WEG CFW500 IP66 Manual de usuario

Tipo
Manual de usuario
English
Frequency Inverter
CFW500 IP66
CFW500 User Manual Addendum
ATTENTION!
The information contained in this addendum applies to inverters with number 66 in the
protection rating field of the inverter smart code; for example: CFW500A07P3S2DB66. For
further information on the smart code, refer to Item 2.3 NOMENCLATURE of the user manual.
Use this guide together with the CFW500 programming and user manuals, available for
download on the website: www.weg.net.
1 INTRODUCTION
The CFW500 IP66 frequency inverter is an inverter dedicated to applications that require a higher protection
degree. Nema 4X/IP66 protection rating ensures protection against dust, dirt and water jets from any direction.
2 INSTALLATION AND CONNECTION
2.1 WORK ENVIRONMENT
The recommended environments for the CFW500 IP66 operation are:
Nema 12. Nema 4X indoor/outdoor. IP66 indoor/outdoor.
Other considerations are identical to the CFW500 IP20 and can be found in Chapter 3 INSTALLATION
AND CONNECTION of the CFW500 user manual, except the environmental application conditions that are
described below:
For temperatures surrounding the inverter above 40 ºC (104 °F), it is necessary to apply a 2 % current
derating for each Celsius degree, limited to an increase of 10 ºC (18 °F).
For proper operation of the inverter (indoor and outdoor), it must not be subject to direct exposure to
sunlight, snow, excessive humidity, explosive or corrosive gases or liquids and excessive vibration.
2.2 DIMENSIONS
See Figure A.1 and Figure A.2 in APPENDIX A - FIGURES.
NOTE!
Consider the positioning, fixation and assembly recommendations described in the CFW500
user manual - see Chapter 3 INSTALLATION AND CONNECTION.
2.3 POSITIONS OF THE POWER, GROUNDING AND CONTROL CONNECTIONS
To access the power, control and ground terminals, the inverter front cover must be removed as shown in
the Figure A.3 in APPENDIX A - FIGURES. Disconnect the cable of the product HMI.
Figure A.4 in APPENDIX A - FIGURES shows the location of the power and control terminals as well as
the place for grounding.
NOTE!
Always disconnect the main power supply before touching any electrical components associated
to the inverter. Many components may remain charged with high voltages and/or moving (fans)
even after the AC power supply input is disconnected or turned off. Wait for at least ten minutes
in order to guarantee the full discharge of the capacitors. Always connect the grounding point
of the inverter to the protective earth (PE).
2.4 ELECTRICAL INSTALLATION
Refer to Chapter 3 INSTALLATION AND CONNECTION of the CFW500 user manual.
2.4.1 Power/Grounding Wiring and Circuit Breakers
Use proper terminals for the power and grounding connection cables. Refer to Table B.1 and Table B.2 of the
CFW500 user manual addendum for the recommended wiring, circuit breakers and fuses. Keep sensitive
equipment and wiring at least 0.25 m away from the inverter and from the cables connecting the inverter to
the motor. It is not recommended to use miniature circuit breakers (MDU) due to the magnet actuation level.
NOTE!
The use of appropriate cables is essential to ensure the specified protection rating. The use of
multipolar cables is recommended. For example, a four-pole cable for power supply (R, S, T)
and grounding, and another four-pole cable for motor connection. Figure 1 shows an example
of a four-pole cable to connect the power cables.
To ensure the specified protection rating, it is necessary to use cable glands on the power and
control connections with protection rating compatible with the one desired for the application.
Entry diameter: 16.1 mm / cable gland: M16 x 1,5 or PG9.
Figure 1: Four-pole cable
NOTE!
Power supply capacity: Suitable for use in circuits capable of delivering a maximum of 30,000
symmetrical Arms (200 V, 480 V or 600 V) when protected by fuses as specified in Table B.2
of the CFW500 user manual addendum.
For further information regarding power and grounding wiring and connections, refer to the
CFW500 user manual.
2.4.2 Control Connections
The control connections (analog input/output, digital input/output and RS485 interface) must be made
according to the specification of the plug-in module connector connected to the CFW500. Refer to the guide
of the plug-in module in the product module package. The typical functions and connections for the CFW500-
IOS standard plug-in module are shown in the Figure A.5 in APPENDIX A - FIGURES. For further details on
the connector signal specifications, refer to Chapter 8 TECHNICAL SPECIFICATIONS of the user manual.
NOTE!
For further information on the control board installation and configuration, refer to Chapter 3
INSTALLATION AND CONNECTION of the CFW500 user manual.
1) Always disconnect the main power supply before touching any electrical components in connection with the
inverter. Many components may remain charged with high voltages and/or moving (fans) even after the AC
power supply input is disconnected or turned off. Wait for at least ten minutes in order to guarantee the full
discharge of the capacitors. Always connect the grounding point of the inverter to the protective earth (PE).
2) To ensure the specified protection rating, it is necessary to use cable glands on the power and control
connections with protection rating compatible with the one desired for the application. Entry diameter:
16.1 mm / cable gland: M16 x 1,5 or PG9.
3) If no electrical connections are present, the rubber plugs that come with the inverter must be kept in place.
4) The maximum and minimum power and control cable diameters must comply with the specifications of
the cable gland supplier to ensure the specified protection rating.
2 INSTALAÇÃO E CONEXÃO
2.1 AMBIENTE DE TRABALHO
Os ambientes recomendados para a utilização do CFW500 IP66 são:
Nema 12. Nema 4X indoor/outdoor. IP66 indoor/outdoor.
Outras considerações são idênticas ao CFW500 IP20 e podem ser encontradas no Capítulo 3 INSTALAÇÃO
E CONEXÃO do manual do usuário CFW500, exceto as condições ambientais de aplicão que eso
descritas abaixo:
Para temperatura ao redor do inversor maior que 40 ºC, é necesrio aplicar redão da corrente
de 2 % para cada grau Celsius limitando o acréscimo em 10 ºC.
Para operação adequada do inversor (indoor e outdoor), o mesmo não deve estar sujeito a exposão
direta de raios solares, a neve, umidade excessiva, gases ou líquidos explosivos ou corrosivos e
vibração excessiva.
2.2 DIMENSÕES
Conforme Figura A.1 e Figura A.2 do ANEXO A - FIGURAS.
NOTA!
Considere as recomendações de posicionamento, fixação e montagem descritas no manual
do usuário do CFW500 - Capítulo 3 INSTALAÇÃO E CONEXÃO.
2.3 LOCALIZAÇÕES DAS CONEXÕES DE POTÊNCIA, ATERRAMENTO E CONTROLE
Para o acesso aos bornes de potência, controle e aterramento, é necesrio remover o fechamento frontal
do inversor conforme indica a Figura A.3 do ANEXO A - FIGURAS. Desconecte o cabo da HMI do produto.
A Figura A.4do ANEXO A - FIGURAS apresenta a localização dos bornes de potência e controle, assim
como a localização para aterramento.
NOTA!
Sempre desconecte a alimentação geral antes de tocar em qualquer componente elétrico
associado ao inversor. Muitos componentes podem permanecer carregados com altas
tenes e/ou em movimento (ventiladores), mesmo depois que a entrada de alimentação CA
for desconectada ou desligada. Aguarde pelo menos 10 minutos para garantir a total descarga
dos capacitores. Sempre conecte o ponto de aterramento do inversor ao terra de proteção (PE).
2.4 INSTALAÇÃO ELÉTRICA
Consulte o Capítulo 3 INSTALAÇÃO E CONEXÃO do manual do usrio CFW500.
2.4.1 Fiação de Potência/Aterramento e Disjuntores
Utilize terminais adequados para os cabos das conexões de potência e aterramento. Consulte a Tabela B.1
e Tabela B.2 do adendo ao manual do usrio CFW500 para fiação, disjuntores e fusíveis recomendados.
Afaste os equipamentos e fiações sensíveis em 0,25 m do inversor e dos cabos de ligação entre inversor
e motor. Não é recomendável utilizar os mini disjuntores (MDU), devido ao nível de atuão do magnético.
NOTA!
A utilização de cabos apropriados é indispensável para que se garanta o grau de proteção
especificado. É recomendado o uso de cabos multipolares. Por exemplo, um cabo tetra-polar
para a alimentão (R, S, T) e aterramento, e outro cabo tetra-polar para a conexão do motor.
A Figura 1 apresenta um exemplo de cabo tetra-polar para a conexão dos cabos de potência.
Para que o grau de proteção especificado seja assegurado, é necessária a utilização de
prensa cabos nas conexões de potência e controle com grau de proteção compatível com o
desejado para a aplicação. Dmetro de entrada: 16,1 mm / prensa-cabo: M16 x 1,5 ou PG9.
Figura 1: Cabo tetra-polar
NOTA!
Capacidade da rede de alimentação: Adequado para uso em circuitos com capacidade de
entregar no máximo 30.000 Arms sitricos (200 V, 480 V ou 600 V), quando protegido por
fusíveis conforme especificação da Tabela B.2 do adendo ao manual do usuário CFW500.
Para mais informações com relação as fiações e conexões de potência e aterramento, consulte
o manual do usuário do CFW500.
2.4.2 Conexões de Controle
As conexões de controle (entrada/saída anagica, entradas/saídas digitais e interface RS485) devem ser
feitas de acordo com a especificação do conector do módulo plug-in conectado ao CFW500, consulte
o guia do módulo plug-in na embalagem do módulo do produto. As fuões e conexões típicas para o
módulo plug-in padrão CFW500-IOS são apresentadas na Figura A.5 do ANEXO A - FIGURAS. Para
mais detalhes sobre as especificações dos sinais do conector consulte o Capítulo 8 ESPECIFICAÇÕES
TÉCNICAS do manual do usuário.
NOTA!
Para mais informações sobre a instalação e configurão do cartão de controle, consulte o
Capítulo 3 INSTALAÇÃO E CONEXÃO do manual do usuário CFW500.
1) Desconecte a alimentação geral antes de tocar em qualquer componente elétrico associado ao
inversor. Muitos componentes podem permanecer carregados com altas tensões e/ou em movimento
(ventiladores), mesmo depois que a entrada de alimentação CA for desconectada ou desligada. Aguarde
pelo menos 10 minutos para garantir a total descarga dos capacitores. Sempre conecte o ponto de
aterramento do inversor ao terra de proteção (PE).
2) Para que o grau de proteção especificado seja assegurado, é necessária a utilização de prensa cabos
nas conexões de potência e controle com grau de proteção compatível com o desejado para a aplicação.
Diâmetro de entrada: 16,1 mm / prensa-cabo: M16 x 1,5 ou PG9.
3) Se não há conexões elétricas, deve-se manter os tames de borracha que acompanham o inversor.
4) Os diâmetros máximos e mínimos dos cabos das conexões de potência e controle devem ser conforme
o especificado pelo fornecedor do prensa cabos para garantir o grau de proteção especificado.
2.5 DIRETIVA EUROPEIA DE COMPATIBILIDADE ELETROMAGNÉTICA – FILTROS PROPOSTOS
A série de inversores CFW500, foi desenvolvida apenas para aplicões profissionais. Por isso não se
aplicam os limites de emissões de correntes harmônicas definidas pelas normas EN 61000-3-2 e EN
61000-3-2/A 14. Mais informações, consulte o manual do usuário CFW500.
2.5.1 Inversores e Filtros
Para os modelos CFW500 IP66, os níveis de emissão são apresentados na Tabela B.4 do adendo ao
manual do usuário CFW500, de acordo com a norma IEC/EN61800-3, edão 3, 2017-02.
2.6 FECHAMENTO
Para assegurar o grau de proteção Nema 4X/IP66 é importante o correto fechamento do inversor de
frequência após concluída a instalação elétrica.
As instruções a seguir orientam como efetuar o fechamento:
Após a conclusão da instalação elétrica e do aperto do prensa-cabos, certifique-se que o cabo que
interliga o cartão de controle ao cartão da HMI está conectado.
Verifique se a borracha de vedação está inserida no canal interno da tampa.
Encaixe a tampa pstica sobre a base.
Aperte os parafusos aos poucos, alternando-os, até que se obtenha torque de 2 Nm, para que a borracha
seja pressionada de forma uniforme até o fechamento completo do inversor.
2.5 EUROPEAN DIRECTIVE OF ELECTROMAGNETIC COMPATIBILITY - PROPOSED FILTERS
The CFW500 inverter series was developed for professional applications only. Therefore, the limits for
emission of harmonic currents established by the EN 61000-3-2 and EN 61000-3-2/A 14 standards are
not applicable. For further information, refer to the CFW500 user manual.
2.5.1 Inverters and Filters
For the CFW500 IP66 models, the emission levels are shown in Table B.4 of the CFW500 user manual
addendum according to IEC/EN61800-3, edition 3, 2017-02.
2.6 CLOSING
To ensure the Nema 4X/IP66 protection rating, it is important to close the frequency inverter properly after
the electrical installation is completed.
Below are the instructions to close the unit:
After completing the electrical installation and tightening the cable glands, make sure that the cable
connecting the control board to the HMI board is connected.
Check that the sealing rubber is inserted into the inner channel of the cover.
Fit the plastic cover over the base.
Tighten the screws gradually, alternating them, until a torque of 2 Nm is obtained, so that the rubber is
pressed evenly until the complete closing of the inverter.
NOTE!
Opening and closing the product many times shortens the life of the rubber. It is not recommended
to do such procedure more than 15 times. See Figure A.6 in APPENDIX A - FIGURES.
3 HUMAN MACHINE INTERFACE (HMI)
For the CFW500 IP66, the HMI functionality is identical to that presented in the CFW500 user manual. See
Figure A.7 in APPENDIX A - FIGURES.
4 OPTIONAL ITEMS AND ACCESSORIES
The RFI filter is available as an optional item for the CFW500 IP66 line. All control accessories described in
Item 7.2 ACCESORIOS of the CFW500 IP20 user manual are available for the CFW500 IP66 line.
5 TECHNICAL SPECIFICATIONS
See Table B.1 to Table B.6 in APPENDIX B - TECHNICAL SPECIFICATIONS.
Español
Convertidor de Frecuencia
CFW500 IP66
Anexo al Manual del Usuario CFW500
¡ATENCIÓN!
Las informaciones de este anexo se aplican a los convertidores que contienen la sigla
66 en el campo grado de protección del código inteligente del convertidor, por ejemplo:
CFW500A07P3S2DB66. Para más informaciones sobre el código inteligente, consultar
el Ítem 2.3 NOMENCLATURA del manual del usuário.
Utilizar esta guía en conjunto con los manuales de programacn y del usuario del CFW500.
1 INTRODUCCIÓN
El convertidor de frecuencia CFW500 IP66 es un convertidor para aplicaciones que exigen un grado más
elevado de protección. El grado de protección Nema 4X/IP66 garantiza protección contra polvo, suciedades
y chorros de agua direccionados.
2 INSTALACIÓN Y CONEXIÓN
2.1 AMBIENTE DE TRABAJO
Los ambientes recomendados para la utilización del CFW500 IP66 son:
Nema 12. Nema 4X indoor/outdoor. IP66 indoor/outdoor.
Otras consideraciones son inticas al CFW500 IP20 y pueden ser encontradas en el Capítulo 3
INSTALACIÓN Y CONEXIÓN del manual del usuario CFW500, excepto las condiciones ambientales de
aplicación que están descritas abajo:
Para temperatura, alrededor del convertidor, mayor a 40 ºC, es necesario aplicar reducción da corriente
de 2 % para cada grado Celsius, limitando el incremento en 10 ºC.
Para la operación adecuada del convertidor (indoor y outdoor), éste no debe estar sujeto a exposición
directa de rayos solares, nieve, humedad excesiva, gases o líquidos explosivos o corrosivos, así como
vibración excesiva.
2.2 DIMENSIONES
Conforme la Figura A.1 y Figura A.2 del ANEXO A - FIGURAS.
¡NOTA!
Considerar las recomendaciones de posicionamiento, fijación y montaje descritas en el manual
del usuario del CFW500 - consulte el Capítulo 3 INSTALACIÓN Y CONEXN, disponible para
download en el sitio: www.weg.net.
2.3 UBICACIONES DE LAS CONEXIONES DE POTENCIA, PUESTA A TIERRA Y CONTROL
Para el acceso a los bornes de potencia, control y puesta a tierra, es necesario remover el cierre frontal
del convertidor, conforme lo indica la Figura A.3 del ANEXO A - FIGURAS. Desconecte el cable de la IHM
del producto.
La Figura A.4 del ANEXO A - FIGURAS. presenta la ubicación de los bornes de potencia y control, a
como la ubicación para puesta a tierra.
¡NOTA!
Siempre desconecte la alimentación general antes de tocar cualquier componente eléctrico
asociado al convertidor. Muchos componentes pueden permanecer cargados con altas
tensiones y/o en movimiento (ventiladores), incluso después de que la entrada de alimentación
CA sea desconectada o apagada. Aguarde por lo menos 10 minutos para garantizar la total
descarga de los condensadores. Siempre conecte el punto de puesta a tierra del convertidor
al tierra de protección (PE).
2.4 INSTALACIÓN ELÉCTRICA
Consulte el Capítulo 3 INSTALACIÓN Y CONEXN del manual del usuario CFW500.
2.4.1 Cableado de Potencia/Puesta a tierra y Disyuntores
Utilizar terminales adecuados para los cables de las conexiones de potencia y de puesta a tierra. Consulte
la Tabla B.1 y la Tabla B.2 del anexo al manual del usuario CFW500 para cableado, disyuntores y fusibles
recomendados. Apartar los equipos y cableados sensibles a 0,25 m del convertidor y de los cables de
conexión entre convertidor y motor. No es recomendable utilizar los mini disyuntores (MDU), debido al
nivel de actuación del magnético.
15169960
¡NOTA!
La utilización de cables apropiados es indispensable para que se garantice el grado de protección
especificado. Es recomendado el uso de cables multipolares. Por ejemplo, un cable tetrapolar,
para la alimentación (R, S, T) y puesta a tierra, y otro cable tetrapolar para la conexión del motor.
La Figura 1 presenta un ejemplo de cable tetrapolar para la conexión de los cables de potencia.
Para que el grado de protección especificado sea asegurado, es necesaria la utilización de
prensacables en las conexiones de potencia y control con grado de protección compatible con
el deseado para la aplicación. Diámetro de entrada: 16,1 mm / prensacables: M16 x 1,5 o PG9.
Figura 1: Cable tetrapolar
¡NOTA!
Capacidad de la red de alimentación: Adecuado para uso en circuitos con capacidad de entregar
como máximo 30.000 Arms sitricos (200 V, 480 V o 600 V), cuando está protegido por
fusibles conforme la especificación de la Tabla B.2 del anexo al manual del usuario CFW500.
Para más informaciones con relación los cableados y conexiones de potencia y de puesta a
tierra, consulte el manual del usuario del CFW500.
2.4.2 Conexiones de Control
As conexiones de control (entrada/salida analógica, entradas/salidas digitales e interfaz RS485) deben ser
hechas de acuerdo con la especificación del conector del módulo plug-in conectado al CFW500, consulte la
guía del módulo plug-in en el embalaje del módulo del producto. Las funciones y conexiones típicas para el
dulo plug-in estándar CFW500-IOS son presentadas en la Figura A.5 del ANEXO A - FIGURAS. Para más
detalles sobre las especificaciones de las señales del conector consulte el Capítulo 8 ESPECIFICACIONES
TÉCNICAS del manual del usuario.
¡NOTA!
Para más informaciones sobre la instalación y configuración de la tarjeta de control, consultar
el Capítulo 3 INSTALACIÓN Y CONEXIÓN del manual del usuario CFW500.
1) Desconecte la alimentación general antes de tocar cualquier componente eléctrico asociado al convertidor.
Muchos componentes pueden permanecer cargados con altas tensiones y/o en movimiento (ventiladores),
incluso después de que la entrada de alimentación CA sea desconectada o apagada. Aguarde por lo
menos 10 minutos para garantizar la total descarga de los condensadores. Siempre conecte el punto de
puesta a tierra del convertidor al tierra de protección (PE).
2) Para que el grado de protección especificado sea asegurado, es necesaria la utilización de prensacables en
las conexiones de potencia y control con grado de protección compatible con el deseado para la aplicación.
Diámetro de entrada: 16,1 mm / prensacables: M16 x 1,5 o PG9.
3) No habiendo conexiones eléctricas, se debe mantener los tampones de goma que vienen con el convertidor.
4) Los diámetros máximos y mínimos de los cables de las conexiones de potencia y control deben ser conforme
lo especificado por el proveedor del prensacables, para así garantizar el grado de protección especificado.
2.5 DIRECTIVA EUROPEA DE COMPATIBILIDAD ELECTROMAGNÉTICA – FILTROS PROPUESTOS
La serie de convertidores CFW500, fue desarrollada solamente para aplicaciones profesionales. Por eso
no se aplican los límites de emisiones de corrientes armónicas definidas por las normas EN 61000-3-2 y
EN 61000-3-2/A 14. Por más informaciones, consulte el manual del usuario del CFW500.
2.5.1 Convertidores y Filtros
Para los modelos CFW500 IP66, los niveles de emisn son presentados en la Tabla B.4 del anexo al manual
del usuario CFW500, de acuerdo con la norma IEC/EN61800-3, edicn 3, 2017-02.
2.6 CIERRE
Para asegurar el grado de protección Nema 4X/IP66 es importante el correcto cierre del convertidor de
frecuencia, luego de concluida la instalación eléctrica.
Las instrucciones a seguir orientan cómo efectuar el cierre:
Tras la conclusión de la instalación eléctrica y del apriete del prensacables, asegúrese de que el cable
que interconecta la tarjeta de control a la tarjeta de la HMI esté conectado.
Verifique si la goma de sellado está insertada en el canal interno de la tapa.
Encaje la tapa pstica sobre la base.
Apriete los tornillos de a poco, alternándolos, hasta que se obtenga torque de 2 Nm, para que la goma
sea presionada de forma uniforme hasta el cierre completo del convertidor.
¡NOTA!
Abrir y cerrar muchas veces el producto reduce la vida útil de la goma. No es recomendado
hacer este procedimiento más de 15 veces. Conforme la Figura A.6 del ANEXO A - FIGURAS.
3 INTERFAZ HOMBRE-MÁQUINA (HMI)
Para el CFW500 IP66, la funcionalidad de la HMI es idéntica a la presentada en el manual del usuario del
CFW500. Conforme la Figura A.7 del ANEXO A - FIGURAS.
4 OPCIONALES Y ACCESORIOS
El filtro RFI está disponible como ítem opcional para la línea CFW500 IP66. Todos los accesorios de control
descritos en en Ítem 7.2 ACCESORIOS del manual del usuario del CFW500 IP20 están disponibles para
la línea CFW500 IP66.
5 ESPECIFICACIONES TÉCNICAS
Conforme la Tabla B.1 a Tabla B.6 del ANEXO B - ESPECIFICACIONES TÉCNICAS.
Português
Inversor de Frequência
CFW500 IP66
Adendo ao Manual do Usuário CFW500
ATENÇÃO!
As informações deste adendo se aplicam aos inversores que contém a sigla 66 no campo
grau de proteção do código inteligente do inversor, por exemplo: CFW500A07P3S2DB66.
Para mais informações sobre o código inteligente, consulte o Item 2.3 NOMENCLATURA
do manual do usuário.
Utilize este guia em conjunto com os manuais de programão e usrio do CFW500,
dispoveis para download no site: www.weg.net.
1 INTRODUÇÃO
O inversor de frequência CFW500 IP66 é um inversor para aplicões que exigem um grau mais elevado de
proteção. O grau de proteção Nema 4X/IP66 garante proteção contra pó, sujeiras e jatos d’água direcionados.
Document: 10007076093 / 00
NOTA!
Abrir e fechar por muitas vezes o produto reduz a vida útil da borracha. Não é recomendado
fazer este procedimento mais de 15 vezes. Conforme Figura A.6 do ANEXO A - FIGURAS.
3 INTERFACE HOMEM-MÁQUINA (HMI)
Para o CFW500 IP66, a funcionalidade da HMI é intica à apresentada no manual do usuário CFW500.
Conforme Figura A.7 do ANEXO A - FIGURAS.
4 OPCIONAIS E ACESSÓRIOS
O filtro RFI está disponível como item opcional para a linha CFW500 IP66. Todos os acessórios de controle
descritos no Item 7.2 ACESSÓRIOS do manual do usuário do CFW500 IP20 estão disponíveis para a
linha CFW500 IP66.
5 ESPECIFICAÇÕES TÉCNICAS
Conforme Tabe l a B.1 a Tabela B.6 do ANEXO B - ESPECIFICAÇÕES TÉCNICAS.
APPENDIX A - FIGURES
ANEXO A - FIGURAS
[6.5]
165
[10.43]
265
[9.94]
252.5
[8.93]
227
[1.5]
38
[2.72]
69.3
[1.5]
38
Ø 28.3
[1.11]
[0.22]
Ø 5.7
Screw M5
Tornilho M5
Parafuso M5
C
1:1 Scale
Escala 1:1
[0.3]
7.5
D
1:1 Scale
Escala 1:1
[0.22]
5.7
Screw M5
Tornilho M5
Parafuso M5
[0.22]
Ø 5.7
[10.43]
265
[0.3]
7.5
[0.3]
7.5
A
B
[8.86]
225
Air flow / Flujo de aire / Fluxo de ar
Figure A.1: Dimensions of the CFW500 IP66 frame size A
Figura A.1: Dimensiones CFW500 IP66 tamaño A
Figura A.1: Dimensões CFW500 IP66 mecânica A
[0.22]
Ø 5.7
A
1:1 Scale
Escala 1:1
Screw M5
Tornilho M5
Parafuso M5
[0.3]
7.5
B
1:1 Scale
Escala 1:1
[0.22]
5.7
Screw M5
Tornilho M5
Parafuso M5
[8.46]
215
[13.39]
340
[11.82]
300
Air flow / Flujo de aire / Fluxo de ar
[0.22]
Ø 5.7
[12.8]
325
[0.3]
7.5
[0.3]
7.5
A
B
[9.96]
252.9
[8.94]
227
[1.63]
41.5
[1.63]
41.5
[1.63]
41.5
[2.72]
69
Ø 28.3
[1.11]
Figure A.2: Dimensions of the CFW500 IP66 frame size B
Figura A.2: Dimensiones CFW500 IP66 tamaño B
Figura A.2: Dimensões CFW500 IP66 mecânica B
(c) HMI cable disconnection
(c) Desconexión del cable de la HMI
(c) Desconexão cabo da HMI
(b) Removal the front cover
(b) Remocn del ciere
(b) Remoção do fechamento
(a) Location of the screws to
remove the unit
(a) Ubicación de los tornillos
para remoción
(a) Localização dos parafusos
para remoção
Figure A.3: (a) to (c) Procedure to remove the CFW500 IP66 front cover
Figura A.3: (a) a (c) Procedimiento de remoción del cierre frontal del CFW500 IP66
Figura A.3: (a) a (c) Procedimento de remoção do fechamento frontal do CFW500 IP66
4
7
6
5
1
3
2
(a) Frame size A
(a) Tamaño A
(a) Mecânica A
4
7
6
1
5
3
2
(b) Frame size B
(b) Tamaño B
(b) Mecânica B
1 - Dynamic braking cable entry
(1) (2)
2 - Control terminal
3 - Power terminal
4 - Ground
5 - Control cable entry
6 - Motor cable entry
7 - Power supply cable entry
1 - Entrada para cables de frenado
reostático
(1) (2)
2 - Borne de control
3 - Borne de potencia
4- Tierra
5 - Entrada para cables de control
6 - Entrada para cables del motor
7- Entrada para cables de alimentación
1 - Entrada para cabos da frenagem
reostática
(1) (2)
2 - Borne de controle
3 - Borne de potência
4- Terra
5 - Entrada para cabos de controle
6 - Entrada para cabos do motor
7- Entrada para cabos de alimentação
(1) When using dynamic braking for models available in frame A, it is necessary to break the entry obstruction and use appropriate cables and
cable glands according to Nema 4XIP66 protection rating. - Entry diameter: 16.1 mm / Cable gland: M16 x 1,5 or PG9.
(1) Cuando utilice el frenado reostático para los modelos disponibles en el tamaño A será necesario quebrar la obstrucción de la entrada y utilizar cables
y prensacables apropiados para el grado de protección Nema 4X/IP66. - Diámetro de la entrada: 16,1 mm / Prensacable: M16 x 1.5 o PG9.
(1) Quando utilizar a frenagem reostática para os modelos disponíveis na mecânica A é necessário quebrar a obstrução da entrada e utilizar cabos
e prensa cabos apropriados para o grau de proteção Nema 4X/IP66. - Diâmetro da entrada: 16,1 mm / Prensa cabo: M16 x 1.5 ou PG9.
(2) For UL compliance, S or SJ cables suitable for wet locations and identified with the letter "W" must be used to ensure Nema 4X protection rating.
(2) Para conformidad con La norma UL, deben ser utilizados cables tipo S o SJ apropiados para locales húmedos e identificados con la letra "W",
para garantizar el grado de protección Nema 4X.
(2) Para conformidade com a norma UL, cabos tipo S ou SJ apropriados para locais úmidos e identificados com a letra "W" devem ser utilizados
para garantir o grau de proteção Nema 4X.
Figure A.4: (a) and (b) Locations of the power, grounding and control connections
Figura A.4: (a) y (b) Ubicaciones de las conexiones de potencia, puesta a tierra y control
Figura A.4: (a) e (b) Localizações das conexões de potência, aterramento e controle
DI1
DI2
DI3
DI4
+24 V
DO1-RL-NO
DO1-RL-F
DO1-RL-NC
GND
GND
A-RS485 (-)
B-RS485 (+)
GND (485)
rpm
+10 V
AI1
GND
AO1
>300 Ω
+24 V
≥5 kΩ
DO2-TR
Connector/
Conector
Description/Descripción/Descrição
(**)
Top connection/Borne superior
1 DI1 Digital input 1 / Entrada digital 1
3 DI2 Digital input 2 / Entrada digital 2
(*)
5 DI3 Digital input 3 / Entrada digital 3
7 DI4 Digital input 4 / Entrada digital 4
9 +24 V
Power supply +24 Vdc /
Fuente +24 Vcc / Fonte +24 Vcc
11 DO1-RL-NO
Digital output 1 (NO contact of relay 1) /
Salida digital 1 (contacto NA del relé) /
Saída digital 1 (contato NA do relé 1)
13 DO1-RL-C
Digital output 1 (common point of relay 1) /
Salida digital 1 (punto común del relé 1) /
Saída digital 1 (ponto comum do relé 1)
15 DO1-RL-NC
Digital output 1 (NC contact of relay 1) /
Salida digital 1 (punto común del relé 1) /
Saída digital 1 (ponto comum do relé 1)
17 GND Reference 0 V/ Referencia 0 V/ Referência 0 V
Bottom connection/Borne inferior
2 AO1 Analog output 1/ Salida analógica 1/ Saída digital 1
4 GND Reference 0 V / Referencia 0 V / Referência 0 V
6 AI1 Analog input 1/ Entrada analógica 1
8 +10 V
Reference +10 Vdc for potentiometer /
Referencia +10 Vcc para potenciómetro /
Referência +10 Vcc para potenciômetro
10 DO2-TR
Digital output 2 (transistor) /
Salida digital 2 (transistor) /
Saída digital 2 (transistor)
12 GND Reference 0 V / Referencia 0 V / Referência 0 V
14 RS485 - A RS485 (terminal A)
16 RS485 - B RS485 (terminal B)
18 GND (485) GND (RS485)
(*) The digital input 2 (DI2) can also be used as input in frequency (FI). For further details refer to the programming manual of the CFW500.
(*) La entrada digital 2 (DI2) también puede ser usada como entrada en frecuencia (FI). Para más detalles consulte el manual de programación
del CFW500.
(*) A entrada digital 2 (DI2) também pode ser usada como entrada em frequência (FI). Para mais detalhes consulte o manual de programação do
CFW500.
(**) For more information see the detailed specification in Section 8.2 ELECTRONICS/GENERAL DATA of the user’s manual CFW500.
(**) Para más informaciones consulte la especificación detallada en la Sección 8.2 DATOS DE LA ELECTRÓNICA/GENERALES del manual del
usuario CFW500.
(**) Para mais informações consulte a especificação detalhada na Seção 8.2 DADOS DA ELETRÔNICA/GERAIS do manual do usuário CFW500.
Figure A.5: CFW500-IOS plug-in module connector signals
Figura A.5: Señales del conector del módulo plug-in CFW500-IOS
Figura A.5: Sinais do conector do módulo plug-in CFW500-IOS
(b) Location of the screws to close the unit
(b) Ubicación de los tornillos para cierre
(b) Localização dos parafusos para fechamento
(a) Position to close the unit
(a) Posicionamiento de cierre
(a) Posicionamento de fechamento
Figure A.6: (a) and (b) Product closing
Figura A.6: (a) y (b) Cierre del producto
Figura A.6: (a) e (b) Fechamento do produto
Figure A.7: HMI of the CFW500 Nema 4X/IP66
Figura A.7: HMI del CFW500 Nema 4X/IP66
Figura A.7: HMI do CFW500 Nema 4X/IP66
APPENDIX B - TECHNICAL SPECIFICATIONS
ANEXO B - ESPECIFICACIONES TÉCNICAS
ANEXO B - ESPECIFICAÇÕES TÉCNICAS
Table B.1: List of models of IP66 series, main electrical specifications
Tabla B.1: Relación de modelos de línea IP66, especificaciones eléctricas principales
Tabela B.1: Relação de modelos da linha IP66, especificações elétricas principais
Inverter
Convertidor
Inversor
Number of Input Phases
N° de Fases de Alimentación
N° de Fases de Alimentação
Power Supply Rated Voltage
Tensión Nominal de Alimentación
Tensão Nominal de Alimentação
Frame Size / Tamaño / Mecânica
Output Rated Current
Corriente Salida Nominal
Corrente Nominal de Saída
Maximum Motor
Motor Máximo
Power Wire Size
Calibre de los Cables de Potencia
Bitola dos Cabos de Poncia
Grounding Wire Size
Calibre del Cable de Aterramiento
Bitola do Cabo de Aterramento
Dynamic Braking
Frenado Reostático
Frenagem Reostática
Maximum Current
Corriente Máxima
Corrente Máxima
Recommended Resistor
Resistor Recomendado
Braking rms Current
Corriente Eficaz de
Frenado Corrente Eficaz de
Frenagem
Power Wire Size for DC+
and BR Terminals
Calibre de los Cables +UD
y BR Bitola dos Cabos
+UD e BR
[Vrms] [Arms] [HP/ kW]
mm²
(AWG)
mm²
(AWG)
(Imax)
[A]
[Ω] [A] mm² (AWG)
CFW500A01P6S2NB66
1
220 ...
240
A
1.6 0.25/0.18 1.5 (16) 2.5 (14) 6 127 4.5 1.5 (16)
CFW500A02P6S2NB66 2.6 0.5/0.37 1.5 (16) 2.5 (14) 6 127 4.5 1.5 (16)
CFW500A04P3S2NB66 4.3 1/0.75 1.5 (16) 2.5 (14) 6 127 4.5 1.5 (16)
CFW500A07P3S2DB66 7.3 2/1.5 4.0 (12) 4.0 (12) 10 39 7 2.5 (14)
CFW500A10P0S2DB66 10 3/2.2 4.0 (12) 4.0 (12) 15 27 11 2.5 (14)
CFW500A01P6B2NB66
1/3
1.6 0.25/0.18 1.5 (16) 2.5 (14) 6 127 4.5 1.5 (16)
CFW500A02P6B2NB66 2.6 0.5/0.37 1.5 (16) 2.5 (14) 6 127 4.5 1.5 (16)
CFW500A04P3B2NB66 4.3 1/0.75 1.5 (16) 2.5 (14) 6 127 4.5 1.5 (16)
CFW500A07P3B2DB66 7.3 2/1.5 4.0 (12) 4.0 (12) 10 39 7 2.5 (14)
CFW500A10P0B2DB66 10 3/2.2 4.0 (12) 4.0 (12) 15 27 11 2.5 (14)
CFW500A16P0T2DB66
3
16 5/3.7 4.0 (12) 4.0 (12) 20 20 14 4.0 (12)
CFW500B24P0T2DB66
B
24 7.5/5.5 6.0 (10) 4.0 (12) 26 15 13 6 (10)
CFW500B28P0T2DB66 28 10/ 7. 5 10.0 (8) 10.0 (8) 38 10 18 10 (8)
CFW500B33P0T2DB66 33 12.5/9.2 10.0 (8) 10.0 (8) 45 8.6 22 10 (8)
CFW500A01P0T4NB66
380 ...
480
A
1.0 0.25/0.18 1.5 (16) 2.5 (14) 6 127 4.5 1.5 (16)
CFW500A01P6T4NB66 1.6 0.5/0.37 1.5 (16) 2.5 (14) 6 127 4.5 1.5 (16)
CFW500A02P6T4DB66 2.6 1.5/1.1 1.5 (16) 2.5 (14) 6 127 4.5 1.5 (16)
CFW500A04P3T4DB66 4.3 2/1.5 1.5 (16) 2.5 (14) 6 127 4.5 1.5 (16)
CFW500A06P5T4DB66 6.5 3/2.2 1.5 (16) 2.5 (14) 8 100 5.7 2.5 (14)
CFW500A10P0T4DB66 10 5/3.7 2.5 (14) 2.5 (14) 16 47 11.5 2.5 (14)
CFW500B14P0T4DB66
B
14 7.5/5.5 4.0 (12) 4.0 (12) 24 33 14 6 (10)
CF W50 0B16P0T4DB66 16 10/7.5 4.0 (12) 4.0 (12) 24 33 14 6 (10)
CFW500B24P0T4DB66 24 15/11 6.0 (10) 6.0 (10) 34 22 21 10 (8)
CFW500B31P0T4DB66 31 20/15 10.0 (8) 10.0 (8) 48 18 27 10 (8)
CFW500B01P7T5DB66
500...
600
1.7 1/0.75 1.5 (16) 2.5 (14) 1.2 825 0.6 1.5 (16)
CFW500B03P0T5DB66 3.0 2/1.5 1.5 (16) 2.5 (14) 2.6 392 1.3 1.5 (16)
CFW500B04P3T5DB66 4.3 3/2.2 1.5 (16) 2.5 (14) 4 249 2 1.5 (16)
CFW500B07P0T5DB66 7.0 5/3.7 2.5 (14) 2.5 (14) 6 165 3 1.5 (16)
CFW500B10P0T5DB66 10 7.5/5.5 2.5 (14) 2.5 (14) 9 110 4.5 1.5 (16)
CFW500B12P0T5DB66 12 10 / 7.5 2.5 (14) 2.5 (14) 12.2 82 6.1 1.5 (16)
(1) The first number refers to the single-phase and the second to the three-phase supply.
(1) El primer número se refiere a la alimentacion monofásica y el segundo número a la alimentacion trifásica.
(1) O primeiro número refere-se à alimentação monofásica e o segundo número à alimentação trifásica.
Table B.2: Fuses and circuit breaker specifications according to UL standard
Tabla B.2: Especificaciones de fusibles y disyuntores conforme la norma UL
Tabela B.2: Especificações de fusíveis e disjuntores conforme norma UL
Inverter
Convertidor
Inversor
Inverter Protection With Fuses / Protección con Fusibles / Proteção com Fusível
Recommended Fuse
Fusible Recomendado
Fusível Recomendado
Circuit Breaker
Disyuntor
Disjuntor
t
[A²s]
Current
Corriente
Corrente [A]
Recommended WEG aR Fuse
Fusible aR WEG Recomendado
Fusível aR WEG Recomendado
[A] WEG
CFW500A01P6S2NB66 450 40
(2)
FNH00-40K-A 5.5 MPW18-3-D063
CFW500A02P6S2NB66 450 40
(2)
FNH00-40K-A 9.0 MPW18-3-U010
CFW500A04P3S2NB66 450 40
(2)
FNH00-40K-A 13.5 MPW18-3-U016
CFW500A07P3S2DB66 450 40
(2)
FNH00-40K-A 25 MPW40-3-U025
CFW500A10P0S2DB66 450 63
(2)
FNH00-40K-A 25 MPW40-3-U025
CFW500A01P6B2NB66 450 40/20
(1) (2)
FNH00-40K-A/
FNH00-20K-A
(1)
5.5/2.5
(1)
MPW18-3-D063/
MPW18-3-D025
(1)
CFW500A02P6B2NB66 450 40/20
(1) (2)
FNH00-40K-A/
FNH00-20K-A
(1)
9.0/4.0
(1)
MPW18-3-U010/
MPW18-3-U040
(1)
CFW500A04P3B2NB66 450 40/20
(1) (2)
FNH00-40K-A/
FNH00-20K-A
(1)
14/6.3
(1)
MPW18-3-U016/
MPW18-3-D063
(1)
CFW500A07P3B2DB66 450 40/20
(1) (2)
FNH00-40K-A/
FNH00-20K-A
(1)
25/12
(1)
MPW40-3-U025/
MPW18-3-U016
(1)
CFW500A10P0B2DB66 450 63/25
(1) (2)
FNH1-63K-A/
FNH00-25K-A
(1)
32/16
(1)
MPW40-3-U032/
MPW18-3-U016
(1)
CFW500A16P0T2DB66 1000 40
(2)
FNH00-40K-A 25 MPW40-3-U025
CFW500B24P0T2DB66 1000 63
(2)
FNH00-63K-A 40 MPW40-3-U040
CFW500B28P0T2DB66 2750 63
(3)
FNH00-63K-A 40 MPW65-3-U040
CFW500B33P0T2DB66 2750 80
(3)
FNH00-80K-A 50 MPW65-3-U050
CFW500A01P0T4NB66 450 20
(2)
FNH00-20K-A 1.6 MPW18-3-D016
CFW500A01P6T4NB66 450 20
(2)
FNH00-20K-A 2.5 MPW18-3-D025
CFW500A02P6T4DB66 450 20
(2)
FNH00-20K-A 4.0 MPW18-3-U004
CFW500A04P3T4DB66 450 20
(2)
FNH00-20K-A 6.3 MPW18-3-U063
CFW500A06P5T4DB66 450 20
(2)
FNH00-20K-A 10 MPW18-3-U010
CFW500A10P0T4DB66 1000 25
(2)
FNH00-25K-A 16 MPW18-3-U016
CFW500B14P0T4DB66 1000 35
(2)
FNH00-35K-A 20 MPW40-3-U020
CF W50 0B16P0T4DB66 1000 35
(2)
FNH00-35K-A 25 MPW40-3-U025
CFW500B24P0T4DB66 1800 60
(3)
FNH00-63K-A 40 MPW65-3-U040
CFW500B31P0T4DB66 1800 60
(3)
FNH00-63K-A 50 MPW65-3-U050
CFW500B01P7T5DB66 495 20
(2)
FNH00-20K-A 2.5 MPW18-3-U025
CFW500B03P0T5DB66 495 20
(2)
FNH00-20K-A 4 MPW18-3-U004
CFW500B04P3T5DB66 495 20
(2)
FNH00-20K-A 6.3 MPW18-3-U063
CFW500B07P0T5DB66 495 20
(2)
FNH00-20K-A 10 MPW18-3-U010
CFW500B10P0T5DB66 495 25
(2)
FNH00-25K-A 16 MPW18-3-U016
CFW500B12P0T5DB66 495 25
(2)
FNH00-25K-A 16 MPW18-3-U016
(1) The first number refers to the single-phase and the second to the three-phase supply.
(1) El primer número se refiere a la alimentacion monofásica y el segundo número a la alimentacion trifásica.
(1) O primeiro número refere-se à alimentação monofásica e o segundo número à alimentação trifásica.
(2) In order to comply with UL508C standard, use UL ultra fast fuses.
(2) Para estar de acuerdo con la norma UL508C, utilizar fusibles UL ultrarrápidos.
(2) Para estar de acordo com a norma UL508C, utilizar fusíveis UL ultra rápidos.
(3) In order to comply with UL508C standard, use fuses UL type J.
(3) Para estar de acuerdo con la norma UL508C, utilizar fusibles UL tipo J.
(3) Para estar de acordo com a norma UL508C, utilizar fusíveis UL tipo J.
Table B.3: Input and output currents, overload currents, carrier frequency, surrounding air temperature and power losses specifications
Tabla B.3: Especificaciones de corriente de salida y entrada, corrientes de sobrecarga, frecuencia de conmutación, temperatura
alrededor del convertidor y pérdidas
Tabela B.3: Especificações de corrente de saída e entrada, correntes de sobrecarga, frequência de chaveamento temperatura
ao redor do inversor e perdas
Inverter
Convertidor
Inversor
Output
Rated
Current
Corriente
Salida
Nominal
Corrente
Nominal de
Saída
Overload
Currents
Corrientes de
Sobrecarga
Correntes de
Sobrecarga
Rated Carrier
Frequency
Frecuencia de
Conmutación
Nominal
Frequência de
Chaveamento
Nominal
Nominal Inverter
Surrounding
Temperature
Temperatura
Nominal
Alrededor del
Convertidor
Temperatura
Nominal ao Redor
do Inversor
Input Rated
Current
Corriente
de Entrada
Nominal
Corrente
Nominal de
Entrada
Dynamic Braking
Frenado
Reostático
Frenagem
Reostática
Surface Mounting
Montaje en
Superfície
Montagem em
Superfície
(Inom)
[Arms]
1 min
[Arms]
3 s
[Arms]
(fsw)
[kHz]
C / ºF] [Arms] (W]
CFW500A01P6S2NB66 1.6 2.4 3.2 5 40 / 104 3.5 18
CFW500A02P6S2NB66 2.6 3.9 5.2 5 40 / 104 5.7 30
CFW500A04P3S2NB66 4.3 6.5 8.6 5 40 / 104 10.5 49
CFW500A07P3S2DB66 7.3 11 14.6 5 40 / 104 16 84
CFW500A10P0S2DB66 10 15 20 5 40 / 104 22.1 115
CFW500A01P6B2NB66 1.6 2.4 3.2 5 40 / 104 3.5/2.0
(1)
18
CFW500A02P6B2NB66 2.6 3.9 5.2 5 40 / 104 5.7 / 3.1
(1)
30
CFW500A04P3B2NB66 4.3 6.5 8.6 5 40 / 104 10.5 / 5.2
(1)
49
CFW500A07P3B2DB66 7. 3 11 14.6 5 40 / 104 16 / 8.6
(1)
84
CFW500A10P0B2DB66 10 15 20 5 40 / 104 22.1 / 12
(1)
115
CFW500A16P0T2DB66 16 24 32 5 40 / 104 19.5 185
CFW500B24P0T2DB66 24 36 48 4 40 / 104 29 275
CFW500B28P0T2DB66 28 42 56 5 40 / 104 34.2 320
CFW500B33P0T2DB66 33 49.5 66 5 40 / 104 40.3 380
CFW500A01P0T4NB66 1 1.5 2 5 40 / 104 1.2 20
CFW500A01P6T4NB66 1.6 2.4 3.2 5 40 / 104 1.9 25
CFW500A02P6T4DB66 2.6 3.9 5.2 5 40 / 104 3.2 45
CFW500A04P3T4DB66 4.3 6.5 8.6 5 40 / 104 5.2 65
CFW500A06P5T4DB66 6.5 9.8 13 5 40 / 104 7.8 105
CFW500A10P0T4DB66 10 15 20 5 40 / 104 12 170
CFW500B14P0T4DB66 14 21 28 5 40 / 104 17.1 220
CF W50 0B16P0T4DB66 16 24 32 5 40 / 104 19.5 270
CFW500B24P0T4DB66 24 36 48 5 40 / 104 29.3 405
CFW500B31P0T4DB66 31 46.5 62 5 40 / 104 37. 8 500
CFW500B01P7T5DB66 1.7 2.55 3.4 5 40 / 104 2.1 40
CFW500B03P0T5DB66 3 4.5 6 5 40 / 104 3.65 70
CFW500B04P3T5DB66 4.3 6.45 8.6 5 40 / 104 5.25 100
CFW500B07P0T5DB66 7 10.5 14 5 40 / 104 8.55 160
CFW500B10P0T5DB66 10 15 20 5 40 / 104 12.2 230
CFW500B12P0T5DB66 12 18 24 5 40 / 104 14.65 280
(1) The first number refers to the cables used at the terminals R/L1/L and S/L2/N, whereas the second number refers to the other power cables.
(1) El primer número se refiere a los cables usados en los bornes R/L1/L y S/L2/N mientras que el segundo número se refiere a los demás cables de
potencia.
(1) O primeiro número refere-se aos casos usados nos bornes R/L1/L e S/L2/N enquanto que o segundo número refere-se aos demais cabos de potência.
Table B.4: Conducted and radiated emission levels, and additional information
Tabla B.4: Niveles de emisión conducida y irradiada y informaciones adicionales
Tabela B.4: Níveis de emissão conduzida e radiada e informações adicionais
Inverter Model
Modelo del Convertidor de
Frecuencia
Modelo do Inversor
Conducted Emission
Emisión Conducida
Emissão Conduzida
Radiated Emission
Emisión Radiada
Emissão Radiada
Category C3
Categoría C3
Categoria C3
Category C2
Categoría C2
Categoria C2
Category
Categoría
Categoria
1 CFW500A01P6S2NB66C3 TBD TBD TBD
2 CFW500A02P6S2NB66C3 TBD TBD TBD
3 CFW500A04P3S2NB66C3 TBD TBD TBD
4 CFW500A07P3S2DB66C2 TBD TBD TBD
5 CFW500A10P0S2DB66C2 TBD TBD TBD
6 CFW500A01P0T4NB66C3 TBD TBD TBD
7 CFW500A01P6T4NB66C3 TBD TBD TBD
8 CFW500A02P6T4DB66C2 TBD TBD TBD
9 CFW500A04P3T4DB66C2 TBD TBD TBD
10 CFW500A06P5T4DB66C2 TBD TBD TBD
11 CFW500A10P0T4DB66C3 TBD TBD TBD
12 CFW500B28P0T2DB66C3 TBD TBD TBD
13 CFW500B33P0T2DB66C3 TBD TBD TBD
14 CFW500B14P0T4DB66C2 TBD TBD TBD
15 CFW500B16P0T4DB66C2 TBD TBD TBD
16 CFW500B24P0T4DB66C3 TBD TBD TBD
17 CFW500B31P0T4DB66C3 TBD TBD TBD
For conducted emission category C2, the switching frequency is 10 KHz for models 1, 2, 3, 4 and 5.
For conducted emission category C2, the switching frequency is 5 KHz for models 6, 7, 8, 9, 10, 14 e 15.
For conducted emission category C2, in model 10, use ferrite 12480705 on the output cables (1 turn).
For conducted emission category C2, in models 14 and 15, use ferrite 12473659 on the output cables (2 turns).
For conducted emission category C3, the switching frequency is 10 KHz for models 1, 2, 3, 4 and 5.
For conducted emission category C3, the switching frequency is 5 KHz for models 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16 and 17.
For conducted emission category C3, in model 11, use the ferrite 12480705 on the output cables (2 turns) and use ferrite 12480705 on the
input cables (2 turns).
For conducted emission C3, in models 14 and 15, use the ferrite 12473659 on the output cables (1 turn).
For conducted emission category C3, in models 12, 13, 16 and 17, use ferrite 12983778 on the output cables (1 turn) and ferrite 12983778 on
the input cables (2 turns).
For Radiated Emission, in models 1, 2, 3, 6, 7, 8 and 9, use shielded cable up to 6 m.
For Radiated Emission, in models 4, 5, 10, 11, 12, 13, 16 and 17, use shielded cable up to 30 m.
For Radiated Emission, in models 14 and 15, use ferrite 12473659. Use shielded cable up to 30 m.
Para emisión conducida categoría C2, la frecuencia de conmutación es de 10 KHz para los modelos 1, 2, 3, 4 y 5.
Para emisión conducida categoría C2, la frecuencia de conmutación es de 5 KHz para los modelos 6, 7, 8, 9, 10, 14 y 15.
Para emisión conducida categoría C2, en el modelo 10 utilizar ferrita 12480705 en los cables de salida (1 vuelta).
Para emisión conducida categoría C2, en los modelos 14 y 15 utilizar ferrita 12473659 en los cables de salida (2 vueltas).
Para emisión conducida categoría C3, la frecuencia de conmutación es de 10 KHz para los modelos 1, 2, 3, 4 y 5.
Para emisión conducida categoría C3, la frecuencia de conmutación es de 5 KHz para los modelos 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16 y 17.
Para emisión conducida categoría C3, en el modelo 11 utilizar ferrita 12480705 en los cables de salida (2 vueltas) y utilizar ferrita 12480705 en
los cables de entrada (2 vueltas).
Para emisión conducida categoría C3, los modelos 14 y 15 utilizar ferrita 12473659 en los cables de salida (1 vuelta).
Para emisión conducida categoría C3, en los modelos 12, 13, 16 y 17 utilizar ferrita 12983778 en los cables de salida (1 vuelta) y utilizar ferrita
12983778 en los cables de entrada (2 vueltas).
Para Emisión Radiada, en los modelos 1, 2, 3, 6, 7, 8 y 9 utilizar cable blindado de hasta 6 m.
Para emisión Radiada, en los modelos 4, 5, 10, 11, 12, 13, 16 y 17 utilizar cable blindado de hasta 30 m.
Para Emisión Radiada, en los modelos 14 y 15 utilizar ferrita 12473659. Utilizar cable blindado de hasta 30 m.
Para emissão conduzida categoria C2, a frequência de chaveamento é de 10 KHz para os modelos 1, 2, 3, 4 e 5.
Para emissão conduzida categoria C2, a frequência de chaveamento é de 5 KHz para os modelos 6, 7, 8, 9, 10, 14 e 15.
Para emissão conduzida categoria C2, no modelo 10 utilizar o ferrite 12480705 nos cabos de saída (1 volta).
Para emissão conduzida categoria C2, nos modelos 14 e 15 utilizar o ferrite 12473659 nos cabos de saída (2 voltas).
Para emissão conduzida categoria C3, a frequência de chaveamento é de 10 KHz para os modelos 1, 2, 3, 4 e 5.
Para emissão conduzida categoria C3, a frequência de chaveamento é de 5 KHz para os modelos 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16 e 17.
Para emissão conduzida categoria C3, no modelo 11 utilizar o ferrite 12480705 nos cabos de saída (2 voltas) e utilizar o ferrite 12480705 nos
cabos de entrada (2 voltas).
Para emissão conduzida categoria C3, os modelos 14 e 15 utilizar o ferrite 12473659 nos cabos de saída (1 volta).
Para emissão conduzida categoria C3, nos modelos 12, 13, 16 e 17 utilizar o ferrite 12983778 nos cabos de saída (1 volta) e utilizar o ferrite
12983778 nos cabos de entrada (2 voltas).
Para Emissão Radiada, nos modelos 1, 2, 3, 6, 7, 8 e 9 utilizar cabo blindado de até 6 m.
Para Emissão Radiada, nos modelos 4, 5, 10, 11, 12, 13, 16 e 17 utilizar cabo blindado de até 30 m.
Para Emissão Radiada, nos modelos 14 e 15 utilizar o ferrite 12473659. Utilizar cabo blindado de até 30 m.
Table B.5: Output current specification as a function of the frequency switching to CFW500 Nema 4x/IP66
Tabla B.5: Especificación de la corriente de salida en función de la frecuencia de conmutación para el CFW500 Nema 4x/IP66
Tabela B.5: Especificação da corrente de saída em função da frequência de chaveamento para o CFW500 Nema 4x/IP66
Inverter Model
Modelo del Convertidor de Frecuencia
Modelo do Inversor
2.5 KHz 5.0 KHz 10.0 KHz 15.0 KHz
CFW500A01P6S2NB66 1.6 1.6 1.6 1.6
CFW500A02P6S2NB66 2.6 2.6 2.6 2.6
CFW500A04P3S2NB66 4.3 4.3 3.5 2.8
CFW500A07P3S2DB66 7.3 7.3 6.1 5.1
CFW500A10P0S2DB66 10 10 8 6.7
CFW500A01P6B2NB66 1.6 1.6 1.6 1.6
CFW500A02P6B2NB66 2.6 2.6 2.6 2.6
CFW500A04P3B2NB66 4.3 4.3 3.5 2.8
CFW500A07P3B2DB66 7.3 7.3 6.1 5.1
CFW500A10P0B2DB66 10 10 8 6.7
CFW500A16P0T2DB66 16 16 12.7 10.1
CFW500B28P0T2DB66 28 28 22 18
CFW500B33P0T2DB66 33 33 26 21
CFW500A01P0T4NB66 1 1 1 1
CFW500A01P6T4NB66 1.6 1.6 1.6 1.6
CFW500A02P6T4DB66 2.6 2.6 2.6 2
CFW500A04P3T4DB66 4.3 4.3 2.9 2
CFW500A06P5T4DB66 6.5 6.5 4.5 3.3
CFW500A10P0T4DB66 10 10 6.5 4.3
CFW500B14P0T4DB66 14 14 10 7
CF W50 0B16P0T4DB66 16 16 10 7
CFW500B24P0T4DB66 24 24 15 12
CFW500B31P0T4DB66 31 31 16 13
CFW500B01P7T5DB66 1.7 1.7 1.7 1.7
CFW500B03P0T5DB66 3 3 3 3
CFW500B04P3T5DB66 4.3 4.3 4.3 4.3
CFW500B07P0T5DB66 7 7 7 7
CFW500B10P0T5DB66 10 10 9 7
CFW500B12P0T5DB66 12 12 9 7
Table B.6: Output current specification as a function of the frequency switching to CFW500 Nema 4x/IP66
Tabla B.6: Especificación de la corriente de salida en función de la frecuencia de conmutación para el CFW500 Nema 4x/IP66
Tabela B.6: Especificação da corrente de saída em função da frequência de chaveamento para o CFW500 Nema 4x/IP66
Inverter Model
Modelo del Convertidor de Frecuencia
Modelo do Inversor
2.5 KHz 4.0 KHz 10.0 KHz 15.0 KHz
CFW500B24P0T2DB66 24 24 19 16
  • Page 1 1
  • Page 2 2

WEG CFW500 IP66 Manual de usuario

Tipo
Manual de usuario

En otros idiomas