Installation Instructions
SLC
®
500 Programmable Controller Isolated
Link Coupler
(Catalog Number 1747-AIC)
Installing the DH-485
Communication Cable
Publication 1747-UM011, SLC 500 Modular Hardware Style User
Manual, contains complete instructions and guidelines for DH-485
link planning.
Powering the Link Coupler
In normal operation with the programmable controller connected to
the link coupler, the processor powers both the link coupler and the
peripheral device (DTAM, PIC, HHT) — if connected — through the
1747-C11 cable. No external power supply is required.
If you do not connect the processor to the link coupler, use a Class 2
24V dc power supply to power the link coupler and peripheral
device.
USB (DF1)
RS485 (DH485)
RS232 (DH485)
USB to DH485
INTERFACE CONVERTER
USB
OK
SW
DH485
R
CUS
CAT SER FRN
1747-UIC A X.X
Mfg
XXXX
LISTED IND. CONT. EQ. FOR HAZ.
LOC. A196,
OPERATING TEMP CODE TAG
CLASS 1 GROUPS A, B, C, AND D, DIV. 2
MADE IN INDIA
N223
DH-485
Peripheral
CPU
Power
SLC 500
ALLEN-BRADLEY
1784-PCM4
Cable
SLC 500 Modular
Controller
to
1784-PCMK
card in
PCMCIA
slot
DH-485 Link
1747-AIC
Link Coupler
1747-C11
Cable
1747-PIC
Interface
Converter
SLC 500 Fixed
Controller
Use Belden#3106
or #9842 shielded,
twisted-pair cable.
Daisy-chain cable
segments together.
Total length of
cable segments
cannot exceed
1219m (4000 ft).
158 mm
(6.22 in)
1747-UIC
Interface
Converter
to USB port
Belden #3106A or #9642
to serial port
1747-C10
Cable
Personal
Computer
1747-C13
Cable
ATTENTION
!
Always connect the CHS GND (chassis ground)
terminal to the nearest earth ground. This connection
must be made whether or not an external 24V dc
power supply is used.
Publication 1747-IN062A-MU-P - April 2003
2 SLC
®
500 Programmable Controller Isolated Link Coupler
DH-485 Connections
Connecting the Communication Cable to the Link Coupler
Attach the terminal block of the link coupler to the Belden #3106A or
#9842 cable as shown below.
Grounding and Terminating the DH-485 Network
Only one of the Link Couplers at the end of the link must have
Terminals 1 and 2 of the network connector jumpered together.
Link couplers at both ends of the network must have Terminals 5 and
6 of the link connectors jumpered together.
Use Belden #9842 shielded, twisted-pair cable.
Belden #3106A Belden #9842
For this wire/pair Connect this wire To this terminal For this wire/pair Connect this wire To this terminal
Shield/Drain Non-jacketed 2 - Shield Shield/Drain Non-jacketed 2 - Shield
Blue Blue 3 - Common Blue/White White with Blue Stripe No connection - cut back
Blue with White Stripe 3 - Common
White/Orange White with Orange Stripe 4 - Data B White/Orange White with Orange Stripe 4 - Data B
Orange with White Stripe 5 - Data A Orange with White Stripe 5 - Data A
Belden #3106A or #9842
Shrink Tubing Recommended
Orange with White Stipes
White with Orange Stipes
Blue (#3106A) or Blue with White Stripes (#9842)
Drain Wire
to Previous Device
to Successive Device
6 Termination
5 A
4 B
3 Common
2 Shield
1 Chassis Ground
6 Termination
5 A
4 B
3 Common
2 Shield
1 Chassis Ground
Multiple ConnectionsSingle Connection
3 Publication 1747-IN062A-MU-P - April 2003
Notice d’installation
Coupleur réseau pour automates
programmables SLC
®
500
(Référence 1747-AIC)
Installation du câble
réseau DH-485
La publication 1747-UM011, SLC 500 Modular Hardware Style User
Manual, contient des instructions et des directives complètes sur la
planification du réseau DH-485.
Alimentation du coupleur
réseau
En fonctionnement normal, lorsque l’automate programmable est relié
au coupleur réseau, le processeur alimente le coupleur réseau et
l’unité périphérique (module d’accès à la table de données, terminal
de programmation portatif,...), s’il y a lieu, par le câble 1747-C11.
Aucune alimentation externe n’est requise.
Si vous ne reliez pas le processeur au coupleur réseau, utilisez une
alimentation 24 V c.c. de Classe 2 pour alimenter le coupleur réseau
et l’unité périphérique.
USB (DF1)
RS485 (DH485)
RS232 (DH485)
USB to DH485
INTERFACE CONVERTER
USB
OK
SW
DH485
R
CUS
CAT SER FRN
1747-UIC A X.X
Mfg
XXXX
LISTED IND. CONT. EQ. FOR HAZ.
LOC. A196,
OPERATING TEMP CODE TAG
CLASS 1 GROUPS A, B, C, AND D, DIV. 2
MADE IN INDIA
N223
DH-485
Peripheral
CPU
Power
SLC 500
ALLEN-BRADLEY
Câble 1784-PCM4
Automate SLC 500
version modulaire
vers la
carte
1784-PCMK
dans le
logement
PCMCIA
Liaison DH-485
Coupleur réseau
1747-AIC
Câble
1747- C11
Convertisseur
d’interface
1747-PIC
Automate SLC 500
version bloc
Utilisez un câble à
paire torsadée
blindé Belden
n° 3106 ou
n° 9842.
Segments de
câbles connectés
en série.
La longueur totale
des segments de
câbles ne doit pas
dépasser 1 219 m.
158 mm
Convertisseur
d’interface
1747-UIC
vers le port USB
Belden n° 3106A ou n° 9642
vers le port série
Câble
1747-C10
PC
Câble
1747-C13
ATTENTION
!
Connectez toujours la borne CHS GND (mise à la
terre du châssis) à la prise de terre la plus proche.
Cette connexion doit être effectuée, qu’une
alimentation 24 V c.c. externe soit utilisée ou non.
Publication 1747-IN062A-MU-P - April 2003
4 Coupleur réseau pour automates programmables SLC
®
500
Connexions DH-485
Branchement du câble réseau sur le coupleur réseau
Reliez le bornier du coupleur réseau au câble Belden n° 3106A ou
n° 9842 comme le montre la figure ci-dessous.
Mise à la terre et terminaison du réseau DH-485
Les bornes 1 et 2 du connecteur réseau d’un seul des coupleurs
réseau situés à l’extrémité de la liaison doivent être reliées par un
cavalier.
Les bornes 5 et 6 des connecteurs de liaison des coupleurs réseau
situés à chaque extrémité du réseau doivent être reliées par un
cavalier.
Utilisez un câble à paire torsadée blindé Belden n° 9842.
Belden n° 3106A Belden n° 9842
Pour ce fil/
cette paire
Connectez ce fil A cette borne Pour ce fil/
cette paire
Connectez ce fil A cette borne
Blindage/Décharge Non gainé 2 - Blindage Blindage/Décharge Non gainé 2 - Blindage
Bleu Bleu 3 - Commun Bleu/Blanc Blanc à bandes bleues Pas de connexion - coupé
Bleu à bandes blanches 3 - Commun
Blanc/Orange Blanc à bandes orange 4 - Données B Blanc/Orange Blanc à bandes orange 4 - Données B
Orange à bandes
blanches
5 - Données A Orange à bandes blanches 5 - Données A
Belden n° 3106A ou n° 9842
Gaine thermorétractable
recommandée
Orange à bandes blanches
Blanc à bandes orange
Bleu (n° 3106A) ou bleu à bandes blanches (n° 9842)
Fil de décharge
vers l’équipement précédent
vers l’équipement suivant
6 Terminaison
5 A
4 B
3 Commun
2 Blindage
1 Mise à la terre
du châssis
6 Terminaison
5 A
4 B
3 Commun
2 Blindage
1 Mise à la terre
du châssis
Connexions multiplesConnexion simple
5 Publication 1747-IN062A-MU-P - April 2003
Installationsanleitung
Isolierter Verbundkoppler für
speicherprogrammierbare SLC
®
500-Steuerungen
(Bestellnummer 1747-AIC)
Installation des DH-485-
Kommunikationskabels
Die Publikation 1747-UM011, SLC 500 Modular Hardware Style User
Manual, enthält umfassende Anleitungen und Richtlinien für die
Einrichtung von DH-485-Verbindungen.
Stromversorgung des
Verbundkopplers
Wenn bei normalem Betrieb die speicherprogrammierbare Steuerung
mit dem Verbundkoppler verbunden ist, versorgt der Prozessor – sofern
angeschlossen – über das Kabel 1747-C11 sowohl den Verbundkoppler
als auch die Peripheriegeräte (DTAM, PIC, HHT) mit Strom. Es ist kein
externes Netzteil erforderlich.
Wenn Sie den Prozessor nicht mit dem Verbundkoppler verbinden,
müssen Sie ein 24-V-DC-Netzteil der Klasse 2 verwenden, um den
Verbundkoppler und das Peripheriegerät mit Strom zu versorgen.
USB (DF1)
RS485 (DH485)
RS232 (DH485)
USB to DH485
INTERFACE CONVERTER
USB
OK
SW
DH485
R
CUS
CAT SER FRN
1747-UIC A X.X
Mfg
XXXX
LISTED IND. CONT. EQ. FOR HAZ.
LOC. A196,
OPERATING TEMP CODE TAG
CLASS 1 GROUPS A, B, C, AND D, DIV. 2
MADE IN INDIA
N223
DH-485
Peripheral
CPU
Power
SLC 500
ALLEN-BRADLEY
1784-PCM4-Kabel
Modulare
SLC 500-Steuerung
zur
1784-PCMK-
Karte im
PCMCIA-
Steckplatz
DH-485-
Verbindung
1747-AIC-
Verbundkoppler
1747-C11-
Kabel
1747-PIC-
Schnittstellen-
wandler
Festverdrahtete
SLC 500-Steuerung
Verwenden Sie
abgeschirmte,
verdrillte Doppel-
kabel vom Typ
Belden 3106
oder 9842.
Verbinden Sie die
Kabelsegmente zu
einer Prioritätskette.
Die Gesamtlänge
aller Kabelsegmente
darf 1219 m nicht
überschreiten.
158 mm
1747-UIC-
Schnittstellen-
wandler
zum USB-Anschluss
Belden 3106A oder 9642
zum seriellen
Anschluss
1747-C10-
Kabel
PC
1747-C13-
Kabel
ATTENTION
!
Verbinden Sie die CHS GND-Klemme (Chassis-
erdung) grundsätzlich mit der nächsten Erde.
Diese Verbindung muss unabhängig davon, ob ein
externes 24-V-DC-Netzteil verwendet wird, immer
hergestellt werden.
Publication 1747-IN062A-MU-P - April 2003
6 Isolierter Verbundkoppler für speicherprogrammierbare SLC
®
500-Steuerungen
DH-485-Verbindungen
Anschluss des Kommunikationskabels an den Verbundkoppler
Schließen Sie, wie nachfolgend dargestellt, die Klemmenleiste des
Verbundkopplers an das Belden-Kabel 3106A oder 9842 an.
Erdung und Abschluss des DH-485-Netzwerks
Nur bei einem der Verbundkoppler am Ende der Verbindung muss
eine Brücke zwischen den Klemmen 1 und 2 des Netzwerkan-
schlusses hergestellt werden.
Bei den Verbundkopplern an beiden Enden des Netzwerks müssen
zwischen den Klemmen 5 und 6 der Netzwerkanschlüsse Brücken
hergestellt werden.
Verwenden Sie abgeschirmte, verdrillte Doppelkabel vom Typ
Belden 9842.
Belden 3106A Belden 9842
Draht/Paar Verbindung Anschlussklemme Draht/Paar Verbindung Anschlussklemme
Abschirmung Nicht umhüllt 2 – Abschirmung Abschirmung Nicht umhüllt 2 – Abschirmung
Blau Blau 3 – Bezugspotenzial Blau/Weiß Weiß mit blauen Streifen Keine Verbindung
Blau mit weißen Streifen 3 – Bezugspotenzial
Weiß/Orange Weiß mit orangen Streifen 4 – Daten B Weiß/Orange Weiß mit orangen Streifen 4 – Daten B
Orange mit weißen Streifen 5 – Daten A Orange mit weißen Streifen 5 – Daten A
Belden 3106A oder 9842
Schrumpfschlauch wird
empfohlen
Orange mit weißen Streifen
Weiß mit orangen Streifen
Blau (3106A) oder blau mit weißen Streifen (9842)
Erdungsdraht
zum vorherigen Gerät
zum nachfolgenden Gerät
6 Abschluss
5A
4B
3 Bezugspotenzial
2 Abschirmung
1 Chassiserdung
6 Abschluss
5A
4B
3 Bezugspotenzial
2 Abschirmung
1 Chassiserdung
Mehrere VerbindungenEine Verbindung
7 Publication 1747-IN062A-MU-P - April 2003
Istruzioni per l'installazione
Accoppiatore isolato per controllore
programmabile SLC
®
500
(Numero di catalogo 1747-AIC)
Installazione del cavo di
comunicazioni DH-485
La pubblicazione 1747-UM011, SLC 500 Modular Hardware Style User
Manual, contiene le istruzioni e le linee guida per la prianificazione
del collegamento DH-485.
Alimentazione
dell'accoppiatore
In condizioni di funzionamento normali con il controllore
programmabile collegato all'accoppiatore, il processore alimenta sia
l'accoppiatore che le periferiche (DTAM, PIC, HHT) — se collegate
mediante il cavo 1747-C11. Non è richiesto alimentatore esterno.
Se non si collega il processore all'accoppiatore, usare un alimentatore
di Classe 2 a 24V cc per alimentare l'accoppiatore e le periferiche.
USB (DF1)
RS485 (DH485)
RS232 (DH485)
USB to DH485
INTERFACE CONVERTER
USB
OK
SW
DH485
R
CUS
CAT SER FRN
1747-UIC A X.X
Mfg
XXXX
LISTED IND. CONT. EQ. FOR HAZ.
LOC. A196,
OPERATING TEMP CODE TAG
CLASS 1 GROUPS A, B, C, AND D, DIV. 2
MADE IN INDIA
N223
DH-485
Peripheral
CPU
Power
SLC 500
ALLEN-BRADLEY
Cavo
1784-PCM4
Controllore modulare
SLC 500
Alla scheda
1784-PCMK
in slot
PCMCIA
Collegamento DH-485
Accoppiatore
1747-AIC
Cavo
1747-C11
Convertitore
di interfaccia
1747-PIC
Controllore compatto
SLC 500
Usare doppino
intrecciato
Belden#3106 o
#9842 schermato.
Collegare a
margherita i
segmenti di cavo.
La lungheza totale
dei segmenti non
deve essere
maggiore di 1219
metri.
158 mm
Convertitore di
interfaccia
1747-UIC
Alla porta USB
Belden #3106A o #9642
Alla porta seriale
Cavo
1747-C10
Personal
Computer
Cavo
1747-C13
ATTENTION
!
Collegare sempre il morsettto CHS GND (terra
chassis) al collegamento a terra più vicino. È
necessario eseguire questo collegamento
indipendentemente dall'utilizzo di un alimentatore
esterno a 24V cc.
Publication 1747-IN062A-MU-P - April 2003
8 Accoppiatore isolato per controllore programmabile SLC
®
500
Collegamenti DH-485
Collegamento del cavo di comunicazione all'accoppiatore
Applicare la morsettiera dell'accoppiatore al cavo Belden #3106A o
#9842 come mostrato in figura.
Messa a terra e terminazione della rete DH-485
Solo uno degli accoppiatori all'estemità di un collegamento deve
avere i morsetti 1 e 2 del connettore ponticellati.
Gli accoppiatori di entrambe le estremità della rete devono avere i
morsetti 5 e 6 dei connettori ponticellati.
Usare cavo a doppino intrecciato Belden #9842 schermato.
Belden #3106A Belden #9842
Per questo filo/coppia Collegare questo filo A questo morsetto Per questo filo/coppia Collegare questo filo A questo morsetto
Schermo/terra Senza guaina 2 - Schermo Schermo/terra Senza guaina 2 - Schermo
Blu Blu 3 - Comune Blu/Bianco Bianco con strisce blu Nessun
collegamento-
tagliare
Blu con strisce bianche 3 - Comune
Bianco/Arancione Bianco con strisce
arancioni
4 - Dati B Bianco/Arancione Bianco con strisce
arancioni
4 - Dati B
Arancione con strisce
bianche
5 - Dati A Arancione con strisce
bianche
5 - Dati A
Belden #3106A o #9842
Si consiglia tubo
termorestringente
Arancione con strisce bianche
Bianco con strisce arancioni
Blu (#3106A) o blu con strisce bianche (#9842)
Filo di terra
al dispositivo precedente
al dispositivo successivo
6
5 A
4 B
3 Comune
2 Schermo
1 Terra chassis
6
5 A
4 B
3 Comune
2 Schermo
1 Terra chassis
Collegamenti multipliCollegamento singolo
9 Publication 1747-IN062A-MU-P - April 2003
Instrucciones de instalación
Acoplador de vínculo aislado de controlador
programable SLC
®
500
(Número de catálogo 1747-AIC)
Instalación del cable de
comunicaciones DH-485
La publicación 1747-UM011, SLC 500 Modular Hardware Style User
Manual, contiene instrucciones completas y pautas para la
planificación de los vínculos DH-485.
Activación del acoplador
de vínculo
En condiciones normales de funcionamiento con el controlador
programable conectado al acoplador de vínculo, el procesador
proporciona alimentación eléctrica tanto al acoplador de vínculo
como al dispositivo periférico (DTAM, PIC, HHT), si está conectado, a
través del cable 1747-C11. No es necesaria una fuente de alimentación
eléctrica externa.
Si no conecta el procesador al acoplador de vínculo, utilice una fuente
de alimentación de 24 VCC de clase 2 para la alimentación del
acoplador de vínculo y del dispositivo periférico.
USB (DF1)
RS485 (DH485)
RS232 (DH485)
USB to DH485
INTERFACE CONVERTER
USB
OK
SW
DH485
R
CUS
CAT SER FRN
1747-UIC A X.X
Mfg
XXXX
LISTED IND. CONT. EQ. FOR HAZ.
LOC. A196,
OPERATING TEMP CODE TAG
CLASS 1 GROUPS A, B, C, AND D, DIV. 2
MADE IN INDIA
N223
DH-485
Peripheral
CPU
Power
SLC 500
ALLEN-BRADLEY
Cable
1784-PCM4
Controlador modular
SLC 500
a la tarjeta
1784-PCMK
en la ranura
PCMCIA
Vínculo
DH-485
Acoplador de
vínculo
1747-AIC
Cable
1747-C11
Convertidor
de interface
1747-PIC
Controlador compacto
SLC 500
Utilice cable de
par trenzado
blindado Belden
3106 ó 9842.
Conecte en
cadena los
segmentos de
cable.
La longitud total
de los segmentos
de cable no puede
superar los 1219 m
(4000 pies).
158 mm
(6.22 pulg.)
Convertidor de
interface
1747-UIC
a puerto USB
Belden 3106A ó 9642
a puerto en serie
Cable
1747-C10
PC
Cable
1747-C13
ATTENTION
!
Conecte siempre el terminal CHS GND (tierra de
chasis) a la toma de tierra más cercana. Esta
conexión es necesaria independientemente de que
se utilice o no una fuente de alimentación eléctrica
de 24 VCC.
Publication 1747-IN062A-MU-P - April 2003
10 Acoplador de vínculo aislado de controlador programable SLC
®
500
Conexiones DH-485
Conexión del cable de comunicaciones al acoplador de vínculo
Conecte el bloque de terminales del acoplador de vínculo al cable
Belden 3106A ó 9842 tal como se muestra a continuación.
Puesta a tierra y terminaciones de la red DH-485
Sólo uno de los acopladores de vínculo en el extremo del vínculo
debe tener los terminales 1 y 2 del conector de red puenteados
entre sí.
Los acopladores de vínculo en ambos extremos de la red deben tener
los terminales 5 y 6 de los conectores del vínculo puenteados entre sí.
Utilice un cable de par trenzado blindado Belden 9842.
Belden 3106A Belden 9842
Para este hilo/par Conecte este hilo A este terminal Para este hilo/par Conecte este hilo A este terminal
Blindaje/tierra Sin forro 2 - Blindaje Blindaje/tierra Sin forro 2 - Blindaje
Azul Azul 3 - Común Azul/blanco Blanco con franjas azules Sin conexión, córtese
Azul con franjas blancas 3 - Común
Blanco/anaranjado Blanco con franjas
anaranjadas
4 - Datos B Blanco/anaranjado Blanco con franjas
anaranjadas
4 - Datos B
Anaranjado con franjas
blancas
5 - Datos A Anaranjado con franjas
blancas
5 - Datos A
Belden 3106A ó 9842
Se recomienda tubo
termorretráctil
Anaranjado con franjas blancas
Blanco con franjas
Azul (3106A) o azul con franjas blancas (9842)
Cable de tierra
a dispositivo anterior
a dispositivo siguiente
6 Terminación
5 A
4 B
3 Común
2 Blindaje
1 Tierra de chasis
6 Terminación
5 A
4 B
3 Común
2 Blindaje
1 Tierra de chasis
Conexiones múltiplesConexión única
Publication 1747-IN062A-MU-P - April 2003
Acoplador de vínculo aislado de controlador programable SLC
®
500 11
Publication 1747-IN062A-MU-P - April 2003 12 PN 40071-150-01(1)
Supersedes Publication 40063-023-01 (C) Copyright © 2003 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.

Transcripción de documentos

Installation Instructions SLC® 500 Programmable Controller Isolated Link Coupler (Catalog Number 1747-AIC) Installing the DH-485 Communication Cable DH-485 Link Personal Computer to serial port USB (DF1) USB OK DH485 USB to DH485 INTERFACE CONVERTER CAT 1747-UIC C SER A R FRN X.X US LISTED IND. CONT. EQ. FOR HAZ. LOC. A196, OPERATING TEMP CODE TAG CLASS 1 GROUPS A, B, C, AND D, DIV. 2 MADE IN INDIA RS485 (DH485) to 1784-PCMK card in PCMCIA slot Belden #3106A or #9642 to USB port SW SLC 500 Fixed Controller 1747-UIC Interface Converter Daisy-chain cable segments together. Mfg XXXX N223 RS232 (DH485) 1747-C13 Cable 1747-PIC Interface Converter 158 mm (6.22 in) DH-485 SLC 500 Peripheral CPU ALLEN-BRADLEY Power 1747-C10 Cable Use Belden#3106 or #9842 shielded, twisted-pair cable. 1747-C11 Cable SLC 500 Modular Controller Total length of cable segments cannot exceed 1219m (4000 ft). 1747-AIC Link Coupler 1784-PCM4 Cable Publication 1747-UM011, SLC 500 Modular Hardware Style User Manual, contains complete instructions and guidelines for DH-485 link planning. Powering the Link Coupler In normal operation with the programmable controller connected to the link coupler, the processor powers both the link coupler and the peripheral device (DTAM, PIC, HHT) — if connected — through the 1747-C11 cable. No external power supply is required. If you do not connect the processor to the link coupler, use a Class 2 24V dc power supply to power the link coupler and peripheral device. ATTENTION ! 1 Always connect the CHS GND (chassis ground) terminal to the nearest earth ground. This connection must be made whether or not an external 24V dc power supply is used. Publication 1747-IN062A-MU-P - April 2003 2 SLC® 500 Programmable Controller Isolated Link Coupler DH-485 Connections Connecting the Communication Cable to the Link Coupler Attach the terminal block of the link coupler to the Belden #3106A or #9842 cable as shown below. Single Connection Multiple Connections to Previous Device to Successive Device Orange with White Stipes White with Orange Stipes Belden #3106A or #9842 Shrink Tubing Recommended 6 Termination 5A 4B 3 Common 2 Shield 1 Chassis Ground 6 Termination 5A 4B 3 Common 2 Shield 1 Chassis Ground Blue (#3106A) or Blue with White Stripes (#9842) Drain Wire Belden #3106A Belden #9842 For this wire/pair Connect this wire To this terminal For this wire/pair Connect this wire To this terminal Shield/Drain Non-jacketed 2 - Shield Shield/Drain Non-jacketed 2 - Shield Blue Blue 3 - Common Blue/White White with Blue Stripe No connection - cut back Blue with White Stripe 3 - Common White with Orange Stripe 4 - Data B Orange with White Stripe 5 - Data A White/Orange White with Orange Stripe 4 - Data B Orange with White Stripe 5 - Data A White/Orange Grounding and Terminating the DH-485 Network Only one of the Link Couplers at the end of the link must have Terminals 1 and 2 of the network connector jumpered together. Link couplers at both ends of the network must have Terminals 5 and 6 of the link connectors jumpered together. Use Belden #9842 shielded, twisted-pair cable. Publication 1747-IN062A-MU-P - April 2003 Notice d’installation Coupleur réseau pour automates programmables SLC® 500 (Référence 1747-AIC) Installation du câble réseau DH-485 Liaison DH-485 PC vers le port série USB (DF1) USB OK DH485 USB to DH485 INTERFACE CONVERTER CAT 1747-UIC C SER A R FRN X.X US LISTED IND. CONT. EQ. FOR HAZ. LOC. A196, OPERATING TEMP CODE TAG CLASS 1 GROUPS A, B, C, AND D, DIV. 2 MADE IN INDIA RS485 (DH485) vers la carte 1784-PCMK dans le logement PCMCIA Belden n° 3106A ou n° 9642 vers le port USB SW Automate SLC 500 version bloc Convertisseur d’interface 1747-UIC Utilisez un câble à paire torsadée blindé Belden n° 3106 ou n° 9842. Mfg XXXX N223 RS232 (DH485) Câble 1747-C13 Convertisseur d’interface 1747-PIC 158 mm DH-485 SLC 500 Peripheral CPU ALLEN-BRADLEY Power Câble 1747-C10 Coupleur réseau 1747-AIC Câble 1784-PCM4 Câble 1747- C11 Automate SLC 500 version modulaire Segments de câbles connectés en série. La longueur totale des segments de câbles ne doit pas dépasser 1 219 m. La publication 1747-UM011, SLC 500 Modular Hardware Style User Manual, contient des instructions et des directives complètes sur la planification du réseau DH-485. Alimentation du coupleur réseau En fonctionnement normal, lorsque l’automate programmable est relié au coupleur réseau, le processeur alimente le coupleur réseau et l’unité périphérique (module d’accès à la table de données, terminal de programmation portatif,...), s’il y a lieu, par le câble 1747-C11. Aucune alimentation externe n’est requise. Si vous ne reliez pas le processeur au coupleur réseau, utilisez une alimentation 24 V c.c. de Classe 2 pour alimenter le coupleur réseau et l’unité périphérique. ATTENTION ! 3 Connectez toujours la borne CHS GND (mise à la terre du châssis) à la prise de terre la plus proche. Cette connexion doit être effectuée, qu’une alimentation 24 V c.c. externe soit utilisée ou non. Publication 1747-IN062A-MU-P - April 2003 4 Coupleur réseau pour automates programmables SLC® 500 Connexions DH-485 Branchement du câble réseau sur le coupleur réseau Reliez le bornier du coupleur réseau au câble Belden n° 3106A ou n° 9842 comme le montre la figure ci-dessous. Connexion simple Connexions multiples vers l’équipement précédent vers l’équipement suivant Orange à bandes blanches Belden n° 3106A ou n° 9842 Gaine thermorétractable recommandée Bleu (n° 3106A) ou bleu à bandes blanches (n° 9842) 6 Terminaison 5A 4B 3 Commun 2 Blindage 1 Mise à la terre du châssis 6 Terminaison 5A 4B 3 Commun 2 Blindage 1 Mise à la terre du châssis Blanc à bandes orange Fil de décharge Belden n° 3106A Belden n° 9842 Pour ce fil/ cette paire Connectez ce fil A cette borne Pour ce fil/ cette paire Connectez ce fil A cette borne Blindage/Décharge Non gainé 2 - Blindage Blindage/Décharge Non gainé 2 - Blindage Bleu Bleu 3 - Commun Bleu/Blanc Blanc à bandes bleues Pas de connexion - coupé Bleu à bandes blanches 3 - Commun Blanc à bandes orange 4 - Données B Orange à bandes blanches 5 - Données A Blanc/Orange Blanc à bandes orange 4 - Données B Orange à bandes blanches 5 - Données A Blanc/Orange Mise à la terre et terminaison du réseau DH-485 Les bornes 1 et 2 du connecteur réseau d’un seul des coupleurs réseau situés à l’extrémité de la liaison doivent être reliées par un cavalier. Les bornes 5 et 6 des connecteurs de liaison des coupleurs réseau situés à chaque extrémité du réseau doivent être reliées par un cavalier. Utilisez un câble à paire torsadée blindé Belden n° 9842. Publication 1747-IN062A-MU-P - April 2003 Installationsanleitung Isolierter Verbundkoppler für speicherprogrammierbare SLC® 500-Steuerungen (Bestellnummer 1747-AIC) Installation des DH-485Kommunikationskabels PC DH-485Verbindung zum USB-Anschluss zum seriellen Anschluss USB (DF1) USB OK DH485 USB to DH485 INTERFACE CONVERTER CAT 1747-UIC C SER A R FRN X.X US LISTED IND. CONT. EQ. FOR HAZ. LOC. A196, OPERATING TEMP CODE TAG CLASS 1 GROUPS A, B, C, AND D, DIV. 2 MADE IN INDIA RS485 (DH485) zur 1784-PCMKKarte im PCMCIASteckplatz SW Belden 3106A oder 9642 Festverdrahtete SLC 500-Steuerung 1747-UICSchnittstellenwandler Verwenden Sie abgeschirmte, verdrillte Doppelkabel vom Typ Belden 3106 oder 9842. Mfg XXXX N223 RS232 (DH485) 1747-C13Kabel 1747-PICSchnittstellenwandler 158 mm DH-485 SLC 500 Peripheral CPU ALLEN-BRADLEY Power 1747-C10Kabel 1747-AICVerbundkoppler 1784-PCM4-Kabel 1747-C11Kabel Modulare SLC 500-Steuerung Verbinden Sie die Kabelsegmente zu einer Prioritätskette. Die Gesamtlänge aller Kabelsegmente darf 1219 m nicht überschreiten. Die Publikation 1747-UM011, SLC 500 Modular Hardware Style User Manual, enthält umfassende Anleitungen und Richtlinien für die Einrichtung von DH-485-Verbindungen. Stromversorgung des Verbundkopplers Wenn bei normalem Betrieb die speicherprogrammierbare Steuerung mit dem Verbundkoppler verbunden ist, versorgt der Prozessor – sofern angeschlossen – über das Kabel 1747-C11 sowohl den Verbundkoppler als auch die Peripheriegeräte (DTAM, PIC, HHT) mit Strom. Es ist kein externes Netzteil erforderlich. Wenn Sie den Prozessor nicht mit dem Verbundkoppler verbinden, müssen Sie ein 24-V-DC-Netzteil der Klasse 2 verwenden, um den Verbundkoppler und das Peripheriegerät mit Strom zu versorgen. ATTENTION ! 5 Verbinden Sie die CHS GND-Klemme (Chassiserdung) grundsätzlich mit der nächsten Erde. Diese Verbindung muss unabhängig davon, ob ein externes 24-V-DC-Netzteil verwendet wird, immer hergestellt werden. Publication 1747-IN062A-MU-P - April 2003 6 Isolierter Verbundkoppler für speicherprogrammierbare SLC® 500-Steuerungen DH-485-Verbindungen Anschluss des Kommunikationskabels an den Verbundkoppler Schließen Sie, wie nachfolgend dargestellt, die Klemmenleiste des Verbundkopplers an das Belden-Kabel 3106A oder 9842 an. Eine Verbindung Mehrere Verbindungen zum vorherigen Gerät zum nachfolgenden Gerät Orange mit weißen Streifen Weiß mit orangen Streifen Belden 3106A oder 9842 Schrumpfschlauch wird empfohlen Blau (3106A) oder blau mit weißen Streifen (9842) 6 Abschluss 5A 4B 3 Bezugspotenzial 2 Abschirmung 1 Chassiserdung 6 Abschluss 5A 4B 3 Bezugspotenzial 2 Abschirmung 1 Chassiserdung Erdungsdraht Belden 3106A Belden 9842 Draht/Paar Verbindung Anschlussklemme Draht/Paar Verbindung Anschlussklemme Abschirmung Nicht umhüllt 2 – Abschirmung Abschirmung Nicht umhüllt 2 – Abschirmung Blau Blau 3 – Bezugspotenzial Blau/Weiß Weiß mit blauen Streifen Keine Verbindung Blau mit weißen Streifen 3 – Bezugspotenzial Weiß mit orangen Streifen 4 – Daten B Orange mit weißen Streifen 5 – Daten A Weiß/Orange Weiß mit orangen Streifen 4 – Daten B Orange mit weißen Streifen 5 – Daten A Weiß/Orange Erdung und Abschluss des DH-485-Netzwerks Nur bei einem der Verbundkoppler am Ende der Verbindung muss eine Brücke zwischen den Klemmen 1 und 2 des Netzwerkanschlusses hergestellt werden. Bei den Verbundkopplern an beiden Enden des Netzwerks müssen zwischen den Klemmen 5 und 6 der Netzwerkanschlüsse Brücken hergestellt werden. Verwenden Sie abgeschirmte, verdrillte Doppelkabel vom Typ Belden 9842. Publication 1747-IN062A-MU-P - April 2003 Istruzioni per l'installazione Accoppiatore isolato per controllore programmabile SLC® 500 (Numero di catalogo 1747-AIC) Installazione del cavo di comunicazioni DH-485 Personal Computer Collegamento DH-485 Alla porta seriale USB (DF1) USB OK DH485 USB to DH485 INTERFACE CONVERTER CAT 1747-UIC C SER A R FRN X.X US LISTED IND. CONT. EQ. FOR HAZ. LOC. A196, OPERATING TEMP CODE TAG CLASS 1 GROUPS A, B, C, AND D, DIV. 2 MADE IN INDIA RS485 (DH485) Alla scheda 1784-PCMK in slot PCMCIA Belden #3106A o #9642 Alla porta USB SW Controllore compatto SLC 500 Convertitore di interfaccia 1747-UIC Collegare a margherita i segmenti di cavo. Mfg XXXX N223 RS232 (DH485) Cavo 1747-C13 Convertitore di interfaccia 1747-PIC Usare doppino intrecciato Belden#3106 o #9842 schermato. 158 mm DH-485 SLC 500 Peripheral CPU ALLEN-BRADLEY Power Cavo 1747-C10 Accoppiatore 1747-AIC Cavo 1784-PCM4 Cavo 1747-C11 Controllore modulare SLC 500 La lungheza totale dei segmenti non deve essere maggiore di 1219 metri. La pubblicazione 1747-UM011, SLC 500 Modular Hardware Style User Manual, contiene le istruzioni e le linee guida per la prianificazione del collegamento DH-485. Alimentazione dell'accoppiatore In condizioni di funzionamento normali con il controllore programmabile collegato all'accoppiatore, il processore alimenta sia l'accoppiatore che le periferiche (DTAM, PIC, HHT) — se collegate — mediante il cavo 1747-C11. Non è richiesto alimentatore esterno. Se non si collega il processore all'accoppiatore, usare un alimentatore di Classe 2 a 24V cc per alimentare l'accoppiatore e le periferiche. ATTENTION ! 7 Collegare sempre il morsettto CHS GND (terra chassis) al collegamento a terra più vicino. È necessario eseguire questo collegamento indipendentemente dall'utilizzo di un alimentatore esterno a 24V cc. Publication 1747-IN062A-MU-P - April 2003 8 Accoppiatore isolato per controllore programmabile SLC® 500 Collegamenti DH-485 Collegamento del cavo di comunicazione all'accoppiatore Applicare la morsettiera dell'accoppiatore al cavo Belden #3106A o #9842 come mostrato in figura. Collegamento singolo Collegamenti multipli al dispositivo precedente al dispositivo successivo Arancione con strisce bianche Bianco con strisce arancioni Belden #3106A o #9842 Si consiglia tubo termorestringente Blu (#3106A) o blu con strisce bianche (#9842) 6 5A 4B 3 Comune 2 Schermo 1 Terra chassis 6 5A 4B 3 Comune 2 Schermo 1 Terra chassis Filo di terra Belden #3106A Belden #9842 Per questo filo/coppia Collegare questo filo A questo morsetto Per questo filo/coppia Collegare questo filo A questo morsetto Schermo/terra Senza guaina 2 - Schermo Schermo/terra Senza guaina 2 - Schermo Blu Blu 3 - Comune Blu/Bianco Bianco con strisce blu Nessun collegamentotagliare Blu con strisce bianche 3 - Comune Bianco con strisce arancioni 4 - Dati B Arancione con strisce bianche 5 - Dati A Bianco/Arancione Bianco con strisce arancioni 4 - Dati B Arancione con strisce bianche 5 - Dati A Bianco/Arancione Messa a terra e terminazione della rete DH-485 Solo uno degli accoppiatori all'estemità di un collegamento deve avere i morsetti 1 e 2 del connettore ponticellati. Gli accoppiatori di entrambe le estremità della rete devono avere i morsetti 5 e 6 dei connettori ponticellati. Usare cavo a doppino intrecciato Belden #9842 schermato. Publication 1747-IN062A-MU-P - April 2003 Instrucciones de instalación Acoplador de vínculo aislado de controlador programable SLC® 500 (Número de catálogo 1747-AIC) Instalación del cable de comunicaciones DH-485 PC Vínculo DH-485 a puerto USB a puerto en serie USB (DF1) USB OK DH485 USB to DH485 INTERFACE CONVERTER CAT 1747-UIC C SER A R FRN X.X US LISTED IND. CONT. EQ. FOR HAZ. LOC. A196, OPERATING TEMP CODE TAG CLASS 1 GROUPS A, B, C, AND D, DIV. 2 MADE IN INDIA RS485 (DH485) a la tarjeta 1784-PCMK en la ranura PCMCIA SW Belden 3106A ó 9642 Controlador compacto SLC 500 Convertidor de interface 1747-UIC Conecte en cadena los segmentos de cable. Mfg XXXX N223 RS232 (DH485) Cable 1747-C13 Convertidor de interface 1747-PIC 158 mm (6.22 pulg.) DH-485 SLC 500 Peripheral CPU ALLEN-BRADLEY Power Cable 1747-C10 Cable 1784-PCM4 Acoplador de vínculo 1747-AIC Utilice cable de par trenzado blindado Belden 3106 ó 9842. Cable 1747-C11 Controlador modular SLC 500 La longitud total de los segmentos de cable no puede superar los 1219 m (4000 pies). La publicación 1747-UM011, SLC 500 Modular Hardware Style User Manual, contiene instrucciones completas y pautas para la planificación de los vínculos DH-485. Activación del acoplador de vínculo En condiciones normales de funcionamiento con el controlador programable conectado al acoplador de vínculo, el procesador proporciona alimentación eléctrica tanto al acoplador de vínculo como al dispositivo periférico (DTAM, PIC, HHT), si está conectado, a través del cable 1747-C11. No es necesaria una fuente de alimentación eléctrica externa. Si no conecta el procesador al acoplador de vínculo, utilice una fuente de alimentación de 24 VCC de clase 2 para la alimentación del acoplador de vínculo y del dispositivo periférico. ATTENTION ! 9 Conecte siempre el terminal CHS GND (tierra de chasis) a la toma de tierra más cercana. Esta conexión es necesaria independientemente de que se utilice o no una fuente de alimentación eléctrica de 24 VCC. Publication 1747-IN062A-MU-P - April 2003 10 Acoplador de vínculo aislado de controlador programable SLC® 500 Conexiones DH-485 Conexión del cable de comunicaciones al acoplador de vínculo Conecte el bloque de terminales del acoplador de vínculo al cable Belden 3106A ó 9842 tal como se muestra a continuación. Conexión única Conexiones múltiples a dispositivo anterior a dispositivo siguiente Anaranjado con franjas blancas Belden 3106A ó 9842 Se recomienda tubo termorretráctil Azul (3106A) o azul con franjas blancas (9842) 6 Terminación 5A 4B 3 Común 2 Blindaje 1 Tierra de chasis 6 Terminación 5A 4B 3 Común 2 Blindaje 1 Tierra de chasis Blanco con franjas Cable de tierra Belden 3106A Belden 9842 Para este hilo/par Conecte este hilo A este terminal Para este hilo/par Conecte este hilo A este terminal Blindaje/tierra Sin forro 2 - Blindaje Blindaje/tierra Sin forro 2 - Blindaje Azul Azul 3 - Común Azul/blanco Blanco con franjas azules Sin conexión, córtese Azul con franjas blancas 3 - Común Blanco con franjas anaranjadas 4 - Datos B Anaranjado con franjas blancas 5 - Datos A Blanco/anaranjado Blanco con franjas anaranjadas 4 - Datos B Anaranjado con franjas blancas 5 - Datos A Blanco/anaranjado Puesta a tierra y terminaciones de la red DH-485 Sólo uno de los acopladores de vínculo en el extremo del vínculo debe tener los terminales 1 y 2 del conector de red puenteados entre sí. Los acopladores de vínculo en ambos extremos de la red deben tener los terminales 5 y 6 de los conectores del vínculo puenteados entre sí. Utilice un cable de par trenzado blindado Belden 9842. Publication 1747-IN062A-MU-P - April 2003 Acoplador de vínculo aislado de controlador programable SLC® 500 11 Publication 1747-IN062A-MU-P - April 2003 Publication 1747-IN062A-MU-P - April 2003 12 Supersedes Publication 40063-023-01 (C) PN 40071-150-01(1) Copyright © 2003 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12

Rockwell Automation Allen-Bradley SLC 500 Guía de instalación

Tipo
Guía de instalación
Este manual también es adecuado para