Haier 1U12BS1ERA El manual del propietario

Categoría
Acondicionadores de aire de sistema dividido
Tipo
El manual del propietario
Please read this manual carefully before installtion.
Keep this operation manual for future reference.
1U12BS1ERA
1U09BS1ERA
1U07BS1ERA
1U18FS1ERA
1U24GS1ERA
INSTALLATION MANUAL
ROOM AIR CONDITIONER
NO.0010535386
14
1
2
9
Indoor/Outdoor Unit Installion Drawings
Safety Precautions
Installation Procedure
Outdoor Unit Troubleshooting
Read Before Installation
6
Contents
Contenido
Unidad interior y exterior Dibujos de extracción
15
Precauciones de seguridad 16
Leer antes de realizar la instalación 20
Procedimiento instalación 23
Unidad interior Resolución de problemas
28
Indice
Unità esterna/interna Immagini per l'installazione
29
Precauzioni di sicurezza
30
Leggere prima dell'installazione
34
Processo di installazione
37
Unità esterna Risoluzione dei problemi
42
Table des matières
Unité intérieure/extérieure Schémas d'installation
43
Consignes de sécurité
À lire avant l'installation
Procédure d'installation
Unité extérieure Dépannage
56
44
48
51
Haier Industrial Park, No.1 Haier Road, Qingdao, P.R.China
CE
All the products are in conformity with the following
European provision:
- Low Voltage Directive 73/23/EEC
- Low Voltage Directive 2006/95/EC
-Electomagnetic CompatibilitY 89/336/EEC
-Electomagnetic CompatibilitY 2004/108/EC
ROHS
The products are fulfilled with the requirements in the
directive 2002/95/EEC of the European parliament and of
council on the Restriction of the use of Certain Hazardous
Substances in Electrical and Electronic Equipment (EU
RoHS Directive)
WEEE
DISPOSAL REQUIREMENTS:
Your air conditioning product is marked with this
symbol.This means that electrical and electronic
products shall not be mixed with unsorted
household waste. Do not try to dismantle the
system yourself : the dismantling of the air
EUROPEAN REGULATIONS
CONFORMITY FOR THE MODELS
1
1+2=
kg
R410A
2
kg
2=
1=
B
C
D
FE
kg
A
This product contains fluorinated greenhouse gases covered
by the Kyoto Protocol. Do not vent into the atmosphere.
Refrigerant type:R410A
GWP* value:1975
GWP=global warming potential
Please fill in with indelible ink,
• 1 the factory refrigerant charge of the product
• 2 the additional refrigerant amount charged in the field
and
• 1+2 the total refrigerant charge
on the refrigerant charge label supplied with the product.
The filled out label must be adhered in the proximity of the
product
charging port (e.g. onto the inside of the stop value
A contains fluorinated greenhouse gases covered by the
Kyoto
Protocol
B factory refrigerant charge of the product: see unit name
plate
C additional refrigerant amount charged in the field
D total refrigerant charge
E outdoor unit
F refrigerant cylinder and manifold for charging
IMPORTANT INFORMATION REGA-
RDING THE REFRIGERANT USED
In accordance with the directive 2002/96/CE of the European
parliament, herewith we inform the consumer about the dis-
posal requirements of the electrical and electronic products.
conditioning system,treatment of the refrigerant, of oil and of
other part must be done by a qualified installer in
accordance
with relevant local and national legislation. Air conditioners
must be treated at a specialized treatment facility for reuse,
recycling and recovery. By ensuring this product is disposed
of correctly, you will help to prevent potential negative cons-
equences for the environment and humen health. Please
contact the installer or local authority for more information.
Battery must be removed from the remote controller and dis-
posed of separately in accordance with relevant local and
nationl legislation.
Contains fluorinated greenhouse gases
covered by the Kyoto Protocol
cover).
Please be subject to the actual product purchased.
The above indoor and outdoor units’ picture is just for your reference.
F
A
C
E
D
Optional parts for piping
Non-adhesive tape
Adhesive tape
Saddle(L.S)withscrews
Connecting electric cable
for indoor and outdoor
Drain hose
Heating insulating material
Piping hole cover
Fixing of outdoor unit
Fix the unit to concrete or blockƽ
with bolts (10mm) and nuts firmly
and horizontally.
When fitting the unit to wall
ƽ
surface,rooforrooftop,fix
asupportersurelywithnails
or wires in consideration of
earthquake and strong wind.
If vibration may affect the
ƽ
house, fix the unit by attaching a
vibration-proof mat.
The marks from to
in the figure are the
parts numbers.
Thedistancebetween
theindoorunitandthe
floor should be more
than 2m.
ThemodelsadoptHFCfreerefrigerantR410A.
more than
10cm
more than 15cm
more than 10cm
more than 20cm
more than
20cm
more than 25cm
more than
60cm
A
G
ƽ
ƽ
A
F
C
E
D
G
B
Arrangement of piping
directions
Rear left
Left
Rear
right
Right
Below
G
Attention must be paid to
the rising up of drain hose
Indoor/Outdoor Unit Installation Drawings
For installation of the indoor units,refer to the installation manual which was provided with the units.
(The diagram shows a wall-mounted indoor unit.)
AIR OUTLET
AIR INLET
CONNECTING PIPING AND ELECTRICAL WIRING
DRAIN HOSE
4
ƽ
Compressor(Inside of Unit)
1
WARNING
CAUTION
2
Have the unit professionally installed.
Improper installation by an unqualified person may result
in water leak, electric shock, or fire.
Be sure to carefully follow each step in this handbook when
installing the unit.
Improper installation may result in water leak, electric shock,
smoke or fire.
Have all electrical work performed by a licensed electrician
according to the local regulations and the instructions given
in this manual. Secure a circuit designated exclusively to
the unit.
Improper installation or a lack of circuit capacity may cause
the unit to malfunction or present a risk of electric shock,
smoke,and fire.
Place the unit on a stable, level surface that withstands the
weight of the unit to prevent the unit from tipping over or
falling causing injury as a result.
Only use specified cables for wiring. Securely connect each
cable, and make sure that the cables are not straining the
terminals.
Cables not connected securely and properly may generate
heat and cause fire.
Take necessary safety measures against typhoons and
earthquakes to prevent the unit from falling over.
Do not make any changes or modifications to the unit. In
case of problems, consult the dealer.
If repairs are not made properly, the unit may leak water
and present a risk of electric shock, or it may produce smoke
or cause fire.
Securely attach the terminal cover(panel) on the unit.
If installed improperly, dust and/or water may enter the unit
and present a risk of electric shock, smoke or fire.
Only use refrigerant R410A as indicated on the unit when
installing or relocating the unit.
The use of any other refrigerant or an introduction of air into
the unit circuit may cause the unit to run an abnormal cycle
and abnormal cycle and cause the unit to burst.
In the event of a refrigerant gas leak, provide adequate
ventilation to the room.
If leaked refrigerant gas is exposed to a heat source, noxious
gases may form.
Do not touch the fins on the heat exchanger with bare hands,
for they are sharp and dangerous.
Do not try to defeat the safety features of the devices, and
do not change the settings.
Defeating the safety features on the unit such as the pressure
switch and temperature switch or using parts other than the
dealer or specialist may result in fire or explosion.
When installing the unit in a small room, safeguard against
hypoxia that results from leaked refrigerant reaching the
threshold level.
Consult the dealer for necessary measures to take.
When relocating the air conditioner, consult the dealer or
a specialist.
Improper installation may result in water leak, electric shock,
or fire.
After completing the service work, check for a refrigerant
gas leak.
If leaked gas refrigerant is exposed to a heat source such
as fan heater,stove,and electric grill, noxious gases may
form.
Only use specified parts.
Have the unit professionally installed. Improper installation
may cause water leak, electric shock,smoke, or fire.
With All-Fresh type air conditioners, outdoor air may be
directly blown into the room upon thermo off. Take this into
consideration when installing the unit.
Direct exposure to outdoor air may present a health hazard,
and it may also cause food items to deteriorate.
WARNING
WARNING
Safety Precautions
3
Precautions for Handling Units for Use with R410A
Do not use the existing refrigerant piping
The old refrigerant and refrigerator oil in the existing piping
contain a large amount of chlorine, which will cause the
refrigerator oil in the new unit to deteriorate.
R410A is a high-pressure refrigerant, and the use of the
existing piping may result in bursting.
Keep the inner and outer surfaces of the pipes clean and
free of contaminants such as sulfur, oxides, dust/dirt shaving
particles,oils,and moisture.
Contaminants inside the refrigerant piping will cause the
refrigerant oil to deteriorate.
Use a vacuum pump with a reverse-flow check valve.
If other types of valves are used, the vacuum pump oil will
flow back into the refrigerant cycle and cause the refrigerator
oil to deteriorate.
Do not use the following tools that have been used with the
conventional refrigerants. Prepare tools that are for exclusive
use with R410A.
(Gauge manifold, charging hose, gas leak detector,
reverse-flow check valve, refrigerant charge base,vacuum
gauge, and refrigerant recovery equipment.)
If refrigerant and/or refrigerant oil left on these tools are
mixed in with R410, or if water is mixed with R410A, it will
cause the refrigerant to deteriorate.
Since R410A does not contain chlorine, gas-leak detectors
for conventional refrigerators will not work.
Store the piping to be used during installation indoors, and
keep both ends of the piping sealed until immediately before
brazing.(keep elbows and other joints wrapped in plastic.)
If dust, dirt, or water enters the refrigerant cycle, it may
cause the oil in the unit to deteriorate or may cause the
compressor to malfunction.
A large amount of mineral oil will cause the refrigerating
machine oil to deteriorate.
Use a small amount of ester oil, ether oil, or alkylbenzene
to coat flares and flange connections.
Use liquid refrigerant to charge the system.
Charge the unit with gas refrigerant will cause the refrigerant
in the cylinder to change its composition and will lead to
a drop in performance
Do not use a charging cylinder.
The use of charging cylinder will change the composition
of the refrigerant and lead to power loss.
Exercise special care when handling the tools.
An introduction of foreign objects such as dust, dirt or
water into the refrigerant cycle will cause the refrigerating
machine oil to deteriorate.
Only use R410A refrigerant.
The use of refrigerants containing chlorine(i.e. R22) will
cause the refrigerant to deteriorate.
Before Installing the Unit
Do not install the unit in a place where there is a possibility
of flammable gas leak.
Leaked gas accumulated around the unit may start a fire.
Do not use the unit to preserve food, animals, plants, artifacts,
or for other special purposes.
The unit is not designed to provide adepuate conditions
to preserve the quality of these items.
Do not use the unit in an unusual environment
The use of the unit in the presence of a large amount of
oil, steam, acid, alkaline solvents or special types of sprays
may lead to a remarkable drop in performance and/or
malfunction and presents a risk of electric shock, smoke,
or fire.
The presence of organic solvents, corroded gas (such as
ammonia,sulfur compounds,and acid may cause gas or
water leak.)
When installing the unit in a hospital, take necessary measures
against noise.
High-frequency medical equipment may interfere with the
normal operation of the air conditioning unit or the air
conditioning unit may interfere with the normal operation
of the medical equipment
When humidity level exceeds 80% or when the drainage
system is clogged, indoor units may drip water.
Installation of a centralized drainage system for the outdoor
unit may also need to be considered to prevent water drips
from the outdoor units.
Do not place the unit on or over things that may not get wet.
Caution
Caution
Caution
Safety Precautions
4
Before Installing (Relocating) the Unit or Performing Electric Work
Ground the unit.
Do not connect the grounding on the unit to gas pipes,water
pipes, lightning rods, or the grounding terminals of
telephones. Improper grounding presents a risk of electric
shock, smoke, fire, or the noise caused by improper
grounding may cause the unit to malfunction.
Before the Test Run
Do not operate switches with wet hands to avoid electric.
Allow for at least five minutes before turning off the unit,
otherwise the unit may leak water or experience other
problems.
Do not turn off the power immediately after stopping the unit.
If the wires are too taut, they may break or generate heat
and/or smoke and cause fire.
Make sure the wires are not subject to tension.
Install a breaker for current leakage at the power source
to avoid the risk of electric shock.
Without a breaker for current leakage, there is a risk of
electric shock, smoke or fire.
Use breakers and fuses (electrical current breaker, remote
switch<switch+Type-B fuse>,molded case circuit breaker)
with a proper current capacity.
The use of large-capacity fuses, steel wire, or copper wire
may damage the unit or cause smoke or fire.
When installing draining pipes, follow the instructions in the
manual, and make sure that they properly drain water so as
to avoid dew condensation.
If not installed properly, they may cause water leaks and
damage the furnishings.
Do not spray water on the air conditioners or immerse the
air conditioners in water.
Water on the unit presents a risk of electric shock.
Periodically check the platform on which is placed for damage
to prevent the unit from falling.
If the unit is left on a damaged plarform, it may topple over,
causing injury.
Things such as nails may be included in the package.
Dispose of them properly to prevent injury.
Plastic bags present a choking hazard to children. Tear
up the plastic bags before disposing of them to prevent
accidents.
Properly dispose of the packing materials.
Do not touch the refrigerant pipes with bare hands during
and immediately after operation.
Depending on the state of the refrigerant in the system,
certain parts of the unit such as the pipes and compressor
may become very cold or hot and may subject the person
to frost bites or burning.
Do not operated the unit without panels and safety guards
in their proper places.
They are there to keep the users from injury from
accidentally touching rotating, high-tempreture or high-
voltage parts.
Dust particles in the air may clog the system and cause
malfunction.
Do not operate the unit without air filters.
Caution
Caution
Safety Precautions
5
Read Before Installation
Tools/Materials Use Notes
Gauge Manifold Evacuating,refrigerant charging 5.09MPa on the High-pressure side.
Charging Hose Evacuating, refrigerant charging Hose diameter larger than the concentional ones.
Refrigerant Recovery Equipment Refrigerant recovery
Refrigerant Cylinder Refrigerant charging Write down the refrigerant type. Pink in color at the top of the cylinder.
Refrigerant Cylinder Charging Port Refrigerant charging Hose diameter larger than the conventional ones.
Flare Nut Connecting the unit to piping Use Type-2 Flare nuts.
Tools/Materials Use Notes
Gas leak detector Detection of gas leaks The ones for HFC type refrigerant may be used.
Vacuum Pump Vacuum drying May be used if a reverse flow check adaptor is attached.
Refrigerant Recovery Equipment Recovery of refrigerant May be used if designed for use with R410A.
Flare Tool Flare machining of piping Chages have been made in the flare machining dimension.Refer to the next page.
Tools/Materials Use Notes
Vacuum Pump with a Check Valve Vacuum drying
Bender Bending pipes
Pipe Cutter Cutting pipes
Torque Wrench Tightening flare nuts Only 12.70 (1/2'') and 15.88(5/8'') have a larger flare machining dimension.
Welder and Nitrogen Cylinder Welding pipes
Refrigerant Charging Meter Refrigerant charging
Vacuum Gauze Checking vacuum degree
Tools/Materials Use Notes
Charging Cylinder Refrigerant Charging Must not be used with R410-type units.
CAUTION
Items to Be Checked
(1). Verify the type of refrigerant used by the unit to be serviced. Refrigerant Type: R410A
(2). Check the symptom exhibited by the unit to be serviced. Look in this service handbook for symptoms relating to the
refrigerant cycle.
(3). Be sure to carefully read the safety precautions at the beginning of this document.
(4). If there is a gas leak or if the remaining refrigerant is exposed to an open flame, a noxious gas hydrofluoric acid may
form. Keep workplace well ventilated.
Install new pipes immediately after removing old ones to keep moisture out of the refrigerant circuit.
Chloride in some types of refrigerants such as R22 will cause the refrigerating machine oil to deteriorate.
Necessary Tools and Materials
Prepare the following tools and materials necessary for installing and servicing the unit.
Necessary tools for use with R410A(Adaptability of tools that are for use with R22 and R407C).
1. To be used exclusively with R410A ( Not to be used if used with R22 or R407C )
2. Tools and materials that may be used with R410 with some restrictions
3. Tools and materials that are used with R22 or R407C that can also be used with R410A
4. Tool and materials that must not used with R410A
Tools for R410A must be handled with special care, and keep moisture and dust from entering the cycle.
6
Read Before Installation
Maximum Operation Pressure Applicable Refrigerants
3.4MPa R22, R407C
4.15MPa R410A
Use pipes that meet the local standards.
Use pipes made of phosphorus deoxidized copper.
Since the operation pressure of the units that use R410A is higher than that of the units for use with R22, use pipes with
at least the radial thickness specified in the chart below. (Pipes with a radial thickness of 0.7mm or less may not be used.)
Although it was possible to use type-O for pipes with a size of up to
19.05(3/4") with conventional refrigerants, use type-
1/2H pipes for units that use R410A.(Type-O pipes may be used if the pipe size is
19.05 and the radial thickness is 1.2t.)
The table shows the standards in Japan. Using this table as a reference, choose pipes that meet the local standards.
The flare machining dimensions for units that use R410A is larger than those for units that use R22 in order to increase
air tightness.
If a clutch type flare tool is used to machine flares on units that use R410A, make the protruding part of the pipe between
1.0 and 1.5mm. Copper pipe gauge for adjusting the length of pipe protrusion is useful.
Size(mm) Radial Thickness(mm)Size(inch)
Type
Type-O pipes
Type-1/2H or Hpipes
Piping Materials
Types of Copper Pipes (Reference)
The table shows the standards in Japan. Using this table as a reference, choose pipes that meet the local standards.
Piping Materials/Radial Thickness
Flare Machining (type-O and OL only)
Flare Machining Dimension(mm)
External dimension of pipes
Size
Dimension A
R410A R22
6.35
9.52
12.7
15.88
19.05
1/4"
3/8"
1/2"
5/8"
3/4"
9.1
13.2
16.6
19.7
24.0
9.0
13.0
16.2
19.4
23.3
Flare Nut
Type-2 flare nuts instead of type-1 nuts are used to increase the strength. The size of some of the flare nuts have also
been changed.
Flare nut dimension(mm)
R410A(Type2) R22(Type1)
6.35
9.52
12.7
15.88
19.05
1/4"
3/8"
1/2"
5/8"
3/4"
17.0
22.0
26.0
29.0
36.0
17.0
22.0
24.0
27.0
36.0
6.35
9.52
12.7
15.88
1/4''
3/8''
1/2''
5/8''
0.8t
0.8t
0.8t
1.0t
19.05 3/4'' 1.0t
Dimension A
External dimension of pipes Size
Dimension B
Dimension B
7
8
NO
Wind direction
Air outlet
Cushion rubber
4.Installation dimension(Unit:mm)
*
9
1U07BS1ERA
1U09BS1ERA
1U12BS1ERA
1U18FS1ERA
1U24GS1ERA
1.
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
A
B
Outdoor unit
Indoor unit
Oil trap
Tobend a pipe,givetheroundnessaslargeaspossiblenottocrushthepipe,
ƽ
andthebendingradiusshouldbe30to40
mm or longer.
Connecting the pipe of gas side first makes working easier.
ƽ
TheconnectionpipeisspecializedforR410A.ƽ
Half union
Flare nut
Torque wrench
CAUTION
Be careful that matters, such as wastes of sand
s,water,
,etc.shallnotenterthepipe.
ThestandardpipelengthisC m.IfitisoverDm,thefunctionoftheunitwillbeaffected.Ifthepipe
has
to be lengthened, the refrigerant should be charged,
according to E g/m. But the charge of refrigerant
must
beconductedbyprofes
sionalairconditionerengineer.Beforeaddingadditionalrefrigerant,
perform
air
purgingfromtherefrigerantpipesandindoorunitusing a vacuumpump,then
Spanner
Forced fastening without careful centering may
damagethethreadsandcause a leakageofgas.
Pipe Diameter(ǿ) Fastening torque
Liquid side6.35mm(1/4") 18N.m
Liquid/Gas side9.52mm(3/8") 42 N.m
Gasside12.7mm(1/2") 55N.m
Gasside15.88mm(5/8") 60N.m
Max.Elevation:
In case the elevation A is more
than 5m, oil trap shoud be
installed every 5~7
Max. Length:
In case the pipe length B is
more thanDm, the refrigerant
should be charged, according
to E g/m.
Connection of pipes
charge
additional refrigerant.
Amax
Bmax
2.
10
11
(e.g.1U18FS1ERA)
12
1U07BS1ERA
1U09BS1ERA
1U12BS1ERA
1U18FS1ERA
1U24GS1ERA
T 25A/250V.
3
2
^
1
)
(
N
)(
L
)(
C
3
2
1
)
(
N
)
(
L
)
(
C
To Indoor unit
1U07BS1ERA
1U09BS1ERA
1U12BS1ERA
1U18FS1ERA 1U24GS1ERA
Model
Connecting wiring
Power cable
3G2.5mm
2
3G4.0mm
2
3G1.5mm
2
4G0.75mm
2
4G0.75mm
2
4G0.75mm
2
N
(
1
3
)
)
C(L
(
2
)
{
L
N
POWER
Outdoor unit
To Indoor unit
Outdoor unit
POWER
FOR 07K 09K 12K
FOR 18K 24K
13
15
Outdoor Unit
2
9
15
8
12
10
5
13
19
1
18
4
11
6
25
25
25
110
Haier Group
Address:No.1 Haier Road,Hi-tech Zone,Qingdao 266101 P.R.ChiQD
Contacts: TEL +86-532-8893-6943;FAX +86-532-8893-1010
Website: www.haier.com
Suction temperature sensor failure
When the The wiring of compressor is wrong or
the connection is poor
17
16
15
Lack of refrigerant
Check if there is leakage in the unit.
m
14
CONFORMIDAD DE LOS MODELOS
SEGÚN LAS NORMATIVAS EUROPEAS
CE
Todos los productos satisfacen los requisitos de las siguientes
normas europeas:
- Directiva de baja tensión, 73/23/CEE
- Directiva de baja tensión, 2006/95/CE
- Compatibilidad electromagnética 89/336/CEE
- Compatibilidad electromagnética 2004/108/CE
ROHS
Los productos satisfacen los requisitos de la directiva 2002/95/
CEE establecida por el Parlamento Europeo y el Consejo sobre
restricciones a la utilización de determinadas sustancias peligrosas
en aparatos eléctricos y electrónicos (Directiva RoHS UE).
WEEE
De acuerdo con la directiva 2002/96/CE del Parlamento Europeo,
se informa al consumidor acerca de los requisitos de eliminación
de productos eléctricos y electrónicos.
REQUISITOS DE ELIMINACIÓN:
Su aparato de aire acondicionado ha sido
marcado con este símbolo, el cual significa que
los productos de tipo eléctrico y electrónico
no deben mezclarse con residuos domésticos
sin clasificar. No intente desmontar el sistema
personalmente: tanto el desmontaje del sistema de aire
acondicionado como la manipulación del refrigerante, el
aceite y cualquier otro componente deben ser llevados
a cabo por un instalador capacitado, de acuerdo con la
legislación local y nacional al efecto. Los aparatos de aire
acondicionado deben ser manipulados en instalaciones de
manipulación especializadas y aptas para su reutilización,
reciclado y recuperación. Al garantizar la correcta
eliminación de este producto, usted contribuirá a evitar las
posibles consecuencias negativas que podría provocar
sobre el medioambiente y la salud humana. Póngase en
contacto con el instalador o la autoridad local pertinente
si desea obtener más información. Las pilas deben ser
extraídas del mando a distancia y eliminadas de forma
independiente, de acuerdo con la legislación local y nacional
al efecto.
INFORMACIÓN IMPORTANTE ACER-
CA DEL REFRIGERANTE UTILIZADO
1
1+2=
kg
R410A
2
kg
2=
1=
B
C
D
FE
kg
A
Este producto contiene gases fluorados de efecto invernadero
regulados por el Protocolo de Kioto. No los libere libremente a la
atmósfera.
Tipo de refrigerante: R410A
Valor GWP*: 1975
GWP = Potencial de contribución al calentamiento global
Escriba con tinta indeleble:
• 1 la carga de refrigerante que contiene el producto de fábrica
• 2 la cantidad de refrigerante adicional cargada durante la
instalación y
• 1+2 la carga total de refrigerante
en la etiqueta de carga de refrigerante suministrada con el
producto.
Una vez escritos los datos correspondientes, la etiqueta deberá
adherirse cerca de la conexión de carga del producto (por ejemplo,
sobre la parte interna de la cubierta de la válvula de retención).
A Contiene gases fluorados de efecto invernadero regulados por el
Protocolo de Kioto.
B Carga de refrigerante que contiene el producto de fábrica:
consulte la placa de características de la unidad.
C Cantidad de refrigerante adicional cargada durante la instalación.
D Carga total de refrigerante.
E Unidad exterior.
F Botella de refrigerante y colector de carga.
Contiene gases fluorados de efecto invernadero
regulados por el Protocolo de Kioto.
Haier Industrial Park, No.1 Haier Road, Qingdao, República Popular China
F
A
C
E
D
A
F
C
E
D
G
B
G
4
Dibujos de instalación de las unidades interior y exterior
Los modelos cumplen la norma R410A sobre refrigerantes libres de HFC.
Para obtener información sobre la instalación de las unidades interiores, consulte el manual de instalación proporcionado
con las mismas.
(El diagrama muestra una unidad interior montada en pared.)
La imagen anterior de las unidades interior y exterior solamente sirve de referencia.
Remítase al producto real adquirido.
más de 15 cm
Debe prestarse atención
a la pendiente del
manguito de drenaje
Organización de la
dirección de los tubos
Izquierda
Izquierda trasera
Derecha
trasera
Derecha
Inferior
más de
10 cm
más de 10 cm
más de
20 cm
más de 60 cm
Fijación de la unidad exterior
Fije la unidad a un bloque de
cemento con pernos (10 mm) y
tuercas firme y horizontalmente.
Si instala la unidad sobre una
pared, techo o tejado, instale un
soporte con clavos o cables consi-
derando la posibilidad de terremo-
tos o viento fuerte.
Si la vibración afectase a la casa,
fije la unidad instalando una alfom-
bra de absorción de vibraciones.
Las marcas comprendidas
entre
A
y
G
en la
ilustración corresponden
a los números de las
piezas.
La distancia entre la
unidad interior y el suelo
debe ser superior a 2 m.
Componentes opcionales para
la instalación de los tubos
Cinta no adhesiva
Cinta adhesiva
Soporte (L.S) con tornillos
Conexión de cable eléctrico para inte-
rior y exterior
Manguito de drenaje
Material aislante de calor
Cubierta
de orificio de entubación
más de 20 cm
más de 25 cm
Compresor (dentro de la unidad)
SALIDA DE AIRE
ENTRADA DE AIRE
TUBOS DE CONEXIÓN Y CABLEADO ELÉCTRICO
4 MANGUITO DE DRENAJE
15
Precauciones de seguridad
Lea detenidamente la siguiente información para poner en funcionamiento el aire acondicionado de forma correcta.
A continuación se enumeran tres tipos de precauciones de seguridad y sugerencias.
ADVERTENCIA Si realiza operaciones de forma incorrecta, pueden producirse graves consecuencias, como
la muerte o graves lesiones.
PRECAUCIÓN Si realiza operaciones de forma incorrecta, pueden producirse lesiones o daños en la
máquina; en algunos casos pueden producirse graves consecuencias.
INSTRUCCIÓN: Esta información puede asegurar el correcto funcionamiento de la máquina.
Símbolos utilizados en las ilustraciones
: indica una acción que se debe evitar.
: indica que es obligatorio seguir las instrucciones importantes.
: indica un componente que se debe conectar a tierra.
: atención a las descargas eléctricas (este símbolo se muestra en la etiqueta de la unidad principal.)
Después de leer este manual, entréguesela a aquellas personas que utilicen a la unidad.
El usuario de esta unidad debe tener este manual a mano y ponerlo a disposición de quienes repararán o reubicarán la unidad. Asimismo,
debe ponerlo a disposición de los nuevos usuarios cuando el producto cambio de manos.
Asegúrese de seguir estas importantes precauciones de seguridad.
ADVERTENCIA
Si se producen fenómenos anormales
(por ejemplo, olor a quemado), corte la
fuente de alimentación inmediatamente,
y póngase en contacto con el distribuidor
para averiguar el método de manipulación.
En dicho caso, si sigue utilizando el aire acondicionado, éste
resultará dañado, y pueden producirse descargas eléctricas o
peligro de incendio.
Tras un largo período de tiempo sin utilizar
el aparato de aire acondicionado, debe
comprobar la base para ver si se han pro-
ducido daños.
Si la base dañada no se repara, es posible
que la unidad se caiga y provoque acci-
dentes.
● No desmonte la boca de salida de la
unidad exterior.
La exposición del ventilador es muy peli-
grosa, ya que puede provocar lesiones
en las personas.
Cuando necesite mantenimiento y repa-
ración, llame al distribuidor para gestio-
narlo.
Si el mantenimiento y la reparación se
realizan de forma incorrecta podrían
producirse fugas de agua, descargas
eléctricas y peligro de incendio.
Desactivar
ADVERTENCIA
No se pueden colocar cosas o personas
sobre la unidad exterior. La caída de cosas o
personas puede provocar accidentes.
No ponga en funcionamiento el aire acon-
dicionado con las manos mojadas. De lo con-
trario, se producirán descargas eléctricas.
Utilice sólo fusibles del tipo correcto.
No se puede utilizar ningún cable ni otro ma-
terial que sustituya al fusible, de lo contrario,
se producirán fallos o incendio.
Utilice el tubo de descarga correctamente
para asegurar la eficacia de la descarga.
Si utiliza el tubo de forma incorrecta podrían
producirse fugas de agua.
Interruptor de circuito de fugas eléctricas instalado.
Provoca descargas eléctricas con facilidad sin el interruptor de
circuito.
El aire acondicionado no puede instalarse en lugares con gases
inflamables, ya que podrían provocar peligro de incendio.
El distribuidor es el responsable de la instalación del aparato de
aire acondicionado. Si la instalación se realiza de forma incor-
recta podrían producirse fugas de agua, descargas eléctricas y
peligro de incendio.
Llame al distribuidor para tomar medidas que eviten fugas de
refrigerante.
Si el aparato de aire acondicionado está instalado en una habita-
ción pequeña, asegúrese de tomar las medidas necesarias para
evitar
asfixia, incluso en caso de fuga de refrigerante.
Cuando el aire acondicionado se instala o se vuelve a instalar, el
distribuidor en el responsable de dichas tareas.
Si la instalación se realiza de forma incorrecta podrían producir-
se fugas de agua, descargas eléctricas y peligro de incendio.
Conecte el cable de conexión a tierra.
El cable de conexión a tierra no debe conectarse al
tubo de gas, tubo de agua, barra pararrayos o línea
telefónica. Si la conexión a tierra se realiza de manera
incorrecta, podrían producirse descargas.
Puesta a
tierra
16
Precauciones de seguridad
ADVERTENCIA
La unidad debe ser instalada por un profesional.
La instalación inadecuada por una persona no cualificada puede
provocar fugas de agua, descargas eléctricas o un incendio.
Coloque la unidad en una superficie estable y nivelada que
soporte el peso de la misma para impedir que se vuelque o se
caiga, evitando así lesiones personales.
Utilice solamente los cables especificados para el cableado. Co
-
necte de forma segura todos los cables y asegúrese de que los
mismos no tensan los terminales.
Los cables que no se conecten de forma correcta y segura, pue
-
den generar calor y provocar un incendio.
Tome las medidas de seguridad necesarias contra tifones y terre
-
motos para evitar que la unidad se caiga.
No realice ningún cambio o modificación a la unidad. Si surgen
problemas, consultar distribuidor.
Si las reparaciones no se realizan correctamente, se pueden
producir fugas de agua en la unidad, lo que supone un riesgo
de descargas eléctricas. También se puede producir humo o un
incendio.
Asegúrese de seguir atentamente todos los pasos de este
manual cuando instale la unidad.
La instalación inadecuada puede provocar fugas de agua, de
-
scargas eléctricas, humo o incendios.
Encomiende todos los trabajos eléctricos a un electricista pro
-
fesional de forma que se cumplan las normativas locales y las
instrucciones proporcionadas en este manual. Fije un circuito
designado exclusivamente a la unidad.
La instalación inadecuada o la falta de capacidad de los circuitos
puede hacer que la unidad no funcione correctamente o presen-
te riesgos de descargas eléctricas, humo e incendio.
Acople de forma segura la cubierta de terminales (panel) a la
unidad.
Si se instala incorrectamente, puede entrar polvo y/o agua en la
unidad lo que supone un riesgo de descargas eléctricas, humo o
incendio.
Utilice únicamente el refrigerante R410A tal y como se indica en
la unidad cuando la instale o reubique.
El uso de cualquier otro refrigerante o la penetración de aire en
el circuito de la unidad puede provocar que ésta funcione en un
ciclo anómalo, lo que puede provocar que se queme.
ADVERTENCIA
No toque las aletas del intercambiador de calor con las manos al
descubierto ya que están afiladas y son peligrosas.
En el caso de que haya una fuga de gas refrigerante, proporcio
-
ne la ventilación adecuada a la sala.
Si el gas refrigerante fugado queda expuesto a una fuente de
calor, se pueden producir gases nocivos.
Con
aparatos de aire acondicionado de tipo All-Fresh, el aire ex-
terior se puede dirigir directamente dentro de la sala. Tenga esto
en cuenta cuando instale la unidad.
La
exposición directa al aire de exterior puede suponer un riesgo
para la salud así como causar deterioro en productos alimenti-
cios.
No pase por alto las instrucciones de seguridad de los dispositi
-
vos y no cambie la configuración.
Si pasa por alto las instrucciones de seguridad de la unidad,
como por ejemplo el cambio de presión y el cambio de tempera-
tura, o utiliza piezas distintas a las proporcionadas por el provee-
dor o el especialista, se pueden producir un incendio o explosión.
Cuando instale la unidad en una sala pequeña, protéjase contra
la hipoxia causada por el refrigerante fugado que alcance el nivel
umbral.
Consulte al distribuidor para tomar las medidas necesarias.
Cuando reubique el aparato de aire acondicionado, consulte al
proveedor o a un especialista.
La instalación inadecuada puede provocar fugas de agua, de
-
scargas eléctricas o incendios.
Después de completar las tarea de servicio, compruebe si que
-
dan fugas de gas refrigerante.
Si el gas refrigerante fugado queda expuesto a una fuente de
calor, como por ejemplo un calefactor, una estufa o una parrilla
eléctrica, se pueden producir gases nocivos.
Utilice solamente las piezas especificadas.
La unidad debe ser instalada por un profesional. La instalación
inadecuada puede provocar fugas de agua, descargas eléctricas,
humo o incendios.
17
Precauciones de seguridad
Precauciones para manipular unidades para utilizarse con R410A
Precaución
No utilizar el tubo refrigerante asistente
El refrigerante usado y el aceite del refrigerador de los tubos
existentes contiene una gran cantidad de cloro que deteriorará el
aceite del refrigerador de la nueva unidad.
R410A es un refrigerante de alta presión y el uso de los tubos
existentes puede dar lugar a reventones.
Mantenga las superficies interior y exterior de los tubos limpias y
sin contaminantes como el sulfuro, óxidos, partículas de polvo o
suciedad, aceites y humedad.
Los contaminantes que se encuentran dentro del tubo refrigeran
-
te provocarán el deterioro del aceite refrigerante.
Utilice una bomba de vacío con una válvula de comprobación de
flujo inverso.
Si se utilizan otros tipos de válvula, el aceite de la bomba de
vacío retrocederá al circuito refrigerante y provocará el deterioro
del aceite del refrigerador.
No utilice las siguientes herramientas que hayan sido utilizadas
con los refrigerantes convencionales. Prepare las herramientas que
vaya utilizar exclusivamente con R410A.
(Colector, manguera de carga, detector de fuga de gas, válvula
de comprobación de flujo inverso, base de carga del refrigerante,
calibrador de vacío y equipo de recuperación de refrigerante.)
Si y el refrigerante y/o el aceite refrigerante residual de estas
herramientas se mezcla con el refrigerante R410A, éste se dete-
riorará.
Dado que el refrigerante R410A no contiene cloro, los detectores
de fuga de gas para refrigeradores convencionales no funcio-
narán.
Precaución
Almacene los tubos que se van a utilizar durante la instalación de
las unidades interiores y mantenga ambos extremos de los tubos
sellados hasta el preciso instante en el que se suelden. (Mantenga
los ángulos y otras juntas envueltas en plásticos.)
Si entra polvo, suciedad o agua en el circuito refrigerante, el
aceite de la unidad podría deteriorarse o provocar averías en el
compresor.
Utilice una pequeña cantidad de aceite de ésteres, aceite de éter o
alcalibenceno para recubrir abocinados y uniones de bridas.
Una gran cantidad de aceite mineral deteriorará el aceite de la
máquina refrigerante.
Utilice refrigerante
líquido para cargar el sistema.
Si carga la unidad con refrigerante gaseoso el refrigerante de
la botella cambiará su composición y provocará una pérdida de
rendimiento.
No utilice una botella carga.
El uso de una botella de carga cambiará la composición del refri
-
gerante y provocará pérdida de potencia.
Preste especial atención cuando manipule las herramientas.
Si se introducen objetos extraños como polvo, sociedad o agua
en el circuito refrigerante, el aceite de la máquina refrigerante se
deteriorará.
Utilice solamente refrigerante R410A.
El uso de refrigerantes que contengan cloro (por ejemplo R22)
deteriorará el refrigerante.
Antes de utilizar la unidad
Precaución
No instale la unidad en lugares donde haya riesgo de fuga de gas
inflamable.
El gas fugado acumulado alrededor de la unidad puede desen-
cadenar un incendio.
No utilice la unidad para conservar comida, animales, plantas, arte-
factos
o para otras finalidades especiales.
La unidad no está diseñada para proporcionar condiciones ade-
cuadas para conservar la calidad de estos elementos.
No utilice la unidad en un entorno inusual.
El uso de la unidad en presencia de una gran cantidad de aceite,
vapor, ácido, disolventes alcalinos o tipos especiales de espray
puede producir una pérdida considerable de rendimiento y/o ave-
rías, además del riesgo existente de descargas eléctricas, humo
o incendio.
La presencia de disolventes orgánicos o gas corroído (como
amoniaco, compuestos de azufre y ácido) puede provocar fugas
de agua o gas.)
Cuando instale la unidad en un hospital, tome las medidas
necesarias para eliminar el ruido.
Los equipos médicos de alta frecuencia pueden interferir en el
funcionamiento normal de la unidad de aire acondicionado o
viceversa.
Lo coloque la unidad sobre objetos que no se puedan mojar.
Cuando el nivel de humedad supere el 80% o cuando el sistema
de drenaje se atasque, las unidades interiores pueden gotear
agua.
La instalación de un sistema de drenaje centralizado para la uni-
dad exterior también debe tenerse en cuenta para evitar el goteo
de agua de las unidades exteriores.
18
Precauciones de seguridad
Antes de instalar (reubicar) la unidad o realizar tareas eléctricas
Precaución
Conecte la unidad a tierra.
No conecte las tomas de tierra de la unidad a tubos de gas,
tubos de agua, pararrayos o a los terminales de conexión a tierra
de teléfonos. La conexión inadecuada a tierra supone riesgos de
descargas eléctricas, humo, incendio. Además, el ruido causa-
do por una conexión de este tipo puede provocar averías en la
unidad.
Asegúrese de que los cables no están tensos.
Si los cables están demasiado tirantes, se pueden romper o
generar calor y/o humo, lo que puede provocar un incendio.
Instale un disyuntor para fugas de corriente en la fuente de alimen-
tación para evitar el riesgo de descargas eléctricas.
Si no cuenta con un disyuntor para fugas de corriente, existe el
riesgo de descargas eléctricas, humo o incendio.
Utilice disyuntores y fusibles (disyuntor de corriente eléctrica,
conmutador remoto <conmutador+fusible de Tipo-B>, disyuntor de
circuito o con carcasa moldeada) con una capacidad de corriente
adecuada.
El uso de fusibles de gran capacidad, cables de acero o cables
de cobre puede dañar la unidad o provocar humo o un incendio.
No rocíe agua en aparatos de aire acondicionado mi sumerja
dichos aparatos en agua.
La presencia de agua sobre la unidad supone un riesgo de de
-
scargas eléctricas.
Compruebe periódicamente la plataforma sobre la que se coloca la
unidad
para ver si existen daños y evitar así que dicha unidad se caiga.
Si la unidad se deja en una plataforma dañada, puede volcarse y
provocar lesiones personales.
Cuando instale tubos de drenaje, siga las instrucciones del manual
y asegúrese de que desaguan el agua correctamente para evitar
condensación.
Si la instalación no se realiza correctamente, se pueden producir
fugas de agua y el mobiliario puede resultar dañado.
Deshágase adecuadamente de los materiales de embalaje.
El embalaje puede incluir objetos como, por ejemplo, clavos.
Deshágase de ellos adecuadamente para evitar lesiones perso-
nales.
Las bolsas de plástico suponen un riesgo de asfixia para los
niños. Despedace las bolsas de plástico antes de deshacerse de
ellas para evitar accidentes.
Antes de ejecutar las comprobaciones
Precaución
Para evitar descargas eléctricas, no utilice los conmutadores con
las manos mojadas.
No toque los tubos refrigerantes con las manos al descubierto
mientras el aparato está en funcionamiento o inmediatamente de-
spués de haberlo estado.
Dependiendo del estado del refrigerante del sistema, ciertas par
-
tes de la unidad como los tubos y el compresor, pueden alcan-
zar una temperatura muy baja o caliente lo que puede provocar
quemaduras a las personas.
No utilice la unidad sin que los paneles y las protecciones de segu-
ridad estén colocados en sus lugares correctos.
Están ahí para evitar lesiones a los usuarios producidas por to
-
car accidentalmente piezas giratorias, con elevada temperatura
o alto voltaje.
No desconecte alimentación inmediatamente después de detener
la unidad.
Deje que transcurran al menos cinco minutos antes de apagar la
unidad. De lo contrario dicha unidad puede tener fugas de agua
u otros problemas.
No ponga en funcionamiento la unidad sin los filtros de aire.
Las partículas de polvo del aire pueden obturar el sistema y cau
-
sar averías.
19
Leer antes de realizar la instalación
Elementos que se deben comprobar
(1). Compruebe el tipo de refrigerante utilizado por la unidad que se va a revisar. Tipo de refrigerante: R410A
(2). Compruebe los síntomas que presenta la unidad que se va a revisar. Busque en el manual de servicio los síntomas relacionados con
el circuito refrigerante.
(3). Asegúrese de leer atentamente las precauciones de seguridad que se encuentran al principio de este documento.
(4). Si hay fuga de gas o si el refrigerante restante se expone a una llama viva, se puede formar ácido fluorhídrico. Mantenga el lugar de
trabajo bien ventilado.
PRECAUCIÓN
Instale los tubos nuevos inmediatamente después de quitar los usados para mantener la humedad fuera del circuito refrigerante.
El cloruro en algunos tipos de refrigerantes como el R22 deteriorarán el aceite de la máquina refrigerante.
Herramientas y materiales necesarios
Preparar las siguientes herramientas y materiales para instalar y reparar la unidad.
Herramientas necesarias para utilizar con R410A (disponibilidad de herramientas para utilizar con R22 y R407C).
1. Para utilizarse exclusivamente con R410A (no se deben utilizar con R22 o R407C)
Herramientas y materiales Uso Notas
Colector Evacuación, carga del refrigerante 5,09 MPa en alta presión.
Manguera de carga
Evacuación, carga del refrigerante Diámetro de la manguera mayor que los convencionales.
Equipo de recuperación del refrigerante Recuperación del refrigerante
Botella de refrigerante Carga de refrigerante Anote el tipo de refrigerante. Color rosa la parte superior de la botella.
Puerto de carga de la botella de
refrigerante
Carga de refrigerante Diámetro de la manguera mayor que los convencionales.
Tuerca cónica Conectar la unidad a los tubos Usar las tuercas cónicas de tipo 2.
2. Herramientas y materiales que se pueden utilizar con R410 con algunas restricciones
Herramientas y materiales Uso Notas
Detector de fuga de gas Detección de fugas de gas Se pueden usar los adecuados para el refrigerante de tipo HFC.
Bomba de vacío Secado en vacío Se puede utilizar si se acopla un adaptador de comprobación de flujo inverso.
Herramienta de conicidad Maquinaria de conicidad de tubos Se han realizo cambios en la dimensión de la maquinaria de conicidad. Consulte la página
siguiente.
Equipo de recuperación del refrigerante Recuperación de refrigerante Se puede utilizar si está pensado para utilizarse con R410A.
3. Herramientas y materiales que se van a utilizar con R22 o R407C que también pueden utilizarse con R410A
Herramientas y materiales Uso Notas
Bomba de vacío con válvula de
comprobación
Secado en vacío
Curvadora Doblar tubos
Llave dinamométrica Apretar tuercas cónicas Solamente
12,70 (1/2'') y 15,88 (5/8'') tienen una dimensión de maquinaria de
conicidad más grande.
Cortatubos Cortar tubos
Soldador y botella de nitrógeno Soldar tubos
Medidor de carga de refrigerante Carga de refrigerante
Malla de vacío Comprobar el grado de vacío
4. Herramientas y materiales que no se deben utilizar con R410A
Herramientas y materiales Uso Notas
Botella de carga Carga de refrigerante No se debe utilizar con unidades de tipo R410.
Las herramientas para R410A se deben utilizar con extremo cuidado y se debe impedir que la humedad y el polvo entre en el circuito.
20
Leer antes de realizar la instalación
Materiales para tubos
Tipos de tubos de cobre (referencia)
Presión de funcionamiento máxima Refrigerantes aplicables
3,4 MPa R22 y R407C
4,15 MPa R410A
Usar tubos que cumplen los estándar locales.
Materiales para tubos/Grosor del radio
Utilice tubos fabricados con cobre desoxidado con fósforo.
Dado que la presión de funcionamiento de las unidades que utilizan R410A es superior a la de las unidades que utilizan R22, emplee
tubos con al menos el grosor radial especificado en el gráfico siguiente. (No se deben utilizar tubos con un grosor radial de 0,7 mm o
menos.)
Tamaño (mm) Tamaño (pulgadas) Grosor radial (mm) Tipo
6.35 1/4'' 0,8t
Tuberías de tipo O
9.52 3/8" 0,8t
12.7 1/2" 0,8t
15.88 5/8" 1,0t
19.05 3/4" 1,0t Tubos de tipo 1/2H o H
Aunque es posible utilizar el tipo O para tubos con un tamaño de hasta 19,05 (3/4") con refrigerantes convencionales, utilice tubos de
tipo 1/2H para unidades que utilicen R410A. (Se pueden utilizar tubos de tipo-O si el tamaño del tubo es 19.05 y el grosor radial es de
1,2 t.)
La tabla
muestra los estándares de Japón. Utilice esta tabla como referencia y elija tubos que cumplan los estándares locales.
Maquinaria de conicidad (solamente para el tipo O y OL)
Las dimensiones de la máquina de conicidad para unidades que utilizan R410A son mayores que las de las unidades que utilizan R22
para aumentar la hermeticidad del aire.
Dimensiones de la máquina de conicidad (mm)
Dimensiones externas de los
tubos
Tamaño
Dimensión A
R410A R22
6.35 1/4'' 9.1 9.0
9.52 3/8" 13.2 13.0
12.7 1/2" 16.6 16.2
15.88 5/8" 19.7 19.4
19.05 3/4" 24.0 23.3
Si una herramienta de comicidad de tipo acoplamiento se utiliza para realizar la conicidad en unidades que usan R410A, haga que
la parte que sobresale del tubo tenga un tamaño comprendido entre 1,0 y 1,5 mm. El calibre de tubos de cobre es útil para ajustar la
longitud de la prominencia del tubo.
Tuerca cónica
Se utilizan tuercas cónicas de tipo 2 en lugar de las de tipo 1 para aumentar la fuerza. El tamaño de algunas de las tuercas cónicas
también ha cambiado.
Dimensiones de la máquina de conicidad (mm)
Dimensiones externas de los
tubos
Tamaño
Dimensión B
R410A (Tipo 2) R22 (Tipo 1)
6.35 1/4'' 17.0 17.0
9.52 3/8" 22.0 22.0
12.7 1/2" 26.0 24.0
15.88 5/8" 29.0 27.0
19.05 3/4" 36.0 36.0
La tabla muestra los estándares de Japón. Utilice esta tabla como referencia y elija tubos que cumplan los estándares locales.
Dimensión A
Dimensión B
21
Leer antes de realizar la instalación
Prueba de hermeticidad del aire
El método convencional NO cambia. Tenga en cuenta que el detector de fugas de refrigerante para R22 o R407C no puede detectar
fugas de R410A.
Elementos que se deben tener muy en cuenta:
1. Presurice el equipo con nitrógeno hasta la presión de diseño y, a continuación, evalúe la hermeticidad del aire de dicho equipo
teniendo en cuenta las variaciones de temperatura.
2. Cuando investigue las ubicaciones de las fugas utilizando un refrigerante, asegúrese de usar R410A.
3. Asegúrese de que R410A se encuentran estado líquido cuando lo cargue.
Razones:
1. El uso de oxígeno cómo gas presurizado puede provocar explosiones.
2. La carga con gas R410A cambiará la composición del refrigerante restante de la botella, por lo que no podrá utilizarlo.
Vacío
1. Bomba de vacío con válvula de comprobación
Se necesita una bomba de vacío con válvula de comprobación para evitar que el aceite de dicha bomba retroceda y se introduzca
en el circuito refrigerante cuando la alimentación de la bomba de vacío se apague (error de alimentación). También es posible
acoplar una válvula de comprobación a la bomba de vacío real después.
2. Grado estándar de vacío para la bomba de vacío
Utilice una bomba que alcance 65 Pa o menos después de 5 minutos de funcionamiento.
Además, asegúrese de utilizar una bomba de vacío en la que se hayan realizado todas las tareas de mantenimiento
y esté engrasada utilizando el aceite especificado. Si no se han realizado las tareas de mantenimiento
adecuadas en la bomba de
vacío, el grado de vacío puede ser demasiado bajo.
3. Precisión necesaria del indicador de vacío
Utilice un indicador de vacío que pueda medir hasta 650Pa. No utilice un colector general ya que no puede medir un grado de
vacío de 650 Pa.
4. Tiempo de evacuación
Evacuó el equipo durante 1 hora después de alcanzar 650 Pa.
Después de la evacuación, deje el equipo en reposo durante 1 hora y asegúrese de que el vacío no se pierde.
5. Procedimiento de funcionamiento cuando la bomba de vacío se detiene
Para evitar flujo de retorno del aceite de la bomba de vacío, abra la válvula de seguridad del lado de la bomba de vacío o afloje la
manguera de carga para retraer el aire antes de detener el funcionamiento. Debe utilizar el mismo procedimiento cuando utilice una
bomba de vacío con válvula de comprobación.
Carga de refrigerante
R410A debe estar en estado líquido durante la carga.
Razones:
R410A es un refrigerante pseudo-azeotrópico (punto de ebullición R32=-52
O
C, R125=-49
O
C) y se puede manipular más o menos de
la misma forma que el R22; sin embargo, asegúrese de rellenar el refrigerante desde el lado del líquido. Si lo hace desde el lado del
gas la composición del refrigerante cambiará en la botella.
Nota
En el caso la botella con sifón, el R410A líquido se carga sin poner la botella boca abajo. Compruebe el tipo de botella antes de
realizar la carga.
Remedios que se deben tomar en caso de fuga del refrigerante
Si el refrigerante se fuga, debe cargar más refrigerante. (Agregue el refrigerante desde el lado del líquido)
Características de los refrigerantes convencionales y nuevos
Debido a que el R410A es un refrigerante azeotrópico simulado, se puede manipular prácticamente de la misma manera que un
refrigerante sencillo, como por ejemplo el R22. Sin embargo, si el refrigerante se retira en la fase de gas, la composición del
refrigerante de la botella cambiará.
Quite el refrigerante en la fase líquida. Si el refrigerante
se fuga, puede agregar más refrigerante.
Antorcha de haluro
Detector de fugas de R22 o R407C
convenientemente
22
Procedimiento instalación
Instalación de la unidad exterior
1. Accesorios
"Borde" para proteger los cables
eléctricos de un borde de apertura.
2. Selección del lugar de instalación
Seleccione un lugar de instalación que cumpla con las siguientes condiciones y, al mismo tiempo, obtenga un consentimiento del cliente o
del usuario.
Coloque la unidad en un lugar en el que circule el aire.
Coloque la unidad en un lugar alejado de radiaciones de calor emitidas por otras fuentes de calor.
Coloque la unidad en un lugar en el que pueda descargarse el agua de drenaje.
Coloque la unidad en un lugar en el que el ruido y el aire caliente no molesten a los vecinos.
Coloque la unidad en un lugar en el que no haya grandes nevadas durante el invierno.
Coloque la unidad en un lugar en el que no existan obstáculos en la entrada o salida de aire.
Coloque la unidad en un lugar en el que la salida de aire no esté expuesta a fuertes vientos.
La instalación no se realizará correctamente si la unidad está rodeada por los cuatro lados. Debe dejar 1 m o más de espacio por
encima de la unidad.
No monte las lamas en lugar en el que exista la posibilidad de que se produzca un cortocircuito.
Al instalar varias unidades, compruebe que existe espacio de aspiración suficiente para evitar cortocircuitos.
Requisito de espacio abierto alrededor de la unidad
3. Instalación de la unidad exterior
Fije la unidad a la base de la forma adecuada en función del estado del
lugar de la instalación. Consulte para ello la siguiente información.
Deje suficiente espacio para fijar la base de hormigón mediante los
pernos de anclaje.
Coloque la base de hormigón a una profundidad suficiente.
Instale la unidad de manera que el ángulo de inclinación sea inferior a 3
grados.
Prohibido colocar la unidad en el suelo directamente. Asegúrese de que
hay espacio suficiente cerca del orificio de drenaje en la placa inferior, lo
que garantizará que el agua se desagua sin problemas.
4. Dimensiones de instalación (unidad: mm)
(Espacio para
mantenimiento)
Entrada de aire
Entrada de aire
Salida de aire
Distancia Caso I Caso II Caso III
L1 abrir abrir 500 mm
L2 300 mm 300 mm abrir
L3 150 mm 300 mm 150 mm
Nota:
(1) Fije las piezas con los tornillos.
(2) No permita que el fuerte viento
entre directamente en el orificio
de flujo de aire de salida.
(3) Debe dejar una distancia de un
metro desde la parte superior de la unidad.
(4) No bloquee los alrededores de la unidad con objetos.
(5) Si la unidad exterior se instala en un lugar expuesto al
viento, instálela de forma que la rejilla de salida de aire NO
apunte en la dirección del viento.
NO
Dirección del
viento
Salida de
aire
Perno de anclaje
Unidad
Goma amortiguadora
Base de
hormigón
Orificio de
distribución del
cableado de
alimentación
Terminal del
cableado de
alimentación
Modelo AN D AL L1 L2 L3
1U07BS1ERA 780 245 540 500 140 256
1U09BS1ERA 780 245 540 500 140 256
1U12BS1ERA 780 245 540 500 140 256
1U18FS1ERA 810 288 688 583 113.5 319.5
1U24GS1ERA 860 308 730 633 113.5 340
Borde
23
Procedimiento instalación
Conexión de los tubos
1. Tamaño de los tubos
1U07BS1ERA 1U09BS1ERA
1U12BS1ERA
Tubo de líquido
6,35x0,8 mm
Tubo de gas
9,52x0,8 mm
1U18FS1ERA
Tubo de líquido
6,35x0,8 mm
Tubo de gas
12,7x0,8 mm
1U24GS1ERA
Tubo de líquido
9,52x0,8 mm
Tubo de gas
15,88x1,0 mm
2
. Conexión de los tubos
Para doblar un tubo, intente hacer la curva lo más suave posible para no aplastar el tubo. El radio de doblado
debe ser de entre 30 y 40 mm o superior.
Será más sencillo conectar en primer lugar el tubo de gas.
El tubo de conexión es especial para el tipo R410A.
Procure que no penetren materiales, como residuos de arena, agua, etc., en el tubo.
PRECAUCIÓN
La longitud del tubo estándar es C m. Si es superior a D m, el funcionamiento de la unidad se verá afectado. Si
es necesario alargar el tubo, deberá cargarse refrigerante adicional a razón de E g/m. No obstante, la carga de
refrigerante deberá ser realizada por un ingeniero profesional en aire acondicionado. Antes de añadir refrigeran-
te adicional, realice una purga de aire desde los tubos refrigerantes y la unidad interior utilizando una bomba de
vacío y cargue después el refrigerante adicional.
A
B
A
B
A
B
Unidad exterior
Unidad
interior
Unidad
interior
Unidad exterior
Unidad exterior
Unidad
interior
Filtro de aceite
Elevación máx. A máx.
En caso de que la elevación A sea
superior a 5 m, el filtro de aceite debe
instalarse cada 5 ~7 m.
Longitud máx.: B máx.
En caso de que la longitud del tubo B
sea superior a D m, deberá cargarse
el refrigerante a razón de E g/m.
Inserte las tuercas cónicas retiradas en los tubos que se
van a conectar y, a continuación, abocarde los tubos.
Si se fuerza la fijación sin aplicar centrado podrían
dañarse los tubos y provocarse una fuga de gas.
Media unión Tuerca cónica
Llave Llave dinamométrica
Diámetro del tubo (ø) Par de apriete
Lado de líquido 6,35 mm (1/4") 18N.m
Lado de líquido/gas 9,52mm (3/8") 42 N.m
Lado de gas 12,7mm (1/2") 55 N.m
Lado de gas 15,88 mm (5/8") 60 N.m
Unidad exterior A máx. B máx. C D E
1U07BS1ERA 10 15 5 7 20
1U09BS1ERA 10 15 5 7 20
1U12BS1ERA 10 15 5 7 20
1U18BS1ERA 15 25 5 7 20
1U24BS1ERA 15 25 5 7 45
24
Procedimiento instalación
Prueba de hermeticidad del aire
Tras finalizar la conexión del tubo de refrigerante, debe realizar la prueba de hermetizado.
La prueba de hermetizado utiliza el depósito de nitrógeno para dar presión según el modo de conexión del tubo tal y como
se muestra en la siguiente figura.
Las válvulas de gas y líquido están cerradas. Para evitar que el nitrógeno entre en el sistema de circulación de la unidad
exterior, apriete el vástago de la válvula antes de dar presión (ambos vástagos de las válvulas de gas y líquido).
1) Presurice durante más de 3 minutos a 0,3 MPa (3,0 kg/cm
2
g)
2) Presurice durante más de 3 minutos a 1,5 MPa (15 kg/cm
2
g) Se encontrarán las fugas más importantes.
3) Presurice durante aproximadamente 24 horas a 3,0 MPa (30 kg/cm
2
g) Se encontrarán las fugas más pequeñas.
Compruebe si la presión disminuye
Si la presión no disminuye, la comprobación se da por buena.
La presión disminuye, compruebe el punto de fuga.
Cuando se presurice durante 24 horas, una variación de 1
O
C en la temperatura ambiente provocará una variación de 0,01 MPa (0,1
kg/cm2 g) en la presión.
Debe corregirse durante la prueba.
Comprobación del punto de fuga
En los pasos 1) a 3), si la presión disminuye, compruebe la fuga en cada junta
escuchando, tocando, utilizando agua de jabón, etc. para
identificar
el punto de fuga. Tras comprobar el punto de fuga, vuelva a soldarlo o vuelva a apretar firmemente la tuerca.
Válvula de retención totalmente
cerrada (lado del líquido)
ExteriorInterior
Completamente apretado
Pieza cónica
Unidades interiores
Válvula de
retención
totalmente cerrada
(lado del gas)
Completamente apretado
Válvula de descarga
Registro
Unidades exteriores
Piezómetro de baja
presión
Piezómetro de alta presión
Separador
Válvula de
goteo
Depósito de nitrógeno
Manguera de
mantenimiento
Manómetro de presión de
línea
Tubos cobresoldados
Junta estañosoldada
Conector de protección grande
Botella de nitrógeno
Manómetro de presión la
botella
Pieza cónica
25
Procedimiento instalación
Vacío
Método de vacío de los tubos: utilizar
una bomba de vacío
1. Retire el tapón del puerto de mantenimiento de la válvula de 3 vías, el tapón del
vástago de la válvula de 2 vías y 3 vías, y conecte el puerto de mantenimiento a
la manguera de proyección de carga (inferior) del colector. Conecte entonces la
manguera de proyección de carga (central) del colector a la bomba de vacío.
2. ed rodacidni le iS .oícav ed abmob al enoicca y rotceloc led roirefni atipse al arbA
la escala (inferior) alcanza la condición de vacío por un momento, compruebe de
nuevo el paso 1.
3. Succione durante 15 minutos. Compruebe el nivel medido, que deberá ser de
-0,1 Mpa (-76cm Hg) en el lado de baja presión. Tras finalizar la succión, cierre el
mando de baja de la bomba de vacío. Compruebe el funcionamiento de las escala
y manténgala durante 1-2 min. Si la escala retrocede a pesar de ajustarse, realice
de nuevo los trabajos de conicidad y vuelva al punto 3.
4. 6
ed séupseD .adreiuqzi al aicah sodarg 09 saív 2 ed aluvláv al ed ogatsáv le arbA
segundos, cierre la válvula de 2 vías e inspeccione si existen fugas de gas.
5. ¿No existen fugas de gas? En caso de que exista una fuga de gas, apriete las conexiones de los tubos. Si la fuga se detiene, siga
con el paso 6. Si la fuga de gas no se detiene, descargue todo el refrigerante a través del puerto de mantenimiento. Después de
realizar de nuevo la operación de conicidad y succión, rellene con el refrigerante especificado desde la botella de gas.
6. Desconecte la manguera de carga del puerto de mantenimiento y abra las válvulas de 2
y 3 vías. Gire el vástago de la válvula hacia la izquierda hasta que golpee ligeramente.
7. Para evitar fugas de gas, gire el tapón del puerto de mantenimiento y el tapón del
vástago de las válvulas de 2 y 3 vías un poco por encima del punto en el que la torsión
aumenta súbitamente.
PRECAUCIÓN:
Si existen fugas de refrigerante en el aire acondicionado, será necesario descargar todo el refrigerante. Haga el vacío primero, y
cargue líquido refrigerante en el acondicionador de aire de acuerdo con la cantidad marcada en la placa de valores nominales.
Cerrar
Válvula de 2 vías
Válvula de 3 vías
Válvula de 2 vías
Válvula de 3 vías
Válvula de 2 vías
Válvula de 3 vías
Válvula de retención de líquido
Válvula de retención de gas
Colector (R410A)
Bomba de vacío (R410A)
Abrir
Puerto de mantenimiento
90 para 6 s
Válvula de 2 vías
Válvula de 3 vías
Válvula de 2 vías
Válvula de 3 vías
Tapa del puerto de mantenimiento
Tapa del vástago de válvula
Tapa del vástago de válvula
(por ejemplo 1U18FS1ERA)
26
Procedimiento instalación
Cableado eléctrico
¡ADVERTENCIA!
PELIGRO DE LESIONES PERSONALES O MUERTE
DESCONECTE LA ENERGÍA ELÉCTRICA EN EL INTERRUPTOR DE CIRCUITO O LA FUENTE DE ALIMENTACIÓN ANTES DE
REALIZAR CONEXIONES ELÉCTRICAS.
LAS CONEXIONES A TIERRA DEBEN COMPLETARSE ANTES DE REALIZAR CONEXIONES DE TENSIÓN DE LÍNEA.
Precauciones para el cableado eléctrico
El trabajo de cableado eléctrico sólo debe realizarlo el personal autorizado para dicha tarea.
No conecte más de tres cables al bloque de terminales. Utilice siempre orejetas de terminales en rizo de tipo redondo con agarre con
funda en los extremos de los cables.
Utilice exclusivamente conductores de cobre.
Selección del tamaño de la fuente de alimentación y los cables de interconexión
Seleccione los tamaños del cable y la protección de circuito en la siguiente tabla. (Esta tabla muestra cables de 20 m con una caída de
tensión inferior al 2%.)
Fase
Interruptor de circuito Tamaño del cable
de la fuente de
alimentación
(mínimo)
(mm
2
)
Interruptor de fugas de masa
Interruptor
(A)
Capacidad nominal del
protector de sobrecarga
de corriente (A)
Interruptor (A)
Corriente de
fuga (mA)
1U07BS1ERA
1U09BS1ERA
1U12BS1ERA
1U18BS1ERA
1 40 26 2.5 40 30
1U24GS1ERA 1 40 26 4.0 40 30
Si el cable de alimentación está dañado deberá ser reemplazado por el fabricante, agente de servicio o profesional cualificado.
Si el fusible de la caja de control se funde, cámbielo por otro de tipo T 25 A/250 V.
El método de cableado debe satisfacer los requisitos de las normas locales de cableado.
El cable de alimentación y el cable de conexión deben estar incluidos.
Todos los cables deben contar con el certificado de autentificación europeo. Durante la instalación, cuando quite los cables de conexión,
debe asegurarse de que el hilo de tierra es el último en quitarse.
El interruptor del aire acondicionado debe estar conectado a todos los polos y la distancia entre los dos contactos del interruptor no
debe ser inferior a 3 mm. Dicho método de desconexión debe instalarse en el cableado fijo.
La distancia entre los dos bloques de terminales de la unidad interior y la unidad exterior no debe ser superior a 5 m. Si es superior, el
diámetro del hilo se debe aumentar conforme al estándar de cableado local.
Se debe instalar un interruptor de fugas.
Procedimiento de cableado
1) Extraiga los tornillos del lateral
antes de tirar el panel delantero hacia la dirección que se muestra en la figura.
2) Conecte los cables al bloque de terminales de forma correcta y fije los cables con una pinza del cable situada junto al bloque de
terminales.
3) Coloque los cables de forma adecuada e introdúzcalos por la apertura del cableado
eléctrico del panel lateral.
ADVERTENCIA:
LOS CABLES DE INTERCONEXIÓN DEBEN CONECTARSE SEGÚN LA FIGURA SIGUIENTE. SI REALIZA EL CABLEADO DE FORMA
INCORRECTA PUEDEN PRODUCIRSE DAÑOS EN EL EQUIPO.
Modelo
Elemento
3
2
1
)
(
N
)(
L
)(
C
3
2
1
)
(
N
)
(
L
)
(
C
N
(
1
3
)
)
C(L(
2
)
{
INTENSO
PARA 07K 09K 12K
PARA 18K 24K
Unidad exterior
A la unidad interior
INTENSO
Unidad exterior
A la unidad interior
Modelo
1U07BS1ERA
1U09BS1ERA
1U12BS1ERA
1U18BS1ERA 1U24GS1ERA
Cableado de conexión
4G 0,75 mm
2
4G 0,75 mm
2
4G 0,75 mm
2
Cable de alimentación 3G 1,5 mm
2
3G 2,5 mm
2
3G 4,0 mm
2
27
L
N
14
Haier Group
Dirección: No.1 Haier Road, Hi-tech Zone, Qingdao 266101 República Popular China
Contactos: TEL: +86-532-8893-6943; FAX: +86-532-8893-1010
Sitio web: www.haier.com
Resolución de problemas en la unidad exterior
¡PRECAUCIÓN!
ESTA UNIDAD SE PONDRÁ EN FUNCIONAMIENTO DE FORMA INSTANTÁNEA SIN ACTIVARLA CUANDO SE SUMINISTRE LA
ENERGÍA ELÉCTRICA. ASEGÚRESE DE DESACTIVARLA ANTES DE DESCONECTAR LA ENERGÍA ELÉCTRICA PARA REALIZAR
EL MANTENIMIENTO.
Esta unidad cuenta con una función de sistema de reinicio automático que se activa al finalizar la interrupción de la energía.
1. Antes de iniciar el funcionamiento de prueba (para los modelos de bomba de calor)
Compruebe si el interruptor de la fuente de alimentación (interruptor principal) de la unidad se ha activado durante más de 12 horas
para energizar el calentador del cárter en previsión de la puesta en marcha.
2. Funcionamiento de prueba
Ponga la unidad en funcionamiento de forma continua durante 30 minutos y compruebe lo siguiente.
La presión de aspiración en la junta de comprobación de la válvula de servicio del tubo de gas.
La presión de descarga de la junta de comprobación del tubo de descarga del compresor.
La diferencia de temperatura entre el aire de retorno y el aire de suministro de la unidad interior.
Destellos del LED
en la
placa principal
Descripción del problema Analizar y diagnosticar
1 Error en la memoria EEPROM Error en la memoria EEPROM de la placa principal externa
2 Error de IPM Error de IPM
4
Error de comunicación entre la placa principal y
el módulo SPDU Error de comunicación SPDU
Error de comunicación superior a 4 minutos
5 Protección de alta presión Presión alta del sistema superior a
4,15 MPa
6
Protección contra exceso de voltaje del módulo
(solamente para SPUD)
Protección contra ausencia de voltaje del módulo
(solamente para SPUD)
Enviar desde el módulo SPUD
8
Protección contra
temperatura descarga del
compresor
Temperatura de descarga del compresor superior a 110 ºC
9 Anomalía en el motor de CC Obstrucción del motor de CC o error del motor
10 Anomalía en el sensor de tubos Cortocircuito o circuito abierto en el sensor de tubos
11 Error en el sensor de temperatura de succión
El cableado del compresor es erróneo o la conexión es
inestable
12
Anomalía en el sensor de temperatura ambiente
exterior
Cortocircuito o circuito abierto en el sensor de temperatura
ambiente exterior
13
Anomalía en el sensor de descarga del
compresor
Cortocircuito o circuito abierto en el sensor de descarga del
compresor
15
Error de comunicación entre las unidades interior
y exterior
Error de comunicación superior a 4 minutos
16
Ausencia de refrigerante o compruebe si hay
alguna fuga la unidad
Alarma y parar si se detecta que TD-tci>=75 dura 1 minuto
después de que el compresor se haya iniciado durante 10
minutos en el modo de refrigeración. Compruebe si hay
fuga en la unidad.
17 Error de inversión de la válvula de cuatro vías
Alarma y parar si se detecta que Tm<=75 dura 1 minuto
después de que el compresor se haya iniciado durante 10
minutos
en el modo de refrigeración. Confirmar el error se
aparece 3 veces en una hora.
18 Compresor obturado (solamente para SPUD) El compresor interno tiene una obstrucción anómala
19 Error en el circuito de selección PWM del módulo Circuito erróneo de selección PWM del módulo
25 Exceso de corriente en la fase U del compresor La corriente de la fase U del compresor es demasiado alta
25 Exceso de corriente en la fase V del compresor La corriente de la fase V del compresor es demasiado alta
25 Exceso de corriente en la fase W del compresor La corriente de la fase W del compresor es demasiado alta
28
CONFORMITÀ AI REGOLAMENTI
EUROPEI PER I MODELLI
CE
Tutti i prodotti sono conformi alle seguenti disposizioni europee:
- Direttiva bassa tensione 73/23/CEE
- Direttiva bassa tensione 2006/95/CEE
- Compatibilità elettromagnetica 89/336/CEE
- Compatibilità elettromagnetica 2004/108/CE
ROHS
I prodotti sono conformi ai requisiti della direttiva 2002/95/CEE
del Parlamento e del Consiglio Europeo sulla limitazione dell'uso
di alcune sostanze pericolose nei dispositivi elettrici ed elettronici
(direttiva RoHS UE).
WEEE
In conformità alla direttiva 2002/96/CE del Parlamento Europeo,
informiamo il consumatore relativamente ai requisiti per lo smalti-
mento dei prodotti elettrici ed elettronici.
REQUISITI PER LO SMALTIMENTO:
Il condizionatore acquistato è contrassegnato
con questo simbolo, che sta a significare che
le parti elettriche ed elettroniche non devono
essere mischiate con i rifiuti domestici. Non
tentare di aprire il sistema da soli: lo smontag-
gio del sistema del condizionatore, il trattamento del refri-
gerante, dell'olio e di altre parti deve essere effettuato da
un installatore qualificato conformemente alle leggi locali e
nazionali pertinenti. I condizionatori devono essere trattati
presso strutture di trattamento specializzate per il riutilizzo,
il riciclaggio e il ricondizionamento. Garantendo che questo
prodotto sia smaltito correttamente, si aiuterà a prevenire
possibili conseguenze negative per l'ambiente e la salute
umana. Contattare l'installatore o l'autorità locale per ulte-
riori informazioni. La batteria deve essere rimossa dal tele-
comando e smaltita separatamente in conformità alle leggi
locali e nazionali pertinenti.
IMPORTANTI INFORMAZIONI RELATIVE
AL REFRIGERANTE UTILIZZATO
1
1+2=
kg
R410A
2
kg
2=
1=
B
C
D
FE
kg
A
Questo prodotto contiene gas serra fluorinato, oggetto del Proto-
collo di Kyoto. Non lasciar sfogare nell'atmosfera.
Tipo di refrigerante:R410A
Valore GWP* :1975
GWP=global warming potential
Inserire, con inchiostro indelebile,
• 1 il carico di refrigerante del prodotto inserito in fabbrica
• 2 il quantitativo aggiuntivo di refrigerante caricato sul campo e
• 1+2 il carico di refrigerante totale
sull'etichetta con il carico di refrigerante in dotazione con il prodot-
to.
L'etichetta compilata deve essere attaccata accanto alla porta di
caricamento del prodotto (es. all'interno del coperchio con il valore
di arresto).
A contiene gas serra fluorinato, trattato nel Protocollo di Kyoto
Protocollo
B carico di refrigerante del prodotto inserito in fabbrica: vedere la
piastra con il nome dell'unità
C quantitativo aggiuntivo di refrigerante caricato sul campo
D carico di refrigerante totale
E unità esterna
F cilindro di refrigerante e collettore per la carica
Questo prodotto contiene gas serra fluorinato,
trattato nel Protocollo di Kyoto
Haier Industrial Park, N.1 Haier Road, Qingdao, Repubblica Popolare Cinese
F
A
C
E
D
A
F
C
E
D
G
B
G
4
Illustrazione installazione dell'unità esterna/interna
I modelli adottano il refrigerante R410A senza HFC.
Per l'installazione delle unità interne, fare riferimento al manuale di installazione fornito con le unità.
(Lo schema rappresenta un'unità interna montata a muro.)
Le immagini di unità esterne e interne sono solo per riferimento.
Attenersi al prodotto acquistato.
USCITA DELL'ARIA
PRESA D'ARIA
CONNESSIONE DELLE TUBAZIONI E DEI CAVI
ELETTRICI
TUBO FLESSIBILE DI DRENAGGIO
più di 15 cm
Deve essere prestata
attenzione al sollevamento
del tubo flessibile di scarico
Disposizione della dire-
zione delle tubature
Sinistra
Posteriore
sinistra
Posterio-
re destra
Destra
Inferiore
più di 10 cm
più di 10 cm
più di 20 cm
più di 60 cm
Fissaggio dell’unità esterna
Fissare l’unità alla pavimentazione
o al blocco di cemento stringen-
do bene dadi e bulloni (10mm) e
accertarsi che l’unità sia a livello
orizzontale.
Quando si installa l’unità su pareti,
tetti o tettoie, fissare in sicurezza
un supporto usando chiodi o cavi
tenendo in considerazione terre-
moti e venti forti.
Se la vibrazione potrebbe avere
un'influenza sulla casa, fissare l’
unità usando un pannello antivi-
brazione.
I simboli da
A
a
G
nelle
immagini sono i numeri
delle parti.
La distanza tra l’unità in-
terna e il pavimento deve
essere superiore ai 2 m.
Parti optional per le tubature
Nastro non adesivo
Nastro adesivo
Supporto (L.S) con viti
Collegamento del cavo elettrico per
interno ed esterno
Tubo flessibile di scarico
Materiale isolante termico
Coperchio foro tubatura
più di 20 cm
più di 25 cm
Compressore (all'interno dell'unità)
29
Norme di sicurezza
Leggere attentamente queste informazioni per il corretto funzionamento del condizionatore.
Di seguito, sono elencati tre tipi di norme di sicurezza e suggerimenti.
AVVERTENZA Operazioni non corrette potrebbero avere conseguenze gravi come morte o gravi ferite.
ATTENZIONE Operazioni non corrette potrebbero causare danni al condizionatore; in alcuni casi si potrebbe-
ro avere conseguenze gravi.
ISTRUZIONI: Queste informazioni assicurano il corretto funzionamento del condizionatore.
Simboli utilizzati nelle illustrazioni
: indica che l'azione deve essere evitata.
: indica che un'istruzione importante deve essere seguita.
: indica una parte che deve essere messa a terra.
: fare attenzione alle scosse elettriche (questo simbolo viene visualizzato sull'etichetta principale dell'unità.)
Dopo aver letto questo manuale, assicurarsi di farlo leggere anche a coloro che utilizzeranno l'unità.
Gli utenti dell'unità dovrebbero conservare il manuale a portata di mano e renderlo disponibile per coloro che effettueranno riparazioni o
spostamenti dell'unità. Inoltre, nel caso in cui ci sia un cambio di proprietà, rendere disponibile il manuale per il nuovo utente.
Assicurarsi di seguire queste importanti precauzioni di sicurezza.
AVVERTENZA
Nel momento in cui venga rilevato qualsiasi
fenomeno anomalo (p.e. odore di bruciato),
interrompere immediatamente l'erogazione
di corrente e contattare il fornitore per cono-
scere il modo in cui affrontare il problema.
In tal caso, continuare a utilizzare il condizionatore potrebbe
causare danni e generare il rischio di folgorazione e di incendio.
Dopo un lungo periodo di utilizzo del condi-
zionatore, è necessario controllare la base
per controllare la presenza di danni
Se la base danneggiata non viene riparata,
l'unità rischia di cadere e causare incidenti.
● Non smontare la bocchetta di uscita
dell'unità interna.
L'esposizione del ventilatore è molto peri-
colosa poichè potrebbe ferire le persone.
In caso di necessità di manutenzione e
riparazioni, contattare il fornitore affinchè
se ne occupi.
Una manutenzione e una riparazione
scorrette potrebbero causare perdite d'ac-
qua, rischio di folgorazione e di incendio.
Spegnere
AVVERTENZA
Sopra l'unità esterna non deve essere po-
sizionato alcun oggetto e non deve esserci
nessuna persona. La caduta di persone e
oggetti potrebbe causare incidenti.
Non utilizzare il condizionatore con le mani
umide. Rischio di scossa elettrica.
Utilizzare solo fusibili della tipologia corretta.
Non utilizzare cavi e nessun altro materiale
per sostituire i fusibili poichè potrebbero cau-
sare incendi o incidenti.
Utilizzare il tubo di scarico in modo corretto
per assicurare uno scarico funzionale.
Un uso scorretto delle tubature potrebbe cau-
sare perdite d'acqua.
Interruttore differenziale installato per proteggere da eventuali
dispersioni elettriche.
Vi è il rischio di folgorazione elettrica in caso di assenza di inter-
ruttore differenziale.
● Il condizionatore non deve essere installato in ambientei in cui
siano presenti gas infiammabili poiché potrebbero generarsi
incendi.
Il rivenditore deve occuparsi dell'installazione del condizionatore.
Un'installazione scorretta può causare perdite d'acqua, rischio di
folgorazione e incendio.
● Rivolgersi al rivenditore per eseguire le azioni necessarie ad
impedire la perdita di refrigerante.
Se il condizionatore viene installato in un ambiente piccolo, assi-
curarsi di eseguire tutte le azioni necessarie per evitare incidenti
di soffocamento anche nel caso in cui ci sia una perdita di refri-
gerante.
Quando il condizionatore viene installato o installato nuovamen-
te, deve occuparsene il rivenditore.
Un'installazione scorretta potrebbe causare perdite d'acqua,
rischio di folgorazione e incendio.
Collegamento del cavo per la messa a terra.
Il cavo per la messa a terra non deve essere connesso
al tubo del gas, al tubo dell'acqua o al parafulmine, una
messa a terra scorretta potrebbe causare folgorazione.
Messa a
terra
30
Norme di sicurezza
AVVERTENZA
Assicurarsi che l'unità venga installata da professionisti.
Un'installazione scorretta eseguita da una persona non qualifi
-
cata potrebbe causare perdite d'acqua, rischio di folgorazione e
incendio.
Posizionare l'unità su una superficie piana e stabile che possa
sorreggere il peso dell'unità per evitare che l'unità si ribalti o cada
causando incidenti.
Utilizzare soltanto cavi specifici per il cablaggio. Collegare corret
-
tamente ogni cavo, e assicurarsi che i cavi non forzino i terminali.
I cavi collegati in modo non corretto potrebbero generare calore
e rischio di incendio.
Adottare le precauzioni necessarie contro tifoni e terremoti per
evitare la caduta del condizionatore.
Non effettuare modifiche e cambiamenti al condizionatore. In
caso di problemi, consultare il rivenditore.
Se le riparazioni non vengono eseguite nella maniera corretta,
potrebbero presentarsi perdite d'acqua, rischio di folgorazione
oppure potrebbe venir prodotto fumo e generati incendi.
Accertarsi di seguire attentamente tutte le fasi del manuale du-
rante l'installazione dell'unità.
Un'installazione scorretta potrebbe causare perdite d'acqua,
rischio di folgorazione, fumo o incendi.
Assicurarsi che tutti i lavori di tipo elettrico vengano eseguiti da
un elettricista con regolare licenza secondo i regolamenti locali e
le istruzioni fornite in questo manuale. Utilizzare un circuito appo-
sito per l'unità.
Un'installazione scorretta o una mancanza di capacità dei circuiti
potrebbe causare un malfunzionamento dell'unità o generare il
rischio di folgorazione, fumo e incendi.
Fissare correttamente il coperchio del terminale (pannello) sul
-
l'unità.
Se l'installazione non viene eseguita correttamente, la polvere o
l'acqua potrebbero entrare nell'unità e generare il rischio di folgo-
razione, fumo o incendi.
Utilizzare soltanto il refrigerante R410A come indicato sull'unità
durante l'installazione o lo spostamento della stessa.
L'utilizzo di qualsiasi altro refrigerante o l'introduzione di aria nei
circuiti dell'unità potrebbe comportare un ciclo di lavoro anomalo
generando il rischio di esplosione dell'unità.
AVVERTENZA
Non toccare le alette sullo scambiatore di calore a mani nude
poichè queste sono affilate e pericolose.
Nel caso di perdita di refrigerante, fare in mdo che l'ambiente sia
ventilato in maniera adeguata.
Se il gas del refrigerante che fuoriesce viene esposto a fonti di
calore, potrebbero generarsi gas nocivi.
Con tutte le tipologie di
condizionatori ad aria fresca, l'aria ester-
na potrebbe venir soffiata direttamente nell'ambiente al disinseri
-
mento del termostato. Questo va tenuto in considerazione duran-
te l'installazione dell'unità.
L'
esposizione diretta all'aria esterna potrebbe causare pericolo
per la salute e potrebbe far guastare il cibo.
Non cercare di aggirare le misure di sicurezza del dispositivo e
non modificare le impostazioni.
La manomissione delle misure di sicurezza dell'unità ad esempio
il pressostato e l'interruttore della temperatura oppure l'utilizzo
di parti che non provengano dal rivenditore o da uno specialista
potrebbero causare incendi ed esplosioni.
Durante l'installazione dell'unità in un ambiente piccolo, eseguire
tutte le operazioni necessarie per proteggersi dall'ipossia che po-
trebbe essere causata dalla perdita di refrigerante che raggiunge
il livello massimo.
Rivolgersi al rivenditore per eseguire quanto necessario.
Quando il condizionatore viene riposizionato, consultare il riven
-
ditore o uno specialista.
Un'installazione scorretta potrebbe causare perdite d'acqua,
rischio di folgorazione o incendi.
Dopo aver completato il lavoro di manutenzione, controllare
eventuali perdite di gas refrigerante.
Se il gas refrigerante è esposto a una fonte di calore come un
ventilatore per il rscaldamento, a una stufa o a un grill elettrico,
potrebbero generarsi gas nocivi.
Utilizzare solo parti specifiche.
Assicurarsi che l'unità venga installata da professionisti. Un'in
-
stallazione scorretta potrebbe causare perdite d'acqua, rischio di
folgorazione, fumo o incendi.
31
Norme di sicurezza
Precauzioni per maneggiare le unità che utilizzano R410A
Attenzione
Non utilizzare vecchie tubature refrigeranti
Il refrigerante e l'olio refrigerante vecchi nelle tubature contengo
una grande quantità di clorina, che potrebbe causare il degrado
dell'olio refrigerante nella nuova unità.
L'R410A è un refrigerante ad alta pressione e l'utilizzo di tubature
vecchie potrebbe generare il rischio di esplosione.
Mantenere le superfici interne ed esterne delle tubature pulite e pri-
ve di contaminati come zolfo, ossidi, particelle di sporco e polvere,
olii e umidità.
Gli agenti contaminanti che si trovano nelle tubature refrigeranti
potrebbero causare il degrado dell'olio refrigerante.
Utilizzare una pompa a vuoto con un valvola di controllo a flusso
inverso.
Se vengono utilizzati altri tipi di valvole, l'olio della pompa a vuoto
penetrerà nel ciclo del refrigerante e causerà il degrado dell'olio
refrigerante.
Non utilizzare i seguenti strumenti usati in precedenza con refrige-
ranti convenzionali. Preparare degli strumenti per l'uso esclusivo
dell'R410A.
(Collettore
manometro, tubo flessibile di carico, rilevatore di per-
dite
di gas, valvola di controllo a flusso inverso, base di carico per
il refrigerante, vacuometro ed equipaggiamento per il recupero di
refrigerante.)
Se il refrigerante e/o l'olio refrigerante lasciato su questi stru-
menti si mescola con l'R410, oppure se l'acqua si mescola con
l'R410A, il refrigerante subirà un processo di degrado.
Poiché l'R410A non contiene cloro, i rilevatori di perdite di gas
per refrigeranti convenzionali non funzioneranno.
Attenzione
Riporre al chiuso le tubature da utilizzare durante l'installazione, e
tenere
entrambe le estremità sigillate fino al momento della brasa-
tura. (tenere i gomiti e le altre connessioni avvolte nella plastica.)
Se la polvere, lo sporco o l'acqua penetrano nel ciclo del refrige-
rante, potrebbero causare il degrado dell'olio nell'unità oppure
causare il malfunzionamento del compressore.
Utilizzare una piccola quantità di olio a base di estere o etere, op-
pure alchilbenzene per applicare uno strato protettivo su tutti i punti
di
connessione delle flange e dei fori svasati.
Una grande quantità di olio minerale potrebbe causare il degrado
dell'olio della macchina refrigerante.
Utilizzare
liquido refrigerante per caricare il sistema.
Caricare l'unità con il gas refrigerante comporta la modifica della
composizione del refrigerante ne cilindro causando un abbassa-
mento della qualità delle prestazioni
Non utilizzare una bombola di carico.
L'utilizzo di una bombola di carico modificherà la composizione
del refrigerante causando una perdita di potenza.
Utilizzare gli strumenti con estrema cautela.
Nel caso in cui elementi esterni come polvere, sporco o acqua
penetrino nel ciclo del refrigerante potrebbe verificarsi il degrado
dell'olio della macchina refrigerante.
Utilizzare soltanto refrigerante R410A.
L'utilizzo di refrigeranti contenenti cloro (per esempio R22) causa
il degrado del refrigerante.
Prima di installare l'unità
Attenzione
Non installare l'unità in un luogo in cui c'è il rischio di perdite di gas
infiammabile.
Il gas disperso accumulato attorno all'unità potrebbe generare un
incendio.
Non utilizzare l'unità per conservare cibi, animali, piante, artefatti o
per altri scopi particolari.
L'unità non è designata per offrire condizioni adeguate per il
mantenimento della qualità di questi oggetti.
Non utilizzare l'unità in ambienti non comuni
L'utilizzo dell'unità in presenza di una grande quantità di olio, vapo-
re, acido, solventi alcalini o particolari tipi di spray potrebbe causa-
re un notevole abbassamento delle prestazioni e/o un malfunzio-
namento comportando il rischio di folgorazione, fumo o incendi.
La presenza di solventi organici, gas corrosi (come ammoniaca,
composti di zolfo e acidi) potrebbe causare perdite di gas o acqua.
Se l'unità viene installata in un ospedale, eseguire le azioni neces-
sarie contro il rumore.
La strumentazione medica ad alta frequenza potrebbe interferire
con il normale funzionamento del condizionatore o dell'equipag-
giamento medico
Non posizionare l'unità al di sopra o al di sotto di oggetti che non
devono essere bagnati.
Quando il livello di umidità supera l'80% o quando il sistema di
drenaggio è otturato, dall'unità interna potrebbe gocciolare acqua.
Per evitare il gocciolamento delle unità esterne, si dovrebbe te-
nere in considerazione l'installazione di un sistema di drenaggio
centralizzato.
32
Norme di sicurezza
Prima di installare (riposizionare) l'unità o prima di eseguire lavori elettrici
Attenzione
Eseguire la messa a terra l'unità.
Non collegare la messa a terra dell'unità ai tubi del gas, ai tubi
dell'acqua, ai parafulmini o ai terminali della messa a terra dei
telefoni. Una messa a terra non corretta comporta il rischio di
folgorazione, fumo, incendio, oppure il rumore generato dalla
scorretta messa a terra potrebbe causare il malfunzionamento
dell'unità.
Accertarsi che i cavi non siano soggetti a tensione.
Se i cavi sono troppo tesi, potrebbero rompersi o generare calore
e/o fumo e incendi.
Installare un interruttore differenziale per la dispersione di corrente
alla sorgente della corrente elettrica per evitare il rischio di folgora-
zione.
In assenza dell'interruttore differenziale per la dispersione di
corrente, si corre il rischio di folgorazione, fumo o incendio.
Utilizzare interruttori e fusibili (interruttori differenziale per la corren-
te elettrica e fusibili, interruttore remoto<interruttore+fusibile di tipo
B>, interruttori differenziali di corrente scatolati) con una capacità di
corrente appropriata.
L'utilizzo di fusibili ad alta capacità, cavi di ferro, o cavi di rame
potrebbe danneggiare l'unità o generare fumo o incendi.
Non spruzzare acuqa sui condizionatori o immergerli nell'acqua.
L'acqua sull'unità comporta il rischio di folgorazione.
Controllare periodicamente la piattaforma sulla quale è posizionata
l'unità in caso di danneggiamento
per evitare la caduta dell'unità.
Se l'unità viene lasciata su una piattaforma danneggiata, potreb
-
be ribaltarsi causando danni.
Durante l'installazione delle tubature di drenaggio, seguire le istru-
zioni nel manuale e assicurarsi che questi drenino correttamente
l'acqua per evitare la formazione di condensa di rugiada.
Se le tubature non vengono installate correttamente, potrebbero
causare perdite d'acqua e danneggiare l'arredamento.
Smaltire correttamente i materiali dell'involucro.
Nella scatola potrebbero essere inclusi elementi come chiodi.
Smaltirli correttamente per evitare lesioni.
Le buste di plastica rappresentano un pericolo di soffocamento
per i bambini. Strappare la buste di plastica prima di smaltirle per
prevenire eventuali incidenti.
Prima del collaudo di avvio
Attenzione
Non premere gli interruttori con le mani bagnate per evitare il ri-
schio di folgorazione.
Non toccare le tubature refrigeranti a mani nude durante e imme-
diatamente dopo il funzionamento.
Secondo lo stato del refrigerante nel sistema, alcune parti del
-
l'unità come le tubature e il compressore potrebbero divenire
molto fredde o calde e causare congelamento o ustioni.
Non utilizzare l'unità se i pannelli o le griglie di sicurezza non siano
in posizione corretta.
La loro presenza previene il rischio di lesioni dell'utente che altri
-
menti potrebbe toccare parti rotanti, o parti ad alta temperatura o
alto voltaggio.
Non spegnere subito dopo aver fermato l'unità.
Prima di spegnere completamente l'unità aspettare almeno
cinque minuti, altrimenti potrebbero verificarsi perdite d'acqua
dall'unità e altri problemi.
Non utilizzare l'unità senza filtri d'aria.
Particelle di polvere nell'aria potrebbero otturare il sistema e cau-
sare malfunzionamento.
33
Leggere prima dell'installazione
Elementi da controllare
(1). Verificare il tipo di refrigerante utilizzato dall'unità su cui deve essere effettuata la manutenzione. Tipo di refrigerante: R410A
(2). Controllare i sintomi mostrati dall'unità su cui deve essere effettuata la manutenzione. Cercare nella guida i
sintomi relativi al ciclo del
refrigerante.
(3). Assicurarsi di leggere con attenzione le precauzioni di sicurezza che si trovano all'inizio di questo documento.
(4). Nel caso di perdita di gas o se il refrigerante residuo è esposto a una fiamma viva, si può produrre un gas nocivo acido fluoridrico. Il
luogo di lavoro deve essere ben ventilato.
AVVERTENZA
Installare nuove tubature subito dopo aver rimosso quelle vecchie per evitare la formazione di umidità sul circuito refrigerante.
La presenza di cloro in alcuni refrigeranti come l'R22 può causare il degrado dell'olio della macchina refrigerante.
Strumenti e materiali necessari
Preparare i seguenti strumenti e materiali necessari per l'installazione e la manutenzione dell'unità.
Strumenti necessari da utilizzare per l'R410A (adattabilità degli strumenti utilizzabili con R22 e R407C).
1. Da utilizzare esclusivamente con l'R410A ( da non utilizzare con l'R22 o l'R407C )
Strumenti/materiali Utilizzo Note
Collettore manometro Consente di eseguire l'evacuazione, e il
caricamento del refrigerante
5.09 MPa sul lato ad alta pressione
Tubo flessibile di carico Permette di eseguire l'evacuazione, e il
caricamento del refrigerante
Diametro del tubo flessibile maggiore di quello dei tubi convenzionali.
Equipaggiamento per il recupero del re-
frigerante
Consente di recuperare il refrigerante
Cilindro refrigerante Consente il caricamento del refrigerante Annotare il tipo di refrigerante. La parte superiore del cilindro è di colore rosa.
Porta di caricamento del cilindro refrige-
rante
Consente il caricamento del refrigerante Diametro del tubo flessibile maggiore di quello dei tubi convenzionali.
Bullone foro svasamento Consente di collegare l'unità alle tubature Utilizzare bulloni per i fori di svasamento di tipo due.
2. Strumenti e i materiali che possono essere utilizzati con l'R410 con alcune restrizioni
Strumenti/materiali Utilizzo Note
Rilevatore di perdite di gas Consente di rilevare perdite di gas È possibile utilizzare il rilevatore per gas di tipo HFC.
Pompa a vuoto Consente di eseguire l'asciugatura sotto
vuoto
Potrebbe essere utilizzata nel caso in cui sia montato un adattatore di controlo a flusso
inverso.
Strumento foro di svasamento Svasatura delle tubature Sono stati apportati dei cambiamenti alle dimensioni della svasatura. Fare riferimento alla
pagina successiva.
Equipaggiamento per il recupero del re-
frigerante
Consente il recupero del refrigerante Potrebbe essere utilizzato se progettato per essere utilizzato con l'R410A.
3. Strumenti e materiali utilizzati perl'R22 o R407C che possono essere utilizzati anche con l'R410A
Strumenti/materiali Utilizzo Note
Pompa del vuoto con valvola di controllo Consente di eseguire l'asciugatura sotto
vuoto
Piegatubi Consente di piegare i tubi
Chiave dinamometrica Consente di stringere i bulloni dei fori di
svasamento
Soltanto
12,70 (1/2'') e 15,88(5/8'') hanno una dimensione maggiore della svasatura.
Tagliatubi Consente di tagliare i tubi
Saldatore e cilindro ad azoto Consente di saldare le tubature
Misuratore di carica del refrigerante Consente il caricamento del refrigerante
Vacuometro Consente di controllare il vuoto
4. Strumenti e materiali che non devono essere utilizzati con l'R410A
Strumenti/materiali Utilizzo Note
Bombola di carico Consente di caricare il refrigerante Non deve essere utilizzato con le unità di tipo R410.
Strumenti per l'R410A devono essere maneggiate con estrema attenzione, evitando di far entrare in circolo la polvere e l'umidità.
34
Leggere prima dell'installazione
Materiali per le tubature
Tipi di tubi in rame (riferimento)
Massima pressione di funzionamento Refrigeranti applicabili
3,4 MPa R22, R407C
4,15 MPa R410A
Utilizzare tubature che rispettino gli standard locali.
Materiali tubature/Spessore radiale
Utilizzare tubature in rame di fosforo disossidato.
Poichè la pressione di attività delle unità che utilizzano l'R410A è più elevata di quella delle unità con l'R22, utilizzare tubature con uno
spessore radiale che sia specificato nel grafico sottostante. (Tubature con uno spessore radiali di 0.7 mm o inferiore non devono essere
usate.)
Dimensione (mm) Dimensione (pollici) Spessore radiale (mm) Tipo
6.35 1/4'' 0,8t
Tubature di tipo O
9.52 3/8" 0,8t
12.7 1/2" 0,8t
15.88 5/8" 1,0 t
19.05 3/4" 1,0 t Tipo-1/2H o tubazioni H
Nonostante sia stato possibile utilizzare tubature di tipo O per una dimensione che arrivi fino a 19,05 (3/4") con refrigeranti convenzio-
nali, utilizzare tubature H di tipo 1/2H per unità che utilizzano l'R410A. (Tubature di tipo O possono essere utilizzate se la dimensione
della tubatura è 19,05 e lo spessore radiale è 1,2 t.)
La tabella
mostra gli standard giapponesi. Utilizzare questa tabella come riferimento, scegliere tubature che corrispondono agli standard
locali.
Svasatura (tipo O e topo OL)
Le dimensioni della svasatura per le unità che utilizzano l'R410A sono maggiori di quelle delle unità che utilizzano l'R22 per migliorare la
tenuta.
Dimensione della svasatura(mm)
Dimensione esterna delle
tubature
Dimensioni
Dimensione A
R410A R22
6.35 1/4'' 9.1 9.0
9.52 3/8" 13.2 13.0
12.7 1/2" 16.6 16.2
15.88 5/8" 19.7 19.4
19.05 3/4" 24.0 23.3
Se viene utilizzato un tipo di foro di svasamento a frizione con le machine flares sulle unità che utilizzano l'R410A, la parte del tubo che
fuoriesce deve avere una lunghezza da 1,0 e 1,5mm. Un tubo di calibro in rame può risultare utile per regolare la lunghezza del tubo che
sporge.
Bullone foro svasamento
Per aumentare la forza vengono utilzzati bulloni svasati di tipo 2 invece che di tipo 1. La dimensione dei bulloni foro svasati è stata cam-
biata.
Dimensione bullone foro svasato (mm)
Dimensione esterna delle
tubature
Dimensioni
Dimensione B
R410A (Tipo 2) R22 (Tipo 1)
6.35 1/4'' 17.0 17.0
9.52 3/8" 22.0 22.0
12.7 1/2" 26.0 24.0
15.88 5/8" 29.0 27.0
19.05 3/4" 36.0 36.0
La tabella mostra gli standard giapponesi. Utilizzare questa tabella come riferimento, scegliere tubature che corrispondono agli stan-
dard locali.
Dimensione A
Dimensione B
35
Leggere prima dell'installazione
Collaudo della tenuta
NESSUN cambiamento rispetto al metodo convenzionale. Fare attenzione poichè un rilevatore di perdita di refrigerante per l'R22 o
l'R407C non può rivelare perdite di R410A.
Oggetti da osservare attentamente:
1. Mettere sotto pressione l'apparecchiatura con l'azoto fino al raggiungimento della pressione designata quindi considerare la tenuta
dell'equipaggiamento, tenere in considerazione le variazioni di temperatura.
2. Quando si ricercano le zone di perdita utilizzando un refrigerante, assicurarsi di utilizzare l'R410A.
3. Assicurarsi che l'R410A sia allo stato liquido quando viene caricato.
Motivazioni:
1. L'utilizzo dell'ossigeno come gas pressurizzato potrebbe causare un'esplosione.
2. Un caricamento di gas R410A causerà la modifica della composizione del refrigerante residuo nel cilindro impedendo l'utilizzo di
questo refrigerante.
Svuotamento
1. Pompa del vuoto con valvola di controllo
È necessaria una pompa del vuoto con valvola di controllo per evitare che l'olio della pompa a vuoto penetri nel circuito refrigerante
quando la pompa del vuoto è spenta (o nel caso in cui si verifichi un black out). In seguito sarà inoltre possibile collegare una valvola
di
controllo alla pompa del vuoto.
2. Vuoto standard della pompa del vuoto
Utilizzare una pompa che raggiunge i 65 Pa o inferiore dopo 5 minuti di funzionamento.
Inoltre, assicurarsi di utilizzare una pompa a vuoto che sia stata mantenuta correttamente e oliata utilizzando l'olio specifico. Se la
pompa del vuoto non è stata mantenuta correttamente, il grado di vuoto potrebbe essere troppo basso.
3. Precisione richiesta per il vacuometro
Utilizzare un vacuometro che possa misurare fino a 650 Pa. Non utilizzare un manometro generale poichè non può misurare un
vuoto di 650 Pa.
4. Tempo di svuotamento
Svuotare l'apparecchiatura per 1 ora dopo aver raggiunto i 650 Pa.
Dopo lo svuotamento, tenere ferma l'apparecchiatura per 1 ora e assicurarsi che il vuoto si conserva.
5. Procedura di funzionamento quando la pompa del vuoto è spenta
Per prevenire un riflusso dell'olio della pompa a vuoto, aprire la valvola di scarico sul lato della pompa a vuoto oppure allentare la
tuba
tura di scarico flessibile per tirare su aria prima di fermare l'operazione. La stessa procedura operativa deve essere eseguita
quando si
utilizza una pompa a vuoto con una valvola di controllo.
Caricamento del refrigerante
L'R410A deve trovarsi allo stato liquido quando viene caricato.
Motivazioni:
L'R410A è un refrigerante pseudo azeotropico (punto d'ebollizione R32= -52
°C, R125= -49°C) e difficilmente può essere maneggiato
allostesso modo dell'R22; comunque, assicurarsi di riempire il refrigerante dalla parte del liquido, poichè fare ciò dalla parte del gas
comporterà in qualche modo la modifica della composizione del refrigerante nel cilindro.
Nota
Nel caso di un cilindro con un sifone, il liquido R410A viene caricato senza capovolgere
il cilindro. Controllare il tipo di cilindro prima
di caricarlo.
Rimedi nel caso di perdita di refrigerante
In caso di perdita di refrigerante, deve essere caricato del refrigerante aggiuntivo. (Aggiungere il refrigerante dalla parte del liquido)
Caratteristiche dei refrigeranti nuovi e convenzionali
Poichè l'R410A è un refrigerante azeotropico simulato, può essere maneggiato allo stesso modo di un singolo refrigerante come
l'R22.In ogni caso, se il refrigerante viene rimosso durante lo stato di vapore, la composizione del refrigerante nel cilindro potrebbe
cambiare.
Rimuovere il refrigerante allo stato liquido. In caso di perdita di refrigerante può essere aggiunto refrigerante aggiuntivo.
Torcia alogenura
Rilevatore di perdita di R22 o R407C
36
Processo di installazione
Installazione dell’unità esterna
gomma
1. Accessori
“Bordatura” per proteggere i cavi elettrici da spigoli vivi.
2. Selezione del luogo di installazione
Selezionare la posizione per un'installazione che soddisfi le seguenti condizioni e, allo stesso tempo, ottenere il consenso dell'utente o del
cliente.
Una posizione in cui circola l'aria.
Una posizione lontana da radiazioni di calore proveniente da altre fonti di calore.
Una posizione dalla quale sia facile scaricare l'acqua drenata.
Una posizione nella quale il rumore e l'aria calda non disturbino i vicini.
Una posizione dove, durante l'inverno, non ci siano abbondanti nevicate.
Una posizione dove non ci siano ostacoli vicini alla presa d'aria o allo scarico dell'aria.
Una posizione dove la presa d'aria non è esposta a forte vento.
Una posizione circondata su tutti e 4 i lati non è ideale per l'installazione. È necessario uno spazio di 1 m o maggiore sopra al condizio
-
natore.
Evitare di montare le griglie in una posizione in cui possano avvenire corto circuiti.
Durante l'installazione di diverse unità, assicurarsi che sia presente abbastanza spazio di aspirazione per evitare corto circuiti.
Requisiti dello spazio aperto intorno all'unità
3. Installazione dell'unità esterna
Fissare l'unità alle fondamenta in maniera corretta secondo le condizioni del
luogo di installazione, facendo riferimento alle seguenti informazioni.
Lasciare abbastanza spazio sul cemento delle fondamenta per fissare i dadi
di ancoraggio.
Una posizione in cui il cemento delle fondamenta sia abbastanza profondo.
Installare l'unità in modo tale che l'angolo di inclinazione sia inferiore ai 3
gradi.
Non posizionare l'unità direttamente a terra. Confermare che ci sia abba
-
stanza spazio accanto al foro di drenaggio nella parte bassa, così da assi-
curare che l'acqua venga drenata senza problemi.
4. Dimensioni di installazione (unità: mm)
(Spazio ma-
nutenzione)
Presa d'aria
Presa d'aria
Bocchetta di
uscita dell'aria
Distanza Caso I Caso II Caso III
L1 aprire aprire 500 mm
L2 300 mm 300 mm aprire
L3 150 mm 300 mm 150 mm
Nota:
(1) Fissare le parti con le viti.
(2) Evitare che il vento forte entri
direttamente nel foro di uscita
del flusso d'aria.
(3) È necessario un metro di di-
stanza dalla parte superiore dell'unità.
(4) Non bloccare l'area intorno all'unità.
(5) Se l'unità è stata installata in una posizione esposta al ven-
to, installare l'unità in modo che la griglia di uscita NON sia
rivolta verso la direzione del vento forte.
NO
Direzione del vento
Bocchetta
di uscita
dell'aria
Bullone di ancoraggio
Unità
Cuscinetto in
Base in cemento
Foro di distribu-
zione del cablag-
gio dell'alimenta-
zione elettrica
Terminale del
cablaggio del-
l'alimentazione
elettrica
Modello W D H L1 L2 L3
1U07BS1ERA 780 245 540 500 140 256
1U09BS1ERA 780 245 540 500 140 256
1U12BS1ERA 780 245 540 500 140 256
1U18FS1ERA 810 288 688 583 113.5 319.5
1U24GS1ERA 860 308 730 633 113.5 340
Bordatura
37
Processo di installazione
Collegamento delle tubature
1. Dimensione delle tubature
1U07BS1ERA 1U09BS1ERA
1U12BS1ERA
Tubo per liquidi
6,35x0,8 mm
Tubo per gas
9,52x0,8 mm
1U18FS1ERA
Tubo per liquidi
6,35x0,8 mm
Tubo per gas
12,7x0,8 mm
1U24GS1ERA
Tubo per liquidi
9,52x0,8 mm
Tubo per gas
15,88x1,0 mm
2
. Collegamento dei tubi
Per piegare un tubo, curvarlo con un raggio molto ampio per non spaccarli, il raggio deve essere compreso tra
30 e 40 mm o più.
Collegare prima le tubature del lato del gas poiché renderà il lavoro più semplice.
Il tubo di collegamento è apposito per R410A.
Prestare attenzione poiché materiali come scarti di sabbia, acqua ecc. non entrino nel tubo.
AVVERTENZA
La lunghezza standard delle tubature è di C m. Se è superiore a D m, il funzionamento del'unità potrebbe
non risultare corretto. Se il tubo deve essere allungato, deve essere caricato il refrigerante, in base a E g/m.
Tuttavia, il caricamento del refrigerante deve essere eseguito da personale professionista. Prima di aggiungere
gerante, eseguire lo sfiato dell’aria dalle tubature del refrigerante e dall’unità interna usando una
pompa a vuoto,
poi caricare il refrigerante.
Installare i dadi svasati rimossi dalle tubature
per collegarle, quindi svasare le tubature.
Un serraggio eccessivo senza eseguire una
centratura accurata può danneggiare le filettature e
provocare perdite di gas.
Unione di mezzo Dado svasato
Chiave per bulloni Chiave dinamo-
metrica
Diametro del tubo (ǿ) Coppia di serraggio
Lato liquidi 6,35 mm (1/4") 18 N.m
Lato liquidi/gas 9,52 mm (3/8") 42 N.m
Lato gas 12,7mm (1/2") 55 N.m
Lato gas 15,88 mm (5/8") 60 N.m
A
B
A
B
A
B
unità esterna
Unità
interna
Unità interna
unità esterna
unità esterna
Unità
interna
Trappola per
l’olio
Elevazione massima: A massimo
Se l’altezza A è superiore ai 5 m, un
raccoglitore dell’olio deve essere
installato ogni 5~7m
Lunghezza massima: B massimo
Se la lunghezza B delle tubature è
maggiore di D m, il refrigerante deve
essere caricato in base a E g/m.
Unità esterna A mas-
simo
B mas-
simo
CDE
1U07BS1ERA 10 15 5 7 20
1U09BS1ERA 10 15 5 7 20
1U12BS1ERA 10 15 5 7 20
1U18BS1ERA 15 25 5 7 20
1U24BS1ERA 15 25 5 7 45
altro refri
38
Processo di installazione
Collaudo della tenuta
Dopo aver collegato la tubatura refrigerante, è necessario eseguire un collaudo per verificarne la tenuta.
Il collaudo della tenuta dell'aria utilizza un serbatoio di azoto per produrre una pressione secondo la modalità di collega-
mento delle tubature come mostrato nella figura seguente.
La valvola del gas e del liquido sono tutte in stato di chiusura. Per prevenire l'entrata dell'azoto nel sistema di circolazione
dell'unità esterna, serrare la valvola ord?? prima di effettuare la pressione (entrambe le valvole del gas e del liquido ords).
1) Mettere sotto pressione per più di 3 minuti a 0,3 MPa
(3,0 kg/cm
2
g)
2) Mettere sotto pressione per più di 3 minuti a 1.5 MPa
(15 kg/cm
2
g). Verrà rilevata una forte perdita.
3) Mettere sotto pressione per 24 ore a 3,0 MPa (30 kg/
cm
2
g). Verrà rilevata una leggera perdita.
Controllare se la pressione diminuisce
Se la pressione non diminuisce, procedere.
Se la pressione diminuisce, cercare il punto di perdita.
Mettendo sotto pressione per 24 ore, la variazione di 1°C della temperatura dell'ambiente causerà una variazione di pressione pari a
0,01 MPa (0,1kg/cm2 g).
Dovrà essere corretto durante il collaudo.
Controllare il punto di perdita
Nelle fasi da 1) a 3), nel caso in cui avvenga una perdiata di pressione, controllare la perdita in ogni giuntura
ascoltando, toccando e
usando acqua saponata ecc.
per identificare il punto di perdita. Dopo aver individuato il punto di perdita, saldarlo nuovamente, oppure
serrare il bullone.
Interrompere le valvole completamente chiuse
Esterno
Interno
Completamente serrato
Parte svasata
Unità interna
Interrompere le valvole completamente chiuse
Completamente serrato
Valvola di scarico
Tombino
Unità esterne
Piezometro a bassa
pressione
Piezometro ad alta pressione
Separatore per contatore
Valvola di scari-
co
Serbatoio dell'azoto
Manutenzione del tubo
flessibile
Manometro di pressione di linea
Brasatura delle tubature
Giunto a gomito
Grande connettore di
inserimento
Cilindro di azoto
Manometro di pressione del cilindro
(lato del gas)
(lato del gas)
Parte svasata
39
Processo di installazione
Svuotamento
Metodo di svuotamento delle tubature: per usare una
pompa del vuoto
1. Staccare il coperchio della porta di servizio della valvola a 3 vie, il coperchio
della valvola a stelo della valvola a 2 vie e della valvola a stelo della valvola a 3
vie, collegare la porta di servizio nella protuberanza del tubo flessibile di carico
(basso) del gruppo monometrico. Poi collegare la protuberanza del tubo di carico
flessibile (centrale) alla pompa a vuoto.
2. a apmop al erarepo ,ocirtemonom oppurg led aloponam al ossab ollevil a erirpA
vuoto. Se l'indicatore (basso) raggiunge la condizione di vuoto immediatamente,
controllare di nuovo il punto 1.
3. eracidni eved e
hc erotacidni'l erallortnoC ,nim 51 id ùip rep otouvottos eraripsA
-0.1MPa (76 cm Hg) sul lato della bassa pressione. Dopo avere completato la
procedura di scarico, chiudere la manopola in posizione "Lo" del gruppo mano-
metrico ed arrestare il funzionamento della pompa a vuoto. Controlla le condizio-
ni della scala graduata e tenerla per 1-2 min. Se l’indicatore si sposta, malgrado
la chiusura, far funzionare di nuovo il degassamento e tornare al principio del
punto 3 .
4. na osnes ni idarg 09 id olod
narig
eiv 2 a alovlav alled olets a alovlav al erirpA -
tiorario. Dopo 6 secondi, chiudere la valvola a 2 vie ed eseguire un'ispezione per
accertarsi che non ci siano perdite di gas.
5. Non ci sono perdite di gas? Se ci sono perdite di gas, stringere i giunti del tubo. Se la perdita di arresta, procedere al punto 6. Se
la perdita non si arresta, scaricare tutto il refrigerante usando la porta di servizio. Dopo avere attivato di nuovo il degassamento
ed aspirato l'aria, riempire con refrigerante raccomandato usando la bombola del gas.
6. Staccare il tubo flessibile della ricarica dall'apertura di servizio, aprire la valvola a 2 vie e
e quella a 3 vie. Ruotare ila valvola a stelo in senso antiorario fino a serrarlo leggermente.
7. Per evitare le perdite di gas, ruotare il tappo della porta di servizio della valvola a 2 vie e
di quello della valvola a 3 vie un po' oltre il punto di serraggio, in cui la resistenza aumen-
ta immediatamente.
ATTENZIONE:
Se c'è una perdita di refrigerante del condizionatore, è necessario scaricare tutto il refrigerante. Per prima cosa aspirare, poi caricare il
refrigerante liquido nel condizionatore in base alla quantità indicata sull'etichetta.
Chiuso
Valvola a 2 vie
Valvola a 3 vie
Valvola a 2 vie
Valvola a 3 vie
Valvola a 2 vie
Valvola a 3 vie
Valvola di interruzione del liquido
Valvola di interruzione del gas
Collettore manometro (R410A)
Pompa del vuoto (R410A)
Aperto
Porta di servizio
90 per 6 secondi.
Valvola a 2 vie
Valvola a 3 vie
Valvola a 2 vie
Valvola a 3 vie
Coperchio porta di servizio
Coperchio valvola a stelo
Coperchio valvola a stelo
(p.e. 1U 18FS1ERA)
40
Processo di installazione
Cablaggio elettrico
AVVISO!
PERICOLO DI LESIONI O MORTE
DISATTIVARE LA CORRENTE ELETTRICA DALL'INTERRUTTORE DIFFERENZIALE O DALLA SORGENTE DI ALIMENTAZIONE
PRIMA DI ESEGUIRE QUALSIASI TIPO DI COLLEGAMENTO ELETTRICO.
METTERE A TERRA TUTTI I COLLEGAMENTI PRIMA DI ESEGUIRE COLLEGAMENTI A TENSIONE.
Precauzioni per il cablaggio elettrico
Il cablaggio elettrico dovrebbere essere eseguito soltanto da personale autorizzato.
Non collegare più di 3 cavi al blocco del terminale. Utilizzare sempre alette terminali ondulate di tipo rotondo con presa isolata alle estre-
mità dei cavi.
Utilizzare soltanto conduttori in rame.
Opzioni per le dimensioni dei cavi di collegamento e del cavo di alimentazione
Scegliere le dimensioni dei cavi e la protezione dei circuiti dalla tabella sottostante. (Questa tabella presenta cavi lunghi 20 m con una
perdita di voltaggio minore del 2%.)
Stato
Interruttore differenziale di corrente
Dimensione del
cavo di alimenta-
zione (minimo)
(
2
mm)
Interruttore di circuito con messa a
terra
Interruttore auto-
matico
(A)
Capacità nominale del
dispositivo di protezione del
sovraccarico di corrente (A)
Interruttore diffe-
renziale (A)
Corrente di di-
spersione (mA)
1U07BS1ERA
1U09BS1ERA
1U12BS1ERA
1U18BS1ERA
1 40 26 2.5 40 30
1U24GS1ERA 1 40 26 4.0 40 30
Se il cavo d'alimentazione è danneggiato, deve essere sostituito dal produttore, il suo rappresentante o persona similarmente qualificata.
Se il fusibile della scatola di controllo è rotto, modificarlo con uno di tipo T 25A/250V
Il metodo di cablaggio deve essere in linea con le normative di cablaggio locali.
Il cavo di alimentazione e i cavi di connessione devono essere forniti.
Tutti i cavi devono avere la Certificazione Europea di Autenticazione. Durante l'installazione, quando vengono interrotti i cavi di connes-
sione, assicurarsi che il cavo della messa a terra sia l'ultimo a venir interrotto.
'interruttore del condizionatore deve essere un interruttore di tutti i poli e la distanza fra i suoi due contatti non deve essere inferiore a
3mm. Questi metodi di scollegamento devono essere .
La distanza tra i suoi due blocchi terminali dell'unità interna e esterna non deve essere superiore ai 5 m. Se superiore, il diametro del
cavo deve essere aumentato secondo le normative di cablaggio locali.
Deve essere installato un interruttore di dispersione.
Procedura per il cablaggio
1) Rimuovere le viti che si trovano lateralmente prima di poter estrarre il pannello frontale.
2) Collegare i cavi al blocco terminale in maniera
corretta e fissarli con un morsetto equipaggiato accanto al blocco terminale.
3) Ruotare i cavi in maniera corretta e inserirli nell'apertura per eseguire il cablaggio
elettrico sul pannello laterale.
AVVISO:
I CAVI DI INTERCONNESSIONE DEVONO ESSERE CABLATI SECONDO LA FIGURA SOTTOSTANTE. UN CABLAGGIO NON COR-
RETTO POTREBBE CAUSARE DANNI ALL'APPARECCHIATURA.
Modello
Oggetto
3
2
1
)
(
N
)(
L
)(
C
3
2
1
)
(
N
)
(
L
)
(
C
N
(
1
3
)
)
C(L(
2
)
{
ALIMENTAZIONE
PER 07K 09K 12K
PER 18 K 24 K
Unità esterna
All'unità interna
ALIMENTAZIONE
Unità esterna
All'unità interna
Modello
1U07BS1ERA
1U09BS1ERA
1U12BS1ERA
1U18BS1ERA 1U24GS1ERA
Cavi di collegamento
4G 0,75 mm
2
4G 0,75 mm
2
4G 0,75 mm
2
Cavo di alimentazione 3G 1,5 mm
2
3G 2,5 mm
2
3G 1,5 mm
2
41
L
N
14
Haier Group
Indirizzo: N. 1 Haier Road, Hi-tech Zone, Qingdao 266101, Repubblica Popolare Cinese
Contatti: TEL +86-532-8893-6943; FAX +86-532-8893-1010
Sito Internet: www.haier.com
Risoluzione dei problemi dell'unità esterna
ATTENZIONE
QUEST'UNITÀ SI AVVIERÀ ISTANTANEAMENTE NEL MOMENTO IN CUI SARÀ FORNITA ENERGIA ELETTRICA SENZA BISOGNO
DI ACCENSIONE. ASSICURARSI DI ESEGUIRE L'OPERAZIONE DI SPEGNIMENTO PRIMA DI INTERROMPERE L'EROGAZIONE
DI ENERGIA ELETTRICA PER LA MANUTENZIONE.
Questa unità possiede una funzione di riavvio automatico dopo il recupero dopo l'interruzione dell'erogazione di energia elettrica.
1. Prima di eseguire il collaudo dell'avvio (per tutti i modelli con pompa di calore)
Assicurarsi che l'interruttore di corrente elettrica (interruttore principale) dell'unità sia stato attivo per più di 12 ore per fornire energia al
riscaldatore del basamento prima delle operazioni.
2. Collaudo di avvio
Avviare l'unità per 30 minuti senza interruzioni e controllare quanto segue.
Pressione di aspirazione nelle giunture di controllo per la valvola di servizio delle tubature del gas.
Scarico della pressione alla giunture di controllo nella tubatura di scarico del compressore.
Differenza di temperatura tra l'aria di ritorno e l'aria fornita all'unità interna.
Il tempo di lam-
peggiamento dei
LED sulla
sche-
da principale
Descrizione dei problemi Analisi e diagnosi
1 Errore EEPROM Errore EEPROM nella scheda principale
2 Errore IPM Errore IPM
4
Errore di comunicazione tra la scheda madre e le
comunicazioni del modulo SPDU
Errore di comunicazione per più di 4 min
5 Protezione alta pressione Alta pressione del sistema superiore ai
4,15 MPa
6
Dispositivo di protezione del sovraccarico di cor-
rente del modulo (solo per lo spud)
Dispositivo di protezione della mancanza di vol-
taggio del modulo (solo per lo spud)
Inviare dal modulo
8
Dispositivo di protezione della
temperatura di
scarico del compressore
Temperatura di scarico del compressore superiore ai 110°C
9 Anomalie nel motore CC Blocco del motore CC o errore nel motore
10 Anomalie nel sensore tubature Sensore tubature di corto circuito o circuito aperto
11 Errore nel sensore di temperatura di aspirazione
Quando il cablaggio del compressore è errato o il collegamento
non è corretto
12 Anomalia nel sensore dell'ambiente esterno Corto circuito o circuito aperto del sensore ambiente esterno
13 Anomalie nel sensore del compressore di scarico Corto circuito o circuito aperto del sensore di scarico
15
Errore di comunicazione tra l'unità interna e l'uni-
tà esterna
Errore di comunicazione per più di 4 min
16
Mancanza di refrigerante o controllo di eventuali
perdite nell'unità
Allarme e interruzione se rilevato TD-tci>=75 che duri per un mi-
nuto dopo che il compressore è stato attivo per 10 min in modali-
tà condizionatore, controllare eventuali perdite nell'unità.
17 Errore nella valvola inversa a 4 vie
Allarme e interruzione se rilevato Tm<=75 che duri per un
minuto dopo che il compressore è stato attivato per 10 min in
modalità condizionatore, controllare l'errore se appare 3 volte in
un'ora.
18 Blocco del compressore (solo per spud) Il compressore interno è bloccato in maniera anomala
19 Errore nella selezione del modulo circuito PWM Selezione del modulo PWM del circuito errata
25 Sovraccarico durante la fase U del compressore La corrente durante la fase U del compressore è troppo elevata
25 Sovraccarico durante la fase V del compressore La corrente durante la fase V del compressore è troppo elevata
25 Sovraccarico durante la fase W del compressore La corrente durante la fase W del compressore è troppo elevata
42
CONFORMITÉ DES MODÈLES
À LA LÉGISLATION EUROPÉENNE
CE
Tous les appareils sont conformes aux directives Européennes
suivantes :
- Directive basse tension 73/23/EEC
- Directive basse tension 2006/95/EC
- Compatibilité électro-magnétique Y 89/336/EEC
- Compatibilité électro-magnétique Y 2004/108/EC
ROHS
Les appareils répondent aux exigences de la directive 2002/95/
EEC du parlement européen et du conseil sur la limitation des
substances dangereuses dans les Équipements Électriques et
Électroniques (Directive UE RoHS).
WEEE
Conformément à la Directive 2002/96/CE du Parlement Européen,
nous informons ici-même le consommateur des conditions d'élimi-
nation des appareils électriques et électroniques.
CONDITIONS D'ÉLIMINATION
L'appareil de climatisation est marqué de ce
symbole. Ceci signifie que les produits élec-
triques et électroniques ne doivent pas être
mêlés aux déchets ménagers non-triés. Ne pas
tenter de démonter le système par soi-même
: le démontage du système de climatisation, le traitement
du liquide réfrigérant, de l'huile et d'autres pièces doivent
être effectués par un installateur qualifié conformément à la
législation locale et nationale. Les climatiseurs doivent être
traités dans des installations spécialisées pour réutilisation,
recyclage et récupération. S'assurer que le produit est élimi-
né de façon correcte permet d'aider à éviter des conséquen-
ces potentielles négatives sur l'environnement et la santé
humaine. Merci de contacter l'installateur ou les autorités
locales pour plus d'information. Les piles doivent être enle-
vées de la télécommande et faire l'objet d'une élimination
séparée conformément à la législation locale et nationale.
INFORMATIONS IMPORTANTES CONCER-
NANT LE LIQUIDE RÉFRIGÉRANT UTILISÉ
1
1+2=
kg
R410A
2
kg
2=
1=
B
C
D
FE
kg
A
Cet appareil contient des gaz à effet de serre fluorés couverts par
le protocole de Kyoto. Ne pas ventiler à l'air.
Type de réfrigérant : R410A
Valeur de GWP*: 1975
GWP = global warming potential - potentiel de réchauffement de la
planète.
Merci de remplir à l'encre indélébile;
• 1 La charge de réfrigérant usine de l'appareil
• 2 la quantité supplémentaire de réfrigérant chargée sur place
et
• 1+2 la charge totale de réfrigérant.
sur l'étiquette de charge de réfrigérant fournie avec l'appareil.
L'étiquette renseignée doit être collée à proximité du port de char-
gement de l'appareil (par ex.sur l'intérieur du couvercle de valeur
d'arrêt).
A Contient des gaz à effet de serre fluorés couverts par le proto-
cole de Kyoto.
Protocole
B Charge de réfrigérant standard de l'unité : voir sur la plaque
signalétique de l'unité
C Quantité supplémentaire de réfrigérant chargée sur place
D Charge totale de réfrigérant
E Unité extérieure
F Cylindre réfrigérant et collecteur de chargement
Contient des gaz à effet de serre  uorés
couverts par le protocole de Kyoto.
Haier Industrial Park, No.1 Haier Road, Qingdao, P.R.Chine
Schéma d'installation des unités intérieures et extérieures
Les modèles utilisent le réfrigérant R410A sans HFC.
Pour l'installation des unités intérieures, veuillez vous référer au manuel d'installation fourni avec les unités.
(Le diagramme illustre une unité intérieure à montage mural.)
L'illustration ci-dessus des unités intérieure et extérieure, n'est indiquée qu'à titre de référence.
Veuillez tenir compte des particularités du modèle acheté.
F
A
C
E
D
A
F
C
E
D
G
B
G
4
plus de 15 cm
Il faut faire particulièrement
attention au soulèvement du
tuyau de vidange.
Disposition des directions
de la tuyauterie
Gauche
Arrière gauche
Arrière
droite
Droite
En bas
plus de
10 cm
plus de 10 cm
plus de 20 cm
plus de 60 cm
Fixation de l'unité extérieure
Fixez l'unité horizontalement et
solidement sur le béton ou un bloc
de béton avec des boulons (10
mm) et des écrous
Lorsque l'unité doit être installée
sur un mur, un toit ou la toiture,
xez un support avec des clous
ou des  ls en tenant compte des
séismes et vents forts.
Si des vibrations risquent d'affec-
ter la maison,  xez l'unité avec un
tapis anti-vibration
Les marques de
A
à
G
sur la  gure, représentent
les références de pièce.
La distance entre l'unité
intérieure et le sol doit
être supérieure à 2 m.
Pièces en option pour la tuyauterie
Ruban non adhésif
Ruban adhésif
Selle (L.S) avec vis
Raccordement du câble électrique
entre unités intérieures et extérieures
Tuyau de vidange
Matériau d'isolation thermique
Cache trou de tuyauterie
plus de 20 cm
plus de 25 cm
Compresseur (Intérieur de l'unité)
4 TUYAU DE VIDANGE
CONNEXION DE LA TUYAUTERIE ET DU CÂBLAGE ÉLEC-
TRIQUE
ENTRÉE D'AIR
SORTIE D'AIR
43
Consignes de sécurité
Pour un fonctionnement adéquat du climatiseur, veuillez lire attentivement les informations suivantes.
Vous trouverez ci-dessous trois types de consignes de sécurité et de suggestions.
AVERTISSEMENT La mauvaise utilisation de l'appareil peut entraîner de graves conséquences, comme la
mort ou des blessures graves.
ATTENTION La mauvaise utilisation de l'appareil peut entraîner des blessures ou des dommages sur
l'appareil. Dans certain cas, les conséquences peuvent être graves.
INSTRUCTION : Ces informations garantissent la bonne utilisation de l'appareil.
Symboles utilisés dans les illustrations
: indique une action à éviter.
: indique qu'il faut se conformer aux instructions importantes.
: indique une pièce qu'il faut relier à la terre.
: attention, risque d'électrocution (Ce symbole gure sur l'étiquette de l'unité principale.)
Une fois ce manuel lu, conservez-le pour le transmettre aux utilisateurs de l'appareil.
L'utilisateur doit conserver ce manuel à portée de main, et le remettre aux réparateurs ou aux personnes qui vont déplacer l'appareil. As-
surez-vous également de pouvoir le transmettre au nouvel utilisateur, si l'appareil change de propriétaire.
Assurez-vous de suivre les importantes consignes de sécurité ci-dessous.
AVERTISSEMENT
En cas de présence de phénomène anor-
mal (par exemple une odeur de brûlé),
coupez immédiatement l'alimentation élec-
trique et contactez votre fournisseur pour
trouver une solution.
Dans ce cas, continuer d'utiliser le climatiseur va l'endommager
et peut entraîner une électrocution ou un incendie.
Lorsque le climatiseur est utilisé sur une
longue période, véri ez l'absence de dom-
mage au niveau de sa base.
Si une base endommagée n'est pas répa-
rée, l'unité peut tomber et provoquer des
accidents.
• Ne pas démonter la sortie de l'unité exté-
rieure.
L'exposition au ventilateur est très dan-
gereux et peut vous blesser.
En cas de maintenance ou de répara-
tion, faites appel à votre fournisseur.
Une mauvaise maintenance et répara-
tion peut entraîner une fuite d'eau, une
électrocution et un incendie.
Mise hors
tension
AVERTISSEMENT
Aucun objet et aucune personne ne doit être
placé, ou se tenir debout, sur l'unité exté-
rieure. La chute d'objet ou de personne peut
entraîner des accidents.
Ne faites pas fonctionner le climatiseur avec
les mains humides. Risque d'électrocution.
N'utilisez qu'un fusible du type recommandé.
N'utilisez pas de câble ou d'autre matériaux
pour remplacer le fusible. Cela peut entraîner
des défaillances ou un risque d'incendie.
Utilisez correctement le conduit de sortie, pour assurer un refou-
lement ef cace.
Une mauvaise utilisation du conduit peut entraîner une fuite
d'eau.
Disjoncteur électrique installé.
Une électrocution est fréquence sans disjoncteur.
Le climatiseur ne peut pas s'installer dans un environnement en
cas de présence de gaz in ammables. Ces gaz à proximité du
climatiseur peuvent entraîner un incendie.
Veuillez con er l'installation du climatiseur à votre fournisseur.
Une mauvaise installation peut entraîner une fuite d'eau, une
électrocution et un incendie.
Appelez le fournisseur pour effectuer des mesures et éviter les
fuites de liquide réfrigérant.
Si le climatiseur est installé dans une petite pièce, assurez-vous
d'avoir pris toutes les mesures pour empêcher les accidents
d'asphyxie en risque de fuite de réfrigérant.
Le fournisseur doit être responsable de l'installation ou de la
réparation du climatiseur.
Une mauvaise installation peut entraîner une fuite d'eau, une
électrocution et un incendie.
Branchement du câble de mise à la terre.
Le câble de mise à la terre ne doit pas être connecté au
tuyau de gaz, au tuyau d'eau, au paratonnerre ou à la
ligne téléphonique. Une mauvaise mise à la terre peut
entraîner une électrocution.
Mise à la
terre
44
Consignes de sécurité
AVERTISSEMENT
L'installation de l'unité doit être effectuée par un professionnel.
La mauvaise installation de l'appareil par une personne non
quali ée, peut entraîner des fuites d'eau, une électrocution ou un
incendie.
Placez l'unité sur une surface stable et de niveau, capable de
supporter le poids de l'unité pour que celle-ci ne bascule ni ne
tombe, de façon à éviter tout risque de blessure.
N'utilisez que les câbles spéci és pour le câblage. Branchez
fermement chaque câble et assurez-vous qu'ils ne sont pas trop
tendus au niveau du bornier.
Les câbles qui ne sont pas bien branchés, peuvent générer de la
chaleur et provoquer un incendie.
Prenez les mesures de sécurité nécessaires contre les thyphons
et les tremblements de terre, de façon à ce que l'unité ne bascule
pas.
N'effectuez aucune modi cation ou altération sur l'appareil. En
cas de problème, consultez le fournisseur.
Si les réparations ne sont pas effectuées correctement, l'unité
peut présenter des fuites d'eau, ou entraîner un risque d'électro-
cution, il peut générer une émission de fumée, ou un incendie.
Soyez attentif à bien suivre chaque étape de ce manuel au mo-
ment d'installer l'unité.
Une mauvaise installation peut entraîner des fuites d'eau, une
électrocution, une émission de fumée ou un incendie.
Tous les travaux d'électricité doivent être réalisés par un électri-
cien quali é, conformément aux réglementations locales et aux
instructions du présent manuel. Sécurisez un circuit exclusif pour
l'unité.
Une mauvaise installation ou un manque de capacité au niveau
du circuit, peut entraîner un dysfonctionnement de l'unité, pré-
senter un risque d'électrocution, une émission de fumée ou un
incendie.
Fixez de façon sûre le cache-borne (panneau) sur l'unité.
Si l'appareil est mal installé, de la poussière et/ou de l'eau peut
pénétrer dans l'unité et entraîner alors un risque d'électrocution,
d'émission de fumée ou d'incendie.
N'utilisez que du réfrigérant R410A, comme indiqué sur l'unité,
lorsque vous installez ou déplacez l'unité.
L'utilisation d'un autre réfrigérant ou la pénétration d'air dans le
circuit de l'unité peut entraîner un fonctionnement en cycle anor-
mal. Un cycle anormal peut entraîner l'explosion de l'unité.
AVERTISSEMENT
Ne touchez pas les ailettes de l'échangeur thermiques à mains
nues, elles sont pointues et dangereuses.
En cas de fuite de gaz réfrigérant, assurez une bonne ventilation
de la pièce.
Si le gaz réfrigérant qui a fuit est exposé à une source de cha-
leur, un gaz nocif peut se dégager.
Avec les
climatiseurs du type All-Fresh, l'air extérieur peut être
directement souf é à l'intérieur de la pièce, lorsque le thermostat
est coupé. Le prendre en considération lors de l'installation de
l'unité.
L'
exposition directe à l'air extérieur peut entraîner un risque pour
la santé et peut également engendrer la détérioration des den-
rées alimentaires.
N'essayez pas de contourner les fonctionnalités de sécurité des
appareils et ne modi ez pas les réglages.
L'altération des fonctionnalités de sécurité de l'unité, comme le
pressostat et le thermocontact, ou l'utilisation de pièces autres
que celles proposées par le fournisseur ou le spécialiste, peut
entraîner un incendie ou une explosion.
Lorsque vous installez l'unité dans une petite pièce, protégez-
vous contre l'hypoxie pouvant survenir en cas de fuite du réfrigé-
rant d'un niveau supérieure au seuil critique.
Consultez le fournisseur pour connaître les mesures à prendre.
Lorsque vous repositionnez un climatiseur, consultez le fournis-
seur ou un spécialiste.
Une mauvaise installation peut entraîner des fuites d'eau, une
électrocution, ou un incendie.
Une fois le service d'entretient effectué, contrôlez l'absence de
fuite du gaz réfrigérant.
Si le gaz réfrigérant qui a fuit est exposé à une source de cha-
leur, comme un radiateur souf ant, une cuisinière ou un grill élec-
trique, un gaz nocif peut se dégager.
N'utilisez que les pièces spéci ées.
L'installation de l'unité doit être effectuée par un professionnel.
Une mauvaise installation peut entraîner des fuites d'eau, une
électrocution, une émission de fumée ou un incendie.
45
Consignes de sécurité
Précautions pour la manipulation des unités lorsque du réfrigérant R410A est utilisé
Avertissement
N'utilisez pas le tuyau du réfrigérant existant
L'ancien réfrigérant et l'huile du réfrigérateur présents dans le
tuyau existant, contiennent une grande quantité de chlore, ce qui
va détériorer la qualité de l'huile du réfrigérateur dans la nouvelle
unité.
Le R410A est un réfrigérant à haute pression. Son utilisation
dans le tuyau existant va entraîner sa  ssuration.
Gardez les surfaces intérieures et extérieures des tuyaux propres
et exempts de contaminants, comme le soufre, les oxydes, la pous-
sières/les particules de saleté, les huiles et la moisissure.
La présence de contaminants dans le tuyau du réfrigérant va
entraîner la détérioration de l'huile réfrigérante.
Utilisez une pompe à vide avec clapet de non-retour en circuit
fermé.
Si d'autres types de clapets sont utilisé, l'huile de la pompe à
vide va retourner dans le cycle du réfrigérant et provoquer la
détérioration de l'huile du réfrigérateur.
N'utilisez pas les outils suivants, ayant déjà été utilisés avec les
réfrigérants conventionnels. Préparez des outils à utiliser exclusive-
ment avec le R410A.
(Collecteur de jauge, tubulure de charge, détecteur de fuite de gaz,
clapet de non-retour en circuit fermé, base de chargement du réfri-
gérant, jauge à vide et équipement de récupération du réfrigérant.)
Si le réfrigérant et/ou l'huile réfrigérante qui reste sur ces outils
est mélangé avec le R410, ou si de l'eau est mélangée avec le
R410A, le réfrigérant sera détérioré.
Le R410A ne contient pas de chlore. Les détecteurs de fuite de
gaz pour les réfrigérateurs conventionnels, ne fonctionnent pas
avec ce type de réfrigérant.
Avertissement
Rangez la tuyauterie à utiliser pour l'installation à l'intérieur et gar-
dez les deux extrémités de la tuyauterie scellées jusqu'au brasage.
(conservez les coudes et autres joints dans leur emballage en
plastique.)
Si de la poussière, de la saleté ou de l'eau pénètre dans le cycle
du réfrigérant, l'huile de l'unité peut se détériorer, ou le compres-
seur mal fonctionner.
Utilisez une petite quantité d'huile d'ester, d'huile d'éther ou d'alkyl-
bensène pour enduire les évasements et les joints à brides.
Une grande quantité d'huile minérale peut entraîner la détériora-
tion de l'huile de la machine réfrigérante.
Utilisez du réfrigérant
liquide pour charger le système.
Chargez l'unité avec du gaz réfrigérant va entraîner la modi ca-
tion de la composition du réfrigérant dans le cylindre. Les perfor-
mances en seront amoindries.
N'utilisez pas de cylindre de chargement
L'utilisation d'un cylindre de chargement va modi er la composi-
tion du réfrigérant et entraîner une perte de puissance.
Faites particulièrement attention à la manipulation des outils.
L'introduction d'objets étrangers, comme la saleté, la poussière
ou l'eau dans le cycle du réfrigérant, va entraîner la détérioration
de l'huile de la machine réfrigérante.
N'utilisez que le réfrigérant R410A.
L'utilisation de réfrigérants contenant du chlore (comme le R22),
va entraîner la détérioration du réfrigérant.
Avant d'installer l'unité
Avertissement
N'installez pas l'unité dans un environnement pouvant être sujet à
une fuite de gaz in ammable.
Le gaz qui a fuit et qui s'accumule autour de l'unité, peut être à
l'origine d'un incendie.
N'utilisez pas l'unité pour conserver des aliments, des animaux, des
plantes, des objets ou pour tout autre usage particulier.
L'unité n'est pas conçue fournir les conditions adéquates de pré-
servation de la qualité de ces articles.
N'utilisez pas l'unité dans un environnement inhabituel.
L'utilisation de l'unité en présence d'une grande quantité d'huile,
de vapeur, d'acide, de solvants alcalins ou de types particuliers
d'embruns, peut entraîner une chute notable des performances
et/ou le dysfonctionnement de l'appareil, et présente un risque
d'électrocution, d'émission de fumée ou d'incendie.
La présence de solvants organiques, de gaz corrosifs(comme
l'ammoniac, les composés du soufre et les acides) peuvent en-
traîner une fuite de gaz ou d'eau.
Lorsque l'unité est installé dans un hôpital, prenez les mesures qui
s'imposent contre le bruit.
Les équipements médicaux de haute fréquence peuvent interfé-
rer avec le fonctionnement normal du climatiseur, ou le climati-
seur peut interférer avec le fonctionnement normal des équipe-
ments médicaux.
Ne placez pas l'unité sur ou par-dessus des éléments qui ne doi-
vent pas être mouillés.
Lorsque le niveau d'humidité dépasse les 80%, ou lorsque le
système de vidange est obturé, de l'eau peut goutter des unités
intérieures.
L'installation d'un système de vidange centralisé pour l'unité ex-
térieure peut également être pris en considération pour éviter les
gouttes d'eau qui s'échappent des unités extérieures.
46
Consignes de sécurité
Avant d'installer (de repositionner) l'unité ou d'effectuer des travaux électrique
Avertissement
Mise à la terre de l'unité.
Ne branchez pas la mise à la terre de l'unité sur les tuyaux de
gaz, les tuyaux d'eau, le paratonnerre ou aux bornes de mise à
la terre des téléphones. Une mauvaise mise à la terre présente
un risque d'électrocution, d'émission de fumée, d'incendie. Le
bruit provoqué par une mauvaise mise à la terre peut également
entraîner le dysfonctionnement de l'unité.
Assurez-vous que les câbles ne sont pas soumis à une tension.
Si les câbles sont trop tendus, ils peuvent se casser ou générer
de la chaleur/une émission de fumée et entraîner un incendie.
Installez un disjoncteur pour fuite de courant au niveau de la source
d'alimentation, pour éviter tout risque d'électrocution.
Sans disjoncteur pour fuite de courant, il existe un risque d'élec-
trocution, d'émission de fumée ou d'incendie.
Utilisez les disjoncteurs et les fusibles (disjoncteur de courant
électrique, interrupteur à distance <interrupteur+fusible de type
B>, disjoncteur à boîtier moulé) présentant la capacité d'intensité
adéquate.
L'utilisation de fusibles à grande capacité, de câble en acier ou
en cuivre, peut endommager l'unité ou générer une émission de
fumée ou un incendie.
Ne vaporisez pas de l'eau sur les climatiseurs. Ne les immergez
pas dans l'eau.
La présence d'eau sur l'unité présente un risque d'électrocution.
Contrôlez périodiquement la plate-forme sur laquelle l'unité est
placée
pour éviter que l'unité ne tombe en cas de dommage.
Si l'unité est placée sur une plate-forme endommagée, elle peut
basculer et blesser quelqu'un.
Lors de l'installation des tubulures de vidange, suivez les instruction
du manuel et assurez-vous qu'elles vidangent correctement l'eau
pour éviter toute condensation.
En cas de mauvaise installation, il y a risque de fuites d'eau et de
dommages aux meubles voisins.
Veuillez vous débarrasser de façon adéquate des matériaux d'em-
ballage.
Des objets, comme des clous, peuvent se trouver dans l'embal-
lage. Veuillez vous en débarrasser de façon adéquate pour éviter
de vous blesser.
Les sacs en plastique présentent un risque suffocation pour les
enfants. Pour éviter tout accident, déchirez les sacs en plastique
avant de les jeter.
Avant d'effectuer le test de fonctionnement
Avertissement
Pour éviter tout risque d'électrocution, ne touchez pas aux interrup-
teurs avec les mains mouillées.
Ne touchez pas les tuyaux de réfrigérant à main nue pendant et
immédiatement après le fonctionnement de l'appareil.
Selon l'état du réfrigérant dans le circuit, certaines pièces de
l'unité, comme les tuyaux et le compresseur, peuvent devenir
très froids ou très chauds. Risque de gelures ou de brûlures.
Ne faites fonctionner l'unité qu'une fois les panneaux et les protec-
tions de sécurité bien en place.
Ces éléments permettent de protéger les utilisateurs des acci-
dents liés aux éléments mobiles, à la haute température ou aux
pièces sous haute tension.
Ne coupez pas immédiatement l'alimentation après avoir arrêté
l'unité.
Laissez au moins cinq minutes avant de mettre l'unité hors
tension. L'unité risque sinon de présenter des fuites d'eau ou
d'autres problèmes.
Ne faites pas fonctionner l'unité sans  ltres à air.
Les particules de poussière dans l'air peuvent obturer le système
et entraîner son dysfonctionnement.
47
À lire avant l'installation
Éléments à contrôler
(1). Véri ez le type de réfrigérant utilisé dans l'unité à réparer. Type de réfrigérant : R410A
(2). Contrôlez la défaillance de l'unité à réparer. Véri ez dans le manuel
d'entretien les symptômes en rapport avec le cycle du réfrigérant.
(3). Assurez-vous d'avoir lu avec attentions les consignes de sécurité qui  gurent au début de ce document.
(4). En cas de fuite de gaz, ou si le réfrigérant restant est exposé à une  amme ouverte, un gaz toxique, l'acide  uorhydrique, peut se
former. Le lieu de l'intervention doit être bien ventilé.
AVERTISSEMENT
Installez les nouveaux tuyaux immédiatement après avoir retiré les anciens pour que l'humidité ne pénètre pas dans le circuit du réfrigérant.
Le chlore présent dans certains types de réfrigérants, comme le R22, peut entraîner la détérioration de l'huile de la machine réfrigérante.
Outils et matériaux nécessaires
Préparez les outils suivants et les matériaux nécessaires pour l'installation et l'entretien de l'unité.
Outils nécessaires lorsque le réfrigérant R410A est utilisé (adaptativité des outils à utiliser avec les réfrigérants R22 et R407C).
1. À utiliser exclusivement avec le R410A (à ne pas utiliser avec le R22 ou le R407C)
Outils/Matériaux Utilisation Remarques
Collecteur de jauge Évacuation, chargement du réfrigérant 5,09 MP du côté haute pression.
Tubulure de charge Évacuation, chargement du réfrigérant Diamètre de la tubulure supérieur aux tubulures conventionnelles.
Équipement de récupération du réfrigé-
rant
Récupération du réfrigérant
Cylindre réfrigérant Pour le chargement du réfrigérant Notez le type de réfrigérant. Couleur rose en haut du cylindre.
Port de chargement du cylindre réfrigé-
rant
Pour le chargement du réfrigérant Diamètre de la tubulure supérieur aux tubulures conventionnelles.
Ecrou d'évasement Connexion de l'unité à la tuyauterie Utilisez des écrous d'évasement du type 2.
2. Outils et matériaux pouvant être utilisés avec le réfrigérant R410 avec quelques restrictions
Outils/Matériaux Utilisation Remarques
Détecteur de fuite de gaz Détection des fuites de gaz Il est possible d'utiliser ceux compatibles avec le réfrigérant du type HFC.
Pompe à vide Séchage sous vide Peut être utilisé si un adaptateur de non-retour en circuit fermé est installé.
Outil d'évasement Outil pour l'évasement des tuyaux Des modi cations ont été apportées dans les dimensions d'évasement. Veuillez vous réfé-
rer à la page suivante.
Équipement de récupération du
réfrigérant
Récupération du réfrigérant Peut être utilisé si conçu pour une utilisation avec le réfrigérant R410A.
3. Outils et matériaux utilisés avec le réfrigérant R22 ou R407C pouvant également être utilisés avec le réfrigérant R410A.
Outils/Matériaux Utilisation Remarques
Pompe à vide avec clapet de non-retour Séchage sous vide
Machine à plier Pour plier les tuyaux
Clé dynamométrique Pour serrer les écrous d'évasement Seuls les diamètres
12,70 (1/2'') et 15,88(5/8'') présentent des dimensions d'évase-
ment plus grandes.
Coupe-tube Pour découper les tuyaux
Machine à souder et bouteille d'azote Pour souder les tuyaux
Instrument de mesure du chargement de
réfrigérant
Pour le chargement du réfrigérant
Videmètre Pour mesurer la raréfaction de l'air
4. Outils et matériaux ne devant pas être utilisés avec le réfrigérant R410A
Outils/Matériaux Utilisation Remarques
Cylindre de chargement Pour le chargement du réfrigérant Ne doit pas être utilisé avec les unités du type R410.
Les outils à utiliser avec le réfrigérant R410A doivent être manipulés avec une attention particulière. L'humidité et la poussière ne doivent
pas entrer dans le cycle.
48
À lire avant l'installation
Matériaux des tuyaux
Types de tuyaux en cuivre (référence)
Pression de fonctionnement maximale Réfrigérants applicables
3,4 MPa R22, R407C
4,15 MPa R410A
Utilisez des tuyaux conformes aux normes locales.
Matériaux des tuyaux/épaisseur radiale
Utilisez les tuyaux en cuivre désoxydé au phosphore.
La pression de fonctionnement des unités utilisant du R410A est plus importante que celle des unités utilisant du R22. Les tuyaux à
utiliser doivent donc présenter une épaisseur radiale au moins égale aux indications du tableau ci-dessous. (Les tuyaux présentant une
épaisseur radiale inférieure ou égale à 0,7 mm, ne doivent pas être utilisés.)
Taille (mm) Taille (pouce) Épaisseur radiale (mm) Type
6.35 1/4'' 0,8t
Tuyaux en O
9.52 3/8" 0,8t
12.7 1/2" 0,8t
15.88 5/8" 1,0 t
19.05 3/4" 1,0 t Tuyaux en 1/2H ou en H
Même s'il est possible d'utiliser des tuyaux en O d'une taille maximale de 19,05 (3/4") avec les réfrigérants conventionnels, utilisez des
tuyaux en 1/2H pour les unités utilisant du réfrigérant R410A. (Les tuyaux en O peuvent être utilisés si leur taille est de 19,05 et que leur
épaisseur radiale est de 1,2t.)
Le tableau répertorie les normes au Japon. Utilisez ce tableau comme référence et choisissez les tuyaux qui sont conformes aux nor-
mes locales.
Outil pour l'évasement (tuyaux en O et OL uniquement)
Pour augmenter l'étanchéité à l'air, les dimensions de l'évasement pour les unités qui utilisent le réfrigérant R410A sont plus importantes
que celles pour les unités qui utilisent le réfrigérant R22.
Dimensions d'évasement (mm)
Dimensions externes des
tuyaux
Taille
Dimension A
R410A R22
6.35 1/4'' 9.1 9.0
9.52 3/8" 13.2 13.0
12.7 1/2" 16.6 16.2
15.88 5/8" 19.7 19.4
19.05 3/4" 24.0 23.3
Si un outil d'évasement du type à embrayage est utilisé pour usiner des évasements sur les unités qui utilisent le réfrigérant R410A, la
partie du tuyau qui dépasse doit faire entre 1,0 et 1,5 mm. Utilisez la jauge pour tuyau en cuivre pour ajuster la longueur de la partie qui
dépasse.
Ecrou d'évasement
Les écrous d'évasement du type 2 sont utilisés, plutôt que les écrous du type 1, de façon à optimiser la résistance. La taille de certains
écrous d'évasement a également été modi ée.
Dimensions des écrous d'évasement (mm)
Dimensions externes des
tuyaux
Taille
Dimension B
R410A (Type2) R22 (Type1)
6.35 1/4'' 17.0 17.0
9.52 3/8" 22.0 22.0
12.7 1/2" 26.0 24.0
15.88 5/8" 29.0 27.0
19.05 3/4" 36.0 36.0
Le tableau répertorie les normes au Japon. Utilisez ce tableau comme référence et choisissez les tuyaux qui sont conformes aux nor-
mes locales.
Dimension A
Dimension B
49
À lire avant l'installation
Test d'étanchéité à l'air
AUCUNE modi cation par rapport à la méthode conventionnelle. Remarquez qu'un détecteur de fuite de réfrigérant pour le R22 ou le
R407C, est incapable de détecter une fuite de R410A.
Se conformer strictement aux éléments suivants :
1. Pressurisez les équipement à l'azote, jusqu'à atteindre la pression de calcul. Véri ez ensuite l'étanchéité à l'air de l'équipement. Les
variations de température sont à prendre en compte.
2. Lorsque vous recherchez les emplacements des fuites en utilisant un réfrigérant, assurez-vous d'utiliser le R410A.
3. Assurez-vous que le R410A est en état liquide au moment du chargement.
Raisons :
1. L'utilisation de l'oxygène comme gaz sous pression, peut entraîner une explosion.
2. Le chargement avec du gaz R410A va entraîner la modi cation de la composition du réfrigérant restant dans le cylindre. Ce réfrigérant
ne peut alors plus être utilisé.
Mise sous vide
1. Pompe à vide avec clapet anti-retour
Une pompe à vide avec un clapet anti-retour est requise pour empêcher le retour de l'huile de la pompe dans le circuit du réfrigérant
lorsque l'alimentation de la pompe à vide est coupée (en cas de coupure d'électricité). Il est également possible d'équiper ultérieure-
ment la pompe à vide d'un clapet anti-retour.
2. Degré de vide standard de la pompe à vide
Utilisez une pompe pouvant atteindre les 65 Pa ou moins, après 5 minutes de fonctionnement.
En outre, assurez-vous d'utiliser une pompe à vide bien entretenue et huilée en utilisant l'huile spéci ée. Si la pompe à vide n'est pas
bien entretenue, le degré de vide peut être trop bas.
3. Précision requise du videmètre
Utilisez un videmètre pouvant mesurer jusqu'à 650 Pa. N'utilisez pas de collecteur de jauge général, car il est incapable de mesurer un
vide de 650 Pa.
4. Durée de la mise sous vide
Faire le vide de l'équipement pendant environ 1 heure à partir du moment où la pression a atteint les 650 Pa.
Une fois le vide atteint, laissez l'équipement pendant 1 heure, et assurez-vous que le vide ne se perd pas.
5. Consignes d'utilisation lorsque la pompe à vide est stoppée
Pour éviter tout retour de l'huile de la pompe à vide, ouvrez le clapet de décharge du côté pompe à vide, ou dévisser le tuyau de charge
pour faire rentrer de l'air avant d'interrompre le fonctionnement. La même consigne d'utilisation est à utiliser lorsque l'appareil fonction-
ne avec une pompe à vide équipée d'un clapet anti-retour.
Chargement du réfrigérant
Le R410A doit être en état liquide au moment du chargement.
Raisons :
Le R410A est un réfrigérant pseudo-azéotropique (point d'ébullition R32=-52
o
C, R125=-4952
o
C). Il peut quasiment se manipuler de la
même façon que le R22. Assurez-vous cependant de procéder au remplissage du réfrigérant du côté liquide. Si vous l'effectuez du côté
gaz, cela va modi er la composition du réfrigérant dans le cylindre.
Remarque
Dans le cas d'un cylindre doté d'un siphon, le R410A liquide est chargé sans retourner le cylindre. Contrôlez le type de cylindre avant de
procéder au chargement.
Mesures à prendre en cas de fuite de réfrigérant
Lorsque le réfrigérant fuit, il est possible d'introduire du réfrigérant additionnel. (Ajoutez du réfrigérant du côté liquide)
Caractéristiques des réfrigérants conventionnels et des nouveaux réfrigérants
Le R410A est un réfrigérant pseudo-azéotropique. Il peut se manipuler quasiment de la même façon qu'un réfrigérant simple, du type
R22. Cependant, si du réfrigérant est retiré dans sa phase vapeur, la composition du réfrigérant dans le cylindre va être quelque peu
modi ée.
Retrait du réfrigérant en phase liquide. Du réfrigérant additionnel peut être ajouté en cas de fuite de réfrigérant.
Lampe haloïde Détecteur de fuite de R22 ou R407C
50
Procédure d'installation
Installation de l’unité extérieure
1. Accessoires
"Bordure" pour protéger les câbles
électriques d'un bord saillant.
2. Choix de l'emplacement de l'installation
Choisissez l'emplacement de l'installation de façon à satisfaire les conditions suivantes, tout en répondant aux besoins du client ou de
l'utilisateur.
Placez l'appareil dans un endroit où l'air circule bien.
Placez l'appareil dans un endroit à distance d'une radiation de chaleur provenant d'autres sources de chaleur.
Placez l'appareil dans un endroit compatible avec le versement de l'eau de vidange.
Placez l'appareil dans un endroit où le bruit et l'air chaud ne dérangent pas le voisinage.
Placez l'appareil dans un endroit qui n'est pas soumis à de fortes chutes de neige en hiver.
Placez l'appareil dans un endroit où l'entrée et la sortie d'air ne sont pas obturées.
Placez l'appareil dans un endroit où la sortie d'air n'est pas exposée à un fort vent.
Le positionnement de l'appareil alors que ses quatre faces sont contre des éléments, ne convient pas à son installation. Il faut un espace
au-dessus de l'appareil, d'au moins 1 mètre.
Évitez d'installer des grilles de transfert aux endroits qui présentent un risque de court-circuit.
Lorsque vous installez plusieurs unités, véri ez que l'espace d'aspiration est suf sant pour éviter tout court-circuit.
Exigence concernant l'espace ouvert autour de l'unité
3. Installation de l’unité extérieure
Fixez l'unité sur la fondation de façon adéquate, conformément aux condi-
tions de l'emplacement de l'installation, et en se référant aux informations
suivantes.
Laissez suf samment d'espace libre au niveau de la fondation béton,
pour y  xer les boulons d'ancrage.
Coulez la fondation béton suf samment en profondeur.
Installez l'unité de façon à ce que l'angle d'inclinaison soit inférieur à 3
degrés.
Il est interdit de placer l'unité directement au sol. Véri ez qu'il y a suf -
samment d'espace libre à proximité du trou de vidange de la plaque inférieure, de façon à pouvoir vidanger l'eau facilement.
4. Dimensions d'installation (Unité : mm)
(Espace
destiné à l'en-
tretien)
Entrée d'air
Entrée d'air
Sortie d'air
Distance Cas I Cas II Cas III
L1 ouvert ouvert 500 mm
L2 300 mm 300 mm ouvert
L3 150 mm 300 mm 150 mm
Remarque :
(1) Fixez les pièces avec des vis.
(2)
Ne pas soumettre l'ori ce de sortie
d'air de l'unité à un vent fort et direct.
(3) Un mètre de distance doit être
conservé à partir du haut de l'unité.
(4) Ne pas obturer les contours de
l'unité avec des objets divers.
(5) Si l'unité extérieure est installé dans un environnement soumis au
vent, installez-la de façon à ce que la grille de sortie NE soit PAS
dirigée dans le sens du vent.
NO
Sens du vent
Sortie d'air
Boulon d'ancrage
Unité
Caoutchouc
amortisseur
Fondation béton
Ori ce de distri-
bution du câblage
d'alimentation
Borne de câblage
de l'alimentation
Modèle W D H L1 L2 L3
1U07BS1ERA 780 245 540 500 140 256
1U09BS1ERA 780 245 540 500 140 256
1U12BS1ERA 780 245 540 500 140 256
1U18FS1ERA 810 288 688 583 113.5 319.5
1U24GS1ERA 860 308 730 633 113.5 340
Bordure
51
Installez les écrous d'évasement sur les
tuyaux à brancher, puis évasez les tuyaux.
A
B
A
B
A
B
unité extérieure
Unité
intérieure
Unité
intérieure
unité extérieure
unité extérieure
Unité
intérieure
Piège dl'huile
Hauteur max: Amax
Si la hauteur A dépasse les 5m,
installez un piège à huile tous les 5 à
7 m
Longueur max: Bmax
Si la longueur du tuyau B dépasse les
D m, le réfrigérant doit être chargé à
E g/m.
Unité extérieure Amax Bmax C D E
1U07BS1ERA 10 15 5 7 20
1U09BS1ERA 10 15 5 7 20
1U12BS1ERA 10 15 5 7 20
1U18BS1ERA 15 25 5 7 20
1U24BS1ERA 15 25 5 7 45
Procédure d'installation
Branchement des tuyaux
1. Taille des tuyaux
1U07BS1ERA 1U09BS1ERA
1U12BS1ERA
Tuyau de liquide
6,35x0,8 mm
Tuyau de gaz
9,52x0,8 mm
1U18FS1ERA
Tuyau de liquide
6,35x0,8 mm
Tuyau de gaz
12,7x0,8 mm
1U24GS1ERA
Tuyau de liquide
9,52x0,8 mm
Tuyau de gaz
15,88x1,0 mm
2
. Raccords de tuyauterie
Lorsque vous courbez un tuyau, donnez-lui autant de rondeur que possible a n de ne pas l’écraser ; le rayon
de courbure doit être d’au moins 30 à 40 mm, voire plus.
Connectez d'abord le côté gaz pour faciliter la suite des travaux.
Le tuyau de raccordement est réservé à R410A.
Faites attention que des particules telles que les déchets,
le sable, l'eau , etc. ne rentrent pas dans le tuyau.
AVERTISSEMENT
La longueur standard d'un tuyau est de C m. Si elle dépasse les D m, la fonction de l'unité s'en trouvera affectée.
S'il faut rallonger le tuyau, le réfrigérant doit être chargé selon E g/m. Toutefois, la charge de réfrigérant doit être
exécuté par un professionnel de la climatisation. Avant d'ajouter du réfrigérant, purgez l'air des tuyaux de réfrigé-
ration et de l'unité intérieure avec pompe à vide. Chargez ensuite le réfrigérant supplémentaire.
Le serrage forcé sans prêter attention au centrage peut
endommager les  lets et entraîner des fuites de gaz.
Demi-raccord
Ecrou
d'évasement
Clé
Clé
dynamométrique
Diamètre du tuyau (Ø) Couple de serrage
Côté liquide 6,35 mm (1/4 po) 18N.m
Côté liquide/gaz 9,52 mm (3/8 po) 42 N.m
Gaz 12,7mm (1/2") 55 N.m
Gaz 15,88mm (5/8") 60 N.m
52
Procédure d'installation
Test d'étanchéité à l'air
Une fois la connexion du tuyau réfrigérant effectuée, procédez au test d'étanchéité à l'air.
Le test d'étanchéité à l'air utilise une bouteille d'azote pour la mise sous pression, selon le mode de connexion du tuyau,
comme le montre l'illustration suivante.
Le clapet du gaz et du liquide sont tous les deux fermés. Pour éviter la pénétration de l'azote dans le système de circula-
tion de l'unité extérieure, serrez le clapet avant la mise sous pression (le clapet du gaz et du liquide).
1) Appliquez une pression pendant au moins 3 minutes à
0,3MPa (3,0 kg/cm
2
g)
2) Appliquez une pression pendant au moins 3 minutes à 1,5
MPa (15kg/cm
2
g) Une fuite importante sera observée.
3) Appliquez une pression pendant au moins 24 heures à 3,0
MPa (30kg/cm
2
g) Une petite fuite sera observée.
Véri ez si la pression a baissé
Si la pression n'a pas bougé, poursuivez.
Si la pression a baissé, veuillez contrôler le point de fuite.
Lors de la mise sous pression pendant 24 heures, une variation de 1°C de la température ambiante va provoquer une variation de 0,01
MPa (0,1kg/cm2 g) de la pression.
Ceci est à corriger au cours du test.
Véri cation du point de fuite
Dans les étapes 1) à 3), en cas de chute de la pression, contrôlez la présence d'une fuite à chaque joint
en écoutant, en touchant, en
utilisant de l'eau savonneuse, etc.
de façon à pouvoir identi er le point de fuite. Une fois le point de fuite con rmé, ressoudez-le ou ser-
rez une nouvelle fois l'écrou.
Soupape d'arrêt complètement
fermée (côté liquide)
ExtérieurIntérieur
Complètement serré
Pièce d'évasement
Unités intérieures
Soupape d'
arrêt complètement
fermée (côté gaz)
Complètement serré
Clapet de refoulement
Regard
Unités extérieures
Piézomètre basse
pression
Piézomètre haute pression
Séparateur
Clapet compte-
goutte
Bouteille d'azote
Tuyau d'entretien
Manomètre linéaire
Tuyau brasé
Joint brasé par capillarité
Connecteur large coulissant
Bouteille d'azote
Manomètre du cylindre
Pièce d'évasement
53
Procédure d'installation
Mise sous vide
Méthode de mise sous vide de la tuyauterie : utilisation de la pompe
à vide
(z. B. 1U18F S1ERA)
1. Enlevez le capuchon de l'ori ce d'entretien de la vanne à 3 voies, le capuchon
du robinet de la vanne à 2 voies et à 3 voies. Connectez ensuite l'ori ce d'entre-
tien dans la projection du tuyau de charge (bas) pour le collecteur à manomètre.
Connectez ensuite la projection du tuyau de charge (centre) pour le collecteur à
manomètre dans la pompe à vide.
2. Ouvrez la poignée du collecteur à manomètre au niveau bas. Mettez la pompe à
vide en marche. Si l’indicateur se déplace (bas), précipitez l'état de vide et véri ez
l'étape 1 à nouveau.
3. Mettez sous vide pendant plus de 15 min. Véri ez également le manomètre qui doit
indiquer -0,1MPa (-76cm Hg) sur le côté basse pression. Une fois la mise sous vide
effectuée, fermez la poignée 'Lo' de la pompe à vide. Inspectez l’indicateur et ob-
servez pendant 1 à 2 minutes. Si l’indicateur revient en dépit du serrage, reprenez
l'opération d'évasement en revenant au début de l'étape 3.
4. En tournant dans le sens antihoraire, ouvrez le robinet de la vanne à 2 voies à un
angle de 90 degrés. Environ 6 secondes plus tard, fermez la vanne à 2 voies et
inspectez a n de détecter toute fuite de gaz.
5. Pas de fuite de gaz? En cas de fuite de gaz, resserrez les pièces de connexion du tuyau. S'il n'y a plus de fuite, continuez avec l'étape 6.
Si la fuite de gaz se maintient, déchargez tout le réfrigérant de l'ori ce d'entretien. Après avoir effectué l'évasement et le vide, remplis-
sez de réfrigérant indiqué de la bouteille.
6. Détachez le tuyau de charge de l'ori ce d'entretien, ouvrez la vanne à 2 et 3 voies. Tour-
nez le robinet de la vanne dans le sens antihoraire.
7. Pour empêcher toute fuite de gaz, tournez le capuchon de l'ori ce d'entretien, le capu-
chon du robinet des vannes à 2 et 3 voies un peu au-delà du point où le couple augmen-
te brusquement.
AVERTISSEMENT :
Si le réfrigérant du climatiseur fuit, il faut vidanger tout le réfrigérant. Mettez d'abord sous vide, puis chargez le réfrigérant liquide dans le
climatiseur d'air jusqu'à la quantité indiquée sur la plaque signalétique.
Fermer
Vanne à 2 voies
Vanne à 3 voies
Vanne à 2 voies
Vanne à 3 voies
Vanne à 2 voies
Vanne à 3 voies
Soupape d'arrêt liquide
Soupape d'arrêt gaz
Collecteur de jauge (R410A)
Pompe à vide (R410A)
Ouvrir
Ori ce d'entretien 90
pendant 6 secondes
Vanne à 2 voies
Vanne à 3 voies
Vanne à 2 voies
Vanne à 3 voies
Capuchon de l'ori ce d’entretien
Capuchon du robinet de vanne
Capuchon du robinet de vanne
54
Procédure d'installation
Câblage électrique
AVERTISSEMENT !
DANGER DE BLESSURE OU DE MORT
COUPEZ L'ALIMENTATION ÉLECTRIQUE AU NIVEAU DU DISJONCTEUR OU METTEZ L'ALIMENTATION HORS TENSION
AVANT D'EFFECTUER UN BRANCHEMENT ÉLECTRIQUE.
LES BRANCHEMENTS DE MISE À LA TERRE DOIVENT ÊTRE TERMINÉS AVANT D'EFFECTUER LES BRANCHEMENTS SUR
SECTEUR.
Précautions concernant le câblage électrique
Les travaux de câblage électrique doivent être réalisés par du personnel autorisé.
Ne branchez pas plus de trois câbles au bornier. Utilisez systématiquement des cosses à poinçonner rondes avec des  ls à extrémités
isolées.
N'utilisez que des conducteurs en cuivre.
Choix de la taille des câbles d'alimentation et d'interconnexion
Choisissez les tailles des câbles et la protection du circuit dans le tableau ci-dessous. (Ce tableau présente des câbles de 20 mètres de
long, avec moins de 2% de chute de tension.)
Phase
Disjoncteur
Taille des câbles
pour l'alimentation
(minimum)
(mm
2
)
Disjoncteur de fuite à la masse
Disjoncteur à
interrupteur
(A)
Calibre du système de
protection contre les
surintensités (A)
Disjoncteur à
interrupteur (A)
Courant de fuite
(mA)
1U07BS1ERA
1U09BS1ERA
1U12BS1ERA
1U18BS1ERA
1 40 26 2.5 40 30
1U24GS1ERA 1 40 26 4.0 40 30
Si le cordon d'alimentation est endommagé, il doit être remplacé par le fabricant, un de ses agents d'entretien ou une personne quali ée.
Si le fusible de la boite de commande a fondu, remplacez-le avec le type T 25A/250V.
La méthode de câblage doit être conforme aux normes locales de câblage.
Procurez-vous le câble d'alimentation et les câbles de connexion.
Tous les câbles doivent disposer d'une certi cation d'authenti cation européenne. Pendant l'installation, lorsque les câbles de connexion
sont coupés, assurez-vous que le câble de mise à la terre soit le dernier à être coupé.
Le disjoncteur du climatiseur doit être omnipolaire et la distance entre ses deux contacts ne doit pas être inférieure à 3 mm. Ce type de
déconnexion doit être incorporé au câblage  xe.
La distance entre les deux borniers de l'unité intérieure et de l'unité extérieure ne doit pas dépasser les 5 mètres. Si cette distance est
plus importante, le diamètre du câble doit être augmenté conformément à la norme locale de câblage.
Installez un disjoncteur de fuite.
Procédure de câblage
1) Retirez les vis de pression sur le côté avant d'ôter le panneau avant dans le sens indiqué.
2) Branchez les câbles de façon adéquate sur le bornier et  xez les câbles avec un attache-câble à proximité du bornier.
3) Dirigez les câbles de façon adéquate et faites-les passer dans l'ouverture prévue pour le câblage
électrique sur le panneau latéral.
AVERTISSEMENT :
LES CÂBLES D'INTERCONNEXION DOIVENT ÊTRE CONNECTÉS COMME LE MONTRE L'ILLUSTRATION CI-DESSOUS. UN MAU-
VAIS CÂBLAGE PEUT ENDOMMAGER L'ÉQUIPEMENT.
Modèle
Élément
3
2
|
1
)
(
N
)(
L
)(
C
3
2
1
)
(
N
)
(
L
)
(
C
N
(
1
3
)
)
C(L
(
2
)
{
ALIMENTATION
POUR 07K 09K 12K
POUR 18K 24K
Unité extérieure
Vers l'unité intérieure
ALIMENTATION
Unité extérieure
Vers l'unité intérieure
Modèle
1U07BS1ERA
1U09BS1ERA
1U12BS1ERA
1U18BS1ERA 1U24GS1ERA
Câblage de
connexion
4G0.75mm
2
4G0.75mm
2
4G0.75mm
2
Câble d'alimentation 3G1.5mm
2
3G2.5mm
2
3G4.0mm
2
L
N
55
14
Haier Group
Adresse : No.1 Haier Road,Hi-tech Zone,Qingdao 266101 P.R.Chine
Contacts : Tél. : +86-532-8893-6943 ; Télécopie +86-532-8893-1010
Site Internet : www.haier.com
Dépannage d'une unité extérieure
AVERTISSEMENT !
CETTE UNITÉ VA DÉMARRER INSTANTANÉMENT, SANS QU'ELLE SOIT EN POSITION "ON" (marche), LORSQUE L'ALIMENTA-
TION ÉLECTRIQUE EST FOURNIE. ASSUREZ-VOUS DE LA METTRE EN POSITION "OFF" (ARRÊT) AVANT DE DÉBRANCHER
L'ALIMENTATION ÉLECTRIQUE POUR TOUT ENTRETIEN OU RÉPARATION.
Cette unité dispose d'une fonction de redémarrage automatique du système dés le retour de l'alimentation électrique après une coupure.
1. Avant d'effectuer un test de fonctionnement (pour tous les modèles de pompe thermique)
Assurez-vous que le disjoncteur de la source d'alimentation (interrupteur principal) de l'unité a bien été fonctionnel pendant plus de 12
heures de façon à alimenter le réchauffeur du carter avant son fonctionnement.
2. Test de fonctionnement
Faites fonctionner l'unité en continu pendant environ 30 minutes, et véri ez les éléments suivants.
Pression d'aspiration au niveau du joint de contrôle du robinet de service du tuyau de gaz.
Pression de refoulement au niveau du joint de contrôle du tuyau de refoulement du compresseur.
Différence de température entre l'air de retour et l'air fourni pour l'unité intérieure.
Intervalles d'allumage du
voyant DEL sur le
tableau
principal
Description du problème Analyse et diagnostic
1 Défaillance Eeprom Défaillance Eeprom du tableau principal extérieur
2 Défaillance IPM Défaillance IPM
4
Erreur de communication entre le tableau principal
et le module de l'injecteur Erreur de communication
SPDU
Échec de la communication pendant plus de 4 min
5 Protection contre la pression élevée Pression élevée du système supérieure à
4,15 MPa
6
Protection contre la surtension du module (uniquement
pour l'injecteur)
Protection contre la sous-tension du module (unique-
ment pour l'injecteur)
Envoyé par le module injecteur
8
Protection
température de déchargement du compres-
seur
La température de déchargement du compresseur est supé-
rieure à 110 centigrades
9 Fonctionnement anormale du moteur CC Blocage du moteur CC ou défaillance du moteur
10 Fonctionnement anormal du capteur du tuyau
Court-circuit ou fonctionnement en circuit ouvert du capteur du
tuyau
11 Défaillance de la sonde thermique d'aspiration
Lorsque le câblage du compression est incorrect ou que la
connexion est faible
12 Fonctionnement anormal du capteur ambiant extérieur
Court-circuit ou fonctionnement en circuit ouvert du capteur
ambiant extérieur
13
Fonctionnement anormal du capteur de décharge du
compresseur
Court-circuit ou fonctionnement en circuit ouvert du capteur de
décharge du compresseur
15
Erreur de communication entre l'unité intérieure et
l'unité extérieure
Échec de la communication pendant plus de 4 min
16
Manque de réfrigérant ou contrôlez la présence de
fuite au niveau de l'unité
Alarme et arrêt en cas de détection TD-tci>=75 pendant 1 min
après le démarrage du compresseur en mode refroidissement
10 min, contrôlez la présence de fuite au niveau de l'unité.
17 Défaillance inverse de la vanne à 2 voies
Alarme et arrêt en cas de détection Tm<=75 pendant 1 min
après le démarrage du compresseur en mode chauffage 10 min,
con rmez la défaillance si elle apparaît 3 fois en une heure.
18 Blocage du compresseur (uniquement pour l'injecteur) Le compresseur intérieur présente un blocage anormal
18 Erreur du circuit de sélection module MID Mauvais circuit de sélection module MID
25 Surintensité phase U du compresseur L'intensité de la phase U du compresseur est trop élevée
25 Surintensité phase V du compresseur L'intensité de la phase V du compresseur est trop élevée
25 Surintensité phase W du compresseur L'intensité de la phase W du compresseur est trop élevée
56

Transcripción de documentos

ROOM AIR CONDITIONER INSTALLATION MANUAL Contents 1U07BS1ERA 1U09BS1ERA 1U12BS1ERA Indoor/Outdoor Unit Installion Drawings 1 Safety Precautions 2 Read Before Installation 6 Installation Procedure Outdoor Unit Troubleshooting 9 14 Contenido 1U18FS1ERA Unidad interior y exterior Dibujos de extracción Precauciones de seguridad Leer antes de realizar la instalación Procedimiento instalación Unidad interior Resolución de problemas 15 16 20 23 28 Indice Unità esterna/interna Immagini per l'installazione 29 Precauzioni di sicurezza Leggere prima dell'installazione 30 34 Processo di installazione 37 42 Unità esterna Risoluzione dei problemi Table des matières 1U24GS1ERA ● Please read this manual carefully before installtion. Keep this operation manual for future reference. NO.0010535386 Unité intérieure/extérieure Schémas d'installation 43 Consignes de sécurité À lire avant l'installation Procédure d'installation Unité extérieure Dépannage 44 48 51 56 Haier Industrial Park, No.1 Haier Road, Qingdao, P.R.China EUROPEAN REGULATIONS CONFORMITY FOR THE MODELS CE All the products are in conformity with the following European provision: - Low Voltage Directive 73/23/EEC - Low Voltage Directive 2006/95/EC -Electomagnetic CompatibilitY 89/336/EEC -Electomagnetic CompatibilitY 2004/108/EC ROHS The products are fulfilled with the requirements in the directive 2002/95/EEC of the European parliament and of council on the Restriction of the use of Certain Hazardous Substances in Electrical and Electronic Equipment (EU RoHS Directive) WEEE In accordance with the directive 2002/96/CE of the European parliament, herewith we inform the consumer about the disposal requirements of the electrical and electronic products. DISPOSAL REQUIREMENTS: Your air conditioning product is marked with this symbol.This means that electrical and electronic products shall not be mixed with unsorted household waste. Do not try to dismantle the system yourself : the dismantling of the air conditioning system,treatment of the refrigerant, of oil and of other part must be done by a qualified installer in accordance with relevant local and national legislation. Air conditioners must be treated at a specialized treatment facility for reuse, recycling and recovery. By ensuring this product is disposed of correctly, you will help to prevent potential negative consequences for the environment and humen health. Please contact the installer or local authority for more information. Battery must be removed from the remote controller and disposed of separately in accordance with relevant local and nationl legislation. IMPORTANT INFORMATION REGARDING THE REFRIGERANT USED Contains fluorinated greenhouse gases covered by the Kyoto Protocol R410A 1= kg 2 2= kg 1+2= kg 1 F A B C D E This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. Do not vent into the atmosphere. Refrigerant type:R410A GWP* value:1975 GWP=global warming potential Please fill in with indelible ink, •1 the factory refrigerant charge of the product •2 the additional refrigerant amount charged in the field and • 1+2 the total refrigerant charge on the refrigerant charge label supplied with the product. The filled out label must be adhered in the proximity of the product charging port (e.g. onto the inside of the stop value cover). A contains fluorinated greenhouse gases covered by the Kyoto Protocol B factory refrigerant charge of the product: see unit name plate C additional refrigerant amount charged in the field D total refrigerant charge E outdoor unit F refrigerant cylinder and manifold for charging Indoor/Outdoor Unit Installation Drawings The models adopt HFC free refrigerant R410A. For installation of the indoor units,refer to the installation manual which was provided with the units. (The diagram shows a wall-mounted indoor unit.) Attention must be paid to the rising up of drain hose more than 15cm Optional parts for piping A Non-adhesive tape B Adhesive tape G more than 10cm Arrangement of piping directions C Saddle (L.S) with screws Connecting electric cable D for indoor and outdoor E Drain hose F Heating insulating material G Piping hole cover more than 10cm F Rear left A Rear right Left Right C Below more than 20cm more than 20cm Fixing of outdoor unit ƽ Fix the unit to concrete or block ƽ The marks from A to G in the figure are the parts numbers. ƽ The distance between the indoor unit and the floor should be more than 2m. with bolts (10mm) and nuts firmly and horizontally. ƽ When fitting the unit to wall surface, roof or rooftop, fix D a supporter surely with nails E or wires in consideration of earthquake and strong wind. ƽ If vibration may affect the more than 60cm house, fix the unit by attaching a vibration-proof mat. more than 25cm AIR OUTLET AIR INLET 4 CONNECTING PIPING AND ELECTRICAL WIRING  DRAIN HOSE Compressor(Inside of Unit) ƽ The above indoor and outdoor units’ picture is just for your reference. Please be subject to the actual product purchased. 1 WARNING CAUTION 2 Safety Precautions WARNING Have the unit professionally installed. Improper installation by an unqualified person may result in water leak, electric shock, or fire. Be sure to carefully follow each step in this handbook when installing the unit. Improper installation may result in water leak, electric shock, smoke or fire. Place the unit on a stable, level surface that withstands the weight of the unit to prevent the unit from tipping over or falling causing injury as a result. Have all electrical work performed by a licensed electrician according to the local regulations and the instructions given in this manual. Secure a circuit designated exclusively to the unit. Improper installation or a lack of circuit capacity may cause the unit to malfunction or present a risk of electric shock, smoke,and fire. Only use specified cables for wiring. Securely connect each cable, and make sure that the cables are not straining the terminals. Cables not connected securely and properly may generate heat and cause fire. Take necessary safety measures against typhoons and earthquakes to prevent the unit from falling over. Securely attach the terminal cover(panel) on the unit. If installed improperly, dust and/or water may enter the unit and present a risk of electric shock, smoke or fire. Do not make any changes or modifications to the unit. In case of problems, consult the dealer. If repairs are not made properly, the unit may leak water and present a risk of electric shock, or it may produce smoke or cause fire. Only use refrigerant R410A as indicated on the unit when installing or relocating the unit. The use of any other refrigerant or an introduction of air into the unit circuit may cause the unit to run an abnormal cycle and abnormal cycle and cause the unit to burst. WARNING Do not touch the fins on the heat exchanger with bare hands, for they are sharp and dangerous. When installing the unit in a small room, safeguard against hypoxia that results from leaked refrigerant reaching the threshold level. Consult the dealer for necessary measures to take. In the event of a refrigerant gas leak, provide adequate ventilation to the room. If leaked refrigerant gas is exposed to a heat source, noxious gases may form. When relocating the air conditioner, consult the dealer or a specialist. Improper installation may result in water leak, electric shock, or fire. With All-Fresh type air conditioners, outdoor air may be directly blown into the room upon thermo off. Take this into consideration when installing the unit. Direct exposure to outdoor air may present a health hazard, and it may also cause food items to deteriorate. After completing the service work, check for a refrigerant gas leak. If leaked gas refrigerant is exposed to a heat source such as fan heater,stove,and electric grill, noxious gases may form. Do not try to defeat the safety features of the devices, and do not change the settings. Defeating the safety features on the unit such as the pressure switch and temperature switch or using parts other than the dealer or specialist may result in fire or explosion. Only use specified parts. Have the unit professionally installed. Improper installation may cause water leak, electric shock,smoke, or fire. 3 Safety Precautions Precautions for Handling Units for Use with R410A Caution Do not use the existing refrigerant piping Use a vacuum pump with a reverse-flow check valve. If other types of valves are used, the vacuum pump oil will The old refrigerant and refrigerator oil in the existing piping flow back into the refrigerant cycle and cause the refrigerator contain a large amount of chlorine, which will cause the oil to deteriorate. refrigerator oil in the new unit to deteriorate. R410A is a high-pressure refrigerant, and the use of the Do not use the following tools that have been used with the existing piping may result in bursting. conventional refrigerants. Prepare tools that are for exclusive use with R410A. (Gauge manifold, charging hose, gas leak detector, reverse-flow check valve, refrigerant charge base,vacuum gauge, and refrigerant recovery equipment.) If refrigerant and/or refrigerant oil left on these tools are Keep the inner and outer surfaces of the pipes clean and mixed in with R410, or if water is mixed with R410A, it will free of contaminants such as sulfur, oxides, dust/dirt shaving cause the refrigerant to deteriorate. particles,oils,and moisture. Contaminants inside the refrigerant piping will cause the Since R410A does not contain chlorine, gas-leak detectors for conventional refrigerators will not work. refrigerant oil to deteriorate. Caution Store the piping to be used during installation indoors, and Do not use a charging cylinder. keep both ends of the piping sealed until immediately before The use of charging cylinder will change the composition brazing.(keep elbows and other joints wrapped in plastic.) of the refrigerant and lead to power loss. If dust, dirt, or water enters the refrigerant cycle, it may cause the oil in the unit to deteriorate or may cause the compressor to malfunction. Exercise special care when handling the tools. An introduction of foreign objects such as dust, dirt or Use a small amount of ester oil, ether oil, or alkylbenzene water into the refrigerant cycle will cause the refrigerating to coat flares and flange connections. machine oil to deteriorate. A large amount of mineral oil will cause the refrigerating machine oil to deteriorate. Use liquid refrigerant to charge the system. Charge the unit with gas refrigerant will cause the refrigerant Only use R410A refrigerant. in the cylinder to change its composition and will lead to The use of refrigerants containing chlorine(i.e. R22) will a drop in performance cause the refrigerant to deteriorate. Before Installing the Unit Caution Do not install the unit in a place where there is a possibility When installing the unit in a hospital, take necessary measures of flammable gas leak. against noise. Leaked gas accumulated around the unit may start a fire. High-frequency medical equipment may interfere with the normal operation of the air conditioning unit or the air Do not use the unit to preserve food, animals, plants, artifacts, conditioning unit may interfere with the normal operation or for other special purposes. of the medical equipment The unit is not designed to provide adepuate conditions to preserve the quality of these items. Do not use the unit in an unusual environment The use of the unit in the presence of a large amount of oil, steam, acid, alkaline solvents or special types of sprays Do not place the unit on or over things that may not get wet. may lead to a remarkable drop in performance and/or When humidity level exceeds 80% or when the drainage malfunction and presents a risk of electric shock, smoke, system is clogged, indoor units may drip water. or fire. Installation of a centralized drainage system for the outdoor The presence of organic solvents, corroded gas (such as ammonia,sulfur compounds,and acid may cause gas or unit may also need to be considered to prevent water drips water leak.) from the outdoor units. 4 Safety Precautions Before Installing (Relocating) the Unit or Performing Electric Work Caution Ground the unit. Do not connect the grounding on the unit to gas pipes,water pipes, lightning rods, or the grounding terminals of telephones. Improper grounding presents a risk of electric shock, smoke, fire, or the noise caused by improper grounding may cause the unit to malfunction. Do not spray water on the air conditioners or immerse the air conditioners in water. Water on the unit presents a risk of electric shock. Periodically check the platform on which is placed for damage to prevent the unit from falling. If the unit is left on a damaged plarform, it may topple over, causing injury. Make sure the wires are not subject to tension. If the wires are too taut, they may break or generate heat When installing draining pipes, follow the instructions in the and/or smoke and cause fire. manual, and make sure that they properly drain water so as Install a breaker for current leakage at the power source to avoid dew condensation. to avoid the risk of electric shock. If not installed properly, they may cause water leaks and Without a breaker for current leakage, there is a risk of damage the furnishings. electric shock, smoke or fire. Properly dispose of the packing materials. Use breakers and fuses (electrical current breaker, remote Things such as nails may be included in the package. switch<switch+Type-B fuse>,molded case circuit breaker) Dispose of them properly to prevent injury. with a proper current capacity. Plastic bags present a choking hazard to children. Tear up the plastic bags before disposing of them to prevent The use of large-capacity fuses, steel wire, or copper wire may damage the unit or cause smoke or fire. accidents. Before the Test Run Caution Do not turn off the power immediately after stopping the unit. Allow for at least five minutes before turning off the unit, otherwise the unit may leak water or experience other problems. Do not operate switches with wet hands to avoid electric. Do not touch the refrigerant pipes with bare hands during and immediately after operation. Depending on the state of the refrigerant in the system, certain parts of the unit such as the pipes and compressor may become very cold or hot and may subject the person to frost bites or burning. Do not operated the unit without panels and safety guards in their proper places. They are there to keep the users from injury from accidentally touching rotating, high-tempreture or highvoltage parts. Do not operate the unit without air filters. Dust particles in the air may clog the system and cause malfunction. 5 Read Before Installation Items to Be Checked (1). Verify the type of refrigerant used by the unit to be serviced. Refrigerant Type: R410A (2). Check the symptom exhibited by the unit to be serviced. Look in this service handbook for symptoms relating to the refrigerant cycle. (3). Be sure to carefully read the safety precautions at the beginning of this document. (4). If there is a gas leak or if the remaining refrigerant is exposed to an open flame, a noxious gas hydrofluoric acid may form. Keep workplace well ventilated. CAUTION Install new pipes immediately after removing old ones to keep moisture out of the refrigerant circuit. Chloride in some types of refrigerants such as R22 will cause the refrigerating machine oil to deteriorate. Necessary Tools and Materials Prepare the following tools and materials necessary for installing and servicing the unit. Necessary tools for use with R410A(Adaptability of tools that are for use with R22 and R407C). 1. To be used exclusively with R410A ( Not to be used if used with R22 or R407C ) Tools/Materials Use Notes Gauge Manifold Evacuating,refrigerant charging 5.09MPa on the High-pressure side. Charging Hose Evacuating, refrigerant charging Hose diameter larger than the concentional ones. Refrigerant Recovery Equipment Refrigerant recovery Refrigerant Cylinder Refrigerant charging Refrigerant Cylinder Charging Port Refrigerant charging Hose diameter larger than the conventional ones. Flare Nut Connecting the unit to piping Use Type-2 Flare nuts. Write down the refrigerant type. Pink in color at the top of the cylinder. 2. Tools and materials that may be used with R410 with some restrictions Tools/Materials Use Notes Gas leak detector Detection of gas leaks The ones for HFC type refrigerant may be used. Vacuum Pump Vacuum drying May be used if a reverse flow check adaptor is attached. Flare Tool Flare machining of piping Chages have been made in the flare machining dimension.Refer to the next page. Refrigerant Recovery Equipment Recovery of refrigerant May be used if designed for use with R410A. 3. Tools and materials that are used with R22 or R407C that can also be used with R410A Tools/Materials Use Vacuum Pump with a Check Valve Vacuum drying Bender Bending pipes Torque Wrench Tightening flare nuts Pipe Cutter Cutting pipes Welder and Nitrogen Cylinder Welding pipes Refrigerant Charging Meter Refrigerant charging Vacuum Gauze Checking vacuum degree Notes Only 12.70 (1/2'') and 15.88(5/8'') have a larger flare machining dimension. 4. Tool and materials that must not used with R410A Tools/Materials Charging Cylinder Use Notes Refrigerant Charging Must not be used with R410-type units. Tools for R410A must be handled with special care, and keep moisture and dust from entering the cycle. 6 Read Before Installation Piping Materials Types of Copper Pipes (Reference) Maximum Operation Pressure Applicable Refrigerants 3.4MPa R22, R407C 4.15MPa R410A Use pipes that meet the local standards. Piping Materials/Radial Thickness Use pipes made of phosphorus deoxidized copper. Since the operation pressure of the units that use R410A is higher than that of the units for use with R22, use pipes with at least the radial thickness specified in the chart below. (Pipes with a radial thickness of 0.7mm or less may not be used.) Size(mm) Size(inch) Radial Thickness(mm) 6.35 1/4'' 0.8t 9.52 3/8'' 0.8t 12.7 1/2'' 0.8t 15.88 5/8'' 1.0t 19.05 3/4'' 1.0t Type Type-O pipes Type-1/2H or Hpipes Although it was possible to use type-O for pipes with a size of up to 19.05(3/4") with conventional refrigerants, use type1/2H pipes for units that use R410A.(Type-O pipes may be used if the pipe size is 19.05 and the radial thickness is 1.2t.) The table shows the standards in Japan. Using this table as a reference, choose pipes that meet the local standards. Flare Machining (type-O and OL only) The flare machining dimensions for units that use R410A is larger than those for units that use R22 in order to increase air tightness. Flare Machining Dimension(mm) Size Dimension A R410A R22 6.35 1/4" 9.1 9.0 9.52 3/8" 13.2 13.0 12.7 1/2" 16.6 16.2 15.88 5/8" 19.7 19.4 19.05 3/4" 24.0 23.3 Dimension A External dimension of pipes If a clutch type flare tool is used to machine flares on units that use R410A, make the protruding part of the pipe between 1.0 and 1.5mm. Copper pipe gauge for adjusting the length of pipe protrusion is useful. Flare Nut Type-2 flare nuts instead of type-1 nuts are used to increase the strength. The size of some of the flare nuts have also been changed. Flare nut dimension(mm) External dimension of pipes Size Dimension B R410A(Type2) R22(Type1) 17.0 17.0 3/8" 22.0 22.0 1/2" 26.0 24.0 15.88 5/8" 29.0 27.0 19.05 3/4" 36.0 36.0 6.35 1/4" 9.52 12.7 Dimension B The table shows the standards in Japan. Using this table as a reference, choose pipes that meet the local standards. 7 8 NO Air outlet Wind direction Cushion rubber 4.Installation dimension(Unit:mm) * 9 1. 1U07BS1ERA 1U09BS1ERA 1U12BS1ERA 1U18FS1ERA 1U24GS1ERA 2. Connection of pipes ƽ To bend a pipe, give the roundness as large as possible not to crush the pipe , ƽ ƽ and the bending radius should be 30 to 40 mm or longer. Connecting the pipe of gas side first makes working easier. The connection pipe is specialized for R410A. Half union Spanner Forced fastening without careful centering may damage the threads and cause a leakage of gas. Flare nut Torque wrench Pipe Diameter(ǿ) Fastening torque Liquid side6.35mm(1/4") 18N.m Liquid/Gas side9.52mm(3/8") 42 N.m Gas side 12.7mm(1/2") 55N.m Gas side 15.88mm(5/8") 60 N.m Be careful that matters, such as wastes of sands,water,, etc. shall not enter the pipe. CAUTION The standard pipe length is C m. If it is over D m, the function of the unit will be affected. If the pipe has to be lengthened, the refrigerant should be charged, according to E g/m. But the charge of refrigerant must be conducted by professional air conditioner engineer. Before adding additional refrigerant, perform air purging from the refrigerant pipes and indoor unit using a vacuum pump,then charge additional refrigerant. Outdoor unit Indoor unit B B A A Indoor unit Outdoor unit ● ● Outdoor unit B A Oil trap Indoor unit ● ● Max.Elevation: Amax In case the elevation A is more than 5m, oil trap shoud be installed every 5~7 Max. Length: Bmax In case the pipe length B is more thanDm, the refrigerant should be charged, according to E g/m. 10 11 (e.g.1U18FS1ERA) 12 1U07BS1ERA 1U09BS1ERA 1U12BS1ERA 1U18FS1ERA 1U24GS1ERA T 25A/250V. FOR 18K 24K Outdoor unit FOR 07K 09K 12K Outdoor unit 1(N) 2 (L) To Indoor unit 3 (C) 1(N) 2 (L) 3 (C) To Indoor unit Model Connecting wiring { N POWER 4G0.75mm 1U18FS1ERA 2 4G0.75mm 1U24GS1ERA 2 4G0.75mm 2 L 1(N ) 2 (L) 3 (C ) ^ POWER 1U07BS1ERA 1U09BS1ERA 1U12BS1ERA Power cable 13 3G1.5mm2 3G2.5mm2 3G4.0mm2 Outdoor Unit 1 2 4 15 5 6 8 110 9 10 11 When the The wiring of compressor is wrong or the connection is poor Suction temperature sensor failure 12 13 15 16 Lack of refrigerant Check if there is leakage in the unit. m 17 18 19 25 25 25 Haier Group Address:No.1 Haier Road,Hi-tech Zone,Qingdao 266101 P.R.ChiQD Contacts: TEL +86-532-8893-6943;FAX +86-532-8893-1010 Website: www.haier.com 14 15 Haier Industrial Park, No.1 Haier Road, Qingdao, República Popular China CONFORMIDAD DE LOS MODELOS SEGÚN LAS NORMATIVAS EUROPEAS INFORMACIÓN IMPORTANTE ACERCA DEL REFRIGERANTE UTILIZADO CE Todos los productos satisfacen los requisitos de las siguientes normas europeas: - Directiva de baja tensión, 73/23/CEE - Directiva de baja tensión, 2006/95/CE - Compatibilidad electromagnética 89/336/CEE - Compatibilidad electromagnética 2004/108/CE Contiene gases fluorados de efecto invernadero regulados por el Protocolo de Kioto. R410A 1= kg 2 2= kg 1+2= kg 1 ROHS Los productos satisfacen los requisitos de la directiva 2002/95/ CEE establecida por el Parlamento Europeo y el Consejo sobre restricciones a la utilización de determinadas sustancias peligrosas en aparatos eléctricos y electrónicos (Directiva RoHS UE). WEEE De acuerdo con la directiva 2002/96/CE del Parlamento Europeo, se informa al consumidor acerca de los requisitos de eliminación de productos eléctricos y electrónicos. REQUISITOS DE ELIMINACIÓN: Su aparato de aire acondicionado ha sido marcado con este símbolo, el cual significa que los productos de tipo eléctrico y electrónico no deben mezclarse con residuos domésticos sin clasificar. No intente desmontar el sistema personalmente: tanto el desmontaje del sistema de aire acondicionado como la manipulación del refrigerante, el aceite y cualquier otro componente deben ser llevados a cabo por un instalador capacitado, de acuerdo con la legislación local y nacional al efecto. Los aparatos de aire acondicionado deben ser manipulados en instalaciones de manipulación especializadas y aptas para su reutilización, reciclado y recuperación. Al garantizar la correcta eliminación de este producto, usted contribuirá a evitar las posibles consecuencias negativas que podría provocar sobre el medioambiente y la salud humana. Póngase en contacto con el instalador o la autoridad local pertinente si desea obtener más información. Las pilas deben ser extraídas del mando a distancia y eliminadas de forma independiente, de acuerdo con la legislación local y nacional al efecto. F A B C D E Este producto contiene gases fluorados de efecto invernadero regulados por el Protocolo de Kioto. No los libere libremente a la atmósfera. Tipo de refrigerante: R410A Valor GWP*: 1975 GWP = Potencial de contribución al calentamiento global Escriba con tinta indeleble: •1 la carga de refrigerante que contiene el producto de fábrica •2 la cantidad de refrigerante adicional cargada durante la instalación y • 1+2 la carga total de refrigerante en la etiqueta de carga de refrigerante suministrada con el producto. Una vez escritos los datos correspondientes, la etiqueta deberá adherirse cerca de la conexión de carga del producto (por ejemplo, sobre la parte interna de la cubierta de la válvula de retención). A Contiene gases fluorados de efecto invernadero regulados por el Protocolo de Kioto. B Carga de refrigerante que contiene el producto de fábrica: consulte la placa de características de la unidad. C Cantidad de refrigerante adicional cargada durante la instalación. D Carga total de refrigerante. E Unidad exterior. F Botella de refrigerante y colector de carga. Dibujos de instalación de las unidades interior y exterior Los modelos cumplen la norma R410A sobre refrigerantes libres de HFC. Para obtener información sobre la instalación de las unidades interiores, consulte el manual de instalación proporcionado con las mismas. (El diagrama muestra una unidad interior montada en pared.) Debe prestarse atención a la pendiente del manguito de drenaje más de 15 cm Componentes opcionales para la instalación de los tubos A Cinta no adhesiva B Cinta adhesiva G más de 10 cm Conexión de cable eléctrico para inte- D rior y exterior E Manguito de drenaje F Material aislante de calor G Cubierta de orificio de entubación Organización de la dirección de los tubos Izquierda C Soporte (L.S) con tornillos más de 10 cm Izquierda trasera F A Derecha trasera Derecha C Inferior más de 20 cm más de 20 cm Fijación de la unidad exterior ● Las marcas comprendidas entre A y G en la ilustración corresponden a los números de las piezas. ● La distancia entre la unidad interior y el suelo debe ser superior a 2 m. D E más de 60 cm ● Fije la unidad a un bloque de cemento con pernos (10 mm) y tuercas firme y horizontalmente. ● Si instala la unidad sobre una pared, techo o tejado, instale un soporte con clavos o cables considerando la posibilidad de terremotos o viento fuerte. ● Si la vibración afectase a la casa, fije la unidad instalando una alfombra de absorción de vibraciones. más de 25 cm SALIDA DE AIRE ENTRADA DE AIRE TUBOS DE CONEXIÓN Y CABLEADO ELÉCTRICO 4  4 MANGUITO DE DRENAJE Compresor (dentro de la unidad) ● La imagen anterior de las unidades interior y exterior solamente sirve de referencia. Remítase al producto real adquirido. 15 Precauciones de seguridad Lea detenidamente la siguiente información para poner en funcionamiento el aire acondicionado de forma correcta. A continuación se enumeran tres tipos de precauciones de seguridad y sugerencias. ADVERTENCIA Si realiza operaciones de forma incorrecta, pueden producirse graves consecuencias, como la muerte o graves lesiones. PRECAUCIÓN Si realiza operaciones de forma incorrecta, pueden producirse lesiones o daños en la máquina; en algunos casos pueden producirse graves consecuencias. INSTRUCCIÓN: Esta información puede asegurar el correcto funcionamiento de la máquina. Símbolos utilizados en las ilustraciones : indica una acción que se debe evitar. : indica que es obligatorio seguir las instrucciones importantes. : indica un componente que se debe conectar a tierra. : atención a las descargas eléctricas (este símbolo se muestra en la etiqueta de la unidad principal.) Después de leer este manual, entréguesela a aquellas personas que utilicen a la unidad. El usuario de esta unidad debe tener este manual a mano y ponerlo a disposición de quienes repararán o reubicarán la unidad. Asimismo, debe ponerlo a disposición de los nuevos usuarios cuando el producto cambio de manos. Asegúrese de seguir estas importantes precauciones de seguridad. ADVERTENCIA ● Si se producen fenómenos anormales (por ejemplo, olor a quemado), corte la Desactivar fuente de alimentación inmediatamente, y póngase en contacto con el distribuidor para averiguar el método de manipulación. En dicho caso, si sigue utilizando el aire acondicionado, éste resultará dañado, y pueden producirse descargas eléctricas o peligro de incendio. ● Tras un largo período de tiempo sin utilizar el aparato de aire acondicionado, debe comprobar la base para ver si se han producido daños. Si la base dañada no se repara, es posible que la unidad se caiga y provoque accidentes. ● No desmonte la boca de salida de la unidad exterior. La exposición del ventilador es muy peligrosa, ya que puede provocar lesiones en las personas. ● Cuando necesite mantenimiento y reparación, llame al distribuidor para gestionarlo. Si el mantenimiento y la reparación se realizan de forma incorrecta podrían producirse fugas de agua, descargas eléctricas y peligro de incendio. ADVERTENCIA ● No se pueden colocar cosas o personas sobre la unidad exterior. La caída de cosas o personas puede provocar accidentes. ● No ponga en funcionamiento el aire acondicionado con las manos mojadas. De lo contrario, se producirán descargas eléctricas. ● Utilice sólo fusibles del tipo correcto. No se puede utilizar ningún cable ni otro material que sustituya al fusible, de lo contrario, se producirán fallos o incendio. ● Utilice el tubo de descarga correctamente para asegurar la eficacia de la descarga. Si utiliza el tubo de forma incorrecta podrían producirse fugas de agua. ● Interruptor de circuito de fugas eléctricas instalado. Provoca descargas eléctricas con facilidad sin el interruptor de circuito. ● El aire acondicionado no puede instalarse en lugares con gases inflamables, ya que podrían provocar peligro de incendio. El distribuidor es el responsable de la instalación del aparato de aire acondicionado. Si la instalación se realiza de forma incorrecta podrían producirse fugas de agua, descargas eléctricas y peligro de incendio. ● Llame al distribuidor para tomar medidas que eviten fugas de refrigerante. Si el aparato de aire acondicionado está instalado en una habitación pequeña, asegúrese de tomar las medidas necesarias para evitar asfixia, incluso en caso de fuga de refrigerante. ● Cuando el aire acondicionado se instala o se vuelve a instalar, el distribuidor en el responsable de dichas tareas. Si la instalación se realiza de forma incorrecta podrían producirse fugas de agua, descargas eléctricas y peligro de incendio. ● Conecte el cable de conexión a tierra. El cable de conexión a tierra no debe conectarse al tubo de gas, tubo de agua, barra pararrayos o línea telefónica. Si la conexión a tierra se realiza de manera incorrecta, podrían producirse descargas. 16 Puesta a tierra Precauciones de seguridad ADVERTENCIA ● Asegúrese de seguir atentamente todos los pasos de este ● La unidad debe ser instalada por un profesional. manual cuando instale la unidad. La instalación inadecuada por una persona no cualificada puede La instalación inadecuada puede provocar fugas de agua, deprovocar fugas de agua, descargas eléctricas o un incendio. scargas eléctricas, humo o incendios. ● Coloque la unidad en una superficie estable y nivelada que soporte el peso de la misma para impedir que se vuelque o se ● Encomiende todos los trabajos eléctricos a un electricista profesional de forma que se cumplan las normativas locales y las caiga, evitando así lesiones personales. instrucciones proporcionadas en este manual. Fije un circuito designado exclusivamente a la unidad. ● Utilice solamente los cables especificados para el cableado. CoLa instalación inadecuada o la falta de capacidad de los circuitos necte de forma segura todos los cables y asegúrese de que los puede hacer que la unidad no funcione correctamente o presenmismos no tensan los terminales. Los cables que no se conecten de forma correcta y segura, puete riesgos de descargas eléctricas, humo e incendio. den generar calor y provocar un incendio. ● Acople de forma segura la cubierta de terminales (panel) a la unidad. ● Tome las medidas de seguridad necesarias contra tifones y terreSi se instala incorrectamente, puede entrar polvo y/o agua en la motos para evitar que la unidad se caiga. unidad lo que supone un riesgo de descargas eléctricas, humo o incendio. ● No realice ningún cambio o modificación a la unidad. Si surgen problemas, consultar distribuidor. Si las reparaciones no se realizan correctamente, se pueden ● Utilice únicamente el refrigerante R410A tal y como se indica en la unidad cuando la instale o reubique. producir fugas de agua en la unidad, lo que supone un riesgo El uso de cualquier otro refrigerante o la penetración de aire en de descargas eléctricas. También se puede producir humo o un el circuito de la unidad puede provocar que ésta funcione en un incendio. ciclo anómalo, lo que puede provocar que se queme. ADVERTENCIA ● No toque las aletas del intercambiador de calor con las manos al ● Cuando instale la unidad en una sala pequeña, protéjase contra descubierto ya que están afiladas y son peligrosas. la hipoxia causada por el refrigerante fugado que alcance el nivel umbral. ● En el caso de que haya una fuga de gas refrigerante, proporcioConsulte al distribuidor para tomar las medidas necesarias. ne la ventilación adecuada a la sala. ● Cuando reubique el aparato de aire acondicionado, consulte al Si el gas refrigerante fugado queda expuesto a una fuente de proveedor o a un especialista. calor, se pueden producir gases nocivos. La instalación inadecuada puede provocar fugas de agua, de● Con aparatos de aire acondicionado de tipo All-Fresh, el aire exscargas eléctricas o incendios. terior se puede dirigir directamente dentro de la sala. Tenga esto ● Después de completar las tarea de servicio, compruebe si queen cuenta cuando instale la unidad. La exposición directa al aire de exterior puede suponer un riesgo dan fugas de gas refrigerante. Si el gas refrigerante fugado queda expuesto a una fuente de para la salud así como causar deterioro en productos alimenticalor, como por ejemplo un calefactor, una estufa o una parrilla cios. eléctrica, se pueden producir gases nocivos. ● No pase por alto las instrucciones de seguridad de los dispositivos y no cambie la configuración. ● Utilice solamente las piezas especificadas. Si pasa por alto las instrucciones de seguridad de la unidad, La unidad debe ser instalada por un profesional. La instalación como por ejemplo el cambio de presión y el cambio de temperainadecuada puede provocar fugas de agua, descargas eléctricas, tura, o utiliza piezas distintas a las proporcionadas por el proveehumo o incendios. dor o el especialista, se pueden producir un incendio o explosión. 17 Precauciones de seguridad Precauciones para manipular unidades para utilizarse con R410A Precaución Utilice una bomba de vacío con una válvula de comprobación de No utilizar el tubo refrigerante asistente flujo inverso. ● El refrigerante usado y el aceite del refrigerador de los tubos existentes contiene una gran cantidad de cloro que deteriorará el ● Si se utilizan otros tipos de válvula, el aceite de la bomba de vacío retrocederá al circuito refrigerante y provocará el deterioro aceite del refrigerador de la nueva unidad. ● R410A es un refrigerante de alta presión y el uso de los tubos del aceite del refrigerador. existentes puede dar lugar a reventones. No utilice las siguientes herramientas que hayan sido utilizadas con los refrigerantes convencionales. Prepare las herramientas que vaya utilizar exclusivamente con R410A. (Colector, manguera de carga, detector de fuga de gas, válvula de comprobación de flujo inverso, base de carga del refrigerante, Mantenga las superficies interior y exterior de los tubos limpias y calibrador de vacío y equipo de recuperación de refrigerante.) ● Si y el refrigerante y/o el aceite refrigerante residual de estas sin contaminantes como el sulfuro, óxidos, partículas de polvo o herramientas se mezcla con el refrigerante R410A, éste se detesuciedad, aceites y humedad. ● Los contaminantes que se encuentran dentro del tubo refrigeranriorará. ● Dado que el refrigerante R410A no contiene cloro, los detectores te provocarán el deterioro del aceite refrigerante. de fuga de gas para refrigeradores convencionales no funcionarán. Precaución Almacene los tubos que se van a utilizar durante la instalación de No utilice una botella carga. ● El uso de una botella de carga cambiará la composición del refrilas unidades interiores y mantenga ambos extremos de los tubos sellados hasta el preciso instante en el que se suelden. (Mantenga gerante y provocará pérdida de potencia. los ángulos y otras juntas envueltas en plásticos.) ● Si entra polvo, suciedad o agua en el circuito refrigerante, el aceite de la unidad podría deteriorarse o provocar averías en el compresor. Preste especial atención cuando manipule las herramientas. ● Si se introducen objetos extraños como polvo, sociedad o agua en el circuito refrigerante, el aceite de la máquina refrigerante se Utilice una pequeña cantidad de aceite de ésteres, aceite de éter o deteriorará. alcalibenceno para recubrir abocinados y uniones de bridas. ● Una gran cantidad de aceite mineral deteriorará el aceite de la máquina refrigerante. Utilice solamente refrigerante R410A. Utilice refrigerante líquido para cargar el sistema. ● El uso de refrigerantes que contengan cloro (por ejemplo R22) ● Si carga la unidad con refrigerante gaseoso el refrigerante de deteriorará el refrigerante. la botella cambiará su composición y provocará una pérdida de rendimiento. Antes de utilizar la unidad Precaución No instale la unidad en lugares donde haya riesgo de fuga de gas inflamable. ● El gas fugado acumulado alrededor de la unidad puede desencadenar un incendio. Cuando instale la unidad en un hospital, tome las medidas necesarias para eliminar el ruido. ● Los equipos médicos de alta frecuencia pueden interferir en el funcionamiento normal de la unidad de aire acondicionado o viceversa. No utilice la unidad para conservar comida, animales, plantas, artefactos o para otras finalidades especiales. ● La unidad no está diseñada para proporcionar condiciones adecuadas para conservar la calidad de estos elementos. No utilice la unidad en un entorno inusual. Lo coloque la unidad sobre objetos que no se puedan mojar. ● El uso de la unidad en presencia de una gran cantidad de aceite, ● Cuando el nivel de humedad supere el 80% o cuando el sistema vapor, ácido, disolventes alcalinos o tipos especiales de espray de drenaje se atasque, las unidades interiores pueden gotear puede producir una pérdida considerable de rendimiento y/o aveagua. rías, además del riesgo existente de descargas eléctricas, humo ● La instalación de un sistema de drenaje centralizado para la unio incendio. dad exterior también debe tenerse en cuenta para evitar el goteo ● La presencia de disolventes orgánicos o gas corroído (como de agua de las unidades exteriores. amoniaco, compuestos de azufre y ácido) puede provocar fugas de agua o gas.) 18 Precauciones de seguridad Antes de instalar (reubicar) la unidad o realizar tareas eléctricas Precaución Conecte la unidad a tierra. ● No conecte las tomas de tierra de la unidad a tubos de gas, tubos de agua, pararrayos o a los terminales de conexión a tierra de teléfonos. La conexión inadecuada a tierra supone riesgos de descargas eléctricas, humo, incendio. Además, el ruido causado por una conexión de este tipo puede provocar averías en la unidad. Asegúrese de que los cables no están tensos. ● Si los cables están demasiado tirantes, se pueden romper o generar calor y/o humo, lo que puede provocar un incendio. No rocíe agua en aparatos de aire acondicionado mi sumerja dichos aparatos en agua. ● La presencia de agua sobre la unidad supone un riesgo de descargas eléctricas. Compruebe periódicamente la plataforma sobre la que se coloca la unidad para ver si existen daños y evitar así que dicha unidad se caiga. ● Si la unidad se deja en una plataforma dañada, puede volcarse y provocar lesiones personales. Cuando instale tubos de drenaje, siga las instrucciones del manual Instale un disyuntor para fugas de corriente en la fuente de alimen- y asegúrese de que desaguan el agua correctamente para evitar tación para evitar el riesgo de descargas eléctricas. condensación. ● Si no cuenta con un disyuntor para fugas de corriente, existe el ● Si la instalación no se realiza correctamente, se pueden producir riesgo de descargas eléctricas, humo o incendio. fugas de agua y el mobiliario puede resultar dañado. Utilice disyuntores y fusibles (disyuntor de corriente eléctrica, conmutador remoto <conmutador+fusible de Tipo-B>, disyuntor de circuito o con carcasa moldeada) con una capacidad de corriente adecuada. ● El uso de fusibles de gran capacidad, cables de acero o cables de cobre puede dañar la unidad o provocar humo o un incendio. Deshágase adecuadamente de los materiales de embalaje. ● El embalaje puede incluir objetos como, por ejemplo, clavos. Deshágase de ellos adecuadamente para evitar lesiones personales. ● Las bolsas de plástico suponen un riesgo de asfixia para los niños. Despedace las bolsas de plástico antes de deshacerse de ellas para evitar accidentes. Antes de ejecutar las comprobaciones Precaución Para evitar descargas eléctricas, no utilice los conmutadores con las manos mojadas. No toque los tubos refrigerantes con las manos al descubierto mientras el aparato está en funcionamiento o inmediatamente después de haberlo estado. ● Dependiendo del estado del refrigerante del sistema, ciertas partes de la unidad como los tubos y el compresor, pueden alcanzar una temperatura muy baja o caliente lo que puede provocar quemaduras a las personas. No desconecte alimentación inmediatamente después de detener la unidad. ● Deje que transcurran al menos cinco minutos antes de apagar la unidad. De lo contrario dicha unidad puede tener fugas de agua u otros problemas. No utilice la unidad sin que los paneles y las protecciones de seguridad estén colocados en sus lugares correctos. ● Están ahí para evitar lesiones a los usuarios producidas por toNo ponga en funcionamiento la unidad sin los filtros de aire. car accidentalmente piezas giratorias, con elevada temperatura ● Las partículas de polvo del aire pueden obturar el sistema y causar averías. o alto voltaje. 19 Leer antes de realizar la instalación Elementos que se deben comprobar (1). Compruebe el tipo de refrigerante utilizado por la unidad que se va a revisar. Tipo de refrigerante: R410A (2). Compruebe los síntomas que presenta la unidad que se va a revisar. Busque en el manual de servicio los síntomas relacionados con el circuito refrigerante. (3). Asegúrese de leer atentamente las precauciones de seguridad que se encuentran al principio de este documento. (4). Si hay fuga de gas o si el refrigerante restante se expone a una llama viva, se puede formar ácido fluorhídrico. Mantenga el lugar de trabajo bien ventilado. PRECAUCIÓN ● Instale los tubos nuevos inmediatamente después de quitar los usados para mantener la humedad fuera del circuito refrigerante. ● El cloruro en algunos tipos de refrigerantes como el R22 deteriorarán el aceite de la máquina refrigerante. Herramientas y materiales necesarios Preparar las siguientes herramientas y materiales para instalar y reparar la unidad. Herramientas necesarias para utilizar con R410A (disponibilidad de herramientas para utilizar con R22 y R407C). 1. Para utilizarse exclusivamente con R410A (no se deben utilizar con R22 o R407C) Herramientas y materiales Uso Notas Colector Evacuación, carga del refrigerante 5,09 MPa en alta presión. Manguera de carga Evacuación, carga del refrigerante Diámetro de la manguera mayor que los convencionales. Equipo de recuperación del refrigerante Recuperación del refrigerante Botella de refrigerante Carga de refrigerante Anote el tipo de refrigerante. Color rosa la parte superior de la botella. Puerto de carga de la botella de refrigerante Carga de refrigerante Diámetro de la manguera mayor que los convencionales. Tuerca cónica Conectar la unidad a los tubos Usar las tuercas cónicas de tipo 2. 2. Herramientas y materiales que se pueden utilizar con R410 con algunas restricciones Herramientas y materiales Uso Notas Detector de fuga de gas Detección de fugas de gas Se pueden usar los adecuados para el refrigerante de tipo HFC. Bomba de vacío Secado en vacío Se puede utilizar si se acopla un adaptador de comprobación de flujo inverso. Herramienta de conicidad Maquinaria de conicidad de tubos Se han realizo cambios en la dimensión de la maquinaria de conicidad. Consulte la página siguiente. Equipo de recuperación del refrigerante Recuperación de refrigerante Se puede utilizar si está pensado para utilizarse con R410A. 3. Herramientas y materiales que se van a utilizar con R22 o R407C que también pueden utilizarse con R410A Herramientas y materiales Uso Notas B o m b a d e v a c í o c o n v á l v u l a d e Secado en vacío comprobación Curvadora Doblar tubos Llave dinamométrica Apretar tuercas cónicas Cortatubos Cortar tubos Soldador y botella de nitrógeno Soldar tubos Medidor de carga de refrigerante Carga de refrigerante Malla de vacío Comprobar el grado de vacío 12,70 (1/2'') y Solamente conicidad más grande. 15,88 (5/8'') tienen una dimensión de maquinaria de 4. Herramientas y materiales que no se deben utilizar con R410A Herramientas y materiales Uso Notas Botella de carga Carga de refrigerante No se debe utilizar con unidades de tipo R410. Las herramientas para R410A se deben utilizar con extremo cuidado y se debe impedir que la humedad y el polvo entre en el circuito. 20 Leer antes de realizar la instalación Materiales para tubos Tipos de tubos de cobre (referencia) Presión de funcionamiento máxima Refrigerantes aplicables 3,4 MPa R22 y R407C 4,15 MPa R410A ● Usar tubos que cumplen los estándar locales. Materiales para tubos/Grosor del radio Utilice tubos fabricados con cobre desoxidado con fósforo. Dado que la presión de funcionamiento de las unidades que utilizan R410A es superior a la de las unidades que utilizan R22, emplee tubos con al menos el grosor radial especificado en el gráfico siguiente. (No se deben utilizar tubos con un grosor radial de 0,7 mm o menos.) Tamaño (mm) Tamaño (pulgadas) Grosor radial (mm) 6.35 1/4'' 0,8t 9.52 3/8" 0,8t 12.7 1/2" 0,8t 15.88 5/8" 1,0t 19.05 3/4" 1,0t Tipo Tuberías de tipo O Tubos de tipo 1/2H o H ● Aunque es posible utilizar el tipo O para tubos con un tamaño de hasta 19,05 (3/4") con refrigerantes convencionales, utilice tubos de tipo 1/2H para unidades que utilicen R410A. (Se pueden utilizar tubos de tipo-O si el tamaño del tubo es 19.05 y el grosor radial es de 1,2 t.) ● La tabla muestra los estándares de Japón. Utilice esta tabla como referencia y elija tubos que cumplan los estándares locales. Maquinaria de conicidad (solamente para el tipo O y OL) Las dimensiones de la máquina de conicidad para unidades que utilizan R410A son mayores que las de las unidades que utilizan R22 para aumentar la hermeticidad del aire. Dimensiones de la máquina de conicidad (mm) Tamaño Dimensión A R410A R22 6.35 1/4'' 9.1 9.0 9.52 3/8" 13.2 13.0 12.7 1/2" 16.6 16.2 15.88 5/8" 19.7 19.4 19.05 3/4" 24.0 23.3 Dimensión A Dimensiones externas de los tubos Si una herramienta de comicidad de tipo acoplamiento se utiliza para realizar la conicidad en unidades que usan R410A, haga que la parte que sobresale del tubo tenga un tamaño comprendido entre 1,0 y 1,5 mm. El calibre de tubos de cobre es útil para ajustar la longitud de la prominencia del tubo. Tuerca cónica Se utilizan tuercas cónicas de tipo 2 en lugar de las de tipo 1 para aumentar la fuerza. El tamaño de algunas de las tuercas cónicas también ha cambiado. Dimensiones de la máquina de conicidad (mm) Dimensiones externas de los tubos Tamaño Dimensión B R410A (Tipo 2) R22 (Tipo 1) 6.35 1/4'' 17.0 17.0 9.52 3/8" 22.0 22.0 12.7 1/2" 26.0 24.0 15.88 5/8" 29.0 27.0 19.05 3/4" 36.0 36.0 Dimensión B ● La tabla muestra los estándares de Japón. Utilice esta tabla como referencia y elija tubos que cumplan los estándares locales. 21 Leer antes de realizar la instalación Prueba de hermeticidad del aire El método convencional NO cambia. Tenga en cuenta que el detector de fugas de refrigerante para R22 o R407C no puede detectar fugas de R410A. Detector de fugas de R22 o R407C Antorcha de haluro Elementos que se deben tener muy en cuenta: 1. Presurice el equipo con nitrógeno hasta la presión de diseño y, a continuación, evalúe la hermeticidad del aire de dicho equipo teniendo en cuenta las variaciones de temperatura. 2. Cuando investigue las ubicaciones de las fugas utilizando un refrigerante, asegúrese de usar R410A. 3. Asegúrese de que R410A se encuentran estado líquido cuando lo cargue. Razones: 1. El uso de oxígeno cómo gas presurizado puede provocar explosiones. 2. La carga con gas R410A cambiará la composición del refrigerante restante de la botella, por lo que no podrá utilizarlo. Vacío 1. Bomba de vacío con válvula de comprobación Se necesita una bomba de vacío con válvula de comprobación para evitar que el aceite de dicha bomba retroceda y se introduzca en el circuito refrigerante cuando la alimentación de la bomba de vacío se apague (error de alimentación). También es posible acoplar una válvula de comprobación a la bomba de vacío real después. 2. Grado estándar de vacío para la bomba de vacío Utilice una bomba que alcance 65 Pa o menos después de 5 minutos de funcionamiento. Además, asegúrese de utilizar una bomba de vacío en la que se hayan realizado todas las tareas de mantenimiento convenientemente y esté engrasada utilizando el aceite especificado. Si no se han realizado las tareas de mantenimiento adecuadas en la bomba de vacío, el grado de vacío puede ser demasiado bajo. 3. Precisión necesaria del indicador de vacío Utilice un indicador de vacío que pueda medir hasta 650Pa. No utilice un colector general ya que no puede medir un grado de vacío de 650 Pa. 4. Tiempo de evacuación Evacuó el equipo durante 1 hora después de alcanzar 650 Pa. Después de la evacuación, deje el equipo en reposo durante 1 hora y asegúrese de que el vacío no se pierde. 5. Procedimiento de funcionamiento cuando la bomba de vacío se detiene Para evitar flujo de retorno del aceite de la bomba de vacío, abra la válvula de seguridad del lado de la bomba de vacío o afloje la manguera de carga para retraer el aire antes de detener el funcionamiento. Debe utilizar el mismo procedimiento cuando utilice una bomba de vacío con válvula de comprobación. Carga de refrigerante R410A debe estar en estado líquido durante la carga. Razones: R410A es un refrigerante pseudo-azeotrópico (punto de ebullición R32=-52 OC, R125=-49 OC) y se puede manipular más o menos de la misma forma que el R22; sin embargo, asegúrese de rellenar el refrigerante desde el lado del líquido. Si lo hace desde el lado del gas la composición del refrigerante cambiará en la botella. Nota ● En el caso la botella con sifón, el R410A líquido se carga sin poner la botella boca abajo. Compruebe el tipo de botella antes de realizar la carga. Remedios que se deben tomar en caso de fuga del refrigerante Si el refrigerante se fuga, debe cargar más refrigerante. (Agregue el refrigerante desde el lado del líquido) Características de los refrigerantes convencionales y nuevos ● Debido a que el R410A es un refrigerante azeotrópico simulado, se puede manipular prácticamente de la misma manera que un refrigerante sencillo, como por ejemplo el R22. Sin embargo, si el refrigerante se retira en la fase de gas, la composición del refrigerante de la botella cambiará. ● Quite el refrigerante en la fase líquida. Si el refrigerante se fuga, puede agregar más refrigerante. 22 Procedimiento instalación Instalación de la unidad exterior Borde 1. Accesorios "Borde" para proteger los cables eléctricos de un borde de apertura. 2. Selección del lugar de instalación Seleccione un lugar de instalación que cumpla con las siguientes condiciones y, al mismo tiempo, obtenga un consentimiento del cliente o del usuario. ● Coloque la unidad en un lugar en el que circule el aire. ● Coloque la unidad en un lugar alejado de radiaciones de calor emitidas por otras fuentes de calor. ● Coloque la unidad en un lugar en el que pueda descargarse el agua de drenaje. ● Coloque la unidad en un lugar en el que el ruido y el aire caliente no molesten a los vecinos. ● Coloque la unidad en un lugar en el que no haya grandes nevadas durante el invierno. ● Coloque la unidad en un lugar en el que no existan obstáculos en la entrada o salida de aire. ● Coloque la unidad en un lugar en el que la salida de aire no esté expuesta a fuertes vientos. ● La instalación no se realizará correctamente si la unidad está rodeada por los cuatro lados. Debe dejar 1 m o más de espacio por encima de la unidad. ● No monte las lamas en lugar en el que exista la posibilidad de que se produzca un cortocircuito. ● Al instalar varias unidades, compruebe que existe espacio de aspiración suficiente para evitar cortocircuitos. Requisito de espacio abierto alrededor de la unidad Entrada de aire Entrada de aire Distancia Caso I Caso II Caso III L1 abrir abrir 500 mm L2 300 mm 300 mm abrir L3 150 mm 300 mm 150 mm Nota: (1) Fije las piezas con los tornillos. NO (2) No permita que el fuerte viento Salida de entre directamente en el orificio aire Dirección del de flujo de aire de salida. viento (3) Debe dejar una distancia de un metro desde la parte superior de la unidad. (4) No bloquee los alrededores de la unidad con objetos. (5) Si la unidad exterior se instala en un lugar expuesto al viento, instálela de forma que la rejilla de salida de aire NO apunte en la dirección del viento. (Espacio para mantenimiento) Salida de aire 3. Instalación de la unidad exterior Fije la unidad a la base de la forma adecuada en función del estado del lugar de la instalación. Consulte para ello la siguiente información. ● Deje suficiente espacio para fijar la base de hormigón mediante los pernos de anclaje. ● Coloque la base de hormigón a una profundidad suficiente. ● Instale la unidad de manera que el ángulo de inclinación sea inferior a 3 grados. ● Prohibido colocar la unidad en el suelo directamente. Asegúrese de que hay espacio suficiente cerca del orificio de drenaje en la placa inferior, lo que garantizará que el agua se desagua sin problemas. Unidad Goma amortiguadora Base de hormigón Perno de anclaje 4. Dimensiones de instalación (unidad: mm) Terminal del cableado de alimentación Orificio de distribución del cableado de alimentación 23 Modelo AN D AL L1 L2 L3 1U07BS1ERA 780 245 540 500 140 256 1U09BS1ERA 780 245 540 500 140 256 1U12BS1ERA 780 245 540 500 140 256 1U18FS1ERA 810 288 688 583 113.5 319.5 1U24GS1ERA 860 308 730 633 113.5 340 Procedimiento instalación Conexión de los tubos 1. Tamaño de los tubos 1U07BS1ERA 1U09BS1ERA 1U12BS1ERA 1U18FS1ERA 1U24GS1ERA Tubo de líquido 6,35x0,8 mm Tubo de gas 9,52x0,8 mm Tubo de líquido 6,35x0,8 mm Tubo de gas 12,7x0,8 mm Tubo de líquido 9,52x0,8 mm Tubo de gas 15,88x1,0 mm ● Inserte las tuercas cónicas retiradas en los tubos que se van a conectar y, a continuación, abocarde los tubos. 2. Conexión de los tubos ● Para doblar un tubo, intente hacer la curva lo más suave posible para no aplastar el tubo. El radio de doblado debe ser de entre 30 y 40 mm o superior. ● Será más sencillo conectar en primer lugar el tubo de gas. ● El tubo de conexión es especial para el tipo R410A. Media unión Llave Si se fuerza la fijación sin aplicar centrado podrían dañarse los tubos y provocarse una fuga de gas. Tuerca cónica Diámetro del tubo (ø) Par de apriete Lado de líquido 6,35 mm (1/4") 18N.m Lado de líquido/gas 9,52mm (3/8") 42 N.m Lado de gas 12,7mm (1/2") 55 N.m Lado de gas 15,88 mm (5/8") 60 N.m Llave dinamométrica Procure que no penetren materiales, como residuos de arena, agua, etc., en el tubo. PRECAUCIÓN La longitud del tubo estándar es C m. Si es superior a D m, el funcionamiento de la unidad se verá afectado. Si es necesario alargar el tubo, deberá cargarse refrigerante adicional a razón de E g/m. No obstante, la carga de refrigerante deberá ser realizada por un ingeniero profesional en aire acondicionado. Antes de añadir refrigerante adicional, realice una purga de aire desde los tubos refrigerantes y la unidad interior utilizando una bomba de vacío y cargue después el refrigerante adicional. Unidad exterior Unidad exterior B Unidad interior B A A Unidad interior Unidad exterior Unidad exterior Filtro de aceite B A Unidad interior ● Elevación máx. A máx. ● En caso de que la elevación A sea superior a 5 m, el filtro de aceite debe instalarse cada 5 ~7 m. ● Longitud máx.: B máx. ● En caso de que la longitud del tubo B sea superior a D m, deberá cargarse el refrigerante a razón de E g/m. 24 C D E 1U07BS1ERA A máx. B máx. 10 15 5 7 20 1U09BS1ERA 10 15 5 7 20 1U12BS1ERA 10 15 5 7 20 1U18BS1ERA 15 25 5 7 20 1U24BS1ERA 15 25 5 7 45 Procedimiento instalación Prueba de hermeticidad del aire Tras finalizar la conexión del tubo de refrigerante, debe realizar la prueba de hermetizado. ● La prueba de hermetizado utiliza el depósito de nitrógeno para dar presión según el modo de conexión del tubo tal y como se muestra en la siguiente figura. ● Las válvulas de gas y líquido están cerradas. Para evitar que el nitrógeno entre en el sistema de circulación de la unidad exterior, apriete el vástago de la válvula antes de dar presión (ambos vástagos de las válvulas de gas y líquido). Piezómetro de baja presión Piezómetro de alta presión Interior Válvula de retención totalmente cerrada (lado del gas) Exterior Completamente apretado Pieza cónica Separador Válvula de descarga Completamente apretado Pieza cónica Registro Válvula de goteo Depósito de nitrógeno Unidades interiores Unidades exteriores Válvula de retención totalmente cerrada (lado del líquido) Manómetro de presión de línea 1) Presurice durante más de 3 minutos a 0,3 MPa (3,0 kg/cm2g) Manómetro de presión la botella las fugas más importantes. 2) Presurice durante más de 3 minutos a 1,5 MPa (15 kg/cm2g) Se encontrarán Tubos cobresoldados 3) Presurice durante aproximadamente 24 horas a 3,0 MPa (30 kg/cm2g) Se encontrarán las fugas más pequeñas. Junta estañosoldada Botella de nitrógeno Conector de protección grande ● Compruebe si la presión disminuye Manguera de Si la presión no disminuye, la comprobación se da por buena. mantenimiento La presión disminuye, compruebe el punto de fuga. O Cuando se presurice durante 24 horas, una variación de 1 C en la temperatura ambiente provocará una variación de 0,01 MPa (0,1 kg/cm2 g) en la presión. Debe corregirse durante la prueba. ● Comprobación del punto de fuga En los pasos 1) a 3), si la presión disminuye, compruebe la fuga en cada junta escuchando, tocando, utilizando agua de jabón, etc. para identificar el punto de fuga. Tras comprobar el punto de fuga, vuelva a soldarlo o vuelva a apretar firmemente la tuerca. 25 Procedimiento instalación Vacío Método de vacío de los tubos: utilizar una bomba de vacío (por ejemplo 1U18FS1ERA) 1. Retire el tapón del puerto de mantenimiento de la válvula de 3 vías, el tapón del vástago de la válvula de 2 vías y 3 vías, y conecte el puerto de mantenimiento a la manguera de proyección de carga (inferior) del colector. Conecte entonces la manguera de proyección de carga (central) del colector a la bomba de vacío. Válvula de retención de líquido Válvula de 2 vías Válvula de retención de gas Válvula de 2 vías Válvula de 3 vías Colector (R410A) Válvula de 3 vías Bomba de vacío (R410A) 2. Abra la espita inferior del colector y accione la bomba de vacío. Si el indicador de la escala (inferior) alcanza la condición de vacío por un momento, compruebe de nuevo el paso 1. 3. Succione durante 15 minutos. Compruebe el nivel medido, que deberá ser de -0,1 Mpa (-76cm Hg) en el lado de baja presión. Tras finalizar la succión, cierre el mando de baja de la bomba de vacío. Compruebe el funcionamiento de las escala y manténgala durante 1-2 min. Si la escala retrocede a pesar de ajustarse, realice de nuevo los trabajos de conicidad y vuelva al punto 3. Abrir Cerrar Válvula de 2 vías Válvula de 3 vías Puerto de mantenimiento 90 para 6 s 4. Abra el vástago de la válvula de 2 vías 90 grados hacia la izquierda. Después de 6 segundos, cierre la válvula de 2 vías e inspeccione si existen fugas de gas. 5. ¿No existen fugas de gas? En caso de que exista una fuga de gas, apriete las conexiones de los tubos. Si la fuga se detiene, siga con el paso 6. Si la fuga de gas no se detiene, descargue todo el refrigerante a través del puerto de mantenimiento. Después de realizar de nuevo la operación de conicidad y succión, rellene con el refrigerante especificado desde la botella de gas. Válvula de 2 vías 6. Desconecte la manguera de carga del puerto de mantenimiento y abra las válvulas de 2 y 3 vías. Gire el vástago de la válvula hacia la izquierda hasta que golpee ligeramente. Válvula de 3 vías Válvula de 2 vías 7. Para evitar fugas de gas, gire el tapón del puerto de mantenimiento y el tapón del vástago de las válvulas de 2 y 3 vías un poco por encima del punto en el que la torsión aumenta súbitamente. Válvula de 3 vías Tapa del vástago de válvula Tapa del vástago de válvula Tapa del puerto de mantenimiento PRECAUCIÓN: Si existen fugas de refrigerante en el aire acondicionado, será necesario descargar todo el refrigerante. Haga el vacío primero, y cargue líquido refrigerante en el acondicionador de aire de acuerdo con la cantidad marcada en la placa de valores nominales. 26 Procedimiento instalación Cableado eléctrico ¡ADVERTENCIA! PELIGRO DE LESIONES PERSONALES O MUERTE ● DESCONECTE LA ENERGÍA ELÉCTRICA EN EL INTERRUPTOR DE CIRCUITO O LA FUENTE DE ALIMENTACIÓN ANTES DE REALIZAR CONEXIONES ELÉCTRICAS. ● LAS CONEXIONES A TIERRA DEBEN COMPLETARSE ANTES DE REALIZAR CONEXIONES DE TENSIÓN DE LÍNEA. Precauciones para el cableado eléctrico ● El trabajo de cableado eléctrico sólo debe realizarlo el personal autorizado para dicha tarea. ● No conecte más de tres cables al bloque de terminales. Utilice siempre orejetas de terminales en rizo de tipo redondo con agarre con funda en los extremos de los cables. ● Utilice exclusivamente conductores de cobre. Selección del tamaño de la fuente de alimentación y los cables de interconexión Seleccione los tamaños del cable y la protección de circuito en la siguiente tabla. (Esta tabla muestra cables de 20 m con una caída de tensión inferior al 2%.) Interruptor de circuito Elemento Tamaño del cable de la fuente de Capacidad nominal del alimentación protector de sobrecarga (mínimo) de corriente (A) (mm2) Fase Interruptor (A) 1U07BS1ERA 1U09BS1ERA 1U12BS1ERA 1U18BS1ERA 1 40 26 1U24GS1ERA 1 40 26 Modelo Interruptor de fugas de masa Interruptor (A) Corriente de fuga (mA) 2.5 40 30 4.0 40 30 ● Si el cable de alimentación está dañado deberá ser reemplazado por el fabricante, agente de servicio o profesional cualificado. ● Si el fusible de la caja de control se funde, cámbielo por otro de tipo T 25 A/250 V. ● El método de cableado debe satisfacer los requisitos de las normas locales de cableado. ● El cable de alimentación y el cable de conexión deben estar incluidos. ● Todos los cables deben contar con el certificado de autentificación europeo. Durante la instalación, cuando quite los cables de conexión, debe asegurarse de que el hilo de tierra es el último en quitarse. ● El interruptor del aire acondicionado debe estar conectado a todos los polos y la distancia entre los dos contactos del interruptor no debe ser inferior a 3 mm. Dicho método de desconexión debe instalarse en el cableado fijo. ● La distancia entre los dos bloques de terminales de la unidad interior y la unidad exterior no debe ser superior a 5 m. Si es superior, el diámetro del hilo se debe aumentar conforme al estándar de cableado local. ● Se debe instalar un interruptor de fugas. Procedimiento de cableado 1) Extraiga los tornillos del lateral antes de tirar el panel delantero hacia la dirección que se muestra en la figura. 2) Conecte los cables al bloque de terminales de forma correcta y fije los cables con una pinza del cable situada junto al bloque de terminales. 3) Coloque los cables de forma adecuada e introdúzcalos por la apertura del cableado eléctrico del panel lateral. ADVERTENCIA: LOS CABLES DE INTERCONEXIÓN DEBEN CONECTARSE SEGÚN LA FIGURA SIGUIENTE. SI REALIZA EL CABLEADO DE FORMA INCORRECTA PUEDEN PRODUCIRSE DAÑOS EN EL EQUIPO. PARA 18K 24K PARA 07K 09K 12K Unidad exterior Unidad exterior 1(N) 2 (L) 1U07BS1ERA 1U09BS1ERA 1U12BS1ERA 1U18BS1ERA 1U24GS1ERA Cableado de conexión 4G 0,75 mm2 4G 0,75 mm2 4G 0,75 mm2 Cable de alimentación 3G 1,5 mm2 3G 2,5 mm2 3G 4,0 mm2 Modelo 3 C) ( 1(N) 2 (L) 3 C) A la unidad interior A la unidad interior ( { N INTENSO L 1(N ) 2 (L) 3 (C ) INTENSO 27 Resolución de problemas en la unidad exterior ¡PRECAUCIÓN! ● ESTA UNIDAD SE PONDRÁ EN FUNCIONAMIENTO DE FORMA INSTANTÁNEA SIN ACTIVARLA CUANDO SE SUMINISTRE LA ENERGÍA ELÉCTRICA. ASEGÚRESE DE DESACTIVARLA ANTES DE DESCONECTAR LA ENERGÍA ELÉCTRICA PARA REALIZAR EL MANTENIMIENTO. ● Esta unidad cuenta con una función de sistema de reinicio automático que se activa al finalizar la interrupción de la energía. 1. Antes de iniciar el funcionamiento de prueba (para los modelos de bomba de calor) Compruebe si el interruptor de la fuente de alimentación (interruptor principal) de la unidad se ha activado durante más de 12 horas para energizar el calentador del cárter en previsión de la puesta en marcha. 2. Funcionamiento de prueba Ponga la unidad en funcionamiento de forma continua durante 30 minutos y compruebe lo siguiente. ● La presión de aspiración en la junta de comprobación de la válvula de servicio del tubo de gas. ● La presión de descarga de la junta de comprobación del tubo de descarga del compresor. ● La diferencia de temperatura entre el aire de retorno y el aire de suministro de la unidad interior. Destellos del LED en la placa principal Descripción del problema Analizar y diagnosticar Error en la memoria EEPROM de la placa principal externa Error de IPM 9 10 Error en la memoria EEPROM Error de IPM Error de comunicación entre la placa principal y el módulo SPDU Error de comunicación SPDU Protección de alta presión Protección contra exceso de voltaje del módulo (solamente para SPUD) Protección contra ausencia de voltaje del módulo (solamente para SPUD) Protección contra temperatura descarga del compresor Anomalía en el motor de CC Anomalía en el sensor de tubos 11 Error en el sensor de temperatura de succión 1 2 4 5 6 8 12 13 15 Anomalía en el sensor de temperatura ambiente exterior Anomalía en el sensor de descarga del compresor Error de comunicación entre las unidades interior y exterior 16 Ausencia de refrigerante o compruebe si hay alguna fuga la unidad 17 Error de inversión de la válvula de cuatro vías 18 19 25 25 25 Compresor obturado (solamente para SPUD) Error en el circuito de selección PWM del módulo Exceso de corriente en la fase U del compresor Exceso de corriente en la fase V del compresor Exceso de corriente en la fase W del compresor Error de comunicación superior a 4 minutos Presión alta del sistema superior a 4,15 MPa Enviar desde el módulo SPUD Temperatura de descarga del compresor superior a 110 ºC Obstrucción del motor de CC o error del motor Cortocircuito o circuito abierto en el sensor de tubos El cableado del compresor es erróneo o la conexión es inestable Cortocircuito o circuito abierto en el sensor de temperatura ambiente exterior Cortocircuito o circuito abierto en el sensor de descarga del compresor Error de comunicación superior a 4 minutos Alarma y parar si se detecta que TD-tci>=75 dura 1 minuto después de que el compresor se haya iniciado durante 10 minutos en el modo de refrigeración. Compruebe si hay fuga en la unidad. Alarma y parar si se detecta que Tm<=75 dura 1 minuto después de que el compresor se haya iniciado durante 10 minutos en el modo de refrigeración. Confirmar el error se aparece 3 veces en una hora. El compresor interno tiene una obstrucción anómala Circuito erróneo de selección PWM del módulo La corriente de la fase U del compresor es demasiado alta La corriente de la fase V del compresor es demasiado alta La corriente de la fase W del compresor es demasiado alta Haier Group Dirección: No.1 Haier Road, Hi-tech Zone, Qingdao 266101 República Popular China Contactos: TEL: +86-532-8893-6943; FAX: +86-532-8893-1010 Sitio web: www.haier.com 28 14 Haier Industrial Park, N.1 Haier Road, Qingdao, Repubblica Popolare Cinese CONFORMITÀ AI REGOLAMENTI EUROPEI PER I MODELLI IMPORTANTI INFORMAZIONI RELATIVE AL REFRIGERANTE UTILIZZATO CE Tutti i prodotti sono conformi alle seguenti disposizioni europee: - Direttiva bassa tensione 73/23/CEE - Direttiva bassa tensione 2006/95/CEE - Compatibilità elettromagnetica 89/336/CEE - Compatibilità elettromagnetica 2004/108/CE Questo prodotto contiene gas serra fluorinato, trattato nel Protocollo di Kyoto R410A 1= kg 2 2= kg 1+2= kg ROHS I prodotti sono conformi ai requisiti della direttiva 2002/95/CEE del Parlamento e del Consiglio Europeo sulla limitazione dell'uso di alcune sostanze pericolose nei dispositivi elettrici ed elettronici (direttiva RoHS UE). WEEE In conformità alla direttiva 2002/96/CE del Parlamento Europeo, informiamo il consumatore relativamente ai requisiti per lo smaltimento dei prodotti elettrici ed elettronici. REQUISITI PER LO SMALTIMENTO: Il condizionatore acquistato è contrassegnato con questo simbolo, che sta a significare che le parti elettriche ed elettroniche non devono essere mischiate con i rifiuti domestici. Non tentare di aprire il sistema da soli: lo smontaggio del sistema del condizionatore, il trattamento del refrigerante, dell'olio e di altre parti deve essere effettuato da un installatore qualificato conformemente alle leggi locali e nazionali pertinenti. I condizionatori devono essere trattati presso strutture di trattamento specializzate per il riutilizzo, il riciclaggio e il ricondizionamento. Garantendo che questo prodotto sia smaltito correttamente, si aiuterà a prevenire possibili conseguenze negative per l'ambiente e la salute umana. Contattare l'installatore o l'autorità locale per ulteriori informazioni. La batteria deve essere rimossa dal telecomando e smaltita separatamente in conformità alle leggi locali e nazionali pertinenti. 1 F A B C D E Questo prodotto contiene gas serra fluorinato, oggetto del Protocollo di Kyoto. Non lasciar sfogare nell'atmosfera. Tipo di refrigerante:R410A Valore GWP* :1975 GWP=global warming potential Inserire, con inchiostro indelebile, •1 il carico di refrigerante del prodotto inserito in fabbrica •2 il quantitativo aggiuntivo di refrigerante caricato sul campo e • 1+2 il carico di refrigerante totale sull'etichetta con il carico di refrigerante in dotazione con il prodotto. L'etichetta compilata deve essere attaccata accanto alla porta di caricamento del prodotto (es. all'interno del coperchio con il valore di arresto). A contiene gas serra fluorinato, trattato nel Protocollo di Kyoto Protocollo B carico di refrigerante del prodotto inserito in fabbrica: vedere la piastra con il nome dell'unità C quantitativo aggiuntivo di refrigerante caricato sul campo D carico di refrigerante totale E unità esterna F cilindro di refrigerante e collettore per la carica Illustrazione installazione dell'unità esterna/interna I modelli adottano il refrigerante R410A senza HFC. Per l'installazione delle unità interne, fare riferimento al manuale di installazione fornito con le unità. (Lo schema rappresenta un'unità interna montata a muro.) Deve essere prestata attenzione al sollevamento del tubo flessibile di scarico più di 15 cm Parti optional per le tubature A Nastro non adesivo B Nastro adesivo G più di 10 cm C Supporto (L.S) con viti D Collegamento del cavo elettrico per interno ed esterno E Tubo flessibile di scarico F Materiale isolante termico Disposizione della direzione delle tubature Sinistra G Coperchio foro tubatura più di 10 cm Posteriore sinistra Posteriore destra F A Destra C Inferiore più di 20 cm più di 20 cm Fissaggio dell’unità esterna ● I simboli da A a G nelle immagini sono i numeri delle parti. ● La distanza tra l’unità interna e il pavimento deve essere superiore ai 2 m. D E più di 60 cm ● Fissare l’unità alla pavimentazione o al blocco di cemento stringendo bene dadi e bulloni (10mm) e accertarsi che l’unità sia a livello orizzontale. ● Quando si installa l’unità su pareti, tetti o tettoie, fissare in sicurezza un supporto usando chiodi o cavi tenendo in considerazione terremoti e venti forti. ● Se la vibrazione potrebbe avere un'influenza sulla casa, fissare l’ unità usando un pannello antivibrazione. più di 25 cm  USCITA DELL'ARIA  PRESA D'ARIA  CONNESSIONE DELLE TUBAZIONI E DEI CAVI 4 ELETTRICI  TUBO FLESSIBILE DI DRENAGGIO Compressore (all'interno dell'unità) ● Le immagini di unità esterne e interne sono solo per riferimento. Attenersi al prodotto acquistato. 29 Norme di sicurezza Leggere attentamente queste informazioni per il corretto funzionamento del condizionatore. Di seguito, sono elencati tre tipi di norme di sicurezza e suggerimenti. AVVERTENZA Operazioni non corrette potrebbero avere conseguenze gravi come morte o gravi ferite. ATTENZIONE Operazioni non corrette potrebbero causare danni al condizionatore; in alcuni casi si potrebbero avere conseguenze gravi. ISTRUZIONI: Queste informazioni assicurano il corretto funzionamento del condizionatore. Simboli utilizzati nelle illustrazioni : indica che l'azione deve essere evitata. : indica che un'istruzione importante deve essere seguita. : indica una parte che deve essere messa a terra. : fare attenzione alle scosse elettriche (questo simbolo viene visualizzato sull'etichetta principale dell'unità.) Dopo aver letto questo manuale, assicurarsi di farlo leggere anche a coloro che utilizzeranno l'unità. Gli utenti dell'unità dovrebbero conservare il manuale a portata di mano e renderlo disponibile per coloro che effettueranno riparazioni o spostamenti dell'unità. Inoltre, nel caso in cui ci sia un cambio di proprietà, rendere disponibile il manuale per il nuovo utente. Assicurarsi di seguire queste importanti precauzioni di sicurezza. AVVERTENZA ● Non smontare la bocchetta di uscita ● Nel momento in cui venga rilevato qualsiasi dell'unità interna. fenomeno anomalo (p.e. odore di bruciato), Spegnere L'esposizione del ventilatore è molto periinterrompere immediatamente l'erogazione colosa poichè potrebbe ferire le persone. di corrente e contattare il fornitore per conoscere il modo in cui affrontare il problema. In tal caso, continuare a utilizzare il condizionatore potrebbe causare danni e generare il rischio di folgorazione e di incendio. ● In caso di necessità di manutenzione e riparazioni, contattare il fornitore affinchè se ne occupi. Una manutenzione e una riparazione ● Dopo un lungo periodo di utilizzo del condiscorrette potrebbero causare perdite d'aczionatore, è necessario controllare la base qua, rischio di folgorazione e di incendio. per controllare la presenza di danni Se la base danneggiata non viene riparata, l'unità rischia di cadere e causare incidenti. AVVERTENZA ● Sopra l'unità esterna non deve essere posizionato alcun oggetto e non deve esserci nessuna persona. La caduta di persone e oggetti potrebbe causare incidenti. ● Il condizionatore non deve essere installato in ambientei in cui siano presenti gas infiammabili poiché potrebbero generarsi incendi. Il rivenditore deve occuparsi dell'installazione del condizionatore. Un'installazione scorretta può causare perdite d'acqua, rischio di folgorazione e incendio. ● Non utilizzare il condizionatore con le mani umide. Rischio di scossa elettrica. ● Rivolgersi al rivenditore per eseguire le azioni necessarie ad impedire la perdita di refrigerante. Se il condizionatore viene installato in un ambiente piccolo, assicurarsi di eseguire tutte le azioni necessarie per evitare incidenti di soffocamento anche nel caso in cui ci sia una perdita di refrigerante. ● Utilizzare solo fusibili della tipologia corretta. Non utilizzare cavi e nessun altro materiale per sostituire i fusibili poichè potrebbero causare incendi o incidenti. ● Quando il condizionatore viene installato o installato nuovamente, deve occuparsene il rivenditore. Un'installazione scorretta potrebbe causare perdite d'acqua, rischio di folgorazione e incendio. ● Utilizzare il tubo di scarico in modo corretto per assicurare uno scarico funzionale. Un uso scorretto delle tubature potrebbe causare perdite d'acqua. ● Interruttore differenziale installato per proteggere da eventuali dispersioni elettriche. Vi è il rischio di folgorazione elettrica in caso di assenza di interruttore differenziale. ● Collegamento del cavo per la messa a terra. Il cavo per la messa a terra non deve essere connesso al tubo del gas, al tubo dell'acqua o al parafulmine, una messa a terra scorretta potrebbe causare folgorazione. 30 Messa a terra Norme di sicurezza AVVERTENZA ● Assicurarsi che l'unità venga installata da professionisti. Un'installazione scorretta eseguita da una persona non qualificata potrebbe causare perdite d'acqua, rischio di folgorazione e incendio. ● Accertarsi di seguire attentamente tutte le fasi del manuale durante l'installazione dell'unità. Un'installazione scorretta potrebbe causare perdite d'acqua, rischio di folgorazione, fumo o incendi. ● Assicurarsi che tutti i lavori di tipo elettrico vengano eseguiti da ● Posizionare l'unità su una superficie piana e stabile che possa un elettricista con regolare licenza secondo i regolamenti locali e sorreggere il peso dell'unità per evitare che l'unità si ribalti o cada le istruzioni fornite in questo manuale. Utilizzare un circuito appocausando incidenti. sito per l'unità. Un'installazione scorretta o una mancanza di capacità dei circuiti ● Utilizzare soltanto cavi specifici per il cablaggio. Collegare corretpotrebbe causare un malfunzionamento dell'unità o generare il tamente ogni cavo, e assicurarsi che i cavi non forzino i terminali. I cavi collegati in modo non corretto potrebbero generare calore rischio di folgorazione, fumo e incendi. e rischio di incendio. ● Fissare correttamente il coperchio del terminale (pannello) sull'unità. ● Adottare le precauzioni necessarie contro tifoni e terremoti per Se l'installazione non viene eseguita correttamente, la polvere o evitare la caduta del condizionatore. l'acqua potrebbero entrare nell'unità e generare il rischio di folgorazione, fumo o incendi. ● Non effettuare modifiche e cambiamenti al condizionatore. In caso di problemi, consultare il rivenditore. Se le riparazioni non vengono eseguite nella maniera corretta, ● Utilizzare soltanto il refrigerante R410A come indicato sull'unità durante l'installazione o lo spostamento della stessa. potrebbero presentarsi perdite d'acqua, rischio di folgorazione L'utilizzo di qualsiasi altro refrigerante o l'introduzione di aria nei oppure potrebbe venir prodotto fumo e generati incendi. circuiti dell'unità potrebbe comportare un ciclo di lavoro anomalo generando il rischio di esplosione dell'unità. AVVERTENZA ● Non toccare le alette sullo scambiatore di calore a mani nude poichè queste sono affilate e pericolose. ● Durante l'installazione dell'unità in un ambiente piccolo, eseguire tutte le operazioni necessarie per proteggersi dall'ipossia che potrebbe essere causata dalla perdita di refrigerante che raggiunge ● Nel caso di perdita di refrigerante, fare in mdo che l'ambiente sia il livello massimo. ventilato in maniera adeguata. Rivolgersi al rivenditore per eseguire quanto necessario. Se il gas del refrigerante che fuoriesce viene esposto a fonti di ● Quando il condizionatore viene riposizionato, consultare il rivencalore, potrebbero generarsi gas nocivi. ditore o uno specialista. ● Con tutte le tipologie di condizionatori ad aria fresca, l'aria esterUn'installazione scorretta potrebbe causare perdite d'acqua, na potrebbe venir soffiata direttamente nell'ambiente al disinseririschio di folgorazione o incendi. mento del termostato. Questo va tenuto in considerazione duran● Dopo aver completato il lavoro di manutenzione, controllare te l'installazione dell'unità. L'esposizione diretta all'aria esterna potrebbe causare pericolo eventuali perdite di gas refrigerante. Se il gas refrigerante è esposto a una fonte di calore come un per la salute e potrebbe far guastare il cibo. ventilatore per il rscaldamento, a una stufa o a un grill elettrico, ● Non cercare di aggirare le misure di sicurezza del dispositivo e potrebbero generarsi gas nocivi. non modificare le impostazioni. ● Utilizzare solo parti specifiche. La manomissione delle misure di sicurezza dell'unità ad esempio Assicurarsi che l'unità venga installata da professionisti. Un'inil pressostato e l'interruttore della temperatura oppure l'utilizzo stallazione scorretta potrebbe causare perdite d'acqua, rischio di di parti che non provengano dal rivenditore o da uno specialista folgorazione, fumo o incendi. potrebbero causare incendi ed esplosioni. 31 Norme di sicurezza Precauzioni per maneggiare le unità che utilizzano R410A Attenzione Non utilizzare vecchie tubature refrigeranti Utilizzare una pompa a vuoto con un valvola di controllo a flusso ● Il refrigerante e l'olio refrigerante vecchi nelle tubature contengo inverso. una grande quantità di clorina, che potrebbe causare il degrado ● Se vengono utilizzati altri tipi di valvole, l'olio della pompa a vuoto dell'olio refrigerante nella nuova unità. penetrerà nel ciclo del refrigerante e causerà il degrado dell'olio ● L'R410A è un refrigerante ad alta pressione e l'utilizzo di tubature refrigerante. vecchie potrebbe generare il rischio di esplosione. Non utilizzare i seguenti strumenti usati in precedenza con refrigeranti convenzionali. Preparare degli strumenti per l'uso esclusivo dell'R410A. (Collettore manometro, tubo flessibile di carico, rilevatore di perdite di gas, valvola di controllo a flusso inverso, base di carico per Mantenere le superfici interne ed esterne delle tubature pulite e pri- il refrigerante, vacuometro ed equipaggiamento per il recupero di ve di contaminati come zolfo, ossidi, particelle di sporco e polvere, refrigerante.) olii e umidità. ● Se il refrigerante e/o l'olio refrigerante lasciato su questi stru● Gli agenti contaminanti che si trovano nelle tubature refrigeranti menti si mescola con l'R410, oppure se l'acqua si mescola con l'R410A, il refrigerante subirà un processo di degrado. potrebbero causare il degrado dell'olio refrigerante. ● Poiché l'R410A non contiene cloro, i rilevatori di perdite di gas per refrigeranti convenzionali non funzioneranno. Attenzione Non utilizzare una bombola di carico. ● L'utilizzo di una bombola di carico modificherà la composizione del refrigerante causando una perdita di potenza. Riporre al chiuso le tubature da utilizzare durante l'installazione, e tenere entrambe le estremità sigillate fino al momento della brasatura. (tenere i gomiti e le altre connessioni avvolte nella plastica.) ● Se la polvere, lo sporco o l'acqua penetrano nel ciclo del refrigerante, potrebbero causare il degrado dell'olio nell'unità oppure causare il malfunzionamento del compressore. Utilizzare gli strumenti con estrema cautela. ● Nel caso in cui elementi esterni come polvere, sporco o acqua Utilizzare una piccola quantità di olio a base di estere o etere, oppenetrino nel ciclo del refrigerante potrebbe verificarsi il degrado pure alchilbenzene per applicare uno strato protettivo su tutti i punti dell'olio della macchina refrigerante. di connessione delle flange e dei fori svasati. ● Una grande quantità di olio minerale potrebbe causare il degrado dell'olio della macchina refrigerante. Utilizzare soltanto refrigerante R410A. Utilizzare liquido refrigerante per caricare il sistema. ● Caricare l'unità con il gas refrigerante comporta la modifica della ● L'utilizzo di refrigeranti contenenti cloro (per esempio R22) causa il degrado del refrigerante. composizione del refrigerante ne cilindro causando un abbassamento della qualità delle prestazioni Prima di installare l'unità Attenzione Non installare l'unità in un luogo in cui c'è il rischio di perdite di gas Se l'unità viene installata in un ospedale, eseguire le azioni necessarie contro il rumore. infiammabile. ● Il gas disperso accumulato attorno all'unità potrebbe generare un ● La strumentazione medica ad alta frequenza potrebbe interferire con il normale funzionamento del condizionatore o dell'equipagincendio. giamento medico Non utilizzare l'unità per conservare cibi, animali, piante, artefatti o per altri scopi particolari. ● L'unità non è designata per offrire condizioni adeguate per il mantenimento della qualità di questi oggetti. Non utilizzare l'unità in ambienti non comuni ● L'utilizzo dell'unità in presenza di una grande quantità di olio, vapore, acido, solventi alcalini o particolari tipi di spray potrebbe causare un notevole abbassamento delle prestazioni e/o un malfunzionamento comportando il rischio di folgorazione, fumo o incendi. ● La presenza di solventi organici, gas corrosi (come ammoniaca, composti di zolfo e acidi) potrebbe causare perdite di gas o acqua. Non posizionare l'unità al di sopra o al di sotto di oggetti che non devono essere bagnati. ● Quando il livello di umidità supera l'80% o quando il sistema di drenaggio è otturato, dall'unità interna potrebbe gocciolare acqua. ● Per evitare il gocciolamento delle unità esterne, si dovrebbe tenere in considerazione l'installazione di un sistema di drenaggio centralizzato. 32 Norme di sicurezza Prima di installare (riposizionare) l'unità o prima di eseguire lavori elettrici Attenzione Eseguire la messa a terra l'unità. ● Non collegare la messa a terra dell'unità ai tubi del gas, ai tubi dell'acqua, ai parafulmini o ai terminali della messa a terra dei telefoni. Una messa a terra non corretta comporta il rischio di folgorazione, fumo, incendio, oppure il rumore generato dalla scorretta messa a terra potrebbe causare il malfunzionamento dell'unità. Non spruzzare acuqa sui condizionatori o immergerli nell'acqua. ● L'acqua sull'unità comporta il rischio di folgorazione. Controllare periodicamente la piattaforma sulla quale è posizionata l'unità in caso di danneggiamento per evitare la caduta dell'unità. ● Se l'unità viene lasciata su una piattaforma danneggiata, potrebbe ribaltarsi causando danni. Accertarsi che i cavi non siano soggetti a tensione. ● Se i cavi sono troppo tesi, potrebbero rompersi o generare calore Durante l'installazione delle tubature di drenaggio, seguire le istruzioni nel manuale e assicurarsi che questi drenino correttamente e/o fumo e incendi. l'acqua per evitare la formazione di condensa di rugiada. Installare un interruttore differenziale per la dispersione di corrente ● Se le tubature non vengono installate correttamente, potrebbero causare perdite d'acqua e danneggiare l'arredamento. alla sorgente della corrente elettrica per evitare il rischio di folgorazione. ● In assenza dell'interruttore differenziale per la dispersione di Smaltire correttamente i materiali dell'involucro. ● Nella scatola potrebbero essere inclusi elementi come chiodi. corrente, si corre il rischio di folgorazione, fumo o incendio. Smaltirli correttamente per evitare lesioni. Utilizzare interruttori e fusibili (interruttori differenziale per la corren- ● Le buste di plastica rappresentano un pericolo di soffocamento per i bambini. Strappare la buste di plastica prima di smaltirle per te elettrica e fusibili, interruttore remoto<interruttore+fusibile di tipo prevenire eventuali incidenti. B>, interruttori differenziali di corrente scatolati) con una capacità di corrente appropriata. ● L'utilizzo di fusibili ad alta capacità, cavi di ferro, o cavi di rame potrebbe danneggiare l'unità o generare fumo o incendi. Prima del collaudo di avvio Attenzione Non premere gli interruttori con le mani bagnate per evitare il rischio di folgorazione. Non toccare le tubature refrigeranti a mani nude durante e immediatamente dopo il funzionamento. ● Secondo lo stato del refrigerante nel sistema, alcune parti dell'unità come le tubature e il compressore potrebbero divenire molto fredde o calde e causare congelamento o ustioni. Non spegnere subito dopo aver fermato l'unità. ● Prima di spegnere completamente l'unità aspettare almeno cinque minuti, altrimenti potrebbero verificarsi perdite d'acqua dall'unità e altri problemi. Non utilizzare l'unità se i pannelli o le griglie di sicurezza non siano in posizione corretta. ● La loro presenza previene il rischio di lesioni dell'utente che altri- Non utilizzare l'unità senza filtri d'aria. menti potrebbe toccare parti rotanti, o parti ad alta temperatura o ● Particelle di polvere nell'aria potrebbero otturare il sistema e causare malfunzionamento. alto voltaggio. 33 Leggere prima dell'installazione Elementi da controllare (1). Verificare il tipo di refrigerante utilizzato dall'unità su cui deve essere effettuata la manutenzione. Tipo di refrigerante: R410A (2). Controllare i sintomi mostrati dall'unità su cui deve essere effettuata la manutenzione. Cercare nella guida i sintomi relativi al ciclo del refrigerante. (3). Assicurarsi di leggere con attenzione le precauzioni di sicurezza che si trovano all'inizio di questo documento. (4). Nel caso di perdita di gas o se il refrigerante residuo è esposto a una fiamma viva, si può produrre un gas nocivo acido fluoridrico. Il luogo di lavoro deve essere ben ventilato. AVVERTENZA ● Installare nuove tubature subito dopo aver rimosso quelle vecchie per evitare la formazione di umidità sul circuito refrigerante. ● La presenza di cloro in alcuni refrigeranti come l'R22 può causare il degrado dell'olio della macchina refrigerante. Strumenti e materiali necessari Preparare i seguenti strumenti e materiali necessari per l'installazione e la manutenzione dell'unità. Strumenti necessari da utilizzare per l'R410A (adattabilità degli strumenti utilizzabili con R22 e R407C). 1. Da utilizzare esclusivamente con l'R410A ( da non utilizzare con l'R22 o l'R407C ) Strumenti/materiali Utilizzo Note Collettore manometro Consente di eseguire l'evacuazione, e il 5.09 MPa sul lato ad alta pressione caricamento del refrigerante Tubo flessibile di carico Permette di eseguire l'evacuazione, e il Diametro del tubo flessibile maggiore di quello dei tubi convenzionali. caricamento del refrigerante Equipaggiamento per il recupero del re- Consente di recuperare il refrigerante frigerante Cilindro refrigerante Consente il caricamento del refrigerante Porta di caricamento del cilindro refrige- Consente il caricamento del refrigerante rante Bullone foro svasamento Annotare il tipo di refrigerante. La parte superiore del cilindro è di colore rosa. Diametro del tubo flessibile maggiore di quello dei tubi convenzionali. Consente di collegare l'unità alle tubature Utilizzare bulloni per i fori di svasamento di tipo due. 2. Strumenti e i materiali che possono essere utilizzati con l'R410 con alcune restrizioni Strumenti/materiali Utilizzo Note Rilevatore di perdite di gas Consente di rilevare perdite di gas È possibile utilizzare il rilevatore per gas di tipo HFC. Pompa a vuoto Consente di eseguire l'asciugatura sotto Potrebbe essere utilizzata nel caso in cui sia montato un adattatore di controlo a flusso vuoto inverso. Strumento foro di svasamento Svasatura delle tubature Equipaggiamento per il recupero del re- Consente il recupero del refrigerante frigerante Sono stati apportati dei cambiamenti alle dimensioni della svasatura. Fare riferimento alla pagina successiva. Potrebbe essere utilizzato se progettato per essere utilizzato con l'R410A. 3. Strumenti e materiali utilizzati perl'R22 o R407C che possono essere utilizzati anche con l'R410A Strumenti/materiali Utilizzo Pompa del vuoto con valvola di controllo Consente di eseguire l'asciugatura sotto vuoto Piegatubi Consente di piegare i tubi Chiave dinamometrica Consente di stringere i bulloni dei fori di Soltanto svasamento Tagliatubi Consente di tagliare i tubi Saldatore e cilindro ad azoto Consente di saldare le tubature Misuratore di carica del refrigerante Consente il caricamento del refrigerante Vacuometro Consente di controllare il vuoto Note 12,70 (1/2'') e 15,88(5/8'') hanno una dimensione maggiore della svasatura. 4. Strumenti e materiali che non devono essere utilizzati con l'R410A Strumenti/materiali Utilizzo Note Bombola di carico Consente di caricare il refrigerante Non deve essere utilizzato con le unità di tipo R410. Strumenti per l'R410A devono essere maneggiate con estrema attenzione, evitando di far entrare in circolo la polvere e l'umidità. 34 Leggere prima dell'installazione Materiali per le tubature Tipi di tubi in rame (riferimento) Massima pressione di funzionamento Refrigeranti applicabili 3,4 MPa R22, R407C 4,15 MPa R410A ● Utilizzare tubature che rispettino gli standard locali. Materiali tubature/Spessore radiale Utilizzare tubature in rame di fosforo disossidato. Poichè la pressione di attività delle unità che utilizzano l'R410A è più elevata di quella delle unità con l'R22, utilizzare tubature con uno spessore radiale che sia specificato nel grafico sottostante. (Tubature con uno spessore radiali di 0.7 mm o inferiore non devono essere usate.) Dimensione (mm) Dimensione (pollici) Spessore radiale (mm) 6.35 1/4'' 0,8t 9.52 3/8" 0,8t 12.7 1/2" 0,8t 15.88 5/8" 1,0 t 19.05 3/4" 1,0 t Tipo Tubature di tipo O Tipo-1/2H o tubazioni H ● Nonostante sia stato possibile utilizzare tubature di tipo O per una dimensione che arrivi fino a 19,05 (3/4") con refrigeranti convenzionali, utilizzare tubature H di tipo 1/2H per unità che utilizzano l'R410A. (Tubature di tipo O possono essere utilizzate se la dimensione della tubatura è 19,05 e lo spessore radiale è 1,2 t.) ● La tabella mostra gli standard giapponesi. Utilizzare questa tabella come riferimento, scegliere tubature che corrispondono agli standard locali. Svasatura (tipo O e topo OL) Le dimensioni della svasatura per le unità che utilizzano l'R410A sono maggiori di quelle delle unità che utilizzano l'R22 per migliorare la tenuta. Dimensione della svasatura(mm) Dimensioni Dimensione A R410A R22 6.35 1/4'' 9.1 9.0 9.52 3/8" 13.2 13.0 12.7 1/2" 16.6 16.2 15.88 5/8" 19.7 19.4 19.05 3/4" 24.0 23.3 Dimensione A Dimensione esterna delle tubature Se viene utilizzato un tipo di foro di svasamento a frizione con le machine flares sulle unità che utilizzano l'R410A, la parte del tubo che fuoriesce deve avere una lunghezza da 1,0 e 1,5mm. Un tubo di calibro in rame può risultare utile per regolare la lunghezza del tubo che sporge. Bullone foro svasamento Per aumentare la forza vengono utilzzati bulloni svasati di tipo 2 invece che di tipo 1. La dimensione dei bulloni foro svasati è stata cambiata. Dimensione bullone foro svasato (mm) Dimensione esterna delle tubature Dimensioni Dimensione B R410A (Tipo 2) R22 (Tipo 1) 6.35 1/4'' 17.0 17.0 9.52 3/8" 22.0 22.0 12.7 1/2" 26.0 24.0 15.88 5/8" 29.0 27.0 19.05 3/4" 36.0 36.0 Dimensione B ● La tabella mostra gli standard giapponesi. Utilizzare questa tabella come riferimento, scegliere tubature che corrispondono agli standard locali. 35 Leggere prima dell'installazione Collaudo della tenuta NESSUN cambiamento rispetto al metodo convenzionale. Fare attenzione poichè un rilevatore di perdita di refrigerante per l'R22 o l'R407C non può rivelare perdite di R410A. Torcia alogenura Rilevatore di perdita di R22 o R407C Oggetti da osservare attentamente: 1. Mettere sotto pressione l'apparecchiatura con l'azoto fino al raggiungimento della pressione designata quindi considerare la tenuta dell'equipaggiamento, tenere in considerazione le variazioni di temperatura. 2. Quando si ricercano le zone di perdita utilizzando un refrigerante, assicurarsi di utilizzare l'R410A. 3. Assicurarsi che l'R410A sia allo stato liquido quando viene caricato. Motivazioni: 1. L'utilizzo dell'ossigeno come gas pressurizzato potrebbe causare un'esplosione. 2. Un caricamento di gas R410A causerà la modifica della composizione del refrigerante residuo nel cilindro impedendo l'utilizzo di questo refrigerante. Svuotamento 1. Pompa del vuoto con valvola di controllo È necessaria una pompa del vuoto con valvola di controllo per evitare che l'olio della pompa a vuoto penetri nel circuito refrigerante quando la pompa del vuoto è spenta (o nel caso in cui si verifichi un black out). In seguito sarà inoltre possibile collegare una valvola di controllo alla pompa del vuoto. 2. Vuoto standard della pompa del vuoto Utilizzare una pompa che raggiunge i 65 Pa o inferiore dopo 5 minuti di funzionamento. Inoltre, assicurarsi di utilizzare una pompa a vuoto che sia stata mantenuta correttamente e oliata utilizzando l'olio specifico. Se la pompa del vuoto non è stata mantenuta correttamente, il grado di vuoto potrebbe essere troppo basso. 3. Precisione richiesta per il vacuometro Utilizzare un vacuometro che possa misurare fino a 650 Pa. Non utilizzare un manometro generale poichè non può misurare un vuoto di 650 Pa. 4. Tempo di svuotamento Svuotare l'apparecchiatura per 1 ora dopo aver raggiunto i 650 Pa. Dopo lo svuotamento, tenere ferma l'apparecchiatura per 1 ora e assicurarsi che il vuoto si conserva. 5. Procedura di funzionamento quando la pompa del vuoto è spenta Per prevenire un riflusso dell'olio della pompa a vuoto, aprire la valvola di scarico sul lato della pompa a vuoto oppure allentare la tubatura di scarico flessibile per tirare su aria prima di fermare l'operazione. La stessa procedura operativa deve essere eseguita quando si utilizza una pompa a vuoto con una valvola di controllo. Caricamento del refrigerante L'R410A deve trovarsi allo stato liquido quando viene caricato. Motivazioni: L'R410A è un refrigerante pseudo azeotropico (punto d'ebollizione R32= -52°C, R125= -49°C) e difficilmente può essere maneggiato allostesso modo dell'R22; comunque, assicurarsi di riempire il refrigerante dalla parte del liquido, poichè fare ciò dalla parte del gas comporterà in qualche modo la modifica della composizione del refrigerante nel cilindro. Nota ● Nel caso di un cilindro con un sifone, il liquido R410A viene caricato senza capovolgere il cilindro. Controllare il tipo di cilindro prima di caricarlo. Rimedi nel caso di perdita di refrigerante In caso di perdita di refrigerante, deve essere caricato del refrigerante aggiuntivo. (Aggiungere il refrigerante dalla parte del liquido) Caratteristiche dei refrigeranti nuovi e convenzionali ● Poichè l'R410A è un refrigerante azeotropico simulato, può essere maneggiato allo stesso modo di un singolo refrigerante come l'R22.In ogni caso, se il refrigerante viene rimosso durante lo stato di vapore, la composizione del refrigerante nel cilindro potrebbe cambiare. ● Rimuovere il refrigerante allo stato liquido. In caso di perdita di refrigerante può essere aggiunto refrigerante aggiuntivo. 36 Processo di installazione Installazione dell’unità esterna gomma 1. Accessori Bordatura “Bordatura” per proteggere i cavi elettrici da spigoli vivi. 2. Selezione del luogo di installazione Selezionare la posizione per un'installazione che soddisfi le seguenti condizioni e, allo stesso tempo, ottenere il consenso dell'utente o del cliente. ● Una posizione in cui circola l'aria. ● Una posizione lontana da radiazioni di calore proveniente da altre fonti di calore. ● Una posizione dalla quale sia facile scaricare l'acqua drenata. ● Una posizione nella quale il rumore e l'aria calda non disturbino i vicini. ● Una posizione dove, durante l'inverno, non ci siano abbondanti nevicate. ● Una posizione dove non ci siano ostacoli vicini alla presa d'aria o allo scarico dell'aria. ● Una posizione dove la presa d'aria non è esposta a forte vento. ● Una posizione circondata su tutti e 4 i lati non è ideale per l'installazione. È necessario uno spazio di 1 m o maggiore sopra al condizionatore. ● Evitare di montare le griglie in una posizione in cui possano avvenire corto circuiti. ● Durante l'installazione di diverse unità, assicurarsi che sia presente abbastanza spazio di aspirazione per evitare corto circuiti. Requisiti dello spazio aperto intorno all'unità Presa d'aria Presa d'aria (Spazio manutenzione) Distanza Caso I Caso II Caso III L1 aprire aprire 500 mm L2 300 mm 300 mm aprire L3 150 mm 300 mm 150 mm Nota: (1) Fissare le parti con le viti. NO Bocchetta (2) Evitare che il vento forte entri di uscita dell'aria direttamente nel foro di uscita Direzione del vento del flusso d'aria. (3) È necessario un metro di distanza dalla parte superiore dell'unità. (4) Non bloccare l'area intorno all'unità. (5) Se l'unità è stata installata in una posizione esposta al vento, installare l'unità in modo che la griglia di uscita NON sia rivolta verso la direzione del vento forte. Bocchetta di uscita dell'aria 3. Installazione dell'unità esterna Fissare l'unità alle fondamenta in maniera corretta secondo le condizioni del luogo di installazione, facendo riferimento alle seguenti informazioni. ● Lasciare abbastanza spazio sul cemento delle fondamenta per fissare i dadi di ancoraggio. ● Una posizione in cui il cemento delle fondamenta sia abbastanza profondo. ● Installare l'unità in modo tale che l'angolo di inclinazione sia inferiore ai 3 gradi. ● Non posizionare l'unità direttamente a terra. Confermare che ci sia abbastanza spazio accanto al foro di drenaggio nella parte bassa, così da assicurare che l'acqua venga drenata senza problemi. Unità Cuscinetto in Base in cemento Bullone di ancoraggio 4. Dimensioni di installazione (unità: mm) Terminale del cablaggio dell'alimentazione elettrica Foro di distribuzione del cablaggio dell'alimentazione elettrica 37 Modello W D H L1 L2 L3 1U07BS1ERA 780 245 540 500 140 256 1U09BS1ERA 780 245 540 500 140 256 1U12BS1ERA 780 245 540 500 140 256 1U18FS1ERA 810 288 688 583 113.5 319.5 1U24GS1ERA 860 308 730 633 113.5 340 Processo di installazione Collegamento delle tubature 1. Dimensione delle tubature 1U07BS1ERA 1U09BS1ERA 1U12BS1ERA 1U18FS1ERA 1U24GS1ERA Tubo per liquidi 6,35x0,8 mm Tubo per gas 9,52x0,8 mm Tubo per liquidi 6,35x0,8 mm Tubo per gas 12,7x0,8 mm Tubo per liquidi 9,52x0,8 mm Tubo per gas 15,88x1,0 mm ● Installare i dadi svasati rimossi dalle tubature per collegarle, quindi svasare le tubature. 2. Collegamento dei tubi ● Per piegare un tubo, curvarlo con un raggio molto ampio per non spaccarli, il raggio deve essere compreso tra 30 e 40 mm o più. ● Collegare prima le tubature del lato del gas poiché renderà il lavoro più semplice. ● Il tubo di collegamento è apposito per R410A. Unione di mezzo Chiave per bulloni Un serraggio eccessivo senza eseguire una centratura accurata può danneggiare le filettature e provocare perdite di gas. Dado svasato Diametro del tubo (ǿ) Coppia di serraggio Lato liquidi 6,35 mm (1/4") 18 N.m Lato liquidi/gas 9,52 mm (3/8") 42 N.m Lato gas 12,7mm (1/2") 55 N.m Lato gas 15,88 mm (5/8") 60 N.m Chiave dinamometrica Prestare attenzione poiché materiali come scarti di sabbia, acqua ecc. non entrino nel tubo. AVVERTENZA La lunghezza standard delle tubature è di C m. Se è superiore a D m, il funzionamento del'unità potrebbe non risultare corretto. Se il tubo deve essere allungato, deve essere caricato il refrigerante, in base a E g/m. Tuttavia, il caricamento del refrigerante deve essere eseguito da personale professionista. Prima di aggiungere altro refri gerante, eseguire lo sfiato dell’aria dalle tubature del refrigerante e dall’unità interna usando una pompa a vuoto, poi caricare il refrigerante. Unità esterna unità esterna B Unità interna B A Unità interna A unità esterna unità esterna Trappola per l’olio B A Unità interna ● Elevazione massima: A massimo ● Se l’altezza A è superiore ai 5 m, un raccoglitore dell’olio deve essere installato ogni 5~7m ● Lunghezza massima: B massimo ● Se la lunghezza B delle tubature è maggiore di D m, il refrigerante deve essere caricato in base a E g/m. 38 A mas- B massimo simo C D E 1U07BS1ERA 10 15 5 7 20 1U09BS1ERA 10 15 5 7 20 1U12BS1ERA 10 15 5 7 20 1U18BS1ERA 15 25 5 7 20 1U24BS1ERA 15 25 5 7 45 Processo di installazione Collaudo della tenuta Dopo aver collegato la tubatura refrigerante, è necessario eseguire un collaudo per verificarne la tenuta. ● Il collaudo della tenuta dell'aria utilizza un serbatoio di azoto per produrre una pressione secondo la modalità di collegamento delle tubature come mostrato nella figura seguente. ● La valvola del gas e del liquido sono tutte in stato di chiusura. Per prevenire l'entrata dell'azoto nel sistema di circolazione dell'unità esterna, serrare la valvola ord?? prima di effettuare la pressione (entrambe le valvole del gas e del liquido ords). Piezometro a bassa pressione Piezometro ad alta pressione Interrompere le valvole completamente chiuse (lato del gas) Esterno Separatore per contatore Interno Completamente serrato Parte svasata Valvola di scarico Completamente serrato Parte svasata Unità interna Tombino Valvola di scarico Serbatoio dell'azoto Unità esterne Interrompere le valvole completamente chiuse (lato del gas) 1) Mettere sotto pressione per più di 3 minuti a 0,3 MPa (3,0 kg/cm2g) Manometro di pressione di linea Brasatura delle tubature 2) Mettere sotto pressione per più di 3 minuti a 1.5 MPa (15 kg/cm2g). Verrà rilevata una forte perdita. 3) Mettere sotto pressione per 24 ore a 3,0 MPa (30 kg/ cm2g). Verrà rilevata una leggera perdita. Manometro di pressione del cilindro Giunto a gomito Cilindro di azoto Grande connettore di inserimento Manutenzione del tubo flessibile ● Controllare se la pressione diminuisce Se la pressione non diminuisce, procedere. Se la pressione diminuisce, cercare il punto di perdita. Mettendo sotto pressione per 24 ore, la variazione di 1°C della temperatura dell'ambiente causerà una variazione di pressione pari a 0,01 MPa (0,1kg/cm2 g). Dovrà essere corretto durante il collaudo. ● Controllare il punto di perdita Nelle fasi da 1) a 3), nel caso in cui avvenga una perdiata di pressione, controllare la perdita in ogni giuntura ascoltando, toccando e usando acqua saponata ecc. per identificare il punto di perdita. Dopo aver individuato il punto di perdita, saldarlo nuovamente, oppure serrare il bullone. 39 Processo di installazione Svuotamento Metodo di svuotamento delle tubature: per usare una pompa del vuoto (p.e.1U 18FS1ERA) 1. Staccare il coperchio della porta di servizio della valvola a 3 vie, il coperchio Valvola a 2 vie della valvola a stelo della valvola a 2 vie e della valvola a stelo della valvola a 3 Valvola a 2 vie vie, collegare la porta di servizio nella protuberanza del tubo flessibile di carico Valvola a 3 vie Valvola a 3 vie (basso) del gruppo monometrico. Poi collegare la protuberanza del tubo di carico flessibile (centrale) alla pompa a vuoto. Valvola di interruzione del liquido Valvola di interruzione del gas Collettore manometro (R410A) Pompa del vuoto (R410A) 2. Aprire a livello basso la manopola del gruppo monometrico, operare la pompa a vuoto. Se l'indicatore (basso) raggiunge la condizione di vuoto immediatamente, controllare di nuovo il punto 1. 3. Aspirare sottovuoto per più di 15 min, Controllare l'indicatore che deve indicare -0.1MPa (76 cm Hg) sul lato della bassa pressione. Dopo avere completato la procedura di scarico, chiudere la manopola in posizione "Lo" del gruppo manometrico ed arrestare il funzionamento della pompa a vuoto. Controlla le condizioni della scala graduata e tenerla per 1-2 min. Se l’indicatore si sposta, malgrado la chiusura, far funzionare di nuovo il degassamento e tornare al principio del punto 3 . Aperto Chiuso Valvola a 2 vie 4. Aprire la valvola a stelo della valvola a 2 vie girandolo di 90 gradi in senso antiorario. Dopo 6 secondi, chiudere la valvola a 2 vie ed eseguire un'ispezione per accertarsi che non ci siano perdite di gas. Valvola a 3 vie Porta di servizio 90 per 6 secondi. 5. Non ci sono perdite di gas? Se ci sono perdite di gas, stringere i giunti del tubo. Se la perdita di arresta, procedere al punto 6. Se la perdita non si arresta, scaricare tutto il refrigerante usando la porta di servizio. Dopo avere attivato di nuovo il degassamento ed aspirato l'aria, riempire con refrigerante raccomandato usando la bombola del gas. Valvola a 2 vie 6. Staccare il tubo flessibile della ricarica dall'apertura di servizio, aprire la valvola a 2 vie e e quella a 3 vie. Ruotare ila valvola a stelo in senso antiorario fino a serrarlo leggermente. 7. Per evitare le perdite di gas, ruotare il tappo della porta di servizio della valvola a 2 vie e di quello della valvola a 3 vie un po' oltre il punto di serraggio, in cui la resistenza aumenta immediatamente. Valvola a 3 vie Valvola a 2 vie Valvola a 3 vie Coperchio valvola a stelo Coperchio valvola a stelo Coperchio porta di servizio ATTENZIONE: Se c'è una perdita di refrigerante del condizionatore, è necessario scaricare tutto il refrigerante. Per prima cosa aspirare, poi caricare il refrigerante liquido nel condizionatore in base alla quantità indicata sull'etichetta. 40 Processo di installazione Cablaggio elettrico AVVISO! PERICOLO DI LESIONI O MORTE ● DISATTIVARE LA CORRENTE ELETTRICA DALL'INTERRUTTORE DIFFERENZIALE O DALLA SORGENTE DI ALIMENTAZIONE PRIMA DI ESEGUIRE QUALSIASI TIPO DI COLLEGAMENTO ELETTRICO. ● METTERE A TERRA TUTTI I COLLEGAMENTI PRIMA DI ESEGUIRE COLLEGAMENTI A TENSIONE. Precauzioni per il cablaggio elettrico ● Il cablaggio elettrico dovrebbere essere eseguito soltanto da personale autorizzato. ● Non collegare più di 3 cavi al blocco del terminale. Utilizzare sempre alette terminali ondulate di tipo rotondo con presa isolata alle estremità dei cavi. ● Utilizzare soltanto conduttori in rame. Opzioni per le dimensioni dei cavi di collegamento e del cavo di alimentazione Scegliere le dimensioni dei cavi e la protezione dei circuiti dalla tabella sottostante. (Questa tabella presenta cavi lunghi 20 m con una perdita di voltaggio minore del 2%.) Interruttore differenziale di corrente Oggetto Dimensione del cavo di alimentaInterruttore autoCapacità nominale del zione (minimo) matico dispositivo di protezione del (2 mm) (A) sovraccarico di corrente (A) Stato Modello Interruttore di circuito con messa a terra Interruttore differenziale (A) Corrente di dispersione (mA) 1U07BS1ERA 1U09BS1ERA 1U12BS1ERA 1U18BS1ERA 1 40 26 2.5 40 30 1U24GS1ERA 1 40 26 4.0 40 30 ● Se il cavo d'alimentazione è danneggiato, deve essere sostituito dal produttore, il suo rappresentante o persona similarmente qualificata. ● Se il fusibile della scatola di controllo è rotto, modificarlo con uno di tipo T 25A/250V ● Il metodo di cablaggio deve essere in linea con le normative di cablaggio locali. ● Il cavo di alimentazione e i cavi di connessione devono essere forniti. ● Tutti i cavi devono avere la Certificazione Europea di Autenticazione. Durante l'installazione, quando vengono interrotti i cavi di connessione, assicurarsi che il cavo della messa a terra sia l'ultimo a venir interrotto. ● 'interruttore del condizionatore deve essere un interruttore di tutti i poli e la distanza fra i suoi due contatti non deve essere inferiore a 3mm. Questi metodi di scollegamento devono essere . ● La distanza tra i suoi due blocchi terminali dell'unità interna e esterna non deve essere superiore ai 5 m. Se superiore, il diametro del cavo deve essere aumentato secondo le normative di cablaggio locali. ● Deve essere installato un interruttore di dispersione. Procedura per il cablaggio 1) Rimuovere le viti che si trovano lateralmente prima di poter estrarre il pannello frontale. 2) Collegare i cavi al blocco terminale in maniera corretta e fissarli con un morsetto equipaggiato accanto al blocco terminale. 3) Ruotare i cavi in maniera corretta e inserirli nell'apertura per eseguire il cablaggio elettrico sul pannello laterale. AVVISO: I CAVI DI INTERCONNESSIONE DEVONO ESSERE CABLATI SECONDO LA FIGURA SOTTOSTANTE. UN CABLAGGIO NON CORRETTO POTREBBE CAUSARE DANNI ALL'APPARECCHIATURA. PER 18 K 24 K PER 07K 09K 12K Unità esterna 1(N) 2 (L) All'unità interna 1U07BS1ERA 1U09BS1ERA 1U12BS1ERA 1U18BS1ERA 1U24GS1ERA Cavi di collegamento 4G 0,75 mm2 4G 0,75 mm2 4G 0,75 mm2 Cavo di alimentazione 3G 1,5 mm2 3G 2,5 mm2 3G 1,5 mm2 Modello 3 (C) { N ALIMENTAZIONE L 1(N ) 2 (L) 3 (C ) ALIMENTAZIONE 1(N) 2 (L) 3 (C) All'unità interna Unità esterna 41 Risoluzione dei problemi dell'unità esterna ATTENZIONE ● QUEST'UNITÀ SI AVVIERÀ ISTANTANEAMENTE NEL MOMENTO IN CUI SARÀ FORNITA ENERGIA ELETTRICA SENZA BISOGNO DI ACCENSIONE. ASSICURARSI DI ESEGUIRE L'OPERAZIONE DI SPEGNIMENTO PRIMA DI INTERROMPERE L'EROGAZIONE DI ENERGIA ELETTRICA PER LA MANUTENZIONE. ● Questa unità possiede una funzione di riavvio automatico dopo il recupero dopo l'interruzione dell'erogazione di energia elettrica. 1. Prima di eseguire il collaudo dell'avvio (per tutti i modelli con pompa di calore) Assicurarsi che l'interruttore di corrente elettrica (interruttore principale) dell'unità sia stato attivo per più di 12 ore per fornire energia al riscaldatore del basamento prima delle operazioni. 2. Collaudo di avvio Avviare l'unità per 30 minuti senza interruzioni e controllare quanto segue. ● Pressione di aspirazione nelle giunture di controllo per la valvola di servizio delle tubature del gas. ● Scarico della pressione alla giunture di controllo nella tubatura di scarico del compressore. ● Differenza di temperatura tra l'aria di ritorno e l'aria fornita all'unità interna. Il tempo di lampeggiamento dei LED sulla scheda principale 1 2 Descrizione dei problemi Analisi e diagnosi 9 10 Errore EEPROM Errore IPM Errore di comunicazione tra la scheda madre e le comunicazioni del modulo SPDU Protezione alta pressione Dispositivo di protezione del sovraccarico di corrente del modulo (solo per lo spud) Dispositivo di protezione della mancanza di voltaggio del modulo (solo per lo spud) Dispositivo di protezione della temperatura di scarico del compressore Anomalie nel motore CC Anomalie nel sensore tubature 11 Errore nel sensore di temperatura di aspirazione 12 13 Anomalia nel sensore dell'ambiente esterno Anomalie nel sensore del compressore di scarico Errore di comunicazione tra l'unità interna e l'unità esterna 4 5 6 8 15 16 Mancanza di refrigerante o controllo di eventuali perdite nell'unità 17 Errore nella valvola inversa a 4 vie 18 19 25 25 25 Blocco del compressore (solo per spud) Errore nella selezione del modulo circuito PWM Sovraccarico durante la fase U del compressore Sovraccarico durante la fase V del compressore Sovraccarico durante la fase W del compressore Errore EEPROM nella scheda principale Errore IPM Errore di comunicazione per più di 4 min Alta pressione del sistema superiore ai 4,15 MPa Inviare dal modulo Temperatura di scarico del compressore superiore ai 110°C Blocco del motore CC o errore nel motore Sensore tubature di corto circuito o circuito aperto Quando il cablaggio del compressore è errato o il collegamento non è corretto Corto circuito o circuito aperto del sensore ambiente esterno Corto circuito o circuito aperto del sensore di scarico Errore di comunicazione per più di 4 min Allarme e interruzione se rilevato TD-tci>=75 che duri per un minuto dopo che il compressore è stato attivo per 10 min in modalità condizionatore, controllare eventuali perdite nell'unità. Allarme e interruzione se rilevato Tm<=75 che duri per un minuto dopo che il compressore è stato attivato per 10 min in modalità condizionatore, controllare l'errore se appare 3 volte in un'ora. Il compressore interno è bloccato in maniera anomala Selezione del modulo PWM del circuito errata La corrente durante la fase U del compressore è troppo elevata La corrente durante la fase V del compressore è troppo elevata La corrente durante la fase W del compressore è troppo elevata Haier Group Indirizzo: N. 1 Haier Road, Hi-tech Zone, Qingdao 266101, Repubblica Popolare Cinese Contatti: TEL +86-532-8893-6943; FAX +86-532-8893-1010 Sito Internet: www.haier.com 42 14 Haier Industrial Park, No.1 Haier Road, Qingdao, P.R.Chine CONFORMITÉ DES MODÈLES À LA LÉGISLATION EUROPÉENNE INFORMATIONS IMPORTANTES CONCERNANT LE LIQUIDE RÉFRIGÉRANT UTILISÉ CE Tous les appareils sont conformes aux directives Européennes suivantes : - Directive basse tension 73/23/EEC - Directive basse tension 2006/95/EC - Compatibilité électro-magnétique Y 89/336/EEC - Compatibilité électro-magnétique Y 2004/108/EC Contient des gaz à effet de serre uorés couverts par le protocole de Kyoto. R410A 1= kg 2 2= kg 1+2= kg 1 ROHS Les appareils répondent aux exigences de la directive 2002/95/ EEC du parlement européen et du conseil sur la limitation des substances dangereuses dans les Équipements Électriques et Électroniques (Directive UE RoHS). WEEE Conformément à la Directive 2002/96/CE du Parlement Européen, nous informons ici-même le consommateur des conditions d'élimination des appareils électriques et électroniques. CONDITIONS D'ÉLIMINATION L'appareil de climatisation est marqué de ce symbole. Ceci signifie que les produits électriques et électroniques ne doivent pas être mêlés aux déchets ménagers non-triés. Ne pas tenter de démonter le système par soi-même : le démontage du système de climatisation, le traitement du liquide réfrigérant, de l'huile et d'autres pièces doivent être effectués par un installateur qualifié conformément à la législation locale et nationale. Les climatiseurs doivent être traités dans des installations spécialisées pour réutilisation, recyclage et récupération. S'assurer que le produit est éliminé de façon correcte permet d'aider à éviter des conséquences potentielles négatives sur l'environnement et la santé humaine. Merci de contacter l'installateur ou les autorités locales pour plus d'information. Les piles doivent être enlevées de la télécommande et faire l'objet d'une élimination séparée conformément à la législation locale et nationale. A F B C D E Cet appareil contient des gaz à effet de serre fluorés couverts par le protocole de Kyoto. Ne pas ventiler à l'air. Type de réfrigérant : R410A Valeur de GWP*: 1975 GWP = global warming potential - potentiel de réchauffement de la planète. Merci de remplir à l'encre indélébile; •1 La charge de réfrigérant usine de l'appareil •2 la quantité supplémentaire de réfrigérant chargée sur place et • 1+2 la charge totale de réfrigérant. sur l'étiquette de charge de réfrigérant fournie avec l'appareil. L'étiquette renseignée doit être collée à proximité du port de chargement de l'appareil (par ex.sur l'intérieur du couvercle de valeur d'arrêt). A Contient des gaz à effet de serre fluorés couverts par le protocole de Kyoto. Protocole B Charge de réfrigérant standard de l'unité : voir sur la plaque signalétique de l'unité C Quantité supplémentaire de réfrigérant chargée sur place D Charge totale de réfrigérant E Unité extérieure F Cylindre réfrigérant et collecteur de chargement Schéma d'installation des unités intérieures et extérieures Les modèles utilisent le réfrigérant R410A sans HFC. Pour l'installation des unités intérieures, veuillez vous référer au manuel d'installation fourni avec les unités. (Le diagramme illustre une unité intérieure à montage mural.) Il faut faire particulièrement attention au soulèvement du tuyau de vidange. plus de 15 cm Pièces en option pour la tuyauterie A Ruban non adhésif B Ruban adhésif G plus de 10 cm C Selle (L.S) avec vis Raccordement du câble électrique D entre unités intérieures et extérieures E Tuyau de vidange F Matériau d'isolation thermique Disposition des directions de la tuyauterie Gauche G Cache trou de tuyauterie plus de 10 cm F Arrière gauche Arrière droite A Droite C En bas plus de 20 cm plus de 20 cm • • Fixation de l'unité extérieure Les marques de A à G sur la gure, représentent les références de pièce. La distance entre l'unité intérieure et le sol doit être supérieure à 2 m. D • Fixez l'unité horizontalement et solidement sur le béton ou un bloc de béton avec des boulons (10 mm) et des écrous • Lorsque l'unité doit être installée sur un mur, un toit ou la toiture, xez un support avec des clous ou des ls en tenant compte des séismes et vents forts. • Si des vibrations risquent d'affecter la maison, xez l'unité avec un tapis anti-vibration E plus de 60 cm plus de 25 cm SORTIE D'AIR 4  ENTRÉE D'AIR CONNEXION DE LA TUYAUTERIE ET DU CÂBLAGE ÉLECTRIQUE 4 TUYAU DE VIDANGE Compresseur (Intérieur de l'unité) • L'illustration ci-dessus des unités intérieure et extérieure, n'est indiquée qu'à titre de référence. Veuillez tenir compte des particularités du modèle acheté. 43 Consignes de sécurité Pour un fonctionnement adéquat du climatiseur, veuillez lire attentivement les informations suivantes. Vous trouverez ci-dessous trois types de consignes de sécurité et de suggestions. AVERTISSEMENT La mauvaise utilisation de l'appareil peut entraîner de graves conséquences, comme la mort ou des blessures graves. ATTENTION La mauvaise utilisation de l'appareil peut entraîner des blessures ou des dommages sur l'appareil. Dans certain cas, les conséquences peuvent être graves. INSTRUCTION : Ces informations garantissent la bonne utilisation de l'appareil. Symboles utilisés dans les illustrations : indique une action à éviter. : indique qu'il faut se conformer aux instructions importantes. : indique une pièce qu'il faut relier à la terre. : attention, risque d'électrocution (Ce symbole gure sur l'étiquette de l'unité principale.) Une fois ce manuel lu, conservez-le pour le transmettre aux utilisateurs de l'appareil. L'utilisateur doit conserver ce manuel à portée de main, et le remettre aux réparateurs ou aux personnes qui vont déplacer l'appareil. Assurez-vous également de pouvoir le transmettre au nouvel utilisateur, si l'appareil change de propriétaire. Assurez-vous de suivre les importantes consignes de sécurité ci-dessous. AVERTISSEMENT • En cas de présence de phénomène anormal (par exemple une odeur de brûlé), Mise hors tension coupez immédiatement l'alimentation électrique et contactez votre fournisseur pour trouver une solution. Dans ce cas, continuer d'utiliser le climatiseur va l'endommager et peut entraîner une électrocution ou un incendie. • Lorsque le climatiseur est utilisé sur une longue période, vériez l'absence de dommage au niveau de sa base. Si une base endommagée n'est pas réparée, l'unité peut tomber et provoquer des accidents. • Ne pas démonter la sortie de l'unité extérieure. L'exposition au ventilateur est très dangereux et peut vous blesser. • En cas de maintenance ou de réparation, faites appel à votre fournisseur. Une mauvaise maintenance et réparation peut entraîner une fuite d'eau, une électrocution et un incendie. AVERTISSEMENT • Aucun objet et aucune personne ne doit être placé, ou se tenir debout, sur l'unité extérieure. La chute d'objet ou de personne peut entraîner des accidents. • Ne faites pas fonctionner le climatiseur avec les mains humides. Risque d'électrocution. • N'utilisez qu'un fusible du type recommandé. N'utilisez pas de câble ou d'autre matériaux pour remplacer le fusible. Cela peut entraîner des défaillances ou un risque d'incendie. • Utilisez correctement le conduit de sortie, pour assurer un refoulement efcace. Une mauvaise utilisation du conduit peut entraîner une fuite d'eau. • Disjoncteur électrique installé. Une électrocution est fréquence sans disjoncteur. • Le climatiseur ne peut pas s'installer dans un environnement en cas de présence de gaz inammables. Ces gaz à proximité du climatiseur peuvent entraîner un incendie. Veuillez coner l'installation du climatiseur à votre fournisseur. Une mauvaise installation peut entraîner une fuite d'eau, une électrocution et un incendie. • Appelez le fournisseur pour effectuer des mesures et éviter les fuites de liquide réfrigérant. Si le climatiseur est installé dans une petite pièce, assurez-vous d'avoir pris toutes les mesures pour empêcher les accidents d'asphyxie en risque de fuite de réfrigérant. • Le fournisseur doit être responsable de l'installation ou de la réparation du climatiseur. Une mauvaise installation peut entraîner une fuite d'eau, une électrocution et un incendie. • Branchement du câble de mise à la terre. Le câble de mise à la terre ne doit pas être connecté au tuyau de gaz, au tuyau d'eau, au paratonnerre ou à la ligne téléphonique. Une mauvaise mise à la terre peut entraîner une électrocution. 44 Mise à la terre Consignes de sécurité AVERTISSEMENT • Soyez attentif à bien suivre chaque étape de ce manuel au mo• L'installation de l'unité doit être effectuée par un professionnel. ment d'installer l'unité. La mauvaise installation de l'appareil par une personne non Une mauvaise installation peut entraîner des fuites d'eau, une qualiée, peut entraîner des fuites d'eau, une électrocution ou un électrocution, une émission de fumée ou un incendie. incendie. • Tous les travaux d'électricité doivent être réalisés par un électricien qualié, conformément aux réglementations locales et aux instructions du présent manuel. Sécurisez un circuit exclusif pour l'unité. Une mauvaise installation ou un manque de capacité au niveau • N'utilisez que les câbles spéciés pour le câblage. Branchez du circuit, peut entraîner un dysfonctionnement de l'unité, préfermement chaque câble et assurez-vous qu'ils ne sont pas trop senter un risque d'électrocution, une émission de fumée ou un tendus au niveau du bornier. incendie. Les câbles qui ne sont pas bien branchés, peuvent générer de la chaleur et provoquer un incendie. • Fixez de façon sûre le cache-borne (panneau) sur l'unité. Si l'appareil est mal installé, de la poussière et/ou de l'eau peut • Prenez les mesures de sécurité nécessaires contre les thyphons pénétrer dans l'unité et entraîner alors un risque d'électrocution, et les tremblements de terre, de façon à ce que l'unité ne bascule d'émission de fumée ou d'incendie. pas. • Placez l'unité sur une surface stable et de niveau, capable de supporter le poids de l'unité pour que celle-ci ne bascule ni ne tombe, de façon à éviter tout risque de blessure. • N'effectuez aucune modication ou altération sur l'appareil. En cas de problème, consultez le fournisseur. Si les réparations ne sont pas effectuées correctement, l'unité peut présenter des fuites d'eau, ou entraîner un risque d'électrocution, il peut générer une émission de fumée, ou un incendie. • N'utilisez que du réfrigérant R410A, comme indiqué sur l'unité, lorsque vous installez ou déplacez l'unité. L'utilisation d'un autre réfrigérant ou la pénétration d'air dans le circuit de l'unité peut entraîner un fonctionnement en cycle anormal. Un cycle anormal peut entraîner l'explosion de l'unité. AVERTISSEMENT • Lorsque vous installez l'unité dans une petite pièce, protégezvous contre l'hypoxie pouvant survenir en cas de fuite du réfrigérant d'un niveau supérieure au seuil critique. • En cas de fuite de gaz réfrigérant, assurez une bonne ventilation Consultez le fournisseur pour connaître les mesures à prendre. de la pièce. • Lorsque vous repositionnez un climatiseur, consultez le fournisSi le gaz réfrigérant qui a fuit est exposé à une source de chaseur ou un spécialiste. leur, un gaz nocif peut se dégager. Une mauvaise installation peut entraîner des fuites d'eau, une • Avec les climatiseurs du type All-Fresh, l'air extérieur peut être électrocution, ou un incendie. directement soufé à l'intérieur de la pièce, lorsque le thermostat • Une fois le service d'entretient effectué, contrôlez l'absence de est coupé. Le prendre en considération lors de l'installation de fuite du gaz réfrigérant. l'unité. Si le gaz réfrigérant qui a fuit est exposé à une source de chaL'exposition directe à l'air extérieur peut entraîner un risque pour leur, comme un radiateur soufant, une cuisinière ou un grill élecla santé et peut également engendrer la détérioration des dentrique, un gaz nocif peut se dégager. rées alimentaires. • Ne touchez pas les ailettes de l'échangeur thermiques à mains nues, elles sont pointues et dangereuses. • N'essayez pas de contourner les fonctionnalités de sécurité des appareils et ne modiez pas les réglages. L'altération des fonctionnalités de sécurité de l'unité, comme le pressostat et le thermocontact, ou l'utilisation de pièces autres que celles proposées par le fournisseur ou le spécialiste, peut entraîner un incendie ou une explosion. • N'utilisez que les pièces spéciées. L'installation de l'unité doit être effectuée par un professionnel. Une mauvaise installation peut entraîner des fuites d'eau, une électrocution, une émission de fumée ou un incendie. 45 Consignes de sécurité Précautions pour la manipulation des unités lorsque du réfrigérant R410A est utilisé Avertissement N'utilisez pas le tuyau du réfrigérant existant • L'ancien réfrigérant et l'huile du réfrigérateur présents dans le tuyau existant, contiennent une grande quantité de chlore, ce qui va détériorer la qualité de l'huile du réfrigérateur dans la nouvelle unité. • Le R410A est un réfrigérant à haute pression. Son utilisation dans le tuyau existant va entraîner sa ssuration. Utilisez une pompe à vide avec clapet de non-retour en circuit fermé. • Si d'autres types de clapets sont utilisé, l'huile de la pompe à vide va retourner dans le cycle du réfrigérant et provoquer la détérioration de l'huile du réfrigérateur. N'utilisez pas les outils suivants, ayant déjà été utilisés avec les réfrigérants conventionnels. Préparez des outils à utiliser exclusivement avec le R410A. (Collecteur de jauge, tubulure de charge, détecteur de fuite de gaz, clapet de non-retour en circuit fermé, base de chargement du réfrigérant, jauge à vide et équipement de récupération du réfrigérant.) • Si le réfrigérant et/ou l'huile réfrigérante qui reste sur ces outils Gardez les surfaces intérieures et extérieures des tuyaux propres est mélangé avec le R410, ou si de l'eau est mélangée avec le et exempts de contaminants, comme le soufre, les oxydes, la pousR410A, le réfrigérant sera détérioré. sières/les particules de saleté, les huiles et la moisissure. • Le R410A ne contient pas de chlore. Les détecteurs de fuite de • La présence de contaminants dans le tuyau du réfrigérant va gaz pour les réfrigérateurs conventionnels, ne fonctionnent pas entraîner la détérioration de l'huile réfrigérante. avec ce type de réfrigérant. Avertissement Rangez la tuyauterie à utiliser pour l'installation à l'intérieur et gar- N'utilisez pas de cylindre de chargement dez les deux extrémités de la tuyauterie scellées jusqu'au brasage. • L'utilisation d'un cylindre de chargement va modier la composition du réfrigérant et entraîner une perte de puissance. (conservez les coudes et autres joints dans leur emballage en plastique.) • Si de la poussière, de la saleté ou de l'eau pénètre dans le cycle du réfrigérant, l'huile de l'unité peut se détériorer, ou le compresseur mal fonctionner. Faites particulièrement attention à la manipulation des outils. • L'introduction d'objets étrangers, comme la saleté, la poussière ou l'eau dans le cycle du réfrigérant, va entraîner la détérioration Utilisez une petite quantité d'huile d'ester, d'huile d'éther ou d'alkylde l'huile de la machine réfrigérante. bensène pour enduire les évasements et les joints à brides. • Une grande quantité d'huile minérale peut entraîner la détérioration de l'huile de la machine réfrigérante. N'utilisez que le réfrigérant R410A. Utilisez du réfrigérant liquide pour charger le système. • Chargez l'unité avec du gaz réfrigérant va entraîner la modica- • L'utilisation de réfrigérants contenant du chlore (comme le R22), va entraîner la détérioration du réfrigérant. tion de la composition du réfrigérant dans le cylindre. Les performances en seront amoindries. Avant d'installer l'unité Avertissement Lorsque l'unité est installé dans un hôpital, prenez les mesures qui s'imposent contre le bruit. • Les équipements médicaux de haute fréquence peuvent interférer avec le fonctionnement normal du climatiseur, ou le climatiseur peut interférer avec le fonctionnement normal des équipeN'utilisez pas l'unité pour conserver des aliments, des animaux, des ments médicaux. plantes, des objets ou pour tout autre usage particulier. N'installez pas l'unité dans un environnement pouvant être sujet à une fuite de gaz inammable. • Le gaz qui a fuit et qui s'accumule autour de l'unité, peut être à l'origine d'un incendie. • L'unité n'est pas conçue fournir les conditions adéquates de préservation de la qualité de ces articles. N'utilisez pas l'unité dans un environnement inhabituel. • L'utilisation de l'unité en présence d'une grande quantité d'huile, de vapeur, d'acide, de solvants alcalins ou de types particuliers d'embruns, peut entraîner une chute notable des performances et/ou le dysfonctionnement de l'appareil, et présente un risque d'électrocution, d'émission de fumée ou d'incendie. • La présence de solvants organiques, de gaz corrosifs(comme l'ammoniac, les composés du soufre et les acides) peuvent entraîner une fuite de gaz ou d'eau. Ne placez pas l'unité sur ou par-dessus des éléments qui ne doivent pas être mouillés. • Lorsque le niveau d'humidité dépasse les 80%, ou lorsque le système de vidange est obturé, de l'eau peut goutter des unités intérieures. • L'installation d'un système de vidange centralisé pour l'unité extérieure peut également être pris en considération pour éviter les gouttes d'eau qui s'échappent des unités extérieures. 46 Consignes de sécurité Avant d'installer (de repositionner) l'unité ou d'effectuer des travaux électrique Avertissement Mise à la terre de l'unité. • Ne branchez pas la mise à la terre de l'unité sur les tuyaux de gaz, les tuyaux d'eau, le paratonnerre ou aux bornes de mise à la terre des téléphones. Une mauvaise mise à la terre présente un risque d'électrocution, d'émission de fumée, d'incendie. Le bruit provoqué par une mauvaise mise à la terre peut également entraîner le dysfonctionnement de l'unité. Assurez-vous que les câbles ne sont pas soumis à une tension. • Si les câbles sont trop tendus, ils peuvent se casser ou générer de la chaleur/une émission de fumée et entraîner un incendie. Ne vaporisez pas de l'eau sur les climatiseurs. Ne les immergez pas dans l'eau. • La présence d'eau sur l'unité présente un risque d'électrocution. Contrôlez périodiquement la plate-forme sur laquelle l'unité est placée pour éviter que l'unité ne tombe en cas de dommage. • Si l'unité est placée sur une plate-forme endommagée, elle peut basculer et blesser quelqu'un. Lors de l'installation des tubulures de vidange, suivez les instruction du manuel et assurez-vous qu'elles vidangent correctement l'eau Installez un disjoncteur pour fuite de courant au niveau de la source pour éviter toute condensation. • En cas de mauvaise installation, il y a risque de fuites d'eau et de d'alimentation, pour éviter tout risque d'électrocution. dommages aux meubles voisins. • Sans disjoncteur pour fuite de courant, il existe un risque d'électrocution, d'émission de fumée ou d'incendie. Veuillez vous débarrasser de façon adéquate des matériaux d'emballage. Utilisez les disjoncteurs et les fusibles (disjoncteur de courant • Des objets, comme des clous, peuvent se trouver dans l'embalélectrique, interrupteur à distance <interrupteur+fusible de type lage. Veuillez vous en débarrasser de façon adéquate pour éviter B>, disjoncteur à boîtier moulé) présentant la capacité d'intensité de vous blesser. adéquate. • Les sacs en plastique présentent un risque suffocation pour les • L'utilisation de fusibles à grande capacité, de câble en acier ou enfants. Pour éviter tout accident, déchirez les sacs en plastique en cuivre, peut endommager l'unité ou générer une émission de avant de les jeter. fumée ou un incendie. Avant d'effectuer le test de fonctionnement Avertissement Pour éviter tout risque d'électrocution, ne touchez pas aux interrup- Ne coupez pas immédiatement l'alimentation après avoir arrêté l'unité. teurs avec les mains mouillées. • Laissez au moins cinq minutes avant de mettre l'unité hors tension. L'unité risque sinon de présenter des fuites d'eau ou Ne touchez pas les tuyaux de réfrigérant à main nue pendant et d'autres problèmes. immédiatement après le fonctionnement de l'appareil. • Selon l'état du réfrigérant dans le circuit, certaines pièces de l'unité, comme les tuyaux et le compresseur, peuvent devenir très froids ou très chauds. Risque de gelures ou de brûlures. Ne faites fonctionner l'unité qu'une fois les panneaux et les protections de sécurité bien en place. • Ces éléments permettent de protéger les utilisateurs des accidents liés aux éléments mobiles, à la haute température ou aux pièces sous haute tension. Ne faites pas fonctionner l'unité sans ltres à air. • Les particules de poussière dans l'air peuvent obturer le système et entraîner son dysfonctionnement. 47 À lire avant l'installation Éléments à contrôler (1). Vériez le type de réfrigérant utilisé dans l'unité à réparer. Type de réfrigérant : R410A (2). Contrôlez la défaillance de l'unité à réparer. Vériez dans le manuel d'entretien les symptômes en rapport avec le cycle du réfrigérant. (3). Assurez-vous d'avoir lu avec attentions les consignes de sécurité qui gurent au début de ce document. (4). En cas de fuite de gaz, ou si le réfrigérant restant est exposé à une amme ouverte, un gaz toxique, l'acide uorhydrique, peut se former. Le lieu de l'intervention doit être bien ventilé. AVERTISSEMENT • Installez les nouveaux tuyaux immédiatement après avoir retiré les anciens pour que l'humidité ne pénètre pas dans le circuit du réfrigérant. • Le chlore présent dans certains types de réfrigérants, comme le R22, peut entraîner la détérioration de l'huile de la machine réfrigérante. Outils et matériaux nécessaires Préparez les outils suivants et les matériaux nécessaires pour l'installation et l'entretien de l'unité. Outils nécessaires lorsque le réfrigérant R410A est utilisé (adaptativité des outils à utiliser avec les réfrigérants R22 et R407C). 1. À utiliser exclusivement avec le R410A (à ne pas utiliser avec le R22 ou le R407C) Outils/Matériaux Utilisation Remarques Collecteur de jauge Évacuation, chargement du réfrigérant 5,09 MP du côté haute pression. Tubulure de charge Évacuation, chargement du réfrigérant Diamètre de la tubulure supérieur aux tubulures conventionnelles. Équipement de récupération du réfrigérant Récupération du réfrigérant Cylindre réfrigérant Pour le chargement du réfrigérant Notez le type de réfrigérant. Couleur rose en haut du cylindre. Port de chargement du cylindre réfrigérant Pour le chargement du réfrigérant Diamètre de la tubulure supérieur aux tubulures conventionnelles. Ecrou d'évasement Connexion de l'unité à la tuyauterie Utilisez des écrous d'évasement du type 2. 2. Outils et matériaux pouvant être utilisés avec le réfrigérant R410 avec quelques restrictions Outils/Matériaux Utilisation Détecteur de fuite de gaz Détection des fuites de gaz Remarques Il est possible d'utiliser ceux compatibles avec le réfrigérant du type HFC. Pompe à vide Séchage sous vide Peut être utilisé si un adaptateur de non-retour en circuit fermé est installé. Outil d'évasement Outil pour l'évasement des tuyaux Des modications ont été apportées dans les dimensions d'évasement. Veuillez vous référer à la page suivante. Équipement de récupération du réfrigérant Récupération du réfrigérant Peut être utilisé si conçu pour une utilisation avec le réfrigérant R410A. 3. Outils et matériaux utilisés avec le réfrigérant R22 ou R407C pouvant également être utilisés avec le réfrigérant R410A. Outils/Matériaux Utilisation Pompe à vide avec clapet de non-retour Séchage sous vide Machine à plier Pour plier les tuyaux Clé dynamométrique Pour serrer les écrous d'évasement Coupe-tube Pour découper les tuyaux Machine à souder et bouteille d'azote Pour souder les tuyaux Instrument de mesure du chargement de réfrigérant Pour le chargement du réfrigérant Videmètre Pour mesurer la raréfaction de l'air Remarques Seuls les diamètres ment plus grandes. 12,70 (1/2'') et 15,88(5/8'') présentent des dimensions d'évase- 4. Outils et matériaux ne devant pas être utilisés avec le réfrigérant R410A Outils/Matériaux Utilisation Remarques Cylindre de chargement Pour le chargement du réfrigérant Ne doit pas être utilisé avec les unités du type R410. Les outils à utiliser avec le réfrigérant R410A doivent être manipulés avec une attention particulière. L'humidité et la poussière ne doivent pas entrer dans le cycle. 48 À lire avant l'installation Matériaux des tuyaux Types de tuyaux en cuivre (référence) Pression de fonctionnement maximale Réfrigérants applicables 3,4 MPa R22, R407C 4,15 MPa R410A • Utilisez des tuyaux conformes aux normes locales. Matériaux des tuyaux/épaisseur radiale Utilisez les tuyaux en cuivre désoxydé au phosphore. La pression de fonctionnement des unités utilisant du R410A est plus importante que celle des unités utilisant du R22. Les tuyaux à utiliser doivent donc présenter une épaisseur radiale au moins égale aux indications du tableau ci-dessous. (Les tuyaux présentant une épaisseur radiale inférieure ou égale à 0,7 mm, ne doivent pas être utilisés.) Taille (mm) Taille (pouce) Épaisseur radiale (mm) 6.35 1/4'' 0,8t 9.52 3/8" 0,8t 12.7 1/2" 0,8t 15.88 5/8" 1,0 t 19.05 3/4" 1,0 t Type Tuyaux en O Tuyaux en 1/2H ou en H • Même s'il est possible d'utiliser des tuyaux en O d'une taille maximale de 19,05 (3/4") avec les réfrigérants conventionnels, utilisez des tuyaux en 1/2H pour les unités utilisant du réfrigérant R410A. (Les tuyaux en O peuvent être utilisés si leur taille est de 19,05 et que leur épaisseur radiale est de 1,2t.) • Le tableau répertorie les normes au Japon. Utilisez ce tableau comme référence et choisissez les tuyaux qui sont conformes aux normes locales. Outil pour l'évasement (tuyaux en O et OL uniquement) Pour augmenter l'étanchéité à l'air, les dimensions de l'évasement pour les unités qui utilisent le réfrigérant R410A sont plus importantes que celles pour les unités qui utilisent le réfrigérant R22. Dimensions d'évasement (mm) Taille Dimension A R410A R22 6.35 1/4'' 9.1 9.0 9.52 3/8" 13.2 13.0 12.7 1/2" 16.6 16.2 15.88 5/8" 19.7 19.4 19.05 3/4" 24.0 23.3 Dimension A Dimensions externes des tuyaux Si un outil d'évasement du type à embrayage est utilisé pour usiner des évasements sur les unités qui utilisent le réfrigérant R410A, la partie du tuyau qui dépasse doit faire entre 1,0 et 1,5 mm. Utilisez la jauge pour tuyau en cuivre pour ajuster la longueur de la partie qui dépasse. Ecrou d'évasement Les écrous d'évasement du type 2 sont utilisés, plutôt que les écrous du type 1, de façon à optimiser la résistance. La taille de certains écrous d'évasement a également été modiée. Dimensions des écrous d'évasement (mm) Dimensions externes des tuyaux Taille Dimension B R410A (Type2) R22 (Type1) 6.35 1/4'' 17.0 17.0 9.52 3/8" 22.0 22.0 12.7 1/2" 26.0 24.0 15.88 5/8" 29.0 27.0 19.05 3/4" 36.0 36.0 Dimension B • Le tableau répertorie les normes au Japon. Utilisez ce tableau comme référence et choisissez les tuyaux qui sont conformes aux normes locales. 49 À lire avant l'installation Test d'étanchéité à l'air AUCUNE modication par rapport à la méthode conventionnelle. Remarquez qu'un détecteur de fuite de réfrigérant pour le R22 ou le R407C, est incapable de détecter une fuite de R410A. Lampe haloïde Détecteur de fuite de R22 ou R407C Se conformer strictement aux éléments suivants : 1. Pressurisez les équipement à l'azote, jusqu'à atteindre la pression de calcul. Vériez ensuite l'étanchéité à l'air de l'équipement. Les variations de température sont à prendre en compte. 2. Lorsque vous recherchez les emplacements des fuites en utilisant un réfrigérant, assurez-vous d'utiliser le R410A. 3. Assurez-vous que le R410A est en état liquide au moment du chargement. Raisons : 1. L'utilisation de l'oxygène comme gaz sous pression, peut entraîner une explosion. 2. Le chargement avec du gaz R410A va entraîner la modication de la composition du réfrigérant restant dans le cylindre. Ce réfrigérant ne peut alors plus être utilisé. Mise sous vide 1. Pompe à vide avec clapet anti-retour Une pompe à vide avec un clapet anti-retour est requise pour empêcher le retour de l'huile de la pompe dans le circuit du réfrigérant lorsque l'alimentation de la pompe à vide est coupée (en cas de coupure d'électricité). Il est également possible d'équiper ultérieurement la pompe à vide d'un clapet anti-retour. 2. Degré de vide standard de la pompe à vide Utilisez une pompe pouvant atteindre les 65 Pa ou moins, après 5 minutes de fonctionnement. En outre, assurez-vous d'utiliser une pompe à vide bien entretenue et huilée en utilisant l'huile spéciée. Si la pompe à vide n'est pas bien entretenue, le degré de vide peut être trop bas. 3. Précision requise du videmètre Utilisez un videmètre pouvant mesurer jusqu'à 650 Pa. N'utilisez pas de collecteur de jauge général, car il est incapable de mesurer un vide de 650 Pa. 4. Durée de la mise sous vide Faire le vide de l'équipement pendant environ 1 heure à partir du moment où la pression a atteint les 650 Pa. Une fois le vide atteint, laissez l'équipement pendant 1 heure, et assurez-vous que le vide ne se perd pas. 5. Consignes d'utilisation lorsque la pompe à vide est stoppée Pour éviter tout retour de l'huile de la pompe à vide, ouvrez le clapet de décharge du côté pompe à vide, ou dévisser le tuyau de charge pour faire rentrer de l'air avant d'interrompre le fonctionnement. La même consigne d'utilisation est à utiliser lorsque l'appareil fonctionne avec une pompe à vide équipée d'un clapet anti-retour. Chargement du réfrigérant Le R410A doit être en état liquide au moment du chargement. Raisons : Le R410A est un réfrigérant pseudo-azéotropique (point d'ébullition R32=-52oC, R125=-4952oC). Il peut quasiment se manipuler de la même façon que le R22. Assurez-vous cependant de procéder au remplissage du réfrigérant du côté liquide. Si vous l'effectuez du côté gaz, cela va modier la composition du réfrigérant dans le cylindre. Remarque • Dans le cas d'un cylindre doté d'un siphon, le R410A liquide est chargé sans retourner le cylindre. Contrôlez le type de cylindre avant de procéder au chargement. Mesures à prendre en cas de fuite de réfrigérant Lorsque le réfrigérant fuit, il est possible d'introduire du réfrigérant additionnel. (Ajoutez du réfrigérant du côté liquide) Caractéristiques des réfrigérants conventionnels et des nouveaux réfrigérants • Le R410A est un réfrigérant pseudo-azéotropique. Il peut se manipuler quasiment de la même façon qu'un réfrigérant simple, du type R22. Cependant, si du réfrigérant est retiré dans sa phase vapeur, la composition du réfrigérant dans le cylindre va être quelque peu modiée. • Retrait du réfrigérant en phase liquide. Du réfrigérant additionnel peut être ajouté en cas de fuite de réfrigérant. 50 Procédure d'installation Installation de l’unité extérieure 1. Accessoires Bordure "Bordure" pour protéger les câbles électriques d'un bord saillant. 2. Choix de l'emplacement de l'installation Choisissez l'emplacement de l'installation de façon à satisfaire les conditions suivantes, tout en répondant aux besoins du client ou de l'utilisateur. • Placez l'appareil dans un endroit où l'air circule bien. • Placez l'appareil dans un endroit à distance d'une radiation de chaleur provenant d'autres sources de chaleur. • Placez l'appareil dans un endroit compatible avec le versement de l'eau de vidange. • Placez l'appareil dans un endroit où le bruit et l'air chaud ne dérangent pas le voisinage. • Placez l'appareil dans un endroit qui n'est pas soumis à de fortes chutes de neige en hiver. • Placez l'appareil dans un endroit où l'entrée et la sortie d'air ne sont pas obturées. • Placez l'appareil dans un endroit où la sortie d'air n'est pas exposée à un fort vent. • Le positionnement de l'appareil alors que ses quatre faces sont contre des éléments, ne convient pas à son installation. Il faut un espace au-dessus de l'appareil, d'au moins 1 mètre. • Évitez d'installer des grilles de transfert aux endroits qui présentent un risque de court-circuit. • Lorsque vous installez plusieurs unités, vériez que l'espace d'aspiration est sufsant pour éviter tout court-circuit. Exigence concernant l'espace ouvert autour de l'unité Entrée d'air Entrée d'air Distance L1 L2 L3 Cas I ouvert 300 mm 150 mm Cas II ouvert 300 mm 300 mm Cas III 500 mm ouvert 150 mm Remarque : (1) Fixez les pièces avec des vis. (2) Ne pas soumettre l'orice de sortie NO d'air de l'unité à un vent fort et direct. (3) Un mètre de distance doit être Sortie d'air conservé à partir du haut de l'unité. Sens du vent (4) Ne pas obturer les contours de l'unité avec des objets divers. (5) Si l'unité extérieure est installé dans un environnement soumis au vent, installez-la de façon à ce que la grille de sortie NE soit PAS dirigée dans le sens du vent. (Espace destiné à l'entretien) Sortie d'air 3. Installation de l’unité extérieure Fixez l'unité sur la fondation de façon adéquate, conformément aux condiUnité tions de l'emplacement de l'installation, et en se référant aux informations suivantes. Caoutchouc amortisseur • Laissez sufsamment d'espace libre au niveau de la fondation béton, Fondation béton pour y xer les boulons d'ancrage. • Coulez la fondation béton sufsamment en profondeur. • Installez l'unité de façon à ce que l'angle d'inclinaison soit inférieur à 3 degrés. Boulon d'ancrage • Il est interdit de placer l'unité directement au sol. Vériez qu'il y a sufsamment d'espace libre à proximité du trou de vidange de la plaque inférieure, de façon à pouvoir vidanger l'eau facilement. 4. Dimensions d'installation (Unité : mm) Borne de câblage de l'alimentation Orice de distribution du câblage d'alimentation 51 Modèle W D H L1 L2 L3 1U07BS1ERA 780 245 540 500 140 256 1U09BS1ERA 780 245 540 500 140 256 1U12BS1ERA 780 245 540 500 140 256 1U18FS1ERA 810 288 688 583 113.5 319.5 1U24GS1ERA 860 308 730 633 113.5 340 Procédure d'installation Branchement des tuyaux 1. Taille des tuyaux 1U07BS1ERA 1U09BS1ERA 1U12BS1ERA 1U18FS1ERA 1U24GS1ERA 2. Tuyau de liquide 6,35x0,8 mm Tuyau de gaz 9,52x0,8 mm Tuyau de liquide 6,35x0,8 mm Tuyau de gaz 12,7x0,8 mm Tuyau de liquide 9,52x0,8 mm Tuyau de gaz 15,88x1,0 mm • Installez les écrous d'évasement sur les tuyaux à brancher, puis évasez les tuyaux. Raccords de tuyauterie • Lorsque vous courbez un tuyau, donnez-lui autant de rondeur que possible an de ne pas l’écraser ; le rayon de courbure doit être d’au moins 30 à 40 mm, voire plus. • Connectez d'abord le côté gaz pour faciliter la suite des travaux. • Le tuyau de raccordement est réservé à R410A. Demi-raccord Clé Ecrou d'évasement Le serrage forcé sans prêter attention au centrage peut endommager les lets et entraîner des fuites de gaz. Diamètre du tuyau (Ø) Couple de serrage Côté liquide 6,35 mm (1/4 po) 18N.m Côté liquide/gaz 9,52 mm (3/8 po) 42 N.m Gaz 12,7mm (1/2") 55 N.m Gaz 15,88mm (5/8") 60 N.m Clé dynamométrique Faites attention que des particules telles que les déchets, le sable, l'eau , etc. ne rentrent pas dans le tuyau. AVERTISSEMENT La longueur standard d'un tuyau est de C m. Si elle dépasse les D m, la fonction de l'unité s'en trouvera affectée. S'il faut rallonger le tuyau, le réfrigérant doit être chargé selon E g/m. Toutefois, la charge de réfrigérant doit être exécuté par un professionnel de la climatisation. Avant d'ajouter du réfrigérant, purgez l'air des tuyaux de réfrigération et de l'unité intérieure avec pompe à vide. Chargez ensuite le réfrigérant supplémentaire. unité extérieure B Unité intérieure B A A Unité intérieure unité extérieure unité extérieure Piège dl'huile B A Unité intérieure • Hauteur max: Amax • Si la hauteur A dépasse les 5m, installez un piège à huile tous les 5 à 7m • Longueur max: Bmax • Si la longueur du tuyau B dépasse les D m, le réfrigérant doit être chargé à E g/m. 52 Unité extérieure Amax Bmax C D E 1U07BS1ERA 10 15 5 7 20 1U09BS1ERA 10 15 5 7 20 1U12BS1ERA 10 15 5 7 20 1U18BS1ERA 15 25 5 7 20 1U24BS1ERA 15 25 5 7 45 Procédure d'installation Test d'étanchéité à l'air Une fois la connexion du tuyau réfrigérant effectuée, procédez au test d'étanchéité à l'air. • Le test d'étanchéité à l'air utilise une bouteille d'azote pour la mise sous pression, selon le mode de connexion du tuyau, comme le montre l'illustration suivante. • Le clapet du gaz et du liquide sont tous les deux fermés. Pour éviter la pénétration de l'azote dans le système de circulation de l'unité extérieure, serrez le clapet avant la mise sous pression (le clapet du gaz et du liquide). Piézomètre basse pression Piézomètre haute pression Intérieur Soupape d'arrêt complètement fermée (côté gaz) Extérieur Complètement serré Pièce d'évasement Séparateur Clapet de refoulement Complètement serré Pièce d'évasement Regard Clapet comptegoutte Bouteille d'azote Unités intérieures Unités extérieures Soupape d'arrêt complètement fermée (côté liquide) 1) Appliquez une pression pendant au moins 3 minutes à 0,3MPa (3,0 kg/cm2g) Manomètre linéaire 2) Appliquez une pression pendant au moins 3 minutes à 1,5 MPa (15kg/cm2g) Une fuite importante sera observée. 3) Appliquez une pression pendant au moins 24 heures à 3,0 MPa (30kg/cm2g) Une petite fuite sera observée. Manomètre du cylindre Tuyau brasé Joint brasé par capillarité Bouteille d'azote Connecteur large coulissant Tuyau d'entretien • Vériez si la pression a baissé Si la pression n'a pas bougé, poursuivez. Si la pression a baissé, veuillez contrôler le point de fuite. Lors de la mise sous pression pendant 24 heures, une variation de 1°C de la température ambiante va provoquer une variation de 0,01 MPa (0,1kg/cm2 g) de la pression. Ceci est à corriger au cours du test. • Vérication du point de fuite Dans les étapes 1) à 3), en cas de chute de la pression, contrôlez la présence d'une fuite à chaque joint en écoutant, en touchant, en utilisant de l'eau savonneuse, etc. de façon à pouvoir identier le point de fuite. Une fois le point de fuite conrmé, ressoudez-le ou serrez une nouvelle fois l'écrou. 53 Procédure d'installation Mise sous vide Méthode de mise sous vide de la tuyauterie : utilisation de la pompe à vide (z. B. 1U18F S1ERA) 1. Enlevez le capuchon de l'orice d'entretien de la vanne à 3 voies, le capuchon Vanne à 2 voies du robinet de la vanne à 2 voies et à 3 voies. Connectez ensuite l'orice d'entreVanne à 2 voies tien dans la projection du tuyau de charge (bas) pour le collecteur à manomètre. Vanne à 3 voies Vanne à 3 voies Connectez ensuite la projection du tuyau de charge (centre) pour le collecteur à manomètre dans la pompe à vide. Soupape d'arrêt liquide Soupape d'arrêt gaz Collecteur de jauge (R410A) Pompe à vide (R410A) 2. Ouvrez la poignée du collecteur à manomètre au niveau bas. Mettez la pompe à vide en marche. Si l’indicateur se déplace (bas), précipitez l'état de vide et vériez l'étape 1 à nouveau. 3. Mettez sous vide pendant plus de 15 min. Vériez également le manomètre qui doit indiquer -0,1MPa (-76cm Hg) sur le côté basse pression. Une fois la mise sous vide effectuée, fermez la poignée 'Lo' de la pompe à vide. Inspectez l’indicateur et observez pendant 1 à 2 minutes. Si l’indicateur revient en dépit du serrage, reprenez l'opération d'évasement en revenant au début de l'étape 3. Ouvrir Fermer Vanne à 2 voies Vanne à 3 voies Orice d'entretien 90 pendant 6 secondes 4. En tournant dans le sens antihoraire, ouvrez le robinet de la vanne à 2 voies à un angle de 90 degrés. Environ 6 secondes plus tard, fermez la vanne à 2 voies et inspectez an de détecter toute fuite de gaz. 5. Pas de fuite de gaz? En cas de fuite de gaz, resserrez les pièces de connexion du tuyau. S'il n'y a plus de fuite, continuez avec l'étape 6. Si la fuite de gaz se maintient, déchargez tout le réfrigérant de l'orice d'entretien. Après avoir effectué l'évasement et le vide, remplissez de réfrigérant indiqué de la bouteille. Vanne à 2 voies 6. Détachez le tuyau de charge de l'orice d'entretien, ouvrez la vanne à 2 et 3 voies. Tournez le robinet de la vanne dans le sens antihoraire. 7. Pour empêcher toute fuite de gaz, tournez le capuchon de l'orice d'entretien, le capuchon du robinet des vannes à 2 et 3 voies un peu au-delà du point où le couple augmente brusquement. Vanne à 3 voies Vanne à 2 voies Vanne à 3 voies Capuchon du robinet de vanne Capuchon du robinet de vanne Capuchon de l'orice d’entretien AVERTISSEMENT : Si le réfrigérant du climatiseur fuit, il faut vidanger tout le réfrigérant. Mettez d'abord sous vide, puis chargez le réfrigérant liquide dans le climatiseur d'air jusqu'à la quantité indiquée sur la plaque signalétique. 54 Procédure d'installation Câblage électrique AVERTISSEMENT ! DANGER DE BLESSURE OU DE MORT • COUPEZ L'ALIMENTATION ÉLECTRIQUE AU NIVEAU DU DISJONCTEUR OU METTEZ L'ALIMENTATION HORS TENSION AVANT D'EFFECTUER UN BRANCHEMENT ÉLECTRIQUE. • LES BRANCHEMENTS DE MISE À LA TERRE DOIVENT ÊTRE TERMINÉS AVANT D'EFFECTUER LES BRANCHEMENTS SUR SECTEUR. Précautions concernant le câblage électrique • Les travaux de câblage électrique doivent être réalisés par du personnel autorisé. • Ne branchez pas plus de trois câbles au bornier. Utilisez systématiquement des cosses à poinçonner rondes avec des ls à extrémités isolées. • N'utilisez que des conducteurs en cuivre. Choix de la taille des câbles d'alimentation et d'interconnexion Choisissez les tailles des câbles et la protection du circuit dans le tableau ci-dessous. (Ce tableau présente des câbles de 20 mètres de long, avec moins de 2% de chute de tension.) Disjoncteur Élément Taille des câbles pour l'alimentation Calibre du système de (minimum) protection contre les (mm2) surintensités (A) Phase Disjoncteur à interrupteur (A) 1U07BS1ERA 1U09BS1ERA 1U12BS1ERA 1U18BS1ERA 1 40 26 1U24GS1ERA 1 40 26 Modèle Disjoncteur de fuite à la masse Disjoncteur à interrupteur (A) Courant de fuite (mA) 2.5 40 30 4.0 40 30 • Si le cordon d'alimentation est endommagé, il doit être remplacé par le fabricant, un de ses agents d'entretien ou une personne qualiée. • Si le fusible de la boite de commande a fondu, remplacez-le avec le type T 25A/250V. • La méthode de câblage doit être conforme aux normes locales de câblage. • Procurez-vous le câble d'alimentation et les câbles de connexion. • Tous les câbles doivent disposer d'une certication d'authentication européenne. Pendant l'installation, lorsque les câbles de connexion sont coupés, assurez-vous que le câble de mise à la terre soit le dernier à être coupé. • Le disjoncteur du climatiseur doit être omnipolaire et la distance entre ses deux contacts ne doit pas être inférieure à 3 mm. Ce type de déconnexion doit être incorporé au câblage xe. • La distance entre les deux borniers de l'unité intérieure et de l'unité extérieure ne doit pas dépasser les 5 mètres. Si cette distance est plus importante, le diamètre du câble doit être augmenté conformément à la norme locale de câblage. • Installez un disjoncteur de fuite. Procédure de câblage 1) Retirez les vis de pression sur le côté avant d'ôter le panneau avant dans le sens indiqué. 2) Branchez les câbles de façon adéquate sur le bornier et xez les câbles avec un attache-câble à proximité du bornier. 3) Dirigez les câbles de façon adéquate et faites-les passer dans l'ouverture prévue pour le câblage électrique sur le panneau latéral. AVERTISSEMENT : LES CÂBLES D'INTERCONNEXION DOIVENT ÊTRE CONNECTÉS COMME LE MONTRE L'ILLUSTRATION CI-DESSOUS. UN MAUVAIS CÂBLAGE PEUT ENDOMMAGER L'ÉQUIPEMENT. POUR 07K 09K 12K Vers l'unité intérieure 1(N) 2 (L) 1U07BS1ERA 1U09BS1ERA 1U12BS1ERA 1U18BS1ERA 1U24GS1ERA Câblage de connexion 4G0.75mm2 4G0.75mm2 4G0.75mm2 Câble d'alimentation 3G1.5mm2 3G2.5mm2 3G4.0mm2 Modèle 3 (C) { N ALIMENTATION L 1(N ) 2 (L) 3 (C ) | ALIMENTATION 1(N) 2 (L) 3 (C) Vers l'unité intérieure POUR 18K 24K Unité extérieure Unité extérieure 55 Dépannage d'une unité extérieure AVERTISSEMENT ! • CETTE UNITÉ VA DÉMARRER INSTANTANÉMENT, SANS QU'ELLE SOIT EN POSITION "ON" (marche), LORSQUE L'ALIMENTATION ÉLECTRIQUE EST FOURNIE. ASSUREZ-VOUS DE LA METTRE EN POSITION "OFF" (ARRÊT) AVANT DE DÉBRANCHER L'ALIMENTATION ÉLECTRIQUE POUR TOUT ENTRETIEN OU RÉPARATION. • Cette unité dispose d'une fonction de redémarrage automatique du système dés le retour de l'alimentation électrique après une coupure. 1. Avant d'effectuer un test de fonctionnement (pour tous les modèles de pompe thermique) Assurez-vous que le disjoncteur de la source d'alimentation (interrupteur principal) de l'unité a bien été fonctionnel pendant plus de 12 heures de façon à alimenter le réchauffeur du carter avant son fonctionnement. 2. Test de fonctionnement Faites fonctionner l'unité en continu pendant environ 30 minutes, et vériez les éléments suivants. • Pression d'aspiration au niveau du joint de contrôle du robinet de service du tuyau de gaz. • Pression de refoulement au niveau du joint de contrôle du tuyau de refoulement du compresseur. • Différence de température entre l'air de retour et l'air fourni pour l'unité intérieure. Intervalles d'allumage du voyant DEL sur le tableau principal 1 2 Description du problème Analyse et diagnostic 9 Défaillance Eeprom Défaillance IPM Erreur de communication entre le tableau principal et le module de l'injecteur Erreur de communication SPDU Protection contre la pression élevée Protection contre la surtension du module (uniquement pour l'injecteur) Protection contre la sous-tension du module (uniquement pour l'injecteur) Protection température de déchargement du compresseur Fonctionnement anormale du moteur CC 10 Fonctionnement anormal du capteur du tuyau 11 Défaillance de la sonde thermique d'aspiration 12 Fonctionnement anormal du capteur ambiant extérieur 4 5 6 8 13 15 Fonctionnement anormal du capteur de décharge du compresseur Erreur de communication entre l'unité intérieure et l'unité extérieure 16 Manque de réfrigérant ou contrôlez la présence de fuite au niveau de l'unité 17 Défaillance inverse de la vanne à 2 voies 18 18 25 25 25 Blocage du compresseur (uniquement pour l'injecteur) Erreur du circuit de sélection module MID Surintensité phase U du compresseur Surintensité phase V du compresseur Surintensité phase W du compresseur Défaillance Eeprom du tableau principal extérieur Défaillance IPM Échec de la communication pendant plus de 4 min Pression élevée du système supérieure à 4,15 MPa Envoyé par le module injecteur La température de déchargement du compresseur est supérieure à 110 centigrades Blocage du moteur CC ou défaillance du moteur Court-circuit ou fonctionnement en circuit ouvert du capteur du tuyau Lorsque le câblage du compression est incorrect ou que la connexion est faible Court-circuit ou fonctionnement en circuit ouvert du capteur ambiant extérieur Court-circuit ou fonctionnement en circuit ouvert du capteur de décharge du compresseur Échec de la communication pendant plus de 4 min Alarme et arrêt en cas de détection TD-tci>=75 pendant 1 min après le démarrage du compresseur en mode refroidissement 10 min, contrôlez la présence de fuite au niveau de l'unité. Alarme et arrêt en cas de détection Tm<=75 pendant 1 min après le démarrage du compresseur en mode chauffage 10 min, conrmez la défaillance si elle apparaît 3 fois en une heure. Le compresseur intérieur présente un blocage anormal Mauvais circuit de sélection module MID L'intensité de la phase U du compresseur est trop élevée L'intensité de la phase V du compresseur est trop élevée L'intensité de la phase W du compresseur est trop élevée Haier Group Adresse : No.1 Haier Road,Hi-tech Zone,Qingdao 266101 P.R.Chine Contacts : Tél. : +86-532-8893-6943 ; Télécopie +86-532-8893-1010 Site Internet : www.haier.com 56 14
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64

Haier 1U12BS1ERA El manual del propietario

Categoría
Acondicionadores de aire de sistema dividido
Tipo
El manual del propietario