Watts PIPFM1-PRESS 1 1/4 Guía de instalación

Tipo
Guía de instalación
Gaskets Not
Supplied
Purge Port
Shut Off Valve
Watts PIPF-M1
Watts IPF-M2
Watts PIPF-M1
Shut Off Valve
Purge Port
Watts IPF-M2
Gaskets Not
Supplied
Series PIPF-M1 Pump Flanges are designed to simplify the
installation, service and removal of pumps and circulators in
hydronic systems. PIPF-M1 pump flanges feature a purge
port which allows system purging at the pump or circulator.
PIPF-M1 pump flanges also feature a swivel flange, which
allows you to rotate the valve body so you can put the purge
port in the best position for your application.
Installation
To install simply bolt the PIPF-M1 flange to the return side
of the pump/circulator flange. Be sure that there is a pump
gasket between each flange. Contact your wholesaler if you
require a gasket.
1. Bolt the PIPF-M1 flange to the return side of the pump/
circulator flange.
Do not install the PIPF flange without
a pump gasket.
2. Tighten the bolts joining the PIPF-M1 flange to the pump
flange, taking care not to over-tighten. Hand-tighten plus
1
2 turn is recommended.
3. When the system is filled, inspect for leaks at the flange.
Tighten the bolts as needed, taking care not to over-tighten.
4. For solder models only, slip the plastic tether on the purge
port over the slotted ball valve to protect tether from heat
applied during soldering.
For Solder Models
This valve is designed to be soft soldered into lines without dis as sem-
bly, using a low temperature solder (420°F / 215ºC). Other sol ders
such as 95/5 tin antimony (460°F / 238ºC) or
96/4 tin silver (430°F / 221ºC) can be used, however, extreme caution
must be used to prevent seal dam age. Higher temperature solders
will dam age the seat ma te ri al. ANSI B16.18 states that the max i mum
operating pres sure of 50-50 solder connections is 200psi at 100°F
(1380kPa at 38ºC) and de creas es with higher temperatures.
Apply heat with the flame directed AWAY from the center of the valve
body. Excessive heat can harm the seats.
Purging the Hydronic System
1. Isolate all circuits by shutting the isolation or zone valve and
the PIPF-M1 shutoff valves. Remove cap from purge port.
2. Starting with one circuit, attach a hose to the purge port of
the PIPF-M1. (Note: A hose must be run into a suitable floor
drain or run to the outside to accommodate purged water).
3. Open the PIPF-M1’s purge port by turning the handle
1
4 turn, and open the isolation or zone valve.
4. Open the make up water or boiler fill valve’s fast fill
feature. Allow water to flow through the PIPF-M1’s purge
port until the water runs clear and free of air bubbles.
5. Close the make up water or boiler fill valve.
6. Next close the PIPF-M1 purge port by turning the purge
handle
1
4 turn until the water stops flowing. Shut off the
isolation or zone valve. Replace cap on purge port.
7. Repeat steps 2 – 6 for each zone.
8. Upon completion of purging all zones of air, open the
PIPF-M1 shutoff valve.
PIPF-M1
S eries PIPF-M1
IS-PIPF-M1
PIPF-M1
3
4" - 1
1
4" (20-32mm)
Installation
Instructions
Instructions
d’installation
Instrucciones
de instalacn
Isolation Pump Flange with Purge Port
and Swivel Flange
Bride d’isolation de pompe avec port de
vidange et bride pivotante
Reborde de la bomba de aislamiento
con puerto de purga y reborde giratorio
Garantie limitée: Watts Regulator Co. (la « Société ») garantit que chacun de ses produits est exempt de vice
de matériau et de fabrication dans des conditions normales d’utilisation pour une période d’un an à compter
de la date d’expédition d’origine. Dans l’éventualité où de tels vices se manifesteraient pendant la période de
garantie, la Société, à sa discrétion, remplacera ou reconditionnera le produit sans frais.
LA PRÉSENTE GARANTIE EST EXPRESSE ET REPRÉSENTE LA SEULE GARANTIE OFFERTE PAR LA
SOCIÉTÉ POUR CE PRODUIT. LA SOCIÉTÉ N’OFFRE AUCUNE AUTRE GARANTIE, EXPRESSE OU TACITE.
PAR LA PRÉSENTE, LA SOCIÉTÉ REJETTE SPÉCIFIQUEMENT TOUTE AUTRE GARANTIE, EXPRESSE OU
TACITE, NOTAMMENT TOUTE GARANTIE TACITE DE QUALITÉ MARCHANDE OU D’ADAPTATION À UN
BUT PARTICULIER.
Le recours décrit dans le premier paragraphe de cette garantie constitue le seul recours à toute violation
de la présente garantie. La Sociéne saurait être tenue responsable de tout dommage accessoire, spécial
ou indirect, y compris, de façon non limitative : la perte de profits ou le coût afférent à la réparation ou au
remplacement d’autres biens qui seraient endommagés par suite du fonctionnement incorrect dudit produit ;
d’autres coûts résultant de frais de main-d’œuvre, de retards, de vandalisme, de négligence, d’une obstruc-
tion causée par des matériaux étrangers, de dommages causés par une eau impropre, des produits chimiques
ou par tout autre événement échappant au contrôle de la Société. La présente garantie est déclarée nulle et
non avenue en cas d’usage abusif ou incorrect, d’application, d’installation ou d’entretien incorrects ou de
modification du produit.
Certains États n’autorisent pas les limitations de durée d’une garantie tacite ou l’exclusion ou la limitation des
dommages accessoires ou indirects. Les limitations susmentionnées peuvent donc ne pas s’appliquer à vous.
Cette garantie limitée vous donne des droits spécifiques et il se peut que vous ayez aussi d’autres droits qui
varient d’un État à l’autre. Veuillez vous référer aux lois applicables de l’État pour déterminer vos droits en
la matière. DANS LA MESURE PERMISE PAR LA LOI APPLICABLE DE L’ÉTAT, TOUTES LES GARANTIES
TACITES NE POUVANT PAS ÊTRE REJETÉES, Y COMPRIS LES GARANTIES TACITES DE QUALITÉ
MARCHANDE ET D’ADAPTATION À UN BUT PARTICULIER, SONT LIMITÉES QUANT À LEUR DURÉE À UN
AN À COMPTER DE LA DATE D’EXPÉDITION D’ORIGINE.
IS-PIPF-M1 1103 EDP# 2915860 © Watts, 2011
USA: 815 Chestnut St., No. Andover, MA 01845-6098; www.watts.com
Canada: 5435 North Service Rd., Burlington, ON. L7L 5H7; www.wattscanada.ca
Garantía limitada: Watts Regulator Co. (en adelante, “la Compañía”) garantiza, por un período de un o a
partir de la fecha de embarque original, que sus productos están libres de defectos en materiales y mano de obra
bajo condiciones de uso normal. En caso de que se encuentren tales defectos dentro del período de garantía, la
Compañía reemplazará o reacondicionará, a su elección, el producto sin costo alguno.
LA GARANTÍA AQ ESTIPULADA SE OTORGA EN FORMA EXPRESA Y ES LA ÚNICA GARANTÍA
OTORGADA POR LA COMPAÑÍA EN RELACIÓN CON EL PRODUCTO. LA COMPAÑÍA NO OTORGA NINGUNA
OTRA GARANTÍA, YA SEA EXPRESA O IMPLÍCITA. LA COMPAÑÍA POR LA PRESENTE RENUNCIA
ESPECÍFICAMENTE A TODAS LAS DEMÁS GARANTÍAS, EXPRESAS O IMPLÍCITAS, INCLUYENDO SIN
LIMITACIÓN, LAS GARANTÍAS IMPLÍCITAS DE APTITUD PARA LA COMERCIALIZACIÓN E IDONEIDAD PARA
UN PROPÓSITO EN PARTICULAR.
La solución descrita en el primer rrafo de esta garantía constituirá la única y exclusiva solución por incum-
plimiento de garantía, y la Compañía no se hará responsable por daños accidentales, especiales o indirectos,
incluyendo sin limitación, la rdida de ganancias o el costo de reparación o reemplazo de otra propiedad que
resulte dañada por el mal funcionamiento de este producto, otros costos resultantes por mano de obra, retardos,
vandalismo, negligencia, obstrucciones ocasionadas por materiales extraños, daños debidos a condiciones
adversas del agua, químicos o cualquier otra circunstancia sobre la cual la Compañía no tenga control. Esta
garantía no tendrá validez en cualquier caso de abuso, uso indebido, aplicación incorrecta, instalación inadecua-
da, o mantenimiento adecuado o alteración del producto.
Algunos Estados no permiten limitaciones en la duración de una garantía implícita y algunos Estados no per-
miten la exclusión o limitación de daños accidentales o indirectos. Por lo tanto, es posible que las limitaciones
anteriores no sean aplicables en su caso. Esta garantía limitada le da derechos legales específicos; usted podría
tener también otros derechos que varían según el Estado. Usted debe consultar las leyes estatales aplicables
para determinar sus derechos. EN LA MEDIDA EN QUE SEA CONGRUENTE CON LAS LEYES ESTATALES
APLICABLES, CUALQUIER GARANTÍA IMPLÍCITA QUE NO SEA RECHAZADA, INCLUYENDO LAS GARANTÍAS
IMPLÍCITAS DE APTITUD PARA LA COMERCIALIZACIÓN E IDONEIDAD PARA UN PROPÓSITO EN
PARTICULAR, SE LIMITA EN SU DURACIÓN A UN AÑO A PARTIR DE LA FECHA DEL EMBARQUE ORIGINAL.
IS-PIPF-M1 1103 EDP# 2915860 © Watts, 2011
USA: 815 Chestnut St., No. Andover, MA 01845-6098; www.watts.com
Canada: 5435 North Service Rd., Burlington, ON. L7L 5H7; www.wattscanada.ca
IS-PIPF-M1 1103 EDP# 2915860 © Watts, 2011
USA: 815 Chestnut St., No. Andover, MA 01845-6098; www.watts.com
Canada: 5435 North Service Rd., Burlington, ON. L7L 5H7; www.wattscanada.ca
Limited Warranty: Watts Regulator Co. (the “Company”) warrants each product to be free from defects
in material and workmanship under normal usage for a period of one year from the date of original ship-
ment. In the event of such defects within the warranty period, the Company will, at its option, replace
or recondition the product without charge.
THE WARRANTY SET FORTH HEREIN IS GIVEN EXPRESSLY AND IS THE ONLY WARRANTY
GIVEN BY THE COMPANY WITH RESPECT TO THE PRODUCT. THE COMPANY MAKES NO OTHER
WARRANTIES, EXPRESS OR IMPLIED. THE COMPANY HEREBY SPECIFICALLY DISCLAIMS ALL
OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO THE IMPLIED
WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
The remedy described in the first paragraph of this warranty shall constitute the sole and exclusive
remedy for breach of warranty, and the Company shall not be responsible for any incidental, special
or consequential damages, including without limitation, lost profits or the cost of repairing or replac-
ing other property which is damaged if this product does not work properly, other costs resulting from
labor charges, delays, vandalism, negligence, fouling caused by foreign material, damage from adverse
water conditions, chemical, or any other circumstances over which the Company has no control. This
warranty shall be invalidated by any abuse, misuse, misapplication, improper installation or improper
maintenance or alteration of the product.
Some States do not allow limitations on how long an implied warranty lasts, and some States do not
allow the exclusion or limitation of incidental or consequential damages. Therefore the above limita-
tions may not apply to you. This Limited Warranty gives you specific legal rights, and you may have
other rights that vary from State to State. You should consult applicable state laws to determine your
rights. SO FAR AS IS CONSISTENT WITH APPLICABLE STATE LAW, ANY IMPLIED WARRANTIES
THAT MAY NOT BE DISCLAIMED, INCLUDING THE IMPLIED WARRANTIES OF MERCHANTABILITY
AND FITNESS FOR A PARTICULAR PURPOSE, ARE LIMITED IN DURATION TO ONE YEAR FROM THE
DATE OF ORIGINAL SHIPMENT.
ENGLISH INSTRUCTIONS
Gaskets Not
Supplied
Purge Port
Shut Off Valve
Watts PIPF-M1
Watts IPF-M2
PIPF-M1 de Watts
Válvula de cierre
Puerto de purga
IPF-M2 de Watts
No se
proporcionan
las juntas
Los rebordes de bomba serie PIPF-M1 están diseñados para
simplificar la instalación, servicio y eliminación de las bombas
y los circuladores en sistemas hidrónicos. Los rebordes de
bomba PIPF-M1 cuentan con un puerto de purga que permite
purgar el sistema en la bomba o el circulador. Los rebordes
de bomba PIPF-M1 también cuentan con un reborde giratorio,
que le permite rotar el cuerpo de la válvula para poder colocar
el puerto de purga en la mejor posición para su aplicación.
Instalación
Para instalar simplemente fije con pernos el reborde PIPF-M1
al lado de retorno del reborde de la bomba/circulador.
Asegúrese de que haya una junta de la bomba entre cada
reborde. Póngase en contacto con su mayorista si necesita
una junta.
1. Fije con pernos el reborde PIPF-M1 al lado de retorno del
reborde de la bomba/circulador. No instale el reborde PIPF
sin un reborde de bomba.
2. Ajuste los pernos que unen el reborde PIPF-M1 al reborde
de la bomba, con cuidado de no ajustar demasiado.
Se recomienda un ajuste a mano más
1
2 vuelta.
3. Cuando el sistema esté lleno, inspeccione que no haya
pérdidas en el reborde. Ajuste los pernos según sea
necesario, con cuidado de no ajustar demasiado.
4. Sólo para modelos con soldadura, deslice la brida de
plástico del puerto de purga sobre la válvula esférica
acanalada para proteger la brida del calor que se aplica
mientras se suelda.
Para modelos con soldadura
Esta válvula está diseñada para soldadura blanda en líneas sin
desarmarse, usando una soldadora de baja temperatura
(215°C / 420°F). Pueden usarse otras soldaduras como 95/5estaño
antimonio (238°C / 460°F) o 96/4 estaño plata (221°C / 430°F),
sin embargo, debe tenerse extremo cuidado para evitar dañar el
sello. Las soldaduras a mayor temperatura dañarán el material del
asiento. ANSI B16.18 establece que la presión de funcionamiento
máxima de las conexiones soldadas 50-50 es de 1380 kPa a 38°C
(200psi a 100°F) y diminuye con las temperaturas más altas.
Aplique calor con la llama ALEJADA del centro del cuerpo de
la válvula. El calor excesivo puede dañar los asientos.
Purgado del sistema hidrónico
1. Aísle todos los circuitos cerrando la válvula de zona
o aislamiento y las válvulas de cierre de PIPF-M1.
Quite la tapa del puerto de purga.
2. Comenzando con un circuito, coloque una manguera en
el puerto de purga de PIPF-M1. (Nota: debe colocarse una
manguera en un drenaje del suelo adecuado o colocarse
por fuera para que lleve el agua purgada).
3. Abra el puerto de purga PIPF-M1 girando la manija
1
4
de vuelta y abra la válvula de zona o aislamiento.
4. Abra la función de llenado rápido de la válvula compensatoria
o de la caldera. Deje que el agua fluya por el puerto de purga
de PIPF-M1 hasta que el agua salga transparente y
sin burbujas de aire.
5. Cierre la válvula compensatoria o de llenado de la caldera.
6. A continuación, cierre el puerto de purga PIPF-M1 girando
la manija de purga
1
4 de vuelta hasta que el agua deje de fluir.
Cierre la válvula de zona o aislamiento. Vuelva a colocar
la tapa en el puerto de purga.
7. Repita los pasos 2 al 6 para cada zona.
8. Después de finalizar la purga de aire de todas las zonas,
abra la válvula de cierre de PIPF-M1.
Gaskets Not
Supplied
Purge Port
Shut Off Valve
Watts PIPF-M1
Watts IPF-M2
Bride PIPF-M1
de Watts
Robinet d’arrêt
Port de vidange
Bride IPF-M2
de Watts
Joints non
fournis
Les brides de pompe de série PIPF-M1 sont conçues pour
simplifier l’installation, l’entretien et la dépose des pompes
et des circulateurs des systèmes de chauffage à eau chaude.
Les brides de pompe PIPF-M1 comportent un port de vidange
qui permet de purger le système au niveau de la pompe ou
du circulateur. Les brides de pompe PIPF-M1 comportent
également une bride pivotante, qui permet de tourner le corps
de la vanne afin de placer le port de vidange dans la meilleure
position pour votre application.
Installation
Pour effectuer l’installation, il suffit de boulonner la bride
PIPF-M1 du côté retour de la bride de la pompe/du
circulateur. Toujours placer un joint entre chaque bride.
Contacter un marchand pour acheter des joints.
1. Pour effectuer l’installation, boulonner la bride PIPF-M1
du côté retour de la bride de la pompe/du circulateur.
Ne pas installer la bride PIPF sans joint.
2. Serrer les boulons qui fixent la bride PIPF-M1 à la bride
de la pompe en prenant soin de ne pas trop serrer. Serrer
à la main, puis serrer d’un demi-tour.
3. Lorsque le système est rempli, vérifier qu’il n’y a pas de
fuites au niveau de la bride. Serrer les boulons au besoin
en prenant soin de ne pas trop serrer.
4. Pour les modèles soudés uniquement, faire glisser l’attache
en plastique du capuchon du port de vidange par-dessus le
robinet à bille fendue pour le protéger de la chaleur produite
lors de la soudure.
Pour les modèles soudés
Cette vanne est conçue pour une soudure tendre dans les lignes
sans démontage, avec une brasure à faible température
(215ºC / 420°F). D’autres types de brasures peuvent être utilisées,
comme l’étain à l’antimoine 95-5 (238ºC / 460°F) ou l’étain à
l’argent 96-4 (221ºC / 430°F). Cependant, faire preuve d’une grande
prudence pour éviter d’endommager le joint. Les soudures effectuées
à des températures plus élevées risquent d’endommager le matériau
du joint. La norme ANSI B16.18 stipule que la pression d’utilisation
maximale des raccords soudés 50-50 est de 1380 kPa à 38ºC
(200 lb/po² à 100°F) et diminue lorsque les températures sont plus
élevées. Appliquer la chaleur avec une flamme dirigée À L’OPPOSÉ
du centre du corps de la vanne. Une température excessive
endommagera les sièges.
Pour purger le système de chauffage à eau
chaude
1. Isoler tous les circuits en fermant la vanne d’isolement ou
vanne de régulation par zone et les soupapes d’arrêt de
la bride PIPF-M1. Enlever le bouchon du port de vidange.
2. En commençant avec un circuit, fixer un tuyau au port de
vidange de la bride PIPF-M1. (Remarque : Le tuyau doit être
acheminé jusqu’à un drain de sol approprié ou à l’extérieur
pour évacuer l’eau vidangée).
3. Ouvrir le port de vidange de la bride PIPF-M1 en tournant
la poignée d’un quart de tour et ouvrir la vanne d’isolement
ou vanne de régulation par zone.
4. Ouvrir le dispositif de remplissage rapide de la soupape de
remplissage ou de la soupape d’alimentation en eau de la
chaudière. Laisser l’eau s’écouler par le port de vidange de
la bride PIPF-M1 jusqu’à ce qu’elle soit propre et sans bulles.
5. Fermer la soupape de remplissage ou d’alimentation en eau
de la chaudière.
6. Fermer ensuite le port de vidange de la bride PIPF-M1 en
tournant la poignée de purge d’un quart de tour jusqu’à ce
que l’eau cesse de s’écouler. Fermer la vanne d’isolement
ou vanne de régulation par zone. Remettre en place le
bouchon du port de vidange.
7. Refaire les étapes 2 à 6 pour chaque zone.
8. Lorsque l’air aura été purgé de toutes les zones, ouvrir
la soupape d’arrêt de la bride PIPF-M1.
INSTRUCTIONS EN FRANçAIS INSTRUCCIONES EN ESPAÑOL

Transcripción de documentos

Watts IPF-M2 Watts IPF-M2 For Solder Models Purging the Hydronic System This valve is designed to be soft soldered into lines without dis­as­sem­ bly, using a low temperature solder (420°F / 215ºC). Other sol­ders such as 95/5 tin antimony (460°F / 238ºC) or 96/4 tin silver (430°F / 221ºC) can be used, however, extreme caution must be used to prevent seal dam­age. Higher temperature solders will dam­age the seat ma­te­ri­al. ANSI B16.18 states that the max­i­mum operating pres­sure of 50-50 solder connections is 200psi at 100°F (1380kPa at 38ºC) and de­creas­es with higher temperatures. 1. Isolate all circuits by shutting the isolation or zone valve and the PIPF-M1 shutoff valves. Remove cap from purge port. Apply heat with the flame directed AWAY from the center of the valve body. Excessive heat can harm the seats. 4. O  pen the make up water or boiler fill valve’s fast fill feature. Allow water to flow through the PIPF-M1’s purge port until the water runs clear and free of air bubbles. 3. Open the PIPF-M1’s purge port by turning the handle 1⁄4 turn, and open the isolation or zone valve. 2. S  tarting with one circuit, attach a hose to the purge port of the PIPF-M1. (Note: A hose must be run into a suitable floor drain or run to the outside to accommodate purged water). S­­eries PIPF-M1 ENGLISH INSTRUCTIONS 5. Close the make up water or boiler fill valve. Shut Off Valve Garantía limitada: Watts Regulator Co. (en adelante, “la Compañía”) garantiza, por un período de un año a partir de la fecha de embarque original, que sus productos están libres de defectos en materiales y mano de obra bajo condiciones de uso normal. En caso de que se encuentren tales defectos dentro del período de garantía, la Compañía reemplazará o reacondicionará, a su elección, el producto sin costo alguno. LA GARANTÍA AQUÍ ESTIPULADA SE OTORGA EN FORMA EXPRESA Y ES LA ÚNICA GARANTÍA OTORGADA POR LA COMPAÑÍA EN RELACIÓN CON EL PRODUCTO. LA COMPAÑÍA NO OTORGA NINGUNA OTRA GARANTÍA, YA SEA EXPRESA O IMPLÍCITA. LA COMPAÑÍA POR LA PRESENTE RENUNCIA ESPECÍFICAMENTE A TODAS LAS DEMÁS GARANTÍAS, EXPRESAS O IMPLÍCITAS, INCLUYENDO SIN LIMITACIÓN, LAS GARANTÍAS IMPLÍCITAS DE APTITUD PARA LA COMERCIALIZACIÓN E IDONEIDAD PARA UN PROPÓSITO EN PARTICULAR. La solución descrita en el primer párrafo de esta garantía constituirá la única y exclusiva solución por incumplimiento de garantía, y la Compañía no se hará responsable por daños accidentales, especiales o indirectos, incluyendo sin limitación, la pérdida de ganancias o el costo de reparación o reemplazo de otra propiedad que resulte dañada por el mal funcionamiento de este producto, otros costos resultantes por mano de obra, retardos, vandalismo, negligencia, obstrucciones ocasionadas por materiales extraños, daños debidos a condiciones adversas del agua, químicos o cualquier otra circunstancia sobre la cual la Compañía no tenga control. Esta garantía no tendrá validez en cualquier caso de abuso, uso indebido, aplicación incorrecta, instalación inadecuada, o mantenimiento adecuado o alteración del producto. Algunos Estados no permiten limitaciones en la duración de una garantía implícita y algunos Estados no permiten la exclusión o limitación de daños accidentales o indirectos. Por lo tanto, es posible que las limitaciones anteriores no sean aplicables en su caso. Esta garantía limitada le da derechos legales específicos; usted podría tener también otros derechos que varían según el Estado. Usted debe consultar las leyes estatales aplicables para determinar sus derechos. EN LA MEDIDA EN QUE SEA CONGRUENTE CON LAS LEYES ESTATALES APLICABLES, CUALQUIER GARANTÍA IMPLÍCITA QUE NO SEA RECHAZADA, INCLUYENDO LAS GARANTÍAS IMPLÍCITAS DE APTITUD PARA LA COMERCIALIZACIÓN E IDONEIDAD PARA UN PROPÓSITO EN PARTICULAR, SE LIMITA EN SU DURACIÓN A UN AÑO A PARTIR DE LA FECHA DEL EMBARQUE ORIGINAL. PIPF-M1 7. Repeat steps 2 – 6 for each zone. 6. N  ext close the PIPF-M1 purge port by turning the purge handle 1⁄4 turn until the water stops flowing. Shut off the isolation or zone valve. Replace cap on purge port. Gaskets Not Gaskets Not Supplied Supplied Shut Off Valve Purge Port Purge Port Garantie limitée: Watts Regulator Co. (la « Société ») garantit que chacun de ses produits est exempt de vice de matériau et de fabrication dans des conditions normales d’utilisation pour une période d’un an à compter de la date d’expédition d’origine. Dans l’éventualité où de tels vices se manifesteraient pendant la période de garantie, la Société, à sa discrétion, remplacera ou reconditionnera le produit sans frais. LA PRÉSENTE GARANTIE EST EXPRESSE ET REPRÉSENTE LA SEULE GARANTIE OFFERTE PAR LA SOCIÉTÉ POUR CE PRODUIT. LA SOCIÉTÉ N’OFFRE AUCUNE AUTRE GARANTIE, EXPRESSE OU TACITE. PAR LA PRÉSENTE, LA SOCIÉTÉ REJETTE SPÉCIFIQUEMENT TOUTE AUTRE GARANTIE, EXPRESSE OU TACITE, NOTAMMENT TOUTE GARANTIE TACITE DE QUALITÉ MARCHANDE OU D’ADAPTATION À UN BUT PARTICULIER. Le recours décrit dans le premier paragraphe de cette garantie constitue le seul recours à toute violation de la présente garantie. La Société ne saurait être tenue responsable de tout dommage accessoire, spécial ou indirect, y compris, de façon non limitative : la perte de profits ou le coût afférent à la réparation ou au remplacement d’autres biens qui seraient endommagés par suite du fonctionnement incorrect dudit produit ; d’autres coûts résultant de frais de main-d’œuvre, de retards, de vandalisme, de négligence, d’une obstruction causée par des matériaux étrangers, de dommages causés par une eau impropre, des produits chimiques ou par tout autre événement échappant au contrôle de la Société. La présente garantie est déclarée nulle et non avenue en cas d’usage abusif ou incorrect, d’application, d’installation ou d’entretien incorrects ou de modification du produit. Certains États n’autorisent pas les limitations de durée d’une garantie tacite ou l’exclusion ou la limitation des dommages accessoires ou indirects. Les limitations susmentionnées peuvent donc ne pas s’appliquer à vous. Cette garantie limitée vous donne des droits spécifiques et il se peut que vous ayez aussi d’autres droits qui varient d’un État à l’autre. Veuillez vous référer aux lois applicables de l’État pour déterminer vos droits en la matière. DANS LA MESURE PERMISE PAR LA LOI APPLICABLE DE L’ÉTAT, TOUTES LES GARANTIES TACITES NE POUVANT PAS ÊTRE REJETÉES, Y COMPRIS LES GARANTIES TACITES DE QUALITÉ MARCHANDE ET D’ADAPTATION À UN BUT PARTICULIER, SONT LIMITÉES QUANT À LEUR DURÉE À UN AN À COMPTER DE LA DATE D’EXPÉDITION D’ORIGINE. 4. F  or solder models only, slip the plastic tether on the purge port over the slotted ball valve to protect tether from heat applied during soldering. 3. W  hen the system is filled, inspect for leaks at the flange. Tighten the bolts as needed, taking care not to over-tighten. 8. U  pon completion of purging all zones of air, open the PIPF-M1 shutoff valve. 2. T  ighten the bolts joining the PIPF-M1 flange to the pump flange, taking care not to over-tighten. Hand-tighten plus 1⁄2 turn is recommended. 1. B  olt the PIPF-M1 flange to the return side of the pump/ circulator flange. Do not install the PIPF flange without a pump gasket. To install simply bolt the PIPF-M1 flange to the return side of the pump/circulator flange. Be sure that there is a pump gasket between each flange. Contact your wholesaler if you require a gasket. Installation Watts PIPF-M1 Watts PIPF-M1 Series PIPF-M1 Pump Flanges are designed to simplify the installation, service and removal of pumps and circulators in hydronic systems. PIPF-M1 pump flanges feature a purge port which allows system purging at the pump or circulator. PIPF-M1 pump flanges also feature a swivel flange, which allows you to rotate the valve body so you can put the purge port in the best position for your application. IS-PIPF-M1 Isolation Pump Flange with Purge Port and Swivel Flange USA: 815 Chestnut St., No. Andover, MA 01845-6098; www.watts.com Canada: 5435 North Service Rd., Burlington, ON. L7L 5H7; www.wattscanada.ca IS-PIPF-M1 1103 EDP# 2915860 © Watts, 2011 USA: 815 Chestnut St., No. Andover, MA 01845-6098; www.watts.com Canada: 5435 North Service Rd., Burlington, ON. L7L 5H7; www.wattscanada.ca IS-PIPF-M1 1103 EDP# 2915860 © Watts, 2011 Limited Warranty: Watts Regulator Co. (the “Company”) warrants each product to be free from defects in material and workmanship under normal usage for a period of one year from the date of original shipment. In the event of such defects within the warranty period, the Company will, at its option, replace or recondition the product without charge. THE WARRANTY SET FORTH HEREIN IS GIVEN EXPRESSLY AND IS THE ONLY WARRANTY GIVEN BY THE COMPANY WITH RESPECT TO THE PRODUCT. THE COMPANY MAKES NO OTHER WARRANTIES, EXPRESS OR IMPLIED. THE COMPANY HEREBY SPECIFICALLY DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. The remedy described in the first paragraph of this warranty shall constitute the sole and exclusive remedy for breach of warranty, and the Company shall not be responsible for any incidental, special or consequential damages, including without limitation, lost profits or the cost of repairing or replacing other property which is damaged if this product does not work properly, other costs resulting from labor charges, delays, vandalism, negligence, fouling caused by foreign material, damage from adverse water conditions, chemical, or any other circumstances over which the Company has no control. This warranty shall be invalidated by any abuse, misuse, misapplication, improper installation or improper maintenance or alteration of the product. Some States do not allow limitations on how long an implied warranty lasts, and some States do not allow the exclusion or limitation of incidental or consequential damages. Therefore the above limitations may not apply to you. This Limited Warranty gives you specific legal rights, and you may have other rights that vary from State to State. You should consult applicable state laws to determine your rights. SO FAR AS IS CONSISTENT WITH APPLICABLE STATE LAW, ANY IMPLIED WARRANTIES THAT MAY NOT BE DISCLAIMED, INCLUDING THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE LIMITED IN DURATION TO ONE YEAR FROM THE DATE OF ORIGINAL SHIPMENT. USA: 815 Chestnut St., No. Andover, MA 01845-6098; www.watts.com Canada: 5435 North Service Rd., Burlington, ON. L7L 5H7; www.wattscanada.ca IS-PIPF-M1 1103 EDP# 2915860 Bride d’isolation de pompe avec port de vidange et bride pivotante Reborde de la bomba de aislamiento con puerto de purga y reborde giratorio ⁄ " - 1 1⁄4" (20-32mm) 34 Installation Instructions Instructions d’installation Instrucciones de instalación PIPF-M1 © Watts, 2011 INSTRUCCIONES EN ESPAÑOL Les brides de pompe de série PIPF-M1 sont conçues pour simplifier l’installation, l’entretien et la dépose des pompes et des circulateurs des systèmes de chauffage à eau chaude. Les brides de pompe PIPF-M1 comportent un port de vidange qui permet de purger le système au niveau de la pompe ou du circulateur. Les brides de pompe PIPF-M1 comportent également une bride pivotante, qui permet de tourner le corps de la vanne afin de placer le port de vidange dans la meilleure position pour votre application. Pour les modèles soudés Bride PIPF-M1 Watts PIPF-M1 de Watts Port de vidange Purge Port Pour effectuer l’installation, il suffit de boulonner la bride PIPF-M1 du côté retour de la bride de la pompe/du circulateur. Toujours placer un joint entre chaque bride. Contacter un marchand pour acheter des joints. 1. P  our effectuer l’installation, boulonner la bride PIPF-M1 du côté retour de la bride de la pompe/du circulateur. Ne pas installer la bride PIPF sans joint. Robinet d’arrêt Shut Off Valve Installation Joints non Gaskets Not fournis Supplied Cette vanne est conçue pour une soudure tendre dans les lignes sans démontage, avec une brasure à faible température (215ºC / 420°F). D’autres types de brasures peuvent être utilisées, comme l’étain à l’antimoine 95-5 (238ºC / 460°F) ou l’étain à l’argent 96-4 (221ºC / 430°F). Cependant, faire preuve d’une grande prudence pour éviter d’endommager le joint. Les soudures effectuées à des températures plus élevées risquent d’endommager le matériau du joint. La norme ANSI B16.18 stipule que la pression d’utilisation maximale des raccords soudés 50-50 est de 1380 kPa à 38ºC (200 lb/po² à 100°F) et diminue lorsque les températures sont plus élevées. Appliquer la chaleur avec une flamme dirigée À L’OPPOSÉ du centre du corps de la vanne. Une température excessive endommagera les sièges. 3. L  orsque le système est rempli, vérifier qu’il n’y a pas de fuites au niveau de la bride. Serrer les boulons au besoin en prenant soin de ne pas trop serrer. Watts IPF-M2 INSTRUCTIONS EN FRANçAIS PIPF-M1 de Watts Watts PIPF-M1 Puerto de purga Purge Port Válvula de cierre Shut Off Valve 4. S  ólo para modelos con soldadura, deslice la brida de plástico del puerto de purga sobre la válvula esférica acanalada para proteger la brida del calor que se aplica mientras se suelda. 4. O  uvrir le dispositif de remplissage rapide de la soupape de remplissage ou de la soupape d’alimentation en eau de la chaudière. Laisser l’eau s’écouler par le port de vidange de la bride PIPF-M1 jusqu’à ce qu’elle soit propre et sans bulles. 7. Refaire les étapes 2 à 6 pour chaque zone. Para modelos con soldadura Purgado del sistema hidrónico Esta válvula está diseñada para soldadura blanda en líneas sin desarmarse, usando una soldadora de baja temperatura (215°C / 420°F). Pueden usarse otras soldaduras como 95/5 estaño antimonio (238°C / 460°F) o 96/4 estaño plata (221°C / 430°F), sin embargo, debe tenerse extremo cuidado para evitar dañar el sello. Las soldaduras a mayor temperatura dañarán el material del asiento. ANSI B16.18 establece que la presión de funcionamiento máxima de las conexiones soldadas 50-50 es de 1380 kPa a 38°C (200psi a 100°F) y diminuye con las temperaturas más altas. 1. A  ísle todos los circuitos cerrando la válvula de zona o aislamiento y las válvulas de cierre de PIPF-M1. Quite la tapa del puerto de purga. Aplique calor con la llama ALEJADA del centro del cuerpo de la válvula. El calor excesivo puede dañar los asientos. No se Gaskets Not proporcionan Supplied las juntas 2. C  omenzando con un circuito, coloque una manguera en el puerto de purga de PIPF-M1. (Nota: debe colocarse una manguera en un drenaje del suelo adecuado o colocarse por fuera para que lleve el agua purgada). 3. A  bra el puerto de purga PIPF-M1 girando la manija 1⁄4 de vuelta y abra la válvula de zona o aislamiento. 4. A  bra la función de llenado rápido de la válvula compensatoria o de la caldera. Deje que el agua fluya por el puerto de purga de PIPF-M1 hasta que el agua salga transparente y sin burbujas de aire. 5. Cierre la válvula compensatoria o de llenado de la caldera. 6. A  continuación, cierre el puerto de purga PIPF-M1 girando la manija de purga 1⁄4 de vuelta hasta que el agua deje de fluir. Cierre la válvula de zona o aislamiento. Vuelva a colocar la tapa en el puerto de purga. 2. A  juste los pernos que unen el reborde PIPF-M1 al reborde de la bomba, con cuidado de no ajustar demasiado. Se recomienda un ajuste a mano más 1⁄2 vuelta. 3. C  uando el sistema esté lleno, inspeccione que no haya pérdidas en el reborde. Ajuste los pernos según sea necesario, con cuidado de no ajustar demasiado. 3. O  uvrir le port de vidange de la bride PIPF-M1 en tournant la poignée d’un quart de tour et ouvrir la vanne d’isolement ou vanne de régulation par zone. 8. L  orsque l’air aura été purgé de toutes les zones, ouvrir la soupape d’arrêt de la bride PIPF-M1. Los rebordes de bomba serie PIPF-M1 están diseñados para simplificar la instalación, servicio y eliminación de las bombas y los circuladores en sistemas hidrónicos. Los rebordes de bomba PIPF-M1 cuentan con un puerto de purga que permite purgar el sistema en la bomba o el circulador. Los rebordes de bomba PIPF-M1 también cuentan con un reborde giratorio, que le permite rotar el cuerpo de la válvula para poder colocar el puerto de purga en la mejor posición para su aplicación. 1. F  ije con pernos el reborde PIPF-M1 al lado de retorno del reborde de la bomba/circulador. No instale el reborde PIPF sin un reborde de bomba. 2. E  n commençant avec un circuit, fixer un tuyau au port de vidange de la bride PIPF-M1. (Remarque : Le tuyau doit être acheminé jusqu’à un drain de sol approprié ou à l’extérieur pour évacuer l’eau vidangée). 6. F  ermer ensuite le port de vidange de la bride PIPF-M1 en tournant la poignée de purge d’un quart de tour jusqu’à ce que l’eau cesse de s’écouler. Fermer la vanne d’isolement ou vanne de régulation par zone. Remettre en place le bouchon du port de vidange. Bride IPF-M2 de Watts 4. P  our les modèles soudés uniquement, faire glisser l’attache en plastique du capuchon du port de vidange par-dessus le robinet à bille fendue pour le protéger de la chaleur produite lors de la soudure. Para instalar simplemente fije con pernos el reborde PIPF-M1 al lado de retorno del reborde de la bomba/circulador. Asegúrese de que haya una junta de la bomba entre cada reborde. Póngase en contacto con su mayorista si necesita una junta. 1. Isoler tous les circuits en fermant la vanne d’isolement ou vanne de régulation par zone et les soupapes d’arrêt de la bride PIPF-M1. Enlever le bouchon du port de vidange. 5. F  ermer la soupape de remplissage ou d’alimentation en eau de la chaudière. 2. S  errer les boulons qui fixent la bride PIPF-M1 à la bride de la pompe en prenant soin de ne pas trop serrer. Serrer à la main, puis serrer d’un demi-tour. Instalación Pour purger le système de chauffage à eau chaude 7. Repita los pasos 2 al 6 para cada zona. Watts IPF-M2 IPF-M2 de Watts 8. D  espués de finalizar la purga de aire de todas las zonas, abra la válvula de cierre de PIPF-M1.
  • Page 1 1
  • Page 2 2

Watts PIPFM1-PRESS 1 1/4 Guía de instalación

Tipo
Guía de instalación