Installation Specications
Overcurrent Protection
Input: Internally fused.
Output: Outputs are capable of providing high currents for short periods of time for
inductive load startup switching
Relay
N.O. contact rated 200 mA/50 Vdc.
Connections
An accessible disconnect device shall be installed external to the equipment.
Use copper conductors only, 90°C.
Input: Screw terminals. Connector size range: 16–10 AWG (1.5–6 mm
2
) for solid
or stranded conductors. Screw torque: 4.4-6.5 lb-inch (50-73 N-cm).
Output: Two terminals per output. Connector size range: 16–10 AWG (1.5–6
mm
2
) for solid or stranded conductors. Screw torque: 4.4-6.5 lb-inch (50-73 N-cm).
Use only one copper wire per terminal for input and output.
Non-ratcheting torque driver recommended.
Note: During power supply replacement, ensure wiring connections are properly
terminated by verifying that terminal ID locations are the same. The location and
arrangement of the terminals can vary between manufacturer and model number.
Safety
The power supplies should meet the following conditions for safe use when
installed in a Class I, Zone 2, Groups IIC Hazardous Location:
(1) The equipment shall only be used in an area of not more than pollution
degree 2, as dened in IEC 60664-1.
(2) The equipment shall be installed in an enclosure that provides a degree of
protection not less than IP54 in accordance with IEC 60079-0.
(3) The operating temperature class (T-code) of this device was determined to
be T4.
Warning — Explosion Hazard Do not disconnect the equipment while the
circuit is live or unless the area is known to be free of ignitable
concentrations.
Warning — Explosion Hazard Do not open the unit. Do not substitute
components. Do not replace fuse.
Warning — Exposure to some chemicals may degrade the sealing
properties of materials used in the sealed relay device.
The power supplies should meet the following when installed in an ordinary
locations environment: Install in a controlled environment.
DIN Rail Mounting
Simple snap to DIN TS35/7.5 or TS35/15 rail system.
1. Tilt unit as illustrated.
2. Put unit onto the DIN rail.
3. Push unit downward until it stops.
4. Push at the lower front edge to lock.
5. Gently shake the unit to ensure that it is secure.
Especicaciones de Instalación
Protección de Sobreintensidad
Entrada: Fusibles internos.
Salida: Las salidas son capaces de proporcionar altas corrientes por períodos
cortos de tiempo para arranque de carga inductiva o conmutación.
Relevo
N.O. contacto valoró 200 mA/50 V CC.
Conexiones
Un dispositivo accesible de desconexión será instalado externo al equipo.
Utilizar sólo conductor de cobre, 90ºC
Entrada: terminales tipo tornillo Rango de tamaños de conectores: 1,5–6 mm
2
para conductores unilares o trenzados. Torque de tornillo: 50-73 N-cm
Salida: dos terminales por salida. Rango de tamaños de conectores: 1,5–6 mm
2
para conductores unilares o trenzados. Torque de tornillo: 50-73 N-cm
Se recomienda un conductor de torque sin ajuste.
Nota: Durante la sustitución del suministro de energía, asegúrese de que las
conexiones de cableado estén correctamente nalizadas, vericando que las
ubicaciones de los ID de los terminales sean las mismas. La ubicación y la
disposición de los terminales pueden variar según el fabricante y el número de
modelo.
Seguridad
Las fuentes de alimentación deben cumplir las siguientes condiciones para un
uso seguro cuando se instala en un área peligrosa de clase I, zona 2, grupos
IIC:
(1) El equipo solo se debe usar en un área de un grado de polución no mayor
que 2, como se dene en IEC 60664-1.
(2) El equipo se debe instalar en un gabinete que proporcione un grado de
protección no menor que IP54 de acuerdo con IEC 60079-0.
(3) La clase de temperatura de operación (código T) de este dispositivo es T4.
Advertencia Peligro de Explosión No desconecte el equipo si el circuito
está conectado, exceptuando si se sabe que no existen concentraciones
inamables en el área.
Advertencia Peligro de Explosión No abra la unidad. No sustituya
componentes. No sustituya el fusible.
Advertencia — La exposición a ciertas sustancias químicas podría degradar las
propiedades selladoras de los materiales utilizados en el relé sellado.
Las fuentes de alimentación deben cumplir con lo siguiente cuando se instalen
en un entorno de áreas ordinarias: instalar en un entorno controlado.
Montaje en Riel DIN
Se adapta de manera sencilla en sistema Riel DIN TS35/7.5 ó Sistema TS35/15.
1. Incline la unidad como se ilustra.
2. Póngala sobre el Riel DIN.
3. Empuje hacia abajo hasta que se detenga.
4. Empuje de la parte baja del frente para asegurar.
5. Mueva la unidad ligeramente para vericar está segura.
Technical Specications
Input
Nominal Voltage 100–240 Vac, 100-250 Vdc
Inrush Current 10 A typical, 33 A max
Power Factor (PFC) >0.92
Nominal Frequency 50/60 Hz
Output
Nominal Voltage 24 V (24–28 Vdc Adjustable)
Current 20 A
Power 480 W
Power Boost 1.5 x nominal current for 4 s
Hold-up Time
>20 ms (full load, 100 Vac input @ T
amb
+25°C) to
95% output voltage
Tolerance <± 2% overall
• Line Regulation <0.5%
• Load Regulation <0.5%
• Time and Temperature
Drift
<1%
Initial Voltage Setting 24.5 V ± 1%
Ripple <100 mVpp
Power Back Immunity < 35 V: no damage, auto-recovery
Parallel Operation Switch selectable
Overvoltage Protection >30.5 Vdc, but <33 Vdc auto recovery
Environmental Data
Ambient Temperature
Storage/Shipment: -40°C to +85°C
Full Nominal Load: -40°C to +60°C
Derate 480 W by 24 W per °C to 240 W from
+60°C to +70°C
Corrosion Resistance
Model SDN 20-24-100CX - Conformal coated to
meet G3 Harsh Rating per ISA 71.04
Group A.
Degree of Protection IP20 (EN60529)
Minimum Required Free
Space for Cooling
1.6 in. (40 mm) above and below, 0.39 in. (10 mm)
left and right, 0.59 in. (15 mm) in front
Weight 3.02 lb. (1370 g)
Certications
UL 508/CSA C22.2 No. 107.1
UL 60950-1/CSA C22.2 60950-1
UL 60079-0, UL 60079-15,
CAN/CSA 60079-0, CAN/CSA 60079-15
Class I, Zone 2 AEx nA nC IIC T4 Gc
Class I, Zone 2 Ex nA nC IIC T4 U
IEC60950-1, EN60950-1
II 3 G Ex ec nC IIC T4 Gc DEMKO 14ATEX1350833X
EN60079-0, EN60079-7, EN60079-15
IECEx Ex ec nC IIC T4 Gc, IECEx UL15.0013X
IEC60079, IEC60079, IEC60079-15
2Ex nA nC IIC T4 Gc X, №TC RU C-US.AA87.B.00539
MSIP-REM-N4C-SDN20
Type Approval
Type Approval
Emissions/Immunity
EN 61326-1; EN 55032 Class B; EN 55011 Group 1 Class B EN 61000-3-2,
EN 61000-3-3; EN 55024; EN 61000-6-1; EN 61000-6-2; EN 61000-6-3;
EN 61000-6-4; SEMI F47 Sag Immunity. KC KN32, KN35
Datos Técnicos
Entrada
Voltaje Nominal 100–240 V CA, 100-250 V CC
Arranque Normal 10 A, máximo 33 A
Factor de Potencia (PFC) >0.92
Frecuencia Nominal 50/60 Hz
Salida
Voltaje Nominal 24 V (24–28 V CC Ajustable)
Corriente 20 A
Potencia 480 W
Elevación de Potencia 1.5 x la corriente nominal por 4 s
Tiempo de Retención
>20 ms (carga completa, entrada 100 V CA a
temperatura
ambiente
mayor a 25°C) al 95% del
voltaje de salida
Tolerancia <± 2% en todo el rango
• Regulación de Línea <0.5%
• Regulación de Carga <0.5%
• Desviación de Tiempo
y Temp
<1%
Ajuste Inicial de Voltaje 24.5 V ± 1%
Rizo <100 mVpp
Inmunidad de Potencia
Inversa
< 35 V: no implica daño, autorecuperación
Operación Paralela Interruptor seleccionable
Protección de Sobre
Voltaje
>30.5 V CC, pero <33 V CC recuperación
automática
Datos Ambientales
Temperatura Ambiente
Almacenamiento/Embarque: -40°C to +85°C
Carga nominal completa: -40°C to +60°C
Reduzca la capacidad normal de 480 W por 24 W
por el °C a 240 W a partir del +60°C a +70°C
Resistencia a la Corrosión
El modelo SDN 20-24-100CX está recubierto con
un revestimiento de conformación que satisface un
nivel G3 para condiciones ambientales difíciles de
acuerdo con la norma ISA 71.04 Grupo A.
Grado de Protección IP20 (EN60529)
Espacio Requerido para
Enfriamiento
1.6 in. (40 mm) por encima y por debajo, 0.39 in.
(10 mm) izquierda y derecha, 0.59 in. (15 mm)
por delante
Peso 3.02 lb. (1370 g)
Certicaciones
UL 508/CSA C22.2 No. 107.1
UL 60950-1/CSA C22.2 60950-1
UL 60079-0, UL 60079-15
CAN/CSA 60079-0, CAN/CSA 60079-15
Class I, Zone 2 AEx nA nC IIC T4 Gc
Class I, Zone 2 Ex nA nC IIC T4 U
IEC60950-1, EN60950-1
II 3 G Ex ec nC IIC T4 Gc DEMKO 14ATEX1350833X
EN60079-0, EN60079-7, EN60079-15
IECEx Ex ec nC IIC T4 Gc, IECEx UL15.0013X
IEC60079, IEC60079, IEC60079-15
2Ex nA nC IIC T4 Gc X, №TC RU C-US.AA87.B.00539
MSIP-REM-N4C-SDN20
Aprobación de Tipo
Aprobación de Tipo
Emisiones/Inmmunidad
EN 61326-1; EN 55032 Clase B; EN 55011 Grupo 1 Clase B EN 61000-3-2,
EN 61000-3-3; EN 55024; EN 61000-6-1; EN 61000-6-2; EN 61000-6-3;
EN 61000-6-4; SEMI F47 Inmmunidad a Picos
Fuentes de Alimentación
SDN 20-24-100C
SDN 20-24-100CX
Manual de Instrucciones
Dimensiones
3.42 in
[86.8 mm]
5.51 in [140.0 mm]
4.85 in [123.3 mm]
4.98 in [126.6 mm]
5.35 in [135.9 mm]
Power Supply
Diagnósticos LED
LED OK
La Per-
dida de
AC
AC
Baja
No DC
Alta
Carga
Sobre-
carga
Cali-
ente
Muy
Cali-
ente
En-
trada
Verde --- Ámbar Verde Verde Verde Verde Verde
Salida Verde --- Verde --- Ámbar Ámbar Verde ---
Alarma --- --- --- Rojo Ámbar Rojo Ámbar Ámbar
Soporte técnico
(800) 377-4384 • (847) 268-6651
www.solahd.com
Aunque se ha tomado toda precaución para asegurar precisión e integridad en
esta información, Appleton Grp LLC d/b/a Appleton Group no asume ninguna
responsabilidad y deniega toda responsabilidad por daños que resulten por el uso
de esta información o por cualquier error u omisión. Las especicaciones están
sujetas a cambios sin previo aviso.
P/N: A272-166 Rev. 10 2/2018
© 2018 Appleton Grp LLC d/b/a
Appleton Group. All rights reserved.
Power Supplies
SDN 20-24-100C
SDN 20-24-100CX
Instruction Manual
Dimensions
3.42 in
[86.8 mm]
5.51 in [140.0 mm]
4.85 in [123.3 mm]
4.98 in [126.6 mm]
5.35 in [135.9 mm]
Power Supply
LED Diagnostics
LED OK
Loss
of AC
Low
AC
No DC
High
Load
Over-
load
Hot
Too
Hot
Input Green --- Amber Green Green Green Green Green
Output Green --- Green --- Amber Amber Green ---
Alarm --- --- --- Red Amber Red Amber Amber
Technical Support
(800) 377-4384 • (847) 268-6651
www.solahd.com
Korean Manual is available on-line.
While every precaution has been taken to ensure accuracy and completeness in
this manual, Appleton Grp LLC d/b/a Appleton Group assumes no responsibility,
and disclaims all liability for damages resulting from use of this information or for
any errors or omissions. Specications are subject to change without notice.
P/N: A272-166 Rev. 10 2/2018
© 2018 Appleton Grp LLC d/b/a
Appleton Group. All rights reserved.

Transcripción de documentos

Input Nominal Voltage Inrush Current Power Factor (PFC) Nominal Frequency Output Nominal Voltage Current Power Power Boost Power Supplies SDN 20-24-100C SDN 20-24-100CX Instruction Manual Hold-up Time Tolerance • Line Regulation • Load Regulation • Time and Temperature Drift Initial Voltage Setting Ripple Power Back Immunity Parallel Operation Overvoltage Protection Environmental Data Dimensions 5.35 in [135.9 mm] 4.85 in [123.3 mm] 5.51 in [140.0 mm] 4.98 in [126.6 mm] Power Supply LED Input Output Alarm OK Green Green --- Loss of AC ------- <1% 24.5 V ± 1% <100 mVpp < 35 V: no damage, auto-recovery Switch selectable >30.5 Vdc, but <33 Vdc auto recovery Use copper conductors only, 90°C. Input: Screw terminals. Connector size range: 16–10 AWG (1.5–6 mm2) for solid or stranded conductors. Screw torque: 4.4-6.5 lb-inch (50-73 N-cm). Output: Two terminals per output. Connector size range: 16–10 AWG (1.5–6 mm2) for solid or stranded conductors. Screw torque: 4.4-6.5 lb-inch (50-73 N-cm). Use only one copper wire per terminal for input and output. Non-ratcheting torque driver recommended. Note: During power supply replacement, ensure wiring connections are properly terminated by verifying that terminal ID locations are the same. The location and arrangement of the terminals can vary between manufacturer and model number. Safety The power supplies should meet the following conditions for safe use when installed in a Class I, Zone 2, Groups IIC Hazardous Location: (1) The equipment shall only be used in an area of not more than pollution degree 2, as defined in IEC 60664-1. (2) The equipment shall be installed in an enclosure that provides a degree of protection not less than IP54 in accordance with IEC 60079-0. (3) The operating temperature class (T-code) of this device was determined to be T4. Minimum Required Free Space for Cooling 1.6 in. (40 mm) above and below, 0.39 in. (10 mm) left and right, 0.59 in. (15 mm) in front The power supplies should meet the following when installed in an ordinary locations environment: Install in a controlled environment. Weight 3.02 lb. (1370 g) DIN Rail Mounting Certifications Warning — Explosion Hazard — Do not disconnect the equipment while the circuit is live or unless the area is known to be free of ignitable concentrations. Warning — Explosion Hazard — Do not open the unit. Do not substitute components. Do not replace fuse. Warning — Exposure to some chemicals may degrade the sealing properties of materials used in the sealed relay device. Simple snap to DIN TS35/7.5 or TS35/15 rail system. UL 508/CSA C22.2 No. 107.1 UL 60950-1/CSA C22.2 60950-1 UL 60079-0, UL 60079-15, CAN/CSA 60079-0, CAN/CSA 60079-15 Class I, Zone 2 AEx nA nC IIC T4 Gc Class I, Zone 2 Ex nA nC IIC T4 U IEC60950-1, EN60950-1 Technical Support II 3 G Ex ec nC IIC T4 Gc DEMKO 14ATEX1350833X EN60079-0, EN60079-7, EN60079-15 (800) 377-4384 • (847) 268-6651 [email protected] www.solahd.com Korean Manual is available on-line. IECEx MSIP-REM-N4C-SDN20 Type Approval 1. 2. 3. 4. 5. Tilt unit as illustrated. Put unit onto the DIN rail. Push unit downward until it stops. Push at the lower front edge to lock. Gently shake the unit to ensure that it is secure. Type Approval Emissions/Immunity EN 61326-1; EN 55032 Class B; EN 55011 Group 1 Class B EN 61000-3-2, EN 61000-3-3; EN 55024; EN 61000-6-1; EN 61000-6-2; EN 61000-6-3; EN 61000-6-4; SEMI F47 Sag Immunity. KC KN32, KN35 P/N: A272-166 Rev. 10 2/2018 © 2018 Appleton Grp LLC d/b/a Appleton Group. All rights reserved. Entrada Voltaje Nominal Arranque Factor de Potencia (PFC) Frecuencia Nominal Salida Voltaje Nominal Corriente Potencia Elevación de Potencia Fuentes de Alimentación SDN 20-24-100C SDN 20-24-100CX Manual de Instrucciones Tiempo de Retención Tolerancia • Regulación de Línea • Regulación de Carga • Desviación de Tiempo y Temp Ajuste Inicial de Voltaje Rizo Inmunidad de Potencia Inversa Operación Paralela Protección de Sobre Voltaje Datos Ambientales Dimensiones 5.35 in [135.9 mm] 4.98 in [126.6 mm] 4.85 in [123.3 mm] Ex ec nC IIC T4 Gc, IECEx UL15.0013X IEC60079, IEC60079, IEC60079-15 2Ex nA nC IIC T4 Gc X, №TC RU C-US.AA87.B.00539 While every precaution has been taken to ensure accuracy and completeness in this manual, Appleton Grp LLC d/b/a Appleton Group assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions. Specifications are subject to change without notice. 5.51 in [140.0 mm] 24 V (24–28 Vdc Adjustable) 20 A 480 W 1.5 x nominal current for 4 s >20 ms (full load, 100 Vac input @ Tamb +25°C) to 95% output voltage <± 2% overall <0.5% <0.5% Degree of Protection Corrosion Resistance LED Diagnostics Low No DC High OverToo Hot AC Load load Hot Amber Green Green Green Green Green Green --Amber Amber Green ----Red Amber Red Amber Amber 100–240 Vac, 100-250 Vdc 10 A typical, 33 A max >0.92 50/60 Hz Installation Specifications Overcurrent Protection Input: Internally fused. Output: Outputs are capable of providing high currents for short periods of time for inductive load startup switching Relay N.O. contact rated 200 mA/50 Vdc. Connections An accessible disconnect device shall be installed external to the equipment. Storage/Shipment: -40°C to +85°C Full Nominal Load: -40°C to +60°C Derate 480 W by 24 W per °C to 240 W from +60°C to +70°C Model SDN 20-24-100CX - Conformal coated to meet G3 Harsh Rating per ISA 71.04 Group A. IP20 (EN60529) Ambient Temperature 3.42 in [86.8 mm] Technical Specifications Power Supply Datos Técnicos 100–240 V CA, 100-250 V CC Normal 10 A, máximo 33 A >0.92 50/60 Hz 24 V (24–28 V CC Ajustable) 20 A 480 W 1.5 x la corriente nominal por 4 s >20 ms (carga completa, entrada 100 V CA a temperatura ambiente mayor a 25°C) al 95% del voltaje de salida <± 2% en todo el rango <0.5% <0.5% <1% 24.5 V ± 1% <100 mVpp < 35 V: no implica daño, autorecuperación Interruptor seleccionable >30.5 V CC, pero <33 V CC recuperación automática Almacenamiento/Embarque: -40°C to +85°C Carga nominal completa: -40°C to +60°C Reduzca la capacidad normal de 480 W por 24 W por el °C a 240 W a partir del +60°C a +70°C El modelo SDN 20-24-100CX está recubierto con revestimiento de conformación que satisface un Resistencia a la Corrosión un nivel G3 para condiciones ambientales difíciles de acuerdo con la norma ISA 71.04 Grupo A. Grado de Protección IP20 (EN60529) 1.6 in. (40 mm) por encima y por debajo, 0.39 in. Espacio Requerido para (10 mm) izquierda y derecha, 0.59 in. (15 mm) Enfriamiento por delante Peso 3.02 lb. (1370 g) Certificaciones Temperatura Ambiente 3.42 in [86.8 mm] Diagnósticos LED LED OK AC Baja No DC Alta Carga Sobrecarga Caliente Entrada Salida Alarma La Perdida de AC Muy Caliente Verde --- Ámbar Verde Verde Verde Verde Verde Verde --- ----- Verde --- --Rojo Ámbar Ámbar Verde --Ámbar Rojo Ámbar Ámbar Especificaciones de Instalación Protección de Sobreintensidad Entrada: Fusibles internos. Salida: Las salidas son capaces de proporcionar altas corrientes por períodos cortos de tiempo para arranque de carga inductiva o conmutación. Relevo N.O. contacto valoró 200 mA/50 V CC. Conexiones Un dispositivo accesible de desconexión será instalado externo al equipo. Utilizar sólo conductor de cobre, 90ºC Entrada: terminales tipo tornillo Rango de tamaños de conectores: 1,5–6 mm2 para conductores unifilares o trenzados. Torque de tornillo: 50-73 N-cm Salida: dos terminales por salida. Rango de tamaños de conectores: 1,5–6 mm2 para conductores unifilares o trenzados. Torque de tornillo: 50-73 N-cm Se recomienda un conductor de torque sin ajuste. Nota: Durante la sustitución del suministro de energía, asegúrese de que las conexiones de cableado estén correctamente finalizadas, verificando que las ubicaciones de los ID de los terminales sean las mismas. La ubicación y la disposición de los terminales pueden variar según el fabricante y el número de modelo. Seguridad Las fuentes de alimentación deben cumplir las siguientes condiciones para un uso seguro cuando se instala en un área peligrosa de clase I, zona 2, grupos IIC: (1) El equipo solo se debe usar en un área de un grado de polución no mayor que 2, como se define en IEC 60664-1. (2) El equipo se debe instalar en un gabinete que proporcione un grado de protección no menor que IP54 de acuerdo con IEC 60079-0. (3) La clase de temperatura de operación (código T) de este dispositivo es T4. Advertencia — Peligro de Explosión — No desconecte el equipo si el circuito está conectado, exceptuando si se sabe que no existen concentraciones inflamables en el área. Advertencia — Peligro de Explosión — No abra la unidad. No sustituya componentes. No sustituya el fusible. Advertencia — La exposición a ciertas sustancias químicas podría degradar las propiedades selladoras de los materiales utilizados en el relé sellado. Las fuentes de alimentación deben cumplir con lo siguiente cuando se instalen en un entorno de áreas ordinarias: instalar en un entorno controlado. Montaje en Riel DIN Se adapta de manera sencilla en sistema Riel DIN TS35/7.5 ó Sistema TS35/15. UL 508/CSA C22.2 No. 107.1 UL 60950-1/CSA C22.2 60950-1 UL 60079-0, UL 60079-15 CAN/CSA 60079-0, CAN/CSA 60079-15 Class I, Zone 2 AEx nA nC IIC T4 Gc Class I, Zone 2 Ex nA nC IIC T4 U IEC60950-1, EN60950-1 Soporte técnico (800) 377-4384 • (847) 268-6651 [email protected] www.solahd.com Aunque se ha tomado toda precaución para asegurar precisión e integridad en esta información, Appleton Grp LLC d/b/a Appleton Group no asume ninguna responsabilidad y deniega toda responsabilidad por daños que resulten por el uso de esta información o por cualquier error u omisión. Las especificaciones están sujetas a cambios sin previo aviso. P/N: A272-166 Rev. 10 2/2018 © 2018 Appleton Grp LLC d/b/a Appleton Group. All rights reserved. II 3 G Ex ec nC IIC T4 Gc DEMKO 14ATEX1350833X EN60079-0, EN60079-7, EN60079-15 IECEx Ex ec nC IIC T4 Gc, IECEx UL15.0013X IEC60079, IEC60079, IEC60079-15 2Ex nA nC IIC T4 Gc X, №TC RU C-US.AA87.B.00539 MSIP-REM-N4C-SDN20 Aprobación de Tipo Aprobación de Tipo Emisiones/Inmmunidad EN 61326-1; EN 55032 Clase B; EN 55011 Grupo 1 Clase B EN 61000-3-2, EN 61000-3-3; EN 55024; EN 61000-6-1; EN 61000-6-2; EN 61000-6-3; EN 61000-6-4; SEMI F47 Inmmunidad a Picos 1. 2. 3. 4. 5. Incline la unidad como se ilustra. Póngala sobre el Riel DIN. Empuje hacia abajo hasta que se detenga. Empuje de la parte baja del frente para asegurar. Mueva la unidad ligeramente para verificar está segura.