Emerson SolaHD SDN 15-12-100C-EPM El manual del propietario

Tipo
El manual del propietario

Este manual también es adecuado para

Installation Specications
Overcurrent Protection
Input: Internally fused.
Output: Outputs are capable of providing high currents for short periods of
time for inductive load startup switching.
Relay
N.O. contact rated 200 mA/50 Vdc.
Connections
An accessible disconnect device shall be installed external to the equipment.
Use copper conductors only, 60/75°C.
Input: Screw terminals. Connector size range: 16–10 AWG (1.5–6 mm
2
) for
solid or stranded conductors. Screw torque: 4.4-6.5 lb-inch (50-73 N-cm).
Output: Two terminals per output. Connector size range: 16–10 AWG (1.5–6
mm
2
) for solid or stranded conductors. Screw torque: 4.4-6.5 lb-inch (50-73
N-cm).
Use only one copper wire per terminal for input and output.
Non-ratcheting torque driver recommended.
Safety
The power supply should meet the following conditions for safe use when
installed in a Class I, Zone 2, Groups IIC Hazardous Location:
(1) The equipment shall only be used in an area of not more than pollution
degree 2, as dened in IEC 60664-1.
(2) The equipment shall be installed in an enclosure that provides a degree
of protection not less than IP54 in accordance with IEC 60079-0.
(3) The operating temperature class (T-code) of this device was determined
to be T4.
Warning — Explosion Hazard Do not disconnect the equipment while
the circuit is live or unless the area is known to be free of ignitable
concentrations.
Warning — Explosion Hazard Do not open the unit. Do not substitute
components. Do not replace fuse.
Warning — Exposure to some chemicals may degrade the sealing
properties of materials used in the sealed relay device.
The power supplies should meet the following when installed in an ordinary
locations environment: Install in a controlled environment.
DIN Rail Mounting
Simple snap to DIN TS35/7.5 or TS35/15 rail system.
1. Tilt unit as illustrated.
2. Put unit onto the DIN rail.
3. Push unit downward until it stops.
4. Push at the lower front edge to lock.
5. Gently shake the unit to ensure that it is secure.
Especicaciones de Instalación
Protección de Sobreintensidad
Entrada: Fusibles internos.
Salida: Las salidas son capaces de proporcionar altas corrientes por
períodos cortos de tiempo para arranque de carga inductiva o conmutación.
Relevo
N.O. contacto valoró 200 mA/50 V CC.
Conexiones
Un dispositivo accesible de desconexión será instalado externo al equipo.
Utilizar sólo conductor de cobre, 60/75ºC.
Entrada: terminales tipo tornillo Rango de tamaños de conectores:
1,5–6 mm
2
para conductores unilares o trenzados. Torque de tornillo:
50-73 N-cm
Salida: dos terminales por salida. Rango de tamaños de conectores:
1,5–6 mm
2
para conductores unilares o trenzados. Torque de tornillo:
50-73 N-cm
Utilizar solo un cable de cobre por terminal para la entrada y la salida.
Se recomienda un conductor de torque sin ajuste.
Seguridad
La Fuente de Poder debe tener las siguientes condiciones para uso
seguro cuando esté instalada en una Clase I, Zona 2, Grupo IIC Ubicación
Peligrosa:
(1) El equipo debe ser usada sólo en un área de no más de 2 grado de
contaminación, tal como se dene en la norma IEC 60664-1.
(2) El equipo debe instalarse en el interior de un recinto que proporciona
un grado de protección no inferior a IP54 de acuerdo con la norma IEC
60079-0.
(3) La clase de temperatura (T-code) de este dispositivo se determinó que
la T4.
Advertencia Peligro de Explosión No desconecte el equipo
si el circuito está conectado, exceptuando si se sabe que no existen
concentraciones inamables en el área.
Advertencia Peligro de Explosión No abra la unidad. No sustituya
componentes. No sustituya el fusible.
Advertencia — La exposición a ciertas sustancias químicas podría
degradar las propiedades selladoras de los materiales utilizados en el relé
sellado.
Las fuentes de alimentación deben cumplir con lo siguiente cuando
se instalen en un entorno de áreas ordinarias: instalar en un entorno
controlado.
Montaje en Riel DIN
Ajuste simple según DIN TS35 / 7.5 o TS35 / 15.
1. Incline la unidad como se ilustra.
2. Póngala sobre el Riel DIN.
3. Empuje hacia abajo hasta que se detenga.
4. Empuje de la parte baja del frente para asegurar.
5. Mueva la unidad ligeramente para vericar está segura.
Technical Specications
Input
Nominal Voltage 100–240 Vac, 100-340 Vdc
Inrush Current <30 A
Power Factor (PFC) >0.95
Nominal Frequency 50/60 Hz
Output
Nominal Voltage 12 Vdc (Adjustable from 12-15 Vdc)
Current 15 A @ 12 Vdc
Power 180 W
Power Boost 1.5 x nominal current for 4 s
Hold-up Time
>40 ms (full load, 100 Vac input @ T
amb
+25°C) to
95% output voltage
Tolerance <± 2% overall
• Line Regulation <0.5%
• Load Regulation <0.5%
• Time and Temperature
Drift
<1.0%
Initial Voltage Setting 12.5 Vdc ± 1%
Ripple <100 mV
pp
Power Back Immunity < 18 V: no damage, auto-recovery
Parallel Operation Switch selectable
Overvoltage Protection >18 Vdc, <20 Vdc auto-recovery
Environmental Data
Ambient Temperature
Storage/Shipment: -40°C to +85°C
Full Nominal Load: -40°C to +60°C
Derate 180 W by 4.5 W per °C to 135 W from
+60°C to +70°C
Corrosion Resistance
Model SDN 15-12-100CX-EPM - Conformal
coated to meet G3 Harsh Rating per ISA 71.04
Group A.
Degree of Protection IP20 (EN60529)
Minimum Required Free
Space for Cooling
0.98 in. (25 mm) above and below, 0.39 in.
(10 mm) left and right, 0.59 (15 mm) in front
Weight 1.76 lb. (800 g)
Certications
UL 508/CSA C22.2 No. 107.1
UL 60950-1/CSA C22.2 60950-1
UL 60079-0, UL 60079-15,
CAN/CSA 60079-0, CAN/CSA 60079-15
Class I, Zone 2 AEx nA nC IIC T4 Gc
Class I, Zone 2 Ex nA nC IIC T4 U
IEC60950-1, EN60950-1
II 3 G Ex ec nC IIC T4 Gc
DEMKO 12ATEX1154772X
EN60079-0, EN60079-7, EN60079-15
IECEx
Ex ec nC IIC T4 Gc, IECEx UL15.0022X
IEC60079-0, IEC60079-7, IEC60079-15
2Ex nA nC IIC T4 Gc X
Type Approval
Type Approval
Emissions/Immunity
EN 61326-1; EN 55032 Class B; EN 55011 Group 1 Class B; EN 61000-3-2; EN 61000-3-3;
EN 55024; EN 61000-6-1; EN 61000-6-2; EN 61000-6-3; EN 61000-6-4; SEMI F47 Sag
Immunity
Datos Técnicos
Entrada
Voltaje Nominal
100–240 V CA
, 100-340 V CC
Arranque <30 A
Factor de Potencia (PFC) >0.95
Frecuencia Nominal 50/60 Hz
Salida
Voltaje Nominal 12 V CC (12-15 V CC Ajustable)
Corriente 15 A @ 12 V CC
Potencia 180 W
Elevación de Potencia 1.5 x la corriente nominal por 4 s
Tiempo de Retención
>40 ms (carga completa, entrada 100 V CA a
temperatura
ambiente
mayor a 25°C) a 95% del
voltaje de salida
Tolerancia <± 2% en todo el rango
• Regulación de Línea <0.5%
• Regulación de Carga <0.5%
• Desviación de Tiempo
y Temp
<1%
Ajuste Inicial de Voltaje 12.5 V CC ± 1%
Rizo
<100 mV
pp
Inmunidad de Potencia
Inversa
< 18 V: no implica daño, autorecuperación
Operación Paralela Interruptor seleccionable
Protección de Sobre
Voltaje
>18 V CC, <20 V CC recuperación automática
Datos Ambientales
Temperatura Ambiente
Almacenamiento/Embarque: -40°C to +85°C
Carga nominal completa: -40°C to +60°C
Reduzca la capacidad normal de 180 W por 4.5 W
por el °C a 135 W a partir del +60°C a +70°C
Resistencia a la Corrosión
El modelo SDN 15-12-100CX-EPM está recubierto
con un revestimiento de conformación que satisface
un nivel G3 para condiciones ambientales difíciles
de acuerdo con la norma ISA 71.04 Grupo A.
Grado de Protección IP20 (EN60529)
Espacio Requerido para
Enfriamiento
0.98 in. (25 mm) por encima y por debajo, 0.39 in.
(10 mm) izquierda y derecha, 0.59 in. (15 mm) por
delante
Peso 1.76 lb. (800 g)
Certicaciones
UL 508/CSA C22.2 No. 107.1
UL 60950-1/CSA C22.2 60950-1
UL 60079-0, UL 60079-15
CAN/CSA 60079-0, CAN/CSA 60079-15
Class I, Zone 2 AEx nA nC IIC T4 Gc
Class I, Zone 2 Ex nA nC IIC T4 U
IEC60950-1, EN60950-1
II 3 G Ex ec nC IIC T4 Gc
DEMKO 12ATEX1154772X
EN60079-0, EN60079-7, EN60079-15
IECEx
Ex ec nC IIC T4 Gc, IECEx UL15.0022X
IEC60079-0, IEC60079-7, IEC60079-15
2Ex nA nC IIC T4 Gc X
Aprobación de Tipo
Aprobación de Tipo
Emisiones/Inmmunidad
EN 61326-1; EN 55032 Clase B; EN 55011 Grupo 1 Clase B EN 61000-3-2;
EN 61000-3-3; EN 55024; EN 61000-6-1; EN 61000-6-2; EN 61000-6-3; EN 61000-6-4;
SEMI F47 Inmmunidad a Picos
Fuentes de alimentación
SDN 15-12-100C-EPM
SDN 15-12-100CX-EPM
Manual de Instrucciones
Dimensiones
Power Supply
5.51 in. [140.0 mm]
4.85 in. [123.3 mm]
2.36 in. [60.0 mm]
4.61 in. [117.2 mm]
4.36 in. [110.8 mm]
4.81 in. [122.1 mm]
Power Supply
5.51 in. [140.0 mm]
4.85 in. [123.3 mm]
2.36 in. [60.0 mm]
4.61 in. [117.2 mm]
4.36 in. [110.8 mm]
4.81 in. [122.1 mm]
Power Supply
5.51 in. [140.0 mm]
4.85 in. [123.3 mm]
2.36 in. [60.0 mm]
4.61 in. [117.2 mm]
4.36 in. [110.8 mm]
4.81 in. [122.1 mm]
Power Supply
5.51 in. [140.0 mm]
4.85 in. [123.3 mm]
2.36 in. [60.0 mm]
4.61 in. [117.2 mm]
4.36 in. [110.8 mm]
4.81 in. [122.1 mm]
Power Supply
5.51 in. [140.0 mm]
4.85 in. [123.3 mm]
2.36 in. [60.0 mm]
4.61 in. [117.2 mm]
4.36 in. [110.8 mm]
4.81 in. [122.1 mm]
Diagnósticos LED
LED OK
La Per-
dida de
CA
CA
Baja
No CC
Alta
Carga
Sobre-
carga
Cali-
ente
Muy
Cali-
ente
Entrada Verde --- Ámbar Verde Verde Verde Verde Verde
Salida Verde --- Verde --- Ámbar Ámbar Verde ---
Alarma --- --- --- Rojo Ámbar Rojo Ámbar Ámbar
Soporte técnico
(800) 377-4384 • (847) 268-6651
www.solahd.com
Aunque se ha tomado toda precaución para asegurar precisión e integridad en esta in-
formación, Appleton Grp LLC d/b/a Appleton Group no asume ninguna responsabilidad y
deniega toda responsabilidad por daños que resulten por el uso de esta información o por
cualquier error u omisión. Las especicaciones están sujetas a cambios sin previo aviso.
P/N: A272-301 Rev. 1 02/2018
© 2018 Appleton Grp LLC d/b/a
Appleton Group. All rights reserved.
Power Supplies
SDN 15-12-100C-EPM
SDN 15-12-100CX-EPM
Instruction Manual
Dimensions
Power Supply
5.51 in. [140.0 mm]
4.85 in. [123.3 mm]
2.36 in. [60.0 mm]
4.61 in. [117.2 mm]
4.36 in. [110.8 mm]
4.81 in. [122.1 mm]
Power Supply
5.51 in. [140.0 mm]
4.85 in. [123.3 mm]
2.36 in. [60.0 mm]
4.61 in. [117.2 mm]
4.36 in. [110.8 mm]
4.81 in. [122.1 mm]
Power Supply
5.51 in. [140.0 mm]
4.85 in. [123.3 mm]
2.36 in. [60.0 mm]
4.61 in. [117.2 mm]
4.36 in. [110.8 mm]
4.81 in. [122.1 mm]
Power Supply
5.51 in. [140.0 mm]
4.85 in. [123.3 mm]
2.36 in. [60.0 mm]
4.61 in. [117.2 mm]
4.36 in. [110.8 mm]
4.81 in. [122.1 mm]
Power Supply
5.51 in. [140.0 mm]
4.85 in. [123.3 mm]
2.36 in. [60.0 mm]
4.61 in. [117.2 mm]
4.36 in. [110.8 mm]
4.81 in. [122.1 mm]
LED Diagnostics
LED OK
Loss
of ac
Low ac No dc
High
Load
Over-
load
Hot Too Hot
Input Green --- Amber Green Green Green Green Green
Output Green --- Green --- Amber Amber Green ---
Alarm --- --- --- Red Amber Red Amber Amber
Technical Support
(800) 377-4384 • (847) 268-6651
www.solahd.com
While every precaution has been taken to ensure accuracy and completeness
in this manual, Appleton Grp LLC d/b/a Appleton Group assumes no
responsibility, and disclaims all liability for damages resulting from use of this
information or for any errors or omissions. Specications are subject to change
without notice.
P/N: A272-301 Rev. 1 02/2018
© 2018 Appleton Grp LLC d/b/a
Appleton Group. All rights reserved.

Transcripción de documentos

Technical Specifications Input Nominal Voltage Inrush Current Power Factor (PFC) Nominal Frequency Output Nominal Voltage Current Power Power Boost Power Supplies SDN 15-12-100C-EPM SDN 15-12-100CX-EPM Instruction Manual 4.61 in. [117.2 mm] Dimensions 2.36 in. [60.0 mm] 4.61 in. [117.2 mm] 4.61 in. [117.2 mm] 4.61 in. in. [110.8 [117.2 mm] mm] 4.36 4.61 in. [117.2 mm] 4.36 in. [110.8 mm] 4.36 in. [110.8 mm] 4.36 in. [110.8 mm] 4.36 in. [110.8 mm] 5.51 in. [140.0 mm] 4.85 in. [123.3 mm] 5.51 5.51 5.51 in.in. 5.51 in. [140.0 [140.0 [140.0 in.mm] [140.0 mm] mm]mm] 2.36 in. [60.0 2.36 mm] in. [60.0 mm] 2.36 in. [60.0 mm] 2.36 in. [60.0 mm] 4.85 4.85 4.85 in.in. 4.85 in. [123.3 [123.3 [123.3 in.mm] [123.3 mm] mm]mm] Hold-up Time Power Supply Power Supply Power Supply Power Supply Power Supply Tolerance • Line Regulation • Load Regulation • Time and Temperature Drift Initial Voltage Setting Ripple Power Back Immunity Parallel Operation Overvoltage Protection Environmental Data Ambient Temperature Corrosion Resistance 4.81 in. [122.1 mm] LED Diagnostics Loss Low ac No dc of ac 4.81 in. [122.1 mm] 4.81 in. [122.1 mm] 4.81 in. [122.1 mm] 4.81 in. [122.1 mm] High Load Overload LED OK Input Green --- Amber Green Green Green Green Green Output Green --- Green --- Alarm --- --- Red --- Hot Amber Amber Green Amber Red Too Hot Degree of Protection Minimum Required Free Space for Cooling Weight Certifications --- Amber Amber Technical Support (800) 377-4384 • (847) 268-6651 [email protected] www.solahd.com IECEx P/N: A272-301 Rev. 1 02/2018 © 2018 Appleton Grp LLC d/b/a Appleton Group. All rights reserved. SDN 15-12-100C-EPM SDN 15-12-100CX-EPM Manual de Instrucciones 4.61 in. [117.2 mm] 4.61 in. [117.2 mm] 4.61 in. in. [110.8 [117.2 mm] mm] 4.36 4.61 in. [117.2 mm] 4.36 in. [110.8 mm] 4.36 in. [110.8 mm] 4.36 in. [110.8 mm] 4.36 in. [110.8 mm] 5.51 in. [140.0 mm] 4.85 in. [123.3 mm] 2.36 in. [60.0 2.36 mm] in. [60.0 mm] 2.36 in. [60.0 mm] 2.36 in. [60.0 mm] 5.51 5.51 5.51 in.in. 5.51 in. [140.0 [140.0 [140.0 in.mm] [140.0 mm] mm]mm] 12.5 Vdc ± 1% <100 mVpp < 18 V: no damage, auto-recovery Switch selectable >18 Vdc, <20 Vdc auto-recovery Storage/Shipment: -40°C to +85°C Full Nominal Load: -40°C to +60°C Derate 180 W by 4.5 W per °C to 135 W from +60°C to +70°C Model SDN 15-12-100CX-EPM - Conformal coated to meet G3 Harsh Rating per ISA 71.04 Group A. IP20 (EN60529) 0.98 in. (25 mm) above and below, 0.39 in. (10 mm) left and right, 0.59 (15 mm) in front 1.76 lb. (800 g) Type Approval Type Approval Emissions/Immunity Power Supply Power Supply Power Supply Power Supply Power Supply Tolerancia • Regulación de Línea • Regulación de Carga • Desviación de Tiempo y Temp Ajuste Inicial de Voltaje Rizo Inmunidad de Potencia Inversa Operación Paralela Protección de Sobre Voltaje Datos Ambientales Temperatura Ambiente 4.81 in. [122.1 mm] Diagnósticos LED 4.81 in. [122.1 mm] 4.81 in. [122.1 mm] 4.81 in. [122.1 mm] 4.81 in. [122.1 mm] La Perdida de CA CA Baja No CC Alta SobreCarga carga Caliente Muy Caliente Entrada Verde --- Ámbar Verde Verde Verde Verde Salida Verde --- Verde --- Ámbar Ámbar Verde --- Alarma --- --- --- Rojo Ámbar Ámbar Ámbar Verde Rojo Datos Técnicos 100–240 V CA, 100-340 V CC <30 A >0.95 50/60 Hz 12 V CC (12-15 V CC Ajustable) 15 A @ 12 V CC 180 W 1.5 x la corriente nominal por 4 s >40 ms (carga completa, entrada 100 V CA a temperatura ambiente mayor a 25°C) a 95% del voltaje de salida <± 2% en todo el rango <0.5% <0.5% <1% 12.5 V CC ± 1% <100 mVpp < 18 V: no implica daño, autorecuperación Interruptor seleccionable >18 V CC, <20 V CC recuperación automática Almacenamiento/Embarque: -40°C to +85°C Carga nominal completa: -40°C to +60°C Reduzca la capacidad normal de 180 W por 4.5 W por el °C a 135 W a partir del +60°C a +70°C El modelo SDN 15-12-100CX-EPM está recubierto un revestimiento de conformación que satisface Resistencia a la Corrosión con un nivel G3 para condiciones ambientales difíciles de acuerdo con la norma ISA 71.04 Grupo A. Grado de Protección Espacio Requerido para Enfriamiento Peso Certificaciones Simple snap to DIN TS35/7.5 or TS35/15 rail system. 1. 2. 3. 4. 5. Tilt unit as illustrated. Put unit onto the DIN rail. Push unit downward until it stops. Push at the lower front edge to lock. Gently shake the unit to ensure that it is secure. IP20 (EN60529) 0.98 in. (25 mm) por encima y por debajo, 0.39 in. (10 mm) izquierda y derecha, 0.59 in. (15 mm) por delante 1.76 lb. (800 g) Especificaciones de Instalación Protección de Sobreintensidad Entrada: Fusibles internos. Salida: Las salidas son capaces de proporcionar altas corrientes por períodos cortos de tiempo para arranque de carga inductiva o conmutación. Relevo N.O. contacto valoró 200 mA/50 V CC. Conexiones Un dispositivo accesible de desconexión será instalado externo al equipo. Utilizar sólo conductor de cobre, 60/75ºC. Entrada: terminales tipo tornillo Rango de tamaños de conectores: 1,5–6 mm2 para conductores unifilares o trenzados. Torque de tornillo: 50-73 N-cm Salida: dos terminales por salida. Rango de tamaños de conectores: 1,5–6 mm2 para conductores unifilares o trenzados. Torque de tornillo: 50-73 N-cm Utilizar solo un cable de cobre por terminal para la entrada y la salida. Se recomienda un conductor de torque sin ajuste. Seguridad La Fuente de Poder debe tener las siguientes condiciones para uso seguro cuando esté instalada en una Clase I, Zona 2, Grupo IIC Ubicación Peligrosa: (1) El equipo debe ser usada sólo en un área de no más de 2 grado de contaminación, tal como se define en la norma IEC 60664-1. (2) El equipo debe instalarse en el interior de un recinto que proporciona un grado de protección no inferior a IP54 de acuerdo con la norma IEC 60079-0. (3) La clase de temperatura (T-code) de este dispositivo se determinó que la T4. Advertencia — Peligro de Explosión — No desconecte el equipo si el circuito está conectado, exceptuando si se sabe que no existen concentraciones inflamables en el área. Advertencia — Peligro de Explosión — No abra la unidad. No sustituya componentes. No sustituya el fusible. Advertencia — La exposición a ciertas sustancias químicas podría degradar las propiedades selladoras de los materiales utilizados en el relé sellado. Las fuentes de alimentación deben cumplir con lo siguiente cuando se instalen en un entorno de áreas ordinarias: instalar en un entorno controlado. Montaje en Riel DIN Ajuste simple según DIN TS35 / 7.5 o TS35 / 15. UL 60950-1/CSA C22.2 60950-1 UL 60079-0, UL 60079-15 CAN/CSA 60079-0, CAN/CSA 60079-15 Class I, Zone 2 AEx nA nC IIC T4 Gc Class I, Zone 2 Ex nA nC IIC T4 U (800) 377-4384 • (847) 268-6651 [email protected] www.solahd.com IEC60950-1, EN60950-1 II 3 G Ex ec nC IIC T4 Gc DEMKO 12ATEX1154772X EN60079-0, EN60079-7, EN60079-15 IECEx Ex ec nC IIC T4 Gc, IECEx UL15.0022X IEC60079-0, IEC60079-7, IEC60079-15 2Ex nA nC IIC T4 Gc X Aprobación de Tipo Aprobación de Tipo P/N: A272-301 Rev. 1 02/2018 © 2018 Appleton Grp LLC d/b/a Appleton Group. All rights reserved. DIN Rail Mounting UL 508/CSA C22.2 No. 107.1 Soporte técnico Aunque se ha tomado toda precaución para asegurar precisión e integridad en esta información, Appleton Grp LLC d/b/a Appleton Group no asume ninguna responsabilidad y deniega toda responsabilidad por daños que resulten por el uso de esta información o por cualquier error u omisión. Las especificaciones están sujetas a cambios sin previo aviso. The power supply should meet the following conditions for safe use when installed in a Class I, Zone 2, Groups IIC Hazardous Location: (1) The equipment shall only be used in an area of not more than pollution degree 2, as defined in IEC 60664-1. (2) The equipment shall be installed in an enclosure that provides a degree of protection not less than IP54 in accordance with IEC 60079-0. (3) The operating temperature class (T-code) of this device was determined to be T4. Warning — Explosion Hazard — Do not disconnect the equipment while the circuit is live or unless the area is known to be free of ignitable concentrations. Warning — Explosion Hazard — Do not open the unit. Do not substitute components. Do not replace fuse. Warning — Exposure to some chemicals may degrade the sealing properties of materials used in the sealed relay device. The power supplies should meet the following when installed in an ordinary locations environment: Install in a controlled environment. EN 61326-1; EN 55032 Class B; EN 55011 Group 1 Class B; EN 61000-3-2; EN 61000-3-3; EN 55024; EN 61000-6-1; EN 61000-6-2; EN 61000-6-3; EN 61000-6-4; SEMI F47 Sag Immunity Tiempo de Retención 4.61 in. [117.2 mm] Dimensiones 2.36 in. [60.0 mm] 4.85 4.85 4.85 in.in. 4.85 in. [123.3 [123.3 [123.3 in.mm] [123.3 mm] mm]mm] <1.0% UL 508/CSA C22.2 No. 107.1 UL 60950-1/CSA C22.2 60950-1 UL 60079-0, UL 60079-15, CAN/CSA 60079-0, CAN/CSA 60079-15 Class I, Zone 2 AEx nA nC IIC T4 Gc Class I, Zone 2 Ex nA nC IIC T4 U IEC60950-1, EN60950-1 II 3 G Ex ec nC IIC T4 Gc DEMKO 12ATEX1154772X EN60079-0, EN60079-7, EN60079-15 Ex ec nC IIC T4 Gc, IECEx UL15.0022X IEC60079-0, IEC60079-7, IEC60079-15 Entrada Voltaje Nominal Arranque Factor de Potencia (PFC) Frecuencia Nominal Salida Voltaje Nominal Corriente Potencia Elevación de Potencia Fuentes de alimentación OK 12 Vdc (Adjustable from 12-15 Vdc) 15 A @ 12 Vdc 180 W 1.5 x nominal current for 4 s >40 ms (full load, 100 Vac input @ Tamb +25°C) to 95% output voltage <± 2% overall <0.5% <0.5% 2Ex nA nC IIC T4 Gc X While every precaution has been taken to ensure accuracy and completeness in this manual, Appleton Grp LLC d/b/a Appleton Group assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions. Specifications are subject to change without notice. LED 100–240 Vac, 100-340 Vdc <30 A >0.95 50/60 Hz Installation Specifications Overcurrent Protection Input: Internally fused. Output: Outputs are capable of providing high currents for short periods of time for inductive load startup switching. Relay N.O. contact rated 200 mA/50 Vdc. Connections An accessible disconnect device shall be installed external to the equipment. Use copper conductors only, 60/75°C. Input: Screw terminals. Connector size range: 16–10 AWG (1.5–6 mm2) for solid or stranded conductors. Screw torque: 4.4-6.5 lb-inch (50-73 N-cm). Output: Two terminals per output. Connector size range: 16–10 AWG (1.5–6 mm2) for solid or stranded conductors. Screw torque: 4.4-6.5 lb-inch (50-73 N-cm). Use only one copper wire per terminal for input and output. Non-ratcheting torque driver recommended. Safety Emisiones/Inmmunidad EN 61326-1; EN 55032 Clase B; EN 55011 Grupo 1 Clase B EN 61000-3-2; EN 61000-3-3; EN 55024; EN 61000-6-1; EN 61000-6-2; EN 61000-6-3; EN 61000-6-4; SEMI F47 Inmmunidad a Picos 1. 2. 3. 4. 5. Incline la unidad como se ilustra. Póngala sobre el Riel DIN. Empuje hacia abajo hasta que se detenga. Empuje de la parte baja del frente para asegurar. Mueva la unidad ligeramente para verificar está segura.
  • Page 1 1
  • Page 2 2

Emerson SolaHD SDN 15-12-100C-EPM El manual del propietario

Tipo
El manual del propietario
Este manual también es adecuado para