filtre a été nettoyé et
lavé.
3. Le filtre est une pièce de rechange que vous trouverez
chez votre détaillant d’unités d’air climatisé.
4. Utilisez le nouveau filtre immédiatement une fois qu’il a
été sorti de son emballage hermétique. Ne sortez pas le
nouveau filtre trop tôt avant de l’utiliser, ceci peut
diminuer son effet désodorisant.
2-16
ANALYSE DES CAUSES DE DYSFONCTIONNEMENT DU CLIMATISEUR
En cas de dysfonctionnement du climatiseur, couper aussitôt l’alimentation électrique. Vérifier ensuite les
points suivants pour détecter la nature et les causes de la panne.
Causes / Action
- Protection contre les démarrages fréquents. Laisser 3 à 4
minutes au compresseur pour démarrer.
- Le circuit est peut être coupé ou un fusible est à changer.
- La prise de courant est peut être débranchée.
- La programmation de mise en marche/arrêt est peut-être mal
réglée.
- Si la panne persiste après ces vérifications, contacter
l’installateur.
- Le filtre à air est sale.
- Les portes ou les fenêtres sont ouvertes.
- Les entrées et sorties d’air sont bouchées.
- La température réglée n’est pas assez élevée.
- Les odeurs peuvent provenir de fumées de cigarettes, parfums ou
autres particules adhérants au refroidisseur.
- La condensation est due à l’humidité de l’air après une période
de fonctionnement prolongée.
- La température affichée est trop basse; augmenter la température
et faire tourner l’appareil à vitesse de ventilation élevée.
- Éteindre le climatisateur et appeler le concessionnaire.
- Le fluide réfrigérant coule dans le serpentin de l’évaporateur.
Defauts
1. Le compresseur ne démarre pas 3 minutes après la mise en
marche du climatiseur.
2. Le climatiseur ne fonctionne pas.
3. Le flux d’air est trop faible.
4. L’air dégagé a une mauvaise odeur.
5. Condensation sur la grille frontale de l’unité intérieure.
6. Ecoulement d’eau du climatiseur.
7. Bruit de chuintement venant du climatiseur.
Si les pannes persistent, appeler votre revendeur ou le service après-vente.
3-1
Deutsch
Das vorliegende Handbuch enthält die Installationsanweisungen für einen sicheren und ordnungsgemäßen Betrieb
dieser Anlage.
Je nach den örtlichen Gegebenheiten können spezielle Anpassungen notwendig sein.
Vor der Inbetriebnahme des Klimagerätes dieses Handbuch bitte aufmerksam zur Kenntnis nehmen und für
künftigen Bedarf aufbewahren.
MONTAGEANLEITUNG
DOPPELFUNKTIONS-KLIMAGERÄT, ANDMONTIERT
MODELL
IM-WM1-0302(2)-Acson
KÜHLFUNKTION (R22)
Bezugsmodell Modell
WM301 AWM301
SL30C ALC30C
SL30B ALC30B
KÜHLFUNKTION (R410A)
Bezugsmodell Modell
5WM311 A5WM311
5SL28C A5LC28C
WÄRMEPUMPE (R22)
Bezugsmodell Modell
WM301R AWM301R
SL30CR ALC30CR
SL30BR ALC30BR
WÄRMEPUMPE (R410A)
Bezugsmodell Modell
5WM301R A5WM301R
5SL28CR A5LC28CR
Part No.: A08019025521
3-2
! Vorsicht
Vor der Installation sind folgende wichtige Punkte zu prüfen.
Gerät nicht installieren, falls ein Leck entzündbaren Gases festgestellt wird.
Es besteht Feuergefahr, wenn Gas aus der Anlage entweicht und sich in der Umgebung ansammelt.
Die Kondensat-Abflußleitung muß sachgemäß angeschlossen sein.
Ist die Abflußleitung nicht richtig angeschlossen, besteht Gefahr, daß durch auslaufendes Wasser
das Mobiliar feucht wird.
Gerät nicht überlasten.
Das Gerät ist werkseitig vorgefüllt. Im Falle einer Überfüllung besteht die Gefahr einer Überbelastung
oder sonstigen Beschädigung des Kompressors.
Nach Installation oder Wartung ist sicherzustellen, daß die Geräteabdeckung wieder montiert ist.
Eine mangelhafte Befestigung der Abdeckung führt zu Geräuschentwicklung während des Betriebs.
INHALT
Vor der Installation sind nachfolgende Sicherheitsmaßnahmen aufmerksam zur Kenntnis zu nehmen.
VORSICHTMASSNAHMEN
! Achtung
Die Installation und Wartung muß durch qualifizietes Personal erfolgen, Welches mit den örtlichen Bestimmungen
und diesem Ausrüstungstyp vertraut ist.
Die gesamte E-Verkabelung hat in Übereinstimmung mit den landesspezifischen Anschlußvorschriften zu erfolgen.
Vor dem Kabelanschluß gemäß Schaltbild ist sicherzustellen, daß die Betriebsspannung mit der auf dem Datenschild
des Gerätes angegebenen Spannung übereinstimmt.
Das Gerät ist zum Schutz gegen fehlerhafte Isolierungen und entsprechende Risiken zu ERDEN.
Die Kabel dürfen weder mit der Kühlmittelleitung, noch mit dem Kompressor oder den beweglichen Teilen der
Gebläsemotoren in Berührung kommen.
Vor der Installation oder Wartung der Anlage ist sicherzustellen, daß das Gerät ausgeschaltet ist (OFF).
WICHTIG
DAS KLIMAGERÄT SOLLTE NICHT IN EINEM WÄSCHERAUM
INSTALLIERT ODER BENUTZT WERDEN.
- Auslegung und Admessung seite i-ii
- Vorsichtmassnahmen seite 2
- Installationsdiagramm seite 3
- Installation des Außengerätes seite 3
- Installation der Öffnungsrohrleitung seite 4
- Installation des Innengerätes seite 6
- Kühlmittelleitung seite 7
- Kabelanschluß seite 8
-
Besondere Vorsichtsmassnahmen, Beim R410A Einheit
seite 10
- Vakuum und Aufladen seite 10
- Betriebsleuchtanzeige seite 11
- Bedienung des Klimagerätes seite 13
- Standard-Betriebsbedingung seite 14
- Elektrostatikfilter seite 14
- Instandhaltung und Wartung seite 15
- Störungs-Behebung seite 16
3-3
Deutsch
INSTALLATIONSDIAGRAMM
LUFTEINLASSGITTER
ABLUFTGITTER
LUFTEINLASS
KÄLTEMITTELLEITUNG
ABLAUFSCHLAUCH
VORDERER RAHMEN
RÜCKWÄRTIGES
GEHÄUSE
EIN-/AUS- SCHALTER
LUFTFILTER
LEUCHTANZEIGE
IR-EMPFÄNGER
ABLUFTAUFSATZ
AUßEN-GERÄT
INNEN-GERÄT
INSTALLATION DES AUßENGERÄTES
LUFTAUSLASSDÜSE
LUFTEINLASS
Die Außenmontage-Einheit ist so zu installieren, daß die
Luftzirkulation an keiner Stelle beeinträchtigt oder durch ein
Hindernis am Abströmen gehindert wird. Auf Einhaltung der
nachstehend gezeigten Mindestabstände achten.
Auszuwählen ist die jeweils kühlste Stelle, an der die
Einlaßlufttemperatur nicht die Außentemperatur überschreitet
(maximal 45°C/113°F).
Montageabstand
Anmerkung: Bei einem Hindernis von über 2m oder soweit
sich irgendein Hindernis im oberen Bereich der Einheit
befindet, muß der in obenstehender Tabelle aufgeführte
Abstand entsprechend vergrößert werden.
A
B
C
D
Wandelement
Wandelement
Luftzufuhr
Auslassluft
Luftzufuhr
Wartungs-Offnung
Wandelement
Abmessung A B C D
Mindest
Entfernung, mm 300 1000 300 500
(11,8) (39,4) (11,8) 19,7
Wandelement
3-4
INSTALLATION DER ÖFFNUNGSROHRLEITUNG
Ablassrohr
1
2
34
1
2
3
4
Außengerät
Innenräume
Ablassstück
Verbindungsrohr
3/8" - Schraubenmutter
3/8" - Sechskanthohlschraube
! Vorsicht
Das Ablassrohr muss, wie oben erläutert, in die richtige Richtung eingebaut werden. Ein falscher
Einbau kann Schäden im Betriebssystem verursachen.
Anmerkung: Dieses Einbauverfahren bezieht sich nur auf die Modelle WM301 / SL30B & WM301 / SL30C
A. Öffnungsrohrleitung des Außengerätes (wo der Installationsraum weit genug ist)
Ablassrohr
Schritte:
1. Verbinden Sie die Schraubenmutter des Ablassrohres
direkt mit dem Flüssigkeitsventil.
2. Bringen Sie das Flüssigkeitsrohr an und verbinden Sie
es mit der Hohlschraube des Auslassrohres.
Ablassrohr
Flüssigkeitsrohr
Schritt 2
Schritt 1
3-5
Deutsch
Flüssigkeitsrohr
Schweißgerät
C. Installation der Öffnungsrohrleitung
Innen-Gerät
Ablassrohr
B. Öffnungsrohrleitung des Außengerätes (wo der installationsraum beschränkt ist)
Schritt 4
Schritt 3
Schritt 2
Schritt 1
Ablassrohr
Wenn das Ablassrohr aufgrund von Platzmangel nicht direkt mit dem Flüssigkeitsventil verbunden werden kann, kann es
entlang des Flüssigkeitsrohres eingebaut werden.
Schritte:
1. Bringen Sie das Flüssigkeitsrohr an und verbinden Sie
es mit dem Flüssigkeitsventil.
2. Schweißen Sie eine zusätzliche
Hohlschraubenverbindung an das Flüssigkeitsrohr.
3. Verbinden Sie die Schraubenmutter des Ablassrohres
mit der Hohlschraube.
4. Bringen Sie ein weiteres Flüssigkeitsrohr an und
verbinden Sie es mit dem Gewinde des Auslassrohres.
Schritte:
1. Schweißen Sie eine zusätzliche
Hohlschraubenverbindung an
das Flüssigkeitsrohr.
3. Bringen Sie ein weiteres
Flüssigkeitsrohr an und
verbinden Sie es mit dem
Gewinde des Auslassrohres.
2. Verbinden Sie die
Schraubenmutter des
Ablassrohres mit der
Hohlschraube.
Flüssigkeitsrohr
Schweißgerät
Flüssigkeitsrohr
Ablassrohr
Flüssigkeitsrohr
Ablassrohr
Flüssigkeitsrohr
Ablassrohr
Flüssigkeitsrohr
Ablassrohr
3-6
Zwischenraum Für
Wartung Und Pflege
Richtung Des
Luftstroms
Oberhalb der
Augenhöhe
Innengeräte sind so zu installieren, daß keine Interferenz
zwischen dem Kühlluftaustritt und der zurückgeführten Luft
besteht. Bei der Installation bitte die in der Zeichnung
angegebenen Abstände beachten. Ein Innenmontage-Gerät
darf nicht unter direkter Sonneneinstrahlung montiert
werden. Die Montageposition ist anhand der Rohrleitung und
der Drainage im gegebenen Abstand zu Türen oder Fenstern
zu gewährleisten.
Montage der installations-halterungsplatte
Sicherstellen, daß die Trägerwand ausreichend fest ist, um
das Gewicht aufnehmen zu können. Falls nicht, müssen
geeignete Vertärkungsplatten, Träger oder Stützen verwendet
werden.
Beim Anbringen des Geräts eine Wasserwaage benutzen,
sodann das Gerät mit 4 geeigneten Schrauben befestigen.
Bei Rohrleitungs-herausführung auf der Rückseite: Eine
Bohrung 65 mm mit einem Konusbohrer setzen. Hierbei die
Bohrung auf der wandungsaußenseite etwas tiefer
positionieren (seihe Abb.).
Verlegungsrichtung Der Rohrleitungen
Die Schraube entfernen, die die Vorderabdeckung hält.
Verlegungsrichtung Der Rohrleitungen
1
2
3
4
5
Montageplatte
Markierung-offline
Gewinde
Innen
Außen
1/50 Neigung
Verlegungsrichtung Rechts Und Hinten
Die Kühlmittel-Rohrleitung kann an die Einheit auf
verschiedene Weise angeschlossen werden (auf der Rückseite
links oder rechts der Einheit). Hierzu sind die Aussparungen
der Gërateverkleidung zu verwenden (siehe Abb.). Die Rohre
vorsichtig auf die entsprechenden Lochpositionen biegen.
Bei einem rechtseitigen bzw. bei einem Anschluß auf der
Rückseite das Rohrleitungsende festhalten und in die
entsprechende Richtung positionsgerecht biegen (siehe
Abb.). Der Kondensat-Drainageschlauch ist an die
Rohrleitungen anzupassen.
Gerätemontage auf der installationsplatte
Innenmontage-Gerät in den oberen Bereich der
Installationsplatte einhängen. (Die beiden hinteren oberen
Laschen der Innenmontage-Einheit in die obere Kante der
Installationsplatte einhängen). Bewegen Sie die
Montageplatte leicht nach links und rechts, um zu prüfen,
ob die Haken ordnungsgemäß eingegriffen haben.
Wasser-entleerungsleitung
Zur problemlosen Kondensatabführung muß die
innenliegende Wasserentleerungsleitung Gefälle aufweisen.
Vermeiden Sie Umstände, die zum Austreten von Wasser
führen können.
Verbindungs-kabel
J
Falsch
J
Falsch
j
Korrekt
50mm
50mm
50mm
INSTALLATION DES INNENGERÄTES
Wasser-
Leck
In Wasser
Eintau-
Chendes
Rohrende
Wasser-
Leck
Wasser-
Leck
Ablaufschlauch
J
Falsch
Wasserablauf
3-7
Deutsch
Leitungslänge und Höhenmaß
Bei zu langer Rohrleitung führt dies zu mangelnder
Kapazität und Zuverlässigkeit des Gerätes. Mit zunehmender
Bögenanzahl steigt der Kältemittelstrom im System an, führt
dadurch zu einer verminderten Kühlkapazität und verursacht
u.U. eine Störung des Kompressors. Immer den kürzesten
Leitungsweg unter Beachtung nachstehender Empfehlungen
wählen:
Anmerkung: Für Außenmontage-Geräte wird werkseitig eine
Kältemittelcharge hinsichtlich einer Rohrleitungslänge
von 7,62 m/25ft vorgenommen.
KÜHLMITTELLEITUNG
Außen-Gerät
Innen-Gerät
Zuschneiden Des
Kupferrohres
Verlegen Und Anschliessen Der Leitungsrohre
Keine verschmutzten oder beschädigten Kupferrohre
verwenden. Plastikabdeckungen, Gummistopfen oder
Messinggewinde sollen nicht von den Ventilen, Armaturen,
Rohrleitungen oder den Heiz- und Kälteschlangen entfernt
werden, bis die Ansaug- bzw. Flüssigkeitsleitung
anschlussbereit ist.
Falls Lötarbeiten vorzunehmen sind, sicherstellen, daß
Während des Lötens Stickstoff durch die Wärmetauscher und
Kupplungen gerührt wird. Dadurch werden Rußablagerungen
auf den Kupferrohr-Innenwandungen vermieden.
Das Verbingungsrohr mit einem Rohrschneider abschneiden.
Die Rohrkanten mit einer Reibahle entgraten. Das Rohrende
dabei nach unten halten, damit keine Metallpartikel in das
Rohr gelangen.
Die Gewindeüberwurfteile an den Armaturen des Innen- und
Außengerätes auf die Kupferrohre ziehen.
Das hinter dem Aufweitungswekzeug überstehende Rohrende
soweit aufweiten, wie in der Tabelle gezeigt.
Die aufgeweitete Kante soll glatt sein und weder Kratzer noch
Sprünge aufweisen.
! Vorsicht
Nur im Kühlgerät WM 301 wird eine Öffnung als Ausdehnungsvorrichtung verwendet. Beim Innengerät ist diese im
Flüssigkeitsrohr festgemacht.
Geräte-rohranschluss
Rohrleitung zentrieren und Gegenmutter des
aufgeweiteten Rohrstückes mit der Hand anziehen.
Abschließend Gewindemutter und Moment-schlüssel bis
an die gewünschte Moment-Einraststelle anziehen.
L
H
Gasleitungs-Durchm 3/8" 1/2" 5/8" 5/8" 5/8"
Modell 07/10 15 20 25 30
Maximale Länge, m (ft), L
12
(39,4)
12
(39,4)
15
(49,2)
15
(49,2)
35
(114,8)
Maximale Höhe, m (ft), H 5 (16,4) 5 (16,4) 8 (26,2) 8 (26,2) 15 (49,2)
Maximale Bogenanzahl 10 10 10 10 10
Flüssigkeitsleitungs-Durchm 1/4" 1/4" 1/4" 3/8" 3/8"
Rohrgröße mm / (zoll) Anzugsmoment Nm / (Ft-lb)
12,7 (1/2) 55 (40,6)
15,88 (5/8) 65 (48,0)
6,35 (1/4) 18 (13,3)
9,53 (3/8) 42 (31,0)
Ø Rohr, D A (mm)
Zoll mm Aufgeweite Starr
1/4" 6,35 1,3 0,7
3/8" 9,52 1,6 1,0
1/2" 12,70 1,9 1,3
5/8" 15,88 2,2 1,7
Innenmontagerohr
Gewindeüberwurf
Aufgeweitetes Rohr
Anzugsring
Anzugsschlüssel
Drehmomentschlüssel
Rohrentgratung
Kupferrohr
Stauchblock
3-8
L
COMP
N2
N1
N
T
COMP
L
N
S
R
COMP
N2
N1
L
COMP
N
KABELANSCHLUß
Kühleinheit
WICHTIG : * Die angegeben Werte sind lediglich Richtwerte. Sie sind zu überprüfen und ggf. den örtlichen und/
oderlandesspezifischen Vorschriften und Bestimmungen anzugleichen. Des weiteren sind sie abhängig von der
Installationsart und dem Adernquerschnitt.
** Der geeignete Spannungsbereich sollte den Etikettdaten auf der Einheit entnommen werden. ETL verzeichnete
Daten gelten nur für einen 60Hz Netzanschluss.
COMP
N2
N1
L
COMP
R
S
N
L
N
L
WM301 VS SL30C
WM07 / 10 / 15 / 20 / 25 / 301 VS SL07 / 10 / 15 / 20 / 25 / 30B
5WM311 VS 5SL28C
Die Stromversorgung muß mit
Schutzeinrichtungen ausgestattet sein (Lei-
tungsunterbrecher oder Sicherung).
Vorzusehen ist ein 2-Pol-Schutzschalter mit
einem Mindestkontak-tabstand von 3mm.
!
Außen-Gerät-
Klemmenblock
Anschluss-Kabel
Anschluss-Kabel
Die Stromversorgung muß mit
Schutzeinrichtungen ausgestattet sein (Lei-
tungsunterbrecher oder Sicherung).
Vorzusehen ist ein 2-Pol-Schutzschalter
mit einem Mindestkontak-tabstand von
3mm.
!
Innen-Gerät-
Klemmenblock
Außen-Gerät-
Klemmenblock
Anschluss-Kabel
Die Stromversorgung muß mit
Schutzeinrichtungen ausgestattet sein (Lei-
tungsunterbrecher oder Sicherung).
Vorzusehen ist ein 2-Pol-Schutzschalter mit
einem Mindestkontak-tabstand von 3mm.
!
WM201 / 251 VS SL20 / 25B (3 Phase)
Innen-Gerät-
Klemmenblock
Außen-Gerät-
Klemmenblock
L
COMP
N2
N1
N
T
COMP
L
N
S
R
Die Stromversorgung muß mit
Schutzeinrichtungen ausgestattet sein (Lei-
tungsunterbrecher oder Sicherung).
Vorzusehen ist ein 2-Pol-Schutzschalter mit
einem Mindestkontak-tabstand von 3mm.
!
Anschluss-Kabel
Innen-Gerät-
Klemmenblock
Außen-Gerät-
Klemmenblock
WM301 VS SL30C (3 Phase)
Drahtklemme
Verbin-
dungskabel
Alle Adern sind fest zu verdrahten.
Jeglicher Kontakt einer Elektrokabelader mit der
Kältemittelleitung, dem Kompressor oder anderen beweglichen
Teilen des Gebläsemotors ist zu vermeiden.
Die Anschlußadern zwischen Außen- und Innenmontage-Gerät
sind gem. Klemmbrücke gegen Abziehen zu sichern.
Das Anschlusskabel muss zumindest dem H05RN-F (245 IEC57)
entsprechen.
Modell Innen-Gerät WM 071/ 101/ 151 WM201/ 251/ 301 5WM311 WM301 WM201/ 251/ 301 WM301
Außen-Gerät SL07/ 10/ 15B SL20/ 25/ 30B 5SL28C SL30C SL20/ 25/ 30B SL30C
Spannungsbereich**
220V-240V/ 1Ph/ 50Hz + oder 208V-230V/ 1Ph/ 60Hz + 380V-415V/ 3Ph/ 50Hz +N+
Zuleitungskabelquerschnitt* mm
2
1,5 2,5 2,5 4 1,5 1,5
Adernanzahl 333355
Zwischenkabelquerschnitt* mm
2
1,5 2,5 2,5 2,5 1,5 1,5
Adernanzahl 333444
Empfohlene Sicherung A 15 20 20 25 15 15
Innen-Gerät-
Klemmenblock
3-9
Deutsch
Wärmepumpe
4WV
OF
COMP
N2
N1
L
4WV
OF
COMP
N
4WV
OF
COMP
N2
N1
L
4WV
A
OF
COMP
L
N
L
N
WM301R VS SL30CR
WM07 / 10 / 15 / 20 / 25 / 301R VS SL07 / 10 / 15 / 20 / 25 / 30BR
5WM301R VS 5SL28CR
Die Stromversorgung muß mit
Schutzeinrichtungen ausgestattet sein (Lei-
tungsunterbrecher oder Sicherung).
Vorzusehen ist ein 2-Pol-Schutzschalter mit
einem Mindestkontak-tabstand von 3mm.
!
Innen-Gerät-
Klemmenblock
Außen-Gerät-
Klemmenblock
Anschluss-Kabel
Aussen-Sensor Spulenanschlussader
(Länge 8m), Verbunden Mit Dem
Innenmontagegerät.
Die Stromversorgung muß mit
Schutzeinrichtungen ausgestattet sein (Lei-
tungsunterbrecher oder Sicherung).
Vorzusehen ist ein 2-Pol-Schutzschalter mit
einem Mindestkontak-tabstand von 3mm.
!
Innen-Gerät-
Klemmenblock
Außen-Gerät-
Klemmenblock
Anschluss-Kabel
Aussen-Sensor Spulenanschlussader
(Länge 8m), Verbunden Mit Dem
Innenmontagegerät.
4WV
OF
COMP
N2
N1
L
4WV
OF
COMP
L
N
S
R
N
T
4WV
OF
COMP
N2
N1
L
4WV
OF
COMP
L
N
A
S
R
N
T
WM301R VS SL30CR (3 Phase)WM201 / 251R VS SL20 / 25BR (3 Phase)
Aussen-Sensor Spulenanschlussader
(Länge 8m), Verbunden Mit Dem Innenmontagegerät.
Aussen-Sensor Spulenanschlussader
(Länge 8m), Verbunden Mit Dem
Innenmontagegerät.
Die Stromversorgung muß mit
Schutzeinrichtungen ausgestattet sein
(Lei-tungsunterbrecher oder Sicherung).
Vorzusehen ist ein 2-Pol-Schutzschalter
mit einem Mindestkontak-tabstand von
3mm.
!
Innen-Gerät-
Klemmenblock
Außen-Gerät-
Klemmenblock
Anschluss-Kabel
Innen-Gerät-
Klemmenblock
Außen-Gerät-
Klemmenblock
Die Stromversorgung muß mit
Schutzeinrichtungen ausgestattet sein (Lei-
tungsunterbrecher oder Sicherung).
Vorzusehen ist ein 2-Pol-Schutzschalter mit
einem Mindestkontak-tabstand von 3mm.
!
Anschluss-Kabel
WICHTIG : * Die angegeben Werte sind lediglich Richtwerte. Sie sind zu überprüfen und ggf. den örtlichen und/
oderlandesspezifischen Vorschriften und Bestimmungen anzugleichen. Des weiteren sind sie abhängig von der
Installationsart und dem Adernquerschnitt.
** Der geeignete Spannungsbereich sollte den Etikettdaten auf der Einheit entnommen werden. ETL verzeichnete
Daten gelten nur für einen 60Hz Netzanschluss.
Modell Innen-Gerät WM 071/ 101/ 151 R WM201/ 251/ 301 R 5WM301R WM301 R WM201/ 251/ 301 R WM301 R
Außen-Gerät SL07/ 10/ 15BR SL20/ 25/ 30BR 5SL28CR SL30CR SL20/ 25/ 30BR SL30CR
Spannungsbereich**
220V-240V/ 1Ph/ 50Hz + oder 208V-230V/ 1Ph/ 60Hz + 380V-415V/ 3Ph/ 50Hz +N+
Zuleitungskabelquerschnitt* mm
2
1,5 2,5 2,5 4 1,5 1,5
Adernanzahl 3 3 3355
Zwischenkabelquerschnitt* mm
2
1,5 2,5 2,5 2,5 1,5 1,5
Adernanzahl 5 5 5664
Empfohlene Sicherung A 15 20 20 25 15 15
3-10
VAKUUM UND AUFLADEN
Entlüftung der leitung und des innenmontage
Gerätes
Mit der Ausnahme des Außenmontage-Gerätes, welches mit
dem Kältemittel vorbefüllt ist, müssen das Innenmontage-
Gerät sowie die Kältemittel-Anschlußleitungen entlüftet
werden, da Feuchtigkeit im Kühlkreis zu einer
Funktionsstörung des Kompressors führen kann.
Die Abdeckungen vom Ventil und dem
Wartungsanschluß abnehmen.
Den Lademesser von der Mitte aus an die Vakuumpumpe
anschliessen.
Den Lademesser an die Wartungsöffnung des 3-Weg-
Ventils anschliessen.
Die Vakuumpumpe einschalten und etwa 30 Minuten
laufen lassen. Die Evakuierungszeiten sind je nach
Kapazität der Pumpe verschieden. Darauf achten, dass die
Nadel des Lademessers bei –76mmHg (0~76mmHg) steht.
Achtung
Falls die Nadel des Lademessers nicht bei 0 ~76mmHg steht,
ist nachzuprüfen (mit dem Kältemittel-Anzeigegerät), ob
an der aus dem aufgeweiteten Rohr bestehenden Verbindung
zwischen Innen- und Aussengerät ein Gasleck besteht. Vor
Ausführen des nächsten Schrittes muss das Leck behoben
werden.
Das Ventil des Lademessers schliessen und und die
Vakuumpumpe abschalten.
Am Aussengerät das Saugventil (3-Weg-Ventil) und das
Flüssigkeitsventil (2-Weg-Ventil) mit einem 4mm-
Schlüssel für 6-kantige Sackschrauben öffnen (gegen den
Uhrzeigersinn).
BESONDERE VORSICHTSMASSNAHMEN, BEIM R410A EINHEIT
R410A ist ein nahezu azeotropes Kühlmittelgemisch aus Hydrofluorkohlenwasserstoff (HFC), welches umweltfreundlich
ist. Es hat ein Ozonabbaupotential von 0 (ODP = 0) und entspricht dem Montreal-Protokoll. Es hat keine Flammenausbreitung
und ein schwach toxisches Kühlmittel (von ARI als A1 eingestuft). R410A ist eine Mischung aus R32 (50%) und R125
(50%).
POE Öl wird als Schmiermittel für R410A Kompressor benutzt, der verschieden vom Erdöl ist, das für R22 Kompressor
benutzt wird. Während Installation oder Wartung muß zusätzliche Vorsichtsmaßnahme nicht genommen werden, das R410A
System zu entblößen, das zu lang ist zu feuchter Luft. Restlich POE Öl in der Rohrleitung und die Bauteile können
Feuchtigkeit von der Luft absorbieren.
Refrigerant R410A wird leichter von Staub der Feuchtigkeit im Vergleich zu R22 beeinflußt, vergewissert sich vorübergehend,
die Enden priop des Schlauchs zu Installation zu bedecken.
Keine additonal Aufladung des Kompressoröls wird die Erlaubnis gehabt.
Kein ander refrigerant anders als R410A.
Werkzeuge ausdrücklich für R410A nur.
i) Mannigfaltiges Meßgerät und ladenden Schlauch
ii) Gas Leck Detektor
iii) Refrigerant Zylinder Laden Zylinder
iv) Vakuumpumpe C/W Adapter
v) Leuchtsignal Werkzeuge
vi) Refrigerant Rückgewinnung Maschine
!!
!!
! VORSICHT
R410A muß als flüssig geladen werden. Gewöhnlich wird R410A Zylinder mit einem Soße Rohr für flüssige Rückzüge
ausgerüstet. Wenn es kein Soße Rohr gibt, sollte der Zylinder um invertiert werden, flüssig R410A vom Ventil
zurückzuziehen.
Nicht Macht Auffüllung beim Warten Lecks, als dies die Einheit Leistung verringern wird. Saugen Sie die Einheit gründlich
ab und laden Sie dann die Einheit mit frischem R410A gemäß dem Betrag, der in der Spezifikation empfohlen wird.
Berühren Sie nicht den Verdichter oder das Kühlrohr, wenn das Kühlgerät in Betrieb ist. Bei Bedarf Schutzhandschuhe
tragen.
Gesamttest
Das Außenmontage-Gerät ist bereits werkseitig mit Kältemittel
befüllt. Falls die Rohrleitung unter 7,62m (25 ft) Länge
aufweist, ist eine zusätzliche Kältemittelbefüllung nach der
Herstellung desVakuums nicht erforderlich. Wenn die
Rohrleitung länger als 7,62m (25 ft) ist, sollte ein zusätzliches
Speiseventil gemäß den Angaben in der untenstehenden
Tabelle verwendet werden.
Wartungsanschluss
Aussengerät-3-
Wege-ventil
Gewinde-
Überwurf
Kältemittel-leitung
Sechskantsteckschlüssel
Außen-Gerät
Innen-Gerät
Vakuum-
Pumpe
Offen
Geschlossen
Hi
Lo
Flüssigkeitsleitung
Sauggasleitung
Gesch-
lossen
Gesch-
lossen
Ablaufventil
Saugventil
3-11
Deutsch
Infrarot-Signalempfänger
Wenn von der Infrarot-Fernbedienung ein Signal an das
Gerät gesendet wird, bestätigt das Innen-gerät den
Empfang mit einem Signalton.
BETRIEBSLEUCHTANZEIGE
Kühleinheit
Die Tabelle erläutert die Bedeutung der Leuchtdioden für
den normalen Betrieb und eventuelle Störungen des
Klimageräts.
Die LED-Anzeigeleuchten befinden sich auf der rechten
unteren Seite des Klimagerätes.
Leuchtdioden : Normalbetrieb und Störungssituationen des Kühlgeräts
Leuchtdiode für Kühlbetrieb
Strom AN
Zeitschalter
Schlafmodul
Entfeuchtungs-
Modus
LED -Funktionsanzeige
Infrarot-Empfanger
Kältemittel-Zusatzbefüllung
Dieser Arbeitsgang erfordert unbedingt den Einsatzeines
Gas-Füllzylinders sowie einer Präzisionswaage. Die
Zusatzbefüllung erfolgt am Außenmontage-Gerät mithilfe
des Ansaugventils und dem Wartungsanschluß.
Abdeckung der Wartungsöffnung entfernen.
Die Niederdrucköffnung des Lademessers an den
Ansauganschluss des Gaszylinders anschliessen und die
Hochdrucköffnung des Lademessers schliessen. Die
verbleibende Luft aus dem Zulieferschlauch entfernen.
Klimaanlage einschalten.
Modell 10 m/32,8 ft 12 m/39,4 ft 15 m/49,2 ft
071 / 101 / 151 35 65 -
201 35 65 110
251 / 301 90 165 280
071R / 101R /151R 50 90 -
201R 60 110 185
251R / 301R 120 220 370
Modell 10 m/32,8 ft 12 m/39,4 ft 15 m/49,2 ft
311 80 150 255
301R 110 200 335
Zusatzfüllung in Gramm (R410A)
Den Gaszylinder und das Niederdruck-Ladeventil öffnen.
Sobald die benötigte Kältemittelmenge in das Gerät
eingepumpt ist, werden die Niederdrucköffnung des
Lademessers und der Gaszylinder geschlossen.
Den Zulieferschlauch vom Gaszylinder entfernen und
dieZylinder-Abdeckung wieder anbringen.
Zusatzfüllung in Gramm (R22)
Außen-Gerät
Innen-Gerät
Flüssigkeitsleitung
Sauggasleitung
Gesch-
lossen
Ablaufventil
Offen
Geschlossen
Hi
Lo
Gesch-
lossen
Saugventil
Ventil
prüfen
EIN oder AUSEIN Blinkend
Betrieb/Falsche Anzeige Maßnahme
Zeitschalter AN.
Schlafmodul AN.
Entfeuchtungs-Modus.
Verhindern von Rauhreif. Filter reinigen und auf hohe
Ventilator-Drehzahl umschalten.
Raum-Luftsensorkontakt unterbrochen/
Händler benachrichtigen.
kurzgeschlossen.
Innenmontage-Sensorspule unterbrochen/
Händler benachrichtigen.
kurzgeschlossen.
Kontaktproblem der Sensoren Kompressoren-
Händler benachrichtigen.
Überlastschutz Schaltauslösung oder Gasleck
Strom Entfeuchtungs Zeitschalter Schlafmodul
Ununterbrochen
Zweimal alle
2 Sekunden.
Drei alle
2 Sekunden.
Mindestens alle
2 Sekunden.
3-12
Leuchtdioden: Normalbetrieb und Störungssituationen des Leuchtdiode für Wärmepumpe
Kühlmodus.
Entfeuchtungs-Modus.
Gebläsemodus.
Heiz-Modus.
Automatik-Modus in Heizfunktion.
Automatik-Modus in Kühlfunktion.
Enteisung.
Kompressor-Überlastungsschutz. Händler benachrichtigen.
Innenmontage-Sensorspule unterbrochen / kurzgeschlossen.
Händler benachrichtigen.
Aussenmontage-Sensorspule unterbrochen / kurzgeschlossen.
Händler benachrichtigen.
Raum-Luftsensorkontakt unterbrochen / kurzgeschlossen.
Händler benachrichtigen.
Befindet sich das System im Kühl- oder Heiz-Modus (mit abgeschalteter Sleep-
Funktion) kann ein Kontaktproblem beim Sensor, eine Auslösung des Kompressor-
Überlastungsschutzes oder ein Gas-Leck-Problem bestehen.
Normalbetrieb/Störungssituationen Maßnahme
Kühlen
Entfeuchtungs
Gebläse Heizen Schlafmodul
Wärmepumpe
Nachstehende Tabelle enhält die einzelnen LED-
Funktionsanzeigen für Normalbetrieb und die verschiedenen
Störungsmeldungen.
Die LED-Anzeigeleuchten befinden sich auf der rechten
unteren Seite des Klimagerätes.
Die Wärmepumpe kann auf automatischen Betrieb (“Auto”)
geschaltet werden, so daß sie zwecks Aufrechterhaltung der
vom Benutzer voreingestellten Raumtemperatur entweder
auf Kühl- oder Heizbetrieb schaltet.
Leuchtdiode für Wärmepumpe
EIN oder AUS
EIN
Blinkend
Entfeuchtungs-
Modus
Kühlmodus
Wärme/Gebläse
Modul (rot/grün)
Schlafmodul
3-13
Deutsch
Kühlen/
Entfeuchtle
Waagerecht
25°C/77°F
BEDIENUNG DES KLIMAGERÄTES
Entfeuchten
Bei hoher Luftfeuchtigkeit ist das Gerät zum Entfeuchten
einsetzbar. Dazu die <MODE>-Taste betätigen und
<DRY> anwählen.
Liegt die Raumtemperatur um 2°C/35,6˚F höher als die
eingestellte Temperatur, arbeitet das Gerät im
Kühlbetrieb, bis die Raumtemperatur sich innerhalt von
2°C/35,6˚F Unterschied gegenüber der eingestellten
Temperatur befindet, und schaltet anschließend auf
Entfeuchten um.
Liegt die Raumtemperatur innerhalb von 2°C/35,6˚F
Unterschied gegenüber der eingestellten Temperatur,
schaltet sich das Gerät direkt auf Entfeuchtung.
Bei Entfeuchtung arbeitet das Gerät mit langsamer
Gebläsedrehzahl.
Heizbetrieb (nur für Wärmepumpe)
Wird das Gerät kalt gestartet oder nach Entfrostung
eingeschaltet, setzt das Gebläse am Innengerät sich erst
in Gang, wenn der Wärmetauscher die gewünschte
Temperatur erreicht hat.
Ist die eingestellte Temperatur erreicht, arbeitet das
Innengebläse so lange, bis der Wärmetauscher seine
maximale Heizkapazität erreicht hat.
Horizontale Luftstromsteuerung
Zur verbesserten Luftzirkulation kann das Abluftgitter
nach links oder rechts mit der Hand verstellt werden.
Während der Kühl- oder Entfeuchtungs-funktion
(cooling/dry) solte das Strömungsrichtungsgitter nicht
über einen längeren Zeitraum hin direkt nach unten
gerichtet werden. Bei einer längeren Funktion in dieser
Einstellung kann sich Kondensat an den Lamellen bilden.
Bei einer Kondensatbildung kann es dadurch zu einer
Tropfenbildung kommen.
Heißer Unterhalt (nur in Bezug auf Wärmepumpe)
Bei Stillsetzung des Kompressors kann das Kühlgebläse
des Innengeräts auf:
(i) EIN (Standardeinstellung), oder
(ii) AUS, oder
(iii) Abstand ein oder aus
geschaltet werden durch Einstellen des Gleitschalters, wie
in der Zeichnung dargestellt.
Die Sprungschaltung ist an der vorderen
Rahmenabdeckung angebracht (zusammen mit dem AN/
AUS Schalter).
ANMERKUNG:Wenn die Wahl vorgewählt wird, das
Spg.Versorgungsteil der Maßeinheit
Notwendigkeit zurückgestellt zu werden,
um die Funktion zu aktivieren.
Überhitzungsschutz (nur für Wärmepumpe)
Wenn die Innen- und/oder Außentemperatur zu hoch liegt,
oder der Filter verschmutzt bzw. verstopft ist, besteht
Überhitzungsgefahr für das Kältemittel. Darum schaltet
sich der Kompressor aus, wenn die Kondenstemperatur
62°C/143,6°F erreicht.
Vorbeugen von Frostbildung
Wenn der Luftfilter verschmutzt ist, sinkt die
Verdunstungstemperatur und führt schließlich zu
Frostbildung.
Der Leuchtanzeiger blinkt, um zu melden, daß der
Filter verschmutzt ist. Wenn die Verdunstungstemperatur
bis auf -2°C/28,4°F fällt, schaltet sich das Gerät aus und
entfrostet.
Gebläsedrehzahl und vorgesehene Kühlleistung
Die vorgesehene Kühlleistung wird bei maximaler
Gebläsedrehzahl erreicht.
Bei mittlerer bzw. langsamer Gebläsedrehzahl liegt die
Kühlleistung niedriger.
ON/OFF schalter
HOT KEEP
OFF
INTERVAL
ON
3-14
DOPPELT WIRKENDES FILTERMATERIAL UND FILTERRAHMEN FÜR
ELEKTROSTATIKBEHANDLUNG UND LUFTREINIGUNG
WIRKUNG 1-
ELEKTROSTATIKFILTER
Entfernt mikroskopisch feinen Staub, Rauch und unsichtbar
kleine Partikel und reinigt die Raumluft fortlaufend mit
positiv vorgeladenem elektrostatischem Polypropylenfilter.
ELEKTROSTATIKFILTER
WIRKUNG 2-
LUFTREINIGUNGSFILTER
Entfernt unangenehme Gerüche aus der Umgebungsluft und
erfrischt den Raum fortlaufend mit Aktivkohlefilter.
STANDARD-BETRIEBSBEDINGUNG
Wärmepumpe
Kühleinheit
! Achtung
Vor Wartung des Klimagerätes das Stromkabel vom Netz trennen.
Das Stromkabel nicht herausziehen, wenn das Gerät noch eingeschaltet ist. Ein elektrischer Schlag oder ein
Wohnungsbrand können die Folge sein.
Ts: Trockenkugel-Temperatur.
Th: Feuchtkugeltemperatur.
Temperatur Ts °C/°F Th °C/°F
Mindest-
19,4 / 66,9 13,9 / 57,0
Innentemperatur
Maximale-
26,7 / 80,1 19,4 / 66,9
Innentemperatur
Mindest-
19,4 / 66,9 13,9 / 57,0
Außentemperatur
Maximale
46 / 114,8 24 / 75,2
Außentemperatur
Temperatur Ts °C/°F Th °C/°F
Mindest-
10 / 50 -
Innentemperatur
Maximale-
26,7 / 80,1 -
Innentemperatur
Mindest-
-8 / 17,6 -9 / 15,8
Außentemperatur
Maximale
24 / 75,2 18 / 64,4
Außentemperatur
INSTALLATIONSANLEITUNG
Öffnen sie das
vordere
rahmengitter
Schieben sie die
originalfilter
heraus
Setzen sie den
doppelwirkungsfilter
fur die
elektrostatikbehandlung
und die luftreinigung in
den schlitzen.
Schieben sie den
originalfilter zuruck.
3-15
Deutsch
Netzstecker ziehen. Falls das
Klimagerät an einen eigenen
Stromkreis angeschlossen ist,
diesen Stromkreis unterbrechen
(Sicherung herausdrehen oder
Sicherungsautomat abschalten).
Batterien aus der Fernbedienung
nehmen.
Betreiben Sie das Gerät 2
Stunden lang in folgender
Einstellung.
Betriebsmodus : kühlen
Temperatur : 30˚C/86˚F
Wartungsverfahren
1. Luftfilter mit Staubsauger absaugen oder in lauwarmem Wasser (unter 40°C/
104˚F) mit neutraler Seife auswaschen.
Intervall
Mindestens alle 2
Wochen.
Ggf. häufiger.
Mindestens alle 2
Wochen.
Ggf. häufiger.
Wartungsteile
Luftfilter
Innen-Gerät
Innen-Gerät
1. Staub oder Schmutz an Gitter und Abdeckung mit einem weichen Tuch
abwischen. Das Tuch vorher in lauwarmem Wasser (unter 40°C/104˚F)
mit neutraler Seife anfeuchten.
2. Weder Benzin, noch Verdünner oder sonstige Chemikalien zum Reinigen
verwenden.
3. Weder Benzin, noch Verdünner oder sonstige Chemikalien zum Reinigen
verwenden.
2. Sorgfältig ausspülen und vor dem Wiedereinsetzen trocknen.
INSTANDHALTUNG UND WARTUNG
! Vorsicht
Keine Heizgeräte in der Nähe der Klimaanlage einschalten, sonst kann die Kunststoffabdeckung durch zu grosse
Wärme schmelzen oder beschädigt werden.
BEI LÄNGERER NICHTBENUTZUNG DES KLIMA-GERÄTES
! Achtung
Vor Wartung des Klimagerätes das Stromkabel vom Netz trennen.
Das Stromkabel nicht herausziehen, wenn das Gerät noch eingeschaltet ist. Ein elektrischer Schlag oder ein
Wohnungsbrand können die Folge sein.
! Vorsicht
1. Der Filter für die Elektrostatikbehandlung und die
Luftreinigung sollte bei bräunlicher Verfärbung oder
spätestens nach 6 Monaten gewechselt werden.
2. Verbrauchte, staubige Filter sollten weggeworfen
werden. Sie können auch nach Reinigen und waschen
nicht wieder verwendet werden.
3. Der Filter ist ein Verbrauchsgegenstand, den Sie von
ihrem Kimagerätehändler beziehen können.
4. Verwenden Sie das neue Filtermaterial sofort nach
Entnahme aus der versiegelten Verpackung. Packen Sie
den neuen Filter nicht zu früh vor der tatsächlichen
Verwendung aus, da er sonst seine Luftreinigungswirkung
verliert.
3-16
Im Falle einer Funktionsstörung ist das Gerät sofort auszuschalten. Nachfolgend einige Hinweise zur
Behebung von einfachen Störungen.
Kann die Störung nicht behoben werden, sollte der örtliche Kundendienst bzw. der Installateur
benachrichtigt werden.
Ursache / Maßnahme
- Schutzeinrichtung gegen häufiges Anlassen. 3 bis 4 Minuten
warten, bevor der Kompressor anläuft.
- Stromversorgung fehlerhaft/ggf. Sicherung austaushen.
- Netzstecker nicht eingesteckt.
- Timer möglicherweise falsch programmiert.
- Falls die Störung nach diesen Kontrollen weiterhin besteht sollte
der Installateur benachrichtigt werden.
- Luftfilter verschmutzt.
- Türen order Fenster geöffnet.
- Lufteinlaß bzw. Luftauslaß verstopft.
- Regeltemperatur nicht hoch genug.
- Geruchsbildung möglicherweise durch Zigarettenrauch, Parfüm
usw. und entsprechenden Ablagerungen am Wärmetauscher.
- Bedingt durch Luftfeuchtigkeit nach längerem Betrieb des
Gerätes.
- Eingestellte Temperatur zu niedrig; Temperatureinstellung
erhöhen und das Gerät bei hoher Gebläsedrehzahl laufen lassen.
- Das Gerät ausschalten und den Reparaturservice benachrichtigen.
- Kälteflüssigkeit tritt in den Verdunster ein.
Störung
1. Der Kompressor setzt sich 3 Minuten nach Einschalten des
Klimagerätes nicht in Gang.
2. Das Klimagerät funktioniert nicht.
3. Der Luftstrom ist zu schwach.
4. Die ausgeblasene Luft riecht unangenehm.
5. Kondensation am Vordergitter des Innengerätes.
6. Wasser fließt aus dem Klimagerät.
7. Zischendes Geräusch während des Betriebs.
STÖRUNGS-BEHEBUNG
4-1
Italiano
Il presente manuale descrive come procedere all’installazione del condizionatore per assicurarne il corretto
funzionamento in condizioni di sicurezza.
Degli adattamenti possono rivelarsi necessari per rispondere a particolari esigenze locali.
Prima di utilizzare il condizionatore, leggere attentamente le presenti istruzioni. Conservarle per ogni evenienza
futura.
MANUALE D’INSTALLAZIONE
CONDIZIONATORE D'ARIA MURALE A FLUSSO RIPARTITO
MODELLO
IM-WM1-0302(2)-Acson
KÜHLFUNKTION (R22)
Modello di Riferimento Modello
WM301 AWM301
SL30C ALC30C
SL30B ALC30B
KÜHLFUNKTION (R410A)
Modello di Riferimento Modello
5WM311 A5WM311
5SL28C A5LC28C
RISCALDAMENTO (R22)
Modello di Riferimento Modello
WM301R AWM301R
SL30CR ALC30CR
SL30BR ALC30BR
RISCALDAMENTO (R410A)
Modello di Riferimento Modello
5WM301R A5WM301R
5SL28CR A5LC28CR
Part No.: A08019025521
4-2
! Cautela
Durante l’installazione, verificare accuratamente i punti seguenti.
Non procedere all’installazione in luoghi dove possano verificarsi fughe di gas.
Pericolo d’incendio in caso di fughe o di concentrazioni di gas intorno al condizionatore.
Verificare che i condotti di drenaggio siano stati correttamente installati.
Un’installazione incorretta può causare delle perdite d’acqua e danneggiare il mobilio.
Non sovraccaricare il condizionatore.
L’apparecchio è precaricato in fabbrica. Qualsiasi sovraccarico provoca una sovracorrente e può
danneggiare il compressore.
Dopo l’installazione o gli interventi di manutenzione accertarsi di rimettere a posto il pannello di
chiusura.
Una difettosa chiusura del pannello è causa di rumori durante il funzionamento.
IMPORTANTE
IL CONDIZIONATORE NON DEVE MAI ESSERE INSTALLATO O USATO
IN UNA LAVANDERIA.
! Avvertenza
L’installazione e la manutenzione devono essere eseguite da personale qualificato, competente in questo genere di
apparecchi e al corrente delle leggi e regolamenti in vigore.
Tutti gli allacciamenti elettrici devono essere eseguiti conformemente alla regolamentazione elettrica in vigore.
Prima di procedere agli allacciamenti secondo lo schema elettrico presentato più avanti, accertarsi che il voltaggio
dell’apparecchio corrisponda a quello della rete.
Dotare il condizionatore di una presa di TERRA al fine di prevenire i rischi originati da eventuali deficienze del
sistema di isolamento.
Evitare chi i fili elettrici tocchino condotti del refrigerante, il compressore o un qualsiasi organo rotante dei motori
della ventola.
Prima di installare il condizionatore o di procedere ad interventi di manutenzione, accertarsi che sia spento (OFF).
SOMMARIO
- Disegni e Dimensioni pag. i-ii
- Norme di Sicurezza pag. 2
- Diagramma per L’installazione pag. 3
- Installazione Dell’unità Esterna pag. 3
- Installazione Del Tubo Dell’orifizio pag. 4
- Installazione Dell’unità Interna pag. 6
- Condotti del Refrigerante pag. 7
- Allacciamenti Elettrici pag. 8
- Speciali Precauzioni per le Unità con R410A pag. 10
- Spurgo e Ricarica pag. 10
- Spie di Controllo pag. 11
- Funzionamento del Condizionatore D’aria pag. 13
- Condizioni di Funzionamento Estandar pag. 14
- Filtro Elettrostatico pag. 14
- Pulizia e Manutenzione pag. 15
- Guasti e Riparazioni pag. 16
Leggere attentamente le norme di sicurezza che seguono, prima di procedere all’installazione.
NORME DI SICUREZZA
4-3
Italiano
DIAGRAMMA PER L’INSTALLAZIONE
Griglia Dell’entrata
Dell’aria
Griglia D’ingresso
Dell’aria
Ingresso dell’aria
Condotti Del Refrigerante
Tubo di drenaggio
Pannello Anteriore
Pannello Posteriore
Interruttore
Avvio/Arresto
Fitri Dell’aria
Spie Luminose
Rejilla de aire de
retorno
Feritoria di Ventilazione
Unità Esterna
Unità Interna
INSTALLAZIONE DELL’UNITÀ ESTERNA
Il blocco esterno deve essere installato in modo da evitare
che la circolazione dell’aria calda di scarico venga strozzata
o ostruita, diminuendone così il flusso normale. Rispettare
nell’installazione le distanze di sicurezza sotto indicate.
Scegliere il luogo più fresco possibile in modo che la
temperatura dell’aria in entrata non sia superiore a quella
esterna (massimo 45°C/113°F).
Distanze di sicurezza
Nota: Se esistono ostacoli di più di 2m di altezza o una
qualsiasi ostruzione al di sopra dell’apparecchiatura,
aumentare le distanze sopra indicate.
Effusore Della
Ventola di
Aerazione
A
B
C
D
Ingresso dell’aria
Ostacolo
Ostacolo
Aria di ritorno
Aria di scarico
Ostacolo
Ostacolo
Aria di ritorno
Portello di Servizio
Dimensioni A
Distanza
minima, mm 300 1000
(in) (11,8) (39,4) (11,8) (19,7)
D
500
B C
300
4-4
INSTALLAZIONE DEL TUBO DELL’ORIFIZIO
Tubo dell’orifizio
1
2
34
1
2
3
4
Unità Esterna
Interno
Orifizio
Tubo di raccordo
Dado svasato 3/8” (femmina)
Raccordo svasato 3/8” (maschio)
! Cautela
Si deve installare il tubo dell’orifizio nella direzione corretta come indicato sopra.
Una direzione inadeguata potrebbe danneggiare il sistema di funzionamento.
Nota: La presente installazione è valida soltanto per WM301 / SL30B & WM301 / SL30C
A. Installazione del tubo dell’orifizio dell’unità esterna (con spazio di installazione sufficiente)
Tubo dell’orifizio
Passi:
1. Collegare il dado “Femmina” del tubo dell’orifizio
direttamente alla valvola liquido.
2. Allargare il tubo della linea liquido e collegarlo al
raccordo “Maschio” del tubo dell’orifizio.
Tubo
dell’orifizio
Tubo linea
liquido
Passo 2
Passo 1
4-5
Italiano
Tubo linea liquido
Brasatore
C. Installazione del tubo dell’orifizio dell’unità interna
Unità Interna
Tubo dell’orifizio
B. Installazione del tubo dell’orifizio dell’unità esterna (con spazio di installazione limitato)
Passo 4
Passo 3
Passo 2
Passo 1
Tubo dell’orifizio
Qualora non fosse possibile collegare il tubo dell’orifizio direttamente alla valvola liquido per motivi di spazio insufficiente,
sarà possibile collegarlo al tubo entro la linea liquido.
Passi:
1. Allargare il tubo della linea liquido e collegarlo alla
valvola liquido.
2. Brasare un raccordo “Maschio” al tubo della linea liquido.
3. Collegare il dado “Femmina” del tubo dell’orifizio al
raccordo “Maschio”.
4. Allargare un altro tubo per la linea liquido e collegarlo al
raccordo “Maschio” del tubo dell’orifizio.
Passi:
1. Brasare un raccordo “Maschio”
al tubo della linea liquido.
3. Allargare un altro tubo per la
linea liquido e collegarlo al
raccordo “Maschio” del tubo
dell’orifizio.
2. Collegare il dado “Femmina”
del tubo dell’orifizio al raccordo
“Maschio”.
Tubo linea liquido
Brasatore
Tubo linea
liquido
Tubo
dell’orifizio
Tubo linea
liquido
Tubo dell’orifizio
Tubo linea
liquido
Tubo
dell’orifizio
Tubo linea
liquido
Tubo
dell’orifizio
4-6
INSTALLAZIONE DELL’UNITÀ INTERNA
Mantenimento e
Servicing spazio
Aria Flusso
Direzione
Più alto del
livello degli
occhi.
Il blocco interno deve essere installato in modo che la
circolazione dell’aria fredda di scarico e dell’aria di ritorno
sia la più ampia possibile. Assicurarsi di mantenere le
distanze di sicurezza illustrate nella figura. Installare il blocco
interno in modo che non si trovi ad ess ere direttamente
esposto ai raggi del sole o in prossimità di porte e finestre.
Questa disposizione è la migliore anche per le tubazioni e il
sistema di drenaggio.
Montaggio dello chassis
Accertarsi della capacità di tenuta della parete. Se il muro
non è in grado di sopportare il peso dell’apparecchio,
rinzorzarlo con delle piastre, delle travi o dei pilastrini di
sostegno.
Per il montaggio orizzontale, utilizzare il filo a piombo.
Fissare con 4 viti appropriate.
Nel caso in cui le tubazioni posteriori fuoriescano, praticare
sul muro un foro di 65mm di diametro servendosi di una
perforatrice a cono. Il foro deve presentare all’esterno una
leggera inclinatura verso il basso (veder figura).
Collegamento del condotti
Rimuovere la vite che assicura il pannello anteriore.
Collegamento Del Condotto
1
2
3
4
5
Dentro
Fuori
Inclinazione 1/50
Collegamento Posteriore Destro
I condotti del refrigerante possono essere collegati
all’apparecchiatura in differenti modi (lato posteriore destro
o sinistro) utilizzando i fori predisposti sul rivestimento
esterno (vedere figura). Piegare accuratamente i tubi nel verso
richiesto per condurli al foro appropriato. Poiché dal lato
posteriore destro la conduttura deve fuoriuscire, sostenerla
opportunamente e fissarne la direzione (vedere figura).
Utilizzado un nastro adesivo, attaccarvi quindi il tubo di
drenaggio.
Montaggio dell’unità sullo chassis
Agganciare l’unità alla parte superiore dello chassis (inserire
i due ganci posteriori dell’unità negli appositi fori dello
chassis). Per controllare se gli agganci sono correttamente
inseriti nella piastra d’installazione, spostare l’unità
leggermente verso destra e sinistra.
Il tubo
pesca
nell’acqua
Perdite di
Liquido
Perdite di
Liquido
Perdite di
Liquido
Tubo di drenaggio
Il tubo di drenaggio interno deve essere posizionato in leggera
pendenza per garantirne un buon funzionamento. Evitare
condizioni che possono causare perdite d’acqua.
Cavetto Di
Collegamento
Tubo di drenaggio
J
Errato
J
Errato
J
Errato
j
Corretto
50mm
50mm
50mm
Drenaggio dell’acqua
Piastra d’installazione
Marcatura off-line
Filo
4-7
Italiano
Lunghezza e altezza delle condutture
Se la conduttura è troppo lunga, la capacità e l’affidabilità
dell’apparecchio risultano entrambe compromesse. Più grande è
il numero dei gomiti, maggiore è la resistenza al flusso del sistema
di raffreddamento. In tale situazione, le capacità di raffreddamento
diminuiscono e l’attività del compressore può ridursi fino a
diventare inefficace. Scegliere sempre il percorso più breve e
attenersi alle indicazioni fornite nella tabella che segue:
Attenzione: Il refrigerante precaricato in fabbrica nel
blocco esterno è calcolatoper una tubatura
di 7,62m/25ft di lunghezza.
CONDOTTI DEL REFRIGERANTE
Unità Esterna
Unità Interna
Taglio del tubo di rame
Condutture
Non usare condotti di rame contaminati o danneggiati. Non
rimuovere le parti in plastica, i tappi in gomma e i dadi di
ottone da valvole, accessori vari, condutture e serpentini fino
a quando non si è pronti a collegare le tubature di aspirazione
e dei liquidi alle valvole ed altri accessori.
Se sono necessari degli interventi di brasatura, assicurarsi di
passare l’azoto sul serpentino e sui giunti mentre si esegue
l’intervento. Ciò eviterà la formazione di fuliggine sulla parete
interna dei tubi di rame.
Tagliare il tubo col tagliatubi.
Rimuovere le bavature dall’estremità del tubo utilizzando
l’apposito attrezzo. Tenere il tubo verso il basso per evitare
che le limature metalliche penetrino al suo interno.
Inserire sui tubi di raome i dadi svasati che si trovano sulle
bocchette d’ingresso delle unità interna ed esterna.
Svasare il tubo secondo le misure mostrate in tablella.
L’estremità svasata del tubo deve essere omogenea e non
presentare fessure o graffiature.
! Cautela
Nell’unità di raffreddamento WM301 si utilizzata un’orifizio come congegno di dilatazione. Questo è montato nel tubo
dell’acqua dell’ unità interna.
Collegamento delle condutture alle unità
Centrare la tubatura e stringere a mano il dado quanto
basta.
A mezzo di una chiave torsiometrica, stringere quindi il
dado fino a che si produca lo scatto previsto.
L
H
Modello 07/10 15 20 30
Lunghezza massima, m (ft), L
12
(39,4)
12
(39,4)
15
(49,2)
15
(49,2)
35
(114,8)
Altezza massima m (ft), H 5 (16,4) 5 (16,4) 8 (26,2) 8 (26,2) 15 (49,2)
Mass. num. di gomiti 10 10 10 10 10
Diametro tubi liquidi 1/4" 1/4" 1/4" 3/8" 3/8"
Diametro tubi gas 3/8" 1/2" 5/8" 5/8" 5/8"
25
Tubo Svasato
Tubature Interne
Dadi Di Svaso
Giunto Svasato
Chiave Fissa
Chiave Torsiometrica
12,7 (1/2) 55 (40,6)
15,88 (5/8) 65 (48,0)
6,35 (1/4) 18 (13,3)
9,53 (3/8) 42 (31,0)
Ø Tubo, D A (mm)
Pollici mm Imperiale Rigido
1/4" 6,35 1,3 0,7
3/8" 9,52 1,6 1,0
1/2" 12,70 1,9 1,3
5/8" 15,88 2,2 1,7
Dimensioni Del Tubi mm / (Pol)
Chiave Rsiometrica (nm)
Togliere Sbavatura Del Tubo
Estremità Rastremata
Tubo Di Rame
4-8
L
COMP
N2
N1
N
T
COMP
L
N
S
R
COMP
N2
N1
L
COMP
N
ALLACCIAMENTI ELETTRICI
Raffreddamento
IMPORTANTE : * I valori sopra indicati hanno solo un carattere indicativo. Devono quindi essere verificati e scelti in modo da
rispondere alle leggi vigenti e ai regolamenti locali. Inoltre, dipendono pure dal tipo di impianto e dai conduttori
utilizzati.
**
L
appropriato intervallo di tensione deve essere confrontato con i dati della targa dell
apparecchio.
ETL unità elencata è soltanto applicabile ad alimentazione di 60Hz esclusivamente.
COMP
N2
N1
L
COMP
R
S
N
L
N
L
WM301 VS SL30C
WM07 / 10 / 15 / 20 / 25 / 301 VS SL07 / 10 / 15 / 20 / 25 / 30B
5WM311 VS 5SL28C
Nell’impianto elettrico esistente sono
necessari un interruttore bipolare con
contatti separati da almeno 3mm e un
fusibile/interruttore automatico.
!
Morsettiera
Dell’Unità Esterno
Corda Di Alimentazione
Di Corrente
Corda Di Alimentazione
Di Corrente
Nell’impianto elettrico esistente sono
necessari un interruttore bipolare con
contatti separati da almeno 3mm e un
fusibile/interruttore automatico.
!
Morsettiera
Dell’Unità Interna
Morsettiera
Dell’Unità Esterno
Corda Di
Alimentazione Di
Corrente
Nell’impianto elettrico esistente sono
necessari un interruttore bipolare con
contatti separati da almeno 3mm e un
fusibile/interruttore automatico.
!
WM201 / 251 VS SL20 / 25B (3 La Fase)
Morsettiera
Dell’Unità Interna
Morsettiera
Dell’Unità Esterno
L
COMP
N2
N1
N
T
COMP
L
N
S
R
Nell’impianto elettrico esistente sono
necessari un interruttore bipolare con
contatti separati da almeno 3mm e un
fusibile/interruttore automatico.
!
Corda Di Alimentazione
Di Corrente
Morsettiera
Dell’Unità Interna
Morsettiera
Dell’Unità Esterno
WM301 VS SL30C (3 La Fase)
Morsa Elettrica
Cavetto Di
Collegamento
Tutti i fili devono essere collegati saldamente.
I fili non devono toccare né i condotti del refrigerante, ne il
compressore né gli organi rotanti del motore della ventola.
I fili di collegamento tra il blocco interno e quello esterno devoso
essere fissati alla morsettiera come indicato nella figura.
La corda di alimentazione di corrente deve equivalere
ad un minimo di H05RN-F (245IEC57).
Modello Interno WM 071/ 101/ 151 WM201/ 251/ 301 5WM311 WM301 WM201/ 251/ 301 WM301
Esterno SL07/ 10/ 15B SL20/ 25/ 30B 5SL28C SL30C SL20/ 25/ 30B SL30C
Voltaggi ammessi**
220V-240V/ 1Ph/ 50Hz + o 208V-230V/ 1Ph/ 60Hz + 380V-415V/ 3Ph/ 50Hz +N+
Dimensioni del cavetto di alimentazione*
mm
2
1,5 2,5 2,5 4 1,5 1,5
Numero dei fili 333355
Dimensioni del cavetto di interconnessione*
mm
2
1,5 2,5 2,5 2,5 1,5 1,5
Numero dei fili 333444
Fusibili consigliati A 15 20 20 25 15 15
Morsettiera
Dell’Unità Interna
4-9
Italiano
Riscaldamento
4WV
OF
COMP
N2
N1
L
4WV
OF
COMP
N
4WV
OF
COMP
N2
N1
L
4WV
A
OF
COMP
L
N
L
N
WM301R VS SL30CR
WM07 / 10 / 15 / 20 / 25 / 301R VS SL07 / 10 / 15 / 20 / 25 / 30BR
5WM301R VS 5SL28CR
Nell’impianto elettrico esistente
sono necessari un interruttore
bipolare con contatti separati da
almeno 3mm e un fusibile/
interruttore automatico.
!
Morsettiera
Dell’Unità Interna
Morsettiera
Dell’Unità Esterno
Corda Di Alimentazione
Di Corrente
Filo Di Collegamento Del Sensore Del
Serpentino Esterno (8m Di Lunghezza)
Collegato Al Dell’Unità Interna
Nell’impianto elettrico esistente
sono necessari un interruttore
bipolare con contatti separati da
almeno 3mm e un fusibile/
interruttore automatico.
!
Morsettiera
Dell’Unità Interna
Morsettiera
Dell’Unità Esterno
Corda Di Alimentazione
Di Corrente
Filo Di Collegamento Del Sensore Del
Serpentino Esterno (8m Di Lunghezza)
Collegato Al Dell’Unità Interna
4WV
OF
COMP
N2
N1
L
4WV
OF
COMP
L
N
S
R
N
T
4WV
OF
COMP
N2
N1
L
4WV
OF
COMP
L
N
A
S
R
N
T
WM301R VS SL30CR (3 La Fase)WM201 / 251R VS SL20 / 25BR (3 La Fase)
Filo Di Collegamento Del Sensore Del
Serpentino Esterno (8m Di Lunghezza)
Collegato Al Dell’Unità Interna
Filo Di Collegamento Del Sensore Del
Serpentino Esterno (8m Di Lunghezza)
Collegato Al Dell’Unità Interna
Nell’impianto elettrico esistente
sono necessari un interruttore
bipolare con contatti separati da
almeno 3mm e un fusibile/
interruttore automatico.
!
Morsettiera
Dell’Unità Interna
Morsettiera
Dell’Unità Esterno
Corda Di Alimentazione
Di Corrente
Morsettiera
Dell’Unità Interna
Morsettiera
Dell’Unità Esterno
Nell’impianto elettrico esistente
sono necessari un interruttore
bipolare con contatti separati da
almeno 3mm e un fusibile/
interruttore automatico.
!
Corda Di Alimentazione
Di Corrente
IMPORTANTE : * I valori sopra indicati hanno solo un carattere indicativo. Devono quindi essere verificati e scelti in modo da
rispondere alle leggi vigenti e ai regolamenti locali. Inoltre, dipendono pure dal tipo di impianto e dai conduttori
utilizzati.
**
L
appropriato intervallo di tensione deve essere confrontato con i dati della targa dell
apparecchio.
ETL unità elencata è soltanto applicabile ad alimentazione di 60Hz esclusivamente.
Modello Interno WM 071/ 101/ 151 R WM201/ 251/ 301 R 5WM301R WM301 R WM201/ 251/ 301 R WM301 R
Esterno SL07/ 10/ 15BR SL20/ 25/ 30BR 5SL28CR SL30CR SL20/ 25/ 30BR SL30CR
Voltaggi ammessi**
220V-240V/ 1Ph/ 50Hz + o 208V-230V/ 1Ph/ 60Hz + 380V-415V/ 3Ph/ 50Hz +N+
Dimensioni del cavetto di alimentazione*
mm
2
1,5 2,5 2,5 4 1,5 1,5
Numero dei fili 3 3 3355
Dimensioni del cavetto di interconnessione*
mm
2
1,5 2,5 2,5 2,5 1,5 1,5
Numero dei fili 5 5 5664
Fusibili consigliati A 15 20 20 25 15 15
4-10
SPURGO E RICARICA
Spurgo delle tubazioni el del unità interna
Fatta eccezione del unita esterno che è precaricato con il
refrigerante, il blocco interno e le tubature di collegamento
devono essere spurgate dell'aria. Essa contiene infatti dei
residui di umidità prodotti dal ciclo di raffreddamento che
possono provocare un malfunzionamento del compressore.
Rimuovere i tappi della valvola e del porto di servizio.
Collegare il centro della valvola del collettore alla pompa
di estrazione.
Collegare la valvola del collettore alla bocchetta di
servizio della valvola a 3 vie.
Avviare la pompa di estrazione. Far spurgare per 30
minuti circa. Il tempo di spurgo varia a seconda della
capacità della pompa di estrazione. Controllare che l’ago
della valvola del collettore si sia portata su -76mmHg
(0~76mmHg).
Attenzione
Se l’ago non si sposta su 0~76mmHg, controllare che non
ci siano perdite di gas (utilizzando il rivelatore di
refrigerante) in prossimità del collegamento svasato del
blocco interno ed esterno e riparare la perdita prima di
procedere.
Chiudere la valvola del collettore e spegnere la pompa di
estrazione.
Sul blocco esterno, aprire la valvola di aspirazione a (3
vie) e la valvola per il liquido a (2 vie) in senso anti-
orario con una brugola di 4mm.
SPECIALI PRECAUZIONI PER LE UNITÀ CON R410A
R410A è una miscela refrigerante quasi azeotropica di idrofluorocarburi (HFC) i quali sono ecologici. Ha un potenziale di
impoverimento dell’ozono uguale a zero (ODP=0) rendendolo conforme alle norme del protocollo di Montreal. È privo di
propagazione di fiamma ed ha un refrigerante a bassa tossicità (classificato come A1 da ARI). R410A è una miscela di R32
(50%) e R125 (50%).
L’olio POE usato come lubrificante nei compressori con R410A è diverso dall’olio minerale usato per i compressori in R22.
Durante l’installazione o le operazioni d’assistenza, si richiedono maggiori attenzioni al fine di non esporre, il refrigerante
troppo tempo all’aria umida. L’olio residuo POE rimasto nei tubi e nei componenti può assorbire umidità dall’aria.
Il refrigerante R410A è più facilmente affetto dall’ umidità della polvere che non l’ R22; assicurarsi quindi di chiudere
i terminali delle tubazioni prima di procedere all’installazione.
Si raccomanda di non effettuare altre cariche d’olio nel commpressore.
Nessuno altro refrigerante diverso da R410A è permesso.
Utilizzare strumenti ed attrezzature specifici per R410A.
i) Valvola di distribuzione e tubo flessibile di carica
ii) Rivelatore di perdita di gas
iii) Cilindro di refrigerante/cilindro di carica
iv) Adattatore pompa del vuoto
v) Attrezzi per saldatura
vi) Macchina per recupero di refrigerante
!!
!!
! ATTENZIONE
L’R410A deve essere caricato in stato liquido. Normalmente, la bombola di R410A è dotata di un tubo profondo per
il prelevamento del liquido. Se la bombola non è provvista di tale tubo, deve essere capovolta per permettere al
refrigerante R410A di uscire dalla valvola.
In caso di perdite, non effettuare aggiunte di refrigerante ma svuotare completamente l’unità ed effettuare di nuovo la
carica attenendosi alle indicazioni contenute nel manuale. Svuotare l’unità completamente e poi riempirla con R410A
nelle sue caratteristiche originali nella quantità raccomandata nelle specifiche.
Non rabboccare mentre si sta riparando una perdita perché potrebbe ridurre la prestazione dell’apparecchio. È necessiario
quindi svuotare completamente l’unità e ricaricare il refrigerante secondo le caratteristiche iniziali.
Ricarica Addizionale
Il blocco esterno è provvisto del refrigerante, precaricato in
fabbrica. Se la lunghezza del tubo è inferiore a 7,62m (25ft),
dopo l'aspirazione non è necessaria alcuna ricarica
addizionale. Se la lunghezza dei condotti è superiore ai
7,62m (25ft), usare i valori di ricarica addizionale come
indicato nella tabella in basso.
Bocchetta di
servizio
Valvola a 3 vie del
blocco esterno
Dadi di
svaso
Condotti del
refrigerante
Brugola
Unità Esterna
Unità Interna
Per il liquido
Per il gas
Pompa Di
Estrazione
Aperto
Chiuso
Chiuso
Valvola
di scarico
Valvola Di
Aspirazione
Chiuso
Hi
Lo
4-11
Italiano
Ricevitore a infrarossi
Il ricevitore segnali dell’unità interna emette un bip per
confermare il ricevimento di un segnale di trasmissione
dal telecomando.
SPIE DI CONTROLLO
Raffreddamento
La tabella mostra le spie luminose “LED” del condizionatore
d’aria durante il normale funzionamento e i guasti.
Le spie di controllo sono a diodi a emissione luminosa (LED)
e si trovano nella zona inferiore destra del condizionatore.
Spie luminose “LED” : Normale funzionamento e guasti dell’unità di raffreddamento
Spie luminose “LED” dell’unità di raffreddamento
Accensiones
Temporizzatore
Modalità
Riposo
Deumidificazione
Spie di Controllo Tipo LED
Ricevitore Infrarossi
Operazioni di ricarica
Tale operazione deve essere obbligatoriamente effettuata
utlizzando il cilindro del gas ed una bilancia di precisione.
Il gas refrigerante viene introdotto nel blocco esterno tramite
la bocchetta di servizio della valvola aspirante.
Rimuovere il tappo della bocchetta di servizio.
Collegare il collettore a bassa pressione alla bocchetta di
aspirazione del serbatoio cilindrico e chiudere il collettore
ad alta pressione. Spurgare l’aria dal tubo flessibile.
Mettere in funzione il condizionatore.
Modello 10 m/32,8 ft 12 m/39,4 ft 15 m/49,2 ft
071 / 101 / 151 35 65 -
201 35 65 110
251 / 301 90 165 280
071R / 101R /151R 50 90 -
201R 60 110 185
251R / 301R 120 220 370
Modello 10 m/32,8 ft 12 m/39,4 ft 15 m/49,2 ft
311 80 150 255
301R 110 200 335
Ricarica addizionale in grammi
(R410A)
Aprire il cilindro del gas e la valvola del collettore a bassa
pressione.
Quando la quantità richiesta di refrigerante è stata
pompata nell’impianto, chiudere la valvola del collettore
a bassa pressione e la valvola del cilindro del gas.
Scollegare il tubo flessibile dalla bocchetta di servizio.
Rimettere il tappo della bocchetta di servizio.
Ricarica addizionale in grammi
(R22)
Unità Esterna
Unità Interna
Per il liquido
Per il gas
Aperto
Valvola
di scarico
Valvola Di
Aspirazione
Chiuso
Hi
Lo
Valvola di
controllo
Chiuso
Chiuso
ACCESO o SPENTOACCESO Lampeggiante
Indicatore Operazione/Difficoltà Intervento
Accensione timer.
Accensione modalità riposo.
Deumidificazione.
Anti-gelo. Pulire il filtro e commutare su ventilazione.
Sensore aria ambiente in corto o
Rivolgersi al servizio di assistenza.
falso contatto.
Sensore serpentino interno in corto o
Rivolgersi al servizio di assistenza.
falso contatto.
Può esserci un problema di contatti a livello del sensore
Rivolgersi al servizio di assistenza.
o un sovraccarico del compressore o una fuga di gas.
Accensione Secco Temporizzatore Riposo
Continuamente
Ogni 2 secondi
Due volte ogni
2 secondi
Tre ogni 2 secondi
4-12
Spie luminose “LED”: Normale funzionamento e guasti dell’unità di riscaldamento
Raffreddamento.
Deumidificazione.
Ventilazione.
Riscaldamento.
Riscaldamento automatico.
Raffreddamento automatico.
Sbrinamento.
Sovraccarico del compressore. Rivolgersi al servizio di assistenza.
Sensore serpentino interno in corto o falso contatto.
Rivolgersi al servizio di assistenza.
Sensore serpentino esterno in corto o falso contatto. Rivolgersi al servizio di assistenza.
Sensore aria ambiente in corto o falso contatto. Rivolgersi al servizio di assistenza.
Se il sistema è su raffreddamento o riscaldamento (senza la marcia notturna inserita),
può esserci un problema di contatti a livello del sensore o un sovraccarico del
compressore o una fuga di gas.
Azione in corso/indicazione del guasto Intervento
Freddo Secco
Ventola
Cald Riposo
Riscaldamento
La tabella che segue indica la funzione della diverse spie di
controllo del condizionatore come pure gli interventi da
effettuare in caso di guasto.
Le spie di controllo sono a diodi a emissione luminosa (LED)
e si trovano nella zona inferiore destra del condizionatore.
I condizionatori provvisti di pompa di calore sono dotati di
una modalità automatica che, alternando automaticamente
tra modalità “freddo” e “caldo”, assicura una temperatura
ambiente confortevole, in corrispondenza della temperatura
impostata dall’utente.
Spie luminose “LED” dell’unità di riscaldamento.
ACCESO o SPENTO
ACCESO
Lampeggiante
Raffreddamento
Modalità calore/
ventilatore
(Rosso/Verde)
Deumidificazione
Modalità
Riposo
4-13
Italiano
Raffreddamento
Secco
Orizzontale
25°C/77°F
FUNZIONAMENTO DEL CONDIZIONATORE D’ARIA
Modalità Secco
Quando c’e molta umidità si può attivare la modalità secco.
Premere il pulsante <MODE> e scegliere <SECCO>.
Se la temperatura ambiente è più di 2ºC/35,6ºF superiore
alla temperatura impostata, il condizionatore funzionerà
in modalità raffreddamento fino a che la differenza tra le
due temperature sarà minore di 2ºC/35,6ºF e poi funzionerà
in modalità secco.
Se la differenza tra la temperastura ambiente e la
temperatura impostata è minore di 2˚C/35,6ºF, il
condizionatore funzionerà direttamente in modalità secco.
In funzione secco il condizionatore funzionerà a velocità
BASSA.
Funzione riscaldamento (solo per i condizionatori
provvisti di pompa di calore)
Quando si avvia il condizionatore iniziaalmente o durante
il ciclo di scongelamento, il ventilatore interno si metterà
in funzione solo dopo che la bobina termica ha raggiunto
la temperatura desiderata.
Una volta raggiunta la temperatura desiderata, il ventilatore
interno continuerà a funzionare fino a che la bobina termica
è in grado di provvedere calore.
Aggiustamento Orizzontale
Per una più efficace circolazione dell'aria, è possibile
aggiustare a mano verso destra o sinistra la griglia di
ventilazione.
Durante il funzionamento in modalità freddo e secco,
evitare di dirigere, per un lungo periodo di tempo, la feritoia
di ventilazione verso il basso. In caso contrario, è possibile
che sulla feritoia si formi della condensa che sgocciolerà
sul pavimento.
Conservazione Calda (solo per pompa di
Riscaldamento)
Durante l’interdizione del compressore, la ventola interva
pud essere portata sulle posizioni:
(i) ON (Acceso) (posizione normale) o
(ii) OFF (spento) o
(iii) Intervallo (Accesò e Spento)
spostando l’interruttore come mostrato nel diagramma.
L’interruttore è posizionato sulla copertura frontale
(vicino all’interruttore ON/OFF)
NOTA : Quando l’opzione è selezionata, il gruppo di
alimentazione della necessità dell’unità di essere
ripristinato per attivare la funzione.
Protezione contro il surriscaldamento (solo per i
condizionatori provvisti di pompa di calore)
Se la temperatura esterna e/o quella interna sono troppo
alte, o se il filtro è sporco e intasto, il refrigerante può
surriscaldarsi. In questi casi il compressore si spegnerà
automaticamente quando la temperatura raggiunge 62˚C/
143,6ºF.
Prevenzione brina
Quando il filtro è sporco, la temperatura di evaporazione
diminuisce e causa la formazione di brina.
La spia luminos lampeggia per indicare che il filtro è
sporco. Se la temperatura di evaporazione scende a
-2˚C/28,4ºF, il condizionatore scatta e inizia l’operazione
di scongelamento automaticamente.
Velocità della ventola e capacità di raffreddamento
nominale
La capacità di raffreddamento nominale è raggiungibile a
velocità massima del ventilatore.
La capacità di raffreddamento è minore quando il
condizionatore funziona a velocità ventola MEDIA o
BASSA.
All’interrusttore ON/OFF
HOT KEEP
OFF
INTERVAL
ON
4-14
INSTALLAZIONE
FILTRO DEODORIZZANTE E PURIFICATORE D’ARIA A DOPPIA AZIONE
ELETTROSTATICA E INTELAIATURA FILTRO
AZIONE 1-
FILTRO PURIFICATORE D’ARIA
ELETTROSTATICO
l filtro in polipropilene precaricato elettrostaticamente
rimuove particelle di polvere microscopiche, fumo ed altre
particelle invisibili in modo da mantenere l’aria pulita.
FILTRO ELETTROSTATICO
AZIONE 2-
FILTRO DEODORIZZANTE
Il filtro di carbone attivato rimuove odori sgradevoli nell’aria
e mantiene l’aria fresca nella stanza.
CONDIZIONI DI FUNZIONAMENTO ESTANDAR
Unità di riscaldamento
Unità di raffreddamento
! Avvertenza
Staccare la corrente prima di procedere a qualsiasi intervento di manutenzione sul condizionatore.
Non rimuovere il cavo di alimentazione quando il condizionatore è acceso. Questo può causare seri
shock elettrici e pericolo d’incendio.
Ts: Temperatura a termometro asciutto.
Th: Temperatura a termometro bagnato.
Temperatura Ts °C/°F Th °C/°F
Temperatura
19,4 / 66,9 13,9 / 57,0
interna minima
Temperatura
26,7 / 80,1 19,4 / 66,9
interna massima
Temperatura
19,4 / 66,9 13,9 / 57,0
esterna minima
Temperatura
46 / 114,8 24 / 75,2
esterna massima
Temperatura Ts °C/°F Th °C/°F
Temperatura
interna minima
Temperatura
interna massima
Temperatura
esterna minima
Temperatura
esterna massima
10 / 50
26,7 / 80,1
-8 / 17,6
24 / 75,2
-9 / 15,8
18 / 64,4
Aprirela
Griglia
Anteriore.
Togliere I Filtri
Original.
Inserire I Filtri A Doppia
Azione Elettrostatica
E Deodorizzante il
Posizione.
Inserire Nuovamente
I Filtri Originali.
4-15
Italiano
Periodo
Almeno due volte
al mese.
Più spesso se
necessario.
Almeno due volte
al mese.
Più spesso se
necessario.
QUANDO NON SI PREVEDE DI UTILIZZARE IL CONDIZIONATORE
PER UN LUNGO PERIODO DI TEMPO
Far funzionare il
condizionatore per 2 ore
nella modalità che segue.
Funzione : freddo
Temperatura : 30°C/86ºF
Disinserire la spina.
Se per il condizionatore si
utilizza un circuito
indipendente, interrompere
la corrente di tale circuito.
Togliere le pile dal
telecomando.
PULIZIA E MANUTENZIONE
Procedure Di Manutenzione
1. Togliere la polvere dal filtro usando un’aspirapolvere o lavarlo in acqua tiepida
(sotto ai 40˚C/104˚F) con detersivo neutro.
2. Sciacquare bene e asciugare il filtro prima di rimetterlo nell’unità.
3. Non usare mai benzina o prodotti chimici per pulire il filtro.
1. Togliere la polvere e la sporcizia dalla griglia e dal pannello, strofinando
con un panno soffice imbevuto di acqua tiepida (sotto ai 40˚C/104˚F) e
detersivo neutro.
2. Non usare mai benzina o prodotti chimici per pulire l’unità interna.
Componenti
Filtro dell’aria
interno
Unità interna
! Cautela
Non utilizzare apparecchiature di riscaldamento nelle immediate vicinanze del condizionatore. L’eccessivo calore
potrebbe danneggiare o deformare il pannello in plastica.
! Avvertenza
Staccare la corrente prima di procedere a qualsiasi intervento di manutenzione sul condizionatore.
Non rimuovere il cavo di alimentazione quando il condizionatore è acceso. Questo può causare seri shock elettrici
e pericolo d’incendio.
! Cautela
1. Il filtro deodorizzante e purificatore d’aria elettrostatico
deve essere cambiato ogni 6 mesi oppure quando diventa
di colore brunastro.
2. Il filtro sporco è da buttare, esso non può essere lavato e
riusato.
3. Il filtro è un componente che può essere acquistato dal
rivenditore di condizionatori d’aria autorizzato.
4. Una volta tolto il filtro dal suo sacchetto ermetico, usarlo
immediatamente. L’effetto deodorizzante del filtro
diminuisce se si apre il sacchetto molto prima di usarlo.
4-16
Non appena si nota che il condizionatore funziona male, spegnerlolo immediatamente. Qui di seguito, sono
elencati alcuni guasti minori con le relative cause.
GUASTI E RIPARAZIONI
Origine / Intervento
- Protezione contro gli avvii riavvicinati. Attendre 3 or 4 minuti
affinchè il compressore si metta in moto.
- Interruzione della corrente o fusibile bruciato.
- La spina non è inserita.
- L’orario impostato sul timer di ritardo non è corretto.
- Se il guaste dopo tali verifiche, chiamare il
servizio assistenza.
- Il filtro dell’aria è sporco.
- Porte e finestre aperte.
- L’aspirazione e lo scarico dell’aria sono ostruiti.
- La temperatura impostata non è sufficientemente bassa.
- Il cattivo odore può essere causato da sigarette, particelle di
fumo, profumi, ecc. depositati sul serpentino.
- La condensa è dovuta all’umidità dell’aria dopo un lungo
periodo di funzionamento.
- La temperatura impostata è troppo bassa. Aumentare la
temperatura e la velocità della ventola.
- Spegnere il condizionatore e chiamare il rivenditore.
- Immissione di refrigerante nel serpentino dell’evaporatore.
Guasto
1. Il compressore nom si mette in funzione 3 minuti dopo aver
acceso il condizionatore.
2. Il condizionatore non funziona.
3. Il funsso d’aria è troppo debole.
4. L’aria che esce dal condizionatore ha cattivo odore.
5. Condensa sulla griglia anteriore di ventilazione dell’unita
interna.
6. Acqua sgocciola dal condizionatore.
7. L’aria esce dal condizionatore emettendo un suono anormale.
Se il guasto persiste, rivolgersi al servizio di assistenza.
5-1
Español
Este manual facilita instrucciones de instalación que garantizan un seguro y buen funcionamiento de la unidad
de aire acondicionado.
Es posible que sea necesario realizar un ajuste especial para adecuarse a los requisitos locales.
Por favor, antes de usar su equipo de aire acondicionado, lea cuidadosamente este manual de instrucciones, y
consérvelo para futuras consultas.
MANUAL DE INSTALACION
EQUIPO DE AIRE ACONDICIONADO DE TIPO DIVIDIDO DE MONTAJE MURAL
MODELO
IM-WM1-0302(2)-Acson
ENFRIAMIENTO (R22)
Modelo de Referencia Modelo
WM301 AWM301
SL30C ALC30C
SL30B ALC30B
ENFRIAMIENTO (R410A)
Modelo de Referencia Modelo
5WM311 A5WM311
5SL28C A5LC28C
CALENTADOR (R22)
Modelo de Referencia Modelo
WM301R AWM301R
SL30CR ALC30CR
SL30BR ALC30BR
CALENTADOR (R410A)
Modelo de Referencia Modelo
5WM301R A5WM301R
5SL28CR A5LC28CR
Part No.: A08019025521
5-2
! Cuidado
Asegúrese de seguir durante la instalación los siguientes puntos importantes.
No instalar la unidad ahí donde pueda haber fuga de gas inflamable.
Siel gas procedente de una fuga de gas se acumula alrededor de la unidad puede producirse unincendio.
Asegúrese de que la tubería de desagüe está conectada correctamente.
Si la tubería de desagüe no está conectada correctamenta se puede producir una fuga de agua que
mojaría los muebles.
No sobrecargar la unidad.
Esta unidad está pre-cargada en fábrica. Su sobrecarga ocasionará sobre-corrinte o rotura del compresor.
Asegúrese de que el panel de la unidad vuelve a cubrirla, bien colocado, después de la instalación
o de cualquier reparación.
Un panel mal sujetado hará que la unidad haga ruido al funcionar.
IMPORTANTE
NO INSTALE NI HAGA USO DE LA UNIDAD DE AIRE ACONDICIONADO EN UN CUARTO
DESTINADO A LAVAR ROPAS.
! Advertencia
La instalación y el mantenimiento deben ser realizador por personas calificadas que estén familiarizadas con el
código y los reglamentos locales y que tengan experiencia en este tipo de equipo.
Todo el cableado de campo debe instalarse de acuerdo al reglamento de cableado nacional.
Antes de comenzar la instalación eléctrica de acuerdo con el diagrama de cableado, asegúrese de que el voltaje
nominal de la unidad se corresponde con el de la place de identificación.
La unidad debe estar PUESTA A TIERRA para evitar posibles peligros debidos a fallas del aislamiento.
Ninguno delos cables de la instalación eléctrica dene estar en contacto con la tubería refrigerante, el compresor o
cualquier pieza móvil de los motores del ventilador.
Antes de iniciar la instalación o reparación de la unidad, asegúrese de que ha sido apagara (OFF).
ÍNDICE
- Esquema y Dimensiones página i-ii
- Precautiones de Seguridad página 2
- Diagramma de la Instalación página 3
- Instalación de la Unidad Exterior página 3
- Instalación de Tubo de orificio página 4
- Instalación de la Unidad Interior página 6
- Tubería de Refrigerante página 7
- Conexión del Cableado Eléctrico página 8
- Precauciones Especiales Para El R410A página 10
- Limpieza de la Tubería de Refrigerante página 10
- Luz Indicadora página 11
- Operación de la Unidad de aire Acondicionado página 13
- Condiciones de Funcionamiento Estándar página 14
- Filtro Electrostático página 14
- Reparaciones y Mantenimiento página 15
- Localización de Averias página 16
Antes de instalar su equipo, sírvase leer las siguientes precauciones de seguridad cuidadosamente.
PRECAUCIONES DE SEGURIDAD
5-3
Español
DIAGRAMMA DE LA INSTALACIÓN
Rejilla de Entrada de
Aire
Rejilla de
Descarga de Aire
Entrada de Aire
Tubería de Refrigerante
Menguera de Desagüe
Cubierta Delantera
Chásis Trasero
Botón de Commutación
ON/OFF (Apagado/
Encendido)
Filtros Del
Aire
Luces indicadoras
Receptor de señal
Persiana de Descarga de
Aire
Unidad Exterior
Unidad Interior
INSTALACIÓN DE LA UNIDAD EXTERIOR
Acess de servicio
La unidad de exterior debe instalarse de manera que no haya
cortocircuitos de la descarga de aire caliente ni obstrucción
a una flujo de aire uniforme. Por favor, siga el espacio
proporcionado para la instalación tal y como se indica en el
gráfico. Seleccionar el lugar más fresco posible donde la
temperatura del aire de entrada no sea superior a la
temperatura externa (máximo 45°C/113°F).
Espacio libre de instalación
Nota: Si hubiese algún obstáculo de más de 2m de altura o
cualquier obstrucción en la parte superior de la unidad, dejar
más espacio que el indicado en la tabla anterior.
Tobera de
Descarga de Aire
A
B
C
D
Entrada de Aire
Obstaculo
Obstaculo
Aire de Retorno
Aire de Descarga
Obstaculo
Obstaculo
Aire de Retorno
Dimensión A
minima, mm 300 1000
(in) (11,8) (39,4) (11,8) (19,7)
B C D
300
500
Distancia
5-4
INSTALACIÓN DE TUBO DE ORIFICIO
Tubo de orificio
1
2
34
1
2
3
4
Unidad Exterior
Interior
Orificio
Tubo, conectando
Tuerca abocardada 3/8" (Hembra)
Junta abocardada 3/8" (Macho)
! Cuidado
El tubo de orificio debe instalarse en la dirección correcta, según se muestra en la figura anterior.
En caso contrario, el sistema podría no funcionar correctamente.
Nota: Esta instalación es sólo para WM301 / SL30B & WM301 / SL30C
A. Instalación del tubo de orificio de la unidad exterior (donde el espacio de instalación sea
suficientemente ancho)
Tubo de orificio
Paso:
1. Conecte directamente la tuerca “Hembra” del tubo de
orificio a la válvula de líquidos.
2. Abocine el tubo de líquido para conectarlo a la junta
“Macho” del tubo de orificio.
Tubo de orificio
Tubo de
líquido
Paso 1
Paso 2
5-5
Español
Tubo de líquido
Unión
C. Instalación de tubo de orificio en la unidad interior
Unidad Interior
Tubo de orificio
B. Instalación del tubo de orificio de la unidad exterior (donde el espacio de instalación sea limitado)
Paso 4
Paso 3
Paso 2
Paso 1
Tubo de orificio
Si no se puede conectar directamente el tubo de orificio a la válvula de líquidos debido a limitaciones de espacio, se puede
conectar en algún punto del tubo de líquido.
Paso:
1. Abocine el tubo de líquido para conectarlo a la válvula.
2. Empalme una junta “Macho” adicional al tubo de
líquido.
3. Conecte la tuerca “Hembra” del tubo de orificio a la
junta “Macho”.
4. Abocine otro tubo de líquido y conéctelo a la junta
“Macho” del tubo de orificio.
Paso:
1. Empalme una junta “Macho”
adicional al tubo de líquido.
3. Abocine otro tubo de líquido y
conéctelo a la junta “Macho” del
tubo de orificio.
2. Conecte la tuerca “Hembra” del
tubo de orificio a la junta
“Macho”.
Tubo de líquido
Unión
Tubo de líquido
Tubo de orificio
Tubo de líquido
Tubo de orificio
Tubo de líquido
Tubo de orificio
Tubo de líquido
Tubo de orificio
5-6
INSTALACIÓN DE LA UNIDAD INTERIOR
Espacio de
mantenimiento y
servicio
Dirección del
flujo del aire
Más arriba que
el nivel de la
vista
La unidad de interior debe estar instalada de modo que el
aire de descarga frío no entre en contacto con el aire de
retorno caliente. Por favor, siga el espacio proporcionado
para la instalación tal y como se indica en el gráfico. No
colocar la unidad de interior donde le caiga la luz del sol
directamente. El emplazamiento debe ser adecuado para las
tuberías y la evacuación y debe estar lejos de la puerta o
ventana.
Montaje de la placa de instalación
Verificar que la pared es lo suficientemente sólida como para
soportar el peso de la unidad. Si no es así, se debe reforzar la
pared con placas, vigas o pilares.
Usar la línea de plomada para el montaje horizontal y fijar
con 4 tornillos adecuados.
En caso de retracción de la tubería trasera, perforar un agujero
de 65mm de diámetro con una broca cónica, ligeramente
más bajo en la pared externa (véase la fig.).
Vía de la tubería
Retirar los tornillos que sujetan el panel frontal.
Vía de la Tubería
1
2
3
4
5
Placa de Instalación
Marca-fuera de línea
Rosca
Interior
Exterior
Inclinación 1/50
Vía lateral derecha y trasera
La tubería de refrigerante se puede dirigir hasta la unidad de
varias maneras (izquierda o derecha detrás de la unidad),
usando los agujeros recortados en la caja de la unidad (véase
la figura). Doblar cuidadosamente las tuberías hasta la
posición requerida para alinearlas con el agujero. Para la
extracción derecha y trasera, sujetar la parte inferior de la
tubería y fijar la dirección (véase la figure). La manguera de
desagüe de condensación debe ser fijada con cinta a las
tuberías.
Montar la unidad en la placa de instalación
Enganchar la unidad de interior en la porción superior de la
placa de instalación (Enganchar los 2 ganchos de la parte
trasera superior en el borde superior de la placa de
instalación). Para asegurar que los ganchos se encuentren
adecuamente instalados en la bandeja de instalación, intente
moverlos ligeramente hacia la izquierda o la derecha.
Extremo
sumejido
in agua
Fuga de
Agua
Fuga de
Agua
Fuga de
Agua
Tubería de desagüe de agua
La tubería de desagüe de interior debe tener una pendiente
descendente para lograr un vaciado uniforme. Evite
situaciones que puedan causar escapes de agua.
Cable De
Interconexión
Menguera de
Desagüe
J
Incorrecto
J
Incorrecto
J
Incorrecto
j
Correcto
50mm
50mm
50mm
Desagüe del agua
5-7
Español
Llave De tuercas
Llave Dinamométrica
Tubería De Interior
Junta Abocinada
Tubo Abocinado
Longitud y elevación de la tubería
Si la tubería es demasiado larga, tanto la capacidad como la
fiabilidad de la unidad disminuirán. A medida que aumenta el
número de curvas, aumenta la resistenci al flujo de refrigerante,
reduciéndose por lo tanto la capacidad de enfriamiento, lo cual
puede resultar en un compresor defectuoso. Siempre escoger
el camino más corto posible y seguir la recomendación tal
como se indica en la siguiente tabla:
TUBERÍA DE REFRIGERANTE
Unidad Exterior
Unidad Interior
Corte del tubo de cobre
Instalación de tuberías
No use tuberías de cobre dañadas o contaminadas. No se deben
retirar los tapones de plástico y caucho, las tuercas de latón de las
válvulas, accesorios, tuberías y serpentines hasta que se esté listo
para conectar las líneas de succión o de líquido a las válvulas o
accesorios.
Si fuese necesario efectuar alguna soldadura, asegúrese de hacer
circular el gas nitrógeno por el serpentín y las juntas durante la
realización de la soldadura. Esto evitará la formación de hollín en
las paredes interiores de las tuberías de cobre.
Corte el tubo de conexión con un cortatubos.
Retire las rebabas de los bordes cortados de las tuberías con un
extractor. Ponga el extremo de la tubería hacia abajo para evitar
que los fragmentos metálicos de las rebabas entren en la tubería.
Inserte las tuercas abocinadas, montadas sobre las partes de la
conexión tanto de la unidad de interior como de la unidad de
exterior, en las tuberías de cobre.
Abocine el tubo con largura extra por encima de la herramienta
de abocinar como se muestra en el cuadro.
El borde abocinado debe estar plano, sin grietas ni rasguños.
! Cuidado
En la unidad de resfriamiento WM301 se utiliza un orificio como dispositivo de dilatación. Eso està fijado a la cañería
del aire de la unidad interior.
Conexión de las tuberías a las unidades
Alinee el centro de la tubería y apriete suficientemente
la tuerca abocinada con los dedos.
Finalmente, apriete la tuerca abocinada con la llave
dinamométrica hasta que la llave haga “clic”.
L
H
Observación: El refrigerante precargado en la unidad de
exterior está previsto para una longitud de
tubería de 7,62m/25ft.
Tuerca Abocinada
Modelo 07/10 15 20 25 30
Longitud máxima, m (ft), L
12
(39,4)
12
(39,4)
15
(49,2)
15
(49,2)
35
(114,8)
Elevación máxima m (ft), H 5 (16,4) 5 (16,4) 8 (26,2) 8 (26,2) 15 (49,2)
N° máx. de curvas 10 10 10 10 10
Tamaño de la tubería de líquido 1/4" 1/4" 1/4" 3/8" 3/8"
Tamaño de la tubería de gas 3/8" 1/2" 5/8" 5/8" 5/8"
Tamaño de la Tubería mm / (in) Par Nm / (Ft-lb)
12,7 (1/2) 55 (40,6)
15,88 (5/8) 65 (48,0)
6,35 (1/4) 18 (13,3)
9,53 (3/8) 42 (31,0)
Ø Tubo, D A (mm)
Pulgada mm Pulgada Rigido
1/4" 6,35 1,3 0,7
3/8" 9,52 1,6 1,0
1/2" 12,70 1,9 1,3
5/8" 15,88 2,2 1,7
Retirar las Rebabas
Tubo de Cobre
Bloque de Estampar
5-8
L
COMP
N2
N1
N
T
COMP
L
N
S
R
COMP
N2
N1
L
COMP
N
CONEXIÓN DEL CABLEADO ELÉCTRICO
Unidad de enfriamiento
IMPORTANTE : * Los valores mostrados arriba se dan a título informativo únicamente. Estos deben ser verificados y seleccionados
a fin de que cumplan con los códi gos y reglamentos locales y/o nacionales. También están sujetos al tipo de
instalación y al tamaño de los conductores.
** L’appropriato intervallo di tensione deve essere confrontato con i dati della targa dell’apparecchio. ETL unità
elencata è soltanto applicabile ad alimentazione di 60Hz esclusivamente.
COMP
N2
N1
L
COMP
R
S
N
L
N
L
WM301 VS SL30C
WM07 / 10 / 15 / 20 / 25 / 301 VS SL07 / 10 / 15 / 20 / 25 / 30B
5WM311 VS 5SL28C
La fuente de alimentación debe poseer
dispositivos de protección (disyuntor
o fusible) con un sistema de
separación bipolar con una separación
entre contactors minima de 3mm.
!
Regleta De Terminales
Unidad De Exterior
El Cable Del Enchufe
El Cable Del Enchufe
La fuente de alimentación debe
poseer dispositivos de protección
(disyuntor o fusible) con un sistema
de separación bipolar con una
separación entre contactors minima
de 3mm.
!
Regleta De Terminales
Unidad De Interior
Regleta De Terminales
Unidad De Exterior
El Cable Del Enchufe
La fuente de alimentación debe poseer
dispositivos de protección (disyuntor o
fusible) con un sistema de separación
bipolar con una separación entre
contactors minima de 3mm.
!
WM201 / 251 VS SL20 / 25B (3 La Fase)
Regleta De Terminales
Unidad De Interior
Regleta De Terminales
Unidad De Exterior
L
COMP
N2
N1
N
T
COMP
L
N
S
R
La fuente de alimentación debe poseer
dispositivos de protección (disyuntor
o fusible) con un sistema de
separación bipolar con una separación
entre contactors minima de 3mm.
!
El Cable Del Enchufe
Regleta De Terminales
Unidad De Interior
Regleta De Terminales
Unidad De Exterior
WM301 VS SL30C (3 La Fase)
El Cable Utilizado
Para Juntar
Cable De
Interconexión
Todos los alambres deben estar conectados firmemente.
Ningún alambre debe tocar ninguna de las tuberías de refrigerante,
el compresor ni las piezas móviles del motor del ventilador.
Los alambres de conexión entre la unidad de interior y la unidad
de exterior deben estar sujetados a la abrazadera del alambre según
la figura mostrada.
El cable del enchufe para el toma corriente debe de ser equivalente
H05RN-F (245IEC57), tomando este como un minimo
requerimiento.
Modelo Intérieure WM 071/ 101/ 151 WM201/ 251/ 301 5WM311 WM301 WM201/ 251/ 301 WM301
Extérieure SL07/ 10/ 15B SL20/ 25/ 30B 5SL28C SL30C SL20/ 25/ 30B SL30C
Margen de la tensión**
220V-240V/ 1Ph/ 50Hz + o 208V-230V/ 1Ph/ 60Hz + 380V-415V/ 3Ph/ 50Hz +N+
Tamaño del cable de alimentación* mm
2
1,5 2,5 2,5 4 1,5 1,5
Número de alambre 333355
Tamaño del cable de interconexión*
mm
2
1,5 2,5 2,5 2,5 1,5 1,5
Número de alambre 333444
Fusible recomendado A 15 20 20 25 15 15
Regleta De Terminales
Unidad De Interior
5-9
Español
Unidad de calentamiento
4WV
OF
COMP
N2
N1
L
4WV
OF
COMP
N
4WV
OF
COMP
N2
N1
L
4WV
A
OF
COMP
L
N
L
N
WM301R VS SL30CR
WM07 / 10 / 15 / 20 / 25 / 301R VS SL07 / 10 / 15 / 20 / 25 / 30BR
5WM301R VS 5SL28CR
La fuente de alimentación debe poseer
dispositivos de protección (disyuntor
o fusible) con un sistema de separación
bipolar con una separación entre
contactors minima de 3mm.
!
Regleta De Terminales
Unidad De Interior
Regleta De Terminales
Unidad De Exterior
El Cable Del Enchufe
Alambre de conexión del sensor del
serpentín de exterior (8m de longitud)
sujetado a la unidad de interior
La fuente de alimentación debe poseer
dispositivos de protección (disyuntor o
fusible) con un sistema de separación
bipolar con una separación entre
contactors minima de 3mm.
!
Regleta De Terminales
Unidad De Interior
Regleta De Terminales
Unidad De Exterior
El Cable Del Enchufe
Alambre de conexión del sensor del
serpentín de exterior (8m de longitud)
sujetado a la unidad de interior
4WV
OF
COMP
N2
N1
L
4WV
OF
COMP
L
N
S
R
N
T
4WV
OF
COMP
N2
N1
L
4WV
OF
COMP
L
N
A
S
R
N
T
WM301R VS SL30CR (3 La Fase)WM201 / 251R VS SL20 / 25BR (3 La Fase)
Alambre de conexión del sensor del
serpentín de exterior (8m de longitud)
sujetado a la unidad de interior
Alambre de conexión del sensor del
serpentín de exterior (8m de longitud)
sujetado a la unidad de interior
La fuente de alimentación debe poseer
dispositivos de protección (disyuntor
o fusible) con un sistema de separación
bipolar con una separación entre
contactors minima de 3mm.
!
Regleta De Terminales
Unidad De Interior
Regleta De Terminales
Unidad De Exterior
El Cable Del Enchufe
Regleta De Terminales
Unidad De Interior
Regleta De Terminales
Unidad De Exterior
La fuente de alimentación debe poseer
dispositivos de protección (disyuntor
o fusible) con un sistema de
separación bipolar con una separación
entre contactors minima de 3mm.
!
El Cable Del Enchufe
IMPORTANTE : * Los valores mostrados arriba se dan a título informativo únicamente. Estos deben ser verificados y seleccionados
a fin de que cumplan con los códi gos y reglamentos locales y/o nacionales. También están sujetos al tipo de
instalación y al tamaño de los conductores.
** L’appropriato intervallo di tensione deve essere confrontato con i dati della targa dell’apparecchio. ETL unità
elencata è soltanto applicabile ad alimentazione di 60Hz esclusivamente.
Modelo Intérieure WM 071/ 101/ 151 R WM201/ 251/ 301 R 5WM301R WM301 R WM201/ 251/ 301 R WM301 R
Extérieure SL07/ 10/ 15BR SL20/ 25/ 30BR 5SL28CR SL30CR SL20/ 25/ 30BR SL30CR
Margen de la tensión**
220V-240V/ 1Ph/ 50Hz + o 208V-230V/ 1Ph/ 60Hz + 380V-415V/ 3Ph/ 50Hz +N+
Tamaño del cable de alimentación* mm
2
1,5 2,5 2,5 4 1,5 1,5
Número de alambre 3 3 3355
Tamaño del cable de interconexión*mm
2
1,5 2,5 2,5 2,5 1,5 1,5
Número de alambre 5 5 5664
Fusible recomendado A 15 20 20 25 15 15
5-10
LIMPIEZA DE LA TUBERÍA DE REFRIGERANTE
Limpieza de la tubería y la unidad de interior
Salvo la unidad de exterior que esta precargada con
refrigerante, se debe limpiar con chorro de aire la unidad de
interior y las tuberías de conexión de refrigerante puesto
que el aire que contiene humedad que queda en el ciclo del
refrigerante puede causar un funcionamiento defectuoso del
compresor.
Retirar las tapas de la válvula y del agujero de servicio.
Conecte el centro del calibrador de carga a la bomba de
vacío.
Conecte el calibrador de carga al orificio de servicio de
la válvula de 3 vías.
Arranque la bomba de vacío. Evacue aproximadamente
durante 30 minutos. El tiempo de evacuación varía según
la capacidad de la bomba de vacío. Asegúrese de que
la aguja del calibrador de carga se ha movido hacia
- 76mmHg (0~76mmHg).
Cuidado
Si la aguja del calibrador no se mueve a 0-76mmHg,
compruebe las fugas de gas (utilizando detector de
refrigerante) en la conexión de tipo abocinada de la unidad
interior y exterior y repare la fuga antes de seguir con el
siguiente paso.
Cierre la válvula del calibrador de cambio y pare la bomba
de vacío.
En la unidad exterior, abra la válvula de succión (3 vías)
y la válvula líquida (2 vías) (en la dirección contraria a
las agujas del reloj) con una llave de 4mm para tornillos
hexagonales.
PRECAUCIONES ESPECIALES PARA EL R410A
R410A es un refrigerante casi azeotrópico de mezcla hidro fluorocarbonada (HFC) que respeta el medio ambiente. Tiene
un ODP = 0 y cumple con las regulaciones del Protocolo de Montreal. No tiene propagación de llama y es un refrigerante
de baja toxicidad (clasificado como A1 por ARI). El R410A es una mezcla de R32 (50%) y R125 (50%).
El aceite de POE se utiliza para la lubricación del compresor con el refrigerante R410A, y es diferente al ageite mineral
empleando con el refrigerante R22. Durante la instalación se debe tener la precaución extra de no exponer el circuito
refrigerante demasiado tiempo a la intemperie, ya que el refrigerante R410A puede absorber la humedad del aire.
Si se compara el refrigerante R410A con el refrigerante R22, el refrigerante R410A se ve más afectado por la humedad y
las partículas sólidas, se racomienda tapar siempre los finales de tubería con tapones mientras se hace la instalación.
No se permite la carga adicional de aceite al compresor.
No se puede emplear ningún refrigerante más que el R410A.
Herramientas específicas para el refrigerante R410A
i) Manómetros y mangueras de descarga
ii) Detector de escape de Gas
iii) Cilíndro de carga del refrigerante
iv) Bomba de vacio
v) Abocardador
vi) Máquina de recuperación de refrigerante
!!
!!
! CUIDADO
R410A se debe cargar como líquido. Generalmente cilíndro R410A se equipa con un tubo de depresión para la
retirada líquida. Si no hay tubo de depresión, el cilíndro se debe invertir para retirar líquido R410A de la válvula.
Cuando exista una fuga en el circuito se debe de extraer el refrigerante que quede. Corregir la fuga, hacer el vacio. Y
cargar por peso el equipo con R410A en los datos originales de no hacerlo as y se repone refrigerante, el rendimiento
del equipo se reducirà.
No toque el compresor o las tuberías de refrigerante con la unidad en funcionamiento. Si lo hace, utilice guantes.
Carga adicional
El refrigerante está precargado en la unidad de exterior. Si
la longitud de la tubería es inferior a 7,62m (25 ft), no es
necesaria una carga adicional después de la aspiración. Si
la longitud de la tubería es de más de 7,62m (25 ft), siga los
valores de carga adicional tal y como se indica en la tabla a
continuación.
Tubería de refrigerante
Agujero De Servicio
Válvula de 3 vías de la
unidad de exterior
Tuerca
Abocinada
Llave Allen
Unidad Interior
Unidad Exterior
Pomba de
Vacío
Lado del
liquido
Lado del gas
Abierta
Cerrada
Cerrada
Válvula de
descarga
Válvula de
Succión
Cerrada
Lo
Hi
5-11
Español
Receptor de señal IR (infrarroja)
Al transmitirse una señal de infrarrojos proveniente del
mando a distancia, el receptor de señales de la unidad de
interior producirá un sonido para confirmar la aceptación
de la señal transmitida.
LUZ INDICADORA
Unidad de enfriamiento
La tabla que se muestra a continuación contiene las luces
indicadoras LED de funcionamiento normal y de condición
de falla de la unidad de aire acondicionado.
Las luces indicadoras LED están situadas en la parte inferior
derecha de la unidad de aire acondicionado.
Luces indicadoras LED : Condiciones de operación normales y condiciones de
operación defectuosas de la unidad de enfriamiento
Luces indicadoras LED de funcionamiento para la
unidad de enfriamiento.
Preder ON
El Programador
del Tiempo
Modo
Vigilia
Modo
Seco
Luces indicadoras LED
Receptor Infrarrojo
Operación de carga
Esta operación se debe realizar usando un cilindro de gas y
una máquina de pesaje obligatoriamente. La carga adicional
se introduce en la unidad de exterior por la válvula de
aspiración a través del agujero de servicio.
Retirar el tapón del agujero de servicio.
Conectar el lado de presión baja del calibrador de carga
al centro del agujero de servicio de succión del depósito
del cilindro y cierre el lado de alta presión del calibrador.
Purgue el aire de la manguera de servicio.
Poner en marcha la unidad de aire acondicionado.
Modelo 10 m/32,8 ft 12 m/39,4 ft 15 m/49,2 ft
071 / 101 / 151 35 65 -
201 35 65 110
251 / 301 90 165 280
071R / 101R /151R 50 90 -
201R 60 110 185
251R / 301R 120 220 370
Modelo 10 m/32,8 ft 12 m/39,4 ft 15 m/49,2 ft
311 80 150 255
301R 110 200 335
Carga adicional en gramos (R410A)
Abrir la válvula del cilindro de gas y la de cierre de baja
presión
Cuando se haya bombeado la unidad con la cantidad de
refrigerante requerida, cerrar la válvula de baja presión y
del cilindro de gas.
Desconectar la manguera de servicio del agujero de
servicio. Volver a colocar la tapa del agujero de servicio.
Carga adicional en gramos (R22)
Unidad Interior
Unidad Exterior
Lado del
liquido
Lado del gas
Abierta
Válvula de
carga
Válvula de
Succión
Cerrada
Válvula de
control
Lo
Hi
Cerrada
Cerrada
ENCENDIDO o APAGADO
ENCENDIDO Parpadeante
Operación/Indicador de falla Acción
Programador de tiempo prendido ON.
Modo vigilia ON.
Modo seco.
Prevention de congelamiento hielo. Limpiar el filtro y pasar a ventilador alto.
Contacto del sensor de aire ambiente suelto/corto.
Llamar a su representante.
Contacto del sensor del serpentín de interior suelto/corto.
Llamar a su representante.
El sensor contacto de problema, proteccion para
Llamar a su representante.
sobrecarga del compresor, goteadura o escape de gas.
Continua
una vez cada
2 segundos
dos veces cada
2 segundos
tres veces cada
2 segundos
Preder
Seco
Vigilia
El Programador
del Tiempo
5-12
Luces indicadoras LED : Condiciones de operación normales y condiciones de operación
defectuosas de la unidad de calentamiento
Unidad de calentamiento
La tabla que se muestra a continuación contiene las luces
indicadoras LED para el funcionamiento normal y la
condición de falla de la unidad de aire acondicionado.
Las luces indicadoras LED están situadas en la parte
inferior derecha de la unidad de aire acondicionado.
Las unidad de calentamiento cuenta con un modo “auto”,
mediante el cual la unidad podrá proporcionar temperatura
de habitación moderada, simplemente con encender
automáticamente en posición “cool” (frío) o “heat” (calor),
de acuerdo a la temperatura seleccionada por el usuario.
Luces indicadoras LED de funcionamiento para la
unidad de calentamiento
Modo de
enfriamiento
Modo Programador para
Calentador / Ventilador
(rojo / verde)
Modo seco Modo vigilia
Modo de enfriamiento.
Modo seco.
Modo ventilador.
Modo de calentamiento.
Modo automático en funcionamiento como calentador.
Modo automático en funcionamiento como enfriador.
Operación de descongelación.
Protección de sobrecarga del compresor. Llamar a su representante.
Contacto del sensor del serpentín de interior suelto /corto. Llamar a su representante.
Contacto del sensor del serpentín de exterior suelto /corto. Llamar a su representante.
Contacto del sensor de aire ambiente suelto /corto. Llamar a su representante.
Si el sistema está en el modo de calentamiento o enfriamiento (con la funcion de vigilia apagada),
es posible que el sensor tenga un problema de contacto, se haya disparado la proteccion de
sobrecarga del compresor o haya una fuga de gas.
Condiciones de operación normales /
condiciones de operación defectuosas
Acción
Frio Seco
Ventilador Oscilación Vigilia
ENCENDIDO
Parpadeante
ENCENDIDO o APAGADO
5-13
Español
Enfriamiento
Seco
Horizontal
25°C/77°F
OPERACIÓN DE LA UNIDAD DE AIRE ACONDICIONADO
Modo seco
Cuando la humedad del aire es alta, la unidad puede operar
en modo seco. Pulse el botón de modo de funcionamiento
<MODE> y elija el seco <DRY>.
Si la temperatura de la habitación está 2°C/35,6°F por
encima de la temperatura elegida en el ajuste, entonces la
unidad de aire acondicionado funcionará en modo de
enfriamiento hasta que se quede a 2°C/35,6°F de diferencia,
comparada con la temperatura elegida antes de pasar a
modo seco.
Si la temperatura de la habitación está dentro de un margen
de 2°C/35,6°F de diferencia, comparada con la temperatura
elegida en el ajuste, funcionará directamente en modo seco.
En el modo de funcionamiento seco, la unidad funcionará
a BAJA velocidad.
Modo de calefacción (únicamente para unidad de
calentamiento)
Cuando la unidad acaba de ser encendida o de pasar por el
ciclo de deshielo, el ventilador de adentro sólo empezará a
funcionar después de que el serpentín alcance la
temperatura deseada.
Cuando se alcanza la temperatura elegida en el ajuste, el
ventilador de adentro funcionará hasta que el serpentín no
pueda proveer más calor adicional.
Control Del Flujo De Aire Horizontal
Para lograr una circulación de aire más eficaz, se puede
ajustar la rejilla de descarga de aire hacia la izquierda o la
derecha manulmente.
Durante el funcionamiento en modo enfriamiento y seco,
no dirigir la rejilla directriz de descarga de aire hacia abajo
mucho tiempo. Si el funcionamiento continúa de esta
manera, puede haber condensación en la rejilla directriz.
Puede haber goteo como resultado de la condensación.
Mantiene Caliente (Sólo para la bomba de
calefacción)
Durante la desconexión del compresor, el ventilador
interno podría estar:
(i) ON [en posición de encendido] (default) o
(ii) OFF [en posición de encendido] o
(iii) en posición de encendido y cerrado intervalo
por medio de ajustar la conexión de corredera en el
diagrama.
El interruptor situado en la cubierta delantera del cuandro
(junto al butón de conexión).
NOTA : Cuando se selecciona la opción, la fuente de
alimentación de la necesidad de la unidad de ser
reajustado para activar la función.
Protección contra el sobre-calentamiento
(únicamente para unidad de calentamiento)
En caso de que la temperatura interna y/o externa sean
demasiado altas, o que el filtro esté sucio y obstruido,
puede que el refrigerante se sobre-caliente. El compresor
se parará sólo cuando la temperatura de condensación
alcance los 62°C/143,6°F.
Prevención de congelamiento
Cuando el filtro de aire está sucio, la temperatura de
evaporación descenderá y acabará por causar hielo.
La luz “LED” empezará a parpadear para indicar que el
filtro está sucio. Si la temperatura de evaporación alcanza
los -2°C/28,4°F la unidad reaccionará y se descongelará.
Velocidad del ventilador y capacidad de
enfriamiento especificada
La capacidad de enfriamiento especificada se provee con
el ventilador a máxima velocidad.
La capacidad de enfriamiento es más baja cuando la
unidad funciona con el ventilador a velocidades media
y baja.
Interruptor ON/OFF
HOT KEEP
OFF
INTERVAL
ON
5-14
! Advertencia
Desconecte la unidad de aire acondicionado de su fuente principal de electricidad antes de intentar repararla.
NO tire del cordón de alimentación cuando la alimentación está conectada. Esto puede causar graves
sacudidas lo que puede producir un incendio.
CONDICION DE FUNCIONAMIENTO ESTÁNDAR
Unidad de calentamiento
Unidad de enfriamiento
Temperatura Ts °C / °F Th °C / °F
Temperatura
19,4 / 66,9 13,9 / 57,0
interior mínima
Temperatura
26,7 / 80,1 19,4 / 66,9
interior máxima
Temperatura
19,4 / 66,9 13,9 / 57,0
exterior mínima
Temperatura
46 / 114,8 24 / 75,2
exterior máxima
Ts: Temperatura de ampolla seca.
Th: Temperatura de ampolla húmeda.
Temperatura Ts °C / °F Th °C / °F
Temperatura
10 / 50
interior mínima
Temperatura
26,7 / 80,1
interior máxima
Temperatura
-8 / 17,6 -9 / 15,8
exterior mínima
Temperatura
24 / 75,2 18 / 64,4
exterior máxima
PURIFICADOR DE AIRE ELECTROSTÁTICO DE ACCIÓN DUAL Y
FILTRO DESODORIZADOR Y MARCO DE FILTRO
ACCIÓN 1-
PURIFICADOR DE AIRE ELECTROSTÁTICO
Elimine el polvo microscópico, humo y pequeñas partículas
invisibles para mantener el aire de la habitación limpio
mediante el filtro de polipropileno electrostático precargado.
FILTRO ELECTROSTÁTICO
ACCIÓN 2-
FILTRO DESODORIZADOR
Elimine odores desagradables y odores en el aire y mantenga
el aire en la habitación fresco mediante el filtro de carbón
activado.
MODO DE INSTALACIÓN
Abarala rejilia
del marco
frontal.
Deslice los filtro original
hacia el exterior.
Inserte los filtros de
acción dual
electrostaticos y
desodorizadores
en la ranura.
Deslice los filtro originales en su
antigua posición.
5-15
Español
Opera la unidad durante
2 horas con el siguiente
programa.
Modo de funcionamiento :
cool (“frio”)
Temperatura : 30˚C/86˚F
Retirar al clavija de
alimentación. Si se usa un
circuito eléctrico
independiente para su unidad,
cortar el circuito.
Retirar las baterías del
control remoto.
CUANDO NO SE VA A USAR LA UNIDAD POR UN TIEMPO PROLONGADO
REPARACIONES Y MANTENIMIENTO
Procedimientos Para Su Maintenimento
1. Elimine el polvo adherido al filtro mediante una aspiradora o lavándolo en
agua templada (a menos de 40°C/104°F) con un jabón neutro.
2. Enjuague y seque bien el filtro antes de volverlo a colocar en la unidad.
3.
No use gasolina, sustancias volátiles ni productos químicos para limpiar el filtro.
1. Limpie cualquier suciedad o polvo de la rejilla o el panel con un trapo
suave empapado de agua tibia (a menos de 40°C/104°F) con una solución
detergente neutra.
2. No use gasolina, sustancias volátiles ni productos químicos para limpiar la
unidad de interior.
Precuencia
Al menos una vez
cada dos semanas.
Con mayor frecuencia
si es necesario.
Al menos una vez
cada dos semanas.
Con mayor frecuencia
si es necesario.
Componentes
Filtro de aire
(unidad de interior)
Unidad de interior
! Cuidado
No opere aparatos de calor cerca de la unidad de aire acondicionado. Esto puede fundir o deformar el panel de
plástico como resultado del excesivo calor.
! Advertencia
Desconecte la unidad de aire acondicionado de su fuente principal de electricidad antes de intentar repararla.
NO tire del cordón de alimentación cuando la alimentación está conectada. Esto puede causar graves
sacudidas lo que puede producir un incendio.
! Cuidado
1. Los filtros purificadores y desodorizadores de aire se
deben cambiar cada seis meses o cuando el color del
filtro cambie a amarronado, cualquiera de los casos que
se de con anterioridad.
2. Tire el filtro usado con polvo y no lo utilice de nuevo,
incluso después de haber sido lavado y limpiado.
3. El filtro es una artículo consumible, que Ud. puede obtener
en cualquier agente de acondicionadores de aire.
4. Utilice el nuevo filtro inmediatamente después de
desenvolverlo. No envuelva el filtro nuevo demasiado
pronto antes de ser usado, pues podría disminuir su efecto
desodorizante.
5-16
Cuando detecte alguna anomalia en el funcionamiento de la unidad de aire acondicionado, desconéctela
inmediatamente de la fuente de alimentación eléctrica. Como unas simples pistas para el mantenimiento y
las reparaciones, compruebe los siguientes fallos y sus causas.
LOCALIZACIÓN DE AVERIAS
Causa / Acción
- Protección contra los arranques frecuentes. Espere 3 ó 4 minutos
hasta que el compresor comience a funcionar.
- Falla de alimentación o se debe remplazar el fusible.
- La clavija de alimentación está desconectada.
- Es posible que no haya ajustado correctamente el temporizador
de retardo
.
- Si la falla persiste después de estas verificaciones,
póngase en contacto con el instalador de la unidad.
- El filtro de aire está sucio.
- Las puertas o ventanas están abiertas.
- La entrada y salida del aire están obstruidas.
- La temperatura elegida en el ajuste no es lo suficientemente alta.
- Estos olores se pueden deber a particularas de humo de cigarrillo,
perfume, sudor, etc. que se hayan adherido al serpentin.
- Esto se debe a la humedad del aire, después de un tiempo de
funcionamiento prolongado.
- La temperatura elegida en el adjuste es demasiado baja. Aumente
la temperatura elegida y empieece la unidad con el ventilador a alta
velocidad.
- Desconecte la unidad y llame a su concesionario.
- El líquido refrigerante está infiltrándose en el infiltrándose en el
serpentin del evaporador.
Falla
1. El compresor no empieza a funcionar 3 minutos después de
haber puesto en marcha la unidad de aire acondicionado.
2. La unidad de aire acondicionado no funciona.
3. El flujo de aire es demasiado bajo.
4. El flujo de aire de descarge huele mal.
5. Condensación en la rejilla de aire frontal-unidad de interior.
6. Sale agua de la unidad de aire acondicionado.
7. El fluio de aire suena como un silbido cuando la unidad de
aire acondicionado está en funcionamiento.
Si la averia persiste, póngase en contacto con el técnico o vendedor local.
6-1
Русский
Это руководство рассматривает процедуру установки с целью обеспечения безопасности и
соответствующих стандартов для функционирования блока кондиционера.
Специальная регулировка по месту установки может быть необходима.
Перед использованием Вашего кондиционера, прочитайте, пожалуйста, внимательно данное
руководство по эксплуатации и сохраните его для обращения за справками в будущем.
РУКОВОДСТВО ПО УСТАНОВКЕ
НАСТЕННЫЙ КОНДИЦОНЕР РАЗДЕЛЬНОГО ТИПА
Модель
IM-WM1-0302(2)-Acson
ТОЛЬКО ОХЛАЖДЕНИЕ (R22)
Справочная модель Модель
WM301 AWM301
SL30C ALC30C
SL30B ALC30B
ТОЛЬКО ОХЛАЖДЕНИЕ (R410A)
Справочная модель Модель
5WM311 A5WM311
5SL28C A5LC28C
ОБОГРЕВАТЕЛЬНЫЙ НАСОС (R22)
Справочная модель Модель
WM301R AWM301R
SL30CR ALC30CR
SL30BR ALC30BR
ОБОГРЕВАТЕЛЬНЫЙ НАСОС (R410A)
Справочная модель Модель
5WM301R A5WM301R
5SL28CR A5LC28CR
Part No.: A08019025521
6-2
! Осторожно
Пожалуйста, обратите внимание на нижеследующие важные моменты при
установке.
Не устанавливайте блок в месте, где может произойти утечка взрывоопасного газа.
Если имеется утечка газа и его сбор рядом с блоком, то он может стать причиной
возгорания.
Удостоверьтесь, что сливные трубы соединены надлежащим образом.
Если сливные трубы не соединены надлежащим образом, это может стать причиной
течи, которая намочит мебель.
Не подвергайте перегрузке блок
Данный блок установлен на определенную нагрузку на заводе-изготовителе.
Перегрузка вызовет перегрузку тока или повредит компрессор.
Удостоверьтесь, что панель блока закрыта после технического обслуживания или
установки.
Неплотно закрепленные панели вызовут шум при работе блока.
ВАЖНО
НЕ УСТАНАВЛИВАЙТЕ ИЛИ НЕ ИСПОЛЬЗУЙТЕ КОНДИЦИОНЕР В МОЕЧНОЙ.
! Внимание
Установка и техническое обслуживание должны проводиться квалифицированным персоналом,
знающим местный код и положения и имеющим опыт работы с данным видом устройств.
Весь монтаж проводов должен проводиться в соответствии с национальными правилами электромонтажа.
Перед началом электромонтажа удостоверьтесь, что напряжение блока соответствует указанному
на табличке, согласно электрической схеме.
Блок должен быть ЗАЗЕМЛЕН для предотвращения возможной опасности в результате неправильной
установки.
Вся электропроводка должна не приходить в соприкосновение с хладагентом насоса или лопастей двигателя.
Удостоверьтесь, что блок ВЫКЛЮЧЕН перед установкой или обслуживанием.
СОДЕРЖАНИЕ
- Схема и Размеры страница i-ii
- Меры Предосторожности страница 2
- Рисунок Установки страница 3
- Установка Комнатного Блока страница 3
- Монтаж Дроссельной трубки страница 4
- Установка Наружного Блока страница 6
- Проведение Трубопроводов
Хладагента страница 7
- Электрическая Схема Соединений страница 8
- Специальные меры предосторожности
при обращении с R410A страница 10
- Откачка Воздуха и Заправка страница 10
- Показания Индикаторов страница 11
- Операция Модуля Кондиционера страница 13
- Уcлoвия Стандapтннй Рaвоты страница 14
- Электростатический Фильтр
При Наличии страница 14
- Сервис и Техническое
Обслуживание страница 15
- Меры по Устранению страница 16
Перед установкой блока кондиционера, прочитайте, пожалуйста, внимательно меры предосторожности.
МЕРЫ ПРЕДОСТОРОЖНОСТИ
6-3
Русский
Внутренний модуль должен быть установлен так, чтобы
предотвратить короткого замыкания выпуска горячего
воздуха, или обеспечить беспрепятственный поток воздуха.
Пожалуйста, оставьте пространство для установки, как
показано на рисунке. По возможности выберите как можно
холодное место, где температура впуска воздуха не
превышает температуру воздуха на улице (максимум
45°C/
113°F
).
РИСУНОК УСТАНОВКИ
Решетка впуска
воздуха
Решетка выпуска
воздуха
Впуск воздуха
Трубопровод хладогента
Дренажный шланг
Передняя панель
Задняя панель
Включатель
ВКЛ/ВЫКЛ
Воздушный фильтр
Показания
индикаторов
Датчик
сигналов
Жалюзи выпуска
воздуха
Наружный Блок
Комнатный Блок
Пространство для установки
Примечание: При наличии препятствия высотой
более 2м, или препятствия в верхней части модуля,
пожалуйста, обеспечьте большее пространство,
чем указано в таблице вверху.
Отверстие выпуска
воздуха
A
B
C
D
Впуск воздуха
УСТАНОВКА КОМНАТНОГО БЛОКА
Возврат Воздуха
Выпуск воздуха
Препятствие
Препятствие
Препятствие
Препятствие
Возврат Воздуха
Доступ Технического
Обслуживания
Размер A
Мин.
Расстояние,
мм 300 1000
(дюйм) (11,8) (39,4) (11,8) (19,7)
500
B C
300
D
6-4
МОНТАЖ ДРОССЕЛЬНОЙ ТРУБКИ
Дроссельная трубка
1
2
34
1
2
3
4
К наружному блоку
В помещение
Диафрагма
Трубка
соединительная
Накидная гайка 3/8" (внутренняя резьба)
Резьбовый патрубок 3/8" (наружная резьба)
! Осторожно
Дроссельной трубку необходимо устанавливать в правильном направлении, как показано выше.
Установка в неправильном направлении может привести к выходу системы из строя.
Примечание: Эта установка производится только для моделей WM301 / SL30B и WM301 / SL30C.
A. Монтаж дроссельной трубки для наружного блока (при наличии свободного места для
выполнения установки)
Шаги:
1. Навинтить накидную гайку дроссельной трубки
непосредственно на жидкостный вентиль.
2. Развальцевать жидкостную трубу и присоединить
ее к резьбовому патрубку дроссельной трубки.
Дроссельная
трубка
Жидкостная
труба
Шаг 1
Шаг 2
Дроссельная трубка
6-5
Русский
Жидкостная
труба
Паяльник
C. Монтаж дроссельной трубки для внутреннего блока
Наружный Блок
Дроссельная трубка
B. Монтаж дроссельной трубки для наружного блока (при условии ограниченного
пространства для выполнения установки)
Шаг 4
Шаг 3
Шаг 2
Шаг 1
Дроссельная трубка
Если дроссельную трубку невозможно присоединить непосредственно к жидкостному вентилю из-за
тесноты, ее можно врезать в жидкостную трубу.
Шаги:
1. Развальцевать жидкостную трубу и
присоединить ее к жидкостному вентилю.
2. Припаять (твердым припоем) к жидкостной
трубе дополнительный патрубок с наружной
резьбой.
3. Навинтить накидную гайку дроссельной
трубки на патрубок с наружной резьбой.
4. Развальцевать другую жидкостную трубку и
присоединить ее к резьбовому патрубку
дроссельной трубки.
Шаги:
1. Припаять (твердым
припоем) к жидкостной
трубе дополнительный
патрубок с наружной
резьбой.
3. Развальцевать другую
жидкостную трубку и
присоединить ее к
резьбовому патрубку
дроссельной трубки.
2. Навинтить накидную гайку
дроссельной трубки на
патрубок с наружной
резьбой.
Жидкостная труба
Паяльник
Жидкостная
труба
Дроссельная
трубка
Жидкостная
труба
Дроссельная
трубка
Жидкостная
труба
Дроссельная
трубка
Жидкостная
труба
Дроссельная
трубка
6-6
Пространство Для
Ремонта и Технического
Обслуживания
Направление
Потока
Воздуха
Выше уровня
глаз
Внутренний модуль должен быть установлен так, чтобы
предотвратить столкновение выпуска холодного воздуха
с возвращающимся потоком горячего воздуха.
Пожалуйста, оставьте пространство для установки, как
показано на рисунке. Не устанавливайте внутренний
модуль там, где модуль подвергается воздействию прямых
солнечных лучей. Также расположение должно быть
удобным для прокладки трубопроводов и дренажа и
удалено от дверей и окон.
Установка Панели Крепления
Удостоверьтесь, что стена достаточно крепкая и
может выдержать вес модуля. В противном случае,
усильте стену панелями, балками или стойками.
С помощью уровня добейтесь горизонтальное
положение, и закрепите панель при помощи 4
крепежными шурупами.
В случае, если задние трубопроводы выступают,
просверлите диаметром 65мм коническим сверлом
отверстие, расположенное более низко на
наружной стене (смотрите рисунок).
Прокладка Трубопроводов
Снимите винт, крепящий переднюю панель.
Прокладка трубопроводов
1
2
3
4
5
Крепежная плита
Маркировка –
автономный режим
Резьба
Наружный
Наклон 1/50
Прокладка Справа и Сзади
Установите Модуль На Панель Крепления
Навесьте модуль на верхнюю часть панели
крепления (Подвесьте двумя крючками задней
верхней части внутреннего модуля на верхний край
панели крепления). Удостоверьтесь, что крючки на
панели крепления установлены должным образом
посредством раскачивания их влево и вправо
Погруженный Конец
в Воду
Течь
Воды
Течь
Воды
Течь
Воды
Трубопровод Дренажа Воды
Внутренняя дренажная труба должна быть
установлена с уклоном вниз для дренажа.
Избегайте ситуаций, которые могут привести к течи
воды.
Кабель
Межсоединения
Дренажный
шланг
J
НЕПРАВИЛЬНО
УСТАНОВКА НАРУЖНОГО БЛОКА
Прокладка трубопровода хладагента может быть
осуществлена несколькими способами (слева или
справа модуля), через выламывающиеся отверстия
на корпусе модуля (смотрите рисунок). Осторожно
согните трубы в необходимое положение для провода
через отверстия. Для провода справа или сзади,
подведите трубы и расположите их в необходимом
направлении (смотрите рисунок). Дренажный шланг
конденсации может быть зафиксирован к трубам.
J
НЕПРАВИЛЬНО
J
НЕПРАВИЛЬНО
j
ПРАВИЛЬНО
комнатный
Пренаж Воды
50mm
50mm
50mm
50мм 50мм
50мм
6-7
Русский
Проведение Трубопроводов
Не используйте грязную или поврежденную
трубную обвязку. Не снимайте пластиковое
покрытие, резиновые пробки и латунные гайки с
клапанов, штуцеров, труб и змеевиков до тех пор,
пока он не готов для соединения подачи газа или
жидкости в клапана или штуцеры.
Если требуется пайка, то удостоверьтесь, что газ азот
проходит через змеевик и соединения, где проводится
пайка. Это позволит избежать формирование копоти
на внутренней стороне медных труб.
Разрежьте соединительную трубу резаком.
Уберите заусенцы с краев среза трубы съемником.
Держите конец трубы вниз, чтобы предотвратить
попадание металлических частиц в трубу.
Вставьте штуцерные гайки, установленные на
соединяющие концы как внутреннего модуля, так и
внешнего модуля, на медные трубы.
Развальцуйте большей длины трубу развальцовочным
инструментом, как показано в таблице.
Край после развальцовви должен быть ровным и,
без трещин или царапин.
ПРОВЕДЕНИЕ ТРУБОПРОВОДОВ ХЛАДАГЕНТА
Комнатный Блок
Наружный Блок
Резка Медных Труб
! Осторожно
Только в воздухоохладителе WM301 в качестве расширительного устройства используется сопло, которое закреплено на
жидкостном трубопроводе во внутреннем блоке.
Соединение Трубопроводов К блокам
Отцентрируйте положение трубы и до конца
затяните штуцер усилием пальцев.
Затем, затяните штуцер динамометрическим
гаечным ключом до щелчка ключа.
L
H
Длина трубопроводов и подъем
Если трубопровод слишком длин, то мощность и
надежность функционирования модуля упадет. С
числом сгибов, сопротивление потока хладагента
увеличивается, понижая степень охлаждения. Это в
результате может привести к поломке компрессора.
Всегда пытайтесь делать трубопровод как можно
короче и следуйте рекомендациям в таблице внизу:
Замечание: Хладагент на внешнем модуле заправлен на
заводе-изготовителе из расчета длины
трубопровода до 7,62 м / 25 фут.
Трубопровод Комнатного Блока Штуцерная Гайка
Труба С Муфтой
Cоединения Муфтой
Ключ
Динамометрический
Гаечный Ключ
Модель 07/10 15 20 25 30
Макс. длина, м (фут), L 12 (39,4) 12 (39,4) 15 (49,2) 15 (49,2) 35 (114,8)
Макс. подъем, м (фут), H 5 (16,4) 5 (16,4) 8 (26,2) 8 (26,2) 15 (49,2)
Макс. число сгибов 10 10 10 10 10
Сечение трубы жидкости 1/4" 1/4" 1/4" 3/8" 3/8"
Сечение трубы газа 3/8" 1/2" 5/8" 5/8" 5/8"
Ø Трубы, D A (мм)
Дюйм мм Империал
Риджид
1/4" 6,35 1,3 0,7
3/8" 9,52 1,6 1,0
Размер Трубы мм / (дюйм) Крутящий Момент Hm / (Ft-lb)
12,7 (1/2) 55 (40,6)
15,88 (5/8) 65 (48,0)
6,35 (1/4) 18 (13,3)
9,53 (3,8) 42 (31,0)
1/2" 12,70 1,9 1,3
5/8" 15,88 2,2 1,7
Уберите Заусенцы
Обжимка
Медная Труба
6-8
L
COMP
N2
N1
N
T
COMP
L
N
S
R
COMP
N2
N1
L
COMP
N
ЭЛЕКТРИЧЕСКАЯ СХЕМА СОЕДИНЕНИЙ
Только Охлаждение
ВАЖНО: * Показатели, представленные в таблице, только для принятия во внимание. Они должны быть сравнены и выбраны
для того, чтобы они отвечали местным положениям/государственным стандартам. Они также зависят от типа
установки и сечения используемых проводников.
**
Соответствующий диапазон напряжений следует сверять с данными, указанными на табличке, прикрепленной к корпусу
аппарата. Указанное значение ETL соответствует только источнику питания с частотой 60 Гц.
COMP
N2
N1
L
COMP
R
S
N
L
N
L
WM301 VS SL30C
WM07 / 10 / 15 / 20 / 25 / 301 VS SL07 / 10 / 15 / 20 / 25 / 30B
5WM311 VS 5SL28C
Электроснабжение должно обеспечено с приборами
защиты (автоматический выключатель или
предохранитель) с двухполярной сепарационной системой
с минимальным расстоянием между клеммами 3 мм.
!
Терминал
Наружного Блока
Шнур Сети
Шнур Сети
Электроснабжение должно обеспечено с приборами
защиты (автоматический выключатель или
предохранитель) с двухполярной сепарационной
системой с минимальным расстоянием между
клеммами 3 мм.
!
Терминал
Комнатного Блока
Терминал
Наружного Блока
Шнур Сети
Электроснабжение должно обеспечено с
приборами защиты (автоматический выключатель
или предохранитель) с двухполярной
сепарационной системой с минимальным
расстоянием между клеммами 3 мм.
!
WM201 / 251 VS SL20 / 25B (3 Фáза)
Терминал
Комнатного Блока
Терминал
Наружного Блока
L
COMP
N2
N1
N
T
COMP
L
N
S
R
Электроснабжение должно обеспечено с приборами
защиты (автоматический выключатель или
предохранитель) с двухполярной сепарационной системой
с минимальным расстоянием между клеммами 3 мм.
!
Шнур Сети
Терминал
Комнатного Блока
Терминал
Наружного Блока
WM301 VS SL30C (3 Фáза)
Зажим Проводов
Кабель
Межсоединения
Все провода должны быть хорошо соединены.
Все электропроводка должна не приходить в
соприкосновение с хладагентом насоса или лопастей
двигателя.
Провода, соединяющие внутренний модуль и внешний
модуль, должны быть закреплены проводными
зажимами как показано на рисунке.
Cнур сети питания должен отвечать параметрам шнура
H05RN-F (245IEC57), который представляет собой
минимальные предъявляемые требования.
Модель Комнатный WM 071/ 101/ 151 WM201/ 251/ 301 5WM311 WM301 WM201/ 251/ 301 WM301
Наружный SL07/ 10/ 15B SL20/ 25/ 30B 5SL28C SL30C SL20/ 25/ 30B SL30C
Диапазон напряжения**
220B-240B/ 1Ф/ 50Гц + или 208B-230B/ 1Ф/ 60Гц + 380B-415B/ 3Ф/ 50Гц +N+
Сечение шнура сети* мм
2
1,5 2,5 2,5 4 1,5 1,5
Номер провода 333355
Сечение проводов межсоединения*
мм
2
1,5 2,5 2,5 2,5 1,5 1,5
Номер провода 333444
Рекомендуемый предохранитель
A 15 20 20 25 15 15
Терминал
Комнатного Блока
6-9
Русский
Обогревательный Насос
4WV
OF
COMP
N2
N1
L
4WV
OF
COMP
N
4WV
OF
COMP
N2
N1
L
4WV
A
OF
COMP
L
N
L
N
WM301R VS SL30CR
WM07 / 10 / 15 / 20 / 25 / 301R VS SL07 / 10 / 15 / 20 / 25 / 30BR
5WM301R VS 5SL28CR
Электроснабжение должно
обеспечено с приборами защиты
(автоматический выключатель или
предохранитель) с двухполярной
сепарационной системой с
минимальным расстоянием между
клеммами 3 мм.
!
Терминал
Комнатного Блока
Терминал
Наружного Блока
Шнур Сети
Соединяющий провод (длинои 8м)
внешето датчика радиатора,
подведенныи к внутреннему модулю
Электроснабжение должно обеспечено с приборами
защиты (автоматический выключатель или
предохранитель) с двухполярной сепарационной
системой с минимальным расстоянием между
клеммами 3 мм.
!
Терминал
Комнатного Блока
Терминал
Наружного Блока
Шнур Сети
Соединяющий провод (длинои 8м) внешето
датчика радиатора, подведенныи к
внутреннему модулю
4WV
OF
COMP
N2
N1
L
4WV
OF
COMP
L
N
S
R
N
T
4WV
OF
COMP
N2
N1
L
4WV
OF
COMP
L
N
A
S
R
N
T
WM301R VS SL30CR (3 Фáза)WM201 / 251R VS SL20 / 25BR (3 Фáза)
Соединяющий провод (длинои 8м) внешето
датчика радиатора, подведенныи к
внутреннему модулю
Соединяющий провод (длинои 8м)
внешето датчика радиатора,
подведенныи к внутреннему модулю
Электроснабжение должно обеспечено с приборами
защиты (автоматический выключатель или
предохранитель) с двухполярной сепарационной системой
с минимальным расстоянием между клеммами 3 мм.
!
Терминал
Комнатного Блока
Терминал
Наружного Блока
Шнур Сети
Терминал
Комнатного Блока
Терминал
Наружного Блока
Электроснабжение должно обеспечено с
приборами защиты (автоматический выключатель
или предохранитель) с двухполярной
сепарационной системой с минимальным
расстоянием между клеммами 3 мм.
!
Шнур Сети
ВАЖНО: * Показатели, представленные в таблице, только для принятия во внимание. Они должны быть сравнены и выбраны
для того, чтобы они отвечали местным положениям/государственным стандартам. Они также зависят от типа
установки и сечения используемых проводников.
**
Соответствующий диапазон напряжений следует сверять с данными, указанными на табличке, прикрепленной к корпусу
аппарата. Указанное значение ETL соответствует только источнику питания с частотой 60 Гц.
Модель Комнатный
WM 071/ 101/ 151 R
WM201/ 251/ 301 R 5WM301R WM301 R WM201/ 251/ 301 R WM301 R
Наружный SL07/ 10/ 15BR SL20/ 25/ 30BR 5SL28CR SL30CR SL20/ 25/ 30BR SL30CR
Диапазон напряжения**
220B-240B/ 1Ф/ 50Гц + или 208B-230B/ 1Ф/ 60Гц + 380B-415B/ 3Ф/ 50Гц +N+
Сечение шнура сети* мм
2
1,5 2,5 2,5 4 1,5 1,5
Номер провода 333355
Сечение проводов межсоединения*
мм
2
1,5 2,5 2,5 2,5 1,5 1,5
Номер провода 555664
Рекомендуемый предохранитель
A 15 20 20 25 15 15
6-10
ОTKAЧKA ВОЗДУХА И ЗАПРАВKA
Прочистите трубопровод и внутренний
модуль
За исключением внешнего модуля, который заправлен
хладагентом на заводе-изготовителе, внутренний
модуль и трубопроводы хладагента должны быть
продуты, поскольку воздух, содержащий влагу в
системе охлаждения, может вызвать сбои в работе
компрессора.
Снимите колпачки с клапана и входа технического
обслуживания.
Соедините центр нагнетательной коробки к
вакуумному насосу.
Cоедините нагнетательную коробку к 3-ходовому
клапану входа технического обслуживания.
Включите вакуумный насос. Проводите откачку в
течение примерно 30 минут. Время откачки зависит
от мощности вакуумного насоса. Удостоверьтесь,
что стрелка манометра нагнетательной коробки
установилась на –76 мм ртутного столба (0~76 мм
ртутного столба).
Осторожно
Если стрелка манометра коробки не достигает
0~76 мм ртутного столба, то проверьте отсутствие
утечки газа (используя течеискатель хладагента) на
щтуцерном соединении внутреннем и внешнего
модулей и ликвидируйте утечку, прежде чем
приступать к следующей операции.
Закройте клапан нагнетательной коробки и
выключите вакуумный насос.
На внешнем модуле, откройте клапан впуска
(3-ходовой) и клапан жидкости (2-ходовой) (против
часовой стрелки) при помощи ключа размером
4 мм для шестигранного винта.
СПЕЦИАЛЬНЫЕ МЕРЫ ПРЕДОСТОРОЖНОСТИ ПРИ ОБРАЩЕНИИ С R410A
R410A представляет собой почти азеотропную охлаждающую смесь гидрофторуглеродов (HFC), которая
является экологически безопасной. Этот хладагент обладает нулевым коэффициентом разрушения
озона (ODP=0), что соответствует требованиям Монреальского протокола. Он содержит негорючий и
низкотоксичный хладагент (A1 по классификации ARI). R410A является смесью R32 (50%) и R125 (50%).
В качестве смазки для компрессора R410A используется масло РОЕ, в отличие от R22, для которого
используется минеральное масло. Во время установки или выполнения ремонтных работ необходимо
принимать особые меры предосторожности, чтобы не допустить длительного контакта системы R410A
с влажным воздухом. Масло РОЕ, оставшееся в трубопроводах и компонентах, может абсорбировать
влагу из воздуха.
Хладагент R410A более подвержен негативному воздействию пыли и влаги по сравнению с R22, поэтому
не забудьте перед установкой временно закрыть концы трубопровода.
Запрещается добавлять компрессорное масло в систему.
Запрещается использовать какой-либо другой хладагент, кроме R410A.
Оборудование, предназначенное специально для R410A
i) Манометр и заправочный шланг
ii) Индикатор утечки газа
iii) Цилиндр хладагента / заправочный цилиндр
iv) Вакуумный насос с переходником
v) Развальцовочный инструмент
vi) Устройство для восстановления хладагента
!!
!!
! ОСТОРОЖНО
Хладагент R410A необходимо заправлять в жидком состоянии. Как правило, цилиндр R410A
оборудован гидравлическим затвором для удаления воды. В отсутствие гидравлического затвора
цилиндр следует перевернуть для удаления жидкого R410A из клапана.
Не рекомендуется дозаправлять систему при ликвидации утечки, так как это приведет к снижению
производительности блока. Необходимо полностью откачать хладагент из системы, после чего
заправить ее свежим хладагентом R410A в количестве, указанном в технических условиях.
Не прикасайтесь к компрессору или трубопроводу хладагента во время работы охлаждающего
аппарата. При необходимости надевайте защитные перчатки.
Дозаправка
Хладагент заправлен заводом-изготовителем на
внешнем модуле. Если длина трубопроводов
меньше, чем 7,62 м (25 фут), то в дозаправке после
откачки воздуха нет необходимости. Если длина
трубопроводов больше, чем 7,62 м (25 фут), то
используйте клапан дозаправки, как показано в
таблице внизу.
Вход технического
обслуживания
3 ходовой клапан
внешнего модуля
Штуцерная
гайка
Трубопровод
хладoгента
Шестигранный
гаечый ключ
Комнатного блока
Сторона
жидкости
Клапан
выпуска
Откройте
Вакуумный
насос
Закройте
Высок
Наружного блока
Сторона
газа
Клапан
впуска
Закройте
Низк
Закройте
6-11
Русский
Датчик ИК сигналов
Когда пульт дистанционного управления передает
инфракрасные сигналы, датчик сигналов на
внутреннем модуле произведет сигнал <бип> для
подтверждения получения сигнала.
ПОКАЗАНИЯ ИНДИКАТОРОВ
Модуль охлаждения
В таблице представлены показания индикаторов
СИД для модуля кондиционера при нормальных
условиях функционирования и при сбое.
Показания индикаторов СИД представлены на
нижней правой стороне модуля кондиционера.
Показания индикаторов СИД : Нормальные условия функционирования и сбой модуля охлаждения
Показания индикаторов СИД модуля охлаждения
Сеть ВКЛ
Таймер
Режим сна
Режим
осушения
Показания индикаторов сид
ИК Датчик
Операция заправки
Операция должна проводиться при помощи газового цилиндра
и обязательно точным дозатором. Дозаправка во внешний
модуль проводится с помощью клапана впуска через вход
технического обслуживания.
Снимите колпачок входа технического обслуживания.
Соедините сторону низкого давления нагнетательной
коробки к входу технического обслуживания,
отцентрируйте для подсоединения к резервуару цилиндра
и закройте сторону высокого давления нагнетательной
коробки. Прочистите от воздуха вспомогательный шланг.
Включите модуль кондиционера.
Модель 10 м/32,8 фут 12 м/39,4 фут 15 м/49,2 фут
071 / 101 / 151 35 65 -
201 35 65 110
251 / 301 90 165 280
071R / 101R /151R 50 90 -
201R 60 110 185
251R / 301R 120 220 370
Модель 10 м/32,8 фут 12 м/39,4 фут 15 м/49,2 фут
311 80 150 255
301R 110 200 335
Дозаправка в гр. (R410A)
Откройте газовый цилиндр и заправочный клапан
низкого давления.
Когда требуемое количество хладагента заправлено в
модуль, то закройте сторону низкого давления и клапан
газового цилиндра.
Отсоедините вспомогательный шланг от входа
технического обслуживания. Установите колпачок входа
технического обслуживания обратно на его место.
Дозаправка в гр. (R22)
ВКЛ или ВЫКЛ
ВКЛ
Мигание
Показания Функцонирования
Действия
Таймер включен.
Режим сна включен.
Режим осушения.
Очистите фильтр и переключите
Предотвращение образования льда.
на высокую скорость вращения
вентилятора.
Обращайтесь к Вашему дилеру.
Обращайтесь к Вашему дилеру.
Обращайтесь к Вашему дилеру.
Сеть
Осушение
Таймер Сна
и Неисправностей
Контакт комнатного датчика воздуха
отсутствует/короткое замыкание.
Контакт комнатного датчика змеевика
отсутствует/короткое замыкание.
Проблема с контактами датчика,
перегрузка компрессора вы звали
его автовыключение или утечка
газа.
Непрерывно
раз в 2 сек.
дважды в 2 сек.
трижды в 2 сек.
Комнатного блока
Сторона
жидкости
Наружного блока
Клапан
выпуска
Сторона
газа
Клапан
впуска
Закройте
Откройте
Закройте
Высок
Низк
Проверте
клапан
Закройте
6-12
Нормальное функционирование/
Действия
Неисправность
ВКЛ или ВЫКЛ
ВКЛ
Мигание
Показания индикаторов СИД : Нормальные условия функционирования и неисправности
модуля обогревательного насоса
Режим охлаждения.
Режим осушения.
Режим вентиляции.
Режим Обогрев.
Авто режим в операции обогрева.
Авто режим в операции охлаждения.
Операция оттаивания.
Защита компрессора от перегрузки.
Обращайтесь к Вашему дилеру.
Обращайтесь к Вашему дилеру.
Обращайтесь к Вашему дилеру.
Обращайтесь к Вашему дилеру.
Если система в режиме охлаждения или обогрева (с выключенной функцией сна),
возможна проблема с контактами датчика, перегрузка компрессора вы звала его
автовыключение или утечка газа.
Осушение Осуш Холод
Обогрев Сна
Модуль обогревательного насоса
В таблице представлены показания индикаторов СИД
для модуля кондиционера при нормальных условиях
функционирования и при сбое.
Показания индикаторов СИД представлены на правой
нижней стороне модуля кондиционера.
Модуль обогревательного насоса оборудован датчиком
режима “авто” для обеспечения оптимальной
температуры в комнате автоматическим переключением
либо в режим “холодно”, либо в “обогрев”, исходя из
установленной температуры пользователем.
Показания индикаторов СИД для модуля
обогревательного насоса
Режим
охлаждения
Режим
осушения
Обогрев /
Режим вентиляции
(красный / зеленый)
Режим сна
Контакт комнатного датчика воздуха
отсутствует/короткое замыкание.
Контакт наружного датчика змеевика
отсутствует/короткое замыкание
Контакт комнатного датчика
змеевика отсутствует/короткое
6-13
Русский
Охлаждение
Осушение
Горизонтально
25°C/77°F
ОПЕРАЦИЯ МОДУЛЯ КОНДИЦИОНЕРА
Режим осушения
При повышенной влажности воздуха, модуль
может работать в режиме осушения. Нажмите
кнопку <РЕЖИМ> и <СУШКА>.
При комнатной температуре на 2°C/35,6°F выше
установленной температуры, кондиционер будет
функционировать в режиме охлаждения до те
пор, пока он не достигнет разницу в 2°C/35,6°F
от установленной температуры прежде, чем он
переключится в режим осушения
Если комнатная температура в пределах разницы
в 2°C/35,6°F по сравнению с установленной
температурой, то модуль сразу же начнет
функционирование в режиме осушения.
Модуль будет функционировать при скорости
НИЗК в режиме осушения.
Режим обогрева (только для
обогревательного насоса)
При включении модуля с холодным стартом или
циклом оттаивания внутренний вентилятор
начнет работать только после того, как радиатор
достигнет желаемой температуры.
При достижении установленной температуры,
внутренний вентилятор начнет работать до тех
пор, пока радиатор не будет в состоянии
обеспечить дополнительное количество тепла.
Управление горизонтальным потоком
воздуха
Для более эффективной циркуляции воздуха, Вы
можете вручную регулировать решетку выпуска
воздуха влево или вправо.
В течение работы в режиме охлаждения или
режиме осушения, не направляйте жалюзи
выпуска воздуха вниз на слишком долгое время.
Если работа будет продолжаться в таких
условиях, то на жалюзи может появиться
конденсат, что вызовет к капанью.
Сохранение тепла (только для
обогревательного насоса)
При отключении компрессора вентилятора
внутреннего блока может быть переключен на
(i) ВКЛ(по умолчанию)
(ii) ВЫКЛ или
(iii) Периодическое включение и выключение
посредством установки ползункового
переключателя так, как показано на рисунке.
Переключатель находится на передней панели
(рядом с включателем ВКЛ/ВЫКЛ).
ПРИМЕЧАНИЕ : Eсли выбрана эта опция,
необходимо выключить и
включить электропитание
блока, чтобы активировать
данную функцию.
Защита от перегрева (только для
обогревательного насоса)
В случае, если внутренняя и/или внешняя
температура высока, или фильтр загрязнен и
забит, то хладагент может быть перегрет.
Компрессор выключится при достижении
температуры конденсата 62°C
/143,6°F.
Предотвращение обледенения
При загрязнении фильтра, температура испарения
уменьшится и в конце концов это может вызвать
обледенении.
Индикатор СИД замигает, обозначая
загрязненность фильтра. Если температура
испарения достигает -2°C/28,4°F, то модуль
автоматически отключится и начнется
оттаивание.
Скорость вентилятора и номинальная
степень охлаждения
Номинальная степень охлаждения
обеспечивается при максимальной скорости
вентилятора.
Номинальная степень охлаждения ниже при
режиме модуля, работающего при скорости
вентилятора СРЕД и НИЗК.
Включатель ВКЛ/ВЫКЛ
HOT KEEP
OFF
INTERVAL
ON
6-14
Температура Ts °C/°F Th °C/°F
Минимальная комнатная
температура
Максимальная комнатная
температура
Минимальная наружная
температура
Максимальная наружная
температура
! Внимание
Отключите сетевое питание перед обслуживанием блока кондиционера.
НЕ вытаскивайте сетевой шнур, когда сеть ВКЛЮЧЕНА. Это может стать причиной резкой нагрузки
тока, что может привести к возгоранию.
УСЛОВИЯ СТАНДАРТНОЙ РАБОТЫ
Обогревательный насос
Только охлаждение
Ts: Шарик сухого термометра.
Th: Шарик смоченного термометра.
Температура Ts °C/°F Th °C/°F
Минимальная комнатная
19,4 / 66,9 13,9 / 57,0
температура
Максимальная комнатная
26,7 / 80,1 19,4 / 66,9
температура
Минимальная наружная
19,4 / 66,9 13,9 / 57,0
температура
Максимальная наружная
46 / 114,8 24 / 75,2
температура
10 / 50
26,7/80,1
-8 / 17,6
24 / 75,2
-
-
-9 / 15,8
18 / 64,4
Электростатические Воздухоочистительные И Дезодорирующие Фильтрируюощие
Средства Двойного Действия И Фильтрная Рамка
Действие 1-
Электростатический
Воздухоочистительный Фильтр
Удаляет микроскопическую пыль, дым и мелкие
невидимые частицы для обеспечения чистоты комнатного
воздуха при помощи заправленного электростатического
полипропиленового фильтра.
ЭЛЕКТРОСТАТИЧЕСКИЙ ФИЛЬТР ПРИ НАЛИЧИИ
Действие2-
Дезодорирующий Фильтр
Удаляет неприятные запахи в воздухе и сохраняет
комнатный воздух свежим С с помощью фильтра с
активированном углем.
КАК УСТАНОВИ ТЬ
ОТКРОЙТЕ
РЕШЕТКУ
ПЕРЕДНЕЙ
РАМКИ.
ВЫТАЩИТЕ
ОСНОВНЫЕ
ФИЛЬТРЫ.
ВСТАВЬТЕ
ЭЛЕКТРОСТАТИЧЕСКИЕ И
ДЕЗОДОРИРУЮЩИЕ ФИЛЬТРЫ
ДВОЙНОГО ДЕЙСТВИЯ В ПАЗ.
ВЫТАЩИТЕ ОСНОВНЫЕ
ФИЛЬТРЫ.
6-15
Русский
Аогда Бодуль Ве жассчитан Ва Ћспользование В кечение Длительного Времени
Функционирование
модуля в течение 2
часов со следующей
установкой.
Режим работы: холодно
Температура: 30
°
C/86
°F
Вытащите вилку.
Если используется
независимый подвод
питания для модуля,
выключите питание.
Выньте батареи из пульта
дистанционного
управления.
СЕРВИС И ТЕХНИЧЕСКОЕ ОБСЛУЖИВАНИЕ
! Осторожно
Процедуры Технического Обслуживания
1. Очистите от пыли фильтр пылесосом или вымойте его в теплой
воде (ниже 40°С/104°F ) нейтральным моющим средством.
2. Хорошо прополоскайте и высушите фильтр перед установкой
его обратно в блок.
3. Не используйте бензиновые, легкоиспаряющиеся вещества
или химические средства для очистки фильтра.
1. Очистите от грязи или пыли решетку или панель, вытирая
при помощи мягкой ткани смоченной в теплой воде (ниже 40°С/
104
°F
) нейтральным моющим средством.
2. Не используйте бензиновые, легкоиспаряющиеся вещества
или химические средства для очистки комнатного блока.
Время
Не реже 2 раз в
неделю.
Чаще при
необходимости.
Не реже 2 раз в
неделю.
Чаще при
необходимости.
Узлы
Обслуживания
Комнатный
воздушный
фильтр
Комнатный
блок
Не устанавливайте обогревательные приборы в непосредственной близости от кондиционеру.
Это может привести к расплавлению пластиковой панели или ее деформации в результате
высокой температуры.
! Осторожно
1. Электростатический и дезодорирующий
фильтры должны быть заменены либо раз в
каждые 6 месяцев, либо при изменении цвета
фильтров в коричневатый, что наступит
первым.
2. Использованные загрязненные фильтры
должны быть выброшены и не применяться
вновь, даже после их очистки и мойки.
3. Фильтр имеется в продаже и его можно
приобрести у дилера Вашего кондиционера.
4. Используйте новый фильтр сразу же после того, как
он был извлечен из запечатанной упаковки. Не
открывайте преждевременно новый фильтр до его
непосредственного применения, поскольку это
может уменьшить его дезодорирующее действие.
! Внимание
Отключите сетевое питание перед обслуживанием блока кондиционера.
НЕ вытаскивайте сетевой шнур, когда сеть ВКЛЮЧЕНА. Это может стать причиной резкой нагрузки
тока, что может привести к возгоранию.
6-16
При обнаружении сбоев в работе кондиционера, немедленно выключите питание сети
блока. Проверьте нижеследующие признаки неисправностей, причины и советы
простейших мер по устранению.
МЕРЫ ПО УСТРАНЕНИЮ
Причины/действия
- Защита от частого включения. Подождите от 3 до 4
минут, чтобы компрессор включился.
- Отсутствие сетевого питания или требуется замена
предохранителя.
- Вилка не вставлена.
- Существует вероятность того, что таймер задержки
установлен неправильно.
- Если неисправность не устранена после всех этих
проверок, пожалуйста, свяжитесь с персоналом,
установившего кондиционер.
- Воздушный фильтр загрязнен.
- Двери или окна открыты.
- Забился впуск и выпуск воздуха.
- Установленная температура недостаточно высока.
- Неприятный запах может быть вызван сигаретами,
частицами дыма, парфюмерии и т.п., которые могли
осесть на змеевике.
- Это вызвано влагой в воздухе после продолжительного
времени функционирования.
- Установленная температура слишком низка, увеличьте
установленную температуру и установите скорость
вентилятора на высокую.
- Выключите блок и обращайтесь к дилеру.
- Попадание хладагента на испарительный змеевик.
Неисправность
1.
Компрессор не начинает функционирование по
прошествии 3 минут после включения кондиционера.
2. Кондиционер не работает.
3. Очень незначительный поток воздуха.
4. При выпуске воздуха имеется неприятный запах.
5. Конденсат на передней решетке комнатного блока.
6. Вода выливается из кондиционера.
7. Шипящий звук воздуха из кондиционера во время
работы.
Если неисправность неустранима, пожалуйста, обращайтесь к Вашему местному дилеру /
специалисту.
OYL MANUFACTURING COMPANY SDN. BHD.
JALAN PENGAPIT 15/19, P.O. BOX 7072, 40702 SHAH ALAM, SELANGOR DARUL EHSAN, MALAYSIA.
In the event that there is any conflict in the interpretation of this manual and any translation of the same in any language,
the English version of this manual shall prevail.
The manufacturer reserves the right to revise any of the specification and design contain herein at any time without prior
notification.
En cas de désaccord sur l’interprétation de ce manuel ou une de ses traductions, la version anglaise fera autorité.
Le fabriquant se réserve le droit de modifier à tout moment et sans préavis la conception et les caractéristiques techniques
des appareils présentés dans ce manuel.
Im Falle einer widersprüchlichen Auslegung der vorliegenden Anleitung bzw. einer ihrer Übersetzungen gilt die Ausführung
in Englisch.
Änderungen von Design und technischen Merkmalen der in dieser Anleitung beschriebenen Geräte bleiben dem Hersteller
jederzeit vorbehalten.
Nel caso ci fossero conflitti nell’interpretazione di questo manuale o delle sue stesse traduzioni in altre lingue, la versione
in lingua inglese prevale.
Il fabbricante mantiene il diritto di cambiare qualsiasi specificazione e disegno contenuti qui senza precedente notifica.
En caso de conflicto en la interpretación de este manual, y en su traducción a cualquier idioma, prevalecerá la versión
inglesa.
El fabricante se reserva el derecho a modificar cualquiera de las especificaciones y diseños contenidos en el presente
manual en cualquier momento y sin notificación previa.
В случае противоречия перевода данного руководства с другими переводами одного и того же текста,
английский вариант рассматривается как приоритетный.
Завод-изготовитель оставляет за собой право изменять характеристики и конструкцию в любое время
без предварительного уведомления.
IM-WM1-0302-ACSON :
i
D
E
A
B
C
Q
N
E
15 (0.6)
39 (1.5)
A
M
P
P
840 (33.1)
D
15 (0.6)
39 (1.5)
5 (0.2)
C
20 (0.8)
20 (0.8)
2.5 (0.1)
F
B
C
5 (0.2)
160 (6.3)
H
G
141 (5.6)
K
J
(2.6)
65
L
20 (0.8)
R
E
280.0 (11.0)
311.0 (12.2)
347.0 (13.7)
A
B
C
D
785.0 (30.9)
WM071 / 101 / 151 / 1R
WM201 / 201R
WM 251 / 251R / 301 / 301R
1050.0 (41.3)
1200.0 (44.1)
297.0 (11.7)
320.0 (12.6)
360.0 (14.2)
174.0 (6.85)
190.0 (7.5)
200.0 (7.9)
595.0 (23.4)
730.0 (28.7)
730.0 (28.7)
(SL-B Series)
ABCDEFGHJKLMNPQR
07B / 07BR
7404942702662334744755651669234831812948268,5
10B / 10BR
(29.1)(19.4)(10.6)(10.5)(9.2)(18.7)(1.9)(2.2)(2.6)(6.5)(3.6)(13.7)(12.5)(5.1)(19.0)(2.7)
15B / 15BR
20B / 20BR
84064633029730962641857517710640837812459278,5
25B / 25BR
(33.1)(25.4)(13.0)(11.7)(12.2)(24.6)(1.6)(3.3)(3.0)(7.0)(4.2)(16.1)(14.9)(4.9)(23.3) (3.1)
30B / 30BR
28C / 28CR
855750328303309730491167518798392362126603164
(33.7)(29.5)(12.9)(11.9)(12.2)(28.7)(1.9)(4.6)(3.0)(7.4)(3.9)(15.4)(14.3)(5.0)(23.7)(6.5)
!
(SL30C)
40 (1.57)
400 (15.75)
320 (12.60)
25 (0.78)
448 (17.64)
141.5 (5.57)
40 (1.57)
141.5 (5.57)
1030 (40.55)
850 (33.46)
50 (1.97)
85 (3.35)
ABCDEFGHIJKLMNO
071 / 1R600 (23.6)475 (18.7)245 (9.6)418 (16.4)177 (6.9)35 (1.3)93 (3.6)81 (3.1)83 (3.2)55 (2.2)398 (15.6)101 (3.9)97 (3.8)17 (0.6)22 (0.8)
10 / 15 C /CR700 (27.5)521 (20.5)250 (9.8)485 (19.1)175 (6.8)36 (1.4)95 (3.7)93 (3.6)86 (3.3)68 (2.6)441 (17.3)130 (5.1)111 (4.3)15 (0.5)18 (0.7)
(1.2)
) (SL071 & 10/15 C/CR
ii
20 (0.79)
20 (0.79)
WOÐdF«WOÐdF«
WOÐdF«WOÐdF«
WOÐdF«
±
Part No.: A08019025521
IM-WM1-0302(2)-Acson
(R22)
WM301AWM301
SL30CALC30C
SL30BALC30B
(R410A)
5WM311A5WM311
5SL28CA5LC28C
(R22)
WM301RAWM301R
SL30CRALC30CR
SL30BRALC30BR
(R410A)
5WM301RA5WM301R
5SL28CRA5LC28CR
i-ii
R410A
!
.
OFF
!
WOÐdF«WOÐdF«
WOÐdF«WOÐdF«
WOÐdF«
ON/OFF
° °
A
B
C
D
ABCD
3001000300500
(11.8)(39.4)(11.8)(19.7)
¥
!
WM301/SL30BWM301/SL30C
A
WOÐdF«WOÐdF«
WOÐdF«WOÐdF«
WOÐdF«
µ
C
B
J
J
J
j
50mm
50mm
50mm
WOÐdF«WOÐdF«
WOÐdF«WOÐdF«
WOÐdF«
65 (48.0)
ftL
ftH
35(114.8) 15(49.2) 15(49.2) 12(39.4) 12(39.4)
15(49.2) 8(26.2) 8(26.2) 5(16.4) 5(16.4)
10 10 10 10 10
3/8" 3/8" 1/4" 1/4" 1/4"
A
1/4"6.351.30.7
3/8"9.521.61.0
1.3 1.9 12.70 1/2"
1.7 2.2 15.88 5/8"
!
WM301
(Nm)
ft
L
H
55 (40.6) 12.7 (1/2)
30 25 20 15 07/10
5/8" 5/8" 5/8" 1/2" 3/8"
42 (31.0)
9.53 (3/8)
18 (13.3)
6.35 (1/4)
15.88 (5/8)
WM 071/ 101/ 151WM201/ 251/ 3015WM311WM301WM201/ 251/ 301WM301
SL07/ 10/ 15BSL20/ 25/ 30B5SL28CSL30CSL20/ 25/ 30BSL30C
**
208V-230V/ 1Ph/ 60Hz +
«Ë
220V-240V/ 1Ph/ 50Hz +380V-415V/ 3Ph/ 50Hz +N+
*
1.52.52.541.51.5
333355
*
1.52.52.52.51.51.5
333444
A152020251515
*
**ETL
H05RN-F(245IEC57)
L
COMP
N2
N1
N
T
COMP
L
N
S
R
L
COMP
N2
N1
N
T
COMP
L
N
S
R
WM301 VS SL30C ( )
WM201 / 251 VS SL20 / 25B ( )
COMP
N2
N1
L
COMP
N
WM07 / 10 / 15 / 20 / 25 / 301 VS SL07 / 10 / 15 / 20 / 25 / 30B
5WM311 VS 5SL28C
COMP
N2
N1
L
COMP
R
S
N
L
N
L
WM301 VS SL30C
!
!
!
!
WOÐdF«WOÐdF«
WOÐdF«WOÐdF«
WOÐdF«
π
WM 071/ 101/ 151 RWM201/ 251/ 301 R5WM301RWM301 RWM201/ 251/ 301 RWM301 R
SL07/ 10/ 15BRSL20/ 25/ 30BR5SL28CRSL30CRSL20/ 25/ 30BRSL30CR
**
208V-230V/ 1Ph/ 60Hz +
«Ë
220V-240V/ 1Ph/ 50Hz +380V-415V/ 3Ph/ 50Hz +N+
*
1.52.52.541.51.5
333355
*
1.52.52.52.51.51.5
555664
A152020251515
!
4WV
OF
COMP
N2
N1
L
4WV
OF
COMP
N
WM07 / 10 / 15 / 20 / 25 / 301R VS SL07 / 10 / 15 / 20 / 25 / 30BR
5WM301R VS 5SL28CR
4WV
OF
COMP
N2
N1
L
4WV
A
OF
COMP
L
N
L
N
4WV
OF
COMP
N2
N1
L
4WV
OF
COMP
L
N
S
R
N
T
4WV
OF
COMP
N2
N1
L
4WV
OF
COMP
L
N
A
S
R
N
T
WM301R VS SL30CR
!
WM201 / 251R VS SL20 / 25BR ( )
WM301R VS SL30CR ( )
!
!
∫ ÂU¼∫ ÂU¼
∫ ÂU¼∫ ÂU¼
∫ ÂU¼
*
**ETL
±∞
R22
≥∞
Hg~Hg
~Hg
R410A
R410A(HFC)
(
ODP=0)
A1ARIR410AR32R125
POER410AR22
R410A
POE
R410AR22
R410A
R410A
!
R410AR410A
R410A
R410A
ALLEN
WOÐdF«WOÐdF«
WOÐdF«WOÐdF«
WOÐdF«
±±
(R410A)
(R22)
10 m/32.8 ft12 m/39.4 ft15 m/49.2 ft
071 / 101 / 1513565-
2013565110
251 / 30190165280
071R / 101R /151R5090-
201R60110185
251R / 301R120220370
10 m/32.8 ft12 m/39.4 ft15 m/49.2 ft
31180150255
301R110200335
LED
LED
IR
IR
><
LED
ON
ON OFF
ON
LED
LED
±≤
LED
LED
LED
LED
ON OFF
ON
WOÐdF«WOÐdF«
WOÐdF«WOÐdF«
WOÐdF«
±≥
<MODE><DRY>
°°
°°
°°
LOW
(i)
ON
(ii)
OFF
(iii)
ON/OFF
°°
LED
°
MEDIUMLOW
25°C/77°F
ON/OFF
HOT KEEP
OFF
INTERVAL
ON
±¥
Ts
Th
!
ON
Ts °C/°FTh °C/°F
10 / 50-
26.7 / 80.1-
-8 / 17.6-9 / 15.8
24 / 75.218 / 64.4
Ts °C/°FTh °C/°F
19.4 / 66.913.9 / 57.0
26.7 / 80.119.4 / 66.9
19.4 / 66.913.9 / 57.0
46 / 114.824 / 75.2
WOÐdF«WOÐdF«
WOÐdF«WOÐdF«
WOÐdF«
±µ
°°
°°
.
.
!
°°
!
!
ON
±∂
-
-
-.
-
-
-
-
-
-
-
-
-
-
-
OYL MANUFACTURING COMPANY SDN. BHD.
JALAN PENGAPIT 15/19, P.O. BOX 7072, 40702 SHAH ALAM, SELANGOR DARUL EHSAN, MALAYSIA.
WM« ÊuJð ¨X½U WG W¹QÐ UNH½ WLłd²« w ·ö²š« Í«Ë VO²J« «c¼ dOHð w ÷—UFð Í« ÀbŠ «–«
Æ…bzU« w¼ W¹eOKJ½ô«
Æo³ —UFý≈ ÊËœ s XË Í« w UM¼ …œułu UH«u W¹«Ë rOLB²« q¹bFð o×Ð lMB*« kH²×¹

Transcripción de documentos

INSTALLATION MANUAL Model: IM-WM1-0302-ACSON WALL MOUNTED SPLIT TYPE AIR CONDITIONER WALL MOUNTED OUTLINE AND DIMENSIONS Indoor Unit A All dimensions are in mm / (in) C D TOP VIEW B E FRONT VIEW INSTALLATION PLATE SIDE VIEW Dimension WM071 / 101 / 151 / 1R WM201 / 201R WM 251 / 251R / 301 / 311 / 301R A 785,0 (30,9) 1050,0 (41,3) 1200,0 (44,1) B 297,0 (11,7) 320,0 (12,6) 360,0 (14,2) C 174,0 (6,85) 190,0 (7,5) 200,0 (7,9) D 595,0 (23,4) 730,0 (28,7) 730,0 (28,7) E 280,0 (11,0) 311,0 (12,2) 347,0 (13,7) A All dimensions are in mm / (in) N 5 (0,2) C 39 (1,5) 15 (0,6) M R 15 (0,6) 39 (1,5) Outdoor Unit (SL-Series) 5 (0,2) P Q P C 840 (33,1) 160 (6,3) H F Dimension 07B / 07BR 10B / 10BR 15B / 15BR 20B / 20BR 25B / 25BR 30B / 30BR A B C D E F 740 494 270 266 233 (29,1) (19,4) (10,6) (10,5) (9,2) 28C / 28CR G H L J K L K 20 (0,8) 20 (0,8) 20 (0,8) (2,6) 65 J E B 141 (5,6) 2,5 (0,1) G D M N P Q R 474 47 (18,7) (1,9) 55 65 (2,2) (2,6) 166 (6,5) 92 (3,6) 348 318 129 482 68,5 (13,7) (12,5) (5,1) (19,0) (2,7) 840 646 330 297 309 626 41 (33,1) (25,4) (13,0) (11,7) (12,2) (24,6) (1,6) 85 75 (3,3) (3,0) 177 (7,0) 106 (4,2) 408 378 124 592 78,5 (16,1) (14,9) (4,9) (23,3) ( 3 , 1 ) 855 750 328 303 309 730 49 (33,7) (29,5) (12,9) (11,9) (12,2) (28,7) (1,9) 116 75 (4,6) (3,0) 187 (7,4) 98 (3,9) 392 362 126 603 164 (15,4) (14,3) (5,0) (23,7) (6,5) Outdoor Unit (SL071 & 10/15 C/CR) All dimensions are in mm / (in) Dimension 071 / 1R A B C D E F G H I J K L M N O 600 (23,6) 475 (18,7) 245 (9,6) 418 (16,4) 177 (6,9) 35 (1,3) 93 (3,6) 81 (3,1) 83 (3,2) 55 (2,2) 398 (15,6) 101 (3,9) 97 (3,8) 17 (0,6) 22 (0,8) 10 / 15 C /CR 700 (27,5) 521 (20,5) 250 (9,8) 485 (19,1) 175 (6,8) 36 (1,4) 95 (3,7) 93 (3,6) 86 (3,3) 68 (2,6) 441 (17,3) 130 (5,1) 111 (4,3) 15 (0,5) 18 (0,7) i 141,5 (5,57) 448 (17,64) 141,5 (5,57) 20 (0,79) Outdoor Unit (SL30C) 850 (33,46) 20 (0,79) 1030 (40,55) 40 (1,57) 400 (15,75) 320 (12,60) 40 (1,57) 50 (1,97) 25 (0,98) 85 (3,35) ! Caution Sharp edges and coil surfaces are potential locations which may cause injury hazards. Avoid from being in contact with these places. ! Avertissement risque de blessure. Mieux vaut éviter le contact avec ces endroits. Les bords coupants et les surfaces du refroidisseur tuulaire présentent un ! Vorsicht Scharfe Kanten und Wärmetauscherflächen stellen eine Gefahrenquelle dar. Jeglicher Kontakt mit diesen Stellen ist zu vermeiden. ! Cautela Per preservarsi da eventuali ferite, evitare di toccare gli spigoli afilati e la superficie dei serpentini. ! Cuidado Los Bordes afilados y la superficie del serpentín pueden producir lesiones. Evite tocarlos. ! Осторожно Острые края и поверхности змеевиков являются потенциальными местами нанесения травм. Остерегайтесь контакта с этими местами. NOTICE This product is subjected to Waste of Electrical and Electronic Equipment Regulations (WEEE Regulations). The waste product shall be separately collected by specific collection and treatment centre. Please refer to local authorithy for these centres. This is only applicable to European Union countries. Ce produit est soumis à la réglementation concernant les déchets des équipements électriques et électroniques (ré r é ê é séparé r ment par un centre de collecte é é ître ces centres. Ceci éenne. Gerää ä ätes getrennt vom Hausmüll bei Ihrer örtlichen Mülldeponie bzw. Ihrem örtlichen äändiges Abfall-Amt. Dieser Hinweis gilt nur fü f r Länder ä der Europäischen Union. Questo prodotto è soggetto alle disposizioni RAEE (Rifiuti di apparecchiature elettriche ed elettroniche). à à locali. Questa disposizione è valida solamente i paesi dell’U.E. ñ éctrico y Electrónico en materia de í ífico á de colecció solamente aplicable a los países de la Unión Europea. данного по ii и . правила , Европейского ii . Эти . English INSTALLATION MANUAL This manual provides the procedures of installation to ensure a safe and good standard of operation for the air conditioner unit. Special adjustment may be necessary to suit local requirements. Before using your air conditioner, please read this instruction manual carefully and keep it for future reference. WALL MOUNTED SPLIT TYPE AIR CONDITIONER MODEL COOLING UNIT (R22) HEAT PUMP UNIT (R22) Reference Model Model Reference Model Model WM301 SL30C SL30B AWM301 ALC30C ALC30B WM301R SL30CR SL30BR AWM301R ALC30CR ALC30BR COOLING UNIT (R410A) HEAT PUMP UNIT (R410A) Reference Model Model Reference Model Model 5WM311 5SL28C A5WM311 A5LC28C 5WM301R 5SL28CR AWM301R A5LC28CR IM-WM1-0302(2)-Acson Part No.: A08019025521 1-1 CONTENTS - Outline and Dimensions - Safety Precautions - Installation Diagram - Installation of the Outdoor Unit - Installation of the Orifice Pipe - Installation of the Indoor Unit - Refrigerant Piping - Electrical Wiring Connection page i-ii page 2 page 3 page 3 page 4 page 6 page 7 page 8 - Special Precautions When Dealing With R410A Unit - Vacuuming and Charging - Indicator Lights - Air Conditioner Unit Operation - Standard Operating Conditions - Electrostatic Filter - Service and Maintenance - Troubleshooting page 10 page 10 page 11 page 13 page 14 page 14 page 15 page 16 SAFETY PRECAUTIONS Before installing the air conditioner unit, please read the following safety precautions carefully. ! Warning • Installation and maintenance should be performed by qualified persons who are familiar with local code and regulation, and experienced with this type of appliance. • All field wiring must be installed in accordance with the national wiring regulation. • Ensure that the rated voltage of the unit corresponds to that of the name plate before commencing wiring work according to the wiring diagram. • The unit must be GROUNDED to prevent possible hazard due to insulation failure. • All electrical wiring must not touch the refrigerant piping, compressor or any moving parts of the fan motors. • Confirm that the unit has been switched OFF before installing or servicing the unit. IMPORTANT DO NOT INSTALL OR USE THE AIR CONDITIONER UNIT IN A LAUNDRY ROOM. ! Caution Please take note of the following important points when installing. • Do not install the unit where leakage of flammable gas may occur. If gas leaks and accumulates at the surrounding of the unit, it may cause fire ignition. • Ensure that the drainage piping is connected properly. If the drainage piping is not connected properly, it may cause water leakage which will dampen the furniture. • Do not overcharge the unit. This unit is factory pre-charged. Overcharge will cause over-current or damage to the compressor. • Ensure that the units panel is closed after service or installation. Unsecured panels will cause the unit to operate noisily. 1-2 Indoor Unit Air Filters Front Frame Back Housing Air Intake Grille On/Off Switch Drain Hose Indicator Lights Air Discharge Louver Signal Receiver Air Discharge Grille Air Intake Refrigerant Piping Air Intake Air Discharge Nozzle Outdoor Unit B Obstacle A Discharge Air Obstacle The outdoor unit must be installed in such a way, so as to prevent short circuit of the hot discharged air or obstruction to the smooth air flow. Please follow the installation clearance shown in the figure. Select the coolest possible place where intake air temperature is not greater than the outside air temperature (maximum 45°C/113°F). Return Air INSTALLATION OF THE OUTDOOR UNIT C D 300 (11.8) 1000 (39.4) 300 (11.8) 500 (19.7) Note: If there is any obstacle higher than 2m, or if there is any obstruction at the upper part of the unit, please allow more space than the figure indicated in the above table. 1-3 C D Obstacle B Service Access A Obstacle Dimension Minimum Distance, mm (in) Return Air Installation clearance English INSTALLATION DIAGRAM INSTALLATION OF ORIFICE PIPE Orifice Pipe 2 3 4 1 Outdoor Unit Indoor 1 Orifice 3 Flare nut 3/8" (Female) 2 Pipe, connecting 4 Flare joint 3/8" (Male) Note: This installation is only for WM301 / SL30B & WM301 / SL30C ! Caution The orifice pipe must be installed in the correct direction as shown above. Improper direction may cause failure to the operating system. A. Outdoor unit orifice pipe installation (where installation space is wide enough) Step 2 Orifice Pipe Step 1 Steps: 1. Directly connect the “Female” nut of the orifice pipe to the liquid valve. 2. Flare the liquid pipe and connect it to the “Male” joint of the orifice pipe. Liquid Pipe Orifice Pipe 1-4 B. Outdoor unit orifice pipe installation (where installation space is limited) Step 4 English Orifice Pipe Step 3 Step 2 Step 1 If the orifice pipe cannot be connected directly to the liquid valve due to space constraint, it can be connected in between of the liquid pipe. Steps: 1. Flare the liquid pipe and connect it to the liquid valve. 3. Connect the “Female” nut of the Orifice pipe to the“Male” joint. Orifice Pipe Liquid Pipe 2. Braze an additional “Male” joint to the liquid pipe. 4. Flare another liquid pipe and connect it to the “Male” joint of the orifice pipe. Liquid Pipe Liquid Pipe Orifice Pipe Brazer C. Indoor unit orifice pipe installation Indoor Unit Orifice Pipe Steps: 1. Braze an additional “Male” joint to the liquid pipe. 2. Connect the “Female” nut of the Orifice pipe to the“Male” joint. Orifice Pipe Liquid Pipe 3. Flare another liquid pipe and connect it to the “Male” joint of the orifice pipe. Liquid Pipe Liquid Pipe Orifice Pipe Brazer 1-5 INSTALLATION OF THE INDOOR UNIT The refrigerant piping can be routed to the unit in a number of ways (left or right from the back of the unit), by using the cut-out holes on the casing of the unit (see figure). Bend the pipes carefully to the required position in order to aligned it with the holes. For the right hand and rear side out, hold the bottom of the piping and then position it to the required direction (see figure). The condensation drain hose can be taped to the pipes. The indoor unit must be installed in such a way so as to prevent short circuit of the cool discharged air with the hot return air. Please follow the installation clearance shown in the figure. Do not place the indoor unit where there could be direct sunlight shining on it. Also, this location must be suitable for piping and drainage, and be away from doors or windows. 50mm 50mm 50mm 50mm 50mm 50mm Right & rear side routing Higher Than Eye Level Air Flow Direction Maintenance & Servicing Space Installation plate Mount the unit onto the installation plate Hook the indoor unit onto the upper portion of the installation plate (Engage the two hooks at the rear top of the indoor unit with the upper edge of the installation plate). Ensure that the hooks are properly seated on the installation plate by moving it to the left and right. Marking-offline Thread Mounting installation plate Ensure that the wall is strong enough to withstand the weight of the unit. Otherwise, it is necessary to reinforce the wall with plates, beams or pillars. Use the level gauge for horizontal mounting, and fix it with 4 suitable screws. In case the rear piping draws out, drill a hole 65mm in diameter with a cone drill, slightly lower on the outside wall (see figure). Connecting cable Drain hose Water drainage piping Inside Outside The indoor drain pipe must be in a downward gradient for smooth drainage. Avoid situations that are likely to cause water to leak. 1/50 Inclination Water Drainage Routing of piping Remove the screw holding the front panel. Water Leaking Water Leaking 3 2 1 Piping routing Water Leaking End Dipped Into Water 4 5 1-6 ✓ j J J J Correct Wrong Wrong Wrong ! Caution An orifice is used as expansion device in WM301 cooling only unit. It is fixed in the liquid pipe in the indoor unit. Piping length and elevation Cutting copper tube If the pipe is too long, both the capacity and reliability of the unit will drop. As the number of bends increases, resistance to the flow of refrigerant system increases, thus lowering cooling capacity. As a result the compressor may become defective. Always choose the shortest path and follow the recommendations as tabulated below: Model Maximum length, m (ft), L 07/10 15 20 25 30 12 (39.4) 12 (39.4) 15 (49.2) 15 (49.2) 35 (114.8) Maximum elevation m (ft), H 5 (16.4) 5 (16.4) 8 (26.2) 8 (26.2) 15 (49.2) Maximum number of bends 10 10 10 10 10 Liquid pipe size 1/4" 1/4" 1/4" 3/8" 3/8" Gas pipe size 3/8" 1/2" 5/8" 5/8" 5/8" Remove burr Copper tube Swaging block Remark: The refrigerant pre-charged in the outdoor unit is for piping length up to 7.62m/25ft. Indoor unit Piping connection to the units • • Align the center of the piping and tighten the flare nut sufficiently with fingers. Finally, tighten the flare nut with the torque wrench until the wrench clicks. Pipe Size mm / (in) L Torque Nm / (Ft-lb) 6.35 (1/4) 9.53 (3/8) 12.7 (1/2) 15.88 (5/8) H 18 42 55 65 Ø Tube, D Outdoor unit A (mm) Inch mm Imperial Rigid 1/4" 3/8" 1/2" 5/8" 6.35 9.52 12.70 15.88 1.3 1.6 1.9 2.2 0.7 1.0 1.3 1.7 Piping works • • • • • • • Do not use contaminated or damaged copper tubing. Do not remove plastic, rubber plugs and brass nuts from the valves, fittings, tubings and coils until you are ready to connect suction or liquid line into valves or fittings. If any brazing work is required, ensure that the nitrogen gas is passed through coil and joints while the brazing work is being done. This will eliminate soot formation on the inside walls of the copper tubings. Cut the connection pipe with a pipe cutter. Remove burrs from cut edges of the pipes with remover. Hold the end of the pipe downwards to prevent metal chips from entering the pipe. Insert the flare nuts, mounted on the connection parts of both the indoor unit and outdoor unit onto the copper pipes. Flare the pipe with extra length above the flaring tool as shown in the table. The flared edge must be even and not cracked or scratched. Flare Joint Flared Tube Indoor Piping Flare Nut Torque Wrench Spanar 1-7 (13.3) (31.0) (40.6) (48.0) English REFRIGERANT PIPING ELECTRICAL WIRING CONNECTION Cooling unit IMPORTANT : * The figures shown in the table are for information purpose only. They should be checked and selected to comply with the local/national codes of regulations. This is also subject to the type of installation and conductors used. ** The appropriate voltage range should be checked with label data on the unit. ETL listed is only applicable to 60Hz power supply only. Model Indoor Outdoor WM 071/ 101/ 151 SL07/ 10/ 15B Voltage range** WM201/ 251/ 301 SL20/ 25/ 30B 220V-240V/ 1Ph/ 50Hz + 5WM311 5SL28C WM301 SL30C or 208V-230V/ 1Ph/ 60Hz + WM201/ 251/ 301 SL20/ 25/ 30B WM301 SL30C 380V-415V/ 3Ph/ 50Hz +N+ Power supply cable size* Number of wires mm2 1.5 3 2.5 3 2.5 3 4 3 1.5 5 1.5 5 Interconnection cable size* Number of wires mm2 1.5 3 2.5 3 2.5 3 2.5 4 1.5 4 1.5 4 A 15 20 20 25 15 15 Recommended fuse WM301 VS SL30C WM07 / 10 / 15 / 20 / 25 / 301 VS SL07 / 10 / 15 / 20 / 25 / 30B 5WM311 VS 5SL28C Indoor Unit Outdoor Unit Terminal Block Terminal Block Indoor Unit Terminal Block Outdoor Unit Terminal Block COMP N COMP COMP N2 N N2 L S N1 R N1 L COMP L L Power Supply Cable Power Supply Cable ! N ! There must be a double pole switch with a minimum 3mm contact gap and fuse/circuit breaker as recommended in the fixed installation circuit. WM201 / 251 VS SL20 / 25B (3 Phase) Indoor Unit Terminal Block There must be a double pole switch with a minimum 3mm contact gap and fuse/circuit breaker as recommended in the fixed installation circuit. WM301 VS SL30C (3 Phase) Outdoor Unit Terminal Block Indoor Unit Terminal Block COMP Outdoor Unit Terminal Block COMP COMP L COMP L N2 N N2 N N1 N1 R L L R S S T Power Supply Cable Power Supply Cable N T N ! ! There must be a double pole switch with a minimum 3mm contact gap and fuse/circuit breaker as recommended in the fixed installation circuit. There must be a double pole switch with a minimum 3mm contact gap and fuse/circuit breaker as recommended in the fixed installation circuit. • All wires must be firmly connected. • All wires must not touch the refrigerant piping, compressor or any moving parts of the fan motor. • The connecting wires between the indoor unit and the outdoor unit must be clamped on the wire clamps as shown in the figure. • The power supply cord must be equivalent to H05RN-F (245IEC57) which is the minimum requirement. Wire Clamp Interconnection Cable 1-8 Heat pump unit The figures shown in the table are for information purpose only. They should be checked and selected to comply with the local/national codes of regulations. This is also subject to the type of installation and conductors used. ** The appropriate voltage range should be checked with label data on the unit. ETL listed is only applicable to 60Hz power supply only. Model Indoor WM 071/ 101/ 151 R WM201/ 251/ 301 R 5WM301R WM301 R WM201/ 251/ 301 R WM301 R Outdoor SL07/ 10/ 15BR SL20/ 25/ 30BR 5SL28CR SL30CR SL20/ 25/ 30BR SL30CR Voltage range** 220V-240V/ 1Ph/ 50Hz + or 208V-230V/ 1Ph/ 60Hz + 380V-415V/ 3Ph/ 50Hz +N+ Power supply cable size* Number of wires mm2 1.5 3 2.5 3 2.5 3 4 3 1.5 5 1.5 5 Interconnection cable size* Number of wires mm2 1.5 5 2.5 5 2.5 5 2.5 6 1.5 6 1.5 4 A 15 20 20 25 15 15 Recommended fuse WM301R VS SL30CR WM07 / 10 / 15 / 20 / 25 / 301R VS SL07 / 10 / 15 / 20 / 25 / 30BR 5WM301R VS 5SL28CR Outdoor Coil Sensor Connection Wire (8m long) attached in the indoor unit Outdoor Unit Terminal Block Indoor Unit A Terminal Block Outdoor Coil Sensor Connection Wire (8m long) attached in the indoor unit Indoor Unit Terminal Block Outdoor Unit Terminal Block 4WV 4WV OF OF COMP COMP N2 N1 N 4WV 4WV OF OF COMP COMP N2 L N1 N L L Power Supply Cable Power Supply Cable N L ! There must be a double pole switch with a minimum 3mm contact gap and fuse/circuit breaker as recommended in the fixed installation circuit. ! WM201 / 251R VS SL20 / 25BR (3 Phase) There must be a double pole switch with a minimum 3mm contact gap and fuse/circuit breaker as recommended in the fixed installation circuit. WM301R VS SL30CR (3 Phase) Outdoor Coil Sensor Connection Wire (8m long) attached in the indoor unit Indoor Unit Outdoor Unit Terminal Block Terminal Block Outdoor Coil Sensor Connection Wire (8m long) attached in the indoor unit Outdoor Unit Terminal Block Indoor Unit A Terminal Block 4WV 4WV OF OF COMP COMP N2 L N2 L N1 N N1 N 4WV 4WV OF OF COMP COMP L L R R S Power Supply Cable S T T Power Supply Cable N ! ! There must be a double pole switch with a minimum 3mm contact gap and fuse/circuit breaker as recommended in the fixed installation circuit. 1-9 There must be a double pole switch with a minimum 3mm contact gap and fuse/circuit breaker as recommended in the fixed installation circuit. N English IMPORTANT : * SPECIAL PRECAUTIONS WHEN DEALING WITH R410A UNIT • • • • • • R410A is a near azeotrope refrigerant blend of hydro fluorocarbon (HFC) which is environmental friendly. It has Zero Ozone Depletion Potential (ODP=0) and this conforms to Montreal Protocol regulations. It has no flame propagation and a low toxic refrigerant (rated as A1 by ARI). R410A is a mixture of R32 (50%) and R125 (50%). POE oil is used as lubricant for R410A compressor, which is different from the mineral oil used for R22 compressor. During installation or servicing, extra precaution must be taken not to expose the R410A system too long to moist air. Residual POE oil in the piping and components can absorb moisture from the air. Refrigerant R410A is more easily affected by dust of moisture compared with R22, make sure to temporarily cover the ends of the tubing prior to installation. No additional charge of compressor oil only is permitted. No refrigerant other than R410A is permitted. Tools designed specifically for R410A only. i) Manifold gauge and charging hose ii) Gas leak detector iii) Refrigerant cylinder/charging cylinder iv) Vacuum pump c/w adaptor v) Flare tools vi) Refrigerant recovery machine ! CAUTION • • • R410A must be charged as liquid. Usually R410A cylinder is equipped with a dip-pipe for liquid withdrawal. If there is no dip-pipe, the cylinder should be inverted so as to withdraw liquid R410A from the valve. Do not top-up when servicing leak, as this will reduce the unit performance. Vacuum the unit thoroughly and then charge the unit with fresh R410A according to the amount recommended in the specification. Do not touch the compressor or refrigerant piping when the chiller is running. If necessary wear protective gloves. VACUUMING AND CHARGING Purging the piping and the indoor unit Additional charge Except for the outdoor unit which is pre-charged with refrigerant, the indoor unit and the refrigerant connection pipes must be air-purged because the air containing moisture that remains in the refrigerant cycle may cause malfunction of the compressor. • Remove the caps from the valve and the service port. • Connect the centre of the charging gauge to the vacuum pump. • Connect the charging gauge to the service port of the 3-way valve. • Start the vacuum pump. Evacuate for approximately 30 minutes. The evacuation time varies with different vacuum pump capacity. Confirm that the charging gauge needle has moved towards -76mmHg (0~76mmHg). Caution If the gauge needle does not move to 0~76mmHg, be sure to check for gas leaks (using the refrigerant detector) at flare type connection of the indoor and outdoor unit and repair the leak before proceeding to the next step. • Close the valve of the changing gauge and stop the vacuum pump. • On the outdoor unit, open the suction valve (3 way) and liquid valve (2 way) (in anti-clockwise direction) with 4mm key for hexagon sacked screw. The refrigerant is pre-charged in the outdoor unit. If the piping length is less than 7.62m (25 ft), then additional charge after vacuuming is not necessary. If the piping length is more than 7.62m (25 ft), then use the additional charge valve as indicated in the table below. Service Port Indoor Unit Refrigerant Piping Flare Unit Allen Key Outdoor Unit 3 Ways Valve Liquid Side Discharge Valve Close Gas Side Suction Valve Open Vacuum Pump Close Hi Low Close 1-10 Outdoor Unit Model 071 / 101 / 151 201 251 / 301 071R / 101R /151R 201R 251R / 301R 10 m/32.8 ft 35 35 90 50 60 120 12 m/39.4 ft 65 65 165 90 110 220 15 m/49.2 ft 110 280 185 370 • Additional charge in gram (R410A) Model 311 301R 10 m/32.8 ft 80 110 12 m/39.4 ft 150 200 Open the gas cylinder and low pressure charging valve. When the required refrigerant quantity is pumped into the unit, close the low pressure side and the gas cylinder valve. Disconnect the service hose from service port. Put back the service port cap. Indoor Unit Liquid Side Outdoor Unit Discharge Valve 15 m/49.2 ft 255 335 Close Charge operation Gas Side This operation must be done by using a gas cylinder and a precise weighing machine. The additional charge is toppedup into the outdoor unit using the suction valve via the service port. • Remove the service port cap. • Connect the low pressure side of the charging gauge to the suction service port center of the cylinder tank and close the high pressure side of the gauge. Purge the air from the service hose. • Start the air conditioner unit. Suction Valve Check Valve Low Open Close Hi Close INDICATOR LIGHTS IR signal receiver Cooling unit When an infrared remote control operating signal has been transmitted, the signal receiver on the indoor unit will make a <beep> sound to confirm acceptance of the signal transmission. The table shows the LED indicator lights for the air conditioner unit under normal operation and fault conditions. The LED indicator lights are located at the bottom right side of the air conditioner unit. LED Indicator Lights for Cooling Unit IR Receiver Power ON Timer Dry mode Sleep mode LED Indicator Lights LED Indicator Lights : Normal Operation And Fault Conditions For Cooling Unit Operation / Fault Indication Power Dry Timer Sleep Timer on. – Sleep mode on. – Dry mode. – Frost prevention. Continuously Action Clean the filter and switch to high fan. Room air sensor contact loose/short. Call your dealer. twice every 2 sec. Indoor coil sensor contact loose/short. Call your dealer. Sensor contact problem, compressor overload protection trip or gas leak Call your dealer. 3 times every 2 sec. once every 2 sec. ON ON or OFF 1-11 Blinking English • • Additional charge in gram (R22) LED Indicator Lights For Heat Pump Unit Heat pump unit The table shows the LED indicator lights for the air conditioner unit under normal operation and fault conditions. The LED indicator lights are located at the bottom right side of the air conditioner unit. The heat pump units are equipped with an “auto” mode sensor whereby it will provide reasonable room temperature by switching automatically to either “cool” or “heat” mode, according to the temperature set by the user. Cooling mode Dry mode Heat/Fan mode (red/green) Sleep mode LED Indicator Lights : Normal Operation And Fault Conditions For Heat Pump Unit Normal Operation/Fault Condition Cool Dry Fan Heat Action Sleep Cooling mode. – Dry mode. – Fan mode. – Heat mode. – Auto mode in heating operation. – Auto mode in cooling operation. – Defrost operation. – Compressor overload protection. Call your dealer. Indoor coil sensor contact loose/short. Call your dealer. Outdoor coil sensor contact loose/short. Call your dealer. Room air sensor contact loose/short. Call your dealer. If the system is in cool mode or heat mode (with the sleep function off), the sensor may have a contact problem, compressor overload protection trip or gas leak. ON ON or OFF 1-12 Blinking Dry mode Frost prevention • When the air humidity is high, the unit can operate in dry mode. Press <MODE> button and choose <DRY>. • If the room temperature is 2°C/35.6°F higher than the set temperature, the air conditioner will operate under cooling mode until it reaches within the 2°C/35.6°F range of difference compared to the set temperature before it converts to dry mode. • If the room temperature is within the 2°C/35.6°F range of difference compared to the set temperature, it will directly operate under dry mode. • The unit will operate at LOW speed under dry mode. • When the air filter is dirty, the evaporating temperature will decrease and eventually cause frosting. • The LED light will blink to indicate that the filter is dirty. If the evaporating temperature reaches -2°C/28.4°F, the unit will trip and defrost. Fan speed and rated cooling capacity • The rated cooling capacity is provided at the maximum fan speed. • The cooling capacity is lower when the unit is operating at MEDIUM and LOW fan speed. Heat mode (for heat pump unit only) • When the unit is switched on from cold start or defrosting cycle, the indoor fan will start to operate only after the coil reaches the desired temperature. • When the set temperature is achieved, the indoor fan will operate until the coil cannot provide anymore additional heat. Cooling Dry Horizontal 25°C/77°F Horizontal air flow control • For more effective air circulation, you can manually adjust the air discharge grille to the left or right. • During cool mode operation and dry mode operation, do not direct the air discharge louver downwards for too long. If operating continues in this way, condensation may occur on the louver, thus resulting in drippings. Hot Keep (for heat pump only) • • During compressor cut off, the indoor fan can be switched to (i) ON (default) or (ii) OFF or (iii) Interval on and off by setting the slide switch shown in the diagram. The switch is located at the front frame cover (next to the ON/OFF switch). HOT KEEP OFF INTERVAL ON ON/OFF switch NOTE : When the option is selected, the power supply of the unit need to be reset in order to activate the function. Overheating protection (for heat pump unit only) • In case the internal and/or the external temperature is to high, or the filter is dirty and clogged up, the refrigerant may be overheated. The compressor will cut out when the condensing temperature reaches 62°C/143.6°F. 1-13 English AIR CONDITIONER UNIT OPERATION STANDARD OPERATING CONDITIONS Heat Pump Unit Cooling unit Temperature Ts °C/°F Th °C/°F Temperature Minimum indoor temperature 19.4 / 66.9 13.9 / 57.0 Minimum indoor temperature Maximum indoor temperature 26.7 / 80.1 19.4 / 66.9 Maximum indoor temperature Minimum outdoor temperature 19.4 / 66.9 13.9 / 57.0 Minimum outdoor temperature -8 / 17.6 -9 / 15.8 Maximum outdoor temperature 46 / 114.8 24 / 75.2 Maximum outdoor temperature 24 / 75.2 18 / 64.4 Ts °C/°F Th °C/°F 10 / 50 - 26.7 / 80.1 - Ts: Dry bulb temperature. Th: Wet bulb temperature. ! Warning • Disconnect from the main power supply before servicing the air conditioner unit. • DO NOT pull out the power cord when the power is ON. This may cause serious electrical shocks which may result in fire hazards. ELECTROSTATIC FILTER DUAL ACTION ELECTROSTATIC AIR PURIFYING AND DEODORIZING FILTER MEDIA AND FILTER FRAME ACTION 1ELECTROSTATIC AIR PURIFYING FILTER ACTION 2DEODORIZING FILTER Removes microscopic dust, smoke and small invisible particles to keep the room air clean with pre-charged electrostatic polypropylene filter. Removes unwanted smells and odors in the air and keeps the room air fresh with activated carbon filter. HOW TO INSTALL 1-14 1. The electrostatic air purifying and deodorizing filter should be replaced once every 6 months or when the filter changes color to brownish, whichever is sooner. 2. Used dusty filters should be disposed and shouldn't be reused, even if it has been cleaned and washed. 3. The filter is a consumable part which you can purchase from your air conditioner dealer. 4. Use the new filter immediately once it has been taken out from its sealed packing. Do not unpack the new filter too early before it is actually used as this may decrease its deodorizing effect. ! Warning • • Disconnect from the main power supply before servicing the air conditioner unit. DO NOT pull out the power cord when the power is ON. This may cause serious electrical shocks which may result in fire hazards. SERVICE AND MAINTENANCE Service Parts Maintenance Procedures Indoor air filter 1. Remove any dust adhering to the filter by using a vacuum cleaner or wash in lukewarm water (below 40°C/104°F ) with a neutral cleaning detergent. 2. Rinse the filter well and dry before placing it back onto the unit. 3. Do not use gasoline, volatile substances or chemicals to clean the filter. At least once every 2 weeks. 1. Clean any dirt or dust on the grille or panel by wiping it off with a soft cloth soaked in lukewarm water (below 40°C/104°F) and a neutral detergent solution. 2. Do not use gasoline, volatile substances or chemicals to clean the indoor unit. At least once every 2 weeks. More frequently if necessary. Indoor unit Period More frequently if necessary. ! Caution Do not operate any heating apparatus too close to the air conditioner unit. This may cause the plastic panel to melt or deform as a result of the excessive heat. WHEN THE UNIT IS NOT USED FOR AN EXTENDED PERIOD OF TIME Operate the unit for 2 hours with the following setting. Operating mode : cool Temperature : 30°C/86°F Remove the power plug. If you are using an independent electric circuit for your unit, cut off the circuit. Remove the batteries in the remote control. 1-15 English ! Caution TROUBLESHOOTING If any malfunction of the air conditioner unit is noted, immediately switch off the power supply to the unit. Check the following fault conditions and causes for some simple troubleshooting tips. Causes / Action Fault 1. The compressor does not operate 3 minutes after the air conditioner unit is started. - Protection against frequent starting. Wait for 3 to 4 minutes for the compressor to start operating. 2. The air conditioner unit does not operate. - Power failure, or the fuse needs to be replaced. - The power plug is disconnected. - It is possible that your delay timer has been set incorrectly. - If the fault persist after all these verifications, please contact the air conditioner unit installer. 3. The air flow is too low. - The air filter is dirty. - The doors or windows are open. - The air suction and discharge are clogged. - The regulated temperature is not high enough. 4. Discharge air flow has bad odour. - Odours may be caused by cigarettes, smoke particles, perfume etc. which might have adhered onto the coil. 5. Condensation on the front air grille of the indoor unit. - This is caused by air humidity after an extended period of operation. - The set temperature is too low, increase the temperature setting and operate the unit at high fan speed. 6. Water flowing out from the air conditioner unit. - Switch off unit and call dealer. 7. Hissing air flow sound from the air conditioner unit during operation. - Refrigerant fluid flowing into the evaporator coil. If the fault persists, please call your local dealer/serviceman. 1-16 Ce manuel fournit les procédures d’installation pour assurer le bon fonctionnement et la sécurité de cet appareil. Des ajustements peuvent être nécéssaires pour suivre les réglementations locales. Avant d’installer et de faire fonctionner le climatiseur, lisez attentivement ce manuel et conservez le. CLIMATISEURS SPLIT SYSTEM MONTAGE MURAL MODÈLE FROID SEUL (R22) POMPE À CHALEUR (R22) Modèle de Référence Modèle Modèle de Référence Modèle WM301 SL30C SL30B AWM301 ALC30C ALC30B WM301R SL30CR SL30BR AWM301R ALC30CR ALC30BR FROID SEUL (R410A) POMPE À CHALEUR (R410A) Modèle de Référence Modèle Modèle de Référence Modèle 5WM311 5SL28C A5WM311 A5LC28C 5WM301R 5SL28CR A5WM301R A5LC28CR IM-WM1-0302(2)-Acson Part No.: A08019025521 2-1 Français MANUEL D’INSTALLATION SOMMAIRE - Contour et Dimensions - Précautions de Sécurité - Diagramme D’installation - Installation de L’unité Extérieure - Installation du Tuyau D’orifice - Installation de L’unité Intérieure - Raccordements des Tuyauteries - Raccordement Électrique page i-ii page 2 page 3 page 3 page 4 page 6 page 7 page 8 - Précautions Spéciales Pour Les Appareils au R410A - Aspiration et Chargement - L’indicateur S’allume - Opération du Climatiseur - Conditions Standard de Fonctionnement - Filtre Électrostatique - Entretien et Maintenance - Analyse des Causes de Dysfonctionnement du Climatiseur page 10 page 10 page 11 page 13 page 14 page 14 page 15 page 16 PRÉCAUTIONS DE SÉCURITÉ Avant de faire fonctionner l’appreil, veuillez bien lire les précautions de sécurité suivantes. ! Attention • L’installation et la maintenance doivent être exécutées par une personne qualifiée qui est familiarisée avec les lois et réglementations en vigueur, et aussi expérimentée dans ce type d’équipements. • Tous les câblages doivent répondre aux réglementations électriques nationales. • Avant de commencer le raccordement suivant le schéma électrique, s’assurer que la tension nominale de l’appareil corresponde bien à celle indiquée sur la plaque signalétique. • L’ unité doit être raccordée à la TERRE pour prévenir tous les risques possibles dûes à un défaut d’isolation. • Aucun câble électrique ne doit toucher la tuyauterie du réfrigérant, le compresseur ou les pièces mobiles des moteurs de ventilation. • Avant l’installation ou l’entretien du climatiseur, s’assurer que l’appareil est éteint (OFF). IMPORTANT NE PAS INSTALLER OU UTILISER LE CLIMATISEUR DANS UNE BUANDERIE. ! Avertissement Vérifier les points suivants au cours de l’installation. • Ne pas installer l’appareil où il peut se produire des fuites de gaz inflammable. En cas de fuite et accumulation de gaz autour de l’appareil, il y a risque d’incendie. • S’assurer que le tuyau d’évacuation du condensat est correctement branché. Si le tuyau d’évacuation n’est pas correctement branché, les éventuelles fuites d’eau risquent de mouiller le mobilier. • Ne pas surcharger l’unité (en fluide frigorigène). Cet appareil est préchargé en usine. Une charge trop importante risque de provoquer une surcharge électrique ou d’endommager le compresseur. • S’assurer que le panneau supérieur de l’appareil est remis en place après l’installation ou l’entretien. Avec un panneau mal fixé l’appareil va fonctionner bruyamment. 2-2 DIAGRAMME D’INSTALLATION Unité Intérieure Filtre à air Cadre Avant Chassis Arriere Grilles de reprise d’air Français Interrupteur ON/OFF Tuyau D’evacuation Led de Visualisation Conduit de ventilation Récepteur de Signal Grilles de Ventilation Reprise Air Tuyauteries Frigorifiques Reprise Air Refoulement d’air Unité Extérieure B Obstacle A Refoulement Obstacle L’unité extérieure (ou groupe de condensation) doit être instalée dans un endroit où aucun obstacle ne doit perturber la circulation de l’air, aussi bien à l’aspiration qu’au refoulement du ventilateur (risque de recyclage d’air chaud). Respecter les dégagements minimum prévus (voir tableau ci-dessous). Choisir un emplacement le moins exposé possible à l’ensoleillement; l’entré d’air sur l’unité extérieure ne devra pas être supérieure à la température ambiante (maximum 45°C/113°F). Entrée d’air INSTALLATION DE L’UNITÉ EXTÉRIEURE D 1000 (39,4) 300 (11,8) 500 (19,7) Remarques : En cas d’obstacles de part et d’autre de l’unité d’une hauteur supérieure à 2 mètres ou toute obstruction d’air sur le dessus de l’unité, augmenter sensibelment les dégagements minimum prévus. 2-3 C D Obstacle C Accès de service B Obstacle Dimension A Minimum Distance, mm 300 (Pouce) (11,8) Entrée d’air Dégagements minimum INSTALLATION DU TUYAU D’ORIFICE Tuyau d’orifice 2 3 4 1 Unité Extérieure Intérieur 1 Orifice 3 Écrou évasé de 3/8 po (femelle) 2 Tuyau de raccord 4 Assemblage par évasement de 3/8 po (mâle) Remarque: Cette installation ne vaut que pour WM301 / SL30B et WM301 / SL30C ! Avertissement Le tuyau d’orifice doit être installé dans la bonne direction (illustration ci-dessus). Une orientation incorrecte peut causer l’échec du système d'exploitation. A. Installation de l’orifice du tuyau de l’unité extérieure (où l’espace pour l’installation est assez large) Étape 2 Tuyau d’orifice Étape 1 Étapes: 1. Raccorder directement l’écrou “Femelle” du tuyau d’orifice sur le robinet de liquide. 2. Évaser le tuyau de liquide et le brancher au joint “Mâle” du tuyau d’orifice. Tuyau d’orifice 2-4 Tuyau de liquide B. Installation de l’orifice du tuyau de l’unité extérieure (où l’espace pour l’installation est limité) Étape 4 Tuyau d’orifice Étape 3 Étape 2 Si le tuyau d’orifice ne peut pas être connecté directement au robinet de liquide à cause d’un manque d’espace, on peut l’installer au milieu du tuyau de liquide. Étapes: 1. Évaser le tuyau de liquide et le brancher au robinet de liquide. 3. Raccorder l’écrou “Femelle” du tuyau d’orifice au joint “Mâle”. Tuyau de liquide Tuyau d’orifice 2. Braser un joint “Mâle” supplémentaire au tuyau de liquide. 4. Évaser un autre tuyau de liquide et le brancher au joint “Mâle” du tuyau d’orifice. Tuyau de liquide Tuyau de liquide Tuyau d’orifice Braseur C. Installation du tuyau d’orifice sur l’unité intérieure Unité Intérieure Tuyau d’orifice Étapes: 1. Braser un joint “Mâle” supplémentaire au tuyau de liquide. 2. Raccorder l’écrou “Femelle” du tuyau d’orifice au joint “Mâle”. Tuyau de liquide 3. Évaser un autre tuyau de liquide et le brancher au joint “Mâle” du tuyau d’orifice. Tuyau de liquide Tuyau d’orifice Tuyau de liquide Tuyau d’orifice Braseur 2-5 Français Étape 1 INSTALLATION DE L’UNITÉ INTÉRIEURE Installer l’unité intérieure de traitement d’air de façon à ce qu’il n’y ait aucun obstacle sur la circulation de l’air (risque de recyclage de l’air refroidi au refoulement de l’unité et l’air à l’entrée). Veuillez respecter l’écartement d’installation illustré sur le diagramme. Ne pas exposer l’unité intérieure à l’influence directe de l’éclairage. L’emplacement de l’unité, doit permettre une évacuation aisée des condensats, et permettre une evacuation aisee des condensats, et doit être suffisamment loin des portes. 50mm L’unité d’évacuations des condensats de l’unité interieure devra être, dans la mesure du possible, dirigé vers la sortie arrière des tuyauteries à travers le mur de support (voir figure). Avant d’orienter le tubing, déclipser le support de tube. Cintrer les tubes frigorifiques avec précaution et les diriger vers la sorte choisie. Ne pas oublier de passer le câble d’alimentation électrique dans l’unité intérieure à travers le mur en même temps que les tuyauteries. Ne pas raccorder le câble. Laisser une longueur de câble suffisante pour permettre la connection ultérieure. Relier ensemble les tubes frigorifiques, le flexible d’évacuation des condensats et le câble électrique. 50mm 50mm Acheminement de la tuyauterie Plus haut que le niveau des yeux Direction de la circulation d’air Espace d’entretien et de reparation Plaque d’Installation Mise en place de l’unite de la platine support Positionner dans un premier temps l’unité intérieure sur la languette d’accrochage supérieure de support. Pour vous assurer que les crochets sont correctement installés sur la plaque d’installation, essayez de les faire légèrement bouger de gauche à droite. Le Marquage-Hors ligne Le fil Montage de la platine support S’assurrer que le mur de support soit suffisamment résistant, pour supporter le poids de l’unité et éviter toutes vibrations. Selon la composition du mur, utiliser des vis chevilles appropriées pour la fixation de la platine support. Utiliser la jauge à niveau pour le montage horizontal, puis la fixer avec 4 vis appropriées. Dans le cas de sortie arrière des tuyauteries, percer le trou Ø 65mm pour les canalisations à l’aide d’une scie cloche. Le trou aura une légère pente vers l’unité extérieure (Voir figure). Câble de liaison Tuyau d’evacuation Évacuation des condensats À l’extèrieur À l’intèrieur Le tube d’évacuation des condensats de l’unité devra être, dans la mesure du possible, dirigé vers la sortie arriere des tuyauteries a travers le mur de support. Evitez les situations susceptibles de causer une fuite d’eau. Inclinaison de 1/50 Orientation des tuyauteries Drainage De L’eau Retirer les vis qui retiennent le panneau de devant. 3 2 1 Acheminement de la tuyauterie Fuite d’eau Fuite d’eau 4 5 2-6 Fuite d’eau Evacuation d’eau de Condensation plongé dans l’eau j ✓ J J J Correct Incorrect Incorrect Incorrect RACCORDEMENTS DES TUYAUTERIES ! Attention Dans l’unité de refroidissement WM301 on utilise un orifice, attaché à la tuyauterie d'eau de l’unité intérieure, comme dispositif d’expansion. Longueur des tuyauteries et différence de niveau Coupe des Tubes Cuivre Modèle 07/10 15 20 25 30 Longueur max, m (ft), L 12 (39,4) 12 (39,4) 15 (49,2) 15 (49,2) 35 (114,8) Elevation max m (ft), H 5 (16,4) 5 (16,4) 8 (26,2) 8 (26,2) 15 (49,2) Nombre de coude max 10 10 10 10 10 Ø racc. Tube liquide 1/4" 1/4" 1/4" 3/8" 3/8" Ø racc. Tube aspiration 3/8" 1/2" 5/8" 5/8" 5/8" Remarque: Français Pour un bon fonctionnement des unités, il est impératif de respecter la longueur maximum des tuyauteries indiquée dans le tableau ci-dessours, de respecter le nombre de coudes maximum autorisé, et de ne pas dépasser la différence de niveau entre l’unite intérieure et l’unite extérieure. Tableau des caracteristiques valables pour les unites froid seul et reversibles. Ebavurage Tube Cuivre Dudgeonniere La charge complète de gaz se trouve dans l’unité extérieure jusqe’à une longueur nominale de 7,62 mètres/ 25ft., aucun complément en réfrigérant n’est nécéssaire. Raccordement de la tuyauterie aux unités Unité Intérieure • Aligner les tubes et serrer l’écrou à la main d’abord. • Enfin, serrer l’écrou à l’aide d’une clef dynamométrique jusqu’au clic. Ø Tuyau mm / (pouce) L 6,35 (1/4) 9,53 (3/8) 12,7 (1/2) 15,88 (5/8) H Pouce 1/4" 3/8" 1/2" 5/8" Unité Extérieure Ø Tube, D mm 6,35 9,52 12,70 15,88 Couple Nm / (Ft-lb) 18 42 55 65 (13,3) (31,0) (40,6) (48,0) A (mm) Impérial Normal 1,3 0,7 1,6 1,0 1,9 1,3 2,2 1,7 Travail des tuyauteries Raccord à visser • • • • • • • Ne pas utiliser de tuyauteries en cuivre encrassé ou endommagé. Ne pas retirer les bouchons en plastique ou caoutchouc et les écrous en laiton des vannes, raccords, tubes et serpentins jusqu’à ce que les tuyauteries d’apiration ou de liquide soient prêtes à être connectées aux vannes et raccords. S’il est nécessaire de braser, s’assurer que de l’azote passe dans les serpentins et raccords pendant le brasage, pour éviter les dépôts de suie sur les faces intérieures des tubes de cuivre. Couper le tuyau de raccordement avec un coupe-tube. Ébarber les bords coupés des tuyaux à l’aide d’un alésoir. Tenir l’extrémité du tuyau vers le bas pour empêcher la limaille d’entrer dans le tuyau. Relier les écrous ‘flare’ montés sur les connexions des unités intérieure et extérieure aux tubes de cuivre. Évaser le tuyau avec longueur supplémentaire au-dessus de l’outil à évaser comme indiqué sur le tableau. Le bord évasé doit être régulier et ne présenter aucune craquelure ou éraflure. Tube de l'unité Intérieure Tube avec dudgeon Ecrou Clef Dynamométrique Clef d'immobilisation 2-7 RACCORDEMENT ÉLECTRIQUE Module refroidisseur IMPORTANT : * Ces valeurs sont données à titre indicatif seulement; elles doivent être vérifiées et ajustées en fonction des normes et de la réglementations en vigueur. Elles dépendent aussi du type d’installation et du choix des conducteurs utilisés. ** Le voltage adéquat doit être vérifié avec les données de l’étiquette sur l’appareil. ETL n’est applicable que pour une alimentation électrique de 60Hz. Modèle Intérieure Extérieure WM 071/ 101/ 151 SL07/ 10/ 15B Tension d’alimentation** WM201/ 251/ 301 SL20/ 25/ 30B 220V-240V/ 1Ph/ 50Hz + 5WM311 5SL28C WM301 SL30C ou 208V-230V/ 1Ph/ 60Hz + WM201/ 251/ 301 SL20/ 25/ 30B WM301 SL30C 380V-415V/ 3Ph/ 50Hz +N+ Section du câble d’alim* Nombre de conducteurs mm2 1,5 3 2,5 3 2,5 3 4 3 1,5 5 1,5 5 Section du câble de liaison* Nombre de conducteurs mm2 1,5 3 2,5 3 2,5 3 2,5 4 1,5 4 1,5 4 A 15 20 20 25 15 15 Fusible aM WM301 VS SL30C WM07 / 10 / 15 / 20 / 25 / 301 VS SL07 / 10 / 15 / 20 / 25 / 30B 5WM311 VS 5SL28C Bornier De Bornier De L’unité Intérieure L’unité Extérieure Bornier De L’unité Intérieure Bornier De L’unité Extérieure L COMP N COMP COMP N2 N N2 S N1 R N1 L COMP L L Cordon Electrique Cordon Electrique ! N ! Il doit y avoir un interrupteur à double pôles avec un intervalle de contact de 3mm minimum et un coupe-circuit/ fusible comme recommandé dans le circuit d’installation fixe. WM201 / 251 VS SL20 / 25B (3 Ph) Bornier De L’unité Intérieure Il doit y avoir un interrupteur à double pôles avec un intervalle de contact de 3mm minimum et un coupe-circuit/ fusible comme recommandé dans le circuit d’installation fixe. WM301 VS SL30C (3 Ph) Bornier De L’unité Extérieure Bornier De L’unité Intérieure COMP Bornier De L’unité Extérieure COMP COMP L COMP L N2 N N2 N N1 N1 R L L R S S T Cordon Electrique Cordon Electrique N T N ! Il doit y avoir un interrupteur à double pôles avec un intervalle de contact de 3mm minimum et un coupe-circuit/ fusible comme recommandé dans le circuit d’installation fixe. ! Il doit y avoir un interrupteur à double pôles avec un intervalle de contact de 3mm minimum et un coupe-circuit/ fusible comme recommandé dans le circuit d’installation fixe. • Tous les fils doivent être fermement connectés. • Aucun fils ne doivent toucher les tubes frigorifiques, le compresseur ou une autre partie mobile du moteur de ventilateur. • Le câble de liaison entre l’unité intérieure et extérieure doit être fixé au boitier de raccordement à l’aide de l’attache comme indiqué dans la figure ci-contre. • Le cordon électrique doit être êquivalent à H05RN-F (245IEC57) au minimum. Pince A Fil Câble De Liaison 2-8 Module pompe à chaleur IMPORTANT : * Ces valeurs sont données à titre indicatif seulement; elles doivent être vérifiées et ajustées en fonction des normes et de la réglementations en vigueur. Elles dépendent aussi du type d’installation et du choix des conducteurs utilisés. ** Le voltage adéquat doit être vérifié avec les données de l’étiquette sur l’appareil. ETL n’est applicable que pour une alimentation électrique de 60Hz. Intérieure WM 071/ 101/ 151 R WM201/ 251/ 301 R 5WM301R WM301 R WM201/ 251/ 301 R WM301 R Extérieure SL07/ 10/ 15BR SL20/ 25/ 30BR 5SL28CR SL30CR SL20/ 25/ 30BR SL30CR Tension d’alimentation** 220V-240V/ 1Ph/ 50Hz + ou 208V-230V/ 1Ph/ 60Hz + 380V-415V/ 3Ph/ 50Hz +N+ Section du câble d’alim* Nombre de conducteurs mm2 1,5 3 2,5 3 2,5 3 4 3 1,5 5 1,5 5 Section du câble de liaison* Nombre de conducteurs mm2 1,5 5 2,5 5 2,5 5 2,5 6 1,5 6 1,5 4 A 15 20 20 25 15 15 Fusible aM WM301R VS SL30CR WM07 / 10 / 15 / 20 / 25 / 301R VS SL07 / 10 / 15 / 20 / 25 / 30BR 5WM301R VS 5SL28CR Câble De Liaison De La Sonde De Température Obligatoire (longueur 8m) Fourni Bornier De Avec L’Unité Intérieure L’unité Extérieure Bornier De Câble De Liaison De La Sonde De Température Obligatoire (longueur 8m) Fourni Avec L’Unité Intérieure Bornier De Bornier De L’unité Intérieure L’unité Extérieure 4WV 4WV OF OF COMP COMP L’unité Intérieure N2 N1 N A 4WV 4WV OF OF COMP COMP N2 L N1 N L L Cordon Electrique Cordon Electrique N L ! Il doit y avoir un interrupteur à double pôles avec un intervalle de contact de 3mm minimum et un coupe-circuit/ fusible comme recommandé dans le circuit d’installation fixe. ! WM201 / 251R VS SL20 / 25BR (3 Ph) Il doit y avoir un interrupteur à double pôles avec un intervalle de contact de 3mm minimum et un coupe-circuit/ fusible comme recommandé dans le circuit d’installation fixe. WM301R VS SL30CR (3 Ph) Câble De Liaison De La Sonde De Température Obligatoire (longueur 8m) Fourni Bornier De Avec L’Unité Intérieure L’unité Extérieure Bornier De A L’unité Intérieure Câble De Liaison De La Sonde De Température Obligatoire (longueur 8m) Fourni Avec L’Unité Intérieure Bornier De Bornier De L’unité Intérieure L’unité Extérieure 4WV 4WV OF OF COMP COMP N2 L N2 L N1 N N1 N 4WV 4WV OF OF COMP COMP L L R R S Cordon Electrique S T T Cordon Electrique N ! ! Il doit y avoir un interrupteur à double pôles avec un intervalle de contact de 3mm minimum et un coupe-circuit/ fusible comme recommandé dans le circuit d’installation fixe. 2-9 Il doit y avoir un interrupteur à double pôles avec un intervalle de contact de 3mm minimum et un coupe-circuit/ fusible comme recommandé dans le circuit d’installation fixe. N Français Modèle PRÉCAUTIONS SPÉCIALES POUR LES APPAREILS AU R410A • • • • • • Le R410A est un mélange quasi-azéotrope de frigorigène d’hydrofluorocarbure (HFC), sans danger pour l’environnement. Il a un potentiel d’appauvrissement de l’ozone de zéro (PAO=0), ce qui est conforme aux dispositions du Protocole de Montréal. Il est coté A1 (frigorigène peu toxique sans propagation de flamme) par l’ARI. Le R410A est un mélange de R32 (50%) et de R125 (50%). L’huile POE est utilisé comme lubrifiant pour les compresseurs R410A, et elle est différent par rapport à l’huile minérale utilisée pour les compresseurs R22. Lors de l’installation ou de la maintenance, des précautions supplémentaires doivent être adoptées pour ne pas exposer le système R410A trop de temps à l’air humíde. L’huile POE résiduelle restée dans les tuyauteries et les équipments peut absorber l’humidité de l’air. Le réfrigérant R410A est plus facilement affecté par l’humidité par rapport à R22, s’assurer de protéger temporairement les extrémités des tuyauteries avant l’installation. Il n’est pas permis de rajouter de l’huile dans le compresseur. Aucun autre réfrigérant que le R410A n'est permis. Garder des instruments seulement pour le R410A i) Manifold et flexible de charge ii) Détecteur de fuite de gaz iii) Cylindre de charge/bouteille de réfrigérant iv) Adaptateur c/w pompe à vide v) Chalumeau et outillage à flare vi) Machine de récupération du réfrigérant ! AVERTISSEMENT • • • La charge du R410A doit être réalisée en phase liquide. Normalement la bouteille de R410A est équipé d’un tube plongeur pour le prélèvement du liquide. Si la bouteille n’est pas pourvu de ce tube elle doit être inversée de façon à prélever le liquide au moyen de la vanne. Ne pas rajouter en cas de réparation de fuites afin de ne pas réduire les performances de l’appareil. Vidanger complètement l’unité pour la recharger avec du R410A frais suivant le poids préconisé dans les spécifications techniques. Ne pas toucher le compresseur ou la tuyauterie du réfrigérant lorsque le mini-chiller est en marche. Porter des gants si besoin est. ASPIRATION ET CHARGEMENT Purge des tuyauteries et de l’unité intérieure Complément De Charge Excepté l’unité extérieure (groupe de condensation) qui contient la charge complète de réfrigérant, l’unité intérieure et les tubes des liaisons frigorifiques doivent être purgés de l’air contenu dans le circuit. • Enlever le bouchon central, ainsi que le bouchon de la prise de pression sur chaque vanne. • Raccorder le centre de la jauge de chargement à la pompe à vide. • Raccorder la jauge de chargement à l’orifice de service de la valve à trois voies. • Démarrer la pompe à vide. Évacuer pendant environ 30 minutes. La période d’évacuation varie selon la capacité de la pompe à vide. S’assurer que l’aiguille de la jauge de chargement se soit déplacée vers -76 mmHg (0~76mmHg). Avertissement Si l'aguille de la jaudge ne se déplace pas vers 0 ~ 76mm Hg, vérifier qu'il n'y ait pas de fuite de gaz (à l'aide d'un détecteur de gaz) au niveau des raccordements évasés des unités intérieures et extérieures, puis réparer la fuite avant de passer à l'étape suivante. • Fermer la valve de la jauge de chargement et éteindre la pompe à vide. • Sur l’unité extérieure, ouvrir la valve de succion (3 voies) et la valve de liquide (2 voies) (dans le sens inverse des aiguilles d’une montre) à l’aide d’une clé pour vis hexagonales de 4mm. La charge complète de gaz se trouve dans l’unité extérieure, jusqu’à une longueur nominale de 7,62m (25 ft), aucun complément de charge n’est nécéssaire. Si la longueur de la liaison est supérieure à 7,62m (25 ft), utilisez alors la valve de charge supplémentaire comme indiqué dans le tableau ci-dessous. Cléf Allen Ecrou Prise de Pression Tuyauteries Frigorifiques Unité Extérieure Vannne 3 Voies Unité Intérieure Côté liquide Valve De Deversement Unité Extérieure Fermé Côté gaz Ouvert Pompe a Lo vide Valve De Succion Fermé Hi Fermé 2-10 • Ouvrir le cylindre de gaz et la valve de chargement de basse pression. • Lorsqu’une quantité suffisante de réfrigérant est injectée dans l’unité, fermer le côté basse pression et la valve du cylindre de gaz. • Débrancher le tuyau de service de l’orifice de service. Remettre le bouchon de l’orifice de service. Tableau de complément de charge en grammes (R22) 10 m/32,8 ft 35 35 90 50 60 120 12 m/39,4 ft 65 65 165 90 110 220 15 m/49,2 ft 110 280 185 370 Tableau de complément de charge en grammes (R410A) Modèle 311 301R 10 m/32,8 ft 80 110 12 m/39,4 ft 150 200 Unité Intérieure Côté liquide 15 m/49,2 ft 255 335 Unité Extérieure Valve De Deversement Fermé Opération de chargement Français Modèle 071 / 101 / 151 201 251 / 301 071R / 101R /151R 201R 251R / 301R Côté gaz Cette opération nécessite impérativement l’utilisation d’un cylindre de charge ou une balance de précision. Le complement de charge se fait sur l’unité extérieure par la vanne d’aspiration via la prise de pression de la vanne de service. • Enlever le bouchon de la vanne de service. • Raccorder le côté de basse pression de la jauge de chargement à l’orifice de succion du réservoir cylindrique et fermer le côté de haute pression de la jauge. Éliminer l’air du tuyau de service. • Mettre le climatisateur en marche. Valve De Succion Valve De Contröle Fermé Lo Ouvert Hi Fermé L’INDICATEUR S’ALLUME IR Récepteur de signal Module refroidisseur Lorsqu’un signal d’opération à infrarouge a été transmis, le récepteur de signal de l’unité intérieure émet un <bip> pour confirmer l’acceptation de transmission du signal. Le tableau montre que l’indicateur LED s’allume pour l’air climatisé dans des conditions de fonctionnements normales et par défaut. Les leds de visualisation apparaissent lorsque le climatseur est sous tension, dans la fenêtre de couleur bleu foncé située dans la partie inférieure droite du climatiseur. L’indicateur LED s’allume pour l’unité de refroidissement IR Récepteur De Signal Interrupteur Minuterie Mode déshumidification Mode de sommeil LED De Visualisation L’indicateur LED s’allume: Conditions de fonctionnement normales et par défaut pour l’unité de refroidissement Interrupteur Déshumidi -fication Minuterie Mode de Sommeil Opération / Indication de panne Action Minuterie en marche. – Mode de sommeil. – Mode déshumidification. – Risque de prise en glace. Nettoyer le filtre puis passer en grande vitesse. Continuellement uni fois toutes les 2 secondes Défaut de la sonde de reprise d’air lâchement/court. Contacter votre revendeur. deux fois toutes les 2 secondes Défaut sonde de l’unité intérieure lâchement / court. Contacter votre revendeur. Détecteur de problèmes de contact, protection de surcharge du compresseur ou fuite de gaz. Contacter votre revendeur. trois fois toutes les 2 secondes LED Allumée LED Allumée ou Éteinte 2-11 LED Clignotante L’indicateur LED s’allume pour l’unité de pompe à chaleur Module pompe à chaleur Le tableau ci-dessous reprend en détail la visualisation par led, des conditions normales de fonctionnement, et conditions de défaut du climatiseur. Les led de visualisation apparaissent lorsque le climatseur est sous tension, dans la fenêtre de couleur bleu foncé située dans la partie inférieure droite du climatiseur. L’unité de pompe de chaleur est équipée d’un mode “auto”; l’unité fournira une température ambiante raisonnable en faisant passer l’unité automatiquement au mode “refroidissement” ou au mode “chaleur”, selon la température réglée par l’utilisateur. Mode refroidissement Mode de déshumidification Mode chaleur/ ventilateur (rouge/vert) Mode de sommeil L’indicateur LED s’allume: Conditions de fonctionnement normales et par défaut pour l’unité de pompe à chaleur Froid Déshumidification Ventilation Chaleur Mode de Sommeil Fonctionnement normales/défaut Action Mode refroidissement. – Mode déshumidification. – Mode ventilation. – Mode chauffage. – Mode chauffage automatique. – Mode refroidissement automatique. – Dégivrage. – Défaut de protection thermique compresseur. Défaut sonde de l’unité intérieure Contacter votre revendeur. Contacter votre revendeur. lâchement / court. Défaut sonde de l’unité extérieure. Défaut de la sonde de reprise Contacter votre revendeur. Contacter votre revendeur. d’air lâchement/court. Si le climatiseur est en mode “froid” ou “chaud” (avec fonction “réduit de nuit” à l’arrêt) la sonde peut avoir un problème de contact, la protection interne compresseur HS ou une fuite de réfrigérant. LED Allumée LED Allumée ou Éteinte 2-12 LED Clignotante Déshumidification Prévention de givrage • Lorsque le taux d’humidité de l’air est élevé, le climatiseur peut fonctionner en mode de déshumidification. Appuyer sur la touche <MODE> et sélectionner <DRY>. • Au cas où la température de la pièce est de 2°C/35,6°F supérieure à la température affichée, le climatiseur - avant de passer en mode de déshumidification - fonctionnera en mode de refroidissement jusqu’à ce que la température soit retombée dans la limite des 2°C/35,6°F de différence par rapport à la température affichée. • Si la température de la pièce se trouve dans la limite des 2°C/35,6°F de différence par rapport à la température affichée, l’appareil fonctionnera directement en mode de déshumidification. • En mode de déshumidification, l’appareil fonctionne à faible vitesse de ventilation. • Quand le filtre à air est encrassé, le température d’évaporation diminue et finit par causer la formation de givre. • Le voyant lumineux correspondant va alors clignoter pour signaler que le filtre est encrassé. Si la température d’évaporation descend à -2°C/28,4°F, l’appareil se coupe et se met en mode de dégivrage. Vitesse de ventilation et capacité nominale de refroidissement • La capacité nominale de refroidissement peut être atteinte en vitesse de ventilation maximum. • La capacité de refroidissement est plus faible lorsque l’appareil fonctionne en vitesse de ventilation moyenne ou faible. Chauffage (concerne seulement la pompe à chaleur) Horizontale Refroidissement Déshumidification • Lorsque l’appareil est mis en marche à froid ou après un cycle de dégivrage, le ventilateur intérieur se mettra à tourner seulement une fois que le serpentin aura atteint la température souhaitée. • Lorsque la température souhaitée est atteinte, le ventilateur intérieur tournera jusqu’à ce que le serpentin ne puisse plus fournir de chaleur supplémentaire. 25°C/77°F Contrôle du débit d’air horizontal • Pour obtenir une meilleure circulation d’air, vous pouvez ajuster la grille de refoulement d’air froid vers la gauche ou vers la droite à la main. • Pendant le fonctionnement en mode froid ou déshumidification, il n’y a pas un refoulement d’air froid pendant un long moment vers le bas. Car il pourrait se produire de la condensation sur les volets d’air suivi d'un écoulement d’eau. Subsitance Chaude (seulement pour la thermopompe) HOT KEEP OFF • • Durant la coupure du compresseur, le moteur du ventilateur intérieur peut être mis en marche sur la position: (i) ON (Allume) (par défaut) ou (ii) OFF (Eteint) ou (iii) ON et OFF (Intervalle en Allume et Eteint) par intermittence en réglant l’interrupteur à coulisse comme indiqué sur le diagramme. L'interrupteur est situé sur le cadre frontal (près de l'interrupteur ON/OFF). INTERVAL ON l'interrupteur ON/OFF REMARQUE: Quand l’option est choisie, l’alimentation d’énergieen nécessité d’unité d’être remis à zéro afin d’activer la fonction. Protection contre la surchauffe (concerne seulement la pompe à chaleur) • Au cas où la température intérieure et/ou extérieure est trop élevée, ou que le filtre est encrassé et bouché, le réfrigérant risque de surchauffer. C’est pourquoi le compresseur se coupe lorsque la température de condensation atteint 62°C/143,6°F. 2-13 Français OPÉRATION DU CLIMATISEUR CONDITIONS STANDARD DE FONCTIONNEMENT Module pompe à chaleur Module refroidisseur Ts °C/°F Th °C/°F Ts °C/°F Th °C/°F 19,4 / 66,9 13,9 / 57,0 26,7 / 80,1 19,4 / 66,9 Température intérieure maximum extérieure minimum 19,4 / 66,9 13,9 / 57,0 extérieure minimum -8 / 17,6 -9 / 15,8 Température extérieure maximum 46 / 114,8 24 / 75,2 Température extérieure maximum 24 / 75,2 18 / 64,4 Température Température intérieure minimum Température intérieure maximum Température Température Température intérieure minimum Température 10 / 50 – 26,7 / 80,1 – Ts: Température au thermomètre sec. Th: Température au thermomètre mouillé. ! Attention • Couper l’alimentation du secteur avant d’effectuer l’entretien du climatiseur. • NE PAS DÉBRANCHER le cordon électrique lorsqu’il y a du courant. Ceci pourrait provoquer des décharges électriques avec pour résultat des risques d’incendie. FILTRE ÉLECTROSTATIQUE CADRE A FILTRE ET MATÉRIEL DE FILTRE ÉLECTROSTATIQUE DOUBLE ACTION PURIFICATEUR D’AIR ET DÉSODORISANT ACTION 2FILTRE DESODORISANT ACTION 1FILTRE PURIFICATEUR D’AIR ELECTROSTATIQUE Débarrassez l’air des odeurs gênantes et conservez l’air de la pièce frais à l’aide du filtre de carbone activé. Otez la poussière microscopique, la fumée et les petites particules invisibles à l’aide d’un filtre polypropylène électrostatique pour garder l’air de la pièce proper. INSTALLATION Ouverzle le grillage du cadre avant. Inserez dans la fente les filtres a double action electrostatique et desodorisant. Sortez les filtres d'origine en les faisant glisser. Replacez le filtre d'origine. 2-14 ! Avertissement ! Attention • • Couper l’alimentation du secteur avant d’effectuer l’entretien du climatiseur. NE PAS DÉBRANCHER le cordon électrique lorsqu’il y a du courant. Ceci pourrait provoquer des décharges électriques avec pour résultat des risques d’incendie. ENTRETIEN ET MAINTENANCE Pieces A Entretenir Filtre à air intérieur Unité intérieure Procédure D’Entretien Périodicité 1. Enlever la poussière du filtre à l’aide d’un aspirateur ou en lavant le filtre à l’eau tiède (moins de 40°C/104°F) avec un détergent neutre. 2. Bien rincer et sécher le filtre avant de le remettre en place. 3. Ne pas utiliser de gasoil, de substances volatiles ou autres produits chimiques pour nettoyer le filtre. Au moins une fois toutes les 2 semaines. 1. Nettoyer la grille et le panneau en les essuyant avec un chiffon doux mouillé à l’eau tiède (moins de 40°C/104°F) et un détergent neutre. 2. Ne pas utiliser de gasoil, de substances volatiles ou autres produits chimiques pour nettoyer l’unité intérieure. Au moins une fois toutes les 2 semaines. Plus souvent si nécessaire. Plus souvent si nécessaire. ! Avertissement Ne pas utiliser d’appareil de chauffage à proximité du climatiseur. La chaleur excessive pourrait faire fondre ou déformer le panneau en plastique. MISE A L’ARRÊT PROLONGUE DU CLIMATISEUR Faites fonctionner l’unité pendant 2 heures sur les réglages suivants: Mode de fonctionnement : froid Température : 30˚C/86˚F Retirer la prise du secteur. Si vous utilisez un circuit électrique unique pour le climatiseur, coupez le circuit. Enlever les piles de la télécommande. 2-15 Français 3. Le filtre est une pièce de rechange que vous trouverez chez votre détaillant d’unités d’air climatisé. 4. Utilisez le nouveau filtre immédiatement une fois qu’il a été sorti de son emballage hermétique. Ne sortez pas le nouveau filtre trop tôt avant de l’utiliser, ceci peut diminuer son effet désodorisant. 1. Le filtre désodorisant et purificateur d’air électrostatique doit être remplacé tous les 6 mois ou quand la couleur du filtre devient marron, suivant ce qui se produit en premier. 2. Les filtres usagés poussiéreux doivent être jetés et ne peuvent être réutilisés, même si le filtre a été nettoyé et lavé. ANALYSE DES CAUSES DE DYSFONCTIONNEMENT DU CLIMATISEUR En cas de dysfonctionnement du climatiseur, couper aussitôt l’alimentation électrique. Vérifier ensuite les points suivants pour détecter la nature et les causes de la panne. Defauts Causes / Action 1. Le compresseur ne démarre pas 3 minutes après la mise en marche du climatiseur. - Protection contre les démarrages fréquents. Laisser 3 à 4 minutes au compresseur pour démarrer. 2. Le climatiseur ne fonctionne pas. - Le circuit est peut être coupé ou un fusible est à changer. - La prise de courant est peut être débranchée. - La programmation de mise en marche/arrêt est peut-être mal réglée. - Si la panne persiste après ces vérifications, contacter l’installateur. 3. Le flux d’air est trop faible. - 4. L’air dégagé a une mauvaise odeur. - Les odeurs peuvent provenir de fumées de cigarettes, parfums ou autres particules adhérants au refroidisseur. 5. Condensation sur la grille frontale de l’unité intérieure. - La condensation est due à l’humidité de l’air après une période de fonctionnement prolongée. - La température affichée est trop basse; augmenter la température et faire tourner l’appareil à vitesse de ventilation élevée. 6. Ecoulement d’eau du climatiseur. - Éteindre le climatisateur et appeler le concessionnaire. 7. Bruit de chuintement venant du climatiseur. - Le fluide réfrigérant coule dans le serpentin de l’évaporateur. Le filtre à air est sale. Les portes ou les fenêtres sont ouvertes. Les entrées et sorties d’air sont bouchées. La température réglée n’est pas assez élevée. Si les pannes persistent, appeler votre revendeur ou le service après-vente. 2-16 MONTAGEANLEITUNG Das vorliegende Handbuch enthält die Installationsanweisungen für einen sicheren und ordnungsgemäßen Betrieb dieser Anlage. Je nach den örtlichen Gegebenheiten können spezielle Anpassungen notwendig sein. Vor der Inbetriebnahme des Klimagerätes dieses Handbuch bitte aufmerksam zur Kenntnis nehmen und für künftigen Bedarf aufbewahren. Deutsch DOPPELFUNKTIONS-KLIMAGERÄT, ANDMONTIERT MODELL KÜHLFUNKTION (R22) WÄRMEPUMPE (R22) Bezugsmodell Modell Bezugsmodell Modell WM301 SL30C SL30B AWM301 ALC30C ALC30B WM301R SL30CR SL30BR AWM301R ALC30CR ALC30BR KÜHLFUNKTION (R410A) WÄRMEPUMPE (R410A) Bezugsmodell Modell Bezugsmodell Modell 5WM311 5SL28C A5WM311 A5LC28C 5WM301R 5SL28CR A5WM301R A5LC28CR IM-WM1-0302(2)-Acson Part No.: A08019025521 3-1 INHALT - Auslegung und Admessung - Vorsichtmassnahmen - Installationsdiagramm - Installation des Außengerätes - Installation der Öffnungsrohrleitung - Installation des Innengerätes - Kühlmittelleitung - Kabelanschluß seite i-ii seite 2 seite 3 seite 3 seite 4 seite 6 seite 7 seite 8 - Besondere Vorsichtsmassnahmen, Beim R410A Einheit seite 10 - Vakuum und Aufladen seite 10 - Betriebsleuchtanzeige seite 11 - Bedienung des Klimagerätes seite 13 - Standard-Betriebsbedingung seite 14 - Elektrostatikfilter seite 14 - Instandhaltung und Wartung seite 15 - Störungs-Behebung seite 16 VORSICHTMASSNAHMEN Vor der Installation sind nachfolgende Sicherheitsmaßnahmen aufmerksam zur Kenntnis zu nehmen. ! Achtung • Die Installation und Wartung muß durch qualifizietes Personal erfolgen, Welches mit den örtlichen Bestimmungen und diesem Ausrüstungstyp vertraut ist. • Die gesamte E-Verkabelung hat in Übereinstimmung mit den landesspezifischen Anschlußvorschriften zu erfolgen. • Vor dem Kabelanschluß gemäß Schaltbild ist sicherzustellen, daß die Betriebsspannung mit der auf dem Datenschild des Gerätes angegebenen Spannung übereinstimmt. • Das Gerät ist zum Schutz gegen fehlerhafte Isolierungen und entsprechende Risiken zu ERDEN. • Die Kabel dürfen weder mit der Kühlmittelleitung, noch mit dem Kompressor oder den beweglichen Teilen der Gebläsemotoren in Berührung kommen. • Vor der Installation oder Wartung der Anlage ist sicherzustellen, daß das Gerät ausgeschaltet ist (OFF). WICHTIG DAS KLIMAGERÄT SOLLTE NICHT IN EINEM WÄSCHERAUM INSTALLIERT ODER BENUTZT WERDEN. ! Vorsicht Vor der Installation sind folgende wichtige Punkte zu prüfen. • Gerät nicht installieren, falls ein Leck entzündbaren Gases festgestellt wird. Es besteht Feuergefahr, wenn Gas aus der Anlage entweicht und sich in der Umgebung ansammelt. • Die Kondensat-Abflußleitung muß sachgemäß angeschlossen sein. Ist die Abflußleitung nicht richtig angeschlossen, besteht Gefahr, daß durch auslaufendes Wasser das Mobiliar feucht wird. • Gerät nicht überlasten. Das Gerät ist werkseitig vorgefüllt. Im Falle einer Überfüllung besteht die Gefahr einer Überbelastung oder sonstigen Beschädigung des Kompressors. • Nach Installation oder Wartung ist sicherzustellen, daß die Geräteabdeckung wieder montiert ist. Eine mangelhafte Befestigung der Abdeckung führt zu Geräuschentwicklung während des Betriebs. 3-2 INSTALLATIONSDIAGRAMM INNEN-GERÄT LUFTFILTER VORDERER RAHMEN RÜCKWÄRTIGES GEHÄUSE LUFTEINLASSGITTER EIN-/AUS- SCHALTER ABLAUFSCHLAUCH LEUCHTANZEIGE ABLUFTAUFSATZ IR-EMPFÄNGER Deutsch ABLUFTGITTER LUFTEINLASS KÄLTEMITTELLEITUNG LUFTEINLASS LUFTAUSLASSDÜSE AUßEN-GERÄT B Wandelement A Auslassluft Wandelement Die Außenmontage-Einheit ist so zu installieren, daß die Luftzirkulation an keiner Stelle beeinträchtigt oder durch ein Hindernis am Abströmen gehindert wird. Auf Einhaltung der nachstehend gezeigten Mindestabstände achten. Auszuwählen ist die jeweils kühlste Stelle, an der die Einlaßlufttemperatur nicht die Außentemperatur überschreitet (maximal 45°C/113°F). Luftzufuhr INSTALLATION DES AUßENGERÄTES C D 300 (11,8) 1000 (39,4) 300 (11,8) 500 19,7 Anmerkung: Bei einem Hindernis von über 2m oder soweit sich irgendein Hindernis im oberen Bereich der Einheit befindet, muß der in obenstehender Tabelle aufgeführte Abstand entsprechend vergrößert werden. 3-3 C D Wandelement B Wartungs-Offnung Mindest Entfernung, mm A Wandelement Abmessung Luftzufuhr Montageabstand INSTALLATION DER ÖFFNUNGSROHRLEITUNG Ablassrohr 2 3 4 1 Außengerät Innenräume 1 Ablassstück 3 3/8" - Schraubenmutter 2 Verbindungsrohr 4 3/8" - Sechskanthohlschraube Anmerkung: Dieses Einbauverfahren bezieht sich nur auf die Modelle WM301 / SL30B & WM301 / SL30C ! Vorsicht Das Ablassrohr muss, wie oben erläutert, in die richtige Richtung eingebaut werden. Ein falscher Einbau kann Schäden im Betriebssystem verursachen. A. Öffnungsrohrleitung des Außengerätes (wo der Installationsraum weit genug ist) Schritt 2 Ablassrohr Schritt 1 Schritte: 1. Verbinden Sie die Schraubenmutter des Ablassrohres direkt mit dem Flüssigkeitsventil. 2. Bringen Sie das Flüssigkeitsrohr an und verbinden Sie es mit der Hohlschraube des Auslassrohres. Flüssigkeitsrohr Ablassrohr 3-4 B. Öffnungsrohrleitung des Außengerätes (wo der installationsraum beschränkt ist) Schritt 4 Ablassrohr Schritt 3 Schritt 2 Schritt 1 Wenn das Ablassrohr aufgrund von Platzmangel nicht direkt mit dem Flüssigkeitsventil verbunden werden kann, kann es entlang des Flüssigkeitsrohres eingebaut werden. Schritte: 1. Bringen Sie das Flüssigkeitsrohr an und verbinden Sie es mit dem Flüssigkeitsventil. Flüssigkeitsrohr 2. Schweißen Sie eine zusätzliche Hohlschraubenverbindung an das Flüssigkeitsrohr. Ablassrohr 4. Bringen Sie ein weiteres Flüssigkeitsrohr an und verbinden Sie es mit dem Gewinde des Auslassrohres. Flüssigkeitsrohr Flüssigkeitsrohr Ablassrohr Schweißgerät C. Installation der Öffnungsrohrleitung Innen-Gerät Ablassrohr Schritte: 1. Schweißen Sie eine zusätzliche Hohlschraubenverbindung an das Flüssigkeitsrohr. 2. Verbinden Sie die Schraubenmutter des Ablassrohres mit der Hohlschraube. Flüssigkeitsrohr 3. Bringen Sie ein weiteres Flüssigkeitsrohr an und verbinden Sie es mit dem Gewinde des Auslassrohres. Ablassrohr Flüssigkeitsrohr Flüssigkeitsrohr Ablassrohr Schweißgerät 3-5 Deutsch 3. Verbinden Sie die Schraubenmutter des Ablassrohres mit der Hohlschraube. INSTALLATION DES INNENGERÄTES Die Kühlmittel-Rohrleitung kann an die Einheit auf verschiedene Weise angeschlossen werden (auf der Rückseite links oder rechts der Einheit). Hierzu sind die Aussparungen der Gërateverkleidung zu verwenden (siehe Abb.). Die Rohre vorsichtig auf die entsprechenden Lochpositionen biegen. Bei einem rechtseitigen bzw. bei einem Anschluß auf der Rückseite das Rohrleitungsende festhalten und in die entsprechende Richtung positionsgerecht biegen (siehe Abb.). Der Kondensat-Drainageschlauch ist an die Rohrleitungen anzupassen. Innengeräte sind so zu installieren, daß keine Interferenz zwischen dem Kühlluftaustritt und der zurückgeführten Luft besteht. Bei der Installation bitte die in der Zeichnung angegebenen Abstände beachten. Ein Innenmontage-Gerät darf nicht unter direkter Sonneneinstrahlung montiert werden. Die Montageposition ist anhand der Rohrleitung und der Drainage im gegebenen Abstand zu Türen oder Fenstern zu gewährleisten. 50mm 50mm 50mm Verlegungsrichtung Rechts Und Hinten Oberhalb der Augenhöhe Richtung Des Luftstroms Zwischenraum Für Wartung Und Pflege Montageplatte Gerätemontage auf der installationsplatte Innenmontage-Gerät in den oberen Bereich der Installationsplatte einhängen. (Die beiden hinteren oberen Laschen der Innenmontage-Einheit in die obere Kante der Installationsplatte einhängen). Bewegen Sie die Montageplatte leicht nach links und rechts, um zu prüfen, ob die Haken ordnungsgemäß eingegriffen haben. Markierung-offline Gewinde Montage der installations-halterungsplatte Sicherstellen, daß die Trägerwand ausreichend fest ist, um das Gewicht aufnehmen zu können. Falls nicht, müssen geeignete Vertärkungsplatten, Träger oder Stützen verwendet werden. Beim Anbringen des Geräts eine Wasserwaage benutzen, sodann das Gerät mit 4 geeigneten Schrauben befestigen. Bei Rohrleitungs-herausführung auf der Rückseite: Eine Bohrung 65 mm mit einem Konusbohrer setzen. Hierbei die Bohrung auf der wandungsaußenseite etwas tiefer positionieren (seihe Abb.). Innen Verbindungs-kabel Ablaufschlauch Wasser-entleerungsleitung Zur problemlosen Kondensatabführung muß die innenliegende Wasserentleerungsleitung Gefälle aufweisen. Vermeiden Sie Umstände, die zum Austreten von Wasser führen können. Außen Wasserablauf 1/50 Neigung Verlegungsrichtung Der Rohrleitungen Die Schraube entfernen, die die Vorderabdeckung hält. WasserLeck 3 2 1 Verlegungsrichtung Der Rohrleitungen 4 5 3-6 In Wasser EintauChendes Rohrende WasserLeck WasserLeck j ✓ J J J Korrekt Falsch Falsch Falsch KÜHLMITTELLEITUNG ! Vorsicht Nur im Kühlgerät WM 301 wird eine Öffnung als Ausdehnungsvorrichtung verwendet. Beim Innengerät ist diese im Flüssigkeitsrohr festgemacht. Leitungslänge und Höhenmaß Zuschneiden Des Kupferrohres Bei zu langer Rohrleitung führt dies zu mangelnder Kapazität und Zuverlässigkeit des Gerätes. Mit zunehmender Bögenanzahl steigt der Kältemittelstrom im System an, führt dadurch zu einer verminderten Kühlkapazität und verursacht u.U. eine Störung des Kompressors. Immer den kürzesten Leitungsweg unter Beachtung nachstehender Empfehlungen wählen: 07/10 15 20 25 30 12 (39,4) 12 (39,4) 15 (49,2) 15 (49,2) 35 Maximale Höhe, m (ft), H 5 (16,4) 5 (16,4) Maximale Bogenanzahl 8 (26,2) (114,8) 8 (26,2) 15 (49,2) 10 10 10 10 10 Flüssigkeitsleitungs-Durchm 1/4" 1/4" 1/4" 3/8" 3/8" Gasleitungs-Durchm 3/8" 1/2" 5/8" 5/8" 5/8" Deutsch Modell Maximale Länge, m (ft), L Rohrentgratung Kupferrohr Stauchblock Anmerkung: Für Außenmontage-Geräte wird werkseitig eine Kältemittelcharge hinsichtlich einer Rohrleitungslänge von 7,62 m/25ft vorgenommen. Innen-Gerät Geräte-rohranschluss • • L Rohrleitung zentrieren und Gegenmutter des aufgeweiteten Rohrstückes mit der Hand anziehen. Abschließend Gewindemutter und Moment-schlüssel bis an die gewünschte Moment-Einraststelle anziehen. Rohrgröße mm / (zoll) 6,35 (1/4) 9,53 (3/8) 12,7 (1/2) 15,88 (5/8) H Anzugsmoment Nm / (Ft-lb) 18 (13,3) 42 (31,0) 55 (40,6) 65 (48,0) Ø Rohr, D Außen-Gerät Verlegen Und Anschliessen Der Leitungsrohre • • • • • • • Keine verschmutzten oder beschädigten Kupferrohre verwenden. Plastikabdeckungen, Gummistopfen oder Messinggewinde sollen nicht von den Ventilen, Armaturen, Rohrleitungen oder den Heiz- und Kälteschlangen entfernt werden, bis die Ansaug- bzw. Flüssigkeitsleitung anschlussbereit ist. Falls Lötarbeiten vorzunehmen sind, sicherstellen, daß Während des Lötens Stickstoff durch die Wärmetauscher und Kupplungen gerührt wird. Dadurch werden Rußablagerungen auf den Kupferrohr-Innenwandungen vermieden. Das Verbingungsrohr mit einem Rohrschneider abschneiden. Die Rohrkanten mit einer Reibahle entgraten. Das Rohrende dabei nach unten halten, damit keine Metallpartikel in das Rohr gelangen. Die Gewindeüberwurfteile an den Armaturen des Innen- und Außengerätes auf die Kupferrohre ziehen. Das hinter dem Aufweitungswekzeug überstehende Rohrende soweit aufweiten, wie in der Tabelle gezeigt. Die aufgeweitete Kante soll glatt sein und weder Kratzer noch Sprünge aufweisen. A (mm) Zoll mm Aufgeweite Starr 1/4" 3/8" 1/2" 5/8" 6,35 9,52 12,70 15,88 1,3 1,6 1,9 2,2 0,7 1,0 1,3 1,7 Anzugsring Innenmontagerohr Anzugsschlüssel 3-7 Aufgeweitetes Rohr Gewindeüberwurf Drehmomentschlüssel KABELANSCHLUß Kühleinheit WICHTIG : * Die angegeben Werte sind lediglich Richtwerte. Sie sind zu überprüfen und ggf. den örtlichen und/ oderlandesspezifischen Vorschriften und Bestimmungen anzugleichen. Des weiteren sind sie abhängig von der Installationsart und dem Adernquerschnitt. ** Der geeignete Spannungsbereich sollte den Etikettdaten auf der Einheit entnommen werden. ETL verzeichnete Daten gelten nur für einen 60Hz Netzanschluss. Modell Innen-Gerät Außen-Gerät WM 071/ 101/ 151 SL07/ 10/ 15B Spannungsbereich** WM201/ 251/ 301 SL20/ 25/ 30B 220V-240V/ 1Ph/ 50Hz + 5WM311 5SL28C WM301 SL30C oder 208V-230V/ 1Ph/ 60Hz + WM201/ 251/ 301 SL20/ 25/ 30B WM301 SL30C 380V-415V/ 3Ph/ 50Hz +N+ Zuleitungskabelquerschnitt* Adernanzahl mm2 1,5 3 2,5 3 2,5 3 4 3 1,5 5 1,5 5 Zwischenkabelquerschnitt* Adernanzahl mm2 1,5 3 2,5 3 2,5 3 2,5 4 1,5 4 1,5 4 A 15 20 20 25 15 15 Empfohlene Sicherung WM301 VS SL30C WM07 / 10 / 15 / 20 / 25 / 301 VS SL07 / 10 / 15 / 20 / 25 / 30B 5WM311 VS 5SL28C Innen-GerätAußen-GerätKlemmenblock Klemmenblock Innen-GerätKlemmenblock Außen-GerätKlemmenblock L COMP N COMP COMP N2 N N2 S N1 R N1 L COMP L L Anschluss-Kabel Anschluss-Kabel ! N ! Die Stromversorgung muß mit Schutzeinrichtungen ausgestattet sein (Leitungsunterbrecher oder Sicherung). Vorzusehen ist ein 2-Pol-Schutzschalter mit einem Mindestkontak-tabstand von 3mm. WM201 / 251 VS SL20 / 25B (3 Phase) Innen-GerätKlemmenblock Die Stromversorgung muß mit Schutzeinrichtungen ausgestattet sein (Leitungsunterbrecher oder Sicherung). Vorzusehen ist ein 2-Pol-Schutzschalter mit einem Mindestkontak-tabstand von 3mm. WM301 VS SL30C (3 Phase) Außen-GerätKlemmenblock Innen-GerätKlemmenblock COMP Außen-GerätKlemmenblock COMP COMP L COMP L N2 N N2 N N1 N1 R L L R S S T Anschluss-Kabel Anschluss-Kabel N T N ! Die Stromversorgung muß mit Schutzeinrichtungen ausgestattet sein (Leitungsunterbrecher oder Sicherung). Vorzusehen ist ein 2-Pol-Schutzschalter mit einem Mindestkontak-tabstand von 3mm. ! Die Stromversorgung muß mit Schutzeinrichtungen ausgestattet sein (Leitungsunterbrecher oder Sicherung). Vorzusehen ist ein 2-Pol-Schutzschalter mit einem Mindestkontak-tabstand von 3mm. • Alle Adern sind fest zu verdrahten. • Jeglicher Kontakt einer Elektrokabelader mit der Kältemittelleitung, dem Kompressor oder anderen beweglichen Teilen des Gebläsemotors ist zu vermeiden. • Die Anschlußadern zwischen Außen- und Innenmontage-Gerät sind gem. Klemmbrücke gegen Abziehen zu sichern. • Das Anschlusskabel muss zumindest dem H05RN-F (245 IEC57) entsprechen. Drahtklemme Verbindungskabel 3-8 Wärmepumpe WICHTIG : * Die angegeben Werte sind lediglich Richtwerte. Sie sind zu überprüfen und ggf. den örtlichen und/ oderlandesspezifischen Vorschriften und Bestimmungen anzugleichen. Des weiteren sind sie abhängig von der Installationsart und dem Adernquerschnitt. ** Der geeignete Spannungsbereich sollte den Etikettdaten auf der Einheit entnommen werden. ETL verzeichnete Daten gelten nur für einen 60Hz Netzanschluss. Innen-Gerät WM 071/ 101/ 151 R WM201/ 251/ 301 R 5WM301R WM301 R WM201/ 251/ 301 R WM301 R Außen-Gerät SL07/ 10/ 15BR SL20/ 25/ 30BR 5SL28CR SL30CR SL20/ 25/ 30BR SL30CR Spannungsbereich** 220V-240V/ 1Ph/ 50Hz + oder 208V-230V/ 1Ph/ 60Hz + 380V-415V/ 3Ph/ 50Hz +N+ Zuleitungskabelquerschnitt* Adernanzahl mm2 1,5 3 2,5 3 2,5 3 4 3 1,5 5 1,5 5 Zwischenkabelquerschnitt* Adernanzahl mm2 1,5 5 2,5 5 2,5 5 2,5 6 1,5 6 1,5 4 A 15 20 20 25 15 15 Empfohlene Sicherung WM301R VS SL30CR WM07 / 10 / 15 / 20 / 25 / 301R VS SL07 / 10 / 15 / 20 / 25 / 30BR 5WM301R VS 5SL28CR Aussen-Sensor Spulenanschlussader (Länge 8m), Verbunden Mit Dem Außen-GerätInnenmontagegerät. Klemmenblock Innen-Gerät- Aussen-Sensor Spulenanschlussader (Länge 8m), Verbunden Mit Dem Innenmontagegerät. Innen-GerätAußen-GerätKlemmenblock Klemmenblock 4WV 4WV OF OF COMP COMP Klemmenblock N2 N1 N A 4WV 4WV OF OF COMP COMP N2 L N1 N L L Anschluss-Kabel Anschluss-Kabel N L ! Die Stromversorgung muß mit Schutzeinrichtungen ausgestattet sein (Leitungsunterbrecher oder Sicherung). Vorzusehen ist ein 2-Pol-Schutzschalter mit einem Mindestkontak-tabstand von 3mm. ! WM201 / 251R VS SL20 / 25BR (3 Phase) Die Stromversorgung muß mit Schutzeinrichtungen ausgestattet sein (Leitungsunterbrecher oder Sicherung). Vorzusehen ist ein 2-Pol-Schutzschalter mit einem Mindestkontak-tabstand von 3mm. WM301R VS SL30CR (3 Phase) Aussen-Sensor Spulenanschlussader (Länge 8m), Verbunden Mit Dem Außen-GerätInnenmontagegerät. Klemmenblock Innen-GerätA Klemmenblock Aussen-Sensor Spulenanschlussader (Länge 8m), Verbunden Mit Dem Innenmontagegerät. Innen-GerätAußen-GerätKlemmenblock Klemmenblock 4WV 4WV OF OF COMP COMP N2 L N2 L N1 N N1 N 4WV 4WV OF OF COMP COMP L L R R S Anschluss-Kabel S T T Anschluss-Kabel N ! ! Die Stromversorgung muß mit Schutzeinrichtungen ausgestattet sein (Lei-tungsunterbrecher oder Sicherung). Vorzusehen ist ein 2-Pol-Schutzschalter mit einem Mindestkontak-tabstand von 3mm. 3-9 Die Stromversorgung muß mit Schutzeinrichtungen ausgestattet sein (Leitungsunterbrecher oder Sicherung). Vorzusehen ist ein 2-Pol-Schutzschalter mit einem Mindestkontak-tabstand von 3mm. N Deutsch Modell BESONDERE VORSICHTSMASSNAHMEN, BEIM R410A EINHEIT • • • • • • R410A ist ein nahezu azeotropes Kühlmittelgemisch aus Hydrofluorkohlenwasserstoff (HFC), welches umweltfreundlich ist. Es hat ein Ozonabbaupotential von 0 (ODP = 0) und entspricht dem Montreal-Protokoll. Es hat keine Flammenausbreitung und ein schwach toxisches Kühlmittel (von ARI als A1 eingestuft). R410A ist eine Mischung aus R32 (50%) und R125 (50%). POE Öl wird als Schmiermittel für R410A Kompressor benutzt, der verschieden vom Erdöl ist, das für R22 Kompressor benutzt wird. Während Installation oder Wartung muß zusätzliche Vorsichtsmaßnahme nicht genommen werden, das R410A System zu entblößen, das zu lang ist zu feuchter Luft. Restlich POE Öl in der Rohrleitung und die Bauteile können Feuchtigkeit von der Luft absorbieren. Refrigerant R410A wird leichter von Staub der Feuchtigkeit im Vergleich zu R22 beeinflußt, vergewissert sich vorübergehend, die Enden priop des Schlauchs zu Installation zu bedecken. Keine additonal Aufladung des Kompressoröls wird die Erlaubnis gehabt. Kein ander refrigerant anders als R410A. Werkzeuge ausdrücklich für R410A nur. i) Mannigfaltiges Meßgerät und ladenden Schlauch ii) Gas Leck Detektor iii) Refrigerant Zylinder Laden Zylinder iv) Vakuumpumpe C/W Adapter v) Leuchtsignal Werkzeuge vi) Refrigerant Rückgewinnung Maschine ! VORSICHT • • • R410A muß als flüssig geladen werden. Gewöhnlich wird R410A Zylinder mit einem Soße Rohr für flüssige Rückzüge ausgerüstet. Wenn es kein Soße Rohr gibt, sollte der Zylinder um invertiert werden, flüssig R410A vom Ventil zurückzuziehen. Nicht Macht Auffüllung beim Warten Lecks, als dies die Einheit Leistung verringern wird. Saugen Sie die Einheit gründlich ab und laden Sie dann die Einheit mit frischem R410A gemäß dem Betrag, der in der Spezifikation empfohlen wird. Berühren Sie nicht den Verdichter oder das Kühlrohr, wenn das Kühlgerät in Betrieb ist. Bei Bedarf Schutzhandschuhe tragen. VAKUUM UND AUFLADEN Entlüftung der leitung und des innenmontage Gerätes Gesamttest Das Außenmontage-Gerät ist bereits werkseitig mit Kältemittel befüllt. Falls die Rohrleitung unter 7,62m (25 ft) Länge aufweist, ist eine zusätzliche Kältemittelbefüllung nach der Herstellung desVakuums nicht erforderlich. Wenn die Rohrleitung länger als 7,62m (25 ft) ist, sollte ein zusätzliches Speiseventil gemäß den Angaben in der untenstehenden Tabelle verwendet werden. Mit der Ausnahme des Außenmontage-Gerätes, welches mit dem Kältemittel vorbefüllt ist, müssen das InnenmontageGerät sowie die Kältemittel-Anschlußleitungen entlüftet werden, da Feuchtigkeit im Kühlkreis zu einer Funktionsstörung des Kompressors führen kann. • Die Abdeckungen vom Ventil und dem Wartungsanschluß abnehmen. • Den Lademesser von der Mitte aus an die Vakuumpumpe anschliessen. • Den Lademesser an die Wartungsöffnung des 3-WegVentils anschliessen. • Die Vakuumpumpe einschalten und etwa 30 Minuten laufen lassen. Die Evakuierungszeiten sind je nach Kapazität der Pumpe verschieden. Darauf achten, dass die Nadel des Lademessers bei –76mmHg (0~76mmHg) steht. Achtung Falls die Nadel des Lademessers nicht bei 0 ~76mmHg steht, ist nachzuprüfen (mit dem Kältemittel-Anzeigegerät), ob an der aus dem aufgeweiteten Rohr bestehenden Verbindung zwischen Innen- und Aussengerät ein Gasleck besteht. Vor Ausführen des nächsten Schrittes muss das Leck behoben werden. • Das Ventil des Lademessers schliessen und und die Vakuumpumpe abschalten. • Am Aussengerät das Saugventil (3-Weg-Ventil) und das Flüssigkeitsventil (2-Weg-Ventil) mit einem 4mmSchlüssel für 6-kantige Sackschrauben öffnen (gegen den Uhrzeigersinn). Kältemittel-leitung GewindeÜberwurf Sechskantsteckschlüssel Wartungsanschluss Aussengerät-3Wege-ventil Innen-Gerät Flüssigkeitsleitung Ablaufventil Außen-Gerät Geschlossen Sauggasleitung Saugventil Offen VakuumPumpe Lo Geschlossen Hi Geschlossen 3-10 • Den Gaszylinder und das Niederdruck-Ladeventil öffnen. • Sobald die benötigte Kältemittelmenge in das Gerät eingepumpt ist, werden die Niederdrucköffnung des Lademessers und der Gaszylinder geschlossen. • Den Zulieferschlauch vom Gaszylinder entfernen und dieZylinder-Abdeckung wieder anbringen. Zusatzfüllung in Gramm (R22) Modell 071 / 101 / 151 201 251 / 301 071R / 101R /151R 201R 251R / 301R 10 m/32,8 ft 35 35 90 50 60 120 12 m/39,4 ft 65 65 165 90 110 220 15 m/49,2 ft 110 280 185 370 Zusatzfüllung in Gramm (R410A) Modell 311 301R 10 m/32,8 ft 80 110 Innen-Gerät 12 m/39,4 ft 150 200 Flüssigkeitsleitung 15 m/49,2 ft 255 335 Außen-Gerät Ablaufventil Geschlossen Kältemittel-Zusatzbefüllung Dieser Arbeitsgang erfordert unbedingt den Einsatzeines Gas-Füllzylinders sowie einer Präzisionswaage. Die Zusatzbefüllung erfolgt am Außenmontage-Gerät mithilfe des Ansaugventils und dem Wartungsanschluß. • Abdeckung der Wartungsöffnung entfernen. • Die Niederdrucköffnung des Lademessers an den Ansauganschluss des Gaszylinders anschliessen und die Hochdrucköffnung des Lademessers schliessen. Die verbleibende Luft aus dem Zulieferschlauch entfernen. • Klimaanlage einschalten. Sauggasleitung Saugventil Ventil prüfen Lo Geschlossen Deutsch Offen Geschlossen Hi BETRIEBSLEUCHTANZEIGE Infrarot-Signalempfänger Kühleinheit Wenn von der Infrarot-Fernbedienung ein Signal an das Gerät gesendet wird, bestätigt das Innen-gerät den Empfang mit einem Signalton. Die Tabelle erläutert die Bedeutung der Leuchtdioden für den normalen Betrieb und eventuelle Störungen des Klimageräts. Die LED-Anzeigeleuchten befinden sich auf der rechten unteren Seite des Klimagerätes. Leuchtdiode für Kühlbetrieb Infrarot-Empfanger Strom AN Zeitschalter EntfeuchtungsModus Schlafmodul LED -Funktionsanzeige Leuchtdioden : Normalbetrieb und Störungssituationen des Kühlgeräts Betrieb/Falsche Anzeige Strom Entfeuchtungs Zeitschalter Maßnahme Schlafmodul Zeitschalter AN. – Schlafmodul AN. – Entfeuchtungs-Modus. – Verhindern von Rauhreif. Ununterbrochen Filter reinigen und auf hohe Ventilator-Drehzahl umschalten. Mindestens alle 2 Sekunden. Raum-Luftsensorkontakt unterbrochen/ kurzgeschlossen. Händler benachrichtigen. Zweimal alle 2 Sekunden. Innenmontage-Sensorspule unterbrochen/ kurzgeschlossen. Händler benachrichtigen. Kontaktproblem der Sensoren KompressorenÜberlastschutz Schaltauslösung oder Gasleck Händler benachrichtigen. Drei alle 2 Sekunden. EIN EIN oder AUS 3-11 Blinkend Leuchtdiode für Wärmepumpe Wärmepumpe Nachstehende Tabelle enhält die einzelnen LEDFunktionsanzeigen für Normalbetrieb und die verschiedenen Störungsmeldungen. Die LED-Anzeigeleuchten befinden sich auf der rechten unteren Seite des Klimagerätes. Die Wärmepumpe kann auf automatischen Betrieb (“Auto”) geschaltet werden, so daß sie zwecks Aufrechterhaltung der vom Benutzer voreingestellten Raumtemperatur entweder auf Kühl- oder Heizbetrieb schaltet. Kühlmodus EntfeuchtungsModus Wärme/Gebläse Modul (rot/grün) Schlafmodul Leuchtdioden: Normalbetrieb und Störungssituationen des Leuchtdiode für Wärmepumpe Normalbetrieb/Störungssituationen Kühlen Entfeuchtungs Gebläse Heizen Maßnahme Schlafmodul Kühlmodus. – Entfeuchtungs-Modus. – Gebläsemodus. – Heiz-Modus. – Automatik-Modus in Heizfunktion. – Automatik-Modus in Kühlfunktion. – Enteisung. – Kompressor-Überlastungsschutz. Händler benachrichtigen. Innenmontage-Sensorspule unterbrochen / kurzgeschlossen. Händler benachrichtigen. Aussenmontage-Sensorspule unterbrochen / kurzgeschlossen. Händler benachrichtigen. Raum-Luftsensorkontakt unterbrochen / kurzgeschlossen. Händler benachrichtigen. Befindet sich das System im Kühl- oder Heiz-Modus (mit abgeschalteter SleepFunktion) kann ein Kontaktproblem beim Sensor, eine Auslösung des KompressorÜberlastungsschutzes oder ein Gas-Leck-Problem bestehen. EIN EIN oder AUS 3-12 Blinkend BEDIENUNG DES KLIMAGERÄTES Entfeuchten Vorbeugen von Frostbildung • • • • • Wenn der Luftfilter verschmutzt ist, sinkt die Verdunstungstemperatur und führt schließlich zu Frostbildung. Der Leuchtanzeiger blinkt, um zu melden, daß der Filter verschmutzt ist. Wenn die Verdunstungstemperatur bis auf -2°C/28,4°F fällt, schaltet sich das Gerät aus und entfrostet. Gebläsedrehzahl und vorgesehene Kühlleistung • Die vorgesehene Kühlleistung wird bei maximaler Gebläsedrehzahl erreicht. • Bei mittlerer bzw. langsamer Gebläsedrehzahl liegt die Kühlleistung niedriger. Deutsch • Bei hoher Luftfeuchtigkeit ist das Gerät zum Entfeuchten einsetzbar. Dazu die <MODE>-Taste betätigen und <DRY> anwählen. Liegt die Raumtemperatur um 2°C/35,6˚F höher als die eingestellte Temperatur, arbeitet das Gerät im Kühlbetrieb, bis die Raumtemperatur sich innerhalt von 2°C/35,6˚F Unterschied gegenüber der eingestellten Temperatur befindet, und schaltet anschließend auf Entfeuchten um. Liegt die Raumtemperatur innerhalb von 2°C/35,6˚F Unterschied gegenüber der eingestellten Temperatur, schaltet sich das Gerät direkt auf Entfeuchtung. Bei Entfeuchtung arbeitet das Gerät mit langsamer Gebläsedrehzahl. Heizbetrieb (nur für Wärmepumpe) • Wird das Gerät kalt gestartet oder nach Entfrostung eingeschaltet, setzt das Gebläse am Innengerät sich erst in Gang, wenn der Wärmetauscher die gewünschte Temperatur erreicht hat. Ist die eingestellte Temperatur erreicht, arbeitet das Innengebläse so lange, bis der Wärmetauscher seine maximale Heizkapazität erreicht hat. Waagerecht Kühlen/ Entfeuchtle • 25°C/77°F Horizontale Luftstromsteuerung • • Zur verbesserten Luftzirkulation kann das Abluftgitter nach links oder rechts mit der Hand verstellt werden. Während der Kühl- oder Entfeuchtungs-funktion (cooling/dry) solte das Strömungsrichtungsgitter nicht über einen längeren Zeitraum hin direkt nach unten gerichtet werden. Bei einer längeren Funktion in dieser Einstellung kann sich Kondensat an den Lamellen bilden. Bei einer Kondensatbildung kann es dadurch zu einer Tropfenbildung kommen. Heißer Unterhalt (nur in Bezug auf Wärmepumpe) • • Bei Stillsetzung des Kompressors kann das Kühlgebläse des Innengeräts auf: (i) EIN (Standardeinstellung), oder (ii) AUS, oder (iii) Abstand ein oder aus geschaltet werden durch Einstellen des Gleitschalters, wie in der Zeichnung dargestellt. Die Sprungschaltung ist an der vorderen Rahmenabdeckung angebracht (zusammen mit dem AN/ AUS Schalter). HOT KEEP OFF INTERVAL ON ON/OFF schalter ANMERKUNG:Wenn die Wahl vorgewählt wird, das Spg.Versorgungsteil der Maßeinheit Notwendigkeit zurückgestellt zu werden, um die Funktion zu aktivieren. Überhitzungsschutz (nur für Wärmepumpe) • Wenn die Innen- und/oder Außentemperatur zu hoch liegt, oder der Filter verschmutzt bzw. verstopft ist, besteht Überhitzungsgefahr für das Kältemittel. Darum schaltet sich der Kompressor aus, wenn die Kondenstemperatur 62°C/143,6°F erreicht. 3-13 STANDARD-BETRIEBSBEDINGUNG Wärmepumpe Kühleinheit Temperatur Ts °C/°F Th °C/°F Temperatur Ts °C/°F Th °C/°F MindestInnentemperatur 19,4 / 66,9 13,9 / 57,0 MindestInnentemperatur 10 / 50 - MaximaleInnentemperatur 26,7 / 80,1 19,4 / 66,9 MaximaleInnentemperatur 26,7 / 80,1 - MindestAußentemperatur 19,4 / 66,9 13,9 / 57,0 MindestAußentemperatur -8 / 17,6 -9 / 15,8 Maximale Außentemperatur 46 / 114,8 24 / 75,2 Maximale Außentemperatur 24 / 75,2 18 / 64,4 Ts: Trockenkugel-Temperatur. Th: Feuchtkugeltemperatur. ! Achtung • • Vor Wartung des Klimagerätes das Stromkabel vom Netz trennen. Das Stromkabel nicht herausziehen, wenn das Gerät noch eingeschaltet ist. Ein elektrischer Schlag oder ein Wohnungsbrand können die Folge sein. ELEKTROSTATIKFILTER DOPPELT WIRKENDES FILTERMATERIAL UND FILTERRAHMEN FÜR ELEKTROSTATIKBEHANDLUNG UND LUFTREINIGUNG WIRKUNG 1ELEKTROSTATIKFILTER WIRKUNG 2LUFTREINIGUNGSFILTER Entfernt mikroskopisch feinen Staub, Rauch und unsichtbar kleine Partikel und reinigt die Raumluft fortlaufend mit positiv vorgeladenem elektrostatischem Polypropylenfilter. Entfernt unangenehme Gerüche aus der Umgebungsluft und erfrischt den Raum fortlaufend mit Aktivkohlefilter. INSTALLATIONSANLEITUNG Öffnen sie das vordere rahmengitter Schieben sie die originalfilter heraus Schieben sie den originalfilter zuruck. 3-14 Setzen sie den doppelwirkungsfilter fur die elektrostatikbehandlung und die luftreinigung in den schlitzen. ! Vorsicht 3. Der Filter ist ein Verbrauchsgegenstand, den Sie von ihrem Kimagerätehändler beziehen können. 4. Verwenden Sie das neue Filtermaterial sofort nach Entnahme aus der versiegelten Verpackung. Packen Sie den neuen Filter nicht zu früh vor der tatsächlichen Verwendung aus, da er sonst seine Luftreinigungswirkung verliert. 1. Der Filter für die Elektrostatikbehandlung und die Luftreinigung sollte bei bräunlicher Verfärbung oder spätestens nach 6 Monaten gewechselt werden. 2. Verbrauchte, staubige Filter sollten weggeworfen werden. Sie können auch nach Reinigen und waschen nicht wieder verwendet werden. ! Achtung Vor Wartung des Klimagerätes das Stromkabel vom Netz trennen. Das Stromkabel nicht herausziehen, wenn das Gerät noch eingeschaltet ist. Ein elektrischer Schlag oder ein Wohnungsbrand können die Folge sein. Deutsch • • INSTANDHALTUNG UND WARTUNG Wartungsverfahren Wartungsteile Luftfilter Innen-Gerät Innen-Gerät Intervall 1. Luftfilter mit Staubsauger absaugen oder in lauwarmem Wasser (unter 40°C/ 104˚F) mit neutraler Seife auswaschen. Mindestens alle 2 Wochen. 2. Sorgfältig ausspülen und vor dem Wiedereinsetzen trocknen. 3. Weder Benzin, noch Verdünner oder sonstige Chemikalien zum Reinigen verwenden. Ggf. häufiger. 1. Staub oder Schmutz an Gitter und Abdeckung mit einem weichen Tuch abwischen. Das Tuch vorher in lauwarmem Wasser (unter 40°C/104˚F) mit neutraler Seife anfeuchten. 2. Weder Benzin, noch Verdünner oder sonstige Chemikalien zum Reinigen verwenden. Mindestens alle 2 Wochen. Ggf. häufiger. ! Vorsicht Keine Heizgeräte in der Nähe der Klimaanlage einschalten, sonst kann die Kunststoffabdeckung durch zu grosse Wärme schmelzen oder beschädigt werden. BEI LÄNGERER NICHTBENUTZUNG DES KLIMA-GERÄTES Betreiben Sie das Gerät 2 Stunden lang in folgender Einstellung. Betriebsmodus : kühlen Temperatur : 30˚C/86˚F Netzstecker ziehen. Falls das Klimagerät an einen eigenen Stromkreis angeschlossen ist, diesen Stromkreis unterbrechen (Sicherung herausdrehen oder Sicherungsautomat abschalten). Batterien aus der Fernbedienung nehmen. 3-15 STÖRUNGS-BEHEBUNG Im Falle einer Funktionsstörung ist das Gerät sofort auszuschalten. Nachfolgend einige Hinweise zur Behebung von einfachen Störungen. Störung Ursache / Maßnahme 1. Der Kompressor setzt sich 3 Minuten nach Einschalten des Klimagerätes nicht in Gang. - Schutzeinrichtung gegen häufiges Anlassen. 3 bis 4 Minuten warten, bevor der Kompressor anläuft. 2. Das Klimagerät funktioniert nicht. - Stromversorgung fehlerhaft/ggf. Sicherung austaushen. - Netzstecker nicht eingesteckt. - Timer möglicherweise falsch programmiert. - Falls die Störung nach diesen Kontrollen weiterhin besteht sollte der Installateur benachrichtigt werden. 3. Der Luftstrom ist zu schwach. - 4. Die ausgeblasene Luft riecht unangenehm. - Geruchsbildung möglicherweise durch Zigarettenrauch, Parfüm usw. und entsprechenden Ablagerungen am Wärmetauscher. 5. Kondensation am Vordergitter des Innengerätes. - Bedingt durch Luftfeuchtigkeit nach längerem Betrieb des Gerätes. - Eingestellte Temperatur zu niedrig; Temperatureinstellung erhöhen und das Gerät bei hoher Gebläsedrehzahl laufen lassen. 6. Wasser fließt aus dem Klimagerät. - Das Gerät ausschalten und den Reparaturservice benachrichtigen. 7. Zischendes Geräusch während des Betriebs. - Kälteflüssigkeit tritt in den Verdunster ein. Luftfilter verschmutzt. Türen order Fenster geöffnet. Lufteinlaß bzw. Luftauslaß verstopft. Regeltemperatur nicht hoch genug. Kann die Störung nicht behoben werden, sollte der örtliche Kundendienst bzw. der Installateur benachrichtigt werden. 3-16 MANUALE D’INSTALLAZIONE Il presente manuale descrive come procedere all’installazione del condizionatore per assicurarne il corretto funzionamento in condizioni di sicurezza. Degli adattamenti possono rivelarsi necessari per rispondere a particolari esigenze locali. Prima di utilizzare il condizionatore, leggere attentamente le presenti istruzioni. Conservarle per ogni evenienza futura. CONDIZIONATORE D'ARIA MURALE A FLUSSO RIPARTITO MODELLO RISCALDAMENTO (R22) Modello di Riferimento Modello Modello di Riferimento Modello WM301 SL30C SL30B AWM301 ALC30C ALC30B WM301R SL30CR SL30BR AWM301R ALC30CR ALC30BR KÜHLFUNKTION (R410A) RISCALDAMENTO (R410A) Modello di Riferimento Modello Modello di Riferimento Modello 5WM311 5SL28C A5WM311 A5LC28C 5WM301R 5SL28CR A5WM301R A5LC28CR IM-WM1-0302(2)-Acson Part No.: A08019025521 4-1 Italiano KÜHLFUNKTION (R22) SOMMARIO - Disegni e Dimensioni - Norme di Sicurezza - Diagramma per L’installazione - Installazione Dell’unità Esterna - Installazione Del Tubo Dell’orifizio - Installazione Dell’unità Interna - Condotti del Refrigerante - Allacciamenti Elettrici pag. i-ii pag. 2 pag. 3 pag. 3 pag. 4 pag. 6 pag. 7 pag. 8 - Speciali Precauzioni per le Unità con R410A - Spurgo e Ricarica - Spie di Controllo - Funzionamento del Condizionatore D’aria - Condizioni di Funzionamento Estandar - Filtro Elettrostatico - Pulizia e Manutenzione - Guasti e Riparazioni pag. 10 pag. 10 pag. 11 pag. 13 pag. 14 pag. 14 pag. 15 pag. 16 NORME DI SICUREZZA Leggere attentamente le norme di sicurezza che seguono, prima di procedere all’installazione. ! Avvertenza • L’installazione e la manutenzione devono essere eseguite da personale qualificato, competente in questo genere di apparecchi e al corrente delle leggi e regolamenti in vigore. • Tutti gli allacciamenti elettrici devono essere eseguiti conformemente alla regolamentazione elettrica in vigore. • Prima di procedere agli allacciamenti secondo lo schema elettrico presentato più avanti, accertarsi che il voltaggio dell’apparecchio corrisponda a quello della rete. • Dotare il condizionatore di una presa di TERRA al fine di prevenire i rischi originati da eventuali deficienze del sistema di isolamento. • Evitare chi i fili elettrici tocchino condotti del refrigerante, il compressore o un qualsiasi organo rotante dei motori della ventola. • Prima di installare il condizionatore o di procedere ad interventi di manutenzione, accertarsi che sia spento (OFF). IMPORTANTE IL CONDIZIONATORE NON DEVE MAI ESSERE INSTALLATO O USATO IN UNA LAVANDERIA. ! Cautela Durante l’installazione, verificare accuratamente i punti seguenti. • Non procedere all’installazione in luoghi dove possano verificarsi fughe di gas. Pericolo d’incendio in caso di fughe o di concentrazioni di gas intorno al condizionatore. • Verificare che i condotti di drenaggio siano stati correttamente installati. Un’installazione incorretta può causare delle perdite d’acqua e danneggiare il mobilio. • Non sovraccaricare il condizionatore. L’apparecchio è precaricato in fabbrica. Qualsiasi sovraccarico provoca una sovracorrente e può danneggiare il compressore. • Dopo l’installazione o gli interventi di manutenzione accertarsi di rimettere a posto il pannello di chiusura. Una difettosa chiusura del pannello è causa di rumori durante il funzionamento. 4-2 DIAGRAMMA PER L’INSTALLAZIONE Unità Interna Fitri Dell’aria Pannello Anteriore Pannello Posteriore Griglia Dell’entrata Dell’aria Interruttore Avvio/Arresto Tubo di drenaggio Spie Luminose Feritoria di Ventilazione Rejilla de aire de retorno Griglia D’ingresso Dell’aria Ingresso dell’aria Italiano Condotti Del Refrigerante Ingresso dell’aria Effusore Della Ventola di Aerazione Unità Esterna B Ostacolo A Aria di scarico Ostacolo Il blocco esterno deve essere installato in modo da evitare che la circolazione dell’aria calda di scarico venga strozzata o ostruita, diminuendone così il flusso normale. Rispettare nell’installazione le distanze di sicurezza sotto indicate. Scegliere il luogo più fresco possibile in modo che la temperatura dell’aria in entrata non sia superiore a quella esterna (massimo 45°C/113°F). Aria di ritorno INSTALLAZIONE DELL’UNITÀ ESTERNA Distanze di sicurezza 300 (11,8) D 500 (19,7) Nota: Se esistono ostacoli di più di 2m di altezza o una qualsiasi ostruzione al di sopra dell’apparecchiatura, aumentare le distanze sopra indicate. 4-3 C D Ostacolo 1000 (39,4) C Portello di Servizio 300 (11,8) B Ostacolo A Aria di ritorno Dimensioni Distanza minima, mm (in) INSTALLAZIONE DEL TUBO DELL’ORIFIZIO Tubo dell’orifizio 2 3 4 1 Unità Esterna Interno 1 Orifizio 3 Dado svasato 3/8” (femmina) 2 Tubo di raccordo 4 Raccordo svasato 3/8” (maschio) Nota: La presente installazione è valida soltanto per WM301 / SL30B & WM301 / SL30C ! Cautela Si deve installare il tubo dell’orifizio nella direzione corretta come indicato sopra. Una direzione inadeguata potrebbe danneggiare il sistema di funzionamento. A. Installazione del tubo dell’orifizio dell’unità esterna (con spazio di installazione sufficiente) Passo 2 Tubo dell’orifizio Passo 1 Passi: 1. Collegare il dado “Femmina” del tubo dell’orifizio direttamente alla valvola liquido. 2. Allargare il tubo della linea liquido e collegarlo al raccordo “Maschio” del tubo dell’orifizio. Tubo dell’orifizio 4-4 Tubo linea liquido B. Installazione del tubo dell’orifizio dell’unità esterna (con spazio di installazione limitato) Passo 4 Tubo dell’orifizio Passo 3 Passo 2 Passo 1 Qualora non fosse possibile collegare il tubo dell’orifizio direttamente alla valvola liquido per motivi di spazio insufficiente, sarà possibile collegarlo al tubo entro la linea liquido. Passi: 1. Allargare il tubo della linea liquido e collegarlo alla valvola liquido. 3. Collegare il dado “Femmina” del tubo dell’orifizio al raccordo “Maschio”. 2. Brasare un raccordo “Maschio” al tubo della linea liquido. 4. Allargare un altro tubo per la linea liquido e collegarlo al raccordo “Maschio” del tubo dell’orifizio. Tubo linea liquido Tubo linea liquido Tubo dell’orifizio Brasatore C. Installazione del tubo dell’orifizio dell’unità interna Unità Interna Tubo dell’orifizio Passi: 1. Brasare un raccordo “Maschio” al tubo della linea liquido. 2. Collegare il dado “Femmina” del tubo dell’orifizio al raccordo “Maschio”. Tubo dell’orifizio Tubo linea liquido Tubo linea liquido 3. Allargare un altro tubo per la linea liquido e collegarlo al raccordo “Maschio” del tubo dell’orifizio. Tubo linea liquido Tubo dell’orifizio Brasatore 4-5 Italiano Tubo dell’orifizio Tubo linea liquido INSTALLAZIONE DELL’UNITÀ INTERNA I condotti del refrigerante possono essere collegati all’apparecchiatura in differenti modi (lato posteriore destro o sinistro) utilizzando i fori predisposti sul rivestimento esterno (vedere figura). Piegare accuratamente i tubi nel verso richiesto per condurli al foro appropriato. Poiché dal lato posteriore destro la conduttura deve fuoriuscire, sostenerla opportunamente e fissarne la direzione (vedere figura). Utilizzado un nastro adesivo, attaccarvi quindi il tubo di drenaggio. Il blocco interno deve essere installato in modo che la circolazione dell’aria fredda di scarico e dell’aria di ritorno sia la più ampia possibile. Assicurarsi di mantenere le distanze di sicurezza illustrate nella figura. Installare il blocco interno in modo che non si trovi ad ess ere direttamente esposto ai raggi del sole o in prossimità di porte e finestre. Questa disposizione è la migliore anche per le tubazioni e il sistema di drenaggio. 50mm 50mm 50mm Collegamento Posteriore Destro Più alto del livello degli occhi. Aria Flusso Direzione Mantenimento e Servicing spazio Piastra d’installazione Montaggio dell’unità sullo chassis Agganciare l’unità alla parte superiore dello chassis (inserire i due ganci posteriori dell’unità negli appositi fori dello chassis). Per controllare se gli agganci sono correttamente inseriti nella piastra d’installazione, spostare l’unità leggermente verso destra e sinistra. Marcatura off-line Filo Montaggio dello chassis Accertarsi della capacità di tenuta della parete. Se il muro non è in grado di sopportare il peso dell’apparecchio, rinzorzarlo con delle piastre, delle travi o dei pilastrini di sostegno. Per il montaggio orizzontale, utilizzare il filo a piombo. Fissare con 4 viti appropriate. Nel caso in cui le tubazioni posteriori fuoriescano, praticare sul muro un foro di 65mm di diametro servendosi di una perforatrice a cono. Il foro deve presentare all’esterno una leggera inclinatura verso il basso (veder figura). Dentro Cavetto Di Collegamento Tubo di drenaggio Tubo di drenaggio Il tubo di drenaggio interno deve essere posizionato in leggera pendenza per garantirne un buon funzionamento. Evitare condizioni che possono causare perdite d’acqua. Fuori Drenaggio dell’acqua Inclinazione 1/50 Collegamento del condotti Rimuovere la vite che assicura il pannello anteriore. Perdite di Liquido 3 2 1 Collegamento Del Condotto 4 5 4-6 Perdite di Liquido Il tubo pesca nell’acqua Perdite di Liquido j ✓ J J J Corretto Errato Errato Errato CONDOTTI DEL REFRIGERANTE ! Cautela Nell’unità di raffreddamento WM301 si utilizzata un’orifizio come congegno di dilatazione. Questo è montato nel tubo dell’acqua dell’ unità interna. Lunghezza e altezza delle condutture Taglio del tubo di rame Se la conduttura è troppo lunga, la capacità e l’affidabilità dell’apparecchio risultano entrambe compromesse. Più grande è il numero dei gomiti, maggiore è la resistenza al flusso del sistema di raffreddamento. In tale situazione, le capacità di raffreddamento diminuiscono e l’attività del compressore può ridursi fino a diventare inefficace. Scegliere sempre il percorso più breve e attenersi alle indicazioni fornite nella tabella che segue: 07/10 15 25 20 30 Lunghezza massima, m (ft), L 12 (39,4) 12 (39,4) 15 (49,2) 15 (49,2) 35 (114,8) Altezza massima m (ft), H 5 (16,4) 5 (16,4) 8 (26,2) Togliere Sbavatura Del Tubo 8 (26,2) 15 (49,2) Mass. num. di gomiti 10 10 10 10 10 Diametro tubi liquidi 1/4" 1/4" 1/4" 3/8" 3/8" Diametro tubi gas 3/8" 1/2" 5/8" 5/8" Tubo Di Rame Estremità Rastremata 5/8" Attenzione: Il refrigerante precaricato in fabbrica nel blocco esterno è calcolatoper una tubatura di 7,62m/25ft di lunghezza. Collegamento delle condutture alle unità • Centrare la tubatura e stringere a mano il dado quanto basta. • A mezzo di una chiave torsiometrica, stringere quindi il dado fino a che si produca lo scatto previsto. Unità Interna Dimensioni Del Tubi mm / (Pol) L Chiave Rsiometrica (nm) 6,35 (1/4) 9,53 (3/8) 12,7 (1/2) 15,88 (5/8) H 18 42 55 65 Ø Tubo, D Unità Esterna Pollici mm 1/4" 3/8" 1/2" 5/8" 6,35 9,52 12,70 15,88 (13,3) (31,0) (40,6) (48,0) A (mm) Imperiale Rigido 1,3 1,6 1,9 2,2 Condutture Giunto Svasato • Non usare condotti di rame contaminati o danneggiati. Non rimuovere le parti in plastica, i tappi in gomma e i dadi di ottone da valvole, accessori vari, condutture e serpentini fino a quando non si è pronti a collegare le tubature di aspirazione e dei liquidi alle valvole ed altri accessori. • Se sono necessari degli interventi di brasatura, assicurarsi di passare l’azoto sul serpentino e sui giunti mentre si esegue l’intervento. Ciò eviterà la formazione di fuliggine sulla parete interna dei tubi di rame. • Tagliare il tubo col tagliatubi. • Rimuovere le bavature dall’estremità del tubo utilizzando l’apposito attrezzo. Tenere il tubo verso il basso per evitare che le limature metalliche penetrino al suo interno. • Inserire sui tubi di raome i dadi svasati che si trovano sulle bocchette d’ingresso delle unità interna ed esterna. • Svasare il tubo secondo le misure mostrate in tablella. • L’estremità svasata del tubo deve essere omogenea e non presentare fessure o graffiature. Tubature Interne Tubo Svasato Dadi Di Svaso Chiave Torsiometrica Chiave Fissa 4-7 0,7 1,0 1,3 1,7 Italiano Modello ALLACCIAMENTI ELETTRICI Raffreddamento IMPORTANTE : * I valori sopra indicati hanno solo un carattere indicativo. Devono quindi essere verificati e scelti in modo da rispondere alle leggi vigenti e ai regolamenti locali. Inoltre, dipendono pure dal tipo di impianto e dai conduttori utilizzati. ** L’appropriato intervallo di tensione deve essere confrontato con i dati della targa dell’apparecchio. ETL unità elencata è soltanto applicabile ad alimentazione di 60Hz esclusivamente. Modello Interno Esterno WM 071/ 101/ 151 SL07/ 10/ 15B Voltaggi ammessi** WM201/ 251/ 301 SL20/ 25/ 30B 220V-240V/ 1Ph/ 50Hz + 5WM311 5SL28C WM301 SL30C o 208V-230V/ 1Ph/ 60Hz + WM201/ 251/ 301 SL20/ 25/ 30B WM301 SL30C 380V-415V/ 3Ph/ 50Hz +N+ Dimensioni del cavetto di alimentazione* mm2 Numero dei fili 1,5 3 2,5 3 2,5 3 4 3 1,5 5 1,5 5 Dimensioni del cavetto di interconnessione* mm2 Numero dei fili 1,5 3 2,5 3 2,5 3 2,5 4 1,5 4 1,5 4 Fusibili consigliati 15 20 20 25 15 15 A WM301 VS SL30C WM07 / 10 / 15 / 20 / 25 / 301 VS SL07 / 10 / 15 / 20 / 25 / 30B 5WM311 VS 5SL28C Morsettiera Morsettiera Dell’Unità Interna Dell’Unità Esterno Morsettiera Dell’Unità Interna Morsettiera Dell’Unità Esterno L COMP N COMP COMP N2 N N2 S N1 R N1 L COMP L Corda Di Alimentazione Di Corrente Corda Di Alimentazione Di Corrente ! ! Nell’impianto elettrico esistente sono necessari un interruttore bipolare con contatti separati da almeno 3mm e un fusibile/interruttore automatico. WM201 / 251 VS SL20 / 25B (3 La Fase) Morsettiera Dell’Unità Interna Nell’impianto elettrico esistente sono necessari un interruttore bipolare con contatti separati da almeno 3mm e un fusibile/interruttore automatico. WM301 VS SL30C (3 La Fase) Morsettiera Dell’Unità Esterno Morsettiera Dell’Unità Interna COMP L N Morsettiera Dell’Unità Esterno COMP COMP L COMP L N2 N N2 N N1 N1 R L L R S S Corda Di Alimentazione Di Corrente Corda Di Alimentazione Di Corrente T N T N ! Nell’impianto elettrico esistente sono necessari un interruttore bipolare con contatti separati da almeno 3mm e un fusibile/interruttore automatico. ! Nell’impianto elettrico esistente sono necessari un interruttore bipolare con contatti separati da almeno 3mm e un fusibile/interruttore automatico. • Tutti i fili devono essere collegati saldamente. • I fili non devono toccare né i condotti del refrigerante, ne il compressore né gli organi rotanti del motore della ventola. • I fili di collegamento tra il blocco interno e quello esterno devoso essere fissati alla morsettiera come indicato nella figura. • La corda di alimentazione di corrente deve equivalere ad un minimo di H05RN-F (245IEC57). Morsa Elettrica Cavetto Di Collegamento 4-8 Riscaldamento IMPORTANTE : * I valori sopra indicati hanno solo un carattere indicativo. Devono quindi essere verificati e scelti in modo da rispondere alle leggi vigenti e ai regolamenti locali. Inoltre, dipendono pure dal tipo di impianto e dai conduttori utilizzati. ** L’appropriato intervallo di tensione deve essere confrontato con i dati della targa dell’apparecchio. ETL unità elencata è soltanto applicabile ad alimentazione di 60Hz esclusivamente. Modello Interno WM 071/ 101/ 151 R WM201/ 251/ 301 R 5WM301R WM301 R WM201/ 251/ 301 R WM301 R Esterno SL07/ 10/ 15BR SL20/ 25/ 30BR 5SL28CR SL30CR SL20/ 25/ 30BR SL30CR Voltaggi ammessi** 220V-240V/ 1Ph/ 50Hz + o 208V-230V/ 1Ph/ 60Hz + 380V-415V/ 3Ph/ 50Hz +N+ Dimensioni del cavetto di alimentazione* mm2 Numero dei fili 1,5 3 2,5 3 2,5 3 4 3 1,5 5 1,5 5 Dimensioni del cavetto di interconnessione* mm2 Numero dei fili 1,5 5 2,5 5 2,5 5 2,5 6 1,5 6 1,5 4 Fusibili consigliati 15 20 20 25 15 15 WM301R VS SL30CR WM07 / 10 / 15 / 20 / 25 / 301R VS SL07 / 10 / 15 / 20 / 25 / 30BR 5WM301R VS 5SL28CR Filo Di Collegamento Del Sensore Del Serpentino Esterno (8m Di Lunghezza) Collegato Al Dell’Unità Interna Morsettiera Filo Di Collegamento Del Sensore Del Serpentino Esterno (8m Di Lunghezza) Collegato Al Dell’Unità Interna Morsettiera Dell’Unità Interna Morsettiera Dell’Unità Interna Morsettiera Dell’Unità Esterno 4WV 4WV OF OF COMP COMP N2 N1 N Dell’Unità Esterno A 4WV 4WV OF OF COMP COMP N2 L N1 N Italiano A L L Corda Di Alimentazione Di Corrente Corda Di Alimentazione Di Corrente N L ! Nell’impianto elettrico esistente sono necessari un interruttore bipolare con contatti separati da almeno 3mm e un fusibile/ interruttore automatico. ! WM201 / 251R VS SL20 / 25BR (3 La Fase) Nell’impianto elettrico esistente sono necessari un interruttore bipolare con contatti separati da almeno 3mm e un fusibile/ interruttore automatico. WM301R VS SL30CR (3 La Fase) Filo Di Collegamento Del Sensore Del Serpentino Esterno (8m Di Lunghezza) Collegato Al Dell’Unità Interna Morsettiera Filo Di Collegamento Del Sensore Del Serpentino Esterno (8m Di Lunghezza) Collegato Al Dell’Unità Interna Morsettiera Dell’Unità Interna 4WV Morsettiera Dell’Unità Esterno Morsettiera Dell’Unità Interna 4WV 4WV A 4WV OF OF COMP COMP N2 L N2 L N1 N N1 N OF OF COMP COMP L L R R Corda Di Alimentazione Di Corrente S S Corda Di Alimentazione Di Corrente T N ! Dell’Unità Esterno ! Nell’impianto elettrico esistente sono necessari un interruttore bipolare con contatti separati da almeno 3mm e un fusibile/ interruttore automatico. 4-9 Nell’impianto elettrico esistente sono necessari un interruttore bipolare con contatti separati da almeno 3mm e un fusibile/ interruttore automatico. T N SPECIALI PRECAUZIONI PER LE UNITÀ CON R410A • • • • • • R410A è una miscela refrigerante quasi azeotropica di idrofluorocarburi (HFC) i quali sono ecologici. Ha un potenziale di impoverimento dell’ozono uguale a zero (ODP=0) rendendolo conforme alle norme del protocollo di Montreal. È privo di propagazione di fiamma ed ha un refrigerante a bassa tossicità (classificato come A1 da ARI). R410A è una miscela di R32 (50%) e R125 (50%). L’olio POE usato come lubrificante nei compressori con R410A è diverso dall’olio minerale usato per i compressori in R22. Durante l’installazione o le operazioni d’assistenza, si richiedono maggiori attenzioni al fine di non esporre, il refrigerante troppo tempo all’aria umida. L’olio residuo POE rimasto nei tubi e nei componenti può assorbire umidità dall’aria. Il refrigerante R410A è più facilmente affetto dall’ umidità della polvere che non l’ R22; assicurarsi quindi di chiudere i terminali delle tubazioni prima di procedere all’installazione. Si raccomanda di non effettuare altre cariche d’olio nel commpressore. Nessuno altro refrigerante diverso da R410A è permesso. Utilizzare strumenti ed attrezzature specifici per R410A. i) Valvola di distribuzione e tubo flessibile di carica ii) Rivelatore di perdita di gas iii) Cilindro di refrigerante/cilindro di carica iv) Adattatore pompa del vuoto v) Attrezzi per saldatura vi) Macchina per recupero di refrigerante ! ATTENZIONE • • • L’R410A deve essere caricato in stato liquido. Normalmente, la bombola di R410A è dotata di un tubo profondo per il prelevamento del liquido. Se la bombola non è provvista di tale tubo, deve essere capovolta per permettere al refrigerante R410A di uscire dalla valvola. In caso di perdite, non effettuare aggiunte di refrigerante ma svuotare completamente l’unità ed effettuare di nuovo la carica attenendosi alle indicazioni contenute nel manuale. Svuotare l’unità completamente e poi riempirla con R410A nelle sue caratteristiche originali nella quantità raccomandata nelle specifiche. Non rabboccare mentre si sta riparando una perdita perché potrebbe ridurre la prestazione dell’apparecchio. È necessiario quindi svuotare completamente l’unità e ricaricare il refrigerante secondo le caratteristiche iniziali. SPURGO E RICARICA Spurgo delle tubazioni el del unità interna Ricarica Addizionale Fatta eccezione del unita esterno che è precaricato con il refrigerante, il blocco interno e le tubature di collegamento devono essere spurgate dell'aria. Essa contiene infatti dei residui di umidità prodotti dal ciclo di raffreddamento che possono provocare un malfunzionamento del compressore. • Rimuovere i tappi della valvola e del porto di servizio. • Collegare il centro della valvola del collettore alla pompa di estrazione. • Collegare la valvola del collettore alla bocchetta di servizio della valvola a 3 vie. • Avviare la pompa di estrazione. Far spurgare per 30 minuti circa. Il tempo di spurgo varia a seconda della capacità della pompa di estrazione. Controllare che l’ago della valvola del collettore si sia portata su -76mmHg (0~76mmHg). Attenzione Se l’ago non si sposta su 0~76mmHg, controllare che non ci siano perdite di gas (utilizzando il rivelatore di refrigerante) in prossimità del collegamento svasato del blocco interno ed esterno e riparare la perdita prima di procedere. • Chiudere la valvola del collettore e spegnere la pompa di estrazione. • Sul blocco esterno, aprire la valvola di aspirazione a (3 vie) e la valvola per il liquido a (2 vie) in senso antiorario con una brugola di 4mm. Il blocco esterno è provvisto del refrigerante, precaricato in fabbrica. Se la lunghezza del tubo è inferiore a 7,62m (25ft), dopo l'aspirazione non è necessaria alcuna ricarica addizionale. Se la lunghezza dei condotti è superiore ai 7,62m (25ft), usare i valori di ricarica addizionale come indicato nella tabella in basso. Dadi di svaso Brugola Bocchetta di servizio Condotti del refrigerante Valvola a 3 vie del blocco esterno Unità Interna Per il liquido Valvola di scarico Unità Esterna Chiuso Per il gas Valvola Di Aspirazione Aperto Pompa Di Estrazione Lo Chiuso Hi Chiuso 4-10 • Aprire il cilindro del gas e la valvola del collettore a bassa pressione. • Quando la quantità richiesta di refrigerante è stata pompata nell’impianto, chiudere la valvola del collettore a bassa pressione e la valvola del cilindro del gas. • Scollegare il tubo flessibile dalla bocchetta di servizio. Rimettere il tappo della bocchetta di servizio. Ricarica addizionale in grammi (R22) Modello 071 / 101 / 151 201 251 / 301 071R / 101R /151R 201R 251R / 301R 10 m/32,8 ft 35 35 90 50 60 120 12 m/39,4 ft 65 65 165 90 110 220 15 m/49,2 ft 110 280 185 370 Ricarica addizionale in grammi (R410A) Modello 311 301R 10 m/32,8 ft 80 110 12 m/39,4 ft 150 200 Unità Interna Per il liquido 15 m/49,2 ft 255 335 Valvola di scarico Unità Esterna Chiuso Operazioni di ricarica Per il gas Tale operazione deve essere obbligatoriamente effettuata utlizzando il cilindro del gas ed una bilancia di precisione. Il gas refrigerante viene introdotto nel blocco esterno tramite la bocchetta di servizio della valvola aspirante. • Rimuovere il tappo della bocchetta di servizio. • Collegare il collettore a bassa pressione alla bocchetta di aspirazione del serbatoio cilindrico e chiudere il collettore ad alta pressione. Spurgare l’aria dal tubo flessibile. • Mettere in funzione il condizionatore. Valvola Di Aspirazione Valvola di controllo Chiuso Hi Lo Aperto Chiuso Ricevitore a infrarossi Raffreddamento Il ricevitore segnali dell’unità interna emette un bip per confermare il ricevimento di un segnale di trasmissione dal telecomando. La tabella mostra le spie luminose “LED” del condizionatore d’aria durante il normale funzionamento e i guasti. Le spie di controllo sono a diodi a emissione luminosa (LED) e si trovano nella zona inferiore destra del condizionatore. Spie luminose “LED” dell’unità di raffreddamento Ricevitore Infrarossi Accensiones Temporizzatore Deumidificazione Modalità Riposo Spie di Controllo Tipo LED Spie luminose “LED” : Normale funzionamento e guasti dell’unità di raffreddamento Indicatore Operazione/Difficoltà Accensione Secco Temporizzatore Intervento Riposo Accensione timer. – Accensione modalità riposo. – Deumidificazione. – Anti-gelo. Pulire il filtro e commutare su ventilazione. Ogni 2 secondi Sensore aria ambiente in corto o falso contatto. Rivolgersi al servizio di assistenza. Due volte ogni 2 secondi Sensore serpentino interno in corto o falso contatto. Rivolgersi al servizio di assistenza. Può esserci un problema di contatti a livello del sensore o un sovraccarico del compressore o una fuga di gas. Rivolgersi al servizio di assistenza. Continuamente Tre ogni 2 secondi ACCESO ACCESO o SPENTO 4-11 Lampeggiante Italiano SPIE DI CONTROLLO Spie luminose “LED” dell’unità di riscaldamento. Riscaldamento La tabella che segue indica la funzione della diverse spie di controllo del condizionatore come pure gli interventi da effettuare in caso di guasto. Le spie di controllo sono a diodi a emissione luminosa (LED) e si trovano nella zona inferiore destra del condizionatore. I condizionatori provvisti di pompa di calore sono dotati di una modalità automatica che, alternando automaticamente tra modalità “freddo” e “caldo”, assicura una temperatura ambiente confortevole, in corrispondenza della temperatura impostata dall’utente. Raffreddamento Deumidificazione Modalità calore/ ventilatore (Rosso/Verde) Modalità Riposo Spie luminose “LED”: Normale funzionamento e guasti dell’unità di riscaldamento Azione in corso/indicazione del guasto Freddo Secco Ventola Cald Intervento Riposo Raffreddamento. – Deumidificazione. – Ventilazione. – Riscaldamento. – Riscaldamento automatico. – Raffreddamento automatico. – Sbrinamento. – Sovraccarico del compressore. Rivolgersi al servizio di assistenza. Sensore serpentino interno in corto o falso contatto. Rivolgersi al servizio di assistenza. Sensore serpentino esterno in corto o falso contatto. Rivolgersi al servizio di assistenza. Sensore aria ambiente in corto o falso contatto. Rivolgersi al servizio di assistenza. Se il sistema è su raffreddamento o riscaldamento (senza la marcia notturna inserita), può esserci un problema di contatti a livello del sensore o un sovraccarico del compressore o una fuga di gas. ACCESO ACCESO o SPENTO 4-12 Lampeggiante FUNZIONAMENTO DEL CONDIZIONATORE D’ARIA Modalità Secco Prevenzione brina • Quando c’e molta umidità si può attivare la modalità secco. Premere il pulsante <MODE> e scegliere <SECCO>. • Se la temperatura ambiente è più di 2ºC/35,6ºF superiore alla temperatura impostata, il condizionatore funzionerà in modalità raffreddamento fino a che la differenza tra le due temperature sarà minore di 2ºC/35,6ºF e poi funzionerà in modalità secco. • Se la differenza tra la temperastura ambiente e la temperatura impostata è minore di 2˚C/35,6ºF, il condizionatore funzionerà direttamente in modalità secco. • In funzione secco il condizionatore funzionerà a velocità BASSA. • Quando il filtro è sporco, la temperatura di evaporazione diminuisce e causa la formazione di brina. • La spia luminos lampeggia per indicare che il filtro è sporco. Se la temperatura di evaporazione scende a -2˚C/28,4ºF, il condizionatore scatta e inizia l’operazione di scongelamento automaticamente. Velocità della ventola e capacità di raffreddamento nominale • La capacità di raffreddamento nominale è raggiungibile a velocità massima del ventilatore. • La capacità di raffreddamento è minore quando il condizionatore funziona a velocità ventola MEDIA o BASSA. Orizzontale Raffreddamento Secco • Quando si avvia il condizionatore iniziaalmente o durante il ciclo di scongelamento, il ventilatore interno si metterà in funzione solo dopo che la bobina termica ha raggiunto la temperatura desiderata. • Una volta raggiunta la temperatura desiderata, il ventilatore interno continuerà a funzionare fino a che la bobina termica è in grado di provvedere calore. Aggiustamento Orizzontale 25°C/77°F • Per una più efficace circolazione dell'aria, è possibile aggiustare a mano verso destra o sinistra la griglia di ventilazione. • Durante il funzionamento in modalità freddo e secco, evitare di dirigere, per un lungo periodo di tempo, la feritoia di ventilazione verso il basso. In caso contrario, è possibile che sulla feritoia si formi della condensa che sgocciolerà sul pavimento. Conservazione Calda (solo per pompa di Riscaldamento) • • Durante l’interdizione del compressore, la ventola interva pud essere portata sulle posizioni: (i) ON (Acceso) (posizione normale) o (ii) OFF (spento) o (iii) Intervallo (Accesò e Spento) spostando l’interruttore come mostrato nel diagramma. L’interruttore è posizionato sulla copertura frontale (vicino all’interruttore ON/OFF) HOT KEEP OFF INTERVAL ON All’interrusttore ON/OFF NOTA : Quando l’opzione è selezionata, il gruppo di alimentazione della necessità dell’unità di essere ripristinato per attivare la funzione. Protezione contro il surriscaldamento (solo per i condizionatori provvisti di pompa di calore) • Se la temperatura esterna e/o quella interna sono troppo alte, o se il filtro è sporco e intasto, il refrigerante può surriscaldarsi. In questi casi il compressore si spegnerà automaticamente quando la temperatura raggiunge 62˚C/ 143,6ºF. 4-13 Italiano Funzione riscaldamento (solo per i condizionatori provvisti di pompa di calore) CONDIZIONI DI FUNZIONAMENTO ESTANDAR Unità di riscaldamento Unità di raffreddamento Temperatura Ts °C/°F Th °C/°F Temperatura Temperatura interna minima 19,4 / 66,9 13,9 / 57,0 Temperatura interna minima 10 / 50 – Temperatura interna massima 26,7 / 80,1 19,4 / 66,9 Temperatura interna massima 26,7 / 80,1 – Temperatura esterna minima 19,4 / 66,9 13,9 / 57,0 Temperatura esterna minima -8 / 17,6 -9 / 15,8 Temperatura esterna massima 46 / 114,8 24 / 75,2 Temperatura esterna massima 24 / 75,2 18 / 64,4 Ts °C/°F Th °C/°F Ts: Temperatura a termometro asciutto. Th: Temperatura a termometro bagnato. ! Avvertenza • • Staccare la corrente prima di procedere a qualsiasi intervento di manutenzione sul condizionatore. Non rimuovere il cavo di alimentazione quando il condizionatore è acceso. Questo può causare seri shock elettrici e pericolo d’incendio. FILTRO ELETTROSTATICO FILTRO DEODORIZZANTE E PURIFICATORE D’ARIA A DOPPIA AZIONE ELETTROSTATICA E INTELAIATURA FILTRO AZIONE 1FILTRO PURIFICATORE D’ARIA ELETTROSTATICO AZIONE 2FILTRO DEODORIZZANTE Il filtro di carbone attivato rimuove odori sgradevoli nell’aria e mantiene l’aria fresca nella stanza. l filtro in polipropilene precaricato elettrostaticamente rimuove particelle di polvere microscopiche, fumo ed altre particelle invisibili in modo da mantenere l’aria pulita. INSTALLAZIONE Aprirela Griglia Anteriore. Inserire I Filtri A Doppia Azione Elettrostatica E Deodorizzante il Posizione. Togliere I Filtri Original. Inserire Nuovamente I Filtri Originali. 4-14 ! Cautela 3. Il filtro è un componente che può essere acquistato dal rivenditore di condizionatori d’aria autorizzato. 4. Una volta tolto il filtro dal suo sacchetto ermetico, usarlo immediatamente. L’effetto deodorizzante del filtro diminuisce se si apre il sacchetto molto prima di usarlo. 1. Il filtro deodorizzante e purificatore d’aria elettrostatico deve essere cambiato ogni 6 mesi oppure quando diventa di colore brunastro. 2. Il filtro sporco è da buttare, esso non può essere lavato e riusato. ! Avvertenza • • Staccare la corrente prima di procedere a qualsiasi intervento di manutenzione sul condizionatore. Non rimuovere il cavo di alimentazione quando il condizionatore è acceso. Questo può causare seri shock elettrici e pericolo d’incendio. Componenti Filtro dell’aria interno Procedure Di Manutenzione Periodo 1. Togliere la polvere dal filtro usando un’aspirapolvere o lavarlo in acqua tiepida (sotto ai 40˚C/104˚F) con detersivo neutro. Almeno due volte al mese. 2. Sciacquare bene e asciugare il filtro prima di rimetterlo nell’unità. Più spesso se necessario. 3. Non usare mai benzina o prodotti chimici per pulire il filtro. Unità interna 1. Togliere la polvere e la sporcizia dalla griglia e dal pannello, strofinando con un panno soffice imbevuto di acqua tiepida (sotto ai 40˚C/104˚F) e detersivo neutro. 2. Non usare mai benzina o prodotti chimici per pulire l’unità interna. Almeno due volte al mese. Più spesso se necessario. ! Cautela Non utilizzare apparecchiature di riscaldamento nelle immediate vicinanze del condizionatore. L’eccessivo calore potrebbe danneggiare o deformare il pannello in plastica. QUANDO NON SI PREVEDE DI UTILIZZARE IL CONDIZIONATORE PER UN LUNGO PERIODO DI TEMPO Far funzionare il condizionatore per 2 ore nella modalità che segue. Disinserire la spina. Se per il condizionatore si utilizza un circuito indipendente, interrompere la corrente di tale circuito. Togliere le pile dal telecomando. Funzione : freddo Temperatura : 30°C/86ºF 4-15 Italiano PULIZIA E MANUTENZIONE GUASTI E RIPARAZIONI Non appena si nota che il condizionatore funziona male, spegnerlolo immediatamente. Qui di seguito, sono elencati alcuni guasti minori con le relative cause. Guasto Origine / Intervento 1. Il compressore nom si mette in funzione 3 minuti dopo aver acceso il condizionatore. - Protezione contro gli avvii riavvicinati. Attendre 3 or 4 minuti affinchè il compressore si metta in moto. 2. Il condizionatore non funziona. - Interruzione della corrente o fusibile bruciato. La spina non è inserita. L’orario impostato sul timer di ritardo non è corretto. Se il guaste dopo tali verifiche, chiamare il servizio assistenza. 3. Il funsso d’aria è troppo debole. - Il filtro dell’aria è sporco. Porte e finestre aperte. L’aspirazione e lo scarico dell’aria sono ostruiti. La temperatura impostata non è sufficientemente bassa. 4. L’aria che esce dal condizionatore ha cattivo odore. - Il cattivo odore può essere causato da sigarette, particelle di fumo, profumi, ecc. depositati sul serpentino. 5. Condensa sulla griglia anteriore di ventilazione dell’unita interna. - La condensa è dovuta all’umidità dell’aria dopo un lungo periodo di funzionamento. - La temperatura impostata è troppo bassa. Aumentare la temperatura e la velocità della ventola. 6. Acqua sgocciola dal condizionatore. - Spegnere il condizionatore e chiamare il rivenditore. 7. L’aria esce dal condizionatore emettendo un suono anormale. - Immissione di refrigerante nel serpentino dell’evaporatore. Se il guasto persiste, rivolgersi al servizio di assistenza. 4-16 MANUAL DE INSTALACION Este manual facilita instrucciones de instalación que garantizan un seguro y buen funcionamiento de la unidad de aire acondicionado. Es posible que sea necesario realizar un ajuste especial para adecuarse a los requisitos locales. Por favor, antes de usar su equipo de aire acondicionado, lea cuidadosamente este manual de instrucciones, y consérvelo para futuras consultas. EQUIPO DE AIRE ACONDICIONADO DE TIPO DIVIDIDO DE MONTAJE MURAL MODELO ENFRIAMIENTO (R22) CALENTADOR (R22) Modelo Modelo de Referencia Modelo WM301 SL30C SL30B AWM301 ALC30C ALC30B WM301R SL30CR SL30BR AWM301R ALC30CR ALC30BR ENFRIAMIENTO (R410A) Español Modelo de Referencia CALENTADOR (R410A) Modelo de Referencia Modelo Modelo de Referencia Modelo 5WM311 5SL28C A5WM311 A5LC28C 5WM301R 5SL28CR A5WM301R A5LC28CR IM-WM1-0302(2)-Acson Part No.: A08019025521 5-1 ÍNDICE - Esquema y Dimensiones - Precautiones de Seguridad - Diagramma de la Instalación - Instalación de la Unidad Exterior - Instalación de Tubo de orificio - Instalación de la Unidad Interior - Tubería de Refrigerante - Conexión del Cableado Eléctrico página i-ii página 2 página 3 página 3 página 4 página 6 página 7 página 8 - Precauciones Especiales Para El R410A - Limpieza de la Tubería de Refrigerante - Luz Indicadora - Operación de la Unidad de aire Acondicionado - Condiciones de Funcionamiento Estándar - Filtro Electrostático - Reparaciones y Mantenimiento - Localización de Averias página 10 página 10 página 11 página 13 página 14 página 14 página 15 página 16 PRECAUCIONES DE SEGURIDAD Antes de instalar su equipo, sírvase leer las siguientes precauciones de seguridad cuidadosamente. ! Advertencia • La instalación y el mantenimiento deben ser realizador por personas calificadas que estén familiarizadas con el código y los reglamentos locales y que tengan experiencia en este tipo de equipo. • Todo el cableado de campo debe instalarse de acuerdo al reglamento de cableado nacional. • Antes de comenzar la instalación eléctrica de acuerdo con el diagrama de cableado, asegúrese de que el voltaje nominal de la unidad se corresponde con el de la place de identificación. • La unidad debe estar PUESTA A TIERRA para evitar posibles peligros debidos a fallas del aislamiento. • Ninguno delos cables de la instalación eléctrica dene estar en contacto con la tubería refrigerante, el compresor o cualquier pieza móvil de los motores del ventilador. • Antes de iniciar la instalación o reparación de la unidad, asegúrese de que ha sido apagara (OFF). IMPORTANTE NO INSTALE NI HAGA USO DE LA UNIDAD DE AIRE ACONDICIONADO EN UN CUARTO DESTINADO A LAVAR ROPAS. ! Cuidado Asegúrese de seguir durante la instalación los siguientes puntos importantes. • No instalar la unidad ahí donde pueda haber fuga de gas inflamable. Siel gas procedente de una fuga de gas se acumula alrededor de la unidad puede producirse unincendio. • Asegúrese de que la tubería de desagüe está conectada correctamente. Si la tubería de desagüe no está conectada correctamenta se puede producir una fuga de agua que mojaría los muebles. • No sobrecargar la unidad. Esta unidad está pre-cargada en fábrica. Su sobrecarga ocasionará sobre-corrinte o rotura del compresor. • Asegúrese de que el panel de la unidad vuelve a cubrirla, bien colocado, después de la instalación o de cualquier reparación. Un panel mal sujetado hará que la unidad haga ruido al funcionar. 5-2 DIAGRAMMA DE LA INSTALACIÓN Unidad Interior Filtros Del Aire Cubierta Delantera Chásis Trasero Rejilla de Entrada de Aire Botón de Commutación ON/OFF (Apagado/ Encendido) Menguera de Desagüe Luces indicadoras Persiana de Descarga de Aire Receptor de señal Rejilla de Descarga de Aire Entrada de Aire Tubería de Refrigerante Entrada de Aire Tobera de Descarga de Aire Español Unidad Exterior B Obstaculo A Aire de Descarga Obstaculo La unidad de exterior debe instalarse de manera que no haya cortocircuitos de la descarga de aire caliente ni obstrucción a una flujo de aire uniforme. Por favor, siga el espacio proporcionado para la instalación tal y como se indica en el gráfico. Seleccionar el lugar más fresco posible donde la temperatura del aire de entrada no sea superior a la temperatura externa (máximo 45°C/113°F). Aire de Retorno INSTALACIÓN DE LA UNIDAD EXTERIOR Espacio libre de instalación 1000 (39,4) 300 (11,8) D 500 (19,7) Nota: Si hubiese algún obstáculo de más de 2m de altura o cualquier obstrucción en la parte superior de la unidad, dejar más espacio que el indicado en la tabla anterior. 5-3 C D Obstaculo 300 (11,8) C Acess de servicio B Obstaculo A Aire de Retorno Dimensión Distancia minima, mm (in) INSTALACIÓN DE TUBO DE ORIFICIO Tubo de orificio 2 3 4 1 Unidad Exterior Interior 1 Orificio 3 Tuerca abocardada 3/8" (Hembra) 2 Tubo, conectando 4 Junta abocardada 3/8" (Macho) Nota: Esta instalación es sólo para WM301 / SL30B & WM301 / SL30C ! Cuidado El tubo de orificio debe instalarse en la dirección correcta, según se muestra en la figura anterior. En caso contrario, el sistema podría no funcionar correctamente. A. Instalación del tubo de orificio de la unidad exterior (donde el espacio de instalación sea suficientemente ancho) Paso 2 Tubo de orificio Paso 1 Paso: 1. Conecte directamente la tuerca “Hembra” del tubo de orificio a la válvula de líquidos. 2. Abocine el tubo de líquido para conectarlo a la junta “Macho” del tubo de orificio. Tubo de orificio 5-4 Tubo de líquido B. Instalación del tubo de orificio de la unidad exterior (donde el espacio de instalación sea limitado) Paso 4 Tubo de orificio Paso 3 Paso 2 Paso 1 Si no se puede conectar directamente el tubo de orificio a la válvula de líquidos debido a limitaciones de espacio, se puede conectar en algún punto del tubo de líquido. Paso: 1. Abocine el tubo de líquido para conectarlo a la válvula. 3. Conecte la tuerca “Hembra” del tubo de orificio a la junta “Macho”. Tubo de líquido Tubo de orificio 4. Abocine otro tubo de líquido y conéctelo a la junta “Macho” del tubo de orificio. Español 2. Empalme una junta “Macho” adicional al tubo de líquido. Tubo de líquido Tubo de líquido Tubo de orificio Unión C. Instalación de tubo de orificio en la unidad interior Unidad Interior Tubo de orificio Paso: 1. Empalme una junta “Macho” adicional al tubo de líquido. 2. Conecte la tuerca “Hembra” del tubo de orificio a la junta “Macho”. Tubo de líquido Tubo de orificio Tubo de líquido 3. Abocine otro tubo de líquido y conéctelo a la junta “Macho” del tubo de orificio. Tubo de líquido Tubo de orificio Unión 5-5 INSTALACIÓN DE LA UNIDAD INTERIOR La tubería de refrigerante se puede dirigir hasta la unidad de varias maneras (izquierda o derecha detrás de la unidad), usando los agujeros recortados en la caja de la unidad (véase la figura). Doblar cuidadosamente las tuberías hasta la posición requerida para alinearlas con el agujero. Para la extracción derecha y trasera, sujetar la parte inferior de la tubería y fijar la dirección (véase la figure). La manguera de desagüe de condensación debe ser fijada con cinta a las tuberías. La unidad de interior debe estar instalada de modo que el aire de descarga frío no entre en contacto con el aire de retorno caliente. Por favor, siga el espacio proporcionado para la instalación tal y como se indica en el gráfico. No colocar la unidad de interior donde le caiga la luz del sol directamente. El emplazamiento debe ser adecuado para las tuberías y la evacuación y debe estar lejos de la puerta o ventana. 50mm 50mm 50mm Vía lateral derecha y trasera Más arriba que el nivel de la vista Dirección del flujo del aire Espacio de mantenimiento y servicio Placa de Instalación Montar la unidad en la placa de instalación Enganchar la unidad de interior en la porción superior de la placa de instalación (Enganchar los 2 ganchos de la parte trasera superior en el borde superior de la placa de instalación). Para asegurar que los ganchos se encuentren adecuamente instalados en la bandeja de instalación, intente moverlos ligeramente hacia la izquierda o la derecha. Marca-fuera de línea Rosca Montaje de la placa de instalación Verificar que la pared es lo suficientemente sólida como para soportar el peso de la unidad. Si no es así, se debe reforzar la pared con placas, vigas o pilares. Usar la línea de plomada para el montaje horizontal y fijar con 4 tornillos adecuados. En caso de retracción de la tubería trasera, perforar un agujero de 65mm de diámetro con una broca cónica, ligeramente más bajo en la pared externa (véase la fig.). Cable De Interconexión Menguera de Desagüe Tubería de desagüe de agua Interior La tubería de desagüe de interior debe tener una pendiente descendente para lograr un vaciado uniforme. Evite situaciones que puedan causar escapes de agua. Exterior Inclinación 1/50 Desagüe del agua Vía de la tubería Retirar los tornillos que sujetan el panel frontal. 3 2 1 Vía de la Tubería Fuga de Agua Fuga de Agua 4 5 5-6 Fuga de Agua Extremo sumejido in agua j ✓ J J J Correcto Incorrecto Incorrecto Incorrecto TUBERÍA DE REFRIGERANTE ! Cuidado En la unidad de resfriamiento WM301 se utiliza un orificio como dispositivo de dilatación. Eso està fijado a la cañería del aire de la unidad interior. Longitud y elevación de la tubería Corte del tubo de cobre Si la tubería es demasiado larga, tanto la capacidad como la fiabilidad de la unidad disminuirán. A medida que aumenta el número de curvas, aumenta la resistenci al flujo de refrigerante, reduciéndose por lo tanto la capacidad de enfriamiento, lo cual puede resultar en un compresor defectuoso. Siempre escoger el camino más corto posible y seguir la recomendación tal como se indica en la siguiente tabla: 07/10 Longitud máxima, m (ft), L 15 20 25 30 Elevación máxima m (ft), H 5 (16,4) 5 (16,4) 8 (26,2) 8 (26,2) 15 (49,2) N° máx. de curvas 10 10 10 10 10 Tamaño de la tubería de líquido 1/4" 1/4" 1/4" 3/8" 3/8" Tamaño de la tubería de gas 3/8" 1/2" 5/8" 5/8" 5/8" Observación: Retirar las Rebabas 12 (39,4) 12 (39,4) 15 (49,2) 15 (49,2) 35 (114,8) Bloque de Estampar Tubo de Cobre El refrigerante precargado en la unidad de exterior está previsto para una longitud de tubería de 7,62m/25ft. Conexión de las tuberías a las unidades • Unidad Interior • Alinee el centro de la tubería y apriete suficientemente la tuerca abocinada con los dedos. Finalmente, apriete la tuerca abocinada con la llave dinamométrica hasta que la llave haga “clic”. Par Nm / (Ft-lb) Tamaño de la Tubería mm / (in) 6,35 (1/4) 9,53 (3/8) 12,7 (1/2) 15,88 (5/8) L 18 42 55 65 Español Modelo (13,3) (31,0) (40,6) (48,0) H Ø Tubo, D Unidad Exterior Instalación de tuberías Pulgada mm Pulgada 1/4" 3/8" 1/2" 5/8" 6,35 9,52 12,70 15,88 1,3 1,6 1,9 2,2 Tubo Abocinado Junta Abocinada • No use tuberías de cobre dañadas o contaminadas. No se deben retirar los tapones de plástico y caucho, las tuercas de latón de las válvulas, accesorios, tuberías y serpentines hasta que se esté listo para conectar las líneas de succión o de líquido a las válvulas o accesorios. • Si fuese necesario efectuar alguna soldadura, asegúrese de hacer circular el gas nitrógeno por el serpentín y las juntas durante la realización de la soldadura. Esto evitará la formación de hollín en las paredes interiores de las tuberías de cobre. • Corte el tubo de conexión con un cortatubos. • Retire las rebabas de los bordes cortados de las tuberías con un extractor. Ponga el extremo de la tubería hacia abajo para evitar que los fragmentos metálicos de las rebabas entren en la tubería. • Inserte las tuercas abocinadas, montadas sobre las partes de la conexión tanto de la unidad de interior como de la unidad de exterior, en las tuberías de cobre. • Abocine el tubo con largura extra por encima de la herramienta de abocinar como se muestra en el cuadro. • El borde abocinado debe estar plano, sin grietas ni rasguños. A (mm) Rigido Tubería De Interior Tuerca Abocinada Llave Dinamométrica Llave De tuercas 5-7 0,7 1,0 1,3 1,7 CONEXIÓN DEL CABLEADO ELÉCTRICO Unidad de enfriamiento IMPORTANTE : * Los valores mostrados arriba se dan a título informativo únicamente. Estos deben ser verificados y seleccionados a fin de que cumplan con los códi gos y reglamentos locales y/o nacionales. También están sujetos al tipo de instalación y al tamaño de los conductores. ** L’appropriato intervallo di tensione deve essere confrontato con i dati della targa dell’apparecchio. ETL unità elencata è soltanto applicabile ad alimentazione di 60Hz esclusivamente. Modelo Intérieure Extérieure WM 071/ 101/ 151 SL07/ 10/ 15B Margen de la tensión** WM201/ 251/ 301 SL20/ 25/ 30B 220V-240V/ 1Ph/ 50Hz + 5WM311 5SL28C WM301 SL30C o 208V-230V/ 1Ph/ 60Hz + WM201/ 251/ 301 SL20/ 25/ 30B WM301 SL30C 380V-415V/ 3Ph/ 50Hz +N+ Tamaño del cable de alimentación* mm2 Número de alambre 1,5 3 2,5 3 2,5 3 4 3 1,5 5 1,5 5 Tamaño del cable de interconexión* mm2 Número de alambre 1,5 3 2,5 3 2,5 3 2,5 4 1,5 4 1,5 4 Fusible recomendado 15 20 20 25 15 15 A WM301 VS SL30C WM07 / 10 / 15 / 20 / 25 / 301 VS SL07 / 10 / 15 / 20 / 25 / 30B 5WM311 VS 5SL28C Regleta De Terminales Regleta De Terminales Unidad De Exterior Unidad De Interior Regleta De Terminales Unidad De Interior Regleta De Terminales Unidad De Exterior L COMP N COMP COMP N2 N N2 S N1 R N1 L COMP L L El Cable Del Enchufe El Cable Del Enchufe ! N ! La fuente de alimentación debe poseer dispositivos de protección (disyuntor o fusible) con un sistema de separación bipolar con una separación entre contactors minima de 3mm. WM201 / 251 VS SL20 / 25B (3 La Fase) Regleta De Terminales Unidad De Interior La fuente de alimentación debe poseer dispositivos de protección (disyuntor o fusible) con un sistema de separación bipolar con una separación entre contactors minima de 3mm. WM301 VS SL30C (3 La Fase) Regleta De Terminales Unidad De Exterior Regleta De Terminales Unidad De Interior COMP Regleta De Terminales Unidad De Exterior COMP COMP L COMP L N2 N N2 N N1 N1 R L L R S S T El Cable Del Enchufe El Cable Del Enchufe N T N ! La fuente de alimentación debe poseer dispositivos de protección (disyuntor o fusible) con un sistema de separación bipolar con una separación entre contactors minima de 3mm. ! La fuente de alimentación debe poseer dispositivos de protección (disyuntor o fusible) con un sistema de separación bipolar con una separación entre contactors minima de 3mm. • Todos los alambres deben estar conectados firmemente. • Ningún alambre debe tocar ninguna de las tuberías de refrigerante, el compresor ni las piezas móviles del motor del ventilador. • Los alambres de conexión entre la unidad de interior y la unidad de exterior deben estar sujetados a la abrazadera del alambre según la figura mostrada. • El cable del enchufe para el toma corriente debe de ser equivalente H05RN-F (245IEC57), tomando este como un minimo requerimiento. El Cable Utilizado Para Juntar Cable De Interconexión 5-8 Unidad de calentamiento IMPORTANTE : * Los valores mostrados arriba se dan a título informativo únicamente. Estos deben ser verificados y seleccionados a fin de que cumplan con los códi gos y reglamentos locales y/o nacionales. También están sujetos al tipo de instalación y al tamaño de los conductores. ** L’appropriato intervallo di tensione deve essere confrontato con i dati della targa dell’apparecchio. ETL unità elencata è soltanto applicabile ad alimentazione di 60Hz esclusivamente. Modelo Intérieure WM 071/ 101/ 151 R WM201/ 251/ 301 R 5WM301R WM301 R WM201/ 251/ 301 R WM301 R Extérieure SL07/ 10/ 15BR SL20/ 25/ 30BR 5SL28CR SL30CR SL20/ 25/ 30BR SL30CR Margen de la tensión** 220V-240V/ 1Ph/ 50Hz + o 208V-230V/ 1Ph/ 60Hz + 380V-415V/ 3Ph/ 50Hz +N+ Tamaño del cable de alimentación* mm2 Número de alambre 1,5 3 2,5 3 2,5 3 4 3 1,5 5 1,5 5 Tamaño del cable de interconexión*mm2 Número de alambre 1,5 5 2,5 5 2,5 5 2,5 6 1,5 6 1,5 4 Fusible recomendado 15 20 20 25 15 15 A WM301R VS SL30CR WM07 / 10 / 15 / 20 / 25 / 301R VS SL07 / 10 / 15 / 20 / 25 / 30BR 5WM301R VS 5SL28CR Alambre de conexión del sensor del serpentín de exterior (8m de longitud) sujetado a la unidad de interior Alambre de conexión del sensor del serpentín de exterior (8m de longitud) sujetado a la unidad de interior Regleta De Terminales Unidad De Interior Regleta De Terminales Unidad De Interior Regleta De Terminales Unidad De Exterior 4WV 4WV OF OF COMP COMP N2 N1 N Regleta De Terminales Unidad De Exterior A 4WV 4WV OF OF COMP COMP N2 L N1 N L L El Cable Del Enchufe El Cable Del Enchufe Español N L ! La fuente de alimentación debe poseer dispositivos de protección (disyuntor o fusible) con un sistema de separación bipolar con una separación entre contactors minima de 3mm. ! WM201 / 251R VS SL20 / 25BR (3 La Fase) La fuente de alimentación debe poseer dispositivos de protección (disyuntor o fusible) con un sistema de separación bipolar con una separación entre contactors minima de 3mm. WM301R VS SL30CR (3 La Fase) Alambre de conexión del sensor del serpentín de exterior (8m de longitud) sujetado a la unidad de interior Alambre de conexión del sensor del serpentín de exterior (8m de longitud) sujetado a la unidad de interior Regleta De Terminales Unidad De Interior 4WV Regleta De Terminales Unidad De Exterior Regleta De Terminales Unidad De Interior Regleta De Terminales Unidad De Exterior A 4WV 4WV 4WV OF OF COMP COMP N2 L N2 L N1 N N1 N OF OF COMP COMP L L R R S El Cable Del Enchufe S T T El Cable Del Enchufe N N ! ! La fuente de alimentación debe poseer dispositivos de protección (disyuntor o fusible) con un sistema de separación bipolar con una separación entre contactors minima de 3mm. 5-9 La fuente de alimentación debe poseer dispositivos de protección (disyuntor o fusible) con un sistema de separación bipolar con una separación entre contactors minima de 3mm. PRECAUCIONES ESPECIALES PARA EL R410A • • • • • • R410A es un refrigerante casi azeotrópico de mezcla hidro fluorocarbonada (HFC) que respeta el medio ambiente. Tiene un ODP = 0 y cumple con las regulaciones del Protocolo de Montreal. No tiene propagación de llama y es un refrigerante de baja toxicidad (clasificado como A1 por ARI). El R410A es una mezcla de R32 (50%) y R125 (50%). El aceite de POE se utiliza para la lubricación del compresor con el refrigerante R410A, y es diferente al ageite mineral empleando con el refrigerante R22. Durante la instalación se debe tener la precaución extra de no exponer el circuito refrigerante demasiado tiempo a la intemperie, ya que el refrigerante R410A puede absorber la humedad del aire. Si se compara el refrigerante R410A con el refrigerante R22, el refrigerante R410A se ve más afectado por la humedad y las partículas sólidas, se racomienda tapar siempre los finales de tubería con tapones mientras se hace la instalación. No se permite la carga adicional de aceite al compresor. No se puede emplear ningún refrigerante más que el R410A. Herramientas específicas para el refrigerante R410A i) Manómetros y mangueras de descarga ii) Detector de escape de Gas iii) Cilíndro de carga del refrigerante iv) Bomba de vacio v) Abocardador vi) Máquina de recuperación de refrigerante ! CUIDADO • • • R410A se debe cargar como líquido. Generalmente cilíndro R410A se equipa con un tubo de depresión para la retirada líquida. Si no hay tubo de depresión, el cilíndro se debe invertir para retirar líquido R410A de la válvula. Cuando exista una fuga en el circuito se debe de extraer el refrigerante que quede. Corregir la fuga, hacer el vacio. Y cargar por peso el equipo con R410A en los datos originales de no hacerlo as y se repone refrigerante, el rendimiento del equipo se reducirà. No toque el compresor o las tuberías de refrigerante con la unidad en funcionamiento. Si lo hace, utilice guantes. LIMPIEZA DE LA TUBERÍA DE REFRIGERANTE Limpieza de la tubería y la unidad de interior Carga adicional Salvo la unidad de exterior que esta precargada con refrigerante, se debe limpiar con chorro de aire la unidad de interior y las tuberías de conexión de refrigerante puesto que el aire que contiene humedad que queda en el ciclo del refrigerante puede causar un funcionamiento defectuoso del compresor. • Retirar las tapas de la válvula y del agujero de servicio. • Conecte el centro del calibrador de carga a la bomba de vacío. • Conecte el calibrador de carga al orificio de servicio de la válvula de 3 vías. • Arranque la bomba de vacío. Evacue aproximadamente durante 30 minutos. El tiempo de evacuación varía según la capacidad de la bomba de vacío. Asegúrese de que la aguja del calibrador de carga se ha movido hacia - 76mmHg (0~76mmHg). Cuidado Si la aguja del calibrador no se mueve a 0-76mmHg, compruebe las fugas de gas (utilizando detector de refrigerante) en la conexión de tipo abocinada de la unidad interior y exterior y repare la fuga antes de seguir con el siguiente paso. • Cierre la válvula del calibrador de cambio y pare la bomba de vacío. • En la unidad exterior, abra la válvula de succión (3 vías) y la válvula líquida (2 vías) (en la dirección contraria a las agujas del reloj) con una llave de 4mm para tornillos hexagonales. El refrigerante está precargado en la unidad de exterior. Si la longitud de la tubería es inferior a 7,62m (25 ft), no es necesaria una carga adicional después de la aspiración. Si la longitud de la tubería es de más de 7,62m (25 ft), siga los valores de carga adicional tal y como se indica en la tabla a continuación. Tuerca Tubería de refrigerante Abocinada Llave Allen Agujero De Servicio Unidad Interior Válvula de 3 vías de la unidad de exterior Lado del liquido Válvula de descarga Unidad Exterior Cerrada Lado del gas Válvula de Succión Abierta Pomba de Vacío Lo Cerrada Hi Cerrada 5-10 • Abrir la válvula del cilindro de gas y la de cierre de baja presión • Cuando se haya bombeado la unidad con la cantidad de refrigerante requerida, cerrar la válvula de baja presión y del cilindro de gas. • Desconectar la manguera de servicio del agujero de servicio. Volver a colocar la tapa del agujero de servicio. Carga adicional en gramos (R22) Modelo 071 / 101 / 151 201 251 / 301 071R / 101R /151R 201R 251R / 301R 10 m/32,8 ft 35 35 90 50 60 120 12 m/39,4 ft 65 65 165 90 110 220 15 m/49,2 ft 110 280 185 370 Carga adicional en gramos (R410A) Modelo 311 301R 10 m/32,8 ft 80 110 12 m/39,4 ft 150 200 Unidad Interior 15 m/49,2 ft 255 335 Lado del liquido Unidad Exterior Válvula de carga Cerrada Operación de carga Esta operación se debe realizar usando un cilindro de gas y una máquina de pesaje obligatoriamente. La carga adicional se introduce en la unidad de exterior por la válvula de aspiración a través del agujero de servicio. • Retirar el tapón del agujero de servicio. • Conectar el lado de presión baja del calibrador de carga al centro del agujero de servicio de succión del depósito del cilindro y cierre el lado de alta presión del calibrador. Purgue el aire de la manguera de servicio. • Poner en marcha la unidad de aire acondicionado. Receptor de señal IR (infrarroja) Lado del gas Válvula de Succión Válvula de control Cerrada Lo Abierta Hi Cerrada LUZ INDICADORA Unidad de enfriamiento Al transmitirse una señal de infrarrojos proveniente del mando a distancia, el receptor de señales de la unidad de interior producirá un sonido para confirmar la aceptación de la señal transmitida. La tabla que se muestra a continuación contiene las luces indicadoras LED de funcionamiento normal y de condición de falla de la unidad de aire acondicionado. Las luces indicadoras LED están situadas en la parte inferior derecha de la unidad de aire acondicionado. Receptor Infrarrojo Preder ON El Programador del Tiempo Modo Seco Modo Vigilia Luces indicadoras LED Luces indicadoras LED : Condiciones de operación normales y condiciones de operación defectuosas de la unidad de enfriamiento Operación/Indicador de falla Preder Seco El Programador del Tiempo Vigilia Programador de tiempo prendido ON. – Modo vigilia ON. – Modo seco. – Prevention de congelamiento hielo. Continua una vez cada 2 segundos dos veces cada 2 segundos tres veces cada 2 segundos ENCENDIDO Acción Limpiar el filtro y pasar a ventilador alto. Contacto del sensor de aire ambiente suelto/corto. Llamar a su representante. Contacto del sensor del serpentín de interior suelto/corto. Llamar a su representante. El sensor contacto de problema, proteccion para sobrecarga del compresor, goteadura o escape de gas. Llamar a su representante. ENCENDIDO o APAGADO 5-11 Parpadeante Español Luces indicadoras LED de funcionamiento para la unidad de enfriamiento. Luces indicadoras LED de funcionamiento para la unidad de calentamiento Unidad de calentamiento La tabla que se muestra a continuación contiene las luces indicadoras LED para el funcionamiento normal y la condición de falla de la unidad de aire acondicionado. Las luces indicadoras LED están situadas en la parte inferior derecha de la unidad de aire acondicionado. Las unidad de calentamiento cuenta con un modo “auto”, mediante el cual la unidad podrá proporcionar temperatura de habitación moderada, simplemente con encender automáticamente en posición “cool” (frío) o “heat” (calor), de acuerdo a la temperatura seleccionada por el usuario. Modo de Modo seco enfriamiento Modo Programador para Calentador / Ventilador (rojo / verde) Modo vigilia Luces indicadoras LED : Condiciones de operación normales y condiciones de operación defectuosas de la unidad de calentamiento Frio Seco Ventilador Oscilación Vigilia Condiciones de operación normales / condiciones de operación defectuosas Modo de enfriamiento. Acción – Modo seco. – Modo ventilador. – Modo de calentamiento. – Modo automático en funcionamiento como calentador. – Modo automático en funcionamiento como enfriador. – Operación de descongelación. – Protección de sobrecarga del compresor. Llamar a su representante. Contacto del sensor del serpentín de interior suelto /corto. Llamar a su representante. Contacto del sensor del serpentín de exterior suelto /corto. Llamar a su representante. Contacto del sensor de aire ambiente suelto /corto. Llamar a su representante. Si el sistema está en el modo de calentamiento o enfriamiento (con la funcion de vigilia apagada), es posible que el sensor tenga un problema de contacto, se haya disparado la proteccion de sobrecarga del compresor o haya una fuga de gas. ENCENDIDO ENCENDIDO o APAGADO 5-12 Parpadeante OPERACIÓN DE LA UNIDAD DE AIRE ACONDICIONADO Modo seco Prevención de congelamiento • Cuando la humedad del aire es alta, la unidad puede operar en modo seco. Pulse el botón de modo de funcionamiento <MODE> y elija el seco <DRY>. • Si la temperatura de la habitación está 2°C/35,6°F por encima de la temperatura elegida en el ajuste, entonces la unidad de aire acondicionado funcionará en modo de enfriamiento hasta que se quede a 2°C/35,6°F de diferencia, comparada con la temperatura elegida antes de pasar a modo seco. • Si la temperatura de la habitación está dentro de un margen de 2°C/35,6°F de diferencia, comparada con la temperatura elegida en el ajuste, funcionará directamente en modo seco. • En el modo de funcionamiento seco, la unidad funcionará a BAJA velocidad. • • Cuando el filtro de aire está sucio, la temperatura de evaporación descenderá y acabará por causar hielo. La luz “LED” empezará a parpadear para indicar que el filtro está sucio. Si la temperatura de evaporación alcanza los -2°C/28,4°F la unidad reaccionará y se descongelará. Velocidad del ventilador y capacidad de enfriamiento especificada • • La capacidad de enfriamiento especificada se provee con el ventilador a máxima velocidad. La capacidad de enfriamiento es más baja cuando la unidad funciona con el ventilador a velocidades media y baja. Modo de calefacción (únicamente para unidad de calentamiento) Horizontal Enfriamiento Seco • Cuando la unidad acaba de ser encendida o de pasar por el ciclo de deshielo, el ventilador de adentro sólo empezará a funcionar después de que el serpentín alcance la temperatura deseada. • Cuando se alcanza la temperatura elegida en el ajuste, el ventilador de adentro funcionará hasta que el serpentín no pueda proveer más calor adicional. 25°C/77°F Control Del Flujo De Aire Horizontal Español • Para lograr una circulación de aire más eficaz, se puede ajustar la rejilla de descarga de aire hacia la izquierda o la derecha manulmente. • Durante el funcionamiento en modo enfriamiento y seco, no dirigir la rejilla directriz de descarga de aire hacia abajo mucho tiempo. Si el funcionamiento continúa de esta manera, puede haber condensación en la rejilla directriz. Puede haber goteo como resultado de la condensación. HOT KEEP OFF Mantiene Caliente (Sólo para la bomba de calefacción) • • INTERVAL ON Durante la desconexión del compresor, el ventilador interno podría estar: (i) ON [en posición de encendido] (default) o (ii) OFF [en posición de encendido] o (iii) en posición de encendido y cerrado intervalo por medio de ajustar la conexión de corredera en el diagrama. El interruptor situado en la cubierta delantera del cuandro (junto al butón de conexión). Interruptor ON/OFF NOTA : Cuando se selecciona la opción, la fuente de alimentación de la necesidad de la unidad de ser reajustado para activar la función. Protección contra el sobre-calentamiento (únicamente para unidad de calentamiento) • En caso de que la temperatura interna y/o externa sean demasiado altas, o que el filtro esté sucio y obstruido, puede que el refrigerante se sobre-caliente. El compresor se parará sólo cuando la temperatura de condensación alcance los 62°C/143,6°F. 5-13 CONDICION DE FUNCIONAMIENTO ESTÁNDAR Unidad de calentamiento Unidad de enfriamiento Temperatura Ts °C / °F Th °C / °F Temperatura Ts °C / °F Th °C / °F Temperatura interior mínima 19,4 / 66,9 13,9 / 57,0 Temperatura interior mínima 10 / 50 – Temperatura interior máxima 26,7 / 80,1 19,4 / 66,9 Temperatura interior máxima 26,7 / 80,1 – Temperatura exterior mínima 19,4 / 66,9 13,9 / 57,0 Temperatura exterior mínima -8 / 17,6 -9 / 15,8 Temperatura exterior máxima 46 / 114,8 24 / 75,2 Temperatura exterior máxima 24 / 75,2 18 / 64,4 Ts: Temperatura de ampolla seca. Th: Temperatura de ampolla húmeda. ! Advertencia • • Desconecte la unidad de aire acondicionado de su fuente principal de electricidad antes de intentar repararla. NO tire del cordón de alimentación cuando la alimentación está conectada. Esto puede causar graves sacudidas lo que puede producir un incendio. FILTRO ELECTROSTÁTICO PURIFICADOR DE AIRE ELECTROSTÁTICO DE ACCIÓN DUAL Y FILTRO DESODORIZADOR Y MARCO DE FILTRO ACCIÓN 1PURIFICADOR DE AIRE ELECTROSTÁTICO ACCIÓN 2FILTRO DESODORIZADOR Elimine el polvo microscópico, humo y pequeñas partículas invisibles para mantener el aire de la habitación limpio mediante el filtro de polipropileno electrostático precargado. Elimine odores desagradables y odores en el aire y mantenga el aire en la habitación fresco mediante el filtro de carbón activado. MODO DE INSTALACIÓN Abarala rejilia del marco frontal. Inserte los filtros de acción dual electrostaticos y desodorizadores en la ranura. Deslice los filtro original hacia el exterior. Deslice los filtro originales en su antigua posición. 5-14 ! Cuidado 1. Los filtros purificadores y desodorizadores de aire se deben cambiar cada seis meses o cuando el color del filtro cambie a amarronado, cualquiera de los casos que se de con anterioridad. 2. Tire el filtro usado con polvo y no lo utilice de nuevo, incluso después de haber sido lavado y limpiado. 3. El filtro es una artículo consumible, que Ud. puede obtener en cualquier agente de acondicionadores de aire. 4. Utilice el nuevo filtro inmediatamente después de desenvolverlo. No envuelva el filtro nuevo demasiado pronto antes de ser usado, pues podría disminuir su efecto desodorizante. ! Advertencia • • Desconecte la unidad de aire acondicionado de su fuente principal de electricidad antes de intentar repararla. NO tire del cordón de alimentación cuando la alimentación está conectada. Esto puede causar graves sacudidas lo que puede producir un incendio. REPARACIONES Y MANTENIMIENTO 1. Filtro de aire (unidad de interior) 2. 3. Procedimientos Para Su Maintenimento Elimine el polvo adherido al filtro mediante una aspiradora o lavándolo en agua templada (a menos de 40°C/104°F) con un jabón neutro. Enjuague y seque bien el filtro antes de volverlo a colocar en la unidad. No use gasolina, sustancias volátiles ni productos químicos para limpiar el filtro. 1. Limpie cualquier suciedad o polvo de la rejilla o el panel con un trapo suave empapado de agua tibia (a menos de 40°C/104°F) con una solución detergente neutra. Unidad de interior 2. No use gasolina, sustancias volátiles ni productos químicos para limpiar la unidad de interior. Precuencia Al menos una vez cada dos semanas. Con mayor frecuencia si es necesario. Al menos una vez cada dos semanas. Con mayor frecuencia si es necesario. ! Cuidado No opere aparatos de calor cerca de la unidad de aire acondicionado. Esto puede fundir o deformar el panel de plástico como resultado del excesivo calor. CUANDO NO SE VA A USAR LA UNIDAD POR UN TIEMPO PROLONGADO Opera la unidad durante 2 horas con el siguiente programa. Modo de funcionamiento : cool (“frio”) Temperatura : 30˚C/86˚F Retirar al clavija de alimentación. Si se usa un circuito eléctrico independiente para su unidad, cortar el circuito. Retirar las baterías del control remoto. 5-15 Español Componentes LOCALIZACIÓN DE AVERIAS Cuando detecte alguna anomalia en el funcionamiento de la unidad de aire acondicionado, desconéctela inmediatamente de la fuente de alimentación eléctrica. Como unas simples pistas para el mantenimiento y las reparaciones, compruebe los siguientes fallos y sus causas. Causa / Acción Falla 1. El compresor no empieza a funcionar 3 minutos después de haber puesto en marcha la unidad de aire acondicionado. - Protección contra los arranques frecuentes. Espere 3 ó 4 minutos hasta que el compresor comience a funcionar. 2. La unidad de aire acondicionado no funciona. 6. Sale agua de la unidad de aire acondicionado. - Falla de alimentación o se debe remplazar el fusible. - La clavija de alimentación está desconectada. - Es posible que no haya ajustado correctamente el temporizador de retardo. - Si la falla persiste después de estas verificaciones, póngase en contacto con el instalador de la unidad. - El filtro de aire está sucio. - Las puertas o ventanas están abiertas. - La entrada y salida del aire están obstruidas. - La temperatura elegida en el ajuste no es lo suficientemente alta. - Estos olores se pueden deber a particularas de humo de cigarrillo, perfume, sudor, etc. que se hayan adherido al serpentin. - Esto se debe a la humedad del aire, después de un tiempo de funcionamiento prolongado. - La temperatura elegida en el adjuste es demasiado baja. Aumente la temperatura elegida y empieece la unidad con el ventilador a alta velocidad. - Desconecte la unidad y llame a su concesionario. 7. El fluio de aire suena como un silbido cuando la unidad de aire acondicionado está en funcionamiento. - El líquido refrigerante está infiltrándose en el infiltrándose en el serpentin del evaporador. 3. El flujo de aire es demasiado bajo. 4. El flujo de aire de descarge huele mal. 5. Condensación en la rejilla de aire frontal-unidad de interior. Si la averia persiste, póngase en contacto con el técnico o vendedor local. 5-16 РУКОВОДСТВО ПО УСТАНОВКЕ Это руководство рассматривает процедуру установки с целью обеспечения безопасности и соответствующих стандартов для функционирования блока кондиционера. Специальная регулировка по месту установки может быть необходима. Перед использованием Вашего кондиционера, прочитайте, пожалуйста, внимательно данное руководство по эксплуатации и сохраните его для обращения за справками в будущем. НАСТЕННЫЙ КОНДИЦОНЕР РАЗДЕЛЬНОГО ТИПА ТОЛЬКО ОХЛАЖДЕНИЕ (R22) ОБОГРЕВАТЕЛЬНЫЙ НАСОС (R22) Справочная модель Модель Справочная модель Модель WM301 SL30C SL30B AWM301 ALC30C ALC30B WM301R SL30CR SL30BR AWM301R ALC30CR ALC30BR ТОЛЬКО ОХЛАЖДЕНИЕ (R410A) ОБОГРЕВАТЕЛЬНЫЙ НАСОС (R410A) Справочная модель Модель Справочная модель Модель 5WM311 5SL28C A5WM311 A5LC28C 5WM301R 5SL28CR A5WM301R A5LC28CR IM-WM1-0302(2)-Acson Part No.: A08019025521 6-1 Русский Модель СОДЕРЖАНИЕ - Схема и Размеры - Меры Предосторожности - Рисунок Установки - Установка Комнатного Блока - Монтаж Дроссельной трубки - Установка Наружного Блока - Проведение Трубопроводов Хладагента - Электрическая Схема Соединений страница i-ii страница 2 страница 3 страница 3 страница 4 страница 6 - Специальные меры предосторожности при обращении с R410A страница 10 - Откачка Воздуха и Заправка страница 10 - Показания Индикаторов страница 11 - Операция Модуля Кондиционера страница 13 - Уcлoвия Стандapтннй Рaвоты страница 14 - Электростатический Фильтр При Наличии страница 14 - Сервис и Техническое Обслуживание страница 15 - Меры по Устранению страница 16 страница 7 страница 8 МЕРЫ ПРЕДОСТОРОЖНОСТИ Перед установкой блока кондиционера, прочитайте, пожалуйста, внимательно меры предосторожности. ! Внимание • Установка и техническое обслуживание должны проводиться квалифицированным персоналом, знающим местный код и положения и имеющим опыт работы с данным видом устройств. • Весь монтаж проводов должен проводиться в соответствии с национальными правилами электромонтажа. • Перед началом электромонтажа удостоверьтесь, что напряжение блока соответствует указанному на табличке, согласно электрической схеме. • Блок должен быть ЗАЗЕМЛЕН для предотвращения возможной опасности в результате неправильной установки. • Вся электропроводка должна не приходить в соприкосновение с хладагентом насоса или лопастей двигателя. • Удостоверьтесь, что блок ВЫКЛЮЧЕН перед установкой или обслуживанием. ВАЖНО НЕ УСТАНАВЛИВАЙТЕ ИЛИ НЕ ИСПОЛЬЗУЙТЕ КОНДИЦИОНЕР В МОЕЧНОЙ. ! Осторожно Пожалуйста, обратите внимание на нижеследующие важные моменты при установке. • Не устанавливайте блок в месте, где может произойти утечка взрывоопасного газа. Если имеется утечка газа и его сбор рядом с блоком, то он может стать причиной возгорания. • Удостоверьтесь, что сливные трубы соединены надлежащим образом. Если сливные трубы не соединены надлежащим образом, это может стать причиной течи, которая намочит мебель. • Не подвергайте перегрузке блок Данный блок установлен на определенную нагрузку на заводе-изготовителе. Перегрузка вызовет перегрузку тока или повредит компрессор. • Удостоверьтесь, что панель блока закрыта после технического обслуживания или установки. Неплотно закрепленные панели вызовут шум при работе блока. 6-2 РИСУНОК УСТАНОВКИ Наружный Блок Воздушный фильтр Передняя панель Решетка впуска воздуха Задняя панель Включатель ВКЛ/ВЫКЛ Показания индикаторов Жалюзи выпуска воздуха Дренажный шланг Датчик сигналов Решетка выпуска воздуха Впуск воздуха Трубопровод хладогента Впуск воздуха Отверстие выпуска воздуха Комнатный Блок Пространство для установки 1000 (39,4) C 300 (11,8) C D 500 (19,7) Примечание: При наличии препятствия высотой более 2м, или препятствия в верхней части модуля, пожалуйста, обеспечьте большее пространство, чем указано в таблице вверху. 6-3 D Доступ Технического Обслуживания Препятствие 300 (11,8) B Возврат Воздуха (дюйм) A Препятствие Размер Мин. Расстояние, мм Русский B Препятствие A Выпуск воздуха Препятствие Внутренний модуль должен быть установлен так, чтобы предотвратить короткого замыкания выпуска горячего воздуха, или обеспечить беспрепятственный поток воздуха. Пожалуйста, оставьте пространство для установки, как показано на рисунке. По возможности выберите как можно холодное место, где температура впуска воздуха не превышает температуру воздуха на улице (максимум 45°C/ 113°F). Возврат Воздуха УСТАНОВКА КОМНАТНОГО БЛОКА МОНТАЖ ДРОССЕЛЬНОЙ ТРУБКИ Дроссельная трубка 2 3 4 1 К наружному блоку В помещение 1 Диафрагма 3 Накидная гайка 3/8" (внутренняя резьба) 2 Трубка соединительная 4 Резьбовый патрубок 3/8" (наружная резьба) Примечание: Эта установка производится только для моделей WM301 / SL30B и WM301 / SL30C. ! Осторожно Дроссельной трубку необходимо устанавливать в правильном направлении, как показано выше. Установка в неправильном направлении может привести к выходу системы из строя. A. Монтаж дроссельной трубки для наружного блока (при наличии свободного места для выполнения установки) Шаг 2 Дроссельная трубка Шаг 1 Шаги: 1. Навинтить накидную гайку дроссельной трубки непосредственно на жидкостный вентиль. 2. Развальцевать жидкостную трубу и присоединить ее к резьбовому патрубку дроссельной трубки. Дроссельная трубка 6-4 Жидкостная труба B. Монтаж дроссельной трубки для наружного блока (при условии ограниченного пространства для выполнения установки) Шаг 4 Дроссельная трубка Шаг 3 Шаг 2 Шаг 1 Если дроссельную трубку невозможно присоединить непосредственно к жидкостному вентилю из-за тесноты, ее можно врезать в жидкостную трубу. Шаги: 3. Навинтить накидную гайку дроссельной 1. Развальцевать жидкостную трубу и трубки на патрубок с наружной резьбой. присоединить ее к жидкостному вентилю. Жидкостная труба 2. Припаять (твердым припоем) к жидкостной трубе дополнительный патрубок с наружной резьбой. Дроссельная трубка 4. Развальцевать другую жидкостную трубку и присоединить ее к резьбовому патрубку дроссельной трубки. Жидкостная труба Жидкостная труба Дроссельная трубка Паяльник Русский C. Монтаж дроссельной трубки для внутреннего блока Наружный Блок Дроссельная трубка Шаги: 1. Припаять (твердым припоем) к жидкостной трубе дополнительный патрубок с наружной резьбой. 2. Навинтить накидную гайку дроссельной трубки на патрубок с наружной резьбой. Жидкостная труба Жидкостная труба Дроссельная трубка Паяльник 6-5 3. Развальцевать другую жидкостную трубку и присоединить ее к резьбовому патрубку дроссельной трубки. Жидкостная труба Дроссельная трубка УСТАНОВКА НАРУЖНОГО БЛОКА Внутренний модуль должен быть установлен так, чтобы предотвратить столкновение выпуска холодного воздуха с возвращающимся потоком горячего воздуха. Пожалуйста, оставьте пространство для установки, как показано на рисунке. Не устанавливайте внутренний модуль там, где модуль подвергается воздействию прямых солнечных лучей. Также расположение должно быть удобным для прокладки трубопроводов и дренажа и удалено от дверей и окон. 50mm 50мм Прокладка трубопровода хладагента может быть осуществлена несколькими способами (слева или справа модуля), через выламывающиеся отверстия на корпусе модуля (смотрите рисунок). Осторожно согните трубы в необходимое положение для провода через отверстия. Для провода справа или сзади, подведите трубы и расположите их в необходимом направлении (смотрите рисунок). Дренажный шланг конденсации может быть зафиксирован к трубам. 50mm 50мм 50mm 50мм Прокладка Справа и Сзади Выше уровня глаз Направление Потока Воздуха Пространство Для Ремонта и Технического Обслуживания Крепежная плита Установите Модуль На Панель Крепления Навесьте модуль на верхнюю часть панели крепления (Подвесьте двумя крючками задней верхней части внутреннего модуля на верхний край панели крепления). Удостоверьтесь, что крючки на панели крепления установлены должным образом посредством раскачивания их влево и вправо Маркировка – автономный режим Резьба Установка Панели Крепления Удостоверьтесь, что стена достаточно крепкая и может выдержать вес модуля. В противном случае, усильте стену панелями, балками или стойками. С помощью уровня добейтесь горизонтальное положение, и закрепите панель при помощи 4 крепежными шурупами. В случае, если задние трубопроводы выступают, просверлите диаметром 65мм коническим сверлом отверстие, расположенное более низко на наружной стене (смотрите рисунок). Кабель Межсоединения Дренажный шланг Трубопровод Дренажа Воды Внутренняя дренажная труба должна быть установлена с уклоном вниз для дренажа. Избегайте ситуаций, которые могут привести к течи воды. комнатный Наружный Пренаж Воды Погруженный Конец в Воду Наклон 1/50 Прокладка Трубопроводов Снимите винт, крепящий переднюю панель. Течь Воды 3 2 1 Прокладка трубопроводов ✓ j 4 Течь Воды J ПРАВИЛЬНО НЕПРАВИЛЬНО 5 6-6 Течь Воды J J НЕПРАВИЛЬНО НЕПРАВИЛЬНО ПРОВЕДЕНИЕ ТРУБОПРОВОДОВ ХЛАДАГЕНТА ! Осторожно Только в воздухоохладителе WM301 в качестве расширительного устройства используется сопло, которое закреплено на жидкостном трубопроводе во внутреннем блоке. Длина трубопроводов и подъем Резка Медных Труб Если трубопровод слишком длин, то мощность и надежность функционирования модуля упадет. С числом сгибов, сопротивление потока хладагента увеличивается, понижая степень охлаждения. Это в результате может привести к поломке компрессора. Всегда пытайтесь делать трубопровод как можно короче и следуйте рекомендациям в таблице внизу: Модель 07/10 15 20 25 30 Макс. длина, м (фут), L 12 (39,4) 12 (39,4) 15 (49,2) 15 (49,2) 35 (114,8) Макс. подъем, м (фут), H 5 (16,4) 5 (16,4) 8 (26,2) Уберите Заусенцы 8 (26,2) 15 (49,2) Макс. число сгибов 10 10 10 10 10 Сечение трубы жидкости 1/4" 1/4" 1/4" 3/8" 3/8" Сечение трубы газа 3/8" 1/2" 5/8" 5/8" 5/8" Медная Труба Обжимка Замечание: Хладагент на внешнем модуле заправлен на заводе-изготовителе из расчета длины трубопровода до 7,62 м / 25 фут. Наружный Блок Соединение Трубопроводов К блокам • Отцентрируйте положение трубы и до конца затяните штуцер усилием пальцев. • Затем, затяните штуцер динамометрическим гаечным ключом до щелчка ключа. L Крутящий Момент Hm / (Ft-lb) 6,35 (1/4) 9,53 (3,8) 12,7 (1/2) 15,88 (5/8) H 18 42 55 65 Ø Трубы, D Комнатный Блок Проведение Трубопроводов • Не используйте грязную или поврежденную трубную обвязку. Не снимайте пластиковое покрытие, резиновые пробки и латунные гайки с клапанов, штуцеров, труб и змеевиков до тех пор, пока он не готов для соединения подачи газа или жидкости в клапана или штуцеры. • Если требуется пайка, то удостоверьтесь, что газ азот проходит через змеевик и соединения, где проводится пайка. Это позволит избежать формирование копоти на внутренней стороне медных труб. • Разрежьте соединительную трубу резаком. • Уберите заусенцы с краев среза трубы съемником. Держите конец трубы вниз, чтобы предотвратить попадание металлических частиц в трубу. • Вставьте штуцерные гайки, установленные на соединяющие концы как внутреннего модуля, так и внешнего модуля, на медные трубы. • Развальцуйте большей длины трубу развальцовочным инструментом, как показано в таблице. • Край после развальцовви должен быть ровным и, без трещин или царапин. A (мм) Дюйм мм 1/4" 3/8" 1/2" 5/8" 6,35 9,52 12,70 15,88 Cоединения Муфтой 6-7 (13,3) (31,0) (40,6) (48,0) Империал Риджид 1,3 1,6 1,9 2,2 Труба С Муфтой Трубопровод Комнатного Блока Штуцерная Гайка Ключ Динамометрический Гаечный Ключ 0,7 1,0 1,3 1,7 Русский Размер Трубы мм / (дюйм) ЭЛЕКТРИЧЕСКАЯ СХЕМА СОЕДИНЕНИЙ Только Охлаждение ВАЖНО: * ** Показатели, представленные в таблице, только для принятия во внимание. Они должны быть сравнены и выбраны для того, чтобы они отвечали местным положениям/государственным стандартам. Они также зависят от типа установки и сечения используемых проводников. Соответствующий диапазон напряжений следует сверять с данными, указанными на табличке, прикрепленной к корпусу аппарата. Указанное значение ETL соответствует только источнику питания с частотой 60 Гц. Модель Комнатный WM 071/ 101/ 151 WM201/ 251/ 301 5WM311 WM301 Наружный SL07/ 10/ 15B SL20/ 25/ 30B 5SL28C SL30C Диапазон напряжения** 220B-240B/ 1Ф/ 50Гц + или 208B-230B/ 1Ф/ 60Гц + WM201/ 251/ 301 WM301 SL20/ 25/ 30B SL30C 380B-415B/ 3Ф/ 50Гц +N+ мм2 1,5 3 2,5 3 2,5 3 4 3 1,5 5 1,5 5 Сечение проводов межсоединения* мм2 Номер провода 1,5 3 2,5 3 2,5 3 2,5 4 1,5 4 1,5 4 Рекомендуемый предохранитель A 15 20 20 25 15 15 Сечение шнура сети* Номер провода WM301 VS SL30C WM07 / 10 / 15 / 20 / 25 / 301 VS SL07 / 10 / 15 / 20 / 25 / 30B 5WM311 VS 5SL28C Терминал Терминал Наружного Блока Комнатного Блока Терминал Комнатного Блока COMP N2 N N2 L N COMP COMP Терминал Наружного Блока S N1 R N1 L COMP L L Шнур Сети Шнур Сети ! ! Электроснабжение должно обеспечено с приборами защиты (автоматический выключатель или предохранитель) с двухполярной сепарационной системой с минимальным расстоянием между клеммами 3 мм. WM201 / 251 VS SL20 / 25B (3 Фáза) Терминал Комнатного Блока Электроснабжение должно обеспечено с приборами защиты (автоматический выключатель или предохранитель) с двухполярной сепарационной системой с минимальным расстоянием между клеммами 3 мм. WM301 VS SL30C (3 Фáза) Терминал Наружного Блока Терминал Комнатного Блока COMP N Терминал Наружного Блока COMP COMP L COMP L N2 N N2 N N1 N1 R R L L S S T Шнур Сети Шнур Сети N T N ! ! Электроснабжение должно обеспечено с приборами защиты (автоматический выключатель или предохранитель) с двухполярной сепарационной системой с минимальным расстоянием между клеммами 3 мм. Зажим Проводов Кабель Межсоединения Электроснабжение должно обеспечено с приборами защиты (автоматический выключатель или предохранитель) с двухполярной сепарационной системой с минимальным расстоянием между клеммами 3 мм. • Все провода должны быть хорошо соединены. • Все электропроводка должна не приходить в соприкосновение с хладагентом насоса или лопастей двигателя. • Провода, соединяющие внутренний модуль и внешний модуль, должны быть закреплены проводными зажимами как показано на рисунке. • Cнур сети питания должен отвечать параметрам шнура H05RN-F (245IEC57), который представляет собой минимальные предъявляемые требования. 6-8 Обогревательный Насос ВАЖНО: * ** Показатели, представленные в таблице, только для принятия во внимание. Они должны быть сравнены и выбраны для того, чтобы они отвечали местным положениям/государственным стандартам. Они также зависят от типа установки и сечения используемых проводников. Соответствующий диапазон напряжений следует сверять с данными, указанными на табличке, прикрепленной к корпусу аппарата. Указанное значение ETL соответствует только источнику питания с частотой 60 Гц. Модель Комнатный WM 071/ 101/ 151 R WM201/ 251/ 301 R 5WM301R WM301 R WM201/ 251/ 301 R WM301 R Наружный SL07/ 10/ 15BR SL20/ 25/ 30BR 5SL28CR SL30CR SL20/ 25/ 30BR SL30CR Диапазон напряжения** 220B-240B/ 1Ф/ 50Гц + или 208B-230B/ 1Ф/ 60Гц + 380B-415B/ 3Ф/ 50Гц +N+ Сечение шнура сети* мм2 1,5 2,5 2,5 4 1,5 1,5 Номер провода 3 3 3 3 5 5 Сечение проводов межсоединения* мм2 Номер провода 1,5 5 2,5 5 2,5 5 2,5 6 1,5 6 1,5 4 Рекомендуемый предохранитель A 15 20 20 25 15 15 WM301R VS SL30CR WM07 / 10 / 15 / 20 / 25 / 301R VS SL07 / 10 / 15 / 20 / 25 / 30BR 5WM301R VS 5SL28CR Соединяющий провод (длинои 8м) внешето датчика радиатора, подведенныи к внутреннему модулю Терминал Соединяющий провод (длинои 8м) внешето датчика радиатора, подведенныи к внутреннему модулю Терминал Комнатного Блока Терминал Наружного Блока Терминал Комнатного Блока 4WV 4WV OF OF COMP COMP N2 N1 N Наружного Блока A 4WV 4WV OF OF COMP COMP N2 L N1 N L L Шнур Сети Шнур Сети N L ! WM201 / 251R VS SL20 / 25BR (3 Фáза) WM301R VS SL30CR (3 Фáза) Соединяющий провод (длинои 8м) внешето датчика радиатора, подведенныи к внутреннему модулю Терминал Соединяющий провод (длинои 8м) внешето датчика радиатора, подведенныи к внутреннему модулю Терминал Комнатного Блока 4WV Электроснабжение должно обеспечено с приборами защиты (автоматический выключатель или предохранитель) с двухполярной сепарационной системой с минимальным расстоянием между клеммами 3 мм. Терминал Наружного Блока Терминал Комнатного Блока 4WV 4WV Наружного Блока A 4WV OF OF COMP COMP N2 L N2 L N1 N N1 N OF OF COMP COMP L L R R S Шнур Сети S T T Шнур Сети N N ! ! Электроснабжение должно обеспечено с приборами защиты (автоматический выключатель или предохранитель) с двухполярной сепарационной системой с минимальным расстоянием между клеммами 3 мм. 6-9 Электроснабжение должно обеспечено с приборами защиты (автоматический выключатель или предохранитель) с двухполярной сепарационной системой с минимальным расстоянием между клеммами 3 мм. Русский ! Электроснабжение должно обеспечено с приборами защиты (автоматический выключатель или предохранитель) с двухполярной сепарационной системой с минимальным расстоянием между клеммами 3 мм. СПЕЦИАЛЬНЫЕ МЕРЫ ПРЕДОСТОРОЖНОСТИ ПРИ ОБРАЩЕНИИ С R410A • • • • • • R410A представляет собой почти азеотропную охлаждающую смесь гидрофторуглеродов (HFC), которая является экологически безопасной. Этот хладагент обладает нулевым коэффициентом разрушения озона (ODP=0), что соответствует требованиям Монреальского протокола. Он содержит негорючий и низкотоксичный хладагент (A1 по классификации ARI). R410A является смесью R32 (50%) и R125 (50%). В качестве смазки для компрессора R410A используется масло РОЕ, в отличие от R22, для которого используется минеральное масло. Во время установки или выполнения ремонтных работ необходимо принимать особые меры предосторожности, чтобы не допустить длительного контакта системы R410A с влажным воздухом. Масло РОЕ, оставшееся в трубопроводах и компонентах, может абсорбировать влагу из воздуха. Хладагент R410A более подвержен негативному воздействию пыли и влаги по сравнению с R22, поэтому не забудьте перед установкой временно закрыть концы трубопровода. Запрещается добавлять компрессорное масло в систему. Запрещается использовать какой-либо другой хладагент, кроме R410A. Оборудование, предназначенное специально для R410A i) Манометр и заправочный шланг ii) Индикатор утечки газа iii) Цилиндр хладагента / заправочный цилиндр iv) Вакуумный насос с переходником v) Развальцовочный инструмент vi) Устройство для восстановления хладагента • • • ! ОСТОРОЖНО Хладагент R410A необходимо заправлять в жидком состоянии. Как правило, цилиндр R410A оборудован гидравлическим затвором для удаления воды. В отсутствие гидравлического затвора цилиндр следует перевернуть для удаления жидкого R410A из клапана. Не рекомендуется дозаправлять систему при ликвидации утечки, так как это приведет к снижению производительности блока. Необходимо полностью откачать хладагент из системы, после чего заправить ее свежим хладагентом R410A в количестве, указанном в технических условиях. Не прикасайтесь к компрессору или трубопроводу хладагента во время работы охлаждающего аппарата. При необходимости надевайте защитные перчатки. ОTKAЧKA ВОЗДУХА И ЗАПРАВKA Прочистите трубопровод и внутренний модуль Дозаправка Хладагент заправлен заводом-изготовителем на внешнем модуле. Если длина трубопроводов меньше, чем 7,62 м (25 фут), то в дозаправке после откачки воздуха нет необходимости. Если длина трубопроводов больше, чем 7,62 м (25 фут), то используйте клапан дозаправки, как показано в таблице внизу. За исключением внешнего модуля, который заправлен хладагентом на заводе-изготовителе, внутренний модуль и трубопроводы хладагента должны быть продуты, поскольку воздух, содержащий влагу в системе охлаждения, может вызвать сбои в работе компрессора. • Снимите колпачки с клапана и входа технического обслуживания. • Соедините центр нагнетательной коробки к вакуумному насосу. • Cоедините нагнетательную коробку к 3-ходовому клапану входа технического обслуживания. • Включите вакуумный насос. Проводите откачку в течение примерно 30 минут. Время откачки зависит от мощности вакуумного насоса. Удостоверьтесь, что стрелка манометра нагнетательной коробки установилась на –76 мм ртутного столба (0~76 мм ртутного столба). Осторожно Если стрелка манометра коробки не достигает 0~76 мм ртутного столба, то проверьте отсутствие утечки газа (используя течеискатель хладагента) на щтуцерном соединении внутреннем и внешнего модулей и ликвидируйте утечку, прежде чем приступать к следующей операции. • Закройте клапан нагнетательной коробки и выключите вакуумный насос. • На внешнем модуле, откройте клапан впуска (3-ходовой) и клапан жидкости (2-ходовой) (против часовой стрелки) при помощи ключа размером 4 мм для шестигранного винта. Трубопровод Штуцерная хладoгента гайка Шестигранный гаечый ключ Вход технического обслуживания Комнатного блока 3 ходовой клапан внешнего модуля Сторона жидкости Наружного блока Закройте Клапан выпуска Сторона газа Низк Высок Клапан впуска Откройте Вакуумный насос Закройте 6-10 Закройте • Откройте газовый цилиндр и заправочный клапан низкого давления. • Когда требуемое количество хладагента заправлено в модуль, то закройте сторону низкого давления и клапан газового цилиндра. • Отсоедините вспомогательный шланг от входа технического обслуживания. Установите колпачок входа технического обслуживания обратно на его место. Дозаправка в гр. (R22) 10 м/32,8 фут 12 м/39,4 фут 35 65 35 65 90 165 50 90 60 110 120 220 15 м/49,2 фут 110 280 185 370 Дозаправка в гр. (R410A) Модель 311 301R Комнатного блока 10 м/32,8 фут 12 м/39,4 фут 80 150 110 200 15 м/49,2 фут 255 335 Сторона жидкости Наружного блока Клапан выпуска Закройте Модель 071 / 101 / 151 201 251 / 301 071R / 101R /151R 201R 251R / 301R Операция заправки Операция должна проводиться при помощи газового цилиндра и обязательно точным дозатором. Дозаправка во внешний модуль проводится с помощью клапана впуска через вход технического обслуживания. • Снимите колпачок входа технического обслуживания. • Соедините сторону низкого давления нагнетательной коробки к входу технического обслуживания, отцентрируйте для подсоединения к резервуару цилиндра и закройте сторону высокого давления нагнетательной коробки. Прочистите от воздуха вспомогательный шланг. • Включите модуль кондиционера. Сторона газа Клапан впуска Низк Откройте Высок Проверте клапан Закройте Закройте ПОКАЗАНИЯ ИНДИКАТОРОВ Датчик ИК сигналов Модуль охлаждения Когда пульт дистанционного управления передает инфракрасные сигналы, датчик сигналов на внутреннем модуле произведет сигнал <бип> для подтверждения получения сигнала. В таблице представлены показания индикаторов СИД для модуля кондиционера при нормальных условиях функционирования и при сбое. Показания индикаторов СИД представлены на нижней правой стороне модуля кондиционера. ИК Датчик Сеть ВКЛ Таймер Режим осушения Режим сна Показания индикаторов сид Показания индикаторов СИД : Нормальные условия функционирования и сбой модуля охлаждения Показания Функцонирования и Неисправностей Сеть Осушение Таймер Действия Сна Таймер включен. – Режим сна включен. – Режим осушения. – Предотвращение образования льда. Очистите фильтр и переключите на высокую скорость вращения вентилятора. раз в 2 сек. Контакт комнатного датчика воздуха отсутствует/короткое замыкание. Обращайтесь к Вашему дилеру. дважды в 2 сек. Контакт комнатного датчика змеевика отсутствует/короткое замыкание. Обращайтесь к Вашему дилеру. Проблема с контактами датчика, перегрузка компрессора вы звали его автовыключение или утечка газа. Обращайтесь к Вашему дилеру. Непрерывно трижды в 2 сек. ВКЛ ВКЛ или ВЫКЛ 6-11 Мигание Русский Показания индикаторов СИД модуля охлаждения Показания индикаторов СИД для модуля обогревательного насоса Модуль обогревательного насоса В таблице представлены показания индикаторов СИД для модуля кондиционера при нормальных условиях функционирования и при сбое. Показания индикаторов СИД представлены на правой нижней стороне модуля кондиционера. Модуль обогревательного насоса оборудован датчиком режима “авто” для обеспечения оптимальной температуры в комнате автоматическим переключением либо в режим “холодно”, либо в “обогрев”, исходя из установленной температуры пользователем. Режим охлаждения Режим осушения Обогрев / Режим сна Режим вентиляции (красный / зеленый) Показания индикаторов СИД : Нормальные условия функционирования и неисправности модуля обогревательного насоса Нормальное функционирование/ Неисправность Осушение Осуш Холод Обогрев Действия Сна Режим охлаждения. – Режим осушения. – Режим вентиляции. – Режим Обогрев. – Авто режим в операции обогрева. – Авто режим в операции охлаждения. – Операция оттаивания. – Защита компрессора от перегрузки. Обращайтесь к Вашему дилеру. Контакт комнатного датчика змеевика отсутствует/короткое Обращайтесь к Вашему дилеру. Контакт наружного датчика змеевика отсутствует/короткое замыкание Обращайтесь к Вашему дилеру. Контакт комнатного датчика воздуха отсутствует/короткое замыкание. Обращайтесь к Вашему дилеру. Если система в режиме охлаждения или обогрева (с выключенной функцией сна), возможна проблема с контактами датчика, перегрузка компрессора вы звала его автовыключение или утечка газа. ВКЛ ВКЛ или ВЫКЛ 6-12 Мигание ОПЕРАЦИЯ МОДУЛЯ КОНДИЦИОНЕРА Режим осушения Предотвращение обледенения • При повышенной влажности воздуха, модуль может работать в режиме осушения. Нажмите кнопку <РЕЖИМ> и <СУШКА>. • При комнатной температуре на 2°C/35,6°F выше установленной температуры, кондиционер будет функционировать в режиме охлаждения до те пор, пока он не достигнет разницу в 2°C/35,6°F от установленной температуры прежде, чем он переключится в режим осушения • Если комнатная температура в пределах разницы в 2°C/35,6°F по сравнению с установленной температурой, то модуль сразу же начнет функционирование в режиме осушения. • Модуль будет функционировать при скорости НИЗК в режиме осушения. • При загрязнении фильтра, температура испарения Режим обогрева (только обогревательного насоса) уменьшится и в конце концов это может вызвать обледенении. • Индикатор СИД замигает, обозначая загрязненность фильтра. Если температура испарения достигает -2°C/28,4°F, то модуль автоматически отключится и начнется оттаивание. Скорость вентилятора и номинальная степень охлаждения • Номинальная степень охлаждения обеспечивается при максимальной скорости вентилятора. • Номинальная степень охлаждения ниже при режиме модуля, работающего при скорости вентилятора СРЕД и НИЗК. для • При включении модуля с холодным стартом или циклом оттаивания внутренний вентилятор начнет работать только после того, как радиатор достигнет желаемой температуры. • При достижении установленной температуры, внутренний вентилятор начнет работать до тех пор, пока радиатор не будет в состоянии обеспечить дополнительное количество тепла. Охлаждение Осушение Горизонтально 25°C/77°F Управление горизонтальным потоком воздуха Сохранение тепла (только обогревательного насоса) для HOT KEEP OFF INTERVAL ON • При отключении компрессора вентилятора внутреннего блока может быть переключен на (i) ВКЛ(по умолчанию) (ii) ВЫКЛ или (iii) Периодическое включение и выключение посредством установки ползункового переключателя так, как показано на рисунке. • Переключатель находится на передней панели (рядом с включателем ВКЛ/ВЫКЛ). Включатель ВКЛ/ВЫКЛ ПРИМЕЧАНИЕ : Eсли выбрана эта опция, необходимо выключить и включить электропитание блока, чтобы активировать данную функцию. Защита от перегрева (только обогревательного насоса) для • В случае, если внутренняя и/или внешняя температура высока, или фильтр загрязнен и забит, то хладагент может быть перегрет. Компрессор выключится при достижении температуры конденсата 62°C/143,6°F. 6-13 Русский • Для более эффективной циркуляции воздуха, Вы можете вручную регулировать решетку выпуска воздуха влево или вправо. • В течение работы в режиме охлаждения или режиме осушения, не направляйте жалюзи выпуска воздуха вниз на слишком долгое время. Если работа будет продолжаться в таких условиях, то на жалюзи может появиться конденсат, что вызовет к капанью. УСЛОВИЯ СТАНДАРТНОЙ РАБОТЫ Обогревательный насос Только охлаждение Температура Ts °C/°F Th °C/°F Ts °C/°F Th °C/°F Минимальная комнатная температура 19,4 / 66,9 13,9 / 57,0 Минимальная комнатная температура 10 / 50 - Максимальная комнатная температура 26,7 / 80,1 19,4 / 66,9 Максимальная комнатная температура 26,7/80,1 - Минимальная наружная температура 19,4 / 66,9 13,9 / 57,0 Минимальная наружная температура -8 / 17,6 -9 / 15,8 Максимальная наружная температура 46 / 114,8 24 / 75,2 Максимальная наружная температура 24 / 75,2 18 / 64,4 Температура Ts: Шарик сухого термометра. Th: Шарик смоченного термометра. ! Внимание • Отключите сетевое питание перед обслуживанием блока кондиционера. • НЕ вытаскивайте сетевой шнур, когда сеть ВКЛЮЧЕНА. Это может стать причиной резкой нагрузки тока, что может привести к возгоранию. ЭЛЕКТРОСТАТИЧЕСКИЙ ФИЛЬТР ПРИ НАЛИЧИИ Электростатические Воздухоочистительные И Дезодорирующие Фильтрируюощие Средства Двойного Действия И Фильтрная Рамка Действие2Дезодорирующий Фильтр Действие 1Электростатический Воздухоочистительный Фильтр Удаляет неприятные запахи в воздухе и сохраняет комнатный воздух свежим С с помощью фильтра с активированном углем. Удаляет микроскопическую пыль, дым и мелкие невидимые частицы для обеспечения чистоты комнатного воздуха при помощи заправленного электростатического полипропиленового фильтра. КАК УСТАНОВИ ТЬ ОТКРОЙТЕ РЕШЕТКУ ПЕРЕДНЕЙ РАМКИ. ВСТАВЬТЕ ЭЛЕКТРОСТАТИЧЕСКИЕ И ДЕЗОДОРИРУЮЩИЕ ФИЛЬТРЫ ДВОЙНОГО ДЕЙСТВИЯ В ПАЗ. ВЫТАЩИТЕ ОСНОВНЫЕ ФИЛЬТРЫ. ВЫТАЩИТЕ ОСНОВНЫЕ ФИЛЬТРЫ. 6-14 ! Осторожно 3. Фильтр имеется в продаже и его можно приобрести у дилера Вашего кондиционера. 4. Используйте новый фильтр сразу же после того, как он был извлечен из запечатанной упаковки. Не открывайте преждевременно новый фильтр до его непосредственного применения, поскольку это может уменьшить его дезодорирующее действие. 1. Электростатический и дезодорирующий фильтры должны быть заменены либо раз в каждые 6 месяцев, либо при изменении цвета фильтров в коричневатый, что наступит первым. 2. Использованные загрязненные фильтры должны быть выброшены и не применяться вновь, даже после их очистки и мойки. ! Внимание • Отключите сетевое питание перед обслуживанием блока кондиционера. • НЕ вытаскивайте сетевой шнур, когда сеть ВКЛЮЧЕНА. Это может стать причиной резкой нагрузки тока, что может привести к возгоранию. СЕРВИС И ТЕХНИЧЕСКОЕ ОБСЛУЖИВАНИЕ Узлы Обслуживания Процедуры Технического Обслуживания Время Комнатный воздушный фильтр 1. Очистите от пыли фильтр пылесосом или вымойте его в теплой воде (ниже 40°С/104°F ) нейтральным моющим средством. 2. Хорошо прополоскайте и высушите фильтр перед установкой его обратно в блок. 3. Не используйте бензиновые, легкоиспаряющиеся вещества или химические средства для очистки фильтра. Не реже 2 раз в неделю. Чаще при необходимости. Комнатный блок 1. Очистите от грязи или пыли решетку или панель, вытирая при помощи мягкой ткани смоченной в теплой воде (ниже 40°С/ 104°F) нейтральным моющим средством. 2. Не используйте бензиновые, легкоиспаряющиеся вещества или химические средства для очистки комнатного блока. Не реже 2 раз в неделю. ! Осторожно Не устанавливайте обогревательные приборы в непосредственной близости от кондиционеру. Это может привести к расплавлению пластиковой панели или ее деформации в результате высокой температуры. Аогда Бодуль Ве жассчитан Ва Ћспользование В кечение Длительного Времени Функционирование модуля в течение 2 часов со следующей установкой. Режим работы: холодно Температура: 30°C/86°F Вытащите вилку. Если используется независимый подвод питания для модуля, выключите питание. Выньте батареи из пульта дистанционного управления. 6-15 Русский Чаще при необходимости. МЕРЫ ПО УСТРАНЕНИЮ При обнаружении сбоев в работе кондиционера, немедленно выключите питание сети блока. Проверьте нижеследующие признаки неисправностей, причины и советы простейших мер по устранению. Причины/действия Неисправность 1. Компрессор не начинает функционирование по прошествии 3 минут после включения кондиционера. - Защита от частого включения. Подождите от 3 до 4 минут, чтобы компрессор включился. 2. Кондиционер не работает. - Отсутствие сетевого питания или требуется замена предохранителя. - Вилка не вставлена. - Существует вероятность того, что таймер задержки установлен неправильно. - Если неисправность не устранена после всех этих проверок, пожалуйста, свяжитесь с персоналом, установившего кондиционер. 3. Очень незначительный поток воздуха. - 4. При выпуске воздуха имеется неприятный запах. - Неприятный запах может быть вызван сигаретами, частицами дыма, парфюмерии и т.п., которые могли осесть на змеевике. 5. Конденсат на передней решетке комнатного блока. - Это вызвано влагой в воздухе после продолжительного времени функционирования. - Установленная температура слишком низка, увеличьте установленную температуру и установите скорость вентилятора на высокую. 6. Вода выливается из кондиционера. - Выключите блок и обращайтесь к дилеру. 7. Шипящий звук воздуха из кондиционера во время работы. - Попадание хладагента на испарительный змеевик. Воздушный фильтр загрязнен. Двери или окна открыты. Забился впуск и выпуск воздуха. Установленная температура недостаточно высока. Если неисправность неустранима, пожалуйста, обращайтесь к Вашему местному дилеру / специалисту. 6-16 • In the event that there is any conflict in the interpretation of this manual and any translation of the same in any language, the English version of this manual shall prevail. • The manufacturer reserves the right to revise any of the specification and design contain herein at any time without prior notification. • En cas de désaccord sur l’interprétation de ce manuel ou une de ses traductions, la version anglaise fera autorité. • Le fabriquant se réserve le droit de modifier à tout moment et sans préavis la conception et les caractéristiques techniques des appareils présentés dans ce manuel. • Im Falle einer widersprüchlichen Auslegung der vorliegenden Anleitung bzw. einer ihrer Übersetzungen gilt die Ausführung in Englisch. • Änderungen von Design und technischen Merkmalen der in dieser Anleitung beschriebenen Geräte bleiben dem Hersteller jederzeit vorbehalten. • Nel caso ci fossero conflitti nell’interpretazione di questo manuale o delle sue stesse traduzioni in altre lingue, la versione in lingua inglese prevale. • Il fabbricante mantiene il diritto di cambiare qualsiasi specificazione e disegno contenuti qui senza precedente notifica. • En caso de conflicto en la interpretación de este manual, y en su traducción a cualquier idioma, prevalecerá la versión inglesa. • El fabricante se reserva el derecho a modificar cualquiera de las especificaciones y diseños contenidos en el presente manual en cualquier momento y sin notificación previa. • В случае противоречия перевода данного руководства с другими переводами одного и того же текста, английский вариант рассматривается как приоритетный. • Завод-изготовитель оставляет за собой право изменять характеристики и конструкцию в любое время без предварительного уведомления. OYL MANUFACTURING COMPANY SDN. BHD. JALAN PENGAPIT 15/19, P.O. BOX 7072, 40702 SHAH ALAM, SELANGOR DARUL EHSAN, MALAYSIA. VOd² « VO² IM-WM1-0302-ACSON : “«dÞ qBHM*« ŸuM « s ¡«u¼ WHOJ —«b'« vKŽ XO³¦² «Ë —«b'« vKŽ oOKFð œUFÐ_«Ë wDOD ²« rÝd« WOKš«b« …bŠu« ©!«® Ø 3 d²LOK*UÐ w¼ œUFÐ_« lOLł A D C ÍuKF« dEM*« B E wU_« dEM*« E s1 _« dEM* « 347.0 (13.7) œUFÐ_« C B A 730.0 (28.7) 174.0 (6.85) 190.0 (7.5) 297.0 (11.7) 320.0 (12.6) 785.0 (30.9) 1050.0 (41.3) 730.0 (28.7) 200.0 (7.9) 360.0 (14.2) 1200.0 (44.1) D 595.0 (23.4) 280.0 (11.0) 311.0 (12.2) VOd²« WŠu WM071 / 101 / 151 / 1R WM201 / 201R WM 251 / 251R / 301 / 301R ©!«® Ø 3 d²LOK*UÐ w¼ œUFÐ_« lOLł A C 5 (0.2) N 39 (1.5) 15 (0.6) M R 15 (0.6) 39 (1.5) (SL-B Series) WOł—U)« …bŠu« P Q P 5 (0.2) 840 (33.1) C 160 (6.3) H B R Q P N M L K J H G F L E D K 20 (0.8) 20 (0.8) 20 (0.8) (2.6) 65 J E F 141 (5.6) 2.5 (0.1) G D C B A 68,5 482 129 (2.7) (19.0) (5.1) 318 348 (12.5) (13.7) 92 166 (3.6) (6.5) 65 55 (2.6) (2.2) 47 474 (1.9) (18.7) 78,5 592 124 (3.1) (23.3) (4.9) 378 408 (14.9) (16.1) 106 177 (4.2) (7.0) 75 85 (3.0) (3.3) 41 626 309 297 330 646 840 (1.6) (24.6) (12.2) (11.7) (13.0) (25.4) (33.1) 164 603 126 (6.5) (23.7) (5.0) 362 392 (14.3) (15.4) 98 187 (3.9) (7.4) 75 116 (3.0) (4.6) 49 730 309 303 328 750 855 (1.9) (28.7) (12.2) (11.9) (12.9) (29.5) (33.7) i 233 266 270 494 740 (9.2) (10.5) (10.6) (19.4) (29.1) œUFÐ_« 07B / 07BR 10B / 10BR 15B / 15BR 20B / 20BR 25B / 25BR 30B / 30BR 28C / 28CR (SL071 & 10/15 C/CR qKð) WOł—U)« …bŠu« (1.2) ©!«® Ø 3 d²LOK*UÐ w¼ œUFÐ_« lOLł O N M L K J I H G F E D C B A 22 (0.8) 17 (0.6) 97 (3.8) 101 (3.9) 398 (15.6) 55 (2.2) 83 (3.2) 81 (3.1) 93 (3.6) 35 (1.3) 177 (6.9) 418 (16.4) 245 (9.6) 475 (18.7) 600 (23.6) œUFÐ_« 071 / 1R 18 (0.7) 15 (0.5) 111 (4.3) 130 (5.1) 441 (17.3) 68 (2.6) 86 (3.3) 93 (3.6) 95 (3.7) 36 (1.4) 175 (6.8) 485 (19.1) 250 (9.8) 521 (20.5) 700 (27.5) 10 / 15 C /CR 141.5 (5.57) 448 (17.64) 141.5 (5.57) 20 (0.79) (SL30C) WOł—U)« …bŠu« 25 (0.78) 850 (33.46) 20 (0.79) 1030 (40.55) 400 (15.75) 40 (1.57) 320 (12.60) 40 (1.57) 50 (1.97) 85 (3.35) Æs U_« ÁcNÐ „UJ²Šô« s VM& ÆÕËd'« dÞU V³ð w²«Ë WMU l«u w WH²K `DÝ« Ë …œUŠ ii UUŠ tO³Mð ! WOÐdF« VOd² « VO² wJ ’Uš j³{ ¡«dł« Í—ËdC « s ÊuJ¹ b Æ¡«uN « WHOJ …bŠu ÊuQ*«Ë bO'« ÍœUF « qOGA² « ÊULC VOd² « ‚dDÐ VO²J « «c¼ „œËe¹ ÆpðU³KD² rzö¹ Æq³I²*« w WFł«dLK tÐ ÿUH²Šô«Ë W¹UMFÐ «c¼ ULOKF² « VO² …¡«d vłd¹ ¨¡«uN « WHOJ ‰ULF²Ý« q³ —«b'« vKŽ XO³¦² «Ë qBHM*« ŸuM « s ¡«u¼ WHOJ “«dÞ (R22) W¾b² (R22) b¹d³² « a{ …bŠË « …bŠË “«dÞ lłd*« “«dÞ “«dÞ lłd*« “«dÞ AWM301R ALC30CR ALC30BR WM301R SL30CR SL30BR AWM301 ALC30C ALC30B WM301 SL30C SL30B (R410A) W¾b² « a{ …bŠË (R410A) b¹d³² « …bŠË “«dÞ lłd*« “«dÞ “«dÞ lłd*« “«dÞ A5WM301R A5LC28CR 5WM301R 5SL28CR A5WM311 A5LC28C 5WM311 5SL28C Part No.: A08019025521 IM-WM1-0302(2)-Acson ± U¹u²;« R410A …bŠu« l qUF²« bMŽ W ±∞ Uš i-ii UÞUO²Š« ≠ œUFÐ_«Ë wDOD²« rÝd« ≠ ±∞ s×A«Ë m¹dH²« ≠ ≤ ±± dýR*« ¡«u{« ≠ ≥ VOd²« jD ≠ ±≥ ¡«uN« WHOJ …bŠË qOGAð ≠ ≥ WOł—U)« …bŠu« VOdð ≠ ±¥ qOGA²K WOÝUOI« ôU(« ≠ ¥ w¼uH« »u³½_« VOdð ≠ ±¥ WOJOðU²Ýô« ¡UÐdNJ« `ýd ∫Í—UO²š« ≠ ∂ WOKš«b« …bŠu« VOdð ≠ ±µ ±∂ tŠö W½UOB«Ë `OKB²« ≠ ∑ «Ë qK)« sŽ Ídײ« qOœ ≠ ∏ ÊU_« ÊU_« UÞUO²Š« ≠ b¹d³²« VOÐU½√ ≠ WOzUÐdNJ« „öÝô« qO uð ≠ UÞUO²Š« ÆW¹UMFÐ WOU²« ÊU_« UÞUO²Š« …¡«d vłd¹ ¨¡«uN« WHOJ …bŠË VOdð q³ ! d¹c% ŸuM« «c¼ l …d³)«Ë ¨wK;« rOEM²«Ë …dHA« vKŽ ŸöÞô« sŠ rN¹b s¹c« 5OB²<« 5OMH« q³ s W½UOB«Ë VOd²« WOKLŽ ¡«dł« V−¹ • Æ…eNłô« s ÆWOzUÐdNJ« ÆsÞu« „öÝ« WJ³ý rOEMð v« ÎUIË …uI« ‰U− „öÝ« WJ³ý VB½ V−¹ • «b¹bL²« jD v« ÎUIË „öÝô« WJ³ý ‰ULŽUÐ √b³ð Ê√ q³ …œb;« WŠuK« l oÐUD²¹ …bŠuK WODuH« ‰bF Ê« s bQð • .‰“UF« hI½ V³Ð WKL²;« dÞU<« lM* …bŠu« i¹—Qð V−¹ • ÆWŠËd*« Ud; Wdײ ¡«eł« W¹« Ë« WDžUC« Ë« ¨b¹d³²« qzUÝ VOÐU½« „öÝô« WJ³ý „öO Æ…bŠuK W½UOB« Ë« VBM« WOKLŽ ¡«dł« q³ uð föðô Ê« V−¹ • OFF ·UI¹ô« l{u vKŽ …bŠu« q¹u% s bQð • ÂU¼ ÆqOG « Wdž w ¡«uN « WHOJ …bŠË qLF²ð Ë« VBMðô ! tO³Mð ÆVBM « bMŽ WO U² « WLN*« ◊UIM « WEŠö vłd¹ Æ»UN² ô« l¹dÝ “UG ÷dF ÊUJ w …bŠu « VBMðô • ÆÊ«dOM« Ÿôb½« w V³²¹ Ê« sJL*« s ¨…bŠu« ‰uŠ r«dðË “UG« »dð «–« ÆW×O× …—uBÐ n¹dB² « VOÐU½√ qOuð s bQð ÆÀUŁ_« VÞdð v« ÍœR¹ Íc« ¡U*« »d²¹ ·uÝ ¨W×O× …—uBÐ n¹dB²« VOÐU½« qO • uð r²¹ r «–« Æ…bŠu « s×ý w ◊dHðô • ÆWDžUC« nKð Ë« —UO²« “ËU& v« bz«e« s×A« ÍœR¹ ÆlMB*« w ÎUI³ …bŠu« s×ý - ÆVBM « Ë« W½UOB « ¡«dł« bFÐ …bŠu « WŠu oKž s bQð Æ¡U{uCUÐ »u×B*« qOGA²« v« …bŠuUÐ ÂUJŠQÐ ≤ UŠuK« oKž ÂbŽ ÍœR¹ • VOd² « jD  WOÐdF« WOKš«b « …bŠu « ¡«uN« U×ýd wU_« —UÞô« wHK)« ·öG« ¡«uN« ‰Ušœ« WJO³ý ON/OFF ÕU²H n¹dB²« »u³½√ dýR*« ¡«u{« ¡«uN« m¹dHð oý …—Uýô« q³I² ¡«uN« m¹dHð WJO³ý ¡«uN« qšb b¹d³²« …œU VOÐU½√ ¡«uN« qšb ¡«uN« m¹dHð W¼u WOł—U)« …bŠu « WOł—U)« …bŠu « VOdð A ¡«uNK …dz«b« dB lM* ¨WI¹dD« Ác¼ q¦0 WOł—U)« …bŠu« VOdð V−¹ B wł—U)« ¡«uN« …—«dŠ Wł—œ sŽ wKš«b« ¡«uN« …—«dŠ Wł—œ b¹eðô ozUŽ ⁄dH*« ¡«uN« ozUŽ lł«d« ¡«uN« WU*« ŸU³ð« vłd¹ Æ¡«uNK qN« »UO½ô« WUŽ« Ë« —U(« ⁄dH*« YO×Ð qL²× ÊUJ œdÐ√ d²š« ÆrÝd« w W×{u*« VOd²K Wž—UH« Æ©vB« b× °±±≥ Ø °¥µ”UOI® VOd²K Wž—UH « WU*« D B A œUFÐ_« vBô« b(« D 500 (19.7) 300 (11.8) 1000 (39.4) 300 (11.8) 3 ¨WULK ©!«® ozUŽ W½UOB« qšb ozUŽ lł«d« ¡«uN« C C rI« vKŽ ozUŽ Í« błË «–« Ë« ¨Â≤ s vKŽ« oz«uŽ błË «–« ∫WEŠö ‰Ëb'« w `{u*« rd« s d¦« ⁄«dH« …œU¹“ vłd¹ ¨…bŠuK ÍuKF« ÆÁöŽ« ≥ w¼uH « »u³½_« VOdð w¼u »u³½« WOł—U)« …bŠu« WOKš«b« ©W¦½R® ≥Ø∏¢ lOÝuð WuL W¼u ©Íd–® ≥Ø∏¢ lOÝu²« qBH qO WM301/SL30C Ë WM301/SL30B tO³Mð u𠨻u³½« “«dD jI VOd²« ∫WEŠö ! ÆÁöŽ« `{u u¼ UL `O×B« ÁU&ôUÐ w¼uH« »u³½ô« VOdð V−¹ ÆqOGA²« ÂUE½ ¡«œ« w —uB v« ¡wÞU)« ÁU&ô« Íœƒ ©VOd²K WOU WŠU „UM¼ ÊuJ¹ UbMŽ® WOł—U)« …bŠu « »u³½« t¼u VOdð ÆA ≤ …uD)« w¼u »u³½« ± …uD)« ∫ «uD)« »u³½ö “Ídc«” qBH*UÐ tK Ë«Ë qzU« »u³½« lOÝu²Ð r Æ≤ ÂULBÐ w¼uH« »u³½ú “W¦½R” WuLB« q Æw¼uH« Ë« …dýU³ Ʊ Î ÆqzU« qzU« »u³½« w¼u »u³½« ¥ ©VOd²K …œËb× WŠU „UM¼ ÊuJ¹ UbMŽ® WOł—U)« …bŠu « »u³½« t¼u VOdð ÆB ¥ …uD)« WOÐdF« w¼u »u³½« ≥ …uD)« ≤ …uD)« ± …uD)« ÆqzU« »u³½« 5Ð tKO uð sJLO ¨WŠU*« oO{ V³Ð qzU« ÂULBÐ dýU³ qJAÐ w¼uH« »u³½ô« qO uð sJ1 r «–« ∫ «uD)« Æ“Ídc«” qBH*UÐ w¼uH« »u³½ö “W¦½R” WuL qzU« »u³½« »u³½ú “Ídc«” qBH*UÐ tK q Ë« Æ≥ ÆqzU« ÂULBÐ tK Ë«Ë qzU« »u³½« lOÝu²Ð r Ʊ w¼u »u³½« Ë«Ë dš¬ qzUÝ »u³½« lOÝu²Ð r Æ¥ ÆqzU« »u³½UÐ wU{« “Íd–” qBH r×KÐ r Æ≤ Æw¼uH« qzU« »u³½« qzU« »u³½« w¼u »u³½« ”U×½ ÆWOKš«b« …bŠuK w¼uH« »u³½_« VOdð ÆC WOKš«b« …bŠu« w¼u »u³½« ∫ «uD)« tK Ë«Ë dš¬ qzUÝ »u³½« lOÝu²Ð r Æ≥ w¼uH« »u³½ö “W¦½R” WuL Æw¼uH« »u³½ú “Ídc«” qBH*UÐ qzU« »u³½« q Ë« Æ≤ »u³½UÐ wU{« “Íd–” qBH r×KÐ r Ʊ Æ“Ídc«” qBH*UÐ ÆqzU« qzU« »u³½« w¼u »u³½« qzU« »u³½« w¼u »u³½« ”U×½ µ WOKš«b « …bŠu « VOdð s 5LO« Ë« —UO«® ‚dÞ …bFÐ …bŠu« v« b¹d³²« …œU VOÐU½√ b sJ1 ¡«uNK …dz«b« dB lM* WI¹dD« Ác¼ q¦0 WOKš«b« …bŠu« VOdð V−¹ ¡UDž vKŽ …œułu*« WŽuDI*« »uI¦« «b²ÝUÐ ¨©…bŠuK WOHK)« WN'« Wž—UH« WU*« ŸU³ð« vłd¹ Ælł«d« —d« —U(« ¡«uN« l œ—U³« ⁄dH*« Æ©rÝd« dE½√® …bŠu« ÊUJ w WOKš«b« …bŠu« l{Ë ÂbŽ V−¹ ÆrÝd« w W×{u*« VOd²K Æ»uI¦« l UNð«–U× r²ð wJ »uKD*« l{u*« v« —c×Ð VOÐU½_« wM¦Ð r VOÐU½ú VÝUM lu*« ÊuJ¹ Ê« ¨ÎUC¹« ÆW¹uI« fLA« WFýô ÷dF sË VOÐU½_« WJ³ý v½œ√ p« ¨wł—U)« wHK)« V½U'«Ë 5LO« WN' Æc«uM« Ë« »«uÐ_« sŽ ΫbOFÐË ¨n¹dB²«Ë n¹dBð »u³½√ bý sJ1 Æ©rÝd« dE½«® »uKD*« ÁU&ô« u×½ tNłË rŁ ÆVOÐU½_« v« nŁUJ²« 50mm 50mm 50mm wHK)«Ë s1_« V½U'« VOÐU½√ —U Èu² s vKŽ« ¡«uN« W½UOB« ⁄«d Wb)«Ë dB³« ÊU¹dł ÁU&« VOd²« WŠu VOd² « WŠu vKŽ …bŠu « XO³¦ð w? 5ÐUÒK?J?« jЗ«® VOd²« WŠuK ÍuKF« rI« vKŽ WOKš«b« …bŠu« X³Ł Ò Æ©VOd²« WŠuK W¹uKF« WU(« l WOKš«b« …bŠu« …dšR vKŽ« ULNJ¹d% WDÝ«uÐ VOd²« WŠu vKŽ W×O× …—uBÐ 5ÐUKJ« Ò XO³¦ð s bQð j)« sŽ bF³«≠WöŽ Æ5LOKË —UOK jOš VOd² « XO³¦ð WŠu ¨Èdš« WI¹dDÐ Æ…bŠu« Ê“Ë qLײ¹ YO×Ð —«b−K WOUJ« …uI« s bQð qO Ærz«uI« Ë√ u²« qÐU UUŽb« Ë« ¨ UŠuK« WDÝ«uÐ —«b'« W¹uIð Í—ËdC« s ÆWLzö dOU ¥ WDÝ«uÐ UN²³ŁË ¨wIô« XO³¦²K ¡«u²Ý« Ê«eO qLF²Ý« n¹dB²« »u³½√ 3∂µ dD nBMÐ Wײ VIŁ« ¨Ã—UK WOHK)« VOÐU½ô« V×Ý WUŠ w dE½«® wł—U)« —«b'« vKŽ tCHš« odÐ ÆwÞËd »UI¦ WDÝ«uÐ Æ©rÝd« ¡U*« n¹dBð VOÐU½√ n¹dB²K ‰“UM« wM×M*« qJAÐ WOKš«b« n¹dB²« VOÐU½« ÊuJð Ê« V−¹ wKš«œ wł—Uš Æ¡U*« »dð UNO qL²×¹ w²« ŸU{Ë_« VM& ÆqN« µ∞ر ·«d×½ô« ¡U*« n¹dBð VOÐU½_« —U ÆWOU_« WŠuK« X³¦ —UL l—« W¹UNM« ✓ j `O× »dð »dð »dð …—uLG ¡U*« ¡U*« ¡U*« ¡U*UÐ J J J QDš QDš QDš VOÐU½_« —U ∂ b¹d³² « VOÐU½√ WOÐdF« tO³Mð ÆWOKš«b« …bŠu« w qzU« »u³½« vKŽ W²³¦ w¼Ë ÆjI ! WM301 b¹d³²« …bŠË w b¹b9 …«œQ W¼uH« qLF²ð VOÐU½_« ŸUHð—«Ë ‰uÞ V³Ð Æ…bŠu« …—«błË WFÝ iHMð ·uÝ ¨Î«bł WK¹uÞ VOÐU½_« X½U «–≈ ”U×M« »u³½« lD ÎW−O²½ Æb¹d³²« …œU ÂUE½ ob² WËUI*« …œU¹“Ë ¨ «¡«u²ô« œbŽ …œU¹“ …œułu*« UO u²« l³ð«Ë —U dB« ÎULz«œ d²š≈ ÆWDžUC« q²ð ¨pc ∫ÁU½œ« ‰Ëb'« w 30 25 20 15 35(114.8) 15(49.2) 15(49.2) 12(39.4) 12(39.4) 15(49.2) 8(26.2) 8(26.2) ld« …dH× ”U×M« »u³½« o¹dD²« WK² j³{ rJŠ«Ë VOÐU½ô« ed …«–U×0 r ÆlÐU WIDIÞ lLð Ê« v« d¹Ëb²« ÂeŽ WDÝ«uÐ ŸUðô« WuL 5(16.4) 5(16.4) L ¨©ft®  ¨‰uDK vBô« b(« H ¨©ft®  ŸUHð—ö vBô« b(« «¡«u² ô« œbF vBô« b(« 10 10 10 10 10 3/8" 3/8" 1/4" 1/4" 1/4" qzU « »u³½√ r−Š 5/8" 5/8" 5/8" 1/2" 3/8" “UG « »u³½√ r−Š w¼ WOł—U)« …bŠu« w ÎUI³ W½u×A*« b¹d³²« …œU Ê« «bŠu « v « VOÐU½ô« qOuð WDÝ«uÐ WOU …—uBÐ ŸUðô« WuL “«dÞ 07/10 ∫oOKFð Æft ≤µ Ø Â∑[∂≤ UNuÞ VOÐU½_ • ô« j³{ rJŠ« ¨«dOš« Î WOKš«b « …bŠu « • Æd¹Ëb²« (Nm)d¹Ëb² « ÂeŽ ©!«® Ø3 »u³½ô« r−Š 18 (13.3) 42 (31.0) 6.35 (1/4) 9.53 (3/8) 55 (40.6) 65 (48.0) 12.7 (1/2) 15.88 (5/8) ©3® A L H dD nBMÐ »u³½« XÐU¦ « Í—uÞ«d³ô« 3 ©!«® WuÐ 0.7 1.3 6.35 1/4" 1.0 1.6 9.52 3/8" 1.3 1.7 1.9 2.2 12.70 15.88 1/2" 5/8" WOł—U)« …bŠu « VOÐU½_« ‰ULŽ« WO J O ² Ý ö ³  « ŸUðô« qBH UÐUI« ‰eðô ÆnUð Ë√ ÀuK wÝU×½ »u³½√ qLF²ðô U³Od²«Ë ¨ UULB« s WOÝU×M« »u³½« qzU« jš Ë« r qO • ôuLB«Ë WOÞUD*«Ë u² «Îe¼Uł ÊuJð Ê« v« WuHK*« „öÝô«Ë Æ U³Od²« Ë« ÂULBUÐ s 5łËd²M« “Už —Ëd s bQ𠨔U×MUÐ r(  ‰ULŽ« Í« X³KDð «–« WOKš«œ VOÐU½« · uÝ « c¼ Æ ”U × M  U Ð r ×  K« ‰ULŽ« “U$« ¡UMŁ« q WuL • U H*« Ë n K * « ‰ ö š ÆWOÝU×M« VOÐU½ú WOKš«b« Ê—«b'« vKŽ ÊuJ²*« ÂU« q¹e¹ Æ»u³½ô« WFÞU WDÝ«uÐ qO Æq¹e*« WDÝ«uÐ WŽuDI*« u ²  « » u ³ ½ « lD  « U¹UNM« s WMA)« U U ( « l — « • • Æ»u³½ô« v« WO½bF*« U¹UEA« ‰ušœ lM* qHÝö »u³½ô« W¹UN½ p« 5ðbŠuK WK u*« ÂUô« vKŽ t²³ÒŁ ¨ ôuLB« lÝu qšœ« • ÆWOÝU×M« VOÐU½ô« vKŽ WOł—U)«Ë WOKš«b« Ò Ë `{u u¼ UL lOÝu²« …«œ« s vKŽ« wU{« ‰uÞ l »u³½ô« lÝ jÐd« ÕU²H • Æ ‰ Ëb' « w  d¹Ëb²« ÂeŽ ÆWýb Ë« …—uJ dOž ÎULz«œ WFÝu*« W¹UNM« ÊuJð Ê« V−¹ ∑ • WOzUÐdNJ « „öÝô« qOuð b¹d³² « …bŠË VBM« ŸuM W{dŽ Î ÎUC¹« Ác¼ ÆWuQ*« WOK;« Æ ö ÆjI eðd¼∂∞ —UO²« …—bIÐ œËe²« l ‰ULF²Ýö qÐU WM301 SL30C WM201/ 251/ 301 SL20/ 25/ 30B WM301 SL30C 380V-415V/ 3Ph/ 50Hz +N+ ETL ‰Ëbł Ê« Æ…bŠu« vKŽ …œułu*« WöF« 5WM311 5SL28C WM201/ 251/ 301 SL20/ 25/ 30B 220V-240V/ 1Ph/ 50Hz + 1.5 4 2.5 2.5 1.5 5 3 3 3 3 1.5 1.5 2.5 2.5 2.5 1.5 “«dÞ ≤3 *—UO²UÐ œËe²« qÐU r−Š ≤3 *jÐd« qÐU r−Š „öÝô« œbŽ 4 4 4 3 3 3 15 15 25 20 20 15 „öÝô« œbŽ A UNÐ v u*« WL UH« WM07 / 10 / 15 / 20 / 25 / 301 VS SL07 / 10 / 15 / 20 / 25 / 30B 5WM311 VS 5SL28C ·«dÞ« WŽuL− WOł—U)« …bŠu« L COMP WOKš«b « **WODuH« Èb 5 `³J ·dÞ ** WOł—U)« Ë« 208V-230V/ 1Ph/ 60Hz + WM301 VS SL30C ∫ ÂU¼ u*« ‰ULF²Ý«Ë UODF l VÝUM*« WODuH« Èb h× V−¹ WM 071/ 101/ 151 SL07/ 10/ 15B 1.5 WOKš«b« …bŠu« * «dHA« l o«u²ð YO×Ð U¼—UO²š«Ë UNB× V−¹ ÆjI ŸöÞô« ÷dG w¼ ‰Ëb'« w …œułu*« ÂU—ô« Ê« N `³J ·dÞ ·«dÞ« WŽuL− WOKš«b« …bŠu« WOł—U)« …bŠu« COMP COMP N2 N N2 S N1 R L N1 COMP L L —UO²UÐ œËe²« qÐU W¹ULŠ qzUÝË dOuð V−¹ lÞU® wzUÐdNJ« —UO²K Ë« WOzUÐdNJ« …dz«b« ÃËœe ÂUE½ l ©WL —UO²UÐ œËe²« qÐU N ! W¹ULŠ qzUÝË dOuð V−¹ lÞU® wzUÐdNJ« —UO²K Ë« WOzUÐdNJ« …dz«b« U ÃËœe ÂUE½ l ©WL …u− l 5³DI« qBHM ! U …u− l 5³DI« qBHM Æv½œ« b× 3≥ ‰UBð« Æv½œ« b× 3≥ ‰UBð« WM301 VS SL30C (≥ WKŠd) WM201 / 251 VS SL20 / 25B (≥ WKŠd) ·«dÞ« WŽuL− WOł—U)« …bŠu« `³J ·dÞ WOKš«b« …bŠu« ·«dÞ« WŽuL− WOł—U)« …bŠu« `³J ·dÞ WOKš«b« …bŠu« COMP COMP COMP L COMP L N2 N N2 N N1 N1 R L R L S S T T —UO²UÐ œËe²« qÐU —UO²UÐ œËe²« qÐU N W¹ULŠ qzUÝË dOuð V−¹ lÞU® wzUÐdNJ« —UO²K Ë« WOzUÐdNJ« …dz«b« ÃËœe ÂUE½ l ©WL ! W¹ULŠ qzUÝË dOuð V−¹ lÞU® wzUÐdNJ« —UO²K Ë« WOzUÐdNJ« …dz«b« U ÃËœe ÂUE½ l ©WL U …u− l 5³DI« qBHM …u− l 5³DI« qBHM Æv½œ« b× 3≥ ‰UBð« Æv½œ« b× 3≥ ‰UBð« ÆÂUJŠUÐ „öÝô« WU qO uð V−¹ W¹« Ë« WDžUC« Ë« ¨b¹d³²« …œU VOÐU½« „öÝô« föðô Ê« V−¹ • • pK« pÝU ÆWŠËd*« „d; Wdײ ¡«eł« WOł—U)« …bŠu«Ë WOKš«b« …bŠu« 5ÐU qO u²« „öÝ« bý V−¹ • ÆrÝd« w `{u u¼ UL „öÝô« pÝU0 (245IEC57) H05RN-F v« —UO²UÐ œËe²« q³ ÍËU¹ Ê« V−¹ • Æv½œô« b(« VKD²¹ Íc«Ë qO ∏ u²« qÐU ! N W¾b² « a{ …bŠË ‰ULF²Ý«Ë VBM« ŸuM W{dŽ Î ÎUC¹« Ác¼ ÆWuQ*« WOK;« WOÐdF« Æ ö ÆjI eðd¼∂∞ —UO²« …—bIÐ œËe²« l ‰ULF²Ýö qÐU ETL ‰Ëbł Ê« Æ…bŠu« vKŽ …œułu*« WöF« 220V-240V/ 1Ph/ 50Hz + 1.5 4 2.5 2.5 1.5 5 5 3 3 3 3 1.5 1.5 2.5 2.5 2.5 1.5 4 6 6 5 5 5 15 15 25 20 20 15 **WODuH« Èb uð pKÝ wł—Uš nK „öÝô« œbŽ „öÝô« œbŽ A 4WV OF OF COMP COMP N2 L N1 N UNÐ v fײ*« qO u*« WL UH« uð pKÝ wł—Uš nK WOKš«b« …bŠuUÐ o×K ©Â∏ ‰uÞ® `³J ·dÞ A 4WV *jÐd« qÐU r−Š ≤3 ·«dÞ« WŽuL− WOł—U)« …bŠu« `³J ·dÞ *—UO²UÐ œËe²« qÐU r−Š ≤3 WOKš«b« …bŠuUÐ o×K ©Â∏ ‰uÞ® WOKš«b« …bŠu« “«dÞ WOł—U)« WM07 / 10 / 15 / 20 / 25 / 301R VS SL07 / 10 / 15 / 20 / 25 / 30BR 5WM301R VS 5SL28CR WM301R VS SL30CR fײ*« qO ** WOKš«b « Ë« 208V-230V/ 1Ph/ 60Hz + 1.5 ∫ ÂU¼ u*« UODF l VÝUM*« WODuH« Èb h× V−¹ WM301 R WM201/ 251/ 301 R WM301 R 5WM301R WM201/ 251/ 301 R WM 071/ 101/ 151 R SL30CR SL20/ 25/ 30BR SL30CR 5SL28CR SL20/ 25/ 30BR SL07/ 10/ 15BR 380V-415V/ 3Ph/ 50Hz +N+ * «dHA« l o«u²ð YO×Ð U¼—UO²š«Ë UNB× V−¹ ÆjI ŸöÞô« ÷dG w¼ ‰Ëb'« w …œułu*« ÂU—ô« Ê« ·«dÞ« WŽuL− WOł—U)« …bŠu« WOKš«b« …bŠu« 4WV 4WV OF OF COMP COMP N2 N1 N L L —UO²UÐ œËe²« qÐU —UO²UÐ œËe²« qÐU N W¹ULŠ qzUÝË dOuð V−¹ L W¹ULŠ qzUÝË dOuð V−¹ lÞU® wzUÐdNJ« —UO²K Ë« WOzUÐdNJ« …dz«b« ÃËœe ÂUE½ l ©WL lÞU® wzUÐdNJ« —UO²K ! Ë« WOzUÐdNJ« …dz«b« ÃËœe ÂUE½ l ©WL ! U …u− l 5³DI« qBHM U Æv½œ« b× 3≥ ‰UBð« …u− l 5³DI« qBHM Æv½œ« b× 3≥ ‰UBð« WM301R VS SL30CR (≥ WKŠd) fײ*« qO WM201 / 251R VS SL20 / 25BR (≥ WKŠd) uð pKÝ wł—Uš nK WOKš«b« …bŠuUÐ o×K ©Â∏ ‰uÞ® `³J ·dÞ WOKš«b« …bŠu« fײ*« qO ·«dÞ« WŽuL− WOł—U)« …bŠu« uð pKÝ wł—Uš nK WOKš«b« …bŠuUÐ o×K ©Â∏ ‰uÞ® ·«dÞ« WŽuL− WOł—U)« …bŠu« `³J ·dÞ WOKš«b« …bŠu« A 4WV 4WV 4WV OF OF OF OF COMP COMP COMP COMP N2 L N2 L N1 N N1 N 4WV L L R R S —UO²UÐ œËe²« qÐU T —UO²UÐ œËe²« qÐU W¹ULŠ qzUÝË dOuð V−¹ lÞU® wzUÐdNJ« —UO²K Ë« WOzUÐdNJ« …dz«b« ÃËœe ÂUE½ l ©WL S T N N W¹ULŠ qzUÝË dOuð V−¹ ! lÞU® wzUÐdNJ« —UO²K Ë« WOzUÐdNJ« …dz«b« ÃËœe ÂUE½ l ©WL U U …u− l 5³DI« qBHM …u− l 5³DI« qBHM Æv½œ« b× 3≥ ‰UBð« Æv½œ« b× 3≥ ‰UBð« π ! R410A …bŠu s ΫdH pKN²ð w²« ÆW¾O³K WI¹b …œU w¼Ë « l qUF² « bMŽ WUš UÞUO²Š« (HFC) ÊuЗU—uK Ë—b¹U¼ …œU Ãe s ÊuJ²¹ Íc« »Ëdðu¹“ sŽ …—U³Ž R410A b¹d³²« …œU Ê« • (ODP=0) Ê“Ë_« WCHM b¹d³ð …œU vKŽ Íu²%Ë —UA²½ö qÐU VN²K “Už vKŽ …œU*« Ác¼ Íu²% ôË Æ‰U¹d²½u ‰uuðËdÐ 5½«u l o«u²ð Ác¼Ë R125 Ë ©•µ∞® R32 s Z¹e w¼ R410A Ê« Æ©ARI WDÝ«uÐ A1 ”UÝ« vKŽ …—bI*«® WOL« –Uð« V−¹ ¨W½UOB« Ë« VBM« ¡UMŁ« ÆR22 WDžUC Âb²*« w½bF*« X¹e« sŽ nK²¹ Íc«Ë ¨R410A WDžUC rO×A²« X¹“ u¼ POE X¹“ Ê« • Æse« s WK¹uÞ …d²H VÞd« ¡«uNK R410A WuEM i¹dFð ÂbFÐ d¦« WDOŠ Æ¡«uN« s WÐuÞd« ’UB²« tMJ1 U½uJ*«Ë VOÐU½ô« w wI³²*« POE X¹“ WOKLŽ qł« s XR qJAÐ VOÐU½ô« U¹UN½ WODGð s bQð ¨R22 b¹d³²« …œU s d¦« WuNÐ WÐuÞd«Ë —U³GUÐ dŁQ²ð R410A b¹d³²« …œU Ê« • Æ©•µ∞® ÆVBM« ÆWDžUC« X¹e wU{ô« s×AUÐ `L¹ ô ÆR410A dOž Èdš« b¹d³ð …œU ‰ULF²Ý« sJ1 ô ÆjI tO³Mð R410A l ‰ULF²Ýö WBB «Ëœô« s×A« ÂuÞdšË pU*« œbF² ”UOI ©± “UG« »dð ·UAJ ©≤ b¹d³²« W½«uDÝ«Øb¹d³²« …œU W½«uDÝ« ©≥ T¹UN lØm¹dHð WC ©¥ lOÝuð …bŽ Ô ©µ b¹d³²« …œU …œUF²Ý« WMOU ©∂ • • • ! R410A W½«uDÝ« ÊuJð Î…œUŽ ÆqzU R410A b¹d³²« …œU s×ý V−¹ • R410A qzUÝ V× W½«uDÝô« fOJMð V−¹ ¨qzU »u³½« „UM¼ sJ¹ r «–« ÆqzU« V× qzU »u³½UÐ …eN− ÆÂULB« s b¹d³ð …œU0 UNM×ý« rŁ qU qJAÐ …bŠu« ⁄d Ò Æ…bŠu« ¡«œ« s qKI¹ ·uÝ «c¼ Êô ¨»d²« `OKBð bMŽ qU qJAÐ UN¾K vKŽ qLFð ô Æ ULOKF²« w UNÐ v u*« WOLJ« v« ÎUIË …b¹bł R410A ÆW¹UL(« «“UH f³« ÎU¹—Ëd{ p– ÊU «–« Æœd³*« qLŽ bMŽ b¹d³²« qzUÝ VOÐU½« Ë« jžUC« fLKð ô • • s×A «Ë m¹dH² « wU{ô« s×A « WOKš«b « …bŠu «Ë VOÐU½_« dONDð VOÐU½ô« ‰uÞ ÊU «–« ÆÎUI³ W½u×A WOł—U)« …bŠu« b¹d³ð …œU Ê« ¨R22 b¹d³²« …œU0 ÎUI³ UNM×ý - w²« WOł—U)« …bŠu« ¡UM¦²ÝUÐ «–« Æm¹dH²« bFÐ wU{« s×A WłUŠô Ê–« ¨©X ≤µ® Â∑\∂≤ s q« ÂUL ¡«uN« Ê_ ¡«uN« s qO qLF²Ý« „«c½¬ ¨©X ≤µ® Â∑\∂≤ s d¦« VOÐU½ô« ‰uÞ ÊU u²« VOÐU½«Ë WOKš«b« …bŠu« dONDð V−¹ qLŽ w qKš V³¹ U2 b¹d³²« …—Ëœ ¡UMŁ« vI³ð WÐuÞ— vKŽ Íu²×¹ ÆÁU½œ« ‰Ëb'« w 5³ u¼ UL wU{ô« s×A« ÆWDžUC« b¹d³²« …œU VOÐU½« lOÝuð WuL ALLEN ÕU²H ÆW½UOB« cHMË ÂULB« s WODžô« l—« Æm¹dH²« WC0 s×A« ”UOI ed q Ë« ÆwŁö¦« ÂULBK W½UOB« cHM0 s×A« ”UOI q Ë« …b nK²ð ÆÎU³¹dIð WIOœ≥∞ …b* m¹dH²« ÊuJ¹ Æm¹dH²« WC qGý Ò • • • • ”UOI …dÐ√ ‰UI²½« s bQð Æm¹dH²« WC WFÝ ·ö²šUÐ m¹dH²« WOł—U)« …bŠu« W½UOB« cHM Æ©Hg 3∑∂~∞® U¼U&« ≥ ÂUL Hg 3∑∂ ÁU&UÐ s×A« tO³Mð h× s ΫbQ² s ¨Hg 3∑∂~∞ u×½ ”UOI*« …dЫ qI²Mð r «–« WOKš«b« …bŠu« l²*« qO qzU« V½Uł WOł—U)« …bŠu« m¹dH²« ÂUL ÆWOU²« …uD)« oKž Æm¹dH²« WC nË«Ë dOOG²« ”UOI* ÂULB« oKž« ÂUL “UG« V½Uł iHM m¹dHð WC Ë © U¼U&« ≥® ’UB²ô« ÂUL `²« ¨WOł—U)« …bŠu« vKŽ 3¥ ÕU²H WDÝ«uÐ ©WŽU« »—UIŽ ÁU&« fJŽ® ©ÁU&« ≤® qzU« ÆwÝ«b« —ULLK ÂUL ’UB²ô« `² u²« Ÿu½ bMŽ ©b¹d³²« …œU ·UAJ qLF²Ý«® “UG« »dð v« ‰UI²½ô« q³ »d²« `OKB²Ð rË WOł—U)«Ë WOKš«b« …bŠuK oKž wUŽ oKž ±∞ • • Ë “UG« W½«uDÝ« `²« • oKž« ¨…bŠu« v« WÐuKD*« b¹d³²« …œU WOL a{ bMŽ • Æs×AK iHM*« jGC« ÂUL jGC« ÂUL (R22) «dG 15 m/49.2 ft 110 280 185 370 WOÐdF« Æ“UG« W½«uDÝ«Ë iHM*« ÆW½UOB« cHM ¡UDž bŽ« ÆW½UOB« cHM s W½UOB« »u³½« qB« • 12 m/39.4 ft 65 65 165 90 110 220 UÐ wU{ô« s×A « “«dÞ 10 m/32.8 ft 35 35 90 50 60 120 071 / 101 / 151 201 251 / 301 071R / 101R /151R 201R 251R / 301R WOKš«b« …bŠu« qzU« V½Uł (R410A) «dG WOł—U)« …bŠu« m¹dH²« ÂUL 15 m/49.2 ft 255 335 oKž 12 m/39.4 ft 150 200 UÐ wU{ô« s×A « “«dÞ 10 m/32.8 ft 80 110 311 301R “UG« V½Uł s×A « WOKLŽ r²ð ÆWIOœ Ê«eO W¬Ë “UG« W½«uDÝ« ‰ULF²ÝUÐ WOKLF« Ác¼ e−Mð Ê« V−¹ ÂUL ÂUL ’UB²ô« h×H« ‰ULF²ÝUÐ WOł—U)« …bŠu« w Èu² vKŽ« v« wU{ô« s×A« W¾³Fð oKž ÆW½UOB« cHM ‰öš s ’UB²ô« ÂUL wUŽ iHM `² ÆW½UOB« cHM ¡UDž l—« oKž cHM ed0 s×A« ”UOI* iHM*« jGC« V½Uł q Ë« • • Æ”UOILK wUF« jGC« WNł oKž«Ë W½«uDÝô« Z¹dNB ’UB²ô« ÆW½UOB« »u³½« s ¡«uN« œdÞ« Æ¡«uN« WHOJ …bŠË qGý Ò • dýR*« ¡«u{« qOGA²« ôUŠ X% ¡«uN« WHOJ …bŠu b¹d³² « …bŠË IR …—Uý« q³I² LED dýR ¡«u{« ‰Ëb'« ÷dF¹ ¨…—Uýô« ‰UÝ—« r²¹ ¨¡«dL(« ÊËœU WFýö bFÐ sŽ rJײ« tłu qOGAð bMŽ Æ¡wÞU)«Ë ÍœUF« Æ¡«uN« WHOJ …bŠË s s1ô« V½U'« qHÝ« w b¹d³² « …bŠu qI½ ‰u³ bOu² <VOÐ> u WOKš«b« …bŠu« vKŽ …—Uýô« q³I² —bB¹ Æ…—Uýô« LED dýR ¡«u{« lIð LED XR ON …—bI« qOGAð ÂuM« l{Ë ·U'« l{u« dýR ¡«u{« IR q³I² LED dýR ¡«u{« b¹d³² « …bŠu ¡wÞU)«Ë ÍœUF « qOGA² « ·dB² « ôUŠ ∫ LED dýR ¡«u{« QD)« ØqOGA² « …—Uý« Âu½ – – – XR ·Uł …—b ÆXR*« qOGAð ÆÂuM« l{Ë qOGAð Æ·U'« l{u« ÆWOUŽ WŽdÐ WŠËd* v« ‰u%Ë `ýd*« nE Ò ½ ÆœUL$ô« lM ÆpKOuÐ qBð« ÆhU½Øwðd WdG« ¡«u¼ fײ ‰UBð« ÆpKOuÐ qBð« ÆhU½Øwðd wKš«b« nK*« fײ ‰UBð« ÆpKOuÐ qBð« iuð dL² 5²O½UŁ q …bŠ«Ë …d 5²O½UŁ q 5ðd qLŽ d¦Fð Ë« ¨fײ*« ‰UBðUÐ WKJA błuð Æ“UG« »dð Ë« bz«e« Ê“u« s WDžUC« wUŠ OFF Ë« ON ±± 5²O½UŁ q ON «d ≥ W¾b² « a{ …bŠu LED W¾b² « a{ …bŠË dýR ¡«u{« qOGA²« ôUŠ X% ¡«uN« WHOJ …bŠu LED dýR ¡«u{« ‰Ëb'« ÷dF¹ Æ¡wÞU)«Ë ÍœUF« Æ¡«uN« WHOJ …bŠË s s1ô« V½U'« qHÝ« w ÂuM« l{Ë …—«d(«ØWŠËd*« l{Ë ·U'« l{u« b¹d³²« l{Ë LED dýR ¡«u{« lIð Wł—œ du¹ Íc« “wzUIK²«” l{uK fײ0 …eN− W¾b²« a{ …bŠË Ê« “W¾b²«” Ë« “b¹d³²«” l{u wzUIK²« q¹uײ« WDÝ«uÐ WdGK WuIF …—«dŠ ©dCš«ØdLŠ«® ÆÂb²*« q³ s WÞu³C*« …—«d(« Wł—œ v« UIË Î W¾b² « a{ …bŠu ¡wÞU)«Ë ÍœUF « qOGA² « ·dB² « ôUŠ ∫ LED dýR ¡«u{« QD)« ØqOGA² « …—Uý« Âu½ – Æb¹d³²« l{Ë – Æ·U'« l{u« – ÆWŠËd*« l{Ë – Æ…—«d(« l{Ë – ÆW¾b²« WOKLŽ w wzUIK²« l{u« – Æb¹d³²« WOKLŽ w wzUIK²« l{u« – ÆlOIB« W«“« WOKLŽ ÆpKOuÐ qBð« Æ◊dH*« Ê“u« s WDžUC« W¹ULŠ ÆpKOuÐ qBð« ÆhU½Øwðd wKš«b« nK*« fײ ‰UBð« ÆpKOuÐ qBð« ÆhU½Øwðd wł—U)« nK*« fײ ‰UBð« ÆpKOuÐ qBð« ÆhU½Øwðd WdG« ¡«u¼ fײ ‰UBð« …—«dŠ WŠËd ·Uł w qUA błuð b ¨©ÂuM« WHOþË ·UI¹« l® W¾b²« l{Ë Ë« b¹d³²« l{Ë w ÂUEM« ÊU «–« Æ“UG« »dð Ë« ◊dH*« Ê“u« s WDžUC« W¹ULŠ ÂUE½ d¦Fð Ë« ¨fײ*« ‰UBð« iuð OFF Ë« ON ±≤ ON b¹d³ð ¡«uN « WHOJ …bŠË qOGAð ·U'« l{u « d?_« d?š¬ w?Ë dO³²« …—«dŠ Wł—œ qIð ·uÝ ¨ÎU??² `ýd*« ÊuJ¹ UbMŽ Æ·U?'« l?{u?U?Ð …b?Šu?« q?O?G?A?ð s?J?1 ¨u'« w WOUŽ WÐuÞd« ÊuJð UbMŽ • Æ<DRY> d²š«Ë ÆœUL$ô« v« ÍœRð …—«dŠ Wł—œ XK Ë «–« Æ`ýd*« ŒUð« v« …—Uýö LED ¡u{ iu¹ ·uÝ • <MODE> —“ • jG{« W?ł—b« s ”UOI°≥µ[∂Ø°≤ 5?²?ł—b?Ð vKŽ« WdG« …—«dŠ Wł—œ X½U «–« ÆlOIB« W«“UÐ √b³ðË …bŠu« nu²ð ·uÝ ¨”UOI ≤∏\¥Ø°≤≠ v« dO³²« • s?L?{ qBð Ê« v« b¹d³²« l{Ë X% ¡«uN« WHOJ qG²Að ·uÝ ¨WÞu³C*« q?³? W?Þu?³?C?*« W?ł—b?« v« W½—UI*UÐ ·ö²šô« Èb s ”U?OI°≥µ[∂Ø°≤ b¹d³²K …—bI*« WF «Ë WŠËd*« WŽdÝ Æ·U'« l{u« v« ‰uײ« • • ·ö²šô« Èb s ”U?OI°≥µ[∂Ø°≤ s?L{ WdG« …—«dŠ Wł—œ X½U «–« ÆWŠËdLK ÈuBI« WŽd« bMŽ b¹d³²K …—bI*« WFUÐ œËe²« r²¹ LOW Ë MEDIUM WŽdÐ …bŠu« qOGAð bMŽ b¹d³²« WFÝ iHMð ·uÝ • Æ·U'« l{u« X% …dýU³ qG²Að ·uÝ ¨WÞu³C*« Wł—b« v« W½—UI*UÐ ÆWŠËdLK Æ·U'« l{u« X% LOW WŽdÐ …bŠu« qG²Að ·uÝ • ©jI W¾b² « a{ …bŠu ® W¾b² « l{Ë W?ŠËd?*« q?G?²?A?ð ¨l?O?I?B« WЫ–« Ë« b¹d³²« …—Ëœ …dýU³0 …bŠu« qOGAð bMŽ • ÆWÐužd*« …—«d(« Wł—œ v« nK*« qB¹ UbFÐ WOKš«b« Âb?Ž 5( WOKš«b« WŠËd*« qG²Að ·uÝ ¨WÞu³C*« Wł—b« v« ‰u wI« u« bMŽ • ÆWOU{« W¾bð W¹UÐ b¹Ëe²« s nK*« sJ9 ·Uł Øb¹d³ð WOÐdF« œUL$ô« lM 25°C/77°F ¡«uNK wIô« »UO½ôUÐ rJײ « Ë« —U??O?K? bOUÐ ⁄dH*« ¡«uN« WJO³ý j³{ pMJ1 ¨¡«uN« Ê«—Ëœ WOUF …œU¹e • Æ5LOK ¡«uN« n¹dBð oý tÒłuðô ¨·U'« l{u« qOGAðË b¹d³²« l{Ë qOGAð ¡UMŁ« • nŁUJð Àb×¹ b ¨WI¹dD« ÁcNÐ qOGA²« dL²Ý« «–« ÆΫbł WK¹uÞ …b* qHÝô« u×½ ÆdODI²« V³Ð «c¼ ¨oA« vKŽ ©jI W¾b² « a{ …bŠu ® …bz«e « W¾b² « s W¹UL(« WOKš«b« WŠËd*« q¹b³ð sJ1 ¨WDžUC« lD ¡UMŁ√ • ON (i) OFF (ii) Ë« ©WOËô« W¾ON²«® Ë« ·UI¹ô«Ë qOGA²« WK HOT KEEP U (iii) ÆwDOD²ULÝd« w `{u u¼ UL ‚ôe½ô« ÕU²H W¾ONð WDÝ«uÐ OFF INTERVAL ON Æ©ON/OFF ÕU²H —«uł v«® wUô« —UÞô« ¡UDž vKŽ ÕU²H*« lI¹ • …œU?Ž« v?« …bŠuK —UO²UÐ œËe²« cšQ ÃU²×¹ ¨—UO)« —UO²š« bMŽ ∫WEŠö ON/OFF ÕU²H ÆWHOþu« jOAMð ÷dG j³C« ©jI W¾b² « a{ …bŠu ® …bz«e « W¾b² « s W¹UL(« `ýd*« ÊU Ë« ¨WOUŽ WOł—U)« Ë«ØË WOKš«b« …—«d(« Wł—œ ÊU «–« WUŠ w W?ł—œ q?B?ð U?b?M?Ž W?D?žU?C?« q?B? r²¹Ë Æb¹d³²« …œU vL% ·uÝ ¨a² Æ”UOI°±¥≥[∂Ø°∂≤ v« nŁUJ²« …—«dŠ ±≥ • qOGA²K WOÝUOI « ôU(« W¾b² « a{ …bŠË Th °C/°F Ts °C/°F - 10 / 50 - 26.7 / 80.1 -9 / 15.8 -8 / 17.6 18 / 64.4 24 / 75.2 b¹d³² « …bŠË …—«d(« Wł—œ Wł—b v½œô« b(« WOKš«b « …—«d(« Wł—b vBô« b(« WOKš«b « …—«d(« Wł—b v½œô« b(« WOł—U)« …—«d(« Wł—b vBô« b(« WOł—U)« …—«d(« ÆWU'« WKOB³« …—«dŠ Wł—œ ∫ ÆW³Þd« WKOB³« …—«dŠ Wł—œ ∫ Th °C/°F Ts °C/°F 13.9 / 57.0 19.4 / 66.9 19.4 / 66.9 26.7 / 80.1 13.9 / 57.0 19.4 / 66.9 24 / 75.2 46 / 114.8 WOKš«b « …—«d(« Wł—b vBô« b(« WOKš«b « …—«d(« Wł—b v½œô« b(« WOł—U)« …—«d(« Wł—b vBô« b(« WOł—U)« …—«d(« ! Æ¡«uN« WHOJ …bŠË Õö Ub Wł—b v½œô« b(« Ts Th d¹c% Æo¹d(« Ÿôb½« dDš v« ÍœR¹ Íc«Ë WOzUÐdN …—«d(« Wł—œ « q³ —UO²K wOzd« q u*« s œËe²« qB« ÀËbŠ v« «c¼ ÍœR¹ ·uÝ ÆON vKŽ WUD« ÊuJð UbMŽ —UO²« q³ V×ðô • • WOJOðU²Ýô« ¡UÐdNJ « `ýd ∫Í—UO²š« W×z«d « W «“«Ë WOJOðU²Ýô« ¡UÐdNJ « s ¡«uN « WOIM² ¡«œô« ÃËœe `ýd `ýd*« —UÞ«Ë jÝu « s WN¹dJ « ≠≤ ¡«œô« ≠± ¡«œô« VI¦ « w WN¹dJ « W×z«d « W «“« WOJOðU²Ýô« ¡UÐdNJ « s ¡«uN « WOIMð `ýd WEU×LK WOzd dOG« …dOGB« ¡«u?¼ ¡U?I?½ v?K?Ž k?U?×?¹Ë ¡«uN« w …œułu*« WN¹dJ« œ«u*«Ë `z«Ëd« q¹e¹ «—c«Ë ÊUšb« ¨Î«bł dOGB« —U³G« q¹e¹ ¡UÐdNJK ÎU?I?³? Êu×A*« ÊdOÐËd³Ou³« `ýd l WdG« ¡«u¼ WUE½ vKŽ ƉUFH« ÊuЗUJ« `ýd WDÝ«uÐ WdG« ÆWOJOðU²Ýô« VOd² « WOHO WJO³ý `²« ± ÆwUô« —UÞô« ¡«œô« `ýd qšœ« ≥ ¡UÐdNJK ÃËœe*« W×z«d« W«“«Ë WOJOðU²Ýô« Æ×UK WOK ô« U×ýd*« o“« ÆVI¦« w WN¹dJ« ≤ `ýd*« ‰Ušœ« bŽ« ¥ ÆwK ±¥ ô« ! WOÐdF« tO³Mð Æ¡«uN« WHOJ qOË s Á¡«dý sJ1 wöN²Ý« ¡eł `ýd*« Æ≥ W?×?z«d?« W?«“«Ë W?O?JOðU²Ýô« ¡UÐdNJ« s ¡«uN« WOIMð `ýd ‰«b³²Ý« V−¹ ·öž `²Hðô ÆœËb*« nOKG²« s tł«dš« bFРΫ—u b¹b'« `ýd*« qLF²Ý« Æ¥ ¨dLÝô« ÊuK« v« `ýd*« Êu dOG²¹ UbMŽ Ë« dNý« ∂ q …bŠ«Ë …d WN¹dJ« Æ»d« ULNM Í« s b¹e¹ ·uÝ «c¼ Êô wKFH« ‰ULF²Ýô« q³ dJ³ XË w b¹b'« `ýd*« - u? v?²?Š ¨U?N?U?L?F?²?Ý« …œU?Ž« Âb?ŽË …d?³G*« ÆWN¹dJ« W×z«d« dŁ« U×ýd*« s hK²« V−¹ ÆUNKžË UNHOEMð d¹c% ! Æ¡«uN« WHOJ …bŠË Õö Æo¹d(« Ÿôb½« dDš v« ÍœR¹ Íc«Ë WOzUÐdN Ub « q³ —UO²K wOzd« q u*« s œËe²« qB« ÀËbŠ v« «c¼ ÍœR¹ ·uÝ ÆON vKŽ WUD« ÊuJð UbMŽ —UO²« q³ V×ðô • • W½UOB«Ë `OKB²« W½UOB « …b*« «¡«dł« W½UOB « ÂU« 5Žu³Ý« q …bŠ«Ë …d s q«® ÎöOK ¡w«œ ¡U0 tÒHE½ Ë« WOzUÐdN WMJ ‰ULF²ÝUÐ `ýd*UÐ oB²K —U³ž Í« ‰“« .qô« vKŽ ƉœUF² nOEMð ‰uK× l ©”UOI°±∞¥Ø °¥∞ Ʊ Æ…bŠu« qš«œ w tF{Ë …œUŽ« q³ tHHłË ΫbOł `ýd*« nDý« Æ≤ Æ…—ËdC« Æ`ýd*« nOEM² W¹ËUOLOJ« Ë« …—UOD« œ«u*« Ë« ¨5Ë“UJ« qLF²ðô Æ≥ 5Žu³Ý« q …bŠ«Ë …d ¡U?0 W?Žu?I?M? WLŽU½ ‘UL WFDIÐ t×0 WŠuK« Ë« WJO³A« vKŽ błu¹ —U³ž Ë« ŒUÝË« W¹« nE½ Ò Æ± .qô« vKŽ ƉœUF² nOEMð ‰uK× l ©”UOI°±∞¥Ø°¥∞ s q«® ÎöOK ¡w«œ bMŽ —«dJ²« …œU¹“ ÆWOKš«b« …bŠu« nOEM² W¹ËUOLOJ« Ë« …—UOD« œ«u*« Ë« 5Ë“UJ« qLF²ðô Æ≤ Æ…—ËdC« tO³Mð ! WŠuK« WЫ–« v« ÍœR¹ ·uÝ «c¼ Æ¡«uN« WHOJ …bŠË s »dIUÐ W¹—«dŠ …eNł« W¹« qGAðô Ò Æ…b¹bA« …—«d×K W−O²M UN¼uAð Ë« WOJO²Ýö³« se « s WK¹uÞ …d²H …bŠu « «b ²Ý« ÂbŽ bMŽ Æ—UO²« fÐU l—« WDÝ«uÐ 5²ŽUÝ …b* …bŠu« qGý Ò WKI² WOzUÐdN …dz«œ Âb²ð XM «–« ÆWOU²« W¾ON²« Æ…dz«b« qB« ¨…bŠuK b¹d³ð ∫qOGA²« l{Ë U¹—UD³« l—« ”UOI°∏∂Ø°≥∞ ∫…—«d(« Wł—œ ±µ ¡«uN « `ýd wKš«b « bMŽ —«dJ²« …œU¹“ ÆbFÐ sŽ rJײ« tłu s Ʊ WOKš«b « …bŠu « Æ≤ tŠö«Ë qK)« sŽ Ídײ « qO œ Æ…bŠuK —UO² UÐ œËe² « nË« Ϋ—u ¨¡«uN « WHOJ …bŠË qLŽ w ‰ö²š« Í« XEŠô «–« ÆtŠö«Ë qK)« sŽ Ídײ « qO b …bOH*« U×OLK² « iF³ WO U² « »U³Ýô«Ë ôU(« h׫ VOF « qFH «Ø»U³Ýô« - Æ¡«uN« WHOJ qOGAð bFÐ ozUœ ≥ …b* WDžUC« qG²Aðô Ʊ - Æ¡«uN« WHOJ …bŠË qG²Aðô Æ≤ - ÆΫbł iHM ¡«uN« »UO½« Æ≥ - ÆWN¹d W×z«— vKŽ Íu²×¹ »UM*« ⁄dH*« ¡«uN« Æ¥ - ÆWOKš«b« …bŠuK WOUô« ¡«uN« WJO³ý vKŽ nŁUJ²« Ƶ ÆqOuUÐ qBð«Ë …bŠu« qOGAð nË« - Æ¡«uN« WHOJ …bŠË s ¡U*« ob²¹ Æ∂ Æd³*« VOÐU½√ nK vKŽ b¹d³²« …œU qzUÝ »UM¹ - wJ ozUœ ¥ v« ≥ …b* dE²½« ÆqOGA²K ·uQ*« ‚öD½ô« qÐUI W¹UL(« ÆqLFUÐ WDžUC« √b³ð Ɖ«b³²Ýô« v« WłU×Ð WL UH« Ë« ¨—UO²« w —uB .‰uBH —UO²« fÐU ÆW¾ÞUš …—uBÐ dOšQ²« XR j³{ qL²;« s hAUÐ ‰UBðô« vłd¹ ¨ UIOIײ« Ác¼ q bFÐ ‰ö²šô« dL²Ý« «–« Æ¡«uN« WHOJ …bŠË VOd²Ð h²<« Æ¡«uN« `ýd ŒUð« ÆWŠu²H c«uM« Ë« »«uÐ_« Æ¡«uN« n¹dBðË m¹dHð ÂU« ozUŽ błu¹ ÆWOU Wł—bÐ ÎUOUŽ fO …—«d(« Wł—œ rOEMð ¨a«ì —uDF« Ë« ¨ÊUšb« «—– Ë« ¨dzU−« V³Ð `z«Ëd« ÊuJð b ÆnK*« vKŽ oB²Kð b w²«Ë Æ«b²Ýô« s WK¹uÞ …d² bFÐ ¡«uN« WÐuÞ— V³Ð «c¼ …—«d(« Wł—œ W¾ONð …œU¹eÐ r ¨Î«bł WCHM WÞu³C*« …—«d(« Wł—œ ÆWOUŽ WŽdÐ WŠËd*« vKŽ …bŠu« qGýË Ò ÆqOGA²« ¡UMŁ« ¡«uN« WHOJ …bŠË s ¡«uN« »UO½« fO¼ u Æ∑ ÆW½UOB UÐ h²<« h A UÐ Ë«ØwK;« pKOuÐ ‰UBðô« vłd¹ ¨‰ö²šô« dL²Ý« «–« ±∂ WM« ÊuJð ¨X½U WG W¹QÐ UNH½ WLłd²« w ·ö²š« Í«Ë VO²J« «c¼ dOHð w ÷—UFð Í« ÀbŠ «–« • Æ…bzU« w¼ W¹eOKJ½ô« Æo³ —UFý≈ ÊËœ s XË Í« w UM¼ …œułu UH «u W¹«Ë rOLB²« q¹bFð o×Ð lMB*« kH²×¹ • OYL MANUFACTURING COMPANY SDN. BHD. JALAN PENGAPIT 15/19, P.O. BOX 7072, 40702 SHAH ALAM, SELANGOR DARUL EHSAN, MALAYSIA.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120

Acson ALC30C Guía de instalación

Categoría
Acondicionadores de aire de sistema dividido
Tipo
Guía de instalación