Eaton 3h.508 Operating Instructions Manual

Tipo
Operating Instructions Manual

Este manual también es adecuado para

For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
Operating Instructions
LCD Hour Meter
E5224C Series
The E5224C Series are battery-powered LCD hour
meters. Typical elapsed timer applications include run
time, product life, cycle time, and time monitoring.
They are controlled by means of dry contacts or voltage
pulses.
DC models:
Timer: INP A: no function
INP B: Timer-Enable-Input
Main technical features:
Display: LCD, 8 decades, height of the figures 8 mm
[0.31 in.]
Display range:
0 – 99999999 with lead zero blanking.
Error: < 100 ppm
Overflow:
In case of a display range overflow, the timer
starts again from 0, but without removing the
leading zeros and activating all decimal
points.
Reset key: Requires rear terminal jumper to enable.
Housing: Panel mounting, 48 x 24 mm [1.89 x 0.94 in.]
according to DIN 43 700, RAL 7021
Panel cut-out:
22.2 x 45 mm [0.87 x 1.77 in.]
22.5 x 45.6 mm [0.89 x 1.80 in.] max.
Mounting depth:
approximately 48 mm [1.89 in.]
Weight: approximately 50 g [1.76 oz.]
Front panel rating:
IP65
AC/DC models:
Timer: INP A: Timer-Enable-Input AC/DC
INP B: reset input AC/DC
Connection:
Screw terminals, RM 5.00, 8 poles
Rated cross-section: 4.0 mm
2
solid wire
2.5 mm
2
stranded wire
AWG 12
Connection diameter:
0.4 – 2.3 mm
2
solid wire
AWG 28-12
EMC: Emissions per EN55011 Class B
Susceptibility per EN 61000-6-2
Low Voltage Directive (for the AC/DC models):
EN 61010 Part 1 ; overvoltage category 2,
pollution level 2
Power supply:
Non-replaceable lithium battery (lifetime
approximately 8 years at 20°C [68°F])
Working temperature:
-10 to +55°C [14 to 131°F], relative humidity
< 85%, non-condensing
Operating temperature:
-10 to +60°C [14 to 140°F]
Storage temperature:
-20 to +70°C [-4 to 158°F]
Backlighting:
must be powered by an external elecrical
source (24V ±20%, 50 mA)
Table 1
Overview
Model Operating mode Time range Inputs
INP A INP B
E5224C0440 Timer 99999h 59 m/
99999.99 h
0 – 0.7V DC NPN
E52240C448 10 – 260V AC/DC AC/DC 10 – 260V AC/DC AC/DC
E5224C0450 Timer 9999 h 59 m 59 s/
9999999.9 s
0 – 0.7V DC NPN
E5224C0458 10 – 260V AC/DC AC/DC 10 – 260V AC/DC AC/DC
deutsch
français
español
english
MN05401006E 1
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
Screw terminal 1: no function
Screw terminal 2:
Timer Enable Input:
time measurement as long as the
input is active
NPN: active for low level
Input resistance: approximately 1 MOhm
Low level: 0 – 0.7V DC
High level: 3 – 30V DC
PNP: active for high level
Input resistance: approximately 100 kOhm
Low-level: 0 – 0.7V DC
High-level: 4 – 30V DC
Screw terminal 3:
Reset input:
active for negative edge contact
input / Open Collector NPN
Low level: 0 – 0.7V DC
High level: 3 – 30V DC
Min. pulse duration: 50 ms
Input resistance: approximately 2.2 MOhm
Screw terminal 4:
Reset key enable
Contact input / Open Collector NPN
Low level: 0 – 0.7V DC
High level: 3 – 5V DC
Input resistance: approximately. 2.2 MOhm
Input not active:
Reset key disabled
Input active (contact with GND):
Reset key enabled
Screw terminal
5:
Time range switching (Mode)
contact input / Open Collector NPN
Low level: 0 – 0.7V DC
High level: 3 – 5V DC
Input resistance: approximately. 2.2 MOhm
Function: see table 2
Remark
If the time range is changed during
operation,
the device must be reset.
Screw terminal
6:
Common GND connection
for all inputs
Screw terminal
7:
(–) external power supply for the backlight option
Screw terminal
8:
(+) external power supply for the backlight option
(24V DC ±20%, 50 mA)
Table 2
2 MN05401006E
Input specifications, terminal assignment and adjustable time ranges (DC versions)
The time range is set via a control input (screw terminal 5).
Screw terminal No. 1 No. 2 No. 3 No. 4 No. 5 No. 6 No. 7 No. 8
Designation
Model
INP A INP B Reset Reset
Enable
Time range (Mode) GND BL
BL
+
E5224C0440
no function
Timer Enable Input
NPN
NPN reset input
Reset key enabled
when connected to
gnd.
open =
99999 h 59 m
contact with
GND =
99999.99 h
GND = 0V DC
Backlighting (–)
Backlighting (+)
E5224C0450 NPN
open =
9999 h 59 m 59 s
contact with
GND =
9999999.9 s
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
Screw terminal 1:
Timer Enable Input:
time measurement as long as the
level at this input is high.
Optocoupler input 10 – 260V AC/DC
galvanic isolation, active for High
signal
Low level: 0 – 2V AC/DC
High level: 10 – 260V AC/DC
Input resistance: approximately 160 kOhm
Screw terminal 2:
Common AC/DC, common connection for the
optocoupler inputs (screw terminals 1 and 3)
Screw terminal 3:
Reset input:
10 – 260V AC/DC galvanic
isolation
Min. pulse duration: 16 ms
Max. frequency: approximately 30 Hz
Low level: 0 – 2V AC/DC
High level: 10 – 260V AC/DC
Input resistance: approximately 160 kOhm
Screw terminal
4:
Reset key enable
Contact input / Open Collector NPN
Low level: 0 – 0.7V DC
High level: 3 – 5V DC
Input resistance: approximately
2.2 MOhm
Input not active: Reset key disabled
Input in contact with GND:
Reset key enabled
Screw terminal 5:
Time range switching (Mode)
Contact input / Open Collector NPN
Low level: 0 – 0.7V DC
High level: 3 – 5V DC
Input resistance: approximately 2.2 MOhm
Function: see table 3
Remark:
If the time range is changed during
operation,
the device must be reset.
Screw terminal 6:
Common GND connection for screw terminal 4
(reset key locking input) and screw terminal 5
(time range switching).
Screw terminal 7:
(–) external power supply for the backlight option
Screw terminal 8:
(+) external power supply for the backlight option
(24V DC ±20%, 50 mA)
Table 3
english
MN05401006E 3
Input specification, terminal assignment and adjustable time ranges (AC/DC versions)
The time range is set via a control input (screw terminal 5).
Screw terminal No. 1 No. 2 No. 3 No. 4 No. 5 No. 6 No. 7 No. 8
Designation
Model
INP A
AC/DC
Common
AC/DC
INP B
AC/DC
Reset
Enable
Time range (Mode) GND BL
BL
+
E5224C0448
Timer Enable
Input AC/DC
Common
connection for
INP A and INP B
reset input
AC/DC
NPN reset key
locking input,
Contact with
GND. key free.
not active =
99999 h 59 m
contact with
GND =
99999.99 h
GND = 0V DC
Backlighting (–)
Backlighting (+)
E5224C0458
not active =
9999 h 59 m 59 s
contact with
GND =
9999999.9 s
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
Contents:
Timer
Clamp
Front frame for screw mounting,
Panel cut-out 50 x 25 mm [1.97 x 0.98 in.]
Front frame for clamp mounting,
Panel cut-out 50 x 25 mm [1.97 x 0.98 in.]
Seal
Operating instructions
Installation:
DC versions:
Use shielded wires for the counting and control inputs to
obtain the maximum EMC resistance.
Use according to the intended purpose:
This device may only be used inside as a panel-
mounted device! Applications of this product may be
found in industrial processes and controls in the branch
of the manufacturing lines for the metal, wood, plastics,
paper, glass, textile, etc., processing industries. It must
be considered that the overvoltages at the terminals of
the device must be limited to the values of overvoltage
category II. Overvoltage category II is described in the
standard EN 61 010 Part 1.
This device shall only operate when it has been
correctly mounted in a panel. It may only be used in
accordance with the chapter “Main technical features”.
This device shall not be used:
– in areas with risks of explosion,
– in the branches expressly quoted in the standard
EN 61 010.
If this device is used to monitor machines or a process
in which, in case of a failure of the device, there might
be risks of damaging the machine or causing accidents
to the operators, it is up to you to take appropriate
safety measures.
Note:
This product includes a lithium battery. Do not
open it by force, do not throw it in the fire.
Avoid temperatures below -20°C [-4°F] and
above 70°C [158°F]!
AC/DC versions:
Use shielded wires for the counting and control inputs to
obtain the maximum EMC resistance.
Safety instructions:
Only use these counters
– according to their intended
purpose
– if their technical condition is
perfect
– adhering to the operating
instructions and the general
safety instructions.
Also take into account the fact that there may exist user
or country-specific safety regulations, which must also
be followed.
!
4 MN05401006E
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
español
MN05401006E 5
Instrucciones de operación
Contadores con pantalla LCD
Serie E5224C
Los contadores con pantalla LCD de la serie E5224C
funcionan a baterías. Las aplicaciones típicas del
contador de tiempo transcurrido incluyen tiempo de
ejecución, vida útil del producto, tiempo de ciclo y
control de tiempo.
Se controlan por medio de contactos secos o por
impulsos de voltaje.
Modelos CC:
Temporizador: ENT A: sin función
ENT B: Entrada de habilitación
de temporizador
Características técnicas principales:
Pantalla: LCD, 8 decimales, altura de cifras 8 mm
[0,31 pulg.]
Rango de pantalla:
0 – 99999999 con supresión de cero inicial.
Error: < 100 ppm
Exceso:
En caso de exceso del rango de pantalla, el
temporizador vuelve a comenzar desde 0,
pero sin quitar los ceros iniciales y activando
los puntos decimales.
Tecla de restablecimiento:
Para habilitar se requiere el puente de borne
posterior.
Cubierta: Montaje en panel, 48 x 24 mm [1,89 x
0,94 pulg.] según DIN 43 700, RAL 7021
Plantilla de recorte del panel:
22,2 x 45 mm [0,87 x 1,77 pulg.]
22,5 x 45,6 mm [0,89 x 1,80 pulg.] máx.
Profundidad de montaje:
48 mm aproximadamente [1,89 pulg.]
Peso: 50 g aproximadamente [1,76 oz.]
Clasificación del panel delantero:
IP65
Modelos CA/CC:
Temporizador: ENT A: Entrada de habilitación
de temporizador CA/CC
ENT B: Entrada de
restablecimiento
CA/CC
Conexión:
Bornes de tornillo, RM 5,00, 8 polos
Sección transversal
clasificada: 4,0 mm
2
cable simple
2,5 mm
2
cable trenzado
AWG 12
Diámetro de la
conexión: 0,4 – 2,3 mm
2
cable
simple
AWG28-12
EMC: Emisiones por EN55011 Clase B
susceptibilidad por EN 61000-6-2
Directiva de bajo voltaje (para los modelos CA/CC):
EN 61010 Parte 1; categoría de sobrevoltaje
2, nivel de contaminación 2
Suministro de energía:
Batería de litio no reemplazable (vida útil
aproximada de 8 años a 20º C [68° F])
Temperatura de trabajo:
-10 a +55° C [14 a 131° F], humedad
relativa < 85%, sin condensación
Temperatura de funcionamiento:
-10 a +60° C [14 a 140° F]
Temperatura de almacenamiento:
-20 a +70° C [-4 a 158° F]
Iluminación posterior:
Se debe alimentar por medio de una fuente
eléctrica externa (24 V ± 20%, 50 mA)
Tabla 1
Información general
Modelo Modo de
funcionamiento
Rango de tiempo Entradas
ENT A ENT B
E5224C0440 Temporizador 99999h 59 m/
99999,99 h
0 – 0,7 V CC NPN
E52240C448 10 – 260 V CA/CC CA/CC 10 – 260 V CA/CC CA/CC
E5224C0450 Temporizador 9999 h 59 m 59 seg./
9999999,9 seg.
0 – 0,7 V CC NPN
E5224C0458 10 – 260 V CA/CC CA/CC 10 – 260 V CA/CC CA/CC
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
6 MN05401006E
Borne de tornillo 1: Sin función
Borne de tornillo 2:
Entrada de habilitación del temporizador:
Medición del tiempo mientras
la entrada esté activa
NPN: Activo para nivel bajo
Resistencia de entrada: Aproximadamente 1 MOhm
Nivel bajo: 0 – 0,7 V CC
Nivel alto: 3 – 30 V CC
PNP: Activo para nivel alto
Resistencia de entrada: Aproximadamente 100 kOhm
Nivel bajo: 0 – 0,7 V CC
Nivel alto: 4 – 30 V CC
Borne de tornillo 3:
Entrada de restablecimiento:
Activo para entrada de
contacto de borde negativo/
NPN de toma de corriente
abierta
Nivel bajo: 0 – 0,7 V CC
Nivel alto: 3 – 30 V CC
Duración de impulso mín: 50 ms
Resistencia de entrada: Aproximadamente 2,2 MOhm
Borne de tornillo 4:
Habilitación de tecla de restablecimiento
Entrada de contacto/NPN de toma de corriente abierta
Nivel bajo: 0 – 0,7 V CC
Nivel alto: 3 – 5 V CC
Resistencia de entrada: Aproximadamente 2,2 MOhm
Entrada inactiva:
Tecla de restablecimiento
deshabilitada
Entrada activa (contacto a tierra):
Tecla de restablecimiento
habilitada
Borne de tornillo
5:
Conmutación de rango de tiempo (modo)
Entrada de contacto/NPN de toma de corriente abierta
Nivel bajo: 0 – 0,7 V CC
Nivel alto: 3 – 5 V CC
Resistencia de entrada: Aproximadamente 2,2 MOhm
Función: Consulte la Tabla 2
Observación
Si se cambia el rango de tiempo durante
la operación,
se debe restablecer el
dispositivo.
Borne de tornillo
6:
Conexión a tierra común
para todas las entradas
Borne de tornillo
7:
(–) suministro de energía para la opción de
iluminación posterior
Borne de tornillo
8:
(+) suministro de energía para la opción de
iluminación posterior
(24 V CC ±20%, 50 mA)
Tabla 2
Especificaciones de entrada, asignación de borne y rangos de tiempo ajustables (versiones de CC)
Se configura el rango de tiempo por medio de una entrada de control (borne de tornillo 5).
Borne de tornillo Nº 1 Nº 2 Nº 3 Nº 4 Nº 5 Nº 6 Nº 7 Nº 8
Designación
Modelo
ENT A ENT B Restable-
cimiento
Habilita-
ción del
restable-
cimiento
Rango de tiempo
(modo)
CONEXIÓN
A TIERRA
BL
BL
+
E5224C0440
Sin función
Entrada de la habilitación
del temporizador
NPN
Entrada de
restablecimiento NPN
La tecla de restablecimiento
se habilita cuando está
conectada a tierra.
Abierto =
99999 h
59 m
Contacto a
tierra =
99999,99 h
CONEXIÓN A TIERRA =
0 V CC
Iluminación posterior (–)
Iluminación posterior (+)
E5224C0450 NPN
Abierto =
9999 h
59 m
59 seg.
Contacto a
tierra =
9999999,9
seg.
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
MN05401006E 7
español
Borne de tornillo 1:
Entrada de habilitación del temporizador:
Medición del tiempo mientras
el nivel en esta entrada sea
alto.
Entrada de optoacoplador:
10 – 260 V CA/CC
Aislamiento galvánico, activo
para señal alta
Nivel bajo: 0 – 2 V CA/CC
Nivel alto: 10 – 260 V CA/CC
Resistencia de entrada: Aproximadamente 160 kOhm
Borne de tornillo 2:
CA/CC común, conexión común para entradas de
optoacoplador (bornes de tornillo 1 y 3)
Borne de tornillo 3:
Entrada de restablecimiento:
10 – 260 V CA/CC
aislamiento galvánico
Duración de impulso mín: 16 ms
Frecuencia máx: Aproximadamente 30 Hz
Nivel bajo: 0 – 2 V CA/CC
Nivel alto: 10 – 260 V CA/CC
Resistencia de entrada: Aproximadamente 160 kOhm
Borne de tornillo
4:
Habilitación de tecla de restablecimiento
Entrada de contacto/NPN de toma de corriente
abierta
Nivel bajo: 0 – 0,7 V CC
Nivel alto: 3 – 5 V CC
Resistencia de entrada: Aproximadamente
2,2 MOhm
Entrada inactiva: Tecla de restablecimiento
deshabilitada
Entrada en contacto a tierra:
Tecla de restablecimiento
habilitada
Borne de tornillo 5:
Conmutación de rango de tiempo (modo)
entrada de contacto/NPN de toma de corriente
abierta
Nivel bajo: 0 – 0,7 V CC
Nivel alto: 3 – 5 V CC
Resistencia de
entrada: Aproximadamente 2.2 MOhm
Función: Consulte la Tabla 3
Observación:
Si se cambia el rango de tiempo durante la
operación,
se debe restablecer el dispositivo.
Borne de tornillo 6:
Conexión a tierra común para borne de tornillo 4
(tecla de restablecimiento entrada de bloqueo) y
borne de tornillo 5 (conmutación del rango de
tiempo).
Borne de tornillo 7:
(–) suministro de energía externo para la opción de
iluminación posterior
Borne de tornillo 8:
(+) suministro de energía externo para la opción de
iluminación posterior
(24 V CC ±20%, 50 mA)
Tabla 3
Especificaciones de entrada, asignación de borne y rangos de tiempo ajustables
(versiones CA/CC)
Se configura el rango de tiempo por medio de una entrada de control (borne de tornillo 5).
Borne de tornillo Nº 1 Nº 2 Nº 3 Nº 4 Nº 5 Nº 6 Nº 7 Nº 8
Designación
Modelo
ENT A
CA/CC
CA/CC
común
ENT B
CA/CC
Habilitación del
restablecimiento
Rango de tiempo (modo) CONEXIÓN
A TIERRA
BL
BL
+
E5224C0448
Entrada de habilitación
del temporizador CA/CC
Conexión común para
ENT A y ENT B
Entrada de
restablecimiento CA/CC
Entrada de bloqueo de
tecla de restablecimiento
NPN, contacto a tierra.
Llave libre.
Inactiva =
99999 h
59 m
Contacto a
tierra =
99999,99 h
CONEXIÓN A TIERRA =
0 V CC
Iluminación posterior (–)
Iluminación posterior (+)
E5224C0458
Inactiva =
9999 h
59 m 59 s
Contacto a
tierra =
9999999,9 seg.
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
8 MN05401006E
Contenido:
Temporizador
Abrazadera de sujeción
Bastidor delantero para el montaje con tornillos, plantilla
de recorte del panel 50 x 25 mm [1,97 x 0,98 pulg.]
Bastidor delantero para montaje de abrazadera de
sujeción, plantilla de recorte del panel de 50 x 25 mm
[1,97 x 0,98 pulg.]
Sello
Instrucciones de operación
Instalación:
Versiones de CC:
Use cables blindados para el conteo y las entradas de
control, para así obtener el máximo de resistencia
EMC.
Úselo de acuerdo al propósito para el que fue
creado:
¡Este dispositivo puede usarse sólo en el interior como
un dispositivo montado en el panel! Las aplicaciones de
este producto se pueden encontrar en procesos
industriales y controles en la derivación de líneas de
fabricación para procesos industriales del metal,
madera, plástico, papel, vidrio, textil, etc. Se debe tener
en cuenta que los sobrevoltajes en los bornes del
dispositivo se deben limitar a los valores de la categoría
de sobrevoltaje II. La categoría de sobrevoltaje II se
describe en la norma EN 61 010 Parte 1.
Este dispositivo sólo funcionará cuando se haya
montado correctamente en un panel. Sólo se puede
usar de acuerdo con el capítulo “Características
técnicas principales”.
Este dispositivo no se debe usar:
– en áreas con riesgo de explosión,
– en las derivaciones expresamente citadas en la
norma EN 61 010.
Si el dispositivo se usa para controlar máquinas o
procesos en los que, en caso de falla del dispositivo,
podría haber riesgos de dañar la máquina o causar
accidentes a los operadores, es su deber tomar las
medidas de seguridad apropiadas.
Nota:
Este producto cuenta con una batería de litio.
No lo abra a la fuerza, no lo lance a las
llamas. ¡Evite temperaturas menores que
-20º C [-4° F] y mayores que 70° C [158° F]!
Versiones de CA/CC:
Use cables blindados para el conteo y las entradas de
control, para así obtener el máximo de resistencia
EMC.
Instrucciones de seguridad:
Sólo use estos contadores
– de acuerdo al propósito para el
que fueron creados;
– si su condición técnica es
perfecta;
– respetando las instrucciones de
operación y las instrucciones
generales de seguridad.
También tenga en cuenta el hecho de que podrían
existir normas de seguridad específicas para el país o
usuario, que también se deben cumplir.
!
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
MN05401006E 9
français
Instructions d’utilisation
Compteurs horaires à affichage LCD
E5224C Série
Les compteurs horaires à affichage LCD E5224C Série
sont alimentés par batterie. Ils trouvent leur place dans
les applications les plus variées, par exemple: mesure
du temps de fonctionnement et de la durée de vie,
mesure du temps de passage, surveillance du temps,
etc.
Ils sont commandés par des contacts secs ou des
impulsions de tension.
Modes opératoires DC :
Compteur: INP A: sans fonction
INP B: entrée Timer Enable
Caractéristiques techniques générales :
Affichage :LCD, 8 décades, hauteur des chiffres 8 mm.
Plage d’affichage :
0 ... 99999999 avec
suppression des zéros de tête.
Précision: < 100 ppm
Dépassement :
En cas de dépassement de la plage
d’affichage, le compteur repart de 0, mais
sans suppression des zéros de tête et en
activant tous les points décimaux.
Touches: Verrouillage électrique de la touche de RAZ
Boîtier : Montage dans tableau, 48 x 24 mm
suivant DIN 43 700, RAL 7021
Découpe d’encastrement :
22,2
+0,3
x 45
+0,6
mm
Profondeur de montage : env. 48 mm
Poids : env. 50 g
Indice de protection : IP65 sur la face avant
Modes opératoires AC :
Compteur: INP A: entrée Timer Enable AC/DC
INP B: entrée de remise à zéro AC/DC
Raccordements :
Bornes à vis, RM 5.00, 8 bornes
Section nominale : 4,0 mm
2
monoconducteur
2,5 mm
2
fils fins AWG 12
Diamètre de raccordement :
0,4 ... 2,3 mm monoconducteur
AWG 28-12
CEM : Emissions parasites EN55011 Classe B
Résistance aux parasites EN 61000-6-2
Directive Basse Tension (pour les modèles AC) :
EN 61010 Partie 1;catégorie de surtension 2,
degré de contamination 2
Alimentation :
Batterie au lithium non remplaçable
(durée de vie env. 8 ans à 20°C)
Température de travail :
–10 ... +55 °C, humidité relative < 85%, sans
condensation
Température de fonctionnement :
–10 ... +60 °C
Température de stockage :
–20 .. +70°C
Rétroéclairage:
doit être alimenté par une source électrique
extérieure (24 V ±20%, 50 mA)
Tableau 1
Modèles
Modèle Mode
opératoire
Plage de temps Entrées de comptage
INP A INP B
E5224C0440 Compteur
horaire
99999h 59 m/
99999.99 h
0 ... 0,7 V DC NPN
E5224C0448 10 ... 260 V AC/DC AC/DC 10 ... 260 V AC/DC AC/DC
E5224C0450 Compteur
horaire
9999 h 59 m 59 s/
9999999.9 s
0 ... 0,7 V DC NPN
E5224C0458 10 ... 260 V AC/DC AC/DC 10 ... 260 V AC/DC AC/DC
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
10 MN05401006E
Borne à vis 1: sans fonction
Borne à vis 2:
Entrée Timer Enable:
Mesure du temps tant que
l’entrée est active
NPN: active pour niveau bas
Résistance d’entrée : env. 1 MOhm
Niveau Bas: 0 ... 0,7 V AC
Niveau Haut: 3 ... 30 V AC
PNP: active pour niveau haut
Résistance d’entrée : env. 100 kOhm
Niveau Bas: 0 ... 0,7 V AC
Niveau Haut: 4 ... 30 V AC
Borne à vis 3:
Entrée de remise à zéro
active pour front négatif
Entrée de contact / Open
Collector NPN
Niveau Bas: 0 ... 0,7 V DC
Niveau Haut: 3 ... 30 V DC
Durée d’impulsion min.: 50 ms
Résistance d’entrée : env. 2,2 MOhm
Borne à vis 4:
Verrouillage électrique de la touche de remise à zéro
Entrée de contact / Open Collector NPN
Niveau Bas: 0 ... 0,7 V DC
Niveau Haut: 3 ... 5 V DC
Résistance d’entrée: env. 2,2 MOhm
Entrée non activée: Touche de remise à zéro
verrouillée
Entrée en contact
avec GND: Touche de remise à zéro
déverrouillée
Borne à vis 5:
Commutation des plages de temps (Mode)
Entrée de contact / Open Collector NPN
Niveau Bas: 0 ... 0,7 V DC
Niveau Haut: 3 ... 5 V DC
Résistance d’entrée: env. 2,2 MOhm
Fonction: voir le Tableau 2
Nota:
Si la plage de temps est modifiée en cours de
fonctionnement, il faut remettre l’appareil à
zéro. Dans le cas contraire, la valeur du
comptage ne sera pas reproductible.
Borne à vis 6 :
Raccordement GND commun à toutes
les entrées
Borne à vis 7 :
(–) alimentation extérieure pour l’option
LCD rétroéclairé
Borne à vis 8 :
(+)
alimentation extérieure pour l’option LCD rétroéclairé
(24 V DC ±20 %, 50 mA)
Tableau 2
Caractéristiques des entrées, affectation des bornes et plages de temps réglables (exécution CC)
La plage de temps se règle par l’intermédiaire d’une entrée de commande (borne à vis 5).
Borne à vis N° 1 N° 2 N° 3 N° 4 N° 5 N° 6 N° 7 N° 8
Désignation
Modèle
INP A INP B Reset Reset Enable Plage de temps (Mode) GND BL
BL
+
E5224C0440
sans fonction
Entrée Timer Enable
NPN
Entrée de remise à
zéro NPN
Entrée de
verrouillage de la
touche de remise à
zéro NPN. Contact
avec GND, touche
libérée.
non activée
= 99999 h 59 m
contact avec
GND
= 99999,99 h
GND = 0 V DC
Rétroéclairage (–)
Rétroéclairage (+)
E5224C0450 NPN
non activée =
9999 h 59 m 59 s
contact avec
GND
=
9999999,9 s
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
français
MN05401006E 11
Borne à vis 1:
Entrée Timer Enable:
Mesure du temps tant que le
niveau de cette entrée est Haut.
Entrée optocoupleur : 10 ... 260 V AC/DC
découplage galvanique, actif
pour signal Haut
Niveau Bas : 0 ... 2 V AC/DC
Niveau Haut : 10 ... 260 V AC/DC
Résistance d’entrée : env. 160 kOhm
Borne à vis 2:
Commun AC/DC, raccordement commun pour les
entrées optocoupleur (borne à vis 1 et borne à vis 3).
Borne à vis 3:
Entrée de remise à zéro:
10 ... 260 V AC/DC découplage
galvanique
Durée d’impulsion min: 16 ms
Fréquence max. env. 30 Hz
Niveau Bas: 0 ... 2 V AC/DC
Niveau Haut : 10 ... 260 V AC/DC
Résistance d’entrée : env. 160 kOhm
Borne à vis
4:
Verrouillage électrique de la touche de remise à zéro
Entrée de contact / Open Collector NPN
Niveau Bas
: 0 ... 0,7 V DC
Niveau Haut
: 3 ... 5 V DC
Résistance d’entrée : env. 2,2 MOhm
Entrée non activée :
Touche de remise à zéro
verrouillée
Entrée en contact
avec GND : Touche de remise à zéro
déverrouillée
Borne à vis
5:
Commutation des plages de temps (Mode)
Entrée de contact / Open Collector NPN
Niveau Bas
: 0 ... 0,7 V DC
Niveau Haut
: 3 ... 5 V DC
Résistance d’entrée
: env. 2,2 MOhm
Fonction: voir Tableau 3
Nota:
Si la plage de temps est modifiée en cours de
fonctionnement, il faut remettre l’appareil à
zéro.
Borne à vis 6 :
Raccordement GND commun pour la borne 4
(entrée de verrouillage de la touche de remise à
zéro) et la borne 5 (commutation des plages de
temps).
Borne à vis 7 :
(–) alimentation extérieure pour l’option
LCD rétro-éclairé
Borne à vis 8 :
(+) alimentation extérieure pour l’option LCD
rétroéclairé
(24 V DC ±20 %, 50 mA)
Tableau 3
Caractéristiques des entrées, affectation des bornes et plages de temps réglables (exécution CA)
La plage de temps se règle par l’intermédiaire d’une entrée de commande (borne à vis 5).
Borne à vis N° 1 N° 2 N° 3 N° 4 N° 5 N° 6 N° 7 N° 8
Désignation
Modèle
INP A
CA/CC
Common
CA/CC
INP B
CA/CC
Reset Enable Plage de temps (Mode) GND BL
BL
+
E5224C0448
Entrée Timer Enable
CA/CC
Raccordement
commun pour INP A
et INP B
Entrée de remise à
zéro CA/CC
Entrée de verrouillage
de la touche de remise
à zéro NPN. Contact
avec GND, touche
libérée.
non activée =
99999 h 59 m
contact avec
GND =
99999,99 h
GND = 0 V DC
Rétroéclairage (–)
Rétroéclairage (+)
E5224C0458
non activée =
9999 h 59 m 59 s
contact avec
GND =
9999999,9 s
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
12 MN05401006E
Etendue de la livraison :
Compteur
Etrier de montage
Cadre avant pour fixation par vis,
Découpe d’encastrement 50 x 25 mm
Cadre avant pour fixation par étrier,
Découpe d’encastrement 50 x 25 mm
Joint
Instructions d’utilisation
Installation :
Exécutions DC :
Utiliser des fils blindés pour les entrées de mesure de
temps et de commande afin d’obtenir la résistance CEM
maximale.
Utilisation conforme :
Cet appareil ne peut être utilisé qu’en tant qu’appareil
encastré, à l’intérieur ! Ce produit trouve son
application dans les process industriels et les
commandes, dans le domaine des chaînes de
fabrication des industries du métal, du bois, des
matères plastiques, du papier, du verre, du textile, etc. Il
faut tenir compte du fait que les surtensions aux bornes
de l’appareil doivent être limitées aux valeurs de la
catégorie de surtension II. La catégorie de surtension II
est décrite dans la norme EN 61 010 Partie 1.
Cet appareil ne doit fonctionner que s’il a été encastré
dans les règles de l’art. Il ne peut être utilisé que
conformément au chapitre “Caractéristiques techniques
générales”.
Cet appareil ne doit pas être utilisé :
– dans des zones présentant des risques d’explosion,
– dans les domaines d’utilisation expressément cités
dans la norme EN 61 010.
Si cet appareil est mis en oeuvre pour la commande de
machines ou d’un process où, en cas de panne de
l’appareil, peuvent apparaître des risques de
dommages à la machine ou d’accidents pour les
opérateurs, il vous appartient de prendre les mesures
de sécurité correspondantes.
Nota :
Ce produit comporte une batterie au lithium.
Ne pas l’ouvrir de force, ne pas le jeter au feu.
Eviter des températures inférieures
à –20 °C et supérieures à 70 °C !
Exécutions AC :
Utiliser des fils blindés pour les entrées de mesure de
temps et de commande afin d’obtenir la résistance CEM
maximale.
Instructions de sécurité :
N’utiliser ces compteurs que
– de manière conforme à leur
destination
– s’ils sont techniquement en
parfait état
en respectant les instructions
d’utilisation et les instructions
générales de sécurité.
Tenez aussi compte de l’existence éventuelle de
réglementations de sécurité spécifiques à l’utilisateur ou
au pays, qu’il convient de respecter également.
!
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
deutsch
MN05401006E 13
Bedienungsanleitung
LCD-Betriebsstundenzähler
E5224C Serie
Die batteriebetriebenen LCD-Betriebsstundenzähler
E5224C Serie lassen sich in unterschiedlichste
Applikationen einsetzen. Typische Anwendungen sind
z.B.: Betriebszeit- und Lebensdauererfassung,
Durchlaufzeitmessung, Zeitüberwachung usw.
Die Ansteuerung erfolgt über potentialfreie Kontakte
oder Spannungsimpulse.
DC-Ausführungen:
Timer: INP A: ohne Funktion
INP B: Timer-Enable-Eingang
Allgemeine technische Daten:
Anzeige: LCD, 8–stellig, Ziffernhöhe 8 mm.
Anzeigebereich:
0 ... 99999999 mit Vornullenunterdrückung.
Genauigkeit: < 100 ppm
Überlauf: Bei Überschreiten des Anzeigebereichs
beginnt der Timer wieder bei 0, jedoch
ohne Vornullenunterdrückung und mit
Ansteuerung aller Dezimalpunkte
Tastatur: Resettaste elektrisch verriegelbar
Gehäuse: Schalttafelgehäuse 48 x 24 mm
nach DIN 43 700, RAL 7021
Schalttafelausschnitt:
22,2
+0,3
x 4
5+0,6
mm
Einbautiefe:
ca. 48 mm
Gewicht: ca. 50 g
Schutzart: IP65 frontseitig
AC-Ausführungen:
Timer: INP A: Timer-Enable-Eingang AC/DC
INP B: Rücksetzeingang AC/DC
Anschluss: Schraubklemme, RM 5.00, 8–polig
Nennquerschnitt: 4,0 mm
2
eindrahtig
2,5 mm
2
feindrahtig AWG 12
Anschlussdurchmesser:
0,4 ... 2,3 mm eindrahtig
AWG 28-12
EMV: Störabstrahlung EN55011 Klasse B
Störfestigkeit EN 61000-6-2
NSR (für AC-Typen):
EN 61010 Teil 1;Überspannungskategorie 2,
Verschmutzungsgrad 2
Spannungsversorgung:
fest eingebaute Lithium-Batterie
(ca. 8 Jahre bei 20 °C)
Arbeitstemperatur:
–10 ... +55 °C, rel. Luftfeuchte < 85 %,
nicht kondensierend
Betriebstemperatur:
–10 ... +60 °C
Lagertemperatur:
–20 ... +70 °C
Hintergrundbeleuchtung:
externe Spannungsversorgung
(24 V DC ±20 %, 50 mA)
Tabelle 1
Typenübersicht
Type Betriebsart Zeitbereich Eingänge
INP A INP B
E5224C0440 Timer 99999h 59 m/
99999.99 h
0 ... 0,7 V DC NPN
E5224C0448 10 ... 260 V AC/DC AC/DC 10 ... 260 V AC/DC AC/DC
E5224C0450 Timer 9999 h 59 m 59 s/
9999999.9 s
0 ... 0,7 V DC NPN
E5224C0458 10 ... 260 V AC/DC AC/DC 10 ... 260 V AC/DC AC/DC
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
14 MN05401006E
Schraubklemme 1: ohne Funktion
Schraubklemme 2:
Time-Enable-Eingang:
Zeitmessung, solange Eingang
aktiv geschaltet ist
NPN: aktiv bei Low-Pegel
Eingangswiderstand: ca. 1 MOhm
Low-Pegel: 0 ... 0,7 V DC
High-Pegel: 3 ... 30 V DC
PNP: aktiv bei High-Pegel
Eingangswiderstand: ca. 100 kOhm
Low-Pegel: 0 ... 0,7 V DC
High-Pegel: 4 ... 30 V DC
Schraubklemme 3:
Rücksetzeingang:
aktiv bei negativer Flanke
Kontakteingang/ Open Collector
NPN
Low-Pegel: 0 ... 0,7 V DC
High-Pegel: 3 ... 30 V DC
min. Impulsdauer: 50 ms
Eingangswiderstand: ca. 2,2 MOhm
Schraubklemme 4:
Elektrische Verriegelung der Rücksetztaste
Kontakteingang / Open Collector NPN
Low-Pegel: 0 ... 0,7 V DC
High-Pegel: 3 ... 5 V DC
Eingangswiderstand: ca. 2,2 MOhm
Eingang unbeschaltet: Rücksetztaste verriegelt
Eingang beschaltet
nach GND: Rücksetztaste freigeschaltet
Schraubklemme 5:
Umschaltung der Zeitbereiche (Mode)
Kontakteingang / Open Collector NPN
Low-Pegel: 0 ... 0,7 V DC
High-Pegel: 3 ... 5 V DC
Eingangswiderstand: ca. 2,2 MOhm
Funktion: siehe Tabelle 2
Hinweis:
Wenn Sie den Zeitbereich während des
Betriebes wechseln, müssen Sie einen Reset
durchführen.
Schraubklemme 6:
Gemeinsamer GND-Anschluss für alle Eingänge
Schraubklemme 7:
(–) externe Spannung bei Option LCD-Hinterleuchtung
Schraubklemme 8:
(+) externe Spannung bei Option LCD-Hinterleuchtung
(24 V DC ±20 %, 50 mA)
Tabelle 2
Eingangsspezifikationen, Anschlussbelegung und einstellbare Zeitbereiche (DC-Ausführung)
Über einen Steuereingang (Schraubklemme 5) wird der Zeitbereich eingestellt).
Schraubklemme Nr. 1 Nr. 2 Nr. 3 Nr. 4 Nr. 5 Nr. 6 Nr. 7 Nr. 8
Bezeichnung
Typ
INP A INP B Reset Reset
Enable
Zeitbereich (Mode) GND BL
BL
+
E5224C0440
ohne Funktion
Timer-Enable-Eingang
NPN
Rücksetzeingang NPN
Verriegelungseingang
für Rücksetztaste NPN.
Beschaltet nach GND,
Taste freigeschaltet.
unbeschaltet =
99999 h 59 m
beschaltet
nach GND
=
99999,99 h
GND = 0 V DC
Hintergrundbeleuchtung
(–)
Hintergrundbeleuchtung
(+)
E5224C0450 NPN
unbeschaltet =
9999 h 59 m 59 s
beschaltet
nach GND
=
9999999,9 s
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
MN05401006E 15
deutsch
Schraubklemme 1:
Timer-Enable-Eingang:
Zeitmessung solange High-Pegel
an diesem Eingang.
Optokoppler-Eingang 10 ... 260 V AC/DC
galvanisch entkoppelt,
aktiv bei High-Signal
Low-Pegel: 0 ... 2 V AC/V DC
High-Pegel: 10 ... 260 V AC/DC
Eingangswiderstand: ca. 160 kOhm
Schraubklemme 2:
Common AC/DC, gemeinsamer Anschluss für
Optokoppler-Eingänge (Schraubklemme 1 und
Schraubklemme 3).
Schraubklemme 3:
Rücksetzeingang:
10 ... 260 V AC/DC galvanisch
entkoppelt
min. Impulszeit: 16 ms
max. Frequenz: ca. 30 Hz
Low-Pegel: 0 ... 2 V AC/V DC
High-Pegel: 10 ... 260 V AC/DC
Eingangswiderstand: ca. 160 kOhm
Schraubklemme 4:
Elektrische Verriegelung der Rücksetztaste
Kontakteingang / Open Collector NPN
Low-Pegel: 0 ... 0,7 V DC
High-Pegel: 3 ... 5 V DC
Eingangswiderstand: ca. 2,2 MOhm
Eingang unbeschaltet:
Rücksetztaste verriegelt
Eingang beschaltet nach GND:
Rücksetztaste freigeschaltet
Schraubklemme 5:
Umschaltung der Zeitbereiche (Mode)
Kontakteingang/Open Collector NPN
Low-Pegel: 0 ... 0,7 V DC
High-Pegel: 3 ... 5 V DC
Eingangswiderstand: ca. 2,2 MOhm
Funktion: siehe Tabelle 3
Hinweis:
Wenn Sie den Zeitbereich während des
Betriebes wechseln, müssen Sie einen Reset
durchführen. Der Zählwert ist sonst nicht
reproduzierbar.
Schraubklemme 6:
Gemeinsamer GND-Anschluss für Schraubklemme 4
(Rücksetztaste-Verriegelungseingang) und
Schraubklemme 5 (Zeitbereichsumschaltung)
Schraubklemme 7:
(–)
externe Spannung bei Option LCD-Hinterleuchtung
Schraubklemme 8:
(+)
externe Spannung bei Option LCD-Hinterleuchtung
(24 V DC ±20 %, 50 mA)
Tabelle 3
Eingangsspezifikation, Anschlussbelegung und einstellbare Zeitbereiche (AC-Ausführungen)
Über einen Steuereingang (Schraubklemme 5) wird der Zeitbereich eingestellt).
Schraubklemme Nr. 1 Nr. 2 Nr. 3 Nr. 4 Nr. 5 Nr. 6 Nr. 7 Nr. 8
Bezeichnung
Typ
INP A
AC/DC
Common
AC/DC
INP B
AC/DC
Reset
Enable
Zeitbereich (Mode) GND BL
BL
+
E5224C0448
Timer-Enable-Eingang
AC/DC
Gemeinsamer Anschluss
für INP A und INP B
Rücksetzeingang AC/DC
Verriegelungseingang für
Rücksetztaste NPN.
Beschaltet nach GND
Taste freigeschaltet.
unbeschaltet =
99999 h 59 m
beschaltet
nach GND =
99999,99 h
GND = 0 V DC
Hintergrundbeleuchtung
(–)
Hintergrundbeleuchtung
(+)
E5224C0458
unbeschaltet =
9999 h 59 m 59 s
beschaltet
nach GND =
9999999,9 s
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
16 MN05401006E
Lieferumfang:
Digitalanzeige
Spannbügel
Frontrahmen für Schraubbefestigung,
Einbauquerschnitt 50 x 25 mm
Frontrahmen für Spannbügelbefestigung,
Einbauquerschnitt 50 x 25 mm
Dichtung
Bedienungsanleitung
Installationshinweise:
DC-Ausführungen:
Damit Sie die maximale EMV-Festigkeit erreichen,
müssen Sie für den Timer-Enable-Eingang und die
Steuereingänge geschirmte Leitungen verwenden.
Bestimmungsgemäßer Gebrauch:
Sie dürfen das Gerät nur als Einbaugerät einsetzen!
Der Anwendungsbereich des Produktes liegt in
industriellen Prozessen und Steuerungen. In den
Bereichen von Fertigungsstraßen der Metall-, Holz-,
Kunststoff-, Papier-, Glas- und Textilindustrie u.ä.
Beachten Sie, daß die Überspannungen, an denen das
Produkt an den Schraubklemmen ausgesetzt ist, auf
den Wert der Überspannungskategorie II begrenzt sein
müssen. Die Überspannungskategorie II ist in der EN
61 010 Teil 1 beschrieben.
Sie dürfen das Gerät nur im ordnungsgemäß
eingebauten Zustand betreiben. Sie dürfen das Gerät
nur entsprechend dem Kapitel “allgemeine technische
Daten” betreiben.
Sie dürfen dieses Gerät nicht
– in explosionsgefährdeten Bereichen,
– in den Einsatzbereichen, die in EN 61 010 T1
ausgeschlossen sind betreiben.
Wenn Sie das Gerät zur Überwachung von Maschinen
oder Ablaufprozessen einsetzen, bei denen infolge
eines Ausfalls oder einer Fehlbedienung des Gerätes
eine Beschädigung der Maschine oder ein Unfall des
Bedienungspersonals möglich ist, müssen Sie
entsprechende Sicherheitsvorkehrungen treffen.
Hinweis:
Dieses Produkt enthält eine Lithium-Batterie.
Nicht gewaltsam öffnen, nicht ins Feuer
werfen. Temperaturen unter –20 °C und über
70 °C vermeiden!
AC-Ausführungen:
Damit Sie die maximale EMV-Festigkeit erreichen,
müssen Sie für die Steuereingänge geschirmte
Leitungen verwenden.
Sicherheitshinweise:
Benutzen Sie diese Zähler nur
– bestimmungsgemäß
– in technisch einwandfreiem
Zustand
– unter Beachtung der Bedien-
ungsanleitung und den
allgemeinen
Sicherheitsbestimmungen.
Beachten Sie zudem, dass es länder- und anwender-
spezifische Sicherheitsbestimmungen geben kann, die
Sie beachten müssen.
!
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
MN05401006E 17
Connections/Conexiones/Schémas de branchement/Anschlussbilder:
max.5VDCmax. 30 V DC
(-) BL
(+) BL
n.c.
INP B
Reset
Mode
GND
24 V DC ±20 %, 50 mA
1
2
3
4
5
6
7
8
Reset
Enable
DC-Typ:
E5224C0440
E5224C0450
BL = backlight/iluminación posterior/rétroéclairage/Hinterleuchtung
max.5VDC
(-) BL
(+) BL
INP A
GND
1
2
4
5
6
7
8
Reset
Mode
Enable
INP B
VAC/VDC
Common
AC/DC
3
10 .. 260
10 .. 260
VAC/VDC
24 V DC ±20 %, 50 mA
AC-Typ:
E5224C0448
E5224C0458
Time ranges and display/Rangos de tiempo y
pantalla/Plages de temps et affichage/
Zeitbereiche und Anzeige des
Betriebsstundenzählers
99999 h 59 m
99999.99 h
9999 h 59 m 59 s
9999999.9 s
Time range/Rango de Display/Pantalla/
tiempo/Plage de Affichage/Anzeige
temps/Zeitbereiche
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
18 MN05401006E
48 [1.89]
max. 19.3 [0.76]
47.7 [1.88]
2.8 [0.11]
3.0 [0.12]
24 [0.94]
22 x 45 [0.87 x 1.77]
Dimensions in mm [in.]/Dimensiones/Dimensions/Abmessungen:
22.2 + 0.3
[0.87 + 0.01]
45.0 + 0.6 [1.77 + 0.02]
50 + 0.6 [1.97 + 0.02]
25 + 0.5
[0.98 + 0.02]
1 [0.04]
4 [0.16]
25 x 50
[0.98 x 1.97]
28 [1.10]
53 [2.09]
56 [2.20]
50 + 0.6 [1.97 + 0.02]
M3
1 [0.04]
4 [0.16]
40 [1.57]
32 [1.26]
25 x 50
[0.98 x 1.97]
25 + 0.5
[0.98 + 0.02]
32 + 0.1
[1.26 + 0.004]
1
Countersinking Af3, DIN 74/Avellanado, Af3, DIN 74/Fraisure Af3, DIN 74/Senkung Af3, DIN 74
1
Panel cut-out/Plantilla de
recorte del panel/
Découpe d’encastrement/
Schalttafelausschnitt :
Panel cut-out/Plantilla de recorte del panel/Découpe d’encastrement/Schalttafelausschnitt :
Panel cut-out/Plantilla de
recorte del panel/
Découpe d’encastrement/
Schalttafelausschnitt :
Frame dimensions in mm [in.]/Dimensiones del marco/Dimensions du cadre/Abmessungen
Einbaurahmen:
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
© 2007 Eaton Corporation
All Rights Reserved
Printed in USA
Publication No. MN05401006E/CPG
March 2007
Eaton Corporation
Electrical Group
1000 Cherrington Parkway
Moon Township, PA 15108
United States
877-ETN CARE (877-386-2273)
Eaton.com

Transcripción de documentos

english Operating Instructions LCD Hour Meter E5224C Series They are controlled by means of dry contacts or voltage pulses. español The E5224C Series are battery-powered LCD hour meters. Typical elapsed timer applications include run time, product life, cycle time, and time monitoring. Overview E5224C0440 E52240C448 E5224C0450 E5224C0458 Timer Timer 99999h 59 m/ 99999.99 h 9999 h 59 m 59 s/ 9999999.9 s Inputs INP A — 10 – 260V AC/DC — 10 – 260V AC/DC AC/DC AC/DC INP B 0 – 0.7V DC 10 – 260V AC/DC 0 – 0.7V DC 10 – 260V AC/DC NPN AC/DC NPN AC/DC français Operating mode Time range Table 1 DC models: Timer: INP A: INP B: AC/DC models: no function Timer-Enable-Input Timer: INP A: INP B: Timer-Enable-Input AC/DC reset input AC/DC Main technical features: Display: LCD, 8 decades, height of the figures 8 mm [0.31 in.] Display range: 0 – 99999999 with lead zero blanking. Error: Connection: Screw terminals, RM 5.00, 8 poles Rated cross-section: 4.0 mm2 solid wire 2.5 mm2 stranded wire AWG 12 Connection diameter: 0.4 – 2.3 mm2 solid wire AWG 28-12 < 100 ppm Overflow: In case of a display range overflow, the timer starts again from 0, but without removing the leading zeros and activating all decimal points. Reset key: Requires rear terminal jumper to enable. Housing: Panel mounting, 48 x 24 mm [1.89 x 0.94 in.] according to DIN 43 700, RAL 7021 Panel cut-out: 22.2 x 45 mm [0.87 x 1.77 in.] 22.5 x 45.6 mm [0.89 x 1.80 in.] max. Mounting depth: approximately 48 mm [1.89 in.] Weight: approximately 50 g [1.76 oz.] Front panel rating: IP65 EMC: Emissions per EN55011 Class B Susceptibility per EN 61000-6-2 Low Voltage Directive (for the AC/DC models): EN 61010 Part 1 ; overvoltage category 2, pollution level 2 Power supply: Non-replaceable lithium battery (lifetime approximately 8 years at 20°C [68°F]) Working temperature: -10 to +55°C [14 to 131°F], relative humidity < 85%, non-condensing Operating temperature: -10 to +60°C [14 to 140°F] Storage temperature: -20 to +70°C [-4 to 158°F] Backlighting: must be powered by an external elecrical source (24V ±20%, 50 mA) MN05401006E For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com 1 deutsch Model Input specifications, terminal assignment and adjustable time ranges (DC versions) The time range is set via a control input (screw terminal 5). open = 99999 h 59 m contact with GND = 99999.99 h open = 9999 h 59 m 59 s contact with GND = 9999999.9 s No. 6 No. 7 No. 8 GND BL BL – + Backlighting (+) NPN No. 5 Time range (Mode) Backlighting (–) NPN No. 4 Reset Enable GND = 0V DC No. 3 Reset Reset key enabled when connected to gnd. E5224C0450 no function Model E5224C0440 No. 2 INP B NPN reset input Designation No. 1 INP A Timer Enable Input Screw terminal Table 2 Screw terminal 1: no function Screw terminal 2: Timer Enable Input: time measurement as long as the input is active NPN: Input resistance: Low level: High level: PNP: Input resistance: Low-level: High-level: active for low level approximately 1 MOhm 0 – 0.7V DC 3 – 30V DC active for high level approximately 100 kOhm 0 – 0.7V DC 4 – 30V DC Screw terminal 4: Reset key enable Contact input / Open Low level: High level: Input resistance: Remark If the time range is changed during operation, the device must be reset. Screw terminal 6: Common GND connection for all inputs Screw terminal 7: (–) external power supply for the backlight option Screw terminal 3: Reset input: Low level: High level: Min. pulse duration: Input resistance: Screw terminal 5: Time range switching (Mode) contact input / Open Collector NPN Low level: 0 – 0.7V DC High level: 3 – 5V DC Input resistance: approximately. 2.2 MOhm Function: see table 2 active for negative edge contact input / Open Collector NPN 0 – 0.7V DC 3 – 30V DC 50 ms approximately 2.2 MOhm Screw terminal 8: (+) external power supply for the backlight option (24V DC ±20%, 50 mA) Collector NPN 0 – 0.7V DC 3 – 5V DC approximately. 2.2 MOhm Input not active: Reset key disabled Input active (contact with GND): Reset key enabled 2 MN05401006E For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com not active = 99999 h 59 m contact with GND = 99999.99 h contact with not active = GND = 9999 h 59 m 59 s 9999999.9 s No. 6 GND No. 7 BL – No. 8 BL + Backlighting (+) No. 5 Time range (Mode) Backlighting (–) No. 4 Reset Enable GND = 0V DC E5224C0458 No. 3 INP B AC/DC NPN reset key locking input, Contact with GND. key free. Model E5224C0448 Common connection for INP A and INP B No. 1 No. 2 Designation INP A Common AC/DC AC/DC Timer Enable Input AC/DC Screw terminal reset input AC/DC The time range is set via a control input (screw terminal 5). Table 3 Screw terminal 1: Timer Enable Input: Optocoupler input Low level: High level: Input resistance: time measurement as long as the level at this input is high. 10 – 260V AC/DC galvanic isolation, active for High signal 0 – 2V AC/DC 10 – 260V AC/DC approximately 160 kOhm Screw terminal 2: Common AC/DC, common connection for the optocoupler inputs (screw terminals 1 and 3) Screw terminal 3: Reset input: Min. pulse duration: Max. frequency: Low level: High level: Input resistance: 10 – 260V AC/DC galvanic isolation 16 ms approximately 30 Hz 0 – 2V AC/DC 10 – 260V AC/DC approximately 160 kOhm Screw terminal 5: Time range switching (Mode) Contact input / Open Collector NPN Low level: 0 – 0.7V DC High level: 3 – 5V DC Input resistance: approximately 2.2 MOhm Function: see table 3 Remark: If the time range is changed during operation, the device must be reset. Screw terminal 6: Common GND connection for screw terminal 4 (reset key locking input) and screw terminal 5 (time range switching). Screw terminal 7: (–) external power supply for the backlight option Screw terminal 8: (+) external power supply for the backlight option (24V DC ±20%, 50 mA) Screw terminal 4: Reset key enable Contact input / Open Collector NPN Low level: 0 – 0.7V DC High level: 3 – 5V DC Input resistance: approximately 2.2 MOhm Input not active: Reset key disabled Input in contact with GND: Reset key enabled MN05401006E For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com 3 english Input specification, terminal assignment and adjustable time ranges (AC/DC versions) Contents: Timer Clamp Front frame for screw mounting, Panel cut-out 50 x 25 mm [1.97 x 0.98 in.] Front frame for clamp mounting, Panel cut-out 50 x 25 mm [1.97 x 0.98 in.] Seal Operating instructions Note: This product includes a lithium battery. Do not open it by force, do not throw it in the fire. Avoid temperatures below -20°C [-4°F] and above 70°C [158°F]! Installation: DC versions: Use shielded wires for the counting and control inputs to obtain the maximum EMC resistance. AC/DC versions: Use shielded wires for the counting and control inputs to obtain the maximum EMC resistance. Use according to the intended purpose: Safety instructions: This device may only be used inside as a panelmounted device! Applications of this product may be found in industrial processes and controls in the branch of the manufacturing lines for the metal, wood, plastics, paper, glass, textile, etc., processing industries. It must be considered that the overvoltages at the terminals of the device must be limited to the values of overvoltage category II. Overvoltage category II is described in the standard EN 61 010 Part 1. This device shall only operate when it has been correctly mounted in a panel. It may only be used in accordance with the chapter “Main technical features”. ! Only use these counters – according to their intended purpose – if their technical condition is perfect – adhering to the operating instructions and the general safety instructions. Also take into account the fact that there may exist user or country-specific safety regulations, which must also be followed. This device shall not be used: – in areas with risks of explosion, – in the branches expressly quoted in the standard EN 61 010. If this device is used to monitor machines or a process in which, in case of a failure of the device, there might be risks of damaging the machine or causing accidents to the operators, it is up to you to take appropriate safety measures. 4 MN05401006E For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com Instrucciones de operación Contadores con pantalla LCD Serie E5224C Se controlan por medio de contactos secos o por impulsos de voltaje. español Los contadores con pantalla LCD de la serie E5224C funcionan a baterías. Las aplicaciones típicas del contador de tiempo transcurrido incluyen tiempo de ejecución, vida útil del producto, tiempo de ciclo y control de tiempo. Información general Modelo Modo de Rango de tiempo funcionamiento E5224C0440 Temporizador E52240C448 E5224C0450 Temporizador E5224C0458 Entradas ENT A 99999h 59 m/ — 99999,99 h 10 – 260 V CA/CC 9999 h 59 m 59 seg./ — 9999999,9 seg. 10 – 260 V CA/CC CA/CC CA/CC ENT B 0 – 0,7 V CC 10 – 260 V CA/CC 0 – 0,7 V CC 10 – 260 V CA/CC NPN CA/CC NPN CA/CC Tabla 1 Modelos CC: Temporizador: Modelos CA/CC: ENT A: ENT B: sin función Entrada de habilitación de temporizador Temporizador: ENT A: ENT B: Características técnicas principales: Entrada de habilitación de temporizador CA/CC Entrada de restablecimiento CA/CC Conexión: Pantalla: Bornes de tornillo, RM 5,00, 8 polos Sección transversal clasificada: 4,0 mm2 cable simple 2,5 mm2 cable trenzado AWG 12 LCD, 8 decimales, altura de cifras 8 mm [0,31 pulg.] Rango de pantalla: 0 – 99999999 con supresión de cero inicial. Error: Diámetro de la conexión: < 100 ppm Exceso: En caso de exceso del rango de pantalla, el temporizador vuelve a comenzar desde 0, pero sin quitar los ceros iniciales y activando los puntos decimales. Tecla de restablecimiento: Para habilitar se requiere el puente de borne posterior. Cubierta: Montaje en panel, 48 x 24 mm [1,89 x 0,94 pulg.] según DIN 43 700, RAL 7021 Plantilla de recorte del panel: 22,2 x 45 mm [0,87 x 1,77 pulg.] 22,5 x 45,6 mm [0,89 x 1,80 pulg.] máx. Profundidad de montaje: 48 mm aproximadamente [1,89 pulg.] Peso: 50 g aproximadamente [1,76 oz.] Clasificación del panel delantero: IP65 EMC: 0,4 – 2,3 mm2 cable simple AWG28-12 Emisiones por EN55011 Clase B susceptibilidad por EN 61000-6-2 Directiva de bajo voltaje (para los modelos CA/CC): EN 61010 Parte 1; categoría de sobrevoltaje 2, nivel de contaminación 2 Suministro de energía: Batería de litio no reemplazable (vida útil aproximada de 8 años a 20º C [68° F]) Temperatura de trabajo: -10 a +55° C [14 a 131° F], humedad relativa < 85%, sin condensación Temperatura de funcionamiento: -10 a +60° C [14 a 140° F] Temperatura de almacenamiento: -20 a +70° C [-4 a 158° F] Iluminación posterior: Se debe alimentar por medio de una fuente eléctrica externa (24 V ± 20%, 50 mA) MN05401006E For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com 5 Especificaciones de entrada, asignación de borne y rangos de tiempo ajustables (versiones de CC) Modelo E5224C0440 NPN Entrada de restablecimiento NPN Entrada de la habilitación del temporizador NPN Sin función E5224C0450 Nº 3 Restablecimiento Nº 4 Habilitación del restablecimiento Nº 5 Rango de tiempo (modo) Abierto = Contacto a 99999 h tierra = 59 m 99999,99 h Abierto = Contacto a 9999 h tierra = 59 m 9999999,9 59 seg. seg. Nº 6 Nº 7 Nº 8 CONEXIÓN BL BL A TIERRA – + Iluminación posterior (+) Nº 2 ENT B Iluminación posterior (–) Nº 1 Designación ENT A CONEXIÓN A TIERRA = 0 V CC Borne de tornillo La tecla de restablecimiento se habilita cuando está conectada a tierra. Se configura el rango de tiempo por medio de una entrada de control (borne de tornillo 5). Tabla 2 Borne de tornillo 1: Sin función Borne de tornillo 2: Entrada de habilitación del temporizador: Medición del tiempo mientras la entrada esté activa NPN: Resistencia de entrada: Nivel bajo: Nivel alto: PNP: Resistencia de entrada: Nivel bajo: Nivel alto: Activo para nivel bajo Aproximadamente 1 MOhm 0 – 0,7 V CC 3 – 30 V CC Activo para nivel alto Aproximadamente 100 kOhm 0 – 0,7 V CC 4 – 30 V CC Borne de tornillo 3: Entrada de restablecimiento: Activo para entrada de contacto de borde negativo/ NPN de toma de corriente abierta Nivel bajo: 0 – 0,7 V CC Nivel alto: 3 – 30 V CC Duración de impulso mín: 50 ms Resistencia de entrada: Aproximadamente 2,2 MOhm Borne de tornillo 5: Conmutación de rango de tiempo (modo) Entrada de contacto/NPN de toma de corriente abierta Nivel bajo: 0 – 0,7 V CC Nivel alto: 3 – 5 V CC Resistencia de entrada: Aproximadamente 2,2 MOhm Función: Consulte la Tabla 2 Observación Si se cambia el rango de tiempo durante la operación, se debe restablecer el dispositivo. Borne de tornillo 6: Conexión a tierra comúnpara todas las entradas Borne de tornillo 7: (–) suministro de energía para la opción de iluminación posterior Borne de tornillo 8: (+) suministro de energía para la opción de iluminación posterior (24 V CC ±20%, 50 mA) Borne de tornillo 4: Habilitación de tecla de restablecimiento Entrada de contacto/NPN de toma de corriente abierta Nivel bajo: 0 – 0,7 V CC Nivel alto: 3 – 5 V CC Resistencia de entrada: Aproximadamente 2,2 MOhm Entrada inactiva: Tecla de restablecimiento deshabilitada Entrada activa (contacto a tierra): Tecla de restablecimiento habilitada 6 MN05401006E For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com Especificaciones de entrada, asignación de borne y rangos de tiempo ajustables (versiones CA/CC) Se configura el rango de tiempo por medio de una entrada de control (borne de tornillo 5). Contacto a Inactiva = tierra = 9999 h 59 m 59 s 9999999,9 seg. español Contacto a tierra = 99999,99 h Iluminación posterior (+) Inactiva = 99999 h 59 m Nº 6 Nº 7 Nº 8 CONEXIÓN BL BL A TIERRA – + Iluminación posterior (–) Nº 5 Rango de tiempo (modo) CONEXIÓN A TIERRA = 0 V CC Entrada de bloqueo de tecla de restablecimiento NPN, contacto a tierra. Llave libre. E5224C0458 Entrada de restablecimiento CA/CC Modelo E5224C0448 Conexión común para ENT A y ENT B Nº 1 Nº 2 Nº 3 Nº 4 Designación ENT A CA/CC ENT B Habilitación del CA/CC común CA/CC restablecimiento Entrada de habilitación del temporizador CA/CC Borne de tornillo Tabla 3 Borne de tornillo 1: Entrada de habilitación del temporizador: Medición del tiempo mientras el nivel en esta entrada sea alto. Entrada de optoacoplador: 10 – 260 V CA/CC Aislamiento galvánico, activo para señal alta Nivel bajo: 0 – 2 V CA/CC Nivel alto: 10 – 260 V CA/CC Resistencia de entrada: Aproximadamente 160 kOhm Borne de tornillo 2: CA/CC común, conexión común para entradas de optoacoplador (bornes de tornillo 1 y 3) Borne de tornillo 3: Entrada de restablecimiento: 10 – 260 V CA/CC aislamiento galvánico Duración de impulso mín: 16 ms Frecuencia máx: Aproximadamente 30 Hz Nivel bajo: 0 – 2 V CA/CC Nivel alto: 10 – 260 V CA/CC Resistencia de entrada: Aproximadamente 160 kOhm Borne de tornillo 4: Habilitación de tecla de restablecimiento Entrada de contacto/NPN de toma de corriente abierta Nivel bajo: 0 – 0,7 V CC Nivel alto: 3 – 5 V CC Resistencia de entrada: Aproximadamente 2,2 MOhm Entrada inactiva: Tecla de restablecimiento deshabilitada Entrada en contacto a tierra: Tecla de restablecimiento habilitada Borne de tornillo 5: Conmutación de rango de tiempo (modo) entrada de contacto/NPN de toma de corriente abierta Nivel bajo: 0 – 0,7 V CC Nivel alto: 3 – 5 V CC Resistencia de entrada: Aproximadamente 2.2 MOhm Función: Consulte la Tabla 3 Observación: Si se cambia el rango de tiempo durante la operación,se debe restablecer el dispositivo. Borne de tornillo 6: Conexión a tierra común para borne de tornillo 4 (tecla de restablecimiento entrada de bloqueo) y borne de tornillo 5 (conmutación del rango de tiempo). Borne de tornillo 7: (–) suministro de energía externo para la opción de iluminación posterior Borne de tornillo 8: (+) suministro de energía externo para la opción de iluminación posterior (24 V CC ±20%, 50 mA) MN05401006E For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com 7 Contenido: Temporizador Abrazadera de sujeción Bastidor delantero para el montaje con tornillos, plantilla de recorte del panel 50 x 25 mm [1,97 x 0,98 pulg.] Bastidor delantero para montaje de abrazadera de sujeción, plantilla de recorte del panel de 50 x 25 mm [1,97 x 0,98 pulg.] Sello Instrucciones de operación Nota: Este producto cuenta con una batería de litio. No lo abra a la fuerza, no lo lance a las llamas. ¡Evite temperaturas menores que -20º C [-4° F] y mayores que 70° C [158° F]! Instalación: Versiones de CC: Use cables blindados para el conteo y las entradas de control, para así obtener el máximo de resistencia EMC. Versiones de CA/CC: Use cables blindados para el conteo y las entradas de control, para así obtener el máximo de resistencia EMC. Úselo de acuerdo al propósito para el que fue creado: Instrucciones de seguridad: ¡Este dispositivo puede usarse sólo en el interior como un dispositivo montado en el panel! Las aplicaciones de este producto se pueden encontrar en procesos industriales y controles en la derivación de líneas de fabricación para procesos industriales del metal, madera, plástico, papel, vidrio, textil, etc. Se debe tener en cuenta que los sobrevoltajes en los bornes del dispositivo se deben limitar a los valores de la categoría de sobrevoltaje II. La categoría de sobrevoltaje II se describe en la norma EN 61 010 Parte 1. Este dispositivo sólo funcionará cuando se haya montado correctamente en un panel. Sólo se puede usar de acuerdo con el capítulo “Características técnicas principales”. ! Sólo use estos contadores – de acuerdo al propósito para el que fueron creados; – si su condición técnica es perfecta; – respetando las instrucciones de operación y las instrucciones generales de seguridad. También tenga en cuenta el hecho de que podrían existir normas de seguridad específicas para el país o usuario, que también se deben cumplir. Este dispositivo no se debe usar: – en áreas con riesgo de explosión, – en las derivaciones expresamente citadas en la norma EN 61 010. Si el dispositivo se usa para controlar máquinas o procesos en los que, en caso de falla del dispositivo, podría haber riesgos de dañar la máquina o causar accidentes a los operadores, es su deber tomar las medidas de seguridad apropiadas. 8 MN05401006E For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com Instructions d’utilisation Compteurs horaires à affichage LCD E5224C Série Les compteurs horaires à affichage LCD E5224C Série sont alimentés par batterie. Ils trouvent leur place dans les applications les plus variées, par exemple: mesure du temps de fonctionnement et de la durée de vie, mesure du temps de passage, surveillance du temps, etc. Ils sont commandés par des contacts secs ou des impulsions de tension. Modèles Mode opératoire Plage de temps E5224C0440 E5224C0448 E5224C0450 E5224C0458 Compteur horaire 99999h 59 m/ 99999.99 h Compteur horaire 9999 h 59 m 59 s/ 9999999.9 s Entrées de comptage INP A — 10 ... 260 V AC/DC AC/DC — 10 ... 260 V AC/DC AC/DC INP B 0 ... 0,7 V DC 10 ... 260 V AC/DC 0 ... 0,7 V DC 10 ... 260 V AC/DC NPN AC/DC NPN AC/DC français Modèle Tableau 1 Modes opératoires DC : Modes opératoires AC : Compteur: INP A: INP B: Compteur: INP A: INP B: sans fonction entrée Timer Enable entrée Timer Enable AC/DC entrée de remise à zéro AC/DC Caractéristiques techniques générales : Affichage : LCD, 8 décades, hauteur des chiffres 8 mm. Plage d’affichage : 0 ... 99999999 avec suppression des zéros de tête. Précision: < 100 ppm Dépassement : En cas de dépassement de la plage d’affichage, le compteur repart de 0, mais sans suppression des zéros de tête et en activant tous les points décimaux. Raccordements : Bornes à vis, RM 5.00, 8 bornes Section nominale : 4,0 mm2 monoconducteur 2,5 mm2 fils fins AWG 12 Diamètre de raccordement : 0,4 ... 2,3 mm monoconducteur AWG 28-12 CEM : Emissions parasites EN55011 Classe B Résistance aux parasites EN 61000-6-2 Directive Basse Tension (pour les modèles AC) : EN 61010 Partie 1;catégorie de surtension 2, degré de contamination 2 Touches: Verrouillage électrique de la touche de RAZ Boîtier : Montage dans tableau, 48 x 24 mm suivant DIN 43 700, RAL 7021 Découpe d’encastrement : 22,2+0,3 x 45+0,6 mm Profondeur de montage : env. 48 mm Poids : env. 50 g Alimentation : Batterie au lithium non remplaçable (durée de vie env. 8 ans à 20°C) Température de travail : –10 ... +55 °C, humidité relative < 85%, sans condensation Température de fonctionnement : –10 ... +60 °C Température de stockage : –20 .. +70°C Indice de protection : IP65 sur la face avant Rétroéclairage: doit être alimenté par une source électrique extérieure (24 V ±20%, 50 mA) MN05401006E For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com 9 Caractéristiques des entrées, affectation des bornes et plages de temps réglables (exécution CC) N° 5 Plage de temps (Mode) non activée = 99999 h 59 m contact avec GND = 99999,99 h non activée = 9999 h 59 m 59 s contact avec GND = 9999999,9 s N° 6 N° 7 N° 8 GND BL BL – + Rétroéclairage (+) NPN N° 4 Reset Enable Rétroéclairage (–) NPN N° 3 Reset GND = 0 V DC E5224C0450 sans fonction Modèle E5224C0440 N° 2 INP B Entrée de verrouillage de la touche de remise à zéro NPN. Contact avec GND, touche libérée. N° 1 Désignation INP A Entrée Timer Enable Borne à vis Entrée de remise à zéro NPN La plage de temps se règle par l’intermédiaire d’une entrée de commande (borne à vis 5). Tableau 2 Borne à vis 1: sans fonction Borne à vis 2: Entrée Timer Enable: Mesure du temps tant que l’entrée est active NPN: active pour niveau bas Résistance d’entrée : env. 1 MOhm Niveau Bas: 0 ... 0,7 V AC Niveau Haut: 3 ... 30 V AC PNP: active pour niveau haut Résistance d’entrée : env. 100 kOhm Niveau Bas: 0 ... 0,7 V AC Niveau Haut: 4 ... 30 V AC Borne à vis 3: Entrée de remise à zéro active pour front négatif Entrée de contact / Open Collector NPN Niveau Bas: 0 ... 0,7 V DC Niveau Haut: 3 ... 30 V DC Durée d’impulsion min.: 50 ms Résistance d’entrée : env. 2,2 MOhm Borne à vis 5: Commutation des plages de temps (Mode) Entrée de contact / Open Collector NPN Niveau Bas: 0 ... 0,7 V DC Niveau Haut: 3 ... 5 V DC Résistance d’entrée: env. 2,2 MOhm Fonction: voir le Tableau 2 Nota: Si la plage de temps est modifiée en cours de fonctionnement, il faut remettre l’appareil à zéro. Dans le cas contraire, la valeur du comptage ne sera pas reproductible. Borne à vis 6 : Raccordement GND commun à toutes les entrées Borne à vis 7 : (–) alimentation extérieure pour l’option LCD rétroéclairé Borne à vis 8 : (+) alimentation extérieure pour l’option LCD rétroéclairé (24 V DC ±20 %, 50 mA) Borne à vis 4: Verrouillage électrique de la touche de remise à zéro Entrée de contact / Open Collector NPN Niveau Bas: 0 ... 0,7 V DC Niveau Haut: 3 ... 5 V DC Résistance d’entrée: env. 2,2 MOhm Entrée non activée: Touche de remise à zéro verrouillée Entrée en contact avec GND: Touche de remise à zéro déverrouillée 10 MN05401006E For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com Caractéristiques des entrées, affectation des bornes et plages de temps réglables (exécution CA) non activée = 99999 h 59 m contact avec GND = 99999,99 h N° 7 BL – N° 8 BL + français contact avec non activée = GND = 9999 h 59 m 59 s 9999999,9 s N° 6 GND Rétroéclairage (+) N° 5 Plage de temps (Mode) GND = 0 V DC Entrée de verrouillage de la touche de remise à zéro NPN. Contact avec GND, touche libérée. E5224C0458 N° 3 N° 4 INP B Reset Enable CA/CC Entrée de remise à zéro CA/CC Modèle E5224C0448 N° 2 Common CA/CC Raccordement commun pour INP A et INP B N° 1 Désignation INP A CA/CC Entrée Timer Enable CA/CC Borne à vis Rétroéclairage (–) La plage de temps se règle par l’intermédiaire d’une entrée de commande (borne à vis 5). Tableau 3 Borne à vis 1: Entrée Timer Enable: Mesure du temps tant que le niveau de cette entrée est Haut. Entrée optocoupleur : 10 ... 260 V AC/DC découplage galvanique, actif pour signal Haut Niveau Bas : 0 ... 2 V AC/DC Niveau Haut : 10 ... 260 V AC/DC Résistance d’entrée : env. 160 kOhm Borne à vis 2: Commun AC/DC, raccordement commun pour les entrées optocoupleur (borne à vis 1 et borne à vis 3). Borne à vis 3: Entrée de remise à zéro: 10 ... 260 V AC/DC découplage galvanique Durée d’impulsion min: 16 ms Fréquence max. env. 30 Hz Niveau Bas: 0 ... 2 V AC/DC Niveau Haut : 10 ... 260 V AC/DC Résistance d’entrée : env. 160 kOhm Borne à vis 4: Verrouillage électrique de la touche de remise à zéro Entrée de contact / Open Collector NPN Niveau Bas: 0 ... 0,7 V DC Niveau Haut : 3 ... 5 V DC Résistance d’entrée : env. 2,2 MOhm Entrée non activée : Touche de remise à zéro verrouillée Entrée en contact avec GND : Touche de remise à zéro déverrouillée Borne à vis 5: Commutation des plages de temps (Mode) Entrée de contact / Open Collector NPN 0 ... 0,7 V DC Niveau Bas : Niveau Haut : 3 ... 5 V DC Résistance d’entrée: env. 2,2 MOhm Fonction: voir Tableau 3 Nota: Si la plage de temps est modifiée en cours de fonctionnement, il faut remettre l’appareil à zéro. Borne à vis 6 : Raccordement GND commun pour la borne 4 (entrée de verrouillage de la touche de remise à zéro) et la borne 5 (commutation des plages de temps). Borne à vis 7 : (–) alimentation extérieure pour l’option LCD rétro-éclairé Borne à vis 8 : (+) alimentation extérieure pour l’option LCD rétroéclairé (24 V DC ±20 %, 50 mA) MN05401006E For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com 11 Etendue de la livraison : Compteur Etrier de montage Cadre avant pour fixation par vis, Découpe d’encastrement 50 x 25 mm Cadre avant pour fixation par étrier, Découpe d’encastrement 50 x 25 mm Joint Instructions d’utilisation Nota : Ce produit comporte une batterie au lithium. Ne pas l’ouvrir de force, ne pas le jeter au feu. Eviter des températures inférieures à –20 °C et supérieures à 70 °C ! Installation : Exécutions DC : Utiliser des fils blindés pour les entrées de mesure de temps et de commande afin d’obtenir la résistance CEM maximale. Exécutions AC : Utiliser des fils blindés pour les entrées de mesure de temps et de commande afin d’obtenir la résistance CEM maximale. Utilisation conforme : Instructions de sécurité : Cet appareil ne peut être utilisé qu’en tant qu’appareil encastré, à l’intérieur ! Ce produit trouve son application dans les process industriels et les commandes, dans le domaine des chaînes de fabrication des industries du métal, du bois, des matères plastiques, du papier, du verre, du textile, etc. Il faut tenir compte du fait que les surtensions aux bornes de l’appareil doivent être limitées aux valeurs de la catégorie de surtension II. La catégorie de surtension II est décrite dans la norme EN 61 010 Partie 1. Cet appareil ne doit fonctionner que s’il a été encastré dans les règles de l’art. Il ne peut être utilisé que conformément au chapitre “Caractéristiques techniques générales”. ! N’utiliser ces compteurs que – de manière conforme à leur destination – s’ils sont techniquement en parfait état – en respectant les instructions d’utilisation et les instructions générales de sécurité. Tenez aussi compte de l’existence éventuelle de réglementations de sécurité spécifiques à l’utilisateur ou au pays, qu’il convient de respecter également. Cet appareil ne doit pas être utilisé : – dans des zones présentant des risques d’explosion, – dans les domaines d’utilisation expressément cités dans la norme EN 61 010. Si cet appareil est mis en oeuvre pour la commande de machines ou d’un process où, en cas de panne de l’appareil, peuvent apparaître des risques de dommages à la machine ou d’accidents pour les opérateurs, il vous appartient de prendre les mesures de sécurité correspondantes. 12 MN05401006E For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com Bedienungsanleitung LCD-Betriebsstundenzähler E5224C Serie Die batteriebetriebenen LCD-Betriebsstundenzähler E5224C Serie lassen sich in unterschiedlichste Applikationen einsetzen. Typische Anwendungen sind z.B.: Betriebszeit- und Lebensdauererfassung, Durchlaufzeitmessung, Zeitüberwachung usw. Die Ansteuerung erfolgt über potentialfreie Kontakte oder Spannungsimpulse. Typenübersicht Type Betriebsart Zeitbereich E5224C0440 E5224C0448 E5224C0450 E5224C0458 Timer 99999h 59 m/ 99999.99 h Timer 9999 h 59 m 59 s/ 9999999.9 s Eingänge INP A — 10 ... 260 V AC/DC AC/DC — 10 ... 260 V AC/DC AC/DC INP B 0 ... 0,7 V DC 10 ... 260 V AC/DC 0 ... 0,7 V DC 10 ... 260 V AC/DC NPN AC/DC NPN AC/DC Tabelle 1 DC-Ausführungen: AC-Ausführungen: Timer: Timer: ohne Funktion Timer-Enable-Eingang INP A: INP B: Timer-Enable-Eingang AC/DC Rücksetzeingang AC/DC deutsch INP A: INP B: Allgemeine technische Daten: Anzeige: LCD, 8–stellig, Ziffernhöhe 8 mm. Anzeigebereich: 0 ... 99999999 mit Vornullenunterdrückung. Anschluss: Schraubklemme, RM 5.00, 8–polig Nennquerschnitt: 4,0 mm2 eindrahtig 2,5 mm2 feindrahtig AWG 12 Anschlussdurchmesser: 0,4 ... 2,3 mm eindrahtig AWG 28-12 Genauigkeit: < 100 ppm Überlauf: Bei Überschreiten des Anzeigebereichs beginnt der Timer wieder bei 0, jedoch ohne Vornullenunterdrückung und mit Ansteuerung aller Dezimalpunkte EMV: Tastatur: NSR (für AC-Typen): EN 61010 Teil 1;Überspannungskategorie 2, Verschmutzungsgrad 2 Resettaste elektrisch verriegelbar Gehäuse: Schalttafelgehäuse 48 x 24 mm nach DIN 43 700, RAL 7021 Schalttafelausschnitt: 22,2+0,3 x 45+0,6 mm Einbautiefe: ca. 48 mm Gewicht: ca. 50 g Schutzart: IP65 frontseitig Störabstrahlung EN55011 Klasse B Störfestigkeit EN 61000-6-2 Spannungsversorgung: fest eingebaute Lithium-Batterie (ca. 8 Jahre bei 20 °C) Arbeitstemperatur: –10 ... +55 °C, rel. Luftfeuchte < 85 %, nicht kondensierend Betriebstemperatur: –10 ... +60 °C Lagertemperatur: –20 ... +70 °C Hintergrundbeleuchtung: externe Spannungsversorgung (24 V DC ±20 %, 50 mA) MN05401006E For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com 13 Eingangsspezifikationen, Anschlussbelegung und einstellbare Zeitbereiche (DC-Ausführung) unbeschaltet = 99999 h 59 m beschaltet nach GND = 99999,99 h unbeschaltet = 9999 h 59 m 59 s beschaltet nach GND = 9999999,9 s Nr. 6 GND Nr. 7 BL – Nr. 8 BL + Hintergrundbeleuchtung (+) Nr. 5 Zeitbereich (Mode) Hintergrundbeleuchtung (–) NPN Nr. 4 Reset Enable GND = 0 V DC NPN Nr. 3 Reset Verriegelungseingang für Rücksetztaste NPN. Beschaltet nach GND, Taste freigeschaltet. E5224C0450 ohne Funktion Typ E5224C0440 Nr. 2 INP B Timer-Enable-Eingang Schraubklemme Nr. 1 Bezeichnung INP A Rücksetzeingang NPN Über einen Steuereingang (Schraubklemme 5) wird der Zeitbereich eingestellt). Tabelle 2 Schraubklemme 1: ohne Funktion Schraubklemme 2: Time-Enable-Eingang: Zeitmessung, solange Eingang aktiv geschaltet ist NPN: Eingangswiderstand: Low-Pegel: High-Pegel: PNP: Eingangswiderstand: Low-Pegel: High-Pegel: aktiv bei Low-Pegel ca. 1 MOhm 0 ... 0,7 V DC 3 ... 30 V DC aktiv bei High-Pegel ca. 100 kOhm 0 ... 0,7 V DC 4 ... 30 V DC Schraubklemme 3: Rücksetzeingang: aktiv bei negativer Flanke Kontakteingang/ Open Collector NPN Low-Pegel: 0 ... 0,7 V DC High-Pegel: 3 ... 30 V DC min. Impulsdauer: 50 ms Eingangswiderstand: ca. 2,2 MOhm Schraubklemme 5: Umschaltung der Zeitbereiche (Mode) Kontakteingang / Open Collector NPN Low-Pegel: 0 ... 0,7 V DC High-Pegel: 3 ... 5 V DC Eingangswiderstand: ca. 2,2 MOhm Funktion: siehe Tabelle 2 Hinweis: Wenn Sie den Zeitbereich während des Betriebes wechseln, müssen Sie einen Reset durchführen. Schraubklemme 6: Gemeinsamer GND-Anschluss für alle Eingänge Schraubklemme 7: (–) externe Spannung bei Option LCD-Hinterleuchtung Schraubklemme 8: (+) externe Spannung bei Option LCD-Hinterleuchtung (24 V DC ±20 %, 50 mA) Schraubklemme 4: Elektrische Verriegelung der Rücksetztaste Kontakteingang / Open Collector NPN Low-Pegel: 0 ... 0,7 V DC High-Pegel: 3 ... 5 V DC Eingangswiderstand: ca. 2,2 MOhm Eingang unbeschaltet: Rücksetztaste verriegelt Eingang beschaltet nach GND: Rücksetztaste freigeschaltet 14 MN05401006E For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com Eingangsspezifikation, Anschlussbelegung und einstellbare Zeitbereiche (AC-Ausführungen) Nr. 4 Reset Enable Nr. 5 Zeitbereich (Mode) Nr. 6 GND Nr. 7 BL – Nr. 8 BL + Hintergrundbeleuchtung (+) Schraubklemme Nr. 1 Nr. 2 Nr. 3 Bezeichnung INP A Common INP B AC/DC AC/DC AC/DC Hintergrundbeleuchtung (–) Über einen Steuereingang (Schraubklemme 5) wird der Zeitbereich eingestellt). unbeschaltet = 99999 h 59 m beschaltet nach GND = 99999,99 h beschaltet unbeschaltet = nach GND = 9999 h 59 m 59 s 9999999,9 s GND = 0 V DC Verriegelungseingang für Rücksetztaste NPN. Beschaltet nach GND Taste freigeschaltet. Rücksetzeingang AC/DC E5224C0458 Gemeinsamer Anschluss für INP A und INP B E5224C0448 Timer-Enable-Eingang AC/DC Typ Tabelle 3 Schraubklemme 2: Common AC/DC, gemeinsamer Anschluss für Optokoppler-Eingänge (Schraubklemme 1 und Schraubklemme 3). Schraubklemme 3: Rücksetzeingang: 10 ... 260 V AC/DC galvanisch entkoppelt min. Impulszeit: 16 ms max. Frequenz: ca. 30 Hz Low-Pegel: 0 ... 2 V AC/V DC High-Pegel: 10 ... 260 V AC/DC Eingangswiderstand: ca. 160 kOhm Schraubklemme 5: Umschaltung der Zeitbereiche (Mode) Kontakteingang/Open Collector NPN Low-Pegel: 0 ... 0,7 V DC High-Pegel: 3 ... 5 V DC Eingangswiderstand: ca. 2,2 MOhm Funktion: siehe Tabelle 3 deutsch Schraubklemme 1: Timer-Enable-Eingang: Zeitmessung solange High-Pegel an diesem Eingang. Optokoppler-Eingang 10 ... 260 V AC/DC galvanisch entkoppelt, aktiv bei High-Signal Low-Pegel: 0 ... 2 V AC/V DC High-Pegel: 10 ... 260 V AC/DC Eingangswiderstand: ca. 160 kOhm Hinweis: Wenn Sie den Zeitbereich während des Betriebes wechseln, müssen Sie einen Reset durchführen. Der Zählwert ist sonst nicht reproduzierbar. Schraubklemme 6: Gemeinsamer GND-Anschluss für Schraubklemme 4 (Rücksetztaste-Verriegelungseingang) und Schraubklemme 5 (Zeitbereichsumschaltung) Schraubklemme 7: (–) externe Spannung bei Option LCD-Hinterleuchtung Schraubklemme 8: (+) externe Spannung bei Option LCD-Hinterleuchtung (24 V DC ±20 %, 50 mA) Schraubklemme 4: Elektrische Verriegelung der Rücksetztaste Kontakteingang / Open Collector NPN Low-Pegel: 0 ... 0,7 V DC High-Pegel: 3 ... 5 V DC Eingangswiderstand: ca. 2,2 MOhm Eingang unbeschaltet: Rücksetztaste verriegelt Eingang beschaltet nach GND: Rücksetztaste freigeschaltet MN05401006E For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com 15 Lieferumfang: Digitalanzeige Spannbügel Frontrahmen für Schraubbefestigung, Einbauquerschnitt 50 x 25 mm Frontrahmen für Spannbügelbefestigung, Einbauquerschnitt 50 x 25 mm Dichtung Bedienungsanleitung Hinweis: Dieses Produkt enthält eine Lithium-Batterie. Nicht gewaltsam öffnen, nicht ins Feuer werfen. Temperaturen unter –20 °C und über 70 °C vermeiden! Installationshinweise: DC-Ausführungen: Damit Sie die maximale EMV-Festigkeit erreichen, müssen Sie für den Timer-Enable-Eingang und die Steuereingänge geschirmte Leitungen verwenden. AC-Ausführungen: Damit Sie die maximale EMV-Festigkeit erreichen, müssen Sie für die Steuereingänge geschirmte Leitungen verwenden. Bestimmungsgemäßer Gebrauch: Sicherheitshinweise: Sie dürfen das Gerät nur als Einbaugerät einsetzen! Der Anwendungsbereich des Produktes liegt in industriellen Prozessen und Steuerungen. In den Bereichen von Fertigungsstraßen der Metall-, Holz-, Kunststoff-, Papier-, Glas- und Textilindustrie u.ä. Beachten Sie, daß die Überspannungen, an denen das Produkt an den Schraubklemmen ausgesetzt ist, auf den Wert der Überspannungskategorie II begrenzt sein müssen. Die Überspannungskategorie II ist in der EN 61 010 Teil 1 beschrieben. Sie dürfen das Gerät nur im ordnungsgemäß eingebauten Zustand betreiben. Sie dürfen das Gerät nur entsprechend dem Kapitel “allgemeine technische Daten” betreiben. ! Benutzen Sie diese Zähler nur – bestimmungsgemäß – in technisch einwandfreiem Zustand – unter Beachtung der Bedienungsanleitung und den allgemeinen Sicherheitsbestimmungen. Beachten Sie zudem, dass es länder- und anwenderspezifische Sicherheitsbestimmungen geben kann, die Sie beachten müssen. Sie dürfen dieses Gerät nicht – in explosionsgefährdeten Bereichen, – in den Einsatzbereichen, die in EN 61 010 T1 ausgeschlossen sind betreiben. Wenn Sie das Gerät zur Überwachung von Maschinen oder Ablaufprozessen einsetzen, bei denen infolge eines Ausfalls oder einer Fehlbedienung des Gerätes eine Beschädigung der Maschine oder ein Unfall des Bedienungspersonals möglich ist, müssen Sie entsprechende Sicherheitsvorkehrungen treffen. 16 MN05401006E For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com Connections/Conexiones/Schémas de branchement/Anschlussbilder: DC-Typ: E5224C0440 E5224C0450 max. 30 V DC n.c. max. 5 V DC 1 INP B Reset 2 3 Reset 4 Enable Mode 5 GND (-) BL (+) BL 6 7 8 24 V DC ±20 %, 50 mA AC-Typ: E5224C0448 E5224C0458 max. 5 V DC INP A 1 Common 2 AC/DC INP B 3 Reset Enable Mode 4 GND 6 (-) BL (+) BL 10 .. 260 VAC/VDC 10 .. 260 VAC/VDC Time ranges and display/Rangos de tiempo y pantalla/Plages de temps et affichage/ Zeitbereiche und Anzeige des Betriebsstundenzählers Time range/Rango de tiempo/Plage de temps/Zeitbereiche Display/Pantalla/ Affichage/Anzeige 99999 h 59 m 99999.99 h 5 7 8 9999 h 59 m 59 s 24 V DC ±20 %, 50 mA 9999999.9 s BL = backlight/iluminación posterior/rétroéclairage/Hinterleuchtung MN05401006E For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com 17 24 [0.94] 48 [1.89] 22 x 45 [0.87 x 1.77] Dimensions in mm [in.]/Dimensiones/Dimensions/Abmessungen: max. 19.3 [0.76] 2.8 [0.11] 3.0 [0.12] 22.2 + 0.3 [0.87 + 0.01] 47.7 [1.88] Panel cut-out/Plantilla de recorte del panel/Découpe d’encastrement/Schalttafelausschnitt : 45.0 + 0.6 [1.77 + 0.02] Frame dimensions in mm [in.]/Dimensiones del marco/Dimensions du cadre/Abmessungen Einbaurahmen: 53 [2.09] 28 [1.10] 25 x 50 [0.98 x 1.97] 25 + 0.5 [0.98 + 0.02] 50 + 0.6 [1.97 + 0.02] Panel cut-out/Plantilla de recorte del panel/ Découpe d’encastrement/ Schalttafelausschnitt : 1 [0.04] 4 [0.16] 25 + 0.5 [0.98 + 0.02] M3 1 [0.04] 1 1 18 32 + 0.1 [1.26 + 0.004] 50 + 0.6 [1.97 + 0.02] 25 x 50 [0.98 x 1.97] 32 [1.26] 40 [1.57] 56 [2.20] Panel cut-out/Plantilla de recorte del panel/ Découpe d’encastrement/ Schalttafelausschnitt : 4 [0.16] Countersinking Af3, DIN 74/Avellanado, Af3, DIN 74/Fraisure Af3, DIN 74/Senkung Af3, DIN 74 MN05401006E For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com Eaton Corporation Electrical Group 1000 Cherrington Parkway Moon Township, PA 15108 United States 877-ETN CARE (877-386-2273) Eaton.com © 2007 Eaton Corporation All Rights Reserved Printed in USA Publication No. MN05401006E/CPG March 2007 For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20

Eaton 3h.508 Operating Instructions Manual

Tipo
Operating Instructions Manual
Este manual también es adecuado para

en otros idiomas