Allen-Bradley SLC 5/01 Installation Instructions Manual

Tipo
Installation Instructions Manual

Este manual también es adecuado para

SLC 5/01™ and SLC 5/02™ Modular
Processors
(Catalog Numbers 1747-L511, 1747-L514,
1747-L524)
Installation Instructions
English Section . . . . . . . . . . . . . . . . 3
Section en francais . . . . . . . . . . . . . 15
Deutscher Abschnitt . . . . . . . . . . . . 27
Sezione italiana . . . . . . . . . . . . . . . 39
Sección en español . . . . . . . . . . . . 51
Inside...
page
Allen-Bradley Replacements
SLC 5/01™ and SLC 5/02™ Modular
Processors
(Catalog Numbers 1747-L511, 1747-L514,
1747-L524)
Installation Instructions
English Section
Important User Information . . . . . . . . .4
For More Information . . . . . . . . . . . . 5
Required Tools and Equipment . . . . 6
Safety Considerations . . . . . . . . . . . 6
Installation Procedure . . . . . . . . . . . 7
Troubleshooting . . . . . . . . . . . . . . . . 9
Specifications . . . . . . . . . . . . . . . . . 10
Battery Handling, Storing, and
Transporting (Cat. No. 1747-BA) . . 12
Inside...
page
4
Publication 1747-5.25
Important User Information
Because of the variety of uses for the products described in this publication, those
responsible for the application and use of this control equipment must satisfy
themselves that all necessary steps have been taken to assure that each
application and use meets all performance and safety requirements, including any
applicable laws, regulations, codes and standards.
The illustrations, charts, sample programs and layout examples shown in this
guide are intended solely for purposes of example. Since there are many
variables and requirements associated with any particular installation,
Allen-Bradley does not assume responsibility or liability (to include intellectual
property liability) for actual use based upon the examples shown in this
publication.
Allen-Bradley publication SGI-1.1, Safety Guidelines for the Application,
Installation, and Maintenance of Solid-State Control (available from your local
Allen-Bradley office), describes some important differences between solid-state
equipment and electromechanical devices that should be taken into consideration
when applying products such as those described in this publication.
Reproduction of the contents of this copyrighted publication, in whole or in part,
without written permission of Allen-Bradley Company, Inc., is prohibited.
Throughout these installation instructions we use notes to make you aware of
safety considerations:
Attention statements help you to:
identify a hazard
avoid the hazard
recognize the consequences
ATTENTION: Identifies information about practices or
circumstances that can lead to personal injury or death, property
damage or economic loss
Important:
Identifies information that is critical for successful application and
understanding of the product.
Allen-Bradley Replacements
5
Publication 1747-5.25
For More Information
As part of our effort to preserve, protect, and improve our environment,
Allen-Bradley is reducing the amount of paper we use. Less paper means more
options for you. In addition to traditional printed publications and CD-ROM
versions, we now offer on-line manuals with the most up-to-date information you
can get. We recommend that you read the related publications listed below
before starting up your control system.
Related Publications
If you would like a manual, you can:
download a free electronic version from the internet:
www.theautomationbookstore.com
purchase a printed manual by:
contacting your local distributor or Rockwell Automation
representative
visiting www.theautomationbookstore.com and placing your order
calling 1.800.963.9548 (USA/Canada) or
001.330.725.1574 (Outside USA/Canada)
For Refer to this Document Pub. No.
A more detailed description on how to
install and use your modular SLC 500
system.
SLC 500 Modular
Hardware Style Installation
and Operation Manual
1747-6.2
A reference manual that contains status
file data, instruction set, and
troubleshooting information.
SLC 500 and MicroLogix
1000 Instruction Set
Reference Manual
1747-6.15
A CD–ROM containing both of the
manuals listed above, plus the:
•SLC 500 Analog I/O Modules User
Manual
•Discrete I/O Modules Installation
Instructions
•Discrete I/O Modules Product Data
SLC 500 Literature
Collection on CD–ROM
1747-CD1-1
6
Publication 1747-5.25
Required Tools and Equipment
medium blade screwdriver
programming equipment
a 1747-PIC, 1784-KTX, or 1784-PCMK communication interfaces
Safety Considerations
For general recommendations concerning installation safety requirements and
safety related work practices, refer to the requirements specific to your region.
Europe: Reference the standards found in EN 60204 and your national
regulations.
United States: refer to NFPA 70E, Electrical Safety Requirements for
Employee Workplaces.
ATTENTION: Never install, remove, or wire any module while
power is applied. Also, do not expose processor modules to
surfaces or other areas that may typically hold an electrostatic
charge. Electrostatic charges can alter or destroy memory.
Important:
See page 10 for information on proper battery handling, storage, and
transporting.
Allen-Bradley Replacements
7
Publication 1747-5.25
Installation Procedure
Install the Battery
1. Open the door of the processor.
2. Remove the jumper from the battery connector socket. Store the jumper in
a safe place for possible future use without the battery.
3. Insert a new or replacement battery in the holder making sure it is held in by
the retainer clips.
4. Plug the battery connector into the socket. See the figure below.
5. Close the processor door.
Important:
If your processor has a battery— the battery is an option for the SLC
5/01 (1747-L511) processor — make sure it is connected before
installing your processor into the chassis. This provides memory
backup for your processor should the controller power supply fail.
Important:
See page 10 for information on proper battery handling, storage, and
transporting.
+
White
Lead
Red
Lead
Battery
Connector
Retainer
Clips
8
Publication 1747-5.25
Install the Processor
Make sure system power is off; then insert the processor into slot 0 of the 1746
chassis.
Apply Power to the Processor
1. Energize the chassis power supply.
2. Check the chassis power supply and processor LEDs. The power LED on the
power supply should be on and the fault LED on the processor should be
flashing.
Important:
The SLC 500t Modular Processors must be inserted into the left slot
(slot 0), as shown below. In addition, remove the protective wrap after
installing the processor.
Processor
Release
Card Guide
Protective Wrap
Power
Supply
Indicates the LED is OFF.
Indicates the LED is ON.
Indicates the LED is
FLASHING.
Status of LED does not matter.
POWER
RUN
CPU FAULT
FORCED I/O
BATTERY LOW
COMM
The RUN LED on the SLC 5/01
processor is actully labeled “PC
RUN.” Also, the SLC 5/01 processor
does not have a COMM LED.
Allen-Bradley Replacements
9
Publication 1747-5.25
Load Your Software
Refer to your programming software documentation.
Establish Communications with the Processor
1. Connect the 1747-PIC to the processor and your personal computer.
2. Set the communication parameters of the software to match the default
parameters of the processor:
DH-485
19.2k baud
Node Address = 1
Troubleshooting
Before troubleshooting your SLC 500 system, please obtain an SLC 500 Modular
Hardware Style Installation and Operation Manual (1747-6.2) from one of the
sources listed on page 3. Refer to the chapter on Troubleshooting.
In addition to the SLC 500 Modular Hardware Style Installation and Operation
Manual, the SLC 500 and MicroLogix 1000 Instruction Set Reference Manual
(1747-6.15) may also be obtained from the sources listed on page 3. This manual
contains explanations and examples for the entire instruction set as well as for all
status words and bits. It also contains explanations for all possible fault codes
found in status word S:6.
10
Publication 1747-5.25
Specifications
Specification
SLC 5/01
(1747-L511, -L514)
SLC 5/02
(1747-L524)
Program Memory 1K or 4K Instructions 4K Instructions
Additional Data Storage 0 0
Maximum I/O Capacity
3940 discrete inputs
3940 discrete outputs
4096 discrete inputs
4096 discrete outputs
Max. Local Chassis/Slots 3/30 3/30
Programming Software RSLogix 500 , PLC–500 A.I. Series, APS, and HHT
Programming Instructions 52 71
Typical Scan Time
(1)
(1)
The scan times are typical for a 1K ladder logic program consisting of simple ladder logic and
communication servicing. Actual scan times depend on your program size, instuctions used, and
the communication protocol.
8 ms/K 4.8 ms/K
Bit Execution (XIC) 4 µs 2.4 µs
Communication Receive Receive or Initiate
DH-485 SLC 5/01
(1)
(1)
A 1747-PIC is required when connecting to the DH-485 channel for programming.
SLC 5/02
(1)
Allen-Bradley Replacements
11
Publication 1747-5.25
The following table summarizes the available memory back up options for the
SLC 5/01 and SLC 5/02 processors. EEPROM and UVPROM memory modules
provide non-volatile memory back-up.
Description Specification
Power Supply Loading at 5V dc 350 mA
Power Supply Loading at 24V dc 105 mA
Program Scan Hold-up Time after Loss of
Power
20 ms to 3 s (dependent on power supply loading)
Noise Immunity NEMA Standard ICS 2-230
Vibration
Displacement: 0.015 inch, peak-to-peak at 5-57
Hz
Acceleration: 2.5Gs at 57-2000 Hz
Shock (operating) 30Gs
Ambient Temperature Rating
Operating: 0 to + 60
°
C (32
°
F to 140
°
F)
Storage: 40
°
C to 85
°
C (-40
°
F to 185
°
F)
Humidity 5 to 95% without condensation
Agency Certification
UL listed
CSA approved
Class 1, Groups A, B, C or D, Division 2
CE compliant for all applicable directives
Memory Back Up Option
SLC 5/01
(1747-L511/1747-L514)
SLC 5/02
(1747-L524)
EEPROM 1747-M1, 1747-M2 1747-M2
UVPROM 1747-M3, 1747-M4 1747-M4
12
Publication 1747-5.25
Battery Handling, Storing, and Transporting (Cat. No. 1747-BA)
Handling
Storing
Store the lithium batteries in a cool, dry environment, typically +20° C to +25° C
(+68° F to +77° F) and 40% to 60% relative humidity.
Transporting
One or Two Batteries Up to two batteries can be shipped together within the
United States without restriction. Regulations governing shipment to or within
other countries may differ.
Three or More Batteries — Procedures for the transportation of three or more
batteries shipped together within the United States are specified by the
Department of Transportation (DOT) in the Code of Federal Regulations,
CFR49, “Transportation.” An exemption to these regulations, DOT - E7052,
covers the transport of certain hazardous materials classified as flammable solids.
This exemption authorizes transport of lithium batteries by motor vehicle, rail
freight, cargo vessel, and cargo-only aircraft, providing certain conditions are
met. Transport by passenger aircraft is not permitted.
Shipment of depleted batteries for disposal may be subject to specific regulation
of the countries involved or to regulations endorsed by those countries, such as
the IATA Restricted Articles Regulations of the International Air Transport
Association, Geneva, Switzerland.
ATTENTION: Do not charge the batteries. An explosion could
result or the cells could overheat causing burns.
Do not open, puncture, crush, or otherwise mutilate the batteries.
An explosion may result and/or toxic, corrosive, and flammable
liquids would be exposed.
Important:
Regulations for transportation of lithium batteries are periodically
revised.
Allen-Bradley Replacements
13
Publication 1747-5.25
For disposal, batteries must be packaged and shipped in accordance with
transportation regulations, to a proper disposal site. The U.S. Department of
Transportation authorizes shipment of “Lithium batteries for disposal” by motor
vehicle only in regulation 173.1015 of CFR 49 (effective January 5, 1983). For
additional information contact:
U.S. Department of Transportation
Research and Special Programs Administration
400 Seventh Street, S.W.
Washington, D.C. 20590
Although the Environmental Protection Agency at this time has no regulations
specific to lithium batteries, the material contained may be considered toxic,
reactive, or corrosive. The person disposing of the material is responsible for any
hazard created in doing so. State and local regulations may exist regarding the
disposal of these materials.
For a lithium battery material safety data sheet, contact the manufacturer:
Sanyo Energy Corporation
600 Supreme Drive
Bensenville, IL 60106
ATTENTION: Do not incinerate or dispose of lithium batteries in
general trash collection. Explosion or violent rupture is possible.
Batteries should be collected for disposal in a manner to prevent
against short circuiting, compacting, or destruction of case integrity
and hermetic seal.
Processeurs modulaires SLC 5/01™
et SLC 5/02™
(Références 1747-L511, 1747-L514, 1747-L524)
Notice d’installation
Section en francais
Informations utilisateur ............................ 16
Complément d’informations .................... 17
Outils et équipement requis .................... 18
Considérations de sécurité ...................... 18
Procédure d’installation ........................... 19
Dépannage .............................................. 21
Spécifications .......................................... 22
Manipulation, stockage et transport de piles
(Réf. 1747-BA) ........................................ 24
pageContenu...
Allen-Bradley Replacements
16
Publication 1747-5.25
Informations utilisateur
En raison de la diversité des utilisations des produits décrits dans le présent
manuel, les personnes responsables de l’équipement doivent s’assurer que toutes
les mesures ont été prises pour que l’application et l’utilisation des produits
soient conformes aux exigences de performance et de sécurité, ainsi qu’aux lois,
règlements, codes et normes en vigueur.
Les illustrations, schémas et exemples de programmes contenus dans ce manuel
sont présentés à titre indicatif seulement. En raison des nombreuses variables et
impératifs associés à chaque installation, la société Allen-Bradley ne saurait être
tenue pour responsable ou redevable (y compris en matière de proprié
intellectuelle) des suites d’utilisation réelle basée sur les exemples et schémas
présentés dans ce manuel.
La publication SGI-1.1, Safety Guidelines for the Application, Installation, and
Maintenance of Solid-State Control (disponible auprès de votre agence
commerciale Allen-Bradley) décrit certaines différences importantes entre les
équipements électroniques et les équipements électromécaniques qui devront être
prises en considération lors de l’application de ces produits comme indiqué dans
la présente publication.
Toute reproduction partielle ou totale du présent manuel sans autorisation écrite
de la société Allen-Bradley est interdite.
Des remarques sont utilisées tout au long de ce manuel pour attirer votre attention
sur les mesures de sécurité à prendre en compte :
Les encarts Attention vous aident à :
identifier un danger
éviter un danger
discerner les conséquences
ATTENTION:
Indique les informations sur les pratiques ou
circonstances pouvant entraîner des dommages corporels, dégâts
matériels ou pertes financières.
Important:
Indique les informations déterminantes pour la bonne
compréhension et application du produit.
17
Publication 1747-5.25
Complément d’informations
Dans le cadre des efforts de protection, de sauvegarde et d’amélioration de
l’environnement, Allen-Bradley réduit la quantité de papier utilisé. Moins de
papier, c’est aussi un plus grand choix pour les utilisateurs : outre les publications
imprimées traditionnelles et versions sur CD-ROM, nous vous offrons
maintenant des manuels en ligne comportant les informations les plus récentes.
Nous vous recommandons de lire les publications associées, énumérées
ci-dessous, avant de lancer votre système de commande.
Publications associées
Comment obtenir plus d’informations
Pour vous procurer un manuel, vous pouvez :
le charger gratuitement depuis le site Internet :
www.theautomationbookstore.com
acheter un manuel imprimé. Pour cela :
contactez votre distributeur local Rockwell Automation
visitez www.theautomationbookstore.com et commandez-le en
ligne
appelez le 1.800.963.9548 (USA/Canada)
ou le 001.330.725.1574 (hors USA/Canada)
Pour Voir ce document Réf.
Une description plus détaillée de l’installation et
de l’utilisation de votre système modulaire SLC
500.
SLC 500 Modular
Hardware Style
Installation and Operation
Manual
1747-6.2
Un manuel de référence comportant des
informations sur les données du fichier détat, le
jeu d’instructions et le dépannage.
Manuel de référence et de
jeu d’instructions SLC 500
et MicroLogix 1000
1747-6.15FR
Un CD-ROM contenant les manuels énumérés
ci-dessus plus :
Manuel d’utilisation des modules d’E/S
analogiques SLC 500
Notice d’installation des modules d’E/S TOR
Description produit des modules d’E/S TOR
Ensemble des manuels
SLC 500 sur CD-ROM
1747-CD1-1
Allen-Bradley Replacements
18
Publication 1747-5.25
Outils et équipement requis
un tournevis plat de taille moyenne
un équipement de programmation
une interface de communication 1747-PIC, 1784-KTX ou 1784-PCMK
Considérations de sécurité
Pour connaître les recommandations générales relatives aux impératifs de
sécurité d’installation et de protection des postes de travail, reportez-vous aux
normes en vigueur dans votre région.
Europe : Référence aux normes EN 60204 et aux réglementations
nationales.
Etats–Unis : Référence au NFPA 70E, « Electrical Safety Requirements for
Employee Workplaces ».
ATTENTION: Ne jamais installer, retirer ou câbler un module
sous tension. N’exposez pas les modules processeurs aux surfaces
ou autres zones généralement soumises à des charges
électrostatiques. Les charges électrostatiques peuvent endommager
ou détruire la mémoire.
Important:
Pour plus d’informations sur la manipulation, le stockage et le
transport des piles, reportez-vous à la page 23.
19
Publication 1747-5.25
Procédure d’installation
Installation de la pile
1. Ouvrez la porte du processeur.
2. Retirez le cavalier de la fiche du connecteur de la pile. Conservez le cavalier
dans un endroit sûr afin de pouvoir l’utiliser ultérieurement sans la pile.
3. Insérez une nouvelle pile ou une pile de rechange dans le support en veillant
à ce qu’elle soit retenue par les clips de blocage.
4. Branchez le connecteur de la pile dans la fiche. Voir figure ci-dessous.
5. Refermez la porte du processeur.
Important:
Si votre processeur est équipé d’une pile — la pile est une option du
processeur SLC 5/01 (1747-L511) — assurez-vous qu’elle est
connectée avant d’installer le processeur dans le châssis. La pile
assure la sauvegarde de la mémoire en cas de coupure de courant de
votre processeur.
Important:
Pour plus d’informations sur la manipulation, le stockage et le
transport des piles, reportez-vous à la page 23.
+
Fil
blanc
Fil
rouge
Connecteur
de la pile
Clips de
blocage
Allen-Bradley Replacements
20
Publication 1747-5.25
Installation du processeur
Assurez-vous que l’alimentation est hors tension, puis insérez le processeur dans
l’emplacement 0 du châssis 1746.
Mise sous tension du processeur
1. Mettez l’alimentation du châssis sous tension.
2. Surveillez les LED de l’alimentation et du processeur. La LED « POWER »
de l’alimentation doit être allumée et la LED d’erreur du processeur doit
clignoter.
Important:
Les processeurs modulaires SLC 500t doivent être insérés dans
l’emplacement de gauche (emplacement 0), comme illustré
ci-dessous. Retirez la bande de protection après avoir installé le
processeur.
Alimentation
Guide-carte
Bande de protection
Loquet du
processor
Indique que la LED est éteinte.
Indique que la LED est allumée.
Indique que la LED clignote.
Letat de la LED n’a pas d’importanc
e
POWER
RUN
CPU FAULT
FORCED I/O
BATTERY LOW
COMM
La LED RUN du processeur SLC 5/01 est
appelée PC RUN. Le processeur SLC 5/
01 n’a pas de LED COMM.
21
Publication 1747-5.25
Chargement de votre logiciel
Réferez-vous à la documentation de votre logiciel de programmation.
Establissement des communications avec le processeur
1. Connectez le 1747-PIC au processeur et à votre ordinateur personnel.
2. Définissez les paramètres de communication du logiciel en fonction des
paramètres par défaut du processeur :
DH-485
19,2 kbauds
Adresse de poste = 1
Dépannage
Avant de commencer à dépanner votre système SLC 500, veuillez vous procurer
le Manuel d’installation et de fonctionnement des SLC 500 modulaires
(1747-6.2) auprès d’une des sources de documentation présentées en page 16.
Référez-vous au chapitre relatif au dépannage.
Outre le manuel précité, le Manuel de référence et jeu d’instructions du SLC 500
et du MicroLogix 1000 (1747-6.15FR) peut également être obtenu auprès des
sources de documentation présentées en page 16. Ce manuel comporte des
explications et exemples pour l’ensemble du jeu d’instructions ainsi que pour
tous les mots et bits d’états. Il comporte également les explications de tous les
codes d’erreur possibles contenus dans le mot d’état S:6.
Allen-Bradley Replacements
22
Publication 1747-5.25
Spécifications
Spécification
SLC 5/01
(1747-L511, -L514)
SLC 5/02
(1747-L524)
Mémoire programme 1 K ou 4 K instructions 4 K instructions
Stockage de données
sup.
00
Capacité d’E/S maximum
3940 entrées TOR
3940 sorties TOR
4096 entrées TOR
4096 sorties TOR
Nbre maxi de châssis
locaux/emplacements
3/30 3/30
Logiciel de
programmation
RSLogix 500
t
, PLC-500 A.I. Series
t
, APS et HHT
Instructions de
programmation
52 71
Durée de scrutation
type
(1)
(1)
Les durées de scrutation sont généralement calculées pour un programme de logique à relais 1 K
composé d’une logique à relais simple et du traitement des communications. Les durées de
scrutations réelles dépendent de la taille de votre programme, des instructions utilisées et du
protocole de communication.
8 ms/K 4,8 ms/K
Exécution de bit (XIC) 4
µ
s2,4
µ
s
Communication Réception Réception ou envoi
DH-485 SLC 5/01
(1)
(1)
Un 1747-PIC est nécessaire pour la connexion de la voie DH-485 à des fins de
programmation.
SLC 5/02
(1)
23
Publication 1747-5.25
Le tableau suivant résume les options de mémoire de sauvegarde disponibles
pour les processeurs SLC 5/01 et SLC 5/02. Les modules mémoire EEPROM et
UVPROM assurent une sauvegarde de la mémoire non volatile.
Description Spécification
Intensité de l’alimentation à 5 V c.c. 350 mA
Intensité de l’alimentation à 24 V
c.c.
105 mA
Temps de maintien de la scrutation
du programme après perte
d’aliementation
de 20 ms à 3 s (selon l’intensité de l’alimentation)
Immunité au bruit Norme NEMA ICS 2-230
Résistance aux vibrations Déplacement : 0,015 in, crête à crête à 5-57 Hz
Accélération : 2,5 G à 57-2000 Hz
Tenue aux chocs (en service) 30 G
Plage des températures
En fonctionnement : de 0 à + 60
°
C (de 32
°
F à 140
°
F)
Stockage : de 40
°
C à 85
°
C (de -40
°
F à 185
°
F)
Humidité ambiante de 5 à 95 % sans condensation
Homologation
Listé UL
Approuvé CSA
Classe 1, Groupes A, B, C ou D, Division 2
Conforme CE pour toutes les directives en vigueur
Option de sauvegarde de la
mémoire
SLC 5/01
(1747-L511/1747-L514)
SLC 5/02
(1747-L524)
EEPROM 1747-M1, 1747-M2 1747-M2
UVPROM 1747-M3, 1747-M4 1747-M4
Allen-Bradley Replacements
24
Publication 1747-5.25
Manipulation, stockage et transport de piles (Réf. 1747-BA)
Manipulation
Stockage
Stockez les piles au lithium dans un endroit sec et frais, entre +20° C et +25° C
(+68° F et +77° F) et une humidité ambiante comprise entre 40 % et 60 %.
Transport
Une ou deux piles Vous pouvez envoyer jusqu’à deux piles à l’intérieur des
Etats-Unis sans aucune restriction. Les réglementations relatives à l’expédition
peuvent varier d’un pays à l’autre.
Trois piles ou plus Les procédures de transport de trois piles ou plus à
l’intérieur des Etats-Unis sont spécifiées par le Ministère américain des
transports (Department of Transportation - DOT) dans le code des
réglementations fédérales (Code of Federal Regulations), CFR49, «
Transportation ». Certains matériaux classés comme solides inflammables
bénéficient d’une exemption DOT - E7052 à cette réglementation. Cette
exemption autorise le transport des piles au lithium par véhicule à moteur, frêt
ferrovière, maritime et avion cargo sous certaines conditions. Le transport par
avion passager est interdit.
L’expédition de piles déchargées pour mise au rebut est soumise aux réglements
spécifiques du pays concerné ou aux réglements avalisés par lesdits pays, tels que
lmes réglementations d’articles restrictifs de l’IATA (l’International Air
Transport Association), Genève.
ATTENTION: Ne pas ouvrir, percer, écraser ou détériorer les
piles. Une explosion pourrait se produire et/ou exposer des
substances inflammables, corrosives et toxiques. Ne pas
recharger les piles. Une explosion pourrait se produire et la
surchauffe des éléments de la pile pourrait provoquer des
brûlures.
Important:
Les réglementations du transport des piles au lithium sont révisées
périodiquement.
25
Publication 1747-5.25
Pour la mise au rebut, les piles doivent être emballées et expédiées vers un site
approprié conformément aux réglementations de transport. Le Ministère
américain des transports autorise l’expédition de « piles au lithium pour la mise
au rebut » par véhicule à moteur dans son réglement 173.1015 de CFR 49 (en
vigueur depuis le 5 janvier 1983). Pour toute information complémentaire,
adressez-vous à :
U.S. Department of Transportation
Research and Special Programs Administration
400 Seventh Street, S.W.
Washington, D.C. 20590
Bien que l’Agence américaine de protection de l’environnement n’ait pas
actuellement de réglementation spécifique aux piles au lithium, la matière
contenue dans ces piles est considérée comme toxique, réactive et corrosive. La
personne en charge de la mise au rebut de ces matières est responsable de tout
risque résultant de son action. Des réglementations nationales et locales relatives
à la mise au rebut de ces matières peuvent exister.
Pour obtenir une fiche technique de sécurité sur les piles au lithium,
adressez-vous au fabricant :
Sanyo Energy Corporation
600 Supreme Drive
Bensenville, IL 60106
ATTENTION: Ne pas incinérer ou jeter les piles au lithium dans
des conteneurs non prévus à cet effet. Une explosion ou une
rupture pourrait se produire. Les piles doivent être collectées pour
la mise au rebut de façon à éviter les court-circuits, le compactage
ou la destruction du boîtier hermétique et de son enveloppe
hermétique.
Allen-Bradley Replacements
26
Publication 1747-5.25
Notes:
Publikation 1747-5.25
Modulare Prozessoren SLC 5/01
und SLC 5/02
(Bestellnummern 1747-L511, 1747-L514,
1747-L524)
Installationsdaten
Deutscher Abschnitt
Wichtige Anwendungshinweise . . . . . . . . . . . 28
Weitere Informationen . . . . . . . . . . . . . . . . . . 29
Erforderliche Werkzeuge und Geräte . . . . . . . 30
Sicherheitshinweise . . . . . . . . . . . . . . . . . . . . 30
Einbauverfahren . . . . . . . . . . . . . . . . . . . . . . . 31
Störungssuche . . . . . . . . . . . . . . . . . . . . . . . . 33
Technische Daten . . . . . . . . . . . . . . . . . . . . . . 34
Handhabung, Lagerung und Transport der Batterie
(Best.-Nr. 1747-BA) . . . . . . . . . . . . . . . . . . . . 36
SeiteInhalt...
Allen-Bradley Replacements
28
Publikation 1747-5.25
Wichtige Anwendungshinweise
Aufgrund der vielfältigen Einsatzmöglichkeiten der in dieser Publikation
beschriebenen Produkte müssen Sie als Verantwortlicher für die Anwendung und
Nutzung dieses Geräts sicherstellen, daß jede Anwendung bzw. jeder Einsatz alle
Leistungs- und Sicherheitsanforderungen, einschließlich sämtlicher
anwendbaren Gesetze, Vorschriften, Codes und Normen erfüllt.
Die in diesem Handbuch dargestellten Abbildungen, Tabellen, Programm- und
Layout-Beispiele sind ausschließlich zur besseren Texterläuterung dieses
Handbuchs aufgeführt. Aufgrund der vielfachen Möglichkeiten und
Anforderungen jedes einzelnen Verwendungszwecks kann Allen-Bradley keine
Verantwortung oder Haftung (einschließlich Haftung für geistiges Eigentum) für
den tatsächlichen Einsatz, der auf den in dieser Publikation enthaltenen
Beispielen beruht, übernehmen.
Die Allen-Bradley Publikation SGI-1.1, Safety Guidelines for the Application,
Installation, and Maintenance of Solid-State Controls (erhältlich über Ihre
örtliche Allen-Bradley Geschäftsstelle) behandelt einige wichtige Unterschiede
zwischen elektronischen und elektromechanischen Geräten, die bei der
Anwendung der in dieser Publikation beschriebenen Produkte berücksichtigt
werden sollten.
Die Vervielfältigung des Inhalts dieses verlagsrechtlich geschützten Handbuchs,
ganz oder auszugsweise, bedarf der schriftlichen Genehmigung der
Allen-Bradley Company, Inc.
Besondere Hinweise in diesem Handbuch sollen den Anwender auf bestimmte
Sicherheitsaspekte aufmerksam machen:
Die Achtungshinweise helfen Ihnen:
Gefahrenzustände zu erkennen
Gefahren zu vermeiden
Folgeschäden zu erkennen
ACHTUNG: Diese Hinweise sollen den Leser auf Vorgehensweisen und Zustände
aufmerksam machen, die Körperverletzungen oder sogar Tod sowie
Geräteschäden oder wirtschaftliche Verluste zur Folge haben können.
Wichtig:
Kennzeichnet Informationen, die für die erfolgreiche Anwendung
sowie für ein gründliches Verstehen des Produkts unabdingbar sind.
29
Publikation 1747-5.25
Weitere Informationen
In unseren Bemühungen, die Umwelt zu erhalten, zu schützen und zu verbessern,
reduzieren wir bei Allen-Bradley die Papiermenge, die wir einsetzen. Weniger
Papier bedeutet mehr Alternativen für Sie. Neben den herkömmlichen
gedruckten Publikationen bieten wir nun Online-Handbücher an, die aktuellste
Daten enthalten. Vor der Inbetriebnahme des Steuerungssystems empfehlen wir
das Lesen der unten aufgeführten themenverwandten Publikationen.
Themenverwandte Publikationen
Zusätzliche Informationen
Zu diesem Produkt gibt es eine Benutzerhandbuch, das Sie wie folgt bestellen
können:
durch kostenloses Herunterladen vom Internet:
www.theautomationbookstore.com
durch Erwerb:
bei Ihrem Distributor oder einer Niederlassung von Rockwell
Automation in Ihrer Nähe
per Internet: www.theautomationbookstore.com
per Telefon unter folgenden Rufnummern:
1.800.963.9548 (USA/Kanada)
oder
001.330.725.1574 (außerhalb den USA/Kanadas)
Informationen über: Dokumentation: Publik.–Nr.
Detailliertere Beschreibung über die
Installation und Anwendung von SLC
500-Steuerungssystemen mit fester
Hardware-Konfiguration
SLC 500 Modular Hardware Style
Installation and Operation Manual
1747-6.2
Referenzhandbuch mit
Statusfiledaten, Befehlssatz und
Hinweisen zur Störungssuche
Befehlssatz für SLC 500
und MicroLogix 1000
Referenzhandbuch
1747-6.15DE
Die beiden oben aufgeführten
Handbücher sowie die folgenden
Publikationen auf CD-ROM:
Analog-E/A-Module SLC 500,
Benutzerhandbuch
Diskrete E/A-Module,
Installationsdaten
Diskrete E/A-Module, Produktdaten
gesammelte SLC
500-Publikationen auf CD-ROM
1747-CD1-1
Allen-Bradley Replacements
30
Publikation 1747-5.25
Erforderliche Werkzeuge und Geräte
mittelgroßer Flachschraubendreher
Programmiergerät
Kommunikationsschnittstelle 1747-PIC, 1784-KTX oder 1784-PCMK
Sicherheitshinweise
Allgemeine Empfehlungen zu den installationsbezogenen Sicherheits-
anforderungen und zu sicherheitsrelevanten Verfahrensweisen am Arbeitsplatz
sind den einschlägigen regionalen Bestimmungen zu entnehmen.
Europa: Normen gemäß EN 60204 und VDE-Vorschriften.
USA: NFPA 70E, Electrical Safety Requirements for Employee Workplaces.
ACHTUNG: Ein Modul darf niemals bei anliegender Spannung installiert, entfernt
oder verdrahtet werden. Ferner darf ein Prozessormodul keinen Flächen oder
Bereichen ausgesetzt werden, die u.U. elektrostatische Ladungen aufweisen, da
sonst die Gefahr besteht, daß der Speicherinhalt verändert oder zerstört wird.
Wichtig:
Hinweise zur ordnungsgemäßen Handhabung, Lagerung und
Entsorgung der Batterie sind auf Seite 23 enthalten.
31
Publikation 1747-5.25
Einbauverfahren
Einbau der Batterie
1. Die Tür des Prozessors öffnen.
2. ie Brücke aus der Batterieanschlußbuchse entfernen und für den eventuellen
späteren Gebrauch ohne Batterie an einem sicheren Ort aufbewahren.
3. Eine neue bzw. Ersatzbatterie in die Halterung einsetzen. Darauf achten,
daß die Batterie fest in den Halteclips sitzt.
4. en Batterieanschluß in die Buchse stecken. Siehe folgende Abbildung.
5. Die Tür des Prozessors schließen.
Wichtig:
Sofern der Prozessor mit einer Batterie ausgestattet ist — beim
Prozessor SLC 5/01 (1747-L511) ist die Batterie optional — muß
sichergestellt werden, daß sie angeschlossen wird, bevor der
Prozessor in das Chassis eingebaut wird. Der Inhalt des
Prozessorspeichers wird somit gesichert, falls die
Spannungsversorgung der speicherprogrammierbaren Steuerung
ausfällt.
Wichtig:
Hinweise zur ordnungsgemäßen Handhabung, Lagerung und
Entsorgung der Batterie sind auf Seite 23 enthalten.
+
Batterie-
anschluß
Halteclips
roter
Draht
weißer
Draht
Allen-Bradley Replacements
32
Publikation 1747-5.25
Einbau des Prozessors
Vergewissern Sie sich, daß die Systemspannung ausgeschaltet ist, und schieben
Sie den Prozessor anschließend in Steckplatz 0 des Chassis der Reihe 1746.
Einschalten der Spannung
1. Das Chassisnetzteil einschalten.
2. Die LED-Anzeigen des Chassisnetzteils und des Prozessors überprüfen.
Die POWER-LED des Netzteils sollte leuchten, und die Fehler-LED des
Prozessors sollte blinken.
Wichtig:
Die modularen Prozessoren der Reihe SLC 500t müssen, wie unten
dargestellt, in den linken Steckplatz (Steckplatz 0) eingeschoben
werden. Außerdem muß nach dem Einbau des Prozessors der
Schutzstreifen entfernt werden.
Netzteil
Prozessor-
entriegelungslasche
Modulführung
Schutzstreifen
LED-Anzeigen des Netzteils sowie des SLC 5/01 und SLC 5/02
LED AUS
LED LEUCHTET
LED BLINKT
LED-Status ist unbedeutend
Nur bei dem Prozessor SlC 5/01: Die
RUN-Anzeige tragt die Beschriftung “PC
RUN.” Die COMM-Anzeige ist nicht
vorhanden.
RUN
CPU FAULT
FORCED I/O
BATTERY LOW
POWER
COMM
33
Publikation 1747-5.25
Laden der Software
Hinweise sind in den Handbüchern der Programmiersoftware enthalten.
Herstellung der Kommunikationsverbindung mit dem Prozessor
1. Das Schnittstellenmodul 1747-PIC am Prozessor und am Personalcomputer
anschließen.
2. Die Kommunikationsparameter der Software so einstellen, daß sie mit den
Vorgabewerten des Prozessors übereinstimmen:
DH-485
19,2 kBaud
Netzknotenadresse = 1
Störungssuche
Vor Beginn der Störungssuche am SLC 500-System sollten Sie ein Installations-
und Bedienungshandbuch für SLC 500-Steuerungen mit modularer
Hardware-Konfiguration (1747-6.2) von einer der auf Seite 16 aufgelisteten
Bezugsquellen anfordern. Beziehen Sie sich in diesem Handbuch auf das Kapitel
Störungssuche.
Zusätzlich zu dem o.g. Handbuch kann das Befehlssatz-Referenzhandbuch für
die Steuerungen SLC 500 und MicroLogix 1000 (1747-6.15DE) von den auf
Seite 16 aufgeführten Bezugsquellen angefordert werden. Dieses Handbuch
enthält Erläuterungen und Beispiele für den gesamten Befehlssatz sowie für alle
Statusworte und -bits. Auch werden alle möglicherweise in Statuswort S:6
enthaltenen Fehlercodes erläutert.
Allen-Bradley Replacements
34
Publikation 1747-5.25
Technische Daten
Spezifikation
SLC 5/01
(1747-L511, -L514)
SLC 5/02
(1747-L524)
Programmspeicher 1K oder 4K Befehlskapazität 4K Befehlskapazität
zusätzlicher
Datenspeicher
00
max. E/A-Kapazität
3940 diskrete Eingänge
3940 diskrete Ausgänge
4096 diskrete Eingänge
4096 diskrete Ausgänge
max. zentrale Chassis/
Steckplätze
3/30 3/30
Programmiersoftware RSLogix 500
t
, PLC–500 A.I. Series
t
, APS und HHT
Programmierbefehle 52 71
typische Abfragezeit
(1)
(1)
Die Abfragezeiten beziehen sich generell auf ein Kontaktplanprogramm (1 K), das aus einfacher
Strompfadlogik und Kommunikationsbefehlen besteht. Die tatsächlichen Abfragezeiten hängen
von der Programmgröße, den programmierten Befehlen und dem Kommunikationsprotokoll ab.
8 ms/K 4,8 ms/K
Bitausführung (XIC) 4
µ
s2,4
µ
s
Kommunikation Empfang Empfang oder Initiierung
DH-485 SLC 5/01
(1)
(1)
Für die Programmierung über den DH-485-Kanal ist ein Modul 1747-PIC erforderlich.
SLC 5/02
(1)
35
Publikation 1747-5.25
Die für die Prozessoren SLC 5/01 und SLC 5/02 verfügbaren
Speicher-Backup-Optionen sind in der folgenden Tabelle zusammengefaßt. Die
EEPROM- und UVPROM-Speichermodule ermöglichen die nichtflüchtige
Aufzeichnung.
Beschreibung Spezifikation
Netzteilbelastung bei 5 V DC 350 mA
Netzteilbelastung bei 24 V DC 105 mA
Aufrechterhaltung der Programmabfrage
nach Spannungsausfall
20 ms bis 3 s (je nach Netzteilbelastung)
Störfestigkeit NEMA-Standard ICS 2-230
Vibration Verschiebung: 0,381 mm, Spitze/Spitze bei 5-57 Hz
Beschleunigung: 2,5 Gs bei 57-2000 Hz
Stoßeinwirkung (während des Betriebs) 30 Gs
Umgebungstemperatur
während des Betriebs: 0 bis + 60
°
C
Lagertemperatur: -40
°
C bis 85
°
C
Luftfeuchtigkeit 5 bis 95%, ohne Kondensation
Amtliche Zulassungen
UL-Zertifizierung
CSA-Zulassung
Klasse 1, Gruppen A, B, C oder D, Abschnitt 2
Erfüllung der CE-Bestimmungen für alle
zutreffenden Richtlinien
Speicher-Backup-Option
SLC 5/01
(1747-L511/1747-L514)
SLC 5/02
(1747-L524)
EEPROM 1747-M1, 1747-M2 1747-M2
UVPROM 1747-M3, 1747-M4 1747-M4
Allen-Bradley Replacements
36
Publikation 1747-5.25
Handhabung, Lagerung und Transport der Batterie
(Best.-Nr. 1747-BA)
Handhabung
Lagerung
Lagern Sie die Lithiumbatterien in einer kühlen, trockenen Umgebung, am
besten bei +20° C bis +25° C, mit einer relativen Luftfeuchtigkeit von 40% bis
60%.
Transport
Eine oder zwei Batterien Innerhalb der USA können bis zu zwei Batterien
ohne Einschränkungen versandt werden. Die für den Versand innerhalb anderer
Länder bzw. in andere Länder geltenden Bestimmungen können anders lauten.
Drei oder mehr Batterien Die Regelung des Transports von drei oder mehr
Batterien innerhalb der USA wurde durch das Verkehrsministerium (Department
of Transportation) im sogenannten Code of Federal Regulations, Absatz CFR49,
“Transportation” festgelegt. In Ausnahmefällen ist der Transport von bestimmten
gefährlichen Feststoffen, die als brennbare Materialien klassifiziert sind, gemäß
der Regelung DOT-E7052 erlaubt. Aufgrund dieser Ausnahme können
Lithiumbatterien per Kraftfahrzeug, Bahn, Frachtschiff und Frachtflugzeug
transportiert werden, vorausgesetzt, daß bestimmte Bedingungen erfüllt werden.
Der Transport per Passagierflugzeug ist nicht gestattet.
Der Versand von verbrauchten Batterien unterliegt den jeweiligen Bestimmungen
des Landes oder den Bestimmungen des Internationalen Lufttransportverbands in
Genf (IATA-Regelung bezüglich des Versands von Gefahrengütern).
ACHTUNG: Die Batterien nicht öffnen, durchlöchern, zerdrücken oder auf sonstige
Weise beschädigen, da dies eine Explosion verursachen und/oder giftige, korrosive
und brennbare Flüssigkeiten freisetzen würde.
Die Batterien nicht laden, da dies zu einer Explosion oder Überhitzung mit
möglichen Verbrennungsfolgen führen könnte.
Wichtig:
Die auf den Transport von Lithiumbatterien zutreffenden
Bestimmungen werden von Zeit zu Zeit neu überarbeitet.
37
Publikation 1747-5.25
Batterien müssen zur Entsorgung verpackt werden und gemäß den zutreffenden
Vorschriften an die zuständige Entsorgungsstelle gesandt werden. In den USA
genehmigt das Verkehrsministerium (Department of Transportation) den Versand
von “Lithiumbatterien zum Zwecke der Entsorgung” ausschließlich per
Kraftfahrzeug in Bestimmung 173.1015 des sog. “Code of Federal Regulations”
(Inkrafttretung am 5. Januar 1983). Für weitere Informationen wenden Sie sich
bitte an die folgende Adresse:
U.S. Department of Transportation
Research and Special Programs Administration
400 Seventh Street, S.W.
Washington, D.C. 20590, USA
Obwohl das US-Ministerium für Umwelt zu diesem Zeitpunkt noch keine
Bestimmungen in bezug auf Lithiumbatterien erlassen hat, sollte das in den
Batterien enthaltene Material als giftig, reaktiv und korrosiv angesehen werden.
Die für die Entsorgung der in der Batterie enthaltenen Stoffe zuständige Person
ist für alle verursachten Gefahren verantwortlich. Im Zusammenhang mit der
Entsorgung dieser Stoffe gelten u.U. staatliche und örtliche Bestimmungen.
Ein Sicherheitsdatenblatt über Lithiumbatterien kann beim Hersteller angefordert
werden:
Sanyo Energy Corporation
600 Supreme Drive
Bensenville, IL 60106, USA
ACHTUNG: Lithiumbatterien nicht verbrennen oder in den Müll werfen, da sie
explodieren oder explosionsartig bersten können. Gehen Sie beim Sammeln von
Batterien zur Entsorgung vorsichtig vor, um Kurzschlüsse, Zusammendrücken oder
Beschädigen des Batteriemantels und der Abdichtung zu vermeiden.
Allen-Bradley Replacements
38
Publikation 1747-5.25
Notes:
Pubblicazione 1747-5.25
Processori modulari SLC 5/01 e
SLC 5/02
(Numeri di catalogo 1747-L511, 1747-L514,
1747-L524)
Istruzioni per l’installazione
Sezione italiana
Informazioni importanti per l’utente ................. 40
Per ulteriori informazioni ................................. 41
Strumenti ed apparecchiature necessari ......... 42
Considerazioni sulla sicurezza ........................ 42
Procedura di installazione ............................... 43
Individuazione dei guasti ................................. 45
Caratteristiche tecniche ................................... 46
Utilizzo, stoccaggio e trasporto della batteria (No. cat.
1747-BA) ......................................................... 48
pagina
All’interno...
Allen-Bradley Replacements
40
Pubblicazione 1747-5.25
Informazioni importanti per l’utente
Poiché i prodotti descritti in questa pubblicazione hanno molteplici usi, i
responsabili dell’applicazione e dell’utilizzo di questa apparecchiatura di
controllo devono accertarsi che sia stato fatto tutto il possibile per assicurare che
ogni applicazione ed ogni utilizzo siano conformi ai requisiti di prestazione e
sicurezza, ivi inclusi qualsiasi legge, regolamento, codice e standard pertinenti.
Le illustrazioni, gli schemi, i programmi campione e gli esempi di configurazioni
di questo manuale sono intesi esclusivamente ad illustrare il testo. A causa dei
numerosi requisiti e variabili propri di ciascuna installazione, la Allen-Bradley
declina ogni responsabilità (compresa la responsabilità per la proprietà
intellettuale) per l’uso dei prodotti basato sulle applicazioni illustrate in questa
pubblicazione.
La pubblicazione Allen-Bradley SGI-1.1, Safety Guidelines for the Application,
Installation, and Maintenance of Solid-State Control (Istruzioni di sicurezza per
l’applicazione, l’installazione e la manutenzione del controllo a stato solido),
disponibile presso il più vicino ufficio Allen-Bradley, descrive importanti
differenze, che si dovrebbero prendere in considerazione nell’applicazione di
prodotti quali quelli descritti in questa pubblicazione, esistenti tra le
apparecchiature allo stato solido ed i dispositivi elettromeccanici.
È proibita la riproduzione, completa o parziale, del contenuto di questa
pubblicazione protetta da copyright, salvo previa autorizzazione scritta della
Allen-Bradley Company, Inc.
In tutto questo manuale facciamo uso di note per attrarre l’attenzione su
considerazioni relative alla sicurezza:
I messaggi di Attenzione permettono di:
identificare un pericolo
evitare il pericolo
rendersi conto delle conseguenze
ATTENZIONE: evidenzia informazioni circa procedure o circostanze che possono
causare pericolo o morte a persone, danni alla proprietà o una perdita economica.
Importante:
identifica informazioni di basilare importanza per un’applicazione
corretta e per la comprensione del prodotto.
41
Pubblicazione 1747-5.25
Per ulteriori informazioni
Nell’ambito dell’impegno profuso per preservare, proteggere e migliorare il
nostro ambiente, la Allen-Bradley sta gradualmente riducendo la quantità di carta
utilizzata. Una minore quantità di carta significa maggiori opportunità per
l’utente. Oltre alle tradizionali pubblicazioni su carta, la Allen-Bradley offre ora
manuali in linea contenenti tutte le informazioni più aggiornate. Prima di avviare
il sistema di controllo si consiglia di leggere le pubblicazioni attinenti di seguito
elencate.
Pubblicazioni attinenti
Come ottenere maggiori informazioni
Se si desidera ricevere un manuale, è possibile:
scaricare una versione elettronica gratis da internet al sito:
www.theautomationbookstore.com
comprare un manuale stampato:
contattando il distributore locale o rappresentante della Rockwell
Automation
visitando il sito www.theautomationbookstore.com ed effettuando
l’ordinazione
telefonando al n.: 1.800.963.9548 (USA/Canada)
oppure al n.: 001.330.725.1574 (fuori degli Stati Uniti/Canada)
Per:
Fare riferimento alla seguente
pubblicazione
No. pub.
informazioni più dettagliate
sull’installazione e l’utilizzo del sistema
modulare SLC 500.
SLC 500 Modular Hardware Style
Installation and Operation
Manual
1747-6.2
un manuale di riferimento contenente
informazioni sui dati del file di stato, sul set
di istruzioni e sull’individuazione dei guasti.
SLC 500 and MicroLogix 1000
Instruction Set Reference Manual
1747-6.15
Un CD-ROM che contiene entrambi i
manuali elencati sopra, oltre a:
Manuale dell’utente dei moduli I/O
analogici SLC 500
Istruzioni per l’installazione dei moduli I/O
discreti
Dati relativi ai moduli I/O discreti
Letteratura sui SLC 500 su
CD-ROM
1747-CD1-1
Allen-Bradley Replacements
42
Pubblicazione 1747-5.25
Strumenti ed apparecchiature necessari
cacciavite a taglio medio
apparecchiatura di programmazione
interfaccia di comunicazione 1747-PIC, 1784-KTX o 1784-PCMK
Considerazioni sulla sicurezza
Per consigli generali sui requisiti relativi alla sicurezza dell’installazione e le
operazioni relative alla sicurezza, fare riferimento ai requisiti specifici della
regione in questione.
Europa: fare riferimento agli standard contenuti nella documentazione EN
60204 ed ai regolamenti nazionali vigenti.
Stati Uniti: fare riferimento alla documentazione NFPA 70E, Electrical
Safety Requirements for Employee Workplaces.
ATTENZIONE: non installare, rimuovere o collegare i moduli quando sono
alimentati. Non esporre i moduli del processore a superfici o altre aree che
potrebbero essere dotate di carica elettrostatica. Le cariche elettrostatiche possono
alterare o distruggere la memoria.
Importante:
per informazioni sul trattamento, lo stoccaggio ed il trasporto della
batteria, vedere pagina 23.
43
Pubblicazione 1747-5.25
Procedura di installazione
Installazione della batteria
Importante:
se il processore è dotato di batteria (per il processore SLC 5/01
(1747-L511) la batteria è opzionale), prima di installare il proces-
sore nello chassis assicurarsi che la batteria sia collegata. In tal
modo il processore viene fornito di backup della memoria in caso
di perdita di alimentazione del controllore.
1. Aprire lo sportello del processore.
2. Rimuovere il ponticello dalla presa del connettore della batteria. Conservare
il ponticello in un luogo sicuro per un eventuale utilizzo futuro senza la
batteria.
3. Inserire una batteria nuova o di ricambio nell’alloggiamento ed assicurarsi
che sia bloccata dalle linguette di ritenuta.
4. Inserire il connettore della batteria nella presa. Vedere la figura di seguito
riportata.
5. Chiudere lo sportello del processore.
Importante:
per informazioni sul trattamento, lo stoccaggio ed il trasporto della
batteria, vedere pagina 23.
+
Connettore
batteria
Conduttore
bianco
Conduttore
rosso
Lingurette
di ritenuta
Allen-Bradley Replacements
44
Pubblicazione 1747-5.25
Installazione del processore
Assicurarsi che il sistema non sia alimentato, quindi inserire il processore nello
slot 0 dello chassis 1746.
Alimentazione del processore
1. Alimentare lo chassis.
2. Controllare i LED dell’alimentatore dello chassis e del processore. Il LED
dell’alimentatore deve essere acceso, mentre il LED di errore del processore
deve lampeggiare.
Importante:
il processore modulare SLC 500t deve essere inserito nello slot di
sinistra (slot 0), come illustrato nella seguente figura. Una volta
installato il processore, rimuovere la fascetta protettiva.
Alimentatore
Fascetta protettiva
Guida della
scheda
Dispositivo di
sgancio del
processore
Indica che il LED è SPENTO.
Indaca che il LED è ACCESO.
Indica che il LED è LAMPEGGIANTE.
Lo stato del LED è irrilevante
LED dell’alimentatore e dei processori SLC 5/01 e SLC 5/02
RUN
CPU FAULT
FORCED I/O
BATTERY LOW
POWER
COMM
Il LED RUN del processore SLC 5/01 è
denominato PC RUN.” Inoltre, il
processore SLC 5/01 non ha il LED COMM.
45
Pubblicazione 1747-5.25
Caricamento del software
Fare riferimento alla documentazione sul software di programmazione.
Attivazione delle comunicazioni con il processore
1. Collegare l’interfaccia 1747-PIC al processore ed al PC.
2. Impostare i parametri di comunicazione del software in modo che
corrispondano ai parametri di default del processore:
DH-485
19,2 k baud
Indirizzo del nodo = 1
Individuazione dei guasti
Prima di procedere all’individuazione dei guasti del sistema SLC 500, procurarsi
una copia del manuale SLC 500 Modular Hardware Style Installation and
Operation Manual (1747-6.2) in uno dei modi illustrati alla pagina 16 e fare
riferimento al capitolo sull’individuazione dei guasti.
Oltre al suindicato manuale, è possibile ottenere anche il manuale SLC 500 and
MicroLogix 1000 Instruction Set Reference Manual (1747-6.15) seguendo la
medesima procedura illustrata alla pagina 16. Tale manuale contiene spiegazioni
ed esempi sull’intero set di istruzioni e su tutte le parole e i bit di stato, nonché su
tutti i codici di errore possibili individuati nella parola di stato S:6.
Allen-Bradley Replacements
46
Pubblicazione 1747-5.25
Caratteristiche tecniche
Caratteristica
SLC 5/01
(1747-L511, -L514)
SLC 5/02
(1747-L524)
Memoria del programma 1 K o 4 K di istruzioni 4 K di istruzioni
Memoria dati addizionale 0 0
Capacità di I/O massima
3940 ingressi discreti
3940 uscite discrete
4096 ingressi discreti
4096 uscite discrete
Chassis/slot locali
massimi
3/30 3/30
Software di
programmazione
RSLogix 500
t
, PLC–500 A.I. Series
t
, APS e HHT
Istruzioni di
programmazione
52 71
Tempo di scansione
tipico
(1)
(1)
I tempi di scansione sono tipici di un programma a logica ladder di 1 K, consistente in una logica
ladder semplice ed in un servizio di comunicazione. I tempi di scansione effettivi dipendono dalle
dimensioni del programma, dalle istruzioni utilizzate e dal protocollo di comunicazione.
8 ms/K 4,8 ms/K
Esecuzione dei bit (XIC) 4
µ
s2,4
µ
s
Comunicazione Ricezione
Ricezione o
Inizializzazione
DH-485 SLC 5/01
(1)
(1)
Per collegarsi al canale DH-485 per la programmazione è richiesta un’interfaccia 1747-PIC.
SLC 5/02
(1)
47
Pubblicazione 1747-5.25
La seguente tabella riassume le opzioni di backup della memoria disponibili per i
processori SLC 5/01 e SLC 5/02. I moduli di memoria EEPROM e UVPROM
forniscono un backup non–volatile della memoria.
Descrizione Caratteristica
Assorbimento di corrente a 5V cc 350 mA
Assorbimento di corrente a 24V cc 105 mA
Tempo di tenuta della scansione del
programma dopo una perdita di corrente
da 20 ms a 3 s (dipende dall’assorbimento di
corrente)
Immunità da rumori NEMA Standard ICS 2-230
Vibrazione
Ampiezza: 0,4 mm, piccopicco a 5-57 Hz
Accelerazione: 2,5G a 57-2000 Hz
Urto (in funzionamento) 30G
Temperatura ambientale
Funzionamento: da 0 a + 60
°
C (da 32
°
F a 140
°
F)
Stoccaggio: da -40
°
C a 85
°
C (da -40
°
F a 185
°
F)
Umidità da 5 a 95% senza condensa
Enti di certificazione
elencato in UL
approvato da CSA
Classe 1, Gruppi A, B, C o D, Divisione 2
conforme CE per tutte le direttive applicabili
Opzioni di backup della
memoria
SLC 5/01
(1747-L511/1747-L514)
SLC 5/02
(1747-L524)
EEPROM 1747-M1, 1747-M2 1747-M2
UVPROM 1747-M3, 1747-M4 1747-M4
Allen-Bradley Replacements
48
Pubblicazione 1747-5.25
Utilizzo, stoccaggio e trasporto della batteria (No. cat. 1747-BA)
Modalità di utilizzo
Modalità di stoccaggio
Conservare le batterie al litio in ambiente fresco e asciutto, con temperatura
compresa tra 20° C e 25° C (tra 68° F e 77° F) ed una umidità relativa compresa
tra 40% e 60%.
Modalità di trasporto
Una o due batterie: le norme statunitensi consentono il trasporto simultaneo di
un numero massimo di due baterie. Le normative in materia vigenti in altri paesi
possono essere diverse da quelle degli Stati Uniti.
Tre o più batterie: le norme statunitensi relative al trasporto di tre o più batterie
sono specificate dal DOT (Department of Transportation) nel Codice degli
Ordinamenti Federali, CFR49, “Trasporto”. Una clausola esonerativa da tali
norme, (DOT - E7052), prevede il trasporto di certi materiali pericolosi
classificati come solidi infiammabili. Tale clausola autorizza il trasporto di
batterie al litio su veicoli a motore, treni merce, navi ed aerei da carico, previo
soddisfacimento di certe condizioni. Non è consentito il trasporto di batterie in
aerei per il trasporto di persone.
Il trasporto di batterie esaurite per il loro smaltimento può essere soggetto alle
norme specifiche dei paesi interessati o ai regolamenti recepiti da tali paesi, quali
ad esempio le Restricted Articles Regulations dello IATA (International Air
Transport Association), Ginevra, Svizzera.
ATTENZIONE: non caricare la batteria. La batteria potrebbe esplodere, oppure le
pile potrebbero surriscaldarsi e causare gravi ustioni.
Non aprire, forare, rompere o danneggiare in altro modo la batteria. La batteria
potrebbe esplodere e/o potrebbero verificarsi fuoriuscite di liquidi tossici, corrosivi e
infiammabili.
Importante:
le normative per il trasporto delle batterie al litio vengono
periodicamente aggiornate.
49
Pubblicazione 1747-5.25
Le batterie da eliminare devono essere imballate e trasportate, in osservanza alle
norme vigenti, in un’appropriata area di smaltimento. Il Dipartimento dei
Trasporti degli Stati Uniti autorizza il trasporto su veicolo a motore di “batterie al
litio da eliminare” esclusivamente in osservanza all’ordinamento 173.1015 del
CFR 49 (in vigore dal 5 gennaio 1983). Per ulteriori informazioni, contattare il
seguente indirizzo:
U.S. Department of Transportation
Research and Special Programs Administration
400 Seventh Street, S.W.
Washington, D.C. 20590
Sebbene la Environmental Protection Agency (Agenzia per la protezione
ambientale) non contempli attualmente norme specifiche per le batterie al litio, i
materiali in esse contenuti potrebbero essere ritenuti tossici, reattivi o corrosivi.
La persona incaricata di provvedere allo smaltimento di tali materiali è
responsabile di qualsiasi danno causato nell’espletamento di tale procedura. È
possibile che esistano ordinamenti locali e statali concernenti lo smaltimento di
questi materiali.
Per un foglio illustrativo delle procedure di sicurezza relative ai materiali
contenuti nelle batterie al litio, contattare l’azienda produttrice:
Sanyo Energy Corporation
600 Supreme Drive
Bensenville, IL 60106
ATTENZIONE: le batterie al litio non devono essere bruciate né gettate nei comuni
raccoglitori di immondizia, in quanto potrebbero esplodere o spaccarsi. La raccolta
delle batterie destinate allo smaltimento deve essere eseguita in modo da evitare
corti circuiti, compattamenti o distruzione del contenitore e del sigillo ermetico.
Allen-Bradley Replacements
50
Pubblicazione 1747-5.25
Notes:
Procesadores modulares SLC 5/01
y SLC 5/02
(Números de catálogo 1747-L511, 1747-L514,
1747-L524)
Instrucciones de instalación
Sección en español
Información importante para el usuario .. 52
Para obtener más información ................ 53
Herramientas y equipo necesarios .......... 54
Consideraciones de seguridad ................ 54
Procedimiento de instalación .................. 55
Localización y corrección de fallos .......... 57
Especificaciones ..................................... 58
Manipulación, almacenamiento y transporte de la batería (Cat.
No. 1747-BA) ........................................... 60
paginaContenido
...
Allen-Bradley Replacements
52
1747-5.25
Información importante para el usuario
Debido a la variedad de usos de los productos descritos en esta publicación, las
personas responsables de la aplicación y uso de este equipo de control deben
asegurarse de que se hayan seguido todos los pasos necesarios para que cada
aplicación y uso cumpla con todos los requisitos de rendimiento y seguridad,
incluyendo leyes, reglamentos, códigos y normas aplicables.
Los ejemplos de ilustraciones, gráficos, programas y esquemas mostrados en esta
guía tienen la única intención de ilustrar el texto. Debido a las muchas variables
y requisitos asociados con cualquier instalación particular, Allen–Bradley no
puede asumir responsabilidad u obligación (incluyendo responsabilidad de
propiedad intelectual) por el uso real basado en los ejemplos mostrados en esta
publicación.
La publicación SGI-1.1 de Allen-Bradley, Safety Guidelines for the Application,
Installation, and Maintenance of Solid State Control (disponible en la oficina
local de Allen-Bradley), describe algunas diferencias importantes entre equipos
transistorizados y dispositivos electromecánicos, las cuales deben tomarse en
consideración al usar productos tales como los descritos en esta publicación.
Está prohibida la reproducción total o parcial del contenido de esta publicación
de propiedad exclusiva sin el permiso por escrito de Allen-Bradley Company,
Inc.
En estas instrucciones de instalación hacemos anotaciones para alertarle de
consideraciones de seguridad:
Las notas de “Atención” le ayudan a:
identificar un peligro
evitar un peligro
reconocer las consecuencias
ATENCION: Identifica información sobre prácticas o circunstancias que pueden
conducir a lesiones personales o la muerte, daños materiales o pérdidas
económicas.
Importante:
Identifica información especialmente importante para una aplicación
y un entendimiento correctos del producto.
53
1747-5.25
Para obtener más información
Como parte de nuestro esfuerzo para preservar, proteger y mejorar nuestro medio
ambiente, Allen-Bradley está reduciendo la cantidad de papel que usa. Menos
papel significa más opciones para usted. Además de las publicaciones impresas
tradicionales, ahora ofrecemos manuales en línea con la información más
actualizada disponible. Recomendamos que lea estas publicaciones relacionadas
listadas a continuación antes de encender el sistema de control.
Publicaciones relacionadas
Para obtener más información
Si quiere recibir un manual puede:
descargar una versión electrónica gratis de la siguiente dirección de
internet: www.theautomationbookstore.com
comprar un manual impreso. Para hacer esto haga una de las siguientes
cosas:
comuníquese con su distribuidor local o representante local de
Rockwell Automation
haga un pedido en la página electrónica:
www.theautomationbookstore.com
llame al: 1.800.963.9548 (USA/Canadá)
ó 001.330.725.1574 (Fuera de los EE.UU./Canadá)
Para Consulte este documento Pub. No.
Obtener una descripción más detallada de
cómo instalar y usar el sistema modular
SLC 500.
SLC 500 Modular Hardware
Style Installation and Operating
Manual
1747-6.2
Obtener un manual de referencia que
contenga información sobre los datos de
archivo de estado, conjunto de
instrucciones y localización y corrección
de fallos.
Manual del referencia del
conjunto de instrucciones SLC
500 y MicroLogix 1000
1747-6.15ES
Un CD-ROM con los dos manuales
indicados anteriormente, además de:
Manual del usuario de módulos de E/S
analógicas SLC 500
Instrucciones de instalación de módulos
de E/S discretas
Datos de productos - Módulos de E/S
discretas
Colección de información
impresa sobre el SLC 500 en
CD-ROM
1747-CD1-1
Allen-Bradley Replacements
54
1747-5.25
Herramientas y equipo necesarios
destornillador de hoja mediana
equipo de programación
interfaces de comunicación 1747-PIC, 1784-KTX ó 1784-PCMK
Consideraciones de seguridad
Para obtener recomendaciones generales referentes a requisitos de seguridad en
la instalación y prácticas de trabajo orientadas a aspectos de seguridad, consulte
los requisitos específicos para su región.
Europa: Consulte los estándares que se encuentran en EN 60204 y las
normas nacionales.
Estados Unidos: consulte NFPA 70E, Electrical Safety Requirements for
Employee workplaces.
ATENCION:
Nunca instale, retire o cablee los módulos mientras esté
conectada la alimentación eléctrica. Además, no exponga los módulos del
procesador a superficies u otras áreas que puedan usualmente contener carga
electrostática. Las cargas electrostáticas pueden alterar o destruir la memoria.
Importante:
Vea la página 23 para obtener información sobre tratamiento
adecuado de baterías, almacenamiento y transporte.
55
1747-5.25
Procedimiento de instalación
Instalación de la batería
1. Abra la puerta del procesador.
2. Retire el puente del conector de la batería. Guarde el puente en un lugar
seguro para un posible uso futuro sin la batería.
3. Inserte una batería nueva o de repuesto en el sujetador asegurándose de que
quede sujeta con las abrazaderas de retención.
4. Conecte el conector de la batería dentro del conector. Vea la siguiente
figura.
5. Cierre la puerta del procesador.
Importante:
Si su procesador tiene una batería— la batería es una opción para el
procesador SLC 5/01 (1747-L511) — asegúrese de que esté
conectada antes de instalar el procesador dentro del chasis. Esto
proporciona memoria de seguridad (backup) para su procesador en
caso de que falle el suministro de alimentación eléctrica al
controlador.
Importante:
Vea la página 23 para obtener información sobre tratamiento
adecuado de baterías, almacenamiento y transporte.
+
Cable
blanco
Cable
rojo
Conector de
la bateria
Abrazaderas
de retención
Allen-Bradley Replacements
56
1747-5.25
Instalación del procesador
Asegúrese de que la alimentación eléctrica del sistema esté deconectada; luego
inserte el procesador en la ranura 0 del chasis 1746.
Conecte la alimentación eléctrica al procesador
1. Energize la fuente de alimentación eléctrica del chasis.
2. Revise los indicadores LED de la fuente de alimentación eléctrica y del
procesador. El indicador LED de power (alimentación eléctrica) en la fuente
de alimentación eléctrica debe estar encendido y el indicador LED de fault
(fallo) en el procesador debe estar parpadenado.
Importante:
Los procesadores modulares SLC 500t deben insertarse en la ranura
izquierda (ranura 0), como se muestra a continuación.
Adicionalmente, retire la cubierta protectora después de instalar el
procesador.
Fuente de alimentación
eléctrica
Guia de tarjetas
Cubierta protectora
Desenganche del
procesador
Indicadores LED de la fuente de alimentacion
electrica y de SLC 5/01 y SLC 5/02
Indica que el LED esta APAGADO.
Indica que el LED esta ENCENDIDO.
Indica que el LED esta PARPADEANDO.
El estado del LED no interesa.
El indicador LED de RUN en el procesador
SLC 5/01 esta marcado comoPC RUN.”
Tambien, el procesador SLC 5/01 no tiene un
indicador LED de COMUNICACION.
RUN
CPU FAULT
FORCED I/O
BATTERY LOW
POWER COMM
57
1747-5.25
Para cargar el software
Consulte la documentación del software de programación.
Para establecer comunicaciones con el procesador
1. Conecte el 1747-PIC al procesador y a su computadora personal.
2. Configure los parámetros de comunicación del software de manera que sean
iguales a los parámetros predeterminados del procesador:
DH-485
19.2k baud
Dirección de nodo = 1
Localización y corrección de fallos
Antes de localizar y corregir fallos del sistema SLC 500, por favor consiga un
Manual de instalación y operación del hardware estilo modular SLC 500
(1747-6.2) de uno de los proveedores listados en la página 16. Consulte el
capítulo de Localización y corrección de fallos.
Además del Manual de instalación y operación del hardware estilo modular SLC
500, también se puede obtener el Manual de referencia del conjunto de
instrucciones SLC 500 y MicroLogix 1000 (1747-6.15ES) de los proveedores
listados en la página 16. Este manual contiene explicaciones y ejemplos para el
todo el conjunto de instrucciones así como para todas las palabras y bits de
estado. También contiene explicaciones para todos los posibles códigos de fallo
que se encuentran en la palabra de estado S:6.
Allen-Bradley Replacements
58
1747-5.25
Especificaciones
Especificación
SLC 5/01
(1747-L511, -L514)
SLC 5/02
(1747-L524)
Memoria de programa Instrucciones 1K ó 4K Instrucciones 4K
Almacenamiento
adicional de datos
00
Capacidad máxima de E/
S
3940 entradas discretas
3940 salidas discretas
4096 entradas discretas
4096 salidas discretas
Máx. de ranuras/chasis
locales
3/30 3/30
Software de
programacn
RSLogix 500
t
, PLC-500 A.I. Series
t
, APS y HHT
Instrucciones de
programacn
52 71
Tiempo de escán típico
(1)
(1)
Los tiempos de escán son típicos para un programa de lógica de escalera de 1k que consiste de
una lógica de escalera simple y servicio de comunicación. Los tiempos de escán reales dependen
del tamaño del programa, instrucciones usadas y el protocolo de comunicación.
8 ms/K 4.8 ms/K
Ejecución de bit (XIC) 4
µ
s2.4
µ
s
Comunicación Recepción Recepción o iniciación
DH-485 SLC 5/01
(1)
(1)
Se necesita un 1747-PIC al conectarse con el canal DH-485 para programación.
SLC 5/02
(1)
59
1747-5.25
La siguiente tabla resume las opciones de memoria de seguridad (back up)
disponibles para los procesadores SLC 5/01 y SLC 5/02. Los módulos de
memoria EEPROM y UVPROM proporcionan una memoria de seguridad (back
up) no volátil.
Descripción Especificación
Carga de fuente de alimentación eléctrica
a 5 VCC
350 mA
Carga de fuente de alimentación eléctrica
a 24 VCC
105 mA
Tiempo de retención del escán de
programa después de pérdida de
alimentación eléctrica
20 ms a 3 s (dependiendo de la carga de la fuente
de alimentación eléctrica)
Inmunidad al ruido Estándar NEMA ICS 2-230
Vibración
Desplazamiento: 0.015 pulgadas, pico a pico a
5-57 Hz
Aceleración: 2.5 Gs at 57-2000 Hz
Choque (operativo) 30 Gs
Límites de temperatura ambiente
Operativo: 0 a + 60
°
C (32
°
F a 140
°
F)
Almacenamiento: -40
°
C a 85
°
C (-40
°
F a 185
°
F)
Humedad 5 a 95% sin condensación
Certificación de agencia
Listado UL
Aprobación CSA
Clase 1, Grupos A, B, C o D, División 2
Cumple con todas las directivas aplicables de la
CE
Opción de memoria de
seguridad (back up)
SLC 5/01
(1747-L511/1747-L514)
SLC 5/02
(1747-L524)
EEPROM 1747-M1, 1747-M2 1747-M2
UVPROM 1747-M3, 1747-M4 1747-M4
Allen-Bradley Replacements
60
1747-5.25
Manipulación, almacenamiento y transporte de la batería
(Cat. No. 1747-BA)
Manipulación
Almacenamiento
Almacene las baterías de litio en un ambiente fresco y seco, típicamente entre
+20° C a +25° C (+68° F a +77° F) y 40% a 60% de humedad relativa.
Transporte
Una o dos baterías Se pueden enviar hasta dos baterías juntas dentro de los
Estados Unidos sin restricciones. Las normas que gobiernan el transporte a otros
países y dentro de otros países pueden ser diferentes.
Tres o más baterías — Los procedimientos para el transporte de tres o más
baterías enviadas juntas dentro de los Estados Unidas están especificados por el
Departamento de Transporte (DOT) en el Código de reglamentos federales ,
CFR49, “Transporte”. Una excepción a este reglamento, DOT - E7052, cubre el
transporte de ciertos materiales peligrosos clasificados como sólidos inflamables.
Esta excepción autoriza el transporte de baterías de litio en vehículos
motorizados, vagones de carga, barcos de carga y aviones de carga solamente,
siempre y cuando se cumplan ciertas condiciones. No se permite el transporte en
aviones de pasajeros.
El transporte de baterías agotadas para desecho puede estar sujeto a reglamentos
específicos de los países envueltos o reglamentos aprobados por esos países, tales
como los Reglamentos de artículos restringidos IATA de la Asociación de trans-
porte aéreo internacional, Ginebra, Suiza.
Importante:
Los reglamentos para el transporte de baterías de litio se revisan
periódicamente.
ATENCION: No cargue las baterías. Una explosión podría producirse o las celdas
se podrían recalentar y causar quemaduras.
No abra, haga agujeros, golpee ni de alguna manera mutile las baterías. Puede
producirse una explosión y/o quedarían expuestos líquidos tóxicos, corrosivos e
inflamables.
61
1747-5.25
-
Para el desecho, las baterías deben ser empacadas y enviadas de acuerdo con los
reglamentos de transporte, a un local de desecho adecuado. El Departamento de
transporte de los EE.UU. autoriza el transporte de “Baterías de litio para
desecho” en vehículos motorizados sólo en el reglamento 173.1015 de CFR 49
(vigente a partir del 5 de enero de 1983). Para obtener más información
comuníquese con:
U.S. Department of Transportation
Research and Special Programs Administration
400 Seventh Street, S.W.
Washington, D.C. 20590
Si bien la Agencia para la protección del medio ambiente en este momento no
tiene reglamentos específicos referentes a las baterías de litio, el material
contenido puede considerarse tóxico, reactivo o corrosivo. La persona que está
desechando el material es responsable por los peligros creados como resultado de
hacerlo. Pueden existir reglamentos estatales y locales referentes al desecho de
estos materiales.
Para obtener una hoja de datos de seguridad para materiales de baterías de litio,
comuníquese con el fabricante:
Sanyo Energy Corporation
600 Supreme Drive
Bensenville, IL 60106
ATENCION: No incinere ni deseche las baterías de litio en tiraderos de basura
generales. Es posible que se produzcan explosiones o rupturas violentas. Las
baterías deben ser recogidas para desecho de una manera que se evite el corto
circuito, la compactación o la destrucción de la integridad de la caja y sello
hermético.
Allen-Bradley Replacements
Publication 1747-5.25 - June 1999 PN 40072-038-01 (B)
Supersedes Publication 1747-5.25 - December 1996 © 1999 Rockwell International Corporation. All rights reserved. Printed in the U.S.A.

Transcripción de documentos

SLC 5/01™ and SLC 5/02™ Modular Processors (Catalog Numbers 1747-L511, 1747-L514, 1747-L524) Installation Instructions Inside... page English Section . . . . . . . . . . . . . . . . 3 Section en francais . . . . . . . . . . . . . 15 Deutscher Abschnitt . . . . . . . . . . . . 27 Sezione italiana . . . . . . . . . . . . . . . 39 Sección en español . . . . . . . . . . . . 51 Allen-Bradley Replacements SLC 5/01™ and SLC 5/02™ Modular Processors (Catalog Numbers 1747-L511, 1747-L514, 1747-L524) Installation Instructions English Section Inside... page Important User Information . . . . . . . . .4 For More Information . . . . . . . . . . . . 5 Required Tools and Equipment . . . . 6 Safety Considerations . . . . . . . . . . . 6 Installation Procedure . . . . . . . . . . . 7 Troubleshooting . . . . . . . . . . . . . . . . 9 Specifications . . . . . . . . . . . . . . . . . 10 Battery Handling, Storing, and Transporting (Cat. No. 1747-BA) . . 12 4 Important User Information Because of the variety of uses for the products described in this publication, those responsible for the application and use of this control equipment must satisfy themselves that all necessary steps have been taken to assure that each application and use meets all performance and safety requirements, including any applicable laws, regulations, codes and standards. The illustrations, charts, sample programs and layout examples shown in this guide are intended solely for purposes of example. Since there are many variables and requirements associated with any particular installation, Allen-Bradley does not assume responsibility or liability (to include intellectual property liability) for actual use based upon the examples shown in this publication. Allen-Bradley publication SGI-1.1, Safety Guidelines for the Application, Installation, and Maintenance of Solid-State Control (available from your local Allen-Bradley office), describes some important differences between solid-state equipment and electromechanical devices that should be taken into consideration when applying products such as those described in this publication. Reproduction of the contents of this copyrighted publication, in whole or in part, without written permission of Allen-Bradley Company, Inc., is prohibited. Throughout these installation instructions we use notes to make you aware of safety considerations:  ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage or economic loss Attention statements help you to: • identify a hazard • avoid the hazard • recognize the consequences Important: Identifies information that is critical for successful application and understanding of the product. Publication 1747-5.25 Allen-Bradley Replacements 5 For More Information As part of our effort to preserve, protect, and improve our environment, Allen-Bradley is reducing the amount of paper we use. Less paper means more options for you. In addition to traditional printed publications and CD-ROM versions, we now offer on-line manuals with the most up-to-date information you can get. We recommend that you read the related publications listed below before starting up your control system. Related Publications For Refer to this Document Pub. No. A more detailed description on how to install and use your modular SLC 500 system. SLC 500 Modular Hardware Style Installation and Operation Manual 1747-6.2 A reference manual that contains status file data, instruction set, and troubleshooting information. SLC 500 and MicroLogix 1000 Instruction Set Reference Manual 1747-6.15 A CD–ROM containing both of the manuals listed above, plus the: •SLC 500 Analog I/O Modules User Manual •Discrete I/O Modules Installation Instructions •Discrete I/O Modules Product Data SLC 500 Literature Collection on CD–ROM 1747-CD1-1 If you would like a manual, you can: • download a free electronic version from the internet: www.theautomationbookstore.com • purchase a printed manual by: — contacting your local distributor or Rockwell Automation representative — visiting www.theautomationbookstore.com and placing your order — calling 1.800.963.9548 (USA/Canada) or 001.330.725.1574 (Outside USA/Canada) Publication 1747-5.25 6 Required Tools and Equipment • medium blade screwdriver • programming equipment • a 1747-PIC, 1784-KTX, or 1784-PCMK communication interfaces Safety Considerations  ATTENTION: Never install, remove, or wire any module while power is applied. Also, do not expose processor modules to surfaces or other areas that may typically hold an electrostatic charge. Electrostatic charges can alter or destroy memory. For general recommendations concerning installation safety requirements and safety related work practices, refer to the requirements specific to your region. • Europe: Reference the standards found in EN 60204 and your national regulations. • United States: refer to NFPA 70E, Electrical Safety Requirements for Employee Workplaces. Important: See page 10 for information on proper battery handling, storage, and transporting. Publication 1747-5.25 Allen-Bradley Replacements 7 Installation Procedure Install the Battery Important: If your processor has a battery— the battery is an option for the SLC 5/01 (1747-L511) processor — make sure it is connected before installing your processor into the chassis. This provides memory backup for your processor should the controller power supply fail. 1. Open the door of the processor. 2. Remove the jumper from the battery connector socket. Store the jumper in a safe place for possible future use without the battery. 3. Insert a new or replacement battery in the holder making sure it is held in by the retainer clips. 4. Plug the battery connector into the socket. See the figure below. White Lead Battery Connector Red Lead Retainer Clips + 5. Close the processor door. Important: See page 10 for information on proper battery handling, storage, and transporting. Publication 1747-5.25 8 Install the Processor Make sure system power is off; then insert the processor into slot 0 of the 1746 chassis. Important: The SLC 500t Modular Processors must be inserted into the left slot (slot 0), as shown below. In addition, remove the protective wrap after installing the processor. Power Supply Processor Release Card Guide Protective Wrap Apply Power to the Processor 1. Energize the chassis power supply. 2. Check the chassis power supply and processor LEDs. The power LED on the power supply should be on and the fault LED on the processor should be flashing. Indicates the LED is OFF. POWER COMM RUN CPU FAULT FORCED I/O BATTERY LOW Indicates the LED is ON. Indicates the LED is FLASHING. Status of LED does not matter. The RUN LED on the SLC 5/01 processor is actully labeled “PC RUN.” Also, the SLC 5/01 processor does not have a COMM LED. Publication 1747-5.25 Allen-Bradley Replacements 9 Load Your Software Refer to your programming software documentation. Establish Communications with the Processor 1. Connect the 1747-PIC to the processor and your personal computer. 2. Set the communication parameters of the software to match the default parameters of the processor: — DH-485 — 19.2k baud — Node Address = 1 Troubleshooting Before troubleshooting your SLC 500 system, please obtain an SLC 500 Modular Hardware Style Installation and Operation Manual (1747-6.2) from one of the sources listed on page 3. Refer to the chapter on Troubleshooting. In addition to the SLC 500 Modular Hardware Style Installation and Operation Manual, the SLC 500 and MicroLogix 1000 Instruction Set Reference Manual (1747-6.15) may also be obtained from the sources listed on page 3. This manual contains explanations and examples for the entire instruction set as well as for all status words and bits. It also contains explanations for all possible fault codes found in status word S:6. Publication 1747-5.25 10 Specifications SLC 5/01 (1747-L511, -L514) Specification SLC 5/02 (1747-L524) Program Memory 1K or 4K Instructions 4K Instructions Additional Data Storage 0 0 Maximum I/O Capacity 3940 discrete inputs 3940 discrete outputs 4096 discrete inputs 4096 discrete outputs Max. Local Chassis/Slots 3/30 3/30 Programming Software RSLogix 500™ , PLC– 500 A.I. Series™ , APS, and HHT Programming Instructions 52 71 Typical Scan Time(1) 8 ms/K 4.8 ms/K Bit Execution (XIC) 4 µs 2.4 µs (1) The scan times are typical for a 1K ladder logic program consisting of simple ladder logic and communication servicing. Actual scan times depend on your program size, instuctions used, and the communication protocol. Communication DH-485 (1) Receive SLC 5/01(1) Receive or Initiate SLC 5/02(1) A 1747-PIC is required when connecting to the DH-485 channel for programming. Publication 1747-5.25 Allen-Bradley Replacements 11 Description Specification Power Supply Loading at 5V dc 350 mA Power Supply Loading at 24V dc 105 mA Program Scan Hold-up Time after Loss of Power 20 ms to 3 s (dependent on power supply loading) Noise Immunity NEMA Standard ICS 2-230 Vibration Displacement: 0.015 inch, peak-to-peak at 5-57 Hz Acceleration: 2.5Gs at 57-2000 Hz Shock (operating) 30Gs Ambient Temperature Rating Operating: 0 to + 60°C (32°F to 140°F) Storage: 40°C to 85°C (-40°F to 185°F) Humidity 5 to 95% without condensation Agency Certification UL listed CSA approved Class 1, Groups A, B, C or D, Division 2 CE compliant for all applicable directives The following table summarizes the available memory back up options for the SLC 5/01 and SLC 5/02 processors. EEPROM and UVPROM memory modules provide non-volatile memory back-up. Memory Back Up Option SLC 5/01 (1747-L511/1747-L514) SLC 5/02 (1747-L524) EEPROM 1747-M1, 1747-M2 1747-M2 UVPROM 1747-M3, 1747-M4 1747-M4 Publication 1747-5.25 12 Battery Handling, Storing, and Transporting (Cat. No. 1747-BA) Handling  ATTENTION: Do not charge the batteries. An explosion could result or the cells could overheat causing burns. Do not open, puncture, crush, or otherwise mutilate the batteries. An explosion may result and/or toxic, corrosive, and flammable liquids would be exposed. Storing Store the lithium batteries in a cool, dry environment, typically +20° C to +25° C (+68° F to +77° F) and 40% to 60% relative humidity. Transporting One or Two Batteries — Up to two batteries can be shipped together within the United States without restriction. Regulations governing shipment to or within other countries may differ. Three or More Batteries — Procedures for the transportation of three or more batteries shipped together within the United States are specified by the Department of Transportation (DOT) in the Code of Federal Regulations, CFR49, “Transportation.” An exemption to these regulations, DOT - E7052, covers the transport of certain hazardous materials classified as flammable solids. This exemption authorizes transport of lithium batteries by motor vehicle, rail freight, cargo vessel, and cargo-only aircraft, providing certain conditions are met. Transport by passenger aircraft is not permitted. Shipment of depleted batteries for disposal may be subject to specific regulation of the countries involved or to regulations endorsed by those countries, such as the IATA Restricted Articles Regulations of the International Air Transport Association, Geneva, Switzerland. Important:Regulations for transportation of lithium batteries are periodically revised. Publication 1747-5.25 Allen-Bradley Replacements 13  ATTENTION: Do not incinerate or dispose of lithium batteries in general trash collection. Explosion or violent rupture is possible. Batteries should be collected for disposal in a manner to prevent against short circuiting, compacting, or destruction of case integrity and hermetic seal. For disposal, batteries must be packaged and shipped in accordance with transportation regulations, to a proper disposal site. The U.S. Department of Transportation authorizes shipment of “Lithium batteries for disposal” by motor vehicle only in regulation 173.1015 of CFR 49 (effective January 5, 1983). For additional information contact: U.S. Department of Transportation Research and Special Programs Administration 400 Seventh Street, S.W. Washington, D.C. 20590 Although the Environmental Protection Agency at this time has no regulations specific to lithium batteries, the material contained may be considered toxic, reactive, or corrosive. The person disposing of the material is responsible for any hazard created in doing so. State and local regulations may exist regarding the disposal of these materials. For a lithium battery material safety data sheet, contact the manufacturer: Sanyo Energy Corporation 600 Supreme Drive Bensenville, IL 60106 Publication 1747-5.25 Processeurs modulaires SLC 5/01™ et SLC 5/02™ (Références 1747-L511, 1747-L514, 1747-L524) Notice d’installation Section en francais Contenu... page Informations utilisateur ............................ 16 Complément d’informations .................... 17 Outils et équipement requis .................... 18 Considérations de sécurité ...................... 18 Procédure d’installation ........................... 19 Dépannage .............................................. 21 Spécifications .......................................... 22 Manipulation, stockage et transport de piles (Réf. 1747-BA) ........................................ 24 Allen-Bradley Replacements 16 Informations utilisateur En raison de la diversité des utilisations des produits décrits dans le présent manuel, les personnes responsables de l’équipement doivent s’assurer que toutes les mesures ont été prises pour que l’application et l’utilisation des produits soient conformes aux exigences de performance et de sécurité, ainsi qu’aux lois, règlements, codes et normes en vigueur. Les illustrations, schémas et exemples de programmes contenus dans ce manuel sont présentés à titre indicatif seulement. En raison des nombreuses variables et impératifs associés à chaque installation, la société Allen-Bradley ne saurait être tenue pour responsable ou redevable (y compris en matière de propriété intellectuelle) des suites d’utilisation réelle basée sur les exemples et schémas présentés dans ce manuel. La publication SGI-1.1, Safety Guidelines for the Application, Installation, and Maintenance of Solid-State Control (disponible auprès de votre agence commerciale Allen-Bradley) décrit certaines différences importantes entre les équipements électroniques et les équipements électromécaniques qui devront être prises en considération lors de l’application de ces produits comme indiqué dans la présente publication. Toute reproduction partielle ou totale du présent manuel sans autorisation écrite de la société Allen-Bradley est interdite. Des remarques sont utilisées tout au long de ce manuel pour attirer votre attention sur les mesures de sécurité à prendre en compte :  ATTENTION: Indique les informations sur les pratiques ou circonstances pouvant entraîner des dommages corporels, dégâts matériels ou pertes financières. Les encarts Attention vous aident à : • identifier un danger • éviter un danger • discerner les conséquences Important: Indique les informations déterminantes pour la bonne compréhension et application du produit. Publication 1747-5.25 17 Complément d’informations Dans le cadre des efforts de protection, de sauvegarde et d’amélioration de l’environnement, Allen-Bradley réduit la quantité de papier utilisé. Moins de papier, c’est aussi un plus grand choix pour les utilisateurs : outre les publications imprimées traditionnelles et versions sur CD-ROM, nous vous offrons maintenant des manuels en ligne comportant les informations les plus récentes. Nous vous recommandons de lire les publications associées, énumérées ci-dessous, avant de lancer votre système de commande. Publications associées Pour Voir ce document Réf. Une description plus détaillée de l’installation et de l’utilisation de votre système modulaire SLC 500. SLC 500 Modular Hardware Style Installation and Operation Manual 1747-6.2 Un manuel de référence comportant des informations sur les données du fichier d’état, le jeu d’instructions et le dépannage. Manuel de référence et de jeu d’instructions SLC 500 et MicroLogix 1000 1747-6.15FR Ensemble des manuels SLC 500 sur CD-ROM 1747-CD1-1 Un CD-ROM contenant les manuels énumérés ci-dessus plus : •Manuel d’utilisation des modules d’E/S analogiques SLC 500 •Notice d’installation des modules d’E/S TOR •Description produit des modules d’E/S TOR Comment obtenir plus d’informations Pour vous procurer un manuel, vous pouvez : • le charger gratuitement depuis le site Internet : www.theautomationbookstore.com • acheter un manuel imprimé. Pour cela : — contactez votre distributeur local Rockwell Automation — visitez www.theautomationbookstore.com et commandez-le en ligne — appelez le 1.800.963.9548 (USA/Canada) ou le 001.330.725.1574 (hors USA/Canada) Publication 1747-5.25 Allen-Bradley Replacements 18 Outils et équipement requis • un tournevis plat de taille moyenne • un équipement de programmation • une interface de communication 1747-PIC, 1784-KTX ou 1784-PCMK Considérations de sécurité  ATTENTION: Ne jamais installer, retirer ou câbler un module sous tension. N’exposez pas les modules processeurs aux surfaces ou autres zones généralement soumises à des charges électrostatiques. Les charges électrostatiques peuvent endommager ou détruire la mémoire. Pour connaître les recommandations générales relatives aux impératifs de sécurité d’installation et de protection des postes de travail, reportez-vous aux normes en vigueur dans votre région. • Europe : Référence aux normes EN 60204 et aux réglementations nationales. • Etats–Unis : Référence au NFPA 70E, « Electrical Safety Requirements for Employee Workplaces ». Important: Pour plus d’informations sur la manipulation, le stockage et le transport des piles, reportez-vous à la page 23. Publication 1747-5.25 19 Procédure d’installation Installation de la pile Important: Si votre processeur est équipé d’une pile — la pile est une option du processeur SLC 5/01 (1747-L511) — assurez-vous qu’elle est connectée avant d’installer le processeur dans le châssis. La pile assure la sauvegarde de la mémoire en cas de coupure de courant de votre processeur. 1. Ouvrez la porte du processeur. 2. Retirez le cavalier de la fiche du connecteur de la pile. Conservez le cavalier dans un endroit sûr afin de pouvoir l’utiliser ultérieurement sans la pile. 3. Insérez une nouvelle pile ou une pile de rechange dans le support en veillant à ce qu’elle soit retenue par les clips de blocage. 4. Branchez le connecteur de la pile dans la fiche. Voir figure ci-dessous. Fil blanc Fil rouge Connecteur de la pile Clips de blocage + 5. Refermez la porte du processeur. Important: Pour plus d’informations sur la manipulation, le stockage et le transport des piles, reportez-vous à la page 23. Publication 1747-5.25 Allen-Bradley Replacements 20 Installation du processeur Assurez-vous que l’alimentation est hors tension, puis insérez le processeur dans l’emplacement 0 du châssis 1746. Important: Les processeurs modulaires SLC 500t doivent être insérés dans l’emplacement de gauche (emplacement 0), comme illustré ci-dessous. Retirez la bande de protection après avoir installé le processeur. Alimentation Loquet du processor Guide-carte Bande de protection Mise sous tension du processeur 1. Mettez l’alimentation du châssis sous tension. 2. Surveillez les LED de l’alimentation et du processeur. La LED « POWER » de l’alimentation doit être allumée et la LED d’erreur du processeur doit clignoter. POWER COMM RUN CPU FAULT FORCED I/O BATTERY LOW Indique que la LED est éteinte. Indique que la LED est allumée. Indique que la LED clignote. L’etat de la LED n’a pas d’importance La LED RUN du processeur SLC 5/01 est appelée PC RUN. Le processeur SLC 5/ 01 n’a pas de LED COMM. Publication 1747-5.25 21 Chargement de votre logiciel Réferez-vous à la documentation de votre logiciel de programmation. Establissement des communications avec le processeur 1. Connectez le 1747-PIC au processeur et à votre ordinateur personnel. 2. Définissez les paramètres de communication du logiciel en fonction des paramètres par défaut du processeur : • DH-485 • 19,2 kbauds • Adresse de poste = 1 Dépannage Avant de commencer à dépanner votre système SLC 500, veuillez vous procurer le Manuel d’installation et de fonctionnement des SLC 500 modulaires (1747-6.2) auprès d’une des sources de documentation présentées en page 16. Référez-vous au chapitre relatif au dépannage. Outre le manuel précité, le Manuel de référence et jeu d’instructions du SLC 500 et du MicroLogix 1000 (1747-6.15FR) peut également être obtenu auprès des sources de documentation présentées en page 16. Ce manuel comporte des explications et exemples pour l’ensemble du jeu d’instructions ainsi que pour tous les mots et bits d’états. Il comporte également les explications de tous les codes d’erreur possibles contenus dans le mot d’état S:6. Publication 1747-5.25 Allen-Bradley Replacements 22 Spécifications SLC 5/01 (1747-L511, -L514) Spécification SLC 5/02 (1747-L524) Mémoire programme 1 K ou 4 K instructions 4 K instructions Stockage de données sup. 0 0 Capacité d’E/S maximum 3940 entrées TOR 3940 sorties TOR 4096 entrées TOR 4096 sorties TOR Nbre maxi de châssis locaux/emplacements 3/30 3/30 Logiciel de programmation RSLogix 500t, PLC-500 A.I. Seriest, APS et HHT Instructions de programmation 52 71 Durée de scrutation type(1) 8 ms/K 4,8 ms/K Exécution de bit (XIC) 4 µs 2,4 µs (1) Les durées de scrutation sont généralement calculées pour un programme de logique à relais 1 K composé d’une logique à relais simple et du traitement des communications. Les durées de scrutations réelles dépendent de la taille de votre programme, des instructions utilisées et du protocole de communication. Communication DH-485 (1) Réception SLC 5/01(1) Réception ou envoi SLC 5/02(1) Un 1747-PIC est nécessaire pour la connexion de la voie DH-485 à des fins de programmation. Publication 1747-5.25 23 Description Spécification Intensité de l’alimentation à 5 V c.c. 350 mA Intensité de l’alimentation à 24 V c.c. 105 mA Temps de maintien de la scrutation du programme après perte d’aliementation de 20 ms à 3 s (selon l’intensité de l’alimentation) Immunité au bruit Norme NEMA ICS 2-230 Résistance aux vibrations Déplacement : 0,015 in, crête à crête à 5-57 Hz Accélération : 2,5 G à 57-2000 Hz Tenue aux chocs (en service) 30 G Plage des températures En fonctionnement : de 0 à + 60 °C (de 32 °F à 140 °F) Stockage : de 40 °C à 85 °C (de -40 °F à 185 °F) Humidité ambiante de 5 à 95 % sans condensation Homologation Listé UL Approuvé CSA Classe 1, Groupes A, B, C ou D, Division 2 Conforme CE pour toutes les directives en vigueur Le tableau suivant résume les options de mémoire de sauvegarde disponibles pour les processeurs SLC 5/01 et SLC 5/02. Les modules mémoire EEPROM et UVPROM assurent une sauvegarde de la mémoire non volatile. Option de sauvegarde de la mémoire SLC 5/01 (1747-L511/1747-L514) SLC 5/02 (1747-L524) EEPROM 1747-M1, 1747-M2 1747-M2 UVPROM 1747-M3, 1747-M4 1747-M4 Publication 1747-5.25 Allen-Bradley Replacements 24 Manipulation, stockage et transport de piles (Réf. 1747-BA) Manipulation  ATTENTION: Ne pas ouvrir, percer, écraser ou détériorer les piles. Une explosion pourrait se produire et/ou exposer des substances inflammables, corrosives et toxiques. Ne pas recharger les piles. Une explosion pourrait se produire et la surchauffe des éléments de la pile pourrait provoquer des brûlures. Stockage Stockez les piles au lithium dans un endroit sec et frais, entre +20° C et +25° C (+68° F et +77° F) et une humidité ambiante comprise entre 40 % et 60 %. Transport Une ou deux piles — Vous pouvez envoyer jusqu’à deux piles à l’intérieur des Etats-Unis sans aucune restriction. Les réglementations relatives à l’expédition peuvent varier d’un pays à l’autre. Trois piles ou plus — Les procédures de transport de trois piles ou plus à l’intérieur des Etats-Unis sont spécifiées par le Ministère américain des transports (Department of Transportation - DOT) dans le code des réglementations fédérales (Code of Federal Regulations), CFR49, « Transportation ». Certains matériaux classés comme solides inflammables bénéficient d’une exemption DOT - E7052 à cette réglementation. Cette exemption autorise le transport des piles au lithium par véhicule à moteur, frêt ferrovière, maritime et avion cargo sous certaines conditions. Le transport par avion passager est interdit. L’expédition de piles déchargées pour mise au rebut est soumise aux réglements spécifiques du pays concerné ou aux réglements avalisés par lesdits pays, tels que lmes réglementations d’articles restrictifs de l’IATA (l’International Air Transport Association), Genève. Important: Les réglementations du transport des piles au lithium sont révisées périodiquement. Publication 1747-5.25 25  ATTENTION: Ne pas incinérer ou jeter les piles au lithium dans des conteneurs non prévus à cet effet. Une explosion ou une rupture pourrait se produire. Les piles doivent être collectées pour la mise au rebut de façon à éviter les court-circuits, le compactage ou la destruction du boîtier hermétique et de son enveloppe hermétique. Pour la mise au rebut, les piles doivent être emballées et expédiées vers un site approprié conformément aux réglementations de transport. Le Ministère américain des transports autorise l’expédition de « piles au lithium pour la mise au rebut » par véhicule à moteur dans son réglement 173.1015 de CFR 49 (en vigueur depuis le 5 janvier 1983). Pour toute information complémentaire, adressez-vous à : U.S. Department of Transportation Research and Special Programs Administration 400 Seventh Street, S.W. Washington, D.C. 20590 Bien que l’Agence américaine de protection de l’environnement n’ait pas actuellement de réglementation spécifique aux piles au lithium, la matière contenue dans ces piles est considérée comme toxique, réactive et corrosive. La personne en charge de la mise au rebut de ces matières est responsable de tout risque résultant de son action. Des réglementations nationales et locales relatives à la mise au rebut de ces matières peuvent exister. Pour obtenir une fiche technique de sécurité sur les piles au lithium, adressez-vous au fabricant : Sanyo Energy Corporation 600 Supreme Drive Bensenville, IL 60106 Publication 1747-5.25 Allen-Bradley Replacements 26 Notes: Publication 1747-5.25 Modulare Prozessoren SLC 5/01™ und SLC 5/02™ (Bestellnummern 1747-L511, 1747-L514, 1747-L524) Installationsdaten Deutscher Abschnitt Inhalt... Seite Wichtige Anwendungshinweise . . . . . . . . . . . 28 Weitere Informationen . . . . . . . . . . . . . . . . . . 29 Erforderliche Werkzeuge und Geräte . . . . . . . 30 Sicherheitshinweise . . . . . . . . . . . . . . . . . . . . 30 Einbauverfahren . . . . . . . . . . . . . . . . . . . . . . . 31 Störungssuche . . . . . . . . . . . . . . . . . . . . . . . . 33 Technische Daten . . . . . . . . . . . . . . . . . . . . . . 34 Handhabung, Lagerung und Transport der Batterie (Best.-Nr. 1747-BA) . . . . . . . . . . . . . . . . . . . . 36 Publikation 1747-5.25 Allen-Bradley Replacements 28 Wichtige Anwendungshinweise Aufgrund der vielfältigen Einsatzmöglichkeiten der in dieser Publikation beschriebenen Produkte müssen Sie als Verantwortlicher für die Anwendung und Nutzung dieses Geräts sicherstellen, daß jede Anwendung bzw. jeder Einsatz alle Leistungs- und Sicherheitsanforderungen, einschließlich sämtlicher anwendbaren Gesetze, Vorschriften, Codes und Normen erfüllt. Die in diesem Handbuch dargestellten Abbildungen, Tabellen, Programm- und Layout-Beispiele sind ausschließlich zur besseren Texterläuterung dieses Handbuchs aufgeführt. Aufgrund der vielfachen Möglichkeiten und Anforderungen jedes einzelnen Verwendungszwecks kann Allen-Bradley keine Verantwortung oder Haftung (einschließlich Haftung für geistiges Eigentum) für den tatsächlichen Einsatz, der auf den in dieser Publikation enthaltenen Beispielen beruht, übernehmen. Die Allen-Bradley Publikation SGI-1.1, Safety Guidelines for the Application, Installation, and Maintenance of Solid-State Controls (erhältlich über Ihre örtliche Allen-Bradley Geschäftsstelle) behandelt einige wichtige Unterschiede zwischen elektronischen und elektromechanischen Geräten, die bei der Anwendung der in dieser Publikation beschriebenen Produkte berücksichtigt werden sollten. Die Vervielfältigung des Inhalts dieses verlagsrechtlich geschützten Handbuchs, ganz oder auszugsweise, bedarf der schriftlichen Genehmigung der Allen-Bradley Company, Inc. Besondere Hinweise in diesem Handbuch sollen den Anwender auf bestimmte Sicherheitsaspekte aufmerksam machen:  ACHTUNG: Diese Hinweise sollen den Leser auf Vorgehensweisen und Zustände aufmerksam machen, die Körperverletzungen oder sogar Tod sowie Geräteschäden oder wirtschaftliche Verluste zur Folge haben können. Die Achtungshinweise helfen Ihnen: • Gefahrenzustände zu erkennen • Gefahren zu vermeiden • Folgeschäden zu erkennen Wichtig: Kennzeichnet Informationen, die für die erfolgreiche Anwendung sowie für ein gründliches Verstehen des Produkts unabdingbar sind. Publikation 1747-5.25 29 Weitere Informationen In unseren Bemühungen, die Umwelt zu erhalten, zu schützen und zu verbessern, reduzieren wir bei Allen-Bradley die Papiermenge, die wir einsetzen. Weniger Papier bedeutet mehr Alternativen für Sie. Neben den herkömmlichen gedruckten Publikationen bieten wir nun Online-Handbücher an, die aktuellste Daten enthalten. Vor der Inbetriebnahme des Steuerungssystems empfehlen wir das Lesen der unten aufgeführten themenverwandten Publikationen. Themenverwandte Publikationen Informationen über: Dokumentation: Publik.–Nr. Detailliertere Beschreibung über die Installation und Anwendung von SLC 500-Steuerungssystemen mit fester Hardware-Konfiguration SLC 500 Modular Hardware Style Installation and Operation Manual 1747-6.2 Referenzhandbuch mit Statusfiledaten, Befehlssatz und Hinweisen zur Störungssuche Befehlssatz für SLC 500 und MicroLogix 1000 Referenzhandbuch 1747-6.15DE gesammelte SLC 500-Publikationen auf CD-ROM 1747-CD1-1 Die beiden oben aufgeführten Handbücher sowie die folgenden Publikationen auf CD-ROM: •Analog-E/A-Module SLC 500, Benutzerhandbuch •Diskrete E/A-Module, Installationsdaten •Diskrete E/A-Module, Produktdaten Zusätzliche Informationen Zu diesem Produkt gibt es eine Benutzerhandbuch, das Sie wie folgt bestellen können: • durch kostenloses Herunterladen vom Internet: www.theautomationbookstore.com • durch Erwerb: — bei Ihrem Distributor oder einer Niederlassung von Rockwell Automation in Ihrer Nähe — per Internet: www.theautomationbookstore.com — per Telefon unter folgenden Rufnummern: 1.800.963.9548 (USA/Kanada) oder 001.330.725.1574 (außerhalb den USA/Kanadas) Publikation 1747-5.25 Allen-Bradley Replacements 30 Erforderliche Werkzeuge und Geräte • mittelgroßer Flachschraubendreher • Programmiergerät • Kommunikationsschnittstelle 1747-PIC, 1784-KTX oder 1784-PCMK Sicherheitshinweise  ACHTUNG: Ein Modul darf niemals bei anliegender Spannung installiert, entfernt oder verdrahtet werden. Ferner darf ein Prozessormodul keinen Flächen oder Bereichen ausgesetzt werden, die u.U. elektrostatische Ladungen aufweisen, da sonst die Gefahr besteht, daß der Speicherinhalt verändert oder zerstört wird. Allgemeine Empfehlungen zu den installationsbezogenen Sicherheitsanforderungen und zu sicherheitsrelevanten Verfahrensweisen am Arbeitsplatz sind den einschlägigen regionalen Bestimmungen zu entnehmen. • Europa: Normen gemäß EN 60204 und VDE-Vorschriften. • USA: NFPA 70E, Electrical Safety Requirements for Employee Workplaces. Wichtig: Hinweise zur ordnungsgemäßen Handhabung, Lagerung und Entsorgung der Batterie sind auf Seite 23 enthalten. Publikation 1747-5.25 31 Einbauverfahren Einbau der Batterie Wichtig: Sofern der Prozessor mit einer Batterie ausgestattet ist — beim Prozessor SLC 5/01 (1747-L511) ist die Batterie optional — muß sichergestellt werden, daß sie angeschlossen wird, bevor der Prozessor in das Chassis eingebaut wird. Der Inhalt des Prozessorspeichers wird somit gesichert, falls die Spannungsversorgung der speicherprogrammierbaren Steuerung ausfällt. 1. Die Tür des Prozessors öffnen. 2. ie Brücke aus der Batterieanschlußbuchse entfernen und für den eventuellen späteren Gebrauch ohne Batterie an einem sicheren Ort aufbewahren. 3. Eine neue bzw. Ersatzbatterie in die Halterung einsetzen. Darauf achten, daß die Batterie fest in den Halteclips sitzt. 4. en Batterieanschluß in die Buchse stecken. Siehe folgende Abbildung. weißer Draht roter Draht Batterieanschluß Halteclips + 5. Die Tür des Prozessors schließen. Wichtig: Hinweise zur ordnungsgemäßen Handhabung, Lagerung und Entsorgung der Batterie sind auf Seite 23 enthalten. Publikation 1747-5.25 Allen-Bradley Replacements 32 Einbau des Prozessors Vergewissern Sie sich, daß die Systemspannung ausgeschaltet ist, und schieben Sie den Prozessor anschließend in Steckplatz 0 des Chassis der Reihe 1746. Wichtig: Die modularen Prozessoren der Reihe SLC 500t müssen, wie unten dargestellt, in den linken Steckplatz (Steckplatz 0) eingeschoben werden. Außerdem muß nach dem Einbau des Prozessors der Schutzstreifen entfernt werden. Netzteil Prozessorentriegelungslasche Modulführung Schutzstreifen Einschalten der Spannung 1. Das Chassisnetzteil einschalten. 2. Die LED-Anzeigen des Chassisnetzteils und des Prozessors überprüfen. Die POWER-LED des Netzteils sollte leuchten, und die Fehler-LED des Prozessors sollte blinken. LED-Anzeigen des Netzteils sowie des SLC 5/01 und SLC 5/02 POWER Publikation 1747-5.25 COMM RUN CPU FAULT FORCED I/O BATTERY LOW LED AUS LED LEUCHTET LED BLINKT LED-Status ist unbedeutend Nur bei dem Prozessor SlC 5/01: Die RUN-Anzeige tragt die Beschriftung “PC RUN.” Die COMM-Anzeige ist nicht vorhanden. 33 Laden der Software Hinweise sind in den Handbüchern der Programmiersoftware enthalten. Herstellung der Kommunikationsverbindung mit dem Prozessor 1. Das Schnittstellenmodul 1747-PIC am Prozessor und am Personalcomputer anschließen. 2. Die Kommunikationsparameter der Software so einstellen, daß sie mit den Vorgabewerten des Prozessors übereinstimmen: • DH-485 • 19,2 kBaud • Netzknotenadresse = 1 Störungssuche Vor Beginn der Störungssuche am SLC 500-System sollten Sie ein Installationsund Bedienungshandbuch für SLC 500-Steuerungen mit modularer Hardware-Konfiguration (1747-6.2) von einer der auf Seite 16 aufgelisteten Bezugsquellen anfordern. Beziehen Sie sich in diesem Handbuch auf das Kapitel Störungssuche. Zusätzlich zu dem o.g. Handbuch kann das Befehlssatz-Referenzhandbuch für die Steuerungen SLC 500 und MicroLogix 1000 (1747-6.15DE) von den auf Seite 16 aufgeführten Bezugsquellen angefordert werden. Dieses Handbuch enthält Erläuterungen und Beispiele für den gesamten Befehlssatz sowie für alle Statusworte und -bits. Auch werden alle möglicherweise in Statuswort S:6 enthaltenen Fehlercodes erläutert. Publikation 1747-5.25 Allen-Bradley Replacements 34 Technische Daten SLC 5/01 (1747-L511, -L514) Spezifikation SLC 5/02 (1747-L524) Programmspeicher 1K oder 4K Befehlskapazität 4K Befehlskapazität zusätzlicher Datenspeicher 0 0 max. E/A-Kapazität 3940 diskrete Eingänge 3940 diskrete Ausgänge 4096 diskrete Eingänge 4096 diskrete Ausgänge max. zentrale Chassis/ Steckplätze 3/30 3/30 Programmiersoftware RSLogix 500t, PLC– 500 A.I. Seriest, APS und HHT Programmierbefehle 52 71 typische Abfragezeit(1) 8 ms/K 4,8 ms/K Bitausführung (XIC) 4 µs 2,4 µs (1) Die Abfragezeiten beziehen sich generell auf ein Kontaktplanprogramm (1 K), das aus einfacher Strompfadlogik und Kommunikationsbefehlen besteht. Die tatsächlichen Abfragezeiten hängen von der Programmgröße, den programmierten Befehlen und dem Kommunikationsprotokoll ab. Kommunikation DH-485 (1) Empfang SLC 5/01(1) Empfang oder Initiierung SLC 5/02(1) Für die Programmierung über den DH-485-Kanal ist ein Modul 1747-PIC erforderlich. Publikation 1747-5.25 35 Beschreibung Spezifikation Netzteilbelastung bei 5 V DC 350 mA Netzteilbelastung bei 24 V DC 105 mA Aufrechterhaltung der Programmabfrage nach Spannungsausfall 20 ms bis 3 s (je nach Netzteilbelastung) Störfestigkeit NEMA-Standard ICS 2-230 Vibration Verschiebung: 0,381 mm, Spitze/Spitze bei 5-57 Hz Stoßeinwirkung (während des Betriebs) 30 Gs Umgebungstemperatur während des Betriebs: 0 bis + 60° C Lagertemperatur: -40° C bis 85° C Luftfeuchtigkeit 5 bis 95%, ohne Kondensation Amtliche Zulassungen UL-Zertifizierung CSA-Zulassung Klasse 1, Gruppen A, B, C oder D, Abschnitt 2 Erfüllung der CE-Bestimmungen für alle zutreffenden Richtlinien Beschleunigung: 2,5 Gs bei 57-2000 Hz Die für die Prozessoren SLC 5/01 und SLC 5/02 verfügbaren Speicher-Backup-Optionen sind in der folgenden Tabelle zusammengefaßt. Die EEPROM- und UVPROM-Speichermodule ermöglichen die nichtflüchtige Aufzeichnung. Speicher-Backup-Option SLC 5/01 (1747-L511/1747-L514) SLC 5/02 (1747-L524) EEPROM 1747-M1, 1747-M2 1747-M2 UVPROM 1747-M3, 1747-M4 1747-M4 Publikation 1747-5.25 Allen-Bradley Replacements 36 Handhabung, Lagerung und Transport der Batterie (Best.-Nr. 1747-BA) Handhabung  ACHTUNG: Die Batterien nicht öffnen, durchlöchern, zerdrücken oder auf sonstige Weise beschädigen, da dies eine Explosion verursachen und/oder giftige, korrosive und brennbare Flüssigkeiten freisetzen würde. Die Batterien nicht laden, da dies zu einer Explosion oder Überhitzung mit möglichen Verbrennungsfolgen führen könnte. Lagerung Lagern Sie die Lithiumbatterien in einer kühlen, trockenen Umgebung, am besten bei +20° C bis +25° C, mit einer relativen Luftfeuchtigkeit von 40% bis 60%. Transport Eine oder zwei Batterien — Innerhalb der USA können bis zu zwei Batterien ohne Einschränkungen versandt werden. Die für den Versand innerhalb anderer Länder bzw. in andere Länder geltenden Bestimmungen können anders lauten. Drei oder mehr Batterien — Die Regelung des Transports von drei oder mehr Batterien innerhalb der USA wurde durch das Verkehrsministerium (Department of Transportation) im sogenannten Code of Federal Regulations, Absatz CFR49, “Transportation” festgelegt. In Ausnahmefällen ist der Transport von bestimmten gefährlichen Feststoffen, die als brennbare Materialien klassifiziert sind, gemäß der Regelung DOT-E7052 erlaubt. Aufgrund dieser Ausnahme können Lithiumbatterien per Kraftfahrzeug, Bahn, Frachtschiff und Frachtflugzeug transportiert werden, vorausgesetzt, daß bestimmte Bedingungen erfüllt werden. Der Transport per Passagierflugzeug ist nicht gestattet. Der Versand von verbrauchten Batterien unterliegt den jeweiligen Bestimmungen des Landes oder den Bestimmungen des Internationalen Lufttransportverbands in Genf (IATA-Regelung bezüglich des Versands von Gefahrengütern). Wichtig: Die auf den Transport von Lithiumbatterien zutreffenden Bestimmungen werden von Zeit zu Zeit neu überarbeitet. Publikation 1747-5.25 37  ACHTUNG: Lithiumbatterien nicht verbrennen oder in den Müll werfen, da sie explodieren oder explosionsartig bersten können. Gehen Sie beim Sammeln von Batterien zur Entsorgung vorsichtig vor, um Kurzschlüsse, Zusammendrücken oder Beschädigen des Batteriemantels und der Abdichtung zu vermeiden. Batterien müssen zur Entsorgung verpackt werden und gemäß den zutreffenden Vorschriften an die zuständige Entsorgungsstelle gesandt werden. In den USA genehmigt das Verkehrsministerium (Department of Transportation) den Versand von “Lithiumbatterien zum Zwecke der Entsorgung” ausschließlich per Kraftfahrzeug in Bestimmung 173.1015 des sog. “Code of Federal Regulations” (Inkrafttretung am 5. Januar 1983). Für weitere Informationen wenden Sie sich bitte an die folgende Adresse: U.S. Department of Transportation Research and Special Programs Administration 400 Seventh Street, S.W. Washington, D.C. 20590, USA Obwohl das US-Ministerium für Umwelt zu diesem Zeitpunkt noch keine Bestimmungen in bezug auf Lithiumbatterien erlassen hat, sollte das in den Batterien enthaltene Material als giftig, reaktiv und korrosiv angesehen werden. Die für die Entsorgung der in der Batterie enthaltenen Stoffe zuständige Person ist für alle verursachten Gefahren verantwortlich. Im Zusammenhang mit der Entsorgung dieser Stoffe gelten u.U. staatliche und örtliche Bestimmungen. Ein Sicherheitsdatenblatt über Lithiumbatterien kann beim Hersteller angefordert werden: Sanyo Energy Corporation 600 Supreme Drive Bensenville, IL 60106, USA Publikation 1747-5.25 Allen-Bradley Replacements 38 Notes: Publikation 1747-5.25 Processori modulari SLC 5/01™ e SLC 5/02™ (Numeri di catalogo 1747-L511, 1747-L514, 1747-L524) Istruzioni per l’installazione Sezione italiana pagina All’interno... Informazioni importanti per l’utente ................. 40 Per ulteriori informazioni ................................. 41 Strumenti ed apparecchiature necessari ......... 42 Considerazioni sulla sicurezza ........................ 42 Procedura di installazione ............................... 43 Individuazione dei guasti ................................. 45 Caratteristiche tecniche ................................... 46 Utilizzo, stoccaggio e trasporto della batteria (No. cat. 1747-BA) ......................................................... 48 Pubblicazione 1747-5.25 Allen-Bradley Replacements 40 Informazioni importanti per l’utente Poiché i prodotti descritti in questa pubblicazione hanno molteplici usi, i responsabili dell’applicazione e dell’utilizzo di questa apparecchiatura di controllo devono accertarsi che sia stato fatto tutto il possibile per assicurare che ogni applicazione ed ogni utilizzo siano conformi ai requisiti di prestazione e sicurezza, ivi inclusi qualsiasi legge, regolamento, codice e standard pertinenti. Le illustrazioni, gli schemi, i programmi campione e gli esempi di configurazioni di questo manuale sono intesi esclusivamente ad illustrare il testo. A causa dei numerosi requisiti e variabili propri di ciascuna installazione, la Allen-Bradley declina ogni responsabilità (compresa la responsabilità per la proprietà intellettuale) per l’uso dei prodotti basato sulle applicazioni illustrate in questa pubblicazione. La pubblicazione Allen-Bradley SGI-1.1, Safety Guidelines for the Application, Installation, and Maintenance of Solid-State Control (Istruzioni di sicurezza per l’applicazione, l’installazione e la manutenzione del controllo a stato solido), disponibile presso il più vicino ufficio Allen-Bradley, descrive importanti differenze, che si dovrebbero prendere in considerazione nell’applicazione di prodotti quali quelli descritti in questa pubblicazione, esistenti tra le apparecchiature allo stato solido ed i dispositivi elettromeccanici. È proibita la riproduzione, completa o parziale, del contenuto di questa pubblicazione protetta da copyright, salvo previa autorizzazione scritta della Allen-Bradley Company, Inc. In tutto questo manuale facciamo uso di note per attrarre l’attenzione su considerazioni relative alla sicurezza:  ATTENZIONE: evidenzia informazioni circa procedure o circostanze che possono causare pericolo o morte a persone, danni alla proprietà o una perdita economica. I messaggi di Attenzione permettono di: • identificare un pericolo • evitare il pericolo • rendersi conto delle conseguenze Importante:identifica informazioni di basilare importanza per un’applicazione corretta e per la comprensione del prodotto. Pubblicazione 1747-5.25 41 Per ulteriori informazioni Nell’ambito dell’impegno profuso per preservare, proteggere e migliorare il nostro ambiente, la Allen-Bradley sta gradualmente riducendo la quantità di carta utilizzata. Una minore quantità di carta significa maggiori opportunità per l’utente. Oltre alle tradizionali pubblicazioni su carta, la Allen-Bradley offre ora manuali in linea contenenti tutte le informazioni più aggiornate. Prima di avviare il sistema di controllo si consiglia di leggere le pubblicazioni attinenti di seguito elencate. Pubblicazioni attinenti Fare riferimento alla seguente pubblicazione Per: No. pub. informazioni più dettagliate sull’installazione e l’utilizzo del sistema modulare SLC 500. SLC 500 Modular Hardware Style Installation and Operation Manual 1747-6.2 un manuale di riferimento contenente informazioni sui dati del file di stato, sul set di istruzioni e sull’individuazione dei guasti. SLC 500 and MicroLogix 1000 Instruction Set Reference Manual 1747-6.15 Letteratura sui SLC 500 su CD-ROM 1747-CD1-1 Un CD-ROM che contiene entrambi i manuali elencati sopra, oltre a: •Manuale dell’utente dei moduli I/O analogici SLC 500 •Istruzioni per l’installazione dei moduli I/O discreti •Dati relativi ai moduli I/O discreti Come ottenere maggiori informazioni Se si desidera ricevere un manuale, è possibile: • scaricare una versione elettronica gratis da internet al sito: www.theautomationbookstore.com • comprare un manuale stampato: — contattando il distributore locale o rappresentante della Rockwell Automation — visitando il sito www.theautomationbookstore.com ed effettuando l’ordinazione — telefonando al n.: 1.800.963.9548 (USA/Canada) oppure al n.: 001.330.725.1574 (fuori degli Stati Uniti/Canada) Pubblicazione 1747-5.25 Allen-Bradley Replacements 42 Strumenti ed apparecchiature necessari • cacciavite a taglio medio • apparecchiatura di programmazione • interfaccia di comunicazione 1747-PIC, 1784-KTX o 1784-PCMK Considerazioni sulla sicurezza  ATTENZIONE: non installare, rimuovere o collegare i moduli quando sono alimentati. Non esporre i moduli del processore a superfici o altre aree che potrebbero essere dotate di carica elettrostatica. Le cariche elettrostatiche possono alterare o distruggere la memoria. Per consigli generali sui requisiti relativi alla sicurezza dell’installazione e le operazioni relative alla sicurezza, fare riferimento ai requisiti specifici della regione in questione. • Europa: fare riferimento agli standard contenuti nella documentazione EN 60204 ed ai regolamenti nazionali vigenti. • Stati Uniti: fare riferimento alla documentazione NFPA 70E, Electrical Safety Requirements for Employee Workplaces. Importante:per informazioni sul trattamento, lo stoccaggio ed il trasporto della batteria, vedere pagina 23. Pubblicazione 1747-5.25 43 Procedura di installazione Installazione della batteria Importante: se il processore è dotato di batteria (per il processore SLC 5/01 (1747-L511) la batteria è opzionale), prima di installare il processore nello chassis assicurarsi che la batteria sia collegata. In tal modo il processore viene fornito di backup della memoria in caso di perdita di alimentazione del controllore. 1. Aprire lo sportello del processore. 2. Rimuovere il ponticello dalla presa del connettore della batteria. Conservare il ponticello in un luogo sicuro per un eventuale utilizzo futuro senza la batteria. 3. Inserire una batteria nuova o di ricambio nell’alloggiamento ed assicurarsi che sia bloccata dalle linguette di ritenuta. 4. Inserire il connettore della batteria nella presa. Vedere la figura di seguito riportata. Conduttore bianco Conduttore rosso Connettore batteria Lingurette di ritenuta + 5. Chiudere lo sportello del processore. Importante:per informazioni sul trattamento, lo stoccaggio ed il trasporto della batteria, vedere pagina 23. Pubblicazione 1747-5.25 Allen-Bradley Replacements 44 Installazione del processore Assicurarsi che il sistema non sia alimentato, quindi inserire il processore nello slot 0 dello chassis 1746. Importante:il processore modulare SLC 500t deve essere inserito nello slot di sinistra (slot 0), come illustrato nella seguente figura. Una volta installato il processore, rimuovere la fascetta protettiva. Alimentatore Dispositivo di sgancio del processore Guida della scheda Fascetta protettiva Alimentazione del processore 1. Alimentare lo chassis. 2. Controllare i LED dell’alimentatore dello chassis e del processore. Il LED dell’alimentatore deve essere acceso, mentre il LED di errore del processore deve lampeggiare. LED dell’alimentatore e dei processori SLC 5/01 e SLC 5/02 POWER COMM RUN CPU FAULT FORCED I/O BATTERY LOW Indica che il LED è SPENTO. Indaca che il LED è ACCESO. Indica che il LED è LAMPEGGIANTE. Lo stato del LED è irrilevante Il LED RUN del processore SLC 5/01 è denominato “PC RUN.” Inoltre, il processore SLC 5/01 non ha il LED COMM. Pubblicazione 1747-5.25 45 Caricamento del software Fare riferimento alla documentazione sul software di programmazione. Attivazione delle comunicazioni con il processore 1. Collegare l’interfaccia 1747-PIC al processore ed al PC. 2. Impostare i parametri di comunicazione del software in modo che corrispondano ai parametri di default del processore: • DH-485 • 19,2 k baud • Indirizzo del nodo = 1 Individuazione dei guasti Prima di procedere all’individuazione dei guasti del sistema SLC 500, procurarsi una copia del manuale SLC 500 Modular Hardware Style Installation and Operation Manual (1747-6.2) in uno dei modi illustrati alla pagina 16 e fare riferimento al capitolo sull’individuazione dei guasti. Oltre al suindicato manuale, è possibile ottenere anche il manuale SLC 500 and MicroLogix 1000 Instruction Set Reference Manual (1747-6.15) seguendo la medesima procedura illustrata alla pagina 16. Tale manuale contiene spiegazioni ed esempi sull’intero set di istruzioni e su tutte le parole e i bit di stato, nonché su tutti i codici di errore possibili individuati nella parola di stato S:6. Pubblicazione 1747-5.25 Allen-Bradley Replacements 46 Caratteristiche tecniche SLC 5/01 (1747-L511, -L514) Caratteristica SLC 5/02 (1747-L524) Memoria del programma 1 K o 4 K di istruzioni 4 K di istruzioni Memoria dati addizionale 0 0 Capacità di I/O massima 3940 ingressi discreti 3940 uscite discrete 4096 ingressi discreti 4096 uscite discrete Chassis/slot locali massimi 3/30 3/30 Software di programmazione RSLogix 500t, PLC– 500 A.I. Seriest, APS e HHT Istruzioni di programmazione 52 71 Tempo di scansione tipico(1) 8 ms/K 4,8 ms/K Esecuzione dei bit (XIC) 4 µs 2,4 µs (1) I tempi di scansione sono tipici di un programma a logica ladder di 1 K, consistente in una logica ladder semplice ed in un servizio di comunicazione. I tempi di scansione effettivi dipendono dalle dimensioni del programma, dalle istruzioni utilizzate e dal protocollo di comunicazione. Comunicazione DH-485 (1) Ricezione SLC 5/01(1) Ricezione o Inizializzazione SLC 5/02(1) Per collegarsi al canale DH-485 per la programmazione è richiesta un’interfaccia 1747-PIC. Pubblicazione 1747-5.25 47 Descrizione Caratteristica Assorbimento di corrente a 5V cc 350 mA Assorbimento di corrente a 24V cc 105 mA Tempo di tenuta della scansione del programma dopo una perdita di corrente da 20 ms a 3 s (dipende dall’assorbimento di corrente) Immunità da rumori NEMA Standard ICS 2-230 Vibrazione Ampiezza: 0,4 mm, picco–picco a 5-57 Hz Accelerazione: 2,5G a 57-2000 Hz Urto (in funzionamento) 30G Temperatura ambientale Funzionamento: da 0 a + 60°C (da 32°F a 140°F) Stoccaggio: da -40°C a 85°C (da -40°F a 185°F) Umidità da 5 a 95% senza condensa Enti di certificazione elencato in UL approvato da CSA Classe 1, Gruppi A, B, C o D, Divisione 2 conforme CE per tutte le direttive applicabili La seguente tabella riassume le opzioni di backup della memoria disponibili per i processori SLC 5/01 e SLC 5/02. I moduli di memoria EEPROM e UVPROM forniscono un backup non–volatile della memoria. Opzioni di backup della memoria SLC 5/01 (1747-L511/1747-L514) SLC 5/02 (1747-L524) EEPROM 1747-M1, 1747-M2 1747-M2 UVPROM 1747-M3, 1747-M4 1747-M4 Pubblicazione 1747-5.25 Allen-Bradley Replacements 48 Utilizzo, stoccaggio e trasporto della batteria (No. cat. 1747-BA) Modalità di utilizzo  ATTENZIONE: non caricare la batteria. La batteria potrebbe esplodere, oppure le pile potrebbero surriscaldarsi e causare gravi ustioni. Non aprire, forare, rompere o danneggiare in altro modo la batteria. La batteria potrebbe esplodere e/o potrebbero verificarsi fuoriuscite di liquidi tossici, corrosivi e infiammabili. Modalità di stoccaggio Conservare le batterie al litio in ambiente fresco e asciutto, con temperatura compresa tra 20° C e 25° C (tra 68° F e 77° F) ed una umidità relativa compresa tra 40% e 60%. Modalità di trasporto Una o due batterie: le norme statunitensi consentono il trasporto simultaneo di un numero massimo di due baterie. Le normative in materia vigenti in altri paesi possono essere diverse da quelle degli Stati Uniti. Tre o più batterie: le norme statunitensi relative al trasporto di tre o più batterie sono specificate dal DOT (Department of Transportation) nel Codice degli Ordinamenti Federali, CFR49, “Trasporto”. Una clausola esonerativa da tali norme, (DOT - E7052), prevede il trasporto di certi materiali pericolosi classificati come solidi infiammabili. Tale clausola autorizza il trasporto di batterie al litio su veicoli a motore, treni merce, navi ed aerei da carico, previo soddisfacimento di certe condizioni. Non è consentito il trasporto di batterie in aerei per il trasporto di persone. Il trasporto di batterie esaurite per il loro smaltimento può essere soggetto alle norme specifiche dei paesi interessati o ai regolamenti recepiti da tali paesi, quali ad esempio le Restricted Articles Regulations dello IATA (International Air Transport Association), Ginevra, Svizzera. Importante:le normative per il trasporto delle batterie al litio vengono periodicamente aggiornate. Pubblicazione 1747-5.25 49  ATTENZIONE: le batterie al litio non devono essere bruciate né gettate nei comuni raccoglitori di immondizia, in quanto potrebbero esplodere o spaccarsi. La raccolta delle batterie destinate allo smaltimento deve essere eseguita in modo da evitare corti circuiti, compattamenti o distruzione del contenitore e del sigillo ermetico. Le batterie da eliminare devono essere imballate e trasportate, in osservanza alle norme vigenti, in un’appropriata area di smaltimento. Il Dipartimento dei Trasporti degli Stati Uniti autorizza il trasporto su veicolo a motore di “batterie al litio da eliminare” esclusivamente in osservanza all’ordinamento 173.1015 del CFR 49 (in vigore dal 5 gennaio 1983). Per ulteriori informazioni, contattare il seguente indirizzo: U.S. Department of Transportation Research and Special Programs Administration 400 Seventh Street, S.W. Washington, D.C. 20590 Sebbene la Environmental Protection Agency (Agenzia per la protezione ambientale) non contempli attualmente norme specifiche per le batterie al litio, i materiali in esse contenuti potrebbero essere ritenuti tossici, reattivi o corrosivi. La persona incaricata di provvedere allo smaltimento di tali materiali è responsabile di qualsiasi danno causato nell’espletamento di tale procedura. È possibile che esistano ordinamenti locali e statali concernenti lo smaltimento di questi materiali. Per un foglio illustrativo delle procedure di sicurezza relative ai materiali contenuti nelle batterie al litio, contattare l’azienda produttrice: Sanyo Energy Corporation 600 Supreme Drive Bensenville, IL 60106 Pubblicazione 1747-5.25 Allen-Bradley Replacements 50 Notes: Pubblicazione 1747-5.25 Procesadores modulares SLC 5/01™ y SLC 5/02™ (Números de catálogo 1747-L511, 1747-L514, 1747-L524) Instrucciones de instalación Sección en español Contenido... pagina Información importante para el usuario .. 52 Para obtener más información ................ 53 Herramientas y equipo necesarios .......... 54 Consideraciones de seguridad ................ 54 Procedimiento de instalación .................. 55 Localización y corrección de fallos .......... 57 Especificaciones ..................................... 58 Manipulación, almacenamiento y transporte de la batería (Cat. No. 1747-BA) ........................................... 60 Allen-Bradley Replacements 52 Información importante para el usuario Debido a la variedad de usos de los productos descritos en esta publicación, las personas responsables de la aplicación y uso de este equipo de control deben asegurarse de que se hayan seguido todos los pasos necesarios para que cada aplicación y uso cumpla con todos los requisitos de rendimiento y seguridad, incluyendo leyes, reglamentos, códigos y normas aplicables. Los ejemplos de ilustraciones, gráficos, programas y esquemas mostrados en esta guía tienen la única intención de ilustrar el texto. Debido a las muchas variables y requisitos asociados con cualquier instalación particular, Allen–Bradley no puede asumir responsabilidad u obligación (incluyendo responsabilidad de propiedad intelectual) por el uso real basado en los ejemplos mostrados en esta publicación. La publicación SGI-1.1 de Allen-Bradley, Safety Guidelines for the Application, Installation, and Maintenance of Solid State Control (disponible en la oficina local de Allen-Bradley), describe algunas diferencias importantes entre equipos transistorizados y dispositivos electromecánicos, las cuales deben tomarse en consideración al usar productos tales como los descritos en esta publicación. Está prohibida la reproducción total o parcial del contenido de esta publicación de propiedad exclusiva sin el permiso por escrito de Allen-Bradley Company, Inc. En estas instrucciones de instalación hacemos anotaciones para alertarle de consideraciones de seguridad:  ATENCION: Identifica información sobre prácticas o circunstancias que pueden conducir a lesiones personales o la muerte, daños materiales o pérdidas económicas. Las notas de “Atención” le ayudan a: • identificar un peligro • evitar un peligro • reconocer las consecuencias Importante:Identifica información especialmente importante para una aplicación y un entendimiento correctos del producto. 1747-5.25 53 Para obtener más información Como parte de nuestro esfuerzo para preservar, proteger y mejorar nuestro medio ambiente, Allen-Bradley está reduciendo la cantidad de papel que usa. Menos papel significa más opciones para usted. Además de las publicaciones impresas tradicionales, ahora ofrecemos manuales en línea con la información más actualizada disponible. Recomendamos que lea estas publicaciones relacionadas listadas a continuación antes de encender el sistema de control. Publicaciones relacionadas Para Consulte este documento Pub. No. Obtener una descripción más detallada de cómo instalar y usar el sistema modular SLC 500. SLC 500 Modular Hardware Style Installation and Operating Manual 1747-6.2 Obtener un manual de referencia que contenga información sobre los datos de archivo de estado, conjunto de instrucciones y localización y corrección de fallos. Manual del referencia del conjunto de instrucciones SLC 500 y MicroLogix 1000 1747-6.15ES Colección de información impresa sobre el SLC 500 en CD-ROM 1747-CD1-1 Un CD-ROM con los dos manuales indicados anteriormente, además de: •Manual del usuario de módulos de E/S analógicas SLC 500 •Instrucciones de instalación de módulos de E/S discretas •Datos de productos - Módulos de E/S discretas Para obtener más información Si quiere recibir un manual puede: • descargar una versión electrónica gratis de la siguiente dirección de internet: www.theautomationbookstore.com • comprar un manual impreso. Para hacer esto haga una de las siguientes cosas: — comuníquese con su distribuidor local o representante local de Rockwell Automation — haga un pedido en la página electrónica: www.theautomationbookstore.com — llame al: 1.800.963.9548 (USA/Canadá) ó 001.330.725.1574 (Fuera de los EE.UU./Canadá) 1747-5.25 Allen-Bradley Replacements 54 Herramientas y equipo necesarios • destornillador de hoja mediana • equipo de programación • interfaces de comunicación 1747-PIC, 1784-KTX ó 1784-PCMK Consideraciones de seguridad  ATENCION: Nunca instale, retire o cablee los módulos mientras esté conectada la alimentación eléctrica. Además, no exponga los módulos del procesador a superficies u otras áreas que puedan usualmente contener carga electrostática. Las cargas electrostáticas pueden alterar o destruir la memoria. Para obtener recomendaciones generales referentes a requisitos de seguridad en la instalación y prácticas de trabajo orientadas a aspectos de seguridad, consulte los requisitos específicos para su región. • Europa: Consulte los estándares que se encuentran en EN 60204 y las normas nacionales. • Estados Unidos: consulte NFPA 70E, Electrical Safety Requirements for Employee workplaces. Importante:Vea la página 23 para obtener información sobre tratamiento adecuado de baterías, almacenamiento y transporte. 1747-5.25 55 Procedimiento de instalación Instalación de la batería Importante:Si su procesador tiene una batería— la batería es una opción para el procesador SLC 5/01 (1747-L511) — asegúrese de que esté conectada antes de instalar el procesador dentro del chasis. Esto proporciona memoria de seguridad (backup) para su procesador en caso de que falle el suministro de alimentación eléctrica al controlador. 1. Abra la puerta del procesador. 2. Retire el puente del conector de la batería. Guarde el puente en un lugar seguro para un posible uso futuro sin la batería. 3. Inserte una batería nueva o de repuesto en el sujetador asegurándose de que quede sujeta con las abrazaderas de retención. 4. Conecte el conector de la batería dentro del conector. Vea la siguiente figura. Cable blanco Cable rojo Conector de la bateria Abrazaderas de retención + 5. Cierre la puerta del procesador. Importante:Vea la página 23 para obtener información sobre tratamiento adecuado de baterías, almacenamiento y transporte. 1747-5.25 Allen-Bradley Replacements 56 Instalación del procesador Asegúrese de que la alimentación eléctrica del sistema esté deconectada; luego inserte el procesador en la ranura 0 del chasis 1746. Importante:Los procesadores modulares SLC 500t deben insertarse en la ranura izquierda (ranura 0), como se muestra a continuación. Adicionalmente, retire la cubierta protectora después de instalar el procesador. Fuente de alimentación eléctrica Desenganche del procesador Guia de tarjetas Cubierta protectora Conecte la alimentación eléctrica al procesador 1. Energize la fuente de alimentación eléctrica del chasis. 2. Revise los indicadores LED de la fuente de alimentación eléctrica y del procesador. El indicador LED de power (alimentación eléctrica) en la fuente de alimentación eléctrica debe estar encendido y el indicador LED de fault (fallo) en el procesador debe estar parpadenado. Indicadores LED de la fuente de alimentacion electrica y de SLC 5/01 y SLC 5/02 POWER 1747-5.25 COMM RUN CPU FAULT FORCED I/O BATTERY LOW Indica que el LED esta APAGADO. Indica que el LED esta ENCENDIDO. Indica que el LED esta PARPADEANDO. El estado del LED no interesa. El indicador LED de RUN en el procesador SLC 5/01 esta marcado como “PC RUN.” Tambien, el procesador SLC 5/01 no tiene un indicador LED de COMUNICACION. 57 Para cargar el software Consulte la documentación del software de programación. Para establecer comunicaciones con el procesador 1. Conecte el 1747-PIC al procesador y a su computadora personal. 2. Configure los parámetros de comunicación del software de manera que sean iguales a los parámetros predeterminados del procesador: • DH-485 • 19.2k baud • Dirección de nodo = 1 Localización y corrección de fallos Antes de localizar y corregir fallos del sistema SLC 500, por favor consiga un Manual de instalación y operación del hardware estilo modular SLC 500 (1747-6.2) de uno de los proveedores listados en la página 16. Consulte el capítulo de Localización y corrección de fallos. Además del Manual de instalación y operación del hardware estilo modular SLC 500, también se puede obtener el Manual de referencia del conjunto de instrucciones SLC 500 y MicroLogix 1000 (1747-6.15ES) de los proveedores listados en la página 16. Este manual contiene explicaciones y ejemplos para el todo el conjunto de instrucciones así como para todas las palabras y bits de estado. También contiene explicaciones para todos los posibles códigos de fallo que se encuentran en la palabra de estado S:6. 1747-5.25 Allen-Bradley Replacements 58 Especificaciones SLC 5/01 (1747-L511, -L514) Especificación SLC 5/02 (1747-L524) Memoria de programa Instrucciones 1K ó 4K Instrucciones 4K Almacenamiento adicional de datos 0 0 Capacidad máxima de E/ S 3940 entradas discretas 3940 salidas discretas 4096 entradas discretas 4096 salidas discretas Máx. de ranuras/chasis locales 3/30 3/30 Software de programación RSLogix 500t, PLC-500 A.I. Seriest, APS y HHT Instrucciones de programación 52 71 Tiempo de escán típico(1) 8 ms/K 4.8 ms/K Ejecución de bit (XIC) 4 µs 2.4 µs (1) Los tiempos de escán son típicos para un programa de lógica de escalera de 1k que consiste de una lógica de escalera simple y servicio de comunicación. Los tiempos de escán reales dependen del tamaño del programa, instrucciones usadas y el protocolo de comunicación. Comunicación DH-485 (1) Recepción SLC 5/01(1) Recepción o iniciación SLC 5/02(1) Se necesita un 1747-PIC al conectarse con el canal DH-485 para programación. 1747-5.25 59 Descripción Especificación Carga de fuente de alimentación eléctrica a 5 VCC 350 mA Carga de fuente de alimentación eléctrica a 24 VCC 105 mA Tiempo de retención del escán de programa después de pérdida de alimentación eléctrica 20 ms a 3 s (dependiendo de la carga de la fuente de alimentación eléctrica) Inmunidad al ruido Estándar NEMA ICS 2-230 Vibración Desplazamiento: 0.015 pulgadas, pico a pico a 5-57 Hz Aceleración: 2.5 Gs at 57-2000 Hz Choque (operativo) 30 Gs Límites de temperatura ambiente Operativo: 0 a + 60°C (32°F a 140°F) Almacenamiento: -40°C a 85°C (-40°F a 185°F) Humedad 5 a 95% sin condensación Certificación de agencia Listado UL Aprobación CSA Clase 1, Grupos A, B, C o D, División 2 Cumple con todas las directivas aplicables de la CE La siguiente tabla resume las opciones de memoria de seguridad (back up) disponibles para los procesadores SLC 5/01 y SLC 5/02. Los módulos de memoria EEPROM y UVPROM proporcionan una memoria de seguridad (back up) no volátil. Opción de memoria de seguridad (back up) SLC 5/01 (1747-L511/1747-L514) SLC 5/02 (1747-L524) EEPROM 1747-M1, 1747-M2 1747-M2 UVPROM 1747-M3, 1747-M4 1747-M4 1747-5.25 Allen-Bradley Replacements 60 Manipulación, almacenamiento y transporte de la batería (Cat. No. 1747-BA) Manipulación  ATENCION: No cargue las baterías. Una explosión podría producirse o las celdas se podrían recalentar y causar quemaduras. No abra, haga agujeros, golpee ni de alguna manera mutile las baterías. Puede producirse una explosión y/o quedarían expuestos líquidos tóxicos, corrosivos e inflamables. Almacenamiento Almacene las baterías de litio en un ambiente fresco y seco, típicamente entre +20° C a +25° C (+68° F a +77° F) y 40% a 60% de humedad relativa. Transporte Una o dos baterías — Se pueden enviar hasta dos baterías juntas dentro de los Estados Unidos sin restricciones. Las normas que gobiernan el transporte a otros países y dentro de otros países pueden ser diferentes. Tres o más baterías — Los procedimientos para el transporte de tres o más baterías enviadas juntas dentro de los Estados Unidas están especificados por el Departamento de Transporte (DOT) en el Código de reglamentos federales , CFR49, “Transporte”. Una excepción a este reglamento, DOT - E7052, cubre el transporte de ciertos materiales peligrosos clasificados como sólidos inflamables. Esta excepción autoriza el transporte de baterías de litio en vehículos motorizados, vagones de carga, barcos de carga y aviones de carga solamente, siempre y cuando se cumplan ciertas condiciones. No se permite el transporte en aviones de pasajeros. El transporte de baterías agotadas para desecho puede estar sujeto a reglamentos específicos de los países envueltos o reglamentos aprobados por esos países, tales como los Reglamentos de artículos restringidos IATA de la Asociación de transporte aéreo internacional, Ginebra, Suiza. Importante: 1747-5.25 Los reglamentos para el transporte de baterías de litio se revisan periódicamente. 61 -  ATENCION: No incinere ni deseche las baterías de litio en tiraderos de basura generales. Es posible que se produzcan explosiones o rupturas violentas. Las baterías deben ser recogidas para desecho de una manera que se evite el corto circuito, la compactación o la destrucción de la integridad de la caja y sello hermético. Para el desecho, las baterías deben ser empacadas y enviadas de acuerdo con los reglamentos de transporte, a un local de desecho adecuado. El Departamento de transporte de los EE.UU. autoriza el transporte de “Baterías de litio para desecho” en vehículos motorizados sólo en el reglamento 173.1015 de CFR 49 (vigente a partir del 5 de enero de 1983). Para obtener más información comuníquese con: U.S. Department of Transportation Research and Special Programs Administration 400 Seventh Street, S.W. Washington, D.C. 20590 Si bien la Agencia para la protección del medio ambiente en este momento no tiene reglamentos específicos referentes a las baterías de litio, el material contenido puede considerarse tóxico, reactivo o corrosivo. La persona que está desechando el material es responsable por los peligros creados como resultado de hacerlo. Pueden existir reglamentos estatales y locales referentes al desecho de estos materiales. Para obtener una hoja de datos de seguridad para materiales de baterías de litio, comuníquese con el fabricante: Sanyo Energy Corporation 600 Supreme Drive Bensenville, IL 60106 1747-5.25 Allen-Bradley Replacements Publication 1747-5.25 - June 1999 PN 40072-038-01 (B) Supersedes Publication 1747-5.25 - December 1996 © 1999 Rockwell International Corporation. All rights reserved. Printed in the U.S.A.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60

Allen-Bradley SLC 5/01 Installation Instructions Manual

Tipo
Installation Instructions Manual
Este manual también es adecuado para