CARLO GAVAZZI EM27172DMV63X2SN Guía de instalación

Tipo
Guía de instalación
CARLO GAVAZZI
Automation Components
Carlo Gavazzi Controls SpA,
Via Safforze, 8 - 32100
Belluno (Italy)
Tel. +39 0437 355811,
Fax +39 0437 355880
EM271 IM ML 8021618 070716
EM271 “Energy Analyzer”
1.2.3...
...3.2.1
OK
a
b
c
fig.3
fig.2
4
1
2
3
P= AL1 130A, AL2 130A, AL3 130A; Q= VL1 230V, VL2 89,0V, VL3 65.0V;
R= VL12 390V, VL23 390V, VL31 390V.
BASIC PROGRAMMING AND RESET: to enter the complete
programming mode, press the key 2 for at least 3 sec. (g 1). Entering the
programming mode, all the measurements and control functions are inhibited.
During this phase the ashing of the LED has not to be considered.
01
PASS?: entering the right password (default value is 0) allows accessing
the main menu.
02
CnG PASS: it allows changing the password.
03
SYS 1P/SYS 3P: 3P/1.3P: 3-phase (3- or 4-wire) supply. Management
of one 3-phase load; 3P/2.3P: 3-phase (3- or 4-wire) supply. Management of
two 3-phase loads; 3P/3.1P: 3-phase (4-wire) supply. Management of three
1-phase loads; 3P/6.1P: 3-phase (4-wire) supply. Management of six 1-phase
loads. 1P/3.1P: 1-phase (2-wire) supply. Management of three 1-phase loads.
1P/6.1P: 1-phase (2-wire) supply. Management of six 1-phase loads.
04
SUM: sum function of TCD.
05
EC: easy connection function.
06
P.int ti:
integration time for “dmd” power calculation.
07
Ut rAt.: VT ratio.
08
PuL
1: it selects the pulse weight (number of kWh per pulse, from 0.01 to 9.99) Load
1.
09
PuL 2: it selects the pulse weight (number of kWh per pulse, from 0.01
to 9.99) Load 2.
10
t.on: T ON time (Pulse duration 40msec or 100msec).
11
AddrESS: serial address: from 1 to 247.
12
bAud: Modbus baud
rate.
13
PAritY: Modbus parity.
14
EnEPA.rE: reset of the Load 1 and
Load 2 energy values.
15
EnEto.rE: reset of the total energy values.
16
End: it allows exiting the programming mode.
ITALIANO
1
premere il tasto per scorrere i menu o incrementare o decrementare i valori da
impostare.
2
è possibile entrare nei sub menù e modicare i valori cambiando
da positivo a negativo come esemplicato in g. 3.
3
il LED lampeggia
proporzionalmente all’energia attiva importata consumata.
4
per bloccare
l’accesso alla programmazione, ruotare il trimmer in senso orario no a ne
corsa.
A= anno di produzione e versione del rmware; B= kWh per impulso (relativo al
LED frontale); C= tipo di sistema (6.1P); D= Rapporto di trasformazione TV; E e
F= valore del primario del TCD; G e H= Uscita digitale 1 e 2 (kWh per impulso). I=
indirizzo di comunicazione seriale; L= reset dei valori demand massimi; M= kWh
765432.1 kW 10.1; N= 221 kW dmd di sistema; O= valore demand massimo 261
kW; P= AL1 130A, AL2 130A, AL3 130A; Q= VL1 230V, VL2 89,0V, VL3 65.0V;
R= VL12 390V, VL23 390V, VL31 390V.
PROGRAMMAZIONE BASE E RESET: per accedere alla
programmazione completa premere il tasto 2 e mantenerlo premuto per almeno
3 secondi (g. 1). Entrati nel modo di programmazione tutte le misure e funzioni
di controllo sono inibiti. In questa fase il lampeggio del DEL non deve essere
considerato.
01
PASS?: inserendo la password corretta (di default è 0) si accede al
menù principale.
02
CnG PASS: permette di modicare la password.
03
SYS 1P/SYS 3P: 3P/1.3P: alimentazione trifase (3 o 4 li). Gestione di
un carico trifase; 3P/2.3P: alimentazione trifase (3 o 4 li). Gestione di due carichi
trifase; 3P/3.1P: alimentazione trifase (4 li). Gestione di tre carichi monofase;
3P/6.1P: alimentazione trifase (4 li). Gestione di sei carichi monofase; 1P/3.1P:
alimentazione monofase (2 li). Gestione di tre carichi monofase; 1P/6.1P:
alimentazione monofase (2 li). Gestione di sei carichi monofase.
04
SUM:
funzione somma dei TCD.
05
EC: funzione easy connection.
06
P.int ti:
tempo di integrazione per il calcolo della potenza “dmd”.
07
Ut rAt.: rapporto
TV.
08
PuL 1: seleziona il peso dell’impulso del carico 1 (numero di kWh per
impulsi, da 0.01 a 9.99).
09
PuL 2: seleziona il peso dell’impulso del carico
1 (numero di kWh per impulsi, da 0.01 a 9.99).
10
t.on: T ON time (durata
dell’impulso 40msec o 100msec).
11
AddrESS: indirizzo porta seriale: da
1 a 247.
12
bAud: baud rate Modbus.
13
PAritY: parità Modbas.
14
EnEPA.rE: reset dei valori di energia del carico 1 e 2.
15
EnEto.rE:
reset dei valori di energia totali.
16
End: permette di uscire dal menu di
programmazione.
DEUTSCH
1
Die Taste drücken, um das Menü durchzublättern oder die einzugebenden
Werte zu erhöhen bzw. zu verringern.
2
Es besteht die Möglichkeit, die
Submenüs aufzurufen und die Werte von positiv auf negativ zu ändern, wie als
Beispiel in Abb. 3 dargestellt.
3
Die LED blinkt proportional zur verbrauchten
aktiven Energie.
4
Zum Sperren des Zugriffs auf die Programmierung, den
Trimmer bis zum Anschlag im Uhrzeitersinn drehen.
A= Herstellungsjahr plus Firmware-Release; B= kWh pro Impuls (relevant
für die Front-LED); C= System-Typ (6.1P); D= Wandlungsverhältnis
TV; E und F= Primärwert von TCD; G und H= digitaler Pulsausgang
1 und 2 (kWh pro Impuls); I= Serielle Kommunikationsadresse; L=
Reset der maximalen Demand-Werte; M= kWh 765432.1 kW 10.1; N=
221 kW dmd des Systems; O= Maximaler Demand-Wert 261 kW; P=
AL1 130A, AL2 130A, AL3 130A; Q= VL1 230V, VL2 89,0V, VL3 65.0V;
R= VL12 390V, VL23 390V, VL31 390V.
BASIS-PROGRAMMIERUNG UND RESET: Zum Aufruf der
kompletten Programmierung die Taste 2 betätigen und mindestens 3 Sekunden
gedrückt halten (Abb.1). Nach Aufruf der Programmierung sind alle Messungen
und Kontrollfunktionen gesperrt. In dieser Phase muss das Blinken von DEL
nicht berücksichtigt werden.
01
PASS?: Bei Eingabe des korrekten Password (Default-Wert ist 0) wird
das Hauptmenü aufgerufen.
02
CnG PASS: Gestattet die Änderung des
Passwords.
03
SYS 1P/SYS 3P: 3P/1.3P: Drehstromversorgung (3 oder
4 Litzen). Steuerung einer Drehstromlast; 3P/2.3P: Drehstromversorgung
(3 oder 4 Litzen). Steuerung von zwei Drehstromlasten; 3P/3.1P:
Drehstromversorgung (4 Litzen). Steuerung von drei Drehstromlasten; 3P/6.1P:
Drehstromversorgung (4 Litzen). Steuerung von sechs Einphasenlasten;
1P/3.1P: Einphasenstromversorgung (2 Litzen). Steuerung von drei
Einphasenlasten; 1P/6.1P: Einphasenstromversorgung (2 Litzen). Steuerung
von sechs Einphasenlasten.
04
SUM: Summen-Funktion der TCD.
05
EC:
Funktion Easy Connection.
06
P.int ti: Integration der Zeit zur Berechnung
der Leistung “dmd”.
07
Ut rAt.: Verhältnis TV.
08
PuL 1: Selektiert das
Gewichts des Impulses der Last 1 (Anzahl kWh für Impulse, von 0.01 bis 9.99).
09
PuL 2: Selektiert das Gewichts des Impulses der Last 1 (Anzahl kWh
für Impulse, von 0.01 bis 9.99).
10
t.on: Zeit T ON (Impulsdauer 40 msec
oder 100 msec).
11
AddrESS: Adresse des seriellen Ports: zwischen 1
und 247.
12
bAud: Modbus- Baudrate.
13
PAritY: Parität Modbus.
14
EnEPA.rE: Reset Energie der Last 1- und Last 2-Energiewerte.
15
EnEto.rE: Reset Gesamt-Energiewerte.
16
End: Gestattet das Verlassen
des Programmierungs-Menüs.
FRANÇAIS
1
presser la touche pour déler les menus ou augmenter ou diminuer les
valeurs à régler.
2
il est possible d’entrer dans les sous-menus et modier les
valeurs en changeant de positif à négatif comme illustré à la g. 3.
3
la LED
clignote proportionnellement à l’énergie active consommée.
4
pour bloquer
l’accès à la programmation, tourner le trimmer dans le sens des aiguilles d’une
montre jusqu’en butée.
A= année de production plus version rmware; B= kWh par impulsion (led
frontale); C= type de système (6.1P); E et F= valeur primaire de TCD; G et H=
Sortie d’impulsion logique 1 et 2 (kWh par impulsion); I= adresse de communication
série; L= réinitialisation des valeurs «demand» maximales; M= kWh 765432.1
kW 10.1; N= 221 kW dmd de système; O= valeur «demand» maximale 261
kW; P= AL1 130A, AL2 130A, AL3 130A; Q= VL1 230V, VL2 89,0V, VL3 65.0V;
R= VL12 390V, VL23 390V, VL31 390V.
PROGRAMMATION DE BASE ET REINITIALISATION: pour
accéder à la programmation complète presser la touche 2 et la maintenir
enfoncée pendant au moins 3 secondes (g. 1). Une fois dans le mode de
programmation toutes les mesures et fonctions de contrôle sont bloquées.
Durant cette phase le clignotement de la LED ne doit pas être pris en
considération.
01
PASS?: en saisissant le mot de passe correct (par défaut 0) on accède
au menu principal.
02
CnG PASS: permet de modier le mot de passe.
03
SYS 1P/SYS 3P: 3P/1.3P: alimentation triphasée (3 ou 4 ls). Gestion
d’une charge triphasée; 3P/2.3P: alimentation triphasée (3 ou 4 ls). Gestion
de deux charges triphasées; 3P/3.1P: alimentation triphasée (4 ls). Gestion de
trois charges monophasées; 3P/6.1P: alimentation triphasée (4 ls). Gestion
de six charges monophasées. 1P/3.1P: alimentation monophasée (2 ls).
Gestion de trois charges monophasées. 1P/6.1P: alimentation monophasée
(2 ls). Gestion de six charges monophasées.
04
SUM: fonction somme
des TCD.
05
EC: fonction easy connection.
06
P.int ti: intégration du
temps pour le calcul de la puissance “dmd”.
07
Ut rAt.: rapport TT.
08
PuL 1: sélectionne le poids de l’impulsion de la charge 1 (nombre de kWh par
impulsion, de 0.01 à 9.99).
09
PuL 2: sélectionne le poids de l’impulsion de
la charge 1 (nombre de kWh par impulsion, de 0.01 à 9.99).
11
t.on: T ON
time (Durée d’impulsion 40msec ou 100msec).
12
AddrESS: adresse port
série: de 1 à 247.
13
bAud: débit en bauds Modbus.
15
PAritY: parité
Modbas.
14
EnEPA.rE: réinitialisation de valeurs d’énergie de la charge 1
et 2.
15
EnEto.rE: réinitialisation des valeurs d’énergie totales.
16
End:
permet de quitter le menu de programmation.
ESPAÑOL
1
pulsar la tecla para avanzar por los menús y para aumentar o reducir los
valores a congurar.
2
es posible entrar en los submenús y modicar los
valores cambiando de positivo a negativo o viceversa, como se indica en la g. 3.
3
el LED parpadea proporcionalmente a la energía activa consumida.
4
para bloquear el acceso a la programación, girar el potenciómetro en
sentido horario hasta el tope.
A= año de producción más la versión de rmware; B= kWh por pulso
(correspondiente al LED delantero); C= tipo de sistema (6.1P); D= orden de
las fases en los TCD; E y F= valor primario de TCD; G y H= Salida 1 y 2 de
pulso digital (kWh por pulso); I= dirección de comunicación en serie; L= puesta
a cero de los valores máximos de demanda; M= kWh 765432.1 kW 10.1; N=
221 kW dmd de sistema; O= valor máximo de demanda 261 kW; P= AL1 130A,
AL2 130A, AL3 130A; Q= VL1 230V, VL2 89,0V, VL3 65.0V; R= VL12 390V,
VL23 390V, VL31 390V.
PROGRAMACIÓN BÁSICA Y PUESTA A CERO: para acceder
a la programación completa, pulsar la tecla 2 y mantenerla pulsada durante
al menos 3 segundos (g. 1). Una vez dentro del modo de programación, se
inhiben todas las medidas y funciones de control. En esta fase no debe tenerse
en cuenta el parpadeo del LED.
01
PASS?: introduciendo la contraseña correcta (por defecto es 0) se
accede al menú principal.
02
CnG PASS: permite modicar la contraseña.
03
SYS 1P/SYS 3P: 3P/1.3P: suministro de 3 fases (3 o 4 hilos).
Administración de una carga trifásicas; 3P/2.3P: suministro de 3 fases (3 o 4
hilos) Administración de dos cargas trifásicas; 3P/3.1P: suministro de 3 fases
(4 hilos) Administración de tres cargas monofásicas; 3P/6.1P: suministro de 3
fases (4 hilos) Gestión de seis cargas monofásicas. 1P/3.1P: suministro de 1
fase (2 hilos) Gestión de tres cargas monofásicas. 1P/6.1P: suministro de 1
fase (2 hilos) Gestión de seis cargas monofásicas.
04
SUM: función suma
de los TCD.
05
EC: función conexión fácil.
06
P.int ti: integración del
tiempo para calcular la potencia “dmd”.
07
Ut rAt.: relación de VT.
08
PuL
1: selecciona el valor del pulso (número de kWh por pulsos, de 0.01 a 9.99).
09
PuL 2: selecciona el valor del pulso (número de kWh por pulsos, de
0.01 a 9.99).
10
t.on: tiempo ON (Duración del pulso 40msec o 100msec).
11
AddrESS: dirección puerto serie: de 1 a 247.
12
bAud: velocidad en
baudios, Modbus.
13
PAritY: paridad Modbas.
14
EnEPA.rE: puesta
a cero de los valores de energía de carga 1 y 2.
15
EnEto.rE: puesta a
cero de los valores de energía totales.
16
End: permite salir del menú de
programación.
DANSK
1
Tryk på tasten for at rulle ned igennem menuerne eller forøge og formindske
de værdier, der skal indstilles.
2
Man kan gå ind i undermenuerne og ændre
værdierne ved at skifte fra positiv til negativ som vist i g. 3.
3
Lysdioden lyser
i forhold til den forbrugte aktive energi.
4
Drej på trimmeren i urets retning,
indtil den ikke kan komme længere, for at spærre for adgang til programmering.
A= Produktionsår og udgivelse af rmware; B= kWh per puls (relevant for
forreste LED); C= systemets type (6.1P); D= omdannelsesforhold for TV; E og
F= primær værdi af TCD; G og H= Digital pulsudgang 1 og 2 (kWh per puls); I=
seriekommunikationsadresse; L= reset af værdier med maksimale krav; M= kWh
765432.1 kW 10.1; N= 221 kW dmd af systemet; O= værdi med maksimalt krav
261 kW; P= AL1 130A, AL2 130A, AL3 130A; Q= VL1 230V, VL2 89,0V, VL3 65.0V;
R= VL12 390V, VL23 390V, VL31 390V.
GRUNDLÆGGENDE PROGRAMMERING OG RESET: For at
få adgang til den fulde programmering skal man trykke på tast 2 og holde den
inde i mindst 3 sekunder (g. 1). Når man er i programmeringsmode, er alle
målinger og kontrolfunktioner blokerede. I denne fase lyser LED’en, men det
skal man ikke tage hensyn til.
01.
PASS?: Ved at indsætte den korrekte adgangskode (standard er 0)
får man adgang til hovedmenuen.
02.
CnG PASS: Tillader en ændring af
adgangskoden.
03.
SYS 1P/SYS 3P: 3P/1.3P: 3 faser (3 eller 4 ledninger)
forsyning. Styring af en trefaset belastning; 3P/2.3P: 3 faser (3 eller 4 ledninger)
forsyning. Styring af to trefasede belastninger; 3P/3.1P: 3 faser (4 ledninger)
forsyning. Styring af tre enfasede belastninger; 3P/6.1P: 3 faser (4 ledninger)
forsyning. Styring af seks enfasede belastninger. 1P/3.1P: 1 fase (2 ledninger)
forsyning. Styring af tre enfasede belastninger. 1P/6.1P: 1 fase (2 ledninger)
forsyning. Styring af seks enfasede belastninger.
04.
SUM: Funktionen Sum
af TCD.
05.
EC: Funktionen Easy connection.
06.
P.int ti: Integrering af
tid for beregning af effekten “dmd”.
07.
Ut rAt.: TV-forhold.
08.
PuL 1:
Vælger vægten af impulsen for belastning 1 (antal kWh for impulser, fra 0,01
til 9,99).
09.
PuL 2: Vælger vægten af impulsen for belastning 1 (antal kWh
for impulser, fra 0,01 til 9,99).
10.
t.on: T ON time (Pulsvarighed 40msec
eller 100msec).
11.
AddrESS: Adressen på den serielle port: fra 1-247.
12.
bAud: Baudhastighed Modbus.
13.
PAritY: Modbus-paritet.
14.
EnEPA.rE: Reset af energiværdier for belastning 1 og 2.
15.
EnEto.
rE: Reset af totale energiværdier.
16.
End: Tillader, at man går ud af
programmeringsmenuen.
A
B
C
D
E
F
I
L
M
N
O
P
Q
R
RESET!
fig.1
60 100 200 400
MV5 MV6 MV5 MV6 MV5 MV6 MV5 MV6
60 999 999 999 999 764 999 432 744
100 999 999 994 999 662 999 397 684
200 764 999 662 999 497 855 331 570
400 432 744 397 684 331 570 248 427
NO TCD 999 999 999 999 999 999 999 999
TCDA1
TCDA2
tab. 1 MAX VT ratio according to the current sensor range - Rapporto VT MAX secondo il range del sensore
di corrente - Max VT Verhältnis gemäß Stromsensorbereich - Rapport max TT selon la plage du capteur de
courant - Relación VT máxima en función del rango del sensor de corriente - Max VT koecient i henhold til
strømsensorområde
In measurement mode
Al modo misura
Zum Messmodus
Au mode mesure
En el modo de
medición
I måletilstand
G
H
ENGLISH
1
press the key, to scroll the menus or increase/decrease the values to be set up.
2
you can enter the submenus and change the value change mode from
positive to negative or vice versa according to the logic indicated in g. 3.
3
the LED ashes proportionally to the active energy consumption.
4
turn the trimmer clockwise up to its run end to block programming mode.
A= Year of production plus rmware release; B= kWh per pulse (relevant to
the front led); C= type of system (6.1P); D= VT rating value; E and F= primary
value of TCD; G and H= Digital pulse output 1 and 2 (kWh per pulse); I=
serial communication address; L= reset the max demand values; M= kWh
765432.1 kW 10.1; N= system kW dmd 221; O= maximum demand 261 kW;
ITALIANO
Rischio di folgorazione. Scollegare la tensione prima di
rimuovere la protezione. L’installazione va eseguita solo da
personale competente. Non rimuovere la protezione [A] se i
terminali 9-10-11-12 sono utilizzati. Destinazione d’uso:
misura dei parametri elettrici, per uso interno. Da utilizzare in installazioni con
categoria di sovratensione III o inferiore. Collegare solo trasformatori di
corrente della serie TCD1X, TCD2X o TCD3X di Carlo Gavazzi.
I cavi di uscita dei trasformatori di corrente (terminalizzati con connettore
RJ) devono essere tenuti lontani da punti a tensione pericolosa.
NOTA: in caso di una connessione 3 li non considerare N riportato negli schemi.
[1] 3P/1.3P, 3 fasi (3 o 4 li) gestione di un carico trifase; [2] 3P/2.3P, 3 fasi (3 o 4 li)
gestione di due carichi trifase; [3] 3P/3.1P, 1 fase (2 li) gestione di tre carichi monofase;
[4] 3P/6.1P, 1 fase (2 li). Gestione di sei carichi monofase; [5] 1P/3.1P, alimentazione
monofase (4 li). Gestione di tre carichi monofase; [6] 1P/6.1P, alimentazione monofase
(4 li). Gestione di sei carichi monofase; [7] Uscita statica 1; [8] Uscita statica 2; [9]
Porta seriale RS485; [10] Doppia porta seriale (entra/esci) RS485.
Nota su RS485: la terminazione della porta seriale va eseguita solo sull’ultimo strumento
della rete mediante un ponticello tra i terminali B+ e T.
[11] Esempio di collegamento delle tensioni in cascata grazie ai connettori predisposti.
MESSAGGI DI ERRORE: [load 1] MISSInG tcd (TC del carico uno non connesso).
[load 2] MISSInG tcd (2nd TC del carico uno non connesso). [load 1] [load 2] MISSInG
tcd (TC dei carici 1 e 2 non connessi). EEE (Condizione di sovrascala degli ingressi di
misura, tensione e corrente).
DEUTSCH
Stromschlaggefahr. Vor Entfernen der Abdeckung die Spannung
unterbrechen. Installation nur durch einen Fachmann. Die Abdeckung [A]
nicht entfernen, wenn die Anschlüsse 9-10-11-12 nicht verwendet werden.
Verwendung: Messung von elektrischen Parametern, in Innenbereichen.
Verwendung in Installationen mit Überspannungs-Kategorie III oder niedriger. Bei
Anschluss von Stromwandlern, nur die Serien TCD1X oder TCD2X oder TCD3X von Carlo
Gavazzi verwenden.
Die Ausgangsleitungen der Stromwandler (welche am Ende mit
einem RJStecker ausgeführt sind), müssen von gefährlichen
spannungsführenden Teilen ferngehalten werden.
HINWEIS: bei 3-drahtigem Anschluss, den in den Plänen mit N bezeichneten Leiter
nicht berücksichtigen.
[1] 1.3P, 3 Phasen (3 oder 4 Litzen) für eine Drehstromlast; [2] 2.3P, 3 Phasen
(3 oder 4 Litzen) für zwei Drehstromlasten; [3] 3.1P, 1 Phase (4 Litzen) für drei
Einphasenlasten; [4] 6.1P, 1 Phase (4 Litzen) für sechs Einphasenlasten; [5] 1P/3.1P,
Einphasenstromversorgung (2 Litzen). Steuerung von drei Einphasenlasten. [6]
1P/6.1P, Einphasenstromversorgung (2 Litzen). Steuerung von sechs Einphasenlasten.
[7] Statischer Ausgang 1; [8] Statischer Ausgang 2; [9] Serieller Port RS485; [10]
Doppelter serieller Port (ein/aus) RS485.
Hinweis zu RS485: der Anschluss des seriellen Ports ist nach dem letzen Instrument
des Netzes anhand einer Brücke zwischen B+ und T vorzunehmen.[11] Beispiel für
Kaskaden-Anschluss der Spannungen anhand entsprechend vorgerüsteter Stecker.
FEHLERMELDUNGEN: [load 1] MISSInG tcd (TC der Last 1 nicht angeschlossen).
[load 2] MISSInG tcd (TC der Last 2 nicht angeschlossen). [load 1] [load 2] MISSInG
tcd (TC der Lasten 1 und 2 nicht angeschlossen). [load 2] WrOnG tcd (TC der Last 2
freigegeben, System 2.3P oder 6.1P, jedoch mit abweichendem Primärstrom im Vergleich
zum ersten TC). EEE (Messeingänge, Spannung und Strom außer Skala).
14 15 16 13
14 15 16 13
14 15 16 13
1 2
3 4
8
6
5
7
8
6
5
7
8
6
5
7
8
6
5
7
8
6
5
7
2
1
3
2
1
3
2
1
3
[1] 3P/1.3P
Load 1
[3] 3P/3.1P
Load 1
Load 2
Load 3
[2] 3P/2.3P
Load 1
Load 2
Load 3
Load 4
Load 5
Load 6
[4] 3P/6.1P
[7] [8]
[9] [10]
14 15 16 13
Load 1
Load 2
13 14 15 16
9 10 11 12
13 14 15 16
9 10 11 12
[11]
FRANÇAIS
Risque de choc électrique. Débrancher la tension avant
d’enlever le cache. L’installation doit être effectuée uniquement par
des personnes qualiées. Ne pas enlever le cache [A] si les bornes
9-10-11-12 ne sont pas utilisées. Usage prévu: mesure des
paramètres électriques, usage en intérieur. À utiliser sur des installations avec
une surtension de cat. III ou inférieure. Lors de la connexion de transformateurs
de courant, utiliser uniquement les séries TCD1X ou TCD2X ou TCD3X de
Carlo Gavazzi.
Le câble de sortie des transformateurs de courant (avec connecteur RJ),
nécessite d’être positionné à l’écart des pièces sous tension.
REMARQUE: en cas de connexion à 3 ls ne pas considérer N reporté sur les
schémas.
[1] 1.3P, 3 phases (3 ou 4 ls) gestion d’une charge triphasée; [2] 2.3P, 3 phases (3
ou 4 ls) gestion de deux charges triphasées; [3] 3.1P, 1 phase (4 ls) gestion de trois
charges monophasées; [4] 6.1P, 1 phase (4 ls) gestion de six charges monophasées;
[5] 1P/3.1P, alimentation monophasée (2 ls). Gestion de trois charges monophasées.
[6] 1P/6.1P, alimentation monophasée (2 ls). Gestion de six charges monophasées.
[7] Sortie statique 1; [8] Sortie statique 2; [9] Port série RS485; [10] Double port série
(entrée/sortie) RS485.
Remarque sur RS485: la terminaison du port série doit être effectuée seulement sur le
dernier instrument du réseau au moyen d’un cavalier entre les bornes B+ et T.
[11] Exemple de connexion des tensions en cascade grâce aux connecteurs prévus.
MESSAGES D’ERREUR: [load 1] MISSInG tcd (TC de la charge une non connecté).
[load 2] MISSInG tcd (2ème TC de la charge une non connecté). [load 1] [load 2] MISSInG
tcd (TC des charges 1 et 2 non connectés). EEE (Condition de dépassement de plage des
entrées de mesure, tension et courant).
ESPAÑOL
Riesgo de electrocución. Desconectar la tensión antes de
quitar la tapa. Debe ser instalado sólo por personal cualicado.
Cuando no se usan los terminales 9-10-11-12 no quitar la tapa [A].
Uso previsto: medición de parámetros eléctricos, uso interno. A
ser utilizado en instalaciones con categoría de sobrevoltaje III o más baja. Al
conectar los transformadores de corriente, sólo utilizar series TCD1X o TCD2X
o TCD3X de Carlo Gavazzi.
Los cables de salida de los transformadores de intensidad (con
terminación en conector RJ) deben mantenerse alejados de partes
vivas peligrosas.
NOTA: en caso de una conexión de 3 hilos no considerar la N indicada en los esquemas.
[1] 1.3P, 3 fases (3 o 4 hilos) gestión de una carga trifásica; [2] 2.3P, 3 fases (3 o 4
hilos) gestión de dos cargas trifásicas; [3] 3.1P, 1 fase (4 hilos) gestión de tres cargas
monofásicas; [4] 6.1P, 1 fase (4 hilos) gestión de seis cargas monofásicas; [5] 1P/3.1P,
suministro de 1 fase (2 hilos). Gestión de tres cargas monofásicas. [6] 1P/6.1P, suministro
de 1 fase (2 hilos). Gestión de seis cargas monofásicas. [7] Salida estática 1; [8] Salida
estática 2; [9] Puerto serie RS485; [10] Doble puerto serie (entrada/salida) RS485.
Nota sobre RS485: la terminación del puerto serie solo se realiza en el último instrumento
de la red mediante un puente entre los terminales B+ y T.
[11] Ejemplo de cableado interno en cascada.
MENSAJES DE ERROR: [load 1] MISSInG tcd (La 1ª carga CT no está conectada).
[load 2] MISSInG tcd (La carga CT está habilitada (sistemas 2.3P o 6.1P) pero no
conectada). [load 1] [load 2] MISSInG tcd (La 1ª y la 2ª carga CT no están conectadas).
EEE (Condiciones fuera de rango de las entradas de medición (tensión e intensidad).
DANSK
Fare for elektrisk stød: Slå spændingen fra, før dækslet
fjernes. Må kun installeres af uddannet personale. Dækslet [A]
ikke fjernes, hvis terminaler 9-10-11-12 ikke anvendes. Tilsigtet
brug: Måling af elektriske parametre, til indendørs brug. Skal
anvendes i installationer med en overspænding i kat. III eller under. Ved
tilslutning af strømtransformere må man kun bruge serie TCD1X, TCD2X eller
TCD3X af Carlo Gavazzi.
Udgangskablerne på strømtransformatorerne (som ender med
RJstikket) skal holdes væk fra farlige strømførende dele.
BEMÆRK: Ved forbindelse med 3 ledninger skal der ikke tages højde for N angivet
i skemaerne.
[1] 1.3P, 3 faser (3 eller 4 ledninger) styring af en trefaset belastning; [2] 2.3P, 3 faser
(3 eller 4 ledninger) styring af to trefasede belastninger; [3] 3.1P, 1 fase (4 ledninger)
styring af tre enfasede belastninger; [4] 6.1P, 1 fase (4 ledninger) styring af seks
enfasede belastninger; [5] 1P/3.1P, 1 fase (2 ledninger) forsyning. Styring af tre enfasede
belastninger. [6] 1P/6.1P, 1 fase (2 ledninger) forsyning. Styring af seks enfasede
belastninger. [7] Statisk udgang 1; [8] Statisk udgang 2; [9] Seriel port RS485; [10]
Dobbelt seriel port (ind-/udgang) RS485.
Bemærkning om RS485: Afslutning af den serielle port udføres kun på det sidste
instrument i nettet ved hjælp af en jumper mellem terminaler B+ og T.
[11] Eksempel tilslutning af kaskadespændinger takket være de klargjorte konnektorer.
FEJLMEDDELELSER: [load 1] MISSInG tcd (TC for belastning 1, ikke tilsluttet).
[load 2] MISSInG tcd (2. TC for belastning 1, ikke tilsluttet). [load 1] [load 2] MISSInG tcd
(TC for belastning 1 og 2, ikke tilsluttet). EEE (Betingelse for over skala ved indgange for
måling, spænding og strøm).
A1= TCD Load 1 - A2= TCD Load 2
mm
16 15 16 15
Load 1
Load 2
Load 3
Load 4
Load 5
Load 6
Load 1
Load 2
Load 3
[5] 1P/3.1P [6] 1P/6.1P
□ 68x68
-0 +0.7mm
ENGLISH
Risk of electric shock. Disconnect voltage before removing
cover. To be installed by skilled people only. Do not remove cover
[A] if terminals 9-10-11-12 are not used. Intended use:
measurement of electrical parameters, indoor use. To be used in
installations with overvoltage cat. III or lower. When connecting current
transformers, use only series TCD1X or TCD2X or TCD3X by Carlo Gavazzi.
The output cables of the current transformers (which end with the RJ
connector), need to be kept away from hazardous live parts.
NOTE: in case of 3 wires connection, do not consider N in these diagrams.
[1] 3P/1.3P, 3-phase (3 or 4 wires) management of one 3-phase load;
[2] 3P/2.3P, 3-phase (3 or 4 wires) management or two 3-phase loads;
[3] 3P/3.1P, 1-phase (4 wires) management of three 1-phase load;
[4] 3P/6.1P, 1-phase (4 wires) management of six 1-phase loads. [5] 1P/3.1P, 1-phase
(2-wire) supply. Management of three 1-phase loads. [6] 1P/6.1P, 1-phase (2-wire)
supply. Management of six 1-phase loads. [7] Static output 1; [8] Static output 2; [9]
Serial Port RS485; [10] Dual (in/out) serial port RS485.
RS485 note: the termination of the serial port is carried out only on the last instrument of
the network, by means of jumper between B and T terminals.
[11] Example of Loom connection with the preset terminals.
ERROR MESSAGES: [load 1] MISSInG tcd (1st load CT not connected). [load 2]
MISSInG tcd (2nd load CT not connected). [load 1] [load 2] MISSInG tcd (1st and 2nd
loads CT not connected). EEE (Over-range condition of the measuring inputs (voltage
and current).
DIN 72x72
A
CARLO GAVAZZI
Automation Components
Carlo Gavazzi Controls SpA,
Via Safforze, 8 - 32100
Belluno (Italy)
Tel. +39 0437 355811,
Fax +39 0437 355880
EM271 72D IM TS ML 8021618 070716
EM271 “Energy Analyzer”
ENGLISH
SAFETY PRECAUTIONS
Read carefully the instruction manual. If the
instrument is used in a manner not specied by
the producer, the protection provided by the
instrument may be impaired. Maintenance:
make sure that the connections are correctly carried out
in order to avoid any malfunctioning or damage to the
instrument. To keep the instrument clean, use a slightly
damp cloth; do not use any abrasives or solvents. We
recommend to disconnect the instrument before cleaning it.
TECHNICAL SPECIFICATIONS
Rated Input. Current type Galvanic insulation carried
out by means of external TCDM current transformer
accessories. Current range. Through TCD current
sensors (up to 400A). Voltage range: Voltage 240VLN and
415VLL (MV5), 133VLN and 230VLL (MV6). Accuracy.
The data considers the whole measuring chain: EM271
base meter and TCDM current transformer (Display,
serial communication). Current range. In: 60, 100, 200,
400A (TCDM primary current); Imax: 1.2 In. Voltage
range: MV5 range Un: 160 to 240VLN (277 to 415VLL).
MV6 range Un: 57.7 to 133VLN (100 to 230VLL). Phase-
neutral voltage: in the range Un: ±(0,5% RDG +1DGT).
Phase-phase voltage: in the range Un: ±(1% RDG
+1DGT). Active power: from 0.2In to Imax, within Un
range, PF=1: ±(1.25% RDG +1DGT). Energies: kWh:
better than the combination of a class 1 of EN62053-
21 meter (EM271 base) and class 0.5 of EN60044-1
CTs (TCDxM current transformer) considering the whole
measurement chain. Reactive power: From 0.2In to
Imax, within Un range, sin(φ)=1: ±(2.25% RDG +1DGT).
Reactive energy: better than the combination of a
class 2 of EN62053-23 meter (EM271 base) and class
0.5 of EN60044-1 CTs (TCDxM current transformer)
considering the whole measurement chain. Display,
instantaneous variables readout: 3-DGT. Energies
Imported Total: 6+1DGT. Overload status: EEE indication.
LED: Red LED (Energy consumption only, 1 imp./kWh).
Green LED for Power-on (steady) and communication
status: RX-TX (in case of RS485 option only), blinking.
Voltage Overloads: Continuous 1.2 Un. For 500ms
2 Un (except power supply terminals). Voltage input
impedance: Self-power supply; power consumption:
< 4VA / 2W. Pulse output: Number of outputs: 2,
Programmable from 0.01 to 9.99 kWh per pulse. Type
Output connectable to the energy meters (kWh). Output:
V
ON
2.5 VAC/DC/ max. 70 mA; V
OFF
40 VAC/DC max.
Insulation 4kVp/2,5kVAC output to measuring inputs.
RS485: Connections 2-wire max. distance 1000m.
Protocol, MODBUS/JBUS (RTU). Driver input capability
1/5 unit load. Maximum 160 transceivers on the same bus.
Insulation: by means of opto-couplers, 4kVp/2,5kVAC
output to measuring input. Transformer ratio: CT
primary current: auto-detection of the primary current of
the TCDM current transformer. The maximum value of the
VT is limited to grant the measurement of the mx possible
power (210MW). Max VT (PT) ratio see tab.1. Reset: By
means of the front keypad: • total energies (function SUM
on): (kWh) • partial energies: single load energy (kWh)
and demanded power (Wdmd) • Max demand (Md) of
active and apparent power. Operating temperature:
Operating temperature -25 to +55°C (-13°F to +131°F)
(R.H. from 0 to 90% non-condensing @ 40°C) according
to EN62052-11. Storage temperature: -30 to +70°C
(-22°F to +158°F) (R.H. < 90% non-condensing @ 40°C) )
according to EN62052-11). Overvoltage category: Cat.
III (IEC 60664, EN60664). Dielectric strength: 4000VAC
RMS for 1 minute (all terminals to front panel). Standard
compliance: safety IEC60664, EN60664, IEC61010-
1, EN61010-1 EN62052-11, EN50470-1. Pulse output
DIN43864, IEC62053-31. Approvals: CE. Connections:
Max wire cross section 1.5 mm² (14 AWG). Min./max.
screws tightening torque: 0.2/0.25 Nm. Outputs (pulse
and RS485 port). Max wire cross section 1.5 mm² (14
AWG). Min./max. screws tightening torque: 0.2/0.25
Nm. Housing: Dimensions (WxHxD) 72 x 72 x 65 mm.
Material Noryl, self-extinguishing: UL 94 V-0. Mounting
DIN-rail or Panel mounting. Protection degree: front
IP50. Screw terminals IP20.
ITALIANO
NORME DI SICUREZZA
Leggere attentamente il manuale istruzioni.
Qualora l’apparecchio venisse adoperato in un
modo non specicato dal costruttore, la
protezione prevista dall’apparecchio potrebbe
essere compromessa. Manutenzione: assicurarsi che i
collegamenti siano eettuati correttamente al ne di
evitare qualsiasi malfunzionamento o danneggiamento
dello strumento. Per mantenere pulito lo strumento usare
un panno leggermente inumidito; non usare abrasivi o
solventi. Si consiglia di scollegare lo strumento prima di
pulirlo.
CARATTERISTICHE TECNICHE
Ingressi di misura Tipo corrente: Isolamento galvanico
ottenuto mediante i trasformatori di corrente TCDM
accessori. Portata corrente: mediante i sensori di
corrente TCD (da 60 a 400A). Portata tensione: tensione
240VLN e 415VLL (MV5), 133VLN e 230VLL (MV6).
Precisione: i dati sotto considerano la misura dell’intera
catena: contatore EM271 base e trasformatori di
corrente TCDM. Portata corrente: In: 60, 100, 200, 400A
(TCDM corrente primaria); Imax 1,2 In. Portata tensione:
Modello MV5: Un: da 160 a 240VLN (da 277 a 415VLL).
Modello MV6: Un: da 57,7 a 133VLN (da 100 a 230VLL).
Tensione fase neutro: nel campo Un: ±(0,5% RDG
+1DGT). Tensione fase fase: nel campo Un: ±(1% RDG
+1DGT). Potenza attiva: da 0,2In a Imax, del campo
Un, PF=1: ±(1,25% RDG +1DGT). Potenza reattiva:
da 0,2In a Imax, allinterno del campo Un, sin(φ)=1:
±(2,25% RDG +1DGT). Energia reattiva: migliore
della combinazione di un contatore classe 2 (secondo
EN62053-23) più un trasformatore classe 0,5 (secondo
EN60044-1) considerando l’intera catena di misura
EM271 + TCDxM. Display: Lettura variabili istantanee:
3-DGT. Energie, importate totali: 6+1DGT. Sovraccarico:
indicazione EEE. LED: LED rosso (Solo consumo di
energia), 1 imp./kWh. LED verde relativo allo stato di
“strumento acceso”, se a luce fissa, a luce lampeggiante
in caso di comunicazione RS485 presente e operativa.
Sovraccarico corrente: Continuo: 1,2 Un. Per 500ms: 2
Un (eccetto le connessioni di alimentazione). Impedenza
d’ingresso tensione: Autoalimentazione, autoconsumo:
< 4VA / 2W. Uscite impulsi: Numero di uscite: 2,
programmabili da 0,01 a 9,99 kWh per impulso. Tipo:
Uscita associabile al contatore di energia (kWh). Uscita
statica: opto-mosfet. Carico V
ON
2.5VCA/CC/ max.70mA
V
OFF
40VCA/CC max. Isolamento 4kVp/2,5kVAC fra
uscita e ingressi di misura. RS485: Connessione:
2- fili max. distanza 1000m. Protocollo: MODBUS/
JBUS (RTU). Dispositivi in rete 1/5 unit load. Massimo
160 dispositivi nella stessa rete. Isolamento tramite
optoisolatori, 4kVp/2,5kVAC tra uscite e ingressi di
misura. Rapporto di trasformazione: Corrente primaria
CT: Auto determinazione della corrente primaria dei
trasformatori di corrente TCDM. Il valore massimo del
TV è limitato per garantire la misura della massima
potenza possibile (210MW). Max rapporto TV (PT):
vedere tab. 1. Reset: Mediante la tastiera frontale: -
energie totali (funzione SUM on): kWh - energie parziali:
energia del singolo carico (kWh) e potenza dmd (Wdmd)
- Max dmd (Md) della potenza attiva e apparente.
Temperatura di funzionamento: da -25°C a +55°C
(da -13°F a 131°F) (U.R. da 0 a 90% senza condensa
@ 40°C) secondo EN62052-11. Temperatura di
immagazzinamento: da -30°C a +70°C (da -22°F a
158°F) (U.R. < 90% senza condensa @ 40°C) secondo
EN62052-11. Categoria d’installazione: Cat. III (IEC
60664, EN60664). Conformità alle norme: Sicurezza:
IEC60664, EN60664, IEC61010-1, EN61010-1 EN62052-
11, EN50470-1. Emissioni in radiofrequenza: DIN43864,
IEC62053-31. Approvazioni: CE. Connessioni:
Tensione: sezione del cavo Max 1,5mm² (14 AWG).
Min./max. coppia di serraggio viti: 0,2/0,25 Nm. Uscite
(impulsi e porta RS485). Sezione del cavo Max 1,5mm²
(14 AWG). Min./max. coppia di serraggio viti: 0,2/0,25
Nm. Custodia: Dimensioni (WxHxD): 72 x 72 x 65 mm.
Materiale: Noryl, autoestinguenza: UL 94 V-0. Montaggio:
guida DIN o Pannello. Grado di protezione: Frontale:
IP50. Connessioni: IP20.
DEUTSCH
SICHERHEITSBESTIMMUNGEN
Die Betriebsanleitung aufmerksam lesen. Sollte
das Gerät nicht gemäss der Herstellerangaben
verwendet werden, könnte der vom Gerät
vorgesehene Schutz beeinträchtigt werden.
Wartung: Beachten Sie den korrekten Anschluss aller
Anschlussterminals um eine Beschädigung des
Instrumentes zu vermeiden. Das Gerät mit einem
feuchten Tuch reinigen; keine Scheuer- oder Lösemittel
verwenden. Das Gerät vor der Reinigung ausschalten.
TECHNISCHE DATEN
Messeingang Stromtyp: Galvanische Isolierung durch
externes TCDM-Stromwandler-Zubehör. Stromspanne:
Durch TCD Stromsensoren (bis 400A). Spannungsbereich:
Spannung 240VLN und 415VLL (MV5), 133VLN und
230VLL (MV6). Genauigkeit die unten aufgeführten
Daten berücksichtigen die gesamte Messkette: EM271-
Basiszähler und TCDM-Stromwandler. Stromspanne
Eingang: 60, 100, 200, 400A (TCDM Primärstrom);
Imax: 1.2 In. Spannungsbereich: MV5 Bereich Un: 160
bis 240VLN (277 bis 415VLL). MV6 Bereich Un: 57,7 bis
133VLN (100 bis 230VLL). Phase-Nullleiter: im Bereich
Un: ±(0,5% RDG +1DGT). Phase-Phasenspannung: im
Bereich Un: ±(1% RDG +1DGT). Wirkstrom: Von 0,2In
bis lmax, innerhalb Un-Bereich, PF=1: ±(1,25% RDG
+1DGT). Energien: kWh: besser als die Kombination
Klasse 1 EN62053-21-Messgerät (EM271-Basis) und
Klasse 0.5 EN60044-1 CTs (TCDxM-Stromwandler)
unter Berücksichtigung der gesamten Messkette.
Blindleistung: Von 0,2In bis lmax, innerhalb Un-
Bereich, sin(φ)=1: ±(2,25% RDG +1DGT). Blindenergie:
besser als die Kombination Klasse 2 EN62053-23-
Messgerät (EM271-Basis) und Klasse 0.5 EN60044-1
CTs (TCDxM-Stromwandler) unter Berücksichtigung der
gesamten Messkette. Anzeige Momentanmessgrößen
3-DGT. Energien: Importiert gesamt: 6+1DGT.
Überlaststungsanzeige: EEE-Angabe. LEDs: Rote
LED (nur Energieverbrauch), 1 imp./kWh. Grüne LED
für Einschaltung (stetig) und Kommunikationsstatus:
RX-TX (nur im Falle der RS485-Option), blinkend.
Überlastspannung kontinuierlich: 1,2 Un. Für 500ms:
2 Un (außer versorgungsklemmen). Spannungs-
Eingangsimpedanz: Eigenstromversorgung;
Energieverbrauch:< 4VA / 2W. Pulsausgang Anzahl der
Ausgänge: 2, programmierbar von 0,01 bis 9,99 kWh pro
Puls. Typ: Ausgang verbindbar mit Stromzählern (kWh).
Ausgang: V
ON
2,5 VAC/DC/ max. 70 mA; V
OFF
40 VAC/DC
max. Isolierung: 4kVp/2,5kVAC Ausgang zur Messung von
Eingängen. RS485: Anschlüsse: 2-adrig. max. Abstand
1000m. Protokoll: MODBUS/JBUS (RTU). Besondere
Funktionen: 1/5 Einheitsladung. Maximal 160 Sender-
Empfänger am selben Bus. Isolierung: Durch Optokoppler,
4kVp/2,5kVAC Ausgang zu Messeingang. Wandler-
Verhältnis: CT-Primärstrom: Automatische Erkennung
des Primärstroms des TCDM-Stromwandlers. Der
Maximalwert des VT ist darauf beschränkt, die Messung
der maximal möglichen Leistung (210MW) zu gewähren.
Max. VT (PT)-Verhältnis siehe Tab.1. Zurücksetzen:
Mittels vorderem Tastenfeld: - Gesamtenergien (Funktion
SUM ein): kWh - Teilenergien: Einzellast-Energie (kWh)
und geforderte Leistung (Wdmd) - Max Anforderung (Md)
von Wirk- und Scheinleistung. Betriebstemperatur:
Betriebstemperatur -25 bis +55°C (-13°F bis +131°F)
(R.F. von 0 bis 90% nicht kondensierend @ 40°C) gemäß
EN62052-11. Lagertemperatur: -30 bis +70°C (-22°F
bis +158°F) (RH < 90% ohne Kondensation bei 40°C)
gemäß EN62052-11). Überspannungs-Kategorie: Kl. III
(IEC 60664, EN60664). Standardkonformität Sicherheit
IEC60664, EN60664, IEC61010-1, EN61010-1 EN62052-
11, EN50470-1 Pulsausgang DIN43864, IEC62053-
31. Zulassungen: CE. Anschlüsse: Spannung.
Max. Drahtquerschnitt 1,5 mm² (14 AWG). Min./Max.
Schraubenanzugsmoment: 0,2/0,25 Nm. Ausgänge
(Puls- und RS485-Port). Max. Drahtquerschnitt 1,5
mm² (14 AWG). Min./Max. Schraubenanzugsmoment:
0,2/0,25 Nm. Gehäuse Abmessungen (BxHxT): 72 x 72
x 65 mm. Gehäusematerial: Noryl, selbstlöschend: UL
94 V-0. Montage: DIN-Schienen- und Panelmontage.
Schutzgrad: Front: IP50. Schraubklemmen: IP20.
FRANÇAIS
PRÉCAUTIONS DE SECURITE
Lire attentivement le manuel de l’utilisateur. Si
l’appareil est utilisé dans des conditions
diérentes de celles spéciées par le fabricant,
le niveau de protection prévu par l’instrument
peut être compromis. Entretien: s’assurer que les
connexions sont réalisées correctement dans le but
d’éviter toutes fautes ou endommagements de l’appareil.
Pour nettoyer l’instrument, utiliser un chion humide; ne
pas utiliser d’abrasifs ou de solvants. Il faut déconnecter
le dispositif avant de procéder au nettoyage.
SPÉCIFICATIONS
Entrées nominales. Type de courant: Isolation galvanique
réalisée au moyen d’accessoires du transf. de courant
TCDM externe. Portée d’émission de courant: À travers
les capteurs de courant TCD (jusqu’à 400A). Plage de
tension: Tension 240VLN et 415VLL (MV5), 133VLN et
230VLL (MV6). Précision. Les données ci-dessous
prennent en considération l’entière chaine de mesure:
le compteur EM271 de base et le transformateur de
courant TCDM. Plage de courant: In: 60, 100, 200, 400A
(courant primaire TCDM) ; Imax: 1.2 In. Plage de tension:
plage MV5 Un: de 160 à 240VLN (de 277 à 415VLL).
Plage MV6 Un: de 57,7 à 133VLN (de 100 à 230VLL).
Tension phase-neutre: Dans la gamme Un: ±(0,5%
RDG +1DGT). Tension phase-phase: Dans la gamme
Un: ±(1% RDG +1DGT). Puissance active: De 0,2In à
Imax, dans la gamme Un, PF=1: ±(1,25% RDG +1DGT).
Energies: kWh: plus efficace que la combinaison de la
classe 1 d’un compteur EN62053-21 (EM271 de base) et
que la classe 0.5 des TC EN60044-1 (transformateur de
courant TCDM) prenant en considération l’entière chaîne
de mesurage. Puissance réactive: De 0.2In à Imax,
dans la gamme Un, sin(φ)=1: ±(2,25% RDG +1DGT).
Énergie réactive: plus efficace que la combinaison de
la classe 2 d’un compteur EN62053-23 (EM271 de base)
et que la classe 0.5 des TC EN60044-1 (transformateur
de courant TCDM) prenant en considération l’entière
chaîne de mesurage. Affichage. Lecture variables
instantanées: 3-DGT. Energies. Total Importé: 6+1DGT.
Etat de surcharge: indication EEE. LED: LED rouge
(seulement Consommation d’énergie, 1 imp./kWh. LED
verte pour Marche (fixe) et état communication: RX-
TX (seulement en cas d’option RS485), clignotante.
Surcharges de tension: Continu: 1,2 Un. Pour 500 ms:
2 Un (sauf bornes d’alimentation). Impédance d’entrée
tension: Auto-alimentation; Consommation d’Energie:
< 4VA/2W. Sortie à impulsions: Nombre de sorties:
2, Programmables de 0,01 à 9,99 kWh par impulsion.
Type: sortie raccordable aux compteurs d’énergie (kWh).
Sortie; V
ON
2,5 VCA/CC/ max. 70 mA; V
OFF
40 VCA/CC
max. Isolation: 4kVp/2,5kVCA entre sortie et entrées
de mesure. RS485. Connexions: 2 fils, distance max
1000m. Protocole MODBUS/JBUS. (RTU). Capacité
d’entrée du pilot 1/5 charge d’unité. Maximum 160
émetteurs-récepteurs sur le même bus. Isolation: au
moyen d’optocoupleurs, 4kVp/2,5kVAC entre sortie et
entrée de mesure. Rapport transformateur: Courant
primaire TC: auto-détection du courant primaire du
transformateur de courant TCDM. La valeur maximum
du transformateur de tension est limitée pour garantir
la mesure de la puissance max possible (210MW).
Rapport max transformateur de tension (TP). voir
tab.1. Réinitialisation. Au moyen du pavé numérique
à l’avant: - énergies totales (fonction SOMME activée):
(kWh). - énergies partielles: énergie charge individuelle
(kWh) et puissance demandée (Wdmd). - Demande max
(Md) de puissance active et apparente. Température
de fonctionnement: Température de fonctionnement
-25 à +55°C (-13°F à +131°F) (H.R. de 0 à 90% sans
condensation @ 40°C) selon EN62052-11. Température
de stockage: -30 à +70°C (-22°F à +158°F) (H.R. <
90% sans condensation @ 40°C) selon EN62052-11.
Catégorie surtension: Cat. III (IEC 60664, EN60664).
Conformité aux normes. Sécurité IEC60664, EN60664,
IEC61010-1, EN61010-1 EN62052-11, EN50470-
1. Sortie à impulsions DIN43864, IEC62053-31.
Approbations: CE. Connexions: Tension. Section max
fil 1,5 mm² (14 AWG). Couple de serrage vis min./max.:
0,2/0,25 Nm. Sorties (impulsion et port RS485). Section
max fil 1,5 mm² (14 AWG). Couple de serrage vis min./
max.: 0,2/0,25 Nm. Boîtier: Dimensions (LxHxP) 72 x 72
x 65 mm. Matériel: Noryl, auto-extinguible: UL 94 V-0.
Montage: Rail DIN ou Montage sur panneau. Indice de
protection: Frontal: IP50. Bornes à vis: IP20.
ESPAÑOL
NORMAS DE SEGURIDAD
Lea el manual y siga atentamente las
instrucciones. Si se utiliza el equipo de manera
distinta de como indica el Fabricante, se puede
dañar la protección de la que está provisto el
instrumento. Mantenimiento: asegurarse de que las
conexiones son correctas para evitar un mal
funcionamiento o daños en el instrumento. Para tener el
instrumento limpio, limpiar periódicamente la carcasa
con un trapo un poco humedecido. No utilizar productos
abrasivos o disolventes. Desconectar el equipo antes de
limpiarlo.
ESPECIFICACIONES
Entrada nominal. Tipo de intensidad. Aislamiento
galvánico que se lleva a cabo por medio de accesorios
del transformador de intensidad TCDM externos. Escala
de intensidad: A través de los sensores de corriente
TCD (hasta 400A). Rango de voltaje: Voltaje 240VLN
y 415VLL (MV5), 133VLN y 230VLL (MV6). Precisión:
los siguientes datos corresponden a toda la cadena
de medición: contador base EM271 y transformador
de intensidad TCDM. Escala de intensidad: In: 60,
100, 200, 400A (Corriente primaria TCDM); Imax: 1.2
In. Rango de tensión: MV5 rango Un: 160 a 240VLN
(277 a 415VLL). MV6 rango Un: 57.7 a 133VLN (100 a
230VLL). Tensión de fase neutra: En el rango Un: ±(0,5%
lec. +1díg.). Tensión fase-fase: En el rango Un: ±(1%
lec. +1díg.). Potencia activa: De 0,2In a Imax, dentro
de la escala Un, PF=1: ±(1,25% lec. +1díg.). Energías:
kWh: mejor que la combinación de una clase 1 del
contador EN62053-21 (base EM271 ) y clase 0.5 de
la norma EN60044-1 CTs (Transformador de corriente
TCDxM) teniendo en cuenta toda la cadena de medición.
Potencia reactiva: De 0,2In a Imax, dentro del rango
Un, seno(φ)=1: ±(2,25% RDG +1DGT). Energía reactiva:
mejor que la combinación de una clase 2 del contador
EN62053-23 (base EM271 ) y clase 0.5 de la norma
EN60044-1 CTs (Transformador de corriente TCDxM)
teniendo en cuenta toda la cadena de medición. Display
Lecturas variables instantáneas 3 dígitos. Energías, total
importado: 6+1díg. Estado de sobrecarga, indicación
EEE. LEDs: LED rojo (solo consumo de energía), 1 kWh
por pulso. LED verde para encendido (fijo) y estado de
la comunicación: RX-TX (parpadeando solo en el caso
de la opción RS485). Protección contra sobretensión
Continua. 1,2 Un. Durante 500ms. 2 Un (excepto los
terminales de alimentación). Impedancia de entrada
(tensión): Autoalimentación; Consumo de energía:
< 4VA/2W. Salida de pulsos Número de salidas: 2,
Programable de 0,01 a 9,99 kWh por pulso. Tipo: Salida
referida a los contadores de energía (kWh). Salida: V
ON
2,5
VCA/CC/ máx. 70 mA; V
OFF
40 VCA/CC máx. Aislamiento:
4kVp/2,5kVCA entre salida y entradas de medida. RS485
Conexiones: 2 hilos máx. distancia 1000m. Protocolo:
MODBUS/JBUS (RTU). Capacidad de entrada del
controlador: 1/5 carga unitaria. 160 transceptores como
máximo en el mismo bus. Aislamiento: por medio de
optoacopladores, 4kVp/2,5kVCA entre salida y entradas
de medida. Relación de transformación: Intensidad
del primario CT: detección automática de la intensidad
del primario del transformador de intensidad TCDM. El
valor máximo de VT se limita a garantizar la medición
de la potencia máx. posible (210MW). Relación VT (PT)
máxima véase tab.1. Puesta a cero: Por medio del
teclado en el frontal: - energías totales (función SUM
activa): (kWh) - energías parciales: energía de una carga
(kWh) y potencia demandada (Wdmd) - Máxima potencia
activa y aparente demandada (Md). Temperatura de
funcionamiento: -25 a +55°C (-13°F a +131°F) (H.R.
de 0 a 90% sin condensación @ 40°C) según la norma
EN62052-11. Temperatura de almacenamiento: -30 a
+70°C (-22°F a +158°F) (H.R. < 90% sin condensación
@ 40°C) según la norma EN62052-11. Categoría
de sobretensión: Cat. III (IEC 60664, EN60664).
Conformidad con las normas Seguridad: IEC60664,
EN60664, IEC61010-1, EN61010-1 EN62052-11,
EN50470-1. Salida de pulso: DIN43864, IEC62053-
31. Marca: CE. Conexiones: Tensión. Sección máx.
del cable: 1,5 mm² (14 AWG). Par de apriete mín./máx.
de los tornillos: 0,2/0,25 Nm. Salidas (puerto RS485 y
pulsos). Sección máx. del cable: 1,5 mm² (14 AWG). Par
de apriete mín./máx. de los tornillos: 0,2/0,25 Nm. Caja:
Dimensiones: (AnxAlxP) 72 x 72 x 65 mm. Material: Noryl,
autoextinguible: UL 94 V-0. Montaje: EN panel o a carril
DIN. Grado de protección: Frontal: IP50. Conexiones:
IP20.
DANSK
SIKKERHEDSFORSKRIFTER
Læs instruktionsmanualen omhyggeligt. Hvis
instrumentet anvendes på en måde, der ikke er
beskrevet af producenten, kan den af
instrumentet ydede beskyttelse forringes.
Vedligeholdelse: Sørg for, at forbindelserne er korrekt
udført for at undgå enhver fejlfunktion eller beskadigelse
af instrumentet. Til rengøring af instrumentet anvendes
en let fugtet klud; anvend ikke slibe- eller rengøringsmidler.
Vi anbefaler, at instrumentet frakobles før rengøring.
TEKNISKE SPECIFIKATIONER
Nominelt input Strømtype: Galvanisk isolering udført
ved hjælp af eksternt tilbehør til TCDM-strømtransformer.
Strømområde: Via TCD strømsensorer (op til 400A).
Spændingsområde: Spænding 240VLN og 415VLL (MV5),
133VLN og 230VLL (MV6). Nøjagtighed Nedenstående
data tager højde for den komplette målingskæde: EM271
basemåler og TCDM-strømtransformer. Strømområde:
In: 60, 100, 200, 400A (TCDM primær strøm). Imax: 1.2In.
Spændingsområde: MV5-område Un: 160-240VLN (277-
415VLL). MV6-område Un: 57,7-133VLN (100-230VLL).
Fase-neutral spænding: I intervallet Un: ±(0,5% RDG
+1DGT). Faseneutral spænding: I intervallet Un: ±(1%
RDG +1DGT). Aktiv effektmåling: Fra 0,2In til Imax,
inden for Un-område, PF=1: ±(1,25% RDG +1DGT).
Energi: kWh: Bedre end kombinationen af klasse 1
af EN62053-21 måler (EM271 base) og klasse 0.5 af
EN60044-1 CTs (TCDxM strømtransformer), idet der
tages højde for hele målekæden. Reaktive strøm: Fra
0.2In til Imax, inden for Un-område, sin(φ)=1: ±(2.25%
RDG +1DGT). Reaktiv energi: Bedre end kombinationen
af klasse 2 af EN62053-23 måler (EM271 base) og klasse
0.5 af EN60044-1 CTs (TCDxM strømtransformer), idet
der tages højde for hele målekæden. Display: Øjeblikkelig
aflæsning af variable: 3-DGT. Energi, Importeret totalt:
6+1DGT. Overbelastningsstatus: EEE-indikation. LED:
Rød LED (kun strømforbrug), 1 imp./kWh. Grøn LED til
tænding (lyser) og kommunikationsstatus: RX-TX (kun ved
RS485 option), blinker. Spændingsoverbelastninger
Løbende: 1,2 Un. For 500ms: 2 Un (undtagen
strømforsyningsstik). Impedans for spændingsinput:
Selvforsynet strømforsyning; Strømforbrug: < 4VA/2W.
Pulsoutput Antal output: 2 Programmerbar fra 0,01
til 9,99 kWh pr. pulse. Type: Udgang kan tilsluttes
energimålerne (kWh). Output: V
ON
2,5 VAC/DC/ max.
70 mA; V
OFF
40 VAC/DC max. Isolering: 4kVp/2,5kVAC
output til måling af input. RS485 Forbindelser: 2 ledere
maks. afstand 1000 m. Protokol: MODBUS/JBUS
(RTU). Driverinputkapacitet: 1/5 enhedsbelastning.
Maksimum 160 transceivere på den samme bus.
Isolering: Ved hjælp af optokoblinger, 4kVp/2,5kVAC
output til målingsinput. Transformerkoefficient: CT
primær strøm: Automatisk detektering af primær strøm
for TCDM-strømtransformer. Maks. værdien for VT
begrænses til målingen af max mulige effekt (210MW).
Max VT (PT) se tab.1. Nulstil: Ved hjælp af den forreste
tastatur: - totale energier (SUM-funktion af): (kWh) -
delvise energier: enkelt belastningsenergi (kWh) og
efterspurgt effekt (Wdmd) - Maks. efterspørgsel (Md) på
aktiv og synlig strøm. Driftstemperatur: -25 °C til +55
°C (-13 °F til +131°F) (relativ fugtighed fra 0 % til 90 %,
ikke-kondenserende ved 40 °C) i henhold til EN62052-11.
Opbevaringstemperatur: -30 til +70°C (-22°F til +158°F)
(relativ fugtighed < 90% ikke-kondenserende ved 40°C)
i henhold til EN62052-11. Overspændingskategori:
Kat. III (IEC 60664, EN60664). Standardoverholdelse
Sikkerhed: IEC60664, EN60664, IEC61010-1, EN61010-
1 EN62052-11, EN50470-1. Pulsoutput: DIN43864,
IEC62053-31. Godkendelser: CE. Forbindelser:
Spænding: Maks. ledningstværsnitsareal 1,5 mm² (14
AWG). Min./maks. skruemoment: 0,2/0,25 Udgange (puls
og RS485 port) Nm. Maks. ledningstværsnitsareal 1,5
mm² (14 AWG). Min./maks. skruemoment: 0,2/0,25 Nm.
Hus: Dimensioner (BxHxD): 72 x 72 x 65 mm. Materiale:
Noryl, selvslukkende: UL 94 V-0. Montering: DIN-skinne
eller panelmontering. Beskyttesesgrad: Forside: IP50.
Skrueklemmer: IP20.

Transcripción de documentos

CARLO GAVAZZI A u t o m a t i o n Carlo Gavazzi Controls SpA, Via Safforze, 8 - 32100 Belluno (Italy) Tel. +39 0437 355811, Fax +39 0437 355880 C o m p o n e n t s EM271 IM ML 8021618 070716 EM271 “Energy Analyzer” 1 4 3 2 fig.1 fig.2 A M B N C O D P= AL1 130A, AL2 130A, AL3 130A; Q= VL1 230V, VL2 89,0V, VL3 65.0V; R= VL12 390V, VL23 390V, VL31 390V.  BASIC PROGRAMMING AND RESET: to enter the complete programming mode, press the key 2 for at least 3 sec. (fig 1). Entering the programming mode, all the measurements and control functions are inhibited. During this phase the flashing of the LED has not to be considered. 01 PASS?: entering the right password (default value is 0) allows accessing the main menu. 02 CnG PASS: it allows changing the password. 03 SYS 1P/SYS 3P: 3P/1.3P: 3-phase (3- or 4-wire) supply. Management of one 3-phase load; 3P/2.3P: 3-phase (3- or 4-wire) supply. Management of two 3-phase loads; 3P/3.1P: 3-phase (4-wire) supply. Management of three 1-phase loads; 3P/6.1P: 3-phase (4-wire) supply. Management of six 1-phase loads. 1P/3.1P: 1-phase (2-wire) supply. Management of three 1-phase loads. 1P/6.1P: 1-phase (2-wire) supply. Management of six 1-phase loads. 04 SUM: sum function of TCD. 05 EC: easy connection function. 06 P.int ti: integration time for “dmd” power calculation. 07 Ut rAt.: VT ratio. 08 PuL 1: it selects the pulse weight (number of kWh per pulse, from 0.01 to 9.99) Load 1. 09 PuL 2: it selects the pulse weight (number of kWh per pulse, from 0.01 to 9.99) Load 2. 10 t.on: T ON time (Pulse duration 40msec or 100msec). 11 AddrESS: serial address: from 1 to 247. 12 bAud: Modbus baud rate. 13 PAritY: Modbus parity. 14 EnEPA.rE: reset of the Load 1 and Load 2 energy values. 15 EnEto.rE: reset of the total energy values. 16 End: it allows exiting the programming mode. ITALIANO E P F Q G R H I L RESET! a 1.2.3... b ...3.2.1 c OK fig.3 ENGLISH 1 press the key, to scroll the menus or increase/decrease the values to be set up. 2 you can enter the submenus and change the value change mode from positive to negative or vice versa according to the logic indicated in fig. 3. 3 the LED flashes proportionally to the active energy consumption. 4 turn the trimmer clockwise up to its run end to block programming mode. A= Year of production plus firmware release; B= kWh per pulse (relevant to the front led); C= type of system (6.1P); D= VT rating value; E and F= primary value of TCD; G and H= Digital pulse output 1 and 2 (kWh per pulse); I= serial communication address; L= reset the max demand values; M= kWh 765432.1 kW 10.1; N= system kW dmd 221; O= maximum demand 261 kW; 1 premere il tasto per scorrere i menu o incrementare o decrementare i valori da impostare. 2 è possibile entrare nei sub menù e modificare i valori cambiando da positivo a negativo come esemplificato in fig. 3. 3 il LED lampeggia proporzionalmente all’energia attiva importata consumata. 4 per bloccare l’accesso alla programmazione, ruotare il trimmer in senso orario fino a fine corsa. A= anno di produzione e versione del firmware; B= kWh per impulso (relativo al LED frontale); C= tipo di sistema (6.1P); D= Rapporto di trasformazione TV; E e F= valore del primario del TCD; G e H= Uscita digitale 1 e 2 (kWh per impulso). I= indirizzo di comunicazione seriale; L= reset dei valori demand massimi; M= kWh 765432.1 kW 10.1; N= 221 kW dmd di sistema; O= valore demand massimo 261 kW; P= AL1 130A, AL2 130A, AL3 130A; Q= VL1 230V, VL2 89,0V, VL3 65.0V; R= VL12 390V, VL23 390V, VL31 390V.  PROGRAMMAZIONE BASE E RESET: per accedere alla programmazione completa premere il tasto 2 e mantenerlo premuto per almeno 3 secondi (fig. 1). Entrati nel modo di programmazione tutte le misure e funzioni di controllo sono inibiti. In questa fase il lampeggio del DEL non deve essere considerato. 01 PASS?: inserendo la password corretta (di default è 0) si accede al menù principale. 02 CnG PASS: permette di modificare la password. 03 SYS 1P/SYS 3P: 3P/1.3P: alimentazione trifase (3 o 4 fili). Gestione di un carico trifase; 3P/2.3P: alimentazione trifase (3 o 4 fili). Gestione di due carichi trifase; 3P/3.1P: alimentazione trifase (4 fili). Gestione di tre carichi monofase; 3P/6.1P: alimentazione trifase (4 fili). Gestione di sei carichi monofase; 1P/3.1P: alimentazione monofase (2 fili). Gestione di tre carichi monofase; 1P/6.1P: alimentazione monofase (2 fili). Gestione di sei carichi monofase. 04 SUM: funzione somma dei TCD. 05 EC: funzione easy connection. 06 P.int ti: tempo di integrazione per il calcolo della potenza “dmd”. 07 Ut rAt.: rapporto TV. 08 PuL 1: seleziona il peso dell’impulso del carico 1 (numero di kWh per impulsi, da 0.01 a 9.99). 09 PuL 2: seleziona il peso dell’impulso del carico 1 (numero di kWh per impulsi, da 0.01 a 9.99). 10 t.on: T ON time (durata dell’impulso 40msec o 100msec). 11 AddrESS: indirizzo porta seriale: da 1 a 247. 12 bAud: baud rate Modbus. 13 PAritY: parità Modbas. 14 EnEPA.rE: reset dei valori di energia del carico 1 e 2. 15 EnEto.rE: reset dei valori di energia totali. 16 End: permette di uscire dal menu di programmazione. DEUTSCH 1 Die Taste drücken, um das Menü durchzublättern oder die einzugebenden Werte zu erhöhen bzw. zu verringern. 2 Es besteht die Möglichkeit, die Submenüs aufzurufen und die Werte von positiv auf negativ zu ändern, wie als Beispiel in Abb. 3 dargestellt. 3 Die LED blinkt proportional zur verbrauchten aktiven Energie. 4 Zum Sperren des Zugriffs auf die Programmierung, den Trimmer bis zum Anschlag im Uhrzeitersinn drehen. A= Herstellungsjahr plus Firmware-Release; B= kWh pro Impuls (relevant für die Front-LED); C= System-Typ (6.1P); D= Wandlungsverhältnis TV; E und F= Primärwert von TCD; G und H= digitaler Pulsausgang 1 und 2 (kWh pro Impuls); I= Serielle Kommunikationsadresse; L= Reset der maximalen Demand-Werte; M= kWh 765432.1 kW 10.1; N= 221 kW dmd des Systems; O= Maximaler Demand-Wert 261 kW; P= AL1 130A, AL2 130A, AL3 130A; Q= VL1 230V, VL2 89,0V, VL3 65.0V; R= VL12 390V, VL23 390V, VL31 390V.  BASIS-PROGRAMMIERUNG UND RESET: Zum Aufruf der kompletten Programmierung die Taste 2 betätigen und mindestens 3 Sekunden gedrückt halten (Abb.1). Nach Aufruf der Programmierung sind alle Messungen und Kontrollfunktionen gesperrt. In dieser Phase muss das Blinken von DEL nicht berücksichtigt werden. 01 PASS?: Bei Eingabe des korrekten Password (Default-Wert ist 0) wird das Hauptmenü aufgerufen. 02 CnG PASS: Gestattet die Änderung des Passwords. 03 SYS 1P/SYS 3P: 3P/1.3P: Drehstromversorgung (3 oder 4 Litzen). Steuerung einer Drehstromlast; 3P/2.3P: Drehstromversorgung (3 oder 4 Litzen). Steuerung von zwei Drehstromlasten; 3P/3.1P: Drehstromversorgung (4 Litzen). Steuerung von drei Drehstromlasten; 3P/6.1P: Drehstromversorgung (4 Litzen). Steuerung von sechs Einphasenlasten; 1P/3.1P: Einphasenstromversorgung (2 Litzen). Steuerung von drei Einphasenlasten; 1P/6.1P: Einphasenstromversorgung (2 Litzen). Steuerung von sechs Einphasenlasten. 04 SUM: Summen-Funktion der TCD. 05 EC: Funktion Easy Connection. 06 P.int ti: Integration der Zeit zur Berechnung der Leistung “dmd”. 07 Ut rAt.: Verhältnis TV. 08 PuL 1: Selektiert das Gewichts des Impulses der Last 1 (Anzahl kWh für Impulse, von 0.01 bis 9.99). 09 PuL 2: Selektiert das Gewichts des Impulses der Last 1 (Anzahl kWh für Impulse, von 0.01 bis 9.99). 10 t.on: Zeit T ON (Impulsdauer 40 msec oder 100 msec). 11 AddrESS: Adresse des seriellen Ports: zwischen 1 und 247. 12 bAud: Modbus- Baudrate. 13 PAritY: Parität Modbus. 14 EnEPA.rE: Reset Energie der Last 1- und Last 2-Energiewerte. 15 EnEto.rE: Reset Gesamt-Energiewerte. 16 End: Gestattet das Verlassen des Programmierungs-Menüs. FRANÇAIS 1 presser la touche pour défiler les menus ou augmenter ou diminuer les valeurs à régler. 2 il est possible d’entrer dans les sous-menus et modifier les valeurs en changeant de positif à négatif comme illustré à la fig. 3. 3 la LED clignote proportionnellement à l’énergie active consommée. 4 pour bloquer l’accès à la programmation, tourner le trimmer dans le sens des aiguilles d’une montre jusqu’en butée. A= année de production plus version firmware; B= kWh par impulsion (led frontale); C= type de système (6.1P); E et F= valeur primaire de TCD; G et H= Sortie d’impulsion logique 1 et 2 (kWh par impulsion); I= adresse de communication série; L= réinitialisation des valeurs «demand» maximales; M= kWh 765432.1 kW 10.1; N= 221 kW dmd de système; O= valeur «demand» maximale 261 kW; P= AL1 130A, AL2 130A, AL3 130A; Q= VL1 230V, VL2 89,0V, VL3 65.0V; R= VL12 390V, VL23 390V, VL31 390V.  PROGRAMMATION DE BASE ET REINITIALISATION: pour accéder à la programmation complète presser la touche 2 et la maintenir enfoncée pendant au moins 3 secondes (fig. 1). Une fois dans le mode de programmation toutes les mesures et fonctions de contrôle sont bloquées. Durant cette phase le clignotement de la LED ne doit pas être pris en considération. 01 PASS?: en saisissant le mot de passe correct (par défaut 0) on accède au menu principal. 02 CnG PASS: permet de modifier le mot de passe. 03 SYS 1P/SYS 3P: 3P/1.3P: alimentation triphasée (3 ou 4 fils). Gestion d’une charge triphasée; 3P/2.3P: alimentation triphasée (3 ou 4 fils). Gestion de deux charges triphasées; 3P/3.1P: alimentation triphasée (4 fils). Gestion de trois charges monophasées; 3P/6.1P: alimentation triphasée (4 fils). Gestion de six charges monophasées. 1P/3.1P: alimentation monophasée (2 fils). Gestion de trois charges monophasées. 1P/6.1P: alimentation monophasée (2 fils). Gestion de six charges monophasées. 04 SUM: fonction somme des TCD. 05 EC: fonction easy connection. 06 P.int ti: intégration du temps pour le calcul de la puissance “dmd”. 07 Ut rAt.: rapport TT. 08 PuL 1: sélectionne le poids de l’impulsion de la charge 1 (nombre de kWh par impulsion, de 0.01 à 9.99). 09 PuL 2: sélectionne le poids de l’impulsion de la charge 1 (nombre de kWh par impulsion, de 0.01 à 9.99). 11 t.on: T ON time (Durée d’impulsion 40msec ou 100msec). 12 AddrESS: adresse port série: de 1 à 247. 13 bAud: débit en bauds Modbus. 15 PAritY: parité Modbas. 14 EnEPA.rE: réinitialisation de valeurs d’énergie de la charge 1 et 2. 15 EnEto.rE: réinitialisation des valeurs d’énergie totales. 16 End: permet de quitter le menu de programmation. ESPAÑOL 1 pulsar la tecla para avanzar por los menús y para aumentar o reducir los valores a configurar. 2 es posible entrar en los submenús y modificar los valores cambiando de positivo a negativo o viceversa, como se indica en la fig. 3. 3 el LED parpadea proporcionalmente a la energía activa consumida. 4 para bloquear el acceso a la programación, girar el potenciómetro en sentido horario hasta el tope. A= año de producción más la versión de firmware; B= kWh por pulso (correspondiente al LED delantero); C= tipo de sistema (6.1P); D= orden de las fases en los TCD; E y F= valor primario de TCD; G y H= Salida 1 y 2 de pulso digital (kWh por pulso); I= dirección de comunicación en serie; L= puesta a cero de los valores máximos de demanda; M= kWh 765432.1 kW 10.1; N= 221 kW dmd de sistema; O= valor máximo de demanda 261 kW; P= AL1 130A, AL2 130A, AL3 130A; Q= VL1 230V, VL2 89,0V, VL3 65.0V; R= VL12 390V, VL23 390V, VL31 390V.  PROGRAMACIÓN BÁSICA Y PUESTA A CERO: para acceder a la programación completa, pulsar la tecla 2 y mantenerla pulsada durante al menos 3 segundos (fig. 1). Una vez dentro del modo de programación, se inhiben todas las medidas y funciones de control. En esta fase no debe tenerse en cuenta el parpadeo del LED. 01 PASS?: introduciendo la contraseña correcta (por defecto es 0) se accede al menú principal. 02 CnG PASS: permite modificar la contraseña. 03 SYS 1P/SYS 3P: 3P/1.3P: suministro de 3 fases (3 o 4 hilos). Administración de una carga trifásicas; 3P/2.3P: suministro de 3 fases (3 o 4 hilos) Administración de dos cargas trifásicas; 3P/3.1P: suministro de 3 fases (4 hilos) Administración de tres cargas monofásicas; 3P/6.1P: suministro de 3 fases (4 hilos) Gestión de seis cargas monofásicas. 1P/3.1P: suministro de 1 fase (2 hilos) Gestión de tres cargas monofásicas. 1P/6.1P: suministro de 1 fase (2 hilos) Gestión de seis cargas monofásicas. 04 SUM: función suma de los TCD. 05 EC: función conexión fácil. 06 P.int ti: integración del tiempo para calcular la potencia “dmd”. 07 Ut rAt.: relación de VT. 08 PuL 1: selecciona el valor del pulso (número de kWh por pulsos, de 0.01 a 9.99). 09 PuL 2: selecciona el valor del pulso (número de kWh por pulsos, de 0.01 a 9.99). 10 t.on: tiempo ON (Duración del pulso 40msec o 100msec). 11 AddrESS: dirección puerto serie: de 1 a 247. 12 bAud: velocidad en baudios, Modbus. 13 PAritY: paridad Modbas. 14 EnEPA.rE: puesta a cero de los valores de energía de carga 1 y 2. 15 EnEto.rE: puesta a cero de los valores de energía totales. 16 End: permite salir del menú de programación. DANSK 1 Tryk på tasten for at rulle ned igennem menuerne eller forøge og formindske de værdier, der skal indstilles. 2 Man kan gå ind i undermenuerne og ændre værdierne ved at skifte fra positiv til negativ som vist i fig. 3. 3 Lysdioden lyser i forhold til den forbrugte aktive energi. 4 Drej på trimmeren i urets retning, indtil den ikke kan komme længere, for at spærre for adgang til programmering. A= Produktionsår og udgivelse af firmware; B= kWh per puls (relevant for forreste LED); C= systemets type (6.1P); D= omdannelsesforhold for TV; E og F= primær værdi af TCD; G og H= Digital pulsudgang 1 og 2 (kWh per puls); I= seriekommunikationsadresse; L= reset af værdier med maksimale krav; M= kWh 765432.1 kW 10.1; N= 221 kW dmd af systemet; O= værdi med maksimalt krav 261 kW; P= AL1 130A, AL2 130A, AL3 130A; Q= VL1 230V, VL2 89,0V, VL3 65.0V; R= VL12 390V, VL23 390V, VL31 390V.  GRUNDLÆGGENDE PROGRAMMERING OG RESET: For at få adgang til den fulde programmering skal man trykke på tast 2 og holde den inde i mindst 3 sekunder (fig. 1). Når man er i programmeringsmode, er alle målinger og kontrolfunktioner blokerede. I denne fase lyser LED’en, men det skal man ikke tage hensyn til. 01. PASS?: Ved at indsætte den korrekte adgangskode (standard er 0) får man adgang til hovedmenuen. 02. CnG PASS: Tillader en ændring af adgangskoden. 03. SYS 1P/SYS 3P: 3P/1.3P: 3 faser (3 eller 4 ledninger) forsyning. Styring af en trefaset belastning; 3P/2.3P: 3 faser (3 eller 4 ledninger) forsyning. Styring af to trefasede belastninger; 3P/3.1P: 3 faser (4 ledninger) forsyning. Styring af tre enfasede belastninger; 3P/6.1P: 3 faser (4 ledninger) forsyning. Styring af seks enfasede belastninger. 1P/3.1P: 1 fase (2 ledninger) forsyning. Styring af tre enfasede belastninger. 1P/6.1P: 1 fase (2 ledninger) forsyning. Styring af seks enfasede belastninger. 04. SUM: Funktionen Sum af TCD. 05. EC: Funktionen Easy connection. 06. P.int ti: Integrering af tid for beregning af effekten “dmd”. 07. Ut rAt.: TV-forhold. 08. PuL 1: Vælger vægten af impulsen for belastning 1 (antal kWh for impulser, fra 0,01 til 9,99). 09. PuL 2: Vælger vægten af impulsen for belastning 1 (antal kWh for impulser, fra 0,01 til 9,99). 10. t.on: T ON time (Pulsvarighed 40msec eller 100msec). 11. AddrESS: Adressen på den serielle port: fra 1-247. 12. bAud: Baudhastighed på Modbus. 13. PAritY: Modbus-paritet. 14. EnEPA.rE: Reset af energiværdier for belastning 1 og 2. 15. EnEto. rE: Reset af totale energiværdier. 16. End: Tillader, at man går ud af programmeringsmenuen. tab. 1 MAX VT ratio according to the current sensor range - Rapporto VT MAX secondo il range del sensore di corrente - Max VT Verhältnis gemäß Stromsensorbereich - Rapport max TT selon la plage du capteur de courant - Relación VT máxima en función del rango del sensor de corriente - Max VT koefficient i henhold til strømsensorområde TCDA1 TCDA2 60 60 100 200 400 MV5 MV6 MV5 MV6 MV5 MV6 MV5 MV6 999 999 999 999 764 999 432 744 100 999 999 994 999 662 999 397 684 200 764 999 662 999 497 855 331 570 400 432 744 397 684 331 570 248 427 NO TCD 999 999 999 999 999 999 999 999 In measurement mode Al modo misura Zum Messmodus Au mode mesure En el modo de medición I måletilstand FRANÇAIS Risque de choc électrique. Débrancher la tension avant d’enlever le cache. L’installation doit être effectuée uniquement par des personnes qualifiées. Ne pas enlever le cache [A] si les bornes 9-10-11-12 ne sont pas utilisées. Usage prévu: mesure des paramètres électriques, usage en intérieur. À utiliser sur des installations avec une surtension de cat. III ou inférieure. Lors de la connexion de transformateurs de courant, utiliser uniquement les séries TCD1X ou TCD2X ou TCD3X de Carlo Gavazzi. Le câble de sortie des transformateurs de courant (avec connecteur RJ), nécessite d’être positionné à l’écart des pièces sous tension. mm A DIN 72x72 REMARQUE: en cas de connexion à 3 fils ne pas considérer N reporté sur les schémas. [1] 1.3P, 3 phases (3 ou 4 fils) gestion d’une charge triphasée; [2] 2.3P, 3 phases (3 ou 4 fils) gestion de deux charges triphasées; [3] 3.1P, 1 phase (4 fils) gestion de trois charges monophasées; [4] 6.1P, 1 phase (4 fils) gestion de six charges monophasées; [5] 1P/3.1P, alimentation monophasée (2 fils). Gestion de trois charges monophasées. [6] 1P/6.1P, alimentation monophasée (2 fils). Gestion de six charges monophasées. [7] Sortie statique 1; [8] Sortie statique 2; [9] Port série RS485; [10] Double port série (entrée/sortie) RS485. Remarque sur RS485: la terminaison du port série doit être effectuée seulement sur le dernier instrument du réseau au moyen d’un cavalier entre les bornes B+ et T. [11] Exemple de connexion des tensions en cascade grâce aux connecteurs prévus. MESSAGES D’ERREUR: [load 1] MISSInG tcd (TC de la charge une non connecté). [load 2] MISSInG tcd (2ème TC de la charge une non connecté). [load 1] [load 2] MISSInG tcd (TC des charges 1 et 2 non connectés). EEE (Condition de dépassement de plage des entrées de mesure, tension et courant). 14 15 16 13 14 15 16 13 Load 1 Load 2 Load 3 Load 1 [1] 3P/1.3P [3] 3P/3.1P 14 15 16 13 14 15 16 13 Load 1 Load 2 Load 3 Load 1 Load 4 Load 5 Load 6 Load 2 [2] 3P/2.3P [4] 3P/6.1P ESPAÑOL □ 68x68 -0 +0.7mm ITALIANO Rischio di folgorazione. Scollegare la tensione prima di rimuovere la protezione. L’installazione va eseguita solo da personale competente. Non rimuovere la protezione [A] se i terminali 9-10-11-12 sono utilizzati. Destinazione d’uso: misura dei parametri elettrici, per uso interno. Da utilizzare in installazioni con categoria di sovratensione III o inferiore. Collegare solo trasformatori di corrente della serie TCD1X, TCD2X o TCD3X di Carlo Gavazzi. I cavi di uscita dei trasformatori di corrente (terminalizzati con connettore RJ) devono essere tenuti lontani da punti a tensione pericolosa. A1= TCD Load 1 - A2= TCD Load 2 NOTA: in caso di una connessione 3 fili non considerare N riportato negli schemi. [1] 3P/1.3P, 3 fasi (3 o 4 fili) gestione di un carico trifase; [2] 3P/2.3P, 3 fasi (3 o 4 fili) gestione di due carichi trifase; [3] 3P/3.1P, 1 fase (2 fili) gestione di tre carichi monofase; [4] 3P/6.1P, 1 fase (2 fili). Gestione di sei carichi monofase; [5] 1P/3.1P, alimentazione monofase (4 fili). Gestione di tre carichi monofase; [6] 1P/6.1P, alimentazione monofase (4 fili). Gestione di sei carichi monofase; [7] Uscita statica 1; [8] Uscita statica 2; [9] Porta seriale RS485; [10] Doppia porta seriale (entra/esci) RS485. Nota su RS485: la terminazione della porta seriale va eseguita solo sull’ultimo strumento della rete mediante un ponticello tra i terminali B+ e T. [11] Esempio di collegamento delle tensioni in cascata grazie ai connettori predisposti. MESSAGGI DI ERRORE: [load 1] MISSInG tcd (TC del carico uno non connesso). [load 2] MISSInG tcd (2nd TC del carico uno non connesso). [load 1] [load 2] MISSInG tcd (TC dei carici 1 e 2 non connessi). EEE (Condizione di sovrascala degli ingressi di misura, tensione e corrente). DEUTSCH ENGLISH Risk of electric shock. Disconnect voltage before removing cover. To be installed by skilled people only. Do not remove cover [A] if terminals 9-10-11-12 are not used. Intended use: measurement of electrical parameters, indoor use. To be used in installations with overvoltage cat. III or lower. When connecting current transformers, use only series TCD1X or TCD2X or TCD3X by Carlo Gavazzi. The output cables of the current transformers (which end with the RJ connector), need to be kept away from hazardous live parts. NOTE: in case of 3 wires connection, do not consider N in these diagrams. [1] 3P/1.3P, 3-phase (3 or 4 wires) management of one 3-phase load; [2] 3P/2.3P, 3-phase (3 or 4 wires) management or two 3-phase loads; [3] 3P/3.1P, 1-phase (4 wires) management of three 1-phase load; [4] 3P/6.1P, 1-phase (4 wires) management of six 1-phase loads. [5] 1P/3.1P, 1-phase (2-wire) supply. Management of three 1-phase loads. [6] 1P/6.1P, 1-phase (2-wire) supply. Management of six 1-phase loads. [7] Static output 1; [8] Static output 2; [9] Serial Port RS485; [10] Dual (in/out) serial port RS485. RS485 note: the termination of the serial port is carried out only on the last instrument of the network, by means of jumper between B and T terminals. [11] Example of Loom connection with the preset terminals. ERROR MESSAGES: [load 1] MISSInG tcd (1st load CT not connected). [load 2] MISSInG tcd (2nd load CT not connected). [load 1] [load 2] MISSInG tcd (1st and 2nd loads CT not connected). EEE (Over-range condition of the measuring inputs (voltage and current). Stromschlaggefahr. Vor Entfernen der Abdeckung die Spannung unterbrechen. Installation nur durch einen Fachmann. Die Abdeckung [A] nicht entfernen, wenn die Anschlüsse 9-10-11-12 nicht verwendet werden. Verwendung: Messung von elektrischen Parametern, in Innenbereichen. Verwendung in Installationen mit Überspannungs-Kategorie III oder niedriger. Bei Anschluss von Stromwandlern, nur die Serien TCD1X oder TCD2X oder TCD3X von Carlo Gavazzi verwenden. Die Ausgangsleitungen der Stromwandler (welche am Ende mit einem RJStecker ausgeführt sind), müssen von gefährlichen spannungsführenden Teilen ferngehalten werden. HINWEIS: bei 3-drahtigem Anschluss, den in den Plänen mit N bezeichneten Leiter nicht berücksichtigen. [1] 1.3P, 3 Phasen (3 oder 4 Litzen) für eine Drehstromlast; [2] 2.3P, 3 Phasen (3 oder 4 Litzen) für zwei Drehstromlasten; [3] 3.1P, 1 Phase (4 Litzen) für drei Einphasenlasten; [4] 6.1P, 1 Phase (4 Litzen) für sechs Einphasenlasten; [5] 1P/3.1P, Einphasenstromversorgung (2 Litzen). Steuerung von drei Einphasenlasten. [6] 1P/6.1P, Einphasenstromversorgung (2 Litzen). Steuerung von sechs Einphasenlasten. [7] Statischer Ausgang 1; [8] Statischer Ausgang 2; [9] Serieller Port RS485; [10] Doppelter serieller Port (ein/aus) RS485. Hinweis zu RS485: der Anschluss des seriellen Ports ist nach dem letzen Instrument des Netzes anhand einer Brücke zwischen B+ und T vorzunehmen.[11] Beispiel für Kaskaden-Anschluss der Spannungen anhand entsprechend vorgerüsteter Stecker. FEHLERMELDUNGEN: [load 1] MISSInG tcd (TC der Last 1 nicht angeschlossen). [load 2] MISSInG tcd (TC der Last 2 nicht angeschlossen). [load 1] [load 2] MISSInG tcd (TC der Lasten 1 und 2 nicht angeschlossen). [load 2] WrOnG tcd (TC der Last 2 freigegeben, System 2.3P oder 6.1P, jedoch mit abweichendem Primärstrom im Vergleich zum ersten TC). EEE (Messeingänge, Spannung und Strom außer Skala). 16 15 Riesgo de electrocución. Desconectar la tensión antes de quitar la tapa. Debe ser instalado sólo por personal cualificado. Cuando no se usan los terminales 9-10-11-12 no quitar la tapa [A]. Uso previsto: medición de parámetros eléctricos, uso interno. A ser utilizado en instalaciones con categoría de sobrevoltaje III o más baja. Al conectar los transformadores de corriente, sólo utilizar series TCD1X o TCD2X o TCD3X de Carlo Gavazzi. 16 15 Load 1 Load 2 Load 3 Load 4 Load 5 Load 6 Load 1 Load 2 Load 3 Los cables de salida de los transformadores de intensidad (con terminación en conector RJ) deben mantenerse alejados de partes vivas peligrosas. NOTA: en caso de una conexión de 3 hilos no considerar la N indicada en los esquemas. [1] 1.3P, 3 fases (3 o 4 hilos) gestión de una carga trifásica; [2] 2.3P, 3 fases (3 o 4 hilos) gestión de dos cargas trifásicas; [3] 3.1P, 1 fase (4 hilos) gestión de tres cargas monofásicas; [4] 6.1P, 1 fase (4 hilos) gestión de seis cargas monofásicas; [5] 1P/3.1P, suministro de 1 fase (2 hilos). Gestión de tres cargas monofásicas. [6] 1P/6.1P, suministro de 1 fase (2 hilos). Gestión de seis cargas monofásicas. [7] Salida estática 1; [8] Salida estática 2; [9] Puerto serie RS485; [10] Doble puerto serie (entrada/salida) RS485. Nota sobre RS485: la terminación del puerto serie solo se realiza en el último instrumento de la red mediante un puente entre los terminales B+ y T. [11] Ejemplo de cableado interno en cascada. MENSAJES DE ERROR: [load 1] MISSInG tcd (La 1ª carga CT no está conectada). [load 2] MISSInG tcd (La 2ª carga CT está habilitada (sistemas 2.3P o 6.1P) pero no conectada). [load 1] [load 2] MISSInG tcd (La 1ª y la 2ª carga CT no están conectadas). EEE (Condiciones fuera de rango de las entradas de medición (tensión e intensidad). [5] 1P/3.1P 1 3 2 [7] DANSK Fare for elektrisk stød: Slå spændingen fra, før dækslet fjernes. Må kun installeres af uddannet personale. Dækslet [A] må ikke fjernes, hvis terminaler 9-10-11-12 ikke anvendes. Tilsigtet brug: Måling af elektriske parametre, til indendørs brug. Skal anvendes i installationer med en overspænding i kat. III eller under. Ved tilslutning af strømtransformere må man kun bruge serie TCD1X, TCD2X eller TCD3X af Carlo Gavazzi. Udgangskablerne på strømtransformatorerne (som ender med RJstikket) skal holdes væk fra farlige strømførende dele. BEMÆRK: Ved forbindelse med 3 ledninger skal der ikke tages højde for N angivet i skemaerne. [1] 1.3P, 3 faser (3 eller 4 ledninger) styring af en trefaset belastning; [2] 2.3P, 3 faser (3 eller 4 ledninger) styring af to trefasede belastninger; [3] 3.1P, 1 fase (4 ledninger) styring af tre enfasede belastninger; [4] 6.1P, 1 fase (4 ledninger) styring af seks enfasede belastninger; [5] 1P/3.1P, 1 fase (2 ledninger) forsyning. Styring af tre enfasede belastninger. [6] 1P/6.1P, 1 fase (2 ledninger) forsyning. Styring af seks enfasede belastninger. [7] Statisk udgang 1; [8] Statisk udgang 2; [9] Seriel port RS485; [10] Dobbelt seriel port (ind-/udgang) RS485. Bemærkning om RS485: Afslutning af den serielle port udføres kun på det sidste instrument i nettet ved hjælp af en jumper mellem terminaler B+ og T. [11] Eksempel på tilslutning af kaskadespændinger takket være de klargjorte konnektorer. FEJLMEDDELELSER: [load 1] MISSInG tcd (TC for belastning 1, ikke tilsluttet). [load 2] MISSInG tcd (2. TC for belastning 1, ikke tilsluttet). [load 1] [load 2] MISSInG tcd (TC for belastning 1 og 2, ikke tilsluttet). EEE (Betingelse for over skala ved indgange for måling, spænding og strøm). [6] 1P/6.1P [9] 4 [8] 8 8 8 8 8 6 6 6 2 6 2 6 2 5 5 5 1 5 1 5 1 7 7 7 3 7 3 7 3 [10] 13 14 15 16 9 10 11 12 13 14 15 16 [11] 9 10 11 12 CARLO GAVAZZI A u t o m a t i o n C o m p o n e n t s EM271 72D IM TS ML 8021618 070716 EM271 “Energy Analyzer” Carlo Gavazzi Controls SpA, Via Safforze, 8 - 32100 Belluno (Italy) Tel. +39 0437 355811, Fax +39 0437 355880 compliance: safety IEC60664, EN60664, IEC610101, EN61010-1 EN62052-11, EN50470-1. Pulse output DIN43864, IEC62053-31. Approvals: CE. Connections: Max wire cross section 1.5 mm² (14 AWG). Min./max. screws tightening torque: 0.2/0.25 Nm. Outputs (pulse and RS485 port). Max wire cross section 1.5 mm² (14 AWG). Min./max. screws tightening torque: 0.2/0.25 Nm. Housing: Dimensions (WxHxD) 72 x 72 x 65 mm. Material Noryl, self-extinguishing: UL 94 V-0. Mounting DIN-rail or Panel mounting. Protection degree: front IP50. Screw terminals IP20. ENGLISH  SAFETY PRECAUTIONS Read carefully the instruction manual. If the instrument is used in a manner not specified by the producer, the protection provided by the instrument may be impaired. Maintenance: make sure that the connections are correctly carried out in order to avoid any malfunctioning or damage to the ITALIANO instrument. To keep the instrument clean, use a slightly  NORME DI SICUREZZA damp cloth; do not use any abrasives or solvents. We Leggere attentamente il manuale istruzioni. recommend to disconnect the instrument before cleaning it. Qualora l’apparecchio venisse adoperato in un modo non specificato dal costruttore, la  TECHNICAL SPECIFICATIONS protezione prevista dall’apparecchio potrebbe Rated Input. Current type Galvanic insulation carried essere compromessa. Manutenzione: assicurarsi che i out by means of external TCDM current transformer collegamenti siano effettuati correttamente al fine di accessories. Current range. Through TCD current evitare qualsiasi malfunzionamento o danneggiamento sensors (up to 400A). Voltage range: Voltage 240VLN and dello strumento. Per mantenere pulito lo strumento usare 415VLL (MV5), 133VLN and 230VLL (MV6). Accuracy. un panno leggermente inumidito; non usare abrasivi o The data considers the whole measuring chain: EM271 solventi. Si consiglia di scollegare lo strumento prima di base meter and TCDM current transformer (Display, pulirlo. serial communication). Current range. In: 60, 100, 200, 400A (TCDM primary current); Imax: 1.2 In. Voltage  CARATTERISTICHE TECNICHE range: MV5 range Un: 160 to 240VLN (277 to 415VLL). Ingressi di misura Tipo corrente: Isolamento galvanico MV6 range Un: 57.7 to 133VLN (100 to 230VLL). Phaseottenuto mediante i trasformatori di corrente TCDM neutral voltage: in the range Un: ±(0,5% RDG +1DGT). accessori. Portata corrente: mediante i sensori di Phase-phase voltage: in the range Un: ±(1% RDG corrente TCD (da 60 a 400A). Portata tensione: tensione +1DGT). Active power: from 0.2In to Imax, within Un 240VLN e 415VLL (MV5), 133VLN e 230VLL (MV6). range, PF=1: ±(1.25% RDG +1DGT). Energies: kWh: Precisione: i dati sotto considerano la misura dell’intera better than the combination of a class 1 of EN62053catena: contatore EM271 base e trasformatori di 21 meter (EM271 base) and class 0.5 of EN60044-1 corrente TCDM. Portata corrente: In: 60, 100, 200, 400A CTs (TCDxM current transformer) considering the whole (TCDM corrente primaria); Imax 1,2 In. Portata tensione: measurement chain. Reactive power: From 0.2In to Modello MV5: Un: da 160 a 240VLN (da 277 a 415VLL). Imax, within Un range, sin(φ)=1: ±(2.25% RDG +1DGT). Modello MV6: Un: da 57,7 a 133VLN (da 100 a 230VLL). Reactive energy: better than the combination of a Tensione fase neutro: nel campo Un: ±(0,5% RDG class 2 of EN62053-23 meter (EM271 base) and class +1DGT). Tensione fase fase: nel campo Un: ±(1% RDG 0.5 of EN60044-1 CTs (TCDxM current transformer) +1DGT). Potenza attiva: da 0,2In a Imax, del campo considering the whole measurement chain. Display, Un, PF=1: ±(1,25% RDG +1DGT). Potenza reattiva: instantaneous variables readout: 3-DGT. Energies da 0,2In a Imax, allinterno del campo Un, sin(φ)=1: Imported Total: 6+1DGT. Overload status: EEE indication. ±(2,25% RDG +1DGT). Energia reattiva: migliore LED: Red LED (Energy consumption only, 1 imp./kWh). della combinazione di un contatore classe 2 (secondo Green LED for Power-on (steady) and communication EN62053-23) più un trasformatore classe 0,5 (secondo status: RX-TX (in case of RS485 option only), blinking. EN60044-1) considerando l’intera catena di misura Voltage Overloads: Continuous 1.2 Un. For 500ms EM271 + TCDxM. Display: Lettura variabili istantanee: 2 Un (except power supply terminals). Voltage input 3-DGT. Energie, importate totali: 6+1DGT. Sovraccarico: impedance: Self-power supply; power consumption: indicazione EEE. LED: LED rosso (Solo consumo di < 4VA / 2W. Pulse output: Number of outputs: 2, energia), 1 imp./kWh. LED verde relativo allo stato di Programmable from 0.01 to 9.99 kWh per pulse. Type “strumento acceso”, se a luce fissa, a luce lampeggiante Output connectable to the energy meters (kWh). Output: in caso di comunicazione RS485 presente e operativa. VON 2.5 VAC/DC/ max. 70 mA; VOFF 40 VAC/DC max. Sovraccarico corrente: Continuo: 1,2 Un. Per 500ms: 2 Insulation 4kVp/2,5kVAC output to measuring inputs. Un (eccetto le connessioni di alimentazione). Impedenza RS485: Connections 2-wire max. distance 1000m. d’ingresso tensione: Autoalimentazione, autoconsumo: Protocol, MODBUS/JBUS (RTU). Driver input capability < 4VA / 2W. Uscite impulsi: Numero di uscite: 2, 1/5 unit load. Maximum 160 transceivers on the same bus. programmabili da 0,01 a 9,99 kWh per impulso. Tipo: Insulation: by means of opto-couplers, 4kVp/2,5kVAC Uscita associabile al contatore di energia (kWh). Uscita output to measuring input. Transformer ratio: CT statica: opto-mosfet. Carico VON 2.5VCA/CC/ max.70mA primary current: auto-detection of the primary current of VOFF 40VCA/CC max. Isolamento 4kVp/2,5kVAC fra the TCDM current transformer. The maximum value of the uscita e ingressi di misura. RS485: Connessione: VT is limited to grant the measurement of the mx possible 2- fili max. distanza 1000m. Protocollo: MODBUS/ power (210MW). Max VT (PT) ratio see tab.1. Reset: By JBUS (RTU). Dispositivi in rete 1/5 unit load. Massimo means of the front keypad: • total energies (function SUM 160 dispositivi nella stessa rete. Isolamento tramite on): (kWh) • partial energies: single load energy (kWh) optoisolatori, 4kVp/2,5kVAC tra uscite e ingressi di and demanded power (Wdmd) • Max demand (Md) of misura. Rapporto di trasformazione: Corrente primaria active and apparent power. Operating temperature: CT: Auto determinazione della corrente primaria dei Operating temperature -25 to +55°C (-13°F to +131°F) trasformatori di corrente TCDM. Il valore massimo del (R.H. from 0 to 90% non-condensing @ 40°C) according TV è limitato per garantire la misura della massima to EN62052-11. Storage temperature: -30 to +70°C potenza possibile (210MW). Max rapporto TV (PT): (-22°F to +158°F) (R.H. < 90% non-condensing @ 40°C) ) vedere tab. 1. Reset: Mediante la tastiera frontale: according to EN62052-11). Overvoltage category: Cat. energie totali (funzione SUM on): kWh - energie parziali: III (IEC 60664, EN60664). Dielectric strength: 4000VAC energia del singolo carico (kWh) e potenza dmd (Wdmd) RMS for 1 minute (all terminals to front panel). Standard - Max dmd (Md) della potenza attiva e apparente. Temperatura di funzionamento: da -25°C a +55°C (da -13°F a 131°F) (U.R. da 0 a 90% senza condensa @ 40°C) secondo EN62052-11. Temperatura di immagazzinamento: da -30°C a +70°C (da -22°F a 158°F) (U.R. < 90% senza condensa @ 40°C) secondo EN62052-11. Categoria d’installazione: Cat. III (IEC 60664, EN60664). Conformità alle norme: Sicurezza: IEC60664, EN60664, IEC61010-1, EN61010-1 EN6205211, EN50470-1. Emissioni in radiofrequenza: DIN43864, IEC62053-31. Approvazioni: CE. Connessioni: Tensione: sezione del cavo Max 1,5mm² (14 AWG). Min./max. coppia di serraggio viti: 0,2/0,25 Nm. Uscite (impulsi e porta RS485). Sezione del cavo Max 1,5mm² (14 AWG). Min./max. coppia di serraggio viti: 0,2/0,25 Nm. Custodia: Dimensioni (WxHxD): 72 x 72 x 65 mm. Materiale: Noryl, autoestinguenza: UL 94 V-0. Montaggio: guida DIN o Pannello. Grado di protezione: Frontale: IP50. Connessioni: IP20. des Primärstroms des TCDM-Stromwandlers. Der Maximalwert des VT ist darauf beschränkt, die Messung der maximal möglichen Leistung (210MW) zu gewähren. Max. VT (PT)-Verhältnis siehe Tab.1. Zurücksetzen: Mittels vorderem Tastenfeld: - Gesamtenergien (Funktion SUM ein): kWh - Teilenergien: Einzellast-Energie (kWh) und geforderte Leistung (Wdmd) - Max Anforderung (Md) von Wirk- und Scheinleistung. Betriebstemperatur: Betriebstemperatur -25 bis +55°C (-13°F bis +131°F) (R.F. von 0 bis 90% nicht kondensierend @ 40°C) gemäß EN62052-11. Lagertemperatur: -30 bis +70°C (-22°F bis +158°F) (RH < 90% ohne Kondensation bei 40°C) gemäß EN62052-11). Überspannungs-Kategorie: Kl. III (IEC 60664, EN60664). Standardkonformität Sicherheit IEC60664, EN60664, IEC61010-1, EN61010-1 EN6205211, EN50470-1 Pulsausgang DIN43864, IEC6205331. Zulassungen: CE. Anschlüsse: Spannung. Max. Drahtquerschnitt 1,5 mm² (14 AWG). Min./Max. Schraubenanzugsmoment: 0,2/0,25 Nm. Ausgänge (Puls- und RS485-Port). Max. Drahtquerschnitt 1,5 mm² (14 AWG). Min./Max. Schraubenanzugsmoment: 0,2/0,25 Nm. Gehäuse Abmessungen (BxHxT): 72 x 72 x 65 mm. Gehäusematerial: Noryl, selbstlöschend: UL 94 V-0. Montage: DIN-Schienen- und Panelmontage. Schutzgrad: Front: IP50. Schraubklemmen: IP20. DEUTSCH  SICHERHEITSBESTIMMUNGEN Die Betriebsanleitung aufmerksam lesen. Sollte das Gerät nicht gemäss der Herstellerangaben verwendet werden, könnte der vom Gerät vorgesehene Schutz beeinträchtigt werden. Wartung: Beachten Sie den korrekten Anschluss aller FRANÇAIS Anschlussterminals um eine Beschädigung des Instrumentes zu vermeiden. Das Gerät mit einem  PRÉCAUTIONS DE SECURITE Lire attentivement le manuel de l’utilisateur. Si feuchten Tuch reinigen; keine Scheuer- oder Lösemittel l’appareil est utilisé dans des conditions verwenden. Das Gerät vor der Reinigung ausschalten. différentes de celles spécifiées par le fabricant, le niveau de protection prévu par l’instrument  TECHNISCHE DATEN Messeingang Stromtyp: Galvanische Isolierung durch peut être compromis. Entretien: s’assurer que les externes TCDM-Stromwandler-Zubehör. Stromspanne: connexions sont réalisées correctement dans le but Durch TCD Stromsensoren (bis 400A). Spannungsbereich: d’éviter toutes fautes ou endommagements de l’appareil. Spannung 240VLN und 415VLL (MV5), 133VLN und Pour nettoyer l’instrument, utiliser un chiffon humide; ne 230VLL (MV6). Genauigkeit die unten aufgeführten pas utiliser d’abrasifs ou de solvants. Il faut déconnecter Daten berücksichtigen die gesamte Messkette: EM271- le dispositif avant de procéder au nettoyage. Basiszähler und TCDM-Stromwandler. Stromspanne Eingang: 60, 100, 200, 400A (TCDM Primärstrom);  SPÉCIFICATIONS Imax: 1.2 In. Spannungsbereich: MV5 Bereich Un: 160 Entrées nominales. Type de courant: Isolation galvanique bis 240VLN (277 bis 415VLL). MV6 Bereich Un: 57,7 bis réalisée au moyen d’accessoires du transf. de courant 133VLN (100 bis 230VLL). Phase-Nullleiter: im Bereich TCDM externe. Portée d’émission de courant: À travers Un: ±(0,5% RDG +1DGT). Phase-Phasenspannung: im les capteurs de courant TCD (jusqu’à 400A). Plage de Bereich Un: ±(1% RDG +1DGT). Wirkstrom: Von 0,2In tension: Tension 240VLN et 415VLL (MV5), 133VLN et bis lmax, innerhalb Un-Bereich, PF=1: ±(1,25% RDG 230VLL (MV6). Précision. Les données ci-dessous +1DGT). Energien: kWh: besser als die Kombination prennent en considération l’entière chaine de mesure: Klasse 1 EN62053-21-Messgerät (EM271-Basis) und le compteur EM271 de base et le transformateur de Klasse 0.5 EN60044-1 CTs (TCDxM-Stromwandler) courant TCDM. Plage de courant: In: 60, 100, 200, 400A unter Berücksichtigung der gesamten Messkette. (courant primaire TCDM) ; Imax: 1.2 In. Plage de tension: Blindleistung: Von 0,2In bis lmax, innerhalb Un- plage MV5 Un: de 160 à 240VLN (de 277 à 415VLL). Bereich, sin(φ)=1: ±(2,25% RDG +1DGT). Blindenergie: Plage MV6 Un: de 57,7 à 133VLN (de 100 à 230VLL). besser als die Kombination Klasse 2 EN62053-23- Tension phase-neutre: Dans la gamme Un: ±(0,5% Messgerät (EM271-Basis) und Klasse 0.5 EN60044-1 RDG +1DGT). Tension phase-phase: Dans la gamme CTs (TCDxM-Stromwandler) unter Berücksichtigung der Un: ±(1% RDG +1DGT). Puissance active: De 0,2In à gesamten Messkette. Anzeige Momentanmessgrößen Imax, dans la gamme Un, PF=1: ±(1,25% RDG +1DGT). 3-DGT. Energien: Importiert gesamt: 6+1DGT. Energies: kWh: plus efficace que la combinaison de la Überlaststungsanzeige: EEE-Angabe. LEDs: Rote classe 1 d’un compteur EN62053-21 (EM271 de base) et LED (nur Energieverbrauch), 1 imp./kWh. Grüne LED que la classe 0.5 des TC EN60044-1 (transformateur de für Einschaltung (stetig) und Kommunikationsstatus: courant TCDM) prenant en considération l’entière chaîne RX-TX (nur im Falle der RS485-Option), blinkend. de mesurage. Puissance réactive: De 0.2In à Imax, Überlastspannung kontinuierlich: 1,2 Un. Für 500ms: dans la gamme Un, sin(φ)=1: ±(2,25% RDG +1DGT). 2 Un (außer versorgungsklemmen). Spannungs- Énergie réactive: plus efficace que la combinaison de Eingangsimpedanz: Eigenstromversorgung; la classe 2 d’un compteur EN62053-23 (EM271 de base) Energieverbrauch:< 4VA / 2W. Pulsausgang Anzahl der et que la classe 0.5 des TC EN60044-1 (transformateur Ausgänge: 2, programmierbar von 0,01 bis 9,99 kWh pro de courant TCDM) prenant en considération l’entière Puls. Typ: Ausgang verbindbar mit Stromzählern (kWh). chaîne de mesurage. Affichage. Lecture variables Ausgang: VON 2,5 VAC/DC/ max. 70 mA; VOFF 40 VAC/DC instantanées: 3-DGT. Energies. Total Importé: 6+1DGT. max. Isolierung: 4kVp/2,5kVAC Ausgang zur Messung von Etat de surcharge: indication EEE. LED: LED rouge Eingängen. RS485: Anschlüsse: 2-adrig. max. Abstand (seulement Consommation d’énergie, 1 imp./kWh. LED 1000m. Protokoll: MODBUS/JBUS (RTU). Besondere verte pour Marche (fixe) et état communication: RXFunktionen: 1/5 Einheitsladung. Maximal 160 Sender- TX (seulement en cas d’option RS485), clignotante. Empfänger am selben Bus. Isolierung: Durch Optokoppler, Surcharges de tension: Continu: 1,2 Un. Pour 500 ms: 4kVp/2,5kVAC Ausgang zu Messeingang. Wandler- 2 Un (sauf bornes d’alimentation). Impédance d’entrée Verhältnis: CT-Primärstrom: Automatische Erkennung tension: Auto-alimentation; Consommation d’Energie: < 4VA/2W. Sortie à impulsions: Nombre de sorties: 2, Programmables de 0,01 à 9,99 kWh par impulsion. Type: sortie raccordable aux compteurs d’énergie (kWh). Sortie; VON 2,5 VCA/CC/ max. 70 mA; VOFF 40 VCA/CC max. Isolation: 4kVp/2,5kVCA entre sortie et entrées de mesure. RS485. Connexions: 2 fils, distance max 1000m. Protocole MODBUS/JBUS. (RTU). Capacité d’entrée du pilot 1/5 charge d’unité. Maximum 160 émetteurs-récepteurs sur le même bus. Isolation: au moyen d’optocoupleurs, 4kVp/2,5kVAC entre sortie et entrée de mesure. Rapport transformateur: Courant primaire TC: auto-détection du courant primaire du transformateur de courant TCDM. La valeur maximum du transformateur de tension est limitée pour garantir la mesure de la puissance max possible (210MW). Rapport max transformateur de tension (TP). voir tab.1. Réinitialisation. Au moyen du pavé numérique à l’avant: - énergies totales (fonction SOMME activée): (kWh). - énergies partielles: énergie charge individuelle (kWh) et puissance demandée (Wdmd). - Demande max (Md) de puissance active et apparente. Température de fonctionnement: Température de fonctionnement -25 à +55°C (-13°F à +131°F) (H.R. de 0 à 90% sans condensation @ 40°C) selon EN62052-11. Température de stockage: -30 à +70°C (-22°F à +158°F) (H.R. < 90% sans condensation @ 40°C) selon EN62052-11. Catégorie surtension: Cat. III (IEC 60664, EN60664). Conformité aux normes. Sécurité IEC60664, EN60664, IEC61010-1, EN61010-1 EN62052-11, EN504701. Sortie à impulsions DIN43864, IEC62053-31. Approbations: CE. Connexions: Tension. Section max fil 1,5 mm² (14 AWG). Couple de serrage vis min./max.: 0,2/0,25 Nm. Sorties (impulsion et port RS485). Section max fil 1,5 mm² (14 AWG). Couple de serrage vis min./ max.: 0,2/0,25 Nm. Boîtier: Dimensions (LxHxP) 72 x 72 x 65 mm. Matériel: Noryl, auto-extinguible: UL 94 V-0. Montage: Rail DIN ou Montage sur panneau. Indice de protection: Frontal: IP50. Bornes à vis: IP20. ESPAÑOL  NORMAS DE SEGURIDAD Lea el manual y siga atentamente las instrucciones. Si se utiliza el equipo de manera distinta de como indica el Fabricante, se puede dañar la protección de la que está provisto el instrumento. Mantenimiento: asegurarse de que las conexiones son correctas para evitar un mal funcionamiento o daños en el instrumento. Para tener el instrumento limpio, limpiar periódicamente la carcasa con un trapo un poco humedecido. No utilizar productos abrasivos o disolventes. Desconectar el equipo antes de limpiarlo.  ESPECIFICACIONES Entrada nominal. Tipo de intensidad. Aislamiento galvánico que se lleva a cabo por medio de accesorios del transformador de intensidad TCDM externos. Escala de intensidad: A través de los sensores de corriente TCD (hasta 400A). Rango de voltaje: Voltaje 240VLN y 415VLL (MV5), 133VLN y 230VLL (MV6). Precisión: los siguientes datos corresponden a toda la cadena de medición: contador base EM271 y transformador de intensidad TCDM. Escala de intensidad: In: 60, 100, 200, 400A (Corriente primaria TCDM); Imax: 1.2 In. Rango de tensión: MV5 rango Un: 160 a 240VLN (277 a 415VLL). MV6 rango Un: 57.7 a 133VLN (100 a 230VLL). Tensión de fase neutra: En el rango Un: ±(0,5% lec. +1díg.). Tensión fase-fase: En el rango Un: ±(1% lec. +1díg.). Potencia activa: De 0,2In a Imax, dentro de la escala Un, PF=1: ±(1,25% lec. +1díg.). Energías: kWh: mejor que la combinación de una clase 1 del contador EN62053-21 (base EM271 ) y clase 0.5 de la norma EN60044-1 CTs (Transformador de corriente TCDxM) teniendo en cuenta toda la cadena de medición. Potencia reactiva: De 0,2In a Imax, dentro del rango Un, seno(φ)=1: ±(2,25% RDG +1DGT). Energía reactiva: mejor que la combinación de una clase 2 del contador EN62053-23 (base EM271 ) y clase 0.5 de la norma EN60044-1 CTs (Transformador de corriente TCDxM) teniendo en cuenta toda la cadena de medición. Display Lecturas variables instantáneas 3 dígitos. Energías, total importado: 6+1díg. Estado de sobrecarga, indicación EEE. LEDs: LED rojo (solo consumo de energía), 1 kWh por pulso. LED verde para encendido (fijo) y estado de la comunicación: RX-TX (parpadeando solo en el caso de la opción RS485). Protección contra sobretensión Continua. 1,2 Un. Durante 500ms. 2 Un (excepto los terminales de alimentación). Impedancia de entrada (tensión): Autoalimentación; Consumo de energía: < 4VA/2W. Salida de pulsos Número de salidas: 2, Programable de 0,01 a 9,99 kWh por pulso. Tipo: Salida referida a los contadores de energía (kWh). Salida: VON 2,5 VCA/CC/ máx. 70 mA; VOFF 40 VCA/CC máx. Aislamiento: 4kVp/2,5kVCA entre salida y entradas de medida. RS485 Conexiones: 2 hilos máx. distancia 1000m. Protocolo: MODBUS/JBUS (RTU). Capacidad de entrada del controlador: 1/5 carga unitaria. 160 transceptores como máximo en el mismo bus. Aislamiento: por medio de optoacopladores, 4kVp/2,5kVCA entre salida y entradas de medida. Relación de transformación: Intensidad del primario CT: detección automática de la intensidad del primario del transformador de intensidad TCDM. El valor máximo de VT se limita a garantizar la medición de la potencia máx. posible (210MW). Relación VT (PT) máxima véase tab.1. Puesta a cero: Por medio del teclado en el frontal: - energías totales (función SUM activa): (kWh) - energías parciales: energía de una carga (kWh) y potencia demandada (Wdmd) - Máxima potencia activa y aparente demandada (Md). Temperatura de funcionamiento: -25 a +55°C (-13°F a +131°F) (H.R. de 0 a 90% sin condensación @ 40°C) según la norma EN62052-11. Temperatura de almacenamiento: -30 a +70°C (-22°F a +158°F) (H.R. < 90% sin condensación @ 40°C) según la norma EN62052-11. Categoría de sobretensión: Cat. III (IEC 60664, EN60664). Conformidad con las normas Seguridad: IEC60664, EN60664, IEC61010-1, EN61010-1 EN62052-11, EN50470-1. Salida de pulso: DIN43864, IEC6205331. Marca: CE. Conexiones: Tensión. Sección máx. del cable: 1,5 mm² (14 AWG). Par de apriete mín./máx. de los tornillos: 0,2/0,25 Nm. Salidas (puerto RS485 y pulsos). Sección máx. del cable: 1,5 mm² (14 AWG). Par de apriete mín./máx. de los tornillos: 0,2/0,25 Nm. Caja: Dimensiones: (AnxAlxP) 72 x 72 x 65 mm. Material: Noryl, autoextinguible: UL 94 V-0. Montaje: EN panel o a carril DIN. Grado de protección: Frontal: IP50. Conexiones: IP20. Fase-neutral spænding: I intervallet Un: ±(0,5% RDG +1DGT). Faseneutral spænding: I intervallet Un: ±(1% RDG +1DGT). Aktiv effektmåling: Fra 0,2In til Imax, inden for Un-område, PF=1: ±(1,25% RDG +1DGT). Energi: kWh: Bedre end kombinationen af klasse 1 af EN62053-21 måler (EM271 base) og klasse 0.5 af EN60044-1 CTs (TCDxM strømtransformer), idet der tages højde for hele målekæden. Reaktive strøm: Fra 0.2In til Imax, inden for Un-område, sin(φ)=1: ±(2.25% RDG +1DGT). Reaktiv energi: Bedre end kombinationen af klasse 2 af EN62053-23 måler (EM271 base) og klasse 0.5 af EN60044-1 CTs (TCDxM strømtransformer), idet der tages højde for hele målekæden. Display: Øjeblikkelig aflæsning af variable: 3-DGT. Energi, Importeret totalt: 6+1DGT. Overbelastningsstatus: EEE-indikation. LED: Rød LED (kun strømforbrug), 1 imp./kWh. Grøn LED til tænding (lyser) og kommunikationsstatus: RX-TX (kun ved RS485 option), blinker. Spændingsoverbelastninger Løbende: 1,2 Un. For 500ms: 2 Un (undtagen strømforsyningsstik). Impedans for spændingsinput: Selvforsynet strømforsyning; Strømforbrug: < 4VA/2W. Pulsoutput Antal output: 2 Programmerbar fra 0,01 til 9,99 kWh pr. pulse. Type: Udgang kan tilsluttes energimålerne (kWh). Output: VON 2,5 VAC/DC/ max. 70 mA; VOFF 40 VAC/DC max. Isolering: 4kVp/2,5kVAC output til måling af input. RS485 Forbindelser: 2 ledere maks. afstand 1000 m. Protokol: MODBUS/JBUS (RTU). Driverinputkapacitet: 1/5 enhedsbelastning. Maksimum 160 transceivere på den samme bus. Isolering: Ved hjælp af optokoblinger, 4kVp/2,5kVAC output til målingsinput. Transformerkoefficient: CT primær strøm: Automatisk detektering af primær strøm for TCDM-strømtransformer. Maks. værdien for VT begrænses til målingen af max mulige effekt (210MW). Max VT (PT) se tab.1. Nulstil: Ved hjælp af den forreste tastatur: - totale energier (SUM-funktion af): (kWh) delvise energier: enkelt belastningsenergi (kWh) og efterspurgt effekt (Wdmd) - Maks. efterspørgsel (Md) på aktiv og synlig strøm. Driftstemperatur: -25 °C til +55 °C (-13 °F til +131°F) (relativ fugtighed fra 0 % til 90 %, ikke-kondenserende ved 40 °C) i henhold til EN62052-11. Opbevaringstemperatur: -30 til +70°C (-22°F til +158°F) (relativ fugtighed < 90% ikke-kondenserende ved 40°C) i henhold til EN62052-11. Overspændingskategori: Kat. III (IEC 60664, EN60664). Standardoverholdelse Sikkerhed: IEC60664, EN60664, IEC61010-1, EN610101 EN62052-11, EN50470-1. Pulsoutput: DIN43864, IEC62053-31. Godkendelser: CE. Forbindelser: Spænding: Maks. ledningstværsnitsareal 1,5 mm² (14 AWG). Min./maks. skruemoment: 0,2/0,25 Udgange (puls og RS485 port) Nm. Maks. ledningstværsnitsareal 1,5 mm² (14 AWG). Min./maks. skruemoment: 0,2/0,25 Nm. Hus: Dimensioner (BxHxD): 72 x 72 x 65 mm. Materiale: Noryl, selvslukkende: UL 94 V-0. Montering: DIN-skinne DANSK eller panelmontering. Beskyttesesgrad: Forside: IP50.  SIKKERHEDSFORSKRIFTER Læs instruktionsmanualen omhyggeligt. Hvis Skrueklemmer: IP20. instrumentet anvendes på en måde, der ikke er beskrevet af producenten, kan den af instrumentet ydede beskyttelse forringes. Vedligeholdelse: Sørg for, at forbindelserne er korrekt udført for at undgå enhver fejlfunktion eller beskadigelse af instrumentet. Til rengøring af instrumentet anvendes en let fugtet klud; anvend ikke slibe- eller rengøringsmidler. Vi anbefaler, at instrumentet frakobles før rengøring.  TEKNISKE SPECIFIKATIONER Nominelt input Strømtype: Galvanisk isolering udført ved hjælp af eksternt tilbehør til TCDM-strømtransformer. Strømområde: Via TCD strømsensorer (op til 400A). Spændingsområde: Spænding 240VLN og 415VLL (MV5), 133VLN og 230VLL (MV6). Nøjagtighed Nedenstående data tager højde for den komplette målingskæde: EM271 basemåler og TCDM-strømtransformer. Strømområde: In: 60, 100, 200, 400A (TCDM primær strøm). Imax: 1.2In. Spændingsområde: MV5-område Un: 160-240VLN (277415VLL). MV6-område Un: 57,7-133VLN (100-230VLL).