Installation Specications
Overcurrent Protection
Input: No internal fuses. UL Listed circuit breakers or fuses rated 3 A to 15 A,
480 V are required to be installed for input protection.
Output: Outputs are capable of providing high currents for short periods of
time for inductive load startup.
Relay
N.O. contact rated 200 mA/50 Vdc
Connections
An accessible disconnect device shall be installed external to the equipment.
Use copper conductors only, 60/75°C.
Input: Screw terminals. Connector size range: 16–10 AWG (1.5–6 mm2) for
solid or stranded conductors. Screw torque: 4.4-6.5 lb-inch (50-73 N-cm).
Output: Two terminals per output. Connector size range: 16–10 AWG (1.5–6
mm2) for solid or stranded conductors. Screw torque: 4.4-6.5 lb-inch (50-73
N-cm). Use only one copper wire per terminal for input and output.
Non-ratcheting torque driver recommended.
Safety
The power supply should meet the following conditions for safe use when
installed in a Class I, Zone 2, Groups IIC Hazardous Location:
(1) The equipment shall only be used in an area of not more than pollution
degree 2, as dened in IEC 60664-1.
(2) The equipment shall be installed in an enclosure that provides a degree
of protection not less than IP54 in accordance with IEC 60079-15.
(3) The operating temperature class (T-code) of this device was determined
to be T4.
Warning — Explosion Hazard — Do not disconnect the equipment
while the circuit is live or unless the area is known to be free of ignitable
concentrations.
Warning — Explosion Hazard — Do not open the unit. Do not substitute
components.
Warning — Exposure to some chemicals may degrade the sealing
properties of materials used in the sealed relay device.
The power supplies should meet the following when installed in an ordinary
locations environment: Install in a controlled environment.
DIN Rail Mounting
Simple snap to DIN TS35/7.5 or TS35/15 rail system.
1. Tilt unit as illustrated.
2. Put unit onto the DIN rail.
3. Push unit downward until it stops.
4. Push at the lower front edge to lock.
5. Gently shake the unit to ensure that it is secure.
Especicaciones de Instalación
Protección de Sobreintensidad
Entrada: No contiene fusibles internos. Para protección de entrada se
requiere instalar interruptores de circuito o fusibles certicados por UL con
valoración de 3 A a 15 A a 480 V.
Salida: Las tomas de salida son capaces de entregar corrientes elevadas
durante lapsos breves para el arranque de cargas inductivas.
Relé
Sin contacto clasicado 200 mA/50 V CC
Conexiones
Un dispositivo accesible de desconexión debe ser instalado externamente
al equipo.
Usar conductores de cobre únicamente, para 60/75°C.
Entrada: terminales tipo tornillo Rango de tamaños de conectores:
1,5–6 mm
2
para conductores unilares o trenzados. Torque de tornillo:
50-73 N-cm
Salida: dos terminales por salida. Rango de tamaños de conectores:
1,5–6 mm
2
para conductores unilares o trenzados. Torque de tornillo:
50-73 N-cm
Se recomienda un conductor de torque sin ajuste.
Seguridad
Las siguientes condiciones son requeridas para uso seguro de la fuente de
poder cuando la instalación es en áreas clasicadas como Clase I, Zona 2,
Grupo IIC de Ubicación Peligrosa:
(1) El equipo debe ser usado sólo en un área de no más de un grado 2 de
contaminación, tal como se dene en la norma IEC 60664-1.
(2) El equipo debe instalarse en el interior de un recinto que proporciona
un grado de protección no inferior a IP54 de acuerdo con la norma IEC
60079-15.
(3) El código de temperatura (T-code) de operación de este equipo es de
clase T4.
Advertencia — Peligro de Explosión — No desconecte el equipo
si el circuito está conectado, exceptuando si se sabe que no existen
concentraciones inamables en el área.
Advertencia — Peligro de Explosión — No abra la unidad. No substituya
componentes.
Advertencia — La exposición a ciertas sustancias químicas podría
degradar las propiedades selladoras de los materiales utilizados en el relé
sellado del equipo.
Las fuentes de alimentación deben cumplir con lo siguiente cuando
se instalen en un entorno de áreas ordinarias: instalar en un entorno
controlado.
Montaje en Riel DIN
Se adapta de manera sencilla en sistema Riel DIN TS35/7.5
ó Sistema TS35/15.
1. Incline la unidad como se ilustra.
2. Póngala sobre el Riel DIN.
3. Empuje hacia abajo hasta que se detenga.
4. Empuje de la parte baja del frente para asegurar.
5. Mueva la unidad ligeramente para vericar está segura.
Technical Specications
Input
Nominal Voltage 380–480 Vac, 3Ph
Inrush Current <25 A
Power Factor (PFC) EN61000-3-2 Class A
Nominal Frequency 50/60 Hz
Output
Nominal Voltage 24 V (Adjustable from 24–28 Vdc)
Current 10 A
Power 240 W
Power Boost 1.5 x nominal current for 4 s
Hold-up Time
>20 ms (full load, 380 Vac input @ T
amb
+25°C) to 95% output voltage
Tolerance <2% overall
• Line Regulation <0.5%
• Load Regulation <0.5%
• Time and Temperature
Drift
<1%
Initial Voltage Setting 24.5 V ± 1%
Ripple <50 mVpp
Power Back Immunity < 35 V: no damage, auto-recovery
Parallel Operation Switch selectable
Overvoltage Protection >30.5 Vdc, but <33 Vdc auto recovery
Environmental Data
Ambient Temperature
Storage/Shipment: -40°C to +85°C.
Operating: -40°C to +60°C at full load. Derate
240 W by 12 W per °C to 120 W from +60°C
to +70°C.
Degree of Protection IP20 (EN60529)
Recommended Minimum
Installation Clearance
0.98 in. (25 mm) above and below; 0.98 in.
(25 mm) left and right. Do not obstruct air ow.
Weight 1.54 lb. (700 g)
Certications
UL 508/CSA C22.2 No. 107.1
UL 60950-1/CSA C22.2 60950-1
UL 60079-0, UL 60079-15
CAN/CSA 60079-0, CAN/CSA 60079-15
Class I, Zone 2 AEx nA nC IIC T4 Gc
Class I, Zone 2 Ex nA nC IIC T4 U
IEC60950-1, EN60950-1
II 3 G Ex ec nC IIC T4 Gc, DEMKO 11ATEX1105449X
EN60079-0, EN60079-7, EN60079-15
IECEx Ex ec nC IIC T4 Gc, IECEx UL15.0017X
IEC60079-0, IEC60079-7, IEC60079-15
№TC RU C-US.MШ06.B.00166
Ex nA nC IIC Gc U
Type Approved
Emissions/Immunity
EN61000-6-1, EN61000-6-2, EN61000-6-3, EN61000-6-4, EN61326-1,
EN55011 Class B, EN55022, EN55024, EN61000-3-2, EN61000-3-3, SEMI
F47 Sag Immunity
Datos Técnicos
Entrada
Voltaje Nominal 380–480 Vac, 3Ph
Arranque <25 A
Factor de Potencia (PFC) EN61000-3-2 Clase A
Frecuencia Nominal 50/60 Hz
Salida
Voltaje Nominal 24 V (Ajustable from 24–28 V CC)
Corriente 10 A
Potencia 240 W
Elevación de Potencia 1.5 x la corriente nominal por 4 s
Tiempo de Retención
>20 ms (la carga llena, 380 V CA entrada @
T
amb
+ 25°C) a 95% de voltaje de salida
Tolerancia <± 2% en conjunto
• Regulación de Línea <0.5%
• Regulación de Carga <0.5%
• Desviación de Tiempo
y Temp
<1%
Ajuste Inicial de Voltaje 24.5 V ± 1%
Rizo <50 mVpp
Inmunidad de Potencia
Inversa
< 35 V: no implica daño, autorecuperación
Operación Paralela Interruptor seleccionable
Protección de Sobre
Voltaje
>30.5 V CC, pero <33 V CC recuperación
automática
Datos Ambientales
Temperatura Ambiente
Almacenamiento/Embarque: -40°C to +85°C
Carga nominal completa: -40°C a +60°C en
carga llena. Disminución de 240 W a razón
de 12 W por °C hasta 120 W desde +60 °C
to +70 °C
Grado de Protección IP20 (EN60529)
Espacio Libre Mínimo
recomendado de Insta-
lación
25 mm por encima y por debajo; 25 mm izqui-
erda y derecha. No obstruya ujo aéreo.
Peso 1.54 lb. (700 g)
Certicaciones
UL 508/CSA C22.2 No. 107.1
UL 60950-1/CSA C22.2 60950-1
UL 60079-0, UL 60079-15
CAN/CSA 60079-0, CAN/CSA 60079-15
Class I, Zone 2 AEx nA nC IIC T4 Gc
Class I, Zone 2 Ex nA nC IIC T4 U
IEC60950-1, EN60950-1
II 3 G Ex ec nC IIC T4 Gc, DEMKO 11ATEX1105449X
EN60079-0, EN60079-7, EN60079-15
IECEx Ex ec nC IIC T4 Gc, IECEx UL15.0017X
IEC60079-0, IEC60079-7, IEC60079-15
№TC RU C-US.MШ06.B.00166
Ex nA nC IIC Gc U
Tipo Aprobado
Emisiones/Inmmunidad
EN61000-6-1, EN61000-6-2, EN61000-6-3, EN61000-6-4, EN61326-1,
EN55011 Clase B, EN55022, EN55024, EN61000-3-2, EN61000-3-3, SEMIF47
Inmunidad a Picos
Fuentes de Poder
SDN 10-24-480C
Manual de instrucciones
Dimensiones
5.51 in. [140.0 mm]
4.85 in. [123.3 mm]
4.73 in. [120.1 mm]
4.36 in. [110.8 mm]
4.78 in. [121.4 mm]
2.36 in. [60.0 mm]
Power Supply
Diagnósticos LED
LED OK
La Per-
dida de
CA
CA
Baja
No CC
Alta
Carga
Sobre-
carga
Cali-
ente
Muy
Cali-
ente
Entrada Verde --- Ámbar Verde Verde Verde Verde Verde
Salida Verde --- Verde --- Ámbar Ámbar Verde ---
Alarma --- --- --- Rojo Ámbar Rojo Ámbar Ámbar
Soporte técnico
(800) 377-4384 • (847) 268-6651
www.solahd.com
Aunque se ha tomado toda precaución para asegurar precisión e integridad en
esta información, Appleton Grp LLC d/b/a Appleton Group no asume ninguna
responsabilidad y deniega toda responsabilidad por daños que resulten por el
uso de esta información o por cualquier error u omisión. Las especicaciones
están sujetas a cambios sin previo aviso.
P/N: A272-230 Rev. 6 02/2018
© 2018 Appleton Grp LLC d/b/a
Appleton Group. All rights reserved.
Power Supplies
SDN 10-24-480C
Instruction Manual
Dimensions
5.51 in. [140.0 mm]
4.85 in. [123.3 mm]
4.36 in. [110.8 mm]
4.78 in. [121.4 mm]
2.36 in. [60.0 mm]
Power Supply
LED Diagnostics
LED OK
Loss
of AC
Low
AC
No
DC
High
Load
Over-
load
Hot
Too
Hot
Input Green --- Amber Green Green Green Green Green
Output Green --- Green --- Amber Amber Green ---
Alarm --- --- --- Red Amber Red Amber Amber
Technical Support
(800) 377-4384 • (847) 268-6651
www.solahd.com
While every precaution has been taken to ensure accuracy and completeness
in this manual, Appleton Grp LLC d/b/a Appleton Group assumes no
responsibility, and disclaims all liability for damages resulting from use of this
information or for any errors or omissions. Specications are subject to change
without notice.
P/N: A272-230 Rev. 6 02/2018
© 2018 Appleton Grp LLC d/b/a
Appleton Group. All rights reserved.