CARLO GAVAZZI EM2172RVV23XOXX Guía de instalación

Tipo
Guía de instalación
Front panel and value setup (fig. 1)
In the measurement mode: press the key 1 to scroll the measurement pages.
press the key 2 to scroll the information pages of the instrument. Holding the but-
ton 2 pressed for at least 3 sec., you access parameter programming and setting.
I
n the programming mode: press the key 1, to scroll the menus or
increase/decrease the values to be set up. With button 2 you can enter the sub-
menus and change the value change mode from positive to negative or vice versa
according to the logic indicated in table 1: a, pressing button 2, the letter C
appears in the bottom row, indicating the possibility to change the values increas-
ing them by means of button 1. b, pressing again button 2, -C appears in the bot-
tom row, indicating the possibility to decrease the values by means of button 1. c,
To confirm the selected value, hold button 2 pressed until the mark - of letter C
disappears. This way, the value is confirmed.
The frontal red LED (3, fig.1) flashes proportionally to the active imported energy
consumption.
Wrong phase sequence indicator (4, fig 1), the hazard triangle is displayed in
case of wrong phase sequence (L2-L1-L3, L1-L3-L2).
PROGRAMMING BLOCK
It is possible to block the access to programming by means of a specific trimmer
positioned on the rear of the removable display unit. Turn the trimmer clockwise
up to its run end with the help of a suitable screwdriver as shown in figure 2 point
5.
BASIC PROGRAMMING AND RESET
To enter the complete programming mode, press the key 2 for at least 3 sec. (fig
1). Entering the programming mode, all the measurements and control functions
are inhibited. During this phase the flashing of the LED has not to be considered.
PASS?: entering the right password (default value is 0) allows
accessing the main menu.
CnG PASS: it allows changing the password.
APPLiC: it allows selecting the pertinent application. A: active positive energy
meter (mesuring of active positive energy and some minor parameters). B: active
and reactive positive energies meter (measuring of energies active and reactive
positive with some minor parameters). C: showing of all the electrical variables
available.
SYS: it allows selecting the electrical system. 3Pn: 3-phase unbalanced with
neutral; 3P: 3-phase unbalanced without neutral; 3P1: 3-phase balanced with or
without neutral 2P: 2-phase; 1P: single phase.
Ut rAtio: VT ratio (1.0 to 6.00k). Example: if the connected VT primary is 5kV
and the secondary is 100V, the VT ratio to be set is 50 (that is 5000/100).
PuLSE: selects the pulse weight (kWh per pulse; programmable from 0,01 to
9,99).
P. tESt: sets the simulated power value (kW) to which a proportional pulse
sequence according to “PULSE” corresponds. The function is active until you remain
within the menu.
tESt: activated on the pulse output when ON (for “APPLiC” C only).
Add. : serial address: from 1 to 247 (with “IS” option only).
EnE rES: reset of all the meters (for “APPLiC” C only).
End : it allows exiting the programming mode by pressing the key 2 (see fig
1).
ENGLISH
05
04
03
02
01
11
10
09
08
07
06
CARLO GAVAZZI
A u t o m a t i o n C o m p o n e n t s
Carlo Gavazzi Controls SpA,
V
ia Safforze, 8 - 32100
Belluno (Italy)
Tel. +39 0437 355811,
F
ax +39 0437 355880
EM21 72R IM ML 8021723 210917
EM21 72R
3-phase Energy Meter for Retro-fit‰
PROGRAMMING
■ Pannello frontale ed impostazioni valori (fig. 1)
In modalità misura: tasto 1, scorre le pagine di misura. Tasto 2 scorre le pagine
informazioni dello strumento. Tenendo premuto per almeno 3sec il tasto 2 si acce-
de alla programmazione e impostazioni parametri.
In modalità programmazione: tasto 1, scorre i menù o incrementa/decremente
i
valori da impostare. Il tasto 2, entra nei sottomenù e cambia la modalità di incre-
mentazione dei valori da positiva a negativa e viceversa secondo la logica ripor-
tata nella tabella 1: a, premendo il tasto 2 compare una lettera C nella riga infe-
riore indicante la possibilità di agire sui valori incrementandoli mediante il tasto 1.
b, premendo ulterioriormente il tasto 2 compare -C nella riga inferiore indicante la
possibilità di agire sui valori decrementandoli mediante il tasto 1. c, Per confer-
mare il valore selezionato tenere premuto il tasto 2 finché il segno - (se presen-
t
e) e la lettera C scompariranno, il valore sarà così confermato.
Il LED rosso frontale (3, fig.1) lampeggia proporzionalmente al consumo di
energia attiva totale.
Indicatore di sequenza fase errata (4, fig 1), il triangolo di pericolo viene visua-
lizzato in caso di sequenza fasi errata (L2-L1-L3, L1-L3-L2).
BLOCCO DELLA PROGRAMMAZIONE
E’ possibile bloccare l’accesso alla programmazione mediante un apposito trim-
mer posizionato nel retro dell’unità display removibile. Girare in senso orario fino
a fondo corsa il trimmer con l’ausilio di un adeguato cacciavite come illustra la fig.
2 punto 5.
PROGRAMMAZIONE E RESET
Per accedere alla programmazione completa dello strumento premere il tasto 2
per almeno 3sec. (fig 1). Quando si accede alla programmazione, si inibiscono
tutte le funzioni di misura e controllo (il trimmer non deve essere posizionato in
lock, fig. 2). In questa fase il lampeggio del LED frontale non deve essere consi-
derato.
PASS? : inserendo il valore di password corretto (di default 0) si accede al
menù principale.
CnGPASS: nuova password, personalizza la password.
APPLiC.: seleziona l’applicazione pertinente. A: contatore di energia attiva
positiva (misura dell’energia attiva positiva e di alcuni parametri minori). B: conta-
tore di energia attiva e reattiva positiva (misura dell’energia attiva e reattiva positi-
ve e di alcuni parametri minori). C: visualizzazione di tutte le variabili elettriche
disponibili.
SYS : sitema elettrico: 3Pn: trifase sbilanciato con neutro; 3P: trifase sbilan-
ciato senza neutro; 3P1: trifase bilanciato con o senza neutro; 2P: bifase; 1P
monofase.
Ut rAt. : rapporto TV (da 1,0 a 6.00k). Esempio: se il primario del TV con-
nesso è di 5kV e il secondario è di 100V il rapporto di TV corrisponde a 50 (otte-
nuto eseguendo il calcolo: 5000/100).
PuLSE: seleziona il peso dell’impulso (kWh per impulso; programmabile da
0,01 a 9,99).
P. tESt: (SOLO CON “APPLiC” C, vedere menù n. 3), imposta il valore di
potenza (kW) simulata a cui corrisponderà una frequenza degli impulsi ad essa
proporzionale in base a “PULSE”, la funzione è attiva finché si rimane nel menù.
tESt: (SOLO CON “APPLiC” C, vedere menù n. 3), attivo su uscita impulsi
con selezione ON.
Add. : (solo con opzione “IS”) indirizzo seriale: da 1 a 247.
EnE rES: azzeramento di tutti i contatori totali (SOLO CON “APPLiC” C).
End : per tornare al modo misura premere il tasto 2 (vedere figura 1).
ITALIANO
11
10
09
08
07
06
05
04
03
02
01
■ Vorderes Bedienfeld und Werteinstellungen (fig. 1)
Im Messmodus: Taste 1, durchblättert die Meßseiten. Taste 2 durchblättert die
I
nformationsseiten des Geräts. Bei Gedrückthalten der Taste 2 für mindestens 3
Sek. loggen Sie sich in die Programmierung und Parametereinstellungen ein.
Im Programmiermodus: Taste 1 durchblättert die Menüs bzw. erhöht/verringert
die einzustellenden Werte. Mit Taste 2 gelangt man in die Untermenüs und ändert
die Zunahmemodalität der Werte von positiv in negativ und umgekehrt je nach der
in Tabelle 1 angegebenen Logik: a, bei Drücken der Taste 2 wird ein Buchstaben
C in der unteren Zeile angezeigt, der die Möglichkeit aufzeigt, die Werte mit der
T
aste 1 zu steigern. b, bei weiterem Drücken der Taste 2 wird –C in der unteren
Zeile angezeigt, was die Möglichkeit aufzeigt, die Werte mit der Taste 1 zu verrin-
gern. c, Zur Bestätigung des gewählten Werts die Taste 2 so lange gedrückt hal-
ten bis das Zeichen – des Buchstabens C erlischt, dadurch wird der Wert
bestätigt.
Die vordere rote LED-Leuchte (3, v fig.1) blinkt, wenn die gemessene
Wirkenergie und der Strom positiv (importiert) sind.
Anzeige von falscher Phasenfolge (4, fig 1), das Gefahrendreieck wird bei
falscher Phasenfolge angezeigt (L2-L1-L3, L1-L3-L2).
SPERRE DER PROGRAMMIERUNG
Der Zugriff auf die Programmierung kann mit einem entsprechenden auf der
Rückseite der entfernbaren Anzeigeneinheit positionierten Trimmer blockiert wer-
den. Den Trimmer mithilfe eines passenden Schraubenziehers, wie auf Abb. 2
Punkt 5 dargestellt, im Uhrzeigersinn bis zum Anschlag drehen.
PROGRAMMIERUNG UND RÜCKSETZEN
Um in den Programmiermodus zu gelangen, muss die Taste 2 für mindestens 3
Sek. gedrückt werden (siehe Abb.1). Im Programmiermodus werden alle Mess-
und Kontrollfunktionen inakt. Diese Phase hat keinen Bezug zu dem Blinken der
LED.
PASS? :
durch Eingabe des richtigen Passworts (Default-Wert beträgt 0) rufen
Sie das Hauptmenü auf
.
CnGPASS:
ermöglicht Passwortänderung
.
APPLiC.:
ermöglicht die Wahl des entsprechenden Applikationsbereichs
. A:
Wirkenergiezähler (Messen der positive Wirkenergie und einiger weniger
Parameter). B: Wirk- und Blindenergiezähler (Messen der positive Wirk- und
Blindenergien mit einigen weniger Parametern). C: Anzeige aller verfügbaren
elektrischen Messgrößen.
SYS : ermöglicht die Wahl des Elektrosystems. 3P.n: 3-phasig unsymmetrisch mit
Nullleiter, 3P:3-phasig symmetrisch ohne Nullleiter, 3P1:
3-phasig symmetrisch mit oder ohne Nullleiter 2P: 2-phasig, 1P: eine Phase.
Ut rAt. : SpW-Verhältnis (von 1,0 bis 6,00k). Beispiel: Wenn der angeschlos-
sene primäre Spannungswandler 5kV beträgt und der sekundäre 100V, beträgt
das einzustellende Spannungswandlerverltnis 50
(d.h. 5000/100).
PuLSE: wählt das Impulsgewicht (kWh pro Impuls; einstellbar von 0,01 bis
9,99).
P. tESt: (NUR MIT “APPLiC” C Option, siehe Menü n. 3), stellt den simulier-
ten Leistungswert (kW) ein, dem eine Frequenz der zu ihr proportionalen Impulse
auf der Grundlage von “PULSE” entspricht, die Funktion ist eingeschaltet solan-
ge Sie im Menü bleiben.
tESt: (NUR MIT “APPLiC” C Option, siehe Menü n. 3), bei ON ist
Impulsausgang eingeschaltet.
Add. : (nur mit “IS” Option) ermöglicht die Wahl der seriellen Geräteadressen
(von 1 bis 247).
EnE rES: ermöglicht das Rücksetzen der Gesamtenergiezähler (NUR MIT
“APPLiC” C).
End : ermöglicht das Verlassen des Programmiermodus durch Drücken der
Taste 2 (siehe Abb. 1).
DEUTSCH
11
10
09
08
07
06
05
04
03
02
01
■ Panneau frontal et configurations valeurs (fig. 1)
E
n mode mesure: touche 1, les pages de mesure défilent. Touche 2, les pages
d’informations de l’instrument défilent. En maintenant enfoncé pendant au moins
3 sec. la touche 2, on accède à la programmation et configurations paramètres.
En mode programmation: touche 1, les menus défilent ou les valeurs à configu-
rer augmentent/baissent. La touche 2 entre dans les sous-menus et change le
mode d’incrémentation des valeurs de positif à négatif et vice-versa selon la
logique reportée dans le tableau 1: a, en appuyant sur la touche 2, la lettre C
a
pparaît sur la ligne inférieure indiquant la possibilité d’actionner sur les valeurs
en les augmentant à l’aide de la touche 1. b, en appuyant encore sur la touche 2,
C apparaît dans la ligne inférieure indiquant la possibilité d’agir sur les valeurs en
les diminuant à l’aide de la touche 1. c, Pour valider, confirmer la valeur sélection-
née, maintenir enfoncée la touche 2 jusqu’à ce que le signe – de la lettre C dis-
paraisse, la valeur sera ainsi confirmée.
La LED rouge frontale (3, fig.1) clignote proportionnellement à l’énergie active
mesurée.
Indicateur de séquence phase erronée (4, fig 1), le triangle de danger est affi-
ché en cas de séquence phases erronée (L2-L1-L3, L1-L3-L2).
BLOCAGE DE LA PROGRAMMATION
Il est possible de bloquer l’accès à la programmation au moyen d’un trimmer posi-
tionné derrière l’unité d’affichage amovible. Tourner à fond dans le sens des
aiguilles d’une montre le trimmer à l’aide d’un tournevis comme l’illustre la fig. 2
point 5.
PROGRAMMATION ET REMISE A ZERO
Pour accéder à la programmation complète de l’instrument, appuyer pendant au
moins 3 sec. sur la touche 2 (comme indiqué à la figure 1). Si l’on accède à la
programmation, toutes les fonctions de mesure et contrôle sont inhibées.
Pendant cette phase, le clignotement de la LED ne doit pas être pris en compte.
PASS? : en introduisant la valeur du mot de passe correct (par défaut 0), on
accède au menu principal.
CnGPASS: nouveau mot de passe, personnalise le mot de passe.
APPLiC.: sélectionne l’application pertinente. A: énergie active positive
(mesure de l’énergie active positive et quelques paramètres plus petits). B: comp-
teur d’énergie active positive et réactive positive (mesure des énergies actives et
réactives positives avec des paramètres plus petits). C: Montre tous les variables
électriques disponibles.
SYS : sélection du réseau électrique. 3P.n: triphasé déséquilibré avec
neutre; 3P: triphasé déséquilibré sans neutre; 3P: triphasé équilibré avec ou sans
neutre; 2P: biphasé; 1P: monophasé.
Ut rAt. : ratio TT (1,0 à 6,00k). Exemple: si le primaire du TT raccordé est de
5kV et le secondaire est de 100V, le ratio TT correspond à 50 (obtenu en effec-
tuant le calcul: 5000/100).
PuLSE: sélectionne le poids de l’impulsion (kWh par impulsion ; program-
mable de 0,01 à 9,99).
P. tESt: (SEULEMENT AVEC “APPLiC” C, voir menù n. 3), configure la valeur
de puissance (kW) simulée à laquelle correspondra une fréquence des impul-
sions proportionnelle à cette dernière en fonction du “PULSE”, la fonction est acti-
vée jusqu’à ce qu’on reste dans le menu.
tESt: (SEULEMENT AVEC “APPLiC” C, voir menù n. 3), activé sur la sortie
impulsion après avoir sélectionné ON.
Add. : (seulement avec option “IS”) adresse série (de 1 à 247).
EnE rES: mise à zero des tous les compteurs d’énergie totaux (SEULEMENT
AVEC “APPLiC” C).
End : pour revenir au mode mesure, appuyer sur la touche 2 (voir fig.1).
11
10
09
08
07
06
05
04
03
02
01
■ Panel frontal y configuración de valores (fig. 1)
En modalidad de medición: tecla 1, avanza por las páginas de medición. La
tecla 2, avanza por las páginas de información del equipo. Si se mantiene pulsa-
d
a la tecla 2 al menos 3 seg. se accede a la programación y configuración de
parámetros.
En modalidad programación: tecla 1, avanza por los menús o incrementa/dis-
minuye los valores a configurar. La tecla 2 permite acceder a los submenús y
cambia la modalidad de incremento de los valores de positiva a negativa y vice-
versa según la lógica indicada en la tabla 1: a, pulsando la tecla 2 aparece una
letra C en la línea inferior para indicar la posibilidad incrementar los valores
mediante la tecla 1. b, pulsando de nuevo la tecla 2 aparece -C en la línea infe-
rior para indicar la posibilidad de disminuir los valores mediante la tecla 1. c, Para
confirmar el valor seleccionado mantenga pulsada la tecla 2 hasta que el signo –
d
e la C desaparezca, así se habrá confirmado el valor.
El LED rojo frontal (3, fig.1) parpadea proporcionalmente al consumo de ener-
gía activa total importada.
Indicador de secuencia fase incorrecta (4, fig 1), el triángulo de peligro se
visualiza en caso de secuencia de fase incorrecta (L2-L1-L3, L1-L3-L2).
BLOQUEO DE LA PROGRAMACIÓN
Es posible bloquear el acceso a la programación mediante el conmutador situa-
do en la parte trasera del módulo display. Gire en sentido horario el conmutador
hasta su tope usando un destornillador adecuado como muestra la fig. 2 punto 5.
PROGRAMACIÓN Y PUESTA A CERO
Para entrar al modo de programación completo hay que pulsar la tecla 2
al menos 3 seg. (ver fig. 1). En el modo de programación completa del instrumen-
to, todas las medidas y las funciones de control están inhibidas. Durante esta
fase el parpadeo del LED no debe ser considerado.
PASS? : introduciendo la clave correcta (valor por defecto 0) se accede al
menú principal.
CnGPASS: permite cambiar la clave.
APPLiC.: permite seleccionar la aplicación correspondiente. A: activar el contador
de energía positiva (midiendo la energía activa positiva y algunos parámetros
menores). B: contador de energía activa positiva y reactiva positiva (midiendo la
energía activa y reactiva positiva con algunos parámetros menores). C: muestra
todas las variables eléctricas disponibles.
SYS : Permite seleccionar el sistema eléctrico. 3P.n: trifásico desequilibrado
con neutro; 3P: trifásico desequilibrado sin neutro; 3P.1: trifásico equilibrado con
o sin neutro; 2P: bifásico; 1P: monofásico.
Ut rAt. : relación del trafo de tensión VT (1,0 a 6,00k). Ej.: si el primario del
trafo conectado es 5kV y el secundario es 100V, la relación del trafo de tensión
es 50 (es decir, 5000/100).
PuLSE: selecciona el valor del pulso (kWh por pulso; programable de 0,01 a
9,99).
P. tESt: (SÓLO CON “APPLiC” C, ver menú n. 3), configura el valor de poten-
cia simulada (kW) a la que corresponderá una frecuencia de los pulsos propor-
cional a ésta en base a "PULSE". La función está activa mientras se permanece
en el menú.
tESt: (SÓLO CON “APPLiC” C, ver menú n. 3), activado en la salida de pulsos
cuando se selecciona ON.
Add. : (sólo opción IS”) permite seleccionar la dirección serie del instrumen-
to: de 1 a 247.
EnE rES: permite la puesta a cero de todos los contadores totales (SÓLO
CON “APPLiC” C).
End : permite salir del modo de programación pulsando la tecla 2 (ver fig. 1).
11
10
09
08
07
06
05
04
03
02
01
1.2.3...
3.2.1...
OK
1
2
3
a
b
c
5
fig. 1 fig. 2
t
ab. 1
3s
3s 3s 3s 3s 3s 3s 3s 3s 3s 3s
To measurement mode
Al modo misura
Zum Messmodus
Au mode mesure
En el modo de medición
3s
FRANçAIS ESPAÑOL
01 02 03 04 05 06 07 08 09 10 11
4
Transforming the instrument from DIN guide fitting to panel fit-
ting and vice versa.
To remove the display unit, by means of a screwdriver of suitable dimensions,
operate on slots (1 and 2) on the sides of the instrument, pressing the fastening
tabs (3 and 4), then carefully remove (5) the display unit.
To transform the instrument from panel fitting to DIN guide fitting,
rotate the measurement base from A to B.
To transform the instrument from DIN guide fitting to panel fitting,
rotate the measurement base from B to A.
To insert the display unit, gently push it (6) in its seat, as shown in the ima-
ges, until you hear the “clicks” of the elastic tabs (3 and 4) which signal the cor-
rect fitting in the slots (1 and 2).
Green LED, fig. C 1
If the instrument is used as converter, that is without display unit, the
green LED shows that the instrument is powered, if the LED flashes, it
shows that the instrument is connected to the serial network and is
communicating.
Trasformare lo strumento da montaggio a guida DIN a montag-
gio a pannello e viceversa.
Per togliere l’unità display, mediante un cacciavite a taglio di dimensioni ade-
guate agire sulle asole (1 e 2) ai lati dello strumento premendo le linguette di
fissaggio (3 e 4) , quindi estrarre (5) con cura l’unità display.
Per trasformare lo strumento da montaggio a pannello a guida DIN, girare
su se stessa la base di misura da A a B.
Per trasformare lo strumento da guida DIN a montaggio a pannello, girare
su se stessa la base di misura da B ad A.
Per inserire l’unità display, spingerla (6) delicatamente nella sede predispo-
sta, come illustrano le immagini a lato, fino a che si avvertiranno i “click” delle
linguette elastiche di fissaggio (3 e 4) a significare il corretto incastro delle stes-
se nelle asole (1 e 2) di chiusura.
LED verde, fig. C 1
Nel caso lo strumento sia utilizzato come convertitore, quindi senza
unità display, il LED verde indica la presenza dell’alimentazione, se il
LED è lampeggiante esso indica che lo strumento è collegato alla rete
seriale e sta comunicando.
Umwandlung der Gerätemontage von DIN Schiene in Tafel und
umgekehrt.
Zur Herausnahme der Anzeigeneinheit, mit einem entsprechend großen
Schlitzschraubenzieher durch die Ösen (1 und 2) an den Seiten des Geräts auf
die Befestigungszungen (3 und 4) drücken und dann die Anzeigeneinheit vorsi-
chtig herausziehen (5).
Zur Umwandlung der Gerätemontage von Tafel in DIN Schiene, die
Messbasis um sich selbst von A auf B drehen.
Zur Umwandlung der Gerätemontage von DIN Schiene in Tafel, die
Messbasis um sich selbst von B auf A drehen.
Zum Einsetzen der Anzeigeneinheit, diese (6) vorsichtig in das vorgesehene
Gehäuse schieben bis das “Klicken” der elastischen Befestigungszungen (3
und 4) zu hören ist, welches ihr korrektes Einrasten in den Verschlussösen (1
und 2) bedeutet.
Grüne LED-Leuchte, Abb. C 1
Wenn das Get als Wandler verwendet wird, also ohne
Anzeigeneinheit, zeigt die grüne LED-Leuchte die vorhandene
Speisung an, bei ihrem Blinken zeigt die LED-Leuchte auch an, dass
das Gerät an ein serielles Netz angeschlossen ist und gerade
kommuniziert.
DEUTSCH
ITALIANO
ENGLISH
Transformer l’instrument de montage en guide DIN en montage
à panneau et vice-versa.
Pour enlever l’unité d’affichage, à l’aide d’un tournevis à coupe de dimen-
sions adéquates, actionner les fentes (1 et 2) aux côtés de l’instrument en
appuyant sur les languettes de fixation (3 et 4) puis extraire (5) avec soin l’unité
display.
Pour transformer l’instrument de montage en panneau à guide DIN, tour-
ner sur elle-même la base de mesure de A à B.
Pour transformer l’instrument de guide DIN à montage en panneau, tour-
ner sur elle-même la base de mesure de B à A.
Pour insérer l’unité d’affichage, la pousser (6) délicatement dans le siège
prédisposé comme les images sur le côté l’illustrent jusqu’à ce qu’on avertisse
les “clics” des languettes élastiques de fixation (3 et 4) ce qui signifie l’encastre-
ment correct de celles-ci dans les fentes (1 et 2) de fermeture.
LED vert, fig. C 1
Dans le cas l’instrument est utilisé en tant que convertisseur et donc
sans unité display, le LED vert indique la présence de l’alimentation si
le LED clignote, cela indique aussi que l’instrument est branché au
réseau sériel et qu’il communique.
Transformar el montaje a carril DIN en montaje a panel y vice-
versa.
Para retirar el módulo display, mediante un destornillador adecuado, accio-
nar en las ranuras (1 y 2) a los lados del equipo presionando las lengüetas de
fijación (3 y 4) y extrayendo (5) con cuidado el módulo display.
Para transformar el montaje en panel a montaje en carril DIN, gire sobre sí
misma la base de A a B.
Para transformar el montaje a carril DIN en montaje a panel, gire sobre
misma la base de B a A.
Para introducir el módulo display, empújelo (6) delicadamente en el hueco
correspondiente, como ilustran las imágenes que aparecen a la izquierda,
hasta que oiga los “clic” de las lengüetas de fijación (3 y 4) que indican que se
han introducido correctamente en los orificios (1 y 2) de cierre.
LED verde, fig. C 1
En caso de que el equipo se use como convertidor, por lo tanto sin
display, el LED verde indica que el equipo está alimentado, si el LED
parpadea indica también que el equipo está conectado a la red en
serie y que está comunicando.
FRANçAIS
ESPAÑOL
123456,7 kWh
12,3 kW sys
1
23456,7 kvarh
12,3 kvar sys
0.98 L PF sys
50 Hz sys
0
.98 L PF L1
0
.97 L PF L2
0.96 L PF L3
400 V L1-2
4
00 V L2-3
4
00 V L3-1
230 V L1
230 V L2
230 V L3
Measuring pages.
Pagine di misura.
Meßseiten.
Pages de mesure.
Páginas de medida.
MEASURING MODE, MODO MISURA,
PROGRAMMIERMODUS, MODO DE MISURE,
MODO DE MEDIDA
Information pages.
Pagine informative.
Informationsseiten.
Pages d’information.
Páginas de información.
Year of production (Y. 2008) and firmware release (r.A0).
Anno di produzione (Y. 2008) e versione del firmware (r.A0).
Herstellungsjahr (Y. 2008) und Version der Firmware (r.A0). Année de
production (Y. 2008) et version firmware (r.A0).
Año de fabricación (Y. 2008) y versión del firmware (r.A0).
kWh per pulse (LED).
kWh per impulso (LED).
kWh pro Impuls (LED).
kWh par impulsion (LED).
kWh por pulso (LED).
Type of system (SYS 3P.n) and type of connection (4 wires).
Tipo di sistema (SYS 3P.n) e tipo di collegamento (4fili).
Systemtyp (SYS 3P.n) und Anschlusstyp (4 Adern).
Type de système (SYS 3P.n) et type de branchement (4 câbles).
Tipo de sistema (SYS 3P.n) y tipo de conexión (4 hilos).
Primary current transformer value.
Valore del primario del trasformatore di corrente.
Stromwandler-Verhältnis.
Ratio de transformateur ampèremètre.
Relación del transformador de corriente.
Voltage transformer ratio.
Rapporto di trasformazione voltmetrica.
Spannungswandler-Verhältnis.
Ratio de transformateur de tension.
Relación del transformador de tensión.
Pulse output: kWh per pulse.
Uscita impulsi: kWh per impulso.
Impulsausgang: kWh pro Impuls.
Sortie impulsions: kWh par impulsion.
Salida pulsos: kWh por pulso.
Serial communication address.
Indirizzo di comunicazione seriale.
Serielle Kommunikationsadresse.
Adresse de communication sériel.
Dirección de comunicación serie.
A
B
1
2
4
3
5
6
1
2
4
3
5
6
C
1
1
0.0 A L1
10.0 A L2
10.0 A L3
APPLiC : A B C B C A B C C C C C
Available variables only with RS485.
Variabili disponibili solo da RS485.
Vorhandene Variablen nur mit RS485.
Variables disponibles seulement avec RS485.
Variables disponibles sólo con RS485.
V L-N sys, V L-L sys, VA sys, VA L1, VA L2, VA
L3, var L1, var L2, var L3, W L1, W L2, W L3.
In case of wrong phase sequence.
In caso di sequenza fasi errata.
Bei falscher Phasenfolge.
En cas de séquence phases erronée.
En caso de secuencia de fase incor-
r
ecta.
Phase to phase voltage
L1-2, L2-3, L3-1.
Tensioni concatenate
L1-2, L2-3, L3-1.
Spannung Phase-Phase
L1-2, L2-3, L3-1.
Tension phase-phase
L1-2, L2-3, L3-1.
Tensión entre fases
L1-2, L2-3, L3-1.
System values.
Valori di sitema.
Systemwerte.
Valeurs de système.
Valores del sistema.
V
R
S
4
85
Op
to
-
m
o
sf
et
CARLO GAVAZZI
A u t o m a t i o n C o m p o n e n t s
C
arlo Gavazzi Controls SpA,
V
ia Safforze, 8 - 32100
Belluno (Italy)
T
el. +39 0437 355811,
F
ax +39 0437 355880
E
M21 72R IM ML 8021723 210917
EM21 72R
3-phase Energy Meter for Retro-fit‰
I
N/OUT
VDC/AC
9
8
7 10
6
54
3
21
9
8710
6
5
4
321
9
8710
6
54
321
9
8
7 10
6
5
9
8710
6
5
9
8 10
6
5
4
3
9
8
10
6
5
4
3
9
1
0
6
5
9
10
6
5
16
15
14
13
B+
A-
16
15
14
13
B+
A-
B+
A-
17 18
DIN
68x68mm
-0 +0.7mm
6A System type selection 3P.n
[1]- 3-ph, 4-wire, unbalanced load, 3-CT connection.
[2]- 3-ph, 4-wire, unbalanced load, 3-CT and 3-VT/PT
connections
6A System type selection 3P
[3]- 3-ph, 3-wire, unbalanced load, 3-CT connection.
[4]- 3-ph, 3-wire, unbalanced load, 3-CT and 2-VT/PT
connections
6A System type selection 3P.1
[5]- 3-ph, 3-wire, balanced load, 1-CT connection (if the neutral is available
the voltage connection can be realized to only 2-wire VL1 and N).
[6]- 3-ph, 3-wire, balanced load, 1-CT and 2-VT/PT connection.
6A System type selection 2P
[7]- 2-ph, 3-wire, 2-CT connection.
[8]- 2-ph, 3-wire, 2-CT and 2-VT/PT connections
6A System type selection 1P
[9]- 1-ph, 2-wire, 1-CT connection.
[10]- 1-ph, 2-wire, 1-CT and 1-VT/PT connection
Static output and serial port
[11]- Opto-mosfet static output
[12]- RS485 connection 2 wires [a]- last instrument,
[b]- instrument 1...n, [c]- RS485/RS232 transducer.
(*) NOTE: For a correct power supply of the instrument, the neutral must
always be connected.
ENGLISH
6A, selezione sistema tipo 3P.n
[1]- 3 fasi, 4 fili, carico squilibrato, connessione da 3 TA.
[2]- 3 fasi, 4 fili, carico squilibrato, connessione da 3 TA e 3 TV
6A, selezione sistema tipo 3P
[3]- 3 fasi, 3 fili, carico squilibrato, connessione da 3 TA.
[4]- 3 fasi, 3 fili, carico squilibrato, connessione da 3 TA e 2 TV
6A, selezione sistema tipo 3P.1
[5]- 3 fasi, 3 fili, carico equilibrato, connessione da 1 TA (se il neutro è dispo-
nibile il collegamento voltmetrico può essere realizzato a soli 2 fili VL1 e
N).
[6]- 3 fasi, 3 fili, carico equilibrato, connessione da 1 TA e 2TV.
6A, selezione sistema tipo 2P
[7]- 2 fasi, 3 fili, connessione da 2 TA.
[8]- 2 fasi, 3 fili, connessione da 2 TA e 2 TV
6A, selezione sistema tipo 1P
[9]- 1 fase, 2 fili, connessione da 1 TA.
[10]- 1 fase, 2 fili, connessione da 1 TA e 1 TV
Uscita statica e porta seriale
[11]- Uscita statica a opto-mosfet
[12]- RS485 connessione a 2 fili [a]- ultimo strumento,
[b]- strumento 1...n, [c]- convertitore RS485/RS232.
(*) NOTA: Per poter alimentare correttamente lo strumento, il neutro deve
sempre essere collegato.
ITALIANO
6A Systemwahl: 3P.n
[1]- 3-ph, 4-Adrig, asymmetrische Last, 3 Stromwandleranschluss.
[2]- 3-ph, 4-Adrig, asymmetrische Last, 3 Strom- und 3
Spannungswandleranschlüsse
6A Systemwahl: 3P
[3]- 3-ph, 3-Adrig, asymmetrische Last, 3 Stromwandleranschlüsse.
[4]- 3-ph, 3-Adrig, asymmetrische Last, 3 Strom- und 2
Spannungswandleranschlüsse
6A, Systemwahl: 3P.1
[5]- 3-ph, 3-Adrig, symmetrische Last, 1-Stromwandleranschluss (wenn der
Nullleiter verfügbar ist, kann der Voltmeteranschluss mit nur 2 Adern VL1
und N vorgenommen werden).
[6]- 3-ph, 3-Adrig, symmetrische Last, 1-Stromwandleranschluss und 2
Spannungswandleranschlüsse
6A, Systemwahl: 2P
[7]- 2-ph, 3-Adrig, 2 Stromwandleranschlüsse.
[8]- 2-ph, 3-Adrig, 3-Strom- und 2 Spannungswandleranschlüsse
6A, Systemwahl: 1P
[9]- 1-ph, 2-Adrig, 1-Stromwandleranschluss.
[10]- 1-ph, 2-Adrig, 1-Stromwandleranschluss und 1
Spannungswandleranschlüsse
Uscite und serielle Schnittstelle
[11]-
Statischer Ausgang mit Opto-Mosfet
[12]- RS485-Anschlüsse, 2-Adrig [a]- letzte Gerät, [b]- Gerät 1...n,
[c]- RS485/RS232 Umformer.
(*) HINWEIS: Der Neutralleiter muss angeschlossen sein, um eine
korrekte Spannungsversorgung des Instrumentes zu gewährleisten.
DEUTSCH
6A Sélection du type de réseau: 3P.n
[1]- 3 phases, 4 câbles, charge déséquilibrée, connexions 3 TC.
[2]- 3 phases, 4 câbles, charge déséquilibrée, connexions 3 TC et 3TT/TP
6A Sélection du type de réseau: 3P
[3]- 3 phases, 3 câbles, charge déséquilibrée, connexions 3 TC.
[4]-
3 phases, 3 câbles, charge déséquilibrée, connexions 3 TC et 2 TT/TP
6A Sélection du type de réseau: 3P.1
[5]- 3 phases, 3 câbles, charge équilibrée, connexions 1 TC ) (si le neutre est
disponible, le branchement voltmétrique peut être réalisé à seulement 2
fils VL1 et N).
[6]- 3 phases, 3 câbles, charge équilibrée, connexions 1 TC et 2 TT/TP
6A Sélection du type de réseau: 2P
[7]- 2 phases, 3 câbles, connexions 2 TC.
[8]- 2 phases, 3 câbles, connexions 3 TC et 2 TT/TP
6A Sélection du type de réseau: 1P
[9]- 1 phases, 2 câbles, connexions 1 TC.
[10]- 1 phases, 2 câbles, connexions 1 TC et 1 TT/TP
Sorties et port série
[11]-
Sortie statique en opto-mosfet
[12]- Connexion RS485 2 câbles [a]- dernier instrument,
[b]- instrument 1...n, [c]- Transducteur RS485/RS232.
(*) NOTE: Pour une alimentation correcte de l'instrument, le neutre doit tou-
jours être relié.
FRANçAIS
6A, selección del sistema: 3P.n
[1]- Trifásico, 4 hilos, carga desequilibrada, conexión 3 trafos de
intensidad.
[2]- Trifásico, 4 hilos, carga desequilibrada, conexión 3 trafos
de intensidad y 3 trafos de tensión/potencia.
6A, selección del sistema: 3P
[3]- Trifásico, 3 hilos, carga desequilibrada, conexión 3 trafos
de intensidad.
[4]- Trifásico, 3 hilos, carga desequilibrada, conexión
3 trafos de intensidad y 2 trafos de tensión/potencia.
6A, selección del sistema: 3P.1
[5]-Trifásico, 3 hilos, carga equilibrada, conexión 1 trafo de intensidad (Si el
neutro está disponible, la conexión de la tensión puede realizarse con
sólo 2 hilos VL1 y N).
[6]- Trifásico, 3 hilos, carga equilibrada, conexión 1 trafo de
intensidad y 2 trafos de tensión/potencia.
6A, selección del sistema: 2P
[7]- Bifásico, 3 hilos, conexión 2 trafos de intensidad.
[8]- Bifásico, 3 hilos, conexiones 2 trafos de intensidad y
2 trafos de tensión/potencia.
6A, selección del sistema: 1P
[9]- Monofásico, 2 hilos, conexión 1 trafo de intensidad.
[10]- Monofásico, 2 hilos, conexión 1 trafo de intensidad y
1 trafo de tensión/potencia.
Salidas y puerto serie
[11]-
Salida estática opto-mosfet
[12]-RS485, conexión dos hilos [a]- último instrumento,
[b]- instrumento 1...n, [c]- transductor RS485/RS232.
(*) NOTA: Para la correcta alimentación del instrumento, el neutro debe estar
siempre conectado.
ESPAÑOL
[1] [2] [3]
[4]
[5] [6]
[7] [8] [9]
[10]
[a]
[12]
[b] [c]
[11]
F=315mA
9
8
7 10
6
54
3
21
(*)
(*)
(*)
WARNING! Before closing the CT, make sure that the surfaces of the iron
core (exposed when the CT is open) of the current transformer are not dirty
or damaged. Ensure the proper closure of the CT. Use CT on power cables
(primary) with isolation of at least 1500VAC. Arrange the connecting CT
cables in a proper way in order to limit electromagnetic coupling noise.
ATTENZIONE! Prima della chiusura del TA, assicurarsi che le superfici
del nucleo (esposto quando il TA è aperto) del trasformatore amperometrico
non siano sporche o danneggiate.
Assicurarsi della corretta chiusura del TA. Utilizzare i TA su cavi di corrente
(primario) aventi isolamento di almeno 1500VCA. Disporre i cavi di collega-
mento dei TA in modo da limitare l’accoppiamento di disturbi di tipo elettroma-
gnetico.
VORSICHT! Vor dem Schließen der Stromwandler ist sicherzustellen,
dass die Oberflächen des Eisenkerns (wenn die CT geöffnet ist) des
Stromwandlers nicht verschmutzt oder beschädigt ist. Gewährleisten Sie ein
ordnungsgemäßes Schließen der Stromwandler.
Verwenden Sie die Stromwandler auf Stromkabel (primär) mit Isolierung von
min. 1500VAC. Verlegen Sie die CT Kabel in geeigneter Weise um elektro-
magnetische Störungen zu vermeiden.
ATTENTION! Afin de fermer le transformateur d'intensité, s'assurer que
les surfaces du noyau ferreux (surfaces apparentes lorsque le TI est ouvert)
ne sont ni sales ni endommagées. S'assurer de la bonne fermeture du tran-
sformateur d'intensité. Utiliser le TI sur des câbles de puissance (primaires)
avec une isolation minimale de 1500 VCA. Ordonner les câbles de connexion
au mieux pour limiter les bruits électromagnétiques.
¡ADVERTENCIA! Antes de cerrar el trafo de intensidad, asegurarse de
que las superficies de su núcleo (expuestas cuando el trafo está abierto) no
estén sucias o dañadas. Cerrar bien el trafo de intensidad. Usar el trafo con
cables de potencia (primario) con aislamiento de al menos 1500VCA.
Realizar la conexión de los cables del trafo de intensidad correctamente para
limitar el ruido por acoplamiento electro-magnético.
72x72
The provided current transformers MUST be
connected so to match with the measuring
inputs, that is CT
I1 with input I1, CT I2 with
input I2 and CT I3 with input I3.
!
I trasformatori di corrente forniti DEVONO essere
collegati rispettando la corrispondenza con gli
ingressi di misura, ovvero TA I1 con ingresso I1,
TA I2 con ingresso I2 e TA I3 con ingresso I3.
!
La intensidad suministrada por los transforma-
dores DEBE estar conectada a las corres-pon-
dientes entradas de medida, es decir: CT I1 con
entrada I1, CT I2 con entrada I2 y CT I3 con
entrada I3.
!
Les transformateurs de courant doivent OBLIGA-
TOIREMENT être raccors de cette manière afin
de correspondre aux mesures d'entrées; soit I1 du
TI sur entrée I1, I2 TI sur entrée I2 et I3 du TI sur
entrée I3.
!
Die vorgesehenen Stromwandler MÜSSEN so
verbunden werden, dass die Eingänge I1 des
CT1 mit I1, C2 mit I2 und C3 mit I3.
!
NORMAS DE SEGURIDAD
L
ea el manual y siga atentamente las instrucciones. Si se utiliza el equi-
po de manera distinta de como indica el fabricante, se puede dañar la pro-
tección de la que está provisto. Mantenimiento: Asegurarse de que las
conexiones son correctas para evitar un mal funcionamiento o daños en el
i
nstrumento. Para tener el instrumento limpio, limpiar periódicamente la carcasa con un
t
rapo un poco humedecido. No utilizar productos abrasivos o disolventes. Desconectar el
e
quipo antes de limpiarlo.
ESPECIFICACIONES TÉCNICAS
E
ntradas nominales: tipo de sistema: trifásico. Tipo de intensidad: no aislada (mediante
C
T). Nota: los transformadores de intensidad externos (CT) pueden ser conectados a tie-
rra individualmente. Escala de intensidad (mediante trafos de intensidad) VV2: 90A, VV3:
150A, VV5: 250A. Tensión (continua o por VT/PT) VVx: 400V
LL
. Precisión (Display +
RS485) (@25°C ±5°C, R.H. 60%, 48 a 62 Hz) Iref: ver a continuación, Vn: ver a conti-
nuación. Escala de tensión modelo VVx Vn: 160 a 260VLN (277 a 450VLL). Escala de
i
ntensidad modelo VV2 Iref: 15A, Imax: 90A, modelo VV3 Iref: 20A, Imax: 150A, modelo
V
V5 Iref: 20A, Imax: 250A. Intensidad de 0,05Iref a 0,1Iref: ± (1% lec. + 3dig.). De 0,1Iref
a
Imax: ± (1% lec. + 1dig.). Tensión entre fase y neutro en la escala Vn: ±(0,5% lec. +
1dig.). Tensión entre fases en la escala Vn: ±(1% lec. + 1dig.). Frecuencia intervalo: 45 a
65Hz; Resolución: ±1Hz. Potencia activa: ±(2% lec. + 2dig). Factor de potencia: ±[0,001
+ 1%(1,000 – lec. PF)]. Potencia reactiva: ±(2% lec. + 2dig.). Energía activa: clase A según
norma EN50470-3. Energía reactiva: clase 2 según norma EN62053-23. Intensidad de
a
rranque: VV2, VV3: 10mA. VV5: 50mA. Deriva térmica ≤200ppm/°C @ PF=1. Error de
f
ase: 0.05/°C. Frecuencia de muestreo: 1600 lecturas/s a 50Hz 1900 lecturas/s a 60Hz.
Frecuencia de muestreo: 1600 lecturas/s a 50Hz 1900 lecturas/s a 60Hz. Tiempo de
refresco del display: 1 segundo. Display: 2 líneas primera línea: 7 dígitos, segunda
línea: 3 dígitos o primera línea: 3 + 3 dígitos, segunda línea: 3 dígitos. Tipo LCD, altura 7
mm. Lectura de variables instantáneas 3 dígitos. Energía consumida: 6 + 1 dígitos indica-
ción de sobrerrango. Indicación EEE cuando el valor medido excede la “Capacidad de
e
ntrada de forma continua” (capacidad máxima de medida). Indicación máx. y mín.
V
ariables instantáneas máximas: 999; energías: 999, 999.9 o 9 999 999. Variables instan-
táneas mínimas: 0; energías: 0,0. LEDs. LED rojo (consumo de energía) 0,01 kWh por
pulso si la relación del trafo de tensión VT es <4 (VV2) o <2 (VV3 o VV5); 0,1 kWh por
pulso si la relación del trafo de tensión VT es <40 (VV2) o <23 (VV3 o VV5); 1kWh por
pulso si la relación del trafo de tensión VT es >40 (VV2) o >23 (VV3 o VV5). Frecuencia
máxima 16Hz, según norma EN50470-3. El LED verde (junto a los bloques de terminales)
i
ndica el estado de la alimentación (estable) y de la comunicación: RX-TX parpadeando
(
sólo en caso de la opción RS485). Medidas: medida TRMS de tensión/intensidad de una
onda distorsionada. Tipo de conexión mediante CTs externos. Factor de cresta: ≤3 (VV2:
230A pico máx.). Protección contra sobreintensidades: sin medición válida.
Permanente VV2: 120A, VV3: 300A, VV5: 360A. Protección contra sobretensiones: per-
manente 1,2 Vn durante 500ms 2 Vn. Impedancia de entrada (tensión): autoalimenta-
ción eléctrica consumo de energía: <2VA. Frecuencia: 45 a 65 Hz. Teclado: dos pulsado-
res para selección de variables y programación de los parámetros de trabajo del instru-
mento. Salida de pulso: Número de salidas 1. Tipo programable de 0,01 a 9,99 kWh por
pulso. Salida conectable a los contadores de energía eléctrica (kWh). Duración del pulso
≥100ms <120ms (ON), ≥120ms (OFF), según norma EN62052-31. Salida estática: opto-
mosfet. Carga V
ON
2.5 VCA/CC máx. 70 mA, V
OFF
260 VCA/CC máx. Aislamiento mediante
optoacopladores, 4000 VRMS entre salida y entradas de medida. RS485 tipo multidrop,
bidireccional (variables estáticas y dinámicas). Conexiones 2 hilos. Distancia máx. 1000m,
terminación directamente en el instrumento. Direcciones 247, seleccionables mediante el
teclado frontal. Protocolo MODBUS/JBUS (RTU). Datos: Dinámicos (solo lectura).
Estáticos (lectura y escritura). Todos los parámetros de configuración. Formato de datos 1
bit inicial, 8 bits de datos, sin paridad, 1 bit final. Velocidad en baudios 9600 bits/s.
Capacidad de entrada de driver 1/5 carga unitaria. Máximo 160 transceptores en el mismo
bus. Aislamiento mediante optoacopladores, 4000 VRMS entre salida y entrada de medi-
da. Relación del transformador: VT (PT) 1,0 a 99,9 / 100 a 999 / 1,00k a 6,00k. CT pri-
mario: 90, 150 o 250A. La potencia máxima medida no puede sobrepasar de 210 MW cal-
culada como la tensión e intensidad máximas de entrada. Temperatura de funcionamien-
to: -20ºC a +50ºC (-13ºF a 131ºF) (HR de 0 a 90% sin condensación a 40ºC). Temperatura
de almacenamiento: -30ºC a +70ºC (-22ºF a 158ºF) (HR < 90% sin condensación a 40ºC).
Categoría de la instalación: Cat. III (IEC60664, EN60664). Aislamiento (durante 1 minu-
to) 4000 VRMS entre entradas de medida y salida digital. Resistencia dieléctrica: 4000
VRMS durante 1 minuto. Rechazo al ruido CMRR 100 dB, 48 a 62 Hz. Compatibilidad
electrom. (EMC) según norma EN62052. Descargas electrostáticas descarga en el aire
15kV; inmunidad a los campos electromagnéticos prueba con corriente: 10V/m de 80 a
2000MHz; prueba sin corriente: 30V/m de 80 a 2000MHz; ráfagas en el circuito de entradas
de medida de intensidad y tensión: 4kV. Inmunidad a las perturbaciones conducidas 10V/m
de 150KHz a 80MHz. Pico de tensión: en el circuito de entradas de medida de intensidad y
tensión: 6kV. Emisiones de radiofrecuencia según norma CISPR 22. Conformidad con las
normas: Seguridad IEC60664, IEC61010-1 EN60664, EN61010-1 EN62052-11. Metrología
EN62053-23, EN50470-3. Salida de pulso DIN43864, IEC62053-31. Homologaciones: CE.
Conexiones: a tornillo. Sección del cable 2,4 x 3,5 mm. Par de apriete mín./máx.: 0,4 Nm /
0,8 Nm. Caja: Dimensiones (An. x Al. x P.) 72 x 72 x 65 mm. Material Noryl PA66, autoextin-
guible: UL 94 V-0. Montaje en panel y a carril DIN. Grado de protección: Panel frontal IP40.
Conexiones IP20. Peso: Aprox. 400 g (embalaje incluido). Autoalimentación: 18 a
260VCA (48-62Hz) (VL1-N). Consumo de potencia: 20VA/1W.
ESPAÑOL
SAFETY PRECAUTIONS
R
ead carefully the instruction manual. If the instrument is used in a man-
ner not specified by the producer, the protection provided by the instrument
may be impaired.
Maintenance: make sure that the connections are correctly carried out in
o
rder to avoid any malfunctioning or damage to the instrument. To keep the instrument
c
lean, use a slightly damp cloth; do not use any abrasives or solvents. We recommend to
d
isconnect the instrument before cleaning it.
TECHNICAL SPECIFICATIONS
Rated inputs: System type: 3.
Current range (by CT) VV2: 90A,
V
V3: 150A, VV5: 250A. Voltage (direct or by VT/PT). VVx: 400VLL. Accuracy (Display + RS485)
I
ref: see below; Un: see below (@25°C ±5°C, R.H. 60%, 48 to 62 Hz). Voltage range VVx model
Un: 160 to 260VLN (277 to 450VLL). Current range VV2 model Iref: 15A, Imax: 90A, VV3 model
Iref: 20A, Imax: 150A, VV5 model Iref: 20A, Imax: 250A. Current From 0,05Iref to 0,1Iref: ± (1%
R
DG + 3DGT). Phase-neutral voltage In the range Un:
±(0.5% RDG +1DGT). Phase-phase voltage In the range Un: ±(1% RDG +1DGT). Frequency
Range: 45 to 65Hz; resolution: ±1Hz. Active power: ±(2%RDG +2DGT). Power Factor:
±
[0.001+2%(1.000 - “PF RDG”)]. Reactive power: ±(3%RDG +2DGT). Active energy class A
according to EN50470-3; class 2 according to EN62053-21. Start up current VV2: 75mA. VV3,
VV5: 100mA.
T
emperature drift: 200ppm/°C @ PF=1. Phase error: 0.05/°C. Sampling
r
ate: 1600 samples/s @ 50Hz, 1900 samples/s @ 60Hz. Display refresh time: 1 second.
Display: 2 lines 1
st
line: 7-DGT, 2
nd
line: 3-DGT or 1
st
line: 3-DGT + 3-DGT, 2
nd
line: 3-
DGT. Type LCD, h 7mm. Instantaneous variables read-out 3-DGT. Energies: imported,
Total: 6+1DGT (or 7 DGT). Overload status EEE indication when the value being measured
is exceeding the “Continuous inputs overload” (maximum measurement capacity). Max.
a
nd Min. indication: Max. instantaneous variables: 999; energies: 999 999.9 or 9 999 999
(
positive only). The negative energy is neither metered nor subtracted. Min. instantaneous
variables: 0; energies 0.0. LEDs. Red LED (Energy consumption) 0.01 kWh by pulse if VT
ratio is <4 (VV2) or <2 (VV3 or VV5) 0.1 kWh by pulse if VT ratio is <40 (VV2) or <23 (VV3
or VV5) 1kWh by pulse if VT ratio is >40 (VV2) or >23 (VV3 or VV5). Max frequency: 16Hz,
according to EN50470-3. Green LED (on the terminal bolcks side) for power on (steady)
and communication status: RX-TX (in case of RS485 option only) blinking.
M
easurements: Method TRMS measurements of distorted wave forms. Coupling type: by
m
eans of external CT’s. Crest factor:3 (VV2: 230A max. peak). Current Overloads:
without valid measurement. Continuous VV2: 120A, VV3: 300A, VV5: 360A. Voltage
Overloads: continuous 1.2 Un. For 500ms 2 Un. Voltage input impedance: self-power
supply power consumption: <2VA. Frequency : 45 to 65 Hz. Key-pad: two push buttons
for variable selection and programming of the instrument working parameters. Pulse out-
put Number of outputs 1. Type programmable from 0.01 to 9.99 kWh per pulses. Output
connectable to the energy meters (kWh). Pulse duration ≥100ms < 120ms (ON), ≥120ms
(OFF), according to EN62052-31. Output Static: opto-mosfet. Load V
ON
2.5 VAC/DC max.
70 mA, V
OFF
260 VAC/DC max. Insulation by means of optocuplers, 4000 VRMS output to
measuring inputs. RS485 type Multidrop, bidirectional (static and dynamic variables).
Connections 2-wire. Max. distance 1000m, termination directly on the instrument.
Addresses 247, selectable by means of the front keypad. Protocol MODBUS/JBUS (RTU).
Data: Dynamic (reading only) single phase and system values. Static (reading and writ-
ing). All the configuration parameters. Data format 1 start bit, 8 data bit, no parity,1 stop bit.
Baud-rate 9600 bits/s. Driver input capability 1/5 unit load. Maximum 160 transceivers on
the same bus. Insulation by means of optocouplers, 4000 VRMS output to measuring input.
Transformer ratio: VT (PT) 1.0 to 99.9 / 100 to 999 / 1.00k to 6.00k CT: fixed primary: 90,
150 or 250A. The maximum power being measured cannot exceed 210 MW calculated as
maximum input voltage and current. Operating temperature -20°C to +50°C (-13°F to
131°F) (R.H. from 0 to 90% non-condensing @ 40°C). Storage temperature -30°C to
+70°C (-22°F to 158°F) (R.H. <90% non-condensing @ 40°C). Installation category Cat.
III (IEC60664, EN60664). Insulation (for 1 minute) 4000 VRMS between measuring
inputs and digital output. Dielectric strength 4000 VRMS for 1 minute. Noise rejection
CMRR 100 dB, 48 to 62 Hz. EMC According to EN62052-11. Electrostatic discharges 15kV
air discharge; Immunity to irradiated test with current: 10V/m from 80 to 2000MHz;
Electromagnetic fields test without any current: 30V/m from 80 to 2000MHz; Burst on cur-
rent and voltage measuring inputs circuit: 4kV. Immunity to conducted disturbances 10V/m
from 150KHz to 80MHz. Surge on current and voltage measuring inputs circuit: 6kV; Radio
frequency suppression according to CISPR 22. Standard compliance: safety IEC60664,
IEC61010-1 EN60664, EN61010-1 EN62052-11. Metrology EN62053-21, EN62053-23,
EN50470-3. Pulse output DIN43864, IEC62053-31. Approvals: CE. Connections: Screw-
type. Cable cross-section area: 2,4 x 3,5 mm. Min./Max. screws tightening torque: 0.4 Nm
/ 0.8 Nm. Housing: dimensions (WxHxD) 72 x 72 x 65 mm. Material Noryl PA66, self-extin-
guishing: UL 94 V-0. Mounting: panel and DIN-rail. Protection degree: front IP40. Screw
terminals: IP20. Weight: approx. 400 g (packing included). Self power supply 18 to
260VAC (48-62Hz) (VL1-N). Power consumption: 20VA/1W.
ENGLISH
NORME DI SICUREZZA
L
eggere attentamente il manuale istruzioni. Qualora l’apparecchio venis-
se adoperato in un modo non specificato dal costruttore, la protezione previ-
sta dall’apparecchio potrebbe essere compromessa. Manutenzione: assicu-
rarsi che i collegamenti siano effettuati correttamente al fine di evitare qual-
s
iasi malfunzionamento o danneggiamento dello strumento. Per mantenere pulito lo stru-
m
ento usare un panno leggermente inumidito; non usare abrasivi o solventi. Si consiglia di
s
collegare lo strumento prima di pulirlo.
CARATTERISTICHE TECNICHE
Ingressi di misura. Sitema: 3-fase. Tipo corrente: non isolato (mediante TA). Nota: i tra-
s
formatori di corrente esterni possono essere collegati a terra individualmente. Portata cor-
r
ente (mediante sensore di corrente) VV2: 90A. VV3: 150A. VV5: 250A. Tensione (diretto
o
mediante TA/TV) VVx: 400VLL. Precisione (Display + RS485) Iref: vedi sotto, Un: vedi
sotto (@25°C ±5°C, U.R. 60%, da 48 a 62 Hz). Portata tensione Modello VVx Un: 160 a
260VLN (277 a 450VLL). Portata corrente Modello VV2 Iref: 15A, Imax: 90A. Modello VV3
Iref: 20A, Imax: 150A. Modello VV5 Iref: 20A, Imax: 250A. Corrente: da 0,05Iref a 0,1Iref:
± (1% RDG + 3DGT). Da 0,1Iref a Imax: ± (1% RDG + 1DGT). Tensione fase-neutro: nel
c
ampo Un: ±(0,5% RDG +1DGT). Tensione fase-fase: nel campo Un: ±(1% RDG +1DGT).
F
requenza Campo: da 45 a 65Hz; risoluzione: ±1Hz. Potenza attiva: ±(2%RDG +2DGT).
F
attore di potenza: ±[0,001+1%(1,000 - “cosj RDG”)]. Potenza reattiva: ±(3%RDG
+2DGT). Energia attiva: classe A secondo EN50470-3; classe 2 secondo EN62053-21.
Corrente di avviamento VV2: 75mA. VV3, VV5: 100mA. Deriva termica: 200ppm/°C @
PF=1 errore fase: 0.05/°C. Frequenza di campionamento: 1600 campioni/s @ 50Hz,
1900 campioni/s @ 60Hz. Tempo di aggiornamento display: 1 secondo. Display: 2
l
inee, 1
a
l
inea: 7-DGT, 2
a
l
inea: 3-DGT o 1
a
l
inea: 3-DGT + 3-DGT, 2
a
l
inea: 3-DGT. Tipo
L
CD, h 7mm. Lettura variabili istantanee 3-DGT. Energie Importate totali: 6+1DGT
(07DGT). Sovraccarico indicazione EEE quando il valore misurato eccede il “sovraccarico
continuo d’ingresso” (massima capacità di misura). Indicazione Max. e Min. Max. variabili
istantanee: 999; energie: 999 999,9 o 9 999 999 (solo positive). L’energia negativa non
viene conteggiata ne sottratta. Min. variabili istantanee: 0; energie 0,0. LED rosso (energia
consumata) 0,01 kWh per impulso se il rapporto TV è <4 (VV2) o <2 (VV3 o VV5) 0,1 kWh
p
er impulso se il rapporto TV è <40 (VV2) o <23 (VV3 o VV5) 1kWh per impulso se il rap-
p
orto TV è >40 (VV2) o >23 (VV3 o VV5). Frequenza massima 16Hz, secondo EN50470-
3. LED verde (posizionato vicino alla morsettiera di collegamento) luce fissa relativo allo
stato di “strumento acceso”, a luce lampeggiante in caso di comunicazione RS485 presen-
te e operativa. Misure: Metodo: misura TRMS delle forme d’onda distorte. Tipo di accop-
piamento mediante TA esterni. Fattore di cresta3 (VV2: 230A picco max.) Sovraccarico
corrente senza misurazione valida Continuo VV2: 120A. VV3: 300A.VV5: 360A
S
ovraccarico tensione: continuo 1,2 Un. Per 500ms 2 Un. Impedenza d’ingresso ten-
sione: autoalimentazione, autoconsumo: <2VA. Frequenza: da 45 a 65 Hz. Tastiera fron-
tale: Due tasti per la selezione delle variabili per la programmazione dei parametri di fun-
zionamento dello strumento. Uscite digitali: Numero d’uscite 1. Tipo programmabile da
0,01 a 9,99 kWh per impulso. Uscita associabile al contatore di energia (kWh). Durata
dell’impulso ≥100ms <120ms (ON), ≥120ms (OFF), secondo EN62052-31. Uscita statica:
opto-mosfet. Carico V
ON
2,5 VCA/CC max. 70 mA, V
OFF
260 VCA/CC max. Isolamento
mediante optoisolatori, 4000 VRMS fra uscita ed ingressi di misura. RS485 tipo multidrop,
bidirezionale (variabili statiche e dinamiche). Connessione 2 fili. Distanza massima 1000m,
terminazione direttamente sullo strumento. Indirizzi 247, selezionabili mediante tastiera
frontale. Protocollo MODBUS/JBUS (RTU). Dati: Dinamici (solo lettura) valori di fase e di
sistema. Statici (lettura e scrittura) tutti i parametri di configurazione. Formato dati 1 bit di
start, 8 bit di dati, nessuna parità, 1 bit di stop. Velocità di comunicazione 9600 bit/s.
Dispositivi in rete, massimo 160 dispositivi nella stessa rete. Isolamento Tramite optoisola-
tori, 4000 VRMS tra uscite e ingressi di misura. Rapporto di trasformazione: TV da 1,0
a 99,9 / da 100 a 999 / da 1,00k a 6,00k. CT primario fisso: 90, 150 o 250A. La massima
potenza misurata non può eccedere 210 MW calcolata come massimo ingresso in corren-
te e tension. Temperatura di funzionamento: da -20°C a +50°C (da -13°F a 131°F) (U.R.
da 0 a 90% senza condensa @ 40°C). Temperatura di immagazzinamento: da
-30°C a +70°C (da -22°F a 158°F) (U.R. <90% senza condensa @ 40°C). Categoria d’in-
stallazione: cat. III (IEC60664, EN60664). Isolamento (per 1 minuto) 4000 VRMS tra
ingressi di misura e uscita. Rigidità dielettrica: 4000 VRMS per 1 minuto. Reiezione
CMRR 100 dB, da 48 a 62 Hz. EMC secondo EN62052-11. Scariche elettrostatiche 15kV
scarica in aria; Immunità campi elettromagnetici irradianti. Provato con corrente applicata:
10V/m da 80 a 2000MHz. Provato senza corrente applicata: da 30V/m da 80 a 2000MHz;
immunità ai transitori veloci sui circuiti degli ingressi di misura in corrente e tensione: 4kV;
immunità ad impulso sui circuiti degli ingressi di misura in corrente e tensione: 4kV; emis-
sioni in radiofrequenza secondo CISPR 22. Conformità alle norme: sicurezza IEC60664,
IEC61010-1 EN60664, EN61010-1 EN62052-11. Metrologia EN62053-21, EN62053-23.
EN50470-3. Uscita impulsiva DIN43864, IEC62053-31. Approvazione CE. Connessioni a
vite. Sezione del cavo 2,4 x 3,5 mm. Coppia di serraggio viti Min./Max.: 0,4 Nm / 0,8 Nm.
Custodia, dimensioni 72 x 72 x 65 mm. Materiale Noryl PA66, autoestiguenza: UL 94 V-0
Montaggio a pannello e a guida DIN. Grado di protezione: frontale IP40. Connessioni:
IP20. Peso circa 400g (imballo incluso). Autoalimentazione da 18 a 260VCA (48-62Hz)
(VL1-N). Autoconsumo 20VA/1W.
ITALIANO
SICHERHEITSBESTIMMUNGEN
D
ie Betriebsanleitung aufmerksam lesen. Sollte das Gerät nicht gemäss
der Herstellerangaben verwendet werden, könnte der vom Gerät vorgesehe-
ne Schutz beeinträchtigt werden. Wartung: Beachten Sie den korrekten
Anschluss aller Anschlussterminals um eine Beschädigung des Instrumentes
z
u vermeiden. Das Gerät mit einem feuchten Tuch reinigen; keine Scheuer- oder
L
ösemittel verwenden. Das Gerät vor der Reinigung ausschalten.
TECHNISCHE DATEN
Messeingänge. Systemtyp: 3. Strommessung: nicht isoliert (Stromwandler). Anm.: die
externen Stromwandler können einzeln geerdet werden. (Stromsensor) VV2: 90A, VV3:
1
50A, VV5: 250A. Spannung (direkt oder Spannungswandler) VVx: 400VLL. Genauigkeit
(
Anzeige + RS485) Iref: siehe unten, Nennspannung: siehe unten (bei25°C ±5°C, R.f.
60%, 48 bis 62 Hz).Spannungsbereich Modell VVx. Nennspannung: 160 bis 260VLN
(277 bis 450VLL). Strombereich Modell VV2 Iref: 15A, Imax: 90A, Modell VV3 Iref: 20A,
Imax: 150A, Modell VV5 Iref: 20A, Imax: 250A. Strom von 0,05Iref bis 0,1Iref: ± (1% RDG
+ 3DGT), von 0,1Iref bis Imax: ± (1% RDG + 1DGT). Spannung Phase - N Im
Nennspannungsbereich: ±(0,5% Anzeigeendwert +1stellig). Spannung Phase-Phase: im
N
ennspannungsbereich: ±(1% Anzeigeendwert +1stellig). Frequenz Bereich: 45 bis 65Hz;
A
uflösung: ±1Hz. Wirkleistung: ±(2%Anzeigeendwert +2stellig).Leistungsfaktor:
±
[0.001+1%(1.000 - “LF Anzeigeendwert”)]. Blindleistung: ±(3%Anzeigeendwert +2stellig).
Wirkleistung: Klasse A gemäß EN50470-3; Klasse 2 gemäß EN62053-21. Startstrom: VV2:
75mA. VV3, VV5: 100mA. Temperaturbewegung 200ppm/°C @ PF=1, Phasenfehler:
0.05/°C. Abtastrate 1600 Abtastpunkte/s bei 50Hz 1900 Abtastpunkte/s bei 60Hz.
Erneuerungszeitanzeige: 1 Sekunde. Anzeige: 2 Linien 1. Linie: 7 stellig, 2. Linie: 3 stel-
l
ig oder 1. Linie: 3 stellig + 3 stellig, 2. Linie: 3 stellig. Art LCD, Höhe 7mm. Anzeigen von
M
omentanmessgrößen 3 stellig. Energien insgesamt aufgenommen: 6+1stellig Überla-
stungsanzeige EEEE Anzeige wenn der gemessene Wert die “Dauerhafte
Eingangsüberlastung” überschreitet (Messeingangsmaximalwerte). Max. und Min. Anzeige
Max Momentanmessgrößen: 999; Energien: 999 999.9 oder 9 999 999 (Nur Positiv). Die
negative Energie wird nicht gemessen oder einberechnet. Min. Momentanmessgrößen: 0;
Energien 0.0. LED-Leuchten Rote LED-Leuchte (Energieverbrauch). 0,01 kWh je Puls wenn
V
T Verhältnis <4 (VV2) oder <2 (VV3 oder VV5). 0,1 kWh je Puls wenn VT Verhältnis <40
(
VV2) oder <23 (VV3 oder VV5). 1kWh je Puls wenn VT Verhältnis >40 (VV2) oder >23
(VV3 oder VV5). Max Frequenz 16Hz, geß EN50470-3. Grüne LED (bei
Anschlussklemmblock) für Spannung ein (dauernd) und Kommunikation ein Status: RX-TX
(wenn RS485 Option ) (blinken). Messungen: Messmethode TRMS-Messungen von ver-
zerrten Wellenformen. Wandleranschluss durch externe Stromwandler.
Scheitelwertfaktor 3 (VV2: 230A Maximum). Überlaststrom ohne gültige Messung.
D
auer VV2: 120A, VV3: 300A, VV5: 360A. Überlastspannung: Dauer 1.2 Nennspannung
r 500ms 2Un. Spannungseingangsimpedanz: Eigenstromversorgung
Leistungsaufnahme: <2VA. Frequenz: 45 bis 65 Hz. Tastenfeld: zwei Drucktasten für die
Messgrößenwahl und die Programmierung der Geräteparameter. Impulsausgang: Anzahl
der Ausgänge 1. Typ programmierbar von 0.01 bis 9.99 kWh pro Impuls. Mit Energiezähler
verknüpfbarer Ausgang (kWh). Impulsdauer ≥100ms <120ms (ON), ≥120ms (OFF),
gemäß EN62052-31. Ausgang Statisch: Opto-Mosfet. Last V
ON
2.5 VAC/DC max. 70 mA, V
OFF
260 VAC/DC max. Isolation durch Optokoppler, 4000 VRMS Ausgang
Eingangsmessungen. RS485 Art Multidrop, Bidirektional (Statik- und Dynamikgrößen)
Anschlüsse 2 Adern. Höchstabstand 1000m, Terminierung direkt am Gerät. Adressen 247,
hlbar über die vorderen Steuerhebel Protokoll MODBUS/JBUS (RTU).
Datenübertragung: Dynamisch (nur lesen) Einzelphasen und Systemmesswerte. Alle
Konfigurationsparameter. Datenformat 1 Start-bit, 8 Daten-bits, keine Parität,1 Stop-bit.
Übertragungsgeschwindigkeit 9600 bits/s. Treibereingangsleistung 1/5
Leistungsaufnahme. Maximum Maximal Geräte 160 am gleichen Bus Isolation durch
Optokoppler, 4000 VRMS-Ausgang zum Messeingang. Wandlerverhältnis:
Spannungswandler 1.0 bis 99.9 / 100 bis 999 /1.00k bis 6.00k Stromwandler Primärstrom,
fest: 90, 150 oder 250A. Die maximal gemessene Leistung darf 210 MW nicht überschrei-
ten, die als Maximalwerte für Eingangsspannung und Strom berechnet werden.
Betriebstemperatur: -20°C bis +50°C (-13°F bis 131°F) (R.f. von 0 bis 90% nicht konden-
sierend bei 40°C). Lagertemperatur: -30°C bis +70°C (-22°F bis 158°F) (R.f. <90% nicht
kondensierend bei 40°C). Gebrauchskategorie Kat. III (IEC60664, EN60664). Isolation (für
1 Minute) 4000 VRMS zwischen Eingangsmessung und Digitalausgang.
Durchschlagfestigkeit 4000 VRMS für 1 Minute. Rauschdrückungsverhältnis CMRR 100
dB, 48 to 62 Hz. EMV gemäß EN62052-11. Elektrostatische Entladungen 15kV
Luftentladung; Strahlungsimmunität Stromtest: 10V/m von 80 bis 2000MHz;
Elektromagnetfelder Test stromlos: 30V/m von 80 bis 2000MHz; Ladungsimpuls am Strom-
und Eingangsspannungsmesskreis: 4kV Leitungsgeb. Störausstrahlung Gemäß CISPR 22.
Standardkonformität: Sicherheit IEC60664, IEC61010-1 EN60664, EN61010-1. EN62052-
11 Messung EN62053-21, EN62053-23, EN50470-3. Impulsausgang DIN43864, IEC62053-
31. Zulassungen: CE. Anschlüsse: Schraubanschluss Kabelquerschnitt 2.4 x 3.5 mm
Min./Max. Anzugsmoment: 0.4 Nm / 0.8 Nm. Gehäuse:Abmessungen (LxHxB) 72 x 72 x 65
mm. Material Noryl PA66, self-extinguishing: UL 94 V-0. Montage Tafel und DIN-Schiene.
Schutzgrad: Vorderseite IP40 Schraubenklemmen IP20. Gewicht: Ca. 400 g (inkl.
Verpackung). Eigenstromversorgung: 18 bis 260VAC (48-62Hz) (VL1-N).
Leistungsaufnahme: 20VA/1W.
DEUTSCH
PRÉCAUTIONS DE SECURITE
L
ire attentivement le manuel de l’utilisateur. Si l’appareil est utilisé dans
des conditions différentes de celles spécifiées par le fabricant, le niveau de
protection prévu par l’instrument peut être compromis. Entretien: s’assurer
que les connexions sont réalisées correctement dans le but d’éviter toutes
f
autes ou endommagements de l’appareil. Pour nettoyer l’instrument, utiliser un chiffon
h
umide; ne pas utiliser d’abrasifs ou de solvants. Il faut déconnecter le dispositif avant de
p
rocéder au nettoyage.
CARACTÉRISTIQUES D’ENTRÉE
P
uissances nominales: type de rèseau: 3 type de courant: non isolé (par CT). Note: les
t
ransformateurs de courant externe peuvent être branchés à la masse séparément.
Gamme de courant (par capteur de courant) VV2: 90A, VV3: 150A, VV5: 250A. Tension
(directe ou par TT/TP) VVx: 400VLL. Précision (Écran + RS485) Iref: voir plus bas, Un:
voir plus bas (@25°C ±5°C, R.H. 60%, 48 à 62 Hz). Gamme de tension modèle VVx Un:
160 à 260VLN (277 à 450VLL). Gamme de courant modèle VV2 Iref: 15A, Imax: 90A;
m
odèle VV3 Iref: 20A, Imax: 150A; modèle VV5 Iref: 20A, Imax: 250A. Courant de 0,05Iref
à
0,1Iref: ± (1% RDG + 3DGT); de 0,1Iref à Imax: ± (1% RDG + 1DGT). Tension phase-
n
eutre sur la gamme Un: ±(0,5% RDG +1DGT). Tension phase-phase sur la gamme Un:
±(1% RDG +1DGT). Fréquence gamme: 45 à 65Hz; résolution: ±1Hz. Énergie active:
±(2%RDG +2DGT). Facteur de puissance: ±[0.001+1%(1.000 - “PF RDG”)]. Énergie réac-
tive: ±(3%RDG +2DGT). Énergie active kWh: classe A selon EN50470-3; classe 2 selon
EN62053-21. Courant de démarrage: VV2: 75mA. VV3, VV5: 100mA. Dérive de
t
empérature 200ppm/°C @ PF=1. Erreur de phase: 0.05/°C. Taux d’échantillonna-
g
e: 1600 échantillon/s @ 50Hz, 1900 échantillon/s @ 60Hz. Temps de mise à jour écran:
1 seconde. Écran: 2 lignes 1° ligne: 7-DGT, 2° ligne: 3-DGT ou 1° ligne: 3-DGT + 3-DGT,
2
°
ligne: 3-DGT. Type LCD, h 7mm. Affichage variables instantanées 3-DGT. Énergies total
importé: 6+1DGT. État de surcharge EEE indication quand la valeur mesurée dépasse la
“surcharge entrées continues” (capacité de mesure maximum) Indications Max. et Min.
Variables instantanées max: 999; énergies: 999 999.9 ou 9 999 999 (positif seulement).
L
'énergie négative n'est ni mesurée ni déduite. Variables instantanées min.: 0; énergies
0
.0. LEDs. LED rouge pour consommation d’énergie, 0,01 kWh par impulsion si ratio TT
<4 (VV2) ou <2 (VV3 ou VV5); 0,1 kWh par impulsion si ratio TT <40 (VV2) ou <23 (VV3
ou VV5): 1kWh par impulsion si ratio TT >40 (VV2) ou >23 (VV3 ou VV5); fréquence max
16Hz, suivant EN50470-3. LED verte (côté bornier) pour présence alimentation (stable) et
état de la communication: RX-TX (en case d’option RS485) clingnotante. Mesures:
méthode TRMS de formes d’onde distordues. Type de couplage: au moyen d’un TC
e
xterne. Facteur de crête ≤3 (VV2: pic max. 230A). Surcharges de courant sans mesu-
r
e valide. Continues VV2: 120A; VV3: 300A; VV5: 360A. Surcharge de tension: continues
1.2 Un pendant 500ms 2Un. Impédance tension d’entrée: auto-alimentation consomma-
tion alimentation: < 2VA. Fréquence: 45 à 65 Hz. Clavier: deux boutons pour la sélection
et programmation variable des paramètres de fonctionnement de l’instrument. Sortie à
impulsions: nombre de sorties 1. Type programmable de 0.01 à 9.99 kWh par impulsions.
Sortie pouvant être branchée aux compteurs d’énergie (kWh). Durée d’impulsion ≥100ms
< 120ms (ON), ≥120ms (OFF), selon EN62052-31. Sortie statique: opto-mosfet. Charge
V
ON
2.5 VCA/CC max. 70 mA, V
OFF
260 VCA/CC max. Isolement: par optocoupleurs, sortie
4000 Veff de l’ entrée mesure à la sortie. RS485 type Multi\point, bidirectionnel (variables
statiques et dynamiques). Branchements 2-fils. distance max. 1000m, terminaison directe-
ment sur l’instrument. Adresses 247, à sélectionner au moyen du clavier frontal. Protocole
MODBUS/JBUS (RTU). Donnée. Dynamique (lecture seulement) valeurs monophasées et
triphasées. Tous les paramètres configuration. Format de données 1 bit de démarrage, 8
bit de donnée, pas de parité,1 bit d’arrêt. Taux (Baud): 9600 bits/s. Capacité entrée driver
1/5 de charge unité. Max. 160 émetteurs-récepteurs sur le même bus. Isolation au moyen
de optocoupleurs, sortie 4000 VRMS vers entrées de mesure. Rapport de transforma-
tion: TT (TP) 1.0 à 99.9 / 100 à 999 / 1.00k à 6.00k TC courant primaire fixe: 90, 150 or
250A. La puissance maximale mesurée ne peut excéder 210 MW calculé comme courant
et tension d’entrée maximum. Température de fonctionnement: -20°C à +50°C (-13°F à
131°F) (R.H. de 0 à 90% pas de condensation @ 40°C). Température de stockage: -30°C
à +70°C (-22°F à 158°F) (R.H. < 90% pas de condensation @ 40°C). Catégorie de l’instal-
lation: Cat. III (IEC60664, EN60664). Isolation (pour 1 minute): 4000 VRMS entre mesure
d’entrée et sortie numérique. Rigidité diélectrique: 4000 VRMS pour 1 minute. Rejet de
bruit CMRR: 100 dB, 48 à 62 Hz. EMC selon EN62052-11. Décharges électrostatiques 15kV
décharge dans l’air; immunité à l’irradiation. Test avec courant: 10V/m de 80 à 2000MHz;
champs électromagnétiques test sans courant: 30V/m de 80 à 2000MHz; èclatement sur
mesure de courant et tension de circuit d’entrée: 4kV. Immunité aux perturbations par
conduction 10V/m de 150KHz à 80MHz. Suppression fréquence radio selon CISPR 22.
Conforme aux standards: Sécurité IEC60664, IEC61010-1 EN60664, EN61010-1
EN62052-11 Métrologie EN62053-21, EN62053-23, EN50470-3. Sortie à impulsions
DIN43864, IEC62053-31. Certification: CE. Branchements: Type par vis. Section du câble
2.4 x 3.5 mm. Couple de serrage de vis Min./Max.: 0.4 Nm / 0.8 Nm. Boîtier: dimensions
(WxHxD) 72 x 72 x 65 mm. Matériel Noryl PA66, auto-extincteur: UL 94 V-0. Support
Panneau et DIN-rail. Indice de protection: Frontal IP40 Bornes de vis IP20. Poids: environ
400 g (emballage inclus). Auto-alimentation: 18 à 260VAC (48-62Hz) (VL1-N).
Consommation d’énergie: 20VA/1W.
FRANçAIS
“Max. Surrounding Air of 40°C”. “Use 60 or 75°C copper (CU)
conductor and wire size No. 24-12 AWG, stranded or solid”.
“Terminal tightening torque of 4 to 7 Lb-In (0.4 to 0.8Nm)”.
“Open Type Device”.
Current measuring input terminals must be connected only through Carlo
Gavazzi accessories current transformers TU10P-90A or TU16P-150A or
TU24P-250A, with one lead connected to Earth.
Direct connection to the line voltage is not allowed.
UL NOTES

Transcripción de documentos

CARLO GAVAZZI A u t o m a t i o n Carlo Gavazzi Controls SpA, Via Safforze, 8 - 32100 Belluno (Italy) Tel. +39 0437 355811, Fax +39 0437 355880 C o m p o n e n t s EM21 72R IM ML 8021723 210917 EM21 72R „3-phase Energy Meter for Retro-fit‰ 1 3 2 4 fig. 1 a c tab. 1 ENGLISH 03 04 05 06 07 08 09 10 11 To measurement mode Al modo misura Zum Messmodus Au mode mesure En el modo de medición 5 fig. 2 3.2.1... 3s 02 3s PROGRAMMING 1.2.3... b 01 OK ■ Front panel and value setup (fig. 1) In the measurement mode: press the key 1 to scroll the measurement pages. press the key 2 to scroll the information pages of the instrument. Holding the button 2 pressed for at least 3 sec., you access parameter programming and setting. In the programming mode: press the key 1, to scroll the menus or increase/decrease the values to be set up. With button 2 you can enter the submenus and change the value change mode from positive to negative or vice versa according to the logic indicated in table 1: a, pressing button 2, the letter C appears in the bottom row, indicating the possibility to change the values increasing them by means of button 1. b, pressing again button 2, -C appears in the bottom row, indicating the possibility to decrease the values by means of button 1. c, To confirm the selected value, hold button 2 pressed until the mark - of letter C disappears. This way, the value is confirmed. The frontal red LED (3, fig.1) flashes proportionally to the active imported energy consumption. Wrong phase sequence indicator (4, fig 1), the hazard triangle is displayed in case of wrong phase sequence (L2-L1-L3, L1-L3-L2). ■ PROGRAMMING BLOCK It is possible to block the access to programming by means of a specific trimmer positioned on the rear of the removable display unit. Turn the trimmer clockwise up to its run end with the help of a suitable screwdriver as shown in figure 2 point 5. ■ BASIC PROGRAMMING AND RESET To enter the complete programming mode, press the key 2 for at least 3 sec. (fig 1). Entering the programming mode, all the measurements and control functions are inhibited. During this phase the flashing of the LED has not to be considered. 01 PASS?: entering the right password (default value is 0) allows accessing the main menu. 02 CnG PASS: it allows changing the password. 03 APPLiC: it allows selecting the pertinent application. A: active positive energy meter (mesuring of active positive energy and some minor parameters). B: active and reactive positive energies meter (measuring of energies active and reactive positive with some minor parameters). C: showing of all the electrical variables available. 04 SYS: it allows selecting the electrical system. 3Pn: 3-phase unbalanced with neutral; 3P: 3-phase unbalanced without neutral; 3P1: 3-phase balanced with or without neutral 2P: 2-phase; 1P: single phase. 05 Ut rAtio: VT ratio (1.0 to 6.00k). Example: if the connected VT primary is 5kV and the secondary is 100V, the VT ratio to be set is 50 (that is 5000/100). 06 PuLSE: selects the pulse weight (kWh per pulse; programmable from 0,01 to 9,99). 07 P. tESt: sets the simulated power value (kW) to which a proportional pulse sequence according to “PULSE” corresponds. The function is active until you remain within the menu. 08 tESt: activated on the pulse output when ON (for “APPLiC” C only). 09 Add. : serial address: from 1 to 247 (with “IS” option only). 10 EnE rES: reset of all the meters (for “APPLiC” C only). 11 End : it allows exiting the programming mode by pressing the key 2 (see fig 1). 3s 3s ITALIANO ■ Pannello frontale ed impostazioni valori (fig. 1) In modalità misura: tasto 1, scorre le pagine di misura. Tasto 2 scorre le pagine informazioni dello strumento. Tenendo premuto per almeno 3sec il tasto 2 si accede alla programmazione e impostazioni parametri. In modalità programmazione: tasto 1, scorre i menù o incrementa/decremente i valori da impostare. Il tasto 2, entra nei sottomenù e cambia la modalità di incrementazione dei valori da positiva a negativa e viceversa secondo la logica riportata nella tabella 1: a, premendo il tasto 2 compare una lettera C nella riga inferiore indicante la possibilità di agire sui valori incrementandoli mediante il tasto 1. b, premendo ulterioriormente il tasto 2 compare -C nella riga inferiore indicante la possibilità di agire sui valori decrementandoli mediante il tasto 1. c, Per confermare il valore selezionato tenere premuto il tasto 2 finché il segno - (se presente) e la lettera C scompariranno, il valore sarà così confermato. Il LED rosso frontale (3, fig.1) lampeggia proporzionalmente al consumo di energia attiva totale. Indicatore di sequenza fase errata (4, fig 1), il triangolo di pericolo viene visualizzato in caso di sequenza fasi errata (L2-L1-L3, L1-L3-L2). ■ BLOCCO DELLA PROGRAMMAZIONE E’ possibile bloccare l’accesso alla programmazione mediante un apposito trimmer posizionato nel retro dell’unità display removibile. Girare in senso orario fino a fondo corsa il trimmer con l’ausilio di un adeguato cacciavite come illustra la fig. 2 punto 5. ■ PROGRAMMAZIONE E RESET Per accedere alla programmazione completa dello strumento premere il tasto 2 per almeno 3sec. (fig 1). Quando si accede alla programmazione, si inibiscono tutte le funzioni di misura e controllo (il trimmer non deve essere posizionato in lock, fig. 2). In questa fase il lampeggio del LED frontale non deve essere considerato. 01 PASS? : inserendo il valore di password corretto (di default 0) si accede al menù principale. 02 CnGPASS: nuova password, personalizza la password. 03 APPLiC.: seleziona l’applicazione pertinente. A: contatore di energia attiva positiva (misura dell’energia attiva positiva e di alcuni parametri minori). B: contatore di energia attiva e reattiva positiva (misura dell’energia attiva e reattiva positive e di alcuni parametri minori). C: visualizzazione di tutte le variabili elettriche disponibili. 04 SYS : sitema elettrico: 3Pn: trifase sbilanciato con neutro; 3P: trifase sbilanciato senza neutro; 3P1: trifase bilanciato con o senza neutro; 2P: bifase; 1P monofase. 05 Ut rAt. : rapporto TV (da 1,0 a 6.00k). Esempio: se il primario del TV connesso è di 5kV e il secondario è di 100V il rapporto di TV corrisponde a 50 (ottenuto eseguendo il calcolo: 5000/100). 06 PuLSE: seleziona il peso dell’impulso (kWh per impulso; programmabile da 0,01 a 9,99). 07 P. tESt: (SOLO CON “APPLiC” C, vedere menù n. 3), imposta il valore di potenza (kW) simulata a cui corrisponderà una frequenza degli impulsi ad essa proporzionale in base a “PULSE”, la funzione è attiva finché si rimane nel menù. 08 tESt: (SOLO CON “APPLiC” C, vedere menù n. 3), attivo su uscita impulsi con selezione ON. 09 Add. : (solo con opzione “IS”) indirizzo seriale: da 1 a 247. 10 EnE rES: azzeramento di tutti i contatori totali (SOLO CON “APPLiC” C). 11 End : per tornare al modo misura premere il tasto 2 (vedere figura 1). 3s 3s 3s DEUTSCH ■ Vorderes Bedienfeld und Werteinstellungen (fig. 1) Im Messmodus: Taste 1, durchblättert die Meßseiten. Taste 2 durchblättert die Informationsseiten des Geräts. Bei Gedrückthalten der Taste 2 für mindestens 3 Sek. loggen Sie sich in die Programmierung und Parametereinstellungen ein. Im Programmiermodus: Taste 1 durchblättert die Menüs bzw. erhöht/verringert die einzustellenden Werte. Mit Taste 2 gelangt man in die Untermenüs und ändert die Zunahmemodalität der Werte von positiv in negativ und umgekehrt je nach der in Tabelle 1 angegebenen Logik: a, bei Drücken der Taste 2 wird ein Buchstaben C in der unteren Zeile angezeigt, der die Möglichkeit aufzeigt, die Werte mit der Taste 1 zu steigern. b, bei weiterem Drücken der Taste 2 wird –C in der unteren Zeile angezeigt, was die Möglichkeit aufzeigt, die Werte mit der Taste 1 zu verringern. c, Zur Bestätigung des gewählten Werts die Taste 2 so lange gedrückt halten bis das Zeichen – des Buchstabens C erlischt, dadurch wird der Wert bestätigt. Die vordere rote LED-Leuchte (3, v fig.1) blinkt, wenn die gemessene Wirkenergie und der Strom positiv (importiert) sind. Anzeige von falscher Phasenfolge (4, fig 1), das Gefahrendreieck wird bei falscher Phasenfolge angezeigt (L2-L1-L3, L1-L3-L2). ■ SPERRE DER PROGRAMMIERUNG Der Zugriff auf die Programmierung kann mit einem entsprechenden auf der Rückseite der entfernbaren Anzeigeneinheit positionierten Trimmer blockiert werden. Den Trimmer mithilfe eines passenden Schraubenziehers, wie auf Abb. 2 Punkt 5 dargestellt, im Uhrzeigersinn bis zum Anschlag drehen. ■ PROGRAMMIERUNG UND RÜCKSETZEN Um in den Programmiermodus zu gelangen, muss die Taste 2 für mindestens 3 Sek. gedrückt werden (siehe Abb.1). Im Programmiermodus werden alle Messund Kontrollfunktionen inakt. Diese Phase hat keinen Bezug zu dem Blinken der LED. 01 PASS? : durch Eingabe des richtigen Passworts (Default-Wert beträgt 0) rufen Sie das Hauptmenü auf. 02 CnGPASS: ermöglicht Passwortänderung. 03 APPLiC.: ermöglicht die Wahl des entsprechenden Applikationsbereichs. A: Wirkenergiezähler (Messen der positive Wirkenergie und einiger weniger Parameter). B: Wirk- und Blindenergiezähler (Messen der positive Wirk- und Blindenergien mit einigen weniger Parametern). C: Anzeige aller verfügbaren elektrischen Messgrößen. 04 SYS : ermöglicht die Wahl des Elektrosystems. 3P.n: 3-phasig unsymmetrisch mit Nullleiter, 3P:3-phasig symmetrisch ohne Nullleiter, 3P1: 3-phasig symmetrisch mit oder ohne Nullleiter 2P: 2-phasig, 1P: eine Phase. 05 Ut rAt. : SpW-Verhältnis (von 1,0 bis 6,00k). Beispiel: Wenn der angeschlossene primäre Spannungswandler 5kV beträgt und der sekundäre 100V, beträgt das einzustellende Spannungswandlerverhältnis 50 (d.h. 5000/100). 06 PuLSE: wählt das Impulsgewicht (kWh pro Impuls; einstellbar von 0,01 bis 9,99). 07 P. tESt: (NUR MIT “APPLiC” C Option, siehe Menü n. 3), stellt den simulierten Leistungswert (kW) ein, dem eine Frequenz der zu ihr proportionalen Impulse auf der Grundlage von “PULSE” entspricht, die Funktion ist eingeschaltet solange Sie im Menü bleiben. 08 tESt: (NUR MIT “APPLiC” C Option, siehe Menü n. 3), bei ON ist Impulsausgang eingeschaltet. 09 Add. : (nur mit “IS” Option) ermöglicht die Wahl der seriellen Geräteadressen (von 1 bis 247). 10 EnE rES: ermöglicht das Rücksetzen der Gesamtenergiezähler (NUR MIT “APPLiC” C). 11 End : ermöglicht das Verlassen des Programmiermodus durch Drücken der Taste 2 (siehe Abb. 1). 3s 3s 3s 3s FRANçAIS ■ Panneau frontal et configurations valeurs (fig. 1) En mode mesure: touche 1, les pages de mesure défilent. Touche 2, les pages d’informations de l’instrument défilent. En maintenant enfoncé pendant au moins 3 sec. la touche 2, on accède à la programmation et configurations paramètres. En mode programmation: touche 1, les menus défilent ou les valeurs à configurer augmentent/baissent. La touche 2 entre dans les sous-menus et change le mode d’incrémentation des valeurs de positif à négatif et vice-versa selon la logique reportée dans le tableau 1: a, en appuyant sur la touche 2, la lettre C apparaît sur la ligne inférieure indiquant la possibilité d’actionner sur les valeurs en les augmentant à l’aide de la touche 1. b, en appuyant encore sur la touche 2, C apparaît dans la ligne inférieure indiquant la possibilité d’agir sur les valeurs en les diminuant à l’aide de la touche 1. c, Pour valider, confirmer la valeur sélectionnée, maintenir enfoncée la touche 2 jusqu’à ce que le signe – de la lettre C disparaisse, la valeur sera ainsi confirmée. La LED rouge frontale (3, fig.1) clignote proportionnellement à l’énergie active mesurée. Indicateur de séquence phase erronée (4, fig 1), le triangle de danger est affiché en cas de séquence phases erronée (L2-L1-L3, L1-L3-L2). ■ BLOCAGE DE LA PROGRAMMATION Il est possible de bloquer l’accès à la programmation au moyen d’un trimmer positionné derrière l’unité d’affichage amovible. Tourner à fond dans le sens des aiguilles d’une montre le trimmer à l’aide d’un tournevis comme l’illustre la fig. 2 point 5. ■ PROGRAMMATION ET REMISE A ZERO Pour accéder à la programmation complète de l’instrument, appuyer pendant au moins 3 sec. sur la touche 2 (comme indiqué à la figure 1). Si l’on accède à la programmation, toutes les fonctions de mesure et contrôle sont inhibées. Pendant cette phase, le clignotement de la LED ne doit pas être pris en compte. 01 PASS? : en introduisant la valeur du mot de passe correct (par défaut 0), on accède au menu principal. 02 CnGPASS: nouveau mot de passe, personnalise le mot de passe. 03 APPLiC.: sélectionne l’application pertinente. A: énergie active positive (mesure de l’énergie active positive et quelques paramètres plus petits). B: compteur d’énergie active positive et réactive positive (mesure des énergies actives et réactives positives avec des paramètres plus petits). C: Montre tous les variables électriques disponibles. 04 SYS : sélection du réseau électrique. 3P.n: triphasé déséquilibré avec neutre; 3P: triphasé déséquilibré sans neutre; 3P: triphasé équilibré avec ou sans neutre; 2P: biphasé; 1P: monophasé. 05 Ut rAt. : ratio TT (1,0 à 6,00k). Exemple: si le primaire du TT raccordé est de 5kV et le secondaire est de 100V, le ratio TT correspond à 50 (obtenu en effectuant le calcul: 5000/100). 06 PuLSE: sélectionne le poids de l’impulsion (kWh par impulsion ; programmable de 0,01 à 9,99). 07 P. tESt: (SEULEMENT AVEC “APPLiC” C, voir menù n. 3), configure la valeur de puissance (kW) simulée à laquelle correspondra une fréquence des impulsions proportionnelle à cette dernière en fonction du “PULSE”, la fonction est activée jusqu’à ce qu’on reste dans le menu. 08 tESt: (SEULEMENT AVEC “APPLiC” C, voir menù n. 3), activé sur la sortie impulsion après avoir sélectionné ON. 09 Add. : (seulement avec option “IS”) adresse série (de 1 à 247). 10 EnE rES: mise à zero des tous les compteurs d’énergie totaux (SEULEMENT AVEC “APPLiC” C). 11 End : pour revenir au mode mesure, appuyer sur la touche 2 (voir fig.1). 3s ESPAÑOL ■ Panel frontal y configuración de valores (fig. 1) En modalidad de medición: tecla 1, avanza por las páginas de medición. La tecla 2, avanza por las páginas de información del equipo. Si se mantiene pulsada la tecla 2 al menos 3 seg. se accede a la programación y configuración de parámetros. En modalidad programación: tecla 1, avanza por los menús o incrementa/disminuye los valores a configurar. La tecla 2 permite acceder a los submenús y cambia la modalidad de incremento de los valores de positiva a negativa y viceversa según la lógica indicada en la tabla 1: a, pulsando la tecla 2 aparece una letra C en la línea inferior para indicar la posibilidad incrementar los valores mediante la tecla 1. b, pulsando de nuevo la tecla 2 aparece -C en la línea inferior para indicar la posibilidad de disminuir los valores mediante la tecla 1. c, Para confirmar el valor seleccionado mantenga pulsada la tecla 2 hasta que el signo – de la C desaparezca, así se habrá confirmado el valor. El LED rojo frontal (3, fig.1) parpadea proporcionalmente al consumo de energía activa total importada. Indicador de secuencia fase incorrecta (4, fig 1), el triángulo de peligro se visualiza en caso de secuencia de fase incorrecta (L2-L1-L3, L1-L3-L2). ■ BLOQUEO DE LA PROGRAMACIÓN Es posible bloquear el acceso a la programación mediante el conmutador situado en la parte trasera del módulo display. Gire en sentido horario el conmutador hasta su tope usando un destornillador adecuado como muestra la fig. 2 punto 5. ■ PROGRAMACIÓN Y PUESTA A CERO Para entrar al modo de programación completo hay que pulsar la tecla 2 al menos 3 seg. (ver fig. 1). En el modo de programación completa del instrumento, todas las medidas y las funciones de control están inhibidas. Durante esta fase el parpadeo del LED no debe ser considerado. 01 PASS? : introduciendo la clave correcta (valor por defecto 0) se accede al menú principal. 02 CnGPASS: permite cambiar la clave. 03 APPLiC.: permite seleccionar la aplicación correspondiente. A: activar el contador de energía positiva (midiendo la energía activa positiva y algunos parámetros menores). B: contador de energía activa positiva y reactiva positiva (midiendo la energía activa y reactiva positiva con algunos parámetros menores). C: muestra todas las variables eléctricas disponibles. 04 SYS : Permite seleccionar el sistema eléctrico. 3P.n: trifásico desequilibrado con neutro; 3P: trifásico desequilibrado sin neutro; 3P.1: trifásico equilibrado con o sin neutro; 2P: bifásico; 1P: monofásico. 05 Ut rAt. : relación del trafo de tensión VT (1,0 a 6,00k). Ej.: si el primario del trafo conectado es 5kV y el secundario es 100V, la relación del trafo de tensión es 50 (es decir, 5000/100). 06 PuLSE: selecciona el valor del pulso (kWh por pulso; programable de 0,01 a 9,99). 07 P. tESt: (SóLO CON “APPLiC” C, ver menú n. 3), configura el valor de potencia simulada (kW) a la que corresponderá una frecuencia de los pulsos proporcional a ésta en base a "PULSE". La función está activa mientras se permanece en el menú. 08 tESt: (SóLO CON “APPLiC” C, ver menú n. 3), activado en la salida de pulsos cuando se selecciona ON. 09 Add. : (sólo opción IS”) permite seleccionar la dirección serie del instrumento: de 1 a 247. 10 EnE rES: permite la puesta a cero de todos los contadores totales (SóLO CON “APPLiC” C). 11 End : permite salir del modo de programación pulsando la tecla 2 (ver fig. 1). MEASURING MODE, MODO MISURA, PROGRAMMIERMODUS, MODO DE MISURE, MODO DE MEDIDA In case of wrong phase sequence. In caso di sequenza fasi errata. Bei falscher Phasenfolge. En cas de séquence phases erronée. En caso de secuencia de fase incorrecta. Phase to phase voltage L1-2, L2-3, L3-1. Tensioni concatenate L1-2, L2-3, L3-1. Spannung Phase-Phase L1-2, L2-3, L3-1. Tension phase-phase L1-2, L2-3, L3-1. Tensión entre fases L1-2, L2-3, L3-1. System values. Valori di sitema. Systemwerte. Valeurs de système. Valores del sistema. Information pages. Pagine informative. Informationsseiten. Pages d’information. Páginas de información. APPLiC : Measuring pages. Pagine di misura. Meßseiten. Pages de mesure. Páginas de medida. A B C B Year of production (Y. 2008) and firmware release (r.A0). Anno di produzione (Y. 2008) e versione del firmware (r.A0). Herstellungsjahr (Y. 2008) und Version der Firmware (r.A0). Année de production (Y. 2008) et version firmware (r.A0). Año de fabricación (Y. 2008) y versión del firmware (r.A0). Primary current transformer value. Valore del primario del trasformatore di corrente. Stromwandler-Verhältnis. Ratio de transformateur ampèremètre. Relación del transformador de corriente. Voltage transformer ratio. Rapporto di trasformazione voltmetrica. Spannungswandler-Verhältnis. Ratio de transformateur de tension. Relación del transformador de tensión. Pulse output: kWh per pulse. Uscita impulsi: kWh per impulso. Impulsausgang: kWh pro Impuls. Sortie impulsions: kWh par impulsion. Salida pulsos: kWh por pulso. Serial communication address. Indirizzo di comunicazione seriale. Serielle Kommunikationsadresse. Adresse de communication sériel. Dirección de comunicación serie. B 0.98 L PF sys 50 Hz sys C C C 0.98 L PF L1 0.97 L PF L2 0.96 L PF L3 10.0 A L1 10.0 A L2 10.0 A L3 C C 400 V L1-2 400 V L2-3 400 V L3-1 230 V L1 230 V L2 230 V L3 V L-N sys, V L-L sys, VA sys, VA L1, VA L2, VA L3, var L1, var L2, var L3, W L1, W L2, W L3. ENGLISH A FRANçAIS ■ Transforming the instrument from DIN guide fitting to panel fit- ■ Transformer l’instrument de montage en guide DIN en montage ting and vice versa. à panneau et vice-versa. 2 6 4 kWh per pulse (LED). kWh per impulso (LED). kWh pro Impuls (LED). kWh par impulsion (LED). kWh por pulso (LED). Type of system (SYS 3P.n) and type of connection (4 wires). Tipo di sistema (SYS 3P.n) e tipo di collegamento (4fili). Systemtyp (SYS 3P.n) und Anschlusstyp (4 Adern). Type de système (SYS 3P.n) et type de branchement (4 câbles). Tipo de sistema (SYS 3P.n) y tipo de conexión (4 hilos). A 123456,7 kvarh 12,3 kvar sys 123456,7 kWh 12,3 kW sys Available variables only with RS485. Variabili disponibili solo da RS485. Vorhandene Variablen nur mit RS485. Variables disponibles seulement avec RS485. Variables disponibles sólo con RS485. C 1 3 To remove the display unit, by means of a screwdriver of suitable dimensions, operate on slots (1 and 2) on the sides of the instrument, pressing the fastening tabs (3 and 4), then carefully remove (5) the display unit. To transform the instrument from panel fitting to DIN guide fitting, rotate the measurement base from A to B. To transform the instrument from DIN guide fitting to panel fitting, rotate the measurement base from B to A. To insert the display unit, gently push it (6) in its seat, as shown in the images, until you hear the “clicks” of the elastic tabs (3 and 4) which signal the correct fitting in the slots (1 and 2). Pour enlever l’unité d’affichage, à l’aide d’un tournevis à coupe de dimensions adéquates, actionner les fentes (1 et 2) aux côtés de l’instrument en appuyant sur les languettes de fixation (3 et 4) puis extraire (5) avec soin l’unité display. Pour transformer l’instrument de montage en panneau à guide DIN, tourner sur elle-même la base de mesure de A à B. Pour transformer l’instrument de guide DIN à montage en panneau, tourner sur elle-même la base de mesure de B à A. Pour insérer l’unité d’affichage, la pousser (6) délicatement dans le siège prédisposé comme les images sur le côté l’illustrent jusqu’à ce qu’on avertisse ■ Green LED, fig. C 1 les “clics” des languettes élastiques de fixation (3 et 4) ce qui signifie l’encastreIf the instrument is used as converter, that is without display unit, the ment correct de celles-ci dans les fentes (1 et 2) de fermeture. green LED shows that the instrument is powered, if the LED flashes, it ■ LED vert, fig. C 1 shows that the instrument is connected to the serial network and is Dans le cas où l’instrument est utilisé en tant que convertisseur et donc communicating. sans unité display, le LED vert indique la présence de l’alimentation si le LED clignote, cela indique aussi que l’instrument est branché au ITALIANO ■ Trasformare lo strumento da montaggio a guida DIN a montag- réseau sériel et qu’il communique. ESPAÑOL gio a pannello e viceversa. Per togliere l’unità display, mediante un cacciavite a taglio di dimensioni ade- ■ Transformar el montaje a carril DIN en montaje a panel y viceguate agire sulle asole (1 e 2) ai lati dello strumento premendo le linguette di versa. 5 Para retirar el módulo display, mediante un destornillador adecuado, accionar en las ranuras (1 y 2) a los lados del equipo presionando las lengüetas de fijación (3 y 4) y extrayendo (5) con cuidado el módulo display. Para transformar el montaje en panel a montaje en carril DIN, gire sobre sí misma la base de A a B. Para transformar el montaje a carril DIN en montaje a panel, gire sobre sí misma la base de B a A. Para introducir el módulo display, empújelo (6) delicadamente en el hueco correspondiente, como ilustran las imágenes que aparecen a la izquierda, ■ LED verde, fig. C 1 hasta que oiga los “clic” de las lengüetas de fijación (3 y 4) que indican que se Nel caso lo strumento sia utilizzato come convertitore, quindi senza han introducido correctamente en los orificios (1 y 2) de cierre. fissaggio (3 e 4) , quindi estrarre (5) con cura l’unità display. Per trasformare lo strumento da montaggio a pannello a guida DIN, girare su se stessa la base di misura da A a B. Per trasformare lo strumento da guida DIN a montaggio a pannello, girare su se stessa la base di misura da B ad A. Per inserire l’unità display, spingerla (6) delicatamente nella sede predisposta, come illustrano le immagini a lato, fino a che si avvertiranno i “click” delle linguette elastiche di fissaggio (3 e 4) a significare il corretto incastro delle stesse nelle asole (1 e 2) di chiusura. B 2 6 4 1 3 5 C 1 unità display, il LED verde indica la presenza dell’alimentazione, se il ■ LED verde, fig. C 1 LED è lampeggiante esso indica che lo strumento è collegato alla rete En caso de que el equipo se use como convertidor, por lo tanto sin seriale e sta comunicando. display, el LED verde indica que el equipo está alimentado, si el LED parpadea indica también que el equipo está conectado a la red en DEUTSCH ■ Umwandlung der Gerätemontage von DIN Schiene in Tafel und serie y que está comunicando. umgekehrt. Zur Herausnahme der Anzeigeneinheit, mit einem entsprechend großen Schlitzschraubenzieher durch die Ösen (1 und 2) an den Seiten des Geräts auf die Befestigungszungen (3 und 4) drücken und dann die Anzeigeneinheit vorsichtig herausziehen (5). Zur Umwandlung der Gerätemontage von Tafel in DIN Schiene, die Messbasis um sich selbst von A auf B drehen. Zur Umwandlung der Gerätemontage von DIN Schiene in Tafel, die Messbasis um sich selbst von B auf A drehen. Zum Einsetzen der Anzeigeneinheit, diese (6) vorsichtig in das vorgesehene Gehäuse schieben bis das “Klicken” der elastischen Befestigungszungen (3 und 4) zu hören ist, welches ihr korrektes Einrasten in den Verschlussösen (1 und 2) bedeutet. ■ Grüne LED-Leuchte, Abb. C 1 Wenn das Gerät als Wandler verwendet wird, also ohne Anzeigeneinheit, zeigt die grüne LED-Leuchte die vorhandene Speisung an, bei ihrem Blinken zeigt die LED-Leuchte auch an, dass das Gerät an ein serielles Netz angeschlossen ist und gerade kommuniziert. A u t o m a t i o n Carlo Gavazzi Controls SpA, Via Safforze, 8 - 32100 Belluno (Italy) Tel. +39 0437 355811, Fax +39 0437 355880 C o m p o n e n t s EM21 72R IM ML 8021723 210917 EM21 72R „3-phase Energy Meter for Retro-fit‰ IN/OUT WARNING! Before closing the CT, make sure that the surfaces of the iron core (exposed when the CT is open) of the current transformer are not dirty or damaged. Ensure the proper closure of the CT. Use CT on power cables (primary) with isolation of at least 1500VAC. Arrange the connecting CT cables in a proper way in order to limit electromagnetic coupling noise. [1] ATTENZIONE! Prima della chiusura del TA, assicurarsi che le superfici [4] del nucleo (esposto quando il TA è aperto) del trasformatore amperometrico non siano sporche o danneggiate. Assicurarsi della corretta chiusura del TA. Utilizzare i TA su cavi di corrente (primario) aventi isolamento di almeno 1500VCA. Disporre i cavi di collegamento dei TA in modo da limitare l’accoppiamento di disturbi di tipo elettromagnetico. DIN VORSICHT! Vor dem Schließen der Stromwandler ist sicherzustellen, dass die Oberflächen des Eisenkerns (wenn die CT geöffnet ist) des Stromwandlers nicht verschmutzt oder beschädigt ist. Gewährleisten Sie ein ordnungsgemäßes Schließen der Stromwandler. Verwenden Sie die Stromwandler auf Stromkabel (primär) mit Isolierung von min. 1500VAC. Verlegen Sie die CT Kabel in geeigneter Weise um elektromagnetische Störungen zu vermeiden. V R S4 85 -0 +0.7mm O pt om os fe t 68x68mm 7 10 6 5 4 2 3 [2] 1 9 [10] ¡ADVERTENCIA! Antes de cerrar el trafo de intensidad, asegurarse de que las superficies de su núcleo (expuestas cuando el trafo está abierto) no estén sucias o dañadas. Cerrar bien el trafo de intensidad. Usar el trafo con cables de potencia (primario) con aislamiento de al menos 1500VCA. Realizar la conexión de los cables del trafo de intensidad correctamente para limitar el ruido por acoplamiento electro-magnético. 7 10 6 8 9 5 4 3 2 [5] 1 (*) [7] ATTENTION! Afin de fermer le transformateur d'intensité, s'assurer que les surfaces du noyau ferreux (surfaces apparentes lorsque le TI est ouvert) ne sont ni sales ni endommagées. S'assurer de la bonne fermeture du transformateur d'intensité. Utiliser le TI sur des câbles de puissance (primaires) avec une isolation minimale de 1500 VCA. Ordonner les câbles de connexion au mieux pour limiter les bruits électromagnétiques. 72x72 8 9 6 8 10 9 10 5 4 6 5 9 [8] 3 9 [11] ENGLISH (*) NOTE: For a correct power supply of the instrument, the neutral must always be connected. ! The provided current transformers MUST be connected so to match with the measuring inputs, that is CT I1 with input I1, CT I2 with input I2 and CT I3 with input I3. ITALIANO 6A, selezione sistema tipo 3P.n [1]- 3 fasi, 4 fili, carico squilibrato, connessione da 3 TA. [2]- 3 fasi, 4 fili, carico squilibrato, connessione da 3 TA e 3 TV 6A, selezione sistema tipo 3P [3]- 3 fasi, 3 fili, carico squilibrato, connessione da 3 TA. [4]- 3 fasi, 3 fili, carico squilibrato, connessione da 3 TA e 2 TV 6A, selezione sistema tipo 3P.1 [5]- 3 fasi, 3 fili, carico equilibrato, connessione da 1 TA (se il neutro è disponibile il collegamento voltmetrico può essere realizzato a soli 2 fili VL1 e N). [6]- 3 fasi, 3 fili, carico equilibrato, connessione da 1 TA e 2TV. 6A, selezione sistema tipo 2P [7]- 2 fasi, 3 fili, connessione da 2 TA. [8]- 2 fasi, 3 fili, connessione da 2 TA e 2 TV 6A, selezione sistema tipo 1P [9]- 1 fase, 2 fili, connessione da 1 TA. [10]- 1 fase, 2 fili, connessione da 1 TA e 1 TV Uscita statica e porta seriale [11]- Uscita statica a opto-mosfet [12]- RS485 connessione a 2 fili [a]- ultimo strumento, [b]- strumento 1...n, [c]- convertitore RS485/RS232. (*) NOTA: Per poter alimentare correttamente lo strumento, il neutro deve sempre essere collegato. VDC/AC 17 ! DEUTSCH 6A Systemwahl: 3P.n [1]- 3-ph, 4-Adrig, asymmetrische Last, 3 Stromwandleranschluss. [2]- 3-ph, 4-Adrig, asymmetrische Last, 3 Strom- und 3 Spannungswandleranschlüsse 6A Systemwahl: 3P [3]- 3-ph, 3-Adrig, asymmetrische Last, 3 Stromwandleranschlüsse. [4]- 3-ph, 3-Adrig, asymmetrische Last, 3 Strom- und 2 Spannungswandleranschlüsse 6A, Systemwahl: 3P.1 [5]- 3-ph, 3-Adrig, symmetrische Last, 1-Stromwandleranschluss (wenn der Nullleiter verfügbar ist, kann der Voltmeteranschluss mit nur 2 Adern VL1 und N vorgenommen werden). [6]- 3-ph, 3-Adrig, symmetrische Last, 1-Stromwandleranschluss und 2 Spannungswandleranschlüsse 6A, Systemwahl: 2P [7]- 2-ph, 3-Adrig, 2 Stromwandleranschlüsse. [8]- 2-ph, 3-Adrig, 3-Strom- und 2 Spannungswandleranschlüsse 6A, Systemwahl: 1P [9]- 1-ph, 2-Adrig, 1-Stromwandleranschluss. [10]- 1-ph, 2-Adrig, 1-Stromwandleranschluss und 1 Spannungswandleranschlüsse Uscite und serielle Schnittstelle [11]- Statischer Ausgang mit Opto-Mosfet [12]- RS485-Anschlüsse, 2-Adrig [a]- letzte Gerät, [b]- Gerät 1...n, [c]- RS485/RS232 Umformer. (*) HINWEIS: Der Neutralleiter muss angeschlossen sein, um eine korrekte Spannungsversorgung des Instrumentes zu gewährleisten. I trasformatori di corrente forniti DEVONO essere collegati rispettando la corrispondenza con gli ingressi di misura, ovvero TA I1 con ingresso I1, TA I2 con ingresso I2 e TA I3 con ingresso I3. 4 5 ! Die vorgesehenen Stromwandler MÜSSEN so verbunden werden, dass die Eingänge I1 des CT1 mit I1, C2 mit I2 und C3 mit I3. 8 7 10 6 3 2 [3] 1 8 10 B+ 18 A- 15 14 13 [6] 5 6 5 16 [a] 6A System type selection 3P.n [1]- 3-ph, 4-wire, unbalanced load, 3-CT connection. [2]- 3-ph, 4-wire, unbalanced load, 3-CT and 3-VT/PT connections 6A System type selection 3P [3]- 3-ph, 3-wire, unbalanced load, 3-CT connection. [4]- 3-ph, 3-wire, unbalanced load, 3-CT and 2-VT/PT connections 6A System type selection 3P.1 [5]- 3-ph, 3-wire, balanced load, 1-CT connection (if the neutral is available the voltage connection can be realized to only 2-wire VL1 and N). [6]- 3-ph, 3-wire, balanced load, 1-CT and 2-VT/PT connection. 6A System type selection 2P [7]- 2-ph, 3-wire, 2-CT connection. [8]- 2-ph, 3-wire, 2-CT and 2-VT/PT connections 6A System type selection 1P [9]- 1-ph, 2-wire, 1-CT connection. [10]- 1-ph, 2-wire, 1-CT and 1-VT/PT connection Static output and serial port [11]- Opto-mosfet static output [12]- RS485 connection 2 wires [a]last instrument, [b]- instrument 1...n, [c]- RS485/RS232 transducer. 7 10 6 8 9 9 8 7 10 6 F=315mA CARLO GAVAZZI 4 [9] 3 A- [b] 2 1 (*) 9 8 7 10 6 5 (*) 9 10 6 5 A- 14 [c] FRANçAIS 6A Sélection du type de réseau: 3P.n [1]- 3 phases, 4 câbles, charge déséquilibrée, connexions 3 TC. [2]- 3 phases, 4 câbles, charge déséquilibrée, connexions 3 TC et 3TT/TP 6A Sélection du type de réseau: 3P [3]- 3 phases, 3 câbles, charge déséquilibrée, connexions 3 TC. [4]- 3 phases, 3 câbles, charge déséquilibrée, connexions 3 TC et 2 TT/TP 6A Sélection du type de réseau: 3P.1 [5]- 3 phases, 3 câbles, charge équilibrée, connexions 1 TC ) (si le neutre est disponible, le branchement voltmétrique peut être réalisé à seulement 2 fils VL1 et N). [6]- 3 phases, 3 câbles, charge équilibrée, connexions 1 TC et 2 TT/TP 6A Sélection du type de réseau: 2P [7]- 2 phases, 3 câbles, connexions 2 TC. [8]- 2 phases, 3 câbles, connexions 3 TC et 2 TT/TP 6A Sélection du type de réseau: 1P [9]- 1 phases, 2 câbles, connexions 1 TC. [10]- 1 phases, 2 câbles, connexions 1 TC et 1 TT/TP Sorties et port série [11]- Sortie statique en opto-mosfet [12]- Connexion RS485 2 câbles [a]- dernier instrument, [b]- instrument 1...n, [c]- Transducteur RS485/RS232. (*) NOTE: Pour une alimentation correcte de l'instrument, le neutre doit toujours être relié. ! 3 B+ 15 13 4 [12] 16 B+ 5 ESPAÑOL 6A, selección del sistema: 3P.n [1]- Trifásico, 4 hilos, carga desequilibrada, conexión 3 trafos de intensidad. [2]- Trifásico, 4 hilos, carga desequilibrada, conexión 3 trafos de intensidad y 3 trafos de tensión/potencia. 6A, selección del sistema: 3P [3]- Trifásico, 3 hilos, carga desequilibrada, conexión 3 trafos de intensidad. [4]- Trifásico, 3 hilos, carga desequilibrada, conexión 3 trafos de intensidad y 2 trafos de tensión/potencia. 6A, selección del sistema: 3P.1 [5]-Trifásico, 3 hilos, carga equilibrada, conexión 1 trafo de intensidad (Si el neutro está disponible, la conexión de la tensión puede realizarse con sólo 2 hilos VL1 y N). [6]- Trifásico, 3 hilos, carga equilibrada, conexión 1 trafo de intensidad y 2 trafos de tensión/potencia. 6A, selección del sistema: 2P [7]- Bifásico, 3 hilos, conexión 2 trafos de intensidad. [8]- Bifásico, 3 hilos, conexiones 2 trafos de intensidad y 2 trafos de tensión/potencia. 6A, selección del sistema: 1P [9]- Monofásico, 2 hilos, conexión 1 trafo de intensidad. [10]- Monofásico, 2 hilos, conexión 1 trafo de intensidad y 1 trafo de tensión/potencia. Salidas y puerto serie [11]- Salida estática opto-mosfet [12]-RS485, conexión dos hilos [a]- último instrumento, [b]- instrumento 1...n, [c]- transductor RS485/RS232. (*) NOTA: Para la correcta alimentación del instrumento, el neutro debe estar siempre conectado. Les transformateurs de courant doivent OBLIGATOIREMENT être raccordés de cette manière afin de correspondre aux mesures d'entrées; soit I1 du TI sur entrée I1, I2 TI sur entrée I2 et I3 du TI sur entrée I3. ! La intensidad suministrada por los transformadores DEBE estar conectada a las corres-pondientes entradas de medida, es decir: CT I1 con entrada I1, CT I2 con entrada I2 y CT I3 con entrada I3. ■ SAFETY PRECAUTIONS Read carefully the instruction manual. If the instrument is used in a manner not specified by the producer, the protection provided by the instrument may be impaired. Maintenance: make sure that the connections are correctly carried out in order to avoid any malfunctioning or damage to the instrument. To keep the instrument clean, use a slightly damp cloth; do not use any abrasives or solvents. We recommend to disconnect the instrument before cleaning it. ENGLISH ■ NORME DI SICUREZZA ■ SICHERHEITSBESTIMMUNGEN Leggere attentamente il manuale istruzioni. Qualora l’apparecchio venisDie Betriebsanleitung aufmerksam lesen. Sollte das Gerät nicht gemäss se adoperato in un modo non specificato dal costruttore, la protezione previder Herstellerangaben verwendet werden, könnte der vom Gerät vorgesehesta dall’apparecchio potrebbe essere compromessa. Manutenzione: assicune Schutz beeinträchtigt werden. Wartung: Beachten Sie den korrekten rarsi che i collegamenti siano effettuati correttamente al fine di evitare qualAnschluss aller Anschlussterminals um eine Beschädigung des Instrumentes siasi malfunzionamento o danneggiamento dello strumento. Per mantenere pulito lo stru- zu vermeiden. Das Gerät mit einem feuchten Tuch reinigen; keine Scheuer- oder mento usare un panno leggermente inumidito; non usare abrasivi o solventi. Si consiglia di Lösemittel verwenden. Das Gerät vor der Reinigung ausschalten. scollegare lo strumento prima di pulirlo. ITALIANO DEUTSCH ■ NORMAS DE SEGURIDAD Lea el manual y siga atentamente las instrucciones. Si se utiliza el equipo de manera distinta de como indica el fabricante, se puede dañar la protección de la que está provisto. Mantenimiento: Asegurarse de que las conexiones son correctas para evitar un mal funcionamiento o daños en el instrumento. Para tener el instrumento limpio, limpiar periódicamente la carcasa con un trapo un poco humedecido. No utilizar productos abrasivos o disolventes. Desconectar el equipo antes de limpiarlo. ■ TECHNICAL SPECIFICATIONS Rated inputs: System type: ■ CARATTERISTICHE TECNICHE Ingressi di misura. Sitema: 3-fase. Tipo corrente: non isolato (mediante TA). Nota: i trasformatori di corrente esterni possono essere collegati a terra individualmente. Portata corrente (mediante sensore di corrente) VV2: 90A. VV3: 150A. VV5: 250A. Tensione (diretto o mediante TA/TV) VVx: 400VLL. Precisione (Display + RS485) Iref: vedi sotto, Un: vedi sotto (@25°C ±5°C, U.R. ≤60%, da 48 a 62 Hz). Portata tensione Modello VVx Un: 160 a 260VLN (277 a 450VLL). Portata corrente Modello VV2 Iref: 15A, Imax: 90A. Modello VV3 Iref: 20A, Imax: 150A. Modello VV5 Iref: 20A, Imax: 250A. Corrente: da 0,05Iref a 0,1Iref: ± (1% RDG + 3DGT). Da 0,1Iref a Imax: ± (1% RDG + 1DGT). Tensione fase-neutro: nel campo Un: ±(0,5% RDG +1DGT). Tensione fase-fase: nel campo Un: ±(1% RDG +1DGT). Frequenza Campo: da 45 a 65Hz; risoluzione: ±1Hz. Potenza attiva: ±(2%RDG +2DGT). Fattore di potenza: ±[0,001+1%(1,000 - “cosj RDG”)]. Potenza reattiva: ±(3%RDG +2DGT). Energia attiva: classe A secondo EN50470-3; classe 2 secondo EN62053-21. Corrente di avviamento VV2: 75mA. VV3, VV5: 100mA. Deriva termica: ≤200ppm/°C @ PF=1 errore fase: ≤0.05/°C. Frequenza di campionamento: 1600 campioni/s @ 50Hz, 1900 campioni/s @ 60Hz. Tempo di aggiornamento display: 1 secondo. Display: 2 linee, 1a linea: 7-DGT, 2a linea: 3-DGT o 1a linea: 3-DGT + 3-DGT, 2a linea: 3-DGT. Tipo LCD, h 7mm. Lettura variabili istantanee 3-DGT. Energie Importate totali: 6+1DGT (07DGT). Sovraccarico indicazione EEE quando il valore misurato eccede il “sovraccarico continuo d’ingresso” (massima capacità di misura). Indicazione Max. e Min. Max. variabili istantanee: 999; energie: 999 999,9 o 9 999 999 (solo positive). L’energia negativa non viene conteggiata ne sottratta. Min. variabili istantanee: 0; energie 0,0. LED rosso (energia consumata) 0,01 kWh per impulso se il rapporto TV è <4 (VV2) o <2 (VV3 o VV5) 0,1 kWh per impulso se il rapporto TV è <40 (VV2) o <23 (VV3 o VV5) 1kWh per impulso se il rapporto TV è >40 (VV2) o >23 (VV3 o VV5). Frequenza massima 16Hz, secondo EN504703. LED verde (posizionato vicino alla morsettiera di collegamento) luce fissa relativo allo stato di “strumento acceso”, a luce lampeggiante in caso di comunicazione RS485 presente e operativa. Misure: Metodo: misura TRMS delle forme d’onda distorte. Tipo di accoppiamento mediante TA esterni. Fattore di cresta≤3 (VV2: 230A picco max.) Sovraccarico corrente senza misurazione valida Continuo VV2: 120A. VV3: 300A.VV5: 360A Sovraccarico tensione: continuo 1,2 Un. Per 500ms 2 Un. Impedenza d’ingresso tensione: autoalimentazione, autoconsumo: <2VA. Frequenza: da 45 a 65 Hz. Tastiera frontale: Due tasti per la selezione delle variabili per la programmazione dei parametri di funzionamento dello strumento. Uscite digitali: Numero d’uscite 1. Tipo programmabile da 0,01 a 9,99 kWh per impulso. Uscita associabile al contatore di energia (kWh). Durata dell’impulso ≥100ms <120ms (ON), ≥120ms (OFF), secondo EN62052-31. Uscita statica: opto-mosfet. Carico VON 2,5 VCA/CC max. 70 mA, VOFF 260 VCA/CC max. Isolamento mediante optoisolatori, 4000 VRMS fra uscita ed ingressi di misura. RS485 tipo multidrop, bidirezionale (variabili statiche e dinamiche). Connessione 2 fili. Distanza massima 1000m, terminazione direttamente sullo strumento. Indirizzi 247, selezionabili mediante tastiera frontale. Protocollo MODBUS/JBUS (RTU). Dati: Dinamici (solo lettura) valori di fase e di sistema. Statici (lettura e scrittura) tutti i parametri di configurazione. Formato dati 1 bit di start, 8 bit di dati, nessuna parità, 1 bit di stop. Velocità di comunicazione 9600 bit/s. Dispositivi in rete, massimo 160 dispositivi nella stessa rete. Isolamento Tramite optoisolatori, 4000 VRMS tra uscite e ingressi di misura. Rapporto di trasformazione: TV da 1,0 a 99,9 / da 100 a 999 / da 1,00k a 6,00k. CT primario fisso: 90, 150 o 250A. La massima potenza misurata non può eccedere 210 MW calcolata come massimo ingresso in corrente e tension. Temperatura di funzionamento: da -20°C a +50°C (da -13°F a 131°F) (U.R. da 0 a 90% senza condensa @ 40°C). Temperatura di immagazzinamento: da -30°C a +70°C (da -22°F a 158°F) (U.R. <90% senza condensa @ 40°C). Categoria d’installazione: cat. III (IEC60664, EN60664). Isolamento (per 1 minuto) 4000 VRMS tra ingressi di misura e uscita. Rigidità dielettrica: 4000 VRMS per 1 minuto. Reiezione CMRR 100 dB, da 48 a 62 Hz. EMC secondo EN62052-11. Scariche elettrostatiche 15kV scarica in aria; Immunità campi elettromagnetici irradianti. Provato con corrente applicata: 10V/m da 80 a 2000MHz. Provato senza corrente applicata: da 30V/m da 80 a 2000MHz; immunità ai transitori veloci sui circuiti degli ingressi di misura in corrente e tensione: 4kV; immunità ad impulso sui circuiti degli ingressi di misura in corrente e tensione: 4kV; emissioni in radiofrequenza secondo CISPR 22. Conformità alle norme: sicurezza IEC60664, IEC61010-1 EN60664, EN61010-1 EN62052-11. Metrologia EN62053-21, EN62053-23. EN50470-3. Uscita impulsiva DIN43864, IEC62053-31. Approvazione CE. Connessioni a vite. Sezione del cavo 2,4 x 3,5 mm. Coppia di serraggio viti Min./Max.: 0,4 Nm / 0,8 Nm. Custodia, dimensioni 72 x 72 x 65 mm. Materiale Noryl PA66, autoestiguenza: UL 94 V-0 Montaggio a pannello e a guida DIN. Grado di protezione: frontale IP40. Connessioni: IP20. Peso circa 400g (imballo incluso). Autoalimentazione da 18 a 260VCA (48-62Hz) (VL1-N). Autoconsumo ≤20VA/1W. ■ TECHNISCHE DATEN Messeingänge. Systemtyp: 3. Strommessung: nicht isoliert (Stromwandler). Anm.: die externen Stromwandler können einzeln geerdet werden. (Stromsensor) VV2: 90A, VV3: 150A, VV5: 250A. Spannung (direkt oder Spannungswandler) VVx: 400VLL. Genauigkeit (Anzeige + RS485) Iref: siehe unten, Nennspannung: siehe unten (bei25°C ±5°C, R.f. ≤60%, 48 bis 62 Hz).Spannungsbereich Modell VVx. Nennspannung: 160 bis 260VLN (277 bis 450VLL). Strombereich Modell VV2 Iref: 15A, Imax: 90A, Modell VV3 Iref: 20A, Imax: 150A, Modell VV5 Iref: 20A, Imax: 250A. Strom von 0,05Iref bis 0,1Iref: ± (1% RDG + 3DGT), von 0,1Iref bis Imax: ± (1% RDG + 1DGT). Spannung Phase - N Im Nennspannungsbereich: ±(0,5% Anzeigeendwert +1stellig). Spannung Phase-Phase: im Nennspannungsbereich: ±(1% Anzeigeendwert +1stellig). Frequenz Bereich: 45 bis 65Hz; Auflösung: ±1Hz. Wirkleistung: ±(2%Anzeigeendwert +2stellig).Leistungsfaktor: ±[0.001+1%(1.000 - “LF Anzeigeendwert”)]. Blindleistung: ±(3%Anzeigeendwert +2stellig). Wirkleistung: Klasse A gemäß EN50470-3; Klasse 2 gemäß EN62053-21. Startstrom: VV2: 75mA. VV3, VV5: 100mA. Temperaturbewegung ≤200ppm/°C @ PF=1, Phasenfehler: ≤0.05/°C. Abtastrate 1600 Abtastpunkte/s bei 50Hz 1900 Abtastpunkte/s bei 60Hz. Erneuerungszeitanzeige: 1 Sekunde. Anzeige: 2 Linien 1. Linie: 7 stellig, 2. Linie: 3 stellig oder 1. Linie: 3 stellig + 3 stellig, 2. Linie: 3 stellig. Art LCD, Höhe 7mm. Anzeigen von Momentanmessgrößen 3 stellig. Energien insgesamt aufgenommen: 6+1stellig Überlastungsanzeige EEEE Anzeige wenn der gemessene Wert die “Dauerhafte Eingangsüberlastung” überschreitet (Messeingangsmaximalwerte). Max. und Min. Anzeige Max Momentanmessgrößen: 999; Energien: 999 999.9 oder 9 999 999 (Nur Positiv). Die negative Energie wird nicht gemessen oder einberechnet. Min. Momentanmessgrößen: 0; Energien 0.0. LED-Leuchten Rote LED-Leuchte (Energieverbrauch). 0,01 kWh je Puls wenn VT Verhältnis <4 (VV2) oder <2 (VV3 oder VV5). 0,1 kWh je Puls wenn VT Verhältnis <40 (VV2) oder <23 (VV3 oder VV5). 1kWh je Puls wenn VT Verhältnis >40 (VV2) oder >23 (VV3 oder VV5). Max Frequenz 16Hz, gemäß EN50470-3. Grüne LED (bei Anschlussklemmblock) für Spannung ein (dauernd) und Kommunikation ein Status: RX-TX (wenn RS485 Option ) (blinken). Messungen: Messmethode TRMS-Messungen von verzerrten Wellenformen. Wandleranschluss durch externe Stromwandler. Scheitelwertfaktor ≤3 (VV2: 230A Maximum). Überlaststrom ohne gültige Messung. Dauer VV2: 120A, VV3: 300A, VV5: 360A. Überlastspannung: Dauer 1.2 Nennspannung für 500ms 2Un. Spannungseingangsimpedanz: Eigenstromversorgung Leistungsaufnahme: <2VA. Frequenz: 45 bis 65 Hz. Tastenfeld: zwei Drucktasten für die Messgrößenwahl und die Programmierung der Geräteparameter. Impulsausgang: Anzahl der Ausgänge 1. Typ programmierbar von 0.01 bis 9.99 kWh pro Impuls. Mit Energiezähler verknüpfbarer Ausgang (kWh). Impulsdauer ≥100ms <120ms (ON), ≥120ms (OFF), gemäß EN62052-31. Ausgang Statisch: Opto-Mosfet. Last VON 2.5 VAC/DC max. 70 mA, VOFF 260 VAC/DC max. Isolation durch Optokoppler, 4000 VRMS Ausgang Eingangsmessungen. RS485 Art Multidrop, Bidirektional (Statik- und Dynamikgrößen) Anschlüsse 2 Adern. Höchstabstand 1000m, Terminierung direkt am Gerät. Adressen 247, wählbar über die vorderen Steuerhebel Protokoll MODBUS/JBUS (RTU). Datenübertragung: Dynamisch (nur lesen) Einzelphasen und Systemmesswerte. Alle Konfigurationsparameter. Datenformat 1 Start-bit, 8 Daten-bits, keine Parität,1 Stop-bit. Übertragungsgeschwindigkeit 9600 bits/s. Treibereingangsleistung 1/5 Leistungsaufnahme. Maximum Maximal Geräte 160 am gleichen Bus Isolation durch Optokoppler, 4000 VRMS-Ausgang zum Messeingang. Wandlerverhältnis: Spannungswandler 1.0 bis 99.9 / 100 bis 999 /1.00k bis 6.00k Stromwandler Primärstrom, fest: 90, 150 oder 250A. Die maximal gemessene Leistung darf 210 MW nicht überschreiten, die als Maximalwerte für Eingangsspannung und Strom berechnet werden. Betriebstemperatur: -20°C bis +50°C (-13°F bis 131°F) (R.f. von 0 bis 90% nicht kondensierend bei 40°C). Lagertemperatur: -30°C bis +70°C (-22°F bis 158°F) (R.f. <90% nicht kondensierend bei 40°C). Gebrauchskategorie Kat. III (IEC60664, EN60664). Isolation (für 1 Minute) 4000 VRMS zwischen Eingangsmessung und Digitalausgang. Durchschlagfestigkeit 4000 VRMS für 1 Minute. Rauschdrückungsverhältnis CMRR 100 dB, 48 to 62 Hz. EMV gemäß EN62052-11. Elektrostatische Entladungen 15kV Luftentladung; Strahlungsimmunität Stromtest: 10V/m von 80 bis 2000MHz; Elektromagnetfelder Test stromlos: 30V/m von 80 bis 2000MHz; Ladungsimpuls am Stromund Eingangsspannungsmesskreis: 4kV Leitungsgeb. Störausstrahlung Gemäß CISPR 22. Standardkonformität: Sicherheit IEC60664, IEC61010-1 EN60664, EN61010-1. EN6205211 Messung EN62053-21, EN62053-23, EN50470-3. Impulsausgang DIN43864, IEC6205331. Zulassungen: CE. Anschlüsse: Schraubanschluss Kabelquerschnitt 2.4 x 3.5 mm Min./Max. Anzugsmoment: 0.4 Nm / 0.8 Nm. Gehäuse: Abmessungen (LxHxB) 72 x 72 x 65 mm. Material Noryl PA66, self-extinguishing: UL 94 V-0. Montage Tafel und DIN-Schiene. Schutzgrad: Vorderseite IP40 Schraubenklemmen IP20. Gewicht: Ca. 400 g (inkl. Verpackung). Eigenstromversorgung: 18 bis 260VAC (48-62Hz) (VL1-N). Leistungsaufnahme: ≤20VA/1W. ■ PRÉCAUTIONS DE SECURITE Lire attentivement le manuel de l’utilisateur. Si l’appareil est utilisé dans des conditions différentes de celles spécifiées par le fabricant, le niveau de protection prévu par l’instrument peut être compromis. Entretien: s’assurer que les connexions sont réalisées correctement dans le but d’éviter toutes fautes ou endommagements de l’appareil. Pour nettoyer l’instrument, utiliser un chiffon humide; ne pas utiliser d’abrasifs ou de solvants. Il faut déconnecter le dispositif avant de procéder au nettoyage. ■ CARACTÉRISTIQUES D’ENTRÉE Puissances nominales: type de rèseau: 3 type de courant: non isolé (par CT). Note: les transformateurs de courant externe peuvent être branchés à la masse séparément. Gamme de courant (par capteur de courant) VV2: 90A, VV3: 150A, VV5: 250A. Tension (directe ou par TT/TP) VVx: 400VLL. Précision (Écran + RS485) Iref: voir plus bas, Un: voir plus bas (@25°C ±5°C, R.H. ≤60%, 48 à 62 Hz). Gamme de tension modèle VVx Un: 160 à 260VLN (277 à 450VLL). Gamme de courant modèle VV2 Iref: 15A, Imax: 90A; modèle VV3 Iref: 20A, Imax: 150A; modèle VV5 Iref: 20A, Imax: 250A. Courant de 0,05Iref à 0,1Iref: ± (1% RDG + 3DGT); de 0,1Iref à Imax: ± (1% RDG + 1DGT). Tension phaseneutre sur la gamme Un: ±(0,5% RDG +1DGT). Tension phase-phase sur la gamme Un: ±(1% RDG +1DGT). Fréquence gamme: 45 à 65Hz; résolution: ±1Hz. Énergie active: ±(2%RDG +2DGT). Facteur de puissance: ±[0.001+1%(1.000 - “PF RDG”)]. Énergie réactive: ±(3%RDG +2DGT). Énergie active kWh: classe A selon EN50470-3; classe 2 selon EN62053-21. Courant de démarrage: VV2: 75mA. VV3, VV5: 100mA. Dérive de température ≤200ppm/°C @ PF=1. Erreur de phase: ≤0.05/°C. Taux d’échantillonnage: 1600 échantillon/s @ 50Hz, 1900 échantillon/s @ 60Hz. Temps de mise à jour écran: 1 seconde. Écran: 2 lignes 1° ligne: 7-DGT, 2° ligne: 3-DGT ou 1° ligne: 3-DGT + 3-DGT, 2° ligne: 3-DGT. Type LCD, h 7mm. Affichage variables instantanées 3-DGT. Énergies total importé: 6+1DGT. État de surcharge EEE indication quand la valeur mesurée dépasse la “surcharge entrées continues” (capacité de mesure maximum) Indications Max. et Min. Variables instantanées max: 999; énergies: 999 999.9 ou 9 999 999 (positif seulement). L'énergie négative n'est ni mesurée ni déduite. Variables instantanées min.: 0; énergies 0.0. LEDs. LED rouge pour consommation d’énergie, 0,01 kWh par impulsion si ratio TT <4 (VV2) ou <2 (VV3 ou VV5); 0,1 kWh par impulsion si ratio TT <40 (VV2) ou <23 (VV3 ou VV5): 1kWh par impulsion si ratio TT >40 (VV2) ou >23 (VV3 ou VV5); fréquence max 16Hz, suivant EN50470-3. LED verte (côté bornier) pour présence alimentation (stable) et état de la communication: RX-TX (en case d’option RS485) clingnotante. Mesures: méthode TRMS de formes d’onde distordues. Type de couplage: au moyen d’un TC externe. Facteur de crête ≤3 (VV2: pic max. 230A). Surcharges de courant sans mesure valide. Continues VV2: 120A; VV3: 300A; VV5: 360A. Surcharge de tension: continues 1.2 Un pendant 500ms 2Un. Impédance tension d’entrée: auto-alimentation consommation alimentation: < 2VA. Fréquence: 45 à 65 Hz. Clavier: deux boutons pour la sélection et programmation variable des paramètres de fonctionnement de l’instrument. Sortie à impulsions: nombre de sorties 1. Type programmable de 0.01 à 9.99 kWh par impulsions. Sortie pouvant être branchée aux compteurs d’énergie (kWh). Durée d’impulsion ≥100ms < 120ms (ON), ≥120ms (OFF), selon EN62052-31. Sortie statique: opto-mosfet. Charge VON 2.5 VCA/CC max. 70 mA, VOFF 260 VCA/CC max. Isolement: par optocoupleurs, sortie 4000 Veff de l’ entrée mesure à la sortie. RS485 type Multi\point, bidirectionnel (variables statiques et dynamiques). Branchements 2-fils. distance max. 1000m, terminaison directement sur l’instrument. Adresses 247, à sélectionner au moyen du clavier frontal. Protocole MODBUS/JBUS (RTU). Donnée. Dynamique (lecture seulement) valeurs monophasées et triphasées. Tous les paramètres configuration. Format de données 1 bit de démarrage, 8 bit de donnée, pas de parité,1 bit d’arrêt. Taux (Baud): 9600 bits/s. Capacité entrée driver 1/5 de charge unité. Max. 160 émetteurs-récepteurs sur le même bus. Isolation au moyen de optocoupleurs, sortie 4000 VRMS vers entrées de mesure. Rapport de transformation: TT (TP) 1.0 à 99.9 / 100 à 999 / 1.00k à 6.00k TC courant primaire fixe: 90, 150 or 250A. La puissance maximale mesurée ne peut excéder 210 MW calculé comme courant et tension d’entrée maximum. Température de fonctionnement: -20°C à +50°C (-13°F à 131°F) (R.H. de 0 à 90% pas de condensation @ 40°C). Température de stockage: -30°C à +70°C (-22°F à 158°F) (R.H. < 90% pas de condensation @ 40°C). Catégorie de l’installation: Cat. III (IEC60664, EN60664). Isolation (pour 1 minute): 4000 VRMS entre mesure d’entrée et sortie numérique. Rigidité diélectrique: 4000 VRMS pour 1 minute. Rejet de bruit CMRR: 100 dB, 48 à 62 Hz. EMC selon EN62052-11. Décharges électrostatiques 15kV décharge dans l’air; immunité à l’irradiation. Test avec courant: 10V/m de 80 à 2000MHz; champs électromagnétiques test sans courant: 30V/m de 80 à 2000MHz; èclatement sur mesure de courant et tension de circuit d’entrée: 4kV. Immunité aux perturbations par conduction 10V/m de 150KHz à 80MHz. Suppression fréquence radio selon CISPR 22. Conforme aux standards: Sécurité IEC60664, IEC61010-1 EN60664, EN61010-1 EN62052-11 Métrologie EN62053-21, EN62053-23, EN50470-3. Sortie à impulsions DIN43864, IEC62053-31. Certification: CE. Branchements: Type par vis. Section du câble 2.4 x 3.5 mm. Couple de serrage de vis Min./Max.: 0.4 Nm / 0.8 Nm. Boîtier: dimensions (WxHxD) 72 x 72 x 65 mm. Matériel Noryl PA66, auto-extincteur: UL 94 V-0. Support Panneau et DIN-rail. Indice de protection: Frontal IP40 Bornes de vis IP20. Poids: environ 400 g (emballage inclus). Auto-alimentation: 18 à 260VAC (48-62Hz) (VL1-N). Consommation d’énergie: ≤20VA/1W. ■ ESPECIFICACIONES TÉCNICAS Entradas nominales: tipo de sistema: trifásico. Tipo de intensidad: no aislada (mediante CT). Nota: los transformadores de intensidad externos (CT) pueden ser conectados a tierra individualmente. Escala de intensidad (mediante trafos de intensidad) VV2: 90A, VV3: 150A, VV5: 250A. Tensión (continua o por VT/PT) VVx: 400VLL. Precisión (Display + RS485) (@25°C ±5°C, R.H. ≤60%, 48 a 62 Hz) Iref: ver a continuación, Vn: ver a continuación. Escala de tensión modelo VVx Vn: 160 a 260VLN (277 a 450VLL). Escala de intensidad modelo VV2 Iref: 15A, Imax: 90A, modelo VV3 Iref: 20A, Imax: 150A, modelo VV5 Iref: 20A, Imax: 250A. Intensidad de 0,05Iref a 0,1Iref: ± (1% lec. + 3dig.). De 0,1Iref a Imax: ± (1% lec. + 1dig.). Tensión entre fase y neutro en la escala Vn: ±(0,5% lec. + 1dig.). Tensión entre fases en la escala Vn: ±(1% lec. + 1dig.). Frecuencia intervalo: 45 a 65Hz; Resolución: ±1Hz. Potencia activa: ±(2% lec. + 2dig). Factor de potencia: ±[0,001 + 1%(1,000 – lec. PF)]. Potencia reactiva: ±(2% lec. + 2dig.). Energía activa: clase A según norma EN50470-3. Energía reactiva: clase 2 según norma EN62053-23. Intensidad de arranque: VV2, VV3: 10mA. VV5: 50mA. Deriva térmica ≤200ppm/°C @ PF=1. Error de fase: ≤0.05/°C. Frecuencia de muestreo: 1600 lecturas/s a 50Hz 1900 lecturas/s a 60Hz. Frecuencia de muestreo: 1600 lecturas/s a 50Hz 1900 lecturas/s a 60Hz. Tiempo de refresco del display: 1 segundo. Display: 2 líneas primera línea: 7 dígitos, segunda línea: 3 dígitos o primera línea: 3 + 3 dígitos, segunda línea: 3 dígitos. Tipo LCD, altura 7 mm. Lectura de variables instantáneas 3 dígitos. Energía consumida: 6 + 1 dígitos indicación de sobrerrango. Indicación EEE cuando el valor medido excede la “Capacidad de entrada de forma continua” (capacidad máxima de medida). Indicación máx. y mín. Variables instantáneas máximas: 999; energías: 999, 999.9 o 9 999 999. Variables instantáneas mínimas: 0; energías: 0,0. LEDs. LED rojo (consumo de energía) 0,01 kWh por pulso si la relación del trafo de tensión VT es <4 (VV2) o <2 (VV3 o VV5); 0,1 kWh por pulso si la relación del trafo de tensión VT es <40 (VV2) o <23 (VV3 o VV5); 1kWh por pulso si la relación del trafo de tensión VT es >40 (VV2) o >23 (VV3 o VV5). Frecuencia máxima 16Hz, según norma EN50470-3. El LED verde (junto a los bloques de terminales) indica el estado de la alimentación (estable) y de la comunicación: RX-TX parpadeando (sólo en caso de la opción RS485). Medidas: medida TRMS de tensión/intensidad de una onda distorsionada. Tipo de conexión mediante CTs externos. Factor de cresta: ≤3 (VV2: 230A pico máx.). Protección contra sobreintensidades: sin medición válida. Permanente VV2: 120A, VV3: 300A, VV5: 360A. Protección contra sobretensiones: permanente 1,2 Vn durante 500ms 2 Vn. Impedancia de entrada (tensión): autoalimentación eléctrica consumo de energía: <2VA. Frecuencia: 45 a 65 Hz. Teclado: dos pulsadores para selección de variables y programación de los parámetros de trabajo del instrumento. Salida de pulso: Número de salidas 1. Tipo programable de 0,01 a 9,99 kWh por pulso. Salida conectable a los contadores de energía eléctrica (kWh). Duración del pulso ≥100ms <120ms (ON), ≥120ms (OFF), según norma EN62052-31. Salida estática: optomosfet. Carga VON 2.5 VCA/CC máx. 70 mA, VOFF 260 VCA/CC máx. Aislamiento mediante optoacopladores, 4000 VRMS entre salida y entradas de medida. RS485 tipo multidrop, bidireccional (variables estáticas y dinámicas). Conexiones 2 hilos. Distancia máx. 1000m, terminación directamente en el instrumento. Direcciones 247, seleccionables mediante el teclado frontal. Protocolo MODBUS/JBUS (RTU). Datos: Dinámicos (solo lectura). Estáticos (lectura y escritura). Todos los parámetros de configuración. Formato de datos 1 bit inicial, 8 bits de datos, sin paridad, 1 bit final. Velocidad en baudios 9600 bits/s. Capacidad de entrada de driver 1/5 carga unitaria. Máximo 160 transceptores en el mismo bus. Aislamiento mediante optoacopladores, 4000 VRMS entre salida y entrada de medida. Relación del transformador: VT (PT) 1,0 a 99,9 / 100 a 999 / 1,00k a 6,00k. CT primario: 90, 150 o 250A. La potencia máxima medida no puede sobrepasar de 210 MW calculada como la tensión e intensidad máximas de entrada. Temperatura de funcionamiento: -20ºC a +50ºC (-13ºF a 131ºF) (HR de 0 a 90% sin condensación a 40ºC). Temperatura de almacenamiento: -30ºC a +70ºC (-22ºF a 158ºF) (HR < 90% sin condensación a 40ºC). Categoría de la instalación: Cat. III (IEC60664, EN60664). Aislamiento (durante 1 minuto) 4000 VRMS entre entradas de medida y salida digital. Resistencia dieléctrica: 4000 VRMS durante 1 minuto. Rechazo al ruido CMRR 100 dB, 48 a 62 Hz. Compatibilidad electrom. (EMC) según norma EN62052. Descargas electrostáticas descarga en el aire 15kV; inmunidad a los campos electromagnéticos prueba con corriente: 10V/m de 80 a 2000MHz; prueba sin corriente: 30V/m de 80 a 2000MHz; ráfagas en el circuito de entradas de medida de intensidad y tensión: 4kV. Inmunidad a las perturbaciones conducidas 10V/m de 150KHz a 80MHz. Pico de tensión: en el circuito de entradas de medida de intensidad y tensión: 6kV. Emisiones de radiofrecuencia según norma CISPR 22. Conformidad con las normas: Seguridad IEC60664, IEC61010-1 EN60664, EN61010-1 EN62052-11. Metrología EN62053-23, EN50470-3. Salida de pulso DIN43864, IEC62053-31. Homologaciones: CE. Conexiones: a tornillo. Sección del cable 2,4 x 3,5 mm. Par de apriete mín./máx.: 0,4 Nm / 0,8 Nm. Caja: Dimensiones (An. x Al. x P.) 72 x 72 x 65 mm. Material Noryl PA66, autoextinguible: UL 94 V-0. Montaje en panel y a carril DIN. Grado de protección: Panel frontal IP40. Conexiones IP20. Peso: Aprox. 400 g (embalaje incluido). Autoalimentación: 18 a 260VCA (48-62Hz) (VL1-N). Consumo de potencia: ≤20VA/1W. 3. Current range (by CT) VV2: 90A, VV3: 150A, VV5: 250A. Voltage (direct or by VT/PT). VVx: 400VLL. Accuracy (Display + RS485) Iref: see below; Un: see below (@25°C ±5°C, R.H. ≤60%, 48 to 62 Hz). Voltage range VVx model Un: 160 to 260VLN (277 to 450VLL). Current range VV2 model Iref: 15A, Imax: 90A, VV3 model Iref: 20A, Imax: 150A, VV5 model Iref: 20A, Imax: 250A. Current From 0,05Iref to 0,1Iref: ± (1% + 3DGT). Phase-neutral voltage In the range Un: RDG ±(0.5% RDG +1DGT). Phase-phase voltage In the range Un: ±(1% RDG +1DGT). Frequency Range: 45 to 65Hz; resolution: ±1Hz. Active power: ±(2%RDG +2DGT). Power Factor: ±[0.001+2%(1.000 - “PF RDG”)]. Reactive power: ±(3%RDG +2DGT). Active energy class A according to EN50470-3; class 2 according to EN62053-21. Start up current VV2: 75mA. VV3, VV5: 100mA. Temperature drift: ≤200ppm/°C @ PF=1. Phase error: ≤0.05/°C. Sampling rate: 1600 samples/s @ 50Hz, 1900 samples/s @ 60Hz. Display refresh time: 1 second. Display: 2 lines 1st line: 7-DGT, 2nd line: 3-DGT or 1st line: 3-DGT + 3-DGT, 2nd line: 3DGT. Type LCD, h 7mm. Instantaneous variables read-out 3-DGT. Energies: imported, Total: 6+1DGT (or 7 DGT). Overload status EEE indication when the value being measured is exceeding the “Continuous inputs overload” (maximum measurement capacity). Max. and Min. indication: Max. instantaneous variables: 999; energies: 999 999.9 or 9 999 999 (positive only). The negative energy is neither metered nor subtracted. Min. instantaneous variables: 0; energies 0.0. LEDs. Red LED (Energy consumption) 0.01 kWh by pulse if VT ratio is <4 (VV2) or <2 (VV3 or VV5) 0.1 kWh by pulse if VT ratio is <40 (VV2) or <23 (VV3 or VV5) 1kWh by pulse if VT ratio is >40 (VV2) or >23 (VV3 or VV5). Max frequency: 16Hz, according to EN50470-3. Green LED (on the terminal bolcks side) for power on (steady) and communication status: RX-TX (in case of RS485 option only) blinking. Measurements: Method TRMS measurements of distorted wave forms. Coupling type: by means of external CT’s. Crest factor:≤3 (VV2: 230A max. peak). Current Overloads: without valid measurement. Continuous VV2: 120A, VV3: 300A, VV5: 360A. Voltage Overloads: continuous 1.2 Un. For 500ms 2 Un. Voltage input impedance: self-power supply power consumption: <2VA. Frequency : 45 to 65 Hz. Key-pad: two push buttons for variable selection and programming of the instrument working parameters. Pulse output Number of outputs 1. Type programmable from 0.01 to 9.99 kWh per pulses. Output connectable to the energy meters (kWh). Pulse duration ≥100ms < 120ms (ON), ≥120ms (OFF), according to EN62052-31. Output Static: opto-mosfet. Load VON 2.5 VAC/DC max. 70 mA, VOFF 260 VAC/DC max. Insulation by means of optocuplers, 4000 VRMS output to measuring inputs. RS485 type Multidrop, bidirectional (static and dynamic variables). Connections 2-wire. Max. distance 1000m, termination directly on the instrument. Addresses 247, selectable by means of the front keypad. Protocol MODBUS/JBUS (RTU). Data: Dynamic (reading only) single phase and system values. Static (reading and writing). All the configuration parameters. Data format 1 start bit, 8 data bit, no parity,1 stop bit. Baud-rate 9600 bits/s. Driver input capability 1/5 unit load. Maximum 160 transceivers on the same bus. Insulation by means of optocouplers, 4000 VRMS output to measuring input. Transformer ratio: VT (PT) 1.0 to 99.9 / 100 to 999 / 1.00k to 6.00k CT: fixed primary: 90, 150 or 250A. The maximum power being measured cannot exceed 210 MW calculated as maximum input voltage and current. Operating temperature -20°C to +50°C (-13°F to 131°F) (R.H. from 0 to 90% non-condensing @ 40°C). Storage temperature -30°C to +70°C (-22°F to 158°F) (R.H. <90% non-condensing @ 40°C). Installation category Cat. III (IEC60664, EN60664). Insulation (for 1 minute) 4000 VRMS between measuring inputs and digital output. Dielectric strength 4000 VRMS for 1 minute. Noise rejection CMRR 100 dB, 48 to 62 Hz. EMC According to EN62052-11. Electrostatic discharges 15kV air discharge; Immunity to irradiated test with current: 10V/m from 80 to 2000MHz; Electromagnetic fields test without any current: 30V/m from 80 to 2000MHz; Burst on current and voltage measuring inputs circuit: 4kV. Immunity to conducted disturbances 10V/m from 150KHz to 80MHz. Surge on current and voltage measuring inputs circuit: 6kV; Radio frequency suppression according to CISPR 22. Standard compliance: safety IEC60664, IEC61010-1 EN60664, EN61010-1 EN62052-11. Metrology EN62053-21, EN62053-23, EN50470-3. Pulse output DIN43864, IEC62053-31. Approvals: CE. Connections: Screwtype. Cable cross-section area: 2,4 x 3,5 mm. Min./Max. screws tightening torque: 0.4 Nm / 0.8 Nm. Housing: dimensions (WxHxD) 72 x 72 x 65 mm. Material Noryl PA66, self-extinguishing: UL 94 V-0. Mounting: panel and DIN-rail. Protection degree: front IP40. Screw terminals: IP20. Weight: approx. 400 g (packing included). Self power supply 18 to 260VAC (48-62Hz) (VL1-N). Power consumption: ≤20VA/1W. UL NOTES “Max. Surrounding Air of 40°C”. “Use 60 or 75°C copper (CU) conductor and wire size No. 24-12 AWG, stranded or solid”. “Terminal tightening torque of 4 to 7 Lb-In (0.4 to 0.8Nm)”. “Open Type Device”. Current measuring input terminals must be connected only through Carlo Gavazzi accessories current transformers TU10P-90A or TU16P-150A or TU24P-250A, with one lead connected to Earth. Direct connection to the line voltage is not allowed. FRANçAIS ESPAÑOL
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

CARLO GAVAZZI EM2172RVV23XOXX Guía de instalación

Tipo
Guía de instalación