Crowcon IRmax Installation, Operating And Maintenance Instruction

Tipo
Installation, Operating And Maintenance Instruction
IRmax
Installation, operating and maintenance instructions
Instructions d’installation, d’utilisation et de maintenance
Installations-, Bedienungs- und Wartungsanleitung
Instrucciones de instalación, operación y mantenimiento
Istruzioni d’installazione, uso e manutenzione
Installatie-, bedienings- en onderhoudsinstructies
Instrukcje montażu, obsługi i konserwacji
Instruções de instalação, funcionamento e manutenção
M07028
Issue 6 Oct 2017
Infrared hydrocarbon gas detector
Contents
Concept and safety ...................................................................................... 1
IRmax concept ..................................................................................... 1
Safety information................................................................................. 2
Product overview................................................................................... 3
1. Introduction ............................................................................................. 4
1.1 General ........................................................................................... 4
1.2 Product description ......................................................................... 4
2. Installation ................................................................................................ 6
WARNING ............................................................................................. 6
2.1 Location .......................................................................................... 6
2.2 Mounting ........................................................................................ 7
2.3 Cabling directly to IRmax .............................................................. 7
2.3.1 Terminal designation .............................................................. 8
2.3.2 Installing IRmax using a mounting bracket ............................ 8
2.4 Installing using a spigot gland and auxiliary junction box ................ 9
2.4.1 To fit IRmax to an auxiliary junction box: ............................. 10
2.5 Cabling requirement ..................................................................... 10
2.6 Connections and settings .............................................................. 11
3. Operation ............................................................................................... 12
3.1 Commissioning procedure ............................................................. 12
3.2 Routine maintenance .................................................................... 13
3.3 Changing gas types ...................................................................... 13
3.4 Relative responses of gas types ..................................................... 14
4. Specification ........................................................................................... 15
5. Accessories and spare parts .................................................................... 16
6. Fault finding .......................................................................................... 17
6.1 Errors signalled by LED .................................................................. 17
6.2 Analogue Output .......................................................................... 17
7. RS485 Modbus configuration ................................................................. 18
7.1 General ......................................................................................... 18
7.2 Wiring topology ............................................................................ 19
7.2.1 Star connection .................................................................... 19
7.2.2 Linear bus connection .......................................................... 19
7.3 Cabling requirements .................................................................... 20
7.3.1 Calculating the minimum level of power required ............... 20
7.3.2 Sample calculation ............................................................... 20
8. Functional Safety Manual ....................................................................... 21
8.1 Introduction .................................................................................. 21
8.2 IRmax and IRmax Modbus Safety Function .................................... 21
8.3 Functional Safety Data .................................................................. 21
8.4 Hardware Configuration ............................................................... 22
8.5 Software Configuration ................................................................. 22
8.6 Systematic Failures ........................................................................ 22
8.7 Diagnostic Interval ......................................................................... 22
8.8 Constraints ................................................................................... 22
8.9 Environmental ............................................................................... 23
8.10 Hardware fault tolerance............................................................. 23
8.11 Systematic Capability .................................................................. 23
8.12 Classification ............................................................................... 23
Warranty .................................................................................................... 24
1
Detecting Gas Saving Lives
English
Concept and safety
IRmax concept
IRmax is an ultra-compact infrared (IR) gas detector, which delivers rapid, fail-safe detection
of hydrocarbon gases and vapours.
Featuring dual-wavelength IR sensor technology in a rugged 316 stainless steel package,
IRmax is designed to operate in the harshest conditions. Unlike conventional IR gas detectors,
IRmax does not incorporate heaters to prevent condensation on windows and mirrors. The
Stay clIR coating on optical components prevents condensation forming while the detector is
operating.
IRmax is compatible with any 4-20mA control system, and can also be installed in an RS485
Modbus addressable network (see Section 7).
IRmax requires only 1 Watt of power, typically 75-90% lower than conventional IR gas detectors.
IRmax features a compact diffusion gas chamber, which in combination with an effective
weatherproof cap provides excellent speed of response. The weatherproof cap has been
designed using flow modelling software to enable remote gassing and calibration of the
IRmax without requiring a special calibration cap.
The IR Display makes it possible to monitor readings from the IRmax both locally and
remotely. An IR Display can be fitted directly to IRmax. Alternatively, IRmax may be
supplied with an Intrinsically Safe (IS) Barrier module attached. An IR Display can then
be connected to the IS Barrier Module via temporary or permanent cabling. The available
options are illustrated on Diagram 3, page 5.
For further information about other accessories for the IRmax see Diagram 3 on page 5 and
Section 5, page 16.
Concept and safety
2
Detecting
Gas Saving Lives
English
Safety information
IRmax gas detectors must be installed, operated and maintained in strict accordance
with these instructions, warnings, label information, and within the limitations stated.
The rear nut on IRmax must be kept tightly closed during operation. Do not attempt
to remove the rear nut until power to the detector is isolated - otherwise ignition
of a flammable atmosphere can occur. Before removing the nut for maintenance,
calibration or servicing, check that the surrounding atmosphere is free of flammable
gases or vapours. Do not open until several minutes after the power has been removed.
Maintenance and calibration operations must only be performed by qualified service personnel.
Only genuine Crowcon replacement parts must be used; substitute components may
invalidate the certification and warranty of the IRmax.
IRmax must be protected from extreme vibration, and direct sunlight in hot
environments as this may cause the temperature of the IRmax to rise above its specified
limits and cause premature failure.
IRmax will not detect hydrogen, ammonia or carbon dioxide.
The equipment must be earthed using the cable gland and steel armoured cable.
Certification for Zone 21/22 dust environments: IRmax basic (without IR Display or
IS Barrier module) may be used in environments that may contain hazardous dusts
(Zones 21 or 22).
IRmax with an IS Barrier module may be used in Zones 21 or 22 provided the ambient
temperature remains below 40°C and a remote IR Display or Hand-Held IR Displays are
installed/used outside the hazardous area only.
IRmax with a Fixed IR Display cannot be installed in a Zone 21 or 22 area.
Concept and safety
3
Detecting
Gas Saving Lives
English
Product overview
IRmax is an infrared gas detector designed for detecting common hydrocarbon gases in
the range 0 to 100%LEL (Lower Explosive Limit: the minimum concentration in air at which
ignition can occur).
IRmax is a certified Flameproof (Exd) detector suitable for use in ATEX Zone 1 or Zone 2
hazardous areas. Please refer to the certification label on the side of the Detector to identify
the type of certification that relates to the product supplied.
Note: if no certification label is fitted to the IRmax, the detector is not certified for
use in hazardous areas.
Diagram 1: IRmax certification labels
0811
.TNESERP EB YAM EREHPSOMTA EVISOLPXE NEHW NEPO TON OD :GNINRAW
04- = bmaT( bG 4T CII bd xE 57+ ot C )C
W5=xamW V23=xamV
04- = bmaT
( bG 6T CII bd xE 05+ ot C )C
X9010.90 SAB xECEI X6020XETA90afeesaB
X6021XETA21 ariS 2LIS
DS4 41XO ,modgniK deitnU ,nodgnibA
DG2 II
ROTCETED SAG RI
)C°57+ aT C°04-( bD C°531T CIII bt xE
°°
°
°
IRmax Basic certification label
Ex db ia IIC T4 Gb (-40°C Ta +75°C)
Vmax=32V Wmax=5W
WARNING: DO NOT OPEN WHEN EXPLOSIVE ATMOSPHERE MAY BE PRESENT.
IR G A S DET E C TOR W I TH R E M OTE D I SPL A Y
Baseefa09ATEX0220X IECEx BAS 09.0104X
Abingdon, United Kingdom, OX14 4SD
1180
II 2GD
Ex tb ia IIIC T135
°C Db (-40°C Ta +40°C)
IRmax with IS Barrier certification label
+75°C)Ex db ia IIC T4 Gb (-40°C Ta
II 2G
1180
Abingdon, United Kingdom, OX14 4SD
Baseefa09ATEX0220X IECEx BAS 09.0104X
IR GA S DE TECT OR WI TH D ISPL AY
WARNING: DO NOT OPEN WHEN EXPLOSIVE ATMOSPHERE MAY BE PRESENT.
Vmax=32V Wmax=5W
IRmax with Fixed IR Display certification label
4
Detecting
Gas Saving Lives
English
1. Introduction
1.1 General
The configuration of each IRmax is identified by a label fitted on the main body. Please
quote the product name, part number and serial number when contacting Crowcon for
advice or spares.
1.2 Product description
IRmax consists of a main body of 316 stainless steel, an antistatic weatherproof cover
over the optics and gas measurement chamber and an electronics assembly. An IR Display
Module can also be fitted. Instructions for fitting the IR Display appear in the IR Display
manual (M07061).
An optional connection spigot gland can be supplied to allow IRmax to be fitted directly
to auxiliary junction boxes with either M20 or ½” NPT cable entries.
All dimensions in millimetres
Diagram 2: IRmax dimensioned view
Note: The IRmax body is supplied with two cable entries; one is M20, one is 1/2"
NPT. The cable entry not specified when ordering an IRmax will be sealed using
a certified plug. The IRmax must be installed with both cable entries sealed: one
with a cable gland, the other with a certified IP66 rated stopping plug.
157.5
74.5
136
60.5
Optional spigot gland
57
Overall
158 Overall
74.5
136 Overall
M20 or 1/2" NPT
cable gland
External
grounding
terminal
(earth)
1. Introduction
5
Detecting
Gas Saving Lives
English
Diagram 3: IRmax exploded view (part numbers shown where applicable)
Calibration cap M041007
Weatherproof cap M04995
Mirror retainer
Mirror
Flow adaptor S012996
O-ring for back-nut, IS Barrier Module or Fixed IR Display Module: M040077
Mounting bracket as complete assembly S012130
Spigot gland M20 or 1/2"NPT versions : M20 ATEX: S012147, 1/2" NPT ATEX: S012190
Retaining plate and bolts for rear plug, Fixed IR Display and IS Barrier module
10
IR Display fixed version
11
IR Display to IRmax connector E07987
12
IS Barrier Module
13
IR Display connecting lead
14
Remote IR Display mounting bracket M03833
15
Remote IR Display
10
11
12
13
14
15
}
Supplied together as ‘mirror replacement kit’
C011206
6
Detecting
Gas Saving Lives
English
2. Installation
WARNING
This detector is designed for use in Zone 1 and Zone 2 hazardous areas.
Certification is dependent upon the accessories fitted and ambient operating
temperature. Please refer to the specifications table on page 15 for
certification details. Installation must be in accordance with the recognised
standards of the appropriate authority in the country concerned.
For further information please contact Crowcon. Prior to carrying out any
installation work ensure local regulations and site procedures are followed.
The equipment must be earthed using the cable gland and steel armoured cable.
Do not attempt to fit an IR Display to an IRmax not supplied for the purpose.
Detectors supplied for use with a display are certified Exd ia, and must be
operated either with a Fixed Display containing an IS barrier, or with a Remote
IR Display or IS Hand-Held Calibrator connected via a Crowcon IS Barrier module.
Detectors supplied without a display are certified Exd IIC and cannot be retro-
fitted for use with an IR Display.
2.1 Location
The IRmax should be mounted where the gas to be detected is most likely to be present.
The following points should be noted when locating gas detectors:
To detect gases which are lighter than air, such as methane, detectors should be
mounted at high level. To detect heavier-than-air gases, such as flammable vapours,
detectors should be mounted at low level.
When locating detectors consider the possible damage caused by natural events
e.g. rain or flooding. For detectors mounted outdoors in very hot regions Crowcon
recommend the use of a sunshade (see Section 5, Accessories and spare parts, on
page 16).
Consider ease of access for functional testing and servicing.
Consider how the escaping gas may behave due to natural or forced air currents.
Mount IRmax in ventilation ducts if appropriate (see Section 5, Accessories and spare
parts, on page 16).
Consider the process conditions. For example, butane is normally heavier than air, but
if released from a process which is at an elevated temperature and/or pressure, the
gas may rise rather than fall.
The placement of sensors should be determined following advice of experts having specialist
knowledge of gas dispersion and the plant processing equipment as well as safety and
engineering issues. The agreement reached on the locations of sensors should be recorded.
2. Installation
7
Detecting
Gas Saving Lives
English
2.2 Mounting
IRmax can be mounted in three ways:
1. Using the Crowcon mounting bracket with direct field cable connection (4-20mA
operation only).
2. Using a spigot gland to connect to an existing Exe or Exd certified junction box. Crowcon
supplies a suitable spigot gland as an optional extra (see 3 below).
3. Using the optional Crowcon auxiliary junction box and spigot gland.
Optional parts are listed in Section 5 on page 16.
IRmax should be installed at the designated location with the sensor barrel horizontal
+/- 15° (orientation shown on Diagram 2 on page 4). This ensures that dust or water
will not collect on the optical components.
2.3 Cabling directly to IRmax
This option is suitable for 4-20mA operation only. A Crowcon mounting bracket is required
to retain the detector to a wall or 2” (50 mm) pipe.
Diagram 4: Field cable connections on the IRmax
Connect field cables using a certified gland via the chosen cable entry on the IRmax body
(M20 or 1/2" NPT), as indicated in Diagram 4. Crowcon recommends cable glands are
installed pointing downwards.
Ensure that cable glands with the appropriate
Exd certification are used, and that the thread
length does not exceed the length specified in the
diagram (left).
Signal
0V (ground)
+V (24V IRmax)
15mm MAX
Status LED
2. Installation
8
Detecting
Gas Saving Lives
English
2.3.1 Terminal designation
With the IRmax oriented as shown in Diagram 2 on page 4 (M20 cable entry at the
top), the 3-core field cable should be terminated using the removable connector as follows:
+24V at the bottom, 0V in the middle, Signal at the top.
The 6-pin connector on the right of the PCB is for servicing and/or connection of an
IR Display module
+ve terminal: +ve supply from the control card.
Sig terminal: Signal/Sense from control card.
0 V terminal: -ve supply from the control card.
2.3.2 Installing IRmax using a mounting bracket
a. IRmax can be supplied with a mounting bracket (S012130) rather than a spigot
gland so that it can be directly connected to field cables (see Diagram 5).
Diagram 5: IRmax with a mounting bracket and cable gland
b. If the IRmax is to be mounted on a flat surface, mark and drill two holes using
the mounting bracket as a template. Loosely fix two parts of the bracket using
fixings suitable for the wall/surface.
c. Remove the weatherproof cap from the IRmax, and slide the body of the IRmax
through the bracket. It is recommended that the IRmax body is installed with the
cable entry facing downwards.
Mounting bracket: 70mm
between fixing centres.
Use M6 bolts
2. Installation
9
Detecting
Gas Saving Lives
English
d. Secure the two bracket fixings so that the IRmax is held firmly in place. Re-fit the
weatherproof cap.
e. Once the IRmax is securely fixed in place, remove the IRmax rear nut to enable
access to the cable terminals.
f. Prepare the field cable – Crowcon recommends 1.5 mm
2
Steel Wire Armoured
(SWA) cable. Other cable types may be used provided they are compatible
with Exd certified glands. Fit a suitably certified Exd cable gland, pass the cable
conductors through the body of the IRmax and screw in the cable gland. Secure
the gland and ensure the cable armour is grounded to the cable gland and the
IRmax body. NB. Don’t forget to re-fit the rear nut after installing the cable.
g. The retaining plate (item 9 on Diagram 3, page 5) must be securely fitted
to prevent any risk of the rear nut (or Fixed IR Display or IS Barrier module
accessory) vibrating loose.
2.4 Installing using a spigot gland and auxiliary
junction box
This option is required where IRmax is to be connected to an existing Exd or Exe certified
auxiliary junction box.
Diagram 6: IRmax connected to the auxiliary junction box
2. Installation
10
Detecting
Gas Saving Lives
English
2.4.1 To fit IRmax to an auxiliary junction box:
a. Carefully remove the outer section of the spigot gland (item 8 in Diagram 3 on
page 5).
b. Screw the narrow end of the spigot gland into the auxiliary junction box.
c. Raise the IRmax to the auxiliary junction box and pass the wires through the
assembly and into the auxiliary junction box. Secure the IRmax by screwing the
collar tightly to the cable gland. Tighten grub screw.
d. The main body of the IRmax can be swivelled horizontally at any angle, provided
it is mechanically secure, does not interfere with other equipment and is
accessible for maintenance.
e. Refer to Section 2.6 for instructions on wiring. See also Diagram 4 on page 7.
2.5 Cabling requirement
Cabling to IRmax must be in accordance with the recognised standards of the appropriate
authority in the country concerned and meet the electrical requirements of the IRmax.
Crowcon recommends the use of steel wire armoured (SWA) cable and suitable explosion
proof glands must be used. Alternative cabling techniques, such as steel conduit, may be
acceptable provided appropriate standards are met.
The maximum recommended cable length is 3.4 km (see Table 1).
IRmax requires a dc supply of 12-30Vdc. Ensure there is a minimum of 12V at the IRmax
from the control panel, taking into account the voltage drop due to cable resistance at a
peak current of 0.1A.
A 1.5mm
2
cable will typically allow cable runs up to 3.0km. Table 1 below shows the
maximum cable distances for typical cable parameters.
C.S.A. Resistance Max. Distance
>20 V
Max. Distance
18 to 20 V
mm
2
(Ohms per km) (km) (km)
1.0 18.4 2.2 1.6
1.5 13.0 3.0 2.3
2.5 11.5 3.4 2.6
Table 1: Maximum cable distances for typical cables
2. Installation
11
Detecting
Gas Saving Lives
English
2.6 Connections and settings
All connections described are with reference to the terminal block mounted within IRmax
connector main body. The terminals on the IRmax connector PCB are marked ‘+’, ‘sig’
and ‘0 V’. Correct polarity should be observed when connecting the IRmax to control
equipment.
IRmax is factory set as a ‘current sink’ device unless otherwise specified when ordering. To
reset to ‘current source’, remove the back nut and move the two links on the terminal PCB
from the ‘sink position to the ‘source’ position, as shown in Diagram 7.
Note: The external grounding terminal is only to be used where local authorities
permit or require such a connection. Where possible, to limit radio frequency
interference, the auxiliary junction box and cable armour should be grounded at
the control panel (safe area) only to avoid earth loops.
Diagram 7: Sink/source jumper location
The 4-20mA signal can be set to current 'Sink' or 'Source' using the pins and jumper link
shown in Diagram 7. Set to current 'Sink' by fitting the jumper link to pins 3 and 4 as
shown on the left-hand photograph. Set to current 'Source' by fitting the jumper link to
pins 1 and 2 as shown on the right-hand photograph. IRmax will be set to current 'Sink'
unless specified otherwise when ordering.
LED indication: an LED is fitted to the terminal PCB to indicate the current
operating status. Refer to Section 6 on page 17 for more information.
CONTROLLER
EARTH
+V
0V
Sg
3
21
Wiring
Number Colour Function
1 Red +V
2 Black 0V
3 Green Signal
Jumper
settings
Sink
setting
Source
setting
IR Display
connector
PC communications
kit connector
Status LED
12
Detecting
Gas Saving Lives
English
3. Operation
WARNING
Prior to carrying out any work ensure local regulations and site procedures are
followed. Never attempt to open the IRmax or auxiliary junction box when
flammable gas is present. Ensure that the associated control panel is inhibited so
as to prevent false alarms.
3.1 Commissioning procedure
1. Check that:
a. The cable connections are correct
b. The supply voltage is set at the control card as 18 to 30 V. The voltage measured
at the IRmax terminals (within the Exe auxiliary junction box if used, or at the
IRmax terminal PCB) and must be set between 12 and 30 V.
c. The links are set for 4-20 mA sink or source as appropriate to control card.
2. Once powered up leave IRmax for 30 minutes before attempting zero/cal. This delay is
to ensure thermal stability. (Note: IRmax will be fully operational from 30 seconds
after power is applied.)
3. Ensure clean air (i.e. no hydrocarbon gas) before zeroing. Zero reading at control card
(refer to control card instructions).
4. Fit a calibration cap over weatherproof cover to isolate measurement chamber from
ambient air. Such a cap is available from Crowcon (M041007). Connect calibration gas
(50% LEL nom) and apply at 1 litre-per-minute flow.
5. After 30 seconds adjust cal/span on control card so that display reads 50% LEL, or
matches concentration of calibration gas applied. The IRmax itself should not require
calibration.
6. Remove gas and calibration cap. Re-check zero.
7. At installation, or after the mirror has been changed, the IRmax can be zeroed
and calibrated either using an IR Display accessory (see page 1) or via a PC
communications kit (see the IRmax Accessories manual).
Note: ATEX Certified IRmax will be supplied calibrated for compliance with
EN61779 (where, for example 100% LEL Methane = 4.4% volume).
Note: It is recommended that the calibration cap is used for initial commissioning.
Subsequent calibrations may be conducted by applying gas to the weatherproof
cap remotely via the pipe spigot (thus avoiding the need to directly access the
IRmax). Calibration without the calibration cap (i.e. directly via the weatherproof
cap) can be performed provided local windspeed is below 2 metres/second. The
flow rate of the gas must be greater than 2.0 litre/minute.
3. Operation
13
Detecting
Gas Saving Lives
English
3.2 Routine maintenance
Site practices will dictate the frequency with which detectors are tested. Crowcon
recommends that IRmax is gas tested at least every 6 months and re-calibrated as
necessary. To re-calibrate an IRmax follow the steps given in Section 3.1.
In the event of an electronic failure please consult your local Crowcon representative.
Calibration interval: Crowcon recommend calibration every 12 months.
Remote calibration via pipe: Wind speed should be less than 2.0 metres per second. If
greater, use the calibration cap to prevent gas dilution.
Cleaning of optics: Is not recommended unless the IRmax is in obscuration
fault. If the window or mirror become contaminated, clean
carefully with the IPA impregnated wipes and/or the soft
cloth supplied in the mirror cleaning kit (see Section 5,
Accessories and spare parts on page 16).
Mirrors: If the mirror is damaged, obtain a mirror replacement
kit (see Section 5, Accessories and spare parts on
page 16). The IRmax must always be re-zeroed and
re-calibrated after mirror replacement.
If condensation starts to cause faults replace mirror
(optical coating may be damaged). Crowcon recommends
replacing mirror every 5 years.
3.3 Changing gas types
Each IRmax is supplied pre-calibrated for a particular type of gas (for example methane
or propane). If re-calibration for a different gas type is required, the IRmax can be
re-configured using the PC communications kit (see Section 5, Accessories and spare
parts on page 16), and then calibrated.
3. Operation
14
Detecting
Gas Saving Lives
English
3.4 Relative responses of gas types
The graph below shows the relative responses to other gas types for an IRmax calibrated
on methane.
Note: many hydrocarbon gases and vapours are more easily detected by IR
detectors than methane. The response of IRmax (and other IR gas detectors) will be
linear across the 0-100%LEL range for the target gas (ie methane in this example),
but non-linear for other hydrocarbons that may also be present.
Diagram 8
The diagram shows the approximate response of the gases mentioned above: from left to
right, butane, propane, pentane, hexane & petrol vapour and methane.
Other gas types and ranges are available. Please contact Crowcon for further details.
15
Detecting Gas Saving Lives
English
4. Specification
Enclosure material 316 Stainless Steel
Dimensions
(Detector only)
158mm x 75mm x 57mm (6.2 x 2.9 x 2.3 ins) (without
spigot)
Weight IRmax 1.58kg (3.5lbs)
IRmax with Fixed IR Display 2kg (4.4lbs)
IRmax with IS Barrier Module 2.4kg (5.3lbs)
Remote IR Display 0.2kg (0.4lbs)
Operating voltage 12Vdc to 30V dc
Power < 1 W
Output 3-wire 4-20 mA (Sink or Source)
Fault signal <1 mA
Maximum cable loop
resistance
80 Ohms (relative to –ve terminal)
Operating temperature -40°C to +75°C (-40°F to +167°F)
Humidity 0–100% Relative Humidity
Degree of protection IP66
Explosion protection Flameproof
Approval code
ATEX
IRmax (without IR Display)
II 2 GD Exd db IIC T6 Gb (Tamb = -40°C to +50°C)
II 2 GD Exd db IIC T4 Gb (Tamb = -40°C to +75°C)
II 2 GD Ex tb IIIC T135°C Db (-40°C ≤ Ta≤ +75°C)
IRmax with IS Barrier module (remote display)
II 2 GD Exd db ia IIC T4 Gb (Tamb = -40°C to +75°C)
Ex tb ia IIIC T135°C Db (Tamb = -40°C to +40°C)
IRmax (with Fixed IR Display)
II 2 G Exd db ia IIC T4 Gb (Tamb = -40°C to +75°C)
Safety certificate no.
ATEX and IECEx
IRmax (without IR Display):
Baseefa 09ATEX0206X and IECEx BAS.09.0109X
IRmax (with IR Display):
Baseefa 09ATEX0220X and IECEx BAS.09.0104X
Functional Safety Certified for use in a SIL 2 system.
Certificate number: Sira 12ATEX1206X
Standards EN 60079-0:2012+A11:2013, EN 60079-1:2014,
EN 60079-31:2014
IEC 60079-0:2011, IEC 60079-1:2014, IEC 60079-31:2013
EN 60079-29-1:2007, IEC 61508:2010, EN50402:2005
Zones Certified for use in Zone 1 or Zone 2
EMC EN50270
16
Detecting
Gas Saving Lives
English
5. Accessories and spare parts
Part Numbers Name Description
M041007 Calibration cap Fits over the standard weathercap
to enable calibration where local air
speed exceeds 2 metres per second.
S012130 Mounting bracket kit Enables mounting to a wall or 2"
(50 mm) pipe. Not required if IRmax
is being fitted to an existing auxiliary
junction box.
S012152 Sun shade/Collector
cone
Can be fitted to IRmax to protect
against elevated temperatures due
to direct sunlight and/or to extend
the detectors footprint for detecting
lighter than air gases (e.g. methane).
S012169 Duct mounting kit Enables monitoring of ducts from
300 mm to 3000 mm, and air-flow
between 2 m/s and 20 m/s.
S012996 Flow adaptor For gas sampling applications.
S012827 PC communications
kit
Communications module, software
and lead to enable configuration of
the detector.
M20: S012295
½” NPT: S012296
Auxiliary junction box Mounting option for IRmax for use in
hazardous environments.
C011210 Mirror cleaning kit Contains IPA impregnated wipes and
microfibre cloth
IRmax Spares
Refer to Diagram 3 on page 5 for details of spare parts.
17
Detecting Gas Saving Lives
English
6. Fault finding
6.1 Errors signalled by LED
The LED fitted to the terminal PCB can help identify faults. Its position is shown on Diagram
7 on page 11. The table below shows how to interpret what is wrong for each pattern
of flashes.
LED Pattern Detector Status Action
Regular flash each second. Healthy.
On with short blips off. Detector in start-
up mode.
Wait 10 seconds.
Fast flash on and off or
irregular flash pattern.
Supply voltage
too low or too
high.
Ensure the IRmax supply voltage is
correctly set. Ensure measurement
is made directly at the detector
terminals.
Permanently on. Fault, host or
i-module error.
Power-cycle the IRmax, if fault
persists, return to Crowcon.
Two long flashes followed
by a short flash.
Fatal error; lamp
or detector fault.
Return to Crowcon.
Fast double flash each
second.
Fatal error,
module or
configuration
fault.
Check the detector configuration
using PC communications kit
software.
Check power supply.
If fault persists, return to Crowcon.
Short blip each second. Optics obscured. Check window and mirror, clean if
necessary. Re-zero IRmax and check
calibration.
Any other faults can only be rectified by returning the IRmax to Crowcon or authorised
service agent.
6.2 Analogue Output
IRmax will remain in Fault state and “Service required” will also be shown on the
IR Display (if fitted) if the analogue output signal has failed or is not connected to a
control system or load resistor. IRmax actively monitors the 4-20mA analogue output
signal to verify it is in range. If the signal is out of range the detector will go into fault
and the output will be set to 1mA. Thus, when testing a detector it is essential that it is
either connected to a control panel or a 100Ω load resistor is connected between the ‘0V’
and ‘Sig’ terminals (detector set to ‘Source’ mode) or between the ‘0V’ and ‘+V’ terminals
(detector set to ‘Sink’ mode).
18
Detecting
Gas Saving Lives
English
7. RS485 Modbus configuration
7.1 General
This section explains how to use IRmax detectors in a Modbus configuration. An RS485
enabled version is available for such applications. Up to 32 IRmax detectors can be linked
in star or bus configurations as described below.
Connections to the RS485 version of the IRmax must be made via a spigot gland to an
auxiliary junction box (see Section 5 on page 16), rather than by cabling directly into
the detector.
Please note that the IR Display cannot be used with RS485 enabled IRmax.
The RS485 enabled version of the IRmax has five field terminals . The terminals are:
1 Positive supply 12 V to 30 V above 0 V
2 0 V Return and RS485 reference
3 4-20 mA signal Source or Sink signal (optional)
4 RS485 B RS485 differential signal
5 RS485 A RS485 differential signal
The signals on the RS485 terminals conform to the EIA/TIA-485 standard, which means that
the common mode range is -7V to +12V with respect to the 0V terminal.
Note that not all RS485 manufacturers agree on the polarity of the A and B signals. If the
wiring does not work one way, users should switch the RS485 A&B wires. There is no risk
in making the wrong connection.
The communication settings are 9600 bps, two stop bits and no parity.
When compiling an interface for a control system, it is important to consider the amount of time it
takes for the system to collect information from each detector in turn. The fastest speed at which
multiple detectors can be polled is 14 detectors per second; practical conditions may reduce this to
7 per second. Users must ensure that the arrangement allows alarm signals to be registered within
acceptable time limits.
It is also important to ensure that the system can supply enough power to keep all the
detectors working. To calculate the amount of power required in a linear bus connection,
see Section 7.3, Cabling requirements, on page 20.
For full Modbus instructions, contact Crowcon (see addresses on back cover).
7. RS485 Modbus configuration
19
Detecting
Gas Saving Lives
English
7.2 Wiring topology
The two common wiring topologies in use are the star connection and the linear bus.
7.2.1 Star connection
In a star-connected topology all detectors are wired to a central point, which is usually the
control panel. No cables are required to have more than 5 cores as all the 4-20mA signal
connections are taken directly to the control panel.
The RS485 A and B signals can then all be connected together at the star point. The bus
should then be terminated at the star point with a single 110 ohm termination resistor.
The length of each arm of the star may not exceed 750 metres.
7.2.2 Linear bus connection
In a bus-connected topology all IRmax are wired to a linear arrangement, usually with the
control panel at one end. A classic situation is a tunnel installation, with IRmax installed at
regular intervals (see Diagram 9 below).
To wire the installation, two 110 ohm-terminating resistors should be fitted: one at each
physical end of the bus.
As the 4-20mA signals cannot be shared, an additional conductor is required on each wiring
hop. If none of the 4-20mA signals are being used, then only four conductors are required.
Diagram 9
7. RS485 Modbus configuration
20
Detecting
Gas Saving Lives
English
7.3 Cabling requirements
7.3.1 Calculating the minimum level of power required
The more IRmax detectors connected to the linear bus, the greater the power required
to run the system. To calculate the power required for a particular setup, it is necessary
to know the cable resistance between each pair of IRmax detectors. A current of at least
0.1mA must be allowed for each ‘hop’ between IRmax. The voltage to be applied can be
calculated by estimating the voltage drop across each ‘hop’ – at the end at least 12V must
remain to ensure that the last IRmax functions correctly.
Contact Crowcon for advice in specific cases. Alternatively, follow the steps outlined below
and the sample calculation shown in the next section.
1. The voltage must not fall below 12V, so start the calculation by setting the voltage at
the last IRmax in the line at that value.
2. Each IRmax may draw up to 0.1 A. Calculate the cable voltage loss of the first ‘hop’
between detectors by taking the ‘aggregate current’ to be 0.1A, and multiply this by the
cable resistance of the ‘hop’ between the last and the last but one IRmax.
3. Add this voltage drop to the initial 12V to get the lowest acceptable voltage at the last
but one IRmax. Add 0.1A to the value for the ‘aggregate current’ to get to 0.2mA, the
minimum current running through the last but one ‘hop’ of the bus. Multiply this by the
cable resistance for the last but one ‘hop’ to get the next voltage drop.
4. Repeat this process for each IRmax, accumulating the voltage losses that will occur
between each IRmax.
5. The maximum detector voltage of 30V must not be exceeded.
7.3.2 Sample calculation
As an example, here are the results of the calculation for six IRmax detectors spaced equally
250 m apart on cable with cross-sectional area of 1mm
2
. Each hop has a resistance of 4.6 ohms.
Station Supply voltage Supply current
1 12 0.1 A
2 12.46 0.2 A
3 13.38 0.3 A
4 14.76 0.4 A
5 16.6 0.5 A
6 18.9 0.6 A
Panel supply 21.66 0.6 A
21
Detecting Gas Saving Lives
English
8. Functional Safety Manual
8.1 Introduction
The following sections provide detail on the certification of IRmax in accordance with the
IEC 61508 and EN 50402 Functional Safety standards. Information is given on the features
considered in the safety case, maintenance requirements and data to enable IRmax to be
integrated into Safety Instrumented System (SIS).
8.2 IRmax and IRmax Modbus Safety Function
To measure the concentration of flammable gas and indicate the measurement by means
of a 4-20mA output.
Failures in respect of the safety function will be detected by the hardware and associated
firmware. They will be revealed as an output signal of less than 3.6mA or more than 21mA.
8.3 Functional Safety Data
Parameter name Symbol Equation / source IRmax
Proof Test Interval T1 As defined by Crowcon.
8,760 hours
(annual)
Mean Time To Repair MTTR As defined by Crowcon. 8 hours
Type A/B Type A As defined by Crowcon. Type B
Total failures:
λ
From FMEDA 1.04E-05
Safe diagnosed failures: λ
SD
From FMEDA 1.95E-08
Safe undiagnosed failures: λ
SU
From FMEDA 8.59E-08
Dangerous diagnosed failures: λ
DD
From FMEDA 9.74E-06
Dangerous undiagnosed failures: λ
DU
From FMEDA 5.06E-07
Safe no-effect failures: λ
NE
From FMEDA 3.21E-09
Diagnostic coverage: DC λ
DD
/ (λ
DU
+ λ
DD
) 95.06%
Safe Failure Fraction: SFF (λ
SD
+ λ
SU
+ λ
DD
) / λ 95.11%
Channel equivalent down time t
CE
DU
/ λ
D
)(T/2 + MTTR) +
(λ
DD
/ λ
D
) MTTR
2.24E+02
PFDAVG (using 61508-6
equation)
PFD
AVG
DU
+ λ
DD
) t
CE
2.30E-03
PFDAVG (using simplified
equation)
PFD
AVG
λ
DU
(T / 2+MTTR) + (λ
DD
MTTR) 2.30E-03
PFDAVG (using IEC 61508-6
equation)
PFD
AVG
1-ε
-(λdd+λdu) tce
2.30E-03
SIL capability (Low demand
mode)
SIL2
SIL capability (High demand
mode)
SIL2
For low demand applications, in respect of random hardware failures and safe failure
fraction, all variants of the system are suitable for use in SIL 2 applications.
Functional Safety Manual
22
Detecting
Gas Saving Lives
English
8.4 Hardware Configuration
Route 1H (Hardware fault tolerance and Safe Failure Fraction) has been used to assess
hardware safety integrity level.
8.5 Software Configuration
Assessment of the Product firmware has been made to the requirements given in IEC
61508:3 2010.
8.6 Systematic Failures
Route 1S (as specified in IEC 61508:2 2010 paragraph 7.4.2.2c) is used for compliance with
the requirements of avoidance of systematic failures.
8.7 Diagnostic Interval
Most diagnostic functions are continuously monitored.
Tests of the system watchdog are to be accomplished during the annual proof test by
power cycling the instrument: IRmax must be power-cycled annually (ie have the 24Vdc
supply removed and re-applied) as part of the maintenance programme for the product
(refer also to section 3.2).
8.8 Constraints
Failure rates are constant.
A proof test conducted at least once a year will identify all un-revealed failures.
Repairs have a mean time to repair of 8 hours.
It is assumed that the user makes use of that diagnostic facility provided via the IR Display
accessory and/or PC interface in order to minimise potential product down time.
Reliability assessment is a statistical process for applying historical failure data to proposed
designs and configurations. It therefore provides a credible target/estimate of the likely
reliability of equipment assuming manufacturing, design and operating conditions identical
to those under which the data was collected. It is a valuable design review technique for
comparing alternative designs, establishing order of magnitude performance targets and
evaluating the potential effects of design changes. The actual predicted values cannot,
however, be guaranteed as forecasting the precise number of field failures which will
actually occur, since this depends on many factors outside the control of a predictive
exercise.
Failure rates (symbol λ), for the purpose of this prediction, are assumed to be constant with
time. Both early and wear-out related failures would decrease the reliability but are assumed
to be removed by burn in and preventive replacement respectively.
Functional Safety Manual
23
Detecting
Gas Saving Lives
English
The Probability of failure on demand is the likelihood that the system will be in a failed
state at a random moment. This is synonymous with the steady state unavailability which
is given by:
Unavailability = (λ x MDT)/(1 + (λ x MDT))
which approximates to, λ x MDT for small values of λ x MDT
where λ is the failure rate and MDT is the Mean Down Time.
This is consistent with the expression for Availability given as: MTBF/(MTBF+MDT)
The failure rates used, and thus the derived availabilities are those credibly associated with
a well proven design after a suitable period of reliability growth.
8.9 Environmental
Environmental constraints:
The product shall be operated over a maximum ambient temperature range of
-40°C to +75 °C.
The product shall be stored over a maximum ambient temperature range of
-40°C to +80 °C.
The product shall be operated over a maximum ambient Relative Humidity range of
0% to +100 % Condensing.
The product has an Ingress Protection rating of IP66 according to the definitions within
standard EN60529.
The product is designed for continuous operation.
8.10 Hardware fault tolerance
The HFT is 0.
8.11 Systematic Capability
The IREX/IRmax is of Class SC2.
8.12 Classification
The IREX/IRmax is a type B component.
24
Detecting
Gas Saving Lives
English
Warranty
This equipment leaves our factory fully tested and calibrated. If within the warranty period
of three years from despatch, the equipment is proved to be defective by reason of faulty
workmanship or material, we undertake at our option either to repair or replace it free of
charge, subject to the conditions below.
Warranty Procedure
To facilitate efficient processing of any claim, contact our customer support team on
+44 (0)1235 557711 with the following information:
Your contact name, phone number, fax number and email address.
Description and quantity of goods being returned, including any accessories.
Instrument serial number(s).
Reason for return.
Obtain a Returns form for identification and traceability purposes. This form may be
downloaded from our website ‘crowconsupport.com’, along with a returns label.
Alternatively we can ‘email’ you a copy.
IRmax will not be accepted for warranty without a Crowcon Returns Number
(CRN). It is essential that the address label is securely attached to the outer
packaging of the returned goods.
The guarantee will be rendered invalid if the instrument is found to have been altered, modified,
dismantled, or tampered with. The warranty does not cover misuse or abuse of the unit.
Warranty Disclaimer
Crowcon accept no liability for consequential or indirect loss or damage howsoever arising
(including any loss or damage arising out of the use of the instrument) and all liability in
respect of any third party is expressly excluded.
This warranty does not cover the accuracy of the calibration of the unit or the cosmetic
finish of the product. The unit must be maintained in accordance with the instructions in
this manual.
The warranty on replacement consumable items (such as the mirror) supplied under warranty
to replace faulty items, will be limited to the unexpired warranty of the original supplied item.
Crowcon reserves the right to determine a reduced warranty period, or decline a warranty
period for any sensor supplied for use in an environment or for an application known to
carry risk of degradation or damage to the sensor.
Our liability in respect of defective equipment shall be limited to the obligations set out
in the guarantee and any extended warranty, condition or statement, express or implied
statutory or otherwise as to the merchantable quality of our equipment or its fitness for
any particular purpose is excluded except as prohibited by statute. This guarantee shall not
affect a customer’s statutory rights.
Warranty
25
Detecting
Gas Saving Lives
English
Crowcon reserves the right to apply a handling and carriage charge whereby units
returned as faulty, are found to require only normal calibration or servicing, which the
customer then declines to proceed with.
For warranty and technical support enquiries please contact:
Customer Support
Tel: +44 (0) 1235 557711
Fax: +44 (0) 1235 557722
TABLE DES MATIÈRES
Concept et sécurité .................................................................................... 29
Concept détecteur IRmax ........................................................................... 29
Informations de sécurité ............................................................................... 30
Présentation du produit ............................................................................... 31
1. Introduction ........................................................................................... 32
1.1 Générales ............................................................................................... 32
2. Installation .............................................................................................. 34
2.1 Implantation .......................................................................................... 34
2.2 Montage ................................................................................................ 35
2.3 Câblage direct vers le détecteur IRmax ................................................ 35
2.3.1 Désignation de bornes .................................................................. 36
2.3.2 Installation du détecteur IRmax à l’aide d’un support de fixation .... 36
2.4 Installation au moyen d’un presse-étoupes à ergot et d’un boîtier de
jonction auxiliaire ........................................................................................ 37
2.4.1 Pour poser le détecteur IRmax sur un boîtier de jonction auxiliaire : ...38
2.5 Exigences de câblage ............................................................................. 38
2.6 Raccordements et paramètres ................................................................ 39
3. Fonctionnement ..................................................................................... 40
3.1 Procédure de mise en service ................................................................. 40
3.2 Maintenance programmée ..................................................................... 41
3.3 Changement de types de gaz ................................................................ 41
3.4 Réponses relatives des types de gaz ....................................................... 42
4. Spécifications ......................................................................................... 43
5. Accessoires et pièces de rechange ......................................................... 44
6. Dépannage du détecteur ....................................................................... 45
6.1 Erreurs signalées par DEL ....................................................................... 45
6.2 Sortie analogique ................................................................................... 45
7. Configuration du Modbus RS485 ........................................................... 46
7.1 Générales ............................................................................................... 46
7.2 Topologie du câblage ............................................................................. 47
7.2.1 Connexion à étoiles ...................................................................... 47
7.2.2 Connexion de bus linéaire ............................................................ 47
7.3 Exigences de câblage ............................................................................. 48
7.3.1 Calcul du niveau minimum d’alimentation requise ....................... 48
7.3.2 Exemple de calcul ......................................................................... 48
8. Manuel de sécurité fonctionnelle ............................................................ 49
8.1 Introduction ........................................................................................... 49
8.2 Fonction de sécurité IRmax et IRmax Modbus ........................................ 49
8.3 Informations relatives à la sécurité fonctionnelle .................................... 49
8.4 Configuration du matériel ...................................................................... 50
8.5 Configuration du logiciel ........................................................................ 50
8.6 Défaillances systématiques ..................................................................... 50
8.7 Intervalle de diagnostic .......................................................................... 50
8.8 Contraintes ............................................................................................ 50
8.9 Questions environnementales ................................................................ 51
8.10 Tolérance aux pannes du matériel ........................................................ 51
8.11 Capacité systématique ......................................................................... 51
8.12 Classification ........................................................................................ 51
Garantie ..................................................................................................... 52
29
Français
Detecting
Gas Saving Lives
Concept et sécurité
Concept détecteur IRmax
Le détecteur IRmax est un détecteur de gaz infrarouge (IR) ultra compact qui assure une détection
rapide et à sécurité intégrée des hydrocarbures et vapeurs gazeux.
Doté de la technologie de capteur IR double longueur d’onde intégrée à un robuste boîtier en acier inoxydable
316, le détecteur IRmax est conçu pour opérer dans les conditions les plus rigoureuses. À la différence des
détecteurs de gaz IR conventionnels, le détecteur IRmax ne comprend pas de chauffage empêchant la
condensation sur les fenêtres et les miroirs. Le film STAY CLIR revêtant les composants optiques empêche la
formation de condensation pendant le fonctionnement du détecteur IRMax.
Le détecteur IRmax est compatible avec tout système de contrôle 4-20 mA et peut également être
installé dans un réseau adressable Modbus RS485. (voir Section 7).
Le détecteur IRmax nécessite une alimentation de 1 Watt uniquement, ce qui représente une
alimentation généralement de 75 à 90 % inférieure à celle des détecteurs de gaz IR conventionnels..
Le détecteur IRmax comporte une chambre de diffusion du gaz laquelle, combinée à un couvercle
étanche et efficace, assure une excellente vitesse de réponse. Le couvercle étanche a été conçu au
moyen d’un logiciel de modélisation de flux en vue de permettre le gazage et le calibrage à distance
du détecteur IRmax, sans nécessiter de couvercle de calibrage spécial.
L’IR Display permet de contrôler localement et à distance les valeurs relevées dans IRmax. Un IR
Display peut être installé directement dans IRmax. Sinon, le détecteur IRmax peut être fourni
avec un module de protection de sécurité intrinsèque (SI) fixe. Un IR Display peut ensuite être
connecté au module de protection SI par le biais d'un câblage temporaire ou permanent. Les
options disponibles sont illustrées en Figure 3, page 33.
Pour de plus amples informations sur d'autres accessoires pour le IRmax, reportez-vous à la Figure 3 de
la page 33 et la section 5, page 44.
Concept et sécurité
30
Français
Detecting
Gas Saving Lives
Informations de sécurité
Les détecteurs de gaz IRmax doivent être installés, utilisés et entretenus en respectant rigoureusement ces
instructions, avertissements, informations d’étiquetage et dans les limites indiquées.
L’écrou arrière figurant sur le détecteur IRmax doit être maintenu fermement en position fermée durant
le fonctionnement. Ne pas tenter d’enlever l’écrou arrière avant que l’alimentation au détecteur n’ait été
isolée, sous risque d’explosion en présence d’une atmosphère inflammable. Avant de retirer l’écrou en vue
de la maintenance, du calibrage ou d’interventions de révision, vérifier que l’atmosphère environnante est
exempte de gaz ou de vapeurs inflammables. Ne pas l’ouvrir avant un délai de quelques minutes après
arrêt de l’alimentation.
Les opérations de maintenance et de calibrage doivent être effectuées uniquement par un personnel de
service qualifié.
Seules des pièces de rechange d’origine Crowcon doivent être utilisées ; l’utilisation de pièces de
substitution peut rendre invalides la certification et la garantie du détecteur IRmax.
Les détecteurs IRmax doivent être protégés contre les risques de vibrations extrêmes et de lumière directe
du soleil dans les environnements chauds car ceux-ci peuvent entraîner une hausse de la température du
détecteur IRmax au-delà des limites spécifiées et ainsi susciter une défaillance prématurée.
Le détecteur IRmax ne détecte pas l’hydrogène, l’ammoniaque ou le dioxyde de carbone.
L’équipement doit être relié à la terre au moyen du presse-étoupe et du câble armé d'acier.
Certification pour les environnements poussiéreux zones 21/22 : La version de base IRmax (sans affichage
IF ou module de sécurité intrinsèque) peut être utilisée dans les environnements susceptibles de contenir
des poussières dangereuses (zones 21 ou 22).
Le détecteur IRmax avec module de barrière à sécurité intrinsèque peut être utilisé dans les zones 21 ou 22
dès lors que la température ambiante demeure en dessous de 40 °C et qu'un affichage IR distant ou des
affichages IR portables sont installés/utilisés uniquement en dehors de la zone dangereuse.
Le détecteur IRmax avec affichage IR fixe ne peut être installé dans une zone 21 ou une zone 22.
Concept et sécurité
31
Français
Detecting
Gas Saving Lives
Présentation du produit
Le détecteur IRmax est un détecteur de gaz infrarouge conçu pour détecter les gaz hydrocarbures
entre 0 et 100 % de la LIE (limite inférieure d’explosivité : concentration minimum dans l’air à
laquelle une explosion peut se produire).
Le détecteur IRmax est un détecteur certifié antidéflagrant (Exd) adapté à un emploi en
environnement à risques Zone 1 ou Zone 2 ATEX . Se reporter à l’étiquette de certification apposée
sur le côté du détecteur pour identifier le type de certification se rapportant au produit fourni.
Remarque : si aucune étiquette de certification n’est apposée sur le détecteur IRmax, le
détecteur n’est pas certifié pour une utilisation dans des espaces dangereux.
Figure 1: Étiquettes de certification du détecteur IRmax
0811
.TNESERP EB YAM EREHPSOMTA EVISOLPXE NEHW NEPO TON OD :GNINRAW
04- = bmaT( bG 4T CII bd xE 57+ ot C )C
W5=xamW V23=xamV
04- = bmaT
( bG 6T CII bd xE 05+ ot C )C
X9010.90 SAB xECEI X6020XETA90afeesaB
X6021XETA21 ariS 2LIS
DS4 41XO ,modgniK deitnU ,nodgnibA
DG2 II
ROTCETED SAG RI
)C°57+ aT C°04-( bD C°531T CIII bt xE
°°
°
°
IRmax Basic certification label
Ex db ia IIC T4 Gb (-40°C Ta +75°C)
Vmax=32V Wmax=5W
WARNING: DO NOT OPEN WHEN EXPLOSIVE ATMOSPHERE MAY BE PRESENT.
IR G A S DET E C TOR W I TH R E M OTE D I SPL A Y
Baseefa09ATEX0220X IECEx BAS 09.0104X
Abingdon, United Kingdom, OX14 4SD
1180
II 2GD
Ex tb ia IIIC T135
°C Db (-40°C Ta +40°C)
IRmax with IS Barrier certification label
+75°C)Ex db ia IIC T4 Gb (-40°C Ta
II 2G
1180
Abingdon, United Kingdom, OX14 4SD
Baseefa09ATEX0220X IECEx BAS 09.0104X
IR GA S DE TECT OR WI TH D ISPL AY
WARNING: DO NOT OPEN WHEN EXPLOSIVE ATMOSPHERE MAY BE PRESENT.
Vmax=32V Wmax=5W
IRmax with Fixed IR Display certification label
32
Français
Detecting
Gas Saving Lives
1. Introduction
1.1 Générales
La configuration de chaque détecteur IRmax est identifiée par une étiquette apposée sur le corps
principal de l'appareil. Lors de tout contact avec Crowcon en vue d’obtenir des conseils ou des
pièces de rechange, veiller à indiquer le nom du produit, le numéro de pièce et le numéro de série.
1.2 Description du produit
Le détecteur IRmax se compose d’un corps principal en acier inoxydable 316, d’une enveloppe
étanche antistatique recouvrant les éléments optiques et d’un ensemble avec chambre de mesure
du gaz et éléments électroniques. Il est également possible d’installer un module d’affichage IR
Display. Les instructions du montage de l'affichage IR Display sont indiquées dans le manuel de
l'afficheur IR Display (M07061).
Un presse-étoupes à ergot de raccordement en option peut être fourni pour permettre la fixation
du détecteur IRmax directement sur un boîtier de jonction auxiliaire doté d’entrées de câble M20
ou NPT ½”.
Toutes les dimensions sont exprimées en millimètres.
Figure 2: Plan coté détecteur IRmax
Remarque : le corps du détecteur IRmax est fourni avec deux entrées de câble, l'une
de type M20 et l’autre NPT 1/2". L’entrée de câble non spécifiée à la commande d’un
détecteur IRmax sera rendue étanche à l’aide d’un obturateur certifié. Le détecteur IRmax
doit être installé avec les deux entrées de câble obturées : l'une à l'aide d'un presse-
étoupe et l'autre à l'aide d'un bouchon obturateur conforme à une norme IP66 certifiée.
157.5
74.5
136
60.5
Presse-étoupes à
ergot en option
57 hors
tout
158 hors tout
74.5
136 hors tout
Presse-étoupes
de câble M20 ou
NPT 1/2"
Borne
de terre
extérieure
(terre)
1. Introduction
33
Français
Detecting
Gas Saving Lives
Figure 3: Vue éclatée du détecteur IRmax (avec numéros de pièce, si indiqué)
Bouchon de calibrage M041007
Enveloppe étanche M04995
Bague de retenue de miroir
Miroir
Adaptateur de flux S012996
Joint torique pour écrou de blocage, module de barrière à sécurité intrinsèque ou module à
affichage IR fixe : M040077
Support de fixation d’assemblage complet S012130
Versions à presse-étoupes à ergot M20 ou NPT 1/2" : M20 ATEX: S012147, 1/2" NPT ATEX: S012190
Plaque de maintien et boulons d'obturateur arrière, affichage IR fixe et module de barrière à
sécurité intrinsèque.
10
Affichage IR Display version fixe
11
Raccord d’affichage IR Display à détecteur IRmax E07987
12
Module de protection SI (sécurité intégrée)
13
Câble de raccordement d’affichage IR Display
14
Support de montage d’affichage IR Display distant M03833
15
Affichage IR Display distant
}
Livré ensemble comme un « kit de remplacement
de miroir »C011206
10
11
12
13
14
15
34
Français
Detecting
Gas Saving Lives
2. Installation
AVERTISSEMENT
Ce détecteur est conçu pour un emploi environnement à risques Zone 1 et Zone
2, la certification dépendant des accessoires montés et de la température de
fonctionnement environnante. Se référer au tableau de spécifications en page 43
pour plus de détails sur la certification. L’installation doit être conforme aux normes
reconnues de l’instance en vigueur dans le pays concerné.
Pour plus d’informations, contacter Crowcon. Avant de procéder à toute intervention
d'installation, veiller à suivre les réglementations et procédures de site en vigueur
localement.
L’équipement doit être relié à la terre au moyen du presse-étoupes et du câble armé
d'acier.
Ne pas tenter de poser l'affichage IR Display sur un détecteur IRmax non fourni à cet
effet. Les détecteurs IRmax fournis pour une utilisation avec un affichage sont certifiés
Exd ia et doivent être utilisés au moyen d’un affichage fixe doté d’une protection SI ou
avec un affichage distant ou manuel raccordé par un module de protection SI Crowcon.
Les détecteurs fournis sans affichage sont certifiés Exd IIC et ne peuvent être soumis
à une réadaptation en vue d’une utilisation avec un affichage IR Display.
2.1 Implantation
Le détecteur IRmax doit être monté à l’endroit où le gaz à détecter est le plus susceptible d’être
présent. Tenir compte des points suivants lors de l’implantation de détecteurs de gaz :
Pour détecter des gaz plus légers que l’air, le méthane par exemple, les détecteurs doivent être montés en
hauteur. Pour détecter des gaz plus lourds que l’air, les vapeurs inflammables par exemple, les détecteurs
doivent être montés à un niveau bas.
Lors de l’implantation de détecteurs, tenir compte des dommages pouvant être provoqués par les
événements naturels tels que la pluie ou les inondations. Pour les détecteurs montés en extérieur dans les
régions très chaudes, Crowcon recommande l’utilisation d’un pare-soleil (see Section 5, Accessoires et
pièces de rechange, on page 44.)
Tenir compte de la facilité d’accès en vue des essais de fonctionnement et des révisions.
Envisager le comportement éventuel d'une fuite de gaz sous l’effet de courants d’air naturels ou forcés.
Si cela s’avère indiqué, monter le détecteur IRmax dans des canalisations de ventilation (au moyen du
kit de montage de canalisation de détecteur IRmax (see Section 5, Accessoires et pièces de rechange,
on page 44).
Tenir compte des conditions du processus. Par exemple, le butane est généralement plus lourd que l'air,
mais diffusé à partir d'un processus à une température et/ou une pression élevée, le gaz est susceptible
de monter plutôt que de descendre.
Le placement des capteurs doit être déterminé en suivant les conseils d’experts possédant des
connaissances spécialisées sur la dispersion du gaz et les équipements de traitement de l’usine,
de même qu'en matière de sécurité et d'ingénierie.. L'accord convenu quant à l’implantation des
capteurs doit être consigné.
2. Installation
35
Français
Detecting
Gas Saving Lives
2.2 Montage
Le détecteur IRmax peut être monté de trois façons :
1. Au moyen du support de fixation en option (Crowcon), avec raccord de câble direct
(utilisation avec 4-20 mA uniquement).
2. À l’aide d’un presse-étoupes à ergot en option pour raccorder un boîtier de jonction certifié Exe
ou Exd existant. Crowcon offre un presse-étoupe à ergot approprié comme pièce supplémentaire
en option (voir 3 ci-dessous)
3. Au moyen du boîtier de jonction et d’un presse-étoupes à ergot Crowcon en option.
La liste des pièces en option est indiquée à la section 5 de la page 44.
Le détecteur IRmax doit être installé dans un emplacement désigné, le cylindre du capteur en
position horizontale à +/- 15° (l’orientation est illustrée sur la Figure 2, en page 32). Ceci permet
de veiller à ce que de la poussière ou de l’eau ne s’accumulent pas sur les composants optiques.
2.3 Câblage direct vers le détecteur IRmax
Cette option convient uniquement à un fonctionnement 4-20 mA. Un Crowcon support de
fixation est nécessaire pour fixer le détecteur à un mur ou un tuyau de 2” (50 mm).
Figure 4: Connexions de câble sur site sur l'IRmax
Raccorder les câbles au moyen d’un presse-étoupes certifié, par l’entrée de câble choisie sur le corps
du détecteur IRmax (M20 ou NPT 1/2"). Crowcon recommande d’installer les presse-étoupes de
câbles orientés vers le bas.
Veiller à utiliser des presse-étoupes de câbles associés
à la certification Exd appropriée et s’assurer que la
longueur de filetage ne dépasse pas la longueur
spécifiée dans la figure (gauche).
Signal
0 V (masse)
+V (24V IRmax)
15mm MAX
DEL d'état
2. Installation
36
Français
Detecting
Gas Saving Lives
2.3.1 Désignation de bornes
Avec le détecteur IRmax orienté comme illustré en Figure 2, page 32 (entrée de câble en haut),
le câble à 3 fils doit être raccordé au moyen du raccord amovible, comme suit :
+24 V en bas, 0 V au milieu et signal en haut.
Le connecteur 6 broches situé à droite du circuit imprimé est destiné aux révisions et/ou au
raccordement d’un module d’affichage IR Display.
Borne positive : alimentation positive depuis la carte de contrôle.
Borne Sig : Signal depuis la carte de contrôle.
Borne 0 V : alimentation négative depuis la carte de contrôle.
2.3.2 Installation du détecteur IRmax à l’aide d’un support de fixation
a. Le détecteur IRmax peut être fourni avec un support de fixation (S012130) plutôt
qu’avec un presse-étoupes à ergot, de manière à pouvoir le raccorder directement à des
câbles (voir Figure 5).
Figure 5: Détecteur IRmax avec support de fixation et presse-étoupes de câble
b. Si le détecteur doit être monté sur une surface plane, marquer l'emplacement de deux
orifices et percer en utilisant le support de fixation comme modèle. Fixer sans serrer deux
parties du support en se servant d’une paroi/surface adéquate.
c. Retirer le couvercle étanche du détecteur IRmax puis faire glisser le corps du détecteur
par le support. Il est recommandé d’installer le corps du détecteur IRmax avec l’entrée
de câble orientée vers le bas.
Support de fixation : 70 mm entre
les centres de fixation. Utilisez des
boulons M6.
2. Installation
37
Français
Detecting
Gas Saving Lives
d. Serrer les deux fixations de support de sorte que le détecteur IRmax soit maintenu
fermement en place. Remettre l’enveloppe étanche en place.
e. Une fois le détecteur IRmax fixement en place, déposer l’écrou arrière du détecteur
IRmax afin de permettre l’accès aux bornes de câble.
f. Préparer le câble. Crowcon recommande un câble à blindage acier (SWA ou Steel Wire
Armoured de 1,5 mm
2
), d'autres types de câble pouvant être utilisés dès lors qu’ils sont
compatibles avec des presse-étoupes certifiés Exd). Poser un presse-étoupes de câble de
certification Exd appropriée, passer les conducteurs de câble par le corps du détecteur
IRmax et visser l’ensemble dans le presse-étoupes de câble. Fixer le presse-étoupes en
place et s’assurer que l’armure du câble est reliée à la masse au presse-étoupes du câble
et au corps du détecteur IRmax. NB. Ne pas oublier de reposer l’écrou arrière après avoir
installé le câble.
g. La plaque de maintien (élément 9 en Figure 3, page 33) doit être fixée solidement
afin d'empêcher que l'écrou arrière (ou l'accessoire d'affichage IR fixe ou de modèle de
barrière à sécurité intrinsèque) risque de se desserrer.
2.4 Installation au moyen d’un presse-étoupes à ergot
et d’un boîtier de jonction auxiliaire
Cette option est requise lorsque le détecteur IRmax doit être raccordé à un boîtier de jonction
auxiliaire certifié Exe ou Exd existant.
Figure 6: Détecteur IRmax raccordé à un boîtier de jonction auxiliaire
2. Installation
38
Français
Detecting
Gas Saving Lives
2.4.1 Pour poser le détecteur IRmax sur un boîtier de jonction auxiliaire :
a. Procéder avec précaution pour retirer la partie extérieure du presse-étoupes à ergot
(élément 8 de la Figure 3, page 33).
b. Visser l'extrémité étroite du presse-étoupes à ergot dans le boîtier de jonction auxiliaire.
c. Lever le détecteur IRmax jusqu’au boîtier de jonction et faire passer les fils par
l'ensemble et dans le boîtier de jonction auxiliaire. Fixer le détecteur IRmax en place en
vissant à fond le collier sur le presse-étoupes de câble. Serrer la vis de rappel.
d. Le corps principal du détecteur IRmax peut être pivoté horizontalement selon un angle,
dès lors qu’il est sûr d’un point de vue mécanique, qu’il est sans incidence sur tout autre
équipement et est accessible en vue d’interventions de maintenance.
e. Se reporter à la Section 2.6 pour des instructions sur le câblage. Voir aussi Figure 4,
page 35.
2.5 Exigences de câblage
Le câblage au détecteur IRmax doit être conforme aux normes reconnues de l’instance en vigueur
dans le pays concerné et il doit satisfaire aux exigences électriques du détecteur IRmax.
Crowcon recommande l’utilisation d’un câble à blindage acier (SWA ou Steel Wire Armoured) et
des presse-étoupes antidéflagrants adéquats doivent être utilisés. D’autres techniques de câblage
telles les conduites en acier peuvent être acceptables, dès lors que des normes appropriées sont
respectées.
La longueur de câble maximum recommandée est de 3,4 km (voir le Tableau 1).
Le détecteur IRmax nécessite une alimentation cc de 12-30 V. Veiller à une alimentation minimum
de 12 V du panneau de commande au détecteur IRmax, en tenant compte de la baisse de tension
due à la résistance du câble à une intensité de crête de 0,1 A.
En général, un câble de 1,5 mm
2
permet de disposer de longueurs de câbles allant jusqu’à
3,0 km. Le Tableau 1 ci-dessous indique les distances de câble maximum lors d’une utilisation de
paramètres de câble types.
Coupe Résistance Max. Distance
>20 V
Max. Distance
18 à 20 V
mm
2
(Ohms par km) (km) (km)
1,0 18,4 2,2 1,6
1,5 13,0 3,0 2,3
2,5 11,5 3,4 2,6
Tableau 1 : distances de câble maximum pour câbles types
2. Installation
39
Français
Detecting
Gas Saving Lives
2.6 Raccordements et paramètres
Tous les raccordements décrits se rapportent au bornier monté sur le corps principal du raccord de
détecteur IRmax. Les bornes du circuit imprimé de raccord de détecteur IRmax sont marquées «
+ », « sig » et « 0 V ». La polarité adéquate doit être observée lors du raccordement du détecteur
IRmax à l’équipement de commande.
Le détecteur IRmax est réglé en usine comme étant un dispositif à « écoulement de courant
», sauf spécification contraire à la commande. Pour réinitialiser la « source de courant »,
retirer la retour écrou et déplacer les deux liaisons du circuit imprimé de borne de la position «
d’écoulement » à la position de « source », comme indiqué sur la Figure 7.
Remarque : La borne de terre extérieure est utilisée uniquement lorsque les autorités
locales permettent ou nécessitent un raccordement de ce type. Lorsque cela est possible,
dans le but de limiter les interférences de fréquence radio, le boîtier de jonction et
l’armure de câble doivent être mis à la terre uniquement au panneau de commande (zone
sûre) afin d’éviter les circuits de terre.
Figure 7: Emplacement de bretelle d’écoulement/de source
Le signal 4-20 mA peut être défini sur « écoulement » ou « source » de courant au moyen des
broches et de la liaison de bretelle indiquées dans la Figure 7. Réglez le collecteur de courant («
Sink ») en installant le cavalier aux broches 3 et 4, comme illustré sur la photo de gauche. Réglez
le circuit source en installant le cavalier aux broches 1 et 2, comme illustré sur la photo de droite.
Les détecteurs IRmax seront définis sur « écoulement de courant », sauf spécification contraire
à la commande.
Indication par DEL : Une DEL est montée sur le circuit imprimé à bornes pour indiquer
l’état de fonctionnement actuel. Se reporter à la Section 6 pour plus d’informations.
CONTROLLER
EARTH
+V
0V
Sg
3
21
Connecteur du kit de
communications PC
Paramètres
de bretelle
DEL d'état
Connecteur de
l'affichage IR Display
Câblage
Numéro Couleur Fonction
1 Rouge +V
2 Noir 0V
3 Vert Signal
Contrôleur
d’écoulement
source
40
Français
Detecting
Gas Saving Lives
3. Fonctionnement
AVERTISSEMENT
Avant de procéder à toute intervention, veiller à suivre les réglementations et procédures
de site en vigueur localement. Ne jamais essayer d’ouvrir le détecteur IRmax ou le boîtier
de jonction en présence de gaz inflammable. S’assurer que le panneau de commande
associé est désarmé afin d'empêcher les fausses alarmes.
3.1 Procédure de mise en service
1. Vérifier que :
a. Les raccordements de câble sont corrects.
b. La tension d’alimentation est réglée au niveau de la carte de contrôle entre 18 et 30 V.
La tension mesurée aux bornes du détecteur IRmax (dans le boîtier de jonction Exe si ce
dernier est utilisé ou au circuit imprimé de bornes de détecteur IRmax) et elle doit être
réglée entre 12 et 30 V.
c. Les liaisons sont réglées pour un écoulement ou une source de courant 4-20 mA, selon
la carte de contrôle.
2. Après la mise sous tension, attendre 30 minutes avant de procéder à la remise à zéro/
au calibrage. Ce délai a pour objet de veiller à la stabilité thermique. (Remarque : Le
détecteur IRmax sera entièrement opérationnel 30 secondes après application de
l’alimentation.)
3. Veiller à disposer d’air propre (c'est-à-dire sans gaz hydrocarbure) avant la remise à zéro.
Indicateur de zéro au niveau de la carte de contrôle (se reporter aux instructions de la carte de
contrôle).
4. Poser un bouchon de calibrage sur l’enveloppe étanche afin d’isoler la chambre de mesure
de l’air ambiant. Un couvercle de ce type est disponible auprès de Crowcon (M041007).
Raccorder le gaz de calibrage (50 % LIE nom.) et appliquer à un débit de 1 litre par minute.
5. Après un délai de 30 secondes régler le calibrage/le réglage sur la carte de contrôle, de sorte
que la valeur soit 50 % de la LIE ou qu’elle corresponde à la concentration de gaz de calibrage
appliquée. Le détecteur IRmax même ne devrait pas nécessiter de calibrage.
6. Retire le bouchon de gaz et de calibrage. Vérifier de nouveau le zéro.
7. Au moment de l’installation ou après changement du miroir, le détecteur peut être remis à
zéro et calibré au moyen d’un accessoire d'affichage IR Display (voir page 29) ou par le
biais d’un kit de communication PC (voir le manuel sur les accessoires IRmax).
Remarque : Des détecteurs IRmax certifiés ATEX seront fournis calibrés en fonction de
la conformité avec EN61779 (selon l’exemple 100 % de la LIE méthane = 4,4 % volume).
Remarque : Il est recommandé d’utiliser le bouchon de calibrage pour la mise en service
initiale. Des calibrages subséquents peuvent être effectués en effectuant une application
distante de gaz vers l’enveloppe étanche, via l’ergot de tuyau (ce qui évite ainsi d’accéder
directement au détecteur IRmax). Un calibrage sans le bouchon de calibrage (c’est-à-dire
par le biais de l’enveloppe étanche) peut être effectué dès lors que la vitesse de vent
locale est inférieure à 2 mètres/seconde. Le débit du gaz doit être supérieur à 2,0 litre/
minute.
3. Fonctionnement
41
Français
Detecting
Gas Saving Lives
3.2 Maintenance programmée
Les pratiques du site gouvernent la fréquence à laquelle le détecteur IRmax doit être testé.
Crowcon recommande qu’un détecteur IRmax soit soumis à des essais sur les gaz et recalibré
au moins tous les 6 mois si nécessaire. Pour recalibrer un détecteur IRmax, suivre les étapes
indiquées en Section 3.1.
En cas de défaillance électronique, consulter votre représentant Crowcon local.
Intervalle de calibrage : Crowcon recommande d’effectuer un calibrage tous
les12 mois.
Calibrage distant par le biais d’un tuyau : La vitesse du vent doit être inférieure à 2 mètres par
seconde. Si elle est supérieure, utiliser le bouchon de
calibrage pour empêcher les risques de dilution du gaz.
Nettoyage des éléments optiques : Il n’est pas recommandé, sauf si le détecteur IRmax
présente un défaut d’obscurcissement. Si la fenêtre ou
le miroir deviennent contaminés, les nettoyer
soigneusement à l’eau (voir Section 5, Accessoires et
pièces de rechange, page 44)
Miroirs : S’ils sont endommagés, contacter Crowcon en
vue d’un remplacement (voir Section 5,
Accessoires et pièces de rechange, page 44) Le
détecteur IRmax doit toujours être remis à zéro et
recalibré après un remplacement de miroir.
Si de la condensation commence à entraîner des
défauts, remplacer le miroir (il se peut que le revêtement
optique soit endommagé). Crowcon recommande de
remplacer le miroir tous les 5 ans.
3.3 Changement de types de gaz
Chaque détecteur IRmax est fourni précalibré pour un type de gaz donné (par exemple du
méthane ou du propane). Si un ré-étalonnage est nécessaire pour un type de gaz différent, le
détecteur IRmax peut être reconfiguré au moyen du kit de communications PC (voir Section 5,
Accessoires et pièces de rechange, page 44), avant d'être étalonné..
3. Fonctionnement
42
Français
Detecting
Gas Saving Lives
3.4 Réponses relatives des types de gaz
Le graphique ci-dessous indique les réponses relatives à d’autres types de gaz pour un détecteur
IRmax calibré en fonction de méthane.
Remarque : de nombreux gaz et vapeurs d'hydrocarbure sont plus aisément détectés par
les détecteurs IR que le méthane. La réponse de l'IRmax (et d'autres détecteurs de gaz IR)
sera linéaire à l'échelle de la plage 0-100 % LEL pour le gaz cible (p.ex. le méthane dans
cet exemple), mais elle sera non -linéaire pour d'autres hydrocarbures pouvant être
également présents.
Figure 8
La figure indique la réponse des gaz mentionnés ci-dessus : de gauche à droite, propane, butane,
pentane et méthane.
D’autres types et plages de gaz sont disponibles. Contacter Crowcon pour plus de détails.
43
Français
Detecting
Gas Saving Lives
4. Spécifications
Matériau d’enceinte Acier inoxydable 316
Dimensions (détecteur uniquement) 158 mm x 75 mm x 57 mm (sans ergot)
Poids IRmax 1,58 kg (3,5 lbs)
IRmax avec IR Display fixe 2 kg (4,4 lbs)
IRmax avec module de protection SI 2,4 kg (5,3 lbs)
IR Display à distance 0,2 kg (0,4 lbs)
Tension de fonctionnement 12 à 30 V cc
Alimentation < 1 W
Sortie 4-20 mA 3 fils (écoulement ou source)
Signal de défaut <1 mA
Résistance de boucle de câble max. 80 ohms (par rapport à la borne négative)
Température de fonctionnement -40 °C à +75 °C (-40 °F à +167 °F)
Humidité Humidité relative de 0 à 100 %
Degré de protection IP66
Protection contre les explosions Antidéflagrant
Code d’approbation
ATEX
Détecteur IRmax (sans affichage IR Display)
II 2 GD Exd db IIC T6 Gb (Tamb = -40°C à +50°C)
II 2 GD Exd db IIC T4 Gb (Tamb = -40°C à +75°C)
II 2 GD Ex tb IIIC T135°C Db (-40°C ≤ Ta≤ +75°C)
IRmax avec module de barrière à sécurité intrinsèque
(afchage distant)
II 2 GD Exd db ia IIC T4 Gb (Tamb = -40°C à +75°C)
Ex tb ia IIIC T135°C Db (Tamb = -40°C à +40°C)
IRmax avec afchage IR xe
II 2 G Exd db ia IIC T4 Gb (Tamb = -40°C à +75°C)
N° de certificat de sécurité
ATEX et IECEx
Détecteur IRmax (sans affichage IR Display) :
Baseefa 09ATEX0206X et IECEx BAS.09.0109X
Détecteur IRmax (avec affichage IR Display) :
Baseefa 09ATEX0220X et IECEx BAS.09.0104X
Sécurité fonctionnelle Certifié en vue d'une utilisation sur un système SIL 2.
Numéro de certificat: Sira 12ATEX1206X
Normes EN 60079-0:2012+A11:2013, EN 60079-1:2014,
EN 60079-31:2014
IEC 60079-0:2011, IEC 60079-1:2014, IEC 60079-31:2013
EN 60079-29-1:2007, IEC 61508:2010, EN50402:2005
Zones Certifié pour une utilisation en Zone 1 ou en Zone 2
CEM EN50270
44
Français
Detecting
Gas Saving Lives
5. Accessoires et pièces de rechange
Numéros de pièce Nom Description
M041007 Bouchon de calibrage S’installe sur l’enveloppe étanche standard
pour permettre un calibrage lorsque la
vitesse de l’air local est supérieure à 2 mètres
par seconde.
S012130 Kit de support de
montage
Permet un montage sur un mur ou un
tuyau de 2" (50 mm). Non nécessaire si le
détecteur IRmax est installé sur un boîtier de
jonction existant.
S012152 Pare-soleil/cône
collecteur
Peut être monté sur un détecteur IRmax en
vue d'une protection contre les températures
élevées résultant de la lumière directe du
soleil et/ou pour étendre l’empreinte des
détecteurs lors de la détection de gaz plus
légers que l’air (par exemple méthane).
S012169 Kit de montage de
canalisation
Permet un contrôle de canalisation entre
300 et 3 000 mm, et de débit de l’air entre
2 et 20 m/s.
S012996 Adaptateur de débit Pour les applications de calibrage du gaz.
S012827 Kit de communication PC Module, logiciel et câble de communication
permettant de configurer le détecteur.
M20: S012295
½” NPT: S012296
Boîtier de jonction
auxiliaire
Option de montage pour IRmax, pour un
emploi en environnements à risques.
C011210 Kit de nettoyage de
mirroir
Contient des lingettes imprégnées d’alcool
isopropylique et un chiffon en en microfibres
Pièces de rechange de détecteur IRmax
Se reporter à la Figure 3 en page 33 pour plus de détails sur les pièces de rechange.
.
45
Français
Detecting
Gas Saving Lives
6. Dépannage du détecteur
6.1 Erreurs signalées par DEL
La DEL montée sur le circuit imprimé de la borne permet d’identifier les défauts. Sa position
est indiquée sur la Figure 7, page 39. Le tableau ci-dessous indique comment interpréter le
problème correspondant à chaque modèle de clignotements.
Modèle DEL État du détecteur Action
Clignotement régulier toutes
les secondes
En bon état
Allumé et s’éteignant lors de
courtes impulsions.
Détecteur IRmax en
mode de démarrage.
Attendre 10 secondes.
Clignotement rapide activé
et désactivé ou modèle de
clignotement irrégulier.
Tension
d'alimentation
trop faible ou trop
élevée.
S’assurer que la tension d’alimentation du
détecteur IRmax est réglée correctement.
S’assurer que la mesure est effectuée
directement au niveau des bornes du
détecteur IRmax.
Allumé en permanence. Défaut, erreur
d’hôte ou
d’i-module.
Effectuer un cycle d’alimentation vers le
détecteur IRmax. Si le défaut persiste, le
renvoyer à Crowcon.
Deux longs clignotements
suivis d’un clignotement
court.
Erreur fatale ;
défaut de voyant
ou de détecteur.
Renvoyer à Crowcon
Clignotement double rapide
toutes les secondes.
Erreur fatale,
défaut de
module ou de
configuration.
Contrôler la configuration du détecteur
IRmax au moyen du logiciel kit de
communication PC.
Contrôler l'alimentation électrique.
Si le défaut persiste, le renvoyer à Crowcon.
Impulsion courte toutes les
secondes.
Obscurcissement
des éléments
optiques.
Contrôler la fenêtre et le miroir et les nettoyer
si nécessaire. Remettre le détecteur IRmax à
zéro et contrôler le calibrage.
Tout autre défaut peut être rectifié uniquement en renvoyant le détecteur IRmax à Crowcon ou
à un agent d’entretien autorisé.
6.2 Sortie analogique
IRmax restera dans l'état de Défaut (Fault) et le message « Entretien requis » (Service
required) sera également indiqué sur l'affichage IR (si monté) si le signal de sortie analogique
est défaillant ou s'il n'est pas connecté à un système de contrôle ou à une résistance de
charge. Le détecteur IRmax contrôle activement le signal de sortie analogique 4-20 mA
afin de vérifier s'il se situe dans cette plage de valeurs. Si le signal se situe en dehors de
cette plage, le détecteur passe en mode Défaut et le signal est défini sur la valeur 1 mA. Par
conséquent, lors des tests d'un détecteur, il importe essentiellement de raccorder celui-ci à un
tableau de commande ou raccorder une résistance de charge de 100 Ω entre les bornes « 0
V » et « Sig » (le détecteur est configuré selon le mode « Source ») ou entre les bornes « 0
V » et « V » (le détecteur est configuré selon le mode « Courant absorbé » ).
46
Français
Detecting
Gas Saving Lives
7. Configuration du Modbus RS485
7.1 Générales
Cette section explique comment utiliser un détecteur IRmax dans une configuration Modbus. Une
version activée RS485 est disponible pour ce type d'application. Il est possible de relier jusqu’à 32
détecteurs IRmax selon des configurations en étoiles ou par bus, comme décrit ci-dessous.
Les connexions à la version RS485 du détecteur IRmax doivent être effectuées au moyen d’un
presse-étoupes à ergot vers un boîtier de jonction auxiliaire (voir Section 5, page 44), plutôt qu’à
l'aide d'un câblage direct dans le détecteur.
Noter que l’affichage IR Display ne peut être utilisé avec des détecteurs IRmax.
La version activée RS485 du détecteur IRmax comporte cinq bornes. Ces bornes sont les suivantes :
1 Alimentation positive 12 à 30 V au-dessus de 0 V
2 0V Référence retour et RS485
3 Signal 4-20 mA Signal source ou écoulement (option)
4 RS485 B Signal différentiel RS485
5 RS485 A Signal différentiel RS485
Les signaux aux bornes RS485 sont conformes à la norme EIA/TIA-485, ce qui signifie que la plage
de mode commune se situe de -7 V à +12 V pour ce qui est de la borne 0 V.
Noter que tous les fabricants ne s’accordent pas en ce qui concerne la polarité des signaux A et
B. Si le câblage ne fonctionne pas dans un sens, les utilisateurs doivent intervertir les câbles A et B
RS485. Il n’y a aucun risque de raccordement incorrect.
Les paramètres de communication sont 9 600 bps, deux bits d’arrêt et aucune parité.
Lors de la compilation d’une interface de système de contrôle, il importe de tenir compte du temps
nécessaire au système pour recueillir les informations tour à tour pour chaque détecteur. La vitesse
la plus rapide à laquelle plusieurs détecteurs peuvent être interrogés est de 14 détecteurs par
seconde, les conditions dans la pratique pouvant réduire ce nombre à 7 détecteurs par seconde.
Les utilisateurs doivent s’assurer que l’arrangement permet aux signaux d'alarme d'être enregistrés
dans les limites de temps acceptables.
Il importe également de veiller à ce que le système puisse fournir une alimentation suffisante en
vue de maintenir le fonctionnement de tous les détecteurs. Pour calculer la quantité d’alimentation
nécessaire à une connexion par bus linéaire, voir Section 7.3, Exigences de câblage, page 48.
Pour obtenir des instructions Modbus complètes, contacter Crowcon (voir les adresses au verso
de la couverture).
7. RS485 Modbus configuration
47
Français
Detecting
Gas Saving Lives
7.2 Topologie du câblage
Les deux topologies de câblage utilisées communément sont la connexion à étoiles et le bus
linéaire.
7.2.1 Connexion à étoiles
Dans une topologie à étoiles, tous les détecteurs sont reliés par câble à un point central,
généralement le panneau de commande. Aucun câble ne nécessite plus de cinq fils, toutes les
connexions de signal 4-20 mA étant acheminées directement vers le panneau de commande.
Les signaux A et B RS485 peuvent ensuite être tous connectés ensemble au point étoile. Le bus doit
ensuite être terminé au point étoile au moyen d’une résistance de connexion de sortie 110 ohms.
La longueur de chaque bras de l’étoile ne peut dépasser 750 mètres.
7.2.2 Connexion de bus linéaire
Dans une topologie à connexion de bus, tous les détecteurs IRmax sont reliés par câble à un
arrangement linéaire, généralement avec le panneau de commande à une extrémité. Selon une
installation classique en tunnel, les détecteurs IRmax sont installés à intervalles réguliers (voir
Figure 9 ci-dessous).
Pour raccorder le câblage de l’installation, poser deux résistances de connexion de sortie 110 ohms
à chaque extrémité physique du bus.
Les signaux 4-20 mA ne pouvant être partagés, un conducteur supplémentaire est nécessaire sur
chaque distance de répétition de câblage. Si aucun des signaux 4-20 mA n’est utilisé, seuls quatre
conducteurs seront nécessaires.
Figure 9
FIGURE DE CONNEXION DE BUS LINÉAIRE
l i n e a r  b u s  X g a r d  J u n c t i o n  B o x  F r e n c h
1 2  O c t o b e r  2 0 1 0  1 8 : 3 9 : 1 9
VERS PANNEAU
DE COMMANDE
7. RS485 Modbus configuration
48
Français
Detecting
Gas Saving Lives
7.3 Exigences de câblage
7.3.1 Calcul du niveau minimum d’alimentation requise
Plus le nombre de détecteurs IRmax connecté au bus linéaire est important et plus l’alimentation
nécessaire au système sera élevée. Pour calculer l’alimentation requise pour une configuration
particulière, il est nécessaire de connaître la résistance de câble entre chaque paire de détecteurs
IRmax. Un courant d’au moins 0,1 mA doit être prévu pour chaque « distance de répétition » entre
les détecteurs IRmax. La tension à appliquer peut être calculée en estimant la baisse de tension au
niveau de chaque « distance de répétition ». À terme, il doit rester une tension d’au moins 12 V
pour veiller à ce que le dernier détecteur IRmax fonctionne correctement.
Contacter Crowcon pour tout conseil sur une situation spécifique. Sinon, suivre les étapes
ci-dessous et le calcul modèle indiqué dans la section suivante.
1. La tension ne doit pas baisser en-dessous de 12 V ; veiller donc à effectuer le calcul en
définissant la tension du dernier détecteur IRmax de la ligne selon cette valeur.
2. Chaque détecteur IRmax peut utiliser jusqu’à 0,1 A. Calculer la perte de tension de câble de la
première distance de répétition séparant les détecteurs en admettant que le « courant cumulé »
correspond à 0,1 A et multiplier cette valeur par la résistance de câble de la distance de répétition
entre le dernier détecteur et l’avant-dernier des détecteurs IRmax.
3. Ajouter cette baisse de tension à la tension initiale de 12 V pour obtenir la tension la plus basse
acceptable à l’avant-dernier des détecteurs IRmax. Ajouter 0,1 A à la valeur de « courant cumulé
» pour parvenir à 0,2 mA, valeur de courant minimum alimentant l’avant-dernière distance de
répétition du bus. Multiplier cette valeur par la résistance de câble de l’avant-dernière distance de
répétition pour obtenir la baisse de tension suivante.
4. Répéter ce processus pour chaque détecteur IRmax, en accumulant les pertes de tension se
produisant entre chaque détecteur IRmax.
5. Une tension de détecteur maximum de 30 V ne doit pas être dépassée.
7.3.2 Exemple de calcul
À titre d’exemple, voici les résultats du calcul pour six détecteurs IRmax séparés d’une distance
égale de 250 m sur câble, avec une section de 1 mm2. Chaque distance de répétition a une
résistance de 4,6 ohms..
Station Tension d’alimentation Alimentation en courant
1 12 0,1 A
2 12,46 0,2 A
3 13,38 0,3 A
4 14,76 0,4 A
5 16,6 0,5 A
6 18,9 0,6 A
Alimentation de panneau 21,66 0,6 A
49
Français
Detecting
Gas Saving Lives
8. Manuel de sécurité fonctionnelle
8.1 Introduction
Les sections suivantes fournissent des informations sur la certification de l'IRmax, conformément
aux normes de sécurité fonctionnelle IEC 61508 et EN 50402. Des informations sont fournies sur
les caractéristiques relatives à la sécurité, aux exigences et aux données de maintenance, afin de
permettre l'intégration de l'IRmax dans le système de sécurité actif (Safety Instrumented System - SIS).
8.2 Fonction de sécurité IRmax et IRmax Modbus
Pour mesurer la concentration de gaz inflammables et indiquer la mesure au moyen d'une sortie 4-20 mA.
Les défaillances liées à la fonction de sécurité seront détectées par le matériel et le micrologiciel
associé. Elles seront indiquées sous forme de signal de sortie inférieur à 3,6 mA ou supérieur à 21 mA.
8.3 Informations relatives à la sécurité fonctionnelle
Nom de paramètre Symbole Équation/source IRmax
Intervalle d'essai de mise à l'épreuve T1 Comme défini par Crowcon.
8 760 heures
(annuel)
Durée moyenne des réparations MTTR Comme défini par Crowcon. 8 heures
Type A/B Type A Comme défini par Crowcon. Type B
Défaillances totales:
λ
De l'AMDEC 1.04E-05
Défaillances diagnostiquées sûres: λ
SD
De l'AMDEC 1.95E-08
Défaillances non diagnostiquées sûres: λ
SU
De l'AMDEC 8.59E-08
Défaillances diagnostiquées
dangereuses:
λ
DD
De l'AMDEC 9.74E-06
Défaillances non diagnostiquées
dangereuses:
λ
DU
De l'AMDEC 5.06E-07
Défaillances sans effet sûres: λ
NE
De l'AMDEC 3.21E-09
Champ d'application des
diagnostics:
DC λ
DD
/ (λ
DU
+ λ
DD
) 95.06%
Fraction de défaillance sans danger : SFF (λ
SD
+ λ
SU
+ λ
DD
) / λ 95.11%
Temps d'arrêt d'équivalent de canal t
CE
DU
/ λ
D
)(T/2 + MTTR) +
(λ
DD
/ λ
D
) MTTR
2.24E+02
PFDAVG (au moyen d'une équation
61508-6)
PFD
AVG
DU
+ λ
DD
) t
CE
2.30E-03
PFDAVG (au moyen d'une équation
simplifiée)
PFD
AVG
λ
DU
(T / 2+MTTR) + (λ
DD
MTTR) 2.30E-03
PFDAVG (au moyen d'une équation
IEC 61508-6)
PFD
AVG
1-ε
-(λdd+λdu) tce
2.30E-03
Capacité SIL (mode demande faible)
SIL2
Capacité SIL (mode demande élevée)
SIL2
Pour les applications à demande faible, toutes les variantes du système conviennent à une
utilisation dans les applications SIL 2, pour ce qui est des défaillances de matériel aléatoires et de
la fraction de défaillance sans danger.
Manuel de sécurité fonctionnelle
50
Français
Detecting
Gas Saving Lives
8.4 Configuration du matériel
Le cheminement 1H (tolérance de défaillance de matériel et fraction de défaillance sans danger) a
été utilisé pour évaluer le niveau d'intégrité de la sécurité du matériel.
8.5 Configuration du logiciel
L'évaluation du micrologiciel du produit a été effectuée conformément aux exigences précisées
dans la norme CIE 61508:3 2010.
8.6 Défaillances systématiques
Le cheminement 1S (défini dans la norme CIE 61508:2 2010 paragraphe 7.4.2.2c) est utilisé pour la
conformité avec les exigences relatives à la prévention des défaillances systématiques.
8.7 Intervalle de diagnostic
La plupart des fonctions de diagnostic sont contrôlées de manière continue.
Des essais portant sur le dispositif de surveillance du système doivent être réalisés durant l'essai
de mise à l'épreuve annuel en éteignant puis en rallumant l'instrument : L'IRmax doit être soumis
annuellement à une mise hors tension puis à une mise sous tension (en coupant l'alimentation
24 V c.c. puis en la rétablissant) dans le cadre du programme d'entretien du produit (se reporter
également à la section 3.2).
8.8 Contraintes
Les taux de défaillance sont constants.
Un essai de mise à l'épreuve réalisé au moins une fois par an identifiera toutes les défaillances
n'ayant pas été repérées.
Les réparations ont une durée moyenne des réparations de 8 heures.
On suppose que l'utilisateur se sert de cette fonction de diagnostic via l'accessoire d'affichage IR
et/ou l'interface PC afin de minimiser le temps d'arrêt potentiel du produit.
L'évaluation de fiabilité est un processus statistique d'application d'informations relatives à
des défaillances précédentes à des conceptions et configurations proposées. Elle fournit par
conséquent une cible/estimation crédible de la fiabilité probable de l'équipement, en supposant
que les conditions de fabrication, de conception et d'utilisation sont identiques à celles utilisées
lorsque les informations ont été recueillies. Il s'agit d'une technique d'examen de conception
précieuse qui permet de comparer des conceptions différentes, d'établir un ordre de grandeur, des
cibles de rendement et d'évaluer les effets potentiels de changements apportés à la conception.
Toutefois, les valeurs prévues effectives ne peuvent être garanties comme prévoyant le nombre
précis de défaillances sur le terrain car ceci dépend de nombreux facteurs indépendants du contrôle
d'une analyse prédictive.
Dans le cadre de cette prévision, on suppose que les taux de défaillances (symbole λ) sont constants
au fil du temps. Les défaillances précoces et liées à l'usure réduiraient la fiabilité mais l'on suppose
que celles-ci sont supprimées respectivement par déverminage et par remplacement préventif.
Manuel de sécurité fonctionnelle
51
Français
Detecting
Gas Saving Lives
Concernant la probabilité de défaillance à la demande, il est probable que le système soit en état
de défaillance à un moment aléatoire. Ceci est synonyme de non disponibilité en régime établi,
indiquée par :
Non disponibilité = (λ x MDT)/(1 + (λ x MDT))
qui correspond approximativement à λ x MDT pour de petites valeurs de λ x MDT
λ correspond au taux de défaillances et MDT au Temps d'arrêt moyen.
Ceci est cohérent avec l'expression liée à la Disponibilité, indiquée comme : MTBF/(MTBF+MDT)
Les taux de défaillance utilisés, et donc, les disponibilités dérivées sont celles associées de manière
crédible à une conception éprouvée suite à une période adéquate de croissance de la fiabilité.
8.9 Questions environnementales
Contraintes environnementales :
Le produit sera utilisé selon une plage de températures ambiantes maximum de -40 °C à +75 °C.
Le produit sera stocké selon une plage de températures ambiantes maximum de -40 °C à +80
°C.
Le produit sera utilisé selon une plage d'humidité relative maximum de 0 % à +100 % Avec
condensation
Ce produit a un indice de protection IP66 selon les définitions comprises dans la norme
EN60529.
Ce produit est conçu en vue d'un fonctionnement continu.
8.10 Tolérance aux pannes du matériel
La tolérance aux pannes du matériel est de 0.
8.11 Capacité systématique
L'IREX/IRmax correspond à la Classe SC2.
8.12 Classification
L'IREX/IRmax est un composant de type B.
52
Français
Detecting
Gas Saving Lives
Garantie
Cet équipement est testé et calibré entièrement lorsqu’il quitte l’usine. Si, au cours de la période de
garantie de trois ans à compter de l’expédition, cet équipement s’avère défectueux en raison d’un
défaut de fabrication ou de matériau, nous procéderons, à notre discrétion, à sa réparation ou à
son remplacement gratuit, en fonction des conditions ci-dessous.
Procédure de garantie
Pour faciliter le traitement efficace de toute réclamation, contacter notre équipe de support client
au +44 (0)1235 557711 en fournissant les informations suivantes :
votre nom, votre numéro de téléphone, de télécopie et votre adresse de messagerie
électronique.
Description et quantité d'articles renvoyés, y compris tout accessoire.
Numéro(s) de série d’instrument.
Motif du renvoi.
Obtenir un formulaire de renvoi aux fins d'identification et de traçabilité. Ce formulaire peut être
téléchargé depuis notre site Internet crowconsupport.com, au même titre qu’une étiquette de
renvoi. Nous pouvons également vous en faire parvenir une copie par messagerie électronique.
Le détecteur IRmax ne sera pas accepté au titre de la garantie sans Numéro de retour
Crowcon (NRC). Il importe impérativement que l’étiquette de l’adresse soit bien fixée à
l’emballage extérieur des articles renvoyés.
La garantie serait rendue non valide s'il s'avérait que l'instrument avait été modifié, démonté ou
avait fait l'objet de toute intervention non autorisée. La garantie ne couvre pas une utilisation
incorrecte ou abusive de l’appareil.
Clause de non-garantie
Crowcon n’accepte aucune responsabilité pour toute perte ou dommage direct ou indirect, quel
qu’en soit l’origine (y compris les pertes ou dommages découlant de l’utilisation de l’instrument) et
toute responsabilité quant à un tiers est exclue expressément.
Cette garantie ne couvre pas la précision du calibrage de l’appareil ni la finition du produit. Cet
appareil doit être entretenu conformément aux instructions de fonctionnement et de maintenance.
La garantie ou le remplacement d’articles consommables (tels que le miroir) fournis dans le cadre de
la garantie en vue du remplacement d’articles défectueux, seront limités à la garantie non expirée
de l’article fourni d’origine.
Crowcon se réserve le droit de déterminer une période de garantie, de réduire ou de refuser une
période de garantie pour tout capteur fourni en vue d’une utilisation dans un environnement ou
pour une application dont on sait qu’ils sont associés à un risque de dégradation ou de dommages
du capteur.
Notre responsabilité concernant un équipement défectueux se limite aux obligations définies dans
la garantie et toute garantie, condition ou déclaration prononcée, expresse ou implicite, statutaire
ou autre quant à la qualité marchande de nos équipements ou de son usage pour quelque but que
ce soit, sauf dans les limites imposées par les statuts. Cette garantie ne saurait affecter les droits
légaux d’un client.
Garantie
53
Français
Detecting
Gas Saving Lives
Crowcon se réserve le droit d’appliquer des frais de manutention et de transport lorsque
des appareils renvoyés en raison d’une défaillance s’avèrent nécessiter un calibrage ou un
entretien normal auquel le client se refuse ensuite à procéder.
Pour toute question concernant la garantie et le support technique, contacter :
L’équipe de support client
Tel: +44 (0) 1235 557711
Fax: +44 (0) 1235 557722
Inhaltsverzeichnis
Konzept und Sicherheit .............................................................................. 57
Beschreibung des IRmax-Detektors .................................................... 57
Sicherheitsinformationen ..................................................................... 58
Produktübersicht ................................................................................. 59
1. Einleitung ............................................................................................... 60
1.1 Allgemeines .................................................................................. 60
1.2 Produktbeschreibung .................................................................... 60
2. Installation .............................................................................................. 62
WARNHINWEIS ................................................................................... 62
2.1 Standort ........................................................................................ 62
2.2 Montage ....................................................................................... 63
2.3 Direktverkabelung an IRmax-Detektor ......................................... 63
2.3.1 Anschlussbezeichnung ......................................................... 64
2.3.2 Installation vom IRmax-Detektor mit einer Montagehalterung .. 64
2.4 Installation mit Doppelverschraubung und Hilfsverteilerkasten ....... 65
2.4.1 Anbringen des IRmax-Detektors an einem Hilfsverteilerkasten: .... 66
2.5 Anforderungen an die Verkabelung .............................................. 66
2.6 Verbindungen und Einstellungen ................................................. 67
3. Betrieb ................................................................................................... 68
3.1 Inbetriebnahmeverfahren .............................................................. 68
3.2 Routinewartung ............................................................................ 69
3.3 Ändern der Gasart ........................................................................ 69
3.4 Relatives Ansprechen auf Gasarten ............................................... 70
4. Technische Daten ................................................................................... 71
5. Zubehör und Ersatzteile .......................................................................... 72
6. Fehlerbehebung .................................................................................... 73
6.1 Von der LED angezeigte Fehler...................................................... 73
6.2 Analogausgang ............................................................................. 73
7. RS485-Modbuskonfiguration .................................................................. 74
7.1 Allgemeines .................................................................................. 74
7.2 Verkabelungstopologie.................................................................. 75
7.2.1 Sternverbindung ................................................................... 75
7.2.2 Lineare Busverbindung ......................................................... 75
7.3 Anforderungen an die Verkabelung .............................................. 76
7.3.1 Berechnung der erforderlichen Mindestleistung .................... 76
7.3.2 Beispielberechnung .............................................................. 76
8. Handbuch für funktionale Sicherheit ...................................................... 77
8.1 Einführung .................................................................................... 77
8.2 IRmax und IRmax Modbus Sicherheitsfunktion .............................. 77
8.3 Daten zur funktionalen Sicherheit ................................................. 77
8.4 Hardwarekonfiguration ................................................................. 78
8.5 Softwarekonfiguration .................................................................. 78
8.6 Systematische Ausfälle .................................................................. 78
8.7 Diagnoseintervall ........................................................................... 78
8.8 Beschränkungen ........................................................................... 78
8.9 Umgebungsbedingungen .............................................................. 79
8.10 Hardwarefehlertoleranz ............................................................... 79
8.11 Systematische Eignung ................................................................ 79
8.12 Klassifizierung ............................................................................. 79
Garantie ..................................................................................................... 80
Deutsch
57
Detecting Gas Saving Lives
Konzept und Sicherheit
Beschreibung des IRmax-Detektors
Der IRmax-Detektor ist ein ultrakompakter Infrarot (IR)-Gasdetektor, der zur schnellen, ausfallsicheren
Detektion von Kohlenwasserstoffgasen und -dämpfen dient.
Der IRmax-Detektor ist mit Doppel-Wellenlängen-IR-Sensortechnologie in einem robusten Stahlgehäuse aus 316
Edelstahl ausgestattet und für den Betrieb unter härtesten Bedingungen ausgelegt. Im Gegensatz zu herkömmlichen
IR-Gasdetektoren enthält der IRmax-Detektor keine Heizgeräte, um Kondensation auf Fenstern und Spiegeln
zu verhindern. Die STAY CLIR-Beschichtung der optischen Komponenten verhindert die Kondensationsbildung
während des Detektorbetriebs.
Der IRmax-Detektor ist mit jedem 4-20mA-Steuersystem kompatibel und kann außerdem in ein über
Modbus adressierbares RS485-Netzwerk eingebaut werden (siehe Abschnitt 7).
Der IRmax-Detektor benötigt nur 1 Watt Leistung, was einem Stromverbrauch von typischerweise 75-90%
weniger als bei herkömmlichen IR-Gasdetektoren entspricht.
Der IRmax-Detektor ist mit einer kompakten Diffusionsgaskammer ausgestattet, die in Kombination
mit einer wirkungsvollen wetterfesten Kappe eine ausgezeichnete Reaktionsgeschwindigkeit bietet.
Die wetterfeste Kappe ist mit Hilfe von Strömungsmodellierungssoftware entworfen worden, um die
Ferngasbeaufschlagung und -kalibrierung des IRmax-Detektors ohne besondere Kalibrierungskappe
zu ermöglichen.
Das IR Display ermöglicht die Überwachung von Messwerten vom IRmax sowohl lokal als auch in
Fernabfrage. Ein IR Display kann direkt am IRmax montiert werden. Alternativ kann IRmax mit
einem montierten eigensicheren (IS) Barrieremodul geliefert werden. Ein IR Display kann dann über
ein temporäres oder permanentes Kabel an das eigensichere Barrieremodul angeschlossen werden. Die
verfügbaren Optionen sind in Diagramm 3 auf Seite 61 dargestellt.
Weitere Informationen über anderes Zubehör für den IRmax siehe Diagramm 3 auf Seite 61 und
Abschnitt 5, Seite 72.
Konzept und Sicherheit
Deutsch
58
Detecting
Gas Saving Lives
Sicherheitsinformationen
IRmax-Gasdetektoren müssen unter strenger Befolgung dieser Anweisungen, Warnhinweise,
Etikettinformationen und innerhalb der angegebenen Grenzwerte installiert, betrieben und gewartet
werden.
Die rückwärtige Mutter am IRmax-Detektor muss während des Betriebs fest geschlossen bleiben.
Versuchen Sie nicht, die rückwärtige Mutter zu entfernen, bevor die Stromversorgung zum
IRmax-Detektor abgetrennt worden ist, ansonsten kann eine Zündung einer entflammbaren
Atmosphäre auftreten. Prüfen Sie vor dem Abnehmen der Mutter zu Wartung, Kalibrierung oder
Servicearbeiten, dass die Umgebungsatmosphäre frei von entflammbaren Gasen oder Dämpfen
ist. Lösen Sie die Mutter erst mehrere Minuten nach dem Abtrennen der Stromversorgung.
Wartungs- und Kalibrierungsarbeiten dürfen nur von qualifiziertem Kundendienstpersonal durchgeführt
werden.
Es dürfen nur Original Crowcon Ersatzteile verwendet werden. Andere Komponenten können die
Zertifizierung und Garantie des IRmax-Detektors ungültig machen.
IRmax-Detektoren müssen vor starker Vibration und direktem Sonnenlicht in heißen Umgebungen
geschützt werden, da dies dazu führen könnte, dass die Temperatur des IRmax-Detektors über
die angegebenen Grenzwerte steigt und zu einem frühzeitigen Versagen führt.
Der IRmax-Detektor weist weder Wasserstoff, Ammoniak noch Kohlendioxid nach.
Die Anlage muss mit der Kabelbuchse und dem stahlbewehrten Kabel geerdet werden.
Zertifizierung für staubexplosionsgefährdete Atmosphären der Zone 21/22: IRmax basic (ohne IR
Display oder IS Barrieremodul) kann in Bereichen eingesetzt werden, die explosionsgefährdete
Stäube enthalten können (Zone 21 oder 22).
IRmax mit einem IS Barrieremodul kann in Zone 21 oder 22 eingesetzt werden, sofern die
Umgebungstemperatur unter 40 °C bleibt und ein Fernbedienungs-IR Display oder Hand-IR
Display nur außerhalb des explosionsgefährdeten Bereichs montiert/eingesetzt wird.
IRmax mit einem stationären IR Display kann nicht in einem Bereich der Zone 21 oder 22 montiert
werden.
Konzept und Sicherheit
Deutsch
59
Detecting Gas Saving Lives
Produktübersicht
Der IRmax-Detektor ist ein Infrarot-Gasdetektor, der zur Detektion von üblichen Kohlenwasserstoffgasen
im Bereich von 0 bis 100% UEG (Untere Explosionsgrenze: die Mindestkonzentration in Luft, bei der
eine Zündung auftreten kann) bestimmt ist.
Der IRmax-Detektor ist ein zugelassener flammensicherer (Exd) Detektor, der zur Verwendung in
Gefahrenbereichen der ATEX Zone 1 oder Zone 2 geeignet ist. Zur Identifikation des Zulassungstyps,
der sich auf das gelieferte Produkt bezieht, siehe Zulassungsetikett an der Seite des IRmax-Detektors.
Hinweis: Wenn der IRmax-Detektor kein Zulassungsetikett hat, ist der Detektor nicht zur
Verwendung in Gefahrenbereichen zugelassen.
Diagramm 1: IRmax-Detektor-Zertifizierungsetiketten
0811
.TNESERP EB YAM EREHPSOMTA EVISOLPXE NEHW NEPO TON OD :GNINRAW
04- = bmaT( bG 4T CII bd xE 57+ ot C )C
W5=xamW V23=xamV
04- = bmaT
( bG 6T CII bd xE 05+ ot C )C
X9010.90 SAB xECEI X6020XETA90afeesaB
X6021XETA21 ariS 2LIS
DS4 41XO ,modgniK deitnU ,nodgnibA
DG2 II
ROTCETED SAG RI
)C°57+ aT C°04-( bD C°531T CIII bt xE
°°
°
°
IRmax Basic certification label
Ex db ia IIC T4 Gb (-40°C Ta +75°C)
Vmax=32V Wmax=5W
WARNING: DO NOT OPEN WHEN EXPLOSIVE ATMOSPHERE MAY BE PRESENT.
IR G A S DET E C TOR W I TH R E M OTE D I SPL A Y
Baseefa09ATEX0220X IECEx BAS 09.0104X
Abingdon, United Kingdom, OX14 4SD
1180
II 2GD
Ex tb ia IIIC T135
°C Db (-40°C Ta +40°C)
IRmax with IS Barrier certification label
+75°C)Ex db ia IIC T4 Gb (-40°C Ta
II 2G
1180
Abingdon, United Kingdom, OX14 4SD
Baseefa09ATEX0220X IECEx BAS 09.0104X
IR GA S DE TECT OR WI TH D ISPL AY
WARNING: DO NOT OPEN WHEN EXPLOSIVE ATMOSPHERE MAY BE PRESENT.
Vmax=32V Wmax=5W
IRmax with Fixed IR Display certification label
Deutsch
60
Detecting
Gas Saving Lives
1. Einleitung
1.1 Allgemeines
Die Konfiguration jedes IRmax-Detektors wird durch ein Etikett angegeben, das am Hauptgehäuse
angebracht ist. Bitte geben Sie den Produktnamen, die Teilenummer und die Seriennummer an, wenn
Sie sich für Hilfestellung oder Ersatzteile an Crowcon wenden.
1.2 Produktbeschreibung
Der IRmax-Detektor besteht aus einem Gehäuse aus Edelstahl 316, einer antistatischen wetterfesten
Abdeckung über der Optik und einer Gasmessungskammer und einer Elektronikbaugruppe. Ein IR
Display-Modul kann ebenfalls enthalten sein. Anleitung für den Einbau des IR Display sind im IR
Display Handbuch (M07061) enthalten.
Es kann eine optionale Doppelverschraubung mit entweder M20- oder ½” NPT-Kabeleingang geliefert
werden, um den IRmax-Detektor direkt an Hilfsverteilerkasten mit entweder M20- oder ½” NPT-
Kabeleingängen anzuschließen.
Alle Abmessungen in Millimetern
Diagramm 2: IRmax-Detektor – bemessene Ansicht
Hinweis: Das Gehäuse des IRmax-Detektors wird mit zwei Kabeleingängen geliefert –
einem M20- und einem 1/2" NPT-Eingang. Der bei der Bestellung eines IRmax-Detektors
nicht angegebene Kabeleingang wird mit Hilfe eines zertifizierten Stopfens versiegelt. Der
IRmax muss mit beiden Kabeleinführungen abgedichtet montiert werden: eine mit einer
Kabelverschraubung, die andere mit einem zertifizierten IP66-Verschlussstopfen.
157.5
74.5
136
60.5
Optionale
Doppelverschraubung
57
insgesamt
158 insgesamt
74,5
136 insgesamt
M20- oder 1/2" NPT-
Kabelverschraubung
Externer
Masseanschluss
(ERDE)
1. Einleitung
Deutsch
61
Detecting Gas Saving Lives
Diagramm 3: IRmax-Detektor – Explosionszeichnung (Teilenummer abgebildet, soweit zutreffend)
Kalibrierungskappe M041007
Wetterfeste Kappe M04995
Spiegelhalter
Spiegel
Strömungsadapter S012996
O-Ring für Gegenmutter, IS Barrierenmodul oder stationäres IR Displaymodul: M040077
Montagehalterung als Komplettbaugruppe S012130
M20- oder 1/2" NPT-Versionen der Doppelverschraubung: M20 ATEX: S012147, 1/2" NPT ATEX: S012190
Halteblech und Schrauben für hinteren Stopfen, stationäres IR Display und IS Barrieremodul.
10
IR Display-Festversion
11
IR Display-an-IRmax-Detektor-Steckverbinder E07987
12
IS-Barrierenmodul
13
IR Display-Anschlusskabel
14
Fernbedienungs-IR Display-Montagebuchse M03833
15
Fernbedienungs-IR Display
}
Zusammen als „Spiegelersatz-Kit” geliefert
C011206
10
11
12
13
14
15
Deutsch
62
Detecting
Gas Saving Lives
2. Installation
WARNHINWEIS
Der IRmax-Detektor ist zur Verwendung in Gefahrenbereichen der Zone 1 und
Zone 2 bestimmt. Die Zulassung hängt von dem eingebauten Zubehör und der
Umgebungsbetriebstemperatur ab. Einzelheiten zur Zulassung entnehmen Sie bitte
der Spezifikationstabelle auf Seite 71. Die Installation muss gemäß der anerkannten
Standards der zuständigen Aufsichtsbehörde in dem jeweiligen Land erfolgen.
Weitere Informationen erhalten Sie von Crowcon. Vor der Ausführung aller
Installationsarbeiten müssen Sie gewährleisten, dass die lokalen Bestimmungen und
Standortverfahren eingehalten werden.
Die Anlage muss mit der Kabelbuchse und dem stahlbewehrten Kabel geerdet werden.
Versuchen Sie nicht, ein IR Display an einem IRmax-Detektor anzubringen, der nicht
für diesen Zweck geliefert worden ist. Zur Verwendung mit einem Display gelieferte
Detektoren sind mit „Exd ia“ zertifiziert und müssen entweder mit einem festen Display,
das eine IS-Barriere enthält, oder mit einem Fernbedienungs- oder Handgerät-Display
betrieben werden, das über ein Crowcon IS-Barrieremodul angeschlossen ist.
Ohne ein Display gelieferte Detektoren sind mit „Exd IIC“ zertifiziert und können nicht
zur Verwendung mit einem IR Display nachgerüstet werden.
2.1 Standort
Der IRmax-Detektor muss dort montiert werden, wo das zu detektierende Gas am ehesten vorhanden
ist. Die folgenden Punkte müssen bei der Anbringung von Gasdetektoren berücksichtigt werden:
Für die Detektion von Gasen, die leichter als Luft sind, wie zum Beispiel Methan, müssen
Detektoren hoch über dem Boden angebracht werden. Für die Detektion von Gasen, die schwerer
als Luft sind, wie zum Beispiel entflammbare Dämpfe, müssen Detektoren niedrig über dem Boden
angebracht werden.
Bedenken Sie beim Anbringen von Detektoren die möglichen Beschädigungen durch
Naturereignisse, zum Beispiel Regen oder Überschwemmungen. Bei der Außenanbringung von
Detektoren in sehr heißen Gebieten empfiehlt Crowcon den Einsatz eines Sonnenschutzes (siehe
Abschnitt 5, Zubehör und Ersatzteile, auf Seite 72).
Achten Sie darauf, dass die Detektoren für Funktionsprüfungen und Servicearbeiten leicht
zugänglich sind.
Überlegen Sie, wie sich das entweichende Gas aufgrund von natürlichen oder erzwungenen
Luftströmungen verhält. Bringen Sie gegebenenfalls Detektoren in Entlüftungsschächten an (mit
Hilfe des IRmax-Detektor-Kanaleinbauadapters (siehe Abschnitt 5, Zubehör und Ersatzteile, auf
Seite 72)).
Berücksichtigen Sie die Prozessbedingungen. Butan ist zum Beispiel normalerweise schwerer als
Luft, wenn es jedoch aus einem Prozess entweicht, der bei erhöhter Temperatur bzw. erhöhtem
Druck abläuft, kann das Gas aufsteigen, anstatt absinken.
Die Platzierung von Sensoren muss mit Hilfe der Ratschläge von Experten erfolgen, die ein Spezialwissen
über Gasverteilung und die Werksprozessanlagen sowie Sicherheits- und technische Fragen besitzen. Die
Vereinbarung bezüglich der Standorte von Sensoren muss aufgezeichnet werden.
2. Installation
Deutsch
63
Detecting Gas Saving Lives
2.2 Montage
Der IRmax-Detektor kann auf drei verschiedene Weisen montiert werden:
1. Mit der Crowcon Montagehalterung mit direktem Kabelanschluss (nur für Betrieb von 4-20mA).
2. Mit einer Doppelverschraubung zum Anschluss an einen vorhandenen zugelassenen Exe- oder Exd-
Verteilerkasten. Crowcon liefert eine geeignete Kabelstopfbüchse als optionales Extra (siehe 3 unten)
3. Mit dem optionalen Crowcon Hilfsverteilerkasten und einer Doppelverschraubung.
Optionalteile sind in Abschnitt 5 auf Seite 72 aufgeführt.
Der IRmax-Detektor muss an dem vorgegebenen Standort mit der Sensortrommel horizontal +/- 15°
installiert werden (Orientierung auf Diagramm 2 auf Seite 60 abgebildet). Dadurch ist gewährleistet,
dass sich weder Staub noch Wasser auf den optischen Komponenten sammeln.
2.3 Direktverkabelung an IRmax-Detektor
Diese Option ist nur für den Betrieb mit 4-20 mA geeignet. Es ist eine Crowcon Montagehalterung
erforderlich, um den IRmax an einer Wand oder an einem 2” (50 mm)-Rohr anzubringen..
Diagramm 4: Kabelanschlüsse beim IRmax
Schließen Sie die Kabel mit einer zertifizierten Verschraubung über den gewählten Kabeleingang am
Gehäuse des IRmax-Detektors an (M20 oder 1/2" NPT). Crowcon empfiehlt, Verschraubungen nach
unten zeigend einzubauen.
Achten Sie darauf, Kabelverschraubungen mit
geeigneter Exd-Zulassung zu verwenden, und dass die
Gewindelänge das in dem Diagramm angegebene Maß
nicht überschreitet (links).
Signal
0V (Masse)
+V (24V IRmax)
15mm MAX
Status-LED
2. Installation
Deutsch
64
Detecting
Gas Saving Lives
2.3.1 Anschlussbezeichnung
Mit dem IRmax wie in Diagramm 2 auf Seite 60 ausgerichtet (M20 Kabel-Eingang oben) muss das
dreiadrige Kabel mit Hilfe des abnehmbaren Steckverbinders wie folgt abgeschlossen werden:
+24V unten, 0V in der Mitte, Signal oben.
Der 6-Stift-Steckverbinder auf der rechten Seite der Leiterplatte ist für Servicearbeiten und/oder
Anschluss eines IR Display-Moduls bestimmt.
Plus-Anschluss: Plus-Versorgung von der Steuerkarte
Signal-Anschluss: Signal von der Steuerkarte
0V-Anschluss Minus-Versorgung von der Steuerkarte
2.3.2 Installation vom IRmax-Detektor mit einer Montagehalterung
a. IRmax kann mit einer Montagehalterung (S012130) anstatt einer Doppelverschraubung
geliefert werden, damit das Gerät direkt an die Kabel angeschlossen werden kann (siehe
Diagramm 5).
Diagramm 5: IRmax-Detektor mit Montagehalterung und Verschraubung
b. Wenn der IRmax-Detektor auf einer flachen Oberfläche montiert werden soll, markieren
und bohren Sie zwei Löcher mit Hilfe der Montagehalterung als Schablone. Befestigen
Sie zwei Teile der Halterung lose mit für die Wand bzw. Oberfläche geeigneten
Befestigungsmitteln.
c. Entfernen Sie die wetterfeste Kappe vom IRmax und schieben Sie das Gehäuse des IRmax
durch die Halterung. Es wird empfohlen, das Gehäuse des IRmax-Detektors mit dem
Kabeleingang nach unten zeigend einzubauen.
Montagehalterung: 70
mm Befestigungsabstand.
M6-Schrauben verwenden.
2. Installation
Deutsch
65
Detecting Gas Saving Lives
d. Befestigten Sie die zwei Halterungen, so dass der IRmax-Detektor fest an seinem Platz
gehalten wird. Setzen Sie die wetterfeste Kappe wieder auf.
e. Sobald der IRmax-Detektor sicher angebracht worden ist, nehmen Sie die rückwärtige
Mutter des IRmax-Detektors ab, um den Zugang zu den Kabelanschlüssen zu ermöglichen.
f. Bereiten Sie das Kabel vor. Crowcon empfiehlt ein stahldrahtbewehrtes (SWA) 1,5 mm
2
-
Kabel (andere Kabeltypen können unter der Voraussetzung verwendet werden, dass sie
mit Exd-zugelassenen Verschraubungen kompatibel sind). Bringen Sie eine geeignete
zugelassene Exd-Kabelverschraubung an, führen Sie die Kabelleiter durch das Gehäuse
des IRmax-Detektors und schrauben Sie die Kabelverschraubung ein. Befestigen Sie die
Verschraubung und gewährleisten Sie, dass der Kabelmantel an der Kabelverschraubung
und dem IRmax-Detektor-Gehäuse geerdet ist. Hinweis: Vergessen Sie nicht, die
rückwärtige Mutter nach dem Einbau des Kabels wieder anzubringen.
g. Das Halteblech (Pos. 9 in Diagramm 3, Seite 61) muss sicher montiert werden, um jede
Gefahr, dass sich die hintere Mutter (oder Zubehörteil für stationäres IR Display oder IS
Barrieremodul) durch Vibrationen lockert, zu vermeiden.
2.4 Installation mit Doppelverschraubung und
Hilfsverteilerkasten
Diese Option ist erforderlich, wenn der IRmax-Detektor an einen vorhandenen zugelassenen Exe- oder
Exd-Hilfsverteilerkasten angeschlossen werden soll.
Diagramm 6: IRmax-Detektor am Verteilerkasten angeschlossen
2. Installation
Deutsch
66
Detecting
Gas Saving Lives
2.4.1 Anbringen des IRmax-Detektors an einem Hilfsverteilerkasten:
a. Nehmen Sie vorsichtig den äußeren Bereich der Doppelverschraubung ab (Punkt 8 in
Diagramm 3 auf Seite 61).
b. Schrauben Sie das schmale Ende der Doppelverschraubung in den Hilfsverteilerkasten.
c. Heben Sie den IRmax-Detektor auf Höhe des Hilfsverteilerkasten und führen Sie die
Kabel durch die Baugruppe und in den Hilfsverteilerkasten. Befestigen Sie den IRmax-
Detektor durch festes Anschrauben des Kragens an die Kabelverschraubung. Ziehen Sie die
Madenschraube an.
d. Das Hauptgehäuse des IRmax-Detektors kann (vorausgesetzt, es ist mechanisch sicher
befestigt, stört keine andere Anlagen und ist zur Wartung zugänglich) horizontal in
beliebigem Winkel geschwenkt werden.
e. Anleitung zur Verkabelung siehe Abschnitt 2.6. Siehe auch Diagramm 4 auf Seite 63.
2.5 Anforderungen an die Verkabelung
Die Verkabelung des IRmax-Detektors muss gemäß der anerkannten Standards der zuständigen
Aufsichtsbehörde in dem jeweiligen Land erfolgen und den elektrischen Anforderungen des IRmax-
Detektors entsprechen.
Crowcon empfiehlt die Verwendung von stahldrahtbewehrtem Kabel (SWA). Außerdem müssen
geeignete explosionssichere Verschraubungen verwendet werden. Alternative Verkabelungsmethoden
wie Stahlpanzerrohr, können zulässig sein, wenn die entsprechenden Normen erfüllt werden.
Die maximale empfohlene Kabellänge beträgt 3,4 km (siehe Tabelle 1).
Der IRmax-Detektor benötigt eine Gleichstromversorgung von 12-30 V DC. Achten Sie darauf, dass
mindestens 12 V am IRmax-Detektor von der Steuerkonsole anliegen und berücksichtigen Sie dabei
den Spannungsabfall aufgrund des Kabelwiderstands bei einer Spitzenstromstärke von 0,1 A.
Ein 1,5 mm
2
ermöglicht typischerweise Kabellängen von bis zu 3,0 km. Tabelle 1 unten zeigt die
maximalen Kabelentfernungen bei typischen Kabelparametern.
Querschnitt Widerstand Max. Entfernung
>20 V
Max. Entfernung
18 bis 20 V
mm
2
(Ohm pro km) (km) (km)
1,0 18,4 2,2 1,6
1,5 13,0 3,0 2,3
2,5 11,5 3,4 2,6
Tabelle 1: Maximale Kabelentfernung für typische Kabel
2. Installation
Deutsch
67
Detecting Gas Saving Lives
2.6 Verbindungen und Einstellungen
Alle beschriebenen Verbindungen beziehen sich auf den Anschlussblock, der im Hauptgehäuse des
IRmax-Detektor-Steckverbinders montiert ist. Die Anschlüsse der IRmax-Detektor-Steckverbinder-
Leiterplatte sind mit „+“, „sig“ und „0 V“ gekennzeichnet. Beim Anschluss des IRmax-Detektors an
die Steueranlage muss auf die korrekte Polarität geachtet werden.
Der IRmax-Detektor ist werkseitig als „stromziehendes“ Gerät eingestellt, wenn dies bei der
Bestellung nicht anderweitig angegeben wird. Um den IRmax-Detektor wieder auf „Stromquelle“
zurückzustellen, entfernen Sie die Rückplatte und setzen die beiden Verbindungsleiter an der
Anschlussleiterplatte von der Position „Sink“ (Senke) auf „Source“ (Quelle), wie in Diagramm 7
dargestellt.
Hinweis: Der externe Masseanschluss darf nur dort benutzt werden, wo lokale Behörden
eine derartige Verbindung zulassen oder verlangen. Soweit möglich müssen
Hilfsverteilerkasten und Kabelmantel zur Vermeidung von Hochfrequenzstörungen an der
Steuerkonsole (sicherer Bereich) geerdet werden, um Erdfehlerschleifen zu verhindern.
Diagramm 7: Lage der Senke-/Quelle-Verbindungsleiter
Das 4-20 mA-Signal kann mit den in Diagramm 7 abgebildeten Stiften und Verbindungsleitern
auf Strom-„Senke“ oder -„Quelle“ eingestellt werden. Durch Anbringen der Leitungsbrücke
zwischen Stiften 3 und 4 wie im linken Foto gezeigt auf Strom-„Sink“ setzen. Durch Anbringen der
Leitungsbrücke zwischen Stiften 1 und 2 wie im rechten Foto gezeigt auf Strom-„Source“ setzen.
IRmax-Detektoren sind auf Strom-„Senke“ eingestellt, wenn dies nicht bei Bestellung anderweitig
angegeben wird.
LED-Anzeige: In die Anschlussleiterplatte ist eine LED eingebaut, um den aktuellen
Betriebszustand anzuzeigen. Weitere Informationen siehe Abschnitt 6 auf Seite 73.
CONTROLLER
EARTH
+V
0V
Sg
3
21
Verdrahtung
Nummer Farbe Funktion
1 Rot +V
2 Schwarz 0V
3 Grün Signal
Verbindungsleiter-
einstellungen
Stecker für das IR Display
Stecker für das
PC-Kommunikationskit
Status-LED
Steuergerät
Quelle
Senke
Deutsch
68
Detecting
Gas Saving Lives
3. Betrieb
WARNHINWEIS
Vor der Ausführung aller Abeiten müssen Sie gewährleisten, dass die lokalen Bestimmungen
und Standortverfahren eingehalten werden. Versuchen Sie niemals, den IRmax-Detektor
oder Hilfsverteilerkasten bei Vorhandensein entflammbarer Gase zu öffnen. Gewährleisten
Sie, dass die zugehörige Steuerkonsole gesperrt ist, um falschen Alarm zu verhindern.
3.1 Inbetriebnahmeverfahren
1. Prüfen Sie, dass
a. die Kabelverbindungen korrekt sind
b. die Versorgungsspannung an der Steuerkarte auf 18 bis 30 V eingestellt ist. Die an den
IRmax-Detektor-Anschlüssen gemessene Spannung (innerhalb des Exe-Hilfsverteilerkastens,
falls verwendet, oder an der IRmax-Detektor-Anschlussleiterplatte) muss auf 12 bis 30 V
eingestellt werden.
c. die Verbindungsleiter sind auf 4-20 mA-Senke oder -Quelle (je nach Steuerkarte) eingestellt.
2. Sobald das Gerät hochgefahren worden ist, lassen Sie es 30 Minuten stehen, bevor Sie eine
Nullstellung bzw. Kalibrierung versuchen. Diese Verzögerung dient zur Sicherstellung der
thermischen Stabilität. (Hinweis: Der IRmax-Detektor ist 30 Sekunden nach dem Einschalten
vollständig betriebsbereit.)
3. Stellen Sie sicher, dass saubere Luft vorliegt (d.h. kein Kohlenwasserstoffgas), bevor Sie die
Nullstellung vornehmen. Nullen Sie den Messwert an der Steuerkarte (siehe Anleitung der
Steuerkarte).
4. Setzen Sie die Kalibrierungskappe über die wetterfeste Abdeckung, um die Messkammer von der
Umgebungsluft zu isolieren. Eine derartige Kappe ist bei Crowcon erhältlich (M041007). Schließen
Sie das Kalibrierungsgas (50% UEG-Nennwert) an und beaufschlagen Sie einen Durchfluss von 1 Liter
pro Minute.
5. Stellen Sie nach 30 Sekunden auf der Steuerkarte Kal/Span ein, so dass auf dem Display 50% LEL
(50% UEG) erscheint oder der Anzeigewert der beaufschlagten Kalibrierungsgaskonzentration
entspricht. Der IRmax-Detektor selbst benötigt keine Kalibrierung.
6. Entfernen Sie die Gas und Kalibrierungskappe. Überprüfen Sie die Nullstellung erneut.
7. Bei der Installation oder nach dem Austauschen des Spiegels kann der Detektor entweder mit
Hilfe eines IR Display-Zubehörs (siehe Seite 57) oder über eine PC-Kommunikationskit auf Null
gestellt und kalibriert werden.(siehe IRmax Zubehörhandbuch).
Hinweis: IRmax-Detektoren mit ATEX-Zulassung werden kalibriert nach EN61779 geliefert
(zum Beispiel 100% UEG Methan = 4,4 % Vol.).
Hinweis: Es wird empfohlen, die Kalibrierungskappe für die erste Inbetriebnahme
einzusetzen. Anschließende Kalibrierungen können durchgeführt werden, indem Gas mit
der wetterfesten Kappe im Fernbetrieb über den Anschlussnippel beaufschlagt wird (und
daher die Notwendigkeit des direkten Zugangs zum IRmax-Detektor entfällt). Kalibrierung
ohne Kalibrierungskappe (d.h. direkt über die wetterfeste Kappe kann durchgeführt
werden, wenn die lokale Windgeschwindigkeit weniger als 2 Meter/Sekunde beträgt. Der
Gasdurchfluss muss größer als 2,0 Liter/Minute sein.
3. Betrieb
Deutsch
69
Detecting Gas Saving Lives
3.2 Routinewartung
Die Frequenz, mit welcher die IRmax-Detektoren geprüft werden, wird von den am Standort
üblichen Praktiken vorgeschrieben. Crowcon empfiehlt eine Gasprüfung des IRmax-Detektors und
gegebenenfalls eine Neukalibrierung mindestens alle 6 Monate. Zur Neukalibrierung eines IRmax-
Detektors befolgen Sie die Schritte in Abschnitt 3.1.
Im Fall eines elektronischen Versagens wenden Sie sich bitte an Ihren lokalen Crowcon-Vertreter.
Kalibrierungsintervall: Crowcon empfiehlt, alle 12 Monate zu kalibrieren.
Fernkalibrierung über Rohr: Windgeschwindigkeit muss weniger als 2,0 Meter pro Sekunde
betragen. Falls die Windgeschwindigkeit höher ist, verwenden Sie
die Kalibrierungskappe, um eine Gasverdünnung zu verhindern.
Reinigung der Optik: Wird nicht empfohlen, es sein denn, der IRmax-Detektor zeigt
einen Verdeckungsfehler. Wenn das Fenster oder der Spiegel
verschmutzt sind, reinigen Sie sie sorgfältig mit Wasser (siehe
Abschnitt 5, Zubehör und Ersatzteile, auf Seite 72.).
Spiegel: Bei Beschädigung wenden Sie sich für den Ersatz an
Crowcon. (siehe Abschnitt 5, Zubehör und Ersatzteile, auf Seite 72.).
Der IRmax-Detektor muss nach jedem Spiegelersatz neu auf Null gestellt
und wieder kalibriert werden.
Falls Kondensation beginnt, zu Fehlern zu führen, ersetzen Sie den
Spiegel (es kann sein, dass die optische Beschichtung beschädigt ist).
Crowcon empfiehlt, den Spiegel alle 5 Jahre zu erneuern.
3.3 Ändern der Gasart
Jeder IRmax-Detektor wird für einen bestimmten Gastyp vorkalibriert geliefert (zum Beispiel Methan
oder Propan). Wenn eine Neukalibrierung für einen anderen Gastyp erforderlich ist, kann der IRmax
mit dem PC-Kommunikationskit (siehe Abschnitt 5, Zubehör und Ersatzteile, auf Seite 72.), neu
konfiguriert und dann kalibriert werden.
3. Betrieb
Deutsch
70
Detecting
Gas Saving Lives
3.4 Relatives Ansprechen auf Gasarten
Der unten abgebildete Graph zeigt das relative Ansprechen auf andere Gastypen für einen auf Methan
kalibrierten IRmax-Detektor.
Hinweis: Viele Kohlenwasserstoffgase und -dämpfe werden von IR-Detektoren einfacher als
Methan gemessen. Die Reaktion des IRmax (und anderer IR-Gasdetektoren) ist linear über den
Bereich 0-100% UEG für das Zielgas (d. h. in diesem Beispiel Methan), jedoch nicht linear für
andere Kohlenwasserstoffe, die vorhanden sein könnten.
Diagramm 8
Das Diagramm zeigt das Ansprechen auf die oben erwähnten Gase: von links nach rechts, Ethan,
Propan, Butan, Pentan und Methan.
Andere Gasarten und –bereiche sind verfügbar. Weitere Einzelheiten erhalten Sie von Crowcon.
Deutsch
71
Detecting Gas Saving Lives
4. Technische Daten
Gehäusematerial Edelstahl 316
Abmessungen (nur IRmax-Detektor) 150 mm x 75 mm x 66 mm (ohne Zapfen)
Gewicht IRmax 1,58 kg
IRmax mit permanentem IR Display 2 kg
IRmax mit IS-Barrieremodul 2,4 kg
Fern-IR Display 0,2 k
Betriebsspannung 12 VDC bis 30 VDC
Stromverbrauch < 1 W
Ausgang 3-adrig 4-20 mA (Senke oder Quelle)
Fehlersignal <1 mA
Max. Kabelschleifenwiderstand 80 Ohm (bezogen auf -ve-Klemme)
Betriebstemperatur -40°C bis +75°C (-40°F bis +167°F)
Luftfeuchtigkeit 0–100% relative Luftfeuchtigkeit
Schutzklasse IP66
Explosionsschutz Flammensicher
Zulassungscode
ATEX
IRmax-Detektor (ohne IR Display)
II 2 GD Exd db IIC T6 Gb (Tamb = -40°C bis +50°C)
II 2 GD Exd db IIC T4 Gb (Tamb = -40°C bis +75°C)
II 2 GD Ex tb IIIC T135°C Db (-40°C ≤ Ta≤ +75°C)
IRmax mit IS Barrieremodul (Fernbedienungsdisplay)
II 2 GD Exd db ia IIC T4 Gb (Tamb = -40°C bis +75°C)
Ex tb ia IIIC T135°C Db (Tamb = -40°C bis +40°C)
IRmax mit stationärem IR Display
II 2 G Exd db ia IIC T4 Gb (Tamb = -40°C bis +75°C)
Sicherheitszertifikat Nr.
ATEX und IECEx
IRmax-Detektor (ohne IR Display):
Baseefa 09ATEX0206X und IECEx BAS.09.0109X
IRmax-Detektor (mit IR Display):
Baseefa 09ATEX0220X und IECEx BAS.09.0104X
Funktionale Sicherheit Zum Einsatz in einem SIL-2-System zertifiziert.
Zertifikatnummer: Sira 12ATEX1206X
Normen EN 60079-0:2012+A11:2013, EN 60079-1:2014,
EN 60079-31:2014
IEC 60079-0:2011, IEC 60079-1:2014, IEC 60079-31:2013
EN 60079-29-1:2007, IEC 61508:2010, EN50402:2005
Zonen Für die Verwendung in Zone 1 oder Zone 2
zugelassen
EMC EN50270
Deutsch
72
Detecting
Gas Saving Lives
5. Zubehör und Ersatzteile
Teilenummer Name Beschreibung
M041007 Kalibrierungskappe Passt über die wetterfeste Standardkappe,
um die Kalibrierung zu ermöglichen, wenn
die lokale Luftgeschwindigkeit mehr als 2
Meter pro Sekunde beträgt.
S012130 Montagehalterungs-Kit Ermöglicht die Montage an einer Wand
oder einem 2” (50 mm)-Rohr. Nicht
erforderlich, falls der IRmax-Detektor
an einem vorhandenen Verteilerkasten
angebracht wird.
S012152 Sonnenschutz/
Kollektorkegel
Kann am IRmax-Detektor angebracht
werden, um das Gerät vor erhöhten
Temperaturen durch direkte
Sonneneinstrahlung zu schützen und/oder
den Empfangsbereich des Detektors für
den Nachweis von Gasen zu erweitern, die
leichter als Luft sind (Methan).
S012169 Kanaleinbauadapter Ermöglicht die Überwachung von Kanälen
mit einer Größe von 300 mm bis 3000 mm
und einer Luftgeschwindigkeit von 2 m/s
bis 20 m/s.
S012996 Strömungsadapter Für Gasprobenentnahmeanwendungen.
S012827 PC-Kommunikationskit Kommunikationsmodul, Software und
Kabel für die Konfiguration des IRmax-
Detektors.
M20: S012295
½” NPT: S012296
Hilfsverteilerkasten Montageoption für IRmax zur Verwendung
in Gefahrenbereichen.
C011210 Spiegelreinigungs-Kit Enthält mit Isopropanol imprägnierte
Wischtücher und Mikrofasertuch
IRmax-Detektor-Ersatzteile
Einzelheiten zu Ersatzteilen siehe Diagramm 3 auf Seite 61.
Deutsch
73
Detecting Gas Saving Lives
6. Fehlerbehebung
6.1 Von der LED angezeigte Fehler
Die an der Terminalplatine montierte LED kann bei der Identifikation von Fehlern helfen. Ihre Position
ist auf Diagramm 7 auf Seite 67 dargestellt. Die Tabelle unten zeigt, wie interpretiert wird, welchen
Fehler jedes Blinkmuster angibt.
LED-Muster IRmax-Detektor-Status Maßnahme
Blinkt regelmäßig einmal pro
Sekunde.
Intakt.
Leuchtet durchgehend mit
kurzen Unterbrechungen.
IRmax-Detektor im
Hochfahrmodus.
10 Sekunden warten.
Schnelles Blinken oder
unregelmäßiges Blinkmuster.
Versorgungsspannung
zu niedrig oder zu
hoch.
Stellen Sie sicher, dass die
Versorgungsspannung des IRmax-Detektors
richtig eingestellt ist. Gewährleisten Sie, dass
die Messung direkt an den IRmax-Detektor-
Anschlüssen erfolgt.
Leuchtet dauerhaft. Fehler, Host- oder
I-Modul-Fehler.
Schalten Sie den IRmax-Detektor aus
und wieder ein. Falls der Fehler immer
noch vorliegt, senden Sie das Gerät an
Crowcon ein.
Zweimaliges langes Blinken
gefolgt von einem kurzen
Blinken.
Fataler Fehler, Leuchten-
oder Detektorfehler.
Senden Sie das Gerät an Crowcon
zurück.
Schnelles Doppelblinken jede
Sekunde.
Fataler Fehler,
Modul- oder
Konfigurationsfehler.
Prüfen Sie die Detektorkonfiguration
mit Hilfe der PC-Kommunikationskit-
Software.
Prüfen Sie die Stromversorgung.
Falls der Fehler immer noch vorliegt,
senden Sie das Gerät an Crowcon.
Blinkt einmal pro Sekunde
kurz auf.
Optik verschmutzt. Fenster und Spiegel prüfen und
gegebenenfalls reinigen. Detektor
erneut auf Null stellen und Kalibrierung
prüfen.
Alle anderen Fehler können nur korrigiert werden, indem der IRmax-Detektor an Crowcon oder einen
autorisierten Kundendienstvertreter eingesendet wird.
6.2 Analogausgang
IRmax wird im Fehlerstatus bleiben und es wird außerdem „Service erforderlich“ (Service required)
auf dem IR Display (falls vorhanden) angezeigt, wenn das Analogausgang-Signal ausgefallen
oder nicht mit einem Steuersystem oder Lastwiderstand verbunden ist. IRmax überwacht das 4-20
mA-Analogausgang-Signal aktiv, um sicherzustellen, dass es sich im zulässigen Bereich befindet. Wenn
das Signal außerhalb des Bereichs liegt, geht der Detektor in den Fehlerzustand über und der Ausgang
wird auf 1 mA gestellt. Daher ist es beim Testen eines Detektors wesentlich, dass er entweder mit
einer Steuerkonsole verbunden wird oder ein 100 Ω-Lastwiderstand zwischen den „0 V“ und „Sig“-
Anschlüssen (Detektor auf Modus „Quelle“ gestellt) oder zwischen den „0 V“ und „+V“-Anschlüssen
(Detektor auf Modus „Senke“ gestellt) angeschlossen wird.
Deutsch
74
Detecting
Gas Saving Lives
7. RS485-Modbuskonfiguration
7.1 Allgemeines
Dieser Abschnitt erklärt, wie IRmax-Detektoren in einer Modbus-Konfiguration verwendet werden. Für
solche Anwendungen ist eine RS485-Version erhältlich. Es können bis zu 28 Detektoren in einer Stern-
oder Bus-Konfiguration wie unten beschrieben miteinander verbunden werden.
Der Anschluss an die RS465-Version des IRmax-Detektors muss über eine Doppelverschraubung an
einen Hilfsverteilerkasten erfolgen (siehe Abschnitt 5 auf Seite 72.), anstatt über Direktverkabelung
in den IRmax-Detektor.
Bitte beachten Sie, dass das IR Display nicht mit dem RS485-IRmax benutzt werden kann.
Die RS-485-Version des IRmax-Detektors hat fünf Feldanschlüsse. Die Anschlüsse sind:
1 Positive Versorgung 12 V bis 30 V über 0 V
2 0 V Rückleitung und RS-485-Referenz
3 4-20 mA-Signal Quellen- oder Senkensignal (optional)
4 RS485 B RS485-Differenzialsignal
5 RS485 A RS485-Differenzialsignal
Die Signale an den RS-485-Anschlüssen entsprechen der EIA/TIA-485-Norm, die besagt, dass der
Gleichtaktbereich bezüglich des 0V-Anschlusses von –7V bis +12V reicht.
Beachten Sie, dass sich nicht alle RS-485-Hersteller über die Polarität der A- und B-Signale einig sind.
Wenn die Verkabelung nicht auf die eine Weise funktioniert, müssen die Anwender die RS-485-A- und
-B-Kabel vertauschen. Es besteht kein Risiko darin, eine falsche Verbindung herzustellen.
Die Kommunikationseinstellungen sind 9600 bps, zwei Stopp-Bits und keine Parität.
Wenn eine Schnittstelle für ein Steuersystem kompiliert wird, ist es wesentlich, die Zeitspanne zu berücksichtigen,
die das System benötigt, um nacheinander Informationen von jedem Detektor zu sammeln. Die schnellste
Geschwindigkeit, mit der mehrere Detektoren zyklisch abgefragt werden können, beträgt 14 Detektoren pro
Sekunde. Unter praktischen Umständen kann sich dieser Wert auf 7 Detektoren pro Sekunde reduzieren. Anwender
müssen gewährleisten, dass die Anordnung erlaubt, dass Alarmsignale innerhalb zulässiger Zeitgrenzen registriert
werden.
Es ist außerdem wichtig sicherzustellen, dass das System ausreichend Leistung bereitstellen kann, damit
alle Detektoren funktionieren können. Zur Berechnung der erforderlichen Leistung bei einer linearen
Busverbindung, siehe Abschnitt 7.3, Anforderungen an die Verkabelung, auf Seite 76.
Die vollständige Modbus-Anleitung erhalten Sie von Crowcon (siehe Anschrift auf der Rückseite).
7. RS485 Modbus configuration
Deutsch
75
Detecting Gas Saving Lives
7.2 Verkabelungstopologie
Zwei häufig verwendete Verkabelungstopologien sind die Sternverbindung und der lineare Bus.
7.2.1 Sternverbindung
Bei einer Sternverbindungstopologie sind alle IRmax-Detektoren mit einem zentralen Punkt verkabelt,
der normalerweise die Steuerkonsole ist. Es sind keine Kabel erforderlich, um mehr als 5 Kerne zu
haben, da alle 4-20 mA-Signalverbindungen direkt zur Steuerkonsole geführt werden.
Die RS-485-A- und -B-Signale können dann alle im Sternpunkt miteinander verbunden werden. Der
Bus muss anschließend im Sternpunkt mit einem einzelnen 110 Ohm-Abschlusswiderstand beendet
werden.
Die Länge jedes Sternarms darf 750 Meter nicht überschreiten.
7.2.2 Lineare Busverbindung
Bei einer Busverbindungstopologie sind alle IRmax-Detektoren in einer linearen Anordnung verkabelt,
normalerweise mit der Steuerkonsole an einem Ende. Eine klassische Situation ist eine Tunnelinstallation
mit Detektoren, mit IRmax in regelmäßigen Abständen montiert (siehe Diagramm 9 unten).
Zur Verkabelung der Installation müssen zwei 110 Ohm-Abschlusswiderstände an jedem physikalischen
Ende des Busses angebracht werden.
Da die 4-20 mA-Signale nicht gemeinsam genutzt werden können, ist an jedem Verkabelungs-Hop ein
zusätzlicher Leiter erforderlich. Falls keines der 4-20 mA-Signale verwendet wird, sind nur vier Leiter
erforderlich.
Diagramm 9
ZUR
STEUERKONSOLE
LINEARES BUSVERBINDUNGS-DIAGRAMM
7. RS485 Modbus configuration
Deutsch
76
Detecting
Gas Saving Lives
7.3 Anforderungen an die Verkabelung
7.3.1 Berechnung der erforderlichen Mindestleistung
Je mehr IRmax-Detektoren an einen linearen Bus angeschlossen werden, um so mehr Leistung ist für
den Betrieb des Systems erforderlich. Zur Berechnung der für eine bestimmte Anordnung erforderlich
Leistung muss der Kabelwiderstand zwischen jedem IRmax-Detektor-Paar bekannt sein. Für jeden
„Hop“ zwischen den IRmax-Detektoren muss eine Stromstärke von mindestens 0,1 mA erlaubt sein.
Die anzulegende Spannung kann durch Schätzung des Spannungsabfalls über jeden „Hop“ berechnete
werden. Am Ende müssen mindestens 12 V übrig bleiben, um zu gewährleisten, dass der letzte IRmax-
Detektor korrekt funktioniert.
Ratschläge in speziellen Fällen erhalten Sie bei Crowcon. Alternativ befolgen Sie die unten
beschriebenen Schritte und die Beispielberechnung im nächsten Abschnitt.
1. Die Spannung darf nicht unter 12 V fallen. Deshalb beginnen Sie die Berechnung, indem Sie die
Spannung am letzten IRmax-Detektor in der Reihe auf diesen Wert setzen.
2. Jeder IRmax-Detektor darf bis zu 0,1 A ziehen. Berechnen Sie den Kabelspannungsverlust des
ersten „Hop“ zwischen den IRmax-Detektoren, indem Sie die „akkumulierte Stromstärke“ als 0,1
A annehmen und diesen Wert mit dem Kabelwiderstand des „Hop“ zwischen dem letzten und
vorletzten Detektor multiplizieren
3. Addieren Sie diesen Spannungsverlust zu den anfänglichen 12 V, um die niedrigste zulässige
Spannung am vorletzten IRmax-Detektor zu erhalten. Addieren Sie 0,1 A zu dem Wert für die
„akkumulierte Stromstärke“, um 0,2 mA zu erhalten, die Mindeststromstärke, die durch den
vorletzten „Hop“ des Busses laufen muss. Multiplizieren Sie diesen Wert mit dem Kabelwiderstand
für den vorletzten „Hop“, um den nächsten Spannungsabfall zu erhalten.
4. Wiederholen Sie diesen Vorgang für jeden Detektor und addieren Sie die Spannungsverluste, die
zwischen jedem Detektorpaar auftreten werden.
5. Die maximale Detektorspannung von 30 V darf nicht überschritten werden.
7.3.2 Beispielberechnung
Als Beispiel folgen die Ergebnisse der Berechnung für sechs IRmax-Detektoren in gleichem Abstand von
250 m und mit einem Kabel einer Querschnittsfläche von 1 mm2 verbunden. Jeder „Hop“ hat einen
Widerstand von 4,6 Ohm.
Station Versorgungs-spannung Versorgungs-stromstärke
1 12 0,1 A
2 12,46 0,2 A
3 13,38 0,3 A
4 14,76 0,4 A
5 16,6 0,5 A
6 18,9 0,6 A
Konsolen-versorgung 21,66 0,6 A
Deutsch
77
Detecting Gas Saving Lives
8. Handbuch für funktionale Sicherheit
8.1 Einführung
Die folgenden Abschnitte enthalten genauere Angaben zu der Zertifizierung des IRmax gemäß
den Normen für funktionale Sicherheit IEC 61508 und EN 50402. Informationen werden zu den
Funktionen, die im Sicherheitsfall berücksichtigt werden, zu Wartungsanforderungen und Daten
gegeben, um die Integration des IRmax in ein sicherheitstechnisches System (SIS) zu ermöglichen.
8.2 IRmax und IRmax Modbus Sicherheitsfunktion
Messung der Konzentration eines brennbaren Gases und Anzeige der Messung über einen
4-20-mA-Ausgang.
Fehler im Hinblick auf die Sicherheitsfunktion werden von der Hardware und zugehöriger Firmware
erkannt. Sie werden als Ausgangssignal unter 3,6 mA oder über 21 mA gezeigt.
8.3 Daten zur funktionalen Sicherheit
Parameterbezeichnung Symbol Gleichung/Quelle IRmax
Intervall von
Wiederholungsprüfungen
T1 Nach Festlegung von Crowcon.
8.760 Stunden
(jährlich)
Mittlere Reparaturzeit MTTR MTTR Nach Festlegung von Crowcon. 8 Stunden
Typ A/B Typ A Nach Festlegung von Crowcon. Typ B
Gesamtausfälle:
λ
Aus FMEDA 1.04E-05
Entdeckte ungefährliche Ausfälle: λ
SD
Aus FMEDA 1.95E-08
Unentdeckte ungefährliche Ausfälle: λ
SU
Aus FMEDA 8.59E-08
Entdeckte gefahrbringende Ausfälle: λ
DD
Aus FMEDA 9.74E-06
Unentdeckte gefahrbringende Ausfälle: λ
DU
Aus FMEDA 5.06E-07
Ungefährliche Ausfälle: λ
NE
Aus FMEDA 3.21E-09
Diagnosedeckungsgrad: DC λ
DD
/ (λ
DU
+ λ
DD
) 95.06%
Anteil ungefährlicher Ausfälle (SFF): SFF (λ
SD
+ λ
SU
+ λ
DD
) / λ 95.11%
Kanaläquivalente Ausfallzeit t
CE
DU
/ λ
D
)(T/2 + MTTR) +
(λ
DD
/ λ
D
) MTTR
2.24E+02
PFDAVG (anhand Gleichung aus
61508-6)
PFD
AVG
DU
+ λ
DD
) t
CE
2.30E-03
PFDAVG (anhand vereinfachter
Gleichung)
PFD
AVG
λ
DU
(T / 2+MTTR) + (λ
DD
MTTR) 2.30E-03
PFDAVG (anhand Gleichung aus IEC
61508-6)
PFD
AVG
1-ε
-(λdd+λdu) tce
2.30E-03
SIL (Betriebsart mit niedriger
Anforderungsrate)
SIL2
SIL (Betriebsart mit hoher
Anforderungsrate)
SIL2
Bei Anwendungen mit niedriger Anforderungsrate sind im Hinblick auf zufällige Hardwarefehler
und den Anteil ungefährlicher Ausfälle alle Varianten des Systems für den Einsatz in SIL-2-
Anwendungen geeignet.
Handbuch für funktionale Sicherheit
Deutsch
78
Detecting
Gas Saving Lives
8.4 Hardwarekonfiguration
Weg 1H (Hardwarefehlertoleranz und Anteil ungefährlicher Ausfälle) wurde zur Beurteilung des Safety
Integrity Level der Hardware verwendet.
8.5 Softwarekonfiguration
Die Beurteilung der Produktfirmware erfolgte gemäß den Anforderungen aus IEC 61508:3 2010.
8.6 Systematische Ausfälle
Weg 1S (laut Festlegung in IEC 61508:2 2010 Absatz 7.4.2.2c) wird zur Prüfung der Einhaltung der
Anforderungen zur Vermeidung systematischer Ausfälle verwendet.
8.7 Diagnoseintervall
Die meisten Diagnosefunktionen werden kontinuierlich überwacht.
Tests des System-Watchdog sind während der jährlichen Wiederholungsprüfung durch Aus- und
Einschalten des Geräts durchzuführen. IRmax muss als Teil des Wartungsprogramms für das Produkt
jährlich aus- und eingeschaltet werden (d. h. die 24-Vdc-Versorgung trennen und wieder anlegen)
(siehe auch Abschnitt 3.2).
8.8 Beschränkungen
Ausfallraten sind konstant.
Eine Wiederholungsprüfung, die mindestens einmal pro Jahr durchgeführt wird, identifiziert alle nicht
gefundenen Fehler.
Reparaturen haben eine mittlere Reparaturzeit von 8 Stunden.
Es wird davon ausgegangen, dass der Benutzer die Diagnosefunktion nutzt, die über das IR Display-
Zubehör und/oder die PC-Schnittstelle bereitgestellt wird, um die mögliche Ausfallzeit des Produkts
zu minimieren.
Die Zuverlässigkeitsbeurteilung ist ein statistischer Prozess zur Anwendung historischer Ausfalldaten
auf geplante Konstruktionen und Konfigurationen. Es bietet daher einen voraussichtlichen Soll-/
Schätzwert der wahrscheinlichen Zuverlässigkeit von Geräten unter der Annahme, dass Herstellungs-,
Konstruktions- und Betriebsbedingungen identisch mit denen sind, unter denen die Daten erfasst
wurden. Es ist ein wertvolles Verfahren der Konstruktionsüberprüfung zum Vergleich alternativer
Konstruktionen, zur Ermittlung von Leistungszielen im Hinblick auf die Größenordnung und zur
Auswertung der möglichen Einflüsse von Konstruktionsänderungen. Die tatsächlich vorhergesagten
Werte können jedoch nicht garantiert werden, da die Prognose der genauen Zahl von Ausfällen
im Feld, die auftreten werden, nicht möglich ist, da dies von Faktoren abhängt, die außerhalb der
Kontrolle einer prädiktiven Prüfung liegen.
Ausfallraten (Symbol λ) werden zum Zwecke dieser Vorhersage als im Zeitverlauf konstant
angenommen. Sowohl frühzeitige Ausfälle als auch verschleißbezogene Ausfälle senken die
Zuverlässigkeit, es wird jedoch davon ausgegangen, dass sie durch Burn-in bzw. vorbeugenden
Austausch vermieden werden.
Handbuch für funktionale Sicherheit
Deutsch
79
Detecting Gas Saving Lives
Die Wahrscheinlichkeit eines Ausfalls im Anforderungsfall PFD ist die Wahrscheinlichkeit, dass das
System in einem zufälligen Moment einen Fehlerzustand aufweist. Dies ist synonym mit der stationären
Nichtverfügbarkeit. Diese wird gegeben durch:
Nichtverfügbarkeit = (λ x MDT)/(1 + (λ x MDT))
die bei kleinen Werten von λ x MDT ungefähr gleich λ x MDT ist
wobei λ die Ausfallrate und MDT die mittlere Ausfallzeit ist.
Dies stimmt mit dem Ausdruck für Verfügbarkeit überein. Diese wird gegeben als: MTBF/(MTBF+MDT)
Die verwendeten Ausfallraten und die so abgeleiteten Verfügbarkeiten sind die Werte, die zuverlässig
nach einer geeigneten Zeitdauer mit Zuverlässigkeitswachstum mit einer bewährten Konstruktion
verbunden sind.
8.9 Umgebungsbedingungen
Umgebungsbeschränkungen:
Das Produkt darf in einem maximalen Umgebungstemperaturbereich von -40 °C bis
+75 °C betrieben werden.
Das Produkt darf in einem maximalen Umgebungstemperaturbereich von -40 °C bis
+80 °C gelagert werden.
Das Produkt darf in einem maximalen relativen Luftfeuchtigkeitsbereich der Umgebung
von 0 % bis +100 % bei Kondensation betrieben werden.
Das Produkt besitzt gemäß den Festlegungen der Norm EN 60529 eine Schutzart von
IP66.
Das Produkt ist für Dauerbetrieb ausgelegt.
8.10 Hardwarefehlertoleranz
Die HFT ist 0.
8.11 Systematische Eignung
Der IREX/IRmax hat Klasse SC2.
8.12 Klassifizierung
Der IREX/IRmax ist ein Typ-B-Gerät.
Deutsch
80
Detecting
Gas Saving Lives
Garantie
Dieses Gerät hat unser Werk vollständig geprüft und kalibriert verlassen. Wenn innerhalb der
Garantiezeit von drei Jahren nach Versand nachgewiesen wird, dass das Gerät aufgrund von
fehlerhafter Ausführung oder fehlerhaftem Material defekt ist, reparieren oder ersetzen wir das Gerät
nach unserem Ermessen kostenlos unter den unten genannten Bedingungen.
Garantieverfahren
Um die effiziente Verarbeitung aller Ansprüche zu erleichtern, kontaktieren Sie bitte unser
Kundendienstteam unter der Telefonnummer +44 (0)1235 557711 mit den folgenden Informationen:
Name, Telefonnummer, Faxnummer und E-Mail-Adresse Ihres Kontakts.
Beschreibung und Menge der zurückgesendeten Waren einschließlich allen Zubehörs.
Seriennummer(n) der Geräte.
Grund für die Rücksendung.
Besorgen Sie sich ein Rücksendeformular zu Identifikations- und Nachverfolgbarkeitszwecken. Dieses
Formular kann von unserer Website crowconsupport.com zusammen mit einem Rücksendeetikett
heruntergeladen werden. Alternativ können wir Ihnen eine Kopie per E-Mail zusenden.
Es werden nur IRmax-Detektoren mit einer Crowcon Rücksendenummer (CRN) zur Garantie
angenommen. Es ist wesentlich, dass das Anschriftsetikett sicher an der Außenverpackung
der zurückgesendeten Waren befestigt wird.
Die Garantie erlischt, wenn das Gerät verändert, modifiziert, zerlegt worden ist oder anderweitige unbefugte
Eingriffe vorgenommen worden sind. Die Garantie beinhaltet weder falsche Benutzung noch Missbrauch
des Geräts.
Garantieausschluss
Crowcon übernimmt keine Haftung für Folgeschäden oder indirekte Verluste oder Schäden aus
beliebigem Grund (einschließlich aller Verluste oder Schäden, die aus der Benutzung des Geräts
entstehen) und es wird ausdrücklich jegliche Haftung bezüglich dritter Parteien ausgeschlossen.
Diese Garantie bezieht sich nicht auf die Genauigkeit der Kalibrierung des Geräts oder das
kosmetische Aussehen des Produkts. Das Gerät muss in Übereinstimmung mit den Betriebs- und
Wartungsanweisungen unterhalten und gewartet werden.
Die Garantie über den Ersatz von Verbrauchsmaterialien (wie dem Spiegel), die im Rahmen der
Garantie für den Ersatz fehlerhafter Artikel geliefert werden, ist auf die nicht abgelaufene Garantie des
Originalartikels beschränkt.
Crowcon behält sich das Recht vor, eine reduzierte Garantiezeit festzulegen oder eine Garantiezeit
für alle Sensoren abzulehnen, die zur Verwendung in einer Umgebung oder für eine Anwendung
geliefert worden sind, die bekanntermaßen ein Risiko der Verschlechterung oder Beschädigung des
Sensors beinhaltet.
Unsere Haftung bezüglich defekter Anlagen beschränkt sich auf die in der Garantie enthaltenen
Verpflichtungen und alle erweiterten Garantien, Bedingungen oder Erklärungen, ausdrücklich
oder implizit, gesetzlich vorgeschrieben oder sonstiger Art bezüglich der marktüblichen Qualität
unserer Anlage oder ihrer Eignung für einen bestimmten Zweck sind (ausgenommen wie gesetzlich
vorgeschrieben) ausgeschlossen. Diese Garantie beeinträchtigt nicht die gesetzlichen Rechte eines
Kunden.
Garantie
Deutsch
81
Detecting Gas Saving Lives
Crowcon behält sich das Recht vor, eine Bearbeitungs- und Frachtgebühr zu berechnen, wenn als
fehlerhaft eingesendete Geräte nur eine normale Kalibrierung oder einen Kundendienst erfordern,
deren Durchführung der Kunde dann ablehnt.
Bei Fragen zur Garantie und technischem Support wenden Sie sich bitte an:
Kundendienst
Tel: +44 (0) 1235 557711
Fax: +44 (0) 1235 557722
Índice
Concepto y seguridad ................................................................................ 85
Concepto de detector IRmax ............................................................. 85
Información de seguridad .................................................................... 86
Descripción del producto ..................................................................... 87
1. Introducción ........................................................................................... 88
1.1 General ......................................................................................... 88
1.2 Descripción del producto............................................................... 88
2. Instalación .............................................................................................. 90
ADVERTENCIA ..................................................................................... 90
2.1 Ubicación ..................................................................................... 90
2.2 Montaje ....................................................................................... 91
2.3 Cableado directo al detector IRmax ............................................ 91
2.3.1 Designación de terminal ....................................................... 92
2.3.2 Instalación del detector IRmax utilizando un soporte de montaje .. 92
2.4 Instalación utilizando un pasacables de espiga y una caja de
conexiones auxiliar .............................................................................. 93
2.4.1 Para instalar el detector IRmax en una caja de conexiones
auxiliar: ......................................................................................... 94
2.5 Requisitos de cableado ................................................................. 94
2.6 Conexiones y ajustes .................................................................... 95
3. Funcionamiento ...................................................................................... 96
3.1 Procedimiento de puesta en servicio ............................................ 96
3.2 Mantenimiento rutinario .............................................................. 97
3.3 Cambio de tipos de gas ............................................................... 97
3.4 Respuestas relativas de tipos de gas ............................................. 98
4. Especificaciones ...................................................................................... 99
5. Accesorios y repuestos ........................................................................ 100
6. Detección de errores ........................................................................... 101
6.1 Errores indicados por LED ............................................................ 101
6.2 Salida analógica .......................................................................... 101
7. Configuración de RS485 Modbus ........................................................ 102
7.1 General ....................................................................................... 102
7.2 Topología del cableado .............................................................. 103
7.2.1 Conexión en estrella .......................................................... 103
7.2.2 Conexión de bus lineal ...................................................... 103
7.3 Requisitos de cableado ............................................................... 104
7.3.1 Cálculo del nivel mínimo de potencia requerida .................. 104
7.3.2 Cálculo de muestra ........................................................... 104
8. Manual de seguridad funcional ............................................................ 105
8.1 Prólogo ....................................................................................... 105
8.2 Función de seguridad del IRmax y del IRmax Modbus.................. 105
8.3 Datos de seguridad funcional ...................................................... 105
8.4 Configuración de hardware......................................................... 106
8.5 Configuración de software .......................................................... 106
8.6 Fallos sistemáticos ....................................................................... 106
8.7 Intervalo de diagnósticos ............................................................. 106
8.8 Restricciones ............................................................................... 106
8.9 Medio ambiente .......................................................................... 107
8.10 Tolerancia de fallo de hardware ................................................ 107
8.11 Capacidad sistemática ............................................................... 107
8.12 Clasificación .............................................................................. 107
Garantía ................................................................................................... 108
Español
85
Detecting
Gas Saving Lives
Concepto y seguridad
Concepto de detector IRmax
El detector IRmax es un detector de gases por infrarrojos (IR) ultracompacto que proporciona
detección rápida y fiable de gases y vapores de hidrocarburos.
Incorporando tecnología de sensor por infrarrojos de longitud de onda doble en una resistente cubierta de acero
inoxidable 316, el detector IRmax está diseñado para funcionar en las condiciones más duras. A diferencia de
detectores de gas por infrarrojos convencionales, el detector IRmax no incorpora calentadores para prevenir
la condensación en ventanas y espejos. El revestimiento STAY CLIR de los componentes ópticos previene la
formación de condensación mientras el detector está funcionando.
El detector IRmax es compatible con cualquier sistema de control de 4-20mA y también puede
instalarse en una red direccionable Modbus RS485 (véase Sección 7).
El detector IRmax requiere sólo 1 W de potencia, típicamente 75-90% menos que los detectores
de gas por infrarrojos convencionales.
El detector IRmax incorpora una cámara compacta de difusión de gas, que combinada con una
eficaz tapa impermeable proporciona una velocidad de respuesta excelente. La tapa impermeable
ha sido diseñada utilizando software de modelización de flujo para permitir la gasificación y
calibración del detector sin necesidad de una tapa de calibración especial.
La IR Display permite monitorizar lecturas del IRmax tanto localmente como remotamente. Es
posible instalar directamente una IR Display en el IRmax. De forma alternativa, la IRmax puede
suministrarse con un módulo de barrera intrínsecamente segura (IS) instalado. Entonces una IR
Display puede conectarse al módulo de barrera IS mediante un cableado temporal o permanente.
Las opciones disponibles se ilustran en el Diagrama 3 en la página 89.
Para obtener información adicional sobre otros accesorios para el IRmax, véase la Diagrama 3, página
89 y la Sección 5, página 100.
Concepto y seguridad
86
Detecting
Gas Saving Lives
Español
Información de seguridad
Los detectores de gas IRmax deben instalarse, utilizarse y mantenerse siguiendo rigurosamente
estas instrucciones, advertencias e información de etiquetas y dentro de los límites indicados.
La tuerca trasera del detector IRmax debe mantenerse bien apretada durante su
funcionamiento. No intente retirar la tuerca trasera hasta que se haya desconectado la
corriente del detector - en caso contrario puede producirse el encendido de un entorno
inflamable. Antes de retirar la tuerca para realizar mantenimiento, calibración o servicio,
compruebe que en el entorno no hay gases o vapores inflamables. No lo abra hasta varios
minutos después de que se haya desconectado la corriente.
Las operaciones de mantenimiento y calibración sólo deben ser realizadas por personal de servicio
cualificado.
Sólo deben utilizarse piezas de repuesto auténticas de Crowcon; otros componentes pueden
invalidar la certificación y la garantía del detector IRmax.
Los detectores IRmax deben ser protegidos contra vibraciones extremas y los rayos directos
del sol en entornos calientes ya que esto puede causar que la temperatura del detector IRmax
supere los limítes especificados y cause un fallo prematuro.
El detector IRmax no detecta hidrógeno, amoníaco o dióxido de carbono.
El equipo debe conectarse a tierra utilizando el pasacables y el cable blindado de acero.
Certificación para entornos de polvo Zona 21/22: El IRmax básico (sin IR Display o su módulo
de barrera IS) puede utilizarse en entornos que pueden contener polvos peligrosos (Zonas 21
ó 22).
El IRmax con un módulo de barrera IS puede utilizarse en Zonas 21 ó 22 siempre y cuando
la temperatura ambiente permanezca por debajo de 40°C y se instale/utilice una IR Display
remota o varias IR Display manuales fuera del área peligrosa solamente.
No puede instalarse un IRmax con una IR Display fija en un área de Zona 21 ó 22.
Concepto y seguridad
87
Detecting
Gas Saving Lives
Español
Descripción del producto
El detector IRmax es un detector de gas por infrarrojos diseñado para detectar gases de
hidrocarburos comunes dentro de la gama de 0 a 100% de LEL (Lower Explosive Limit - Límite
explosivo inferior: la concentración mínima en aire a la que puede ocurrir inflamación).
El detector IRmax es un detector antideflagrante (Exd) certificado adecuado para utilizarse en
zonas peligrosas Zona 1 ó Zona 2 ATEX . Consulte la etiqueta de certificación en el lateral del
detector para identificar el tipo de certificación relacionada con el producto suministrado.
Nota: Si el detector IRmax no incorpora una etiqueta de certificación, el detector no está
certificado para uso en áreas peligrosas.
Diagrama 1: Etiquetas de certificación del detector IRmax
0811
.TNESERP EB YAM EREHPSOMTA EVISOLPXE NEHW NEPO TON OD :GNINRAW
04- = bmaT( bG 4T CII bd xE 57+ ot C )C
W5=xamW V23=xamV
04- = bmaT
( bG 6T CII bd xE 05+ ot C )C
X9010.90 SAB xECEI X6020XETA90afeesaB
X6021XETA21 ariS 2LIS
DS4 41XO ,modgniK deitnU ,nodgnibA
DG2 II
ROTCETED SAG RI
)C°57+ aT C°04-( bD C°531T CIII bt xE
°°
°
°
Etiqueta de certificación de IRmax básico
Ex db ia IIC T4 Gb (-40°C Ta +75°C)
Vmax=32V Wmax=5W
WARNING: DO NOT OPEN WHEN EXPLOSIVE ATMOSPHERE MAY BE PRESENT.
IR G A S DET E C TOR W I TH R E M OTE D I SPL A Y
Baseefa09ATEX0220X IECEx BAS 09.0104X
Abingdon, United Kingdom, OX14 4SD
1180
II 2GD
Ex tb ia IIIC T135
°C Db (-40°C Ta +40°C)
IRmax con su etiqueta de certificación
de barrera
+75°C)Ex db ia IIC T4 Gb (-40°C Ta
II 2G
1180
Abingdon, United Kingdom, OX14 4SD
Baseefa09ATEX0220X IECEx BAS 09.0104X
IR GA S DE TECT OR WI TH D ISPL AY
WARNING: DO NOT OPEN WHEN EXPLOSIVE ATMOSPHERE MAY BE PRESENT.
Vmax=32V Wmax=5W
IRmax con etiqueta de certificación de IR Display fija
Español
88
Detecting
Gas Saving Lives
1. Introducción
1.1 General
La configuración de cada IRmax se identifica por una etiqueta colocada en el cuerpo principal.
Cuando contacte con Crowcon para obtener asesoría o repuestos, indique el nombre del
producto, el número de pieza y el número de serie.
1.2 Descripción del producto
El detector IRmax comprende un cuerpo principal de acero inoxidable 316, una cubierta
impermeable antiestática sobre la óptica y la cámara de medición de gas y un conjunto electrónico.
También se le puede instalar un módulo IR Display. Las instrucciones para instalar la IR Display
se muestran en el manual de la IR Display (M07061).
Puede suministrarse un pasacables de conexión opcional para permitir que el detector IRmax se
instale directamente en cajas de conexiones auxiliares con entradas de cable M20 o NPT de ½”.
Todas las dimensiones se expresan en milímetros
Diagrama 2: Vista dimensionada del detector IRmax
Nota: el cuerpo del detector IRmax se suministra con dos entradas de cable: una es M20,
la otra NPT de 1/2". La entrada de cable no especificada cuando se pide un detector IRmax
se sellará utilizando un tapón certificado. El IRmax debe instalarse con ambas entradas de
cable selladas: una con un pasacables, la otra con un tapón certificado con nominal IP66.
157.5
74.5
136
60.5
Pasacables opcional
57
en total
158 en total
74,5
136 en total
Pasacables M20 o
NPT de 1/2"
Terminal de
conexión a tierra
externa (TIERRA)
1. Introducción
89
Detecting
Gas Saving Lives
Español
Diagrama 3: Despiece del detector IRmax (números de pieza mostrados si es aplicable)
Tapa de calibración M041007
Tapa impermeable M04995
Retenedor de espejo
Espejo
Adaptador de flujo S012996
Junta tórica para tuerca trasera, módulo de barrera IS o módulo de IR Display fija: M040077
Soporte de montaje como conjunto completo S012130
Pasacables versiones M20 o NPT de 1/2" : M20 ATEX: S012147, 1/2" NPT ATEX: S012190
Placa de retención y tornillos para tapón trasero, IR Display fija y módulo de barrera IS.
10
Versión fija de la IR Display
11
Conector de la IR Display al detector IRmax E07987
12
Módulo Barrera
13
Cable de conexión de la IR Display
14
Zócalo de montaje de la IR Display remota M03833
15
IR Display remota
}
Suministrados juntos como ‘kit de repuesto de espejo’
C011206
10
11
12
13
14
15
Español
90
Detecting
Gas Saving Lives
2. Instalación
ADVERTENCIA
Este detector ha sido diseñado para utilizarse en áreas peligrosas de Zona 1 y Zona
2, la certificación depende de los accesorios instalados y la temperatura ambiente
de funcionamiento. Para obtener los detalles de la certificación, consulte la tabla de
especificaciones de la página 99. La instalación debe realizarse de acuerdo con las
normas reconocidas de la autoridad apropiada del país en cuestión.
Para obtener información adicional, contacte con Crowcon. Antes de realizar cualquier
trabajo de instalación, asegúrese de que se sigan las normas y procedimientos locales.
El equipo debe conectarse a tierra utilizando el pasacables y el cable blindado de acero.
No intente instalar un Display IR a un detector no suministrado para ese fin. Los detectores
suministrados para utilizarse con una pantalla están certificados según Exd ia, y deben
utilizarse o bien con una pantalla gráfica que contenga una barrera IS o con una pantalla
remota o manual conectada a través de un módulo de barrera IS de Crowcon.
Los detectores IRmax suministrados sin pantalla están certificados según Exd IIC y no se
les puede instalar una IR Display.
2.1 Ubicación
El detector IRmax debe montarse en el lugar donde sea más probable que esté presente el gas a
detectar. Al ubicar detectores de gas, deben observarse los puntos siguientes:
Para detectar gases más ligeros que el aire, como el metano, los detectores deben montarse
a un nivel alto. Para detectar gases más pesados que el aire, como vapores inflamables, los
detectores deben montarse a un nivel bajo.
Al ubicar detectores, debe considerarse el posible daño causado por eventos naturales, por
ejemplo, lluvias o inundaciones. Para detectores montados en el exterior en regiones muy
cálidas, Crowcon recomienda el uso de un toldo o parasol (véase la Sección 5, Accesorios y
piezas de repuesto, en la página 100).
Debe tenerse en cuenta facilitar el acceso para tareas de servicio y pruebas funcionales.
Debe tenerse en cuenta cómo puede comportarse el gas que se escape debido a corrientes
de aire naturales o forzadas. Monte los detectores IRmax en conductos de ventilación si es
apropiado (utilizando el kit de montaje en conducto del detector IRmax (véase la Sección 5,
Accesorios y piezas de repuesto, en la página 100).
Deben considerarse las condiciones del proceso. Por ejemplo, normalmente el butano es más
pesado que el aire pero si es emitido por un proceso a alta temperatura y/o presión, el gas
puede subir en lugar de bajar.
El posicionamiento de los sensores debe determinarse después de recibir la asesoría de expertos con
conocimientos especializados de la dispersión de gases, el equipo de procesamiento de la planta y
cuestiones de seguridad e ingeniería. Debe registrarse el acuerdo respecto a las ubicaciones de los
sensores.
2. Instalación
91
Detecting
Gas Saving Lives
Español
2.2 Montaje
El detector IRmax puede montarse de tres formas:
1. Utilizando el soporte de montaje de Crowcon con la conexión de cable directa
(funcionamiento de 4-20 mA solamente).
2. Utilizando un pasacables de espiga opcional para conexión a una caja de conexiones certificada
según Exe o Exd. Crowcon suministra un pasacables de espiga adecuado como extra opcional
(véase 3 a continuación)
3. Utilizando la caja de conexiones auxiliar y pasacables de espiga opcionales de Crowcon.
Se detallan piezas opcionales en la Sección 5, página 100.
El detector IRmax debe instalarse en el lugar asignado con el tubo sensor en posición horizontal +/-
15° (orientación mostrada en el Diagrama 2 de la página 88). Esto garantiza que no se acumule
polvo o agua en los componentes ópticos.
2.3 Cableado directo al detector IRmax
Esta opción es adecuada para funcionamiento de 4-20 mA solamente. Se requiere un soporte de
montaje de Crowcon para sujetar el detector a una pared o un tubo de 50 mm.
Diagrama 4: Conexiones de cable de campo en el IRmax
Conecte los cables utilizando un pasacables certificado a través de la entrada de cable escogida en
el cuerpo del detector IRmax (M20 o NPT de1/2"). Crowcon recomienda que los pasacables se
instalen apuntando hacia abajo.
Asegúrese de que se utilicen pasacables con la
certificación Exd apropiada y que la longitud de
la rosca no exceda la longitud especificada en el
diagrama (a la izquierda).
Señal
0V (tierra)
+V (IRmax de 24 V )
15mm MAX
LED de estado
2. Instalación
92
Detecting
Gas Saving Lives
Español
2.3.1 Designación de terminal
Con el IRmax orientado de la forma mostrada en el Diagrama 2 de la página 3 (entrada de
cable M20 en la parte superior), el cable de 3 conductores debe terminarse utilizando el conector
removible, de la forma siguiente:
+24V en la parte inferior, 0V en el centro, Signal en la parte superior.
El conector de 6 patillas a la derecha de la PCB se utiliza para el servicio y/o conexión de un
módulo IR Display
terminal +ve: suministro de +ve desde la tarjeta de control.
Terminal Sig: Señal/Detección desde tarjeta de control.
Terminal 0 V: Suministro de +ve desde la tarjeta de control.
2.3.2 Instalación del detector IRmax utilizando un soporte de montaje
a. El IRmax puede suministrarse con un soporte de montaje (S012130) en lugar de un
pasacables de espiga para que pueda conectarse directamente a los cables (véase el
Diagrama 5).
Diagrama 5: IRmax con un soporte de montaje y un pasacables
b. Si el IRmax va a montarse en una superficie plana, marque y perfore dos agujeros
utilizando el soporte de montaje como plantilla. Fije sin sujetarlas firmemente dos piezas
del soporte utilizando elementos de fijación adecuados para la pared/superficie.
c. Retire la tapa impermeable del IRmax, y deslice el cuerpo del detector a través del
soporte. Se recomienda que el cuerpo del IRmax se instale con la entrada de cable
encarada hacia abajo.
Soporte de montaje: 70 mm
entre centros de fijación.
Utilice tornillos M6.
2. Instalación
93
Detecting
Gas Saving Lives
Español
d. Apriete los elementos de fijación del soporte de forma que el IRmax quede sujeto
firmemente en posición. Vuelva a colocar la tapa impermeable.
e. Cuando el IRmax esté firmemente sujeto en posición, retire la tuerca trasera del IRmax
para permitir el acceso a los terminales del cable.
f. Prepare el cable – Crowcon recomienda el cable SWA (Steel Wire Armoured - blindado
de acero inoxidable) de 1,5 mm
2
. Pueden utilizarse otros tipos de cable siempre y cuando
sean compatibles con pasacables certificados por Exd. Instale un pasacables certificado
por Exd, pase los conductores de cable a través del cuerpo del IRmax y enrosque el
pasacables. Sujete el pasacables y asegúrese de que el blindaje del cable esté conectado
a tierra con el pasacables y el cuerpo del IRmax. Nota: No olvide volver a colocar la
tuerca trasera después de instalar el cable.
g. La placa de retención (pieza 9 en Diagrama 3, página 89) debe estar instalada de
forma segura para prevenir cualquier riesgo de que la tuerca trasera (o IR Display fija
o su accesorio de módulo de barrera IS) se afloje a causa de las vibraciones.
2.4 Instalación utilizando un pasacables de espiga y
una caja de conexiones auxiliar
Se requiere esta opción si el IRmax va a conectarse a una caja de conexiones auxiliar existente
certificada por Exd o Exe.
Diagrama 6: IRmax conectado a caja de conexiones auxiliar
2. Instalación
94
Detecting
Gas Saving Lives
Español
2.4.1 Para instalar el detector IRmax en una caja de conexiones auxiliar:
a. Retire cuidadosamente la sección externa del pasacables de espiga (pieza 8 en Diagrama
3, página 89).
b. Enrosque el extremo estrecho del pasacables de espiga en la caja de conexiones auxiliar.
c. Levante el IRmax hasta la caja de conexiones auxiliar de detector y pase los cables a
través del conjunto e introdúzcalos en la caja de conexiones auxiliar. Sujete el IRmax
enroscando al máximo el collarín en el pasacables. Apriete el espárrago.
d. El cuerpo principal del IRmax puede bascularse horizontalmente en cualquier ángulo,
siempre que sea mecánicamente seguro, no interfiera con otro equipo y sea accesible
para mantenimiento.
e. Consulte la sección 2.6 para ver instrucciones sobre el cableado. Véase también el
Diagrama 4 (página 91).
2.5 Requisitos de cableado
El cableado al IRmax debe realizarse de acuerdo con las normas reconocidas del organismo
apropiado del país en cuestión y deben satisfacer los requisitos eléctricos del IRmax.
Crowcon recomienda el uso de cable blindado de acero inoxidable (SWA) y deben utilizarse
pasacables a prueba de explosión adecuados. Pueden ser aceptables técnicas de cableado
alternativas, como un conducto de acero, siempre y cuando se satisfagan las normas apropiadas.
La longitud de cable máxima recomendada es 3,4 km (véase la Tabla 1).
El IRmax requiere un suministro de 12-30 VCC. Asegúrese de que el IRmax reciba un mínimo de
12 V del panel de control, teniendo en cuenta la caída de tensión causada por la resistencia del cable
a una corriente pico de 0,1A.
Un cable de 1,5 mm
2
permitirá típicamente tendidos de cable de hasta 3,0 km. La Tabla 1 siguiente
muestra las distancias de cable máximas considerando parámetros de cable típicos.
Área de sección
transversal
Resistencia Distancia máx.
>20 V
Distancia máx.
18 a 20 V
mm
2
(Ohmios por km) (km) (km)
1,0 18,4 2,2 1,6
1,5 13,0 3,0 2,3
2,5 11,5 3,4 2,6
Tabla 1: distancias de cable máximas para cables típicos
2. Instalación
95
Detecting
Gas Saving Lives
Español
2.6 Conexiones y ajustes
Todas las conexiones descritas se refieren al bloque terminal montado en el interior del cuerpo
principal del conector del IRmax. Los terminales de la PCB del conector del IRmax están marcados
‘+’, ‘sig’ y ‘0 V’. Cuando se conecta el IRmax a equipo de control debe observarse la polaridad
correcta.
El IRmax se ajusta en fábrica como dispositivo ‘sumidero de corriente’ a menos que se especifique
de otra manera al hacer el pedido. Para restaurarlo a ‘fuente de corriente’, retire la placa posterior
y mueva las dos conexiones de la PCB terminal de la posición de ‘sumidero‘ a la posición de
‘fuente’ tal como se muestra en el Diagrama 7.
Nota: El terminal de conexión a tierra externa sólo debe utilizarse cuando las autoridades
locales permitan o requieran dicha conexión. Si es posible, para limitar la interferencia de
frecuencias radiofónicas, la caja de conexiones y el blindaje del cable deben conectarse a
tierra al panel de control (área segura) solamente para evitar bucles de tierra.
Diagrama 7: Ubicación del puente de sumidero/fuente
La señal de 4-20mA puede ponerse a corriente de 'sumidero' o 'fuente' utilizando las patillas y
la conexión de puente mostraba en el Diagrama 7. Ajuste a ‘sumidero' de corriente instalando
la conexión de puente en las patillas 3 y 4, tal como se muestra en la fotografía de la izquierda.
Ajuste a ‘fuente' de corriente instalando la conexión de puente en las patillas 1 y 2, tal como
se muestra en la fotografía de la derecha. Los detectores IRmax se ajustarán a 'sumidero' de
corriente a menos que se especifique de otra manera al hacer el pedido.
Indicación LED: Hay instalado un LED en el PCB terminal para indicar el estado operativo
de la corriente. Consulte la Sección 6 para obtener más información.
CONTROLLER
EARTH
+V
0V
Sg
3
21
Cableado
Número Color Función
1 Rojo +V
2 Negro 0V
3 Verde Señal
Ajustes del
puente
Fuente
Conector de la IR Display
Conector de kit de
comunicaciones de PC
LED de estado
Controlador
Sumidero
Español
96
Detecting
Gas Saving Lives
3. Funcionamiento
ADVERTENCIA
Antes de realizar cualquier trabajo, asegúrese de que se sigan las normas locales y los
procedimientos del lugar en cuestión. No intente nunca abrir el detector IRmax o la caja
de conexiones auxiliares cuando haya gas inflamable presente. Asegúrese de que el
panel de control asociado esté inhibido a fin de prevenir alarmas falsas.
3.1 Procedimiento de puesta en servicio
1. Compruebe que:
a. Las conexiones de cable son correctas
b. La tensión de alimentación está ajustada en la tarjeta de control como 18 a 30 V. La
tensión medida en los terminales del detector IRmax (dentro de la caja de conexiones
auxiliaire Exe si se utiliza o en el PCB terminal del detector IRmax) y debe ajustarse a
entre 12 y 30 V.
c. Las conexiones se ajustan para sumidero o fuente de 4-20 mA según sea apropiado en
la tarjeta de control.
2. Una vez se ha activado, el dispositivo debe dejarse durante 30 minutos antes de intentar
una puesta a cero/calibración. Este retardo tiene el fin de garantizar la estabilidad térmica.
(Nota: El IRmax será totalmente operativo 30 segundos después de que se le aplique
corriente.)
3. Asegúrese de que el aire es limpio (es decir, no hay gases de hidrocarburos) antes de la puesta
a cero. Lectura cero en la tarjeta de control (consulte las instrucciones de la tarjeta de control).
4. Coloque la tapa de calibración sobre la cubierta impermeable para aislar la cámara de medición
del aire ambiental. Esta tapa puede obtenerse de Crowcon (M041007). Conecte el gas de
calibración (50% de LEL nom.) y aplíquelo a un flujo de 1 litro por minuto.
5. Después de 30 segundos ajuste cal/span en la tarjeta de control de forma que la lectura de la
pantalla sea 50% de LEL, o corresponda a la concentración del gas de calibración aplicado. El
IRmax en sí no debería requerir calibración.
6. Expulse el gas y retire la tapa de calibración. Vuelva a comprobar el cero.
7. A la instalación, o después de que se haya cambiado el espejo, el IRmax puede ponerse a cero
y calibrarse bien utilizando un accesorio de IR Display (véase página 85) o a través de un
kit de comunicaciones de PC (véase manual de accesorios de IRmax).
Nota: Los detectores IRmax certificados por ATEX serán suministrados calibrados para
el cumplimiento con EN61779 (donde, por ejemplo metano con 100% de LEL = 4,4%
volumen).
Nota: Se recomienda que se utilice la tapa de calibración para la puesta en servicio inicial.
Las calibraciones posteriores pueden realizarse aplicando gas a la tapa impermeable
remotamente a través de la espiga de tubo (lo cual evita la necesidad de acceder
directamente al IRmax). La calibración sin la tapa de calibración (es decir, directamente
a través de la tapa impermeable) puede realizarse siempre y cuando la velocidad del
viento local sea inferior a 2 metros/segundo. El caudal del gas debe ser superior a 2,0
litros/minuto.
3. Funcionamiento
97
Detecting
Gas Saving Lives
Español
3.2 Mantenimiento rutinario
La aplicación del lugar dictarán la frecuencia de verificación de los detectores. Crowcon
recomienda que el IRmax se verifique con gas como mínimo cada 6 meses y se recalibre si es
necesario. Para recalibrar un IRmax, siga los pasos indicados en 3.1.
En el caso de un fallo de la electrónica, consulte a su representante local de Crowcon.
Intervalo de calibración: Crowcon recomienda una calibración cada 12 meses.
Calibración remota a través de tubo: La velocidad del viento debe ser inferior a 2,0 metros por
segundo. Si es superior, utilice la tapa de calibración para impedir
la dilución del gas.
Limpieza de la óptica: No se recomienda a menos que el IRmax tenga un fallo
de oscurecimiento. Si la ventana o el espejo se contaminan,
límpielos cuidadosamente con agua (véase la Sección 5 del
manual de accesorios de IRmax, página 100).
Espejos: Si están dañados, contacte con Crowcon para obtener un
repuesto. (véase la Sección 5 del manual de accesorios de IRmax,
página 100). El IRmax siempre debe reponerse a cero y
recalibrarse después de un cambio de espejo.
Si la condensación empieza a causar fallos, cambie el espejo (el
revestimiento óptico puede estar dañado). Crowcon recomienda
cambiar el espejo cada 5 años.
3.3 Cambio de tipos de gas
Cada IRmax se suministra precalibrado para un tipo de gas particular (por ejemplo, metano o
propano). Si se requiere recalibración para un tipo de gas diferente, el IRmax puede reconfigurarse
utilizando el kit de comunicaciones de PC, (véase la Sección 5 del manual de accesorios de IRmax,
página 100), y después calibrarse.
3. Funcionamiento
98
Detecting
Gas Saving Lives
Español
3.4 Respuestas relativas de tipos de gas
En el gráfico siguiente se muestran las respuestas relativas a otros tipos de gas para un detector
IRmax calibrado con metano.
Nota: muchos gases y vapores de hidrocarburo son detectados más fácilmente por
detectores IR que el metano. La respuesta del IRmax (y otros detectores de gas IR) será
lineal a través de la gama 0-100% de LEL para el gas objetivo (es decir, metano en este
ejemplo), pero no lineal para otros hidrocarburos que también estén presentes
Diagrama 8
El diagrama muestra la respuesta de los gases indicados: de izquierda a derecha: propano, butano,
pentano y metano.
Hay disponibles otros tipos y gamas de gas. Para más detalles, contacte con Crowcon.
Español
99
Detecting
Gas Saving Lives
4. Especificaciones
Material de la caja Acero inoxidable 316
Dimensiones (detector solamente) 150 mm x 75 mm x 66 mm (sin espiga)
Peso IRmax, 1,58 kg
IRmax con IR Display fija, 2 kg
IRmax con módulo de barrera IS, 2,4 kg
IR Display remota , 0,2 kg
Tensión de funcionamiento 12 VCC a 30 VCC
Potencia < 1 W
Salida 3 hilos 4-20 mA (sumidero o fuente)
Señal de fallo <1 mA
Resistencia de bucle de cable máxima 80 ohmios (relativa a terminal -ve)
Temperatura de funcionamiento -40°C a +75°C (-40°F a +167°F)
Humedad 0–100% de humedad relativa
Grado de protección IP66
Protección contra explosión Antideflagrante
Código de aprobación
ATEX
IRmax (sin IR Display)
II 2 GD Exd db IIC T6 Gb (Tamb = -40°C a +50°C)
II 2 GD Exd db IIC T4 Gb (Tamb = -40°C a +75°C)
II 2 GD Ex tb IIIC T135°C Db (-40°C ≤ Ta≤ +75°C)
IRmax con su módulo de barrera IS (pantalla remota)
II 2 GD Exd db ia IIC T4 Gb (Tamb = -40°C a +75°C)
Ex tb ia IIIC T135°C Db (Tamb = -40°C a +40°C)
IRmax con IR Display ja
II 2 G Exd db ia IIC T4 Gb (Tamb = -40°C a +75°C)
No. de certificado de seguridad
ATEX y IECEx
IRmax (sin IR Display):
Baseefa 09ATEX0206X y IECEx BAS.09.0109X
IRmax (con IR Display):
Baseefa 09ATEX0220X y IECEx BAS.09.0104X
Seguridad funcional Certificado para uso en un sistema SIL 2.
Número de certificado: Sira 12ATEX1206X
Estándares EN 60079-0:2012+A11:2013, EN 60079-1:2014,
EN 60079-31:2014
IEC 60079-0:2011, IEC 60079-1:2014, IEC 60079-31:2013
EN 60079-29-1:2007, IEC 61508:2010, EN50402:2005
Zonas Certificado para uso en Zona 1 o Zona 2
EMC EN50270
Español
100
Detecting
Gas Saving Lives
5. Accesorios y repuestos
Números de pieza Nombre Descripción
M041007 Tapa de calibración Encaja sobre la tapa estanca estándar
para permitir la calibración cuando la
velocidad del aire local es superior a 2
metros/segundo.
S012130 Kit de soporte de
montaje
Permite realizar el montaje en una pared
o un tubo de 50 mm. No se requiere
si el IRmax se instala en una caja de
conexiones existente.
S012152 Parasol/Cono colector Puede instalarse en el IRmax para
protegerlo contra altas temperaturas
causadas por los rayos directos del sol
y/o ampliar la huella del detector para
detectar gases más ligeros que el aire
(metano).
S012169 Kit de montaje de
conducto
Permite la monitorización de conductos
de 300 mm a 3000 mm, y flujo de aire
entre 2 m/s y 20 m/s.
S012996 Adaptador de flujo Para aplicaciones de muestreo de gas
S012827 Kit de comunicaciones
de PC
Módulo de comunicaciones, software y
cable que permiten la configuración del
detector.
M20: S012295
½” NPT: S012296
Caja de conexiones
auxiliar
Opción de montaje de IRmax para uso en
entornos peligrosos.
C011210 Kit de limpieza de
espejo
Contiene paño de microfibras y toallitas
impregnadasde alcohol isopropílico
Repuestos del detector IRmax
Para ver los detalles de los repuestos, consulte el Diagrama 3 de la página 89.
Español
101
Detecting
Gas Saving Lives
6. Detección de errores
6.1 Errores indicados por LED
El LED instalado en el PCB terminal puede ayudar a identificar fallos. Su posición se muestra en
el Diagrama 7 de la página 95. La tabla siguiente muestra cómo interpretar lo que falla según
cada patrón de destellos.
Patrón de LED Estado del detector Acción
Destello regular cada
segundo.
Buen estado.
Encendido con pitidos
cortos.
Detector en modo
de inicialización.
Espere 10 segundos.
Destello rápido o patrón de
destellos irregular.
Tensión de
alimentación
demasiado baja o
demasiado alta.
Asegúrese de que la tensión de
alimentación del IRmax está ajustada
correctamente. Asegúrese de que la
medición se realizó directamente en los
terminales del IRmax.
Encendido
permanentemente.
Fallo, error del host
o i-module
Encienda y apague el IRmax y si el fallo
continúa, devuélvalo a Crowcon
Dos destellos largos seguidos
de un destello corto.
Error fatal; fallo de la
lámpara o detector.
Devuélvalo a Crowcon.
Doble destello rápido cada
segundo.
Error fatal, fallo
de módulo o
configuración.
Compruebe la configuración del
IRmax utilizando software kit de
comunicaciones de PC .
Compruebe la fuente de alimentación.
Si el fallo continúa, devuélvalo a Crowcon.
Un pitido corto cada
segundo.
Óptica oscurecida. Compruebe la ventana y el espejo,
límpielos si es necesario. Reponga a cero el
detector IRmax y compruebe la calibración.
Cualquier otro fallo sólo puede ser rectificado devolviendo el IRmax a Crowcon o a un agente de
servicio autorizado.
6.2 Salida analógica
El IRmax sigue en estado de fallo (Fault) y también aparece “Servicio requerido" (Service required)
en la IR Display (si está instalada) si la señal de salida analógica ha fallado o si no está conectado
a un sistema de control o un resistor de carga. El IRmax monitoriza activamente la señal de salida
analógica de 4-20 mA para verificar que está dentro del rango. Si la señal está fuera del rango el
detector se pone en estado de fallo y la salida se pone a 1 mA. Por consiguiente, cuando se prueba
un detector es esencial que esté conectado a un panel de control o que un resistor de carga de
100 Ω esté conectado entre los terminales ‘0V’ y ‘Sig’ (detector puesto a modo ‘Fuente’) o entre
los terminales ‘0V’ y ‘+V’ (detector puesto a modo ‘Sumidero’).
Español
102
Detecting
Gas Saving Lives
7. Configuración de RS485 Modbus
7.1 General
En esta sección se explica cómo utilizar detectores IRmax en una configuración Modbus. Hay
disponible una versión habilitada con RS485 para dichas aplicaciones. Es posible conectar hasta
28 detectores IRmax en configuraciones de estrella o bus, de la forma descrita a continuación.
Las conexiones a la versión RS485 del detector IRmax deben realizarse a través de un pasacables
de espiga a una caja de conexiones auxiliar (Véase Sección 5, página 92.), en lugar de cablearlas
directamente al interior del detector.
Debe observarse que la pantalla del IR Display no puede utilizarse con detectores IRmax
habilitados con RS485.
La versión del IRmax habilitada con RS-485 tiene cinco terminales de campo. Los terminales son:
1 Electricidad positiva 12 V a 30 V a más de 0 V
2 0 V Retorno y referencia RS-485
3 Señal de 4-20 mA Señal fuente o sumidero (opcional)
4 RS485 B Señal diferencial RS-485
5 RS485 A Señal diferencial RS-485
Las señales de los terminales RS-485 cumplen con la norma EIA/TIA-485, lo que significa que la
gama de modo común es -7V a +12V respecto al terminal 0V.
Debe observarse que no todos los fabricantes de RS-485 están de acuerdo respecto a la polaridad
de las señales A y B. Si el cableado no funciona de una forma, los usuarios deben intercambiar los
cables RS-485 A&B. Hacer una conexión incorrecta no implica ningún riesgo.
Los ajustes de comunicaciones son 9600 bps, dos bits de parada y no paridad.
Cuando se compila un interfaz para un sistema de control, es importante considerar el tiempo que el sistema
tarda en recoger información de cada detector, uno después de otro. La velocidad más rápida a la que
detectores múltiples pueden ser sondeados es 14 detectores por segundo, pero en la práctica las condiciones
pueden reducir esto a 7 por segundo. Los usuarios deben asegurarse de que el plan permita que las señales de
alarma se registren dentro de límites de tiempo aceptables.
También es importante asegurarse de que el sistema pueda suministrar energía suficiente para
mantener todos los detectores en funcionamiento. Para calcular la cantidad de energía requerida en
una conexión de bus lineal, véase la Sección 7.3, Requisitos de cableado, página 104.
Para obtener las instrucciones completas sobre Modbus, contacte con Crowcon (véanse las
direcciones en la contraportada).
7. RS485 Modbus configuration
103
Detecting
Gas Saving Lives
Español
7.2 Topología del cableado
Las dos topologías de cableado más comunes son la conexión en estrella y el bus lineal.
7.2.1 Conexión en estrella
En una topología de conexión en estrella, todos los detectores están cableados a un punto central,
que usualmente es el panel de control. No se requiere que los cables tengan más de 5 núcleos ya
que todas las conexiones de señales de 4-20mA se llevan directamente al panel de control.
Entonces las señales A y B de RS-485 pueden conectarse juntas en el punto de estrella.
Seguidamente el bus debe terminarse en el punto de salida con un solo resistor de 110 ohmios.
La longitud de cada brazo de la estrella no puede superar los 750 metros.
7.2.2 Conexión de bus lineal
En una topología de conexión de bus, todos los detectores IRmax se cablean en una disposición
lineal, usualmente con el panel de control en un extremo. Una situación clásica es una instalación
de túnel, con los detectores IRmax instalados a intervalos regulares (véase el Diagrama 9 a
continuación).).
Para cablear la instalación, deben instalarse dos resistores de terminación de 110 ohmios en cada
extremo físico del bus.
Como las señales de 4-20 mA no puede compartirse, se requiere un conductor adicional en cada
tramo de cableado. Si no se utiliza ninguna de las señales de 4-20 mA, sólo se requieren cuatro
conductores.
Diagrama 9
A PANEL DE
CONTROL
DIAGRAMA DE CONEXIÓN DE BUS LINEAL
7. RS485 Modbus configuration
104
Detecting
Gas Saving Lives
Español
7.3 Requisitos de cableado
7.3.1 Cálculo del nivel mínimo de potencia requerida
Cuantos más detectores IRmax estén conectados al bus lineal, mayor será la potencia requerida
para el funcionamiento del sistema. Para calcular la potencia requerida para una instalación
particular es necesario conocer la resistencia del cable entre cada par de detectores IRmax. Debe
permitirse una corriente de por lo menos 0,1 mA para cada ‘tramo’ entre los detectores IRmax.
La tensión aplicada puede calcularse calculando la caída de voltaje a través de cada ‘tramo’ – al
final deben quedar por lo menos 12 V para asegurarse de que el último detector IRmax funciona
correctamente.
Para obtener asesoría en casos específicos, contacte con Crowcon. De forma alternativa, siga los
pasos descritos a continuación y el cálculo de muestra presentado en la sección siguiente.
1. La tensión no debe descender por debajo de 12 V, por tanto empiece el cálculo ajustando la
tensión en el último IRmax de la línea a ese valor.
2. Cada IRmax puede tomar hasta 0,1 A. Calcule la pérdida de tensión de cable del primer ‘tramo’
entre detectores suponiendo que la ‘corriente agregada’ es 0,1A, y multiplique esto por la
resistencia de cable del ‘tramo’ entre los detectores IRmax último y penúltimo.
3. Añada esta caída de tensión a los 12 V iniciales para obtener la tensión aceptable más baja
en el penúltimo IRmax. Añada 0,1 A al valor de la ‘corriente agregada’ para llegar a 0,2 mA,
la corriente mínima que pasa a través del penúltimo ‘tramo’ del bus. Multiplique esto por la
resistencia de cable para el penúltimo ‘tramo’ para obtener la caída de tensión siguiente.
4. Repita este proceso para cada IRmax, acumulando las pérdidas de tensión que ocurrirán entre
todos los detectores IRmax.
5. No debe excederse la tensión de detector máxima de 30 V.
7.3.2 Cálculo de muestra
Como ejemplo, aquí se muestran los resultados del cálculo realizado para seis detectores IRmax
espaciados uniformemente en un cable con un área de sección transversal de 1 mm
2
. Cada tramo tiene
una resistencia de 4,6 ohmios.
Estación Tensión de
alimentación
Corriente de alimentación
1 12 0,1 A
2 12,46 0,2 A
3 13,38 0,3 A
4 14,76 0,4 A
5 16,6 0,5 A
6 18,9 0,6 A
Alimentación del panel 21,66 0,6 A
Español
105
Detecting
Gas Saving Lives
8. Manual de seguridad funcional
8.1 Prólogo
Las secciones siguientes proporcionan detalles sobre la certificación del IRmax de acuerdo con
los estándares de seguridad funcional IEC 61508 y EN 50402. Se da información sobre las
características consideradas respecto a seguridad, requisitos de mantenimiento y datos que
permiten que el IRmax se integre en el Safety Instrumented System (SIS) (Sistema instrumentado
de seguridad).
8.2 Función de seguridad del IRmax y del IRmax Modbus
Para medir la concentración de gas inflamable e indicar la medición por medio de una salida de 4-20 mA.
Los fallos relacionados con la función de seguridad serán detectados por el hardware y firmware
asociados. Serán revelados en la forma de una señal de salida de menos de 3,6 mA o de más de 21 mA.
8.3 Datos de seguridad funcional
Nombre de parámetro Símbolo Ecuación / fuente IRmax
Intervalo de ensayo de prueba T1 Según define Crowcon.
8.760 horas
(anuales)
Tiempo medio de reparación MTTR Según define Crowcon. 8 horas
Tipo A/B Tipo A Según define Crowcon. Tipo B
Fallos totales:
λ
De FMEDA 1.04E-05
Fallos diagnosticados no peligrosos: λ
SD
De FMEDA 1.95E-08
Fallos no diagnosticados no peligrosos: λ
SU
De FMEDA 8.59E-08
Fallos diagnosticados peligrosos: λ
DD
De FMEDA 9.74E-06
Fallos no diagnosticados peligrosos: λ
DU
De FMEDA 5.06E-07
Fallos sin efecto no peligrosos: λ
NE
De FMEDA 3.21E-09
Cobertura de diagnósticos: DC λ
DD
/ (λ
DU
+ λ
DD
) 95.06%
Fracción de fallo no peligroso: SFF (λ
SD
+ λ
SU
+ λ
DD
) / λ 95.11%
Tiempo inactivo equivalente de
canal
t
CE
DU
/ λ
D
)(T/2 + MTTR) +
(λ
DD
/ λ
D
) MTTR
2.24E+02
PFDAVG (utilizando la ecuación
61508-6)
PFD
AVG
DU
+ λ
DD
) t
CE
2.30E-03
PFDAVG (utilizando ecuación
simplificada)
PFD
AVG
λ
DU
(T / 2+MTTR) + (λ
DD
MTTR) 2.30E-03
PFDAVG (utilizando la ecuación IEC
61508-6)
PFD
AVG
1-ε
-(λdd+λdu) tce
2.30E-03
Capacidad de SIL (modo de baja
demanda)
SIL2
Capacidad de SIL (modo de alta
demanda)
SIL2
Para aplicaciones de baja demanda, respecto a fallos de hardware aleatorios y fracciones de
fallos no peligrosos, todas las variantes del sistema son adecuadas para utilizarse en aplicaciones
SIL 2.
Manual de seguridad funcional
106
Detecting
Gas Saving Lives
Español
8.4 Configuración de hardware
Se ha utilizado la Ruta 1H (tolerancia de fallo de hardware y fracción de fallo no peligroso) para
evaluar el nivel de integridad de seguridad del hardware.
8.5 Configuración de software
Sea realizado la evaluación del firmware del producto de acuerdo con los requisitos dados en IEC
61508:3 2010.
8.6 Fallos sistemáticos
La Ruta 1S (especificada en IEC 61508:2 2010, párrafo 7.4.2.2c) se utiliza para cumplir con los
requisitos de evitar fallos sistemáticos.
8.7 Intervalo de diagnósticos
La mayoría de funciones de diagnósticos se monitorizan continuamente.
Se comprueba el circuito vigilante del sistema durante el ensayo de prueba anual mediante un ciclo
de desconexión y conexión eléctricas: El IRmax debe verificarse mediante un ciclo de desconexión
y conexión eléctricas (desconectar y reconectar el suministro de 24 VCC) como parte del programa
de mantenimiento para el producto (consulte también la sección 3.2).
8.8 Restricciones
Los índices de fallos son constantes.
Un ensayo de prueba realizado por lo menos una vez al año identificará todos los fallos no
revelados.
Las reparaciones tienen un tiempo medio de 8 horas.
Se supone que el usuario utiliza esta función de diagnósticos proporcionada a través del accesorio
IR Display y/o interfaz de PC a fin de minimizar el tiempo inactivo potencial del producto.
La evaluación de la fiabilidad es un proceso estadístico para aplicar datos de fallos históricos
a diseños y configuraciones propuestos. Por consiguiente proporciona un objetivo/evaluación
creíble de la probable fiabilidad del equipo suponiendo condiciones de fabricación, diseño y
funcionamiento idénticas a aquellas en las que los datos se recopilaron. Es una valiosa técnica
de revisión de diseño para comparar diseños alternativos, establecer el orden de objetivos de
rendimiento de magnitudes y evaluar los efectos potenciales de cambios de diseño. Sin embargo
no puede garantizarse que los valores previstos reales pronostiquen el número preciso de fallos
sobre el terreno que pueden ocurrir realmente, ya que esto depende de muchos factores fuera del
control de un ejercicio predictivo.
A efectos de esta predicción, se supone que los índices de fallos (símbolo λ) son constantes con
el tiempo. Tanto los fallos prematuros como los asociados con el desgaste reducirían la fiabilidad
pero se supone que pueden ser eliminados mediante pruebas previas y cambios preventivos
respectivamente.
Manual de seguridad funcional
107
Detecting
Gas Saving Lives
Español
La probabilidad de fallo a solicitud significa la probabilidad de que el sistema esté en un estado
de fallo en un momento al azar. Esto es sinónimo de la indisponibilidad de estado estable, que
es dada por:
Indisponibilidad = (λ x MDT)/(1 + (λ x MDT))
que se aproxima a λ x MDT para valores pequeños de λ x MDT
donde λ es el índice de fallos y MDT es el tiempo inactivo medio (Mean Down Time).
Esto concuerda con la expresión de disponibilidad, dada como: MTBF/(MTBF+MDT)
Los índices de fallo utilizados, y por tanto las disponibilidades derivadas, son las asociadas de
forma creíble con un diseño de probada eficacia después de un periodo adecuado de aumento
de fiabilidad.
8.9 Medio ambiente
Restricciones medioambientales:
El producto se hará funcionar dentro de una gama de temperatura ambiente máxima de
40°C a +75 °C
El producto se almacenará dentro de una gama de temperatura ambiente máxima de
40°C a +80 °C.
El producto se hará funcionar dentro de una gama de humedad relativa ambiente máxima
de 0% a +100 % de condensación.
El producto tiene un nominal de “protección contra penetración" de IP66 de acuerdo con
las definiciones del estándar EN60529.
El producto está diseñado para funcionamiento continuo.
8.10 Tolerancia de fallo de hardware
La tolerancia de fallo de hardware es 0.
8.11 Capacidad sistemática
El IREX/IRmax es de Clase SC2.
8.12 Clasificación
El IREX/IRmax es un componente tipo B.
Español
108
Detecting
Gas Saving Lives
Garantía
Este equipo sale de nuestra fábrica completamente verificado y calibrado. Si durante el período
de garantía de tres años, calculado a partir de la fecha de envío, se demuestra que el equipo
es defectuoso debido a material o fabricación deficiente, nos comprometemos a repararlo o
cambiarlo, a nuestro criterio, gratuitamente, bajo las condiciones siguientes.
Procedimento de garantía
Para facilitar el procesamiento eficiente de cualquier reclamación, contacte con nuestro equipo
de asistencia al cliente, llamando al nº de teléfono +44 (0)1235 557711 y proporcionando la
información siguiente:
Su nombre y número de teléfono, número de fax y dirección de email de contacto.
La descripción y cantidad de productos que se devuelven, incluidos cualesquiera accesorios.
Número(s) de serie de instrumento(s).
El motivo de la devolución.
Obtenga un formulario de devolución para fines de identificación y localización. Este formulario
puede ser descargado de nuestro sitio web ‘crowconsupport.com’, junto con una etiqueta de
devoluciones. De forma alternativa podemos enviarle una copia por email.
No se aceptarán detectores IRmax bajo garantía sin un número de devolución de Crowcon
(Crowcon Returns Number (CRN)). Es esencial que la etiqueta de la dirección esté fijada de
forma segura en el embalaje externo de los productos devueltos.
La garantía quedará anulada si se descubre que el instrumento ha sido alterado, modificado, desmontado
o manipulado indebidamente. La garantía no cubre el uso indebido o el maltrato de la unidad.
Descargo de responsabilidad de garantía
Crowcon no acepta ninguna responsabilidad por pérdidas o daños consecuenciales o indirectos,
sea cual sea su causa (incluida cualquier pérdida o daño CAUSADO por el uso del instrumento) y
se excluye expresamente cualquier responsabilidad respecto a terceros.
La garantía respecto a elementos consumibles de repuesto (como el espejo) suministrados bajo
garantía para reemplazar elementos defectuosos, se limitará a la garantía vigente del elemento
suministrado original.
La garantía respecto a elementos consumibles de repuesto (como el espejo) suministrados bajo
garantía para reemplazar elementos defectuosos, se limitará a la garantía vigente del elemento
suministrado original.
Crowcon se reserva el derecho de determinar un periodo de garantía reducido, o declinar un
periodo de garantía para cualquier sensor suministrado para utilizarse en un entorno o para una
aplicación que se sabe que presenta un riesgo de degradar o dañar el sensor..
Nuestra responsabilidad respecto a equipo defectuoso se limitará a las obligaciones establecidas en
la garantía y se excluye cualquier garantía extendida, condición o declaración, explícita o implícita,
estatutaria o de otro tipo respecto a la calidad comercializable de nuestro equipo o su idoneidad
para algún fin particular excepto si esta exclusión está prohibida por la ley. Esa garantía no afectará
los derechos estatutarios de un cliente.
Warranty
109
Detecting
Gas Saving Lives
Español
Crowcon se reserva el derecho de aplicar un recargo de manipulación y transporte si se descubre
que unidades devueltas como defectuosas sólo requieren calibración o servicio normal, que el
cliente declina realizar.
Para consultas sobre garantía y asistencia técnica, contacte con:
Asistencia al cliente
Tel: +44 (0) 1235 557711
Fax: +44 (0) 1235 557722
Contenuto
Principi di funzionamento e informazioni di sicurezza ............................... 113
Principi di funzionamento del rilevatore IRmax ................................ 113
Informazioni per la sicurezza ............................................................. 114
Panoramica del prodotto ................................................................... 115
1. Introduzione ......................................................................................... 116
1.1 Considerazioni generali ............................................................... 116
1.2 Descrizione del prodotto ............................................................. 116
2. Installazione ......................................................................................... 118
AVVERTENZA .................................................................................... 118
2.1 Collocazione ............................................................................... 118
2.2 Montaggio .................................................................................. 119
2.3 Collegamento diretto del cablaggio al rilevatore IRmax ............. 119
2.3.1 Assegnazione dei terminali ................................................. 120
2.3.2 Installazione del rilevatore IRmax con la staffa di montaggio ...120
2.4 Installazione con attacco e scatola di derivazione ausiliaria .......... 121
2.4.1 Montaggio del rilevatore IRmax a una scatola di
derivazione ausiliaria ................................................................... 122
2.5 Requisiti per il cablaggio ............................................................. 122
2.6 Collegamenti e impostazioni ....................................................... 123
3. Funzionamento .................................................................................... 124
3.1 Commissioning procedure ........................................................... 124
3.2 Manutenzione ordinaria .............................................................. 125
3.3 Applicazioni con rilevazione di più gas ........................................ 125
3.4 Risposte relative ai tipi di gas ...................................................... 126
4. Dati tecnici ........................................................................................... 127
5. Accessori e ricambi ............................................................................... 128
6. Diagnostica ......................................................................................... 129
6.1 Errori segnalati dal LED ............................................................... 129
6.2 Uscita analogica .......................................................................... 129
7. Configurazione Modbus RS485 ............................................................ 130
7.1 Considerazioni generali ............................................................... 130
7.2 Topologia di collegamento .......................................................... 131
7.2.1 Collegamento a stella ......................................................... 131
7.2.2 Collegamento a bus lineare ................................................ 131
7.3 Requisiti di cablaggio .................................................................. 132
7.3.1 Calcolo del livello minimo di potenza richiesto ................... 132
7.3.2 Esempio di calcolo .............................................................. 132
8. Manuale della sicurezza funzionale....................................................... 133
8.1 Introduzione ............................................................................... 133
8.2 Funzione di sicurezza IRmax e IRmax Modbus ............................. 133
8.3 Dati di sicurezza funzionale ......................................................... 133
8.4 Configurazione dell’hardware ..................................................... 134
8.5 Configurazione del software ....................................................... 134
8.6 Guasti sistematici ........................................................................ 134
8.7 Intervallo diagnostico .................................................................. 134
8.8 Limiti ........................................................................................... 134
8.9 Ambientale ................................................................................. 135
8.10 Tolleranza ai guasti hardware .................................................... 135
8.11 Capacità sistematica .................................................................. 135
8.12 Classificazione ........................................................................... 135
Garanzia ................................................................................................... 136
Italiano
113
Detecting Gas Saving Lives
Principi di funzionamento e informazioni
di sicurezza
Principi di funzionamento del rilevatore IRmax
Il rilevatore di gas a infrarossi (IR) ultracompatto IRmax consente la rilevazione rapida e fail-safe
di vapori e gas idrocarburi.
Progettato per operare nelle condizioni più gravose, IRmax integra la tecnologia dei sensori IR a doppia
lunghezza d’onda in una robusta esecuzione in acciaio inox 316. A differenza dei tradizionali rilevatori di gas
a IR, IRmax non incorpora elementi scaldanti per prevenire la formazione di condensa su vetri e finestrine.
Grazie al rivestimento STAY CLIR, infatti, il rilevatore IRmax previene la formazione di condensa durante il
funzionamento.
Il rilevatore IRmax è compatibile con qualunque sistema di controllo 4-20mA e può anche essere
installato in una rete di Modbus RS485 indirizzabili. (vedere Sezione 7).
Il rilevatore IRmax assorbe solo 1 Watt di potenza, con un consumo tra il 75 e il 90% inferiore rispetto
ai tradizionali rilevatori di gas a IR.
Il rilevatore IRmax è caratterizzato da una camera di diffusione compatta che, insieme all’efficiente
copertura di protezione anti-intemperie, assicura un’eccellente velocità di risposta. La copertura
anti-intemperie è stata progettata con l’ausilio di un software di modellazione del flusso d’aria
per effettuare la gassatura e la calibrazione a distanza senza l’impiego di speciali cappucci di
calibrazione.
IR Display consente di monitorare le letture del rilevatore IRmax sia in sede che a distanza. IR
Display può essere montato direttamente sul rilevatore IRmax o fornito con una barriera Crowcon
a sicurezza intrinseca. In questo modo l’unità IR Display può essere collegata alla barriera mediante
cablaggio provvisorio o permanente. Le opzioni disponibili sono illustrate nello Schema 3, pagina
116.
Per ulteriori informazioni sugli altri accessori per il rilevatore IRmax v. la Schema 3 a pagina 117
e la Sezione 5 a pagina 128.
Principi di funzionamento e informazioni di sicurezza
Italiano
114
Detecting
Gas Saving Lives
Informazioni per la sicurezza
I rilevatori di gas IRmax devono essere installati, utilizzati e riparati attenendosi rigorosamente alle
istruzioni e ai messaggi di avviso contenuti nel presente manuale, alle informazioni riportate sulle
etichette ed entro i limiti stabiliti.
Il dado posteriore del rilevatore IRmax deve essere sempre ben serrato durante il funzionamento.
Non tentare di rimuovere il dado posteriore prima di avere isolato l’alimentazione del rilevatore
per evitare possibili accensioni in atmosfere esplosive. Prima di rimuovere il dado per eseguire
interventi di manutenzione, calibrazione o riparazione, controllare che l’atmosfera circostante
non contenga gas o vapori infiammabili. Dopo avere scollegato l’alimentazione, attendere sempre
qualche minuto prima di procedere.
Gli interventi di manutenzione e calibrazione devono essere affidati esclusivamente a personale qualificato.
Utilizzare solo ricambi originali Crowcon; l’utilizzo di componenti non originali può invalidare la
certificazione e la garanzia del rilevatore IRmax.
In ambienti riscaldati, i rilevatori IRmax devono essere protetti dalle vibrazioni eccessive e dalla luce
solare diretta per evitare un aumento della temperatura superiore ai limiti specificati e ridurre la
durata di esercizio dell’apparecchio.
I rilevatori IRmax non rilevano idrogeno, ammoniaca o anidride carbonica.
L’apparecchiatura deve essere collegata a terra mediante il pressacavo e il cavo in acciaio armato.
Omologazione per ambienti polverosi Zona 21/22: il modello IRmax base (senza display IR o modulo
barriera IS) può essere usato in ambienti contenenti polveri pericolose (Zone 21 o 22).
Il modello IRmax con modulo barriera IS può essere usato nelle Zone 21 o 22 a condizione che la
temperatura ambiente non superi 40°C e che si installi/utilizzi un display IR remoto o display IR
palmari solo all'esterno dell'area pericolosa.
Il modello IRmax con display IR fisso non può essere installato in ambienti classificati come Zona
21 o 22.
Principi di funzionamento e informazioni di sicurezza
Italiano
115
Detecting Gas Saving Lives
Panoramica del prodotto
Il rilevatore IRmax è un rilevatore di gas a infrarossi usato per la rilevazione dei comuni gas
idrocarburi entro una gamma compresa tra 0 e 100%LEL (Lower Explosive Limit: limite inferiore di
esplosività, ossia la concentrazione minima nell’aria a cui può verificarsi l’accensione).
L’apparecchio IRmax è un rilevatore antideflagrante certificato (Exd) idoneo all’uso nelle Zone 1 o
2 definite dalla direttiva ATEX relativa alle aree pericolose. Per individuare il tipo di certificazione
del proprio apparecchio fare riferimento ai dati della targhetta di certificazione riportata su un
lato dell’apparecchio.
Nota: se non è presente alcuna targhetta di certificazione, il rilevatore IRmax non è certificato
per l’impiego nelle aree pericolose.
Schema 1: targhette di certificazione del rilevatore IRmax
0811
.TNESERP EB YAM EREHPSOMTA EVISOLPXE NEHW NEPO TON OD :GNINRAW
04- = bmaT( bG 4T CII bd xE 57+ ot C )C
W5=xamW V23=xamV
04- = bmaT
( bG 6T CII bd xE 05+ ot C )C
X9010.90 SAB xECEI X6020XETA90afeesaB
X6021XETA21 ariS 2LIS
DS4 41XO ,modgniK deitnU ,nodgnibA
DG2 II
ROTCETED SAG RI
)C°57+ aT C°04-( bD C°531T CIII bt xE
°°
°
°
Targhetta omologazione modello IRmax base
Ex db ia IIC T4 Gb (-40°C Ta +75°C)
Vmax=32V Wmax=5W
WARNING: DO NOT OPEN WHEN EXPLOSIVE ATMOSPHERE MAY BE PRESENT.
IR G A S DET E C TOR W I TH R E M OTE D I SPL A Y
Baseefa09ATEX0220X IECEx BAS 09.0104X
Abingdon, United Kingdom, OX14 4SD
1180
II 2GD
Ex tb ia IIIC T135
°C Db (-40°C Ta +40°C)
Targhetta omologazione IRmax con barriera IS
+75°C)Ex db ia IIC T4 Gb (-40°C Ta
II 2G
1180
Abingdon, United Kingdom, OX14 4SD
Baseefa09ATEX0220X IECEx BAS 09.0104X
IR GA S DE TECT OR WI TH D ISPL AY
WARNING: DO NOT OPEN WHEN EXPLOSIVE ATMOSPHERE MAY BE PRESENT.
Vmax=32V Wmax=5W
Targhetta omologazione IRmax con display IR fisso
Italiano
116
Detecting
Gas Saving Lives
1. Introduzione
1.1 Considerazioni generali
Tutti i rilevatori IRmax sono identificati da una targhetta attaccata al corpo principale. Al momento
di contattare Crowcon per richiedere assistenza o ricambi, si prega di avere a portata di mano
nome, numero di parte e di matricola del prodotto.
1.2 Descrizione del prodotto
Il rilevatore IRmax è costituito da un corpo principale in acciaio inox 316, una copertura
antistatica per la protezione del sistema ottico, una camera di misurazione dei gas e un gruppo
elettronico. Inoltre, il rilevatore IRmax può essere dotato di un modulo IR Display. Le istruzioni
per il montaggio dell’unità IR Display sono riportate nel relativo manuale (M07061).
È inoltre disponibile un attacco opzionale per collegare il rilevatore IRmax direttamente alle scatole
di derivazione ausiliarie con ingressi per cavi M20 o ½” NPT.
Tutte le dimensioni sono espresse in millimetri
Schema 2: disegno dimensionale del rilevatore IRmax
Nota: il corpo del rilevatore IRmax è dotato di due ingressi per cavi: uno M20 e l’altro
1/2" NPT. L’ingresso per cavo non specificato al momento dell’ordinazione del rilevatore
IRmax viene sigillato in fabbrica con un tappo certificato. Il rilevatore IRmax deve essere
installato con entrambi gli ingressi sigillati: uno mediante pressacavo, l’altro mediante tappo
omologato.
157.5
74.5
136
60.5
Attacco opzionale
57
totale
158 totale
74,5
136 totale
Pressacavi M20 o
1/2" NPT
Terminale di
terra esterno
(EARTH)
1. Introduzione
Italiano
117
Detecting Gas Saving Lives
Schema 3: disegno esploso del rilevatore IRmax (con numeri di parte dove applicabile)
Cappuccio di calibrazione M041007
Copertura protettiva M04995
Fermaspecchio
Specchio
Adattatore di flusso S012996
O-ring per controdado, modulo barriera IS o modulo per display IR fisso: M040077
Staffa di montaggio come gruppo completo S012130
Attacco versione M20 o 1/2"NPT: M20 ATEX: S012147, 1/2" NPT ATEX: S012190
Piastra e bulloni di fissaggio per tappo posteriore, display IR fisso e modulo barriera IS.
10
IR Display versione fissa
11
Connettore da IR Display a IRmax E07987
12
Barriera a sicurezza intrinseca
13
Cavo collegamento IR Display
14
Presa montaggio IR Display remoto M03833
15
IR Display remoto
}
Fornito come kit di ricambio completo dello specchio
C011206
10
11
12
13
14
15
Italiano
118
Detecting
Gas Saving Lives
2. Installazione
AVVERTENZA
Questo rilevatore è progettato per l’impiego in Zone a rischio 1 e 2; il tipo di
certificazione dipende dagli accessori montati e dalla temperatura ambiente di esercizio.
Per informazioni dettagliate sulla certificazione fare riferimento alla tabella delle
specifiche a pagina 14. L’installazione deve essere conforme agli standard approvati
dall’autorità competente nei rispettivi Paesi.
Per ulteriori informazioni contattare Crowcon. Prima di eseguire qualunque installazione,
garantire la stretta osservanza di tutte le norme locali e delle procedure del sito.
L’apparecchiatura deve essere collegata a terra mediante il pressacavo e il cavo in acciaio
armato.
Non tentare di collegare un’unità IR Display a un rilevatore non progettato per lo scopo.
I rilevatori progettati per l’impiego con il display sono certificati Exd e devono essere
azionati con un display fisso contenente una barriera a sicurezza intrinseca o con un
display remoto o palmare collegato mediante il modulo Crowcon IS Barrier.
I rilevatori IRmax forniti senza display sono certificati Exd IIC e non sono adatti all’uso
con l’unità IR Display.
2.1 Collocazione
Il rilevatore IRmax deve essere montato dove è più probabile che sia presente il gas da rilevare.
Al momento di scegliere il punto di installazione, tenere presente quanto riportato di seguito.
Per rilevare gas più leggeri dell’aria, come il metano, i rilevatori devono essere montati in alto.
Per rilevare gas più pesanti dell’aria, quali i vapori infiammabili, i rilevatori devono essere montati
in basso.
Al momento di scegliere il punto di installazione dei rilevatori, si raccomanda di valutare i possibili
danni causati da eventi naturali quali pioggia o allagamenti. Nel caso dei rilevatori montati
all’esterno in regioni molto calde, Crowcon raccomanda l’uso di un schermo solare (vedere
Sezione 5, Accessori e ricambi, a pagina 128).
Tenere conto della facilità di accesso al rilevatore per le procedure di verifica e gli interventi di
manutenzione.
Valutare il possibile comportamento delle fughe di gas in presenza di correnti d’aria naturali
o indotte. Se del caso, montare i rilevatori nelle condotte di ventilazione (vedere Sezione 5,
Accessori e ricambi, a pagina 128).
Valutare le condizioni del processo. Per esempio, il butano è normalmente più pesante dell’aria,
tuttavia - se liberato da un processo eseguito a temperatura e/o pressione elevata - può salire
invece di scendere.
La posizione dei sensori deve essere determinata con la consulenza di periti nella dispersione dei gas,
nelle apparecchiature di processo del sito e negli aspetti relativi alla sicurezza e alla progettazione.
Conservare la documentazione relativa alla posizione dei sensori concordata con i periti.
2. Installazione
Italiano
119
Detecting Gas Saving Lives
2.2 Montaggio
Il rilevatore IRmax può essere montato in tre modi:
1. Usando la staffa di montaggio opzionale e creando un collegamento diretto con il cavo di
campo (solo per il funzionamento a 4-20mA)
2. Usando un attacco opzionale da collegare a una scatola di giunzione preesistente e omologata Exe
o Exd. Crowcon fornisce una guarnizione per l’attacco come extra opzionale (v. 3 sotto)
3. con la scatola di derivazione ausiliaria e l’attacco opzionali Crowcon.
I componenti opzionali sono riportati nella Sezione 5, pagina 128.
Il rilevatore IRmax deve essere installato nel punto designato con il cilindro del sensore orizzontale
+/- 15° (come mostrato nello schema 2 a pagina 3). Questa disposizione consente di evitare
l’accumulo di polvere o acqua nei componenti ottici.
2.3 Collegamento diretto del cablaggio al rilevatore IRmax
Questa opzione è disponibile solo per il funzionamento a 4-20mA. Per fissare il rilevatore a una
parete o a un tubo da 50 mm occorre utilizzare una staffa di montaggio..
Schema 4: Collegamenti del cavo di campo sul rilevatore IRmax
Collegare i cavi di campo montando un pressacavo certificato nell’ingresso prescelto sul corpo del
rilevatore IRmax (M20 o 1/2" NPT). Crowcon raccomanda di installare il pressacavo orientandolo
verso il basso.
Accertarsi di utilizzare un pressacavo con idonea
certificazione Exd e filettature con passo non superiore
alla lunghezza specificata nello schema (a sinistra).
Segnale
0V (terra)
+V (24V IRmax)
15mm MAX
LED di stato
2. Installazione
Italiano
120
Detecting
Gas Saving Lives
2.3.1 Assegnazione dei terminali
Con il rilevatore IRmax orientato come mostrato nello Schema 2, pagina 116 (ingresso del cavo
M20 nella parte superiore), collegare il cavo di campo utilizzando il connettore estraibile come
indicato di seguito:
+24V nella parte inferiore, 0V al centro, segnale nella parte superiore.
Il connettore a 6-pin a destra della scheda a circuiti stampati serve per la manutenzione e/o il
collegamento di un modulo IR Display.
Terminale +ve: alimentazione +ve dalla scheda di controllo.
Terminale Sig: segnale dalla scheda di controllo.
Terminale 0 V: alimentazione -ve dalla scheda di controllo.
2.3.2 Installazione del rilevatore IRmax con la staffa di montaggio
a. Il rilevatore IRmax può essere fornito con una staffa di montaggio (S012130) al posto
dell’attacco per consentire il collegamento diretto ai cavi di campo (vedere Schema 5).
Schema 5: rilevatore IRmax con staffa di montaggio e pressacavo
b. Se il rilevatore IRmax viene montato su una superficie in piano, utilizzare la staffa di
montaggio come maschera per segnare e trapanare due fori. Utilizzando fissaggi adatti
alla parete/superficie di montaggio, montare senza serrare le due parti della staffa.
c. Rimuovere la copertura protettiva dal rilevatore IRmax e fare scorrere il corpo del
rilevatore nella staffa. Si raccomanda di installare il corpo del rilevatore in modo che
l’ingresso del cavo sia rivolto verso il basso.
Staffa di montaggio: 70mm
tra i centri di fissaggio.
Usare bulloni M6.
2. Installazione
Italiano
121
Detecting Gas Saving Lives
d. Serrare i due fissaggi della staffa in modo che il rilevatore IRmax risulti saldamente
bloccato in posizione. Rimontare la copertura protettiva.
e. Dopo avere fissato il rilevatore IRmax, rimuovere il dado posteriore per accedere ai
terminali dei cavi.
f. Predisporre il cavo di campo. Crowcon raccomanda l’uso di un cavo con filo in acciaio
armato (SWA) da 1,5 mm
2
è possibile utilizzare altri tipi di cavi a condizione che siano
compatibili con i pressacavi certificati Exd. Montare un pressacavo idoneo certificato
Exd, fare passare i conduttori nel corpo del rilevatore IRmax e avvitare il pressacavo.
Fissare il pressacavo e controllare che l’armatura del cavo sia collegata a terra mediante
il pressacavo e il corpo del rilevatore IRmax. N.B.:non dimenticare di rimontare il dado
posteriore dopo aver installato il cavo.
g. La piastra di fissaggio (componente 9 nello Schema 3 a pagina 117) deve essere
saldamente fissata per prevenire eventuali rischi di allentamento del dado posteriore (o
dell’accessorio del display IR fisso o del modulo barriera IS) a causa delle vibrazioni.
2.4 Installazione con attacco e scatola di derivazione
ausiliaria
Questa opzione di montaggio è richiesta se il rilevatore IRmax deve essere collegato a una scatola
di derivazione ausiliaria preesistente certificata Exd o Exe.
Schema 6: rilevatore IRmax collegato alla scatola di derivazione ausiliaria
2. Installazione
Italiano
122
Detecting
Gas Saving Lives
2.4.1 Montaggio del rilevatore IRmax a una scatola di derivazione ausiliaria
a. Rimuovere con cura la sezione esterna dell’attacco (componente 8 nello Schema 3
a pagina 117).
b. Avvitare l’estremità stretta dell’attacco nella scatola di derivazione ausiliaria del rilevatore
IRmax.
c. Sollevare il rilevatore IRmax fino alla scatola di derivazione ausiliaria e fare passare i
fili attraverso il gruppo e la scatola di derivazione ausiliaria. Fissare il rilevatore IRmax
avvitando saldamente il colletto al pressacavo. Serrare il grano.
d. Il corpo principale del rilevatore IRmax può essere orientato orizzontalmente a qualunque
angolazione, a condizione che sia fissato meccanicamente, che non interferisca con altre
apparecchiature e che sia facilmente accessibile per la manutenzione.
e. Per istruzioni sul cablaggio consultare la sezione 2.6. Vedere anche lo Schema
4, pagina 119.
2.5 Requisiti per il cablaggio
I collegamenti elettrici al rilevatore IRmax devono essere conformi alle norme approvate
dall’autorità locale in materia e soddisfare i requisiti elettrici del rilevatore IRmax.
Crowcon raccomanda l’uso di un cavo armato con filo in acciaio (SWA) e di un pressacavo
antideflagrante. Tecniche di cablaggio alternative, quali tubi in acciaio, sono accettabili solo se
a norma.
La lunghezza massima raccomandata dei cavi è 3,4 km (v. Tabella 1).
Il rilevatore IRmax richiede un’alimentazione cc di 12-30V.c.c. Controllare che la tensione
erogata al rilevatore IRmax dal quadro di comando sia 12V minimo, tenendo conto della caduta
di tensione dovuta alla resistenza del cavo a una corrente di picco di 0,1A.
Normalmente, un cavo da 1,5 mm
2
consente di coprire una lunghezza massima di 3,0 km. La
tabella 1 sotto mostra le distanze massime dei cavi secondo i parametri standard.
C.S.A. Resistenza Distanza max.
>20 V
Distanza max.
da 18 a 20 V
mm
2
(Ohm per km) (km) (km)
1,0 18,4 2,2 1,6
1,5 13,0 3,0 2,3
2,5 11,5 3,4 2,6
Tabella 1: distanze max. per cavi tipici
2. Installazione
Italiano
123
Detecting Gas Saving Lives
2.6 Collegamenti e impostazioni
Tutti i collegamenti descritti si riferiscono alla morsettiera montata nel corpo principale del
connettore del rilevatore IRmax. I terminali della scheda a circuiti stampati del connettore IRmax
sono contrassegnati con ‘+’, ‘sig’ e ‘0 V’. Rispettare la polarità corretta al momento di collegare il
rilevatore IRmax all’apparecchiatura di controllo.
Il rilevatore IRmax è preimpostato come dispositivo con corrente a ‘pozzo di corrente’, salvo
diversamente specificato al momento dell’ordine. Per impostare l’apparecchio a ‘sorgente di
corrente’, smontare la piastra posteriore e spostare i due collegamenti della scheda a circuiti
stampati dalla posizione ‘sink’ alla posizione ‘source’, come mostrato nello Schema 7.
Nota: il terminale esterno di terra può essere usato solo se permesso o richiesto dalle autorità
locali competenti. Per limitare l'interferenza prodotta dalle radiofrequenze, si consiglia - per
quanto possibile - di eseguire la messa a terra della scatola di derivazione ausiliaria e
dell’armatura del cavo solo nel quadro di comando (aerea sicura) per evitare ritorni di terra.
Schema 7: punto di installazione ponticello sink/source
Il segnale 4-20mA può essere impostato come corrente 'Sink' o 'Source' utilizzando i pin e il
ponticello mostrati nello Schema 7. Impostare la corrente su ‘Sink’ collegando il ponticello ai pin
3 e 4 come mostrato nella fotografia a sinistra. Impostare la corrente su ‘Source’ collegando il
ponticello ai pin 1 e 2 come mostrato nella fotografia a destra. I rilevatori IRmax sono impostati
con corrente 'Sink' salvo diversamente specificato al momento dell’ordine.
Indicatore LED: la scheda a circuiti stampati è dotata di un LED per indicare lo stato operativo
della corrente. Per ulteriori informazioni consultare la Sezione 6 a pagina 129.
CONTROLLER
EARTH
+V
0V
Sg
3
21
Cablaggio
Numero Colore Funzione
1 Rosso +V
2 Nero 0V
3 Verde Segnale
Impostazioni
ponticello
Sink
Source
Connettore IR Display
Controllore
Connettore per kit
comunicazione PC
LED di stato
Italiano
124
Detecting
Gas Saving Lives
3. Funzionamento
AVVERTENZA
Prima di eseguire qualunque intervento, garantire l’ottemperanza alle norme locali e
alle procedure stabilite dal sito. Non tentare mai di aprire il rilevatore o la scatola di
derivazione ausiliaria in presenza di gas infiammabili. Accertarsi che il quadro di comando
associato sia inibito per evitare falsi allarmi.
3.1 Commissioning procedure
1. Controllare che:
a. i collegamenti dei cavi siano corretti
b. la tensione di alimentazione nella scheda di controllo sia impostata tra 18 e 30 V. La
tensione misurata in corrispondenza dei terminali del rilevatore IRmax (nella scatola
di giunzione Exe, se utilizzata, o in corrispondenza della scheda a circuiti stampati del
rilevatore IRmax) deve essere impostata tra 12 e 30 V.
c. i collegamenti siano impostati per una corrente 4-20 mA sink o source in base alla
scheda di controllo.
2. Dopo l’accensione, attendere almeno 30 minuti prima di procedere all’azzeramento/
calibrazione per consentire al dispositivo di raggiungere la stabilità termica. (Nota: Il
rilevatore IRmax è pronto al funzionamento 30 secondi dopo l’accensione.)
3. Controllare che l’aria sia pulita (nessun gas idrocarburo) prima di procedere all’azzeramento.
Effettuare la lettura dello zero sulla scheda di controllo (consultare le istruzioni della scheda di
controllo).
4. Montare il cappuccio di calibrazione sulla copertura protettiva per isolare la camera di
misurazione dall’aria ambiente. Questa copertura è disponibile rivolgendosi a Crowcon
(M041007). Collegare il gas di calibrazione (50% LEL nom) ed erogare alla portata di 1 litro/
minuto.
5. Dopo 30 secondi, regolare calibrazione/span sulla scheda di controllo in modo che il display
visualizzi 50% LEL o corrisponda alla concentrazione del gas di calibrazione erogato. Il
rilevatore IRmax non dovrebbe richiedere alcuna calibrazione.
6. Interrompere l’erogazione del gas e rimuovere il cappuccio di calibrazione. Verificare
nuovamente l’azzeramento.
7. Al momento dell’installazione, o dopo avere cambiato lo specchio, il rilevatore può essere
azzerato e calibrato utilizzando un accessorio dell’unità IR Display (vedere pagina 113) o
mediante un kit di comunicazione con il PC (vedere il manuale degli accessori IRmax).
Nota: i rilevatori IRmax certificati ATEX sono forniti calibrati in conformità alla norma
EN61779 (dove, per esempio 100% LEL Metano = 4,4% volume).
Nota: si raccomanda di utilizzare il cappuccio di calibrazione per la messa in servizio iniziale.
Le calibrature successive possono essere eseguite erogando gas alla copertura protettiva
a distanza mediante il tubo (evitando pertanto la necessità di accedere direttamente al
rilevatore). La calibrazione senza il cappuccio (i.e. direttamente mediante la copertura
protettiva) può essere eseguita a condizione che la velocità del vento sia inferiore a 2 metri/
secondo. La portata del gas deve essere superiore a 2,0 litri/minuto.
3. Funzionamento
Italiano
125
Detecting Gas Saving Lives
3.2 Manutenzione ordinaria
Le pratiche del sito indicano la frequenza di verifica dei rilevatori. Crowcon consiglia di testare i
rilevatori IRmax con gas almeno ogni 6 mesi e di eseguire una nuova calibrazione ove e quando
necessario. Per eseguire una nuova calibrazione, seguire la procedura riportata nella Sezione 3.1.
In caso di guasto ai componenti elettronici, rivolgersi al rappresentante Crowcon di zona.
Intervalli di calibrazione: Crowcon raccomanda di eseguire la calibrazione a
intervalli di 12 mesi.
Calibrazione a distanza mediante tubo: la velocità del vento deve essere inferiore a 2,0 metri/
secondo. Se superiore, usare il cappuccio di calibrazione
per evitare la diluizione del gas.
Pulizia dell sistema ottico: non raccomandata salvo in caso di guasti dovuti
a oscuramento del percorso ottico. In caso di
contaminazione della finestrina o dello specchio, pulire
bene con acqua. (vedere Sezione 5, Accessori e
ricambi, a pagina 128).
Mirrors: se danneggiato, rivolgersi a Crowcon per ordinare
il ricambio (vedere Sezione 5, Accessori e ricambi,
a pagina 128). Dopo la sostituzione dello specchio,
il rilevatore IRmax deve essere sempre azzerato e
ricalibrato.
se la condensa inizia a causare guasti, sostituire lo
specchio (è possibile che il rivestimento ottico sia
danneggiato). Crowcon raccomanda di sostituire lo
specchio ogni 5 anni.
3.3 Applicazioni con rilevazione di più gas
Tutti i rilevatori IRmax sono forniti precalibrati per un certo tipo di gas (ad esempio metano o
propano). Se è necessario eseguire la ricalibrazione per un gas di diverso tipo, il rilevatore IRmax
può essere riconfigurato usando il kit di comunicazione per PC (vedere Sezione 5, Accessori e
ricambi, a pagina 128), e successivamente calibrato.
3. Funzionamento
Italiano
126
Detecting
Gas Saving Lives
3.4 Risposte relative ai tipi di gas
Il grafico riportato di seguito mostra le risposte relative ad altri tipi di gas ottenute con un rilevatore
IRmax calibrato per il metano.
Nota: i rilevatori IR rilevano molti gas e vapori di idrocarburi più facilmente rispetto al
metano. La risposta di IRmax (e di altri rilevatori di gas IR) sarà lineare nel range da 0 a
100%LEL per il gas target (il metano nell’esempio specifico), ma non-lineare per altri
idrocarburi eventualmente presenti.
Schema 8
Il diagramma mostra la risposta dei gas menzionati sopra: da sinistra a destra propano, butano,
pentano e metano.
Per ulteriori informazioni su altri tipi di gas e gamme disponibili contattare Crowcon.
Italiano
127
Detecting Gas Saving Lives
4. Dati tecnici
Materiale corpo Acciaio inox 316
Dimensioni (Solo rilevatore) 150 mm x 75 mm x 66 mm (senza tubo)
Peso IRmax 1,58 kg
IRmax con unità IR Display fissa 2 kg
IRmax con barriera IS 2,4 kg
IR Display remoto 0,2 kg
Tensione operativa Da 12Vcc a 30V cc
Alimentazione < 1 W
Uscita 4-20 mA a 3 fili (Sink o Source)
Segnale di guasto <1 mA
Resistenza max. circuito cavo 80 Ohm (relativo al terminale –ve)
Temperatura operativa Da -40°C a +75°C
Umidità 0–100% umidità relativa
Grado di protezione IP66
Protezione antideflagrazione Antideflagrante
Codice di approvazione
ATEX
IRmax (senza IR Display)
II 2 GD Exd db IIC T6 Gb (Tamb = -40°C a +50°C)
II 2 GD Exd db IIC T4 Gb (Tamb = -40°C a +75°C)
II 2 GD Ex tb IIIC T135°C Db (-40°C ≤ Ta≤ +75°C)
IRmax con modulo barriera IS (display remoto)
II 2 GD Exd db ia IIC T4 Gb (Tamb = -40°C a +75°C)
Ex tb ia IIIC T135°C Db (Tamb = -40°C a +40°C)
IRmax con display IR sso
II 2 G Exd db ia IIC T4 Gb (Tamb = -40°C a +75°C)
Numero di certificato di sicurezza
ATEX e IECEx
IRmax (senza IR Display):
Baseefa 09ATEX0206X e IECEx BAS.09.0109X
IRmax (con IR Display):
Baseefa 09ATEX0220X e IECEx BAS.09.0104X
Sicurezza funzionale Omologato per l’uso in un sistema SIL 2.
Numero di omologazione: Sira 12ATEX1206X
Norme EN 60079-0:2012+A11:2013, EN 60079-1:2014,
EN 60079-31:2014
IEC 60079-0:2011, IEC 60079-1:2014, IEC 60079-31:2013
EN 60079-29-1:2007, IEC 61508:2010, EN50402:2005
Zone Certificato per l’uso in Zona 1 o Zona 2
EMC EN50270
Italiano
128
Detecting
Gas Saving Lives
5. Accessori e ricambi
Numeri di parte Nome Descrizione
M041007 Cappuccio di
calibrazione
Si monta sulla copertura anti-intemperie
standard per eseguire la calibrazione
quando la velocità del vento supera i 2
metri/secondo.
S012130 Kit staffa di montaggio Consente il montaggio su parete o tubo
da 50 mm. Non richiesto se il rilevatore
IRmax viene montato su una scatola di
giunzione preesistente.
S012152 Schermo solare/cono
collettore
Può essere montato sul rilevatore IRmax
per proteggerlo da temperature elevate
causate dall’esposizione alla luce solare
diretta e/o per estendere l’ingombro
del rilevatore e rilevare gas più leggeri
dell’aria (ad esempio, metano).
S012169 Kit montaggio condotta Consente il monitoraggio in condotte da
300 mm a 3000 mm e con flussi d’aria
compresi tra 2 m/s e 20 m/s.
S012996 Adattatore di flusso Per applicazioni di campionamento dei
gas.
S012827 Kit di comunicazione
PC
Modulo, software e cavo di
comunicazione per la configurazione del
rilevatore.
M20: S012295
½” NPT: S012296
Scatola di derivazione
ausiliaria
Opzione di montaggio del rilevatore
IRmax negli ambienti pericolosi.
C011210 Kit pulizia specchio Contiene salviette IPA impregnate e un
panno microfibra
Ricambi del rilevatore IRmax
Per informazioni sui ricambi fare riferimento allo Schema 3 a pagina 117.
Italiano
129
Detecting Gas Saving Lives
6. Diagnostica
6.1 Errori segnalati dal LED
IL LED montato sulla scheda a circuiti stampati del terminale può assistere l’operatore
nell’individuazione dei guasti. La posizione del LED è illustrata nello Schema 7, pagina 123. La
tabella sotto spiega come interpretare il guasto per ciascun tipo di lampeggio.
Comportamento LED Stato rilevatore Azione
Lampeggio regolare ogni
secondo.
Funzionamento
corretto.
Acceso, brevi segnali acustici
e spento.
Rilevatore in
modalità di avvio.
Attendere 10 secondi.
Lampeggio veloce e
irregolare.
Tensione di
alimentazione
troppo bassa o
troppo alta.
Controllare che la tensione di alimentazione
del rilevatore IRmax sia impostata
correttamente. Effettuare la misurazione
direttamente in corrispondenza dei
terminali del rilevatore IRmax.
Sempre acceso. Guasto, errore
host o I-module.
Spegnere e riaccendere il rilevatore IRmax;
se il guasto persiste, rispedire a Crowcon.
Due lampeggi lunghi seguiti
da un lampeggio corto.
Errore irreversibile;
lampada o
rilevatore guasto.
Rispedire a Crowcon.
Doppio lampeggio rapido
ogni secondo.
Errore irreversibile,
guasto modulo o
configurazione.
Verificare la configurazione del
rilevatore IRmax utilizzando kit di
comunicazione PC software.
Controllare l’alimentazione.
Se il guasto persiste, rispedire a Crowcon.
Breve segnale acustico ogni
secondo.
Sistema ottico
oscurato.
Verificare finestrina e specchio e pulirli
se necessario. Riazzerare il rilevatore
IRmax e verificare la calibrazione.
Altri guasti possono essere corretti solo rispedendo il rilevatore IRmax a Crowcon o a un
tecnico di assistenza autorizzato.
6.2 Uscita analogica
Se il segnale analogico di uscita è fallito o se non è connesso ad un sistema di controllo o ad
un resistore di carico, l’IRmax rimarrà in stato di Errore, e sul display IR (se presente) apparirà
anche la scritta “Necessaria Manutenzione” (Service required). L’IRmax tiene sotto controllo
attivo il segnale analogico di uscita 4-20mA per verificare che sia nel campo di valori giusto. Se
il segnale è fuori specifica, il rivelatore si porta in modalità di errore e il segnale di uscita viene
impostato su 1mA. Così, quando si esegue la verifica di un rivelatore, è essenziale che questo
sia collegato ad un pannello di controllo o che un resistore di carico da 100Ω sia collegato fra
i terminali ‘0 V’ e ‘Sig’ (rivelatore impostato su modalità ‘Source’) o fra i terminali ‘0 V’ e ‘+V’
(rilevatore impostato su modalità ‘Sink’).
Italiano
130
Detecting
Gas Saving Lives
7. Configurazione Modbus RS485
7.1 Considerazioni generali
La presente sezione illustra l’utilizzo dei rilevatori IRmax in una configurazione Modbus. Per queste
applicazioni è disponibile una versione con abilitazione RS485. È possibile collegare fino a 28
rilevatori IRmax in configurazioni a stella o a bus, come descritto di seguito.
I collegamenti al rilevatore IRmax versione RS485 devono essere effettuati mediante attacco a
una scatola di derivazione ausiliaria (vedere Sezione 5 a pagina 128), piuttosto che mediante
collegamento diretto del cablaggio al rilevatore.
Tenere presente che l’unità IR Display non può essere utilizzata con un rilevatore IRmax con
abilitazione RS485.
La versione del rilevatore IRmax con abilitazione RS485 è dotata di cinque terminali di campo.
Questi terminali sono:
1 Alimentazione positiva Da 12 V a 30 V sopra 0 V
2 0 V Ritorno e riferimento RS485
3 Segnale 4-20 mA Segnale Source o Sink (opzionale)
4 RS485 B Segnale differenziale RS485
5 RS485 A Segnale differenziale RS485
I segnali sui terminali RS485 sono conformi allo standard EIA/TIA-485, pertanto la gamma della
modalità comune è compresa tra -7V e +12V rispetto al terminale 0V.
Tenere presente che l’assegnazione della polarità dei segnali A e B non è unanime tra i produttori
RS485. Se il collegamento non funziona in un modo, invertire i fili RS485 A e B. Non sussiste alcun
rischio di effettuare un collegamento sbagliato.
Le impostazioni della comunicazione sono 9600 bps, due stop bit e no parity.
Al momento di creare l’interfaccia per un sistema di controllo, è importante considerare la quantità di tempo
necessaria al sistema per raccogliere le informazioni da ciascun rilevatore. La velocità massima di raccolta dei dati
da più rilevatori è 14 rilevatori al secondo, ma le condizioni pratiche possono ridurre questa velocità a 7 rilevatori
al secondo. Spetta agli utenti verificare che la disposizione scelta consenta la rilevazione dei segnali di allarme
entro limiti di tempo accettabili.
Inoltre, è importante controllare che il sistema sia in grado di erogare una potenza sufficiente a
tenere in funzione tutti i rilevatori. Per calcolare la potenza richiesta in un collegamento a bus
lineare vedere Sezione 7.3, Considerazioni generali, pagina 132.
Per istruzioni dettagliati relative al Modbus contattare Crowcon (all’indirizzo riportato a tergo).
7. Configurazione Modbus RS485
Italiano
131
Detecting Gas Saving Lives
7.2 Topologia di collegamento
Le due topologie di collegamento comunemente usate sono a stella e a bus lineare.
7.2.1 Collegamento a stella
Nella topologia a stella, tutti i rilevatori sono collegati a un nodo centrale, normalmente
rappresentato dal quadro di comando. Nessun cavo deve avere più di 5 anime in quanto tutti i
collegamenti dei segnali da 4-20mA fanno direttamente capo al quadro di comando.
I segnali RS485 A e B possono essere collegati insieme nel punto a stella. Il bus deve essere
terminato nel punto a stella con un’unica resistenza di terminazione da 110 ohm.
La lunghezza di ciascun raggio della stella non deve essere maggiore a 750 metri.
7.2.2 Collegamento a bus lineare
Nella topologia a bus tutti i rilevatori IRmax sono collegati secondo una disposizione lineare,
normalmente con il quadro di comando ad un’estremità. Una situazione classica è rappresentata
dall’installazione a tunnel, con i rilevatori IRmax installati a intervalli regolari (vedere Schema 9
sotto).
Per collegare l’installazione occorre montare due resistenze di terminazione da 110 ohm alle due
estremità fisiche del bus.
Poiché i segnali da 4-20mA non possono essere condivisi, occorre installare un conduttore
aggiuntivo per ciascun nodo intermedio. Se non viene utilizzato nessuno dei segnali da 4-20mA,
questa installazione richiede solo quattro conduttori.
Schema 9
AL QUADRO DI
COMANDO
SCHEMA COLLEGAMENTO BUS
LINEARE
7. Configurazione Modbus RS485
Italiano
132
Detecting
Gas Saving Lives
7.3 Requisiti di cablaggio
7.3.1 Calcolo del livello minimo di potenza richiesto
Quanti più rilevatori IRmax sono collegati al bus lineare, tanto maggiore la potenza richiesta per
alimentare il sistema. Per calcolare la potenza richiesta per una data configurazione, è necessario
conoscere la resistenza dei cavi tra ciascuna coppia di rilevatori IRmax. Occorre calcolare una
corrente di almeno 0,1mA per ciascun nodo intermedio tra rilevatori. La tensione da erogare può
essere calcolata stimando la caduta di tensione per ciascun nodo intermedio – alla fine devono
restare almeno 12V per garantire il corretto funzionamento dell’ultimo rilevatore IRmax.
Contattare Crowcon per richiedere consulenze relative a casi specifici oppure seguire la procedura
riportata sotto ed eseguire il semplice calcolo illustrato nella sezione successiva.
1. La tensione non deve scendere al di sotto di 12V, pertanto si raccomanda di iniziare il calcolo
impostando su questo valore la tensione dell’ultimo rilevatore IRmax della linea.
2. Ciascun rilevatore IRmax può assorbire fino a 0,1 A. Calcolare la perdita di tensione del cavo
del primo nodo intermedio tra rilevatori assumendo che la ‘corrente aggregata’ sia pari a 0,1A
e moltiplicando questo valore per la resistenza del cavo del nodo intermedio tra l’ultimo e il
penultimo rilevatore IRmax.
3. Aggiungere questa caduta di tensione ai 12V iniziali per ottenere la tensione minima accettabile
al penultimo rilevatore IRmax. Aggiungere 0,1A al valore della ‘corrente aggregata’ per arrivare
a 0,2mA, la corrente minima che alimenta il penultimo nodo intermedio del bus. Moltiplicando
questo valore per la resistenza del cavo per il penultimo nodo intermedio si ottiene la caduta di
tensione successiva.
4. Ripetere questa procedura per ciascun rilevatore IRmax, accumulando le cadute di tensione che
si verificheranno tra ciascun rilevatore IRmax.
5. Non superare la tensione massima di 30V dei rilevatori.
7.3.2 Esempio di calcolo
A titolo esemplificativo, la tabella seguente riporta i risultati del calcolo per sei rilevatori IRmax
equidistanti installati a una distanza di 250m su un cavo di sezione pari a 1 mm2. Ciascun nodo
intermedio ha una resistenza di 4,6 ohm.
Stazione Tensione di alimentazione Corrente di alimentazione
1 12 0,1 A
2 12,46 0,2 A
3 13,38 0,3 A
4 14,76 0,4 A
5 16,6 0,5 A
6 18,9 0,6 A
Alimentazione quadro 21,66 0,6 A
Italiano
133
Detecting Gas Saving Lives
8. Manuale della sicurezza funzionale
8.1 Introduzione
Le sezioni seguenti contengono informazioni relative all’omologazione del rilevatore IRmax in
base alle norme di sicurezza funzionale IEC 61508 e EN 50402. Queste informazioni riguardano le
caratteristiche riportate nel dossier di sicurezza e nei requisiti e dati di manutenzione per consentire
l'integrazione del rilevatore IRmax in un sistema strumentale di sicurezza (SIS).
8.2 Funzione di sicurezza IRmax e IRmax Modbus
Per la misurazione della concentrazione di gas infiammabili e l’indicazione della misurazione
mediante un’uscita 4-20mA.
I guasti relativi alla funzione di sicurezza vengono rilevati dall’hardware e dal relativo firmware. Tali
guasti saranno rilevati come un segnale di uscita inferiore a 3,6mA o superiore a 21mA.
8.3 Dati di sicurezza funzionale
Nome parametro Simbolo Equazione / sorgente IRmax
Intervallo test funzionale T1 Secondo istruzioni Crowcon.
8.760 ore
(annuale)
Tempo medio alla riparazione MTTR Secondo istruzioni Crowcon. 8 ore
Tipo A/B Tipo A Secondo istruzioni Crowcon. Tipo B
Guasti totali:
λ
Da FMEDA 1.04E-05
Guasti sicuri diagnosticati: λ
SD
Da FMEDA 1.95E-08
Guasti sicuri non diagnosticati: λ
SU
Da FMEDA 8.59E-08
Guasti pericolosi diagnosticati: λ
DD
Da FMEDA 9.74E-06
Guasti pericolosi non diagnosticati: λ
DU
Da FMEDA 5.06E-07
Guasti senza effetti per la sicurezza: λ
NE
Da FMEDA 3.21E-09
Copertura diagnostica: DC λ
DD
/ (λ
DU
+ λ
DD
) 95.06%
Frazione dei guasti sicuri: SFF (λ
SD
+ λ
SU
+ λ
DD
) / λ 95.11%
Indisponibilità equivalente per
canale
t
CE
DU
/ λ
D
)(T/2 + MTTR) +
(λ
DD
/ λ
D
) MTTR
2.24E+02
PFDAVG (usando l’equazione
61508-6)
PFD
AVG
DU
+ λ
DD
) t
CE
2.30E-03
PFDAVG (usando l’equazione
semplificata)
PFD
AVG
λ
DU
(T / 2+MTTR) + (λ
DD
MTTR) 2.30E-03
PFDAVG (usando l’equazione IEC
61508-6)
PFD
AVG
1-ε
-(λdd+λdu) tce
2.30E-03
Capacità SIL (modalità a domanda
bassa)
SIL2
Capacità SIL (modalità a domanda
alta)
SIL2
Per quanto concerne i guasti hardware casuali e la frazione di guasti sicuri nelle
applicazione a domanda bassa, tutte le varianti del sistema risultano adatte all’uso nelle
applicazioni SIL 2.
Manuale della sicurezza funzionale
Italiano
134
Detecting
Gas Saving Lives
8.4 Configurazione dell’hardware
Per la valutazione del livello di integrità della sicurezza dell’hardware è stata adottata la Route 1H
(tolleranza ai guasti hardware e frazione dei guasti sicuri).
8.5 Configurazione del software
La valutazione del firmware del prodotto è stata effettuata conformemente ai requisiti stabiliti
dalla norma IEC 61508:3 2010.
8.6 Guasti sistematici
Per la conformità ai requisiti di prevenzione dei guasti sistematici è stata adottata la Route 1S
(come stabilito dalla norma IEC 61508:2 2010 paragrafo 7.4.2.2c).
8.7 Intervallo diagnostico
La maggior parte delle funzioni diagnostiche vengono monitorate continuamente.
Le verifiche del sistema watchdog devono essere eseguite durante il test funzionale annuale
spegnendo e riaccendendo lo strumento: IRmax deve essere sottoposto a un ciclo di accensione e
spegnimento una volta l’anno (scollegando l’alimentazione 24Vcc e ricollegandola), come previsto
nel programma di manutenzione del prodotto (leggere anche la sezione 3.2).
8.8 Limiti
Le percentuali di guasto sono costanti.
Eventuali guasti non rilevati saranno registrati dal test funzionale da eseguirsi almeno una volta
l’anno.
Eventuali guasti non rilevati saranno registrati dal test funzionale da eseguirsi almeno una volta
l’anno.
Si presume che l’utente utilizzi la funzionalità diagnostica fornita mediante l’accessorio del display
IR e/o l'interfaccia PC per ridurre l’indisponibilità potenziale del prodotto.
La valutazione dell’affidabilità è una procedura statistica usata per applicare i dati storici dei
guasti alle configurazioni e ai design proposti. Pertanto, questa valutazione fornisce un target/
stima credibili della probabile affidabilità dell’apparecchiatura, presumendo che le condizioni
di fabbricazione, progettazione e funzionamento siano identiche a quelle usate per la raccolta
dei dati. Questa utile tecnica di verifica in fase di progettazione consente di confrontare design
alternativi, stabilendo target prestazionali per ordine di grandezza e valutando i possibili effetti
prodotti da modifiche apportate al progetto. Gli effettivi valori previsti, tuttavia, non possono
essere garantiti in quanto il numero preciso di guasti che si verificheranno su campo dipende da
molti fattori al di fuori del controllo di un mero esercizio predittivo.
Per le finalità di questa previsione, si presuppone che i tassi di guasto (simbolo λ) siano costanti nel
tempo. I guasti precoci e di usura ridurrebbero l’affidabilità, tuttavia si presuppone che vengano
eliminati rispettivamente mediante burn in e sostituzione preventiva.
Manuale della sicurezza funzionale
Italiano
135
Detecting Gas Saving Lives
La probabilità di guasto a richiesta corrisponde alla probabilità che il sistema entri in stato di guasto
in un momento qualunque. Questa espressione è sinonimo di indisponibilità in stato stazionario,
calcolata come:
Indisponibilità = (λ x MDT)/(1 + (λ x MDT))
che approssima λ x MDT per valori bassi di λ x MDT
dove λ è il tasso di guasto e MDT è la durata media di indisponibilità.
Questo valore è confermato dall’espressione per la disponibilità, calcolata come: MTBF/
(MTBF+MDT)
I tassi di guasto adottati, e pertanto le disponibilità derivate, sono valori verosimilmente associati a
un design comprovato dopo un periodo di affidabilità della crescita di durata idonea.
8.9 Ambientale
Limiti ambientali:
Il prodotto deve essere utilizzato entro un intervallo massimo di temperatura compreso
tra -40°C e +75 °C
Il prodotto deve essere utilizzato entro un intervallo massimo di temperatura compreso
tra -40°C e +80 °C
Il prodotto deve essere utilizzato entro un intervallo massimo di umidità relativa ambiente
compreso tra 0% e +100 % di condensa
Il prodotto ha una protezione di ingresso di classe IP66 conformemente alle definizioni
contenute nella norma EN60529.
Il prodotto è progettato per il funzionamento continuo.
8.10 Tolleranza ai guasti hardware
L’HFT è 0.
8.11 Capacità sistematica
IREX/IRmax appartiene alla Classe SC2.
8.12 Classificazione
IREX/IRmax è un componente di tipo B.
Italiano
136
Detecting
Gas Saving Lives
Garanzia
Prima della spedizione al cliente, questo apparecchio è stato sottoposto a test completi e a
calibrazione. Se, entro il periodo di garanzia o tre anni dalla consegna, l’apparecchio risultasse
difettoso per ragioni imputabili a difetti di lavorazione o materiali, ci impegniamo a nostra
discrezione a provvedere alla sua riparazione o sostituzione senza ulteriori addebiti al cliente, fatte
salve le condizioni riportate di seguito.
Procedura per i reclami in garanzia
Per consentire una gestione più efficiente dei reclami in garanzia, si prega di chiamare il team di
assistenza clienti Crowcon al numero +44 (0)1235 557711 indicando i dati seguenti:
nome, numero di telefono, numero di fax e indirizzo e-mail;
descrizione e quantità delle merci da rispedire, compresi eventuali accessori.
numero(i) di matricola;
Reason for return.
Munirsi di un modulo di restituzione per consentire l’identificazione e la tracciabilità dell’apparecchio.
Questo modulo può essere scaricato dal nostro sito web ‘crowconsupport.com’ insieme all’etichetta
per la restituzione. In alternativa, rivolgersi a Crowcon per richiedere l‘invio di una copia tramite
e-mail.
Non si accettano resi in garanzia non accompagnati dall’apposito codice CRN rilasciato
da Crowcon. È essenziale che l’etichetta con l’indirizzo sia correttamente attaccata
all’imballaggio esterno della merce resa.
La garanzia sarà invalidata qualora si rilevi che l’apparecchio è stato alterato, modificato, smontato o
manomesso. La garanzia non copre danni causati dall’utilizzo inadeguato o improprio dell’apparecchio.
Limitazione di garanzia
Crowcon declina qualunque responsabilità per perdite o danni consequenziali o indiretti (ivi
compresi perdite o danni conseguenti all'utilizzo dell’apparecchio) ed esclude espressamente
qualunque responsabilità verso terzi.
La presente garanzia non copre la precisione di calibrazione dell’apparecchio o la finitura cosmetica
del prodotto. L’apparecchio deve essere sottoposto a manutenzione conformemente alle istruzioni
contenute nel relativo manuale d'uso e manutenzione.
La garanzia delle parti di ricambio (p. es. specchio) fornite in sostituzione di elementi difettosi in
garanzia è limitata al termine di validità della garanzia dell’apparecchio originariamente fornito.
Crowcon si riserva il diritto di ridurre o declinare il periodo di garanzia dei sensori se destinati
all’impiego in ambienti o applicazioni che li espongono a rischi noti di usura o danneggiamento
dei sensori.
La responsabilità di Crowcon in caso di apparecchiature difettose è limitata agli obblighi previsti
dalla presente garanzia; entro i limiti consentiti dalla legge, Crowcon declina qualunque garanzia
estesa, condizione o dichiarazione – espressa o implicita, prevista per legge o di altro genere –
relativa alla qualità commerciabile dell’apparecchiatura o alla sua idoneità a scopi particolari. La
presente garanzia non limita i diritti del cliente previsti per legge.
Garanzia
Italiano
137
Detecting Gas Saving Lives
Crowcon si riserva il diritto di addebitare le spese di spedizione e consegna qualora
l’apparecchiatura resa come difettosa richieda solo un normale intervento di calibrazione o
manutenzione e il cliente non dia il proprio consenso a procedere.
Per qualunque richiesta relativa alla garanzia e all’assistenza tecnica contattare:
Customer Support
Tel: +44 (0) 1235 557711
Fax: +44 (0) 1235 557722
Inhoud
Concept en veiligheid ............................................................................... 141
IRmax detector concept ................................................................... 141
Veiligheidsinformatie ......................................................................... 142
Productoverzicht ............................................................................... 143
1. Inleiding ............................................................................................... 144
1.1 Algemeen ................................................................................... 144
1.2 Productbeschrijving ..................................................................... 144
2. Installatie .............................................................................................. 146
WAARSCHUWING ............................................................................ 146
2.1 Locatie ........................................................................................ 146
2.2 Montage ..................................................................................... 147
2.3 Bekabeling rechtstreeks naar de IRmax detector ....................... 147
2.3.1 Plaats van klemmen ........................................................... 148
2.3.2 De IRmax detector installeren met een montagebeugel ..... 148
2.4 Installatie met een ringpakking en extra junction box .................. 149
2.4.1 De IRmax detector op een extra junction box bevestigen: . 150
2.5 Kabelvereisten ............................................................................. 150
2.6 Aansluitingen en instellingen....................................................... 151
3. Bediening ............................................................................................. 152
3.1 Inbedrijfstelling............................................................................ 152
3.2 Routineonderhoud ...................................................................... 153
3.3 Gassoorten wijzigen .................................................................... 153
3.4 Relatieve respons van gassoorten ................................................ 154
4. Specificatie ........................................................................................... 155
5. Accessoires en reserveonderdelen ......................................................... 156
6. Problemen oplossen ........................................................................... 157
6.1 Fouten gesignaleerd door LED ..................................................... 157
6.2 Analoge uitgang ......................................................................... 157
7. Configuratie RS485 Modbus ................................................................ 158
7.1 Algemeen ................................................................................... 158
7.2 Bedradingstopologie ................................................................... 159
7.2.1 Steraansluiting ................................................................... 159
7.2.2 Lineaire busaansluiting ....................................................... 159
7.3 Bekabelingsvereisten ................................................................... 160
7.3.1 Berekenen van de minimum vereiste stroom .................... 160
7.3.2 Voorbeeldberekening ......................................................... 160
8. Functionele veiligheidshandleiding ........................................................ 161
8.1 Inleiding ...................................................................................... 161
8.2 Modbus veiligheidsfunctie van IRmax en IRmax ........................... 161
8.3 Informatie over functionele veiligheid .......................................... 161
8.4 Hardwareconfiguratie.................................................................. 162
8.5 Softwareconfiguratie ................................................................... 162
8.6 Systematische storingen .............................................................. 162
8.7 Diagnostisch interval ................................................................... 162
8.8 Beperkingen ................................................................................ 162
8.9 Omgevingsfactoren ..................................................................... 163
8.10 Hardwarestoringstolerantie ....................................................... 163
8.11 Systematische capaciteit ............................................................ 163
8.12 Classificatie ............................................................................... 163
Garantie ................................................................................................... 164
Nederlands
141
Detecting
Gas Saving Lives
Concept en veiligheid
IRmax detector concept
De IRmax detector is een ultracompacte infrarood (IR) gasdetector die snel en faalveilig
koolwaterstofgassen en -dampen detecteert.
Met een IR-sensor met dubbele golflengte in een robuuste 316 roestvrijstalen behuizing kan de IRmax detector in
de zwaarste omstandigheden werken. In tegenstelling tot conventionele IR gasdetectors heeft de IRmax detector
geen verwarmers om condensatie op ramen en spiegels te voorkomen. De STAY CLIR coating op de optische
componenten voorkomt condensatievorming als de detector in bedrijf is.
De IRmax detector is compatibel met een besturingssysteem van 4-20mA en kan ook geïnstalleerd
worden in een RS485 Modbus netwerk (zie hoofdstuk 7).
De IRmax detector verbruikt slechts 1 Watt vermogen, typisch 75-90% minder dan conventionele IR
gasdetectors.
De IRmax detector heeft een compacte diffusiekamer die, in combinatie met een effectieve
weersbestendige kap, een uitmuntende responssnelheid geeft. De weersbestendige kap is ontworpen
middels luchtstroomsoftware zodat kalibratie en gastoevoer op afstand van de detector mogelijk is
gemaakt, zonder dat er een speciale kalibratiekap nodig is.
De het IR Display kunt u de uitlezingen van de IRmax zowel plaatselijk als op afstand bekijken. De IR
Display kan direct op de IRmax worden gemonteerd. Als alternatief kan de IRmax compleet met een
intrinsiek veilige IS-barrièremodule worden geleverd. De IR Display kan dan op de IS-barrièremodule
worden aangesloten, via een tijdelijke of permanente kabelverbinding. De leverbare opties staan in
Afbeelding 3 op pagina 145 weergegeven.
Voor nadere informatie over andere accessoires voor de IRmax wordt u verwezen naar Afbeelding 3
op pagina 145 en hoofdstuk 5, pagina 156.
Concept en veiligheid
Nederlands
142
Detecting
Gas Saving Lives
Veiligheidsinformatie
De IRmax gasdetectors moeten in strikte overeenstemming met deze instructies, waarschuwingen
en labelinformatie geïnstalleerd, bediend en onderhouden worden en binnen de vermelde
beperkingen.
De achterste moer op de IRmax detector moet tijdens bedrijf goed gesloten blijven. Probeer
de achterste moer niet te verwijderen, totdat de stroom naar de detector afgesloten is. Anders
kan een brandbare atmosfeer ontvlammen. Voordat de moer verwijderd wordt voor onderhoud
of kalibratie, dient er gecontroleerd te worden of er geen brandbare gassen of dampen in de
omliggende atmosfeer aanwezig zijn. Wacht een paar minuten nadat de stroom uitgeschakeld is,
voordat de hij geopend wordt.
Onderhoud en kalibratie mogen uitsluitend gedaan worden door bevoegd onderhoudspersoneel.
Er mogen alleen echte Crowcon vervangingsonderdelen gebruikt worden; andere onderdelen
kunnen de certificering en garantie van de IRmax detector ongeldig maken.
De IRmax detector moet tegen extreme vibratie en direct zonlicht in warme omgevingen
beschermd worden omdat hierdoor de temperatuur van de IRmax detector boven de
gespecificeerde limiet kan stijgen en voortijdige storing kan veroorzaken.
De IRmax detector detecteert geen waterstof, ammoniak of kooldioxide.
De apparatuur moet geaard zijn met behulp van de kabelpakking en de gepantserde stalen kabel.
Certificatie voor Zone 21/22, omgevingen met stof: IRmax basistoestel (zonder IR Display of IS
Barrier module) kan worden gebruikt in omgevingen die explosiegevaarlijk stof bevatten (Zone
21 of 22).
IRmax met een IS Barrier module kan worden gebruikt in Zone 21 of 22, zolang de
omgevingstemperatuur lager is dan 40°C en er een extern IR-display of handheld IR-displays
buiten de explosiegevaarlijke zone zijn geïnstalleerd of worden gebruikt.
IRmax met een vast IR Display kan niet in een Zone 21 of 22 worden geïnstalleerd.
Concept en veiligheid
Nederlands
143
Detecting
Gas Saving Lives
Productoverzicht
De IRmax detector is een infrarood gasdetector ontworpen om gewone koolwaterstofgassen te
detecteren in het bereik van 0 tot 100%LEL (onderste explosiegrens: de minimum concentratie in de
lucht waarop ontvlamming kan ontstaan).
De IRmax detector is een gecertificeerde explosieveilige (Exd) detector, die gebruikt kan worden
in gevaarlijke gebieden ATEX zone 1 of Zone 2. Bekijk het certificeringslabel aan de zijkant van de
detector voor de soort certificering op het betreffende product.
N.B.: Als er geen certificeringslabel op de IRmax detector zit, is de detector niet gecertificeerd
voor gebruik in gevaarlijke gebieden.
Afbeelding 1: IRmax detector certificeringslabels
0811
.TNESERP EB YAM EREHPSOMTA EVISOLPXE NEHW NEPO TON OD :GNINRAW
04- = bmaT( bG 4T CII bd xE 57+ ot C )C
W5=xamW V23=xamV
04- = bmaT
( bG 6T CII bd xE 05+ ot C )C
X9010.90 SAB xECEI X6020XETA90afeesaB
X6021XETA21 ariS 2LIS
DS4 41XO ,modgniK deitnU ,nodgnibA
DG2 II
ROTCETED SAG RI
)C°57+ aT C°04-( bD C°531T CIII bt xE
°°
°
°
Certificatie-etiket voor het IRmax
basismodel
Ex db ia IIC T4 Gb (-40°C Ta +75°C)
Vmax=32V Wmax=5W
WARNING: DO NOT OPEN WHEN EXPLOSIVE ATMOSPHERE MAY BE PRESENT.
IR G A S DET E C TOR W I TH R E M OTE D I SPL A Y
Baseefa09ATEX0220X IECEx BAS 09.0104X
Abingdon, United Kingdom, OX14 4SD
1180
II 2GD
Ex tb ia IIIC T135
°C Db (-40°C Ta +40°C)
Certificatie-etiket voor IRmax met
IS Barrier
+75°C)Ex db ia IIC T4 Gb (-40°C Ta
II 2G
1180
Abingdon, United Kingdom, OX14 4SD
Baseefa09ATEX0220X IECEx BAS 09.0104X
IR GA S DE TECT OR WI TH D ISPL AY
WARNING: DO NOT OPEN WHEN EXPLOSIVE ATMOSPHERE MAY BE PRESENT.
Vmax=32V Wmax=5W
Certificatie-etiket voor IRmax met vast IR Display
Nederlands
144
Detecting
Gas Saving Lives
1. Inleiding
1.1 Algemeen
De configuratie van elke IRmax detector wordt aangegeven door een label op het huis. Als u contact
opneemt met Crowcon voor advies of reserveonderdelen, vermeldt dan het onderdeelnummer en
het serienummer.
1.2 Productbeschrijving
De IRmax detector bestaat uit een huis van 316 roestvrij staal, een antistatisch weersbestendige
kap over de optische delen en een gasmetingskamer en een elektronicagedeelte. Er kan ook een IR
Display bevestigd worden. Instructies voor het aanbrengen van de IR Display staan in de handleiding
bij de IR Display (M07061).
Er kan een optionele ringpakking geleverd worden, zodat de IRmax detector rechtstreeks op extra
aansluitdozen aangesloten kan worden met een kabelinvoer van M20 of ½” NPT.
Alle afmetingen zijn in millimeters
Afbeelding 2: IRmax detector dimensionaal aanzicht
N.B.: De behuizing van de IRmax detector wordt met twee kabelingangen geleverd; één
is M20, één is 1/2" NPT. De kabelingang die niet gespecificeerd is bij het bestellen van een
IRmax detector wordt met een gecertificeerde plug afgesloten. De IRmax moet worden
geïnstalleerd met twee afgedichte kabelingangen: één met een kabelpakking, de ander met
een gecertificeerde afdichtplug met een IP66-certificaat.
157.5
74.5
136
60.5
Optionele ringpakking
57
totaal
158 totaal
74,5
136 totaal
kabelpakking
M20 of 1/2" NPT
Externe
aardeklem
(AARDE)
1. Inleiding
Nederlands
145
Detecting
Gas Saving Lives
Afbeelding 3: IRmax detector uitvergroot aanzicht (onderdeelnummers aangegeven, waar van toepassing)
Kalibratiekap M041007
Weersbestendige kap M04995
Spiegelborgring
Spiegel
Stroomadapter S012996
O-ring voor achtermoer, IS Barrier module voor vaste IR Display module: M040077
Montagebeugel (complete set) S012130
Kabelpakking M20 of 1/2"NPT: M20 ATEX: S012147, 1/2" NPT ATEX: S012190
Borgplaat en borgbouten voor achterplug, vast IR Display en IS Barrier module.
10
IR Display vaste versie
11
Connector IR Display naar IRmax detector E07987
12
IS-barrièremodule
13
Verbindingssnoer IR Display
14
Montagefitting Extern IR Display M03833
15
Extern IR Display
}
Samen geleverd als ‘spiegelvervangingsset’
C011206
10
11
12
13
14
15
Nederlands
146
Detecting
Gas Saving Lives
2. Installatie
WAARSCHUWING
Deze detector is ontworpen voor gebruik in gevaarlijke gebieden van zone 1
en zone 2. De certificering is afhankelijk van de bevestigde accessoires en de
omgevingstemperatuur. Zie de specificatietabel op pagina 155 voor informatie over de
certificering. De installatie moet ook in overeenstemming zijn met de erkende normen
van de betreffende instantie in het betrokken land.
Neem voor meer informatie contact op met Crowcon. Voordat er met installeren
begonnen wordt, moet ervoor gezorgd worden dat de plaatselijke voorschriften en
fabrieksprocedures opgevolgd worden.
De apparatuur moet geaard zijn via de kabelpakking en de gepantserde stalen kabel.
Probeer geen IR Display te monteren aan een IRmax detector die niet voor dat doel
geschikt is. Detectors die met een display gebruikt worden, zijn gecertificeerd Exd ia, en
moeten hetzij met een vast display bediend worden met een IS-barrière, of met een extern
of handdisplay dat via een IS-barrièremodule van Crowcon is aangesloten.
Een IRmax detector die geleverd wordt zonder display, is gecertificeerd Exd IIC en deze
kan niet met een IR Display gebruikt worden.
2.1 Locatie
De IRmax detector dient daar gemonteerd te worden waar het het meest waarschijnlijk is dat het te
detecteren gas aanwezig is. De volgende punten dienen in gedachten te worden gehouden bij het
plaatsen van gasdetectors:
Om gassen te detecteren die lichter zijn dan lucht, zoals methaan, moeten detectors hoog
geplaatst worden. Om gassen te detecteren die zwaarder zijn dan lucht, zoals brandbare dampen,
moeten detectors laag geplaatst worden.
Denk bij het plaatsen van detectors aan mogelijke schade die door de natuur veroorzaakt
kan worden, zoals regen of overstroming. Voor detectors die buiten in zeer warme gebieden
gemonteerd worden, beveelt Crowcon het gebruik van een zonnekap aan (Zie hoofdstuk 5,
Accessoires en reserveonderdelen, op pagina 144).
Denk ook aan toegang voor functietesten en onderhoud.
Bedenk hoe het ontsnappende gas zich zal gedragen als gevolg van een natuurlijke of geforceerde
luchtstroom. Monteer detectors in ventilatieleidingen indien van toepassing, gebruik hiervoor de
IRmax detector leidingmontageset (Zie hoofdstuk 5, Accessoires en reserveonderdelen, op
pagina 144).
Denk aan de procesomstandigheden. Butaan is bijvoorbeeld normaliter zwaarder dan lucht, maar
als het vrijkomt bij een proces dat op een verhoogde temperatuur en/of druk is, kan het gas
stijgen in plaats van dalen.
De plaatsing van de sensoren dient bepaald te worden na advies van experts die specialistische kennis
hebben van gasverspreiding en de verwerkingsapparatuur maar ook veiligheids- en technische kwesties.
Nederlands
147
Detecting
Gas Saving Lives
2.2 Montage
De IRmax detector kan op drie manieren gemonteerd worden:
1. Met de Crowcon montagebeugel met een directe veldkabelaansluiting (uitsluitend 4-20mA
bedrijf).
2. Met een ringpakking voor aansluiting op een bestaan junction box met Exe- of Exc-certificering.
Crowcon levert een geschikte pakkingring als optionele extra accessoire (zie 3 hieronder)
3. Met de optionele extra junction box en ringpakking van Crowcon.
Optionele onderdelen staan in hoofdstuk 5 op pagina 156.
De IRmax detector dient op de gewenste locatie geïnstalleerd te worden met de sensorkop +/- 15°
horizontaal (oriëntatie staat op Afbeelding 2 op pagina 144). Zo kan er geen vuil of water op de
optische componenten ophopen.
2.3 Bekabeling rechtstreeks naar de IRmax detector
Deze optie is alleen geschikt bij een werking van 4-20mA. Er is een Crowcon montagebeugel nodig
om de detector op een muur of pijp van 50 mm te bevestigen..
Afbeelding 4: Veldkabelverbindingen op de IRmax
Sluit veldkabels op de behuizing van de IRmax detector aan met een gecertificeerde wartel via de
gekozen kabelingang (M20 of 1/2" NPT). Crowcon beveelt aan dat de kabelwartel naar beneden
wijzend geïnstalleerd worden.
Zorg ervoor dat er kabelpakkingen met de juiste Exd
certificering gebruikt worden en dat de draadlengte
niet langer is dan de in de afbeelding gespecificeerde
lengte (links).
Signal
0V (ground)
+V (24V IRmax)
15mm MAX
Status-LED
Nederlands
148
Detecting
Gas Saving Lives
2.3.1 Plaats van klemmen
Met de IRmax in de richting van Afbeelding 2 op pagina 144 weergegeven (M20 kabelingang
bovenaan) dient de 3-aderige veldkabel als volgt afgesloten worden met de verwijderbare connector:
+24V onderaan, 0V in het midden, signaal bovenaan.
De 6-pins connector rechts van de printplaat is voor onderhoud en/of aansluiting van een IR Display
module.
+ klem : + toevoer van de besturingskaart.
Sig klem: Signaal van de besturingskaart.
0 V klem: - toevoer van de besturingskaart.
2.3.2 De IRmax detector installeren met een montagebeugel
a. De IRmax kan in plaats van met een ringpakking met een montagebeugel (S012130)
geleverd worden, zodat hij rechtstreeks op veldkabels gemonteerd kan worden (zie
Afbeelding 5).
Afbeelding 5: De IRmax detector met een montagebeugel en kabelpakking
b. Als de IRmax detector op een plat oppervlak gemonteerd wordt, markeer en boor dan twee
gaten waarbij de montagebeugel als sjabloon gebruikt wordt. Bevestig twee delen van de
beugel losjes vast met voor de muur/oppervlakte geschikte bevestigingsmiddelen.
c. Verwijder de weersbestendige kap van de IRmax detector en schuif de behuizing van de
detector door de beugel. Het wordt aanbevolen dat de behuizing van de IRmax detector
geïnstalleerd wordt met de kabelingang naar beneden wijzend.
Bevestigingsbeugel: 70 mm
bussen het midden van
de bevestigingen. Gebruik
M6-bouten.
2. Installatie
Nederlands
149
Detecting
Gas Saving Lives
d. Zet de twee beugelbevestigingen vast zodat de IRmax detector stevig op zijn plaats
gehouden wordt. Plaats de weersbestendige kap weer terug.
e. Als de IRmax detector stevig op zijn plaats zit, kan de achtermoer van de IRmax detector
verwijderd worden zodat u bij de kabelklemmen kunt.
f. Maak de veldkabel klaar – Crowcon beveelt een gepantserde stalen kabel van 1,5 mm
2
aan. Er kunnen andere kabelsoorten gebruikt worden, mits deze compatibel zijn met Exd
gecertificeerde pakkingen. Bevestig een geschikte, gecertificeerde Exd kabelpakking, leid de
kabelgeleiders door de behuizing van de IRmax detector en schroef de kabelpakking erin.
Draai de pakking vast en zorg ervoor dat de kabelpantsering geaard is op de kabelpakking
en de behuizing van de IRmax detector. N.B.: Vergeet niet de achtermoer weer terug te
plaatsen nadat de kabel geïnstalleerd is.
g. De borgplaat (item 9 op Afbeelding 3, pagina 145) moet goed vast zitten om te voorkomen
dat de achtermoer (of het vaste IR Display of de IS Barrier module) lostrilt.
2.4 Installatie met een ringpakking en extra junction box
Deze optie wordt gebruikt als de IRmax detector aangesloten moet worden op een bestaande Exd of
Exe gecertificeerde extra junction box.
Afbeelding 6: IRmax detector aangesloten op extra junction box
2. Installatie
Nederlands
150
Detecting
Gas Saving Lives
2.4.1 De IRmax detector op een extra junction box bevestigen:
a. Verwijder voorzichtig het buitenste gedeelte van de ringpakking (onderdeel 8 in Afbeelding
3 op pagina 145).
b. Schroef het smalle einde van de ringpakking in de extra junction box.
c. Breng de IRmax detector bij de extra junction box en leid de draden door de behuizing naar
de extra junction box. Zet de IRmax detector vast door de kraag stevig op de kabelpakking
te schroeven. Draai de stifttap vast.
d. De behuizing van de IRmax detector kan horizontaal tot elke hoek gedraaid worden, mits
hij mechanisch goed vast zit. Hij belemmert andere apparatuur niet en hij kan vanuit deze
positie ook onderhouden worden.
e. Zie hoofdstuk 2.6 instructies over bedrading. Zie ook Afbeelding 4 (pagina 147).
2.5 Kabelvereisten
De bekabeling naar de IRmax detector moet in overeenstemming met de erkende normen van de
betreffende instantie in het betrokken land zijn en voldoen aan de elektrische vereisten van de IRmax
detector.
Crowcon beveelt het gebruik van een gepantserde, stalen kabel aan en er moeten geschikte,
explosieveilige pakkingen gebruikt worden. Alternatieve bekabeling zoals stalen leidingen zijn
acceptabel, mits voldaan wordt aan de betreffende normen.
De maximum aanbevolen kabellengte is 3,4 km (zie tabel 1).
De IRmax detector behoeft een gelijkstroomvoeding van 12-30Vdc. Zorg ervoor dat er minimaal
12V bij de IRmax detector is vanaf het besturingspaneel waarbij rekening gehouden wordt met een
spanningsdaling vanwege kabelweerstand bij een piekstroom van 0,1mA.
Een kabel van 1,5mm
2
kan over het algemeen een kabellengte van maximaal 3,0 km aan. In tabel 1
staan de maximum kabelafstanden met typische kabelparameters.
Doorsnede Weerstand Max. Afstand
>20 V
Max. Afstand
18 tot 20 V
mm
2
(Ohm per km) (km) (km)
1,0 18,4 2,2 1,6
1,5 13,0 3,0 2,3
2,5 11,5 3,4 2,6
Tabel 1: maximum kabelafstanden voor standard kabels
2. Installatie
Nederlands
151
Detecting
Gas Saving Lives
2.6 Aansluitingen en instellingen
Alle beschreven aansluitingen hebben betrekking op het klemmenblok dat in de IRmax detector
connector gemonteerd is. De klemmen op de printplaat van de IRmax detector connector zijn
gemarkeerd met ‘+’, ‘sig’ en ‘0 V’. Houd rekening met de juiste polariteit bij het aansluiten van de
IRmax detector op besturingsapparatuur.
De IRmax detector is in de fabriek ingesteld als een 'verzamelstroom' (sink) apparaat, tenzij bij het
bestellen anders is gespecificeerd. Om hem in te stellen op 'stroombron' (source), moet de achterplaat
verwijderd worden en de twee verbindingen op de printplaat van de 'sink' (verzamel) positie naar de
'bron' (source) positie verplaatst worden, zoals weergegeven in Afbeelding 7.
N.B: De externe aardeklem mag alleen gebruikt worden als de plaatselijke autoriteiten een
dergelijke aansluiting toestaan of dit vereisen. Om waar mogelijk interferentie met
radiofrequenties te vermijden moeten de extra junction box en kabelpantsering alleen bij het
besturingspaneel (veilig gebied) geaard worden om aardlussen te vermijden.
Afbeelding 7: Jumperplaats sink/source
Het 4-20mA signaal kan ingesteld worden op 'sink' of 'source' met de pinnen en jumperverbinding
zoals weergegeven in afbeelding 7. Instellen op 'sink' stroom door de jumper aan te sluiten op
pennen 3 en 4, zoals aangegeven op de linkerfoto. Instellen op 'source' stroom door de jumper aan
te sluiten op pennen 1 en 2, zoals aangegeven op de rechterfoto. De IRmax detectors staan op
'verzamelstroom' (sink) tenzij dit bij het bestellen anders is gespecificeerd.
LED-indicatie: op de printplaat is een LED gemonteerd om de huidige bedrijfsstatus aan te
geven. Raadpleeg hoofdstuk 6 op pagina 157 voor nadere informatie.
CONTROLLER
EARTH
+V
0V
Sg
3
21
Bedrading
Nummer Kleur Functie
1 Rood +V
2 Zwart 0V
3 Groen Signaal
Jumperinstellingen
Source
Sink
Connector IR Display
Connector
pc-communicatieset
Status-LED
Besturingssysteem
Nederlands
152
Detecting
Gas Saving Lives
3. Bediening
WAARSCHUWING
Voordat er werk uitgevoerd wordt, moet ervoor gezorgd worden dat de plaatselijke
voorschriften en fabrieksprocedures opgevolgd worden. Probeer de IRmax detector of
extra junction box nooit te openen als er brandbaar gas aanwezig is. Zorg ervoor dat het
bijbehorende besturingspaneel geblokkeerd is om een vals alarm te voorkomen.
3.1 Inbedrijfstelling
1. Controleer of:
a. De kabelaansluitingen juist zijn
b. De toevoerspanning op de besturingskaart ingesteld is op 18 tot 30 V. De spanning die bij de
klemmen van de IRmax detector gemeten wordt (binnen de Exe extra junction box, indien
gebruikt, of bij de IRmax detector klemplaat) moet ingesteld zijn tussen 12 en 30V.
c. De verbindingen op de besturingskaart ingesteld zijn op 4-20mA sink of source, wat van
toepassing is.
2. Als hij aangezet is, laat hem dan 30 minuten rusten voordat er geprobeerd wordt op nul in te
stellen/te kalibreren. Deze vertraging is nodig om thermische stabiliteit te waarborgen. (N.B: Vanaf
30 seconden nadat de stroom is aangezet, is de IRmax detector volledig operationeel.)
3. Zorg voor schone lucht (d.w.z. geen koolwaterstofgas) voordat u op nul gaat instellen. Nullezing
via besturingspaneel (zie instructies van besturingskaart).
4. Bevestig de kalibratiekap over de weersbestendige kap om de meetkamer af te sluiten van
omgevingslucht. Zo'n kap is verkrijgbaar bij Crowcon (M041007). Sluit kalibratiegas aan (50% LEL
nom) met een stroom van 1 liter per minuut.
5. Pas na 30 seconden de kal/corr op besturingskaart aan zodat het display 50% LEL weergeeft, of
overeenkomst met de concentratie van het toegepaste kalibratiegas. De IRmax detector zelf hoeft
niet gekalibreerd te worden.
6. Verwijder de gas- en kalibratiekap. Controleer de nul opnieuw.
7. Bij de installatie of als de spiegel vervangen is, kan de detector op nul ingesteld en gekalibreerd
worden via een IR Display (zie pagina 141) of via een PC communicatieset (zie IRmax
accessoirehandleiding).
N.B: ATEX gecertificeerde IRmax detectors worden gekalibreerd geleverd zodat ze voldoen
aan EN61779 (waar bijvoorbeeld 100% LEL methaan = 4,4% volume).
N.B: Het wordt aanbevolen dat bij de eerste inbedrijfstelling de kalibratiekap gebruikt wordt.
Daaropvolgende kalibraties kunnen gedaan worden door gas extern op de weersbestendige
kap via de pijpring toe te passen (zodat er geen noodzaak is om direct toegang te hebben tot
de IRmax detector). Er kan gekalibreerd worden zonder de kalibratiekap (d.w.z. rechtstreeks
via de weersbestendige kap), mits de plaatselijke windsnelheid lager is dan 2 meter/seconde.
De stroomsnelheid van het gas moet hoger zijn dan 2,0 liter/minuut.
3. Bediening
Nederlands
153
Detecting
Gas Saving Lives
3.2 Routineonderhoud
De werkwijzen op uw locatie zullen de frequentie aangeven waarmee detectors getest moeten worden
Crowcon beveelt aan dat de IRmax minstens elke 6 maanden met gas getest wordt en zo nodig
opnieuw gekalibreerd wordt. Om de IRmax detector opnieuw te kalibreren volgt u de stappen in 3.1.
In het geval van een elektronicastoring dient u contact op te nemen met uw plaatselijke vertegenwoordiger
van Crowcon.
Kalibratie-interval: Crowcon beveelt aan dat er elke 12 maanden gekalibreerd wordt.
Externe kalibratie via pijp: De windsnelheid moet lager zijn dan 2,0 meter per seconde.
Als deze hoger is, moet de kalibratiekap gebruikt worden om
gasverdunning te voorkomen.
De optische delen reinigen: Dit wordt niet aanbevolen, tenzij de IRmax detector een
belemmeringsfout aangeeft. Als het venster of de spiegel vuil
worden, maak deze dan voorzichtig met water schoon. (Zie
hoofdstuk 5, Accessoires en reserveonderdelen op pagina
156).
Spiegels: Als de spiegel beschadigd is, moet een spiegelvervangingsset worden
aangeschaft (Zie hoofdstuk 5, Accessoires en reserveonderdelen
op pagina 156). Als de spiegel vervangen is, moet de IRmax
detector altijd opnieuw op nul ingesteld en gekalibreerd worden.
Als condensatie storingen veroorzaakt, vervang de spiegel dan (de
optische laag kan beschadigd zijn). Crowcon beveelt aan dat de
spiegel elke 5 jaar vervangen wordt.
3.3 Gassoorten wijzigen
Elke IRmax detector wordt voorgekalibreerd geleverd voor een bepaald type gas (bijvoorbeeld methaan
of propaan). Indien herkalibratie voor een ander soort gas nodig is, kan de IRmax opnieuw met de
PC-communicatiekit geconfigureerd en daarna gekalibreerd worden (Zie hoofdstuk 5, Accessoires en
reserveonderdelen op pagina 156).
3. Bediening
Nederlands
154
Detecting
Gas Saving Lives
3.4 Relatieve respons van gassoorten
De onderstaande grafiek geeft de relatieve respons weer op andere gassoorten voor een IRmax
detector die voor methaan gekalibreerd is.
Opmerking: veel koolwaterstofgassen en -dampen worden eerder door IR-detectoren
opgemerkt dan methaan. De reactie van IRmax (en andere IR-gasdetectoren) is lineair over het
0-100% LEL-bereik van het doelgas (in dit voorbeeld methaan), maar is niet-lineair voor andere
waterstoffen die ook aanwezig kunnen zijn.
Afbeelding 8
De grafiek geeft de respons weer van de bovengenoemde gassen: van links naar rechts, propaan,
butaan, pentaan en methaan.
Andere gassoorten en bereiken zijn beschikbaar. Neem contact op met Crowcon voor meer
informatie.
Nederlands
155
Detecting
Gas Saving Lives
4. Specificatie
Materiaal behuizing 316 roestvrij staal
Afmetingen (alleen detector) 150mm x 75mm x 66mm (zonder pakking)
Gewicht IRmax 1,58 kg
IRmax met vaste IR Display 2 kg
IRmax met IS-barrièremodule 2,4 kg
Afstands-IR Display 0,2 kg
Bedrijfsspanning 12Vdc tot 30V dc
Stroom < 1 W
Uitvoer 3-dradig 4-20 mA (sink of source)
Storingssignaal <1 mA
Maximale kabellusweerstand 80 Ohm (in relatie tot de -ve pool)
Bedrijfstemperatuur -40°C tot +75°C
Vochtigheid 0–100% relatieve vochtigheid
Afdichting IP66
Explosiebescherming Brandveilig
Certificering
ATEX
IRmax (zonder IR Display)
II 2 GD Exd db IIC T6 Gb (Tamb = -40°C tot +50°C)
II 2 GD Exd db IIC T4 Gb (Tamb = -40°C tot +75°C)
II 2 GD Ex tb IIIC T135°C Db (-40°C ≤ Ta≤ +75°C)
IRmax met IS Barrier module (extern display)
II 2 GD Exd db ia IIC T4 Gb (Tamb = -40°C tot +75°C)
Ex tb ia IIIC T135°C Db (Tamb = -40°C tot +40°C)
IRmax met vast IR Display
II 2 G Exd db ia IIC T4 Gb (Tamb = -40°C tot +75°C)
Nr. veiligheidscertificaat
ATEX en IECEx
IRmax (zonder IR Display):
Baseefa 09ATEX0206X en IECEx BAS.09.0109X
IRmax (met IR Display):
Baseefa 09ATEX0220X en IECEx BAS.09.0104X
Functionele veiligheid Gecertificeerd voor gebruik in een SIL 2-systeem.
Certificaatnummer: Sira 12ATEX1206X
Normen EN 60079-0:2012+A11:2013, EN 60079-1:2014,
EN 60079-31:2014
IEC 60079-0:2011, IEC 60079-1:2014, IEC 60079-31:2013
EN 60079-29-1:2007, IEC 61508:2010, EN50402:2005
Zones Gecertificeerd voor gebruik in zone 1 of zone 2
EMC EN50270
Nederlands
156
Detecting
Gas Saving Lives
5. Accessoires en reserveonderdelen
Onderdeelnummers Naam Beschrijving
M041007 Kalibratiekap Past over de standaard weerkap om te
kunnen kalibreren als de plaatselijke
windsnelheid hoger is dan 2 meter per
seconde.
S012130 Montagebeugelset Geschikt voor montage aan een muur of
een pijp van 50 mm. Niet nodig als de
IRmax detector gemonteerd wordt aan
een bestaande extra junction box.
S012152 Zonnekap/
zonnecollector
Kan op de IRmax detector bevestigd
worden om tegen verhoogde
temperaturen vanwege direct zonlicht te
beschermen en/of om de voetafdruk van
de detector te verlengen om lichtere dan
luchtgassen (methaan) te detecteren.
S012169 Leidingmontageset Hiermee kunnen leidingen van 300 mm
tot 3000 mm gecontroleerd worden en
luchtstroom tussen 2 m/s en 20 m/s.
S012996 Stroomadapter Voor toepassingen met gasmonsters
S012827 PC-communicatieset Communicatiemodule, software en snoer
om de detector te kunnen configureren.
M20: S012295
½” NPT: S012296
Extra junction box Montageoptie voor IRmax voor gebruik
in gevaarlijk omgevingen.
C011210 Spiegelreinigingsset Bevat met IPA doordrenkte doekjes en
microvezeldoek
IRmax detector reserveonderdelen
Zie Afbeelding 3 op pagina 145 voor gegevens over reserveonderdelen.
Nederlands
157
Detecting
Gas Saving Lives
6. Problemen oplossen
6.1 Fouten gesignaleerd door LED
De LED die op de contactprintplaat zit, kan storingen helpen identificeren. Zijn positie is getoond in
Afbeelding 7 op pagina 151. De onderstaande tabel toont hoe elk knipperpatroon moet worden
uitgelegd.
LED-patroon Detectorstatus Actie
Elke seconde regelmatig
knipperend.
Normaal.
Aan met korte uitpauzes. Detector bezig
met opstarten.
Wacht 10 seconden.
Snel aan en uit knipperend
of onregelmatig
knipperpatroon
Toevoerspanning
te laag of te hoog.
Controleer of de toevoerspanning naar
de IRmax detector juist is ingesteld.
Controleer of de meting direct bij de
detectorklemmen gemaakt wordt.
Permanent aan. Storing, fout bij
host of i-module.
Laat de IRmax detector rusten, als
de storing blijft, stuur hem dan terug
naar Crowcon.
Twee keer lang knipperen,
gevolgd door kort knipperen.
Fatale fout; fout in
lamp of detector.
Stuur terug naar Crowcon.
Elke seconde snel dubbel
knipperen.
Fatale fout,
module- of
configuratiefout.
Controleer de configuratie van
de IRmax detector met de PC-
communicatieset-software.
Controleer de stroomtoevoer.
Als de storing blijft, stuur hem dan
terug naar Crowcon.
Elke seconde een korte piep. Optische delen
vuil.
Controleer venster en spiegel en maak
zonodig schoon. Zet de IRmax detector
opnieuw op nul en controleer de kalibratie.
Andere fouten kunnen gecorrigeerd worden door de IRmax detector naar Crowcon of een
bevoegde agent te retourneren.
6.2 Analoge uitgang
IRmax blijft in de storingsstand staan en ''Onderhoud nodig" (Service required) wordt op het
IR-display weergegeven (indien aanwezig), als het analoge outputsignaal een storing vertoont of
niet aangesloten is op een regelsysteem of belastingsweerstand. IRmax controleert op actieve wijze
of het analoge outputsignaal van 4-20 mA binnen het bereik valt. Als het signaal buiten het bereik
valt, geeft de detector een storing weer en wordt de output ingesteld op 1 mA. Dit betekent dat
als een detector wordt getest, hij ofwel aangesloten moet zijn op een regelpaneel, of dat er een
belastingsweerstand van 100 Ω aangesloten is tussen de ‘0V’ en ‘Sig’ terminals (detector ingesteld
op ‘Source’) of tussen de ‘0V’ en ‘+V’ terminals (detector ingesteld op ‘Sink’).
Nederlands
158
Detecting
Gas Saving Lives
7. Configuratie RS485 Modbus
7.1 Algemeen
Deze paragraaf vertelt hoe de IRmax detector gebruikt moet worden in een Modbus-configuratie. Er
is een RS485 versie verkrijgbaar voor dergelijke toepassingen. Er kunnen maximaal 28 IRmax detectors
in een ster- of busconfiguratie verbonden worden, zie onder.
Aansluitingen op de RS485 versie van de IRmax detector moeten gemaakt worden via een ringpakking
op een extra aansluitkast (zie hoofdstuk 5 op pagina 156), in plaats van de bekabeling rechtstreeks
naar de IRmax detector te leiden.
Let wel dat het IR Display niet kan worden gebruikt met een RS485-geactiveerde IRmax.
De RS485 ingeschakelde versie van de IRmax detector heeft vijf veldklemmen. De klemmen zijn:
1 Positieve toevoer 12 V tot 30 V boven 0 V
2 0 V Retour en RS485 referentie
3 4-20 mA signaal Source of Sink signaal (optioneel)
4 RS485 B RS-485 verschilsignaal
5 RS485 A RS-485 verschilsignaal
De signalen op de RS485 klemmen voldoen aan de EIA/TIA-485 norm. Dit houdt in dat het algemene
bereik met betrekking tot de 0V-klem van -7V tot +12V is.
Let op dat niet alle RS485 fabrikanten het eens zijn over de polariteit van de A- en B-signalen. Als de
bedrading op de ene manier niet werkt, wissel de RS485 A- en B-draden dan om. Er bestaat geen risico
als er een verkeerde aansluiting gemaakt wordt.
De communicatie-instellingen zijn 9600 bps, twee stopbits en geen pariteit.
Als er een interface samengesteld wordt voor een besturingssysteem, is het belangrijk de hoeveelheid tijd in
overweging te nemen die het systeem nodig heeft om van elke detector informatie te verzamelen. De snelste
snelheid waarmee meerdere detectors ontvangen kunnen worden is 14 detectors per seconde, praktische
omstandigheden kunnen dit aantal verlagen tot 7 per seconde. Gebruikers moeten ervoor zorgen dat de opstelling
alarmsignalen binnen een acceptabele tijdslimiet kan laten registeren.
Het is ook belangrijk ervoor te zorgen dat het systeem genoeg stroom kan leveren om alle detectoren
te laten werken. Om de benodigde hoeveelheid stroom te berekenen voor een lineaire busaansluiting
zie hoofdstuk 7.3, Bekabelingsvereisten, op pagina 160.
Neem voor volledige Modbus-instructies contact op met Crowcon (zie adressen op de achterzijde).
7. Configuratie RS485 Modbus
Nederlands
159
Detecting
Gas Saving Lives
7.2 Bedradingstopologie
De twee algemeen gebruikte bedradingstopologieën zijn de steraansluiting en de lineaire bus.
7.2.1 Steraansluiting
In een steraangesloten topologie zijn alle detectoren aangesloten op een centraal punt. Dit is
meestal het besturingspaneel. Geen enkele kabel heeft meer dan 5 kernen nodig omdat alle 4-20mA
signaalaansluitingen direct naar het besturingspaneel gaan.
De RS485 A- en B-signalen kunnen dan allemaal samen aangesloten worden op het sterpunt. De bus
moet dan op het sterpunt afgesloten worden met een enkele 110 Ohm afsluitweerstand.
De lengte van elke arm van de ster mag niet langer zijn dan 750 meter.
7.2.2 Lineaire busaansluiting
In een busaangesloten topologie worden alle IRmax detectors via een lineaire opstelling aangesloten,
meestal met het besturingspaneel aan één einde. Een klassieke situatie is een tunnelinstallatie, waarbij
er op regelmatige afstanden een IRmax detector geïnstalleerd wordt (zie Afbeelding 9 hieronder).
Om de installatie te bedraden, bevestigt u twee 110 Ohm afsluitweerstanden aan elk fysieke eind van
de bus.
Omdat de 4-20mA signalen niet gedeeld kunnen worden, is er voor elke bedradingverbinding een
extra conductor nodig. Als geen van de 4-20mA signalen gebruikt worden, dan zijn er slechts vier
conductors nodig.
Afbeelding 9
SCHAKELSCHEMA LINEAIRE BUS
NAAR
BEDIENINGSPANEEL
7. Configuratie RS485 Modbus
Nederlands
160
Detecting
Gas Saving Lives
7.3 Bekabelingsvereisten
7.3.1 Berekenen van de minimum vereiste stroom
Hoe meer IRmax detectors er op de lineaire bus aangesloten zijn, hoe meer stroom er nodig is om
het systeem te laten draaien. Om de benodigde stroom voor een bepaalde opstelling te berekenen,
is het nodig om te weten wat de kabelweerstand is tussen elk paar IRmax detectors. Er is minimaal
0,1mA stroom nodig voor elke 'verbinding' tussen de IRmax detectors. De toe te passen spanning kan
berekend worden door de spanningsdaling over elke 'verbinding' in te schatten. Aan het einde moet er
nog minimaal 12V overblijven om de laatste IRmax detector goed te laten functioneren.
Neem voor specifieke gevallen contact op met Crowcon. Eventueel kunnen ook de onderstaande
stappen gevolgd worden en de voorbeeldberekening in het volgende deel.
1. De spanning mag niet onder de 12V dalen. Begin dus de berekening door de spanning op de laatste
IRmax detector in de lijn op die waarde in te stellen.
2. Elke IRmax detector kan tot 0,1A trekken. Bereken het kabelspanningsverlies van de eerste
'verbinding' tussen de IRmax detectors door ervan uit te gaan dat de 'totale stroom' 0,1A is en
vermenigvuldig dit dan met de kabelweerstand van de 'verbinding' tussen de laatste en een na laatste
IRmax detector.
3. Voeg deze spanningsdaling toe aan de 12V voor de laagste acceptabele spanning bij de een na laatste
IRmax detector. Voeg 0,1A toe aan de waarde voor de 'totale stroom' om op 0,2mA uit te komen,
de minimum stroom die door de een na laatste 'verbinding' van de bus loopt. Vermenigvuldig dit met
de kabelweerstand voor de een na laatste 'verbinding' om de volgende spanningsdaling te krijgen.
4. Herhaal dit proces voor elke IRmax detector, waarbij de spanningsverliezen tussen elke detector
vermeerderd worden.
5. De maximum detectorspanning van 30V mag niet overschreden worden.
7.3.2 Voorbeeldberekening
Als voorbeeld geven we de resultaten van de berekening voor zes stuks IRmax detectors die 250 m van
elkaar geplaatst zijn op een kabel met een dwarsdoorsnede van 1mm2. Elke 'verbinding' heeft een weerstand
van 4,6 ohm.
Station Toevoerspanning Toevoerstroom
1 12 0.1 A
2 12.46 0.2 A
3 13.38 0.3 A
4 14.76 0.4 A
5 16.6 0.5 A
6 18.9 0.6 A
Stroom t.b.v. paneel 21.66 0.6 A
Nederlands
161
Detecting
Gas Saving Lives
8. Functionele veiligheidshandleiding
8.1 Inleiding
De volgende delen verschaffen informatie over de certificatie van IRmax volgens de functionele
veiligheidsnormen IEC 61508 en EN 50402. Er wordt informatie verstrekt over de functies voor
veiligheid, onderhoud en data, zodat de IRmax geïntegreerd kan worden in een Safety Instrumented
System (SIS).
8.2 Modbus veiligheidsfunctie van IRmax en IRmax
Concentratiemeting van een brandbaar gas en indicatie van de waarde via een 4-20 mA output.
Storingen van de veiligheidsfunctie worden opgemerkt door de hardware en de bijbehorende
firmware. Ze worden weergegeven als een uitgangssignaal van minder dan 3,6 mA of meer dan 21
mA.
8.3 Informatie over functionele veiligheid
Naam van parameter Symbool Vergelijking / bron IRmax
Proeftestinterval T1 Zoals gedefinieerd door Crowcon.
8760 uur
(jaarlijks)
Gemiddelde tijd voor reparatie MTTR Zoals gedefinieerd door Crowcon. 8 uur
Type A/B Type A Zoals gedefinieerd door Crowcon. Type B
Totale storingen:
λ
Van FMEDA 1.04E-05
Veilige gediagnosticeerde storingen: λ
SD
Van FMEDA 1.95E-08
Veilige niet-gediagnosticeerde storingen: λ
SU
Van FMEDA 8.59E-08
Gevaarlijke gediagnosticeerde storingen: λ
DD
Van FMEDA 9.74E-06
Gevaarlijke niet-gediagnosticeerde
storingen:
λ
DU
Van FMEDA 5.06E-07
Veilige storingen zonder effect: λ
NE
Van FMEDA 3.21E-09
Diagnostische dekking: DC λ
DD
/ (λ
DU
+ λ
DD
) 95.06%
Fractie veilige storingen: SFF (λ
SD
+ λ
SU
+ λ
DD
) / λ 95.11%
Fractie veilige storingen: t
CE
DU
/ λ
D
)(T/2 + MTTR) +
(λ
DD
/ λ
D
) MTTR
2.24E+02
PFDAVG (met gebruik van 61508-6
vergelijking)
PFD
AVG
DU
+ λ
DD
) t
CE
2.30E-03
PFDAVG (met een vereenvoudigde
vergelijking)
PFD
AVG
λ
DU
(T / 2+MTTR) + (λ
DD
MTTR) 2.30E-03
PFDAVG (met gebruik van IEC
61508-6 vergelijking)
PFD
AVG
1-ε
-(λdd+λdu) tce
2.30E-03
SIL-capaciteit (stand voor weinig
vraag)
SIL2
SIL-capaciteit (stand voor hoge
vraag)
SIL2
Voor toepassingen met weinig vraag en gezien willekeurige hardwarestoringen en fractie
veilige storingen, zijn alle systeemvariaties geschikt voor gebruik in SIL 2-toepassingen.
Functionele veiligheidshandleiding
Nederlands
162
Detecting
Gas Saving Lives
8.4 Hardwareconfiguratie
Route 1H (hardwarestoringstolerantie en fractie veilige storingen) is gebruikt om het integriteitsniveau
van de hardware te beoordelen.
8.5 Softwareconfiguratie
De productfirmware is beoordeeld op basis van de vereisten van IEC 61508:3 2010.
8.6 Systematische storingen
Route 1S (zoals gespecificeerd in IEC 61508:2 2010 paragraaf 7.4.2.2c) wordt gebruikt voor naleving
met de vereisten om systematische storingen te voorkomen.
8.7 Diagnostisch interval
De meeste diagnostische functies worden voortdurend gemonitord.
Testen van de systeembewaker moeten worden uitgevoerd tijdens de jaarlijkse proeftest door een
rustfase in te lassen: de IRmax moet elk jaar een rustfase doorlopen (door het verwijderen en weer
aansluiten van de 24 Vdc stroomtoevoer) als onderdeel van het onderhoudsprogramma voor het
product (raadpleeg ook deel 3.2).
8.8 Beperkingen
Storingsfrequentie is constant.
Een proeftest die minstens eenmaal per jaar wordt uitgevoerd wijst op alle verborgen storingen.
Reparaties duren gemiddeld 8 uur.
Aangenomen wordt dat de gebruiker de diagnostische voorziening gebruikt die wordt geleverd via het
IR Display en/of de pc-interface om de mogelijke stilstand te minimaliseren.
De betrouwbaarheidsbeoordeling is een statistisch proces voor toepassing van historische storingsdata
op de voorgestelde designs en configuraties. Dit levert een geloofwaardig doel of een goede schatting
van de waarschijnlijke betrouwbaarheid van de apparatuur, als de productie, het design en de
bedrijfsomstandigheden identiek zijn aan die van de apparatuur waarvan de gegevens zijn verzameld.
Dit is een waardevolle techniek voor het vergelijken van alternatieve designs, het vaststellen van de orde
van grootte van de prestatietargets en het evalueren van de mogelijke gevolgen van designwijzigingen.
De eigenlijke voorspelde waarden kunnen echter niet worden gegarandeerd, omdat het exacte aantal
veldstoringen afhangt van veel facturen die niet gecontroleerd kunnen worden.
Aangenomen wordt dat de storingsfrequentie (symbool λ), voor het doel van deze prognose, over
tijd constant is. Zowel vroege als slijtagestoringen reduceren de betrouwbaarheid, maar aangenomen
wordt dat dergelijke storingen worden voorkomen door inbranden en preventieve vervanging.
Functionele veiligheidshandleiding
Nederlands
163
Detecting
Gas Saving Lives
De storingswaarschijnlijkheid op aanvraag is de waarschijnlijkheid dat het systeem op een willekeurig
moment een storing vertoont. Dit is synoniem aan de permanente onbeschikbaarheid, die wordt
aangegeven door:
Onbeschikbaarheid = (λ x MDT)/(1 + (λ x MDT))
die ongeveer gelijk is aan λ x GST voor kleine waarden van λ x GST
waarbij λ de defectfrequentie is en GST de duur van de gemiddelde stilstand.
Dit komt overeen met de formule voor beschikbaarheid: MTBF/(MTBF+MDT)
De gebruikte defectfrequenties en de verkregen beschikbaarheidswaarden kunnen worden toegepast
op een goed bewezen design, na een geschikte periode van betrouwbaarheidstoename.
8.9 Omgevingsfactoren
Beperkingen door omgevingsfactoren:
Het product moet worden gebruikt bij een maximaal omgevingstemperatuurbereik van
-40°C tot +75°C
Het product moet worden opgeborgen bij een maximaal omgevingstemperatuurbereik
van -40°C tot +80°C
Het product moet worden gebruikt bij een maximaal relatief vochtigheidsbereik van 0%
tot +100% condenserend
Het product heeft een beschermingsklasse van IP66, volgens de definities van norm
EN60529.
Het product is ontworpen voor een voortdurende werking.
8.10 Hardwarestoringstolerantie
De HST is 0.
8.11 Systematische capaciteit
De IREX/IRmax heeft Klasse SC2.
8.12 Classificatie
De IREX/IRmax is een component van type B.
Nederlands
164
Detecting
Gas Saving Lives
Garantie
Deze apparatuur verlaat onze fabriek volledig getest en gekalibreerd. Als binnen de garantieperiode
van drie jaar na verzending blijkt dat de apparatuur defect is als gevolg van een fout in vakmanschap
of materiaal, zullen we het repareren of kosteloos vervangen, onderhevig aan de onderstaande
voorwaarden.
Garantieprocedure
Om een claim zo efficiënt mogelijk te kunnen verwerken, kunt u contact opnemen met ons
ondersteuningsteam op +44 (0)1235 557711 met de volgende informatie:
Uw naam, telefoonnummer, faxnummer en e-mailadres.
Beschrijving en aantal van de te retourneren goederen, waaronder eventuele accessoires.
Serienummer(s) van het instrument.
Reden voor retourneren.
Vraag om een retourformulier voor identificatie en vindbaarheid. Dit formulier kan vanaf onze website
‘crowconsupport.com’ gedownload worden, samen met een retourlabel. We kunnen eventueel ook
een exemplaar e-mailen.
Een IRmax detector wordt zonder een Crowcon retournummer niet onder garantie
geaccepteerd. Het is essentieel dat het adreslabel stevig bevestigd is aan de buitenverpakking
van de te retourneren goederen.
De garantie wordt ongeldig als blijkt dat het instrument gewijzigd, gemodificeerd, ontmanteld is of als er op
andere wijze mee geknoeid is. De garantie dekt geen misbruik van het product.
Garantie disclaimer
Crowcon accepteert geen aansprakelijkheid voor gevolghebbend of indirect verlies of schade die
op wat voor manier dan ook ontstaat (waaronder eventueel verlies of schade die ontstaan door het
gebruik van het instrument) en alle aansprakelijkheid met betrekking tot een derde partij is uitdrukkelijk
uitgesloten.
Deze garantie dekt niet de nauwkeurigheid van de kalibratie van de eenheid of de cosmetische
afwerking van het product. De eenheid moet in overeenstemming met de bedienings- en
onderhoudsinstructies onderhouden worden.
De garantie op vervanging van verbruiksartikelen (zoals de spiegel) die onder garantie geleverd is om
defecte items te vervangen, zal beperkt zijn tot de niet verlopen garantie van het originele geleverde item.
Crowcon behoudt zich het recht voor om een kortere garantieperiode vast te stellen, of om een
garantieperiode af te wijzen voor een sensor die gebruikt wordt in een omgeving of toepassing waarvan
bekend is dat er een risico bestaat van degradatie of schade aan de sensor.
Onze aansprakelijkheid met betrekking tot defecte apparatuur zal beperkt zijn tot de verplichtingen
zoals uiteengezet in de garantie en eventuele verlengde garantie, voorwaarde of verklaring,
uitdrukkelijk of geïmpliceerd, statutair of anderszins met betrekking tot de verkoopbare kwaliteit van
onze apparatuur of de geschiktheid ervan voor een bepaald doel is uitgesloten, behalve als wettelijk is
bepaald. Deze garantie heeft geen invloed op de wettelijke rechten van een klant.
Crowcon behoudt zich het recht voor om verwerkings- en verzendkosten door te berekenen als defecte
geretourneerde items alleen normaal gekalibreerd of onderhouden moesten worden, en dat de klant
dan niet wil laten doen.
Garantie
Nederlands
165
Detecting
Gas Saving Lives
Voor garantie en technische ondersteuning kunt u contact opnemen met:
Customer Support
Tel: +44 (0) 1235 557711
Fax: +44 (0) 1235 557722
Zawartość
Zasada działania i bezpieczeństwo .........................................................169
Idea wykrywacza IRmax .................................................................169
Informacje dotyczące bezpieczeństwa .............................................170
Informacje ogólne o produkcie .........................................................171
1. Wprowadzenie .....................................................................................172
1.1 Informacje ogólne .......................................................................172
1.2 Opis produktu .............................................................................172
2. Instalacja ..............................................................................................174
OSTRZEŻENIE .................................................................................174
2.1 Lokalizacja ..................................................................................174
2.2 Montaż ........................................................................................175
2.3 Podłączanie kabla bezpośrednio do IRmax ..............................175
2.3.1 Oznaczenie zacisku ...........................................................176
2.3.2 Instalowanie wykrywacza IRmax za pomocą wspornika
montażowego ..............................................................................176
2.4 Instalowanie za pomocą dławnicy z króćcem z gwintem
zewnętrznym i dodatkowej skrzynki przyłączowej ............................177
2.4.1 Aby przymocować wykrywacz IRmax do dodatkowej
skrzynki przyłączowej: ................................................................178
2.5 Wymagania dotyczące okablowania ..........................................178
2.6 Połączenia i ustawienia ..............................................................179
3. Działanie ..............................................................................................180
3.1 Procedura przekazania do ekploatacji........................................180
3.2 Rutynowa konserwacja ...............................................................181
3.3 Zmiana typu gazu .......................................................................181
3.4 Odpowiedź względna na inne typy gazów .................................182
4. Dane techniczne ..................................................................................183
5. Akcesoria i części zamienne ...............................................................184
6. Wykrywanie usterek ............................................................................185
6.1 Błędy sygnalizowane przez diodę LED ......................................185
6.2 Wyjście analogowe .....................................................................185
7. Konfiguracja RS485 Modbus ...............................................................186
7.1 Informacje ogólne .......................................................................186
7.2 Topologia okablowania ...............................................................187
7.2.1 Połączenie w układzie gwiazdy ..........................................187
7.2.2 Połączenie magistrali liniowej ............................................187
7.3 Wymaganie dotyczące okablowania ..........................................188
7.3.1 Obliczanie minimalnego wymaganego poziomu mocy .....188
7.3.2 Przykładowe obliczenie......................................................188
8. Podręcznik Bezpieczeństwa Funkcjonalnego ......................................189
8.1 Wstęp ..........................................................................................189
8.2 Urządzenie IRmax i funkcja zabezpieczająca IRmax Modbus ...189
8.3 Dane Bezpieczeństwa Funkcjonalnego ......................................189
8.4 Konfiguracja Sprzętowa ..............................................................190
8.5 Konfiguracja Oprogramowania ...................................................190
8.6 Awarie systemowe ......................................................................190
8.7 Częstotliwość diagnostyki ...........................................................190
8.8 Ograniczenia ...............................................................................190
8.9 Środowiskowe .............................................................................191
8.10 Tolerancja na usterki sprzętowe ...............................................191
8.11 Zdolność systemowa ................................................................191
8.12 Klasyfikacja ...............................................................................191
Gwarancja ................................................................................................192
Polski
169
Detecting Gas Saving Lives
Zasada działania i bezpieczeństwo
Idea wykrywacza IRmax
IRmax jest ultrakompaktowym wykrywaczem gazów na podczerwień (IR), zapewniającym szybkie i
niezawodne wykrywanie gazów oraz par węglowodorów.
Wykrywacz IRmax, cechujący się zastosowaniem technologii czujnika podczerwieni o podwójnej
długości fali i wytrzymałą obudową ze stali nierdzewnej 316, został zaprojektowany do pracy w
najtrudniejszych warunkach. W odróżnieniu od konwencjonalnych wykrywaczy gazów na podczerwień
w IRmax nie są używane ogrzewacze zapobiegające kondensacji na szybkach i lusterkach. Pokrycie
STAY CLIR na elementach optycznych zapobiega kondensacji podczas pracy wykrywacza.
Wykrywacz IRmax jest zgodny z dowolnym układem sterowania działającym zakresie 4 20 mA.
Można go również zamontować w sieci adresowalnej magistrali RS485 Modbus (opis w Rozdziale 7).
Wykrywacz IRmax wymaga mocy zaledwie 1 W — jest to wartość o 75 – 90% niższa niż w
przypadku konwencjonalnych wykrywaczy gazów na podczerwień.
Wykrywacz IRmax jest wyposażony w kompaktową dyfuzyjną komorę gazów, która w połączeniu
ze skuteczną, zabezpieczającą przed warunkami atmosferycznymi nasadką zapewnia doskonałą
szybkość reakcji. Nasadka ta została zaprojektowana z zastosowaniem oprogramowania
modelującego przepływy w celu umożliwienia zdalnego gazowania i kalibracji wykrywacza bez
wymogu stosowania specjalnej nasadki kalibracyjnej.
Wyświetlacz IR Display umożliwia śledzenie odczytów z wykrywacza IRmax, zarówno lokalnie,
jak i zdalnie. Wyświetlacz IR Display można przymocować bezpośrednio do wykrywacza IRmax.
Alternatywnie, IRmax może być dostarczony wraz z modułem bariery iskrobezpiecznej (IS).
Wyświetlacz IR Display można podłączyć do modułu bariery iskrobezpiecznej za pomocą okablowania
tymczasowego lub stałego. Dostępne rozwiązania przedstawiono na Schemat 3, strona 173.
W celu uzyskania szczegółowych informacji o innych akcesoriach do urządzenia IRmax, patrz
Schemat 3 na strona 173 i Dziale 5 na strona 184.
Zasada działania i bezpieczeństwo
Polski
170
Detecting
Gas Saving Lives
Informacje dotyczące bezpieczeństwa
Instalację, obsługę i konserwację wykrywaczy gazów IRmax należy prowadzić ściśle według niniejszych
instrukcji, ostrzeżeń, informacji zawartych na etykietach oraz w ramach określonych ograniczeń.
Tylna pokrywa na wykrywaczu IRmax musi być podczas pracy mocno dokręcona. Nie wolno
podejmować prób odkręcania tylnej zaślepki do chwili odizolowania zasilania wykrywacza
— mogłoby to spowodować zapłon palnej atmosfery. Przed odkręceniem pokrywy w celu
konserwacji, kalibracji lub serwisu należy sprawdzić, czy otaczająca atmosfera nie zawiera
łatwopalnych gazów lub par. Nie otwierać przez kilka minut po odłączeniu zasilania.
Czynności konserwacyjne i kalibrację może wykonywać wyłącznie wykwalifikowany personel
serwisowy.
Należy używać wyłącznie oryginalnych części zamiennych firmy Crowcon. Użycie elementów
zastępczych może spowodować unieważnienie certyfikacji i gwarancji wykrywacza IRMax.
Wykrywacze IRmax należy chronić przed drganiami o skrajnie wysokim natężeniu oraz
bezpośrednim światłem słonecznym w środowisku wysokich temperatur może to
spowodować wzrost temperatury wykrywacza powyżej określonych wartości granicznych i
spowodować przedwczesne uszkodzenie.
Wykrywacz IRmax nie wykrywa wodoru, amoniaku i dwutlenku węgla.
Sprzęt należy uziemić za pomocą dławnicy kablowej i kabla ze stalowym opancerzeniem.
Certyfikat dla Strefy 21/22 - środowisko zapylone IRmax basic (bez wyświetlacza IR lub modułu
IS Barrier) może być wykorzystywany w środowisku, w którym występuje niebezpieczny pył
(Strefy 21 lub 22).
IRmax z modułem IS Barrier może być stosowany w strefach 21 lub 22 pod warunkiem, że
temperatura otoczenia nie przekroczy 40°C, a zdalny wyświetlacz IR lub ręczny wyświetlacz
zainstalowany/używany będzie poza strefą zagrożenia.
Urządzenia IRmax z zamontowanym na stałe wyświetlaczem IR nie można instalować w
Strefach 21 ani 22.
Zasada działania i bezpieczeństwo
Polski
171
Detecting Gas Saving Lives
Informacje ogólne o produkcie
Wykrywacz IRmax jest wykrywaczem gazów na podczerwień zaprojektowanym do wykrywania
powszechnie występujących gazów węglowodorowych w zakresie od 0 do 100% dolnej granicy
wybuchowości: (najniższego stężenia w powietrzu, przy którym może nastąpić zapłon).
Wykrywacz IRmax jest certyfikowanym wykrywaczem przeciwwybuchowym (Exd) zdatnym do
użytku w obszarach niebezpiecznych określanych jako Strefy 1 i 2 ATEX. Etykieta certyfikacyjna z
boku wykrywacza identyfikuje typ certyfikatu odnoszący się do dostarczonego produktu.
Uwaga: jeśli na wykrywaczu IRmax nie jest zamocowana żadna etykieta, nie jest on
certyfikowany do wykorzystania w obszarach niebezpiecznych.
Schemat 1: Etykiety certyfikacyjne wykrywacza IRmax
0811
.TNESERP EB YAM EREHPSOMTA EVISOLPXE NEHW NEPO TON OD :GNINRAW
04- = bmaT( bG 4T CII bd xE 57+ ot C )C
W5=xamW V23=xamV
04- = bmaT
( bG 6T CII bd xE 05+ ot C )C
X9010.90 SAB xECEI X6020XETA90afeesaB
X6021XETA21 ariS 2LIS
DS4 41XO ,modgniK deitnU ,nodgnibA
DG2 II
ROTCETED SAG RI
)C°57+ aT C°04-( bD C°531T CIII bt xE
°°
°
°
Etykieta certyfikacji urządzenia IRmax
Basic
Ex db ia IIC T4 Gb (-40°C Ta +75°C)
Vmax=32V Wmax=5W
WARNING: DO NOT OPEN WHEN EXPLOSIVE ATMOSPHERE MAY BE PRESENT.
IR G A S DET E C TOR W I TH R E M OTE D I SPL A Y
Baseefa09ATEX0220X IECEx BAS 09.0104X
Abingdon, United Kingdom, OX14 4SD
1180
II 2GD
Ex tb ia IIIC T135
°C Db (-40°C Ta +40°C)
Etykieta certyfikatu iskrobezpieczeństwa
urządzenia IRmax
+75°C)Ex db ia IIC T4 Gb (-40°C Ta
II 2G
1180
Abingdon, United Kingdom, OX14 4SD
Baseefa09ATEX0220X IECEx BAS 09.0104X
IR GA S DE TECT OR WI TH D ISPL AY
WARNING: DO NOT OPEN WHEN EXPLOSIVE ATMOSPHERE MAY BE PRESENT.
Vmax=32V Wmax=5W
Etykieta bezpieczeństwa urządzenie IRmax z
zamontowanym na stałe wyświetlaczem IR
Polski
172
Detecting
Gas Saving Lives
1. Wprowadzenie
1.1 Informacje ogólne
Konfiguracja każdego wykrywacza IRmax jest określona przez etykietę umieszczoną na korpusie.
W przypadku kontaktu z firmą Crowcon w celu uzyskania porady lub części zamiennych należy
podać nazwę produktu, nazwę części oraz numer seryjny.
1.2 Opis produktu
Wykrywacz IRmax składa się z korpusu wykonanego ze stali nierdzewnej 316 oraz antystatycznej,
odpornej na działanie czynników atmosferycznych pokrywy optyki i komory pomiarowej gazu oraz
zespołu elektroniki. Można również zamontować moduł IR Display. Instrukcje dotyczące montażu
wyświetlacza IR Display zamieszczono w instrukcji obsługi wyświetlacza (M07061).
Może zostać dostarczona opcjonalna dławnica z króćcem z gwintem zewnętrznym, umożliwiająca
zamocowanie wykrywacza IRmax bezpośrednio na dodatkowych skrzynek przyłączowych z
wlotami kablowymi M20 lub NPT ½ cala.
Wszystkie wymiary podano w milimetrach
Schemat 2: Widok wymiarowy wykrywacza IRmax
Uwaga: korpus wykrywacza IRmax jest dostarczany z dwoma wlotami kablowymi, M20 i
NPT ½ cala. Wlot kablowy, który nie został określony podczas zamawiania wykrywacza
IRmax, jest zaślepiony certyfikowaną zaślepką. Oba przewody urządzenia IRmax muszą być
szczelnie zabezpieczone: jeden z użyciem dławika kablowego, a drugi z użyciem zaślepki
mającej certyfikat IP66.
157.5
74.5
136
60.5
Opcjonalna dławnica
z króćcem z gwintem
zewnętrznym
Łącznie
57
Łącznie 158
74,5
Łącznie 136
Dławnica kablowa
M20 lub NPT ½ cala
Końcówka
zewnętrznego
uziemienia (EARTH)
1. Wprowadzenie
Polski
173
Detecting Gas Saving Lives
Schemat 3: Widok rozebranego wykrywacza IRmax (numery części przedstawiono tam, gdzie mają
zastosowanie)
Nasadka kalibracyjna M041007
Nasadka chroniąca przed wpływem warunków atmosferycznych M04995
Ustalacz lusterka
Lusterko
Adaptor przepływowy S012996
Pierścień uszczelniający typu „O“ do nakrętki oporowej, moduł IS Barrier lub moduł instalow
anego na stałe wyświetlacza IR: M040077
Wspornik montażowy jako kompletny zespół S012130
Dławnica z króćcem z gwintem zewnętrznym, wersje M20 lub NPT ½ cala: M20 ATEX:
S012147, 1/2" NPT ATEX: S012190
Płytka i sworzeń mocujący do tylnej wtyczki, instalowany na stałe wyświetlacz IR i moduł IS Barrier
10
Stała wersja wyświetlacza IR Display
11
Złącze wyświetlacz IR Display – wykrywacz IRmax E07987
12
Moduł bariery iskrobezpiecznej
13
Przewód łączący wyświetlacz IR Display
14
Gniazdo montażowe zdalnego wyświetlacza IR Display M03833
15
Zdalny wyświetlacz IR Display
}
Dostarczane razem z zestawem do wymiany lusterka
C011206
10
11
12
13
14
15
Polski
174
Detecting
Gas Saving Lives
2. Instalacja
OSTRZEŻENIE
Ten wykrywacz został zaprojektowany w sposób umożliwiający zastosowanie w
obszarach niebezpiecznych określanych jako Strefy 1 i 2. Certyfikacja jest uzależniona
od zamontowanych akcesoriów i temperatury otoczenia, w którym urządzenie
pracuje. Szczegóły dotyczące certyfikacji znajdują się w tabeli danych technicznych
na strona 183. Instalację należy przeprowadzić zgodnie z uznanymi standardami
ustalonymi przez odpowiednie władze krajowe.
Aby uzyskać dodatkowe informacje, należy skontaktować się z firmą Crowcon. Przed
wykonaniem jakichkolwiek prac instalacyjnych należy się upewnić, że są przestrzegane
lokalne przepisy i procedury właściwe dla miejsca instalacji.
Sprzęt należy uziemić za pomocą dławnicy kablowej i kabla ze stalowym opancerzeniem.
Nie należy podejmować prób zamontowania wyświetlacza IR Display na wykrywaczu,
który nie został dostarczony w tym celu. Wykrywacze IRmax dostarczone do użytku
z wyświetlaczem mają certyfikat Exd ia i muszą pracować z wyświetlaczem stałym z
barierą iskrobezpieczną lub ze zdalnym bądź ręcznym wyświetlaczem podłączonym za
pośrednictwem modułu bariery iskrobezpiecznej firmy Crowcon.
Wykrywacze IRmax dostarczone bez wyświetlacza mają certyfikat Exd IIC i nie można
ich zmodernizować w celu użycia z wyświetlaczem IR Display.
2.1 Lokalizacja
Wykrywacz IRmax należy zamontować w miejscach, w których występowanie wykrywanego gazu
jest najbardziej prawdopodobne. Podczas umieszczania wykrywaczy gazu należy zwrócić uwagę
na następujące elementy:
W celu wykrycia gazów lżejszych od powietrza, takich jak metan, wykrywacze należy
zamontować na dużej wysokości. W celu wykrycia gazów cięższych od powietrza, takich jak
opary łatwopalne, wykrywacze należy zamontować na małej wysokości.
Umieszczając wykrywacze, należy wziąć pod uwagę uszkodzenia, które mogą zostać
spowodowane przez czynniki naturalne, takie jak deszcz lub powódź. W przypadku
wykrywaczy montowanych na zewnątrz w obszarach bardzo wysokich temperatur firma
Crowcon zaleca stosowanie zasłony przeciwsłonecznej (opis w Dziale 5, Akcesoria i części
zamienne, na strona 184).
Należy wziąć pod uwagę łatwość dostępu do celów związanych z testami funkcjonalnymi i
serwisem.
Należy wziąć pod uwagę zachowanie ulatniających się gazów, wywołane naturalnymi lub
wymuszonymi prądami powietrza. Jeśli jest to właściwe, wykrywacze IRmax należy montować
w kanałach wentylacyjnych (z zastosowaniem zestawu montażowego IRmax do kanałów (opis
w Dziale 5, Akcesoria i części zamienne, na strona 184)).
Należy wziąć pod uwagę warunki procesu. Butan jest na przykład w normalnych warunkach
cięższy od powietrza, ale w przypadku uwolnienia z procesu, w którym występuje podwyższona
temperatura i/lub ciśnienie, może wznosić się zamiast opadać.
Rozmieszczenie czujników należy określić z uwzględnieniem porad ekspertów dysponujących
specjalistyczną wiedzą na temat rozpraszania gazów, sprzętu procesowego stosowanego w
zakładzie, a także kwestii bezpieczeństwa i uwarunkowań technicznych.
2. Instalacja
Polski
175
Detecting Gas Saving Lives
2.2 Montaż
Wykrywacz IRmax można zamontować na trzy sposoby:
1. Za pomocą wspornika montażowego Crowcon z bezpośrednim podłączeniem kabla
(dotyczy wyłącznie zakresu pracy 4 – 20 mA).
2. Za pomocą dławnicy czopowej, w celu podłączenia do istniejącej skrzynki przyłączowej z
certyfikatem Exe lub Exd. Firma Crowcon oferuje dławik z króćcem jako wyposażenie dodatkowe
(patrz punkt 3 poniżej)
3. Za pomocą opcjonalnej dodatkowej skrzynki przyłączowej firmy Crowcon i dławnicy
czopowej.
Części wchodzące w skład wyposażenia dodatkowego podano w wykazie w Dziale 5 na strona 184.
Wykrywacz IRmax należy zainstalować w wyznaczonej lokalizacji z tuleją czujnika umieszczoną
poziomo +/- 15° (orientację przedstawiono na Schemat 2 na strona 172). Zabezpiecza to przed
gromadzeniem się pyłu lub wody na podzespołach optycznych,
2.3 Podłączanie kabla bezpośrednio do IRmax
Ta opcja jest odpowiednia wyłącznie dla działania w zakresie 4 – 20mA. Do przymocowania
wykrywacza do ściany lub rury o średnicy 50 mm wymagany jest wspornik montażowy Crowcon.
Schemat 4: • Połączenia kabli roboczych w detektorze IRmax
Należy podłączyć kable, używając certyfikowanej dławnicy, przez wybrany wlot kablowy na korpusie
wykrywacza IRmax (M20 lub NPT ½ cala). Firma Crowcon zaleca instalację dławnic kablowych
tak, aby były skierowane w dół.
Należy sprawdzić, czy używane dławnice kablowe
mają odpowiedni certyfikat Exd i czy długość gwintu
nie przekracza długości określonej na schemacie
(po lewej).
Sygna³
0V (uziemienie)
+V (24V IRmax)
15mm MAX
Diody LED stanu
2. Instalacja
Polski
176
Detecting
Gas Saving Lives
2.3.1 Oznaczenie zacisku
Przy wykrywaczu IRmax zorientowanym jak na Schemat 2 na strona 172 (wlot kablowy M20 na
górze) trójprzewodowy kabel należy podłączyć, stosując wtyczkę w następujący sposób:
+24 V na dole, 0 V w środku, sygnał na górze.
Złącze z 6 wtykami z prawej strony płytki drukowanej służy do celów serwisowych i/lub podłączania
modułu IR Display.
Zacisk +ve: zasilanie +ve z karty sterowania.
Zacisk Sig: Sygnał/wykrywanie z karty sterowania.
Zacisk 0 V zasilanie -ve z karty sterowania.
2.3.2 Instalowanie wykrywacza IRmax za pomocą wspornika montażowego
a. Wykrywacz IRmax może być dostarczony ze wspornikiem montażowym (S012130)
zamiast dławnicy z króćcem z gwintem zewnętrznym, tak aby można było podłączyć go
bezpośrednio do kabli (opis w Schemat 5).
Schemat 5: Wykrywacz IRmax ze wspornikiem montażowym i dławnicą kablową
b. Jeśli wykrywacz IRmax ma zostać zamontowany na płaskiej powierzchni, należy
zaznaczyć i wywiercić dwa otwory, używając wspornika montażowego jako szablonu.
Obie części wspornika należy luźno zamocować, używając odpowiednich dla ściany/
powierzchni mocowań.
c. Zdjąć nasadkę zabezpieczającą przed działaniem czynników atmosferycznych z
wykrywacza IRmax i przeprowadzić korpus wykrywacza przez wspornik. Zalecana jest
instalacja kadłuba wykrywacza IRmax z wlotem kablowym skierowanym w dół.
wspornik montażowy
70mm pomiędzy środkami
mocowania. Użyj śrub M6.
2. Instalacja
Polski
177
Detecting Gas Saving Lives
d. Zabezpieczyć dwa mocowania wspornika tak, aby wykrywacz IRmax był pewnie
utrzymywany na miejscu. Założyć ponownie nasadkę zabezpieczającą przed wpływem
czynników atmosferycznych.
e. Po pewnym zamocowaniu wykrywacza IRmax na miejscu odkręcić jego tylną zaślepkę,
aby umożliwić dostęp do zacisków kabli.
f. Przygotować kabel — firma Crowcon zaleca zastosowanie kabla z pancerzem 1,5
mm
2
z drutu stalowego (SWA). Można używać kabli innych typów pod warunkiem
ich zgodności z dławnicami z certyfikatem Exd. Zamocować dławnicę kablową z
odpowiednim certyfikatem Exd, przeciągnąć żyły kablowe przez korpus wykrywacza
IRmax i wkręcić dławnicę kablową. Zamocować dławnicę i sprawdzić, czy opancerzenie
kabla jest uziemione do dławnicy kablowej i korpusu wykrywacza IRmax. UWAGA: po
zainstalowaniu kabla należy ponownie zamontować tylną nakrętkę.
g. Płytka mocująca (pozycja 9 na Schemat 3 ze strona 173) musi być bezpiecznie
zamocowana aby zapobiec ryzyku poluzowania się tylnej nakrętki (lub instalowanego na
stałe wyświetlacza IR względnie modułu IS Barrier) na skutek wibracji.
2.4 Instalowanie za pomocą dławnicy z króćcem z gwintem
zewnętrznym i dodatkowej skrzynki przyłączowej
opcję należy zastosować, jeśli wymagane jest połączenie wykrywacza IRmax z istniejącą
dodatkowej skrzynki przyłączowej z certyfikatem Exd lub Exe.
Schemat 6: Wykrywacz IRmax podłączony do skrzynki przyłączowej
2. Instalacja
Polski
178
Detecting
Gas Saving Lives
2.4.1 Aby przymocować wykrywacz IRmax do dodatkowej skrzynki przyłączowej:
a. Ostrożnie zdemontować zewnętrzną część dławnicy z króćcem z gwintem zewnętrznym
(poz. 8, Schemat 3 na strona 173).
b. Przykręcić wąski koniec dławnicy z króćcem z gwintem zewnętrznym do dodatkowej
skrzynki przyłączowej.
c. Podnieść IRmax do skrzynki przyłączowej i poprowadzić przewody przez zespół i do
dodatkowej skrzynki przyłączowej. Przymocować wykrywacz IRmax, przykręcając
mocno pierścień do dławnicy kablowej. Przykręcić wkręt bez łba.
d. Korpus wykrywacza IRmax można obrócić poziomo pod dowolnym kątem pod
warunkiem, że jest to mechanicznie bezpieczne, nie koliduje z innym sprzętem i
umożliwia dostęp do celów związanych z konserwacją
e. Instrukcje dotyczące przewodów zawiera Dziale 2.6. Patrz również Schemat 4 na
strona 175.
2.5 Wymagania dotyczące okablowania
Okablowanie dochodzące do wykrywacza IRmax musi być zgodne z uznanymi standardami
ustalonymi przez odpowiednie władze krajowe i spełniać wymagania elektryczne wykrywacza
IRmax.
Firma Crowcon zaleca zastosowanie kabla z pancerzem z drutu stalowego (SWA) i odpowiednich
dławnic przeciwwybuchowych. Alternatywne techniki wykonania okablowania, takie jak stalowy
kanał kablowy, są akceptowalne pod warunkiem spełnienia odpowiednich standardów.
Maksymalna zalecana długość kabla wynosi 3,4 km (patrz tabela 1).
Wykrywacz IRmax wymaga zasilania prądem stałym 12 30 VDC. Należy zapewnić dopływ z
panelu sterowania do wykrywacza IRmax napięcia przynajmniej 12 V, biorąc pod uwagę spadek
napięcia z powodu oporu kabla przy szczytowym natężeniu prądu 0,1 A. .
Kabel 1,5 mm
2
umożliwia zwykle poprowadzenie na odległość do 3,0 km. W tabeli 1 przedstawiono
maksymalne odległości poprowadzenia kabla dla typowych parametrów.
Powierzchnia
przekroju kabla
Opór Maksymalna odległość
>20 V
Maksymalna odległość
od 18 do 20
mm
2
(Omów na km) (km) (km)
1,0 18,4 2,2 1,6
1,5 13,0 3,0 2,3
2,5 11,5 3,4 2,6
Tabela 1: maksymalne odległości poprowadzenia dla typowych kabli
2. Instalacja
Polski
179
Detecting Gas Saving Lives
2.6 Połączenia i ustawienia
Wszystkie opisane połączenia odnoszą się do zespołu listew zaciskowych korpusu złącza
wykrywacza IRmax. Zaciski na płytce drukowanej złącza wykrywacza IRmax oznaczone „+”,
„sig” i „0 V”. Podłączając wykrywacz do sprzętu sterującego, należy sprawdzić prawidłowość
polaryzacji.
Wykrywacz IRmax jest fabrycznie ustawiony jako „upływ prądowy”, chyba że w zamówieniu
określono inaczej. W razie przestawienia na „źródło prądu” należy zdemontować płytę tylną
i przesunąć dwa łączniki na płytce drukowanej zacisku z położenia „upływu prądowego” do
położenia „źródło”, jak przedstawiono na Schemat 7.
Uwaga: Zacisku uziemienia zewnętrznego należy używać tylko, jeśli lokalne władze
zezwalają na takie połączenie lub wymagają go. Jeśli to możliwe, w celu ograniczenia
zakłóceń częstotliwości radiowej dodatkowej skrzynki przyłączowej i opancerzenie kabla
należy uziemić wyłącznie w panelu sterowania (obszar bezpieczny). Pozwala to uniknąć pętli
uziemienia.
Schemat 7: Położenie zworki upływu/źródła
Sygnał 4 – 20 mA można ustawić na „upływ” lub „źródło” prądu, używając wtyków i łącznika zworki
przedstawionych na schemacie 7. Ustaw prąd na „Sink“ (pochłanianie) poprzez ustawienie łącznika
na piny 3 i 4 zgodnie z ilustracją na zdjęciu po lewej. Ustaw prąd na „Source“ (Źródło) poprzez
ustawienie łącznika na piny 1 i 2 zgodnie z ilustracją na zdjęciu po lewej. Wykrywacze IRmax
ustawione na „upływ” prądu, chyba że w zamówieniu określono inaczej.
Wskazanie diody LED: na płytce drukowanej zacisku jest zamocowana dioda LED,
wskazująca bieżący stan działania. Dodatkowe informacje przedstawiono w Dziale 6 na
strona 185.
CONTROLLER
EARTH
+V
0V
Sg
3
21
Okablowanie
Numer Kolor Funkcja
1 Czerwony +V
2 Czarny 0V
3 Zielony Sygnał
Ustawienia
zworek
upływu
prądowego
źródło
Złącze do podłączania
wyświetlacza IR Display
Złącze do podłączania
zestawu do komunikacji
z komputerem klasy PC
Diody LED stanu
Sterownik
Polski
180
Detecting
Gas Saving Lives
3. Działanie
OSTRZEŻENIE
Przed wykonaniem jakichkolwiek prac instalacyjnych należy się upewnić, że
przestrzegane lokalne przepisy i procedury właściwe dla miejsca instalacji. Nie wolno
podejmować prób otwarcia wykrywacza IRmax lub dodatkowej skrzynki przyłączowej w
obecności łatwopalnego gazu. Aby uniknąć fałszywych alarmów, należy sprawdzić, czy
powiązany panel sterowania jest w stanie wstrzymania.
3.1 Procedura przekazania do ekploatacji
1. Sprawdzić, czy:
a. Połączenia kabli są prawidłowe.
b. Napięcie zasilania jest ustawione na karcie sterowania na zakres od 18 do 30 V. Napięcie
mierzone na zaciskach wykrywacza IRmax (w skrzynce przyłączowej Exe, jeśli jest
używana, lub zacisku na płytce drukowanej wykrywacza IRmax) i musi być ustawione
na zakres od 12 do 30 V.
c. Zwory są ustawione na karcie sterowania odpowiednio na upływ lub źródło 4 – 20 mA.
2. Po uruchomieniu, a przed podjęciem próby wyzerowania/kalibracji należy pozostawić
urządzenie na 30 minut. To opóźnienie zapewnia osiągnięcie stabilności termicznej. (Uwaga:
Wykrywacz IRmax będzie całkowicie zdatny do działania po upływie 30 sekund po
doprowadzeniu mocy).
3. Przed zerowaniem należy zapewnić czyste powietrze (tj. bez gazu węglowodorowego). Odczyt
zera jest dokonywany na karcie sterowania (patrz instrukcje karty sterowania).
4. Założyć nasadkę kalibracyjną na pokrywę zabezpieczającą przed działaniem czynników
atmosferycznych aby odizolować komorę pomiarową od powietrza otoczenia. Taką nasadkę
można zamówić w firmie Crowcon (M041007). Podłączyć gaz kalibracyjny (50% wartości
nominalnej dolnej granicy wybuchowości) i zastosować przepływ 1 litr na minutę.
5. Po 30 sekundach dostosować kalibrację/okres na karcie sterowania tak, aby odczyt
wskazywał 50% dolnej granicy wybuchowości lub odpowiadał zastosowanemu stężeniu gazu
kalibracyjnego. Sam wykrywacz IRmax nie wymaga kalibracji.
6. Odciąć gaz i zdemontować nasadkę kalibracyjną. Sprawdzić ponownie punkt zerowy
7. Po instalacji lub wymianie lusterka wykrywacz można wyzerować i skalibrować z zastosowaniem
wyświetlacza IR Display (opis w strona 169) lub za pośrednictwem zestawu do komunikacji
z komputerem (patrz podręcznik Akcesoria IRmax”).
Uwaga: Wykrywacze IRmax z certyfikatem ATEX dostarczane skalibrowane zgodnie z
normą EN61779 (gdzie na przykład 100% dolnej granicy wybuchowości metanu = 4,4%
objętości).
Uwaga: zaleca się użycie w celu wstępnego przekazania do eksploatacji nasadki
kalibracyjnej. Kolejne kalibracje można wykonywać przez zdalne doprowadzenie gazu
do nasadki zabezpieczającej przed działaniem czynników atmosferycznych przez króciec
(unikając bezpośredniego dostępu do wykrywacza IRmax). Kalibrację bez nasadki
kalibracyjnej (tj. bezpośrednio przez nasadkę zabezpieczającą przed działaniem czynników
atmosferycznych) można wykonać pod warunkiem, że lokalna prędkość wiatru jest niższa
niż 2 m/s. Szybkość przepływu gazu musi przekraczać 2,0 litra/min.
3. Działanie
Polski
181
Detecting Gas Saving Lives
3.2 Rutynowa konserwacja
Częstotliwość testowania wykrywaczy jest określana przez procedury zakładowe. Crowcon zaleca
wykonywanie testów gazowych wykrywacza IRmax przynajmniej co 6 miesięcy i, w razie potrzeby,
ponowną kalibrację. W celu przeprowadzenia ponownej kalibracji wykrywacza IRmax należy
wykonać kroki podane w Dziale 3.1.
W przypadku usterki elektrycznej należy skonsultować się z lokalnym przedstawicielem firmy Crowcon.
Częstotliwość kalibracji: Firma Crowcon zaleca wykonywanie kalibracji co 12
miesięcy.
Zdalna kalibracja przy użyciu przewodu: Szybkość wiatru musi być mniejsza niż 2,0 m/s. Jeśli
jest większa, należy zastosować nasadkę kalibracyjną
w celu zapobieżenia rozcieńczeniu gazu.
Czyszczenie optyki: Nie zaleca się, chyba że wykrywacz IRmax jest w
stanie awarii z powodu całkowitego zaślepienia optyki.
Jeśli dojdzie do zabrudzenia jakiegokolwiek elementu
optycznego, należy go ostrożnie wyczyścić przy pomocy
chusteczek nasączonych alkoholem izopropylowym
lub miękkiej tkaniny znajdującej się w zestawie do
czyszczenia lusterka. (Patrz Dziale 5, Akcesoria i
części zamienne na strona 184).
Zwierciadła: Jeśli lusterko zostało uszkodzone, należy nabyć zestaw
do wymiany lusterka (patrz Dziale 5, Akcesoria i części
zamienne na strona 184). Po wymianie lusterek
wykrywacz IRmax należy zawsze ponownie wyzerować
i powtórzyć kalibrację.
Jeśli kondensacja zaczyna powodować usterki,
wymienić lusterko (pokrycie optyczne mogło ulec
uszkodzeniu). Firma Crowcon zaleca wymianę lusterek
co 5 lat.
3.3 Zmiana typu gazu
Każdy wykrywacz IRmax jest dostarczany wstępnie skalibrowany dla określonego typu gazu (np.
metan lub propan). Jeżeli potrzebna jest rekalibracja dla poszczególnych gazów, wówczas można
przeprowadzić rekonfigurację urządzenia IRmax przy pomocy zestawu do połączenia z komputerem
PC (patrz Dziale 5, Akcesoria i części zamienne na strona 184), a następnie dokonać kalibracji
urządzenia.
3. Działanie
Polski
182
Detecting
Gas Saving Lives
3.4 Odpowiedź względna na inne typy gazów
Na poniższym wykresie przedstawiono odpowiedzi względne wykrywacza IRmax skalibrowanego
na metan na inne typy gazów.
Uwaga: wiele węglowodorów w formie gazów i oparów jest wykrywane przez czujniki IR
zdecydowanie łatwiej niż metan. Reakcja urządzenia IRmax (oraz innych czujników gazu
wykorzystujących promieniowanie podczerwone) działa linearnie w całym przedziale (0-100%)
dolnej granicy wybuchowości (tzn. w tym przypadku metanu) ale nie działa linearnie w
przypadku innych węglowodorów, które mogą być obecne.
Schemat 8
Na schemacie przedstawiono odpowiedź wymienionych powyżej gazów: od lewej do prawej
propan, butan, pentan i metan.
Dostępne inne typy i zakresy gazów. Aby uzyskać bardziej szczegółowe informacje, należy
skontaktować się z firmą Crowcon.
Polski
183
Detecting Gas Saving Lives
4. Dane techniczne
Materiał obudowy Stal nierdzewna 316
Wymiany (tylko wykrywacz IRmax) 150 mm x 75 mm x 66 mm (bez czopu)
Masa IRmax 1,58 kg
IRmax z wersją stałą wyświetlacza IR Display 2 kg
IRmax z modułem bariery iskrobezpiecznej 2,4 kg
Zdalny wyświetlacz IR Display 0,2 kg
Napięcie robocze Od 12VDC do 30VDC
Moc < 1 W
Sygnał wyjściowy 3 przewody, 4 – 20 mA (upływ lub źródło)
Sygnał usterki <1 mA
Maksymalna resystancja pętli przewodu 80 Ohmów (stosunkowo do –terminalu ve)
Temperatura pracy Od -40°C do +75°C (od -40°F do +167°F)
Wilgotność Wilgotność względna 0 – 100%
Stopień ochrony IP66
Zabezpieczenie przed wybuchem Przeciwwybuchowy
Kod atestu
ATEX
IRmax (bez wyświetlacza IR Display)
II 2 GD Exd db IIC T6 Gb (Tamb = -40°C do +50°C)
II 2 GD Exd db IIC T4 Gb (Tamb = -40°C do +75°C)
II 2 GD Ex tb IIIC T135°C Db (-40°C ≤ Ta≤ +75°C)
Urządzenie IRmax z modułem IS Barrier
(wyświetlacz zdalny)
II 2 GD Exd db ia IIC T4 Gb (Tamb = -40°C do +75°C)
Ex tb ia IIIC T135°C Db (Tamb = -40°C do +40°C)
Urządzenie IRmax z zamontowanym na stałe
wyświetlaczem
II 2 G Exd db ia IIC T4 Gb (Tamb = -40°C do +75°C)
Nr certykatu bezpieczeństwa
ATEX i IECEx
IRmax (bez wyświetlacza IR Display):
Baseefa 09ATEX0206X i IECEx BAS.09.0109X
IRmax (z wyświetlaczem IR Display):
Baseefa 09ATEX0220X i IECEx BAS.09.0104X
Bezpieczeństwo Funkcjonale Urządzenie certykowane do użytku w systemach SIL 2.
Numer certykatu Sira 12ATEX1206X
Standardy EN 60079-0:2012+A11:2013, EN 60079-1:2014,
EN 60079-31:2014
IEC 60079-0:2011, IEC 60079-1:2014, IEC 60079-31:2013
EN 60079-29-1:2007, IEC 61508:2010, EN50402:2005
Strefy Certykowany do użytku w Stree 1 lub Stree 2
Zgodność elektromagnetyczna EN50270
Polski
184
Detecting
Gas Saving Lives
5. Akcesoria i części zamienne
Numery części Nazwa Opis
M041007 Nasadka kalibracyjna Mocowana na standardowej nasadce
odpornej na działanie czynników
atmosferycznych, gdy lokalna prędkość
wiatru przekracza 2 m/s.
S012130 Zestaw wspornika
montażowego
Umożliwia zamontowanie na ścianie
lub rurze 2-calowej (50 mm). Nie jest
wymagany w przypadku mocowania
wykrywacza IRmax do istniejącej skrzynki
przyłączowej.
S012152 Zasłona
przeciwsłoneczna/
stożek kolektora
w celu zabezpieczenia przed
podwyższonymi temperaturami
powstającymi w wyniku bezpośredniego
wystawienia na światło słoneczne i/lub
w celu zwiększenia zakresu pokrycia
wykrywaczy, aby umożliwić wykrywanie
gazów lżejszych niż powietrze (metan).
S012169 Zestaw montażowy do
kanałów
Umożliwia monitorowanie kanałów od 300
mm do 3000 mm i przepływu powietrza
między 2 m/s a 20 m/s.
S012996 Adaptor przepływowy Do próbkowania gazu.
S012827 Zestaw do komunikacji
z komputerem
Moduł komunikacyjny, oprogramowanie i
przewód, umożliwiające skongurowanie
wykrywacza.
M20: S012295
½” NPT: S012296
Dodatkowej skrzynki
przyłączowej
Opcja montażu wykrywacza
IRmax do stosowania w obszarach
niebezpiecznych.
C011210 Zestaw do czyszczenia
lustra
Zawiera chusteczki nasycone IPA oraz
ściereczkę z mikrowłókien
Części zamienne wykrywacza IRmax
Szczegóły dotyczące części zamiennych patrz Schemat 3 on strona 173.
Polski
185
Detecting Gas Saving Lives
6. Wykrywanie usterek
6.1 Błędy sygnalizowane przez diodę LED
Wskazania diody LED zamontowanej na płytce drukowanej wyprowadzeń mogą być pomocne
w diagnozowaniu uszkodzeń. Położenie diody przedstawiono na Schemat 7 na strona 179. W
tabeli poniżej przedstawiono interpretację nieprawidłowości na podstawie sekwencji wskazań diody.
Wzorzec sygnału diody LED Stan IRmax Działanie
Regularne błyski odstępach
sekundowych
Prawidłowy.
Włączenie z krótkimi gasnącymi
impulsami.
Wykrywacz IRmax w
trybie uruchamiania.
Odczekać 10 sekund.
Szybkie lub nieregularne błyski. Napięcie zasilania
za niskie lub za
wysokie.
Sprawdzić, czy napięcie zasilania
wykrywacza IRmax jest prawidłowo
ustawione. Sprawdzić, czy pomiar
jest wykonywany bezpośrednio na
zaciskach wykrywacza IRmax.
Stale włączona. Usterka, błąd
hosta lub modułu
i-Module.
Wyłączyć i włączyć IRmax; jeśli
usterka utrzymuje się, zwrócić go do
rmy Crowcon.
Dwa długie błyski, po których
następuje krótki błysk.
Błąd krytyczny;
usterka lampy lub
wykrywacza
Zwrócić wykrywacz do rmy
Crowcon.
Szybkie dwukrotne błyski w
odstępach sekundowych.
Błąd krytyczny;
usterka modułu lub
konguracji.
Sprawdzić kongurację wykrywacza
IRmax za pomocą oprogramowania
Zestaw do komunikacji z
komputerem.
Sprawdzić zasilanie.
Jeśli usterka utrzymuje się, zwrócić
wykrywacz do rmy Crowcon.
Krótkie impulsy w odstępach
sekundowych.
Zasłonięcie
elementów
optycznych.
Sprawdzić szybkę i lusterko, w
razie potrzeby wyczyścić. Ponownie
wyzerować wykrywacz IRmax i
sprawdzić kalibrację.
Jedyną drogą usunięcia innych usterek jest zwrot wykrywacza IRmax do firmy Crowcon lub
autoryzowanego agenta serwisowego.
6.2 Wyjście analogowe
Jeśli wystąpi błąd analogowego sygnału wyjściowego lub jeśli brak połączenia z układem
sterowania lub rezystorem obciążającym, detektor IRmax pozostanie w trybie usterki, a na
wyświetlaczu IR Display (jeśli na wyposażeniu) pojawi się komunikat „Wymagana naprawa”
(Service required). Detektor IRmax aktywnie monitoruje analogowy sygnał wyjściowy 4 20
mA w celu sprawdzenia, czy znajduje się w zakresie. Jeśli sygnał jest poza zakresem, detektor
przechodzi w tryb usterki i ustawia sygnał wyjściowy na 1 mA. Dlatego też podczas testowania
detektora bardzo ważne jest, aby był on podłączony do panelu sterowania lub by między
zaciskiem „0 V” i „Sig” (detektor ustawiony w trybie „źródło”) lub zaciskiem „0 V” i „+V” (detektor
ustawiony w trybie „ujście”) był podłączony rezystor obciążający 100 Ω.
Polski
186
Detecting
Gas Saving Lives
7. Konfiguracja RS485 Modbus
7.1 Informacje ogólne
W tym rozdziale wyjaśniono sposób zastosowania wykrywaczy IRmax w konfiguracji magistrali
Modbus. Dla takich zastosowań dostępna jest wersja obsługująca standard RS485. W
konfiguracjach gwiazdy lub magistrali można połączyć do 28 wykrywaczy IRmax, zgodnie z
zamieszczonym poniżej opisem.
Połączenia z wersją wykrywacza IRmax obsługującą standard RS485 należy wykonywać przez
dławnicę czopową, do dodatkowej skrzynki przyłączowej (patrz Dziale 5 na strona 184); jest to
rozwiązanie lepsze niż prowadzenie okablowania bezpośrednio do wykrywacza.
Należy zauważyć, że wyświetlacz IR Display nie może być stosowany z wykrywaczem IRmax z
odblokowanym interfejsem RS485.
Wersja wykrywacza IRmax obsługująca standard RS-485 ma pięć zacisków pola. Zaciski to:
1 Zasilanie dodatnie Od 12 V do 30 V powyżej 0 V
2 0 V Powrót i odniesienie RS485
3 Sygnały 4 – 20 mA Sygnał źródła lub upływu (wyposażenie opcjonalne)
4 RS485 B Sygnał różnicowy RS485
5 RS485 A Sygnał różnicowy RS485
Sygnały na zaciskach RS485 zgodne ze standardem EIA/TIA-485, co oznacza zakres trybu
ogólnego wynoszący od -7 V do +12 V w odniesieniu do zacisku 0V.
Należy zauważyć, że nie wszyscy producenci urządzeń RS485 zachowują zgodność w odniesieniu
do polaryzacji sygnałów A i B. Jeśli okablowanie nie działa w jeden sposób, użytkownik powinien
zamienić przewody A i B RS-485. Nie występuje niebezpieczeństwo utworzenia nieprawidłowego
połączenia.
Ustawienie komunikacji to 9600 b/s, dwa bity zakończenia transmisji i brak parzystości.
Ważne jest, aby podczas kompilowania interfejsu dla układu sterowania wziąć pod uwagę czas, jaki zajmuje
układowi zgromadzenie informacji z poszczególnych wykrywaczy po kolei. Największa szybkość, z jaką można
odpytywać wiele wykrywaczy, wynosi 14 wykrywaczy na sekundę; względy praktyczne mogą spowodować
ograniczenie tej wartości do 7 wykrywaczy na sekundę. Użytkownik musi zapewnić, aby układ umożliwiał
rejestrację sygnałów alarmowych w akceptowalnych granicach czasu.
Ważne jest również, aby zapewnić zasilanie całego systemu wystarczające dla utrzymania pracy
wszystkich wykrywaczy. Informacje na temat mocy wymaganej przy łączeniu magistrali liniowej
zawiera patrz Dziale 7.3, Wymaganie dotyczące okablowania, na strona 188.
Aby uzyskać wyczerpujące instrukcje dotyczące magistrali Modbus, należy skontaktować się z firmą
Crowcon (patrz adresy na tylnej okładce).
7. Konfiguracja RS485 Modbus
Polski
187
Detecting Gas Saving Lives
7.2 Topologia okablowania
Dwoma używanymi powszechnie topologiami są połączenie w układzie gwiazdy i magistrala liniowa.
7.2.1 Połączenie w układzie gwiazdy
W połączeniu w układzie gwiazdy wszystkie wykrywacze połączone przewodami z punktem
centralnym, którym zwykle jest panel sterowania. Nie są wymagane kable z więcej niż 5 rdzeniami,
ponieważ wszystkie połączenia sygnałów 4 20 mA wykonywane bezpośrednio do panelu
sterowania.
Wszystkie sygnały A i B RS485 można następnie połączyć w punkcie gwiazdy. Magistralę należy
następnie zakończyć w punkcie gwiazdy pojedynczym opornikiem zakończeniowym 110 omów.
Długość poszczególnych ramion gwiazdy nie może przekraczać 750 metrów.
7.2.2 Połączenie magistrali liniowej
W połączeniu z magistralą wszystkie wykrywacze IRmax połączone przewodami w układzie
liniowym, zwykle z panelem sterowania na jednym końcu. Klasycznym przykładem jest instalacja
tunelowa, ze wszystkimi wykrywaczami IRmax instalowanymi w regularnych odstępach (patrz
Schemat 9 poniżej).
Aby wykonać okablowanie instalacji, należy zamontować dwa rezystory końcowe 110 omów na
każdym z fizycznych końców magistrali.
Ponieważ sygnały 4 – 20 mA nie mogą być współdzielone, na każdym hopie okablowania
wymagany jest dodatkowy przewodnik. Jeśli nie jest używany żaden z sygnałów 4 – 20 mA,
wymagane są tylko cztery przewodniki.
Schemat 9
RYSUNEK POŁĄCZEŃ MAGISTRALI LINIOWEJ
DO PANELU
STEROWANIA
7. Konfiguracja RS485 Modbus
Polski
188
Detecting
Gas Saving Lives
7.3 Wymaganie dotyczące okablowania
7.3.1 Obliczanie minimalnego wymaganego poziomu mocy
Im więcej wykrywaczy IRmax jest podłączonych do magistrali liniowej, tym większa moc jest
wymagana do działania systemu. Aby obliczyć moc wymaganą dla określonej konfiguracji, należy
znać opór kabla między poszczególnymi parami wykrywaczy IRmax. Dla każdego hopu między
wykrywaczami IRmax należy dostarczyć prąd przynajmniej 0,1 mA. Napięcie, które należy
zastosować, można obliczyć, szacując spadek napięcia na każdym hopie — aby ostatni wykrywacz
IRmax działał prawidłowo, na końcu musi pozostać przynajmniej 12 V.
W celu uzyskania porady w szczególnych przypadkach należy skontaktować się z firmą Crowcon.
Można również wykonać kroki opisane poniżej i przykładowe obliczenie podane w następnym
rozdziale.
1. Napięcie nie może spaść poniżej 12 V, więc obliczenie należy rozpocząć od ustawienia napięcia
na ostatnim wykrywaczu IRmax w linii na tę wartość.
2. Każdy wykrywacz IRmax może zużyć do 0,1 A. Stratę napięcia kabla na pierwszym hopie między
wykrywaczami można obliczyć, przyjmując prąd sumaryczny o wartości 0,1 A i mnożąc go przez
opór kabla na hopie między ostatnim a przedostatnim wykrywaczem.
3. To napięcie należy dodać do wstępnej wartości 12 V w celu uzyskania najniższej dopuszczalnej
wartości napięcia na przedostatnim wykrywaczu IRmax. Należy dodać 0,1 A do wartości prądu
sumarycznego, aby uzyskać wartość 0,2 mA, minimalny prąd przepływający przez przedostatni
hop magistrali. wartość należy pomnożyć przez opór kabla dla przedostatniego hopu, aby
uzyskać następny spadek napięcia.
4. Ten proces należy powtórzyć dla wszystkich wykrywaczy IRmax, akumulując straty napięcia
występujące między poszczególnymi wykrywaczami.
5. Nie może zostać przekroczona maksymalna wartość napięcia wykrywacza IRmax wynosząca
30 V.
7.3.2 Przykładowe obliczenie
W ramach przykładu podano tu wyniki obliczeń dla sześciu wykrywaczy IRmax rozmieszczonych równo
w odległościach 250 m na kablu o przekroju 1 mm2. Każdy hop ma opór 4,6 oma.
Stanowisko Napięcie zasilania Prąd zasilania
1 12 0,1 A
2 12,46 0,2 A
3 13,38 0,3 A
4 14,76 0,4 A
5 16,6 0,5 A
6 18,9 0,6 A
Zasilanie panelu 21,66 0,6 A
Polski
189
Detecting Gas Saving Lives
8. Podręcznik Bezpieczeństwa Funkcjonalnego
8.1 Wstęp
Poniższe sekcje przedstawiają szczegółowe informacje o certyfikacji urządzeń IRmax zgodnej z
normami Bezpieczeństwa Funkcjonalnego IEC 61508 i EN 50402. Przedstawione informacje
o funkcjach uwzględnianych w obudowach bezpiecznych, wymogach konserwacyjnych i dane
umożliwiające integrację urządzenia IRmax z Systemem Automatyki Zabezpieczeniowej.
8.2 Urządzenie IRmax i funkcja zabezpieczająca IRmax Modbus
Aby zmierzyć stężenie gazu palnego i przedstawić wyniki pomiaru za pomocą mocy wyjściowej 4-20mA.
Błędy w funkcjach bezpieczeństwa będą wykrywane przez sprzęt i oprogramowanie układowe.
Będą one przedstawiane za pomocą mocy wyjściowej niższej niż 3,6mA lub wyższej niż 21mA.
8.3 Dane Bezpieczeństwa Funkcjonalnego
Nazwa parametru Symbol Równanie / źródło IRmax
Przedział czasowy badania
potwierdzającego
T1 Zgodnie z denicją Crowcon.
8 760 godzin
(rocznie)
Średni czas potrzebny na naprawę MTTR Zgodnie z denicją Crowcon. 8 godzin
Rodzaj A/B Rodzaj A Zgodnie z denicją Crowcon. Rodzaj B
Łącznie usterek:
λ
Od FMEDA 1.04E-05
Bezpieczne zdiagnozowane usterki: λ
SD
Od FMEDA 1.95E-08
Bezpieczne niezdiagnozowane usterki: λ
SU
Od FMEDA 8.59E-08
Niebezpieczne zdiagnozowane usterki: λ
DD
Od FMEDA 9.74E-06
Niebezpieczne niezdiagnozowane
usterki:
λ
DU
Od FMEDA 5.06E-07
Bezpieczne usterki nie mające
wpływu na działanie:
λ
NE
Od FMEDA 3.21E-09
Diagnozowany obszar: DC λ
DD
/ (λ
DU
+ λ
DD
) 95.06%
Ułamek Bezpiecznych Usterek: SFF (λ
SD
+ λ
SU
+ λ
DD
) / λ 95.11%
Odpowiednik okresu przestoju
kanału
t
CE
DU
/ λ
D
)(T/2 + MTTR) +
(λ
DD
/ λ
D
) MTTR
2.24E+02
PFDAVG (z wykorzystaniem
równania 61508-6)
PFD
AVG
DU
+ λ
DD
) t
CE
2.30E-03
PFDAVG (z wykorzystaniem
równania uproszczonego)
PFD
AVG
λ
DU
(T / 2+MTTR) + (λ
DD
MTTR) 2.30E-03
PFDAVG (z wykorzystaniem
równania IEC 61508-6)
PFD
AVG
1-ε
-(λdd+λdu) tce
2.30E-03
Kompatybilność z SIL (Tryb niskiego
zapotrzebowania)
SIL2
Kompatybilność z SIL (Tryb
wysokiego zapotrzebowania)
SIL2
W przypadku zastosowań z niskim zapotrzebowaniem i ułamka bezpiecznych usterek, wszystkie
warianty systemu nadają się do wykorzystania w zastosowaniach SIL 2.
Podręcznik Bezpieczeństwa Funkcjonalnego
Polski
190
Detecting
Gas Saving Lives
8.4 Konfiguracja Sprzętowa
Do oceny poziomu integralności bezpieczeństwa sprzętu zastosowano Kolejność operacji 1H
(Odporność na błędy sprzętowe i ułamek bezpiecznych awarii).
8.5 Konfiguracja Oprogramowania
Oceniono oprogramowanie układowe produktu zgodnie z kryteriami określonymi w IEC 61508:3
2010.
8.6 Awarie systemowe
Do oceny zgodności z wymaganiami w zakresie unikania awarii systemowych zastosowano
kolejność operacji 1S (określona w paragrafie 7.4.2.2c IEC 61508:2 2010).
8.7 Częstotliwość diagnostyki
Większość funkcji diagnostycznych jest monitorowana na bieżąco.
Badania systemu nadzoru realizowane w trakcie corocznego badania, w trakcie których
urządzenie poddaje się cyklicznym zmianom mocy: Urządzenie IRmax musi być corocznie poddane
cyklicznym zmianom mocy (tzn. odłącza się zasilanie prądem stałym 24V i podłącza je ponownie),
stanowi to część programu konserwacji produktu (prosimy sprawdzić tez sekcję 3.2).
8.8 Ograniczenia
Wskaźnik awaryjności jest stały.
Przeprowadzane nie rzadziej niż raz do roku badanie sprawności urządzenia wykryje wszystkie
niewykryte wcześniej usterki.
Średni czas potrzebny na przeprowadzenie naprawy to 8 godzin.
Zakłada się, że użytkownik korzysta z funkcji diagnozowania poprzez wyświetlacz IR i/lub poprzez
interfejs PC, w celu zminimalizowania potencjalnego czasu przestoju urządzenia.
Ocena niezawodności to proces statystyczny, w którym wykorzystuje się informacje o awariach
do jakich dochodziło w przeszłości do odpowiednich modyfikacji projektu i konfiguracji. Zapewnia
on wiarygodny cel/szacunkowe dane prawdopodobnej niezawodności urządzenia, zakładając, że
produkcja, projektowanie i warunki eksploatacji identyczne jak te, w których gromadzono dane.
Jest to cenna metoda przeglądu projektu pozwalająca porównywać alternatywne projekty, określać
rząd wielkości docelowej wydajności i oceniać potencjalny wpływ zmian w projekcie. Nie można
jednak zagwarantować, że konkretne przewidywane wartości będą identyczne co liczba awarii,
jaka wystąpi w praktyce, liczba ta zależy od wielu czynników, których nie można uwzględnić w
obliczeniach.
Na potrzeby tej prognozy zakłada się, wskaźnik awaryjności (symbol λ) będzie wartością stałą.
Niezawodność urządzeń malałyby na skutek wczesnych usterek, jak również usterek wynikających
ze zużycia, jednak zakłada się, że ryzyko to jest wyeliminowane poprzez wygrzewanie wczesne i
prewencyjną wymianę urządzeń na nowe.
Podręcznik Bezpieczeństwa Funkcjonalnego
Polski
191
Detecting Gas Saving Lives
Prawdopodobieństwo uszkodzenia w chwili zadziałania jest prawdopodobieństwem, że usterka
systemu wystąpi w dowolnym, losowo wybranym, momencie. Jest to tożsame z niedostępnością w
stanie ustalonym, powodowaną przez:
Niedostępność = (λ x MDT)/(1 + (λ x MDT))
która wynosi w przybliżeniu λ x MDT dla niskich wartości λ x MDT
gdzie λ to wskaźnik awaryjności a MDT to Średni Czas Przestoju (Mean Down Time).
Jest to zgodne z wyrażeniem Dostępności jako: MTBF/(MTBF+MDT)
Użyty wskaźnik awaryjności, i określona w ten sposób dostępność to wartości związane z dobrze
przetestowanym projektem, po odpowiednim okresie wzrostu niezawodności.
8.9 Środowiskowe
Ograniczenia środowiskowe:
Produkt powinien być używany w temperaturze otoczenia mieszczącej się w przedziale od
-40°C do +75 °C
Produkt powinien być przechowywany w temperaturze otoczenia mieszczącej się w
przedziale od -40°C do +80 °C
Produkt powinien być używany przy wilgotności otoczenia mieszczącej się w przedziale
od 0% do 100% kondensacji.
Produkt spełnia wymagania odporności na kurz i wodę IP66, zgodnie z definicją zawartą
w normie EN60529.
Produkt jest przeznaczony do pracy ciągłej.
8.10 Tolerancja na usterki sprzętowe
Współczynnik HFT (tolerancja na usterki sprzętowe) wynosi 0
8.11 Zdolność systemowa
Urządzenia IREX/IRmax należą do klasy SC2.
8.12 Klasyfikacja
IREX/IRmax jest komponentem typu B.
Polski
192
Detecting
Gas Saving Lives
Gwarancja
To wyposażenie opuszcza naszą fabrykę jako w pełni przetestowane i skalibrowane. Jeśli w ciągu
okresu obowiązywania gwarancji, wynoszącego trzy lata od wysyłki, wyposażenie ulegnie awarii z
powodu wadliwego wykonawstwa lub wadliwych materiałów, producent wedle własnego uznania
wykona bezpłatną naprawę lub wymieni wyposażenie, pod następującymi warunkami.
Procedura gwarancyjna
W celu ułatwienia skutecznego przetwarzania wszelkiego rodzaju roszczeń, należy skontaktować
się z naszym działem wsparcia klienta pod numerem +44 (0)1235 557711, podając następujące
informacje:
Nazwa kontaktowa, numer telefonu, numer faksu i adres e-mail.
Opis i ilość zwracanych towarów, z uwzględnieniem wszystkich akcesoriów.
Numery seryjne przyrządu.
Przyczyna dokonania zwrotu.
W celu identyfikacji i śledzenia należy uzyskać formularz zwrotu. Formularz ten wraz z etykietami
zwrotu można pobrać z naszej witryny internetowej crowconsupport.com. Możemy również wysłać
kopię pocztą e-mail.
Przyrządy IRmax bez Numeru Zwrotu Crowcon (CRN) nie będą akceptowane do obsługi
gwarancyjnej. Konieczne jest mocne przytwierdzenie etykiety adresowej do zewnętrznego
opakowania zwracanych towarów
W przypadku stwierdzenia zmian, modyfikacji, demontażu lub manipulacji przy przyrządzie gwarancja
zostanie uznana za nieważną. Gwarancja nie obejmuje nieprawidłowego lub niezgodnego z
przeznaczeniem użycia urządzenia.
Zrzeczenie się odpowiedzialności
Firma Crowcon nie ponosi żadnej odpowiedzialności za straty lub szkody wynikowe lub
pośrednie, powstające w jakikolwiek sposób (z uwzględnieniem wszelkich strat lub szkód
wynikających z zastosowania przyrządu). Ponadto firma Crowcon jednoznacznie wyklucza wszelką
odpowiedzialność wobec stron trzecich.
Niniejsza gwarancja nie obejmuje dokładności kalibracji urządzenia ani wykończenia estetycznego
produktu. Urządzenie należy konserwować zgodnie z instrukcjami obsługi i konserwacji.
Gwarancja dotycząca wymiany elementów zużywalnych (takich, jak lusterka), dostarczanych w
ramach gwarancji w celu wymiany uszkodzonych elementów, jest ograniczona do niewygasłej
gwarancji pierwotnie dostarczonego elementu.
Firma Crowcon zastrzega sobie prawo do określenia skróconego okresu gwarancji lub odrzucenia
okresu gwarancji dla dowolnego czujnika dostarczonego w celu zastosowania w środowisku lub
w celu, o którym wiadomo, że wiąże się z nim niebezpieczeństwo zniszczenia lub uszkodzenia
czujnika.
Nasza odpowiedzialność dotycząca uszkodzonego wyposażenia jest ograniczona do zobowiązań
ustanowionych w gwarancji i wszelkie rozszerzone gwarancje, warunki lub stwierdzenia, wyraźnie
lub w dorozumiany sposób wynikające z ustaw, dotyczące jakości handlowej naszego sprzętu lub
jego odpowiedniości do jakiegokolwiek konkretnego zastosowania, są wyłączone, z wyjątkiem
przypadków ustawowo zabronionych. Niniejsza gwarancja nie wpływa na ustawowe prawa klienta.
Warranty
Polski
193
Detecting Gas Saving Lives
Firma Crowcon zastrzega sobie prawo do zastosowania opłat za obsługę i transport, jeśli
urządzenie zwrócone jako uszkodzone okaże się wymagać tylko normalnej kalibracji lub serwisu,
których dokonania klient odmówi.
Aby zadać pytania dotyczące gwarancji i wsparcia technicznego, należy skontaktować się z:
Dział wsparcia klienta
Tel: +44 (0) 1235 557711
Faks: +44 (0) 1235 557722
Conteúdo
Conceito e segurança ............................................................................... 197
Conceito do detector IRmax ............................................................ 197
Informações de segurança ................................................................. 198
Visão geral do produto...................................................................... 199
1. Introdução ............................................................................................ 200
1.1 Geral ........................................................................................... 200
1.2 Descrição do produto .................................................................. 200
2. Instalação ............................................................................................. 202
AVISO ............................................................................................... 202
2.1 Local ........................................................................................... 202
2.2 Montagem .................................................................................. 203
2.3 Conexão de cabos diretamente ao detector IRmax ................... 203
2.3.1 Designação de terminal ...................................................... 204
2.3.2 Como instalar o detector IRmax utilizando um suporte de
montagem .................................................................................. 204
2.4 Como instalar usando um adaptador de conexão e uma caixa de
derivação auxiliar............................................................................... 205
2.4.1 Para encaixar o detector IRmax em uma caixa de derivação
auxiliar: ....................................................................................... 206
2.5 Requisitos de cabeamento........................................................... 206
2.6 Conexões e configurações........................................................... 207
3. Operação ............................................................................................. 208
3.1 Procedimento de preparação....................................................... 208
3.2 Manutenção de rotina................................................................. 209
3.3 Como alterar tipos de gás ........................................................... 209
3.4 Respostas relativas de tipos de gás .............................................. 210
4. Especificações ....................................................................................... 211
5. Acessórios e peças de reposição ........................................................... 212
6. Como localizar falhas ......................................................................... 213
6.1 Erros indicados pela LED ............................................................. 213
6.2 Saída Analógica .......................................................................... 213
7. Configuração do Modbus RS485 .......................................................... 214
7.1 Geral ........................................................................................... 214
7.2 Topologias de cabeamento ......................................................... 215
7.2.1 Conexão estrela .................................................................. 215
7.2.2 Conexão de barramento linear ........................................... 215
7.3 Requisitos de cabeamento........................................................... 216
7.3.1 Como calcular o nível mínimo de energia necessária ......... 216
7.3.2 Cálculo de amostra ............................................................ 216
8. Manual de Segurança Funcional ........................................................... 217
8.1 Introdução .................................................................................. 217
8.2 Função de Segurança do IRmax e do Modbus do IRmax ............. 217
8.3 Dados de Segurança Funcional .................................................... 217
8.4 Configuração do Hardware ......................................................... 218
8.5 Configuração do Software .......................................................... 218
8.6 Falhas Sistemáticas ...................................................................... 218
8.7 Intervalo de Diagnóstico .............................................................. 218
8.8 Restrições .................................................................................... 218
8.9 Meio ambiente ............................................................................ 219
8.10 Tolerância de Falha de Hardware (TFH) ..................................... 219
8.11 Capacidade do Sistema ............................................................. 219
8.12 Classificação.............................................................................. 219
Garantia ................................................................................................... 220
Português
Brasileiro
197
Detecting Gas Saving Lives
Conceito e segurança
Conceito do detector IRmax
IRmax é um detector infravermelho (IV) de gases ultra compacto que fornece uma detecção rápida
e à prova de falhas de vapores e gases de hidrocarbonetos.
Com uma tecnologia de sensores IV com duplo comprimento de onda em uma resistente caixa
de aço inoxidável 316, o detector IRmax foi projetado para operação nas áreas mais críticas. Ao
contrário dos detectores de gases convencionais, o detector IRmax não possui aquecedores a fim
de evitar condensação em janelas e espelhos. O revestimento STAY CLIR em componentes ópticos
evita a formação de condensação enquanto o detector IRmax está em funcionamento.
O detector IRmax é compatível com qualquer sistema de controle 4-20mA e também pode ser
instalado em uma rede endereçável RS485 Modbus. (consulte a Seção 7).
O detector IRmax requer somente 1 Watt de energia, em geral de 75 a 90% menos que os detectores
de gases IV convencionais.
O detector IRmax inclui uma câmara de gases de difusão compacta que, em combinação com uma
tampa à prova de intempéries eficaz, fornece uma excelente velocidade de resposta. A tampa à prova de
intempéries foi projetada com uso de um software de modelação de fluxo a fim de permitir a exposição
a gases remota e a calibração do detector IRmax, desta forma um adaptador de calibração especial
não é necessário.
O IR Display torna possível monitorar as leituras do IRmax tanto localmente como remotamente.
Um IR Display pode ser instalado diretamente no IRmax. Como alternativa, o IRmax pode ser
fornecido com um módulo de barreira Intrinsecamente Seguro (IS) incluído. Um IR Display pode
então ser conectado ao Módulo de barreira IS por um cabeamento temporário ou permanente. As
opções disponíveis estão ilustradas no Diagrama 2, página 201.
Para mais informações sobre outros acessórios para o IRmax, consulte a Figura 3 na página 28 e a
Seção 5, na página 39.
Conceito e segurança
Português
Brasileiro
198
Detecting
Gas Saving Lives
Informações de segurança
Os detectores de gases IRmax devem ser instalados, operados e mantidos rigidamente de
acordo com estas instruções, avisos, informações de rótulo e dentro das limitações indicadas.
A porca da parte traseira do detector IRmax deve ser mantida firmemente fechada durante a
operação. Não tente remover a porca traseira até que a alimentação elétrica para o detector
IRmax esteja isolada – ou você poderá causar a ignição em uma atmosfera inflamável. Antes
de remover a porca para realizar manutenção ou calibração, verifique se o ambiente que
a envolve está livre de gases ou vapores inflamáveis. Não a abra até que se passem vários
minutos após a remoção da alimentação elétrica.
Operações de manutenção e calibração somente devem ser realizadas por funcionários de assistência
qualificada.
Somente peças de substituição genuínas da Crowcon devem ser utilizadas. Componentes de
substituição invalidarão a certificação e a garantia do detector IRmax.
Os detectores IRmax devem ser protegidos de vibrações extremas e da luz solar direta em
ambientes quentes, pois isto pode fazer com que sua temperatura suba acima dos limites
especificados e resulte em uma falha prematura.
O detector IRmax não detecta hidrogênio, amônia ou dióxido de carbono.
O equipamento deve ser aterrado usando um prensa cabos e cabo de aço blindado.
Certificação para ambientes com poeiras Zona 21/22: O IRmax Básico (sem os módulos IR
Display e Barreira IS) pode ser usado em ambientes que podem conter poeiras perigosas
(Zonas 21 ou 22).
O IRmax com um módulo Barreira IS pode ser usado em Zonas 21 ou 22 desde que a
temperatura ambiente permaneça abaixo de 40°C e um IR Display Remoto ou IR Displays
Portáteis estejam instalados/sejam usados somente fora da área perigosa.
O IRmax com um IR Display fixo não pode ser instalado em uma área Zona 21 ou 22.
Conceito e segurança
Português
Brasileiro
199
Detecting Gas Saving Lives
Visão geral do produto
O detector IRmax é um detector de gases infravermelho projetado para detectar gases de
hidrocarbonetos comuns na faixa de 0 a 100% LIE (Limite inferior de explosão: a concentração
mínima no ar na qual uma ignição pode ocorrer).
O detector IRmax é um detector certificado à Prova de explosão (Exd) adequado para uso em
áreas de risco de Zona 1 ou 2 ATEX. Consulte o rótulo de certificação na lateral do detector IRmax
para identificar o tipo de certificação que está relacionado ao produto fornecido.
Observação: se não existir nenhum rótulo de certificação no detector IRmax, ele não é
certificado para uso em áreas perigosas.
Diagrama 1: Rótulos de certificação do detector IRmax
0811
.TNESERP EB YAM EREHPSOMTA EVISOLPXE NEHW NEPO TON OD :GNINRAW
04- = bmaT( bG 4T CII bd xE 57+ ot C )C
W5=xamW V23=xamV
04- = bmaT
( bG 6T CII bd xE 05+ ot C )C
X9010.90 SAB xECEI X6020XETA90afeesaB
X6021XETA21 ariS 2LIS
DS4 41XO ,modgniK deitnU ,nodgnibA
DG2 II
ROTCETED SAG RI
)C°57+ aT C°04-( bD C°531T CIII bt xE
°°
°
°
Etiqueta de certificação do IRmax Básico
Ex db ia IIC T4 Gb (-40°C Ta +75°C)
Vmax=32V Wmax=5W
WARNING: DO NOT OPEN WHEN EXPLOSIVE ATMOSPHERE MAY BE PRESENT.
IR G A S DET E C TOR W I TH R E M OTE D I SPL A Y
Baseefa09ATEX0220X IECEx BAS 09.0104X
Abingdon, United Kingdom, OX14 4SD
1180
II 2GD
Ex tb ia IIIC T135
°C Db (-40°C Ta +40°C)
Etiqueta de certificação do IRmax com
Barreira IS
+75°C)Ex db ia IIC T4 Gb (-40°C Ta
II 2G
1180
Abingdon, United Kingdom, OX14 4SD
Baseefa09ATEX0220X IECEx BAS 09.0104X
IR GA S DE TECT OR WI TH D ISPL AY
WARNING: DO NOT OPEN WHEN EXPLOSIVE ATMOSPHERE MAY BE PRESENT.
Vmax=32V Wmax=5W
Etiqueta de certificação do IRmax com IR Display Fixo
Português
Brasileiro
200
Detecting
Gas Saving Lives
1. Introdução
1.1 Geral
A configuração de cada detector IRmax está identificada em um rótulo localizado no corpo
principal. Ao entrar em contato a Crowcon para obter assistência ou peças, forneça o nome do
produto, o número de peça e o número de série.
1.2 Descrição do produto
O detector IRmax inclui o corpo principal de aço inoxidável 316, uma tampa antiestática à prova
de intempéries no sistema óptico e na câmara de medição de gás e uma montagem eletrônica.
Também é possível incluir um Módulo do IR Display. As instruções para a instalação do IR Display
aparecem no manual do IR Display (M07061).
Um adaptador de conexão pode ser fornecido para permitir que o detector IRmax seja encaixado
diretamente na caixas de derivação auxiliares com entradas de cabo M20 ou ½” NPT.
Todas as dimensões em milímetros
Diagrama 2: Visualização dimensionada do detector IRmax
Observação: o corpo do detector IRmax é fornecido com duas entradas de cabo: M20 e
1/2" NPT. A entrada de cabo não especificada no momento da encomenda do detector
IRmax será selada com um tampão certificado. O IRmax deve ser instalado com as duas
entradas de cabos vedadas: uma com um prensacabos e a outra com um tampão de
proteção com certificado IP66.
157.5
74.5
136
60.5
Adaptador de
Conexão opcional
57 Total
158 Total
74,5
136 Total
Prensa cabos
M20 ou 1/2" NPT
Terminal de
aterramento
externo
(TERRA)
1. Introdução
Português
Brasileiro
201
Detecting Gas Saving Lives
Diagrama 3: Visualização expandida do detector IRmax (os números de peças estão exibidos se aplicável)
Adaptador de calibração M041007
Tampa a prova de intempéries M04995
Fixador de espelho
Espelho
Adaptador de fluxo S012996
Anel em "O" para a contraporca, Módulo Barreira IS ou Módulo IR Display Fixo: M040077
Suporte de montagem como conjunto completo S012130
Versões M20 ou 1/2" NPT de adaptador de conexão: M20 ATEX: S012147, 1/2" NPT ATEX: S012190
Placa de fixação e parafusos para o tampão traseiro, módulo IR Display Fixo e Barreira IS.
10
Versão fixa do IR Display
11
IR Display para conector do detector IRmax E07987
12
Módulo de barreira IS
13
Condutor de conexão do IR Display
14
Entrada ing de montagem do IR Display remoto M03833
15
IR Display Remoto
}
Fornecido junto como "kit de substituição da lente óptica" C011206
10
11
12
13
14
15
Português
Brasileiro
202
Detecting
Gas Saving Lives
2. Instalação
AVISO
Este detector IRmax é projetado para uso em áreas perigosas Zonas 1 e 2 e a certificação
irá depender dos acessórios instalados e da temperatura operacional do ambiente.
Consulte a tabela de especificações na página 14 para obter os detalhes da certificação. A
instalação deve estar de acordo com os padrões reconhecidos da autoridade apropriada
do país em questão.
Para obter mais informações, entre em contato com a Crowcon. Antes de iniciar qualquer
trabalho de instalação, certifique-se de seguir os regulamentos locais e os procedimentos
da área.
O equipamento deve ser aterrado usando um prensa cabos e cabo de aço blindado.
Não tente encaixar um IR Display em um detector IRmax que não foi fornecido para este
propósito. O detector IRmax fornecido para uso com um visor é certificado por Exd ia e
deve ser operado com um visor fixo que contenha uma barreira IS ou com um visor Remoto
ou Portátil conectado por um módulo de barreira IS da Crowcon.
Os detectores IRmax fornecidos sem um visor são certificados por Exd IIC e não podem
ser retro-instalados para uso com um IR Display.
2.1 Local
O detector IRmax deve ser montado onde há a maior probabilidade de presença dos gases a
serem detectados. Ao escolher uma localidade para detectores de gases, observe o seguinte:
Para a detecção de gases mais leves que o ar, como o metano, os detectores devem estar
montados em um nível alto. Para detectar gases mais pesados que o ar, como vapores
inflamáveis, os detectores devem estar montados em um nível baixo.
Ao posicionar os detectores, considere a possibilidade de danos causados por eventos
naturais, como chuvas ou inundações. Para detectores montados em áreas externas em
regiões de temperaturas altas, a Crowcon recomenda o uso de um protetor solar (consulte a
Seção 5, Acessórios e peças de reposição, na página 212).
Considere uma área de fácil acesso para a realização de testes funcionais e de assistência.
Considere como os gases sendo emitidos podem se comportar dependendo de correntes de
ar naturais ou forçadas. Monte o detector IRmax em dutos de ventilação se for apropriado
(consulte a Seção 5, Acessórios e peças de reposição, na página 212).
Considere as condições do processo. Por exemplo, o butano é geralmente mais pesado que o
ar, mas se ele for liberado de um processo em uma pressão e/ou temperatura elevada, o gás
pode subir em vez de descer.
O posicionamento dos sensores deve ser determinado seguindo o direcionamento de profissionais
com conhecimentos especialistas em dispersão de gases, no equipamento de operações da
instalação e também em relação à engenharia e segurança. É recomendável registrar a decisão final
a respeito do posicionamento dos sensores.
2. Instalação
Português
Brasileiro
203
Detecting Gas Saving Lives
2.2 Montagem
O detector IRmax pode ser montado de três maneiras:
1. Com a utilização do suporte de montagem da Crowcon conectado diretamente ao cabo de
campo (somente operação 4-20mA).
2. Com a utilização de um prensaestopas para conexão com uma caixa de derivação existente
certificada por Exe ou Exd. A Crowcon fornece uma bucha de encaixe adequada como extra
opcional (veja 3 abaixo)
3. Com a utilização de um adaptador de conexão e de uma caixa de derivação auxiliar opcional
Crowcon.
As partes opcionais estão listadas na Seção 5 na página 212.
O detector IRmax deve ser instalado na localidade designada com o tambor do sensor em posição
horizontal +/- 15° (demonstrada no Diagrama 2 da página 200). Isto garantirá que poeira ou água
não se acumulem nos componentes ópticos.
2.3 Conexão de cabos diretamente ao detector IRmax
Esta opção está disponível somente para a operação 4-20mA. É necessário ter um suporte de
montagem da Crowcon para instalar o detector em uma parede ou em um tubo de 2” (50 mm).
Diagrama 4: Conexões dos cabos de campo do IRmax
Conecte aos cabos de campo utilizando uma prensa certificada na entrada de cabo escolhida do
corpo do detector IRmax (M20 ou 1/2" NPT). A Crowcon recomenda instalar o prensa cabos
apontando para baixo.
Certifique-se de usar prensa cabos com a certificação
Exd apropriada e que o comprimento da rosca não
exceda o especificado no diagrama (esquerda).
Sinal
0V (terra)
+V (24V IRmax)
15mm MAX
LED de status
2. Instalação
Português
Brasileiro
204
Detecting
Gas Saving Lives
2.3.1 Designação de terminal
Com o IRmax posicionado conforme demonstrado no Diagrama 2 na página 200 (entrada do
cabo M20 no topo), o cabo de campo de 3 núcleos da instalação deve ser conectado ao terminal
com uso de um conector removível conforme o seguinte:
+24 V na parte inferior, 0V no meio, Sinal na parte superior.
O conector de 6 pinos à direita da PCI é destinado para manutenção e/ou conexão de um módulo
do IR Display
Terminal +ve: fornecimento de +ve do cartão de controle.
Terminal Sig: Sinal do cartão de controle.
Terminal 0 V: fornecimento de -ve do cartão de controle.
2.3.2 Como instalar o detector IRmax utilizando um suporte de montagem
a. O IRmax pode ser fornecido com um suporte de montagem (S012130), em vez de um
prensaestopas, para que ele possa ser conectado diretamente aos cabos de campo
(consulte o Diagrama 5).
Diagrama 5: Detector IRmax com um suporte de montagem e um prensa cabos
b. Se o detector IRmax estiver sendo montado em uma superfície plana, marque e faça os
dois furos com o uso do suporte para montagem como modelo. Encaixe levemente as
duas partes do suporte utilizando acessórios adequados para parede/superfície.
c. Remova a tampa à prova de intempéries do IRmax e deslize o corpo do IRmax pelo
suporte. É recomendável que o corpo do detector IRmax esteja instalado com a entrada
do cabo apontando para baixo.
Suporte de montagem:
70 mm entre os centros de
fixação. Use parafusos M6.
2. Instalação
Português
Brasileiro
205
Detecting Gas Saving Lives
d. Aperte os dois acessórios do suporte para que detector IRmax fique firmemente seguro
no local. Encaixe a tampa à prova de intempéries de volta.
e. Depois de posicionar o detector IRmax de forma segura no local, remova a sua porca
traseira para permitir acesso aos terminais dos cabos.
f. Prepare o cabo: a Crowcon recomenda o cabo de fio de aço blindado (SWA) de 1,5
mm
2
. Outros tipos de cabos podem ser usados se forem compatíveis com os adaptadores
certificados por Exd. Encaixe um prensa cabos adequado e certificado por Exd, passe os
condutores do cabo pelo corpo do detector IRmax e parafuse-o no prensa cabos. Encaixe
a prensa e verifique se a proteção do cabo está aterrada ao prensa cabos e ao corpo do
detector IRmax. Nota: não se esqueça de encaixar a porca traseira de volta após instalar
o cabo.
g. A placa de fixação (item 9 no Diagrama 3, na página 201) deve ser montada firmemente
para evitar qualquer risco de a porca traseira (ou o acessório do módulo IR Display Fixo
ou Barreira IS) ficar frouxa com a vibração.
2.4 Como instalar usando um adaptador de conexão
e uma caixa de derivação auxiliar
Será necessário usar esta opção ao conectar o detector IRmax a uma caixa de derivação auxiliar
existente certificada por Exd ou Exe.
Diagrama 6: Detector IRmax conectado a uma caixa de derivação auxiliar
2. Instalação
Português
Brasileiro
206
Detecting
Gas Saving Lives
2.4.1 Para encaixar o detector IRmax em uma caixa de derivação auxiliar:
a. Remova cuidadosamente a seção exterior do adaptador de conexão (item 8 no Diagrama
3 na página 201).
b. Parafuse a extremidade estreita do adaptador de conexão na caixa de derivação auxiliar.
c. Levante o detector IRmax para a caixa de derivação auxiliar e passe os fios pela
montagem e para dentro da caixa. Fixe o detector IRmax parafusando o anel
firmemente ao prensa cabos. Aperte o parafuso sem cabeça.
d. O corpo principal do detector IRmax pode ser virado horizontalmente em qualquer
ângulo desde que esteja mecanicamente seguro, não interfira com outro equipamento
e que seja acessível para manutenção.
e. Consulte a Seção 2.6 para obter instruções sobre o cabeamento. Consulte também o
Diagrama 4 (página 203).
2.5 Requisitos de cabeamento
A conexão de cabos ao detector IRmax deve estar de acordo com os padrões reconhecidos da
autoridade apropriada do país em questão e deve atender aos requisitos elétricos do detector
IRmax.
A Crowcon recomenda o uso de cabo de fio de aço blindado (SWA) além do uso de prensas
apropriadas à prova de explosões. Técnicas de cabeamento alternativas, como condutos de aço,
são aceitáveis com a condição que elas atendam aos padrões adequados.
O comprimento máximo de cabo recomendável é de 3,4 km (veja a Tabela 1).
O detector IRmax requer uma alimentação dc de 12 - 30 Vdc. Verifique se há um mínimo de 12 V
no detector IRmax do painel de controle, levando em consideração uma queda de tensão devido
à resistência do cabo em uma corrente pico de 0,1 A.
Um cabo de 1,5 mm
2
geralmente permitirá execuções de cabo de até 3,0 km. A tabela 1 abaixo
demonstra as distâncias máximas para os parâmetros típicos de cabos.
C.S.A. Resistência Distância máx.
>20 V
Distância máx.
18 a 20 V
mm
2
(Ohms por km) (km) (km)
1,0 18,4 2,2 1,6
1,5 13,0 3,0 2,3
2,5 11,5 3,4 2,6
Tabela 1: distâncias máximas para cabos típicos
2. Instalação
Português
Brasileiro
207
Detecting Gas Saving Lives
2.6 Conexões e configurações
Todas as conexões descritas possuem referência ao bloco terminal montado no corpo principal do
conector do detector IRmax. Os terminais no conector do detector IRmax da PCI estão marcados
com ‘+’, ‘sig’ e ‘0 V’. Verifique a polaridade correta ao conectar o detector IRmax ao equipamento de
controle.
O detector IRmax está configurado por fábrica como um dispositivo ‘dreno de corrente’, a menos
que seja especificado de outra forma no momento da encomenda. Para redefinir como ‘fonte de
corrente’, remova a placa traseira e mova as duas conexões no terminal da PCI da posição ‘dreno’
para a ‘fonte’, conforme mostrado no Diagrama 7.
Observação: O terminal de aterramento externo somente deve ser usado quando as autoridades
locais permitirem ou solicitarem este tipo de conexão. Quando possível, para limitar a
interferência de frequência de rádio, a caixa de derivação auxiliar e a blindagem de cabo devem
ser aterradas no painel de controle (área segura) somente para evitar loop de terra.
Diagrama 7: Localidade de conector de dreno/fonte
O sinal 4-20 mA pode ser definido como corrente 'Dreno' ou 'Fonte' com o uso dos pinos e do
conector mostrado no Diagrama 7. Defina como "Carga" de corrente instalando o conector
nos pinos 3 e 4 como está ilustrado na fotografia à esquerda. Defina como "Fonte" de corrente
instalando o conector nos pinos 1 e 2 como está ilustrado na fotografia à direita. Os detectores
IRmax estarão definidos como corrente 'Dreno' a não ser que tenha sido especificado ao contrário
no momento da encomenda.
Indicação LED: Uma LED está incluída no terminal da PCI para indicar o status de operação
atual. Consulte a Seção 6 na página 213 para obter mais informações.
CONTROLLER
EARTH
+V
0V
Sg
3
21
Cabeamento
Número Cor Função
1 Vermelho +V
2 Preto 0V
3 Verde Sinal
Configurações
de conector
fonte
dreno
Conector do IR Display
Conector do kit de
comunicações com PC
LED de status
Controlador
Português
Brasileiro
208
Detecting
Gas Saving Lives
3. Operação
AVISO
Antes de executar qualquer trabalho, certifique-se de seguir os regulamentos locais e
os procedimentos da área. Nunca tente abrir o detector IRmax ou a caixa de derivação
auxiliar quando algum gás inflamável estiver presente. Verifique se o controle de painel
associado está inibido para que alarmes falsos sejam evitados.
3.1 Procedimento de preparação
1. Verifique:
a. Se as conexões de cabo estão corretas
b. Se a alimentação de tensão está definida no cartão de controle como de 18 a 30 V. A
tensão medida nos terminais do detector IRmax (na caixa de derivação auxiliar Exe, se
usada, ou na PCI do terminal do detector IRmax) deve estar definida entre 12 e 30 V.
c. Se as conexões estão definidas para dreno ou fonte 4-20 mA, conforme apropriado ao
cartão de controle.
2. Depois o acionar, aguarde 30 minutos antes de tentar zerar/cal. Este atraso existe para
garantir a estabilidade térmica. (Observação: O detector IRmax estará completamente
operacional depois de 30 segundos de sua ativação.)
3. Certifique-se de que somente exista ar limpo (por exemplo, sem gases de hidrocarbonetos)
antes de zerar. Leitura Zero no cartão de controle (consulte as instruções do cartão de
controle).
4. Encaixe o adaptador de calibração na tampa à prova de intempéries para isolar a câmara de
medidas do ar ambiente. Esse tipo de cobertura está disponível pela Crowcon (M041007).
Conecte o gás de calibração (50% de LIE nom) e aplique em uma vazão de 1 litro por minuto.
5. Após 30 segundos, ajuste cal./span no cartão de controle para que o visor leia 50% LIE ou
se corresponda à concentração do gás de calibração aplicado. O detector IRmax não requer
calibração.
6. Remover o adaptador de calibração e o gás. Realize o zero novamente.
7. Na instalação, ou após a alteração do espelho, o detector IRmax pode ser zerado e calibrado
usando um acessório IR Display (consulte a página 197) ou por um Kit de Comunicações
para PC (consulte o Manual Acessórios da IRmax ).
Observação: Detectores IRmax certificados por ATEX serão fornecidos calibrados em
conformidade ao EN61779 (onde, por exemplo, 100% LIE Metano = 4,4% de volume).
Observação: é recomendável usar o adaptador de calibração para a preparação inicial.
As calibrações subsequentes podem ser conduzidas aplicando gás na tampa à prova de
intempéries remotamente pela ponta do tubo (evitando assim a necessidade de acessar
diretamente o detector IRmax). Uma calibração sem o adaptador de calibração (por
exemplo, diretamente pela tampa à prova de intempéries) pode ser executada desde que
a velocidade do vento local esteja abaixo de 2 metros/segundo. A vazão do gás deve ser
superior a 2,0 litros/minuto.
3. Operação
Português
Brasileiro
209
Detecting Gas Saving Lives
3.2 Manutenção de rotina
As práticas locais determinarão com qual frequência o detector IRmax deve ser testado. A
Crowcon recomenda testar o IRmax a gás pelo menos a cada 6 meses e recalibrar conforme
necessário. Para recalibrar um detector IRmax, siga as etapas fornecidas na Seção 3.1.
No caso de uma falha eletrônica, entre em contato com o seu representante local da Crowcon.
Intervalo de tempo para calibração: A Crowcon recomenda a calibração a cada 12 meses.
Calibração remota pela tubulação: Wind speed should be less than 2.0 metres per second.
If greater, use the calibration cap to prevent gas
dilution.
Limpeza dos ópticos: Não é recomendável a menos que o detector
IRmax tenha uma falha de obscurecimento. Se a
janela ou a lente óptica ficarem contaminadas, limpe
cuidadosamente com lenços impregnados IPA e/ou
com o pano macio fornecido no kit de limpeza da lente
óptica (consulte a Seção 5, Acessórios e peças de
reposição na página 212).
Espelhos: Se a lente óptica estiver danificada, obtenha um kit
de substituição da lente óptica (consulte a Seção 5,
Acessórios e peças de reposição na página 212).
O detector IRmax deve sempre ser zerado e calibrado
novamente após uma substituição de espelho.
Se condensação começar a causar falhas, substitua o
espelho (a cobertura óptica pode estar danificada). A
Crowcon recomenda substituir o espelho a cada 5
anos.
3.3 Como alterar tipos de gás
Cada detector IRmax é fornecido pré-calibrado para um tipo de gás em particular (por exemplo,
metano ou propano). Se for necessário recalibrar para um tipo de gás diferente, o IRmax pode ser
reconfigurado usando o kit de comunicações para PC (consulte a Seção 5, Acessórios e peças de
reposição na página 212), e depois calibrado.
3. Operação
Português
Brasileiro
210
Detecting
Gas Saving Lives
3.4 Respostas relativas de tipos de gás
O gráfico abaixo demonstra as respostas relativas a outros tipos de gases para um detector IRmax
calibrado para metano.
Nota: muitos gases e vapores de hidrocarbonetos são detectados com mais facilidade do
que o metano pelos detectores infravermelhos. A resposta do IRmax (e de outros
detectores de gases infravermelhos) será linear em todo intervalo de 0-100% LIE para o gás
alvo (isto é, metano neste exemplo), mas não linear para outros gases de hidrocarbonetos
que também possam estar presentes.
Diagrama 8
O diagrama mostra a resposta dos gases mencionados acima: da esquerda para a direita, etano,
propano, butano, pentano e metano.
Outros tipos e variações de gases estão disponíveis. Entre em contato com a Crowcon para obter
mais detalhes.
Português
Brasileiro
211
Detecting Gas Saving Lives
4. Especificações
Material do Invólucro Aço inoxidável 316
Dimensões (somente
detector IRmax)
150 mm x 75 mm x 66 mm (sem bocal)
Peso IRmax 1,58kg (3,5 lbs)
IRmax com IR Display Fixo 2 kg (4,4 lbs)
IRmax com Módulo de Barreira IS 2,4 kg (5,3 lbs)
IR Display Remoto 0,2 kg (0,4 lbs)
Tensão de operação de 12 Vdc a 30 V dc
Alimentação < 1 W
Saída 3 fios 4 - 20 mA (Dreno ou Fonte)
Sinal de falha <1 mA
Resistência de loop
máxima de cabo
80Ohms (relativo ao terminal negativo)
Temperatura operacional de -40°C a +75°C (-40°F a +167°F)
Umidade 0 – 100% de umidade relativa
Grau de proteção IP66
Proteção contra explosão À prova de explosão
Código de aprovação
ATEX & IECEx
Versão sem display
Ex II 2 GD Ex db IIC T6 Gb (Tamb -40°C ≤ a ≤ +50°C)
Ex II 2 GD Ex db IIC T4 Gb (Tamb -40°C ≤ a ≤ +75°C)
Ex II 2 GD Ex tb IIIC T135°C Db (Tamb -40°C ≤ a ≤ +75°C)
Versão com IS Barrier module
Ex II 2 G Ex db ia IIC T4 Gb (Tamb -40°C ≤ a ≤ +75°C)
Ex II 2 GD Ex tb IIIC T135°C Db (Tamb -40°C ≤ Ta ≤ +40°C)
Versão com display
Ex II 2 GD Ex db ia IIC T4 Gb (Tamb -40°C ≤ a ≤ +75°C)
Nº de certificado de
segurança
ATEX e IECEx
IRmax (sem IR Display):
Baseefa 09ATEX0206X and IECEx BAS.09.0109X
IRmax (com IR Display):
Baseefa 09ATEX0220X and IECEx BAS.09.0104X
Segurança funcional Certificado para uso num sistema SIL 2.
Número do certificado: Sira 12ATEX1206X
Padrões EN 60079-0:2012+A11:2013, EN 60079-1:2014,
EN 60079-31:2014
IEC 60079-0:2011, IEC 60079-1:2014, IEC 60079-31:2013
EN 60079-29-1:2007, IEC 61508:2010, EN50402:2005
Zonas Certificado para uso em Zona 1 ou Zona 2
EMC EN50270
Português
Brasileiro
212
Detecting
Gas Saving Lives
5. Acessórios e peças de reposição
Código Nome Descrição
M041007 Adaptador de
calibração
Encaixa no detector para permitir a
calibração quando a velocidade do
vento local for superior a 2 metros por
segundo.
S012130 Kit suporte de
montagem
Permite montagem em uma parede ou
tubo de 2" (50 mm). Não é necessário
se o detector IRmax já tiver uma caixa
de junção existente instalada.
S012152 Cone coletor/protetor
solar
Pode ser instalado no detector IRmax
para proteção contra temperaturas
elevadas devido luz direta do sol e/
ou aumentar a área de cobertura dos
detectores para que gases mais leves
que o ar sejam detectados (metano).
S012169 Kit de montagem
de duto
Permite a monitoração de dutos de
300 mm a 3000 mm e fluxo de ar
entre 2 m/s e 20 m/s.
S012996 Adaptador de fluxo Para aplicativos de amostragem de
gás.
S012827 Kit de Comunicações
para PC
Módulo de comunicações, software e
conector que permitem a configuração
do detector IRmax.
M20: S012295
½” NPT: S012296
Auxiliary junction box Opção de montagem do IRmax para
uso em ambientes perigosos.
C011210 Kit de limpeza de
espelho
Contém limpadores com álcool
isopropílico (IPA) e tecido de microfibra
Peças do detector IRmax
Consulte o Diagrama 3 na página 201 para detalhes a respeito das peças de reposição.
Português
Brasileiro
213
Detecting Gas Saving Lives
6. Como localizar falhas
6.1 Erros indicados pela LED
A LED instalada no terminal PCB pode ajudar a identificar falhas. A sua posição está
demonstrada no Diagrama 7 na página 207. A tabela abaixo mostra como interpretar o que
há de errado em cada padrão de piscadas.
Padrão de LED Status do
detector IRmax
Ação
Piscadas regulares a cada
segundo.
Saudável.
Ligada com períodos curtos
sem iluminação.
Detector IRmax
no modo de
inicialização.
Aguarde 10 segundos.
Padrão de piscadas
irregulares ou luz ativada e
desativada.
Tensão de
alimentação baixa
ou alta demais.
Verifique se a tensão de alimentação
do detector IRmax está definida
corretamente. Verifique se a medição
foi realizada diretamente dos
terminais do detector IRmax.
Sempre ligada. Falha, erro de
host ou i-módulo.
Realize um ciclo de energia no
detector IRmax. Se o problema
continuar, retorne-o à Crowcon.
Duas longas piscadas
seguidas por uma piscada
curta.
Erro fatal; falha da
lâmpada ou do
detector IRmax.
Retornar à Crowcon ou
Representante.
Piscada dupla rápida a cada
segundo.
Erro fatal; falha
de configuração
ou módulo.
Verifique as configurações do
detector IRmax usando o software
para Kit de Comunicações para PC.
Verifique a alimentação elétrica.
Se o problema continuar, devolva-o
à Crowcon.
Luz apaga rapidamente a
cada segundo.
Os ópticos foram
obstruídos.
Verifique a janela e o espelho, limpe-os
se necessário. Zere o detector IRmax
novamente e verifique a calibração.
Quaisquer outras falhas somente poderão ser reparadas perante a devolução do detector IRmax
à Crowcon ou a um agente de serviços autorizados.
6.2 Saída Analógica
O IRmax permanecerá em estado de Defeito e aparecerá "Manutenção necessária" (Service
required) no IR Display (se instalado) se o sinal analógico de saída tiver falhado ou se não estiver
conectado a um sistema de controle ou resistência de carga. O IRmax monitora ativamente o sinal
analógico de saída de 4-20 mA para verificar se está dentro da faixa. Se o sinal estiver fora da
faixa, o detector passa ao estado de defeito e a saída é definida para 1 mA. Assim, ao testar um
detector, é imprescindível que ele esteja conectado a um painel de controle ou que uma resistência
de carga de 100 Ω esteja conectada entre os terminais de "0 V" e "Sig" (detector definido no
modo "Fonte") ou entre os terminais de "0 V" e "Pos" (detector definido no modo "Carga").
Português
Brasileiro
214
Detecting
Gas Saving Lives
7. Configuração do Modbus RS485
7.1 Geral
Esta seção explica como usar os detectores IRmax em uma configuração Modbus. Uma versão
ativada RS485 está disponível para estes aplicativos. Até 28 detectores IRmax podem ser
vinculados nas configurações de estrela ou de barramento, conforme descrito abaixo.
As conexões para a versão RS485 do detector IRmax devem ser feitas por um adaptador de
conexão para uma caixa de junção (consulte a Seção 5 na página 200), em vez de ser cabeada
diretamente no detector IRmax.
Observe que o IR Display não pode ser usado com um IRmax ativado com RS485.
A versão ativada por RS-485 do detector IRmax possui cinco terminais de campo. Os terminais são:
1 Alimentação positiva 12 V a 30 V acima de 0 V
2 0 V Retorno e referência RS485
3 4-20 mA sinal Sinal fonte ou dreno (opcional)
4 RS485 B Sinal diferencial RS485
5 RS485 A Sinal diferencial RS485
Os sinais nos terminais RS485 estão em conformidade com o padrão EIA/TIA-485, o que significa
que o intervalo de modo comum é de -7V a +12V em relação ao terminal 0V.
Observe que nem todos os fabricantes de RS485 concordam com a polaridade dos sinais A e B. Se
o cabeamento não funcionar de alguma forma, os usuários devem alternar os fios A&B do RS485.
Não há nenhum risco se uma conexão errada for realizada.
As configurações de comunicação são de 9600 bps, dois bits de parada e nenhuma paridade.
Ao compilar uma interface para um sistema de controle, é importante considerar a quantidade de tempo que
o sistema leva para coletar informações de cada detector por vez. A velocidade mais rápida, na qual vários
detectores podem ser reunidos, é de 14 detectores por segundo, mas condições práticas podem reduzir
isto para 7 por segundo. Os usuários devem se certificar de que o ajuste permita que sinais de alarme sejam
registrados dentro de limites de tempo aceitáveis.
Também é importante certificar-se de que o sistema seja capaz de fornecer energia suficiente para
manter todos os detectores em funcionamento. Para calcular a quantidade de energia necessária
em uma conexão de barramento linear, consulte Seção 7.3, Requisitos de cabeamento, na
página 216.
Para obter instruções completas sobre Modbus, entre em contato com a Crowcon (endereços
localizados na capa traseira).
7. Configuração do Modbus RS485
Português
Brasileiro
215
Detecting Gas Saving Lives
7.2 Topologias de cabeamento
As duas topologias comuns de cabeamento em uso são a conexão estrela e o barramento linear.
7.2.1 Conexão estrela
Em uma topologia conectada por estrela, todos os detectores IRmax estão conectados por fios
em um ponto central, que geralmente é o painel de controle. Nenhum dos cabos são requeridos
a ter mais de 5 núcleos e todas as conexões de sinal 4-20 mA são direcionadas diretamente para
o painel de controle.
Os sinais RS485 A e B podem então ser conectados todos juntos em um ponto de estrela. O
barramento pode então ser encerrado no ponto de estrela com um único resistor de terminação
de 110 ohm.
O comprimento de cada braço da estrela não pode exceder 750 metros.
7.2.2 Conexão de barramento linear
IEm uma topologia conectada por barramento, todos os detectores IRmax estão cabeados por
fio a um ajuste linear, geralmente com o painel de controle em uma extremidade. Uma situação
clássica seria uma instalação de túnel, com os detectores IRmax instalados em intervalos regulares
(consulte o Diagrama 9 abaixo).
Para fazer as ligações da instalação, devem ser montados dois resistores de terminação de 110
ohm: um em cada extremidade física do barramento.
Como os sinais 4-20mA não podem ser compartilhados, um condutor adicional é necessário em
cada salto de cabeamento. Se nenhum dos sinais 4-20 mA estão sendo usados, somente quatro
condutores serão necessários.
Diagrama 9
PARA O PAINEL
DE CONTROLE
DIAGRAMA DE CONEXÃO DE BARRAMENTO
LINEAR
7. Configuração do Modbus RS485
Português
Brasileiro
216
Detecting
Gas Saving Lives
7.3 Requisitos de cabeamento
7.3.1 Como calcular o nível mínimo de energia necessária
Quanto mais detectores IRmax estiverem conectados ao barramento linear, uma maior quantidade
de energia será necessária para executar o sistema. Para calcular a energia necessária para uma
configuração em particular, é necessário saber a resistência do cabo entre cada par de detectores
IRmax. Uma corrente de pelo menos 0,1 mA deve ser permitida para cada ‘salto’ entre os
detectores IRmax. A tensão a ser aplicada pode ser calculada estimando a queda de tensão em
cada ‘salto’ – no final, pelo menos 12 V devem permanecer para garantir que o último detector
IRmax funcione corretamente.
Entre em contato com a Crowcon para obter assistência sobre casos específicos. Como alternativa,
siga as etapas descritas abaixo e o cálculo de amostra mostrado na próxima seção.
1. A tensão não deve cair abaixo de 12 V, logo comece o cálculo definindo a tensão no último
detector IRmax da linha na válvula.
2. Cada detector IRmax pode chegar a 0,1 A. Calcule a perda de tensão do cabo do primeiro
‘salto’ entre os detectores assumindo a ‘corrente agregada’ como 0,1 A e multiplique isto pela
resistência de cabo do ‘salto’ entre o último e o "último menos um” detector IRmax.
3. Adicione esta queda de tensão ao 12 V inicial para obter a tensão mínima aceitável no último e
único detector IRmax. Adicione 0,1 A ao valor para a ‘corrente agregada’ para obter 0,2 mA, a
corrente mínima correndo através do último, porém único, ‘salto’ do barramento. Multiplique isto
pela resistência do cabo para o último, porém único ‘salto’ para obter a próxima queda de tensão.
4. Repita este processo para cada detector IRmax, acumulando as perdas de tensão que irão
ocorrer entre cada detector IRmax.
5. A tensão do detector IRmax máxima de 30 V não deve ser excedida.
7.3.2 Cálculo de amostra
Como exemplo, em seguida estão os resultados de cálculos de seis detectores IRmax espaçados
igualmente 250 m uns dos outros no cabo com uma área de seção transversal de 1 mm
2
. Cada salto
possui uma resistência de 4,6 ohms.
Estação Tensão de alimentação Corrente de alimentação
1 12 0,1 A
2 12,46 0,2 A
3 13,38 0,3 A
4 14,76 0,4 A
5 16,6 0,5 A
6 18,9 0,6 A
Alimentação de painel 21,66 0,6 A
Português
Brasileiro
217
Detecting Gas Saving Lives
8. Manual de Segurança Funcional
8.1 Introdução
As seções a seguir fornecem detalhes sobre a certificação do IRmax de acordo com as normas
de Segurança Funcional IEC 61508 e EN 50402. São dadas informações sobre as características
consideradas no caso de segurança, requisitos de manutenção e dados para permitir que o IRmax
seja integrado no Sistema de Instrumentos de Segurança (SIS).
8.2 Função de Segurança do IRmax e do Modbus do IRmax
Para medir a concentração de gás inflamável e indicar a medida por meio de uma saída de 4-20 mA.
Falhas relativas à função de segurança serão detectadas pelo hardware e firmware associado. Elas
serão reveladas como uma saída de menos de 3,6 mA ou mais de 21 mA.
8.3 Dados de Segurança Funcional
Nome do parâmetro Símbolo Equação / Fonte IRmax
Intervalo de Teste de Prova T1 Conforme definição da Crowcon.
8.760 horas
(anuais)
Tempo médio para reparar MTTR Conforme definição da Crowcon. 8 horas
Tipo A/B Tipo A Conforme definição da Crowcon. Tipo B
Total de falhas:
λ
Da FMEDA 1.04E-05
Falhas seguras diagnosticadas: λ
SD
Da FMEDA 1.95E-08
Falhas seguras não diagnosticadas: λ
SU
Da FMEDA 8.59E-08
Falhas perigosas diagnosticadas: λ
DD
Da FMEDA 9.74E-06
Falhas perigosas não diagnosticadas: λ
DU
Da FMEDA 5.06E-07
Falhas seguras sem efeito: λ
NE
Da FMEDA 3.21E-09
Cobertura de diagnóstico: DC λ
DD
/ (λ
DU
+ λ
DD
) 95.06%
Fração de falhas seguras: SFF (λ
SD
+ λ
SU
+ λ
DD
) / λ 95.11%
Tempo de paralisação
equivalente do canal
t
CE
DU
/ λ
D
)(T/2 + MTTR) +
(λ
DD
/ λ
D
) MTTR
2.24E+02
PFDAVG (usando a equação
61508-6)
PFD
AVG
DU
+ λ
DD
) t
CE
2.30E-03
PFDAVG (usando equação
simplificada)
PFD
AVG
λ
DU
(T / 2+MTTR) + (λ
DD
MTTR) 2.30E-03
PFDAVG (usando a equação IEC
61508-6)
PFD
AVG
1-ε
-(λdd+λdu) tce
2.30E-03
Capacidade SIL (modo baixa
demanda)
SIL2
Capacidade SIL (modo alta
demanda)
SIL2
Para aplicações de baixa demanda, com respeito a falhas aleatórias de hardware e fração de
falha segura, todas as versões do sistema são adequadas para uso em aplicações SIL 2.
Manual de Segurança Funcional
Português
Brasileiro
218
Detecting
Gas Saving Lives
8.4 Configuração do Hardware
A Rota 1H (tolerância de falha de hardware e fração de falha segura) foi usada para avaliar o nível
de integridade de segurança do hardware.
8.5 Configuração do Software
A avaliação do firmware do produto foi feita de acordo com os requisitos da norma IEC 61508:3
2010.
8.6 Falhas Sistemáticas
A Rota 1S (conforme especificação na IEC 61508:2 2010 parágrafo 7.4.2.2c) é usada para
conformidade com os requisitos de evitar falhas sistemáticas.
8.7 Intervalo de Diagnóstico
A maioria das funções de diagnóstico são monitoradas continuamente.
Testes do watchdog do sistema devem ser realizados durante o teste de prova anual desligando
e religando o instrumento: O IRmax deve ser desligado e religado anualmente (isto é, a fonte de
alimentação de 24 VCC deve ser removida e reaplicada) como parte do programa de manutenção
do produto (consulte também a seção 3.2).
8.8 Restrições
As taxas de falha são constantes.
Um teste de prova realizado pelo menos uma vez por ano identificará todas as falhas não reveladas.
Os reparos têm um tempo médio de duração de 8 horas.
Supõe-se que o usuário utiliza a função de diagnóstico fornecida através do acessório IR Display e/
ou da interface para PC, a fim de minimizar possível tempo de paralisação do produto.
A avaliação de confiabilidade é um processo estatístico para aplicar dados de falha históricos a
desenhos e configurações propostos. Portanto, proporciona uma meta/estimativa verossímil da
provável confiabilidade do equipamento, supondo-se que a fabricação, desenho e condições
operacionais sejam idênticas àquelas sob as quais os dados foram coletados. É uma técnica de
revisão de desenho importante para comparar desenhos alternativos, estabelecendo metas de
desempenho em ordem de grandeza e avaliando os efeitos potenciais de mudanças no desenho.
No entanto, os valores previstos reais não podem ser garantidos como previsão do número preciso
de falhas em campo que realmente ocorrerão, já que isto depende de muitos fatores fora do
controle do exercício de previsão.
Supõe-se que as taxas de falha (símbolo λ), para os fins desta previsão, são constantes no tempo.
Falhas precoces ou relacionadas com o desgaste reduziriam a confiabilidade, mas supõe-se que
sejam removidas por queima e substituição preventiva respectivamente.
Manual de Segurança Funcional
Português
Brasileiro
219
Detecting Gas Saving Lives
A probabilidade de falha sob demanda é a probabilidade de que o sistema estará em um estado
de falha num momento aleatório. Isto é sinônimo de uma indisponibilidade estável que é dada por:
Indisponibilidade = = (λ x TMP)/(1 + (λ x TMP))
que se aproxima a λ x TMP para pequenos valores de λ x TMP
onde λ é a taxa de falhas e TMP é o Tempo Médio de Paralisação.
Isto é consistente com a expressão de disponibilidade dada como: MTBF/(MTBF+TMP)
As taxas de falhas usadas, e assim as disponibilidades derivadas, são as plausivelmente associadas
a um desenho bem comprovado após um período adequado de crescimento de confiabilidade.
8.9 Meio ambiente
Restrições ambientais:
O produto deve ser operado a uma gama de temperatura ambiente máxima de -40°C a
+75°C.
O produto deve ser armazenado a uma gama de temperatura ambiente máxima de
-40°C a +80°C.
O produto deve ser operado a uma gama de umidade relativa ambiente máxima de 0% a
+100% com condensação.
O produto tem um Índice de Proteção contra Líquidos e Poeira IP66 de acordo com as
definições da norma EN60529.
O produto é projetado para operação contínua.
8.10 Tolerância de Falha de Hardware (TFH)
A TFH é 0.
8.11 Capacidade do Sistema
O IREX/IRmax é da Classe SC2.
8.12 Classificação
O IREX/IRmax é um componente tipo B.
Português
Brasileiro
220
Detecting
Gas Saving Lives
Garantia
Este equipamento sai da fábrica completamente testado e calibrado. Se, dentro do período de
garantia de três anos da entrega, for provado que o equipamento se encontrava defeituoso devido
a falhas na fabricação ou material, nós garantimos o seu conserto ou substituição gratuita de
acordo com as condições abaixo.
Procedimento de garantia
Para facilitar um processamento eficaz de qualquer solicitação, entre em contato com a nossa
equipe de assistência ao cliente pelo número +44 (0)1235 557711 com as seguintes informações:
O seu nome, número de contato, número de fax e endereço de email.
A descrição e a quantidade dos produtos que estão sendo retornados, incluindo quaisquer
acessórios.
Número(s) de série do instrumento.
Motivo de devolução.
Obtenha um formulário de devoluções para motivos de identificação e rastreamento. Este
formulário pode ser baixado de nosso site da web ‘crowconsupport.com’, juntamente de uma
etiqueta para devolução. Como alternativa, nós podemos enviar uma cópia por e-mail para você.
O detector IRmax não será aceito para garantia sem um número de devolução da Crowcon
(CRN). É essencial que a etiqueta com o endereço esteja anexada de forma segura na parte
externa do pacote dos produtos retornados.
A garantia será invalidada se o for descoberto que o produto foi alterado, desmontado ou violado. A
garantia não cobre mau uso ou abuso da unidade.
Aviso de isenção de responsabilidade da garantia
A Crowcon não aceita nenhuma responsabilidade pela perda indireta ou consequencial ou por
danos de qualquer forma provenientes (incluindo quaisquer perdas ou danos provenientes do
uso do produto) e toda a responsabilidade relacionada a quaisquer terceiros está particularmente
excluída.
Esta garantia não cobre a precisão da calibração da unidade ou o acabamento final do produto. A
unidade deve ser mantida de acordo com as instruções de operação e manutenção.
A garantia das peças consumíveis de substituição (como o espelho), fornecidas com a garantia
da substituição de itens defeituosos, será limitada à data de validade da garantia do produto
originalmente fornecido.
A Crowcon se reserva ao direito de determinar um período de garantia inferior, ou declinar um
período de garantia, para qualquer um dos sensores fornecidos utilizados em um ambiente, ou para
um aplicativo, conhecido por produzir riscos de degradação ou danos ao sensor.
A nossa responsabilidade em relação a um equipamento defeituoso será limitada às obrigações
descritas e quaisquer garantias estendidas, condição ou instrução, estatuárias implícitas ou
expressas, ou diferentes das qualidades comerciáveis de nosso equipamento ou de seu
desempenho para qualquer propósito em particular é excluída exceto à medida que proibida pelo
estatuto. Esta garantia não afetará os direitos estatuários do cliente.
Garantia
Português
Brasileiro
221
Detecting Gas Saving Lives
A Crowcon se reserva ao direito de cobrar uma taxa de manuseio e transporte quando descobrir
que unidades retornadas como defeituosas somente necessitavam calibração ou assistência
rotineira, as quais não foram desempenhadas pelo cliente.
No caso de dúvidas a respeito da garantia ou da assistência técnica, entre em contato:
Assistência ao cliente
Tel: +44 (0) 1235 557711
Fax: +44 (0) 1235 557722
UK Office
Crowcon Detection Instruments Ltd
172 Brook Drive,
Milton Park,
Abingdon
Oxfordshire
OX14 4SD
Tel: +44 (0)1235 557700
Fax: +44 (0)1235 557749
Netherlands Office
Crowcon Detection Instruments Ltd
Vlambloem 129
3068JG, Rotterdam
Netherlands
Tel: +31 10 421 1232
Fax: +31 10 421 0542
USA Office
Crowcon Detection Instruments Ltd
1455 Jamike Ave.
Suite 100
Erlanger
KY 41018
Tel: +1 859 957 1039 or
+1 800 527 6926
Fax: +1 859 957 1044
Singapore Office
Crowcon Detection Instruments Ltd
Block 194, Pandan Loop
#06-20 Pantech Industrial Complex
Singapore 128383
Tel: +65 6745 2936
Fax: +65 6745 0467
China Office
Crowcon Detection Instruments Ltd (Beijing)
Unit 316, Area 1, Tower B,
Chuangxin Building,
12 Hongda North Road,
Beijing Economic & Technological
Development Area,
Beijing, China 100176
Tel: +86 10 6787 0335
Fax: +86 10 6787 4879
Web site: www.crowcon.com

Transcripción de documentos

IRmax Infrared hydrocarbon gas detector Installation, operating and maintenance instructions Instructions d’installation, d’utilisation et de maintenance Installations-, Bedienungs- und Wartungsanleitung Instrucciones de instalación, operación y mantenimiento Istruzioni d’installazione, uso e manutenzione Installatie-, bedienings- en onderhoudsinstructies Instrukcje montażu, obsługi i konserwacji Instruções de instalação, funcionamento e manutenção M07028 Issue 6 Oct 2017 Contents Concept and safety....................................................................................... 1 IRmax concept...................................................................................... 1 Safety information................................................................................. 2 Product overview................................................................................... 3 1. Introduction.............................................................................................. 4 1.1 General............................................................................................ 4 1.2 Product description.......................................................................... 4 2. Installation................................................................................................. 6 WARNING.............................................................................................. 6 2.1 Location........................................................................................... 6 2.2 Mounting......................................................................................... 7 2.3 Cabling directly to IRmax ............................................................... 7 2.3.1 Terminal designation............................................................... 8 2.3.2 Installing IRmax using a mounting bracket............................. 8 2.4 Installing using a spigot gland and auxiliary junction box................. 9 2.4.1 To fit IRmax to an auxiliary junction box:.............................. 10 2.5 Cabling requirement...................................................................... 10 2.6 Connections and settings............................................................... 11 3. Operation................................................................................................ 12 3.1 Commissioning procedure.............................................................. 12 3.2 Routine maintenance..................................................................... 13 3.3 Changing gas types....................................................................... 13 3.4 Relative responses of gas types...................................................... 14 4. Specification............................................................................................ 15 5. Accessories and spare parts..................................................................... 16 6. Fault finding........................................................................................... 17 6.1 Errors signalled by LED................................................................... 17 6.2 Analogue Output........................................................................... 17 7. RS485 Modbus configuration.................................................................. 18 7.1 General.......................................................................................... 18 7.2 Wiring topology............................................................................. 19 7.2.1 Star connection..................................................................... 19 7.2.2 Linear bus connection........................................................... 19 7.3 Cabling requirements..................................................................... 20 7.3.1 Calculating the minimum level of power required ................ 20 7.3.2 Sample calculation................................................................ 20 8. Functional Safety Manual........................................................................ 21 8.1 Introduction................................................................................... 21 8.2 IRmax and IRmax Modbus Safety Function..................................... 21 8.3 Functional Safety Data................................................................... 21 8.4 Hardware Configuration................................................................ 22 8.5 Software Configuration.................................................................. 22 8.6 Systematic Failures......................................................................... 22 8.7 Diagnostic Interval.......................................................................... 22 8.8 Constraints.................................................................................... 22 8.9 Environmental................................................................................ 23 8.10 Hardware fault tolerance............................................................. 23 8.11 Systematic Capability................................................................... 23 8.12 Classification................................................................................ 23 Warranty..................................................................................................... 24 IRmax concept IRmax is an ultra-compact infrared (IR) gas detector, which delivers rapid, fail-safe detection of hydrocarbon gases and vapours. Featuring dual-wavelength IR sensor technology in a rugged 316 stainless steel package, IRmax is designed to operate in the harshest conditions. Unlike conventional IR gas detectors, IRmax does not incorporate heaters to prevent condensation on windows and mirrors. The Stay clIR coating on optical components prevents condensation forming while the detector is operating. IRmax is compatible with any 4-20mA control system, and can also be installed in an RS485 Modbus addressable network (see Section 7). IRmax requires only 1 Watt of power, typically 75-90% lower than conventional IR gas detectors. IRmax features a compact diffusion gas chamber, which in combination with an effective weatherproof cap provides excellent speed of response. The weatherproof cap has been designed using flow modelling software to enable remote gassing and calibration of the IRmax without requiring a special calibration cap. The IR Display makes it possible to monitor readings from the IRmax both locally and remotely. An IR Display can be fitted directly to IRmax. Alternatively, IRmax may be supplied with an Intrinsically Safe (IS) Barrier module attached. An IR Display can then be connected to the IS Barrier Module via temporary or permanent cabling. The available options are illustrated on Diagram 3, page 5. For further information about other accessories for the IRmax see Diagram 3 on page 5 and Section 5, page 16. Detecting Gas Saving Lives 1 English Concept and safety Concept and safety English Safety information • IRmax gas detectors must be installed, operated and maintained in strict accordance with these instructions, warnings, label information, and within the limitations stated. • The rear nut on IRmax must be kept tightly closed during operation. Do not attempt to remove the rear nut until power to the detector is isolated - otherwise ignition of a flammable atmosphere can occur. Before removing the nut for maintenance, calibration or servicing, check that the surrounding atmosphere is free of flammable gases or vapours. Do not open until several minutes after the power has been removed. • Maintenance and calibration operations must only be performed by qualified service personnel. • Only genuine Crowcon replacement parts must be used; substitute components may invalidate the certification and warranty of the IRmax. • IRmax must be protected from extreme vibration, and direct sunlight in hot environments as this may cause the temperature of the IRmax to rise above its specified limits and cause premature failure. • IRmax will not detect hydrogen, ammonia or carbon dioxide. • The equipment must be earthed using the cable gland and steel armoured cable. • Certification for Zone 21/22 dust environments: IRmax basic (without IR Display or IS Barrier module) may be used in environments that may contain hazardous dusts (Zones 21 or 22). • IRmax with an IS Barrier module may be used in Zones 21 or 22 provided the ambient temperature remains below 40°C and a remote IR Display or Hand-Held IR Displays are installed/used outside the hazardous area only. • IRmax with a Fixed IR Display cannot be installed in a Zone 21 or 22 area. 2 Detecting Gas Saving Lives Product overview IRmax is an infrared gas detector designed for detecting common hydrocarbon gases in the range 0 to 100%LEL (Lower Explosive Limit: the minimum concentration in air at which ignition can occur). IRmax is a certified Flameproof (Exd) detector suitable for use in ATEX Zone 1 or Zone 2 hazardous areas. Please refer to the certification label on the side of the Detector to identify the type of certification that relates to the product supplied. Note: if no certification label is fitted to the IRmax, the detector is not certified for use in hazardous areas. IR GAS DE TECTOR 1180 IR GAS DETECTOR WITH REMOTE DISPLAY II 2 GD 1180 V m ax= 32V W m ax= 5W II 2GD Vmax=32V Wmax=5W B a s e e fa 0 9 A T E X 0 2 0 6 X IE C E x B A S 0 9 . 0 1 0 9 X S IL 2 S i r a 1 2 A T E X 1 2 0 6 X Baseefa09ATEX0220X IECEx BAS 09.0104X Ex db ia IIC T4 Gb (-40°C ≤ Ta ≤ +75°C) Ex tb ia IIIC T135°C Db (-40°C ≤ Ta ≤ +40°C) E x d b II C T 4 Gb (T am b = -40 °C to + 75 °C ) E x d b II C T 6 Gb (T am b = -40 °C to + 50 °C ) E x tb II IC T 135° C D b (-4 0° C T a + 75° C ) WARNING: DO NOT OPEN WHEN EXPLOSIVE ATMOSPHERE MAY BE PRESENT. W A R N IN G : D O N O T O P E N W H E N E X P L O S IV E A TM O S P H E R E M A Y B E P R E S E N T. A b i n g d o n , U nit e d K in g d o m , O X 1 4 4 S D Abingdon, United Kingdom, OX14 4SD IRmax Basic certification label IRmax with IS Barrier certification label IR GAS DETECTOR WITH DISPLAY II 2G 1180 Baseefa09ATEX0220X IECEx BAS 09.0104X Vmax=32V Wmax=5W Ex db ia IIC T4 Gb (-40°C Ta +75°C) WARNING: DO NOT OPEN WHEN EXPLOSIVE ATMOSPHERE MAY BE PRESENT. Abingdon, United Kingdom, OX14 4SD IRmax with Fixed IR Display certification label Diagram 1: IRmax certification labels Detecting Gas Saving Lives 3 English Concept and safety 1. Introduction The configuration of each IRmax is identified by a label fitted on the main body. Please quote the product name, part number and serial number when contacting Crowcon for advice or spares. 1.2 Product description IRmax consists of a main body of 316 stainless steel, an antistatic weatherproof cover over the optics and gas measurement chamber and an electronics assembly. An IR Display Module can also be fitted. Instructions for fitting the IR Display appear in the IR Display manual (M07061). An optional connection spigot gland can be supplied to allow IRmax to be fitted directly to auxiliary junction boxes with either M20 or ½” NPT cable entries. Optional spigot gland M20 or 1/2" NPT cable gland 74.5 74.5 136 136 Overall English 1.1 General 57 Overall 60.5 158 Overall 157.5 External grounding terminal (earth) All dimensions in millimetres Diagram 2: IRmax dimensioned view Note: The IRmax body is supplied with two cable entries; one is M20, one is 1/2" NPT. The cable entry not specified when ordering an IRmax will be sealed using a certified plug. The IRmax must be installed with both cable entries sealed: one with a cable gland, the other with a certified IP66 rated stopping plug. 4 Detecting Gas Saving Lives 15 12 14 13 11 “ 10  ‘ ”  ‘ Ž    Œ Diagram 3: IRmax exploded view (part numbers shown where applicable) Œ Calibration cap M041007  Weatherproof cap M04995 Ž Mirror retainer Supplied together as ‘mirror replacement kit’ C011206  Mirror  Flow adaptor S012996 ‘ O-ring for back-nut, IS Barrier Module or Fixed IR Display Module: M040077  Mounting bracket as complete assembly S012130 “ Spigot gland M20 or 1/2"NPT versions : M20 ATEX: S012147, 1/2" NPT ATEX: S012190 ” Retaining plate and bolts for rear plug, Fixed IR Display and IS Barrier module } 10 11 12 13 14 15 IR Display fixed version IR Display to IRmax connector E07987 IS Barrier Module IR Display connecting lead Remote IR Display mounting bracket M03833 Remote IR Display Detecting Gas Saving Lives 5 English 1. Introduction 2. Installation English WARNING • This detector is designed for use in Zone 1 and Zone 2 hazardous areas. Certification is dependent upon the accessories fitted and ambient operating temperature. Please refer to the specifications table on page 15 for certification details. Installation must be in accordance with the recognised standards of the appropriate authority in the country concerned. • For further information please contact Crowcon. Prior to carrying out any installation work ensure local regulations and site procedures are followed. • The equipment must be earthed using the cable gland and steel armoured cable. • Do not attempt to fit an IR Display to an IRmax not supplied for the purpose. Detectors supplied for use with a display are certified Exd ia, and must be operated either with a Fixed Display containing an IS barrier, or with a Remote IR Display or IS Hand-Held Calibrator connected via a Crowcon IS Barrier module. • Detectors supplied without a display are certified Exd IIC and cannot be retrofitted for use with an IR Display. 2.1 Location The IRmax should be mounted where the gas to be detected is most likely to be present. The following points should be noted when locating gas detectors: • To detect gases which are lighter than air, such as methane, detectors should be mounted at high level. To detect heavier-than-air gases, such as flammable vapours, detectors should be mounted at low level. • When locating detectors consider the possible damage caused by natural events e.g. rain or flooding. For detectors mounted outdoors in very hot regions Crowcon recommend the use of a sunshade (see Section 5, Accessories and spare parts, on page 16). • Consider ease of access for functional testing and servicing. • Consider how the escaping gas may behave due to natural or forced air currents. Mount IRmax in ventilation ducts if appropriate (see Section 5, Accessories and spare parts, on page 16). • Consider the process conditions. For example, butane is normally heavier than air, but if released from a process which is at an elevated temperature and/or pressure, the gas may rise rather than fall. The placement of sensors should be determined following advice of experts having specialist knowledge of gas dispersion and the plant processing equipment as well as safety and engineering issues. The agreement reached on the locations of sensors should be recorded. 6 Detecting Gas Saving Lives 2.2 Mounting IRmax can be mounted in three ways: 1. Using the Crowcon mounting bracket with direct field cable connection (4-20mA operation only). 2. Using a spigot gland to connect to an existing Exe or Exd certified junction box. Crowcon supplies a suitable spigot gland as an optional extra (see 3 below). 3. Using the optional Crowcon auxiliary junction box and spigot gland. Optional parts are listed in Section 5 on page 16. IRmax should be installed at the designated location with the sensor barrel horizontal +/- 15° (orientation shown on Diagram 2 on page 4). This ensures that dust or water will not collect on the optical components. 2.3 Cabling directly to IRmax This option is suitable for 4-20mA operation only. A Crowcon mounting bracket is required to retain the detector to a wall or 2” (50 mm) pipe. Status LED Signal 0V (ground) +V (24V IRmax) Diagram 4: Field cable connections on the IRmax Connect field cables using a certified gland via the chosen cable entry on the IRmax body (M20 or 1/2" NPT), as indicated in Diagram 4. Crowcon recommends cable glands are installed pointing downwards. Ensure that cable glands with the appropriate Exd certification are used, and that the thread length does not exceed the length specified in the diagram (left). 15mm MAX Detecting Gas Saving Lives 7 English 2. Installation 2. Installation 2.3.1 Terminal designation English With the IRmax oriented as shown in Diagram 2 on page 4 (M20 cable entry at the top), the 3-core field cable should be terminated using the removable connector as follows: +24V at the bottom, 0V in the middle, Signal at the top. The 6-pin connector on the right of the PCB is for servicing and/or connection of an IR Display module +ve terminal: +ve supply from the control card. Sig terminal: Signal/Sense from control card. 0 V terminal: -ve supply from the control card. 2.3.2 Installing IRmax using a mounting bracket a. IRmax can be supplied with a mounting bracket (S012130) rather than a spigot gland so that it can be directly connected to field cables (see Diagram 5). Mounting bracket: 70mm between fixing centres. Use M6 bolts Diagram 5: IRmax with a mounting bracket and cable gland b. If the IRmax is to be mounted on a flat surface, mark and drill two holes using the mounting bracket as a template. Loosely fix two parts of the bracket using fixings suitable for the wall/surface. c. Remove the weatherproof cap from the IRmax, and slide the body of the IRmax through the bracket. It is recommended that the IRmax body is installed with the cable entry facing downwards. 8 Detecting Gas Saving Lives d. Secure the two bracket fixings so that the IRmax is held firmly in place. Re-fit the weatherproof cap. e. Once the IRmax is securely fixed in place, remove the IRmax rear nut to enable access to the cable terminals. f. Prepare the field cable – Crowcon recommends 1.5 mm2 Steel Wire Armoured (SWA) cable. Other cable types may be used provided they are compatible with Exd certified glands. Fit a suitably certified Exd cable gland, pass the cable conductors through the body of the IRmax and screw in the cable gland. Secure the gland and ensure the cable armour is grounded to the cable gland and the IRmax body. NB. Don’t forget to re-fit the rear nut after installing the cable. g. The retaining plate (item 9 on Diagram 3, page 5) must be securely fitted to prevent any risk of the rear nut (or Fixed IR Display or IS Barrier module accessory) vibrating loose. 2.4 Installing using a spigot gland and auxiliary junction box This option is required where IRmax is to be connected to an existing Exd or Exe certified auxiliary junction box. Diagram 6: IRmax connected to the auxiliary junction box Detecting Gas Saving Lives 9 English 2. Installation 2. Installation 2.4.1 To fit IRmax to an auxiliary junction box: English a. Carefully remove the outer section of the spigot gland (item 8 in Diagram 3 on page 5). b. Screw the narrow end of the spigot gland into the auxiliary junction box. c. Raise the IRmax to the auxiliary junction box and pass the wires through the assembly and into the auxiliary junction box. Secure the IRmax by screwing the collar tightly to the cable gland. Tighten grub screw. d. The main body of the IRmax can be swivelled horizontally at any angle, provided it is mechanically secure, does not interfere with other equipment and is accessible for maintenance. e. Refer to Section 2.6 for instructions on wiring. See also Diagram 4 on page 7. 2.5 Cabling requirement Cabling to IRmax must be in accordance with the recognised standards of the appropriate authority in the country concerned and meet the electrical requirements of the IRmax. Crowcon recommends the use of steel wire armoured (SWA) cable and suitable explosion proof glands must be used. Alternative cabling techniques, such as steel conduit, may be acceptable provided appropriate standards are met. The maximum recommended cable length is 3.4 km (see Table 1). IRmax requires a dc supply of 12-30Vdc. Ensure there is a minimum of 12V at the IRmax from the control panel, taking into account the voltage drop due to cable resistance at a peak current of 0.1A. A 1.5mm2 cable will typically allow cable runs up to 3.0km. Table 1 below shows the maximum cable distances for typical cable parameters. C.S.A. Resistance Max. Distance >20 V Max. Distance 18 to 20 V mm2 (Ohms per km) (km) (km) 1.0 18.4 2.2 1.6 1.5 13.0 3.0 2.3 2.5 11.5 3.4 2.6 Table 1: Maximum cable distances for typical cables 10 Detecting Gas Saving Lives 2.6 Connections and settings All connections described are with reference to the terminal block mounted within IRmax connector main body. The terminals on the IRmax connector PCB are marked ‘+’, ‘sig’ and ‘0 V’. Correct polarity should be observed when connecting the IRmax to control equipment. IRmax is factory set as a ‘current sink’ device unless otherwise specified when ordering. To reset to ‘current source’, remove the back nut and move the two links on the terminal PCB from the ‘sink position to the ‘source’ position, as shown in Diagram 7. Note: The external grounding terminal is only to be used where local authorities permit or require such a connection. Where possible, to limit radio frequency interference, the auxiliary junction box and cable armour should be grounded at the control panel (safe area) only to avoid earth loops. +V 0V Sg 1 2 3 CONTROLLER Sink setting Jumper settings EARTH Wiring Number Colour Function 1 2 3 Red +V Black 0V Green Signal PC communications kit connector Source setting IR Display connector Status LED Diagram 7: Sink/source jumper location The 4-20mA signal can be set to current 'Sink' or 'Source' using the pins and jumper link shown in Diagram 7. Set to current 'Sink' by fitting the jumper link to pins 3 and 4 as shown on the left-hand photograph. Set to current 'Source' by fitting the jumper link to pins 1 and 2 as shown on the right-hand photograph. IRmax will be set to current 'Sink' unless specified otherwise when ordering. LED indication: an LED is fitted to the terminal PCB to indicate the current operating status. Refer to Section 6 on page 17 for more information. Detecting Gas Saving Lives 11 English 2. Installation 3. Operation English WARNING Prior to carrying out any work ensure local regulations and site procedures are followed. Never attempt to open the IRmax or auxiliary junction box when flammable gas is present. Ensure that the associated control panel is inhibited so as to prevent false alarms. 3.1 Commissioning procedure 1. Check that: a. The cable connections are correct b. The supply voltage is set at the control card as 18 to 30 V. The voltage measured at the IRmax terminals (within the Exe auxiliary junction box if used, or at the IRmax terminal PCB) and must be set between 12 and 30 V. c. The links are set for 4-20 mA sink or source as appropriate to control card. 2. Once powered up leave IRmax for 30 minutes before attempting zero/cal. This delay is to ensure thermal stability. (Note: IRmax will be fully operational from 30 seconds after power is applied.) 3. Ensure clean air (i.e. no hydrocarbon gas) before zeroing. Zero reading at control card (refer to control card instructions). 4. Fit a calibration cap over weatherproof cover to isolate measurement chamber from ambient air. Such a cap is available from Crowcon (M041007). Connect calibration gas (50% LEL nom) and apply at 1 litre-per-minute flow. 5. After 30 seconds adjust cal/span on control card so that display reads 50% LEL, or matches concentration of calibration gas applied. The IRmax itself should not require calibration. 6. Remove gas and calibration cap. Re-check zero. 7. At installation, or after the mirror has been changed, the IRmax can be zeroed and calibrated either using an IR Display accessory (see page 1) or via a PC communications kit (see the IRmax Accessories manual). Note: ATEX Certified IRmax will be supplied calibrated for compliance with EN61779 (where, for example 100% LEL Methane = 4.4% volume). Note: It is recommended that the calibration cap is used for initial commissioning. Subsequent calibrations may be conducted by applying gas to the weatherproof cap remotely via the pipe spigot (thus avoiding the need to directly access the IRmax). Calibration without the calibration cap (i.e. directly via the weatherproof cap) can be performed provided local windspeed is below 2 metres/second. The flow rate of the gas must be greater than 2.0 litre/minute. 12 Detecting Gas Saving Lives 3.2 Routine maintenance Site practices will dictate the frequency with which detectors are tested. Crowcon recommends that IRmax is gas tested at least every 6 months and re-calibrated as necessary. To re-calibrate an IRmax follow the steps given in Section 3.1. In the event of an electronic failure please consult your local Crowcon representative. Calibration interval: Crowcon recommend calibration every 12 months. Remote calibration via pipe: Wind speed should be less than 2.0 metres per second. If greater, use the calibration cap to prevent gas dilution. Cleaning of optics: Is not recommended unless the IRmax is in obscuration fault. If the window or mirror become contaminated, clean carefully with the IPA impregnated wipes and/or the soft cloth supplied in the mirror cleaning kit (see Section 5, Accessories and spare parts on page 16). Mirrors:  If the mirror is damaged, obtain a mirror replacement kit (see Section 5, Accessories and spare parts on page 16). The IRmax must always be re-zeroed and re-calibrated after mirror replacement.  If condensation starts to cause faults replace mirror (optical coating may be damaged). Crowcon recommends replacing mirror every 5 years. 3.3 Changing gas types Each IRmax is supplied pre-calibrated for a particular type of gas (for example methane or propane). If re-calibration for a different gas type is required, the IRmax can be re-configured using the PC communications kit (see Section 5, Accessories and spare parts on page 16), and then calibrated. Detecting Gas Saving Lives 13 English 3. Operation 3. Operation English 3.4 Relative responses of gas types The graph below shows the relative responses to other gas types for an IRmax calibrated on methane. Note: many hydrocarbon gases and vapours are more easily detected by IR detectors than methane. The response of IRmax (and other IR gas detectors) will be linear across the 0-100%LEL range for the target gas (ie methane in this example), but non-linear for other hydrocarbons that may also be present. Diagram 8 The diagram shows the approximate response of the gases mentioned above: from left to right, butane, propane, pentane, hexane & petrol vapour and methane. Other gas types and ranges are available. Please contact Crowcon for further details. 14 Detecting Gas Saving Lives Enclosure material 316 Stainless Steel Dimensions (Detector only) 158mm x 75mm x 57mm (6.2 x 2.9 x 2.3 ins) (without spigot) Weight IRmax 1.58kg (3.5lbs) IRmax with Fixed IR Display 2kg (4.4lbs) IRmax with IS Barrier Module 2.4kg (5.3lbs) Remote IR Display 0.2kg (0.4lbs) Operating voltage 12Vdc to 30V dc Power <1W Output 3-wire 4-20 mA (Sink or Source) Fault signal <1 mA Maximum cable loop resistance 80 Ohms (relative to –ve terminal) Operating temperature -40°C to +75°C (-40°F to +167°F) Humidity 0–100% Relative Humidity Degree of protection IP66 Explosion protection Flameproof Approval code ATEX IRmax (without IR Display) II 2 GD Exd db IIC T6 Gb (Tamb = -40°C to +50°C) II 2 GD Exd db IIC T4 Gb (Tamb = -40°C to +75°C) II 2 GD Ex tb IIIC T135°C Db (-40°C ≤ Ta≤ +75°C) IRmax with IS Barrier module (remote display) II 2 GD Exd db ia IIC T4 Gb (Tamb = -40°C to +75°C) Ex tb ia IIIC T135°C Db (Tamb = -40°C to +40°C) IRmax (with Fixed IR Display) II 2 G Exd db ia IIC T4 Gb (Tamb = -40°C to +75°C) Safety certificate no. ATEX and IECEx IRmax (without IR Display): Baseefa 09ATEX0206X and IECEx BAS.09.0109X IRmax (with IR Display): Baseefa 09ATEX0220X and IECEx BAS.09.0104X Functional Safety Certified for use in a SIL 2 system. Certificate number: Sira 12ATEX1206X Standards EN 60079-0:2012+A11:2013, EN 60079-1:2014, EN 60079-31:2014 IEC 60079-0:2011, IEC 60079-1:2014, IEC 60079-31:2013 EN 60079-29-1:2007, IEC 61508:2010, EN50402:2005 Zones Certified for use in Zone 1 or Zone 2 EMC EN50270 Detecting Gas Saving Lives 15 English 4. Specification 5. Accessories and spare parts English Part Numbers Name Description M041007 Calibration cap Fits over the standard weathercap to enable calibration where local air speed exceeds 2 metres per second. S012130 Mounting bracket kit Enables mounting to a wall or 2" (50 mm) pipe. Not required if IRmax is being fitted to an existing auxiliary junction box. S012152 Sun shade/Collector cone Can be fitted to IRmax to protect against elevated temperatures due to direct sunlight and/or to extend the detectors footprint for detecting lighter than air gases (e.g. methane). S012169 Duct mounting kit Enables monitoring of ducts from 300 mm to 3000 mm, and air-flow between 2 m/s and 20 m/s. S012996 Flow adaptor For gas sampling applications. S012827 PC communications kit Communications module, software and lead to enable configuration of the detector. M20: S012295 ½” NPT: S012296 Auxiliary junction box Mounting option for IRmax for use in hazardous environments. C011210 Mirror cleaning kit Contains IPA impregnated wipes and microfibre cloth IRmax Spares Refer to Diagram 3 on page 5 for details of spare parts. 16 Detecting Gas Saving Lives 6.1 Errors signalled by LED The LED fitted to the terminal PCB can help identify faults. Its position is shown on Diagram 7 on page 11. The table below shows how to interpret what is wrong for each pattern of flashes. LED Pattern Detector Status Regular flash each second. Healthy. Action On with short blips off. Detector in startup mode. Wait 10 seconds. Fast flash on and off or irregular flash pattern. Supply voltage too low or too high. Ensure the IRmax supply voltage is correctly set. Ensure measurement is made directly at the detector terminals. Permanently on. Fault, host or i-module error. Power-cycle the IRmax, if fault persists, return to Crowcon. Two long flashes followed by a short flash. Fatal error; lamp or detector fault. Return to Crowcon. Fast double flash each second. Fatal error, module or configuration fault. Check the detector configuration using PC communications kit software. Check power supply. If fault persists, return to Crowcon. Short blip each second. Optics obscured. Check window and mirror, clean if necessary. Re-zero IRmax and check calibration. Any other faults can only be rectified by returning the IRmax to Crowcon or authorised service agent. 6.2 Analogue Output IRmax will remain in Fault state and “Service required” will also be shown on the IR Display (if fitted) if the analogue output signal has failed or is not connected to a control system or load resistor. IRmax actively monitors the 4-20mA analogue output signal to verify it is in range. If the signal is out of range the detector will go into fault and the output will be set to 1mA. Thus, when testing a detector it is essential that it is either connected to a control panel or a 100Ω load resistor is connected between the ‘0V’ and ‘Sig’ terminals (detector set to ‘Source’ mode) or between the ‘0V’ and ‘+V’ terminals (detector set to ‘Sink’ mode). Detecting Gas Saving Lives 17 English 6. Fault finding 7. RS485 Modbus configuration English 7.1 General This section explains how to use IRmax detectors in a Modbus configuration. An RS485 enabled version is available for such applications. Up to 32 IRmax detectors can be linked in star or bus configurations as described below. Connections to the RS485 version of the IRmax must be made via a spigot gland to an auxiliary junction box (see Section 5 on page 16), rather than by cabling directly into the detector. Please note that the IR Display cannot be used with RS485 enabled IRmax. The RS485 enabled version of the IRmax has five field terminals . The terminals are: 1 Positive supply 12 V to 30 V above 0 V 2 0V Return and RS485 reference 3 4-20 mA signal Source or Sink signal (optional) 4 RS485 B RS485 differential signal 5 RS485 A RS485 differential signal The signals on the RS485 terminals conform to the EIA/TIA-485 standard, which means that the common mode range is -7V to +12V with respect to the 0V terminal. Note that not all RS485 manufacturers agree on the polarity of the A and B signals. If the wiring does not work one way, users should switch the RS485 A&B wires. There is no risk in making the wrong connection. The communication settings are 9600 bps, two stop bits and no parity. When compiling an interface for a control system, it is important to consider the amount of time it takes for the system to collect information from each detector in turn. The fastest speed at which multiple detectors can be polled is 14 detectors per second; practical conditions may reduce this to 7 per second. Users must ensure that the arrangement allows alarm signals to be registered within acceptable time limits. It is also important to ensure that the system can supply enough power to keep all the detectors working. To calculate the amount of power required in a linear bus connection, see Section 7.3, Cabling requirements, on page 20. For full Modbus instructions, contact Crowcon (see addresses on back cover). 18 Detecting Gas Saving Lives 7.2 Wiring topology The two common wiring topologies in use are the star connection and the linear bus. 7.2.1 Star connection In a star-connected topology all detectors are wired to a central point, which is usually the control panel. No cables are required to have more than 5 cores as all the 4-20mA signal connections are taken directly to the control panel. The RS485 A and B signals can then all be connected together at the star point. The bus should then be terminated at the star point with a single 110 ohm termination resistor. The length of each arm of the star may not exceed 750 metres. 7.2.2 Linear bus connection In a bus-connected topology all IRmax are wired to a linear arrangement, usually with the control panel at one end. A classic situation is a tunnel installation, with IRmax installed at regular intervals (see Diagram 9 below). To wire the installation, two 110 ohm-terminating resistors should be fitted: one at each physical end of the bus. As the 4-20mA signals cannot be shared, an additional conductor is required on each wiring hop. If none of the 4-20mA signals are being used, then only four conductors are required. Diagram 9 Detecting Gas Saving Lives 19 English 7. RS485 Modbus configuration 7. RS485 Modbus configuration English 7.3 Cabling requirements 7.3.1 Calculating the minimum level of power required The more IRmax detectors connected to the linear bus, the greater the power required to run the system. To calculate the power required for a particular setup, it is necessary to know the cable resistance between each pair of IRmax detectors. A current of at least 0.1mA must be allowed for each ‘hop’ between IRmax. The voltage to be applied can be calculated by estimating the voltage drop across each ‘hop’ – at the end at least 12V must remain to ensure that the last IRmax functions correctly. Contact Crowcon for advice in specific cases. Alternatively, follow the steps outlined below and the sample calculation shown in the next section. 1. The voltage must not fall below 12V, so start the calculation by setting the voltage at the last IRmax in the line at that value. 2. Each IRmax may draw up to 0.1 A. Calculate the cable voltage loss of the first ‘hop’ between detectors by taking the ‘aggregate current’ to be 0.1A, and multiply this by the cable resistance of the ‘hop’ between the last and the last but one IRmax. 3. Add this voltage drop to the initial 12V to get the lowest acceptable voltage at the last but one IRmax. Add 0.1A to the value for the ‘aggregate current’ to get to 0.2mA, the minimum current running through the last but one ‘hop’ of the bus. Multiply this by the cable resistance for the last but one ‘hop’ to get the next voltage drop. 4. Repeat this process for each IRmax, accumulating the voltage losses that will occur between each IRmax. 5. The maximum detector voltage of 30V must not be exceeded. 7.3.2 Sample calculation As an example, here are the results of the calculation for six IRmax detectors spaced equally 250 m apart on cable with cross-sectional area of 1mm2. Each hop has a resistance of 4.6 ohms. Station Supply voltage Supply current 1 12 0.1 A 2 12.46 0.2 A 3 13.38 0.3 A 4 14.76 0.4 A 5 16.6 0.5 A 6 18.9 0.6 A Panel supply 21.66 0.6 A 20 Detecting Gas Saving Lives 8.1 Introduction The following sections provide detail on the certification of IRmax in accordance with the IEC 61508 and EN 50402 Functional Safety standards. Information is given on the features considered in the safety case, maintenance requirements and data to enable IRmax to be integrated into Safety Instrumented System (SIS). 8.2 IRmax and IRmax Modbus Safety Function To measure the concentration of flammable gas and indicate the measurement by means of a 4-20mA output. Failures in respect of the safety function will be detected by the hardware and associated firmware. They will be revealed as an output signal of less than 3.6mA or more than 21mA. 8.3 Functional Safety Data Parameter name Symbol Equation / source Proof Test Interval T1 As defined by Crowcon. Mean Time To Repair MTTR As defined by Crowcon. IRmax 8,760 hours (annual) 8 hours Type A/B As defined by Crowcon. Type B Total failures: Type A λ From FMEDA 1.04E-05 Safe diagnosed failures: λSD From FMEDA 1.95E-08 Safe undiagnosed failures: λSU From FMEDA 8.59E-08 Dangerous diagnosed failures: λDD From FMEDA 9.74E-06 Dangerous undiagnosed failures: λDU From FMEDA 5.06E-07 Safe no-effect failures: λNE From FMEDA 3.21E-09 Diagnostic coverage: DC λDD / (λDU + λDD) 95.06% Safe Failure Fraction: SFF 95.11% Channel equivalent down time tCE (λSD + λSU + λDD) / λ (λDU / λD)(T/2 + MTTR) + (λDD / λD ) MTTR 2.24E+02 PFDAVG (using 61508-6 PFDAVG (λDU + λDD) tCE 2.30E-03 equation) PFDAVG (using simplified PFDAVG λDU (T / 2+MTTR) + (λDD MTTR) 2.30E-03 equation) PFDAVG (using IEC 61508-6 PFDAVG 1-ε-(λdd+λdu) tce 2.30E-03 equation) SIL capability (Low demand SIL2 mode) SIL capability (High demand SIL2 mode) For low demand applications, in respect of random hardware failures and safe failure fraction, all variants of the system are suitable for use in SIL 2 applications. Detecting Gas Saving Lives 21 English 8. Functional Safety Manual Functional Safety Manual English 8.4 Hardware Configuration Route 1H (Hardware fault tolerance and Safe Failure Fraction) has been used to assess hardware safety integrity level. 8.5 Software Configuration Assessment of the Product firmware has been made to the requirements given in IEC 61508:3 2010. 8.6 Systematic Failures Route 1S (as specified in IEC 61508:2 2010 paragraph 7.4.2.2c) is used for compliance with the requirements of avoidance of systematic failures. 8.7 Diagnostic Interval Most diagnostic functions are continuously monitored. Tests of the system watchdog are to be accomplished during the annual proof test by power cycling the instrument: IRmax must be power-cycled annually (ie have the 24Vdc supply removed and re-applied) as part of the maintenance programme for the product (refer also to section 3.2). 8.8 Constraints Failure rates are constant. A proof test conducted at least once a year will identify all un-revealed failures. Repairs have a mean time to repair of 8 hours. It is assumed that the user makes use of that diagnostic facility provided via the IR Display accessory and/or PC interface in order to minimise potential product down time. Reliability assessment is a statistical process for applying historical failure data to proposed designs and configurations. It therefore provides a credible target/estimate of the likely reliability of equipment assuming manufacturing, design and operating conditions identical to those under which the data was collected. It is a valuable design review technique for comparing alternative designs, establishing order of magnitude performance targets and evaluating the potential effects of design changes. The actual predicted values cannot, however, be guaranteed as forecasting the precise number of field failures which will actually occur, since this depends on many factors outside the control of a predictive exercise. Failure rates (symbol λ), for the purpose of this prediction, are assumed to be constant with time. Both early and wear-out related failures would decrease the reliability but are assumed to be removed by burn in and preventive replacement respectively. 22 Detecting Gas Saving Lives The Probability of failure on demand is the likelihood that the system will be in a failed state at a random moment. This is synonymous with the steady state unavailability which is given by: Unavailability = (λ x MDT)/(1 + (λ x MDT)) which approximates to, λ x MDT for small values of λ x MDT where λ is the failure rate and MDT is the Mean Down Time. This is consistent with the expression for Availability given as: MTBF/(MTBF+MDT) The failure rates used, and thus the derived availabilities are those credibly associated with a well proven design after a suitable period of reliability growth. 8.9 Environmental Environmental constraints: The product shall be operated over a maximum ambient temperature range of -40°C to +75 °C. The product shall be stored over a maximum ambient temperature range of -40°C to +80 °C. The product shall be operated over a maximum ambient Relative Humidity range of 0% to +100 % Condensing. The product has an Ingress Protection rating of IP66 according to the definitions within standard EN60529. The product is designed for continuous operation. 8.10 Hardware fault tolerance The HFT is 0. 8.11 Systematic Capability The IREX/IRmax is of Class SC2. 8.12 Classification The IREX/IRmax is a type B component. Detecting Gas Saving Lives 23 English Functional Safety Manual Warranty English This equipment leaves our factory fully tested and calibrated. If within the warranty period of three years from despatch, the equipment is proved to be defective by reason of faulty workmanship or material, we undertake at our option either to repair or replace it free of charge, subject to the conditions below. Warranty Procedure To facilitate efficient processing of any claim, contact our customer support team on +44 (0)1235 557711 with the following information: Your contact name, phone number, fax number and email address. Description and quantity of goods being returned, including any accessories. Instrument serial number(s). Reason for return. Obtain a Returns form for identification and traceability purposes. This form may be downloaded from our website ‘crowconsupport.com’, along with a returns label. Alternatively we can ‘email’ you a copy. IRmax will not be accepted for warranty without a Crowcon Returns Number (CRN). It is essential that the address label is securely attached to the outer packaging of the returned goods. The guarantee will be rendered invalid if the instrument is found to have been altered, modified, dismantled, or tampered with. The warranty does not cover misuse or abuse of the unit. Warranty Disclaimer Crowcon accept no liability for consequential or indirect loss or damage howsoever arising (including any loss or damage arising out of the use of the instrument) and all liability in respect of any third party is expressly excluded. This warranty does not cover the accuracy of the calibration of the unit or the cosmetic finish of the product. The unit must be maintained in accordance with the instructions in this manual. The warranty on replacement consumable items (such as the mirror) supplied under warranty to replace faulty items, will be limited to the unexpired warranty of the original supplied item. Crowcon reserves the right to determine a reduced warranty period, or decline a warranty period for any sensor supplied for use in an environment or for an application known to carry risk of degradation or damage to the sensor. Our liability in respect of defective equipment shall be limited to the obligations set out in the guarantee and any extended warranty, condition or statement, express or implied statutory or otherwise as to the merchantable quality of our equipment or its fitness for any particular purpose is excluded except as prohibited by statute. This guarantee shall not affect a customer’s statutory rights. 24 Detecting Gas Saving Lives Crowcon reserves the right to apply a handling and carriage charge whereby units returned as faulty, are found to require only normal calibration or servicing, which the customer then declines to proceed with. For warranty and technical support enquiries please contact: Customer Support Tel: +44 (0) 1235 557711 Fax: +44 (0) 1235 557722 Email: [email protected] Detecting Gas Saving Lives 25 English Warranty TABLE DES MATIÈRES Concept et sécurité..................................................................................... 29 Concept détecteur IRmax ............................................................................ 29 Informations de sécurité................................................................................ 30 Présentation du produit................................................................................ 31 1. Introduction............................................................................................ 32 1.1 Générales................................................................................................ 32 2. Installation............................................................................................... 34 2.1 Implantation........................................................................................... 34 2.2 Montage................................................................................................. 35 2.3 Câblage direct vers le détecteur IRmax ................................................. 35 2.3.1 Désignation de bornes................................................................... 36 2.3.2 Installation du détecteur IRmax à l’aide d’un support de fixation..... 36 2.4 Installation au moyen d’un presse-étoupes à ergot et d’un boîtier de jonction auxiliaire ......................................................................................... 37 2.4.1 Pour poser le détecteur IRmax sur un boîtier de jonction auxiliaire :....38 2.5 Exigences de câblage.............................................................................. 38 2.6 Raccordements et paramètres................................................................. 39 3. Fonctionnement...................................................................................... 40 3.1 3.2 3.3 3.4 Procédure de mise en service.................................................................. 40 Maintenance programmée...................................................................... 41 Changement de types de gaz................................................................. 41 Réponses relatives des types de gaz........................................................ 42 4. Spécifications.......................................................................................... 43 5. Accessoires et pièces de rechange .......................................................... 44 6. Dépannage du détecteur........................................................................ 45 6.1 Erreurs signalées par DEL........................................................................ 45 6.2 Sortie analogique.................................................................................... 45 7. Configuration du Modbus RS485............................................................ 46 7.1 Générales................................................................................................ 46 7.2 Topologie du câblage.............................................................................. 47 7.2.1 Connexion à étoiles....................................................................... 47 7.2.2 Connexion de bus linéaire............................................................. 47 7.3 Exigences de câblage.............................................................................. 48 7.3.1 Calcul du niveau minimum d’alimentation requise ........................ 48 7.3.2 Exemple de calcul.......................................................................... 48 8. Manuel de sécurité fonctionnelle............................................................. 49 8.1 Introduction............................................................................................ 49 8.2 Fonction de sécurité IRmax et IRmax Modbus......................................... 49 8.3 Informations relatives à la sécurité fonctionnelle..................................... 49 8.4 Configuration du matériel....................................................................... 50 8.5 Configuration du logiciel......................................................................... 50 8.6 Défaillances systématiques...................................................................... 50 8.7 Intervalle de diagnostic........................................................................... 50 8.8 Contraintes............................................................................................. 50 8.9 Questions environnementales................................................................. 51 8.10 Tolérance aux pannes du matériel......................................................... 51 8.11 Capacité systématique.......................................................................... 51 8.12 Classification......................................................................................... 51 Garantie...................................................................................................... 52 Concept et sécurité Concept détecteur IRmax Doté de la technologie de capteur IR double longueur d’onde intégrée à un robuste boîtier en acier inoxydable 316, le détecteur IRmax est conçu pour opérer dans les conditions les plus rigoureuses. À la différence des détecteurs de gaz IR conventionnels, le détecteur IRmax ne comprend pas de chauffage empêchant la condensation sur les fenêtres et les miroirs. Le film STAY CLIR revêtant les composants optiques empêche la formation de condensation pendant le fonctionnement du détecteur IRMax. Le détecteur IRmax est compatible avec tout système de contrôle 4-20 mA et peut également être installé dans un réseau adressable Modbus RS485. (voir Section 7). Le détecteur IRmax nécessite une alimentation de 1 Watt uniquement, ce qui représente une alimentation généralement de 75 à 90 % inférieure à celle des détecteurs de gaz IR conventionnels.. Le détecteur IRmax comporte une chambre de diffusion du gaz laquelle, combinée à un couvercle étanche et efficace, assure une excellente vitesse de réponse. Le couvercle étanche a été conçu au moyen d’un logiciel de modélisation de flux en vue de permettre le gazage et le calibrage à distance du détecteur IRmax, sans nécessiter de couvercle de calibrage spécial. L’IR Display permet de contrôler localement et à distance les valeurs relevées dans IRmax. Un IR Display peut être installé directement dans IRmax. Sinon, le détecteur IRmax peut être fourni avec un module de protection de sécurité intrinsèque (SI) fixe. Un IR Display peut ensuite être connecté au module de protection SI par le biais d'un câblage temporaire ou permanent. Les options disponibles sont illustrées en Figure 3, page 33. Pour de plus amples informations sur d'autres accessoires pour le IRmax, reportez-vous à la Figure 3 de la page 33 et la section 5, page 44. Detecting Gas Saving Lives 29 Français Le détecteur IRmax est un détecteur de gaz infrarouge (IR) ultra compact qui assure une détection rapide et à sécurité intégrée des hydrocarbures et vapeurs gazeux. Concept et sécurité Informations de sécurité • Les détecteurs de gaz IRmax doivent être installés, utilisés et entretenus en respectant rigoureusement ces instructions, avertissements, informations d’étiquetage et dans les limites indiquées. Français • L’écrou arrière figurant sur le détecteur IRmax doit être maintenu fermement en position fermée durant le fonctionnement. Ne pas tenter d’enlever l’écrou arrière avant que l’alimentation au détecteur n’ait été isolée, sous risque d’explosion en présence d’une atmosphère inflammable. Avant de retirer l’écrou en vue de la maintenance, du calibrage ou d’interventions de révision, vérifier que l’atmosphère environnante est exempte de gaz ou de vapeurs inflammables. Ne pas l’ouvrir avant un délai de quelques minutes après arrêt de l’alimentation. • Les opérations de maintenance et de calibrage doivent être effectuées uniquement par un personnel de service qualifié. • Seules des pièces de rechange d’origine Crowcon doivent être utilisées ; l’utilisation de pièces de substitution peut rendre invalides la certification et la garantie du détecteur IRmax. • Les détecteurs IRmax doivent être protégés contre les risques de vibrations extrêmes et de lumière directe du soleil dans les environnements chauds car ceux-ci peuvent entraîner une hausse de la température du détecteur IRmax au-delà des limites spécifiées et ainsi susciter une défaillance prématurée. • Le détecteur IRmax ne détecte pas l’hydrogène, l’ammoniaque ou le dioxyde de carbone. • L’équipement doit être relié à la terre au moyen du presse-étoupe et du câble armé d'acier. • Certification pour les environnements poussiéreux zones 21/22 : La version de base IRmax (sans affichage IF ou module de sécurité intrinsèque) peut être utilisée dans les environnements susceptibles de contenir des poussières dangereuses (zones 21 ou 22). • Le détecteur IRmax avec module de barrière à sécurité intrinsèque peut être utilisé dans les zones 21 ou 22 dès lors que la température ambiante demeure en dessous de 40 °C et qu'un affichage IR distant ou des affichages IR portables sont installés/utilisés uniquement en dehors de la zone dangereuse. • Le détecteur IRmax avec affichage IR fixe ne peut être installé dans une zone 21 ou une zone 22. 30 Detecting Gas Saving Lives Concept et sécurité Présentation du produit Le détecteur IRmax est un détecteur certifié antidéflagrant (Exd) adapté à un emploi en environnement à risques Zone 1 ou Zone 2 ATEX . Se reporter à l’étiquette de certification apposée sur le côté du détecteur pour identifier le type de certification se rapportant au produit fourni. Remarque : si aucune étiquette de certification n’est apposée sur le détecteur IRmax, le détecteur n’est pas certifié pour une utilisation dans des espaces dangereux. IR GAS DE TECTOR 1180 IR GAS DETECTOR WITH REMOTE DISPLAY II 2 GD 1180 V m ax= 32V W m ax= 5W II 2GD Vmax=32V Wmax=5W B a s e e fa 0 9 A T E X 0 2 0 6 X IE C E x B A S 0 9 . 0 1 0 9 X S IL 2 S i r a 1 2 A T E X 1 2 0 6 X Baseefa09ATEX0220X IECEx BAS 09.0104X Ex db ia IIC T4 Gb (-40°C ≤ Ta ≤ +75°C) Ex tb ia IIIC T135°C Db (-40°C ≤ Ta ≤ +40°C) E x d b II C T 4 Gb (T am b = -40 °C to + 75 °C ) E x d b II C T 6 Gb (T am b = -40 °C to + 50 °C ) E x tb II IC T 135° C D b (-4 0° C T a + 75° C ) WARNING: DO NOT OPEN WHEN EXPLOSIVE ATMOSPHERE MAY BE PRESENT. W A R N IN G : D O N O T O P E N W H E N E X P L O S IV E A TM O S P H E R E M A Y B E P R E S E N T. A b i n g d o n , U nit e d K in g d o m , O X 1 4 4 S D Abingdon, United Kingdom, OX14 4SD IRmax Basic certification label IRmax with IS Barrier certification label IR GAS DETECTOR WITH DISPLAY 1180 II 2G Baseefa09ATEX0220X IECEx BAS 09.0104X Vmax=32V Wmax=5W Ex db ia IIC T4 Gb (-40°C Ta +75°C) WARNING: DO NOT OPEN WHEN EXPLOSIVE ATMOSPHERE MAY BE PRESENT. Abingdon, United Kingdom, OX14 4SD IRmax with Fixed IR Display certification label Figure 1: Étiquettes de certification du détecteur IRmax Detecting Gas Saving Lives 31 Français Le détecteur IRmax est un détecteur de gaz infrarouge conçu pour détecter les gaz hydrocarbures entre 0 et 100 % de la LIE (limite inférieure d’explosivité : concentration minimum dans l’air à laquelle une explosion peut se produire). 1. Introduction 1.1 Générales La configuration de chaque détecteur IRmax est identifiée par une étiquette apposée sur le corps principal de l'appareil. Lors de tout contact avec Crowcon en vue d’obtenir des conseils ou des pièces de rechange, veiller à indiquer le nom du produit, le numéro de pièce et le numéro de série. Le détecteur IRmax se compose d’un corps principal en acier inoxydable 316, d’une enveloppe étanche antistatique recouvrant les éléments optiques et d’un ensemble avec chambre de mesure du gaz et éléments électroniques. Il est également possible d’installer un module d’affichage IR Display. Les instructions du montage de l'affichage IR Display sont indiquées dans le manuel de l'afficheur IR Display (M07061). Un presse-étoupes à ergot de raccordement en option peut être fourni pour permettre la fixation du détecteur IRmax directement sur un boîtier de jonction auxiliaire doté d’entrées de câble M20 ou NPT ½”. Presse-étoupes à ergot en option Presse-étoupes de câble M20 ou NPT 1/2" 74.5 74.5 136 136 hors tout Français 1.2 Description du produit 57 hors tout 60.5 158 hors tout 157.5 Borne de terre extérieure (terre) Toutes les dimensions sont exprimées en millimètres. Figure 2: Plan coté détecteur IRmax Remarque : le corps du détecteur IRmax est fourni avec deux entrées de câble, l'une de type M20 et l’autre NPT 1/2". L’entrée de câble non spécifiée à la commande d’un détecteur IRmax sera rendue étanche à l’aide d’un obturateur certifié. Le détecteur IRmax doit être installé avec les deux entrées de câble obturées : l'une à l'aide d'un presseétoupe et l'autre à l'aide d'un bouchon obturateur conforme à une norme IP66 certifiée. 32 Detecting Gas Saving Lives 1. Introduction 15 12 Français 14 13 11 “ 10  ‘ ”  ‘ Ž    Œ Figure 3: Vue éclatée du détecteur IRmax (avec numéros de pièce, si indiqué) Œ Bouchon de calibrage M041007  Enveloppe étanche M04995 Ž Bague de retenue de miroir Livré ensemble comme un « kit de remplacement de miroir »C011206  Miroir  Adaptateur de flux S012996 ‘ Joint torique pour écrou de blocage, module de barrière à sécurité intrinsèque ou module à } affichage IR fixe : M040077  Support de fixation d’assemblage complet S012130 “ Versions à presse-étoupes à ergot M20 ou NPT 1/2" : M20 ATEX: S012147, 1/2" NPT ATEX: S012190 ” Plaque de maintien et boulons d'obturateur arrière, affichage IR fixe et module de barrière à sécurité intrinsèque. 10 Affichage IR Display version fixe 11 Raccord d’affichage IR Display à détecteur IRmax E07987 12 Module de protection SI (sécurité intégrée) 13 Câble de raccordement d’affichage IR Display 14 Support de montage d’affichage IR Display distant M03833 15 Affichage IR Display distant Detecting Gas Saving Lives 33 2. Installation AVERTISSEMENT • Ce détecteur est conçu pour un emploi environnement à risques Zone 1 et Zone 2, la certification dépendant des accessoires montés et de la température de fonctionnement environnante. Se référer au tableau de spécifications en page 43 pour plus de détails sur la certification. L’installation doit être conforme aux normes reconnues de l’instance en vigueur dans le pays concerné. Français • Pour plus d’informations, contacter Crowcon. Avant de procéder à toute intervention d'installation, veiller à suivre les réglementations et procédures de site en vigueur localement. • L’équipement doit être relié à la terre au moyen du presse-étoupes et du câble armé d'acier. • Ne pas tenter de poser l'affichage IR Display sur un détecteur IRmax non fourni à cet effet. Les détecteurs IRmax fournis pour une utilisation avec un affichage sont certifiés Exd ia et doivent être utilisés au moyen d’un affichage fixe doté d’une protection SI ou avec un affichage distant ou manuel raccordé par un module de protection SI Crowcon. • Les détecteurs fournis sans affichage sont certifiés Exd IIC et ne peuvent être soumis à une réadaptation en vue d’une utilisation avec un affichage IR Display. 2.1 Implantation Le détecteur IRmax doit être monté à l’endroit où le gaz à détecter est le plus susceptible d’être présent. Tenir compte des points suivants lors de l’implantation de détecteurs de gaz : • Pour détecter des gaz plus légers que l’air, le méthane par exemple, les détecteurs doivent être montés en hauteur. Pour détecter des gaz plus lourds que l’air, les vapeurs inflammables par exemple, les détecteurs doivent être montés à un niveau bas. • Lors de l’implantation de détecteurs, tenir compte des dommages pouvant être provoqués par les événements naturels tels que la pluie ou les inondations. Pour les détecteurs montés en extérieur dans les régions très chaudes, Crowcon recommande l’utilisation d’un pare-soleil (see Section 5, Accessoires et pièces de rechange, on page 44.) • Tenir compte de la facilité d’accès en vue des essais de fonctionnement et des révisions. • Envisager le comportement éventuel d'une fuite de gaz sous l’effet de courants d’air naturels ou forcés. Si cela s’avère indiqué, monter le détecteur IRmax dans des canalisations de ventilation (au moyen du kit de montage de canalisation de détecteur IRmax (see Section 5, Accessoires et pièces de rechange, on page 44). • Tenir compte des conditions du processus. Par exemple, le butane est généralement plus lourd que l'air, mais diffusé à partir d'un processus à une température et/ou une pression élevée, le gaz est susceptible de monter plutôt que de descendre. Le placement des capteurs doit être déterminé en suivant les conseils d’experts possédant des connaissances spécialisées sur la dispersion du gaz et les équipements de traitement de l’usine, de même qu'en matière de sécurité et d'ingénierie.. L'accord convenu quant à l’implantation des capteurs doit être consigné. 34 Detecting Gas Saving Lives 2. Installation 2.2 Montage Le détecteur IRmax peut être monté de trois façons : 2. À l’aide d’un presse-étoupes à ergot en option pour raccorder un boîtier de jonction certifié Exe ou Exd existant. Crowcon offre un presse-étoupe à ergot approprié comme pièce supplémentaire en option (voir 3 ci-dessous) 3. Au moyen du boîtier de jonction et d’un presse-étoupes à ergot Crowcon en option. La liste des pièces en option est indiquée à la section 5 de la page 44. Le détecteur IRmax doit être installé dans un emplacement désigné, le cylindre du capteur en position horizontale à +/- 15° (l’orientation est illustrée sur la Figure 2, en page 32). Ceci permet de veiller à ce que de la poussière ou de l’eau ne s’accumulent pas sur les composants optiques. 2.3 Câblage direct vers le détecteur IRmax Cette option convient uniquement à un fonctionnement 4-20 mA. Un Crowcon support de fixation est nécessaire pour fixer le détecteur à un mur ou un tuyau de 2” (50 mm). DEL d'état Signal 0 V (masse) +V (24V IRmax) Figure 4: Connexions de câble sur site sur l'IRmax Raccorder les câbles au moyen d’un presse-étoupes certifié, par l’entrée de câble choisie sur le corps du détecteur IRmax (M20 ou NPT 1/2"). Crowcon recommande d’installer les presse-étoupes de câbles orientés vers le bas. 15mm MAX Detecting Gas Saving Lives Veiller à utiliser des presse-étoupes de câbles associés à la certification Exd appropriée et s’assurer que la longueur de filetage ne dépasse pas la longueur spécifiée dans la figure (gauche). 35 Français 1. Au moyen du support de fixation en option (Crowcon), avec raccord de câble direct (utilisation avec 4-20 mA uniquement). 2. Installation 2.3.1 Désignation de bornes Avec le détecteur IRmax orienté comme illustré en Figure 2, page 32 (entrée de câble en haut), le câble à 3 fils doit être raccordé au moyen du raccord amovible, comme suit : +24 V en bas, 0 V au milieu et signal en haut. Le connecteur 6 broches situé à droite du circuit imprimé est destiné aux révisions et/ou au raccordement d’un module d’affichage IR Display. Français Borne positive : alimentation positive depuis la carte de contrôle. Borne Sig : Signal depuis la carte de contrôle. Borne 0 V : alimentation négative depuis la carte de contrôle. 2.3.2 Installation du détecteur IRmax à l’aide d’un support de fixation a. Le détecteur IRmax peut être fourni avec un support de fixation (S012130) plutôt qu’avec un presse-étoupes à ergot, de manière à pouvoir le raccorder directement à des câbles (voir Figure 5). Support de fixation : 70 mm entre les centres de fixation. Utilisez des boulons M6. Figure 5: Détecteur IRmax avec support de fixation et presse-étoupes de câble b. Si le détecteur doit être monté sur une surface plane, marquer l'emplacement de deux orifices et percer en utilisant le support de fixation comme modèle. Fixer sans serrer deux parties du support en se servant d’une paroi/surface adéquate. c. Retirer le couvercle étanche du détecteur IRmax puis faire glisser le corps du détecteur par le support. Il est recommandé d’installer le corps du détecteur IRmax avec l’entrée de câble orientée vers le bas. 36 Detecting Gas Saving Lives 2. Installation d. Serrer les deux fixations de support de sorte que le détecteur IRmax soit maintenu fermement en place. Remettre l’enveloppe étanche en place. f. Préparer le câble. Crowcon recommande un câble à blindage acier (SWA ou Steel Wire Armoured de 1,5 mm2), d'autres types de câble pouvant être utilisés dès lors qu’ils sont compatibles avec des presse-étoupes certifiés Exd). Poser un presse-étoupes de câble de certification Exd appropriée, passer les conducteurs de câble par le corps du détecteur IRmax et visser l’ensemble dans le presse-étoupes de câble. Fixer le presse-étoupes en place et s’assurer que l’armure du câble est reliée à la masse au presse-étoupes du câble et au corps du détecteur IRmax. NB. Ne pas oublier de reposer l’écrou arrière après avoir installé le câble. g. La plaque de maintien (élément 9 en Figure 3, page 33) doit être fixée solidement afin d'empêcher que l'écrou arrière (ou l'accessoire d'affichage IR fixe ou de modèle de barrière à sécurité intrinsèque) risque de se desserrer. 2.4 Installation au moyen d’un presse-étoupes à ergot et d’un boîtier de jonction auxiliaire Cette option est requise lorsque le détecteur IRmax doit être raccordé à un boîtier de jonction auxiliaire certifié Exe ou Exd existant. Figure 6: Détecteur IRmax raccordé à un boîtier de jonction auxiliaire Detecting Gas Saving Lives 37 Français e. Une fois le détecteur IRmax fixement en place, déposer l’écrou arrière du détecteur IRmax afin de permettre l’accès aux bornes de câble. 2. Installation 2.4.1 Pour poser le détecteur IRmax sur un boîtier de jonction auxiliaire : a. Procéder avec précaution pour retirer la partie extérieure du presse-étoupes à ergot (élément 8 de la Figure 3, page 33). b. Visser l'extrémité étroite du presse-étoupes à ergot dans le boîtier de jonction auxiliaire. Français c. Lever le détecteur IRmax jusqu’au boîtier de jonction et faire passer les fils par l'ensemble et dans le boîtier de jonction auxiliaire. Fixer le détecteur IRmax en place en vissant à fond le collier sur le presse-étoupes de câble. Serrer la vis de rappel. d. Le corps principal du détecteur IRmax peut être pivoté horizontalement selon un angle, dès lors qu’il est sûr d’un point de vue mécanique, qu’il est sans incidence sur tout autre équipement et est accessible en vue d’interventions de maintenance. e. Se reporter à la Section 2.6 pour des instructions sur le câblage. Voir aussi Figure 4, page 35. 2.5 Exigences de câblage Le câblage au détecteur IRmax doit être conforme aux normes reconnues de l’instance en vigueur dans le pays concerné et il doit satisfaire aux exigences électriques du détecteur IRmax. Crowcon recommande l’utilisation d’un câble à blindage acier (SWA ou Steel Wire Armoured) et des presse-étoupes antidéflagrants adéquats doivent être utilisés. D’autres techniques de câblage telles les conduites en acier peuvent être acceptables, dès lors que des normes appropriées sont respectées. La longueur de câble maximum recommandée est de 3,4 km (voir le Tableau 1). Le détecteur IRmax nécessite une alimentation cc de 12-30 V. Veiller à une alimentation minimum de 12 V du panneau de commande au détecteur IRmax, en tenant compte de la baisse de tension due à la résistance du câble à une intensité de crête de 0,1 A. En général, un câble de 1,5 mm2 permet de disposer de longueurs de câbles allant jusqu’à 3,0 km. Le Tableau 1 ci-dessous indique les distances de câble maximum lors d’une utilisation de paramètres de câble types. Coupe Résistance Max. Distance >20 V Max. Distance 18 à 20 V mm2 (Ohms par km) (km) (km) 1,0 18,4 2,2 1,6 1,5 13,0 3,0 2,3 2,5 11,5 3,4 2,6 Tableau 1 : distances de câble maximum pour câbles types 38 Detecting Gas Saving Lives 2. Installation 2.6 Raccordements et paramètres Le détecteur IRmax est réglé en usine comme étant un dispositif à « écoulement de courant », sauf spécification contraire à la commande. Pour réinitialiser la « source de courant », retirer la retour écrou et déplacer les deux liaisons du circuit imprimé de borne de la position « d’écoulement » à la position de « source », comme indiqué sur la Figure 7. Remarque : La borne de terre extérieure est utilisée uniquement lorsque les autorités locales permettent ou nécessitent un raccordement de ce type. Lorsque cela est possible, dans le but de limiter les interférences de fréquence radio, le boîtier de jonction et l’armure de câble doivent être mis à la terre uniquement au panneau de commande (zone sûre) afin d’éviter les circuits de terre. +V 0V Sg 1 2 3 Contrôleur CONTROLLER d’écoulement Paramètres de bretelle EARTH Câblage Numéro Couleur Fonction 1 2 3 Rouge Noir Vert +V 0V Signal source Connecteur du kit de communications PC Connecteur de l'affichage IR Display DEL d'état Figure 7: Emplacement de bretelle d’écoulement/de source Le signal 4-20 mA peut être défini sur « écoulement » ou « source » de courant au moyen des broches et de la liaison de bretelle indiquées dans la Figure 7. Réglez le collecteur de courant (« Sink ») en installant le cavalier aux broches 3 et 4, comme illustré sur la photo de gauche. Réglez le circuit source en installant le cavalier aux broches 1 et 2, comme illustré sur la photo de droite. Les détecteurs IRmax seront définis sur « écoulement de courant », sauf spécification contraire à la commande. Indication par DEL : Une DEL est montée sur le circuit imprimé à bornes pour indiquer l’état de fonctionnement actuel. Se reporter à la Section 6 pour plus d’informations. Detecting Gas Saving Lives 39 Français Tous les raccordements décrits se rapportent au bornier monté sur le corps principal du raccord de détecteur IRmax. Les bornes du circuit imprimé de raccord de détecteur IRmax sont marquées « + », « sig » et « 0 V ». La polarité adéquate doit être observée lors du raccordement du détecteur IRmax à l’équipement de commande. 3. Fonctionnement AVERTISSEMENT Avant de procéder à toute intervention, veiller à suivre les réglementations et procédures de site en vigueur localement. Ne jamais essayer d’ouvrir le détecteur IRmax ou le boîtier de jonction en présence de gaz inflammable. S’assurer que le panneau de commande associé est désarmé afin d'empêcher les fausses alarmes. Français 3.1 Procédure de mise en service 1. Vérifier que : a. Les raccordements de câble sont corrects. b. La tension d’alimentation est réglée au niveau de la carte de contrôle entre 18 et 30 V. La tension mesurée aux bornes du détecteur IRmax (dans le boîtier de jonction Exe si ce dernier est utilisé ou au circuit imprimé de bornes de détecteur IRmax) et elle doit être réglée entre 12 et 30 V. c. Les liaisons sont réglées pour un écoulement ou une source de courant 4-20 mA, selon la carte de contrôle. 2. Après la mise sous tension, attendre 30 minutes avant de procéder à la remise à zéro/ au calibrage. Ce délai a pour objet de veiller à la stabilité thermique. (Remarque : Le détecteur IRmax sera entièrement opérationnel 30 secondes après application de l’alimentation.) 3. Veiller à disposer d’air propre (c'est-à-dire sans gaz hydrocarbure) avant la remise à zéro. Indicateur de zéro au niveau de la carte de contrôle (se reporter aux instructions de la carte de contrôle). 4. Poser un bouchon de calibrage sur l’enveloppe étanche afin d’isoler la chambre de mesure de l’air ambiant. Un couvercle de ce type est disponible auprès de Crowcon (M041007). Raccorder le gaz de calibrage (50 % LIE nom.) et appliquer à un débit de 1 litre par minute. 5. Après un délai de 30 secondes régler le calibrage/le réglage sur la carte de contrôle, de sorte que la valeur soit 50 % de la LIE ou qu’elle corresponde à la concentration de gaz de calibrage appliquée. Le détecteur IRmax même ne devrait pas nécessiter de calibrage. 6. Retire le bouchon de gaz et de calibrage. Vérifier de nouveau le zéro. 7. Au moment de l’installation ou après changement du miroir, le détecteur peut être remis à zéro et calibré au moyen d’un accessoire d'affichage IR Display (voir page 29) ou par le biais d’un kit de communication PC (voir le manuel sur les accessoires IRmax). Remarque : Des détecteurs IRmax certifiés ATEX seront fournis calibrés en fonction de la conformité avec EN61779 (selon l’exemple 100 % de la LIE méthane = 4,4 % volume). Remarque : Il est recommandé d’utiliser le bouchon de calibrage pour la mise en service initiale. Des calibrages subséquents peuvent être effectués en effectuant une application distante de gaz vers l’enveloppe étanche, via l’ergot de tuyau (ce qui évite ainsi d’accéder directement au détecteur IRmax). Un calibrage sans le bouchon de calibrage (c’est-à-dire par le biais de l’enveloppe étanche) peut être effectué dès lors que la vitesse de vent locale est inférieure à 2 mètres/seconde. Le débit du gaz doit être supérieur à 2,0 litre/ minute. 40 Detecting Gas Saving Lives 3. Fonctionnement 3.2 Maintenance programmée Les pratiques du site gouvernent la fréquence à laquelle le détecteur IRmax doit être testé. Crowcon recommande qu’un détecteur IRmax soit soumis à des essais sur les gaz et recalibré au moins tous les 6 mois si nécessaire. Pour recalibrer un détecteur IRmax, suivre les étapes indiquées en Section 3.1. Intervalle de calibrage : Crowcon recommande d’effectuer un calibrage tous les12 mois. Calibrage distant par le biais d’un tuyau : La vitesse du vent doit être inférieure à 2 mètres par seconde. Si elle est supérieure, utiliser le bouchon de calibrage pour empêcher les risques de dilution du gaz. Nettoyage des éléments optiques : Il n’est pas recommandé, sauf si le détecteur IRmax présente un défaut d’obscurcissement. Si la fenêtre ou le miroir deviennent contaminés, les nettoyer soigneusement à l’eau (voir Section 5, Accessoires et pièces de rechange, page 44) Miroirs : S’ils sont endommagés, contacter Crowcon vue d’un remplacement (voir Section Accessoires et pièces de rechange, page 44) détecteur IRmax doit toujours être remis à zéro recalibré après un remplacement de miroir. en 5, Le et Si de la condensation commence à entraîner des défauts, remplacer le miroir (il se peut que le revêtement optique soit endommagé). Crowcon recommande de remplacer le miroir tous les 5 ans. 3.3 Changement de types de gaz Chaque détecteur IRmax est fourni précalibré pour un type de gaz donné (par exemple du méthane ou du propane). Si un ré-étalonnage est nécessaire pour un type de gaz différent, le détecteur IRmax peut être reconfiguré au moyen du kit de communications PC (voir Section 5, Accessoires et pièces de rechange, page 44), avant d'être étalonné.. Detecting Gas Saving Lives 41 Français En cas de défaillance électronique, consulter votre représentant Crowcon local. 3. Fonctionnement 3.4 Réponses relatives des types de gaz Le graphique ci-dessous indique les réponses relatives à d’autres types de gaz pour un détecteur IRmax calibré en fonction de méthane. Français Remarque : de nombreux gaz et vapeurs d'hydrocarbure sont plus aisément détectés par les détecteurs IR que le méthane. La réponse de l'IRmax (et d'autres détecteurs de gaz IR) sera linéaire à l'échelle de la plage 0-100 % LEL pour le gaz cible (p.ex. le méthane dans cet exemple), mais elle sera non -linéaire pour d'autres hydrocarbures pouvant être également présents. Figure 8 La figure indique la réponse des gaz mentionnés ci-dessus : de gauche à droite, propane, butane, pentane et méthane. D’autres types et plages de gaz sont disponibles. Contacter Crowcon pour plus de détails. 42 Detecting Gas Saving Lives Matériau d’enceinte Acier inoxydable 316 Dimensions (détecteur uniquement) 158 mm x 75 mm x 57 mm (sans ergot) Poids IRmax 1,58 kg (3,5 lbs) IRmax avec IR Display fixe 2 kg (4,4 lbs) IRmax avec module de protection SI 2,4 kg (5,3 lbs) IR Display à distance 0,2 kg (0,4 lbs) Tension de fonctionnement 12 à 30 V cc Alimentation <1W Sortie 4-20 mA 3 fils (écoulement ou source) Signal de défaut <1 mA Résistance de boucle de câble max. 80 ohms (par rapport à la borne négative) Température de fonctionnement -40 °C à +75 °C (-40 °F à +167 °F) Humidité Humidité relative de 0 à 100 % Degré de protection IP66 Protection contre les explosions Antidéflagrant Code d’approbation Détecteur IRmax (sans affichage IR Display) II 2 GD Exd db IIC T6 Gb (Tamb = -40°C à +50°C) II 2 GD Exd db IIC T4 Gb (Tamb = -40°C à +75°C) II 2 GD Ex tb IIIC T135°C Db (-40°C ≤ Ta≤ +75°C) IRmax avec module de barrière à sécurité intrinsèque (affichage distant) II 2 GD Exd db ia IIC T4 Gb (Tamb = -40°C à +75°C) Ex tb ia IIIC T135°C Db (Tamb = -40°C à +40°C) IRmax avec affichage IR fixe II 2 G Exd db ia IIC T4 Gb (Tamb = -40°C à +75°C) N° de certificat de sécurité ATEX et IECEx Détecteur IRmax (sans affichage IR Display) : Baseefa 09ATEX0206X et IECEx BAS.09.0109X Détecteur IRmax (avec affichage IR Display) : Baseefa 09ATEX0220X et IECEx BAS.09.0104X Sécurité fonctionnelle Certifié en vue d'une utilisation sur un système SIL 2. Numéro de certificat : Sira 12ATEX1206X Normes EN 60079-0:2012+A11:2013, EN 60079-1:2014, EN 60079-31:2014 IEC 60079-0:2011, IEC 60079-1:2014, IEC 60079-31:2013 EN 60079-29-1:2007, IEC 61508:2010, EN50402:2005 Zones Certifié pour une utilisation en Zone 1 ou en Zone 2 CEM EN50270 ATEX Detecting Gas Saving Lives 43 Français 4. Spécifications 5. Accessoires et pièces de rechange Français Numéros de pièce Nom Description M041007 Bouchon de calibrage S’installe sur l’enveloppe étanche standard pour permettre un calibrage lorsque la vitesse de l’air local est supérieure à 2 mètres par seconde. S012130 Kit de support de montage Permet un montage sur un mur ou un tuyau de 2" (50 mm). Non nécessaire si le détecteur IRmax est installé sur un boîtier de jonction existant. S012152 Pare-soleil/cône collecteur Peut être monté sur un détecteur IRmax en vue d'une protection contre les températures élevées résultant de la lumière directe du soleil et/ou pour étendre l’empreinte des détecteurs lors de la détection de gaz plus légers que l’air (par exemple méthane). S012169 Kit de montage de canalisation Permet un contrôle de canalisation entre 300 et 3 000 mm, et de débit de l’air entre 2 et 20 m/s. S012996 Adaptateur de débit Pour les applications de calibrage du gaz. S012827 Kit de communication PC Module, logiciel et câble de communication permettant de configurer le détecteur. M20: S012295 ½” NPT: S012296 Boîtier de jonction auxiliaire Option de montage pour IRmax, pour un emploi en environnements à risques. C011210 Kit de nettoyage de mirroir Contient des lingettes imprégnées d’alcool isopropylique et un chiffon en en microfibres Pièces de rechange de détecteur IRmax Se reporter à la Figure 3 en page 33 pour plus de détails sur les pièces de rechange. . 44 Detecting Gas Saving Lives 6. Dépannage du détecteur 6.1 Erreurs signalées par DEL La DEL montée sur le circuit imprimé de la borne permet d’identifier les défauts. Sa position est indiquée sur la Figure 7, page 39. Le tableau ci-dessous indique comment interpréter le problème correspondant à chaque modèle de clignotements. État du détecteur Clignotement régulier toutes les secondes En bon état Action Allumé et s’éteignant lors de courtes impulsions. Détecteur IRmax en mode de démarrage. Attendre 10 secondes. Clignotement rapide activé et désactivé ou modèle de clignotement irrégulier. Tension d'alimentation trop faible ou trop élevée. S’assurer que la tension d’alimentation du détecteur IRmax est réglée correctement. S’assurer que la mesure est effectuée directement au niveau des bornes du détecteur IRmax. Allumé en permanence. Défaut, erreur d’hôte ou d’i-module. Effectuer un cycle d’alimentation vers le détecteur IRmax. Si le défaut persiste, le renvoyer à Crowcon. Deux longs clignotements suivis d’un clignotement court. Erreur fatale ; défaut de voyant ou de détecteur. Renvoyer à Crowcon Clignotement double rapide toutes les secondes. Erreur fatale, défaut de module ou de configuration. Contrôler la configuration du détecteur IRmax au moyen du logiciel kit de communication PC. Contrôler l'alimentation électrique. Si le défaut persiste, le renvoyer à Crowcon. Impulsion courte toutes les secondes. Obscurcissement des éléments optiques. Contrôler la fenêtre et le miroir et les nettoyer si nécessaire. Remettre le détecteur IRmax à zéro et contrôler le calibrage. Tout autre défaut peut être rectifié uniquement en renvoyant le détecteur IRmax à Crowcon ou à un agent d’entretien autorisé. 6.2 Sortie analogique IRmax restera dans l'état de Défaut (Fault) et le message « Entretien requis » (Service required) sera également indiqué sur l'affichage IR (si monté) si le signal de sortie analogique est défaillant ou s'il n'est pas connecté à un système de contrôle ou à une résistance de charge. Le détecteur IRmax contrôle activement le signal de sortie analogique 4-20 mA afin de vérifier s'il se situe dans cette plage de valeurs. Si le signal se situe en dehors de cette plage, le détecteur passe en mode Défaut et le signal est défini sur la valeur 1 mA. Par conséquent, lors des tests d'un détecteur, il importe essentiellement de raccorder celui-ci à un tableau de commande ou raccorder une résistance de charge de 100 Ω entre les bornes « 0 V » et « Sig » (le détecteur est configuré selon le mode « Source ») ou entre les bornes « 0 V » et « V » (le détecteur est configuré selon le mode « Courant absorbé » ). Detecting Gas Saving Lives 45 Français Modèle DEL 7. Configuration du Modbus RS485 7.1 Générales Cette section explique comment utiliser un détecteur IRmax dans une configuration Modbus. Une version activée RS485 est disponible pour ce type d'application. Il est possible de relier jusqu’à 32 détecteurs IRmax selon des configurations en étoiles ou par bus, comme décrit ci-dessous. Français Les connexions à la version RS485 du détecteur IRmax doivent être effectuées au moyen d’un presse-étoupes à ergot vers un boîtier de jonction auxiliaire (voir Section 5, page 44), plutôt qu’à l'aide d'un câblage direct dans le détecteur. Noter que l’affichage IR Display ne peut être utilisé avec des détecteurs IRmax. La version activée RS485 du détecteur IRmax comporte cinq bornes. Ces bornes sont les suivantes : 1 Alimentation positive 12 à 30 V au-dessus de 0 V 2 0V Référence retour et RS485 3 Signal 4-20 mA Signal source ou écoulement (option) 4 RS485 B Signal différentiel RS485 5 RS485 A Signal différentiel RS485 Les signaux aux bornes RS485 sont conformes à la norme EIA/TIA-485, ce qui signifie que la plage de mode commune se situe de -7 V à +12 V pour ce qui est de la borne 0 V. Noter que tous les fabricants ne s’accordent pas en ce qui concerne la polarité des signaux A et B. Si le câblage ne fonctionne pas dans un sens, les utilisateurs doivent intervertir les câbles A et B RS485. Il n’y a aucun risque de raccordement incorrect. Les paramètres de communication sont 9 600 bps, deux bits d’arrêt et aucune parité. Lors de la compilation d’une interface de système de contrôle, il importe de tenir compte du temps nécessaire au système pour recueillir les informations tour à tour pour chaque détecteur. La vitesse la plus rapide à laquelle plusieurs détecteurs peuvent être interrogés est de 14 détecteurs par seconde, les conditions dans la pratique pouvant réduire ce nombre à 7 détecteurs par seconde. Les utilisateurs doivent s’assurer que l’arrangement permet aux signaux d'alarme d'être enregistrés dans les limites de temps acceptables. Il importe également de veiller à ce que le système puisse fournir une alimentation suffisante en vue de maintenir le fonctionnement de tous les détecteurs. Pour calculer la quantité d’alimentation nécessaire à une connexion par bus linéaire, voir Section 7.3, Exigences de câblage, page 48. Pour obtenir des instructions Modbus complètes, contacter Crowcon (voir les adresses au verso de la couverture). 46 Detecting Gas Saving Lives 7. RS485 Modbus configuration 7.2 Topologie du câblage 7.2.1 Connexion à étoiles Dans une topologie à étoiles, tous les détecteurs sont reliés par câble à un point central, généralement le panneau de commande. Aucun câble ne nécessite plus de cinq fils, toutes les connexions de signal 4-20 mA étant acheminées directement vers le panneau de commande. Les signaux A et B RS485 peuvent ensuite être tous connectés ensemble au point étoile. Le bus doit ensuite être terminé au point étoile au moyen d’une résistance de connexion de sortie 110 ohms. La longueur de chaque bras de l’étoile ne peut dépasser 750 mètres. 7.2.2 Connexion de bus linéaire Dans une topologie à connexion de bus, tous les détecteurs IRmax sont reliés par câble à un arrangement linéaire, généralement avec le panneau de commande à une extrémité. Selon une installation classique en tunnel, les détecteurs IRmax sont installés à intervalles réguliers (voir Figure 9 ci-dessous). Pour raccorder le câblage de l’installation, poser deux résistances de connexion de sortie 110 ohms à chaque extrémité physique du bus. Les signaux 4-20 mA ne pouvant être partagés, un conducteur supplémentaire est nécessaire sur chaque distance de répétition de câblage. Si aucun des signaux 4-20 mA n’est utilisé, seuls quatre conducteurs seront nécessaires. FIGURE DE CONNEXION DE BUS LINÉAIRE linear bus Xgard Junction Box French Figure 9 Detecting Gas Saving Lives 47 12 October 2010 18:39:19 VERS PANNEAU DE COMMANDE Français Les deux topologies de câblage utilisées communément sont la connexion à étoiles et le bus linéaire. 7. RS485 Modbus configuration 7.3 Exigences de câblage Français 7.3.1 Calcul du niveau minimum d’alimentation requise Plus le nombre de détecteurs IRmax connecté au bus linéaire est important et plus l’alimentation nécessaire au système sera élevée. Pour calculer l’alimentation requise pour une configuration particulière, il est nécessaire de connaître la résistance de câble entre chaque paire de détecteurs IRmax. Un courant d’au moins 0,1 mA doit être prévu pour chaque « distance de répétition » entre les détecteurs IRmax. La tension à appliquer peut être calculée en estimant la baisse de tension au niveau de chaque « distance de répétition ». À terme, il doit rester une tension d’au moins 12 V pour veiller à ce que le dernier détecteur IRmax fonctionne correctement. Contacter Crowcon pour tout conseil sur une situation spécifique. Sinon, suivre les étapes ci-dessous et le calcul modèle indiqué dans la section suivante. 1. La tension ne doit pas baisser en-dessous de 12 V ; veiller donc à effectuer le calcul en définissant la tension du dernier détecteur IRmax de la ligne selon cette valeur. 2. Chaque détecteur IRmax peut utiliser jusqu’à 0,1 A. Calculer la perte de tension de câble de la première distance de répétition séparant les détecteurs en admettant que le « courant cumulé » correspond à 0,1 A et multiplier cette valeur par la résistance de câble de la distance de répétition entre le dernier détecteur et l’avant-dernier des détecteurs IRmax. 3. Ajouter cette baisse de tension à la tension initiale de 12 V pour obtenir la tension la plus basse acceptable à l’avant-dernier des détecteurs IRmax. Ajouter 0,1 A à la valeur de « courant cumulé » pour parvenir à 0,2 mA, valeur de courant minimum alimentant l’avant-dernière distance de répétition du bus. Multiplier cette valeur par la résistance de câble de l’avant-dernière distance de répétition pour obtenir la baisse de tension suivante. 4. Répéter ce processus pour chaque détecteur IRmax, en accumulant les pertes de tension se produisant entre chaque détecteur IRmax. 5. Une tension de détecteur maximum de 30 V ne doit pas être dépassée. 7.3.2 Exemple de calcul À titre d’exemple, voici les résultats du calcul pour six détecteurs IRmax séparés d’une distance égale de 250 m sur câble, avec une section de 1 mm2. Chaque distance de répétition a une résistance de 4,6 ohms.. Station Tension d’alimentation Alimentation en courant 1 12 0,1 A 2 12,46 0,2 A 3 13,38 0,3 A 4 14,76 0,4 A 5 16,6 0,5 A 6 18,9 0,6 A Alimentation de panneau 21,66 0,6 A 48 Detecting Gas Saving Lives 8. Manuel de sécurité fonctionnelle 8.1 Introduction 8.2 Fonction de sécurité IRmax et IRmax Modbus Pour mesurer la concentration de gaz inflammables et indiquer la mesure au moyen d'une sortie 4-20 mA. Les défaillances liées à la fonction de sécurité seront détectées par le matériel et le micrologiciel associé. Elles seront indiquées sous forme de signal de sortie inférieur à 3,6 mA ou supérieur à 21 mA. 8.3 Informations relatives à la sécurité fonctionnelle Nom de paramètre Symbole Équation/source IRmax Intervalle d'essai de mise à l'épreuve T1 Comme défini par Crowcon. Durée moyenne des réparations MTTR Comme défini par Crowcon. 8 760 heures (annuel) 8 heures Type A/B Type A Comme défini par Crowcon. Type B Défaillances totales : λ De l'AMDEC 1.04E-05 Défaillances diagnostiquées sûres : λSD De l'AMDEC 1.95E-08 Défaillances non diagnostiquées sûres : Défaillances diagnostiquées dangereuses : Défaillances non diagnostiquées dangereuses : Défaillances sans effet sûres : Champ d'application des diagnostics : Fraction de défaillance sans danger : λSU De l'AMDEC 8.59E-08 λDD De l'AMDEC 9.74E-06 λDU De l'AMDEC 5.06E-07 λNE De l'AMDEC 3.21E-09 DC λDD / (λDU + λDD) 95.06% SFF (λSD + λSU + λDD) / λ (λDU / λD)(T/2 + MTTR) + (λDD / λD ) MTTR 95.11% (λDU + λDD) tCE 2.30E-03 λDU (T / 2+MTTR) + (λDD MTTR) 2.30E-03 1-ε-(λdd+λdu) tce 2.30E-03 Temps d'arrêt d'équivalent de canal tCE PFDAVG (au moyen d'une équation PFDAVG 61508-6) PFDAVG (au moyen d'une équation PFDAVG simplifiée) PFDAVG (au moyen d'une équation PFDAVG IEC 61508-6) Capacité SIL (mode demande faible) 2.24E+02 SIL2 SIL2 Capacité SIL (mode demande élevée) Pour les applications à demande faible, toutes les variantes du système conviennent à une utilisation dans les applications SIL 2, pour ce qui est des défaillances de matériel aléatoires et de la fraction de défaillance sans danger. Detecting Gas Saving Lives 49 Français Les sections suivantes fournissent des informations sur la certification de l'IRmax, conformément aux normes de sécurité fonctionnelle IEC 61508 et EN 50402. Des informations sont fournies sur les caractéristiques relatives à la sécurité, aux exigences et aux données de maintenance, afin de permettre l'intégration de l'IRmax dans le système de sécurité actif (Safety Instrumented System - SIS). Manuel de sécurité fonctionnelle 8.4 Configuration du matériel Le cheminement 1H (tolérance de défaillance de matériel et fraction de défaillance sans danger) a été utilisé pour évaluer le niveau d'intégrité de la sécurité du matériel. 8.5 Configuration du logiciel Français L'évaluation du micrologiciel du produit a été effectuée conformément aux exigences précisées dans la norme CIE 61508:3 2010. 8.6 Défaillances systématiques Le cheminement 1S (défini dans la norme CIE 61508:2 2010 paragraphe 7.4.2.2c) est utilisé pour la conformité avec les exigences relatives à la prévention des défaillances systématiques. 8.7 Intervalle de diagnostic La plupart des fonctions de diagnostic sont contrôlées de manière continue. Des essais portant sur le dispositif de surveillance du système doivent être réalisés durant l'essai de mise à l'épreuve annuel en éteignant puis en rallumant l'instrument : L'IRmax doit être soumis annuellement à une mise hors tension puis à une mise sous tension (en coupant l'alimentation 24 V c.c. puis en la rétablissant) dans le cadre du programme d'entretien du produit (se reporter également à la section 3.2). 8.8 Contraintes Les taux de défaillance sont constants. Un essai de mise à l'épreuve réalisé au moins une fois par an identifiera toutes les défaillances n'ayant pas été repérées. Les réparations ont une durée moyenne des réparations de 8 heures. On suppose que l'utilisateur se sert de cette fonction de diagnostic via l'accessoire d'affichage IR et/ou l'interface PC afin de minimiser le temps d'arrêt potentiel du produit. L'évaluation de fiabilité est un processus statistique d'application d'informations relatives à des défaillances précédentes à des conceptions et configurations proposées. Elle fournit par conséquent une cible/estimation crédible de la fiabilité probable de l'équipement, en supposant que les conditions de fabrication, de conception et d'utilisation sont identiques à celles utilisées lorsque les informations ont été recueillies. Il s'agit d'une technique d'examen de conception précieuse qui permet de comparer des conceptions différentes, d'établir un ordre de grandeur, des cibles de rendement et d'évaluer les effets potentiels de changements apportés à la conception. Toutefois, les valeurs prévues effectives ne peuvent être garanties comme prévoyant le nombre précis de défaillances sur le terrain car ceci dépend de nombreux facteurs indépendants du contrôle d'une analyse prédictive. Dans le cadre de cette prévision, on suppose que les taux de défaillances (symbole λ) sont constants au fil du temps. Les défaillances précoces et liées à l'usure réduiraient la fiabilité mais l'on suppose que celles-ci sont supprimées respectivement par déverminage et par remplacement préventif. 50 Detecting Gas Saving Lives Manuel de sécurité fonctionnelle Concernant la probabilité de défaillance à la demande, il est probable que le système soit en état de défaillance à un moment aléatoire. Ceci est synonyme de non disponibilité en régime établi, indiquée par : Non disponibilité = (λ x MDT)/(1 + (λ x MDT)) qui correspond approximativement à λ x MDT pour de petites valeurs de λ x MDT Les taux de défaillance utilisés, et donc, les disponibilités dérivées sont celles associées de manière crédible à une conception éprouvée suite à une période adéquate de croissance de la fiabilité. 8.9 Questions environnementales Contraintes environnementales : Le produit sera utilisé selon une plage de températures ambiantes maximum de -40 °C à +75 °C. Le produit sera stocké selon une plage de températures ambiantes maximum de -40 °C à +80 °C. Le produit sera utilisé selon une plage d'humidité relative maximum de 0 % à +100 % Avec condensation Ce produit a un indice de protection IP66 selon les définitions comprises dans la norme EN60529. Ce produit est conçu en vue d'un fonctionnement continu. 8.10 Tolérance aux pannes du matériel La tolérance aux pannes du matériel est de 0. 8.11 Capacité systématique L'IREX/IRmax correspond à la Classe SC2. 8.12 Classification L'IREX/IRmax est un composant de type B. Detecting Gas Saving Lives 51 Français où λ correspond au taux de défaillances et MDT au Temps d'arrêt moyen. Ceci est cohérent avec l'expression liée à la Disponibilité, indiquée comme : MTBF/(MTBF+MDT) Garantie Cet équipement est testé et calibré entièrement lorsqu’il quitte l’usine. Si, au cours de la période de garantie de trois ans à compter de l’expédition, cet équipement s’avère défectueux en raison d’un défaut de fabrication ou de matériau, nous procéderons, à notre discrétion, à sa réparation ou à son remplacement gratuit, en fonction des conditions ci-dessous. Procédure de garantie Français Pour faciliter le traitement efficace de toute réclamation, contacter notre équipe de support client au +44 (0)1235 557711 en fournissant les informations suivantes : votre nom, votre numéro de téléphone, de télécopie et votre adresse de messagerie électronique. Description et quantité d'articles renvoyés, y compris tout accessoire. Numéro(s) de série d’instrument. Motif du renvoi. Obtenir un formulaire de renvoi aux fins d'identification et de traçabilité. Ce formulaire peut être téléchargé depuis notre site Internet crowconsupport.com, au même titre qu’une étiquette de renvoi. Nous pouvons également vous en faire parvenir une copie par messagerie électronique. Le détecteur IRmax ne sera pas accepté au titre de la garantie sans Numéro de retour Crowcon (NRC). Il importe impérativement que l’étiquette de l’adresse soit bien fixée à l’emballage extérieur des articles renvoyés. La garantie serait rendue non valide s'il s'avérait que l'instrument avait été modifié, démonté ou avait fait l'objet de toute intervention non autorisée. La garantie ne couvre pas une utilisation incorrecte ou abusive de l’appareil. Clause de non-garantie Crowcon n’accepte aucune responsabilité pour toute perte ou dommage direct ou indirect, quel qu’en soit l’origine (y compris les pertes ou dommages découlant de l’utilisation de l’instrument) et toute responsabilité quant à un tiers est exclue expressément. Cette garantie ne couvre pas la précision du calibrage de l’appareil ni la finition du produit. Cet appareil doit être entretenu conformément aux instructions de fonctionnement et de maintenance. La garantie ou le remplacement d’articles consommables (tels que le miroir) fournis dans le cadre de la garantie en vue du remplacement d’articles défectueux, seront limités à la garantie non expirée de l’article fourni d’origine. Crowcon se réserve le droit de déterminer une période de garantie, de réduire ou de refuser une période de garantie pour tout capteur fourni en vue d’une utilisation dans un environnement ou pour une application dont on sait qu’ils sont associés à un risque de dégradation ou de dommages du capteur. Notre responsabilité concernant un équipement défectueux se limite aux obligations définies dans la garantie et toute garantie, condition ou déclaration prononcée, expresse ou implicite, statutaire ou autre quant à la qualité marchande de nos équipements ou de son usage pour quelque but que ce soit, sauf dans les limites imposées par les statuts. Cette garantie ne saurait affecter les droits légaux d’un client. 52 Detecting Gas Saving Lives Garantie Crowcon se réserve le droit d’appliquer des frais de manutention et de transport lorsque des appareils renvoyés en raison d’une défaillance s’avèrent nécessiter un calibrage ou un entretien normal auquel le client se refuse ensuite à procéder. Pour toute question concernant la garantie et le support technique, contacter : Français L’équipe de support client Tel: +44 (0) 1235 557711 Fax: +44 (0) 1235 557722 Email: [email protected] Detecting Gas Saving Lives 53 Inhaltsverzeichnis Konzept und Sicherheit............................................................................... 57 Beschreibung des IRmax-Detektors .................................................... 57 Sicherheitsinformationen...................................................................... 58 Produktübersicht.................................................................................. 59 1. Einleitung................................................................................................ 60 1.1 Allgemeines................................................................................... 60 1.2 Produktbeschreibung..................................................................... 60 2. Installation............................................................................................... 62 WARNHINWEIS.................................................................................... 62 2.1 Standort......................................................................................... 62 2.2 Montage........................................................................................ 63 2.3 Direktverkabelung an IRmax-Detektor .......................................... 63 2.3.1 Anschlussbezeichnung.......................................................... 64 2.3.2 Installation vom IRmax-Detektor mit einer Montagehalterung... 64 2.4 Installation mit Doppelverschraubung und Hilfsverteilerkasten........ 65 2.4.1 Anbringen des IRmax-Detektors an einem Hilfsverteilerkasten:..... 66 2.5 Anforderungen an die Verkabelung............................................... 66 2.6 Verbindungen und Einstellungen.................................................. 67 3. Betrieb.................................................................................................... 68 3.1 Inbetriebnahmeverfahren............................................................... 68 3.2 Routinewartung............................................................................. 69 3.3 Ändern der Gasart......................................................................... 69 3.4 Relatives Ansprechen auf Gasarten................................................ 70 4. Technische Daten.................................................................................... 71 5. Zubehör und Ersatzteile........................................................................... 72 6. Fehlerbehebung..................................................................................... 73 6.1 Von der LED angezeigte Fehler...................................................... 73 6.2 Analogausgang.............................................................................. 73 7. RS485-Modbuskonfiguration................................................................... 74 7.1 Allgemeines................................................................................... 74 7.2 Verkabelungstopologie.................................................................. 75 7.2.1 Sternverbindung.................................................................... 75 7.2.2 Lineare Busverbindung.......................................................... 75 7.3 Anforderungen an die Verkabelung............................................... 76 7.3.1 Berechnung der erforderlichen Mindestleistung..................... 76 7.3.2 Beispielberechnung............................................................... 76 8. Handbuch für funktionale Sicherheit....................................................... 77 8.1 Einführung..................................................................................... 77 8.2 IRmax und IRmax Modbus Sicherheitsfunktion............................... 77 8.3 Daten zur funktionalen Sicherheit.................................................. 77 8.4 Hardwarekonfiguration.................................................................. 78 8.5 Softwarekonfiguration................................................................... 78 8.6 Systematische Ausfälle................................................................... 78 8.7 Diagnoseintervall............................................................................ 78 8.8 Beschränkungen............................................................................ 78 8.9 Umgebungsbedingungen............................................................... 79 8.10 Hardwarefehlertoleranz................................................................ 79 8.11 Systematische Eignung................................................................. 79 8.12 Klassifizierung.............................................................................. 79 Garantie...................................................................................................... 80 Konzept und Sicherheit Beschreibung des IRmax-Detektors Der IRmax-Detektor ist ein ultrakompakter Infrarot (IR)-Gasdetektor, der zur schnellen, ausfallsicheren Detektion von Kohlenwasserstoffgasen und -dämpfen dient. Der IRmax-Detektor ist mit Doppel-Wellenlängen-IR-Sensortechnologie in einem robusten Stahlgehäuse aus 316 Edelstahl ausgestattet und für den Betrieb unter härtesten Bedingungen ausgelegt. Im Gegensatz zu herkömmlichen IR-Gasdetektoren enthält der IRmax-Detektor keine Heizgeräte, um Kondensation auf Fenstern und Spiegeln zu verhindern. Die STAY CLIR-Beschichtung der optischen Komponenten verhindert die Kondensationsbildung während des Detektorbetriebs. Der IRmax-Detektor benötigt nur 1 Watt Leistung, was einem Stromverbrauch von typischerweise 75-90% weniger als bei herkömmlichen IR-Gasdetektoren entspricht. Der IRmax-Detektor ist mit einer kompakten Diffusionsgaskammer ausgestattet, die in Kombination mit einer wirkungsvollen wetterfesten Kappe eine ausgezeichnete Reaktionsgeschwindigkeit bietet. Die wetterfeste Kappe ist mit Hilfe von Strömungsmodellierungssoftware entworfen worden, um die Ferngasbeaufschlagung und -kalibrierung des IRmax-Detektors ohne besondere Kalibrierungskappe zu ermöglichen. Das IR Display ermöglicht die Überwachung von Messwerten vom IRmax sowohl lokal als auch in Fernabfrage. Ein IR Display kann direkt am IRmax montiert werden. Alternativ kann IRmax mit einem montierten eigensicheren (IS) Barrieremodul geliefert werden. Ein IR Display kann dann über ein temporäres oder permanentes Kabel an das eigensichere Barrieremodul angeschlossen werden. Die verfügbaren Optionen sind in Diagramm 3 auf Seite 61 dargestellt. Weitere Informationen über anderes Zubehör für den IRmax siehe Diagramm 3 auf Seite 61 und Abschnitt 5, Seite 72. Detecting Gas Saving Lives 57 Deutsch Der IRmax-Detektor ist mit jedem 4-20mA-Steuersystem kompatibel und kann außerdem in ein über Modbus adressierbares RS485-Netzwerk eingebaut werden (siehe Abschnitt 7). Konzept und Sicherheit Sicherheitsinformationen • IRmax-Gasdetektoren müssen unter strenger Befolgung dieser Anweisungen, Warnhinweise, Etikettinformationen und innerhalb der angegebenen Grenzwerte installiert, betrieben und gewartet werden. • Die rückwärtige Mutter am IRmax-Detektor muss während des Betriebs fest geschlossen bleiben. Versuchen Sie nicht, die rückwärtige Mutter zu entfernen, bevor die Stromversorgung zum IRmax-Detektor abgetrennt worden ist, ansonsten kann eine Zündung einer entflammbaren Atmosphäre auftreten. Prüfen Sie vor dem Abnehmen der Mutter zu Wartung, Kalibrierung oder Servicearbeiten, dass die Umgebungsatmosphäre frei von entflammbaren Gasen oder Dämpfen ist. Lösen Sie die Mutter erst mehrere Minuten nach dem Abtrennen der Stromversorgung. • Wartungs- und Kalibrierungsarbeiten dürfen nur von qualifiziertem Kundendienstpersonal durchgeführt werden. Deutsch • Es dürfen nur Original Crowcon Ersatzteile verwendet werden. Andere Komponenten können die Zertifizierung und Garantie des IRmax-Detektors ungültig machen. • IRmax-Detektoren müssen vor starker Vibration und direktem Sonnenlicht in heißen Umgebungen geschützt werden, da dies dazu führen könnte, dass die Temperatur des IRmax-Detektors über die angegebenen Grenzwerte steigt und zu einem frühzeitigen Versagen führt. • Der IRmax-Detektor weist weder Wasserstoff, Ammoniak noch Kohlendioxid nach. • Die Anlage muss mit der Kabelbuchse und dem stahlbewehrten Kabel geerdet werden. • Zertifizierung für staubexplosionsgefährdete Atmosphären der Zone 21/22: IRmax basic (ohne IR Display oder IS Barrieremodul) kann in Bereichen eingesetzt werden, die explosionsgefährdete Stäube enthalten können (Zone 21 oder 22). • IRmax mit einem IS Barrieremodul kann in Zone 21 oder 22 eingesetzt werden, sofern die Umgebungstemperatur unter 40 °C bleibt und ein Fernbedienungs-IR Display oder Hand-IR Display nur außerhalb des explosionsgefährdeten Bereichs montiert/eingesetzt wird. • IRmax mit einem stationären IR Display kann nicht in einem Bereich der Zone 21 oder 22 montiert werden. 58 Detecting Gas Saving Lives Konzept und Sicherheit Produktübersicht Der IRmax-Detektor ist ein Infrarot-Gasdetektor, der zur Detektion von üblichen Kohlenwasserstoffgasen im Bereich von 0 bis 100% UEG (Untere Explosionsgrenze: die Mindestkonzentration in Luft, bei der eine Zündung auftreten kann) bestimmt ist. Der IRmax-Detektor ist ein zugelassener flammensicherer (Exd) Detektor, der zur Verwendung in Gefahrenbereichen der ATEX Zone 1 oder Zone 2 geeignet ist. Zur Identifikation des Zulassungstyps, der sich auf das gelieferte Produkt bezieht, siehe Zulassungsetikett an der Seite des IRmax-Detektors. IR GAS DE TECTOR 1180 IR GAS DETECTOR WITH REMOTE DISPLAY II 2 GD 1180 V m ax= 32V W m ax= 5W II 2GD Vmax=32V Wmax=5W B a s e e fa 0 9 A T E X 0 2 0 6 X IE C E x B A S 0 9 . 0 1 0 9 X S IL 2 S i r a 1 2 A T E X 1 2 0 6 X Baseefa09ATEX0220X IECEx BAS 09.0104X Ex db ia IIC T4 Gb (-40°C ≤ Ta ≤ +75°C) Ex tb ia IIIC T135°C Db (-40°C ≤ Ta ≤ +40°C) E x d b II C T 4 Gb (T am b = -40 °C to + 75 °C ) E x d b II C T 6 Gb (T am b = -40 °C to + 50 °C ) E x tb II IC T 135° C D b (-4 0° C T a + 75° C ) WARNING: DO NOT OPEN WHEN EXPLOSIVE ATMOSPHERE MAY BE PRESENT. W A R N IN G : D O N O T O P E N W H E N E X P L O S IV E A TM O S P H E R E M A Y B E P R E S E N T. A b i n g d o n , U nit e d K in g d o m , O X 1 4 4 S D Abingdon, United Kingdom, OX14 4SD IRmax Basic certification label IRmax with IS Barrier certification label IR GAS DETECTOR WITH DISPLAY 1180 II 2G Baseefa09ATEX0220X IECEx BAS 09.0104X Vmax=32V Wmax=5W Ex db ia IIC T4 Gb (-40°C Ta +75°C) WARNING: DO NOT OPEN WHEN EXPLOSIVE ATMOSPHERE MAY BE PRESENT. Abingdon, United Kingdom, OX14 4SD IRmax with Fixed IR Display certification label Diagramm 1: IRmax-Detektor-Zertifizierungsetiketten Detecting Gas Saving Lives 59 Deutsch Hinweis: Wenn der IRmax-Detektor kein Zulassungsetikett hat, ist der Detektor nicht zur Verwendung in Gefahrenbereichen zugelassen. 1. Einleitung 1.1 Allgemeines Die Konfiguration jedes IRmax-Detektors wird durch ein Etikett angegeben, das am Hauptgehäuse angebracht ist. Bitte geben Sie den Produktnamen, die Teilenummer und die Seriennummer an, wenn Sie sich für Hilfestellung oder Ersatzteile an Crowcon wenden. 1.2 Produktbeschreibung Der IRmax-Detektor besteht aus einem Gehäuse aus Edelstahl 316, einer antistatischen wetterfesten Abdeckung über der Optik und einer Gasmessungskammer und einer Elektronikbaugruppe. Ein IR Display-Modul kann ebenfalls enthalten sein. Anleitung für den Einbau des IR Display sind im IR Display Handbuch (M07061) enthalten. Optionale Doppelverschraubung M20- oder 1/2" NPTKabelverschraubung 74.5 74,5 136 136 insgesamt Deutsch Es kann eine optionale Doppelverschraubung mit entweder M20- oder ½” NPT-Kabeleingang geliefert werden, um den IRmax-Detektor direkt an Hilfsverteilerkasten mit entweder M20- oder ½” NPTKabeleingängen anzuschließen. 57 insgesamt 60.5 158 insgesamt 157.5 Externer Masseanschluss (ERDE) Alle Abmessungen in Millimetern Diagramm 2: IRmax-Detektor – bemessene Ansicht Hinweis: Das Gehäuse des IRmax-Detektors wird mit zwei Kabeleingängen geliefert – einem M20- und einem 1/2" NPT-Eingang. Der bei der Bestellung eines IRmax-Detektors nicht angegebene Kabeleingang wird mit Hilfe eines zertifizierten Stopfens versiegelt. Der IRmax muss mit beiden Kabeleinführungen abgedichtet montiert werden: eine mit einer Kabelverschraubung, die andere mit einem zertifizierten IP66-Verschlussstopfen. 60 Detecting Gas Saving Lives 1. Einleitung 15 12 14 13 11 “ Deutsch 10  ‘ ”  ‘ Ž    Œ Diagramm 3: IRmax-Detektor – Explosionszeichnung (Teilenummer abgebildet, soweit zutreffend) Œ Kalibrierungskappe M041007  Wetterfeste Kappe M04995 Ž Spiegelhalter Zusammen als „Spiegelersatz-Kit” geliefert C011206  Spiegel  Strömungsadapter S012996 ‘ O-Ring für Gegenmutter, IS Barrierenmodul oder stationäres IR Displaymodul: M040077  Montagehalterung als Komplettbaugruppe S012130 “ M20- oder 1/2" NPT-Versionen der Doppelverschraubung: M20 ATEX: S012147, 1/2" NPT ATEX: S012190 ” Halteblech und Schrauben für hinteren Stopfen, stationäres IR Display und IS Barrieremodul. } 10 IR Display-Festversion 11 IR Display-an-IRmax-Detektor-Steckverbinder E07987 12 IS-Barrierenmodul 13 IR Display-Anschlusskabel 14 Fernbedienungs-IR Display-Montagebuchse M03833 15 Fernbedienungs-IR Display Detecting Gas Saving Lives 61 2. Installation WARNHINWEIS • Der IRmax-Detektor ist zur Verwendung in Gefahrenbereichen der Zone 1 und Zone 2 bestimmt. Die Zulassung hängt von dem eingebauten Zubehör und der Umgebungsbetriebstemperatur ab. Einzelheiten zur Zulassung entnehmen Sie bitte der Spezifikationstabelle auf Seite 71. Die Installation muss gemäß der anerkannten Standards der zuständigen Aufsichtsbehörde in dem jeweiligen Land erfolgen. • Weitere Informationen erhalten Sie von Crowcon. Vor der Ausführung aller Installationsarbeiten müssen Sie gewährleisten, dass die lokalen Bestimmungen und Standortverfahren eingehalten werden. • Die Anlage muss mit der Kabelbuchse und dem stahlbewehrten Kabel geerdet werden. Deutsch • Versuchen Sie nicht, ein IR Display an einem IRmax-Detektor anzubringen, der nicht für diesen Zweck geliefert worden ist. Zur Verwendung mit einem Display gelieferte Detektoren sind mit „Exd ia“ zertifiziert und müssen entweder mit einem festen Display, das eine IS-Barriere enthält, oder mit einem Fernbedienungs- oder Handgerät-Display betrieben werden, das über ein Crowcon IS-Barrieremodul angeschlossen ist. • Ohne ein Display gelieferte Detektoren sind mit „Exd IIC“ zertifiziert und können nicht zur Verwendung mit einem IR Display nachgerüstet werden. 2.1 Standort Der IRmax-Detektor muss dort montiert werden, wo das zu detektierende Gas am ehesten vorhanden ist. Die folgenden Punkte müssen bei der Anbringung von Gasdetektoren berücksichtigt werden: • Für die Detektion von Gasen, die leichter als Luft sind, wie zum Beispiel Methan, müssen Detektoren hoch über dem Boden angebracht werden. Für die Detektion von Gasen, die schwerer als Luft sind, wie zum Beispiel entflammbare Dämpfe, müssen Detektoren niedrig über dem Boden angebracht werden. • Bedenken Sie beim Anbringen von Detektoren die möglichen Beschädigungen durch Naturereignisse, zum Beispiel Regen oder Überschwemmungen. Bei der Außenanbringung von Detektoren in sehr heißen Gebieten empfiehlt Crowcon den Einsatz eines Sonnenschutzes (siehe Abschnitt 5, Zubehör und Ersatzteile, auf Seite 72). • Achten Sie darauf, dass die Detektoren für Funktionsprüfungen und Servicearbeiten leicht zugänglich sind. • Überlegen Sie, wie sich das entweichende Gas aufgrund von natürlichen oder erzwungenen Luftströmungen verhält. Bringen Sie gegebenenfalls Detektoren in Entlüftungsschächten an (mit Hilfe des IRmax-Detektor-Kanaleinbauadapters (siehe Abschnitt 5, Zubehör und Ersatzteile, auf Seite 72)). • Berücksichtigen Sie die Prozessbedingungen. Butan ist zum Beispiel normalerweise schwerer als Luft, wenn es jedoch aus einem Prozess entweicht, der bei erhöhter Temperatur bzw. erhöhtem Druck abläuft, kann das Gas aufsteigen, anstatt absinken. Die Platzierung von Sensoren muss mit Hilfe der Ratschläge von Experten erfolgen, die ein Spezialwissen über Gasverteilung und die Werksprozessanlagen sowie Sicherheits- und technische Fragen besitzen. Die Vereinbarung bezüglich der Standorte von Sensoren muss aufgezeichnet werden. 62 Detecting Gas Saving Lives 2. Installation 2.2 Montage Der IRmax-Detektor kann auf drei verschiedene Weisen montiert werden: 1. Mit der Crowcon Montagehalterung mit direktem Kabelanschluss (nur für Betrieb von 4-20mA). 2. Mit einer Doppelverschraubung zum Anschluss an einen vorhandenen zugelassenen Exe- oder ExdVerteilerkasten. Crowcon liefert eine geeignete Kabelstopfbüchse als optionales Extra (siehe 3 unten) 3. Mit dem optionalen Crowcon Hilfsverteilerkasten und einer Doppelverschraubung. Optionalteile sind in Abschnitt 5 auf Seite 72 aufgeführt. 2.3 Direktverkabelung an IRmax-Detektor Diese Option ist nur für den Betrieb mit 4-20 mA geeignet. Es ist eine Crowcon Montagehalterung erforderlich, um den IRmax an einer Wand oder an einem 2” (50 mm)-Rohr anzubringen.. Status-LED Signal 0V (Masse) +V (24V IRmax) Diagramm 4: Kabelanschlüsse beim IRmax Schließen Sie die Kabel mit einer zertifizierten Verschraubung über den gewählten Kabeleingang am Gehäuse des IRmax-Detektors an (M20 oder 1/2" NPT). Crowcon empfiehlt, Verschraubungen nach unten zeigend einzubauen. Achten Sie darauf, Kabelverschraubungen mit geeigneter Exd-Zulassung zu verwenden, und dass die Gewindelänge das in dem Diagramm angegebene Maß nicht überschreitet (links). 15mm MAX Detecting Gas Saving Lives 63 Deutsch Der IRmax-Detektor muss an dem vorgegebenen Standort mit der Sensortrommel horizontal +/- 15° installiert werden (Orientierung auf Diagramm 2 auf Seite 60 abgebildet). Dadurch ist gewährleistet, dass sich weder Staub noch Wasser auf den optischen Komponenten sammeln. 2. Installation 2.3.1 Anschlussbezeichnung Mit dem IRmax wie in Diagramm 2 auf Seite 60 ausgerichtet (M20 Kabel-Eingang oben) muss das dreiadrige Kabel mit Hilfe des abnehmbaren Steckverbinders wie folgt abgeschlossen werden: +24V unten, 0V in der Mitte, Signal oben. Der 6-Stift-Steckverbinder auf der rechten Seite der Leiterplatte ist für Servicearbeiten und/oder Anschluss eines IR Display-Moduls bestimmt. Plus-Anschluss: Plus-Versorgung von der Steuerkarte Signal-Anschluss: Signal von der Steuerkarte 0V-Anschluss Minus-Versorgung von der Steuerkarte Deutsch 2.3.2 Installation vom IRmax-Detektor mit einer Montagehalterung a. IRmax kann mit einer Montagehalterung (S012130) anstatt einer Doppelverschraubung geliefert werden, damit das Gerät direkt an die Kabel angeschlossen werden kann (siehe Diagramm 5). Montagehalterung: 70 mm Befestigungsabstand. M6-Schrauben verwenden. Diagramm 5: IRmax-Detektor mit Montagehalterung und Verschraubung b. Wenn der IRmax-Detektor auf einer flachen Oberfläche montiert werden soll, markieren und bohren Sie zwei Löcher mit Hilfe der Montagehalterung als Schablone. Befestigen Sie zwei Teile der Halterung lose mit für die Wand bzw. Oberfläche geeigneten Befestigungsmitteln. c. Entfernen Sie die wetterfeste Kappe vom IRmax und schieben Sie das Gehäuse des IRmax durch die Halterung. Es wird empfohlen, das Gehäuse des IRmax-Detektors mit dem Kabeleingang nach unten zeigend einzubauen. 64 Detecting Gas Saving Lives 2. Installation d. Befestigten Sie die zwei Halterungen, so dass der IRmax-Detektor fest an seinem Platz gehalten wird. Setzen Sie die wetterfeste Kappe wieder auf. e. Sobald der IRmax-Detektor sicher angebracht worden ist, nehmen Sie die rückwärtige Mutter des IRmax-Detektors ab, um den Zugang zu den Kabelanschlüssen zu ermöglichen. g. Das Halteblech (Pos. 9 in Diagramm 3, Seite 61) muss sicher montiert werden, um jede Gefahr, dass sich die hintere Mutter (oder Zubehörteil für stationäres IR Display oder IS Barrieremodul) durch Vibrationen lockert, zu vermeiden. 2.4 Installation mit Doppelverschraubung und Hilfsverteilerkasten Diese Option ist erforderlich, wenn der IRmax-Detektor an einen vorhandenen zugelassenen Exe- oder Exd-Hilfsverteilerkasten angeschlossen werden soll. Diagramm 6: IRmax-Detektor am Verteilerkasten angeschlossen Detecting Gas Saving Lives 65 Deutsch f. Bereiten Sie das Kabel vor. Crowcon empfiehlt ein stahldrahtbewehrtes (SWA) 1,5 mm2Kabel (andere Kabeltypen können unter der Voraussetzung verwendet werden, dass sie mit Exd-zugelassenen Verschraubungen kompatibel sind). Bringen Sie eine geeignete zugelassene Exd-Kabelverschraubung an, führen Sie die Kabelleiter durch das Gehäuse des IRmax-Detektors und schrauben Sie die Kabelverschraubung ein. Befestigen Sie die Verschraubung und gewährleisten Sie, dass der Kabelmantel an der Kabelverschraubung und dem IRmax-Detektor-Gehäuse geerdet ist. Hinweis: Vergessen Sie nicht, die rückwärtige Mutter nach dem Einbau des Kabels wieder anzubringen. 2. Installation 2.4.1 Anbringen des IRmax-Detektors an einem Hilfsverteilerkasten: a. Nehmen Sie vorsichtig den äußeren Bereich der Doppelverschraubung ab (Punkt 8 in Diagramm 3 auf Seite 61). b. Schrauben Sie das schmale Ende der Doppelverschraubung in den Hilfsverteilerkasten. c. Heben Sie den IRmax-Detektor auf Höhe des Hilfsverteilerkasten und führen Sie die Kabel durch die Baugruppe und in den Hilfsverteilerkasten. Befestigen Sie den IRmaxDetektor durch festes Anschrauben des Kragens an die Kabelverschraubung. Ziehen Sie die Madenschraube an. d. Das Hauptgehäuse des IRmax-Detektors kann (vorausgesetzt, es ist mechanisch sicher befestigt, stört keine andere Anlagen und ist zur Wartung zugänglich) horizontal in beliebigem Winkel geschwenkt werden. e. Anleitung zur Verkabelung siehe Abschnitt 2.6. Siehe auch Diagramm 4 auf Seite 63. Deutsch 2.5 Anforderungen an die Verkabelung Die Verkabelung des IRmax-Detektors muss gemäß der anerkannten Standards der zuständigen Aufsichtsbehörde in dem jeweiligen Land erfolgen und den elektrischen Anforderungen des IRmaxDetektors entsprechen. Crowcon empfiehlt die Verwendung von stahldrahtbewehrtem Kabel (SWA). Außerdem müssen geeignete explosionssichere Verschraubungen verwendet werden. Alternative Verkabelungsmethoden wie Stahlpanzerrohr, können zulässig sein, wenn die entsprechenden Normen erfüllt werden. Die maximale empfohlene Kabellänge beträgt 3,4 km (siehe Tabelle 1). Der IRmax-Detektor benötigt eine Gleichstromversorgung von 12-30 V DC. Achten Sie darauf, dass mindestens 12 V am IRmax-Detektor von der Steuerkonsole anliegen und berücksichtigen Sie dabei den Spannungsabfall aufgrund des Kabelwiderstands bei einer Spitzenstromstärke von 0,1 A. Ein 1,5 mm2 ermöglicht typischerweise Kabellängen von bis zu 3,0 km. Tabelle 1 unten zeigt die maximalen Kabelentfernungen bei typischen Kabelparametern. Querschnitt Widerstand Max. Entfernung >20 V Max. Entfernung 18 bis 20 V mm2 (Ohm pro km) (km) (km) 1,0 18,4 2,2 1,6 1,5 13,0 3,0 2,3 2,5 11,5 3,4 2,6 Tabelle 1: Maximale Kabelentfernung für typische Kabel 66 Detecting Gas Saving Lives 2. Installation 2.6 Verbindungen und Einstellungen Alle beschriebenen Verbindungen beziehen sich auf den Anschlussblock, der im Hauptgehäuse des IRmax-Detektor-Steckverbinders montiert ist. Die Anschlüsse der IRmax-Detektor-SteckverbinderLeiterplatte sind mit „+“, „sig“ und „0 V“ gekennzeichnet. Beim Anschluss des IRmax-Detektors an die Steueranlage muss auf die korrekte Polarität geachtet werden. Hinweis: Der externe Masseanschluss darf nur dort benutzt werden, wo lokale Behörden eine derartige Verbindung zulassen oder verlangen. Soweit möglich müssen Hilfsverteilerkasten und Kabelmantel zur Vermeidung von Hochfrequenzstörungen an der Steuerkonsole (sicherer Bereich) geerdet werden, um Erdfehlerschleifen zu verhindern. +V 0V Sg 1 2 3 Steuergerät CONTROLLER Verbindungsleitereinstellungen EARTH Verdrahtung Nummer Farbe 1 2 3 Senke Funktion Rot +V Schwarz 0V Grün Signal Quelle Stecker für das PC-Kommunikationskit Stecker für das IR Display Status-LED Diagramm 7: Lage der Senke-/Quelle-Verbindungsleiter Das 4-20 mA-Signal kann mit den in Diagramm 7 abgebildeten Stiften und Verbindungsleitern auf Strom-„Senke“ oder -„Quelle“ eingestellt werden. Durch Anbringen der Leitungsbrücke zwischen Stiften 3 und 4 wie im linken Foto gezeigt auf Strom-„Sink“ setzen. Durch Anbringen der Leitungsbrücke zwischen Stiften 1 und 2 wie im rechten Foto gezeigt auf Strom-„Source“ setzen. IRmax-Detektoren sind auf Strom-„Senke“ eingestellt, wenn dies nicht bei Bestellung anderweitig angegeben wird. LED-Anzeige: In die Anschlussleiterplatte ist eine LED eingebaut, um den aktuellen Betriebszustand anzuzeigen. Weitere Informationen siehe Abschnitt 6 auf Seite 73. Detecting Gas Saving Lives 67 Deutsch Der IRmax-Detektor ist werkseitig als „stromziehendes“ Gerät eingestellt, wenn dies bei der Bestellung nicht anderweitig angegeben wird. Um den IRmax-Detektor wieder auf „Stromquelle“ zurückzustellen, entfernen Sie die Rückplatte und setzen die beiden Verbindungsleiter an der Anschlussleiterplatte von der Position „Sink“ (Senke) auf „Source“ (Quelle), wie in Diagramm 7 dargestellt. 3. Betrieb WARNHINWEIS Vor der Ausführung aller Abeiten müssen Sie gewährleisten, dass die lokalen Bestimmungen und Standortverfahren eingehalten werden. Versuchen Sie niemals, den IRmax-Detektor oder Hilfsverteilerkasten bei Vorhandensein entflammbarer Gase zu öffnen. Gewährleisten Sie, dass die zugehörige Steuerkonsole gesperrt ist, um falschen Alarm zu verhindern. 3.1 Inbetriebnahmeverfahren 1. Prüfen Sie, dass a. die Kabelverbindungen korrekt sind Deutsch b. die Versorgungsspannung an der Steuerkarte auf 18 bis 30 V eingestellt ist. Die an den IRmax-Detektor-Anschlüssen gemessene Spannung (innerhalb des Exe-Hilfsverteilerkastens, falls verwendet, oder an der IRmax-Detektor-Anschlussleiterplatte) muss auf 12 bis 30 V eingestellt werden. c. die Verbindungsleiter sind auf 4-20 mA-Senke oder -Quelle (je nach Steuerkarte) eingestellt. 2. Sobald das Gerät hochgefahren worden ist, lassen Sie es 30 Minuten stehen, bevor Sie eine Nullstellung bzw. Kalibrierung versuchen. Diese Verzögerung dient zur Sicherstellung der thermischen Stabilität. (Hinweis: Der IRmax-Detektor ist 30 Sekunden nach dem Einschalten vollständig betriebsbereit.) 3. Stellen Sie sicher, dass saubere Luft vorliegt (d.h. kein Kohlenwasserstoffgas), bevor Sie die Nullstellung vornehmen. Nullen Sie den Messwert an der Steuerkarte (siehe Anleitung der Steuerkarte). 4. Setzen Sie die Kalibrierungskappe über die wetterfeste Abdeckung, um die Messkammer von der Umgebungsluft zu isolieren. Eine derartige Kappe ist bei Crowcon erhältlich (M041007). Schließen Sie das Kalibrierungsgas (50% UEG-Nennwert) an und beaufschlagen Sie einen Durchfluss von 1 Liter pro Minute. 5. Stellen Sie nach 30 Sekunden auf der Steuerkarte Kal/Span ein, so dass auf dem Display 50% LEL (50% UEG) erscheint oder der Anzeigewert der beaufschlagten Kalibrierungsgaskonzentration entspricht. Der IRmax-Detektor selbst benötigt keine Kalibrierung. 6. Entfernen Sie die Gas und Kalibrierungskappe. Überprüfen Sie die Nullstellung erneut. 7. Bei der Installation oder nach dem Austauschen des Spiegels kann der Detektor entweder mit Hilfe eines IR Display-Zubehörs (siehe Seite 57) oder über eine PC-Kommunikationskit auf Null gestellt und kalibriert werden.(siehe IRmax Zubehörhandbuch). Hinweis: IRmax-Detektoren mit ATEX-Zulassung werden kalibriert nach EN61779 geliefert (zum Beispiel 100% UEG Methan = 4,4 % Vol.). Hinweis: Es wird empfohlen, die Kalibrierungskappe für die erste Inbetriebnahme einzusetzen. Anschließende Kalibrierungen können durchgeführt werden, indem Gas mit der wetterfesten Kappe im Fernbetrieb über den Anschlussnippel beaufschlagt wird (und daher die Notwendigkeit des direkten Zugangs zum IRmax-Detektor entfällt). Kalibrierung ohne Kalibrierungskappe (d.h. direkt über die wetterfeste Kappe kann durchgeführt werden, wenn die lokale Windgeschwindigkeit weniger als 2 Meter/Sekunde beträgt. Der Gasdurchfluss muss größer als 2,0 Liter/Minute sein. 68 Detecting Gas Saving Lives 3. Betrieb 3.2 Routinewartung Die Frequenz, mit welcher die IRmax-Detektoren geprüft werden, wird von den am Standort üblichen Praktiken vorgeschrieben. Crowcon empfiehlt eine Gasprüfung des IRmax-Detektors und gegebenenfalls eine Neukalibrierung mindestens alle 6 Monate. Zur Neukalibrierung eines IRmaxDetektors befolgen Sie die Schritte in Abschnitt 3.1. Kalibrierungsintervall: Crowcon empfiehlt, alle 12 Monate zu kalibrieren. Fernkalibrierung über Rohr: Windgeschwindigkeit muss weniger als 2,0 Meter pro Sekunde betragen. Falls die Windgeschwindigkeit höher ist, verwenden Sie die Kalibrierungskappe, um eine Gasverdünnung zu verhindern. Reinigung der Optik: Wird nicht empfohlen, es sein denn, der IRmax-Detektor zeigt einen Verdeckungsfehler. Wenn das Fenster oder der Spiegel verschmutzt sind, reinigen Sie sie sorgfältig mit Wasser (siehe Abschnitt 5, Zubehör und Ersatzteile, auf Seite 72.). Spiegel: Bei Beschädigung wenden Sie sich für den Ersatz an Crowcon. (siehe Abschnitt 5, Zubehör und Ersatzteile, auf Seite 72.). Der IRmax-Detektor muss nach jedem Spiegelersatz neu auf Null gestellt und wieder kalibriert werden. Falls Kondensation beginnt, zu Fehlern zu führen, ersetzen Sie den Spiegel (es kann sein, dass die optische Beschichtung beschädigt ist). Crowcon empfiehlt, den Spiegel alle 5 Jahre zu erneuern. 3.3 Ändern der Gasart Jeder IRmax-Detektor wird für einen bestimmten Gastyp vorkalibriert geliefert (zum Beispiel Methan oder Propan). Wenn eine Neukalibrierung für einen anderen Gastyp erforderlich ist, kann der IRmax mit dem PC-Kommunikationskit (siehe Abschnitt 5, Zubehör und Ersatzteile, auf Seite 72.), neu konfiguriert und dann kalibriert werden. Detecting Gas Saving Lives 69 Deutsch Im Fall eines elektronischen Versagens wenden Sie sich bitte an Ihren lokalen Crowcon-Vertreter. 3. Betrieb 3.4 Relatives Ansprechen auf Gasarten Der unten abgebildete Graph zeigt das relative Ansprechen auf andere Gastypen für einen auf Methan kalibrierten IRmax-Detektor. Hinweis: Viele Kohlenwasserstoffgase und -dämpfe werden von IR-Detektoren einfacher als Methan gemessen. Die Reaktion des IRmax (und anderer IR-Gasdetektoren) ist linear über den Bereich 0-100% UEG für das Zielgas (d. h. in diesem Beispiel Methan), jedoch nicht linear für andere Kohlenwasserstoffe, die vorhanden sein könnten. Deutsch Diagramm 8 Das Diagramm zeigt das Ansprechen auf die oben erwähnten Gase: von links nach rechts, Ethan, Propan, Butan, Pentan und Methan. Andere Gasarten und –bereiche sind verfügbar. Weitere Einzelheiten erhalten Sie von Crowcon. 70 Detecting Gas Saving Lives Gehäusematerial Edelstahl 316 Abmessungen (nur IRmax-Detektor) 150 mm x 75 mm x 66 mm (ohne Zapfen) Gewicht IRmax 1,58 kg IRmax mit permanentem IR Display 2 kg IRmax mit IS-Barrieremodul 2,4 kg Fern-IR Display 0,2 k Betriebsspannung 12 VDC bis 30 VDC Stromverbrauch <1W Ausgang 3-adrig 4-20 mA (Senke oder Quelle) Fehlersignal <1 mA Max. Kabelschleifenwiderstand 80 Ohm (bezogen auf -ve-Klemme) Betriebstemperatur -40°C bis +75°C (-40°F bis +167°F) Luftfeuchtigkeit 0–100% relative Luftfeuchtigkeit Schutzklasse IP66 Explosionsschutz Flammensicher Zulassungscode ATEX IRmax-Detektor (ohne IR Display) II 2 GD Exd db IIC T6 Gb (Tamb = -40°C bis +50°C) II 2 GD Exd db IIC T4 Gb (Tamb = -40°C bis +75°C) II 2 GD Ex tb IIIC T135°C Db (-40°C ≤ Ta≤ +75°C) IRmax mit IS Barrieremodul (Fernbedienungsdisplay) II 2 GD Exd db ia IIC T4 Gb (Tamb = -40°C bis +75°C) Ex tb ia IIIC T135°C Db (Tamb = -40°C bis +40°C) IRmax mit stationärem IR Display II 2 G Exd db ia IIC T4 Gb (Tamb = -40°C bis +75°C) Sicherheitszertifikat Nr. ATEX und IECEx IRmax-Detektor (ohne IR Display): Baseefa 09ATEX0206X und IECEx BAS.09.0109X IRmax-Detektor (mit IR Display): Baseefa 09ATEX0220X und IECEx BAS.09.0104X Funktionale Sicherheit Zum Einsatz in einem SIL-2-System zertifiziert. Zertifikatnummer: Sira 12ATEX1206X Normen EN 60079-0:2012+A11:2013, EN 60079-1:2014, EN 60079-31:2014 IEC 60079-0:2011, IEC 60079-1:2014, IEC 60079-31:2013 EN 60079-29-1:2007, IEC 61508:2010, EN50402:2005 Zonen Für die Verwendung in Zone 1 oder Zone 2 zugelassen EMC EN50270 Detecting Gas Saving Lives 71 Deutsch 4. Technische Daten 5. Zubehör und Ersatzteile Name Beschreibung M041007 Kalibrierungskappe Passt über die wetterfeste Standardkappe, um die Kalibrierung zu ermöglichen, wenn die lokale Luftgeschwindigkeit mehr als 2 Meter pro Sekunde beträgt. S012130 Montagehalterungs-Kit Ermöglicht die Montage an einer Wand oder einem 2” (50 mm)-Rohr. Nicht erforderlich, falls der IRmax-Detektor an einem vorhandenen Verteilerkasten angebracht wird. S012152 Sonnenschutz/ Kollektorkegel Kann am IRmax-Detektor angebracht werden, um das Gerät vor erhöhten Temperaturen durch direkte Sonneneinstrahlung zu schützen und/oder den Empfangsbereich des Detektors für den Nachweis von Gasen zu erweitern, die leichter als Luft sind (Methan). S012169 Kanaleinbauadapter Ermöglicht die Überwachung von Kanälen mit einer Größe von 300 mm bis 3000 mm und einer Luftgeschwindigkeit von 2 m/s bis 20 m/s. S012996 Strömungsadapter Für Gasprobenentnahmeanwendungen. S012827 PC-Kommunikationskit Kommunikationsmodul, Software und Kabel für die Konfiguration des IRmaxDetektors. M20: S012295 ½” NPT: S012296 Hilfsverteilerkasten Montageoption für IRmax zur Verwendung in Gefahrenbereichen. C011210 Spiegelreinigungs-Kit Enthält mit Isopropanol imprägnierte Wischtücher und Mikrofasertuch Deutsch Teilenummer IRmax-Detektor-Ersatzteile Einzelheiten zu Ersatzteilen siehe Diagramm 3 auf Seite 61. 72 Detecting Gas Saving Lives 6. Fehlerbehebung 6.1 Von der LED angezeigte Fehler Die an der Terminalplatine montierte LED kann bei der Identifikation von Fehlern helfen. Ihre Position ist auf Diagramm 7 auf Seite 67 dargestellt. Die Tabelle unten zeigt, wie interpretiert wird, welchen Fehler jedes Blinkmuster angibt. IRmax-Detektor-Status Blinkt regelmäßig einmal pro Sekunde. Intakt. Maßnahme Leuchtet durchgehend mit kurzen Unterbrechungen. IRmax-Detektor im Hochfahrmodus. 10 Sekunden warten. Schnelles Blinken oder unregelmäßiges Blinkmuster. Versorgungsspannung zu niedrig oder zu hoch. Stellen Sie sicher, dass die Versorgungsspannung des IRmax-Detektors richtig eingestellt ist. Gewährleisten Sie, dass die Messung direkt an den IRmax-DetektorAnschlüssen erfolgt. Leuchtet dauerhaft. Fehler, Host- oder I-Modul-Fehler. Schalten Sie den IRmax-Detektor aus und wieder ein. Falls der Fehler immer noch vorliegt, senden Sie das Gerät an Crowcon ein. Zweimaliges langes Blinken gefolgt von einem kurzen Blinken. Fataler Fehler, Leuchtenoder Detektorfehler. Senden Sie das Gerät an Crowcon zurück. Schnelles Doppelblinken jede Sekunde. Fataler Fehler, Modul- oder Konfigurationsfehler. Prüfen Sie die Detektorkonfiguration mit Hilfe der PC-KommunikationskitSoftware. Prüfen Sie die Stromversorgung. Falls der Fehler immer noch vorliegt, senden Sie das Gerät an Crowcon. Blinkt einmal pro Sekunde kurz auf. Optik verschmutzt. Fenster und Spiegel prüfen und gegebenenfalls reinigen. Detektor erneut auf Null stellen und Kalibrierung prüfen. Alle anderen Fehler können nur korrigiert werden, indem der IRmax-Detektor an Crowcon oder einen autorisierten Kundendienstvertreter eingesendet wird. 6.2 Analogausgang IRmax wird im Fehlerstatus bleiben und es wird außerdem „Service erforderlich“ (Service required) auf dem IR Display (falls vorhanden) angezeigt, wenn das Analogausgang-Signal ausgefallen oder nicht mit einem Steuersystem oder Lastwiderstand verbunden ist. IRmax überwacht das 4-20 mA-Analogausgang-Signal aktiv, um sicherzustellen, dass es sich im zulässigen Bereich befindet. Wenn das Signal außerhalb des Bereichs liegt, geht der Detektor in den Fehlerzustand über und der Ausgang wird auf 1 mA gestellt. Daher ist es beim Testen eines Detektors wesentlich, dass er entweder mit einer Steuerkonsole verbunden wird oder ein 100 Ω-Lastwiderstand zwischen den „0 V“ und „Sig“Anschlüssen (Detektor auf Modus „Quelle“ gestellt) oder zwischen den „0 V“ und „+V“-Anschlüssen (Detektor auf Modus „Senke“ gestellt) angeschlossen wird. Detecting Gas Saving Lives 73 Deutsch LED-Muster 7. RS485-Modbuskonfiguration 7.1 Allgemeines Dieser Abschnitt erklärt, wie IRmax-Detektoren in einer Modbus-Konfiguration verwendet werden. Für solche Anwendungen ist eine RS485-Version erhältlich. Es können bis zu 28 Detektoren in einer Sternoder Bus-Konfiguration wie unten beschrieben miteinander verbunden werden. Der Anschluss an die RS465-Version des IRmax-Detektors muss über eine Doppelverschraubung an einen Hilfsverteilerkasten erfolgen (siehe Abschnitt 5 auf Seite 72.), anstatt über Direktverkabelung in den IRmax-Detektor. Bitte beachten Sie, dass das IR Display nicht mit dem RS485-IRmax benutzt werden kann. Die RS-485-Version des IRmax-Detektors hat fünf Feldanschlüsse. Die Anschlüsse sind: Deutsch 1 Positive Versorgung 12 V bis 30 V über 0 V 2 0V Rückleitung und RS-485-Referenz 3 4-20 mA-Signal Quellen- oder Senkensignal (optional) 4 RS485 B RS485-Differenzialsignal 5 RS485 A RS485-Differenzialsignal Die Signale an den RS-485-Anschlüssen entsprechen der EIA/TIA-485-Norm, die besagt, dass der Gleichtaktbereich bezüglich des 0V-Anschlusses von –7V bis +12V reicht. Beachten Sie, dass sich nicht alle RS-485-Hersteller über die Polarität der A- und B-Signale einig sind. Wenn die Verkabelung nicht auf die eine Weise funktioniert, müssen die Anwender die RS-485-A- und -B-Kabel vertauschen. Es besteht kein Risiko darin, eine falsche Verbindung herzustellen. Die Kommunikationseinstellungen sind 9600 bps, zwei Stopp-Bits und keine Parität. Wenn eine Schnittstelle für ein Steuersystem kompiliert wird, ist es wesentlich, die Zeitspanne zu berücksichtigen, die das System benötigt, um nacheinander Informationen von jedem Detektor zu sammeln. Die schnellste Geschwindigkeit, mit der mehrere Detektoren zyklisch abgefragt werden können, beträgt 14 Detektoren pro Sekunde. Unter praktischen Umständen kann sich dieser Wert auf 7 Detektoren pro Sekunde reduzieren. Anwender müssen gewährleisten, dass die Anordnung erlaubt, dass Alarmsignale innerhalb zulässiger Zeitgrenzen registriert werden. Es ist außerdem wichtig sicherzustellen, dass das System ausreichend Leistung bereitstellen kann, damit alle Detektoren funktionieren können. Zur Berechnung der erforderlichen Leistung bei einer linearen Busverbindung, siehe Abschnitt 7.3, Anforderungen an die Verkabelung, auf Seite 76. Die vollständige Modbus-Anleitung erhalten Sie von Crowcon (siehe Anschrift auf der Rückseite). 74 Detecting Gas Saving Lives 7. RS485 Modbus configuration 7.2 Verkabelungstopologie Zwei häufig verwendete Verkabelungstopologien sind die Sternverbindung und der lineare Bus. 7.2.1 Sternverbindung Bei einer Sternverbindungstopologie sind alle IRmax-Detektoren mit einem zentralen Punkt verkabelt, der normalerweise die Steuerkonsole ist. Es sind keine Kabel erforderlich, um mehr als 5 Kerne zu haben, da alle 4-20 mA-Signalverbindungen direkt zur Steuerkonsole geführt werden. Die RS-485-A- und -B-Signale können dann alle im Sternpunkt miteinander verbunden werden. Der Bus muss anschließend im Sternpunkt mit einem einzelnen 110 Ohm-Abschlusswiderstand beendet werden. 7.2.2 Lineare Busverbindung Bei einer Busverbindungstopologie sind alle IRmax-Detektoren in einer linearen Anordnung verkabelt, normalerweise mit der Steuerkonsole an einem Ende. Eine klassische Situation ist eine Tunnelinstallation mit Detektoren, mit IRmax in regelmäßigen Abständen montiert (siehe Diagramm 9 unten). Zur Verkabelung der Installation müssen zwei 110 Ohm-Abschlusswiderstände an jedem physikalischen Ende des Busses angebracht werden. Da die 4-20 mA-Signale nicht gemeinsam genutzt werden können, ist an jedem Verkabelungs-Hop ein zusätzlicher Leiter erforderlich. Falls keines der 4-20 mA-Signale verwendet wird, sind nur vier Leiter erforderlich. LINEARES BUSVERBINDUNGS-DIAGRAMM ZUR STEUERKONSOLE Diagramm 9 Detecting Gas Saving Lives 75 Deutsch Die Länge jedes Sternarms darf 750 Meter nicht überschreiten. 7. RS485 Modbus configuration 7.3 Anforderungen an die Verkabelung 7.3.1 Berechnung der erforderlichen Mindestleistung Je mehr IRmax-Detektoren an einen linearen Bus angeschlossen werden, um so mehr Leistung ist für den Betrieb des Systems erforderlich. Zur Berechnung der für eine bestimmte Anordnung erforderlich Leistung muss der Kabelwiderstand zwischen jedem IRmax-Detektor-Paar bekannt sein. Für jeden „Hop“ zwischen den IRmax-Detektoren muss eine Stromstärke von mindestens 0,1 mA erlaubt sein. Die anzulegende Spannung kann durch Schätzung des Spannungsabfalls über jeden „Hop“ berechnete werden. Am Ende müssen mindestens 12 V übrig bleiben, um zu gewährleisten, dass der letzte IRmaxDetektor korrekt funktioniert. Ratschläge in speziellen Fällen erhalten Sie bei Crowcon. Alternativ befolgen Sie die unten beschriebenen Schritte und die Beispielberechnung im nächsten Abschnitt. Deutsch 1. Die Spannung darf nicht unter 12 V fallen. Deshalb beginnen Sie die Berechnung, indem Sie die Spannung am letzten IRmax-Detektor in der Reihe auf diesen Wert setzen. 2. Jeder IRmax-Detektor darf bis zu 0,1 A ziehen. Berechnen Sie den Kabelspannungsverlust des ersten „Hop“ zwischen den IRmax-Detektoren, indem Sie die „akkumulierte Stromstärke“ als 0,1 A annehmen und diesen Wert mit dem Kabelwiderstand des „Hop“ zwischen dem letzten und vorletzten Detektor multiplizieren 3. Addieren Sie diesen Spannungsverlust zu den anfänglichen 12 V, um die niedrigste zulässige Spannung am vorletzten IRmax-Detektor zu erhalten. Addieren Sie 0,1 A zu dem Wert für die „akkumulierte Stromstärke“, um 0,2 mA zu erhalten, die Mindeststromstärke, die durch den vorletzten „Hop“ des Busses laufen muss. Multiplizieren Sie diesen Wert mit dem Kabelwiderstand für den vorletzten „Hop“, um den nächsten Spannungsabfall zu erhalten. 4. Wiederholen Sie diesen Vorgang für jeden Detektor und addieren Sie die Spannungsverluste, die zwischen jedem Detektorpaar auftreten werden. 5. Die maximale Detektorspannung von 30 V darf nicht überschritten werden. 7.3.2 Beispielberechnung Als Beispiel folgen die Ergebnisse der Berechnung für sechs IRmax-Detektoren in gleichem Abstand von 250 m und mit einem Kabel einer Querschnittsfläche von 1 mm2 verbunden. Jeder „Hop“ hat einen Widerstand von 4,6 Ohm. Station Versorgungs-spannung Versorgungs-stromstärke 1 12 0,1 A 2 12,46 0,2 A 3 13,38 0,3 A 4 14,76 0,4 A 5 16,6 0,5 A 6 18,9 0,6 A Konsolen-versorgung 21,66 0,6 A 76 Detecting Gas Saving Lives 8. Handbuch für funktionale Sicherheit 8.1 Einführung Die folgenden Abschnitte enthalten genauere Angaben zu der Zertifizierung des IRmax gemäß den Normen für funktionale Sicherheit IEC 61508 und EN 50402. Informationen werden zu den Funktionen, die im Sicherheitsfall berücksichtigt werden, zu Wartungsanforderungen und Daten gegeben, um die Integration des IRmax in ein sicherheitstechnisches System (SIS) zu ermöglichen. 8.2 IRmax und IRmax Modbus Sicherheitsfunktion Fehler im Hinblick auf die Sicherheitsfunktion werden von der Hardware und zugehöriger Firmware erkannt. Sie werden als Ausgangssignal unter 3,6 mA oder über 21 mA gezeigt. 8.3 Daten zur funktionalen Sicherheit Parameterbezeichnung Intervall von Wiederholungsprüfungen Mittlere Reparaturzeit MTTR Symbol Gleichung/Quelle T1 Nach Festlegung von Crowcon. MTTR Nach Festlegung von Crowcon. IRmax 8.760 Stunden (jährlich) 8 Stunden Typ A/B Typ A Nach Festlegung von Crowcon. Typ B Gesamtausfälle: λ Aus FMEDA 1.04E-05 Entdeckte ungefährliche Ausfälle: λSD Aus FMEDA 1.95E-08 Unentdeckte ungefährliche Ausfälle: λSU Aus FMEDA 8.59E-08 Entdeckte gefahrbringende Ausfälle: λDD Aus FMEDA 9.74E-06 Unentdeckte gefahrbringende Ausfälle: λDU Aus FMEDA 5.06E-07 Ungefährliche Ausfälle: λNE Aus FMEDA 3.21E-09 Diagnosedeckungsgrad: DC λDD / (λDU + λDD) 95.06% Anteil ungefährlicher Ausfälle (SFF): SFF 95.11% Kanaläquivalente Ausfallzeit tCE (λSD + λSU + λDD) / λ (λDU / λD)(T/2 + MTTR) + (λDD / λD ) MTTR 2.24E+02 PFDAVG (anhand Gleichung aus PFDAVG (λDU + λDD) tCE 2.30E-03 61508-6) PFDAVG (anhand vereinfachter PFDAVG λDU (T / 2+MTTR) + (λDD MTTR) 2.30E-03 Gleichung) PFDAVG (anhand Gleichung aus IEC -(λdd+λdu) tce PFDAVG 1-ε 2.30E-03 61508-6) SIL (Betriebsart mit niedriger SIL2 Anforderungsrate) SIL (Betriebsart mit hoher SIL2 Anforderungsrate) Bei Anwendungen mit niedriger Anforderungsrate sind im Hinblick auf zufällige Hardwarefehler und den Anteil ungefährlicher Ausfälle alle Varianten des Systems für den Einsatz in SIL-2Anwendungen geeignet. Detecting Gas Saving Lives 77 Deutsch Messung der Konzentration eines brennbaren Gases und Anzeige der Messung über einen 4-20-mA-Ausgang. Handbuch für funktionale Sicherheit 8.4 Hardwarekonfiguration Weg 1H (Hardwarefehlertoleranz und Anteil ungefährlicher Ausfälle) wurde zur Beurteilung des Safety Integrity Level der Hardware verwendet. 8.5 Softwarekonfiguration Die Beurteilung der Produktfirmware erfolgte gemäß den Anforderungen aus IEC 61508:3 2010. 8.6 Systematische Ausfälle Weg 1S (laut Festlegung in IEC 61508:2 2010 Absatz 7.4.2.2c) wird zur Prüfung der Einhaltung der Anforderungen zur Vermeidung systematischer Ausfälle verwendet. Deutsch 8.7 Diagnoseintervall Die meisten Diagnosefunktionen werden kontinuierlich überwacht. Tests des System-Watchdog sind während der jährlichen Wiederholungsprüfung durch Aus- und Einschalten des Geräts durchzuführen. IRmax muss als Teil des Wartungsprogramms für das Produkt jährlich aus- und eingeschaltet werden (d. h. die 24-Vdc-Versorgung trennen und wieder anlegen) (siehe auch Abschnitt 3.2). 8.8 Beschränkungen Ausfallraten sind konstant. Eine Wiederholungsprüfung, die mindestens einmal pro Jahr durchgeführt wird, identifiziert alle nicht gefundenen Fehler. Reparaturen haben eine mittlere Reparaturzeit von 8 Stunden. Es wird davon ausgegangen, dass der Benutzer die Diagnosefunktion nutzt, die über das IR DisplayZubehör und/oder die PC-Schnittstelle bereitgestellt wird, um die mögliche Ausfallzeit des Produkts zu minimieren. Die Zuverlässigkeitsbeurteilung ist ein statistischer Prozess zur Anwendung historischer Ausfalldaten auf geplante Konstruktionen und Konfigurationen. Es bietet daher einen voraussichtlichen Soll-/ Schätzwert der wahrscheinlichen Zuverlässigkeit von Geräten unter der Annahme, dass Herstellungs-, Konstruktions- und Betriebsbedingungen identisch mit denen sind, unter denen die Daten erfasst wurden. Es ist ein wertvolles Verfahren der Konstruktionsüberprüfung zum Vergleich alternativer Konstruktionen, zur Ermittlung von Leistungszielen im Hinblick auf die Größenordnung und zur Auswertung der möglichen Einflüsse von Konstruktionsänderungen. Die tatsächlich vorhergesagten Werte können jedoch nicht garantiert werden, da die Prognose der genauen Zahl von Ausfällen im Feld, die auftreten werden, nicht möglich ist, da dies von Faktoren abhängt, die außerhalb der Kontrolle einer prädiktiven Prüfung liegen. Ausfallraten (Symbol λ) werden zum Zwecke dieser Vorhersage als im Zeitverlauf konstant angenommen. Sowohl frühzeitige Ausfälle als auch verschleißbezogene Ausfälle senken die Zuverlässigkeit, es wird jedoch davon ausgegangen, dass sie durch Burn-in bzw. vorbeugenden Austausch vermieden werden. 78 Detecting Gas Saving Lives Handbuch für funktionale Sicherheit Die Wahrscheinlichkeit eines Ausfalls im Anforderungsfall PFD ist die Wahrscheinlichkeit, dass das System in einem zufälligen Moment einen Fehlerzustand aufweist. Dies ist synonym mit der stationären Nichtverfügbarkeit. Diese wird gegeben durch: Nichtverfügbarkeit = (λ x MDT)/(1 + (λ x MDT)) die bei kleinen Werten von λ x MDT ungefähr gleich λ x MDT ist wobei λ die Ausfallrate und MDT die mittlere Ausfallzeit ist. Dies stimmt mit dem Ausdruck für Verfügbarkeit überein. Diese wird gegeben als: MTBF/(MTBF+MDT) 8.9 Umgebungsbedingungen Umgebungsbeschränkungen: Das Produkt darf in einem maximalen Umgebungstemperaturbereich von -40 °C bis +75 °C betrieben werden. Das Produkt darf in einem maximalen Umgebungstemperaturbereich von -40 °C bis +80 °C gelagert werden. Das Produkt darf in einem maximalen relativen Luftfeuchtigkeitsbereich der Umgebung von 0 % bis +100 % bei Kondensation betrieben werden. Das Produkt besitzt gemäß den Festlegungen der Norm EN 60529 eine Schutzart von IP66. Das Produkt ist für Dauerbetrieb ausgelegt. 8.10 Hardwarefehlertoleranz Die HFT ist 0. 8.11 Systematische Eignung Der IREX/IRmax hat Klasse SC2. 8.12 Klassifizierung Der IREX/IRmax ist ein Typ-B-Gerät. Detecting Gas Saving Lives 79 Deutsch Die verwendeten Ausfallraten und die so abgeleiteten Verfügbarkeiten sind die Werte, die zuverlässig nach einer geeigneten Zeitdauer mit Zuverlässigkeitswachstum mit einer bewährten Konstruktion verbunden sind. Garantie Dieses Gerät hat unser Werk vollständig geprüft und kalibriert verlassen. Wenn innerhalb der Garantiezeit von drei Jahren nach Versand nachgewiesen wird, dass das Gerät aufgrund von fehlerhafter Ausführung oder fehlerhaftem Material defekt ist, reparieren oder ersetzen wir das Gerät nach unserem Ermessen kostenlos unter den unten genannten Bedingungen. Garantieverfahren Um die effiziente Verarbeitung aller Ansprüche zu erleichtern, kontaktieren Sie bitte unser Kundendienstteam unter der Telefonnummer +44 (0)1235 557711 mit den folgenden Informationen: Name, Telefonnummer, Faxnummer und E-Mail-Adresse Ihres Kontakts. Beschreibung und Menge der zurückgesendeten Waren einschließlich allen Zubehörs. Seriennummer(n) der Geräte. Deutsch Grund für die Rücksendung. Besorgen Sie sich ein Rücksendeformular zu Identifikations- und Nachverfolgbarkeitszwecken. Dieses Formular kann von unserer Website crowconsupport.com zusammen mit einem Rücksendeetikett heruntergeladen werden. Alternativ können wir Ihnen eine Kopie per E-Mail zusenden. Es werden nur IRmax-Detektoren mit einer Crowcon Rücksendenummer (CRN) zur Garantie angenommen. Es ist wesentlich, dass das Anschriftsetikett sicher an der Außenverpackung der zurückgesendeten Waren befestigt wird. Die Garantie erlischt, wenn das Gerät verändert, modifiziert, zerlegt worden ist oder anderweitige unbefugte Eingriffe vorgenommen worden sind. Die Garantie beinhaltet weder falsche Benutzung noch Missbrauch des Geräts. Garantieausschluss Crowcon übernimmt keine Haftung für Folgeschäden oder indirekte Verluste oder Schäden aus beliebigem Grund (einschließlich aller Verluste oder Schäden, die aus der Benutzung des Geräts entstehen) und es wird ausdrücklich jegliche Haftung bezüglich dritter Parteien ausgeschlossen. Diese Garantie bezieht sich nicht auf die Genauigkeit der Kalibrierung des Geräts oder das kosmetische Aussehen des Produkts. Das Gerät muss in Übereinstimmung mit den Betriebs- und Wartungsanweisungen unterhalten und gewartet werden. Die Garantie über den Ersatz von Verbrauchsmaterialien (wie dem Spiegel), die im Rahmen der Garantie für den Ersatz fehlerhafter Artikel geliefert werden, ist auf die nicht abgelaufene Garantie des Originalartikels beschränkt. Crowcon behält sich das Recht vor, eine reduzierte Garantiezeit festzulegen oder eine Garantiezeit für alle Sensoren abzulehnen, die zur Verwendung in einer Umgebung oder für eine Anwendung geliefert worden sind, die bekanntermaßen ein Risiko der Verschlechterung oder Beschädigung des Sensors beinhaltet. Unsere Haftung bezüglich defekter Anlagen beschränkt sich auf die in der Garantie enthaltenen Verpflichtungen und alle erweiterten Garantien, Bedingungen oder Erklärungen, ausdrücklich oder implizit, gesetzlich vorgeschrieben oder sonstiger Art bezüglich der marktüblichen Qualität unserer Anlage oder ihrer Eignung für einen bestimmten Zweck sind (ausgenommen wie gesetzlich vorgeschrieben) ausgeschlossen. Diese Garantie beeinträchtigt nicht die gesetzlichen Rechte eines Kunden. 80 Detecting Gas Saving Lives Garantie Crowcon behält sich das Recht vor, eine Bearbeitungs- und Frachtgebühr zu berechnen, wenn als fehlerhaft eingesendete Geräte nur eine normale Kalibrierung oder einen Kundendienst erfordern, deren Durchführung der Kunde dann ablehnt. Bei Fragen zur Garantie und technischem Support wenden Sie sich bitte an: Kundendienst Tel: +44 (0) 1235 557711 Fax: +44 (0) 1235 557722 Deutsch Email: [email protected] Detecting Gas Saving Lives 81 Índice Concepto y seguridad................................................................................. 85 Concepto de detector IRmax .............................................................. 85 Información de seguridad..................................................................... 86 Descripción del producto...................................................................... 87 1. Introducción............................................................................................ 88 1.1 General.......................................................................................... 88 1.2 Descripción del producto............................................................... 88 2. Instalación............................................................................................... 90 ADVERTENCIA...................................................................................... 90 2.1 Ubicación ...................................................................................... 90 2.2 Montaje ........................................................................................ 91 2.3 Cableado directo al detector IRmax ............................................. 91 2.3.1 Designación de terminal........................................................ 92 2.3.2 Instalación del detector IRmax utilizando un soporte de montaje ... 92 2.4 Instalación utilizando un pasacables de espiga y una caja de conexiones auxiliar............................................................................... 93 2.4.1 Para instalar el detector IRmax en una caja de conexiones auxiliar:.......................................................................................... 94 2.5 Requisitos de cableado .................................................................. 94 2.6 Conexiones y ajustes ..................................................................... 95 3. Funcionamiento....................................................................................... 96 3.1 Procedimiento de puesta en servicio ............................................. 96 3.2 Mantenimiento rutinario ............................................................... 97 3.3 Cambio de tipos de gas ................................................................ 97 3.4 Respuestas relativas de tipos de gas .............................................. 98 4. Especificaciones....................................................................................... 99 5. Accesorios y repuestos ......................................................................... 100 6. Detección de errores............................................................................ 101 6.1 Errores indicados por LED............................................................. 101 6.2 Salida analógica........................................................................... 101 7. Configuración de RS485 Modbus ......................................................... 102 7.1 General........................................................................................ 102 7.2 Topología del cableado ............................................................... 103 7.2.1 Conexión en estrella ........................................................... 103 7.2.2 Conexión de bus lineal ....................................................... 103 7.3 Requisitos de cableado ................................................................ 104 7.3.1 Cálculo del nivel mínimo de potencia requerida................... 104 7.3.2 Cálculo de muestra ............................................................ 104 8. Manual de seguridad funcional............................................................. 105 8.1 Prólogo........................................................................................ 105 8.2 Función de seguridad del IRmax y del IRmax Modbus.................. 105 8.3 Datos de seguridad funcional....................................................... 105 8.4 Configuración de hardware......................................................... 106 8.5 Configuración de software........................................................... 106 8.6 Fallos sistemáticos........................................................................ 106 8.7 Intervalo de diagnósticos.............................................................. 106 8.8 Restricciones................................................................................ 106 8.9 Medio ambiente........................................................................... 107 8.10 Tolerancia de fallo de hardware................................................. 107 8.11 Capacidad sistemática................................................................ 107 8.12 Clasificación............................................................................... 107 Garantía.................................................................................................... 108 Concepto y seguridad Concepto de detector IRmax El detector IRmax es un detector de gases por infrarrojos (IR) ultracompacto que proporciona detección rápida y fiable de gases y vapores de hidrocarburos. Incorporando tecnología de sensor por infrarrojos de longitud de onda doble en una resistente cubierta de acero inoxidable 316, el detector IRmax está diseñado para funcionar en las condiciones más duras. A diferencia de detectores de gas por infrarrojos convencionales, el detector IRmax no incorpora calentadores para prevenir la condensación en ventanas y espejos. El revestimiento STAY CLIR de los componentes ópticos previene la formación de condensación mientras el detector está funcionando. El detector IRmax es compatible con cualquier sistema de control de 4-20mA y también puede instalarse en una red direccionable Modbus RS485 (véase Sección 7). El detector IRmax requiere sólo 1 W de potencia, típicamente 75-90% menos que los detectores de gas por infrarrojos convencionales. La IR Display permite monitorizar lecturas del IRmax tanto localmente como remotamente. Es posible instalar directamente una IR Display en el IRmax. De forma alternativa, la IRmax puede suministrarse con un módulo de barrera intrínsecamente segura (IS) instalado. Entonces una IR Display puede conectarse al módulo de barrera IS mediante un cableado temporal o permanente. Las opciones disponibles se ilustran en el Diagrama 3 en la página 89. Para obtener información adicional sobre otros accesorios para el IRmax, véase la Diagrama 3, página 89 y la Sección 5, página 100. Detecting Gas Saving Lives 85 Español El detector IRmax incorpora una cámara compacta de difusión de gas, que combinada con una eficaz tapa impermeable proporciona una velocidad de respuesta excelente. La tapa impermeable ha sido diseñada utilizando software de modelización de flujo para permitir la gasificación y calibración del detector sin necesidad de una tapa de calibración especial. Concepto y seguridad Información de seguridad • Los detectores de gas IRmax deben instalarse, utilizarse y mantenerse siguiendo rigurosamente estas instrucciones, advertencias e información de etiquetas y dentro de los límites indicados. • La tuerca trasera del detector IRmax debe mantenerse bien apretada durante su funcionamiento. No intente retirar la tuerca trasera hasta que se haya desconectado la corriente del detector - en caso contrario puede producirse el encendido de un entorno inflamable. Antes de retirar la tuerca para realizar mantenimiento, calibración o servicio, compruebe que en el entorno no hay gases o vapores inflamables. No lo abra hasta varios minutos después de que se haya desconectado la corriente. • Las operaciones de mantenimiento y calibración sólo deben ser realizadas por personal de servicio cualificado. • Sólo deben utilizarse piezas de repuesto auténticas de Crowcon; otros componentes pueden invalidar la certificación y la garantía del detector IRmax. • Los detectores IRmax deben ser protegidos contra vibraciones extremas y los rayos directos del sol en entornos calientes ya que esto puede causar que la temperatura del detector IRmax supere los limítes especificados y cause un fallo prematuro. • El detector IRmax no detecta hidrógeno, amoníaco o dióxido de carbono. • El equipo debe conectarse a tierra utilizando el pasacables y el cable blindado de acero. Español • Certificación para entornos de polvo Zona 21/22: El IRmax básico (sin IR Display o su módulo de barrera IS) puede utilizarse en entornos que pueden contener polvos peligrosos (Zonas 21 ó 22). • El IRmax con un módulo de barrera IS puede utilizarse en Zonas 21 ó 22 siempre y cuando la temperatura ambiente permanezca por debajo de 40°C y se instale/utilice una IR Display remota o varias IR Display manuales fuera del área peligrosa solamente. • No puede instalarse un IRmax con una IR Display fija en un área de Zona 21 ó 22. 86 Detecting Gas Saving Lives Concepto y seguridad Descripción del producto El detector IRmax es un detector de gas por infrarrojos diseñado para detectar gases de hidrocarburos comunes dentro de la gama de 0 a 100% de LEL (Lower Explosive Limit - Límite explosivo inferior: la concentración mínima en aire a la que puede ocurrir inflamación). El detector IRmax es un detector antideflagrante (Exd) certificado adecuado para utilizarse en zonas peligrosas Zona 1 ó Zona 2 ATEX . Consulte la etiqueta de certificación en el lateral del detector para identificar el tipo de certificación relacionada con el producto suministrado. Nota: Si el detector IRmax no incorpora una etiqueta de certificación, el detector no está certificado para uso en áreas peligrosas. IR GAS DE TECTOR 1180 IR GAS DETECTOR WITH REMOTE DISPLAY II 2 GD 1180 V m ax= 32V W m ax= 5W II 2GD Vmax=32V Wmax=5W B a s e e fa 0 9 A T E X 0 2 0 6 X IE C E x B A S 0 9 . 0 1 0 9 X S IL 2 S i r a 1 2 A T E X 1 2 0 6 X Baseefa09ATEX0220X IECEx BAS 09.0104X Ex db ia IIC T4 Gb (-40°C ≤ Ta ≤ +75°C) Ex tb ia IIIC T135°C Db (-40°C ≤ Ta ≤ +40°C) E x d b II C T 4 Gb (T am b = -40 °C to + 75 °C ) E x d b II C T 6 Gb (T am b = -40 °C to + 50 °C ) E x tb II IC T 135° C D b (-4 0° C T a + 75° C ) WARNING: DO NOT OPEN WHEN EXPLOSIVE ATMOSPHERE MAY BE PRESENT. A b i n g d o n , U nit e d K in g d o m , O X 1 4 4 S D Abingdon, United Kingdom, OX14 4SD Etiqueta de certificación de IRmax básico IRmax con su etiqueta de certificación de barrera IR GAS DETECTOR WITH DISPLAY 1180 II 2G Baseefa09ATEX0220X IECEx BAS 09.0104X Vmax=32V Wmax=5W Ex db ia IIC T4 Gb (-40°C Ta +75°C) WARNING: DO NOT OPEN WHEN EXPLOSIVE ATMOSPHERE MAY BE PRESENT. Abingdon, United Kingdom, OX14 4SD IRmax con etiqueta de certificación de IR Display fija Diagrama 1: Etiquetas de certificación del detector IRmax Detecting Gas Saving Lives 87 Español W A R N IN G : D O N O T O P E N W H E N E X P L O S IV E A TM O S P H E R E M A Y B E P R E S E N T. 1. Introducción 1.1 General La configuración de cada IRmax se identifica por una etiqueta colocada en el cuerpo principal. Cuando contacte con Crowcon para obtener asesoría o repuestos, indique el nombre del producto, el número de pieza y el número de serie. 1.2 Descripción del producto El detector IRmax comprende un cuerpo principal de acero inoxidable 316, una cubierta impermeable antiestática sobre la óptica y la cámara de medición de gas y un conjunto electrónico. También se le puede instalar un módulo IR Display. Las instrucciones para instalar la IR Display se muestran en el manual de la IR Display (M07061). Puede suministrarse un pasacables de conexión opcional para permitir que el detector IRmax se instale directamente en cajas de conexiones auxiliares con entradas de cable M20 o NPT de ½”. Español Pasacables opcional 74.5 74,5 136 136 en total Pasacables M20 o NPT de 1/2" 57 en total 60.5 158 en total 157.5 Terminal de conexión a tierra externa (TIERRA) Todas las dimensiones se expresan en milímetros Diagrama 2: Vista dimensionada del detector IRmax Nota: el cuerpo del detector IRmax se suministra con dos entradas de cable: una es M20, la otra NPT de 1/2". La entrada de cable no especificada cuando se pide un detector IRmax se sellará utilizando un tapón certificado. El IRmax debe instalarse con ambas entradas de cable selladas: una con un pasacables, la otra con un tapón certificado con nominal IP66. 88 Detecting Gas Saving Lives 1. Introducción 15 12 14 13 11 “ 10  ‘ ”  Ž Español ‘    Œ Diagrama 3: Despiece del detector IRmax (números de pieza mostrados si es aplicable) Œ Tapa de calibración M041007  Tapa impermeable M04995 Ž Retenedor de espejo Suministrados juntos como ‘kit de repuesto de espejo’ C011206  Espejo  Adaptador de flujo S012996 ‘ Junta tórica para tuerca trasera, módulo de barrera IS o módulo de IR Display fija: M040077  Soporte de montaje como conjunto completo S012130 “ Pasacables versiones M20 o NPT de 1/2" : M20 ATEX: S012147, 1/2" NPT ATEX: S012190 ” Placa de retención y tornillos para tapón trasero, IR Display fija y módulo de barrera IS. } 10 11 12 13 14 15 Versión fija de la IR Display Conector de la IR Display al detector IRmax E07987 Módulo Barrera Cable de conexión de la IR Display Zócalo de montaje de la IR Display remota M03833 IR Display remota Detecting Gas Saving Lives 89 2. Instalación ADVERTENCIA • Este detector ha sido diseñado para utilizarse en áreas peligrosas de Zona 1 y Zona 2, la certificación depende de los accesorios instalados y la temperatura ambiente de funcionamiento. Para obtener los detalles de la certificación, consulte la tabla de especificaciones de la página 99. La instalación debe realizarse de acuerdo con las normas reconocidas de la autoridad apropiada del país en cuestión. • Para obtener información adicional, contacte con Crowcon. Antes de realizar cualquier trabajo de instalación, asegúrese de que se sigan las normas y procedimientos locales. • El equipo debe conectarse a tierra utilizando el pasacables y el cable blindado de acero. • No intente instalar un Display IR a un detector no suministrado para ese fin. Los detectores suministrados para utilizarse con una pantalla están certificados según Exd ia, y deben utilizarse o bien con una pantalla gráfica que contenga una barrera IS o con una pantalla remota o manual conectada a través de un módulo de barrera IS de Crowcon. • Los detectores IRmax suministrados sin pantalla están certificados según Exd IIC y no se les puede instalar una IR Display. Español 2.1 Ubicación El detector IRmax debe montarse en el lugar donde sea más probable que esté presente el gas a detectar. Al ubicar detectores de gas, deben observarse los puntos siguientes: • Para detectar gases más ligeros que el aire, como el metano, los detectores deben montarse a un nivel alto. Para detectar gases más pesados que el aire, como vapores inflamables, los detectores deben montarse a un nivel bajo. • Al ubicar detectores, debe considerarse el posible daño causado por eventos naturales, por ejemplo, lluvias o inundaciones. Para detectores montados en el exterior en regiones muy cálidas, Crowcon recomienda el uso de un toldo o parasol (véase la Sección 5, Accesorios y piezas de repuesto, en la página 100). • Debe tenerse en cuenta facilitar el acceso para tareas de servicio y pruebas funcionales. • Debe tenerse en cuenta cómo puede comportarse el gas que se escape debido a corrientes de aire naturales o forzadas. Monte los detectores IRmax en conductos de ventilación si es apropiado (utilizando el kit de montaje en conducto del detector IRmax (véase la Sección 5, Accesorios y piezas de repuesto, en la página 100). • Deben considerarse las condiciones del proceso. Por ejemplo, normalmente el butano es más pesado que el aire pero si es emitido por un proceso a alta temperatura y/o presión, el gas puede subir en lugar de bajar. El posicionamiento de los sensores debe determinarse después de recibir la asesoría de expertos con conocimientos especializados de la dispersión de gases, el equipo de procesamiento de la planta y cuestiones de seguridad e ingeniería. Debe registrarse el acuerdo respecto a las ubicaciones de los sensores. 90 Detecting Gas Saving Lives 2. Instalación 2.2 Montaje El detector IRmax puede montarse de tres formas: 1. Utilizando el soporte de montaje de Crowcon con la conexión de cable directa (funcionamiento de 4-20 mA solamente). 2. Utilizando un pasacables de espiga opcional para conexión a una caja de conexiones certificada según Exe o Exd. Crowcon suministra un pasacables de espiga adecuado como extra opcional (véase 3 a continuación) 3. Utilizando la caja de conexiones auxiliar y pasacables de espiga opcionales de Crowcon. Se detallan piezas opcionales en la Sección 5, página 100. El detector IRmax debe instalarse en el lugar asignado con el tubo sensor en posición horizontal +/15° (orientación mostrada en el Diagrama 2 de la página 88). Esto garantiza que no se acumule polvo o agua en los componentes ópticos. 2.3 Cableado directo al detector IRmax Español Esta opción es adecuada para funcionamiento de 4-20 mA solamente. Se requiere un soporte de montaje de Crowcon para sujetar el detector a una pared o un tubo de 50 mm. LED de estado Señal 0V (tierra) +V (IRmax de 24 V ) Diagrama 4: Conexiones de cable de campo en el IRmax Conecte los cables utilizando un pasacables certificado a través de la entrada de cable escogida en el cuerpo del detector IRmax (M20 o NPT de1/2"). Crowcon recomienda que los pasacables se instalen apuntando hacia abajo. Asegúrese de que se utilicen pasacables con la certificación Exd apropiada y que la longitud de la rosca no exceda la longitud especificada en el diagrama (a la izquierda). 15mm MAX Detecting Gas Saving Lives 91 2. Instalación 2.3.1 Designación de terminal Con el IRmax orientado de la forma mostrada en el Diagrama 2 de la página 3 (entrada de cable M20 en la parte superior), el cable de 3 conductores debe terminarse utilizando el conector removible, de la forma siguiente: +24V en la parte inferior, 0V en el centro, Signal en la parte superior. El conector de 6 patillas a la derecha de la PCB se utiliza para el servicio y/o conexión de un módulo IR Display terminal +ve: suministro de +ve desde la tarjeta de control. Terminal Sig: Señal/Detección desde tarjeta de control. Terminal 0 V: Suministro de +ve desde la tarjeta de control. 2.3.2 Instalación del detector IRmax utilizando un soporte de montaje a. El IRmax puede suministrarse con un soporte de montaje (S012130) en lugar de un pasacables de espiga para que pueda conectarse directamente a los cables (véase el Diagrama 5). Español Soporte de montaje: 70 mm entre centros de fijación. Utilice tornillos M6. Diagrama 5: IRmax con un soporte de montaje y un pasacables b. Si el IRmax va a montarse en una superficie plana, marque y perfore dos agujeros utilizando el soporte de montaje como plantilla. Fije sin sujetarlas firmemente dos piezas del soporte utilizando elementos de fijación adecuados para la pared/superficie. c. Retire la tapa impermeable del IRmax, y deslice el cuerpo del detector a través del soporte. Se recomienda que el cuerpo del IRmax se instale con la entrada de cable encarada hacia abajo. 92 Detecting Gas Saving Lives 2. Instalación d. Apriete los elementos de fijación del soporte de forma que el IRmax quede sujeto firmemente en posición. Vuelva a colocar la tapa impermeable. e. Cuando el IRmax esté firmemente sujeto en posición, retire la tuerca trasera del IRmax para permitir el acceso a los terminales del cable. f. Prepare el cable – Crowcon recomienda el cable SWA (Steel Wire Armoured - blindado de acero inoxidable) de 1,5 mm2. Pueden utilizarse otros tipos de cable siempre y cuando sean compatibles con pasacables certificados por Exd. Instale un pasacables certificado por Exd, pase los conductores de cable a través del cuerpo del IRmax y enrosque el pasacables. Sujete el pasacables y asegúrese de que el blindaje del cable esté conectado a tierra con el pasacables y el cuerpo del IRmax. Nota: No olvide volver a colocar la tuerca trasera después de instalar el cable. g. La placa de retención (pieza 9 en Diagrama 3, página 89) debe estar instalada de forma segura para prevenir cualquier riesgo de que la tuerca trasera (o IR Display fija o su accesorio de módulo de barrera IS) se afloje a causa de las vibraciones. Se requiere esta opción si el IRmax va a conectarse a una caja de conexiones auxiliar existente certificada por Exd o Exe. Diagrama 6: IRmax conectado a caja de conexiones auxiliar Detecting Gas Saving Lives 93 Español 2.4 Instalación utilizando un pasacables de espiga y una caja de conexiones auxiliar 2. Instalación 2.4.1 Para instalar el detector IRmax en una caja de conexiones auxiliar: a. Retire cuidadosamente la sección externa del pasacables de espiga (pieza 8 en Diagrama 3, página 89). b. Enrosque el extremo estrecho del pasacables de espiga en la caja de conexiones auxiliar. c. Levante el IRmax hasta la caja de conexiones auxiliar de detector y pase los cables a través del conjunto e introdúzcalos en la caja de conexiones auxiliar. Sujete el IRmax enroscando al máximo el collarín en el pasacables. Apriete el espárrago. d. El cuerpo principal del IRmax puede bascularse horizontalmente en cualquier ángulo, siempre que sea mecánicamente seguro, no interfiera con otro equipo y sea accesible para mantenimiento. e. Consulte la sección 2.6 para ver instrucciones sobre el cableado. Véase también el Diagrama 4 (página 91). 2.5 Requisitos de cableado El cableado al IRmax debe realizarse de acuerdo con las normas reconocidas del organismo apropiado del país en cuestión y deben satisfacer los requisitos eléctricos del IRmax. Español Crowcon recomienda el uso de cable blindado de acero inoxidable (SWA) y deben utilizarse pasacables a prueba de explosión adecuados. Pueden ser aceptables técnicas de cableado alternativas, como un conducto de acero, siempre y cuando se satisfagan las normas apropiadas. La longitud de cable máxima recomendada es 3,4 km (véase la Tabla 1). El IRmax requiere un suministro de 12-30 VCC. Asegúrese de que el IRmax reciba un mínimo de 12 V del panel de control, teniendo en cuenta la caída de tensión causada por la resistencia del cable a una corriente pico de 0,1A. Un cable de 1,5 mm2 permitirá típicamente tendidos de cable de hasta 3,0 km. La Tabla 1 siguiente muestra las distancias de cable máximas considerando parámetros de cable típicos. Área de sección transversal Resistencia Distancia máx. >20 V Distancia máx. 18 a 20 V mm2 (Ohmios por km) (km) (km) 1,0 18,4 2,2 1,6 1,5 13,0 3,0 2,3 2,5 11,5 3,4 2,6 Tabla 1: distancias de cable máximas para cables típicos 94 Detecting Gas Saving Lives 2. Instalación 2.6 Conexiones y ajustes Todas las conexiones descritas se refieren al bloque terminal montado en el interior del cuerpo principal del conector del IRmax. Los terminales de la PCB del conector del IRmax están marcados ‘+’, ‘sig’ y ‘0 V’. Cuando se conecta el IRmax a equipo de control debe observarse la polaridad correcta. El IRmax se ajusta en fábrica como dispositivo ‘sumidero de corriente’ a menos que se especifique de otra manera al hacer el pedido. Para restaurarlo a ‘fuente de corriente’, retire la placa posterior y mueva las dos conexiones de la PCB terminal de la posición de ‘sumidero‘ a la posición de ‘fuente’ tal como se muestra en el Diagrama 7. Nota: El terminal de conexión a tierra externa sólo debe utilizarse cuando las autoridades locales permitan o requieran dicha conexión. Si es posible, para limitar la interferencia de frecuencias radiofónicas, la caja de conexiones y el blindaje del cable deben conectarse a tierra al panel de control (área segura) solamente para evitar bucles de tierra. 1 2 3 Controlador CONTROLLER Sumidero Ajustes del puente EARTH Cableado Número Color Función 1 2 3 Rojo +V Negro 0V Verde Señal Conector de kit de comunicaciones de PC Fuente Conector de la IR Display LED de estado Diagrama 7: Ubicación del puente de sumidero/fuente La señal de 4-20mA puede ponerse a corriente de 'sumidero' o 'fuente' utilizando las patillas y la conexión de puente mostraba en el Diagrama 7. Ajuste a ‘sumidero' de corriente instalando la conexión de puente en las patillas 3 y 4, tal como se muestra en la fotografía de la izquierda. Ajuste a ‘fuente' de corriente instalando la conexión de puente en las patillas 1 y 2, tal como se muestra en la fotografía de la derecha. Los detectores IRmax se ajustarán a 'sumidero' de corriente a menos que se especifique de otra manera al hacer el pedido. Indicación LED: Hay instalado un LED en el PCB terminal para indicar el estado operativo de la corriente. Consulte la Sección 6 para obtener más información. Detecting Gas Saving Lives 95 Español +V 0V Sg 3. Funcionamiento ADVERTENCIA Antes de realizar cualquier trabajo, asegúrese de que se sigan las normas locales y los procedimientos del lugar en cuestión. No intente nunca abrir el detector IRmax o la caja de conexiones auxiliares cuando haya gas inflamable presente. Asegúrese de que el panel de control asociado esté inhibido a fin de prevenir alarmas falsas. 3.1 Procedimiento de puesta en servicio 1. Compruebe que: a. Las conexiones de cable son correctas b. La tensión de alimentación está ajustada en la tarjeta de control como 18 a 30 V. La tensión medida en los terminales del detector IRmax (dentro de la caja de conexiones auxiliaire Exe si se utiliza o en el PCB terminal del detector IRmax) y debe ajustarse a entre 12 y 30 V. c. Las conexiones se ajustan para sumidero o fuente de 4-20 mA según sea apropiado en la tarjeta de control. Español 2. Una vez se ha activado, el dispositivo debe dejarse durante 30 minutos antes de intentar una puesta a cero/calibración. Este retardo tiene el fin de garantizar la estabilidad térmica. (Nota: El IRmax será totalmente operativo 30 segundos después de que se le aplique corriente.) 3. Asegúrese de que el aire es limpio (es decir, no hay gases de hidrocarburos) antes de la puesta a cero. Lectura cero en la tarjeta de control (consulte las instrucciones de la tarjeta de control). 4. Coloque la tapa de calibración sobre la cubierta impermeable para aislar la cámara de medición del aire ambiental. Esta tapa puede obtenerse de Crowcon (M041007). Conecte el gas de calibración (50% de LEL nom.) y aplíquelo a un flujo de 1 litro por minuto. 5. Después de 30 segundos ajuste cal/span en la tarjeta de control de forma que la lectura de la pantalla sea 50% de LEL, o corresponda a la concentración del gas de calibración aplicado. El IRmax en sí no debería requerir calibración. 6. Expulse el gas y retire la tapa de calibración. Vuelva a comprobar el cero. 7. A la instalación, o después de que se haya cambiado el espejo, el IRmax puede ponerse a cero y calibrarse bien utilizando un accesorio de IR Display (véase página 85) o a través de un kit de comunicaciones de PC (véase manual de accesorios de IRmax). Nota: Los detectores IRmax certificados por ATEX serán suministrados calibrados para el cumplimiento con EN61779 (donde, por ejemplo metano con 100% de LEL = 4,4% volumen). Nota: Se recomienda que se utilice la tapa de calibración para la puesta en servicio inicial. Las calibraciones posteriores pueden realizarse aplicando gas a la tapa impermeable remotamente a través de la espiga de tubo (lo cual evita la necesidad de acceder directamente al IRmax). La calibración sin la tapa de calibración (es decir, directamente a través de la tapa impermeable) puede realizarse siempre y cuando la velocidad del viento local sea inferior a 2 metros/segundo. El caudal del gas debe ser superior a 2,0 litros/minuto. 96 Detecting Gas Saving Lives 3. Funcionamiento 3.2 Mantenimiento rutinario La aplicación del lugar dictarán la frecuencia de verificación de los detectores. Crowcon recomienda que el IRmax se verifique con gas como mínimo cada 6 meses y se recalibre si es necesario. Para recalibrar un IRmax, siga los pasos indicados en 3.1. En el caso de un fallo de la electrónica, consulte a su representante local de Crowcon. Intervalo de calibración: Crowcon recomienda una calibración cada 12 meses. Limpieza de la óptica: No se recomienda a menos que el IRmax tenga un fallo de oscurecimiento. Si la ventana o el espejo se contaminan, límpielos cuidadosamente con agua (véase la Sección 5 del manual de accesorios de IRmax, página 100). Espejos: Si están dañados, contacte con Crowcon para obtener un repuesto. (véase la Sección 5 del manual de accesorios de IRmax, página 100). El IRmax siempre debe reponerse a cero y recalibrarse después de un cambio de espejo. Si la condensación empieza a causar fallos, cambie el espejo (el revestimiento óptico puede estar dañado). Crowcon recomienda cambiar el espejo cada 5 años. 3.3 Cambio de tipos de gas Cada IRmax se suministra precalibrado para un tipo de gas particular (por ejemplo, metano o propano). Si se requiere recalibración para un tipo de gas diferente, el IRmax puede reconfigurarse utilizando el kit de comunicaciones de PC, (véase la Sección 5 del manual de accesorios de IRmax, página 100), y después calibrarse. Detecting Gas Saving Lives 97 Español Calibración remota a través de tubo: La velocidad del viento debe ser inferior a 2,0 metros por segundo. Si es superior, utilice la tapa de calibración para impedir la dilución del gas. 3. Funcionamiento 3.4 Respuestas relativas de tipos de gas En el gráfico siguiente se muestran las respuestas relativas a otros tipos de gas para un detector IRmax calibrado con metano. Nota: muchos gases y vapores de hidrocarburo son detectados más fácilmente por detectores IR que el metano. La respuesta del IRmax (y otros detectores de gas IR) será lineal a través de la gama 0-100% de LEL para el gas objetivo (es decir, metano en este ejemplo), pero no lineal para otros hidrocarburos que también estén presentes Español Diagrama 8 El diagrama muestra la respuesta de los gases indicados: de izquierda a derecha: propano, butano, pentano y metano. Hay disponibles otros tipos y gamas de gas. Para más detalles, contacte con Crowcon. 98 Detecting Gas Saving Lives Material de la caja Acero inoxidable 316 Dimensiones (detector solamente) 150 mm x 75 mm x 66 mm (sin espiga) Peso IRmax, 1,58 kg IRmax con IR Display fija, 2 kg IRmax con módulo de barrera IS, 2,4 kg IR Display remota , 0,2 kg Tensión de funcionamiento 12 VCC a 30 VCC Potencia <1W Salida 3 hilos 4-20 mA (sumidero o fuente) Señal de fallo <1 mA Resistencia de bucle de cable máxima 80 ohmios (relativa a terminal -ve) Temperatura de funcionamiento -40°C a +75°C (-40°F a +167°F) Humedad 0–100% de humedad relativa Grado de protección IP66 Protección contra explosión Antideflagrante Código de aprobación ATEX IRmax (sin IR Display) II 2 GD Exd db IIC T6 Gb (Tamb = -40°C a +50°C) II 2 GD Exd db IIC T4 Gb (Tamb = -40°C a +75°C) II 2 GD Ex tb IIIC T135°C Db (-40°C ≤ Ta≤ +75°C) IRmax con su módulo de barrera IS (pantalla remota) II 2 GD Exd db ia IIC T4 Gb (Tamb = -40°C a +75°C) Ex tb ia IIIC T135°C Db (Tamb = -40°C a +40°C) IRmax con IR Display fija II 2 G Exd db ia IIC T4 Gb (Tamb = -40°C a +75°C) No. de certificado de seguridad ATEX y IECEx IRmax (sin IR Display): Baseefa 09ATEX0206X y IECEx BAS.09.0109X IRmax (con IR Display): Baseefa 09ATEX0220X y IECEx BAS.09.0104X Seguridad funcional Certificado para uso en un sistema SIL 2. Número de certificado: Sira 12ATEX1206X Estándares EN 60079-0:2012+A11:2013, EN 60079-1:2014, EN 60079-31:2014 IEC 60079-0:2011, IEC 60079-1:2014, IEC 60079-31:2013 EN 60079-29-1:2007, IEC 61508:2010, EN50402:2005 Zonas Certificado para uso en Zona 1 o Zona 2 EMC EN50270 Detecting Gas Saving Lives 99 Español 4. Especificaciones 5. Accesorios y repuestos Español Números de pieza Nombre Descripción M041007 Tapa de calibración Encaja sobre la tapa estanca estándar para permitir la calibración cuando la velocidad del aire local es superior a 2 metros/segundo. S012130 Kit de soporte de montaje Permite realizar el montaje en una pared o un tubo de 50 mm. No se requiere si el IRmax se instala en una caja de conexiones existente. S012152 Parasol/Cono colector Puede instalarse en el IRmax para protegerlo contra altas temperaturas causadas por los rayos directos del sol y/o ampliar la huella del detector para detectar gases más ligeros que el aire (metano). S012169 Kit de montaje de conducto Permite la monitorización de conductos de 300 mm a 3000 mm, y flujo de aire entre 2 m/s y 20 m/s. S012996 Adaptador de flujo Para aplicaciones de muestreo de gas S012827 Kit de comunicaciones de PC Módulo de comunicaciones, software y cable que permiten la configuración del detector. M20: S012295 ½” NPT: S012296 Caja de conexiones auxiliar Opción de montaje de IRmax para uso en entornos peligrosos. C011210 Kit de limpieza de espejo Contiene paño de microfibras y toallitas impregnadas de alcohol isopropílico Repuestos del detector IRmax Para ver los detalles de los repuestos, consulte el Diagrama 3 de la página 89. 100 Detecting Gas Saving Lives 6. Detección de errores 6.1 Errores indicados por LED El LED instalado en el PCB terminal puede ayudar a identificar fallos. Su posición se muestra en el Diagrama 7 de la página 95. La tabla siguiente muestra cómo interpretar lo que falla según cada patrón de destellos. Estado del detector Acción Destello regular cada segundo. Buen estado. Encendido con pitidos cortos. Detector en modo de inicialización. Espere 10 segundos. Destello rápido o patrón de destellos irregular. Tensión de alimentación demasiado baja o demasiado alta. Asegúrese de que la tensión de alimentación del IRmax está ajustada correctamente. Asegúrese de que la medición se realizó directamente en los terminales del IRmax. Encendido permanentemente. Fallo, error del host o i-module Encienda y apague el IRmax y si el fallo continúa, devuélvalo a Crowcon Dos destellos largos seguidos de un destello corto. Error fatal; fallo de la lámpara o detector. Devuélvalo a Crowcon. Doble destello rápido cada segundo. Error fatal, fallo de módulo o configuración. Compruebe la configuración del IRmax utilizando software kit de comunicaciones de PC . Compruebe la fuente de alimentación. Si el fallo continúa, devuélvalo a Crowcon. Un pitido corto cada segundo. Óptica oscurecida. Compruebe la ventana y el espejo, límpielos si es necesario. Reponga a cero el detector IRmax y compruebe la calibración. Cualquier otro fallo sólo puede ser rectificado devolviendo el IRmax a Crowcon o a un agente de servicio autorizado. 6.2 Salida analógica El IRmax sigue en estado de fallo (Fault) y también aparece “Servicio requerido" (Service required) en la IR Display (si está instalada) si la señal de salida analógica ha fallado o si no está conectado a un sistema de control o un resistor de carga. El IRmax monitoriza activamente la señal de salida analógica de 4-20 mA para verificar que está dentro del rango. Si la señal está fuera del rango el detector se pone en estado de fallo y la salida se pone a 1 mA. Por consiguiente, cuando se prueba un detector es esencial que esté conectado a un panel de control o que un resistor de carga de 100 Ω esté conectado entre los terminales ‘0V’ y ‘Sig’ (detector puesto a modo ‘Fuente’) o entre los terminales ‘0V’ y ‘+V’ (detector puesto a modo ‘Sumidero’). Detecting Gas Saving Lives 101 Español Patrón de LED 7. Configuración de RS485 Modbus 7.1 General En esta sección se explica cómo utilizar detectores IRmax en una configuración Modbus. Hay disponible una versión habilitada con RS485 para dichas aplicaciones. Es posible conectar hasta 28 detectores IRmax en configuraciones de estrella o bus, de la forma descrita a continuación. Las conexiones a la versión RS485 del detector IRmax deben realizarse a través de un pasacables de espiga a una caja de conexiones auxiliar (Véase Sección 5, página 92.), en lugar de cablearlas directamente al interior del detector. Debe observarse que la pantalla del IR Display no puede utilizarse con detectores IRmax habilitados con RS485. La versión del IRmax habilitada con RS-485 tiene cinco terminales de campo. Los terminales son: Español 1 Electricidad positiva 12 V a 30 V a más de 0 V 2 0V Retorno y referencia RS-485 3 Señal de 4-20 mA Señal fuente o sumidero (opcional) 4 RS485 B Señal diferencial RS-485 5 RS485 A Señal diferencial RS-485 Las señales de los terminales RS-485 cumplen con la norma EIA/TIA-485, lo que significa que la gama de modo común es -7V a +12V respecto al terminal 0V. Debe observarse que no todos los fabricantes de RS-485 están de acuerdo respecto a la polaridad de las señales A y B. Si el cableado no funciona de una forma, los usuarios deben intercambiar los cables RS-485 A&B. Hacer una conexión incorrecta no implica ningún riesgo. Los ajustes de comunicaciones son 9600 bps, dos bits de parada y no paridad. Cuando se compila un interfaz para un sistema de control, es importante considerar el tiempo que el sistema tarda en recoger información de cada detector, uno después de otro. La velocidad más rápida a la que detectores múltiples pueden ser sondeados es 14 detectores por segundo, pero en la práctica las condiciones pueden reducir esto a 7 por segundo. Los usuarios deben asegurarse de que el plan permita que las señales de alarma se registren dentro de límites de tiempo aceptables. También es importante asegurarse de que el sistema pueda suministrar energía suficiente para mantener todos los detectores en funcionamiento. Para calcular la cantidad de energía requerida en una conexión de bus lineal, véase la Sección 7.3, Requisitos de cableado, página 104. Para obtener las instrucciones completas sobre Modbus, contacte con Crowcon (véanse las direcciones en la contraportada). 102 Detecting Gas Saving Lives 7. RS485 Modbus configuration 7.2 Topología del cableado Las dos topologías de cableado más comunes son la conexión en estrella y el bus lineal. 7.2.1 Conexión en estrella En una topología de conexión en estrella, todos los detectores están cableados a un punto central, que usualmente es el panel de control. No se requiere que los cables tengan más de 5 núcleos ya que todas las conexiones de señales de 4-20mA se llevan directamente al panel de control. Entonces las señales A y B de RS-485 pueden conectarse juntas en el punto de estrella. Seguidamente el bus debe terminarse en el punto de salida con un solo resistor de 110 ohmios. La longitud de cada brazo de la estrella no puede superar los 750 metros. 7.2.2 Conexión de bus lineal En una topología de conexión de bus, todos los detectores IRmax se cablean en una disposición lineal, usualmente con el panel de control en un extremo. Una situación clásica es una instalación de túnel, con los detectores IRmax instalados a intervalos regulares (véase el Diagrama 9 a continuación).). Como las señales de 4-20 mA no puede compartirse, se requiere un conductor adicional en cada tramo de cableado. Si no se utiliza ninguna de las señales de 4-20 mA, sólo se requieren cuatro conductores. DIAGRAMA DE CONEXIÓN DE BUS LINEAL A PANEL DE CONTROL Diagrama 9 Detecting Gas Saving Lives 103 Español Para cablear la instalación, deben instalarse dos resistores de terminación de 110 ohmios en cada extremo físico del bus. 7. RS485 Modbus configuration 7.3 Requisitos de cableado 7.3.1 Cálculo del nivel mínimo de potencia requerida Cuantos más detectores IRmax estén conectados al bus lineal, mayor será la potencia requerida para el funcionamiento del sistema. Para calcular la potencia requerida para una instalación particular es necesario conocer la resistencia del cable entre cada par de detectores IRmax. Debe permitirse una corriente de por lo menos 0,1 mA para cada ‘tramo’ entre los detectores IRmax. La tensión aplicada puede calcularse calculando la caída de voltaje a través de cada ‘tramo’ – al final deben quedar por lo menos 12 V para asegurarse de que el último detector IRmax funciona correctamente. Para obtener asesoría en casos específicos, contacte con Crowcon. De forma alternativa, siga los pasos descritos a continuación y el cálculo de muestra presentado en la sección siguiente. 1. La tensión no debe descender por debajo de 12 V, por tanto empiece el cálculo ajustando la tensión en el último IRmax de la línea a ese valor. 2. Cada IRmax puede tomar hasta 0,1 A. Calcule la pérdida de tensión de cable del primer ‘tramo’ entre detectores suponiendo que la ‘corriente agregada’ es 0,1A, y multiplique esto por la resistencia de cable del ‘tramo’ entre los detectores IRmax último y penúltimo. Español 3. Añada esta caída de tensión a los 12 V iniciales para obtener la tensión aceptable más baja en el penúltimo IRmax. Añada 0,1 A al valor de la ‘corriente agregada’ para llegar a 0,2 mA, la corriente mínima que pasa a través del penúltimo ‘tramo’ del bus. Multiplique esto por la resistencia de cable para el penúltimo ‘tramo’ para obtener la caída de tensión siguiente. 4. Repita este proceso para cada IRmax, acumulando las pérdidas de tensión que ocurrirán entre todos los detectores IRmax. 5. No debe excederse la tensión de detector máxima de 30 V. 7.3.2 Cálculo de muestra Como ejemplo, aquí se muestran los resultados del cálculo realizado para seis detectores IRmax espaciados uniformemente en un cable con un área de sección transversal de 1 mm2. Cada tramo tiene una resistencia de 4,6 ohmios. Estación Tensión de alimentación Corriente de alimentación 1 12 0,1 A 2 12,46 0,2 A 3 13,38 0,3 A 4 14,76 0,4 A 5 16,6 0,5 A 6 18,9 0,6 A Alimentación del panel 21,66 0,6 A 104 Detecting Gas Saving Lives 8. Manual de seguridad funcional 8.1 Prólogo Las secciones siguientes proporcionan detalles sobre la certificación del IRmax de acuerdo con los estándares de seguridad funcional IEC 61508 y EN 50402. Se da información sobre las características consideradas respecto a seguridad, requisitos de mantenimiento y datos que permiten que el IRmax se integre en el Safety Instrumented System (SIS) (Sistema instrumentado de seguridad). 8.2 Función de seguridad del IRmax y del IRmax Modbus Para medir la concentración de gas inflamable e indicar la medición por medio de una salida de 4-20 mA. Los fallos relacionados con la función de seguridad serán detectados por el hardware y firmware asociados. Serán revelados en la forma de una señal de salida de menos de 3,6 mA o de más de 21 mA. Nombre de parámetro Símbolo Ecuación / fuente Intervalo de ensayo de prueba T1 Según define Crowcon. Tiempo medio de reparación MTTR Según define Crowcon. IRmax 8.760 horas (anuales) 8 horas Tipo A/B Tipo A Según define Crowcon. Tipo B Fallos totales: λ De FMEDA 1.04E-05 Fallos diagnosticados no peligrosos: λSD De FMEDA 1.95E-08 Fallos no diagnosticados no peligrosos: λSU De FMEDA 8.59E-08 λDD De FMEDA 9.74E-06 Fallos no diagnosticados peligrosos: λDU De FMEDA 5.06E-07 Fallos sin efecto no peligrosos: λNE De FMEDA 3.21E-09 Cobertura de diagnósticos: DC λDD / (λDU + λDD) 95.06% Fallos diagnosticados peligrosos: Fracción de fallo no peligroso: SFF (λSD + λSU + λDD) / λ Tiempo inactivo equivalente de (λDU / λD)(T/2 + MTTR) + tCE canal (λDD / λD ) MTTR PFDAVG (utilizando la ecuación PFDAVG (λDU + λDD) tCE 61508-6) PFDAVG (utilizando ecuación PFDAVG λDU (T / 2+MTTR) + (λDD MTTR) simplificada) PFDAVG (utilizando la ecuación IEC PFDAVG 1-ε-(λdd+λdu) tce 61508-6) Capacidad de SIL (modo de baja demanda) Capacidad de SIL (modo de alta demanda) Para aplicaciones de baja demanda, respecto a fallos de hardware aleatorios fallos no peligrosos, todas las variantes del sistema son adecuadas para utilizarse SIL 2. Detecting Gas Saving Lives 105 95.11% 2.24E+02 2.30E-03 2.30E-03 2.30E-03 SIL2 SIL2 y fracciones de en aplicaciones Español 8.3 Datos de seguridad funcional Manual de seguridad funcional 8.4 Configuración de hardware Se ha utilizado la Ruta 1H (tolerancia de fallo de hardware y fracción de fallo no peligroso) para evaluar el nivel de integridad de seguridad del hardware. 8.5 Configuración de software Sea realizado la evaluación del firmware del producto de acuerdo con los requisitos dados en IEC 61508:3 2010. 8.6 Fallos sistemáticos La Ruta 1S (especificada en IEC 61508:2 2010, párrafo 7.4.2.2c) se utiliza para cumplir con los requisitos de evitar fallos sistemáticos. 8.7 Intervalo de diagnósticos La mayoría de funciones de diagnósticos se monitorizan continuamente. Español Se comprueba el circuito vigilante del sistema durante el ensayo de prueba anual mediante un ciclo de desconexión y conexión eléctricas: El IRmax debe verificarse mediante un ciclo de desconexión y conexión eléctricas (desconectar y reconectar el suministro de 24 VCC) como parte del programa de mantenimiento para el producto (consulte también la sección 3.2). 8.8 Restricciones Los índices de fallos son constantes. Un ensayo de prueba realizado por lo menos una vez al año identificará todos los fallos no revelados. Las reparaciones tienen un tiempo medio de 8 horas. Se supone que el usuario utiliza esta función de diagnósticos proporcionada a través del accesorio IR Display y/o interfaz de PC a fin de minimizar el tiempo inactivo potencial del producto. La evaluación de la fiabilidad es un proceso estadístico para aplicar datos de fallos históricos a diseños y configuraciones propuestos. Por consiguiente proporciona un objetivo/evaluación creíble de la probable fiabilidad del equipo suponiendo condiciones de fabricación, diseño y funcionamiento idénticas a aquellas en las que los datos se recopilaron. Es una valiosa técnica de revisión de diseño para comparar diseños alternativos, establecer el orden de objetivos de rendimiento de magnitudes y evaluar los efectos potenciales de cambios de diseño. Sin embargo no puede garantizarse que los valores previstos reales pronostiquen el número preciso de fallos sobre el terreno que pueden ocurrir realmente, ya que esto depende de muchos factores fuera del control de un ejercicio predictivo. A efectos de esta predicción, se supone que los índices de fallos (símbolo λ) son constantes con el tiempo. Tanto los fallos prematuros como los asociados con el desgaste reducirían la fiabilidad pero se supone que pueden ser eliminados mediante pruebas previas y cambios preventivos respectivamente. 106 Detecting Gas Saving Lives Manual de seguridad funcional La probabilidad de fallo a solicitud significa la probabilidad de que el sistema esté en un estado de fallo en un momento al azar. Esto es sinónimo de la indisponibilidad de estado estable, que es dada por: Indisponibilidad = (λ x MDT)/(1 + (λ x MDT)) que se aproxima a λ x MDT para valores pequeños de λ x MDT donde λ es el índice de fallos y MDT es el tiempo inactivo medio (Mean Down Time). Esto concuerda con la expresión de disponibilidad, dada como: MTBF/(MTBF+MDT) Los índices de fallo utilizados, y por tanto las disponibilidades derivadas, son las asociadas de forma creíble con un diseño de probada eficacia después de un periodo adecuado de aumento de fiabilidad. 8.9 Medio ambiente Restricciones medioambientales: El producto se almacenará dentro de una gama de temperatura ambiente máxima de 40°C a +80 °C. El producto se hará funcionar dentro de una gama de humedad relativa ambiente máxima de 0% a +100 % de condensación. El producto tiene un nominal de “protección contra penetración" de IP66 de acuerdo con las definiciones del estándar EN60529. El producto está diseñado para funcionamiento continuo. 8.10 Tolerancia de fallo de hardware La tolerancia de fallo de hardware es 0. 8.11 Capacidad sistemática El IREX/IRmax es de Clase SC2. 8.12 Clasificación El IREX/IRmax es un componente tipo B. Detecting Gas Saving Lives 107 Español El producto se hará funcionar dentro de una gama de temperatura ambiente máxima de 40°C a +75 °C Garantía Este equipo sale de nuestra fábrica completamente verificado y calibrado. Si durante el período de garantía de tres años, calculado a partir de la fecha de envío, se demuestra que el equipo es defectuoso debido a material o fabricación deficiente, nos comprometemos a repararlo o cambiarlo, a nuestro criterio, gratuitamente, bajo las condiciones siguientes. Procedimento de garantía Para facilitar el procesamiento eficiente de cualquier reclamación, contacte con nuestro equipo de asistencia al cliente, llamando al nº de teléfono +44 (0)1235 557711 y proporcionando la información siguiente: Su nombre y número de teléfono, número de fax y dirección de email de contacto. La descripción y cantidad de productos que se devuelven, incluidos cualesquiera accesorios. Número(s) de serie de instrumento(s). El motivo de la devolución. Español Obtenga un formulario de devolución para fines de identificación y localización. Este formulario puede ser descargado de nuestro sitio web ‘crowconsupport.com’, junto con una etiqueta de devoluciones. De forma alternativa podemos enviarle una copia por email. No se aceptarán detectores IRmax bajo garantía sin un número de devolución de Crowcon (Crowcon Returns Number (CRN)). Es esencial que la etiqueta de la dirección esté fijada de forma segura en el embalaje externo de los productos devueltos. La garantía quedará anulada si se descubre que el instrumento ha sido alterado, modificado, desmontado o manipulado indebidamente. La garantía no cubre el uso indebido o el maltrato de la unidad. Descargo de responsabilidad de garantía Crowcon no acepta ninguna responsabilidad por pérdidas o daños consecuenciales o indirectos, sea cual sea su causa (incluida cualquier pérdida o daño CAUSADO por el uso del instrumento) y se excluye expresamente cualquier responsabilidad respecto a terceros. La garantía respecto a elementos consumibles de repuesto (como el espejo) suministrados bajo garantía para reemplazar elementos defectuosos, se limitará a la garantía vigente del elemento suministrado original. La garantía respecto a elementos consumibles de repuesto (como el espejo) suministrados bajo garantía para reemplazar elementos defectuosos, se limitará a la garantía vigente del elemento suministrado original. Crowcon se reserva el derecho de determinar un periodo de garantía reducido, o declinar un periodo de garantía para cualquier sensor suministrado para utilizarse en un entorno o para una aplicación que se sabe que presenta un riesgo de degradar o dañar el sensor.. Nuestra responsabilidad respecto a equipo defectuoso se limitará a las obligaciones establecidas en la garantía y se excluye cualquier garantía extendida, condición o declaración, explícita o implícita, estatutaria o de otro tipo respecto a la calidad comercializable de nuestro equipo o su idoneidad para algún fin particular excepto si esta exclusión está prohibida por la ley. Esa garantía no afectará los derechos estatutarios de un cliente. 108 Detecting Gas Saving Lives Warranty Crowcon se reserva el derecho de aplicar un recargo de manipulación y transporte si se descubre que unidades devueltas como defectuosas sólo requieren calibración o servicio normal, que el cliente declina realizar. Para consultas sobre garantía y asistencia técnica, contacte con: Asistencia al cliente Tel: +44 (0) 1235 557711 Fax: +44 (0) 1235 557722 Español Email: [email protected] Detecting Gas Saving Lives 109 Contenuto Principi di funzionamento e informazioni di sicurezza................................ 113 Principi di funzionamento del rilevatore IRmax ................................. 113 Informazioni per la sicurezza.............................................................. 114 Panoramica del prodotto.................................................................... 115 1. Introduzione.......................................................................................... 116 1.1 Considerazioni generali................................................................ 116 1.2 Descrizione del prodotto.............................................................. 116 2. Installazione.......................................................................................... 118 AVVERTENZA..................................................................................... 118 2.1 Collocazione................................................................................ 118 2.2 Montaggio................................................................................... 119 2.3 Collegamento diretto del cablaggio al rilevatore IRmax .............. 119 2.3.1 Assegnazione dei terminali.................................................. 120 2.3.2 Installazione del rilevatore IRmax con la staffa di montaggio....120 2.4 Installazione con attacco e scatola di derivazione ausiliaria........... 121 2.4.1 Montaggio del rilevatore IRmax a una scatola di derivazione ausiliaria.................................................................... 122 2.5 Requisiti per il cablaggio.............................................................. 122 2.6 Collegamenti e impostazioni........................................................ 123 3. Funzionamento..................................................................................... 124 3.1 Commissioning procedure............................................................ 124 3.2 Manutenzione ordinaria............................................................... 125 3.3 Applicazioni con rilevazione di più gas......................................... 125 3.4 Risposte relative ai tipi di gas....................................................... 126 4. Dati tecnici............................................................................................ 127 5. Accessori e ricambi................................................................................ 128 6. Diagnostica.......................................................................................... 129 6.1 Errori segnalati dal LED................................................................ 129 6.2 Uscita analogica........................................................................... 129 7. Configurazione Modbus RS485............................................................. 130 7.1 Considerazioni generali................................................................ 130 7.2 Topologia di collegamento........................................................... 131 7.2.1 Collegamento a stella.......................................................... 131 7.2.2 Collegamento a bus lineare................................................. 131 7.3 Requisiti di cablaggio................................................................... 132 7.3.1 Calcolo del livello minimo di potenza richiesto .................... 132 7.3.2 Esempio di calcolo............................................................... 132 8. Manuale della sicurezza funzionale....................................................... 133 8.1 Introduzione................................................................................ 133 8.2 Funzione di sicurezza IRmax e IRmax Modbus.............................. 133 8.3 Dati di sicurezza funzionale.......................................................... 133 8.4 Configurazione dell’hardware...................................................... 134 8.5 Configurazione del software........................................................ 134 8.6 Guasti sistematici......................................................................... 134 8.7 Intervallo diagnostico................................................................... 134 8.8 Limiti............................................................................................ 134 8.9 Ambientale.................................................................................. 135 8.10 Tolleranza ai guasti hardware..................................................... 135 8.11 Capacità sistematica................................................................... 135 8.12 Classificazione............................................................................ 135 Garanzia.................................................................................................... 136 Principi di funzionamento e informazioni di sicurezza Principi di funzionamento del rilevatore IRmax Il rilevatore di gas a infrarossi (IR) ultracompatto IRmax consente la rilevazione rapida e fail-safe di vapori e gas idrocarburi. Progettato per operare nelle condizioni più gravose, IRmax integra la tecnologia dei sensori IR a doppia lunghezza d’onda in una robusta esecuzione in acciaio inox 316. A differenza dei tradizionali rilevatori di gas a IR, IRmax non incorpora elementi scaldanti per prevenire la formazione di condensa su vetri e finestrine. Grazie al rivestimento STAY CLIR, infatti, il rilevatore IRmax previene la formazione di condensa durante il funzionamento. Il rilevatore IRmax è compatibile con qualunque sistema di controllo 4-20mA e può anche essere installato in una rete di Modbus RS485 indirizzabili. (vedere Sezione 7). Il rilevatore IRmax assorbe solo 1 Watt di potenza, con un consumo tra il 75 e il 90% inferiore rispetto ai tradizionali rilevatori di gas a IR. IR Display consente di monitorare le letture del rilevatore IRmax sia in sede che a distanza. IR Display può essere montato direttamente sul rilevatore IRmax o fornito con una barriera Crowcon a sicurezza intrinseca. In questo modo l’unità IR Display può essere collegata alla barriera mediante cablaggio provvisorio o permanente. Le opzioni disponibili sono illustrate nello Schema 3, pagina 116. Per ulteriori informazioni sugli altri accessori per il rilevatore IRmax v. la Schema 3 a pagina 117 e la Sezione 5 a pagina 128. Detecting Gas Saving Lives 113 Italiano Il rilevatore IRmax è caratterizzato da una camera di diffusione compatta che, insieme all’efficiente copertura di protezione anti-intemperie, assicura un’eccellente velocità di risposta. La copertura anti-intemperie è stata progettata con l’ausilio di un software di modellazione del flusso d’aria per effettuare la gassatura e la calibrazione a distanza senza l’impiego di speciali cappucci di calibrazione. Principi di funzionamento e informazioni di sicurezza Informazioni per la sicurezza • I rilevatori di gas IRmax devono essere installati, utilizzati e riparati attenendosi rigorosamente alle istruzioni e ai messaggi di avviso contenuti nel presente manuale, alle informazioni riportate sulle etichette ed entro i limiti stabiliti. • Il dado posteriore del rilevatore IRmax deve essere sempre ben serrato durante il funzionamento. Non tentare di rimuovere il dado posteriore prima di avere isolato l’alimentazione del rilevatore per evitare possibili accensioni in atmosfere esplosive. Prima di rimuovere il dado per eseguire interventi di manutenzione, calibrazione o riparazione, controllare che l’atmosfera circostante non contenga gas o vapori infiammabili. Dopo avere scollegato l’alimentazione, attendere sempre qualche minuto prima di procedere. • Gli interventi di manutenzione e calibrazione devono essere affidati esclusivamente a personale qualificato. • Utilizzare solo ricambi originali Crowcon; l’utilizzo di componenti non originali può invalidare la certificazione e la garanzia del rilevatore IRmax. • In ambienti riscaldati, i rilevatori IRmax devono essere protetti dalle vibrazioni eccessive e dalla luce solare diretta per evitare un aumento della temperatura superiore ai limiti specificati e ridurre la durata di esercizio dell’apparecchio. • I rilevatori IRmax non rilevano idrogeno, ammoniaca o anidride carbonica. • L’apparecchiatura deve essere collegata a terra mediante il pressacavo e il cavo in acciaio armato. • Omologazione per ambienti polverosi Zona 21/22: il modello IRmax base (senza display IR o modulo barriera IS) può essere usato in ambienti contenenti polveri pericolose (Zone 21 o 22). • Il modello IRmax con modulo barriera IS può essere usato nelle Zone 21 o 22 a condizione che la temperatura ambiente non superi 40°C e che si installi/utilizzi un display IR remoto o display IR palmari solo all'esterno dell'area pericolosa. Italiano • Il modello IRmax con display IR fisso non può essere installato in ambienti classificati come Zona 21 o 22. 114 Detecting Gas Saving Lives Principi di funzionamento e informazioni di sicurezza Panoramica del prodotto Il rilevatore IRmax è un rilevatore di gas a infrarossi usato per la rilevazione dei comuni gas idrocarburi entro una gamma compresa tra 0 e 100%LEL (Lower Explosive Limit: limite inferiore di esplosività, ossia la concentrazione minima nell’aria a cui può verificarsi l’accensione). L’apparecchio IRmax è un rilevatore antideflagrante certificato (Exd) idoneo all’uso nelle Zone 1 o 2 definite dalla direttiva ATEX relativa alle aree pericolose. Per individuare il tipo di certificazione del proprio apparecchio fare riferimento ai dati della targhetta di certificazione riportata su un lato dell’apparecchio. Nota: se non è presente alcuna targhetta di certificazione, il rilevatore IRmax non è certificato per l’impiego nelle aree pericolose. IR GAS DE TECTOR 1180 IR GAS DETECTOR WITH REMOTE DISPLAY II 2 GD 1180 V m ax= 32V W m ax= 5W II 2GD Vmax=32V Wmax=5W B a s e e fa 0 9 A T E X 0 2 0 6 X IE C E x B A S 0 9 . 0 1 0 9 X S IL 2 S i r a 1 2 A T E X 1 2 0 6 X Baseefa09ATEX0220X IECEx BAS 09.0104X Ex db ia IIC T4 Gb (-40°C ≤ Ta ≤ +75°C) Ex tb ia IIIC T135°C Db (-40°C ≤ Ta ≤ +40°C) E x d b II C T 4 Gb (T am b = -40 °C to + 75 °C ) E x d b II C T 6 Gb (T am b = -40 °C to + 50 °C ) E x tb II IC T 135° C D b (-4 0° C T a + 75° C ) WARNING: DO NOT OPEN WHEN EXPLOSIVE ATMOSPHERE MAY BE PRESENT. W A R N IN G : D O N O T O P E N W H E N E X P L O S IV E A TM O S P H E R E M A Y B E P R E S E N T. Abingdon, United Kingdom, OX14 4SD A b i n g d o n , U nit e d K in g d o m , O X 1 4 4 S D Targhetta omologazione IRmax con barriera IS IR GAS DETECTOR WITH DISPLAY 1180 II 2G Baseefa09ATEX0220X IECEx BAS 09.0104X Vmax=32V Wmax=5W Ex db ia IIC T4 Gb (-40°C Ta +75°C) WARNING: DO NOT OPEN WHEN EXPLOSIVE ATMOSPHERE MAY BE PRESENT. Abingdon, United Kingdom, OX14 4SD Targhetta omologazione IRmax con display IR fisso Schema 1: targhette di certificazione del rilevatore IRmax Detecting Gas Saving Lives 115 Italiano Targhetta omologazione modello IRmax base 1. Introduzione 1.1 Considerazioni generali Tutti i rilevatori IRmax sono identificati da una targhetta attaccata al corpo principale. Al momento di contattare Crowcon per richiedere assistenza o ricambi, si prega di avere a portata di mano nome, numero di parte e di matricola del prodotto. 1.2 Descrizione del prodotto Il rilevatore IRmax è costituito da un corpo principale in acciaio inox 316, una copertura antistatica per la protezione del sistema ottico, una camera di misurazione dei gas e un gruppo elettronico. Inoltre, il rilevatore IRmax può essere dotato di un modulo IR Display. Le istruzioni per il montaggio dell’unità IR Display sono riportate nel relativo manuale (M07061). È inoltre disponibile un attacco opzionale per collegare il rilevatore IRmax direttamente alle scatole di derivazione ausiliarie con ingressi per cavi M20 o ½” NPT. Attacco opzionale 74.5 74,5 57 totale 60.5 158 totale 157.5 136 totale 136 Italiano Pressacavi M20 o 1/2" NPT Terminale di terra esterno (EARTH) Tutte le dimensioni sono espresse in millimetri Schema 2: disegno dimensionale del rilevatore IRmax Nota: il corpo del rilevatore IRmax è dotato di due ingressi per cavi: uno M20 e l’altro 1/2" NPT. L’ingresso per cavo non specificato al momento dell’ordinazione del rilevatore IRmax viene sigillato in fabbrica con un tappo certificato. Il rilevatore IRmax deve essere installato con entrambi gli ingressi sigillati: uno mediante pressacavo, l’altro mediante tappo omologato. 116 Detecting Gas Saving Lives 1. Introduzione 15 12 14 13 11 “ 10  ‘ ”  ‘    Œ Schema 3: disegno esploso del rilevatore IRmax (con numeri di parte dove applicabile) Œ Cappuccio di calibrazione M041007  Copertura protettiva M04995 Ž Fermaspecchio Fornito come kit di ricambio completo dello specchio C011206  Specchio  Adattatore di flusso S012996 ‘ O-ring per controdado, modulo barriera IS o modulo per display IR fisso: M040077  Staffa di montaggio come gruppo completo S012130 “ Attacco versione M20 o 1/2"NPT: M20 ATEX: S012147, 1/2" NPT ATEX: S012190 ” Piastra e bulloni di fissaggio per tappo posteriore, display IR fisso e modulo barriera IS. } 10 11 12 13 14 15 IR Display versione fissa Connettore da IR Display a IRmax E07987 Barriera a sicurezza intrinseca Cavo collegamento IR Display Presa montaggio IR Display remoto M03833 IR Display remoto Detecting Gas Saving Lives 117 Italiano Ž 2. Installazione AVVERTENZA • Questo rilevatore è progettato per l’impiego in Zone a rischio 1 e 2; il tipo di certificazione dipende dagli accessori montati e dalla temperatura ambiente di esercizio. Per informazioni dettagliate sulla certificazione fare riferimento alla tabella delle specifiche a pagina 14. L’installazione deve essere conforme agli standard approvati dall’autorità competente nei rispettivi Paesi. • Per ulteriori informazioni contattare Crowcon. Prima di eseguire qualunque installazione, garantire la stretta osservanza di tutte le norme locali e delle procedure del sito. • L’apparecchiatura deve essere collegata a terra mediante il pressacavo e il cavo in acciaio armato. • Non tentare di collegare un’unità IR Display a un rilevatore non progettato per lo scopo. I rilevatori progettati per l’impiego con il display sono certificati Exd e devono essere azionati con un display fisso contenente una barriera a sicurezza intrinseca o con un display remoto o palmare collegato mediante il modulo Crowcon IS Barrier. • I rilevatori IRmax forniti senza display sono certificati Exd IIC e non sono adatti all’uso con l’unità IR Display. 2.1 Collocazione Il rilevatore IRmax deve essere montato dove è più probabile che sia presente il gas da rilevare. Al momento di scegliere il punto di installazione, tenere presente quanto riportato di seguito. • Per rilevare gas più leggeri dell’aria, come il metano, i rilevatori devono essere montati in alto. Per rilevare gas più pesanti dell’aria, quali i vapori infiammabili, i rilevatori devono essere montati in basso. Italiano • Al momento di scegliere il punto di installazione dei rilevatori, si raccomanda di valutare i possibili danni causati da eventi naturali quali pioggia o allagamenti. Nel caso dei rilevatori montati all’esterno in regioni molto calde, Crowcon raccomanda l’uso di un schermo solare (vedere Sezione 5, Accessori e ricambi, a pagina 128). • Tenere conto della facilità di accesso al rilevatore per le procedure di verifica e gli interventi di manutenzione. • Valutare il possibile comportamento delle fughe di gas in presenza di correnti d’aria naturali o indotte. Se del caso, montare i rilevatori nelle condotte di ventilazione (vedere Sezione 5, Accessori e ricambi, a pagina 128). • Valutare le condizioni del processo. Per esempio, il butano è normalmente più pesante dell’aria, tuttavia - se liberato da un processo eseguito a temperatura e/o pressione elevata - può salire invece di scendere. La posizione dei sensori deve essere determinata con la consulenza di periti nella dispersione dei gas, nelle apparecchiature di processo del sito e negli aspetti relativi alla sicurezza e alla progettazione. Conservare la documentazione relativa alla posizione dei sensori concordata con i periti. 118 Detecting Gas Saving Lives 2. Installazione 2.2 Montaggio Il rilevatore IRmax può essere montato in tre modi: 1. Usando la staffa di montaggio opzionale e creando un collegamento diretto con il cavo di campo (solo per il funzionamento a 4-20mA) 2. Usando un attacco opzionale da collegare a una scatola di giunzione preesistente e omologata Exe o Exd. Crowcon fornisce una guarnizione per l’attacco come extra opzionale (v. 3 sotto) 3. con la scatola di derivazione ausiliaria e l’attacco opzionali Crowcon. I componenti opzionali sono riportati nella Sezione 5, pagina 128. Il rilevatore IRmax deve essere installato nel punto designato con il cilindro del sensore orizzontale +/- 15° (come mostrato nello schema 2 a pagina 3). Questa disposizione consente di evitare l’accumulo di polvere o acqua nei componenti ottici. 2.3 Collegamento diretto del cablaggio al rilevatore IRmax Questa opzione è disponibile solo per il funzionamento a 4-20mA. Per fissare il rilevatore a una parete o a un tubo da 50 mm occorre utilizzare una staffa di montaggio.. Segnale 0V (terra) +V (24V IRmax) Schema 4: Collegamenti del cavo di campo sul rilevatore IRmax Collegare i cavi di campo montando un pressacavo certificato nell’ingresso prescelto sul corpo del rilevatore IRmax (M20 o 1/2" NPT). Crowcon raccomanda di installare il pressacavo orientandolo verso il basso. Accertarsi di utilizzare un pressacavo con idonea certificazione Exd e filettature con passo non superiore alla lunghezza specificata nello schema (a sinistra). 15mm MAX Detecting Gas Saving Lives 119 Italiano LED di stato 2. Installazione 2.3.1 Assegnazione dei terminali Con il rilevatore IRmax orientato come mostrato nello Schema 2, pagina 116 (ingresso del cavo M20 nella parte superiore), collegare il cavo di campo utilizzando il connettore estraibile come indicato di seguito: +24V nella parte inferiore, 0V al centro, segnale nella parte superiore. Il connettore a 6-pin a destra della scheda a circuiti stampati serve per la manutenzione e/o il collegamento di un modulo IR Display. Terminale +ve: alimentazione +ve dalla scheda di controllo. Terminale Sig: segnale dalla scheda di controllo. Terminale 0 V: alimentazione -ve dalla scheda di controllo. 2.3.2 Installazione del rilevatore IRmax con la staffa di montaggio a. Il rilevatore IRmax può essere fornito con una staffa di montaggio (S012130) al posto dell’attacco per consentire il collegamento diretto ai cavi di campo (vedere Schema 5). Italiano Staffa di montaggio: 70mm tra i centri di fissaggio. Usare bulloni M6. Schema 5: rilevatore IRmax con staffa di montaggio e pressacavo b. Se il rilevatore IRmax viene montato su una superficie in piano, utilizzare la staffa di montaggio come maschera per segnare e trapanare due fori. Utilizzando fissaggi adatti alla parete/superficie di montaggio, montare senza serrare le due parti della staffa. c. Rimuovere la copertura protettiva dal rilevatore IRmax e fare scorrere il corpo del rilevatore nella staffa. Si raccomanda di installare il corpo del rilevatore in modo che l’ingresso del cavo sia rivolto verso il basso. 120 Detecting Gas Saving Lives 2. Installazione d. Serrare i due fissaggi della staffa in modo che il rilevatore IRmax risulti saldamente bloccato in posizione. Rimontare la copertura protettiva. e. Dopo avere fissato il rilevatore IRmax, rimuovere il dado posteriore per accedere ai terminali dei cavi. f. Predisporre il cavo di campo. Crowcon raccomanda l’uso di un cavo con filo in acciaio armato (SWA) da 1,5 mm2 è possibile utilizzare altri tipi di cavi a condizione che siano compatibili con i pressacavi certificati Exd. Montare un pressacavo idoneo certificato Exd, fare passare i conduttori nel corpo del rilevatore IRmax e avvitare il pressacavo. Fissare il pressacavo e controllare che l’armatura del cavo sia collegata a terra mediante il pressacavo e il corpo del rilevatore IRmax. N.B.:non dimenticare di rimontare il dado posteriore dopo aver installato il cavo. g. La piastra di fissaggio (componente 9 nello Schema 3 a pagina 117) deve essere saldamente fissata per prevenire eventuali rischi di allentamento del dado posteriore (o dell’accessorio del display IR fisso o del modulo barriera IS) a causa delle vibrazioni. 2.4 Installazione con attacco e scatola di derivazione ausiliaria Italiano Questa opzione di montaggio è richiesta se il rilevatore IRmax deve essere collegato a una scatola di derivazione ausiliaria preesistente certificata Exd o Exe. Schema 6: rilevatore IRmax collegato alla scatola di derivazione ausiliaria Detecting Gas Saving Lives 121 2. Installazione 2.4.1 Montaggio del rilevatore IRmax a una scatola di derivazione ausiliaria a. Rimuovere con cura la sezione esterna dell’attacco (componente 8 nello Schema 3 a pagina 117). b. Avvitare l’estremità stretta dell’attacco nella scatola di derivazione ausiliaria del rilevatore IRmax. c. Sollevare il rilevatore IRmax fino alla scatola di derivazione ausiliaria e fare passare i fili attraverso il gruppo e la scatola di derivazione ausiliaria. Fissare il rilevatore IRmax avvitando saldamente il colletto al pressacavo. Serrare il grano. d. Il corpo principale del rilevatore IRmax può essere orientato orizzontalmente a qualunque angolazione, a condizione che sia fissato meccanicamente, che non interferisca con altre apparecchiature e che sia facilmente accessibile per la manutenzione. e. Per istruzioni sul cablaggio consultare la sezione 2.6. Vedere anche lo Schema 4, pagina 119. 2.5 Requisiti per il cablaggio I collegamenti elettrici al rilevatore IRmax devono essere conformi alle norme approvate dall’autorità locale in materia e soddisfare i requisiti elettrici del rilevatore IRmax. Crowcon raccomanda l’uso di un cavo armato con filo in acciaio (SWA) e di un pressacavo antideflagrante. Tecniche di cablaggio alternative, quali tubi in acciaio, sono accettabili solo se a norma. La lunghezza massima raccomandata dei cavi è 3,4 km (v. Tabella 1). Italiano Il rilevatore IRmax richiede un’alimentazione cc di 12-30V.c.c. Controllare che la tensione erogata al rilevatore IRmax dal quadro di comando sia 12V minimo, tenendo conto della caduta di tensione dovuta alla resistenza del cavo a una corrente di picco di 0,1A. Normalmente, un cavo da 1,5 mm2 consente di coprire una lunghezza massima di 3,0 km. La tabella 1 sotto mostra le distanze massime dei cavi secondo i parametri standard. C.S.A. Resistenza Distanza max. >20 V Distanza max. da 18 a 20 V mm2 (Ohm per km) (km) (km) 1,0 18,4 2,2 1,6 1,5 13,0 3,0 2,3 2,5 11,5 3,4 2,6 Tabella 1: distanze max. per cavi tipici 122 Detecting Gas Saving Lives 2. Installazione 2.6 Collegamenti e impostazioni Tutti i collegamenti descritti si riferiscono alla morsettiera montata nel corpo principale del connettore del rilevatore IRmax. I terminali della scheda a circuiti stampati del connettore IRmax sono contrassegnati con ‘+’, ‘sig’ e ‘0 V’. Rispettare la polarità corretta al momento di collegare il rilevatore IRmax all’apparecchiatura di controllo. Il rilevatore IRmax è preimpostato come dispositivo con corrente a ‘pozzo di corrente’, salvo diversamente specificato al momento dell’ordine. Per impostare l’apparecchio a ‘sorgente di corrente’, smontare la piastra posteriore e spostare i due collegamenti della scheda a circuiti stampati dalla posizione ‘sink’ alla posizione ‘source’, come mostrato nello Schema 7. Nota: il terminale esterno di terra può essere usato solo se permesso o richiesto dalle autorità locali competenti. Per limitare l'interferenza prodotta dalle radiofrequenze, si consiglia - per quanto possibile - di eseguire la messa a terra della scatola di derivazione ausiliaria e dell’armatura del cavo solo nel quadro di comando (aerea sicura) per evitare ritorni di terra. +V 0V Sg 1 2 3 Controllore CONTROLLER Sink Impostazioni ponticello EARTH 1 2 3 Rosso +V Nero 0V Verde Segnale Source Connettore per kit comunicazione PC Connettore IR Display LED di stato Schema 7: punto di installazione ponticello sink/source Il segnale 4-20mA può essere impostato come corrente 'Sink' o 'Source' utilizzando i pin e il ponticello mostrati nello Schema 7. Impostare la corrente su ‘Sink’ collegando il ponticello ai pin 3 e 4 come mostrato nella fotografia a sinistra. Impostare la corrente su ‘Source’ collegando il ponticello ai pin 1 e 2 come mostrato nella fotografia a destra. I rilevatori IRmax sono impostati con corrente 'Sink' salvo diversamente specificato al momento dell’ordine. Indicatore LED: la scheda a circuiti stampati è dotata di un LED per indicare lo stato operativo della corrente. Per ulteriori informazioni consultare la Sezione 6 a pagina 129. Detecting Gas Saving Lives 123 Italiano Cablaggio Numero Colore Funzione 3. Funzionamento AVVERTENZA Prima di eseguire qualunque intervento, garantire l’ottemperanza alle norme locali e alle procedure stabilite dal sito. Non tentare mai di aprire il rilevatore o la scatola di derivazione ausiliaria in presenza di gas infiammabili. Accertarsi che il quadro di comando associato sia inibito per evitare falsi allarmi. 3.1 Commissioning procedure 1. Controllare che: a. i collegamenti dei cavi siano corretti b. la tensione di alimentazione nella scheda di controllo sia impostata tra 18 e 30 V. La tensione misurata in corrispondenza dei terminali del rilevatore IRmax (nella scatola di giunzione Exe, se utilizzata, o in corrispondenza della scheda a circuiti stampati del rilevatore IRmax) deve essere impostata tra 12 e 30 V. c. i collegamenti siano impostati per una corrente 4-20 mA sink o source in base alla scheda di controllo. 2. Dopo l’accensione, attendere almeno 30 minuti prima di procedere all’azzeramento/ calibrazione per consentire al dispositivo di raggiungere la stabilità termica. (Nota: Il rilevatore IRmax è pronto al funzionamento 30 secondi dopo l’accensione.) 3. Controllare che l’aria sia pulita (nessun gas idrocarburo) prima di procedere all’azzeramento. Effettuare la lettura dello zero sulla scheda di controllo (consultare le istruzioni della scheda di controllo). Italiano 4. Montare il cappuccio di calibrazione sulla copertura protettiva per isolare la camera di misurazione dall’aria ambiente. Questa copertura è disponibile rivolgendosi a Crowcon (M041007). Collegare il gas di calibrazione (50% LEL nom) ed erogare alla portata di 1 litro/ minuto. 5. Dopo 30 secondi, regolare calibrazione/span sulla scheda di controllo in modo che il display visualizzi 50% LEL o corrisponda alla concentrazione del gas di calibrazione erogato. Il rilevatore IRmax non dovrebbe richiedere alcuna calibrazione. 6. Interrompere l’erogazione del gas e rimuovere il cappuccio di calibrazione. Verificare nuovamente l’azzeramento. 7. Al momento dell’installazione, o dopo avere cambiato lo specchio, il rilevatore può essere azzerato e calibrato utilizzando un accessorio dell’unità IR Display (vedere pagina 113) o mediante un kit di comunicazione con il PC (vedere il manuale degli accessori IRmax). Nota: i rilevatori IRmax certificati ATEX sono forniti calibrati in conformità alla norma EN61779 (dove, per esempio 100% LEL Metano = 4,4% volume). Nota: si raccomanda di utilizzare il cappuccio di calibrazione per la messa in servizio iniziale. Le calibrature successive possono essere eseguite erogando gas alla copertura protettiva a distanza mediante il tubo (evitando pertanto la necessità di accedere direttamente al rilevatore). La calibrazione senza il cappuccio (i.e. direttamente mediante la copertura protettiva) può essere eseguita a condizione che la velocità del vento sia inferiore a 2 metri/ secondo. La portata del gas deve essere superiore a 2,0 litri/minuto. 124 Detecting Gas Saving Lives 3. Funzionamento 3.2 Manutenzione ordinaria Le pratiche del sito indicano la frequenza di verifica dei rilevatori. Crowcon consiglia di testare i rilevatori IRmax con gas almeno ogni 6 mesi e di eseguire una nuova calibrazione ove e quando necessario. Per eseguire una nuova calibrazione, seguire la procedura riportata nella Sezione 3.1. In caso di guasto ai componenti elettronici, rivolgersi al rappresentante Crowcon di zona. Intervalli di calibrazione: Crowcon raccomanda di eseguire la calibrazione a intervalli di 12 mesi. Calibrazione a distanza mediante tubo: la velocità del vento deve essere inferiore a 2,0 metri/ secondo. Se superiore, usare il cappuccio di calibrazione per evitare la diluizione del gas. Pulizia dell sistema ottico: non raccomandata salvo in caso di guasti dovuti a oscuramento del percorso ottico. In caso di contaminazione della finestrina o dello specchio, pulire bene con acqua. (vedere Sezione 5, Accessori e ricambi, a pagina 128).  se la condensa inizia a causare guasti, sostituire lo specchio (è possibile che il rivestimento ottico sia danneggiato). Crowcon raccomanda di sostituire lo specchio ogni 5 anni. 3.3 Applicazioni con rilevazione di più gas Tutti i rilevatori IRmax sono forniti precalibrati per un certo tipo di gas (ad esempio metano o propano). Se è necessario eseguire la ricalibrazione per un gas di diverso tipo, il rilevatore IRmax può essere riconfigurato usando il kit di comunicazione per PC (vedere Sezione 5, Accessori e ricambi, a pagina 128), e successivamente calibrato. Detecting Gas Saving Lives 125 Italiano Mirrors:  se danneggiato, rivolgersi a Crowcon per ordinare il ricambio (vedere Sezione 5, Accessori e ricambi, a pagina 128). Dopo la sostituzione dello specchio, il rilevatore IRmax deve essere sempre azzerato e ricalibrato. 3. Funzionamento 3.4 Risposte relative ai tipi di gas Il grafico riportato di seguito mostra le risposte relative ad altri tipi di gas ottenute con un rilevatore IRmax calibrato per il metano. Nota: i rilevatori IR rilevano molti gas e vapori di idrocarburi più facilmente rispetto al metano. La risposta di IRmax (e di altri rilevatori di gas IR) sarà lineare nel range da 0 a 100%LEL per il gas target (il metano nell’esempio specifico), ma non-lineare per altri idrocarburi eventualmente presenti. Italiano Schema 8 Il diagramma mostra la risposta dei gas menzionati sopra: da sinistra a destra propano, butano, pentano e metano. Per ulteriori informazioni su altri tipi di gas e gamme disponibili contattare Crowcon. 126 Detecting Gas Saving Lives Materiale corpo Acciaio inox 316 Dimensioni (Solo rilevatore) 150 mm x 75 mm x 66 mm (senza tubo) Peso IRmax 1,58 kg IRmax con unità IR Display fissa 2 kg IRmax con barriera IS 2,4 kg IR Display remoto 0,2 kg Tensione operativa Da 12Vcc a 30V cc Alimentazione <1W Uscita 4-20 mA a 3 fili (Sink o Source) Segnale di guasto <1 mA Resistenza max. circuito cavo 80 Ohm (relativo al terminale –ve) Temperatura operativa Da -40°C a +75°C Umidità 0–100% umidità relativa Grado di protezione IP66 Protezione antideflagrazione Antideflagrante Codice di approvazione ATEX IRmax (senza IR Display) II 2 GD Exd db IIC T6 Gb (Tamb = -40°C a +50°C) II 2 GD Exd db IIC T4 Gb (Tamb = -40°C a +75°C) II 2 GD Ex tb IIIC T135°C Db (-40°C ≤ Ta≤ +75°C) IRmax con modulo barriera IS (display remoto) II 2 GD Exd db ia IIC T4 Gb (Tamb = -40°C a +75°C) Ex tb ia IIIC T135°C Db (Tamb = -40°C a +40°C) IRmax con display IR fisso II 2 G Exd db ia IIC T4 Gb (Tamb = -40°C a +75°C) Numero di certificato di sicurezza ATEX e IECEx IRmax (senza IR Display): Baseefa 09ATEX0206X e IECEx BAS.09.0109X IRmax (con IR Display): Baseefa 09ATEX0220X e IECEx BAS.09.0104X Sicurezza funzionale Omologato per l’uso in un sistema SIL 2. Numero di omologazione: Sira 12ATEX1206X Norme EN 60079-0:2012+A11:2013, EN 60079-1:2014, EN 60079-31:2014 IEC 60079-0:2011, IEC 60079-1:2014, IEC 60079-31:2013 EN 60079-29-1:2007, IEC 61508:2010, EN50402:2005 Zone Certificato per l’uso in Zona 1 o Zona 2 EMC EN50270 Detecting Gas Saving Lives 127 Italiano 4. Dati tecnici 5. Accessori e ricambi Italiano Numeri di parte Nome Descrizione M041007 Cappuccio di calibrazione Si monta sulla copertura anti-intemperie standard per eseguire la calibrazione quando la velocità del vento supera i 2 metri/secondo. S012130 Kit staffa di montaggio Consente il montaggio su parete o tubo da 50 mm. Non richiesto se il rilevatore IRmax viene montato su una scatola di giunzione preesistente. S012152 Schermo solare/cono collettore Può essere montato sul rilevatore IRmax per proteggerlo da temperature elevate causate dall’esposizione alla luce solare diretta e/o per estendere l’ingombro del rilevatore e rilevare gas più leggeri dell’aria (ad esempio, metano). S012169 Kit montaggio condotta Consente il monitoraggio in condotte da 300 mm a 3000 mm e con flussi d’aria compresi tra 2 m/s e 20 m/s. S012996 Adattatore di flusso Per applicazioni di campionamento dei gas. S012827 Kit di comunicazione PC Modulo, software e cavo di comunicazione per la configurazione del rilevatore. M20: S012295 ½” NPT: S012296 Scatola di derivazione ausiliaria Opzione di montaggio del rilevatore IRmax negli ambienti pericolosi. C011210 Kit pulizia specchio Contiene salviette IPA impregnate e un panno microfibra Ricambi del rilevatore IRmax Per informazioni sui ricambi fare riferimento allo Schema 3 a pagina 117. 128 Detecting Gas Saving Lives 6. Diagnostica 6.1 Errori segnalati dal LED IL LED montato sulla scheda a circuiti stampati del terminale può assistere l’operatore nell’individuazione dei guasti. La posizione del LED è illustrata nello Schema 7, pagina 123. La tabella sotto spiega come interpretare il guasto per ciascun tipo di lampeggio. Stato rilevatore Lampeggio regolare ogni secondo. Funzionamento corretto. Azione Acceso, brevi segnali acustici e spento. Rilevatore in modalità di avvio. Attendere 10 secondi. Lampeggio veloce e irregolare. Tensione di alimentazione troppo bassa o troppo alta. Controllare che la tensione di alimentazione del rilevatore IRmax sia impostata correttamente. Effettuare la misurazione direttamente in corrispondenza dei terminali del rilevatore IRmax. Sempre acceso. Guasto, errore host o I-module. Spegnere e riaccendere il rilevatore IRmax; se il guasto persiste, rispedire a Crowcon. Due lampeggi lunghi seguiti da un lampeggio corto. Errore irreversibile; lampada o rilevatore guasto. Rispedire a Crowcon. Doppio lampeggio rapido ogni secondo. Errore irreversibile, guasto modulo o configurazione. Verificare la configurazione del rilevatore IRmax utilizzando kit di comunicazione PC software. Controllare l’alimentazione. Se il guasto persiste, rispedire a Crowcon. Breve segnale acustico ogni secondo. Sistema ottico oscurato. Verificare finestrina e specchio e pulirli se necessario. Riazzerare il rilevatore IRmax e verificare la calibrazione. Altri guasti possono essere corretti solo rispedendo il rilevatore IRmax a Crowcon o a un tecnico di assistenza autorizzato. 6.2 Uscita analogica Se il segnale analogico di uscita è fallito o se non è connesso ad un sistema di controllo o ad un resistore di carico, l’IRmax rimarrà in stato di Errore, e sul display IR (se presente) apparirà anche la scritta “Necessaria Manutenzione” (Service required). L’IRmax tiene sotto controllo attivo il segnale analogico di uscita 4-20mA per verificare che sia nel campo di valori giusto. Se il segnale è fuori specifica, il rivelatore si porta in modalità di errore e il segnale di uscita viene impostato su 1mA. Così, quando si esegue la verifica di un rivelatore, è essenziale che questo sia collegato ad un pannello di controllo o che un resistore di carico da 100Ω sia collegato fra i terminali ‘0 V’ e ‘Sig’ (rivelatore impostato su modalità ‘Source’) o fra i terminali ‘0 V’ e ‘+V’ (rilevatore impostato su modalità ‘Sink’). Detecting Gas Saving Lives 129 Italiano Comportamento LED 7. Configurazione Modbus RS485 7.1 Considerazioni generali La presente sezione illustra l’utilizzo dei rilevatori IRmax in una configurazione Modbus. Per queste applicazioni è disponibile una versione con abilitazione RS485. È possibile collegare fino a 28 rilevatori IRmax in configurazioni a stella o a bus, come descritto di seguito. I collegamenti al rilevatore IRmax versione RS485 devono essere effettuati mediante attacco a una scatola di derivazione ausiliaria (vedere Sezione 5 a pagina 128), piuttosto che mediante collegamento diretto del cablaggio al rilevatore. Tenere presente che l’unità IR Display non può essere utilizzata con un rilevatore IRmax con abilitazione RS485. La versione del rilevatore IRmax con abilitazione RS485 è dotata di cinque terminali di campo. Questi terminali sono: 1 Alimentazione positiva Da 12 V a 30 V sopra 0 V 2 0V Ritorno e riferimento RS485 3 Segnale 4-20 mA Segnale Source o Sink (opzionale) 4 RS485 B Segnale differenziale RS485 5 RS485 A Segnale differenziale RS485 I segnali sui terminali RS485 sono conformi allo standard EIA/TIA-485, pertanto la gamma della modalità comune è compresa tra -7V e +12V rispetto al terminale 0V. Italiano Tenere presente che l’assegnazione della polarità dei segnali A e B non è unanime tra i produttori RS485. Se il collegamento non funziona in un modo, invertire i fili RS485 A e B. Non sussiste alcun rischio di effettuare un collegamento sbagliato. Le impostazioni della comunicazione sono 9600 bps, due stop bit e no parity. Al momento di creare l’interfaccia per un sistema di controllo, è importante considerare la quantità di tempo necessaria al sistema per raccogliere le informazioni da ciascun rilevatore. La velocità massima di raccolta dei dati da più rilevatori è 14 rilevatori al secondo, ma le condizioni pratiche possono ridurre questa velocità a 7 rilevatori al secondo. Spetta agli utenti verificare che la disposizione scelta consenta la rilevazione dei segnali di allarme entro limiti di tempo accettabili. Inoltre, è importante controllare che il sistema sia in grado di erogare una potenza sufficiente a tenere in funzione tutti i rilevatori. Per calcolare la potenza richiesta in un collegamento a bus lineare vedere Sezione 7.3, Considerazioni generali, pagina 132. Per istruzioni dettagliati relative al Modbus contattare Crowcon (all’indirizzo riportato a tergo). 130 Detecting Gas Saving Lives 7. Configurazione Modbus RS485 7.2 Topologia di collegamento Le due topologie di collegamento comunemente usate sono a stella e a bus lineare. 7.2.1 Collegamento a stella Nella topologia a stella, tutti i rilevatori sono collegati a un nodo centrale, normalmente rappresentato dal quadro di comando. Nessun cavo deve avere più di 5 anime in quanto tutti i collegamenti dei segnali da 4-20mA fanno direttamente capo al quadro di comando. I segnali RS485 A e B possono essere collegati insieme nel punto a stella. Il bus deve essere terminato nel punto a stella con un’unica resistenza di terminazione da 110 ohm. La lunghezza di ciascun raggio della stella non deve essere maggiore a 750 metri. 7.2.2 Collegamento a bus lineare Nella topologia a bus tutti i rilevatori IRmax sono collegati secondo una disposizione lineare, normalmente con il quadro di comando ad un’estremità. Una situazione classica è rappresentata dall’installazione a tunnel, con i rilevatori IRmax installati a intervalli regolari (vedere Schema 9 sotto). Per collegare l’installazione occorre montare due resistenze di terminazione da 110 ohm alle due estremità fisiche del bus. Poiché i segnali da 4-20mA non possono essere condivisi, occorre installare un conduttore aggiuntivo per ciascun nodo intermedio. Se non viene utilizzato nessuno dei segnali da 4-20mA, questa installazione richiede solo quattro conduttori. AL QUADRO DI COMANDO Schema 9 Detecting Gas Saving Lives 131 Italiano SCHEMA COLLEGAMENTO BUS LINEARE 7. Configurazione Modbus RS485 7.3 Requisiti di cablaggio 7.3.1 Calcolo del livello minimo di potenza richiesto Quanti più rilevatori IRmax sono collegati al bus lineare, tanto maggiore la potenza richiesta per alimentare il sistema. Per calcolare la potenza richiesta per una data configurazione, è necessario conoscere la resistenza dei cavi tra ciascuna coppia di rilevatori IRmax. Occorre calcolare una corrente di almeno 0,1mA per ciascun nodo intermedio tra rilevatori. La tensione da erogare può essere calcolata stimando la caduta di tensione per ciascun nodo intermedio – alla fine devono restare almeno 12V per garantire il corretto funzionamento dell’ultimo rilevatore IRmax. Contattare Crowcon per richiedere consulenze relative a casi specifici oppure seguire la procedura riportata sotto ed eseguire il semplice calcolo illustrato nella sezione successiva. 1. La tensione non deve scendere al di sotto di 12V, pertanto si raccomanda di iniziare il calcolo impostando su questo valore la tensione dell’ultimo rilevatore IRmax della linea. 2. Ciascun rilevatore IRmax può assorbire fino a 0,1 A. Calcolare la perdita di tensione del cavo del primo nodo intermedio tra rilevatori assumendo che la ‘corrente aggregata’ sia pari a 0,1A e moltiplicando questo valore per la resistenza del cavo del nodo intermedio tra l’ultimo e il penultimo rilevatore IRmax. 3. Aggiungere questa caduta di tensione ai 12V iniziali per ottenere la tensione minima accettabile al penultimo rilevatore IRmax. Aggiungere 0,1A al valore della ‘corrente aggregata’ per arrivare a 0,2mA, la corrente minima che alimenta il penultimo nodo intermedio del bus. Moltiplicando questo valore per la resistenza del cavo per il penultimo nodo intermedio si ottiene la caduta di tensione successiva. 4. Ripetere questa procedura per ciascun rilevatore IRmax, accumulando le cadute di tensione che si verificheranno tra ciascun rilevatore IRmax. 5. Non superare la tensione massima di 30V dei rilevatori. Italiano 7.3.2 Esempio di calcolo A titolo esemplificativo, la tabella seguente riporta i risultati del calcolo per sei rilevatori IRmax equidistanti installati a una distanza di 250m su un cavo di sezione pari a 1 mm2. Ciascun nodo intermedio ha una resistenza di 4,6 ohm. Stazione Tensione di alimentazione Corrente di alimentazione 1 12 0,1 A 2 12,46 0,2 A 3 13,38 0,3 A 4 14,76 0,4 A 5 16,6 0,5 A 6 18,9 0,6 A Alimentazione quadro 21,66 0,6 A 132 Detecting Gas Saving Lives 8. Manuale della sicurezza funzionale 8.1 Introduzione Le sezioni seguenti contengono informazioni relative all’omologazione del rilevatore IRmax in base alle norme di sicurezza funzionale IEC 61508 e EN 50402. Queste informazioni riguardano le caratteristiche riportate nel dossier di sicurezza e nei requisiti e dati di manutenzione per consentire l'integrazione del rilevatore IRmax in un sistema strumentale di sicurezza (SIS). 8.2 Funzione di sicurezza IRmax e IRmax Modbus Per la misurazione della concentrazione di gas infiammabili e l’indicazione della misurazione mediante un’uscita 4-20mA. I guasti relativi alla funzione di sicurezza vengono rilevati dall’hardware e dal relativo firmware. Tali guasti saranno rilevati come un segnale di uscita inferiore a 3,6mA o superiore a 21mA. Nome parametro Simbolo Equazione / sorgente Intervallo test funzionale T1 Secondo istruzioni Crowcon. Tempo medio alla riparazione MTTR Secondo istruzioni Crowcon. IRmax 8.760 ore (annuale) 8 ore Tipo A/B Tipo A Secondo istruzioni Crowcon. Tipo B Guasti totali: λ Da FMEDA 1.04E-05 Guasti sicuri diagnosticati: λSD Da FMEDA 1.95E-08 Guasti sicuri non diagnosticati: λSU Da FMEDA 8.59E-08 Guasti pericolosi diagnosticati: λDD Da FMEDA 9.74E-06 Guasti pericolosi non diagnosticati: λDU Da FMEDA 5.06E-07 Guasti senza effetti per la sicurezza: λNE Da FMEDA 3.21E-09 Copertura diagnostica: λDD / (λDU + λDD) 95.06% DC Frazione dei guasti sicuri: SFF (λSD + λSU + λDD) / λ 95.11% Indisponibilità equivalente per (λDU / λD)(T/2 + MTTR) + tCE 2.24E+02 canale (λDD / λD ) MTTR PFDAVG (usando l’equazione PFDAVG (λDU + λDD) tCE 2.30E-03 61508-6) PFDAVG (usando l’equazione PFDAVG λDU (T / 2+MTTR) + (λDD MTTR) 2.30E-03 semplificata) PFDAVG (usando l’equazione IEC PFDAVG 1-ε-(λdd+λdu) tce 2.30E-03 61508-6) Capacità SIL (modalità a domanda SIL2 bassa) Capacità SIL (modalità a domanda SIL2 alta) Per quanto concerne i guasti hardware casuali e la frazione di guasti sicuri nelle applicazione a domanda bassa, tutte le varianti del sistema risultano adatte all’uso nelle applicazioni SIL 2. Detecting Gas Saving Lives 133 Italiano 8.3 Dati di sicurezza funzionale Manuale della sicurezza funzionale 8.4 Configurazione dell’hardware Per la valutazione del livello di integrità della sicurezza dell’hardware è stata adottata la Route 1H (tolleranza ai guasti hardware e frazione dei guasti sicuri). 8.5 Configurazione del software La valutazione del firmware del prodotto è stata effettuata conformemente ai requisiti stabiliti dalla norma IEC 61508:3 2010. 8.6 Guasti sistematici Per la conformità ai requisiti di prevenzione dei guasti sistematici è stata adottata la Route 1S (come stabilito dalla norma IEC 61508:2 2010 paragrafo 7.4.2.2c). 8.7 Intervallo diagnostico La maggior parte delle funzioni diagnostiche vengono monitorate continuamente. Le verifiche del sistema watchdog devono essere eseguite durante il test funzionale annuale spegnendo e riaccendendo lo strumento: IRmax deve essere sottoposto a un ciclo di accensione e spegnimento una volta l’anno (scollegando l’alimentazione 24Vcc e ricollegandola), come previsto nel programma di manutenzione del prodotto (leggere anche la sezione 3.2). 8.8 Limiti Le percentuali di guasto sono costanti. Italiano Eventuali guasti non rilevati saranno registrati dal test funzionale da eseguirsi almeno una volta l’anno. Eventuali guasti non rilevati saranno registrati dal test funzionale da eseguirsi almeno una volta l’anno. Si presume che l’utente utilizzi la funzionalità diagnostica fornita mediante l’accessorio del display IR e/o l'interfaccia PC per ridurre l’indisponibilità potenziale del prodotto. La valutazione dell’affidabilità è una procedura statistica usata per applicare i dati storici dei guasti alle configurazioni e ai design proposti. Pertanto, questa valutazione fornisce un target/ stima credibili della probabile affidabilità dell’apparecchiatura, presumendo che le condizioni di fabbricazione, progettazione e funzionamento siano identiche a quelle usate per la raccolta dei dati. Questa utile tecnica di verifica in fase di progettazione consente di confrontare design alternativi, stabilendo target prestazionali per ordine di grandezza e valutando i possibili effetti prodotti da modifiche apportate al progetto. Gli effettivi valori previsti, tuttavia, non possono essere garantiti in quanto il numero preciso di guasti che si verificheranno su campo dipende da molti fattori al di fuori del controllo di un mero esercizio predittivo. Per le finalità di questa previsione, si presuppone che i tassi di guasto (simbolo λ) siano costanti nel tempo. I guasti precoci e di usura ridurrebbero l’affidabilità, tuttavia si presuppone che vengano eliminati rispettivamente mediante burn in e sostituzione preventiva. 134 Detecting Gas Saving Lives Manuale della sicurezza funzionale La probabilità di guasto a richiesta corrisponde alla probabilità che il sistema entri in stato di guasto in un momento qualunque. Questa espressione è sinonimo di indisponibilità in stato stazionario, calcolata come: Indisponibilità = (λ x MDT)/(1 + (λ x MDT)) che approssima λ x MDT per valori bassi di λ x MDT dove λ è il tasso di guasto e MDT è la durata media di indisponibilità. Questo valore è confermato dall’espressione per la disponibilità, calcolata come: MTBF/ (MTBF+MDT) I tassi di guasto adottati, e pertanto le disponibilità derivate, sono valori verosimilmente associati a un design comprovato dopo un periodo di affidabilità della crescita di durata idonea. 8.9 Ambientale Limiti ambientali: Il prodotto deve essere utilizzato entro un intervallo massimo di temperatura compreso tra -40°C e +75 °C Il prodotto deve essere utilizzato entro un intervallo massimo di temperatura compreso tra -40°C e +80 °C Il prodotto ha una protezione di ingresso di classe IP66 conformemente alle definizioni contenute nella norma EN60529. Il prodotto è progettato per il funzionamento continuo. 8.10 Tolleranza ai guasti hardware L’HFT è 0. 8.11 Capacità sistematica IREX/IRmax appartiene alla Classe SC2. 8.12 Classificazione IREX/IRmax è un componente di tipo B. Detecting Gas Saving Lives 135 Italiano Il prodotto deve essere utilizzato entro un intervallo massimo di umidità relativa ambiente compreso tra 0% e +100 % di condensa Garanzia Prima della spedizione al cliente, questo apparecchio è stato sottoposto a test completi e a calibrazione. Se, entro il periodo di garanzia o tre anni dalla consegna, l’apparecchio risultasse difettoso per ragioni imputabili a difetti di lavorazione o materiali, ci impegniamo a nostra discrezione a provvedere alla sua riparazione o sostituzione senza ulteriori addebiti al cliente, fatte salve le condizioni riportate di seguito. Procedura per i reclami in garanzia Per consentire una gestione più efficiente dei reclami in garanzia, si prega di chiamare il team di assistenza clienti Crowcon al numero +44 (0)1235 557711 indicando i dati seguenti: nome, numero di telefono, numero di fax e indirizzo e-mail; descrizione e quantità delle merci da rispedire, compresi eventuali accessori. numero(i) di matricola; Reason for return. Munirsi di un modulo di restituzione per consentire l’identificazione e la tracciabilità dell’apparecchio. Questo modulo può essere scaricato dal nostro sito web ‘crowconsupport.com’ insieme all’etichetta per la restituzione. In alternativa, rivolgersi a Crowcon per richiedere l‘invio di una copia tramite e-mail. Non si accettano resi in garanzia non accompagnati dall’apposito codice CRN rilasciato da Crowcon. È essenziale che l’etichetta con l’indirizzo sia correttamente attaccata all’imballaggio esterno della merce resa. La garanzia sarà invalidata qualora si rilevi che l’apparecchio è stato alterato, modificato, smontato o manomesso. La garanzia non copre danni causati dall’utilizzo inadeguato o improprio dell’apparecchio. Italiano Limitazione di garanzia Crowcon declina qualunque responsabilità per perdite o danni consequenziali o indiretti (ivi compresi perdite o danni conseguenti all'utilizzo dell’apparecchio) ed esclude espressamente qualunque responsabilità verso terzi. La presente garanzia non copre la precisione di calibrazione dell’apparecchio o la finitura cosmetica del prodotto. L’apparecchio deve essere sottoposto a manutenzione conformemente alle istruzioni contenute nel relativo manuale d'uso e manutenzione. La garanzia delle parti di ricambio (p. es. specchio) fornite in sostituzione di elementi difettosi in garanzia è limitata al termine di validità della garanzia dell’apparecchio originariamente fornito. Crowcon si riserva il diritto di ridurre o declinare il periodo di garanzia dei sensori se destinati all’impiego in ambienti o applicazioni che li espongono a rischi noti di usura o danneggiamento dei sensori. La responsabilità di Crowcon in caso di apparecchiature difettose è limitata agli obblighi previsti dalla presente garanzia; entro i limiti consentiti dalla legge, Crowcon declina qualunque garanzia estesa, condizione o dichiarazione – espressa o implicita, prevista per legge o di altro genere – relativa alla qualità commerciabile dell’apparecchiatura o alla sua idoneità a scopi particolari. La presente garanzia non limita i diritti del cliente previsti per legge. 136 Detecting Gas Saving Lives Garanzia Crowcon si riserva il diritto di addebitare le spese di spedizione e consegna qualora l’apparecchiatura resa come difettosa richieda solo un normale intervento di calibrazione o manutenzione e il cliente non dia il proprio consenso a procedere. Per qualunque richiesta relativa alla garanzia e all’assistenza tecnica contattare: Customer Support Tel: +44 (0) 1235 557711 Fax: +44 (0) 1235 557722 Italiano Email: [email protected] Detecting Gas Saving Lives 137 Inhoud Concept en veiligheid................................................................................ 141 IRmax detector concept.................................................................... 141 Veiligheidsinformatie.......................................................................... 142 Productoverzicht................................................................................ 143 1. Inleiding................................................................................................ 144 1.1 Algemeen.................................................................................... 144 1.2 Productbeschrijving...................................................................... 144 2. Installatie............................................................................................... 146 WAARSCHUWING ............................................................................ 146 2.1 Locatie......................................................................................... 146 2.2 Montage...................................................................................... 147 2.3 Bekabeling rechtstreeks naar de IRmax detector ........................ 147 2.3.1 Plaats van klemmen............................................................ 148 2.3.2 De IRmax detector installeren met een montagebeugel...... 148 2.4 Installatie met een ringpakking en extra junction box................... 149 2.4.1 De IRmax detector op een extra junction box bevestigen:.. 150 2.5 Kabelvereisten.............................................................................. 150 2.6 Aansluitingen en instellingen....................................................... 151 3. Bediening.............................................................................................. 152 3.1 Inbedrijfstelling............................................................................ 152 3.2 Routineonderhoud....................................................................... 153 3.3 Gassoorten wijzigen..................................................................... 153 3.4 Relatieve respons van gassoorten................................................. 154 4. Specificatie............................................................................................ 155 5. Accessoires en reserveonderdelen.......................................................... 156 6. Problemen oplossen ............................................................................ 157 6.1 Fouten gesignaleerd door LED...................................................... 157 6.2 Analoge uitgang.......................................................................... 157 7. Configuratie RS485 Modbus................................................................. 158 7.1 Algemeen.................................................................................... 158 7.2 Bedradingstopologie.................................................................... 159 7.2.1 Steraansluiting.................................................................... 159 7.2.2 Lineaire busaansluiting........................................................ 159 7.3 Bekabelingsvereisten.................................................................... 160 7.3.1 Berekenen van de minimum vereiste stroom ..................... 160 7.3.2 Voorbeeldberekening.......................................................... 160 8. Functionele veiligheidshandleiding......................................................... 161 8.1 Inleiding....................................................................................... 161 8.2 Modbus veiligheidsfunctie van IRmax en IRmax............................ 161 8.3 Informatie over functionele veiligheid........................................... 161 8.4 Hardwareconfiguratie.................................................................. 162 8.5 Softwareconfiguratie.................................................................... 162 8.6 Systematische storingen............................................................... 162 8.7 Diagnostisch interval.................................................................... 162 8.8 Beperkingen................................................................................. 162 8.9 Omgevingsfactoren...................................................................... 163 8.10 Hardwarestoringstolerantie........................................................ 163 8.11 Systematische capaciteit............................................................. 163 8.12 Classificatie................................................................................ 163 Garantie.................................................................................................... 164 Concept en veiligheid IRmax detector concept De IRmax detector is een ultracompacte infrarood (IR) gasdetector die snel en faalveilig koolwaterstofgassen en -dampen detecteert. Met een IR-sensor met dubbele golflengte in een robuuste 316 roestvrijstalen behuizing kan de IRmax detector in de zwaarste omstandigheden werken. In tegenstelling tot conventionele IR gasdetectors heeft de IRmax detector geen verwarmers om condensatie op ramen en spiegels te voorkomen. De STAY CLIR coating op de optische componenten voorkomt condensatievorming als de detector in bedrijf is. De IRmax detector is compatibel met een besturingssysteem van 4-20mA en kan ook geïnstalleerd worden in een RS485 Modbus netwerk (zie hoofdstuk 7). De IRmax detector verbruikt slechts 1 Watt vermogen, typisch 75-90% minder dan conventionele IR gasdetectors. De IRmax detector heeft een compacte diffusiekamer die, in combinatie met een effectieve weersbestendige kap, een uitmuntende responssnelheid geeft. De weersbestendige kap is ontworpen middels luchtstroomsoftware zodat kalibratie en gastoevoer op afstand van de detector mogelijk is gemaakt, zonder dat er een speciale kalibratiekap nodig is. De het IR Display kunt u de uitlezingen van de IRmax zowel plaatselijk als op afstand bekijken. De IR Display kan direct op de IRmax worden gemonteerd. Als alternatief kan de IRmax compleet met een intrinsiek veilige IS-barrièremodule worden geleverd. De IR Display kan dan op de IS-barrièremodule worden aangesloten, via een tijdelijke of permanente kabelverbinding. De leverbare opties staan in Afbeelding 3 op pagina 145 weergegeven. Nederlands Voor nadere informatie over andere accessoires voor de IRmax wordt u verwezen naar Afbeelding 3 op pagina 145 en hoofdstuk 5, pagina 156. Detecting Gas Saving Lives 141 Concept en veiligheid Veiligheidsinformatie • De IRmax gasdetectors moeten in strikte overeenstemming met deze instructies, waarschuwingen en labelinformatie geïnstalleerd, bediend en onderhouden worden en binnen de vermelde beperkingen. • De achterste moer op de IRmax detector moet tijdens bedrijf goed gesloten blijven. Probeer de achterste moer niet te verwijderen, totdat de stroom naar de detector afgesloten is. Anders kan een brandbare atmosfeer ontvlammen. Voordat de moer verwijderd wordt voor onderhoud of kalibratie, dient er gecontroleerd te worden of er geen brandbare gassen of dampen in de omliggende atmosfeer aanwezig zijn. Wacht een paar minuten nadat de stroom uitgeschakeld is, voordat de hij geopend wordt. • Onderhoud en kalibratie mogen uitsluitend gedaan worden door bevoegd onderhoudspersoneel. • Er mogen alleen echte Crowcon vervangingsonderdelen gebruikt worden; andere onderdelen kunnen de certificering en garantie van de IRmax detector ongeldig maken. • De IRmax detector moet tegen extreme vibratie en direct zonlicht in warme omgevingen beschermd worden omdat hierdoor de temperatuur van de IRmax detector boven de gespecificeerde limiet kan stijgen en voortijdige storing kan veroorzaken. • De IRmax detector detecteert geen waterstof, ammoniak of kooldioxide. • De apparatuur moet geaard zijn met behulp van de kabelpakking en de gepantserde stalen kabel. • Certificatie voor Zone 21/22, omgevingen met stof: IRmax basistoestel (zonder IR Display of IS Barrier module) kan worden gebruikt in omgevingen die explosiegevaarlijk stof bevatten (Zone 21 of 22). • IRmax met een IS Barrier module kan worden gebruikt in Zone 21 of 22, zolang de omgevingstemperatuur lager is dan 40°C en er een extern IR-display of handheld IR-displays buiten de explosiegevaarlijke zone zijn geïnstalleerd of worden gebruikt. • IRmax met een vast IR Display kan niet in een Zone 21 of 22 worden geïnstalleerd. Nederlands 142 Detecting Gas Saving Lives Concept en veiligheid Productoverzicht De IRmax detector is een infrarood gasdetector ontworpen om gewone koolwaterstofgassen te detecteren in het bereik van 0 tot 100%LEL (onderste explosiegrens: de minimum concentratie in de lucht waarop ontvlamming kan ontstaan). De IRmax detector is een gecertificeerde explosieveilige (Exd) detector, die gebruikt kan worden in gevaarlijke gebieden ATEX zone 1 of Zone 2. Bekijk het certificeringslabel aan de zijkant van de detector voor de soort certificering op het betreffende product. N.B.: Als er geen certificeringslabel op de IRmax detector zit, is de detector niet gecertificeerd voor gebruik in gevaarlijke gebieden. IR GAS DE TECTOR 1180 IR GAS DETECTOR WITH REMOTE DISPLAY II 2 GD 1180 V m ax= 32V W m ax= 5W II 2GD Vmax=32V Wmax=5W B a s e e fa 0 9 A T E X 0 2 0 6 X IE C E x B A S 0 9 . 0 1 0 9 X S IL 2 S i r a 1 2 A T E X 1 2 0 6 X Baseefa09ATEX0220X IECEx BAS 09.0104X Ex db ia IIC T4 Gb (-40°C ≤ Ta ≤ +75°C) Ex tb ia IIIC T135°C Db (-40°C ≤ Ta ≤ +40°C) E x d b II C T 4 Gb (T am b = -40 °C to + 75 °C ) E x d b II C T 6 Gb (T am b = -40 °C to + 50 °C ) E x tb II IC T 135° C D b (-4 0° C T a + 75° C ) WARNING: DO NOT OPEN WHEN EXPLOSIVE ATMOSPHERE MAY BE PRESENT. W A R N IN G : D O N O T O P E N W H E N E X P L O S IV E A TM O S P H E R E M A Y B E P R E S E N T. Abingdon, United Kingdom, OX14 4SD A b i n g d o n , U nit e d K in g d o m , O X 1 4 4 S D Certificatie-etiket voor het IRmax basismodel Certificatie-etiket voor IRmax met IS Barrier IR GAS DETECTOR WITH DISPLAY 1180 II 2G Baseefa09ATEX0220X IECEx BAS 09.0104X Ex db ia IIC T4 Gb (-40°C Ta +75°C) WARNING: DO NOT OPEN WHEN EXPLOSIVE ATMOSPHERE MAY BE PRESENT. Abingdon, United Kingdom, OX14 4SD Certificatie-etiket voor IRmax met vast IR Display Afbeelding 1: IRmax detector certificeringslabels Detecting Gas Saving Lives 143 Nederlands Vmax=32V Wmax=5W 1. Inleiding 1.1 Algemeen De configuratie van elke IRmax detector wordt aangegeven door een label op het huis. Als u contact opneemt met Crowcon voor advies of reserveonderdelen, vermeldt dan het onderdeelnummer en het serienummer. 1.2 Productbeschrijving De IRmax detector bestaat uit een huis van 316 roestvrij staal, een antistatisch weersbestendige kap over de optische delen en een gasmetingskamer en een elektronicagedeelte. Er kan ook een IR Display bevestigd worden. Instructies voor het aanbrengen van de IR Display staan in de handleiding bij de IR Display (M07061). Er kan een optionele ringpakking geleverd worden, zodat de IRmax detector rechtstreeks op extra aansluitdozen aangesloten kan worden met een kabelinvoer van M20 of ½” NPT. Optionele ringpakking 74.5 74,5 Nederlands 60.5 57 totaal 157.5 158 totaal 136 totaal 136 kabelpakking M20 of 1/2" NPT Externe aardeklem (AARDE) Alle afmetingen zijn in millimeters Afbeelding 2: IRmax detector dimensionaal aanzicht N.B.: De behuizing van de IRmax detector wordt met twee kabelingangen geleverd; één is M20, één is 1/2" NPT. De kabelingang die niet gespecificeerd is bij het bestellen van een IRmax detector wordt met een gecertificeerde plug afgesloten. De IRmax moet worden geïnstalleerd met twee afgedichte kabelingangen: één met een kabelpakking, de ander met een gecertificeerde afdichtplug met een IP66-certificaat. 144 Detecting Gas Saving Lives 1. Inleiding 15 12 14 13 11 “ 10  ‘ ”  ‘ Ž    Œ Œ Kalibratiekap M041007  Weersbestendige kap M04995 Ž Spiegelborgring Samen geleverd als ‘spiegelvervangingsset’ C011206  Spiegel  Stroomadapter S012996 ‘ O-ring voor achtermoer, IS Barrier module voor vaste IR Display module: M040077  Montagebeugel (complete set) S012130 “ Kabelpakking M20 of 1/2"NPT: M20 ATEX: S012147, 1/2" NPT ATEX: S012190 ” Borgplaat en borgbouten voor achterplug, vast IR Display en IS Barrier module. } 10 11 12 13 14 15 IR Display vaste versie Connector IR Display naar IRmax detector E07987 IS-barrièremodule Verbindingssnoer IR Display Montagefitting Extern IR Display M03833 Extern IR Display Detecting Gas Saving Lives 145 Nederlands Afbeelding 3: IRmax detector uitvergroot aanzicht (onderdeelnummers aangegeven, waar van toepassing) 2. Installatie WAARSCHUWING • Deze detector is ontworpen voor gebruik in gevaarlijke gebieden van zone 1 en zone 2. De certificering is afhankelijk van de bevestigde accessoires en de omgevingstemperatuur. Zie de specificatietabel op pagina 155 voor informatie over de certificering. De installatie moet ook in overeenstemming zijn met de erkende normen van de betreffende instantie in het betrokken land. • Neem voor meer informatie contact op met Crowcon. Voordat er met installeren begonnen wordt, moet ervoor gezorgd worden dat de plaatselijke voorschriften en fabrieksprocedures opgevolgd worden. • De apparatuur moet geaard zijn via de kabelpakking en de gepantserde stalen kabel. • Probeer geen IR Display te monteren aan een IRmax detector die niet voor dat doel geschikt is. Detectors die met een display gebruikt worden, zijn gecertificeerd Exd ia, en moeten hetzij met een vast display bediend worden met een IS-barrière, of met een extern of handdisplay dat via een IS-barrièremodule van Crowcon is aangesloten. • Een IRmax detector die geleverd wordt zonder display, is gecertificeerd Exd IIC en deze kan niet met een IR Display gebruikt worden. 2.1 Locatie De IRmax detector dient daar gemonteerd te worden waar het het meest waarschijnlijk is dat het te detecteren gas aanwezig is. De volgende punten dienen in gedachten te worden gehouden bij het plaatsen van gasdetectors: • Om gassen te detecteren die lichter zijn dan lucht, zoals methaan, moeten detectors hoog geplaatst worden. Om gassen te detecteren die zwaarder zijn dan lucht, zoals brandbare dampen, moeten detectors laag geplaatst worden. • Denk bij het plaatsen van detectors aan mogelijke schade die door de natuur veroorzaakt kan worden, zoals regen of overstroming. Voor detectors die buiten in zeer warme gebieden gemonteerd worden, beveelt Crowcon het gebruik van een zonnekap aan (Zie hoofdstuk 5, Accessoires en reserveonderdelen, op pagina 144). Nederlands • Denk ook aan toegang voor functietesten en onderhoud. • Bedenk hoe het ontsnappende gas zich zal gedragen als gevolg van een natuurlijke of geforceerde luchtstroom. Monteer detectors in ventilatieleidingen indien van toepassing, gebruik hiervoor de IRmax detector leidingmontageset (Zie hoofdstuk 5, Accessoires en reserveonderdelen, op pagina 144). • Denk aan de procesomstandigheden. Butaan is bijvoorbeeld normaliter zwaarder dan lucht, maar als het vrijkomt bij een proces dat op een verhoogde temperatuur en/of druk is, kan het gas stijgen in plaats van dalen. De plaatsing van de sensoren dient bepaald te worden na advies van experts die specialistische kennis hebben van gasverspreiding en de verwerkingsapparatuur maar ook veiligheids- en technische kwesties. 146 Detecting Gas Saving Lives 2.2 Montage De IRmax detector kan op drie manieren gemonteerd worden: 1. Met de Crowcon montagebeugel met een directe veldkabelaansluiting (uitsluitend 4-20mA bedrijf). 2. Met een ringpakking voor aansluiting op een bestaan junction box met Exe- of Exc-certificering. Crowcon levert een geschikte pakkingring als optionele extra accessoire (zie 3 hieronder) 3. Met de optionele extra junction box en ringpakking van Crowcon. Optionele onderdelen staan in hoofdstuk 5 op pagina 156. De IRmax detector dient op de gewenste locatie geïnstalleerd te worden met de sensorkop +/- 15° horizontaal (oriëntatie staat op Afbeelding 2 op pagina 144). Zo kan er geen vuil of water op de optische componenten ophopen. 2.3 Bekabeling rechtstreeks naar de IRmax detector Deze optie is alleen geschikt bij een werking van 4-20mA. Er is een Crowcon montagebeugel nodig om de detector op een muur of pijp van 50 mm te bevestigen.. Status-LED Afbeelding 4: Veldkabelverbindingen op de IRmax Sluit veldkabels op de behuizing van de IRmax detector aan met een gecertificeerde wartel via de gekozen kabelingang (M20 of 1/2" NPT). Crowcon beveelt aan dat de kabelwartel naar beneden wijzend geïnstalleerd worden. Zorg ervoor dat er kabelpakkingen met de juiste Exd certificering gebruikt worden en dat de draadlengte niet langer is dan de in de afbeelding gespecificeerde lengte (links). 15mm MAX Detecting Gas Saving Lives 147 Nederlands Signal 0V (ground) +V (24V IRmax) 2.3.1 Plaats van klemmen Met de IRmax in de richting van Afbeelding 2 op pagina 144 weergegeven (M20 kabelingang bovenaan) dient de 3-aderige veldkabel als volgt afgesloten worden met de verwijderbare connector: +24V onderaan, 0V in het midden, signaal bovenaan. De 6-pins connector rechts van de printplaat is voor onderhoud en/of aansluiting van een IR Display module. + klem : + toevoer van de besturingskaart. Sig klem: Signaal van de besturingskaart. 0 V klem: - toevoer van de besturingskaart. 2.3.2 De IRmax detector installeren met een montagebeugel a. De IRmax kan in plaats van met een ringpakking met een montagebeugel (S012130) geleverd worden, zodat hij rechtstreeks op veldkabels gemonteerd kan worden (zie Afbeelding 5). Bevestigingsbeugel: 70 mm bussen het midden van de bevestigingen. Gebruik M6-bouten. Nederlands Afbeelding 5: De IRmax detector met een montagebeugel en kabelpakking b. Als de IRmax detector op een plat oppervlak gemonteerd wordt, markeer en boor dan twee gaten waarbij de montagebeugel als sjabloon gebruikt wordt. Bevestig twee delen van de beugel losjes vast met voor de muur/oppervlakte geschikte bevestigingsmiddelen. c. Verwijder de weersbestendige kap van de IRmax detector en schuif de behuizing van de detector door de beugel. Het wordt aanbevolen dat de behuizing van de IRmax detector geïnstalleerd wordt met de kabelingang naar beneden wijzend. 148 Detecting Gas Saving Lives 2. Installatie d. Zet de twee beugelbevestigingen vast zodat de IRmax detector stevig op zijn plaats gehouden wordt. Plaats de weersbestendige kap weer terug. e. Als de IRmax detector stevig op zijn plaats zit, kan de achtermoer van de IRmax detector verwijderd worden zodat u bij de kabelklemmen kunt. f. Maak de veldkabel klaar – Crowcon beveelt een gepantserde stalen kabel van 1,5 mm2 aan. Er kunnen andere kabelsoorten gebruikt worden, mits deze compatibel zijn met Exd gecertificeerde pakkingen. Bevestig een geschikte, gecertificeerde Exd kabelpakking, leid de kabelgeleiders door de behuizing van de IRmax detector en schroef de kabelpakking erin. Draai de pakking vast en zorg ervoor dat de kabelpantsering geaard is op de kabelpakking en de behuizing van de IRmax detector. N.B.: Vergeet niet de achtermoer weer terug te plaatsen nadat de kabel geïnstalleerd is. g. De borgplaat (item 9 op Afbeelding 3, pagina 145) moet goed vast zitten om te voorkomen dat de achtermoer (of het vaste IR Display of de IS Barrier module) lostrilt. 2.4 Installatie met een ringpakking en extra junction box Nederlands Deze optie wordt gebruikt als de IRmax detector aangesloten moet worden op een bestaande Exd of Exe gecertificeerde extra junction box. Afbeelding 6: IRmax detector aangesloten op extra junction box Detecting Gas Saving Lives 149 2. Installatie 2.4.1 De IRmax detector op een extra junction box bevestigen: a. Verwijder voorzichtig het buitenste gedeelte van de ringpakking (onderdeel 8 in Afbeelding 3 op pagina 145). b. Schroef het smalle einde van de ringpakking in de extra junction box. c. Breng de IRmax detector bij de extra junction box en leid de draden door de behuizing naar de extra junction box. Zet de IRmax detector vast door de kraag stevig op de kabelpakking te schroeven. Draai de stifttap vast. d. De behuizing van de IRmax detector kan horizontaal tot elke hoek gedraaid worden, mits hij mechanisch goed vast zit. Hij belemmert andere apparatuur niet en hij kan vanuit deze positie ook onderhouden worden. e. Zie hoofdstuk 2.6 instructies over bedrading. Zie ook Afbeelding 4 (pagina 147). 2.5 Kabelvereisten De bekabeling naar de IRmax detector moet in overeenstemming met de erkende normen van de betreffende instantie in het betrokken land zijn en voldoen aan de elektrische vereisten van de IRmax detector. Crowcon beveelt het gebruik van een gepantserde, stalen kabel aan en er moeten geschikte, explosieveilige pakkingen gebruikt worden. Alternatieve bekabeling zoals stalen leidingen zijn acceptabel, mits voldaan wordt aan de betreffende normen. De maximum aanbevolen kabellengte is 3,4 km (zie tabel 1). De IRmax detector behoeft een gelijkstroomvoeding van 12-30Vdc. Zorg ervoor dat er minimaal 12V bij de IRmax detector is vanaf het besturingspaneel waarbij rekening gehouden wordt met een spanningsdaling vanwege kabelweerstand bij een piekstroom van 0,1mA. Een kabel van 1,5mm2 kan over het algemeen een kabellengte van maximaal 3,0 km aan. In tabel 1 staan de maximum kabelafstanden met typische kabelparameters. Nederlands Doorsnede Weerstand Max. Afstand >20 V Max. Afstand 18 tot 20 V mm2 (Ohm per km) (km) (km) 1,0 18,4 2,2 1,6 1,5 13,0 3,0 2,3 2,5 11,5 3,4 2,6 Tabel 1: maximum kabelafstanden voor standard kabels 150 Detecting Gas Saving Lives 2. Installatie 2.6 Aansluitingen en instellingen Alle beschreven aansluitingen hebben betrekking op het klemmenblok dat in de IRmax detector connector gemonteerd is. De klemmen op de printplaat van de IRmax detector connector zijn gemarkeerd met ‘+’, ‘sig’ en ‘0 V’. Houd rekening met de juiste polariteit bij het aansluiten van de IRmax detector op besturingsapparatuur. De IRmax detector is in de fabriek ingesteld als een 'verzamelstroom' (sink) apparaat, tenzij bij het bestellen anders is gespecificeerd. Om hem in te stellen op 'stroombron' (source), moet de achterplaat verwijderd worden en de twee verbindingen op de printplaat van de 'sink' (verzamel) positie naar de 'bron' (source) positie verplaatst worden, zoals weergegeven in Afbeelding 7. N.B: De externe aardeklem mag alleen gebruikt worden als de plaatselijke autoriteiten een dergelijke aansluiting toestaan of dit vereisen. Om waar mogelijk interferentie met radiofrequenties te vermijden moeten de extra junction box en kabelpantsering alleen bij het besturingspaneel (veilig gebied) geaard worden om aardlussen te vermijden. +V 0V Besturingssysteem CONTROLLER Sg 1 2 3 Sink Jumperinstellingen EARTH Bedrading Nummer Kleur Functie Rood +V Zwart 0V Groen Signaal Source Connector pc-communicatieset Connector IR Display Status-LED Afbeelding 7: Jumperplaats sink/source Het 4-20mA signaal kan ingesteld worden op 'sink' of 'source' met de pinnen en jumperverbinding zoals weergegeven in afbeelding 7. Instellen op 'sink' stroom door de jumper aan te sluiten op pennen 3 en 4, zoals aangegeven op de linkerfoto. Instellen op 'source' stroom door de jumper aan te sluiten op pennen 1 en 2, zoals aangegeven op de rechterfoto. De IRmax detectors staan op 'verzamelstroom' (sink) tenzij dit bij het bestellen anders is gespecificeerd. LED-indicatie: op de printplaat is een LED gemonteerd om de huidige bedrijfsstatus aan te geven. Raadpleeg hoofdstuk 6 op pagina 157 voor nadere informatie. Detecting Gas Saving Lives 151 Nederlands 1 2 3 3. Bediening WAARSCHUWING Voordat er werk uitgevoerd wordt, moet ervoor gezorgd worden dat de plaatselijke voorschriften en fabrieksprocedures opgevolgd worden. Probeer de IRmax detector of extra junction box nooit te openen als er brandbaar gas aanwezig is. Zorg ervoor dat het bijbehorende besturingspaneel geblokkeerd is om een vals alarm te voorkomen. 3.1 Inbedrijfstelling 1. Controleer of: a. De kabelaansluitingen juist zijn b. De toevoerspanning op de besturingskaart ingesteld is op 18 tot 30 V. De spanning die bij de klemmen van de IRmax detector gemeten wordt (binnen de Exe extra junction box, indien gebruikt, of bij de IRmax detector klemplaat) moet ingesteld zijn tussen 12 en 30V. c. De verbindingen op de besturingskaart ingesteld zijn op 4-20mA sink of source, wat van toepassing is. 2. Als hij aangezet is, laat hem dan 30 minuten rusten voordat er geprobeerd wordt op nul in te stellen/te kalibreren. Deze vertraging is nodig om thermische stabiliteit te waarborgen. (N.B: Vanaf 30 seconden nadat de stroom is aangezet, is de IRmax detector volledig operationeel.) 3. Zorg voor schone lucht (d.w.z. geen koolwaterstofgas) voordat u op nul gaat instellen. Nullezing via besturingspaneel (zie instructies van besturingskaart). 4. Bevestig de kalibratiekap over de weersbestendige kap om de meetkamer af te sluiten van omgevingslucht. Zo'n kap is verkrijgbaar bij Crowcon (M041007). Sluit kalibratiegas aan (50% LEL nom) met een stroom van 1 liter per minuut. 5. Pas na 30 seconden de kal/corr op besturingskaart aan zodat het display 50% LEL weergeeft, of overeenkomst met de concentratie van het toegepaste kalibratiegas. De IRmax detector zelf hoeft niet gekalibreerd te worden. 6. Verwijder de gas- en kalibratiekap. Controleer de nul opnieuw. Nederlands 7. Bij de installatie of als de spiegel vervangen is, kan de detector op nul ingesteld en gekalibreerd worden via een IR Display (zie pagina 141) of via een PC communicatieset (zie IRmax accessoirehandleiding). N.B: ATEX gecertificeerde IRmax detectors worden gekalibreerd geleverd zodat ze voldoen aan EN61779 (waar bijvoorbeeld 100% LEL methaan = 4,4% volume). N.B: Het wordt aanbevolen dat bij de eerste inbedrijfstelling de kalibratiekap gebruikt wordt. Daaropvolgende kalibraties kunnen gedaan worden door gas extern op de weersbestendige kap via de pijpring toe te passen (zodat er geen noodzaak is om direct toegang te hebben tot de IRmax detector). Er kan gekalibreerd worden zonder de kalibratiekap (d.w.z. rechtstreeks via de weersbestendige kap), mits de plaatselijke windsnelheid lager is dan 2 meter/seconde. De stroomsnelheid van het gas moet hoger zijn dan 2,0 liter/minuut. 152 Detecting Gas Saving Lives 3. Bediening 3.2 Routineonderhoud De werkwijzen op uw locatie zullen de frequentie aangeven waarmee detectors getest moeten worden Crowcon beveelt aan dat de IRmax minstens elke 6 maanden met gas getest wordt en zo nodig opnieuw gekalibreerd wordt. Om de IRmax detector opnieuw te kalibreren volgt u de stappen in 3.1. In het geval van een elektronicastoring dient u contact op te nemen met uw plaatselijke vertegenwoordiger van Crowcon. Kalibratie-interval: Crowcon beveelt aan dat er elke 12 maanden gekalibreerd wordt. Externe kalibratie via pijp:  De windsnelheid moet lager zijn dan 2,0 meter per seconde. Als deze hoger is, moet de kalibratiekap gebruikt worden om gasverdunning te voorkomen. De optische delen reinigen: Dit wordt niet aanbevolen, tenzij de IRmax detector een belemmeringsfout aangeeft. Als het venster of de spiegel vuil worden, maak deze dan voorzichtig met water schoon. (Zie hoofdstuk 5, Accessoires en reserveonderdelen op pagina 156). Spiegels: Als de spiegel beschadigd is, moet een spiegelvervangingsset worden aangeschaft (Zie hoofdstuk 5, Accessoires en reserveonderdelen op pagina 156). Als de spiegel vervangen is, moet de IRmax detector altijd opnieuw op nul ingesteld en gekalibreerd worden. Als condensatie storingen veroorzaakt, vervang de spiegel dan (de optische laag kan beschadigd zijn). Crowcon beveelt aan dat de spiegel elke 5 jaar vervangen wordt. 3.3 Gassoorten wijzigen Nederlands Elke IRmax detector wordt voorgekalibreerd geleverd voor een bepaald type gas (bijvoorbeeld methaan of propaan). Indien herkalibratie voor een ander soort gas nodig is, kan de IRmax opnieuw met de PC-communicatiekit geconfigureerd en daarna gekalibreerd worden (Zie hoofdstuk 5, Accessoires en reserveonderdelen op pagina 156). Detecting Gas Saving Lives 153 3. Bediening 3.4 Relatieve respons van gassoorten De onderstaande grafiek geeft de relatieve respons weer op andere gassoorten voor een IRmax detector die voor methaan gekalibreerd is. Opmerking: veel koolwaterstofgassen en -dampen worden eerder door IR-detectoren opgemerkt dan methaan. De reactie van IRmax (en andere IR-gasdetectoren) is lineair over het 0-100% LEL-bereik van het doelgas (in dit voorbeeld methaan), maar is niet-lineair voor andere waterstoffen die ook aanwezig kunnen zijn. Afbeelding 8 De grafiek geeft de respons weer van de bovengenoemde gassen: van links naar rechts, propaan, butaan, pentaan en methaan. Andere gassoorten en bereiken zijn beschikbaar. Neem contact op met Crowcon voor meer informatie. Nederlands 154 Detecting Gas Saving Lives Materiaal behuizing 316 roestvrij staal Afmetingen (alleen detector) 150mm x 75mm x 66mm (zonder pakking) Gewicht IRmax 1,58 kg IRmax met vaste IR Display 2 kg IRmax met IS-barrièremodule 2,4 kg Afstands-IR Display 0,2 kg Bedrijfsspanning 12Vdc tot 30V dc Stroom <1W Uitvoer 3-dradig 4-20 mA (sink of source) Storingssignaal <1 mA Maximale kabellusweerstand 80 Ohm (in relatie tot de -ve pool) Bedrijfstemperatuur -40°C tot +75°C Vochtigheid 0–100% relatieve vochtigheid Afdichting IP66 Explosiebescherming Brandveilig Certificering ATEX IRmax (zonder IR Display) II 2 GD Exd db IIC T6 Gb (Tamb = -40°C tot +50°C) II 2 GD Exd db IIC T4 Gb (Tamb = -40°C tot +75°C) II 2 GD Ex tb IIIC T135°C Db (-40°C ≤ Ta≤ +75°C) IRmax met IS Barrier module (extern display) II 2 GD Exd db ia IIC T4 Gb (Tamb = -40°C tot +75°C) Ex tb ia IIIC T135°C Db (Tamb = -40°C tot +40°C) IRmax met vast IR Display II 2 G Exd db ia IIC T4 Gb (Tamb = -40°C tot +75°C) Nr. veiligheidscertificaat ATEX en IECEx IRmax (zonder IR Display): Baseefa 09ATEX0206X en IECEx BAS.09.0109X IRmax (met IR Display): Baseefa 09ATEX0220X en IECEx BAS.09.0104X Functionele veiligheid Gecertificeerd voor gebruik in een SIL 2-systeem. Certificaatnummer: Sira 12ATEX1206X Normen EN 60079-0:2012+A11:2013, EN 60079-1:2014, EN 60079-31:2014 IEC 60079-0:2011, IEC 60079-1:2014, IEC 60079-31:2013 EN 60079-29-1:2007, IEC 61508:2010, EN50402:2005 Zones Gecertificeerd voor gebruik in zone 1 of zone 2 EMC EN50270 Detecting Gas Saving Lives 155 Nederlands 4. Specificatie 5. Accessoires en reserveonderdelen Onderdeelnummers Naam Beschrijving M041007 Kalibratiekap Past over de standaard weerkap om te kunnen kalibreren als de plaatselijke windsnelheid hoger is dan 2 meter per seconde. S012130 Montagebeugelset Geschikt voor montage aan een muur of een pijp van 50 mm. Niet nodig als de IRmax detector gemonteerd wordt aan een bestaande extra junction box. S012152 Zonnekap/ zonnecollector Kan op de IRmax detector bevestigd worden om tegen verhoogde temperaturen vanwege direct zonlicht te beschermen en/of om de voetafdruk van de detector te verlengen om lichtere dan luchtgassen (methaan) te detecteren. S012169 Leidingmontageset Hiermee kunnen leidingen van 300 mm tot 3000 mm gecontroleerd worden en luchtstroom tussen 2 m/s en 20 m/s. S012996 Stroomadapter Voor toepassingen met gasmonsters S012827 PC-communicatieset Communicatiemodule, software en snoer om de detector te kunnen configureren. M20: S012295 ½” NPT: S012296 Extra junction box Montageoptie voor IRmax voor gebruik in gevaarlijk omgevingen. C011210 Spiegelreinigingsset Bevat met IPA doordrenkte doekjes en microvezeldoek IRmax detector reserveonderdelen Zie Afbeelding 3 op pagina 145 voor gegevens over reserveonderdelen. Nederlands 156 Detecting Gas Saving Lives 6. Problemen oplossen 6.1 Fouten gesignaleerd door LED De LED die op de contactprintplaat zit, kan storingen helpen identificeren. Zijn positie is getoond in Afbeelding 7 op pagina 151. De onderstaande tabel toont hoe elk knipperpatroon moet worden uitgelegd. Detectorstatus Actie Elke seconde regelmatig knipperend. Normaal. Aan met korte uitpauzes. Detector bezig met opstarten. Wacht 10 seconden. Snel aan en uit knipperend of onregelmatig knipperpatroon Toevoerspanning te laag of te hoog. Controleer of de toevoerspanning naar de IRmax detector juist is ingesteld. Controleer of de meting direct bij de detectorklemmen gemaakt wordt. Permanent aan. Storing, fout bij host of i-module. Laat de IRmax detector rusten, als de storing blijft, stuur hem dan terug naar Crowcon. Twee keer lang knipperen, gevolgd door kort knipperen. Fatale fout; fout in lamp of detector. Stuur terug naar Crowcon. Elke seconde snel dubbel knipperen. Fatale fout, module- of configuratiefout. Controleer de configuratie van de IRmax detector met de PCcommunicatieset-software. Controleer de stroomtoevoer. Als de storing blijft, stuur hem dan terug naar Crowcon. Elke seconde een korte piep. Optische delen vuil. Controleer venster en spiegel en maak zonodig schoon. Zet de IRmax detector opnieuw op nul en controleer de kalibratie. Andere fouten kunnen gecorrigeerd worden door de IRmax detector naar Crowcon of een bevoegde agent te retourneren. 6.2 Analoge uitgang IRmax blijft in de storingsstand staan en ''Onderhoud nodig" (Service required) wordt op het IR-display weergegeven (indien aanwezig), als het analoge outputsignaal een storing vertoont of niet aangesloten is op een regelsysteem of belastingsweerstand. IRmax controleert op actieve wijze of het analoge outputsignaal van 4-20 mA binnen het bereik valt. Als het signaal buiten het bereik valt, geeft de detector een storing weer en wordt de output ingesteld op 1 mA. Dit betekent dat als een detector wordt getest, hij ofwel aangesloten moet zijn op een regelpaneel, of dat er een belastingsweerstand van 100 Ω aangesloten is tussen de ‘0V’ en ‘Sig’ terminals (detector ingesteld op ‘Source’) of tussen de ‘0V’ en ‘+V’ terminals (detector ingesteld op ‘Sink’). Detecting Gas Saving Lives 157 Nederlands LED-patroon 7. Configuratie RS485 Modbus 7.1 Algemeen Deze paragraaf vertelt hoe de IRmax detector gebruikt moet worden in een Modbus-configuratie. Er is een RS485 versie verkrijgbaar voor dergelijke toepassingen. Er kunnen maximaal 28 IRmax detectors in een ster- of busconfiguratie verbonden worden, zie onder. Aansluitingen op de RS485 versie van de IRmax detector moeten gemaakt worden via een ringpakking op een extra aansluitkast (zie hoofdstuk 5 op pagina 156), in plaats van de bekabeling rechtstreeks naar de IRmax detector te leiden. Let wel dat het IR Display niet kan worden gebruikt met een RS485-geactiveerde IRmax. De RS485 ingeschakelde versie van de IRmax detector heeft vijf veldklemmen. De klemmen zijn: 1 Positieve toevoer 12 V tot 30 V boven 0 V 2 0V Retour en RS485 referentie 3 4-20 mA signaal Source of Sink signaal (optioneel) 4 RS485 B RS-485 verschilsignaal 5 RS485 A RS-485 verschilsignaal De signalen op de RS485 klemmen voldoen aan de EIA/TIA-485 norm. Dit houdt in dat het algemene bereik met betrekking tot de 0V-klem van -7V tot +12V is. Let op dat niet alle RS485 fabrikanten het eens zijn over de polariteit van de A- en B-signalen. Als de bedrading op de ene manier niet werkt, wissel de RS485 A- en B-draden dan om. Er bestaat geen risico als er een verkeerde aansluiting gemaakt wordt. De communicatie-instellingen zijn 9600 bps, twee stopbits en geen pariteit. Als er een interface samengesteld wordt voor een besturingssysteem, is het belangrijk de hoeveelheid tijd in overweging te nemen die het systeem nodig heeft om van elke detector informatie te verzamelen. De snelste snelheid waarmee meerdere detectors ontvangen kunnen worden is 14 detectors per seconde, praktische omstandigheden kunnen dit aantal verlagen tot 7 per seconde. Gebruikers moeten ervoor zorgen dat de opstelling alarmsignalen binnen een acceptabele tijdslimiet kan laten registeren. Nederlands Het is ook belangrijk ervoor te zorgen dat het systeem genoeg stroom kan leveren om alle detectoren te laten werken. Om de benodigde hoeveelheid stroom te berekenen voor een lineaire busaansluiting zie hoofdstuk 7.3, Bekabelingsvereisten, op pagina 160. Neem voor volledige Modbus-instructies contact op met Crowcon (zie adressen op de achterzijde). 158 Detecting Gas Saving Lives 7. Configuratie RS485 Modbus 7.2 Bedradingstopologie De twee algemeen gebruikte bedradingstopologieën zijn de steraansluiting en de lineaire bus. 7.2.1 Steraansluiting In een steraangesloten topologie zijn alle detectoren aangesloten op een centraal punt. Dit is meestal het besturingspaneel. Geen enkele kabel heeft meer dan 5 kernen nodig omdat alle 4-20mA signaalaansluitingen direct naar het besturingspaneel gaan. De RS485 A- en B-signalen kunnen dan allemaal samen aangesloten worden op het sterpunt. De bus moet dan op het sterpunt afgesloten worden met een enkele 110 Ohm afsluitweerstand. De lengte van elke arm van de ster mag niet langer zijn dan 750 meter. 7.2.2 Lineaire busaansluiting In een busaangesloten topologie worden alle IRmax detectors via een lineaire opstelling aangesloten, meestal met het besturingspaneel aan één einde. Een klassieke situatie is een tunnelinstallatie, waarbij er op regelmatige afstanden een IRmax detector geïnstalleerd wordt (zie Afbeelding 9 hieronder). Om de installatie te bedraden, bevestigt u twee 110 Ohm afsluitweerstanden aan elk fysieke eind van de bus. Omdat de 4-20mA signalen niet gedeeld kunnen worden, is er voor elke bedradingverbinding een extra conductor nodig. Als geen van de 4-20mA signalen gebruikt worden, dan zijn er slechts vier conductors nodig. SCHAKELSCHEMA LINEAIRE BUS Nederlands NAAR BEDIENINGSPANEEL Afbeelding 9 Detecting Gas Saving Lives 159 7. Configuratie RS485 Modbus 7.3 Bekabelingsvereisten 7.3.1 Berekenen van de minimum vereiste stroom Hoe meer IRmax detectors er op de lineaire bus aangesloten zijn, hoe meer stroom er nodig is om het systeem te laten draaien. Om de benodigde stroom voor een bepaalde opstelling te berekenen, is het nodig om te weten wat de kabelweerstand is tussen elk paar IRmax detectors. Er is minimaal 0,1mA stroom nodig voor elke 'verbinding' tussen de IRmax detectors. De toe te passen spanning kan berekend worden door de spanningsdaling over elke 'verbinding' in te schatten. Aan het einde moet er nog minimaal 12V overblijven om de laatste IRmax detector goed te laten functioneren. Neem voor specifieke gevallen contact op met Crowcon. Eventueel kunnen ook de onderstaande stappen gevolgd worden en de voorbeeldberekening in het volgende deel. 1. De spanning mag niet onder de 12V dalen. Begin dus de berekening door de spanning op de laatste IRmax detector in de lijn op die waarde in te stellen. 2. Elke IRmax detector kan tot 0,1A trekken. Bereken het kabelspanningsverlies van de eerste 'verbinding' tussen de IRmax detectors door ervan uit te gaan dat de 'totale stroom' 0,1A is en vermenigvuldig dit dan met de kabelweerstand van de 'verbinding' tussen de laatste en een na laatste IRmax detector. 3. Voeg deze spanningsdaling toe aan de 12V voor de laagste acceptabele spanning bij de een na laatste IRmax detector. Voeg 0,1A toe aan de waarde voor de 'totale stroom' om op 0,2mA uit te komen, de minimum stroom die door de een na laatste 'verbinding' van de bus loopt. Vermenigvuldig dit met de kabelweerstand voor de een na laatste 'verbinding' om de volgende spanningsdaling te krijgen. 4. Herhaal dit proces voor elke IRmax detector, waarbij de spanningsverliezen tussen elke detector vermeerderd worden. 5. De maximum detectorspanning van 30V mag niet overschreden worden. 7.3.2 Voorbeeldberekening Als voorbeeld geven we de resultaten van de berekening voor zes stuks IRmax detectors die 250 m van elkaar geplaatst zijn op een kabel met een dwarsdoorsnede van 1mm2. Elke 'verbinding' heeft een weerstand van 4,6 ohm. Nederlands Station Toevoerspanning Toevoerstroom 1 12 0.1 A 2 12.46 0.2 A 3 13.38 0.3 A 4 14.76 0.4 A 5 16.6 0.5 A 6 18.9 0.6 A Stroom t.b.v. paneel 21.66 0.6 A 160 Detecting Gas Saving Lives 8. Functionele veiligheidshandleiding 8.1 Inleiding De volgende delen verschaffen informatie over de certificatie van IRmax volgens de functionele veiligheidsnormen IEC 61508 en EN 50402. Er wordt informatie verstrekt over de functies voor veiligheid, onderhoud en data, zodat de IRmax geïntegreerd kan worden in een Safety Instrumented System (SIS). 8.2 Modbus veiligheidsfunctie van IRmax en IRmax Concentratiemeting van een brandbaar gas en indicatie van de waarde via een 4-20 mA output. Storingen van de veiligheidsfunctie worden opgemerkt door de hardware en de bijbehorende firmware. Ze worden weergegeven als een uitgangssignaal van minder dan 3,6 mA of meer dan 21 mA. 8.3 Informatie over functionele veiligheid Symbool Vergelijking / bron Proeftestinterval T1 Zoals gedefinieerd door Crowcon. IRmax Gemiddelde tijd voor reparatie MTTR 8760 uur (jaarlijks) Zoals gedefinieerd door Crowcon. 8 uur Type A/B Type A Zoals gedefinieerd door Crowcon. Type B Totale storingen: λ Van FMEDA 1.04E-05 Veilige gediagnosticeerde storingen: λSD Van FMEDA 1.95E-08 Veilige niet-gediagnosticeerde storingen: λSU Van FMEDA 8.59E-08 Gevaarlijke gediagnosticeerde storingen: λDD Gevaarlijke niet-gediagnosticeerde λDU storingen: Veilige storingen zonder effect: λNE Van FMEDA 9.74E-06 Van FMEDA 5.06E-07 Van FMEDA 3.21E-09 Diagnostische dekking: DC λDD / (λDU + λDD) 95.06% Fractie veilige storingen: SFF 95.11% Fractie veilige storingen: tCE (λSD + λSU + λDD) / λ (λDU / λD)(T/2 + MTTR) + (λDD / λD ) MTTR 2.24E+02 PFDAVG (met gebruik van 61508-6 PFDAVG (λDU + λDD) tCE 2.30E-03 vergelijking) PFDAVG (met een vereenvoudigde PFDAVG λDU (T / 2+MTTR) + (λDD MTTR) 2.30E-03 vergelijking) PFDAVG (met gebruik van IEC PFDAVG 1-ε-(λdd+λdu) tce 2.30E-03 61508-6 vergelijking) SIL-capaciteit (stand voor weinig SIL2 vraag) SIL-capaciteit (stand voor hoge SIL2 vraag) Voor toepassingen met weinig vraag en gezien willekeurige hardwarestoringen en fractie veilige storingen, zijn alle systeemvariaties geschikt voor gebruik in SIL 2-toepassingen. Detecting Gas Saving Lives 161 Nederlands Naam van parameter Functionele veiligheidshandleiding 8.4 Hardwareconfiguratie Route 1H (hardwarestoringstolerantie en fractie veilige storingen) is gebruikt om het integriteitsniveau van de hardware te beoordelen. 8.5 Softwareconfiguratie De productfirmware is beoordeeld op basis van de vereisten van IEC 61508:3 2010. 8.6 Systematische storingen Route 1S (zoals gespecificeerd in IEC 61508:2 2010 paragraaf 7.4.2.2c) wordt gebruikt voor naleving met de vereisten om systematische storingen te voorkomen. 8.7 Diagnostisch interval De meeste diagnostische functies worden voortdurend gemonitord. Testen van de systeembewaker moeten worden uitgevoerd tijdens de jaarlijkse proeftest door een rustfase in te lassen: de IRmax moet elk jaar een rustfase doorlopen (door het verwijderen en weer aansluiten van de 24 Vdc stroomtoevoer) als onderdeel van het onderhoudsprogramma voor het product (raadpleeg ook deel 3.2). 8.8 Beperkingen Storingsfrequentie is constant. Een proeftest die minstens eenmaal per jaar wordt uitgevoerd wijst op alle verborgen storingen. Reparaties duren gemiddeld 8 uur. Aangenomen wordt dat de gebruiker de diagnostische voorziening gebruikt die wordt geleverd via het IR Display en/of de pc-interface om de mogelijke stilstand te minimaliseren. Nederlands De betrouwbaarheidsbeoordeling is een statistisch proces voor toepassing van historische storingsdata op de voorgestelde designs en configuraties. Dit levert een geloofwaardig doel of een goede schatting van de waarschijnlijke betrouwbaarheid van de apparatuur, als de productie, het design en de bedrijfsomstandigheden identiek zijn aan die van de apparatuur waarvan de gegevens zijn verzameld. Dit is een waardevolle techniek voor het vergelijken van alternatieve designs, het vaststellen van de orde van grootte van de prestatietargets en het evalueren van de mogelijke gevolgen van designwijzigingen. De eigenlijke voorspelde waarden kunnen echter niet worden gegarandeerd, omdat het exacte aantal veldstoringen afhangt van veel facturen die niet gecontroleerd kunnen worden. Aangenomen wordt dat de storingsfrequentie (symbool λ), voor het doel van deze prognose, over tijd constant is. Zowel vroege als slijtagestoringen reduceren de betrouwbaarheid, maar aangenomen wordt dat dergelijke storingen worden voorkomen door inbranden en preventieve vervanging. 162 Detecting Gas Saving Lives Functionele veiligheidshandleiding De storingswaarschijnlijkheid op aanvraag is de waarschijnlijkheid dat het systeem op een willekeurig moment een storing vertoont. Dit is synoniem aan de permanente onbeschikbaarheid, die wordt aangegeven door: Onbeschikbaarheid = (λ x MDT)/(1 + (λ x MDT)) die ongeveer gelijk is aan λ x GST voor kleine waarden van λ x GST waarbij λ de defectfrequentie is en GST de duur van de gemiddelde stilstand. Dit komt overeen met de formule voor beschikbaarheid: MTBF/(MTBF+MDT) De gebruikte defectfrequenties en de verkregen beschikbaarheidswaarden kunnen worden toegepast op een goed bewezen design, na een geschikte periode van betrouwbaarheidstoename. 8.9 Omgevingsfactoren Beperkingen door omgevingsfactoren: Het product moet worden gebruikt bij een maximaal omgevingstemperatuurbereik van -40°C tot +75°C Het product moet worden opgeborgen bij een maximaal omgevingstemperatuurbereik van -40°C tot +80°C Het product moet worden gebruikt bij een maximaal relatief vochtigheidsbereik van 0% tot +100% condenserend Het product heeft een beschermingsklasse van IP66, volgens de definities van norm EN60529. 8.10 Hardwarestoringstolerantie De HST is 0. 8.11 Systematische capaciteit De IREX/IRmax heeft Klasse SC2. 8.12 Classificatie De IREX/IRmax is een component van type B. Detecting Gas Saving Lives 163 Nederlands Het product is ontworpen voor een voortdurende werking. Garantie Deze apparatuur verlaat onze fabriek volledig getest en gekalibreerd. Als binnen de garantieperiode van drie jaar na verzending blijkt dat de apparatuur defect is als gevolg van een fout in vakmanschap of materiaal, zullen we het repareren of kosteloos vervangen, onderhevig aan de onderstaande voorwaarden. Garantieprocedure Om een claim zo efficiënt mogelijk te kunnen verwerken, kunt u contact opnemen met ons ondersteuningsteam op +44 (0)1235 557711 met de volgende informatie: Uw naam, telefoonnummer, faxnummer en e-mailadres. Beschrijving en aantal van de te retourneren goederen, waaronder eventuele accessoires. Serienummer(s) van het instrument. Reden voor retourneren. Vraag om een retourformulier voor identificatie en vindbaarheid. Dit formulier kan vanaf onze website ‘crowconsupport.com’ gedownload worden, samen met een retourlabel. We kunnen eventueel ook een exemplaar e-mailen. Een IRmax detector wordt zonder een Crowcon retournummer niet onder garantie geaccepteerd. Het is essentieel dat het adreslabel stevig bevestigd is aan de buitenverpakking van de te retourneren goederen. De garantie wordt ongeldig als blijkt dat het instrument gewijzigd, gemodificeerd, ontmanteld is of als er op andere wijze mee geknoeid is. De garantie dekt geen misbruik van het product. Garantie disclaimer Crowcon accepteert geen aansprakelijkheid voor gevolghebbend of indirect verlies of schade die op wat voor manier dan ook ontstaat (waaronder eventueel verlies of schade die ontstaan door het gebruik van het instrument) en alle aansprakelijkheid met betrekking tot een derde partij is uitdrukkelijk uitgesloten. Nederlands Deze garantie dekt niet de nauwkeurigheid van de kalibratie van de eenheid of de cosmetische afwerking van het product. De eenheid moet in overeenstemming met de bedienings- en onderhoudsinstructies onderhouden worden. De garantie op vervanging van verbruiksartikelen (zoals de spiegel) die onder garantie geleverd is om defecte items te vervangen, zal beperkt zijn tot de niet verlopen garantie van het originele geleverde item. Crowcon behoudt zich het recht voor om een kortere garantieperiode vast te stellen, of om een garantieperiode af te wijzen voor een sensor die gebruikt wordt in een omgeving of toepassing waarvan bekend is dat er een risico bestaat van degradatie of schade aan de sensor. Onze aansprakelijkheid met betrekking tot defecte apparatuur zal beperkt zijn tot de verplichtingen zoals uiteengezet in de garantie en eventuele verlengde garantie, voorwaarde of verklaring, uitdrukkelijk of geïmpliceerd, statutair of anderszins met betrekking tot de verkoopbare kwaliteit van onze apparatuur of de geschiktheid ervan voor een bepaald doel is uitgesloten, behalve als wettelijk is bepaald. Deze garantie heeft geen invloed op de wettelijke rechten van een klant. Crowcon behoudt zich het recht voor om verwerkings- en verzendkosten door te berekenen als defecte geretourneerde items alleen normaal gekalibreerd of onderhouden moesten worden, en dat de klant dan niet wil laten doen. 164 Detecting Gas Saving Lives Garantie Voor garantie en technische ondersteuning kunt u contact opnemen met: Customer Support Tel: +44 (0) 1235 557711 Fax: +44 (0) 1235 557722 Nederlands Email: [email protected] Detecting Gas Saving Lives 165 Zawartość Zasada działania i bezpieczeństwo..........................................................169 Idea wykrywacza IRmax ..................................................................169 Informacje dotyczące bezpieczeństwa..............................................170 Informacje ogólne o produkcie..........................................................171 1. Wprowadzenie......................................................................................172 1.1 Informacje ogólne........................................................................172 1.2 Opis produktu..............................................................................172 2. Instalacja...............................................................................................174 OSTRZEŻENIE..................................................................................174 2.1 Lokalizacja...................................................................................174 2.2 Montaż.........................................................................................175 2.3 Podłączanie kabla bezpośrednio do IRmax ...............................175 2.3.1 Oznaczenie zacisku............................................................176 2.3.2 Instalowanie wykrywacza IRmax za pomocą wspornika montażowego...............................................................................176 2.4 Instalowanie za pomocą dławnicy z króćcem z gwintem zewnętrznym i dodatkowej skrzynki przyłączowej.............................177 2.4.1 Aby przymocować wykrywacz IRmax do dodatkowej skrzynki przyłączowej:.................................................................178 2.5 Wymagania dotyczące okablowania...........................................178 2.6 Połączenia i ustawienia...............................................................179 3. Działanie...............................................................................................180 3.1 Procedura przekazania do ekploatacji........................................180 3.2 Rutynowa konserwacja................................................................181 3.3 Zmiana typu gazu........................................................................181 3.4 Odpowiedź względna na inne typy gazów..................................182 4. Dane techniczne...................................................................................183 5. Akcesoria i części zamienne ................................................................184 6. Wykrywanie usterek.............................................................................185 6.1 Błędy sygnalizowane przez diodę LED.......................................185 6.2 Wyjście analogowe......................................................................185 7. Konfiguracja RS485 Modbus................................................................186 7.1 Informacje ogólne........................................................................186 7.2 Topologia okablowania................................................................187 7.2.1 Połączenie w układzie gwiazdy...........................................187 7.2.2 Połączenie magistrali liniowej.............................................187 7.3 Wymaganie dotyczące okablowania...........................................188 7.3.1 Obliczanie minimalnego wymaganego poziomu mocy ......188 7.3.2 Przykładowe obliczenie......................................................188 8. Podręcznik Bezpieczeństwa Funkcjonalnego.......................................189 8.1 Wstęp...........................................................................................189 8.2 Urządzenie IRmax i funkcja zabezpieczająca IRmax Modbus....189 8.3 Dane Bezpieczeństwa Funkcjonalnego.......................................189 8.4 Konfiguracja Sprzętowa...............................................................190 8.5 Konfiguracja Oprogramowania....................................................190 8.6 Awarie systemowe.......................................................................190 8.7 Częstotliwość diagnostyki............................................................190 8.8 Ograniczenia................................................................................190 8.9 Środowiskowe..............................................................................191 8.10 Tolerancja na usterki sprzętowe................................................191 8.11 Zdolność systemowa.................................................................191 8.12 Klasyfikacja................................................................................191 Gwarancja.................................................................................................192 Zasada działania i bezpieczeństwo Idea wykrywacza IRmax IRmax jest ultrakompaktowym wykrywaczem gazów na podczerwień (IR), zapewniającym szybkie i niezawodne wykrywanie gazów oraz par węglowodorów. Wykrywacz IRmax, cechujący się zastosowaniem technologii czujnika podczerwieni o podwójnej długości fali i wytrzymałą obudową ze stali nierdzewnej 316, został zaprojektowany do pracy w najtrudniejszych warunkach. W odróżnieniu od konwencjonalnych wykrywaczy gazów na podczerwień w IRmax nie są używane ogrzewacze zapobiegające kondensacji na szybkach i lusterkach. Pokrycie STAY CLIR na elementach optycznych zapobiega kondensacji podczas pracy wykrywacza. Wykrywacz IRmax jest zgodny z dowolnym układem sterowania działającym zakresie 4 – 20 mA. Można go również zamontować w sieci adresowalnej magistrali RS485 Modbus (opis w Rozdziale 7). Wykrywacz IRmax wymaga mocy zaledwie 1 W — jest to wartość o 75 – 90% niższa niż w przypadku konwencjonalnych wykrywaczy gazów na podczerwień. Wykrywacz IRmax jest wyposażony w kompaktową dyfuzyjną komorę gazów, która w połączeniu ze skuteczną, zabezpieczającą przed warunkami atmosferycznymi nasadką zapewnia doskonałą szybkość reakcji. Nasadka ta została zaprojektowana z zastosowaniem oprogramowania modelującego przepływy w celu umożliwienia zdalnego gazowania i kalibracji wykrywacza bez wymogu stosowania specjalnej nasadki kalibracyjnej. Wyświetlacz IR Display umożliwia śledzenie odczytów z wykrywacza IRmax, zarówno lokalnie, jak i zdalnie. Wyświetlacz IR Display można przymocować bezpośrednio do wykrywacza IRmax. Alternatywnie, IRmax może być dostarczony wraz z modułem bariery iskrobezpiecznej (IS). Wyświetlacz IR Display można podłączyć do modułu bariery iskrobezpiecznej za pomocą okablowania tymczasowego lub stałego. Dostępne rozwiązania przedstawiono na Schemat 3, strona 173. Polski W celu uzyskania szczegółowych informacji o innych akcesoriach do urządzenia IRmax, patrz Schemat 3 na strona 173 i Dziale 5 na strona 184. Detecting Gas Saving Lives 169 Zasada działania i bezpieczeństwo Informacje dotyczące bezpieczeństwa • Instalację, obsługę i konserwację wykrywaczy gazów IRmax należy prowadzić ściśle według niniejszych instrukcji, ostrzeżeń, informacji zawartych na etykietach oraz w ramach określonych ograniczeń. • Tylna pokrywa na wykrywaczu IRmax musi być podczas pracy mocno dokręcona. Nie wolno podejmować prób odkręcania tylnej zaślepki do chwili odizolowania zasilania wykrywacza — mogłoby to spowodować zapłon palnej atmosfery. Przed odkręceniem pokrywy w celu konserwacji, kalibracji lub serwisu należy sprawdzić, czy otaczająca atmosfera nie zawiera łatwopalnych gazów lub par. Nie otwierać przez kilka minut po odłączeniu zasilania. • Czynności konserwacyjne i kalibrację może wykonywać wyłącznie wykwalifikowany personel serwisowy. • Należy używać wyłącznie oryginalnych części zamiennych firmy Crowcon. Użycie elementów zastępczych może spowodować unieważnienie certyfikacji i gwarancji wykrywacza IRMax. • Wykrywacze IRmax należy chronić przed drganiami o skrajnie wysokim natężeniu oraz bezpośrednim światłem słonecznym w środowisku wysokich temperatur — może to spowodować wzrost temperatury wykrywacza powyżej określonych wartości granicznych i spowodować przedwczesne uszkodzenie. • Wykrywacz IRmax nie wykrywa wodoru, amoniaku i dwutlenku węgla. • Sprzęt należy uziemić za pomocą dławnicy kablowej i kabla ze stalowym opancerzeniem. • Certyfikat dla Strefy 21/22 - środowisko zapylone IRmax basic (bez wyświetlacza IR lub modułu IS Barrier) może być wykorzystywany w środowisku, w którym występuje niebezpieczny pył (Strefy 21 lub 22). • IRmax z modułem IS Barrier może być stosowany w strefach 21 lub 22 pod warunkiem, że temperatura otoczenia nie przekroczy 40°C, a zdalny wyświetlacz IR lub ręczny wyświetlacz zainstalowany/używany będzie poza strefą zagrożenia. • Urządzenia IRmax z zamontowanym na stałe wyświetlaczem IR nie można instalować w Strefach 21 ani 22. Polski 170 Detecting Gas Saving Lives Zasada działania i bezpieczeństwo Informacje ogólne o produkcie Wykrywacz IRmax jest wykrywaczem gazów na podczerwień zaprojektowanym do wykrywania powszechnie występujących gazów węglowodorowych w zakresie od 0 do 100% dolnej granicy wybuchowości: (najniższego stężenia w powietrzu, przy którym może nastąpić zapłon). Wykrywacz IRmax jest certyfikowanym wykrywaczem przeciwwybuchowym (Exd) zdatnym do użytku w obszarach niebezpiecznych określanych jako Strefy 1 i 2 ATEX. Etykieta certyfikacyjna z boku wykrywacza identyfikuje typ certyfikatu odnoszący się do dostarczonego produktu. Uwaga: jeśli na wykrywaczu IRmax nie jest zamocowana żadna etykieta, nie jest on certyfikowany do wykorzystania w obszarach niebezpiecznych. IR GAS DE TECTOR 1180 IR GAS DETECTOR WITH REMOTE DISPLAY II 2 GD 1180 V m ax= 32V W m ax= 5W II 2GD Vmax=32V Wmax=5W B a s e e fa 0 9 A T E X 0 2 0 6 X IE C E x B A S 0 9 . 0 1 0 9 X S IL 2 S i r a 1 2 A T E X 1 2 0 6 X Baseefa09ATEX0220X IECEx BAS 09.0104X Ex db ia IIC T4 Gb (-40°C ≤ Ta ≤ +75°C) Ex tb ia IIIC T135°C Db (-40°C ≤ Ta ≤ +40°C) E x d b II C T 4 Gb (T am b = -40 °C to + 75 °C ) E x d b II C T 6 Gb (T am b = -40 °C to + 50 °C ) E x tb II IC T 135° C D b (-4 0° C T a + 75° C ) WARNING: DO NOT OPEN WHEN EXPLOSIVE ATMOSPHERE MAY BE PRESENT. W A R N IN G : D O N O T O P E N W H E N E X P L O S IV E A TM O S P H E R E M A Y B E P R E S E N T. Abingdon, United Kingdom, OX14 4SD A b i n g d o n , U nit e d K in g d o m , O X 1 4 4 S D Etykieta certyfikacji urządzenia IRmax Basic Etykieta certyfikatu iskrobezpieczeństwa urządzenia IRmax IR GAS DETECTOR WITH DISPLAY 1180 II 2G Baseefa09ATEX0220X IECEx BAS 09.0104X Vmax=32V Wmax=5W Ex db ia IIC T4 Gb (-40°C Ta +75°C) WARNING: DO NOT OPEN WHEN EXPLOSIVE ATMOSPHERE MAY BE PRESENT. Abingdon, United Kingdom, OX14 4SD Schemat 1: Etykiety certyfikacyjne wykrywacza IRmax Detecting Gas Saving Lives 171 Polski Etykieta bezpieczeństwa urządzenie IRmax z zamontowanym na stałe wyświetlaczem IR 1. Wprowadzenie 1.1 Informacje ogólne Konfiguracja każdego wykrywacza IRmax jest określona przez etykietę umieszczoną na korpusie. W przypadku kontaktu z firmą Crowcon w celu uzyskania porady lub części zamiennych należy podać nazwę produktu, nazwę części oraz numer seryjny. 1.2 Opis produktu Wykrywacz IRmax składa się z korpusu wykonanego ze stali nierdzewnej 316 oraz antystatycznej, odpornej na działanie czynników atmosferycznych pokrywy optyki i komory pomiarowej gazu oraz zespołu elektroniki. Można również zamontować moduł IR Display. Instrukcje dotyczące montażu wyświetlacza IR Display zamieszczono w instrukcji obsługi wyświetlacza (M07061). Może zostać dostarczona opcjonalna dławnica z króćcem z gwintem zewnętrznym, umożliwiająca zamocowanie wykrywacza IRmax bezpośrednio na dodatkowych skrzynek przyłączowych z wlotami kablowymi M20 lub NPT ½ cala. Opcjonalna dławnica z króćcem z gwintem zewnętrznym 74.5 74,5 Łącznie 57 60.5 157.5 Łącznie 158 Łącznie 136 136 Dławnica kablowa M20 lub NPT ½ cala Końcówka zewnętrznego uziemienia (EARTH) Wszystkie wymiary podano w milimetrach Polski Schemat 2: Widok wymiarowy wykrywacza IRmax Uwaga: korpus wykrywacza IRmax jest dostarczany z dwoma wlotami kablowymi, M20 i NPT ½ cala. Wlot kablowy, który nie został określony podczas zamawiania wykrywacza IRmax, jest zaślepiony certyfikowaną zaślepką. Oba przewody urządzenia IRmax muszą być szczelnie zabezpieczone: jeden z użyciem dławika kablowego, a drugi z użyciem zaślepki mającej certyfikat IP66. 172 Detecting Gas Saving Lives 1. Wprowadzenie 15 12 14 13 11 “ 10  ‘ ”  ‘ Ž    Œ Schemat 3: Widok rozebranego wykrywacza IRmax (numery części przedstawiono tam, gdzie mają zastosowanie) Œ Nasadka kalibracyjna M041007  Nasadka chroniąca przed wpływem warunków atmosferycznych M04995 Ž Ustalacz lusterka Dostarczane razem z zestawem do wymiany lusterka C011206  Lusterko  Adaptor przepływowy S012996 ‘ Pierścień uszczelniający typu „O“ do nakrętki oporowej, moduł IS Barrier lub moduł instalow } anego na stałe wyświetlacza IR: M040077  Wspornik montażowy jako kompletny zespół S012130 “ Dławnica z króćcem z gwintem zewnętrznym, wersje M20 lub NPT ½ cala: M20 ATEX: S012147, 1/2" NPT ATEX: S012190 10 Stała wersja wyświetlacza IR Display 11 Złącze wyświetlacz IR Display – wykrywacz IRmax E07987 12 Moduł bariery iskrobezpiecznej 13 Przewód łączący wyświetlacz IR Display 14 Gniazdo montażowe zdalnego wyświetlacza IR Display M03833 15 Zdalny wyświetlacz IR Display Detecting Gas Saving Lives 173 Polski ” Płytka i sworzeń mocujący do tylnej wtyczki, instalowany na stałe wyświetlacz IR i moduł IS Barrier 2. Instalacja OSTRZEŻENIE • Ten wykrywacz został zaprojektowany w sposób umożliwiający zastosowanie w obszarach niebezpiecznych określanych jako Strefy 1 i 2. Certyfikacja jest uzależniona od zamontowanych akcesoriów i temperatury otoczenia, w którym urządzenie pracuje. Szczegóły dotyczące certyfikacji znajdują się w tabeli danych technicznych na strona 183. Instalację należy przeprowadzić zgodnie z uznanymi standardami ustalonymi przez odpowiednie władze krajowe. • Aby uzyskać dodatkowe informacje, należy skontaktować się z firmą Crowcon. Przed wykonaniem jakichkolwiek prac instalacyjnych należy się upewnić, że są przestrzegane lokalne przepisy i procedury właściwe dla miejsca instalacji. • Sprzęt należy uziemić za pomocą dławnicy kablowej i kabla ze stalowym opancerzeniem. • Nie należy podejmować prób zamontowania wyświetlacza IR Display na wykrywaczu, który nie został dostarczony w tym celu. Wykrywacze IRmax dostarczone do użytku z wyświetlaczem mają certyfikat Exd ia i muszą pracować z wyświetlaczem stałym z barierą iskrobezpieczną lub ze zdalnym bądź ręcznym wyświetlaczem podłączonym za pośrednictwem modułu bariery iskrobezpiecznej firmy Crowcon. • Wykrywacze IRmax dostarczone bez wyświetlacza mają certyfikat Exd IIC i nie można ich zmodernizować w celu użycia z wyświetlaczem IR Display. 2.1 Lokalizacja Wykrywacz IRmax należy zamontować w miejscach, w których występowanie wykrywanego gazu jest najbardziej prawdopodobne. Podczas umieszczania wykrywaczy gazu należy zwrócić uwagę na następujące elementy: Polski • W celu wykrycia gazów lżejszych od powietrza, takich jak metan, wykrywacze należy zamontować na dużej wysokości. W celu wykrycia gazów cięższych od powietrza, takich jak opary łatwopalne, wykrywacze należy zamontować na małej wysokości. • Umieszczając wykrywacze, należy wziąć pod uwagę uszkodzenia, które mogą zostać spowodowane przez czynniki naturalne, takie jak deszcz lub powódź. W przypadku wykrywaczy montowanych na zewnątrz w obszarach bardzo wysokich temperatur firma Crowcon zaleca stosowanie zasłony przeciwsłonecznej (opis w Dziale 5, Akcesoria i części zamienne, na strona 184). • Należy wziąć pod uwagę łatwość dostępu do celów związanych z testami funkcjonalnymi i serwisem. • Należy wziąć pod uwagę zachowanie ulatniających się gazów, wywołane naturalnymi lub wymuszonymi prądami powietrza. Jeśli jest to właściwe, wykrywacze IRmax należy montować w kanałach wentylacyjnych (z zastosowaniem zestawu montażowego IRmax do kanałów (opis w Dziale 5, Akcesoria i części zamienne, na strona 184)). • Należy wziąć pod uwagę warunki procesu. Butan jest na przykład w normalnych warunkach cięższy od powietrza, ale w przypadku uwolnienia z procesu, w którym występuje podwyższona temperatura i/lub ciśnienie, może wznosić się zamiast opadać. Rozmieszczenie czujników należy określić z uwzględnieniem porad ekspertów dysponujących specjalistyczną wiedzą na temat rozpraszania gazów, sprzętu procesowego stosowanego w zakładzie, a także kwestii bezpieczeństwa i uwarunkowań technicznych. 174 Detecting Gas Saving Lives 2. Instalacja 2.2 Montaż Wykrywacz IRmax można zamontować na trzy sposoby: 1. Za pomocą wspornika montażowego Crowcon z bezpośrednim podłączeniem kabla (dotyczy wyłącznie zakresu pracy 4 – 20 mA). 2. Za pomocą dławnicy czopowej, w celu podłączenia do istniejącej skrzynki przyłączowej z certyfikatem Exe lub Exd. Firma Crowcon oferuje dławik z króćcem jako wyposażenie dodatkowe (patrz punkt 3 poniżej) 3. Za pomocą opcjonalnej dodatkowej skrzynki przyłączowej firmy Crowcon i dławnicy czopowej. Części wchodzące w skład wyposażenia dodatkowego podano w wykazie w Dziale 5 na strona 184. Wykrywacz IRmax należy zainstalować w wyznaczonej lokalizacji z tuleją czujnika umieszczoną poziomo +/- 15° (orientację przedstawiono na Schemat 2 na strona 172). Zabezpiecza to przed gromadzeniem się pyłu lub wody na podzespołach optycznych, 2.3 Podłączanie kabla bezpośrednio do IRmax Ta opcja jest odpowiednia wyłącznie dla działania w zakresie 4 – 20mA. Do przymocowania wykrywacza do ściany lub rury o średnicy 50 mm wymagany jest wspornik montażowy Crowcon. Diody LED stanu Sygna³ 0V (uziemienie) +V (24V IRmax) Schemat 4: • Połączenia kabli roboczych w detektorze IRmax Należy sprawdzić, czy używane dławnice kablowe mają odpowiedni certyfikat Exd i czy długość gwintu nie przekracza długości określonej na schemacie (po lewej). 15mm MAX Detecting Gas Saving Lives 175 Polski Należy podłączyć kable, używając certyfikowanej dławnicy, przez wybrany wlot kablowy na korpusie wykrywacza IRmax (M20 lub NPT ½ cala). Firma Crowcon zaleca instalację dławnic kablowych tak, aby były skierowane w dół. 2. Instalacja 2.3.1 Oznaczenie zacisku Przy wykrywaczu IRmax zorientowanym jak na Schemat 2 na strona 172 (wlot kablowy M20 na górze) trójprzewodowy kabel należy podłączyć, stosując wtyczkę w następujący sposób: +24 V na dole, 0 V w środku, sygnał na górze. Złącze z 6 wtykami z prawej strony płytki drukowanej służy do celów serwisowych i/lub podłączania modułu IR Display. Zacisk +ve: zasilanie +ve z karty sterowania. Zacisk Sig: Sygnał/wykrywanie z karty sterowania. Zacisk 0 V zasilanie -ve z karty sterowania. 2.3.2 Instalowanie wykrywacza IRmax za pomocą wspornika montażowego a. Wykrywacz IRmax może być dostarczony ze wspornikiem montażowym (S012130) zamiast dławnicy z króćcem z gwintem zewnętrznym, tak aby można było podłączyć go bezpośrednio do kabli (opis w Schemat 5). wspornik montażowy 70mm pomiędzy środkami mocowania. Użyj śrub M6. Schemat 5: Wykrywacz IRmax ze wspornikiem montażowym i dławnicą kablową Polski b. Jeśli wykrywacz IRmax ma zostać zamontowany na płaskiej powierzchni, należy zaznaczyć i wywiercić dwa otwory, używając wspornika montażowego jako szablonu. Obie części wspornika należy luźno zamocować, używając odpowiednich dla ściany/ powierzchni mocowań. c. Zdjąć nasadkę zabezpieczającą przed działaniem czynników atmosferycznych z wykrywacza IRmax i przeprowadzić korpus wykrywacza przez wspornik. Zalecana jest instalacja kadłuba wykrywacza IRmax z wlotem kablowym skierowanym w dół. 176 Detecting Gas Saving Lives 2. Instalacja d. Zabezpieczyć dwa mocowania wspornika tak, aby wykrywacz IRmax był pewnie utrzymywany na miejscu. Założyć ponownie nasadkę zabezpieczającą przed wpływem czynników atmosferycznych. e. Po pewnym zamocowaniu wykrywacza IRmax na miejscu odkręcić jego tylną zaślepkę, aby umożliwić dostęp do zacisków kabli. f. Przygotować kabel — firma Crowcon zaleca zastosowanie kabla z pancerzem 1,5 mm2 z drutu stalowego (SWA). Można używać kabli innych typów pod warunkiem ich zgodności z dławnicami z certyfikatem Exd. Zamocować dławnicę kablową z odpowiednim certyfikatem Exd, przeciągnąć żyły kablowe przez korpus wykrywacza IRmax i wkręcić dławnicę kablową. Zamocować dławnicę i sprawdzić, czy opancerzenie kabla jest uziemione do dławnicy kablowej i korpusu wykrywacza IRmax. UWAGA: po zainstalowaniu kabla należy ponownie zamontować tylną nakrętkę. g. Płytka mocująca (pozycja 9 na Schemat 3 ze strona 173) musi być bezpiecznie zamocowana aby zapobiec ryzyku poluzowania się tylnej nakrętki (lub instalowanego na stałe wyświetlacza IR względnie modułu IS Barrier) na skutek wibracji. 2.4 Instalowanie za pomocą dławnicy z króćcem z gwintem zewnętrznym i dodatkowej skrzynki przyłączowej Polski Tę opcję należy zastosować, jeśli wymagane jest połączenie wykrywacza IRmax z istniejącą dodatkowej skrzynki przyłączowej z certyfikatem Exd lub Exe. Schemat 6: Wykrywacz IRmax podłączony do skrzynki przyłączowej Detecting Gas Saving Lives 177 2. Instalacja 2.4.1 Aby przymocować wykrywacz IRmax do dodatkowej skrzynki przyłączowej: a. Ostrożnie zdemontować zewnętrzną część dławnicy z króćcem z gwintem zewnętrznym (poz. 8, Schemat 3 na strona 173). b. Przykręcić wąski koniec dławnicy z króćcem z gwintem zewnętrznym do dodatkowej skrzynki przyłączowej. c. Podnieść IRmax do skrzynki przyłączowej i poprowadzić przewody przez zespół i do dodatkowej skrzynki przyłączowej. Przymocować wykrywacz IRmax, przykręcając mocno pierścień do dławnicy kablowej. Przykręcić wkręt bez łba. d. Korpus wykrywacza IRmax można obrócić poziomo pod dowolnym kątem pod warunkiem, że jest to mechanicznie bezpieczne, nie koliduje z innym sprzętem i umożliwia dostęp do celów związanych z konserwacją e. Instrukcje dotyczące przewodów zawiera Dziale 2.6. Patrz również Schemat 4 na strona 175. 2.5 Wymagania dotyczące okablowania Okablowanie dochodzące do wykrywacza IRmax musi być zgodne z uznanymi standardami ustalonymi przez odpowiednie władze krajowe i spełniać wymagania elektryczne wykrywacza IRmax. Firma Crowcon zaleca zastosowanie kabla z pancerzem z drutu stalowego (SWA) i odpowiednich dławnic przeciwwybuchowych. Alternatywne techniki wykonania okablowania, takie jak stalowy kanał kablowy, są akceptowalne pod warunkiem spełnienia odpowiednich standardów. Maksymalna zalecana długość kabla wynosi 3,4 km (patrz tabela 1). Wykrywacz IRmax wymaga zasilania prądem stałym 12 – 30 VDC. Należy zapewnić dopływ z panelu sterowania do wykrywacza IRmax napięcia przynajmniej 12 V, biorąc pod uwagę spadek napięcia z powodu oporu kabla przy szczytowym natężeniu prądu 0,1 A. . Kabel 1,5 mm2 umożliwia zwykle poprowadzenie na odległość do 3,0 km. W tabeli 1 przedstawiono maksymalne odległości poprowadzenia kabla dla typowych parametrów. Powierzchnia przekroju kabla Opór Maksymalna odległość >20 V Maksymalna odległość od 18 do 20 mm2 (Omów na km) (km) (km) 1,0 18,4 2,2 1,6 1,5 13,0 3,0 2,3 2,5 11,5 3,4 2,6 Tabela 1: maksymalne odległości poprowadzenia dla typowych kabli Polski 178 Detecting Gas Saving Lives 2. Instalacja 2.6 Połączenia i ustawienia Wszystkie opisane połączenia odnoszą się do zespołu listew zaciskowych korpusu złącza wykrywacza IRmax. Zaciski na płytce drukowanej złącza wykrywacza IRmax są oznaczone „+”, „sig” i „0 V”. Podłączając wykrywacz do sprzętu sterującego, należy sprawdzić prawidłowość polaryzacji. Wykrywacz IRmax jest fabrycznie ustawiony jako „upływ prądowy”, chyba że w zamówieniu określono inaczej. W razie przestawienia na „źródło prądu” należy zdemontować płytę tylną i przesunąć dwa łączniki na płytce drukowanej zacisku z położenia „upływu prądowego” do położenia „źródło”, jak przedstawiono na Schemat 7. Uwaga: Zacisku uziemienia zewnętrznego należy używać tylko, jeśli lokalne władze zezwalają na takie połączenie lub wymagają go. Jeśli to możliwe, w celu ograniczenia zakłóceń częstotliwości radiowej dodatkowej skrzynki przyłączowej i opancerzenie kabla należy uziemić wyłącznie w panelu sterowania (obszar bezpieczny). Pozwala to uniknąć pętli uziemienia. +V 0V Sg 1 2 3 Sterownik CONTROLLER Ustawienia zworek EARTH Okablowanie Numer Kolor 1 2 3 upływu prądowego Funkcja Czerwony +V Czarny 0V Zielony Sygnał Złącze do podłączania zestawu do komunikacji z komputerem klasy PC źródło Złącze do podłączania wyświetlacza IR Display Diody LED stanu Sygnał 4 – 20 mA można ustawić na „upływ” lub „źródło” prądu, używając wtyków i łącznika zworki przedstawionych na schemacie 7. Ustaw prąd na „Sink“ (pochłanianie) poprzez ustawienie łącznika na piny 3 i 4 zgodnie z ilustracją na zdjęciu po lewej. Ustaw prąd na „Source“ (Źródło) poprzez ustawienie łącznika na piny 1 i 2 zgodnie z ilustracją na zdjęciu po lewej. Wykrywacze IRmax są ustawione na „upływ” prądu, chyba że w zamówieniu określono inaczej. Wskazanie diody LED: na płytce drukowanej zacisku jest zamocowana dioda LED, wskazująca bieżący stan działania. Dodatkowe informacje przedstawiono w Dziale 6 na strona 185. Detecting Gas Saving Lives 179 Polski Schemat 7: Położenie zworki upływu/źródła 3. Działanie OSTRZEŻENIE Przed wykonaniem jakichkolwiek prac instalacyjnych należy się upewnić, że są przestrzegane są lokalne przepisy i procedury właściwe dla miejsca instalacji. Nie wolno podejmować prób otwarcia wykrywacza IRmax lub dodatkowej skrzynki przyłączowej w obecności łatwopalnego gazu. Aby uniknąć fałszywych alarmów, należy sprawdzić, czy powiązany panel sterowania jest w stanie wstrzymania. 3.1 Procedura przekazania do ekploatacji 1. Sprawdzić, czy: a. Połączenia kabli są prawidłowe. b. Napięcie zasilania jest ustawione na karcie sterowania na zakres od 18 do 30 V. Napięcie mierzone na zaciskach wykrywacza IRmax (w skrzynce przyłączowej Exe, jeśli jest używana, lub zacisku na płytce drukowanej wykrywacza IRmax) i musi być ustawione na zakres od 12 do 30 V. c. Zwory są ustawione na karcie sterowania odpowiednio na upływ lub źródło 4 – 20 mA. 2. Po uruchomieniu, a przed podjęciem próby wyzerowania/kalibracji należy pozostawić urządzenie na 30 minut. To opóźnienie zapewnia osiągnięcie stabilności termicznej. (Uwaga: Wykrywacz IRmax będzie całkowicie zdatny do działania po upływie 30 sekund po doprowadzeniu mocy). 3. Przed zerowaniem należy zapewnić czyste powietrze (tj. bez gazu węglowodorowego). Odczyt zera jest dokonywany na karcie sterowania (patrz instrukcje karty sterowania). 4. Założyć nasadkę kalibracyjną na pokrywę zabezpieczającą przed działaniem czynników atmosferycznych aby odizolować komorę pomiarową od powietrza otoczenia. Taką nasadkę można zamówić w firmie Crowcon (M041007). Podłączyć gaz kalibracyjny (50% wartości nominalnej dolnej granicy wybuchowości) i zastosować przepływ 1 litr na minutę. 5. Po 30 sekundach dostosować kalibrację/okres na karcie sterowania tak, aby odczyt wskazywał 50% dolnej granicy wybuchowości lub odpowiadał zastosowanemu stężeniu gazu kalibracyjnego. Sam wykrywacz IRmax nie wymaga kalibracji. 6. Odciąć gaz i zdemontować nasadkę kalibracyjną. Sprawdzić ponownie punkt zerowy 7. Po instalacji lub wymianie lusterka wykrywacz można wyzerować i skalibrować z zastosowaniem wyświetlacza IR Display (opis w strona 169) lub za pośrednictwem zestawu do komunikacji z komputerem (patrz podręcznik „Akcesoria IRmax”). Uwaga: Wykrywacze IRmax z certyfikatem ATEX są dostarczane skalibrowane zgodnie z normą EN61779 (gdzie na przykład 100% dolnej granicy wybuchowości metanu = 4,4% objętości). Polski Uwaga: zaleca się użycie w celu wstępnego przekazania do eksploatacji nasadki kalibracyjnej. Kolejne kalibracje można wykonywać przez zdalne doprowadzenie gazu do nasadki zabezpieczającej przed działaniem czynników atmosferycznych przez króciec (unikając bezpośredniego dostępu do wykrywacza IRmax). Kalibrację bez nasadki kalibracyjnej (tj. bezpośrednio przez nasadkę zabezpieczającą przed działaniem czynników atmosferycznych) można wykonać pod warunkiem, że lokalna prędkość wiatru jest niższa niż 2 m/s. Szybkość przepływu gazu musi przekraczać 2,0 litra/min. 180 Detecting Gas Saving Lives 3. Działanie 3.2 Rutynowa konserwacja Częstotliwość testowania wykrywaczy jest określana przez procedury zakładowe. Crowcon zaleca wykonywanie testów gazowych wykrywacza IRmax przynajmniej co 6 miesięcy i, w razie potrzeby, ponowną kalibrację. W celu przeprowadzenia ponownej kalibracji wykrywacza IRmax należy wykonać kroki podane w Dziale 3.1. W przypadku usterki elektrycznej należy skonsultować się z lokalnym przedstawicielem firmy Crowcon. Częstotliwość kalibracji: Firma Crowcon zaleca wykonywanie kalibracji co 12 miesięcy. Zdalna kalibracja przy użyciu przewodu: Szybkość wiatru musi być mniejsza niż 2,0 m/s. Jeśli jest większa, należy zastosować nasadkę kalibracyjną w celu zapobieżenia rozcieńczeniu gazu. Czyszczenie optyki: Nie zaleca się, chyba że wykrywacz IRmax jest w stanie awarii z powodu całkowitego zaślepienia optyki. Jeśli dojdzie do zabrudzenia jakiegokolwiek elementu optycznego, należy go ostrożnie wyczyścić przy pomocy chusteczek nasączonych alkoholem izopropylowym lub miękkiej tkaniny znajdującej się w zestawie do czyszczenia lusterka. (Patrz Dziale 5, Akcesoria i części zamienne na strona 184). Zwierciadła: Jeśli lusterko zostało uszkodzone, należy nabyć zestaw do wymiany lusterka (patrz Dziale 5, Akcesoria i części zamienne na strona 184). Po wymianie lusterek wykrywacz IRmax należy zawsze ponownie wyzerować i powtórzyć kalibrację. Jeśli kondensacja zaczyna powodować usterki, wymienić lusterko (pokrycie optyczne mogło ulec uszkodzeniu). Firma Crowcon zaleca wymianę lusterek co 5 lat. 3.3 Zmiana typu gazu Polski Każdy wykrywacz IRmax jest dostarczany wstępnie skalibrowany dla określonego typu gazu (np. metan lub propan). Jeżeli potrzebna jest rekalibracja dla poszczególnych gazów, wówczas można przeprowadzić rekonfigurację urządzenia IRmax przy pomocy zestawu do połączenia z komputerem PC (patrz Dziale 5, Akcesoria i części zamienne na strona 184), a następnie dokonać kalibracji urządzenia. Detecting Gas Saving Lives 181 3. Działanie 3.4 Odpowiedź względna na inne typy gazów Na poniższym wykresie przedstawiono odpowiedzi względne wykrywacza IRmax skalibrowanego na metan na inne typy gazów. Uwaga: wiele węglowodorów w formie gazów i oparów jest wykrywane przez czujniki IR zdecydowanie łatwiej niż metan. Reakcja urządzenia IRmax (oraz innych czujników gazu wykorzystujących promieniowanie podczerwone) działa linearnie w całym przedziale (0-100%) dolnej granicy wybuchowości (tzn. w tym przypadku metanu) ale nie działa linearnie w przypadku innych węglowodorów, które mogą być obecne. Schemat 8 Na schemacie przedstawiono odpowiedź wymienionych powyżej gazów: od lewej do prawej propan, butan, pentan i metan. Dostępne są inne typy i zakresy gazów. Aby uzyskać bardziej szczegółowe informacje, należy skontaktować się z firmą Crowcon. Polski 182 Detecting Gas Saving Lives Materiał obudowy Stal nierdzewna 316 Wymiany (tylko wykrywacz IRmax) 150 mm x 75 mm x 66 mm (bez czopu) Masa IRmax 1,58 kg IRmax z wersją stałą wyświetlacza IR Display 2 kg IRmax z modułem bariery iskrobezpiecznej 2,4 kg Zdalny wyświetlacz IR Display 0,2 kg Napięcie robocze Od 12VDC do 30VDC Moc <1W Sygnał wyjściowy 3 przewody, 4 – 20 mA (upływ lub źródło) Sygnał usterki <1 mA Maksymalna resystancja pętli przewodu 80 Ohmów (stosunkowo do –terminalu ve) Temperatura pracy Od -40°C do +75°C (od -40°F do +167°F) Wilgotność Wilgotność względna 0 – 100% Stopień ochrony IP66 Zabezpieczenie przed wybuchem Przeciwwybuchowy Kod atestu ATEX IRmax (bez wyświetlacza IR Display) II 2 GD Exd db IIC T6 Gb (Tamb = -40°C do +50°C) II 2 GD Exd db IIC T4 Gb (Tamb = -40°C do +75°C) II 2 GD Ex tb IIIC T135°C Db (-40°C ≤ Ta≤ +75°C) Urządzenie IRmax z modułem IS Barrier (wyświetlacz zdalny) II 2 GD Exd db ia IIC T4 Gb (Tamb = -40°C do +75°C) Ex tb ia IIIC T135°C Db (Tamb = -40°C do +40°C) Urządzenie IRmax z zamontowanym na stałe wyświetlaczem II 2 G Exd db ia IIC T4 Gb (Tamb = -40°C do +75°C) Nr certyfikatu bezpieczeństwa ATEX i IECEx IRmax (bez wyświetlacza IR Display): Baseefa 09ATEX0206X i IECEx BAS.09.0109X IRmax (z wyświetlaczem IR Display): Baseefa 09ATEX0220X i IECEx BAS.09.0104X Bezpieczeństwo Funkcjonale Urządzenie certyfikowane do użytku w systemach SIL 2. Numer certyfikatu Sira 12ATEX1206X Standardy EN 60079-0:2012+A11:2013, EN 60079-1:2014, EN 60079-31:2014 IEC 60079-0:2011, IEC 60079-1:2014, IEC 60079-31:2013 EN 60079-29-1:2007, IEC 61508:2010, EN50402:2005 Strefy Certyfikowany do użytku w Strefie 1 lub Strefie 2 Zgodność elektromagnetyczna EN50270 Detecting Gas Saving Lives 183 Polski 4. Dane techniczne 5. Akcesoria i części zamienne Numery części Nazwa Opis M041007 Nasadka kalibracyjna Mocowana na standardowej nasadce odpornej na działanie czynników atmosferycznych, gdy lokalna prędkość wiatru przekracza 2 m/s. S012130 Zestaw wspornika montażowego Umożliwia zamontowanie na ścianie lub rurze 2-calowej (50 mm). Nie jest wymagany w przypadku mocowania wykrywacza IRmax do istniejącej skrzynki przyłączowej. S012152 Zasłona przeciwsłoneczna/ stożek kolektora w celu zabezpieczenia przed podwyższonymi temperaturami powstającymi w wyniku bezpośredniego wystawienia na światło słoneczne i/lub w celu zwiększenia zakresu pokrycia wykrywaczy, aby umożliwić wykrywanie gazów lżejszych niż powietrze (metan). S012169 Zestaw montażowy do kanałów Umożliwia monitorowanie kanałów od 300 mm do 3000 mm i przepływu powietrza między 2 m/s a 20 m/s. S012996 Adaptor przepływowy Do próbkowania gazu. S012827 Zestaw do komunikacji z komputerem Moduł komunikacyjny, oprogramowanie i przewód, umożliwiające skonfigurowanie wykrywacza. M20: S012295 ½” NPT: S012296 Dodatkowej skrzynki przyłączowej Opcja montażu wykrywacza IRmax do stosowania w obszarach niebezpiecznych. C011210 Zestaw do czyszczenia lustra Zawiera chusteczki nasycone IPA oraz ściereczkę z mikrowłókien Części zamienne wykrywacza IRmax Szczegóły dotyczące części zamiennych — patrz Schemat 3 on strona 173. Polski 184 Detecting Gas Saving Lives 6. Wykrywanie usterek 6.1 Błędy sygnalizowane przez diodę LED Wskazania diody LED zamontowanej na płytce drukowanej wyprowadzeń mogą być pomocne w diagnozowaniu uszkodzeń. Położenie diody przedstawiono na Schemat 7 na strona 179. W tabeli poniżej przedstawiono interpretację nieprawidłowości na podstawie sekwencji wskazań diody. Wzorzec sygnału diody LED Stan IRmax Regularne błyski odstępach sekundowych Włączenie z krótkimi gasnącymi impulsami. Szybkie lub nieregularne błyski. Prawidłowy. Stale włączona. Usterka, błąd hosta lub modułu i-Module. Błąd krytyczny; usterka lampy lub wykrywacza Błąd krytyczny; usterka modułu lub konfiguracji. Dwa długie błyski, po których następuje krótki błysk. Szybkie dwukrotne błyski w odstępach sekundowych. Krótkie impulsy w odstępach sekundowych. Wykrywacz IRmax w trybie uruchamiania. Napięcie zasilania za niskie lub za wysokie. Zasłonięcie elementów optycznych. Działanie Odczekać 10 sekund. Sprawdzić, czy napięcie zasilania wykrywacza IRmax jest prawidłowo ustawione. Sprawdzić, czy pomiar jest wykonywany bezpośrednio na zaciskach wykrywacza IRmax. Wyłączyć i włączyć IRmax; jeśli usterka utrzymuje się, zwrócić go do firmy Crowcon. Zwrócić wykrywacz do firmy Crowcon. Sprawdzić konfigurację wykrywacza IRmax za pomocą oprogramowania Zestaw do komunikacji z komputerem. Sprawdzić zasilanie. Jeśli usterka utrzymuje się, zwrócić wykrywacz do firmy Crowcon. Sprawdzić szybkę i lusterko, w razie potrzeby wyczyścić. Ponownie wyzerować wykrywacz IRmax i sprawdzić kalibrację. Jedyną drogą usunięcia innych usterek jest zwrot wykrywacza IRmax do firmy Crowcon lub autoryzowanego agenta serwisowego. Jeśli wystąpi błąd analogowego sygnału wyjściowego lub jeśli brak połączenia z układem sterowania lub rezystorem obciążającym, detektor IRmax pozostanie w trybie usterki, a na wyświetlaczu IR Display (jeśli na wyposażeniu) pojawi się komunikat „Wymagana naprawa” (Service required). Detektor IRmax aktywnie monitoruje analogowy sygnał wyjściowy 4 – 20 mA w celu sprawdzenia, czy znajduje się w zakresie. Jeśli sygnał jest poza zakresem, detektor przechodzi w tryb usterki i ustawia sygnał wyjściowy na 1 mA. Dlatego też podczas testowania detektora bardzo ważne jest, aby był on podłączony do panelu sterowania lub by między zaciskiem „0 V” i „Sig” (detektor ustawiony w trybie „źródło”) lub zaciskiem „0 V” i „+V” (detektor ustawiony w trybie „ujście”) był podłączony rezystor obciążający 100 Ω. Detecting Gas Saving Lives 185 Polski 6.2 Wyjście analogowe 7. Konfiguracja RS485 Modbus 7.1 Informacje ogólne W tym rozdziale wyjaśniono sposób zastosowania wykrywaczy IRmax w konfiguracji magistrali Modbus. Dla takich zastosowań dostępna jest wersja obsługująca standard RS485. W konfiguracjach gwiazdy lub magistrali można połączyć do 28 wykrywaczy IRmax, zgodnie z zamieszczonym poniżej opisem. Połączenia z wersją wykrywacza IRmax obsługującą standard RS485 należy wykonywać przez dławnicę czopową, do dodatkowej skrzynki przyłączowej (patrz Dziale 5 na strona 184); jest to rozwiązanie lepsze niż prowadzenie okablowania bezpośrednio do wykrywacza. Należy zauważyć, że wyświetlacz IR Display nie może być stosowany z wykrywaczem IRmax z odblokowanym interfejsem RS485. Wersja wykrywacza IRmax obsługująca standard RS-485 ma pięć zacisków pola. Zaciski to: 1 Zasilanie dodatnie Od 12 V do 30 V powyżej 0 V 2 0V Powrót i odniesienie RS485 3 Sygnały 4 – 20 mA Sygnał źródła lub upływu (wyposażenie opcjonalne) 4 RS485 B Sygnał różnicowy RS485 5 RS485 A Sygnał różnicowy RS485 Sygnały na zaciskach RS485 są zgodne ze standardem EIA/TIA-485, co oznacza zakres trybu ogólnego wynoszący od -7 V do +12 V w odniesieniu do zacisku 0V. Należy zauważyć, że nie wszyscy producenci urządzeń RS485 zachowują zgodność w odniesieniu do polaryzacji sygnałów A i B. Jeśli okablowanie nie działa w jeden sposób, użytkownik powinien zamienić przewody A i B RS-485. Nie występuje niebezpieczeństwo utworzenia nieprawidłowego połączenia. Ustawienie komunikacji to 9600 b/s, dwa bity zakończenia transmisji i brak parzystości. Ważne jest, aby podczas kompilowania interfejsu dla układu sterowania wziąć pod uwagę czas, jaki zajmuje układowi zgromadzenie informacji z poszczególnych wykrywaczy po kolei. Największa szybkość, z jaką można odpytywać wiele wykrywaczy, wynosi 14 wykrywaczy na sekundę; względy praktyczne mogą spowodować ograniczenie tej wartości do 7 wykrywaczy na sekundę. Użytkownik musi zapewnić, aby układ umożliwiał rejestrację sygnałów alarmowych w akceptowalnych granicach czasu. Ważne jest również, aby zapewnić zasilanie całego systemu wystarczające dla utrzymania pracy wszystkich wykrywaczy. Informacje na temat mocy wymaganej przy łączeniu magistrali liniowej zawiera patrz Dziale 7.3, Wymaganie dotyczące okablowania, na strona 188. Polski Aby uzyskać wyczerpujące instrukcje dotyczące magistrali Modbus, należy skontaktować się z firmą Crowcon (patrz adresy na tylnej okładce). 186 Detecting Gas Saving Lives 7. Konfiguracja RS485 Modbus 7.2 Topologia okablowania Dwoma używanymi powszechnie topologiami są połączenie w układzie gwiazdy i magistrala liniowa. 7.2.1 Połączenie w układzie gwiazdy W połączeniu w układzie gwiazdy wszystkie wykrywacze są połączone przewodami z punktem centralnym, którym zwykle jest panel sterowania. Nie są wymagane kable z więcej niż 5 rdzeniami, ponieważ wszystkie połączenia sygnałów 4 – 20 mA są wykonywane bezpośrednio do panelu sterowania. Wszystkie sygnały A i B RS485 można następnie połączyć w punkcie gwiazdy. Magistralę należy następnie zakończyć w punkcie gwiazdy pojedynczym opornikiem zakończeniowym 110 omów. Długość poszczególnych ramion gwiazdy nie może przekraczać 750 metrów. 7.2.2 Połączenie magistrali liniowej W połączeniu z magistralą wszystkie wykrywacze IRmax są połączone przewodami w układzie liniowym, zwykle z panelem sterowania na jednym końcu. Klasycznym przykładem jest instalacja tunelowa, ze wszystkimi wykrywaczami IRmax instalowanymi w regularnych odstępach (patrz Schemat 9 poniżej). Aby wykonać okablowanie instalacji, należy zamontować dwa rezystory końcowe 110 omów na każdym z fizycznych końców magistrali. Ponieważ sygnały 4 – 20 mA nie mogą być współdzielone, na każdym hopie okablowania wymagany jest dodatkowy przewodnik. Jeśli nie jest używany żaden z sygnałów 4 – 20 mA, wymagane są tylko cztery przewodniki. RYSUNEK POŁĄCZEŃ MAGISTRALI LINIOWEJ DO PANELU STEROWANIA Polski Schemat 9 Detecting Gas Saving Lives 187 7. Konfiguracja RS485 Modbus 7.3 Wymaganie dotyczące okablowania 7.3.1 Obliczanie minimalnego wymaganego poziomu mocy Im więcej wykrywaczy IRmax jest podłączonych do magistrali liniowej, tym większa moc jest wymagana do działania systemu. Aby obliczyć moc wymaganą dla określonej konfiguracji, należy znać opór kabla między poszczególnymi parami wykrywaczy IRmax. Dla każdego hopu między wykrywaczami IRmax należy dostarczyć prąd przynajmniej 0,1 mA. Napięcie, które należy zastosować, można obliczyć, szacując spadek napięcia na każdym hopie — aby ostatni wykrywacz IRmax działał prawidłowo, na końcu musi pozostać przynajmniej 12 V. W celu uzyskania porady w szczególnych przypadkach należy skontaktować się z firmą Crowcon. Można również wykonać kroki opisane poniżej i przykładowe obliczenie podane w następnym rozdziale. 1. Napięcie nie może spaść poniżej 12 V, więc obliczenie należy rozpocząć od ustawienia napięcia na ostatnim wykrywaczu IRmax w linii na tę wartość. 2. Każdy wykrywacz IRmax może zużyć do 0,1 A. Stratę napięcia kabla na pierwszym hopie między wykrywaczami można obliczyć, przyjmując prąd sumaryczny o wartości 0,1 A i mnożąc go przez opór kabla na hopie między ostatnim a przedostatnim wykrywaczem. 3. To napięcie należy dodać do wstępnej wartości 12 V w celu uzyskania najniższej dopuszczalnej wartości napięcia na przedostatnim wykrywaczu IRmax. Należy dodać 0,1 A do wartości prądu sumarycznego, aby uzyskać wartość 0,2 mA, minimalny prąd przepływający przez przedostatni hop magistrali. Tę wartość należy pomnożyć przez opór kabla dla przedostatniego hopu, aby uzyskać następny spadek napięcia. 4. Ten proces należy powtórzyć dla wszystkich wykrywaczy IRmax, akumulując straty napięcia występujące między poszczególnymi wykrywaczami. 5. Nie może zostać przekroczona maksymalna wartość napięcia wykrywacza IRmax wynosząca 30 V. 7.3.2 Przykładowe obliczenie W ramach przykładu podano tu wyniki obliczeń dla sześciu wykrywaczy IRmax rozmieszczonych równo w odległościach 250 m na kablu o przekroju 1 mm2. Każdy hop ma opór 4,6 oma. Polski Stanowisko Napięcie zasilania Prąd zasilania 1 12 0,1 A 2 12,46 0,2 A 3 13,38 0,3 A 4 14,76 0,4 A 5 16,6 0,5 A 6 18,9 0,6 A Zasilanie panelu 21,66 0,6 A 188 Detecting Gas Saving Lives 8. Podręcznik Bezpieczeństwa Funkcjonalnego 8.1 Wstęp Poniższe sekcje przedstawiają szczegółowe informacje o certyfikacji urządzeń IRmax zgodnej z normami Bezpieczeństwa Funkcjonalnego IEC 61508 i EN 50402. Przedstawione są informacje o funkcjach uwzględnianych w obudowach bezpiecznych, wymogach konserwacyjnych i dane umożliwiające integrację urządzenia IRmax z Systemem Automatyki Zabezpieczeniowej. 8.2 Urządzenie IRmax i funkcja zabezpieczająca IRmax Modbus Aby zmierzyć stężenie gazu palnego i przedstawić wyniki pomiaru za pomocą mocy wyjściowej 4-20mA. Błędy w funkcjach bezpieczeństwa będą wykrywane przez sprzęt i oprogramowanie układowe. Będą one przedstawiane za pomocą mocy wyjściowej niższej niż 3,6mA lub wyższej niż 21mA. Nazwa parametru Przedział czasowy badania potwierdzającego Średni czas potrzebny na naprawę Symbol Równanie / źródło T1 Zgodnie z definicją Crowcon. MTTR Zgodnie z definicją Crowcon. IRmax 8 760 godzin (rocznie) 8 godzin Rodzaj A/B Rodzaj A Zgodnie z definicją Crowcon. Rodzaj B Łącznie usterek: λ Od FMEDA 1.04E-05 Bezpieczne zdiagnozowane usterki: λSD Od FMEDA 1.95E-08 Bezpieczne niezdiagnozowane usterki: λSU Od FMEDA 8.59E-08 Niebezpieczne zdiagnozowane usterki: Niebezpieczne niezdiagnozowane usterki: Bezpieczne usterki nie mające wpływu na działanie: Diagnozowany obszar: λDD Od FMEDA 9.74E-06 λDU Od FMEDA 5.06E-07 λNE Od FMEDA 3.21E-09 DC λDD / (λDU + λDD) 95.06% Ułamek Bezpiecznych Usterek: SFF (λSD + λSU + λDD) / λ 95.11% Odpowiednik okresu przestoju (λDU / λD)(T/2 + MTTR) + tCE 2.24E+02 kanału (λDD / λD ) MTTR PFDAVG (z wykorzystaniem PFDAVG (λDU + λDD) tCE 2.30E-03 równania 61508-6) PFDAVG (z wykorzystaniem PFDAVG λDU (T / 2+MTTR) + (λDD MTTR) 2.30E-03 równania uproszczonego) PFDAVG (z wykorzystaniem PFDAVG 1-ε-(λdd+λdu) tce 2.30E-03 równania IEC 61508-6) Kompatybilność z SIL (Tryb niskiego SIL2 zapotrzebowania) Kompatybilność z SIL (Tryb SIL2 wysokiego zapotrzebowania) W przypadku zastosowań z niskim zapotrzebowaniem i ułamka bezpiecznych usterek, wszystkie warianty systemu nadają się do wykorzystania w zastosowaniach SIL 2. Detecting Gas Saving Lives 189 Polski 8.3 Dane Bezpieczeństwa Funkcjonalnego Podręcznik Bezpieczeństwa Funkcjonalnego 8.4 Konfiguracja Sprzętowa Do oceny poziomu integralności bezpieczeństwa sprzętu zastosowano Kolejność operacji 1H (Odporność na błędy sprzętowe i ułamek bezpiecznych awarii). 8.5 Konfiguracja Oprogramowania Oceniono oprogramowanie układowe produktu zgodnie z kryteriami określonymi w IEC 61508:3 2010. 8.6 Awarie systemowe Do oceny zgodności z wymaganiami w zakresie unikania awarii systemowych zastosowano kolejność operacji 1S (określona w paragrafie 7.4.2.2c IEC 61508:2 2010). 8.7 Częstotliwość diagnostyki Większość funkcji diagnostycznych jest monitorowana na bieżąco. Badania systemu nadzoru są realizowane w trakcie corocznego badania, w trakcie których urządzenie poddaje się cyklicznym zmianom mocy: Urządzenie IRmax musi być corocznie poddane cyklicznym zmianom mocy (tzn. odłącza się zasilanie prądem stałym 24V i podłącza je ponownie), stanowi to część programu konserwacji produktu (prosimy sprawdzić tez sekcję 3.2). 8.8 Ograniczenia Wskaźnik awaryjności jest stały. Przeprowadzane nie rzadziej niż raz do roku badanie sprawności urządzenia wykryje wszystkie niewykryte wcześniej usterki. Średni czas potrzebny na przeprowadzenie naprawy to 8 godzin. Zakłada się, że użytkownik korzysta z funkcji diagnozowania poprzez wyświetlacz IR i/lub poprzez interfejs PC, w celu zminimalizowania potencjalnego czasu przestoju urządzenia. Ocena niezawodności to proces statystyczny, w którym wykorzystuje się informacje o awariach do jakich dochodziło w przeszłości do odpowiednich modyfikacji projektu i konfiguracji. Zapewnia on wiarygodny cel/szacunkowe dane prawdopodobnej niezawodności urządzenia, zakładając, że produkcja, projektowanie i warunki eksploatacji są identyczne jak te, w których gromadzono dane. Jest to cenna metoda przeglądu projektu pozwalająca porównywać alternatywne projekty, określać rząd wielkości docelowej wydajności i oceniać potencjalny wpływ zmian w projekcie. Nie można jednak zagwarantować, że konkretne przewidywane wartości będą identyczne co liczba awarii, jaka wystąpi w praktyce, liczba ta zależy od wielu czynników, których nie można uwzględnić w obliczeniach. Polski Na potrzeby tej prognozy zakłada się, iż wskaźnik awaryjności (symbol λ) będzie wartością stałą. Niezawodność urządzeń malałyby na skutek wczesnych usterek, jak również usterek wynikających ze zużycia, jednak zakłada się, że ryzyko to jest wyeliminowane poprzez wygrzewanie wczesne i prewencyjną wymianę urządzeń na nowe. 190 Detecting Gas Saving Lives Podręcznik Bezpieczeństwa Funkcjonalnego Prawdopodobieństwo uszkodzenia w chwili zadziałania jest prawdopodobieństwem, że usterka systemu wystąpi w dowolnym, losowo wybranym, momencie. Jest to tożsame z niedostępnością w stanie ustalonym, powodowaną przez: Niedostępność = (λ x MDT)/(1 + (λ x MDT)) która wynosi w przybliżeniu λ x MDT dla niskich wartości λ x MDT gdzie λ to wskaźnik awaryjności a MDT to Średni Czas Przestoju (Mean Down Time). Jest to zgodne z wyrażeniem Dostępności jako: MTBF/(MTBF+MDT) Użyty wskaźnik awaryjności, i określona w ten sposób dostępność to wartości związane z dobrze przetestowanym projektem, po odpowiednim okresie wzrostu niezawodności. 8.9 Środowiskowe Ograniczenia środowiskowe: Produkt powinien być używany w temperaturze otoczenia mieszczącej się w przedziale od -40°C do +75 °C Produkt powinien być przechowywany w temperaturze otoczenia mieszczącej się w przedziale od -40°C do +80 °C Produkt powinien być używany przy wilgotności otoczenia mieszczącej się w przedziale od 0% do 100% kondensacji. Produkt spełnia wymagania odporności na kurz i wodę IP66, zgodnie z definicją zawartą w normie EN60529. Produkt jest przeznaczony do pracy ciągłej. 8.10 Tolerancja na usterki sprzętowe Współczynnik HFT (tolerancja na usterki sprzętowe) wynosi 0 8.11 Zdolność systemowa Urządzenia IREX/IRmax należą do klasy SC2. 8.12 Klasyfikacja Detecting Gas Saving Lives Polski IREX/IRmax jest komponentem typu B. 191 Gwarancja To wyposażenie opuszcza naszą fabrykę jako w pełni przetestowane i skalibrowane. Jeśli w ciągu okresu obowiązywania gwarancji, wynoszącego trzy lata od wysyłki, wyposażenie ulegnie awarii z powodu wadliwego wykonawstwa lub wadliwych materiałów, producent wedle własnego uznania wykona bezpłatną naprawę lub wymieni wyposażenie, pod następującymi warunkami. Procedura gwarancyjna W celu ułatwienia skutecznego przetwarzania wszelkiego rodzaju roszczeń, należy skontaktować się z naszym działem wsparcia klienta pod numerem +44 (0)1235 557711, podając następujące informacje: Nazwa kontaktowa, numer telefonu, numer faksu i adres e-mail. Opis i ilość zwracanych towarów, z uwzględnieniem wszystkich akcesoriów. Numery seryjne przyrządu. Przyczyna dokonania zwrotu. W celu identyfikacji i śledzenia należy uzyskać formularz zwrotu. Formularz ten wraz z etykietami zwrotu można pobrać z naszej witryny internetowej crowconsupport.com. Możemy również wysłać kopię pocztą e-mail. Przyrządy IRmax bez Numeru Zwrotu Crowcon (CRN) nie będą akceptowane do obsługi gwarancyjnej. Konieczne jest mocne przytwierdzenie etykiety adresowej do zewnętrznego opakowania zwracanych towarów W przypadku stwierdzenia zmian, modyfikacji, demontażu lub manipulacji przy przyrządzie gwarancja zostanie uznana za nieważną. Gwarancja nie obejmuje nieprawidłowego lub niezgodnego z przeznaczeniem użycia urządzenia. Zrzeczenie się odpowiedzialności Firma Crowcon nie ponosi żadnej odpowiedzialności za straty lub szkody wynikowe lub pośrednie, powstające w jakikolwiek sposób (z uwzględnieniem wszelkich strat lub szkód wynikających z zastosowania przyrządu). Ponadto firma Crowcon jednoznacznie wyklucza wszelką odpowiedzialność wobec stron trzecich. Niniejsza gwarancja nie obejmuje dokładności kalibracji urządzenia ani wykończenia estetycznego produktu. Urządzenie należy konserwować zgodnie z instrukcjami obsługi i konserwacji. Gwarancja dotycząca wymiany elementów zużywalnych (takich, jak lusterka), dostarczanych w ramach gwarancji w celu wymiany uszkodzonych elementów, jest ograniczona do niewygasłej gwarancji pierwotnie dostarczonego elementu. Polski Firma Crowcon zastrzega sobie prawo do określenia skróconego okresu gwarancji lub odrzucenia okresu gwarancji dla dowolnego czujnika dostarczonego w celu zastosowania w środowisku lub w celu, o którym wiadomo, że wiąże się z nim niebezpieczeństwo zniszczenia lub uszkodzenia czujnika. Nasza odpowiedzialność dotycząca uszkodzonego wyposażenia jest ograniczona do zobowiązań ustanowionych w gwarancji i wszelkie rozszerzone gwarancje, warunki lub stwierdzenia, wyraźnie lub w dorozumiany sposób wynikające z ustaw, dotyczące jakości handlowej naszego sprzętu lub jego odpowiedniości do jakiegokolwiek konkretnego zastosowania, są wyłączone, z wyjątkiem przypadków ustawowo zabronionych. Niniejsza gwarancja nie wpływa na ustawowe prawa klienta. 192 Detecting Gas Saving Lives Warranty Firma Crowcon zastrzega sobie prawo do zastosowania opłat za obsługę i transport, jeśli urządzenie zwrócone jako uszkodzone okaże się wymagać tylko normalnej kalibracji lub serwisu, których dokonania klient odmówi. Aby zadać pytania dotyczące gwarancji i wsparcia technicznego, należy skontaktować się z: Dział wsparcia klienta Tel: +44 (0) 1235 557711 Faks: +44 (0) 1235 557722 Polski Email: [email protected] Detecting Gas Saving Lives 193 Conteúdo Conceito e segurança................................................................................ 197 Conceito do detector IRmax ............................................................. 197 Informações de segurança.................................................................. 198 Visão geral do produto...................................................................... 199 1. Introdução............................................................................................. 200 1.1 Geral............................................................................................ 200 1.2 Descrição do produto................................................................... 200 2. Instalação.............................................................................................. 202 AVISO................................................................................................ 202 2.1 Local............................................................................................ 202 2.2 Montagem................................................................................... 203 2.3 Conexão de cabos diretamente ao detector IRmax .................... 203 2.3.1 Designação de terminal....................................................... 204 2.3.2 Como instalar o detector IRmax utilizando um suporte de montagem................................................................................... 204 2.4 Como instalar usando um adaptador de conexão e uma caixa de derivação auxiliar............................................................................... 205 2.4.1 Para encaixar o detector IRmax em uma caixa de derivação auxiliar:........................................................................................ 206 2.5 Requisitos de cabeamento........................................................... 206 2.6 Conexões e configurações........................................................... 207 3. Operação.............................................................................................. 208 3.1 Procedimento de preparação....................................................... 208 3.2 Manutenção de rotina................................................................. 209 3.3 Como alterar tipos de gás............................................................ 209 3.4 Respostas relativas de tipos de gás............................................... 210 4. Especificações........................................................................................ 211 5. Acessórios e peças de reposição............................................................ 212 6. Como localizar falhas .......................................................................... 213 6.1 Erros indicados pela LED.............................................................. 213 6.2 Saída Analógica........................................................................... 213 7. Configuração do Modbus RS485........................................................... 214 7.1 Geral............................................................................................ 214 7.2 Topologias de cabeamento.......................................................... 215 7.2.1 Conexão estrela................................................................... 215 7.2.2 Conexão de barramento linear............................................ 215 7.3 Requisitos de cabeamento........................................................... 216 7.3.1 Como calcular o nível mínimo de energia necessária .......... 216 7.3.2 Cálculo de amostra............................................................. 216 8. Manual de Segurança Funcional............................................................ 217 8.1 Introdução................................................................................... 217 8.2 Função de Segurança do IRmax e do Modbus do IRmax.............. 217 8.3 Dados de Segurança Funcional..................................................... 217 8.4 Configuração do Hardware.......................................................... 218 8.5 Configuração do Software........................................................... 218 8.6 Falhas Sistemáticas....................................................................... 218 8.7 Intervalo de Diagnóstico............................................................... 218 8.8 Restrições..................................................................................... 218 8.9 Meio ambiente............................................................................. 219 8.10 Tolerância de Falha de Hardware (TFH)...................................... 219 8.11 Capacidade do Sistema.............................................................. 219 8.12 Classificação.............................................................................. 219 Garantia.................................................................................................... 220 Conceito e segurança Conceito do detector IRmax IRmax é um detector infravermelho (IV) de gases ultra compacto que fornece uma detecção rápida e à prova de falhas de vapores e gases de hidrocarbonetos. Com uma tecnologia de sensores IV com duplo comprimento de onda em uma resistente caixa de aço inoxidável 316, o detector IRmax foi projetado para operação nas áreas mais críticas. Ao contrário dos detectores de gases convencionais, o detector IRmax não possui aquecedores a fim de evitar condensação em janelas e espelhos. O revestimento STAY CLIR em componentes ópticos evita a formação de condensação enquanto o detector IRmax está em funcionamento. O detector IRmax é compatível com qualquer sistema de controle 4-20mA e também pode ser instalado em uma rede endereçável RS485 Modbus. (consulte a Seção 7). O detector IRmax requer somente 1 Watt de energia, em geral de 75 a 90% menos que os detectores de gases IV convencionais. O detector IRmax inclui uma câmara de gases de difusão compacta que, em combinação com uma tampa à prova de intempéries eficaz, fornece uma excelente velocidade de resposta. A tampa à prova de intempéries foi projetada com uso de um software de modelação de fluxo a fim de permitir a exposição a gases remota e a calibração do detector IRmax, desta forma um adaptador de calibração especial não é necessário. O IR Display torna possível monitorar as leituras do IRmax tanto localmente como remotamente. Um IR Display pode ser instalado diretamente no IRmax. Como alternativa, o IRmax pode ser fornecido com um módulo de barreira Intrinsecamente Seguro (IS) incluído. Um IR Display pode então ser conectado ao Módulo de barreira IS por um cabeamento temporário ou permanente. As opções disponíveis estão ilustradas no Diagrama 2, página 201. Detecting Gas Saving Lives 197 Português Brasileiro Para mais informações sobre outros acessórios para o IRmax, consulte a Figura 3 na página 28 e a Seção 5, na página 39. Conceito e segurança Informações de segurança • Os detectores de gases IRmax devem ser instalados, operados e mantidos rigidamente de acordo com estas instruções, avisos, informações de rótulo e dentro das limitações indicadas. • A porca da parte traseira do detector IRmax deve ser mantida firmemente fechada durante a operação. Não tente remover a porca traseira até que a alimentação elétrica para o detector IRmax esteja isolada – ou você poderá causar a ignição em uma atmosfera inflamável. Antes de remover a porca para realizar manutenção ou calibração, verifique se o ambiente que a envolve está livre de gases ou vapores inflamáveis. Não a abra até que se passem vários minutos após a remoção da alimentação elétrica. • Operações de manutenção e calibração somente devem ser realizadas por funcionários de assistência qualificada. • Somente peças de substituição genuínas da Crowcon devem ser utilizadas. Componentes de substituição invalidarão a certificação e a garantia do detector IRmax. • Os detectores IRmax devem ser protegidos de vibrações extremas e da luz solar direta em ambientes quentes, pois isto pode fazer com que sua temperatura suba acima dos limites especificados e resulte em uma falha prematura. • O detector IRmax não detecta hidrogênio, amônia ou dióxido de carbono. • O equipamento deve ser aterrado usando um prensa cabos e cabo de aço blindado. • Certificação para ambientes com poeiras Zona 21/22: O IRmax Básico (sem os módulos IR Display e Barreira IS) pode ser usado em ambientes que podem conter poeiras perigosas (Zonas 21 ou 22). • O IRmax com um módulo Barreira IS pode ser usado em Zonas 21 ou 22 desde que a temperatura ambiente permaneça abaixo de 40°C e um IR Display Remoto ou IR Displays Portáteis estejam instalados/sejam usados somente fora da área perigosa. • O IRmax com um IR Display fixo não pode ser instalado em uma área Zona 21 ou 22. Português Brasileiro 198 Detecting Gas Saving Lives Conceito e segurança Visão geral do produto O detector IRmax é um detector de gases infravermelho projetado para detectar gases de hidrocarbonetos comuns na faixa de 0 a 100% LIE (Limite inferior de explosão: a concentração mínima no ar na qual uma ignição pode ocorrer). O detector IRmax é um detector certificado à Prova de explosão (Exd) adequado para uso em áreas de risco de Zona 1 ou 2 ATEX. Consulte o rótulo de certificação na lateral do detector IRmax para identificar o tipo de certificação que está relacionado ao produto fornecido. Observação: se não existir nenhum rótulo de certificação no detector IRmax, ele não é certificado para uso em áreas perigosas. IR GAS DE TECTOR 1180 IR GAS DETECTOR WITH REMOTE DISPLAY II 2 GD 1180 V m ax= 32V W m ax= 5W II 2GD Vmax=32V Wmax=5W B a s e e fa 0 9 A T E X 0 2 0 6 X IE C E x B A S 0 9 . 0 1 0 9 X S IL 2 S i r a 1 2 A T E X 1 2 0 6 X Baseefa09ATEX0220X IECEx BAS 09.0104X Ex db ia IIC T4 Gb (-40°C ≤ Ta ≤ +75°C) Ex tb ia IIIC T135°C Db (-40°C ≤ Ta ≤ +40°C) E x d b II C T 4 Gb (T am b = -40 °C to + 75 °C ) E x d b II C T 6 Gb (T am b = -40 °C to + 50 °C ) E x tb II IC T 135° C D b (-4 0° C T a + 75° C ) WARNING: DO NOT OPEN WHEN EXPLOSIVE ATMOSPHERE MAY BE PRESENT. W A R N IN G : D O N O T O P E N W H E N E X P L O S IV E A TM O S P H E R E M A Y B E P R E S E N T. Abingdon, United Kingdom, OX14 4SD A b i n g d o n , U nit e d K in g d o m , O X 1 4 4 S D Etiqueta de certificação do IRmax Básico Etiqueta de certificação do IRmax com Barreira IS IR GAS DETECTOR WITH DISPLAY 1180 II 2G Baseefa09ATEX0220X IECEx BAS 09.0104X Vmax=32V Wmax=5W Ex db ia IIC T4 Gb (-40°C Ta +75°C) WARNING: DO NOT OPEN WHEN EXPLOSIVE ATMOSPHERE MAY BE PRESENT. Abingdon, United Kingdom, OX14 4SD Etiqueta de certificação do IRmax com IR Display Fixo Detecting Gas Saving Lives 199 Português Brasileiro Diagrama 1: Rótulos de certificação do detector IRmax 1. Introdução 1.1 Geral A configuração de cada detector IRmax está identificada em um rótulo localizado no corpo principal. Ao entrar em contato a Crowcon para obter assistência ou peças, forneça o nome do produto, o número de peça e o número de série. 1.2 Descrição do produto O detector IRmax inclui o corpo principal de aço inoxidável 316, uma tampa antiestática à prova de intempéries no sistema óptico e na câmara de medição de gás e uma montagem eletrônica. Também é possível incluir um Módulo do IR Display. As instruções para a instalação do IR Display aparecem no manual do IR Display (M07061). Um adaptador de conexão pode ser fornecido para permitir que o detector IRmax seja encaixado diretamente na caixas de derivação auxiliares com entradas de cabo M20 ou ½” NPT. Adaptador de Conexão opcional 74.5 74,5 57 Total 60.5 158 Total 157.5 136 Total 136 Prensa cabos M20 ou 1/2" NPT Terminal de aterramento externo (TERRA) Todas as dimensões em milímetros Diagrama 2: Visualização dimensionada do detector IRmax Português Brasileiro Observação: o corpo do detector IRmax é fornecido com duas entradas de cabo: M20 e 1/2" NPT. A entrada de cabo não especificada no momento da encomenda do detector IRmax será selada com um tampão certificado. O IRmax deve ser instalado com as duas entradas de cabos vedadas: uma com um prensacabos e a outra com um tampão de proteção com certificado IP66. 200 Detecting Gas Saving Lives 1. Introdução 15 12 14 13 11 “ 10  ‘ ”  ‘ Ž    Œ Diagrama 3: Visualização expandida do detector IRmax (os números de peças estão exibidos se aplicável) Œ Adaptador de calibração M041007  Tampa a prova de intempéries M04995 Ž Fixador de espelho Fornecido junto como "kit de substituição da lente óptica" C011206  Espelho  Adaptador de fluxo S012996 ‘ Anel em "O" para a contraporca, Módulo Barreira IS ou Módulo IR Display Fixo: M040077  Suporte de montagem como conjunto completo S012130 “ Versões M20 ou 1/2" NPT de adaptador de conexão: M20 ATEX: S012147, 1/2" NPT ATEX: S012190 ” Placa de fixação e parafusos para o tampão traseiro, módulo IR Display Fixo e Barreira IS. 10 Versão fixa do IR Display 11 IR Display para conector do detector IRmax E07987 12 Módulo de barreira IS 13 Condutor de conexão do IR Display 14 Entrada ing de montagem do IR Display remoto M03833 15 IR Display Remoto Detecting Gas Saving Lives 201 Português Brasileiro } 2. Instalação AVISO • Este detector IRmax é projetado para uso em áreas perigosas Zonas 1 e 2 e a certificação irá depender dos acessórios instalados e da temperatura operacional do ambiente. Consulte a tabela de especificações na página 14 para obter os detalhes da certificação. A instalação deve estar de acordo com os padrões reconhecidos da autoridade apropriada do país em questão. • Para obter mais informações, entre em contato com a Crowcon. Antes de iniciar qualquer trabalho de instalação, certifique-se de seguir os regulamentos locais e os procedimentos da área. • O equipamento deve ser aterrado usando um prensa cabos e cabo de aço blindado. • Não tente encaixar um IR Display em um detector IRmax que não foi fornecido para este propósito. O detector IRmax fornecido para uso com um visor é certificado por Exd ia e deve ser operado com um visor fixo que contenha uma barreira IS ou com um visor Remoto ou Portátil conectado por um módulo de barreira IS da Crowcon. • Os detectores IRmax fornecidos sem um visor são certificados por Exd IIC e não podem ser retro-instalados para uso com um IR Display. 2.1 Local O detector IRmax deve ser montado onde há a maior probabilidade de presença dos gases a serem detectados. Ao escolher uma localidade para detectores de gases, observe o seguinte: • Para a detecção de gases mais leves que o ar, como o metano, os detectores devem estar montados em um nível alto. Para detectar gases mais pesados que o ar, como vapores inflamáveis, os detectores devem estar montados em um nível baixo. • Ao posicionar os detectores, considere a possibilidade de danos causados por eventos naturais, como chuvas ou inundações. Para detectores montados em áreas externas em regiões de temperaturas altas, a Crowcon recomenda o uso de um protetor solar (consulte a Seção 5, Acessórios e peças de reposição, na página 212). • Considere uma área de fácil acesso para a realização de testes funcionais e de assistência. • Considere como os gases sendo emitidos podem se comportar dependendo de correntes de ar naturais ou forçadas. Monte o detector IRmax em dutos de ventilação se for apropriado (consulte a Seção 5, Acessórios e peças de reposição, na página 212). • Considere as condições do processo. Por exemplo, o butano é geralmente mais pesado que o ar, mas se ele for liberado de um processo em uma pressão e/ou temperatura elevada, o gás pode subir em vez de descer. O posicionamento dos sensores deve ser determinado seguindo o direcionamento de profissionais com conhecimentos especialistas em dispersão de gases, no equipamento de operações da instalação e também em relação à engenharia e segurança. É recomendável registrar a decisão final a respeito do posicionamento dos sensores. Português Brasileiro 202 Detecting Gas Saving Lives 2. Instalação 2.2 Montagem O detector IRmax pode ser montado de três maneiras: 1. Com a utilização do suporte de montagem da Crowcon conectado diretamente ao cabo de campo (somente operação 4-20mA). 2. Com a utilização de um prensaestopas para conexão com uma caixa de derivação existente certificada por Exe ou Exd. A Crowcon fornece uma bucha de encaixe adequada como extra opcional (veja 3 abaixo) 3. Com a utilização de um adaptador de conexão e de uma caixa de derivação auxiliar opcional Crowcon. As partes opcionais estão listadas na Seção 5 na página 212. O detector IRmax deve ser instalado na localidade designada com o tambor do sensor em posição horizontal +/- 15° (demonstrada no Diagrama 2 da página 200). Isto garantirá que poeira ou água não se acumulem nos componentes ópticos. 2.3 Conexão de cabos diretamente ao detector IRmax Esta opção está disponível somente para a operação 4-20mA. É necessário ter um suporte de montagem da Crowcon para instalar o detector em uma parede ou em um tubo de 2” (50 mm). LED de status Sinal 0V (terra) +V (24V IRmax) Diagrama 4: Conexões dos cabos de campo do IRmax Conecte aos cabos de campo utilizando uma prensa certificada na entrada de cabo escolhida do corpo do detector IRmax (M20 ou 1/2" NPT). A Crowcon recomenda instalar o prensa cabos apontando para baixo. 15mm MAX Detecting Gas Saving Lives 203 Português Brasileiro Certifique-se de usar prensa cabos com a certificação Exd apropriada e que o comprimento da rosca não exceda o especificado no diagrama (esquerda). 2. Instalação 2.3.1 Designação de terminal Com o IRmax posicionado conforme demonstrado no Diagrama 2 na página 200 (entrada do cabo M20 no topo), o cabo de campo de 3 núcleos da instalação deve ser conectado ao terminal com uso de um conector removível conforme o seguinte: +24 V na parte inferior, 0V no meio, Sinal na parte superior. O conector de 6 pinos à direita da PCI é destinado para manutenção e/ou conexão de um módulo do IR Display Terminal +ve: fornecimento de +ve do cartão de controle. Terminal Sig: Sinal do cartão de controle. Terminal 0 V: fornecimento de -ve do cartão de controle. 2.3.2 Como instalar o detector IRmax utilizando um suporte de montagem a. O IRmax pode ser fornecido com um suporte de montagem (S012130), em vez de um prensaestopas, para que ele possa ser conectado diretamente aos cabos de campo (consulte o Diagrama 5). Suporte de montagem: 70 mm entre os centros de fixação. Use parafusos M6. Diagrama 5: Detector IRmax com um suporte de montagem e um prensa cabos b. Se o detector IRmax estiver sendo montado em uma superfície plana, marque e faça os dois furos com o uso do suporte para montagem como modelo. Encaixe levemente as duas partes do suporte utilizando acessórios adequados para parede/superfície. Português Brasileiro c. Remova a tampa à prova de intempéries do IRmax e deslize o corpo do IRmax pelo suporte. É recomendável que o corpo do detector IRmax esteja instalado com a entrada do cabo apontando para baixo. 204 Detecting Gas Saving Lives 2. Instalação d. Aperte os dois acessórios do suporte para que detector IRmax fique firmemente seguro no local. Encaixe a tampa à prova de intempéries de volta. e. Depois de posicionar o detector IRmax de forma segura no local, remova a sua porca traseira para permitir acesso aos terminais dos cabos. f. Prepare o cabo: a Crowcon recomenda o cabo de fio de aço blindado (SWA) de 1,5 mm2. Outros tipos de cabos podem ser usados se forem compatíveis com os adaptadores certificados por Exd. Encaixe um prensa cabos adequado e certificado por Exd, passe os condutores do cabo pelo corpo do detector IRmax e parafuse-o no prensa cabos. Encaixe a prensa e verifique se a proteção do cabo está aterrada ao prensa cabos e ao corpo do detector IRmax. Nota: não se esqueça de encaixar a porca traseira de volta após instalar o cabo. g. A placa de fixação (item 9 no Diagrama 3, na página 201) deve ser montada firmemente para evitar qualquer risco de a porca traseira (ou o acessório do módulo IR Display Fixo ou Barreira IS) ficar frouxa com a vibração. 2.4 Como instalar usando um adaptador de conexão e uma caixa de derivação auxiliar Diagrama 6: Detector IRmax conectado a uma caixa de derivação auxiliar Detecting Gas Saving Lives 205 Português Brasileiro Será necessário usar esta opção ao conectar o detector IRmax a uma caixa de derivação auxiliar existente certificada por Exd ou Exe. 2. Instalação 2.4.1 Para encaixar o detector IRmax em uma caixa de derivação auxiliar: a. Remova cuidadosamente a seção exterior do adaptador de conexão (item 8 no Diagrama 3 na página 201). b. Parafuse a extremidade estreita do adaptador de conexão na caixa de derivação auxiliar. c. Levante o detector IRmax para a caixa de derivação auxiliar e passe os fios pela montagem e para dentro da caixa. Fixe o detector IRmax parafusando o anel firmemente ao prensa cabos. Aperte o parafuso sem cabeça. d. O corpo principal do detector IRmax pode ser virado horizontalmente em qualquer ângulo desde que esteja mecanicamente seguro, não interfira com outro equipamento e que seja acessível para manutenção. e. Consulte a Seção 2.6 para obter instruções sobre o cabeamento. Consulte também o Diagrama 4 (página 203). 2.5 Requisitos de cabeamento A conexão de cabos ao detector IRmax deve estar de acordo com os padrões reconhecidos da autoridade apropriada do país em questão e deve atender aos requisitos elétricos do detector IRmax. A Crowcon recomenda o uso de cabo de fio de aço blindado (SWA) além do uso de prensas apropriadas à prova de explosões. Técnicas de cabeamento alternativas, como condutos de aço, são aceitáveis com a condição que elas atendam aos padrões adequados. O comprimento máximo de cabo recomendável é de 3,4 km (veja a Tabela 1). O detector IRmax requer uma alimentação dc de 12 - 30 Vdc. Verifique se há um mínimo de 12 V no detector IRmax do painel de controle, levando em consideração uma queda de tensão devido à resistência do cabo em uma corrente pico de 0,1 A. Um cabo de 1,5 mm2 geralmente permitirá execuções de cabo de até 3,0 km. A tabela 1 abaixo demonstra as distâncias máximas para os parâmetros típicos de cabos. C.S.A. Resistência Distância máx. >20 V Distância máx. 18 a 20 V mm2 (Ohms por km) (km) (km) 1,0 18,4 2,2 1,6 1,5 13,0 3,0 2,3 2,5 11,5 3,4 2,6 Tabela 1: distâncias máximas para cabos típicos Português Brasileiro 206 Detecting Gas Saving Lives 2. Instalação 2.6 Conexões e configurações Todas as conexões descritas possuem referência ao bloco terminal montado no corpo principal do conector do detector IRmax. Os terminais no conector do detector IRmax da PCI estão marcados com ‘+’, ‘sig’ e ‘0 V’. Verifique a polaridade correta ao conectar o detector IRmax ao equipamento de controle. O detector IRmax está configurado por fábrica como um dispositivo ‘dreno de corrente’, a menos que seja especificado de outra forma no momento da encomenda. Para redefinir como ‘fonte de corrente’, remova a placa traseira e mova as duas conexões no terminal da PCI da posição ‘dreno’ para a ‘fonte’, conforme mostrado no Diagrama 7. Observação: O terminal de aterramento externo somente deve ser usado quando as autoridades locais permitirem ou solicitarem este tipo de conexão. Quando possível, para limitar a interferência de frequência de rádio, a caixa de derivação auxiliar e a blindagem de cabo devem ser aterradas no painel de controle (área segura) somente para evitar loop de terra. +V 0V Sg 1 2 3 Controlador CONTROLLER Configurações de conector EARTH Cabeamento Número Cor 1 2 3 dreno Função Vermelho +V Preto 0V Verde Sinal Conector do kit de comunicações com PC fonte Conector do IR Display LED de status Diagrama 7: Localidade de conector de dreno/fonte Indicação LED: Uma LED está incluída no terminal da PCI para indicar o status de operação atual. Consulte a Seção 6 na página 213 para obter mais informações. Detecting Gas Saving Lives 207 Português Brasileiro O sinal 4-20 mA pode ser definido como corrente 'Dreno' ou 'Fonte' com o uso dos pinos e do conector mostrado no Diagrama 7. Defina como "Carga" de corrente instalando o conector nos pinos 3 e 4 como está ilustrado na fotografia à esquerda. Defina como "Fonte" de corrente instalando o conector nos pinos 1 e 2 como está ilustrado na fotografia à direita. Os detectores IRmax estarão definidos como corrente 'Dreno' a não ser que tenha sido especificado ao contrário no momento da encomenda. 3. Operação AVISO Antes de executar qualquer trabalho, certifique-se de seguir os regulamentos locais e os procedimentos da área. Nunca tente abrir o detector IRmax ou a caixa de derivação auxiliar quando algum gás inflamável estiver presente. Verifique se o controle de painel associado está inibido para que alarmes falsos sejam evitados. 3.1 Procedimento de preparação 1. Verifique: a. Se as conexões de cabo estão corretas b. Se a alimentação de tensão está definida no cartão de controle como de 18 a 30 V. A tensão medida nos terminais do detector IRmax (na caixa de derivação auxiliar Exe, se usada, ou na PCI do terminal do detector IRmax) deve estar definida entre 12 e 30 V. c. Se as conexões estão definidas para dreno ou fonte 4-20 mA, conforme apropriado ao cartão de controle. 2. Depois o acionar, aguarde 30 minutos antes de tentar zerar/cal. Este atraso existe para garantir a estabilidade térmica. (Observação: O detector IRmax estará completamente operacional depois de 30 segundos de sua ativação.) 3. Certifique-se de que somente exista ar limpo (por exemplo, sem gases de hidrocarbonetos) antes de zerar. Leitura Zero no cartão de controle (consulte as instruções do cartão de controle). 4. Encaixe o adaptador de calibração na tampa à prova de intempéries para isolar a câmara de medidas do ar ambiente. Esse tipo de cobertura está disponível pela Crowcon (M041007). Conecte o gás de calibração (50% de LIE nom) e aplique em uma vazão de 1 litro por minuto. 5. Após 30 segundos, ajuste cal./span no cartão de controle para que o visor leia 50% LIE ou se corresponda à concentração do gás de calibração aplicado. O detector IRmax não requer calibração. 6. Remover o adaptador de calibração e o gás. Realize o zero novamente. 7. Na instalação, ou após a alteração do espelho, o detector IRmax pode ser zerado e calibrado usando um acessório IR Display (consulte a página 197) ou por um Kit de Comunicações para PC (consulte o Manual Acessórios da IRmax ). Observação: Detectores IRmax certificados por ATEX serão fornecidos calibrados em conformidade ao EN61779 (onde, por exemplo, 100% LIE Metano = 4,4% de volume). Observação: é recomendável usar o adaptador de calibração para a preparação inicial. As calibrações subsequentes podem ser conduzidas aplicando gás na tampa à prova de intempéries remotamente pela ponta do tubo (evitando assim a necessidade de acessar diretamente o detector IRmax). Uma calibração sem o adaptador de calibração (por exemplo, diretamente pela tampa à prova de intempéries) pode ser executada desde que a velocidade do vento local esteja abaixo de 2 metros/segundo. A vazão do gás deve ser superior a 2,0 litros/minuto. Português Brasileiro 208 Detecting Gas Saving Lives 3. Operação 3.2 Manutenção de rotina As práticas locais determinarão com qual frequência o detector IRmax deve ser testado. A Crowcon recomenda testar o IRmax a gás pelo menos a cada 6 meses e recalibrar conforme necessário. Para recalibrar um detector IRmax, siga as etapas fornecidas na Seção 3.1. No caso de uma falha eletrônica, entre em contato com o seu representante local da Crowcon. Intervalo de tempo para calibração: A Crowcon recomenda a calibração a cada 12 meses. Calibração remota pela tubulação: Wind speed should be less than 2.0 metres per second. If greater, use the calibration cap to prevent gas dilution. Limpeza dos ópticos: Não é recomendável a menos que o detector IRmax tenha uma falha de obscurecimento. Se a janela ou a lente óptica ficarem contaminadas, limpe cuidadosamente com lenços impregnados IPA e/ou com o pano macio fornecido no kit de limpeza da lente óptica (consulte a Seção 5, Acessórios e peças de reposição na página 212). Espelhos:  Se a lente óptica estiver danificada, obtenha um kit de substituição da lente óptica (consulte a Seção 5, Acessórios e peças de reposição na página 212). O detector IRmax deve sempre ser zerado e calibrado novamente após uma substituição de espelho. Se condensação começar a causar falhas, substitua o espelho (a cobertura óptica pode estar danificada). A Crowcon recomenda substituir o espelho a cada 5 anos. 3.3 Como alterar tipos de gás Detecting Gas Saving Lives 209 Português Brasileiro Cada detector IRmax é fornecido pré-calibrado para um tipo de gás em particular (por exemplo, metano ou propano). Se for necessário recalibrar para um tipo de gás diferente, o IRmax pode ser reconfigurado usando o kit de comunicações para PC (consulte a Seção 5, Acessórios e peças de reposição na página 212), e depois calibrado. 3. Operação 3.4 Respostas relativas de tipos de gás O gráfico abaixo demonstra as respostas relativas a outros tipos de gases para um detector IRmax calibrado para metano. Nota: muitos gases e vapores de hidrocarbonetos são detectados com mais facilidade do que o metano pelos detectores infravermelhos. A resposta do IRmax (e de outros detectores de gases infravermelhos) será linear em todo intervalo de 0-100% LIE para o gás alvo (isto é, metano neste exemplo), mas não linear para outros gases de hidrocarbonetos que também possam estar presentes. Diagrama 8 O diagrama mostra a resposta dos gases mencionados acima: da esquerda para a direita, etano, propano, butano, pentano e metano. Outros tipos e variações de gases estão disponíveis. Entre em contato com a Crowcon para obter mais detalhes. Português Brasileiro 210 Detecting Gas Saving Lives Material do Invólucro Aço inoxidável 316 Dimensões (somente detector IRmax) 150 mm x 75 mm x 66 mm (sem bocal) Peso IRmax 1,58kg (3,5 lbs) IRmax com IR Display Fixo 2 kg (4,4 lbs) IRmax com Módulo de Barreira IS 2,4 kg (5,3 lbs) IR Display Remoto 0,2 kg (0,4 lbs) Tensão de operação de 12 Vdc a 30 V dc Alimentação <1W Saída 3 fios 4 - 20 mA (Dreno ou Fonte) Sinal de falha <1 mA Resistência de loop máxima de cabo 80 Ohms (relativo ao terminal negativo) Temperatura operacional de -40°C a +75°C (-40°F a +167°F) Umidade 0 – 100% de umidade relativa Grau de proteção IP66 Proteção contra explosão À prova de explosão Código de aprovação ATEX & IECEx Versão sem display Ex II 2 GD Ex db IIC T6 Gb (Tamb -40°C ≤ a ≤ +50°C) Ex II 2 GD Ex db IIC T4 Gb (Tamb -40°C ≤ a ≤ +75°C) Ex II 2 GD Ex tb IIIC T135°C Db (Tamb -40°C ≤ a ≤ +75°C) Versão com IS Barrier module Ex II 2 G Ex db ia IIC T4 Gb (Tamb -40°C ≤ a ≤ +75°C) Ex II 2 GD Ex tb IIIC T135°C Db (Tamb -40°C ≤ Ta ≤ +40°C) Versão com display Ex II 2 GD Ex db ia IIC T4 Gb (Tamb -40°C ≤ a ≤ +75°C) Nº de certificado de segurança ATEX e IECEx IRmax (sem IR Display): Baseefa 09ATEX0206X and IECEx BAS.09.0109X IRmax (com IR Display): Baseefa 09ATEX0220X and IECEx BAS.09.0104X Segurança funcional Certificado para uso num sistema SIL 2. Número do certificado: Sira 12ATEX1206X Padrões EN 60079-0:2012+A11:2013, EN 60079-1:2014, EN 60079-31:2014 IEC 60079-0:2011, IEC 60079-1:2014, IEC 60079-31:2013 EN 60079-29-1:2007, IEC 61508:2010, EN50402:2005 Zonas Certificado para uso em Zona 1 ou Zona 2 EMC EN50270 Detecting Gas Saving Lives 211 Português Brasileiro 4. Especificações 5. Acessórios e peças de reposição Código Nome Descrição M041007 Adaptador de calibração Encaixa no detector para permitir a calibração quando a velocidade do vento local for superior a 2 metros por segundo. S012130 Kit suporte de montagem Permite montagem em uma parede ou tubo de 2" (50 mm). Não é necessário se o detector IRmax já tiver uma caixa de junção existente instalada. S012152 Cone coletor/protetor solar Pode ser instalado no detector IRmax para proteção contra temperaturas elevadas devido luz direta do sol e/ ou aumentar a área de cobertura dos detectores para que gases mais leves que o ar sejam detectados (metano). S012169 Kit de montagem de duto Permite a monitoração de dutos de 300 mm a 3000 mm e fluxo de ar entre 2 m/s e 20 m/s. S012996 Adaptador de fluxo Para aplicativos de amostragem de gás. S012827 Kit de Comunicações para PC Módulo de comunicações, software e conector que permitem a configuração do detector IRmax. M20: S012295 ½” NPT: S012296 Auxiliary junction box Opção de montagem do IRmax para uso em ambientes perigosos. C011210 Kit de limpeza de espelho Contém limpadores com álcool isopropílico (IPA) e tecido de microfibra Peças do detector IRmax Consulte o Diagrama 3 na página 201 para detalhes a respeito das peças de reposição. Português Brasileiro 212 Detecting Gas Saving Lives 6. Como localizar falhas 6.1 Erros indicados pela LED A LED instalada no terminal PCB pode ajudar a identificar falhas. A sua posição está demonstrada no Diagrama 7 na página 207. A tabela abaixo mostra como interpretar o que há de errado em cada padrão de piscadas. Padrão de LED Status do detector IRmax Piscadas regulares a cada segundo. Saudável. Ligada com períodos curtos Detector IRmax sem iluminação. no modo de inicialização. Ação Aguarde 10 segundos. Padrão de piscadas irregulares ou luz ativada e desativada. Tensão de Verifique se a tensão de alimentação alimentação baixa do detector IRmax está definida ou alta demais. corretamente. Verifique se a medição foi realizada diretamente dos terminais do detector IRmax. Sempre ligada. Falha, erro de host ou i-módulo. Realize um ciclo de energia no detector IRmax. Se o problema continuar, retorne-o à Crowcon. Duas longas piscadas seguidas por uma piscada curta. Erro fatal; falha da lâmpada ou do detector IRmax. Retornar à Crowcon ou Representante. Piscada dupla rápida a cada Erro fatal; falha segundo. de configuração ou módulo. Verifique as configurações do detector IRmax usando o software para Kit de Comunicações para PC. Verifique a alimentação elétrica. Se o problema continuar, devolva-o à Crowcon. Luz apaga rapidamente a cada segundo. Verifique a janela e o espelho, limpe-os se necessário. Zere o detector IRmax novamente e verifique a calibração. Os ópticos foram obstruídos. Quaisquer outras falhas somente poderão ser reparadas perante a devolução do detector IRmax à Crowcon ou a um agente de serviços autorizados. O IRmax permanecerá em estado de Defeito e aparecerá "Manutenção necessária" (Service required) no IR Display (se instalado) se o sinal analógico de saída tiver falhado ou se não estiver conectado a um sistema de controle ou resistência de carga. O IRmax monitora ativamente o sinal analógico de saída de 4-20 mA para verificar se está dentro da faixa. Se o sinal estiver fora da faixa, o detector passa ao estado de defeito e a saída é definida para 1 mA. Assim, ao testar um detector, é imprescindível que ele esteja conectado a um painel de controle ou que uma resistência de carga de 100 Ω esteja conectada entre os terminais de "0 V" e "Sig" (detector definido no modo "Fonte") ou entre os terminais de "0 V" e "Pos" (detector definido no modo "Carga"). Detecting Gas Saving Lives 213 Português Brasileiro 6.2 Saída Analógica 7. Configuração do Modbus RS485 7.1 Geral Esta seção explica como usar os detectores IRmax em uma configuração Modbus. Uma versão ativada RS485 está disponível para estes aplicativos. Até 28 detectores IRmax podem ser vinculados nas configurações de estrela ou de barramento, conforme descrito abaixo. As conexões para a versão RS485 do detector IRmax devem ser feitas por um adaptador de conexão para uma caixa de junção (consulte a Seção 5 na página 200), em vez de ser cabeada diretamente no detector IRmax. Observe que o IR Display não pode ser usado com um IRmax ativado com RS485. A versão ativada por RS-485 do detector IRmax possui cinco terminais de campo. Os terminais são: 1 Alimentação positiva 12 V a 30 V acima de 0 V 2 0V Retorno e referência RS485 3 4-20 mA sinal Sinal fonte ou dreno (opcional) 4 RS485 B Sinal diferencial RS485 5 RS485 A Sinal diferencial RS485 Os sinais nos terminais RS485 estão em conformidade com o padrão EIA/TIA-485, o que significa que o intervalo de modo comum é de -7V a +12V em relação ao terminal 0V. Observe que nem todos os fabricantes de RS485 concordam com a polaridade dos sinais A e B. Se o cabeamento não funcionar de alguma forma, os usuários devem alternar os fios A&B do RS485. Não há nenhum risco se uma conexão errada for realizada. As configurações de comunicação são de 9600 bps, dois bits de parada e nenhuma paridade. Ao compilar uma interface para um sistema de controle, é importante considerar a quantidade de tempo que o sistema leva para coletar informações de cada detector por vez. A velocidade mais rápida, na qual vários detectores podem ser reunidos, é de 14 detectores por segundo, mas condições práticas podem reduzir isto para 7 por segundo. Os usuários devem se certificar de que o ajuste permita que sinais de alarme sejam registrados dentro de limites de tempo aceitáveis. Também é importante certificar-se de que o sistema seja capaz de fornecer energia suficiente para manter todos os detectores em funcionamento. Para calcular a quantidade de energia necessária em uma conexão de barramento linear, consulte Seção 7.3, Requisitos de cabeamento, na página 216. Para obter instruções completas sobre Modbus, entre em contato com a Crowcon (endereços localizados na capa traseira). Português Brasileiro 214 Detecting Gas Saving Lives 7. Configuração do Modbus RS485 7.2 Topologias de cabeamento As duas topologias comuns de cabeamento em uso são a conexão estrela e o barramento linear. 7.2.1 Conexão estrela Em uma topologia conectada por estrela, todos os detectores IRmax estão conectados por fios em um ponto central, que geralmente é o painel de controle. Nenhum dos cabos são requeridos a ter mais de 5 núcleos e todas as conexões de sinal 4-20 mA são direcionadas diretamente para o painel de controle. Os sinais RS485 A e B podem então ser conectados todos juntos em um ponto de estrela. O barramento pode então ser encerrado no ponto de estrela com um único resistor de terminação de 110 ohm. O comprimento de cada braço da estrela não pode exceder 750 metros. 7.2.2 Conexão de barramento linear IEm uma topologia conectada por barramento, todos os detectores IRmax estão cabeados por fio a um ajuste linear, geralmente com o painel de controle em uma extremidade. Uma situação clássica seria uma instalação de túnel, com os detectores IRmax instalados em intervalos regulares (consulte o Diagrama 9 abaixo). Para fazer as ligações da instalação, devem ser montados dois resistores de terminação de 110 ohm: um em cada extremidade física do barramento. Como os sinais 4-20mA não podem ser compartilhados, um condutor adicional é necessário em cada salto de cabeamento. Se nenhum dos sinais 4-20 mA estão sendo usados, somente quatro condutores serão necessários. DIAGRAMA DE CONEXÃO DE BARRAMENTO LINEAR PARA O PAINEL DE CONTROLE Detecting Gas Saving Lives 215 Português Brasileiro Diagrama 9 7. Configuração do Modbus RS485 7.3 Requisitos de cabeamento 7.3.1 Como calcular o nível mínimo de energia necessária Quanto mais detectores IRmax estiverem conectados ao barramento linear, uma maior quantidade de energia será necessária para executar o sistema. Para calcular a energia necessária para uma configuração em particular, é necessário saber a resistência do cabo entre cada par de detectores IRmax. Uma corrente de pelo menos 0,1 mA deve ser permitida para cada ‘salto’ entre os detectores IRmax. A tensão a ser aplicada pode ser calculada estimando a queda de tensão em cada ‘salto’ – no final, pelo menos 12 V devem permanecer para garantir que o último detector IRmax funcione corretamente. Entre em contato com a Crowcon para obter assistência sobre casos específicos. Como alternativa, siga as etapas descritas abaixo e o cálculo de amostra mostrado na próxima seção. 1. A tensão não deve cair abaixo de 12 V, logo comece o cálculo definindo a tensão no último detector IRmax da linha na válvula. 2. Cada detector IRmax pode chegar a 0,1 A. Calcule a perda de tensão do cabo do primeiro ‘salto’ entre os detectores assumindo a ‘corrente agregada’ como 0,1 A e multiplique isto pela resistência de cabo do ‘salto’ entre o último e o "último menos um” detector IRmax. 3. Adicione esta queda de tensão ao 12 V inicial para obter a tensão mínima aceitável no último e único detector IRmax. Adicione 0,1 A ao valor para a ‘corrente agregada’ para obter 0,2 mA, a corrente mínima correndo através do último, porém único, ‘salto’ do barramento. Multiplique isto pela resistência do cabo para o último, porém único ‘salto’ para obter a próxima queda de tensão. 4. Repita este processo para cada detector IRmax, acumulando as perdas de tensão que irão ocorrer entre cada detector IRmax. 5. A tensão do detector IRmax máxima de 30 V não deve ser excedida. 7.3.2 Cálculo de amostra Como exemplo, em seguida estão os resultados de cálculos de seis detectores IRmax espaçados igualmente 250 m uns dos outros no cabo com uma área de seção transversal de 1 mm2. Cada salto possui uma resistência de 4,6 ohms. Estação Tensão de alimentação Corrente de alimentação 1 12 0,1 A 2 12,46 0,2 A 3 13,38 0,3 A 4 14,76 0,4 A 5 16,6 0,5 A 6 18,9 0,6 A Alimentação de painel 21,66 0,6 A Português Brasileiro 216 Detecting Gas Saving Lives 8. Manual de Segurança Funcional 8.1 Introdução As seções a seguir fornecem detalhes sobre a certificação do IRmax de acordo com as normas de Segurança Funcional IEC 61508 e EN 50402. São dadas informações sobre as características consideradas no caso de segurança, requisitos de manutenção e dados para permitir que o IRmax seja integrado no Sistema de Instrumentos de Segurança (SIS). 8.2 Função de Segurança do IRmax e do Modbus do IRmax Para medir a concentração de gás inflamável e indicar a medida por meio de uma saída de 4-20 mA. Falhas relativas à função de segurança serão detectadas pelo hardware e firmware associado. Elas serão reveladas como uma saída de menos de 3,6 mA ou mais de 21 mA. 8.3 Dados de Segurança Funcional Nome do parâmetro Símbolo Equação / Fonte Intervalo de Teste de Prova T1 Conforme definição da Crowcon. Tempo médio para reparar MTTR Tipo A/B Tipo A λ Conforme definição da Crowcon. Tipo B Total de falhas: Da FMEDA 1.04E-05 Falhas seguras diagnosticadas: λSD Da FMEDA 1.95E-08 Falhas seguras não diagnosticadas: λSU Da FMEDA 8.59E-08 Falhas perigosas diagnosticadas: λDD Da FMEDA 9.74E-06 Falhas perigosas não diagnosticadas: λDU Da FMEDA 5.06E-07 Falhas seguras sem efeito: λNE Da FMEDA 3.21E-09 Cobertura de diagnóstico: DC λDD / (λDU + λDD) 95.06% Fração de falhas seguras: Tempo de paralisação equivalente do canal PFDAVG (usando a equação 61508-6) PFDAVG (usando equação simplificada) PFDAVG (usando a equação IEC 61508-6) Capacidade SIL (modo baixa demanda) Capacidade SIL (modo alta demanda) SFF (λSD + λSU + λDD) / λ (λDU / λD)(T/2 + MTTR) + (λDD / λD ) MTTR 95.11% PFDAVG (λDU + λDD) tCE 2.30E-03 PFDAVG λDU (T / 2+MTTR) + (λDD MTTR) 2.30E-03 PFDAVG 1-ε-(λdd+λdu) tce 8.760 horas (anuais) Conforme definição da Crowcon. 8 horas 2.24E+02 2.30E-03 SIL2 SIL2 Para aplicações de baixa demanda, com respeito a falhas aleatórias de hardware e fração de falha segura, todas as versões do sistema são adequadas para uso em aplicações SIL 2. Detecting Gas Saving Lives 217 Português Brasileiro tCE IRmax Manual de Segurança Funcional 8.4 Configuração do Hardware A Rota 1H (tolerância de falha de hardware e fração de falha segura) foi usada para avaliar o nível de integridade de segurança do hardware. 8.5 Configuração do Software A avaliação do firmware do produto foi feita de acordo com os requisitos da norma IEC 61508:3 2010. 8.6 Falhas Sistemáticas A Rota 1S (conforme especificação na IEC 61508:2 2010 parágrafo 7.4.2.2c) é usada para conformidade com os requisitos de evitar falhas sistemáticas. 8.7 Intervalo de Diagnóstico A maioria das funções de diagnóstico são monitoradas continuamente. Testes do watchdog do sistema devem ser realizados durante o teste de prova anual desligando e religando o instrumento: O IRmax deve ser desligado e religado anualmente (isto é, a fonte de alimentação de 24 VCC deve ser removida e reaplicada) como parte do programa de manutenção do produto (consulte também a seção 3.2). 8.8 Restrições As taxas de falha são constantes. Um teste de prova realizado pelo menos uma vez por ano identificará todas as falhas não reveladas. Os reparos têm um tempo médio de duração de 8 horas. Supõe-se que o usuário utiliza a função de diagnóstico fornecida através do acessório IR Display e/ ou da interface para PC, a fim de minimizar possível tempo de paralisação do produto. A avaliação de confiabilidade é um processo estatístico para aplicar dados de falha históricos a desenhos e configurações propostos. Portanto, proporciona uma meta/estimativa verossímil da provável confiabilidade do equipamento, supondo-se que a fabricação, desenho e condições operacionais sejam idênticas àquelas sob as quais os dados foram coletados. É uma técnica de revisão de desenho importante para comparar desenhos alternativos, estabelecendo metas de desempenho em ordem de grandeza e avaliando os efeitos potenciais de mudanças no desenho. No entanto, os valores previstos reais não podem ser garantidos como previsão do número preciso de falhas em campo que realmente ocorrerão, já que isto depende de muitos fatores fora do controle do exercício de previsão. Supõe-se que as taxas de falha (símbolo λ), para os fins desta previsão, são constantes no tempo. Falhas precoces ou relacionadas com o desgaste reduziriam a confiabilidade, mas supõe-se que sejam removidas por queima e substituição preventiva respectivamente. Português Brasileiro 218 Detecting Gas Saving Lives Manual de Segurança Funcional A probabilidade de falha sob demanda é a probabilidade de que o sistema estará em um estado de falha num momento aleatório. Isto é sinônimo de uma indisponibilidade estável que é dada por: Indisponibilidade = = (λ x TMP)/(1 + (λ x TMP)) que se aproxima a λ x TMP para pequenos valores de λ x TMP onde λ é a taxa de falhas e TMP é o Tempo Médio de Paralisação. Isto é consistente com a expressão de disponibilidade dada como: MTBF/(MTBF+TMP) As taxas de falhas usadas, e assim as disponibilidades derivadas, são as plausivelmente associadas a um desenho bem comprovado após um período adequado de crescimento de confiabilidade. 8.9 Meio ambiente Restrições ambientais: O produto deve ser operado a uma gama de temperatura ambiente máxima de -40°C a +75°C. O produto deve ser armazenado a uma gama de temperatura ambiente máxima de -40°C a +80°C. O produto deve ser operado a uma gama de umidade relativa ambiente máxima de 0% a +100% com condensação. O produto tem um Índice de Proteção contra Líquidos e Poeira IP66 de acordo com as definições da norma EN60529. O produto é projetado para operação contínua. 8.10 Tolerância de Falha de Hardware (TFH) A TFH é 0. 8.11 Capacidade do Sistema O IREX/IRmax é da Classe SC2. 8.12 Classificação Detecting Gas Saving Lives 219 Português Brasileiro O IREX/IRmax é um componente tipo B. Garantia Este equipamento sai da fábrica completamente testado e calibrado. Se, dentro do período de garantia de três anos da entrega, for provado que o equipamento se encontrava defeituoso devido a falhas na fabricação ou material, nós garantimos o seu conserto ou substituição gratuita de acordo com as condições abaixo. Procedimento de garantia Para facilitar um processamento eficaz de qualquer solicitação, entre em contato com a nossa equipe de assistência ao cliente pelo número +44 (0)1235 557711 com as seguintes informações: O seu nome, número de contato, número de fax e endereço de email. A descrição e a quantidade dos produtos que estão sendo retornados, incluindo quaisquer acessórios. Número(s) de série do instrumento. Motivo de devolução. Obtenha um formulário de devoluções para motivos de identificação e rastreamento. Este formulário pode ser baixado de nosso site da web ‘crowconsupport.com’, juntamente de uma etiqueta para devolução. Como alternativa, nós podemos enviar uma cópia por e-mail para você. O detector IRmax não será aceito para garantia sem um número de devolução da Crowcon (CRN). É essencial que a etiqueta com o endereço esteja anexada de forma segura na parte externa do pacote dos produtos retornados. A garantia será invalidada se o for descoberto que o produto foi alterado, desmontado ou violado. A garantia não cobre mau uso ou abuso da unidade. Aviso de isenção de responsabilidade da garantia A Crowcon não aceita nenhuma responsabilidade pela perda indireta ou consequencial ou por danos de qualquer forma provenientes (incluindo quaisquer perdas ou danos provenientes do uso do produto) e toda a responsabilidade relacionada a quaisquer terceiros está particularmente excluída. Esta garantia não cobre a precisão da calibração da unidade ou o acabamento final do produto. A unidade deve ser mantida de acordo com as instruções de operação e manutenção. A garantia das peças consumíveis de substituição (como o espelho), fornecidas com a garantia da substituição de itens defeituosos, será limitada à data de validade da garantia do produto originalmente fornecido. A Crowcon se reserva ao direito de determinar um período de garantia inferior, ou declinar um período de garantia, para qualquer um dos sensores fornecidos utilizados em um ambiente, ou para um aplicativo, conhecido por produzir riscos de degradação ou danos ao sensor. Português Brasileiro A nossa responsabilidade em relação a um equipamento defeituoso será limitada às obrigações descritas e quaisquer garantias estendidas, condição ou instrução, estatuárias implícitas ou expressas, ou diferentes das qualidades comerciáveis de nosso equipamento ou de seu desempenho para qualquer propósito em particular é excluída exceto à medida que proibida pelo estatuto. Esta garantia não afetará os direitos estatuários do cliente. 220 Detecting Gas Saving Lives Garantia A Crowcon se reserva ao direito de cobrar uma taxa de manuseio e transporte quando descobrir que unidades retornadas como defeituosas somente necessitavam calibração ou assistência rotineira, as quais não foram desempenhadas pelo cliente. No caso de dúvidas a respeito da garantia ou da assistência técnica, entre em contato: Assistência ao cliente Tel: +44 (0) 1235 557711 Fax: +44 (0) 1235 557722 Detecting Gas Saving Lives 221 Português Brasileiro Email: [email protected] UK Office Crowcon Detection Instruments Ltd 172 Brook Drive, Milton Park, Abingdon Oxfordshire OX14 4SD Tel: +44 (0)1235 557700 Fax: +44 (0)1235 557749 Email: [email protected] Netherlands Office Crowcon Detection Instruments Ltd Vlambloem 129 3068JG, Rotterdam Netherlands Tel: +31 10 421 1232 Fax: +31 10 421 0542 Email: [email protected] USA Office Crowcon Detection Instruments Ltd 1455 Jamike Ave. Suite 100 Erlanger KY 41018 Tel: +1 859 957 1039 or +1 800 527 6926 Fax: +1 859 957 1044 Email: [email protected] Singapore Office Crowcon Detection Instruments Ltd Block 194, Pandan Loop #06-20 Pantech Industrial Complex Singapore 128383 Tel: +65 6745 2936 Fax: +65 6745 0467 Email: [email protected] China Office Crowcon Detection Instruments Ltd (Beijing) Unit 316, Area 1, Tower B, Chuangxin Building, 12 Hongda North Road, Beijing Economic & Technological Development Area, Beijing, China 100176 Tel: +86 10 6787 0335 Fax: +86 10 6787 4879 Email: [email protected] Web site: www.crowcon.com
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163
  • Page 164 164
  • Page 165 165
  • Page 166 166
  • Page 167 167
  • Page 168 168
  • Page 169 169
  • Page 170 170
  • Page 171 171
  • Page 172 172
  • Page 173 173
  • Page 174 174
  • Page 175 175
  • Page 176 176
  • Page 177 177
  • Page 178 178
  • Page 179 179
  • Page 180 180
  • Page 181 181
  • Page 182 182
  • Page 183 183
  • Page 184 184
  • Page 185 185
  • Page 186 186
  • Page 187 187
  • Page 188 188
  • Page 189 189
  • Page 190 190
  • Page 191 191
  • Page 192 192
  • Page 193 193
  • Page 194 194
  • Page 195 195
  • Page 196 196
  • Page 197 197
  • Page 198 198
  • Page 199 199
  • Page 200 200
  • Page 201 201
  • Page 202 202
  • Page 203 203
  • Page 204 204
  • Page 205 205
  • Page 206 206
  • Page 207 207
  • Page 208 208
  • Page 209 209
  • Page 210 210
  • Page 211 211
  • Page 212 212
  • Page 213 213
  • Page 214 214
  • Page 215 215
  • Page 216 216
  • Page 217 217
  • Page 218 218
  • Page 219 219
  • Page 220 220
  • Page 221 221
  • Page 222 222
  • Page 223 223
  • Page 224 224
  • Page 225 225
  • Page 226 226
  • Page 227 227
  • Page 228 228

Crowcon IRmax Installation, Operating And Maintenance Instruction

Tipo
Installation, Operating And Maintenance Instruction

en otros idiomas