Operating Instructions
Electronic Preset Counter
E5148C142 Series
3. Display
—— count value
1. Description
2.1 INP A, INP B
Count inputs; max. count frequency 30 Hz or 10 kHz
separately selectable for both inputs via programming
switches C and D at the right side of the housing.
A B C D
D
C
symbol for activated output
français
indicator for current preset value
4. Output
deutsch
Relay with potential free change-over contact or
optocoupler with open collector and emitter.
Activated output will be indicated by
I.
For safety circuits the operation of the relay, or the
optocoupler may be inverted. Thus the relay coil will be
dead, or the optocoupler will be locked when reaching
the preset point. For this application, the output signal
Out 1 must be set to –l– (permanent signal) or –l–l–
(timed signal) during the programming routine.
Caution: For operating modes with automatic reset
(AddAr, SubAr) the duration of the timed signal for the
output has to be programmed, otherwise the output
signal has no defined duration (see programming).
5. Setting of the operating parameters
a. connect to supply voltage
2. Inputs
DIP switch
español
—— preset value
– 6 digit preset counter, 1 preset, add./subtr.
– bright 2-line LCD display with symbols for activated
output and current preset value
– count and preset range – 999999 to 999999, over- or
underflow without count loss up to 1 decade (will be
indicated by flashing of the display with 1 Hz
frequency)
– programmable to operate as a preset counter, timer or
frequency meter
– relay or optocoupler output
– programming of count functions/operating parameters
via the setting keys. During programming the display
guides the user with text prompts.
– programmable features:
operating mode (output signal at zero or at preset
point, with or without automatic reset)
decimal point
polarity of the inputs (NPN or PNP)
input mode and scaling factor
output signals to be permanent or timed
gate time when programmed as a frequency meter
resolution when programmed as a timer (s, min, h or
h:min:s)
– supply voltage 230V AC, 115V AC, 48V AC, 24V AC or
11 – 30V DC
– backlit display (optional)
OFF
ON
INP A
30 Hz
10 kHz
ON
OFF
INP B
30 Hz
10 kHz
ON
OFF
2.2 Gate
Static input; no counting while this input is activated.
If operated as a timer (only h, min and 0.1 min resolutions), the decimal point between the 5th and 6th
decade flashes while gate input is not activated
(operating indication).
b. set DIP switch “A” (right side of the housing) to “ON”
for a short time. Display will show 1st menu item
“Mode”.
c. select required function via
key
d. press P-key to store selected function/enter data and
to change over to next menu item.
e. select the desired function again via key to enter
data (prescaling factor, duration of timed signal, gate
time, resolution) directly via the two arrow-keys.
f.
After programming the last menu item (permanent or
timed signal), the programming routine will be exited
by pressing the P-key, if DIP switch “A” is set to
“OFF”. If it is still set to “ON”, the programming
routine will be passed through once again.
OFF
ON
A B C D
2.3 Reset
Dynamic input; switched in parallel with the red set key
and sets the counter to zero (adding mode) or to the
preset value (subtracting mode).
MN05401009E
english
2.4 Key
1
6. Setting of the operating mode
6.1 Selection of basic function
After DIP switch “A” has been switched to “ON” for a
short time, one of the basic functions will be displayed
as follows:
programming
routine
Impulse Counter
programming
routine
Timer
programming
routine
Frequency Meter
Scaling factor:
0.0001…9.9999
Setting with and
keys
Factor 0.0000 wonʼt be accepted
Caution! In operating modes Sub
and SubAr (output signal at
count value = zero) the preset
value has to be evenly divisible
by the factor, otherwise the
counter — when reset — will be
set to the next integer multiple of
the factor.
Decimal point
(only optical function)
0
= no decimal point
0.0 = one decimal place
0.00 = two decimal places
0.000 = three decimal places
6.2.1 Programming routine Impulse Counter
Operating mode Add:
Adding mode
Permanent signal at count value ≥
preset value or timed signal at
count value = preset value
Reset to zero
Operating mode Sub:
Subtracting mode
Permanent signal at count value ≤
zero or timed signal at count value
≤ zero. Reset to preset value
Permanent signal of the output,
activated at count value ≥ preset
value in adding mode and at
count value ≤ zero in subtracting
mode*
Permanent signal of the output,
will become passive at count
value ≥ preset value in adding
mode and at count value ≤ zero
in subtracting mode**
Operating mode AddAr:
Adding mode
Timed signal at count value =
preset value
Automatic reset to zero
Timed signal of the output, will
become passive at count value =
preset value in adding mode
and at count value = zero in
subtracting mode**
Operating mode SubAr:
Subtracting mode
Timed signal at count value = zero
Automatic reset to preset value
Timed signal of the output,
activated at count value = preset
value in adding mode and at
count value = zero in subtracting
mode*
Polarity of the inputs:
pospol: positive polarity (PNP)
sourcing from + 24V
negpol: negative polarity (NPN)
sinking to 0V
Input modes:
E1: INP A = count input
INP B = count direction input
Duration of timed signal of the
output can be set from 00.01 s to
99.99 s
* Activation of relay coil or
optocoupler when reaching the
preset value
** Relay coil becomes dead or
optocoupler will be locked when
reaching the preset value.
E2: INP A = count input adding
INP B = count input subtr.
E3: Quadrature input
INP A = count input 0°
INP B = count input 90°
E4: same as E3, but with pulse
doubling.
Each pulse edge of INP A will
be counted.
2
MN05401009E
Operating mode Add:
Adding mode
Permanent signal at count value
≥ preset value or timed signal at
count value = preset value
Reset to zero
Operating mode Sub:
Subtracting mode
Permanent signal at count value
≤ zero or timed signal at count
value = zero. Reset to preset
value
Operating mode AddAr:
Adding mode
Timed signal at count value =
preset value. Automatic reset to
zero
Operating mode SubAr:
Subtracting mode
Timed signal at count value = zero
Automatic reset to preset value
Polarity of the inputs:
pospol: positive polarity (PNP),
soucing from + 24V
negpol: negative polarity (NPN),
sinking to 0V
Permanent signal of the output,
activated at count value ≥ preset
value in adding mode and at
count value ≤ zero in subtracting
mode *
Permanent signal of the output
will become passive at count
value ≥ preset value in adding
mode and at count value ≤ zero
in subtracting mode**
Timed signal of the output, will
become passive at count value
= preset value in adding mode
and at count value = zero in
subtracting mode**
Timed signal of the output,
activated at count value = preset
value in adding mode and at
count value = zero in subtracting
mode*
Duration of timed signal of the
output, can be set from 00.01s
to 99.99 s.
* Activation of relay coil or
optocoupler when reaching the
preset value
** Relay coil becomes dead or
optocoupler will be locked when
reaching the preset value.
Unit of time:
Timing in s; 0.1 s; 0.01 s or 0.001 s*
Timing in min; 0.1 min; 0.01 min*
or 0.001 min*
Timing in h; 0.1 h; 0.01 h or 0.001 h*
* depending on position of the
decimal point
Timing in h: min: s
Decimal point (resolution):
0
= no decimal point
0.0 = one decimal place
0.00 = two decimal places
0.000 = three decimal places
MN05401009E
3
english
6.2.2 Programming routine Timer
6.2.3 Programming routine Frequency Meter
Gate time = within this period the
incoming pulses will be counted
and displayed.
Programmable range from 00.01 s
to 99.99 s
Setting with and keys
00.00 wonʼt be accepted
Polarity of the inputs:
pospol: positive polarity (PNP),
sourcing sensor
Permanent signal of the output,
activated at count value ≥ preset
value*
Permanent signal of the output,
will become passive at count
value ≥ preset value**
Timed signal of the output, will
become passive at count value =
preset value**
negpol: negative polarity (NPN),
sinking sensor
Timed signal of the output,
activated at count value = preset
value*
Input modes:
E1: INP A = count input
INP B = count direction input
E2: INP A = count input adding
INP B = count input subtr.
E3: Quadrature input
INP A = count input 0°
INP B = count input 90°
E4: same as E3, but with pulse
doubling.
Each pulse edge of INP A will
be counted.
Duration of timed signal of the
output can be set from 00.01 s to
99.99 s
* Activation of relay coil or
optocoupler when reaching the
preset value
** Relay coil becomes dead or
optocoupler will be locked when
reaching the preset value.
Scaling factor:
0.0001…9.9999
Setting with and keys
Factor 0.0000 wonʼt be accepted
Decimal point
(only optical function):
0
= no decimal point
0.0 = one decimal place
0.00 = two decimal places
0.000 = three decimal places
4
MN05401009E
7. Programming of the Preset Value:
8. Examples for application connections:
english
After pressing one of the arrow keys, the leading zero
blanking will be suppressed for approx. 4 seconds and
the least significant digit of the preset value flashes with
a frequency of 1 Hz.
The value of the flashing digit can be increased by using
the key. With the key it will be changed to the next
digit. If no key is pressed for 4 seconds, the
leading zero blanking will be activated automatically
again.
In operating mode Impulse Counter and Frequency
Meter the new value will be selected.
Caution! Do not change presets with output powered.
Count pulses from contact closure
(programmed polarity PNP)
Setting of the 6th decade
Count pulses from a light barrier
7.1 Setting of the sign
Select the sign by using the key. The sign will start to
flash now and can be assigned to the preset value or
eliminated by using the key.
If no key is pressed for 4 seconds, the leading zero
blanking will be activated automatically again. Preset
value and count value are displayed now with the
corresponding sign. Intent of negative presets is to allow
reset to a negative value.
Caution! In case of automatic reset no negative values
are to be set for the preset value.
Count pulses from a shaft encoder
MN05401009E
5
9. Connections
10. Technical Data
Supply voltage:
90 – 260V AC, 48V AC, 24V AC,
50/60 Hz, ±10 %,
max. 4 VA
or 11 – 30V DC, max. 0.1 A
Display:
6 digit, 2-line 7 segment LCD display
with sign
count value 9 mm [0.35 in.] high characters
preset value 7 mm [0.28 in.] high characters
symbols for displayed preset and closed
output contact
Polarity of input signals:
programmable, all inputs in common
Input sensitivity:
approx. 10 kOhm
9.1 Plug connection X1
Terminal
No.
1
2
3
4
5
6
7
AC version
DC version
no connection
no connection
relay output common contact (C)
optocoupler output emitter
relay output normally open contact (NO)
relay output normally closed contact (NC)
optocoupler output collector
90 – 260V AC/
11 – 30V DC
48V/24V AC
operating voltage
90 – 260V AC
0V DC (GND)
48V/24V AC
Caution! For settings –l– and –l–l– (inverted operation of
relay or optocoupler) the connections of terminal 4 and 5
change as follows:
Terminal AC and DC versions
No.
4
relay output normally closed contact (NC)
5
relay output normally open contact (NO)
9.2 Plug connection X2
Terminal Designation Function
Function
No.
230V/115V AC
11 – 30V DC
48V/24V AC
version
version
1
+ 24V DC Transmitter voltage —
2
GND
0V DC reference —
voltage
3
INP A
count input A
4
INP B
count input B
5
RESET
reset input
6
GATE
gate input
7
KEY
keyboard lock input
Count frequency:
via DIP switches separately selectable for
INP A and INP B
30 Hz
10 kHz (7 kHz for input modes E3 and E4,
quadrature inputs)
in case of automatic reset 900 Hz
without count losses (500 Hz for input
mode E4)
Min. pulse length of the control inputs:
5 ms
Input sensitivity:
For AC supply voltages
Log “0”: 0 – 4V DC
Log “1”: 12 – 30V DC
For DC supply voltage Ub
Log “0”: 0 – 0.2 x Ub
Log “1”: 0.6 x Ub – 30V DC
Ub = Supply Voltage
Pulse shape: variable (Schmitt Trigger characteristic)
Output:
Relay with potential free make or break
contact
switching voltage max.
250V AC / 300V DC
switching current max. 3 A
switching current for DC min. 30 mA
switching performance max. 50W for DC
and max. 2000 VA for AC
or
optocoupler with open collector and emitter
switching performance: 30V DC/15 mA
Vce sat at Ic = 15 mA: max. 2.0V
Vce sat at Ic = 5 mA: max. 0.4V
Responding time of outputs:
Relay:
approx. 6 ms
Optocoupler: approx. 1 ms
Data retention:
min. 10 years or 106 memory cycles
Transmitter voltage:
24V DC –40 % / +15 %, 80 mA
unregulated for 24 and 48V AC-versions
24V DC –40 % / +15 %, 100 mA
unregulated for 90 – 260V AC-versions
6
MN05401009E
english
Fuse protection:
recommended fuse
for DC:
0.125 A Time Delay
for 90 – 260V AC: 0.05 A Time Delay
for 48V AC:
0.2 A Time Delay
for 24V AC:
0.4 A Time Delay
Noise immunity:
EN 55011 class B and EN 50082-2
with shielded data inputs
Ambient temperature:
0 to 50°C [32 to 122°F]
Storage temperature:
-25 to 70°C [-13 to 158°F]
Weight:
approx. 240 g [8.46 oz.]
(AC-version with relay)
Front panel rating:
IP 65
Color of housing:
black
Cleaning:
The front of the unit is only to be cleaned
with a soft cloth moistened with water.
11. Contents:
– Counter
– Screw terminal plug 7 poles, 5.08 mm [0.2 in] spacing
– Screw terminal plug 7 poles, 3.81 mm [0.15 in.]
spacing
– Bezel for screw mount, panel cut-out 50 x 50 mm
[1.97 x 1.97 in.]
– Bezel for clip mount, panel cut-out 50 x 50 mm
[1.97 x 1.97 in.]
– Panel mounting clip
12. Ordering Code
E5148C142X
1 = 90 – 260V AC
2 = 10 – 30V DC
MN05401009E
7
Dimensions in mm [in.]:
max. 10.5 [0.41]
48 [1.89]
45 [1.77]
48 [1.89]
86.5 [3.41]
55 [2.17]
max. 9.5 [0.37]
50 [1.97]
45 [1.77]
55 [2.17]
3 [0.12]
15.5
[0.61]
Panel cut-out 45 x 45 [1.77 x 1.77]
85.5 [3.37]
Shown with front frame No. 2
panel cut-out 50 x 50 [1.97 x 1.97]
4 [0.16]
15.5
[0.61]
60 [2.36]
50 [1.97]
75 [2.95]
63 [2.48]
45 [1.77]
max. 9.5 [0.37]
85.5 [3.37]
Sinking
4 [0.16]
DIN 74
Shown with front frame No. 3
panel cut-out 50 x 50 mm [1.97 x 1.97]
15.5
[0.61]
– Subject to changes without prior notice –
8
MN05401009E
2.4 Tecla
Instrucciones de operación
Contador electrónico preconfigurado
Serie E5148C142
Entrada de bloqueo del teclado estático. Mientras esta
entrada esté activada, no es posible restablecer el
contador ni cambiar el valor preconfigurado.
3. Pantalla
—— Valor de conteo
1. Descripción
2. Entradas
2.1 ENTRADA A, ENTRADA B
Entradas de conteo; frecuencia máxima de conteo de
30 Hz o 10 kHz que se pueden seleccionar por separado
para ambas entradas mediante interruptores de
programación C y D en el costado derecho de la cubierta.
OFF
ON
A B C D
Conmutador
DIP
D
C
ENT A
30 Hz
10 kHz
ON
OFF
ENT B
30 Hz
10 kHz
ON
OFF
2.2 Cómputo
Entrada estática; no se efectúa conteo mientras esta
entrada está activada. Si se opera como temporizador
(sólo resoluciones de horas, minutos y 0,1 minuto), el
punto decimal entre el quinto y sexto decimal destella
mientras la entrada de cómputo no está activada
(indicación de funcionamiento).
—— Valor preconfigurado
español
– Contador preconfigurado de 6 dígitos, 1 valor
preconfigurado, adición/sustracción.
– Pantalla LCD brillante de 2 líneas con símbolos para
la salida activada y el valor preconfigurado de corriente.
– Rango de conteo y preconfigurado (de – 999999 a
999999), sobre o bajo el flujo sin pérdidas de conteo
de hasta 1 decimal (se indicará mediante destellos de
la pantalla con una frecuencia de 1 Hz).
– Programable para operar como un contador,
temporizador o medidor de frecuencia preconfigurado.
– Salida de relé u optoacoplador.
– Programación de funciones de conteo/parámetros de
operación por medio de las teclas de configuración.
Durante la programación, la pantalla guía al usuario
con indicaciones de texto.
– Funciones programables:
Modo de funcionamiento (señal de salida en cero o en
un punto preconfigurado, con o sin restablecimiento
automático)
Punto decimal
Polaridad de las entradas (NPN o PNP)
Modo de entrada y factor de escala
Señales de salida que serán permanentes o
temporizadas
Tiempo de cómputo cuando se programa como
medidor de frecuencia
Resolución cuando se programa como temporizador
(s, min, h u h:min:s)
– Voltaje de suministro 230 V CA, 115 V CA, 48 V CA,
24 V CA o 11 a 30 V CC
– Pantalla con luz posterior (opcional)
Símbolo de salida activada
Indicador de valor
preconfigurado de corriente
4. Salida
Relé con contacto inversor libre de potencial u
optoacoplador con toma de corriente y emisor abiertos.
Se indicará la salida activada mediante
I.
Para circuitos de seguridad, la operación del relé o del
optoacoplador se puede invertir. De este modo, la
bobina de relé se inactivará o el optoacoplador se
bloqueará al llegar al punto preconfigurado. Para esta
aplicación, la señal de salida Out 1 (Salida 1) debe
configurarse en –l– (señal permanente) o en –l–l– (señal
temporizada) durante la rutina de programación.
Precaución: En los modos de funcionamiento con
restablecimiento automático (AddAr, SubAr) se debe
programar la duración de la señal temporizada para la
salida, de lo contrario, la señal de salida no tendrá
duración definida (consulte Programación).
5. Configuración de los parámetros de
funcionamiento
a. Conecte el voltaje de suministro.
b. Coloque el conmutador DIP “A” (lado derecho de la
carcasa) en “ON” (encendido) durante un tiempo
breve. La pantalla mostrará el elemento del primer
menú “Modo”.
c. Seleccione la función necesaria mediante la tecla .
d. Presione la tecla P para almacenar la función
seleccionada/ingresar datos y para cambiar al
siguiente elemento del menú.
e. Seleccione la función que desee nuevamente con la
tecla para ingresar datos (factor de escala previa,
duración de la señal temporizada, tiempo de
cómputo, resolución) de forma directa mediante las
dos teclas de flecha.
f. Después de programar el último elemento del menú
(señal permanente o temporizada), saldrá de la
rutina de programación presionando la tecla P, si el
conmutador DIP “A” está en “OFF” (Apagado). Si
todavía está en “ON”, la rutina de programación
volverá a pasar una vez más.
OFF
ON
A B C D
2.3 Restablecimiento
Entrada dinámica; entra en funcionamiento en paralelo
con la tecla de configuración roja y ajusta el contador en
cero (modo de adición) o en el valor preconfigurado
(modo de sustracción).
MN05401009E
9
6. Configuración del modo de
funcionamiento
6.1 Selección de función básica
Después de que se ha encendido el conmutador DIP “A”
durante un tiempo breve, se mostrará una de las
funciones básicas del siguiente modo:
Rutina de
programación del
contador de
impulsos
Rutina de
programación
del
temporizador
Rutina de
programación del
medidor de
frecuencia
6.2.1 Rutina de programación del contador de
impulsos
Modo de funcionamiento Add:
Modo de adición
Señal permanente en el valor de
conteo ≥ valor preconfigurado o
señal temporizada en el valor de
conteo = valor preconfigurado
Restablecimiento en cero
Modo de funcionamiento Sub:
Modo de sustracción
Señal permanente en el valor de
conteo ≤ cero o señal temporizada
en el valor de conteo ≤ cero.
Restablezca el valor preconfigurado
Modo de funcionamiento AddAr:
Modo de adición
Señal temporizada en el valor de
conteo = valor preconfigurado
Restablecimiento automático en
cero
Modo de funcionamiento SubAr:
Modo de sustracción
Señal temporizada en el valor de
conteo = cero
Restablecimiento automático en el
valor preconfigurado
Polaridad de las entradas:
pospol: polaridad positiva (PNP)
modificación a + 24 V
Factor de escala:
0,0001…9,9999
Configuración con las teclas
y
No se aceptará el factor 0,0000
¡Precaución! En los modos de
funcionamiento Sub y SubAr
(señal de salida en el valor de
conteo = cero) el valor
preconfigurado debe ser
igualmente divisible por el factor;
de lo contrario, cuando — se
restablezca —el contador se
ajustará en el siguiente múltiplo
entero del factor.
Punto decimal
(sólo función óptica)
0
= sin punto decimal
0.0 = una cifra decimal
0.00 = dos cifras decimales
0.000 = tres cifras decimales
Señal permanente de la salida,
activada en el valor de conteo ≥
valor preconfigurado en el modo
de adición y en el valor de
conteo ≤ cero en el modo de
sustracción*
La señal permanente de la
salida, será pasiva en el valor de
conteo ≥ valor preconfigurado en
el modo de adición y en el valor
de conteo ≤ cero en el modo de
sustracción**
La señal temporizada de la
salida será pasiva en el valor de
conteo = valor preconfigurado en
el modo de adición y en el valor
de conteo = cero en el modo de
sustracción**
Señal temporizada de la salida,
activada en el valor de conteo =
valor preconfigurado en el modo
de adición y en el valor de
conteo = cero en el modo de
sustracción*
negpol: polaridad negativa (NPN)
profundización a 0 V
Modos de entrada:
E1: ENT A = entrada de conteo
ENT B = entrada de dirección
de conteo
E2: ENT A = adición de entrada de
conteo
ENT B = sustracción de
entrada de conteo
La duración de la señal
temporizada de la salida se
puede ajustar de 00,01 s a
99,99 s
* Activación de la bobina de relé
u optoacoplador al llegar al valor
preconfigurado
** La bobina de relé se inactivará
o el optoacoplador se bloqueará
al llegar al valor preconfigurado
E3: Entrada de cuadratura
ENT A = entrada de conteo 0°
ENT B = entrada de conteo
90°
E4: Igual que E3, pero con
duplicación de impulsos.
Se contará cada flanco del
impulso de la ENT A.
10
MN05401009E
6.2.2 Rutina de programación del
temporizador
Modo de funcionamiento Sub:
Modo de sustracción
Señal permanente en el valor de
conteo ≤ cero o señal
temporizada en el valor de
conteo = cero. Restablezca el
valor preconfigurado
Modo de funcionamiento
AddAr:
Modo de adición
Señal temporizada en el valor de
conteo = valor preconfigurado.
Restablecimiento automático en
cero
Modo de funcionamiento
SubAr:
Modo de sustracción
Señal temporizada en el valor de
conteo = cero
Restablecimiento automático en
el valor preconfigurado
Polaridad de las entradas:
pospol: polaridad positiva (PNP)
modificación a + 24 V
negpol: polaridad negativa
(NPN), profundización a 0 V
Unidad de tiempo:
Tiempo en segundos; 0,1 s; 0,01 s
o 0,001 s*
Señal permanente de la salida,
activada en el valor de conteo ≥
valor preconfigurado en el modo
de adición y en el valor de
conteo ≤ cero en el modo de
sustracción*
La señal permanente de la
salida, será pasiva en el valor
de conteo ≥ valor
preconfigurado en el modo de
adición y en el valor de conteo ≤
cero en el modo de
sustracción**
La señal temporizada de la
salida será pasiva en el valor de
conteo = valor preconfigurado
en el modo de adición y en el
valor de conteo = cero en el
modo de sustracción**
Señal temporizada de la salida,
activada en el valor de conteo =
valor preconfigurado en el modo
de adición y en el valor de
conteo = cero en el modo de
sustracción*
La duración de la señal
temporizada de la salida se
puede ajustar de 00,01 s
a 99,99 s
* Activación de la bobina de relé
u optoacoplador al llegar al
valor preconfigurado
** La bobina de relé se
inactivará o el optoacoplador se
bloqueará al llegar al valor
preconfigurado
Tiempo en minutos; 0,1 min; 0,01
min* o 0,001 min*
Tiempo en horas; 0,1 h; 0,01 h
o 0,001 h*
* Dependiendo de la posición del
punto decimal
Tiempo en horas, minutos y
segundos
Punto decimal (resolución):
0
= sin punto decimal
0.0 = una cifra decimal
0.00 = dos cifras decimales
0.000 = tres cifras decimales
MN05401009E
11
español
Modo de funcionamiento Add:
Modo de adición
Señal permanente en el valor de
conteo ≥ valor preconfigurado o
señal temporizada en el valor de
conteo = valor preconfigurado
Restablecimiento en cero
6.2.3 Rutina de programación del medidor de
frecuencia
Tiempo de cómputo = dentro de
este período se contarán y
mostrarán los impulsos.
El rango programable es de 00,01
s a 99,99 s
Configuración con las teclas
y
00,00 no se aceptará
Polaridad de las entradas:
pospol: polaridad positiva (PNP)
sensor de modificación
negpol: polaridad negativa (NPN),
sensor de profundización
Señal permanente de la salida,
activada en el valor de conteo ≥
valor preconfigurado*
La señal permanente de la salida
será pasiva en el valor de conteo
≥ valor preconfigurado**
La señal temporizada de la salida
será pasiva en el valor de conteo
= valor preconfigurado**
Señal temporizada de la salida,
activada en el valor de conteo =
valor preconfigurado*
Modos de entrada:
E1: ENT A = entrada de conteo
ENT B = entrada de dirección
de conteo
E2: ENT A = adición de entrada de
conteo
ENT B = sustracción de
entrada de conteo
E3: Entrada de cuadratura
ENT A = entrada de conteo 0°
ENT B = entrada de conteo
90°
E4: Igual que E3, pero con
duplicación de impulsos.
Se contará cada flanco del
impulso de la ENT A.
La duración de la señal
temporizada de la salida se
puede ajustar de 00,01 s a
99,99 s
* Activación de la bobina de relé u
optoacoplador al llegar al valor
preconfigurado
** La bobina de relé se inactivará
o el optoacoplador se bloqueará
al llegar al valor preconfigurado
Factor de escala:
0,0001…9,9999
Configuración con las teclas
y
No se aceptará el factor 0.0000
Punto decimal
(sólo función óptica):
0
= sin punto decimal
0.0 = una cifra decimal
0.00 = dos cifras decimales
0.000 = tres cifras decimales
12
MN05401009E
Después de presionar una de las teclas de flecha, se
eliminará la supresión de cero inicial por
aproximadamente 4 segundos y el último dígito
importante de los valores preconfigurados destellará
con una frecuencia de 1 Hz.
El valor del digito que destella se puede aumentar con
la tecla . Con la tecla cambiará al siguiente dígito.
Si no se presiona ninguna tecla durante 4 segundos, la
supresión del cero inicial se activará automáticamente
de nuevo.
En el modo de funcionamiento del contador de impulsos
y medidor de frecuencia se seleccionará el nuevo valor.
8. Ejemplos de conexiones de
aplicaciones:
español
7. Programación del valor
preconfigurado:
Impulsos de conteo del cierre del
contacto (polaridad programada PNP)
Configuración del sexto decimal
Impulsos de conteo de una barrera de luz
7.1 Configuración del signo
Seleccione el signo utilizando la tecla . El signo
comenzará a destellar ahora y se puede asignar un
valor preconfigurado o eliminar con la tecla .
Si no se presiona ninguna tecla durante 4 segundos, la
supresión del cero inicial se activará automáticamente
de nuevo. Ahora aparece el valor preconfigurado y el
valor de conteo con el signo correspondiente.
¡Precaución! En caso de restablecimiento automático,
no se configurará ningún valor negativo para el valor
preconfigurado.
Impulsos de conteo de un codificador de eje
MN05401009E
13
9. Conexiones
10. Datos técnicos
Voltaje de suministro:
90 – 260 V CA, 48 V CA, 24 V CA, 50/60
Hz, ±10 %, máx. 4 V A o 11 – 30 V CC,
máx. 0,1 A
Pantalla:
Pantalla LCD de 7 segmentos, 2 líneas y
6 dígitos con signo
Caracteres de 9 mm [0,35 pulg.] de altura
para el valor de conteo
Caracteres de 7 mm [0,28 pulg.] de altura
para el valor preconfigurado
Símbolos para mostrar el contacto de
salida preconfigurado y cerrado
Polaridad de las señales de entrada:
Programable, todas las entradas en común
9.1 Conexión de enchufe X1
Borne
Nº
1
2
3
4
5
6
7
Versión CA
Versión CC
sin conexión
sin conexión
contacto común de salida del relé (C) emisor
de salida del optoacoplador
contacto normalmente abierto (NA) de salida
del relé
contacto normalmente cerrado (NC) de salida
del relé emisor de salida del optoacoplador
90 – 260 V CA/
11 – 30 V CC
48 V/24 V CA
Voltaje de
funcionamiento
90 – 260 V CA
0 V CC
48 V/24 V CA
(Conex. a tierra)
¡Precaución! Para las configuraciones de –l– y –l–l–
(funcionamiento inverso del relé u optoacoplador) las
conexiones del borne 4 y 5 cambian del siguiente modo:
Borne
Nº
4
5
Versiones de CA y CC
contacto normalmente cerrado (NC) de salida
del relé
contacto normalmente abierto (NA) de salida
del relé
9.2 Conexión de enchufe X2
Borne
Nº
1
2
3
4
5
6
7
Designación Función
Función
versión
versión
230 V/115 V CA 11 – 30 V CC
48 V/24 V CA
+ 24 V CC
Voltaje del
—
transmisor
Conex. a
Voltaje de
—
tierra
referencia
de 0 V CC
ENT A
entrada de conteo A
ENT B
entrada de conteo B
RESTABLE- entrada de restablecimiento
CIMIENTO
CÓMPUTO entrada de cómputo
TECLA
entrada de bloqueo del teclado
Sensibilidad de entrada:
Aprox. 10 kOhm
Frecuencia de conteo:
Mediante conmutadores DIP que se
pueden seleccionar por separado para ENT
A y ENT B
30 Hz
10 kHz (7 kHz para los modos de entrada
E3 y E4, entradas de cuadratura)
En caso de restablecimiento automático
900 Hz sin pérdidas de conteo (500 Hz
para el modo de entrada E4)
Duración mínima del impulso de las entradas de control:
5 ms
Sensibilidad de entrada:
Para voltajes de suministro de CA
Registro “0”: 0 – 4 V CC
Registro “1”: 12 – 30 V CC
Para voltaje de suministro de CC Ub
Registro “0”: 0 – 0.2 x Ub
Registro “1”: 0,6 x Ub – 30 V CC
Ub = Voltajes de suministro
Forma del impulso:
variable (característica de trigger de Schmitt)
Salida:
Relé con contacto de trabajo o reposo libre
de potencial
Voltaje de conmutación máx. 250 V
AC / 300 V CC
Corriente de conmutación máx. 3 A
Corriente de conmutación para CC mín.
30 mA
Rendimiento de conmutación máx. 50 W
para CC y máx. 2000 V A para CA
u
optoacoplador con toma de corriente y
emisor abiertos
Rendimiento de conmutación:
30 V CC/15 mA
Vce sat at Ic = 15 mA: máx. 2,0 V
Vce sat at Ic = 5 mA: máx. 0,4 V
Tiempo de respuesta de las salidas:
Relé:
Aprox. 6 ms
Optoacoplador: Aprox. 1 ms
Retención de datos:
mín. 10 años o 106 ciclos de memoria
Voltaje del transmisor:
24 V CC –40 % / +15 %, 80 mA no
regulado para versiones de 24 y 48 V CA
24 V CC –40 % / +15 %, 100 mA no
regulado para versiones de 90 y 260 V CA
14
MN05401009E
Protección de fusibles:
Fusible recomendado
Para CC:
Retardo de tiempo de
0,125 A
Para 90 – 260 V C: Retardo de tiempo de
0,05 A
Para 48 V CA:
Retardo de tiempo de
0,2 A
Para 24 V CA:
Retardo de tiempo de
0,4 A
español
Inmunidad al ruido:
EN 55011 clase B y EN 50082-2 con
entradas de datos blindadas
Temperatura ambiente:
0 a 50° C [32 a 122° F]
Temperatura de almacenamiento:
-25 a 70° C [-13 a 158° F]
Peso:
Aprox. 240 g [8,46 oz.]
(versión CA con relé)
Clasificación del panel delantero:
IP 65
Color de la carcasa:
Negra
Limpieza:
La parte delantera de la unidad sólo se
debe limpiar con un paño suave
humedecido con agua.
11. Contenido:
– Contador
– Enchufe de bornes de tornillo, 7 polos, espaciado de
5,08 mm [0,2 pulg.]
– Enchufe de bornes de tornillo, 7 polos, espaciado de
3,81 mm [0,15 pulg.]
– Bísel para montaje con tornillos, plantilla de recorte del
panel de 50 x 50 mm [1,97 x 1,97 pulg.]
– Bísel para montaje con abrazadera, plantilla de recorte
del panel de 50 x 50 mm [1,97 x 1,97 pulg.]
– Abrazadera de montaje del panel
12. Código de pedido
E5148C142X
1 = 90 – 260 V CA
2 = 10 – 30 V CC
MN05401009E
15
Dimensiones en mm [pulgadas]:
máx. 10,5 [0,41]
48 [1,89]
45 [1,77]
48 [1,89]
86,5 [3,41]
3 [0,12]
15,5
[0,61]
Plantilla de recorte del panel de 45 x 45 [1,77 x 1,77]
55 [2,17]
50 [1.97]
55 [2,17]
45 [1.77]
máx. 9,5 [0,37]
85,5 [3,37]
4 [0,16]
15,5
[0,61]
Se muestra con la plantilla de recorte del panel de 50 x 50 [1,97 x 1,97] del bastidor delantero Nº 2
60 [2,36]
50 [1.97]
75 [2,95]
63 [2,48]
45 [1,77]
máx. 9,5 [0,37]
85,5 [3,37]
Profundización
DIN 74
4 [0,16]
15,5
[0,61]
Se muestra con la plantilla de recorte del panel de 50 x 50 mm [1,97 x 1,97] del bastidor delantero Nº 3
– Sujeto a cambios sin aviso previo –
16
MN05401009E
2.4 Key
Entrée statique de verrouillage des touches. Tant
que cette entrée est activée, il est impossible de
repositionner le comptage ou de modifier la valeur
de la présélection (au moyen des touches).
Notice de mise en service
du compteur éléctronique
à présélection E5148C142 Série
3. Affichage
1. Description
2.1 INP A, INP B
Entrées de comptage. La fréquence de comptage
maximale de ces 2 entrées est programmable à 30 Hz
ou 10 kHz, au moyen des commutateurs C et D (sur le
côté de lʼappareil).
A B C D
Micro
commut.
D
C
—— Présélection
Sortie active
4. Sortie
Par contact relais inverseur (hors potentiel), ou par
optocoupleur à émetteur et collecteur ouverts.
La sortie active est affichée par le symbole.
.
Pour des commutations de sécurité, il est possible
dʼinverser lʼactivation de la sortie, cʼest à dire, de
désactiver la bobine du relais ou de désaturer
lʼoptocoupleur.
A cet effet, il convient de programmer le signal de sortie
OUT 1 en maintenu par –l– , en fugitif par –l–l–.
ATTENTION: Pour les modes avec répétition automatique (AddAr, SubAr), la sortie doit être programmée
en mode fugitif, sinon cette dernière se retrouve dans un
état indéterminé (voir programmation).
5. Réglage des paramètres
a. Mettre lʼappareil sous tension
b. Commuter brièvement lʼinterrupteur «A» en position
«ON» (à droite du boîtier). Le point 1 «MODE» du
MENU est affiché.
2. Entrées
OFF
ON
—— Comptage
INP A
30 Hz
10 kHz
ON
OFF
INP B
30 Hz
10 kHz
ON
OFF
2.2 Gate
Commande de porte statique. Pas de comptage tant
que cette entrée est activée.
Le point décimal situé entre la 5ème et la 6ème décade
clignote en mode comptage horaire lorsque la
commande de porte est inactive (témoin de marche en
h, min ou 0,1 min.).
c. Sélectionner la fonction voulue au moyen de la
touche .
d. La touche «P» permet de valider la fonction choisie
et de passer au pas de programmation suivant.
e. Continuer la sélection et la validation des fonctions
(facteur, durée de sortie fugitive, base de temps,
résolution), à lʼaide des 2 touches décrites ci-dessus.
f.
Après la mise au point du dernier pas du MENU
(sortie maintenue ou fugitive), lʼappui de la touche
«P» clôt le paramètrage (à condition que le
commutateur «A» soit en position «OFF»). Dans le
cas contraire, le «MENU» de paramètrage reprend
au début.
OFF
ON
A B C D
2.3 Reset
En parallèle avec la touche rouge en façade, elle
repositionne le comptage à zéro en mode additionnant,
à la valeur de la présélection en mode soustrayant.
MN05401009E
17
français
– Compteur à 6 décades, add./soustrayant et à
1 présélection
– Double rangée dʼaffichage à LCD très lisible, avec
symboles pour lʼétat de la sortie
– Capacité de comptage et de présélections: de
–999999 à 999999. Dépassement de capacité sans
perte dʼimpulsions sur 1 décade; dans ce cas,
lʼaffichage clignote au rythme de 1 Hz
– Programmable en compteur horaire, dʼimpulsions ou
en fréquencemètre
– Sortie à relais ou optocoupleur
– La programmation des fonctions de comptage ou des
paramètres sʼéffectue au moyen des touches en
façade. Un guide utilisateur est actif à lʼaffichage
pendant la routine de programmation
– ProgrammableS sont:
Le mode (sortie active à zéro ou à la présélection,
avec ou sans répétition automatique)
Le point décimal
La polarité des entrées (NPN ou PNP)
Le type dʼentrée de comptage et la valeur du facteur
Le signal de sortie en fugitif ou en maintenu
La base de temps en fréquencemètre
La résolution en s, min, h ou h:min:s, en
comptage horaire
– Alimentation: 230, 115, 48, 24 VAC ou 11…30 VDC
6. Sélection du mode de fonctionnement
6.1 Selection de la fonction primaire.
Un brève commutation de lʼinterrupteur «A» en «ON»,
donne lʼaffichage suivant:
Facteur:
0,0001…9,9999
réglable par les touches
et
Un facteur 0,0000 est refusé.
ATTENTION ! en MODE Sub,
SubAR et la valeur de
prépositionnement doit être
divisible par le facteur (sans
décimale), sinon la valeur de
comptage est repositionnée à un
multiple du facteur.
Routine de
programmation
en compteur
dʼimpulsions
Routine de
programmation
en compteur
horaire
Routine de programmation en
fréquencemètre
6.2.1 Paramètrage en compteur dʼimpulsions
Mode Add:
Comptage additionnant.
Signal maintenu pour comptage
≥ à la consigne ou signal fugitif
pour comptage = à la consigne.
Repositionnement à zéro.
Mode Sub:
Comptage soustrayant.
Signal maintenu pour comptage
≤ à zéro.
Signal fugitif pour comptage = à la
consigne.
Repositionnement à la valeur de la
consigne.
Mode Add Ar:
Comptage additionnant:
Signal fugitif pour comptage =
consigne.
Repositionnement automatique
à zéro.
Mode Sub Ar:
Comptage soustrayant:
Signal fugitif pour comptage = zéro.
Repositionnement automatique
à valeur de la consigne.
Polarité des entrées:
PoSPol; polarité positive (PNP),
commutant vers le +24 V.
nEGPoL; polarité négative (NPN),
commutant vers le +0 V.
Type dʼentrée:
E1: INP A = impulsions
INP B = sens de comptage
E2: INP A = impuls. additionnant
INP B = impuls. soustrayant
Point décimal (uniq. visuel)
0
= pas de décimale
0,0 = 1 décimale
0,00 = 2 décimales
0,000 = 3 décimales
Sortie en maintenue, activée en
mode additionnant pour le
comptage ≥ à la consigne
1 et en mode soustrayant pour le
comptage ≤ à zéro*.
Sortie en maintenue, désactivée
en mode additionnant pour le
comptage ≥ à la consigne et en
mode soustrayant pour le
comptage ≤ zéro en mode
soustrayant**.
Sortie en fugitive, désactivée
lorsque le comptage = à la
consigne en mode additionnant
et le comptage = zéro en mode
soustrayant**.
Sortie en fugitive, activée lorsque
le comptage = à la consigne en
mode additionnant et le
comptage = zéro en mode
soustrayant*.
Durée du signal fugitif de la
sortie, règlable de 00,01 s à
99,99 s.
* A lʼatteinte de la consigne, la
bobine du relais est alimentée,
respectivement lʼoptocoupleur est
saturé.
** A lʼatteinte de la consigne, la
bobine du relais nʼest plus
alimentée, respectievement
lʼoptocoupleur est bloqueé.
E3: Quadrature
INP A = impulsions 0°
INP B = impulsions 90°
E4: Idem à E3 avec multiplication
par 2 des impulsions.
Chaque front de INP A est pris
en compte
18
MN05401009E
6.2.2 Paramètrage en compteur horaire
Mode Sub:
Comptage soustrayant.
Signal maintenu pour comptage
≤ à la consigne ou signal fugitif
pour comptage = à la consigne.
Repositionnement à la valeur de
la consigne.
Mode Add Ar:
Comptage additionnant:
Signal fugitif pour comptage
= consigne.
Repositionnement automatique
à zéro.
Sortie maintenue, activée en
mode additionnant pour le
comptage ≥ à la consigne et en
mode soustrayant pour le
comptage ≤ à zéro*.
Sortie maintenue, désactivée en
mode additionnant pur le
comptage ≥ à la consigne et en
mode soustrayant pour le
comptage ≤ à zéro**.
Sortie fugitive, désactivée lorsque
le comptage = à la consigne en
mode additionnant et le comptage
= zéro en mode soustrayant**.
Sortie fugitive, activée lorsque le
comptage = à la consigne en
mode additionnant et le comptage
= zéro en mode soustrayant*.
Mode Sub Ar:
Comptage soustrayant:
Signal fugitif pour comptage
= consigne.
Repositionnement automatique
à valeur de la consigne.
Durée du signal fugitif de la sortie,
règlable de 00,01 s à 99,99 s.
Polarité des entrées
PoSPoL; polarité positive (PNP)
commutant vers le + 24 V.
** A lʼatteinte de la consigne, la
bobine du relais nʼest plus
alimentée, respectivement
lʼoptocoupleur est bloqué.
* A lʼatteinte de la consigne, la
bobine du relais est alimentée,
respectivement lʼoptocoupleur
est saturé.
nEGPoL; polarité négative (NPN),
commutant vers le 0 V.
Unité de mesure:
Comptage en s; 0,1 s; 0,01 s; ou
0,001 s*.
Comptage en min; 0,1 min;
0,01 min; ou 0,001 min*.
Comptage en h; 0,1 h; 0,01 h; ou
0,001 h*.
* selon la position décimale
Point décimal (résolution)
0
= pas de décimale
0,0 = 1 décimale
0,00 = 2 décimales
0,000 = 3 décimales
MN05401009E
19
français
Mode Add:
Comptage additionnant.
Signal maintenu pour comptage
≥ à la consigne ou signal fugitif
pour comptage = à la consigne.
Repositionnement à zéro.
6.2.3 Paramètrage en fréquence
Base de temps = Durée de
comptage des impulsions et
dʼintervalle de réactualisation de
lʼaffichage, règlable de 00,01 s à
99,99 s.
Programmation par les touches et
; une valeur 00,00 est refusée.
Polarité des entrées
PoSPoL; polarité positive (PNP),
commutant vers le + 24 V.
nEGPoL; polarité négative (NPN),
commutant vers le 0 V.
Type dʼentrée:
E1: INP A = impulsions
INP B = sens de comptage
Sortie maintenue pour le
comptage ≥ à la consigne *.
Sortie maintenue pour le
comptage ≥ à la consigne**.
Sortie en fugitive, désactivée
lorsque le comptage = à la
consigne**.
Sortie du signal fugitive, activée
lorsque le comptage = à la
consigne*.
Durée du signal fugitif de la sortie,
réglable de 00,01 s à 99,99 s.
E2: INP A = impuls. additionnant
INP B = impuls. soustrayant
E3: Quadrature
INP A = impulsions 0°
INP B = impulsions 90°
E4: Idem à E3 avec multiplication
par 2 des impulsions.
Chaque front de INP A est pris
en compte
* A lʼatteinte de la consigne, la
bobine du relais est alimentée,
respectivement lʼoptocoupleur est
saturé.
** A lʼatteinte de la consigne, la
bobine du relais nʼest plus
alimentée, respectivement
lʼoptocoupleur est bloqué.
Facteur:
0,0001…9,9999
règlable par les touches et
Un facteur 0,0000 est refusé.
Point décimal (uniq. visuel)
0
= pas de décimale
0,0 = 1 décimale
0,00 = 2 décimales
0,000 = 3 décimales
20
MN05401009E
7. Reglage de la consigne:
8. Exemples de raccordements
Lʼactivation dʼune touche «flèche» désactive la
suppression des zéros pendant 4 secondes environ et la
décade des unités (à droite) de la présélection clignote
au rythme de 1 Hz.
La touche permet dʼincrémenter la décade clignotante.
La touche etpermet de sélectionner la décade
supérieure. Après 4 secondes, si aucune des touches
déscrites ci-dessus nʼest activée la suppression des
zéros inutiles est remise en service. En mode compteur
dʼimpulsions ou fréquencemètre, la nouvelle valeur de
consigne est prise en compte.
Commande par contact et
une polarité en PNP
français
Règlage de la 6ème décade
7.1 Reglage du signe
La touche permet dʼactiver le signe; celui-ci apparait
en clignotant à gauche de la valeur de comptage. La
touche attribue ce signe à la consigne, le cas échéant,
le supprime.
4 secondes après lʼactivation dʼune touche, la
suppression des zéros inutiles est réactivée et la
consigne ainsi que la valeur de comptage sont affichés
avec le signe attribué.
ATTENTION: La valeur de la consigne ne doit pas être
négative lorque le mode «répétition automatique» est
actif !
Commande par barrière de lumière
Commande par générateur dʼimpulsions
MN05401009E
21
9. Raccordements
10. Caractéristiques techniques
Alimentation:
230, 115, 48, 24 VAC, ± 10 %,
max. 4 VA
ou 11…30 VDC, max. 0,1 A
Affichage:
6 décades, 2 lignes, en 7 segments à LCD
avec signe. Comptage 9 mm, consigne
7 mm de hauteur. Symboles pour la sortie
active.
Polarité des entrées:
programmable; commune à toutes les
entrées
Résistance dʼentrée:
env. 10 kOhm
9.1 Connecteur X1
Broche
Nr.
1
2
3
4
5
6
7
230, 115, 48
11…30 VDC
ou 24 VAC
non reliée
non reliée
Sortie 2, commun du relais
Emetteur en optocoupleur
Sortie 2, contact travail du relais
Sortie 2, contact repos du relais
Collecteur en optocoupleur
230 VAC/115 VAC/
11…30 VDC
48 VAC/24 VAC
Alimentation
230 VAC/115 VAC
0 VDC (GND)
48 VAC/24 VAC
ATTENTION! Les raccordements différent lorsque les
sorties sont règlées en –l– ou en –l–l–.(inversion du mode
de commutation de la sortie)
Broche Versions AC et DC
Nr.
4
Sortie relais à ouverture NC
5
Sortie relais à fermeture NO
9.2 Connecteur X2
Broche Désignation Fonction
Fonction
Nr.
en 230,
en
115, 48,
11…30 VDC
24 VAC
1
+ 24 VDC Aliment.
non
générat.
raccordé
2
GND
0 VDC
non
référen.
raccordé
3
INP A
ent. comptage A
4
INP B
ent. comptage B
5
RESET
entrée de repositionnement
6
GATE
commande de porte
7
KEY
ent. verrouillage des touches
Fréquence de comptage:
règlable séparément par commutateurs
DIL, pour les entrées INP A et INP B
30 Hz
10 kHz (7 kHz en mode E3 ou E4,
quadrature)
900 Hz en répétition
automatique sans perte
dʼimpulsions (500 Hz en mode E4).
Durée minimale dʼimpulsions des entrées de commande:
5 ms
Niveau des entrées:
En alimentation AC;
Niv. «0»: 0…4 VDC
Niv. «1»: 12…30 VDC
En alimentation DC, Ub
Niv. «0»: 0…0,2 x Ub
Niv. «1»: 0,6 x Ub–30 VDC
Ub = Tension dʼalimentation
Forme des impulsions:
quelconque, Trigger de Schmitt
Sortie:
Relais à contact inverseur
hors potentiel
Tension max. 250 VAC / 300 VDC
Courant max. 3 A
Courant min. en DC: 30 mA
Pouvoir de commutation max.:
50 W en DC, 2000 VA en VAC
ou
optocoupleur à émetteur et collecteur
ouvert
Pouvoir de commutation max.:
30 VDC / 15 mA
Vce sat pour Ic = 15 mA: max. 2,0 V
Vce sat pour Ic = 5 mA: max. 0,4 V
Temps de réponse de la sortie:
Relais:
env. 6 ms
Optocoupleur: env. 1 ms
Sauvegarde des données:
min. 10 ans ou 106 cycles dʼécriture
Tension dʼémetteur:
24 V DC -40 % / + 15 %, 80 mA
non stabilisés en version AC24 et 48 V
24 V DC -40 % / + 15 %, 100 mA
non stabilisés enn version AC 90 – 280 V
22
MN05401009E
Fusible de protection:
en DC:
en 230 VAC:
en 115 VAC:
en 48 VAC:
en 24 VAC:
0,125 A temporisé
0,05 A temporisé
0,1 A temporisé
0,2 A temporisé
0,4 A temporisé
Insensibilité aux parasites:
EN 55011 classe B et
50082-2, avec câblage blindé
Température de service:
0…50°C
Température de stockage:
–25°C…+70°C
Poids:
env. 240 g (en version AC et relais)
Protection: IP 65 par lʼavant
français
Teinte du boîtier:
noir
Nettoyage: La façade de lʼappareil peut être nettoyée
avec un chiffon doux humecté dʼeau.
11. Fournitures incluses à la livraison
– Compteur
– Connecteur à vis débrochable, 7 pôles,
écartement 5,08 mm
– Connecteur à vis débrochable, 7 pôles,
écartement 3,81 mm
– Cadre frontal à fixation par vis, découpe 50 x 50 mm
– Cadre frontal à fixation par étrier, découpe 50 x 50 mm
– Etrier de fixation
12. Codification de commande
E5148C142X
1 = 90 ... 260 V AC
2 = 10 ... 30 V DC
MN05401009E
23
Dimensions :
max. 10.5 [0.41]
48 [1.89]
45 [1.77]
48 [1.89]
86.5 [3.41]
3 [0.12]
15.5
[0.61]
Découpe 45 x 45 mm
55 [2.17]
50 [1.97]
55 [2.17]
45 [1.77]
max. 9.5 [0.37]
85.5 [3.37]
Montré avec cadre frontal Nr. 2
Découpe 50 x 50 mm
4 [0.16]
15.5
[0.61]
60 [2.36]
Fraisage Bf4
DIN 74
Montré avec cadre frontal Nr. 3
Découpe 50 x 50 mm
50 [1.97]
75 [2.95]
63 [2.48]
45 [1.77]
max. 9.5 [0.37]
85.5 [3.37]
4 [0.16]
15.5
[0.61]
– Erreurs ou modifications réservées –
24
MN05401009E
2.4 Key
Bedienungsanleitung
Elektronischer Vorwahlzähler
E5148C142 Serie
R.600.300
Statischer Tastaturverriegelungseingang.
Solange dieser Eingang aktiviert ist, kann der Zähler
nicht zurückgesetzt oder die Vorwahl verändert werden.
3. Anzeige
—— Zählerstand
1. Beschreibung
Zähleingänge. Die max. Zählfrequenz dieser beiden
Eingänge ist über die Programmierschalter C und D (an
der rechten Seite des Zählergehäuses) auf 30 Hz oder
10 kHz einstellbar.
Relais mit potentialfreiem Wechselkontakt oder
Optokoppler mit offenem Emitter und Kollektor
Aktiver Ausgang wird auf dem Display mit
1
angezeigt
Für Sicherheitsschaltungen kann die Relais- bzw.
Optokoppleransteuerung invertiert werden, d.h. die
Relaisspule wird bei Erreichen der Vorwahl
spannungslos, bzw. der Optokoppler gesperrt.
Hierzu muß in der Programmierroutine das
Ausgangssignal Out1 bei Dauersignal auf –l– und bei
Wischsignal auf –l–l– eingestellt werden.
Achtung: Bei den Betriebsarten mit automatischer
Wiederholung (AddAr, SubAr) muß für den Ausgang
eine Wischzeit programmiert werden, da sonst das
Ausgangssignal keine definierte Länge hat (siehe
Programmierung).
b. Programmierschalter „A“ (an der rechten Seite des
Zählergehäuses) kurzzeitig auf „ON“ stellen. Auf
dem Display wird der 1. Menüpunkt „Mode“
angezeigt.
c. Mit der
A B C D
D
C
4. Ausgang
a. Spannungsversorgung einschalten
2.1 INP A, INP B
Mikroschalter
Symbol für aktiven Ausgang
5. Einstellung des Betriebsparameter
2. Eingänge
OFF
ON
—— Vorwahlwert
deutsch
– 6stelliger add./subtr. Vorwahlzähler mit einer Vorwahl
– gut ablesbare 2-zeilige LCD-Anzeige mit Symbolen für
die angezeigte Vorwahl und den Zustand des
Ausgangs.
– Zähl- und Vorwahlbereich –999999 bis 999999
Über- oder Unterlauf ohne Zählverluste bis jeweils
1 Dekade, hierbei blinkt die Anzeige im s-Takt
– programmierbar als Impuls-, Frequenz- oder Zeit- bzw.
Betriebsstundenzähler
– Relais- oder Optokopplerausgang
– Die Programmierung der Zählfunktionen bzw. Betriebsparameter erfolgt über die Einstelltasten.
Bedienerführung auf dem Display während der Programmierroutine.
– programmierbar sind:
Betriebsart (Ausgangssignal bei Null oder Vorwahl,
mit oder ohne automat. Wiederholung)
Dezimalpunkt
Polarität der Eingänge (NPN oder PNP)
Eingangsart und Faktor
Ausgangssignal als Dauer- oder Wischsignal
Torzeit bei Programmierung als Frequenzzähler,
Auflösung in s, min, h oder h:min:s als Zeitzähler
– Spannungsversorgung 230 VAC, 115 VAC, 48 VAC,
24 VAC oder 11…30 VDC
INP A
30 Hz
10 kHz
ON
OFF
INP B
30 Hz
10 kHz
ON
OFF
2.2 Gate
Statischer Toreingang; keine Zählung solange dieser
Eingang aktiviert ist.
In der Betriebsart Zeitzähler blinkt bei nichtaktiviertem
Toreingang der Dezimalpunkt zwischen der 5. und
6. Dekade (Laufanzeige bei Zeiteinheiten h, min oder
0,1 min).
-Taste die gewünschte Funktion auswählen
d. Mit der P-Taste wird der eingestellte Wert
übernommen und auf den jeweiligen nächsten
Menüpunkt weitergeschaltet.
e. Erneut mit der -Taste die gewünschte Funktion
bzw. Zählerwerte (Faktor, Wisch- oder Torzeit, Auflösung) direkt über die beiden Pfeiltasten eingeben.
f.
Nach dem letzten Menüpunkt (Dauersignal oder
Wischsignal) wird mit der P-Taste die Programmierroutine verlassen (Programmierschalter „A“ auf
„OFF“). Falls Schalter „A“ noch auf „ON“ geschaltet
ist, wird die Programmierroutine nochmals durchlaufen.
OFF
ON
A B C D
2.3 Reset
Dynamischer Rücksetzeingang; er ist mit der roten SetTaste parallel geschaltet und setzt den Zähler bei add.
Zählweise auf Null, bei subtr. Zählweise auf den
Vorwahlwert.
MN05401009E
25
6. Einstellung der Betriebsart
6.1 Einstellung der Grundbetriebsart.
Nach kurzzeitigem Umschalten des Programmierschalters „A“ auf „ON“ erscheint eines der folgenden
Bilder auf dem Display:
Programmierroutine
Impulszähler
Programmierroutine
Zeitzähler
Programmierroutine
Frequenzzähler
6.2.1 Programmierroutine Impulszähler
Betriebsart Add:
Zähler arbeitet addierend
Dauersignal bei Zählerstand ≥
Vorwahl oder Wischsignal bei
Zählerstand ≥ Vorwahl
Reset auf Null
Betriebsart Sub:
Zähler arbeitet subtrahierend
Dauersignal bei Zählerstand ≤ Null
Wischsignal bei Zählerstand ≤ Null
Reset auf Vorwahl
Betriebsart Add Ar:
Zähler arbeitet addierend
Wischsignal bei Zählerstand =
Vorwahl
automatisches Nullsetzen
Betriebsart Sub Ar:
Zähler arbeitet subtrahierend
Wischsignal bei Zählerstand = Null
automatisches Setzen auf Vorwahl
Polarität der Eingänge
pospol: positive Polarität (PNP)
nach +24 V schaltend
negpol: negative Polarität (NPN)
nach 0V schaltend
Eingangsart:
E1: INP A = Zähleingang
INP B = Zählrichtungseingang
Faktor:
0,0001…9,9999
Einstellung mit den Tasten
und
Faktor 0,0000 wird nicht
akzeptiert
Achtung! In den Betriebsarten
sub, sub Ar (Ausgangssignal bei
Zählerstand = Null) muß der
Vorwahlwert ganzzahlig durch
den Faktor teilbar sein,
andernfalls wird der Zähler bei
einem Reset auf das
nächstgrößere ganzzahlige
Vielfache des Faktors gesetzt.
Dezimalpunkt (nur anzeigend)
0
= keine Dezimalstelle
0,0 = 1 Dezimalstelle
0,00 = 2 Dezimalstellen
0,000 = 3 Dezimalstellen
Dauersignal des Ausgangs, wird
bei add. Zählung bei Zählerstand
≥ Vorwahl und bei subtr. Zählung
bei Zählerstand ≤ Null aktiv*
Dauersignal des Ausgangs, wird
bei add. Zählung bei Zählerstand
≥ Vorwahl und bei subtr. Zählung
bei Zählerstand ≤ Null passiv**
Wischsignal des Ausgangs, wird
bei add. Zählung bei Zählerstand
= Vorwahl und bei subtr. Zählung
bei Zählerstand = Null passiv**
Wischsignal des Ausgangs,wird
bei add. Zählung bei Zählerstand
= Vorwahl und bei subtr. Zählung
bei Zählerstand = Null aktiv*
Dauer des Wischsignals des
Ausgangs, einstellbar von 00,01 s
bis 99,99 s
* Relaisspule bzw. Optokoppler
werden bei Erreichen des
Vorwahlwertes angesteuert
** Relaisspule wird bei Erreichen
des Vorwahlwertes spannungslos
bzw. Optokoppler gesperrt.
E2: INP A = Zähleingang add.
INP B = Zähleingang subtr.
E3: Quadratureingang
INP A = Zähleingang 0°
INP B = Zähleingang 90°
E4: wie E 3, jedoch mit Impulsverdoppelung.
Jede Flanke von INP A wird
gezählt
26
MN05401009E
6.2.2 Programmierroutine Zeitzähler
Betriebsart Sub:
Zähler arbeitet subtrahierend
Dauersignal bei Zählerstand ≤ Null
Wischsignal bei Zählerstand = Null
Reset auf Vorwahl
Betriebsart Add Ar:
Zähler arbeitet addierend
Wischsignal bei Zählerstand =
Vorwahl
automatisches Nullsetzen
Betriebsart Sub Ar:
Zähler arbeitet subtrahierend
Wischsignal bei Zählerstand =
Null
automatisches Setzen auf
Vorwahl
Polarität der Eingänge
pospol: positive Polarität (PNP),
nach +24 V schaltend
Dauersignal des Ausgangs,wird
bei add. Zählung bei Zählerstand
≥ Vorwahl und bei subtr. Zählung
bei Zählerstand ≤ Null aktiv *
Dauersignal des Ausgangs,wird
bei add. Zählung bei Zählerstand
≥ Vorwahl und bei subtr. Zählung
bei Zählerstand ≤ Null passiv**
Wischsignal des Ausgangs,wird
bei add. Zählung bei Zählerstand
= Vorwahl und bei subtr. Zählung
bei Zählerstand = Null passiv**
Wischsignal des Ausgangs,wird
bei add. Zählung bei Zählerstand
= Vorwahl und bei subtr. Zählung
bei Zählerstand = Null aktiv*
Dauer des Wischsignals des
Ausgangs,einstellbar von 00,01s
bis 99,99 s
* Relaisspule bzw. Optokoppler
werden bei Erreichen des
Vorwahlwertes angesteuert
** Relaisspule wird bei Erreichen
des Vorwahlwertes
spannungslos bzw. Optokoppler
gesperrt.
negpol: negative Polarität (NPN),
nach 0 V schaltend
Zeiteinheit:
Zählung in s; 0,1 s; 0,01 s oder
0,001 s*
Zählung in min; 0,1 min; 0,01
min*
oder 0,001 min
Zählung in h; 0,1 h; 0,01 h oder
0,001 h*
* je nach Stellung des Dezimalpunktes
Zählung in h: min: s
Dezimalpunkt (Auflösung)
0
= keine Dezimalstelle
0,0 = 1 Dezimalstelle
0,00 = 2 Dezimalstellen
0,000 = 3 Dezimalstellen
MN05401009E
27
deutsch
Betriebsart Add:
Zähler arbeitet addierend
Dauersignal bei Zählerstand ≥
Vorwahl oder Wischsignal bei
Zählerstand = Vorwahl
Reset auf Null
6.2.3 Programmierroutine Frequenzzähler
Torzeit = Zeit, innerhalb der
eingehende Impulse gezählt und
zur Anzeige gebracht werden.
Einstellbereich von 00,01 s bis
99,99 s
Einstellung über die Tasten und
00,00 wird als Einstellung nicht
akzeptiert
Polarität der Eingänge
pospol: positive Polarität (PNP),
nach +24 V schaltend
negpol: negative Polarität (NPN),
nach 0 V schaltend
Eingangsart:
E1: INP A = Zähleingang
INP B = Zählrichtungseingang
E2: INP A = Zähleingang add.
INP B = Zähleingang subtr.
E3: Quadratureingang
INP A = Zähleingang 0°
INP B = Zähleingang 90°
E4: wie E 3, jedoch mit
Impulsverdoppelung.
Jede Flanke von INP A wird
gezählt
Dauersignal des Ausgangs, wird
bei Zählerstand ≥ Vorwahl aktiv *
Dauersignal des Ausgangs, wird
bei Zählerstand ≥ Vorwahl
passiv**
Wischsignal des Ausgangs, wird
bei Zählerstand = Vorwahl
passiv**
Wischsignal des Ausgangs, wird
bei Zählerstand = Vorwahl aktiv*
Dauer des Wischsignals des
Ausgangs, einstellbar von 00,01 s
bis 99,99 s
* Relaisspule bzw. Optokoppler
werden bei Erreichen des
Vorwahlwertes angesteuert
** Relaisspule wird bei Erreichen
des Vorwahlwertes spannungslos
bzw. Optokoppler gesperrt.
Faktor:
0,0001…9,9999
Einstellung mit den Tasten und
Faktor 0,0000 wird nicht akzeptiert
Dezimalpunkt (nur anzeigend)
0
= keine Dezimalstelle
0,0 = 1 Dezimalstelle
0,00 = 2 Dezimalstellen
0,000 = 3 Dezimalstellen
28
MN05401009E
7. Vorwahleinstellung:
8. Anschlußbeispiele
Wird eine der Pfeiltasten betätigt, ist die
Vornullenunterdrückung ca. 4 Sekunden aufgehoben
und die rechte Dekade der Vorwahl blinkt im 1-HzRhythmus.
Mit der -Taste wird der Wert der blinkenden Dekade in
steigender Reihenfolge verändert. Mit der -Taste wird
die nächst höhere Dekade angewählt. 4 Sekunden nach
der letzten Tastenbetätigung wird automatisch die
Vornullenunterdrückung aktiv.
In den Betriebsarten Impulszähler und Frequenzzähler
wird jetzt der neue Wert übernommen.
Ansteuerung über Kontakt
programmierte Polarität PNP
Einstellung in der 6. Dekade
Mit der -Taste das Vorzeichen anwählen; das
Vorzeichen erscheint blinkend vor dem aktuellen
Zählerstand. Mit der -Taste wird das Vorzeichen dem
Vorwahlwert zugeordnet bzw. entfernt.
4 Sekunden nach der letzten Tastenbetätigung wird die
Vornullenunterdrückung aktiviert und Vorwahl und
Zählerstand mit dem entsprechenden Vorzeichen
angezeigt.
Achtung: Bei automatischer Wiederholung dürfen keine
negativen Vorwahlwerte eingestellt werden!
Ansteuerung über Lichtschranke
deutsch
7.1 Einstellung des Vorzeichens
Ansteuerung über Drehgeber
MN05401009E
29
9. Anschlußbelegung
10. Technische Daten
Spannungsversorgung:
90…260 VAC, 48 VAC, 24 VAC,
50/60 Hz, ±10%,
max. 4 VA
oder 11…30 VDC,max. 0,1 A
Anzeige:
6stellige, 2zeilige 7-Segment-LCD-Anzeige
mit Vorzeichen
Istwert 9 mm hoch, Vorwahl 7 mm hoch
Symbole für angezeigte Vorwahl und
Ausgangskontakt geschlossen
Polarität der Eingangssignale:
programmierbar; für alle Eingänge
gemeinsam
Eingangswiderstand:
ca. 10 kOhm
9.1 Steckerbelegung X1
Klemme
Nr.
1
2
3
4
5
6
7
AC-Version
DC-Version
nicht belegt
nicht belegt
Relaisausgang gemeinsamer Kontakt (C)
Optokopplerausgang Emitter
Relaisausgang Schließer (NO)
Relaisausgang Öffner (NC)
Optokopplerausgang Kollektor
90…260 VAC/
11…30 VDC
48 VAC/24 VAC
Betriebsspannung
90…260 VAC
0 VDC (GND)
48 VAC/24 VAC
Achtung! Bei Einstellung –l– und –l–l– (invertierte Relaisoder Optokoppleransteuerung) ändern sich die
Anschlüsse der Klemmen 4 und 5
Klemme AC- und DC-Version
Nr.
4
Relaisausgang Öffner (NC)
5
Relaisausgang Schließer (NO)
9.2 Steckerbelegung X2
Klemme Benennung Funktion
Funktion
Nr.
90…260 VAC
11…30 VDC48 VAC/24 VACVersion
Version
1
+ 24 VDC Geberversorgungs- nicht belegt
spannung
2
GND
0 VDC Bezugsnicht belegt
spannung
3
INP A
Zähleingang A
4
INP B
Zähleingang B
5
RESET
Rücksetzeingang
6
GATE
Toreingang
7
KEY
Tastaturverriegelungseingang
Zählfrequenz:
über DIL-Schalter für INP A und INP B
separat einstellbar
30 Hz
10 kHz (7 kHz bei Eingangsart E3 und E4
Quadratureingang)
bei automatischer Wiederholung 900 Hz
ohne Zählverluste (500 Hz bei Eingangsart
E4)
Mindestimpulszeit der Steuereingänge:
5 ms
Schaltpegel der Eingänge:
Bei AC-Spannungsversorgung
Log „0“: 0… 4 VDC
Log „1“: 12…30 VDC
Bei DC-Spannungsversorgung Ub
Log „0“: 0…0,2 x Ub
Log „1“: 0,6 x Ub…30 VDC
Ub = Netzspannung
Impulsform: beliebig, da Schmitt-Trigger-Eingänge
Ausgang:
Relais mit potentialfreiem Schaltkontakt,
Schaltspannung max. 250 VAC/300 VDC
Schaltstrom max. 3 A
Schaltstrom bei DC min. 30 mA
Schaltleistung max. 50 W bei DC
max. 2000 VA bei AC
oder
Optokoppler mit offenem Kollektor und
Emitter
Schaltleistung: 30 VDC/15 mA
Vce sat bei Ic = 15 mA: max. 2,0 V
Vce sat bei Ic = 5 mA: max. 0,4 V
Ansprechzeit des Ausgangs:
Relais:
ca. 6 ms
Optokoppler: ca. 1 ms
Datensicherung:
min. 10 Jahre oder 106 Speicherzyklen
Geberspannung:
24 VDC –40% / +15 %, 80 mA
unstabilisiert bei 24 + 48 VAC-Ausführung
24 VDC –40% / +15 %, 100 mA
unstabilisiert bei 90…260 VAC-Ausführung
30
MN05401009E
Absicherung:
empfohlene externe Sicherung
bei DC:
0,125 A, zeitverzögert
90…260 VAC: 0,05 A, zeitverzögert
bei 48 VAC: 0,2 A, zeitverzögert
bei 24 VAC: 0,4 A, zeitverzögert
Störfestigkeit:
EN 55011 Klasse B und EN 50082-2
mit geschirmten Dateneingängen
Umgebungstemperatur:
0…50°C
Lagertemperatur:
–25°C…+70°C
Gewicht:
ca. 240 g (AC-Ausführung mit Relais)
Schutzart:
IP 65 von vorne
Gehäusefarbe:
schwarz
Reinigung: Die Frontseite des Gerätes darf nur mit
einem weichen, mit Wasser angefeuchteten
Tuch gereinigt werden.
11. Lieferumfang
deutsch
– Zähler
– Schraubsteckklemme 7polig, Rastermaß 5,08 mm
– Schraubsteckklemme 7polig, Rastermaß 3,81 mm
– Frontrahmen für Schraubbefestigung
Einbauquerschnitt 50 x 50 mm
– Frontrahmen für Spannbügelbefestigung
Einbauquerschnitt 50 x 50 mm
– Spannbügel
12. Bestellschlüssel
E5148C142X
1 = 90 ... 260 V AC
2 = 10 ... 30 V DC
MN05401009E
31
Maßbilder:
max. 10.5 [0.41]
48 [1.89]
45 [1.77]
48 [1.89]
86.5 [3.41]
55 [2.17]
max. 9.5 [0.37]
50 [1.97]
45 [1.77]
55 [2.17]
3 [0.12]
15.5
[0.61]
Einbauquerschnitt 45 x 45 mm
85.5 [3.37]
Mit Frontrahmen abgebildet Nr. 2
Einbauquerschnitt 50 x 50 mm
4 [0.16]
15.5
[0.61]
60 [2.36]
50 [1.97]
63 [2.48]
45 [1.77]
75 [2.95]
max. 9.5 [0.37]
85.5 [3.37]
4 [0.16]
Mit Frontrahmen abgebildet Nr. 3
Einbauquerschnitt 50 x 50 mm
15.5
[0.61]
– Änderungen vorbehalten –
Eaton Corporation
Electrical Group
1000 Cherrington Parkway
Moon Township, PA 15108
United States
877-ETN CARE (877-386-2273)
Eaton.com
© 2007 Eaton Corporation
All Rights Reserved
Printed in USA
Publication No. MN05401009E/CPG
March 2007