WEG Electric motors for Hazardous Areas Manual de usuario

Tipo
Manual de usuario
Motores eléctricos para
atmósferas explosivas
Instrucciones de seguridad para instalación,
operación y mantenimiento de motores eléctricos
Motors | Automation | Energy | Transmission & Distribution | Coatings
Electric motors for
explosive atmospheres
Instructions manual for installation,
operation and maintenance of electric motors
Cod: 50034031 | Rev: 13 | Date (m/y): 07/2019
The values shown are subject to change without prior notice.
1 2 3 4
8 9 10 11 12 13 14
5 76
BRAZIL
WEG EQUIPAMENTOS ETRICOS S.A.
Av. Prefeito Waldemar Grubba, 3000
89256-900 - Jaraguá do Sul - SC
Phone: 55 (47) 3276-4000
www.weg.net/br
CHINA
WEG (NANTONG) ELECTRIC MOTOR MANUFACTURING CO., LTD.
No. 128# - Xinkai South Road,
Nantong Economic &
Technical Development Zone, Nantong, Jiangsu Province.
Phone: (86) 0513-85989333
WEG (Jiangsu) Electric Equipment CO., LTD.
No. 15 Group, North City Street, Dengyuan Community
Rugao City, Jiangsu Province – China
www.weg.net/cn
MEXICO
WEG MEXICO, S.A. DE C.V.
Carretera Jorobas-Tula Km. 3.5, Manzana 5, Lote 1
Fraccionamiento Parque
Industrial - Huehuetoca,
Estado de México - C.P. 54680
Phone: + 52 (55) 5321 4275
www.weg.net/mx
PORTUGAL
WEG EURO - INDÚSTRIA ELÉCTRICA, S.A.
Rua Eng. Frederico Ulrich
Apartado 6074
4476-908 - Maia
Phone(s): +351 229 477 705
www.weg.net/pt
More languages see website www.weg.net
1. INTRODUCCIÓN
La instalacn, operación y mantenimiento del motor debe
llevarse siempre a cabo por personal cualificado y autorizado,
utilizando herramientas y métodos adecuados, y siguiendo los
procedimientos indicados en los documentos suministrados
con el motor.
Las instrucciones presentadas en este documento son válidas para
motores WEG con las siguientes características:
g Motores de inducción trifásicos y monofásicos (con rotor de jaula);
g Motores trifásicos de imanes permanentes;
g Motores trifásicos híbridos (con rotor de jaula + imanes
permanentes);
Estos motores pueden ser utilizados en áreas clasificadas con los
siguientes tipos de protección:
g Seguridad Aumentada – “Ex eb;
g A Prueba de Explosn – “Ex db” o “Ex db eb”;
g Proteccn por carcasa (polvo conductivo) – “Ex t”;
g Clase I Divisn 1;
g Clase I Divisn 2;
g Clase II División 1;
g Clase II División 2.
Los detalles de la marcación pueden ser encontrados en la placa de
caractesticas y en el certificado del producto, que forma parte de la
documentación del motor. Como referencia, este manual presenta la
lista de certificados para cada tipo de protección y su marcacn.
Además de eso, las normas aplicables pueden ser encontradas en
los certificados del producto y en el “Manual General de Instalación,
Operacn y Mantenimiento de Motores Eléctricos para Atmósferas
Explosivas” – código 50034162. El manual está disponible en el sitio
web:
www.weg.net.
El objetivo de este manual es aportar informaciones importantes que
deben ser seguidas durante el transporte, almacenamiento,
instalación, funcionamiento y mantenimiento de los motores WEG.
Por ese motivo, recomendamos leer atentamente las instrucciones
antes de hacer cualquier intervención en el motor. El incumplimiento
de las instrucciones reflejadas en este manual, y demás instrucciones
a las que se hace referencia en el sitio www.weg.net, ocasionará la
anulación de la garantía del producto, y puede comprometer el tipo de
protección del motor y ocasionar serios daños personales y materiales.
Cualquier componente añadido al motor por el usuario,
como por ejemplo, prensa, tapón, encoder, etc., debe
corresponder al tipo de proteccn de la carcasa, el
“nivel de proteccn de equipamiento” (EPL) y el grado de
protección del motor, de acuerdo con las normas indicadas en
el certificado del producto.
Condiciones especiales de utilización
El símbolo “X” junto al número de certificado, reflejado
en la placa de características del motor, indica que el
mismo requiere condiciones especiales de instalación,
utilización y/o mantenimiento del equipo, siendo éstas
descritas en el certificado y suministradas en la documentación
del motor. Como referencia, el capítulo 8 presenta la lista de
certificados para cada tipo de protección y su marcación en
placa. El incumplimiento de estos requisitos compromete la
seguridad del producto y de su instalacn.
La correcta clasificación del área de instalación y de las
características del ambiente es de responsabilidad del usuario.
Los motores eléctricos tienen circuitos bajo tensión, y
componentes giratorios que pueden causar daños a las personas.
2. Transporte, almacenamiento y manipulación
Verifique la situación del motor al recibirlo. De encontrarse daños,
estos deben ser informados por escrito a la agencia de transporte, y
comunicarlos inmediatamente tanto a la empresa aseguradora como a
WEG. En ese caso, no se debe iniciar ningún trabajo de instalación hasta
que se haya solucionado el problema encontrado.
Los datos que aparecen en la placa de caractesticas, deben
corresponder con los del pedido del producto y las condiciones
ambientales de trabajo en el lugar donde el motor será instalado, con el
tipo de proteccn y nivel de proteccn de equipamiento (EPL). En caso
de que el motor no fuera instalado inmediatamente, se recomienda
almacenarlo en lugar limpio y seco, libre de polvo, vibraciones, gases y
agentes corrosivos, y con una humedad relativa del aire no superior al
60%. Para evitar la condensacn de agua en el interior del motor durante
el período de almacenamiento, se recomienda mantener la resistencia de
ESPAÑOL
caldeo encendida (de estar incluida). Para evitar la oxidacn de los
rodamientos y asegurar una distribución uniforme del lubricante, gire el
eje del motor por lo menos una vez por mes (dando, como mínimo, 5
vueltas) y dejándolo siempre en una posición diferente. Para rodamientos
con sistema de lubricacn tipo “oil mist, el motor debe estar ubicado en
posición horizontal, independientemente de su forma constructiva, con
aceite ISO VG 68 en el rodamiento, con la cantidad indicada en el manual
disponible en la página web, y el eje debe girarse semanalmente. En caso
de que los motores queden almacenados por un periodo superior a 2
años, se recomienda cambiar los rodamientos, o como alternativa,
desmontarlos, lavarlos, revisarlos y lubricarlos nuevamente antes de
hacer trabajar el motor. Tras este período de almacenamiento tambn se
recomienda que los condensadores de arranque de motores
monofásicos sean cambiados debido a posibles pérdidas de sus
características de trabajo.
Toda manipulación del motor debe ser realizada con
cuidado para evitar impactos y dos a los cojinetes, y
con el dispositivo de transporte/bloqueo del eje (de ser
suministrado) siempre instalado. Levante el motor
siempre por los elementos de elevacn, los cuales han sido
diseñados para el peso del motor, y nunca deben utilizarse para
levantar cargas adicionales acopladas. Los elementos de
elevación de los componentes, como la caja de bornes, la tapa
deflectora, etc., deben utilizarse solo para manipular estas
piezas cuando estén desmontadas. En el manual general
disponible en la página web, se podrá encontrar información
adicional sobre los ángulos máximos de elevación.
Mida periódicamente la resistencia de aislamiento del motor y sobre
todo, antes de la primera puesta en marcha. Verifique los valores
recomendados y los procedimientos de medicn en la página web.
3. Instalación
Durante la instalacn, los motores deben estar
protegidos contra puestas en marcha accidentales.
Verifique el sentido de rotación del motor, haciéndolo
funcionar en vacío antes de acoplarlo a la carga.
Elimine los dispositivos de transporte y de bloqueo del eje (en caso que
existan) antes de iniciar la instalación del motor.
Los motores solo deben estar instalados en lugares compatibles con
sus características constructivas y en las aplicaciones y ambientes
reflejados en la documentación del producto. Debe ser respetado el tipo
de proteccn y el EPL indicados en la placa de características del motor,
de acuerdo con la clasificación del área donde el motor será instalado.
Los motores con patas deben estar ubicados sobre bases
debidamente proyectadas para evitar vibraciones y asegurar un perfecto
alineamiento. El eje del motor debe estar adecuadamente alineado con
el eje de la máquina accionada.
Un alineamiento incorrecto, así como una tensión inadecuada de las
correas de accionamiento, seguramente dañarán los rodamientos,
resultando en excesivas vibraciones e incluso causar la ruptura del eje.
Se deben respetar las cargas radiales y axiales admisibles en el eje, las
cuales se indican en el manual general disponible en la página web. Se
recomienda el uso de acoplamientos flexibles.
En los motores con rodamientos cuya lubricación sea a base de aceite o
un sistema de lubricación tipo “oil mist”, conecte los tubos de
refrigeración y lubricación (caso de estar disponibles).
Para cojinetes con lubricación a aceite, el nivel de aceite debe
permanecer en la mitad del visor de nivel.
Elimine la grasa de proteccn contra corrosn de la punta del eje y de la
brida únicamente justo antes de la instalación del motor.
A no ser que se especifique lo contrario en el pedido de compra, los
motores WEG se equilibran dinámicamente con “media chaveta” y en
vacío (desacoplados). Los elementos de transmisión, como poleas,
acoplamientos, etc., deben equilibrarse antes de ser instalados en el eje
del motor.
Los motores siempre deben estar posicionados de
forma que el drenaje sea facilitado (en el punto mas bajo
del motor). Motores con drenaje de goma salen de la
fabrica en la posicion cerrado y deben ser abiertos
periodicamente para permitir la salida del agua condensado. Para
ambientes con elevada condensacion del agua y motores con
grado de proteccion IP55, los drenajes pueden ser armados en la
posicion abierto. Para motores con grado de proteccion IP56,
IP65 o IP66, los drenajes deben permanecer en la posicion
cerrado, siendo abiertos solamente durante el mantenimiento del
motor.
Los motores con lubricacion de tipo Oil Mist deben tener sus
drenajes conectados a un sistema de recoleccion especifico.
Los drenajes de motores a prueba de explosn no se pueden
quitar durante los procedimientos de instalación y mantenimiento.
Para el dimensionamiento de los cables de alimentación y de
los dispositivos de maniobra y proteccn se debe considerar
la corriente nominal del motor, el factor de servicio, la longitud
de los cables, entre otros.
Para motores sin placa de bornes, aísle los terminales del
motor, utilizando materiales aislantes compatibles con la clase
de aislamiento informada en la placa de características.
La distancia mínima de aislamiento entre partes vivas no
aisladas entre sí y entre partes vivas y la tierra debe respetar
las normas y reglamentaciones vigentes en cada país.
Tabla 3 - Temperatura máxima de actuación de las protecciones térmicas
No cubra u obstruya la ventilación del motor. Mantenga
una distancia libre mínimo de ¼ (25%) del diámetro de
la entrada de aire de la deflectora en relación a la
distancia de las paredes. El aire utilizado para la refrigeracn del
motor debe estar a temperatura ambiente, limitada a la
temperatura indicada en la placa de características del motor
(caso de no estar indicado, considerar de -20 °C a +40 °C).
Para motores instalados a la intemperie o montados en la
posición vertical, se necesitará utilizar una protección adicional
contra la entrada de líquidos y/o partículas sólidas, por ejemplo,
el uso de un sombrerete.
Para evitar accidentes, con anterioridad al arranque del motor,
se ha de asegurar que la puesta a tierra fue realizada conforme a
las normas vigentes y que la conexn esté bien apretada.
Conecte el motor correctamente a la red ectrica a través de
contactos seguros y permanentes, siguiendo siempre los datos
mostrados en la placa de características, como la tensión
nominal, el esquema de conexionado, etc.
Cuando se utilicen terminales, todos los conductores que forman
el cable trenzado deben estar fijados dentro de la camisa. El
aislamiento de los cables de los accesorios debe ser mantenido
hasta 1 mm desde el punto de conexn del conector.
Para la conexión del cable de alimentación, sistema de puesta a tierra
y montaje de la tapa de la caja de bornes, deben ser respetados los
pares de apriete indicados en las Tablas 1 y 2.
Tabla 1 - Pares de apriete para elementos de fijación [Nm]
Notas:
1) La cantidad y el tipo de protección térmica instalada en el motor están
informados en las placas adicionales del mismo.
2) En el caso de proteccn térmica con resistencia calibrada (por ejemplo,
Pt-100), el sistema de monitoreo debe ser ajustado a la temperatura de
operación indicada en la Tabla 3.
Tomar las medidas necesarias para asegurar el tipo
de proteccn, el EPL y el grado de protección
indicado en la placa de identificación del motor:
- En las entradas de cables no utilizadas de la caja de
conexiones, las cuales deben ser debidamente cerradas con
tapones certificados;
- En componentes suministrados de forma independiente
(por ejemplo cajas de conexiones montadas por separado).
Las entradas de cables utilizadas para alimentación y control
deben emplear componentes (como, por ejemplo, prensas y
pasacables) que respeten las normas y reglamentaciones
vigentes en cada ps. Para motores “Ex db”, los pasacables
están permitidos solamente para equipamientos eléctricos
del grupo II.
Los elementos de fijación montados en agujeros roscados
pasantes del involucro del motor (por ejemplo, en la brida)
deben ser sellados, con los productos enumerados en el
punto 5, para asegurar el grado de proteccn indicado en la
placa de identificación del motor.
El motor debe ser protegido con dispositivos de proteccn contra
sobrecarga. Estos dispositivos de protección pueden ser integrados
en el motor (tales como termistores en los devanados) o dispositivos
de protección externos, donde la carga del motor se controla por la
corriente nominal. Para motores trifásicos se recomienda también la
instalación de sistemas de protección contra fallo de fase.
Componente
Marcación del
área clasificada
en la placa de
identificación
Área clasificada
donde el
producto será
instalado
Temperatura máxima de
operación (°C)
Alarma Apagado
Bobinado
Ex db Ex db 130 150
Ex ec Ex ec 130 155
Ex t Ex t 120 140
Ex eb Ex eb - 110
Ex ec + Ex t
Ex ec 140 155
Ex t - 140
Ex db + Ex t
Ex db 140 150
Ex t - 140
Clase I Div. 1 Clase I Div. 1 130 150
Clase I Div. 2 Clase I Div. 2 130 155
Clase II Div. 1 Clase II Div. 1 120 140
Cojinete Todas Todas 110 120
Tipo de
protección
Componente M4 M5 M6 M8 M10 M12 M14 M16 M20
Clase I
División 1
Clase II
División 1
Clase I
Zona 1
Tapa de
la caja de
conexión
Clase
8.8/12.9
- 3,5 a 5 6 a 12 14 a 30 28 a 60 45 a 105 75 a 110
115 a
170
230 a
330
Clase
A2-70 /
A4-70
- 3,5 a 5 6 a 8,5 14 a 19 28 a 40 45 a 60 75 a 100
115 a
170
225 a
290
Puesta a tierra 1,5 a 3 3 a 5 5 a 10 10 a 18 28 a 40 45 a 70 -
115 a
170
-
Placa de bornes /
cables sueltos
1 a 1,5 2 a 4 4 a 6,5 6,5 a 9 10 a 18 15,5 a 30 - 30 a 50 50 a 75
Clase I
División 2
Clase II
División 2
Clase I
Zona 2
Tapa de la caja de
conexión
- 3 a 5 4 a 8 8 a 15 18 a 30 25 a 40 30 a 45 35 a 50 -
Puesta a tierra 1,5 a 3 3 a 5 5 a 10 10 a 18 28 a 40 45 a 70 -
115 a
170
-
Placa de bornes /
cables sueltos
1 a 1,5 2 a 4 4 a 6,5 6,5 a 9 10 a 18 15,5 a 30 - 30 a 50 50 a 75
Tornillos de fijación
de la placa de
bornes
- 3 a 5 5 a 10 10 a 18 28 a 40 45 a 70 75 a 110
115 a
170
-
Tabla 2 - Pares de apriete para prensa cables y tapón [Nm]
Rosca Material M16 M20 M25 M32 M40 M50 M63 M80
Métrica
Plástico 3 a 5 3 a 5 6 a 8 6 a 8 6 a 8 6 a 8 6 a 8 6 a 8
Metálico 40 a 50 40 a 50 55 a 70 65 a 80 80 a 100 100 a 120 115 a 140 160 a 190
Rosca Material
NPT
1/2"
NPT
3/4"
NPT
1"
NPT
1 1/2"
NPT
2"
NPT
2 1/2"
NPT
3"
NPT
4"
NPT
Plástico - 5 a 6 6 a 8 6 a 8 6 a 8 6 a 8 6 a 8 6 a 8
Metálico 40 a 50 40 a 50 55 a 70 65 a 80 100 a 120 115 a 140 150 a 175 200 a 240
Los motores con conexión triángulo deben ser protegidos contra la
caída de una de las fases. Para eso, se
debe conectar el relé en serie con las fases del devanado y ajustarlo
en 0,58 veces la corriente nominal.
Para motores Clase I y II Divisn 1 y / o motores accionados por
convertidor de frecuencia, es obligatorio el uso de protecciones
térmicas (excepto las clases de temperatura T2B o más).
Para motores División 2 o área segura, el uso de las protecciones
térmicas es opcional.
Para motores sin placa de bornes, no forzar los cables
de alimentacn para el interior para evitar contacto
con el rotor.
Verifique el correcto funcionamiento de los accesorios (freno,
encoder, protección térmica, ventilación forzada, etc.) instalados en el
motor antes del arranque.
Los límites de temperatura de alarma y disparo de las protecciones
térmicas pueden ser definidos de acuerdo a la aplicación, no
obstante, no deben sobrepasar los valores indicados en la Tabla 3.
4. Funcionamiento
Durante el funcionamiento, no toque las zonas
con riesgo de contacto ectrico, y nunca toque o
permanezca muy cerca de partes giratorias.
Asegúrese de que la resistencia de caldeo es
desconectada durante el funcionamiento del
motor.
Los valores nominales de trabajo y las condiciones de
funcionamiento están especificados en la placa de características
del motor. Las variaciones de la tensión y la frecuencia de
alimentación nunca deben exceder los límites establecidos en las
normas vigentes. Posibles desvíos en relación al normal
funcionamiento (actuación de las protecciones térmicas, aumento
de los niveles de ruido y vibración, temperatura y corriente) deben
ser evaluados por personal cualificado.
No se recomienda la utilización de rodamiento de cilindros para
acoplamiento directo. Los motores equipados con estos
rodamientos necesitan una carga radial mínima para garantizar su
correcto funcionamiento.
Los sistemas de lubricacn de los cojinetes de aceite u “oil mist” y
de refrigeración tienen que permanecer conectados incluso tras el
5. Mantenimiento
Antes de iniciar cualquier tipo de servicio en el
motor, éste debe estar completamente parado,
desconectado de la red de alimentacn y
protegido contra una posible reconexión. Aunque
el motor estuviese parado, puede haber tensión en los
terminales de las resistencias de caldeo.
El desmontaje del motor durante el período de garana
solamente debe ser realizado por un servicio técnico
autorizado WEG para atmósferas explosivas.
En el caso de motores con rotor de imanes permanentes
(lineas W22 Quattro y W22 Magnet), el montaje y desmontaje
del motor requiere de la utilización de dispositivos
adecuados debido a las fuerzas de atraccn o de repulsión
entre piezas metálicas. Este servicio solamente debe
llevarse a cabo por un Servicio Técnico Autorizado WEG con
formación específica para dicha operación.
Las personas que utilicen marcapasos no pueden manipular
estos motores. Los imanes permanentes también pueden
causar perturbaciones o daños en otros equipamientos
eléctricos y componentes durante el mantenimiento.
Para motores a prueba de explosión o con proteccn por
carcasa, abra la caja de conexn y/o desmonte el motor
solamente cuando la temperatura superficial esté a la
temperatura ambiente.
En los motores de las líneas W40, W50 y HGF, suministrados
con ventiladores axiales, el motor y el ventilador axial tienen
indicación de sentido de rotación distintas, para prevenir un
montaje erróneo. El ventilador debe ser montado de tal
forma que la flecha indicativa del sentido de rotacn este
siempre visible, cuando observadas desde el lado externo
del motor (en el lado no accionado). La marca indicada en
las aspas del ventilador, CW para sentido de rotación
horario o CCW para sentido de rotación anti-horario, indica
el sentido de rotación del motor.
Para el montaje de las tapas de la caja de conexn, observe los
pares de apriete indicados en la Tabla 1.
En caso de reemplazo de un elemento de fijación, es necesario
que la calidad y las dimensiones del mismo sean respetadas.
Para motores a prueba de explosn, los elementos de fijación
deberán tener una resistencia a tracción igual o superior a clase
12.9, para material de acero carbono y, clase A2-70 o A4-70, en
material de acero inoxidable.
Motores que poseen riesgo potencial de acumulación de carga
electrostática, suministrados debidamente identificados, deben
ser limpiados de manera cuidadosa, como por ejemplo, con
uso de po húmedo, a fin de evitar la generación de
descargas electrostáticas.
Tabla 4 - Holgura máxima entre tapa y caja de conexión
Para motores con protección por carcasa (del grupo III), se
permite una capa de polvo combustible sobre el envoltorio de
un máximo de cinco milímetros (5 mm).
Inspeccione periódicamente el funcionamiento del
motor según su aplicacn, asegurándose de que el
aire fluya libremente. Inspeccione los sellos, los
tornillos de fijación, los cojinetes, los niveles de vibración y
ruido, los drenajes, etc.
El intervalo de lubricación está especificado en la placa de
identificación del motor.
6. Instrucciones adicionales
Para informaciones adicionales sobre transporte, almacenaje,
manipulación, instalación, funcionamiento y mantenimiento de
motores eléctricos, entre en
www.weg.net.
Para aplicaciones y condiciones especiales de trabajo (ejemplo:
motores de extracción de humos, totally enclosed air over (TEAO),
motores para altas cargas radiales y axiales, motores con freno,
motores con encoder) se debe consultar el manual específico
suministrado con el equipamiento, o el manual en el sitio o entrar
en contacto con WEG.
Al entrar en contacto con WEG, tenga a mano la denominacn
completa del motor, así como también su número de serie y fecha
de fabricación indicados en la placa de características del mismo.
7. Términos de garantía
WEG Equipamentos Elétricos S/A, Unidad Motores (“WEG”),
ofrece garantía contra defectos de fabricación o de materiales para
sus productos por un período de 18 meses, contados a partir de la
fecha de emisión de la factura de fábrica, o del distribuidor/
revendedor, limitado a 24 meses de la fecha de fabricación.
Para motores de las líneas HGF y W60, la garantía ofrecida es de
12 meses, contados a partir de la fecha de emisión de la factura de
brica, o del distribuidor/revendedor, limitado a 18 meses a partir
de la fecha de fabricación.
El párrafo anterior cuenta con los plazos de garantía legal, no
siendo acumulativos entre sí.
En caso de que un plazo de garantía diferenciado esté definido en
la propuesta técnica comercial para un determinado suministro,
éste prevalecerá por sobre los plazos definidos anteriormente.
Los plazos establecidos anteriormente no dependen de la fecha
de instalacn del producto ni de su puesta en operacn.
8. Certificados
Las siguientes tablas muestran la lista de motores para cada
tipo de proteccn, sus certificados y su marcacn en la placa
de características:
Ante un desvío en relación a la operación normal del producto, el
cliente debe comunicar inmediatamente por escrito a WEG sobre
los defectos ocurridos, y poner a disposición el producto para
WEG o su Asistente Técnico Autorizado por el plazo necesario
para la identificación de la causa del deso, verificación de la
cobertura de garantía, y para su debida reparación.
Para tener derecho a la garantía, el cliente debe cumplir las
especificaciones de los documentos técnicos de WEG,
especialmente aquellas previstas en el Manual de Instalación,
Operacn y Mantenimiento de los productos, y las normas y
regulaciones vigentes en cada país.
No poseen cobertura de garantía los defectos derivados de
utilización, operación y/o instalación inadecuadas o inapropiadas
de los equipos, su falta de mantenimiento preventivo, así como
defectos derivados de factores externos o equipos y
componentes no suministrados por WEG.
La garantía no se aplica si el cliente, por iniciativa propia, efectúa
reparaciones y/o modificaciones en el equipo sin previo
consentimiento por escrito de WEG.
La garantía no cubre equipos, partes y/o componentes, cuya vida
útil sea inferior al peodo de garantía. No cubre, igualmente,
defectos y/o problemas derivados de fuerza mayor u otras causas
que no puedan ser atribuidas a WEG, como por ejemplo, pero no
limitado a: especificaciones o datos incorrectos o incompletos por
parte del cliente, transporte, almacenado, manipulación,
instalación, operación y mantenimiento en desacuerdo con las
instrucciones suministradas, accidentes, deficiencias de obras
civiles, utilización en aplicaciones y/o ambientes para los cuales el
producto no fue proyectado, equipos y/o componentes no
incluidos en el alcance de suministro de WEG. La garantía no
incluye los servicios de desmantelamiento en las instalaciones del
cliente, los costos de transporte del producto, los costos de
locomoción, hospedaje y alimentación del personal de Asistencia
Técnica, cuando sean solicitados por el cliente.
Los servicios en garantía serán prestados exclusivamente en
talleres de Asistencia Técnica autorizadas por WEG o en su propia
fábrica. Bajo ninguna hipótesis, estos servicios en garantía
prorrogarán los plazos de garantía del equipo.
La responsabilidad civil de WEG está limitada al producto
suministrado, no responsabilizándose por daños indirectos o
emergentes, tales como lucros cesantes, pérdidas de ingresos y
similares que deriven del contrato firmado entre las partes.
Los motores con grado de protección superior a IP55 son
suministrados con elemento sellador en los encajes y tornillos. Antes
de montar los componentes mecanizados (por ejemplo, tapas de la
caja de conexión de motores a prueba de explosión), limpie las
superficies y aplique una nueva capa de este producto.
Para motores a prueba de explosn, utilice en los encajes solamente
los siguientes productos anticorrosivos: Lumomoly PT/4 (fabricante
Lumobras para rango de temperatura ambiente -20 °C a +80 °C) o
Molykote DC 33 (fabricante Dow Corning para rango de -55 °C a +80
°C). Para los des tipos de proteccn, utilice en los encajes el
producto Loctite 5923 (fabricante Henkel).
Para motores a prueba de explosn, debe tenerse un cuidado
adicional con las superficies mecanizadas para paso de de llama, de
manera de no contener rebordes, roturas, etc., que reduzcan su
longitud y/o aumenten la holgura del paso de llama. Para las cajas de
bornes a prueba de llama y sus respectivas tapas, la holgura entre las
mismas no debe exceder los valores indicados en la Tabla 4.
corte de alimentación, y hasta la parada total de la máquina.
En caso de fallas en el sistema de lubricación y/o refrigeración,
desconecte el motor inmediatamente.
Tras la parada del motor, los sistemas de refrigeración y de
lubricacn (de existir) deben desconectarse y se deben
conectar las resistencias de caldeo (de existir).
En caso de dudas, desconecte el motor inmediatamente y
contacte al asistente técnico autorizado WEG para atmósferas
explosivas más cercano.
Línea de
producto
Carcasa
Junta plana Junta cilíndrica
Holgura
(max)
Largo
(min)
Holgura
(max)
Largo
(min)
W21Xdb
IEC 90 hasta 355
NEMA 143
hasta 586/7
0,05 mm
Bajo
consulta
No disponible
W22Xdb
IEC 71 y 80
No disponible 0,15 mm 12,5 mm
IEC 90 hasta 355
NEMA 143
hasta 586/7
0,075 mm 6 mm 0,15 mm 19 mm
Certificados UL:
Modelo Marcaje Nº Certificado
Div 1 - Zona peligrosa
Carcasas 143-326,
trifásico
Clase I, Div 1,
Grupos C y D, T4
Archivo E87848
- Sec 1
Clase II, Div 1,
Grupos F y G, T4
Carcasas 364-587,
trifásico
Clase I, Div 1,
Grupos C y D, T3C
Archivo E87848
- Sec 2
Clase II, Div 1,
Grupos F y G, T3C
Carcasas 56 y 61
trifásico/monofásico
Clase I, Div 1,
Grupo D, T3B
Archivo E87848
- Sec 3
Carcasa 61,
trifásico/monofásico
Clase I, Div 1,
Grupo D, T3C
Archivo E87848
- Sec 4
El tiempo “t
E
” indicado en la placa del motor no podrá ser rebasado. Los
motores “Ex e, sometidos a condiciones de tiempo de aceleración
mayor a 1,7 x tiempo “t
E
, deben ser protegidos con dispositivo de
protección contra sobrecorriente.
Los motores equipados con protectores térmicos del tipo
Automático se reconectarán automáticamente cuando se
alcance la temperatura adecuada para el motor.
No utilizar motores con protección térmica del tipo
automática en aplicaciones en donde el rearranque automático
pueda ser peligroso para personas o para el equipamiento.
En caso de que se active la protección térmica del tipo
Automático, desconecte el motor de la red ectrica y verifique la
causa que provocó la actuacn del protector térmico.
Para los motores de la línea W60 con intercambiador de calor aire/agua,
consulte los datos de agua en la placa fija del radiador.
Para más información sobre el uso del inversor de frecuencia es
obligatorio seguir las instrucciones del manual del motor en
www.weg.net y del manual del convertidor de frecuencia.
En la aplicacn de motores “Ex e”, el dispositivo de proteccn térmica,
en caso de sobrecarga o de rotor bloqueado, debe actuar con tiempo
retardado, en función de la corriente y comprobación de los cables de
alimentación externos.
Certificados CSA:
Modelo Marcaje Nº Certificado
Div 1 - Zona peligrosa
Carcasas 143-587,
trifásico
Clase I, Div 1,
Grupos C y D, T3C
1629892
Clase II, Div 1,
Grupos F y G, T3C
Carcasa 56
trifásico/monofásico
Clase I, Div 1,
Grupos C y D, T3C
File LR 50962
Clase II, Div 1,
Grupos F y G, T3C
Carcasa 61
trifásico/monofásico
Clase I, Div 1,
Grupos D, T3C
File LR 50962
Carcasa 56
trifásico/monofásico
Clase I, Div 1,
Grupos D, T3C
Div 2 - Zona peligrosa
Carcasas 56, 143-587,
trifásico (W21)
Clase I, Div 2,
Grupos A, B, C y D, T4 - T2D
1619832
Clase II, Div 2,
Grupos F y G, T4 - T2D
Carcasas 143-587,
trifásico (W22)
Clase I, Div 2,
Grupos A, B, C y D, T5 - T2B
2156668
Clase II, Div 2,
Grupos F y G, T6 - T3C
Carcasas 5006-9610,
trifásico (HGF)
Clase I, Div 2, Grupos A, B, C y
D, T3 o T3C
1959652
Clase II, Div 2, Grupos F y G,
T3 o T3C
Carcasas 5009/10-
7008/09, trifásico (W50)
Clase I, Div 2, Grupos A, B, C y
D, T3 o T3C
Clase II, Div 2, Grupos F y G,
T3 o T3C
Carcasas 447/9-588/9,
trifásico (W22 Media
tensión)
Clase I, Div 2, Grupos A, B, C y D,
T3A, T3B, T2D, T4A o T5
Clase II, Div 2, Grupos F y G, T3A,
T3B, T2D, T4A o T5
Carcasas 5010, L5010,
L5810 y L6808/09,
trifásico (W40)
Clase I, Div 2, Grupos A, B, C y D,
T3, T2B, T2C y T2D
Carcasas NEMA 58 a 160
y IEC 355 a 1000) (W60)
Clase I, Div 2, Grupos A, B, C y D,
T3B, T3C, T3.
Clase II, Div 2, Grupos F y G, T3B,
T3C, T3.
70006808
19 20 21
22 23 24 25
15 16 17 18
26 27 28
5. Maintenance
Before any service is performed, ensure that motor
is at standstill, disconnected from the power supply
and protected against accidental energization.
Even when the motor is stopped, dangerous voltages may be
present in space heater terminals.
Motor disassemble during the warranty period must be
performed by a WEG authorized service center for Explosive
Atmospheres only.
In “Ex eb” motors application, the thermal protection device, in
case of overload or locked rotor, must actuate with time delay
according to the current and track the external power cables.
The “t
E
” time indicated in the motor nameplate can not be
exceeded. The “Ex eb” motors, submitted to acceleration time
conditions greater than 1,7 x “t
E
” time, must be protected with
protection devices against overcurrent.
Motors fitted with Automatic Thermal Protectors will
reset automatically as soon as the motor cools
down. Thus, do not use motors with Automatic
Thermal Protection in applications where the auto-
reseting of this device may cause injuries to people or
damage to equipment. If the Automatic Thermal Protector
trips, disconnect the motor from the power supply and check
the cause why the thermal protector trips.
For W60 motors with air-water heat exchanger, please see the
nameplate at heat-exchanger.
For more information about the use of variable frequency drives,
you must follow the instructions in the motor manual in the
website and in the manual of the variable frequency drive.
For terminal box cover mounting, please follow the tightening
torques indicated on Table 1 for fixing bolts.
In case of replacement of a fixing bolt, it is necessary to keep its
Table 4 - Maximum clearance between terminal box and
terminal box cover for flameproof motors
Notes:
1) The quantity and type of thermal protections installed in the motor are
infomed in the additional nameplates included on it.
2) In case of calibrated thermal protection (for example, Pt-100), the
monitoring system must be set at the operation temperature indicated
on Table 3.
Component
Classified area
marked on
nameplate
Classified area
where product
will be installed
Maximum operating
temperature (°C)
Alarm Tripping
Winding
Ex db Ex db 130 150
Ex ec Ex ec 130 155
Ex t Ex t 120 140
Ex eb Ex eb - 110
Ex ec + Ex t
Ex ec 140 155
Ex t - 140
Ex db + Ex t
Ex db 140 150
Ex t - 140
Class I Div. 1 Class I Div. 1 130 150
Class I Div. 2 Class I Div. 2 130 155
Class II Div. 1 Class II Div. 1 120 140
Bearings All All 110 120
dimensions and quality of material. For flameproof motors, the
yield stress of the fastener elements of motor and terminal
boxes enclosures must be at least equal to class 12.9 for
carbon steel bolts and class A2-70 or A4-70 for stainless steel
bolts.
Motors which may have a potential risk of electrostatic charge
accumulation, supplied duly identified, must receive proper
cleaning and maintenance interventions, i.e. with the use of a
damp cloth, avoiding electrostatic discharges.
For Protection by Enclosure motors (group III), the maximum
permissible dust layer on the motor enclosure is five millimeters
(5 mm).
Regularly inspect the operation of the motor,
according to its application, and ensure a free air
flow. Inspect the seals, the fastening bolts, the
bearings, the vibration and noise levels, the drain
operation, etc. The lubrication interval is specified on motor the
nameplate.
6. Additional information
8. Certificates
A list of the motors for each Type of Protection, their certificates
and markings is shown below:
Model Marking Certificate Nº
UL Certificates:
Div 1 - Hazardous Location
Frame sizes 143-326,
three-phase
Class I, Div 1,
Groups C and D, T4
File E87848 - Sec 1
Class II, Div 1,
Groups F and G, T4
Frame sizes 364-587,
three-phase
Class I, Div 1,
Groups C and D, T3C
File E87848 - Sec 2
Class II, Div 1,
Groups F and G, T3C
Frame sizes 56 and 61
three-phase/single phase
Class I, Div 1,
Group D, T3B
File E87848 - Sec 3
Frame size 61,
three-phase/single phase
Class I, Div 1,
Group D, T3C
File E87848 - Sec 4
CSA Certificates:
Div 1 - Hazardous Location
Frame sizes 143-587,
three-phase
Class I, Div 1,
Groups C and D, T3C
1629892
Class II, Div 1,
Groups F and G, T3C
Frame size 56
three-phase/single phase
Class I, Div 1,
Groups C and D, T3C
File LR 50962
Class II, Div 1,
Groups F and G, T3C
Frame size 61
three-phase/single phase
Class I, Div 1,
Group D, T3C
File LR 50962
Frame size 56
three-phase/single phase
Class I, Div 1,
Group D, T3C
Div 2 - Hazardous Location
Frame sizes 56, 143-587,
three-phase (W21)
Class I, Div 2, Groups A, B, C and
D, T4 - T2D
1619832
Class II, Div 2,
Groups F and G, T4 - T2D
Frame sizes 143-587,
three-phase (W22)
Class I, Div 2,Groups A, B, C and
D, T5 - T2B
2156668
Class II, Div 2, Groups F and G,
T6 - T3C
Frame sizes 5006-9610,
three-phase (HGF)
Class I, Div 2, Groups A, B, C and
D, T3 or T3C
1959652
Class II, Div 2, Groups F and G,
T3 or T3C
Frame sizes 5009/10-
7008/09, three-phase (W50)
Class I, Div 2, Groups A, B, C and
D, T3 or T3C
Class II, Div 2, Groups F and G,
T3 or T3C
Frame sizes 447/9 to 588/9,
three phase
(W22 Medium voltage)
Class I, Div 2, Groups A, B, C
and D, T3A, T3B, T2D, T4A or T5
Class II, Div 2, Groups F and G,
T3A, T3B, T2D, T4A or T5
Frame sizes 5010, L5010,
L5810 and L6808/09,
three-phase (W40)
Class I, Div 2, Groups A, B, C and
D, T3, T2B, T2C and T2D
Frame sizes NEMA 58 to
160 and IEC 355 to 1000
(W60)
Class I, Div 2, Groups A, B, C and
D, T3B, T3C, T3.
Class II, Div 2, Groups F and G,
T3B, T3C, T3.
70006808
4. Operation
During operation, do not touch the non-insulated
energized parts and never touch or stay too close to
rotating parts.
Ensure that the space heater is always OFF during
the motor operation.
The rated perfomance values and the operating conditions are
specified on the motor nameplate. The voltage and frequency
variations of the power supply should never exceed the limits
established in the applicable standards.
Occasional different behavior during the normal operation
(actuation of thermal protections, noise level, vibration level,
temperature and current increase) must always be assessed
by qualified personnel. In case of doubt, turn off the motor
immediately and contact the nearest WEG service center.
Do not use roller bearings for direct coupling. Motors fitted
with roller bearings require a minimum radial load to ensure a
proper operation.
For motors fitted with oil lubrication or oil mist systems, the
cooling system must be ON even after the machine is OFF and
until the machine is at complete standstill.
In case of failure in the lubrication and/or cooling system, turn
the motor OFF immediatly.
After complete standstill, the cooling and lubrication systems
(if any exist) must be switched OFF and the space heaters (if
available) must be switched ON.
In case of doubts, turn the motor OFF immediately and
contact the nearest WEG authorized service Center for
explosive atmospheres.
For Flameproof or Protection by Enclosure motors, only
open the terminal box and/or disassembly the motor when
the motor surface temperature is at ambient temperature.
For the W40, W50 and HGF motor lines provided with axial
fans, the motor and the axial fan have different markings
for indicating the direction of rotation for prevent incorrect
assembly.
The axial fan must be assembled so that the indicative
arrow for direction of rotation is always visible, viewing the
non-drive end side. The marking indicated on the axial fan
blade, CW for clockwise direction of rotation or CCW for
counterclockwise direction of rotation, indicates the
direction of rotation of the motor viewing the drive end
side.
Motors with degree of protection greater than IP55 are supplied
with a rust inhibitor on joints and fixing bolts. Before assembly
the components with machined surfaces (for example, terminal
box cover of Flameproof motors), clean these surfaces and
apply a new layer of this product.
For Flameproof motors joints only the following products can be
used: Lumomoly PT/4 (manufacturer: Lumobras – for ambient
temperature ranging from -20 °C to +80 °C) or Molykote DC 33
(manufacturer: Dow Corning – for ambient temperature ranging
from -55 °C to +80 °C). For motors with other types of
protection, use Loctite 5923 (manufacturer: Henkel) on joints.
For explosion-proof motors special care should be taken with
For special applications and operating conditions (for example,
smoke extraction motors, totally enclosed air over (TEAO),
motors for high thrust applications, motors with brake, motors
with encoder) refer to the dedicated manual supplied with the
equipment, or the manual 50034162 available in the website or
contact WEG.
When contacting WEG, please, have the full description of the
motor at hand, as well as the serial number and manufacturing
date, indicated on the motor nameplate.
7. Warranty terms
WEG Equipamentos Elétricos S/A, Motors Business Unit (“WEG”),
offers warranty against defects in workmanship and materials
for its products for a period of 18 months from the invoice date
issued by the factory or distributor/dealer, limited to 24 months
from the date of manufacture.
Motors of the HGF and W60 Lines are covered for a period of
12 months from the invoice date issued by the factory or
distributor / dealer, limited to 18 months from the date of
manufacture.
The paragraphs above contain the legal warranty periods.
If a warranty period is defined in a different way in the
commercial/technical proposal of a particular sale, that will
supersede the time limits set out above.
The warranty periods above are independent of the product
installation date and the startup.
If any defect or abnormal occurrence is detected during
machine operation, the customer must immediately notify WEG
in writing about the occurred defect, and make the product
available for WEG or its Authorized Service Center for the period
required to identify the cause of the defect, check the warranty
coverage, and perform the proper repairs.
In order for the warranty to be valid, the customer must be sure
to follow the requirements of WEG technical documents,
especially those set out in the product Installation, Operation
and Maintenance Manual, as well as the applicable standards
and regulations in force in each country.
Defects arising from the inappropriate or negligent use,
operation, and/or installation of the equipment, non-execution
of regular preventive maintenance, as well as defects resulting
from external factors or equipment and components not
supplied by WEG, will not be covered by the warranty.
The warranty will not apply if the customer at its own discretion
Product
line
Frame size
Flat joint Cylindrical joint
Gap
(max)
Lenght
(min)
Gap
(max)
Lenght
(min)
W21Xdb
IEC 90 to 355
NEMA 143 to 586/7
0.05 mm
Under
request
Not available
W22Xdb
IEC 71 and 80
Not available 0.15 mm 12.5 mm
IEC 90 to 355
NEMA 143 to 586/7
0.075
mm
6 mm 0.15 mm 19 mm
makes repairs and/or modifications to the equipment without
prior written consent from WEG.
The warranty will not cover equipment, components, parts and
materials whose lifetime is usually shorter than the warranty
period. It will not cover defects and/or problems resulting from
force majeure or other causes not imputable to WEG, such as,
but not limited to: incorrect or incomplete specifications or data
supplied by the customer; transportation, storage, handling,
installation, operation and maintenance not complying with the
provided instructions; accidents; defects in the construction
works; use in applications and/or environments for which the
machine was not designed; equipment and/or components not
included in the scope of WEG supply. The warranty does not
include disassembly services at the buyer’s premises, product
transportation costs and travel, lodging and meal expenses for
the technical staff of the Service Centers, when requested by
the customer.
The services under warranty will be provided exclusively at
WEG authorized Service Centers or at one of its manufacturing
plants. Under no circumstances will the warranty services
extend the equipment warranty period.
WEG’s Civil Liability is limited to the supplied product; WEG will
not be liable for indirect or consequential damages, such as
losses of profit and revenue losses and alike which may arise
from the contract signed between the parties.
the machined surfaces of the flame path. These surfaces must
be free of burrs, scratches, etc. that reduce the flame path
length and increase the gap. The gaps between terminal boxes
and the respective terminal box covers should not exceed the
values specified in Table 4.
For motors with permanent magnet rotor (lines W22
Quattro and W22 Magnet), the motor assembly and
disassembly require the use of proper devices due
to the attractive or repulsive forces that occur between
metallic parts. This job must be only performed by a WEG
Authorized service center specifically trained for such an
operation. People with pacemakers cannot handle these
motors.
The permanent magnets can also cause disturbances or
damages to other electric equipment and components
during maintenance.
1. Introduction
The installation, operation and maintenance of the motor must
be always performed by qualified and authorized personnel
using proper tools and methods and following the instructions
contained in the documents supplied with the motor.
The instructions presented in this document are valid for WEG
motors with the following characteristics:
g
Three-phase and single-phase induction motors (squirrel cage rotor);
g
Three-phase permanent magnet motors;
g
Three-phase hybrid motors (squirrel cage rotor + permanent ‘
magnets);
These motors can be used in hazardous areas with the following
types of protection:
g
Increased Safety – “Ex eb”;
g
Flameproof – “Ex db” or “Ex db eb”;
g
Protection by Enclosure (combustible dust) - “Ex t”;
g
Class I Division 1;
g
Class I Division 2;
g
Class II Division 1;
g
Class II Division 2.
Details of motor marking may be found on nameplate and product
certification, which is part of the motor documentation. For
reference, this manual lists the certificate numbers for each type of
protection and their nameplate markings. Furthermore, the
applicable Standards may be found in the product certification and
at the “Installation, Operation and Maintenance Manual of Electric
Motors for Use in Explosive Atmospheres” – code 50034162. This
manual is available in the website www.weg.net
The objective of this manual is to provide important information, which
must be considered during the shipment, storage, installation, operation
and maintenance of WEG motors. Therefore, we advise to make a
careful and detailed reading of the instructions contained herein before
performing any intervention on the motor.
ENGLISH
The noncompliance with the instructions informed in this manual and
others mentioned in the website www.weg.net voids the product
warranty and may compromise the type of protection of the motor and
still result in serious personal injuries and material damages.
Any component added to the motor by the user, for
example, cable glands, thread plug, encoder, etc., must
meet the type of protection of the enclosure, the
“equipment protection levels” (EPL) and the degree of protection
of the motor, according to the Standards indicated in the product
certification.
Special Conditions for Safe Use
The sign “X” added to the certificate number, informed
on the nameplate of the motor, indicates that the
equipment demands special conditions for installation,
operation and/or maintenance, being those described in the
certificate and the motor documentation.
For reference, the chapter 8 lists the certificate numbers for each
type of protection and their nameplate markings.
The noncompliance with these requirements compromises the
safety of the product and of the installation.
The correct classification of the installation area and ambient
characteristics is user’s responsibility.
Electric motors have energized circuits and exposed rotating
parts which may cause injuries to people.
2. Shipment, storage and handling
Check the conditions of the motor right after receiving. When any
damage is noticed, this must be reported in writing to the transportation
company, and immediately communicated to the insurance company
and to WEG. In this case, no installation job can be started before the
detected problem has been solved.
Check if the nameplate data match the invoice data, the environment
conditions where the motor will be installed, the type of protection and
EPL of the motor. If the motor is not immediately installed, it must be
stored in a clean and dry room protected against dust, vibrations, gases
and corrosive agents, with relative humidity not over 60%.
In order to prevent water condensation within the motor during the
storage period, it is recommended to keep the space heater ON (if
available). In order to prevent oxidation of the bearings and ensure an
even distribution of the lubricant, rotate the motor shaft at least once a
month (at least five turns), always leaving it in a different position. For
bearings with oil mist lubrication systems, the motor must be stored
horizontally with ISO VG 68 oil in the bearing, with the amount indicated
in the motor manual available in the website and the shaft must be
turned every week. If the motors are stored for more than two years, it is
recommended to change the bearings, or to remove, wash, inspect
and relubricate them before the motor is started. After this storage
period, it is also recommended to change the start capacitors of single-
phase motors since they loss their operating characteristics.
Always handle the motor carefully in order to prevent
impacts and damages to the bearings and always install
the shaft transportation/locking device (if supplied)
when transporting the motor.
Use only the eyebolts to lift the motor. However these eyebolts are
designed for the motor weight only. Thus never use these eyebolts
to lift the motor with additional loads coupled to it.
The lifting eyebolts of the terminal box, fan cover, etc., are
intended to handle only these parts when disassembled from the
motor. Additional information regarding the maximum allowable
angle-of-inclination is indicated in the general manual available on
the website
www.weg.net.
Periodically and mainly before the initial star-up, measure the insulation
resistance of the motor winding. Check the recommended values and
the measuring procedures in the website.
3. Installation
During the installation, the motors must be protected
against accidental energization.
Check the motor direction of rotation, turning it without
load before it is coupled to the load.
For power cables, switching and protection devices dimensioning,
consider the rated motor current, the service factor, and the cable
length, among others. For motors without terminal block, insulate
the motor terminal cables by using insulating materials that are
compatible with the insulation class informed on the nameplate.
The minimum insulation distance between the non-insulated live
parts themselves and between live parts and the grounding must
meet the applicable standards and regulations for each country.
Remove the transportation devices and shaft locking device (if supplied)
before starting the motor installation.
Motors must be only installed in places compatible with their mounting
features and in applications and environments for which they are
intended. It must be respected the type of protection and the EPL of the
motor, according to the classification of the area where the motor will be
installed.
The motors with feet must be installed on bases duly planned in order to
prevent vibrations and assure perfect alignment. The motor shaft must
be properly aligned with the shaft of the driven machine. Incorrect
alignment, as well as improper belt tension, will certainly damage the
bearings, resulting in excessive vibrations and even causing the shaft
rupture. The admissible shaft radial and axial loads indicated in the
general manual of the website must be respected. Use flexible coupling
whenever possible.
When motors are fitted with oil lubricated bearings or oil mist lubrication
systems, connect the cooling and lubrication tubes (if available).
For oil lubricated bearings, the oil level must be in the center of the sight
glass.
Remove the corrosion protection grease from the shaft end and flange
only right before the motor installation.
Unless specified otherwise in the purchase order, WEG motors are
dynamically balanced with “half key” and without load (uncoupled). The
driving elements, such as pulleys, couplings, etc., must be balanced
with “half key” before they are mounted on the shaft of the motors.
The motor must always be positioned so the drain hole is
at the lowest position.
Motors supplied with rubber drain plugs leave the
factory in the closed position and must be opened periodically to
allow the exit of condensed water. For environments with high
water condensation levels and motor with degree of protection
IP55, the drain plugs can be mounted in open position .
For motors with degree of protection IP56, IP65 or IP66, the drain
plugs must remain at closed position, being opened only during
the motor maintenance procedures.
The drain system of motors with Oil Mist lubrication system must
be connected to a specific collection system.
The motor must be installed with overload protection devices.
These protection devices can be integrated to the motor (such
as thermistors in the windings) or external protection devices,
where the motor load is monitored by the nominal current. For
three-phase motors, it is recommended to install a phase failure
protection device. Delta connected motors must be protected
against phase fault. To do that, connect the overload relay in
series to the winding phases and set it to 0.58 times the rated
current.
For Class I & II Division 1 motors and/or motors driven by
frequency inverters, the use of the thermal protections is
mandatory (except for temperature classes T2B or higher).
For Division 2 or non-hazardous areas, the use of the thermal
protections is optional.
For flying leads motors, do not push the overlength
of leads into the motor in order to prevent that they
touch the rotor.
Ensure the correct operation of the accessories (brake, encoder,
thermal protection, forced ventilation, etc.) installed on the motor
before it is started. The temperature limits for alarm and tripping of
the thermal protection can be defined according to the application,
however they may not exceed the values
shown in Table 3.
The drain plugs of explosion proof motors cannot be
removed during installation and maintenance
procedures.
Do not block the motor ventilation openings. Ensure a
minimum clearance of ¼ of the diameter of the air intake of the fan
cover from the walls. The air used for cooling the motor must be at
ambient temperature, limited to the temperature range indicated
on the motor nameplate (when not indicated,
-20 °C to +40 °C must be considered).
Motors installed outdoors or in the vertical position require the
use of additional shelter to protect them from water; for instance,
use of a drip cover.
To prevent accidents, ensure that the grounding connection has
been performed according to the applicable standards and that
the shaft key has been well-fixed fastened before the motor is
started.
Connect the motor properly to the power supply by means of safe
and permanent contacts, always considering the data informed
on the nameplate, such as rated voltage, wiring diagram, etc.
When using terminals, all wires that form the stranded cable must
be fastened inside the sleeve. The insulation of the accessories
cables must be kept up to 1 mm from the connector connection
point.
For power cables and grounding system connections and terminal box
assembly, the tightening torques indicated on Tables 1 and 2 must be
respected.
Table 2 - Tightening torques for cable-glands and threaded plugs [Nm]
Thread Material M16 M20 M25 M32 M40 M50 M63 M80
Metric
Plastic 3 to 5 3 to 5 6 to 8 6 to 8 6 to 8 6 to 8 6 to 8 6 to 8
Metallic 40 to 50 40 to 50 55 to 70 65 to 80 80 to 100 100 to 120 115 to 140 160 to 190
Thread Material
NPT
1/2"
NPT
3/4"
NPT
1"
NPT
1 1/2"
NPT
2"
NPT
2 1/2"
NPT
3"
NPT
4"
NPT
Plastic - 5 to 6 6 to 8 6 to 8 6 to 8 6 to 8 6 to 8 6 to 8
Metallic 40 to 50 40 to 50 55 to 70 65 to 80 100 to 120 115 to 140 150 to 175 200 to 240
Alexandre Eiji Amano
Quality System & Certification Manager
Brasil
The manufacturer declares under sole responsibility that:
WEG electric motors and components used for
following motor lines:
W21, W22X…, W50X…, W60X…, HGF and EX61G
……………
when installed, maintained and used in applications for which they
were designed, and in compliance with the relevant installation
standards and manufacturer’s instructions, comply with the provisions
of the following relevant European Union harmonisation legislation,
wherever applicable:
ATEX Directive 2014/34/EU;
RoHS Directive 2011/65/EU** and its amendments (including Directive
2015/863/EU);
Machinery Directive 2006/42/EC****;
EMC Directive 2014/30/EU (electric motors are considered
inherently benign in terms of electromagnetic compatibility);
The fulfilment of the safety objectives of the relevant European Union
harmonisation legislation has been demonstrated by compliance with
the following standards, wherever applicable:
EN 60079-0:2012 + A11:2013*/ EN 60079-0:2018***/ EN 60079-
1:2014*/ EN 60079-7:2015*/ EN 60079 31:2014/
EN 60204-1:2006 + A1:2009 + AC:2010 / EN 60204-11:2000 +
AC:2010 / EN 50581:2012 and IEC TS 60034-25.
* A comparison of the current version of the EN 60079-0:2012+A11:2013, EN
60079-1:2014 and EN 60079-7:2015 standards with the previous versions
used by some Baseefa, CESI, PTB and SIRA ATEX certificates shows that
there are no changes in the “state of the art” applicable to the product covered
by this Declaration of Conformity. The manufacturer hereby declares that the
ATEX Certificates issued by Baseefa, CESI, PTB and SIRA meet the Essential
Health and Safety Requirements of ATEX Directive 2014/34/EU.
** Electric motors with a voltage rating higher than 1000V for alternate current
and 1500 V for continuous current are not under the scope.
*** Electric motors evaluated by the certificates Baseefa 07 ATEX 0148X,
Baseefa 10 ATEX 0124X, Baseefa 10 ATEX 0192X, Baseefa 10 ATEX 0193X,
Baseefa 13 ATEX 0016X, Baseefa 13 ATEX 0079X, Baseefa 13 ATEX 0288X,
Baseefa 06 ATEX 0349X, Baseefa 10 ATEX 0205X, Baseefa 14 ATEX 0209X
and Baseefa 14 ATEX 0210X are in conformity with EN 60079-0:2018
requirements.
**** Electric motors are considered partly completed machinery and are
supplied with a “Declaration of Incorporation”:
Declaration of Incorporation:
The products above cannot be put into service until the machinery into
which they have been incorporated has been declared in conformity with
the Machinery Directive.
A Technical Documentation for the products above is compiled in
accordance with part B of annex VII of Machinery Directive 2006/42/EC.
We undertake to transmit, in response to a reasoned request by the
national authorities, relevant information on the partly completed machinery
identified above through WEG authorised representative established in the
European Union. The method of transmission shall be electronic or physical
method and shall be without prejudice to the intellectual property rights of
the manufacturer.
The Quality System for the certificates described above is approved by SGS
Fimko Oy (NB0598) under the Quality Assurance Notification SGS ATEX 5886
(WEG Equipamentos Elétricos S.A. and WEG Linhares Equipamentos Elétricos
S.A.) and SGS ATEX 3862 (WEGeuro – Indústria Eléctrica S.A.).
CE marking in: 1996
Jaraguá do Sul, May 24
th
, 2019
EU DECLARATION OF CONFORMITY
Manufacturers:
WEG EQUIPAMENTOS
ELÉTRICOS S.A.
Av. Prefeito Waldemar Grubba,
3000 - CEP 89256-900
Jaraguá do Sul – SC – Brazil
www.weg.net
WEGeuro – Industria
Electrica S.A.
Headquarters:
Rua Eng. Frederico Ulrich,
Zona Industrial da Maia Sector V
4470-605 – Maia – Portugal
www.weg.net/pt
CONTACT PERSON: Luís Filipe
Oliveira Silva Castro Araújo
Authorised Representative in the
European Union
(Single Contact Point)
Branch – Santo Tirso:
Parque Industrial da Ermida
Avenida Luis Areal – Sta Cristina
do Couto
4780-165 – Santo Tirso –
Portugal
www.weg.net/pt
WEG (Nantong) Electric Motor
Manufacturing CO. LTD.
No. 128# - Xinkai South Road,
Nantong - Economic & Technical
Development - Zone, Nantong,
Jiangsu Province – China
www.weg.net/cn
WEG (Jiangsu) Electric
Equipment CO. LTD.
No. 15 Group, North City Street,
Dengyuan Community - Rugao
City, Jiangsu Province – China
www.weg.net/cn
WEG Linhares Equipamentos
Elétricos S.A.
Rod. BR 101, Km 161,5, s/n
Distrito Industrial Rio Quartel
Bairro Rio Quartel de Baixo
29915-500 – Linhares – ES – Brazil
www.weg.net
Table 1 - Tightening torques for fixing elements [Nm]
Type of
protection
of enclo-
sure
Component M4 M5 M6 M8 M10 M12 M14 M16 M20
Class I
Division 1
Class II
Division 1
Class I
Zone 1
Terminal
Box
Cover
Class
8.8/12.9
- 3,5 to 5 6 to 12 14 to 30 28 to 60 45 to 105
75 to
110
115 to
170
230 to
330
Class
A2-70 /
A4-70
- 3,5 to 5 6 to 8,5 14 to 19 28 to 40 45 to 60
75 to
100
115 to
170
225 to
290
Grounding 1,5 to 3 3 to 5 5 to 10 10 to 18 28 to 40 45 to 70 -
115 to
170
-
Terminal Block /
Flying leads
1 to 1,5 2 to 4 4 to 6,5 6,5 to 9 10 to 18
15,5 to
30
-
30 to
50
50 to 75
Class I
Division 2
Class II
Division 2
Class I
Zone 2
Terminal Box Cover - 3 to 5 4 to 8 8 to 15 18 to 30 25 to 40
30 to
45
35 to
50
-
Grounding 1,5 to 3 3 to 5 5 to 10 10 to 18 28 to 40 45 to 70 -
115 to
170
-
Terminal Block /
Flying leads
1 to 1,5 2 to 4 4 to 6,5 6,5 to 9 10 to 18
15,5 to
30
-
30 to
50
50 to 75
Terminal block
fixing bolts
- 3 to 5 5 to 10 10 to 18 28 to 40 45 to 70
75 to
110
115 to
170
-
For further information about shipment, storage, handling,
installation, operation and maintenance of electric motors,
access the website
www.weg.net.
Table 3 - Maximum operating temperature of the thermal protection
Luis Filipe Araujo
Industrial Director
Portugal
Rodrigo Fumo Fernandes
Engineering Director
China
Take the required measures in order to ensure the
type of protection, the EPL and the degree of
protection indicated on the motor nameplate:
- unused cable inlet holes in the terminal boxes
must be properly closed with certified plugs;
- components supplied loose (for example, terminal boxes
mounted separately) must be properly closed and sealed;
The cable entries used must be fitted with components
(such as, cable glands and conduits) that meet the
applicable standards and regulations for each country. For
“Ex db” motors, the conduit entries are permitted only for
electrical equipment of group II.
The fixing elements mounted in the threaded through holes
in the motor enclosure (for example, the flange) must be
properly sealed, with the products listed in item 5, to
ensure the degree of protection indicated on the motor
nameplate.
  • Page 1 1
  • Page 2 2

WEG Electric motors for Hazardous Areas Manual de usuario

Tipo
Manual de usuario