CARLO GAVAZZI EM24DINAV53XE1X Manual de usuario

Tipo
Manual de usuario
EM24 E1
USER MANUAL
MANUALE UTENTE
BETRIEBSANLEITUNG
MANUEL D’EMPLOI
INSTRUCCIONES DE USO
BRUGERMANUAL
EN ITDA ES FR DE
EM24 E1
Three-phase energy analyzer
USER MANUAL
3EM24 E1 - Instruction manual | CARLO GAVAZZI Controls SpA
Contents
EM24 E1 4
Introduction 4
Description 4
UCS (Universal Conguration Software) 4
EM24 E1 use 5
Introduction 5
Display 5
Network parameters setting 6
Setting network parameters via DHCP 6
Setting network parameters without DHCP 6
Working with EM24 E1 7
Working with the measurement/info menu 7
Working with the settings menu 7
Resetting partial energy meter 7
Setting a parameter 8
Menu description 9
Measurement menu - measurement pages 9
Information Menu 10
Settings from EM24 E1 11
General settings 11
Essential information 12
Applications 12
Programming pages 13
Managing taris via Modbus command 14
Disabling tari management 14
Frontal LED 14
Frontal selector 14
Maintenance and disposal 15
4 EM24 E1 - Instruction manual | CARLO GAVAZZI Controls SpA
Information property
Copyright © 2018, CARLO GAVAZZI Controls SpA
All rights reserved in all countries.
CARLO GAVAZZI Controls SpA reserves the right to apply modifications or make improvements to the relative documentation
without the obligation of advance notice.
Safety messages
The following section describes the warnings related to user and device safety included in this document:
NOTICE: indicates obligations that if not observed may lead to damage to the device.
CAUTION! Indicates a risky situation which, if not avoided, may cause data loss.
IMPORTANT: provides essential information on completing the task that should not be neglected.
General warnings
This manual is an integral part of the product and accompanies it for its entire working life. It should be consulted for all
situations tied to configuration, use and maintenance. For this reason, it should always be accessible to operators.
NOTICE: no one is authorized to open the analyzer. This operation is reserved exclusively for CARLO GAVAZZI technical
service personnel.
Protection may be impaired if the instrument is used in a manner not specified by the manufacturer.
Service and warranty
In the event of malfunction, fault, requests for information, contact the CARLO GAVAZZI branch or distributor in your country.
Installation and use of analyzers other than those indicated in the provided instructions void the warranty.
Download
This manual www.productselection.net/MANUALS/UK/EM24_im_use.pdf
Installation instruction - EM24 www.productselection.net/MANUALS/UK/EM24_im_inst.pdf
UCS software www.productselection.net/Download/UK/ucs.zip
5EM24 E1 - Instruction manual | CARLO GAVAZZI Controls SpAEM24 E1 - Instruction manual | CARLO GAVAZZI Controls SpA
EM24 E1
Introduction
EM24 is a three-phase energy analyzer for DIN-rail mounting, with configuration joystick, frontal selector and LCD display.
The direct connection version (AV2) allows to measure up to 65 A, the CT connection version (AV5) allows to measure up to 34875 A by
means of current transformers (5 A secondary output).
The DHCP function is able to speed the commissioning and all the configuration parameters can be set up via UCS.
Description
AV2 AV5
Part
Description
A LCD display
B Voltage/current connections
C Joystick
D Selector with pin for MID seal (programming block)
E Inputs/outputs or communication port
F Pins for MID seal (protection covers included)
UCS (Universal Conguration Software)
UCS desktop is available for free download. It can be connected to EM24 via Ethernet (Modbus TCP/IP) .
The following is possible with UCS:
configure EM24 (online or offline)
view system status for diagnostics and configuration checks function overview
6 EM24 E1 - Instruction manual | CARLO GAVAZZI Controls SpA
EM24 E1 use
Introduction
EM24 is organized in two menus:
measurement and information menu: pages used to display the measurement pages, information relevant to the programmed parameters
and instrument firmware release
settings menu: pages used to set parameters
Display
The display is divided into 3 lines.
Symbol Description
Displaying of phase-to-neutral system voltage
Displaying of phase-to-phase system voltage
Displaying of max values
User ID
Displaying of system variables
Displaying of dmd variables
EEEE
Overflow.
Note: the DMD calculation, the hour-counter and the
energy meters functions are inhibited and the alarm
outputs are activated. The indication “EEEE” in a single
phase variable automatically implies the overflow condi-
tion of the relevant system variable, and the PF indica-
tion is forced to “0.000”.
7EM24 E1 - Instruction manual | CARLO GAVAZZI Controls SpAEM24 E1 - Instruction manual | CARLO GAVAZZI Controls SpA
Network parameters setting
Setting network parameters via DHCP
Step Action
1 Install EM24
2 Enable DHCP and exit with End
3 Connect the EM24 to the LAN network to which the PC is connected
4 Access the Info pages to view the assigned network parameters
5 Start UCS software and connect to EM24 via Manual connection> Modbus TCP
6 Enter the IP address displayed on the Info page (see point 4)
7 Access the settings, disable DHCP and assign the required network parameters (assigned by network administrator)
Setting network parameters without DHCP
Step Action
1 Install EM24
2 Disable DHCP (default setting)
3 Connect the PC to the EM24 via Ethernet cable (point to point connection)
4
Set the PC network properties as follows:
static IP address
IP address of the same class as the EM24, e.g. if the IP of EM24 is 192.168.1.10 (default), you can set the PC address to
192.168.1.20
Subnet mask: 255.255.255.0
Gateway: not necessary
5
Start UCS software and connect to EM24 via Manual connection> Modbus TCP, enter the EM24 IP address
(192.168.1.10 by default)
6 Access the settings and enter the required network parameters
7 Disconnect the Ethernet cable and connect the EM24 to the network to which the Modbus master is connected
8
EM24 E1 use
EM24 E1 - Instruction manual | CARLO GAVAZZI Controls SpA
Working with EM24 E1
Working with the measurement/info menu
Working with the settings menu
Resetting partial energy meter
Step Action Button
1 Press the button for at least 3 seconds
2 In the PASS page, set the password 1357
3 Confirm operation
4 In the rESEt page, set YES
5 Confirm operation
to next measurement page
to previous measurement page
to sengs menu
to previous info page to next info page
increase a parameter value
decrease a parameter value
edit/conrm
to previous page to next page
9
EM24 E1 use
EM24 E1 - Instruction manual | CARLO GAVAZZI Controls SpAEM24 E1 - Instruction manual | CARLO GAVAZZI Controls SpA
Step Action Button
6 In the EnE PrES page, set YES
7 Confirm operation
Setting a parameter
Example procedure: how to set Ct rAtio=20 and save changes.
Step Action Button
1 Power on the energy analyzer
2 Press the joystick for at least 3 seconds
3 In the PASS? page, select the correct password (default 0)
4 Confirm operation
5 Scroll pages until Ct rAtio
6 Enter the editing mode
7 Select 20
8 Confirm operation
9 Scroll pages until End to exit
10
EM24 E1 use
EM24 E1 - Instruction manual | CARLO GAVAZZI Controls SpA
Menu description
Measurement menu - measurement pages
The displayed pages depend on the application set.
Page Displayed measurements Description
1
L1-L2-L3
V
LNΣ
Hz
Phase sequence
System phase-neutral voltage
Frequency
2
L1-L2-L3
V
LLΣ
Hz
Phase sequence
System phase-phase voltage
Frequency
3
Tot kWh (+)
W
Σ
dmd
W
Σ
dmd max
Total imported active energy
System active power dmd
System active power dmd max
4
kWh
A dmd max
PArt
Active energy
Maximum dmd current
Partial active energy
5
Tot kvarh (+)
VA
Σ
dmd
VA
Σ
dmd max
Total imported reactive energy
System apparent power dmd
System apparent power dmd max
6
kvarh
VA
Σ
PArt
Reactive energy
System apparent power
Partial reactive energy
7
kWh (+)
t1
W
Σ
dmd
Imported active energy, tariff 1
System active power dmd
8
kWh (+)
t2
W
Σ
dmd
Imported active energy, tariff 2
System active power dmd
9
kWh (+)
t3
W
Σ
dmd
Imported active energy, tariff 3
System active power dmd
10
kWh (+)
t4
W
Σ
dmd
Imported active energy, tariff 4
System active power dmd
11
kvarh (+)
t1
W
Σ
dmd
Imported reactive energy, tariff 1
W
Σ
dmd
12
kvarh (+)
t2
W
Σ
dmd
Imported reactive energy, tariff 2
W
Σ
dmd
13
kvarh (+)
t3
W
Σ
dmd
Imported reactive energy, tariff 3
W
Σ
dmd
14
kvarh (+)
t4
W
Σ
dmd
Imported reactive energy, tariff 4
W
Σ
dmd
15
kWh (+) X
W X
User X
Imported active energy
Active power
User
16
kWh (+) Y
W Y
User Y
Imported active energy
Active power
User
17
kWh (+) Z
W Z
User Z
Imported active energy
Active power
User
18
Total kvarh (-)
VA
Σ
dmd
VA
Σ
dmd max
Total exported reactive energy
System apparent power dmd
System apparent power dmd max
19
Total kWh (-)
W
Σ
dmd
W
Σ
dmd max
Total exported active energy
System active power dmd
System active power dmd max
11
Congure the system
EM24 E1 - Instruction manual | CARLO GAVAZZI Controls SpAEM24 E1 - Instruction manual | CARLO GAVAZZI Controls SpA
20
Hours
W
Σ
PF
Σ
Total load operating hours
System active power
System power factor
21
Hours
VAr
Σ
PF
Σ
Total load operating hours
System reactive power
System power factor
22
var L1
var L2
var L3
Phase 1 reactive power
Phase 2 reactive power
Phase 3 reactive power
23
VA L1
VA L2
VA L3
Phase 1 apparent power
Phase 2 apparent power
Phase 3 apparent power
24
PF L1
PF L2
PF L3
Phase 1 power factor
Phase 2 power factor
Phase 3 power factor
25
W L1
W L2
W L3
Phase 1 active power
Phase 2 active power
Phase 3 active power
26
A L1
A L2
A L3
Phase 1 current
Phase 2 current
Phase 3 current
27
V L1-2
V L2-3
V L3-1
Phase 1-phase 2 voltage
Phase 2-phase 3 voltage
Phase 3-phase 1 voltage
28
V L1
V L2
V L3
Phase 1 voltage
Phase 2 voltage
Phase 3 voltage
Note: in programming mode, the last displayed page is stored.
Information Menu
Page Page title Information displayed
1 IP o.o.-.- IP address (first part)
2 IP -.-.o.o IP address (second part)
3 Sub o.o.-.- Subnet mask (first part)
4 Sub -.-.o.o Subnet mask (second part)
5 Gateo.o.-.- Default gateway (first part)
6 Gate-.-.o.o Default gateway (second part)
7 Port Modbus TCP port
8 DHCP DHCP enabling
9 Info Ethernet diagnostic
10 Ut ratio VT/PT ratio
11 CT ratio CT ratio
12
1P/2P/3P/3Pn
(2-3-4-wire)
dmd (time)
System
Connection (2-3-4-wire)
Dmd integration time (min.)
13 Pulse LED pulse weight (Number of kWh/kvarh per pulse)
14 Year
Firmware release
Year of production
12
Congure the system
EM24 E1 - Instruction manual | CARLO GAVAZZI Controls SpA
Settings from EM24 E1
General settings
The available settings depend on the application set.
Page title Sub-menu Description Values Default value
Cng PASS - Change password From 0 to 9999 0
APPLiCAt Application tYP.A
tYP.b
tYP.C
tYP.d
tYP.E
tYP.F
tYP.G
tYP.H
tYP.H
User USEr 1 User From 0 to 9999 1
USEr 2 From 0 to 9999 2
USEr 3 From 0 to 9999 3
dHCP - DHCP enabling oFF/on oFF
IP Addr IP o.-.-.- IP address From 000 to 255 192
IP -.o.-.- From 000 to 255 168
IP -.-.o.- From 000 to 255 1
IP -.-.-.o From 000 to 255 10
SUb SUb o.-.-.- Subnet mask From 000 to 255 255
SUb -.o.-.- From 000 to 255 255
SUb -.-.o.- From 000 to 255 255
SUb -.-.-.o From 000 to 255 0
GAtE GAtE o.-.-.- Default gateway From 000 to 255 192
GAtE -.o.-.- From 000 to 255 168
GAtE -.-.o.- From 000 to 255 1
GAtE -.-.-.o From 000 to 255 1
Port - MODBUS TCP port 502
SELECtor SELEC. 1 Page displayed according to selector
position among the available pages for
each application (see”Frontal selector”
on page 15)
From 1 to 28 1
SELEC. 2 From 1 to 28 25
SELEC. 3 From 1 to 28 28
SELEC.LoC From 1 to 28 3
SYS - System 3P.n
3P.1
2P
1P
3P
Note: MID (PFA, PFB): only 3P.n
3P.n
Ut rAtio - Voltage transformer ratio (VT) AV5: from 1 to 6975
AV2: N/A
1
Ct rAtio - Current transformer ratio (CT) AV5: from 1 to 6975
AV2: N/A
1
P int.ti - Dmd integration time (min) From 1 to 30 15
FiLtEr.S - Interval of lter intervention with respect
to full scale (%)
From 0 to 100 2
FiLtEr.Co - Filter coefcient From 1 to 32 2
End - Exit and save - -
Note: the Ut rAtio is available for compatibility with other versions, even though the AV5 version is not meant to be used with voltage transformers. It should
be therefore set to 1.
13
Essential information
EM24 E1 - Instruction manual | CARLO GAVAZZI Controls SpAEM24 E1 - Instruction manual | CARLO GAVAZZI Controls SpA
Essential information
Measurement management
Applications
Note: if an application with easy connection is selected, for the calculation of the active energy the power is always integrated, both in the case of imported
and exported power . The current direction does not affect the measurement. If an application without easy connection is selected, both the active imported
and exported are available.
Application Measurements Easy connection
A
System:
phase sequence
phase-neutral voltage
frequency
total imported active energy
active power dmd and dmd max
YES
B
System:
phase sequence
phase-neutral voltage
frequency
total imported active energy
active power dmd and dmd max
total imported reactive energy
apparent power dmd and dmd max
YES
C
System:
phase sequence
phase-neutral voltage
frequency
total imported active energy
active power dmd and dmd max
imported active and reactive energy by tariff
YES
D
Single phase:
imported active energy
voltage
YES
E
System:
phase sequence
phase-neutral voltage
frequency
total imported and exported active energy
active power dmd and dmd max
run hour meter
active power
power factor
NO
F
System:
phase sequence
phase-neutral voltage
frequency
total imported and exported active energy
active power dmd and dmd max
phase-phase voltage
active energy
maximum dmd current
partial active energy
total imported and exported reactive energy
apparent power, dmd and dmd max
partial reactive energy
run hour meter
active power
power factor
NO
14
Essential information
EM24 E1 - Instruction manual | CARLO GAVAZZI Controls SpA
G
System:
phase sequence
phase-neutral voltage
frequency
total imported active energy
active power dmd and dmd max
phase-phase voltage
active energy
maximum dmd current
partial active energy
total imported reactive energy
apparent power, dmd and dmd max
reactive energy
run hour meter
active power
active power dmd
reactive power
power factor
imported active and reactive energy by tariff
Single phase:
reactive power per phase
apparent power per phase
power factor per phase
active power per phase
current per phase
line-line voltages
line-neutral voltages
YES
H
System:
phase sequence
phase-neutral voltage
frequency
total imported and exported active energy
active power dmd and dmd max
phase-phase voltage
active energy
maximum dmd current
partial active energy
total imported and exported reactive energy
apparent power, dmd and dmd max
reactive energy
run hour meter
active power
active power dmd
reactive power
power factor
imported active and reactive energy by tariff
Single phase:
reactive power per phase
apparent power per phase
power factor per phase
active power per phase
current per phase
line-line voltages
line-neutral voltages
NO
Programming pages
The following table shows which programming pages are available for each application
Page Application
A B C D E F G H
Change password x x x x x x x x
Application x x x x x x x x
User - - - x - - - -
DHCP enabling x x x x x x x x
IP address x x x x x x x x
Subnet mask x x x x x x x x
Default gateway x x x x x x x x
MODBUS TCP port x x x x x x x x
15
Essential information
EM24 E1 - Instruction manual | CARLO GAVAZZI Controls SpAEM24 E1 - Instruction manual | CARLO GAVAZZI Controls SpA
Selector x x x x x x x x
System x x x x x x x
VT ratio x x x x x x x x
CT ratio x x x x x x x x
Average power integration time x x x - x x x x
Filter S - - - - - x x x
Filter Co - - - - - x x x
End x x x x x x x x
Tariff management
Managing taris via Modbus command
Change the tariff by entering the value corresponding to the current tariff according to the following table in the 1201Fh registry:
Current
tariff
Register
value
T1 1
T2 2
T3 3
T4 4
Disabling tari management
Set tariff management as disabled or enter 0 (default value) in the 1201Fh register.
Frontal LED and selector
Frontal LED
The frontal red LED flashes proportionally to the active imported energy consumption if the selector is in - 1 - 2 position, and to the reactive inductive
energy consumption in kvarh
position. Any kind of negative (exported) energy will not be managed by the front LED.
Frontal selector
Lock position: the frontal selector prevents from accessing the programming mode
1, 2, kvarh
position: quick access to measuring pages. Each position is associated with one measuring page according to the following table:
Application Selector position Page available
A
Lock
3
1,2,3 1
B, C, E, F, G, H
Lock, 1, 2, kvarh
Can be set from 1 to 28
C
Lock, 1, 2, kvarh
Can be set from 1 to 28
D
Lock 28
1 15
2 16
3 17
16
Maintenance and disposal
EM24 E1 - Instruction manual | CARLO GAVAZZI Controls SpA
Maintenance and disposal
Cleaning
Use a slightly dampened cloth to clean the display. Do not use abrasives or solvents.
Responsibility for disposal
The product must be disposed of at the relative recycling centers specified by the government or local public authorities. Correct disposal
and recycling will contribute to the prevention of potentially harmful consequences to the environment and persons.
EM24 E1 - Instruction manual | CARLO GAVAZZI Controls SpA
EM24 E1 - User manual
2018-06 | Copyright © 2018
CARLO GAVAZZI Controls SpA
via Safforze, 8
32100 Belluno (BL) Italy
www.gavazziautomation.com
info: +39 0437 355811
fax: +39 0437 355880
EM24 E1
Analizzatore di energia per sistemi trifase
MANUALE UTENTE
19EM24 E1 - Manuale utente | CARLO GAVAZZI Controls SpA
Sommario
EM24 E1 21
Introduzione 21
Descrizione 21
UCS (Universal Conguration Software) 21
Uso di EM24 E1 22
Introduzione 22
Display 22
Impostare i parametri di rete 23
Impostare i parametri di rete via DHCP 23
Impostare i parametri di rete senza DHCP 23
Operare nell’EM24 E1 24
Operare nel menu misure/info 24
Operare nel menuimpostazioni 24
Azzerare il contatore di energia parziale 24
Impostare un parametro 25
Descrizione dei manu 26
Menu misure- pagine di misura 26
Menu informazioni 27
Impostazioni da EM24 E1 28
Impostazioni generali 28
Cose da sapere 29
Applicazioni 29
Pagine di programmazione 30
Gestire le tarie tramite comando Modbus 31
Disabilitare la gestione tarie 31
LED frontale 31
Selettore frontale 31
Manutenzione e smaltimento 32
20 EM24 E1 - Manuale utente | CARLO GAVAZZI Controls SpA
Proprietà delle informazioni
Copyright © 2018, CARLO GAVAZZI Controls SpA
Tutti i diritti riservati in tutti i paesi.
CARLO GAVAZZI Controls SpA si riserva il diritto di apportare modifiche o miglioramenti alla relativa documentazione senza
obbligo di preavviso.
Messaggi di sicurezza
Di seguito le segnalazioni legate alla sicurezza dell’utilizzatore e dell’apparecchio contenute in questo documento:
AVVISO: indica obblighi che se non ottemperati possono causare danni all’apparecchio.
ATTENZIONE! Indica una situazione rischiosa che se non evitata, può causare la perdita di dati.
IMPORTANTE: offre indicazioni essenziali al completamento del compito che non devono essere trascurate.
Avvertenze generali
Questo manuale è parte integrante del prodotto e accompagna il prodotto per tutta la sua vita. Deve essere consultato per
tutte le situazioni legate alla configurazione, all’uso e alla manutenzione. Per questo motivo deve essere sempre accessibile
agli operatori.
AVVISO: nessuno è autorizzato ad aprire l’analizzatore. TSolo il personale dell’assistenza tecnica CARLO GAVAZZI può
farlo. La protezione può essere compromessa se lo strumento viene usato in un modo non specificato dal costruttore.
Assistenza e garanzia
In caso di malfunzionamento, guasto, necessità informazioni o per acquistare componenti contattare la filiale CARLO GAVAZZI o
il distributore nel paese di appartenenza.
L’installazione e l’uso dell’analizzatore diversi da quanto indicato nelle istruzioni fornite invalidano la garanzia.
Download
Questo manuale www.productselection.net/MANUALS/UK/EM24_im_use.pdf
Istruzioni per l’installazione - EM24 www.productselection.net/MANUALS/UK/EM24_im_inst.pdf
UCS software www.productselection.net/Download/UK/ucs.zip
21EM24 E1 - Manuale utente | CARLO GAVAZZI Controls SpAEM24 E1 - Manuale utente | CARLO GAVAZZI Controls SpA
EM24 E1
Introduzione
EM24 è un analizzatore di energia trifase per il montaggio su guida DIN, con joystick di configurazione, selettore frontale e display LCD.
La versione con connessione diretta (AV2) consente di misurare fino a 65 A, la versione con connessione TA (AV5) consente di misurare fino
a 34875 A tramite trasformatori di corrente (uscita secondaria 5 A).
La funzione DHCP è in grado di velocizzare la messa in servizio e tutti i parametri di configurazione possono essere impostati tramite UCS.
Descrizione
AV2 AV5
Parte Descrizione
A Display LCD
B Connessioni tensione/corrente
C Joystick
D Selettore con perno per sigillo MID (blocco programmazione)
E Uscite/ingressi o porta di comunicazione
F Perni per sigillo MID (coperture di protezione incluse)
UCS (Universal Conguration Software)
UCS desktop è disponibile per il download gratuito. Può essere collegato a EM24 via Ethernet (Modbus TCP/IP).
Con UCS è possibile:
configurare EM24 (online oppure offline)
visualizzare lo stato del sistema a fini diagnostici e di verifica della configurazione function overview
22 EM24 E1 - Manuale utente | CARLO GAVAZZI Controls SpA
Uso di EM24 E1
Introduzione
EM24 è organizzato in quattro menu:
menu misura e informazioni: pagine che mostrano le pagine di misura, informazioni sui parametri programmati e release firmware dello
strumento
menu impostazioni: pagine per impostare i parametri
Display
Il display è suddiviso in 3 righe.
Simbolo Descrizione
Visualizzazione tensione fase-neutro di sistema
Visualizzazione tensione fase-fase di sistema
Visualizzazione valori massimi
User ID (Identificatore utente)
Visualizzazione variabili di sistema
Visualizzazione variabili dmd
EEEE
Overflow.
Nota: le funzioni di calcolo DMD, conta-ore e contato-
ri di energia vengono inibite e le uscite allarme
vengono attivate. L’indicazione “EEEE” su una varia-
bile di singola fase si estende automaticamente alla
corrispondente variabile di sistema e l’indicazione PF
viene portata a “0.000”.
23EM24 E1 - Manuale utente | CARLO GAVAZZI Controls SpAEM24 E1 - Manuale utente | CARLO GAVAZZI Controls SpA
Impostare i parametri di rete
Impostare i parametri di rete via DHCP
Passo Azione
1 Installare l’EM24
2 Abilitare il DHCP ed uscire con End
3 Collegare l’EM24 alla rete LAN alla quale è connesso il PC
4 Accedere alle pagine Info er visualizzare i parametri di rete assegnati
5 Avviare il software UCS e collegare l’EM24 via Connessione manuale> Modbus TCP
6 Digitare l’indirizzo IP visualizzato nelle pagine Info (vedere punto 4)
7 Accedere alle impostazioni, disabilitare il DHCP ed assegnare i parametri di rete (forniti dall’amministratore di rete)
Impostare i parametri di rete senza DHCP
Passo Azione
1 Installare l’EM24
2 Disabilitare il DHCP (disabilitato per default)
3 Collegare il PC all’EM24 via cavo Ethernet (connessione punto-punto)
4
Impostare le proprietà di rete del PC come segue:
indirizzo IP statico
indirizzo IP della stessa classe dell’ IP dell’ EM24, e.g. se l’IP dell’EM24 è 192.168.1.10 (di default), è possibile impostare
l’indirizzo del PC a 192.168.1.20
Maschera di sottorete: 255.255.255.0
Gateway: non necessario
5
Avviare il software UCS e collegare l’EM24 via Connessione manuale> Modbus TCP, igitare l’indirizzo IP dell’EM24 (di
default 192.168.1.10)
6 Accedere alle impostazioni e digitare i parametri di rete richiesti
7 Scollegare il cavo Ethernet e collegare l’EM24 alla rete alla quale è connesso il master Modbus
24
Uso di EM24 E1
EM24 E1 - Manuale utente | CARLO GAVAZZI Controls SpA
Operare nell’EM24 E1
Operare nel menu misure/info
Operare nel menu impostazioni
Azzerare il contatore di energia parziale
Passo Azione Button
1 Premere il tasto per almeno 3 secondi
2 Nella pagina PASS, inserire la password 1357
3 Confermare l’operazione
4 Nella pagina rESEt, impostare YES
5 Confermare l’operazione
Visualizzare la pagina misura
successiva
Visualizzare la pagina misura
precedente
Visualizzare il menu
impostazioni
Visualizzare la pagina
info precedente
Visualizzare la pagina info
successiva
Aumentare il valore di un
parametro
Diminuire il valore di un
parametro
Modicare/
confermare
Visualizzare la
pagina precedente
Visualizzare la pagina
successiva
25
Uso di EM24 E1
EM24 E1 - Manuale utente | CARLO GAVAZZI Controls SpAEM24 E1 - Manuale utente | CARLO GAVAZZI Controls SpA
Passo Azione Button
6 Nella pagina EnE PrES, impostare YES
7 Confermare l’operazione
Impostare un parametro
Procedura di esempio: compe impostare Ct rAtio=20 salvare la modifica.
Passo Azione Tasto
1 Alimentare l’EM24
2 Premese il tasto per lameno 3 secondi
3 Nella pagina PASS?, selezionare la password corretta (di default 0)
4 Confermare l’operazione
5 Scorrere le pagine fino a Ct rAtio
6 Accedere alla modalità modifica
7 Selezionare 20
8 Confermare l’operazione
9 Scorrere le pagine fino a End per uscire
26
Uso di EM24 E1
EM24 E1 - Manuale utente | CARLO GAVAZZI Controls SpA
Descrizione dei menu
Menu misure- pagine di misura
Le pagine visualizzate dipendono dall’applicazione impostata.
Pagina Misure visualizzate Descrizione
1
L1-L2-L3
V
LNΣ
Hz
Sequenza fasi
Tensione fase-neutro di sistema
Frequenza
2
L1-L2-L3
V
LLΣ
Hz
Sequenza fasi
Tensione fase-fase di sistema
Frequenza
3
Tot kWh (+)
W
Σ
dmd
W
Σ
dmd max
Energia attiva importata totale
Potenza attiva di sistema dmd
Potenza attiva di sistema dmd max
4
kWh
A dmd max
PArt
Energia attiva
Corrente dmd massima
Energia attiva parziale
5
Tot kvarh (+)
VA
Σ
dmd
VA
Σ
dmd max
Energia reattiva importata totale
Potenza apparente di sistema dmd
Potenza apparente di sistema dmd max
6
kvarh
VA
Σ
PArt
Energia reattiva
Potenza apparente di sistema
Energia reattiva parziale
7
kWh (+)
t1
W
Σ
dmd
Energia attiva importata, tariffa 1
Potenza attiva di sistema dmd
8
kWh (+)
t2
W
Σ
dmd
Energia attiva importata, tariffa 2
Potenza attiva di sistema dmd
9
kWh (+)
t3
W
Σ
dmd
Energia attiva importata, tariffa 3
Potenza attiva di sistema dmd
10
kWh (+)
t4
W
Σ
dmd
Energia attiva importata, tariffa 4
Potenza attiva di sistema dmd
11
kvarh (+)
t1
W
Σ
dmd
Energia reattiva importata, tariffa 1
W
Σ
dmd
12
kvarh (+)
t2
W
Σ
dmd
Energia reattiva importata, tariffa 2
W
Σ
dmd
13
kvarh (+)
t3
W
Σ
dmd
Energia reattiva importata, tariffa 3
W
Σ
dmd
14
kvarh (+)
t4
W
Σ
dmd
Energia reattiva importata, tariffa 4
W
Σ
dmd
15
kWh (+) X
W X
User X
Energia attiva importata
Potenza attiva
Utente
16
kWh (+) Y
W Y
User Y
Energia attiva importata
Potenza attiva
Utente
17
kWh (+) Z
W Z
User Z
Energia attiva importata
Potenza attiva
Utente
18
Total kvarh (-)
VA
Σ
dmd
VA
Σ
dmd max
Energia reattiva esportata totale
Potenza apparente di sistema dmd
Potenza apparente di sistema dmd max
19
Total kWh (-)
W
Σ
dmd
W
Σ
dmd max
Energia attiva esportata totale
Potenza attiva di sistema dmd
Potenza attiva di sistema dmd max
27
Congurare il sistema
EM24 E1 - Manuale utente | CARLO GAVAZZI Controls SpAEM24 E1 - Manuale utente | CARLO GAVAZZI Controls SpA
20
Hours
W
Σ
PF
Σ
Contaore
Potenza attiva di sistema
Fattore di potenza di sistema
21
Hours
VAr
Σ
PF
Σ
Contaore
Potenza reattiva di sistema
Fattore di potenza di sistema
22
var L1
var L2
var L3
Potenza reattiva di fase 1
Potenza reattiva di fase 2
Potenza reattiva di fase 3
23
VA L1
VA L2
VA L3
Potenza apparente di fase 1
Potenza apparente di fase 2
Potenza apparente di fase 3
24
PF L1
PF L2
PF L3
Fattore di potenza di fase 1
Fattore di potenza di fase 2
Fattore di potenza di fase 3
25
W L1
W L2
W L3
Potenza attiva di fase 1
Potenza attiva di fase 2
Potenza attiva di fase 3
26
A L1
A L2
A L3
Corrente di fase 1
Corrente di fase 2
Corrente di fase 3
27
V L1-2
V L2-3
V L3-1
Tensione di fase 1-fase 2
Tensione di fase 2-fase 3
Tensione di fase 3-fase 1
28
V L1
V L2
V L3
Tensione di fase 1
Tensione di fase 2
Tensione di fase 3
Note: in modalità programmazione, rimane in memoria l’ultima pagina visualizzata.
Menu informazioni
Pagina Titolo pagina Informazioni visualizzate
1 IP o.o.-.- Indirizzo IP (prima parte)
2 IP -.-.o.o Indirizzo IP (seconda parte)
3 Sub o.o.-.- Maschera di sottorete (prima parte)
4 Sub -.-.o.o Maschera di sottorete (seconda parte)
5 Gateo.o.-.- Default gateway (prima parte)
6 Gate-.-.o.o Default gateway (seconda parte)
7 Port Porta Modbus TCP
8 DHCP Abilitazione DHCP
9 Info Diagnostica Ethernet
10 Ut ratio Rapporto TV
11 CT ratio Rapporto TA
12
1P/2P/3P/3Pn
(2-3-4-wire)
dmd (time)
Sistema
Connessione (2-3-4 fili)
Intervallo per il calcolo dei valori medi (min.)
13 Pulse Peso impulsi LED (numero di kWh/kvarh per impulso)
14 Year
Release firmware
Anno di produzione
28
Congurare il sistema
EM24 E1 - Manuale utente | CARLO GAVAZZI Controls SpA
Impostazioni da EM24 E1
Impostazioni generali
Le impostazioni disponibili dipendono dall’applicazione impostata.
Titolo pagina Sotto-menu Descrizione Valori Valori di default
Cng PASS - Modica password Da 0 a 9999 0
APPLiCAt Applicazione tYP.A
tYP.b
tYP.C
tYP.d
tYP.E
tYP.F
tYP.G
tYP.H
tYP.H
User USEr 1 Utente Da 0 a 9999 1
USEr 2 Da 0 a 9999 2
USEr 3 Da 0 a 9999 3
dHCP - Abilitazione DHCP oFF/on oFF
IP Addr IP o.-.-.- Indirizzo IP Da 000 a 255 192
IP -.o.-.- Da 000 a 255 168
IP -.-.o.- Da 000 a 255 1
IP -.-.-.o Da 000 a 255 10
SUb SUb o.-.-.- Maschera di sottorete Da 000 a 255 255
SUb -.o.-.- Da 000 a 255 255
SUb -.-.o.- Da 000 a 255 255
SUb -.-.-.o Da 000 a 255 0
GAtE GAtE o.-.-.- Gateway di default Da 000 a 255 192
GAtE -.o.-.- Da 000 a 255 168
GAtE -.-.o.- Da 000 a 255 1
GAtE -.-.-.o Da 000 a 255 1
Port - Porta MODBUS TCP 502
SELECtor SELEC. 1 Pagina visualizzata in base alla
posizione del selettore tra le pagine
disponibili per ciascuna applicazione (ve-
dere “Selettore frontale” a pagina 31)
Da 1 a 28 1
SELEC. 2 Da 1 a 28 25
SELEC. 3 Da 1 a 28 28
SELEC.LoC Da 1 a 28 3
SYS - Sistema 3P.n
3P.1
2P
1P
3P
Nota: MID (PFA, PFB): solo 3P.n
3P.n
Ut rAtio - Rapporto del trasformatore di tensione
(TV)
AV5: da 1 a 6975
AV2: N/D
1
Ct rAtio - Rapporto del trasformatore di corrente
(TA)
AV5: da 1 a 6975
AV2: N/D
1
P int.ti - Intervallo per il calcolo dei valori medi
(min)
Da 1 a 30 15
FiLtEr.S - Intervallo di intervento del ltro rispetto al
fondo scala (%)
Da 0 a 100 2
FiLtEr.Co - Coefciente del ltro Da 1 a 32 2
End - Esci e salva le modiche - -
Nota: Ut rAtio è disponibile per compatibilità con altre versioni, anche se la versione AV5 non è destinata ad essere utilizzata con trasformatori di tensione.
Dovrebbe essere quindi impostato a 1.
29
Cose da sapere
EM24 E1 - Manuale utente | CARLO GAVAZZI Controls SpAEM24 E1 - Manuale utente | CARLO GAVAZZI Controls SpA
Cose da sapere
Gestione misure
Applicazioni
Nota: se l’applicazione selezionata prevede la funzione Easy connection, per il calcolo dell’energia attiva la potenza è sempre integrata, sia nel caso di potenza
importata che esportata. La direzione della corrente non influisce sulla misura. Se l’applicazione selezionata non prevede la funzione Easy connection, sono
disponibili sia l’energia attiva importata che quella esportata.
Applicazione Misure Easy connection
A
Sistema:
sequenza fasi
tensione fase-neutro
frequenza
energia attiva importata totale
potenza attiva dmd e dmd max
B
Sistema:
sequenza fasi
tensione fase-neutro
frequenza
energia attiva importata totale
potenza attiva dmd e dmd max
energia reattiva importata totale
potenza apparente dmd e dmd max
C
Sistema:
sequenza fasi
tensione fase-neutro
frequenza
energia attiva importata totale
potenza attiva dmd e dmd max
energia attiva e reattiva importata per tariffa
D
Monofase:
energia attiva importata
tensione
E
Sistema:
sequenza fasi
tensione fase-neutro
frequenza
energia attiva e reattiva importata totale
potenza attiva dmd e dmd max
contaore
potenza attiva
fattore di potenza
NO
F
Sistema:
sequenza fasi
tensione fase-neutro
frequenza
energia attiva e reattiva importata totale
potenza attiva dmd e dmd max
tensione fase-fase
energia attiva
corrente dmd massima
energia attiva parziale
energia reattiva importata ed esportata totale
potenza apparente, dmd e dmd max
energia reattiva parziale
contaore
potenza attiva
fattore di potenza
NO
30
Cose da sapere
EM24 E1 - Manuale utente | CARLO GAVAZZI Controls SpA
G
Sistema:
sequenza fasi
tensione fase-neutro
frequenza
energia attiva importata totale
potenza attiva dmd e dmd max
tensione fase-fase
energia attiva
corrente dmd massima
energia attiva parziale
energia reattiva importata totale
potenza apparente, dmd e dmd max
energia reattiva
contaore
potenza attiva
potenza attiva dmd
potenza reattiva
fattore di potenza
energia attiva e reattiva importata per tariffa
Monofase:
potenza reattiva per fase
potenza apparente per fase
fattore di potenza per fase
potenza attiva per fase
corrente per fase
tensioni linea-linea
tensioni linea-neutro
H
Sistema:
sequenza fasi
tensione fase-neutro
frequenza
energia attiva e reattiva importata totale
potenza attiva dmd e dmd max
tensione fase-fase
energia attiva
corrente dmd massima
energia attiva parziale
energia reattiva importata ed esportata totale
potenza apparente, dmd e dmd max
energia reattiva
contaore
potenza attiva
potenza attiva dmd
potenza reattiva
fattore di potenza
energia attiva e reattiva importata per tariffa
Monofase:
potenza reattiva per fase
potenza apparente per fase
fattore di potenza per fase
potenza attiva per fase
corrente per fase
tensioni linea-linea
tensioni linea-neutro
NO
Pagine di programmazione
La tabella seguente mostra quali pagine di programmazione sono disponibili per ciascuna applicazione
Pagina Applicazione
A B C D E F G H
Modica password x x x x x x x x
Applicazione x x x x x x x x
Utente - - - x - - - -
Abilitazione DHCP x x x x x x x x
Indirizzo IP x x x x x x x x
Maschera di sottorete x x x x x x x x
Gateway di default x x x x x x x x
Porta MODBUS TCP x x x x x x x x
31
Cose da sapere
EM24 E1 - Manuale utente | CARLO GAVAZZI Controls SpAEM24 E1 - Manuale utente | CARLO GAVAZZI Controls SpA
Selettore x x x x x x x x
Sistema x x x x x x x
Rapporto del trasformatore di tensione (TV) x x x x x x x x
Rapporto del trasformatore di corrente (TA) x x x x x x x x
Intervallo per il calcolo dei valori medi x x x - x x x x
Intervallo di intervento del ltro rispetto al
fondo scala (%)
- - - - - x x x
Coeciente del ltro - - - - - x x x
End x x x x x x x x
Gestione tariffe
Gestire le tarie tramite comando Modbus
Comandare il cambio tariffa scrivendo nel registro 1201Fh il valore corrispondente alla tariffa attuale in accordo alla seguente tabella:
Tariffa
attuale
Valore
registro
T1 1
T2 2
T3 3
T4 4
Disabilitare la gestione tarie
Impostare la gestione delle tariffe come disabilitata oppure scrivere nel registro 1201Fh il valore 0 (valore di default)
LED e selettore frontali
LED frontale
Il LED rosso frontale lampeggia proporzionalmente al consumo di energia attiva importata se il selettore si trova in posizione - 1 - 2, e al consumo di
energia reattiva induttiva se in posizione kvarh
. Ogni tipo di energia negativa (esportata) non è gestita dal LED.
Selettore frontale
Posizione Lock : il selettore frontale impedisce l’accesso alla modalità di programmazione
Posizione 1, 2, kvarh
: accesso rapido alle pagine di misura. Ogni posizione è associata ad una pagina di misura in base alla tabella seguente:
Applicazione Posizione del seletore Pagina disponibile
A
Lock
3
1,2,3 1
B, C, E, F, G, H
Lock, 1, 2, kvarh
Selezionabile, da 1 a 28
C
Lock, 1, 2, kvarh
Selezionabile, da 1 a 28
D
Lock 28
1 15
2 16
3 17
32
Manutenzione e smaltimento
EM24 E1 - Manuale utente | CARLO GAVAZZI Controls SpA
Manutenzione e smaltimento
Pulizia
Per mantenere pulito il display usare un panno leggermente inumidito. Non usare abrasivi o solventi.
Responsabilità di smaltimento
Smaltire con raccolta differenziata tramite le strutture di raccolte indicate dal governo o dagli enti pubblici locali. Il corretto smaltimento
e il riciclaggio aiuteranno a prevenire conseguenze potenzialmente negative per l’ambiente e per le persone.
EM24 E1 - Manuale utente | CARLO GAVAZZI Controls SpA
EM24 E1 - Manuale utente
2018-06 | Copyright © 2018
CARLO GAVAZZI Controls SpA
via Safforze, 8
32100 Belluno (BL) Italy
www.gavazziautomation.com
info: +39 0437 355811
fax: +39 0437 355880
EM24 E1
Dreiphasen-Energieanalysator
BETRIEBSANLEITUNG
35EM24 E1 - Bedienungsanleitung | CARLO GAVAZZI Controls SpA
Inhaltsverzeichnis
EM24 E1 37
Einleitung 37
Beschreibung 37
UCS (Universal Conguration Software) (Kongurationssoftware) 37
Benutzung des EM24 E1 38
Einleitung 38
Anzeige 38
Netzwerkparametereinstellungen 39
Netzwerkparameter über DHCP einstellen 39
Netzwerkparameter ohne DHCP einstellen 39
Arbeiten mit EM24 E1 40
Arbeiten mit dem Messungs-/Infomenü 40
Arbeiten mit dem Einstellungsmenü 40
Setzt den partiellen Energiezähler zurück 40
Einstellen eines Parameters 41
Beschreibung der Menüs 42
Messungsmenü - Messungsseiten 42
Informationsmenü 43
Einstellungen vom EM24 E1 44
Allgemeine Einstellungen 44
Wichtige Informationen 45
Anwendungen 45
Programmierseiten 46
Tarifverwaltung über Modbus-Befehl 47
Deaktivierung der Tarifverwaltung 47
Front-LED 47
Vorderer Wahlschalter 47
Instandhaltung und Entsorgung 48
36 EM24 E1 - Bedienungsanleitung | CARLO GAVAZZI Controls SpA
Information über Eigentumsrechte
Copyright © 2018, CARLO GAVAZZI Controls SpA
Alle Rechte vorbehalten in allen Ländern.
CARLO GAVAZZI Controls SpA behält sich das Recht vor, ohne vorherige Ankündigung Änderungen oder Verbesserungen in der
entsprechenden Dokumentation vorzunehmen.
Sicherheitshinweise
Der folgende Abschnitt beschreibt die in diesem Dokument enthaltenen Warnungen in Bezug auf Benutzer- und Gerätesicherheit:
HINWEIS: Bezeichnet Bedienungsregeln, deren Nichtbeachtung zu Schäden am Gerät führen können.
VORSICHT! Bezeichnet eine riskante Situation, die Datenverlust verursachen kann, wenn sie nicht vermieden
wird.
WICHTIG: Bietet wesentliche Informationen zur Erledigung einer Aufgabe, die nicht vernachlässigt werden sollte.
Allgemeine Warnungen
Diese Anleitung ist ein integraler Bestandteil des Produkts und verbleibt bei ihm für seine gesamte Lebensdauer. Sie sollte
in allen Situationen betreffend Konfiguration, Gebrauch und Instandhaltung zu Rate gezogen werden. Deshalb sollte sie
dem Benutzer jederzeit zugänglich sein.
HINWEIS: Niemand ist autorisiert, das Analysator zu öffnen. Diese Operation ist ausschließlich dem technischen
Kundendienstpersonal von CARLO GAVAZZI vorbehalten.
Die Schutzfunktion kann beeinträchtigt werden, wenn das Instrument anders als vom Hersteller vorgesehen benutzt wird.
Kundendienst und Garantie
Bei Störungen oder Fehlern bzw. wenn Sie Auskünfte benötigen, wenden Sie sich bitte an die Niederlassung von CARLO GAVAZZI
oder den zuständigen Vertriebspartner in Ihrem Land.
Installation und Gebrauch von Analysatoren abweichend von der Beschreibung in der mitgelieferten Anleitung macht die Garantie
ungültig.
Download
Diese Anleitung www.productselection.net/MANUALS/UK/EM24_im_use.pdf
Installationsanleitung - EM24 www.productselection.net/MANUALS/UK/EM24_im_inst.pdf
UCS-Software www.productselection.net/Download/UK/ucs.zip
37EM24 E1 - Bedienungsanleitung | CARLO GAVAZZI Controls SpA
EM24 E1
Einleitung
EM24 ist ein Drei-Phasen-Energieanalysator für DIN-Schienenmontage mit Konfigurationsjoystick, frontseitigem Wahlschalter und LCD-
Anzeige.
Die Ausführung mit direktem Anschluss (AV2) ermöglicht die Messung bis zu 65 A, während die CT-Anschlussversion (AV5) die Messung bis
zu 34875 A mit Stromwandlern (5 A Sekundärausgang) erlaubt.
Die DHCP-Funktion kann die Inbetriebnahme beschleunigen, und alle Konfigurationsparameter können über die UCS eingestellt werden.
Beschreibung
AV2 AV5
Teil
Beschreibung
A LCD-Anzeige
B Spannungs-/Stromverbindungen
C Joystick
D Wahlschalter mit Stift für MID-Dichtung (Programmiersatz)
E Eingänge/Ausgänge oder Kommunikationsschnittstelle
F Stifte für MID-Dichtung (Schutzabdeckungen inbegriffen)
UCS (Universal Conguration Software) (Kongurationssoftware)
Die Arbeitsoberfläche der UCS ist frei herunterladbar. Sie kann über Ethernet (Modbus TCP/IP) mit EM24 verbunden werden.
UCS ermöglicht folgendes:
Konfiguration EM24 (Online oder Offline)
Anzeigen des Systemstatus für Diagnostik und zum Überprüfen der Konfiguration Funktionsüberblick
38 EM24 E1 - Bedienungsanleitung | CARLO GAVAZZI Controls SpA
Benutzung des EM24 E1
Einleitung
Der EM24 bietet zwei Menüs an:
Messungs- und Informationsmenü: Die Seiten zeigen Messwerteseiten, Informationen über die programmierten Parameter und
Firmwarefreigabe an
Einstellungsmenü: Die Seiten stellen die Parametereinstellungen dar
Anzeige
Die Anzeige ist in 3 Zeilen unterteilt.
Symbol Beschreibung
Anzeige der Phasen-Nullleiter-Systemspannung
Anzeige der Phasen-Phasen-Systemspannung
Anzeige der MAX-Werte
Benutzer-ID
Anzeige der Systemvariablen
Anzeige der DMD Variablen
EEEE
Overflow.
Hinweis:
Die DMD Berechnungs-, die Stundenzähler-
sowie die Energiezählerfunktionen sind gesperrt, und die
Alarmausgänge sind eingeschaltet. Die Angabe „EEEE”
in einer Einphasen-Variable deutet automatisch auf den
Overflow-Zustand der relevanten Systemvariable hin,
und die PF-Angabe wird zu „0.000” gezwungen.
39EM24 E1 - Bedienungsanleitung | CARLO GAVAZZI Controls SpA
Netzwerkparametereinstellungen
Netzwerkparameter über DHCP einstellen
Schritt Aktion
1 EM24 installieren
2 DHCP aktivieren und mit End verlassen
3 EM24 mit dem LAN-Netzwerk verbinden, an dem der PC angeschlossen ist
4 Zur Ansicht der zugeordneten Netzwerkparameter greifen Sie auf die Info Seiten
5 UCS-Software starten und mit EM24 über Manuelle Verbindung> Modbus TCP verbinden
6 Die auf der Info-Seite (siehe Punkt 4) angezeigte IP-Adresse eingeben
7
Greifen Sie auf die Einstellungen, deaktivieren Sie DHCP und ordnen Sie die notwendigen Netzwerkparameter zu (vom
Netzwerkadministrator vergeben)
Netzwerkparameter ohne DHCP einstellen
Schritt Aktion
1 EM24 installieren
2 DHCP deaktivieren (Standard-Einstellung)
3 Verbinden Sie den PC mit dem EM24 durch ein Ethernetkabel (Punkt-zu-Punkt Verbindung)
4
Die Netzwerkeigenschaften des PCs wie folgt einstellen:
statische IP-Adresse
IP-Adresse der gleichen Art wie EM24, z. Bsp. falls die IP von EM24 192.168.1.10 (Standard) ist, können Sie die PC-
Adresse auf 192.168.1.20 einstellen
Subnetzmaske: 255.255.255.0
Gateway: nicht nötig
5
UCS-Software starten und mit EM24 über Manuelle Verbindung> Modbus TCP verbinden, die EM24 IP-Adresse einge-
ben (192.168.1.10 standardmäßig)
6 Gelangen Sie zu den Einstellungen, und geben Sie die erforderlichen Netzwerkparameter ein
7 Ethernet-Kabel entfernen und EM24 mit dem Netzwerk verbinden, an dem der Modbus-Master angeschlossen ist
40
Benutzung des EM24 E1
EM24 E1 - Bedienungsanleitung | CARLO GAVAZZI Controls SpA
Arbeiten mit EM24 E1
Arbeiten mit dem Messungs-/Infomenü
Arbeiten mit dem Einstellungsmenü
Setzt den partiellen Energiezähler zurück
Schritt Aktion Taste
1 Die Taste für mindestens 3 Sekunden gedrückt halten
2
Auf der Seite PASS das Passwort 1357 eingeben
3 Operation bestätigen
4 Auf der Seite rESEt YES eingeben
5 Operation bestätigen
zur nächsten Messungsseite
zur vorherigen Messungsseite
zum Einstellungsmenü
zur vorherigen Seite zur nächsten Infoseite
Parameterwert erhöhen
Parameterwert verringern
Bearbeiten/Bestägen
zur vorherigen Seite
zur nächsten Seite
41
Benutzung des EM24 E1
EM24 E1 - Bedienungsanleitung | CARLO GAVAZZI Controls SpA
Schritt Aktion Taste
6 Auf der Seite EnE PrES YES eingeben
7 Operation bestätigen
Einstellen eines Parameters
Beispielprozedur: Wie Ct rAtio=20 gesetzt und die Änderung gespeichert wird.
Schritt Aktion Taste
1 Energiezähler einschalten
2 Joystick für mindestens 3 Sekunden gedrückt halten
3 Auf der Seite PASS? das richtige Passwort eingeben (Standard 0)
4 Operation bestätigen
5 Seiten scrollen bis Ct rAtio
6 Gelangen Sie in den Bearbeitungsmodus
7 20 auswählen
8 Operation bestätigen
9 Seiten scrollen bis End, um das Menü abzuschließen
42
Benutzung des EM24 E1
EM24 E1 - Bedienungsanleitung | CARLO GAVAZZI Controls SpA
Beschreibung der Menüs
Messungsmenü - Messungsseiten
Die angezeigten Seiten hängen von der eingestellten Anwendung ab.
Page Angezeigte Messungen Beschreibung
1
L1-L2-L3
V
LNΣ
Hz
Phasensequenz
System Phase-Nullleiter-Spannung
Frequenz
2
L1-L2-L3
V
LLΣ
Hz
Phasensequenz
System Phase-Phase-Spannung
Frequenz
3
Tot kWh (+)
W
Σ
dmd
W
Σ
dmd max
Importierte Wirkenergie gesamt
System-Wirkleistung DMD
System-Wirkleistung DMD max.
4
kWh
A dmd max
PArt
Wirkenergie
Maximalstrom DMD
Partielle Wirkenergie
5
Tot kvarh (+)
VA
Σ
dmd
VA
Σ
dmd max
Importierte Blindenergie gesamt
System-Scheinleistung DMD
System-Scheinleistung DMD max.
6
kvarh
VA
Σ
PArt
Blindenergie
System-Scheinleistung
Partielle Blindenergie
7
kWh (+)
t1
W
Σ
dmd
Importierte Wirkenergie, Tarif 1
System-Wirkleistung DMD
8
kWh (+)
t2
W
Σ
dmd
Importierte Wirkenergie, Tarif 2
System-Wirkleistung DMD
9
kWh (+)
t3
W
Σ
dmd
Importierte Wirkenergie, Tarif 3
System-Wirkleistung DMD
10
kWh (+)
t4
W
Σ
dmd
Importierte Wirkenergie, Tarif 4
System-Wirkleistung DMD
11
kvarh (+)
t1
W
Σ
dmd
Importierte Blindenergie, Tarif 1
W
Σ
DMD
12
kvarh (+)
t2
W
Σ
dmd
Importierte Blindenergie, Tarif 2
W
Σ
DMD
13
kvarh (+)
t3
W
Σ
dmd
Importierte Blindenergie, Tarif 3
W
Σ
DMD
14
kvarh (+)
t4
W
Σ
dmd
Importierte Blindenergie, Tarif 4
W
Σ
DMD
15
kWh (+) X
W X
User X
Importierte Wirkenergie
Wirkleistung
Benutzer
16
kWh (+) Y
W Y
User Y
Importierte Wirkenergie
Wirkleistung
Benutzer
17
kWh (+) Z
W Z
User Z
Importierte Wirkenergie
Wirkleistung
Benutzer
18
Total kvarh (-)
VA
Σ
dmd
VA
Σ
dmd max
Exportierte Blindenergie gesamt
System-Scheinleistung DMD
System-Scheinleistung DMD max.
19
Total kWh (-)
W
Σ
dmd
W
Σ
dmd max
Exportierte Wirkenergie gesamt
System-Wirkleistung DMD
System-Wirkleistung DMD max.
43
Systemkonguration
EM24 E1 - Bedienungsanleitung | CARLO GAVAZZI Controls SpA
20
Hours
W
Σ
PF
Σ
Gesamt-Betriebsstunden unter Last
System-Wirkleistung
System-Leistungsfaktor
21
Hours
VAr
Σ
PF
Σ
Gesamt-Betriebsstunden unter Last
System-Blindleistung
System-Leistungsfaktor
22
var L1
var L2
var L3
Blindleistung Phase 1
Blindleistung Phase 2
Blindleistung Phase 3
23
VA L1
VA L2
VA L3
Scheinleistung Phase 1
Scheinleistung Phase 2
Scheinleistung Phase 3
24
PF L1
PF L2
PF L3
Leistungsfaktor Phase 1
Leistungsfaktor Phase 2
Leistungsfaktor Phase 3
25
W L1
W L2
W L3
Wirkleistung Phase 1
Wirkleistung Phase 2
Wirkleistung Phase 3
26
A L1
A L2
A L3
Strom Phase 1
Strom Phase 2
Strom Phase 3
27
V L1-2
V L2-3
V L3-1
Spannung Phase 1-Phase 2
Spannung Phase 2-Phase 3
Spannung Phase 3-Phase 1
28
V L1
V L2
V L3
Spannung Phase 1
Spannung Phase 2
Spannung Phase 3
Hinweis: Die zuletzt angezeigte Seite wird im Programmiermodus gespeichert.
Informationsmenü
Page Seitentitel Angezeigte Information
1 IP o.o.-.- IP-Adresse (erster Teil)
2 IP -.-.o.o IP-Adresse (zweiter Teil)
3 Sub o.o.-.- Subnetzmaske (erster Teil)
4 Sub -.-.o.o Subnetzmaske (zweiter Teil)
5 Gateo.o.-.- Standard-Gateway (erster Teil)
6 Gate-.-.o.o Standard-Gateway (zweiter Teil)
7 Port Modbus TCP Port
8 DHCP DHCP aktiviert
9 Info Ethernet-Diagnose
10 Ut ratio Spannungswandler-/Stromwandlerverhältnis
11 CT ratio CT-Verhältnis
12
1P/2P/3P/3Pn
(2-3-4-wire)
dmd (time)
System
Anschluss (2-3-4-Draht)
DMD Integrationszeit (Min.)
13 Pulse LED Impulsgewicht (Anzahl der kWh/kvarh pro Impuls)
14 Year
Firmwarefreigabe
Herstellungsjahr
44
Systemkonguration
EM24 E1 - Bedienungsanleitung | CARLO GAVAZZI Controls SpA
Einstellungen vom EM24 E1
Allgemeine Einstellungen
Die verfügbaren Einstellungen hängen von der eingestellten Anwendung ab.
Seitentitel Untermenü Beschreibung Werte Standardwert
Cng PASS - Passwort ändern Von 0 bis 9999 0
APPLiCAt Anwendung tYP.A
tYP.b
tYP.C
tYP.d
tYP.E
tYP.F
tYP.G
tYP.H
tYP.H
User USEr 1 Benutzer Von 0 bis 9999 1
USEr 2 Von 0 bis 9999 2
USEr 3 Von 0 bis 9999 3
dHCP - DHCP aktiviert oFF/on oFF
IP Addr IP o.-.-.- IP-Adresse Von 000 bis 255 192
IP -.o.-.- Von 000 bis 255 168
IP -.-.o.- Von 000 bis 255 1
IP -.-.-.o Von 000 bis 255 10
SUb SUb o.-.-.- Subnetzmaske Von 000 bis 255 255
SUb -.o.-.- Von 000 bis 255 255
SUb -.-.o.- Von 000 bis 255 255
SUb -.-.-.o Von 000 bis 255 0
GAtE GAtE o.-.-.- Standard-Gateway Von 000 bis 255 192
GAtE -.o.-.- Von 000 bis 255 168
GAtE -.-.o.- Von 000 bis 255 1
GAtE -.-.-.o Von 000 bis 255 1
Port - MODBUS TCP Port 502
SELECtor SELEC. 1 Die Seite wird nach Stellung des Wahl-
schalters unter den verfügbaren Seiten
für jede Anwendung angezeigt (siehe
„Vorderer Wahlschalter“ auf Seite 47)
Von 1 bis 28 1
SELEC. 2 Von 1 bis 28 25
SELEC. 3 Von 1 bis 28 28
SELEC.LoC Von 1 bis 28 3
SYS - System 3P.n
3P.1
2P
1P
3P
Hinweis: MID (PFA, PFB): nur 3P.n
3P.n
Ut rAtio - Spannungswandlerverhältnis (VT) AV5: von 1 bis 6975
AV2: N/A
1
Ct rAtio - Stromwandlerverhältnis (CT) AV5: von 1 bis 6975
AV2: N/A
1
P int.ti - DMD Integrationszeit (Min) Von 1 bis 30 15
FiLtEr.S - Intervall für die Filteranwendung
bezüglich
der Vollausschläge (%)
Von 0 bis 100 2
FiLtEr.Co - Filterkoefzient Von 1 bis 32 2
End - Beenden und speichern - -
Hinweis: Das Ut rAtio ist zur Kompatibilität mit anderen Versionen verfügbar, obwohl die AV5 Version nicht für die Benutzung mit Spannungswandlern
vorgesehen ist. Daher soll es auf 1 eingestellt werden.
45
Wichtige Informationen
EM24 E1 - Bedienungsanleitung | CARLO GAVAZZI Controls SpA
Wichtige Informationen
Verwaltung der Messungen
Anwendungen
Hinweis: Wenn eine Anwendung mit einfachem Anschluss ausgewählt wird, ist der Strom für die Berechnung der Wirkenergie immer integriert, sowohl bei der
importierten als auch exportierten Leistung. Die Stromrichtung beeinträchtigt nicht die Messung. Wenn eine Anwendung ohne einfachen Anschluss ausgewählt
wird, ist sowohl die importierte als auch die exportierte Wirkleistung verfügbar.
Anwendung Messungen
Einfacher
Anschluss
A
System:
Phasensequenz
Phase-Nullleiter-Spannung
Frequenz
importierte Wirkenergie gesamt
Wirkleistung DMD und DMD max
JA
B
System:
Phasensequenz
Phase-Nullleiter-Spannung
Frequenz
importierte Wirkenergie gesamt
Wirkleistung DMD und DMD max
importierte Blindenergie gesamt
Scheinleistung DMD und DMD max
JA
C
System:
Phasensequenz
Phase-Nullleiter-Spannung
Frequenz
importierte Wirkenergie gesamt
Wirkleistung DMD und DMD max
importierte Wirk- und Blindenergie nach Tarif
JA
D
Einphasig:
importierte Wirkenergie
Spannung
JA
E
System:
Phasensequenz
Phase-Nullleiter-Spannung
Frequenz
importierte und exportierte Wirkenergie gesamt
Wirkleistung DMD und DMD max
Betriebsstundenzähler
Wirkleistung
Leistungsfaktor
NEIN
F
System:
Phasensequenz
Phase-Nullleiter-Spannung
Frequenz
importierte und exportierte Wirkenergie gesamt
Wirkleistung DMD und DMD max
Phase-Phase-Spannung
Wirkenergie
Maximalstrom DMD
Partielle Wirkenergie
importierte und exportierte Blindenergie gesamt
Scheinleistung, DMD und DMD max
Partielle Blindenergie
Betriebsstundenzähler
Wirkleistung
Leistungsfaktor
NEIN
46
Wichtige Informationen
EM24 E1 - Bedienungsanleitung | CARLO GAVAZZI Controls SpA
G
System:
Phasensequenz
Phase-Nullleiter-Spannung
Frequenz
importierte Wirkenergie gesamt
Wirkleistung DMD und DMD max
Phase-Phase-Spannung
Wirkenergie
Maximalstrom DMD
Partielle Wirkenergie
importierte Blindenergie gesamt
Scheinleistung, DMD und DMD max
Blindenergie
Betriebsstundenzähler
Wirkleistung
Wirkleistung DMD
Blindleistung
Leistungsfaktor
importierte Wirk- und Blindenergie nach Tarif
Einphasig:
Blindleistung pro Phase
Scheinleistung pro Phase
Leistungsfaktor pro Phase
Wirkleistung pro Phase
Strom pro Phase
Netznennspannung
Netz-Nullleiter-Spannung
JA
H
System:
Phasensequenz
Phase-Nullleiter-Spannung
Frequenz
importierte und exportierte Wirkenergie gesamt
Wirkleistung DMD und DMD max
Phase-Phase-Spannung
Wirkenergie
Maximalstrom DMD
Partielle Wirkenergie
importierte und exportierte Blindenergie gesamt
Scheinleistung, DMD und DMD max
Blindenergie
Betriebsstundenzähler
Wirkleistung
Wirkleistung DMD
Blindleistung
Leistungsfaktor
importierte Wirk- und Blindenergie nach Tarif
Einphasig:
Blindleistung pro Phase
Scheinleistung pro Phase
Leistungsfaktor pro Phase
Wirkleistung pro Phase
Strom pro Phase
Netznennspannung
Netz-Nullleiter-Spannung
NEIN
Programmierseiten
Die folgende Tabelle zeigt welche Programmierseiten für jede Anwendung zur Verfügung stehen
Page Anwendung
A B C D E F G H
Passwort ändern x x x x x x x x
Anwendung x x x x x x x x
Benutzer - - - x - - - -
DHCP aktiviert x x x x x x x x
IP-Adresse x x x x x x x x
Subnetzmaske x x x x x x x x
Standard-Gateway x x x x x x x x
MODBUS TCP Port x x x x x x x x
47
Wichtige Informationen
EM24 E1 - Bedienungsanleitung | CARLO GAVAZZI Controls SpA
Wahlschalter x x x x x x x x
System x x x x x x x
Spannungswandlerverhältnis x x x x x x x x
CT-Verhältnis x x x x x x x x
Durchschnittsleistung Integrationszeit x x x - x x x x
Filter S - - - - - x x x
Filter Co - - - - - x x x
End x x x x x x x x
Tarifverwaltung
Tarifverwaltung über Modbus-Befehl
Ändern Sie den Tarif durch Eingabe des Wertes, der gemäß folgender Tabelle dem aktuellen Tarif entspricht, in das Register 1201Fh:
Aktueller
Tarif
Register-
wert
T1 1
T2 2
T3 3
T4 4
Deaktivierung der Tarifverwaltung
Stellen Sie die Tarifverwaltung auf deaktiviert ein oder setzen Sie den Wert im Register 1201Fh auf 0 (Standardwert).
Front-LED und Wahlschalter
Front-LED
Die rote Front-LED blinkt proportional zum importierten Wirkenergieverbrauch falls sich der Wahlschalter in - 1 - 2 Position befindet sowie zum indukti-
ven Blindleistungsenergieverbrauch in kvarh Position befindet. Jede Art negativer (exportierter) Energie wird nicht von der Front-LED verwaltet.
Vorderer Wahlschalter
Lock Position: Der vordere Wahlschalter verhindert den Zugriff auf den Programmiermodus
1, 2, kvarh Position: Schnellzugriff auf die Messungsseiten. Jede Position steht in Verbindung mit einer Messungsseite gemäß folgender Tabelle:
Anwendung Wahlschalterposition Verfügbare Seite
A
Lock
3
1,2,3 1
B, C, E, F, G, H
Lock, 1, 2, kvarh
Kann von 1 bis 28 eingestellt werden
C
Lock, 1, 2, kvarh
Kann von 1 bis 28 eingestellt werden
D
Lock 28
1 15
2 16
3 17
48
Instandhaltung und Entsorgung
EM24 E1 - Bedienungsanleitung | CARLO GAVAZZI Controls SpA
Instandhaltung und Entsorgung
Reinigung
Benutzen Sie ein leicht angefeuchtetes Tuch zum Reinigen des Displays. Benutzen Sie keine Scheuer- oder Lösungsmittel.
Verantwortlichkeit für Entsorgung
Dieses Produkt muss bei einem geeigneten von der Regierung oder lokalen öffentlichen Autoritäten anerkannten Recyclingbetrieb
entsorgt werden. Ordnungsgemäße Entsorgung und Recycling tragen zur Vermeidung möglicher schädlicher Folgen für Umwelt und
Personen bei.
EM24 E1 - Betriebsanleitung
2018-06 | Copyright © 2018
CARLO GAVAZZI Controls SpA
via Safforze, 8
32100 Belluno (BL) Italien
www.gavazziautomation.com
Tel.: +39 0437 355811
Fax: +39 0437 355880
EM24 E1
Analyseur d’énergie triphasé
MANUEL D’EMPLOI
51EM24 E1 - Manuel d’instructions | CARLO GAVAZZI Controls SpA
Sommaire
EM24 E1 53
Introduction 53
Description 53
UCS (Logiciel de conguration universelle) 53
Utilisation EM24 E1 54
Introduction 54
Achage 54
Configuration des paramètres du réseau 55
Paramétrage du réseau via DHCP 55
Paramétrage du réseau sans DHCP 55
Travailler avec l’EM24 E1 56
Travailler avec le menu mesures/infos 56
Travailler avec le menu paramètres 56
Réinitialiser le compteur d’énergie partiel 56
Congurer un paramètre 57
Description du menu 58
Menu Mesures - pages mesures 58
Menu informations 59
Paramètres d’EM24 E1 60
Paramètres généraux 60
Informations essentielles 61
Applications 61
Pages de programmation 62
Gérer les tarifs via la commande Modbus 63
Désactivation de la gestion tarifaire 63
LED frontale 63
Sélecteur frontal 63
Entretien et élimination 64
52 EM24 E1 - Manuel d’instructions | CARLO GAVAZZI Controls SpA
Propriété des informations
Copyright © 2018, CARLO GAVAZZI Controls SpA
Tous droits réservés dans tous les pays.
CARLO GAVAZZI Controls SpA se réserve le droit d’apporter des modifications ou des améliorations à la documentation relative
sans préavis.
Messages de sécurité
La section suivante décrit les avertissements relatifs à la sécurité de l’utilisateur et du dispositif inclus dans ce document :
AVIS : indique les obligations qui, si non observées, peuvent entraîner l’endommagement du dispositif.
ATTENTION! Indique une situation de risque qui, si elle n’est pas évitée, peut entraîner la perte de données.
IMPORTANT : fournit des informations essentielles pour compléter la tâche qui ne doivent pas être négligées.
Avertissements généraux
Ce manuel fait partie intégrante du produit et l’accompagne pendant toute sa durée de vie. Il doit être consulté pour toutes
les situations liées à la configuration, et à l’entretien. Pour cette raison, il devra toujours être accessible aux opérateurs.
AVERTISSEMENT : personne n’est autorisé à ouvrir l’analyseur. Cette opération est réservée exclusivement au personnel
du service technique CARLO GAVAZZI.
La protection peut être compromise si l’instrument est utilisé d’une manière non spécifiée par le fabricant.
Entretien et garantie
En cas de dysfonctionnement, de panne ou de besoin d’informations, contactez la filiale ou le distributeur CARLO GAVAZZI de
votre pays.
L’installation et l’utilisation d’analyseurs autres que ceux indiqués dans les instructions fournies annulent la garantie.
Télécharger
Ce manuel www.productselection.net/MANUALS/UK/EM24_im_use.pdf
Instructions d’installation - EM24 www.productselection.net/MANUALS/UK/EM24_im_inst.pdf
logiciel UCS www.productselection.net/Download/UK/ucs.zip
53EM24 E1 - Manuel d’instructions | CARLO GAVAZZI Controls SpA
EM24 E1
Introduction
L’EM24 est un analyseur d’énergie triphasé pour montage sur rail DIN avec joystick de configuration, sélecteur frontal et écran à cristaux
liquides.
La version à connexion directe (AV2) permet de mesurer jusqu’à 65 A, la version à connexion CT (AV5) permet de mesurer jusqu’à 34875 A au
moyen de transformateurs de courant (sortie secondaire 5 A).
La fonction DHCP est capable d’accélérer la mise en service et tous les paramètres de configuration peuvent être configurés via UCS.
Description
AV2 AV5
Pièce
Description
A Affichage LCD
B Connexions tension/courants
C Joystick
D Sélecteur avec broche pour scellé MID (bloc de programmation)
E Entrées/sorties ou port de communication
F Broches pour scellé MID (couvercles de protection inclus)
UCS (Logiciel de conguration universelle)
Le bureau UCS est disponible en téléchargement gratuit. Il peut être connecté à l’EM24 via Ethernet (Modbus TCP/IP).
Ce qui suit est possible avec UCS :
configurer l’EM24 (en ligne ou hors ligne)
afficher l’état du système pour les diagnostics et les vérifications de configuration vue d’ensemble de la fonction
54 EM24 E1 - Manuel d’instructions | CARLO GAVAZZI Controls SpA
Utilisation EM24 E1
Introduction
EM24 est organisé en deux menus :
menu de mesure et d’information : pages d’affichage des pages de mesure, des informations relatives aux paramètres programmés et de
la version du micrologiciel de l’instrument
menu paramètres : pages utilisées pour définir les paramètres
Achage
L’écran est réparti en 3 lignes.
Symbole
Description
Affichage de la tension simple
Affichage de la tension système phase à phase
Affichage des valeurs maximales
Identifiant utilisateur
Affichage des variables système
Affichage des variables dmd
EEEE
Surcharge.
Remarque :
les fonctions de calcul DMD, du compteur
d’heures et des compteurs d’énergie sont bloquées et
les sorties d’alarme sont activées. L’indication « EEEE »
dans une variable monophasé implique automatique-
ment la condition de surcharge de la variable système
en question, et l’indication PF est forcée sur « 0,000 ».
55EM24 E1 - Manuel d’instructions | CARLO GAVAZZI Controls SpA
Configuration des paramètres du réseau
Paramétrage du réseau via DHCP
Étape Action
1 Installer l’EM24
2 Activer le DHCP et quitter sortir à l’aide de l’option Fin
3 Connecter l’EM24 au réseau LAN auquel le PC est connecté
4 Accéder aux pages Infos pour afficher les paramètres réseau assignés
5 Démarrer le logiciel UCS et se connecter au EM24 via Connexion manuelle > Modbus TCP
6 Saisir l’adresse IP affichée sur la page Infos (voir point 4)
7 Accéder aux paramètres, désactiver DHCP et attribuer les paramètres réseau requis (attribués par l’administrateur réseau)
Paramétrage du réseau sans DHCP
Étape Action
1 Installer l’EM24
2 Désactiver DHCP (réglage par défaut)
3 Connecter le PC à l’EM24 par le câble Ethernet (connexion point à point)
4
Régler les propriétés de réseau du PC comme suit :
adresse IP statique
Adresse IP de la même classe que l’EM24, par exemple si l’IP de l’EM24 est 192.168.1.10 (par défaut), vous pouvez définir
l’adresse du PC sur 192.168.1.20
Masque de sous-réseau : 255.255.255.0
Passerelle : pas nécessaire
5
Démarrer le logiciel UCS et se connecter à l’EM24 via Connexion manuelle> Modbus TCP, saisir l’adresse IP de l’EM24
(192.168.1.10 par défaut)
6 Accéder aux paramètres et saisir les paramètres réseau requis
7 Débrancher le câble Ethernet et connecter l’EM24 au réseau auquel le maître Modbus est connecté
56
Utilisation EM24 E1
EM24 E1 - Manuel d’instructions | CARLO GAVAZZI Controls SpA
Travailler avec l’EM24 E1
Travailler avec le menu mesures/infos
Travailler avec le menu paramètres
Réinitialiser le compteur d’énergie partiel
Étape Action Bouton
1 Appuyer sur le bouton pendant au moins 3 secondes
2
Sur la page PASS, sélectionner le mot de passe 1357
3 Confirmer l’opération
4 Sur la page rESEt, régler sur YES
5 Confirmer l’opération
vers la page de mesure suivante
vers la page de mesure précédente
vers le menu paramètres
vers la page d’infos précédente vers la page d’infos suivante
augmenter la valeur d’un paramètre
diminuer la valeur d’un paramètre
modier/conrmer
vers la page précédente
vers la page suivante
57
Utilisation EM24 E1
EM24 E1 - Manuel d’instructions | CARLO GAVAZZI Controls SpA
Étape Action Bouton
6 Sur la page EnE PrES, régler sur YES
7 Confirmer l’opération
Congurer un paramètre
Exemple de procédure : comment configurer Ct rAtio=20 et enregistrer les modifications.
Étape Action Bouton
1 Mettre l’analyseur d’énergie sous tension
2 Appuyer sur le joystick pendant au moins 3 secondes
3 Sur la page PASS?, sélectionner le bon mot de passe (0 par défaut)
4 Confirmer l’opération
5 Faire défiler les pages jusqu’à Ct rAtio
6 Accéder au mode d’édition
7 Sélectionner 20
8 Confirmer l’opération
9 Faire défiler les pages jusqu’à Fin pour quitter
58
Utilisation EM24 E1
EM24 E1 - Manuel d’instructions | CARLO GAVAZZI Controls SpA
Description du menu
Menu Mesures - pages mesures
Les pages affichées dépendent de l’ensemble de l’application.
Page Mesures affichées Description
1
L1-L2-L3
V
LNΣ
Hz
Séquence de phase
Tension phase-neutre système
Fréquence
2
L1-L2-L3
V
LLΣ
Hz
Séquence de phase
Tension phase-phase système
Fréquence
3
Tot kWh (+)
W
Σ
dmd
W
Σ
dmd max
Énergie active importée totale
Puissance active système dmd
Puissance active système dmd max
4
kWh
A dmd max
PArt
Énergie active
Courant dmd maximal
Énergie active partielle
5
Tot kvarh (+)
VA
Σ
dmd
VA
Σ
dmd max
Énergie réactive importée totale
Puissance apparente système dmd
Puissance apparente système dmd max
6
kvarh
VA
Σ
PArt
Énergie réactive
Puissance apparente système
Énergie réactive partielle
7
kWh (+)
t1
W
Σ
dmd
Énergie active importée, tarif 1
Puissance active système dmd
8
kWh (+)
t2
W
Σ
dmd
Énergie active importée, tarif 2
Puissance active système dmd
9
kWh (+)
t3
W
Σ
dmd
Énergie active importée, tarif 3
Puissance active système dmd
10
kWh (+)
t4
W
Σ
dmd
Énergie active importée, tarif 4
Puissance active système dmd
11
kvarh (+)
t1
W
Σ
dmd
Énergie réactive importée, tarif 1
W
Σ
dmd
12
kvarh (+)
t2
W
Σ
dmd
Énergie réactive importée, tarif 2
W
Σ
dmd
13
kvarh (+)
t3
W
Σ
dmd
Énergie réactive importée, tarif 3
W
Σ
dmd
14
kvarh (+)
t4
W
Σ
dmd
Énergie réactive importée, tarif 4
W
Σ
dmd
15
kWh (+) X
W X
User X
Énergie active importée
Puissance active
Utilisateur
16
kWh (+) Y
W Y
User Y
Énergie active importée
Puissance active
Utilisateur
17
kWh (+) Z
W Z
User Z
Énergie active importée
Puissance active
Utilisateur
18
Total kvarh (-)
VA
Σ
dmd
VA
Σ
dmd max
Énergie réactive exportée totale
Puissance apparente système dmd
Puissance apparente système dmd max
19
Total kWh (-)
W
Σ
dmd
W
Σ
dmd max
Énergie active exportée totale
Puissance active système dmd
Puissance active système dmd max
59
Congurer le système
EM24 E1 - Manuel d’instructions | CARLO GAVAZZI Controls SpA
20
Hours
W
Σ
PF
Σ
Total heures de fonctionnement de la charge
Puissance active système
Facteur de puissance système
21
Hours
VAr
Σ
PF
Σ
Total heures de fonctionnement de la charge
Puissance réactive système
Facteur de puissance système
22
var L1
var L2
var L3
Puissance réactive phase 1
Puissance réactive phase 2
Puissance réactive phase 3
23
VA L1
VA L2
VA L3
Puissance apparente phase 1
Puissance apparente phase 2
Puissance apparente phase 3
24
PF L1
PF L2
PF L3
Facteur de puissance phase 1
Facteur de puissance phase 2
Facteur de puissance phase 3
25
W L1
W L2
W L3
Puissance active phase 1
Puissance active phase 2
Puissance active phase 3
26
A L1
A L2
A L3
Courant phase 1
Courant phase 2
Courant phase 3
27
V L1-2
V L2-3
V L3-1
Tension phase 1-phase 2
Tension phase 2-phase 3
Tension phase 3-phase 1
28
V L1
V L2
V L3
Tension de phase 1
Tension de phase 2
Tension de phase 3
Remarque : en mode de programmation, la dernière page affichée est stockée.
Menu informations
Page Titre page Informations affichées
1 IP o.o.-.- Adresse IP (première partie)
2 IP -.-.o.o Adresse IP (deuxième partie)
3 Sub o.o.-.- Masque de sous-réseau (première partie)
4 Sub -.-.o.o Masque de sous-réseau (deuxième partie)
5 Gateo.o.-.- Passerelle par défaut (première partie)
6 Gate-.-.o.o Passerelle par défaut (deuxième partie)
7 Port Port Modbus TCP
8 DHCP Activation du DHCP
9 Info Diagnostic Ethernet
10 Ut ratio Rapport transformateur de tension (TT)/de puissance (TP)
11 CT ratio Rapport CT
12
1P/2P/3P/3Pn
(2-3-4-wire)
dmd (time)
Système
Connexion (à 2-3-4 fils)
Temps d’intégration dmd (min.)
13 Pulse Poids d’impulsion LED (Nombre de kWh/kvarh par impulsion)
14 Year
Version du micrologiciel
Année de production
60
Congurer le système
EM24 E1 - Manuel d’instructions | CARLO GAVAZZI Controls SpA
Paramètres d’EM24 E1
Paramètres généraux
Les paramètres disponibles dépendent de l’ensemble de l’application.
Titre page Sous-me-
nu
Description Valeur Valeur par
défaut
Cng PASS - Changer le mot de passe De 0 à 9999 0
APPLiCAt Application tYP.A
tYP.b
tYP.C
tYP.d
tYP.E
tYP.F
tYP.G
tYP.H
tYP.H
User USEr 1 Utilisateur De 0 à 9999 1
USEr 2 De 0 à 9999 2
USEr 3 De 0 à 9999 3
dHCP - Activation du DHCP oFF/on oFF
IP Addr IP o.-.-.- Adresse IP De 000 à 255 192
IP -.o.-.- De 000 à 255 168
IP -.-.o.- De 000 à 255 1
IP -.-.-.o De 000 à 255 10
SUb SUb o.-.-.- Masque de sous-réseau De 000 à 255 255
SUb -.o.-.- De 000 à 255 255
SUb -.-.o.- De 000 à 255 255
SUb -.-.-.o De 000 à 255 0
GAtE GAtE o.-.-.- Passerelle par défaut De 000 à 255 192
GAtE -.o.-.- De 000 à 255 168
GAtE -.-.o.- De 000 à 255 1
GAtE -.-.-.o De 000 à 255 1
Port - Port MODBUS TCP 502
SELECtor SELEC. 1 Page afchée selon la position du
sélecteur parmi les pages disponibles
pour chaque application (voir «Sélecteur
frontal» à la page 63)
De 1 à 28 1
SELEC. 2 De 1 à 28 25
SELEC. 3 De 1 à 28 28
SELEC.LoC De 1 à 28 3
SYS - Système 3P.n
3P.1
2P
1P
3P
Remarque : MID (PFA, PFB) : uniquement 3P.n
3P.n
Ut rAtio - Rapport transformateur de tension (TT) AV5 : de 1 à 6975
AV2 : S.O.
1
Ct rAtio - Rapport de transformateur courant (CT) AV5 : de 1 à 6975
AV2 : S.O.
1
P int.ti - Temps d’intégration dmd (min.) De 1 à 30 15
FiLtEr.S - Intervalle d’intervention du ltre par
rapport à
la pleine échelle (%)
De 0 à 100 2
FiLtEr.Co - Coefcient du ltre De 1 à 32 2
End - Quitter et enregistrer - -
Remarque : la valeur Ut rAtio est disponible pour assurer la compatibilité avec les autres versions même si la version AV5 n’est pas destinée à être utilisée avec
des transformateurs de tension. Elle doit donc être réglée sur 1.
61
Informations essentielles
EM24 E1 - Manuel d’instructions | CARLO GAVAZZI Controls SpA
Informations essentielles
Gestion des mesures
Applications
Remarque : si une application avec une connexion facile est sélectionnée, pour le calcul de l’énergie active, la puissance est toujours intégrée, à la fois dans le
cas de l’alimentation importée et exportée. La direction actuelle n’a pas d’incidence sur la mesure. Si une application sans connexion facile est sélectionnée, les
alimentations active importée et exportée sont disponibles.
Application Mesures
Connexion
simple
A
Système :
séquence de phase
tension phase-neutre
fréquence
énergie active importée totale
puissance active dmd et dmd max
OUI
B
Système :
séquence de phase
tension phase-neutre
fréquence
énergie active importée totale
puissance active dmd et dmd max
énergie réactive importée totale
puissance apparente dmd et dmd max
OUI
C
Système :
séquence de phase
tension phase-neutre
fréquence
énergie active importée totale
puissance active dmd et dmd max
énergie importée active et réactive par tarif
OUI
D
Monophasé:
énergie active importée
tension
OUI
E
Système :
séquence de phase
tension phase-neutre
fréquence
énergie active importée et exportée totale
puissance active dmd et dmd max
compte-heures
puissance active
facteur de puissance
NO
F
Système :
séquence de phase
tension phase-neutre
fréquence
énergie active importée et exportée totale
puissance active dmd et dmd max
tension phase-phase
énergie active
courant dmd maximal
énergie active partielle
énergie réactive importée et exportée totale
puissance apparente, dmd et dmd max
énergie réactive partielle
compte-heures
puissance active
facteur de puissance
NO
62
Informations essentielles
EM24 E1 - Manuel d’instructions | CARLO GAVAZZI Controls SpA
G
Système :
séquence de phase
tension phase-neutre
fréquence
énergie active importée totale
puissance active dmd et dmd max
tension phase-phase
énergie active
courant dmd maximal
énergie active partielle
énergie réactive importée totale
puissance apparente, dmd et dmd max
énergie réactive
compte-heures
puissance active
puissance active dmd
puissance réactive
facteur de puissance
énergie importée active et réactive par tarif
Monophasé:
puissance réactive par phase
puissance apparente par phase
facteur de puissance par phase
puissance active par phase
courant par phase
tensions ligne-ligne
tensions ligne-neutre
OUI
H
Système :
séquence de phase
tension phase-neutre
fréquence
énergie active importée et exportée totale
puissance active dmd et dmd max
tension phase-phase
énergie active
courant dmd maximal
énergie active partielle
énergie réactive importée et exportée totale
puissance apparente, dmd et dmd max
énergie réactive
compte-heures
puissance active
puissance active dmd
puissance réactive
facteur de puissance
énergie importée active et réactive par tarif
Monophasé:
puissance réactive par phase
puissance apparente par phase
facteur de puissance par phase
puissance active par phase
courant par phase
tensions ligne-ligne
tensions ligne-neutre
NO
Pages de programmation
Le tableau ci-dessous ache les pages de programmation disponibles pour chaque application
Page Application
A B C D E F G H
Changer le mot de passe x x x x x x x x
Application x x x x x x x x
Utilisateur - - - x - - - -
Activation du DHCP x x x x x x x x
Adresse IP x x x x x x x x
Masque de sous-réseau x x x x x x x x
Passerelle par défaut x x x x x x x x
Port MODBUS TCP x x x x x x x x
63
Informations essentielles
EM24 E1 - Manuel d’instructions | CARLO GAVAZZI Controls SpA
Sélecteur x x x x x x x x
Système x x x x x x x
Rapport transformateur de tension x x x x x x x x
Rapport CT x x x x x x x x
Temps d’intégration de puissance moyenne x x x - x x x x
Filtre S - - - - - x x x
Filtre Co - - - - - x x x
Fin x x x x x x x x
Gestion tarifaire
Gérer les tarifs via la commande Modbus
Modifier le tarif en entrant la valeur correspondant au tarif actuel selon le tableau suivant dans le registre 1201Fh :
Tarif actuel
Valeur de
registre
T1 1
T2 2
T3 3
T4 4
Désactivation de la gestion tarifaire
Paramétrer la gestion des tarifs comme désactivée ou saisir 0 (valeur par défaut) dans le registre 1201Fh.
LED frontale et sélecteur
LED frontale
La LED rouge frontale clignote proportionnellement à la consommation d’énergie importée active si le sélecteur est en position 1 - 2 , et à la consomma-
tion d’énergie réactive à induction en position kvarh
. La LED frontale ne gère pas tous les types d’énergie (exporté) négative.
Sélecteur frontal
Position Verrouiller : le sélecteur frontal empêche d’accéder au mode de programmation
Position 1, 2, kvarh : accès rapide aux pages de mesure. Chaque position est associée à une seule page de mesure conformément au tableau suivant :
Application Position du sélecteur Page disponible
A
Verrouiller
3
1,2,3 1
B, C, E, F, G, H
Verrouiller, 1, 2, kvarh
Peut être réglée de 1 à 28
C
Verrouiller, 1, 2, kvarh
Peut être réglée de 1 à 28
D
Verrouiller 28
1 15
2 16
3 17
64
Entretien et élimination
EM24 E1 - Manuel d’instructions | CARLO GAVAZZI Controls SpA
Entretien et élimination
Nettoyage
Utiliser un chiffon humide pour nettoyer l’afficheur. Ne pas utiliser d’abrasifs ou de solvants.
Responsabilité de l’élimination
Le produit doit être éliminé dans les déchetteries spécifiés par le gouvernement ou les autorités locales. Une élimination et un recyclage
corrects contribueront à prévenir des conséquences potentiellement nuisibles pour l’environnement et les personnes.
EM24 E1 - Manuel d’emploi
2018-06 | Copyright © 2018
CARLO GAVAZZI Controls SpA
via Safforze, 8
32100 Belluno (BL) Italy
www.gavazziautomation.com
info : +39 0437 355811
fax : +86 755 355880
EM24 E1
Analizador de energía trifásico
INSTRUCCIONES DE USO
67EM24 E1 - Manual de instrucciones | CARLO GAVAZZI Controls SpA
Contenido
EM24 E1 69
Introducción 69
Descripción 69
UCS (software de conguración universal) 69
Uso del EM24 E1 70
Introducción 70
Display 70
Ajuste de los parámetros de la red 71
Ajuste de los parámetros de red a través de DHCP 71
Ajuste de los parámetros de red sin DHCP 71
Operaciones con el EM24 E1 72
Operaciones con el menú de medición/información 72
Operaciones con el menú de conguración 72
Reinicio del medidor de la energía parcial 72
Establecimiento de un parámetro 73
Descripción del menú 74
Menú de medición - páginas de medición 74
Menú de información 75
Ajustes desde EM24 E1 76
Ajustes generales 76
Información esencial 77
Aplicaciones 77
Páginas de programación 78
Gestión de tarifas a través de un comando Modbus 79
Inhabilitación de la gestión de tarifas 79
LED frontal 79
Selector frontal 79
Mantenimiento y eliminación 80
68 EM24 E1 - Manual de instrucciones | CARLO GAVAZZI Controls SpA
Información sobre propiedad
Copyright © 2018, CARLO GAVAZZI Controls SpA
Todos los derechos reservados en todos los países.
CARLO GAVAZZI Controls SpA se reserva el derecho a realizar modificaciones o mejoras en la documentación relativa sin
obligación de aviso previo.
Mensajes de seguridad
La siguiente sección describe las advertencias relacionadas con la seguridad de los usuarios y los dispositivos incluidos en este
documento:
ADVERTENCIA: indica obligaciones que si no se cumplen pueden provocar daños en el dispositivo.
¡CUIDADO! Indica una situación de riesgo que, si no se evita, puede provocar pérdidas de datos.
IMPORTANTE: proporciona información esencial sobre la conclusión de una tarea que no debe pasarse por alto.
Advertencias generales
Este manual forma parte integral del producto y debe acompañarlo a lo largo de toda su vida útil. Debe consultarse para
todo lo que tenga que ver con su configuración, uso y mantenimiento. Por este motivo, los operadores deben disponer de
acceso a él en todo momento.
ADVERTENCIA: nadie está autorizado a abrir el analizador. Esta operación está exclusivamente reservada para el
personal de servicio técnico de CARLO GAVAZZI.
El uso del instrumento de un modo no especificado por el fabricante podría afectar a la protección.
Reparación y garantía
Si se producen fallos o anomalías en el funcionamiento o quiere solicitar información, póngase en contacto con la filial o distribuidor
de CARLO GAVAZZI de su país.
Cualquier instalación o uso de los analizadores que no se ajuste a las instrucciones facilitadas invalidará la garantía.
Descargar
Este manual www.productselection.net/MANUALS/UK/EM24_im_use.pdf
Instrucciones de instalación - EM24 www.productselection.net/MANUALS/UK/EM24_im_inst.pdf
Software UCS www.productselection.net/Download/UK/ucs.zip
69EM24 E1 - Manual de instrucciones | CARLO GAVAZZI Controls SpA
EM24 E1
Introducción
El EM24 es un analizador de energía trifásico para instalación en carril DIN con configuración de palanca de mando, selector frontal y pantalla
LCD.
La versión para conexión directa (AV2) permite medir hasta 65 A, la versión para conexión CT (AV5) permite medir hasta 34875 A a través de
transformadores de corriente (salida secundaria 5 A).
La función DHCP permite acelerar la puesta en servicio y todos los parámetros de configuración se pueden establecer mediante UCS.
Descripción
AV2 AV5
Parte
Descripción
A Pantalla LCD
B Conexiones de tensión/intensidad
C Palanca de mando
D Selector con patilla para cierre MID (bloque de programación)
E Entradas/salidas o puerto de comunicación
F Patillas para cierre MID (cubiertas de protección incluidas)
UCS (software de conguración universal)
El software UCS de escritorio se encuentra disponible para su descarga de manera gratuita. Se puede conectar al EM24 a través de Ethernet
(Modbus TCP/IP) .
El UCS permite llevar a cabo estas acciones:
configurar el EM24 (en línea o sin conexión)
ver el estado del sistema con fines de diagnóstico y comprobación de la configuración descripción general de la función
70 EM24 E1 - Manual de instrucciones | CARLO GAVAZZI Controls SpA
Uso del EM24 E1
Introducción
El EM24 se organiza en dos menús:
menú de información y medición: páginas utilizadas para visualizar las páginas de medición, la información relevante para los parámetros
programados y la versión del firmware del instrumento
menú de ajustes: páginas utilizadas para configurar los parámetros
Display
La pantalla se divide en 3 líneas.
Símbolo
Descripción
Visualización de la tensión del sistema fase-a-neutro
Visualización de la tensión del sistema fase-a-fase
Visualización de los valores máx.
Id. del usuario
Visualización de las variables del sistema
Visualización de las variables dmd
EEEE
Desbordamiento.
Nota:
las funciones del cálculo DMD, el contador horario
y los medidores de energía se han inhibido y las salidas
de alarma se han activado. La indicación “EEEE” en
una variable monofásica implica automáticamente la
condición de desbordamiento de la variable del sistema
en cuestión y la indicación PF se fuerza a “0.000”.
71EM24 E1 - Manual de instrucciones | CARLO GAVAZZI Controls SpA
Ajuste de los parámetros de la red
Ajuste de los parámetros de red a través de DHCP
Paso Acción
1 Instale el EM24
2 Habilite la función DHCP y salga con End
3 Conecte el EM24 a la red LAN a la que esté conectado el PC
4 Acceda a las páginas Info para ver los parámetros de red asignados
5 Inicie el software UCS y conéctelo al EM24 a través de Manual connection> Modbus TCP
6 Introduzca la dirección IP que aparece en la página Info (véase el punto 4)
7
Acceda a los ajustes, inhabilite DHCP y asigne los parámetros de red necesarios (asignados por el administrador de la
red)
Ajuste de los parámetros de red sin DHCP
Paso Acción
1 Instale el EM24
2 Inhabilite DHCP (ajuste predeterminado)
3 Conecte el PC al EM24 a través del cable Ethernet (conexión de punto a punto)
4
Configure las propiedades de la red del PC de este modo:
Dirección IP estática
Dirección IP de la misma clase que el EM24; por ejemplo, si la IP del EM24 es 192.168.1.10 (predeterminada), puede
configurar la dirección del PC como 192.168.1.20
Máscara de subred: 255.255.255.0
Pasarela: no es necesaria
5
Inicie el software UCS y conecte con el EM24 a través de Manual connection> Modbus TCP; introduzca la dirección IP
del EM24 (192.168.1.10 por defecto)
6 Acceda a los ajustes e introduzca los parámetros de red necesarios
7 Desconecte el cable Ethernet y conecte el EM24 a la red a la que esté conectado el maestro Modbus
72
Uso del EM24 E1
EM24 E1 - Manual de instrucciones | CARLO GAVAZZI Controls SpA
Operaciones con el EM24 E1
Operaciones con el menú de medición/información
Operaciones con el menú de conguración
Reinicio del medidor de la energía parcial
Paso Acción Botón
1 Pulse el botón durante un mínimo de 3 segundos
2 En la página PASS, configure la contraseña 1357
3 Confirmar operación
4 En la página rESEt, configure YES
5 Confirmar operación
a la siguiente página de medición
a la página de medición anterior
al menú de ajustes
a la página de información
anterior
a la siguiente página de
información
incrementar un valor del parámetro
disminuir un valor del parámetro
editar/conrmar
a la página anterior
a la siguiente página
73
Uso del EM24 E1
EM24 E1 - Manual de instrucciones | CARLO GAVAZZI Controls SpA
Paso Acción Botón
6 En la página EnE PrES, configure YES
7 Confirmar operación
Establecimiento de un parámetro
Procedimiento de ejemplo: cómo configurar Ct rAtio=20 y guardar los cambios.
Paso Acción Botón
1 Encienda el analizador de energía
2 Pulse la palanca de mando durante un mínimo de 3 segundos
3 En la página PASS?, seleccione la contraseña correcta (valor predeterminado 0)
4 Confirmar operación
5 Recorra las páginas hasta llegar a Ct rAtio
6 Acceda al modo de edición
7 Seleccione 20
8 Confirmar operación
9 Recorra las páginas hasta llegar a End para salir
74
Uso del EM24 E1
EM24 E1 - Manual de instrucciones | CARLO GAVAZZI Controls SpA
Descripción del menú
Menú de medición - páginas de medición
Las páginas mostradas dependerán del conjunto de la aplicación.
Page Mediciones mostradas Descripción
1
L1-L2-L3
V
LNΣ
Hz
Secuencia de fase
Tensión fase-neutro del sistema
Frecuencia
2
L1-L2-L3
V
LLΣ
Hz
Secuencia de fase
Tensión fase-fase del sistema
Frecuencia
3
Tot kWh (+)
W
Σ
dmd
W
Σ
dmd max
Energía activa consumida total
Potencia activa del sistema dmd
Potencia activa del sistema dmd máx.
4
kWh
A dmd max
PArt
Energía activa
Intensidad dmd máx.
Energía activa parcial
5
Tot kvarh (+)
VA
Σ
dmd
VA
Σ
dmd max
Energía reactiva consumida total
Potencia aparente del sistema dmd
Potencia aparente del sistema dmd máx.
6
kvarh
VA
Σ
PArt
Energía reactiva
Potencia aparente del sistema
Energía reactiva parcial
7
kWh (+)
t1
W
Σ
dmd
Energía activa consumida, tarifa 1
Potencia activa del sistema dmd
8
kWh (+)
t2
W
Σ
dmd
Energía activa consumida, tarifa 2
Potencia activa del sistema dmd
9
kWh (+)
t3
W
Σ
dmd
Energía activa consumida, tarifa 3
Potencia activa del sistema dmd
10
kWh (+)
t4
W
Σ
dmd
Energía activa consumida, tarifa 4
Potencia activa del sistema dmd
11
kvarh (+)
t1
W
Σ
dmd
Energía reactiva consumida, tarifa 1
W
Σ
dmd
12
kvarh (+)
t2
W
Σ
dmd
Energía reactiva consumida, tarifa 2
W
Σ
dmd
13
kvarh (+)
t3
W
Σ
dmd
Energía reactiva consumida, tarifa 3
W
Σ
dmd
14
kvarh (+)
t4
W
Σ
dmd
Energía reactiva consumida, tarifa 4
W
Σ
dmd
15
kWh (+) X
W X
User X
Energía activa consumida
Potencia activa
Usuario
16
kWh (+) Y
W Y
User Y
Energía activa consumida
Potencia activa
Usuario
17
kWh (+) Z
W Z
User Z
Energía activa consumida
Potencia activa
Usuario
18
Total kvarh (-)
VA
Σ
dmd
VA
Σ
dmd max
Energía reactiva generada total
Potencia aparente del sistema dmd
Potencia aparente del sistema dmd máx.
19
Total kWh (-)
W
Σ
dmd
W
Σ
dmd max
Energía activa generada total
Potencia activa del sistema dmd
Potencia activa del sistema dmd máx.
75
Conguración del sistema
EM24 E1 - Manual de instrucciones | CARLO GAVAZZI Controls SpA
20
Hours
W
Σ
PF
Σ
Horas del funcionamiento de la carga totales
Potencia activa del sistema
Factor de potencia del sistema
21
Hours
VAr
Σ
PF
Σ
Horas del funcionamiento de la carga totales
Potencia reactiva del sistema
Factor de potencia del sistema
22
var L1
var L2
var L3
Potencia reactiva fase 1
Potencia reactiva fase 2
Potencia reactiva fase 3
23
VA L1
VA L2
VA L3
Potencia aparente fase 1
Potencia aparente fase 2
Potencia aparente fase 3
24
PF L1
PF L2
PF L3
Factor de potencia fase 1
Factor de potencia fase 2
Factor de potencia fase 3
25
W L1
W L2
W L3
Potencia activa fase 1
Potencia activa fase 2
Potencia activa fase 3
26
A L1
A L2
A L3
Intensidad fase 1
Intensidad fase 2
Intensidad fase 3
27
V L1-2
V L2-3
V L3-1
Tensión fase 1-fase 2
Tensión fase 2-fase 3
Tensión fase 3-fase 1
28
V L1
V L2
V L3
Tensión de fase 1
Tensión de fase 2
Tensión de fase 3
Nota: en el modo de programación, se guarda la última página mostrada.
Menú de información
Page Título de la página Información mostrada
1 IP o.o.-.- Dirección IP (primera parte)
2 IP -.-.o.o Dirección IP (segunda parte)
3 Sub o.o.-.- Máscara de subred (primera parte)
4 Sub -.-.o.o Máscara de subred (segunda parte)
5 Gateo.o.-.- Pasarela predeterminada (primera parte)
6 Gate-.-.o.o Pasarela predeterminada (segunda parte)
7 Port Puerto modbus TCP
8 DHCP Habilitación de DHCP
9 Info Diagnóstico Ethernet
10 Ut ratio Relación transformador de tensión/potencia
11 CT ratio Ratio CT
12
1P/2P/3P/3Pn
(2-3-4-wire)
dmd (time)
Sistema
Conexión (2, 3, 4 alambres)
Tiempo de integración dmd (min)
13 Pulse Proporción de pulsos LED (número de kWh/kvarh por pulso)
14 Year
Versión del firmware
Año de producción
76
Conguración del sistema
EM24 E1 - Manual de instrucciones | CARLO GAVAZZI Controls SpA
Ajustes desde EM24 E1
Ajustes generales
Los ajustes disponibles dependerán del conjunto de la aplicación.
Título de la
página
Submenú Descripción Valores Valor por
defecto
Cng PASS - Cambie la contraseña Desde 0 hasta 9999 0
APPLiCAt Aplicación tYP.A
tYP.b
tYP.C
tYP.d
tYP.E
tYP.F
tYP.G
tYP.H
tYP.H
User USEr 1 Usuario Desde 0 hasta 9999 1
USEr 2 Desde 0 hasta 9999 2
USEr 3 Desde 0 hasta 9999 3
dHCP - Habilitación de DHCP oFF/on oFF
IP Addr IP o.-.-.- Dirección IP Desde 000 hasta 255 192
IP -.o.-.- Desde 000 hasta 255 168
IP -.-.o.- Desde 000 hasta 255 1
IP -.-.-.o Desde 000 hasta 255 10
SUb SUb o.-.-.- Máscara de subred Desde 000 hasta 255 255
SUb -.o.-.- Desde 000 hasta 255 255
SUb -.-.o.- Desde 000 hasta 255 255
SUb -.-.-.o Desde 000 hasta 255 0
GAtE GAtE o.-.-.- Puerta de enlace predeterminada Desde 000 hasta 255 192
GAtE -.o.-.- Desde 000 hasta 255 168
GAtE -.-.o.- Desde 000 hasta 255 1
GAtE -.-.-.o Desde 000 hasta 255 1
Port - Puerto MODBUS TCP 502
SELECtor SELEC. 1 Página mostrada en función de la
posición del selector entre las páginas
disponibles para cada aplicación (véase
“Selector frontal” en página 79)
Desde 1 hasta 28 1
SELEC. 2 Desde 1 hasta 28 25
SELEC. 3 Desde 1 hasta 28 28
SELEC.LoC Desde 1 hasta 28 3
SYS - Sistema 3P.n
3P.1
2P
1P
3P
Nota: MID (PFA, PFB): solamente 3P.n
3P.n
Ut rAtio - Relación del transformador de tensión
(VT)
AV5: entre 1 y 6975
AV2: N/D
1
Ct rAtio - Relación del transformador de intensidad
(CT)
AV5: entre 1 y 6975
AV2: N/D
1
P int.ti - Tiempo de integración dmd (min) Desde 1 hasta 30 15
FiLtEr.S - Intervalo de la intervención del ltro con
respecto
a la escala completa (%)
Desde 0 hasta 100 2
FiLtEr.Co - Coeciente del ltro Desde 1 hasta 32 2
End - Salir y guardar - -
Nota: la página Ut rAtio se encuentra disponible con fines de compatibilidad con otras versiones, a pesar de que la versión AV5 no se ha ideado para su uso con
transformadores de tensión. Por lo tanto, debe configurarse como 1.
77
Información esencial
EM24 E1 - Manual de instrucciones | CARLO GAVAZZI Controls SpA
Información esencial
Gestión de la medición
Aplicaciones
Nota: cuando se selecciona una aplicación con conexión fácil, para el cálculo de la energía activa siempre se integra la potencia, tanto consumida como
generada. La dirección de la intensidad no afecta a la medición. Cuando se selecciona una aplicación sin conexión fácil, se encuentra disponible la activa tanto
generada como consumida.
Aplicación Mediciones Conexión fácil
A
Sistema:
secuencia de fase
tensión fase-neutro
frecuencia
energía activa consumida total
potencia activa dmd y dmd máx.
B
Sistema:
secuencia de fase
tensión fase-neutro
frecuencia
energía activa consumida total
potencia activa dmd y dmd máx.
energía reactiva consumida total
potencia aparente dmd y dmd máx.
C
Sistema:
secuencia de fase
tensión fase-neutro
frecuencia
energía activa consumida total
potencia activa dmd y dmd máx.
energía reactiva y activa consumida por tarifa
D
monofase
energía activa consumida
tensión
E
Sistema:
secuencia de fase
tensión fase-neutro
frecuencia
energía activa generada y consumida total
potencia activa dmd y dmd máx.
contador de horas
potencia activa
factor de potencia
NA
F
Sistema:
secuencia de fase
tensión fase-neutro
frecuencia
energía activa generada y consumida total
potencia activa dmd y dmd máx.
tensión fase-fase
energía activa
Intensidad dmd máx.
Energía activa parcial
energía reactiva generada y consumida total
potencia aparente, dmd y dmd máx.
Energía reactiva parcial
contador de horas
potencia activa
factor de potencia
NA
78
Información esencial
EM24 E1 - Manual de instrucciones | CARLO GAVAZZI Controls SpA
G
Sistema:
secuencia de fase
tensión fase-neutro
frecuencia
energía activa consumida total
potencia activa dmd y dmd máx.
tensión fase-fase
energía activa
Intensidad dmd máx.
Energía activa parcial
energía reactiva consumida total
potencia aparente, dmd y dmd máx.
energía reactiva
contador de horas
potencia activa
potencia activa dmd
potencia reactiva
factor de potencia
energía reactiva y activa consumida por tarifa
monofase
potencia reactiva por fase
potencia aparente por fase
factor de potencia por fase
potencia activa por fase
intensidad por fase
tensiones línea-línea
tensiones línea-neutro
H
Sistema:
secuencia de fase
tensión fase-neutro
frecuencia
energía activa generada y consumida total
potencia activa dmd y dmd máx.
tensión fase-fase
energía activa
Intensidad dmd máx.
Energía activa parcial
energía reactiva generada y consumida total
potencia aparente, dmd y dmd máx.
energía reactiva
contador de horas
potencia activa
potencia activa dmd
potencia reactiva
factor de potencia
energía reactiva y activa consumida por tarifa
monofase
potencia reactiva por fase
potencia aparente por fase
factor de potencia por fase
potencia activa por fase
intensidad por fase
tensiones línea-línea
tensiones línea-neutro
NA
Páginas de programación
La tabla a continuación muestra las páginas de programación disponibles para cada aplicación
Page Aplicación
A B C D E F G H
Cambie la contraseña x x x x x x x x
Aplicación x x x x x x x x
Usuario - - - x - - - -
Habilitación de DHCP x x x x x x x x
Dirección IP x x x x x x x x
Máscara de subred x x x x x x x x
Puerta de enlace predeterminada x x x x x x x x
Puerto MODBUS TCP x x x x x x x x
79
Información esencial
EM24 E1 - Manual de instrucciones | CARLO GAVAZZI Controls SpA
Selector x x x x x x x x
Sistema x x x x x x x
Relación del transformador de tensión x x x x x x x x
Ratio CT x x x x x x x x
Tiempo de integración de la potencia media x x x - x x x x
Filter S - - - - - x x x
Filter Co - - - - - x x x
End x x x x x x x x
Gestión de tarifas
Gestión de tarifas a través de un comando Modbus
Modifique la tarifa introduciendo el valor correspondiente en la tarifa actual en función de esta tabla en el registro 1201Fh:
Tarifa
actual
Valor del
registro
T1 1
T2 2
T3 3
T4 4
Inhabilitación de la gestión de tarifas
Configure la gestión de tarifas como inhabilitada o introduzca 0 (valor predeterminado) en el registro 1201Fh.
LED frontal y selector
LED frontal
El LED frontal rojo parpadea de manera proporcional al consumo de energía consumida activa cuando el selector está en la posición - 1 - 2 y al consumo
de energía inductiva reactiva en la posición kvarh . El LED frontal no gestionará ningún tipo de energía (generada) negativa.
Selector frontal
Posición Lock : el selector frontal impide el acceso al modo de programación
Posición 1, 2, kvarh : acceso rápido a las páginas de medición. Cada posición está asociada a una página de medición según esta tabla:
Aplicación Posición del selector Página disponible
A
Lock
3
1,2,3 1
B, C, E, F, G, H
Lock, 1, 2, kvarh
Se puede configurar con un valor entre 1 y 28
C
Lock, 1, 2, kvarh
Se puede configurar con un valor entre 1 y 28
D
Lock 28
1 15
2 16
3 17
80
Mantenimiento y eliminación
EM24 E1 - Manual de instrucciones | CARLO GAVAZZI Controls SpA
Mantenimiento y eliminación
Limpieza
Utilice un paño ligeramente humedecido para limpiar la pantalla. No utilice abrasivos ni disolventes.
Responsabilidad de la eliminación
El producto debe desecharse en los centros de reciclaje correspondientes especificados por el gobierno o las autoridades públicas
locales. Una eliminación adecuada y su reciclaje contribuirán a prevenir consecuencias potencialmente dañinas para el medioambiente
y las personas.
EM24 E1 - Instrucciones de uso
2018-06 | Copyright © 2018
CARLO GAVAZZI Controls SpA
via Safforze, 8
32100 Belluno (BL) Italia
www.gavazziautomation.com
info: +39 0437 355811
fax: +39 0437 355880
EM24 E1
Trefaset energianalyseapparat
BRUGERMANUAL
83EM24 E1 - Brugervejledning | CARLO GAVAZZI Controls SpA
Indhold
EM24 E1 85
Introduktion 85
Beskrivelse 85
UCS (Universel kongurationssoftware) 85
Brug af EM24 E1 86
Introduktion 86
Display 86
Indstilling af netværksparametre 87
Indstilling af netværksparametre via DHCP 87
Indstilling af netværksparametre uden DHCP 87
Arbejde med EM24 E1 88
Arbejde med aæsnings-/infomenuen 88
Arbejde med indstillingsmenuen 88
Nulstilling af partial energimåler 88
Indstilling af en parameter 89
Menubeskrivelse 90
Aæsningsmenuen - aæsningssider 90
Informationsmenu 91
Indstillinger fra EM24 E1 92
Generelle indstillinger 92
Vigtig information 93
Anvendelsesområder 93
Programmeringssider 94
Tarifstyring via Modbus-kommandoer 95
Deaktivering af tarifstyring 95
Forreste LED 95
Frontvælger 95
Vedligeholdelse og bortskaffelse 96
84 EM24 E1 - Brugervejledning | CARLO GAVAZZI Controls SpA
Informationsret
Copyright © 2018, CARLO GAVAZZI Controls SpA
Alle rettigheder er forbeholdt i alle lande.
CARLO GAVAZZI Controls SpA forbeholder sig ret til at udføre ændringer eller forbedringer i den tilhørende dokumentation uden
forudgående meddelelse herom.
Meddelelser vedr. sikkerhed
Det følgende afsnit beskriver advarsler, som har relation til sikkerhedsforhold for brugeren og apparaturet:
ADVARSEL: angiver påbud, som, hvis de ikke overholdes, kan medføre skader på apparaturet.
PAS PÅ! Angiver en risikobetonet situation, som, hvis den ikke undgås, kan medføre tab af data.
VIGTIGT: indeholder vigtig information, som ikke må tilsidesættes vedr. en opgaves udførelse.
Generelle advarsler
Denne vejledning er en integreret del af produktet og skal være i nærheden i hele produktets levetid. Den skal altid
konsulteres i alle situationer, som drejer sig om konfiguration, brug og vedligeholdelse. Af denne grund skal den altid være
tilgængelig for brugerne.
NOTICE: Ingen er autoriseret til åbning af analysatoren. Denne handling må kun udføres af det tekniske personale hos
CARLO GAVAZZI
Beskyttelsen kan blive forringet, hvis instrumentet bruges på anden vis end det, der er angivet af fabrikanten.
Service og garanti
Hvis der opstår fejlfunktioner og defekter eller anmodninger om oplysninger, bedes du kontakte den lokale CARLO GAVAZZI-
forhandler eller afdeling.
Installation og brug af analyseapparater udover dem, der er beskrevet i de medfølgende instruktioner medfører bortfald af
garantien.
Download
Denne manual www.productselection.net/MANUALS/UK/EM24_im_use.pdf
Installationsvejledning - EM24 www.productselection.net/MANUALS/UK/EM24_im_inst.pdf
UCS-software www.productselection.net/Download/UK/ucs.zip
85EM24 E1 - Brugervejledning | CARLO GAVAZZI Controls SpA
EM24 E1
Introduktion
EM24 er en trefaset energianalysator til DIN-skinnemontering med konfigurationsjoystick, frontvælger og LCD-display.
Versionen med direkte tilslutning (AV2) gør det muligt at måle op til 65 A, mens versionen med CT-forbindelse (AV5) gør det muligt at måle op
til 34875 A ved hjælp af strømtransformere (5 A sekundær udgang).
Med DHCP-funktionen bliver ibrugtagningen hurtigere, og alle konfigurationsparametre kan opsættes via UCS.
Beskrivelse
AV2 AV5
Del
Beskrivelse
A LCD-display
B Spænding-/strømtilslutninger
C Joystick
D Vælger med pinkode for MID-forsegling (programmeringsblok)
E Ind- og udgange eller kommunikationsport
F Stifter til MID-forsegling (beskyttelsescovers medfølger)
UCS (Universel kongurationssoftware)
UCS-desktop er tilgængelig til gratis download. Den kan tilsluttes EM24 via Ethernet (Modbus TCP/IP) .
Følgende er muligt med UCS:
konfigurere EM24 (online eller offline)
vise systemstatus for diagnostik og konfigurationstjek funktionsoversigt
86 EM24 E1 - Brugervejledning | CARLO GAVAZZI Controls SpA
Brug af EM24 E1
Introduktion
EM24 er opbygget med to menuer:
Aflæsnings- og informationsmenusider: bruges tl at vise aflæsningssiderne, information er relevant for de programmerede parametre og
instrumentets firmwareudgivelse
indstillingsmenu: Sider, der anvendes for at indstille parametre
Display
Displayet er opdelt i tre linjer:
Symbol Beskrivelse
Visning af fase-til-neutral-systemspænding
Visning af fase-til-fase-systemspænding
Visning af maks. værdier
Bruger-id
Visning af systemvariable
Visning af dmd-systemvariable
EEEE
Overløb.
Bemærk:
Funktionerne for DMD-beregningen, time-
tælleren og energimålerne undertrykkes, og alarmud-
gangene aktiveres. Angivelsen “EEEE” i en enkelt
fase-variabel medfører automatisk overløbstilstanden i
den relevante systemvariabel, og PF-angivelsen tvinges
til “0,000”.
87EM24 E1 - Brugervejledning | CARLO GAVAZZI Controls SpA
Indstilling af netværksparametre
Indstilling af netværksparametre via DHCP
Trin Handling
1 Installér EM24
2 Aktivér DHCP, og afslut med End
3 Forbind EM24 til LAN-netværket, som PC'en er tilsluttet
4 Gå til Info siderne for at få vist de tildelte netværksparametre
5 Start UCS-softwaren, og tilslut til EM24 via Manuel tilslutning > Modbus TCP
6 Indtast den IP-adresse, der vises på Info-siden (se pkt. 4)
7 Gå til indstillingerne, deaktiver DHCP, og tildel de krævede netværksparametre (tildelt af netværksadministrator)
Indstilling af netværksparametre uden DHCP
Trin Handling
1 Installér EM24
2 Deaktiver DHCP (standardindstilling)
3 Tilslut PC'en til EM24 via Ethernet-kabel (punkt-til-punkt tilslutning)
4
Indstil netværksegenskaberne for PC som følger:
statisk IP-adresse
IP-adressen samme klasse som EM24, f.eks. hvis IP for EM24 er 192.168.1.10 (standard), kan du indstille PC-adressen
til 192.168.1.20
Undernetmaske: 255.255.255.0
Gateway: Ikke nødvendig
5
Start UCS-softwaren, og tilslut til EM24 via Manuel tilslutning > Modbus TC, indtast IP-adressen for EM24 (192.168.1.10
som standard)
6 Gå til indstillingerne, og indtast de krævede netværksparametre
7 Tag Ethernet-kablet ud, og tilslut EM24 til netværket, som Modbus master er tilsluttet
88
Brug af EM24 E1
EM24 E1 - Brugervejledning | CARLO GAVAZZI Controls SpA
Arbejde med EM24 E1
Arbejde med aæsnings-/infomenuen
Arbejde med indstillingsmenuen
Nulstilling af partial energimåler
Trin Handling Knap
1 Tryk på knappen i mindst 3 sekunder
2 På siden PASS indstilles adgangskoden 1357
3 Bekræft handling
4 På siden rESEt indstilles YES
5 Bekræft handling
l næste aæsningsside
l forrige aæsningsside
l indsllingsmenu
l forrige infoside l næste infoside
forøg parameterværdien
formindsk parameterværdien
rediger/bekræ
l forrige side l næste side
89
Brug af EM24 E1
EM24 E1 - Brugervejledning | CARLO GAVAZZI Controls SpA
Trin Handling Knap
6 På siden EnE PrES indstilles YES
7 Bekræft handling
Indstilling af en parameter
Eksempelprocedure: indstilling af Ct rAtio=20 hvor ændringer skal gemmes.
Trin Handling Knap
1 Tænd energianalysatoren
2 Tryk på joysticket i mindst 3 sekunder
3 På siden PASS? vælges den korrekte adgangskode (standard 0)
4 Bekræft handling
5 Rul igennem siderne til Ct rAtio
6 Aktivér redigeringstilstand
7 Vælg 20
8 Bekræft handling
9 Rul igennem siderne indtil End for at afslutte
90
Brug af EM24 E1
EM24 E1 - Brugervejledning | CARLO GAVAZZI Controls SpA
Menubeskrivelse
Aæsningsmenuen - aæsningssider
De viste sider afhænger af den valgte applikation.
Side Viste målinger Beskrivelse
1
L1-L2-L3
V
LNΣ
Hz
Fasesekvens
System, faseneutral spænding
Frekvens
2
L1-L2-L3
V
LLΣ
Hz
Fasesekvens
System, fase-fase spænding
Frekvens
3
Tot kWh (+)
W
Σ
dmd
W
Σ
dmd max
Totale importerede aktive energi
Aktiv dmd systemeffekt
Aktiv maks. dmd systemeffekt
4
kWh
A dmd max
PArt
Aktiv energi
Maks. dmd strøm
Partial aktiv energi
5
Tot kvarh (+)
VA
Σ
dmd
VA
Σ
dmd max
Totale importerede reaktiv energi
Tilsyneladende dmd systemeffekt
Tilsyneladende maks. dmd systemeffekt
6
kvarh
VA
Σ
PArt
Reaktiv energi
Tilsyneladende systemeffekt
Partial reaktiv energi
7
kWh (+)
t1
W
Σ
dmd
Importeret aktiv energi, tarif 1
Aktiv dmd systemeekt
8
kWh (+)
t2
W
Σ
dmd
Importeret aktiv energi, tarif 2
Aktiv dmd systemeekt
9
kWh (+)
t3
W
Σ
dmd
Importeret aktiv energi, tarif 3
Aktiv dmd systemeekt
10
kWh (+)
t4
W
Σ
dmd
Importeret aktiv energi, tarif 4
Aktiv dmd systemeekt
11
kvarh (+)
t1
W
Σ
dmd
Importeret reaktiv energi, tarif 1
W
Σ
dmd
12
kvarh (+)
t2
W
Σ
dmd
Importeret reaktiv energi, tarif 2
W
Σ
dmd
13
kvarh (+)
t3
W
Σ
dmd
Importeret reaktiv energi, tarif 3
W
Σ
dmd
14
kvarh (+)
t4
W
Σ
dmd
Importeret reaktiv energi, tarif 4
W
Σ
dmd
15
kWh (+) X
W X
User X
Importeret aktiv energi
Aktiv effekt
Bruger
16
kWh (+) Y
W Y
User Y
Importeret aktiv energi
Aktiv effekt
Bruger
17
kWh (+) Z
W Z
User Z
Importeret aktiv energi
Aktiv effekt
Bruger
18
Total kvarh (-)
VA
Σ
dmd
VA
Σ
dmd max
Totale eksporteret reaktiv energi
Tilsyneladende dmd systemeffekt
Tilsyneladende maks. dmd systemeffekt
19
Total kWh (-)
W
Σ
dmd
W
Σ
dmd max
Totale eksporteret aktiv energi
Aktiv dmd systemeekt
Aktiv maks. dmd systemeekt
91
Kongurering af systemet
EM24 E1 - Brugervejledning | CARLO GAVAZZI Controls SpA
20
Hours
W
Σ
PF
Σ
Samlede antal driftstimer med belastning
Aktiv systemeekt
Systemeffektfaktor
21
Hours
VAr
Σ
PF
Σ
Samlede antal driftstimer med belastning
Reaktiv systemeffekt
Systemeffektfaktor
22
var L1
var L2
var L3
Reaktiv effekt, fase 1
Reaktiv effekt, fase 2
Reaktiv effekt, fase 3
23
VA L1
VA L2
VA L3
Tilsyneladende effekt, fase 1
Tilsyneladende effekt, fase 2
Tilsyneladende effekt, fase 3
24
PF L1
PF L2
PF L3
Effektfaktor, fase 1
Effektfaktor, fase 2
Effektfaktor, fase 3
25
W L1
W L2
W L3
Aktiv effekt, fase 1
Aktiv effekt, fase 2
Aktiv effekt, fase 3
26
A L1
A L2
A L3
Fase 1 strøm
Fase 2 strøm
Fase 3 strøm
27
V L1-2
V L2-3
V L3-1
Fase 1-fase 2 spænding
Fase 2-fase 3 spænding
Fase 3-fase 1 spænding
28
V L1
V L2
V L3
Fase 1 spænding
Fase 2 spænding
Fase 3 spænding
Bemærk: I programmeringstilstand lagres er den sidste side, der vises.
Informationsmenu
Side Sidenavn Vist information
1 IP o.o.-.- IP-adresse (første del)
2 IP -.-.o.o IP-adresse (anden del)
3 Sub o.o.-.- Undernetmaske (første del)
4 Sub -.-.o.o Undernetmaske (anden del)
5 Gateo.o.-.- Standardgateway (første del)
6 Gate-.-.o.o Standardgateway (anden del)
7 Port Modbus TCP-port
8 DHCP Aktivering af DHCP
9 Info Ethernet-diagnostik
10 Ut ratio VT/PT-koefficient
11 CT ratio CT-koefficient
12
1P/2P/3P/3Pn
(2-3-4-wire)
dmd (time)
System
Tilslutning (2-3-4 ledere)
Dmd-integrationstid (min.)
13 Pulse LED-impulsvægt (Antal kWh/kvarh pr. impuls)
14 Year
Firmware-udgivelse
Produktionsår
92
Kongurering af systemet
EM24 E1 - Brugervejledning | CARLO GAVAZZI Controls SpA
Indstillinger fra EM24 E1
Generelle indstillinger
De tilgængelige indstillinger afhænger af
Sidenavn Underme-
nu
Beskrivelse Værdier Standardværdi
Cng PASS - Skift adgangskode Fra 0 til 9.999 0
APPLiCAt Applikation tYP.A
tYP.b
tYP.C
tYP.d
tYP.E
tYP.F
tYP.G
tYP.H
tYP.H
User USEr 1 Bruger Fra 0 til 9.999 1
USEr 2 Fra 0 til 9.999 2
USEr 3 Fra 0 til 9.999 3
dHCP - Aktivering af DHCP oFF/on oFF
IP Addr IP o.-.-.- IP-adresse Fra 000 til 255 192
IP -.o.-.- Fra 000 til 255 168
IP -.-.o.- Fra 000 til 255 1
IP -.-.-.o Fra 000 til 255 10
SUb SUb o.-.-.- Subnetmaske Fra 000 til 255 255
SUb -.o.-.- Fra 000 til 255 255
SUb -.-.o.- Fra 000 til 255 255
SUb -.-.-.o Fra 000 til 255 0
GAtE GAtE o.-.-.- Standardgateway Fra 000 til 255 192
GAtE -.o.-.- Fra 000 til 255 168
GAtE -.-.o.- Fra 000 til 255 1
GAtE -.-.-.o Fra 000 til 255 1
Port - MODBUS TCP-port 502
SELECtor SELEC. 1 Siden vises i henhold til vælgerposition
blandt de tilgængelige side for hver ap-
plikation (se ”Frontvælger” på side 95)
Fra 1 til 28 1
SELEC. 2 Fra 1 til 28 25
SELEC. 3 Fra 1 til 28 28
SELEC.LoC Fra 1 til 28 3
SYS - System 3P.n
3P.1
2P
1P
3P
Bemærk: MID (PFA, PFB): kun 3P.n
3P.n
Ut rAtio - Transformerkoefcient for spænding (VT) AV5: fra 1 til 6975
AV2: N/A
1
Ct rAtio - Strømtransformerkoefcient (Ct) AV5: fra 1 til 6975
AV2: N/A
1
P int.ti - Dmd-integrationstid (min.) Fra 1 til 30 15
FiLtEr.S - Interval af lterindgreb i forhold
til fuld skala (%)
Fra 0 til 100 2
FiLtEr.Co - Filterkoefcient Fra 1 til 32 2
End - Afslut og gem - -
Bemærk: Ut-koefficientværdien er tilgængelig for kompatibilitet med andre versioner, selv om AV5 versionen ikke skal bruges sammen med
spændingstransformere. Den skal derfor indstilles på 1
93
Vigtig information
EM24 E1 - Brugervejledning | CARLO GAVAZZI Controls SpA
Vigtig information
Administration af aflæsninger
Anvendelsesområder
Bemærk: Hvis en applikation med nem tilslutning vælges, er effekten altid integreret i beregningen af den aktive energi, både ved importeret og eksporteret
effekt. Strømretningen påvirker ikke aflæsningen. Hvis en applikation uden nem tilslutning vælges, er både den aktive importerede og eksporterede effekt
tilgængelig.
Applikation Målinger Nem tilslutning
A
System:
fasesekvens
fase-neutral, spænding
frekvens
totale importerede aktive energi
aktiv dmd effekt og maks. dmd
JA
B
System:
fasesekvens
fase-neutral, spænding
frekvens
totale importerede aktive energi
aktiv dmd effekt og maks. dmd
totale importerede reaktiv energi
tilsyneladende dmd effekt og maks. dmd
JA
C
System:
fasesekvens
fase-neutral, spænding
frekvens
totale importerede aktive energi
aktiv dmd effekt og maks. dmd
importeret aktiv og reaktiv energi efter tarif
JA
D
Enkeltfase:
importeret aktiv energi.
spænding
JA
E
System:
fasesekvens
fase-neutral, spænding
frekvens
total importeret og eksporteret aktiv energi
aktiv dmd effekt og maks. dmd
driftstimetæller
aktiv effekt
effektfaktor
NO
F
System:
fasesekvens
fase-neutral, spænding
frekvens
total importeret og eksporteret aktive energi
aktiv dmd effekt og maks. dmd
fase-fase, spænding
aktiv energi
maks. dmd strøm
partial aktiv energi
total importeret og eksporteret reaktiv energi
tilsyneladende effekt, dmd og maks. dmd
partial reaktiv energi
driftstimetæller
aktiv effekt
effektfaktor
NO
94
Vigtig information
EM24 E1 - Brugervejledning | CARLO GAVAZZI Controls SpA
G
System:
fasesekvens
fase-neutral, spænding
frekvens
totale importerede aktive energi
aktiv dmd effekt og maks. dmd
fase-fase, spænding
aktiv energi
maks. dmd strøm
partial aktiv energi
totale importerede reaktiv energi
tilsyneladende effekt, dmd og maks. dmd
reaktiv energi
driftstimetæller
aktiv effekt
aktiv dmd effekt
reaktiv effekt
effektfaktor
importeret aktiv og reaktiv energi efter tarif
Enkeltfase:
reaktiv effekt pr. fase
tilsyneladende effekt pr. fase
effektfaktor pr. fase
aktiv effekt pr. fase
strøm pr. fase
linje-linje spændinger
linj-neutral spændinger
JA
H
System:
fasesekvens
fase-neutral, spænding
frekvens
total importeret og eksporteret aktiv energi
aktiv dmd effekt og maks. dmd
fase-fase, spænding
aktiv energi
maks. dmd strøm
partial aktiv energi
total importeret og eksporteret reaktiv energi
tilsyneladende effekt, dmd og maks. dmd
reaktiv energi
driftstimetæller
aktiv effekt
aktiv dmd effekt
reaktiv effekt
effektfaktor
importeret aktiv og reaktiv energi efter tarif
Enkeltfase:
reaktiv effekt pr. fase
tilsyneladende effekt pr. fase
effektfaktor pr. fase
aktiv effekt pr. fase
strøm pr. fase
linje-linje spændinger
linj-neutral spændinger
NO
Programmeringssider
Følgende tabel viser, hvilke programmeringssider der er til rådighed for hver applikation
Side Applikation
A B C D E F G H
Skift adgangskode x x x x x x x x
Applikation x x x x x x x x
Bruger - - - x - - - -
Aktivering af DHCP x x x x x x x x
IP-adresse x x x x x x x x
Subnetmaske x x x x x x x x
Standardgateway x x x x x x x x
MODBUS TCP-port x x x x x x x x
95
Vigtig information
EM24 E1 - Brugervejledning | CARLO GAVAZZI Controls SpA
Vælger x x x x x x x x
System x x x x x x x
VT-koecient x x x x x x x x
CT-koecient x x x x x x x x
Gns. eektintegrationstid x x x - x x x x
Filter S - - - - - x x x
Filter Co - - - - - x x x
End x x x x x x x x
Tarifstyring
Tarifstyring via Modbus-kommandoer
Skift tariffen ved at ændre værdien svarende til den aktuelle tarif i henhold til flg. tabel i 1201Fh registret:
Gældende
tarif
Register-
værdi
T1 1
T2 2
T3 3
T4 4
Deaktivering af tarifstyring
Sæt tarifstyringen til deaktiveret, eller angiv 0 (standardværdi) i 1201Fh registret.
Forreste LED og vælger
Forreste LED
Den forreste, røde LED blinker proportionalt med det aktive, importerede energiforbrug, hvis vælgeren er i positionen - 1 - 2 og med det reaktive, induk-
tive energiforbrug i
positionen kvarh. Al slags negativ (eksporteret) energi vil ikke blive styret af den forreste LED.
Frontvælger
Lock position: Frontvælgeren forhindrer, at der kan fås adgang til programmeringstilstanden
1, 2, kvarh position: Giver hurtig adgang til aflæsningssiderne. Hver position er tilknyttet én aflæsningsside i henhold til følgende tabel:
Applikation Vælgerposition Side til rådighed
A
Lås
3
1,2,3 1
B, C, E, F, G, H
Lås, 1, 2, kvarh
Kan indstilles fra 1 til 28
C
Lås, 1, 2, kvarh
Kan indstilles fra 1 til 28
D
Lås 28
1 15
2 16
3 17
96
Vedligeholdelse og bortskaelse
EM24 E1 - Brugervejledning | CARLO GAVAZZI Controls SpA
Vedligeholdelse og bortskaffelse
Rengøring
Brug en let fugtet klud til at rengøre displayet Brug ikke slibende midler eller opløsningsmidler
Ansvar for bortskaffelse
Produktet skal bortskaffes en lokal, godkendt genbrugsstation. Korrekt bortskaffelse og genbrug vil bidrage til at mindske eventuelle
skadelige konsekvenser for miljøet, mennesker og dyr.
EM24 E1 - Brugermanual
2018-06 | Copyright © 2018
CARLO GAVAZZI Controls SpA
via Safforze, 8
32100 Belluno (BL) Italien
www.gavazziautomation.com
info: +39 0437 355811
fax: +39 0437 355880

Transcripción de documentos

EN IT DE FR ES DA EM24 E1 USER MANUAL MANUALE UTENTE BETRIEBSANLEITUNG MANUEL D’EMPLOI INSTRUCCIONES DE USO BRUGERMANUAL EM24 E1 Three-phase energy analyzer USER MANUAL Contents EM24 E1 4 Introduction4 Description4 UCS (Universal Configuration Software) 4 EM24 E1 use 5 Introduction5 Display5 Network parameters setting 6 Setting network parameters via DHCP 6 Setting network parameters without DHCP 6 Working with EM24 E1 7 Working with the measurement/info menu 7 Working with the settings menu 7 Resetting partial energy meter 7 Setting a parameter 8 Menu description 9 Measurement menu - measurement pages 9 Information Menu 10 Settings from EM24 E1 11 General settings 11 Essential information 12 Applications 12 Programming pages 13 Managing tariffs via Modbus command 14 Disabling tariff management 14 Frontal LED 14 Frontal selector 14 Maintenance and disposal 15 EM24 E1 - Instruction manual | CARLO GAVAZZI Controls SpA 3 Information property Copyright © 2018, CARLO GAVAZZI Controls SpA All rights reserved in all countries. CARLO GAVAZZI Controls SpA reserves the right to apply modifications or make improvements to the relative documentation without the obligation of advance notice. Safety messages The following section describes the warnings related to user and device safety included in this document: NOTICE: indicates obligations that if not observed may lead to damage to the device. CAUTION! Indicates a risky situation which, if not avoided, may cause data loss. IMPORTANT: provides essential information on completing the task that should not be neglected. General warnings This manual is an integral part of the product and accompanies it for its entire working life. It should be consulted for all situations tied to configuration, use and maintenance. For this reason, it should always be accessible to operators. NOTICE: no one is authorized to open the analyzer. This operation is reserved exclusively for CARLO GAVAZZI technical service personnel. Protection may be impaired if the instrument is used in a manner not specified by the manufacturer. Service and warranty In the event of malfunction, fault, requests for information, contact the CARLO GAVAZZI branch or distributor in your country. Installation and use of analyzers other than those indicated in the provided instructions void the warranty. Download This manual www.productselection.net/MANUALS/UK/EM24_im_use.pdf Installation instruction - EM24 www.productselection.net/MANUALS/UK/EM24_im_inst.pdf UCS software www.productselection.net/Download/UK/ucs.zip 4 EM24 E1 - Instruction manual | CARLO GAVAZZI Controls SpA EM24 E1 Introduction EM24 is a three-phase energy analyzer for DIN-rail mounting, with configuration joystick, frontal selector and LCD display. The direct connection version (AV2) allows to measure up to 65 A, the CT connection version (AV5) allows to measure up to 34875 A by means of current transformers (5 A secondary output). The DHCP function is able to speed the commissioning and all the configuration parameters can be set up via UCS. Description AV2 Part AV5 Description A LCD display B Voltage/current connections C Joystick D Selector with pin for MID seal (programming block) E Inputs/outputs or communication port F Pins for MID seal (protection covers included) UCS (Universal Configuration Software) UCS desktop is available for free download. It can be connected to EM24 via Ethernet (Modbus TCP/IP) . The following is possible with UCS: • configure EM24 (online or offline) • view system status for diagnostics and configuration checks function overview EM24 E1 - Instruction manual | CARLO GAVAZZI Controls SpA 5 EM24 E1 use Introduction EM24 is organized in two menus: • measurement and information menu: pages used to display the measurement pages, information relevant to the programmed parameters and instrument firmware release • settings menu: pages used to set parameters Display The display is divided into 3 lines. Symbol Description Displaying of phase-to-neutral system voltage Displaying of phase-to-phase system voltage Displaying of max values User ID Displaying of system variables Displaying of dmd variables EEEE 6 EM24 E1 - Instruction manual | CARLO GAVAZZI Controls SpA Overflow. Note: the DMD calculation, the hour-counter and the energy meters functions are inhibited and the alarm outputs are activated. The indication “EEEE” in a single phase variable automatically implies the overflow condition of the relevant system variable, and the PF indication is forced to “0.000”. Network parameters setting Setting network parameters via DHCP Step Action 1 Install EM24 2 Enable DHCP and exit with End 3 Connect the EM24 to the LAN network to which the PC is connected 4 Access the Info pages to view the assigned network parameters 5 Start UCS software and connect to EM24 via Manual connection> Modbus TCP 6 Enter the IP address displayed on the Info page (see point 4) 7 Access the settings, disable DHCP and assign the required network parameters (assigned by network administrator) Setting network parameters without DHCP Step Action 1 Install EM24 2 Disable DHCP (default setting) 3 Connect the PC to the EM24 via Ethernet cable (point to point connection) 4 Set the PC network properties as follows: • static IP address • IP address of the same class as the EM24, e.g. if the IP of EM24 is 192.168.1.10 (default), you can set the PC address to 192.168.1.20 • Subnet mask: 255.255.255.0 • Gateway: not necessary 5 Start UCS software and connect to EM24 via Manual connection> Modbus TCP, enter the EM24 IP address (192.168.1.10 by default) 6 Access the settings and enter the required network parameters 7 Disconnect the Ethernet cable and connect the EM24 to the network to which the Modbus master is connected EM24 E1 - Instruction manual | CARLO GAVAZZI Controls SpA 7 EM24 E1 use Working with EM24 E1 Working with the measurement/info menu to next measurement page to settings menu to previous info page to next info page to previous measurement page Working with the settings menu increase a parameter value edit/confirm to previous page to next page decrease a parameter value Resetting partial energy meter Step 8 Action 1 Press the button for at least 3 seconds 2 In the PASS page, set the password 1357 3 Confirm operation 4 In the rESEt page, set YES 5 Confirm operation EM24 E1 - Instruction manual | CARLO GAVAZZI Controls SpA Button EM24 E1 use Step Action 6 In the EnE PrES page, set YES 7 Confirm operation Button Setting a parameter Example procedure: how to set Ct rAtio=20 and save changes. Step Action 1 Power on the energy analyzer 2 Press the joystick for at least 3 seconds 3 In the PASS? page, select the correct password (default 0) 4 Confirm operation 5 Scroll pages until Ct rAtio 6 Enter the editing mode 7 Select 20 8 Confirm operation 9 Scroll pages until End to exit Button EM24 E1 - Instruction manual | CARLO GAVAZZI Controls SpA 9 EM24 E1 use Menu description Measurement menu - measurement pages The displayed pages depend on the application set. Page Displayed measurements L1-L2-L3 VLNΣ Hz Phase sequence System phase-neutral voltage Frequency 2 L1-L2-L3 VLLΣ Hz Phase sequence System phase-phase voltage Frequency 3 Tot kWh (+) WΣ dmd WΣ dmd max Total imported active energy System active power dmd System active power dmd max 4 kWh A dmd max PArt Active energy Maximum dmd current Partial active energy 5 Tot kvarh (+) VAΣ dmd VAΣ dmd max Total imported reactive energy System apparent power dmd System apparent power dmd max 6 kvarh VAΣ PArt Reactive energy System apparent power Partial reactive energy 7 kWh (+) t1 WΣ dmd Imported active energy, tariff 1 System active power dmd 8 kWh (+) t2 WΣ dmd Imported active energy, tariff 2 System active power dmd 9 kWh (+) t3 WΣ dmd Imported active energy, tariff 3 System active power dmd 10 kWh (+) t4 WΣ dmd Imported active energy, tariff 4 System active power dmd 11 kvarh (+) t1 WΣ dmd Imported reactive energy, tariff 1 WΣ dmd 12 kvarh (+) t2 WΣ dmd Imported reactive energy, tariff 2 WΣ dmd 13 kvarh (+) t3 WΣ dmd Imported reactive energy, tariff 3 WΣ dmd 14 kvarh (+) t4 WΣ dmd Imported reactive energy, tariff 4 WΣ dmd 15 kWh (+) X WX User X Imported active energy Active power User 16 kWh (+) Y WY User Y Imported active energy Active power User 17 kWh (+) Z WZ User Z Imported active energy Active power User 18 Total kvarh (-) VAΣ dmd VAΣ dmd max Total exported reactive energy System apparent power dmd System apparent power dmd max 19 Total kWh (-) WΣ dmd WΣ dmd max Total exported active energy System active power dmd System active power dmd max 1 10 EM24 E1 - Instruction manual | CARLO GAVAZZI Controls SpA Description Configure the system 20 Hours WΣ PFΣ Total load operating hours System active power System power factor 21 Hours VArΣ PFΣ Total load operating hours System reactive power System power factor 22 var L1 var L2 var L3 Phase 1 reactive power Phase 2 reactive power Phase 3 reactive power 23 VA L1 VA L2 VA L3 Phase 1 apparent power Phase 2 apparent power Phase 3 apparent power 24 PF L1 PF L2 PF L3 Phase 1 power factor Phase 2 power factor Phase 3 power factor 25 W L1 W L2 W L3 Phase 1 active power Phase 2 active power Phase 3 active power 26 A L1 A L2 A L3 Phase 1 current Phase 2 current Phase 3 current 27 V L1-2 V L2-3 V L3-1 Phase 1-phase 2 voltage Phase 2-phase 3 voltage Phase 3-phase 1 voltage 28 V L1 V L2 V L3 Phase 1 voltage Phase 2 voltage Phase 3 voltage Note: in programming mode, the last displayed page is stored. Information Menu Page Page title Information displayed 1 IP o.o.-.- IP address (first part) 2 IP -.-.o.o IP address (second part) 3 Sub o.o.-.- Subnet mask (first part) 4 Sub -.-.o.o Subnet mask (second part) 5 Gateo.o.-.- Default gateway (first part) 6 Gate-.-.o.o Default gateway (second part) 7 Port Modbus TCP port 8 DHCP DHCP enabling 9 Info Ethernet diagnostic 10 Ut ratio VT/PT ratio 11 CT ratio CT ratio 12 1P/2P/3P/3Pn (2-3-4-wire) dmd (time) System Connection (2-3-4-wire) Dmd integration time (min.) 13 Pulse LED pulse weight (Number of kWh/kvarh per pulse) 14 Year Firmware release Year of production EM24 E1 - Instruction manual | CARLO GAVAZZI Controls SpA 11 Configure the system Settings from EM24 E1 General settings The available settings depend on the application set. Page title Sub-menu Description Values Default value Cng PASS - Change password From 0 to 9999 0 Application tYP.A tYP.b tYP.C tYP.d tYP.E tYP.F tYP.G tYP.H tYP.H User From 0 to 9999 1 From 0 to 9999 2 APPLiCAt User USEr 1 USEr 2 From 0 to 9999 3 dHCP - USEr 3 DHCP enabling oFF/on oFF IP Addr IP o.-.-.- IP address From 000 to 255 192 IP -.o.-.- From 000 to 255 168 IP -.-.o.- From 000 to 255 1 From 000 to 255 10 From 000 to 255 255 SUb -.o.-.- From 000 to 255 255 SUb -.-.o.- From 000 to 255 255 From 000 to 255 0 From 000 to 255 192 GAtE -.o.-.- From 000 to 255 168 GAtE -.-.o.- From 000 to 255 1 GAtE -.-.-.o From 000 to 255 1 IP -.-.-.o SUb SUb o.-.-.- Subnet mask SUb -.-.-.o GAtE GAtE o.-.-.- Default gateway Port - MODBUS TCP port SELECtor SELEC. 1 Page displayed according to selector position among the available pages for each application (see”Frontal selector” on page 15) SELEC. 2 SELEC. 3 SELEC.LoC 502 From 1 to 28 1 From 1 to 28 25 From 1 to 28 28 From 1 to 28 3 3P.n 3P.1 2P 1P 3P 3P.n SYS - System Ut rAtio - Voltage transformer ratio (VT) AV5: from 1 to 6975 AV2: N/A 1 Ct rAtio - Current transformer ratio (CT) AV5: from 1 to 6975 AV2: N/A 1 P int.ti - Dmd integration time (min) From 1 to 30 15 FiLtEr.S - Interval of filter intervention with respect to full scale (%) From 0 to 100 2 FiLtEr.Co - Filter coefficient From 1 to 32 2 End - Exit and save - - Note: MID (PFA, PFB): only 3P.n Note: the Ut rAtio is available for compatibility with other versions, even though the AV5 version is not meant to be used with voltage transformers. It should be therefore set to 1. 12 EM24 E1 - Instruction manual | CARLO GAVAZZI Controls SpA Essential information Essential information Measurement management Applications Note: if an application with easy connection is selected, for the calculation of the active energy the power is always integrated, both in the case of imported and exported power . The current direction does not affect the measurement. If an application without easy connection is selected, both the active imported and exported are available. Application A Measurements System: • phase sequence • phase-neutral voltage • frequency • total imported active energy • active power dmd and dmd max Easy connection YES B System: • phase sequence • phase-neutral voltage • frequency • total imported active energy • active power dmd and dmd max • total imported reactive energy • apparent power dmd and dmd max YES C System: • phase sequence • phase-neutral voltage • frequency • total imported active energy • active power dmd and dmd max • imported active and reactive energy by tariff YES D Single phase: • imported active energy • voltage YES E System: • phase sequence • phase-neutral voltage • frequency • total imported and exported active energy • active power dmd and dmd max • run hour meter • active power • power factor NO F System: • phase sequence • phase-neutral voltage • frequency • total imported and exported active energy • active power dmd and dmd max • phase-phase voltage • active energy • maximum dmd current • partial active energy • total imported and exported reactive energy • apparent power, dmd and dmd max • partial reactive energy • run hour meter • active power • power factor NO EM24 E1 - Instruction manual | CARLO GAVAZZI Controls SpA 13 Essential information G System: • phase sequence • phase-neutral voltage • frequency • total imported active energy • active power dmd and dmd max • phase-phase voltage • active energy • maximum dmd current • partial active energy • total imported reactive energy • apparent power, dmd and dmd max • reactive energy • run hour meter • active power • active power dmd • reactive power • power factor • imported active and reactive energy by tariff Single phase: • reactive power per phase • apparent power per phase • power factor per phase • active power per phase • current per phase • line-line voltages • line-neutral voltages YES H System: • phase sequence • phase-neutral voltage • frequency • total imported and exported active energy • active power dmd and dmd max • phase-phase voltage • active energy • maximum dmd current • partial active energy • total imported and exported reactive energy • apparent power, dmd and dmd max • reactive energy • run hour meter • active power • active power dmd • reactive power • power factor • imported active and reactive energy by tariff Single phase: • reactive power per phase • apparent power per phase • power factor per phase • active power per phase • current per phase • line-line voltages • line-neutral voltages NO Programming pages The following table shows which programming pages are available for each application Page Application A B C D E F G H Change password x x x x x x x x Application x x x x x x x x User - - - x - - - - DHCP enabling x x x x x x x x IP address x x x x x x x x Subnet mask x x x x x x x x Default gateway x x x x x x x x MODBUS TCP port x x x x x x x x 14 EM24 E1 - Instruction manual | CARLO GAVAZZI Controls SpA Essential information Selector x x x System x x x VT ratio x x x x x x x x x x x x x x x x x CT ratio x x x x x x x x Average power integration time x x x - x x x x Filter S - - - - - x x x Filter Co - - - - - x x x End x x x x x x x x Tariff management Managing tariffs via Modbus command Change the tariff by entering the value corresponding to the current tariff according to the following table in the 1201Fh registry: Current tariff Register value T1 1 T2 2 T3 3 T4 4 Disabling tariff management Set tariff management as disabled or enter 0 (default value) in the 1201Fh register. Frontal LED and selector Frontal LED The frontal red LED flashes proportionally to the active imported energy consumption if the selector is in - 1 - 2 position, and to the reactive inductive energy consumption in kvarh position. Any kind of negative (exported) energy will not be managed by the front LED. Frontal selector • Lock position: the frontal selector prevents from accessing the programming mode • 1, 2, kvarh position: quick access to measuring pages. Each position is associated with one measuring page according to the following table: Application Selector position Lock 3 1,2,3 1 B, C, E, F, G, H Lock, 1, 2, kvarh Can be set from 1 to 28 C Lock, 1, 2, kvarh Can be set from 1 to 28 Lock 28 1 15 2 16 3 17 A D Page available EM24 E1 - Instruction manual | CARLO GAVAZZI Controls SpA 15 Maintenance and disposal Maintenance and disposal Cleaning Use a slightly dampened cloth to clean the display. Do not use abrasives or solvents. Responsibility for disposal The product must be disposed of at the relative recycling centers specified by the government or local public authorities. Correct disposal and recycling will contribute to the prevention of potentially harmful consequences to the environment and persons. 16 EM24 E1 - Instruction manual | CARLO GAVAZZI Controls SpA CARLO GAVAZZI Controls SpA via Safforze, 8 32100 Belluno (BL) Italy www.gavazziautomation.com [email protected] info: +39 0437 355811 fax: +39 0437 355880 EM24 E1 - User manual 2018-06 | Copyright © 2018 EM24 E1 Analizzatore di energia per sistemi trifase MANUALE UTENTE Sommario EM24 E1 21 Introduzione21 Descrizione21 UCS (Universal Configuration Software) 21 Uso di EM24 E1 22 Introduzione22 Display22 Impostare i parametri di rete 23 Impostare i parametri di rete via DHCP 23 Impostare i parametri di rete senza DHCP 23 Operare nell’EM24 E1 24 Operare nel menu misure/info 24 Operare nel menuimpostazioni 24 Azzerare il contatore di energia parziale 24 Impostare un parametro 25 Descrizione dei manu 26 Menu misure- pagine di misura 26 Menu informazioni 27 Impostazioni da EM24 E1 28 Impostazioni generali 28 Cose da sapere 29 Applicazioni29 Pagine di programmazione 30 Gestire le tariffe tramite comando Modbus 31 Disabilitare la gestione tariffe 31 LED frontale 31 Selettore frontale 31 Manutenzione e smaltimento 32 EM24 E1 - Manuale utente | CARLO GAVAZZI Controls SpA 19 Proprietà delle informazioni Copyright © 2018, CARLO GAVAZZI Controls SpA Tutti i diritti riservati in tutti i paesi. CARLO GAVAZZI Controls SpA si riserva il diritto di apportare modifiche o miglioramenti alla relativa documentazione senza obbligo di preavviso. Messaggi di sicurezza Di seguito le segnalazioni legate alla sicurezza dell’utilizzatore e dell’apparecchio contenute in questo documento: AVVISO: indica obblighi che se non ottemperati possono causare danni all’apparecchio. ATTENZIONE! Indica una situazione rischiosa che se non evitata, può causare la perdita di dati. IMPORTANTE: offre indicazioni essenziali al completamento del compito che non devono essere trascurate. Avvertenze generali Questo manuale è parte integrante del prodotto e accompagna il prodotto per tutta la sua vita. Deve essere consultato per tutte le situazioni legate alla configurazione, all’uso e alla manutenzione. Per questo motivo deve essere sempre accessibile agli operatori. AVVISO: nessuno è autorizzato ad aprire l’analizzatore. TSolo il personale dell’assistenza tecnica CARLO GAVAZZI può farlo. La protezione può essere compromessa se lo strumento viene usato in un modo non specificato dal costruttore. Assistenza e garanzia In caso di malfunzionamento, guasto, necessità informazioni o per acquistare componenti contattare la filiale CARLO GAVAZZI o il distributore nel paese di appartenenza. L’installazione e l’uso dell’analizzatore diversi da quanto indicato nelle istruzioni fornite invalidano la garanzia. Download Questo manuale www.productselection.net/MANUALS/UK/EM24_im_use.pdf Istruzioni per l’installazione - EM24 www.productselection.net/MANUALS/UK/EM24_im_inst.pdf UCS software www.productselection.net/Download/UK/ucs.zip 20 EM24 E1 - Manuale utente | CARLO GAVAZZI Controls SpA EM24 E1 Introduzione EM24 è un analizzatore di energia trifase per il montaggio su guida DIN, con joystick di configurazione, selettore frontale e display LCD. La versione con connessione diretta (AV2) consente di misurare fino a 65 A, la versione con connessione TA (AV5) consente di misurare fino a 34875 A tramite trasformatori di corrente (uscita secondaria 5 A). La funzione DHCP è in grado di velocizzare la messa in servizio e tutti i parametri di configurazione possono essere impostati tramite UCS. Descrizione AV2 Parte Descrizione A Display LCD B Connessioni tensione/corrente C Joystick D Selettore con perno per sigillo MID (blocco programmazione) E Uscite/ingressi o porta di comunicazione F Perni per sigillo MID (coperture di protezione incluse) AV5 UCS (Universal Configuration Software) UCS desktop è disponibile per il download gratuito. Può essere collegato a EM24 via Ethernet (Modbus TCP/IP). Con UCS è possibile: • configurare EM24 (online oppure offline) • visualizzare lo stato del sistema a fini diagnostici e di verifica della configurazione function overview EM24 E1 - Manuale utente | CARLO GAVAZZI Controls SpA 21 Uso di EM24 E1 Introduzione EM24 è organizzato in quattro menu: • menu misura e informazioni: pagine che mostrano le pagine di misura, informazioni sui parametri programmati e release firmware dello strumento • menu impostazioni: pagine per impostare i parametri Display Il display è suddiviso in 3 righe. Simbolo Descrizione Visualizzazione tensione fase-neutro di sistema Visualizzazione tensione fase-fase di sistema Visualizzazione valori massimi User ID (Identificatore utente) Visualizzazione variabili di sistema Visualizzazione variabili dmd EEEE 22 EM24 E1 - Manuale utente | CARLO GAVAZZI Controls SpA Overflow. Nota: le funzioni di calcolo DMD, conta-ore e contatori di energia vengono inibite e le uscite allarme vengono attivate. L’indicazione “EEEE” su una variabile di singola fase si estende automaticamente alla corrispondente variabile di sistema e l’indicazione PF viene portata a “0.000”. Impostare i parametri di rete Impostare i parametri di rete via DHCP Passo Azione 1 Installare l’EM24 2 Abilitare il DHCP ed uscire con End 3 Collegare l’EM24 alla rete LAN alla quale è connesso il PC 4 Accedere alle pagine Info er visualizzare i parametri di rete assegnati 5 Avviare il software UCS e collegare l’EM24 via Connessione manuale> Modbus TCP 6 Digitare l’indirizzo IP visualizzato nelle pagine Info (vedere punto 4) 7 Accedere alle impostazioni, disabilitare il DHCP ed assegnare i parametri di rete (forniti dall’amministratore di rete) Impostare i parametri di rete senza DHCP Passo Azione 1 Installare l’EM24 2 Disabilitare il DHCP (disabilitato per default) 3 Collegare il PC all’EM24 via cavo Ethernet (connessione punto-punto) 4 Impostare le proprietà di rete del PC come segue: • indirizzo IP statico • indirizzo IP della stessa classe dell’ IP dell’ EM24, e.g. se l’IP dell’EM24 è 192.168.1.10 (di default), è possibile impostare l’indirizzo del PC a 192.168.1.20 • Maschera di sottorete: 255.255.255.0 • Gateway: non necessario 5 Avviare il software UCS e collegare l’EM24 via Connessione manuale> Modbus TCP, igitare l’indirizzo IP dell’EM24 (di default 192.168.1.10) 6 Accedere alle impostazioni e digitare i parametri di rete richiesti 7 Scollegare il cavo Ethernet e collegare l’EM24 alla rete alla quale è connesso il master Modbus EM24 E1 - Manuale utente | CARLO GAVAZZI Controls SpA 23 Uso di EM24 E1 Operare nell’EM24 E1 Operare nel menu misure/info Visualizzare la pagina misura successiva Visualizzare il menu impostazioni Visualizzare la pagina info precedente Visualizzare la pagina info successiva Visualizzare la pagina misura precedente Operare nel menu impostazioni Aumentare il valore di un parametro Modificare/ confermare Visualizzare la pagina successiva Visualizzare la pagina precedente Diminuire il valore di un parametro Azzerare il contatore di energia parziale Passo Azione 1 Premere il tasto per almeno 3 secondi 2 Nella pagina PASS, inserire la password 1357 3 Confermare l’operazione 4 Nella pagina rESEt, impostare YES 5 Confermare l’operazione 24 EM24 E1 - Manuale utente | CARLO GAVAZZI Controls SpA Button Uso di EM24 E1 Passo Azione 6 Nella pagina EnE PrES, impostare YES 7 Confermare l’operazione Button Impostare un parametro Procedura di esempio: compe impostare Ct rAtio=20 salvare la modifica. Passo Azione 1 Alimentare l’EM24 2 Premese il tasto per lameno 3 secondi 3 Nella pagina PASS?, selezionare la password corretta (di default 0) 4 Confermare l’operazione 5 Scorrere le pagine fino a Ct rAtio 6 Accedere alla modalità modifica 7 Selezionare 20 8 Confermare l’operazione 9 Scorrere le pagine fino a End per uscire Tasto EM24 E1 - Manuale utente | CARLO GAVAZZI Controls SpA 25 Uso di EM24 E1 Descrizione dei menu Menu misure- pagine di misura Le pagine visualizzate dipendono dall’applicazione impostata. Pagina Misure visualizzate L1-L2-L3 VLNΣ Hz Sequenza fasi Tensione fase-neutro di sistema Frequenza 2 L1-L2-L3 VLLΣ Hz Sequenza fasi Tensione fase-fase di sistema Frequenza 3 Tot kWh (+) WΣ dmd WΣ dmd max Energia attiva importata totale Potenza attiva di sistema dmd Potenza attiva di sistema dmd max 4 kWh A dmd max PArt Energia attiva Corrente dmd massima Energia attiva parziale 5 Tot kvarh (+) VAΣ dmd VAΣ dmd max Energia reattiva importata totale Potenza apparente di sistema dmd Potenza apparente di sistema dmd max 6 kvarh VAΣ PArt Energia reattiva Potenza apparente di sistema Energia reattiva parziale 7 kWh (+) t1 WΣ dmd Energia attiva importata, tariffa 1 Potenza attiva di sistema dmd 8 kWh (+) t2 WΣ dmd Energia attiva importata, tariffa 2 Potenza attiva di sistema dmd 9 kWh (+) t3 WΣ dmd Energia attiva importata, tariffa 3 Potenza attiva di sistema dmd 10 kWh (+) t4 WΣ dmd Energia attiva importata, tariffa 4 Potenza attiva di sistema dmd 11 kvarh (+) t1 WΣ dmd Energia reattiva importata, tariffa 1 WΣ dmd 12 kvarh (+) t2 WΣ dmd Energia reattiva importata, tariffa 2 WΣ dmd 13 kvarh (+) t3 WΣ dmd Energia reattiva importata, tariffa 3 WΣ dmd 14 kvarh (+) t4 WΣ dmd Energia reattiva importata, tariffa 4 WΣ dmd 15 kWh (+) X WX User X Energia attiva importata Potenza attiva Utente 16 kWh (+) Y WY User Y Energia attiva importata Potenza attiva Utente 17 kWh (+) Z WZ User Z Energia attiva importata Potenza attiva Utente 18 Total kvarh (-) VAΣ dmd VAΣ dmd max Energia reattiva esportata totale Potenza apparente di sistema dmd Potenza apparente di sistema dmd max 19 Total kWh (-) WΣ dmd WΣ dmd max Energia attiva esportata totale Potenza attiva di sistema dmd Potenza attiva di sistema dmd max 1 26 EM24 E1 - Manuale utente | CARLO GAVAZZI Controls SpA Descrizione Configurare il sistema 20 Hours WΣ PFΣ Contaore Potenza attiva di sistema Fattore di potenza di sistema 21 Hours VArΣ PFΣ Contaore Potenza reattiva di sistema Fattore di potenza di sistema 22 var L1 var L2 var L3 Potenza reattiva di fase 1 Potenza reattiva di fase 2 Potenza reattiva di fase 3 23 VA L1 VA L2 VA L3 Potenza apparente di fase 1 Potenza apparente di fase 2 Potenza apparente di fase 3 24 PF L1 PF L2 PF L3 Fattore di potenza di fase 1 Fattore di potenza di fase 2 Fattore di potenza di fase 3 25 W L1 W L2 W L3 Potenza attiva di fase 1 Potenza attiva di fase 2 Potenza attiva di fase 3 26 A L1 A L2 A L3 Corrente di fase 1 Corrente di fase 2 Corrente di fase 3 27 V L1-2 V L2-3 V L3-1 Tensione di fase 1-fase 2 Tensione di fase 2-fase 3 Tensione di fase 3-fase 1 28 V L1 V L2 V L3 Tensione di fase 1 Tensione di fase 2 Tensione di fase 3 Note: in modalità programmazione, rimane in memoria l’ultima pagina visualizzata. Menu informazioni Pagina Titolo pagina Informazioni visualizzate 1 IP o.o.-.- Indirizzo IP (prima parte) 2 IP -.-.o.o Indirizzo IP (seconda parte) 3 Sub o.o.-.- Maschera di sottorete (prima parte) 4 Sub -.-.o.o Maschera di sottorete (seconda parte) 5 Gateo.o.-.- Default gateway (prima parte) 6 Gate-.-.o.o Default gateway (seconda parte) 7 Port Porta Modbus TCP 8 DHCP Abilitazione DHCP 9 Info Diagnostica Ethernet 10 Ut ratio Rapporto TV 11 CT ratio Rapporto TA 12 1P/2P/3P/3Pn (2-3-4-wire) dmd (time) Sistema Connessione (2-3-4 fili) Intervallo per il calcolo dei valori medi (min.) 13 Pulse Peso impulsi LED (numero di kWh/kvarh per impulso) 14 Year Release firmware Anno di produzione EM24 E1 - Manuale utente | CARLO GAVAZZI Controls SpA 27 Configurare il sistema Impostazioni da EM24 E1 Impostazioni generali Le impostazioni disponibili dipendono dall’applicazione impostata. Titolo pagina Sotto-menu Descrizione Valori Valori di default Cng PASS - Modifica password Da 0 a 9999 0 Applicazione tYP.A tYP.b tYP.C tYP.d tYP.E tYP.F tYP.G tYP.H tYP.H Utente Da 0 a 9999 1 Da 0 a 9999 2 APPLiCAt User USEr 1 USEr 2 Da 0 a 9999 3 dHCP - Abilitazione DHCP oFF/on oFF IP Addr IP o.-.-.- Indirizzo IP Da 000 a 255 192 IP -.o.-.- Da 000 a 255 168 IP -.-.o.- Da 000 a 255 1 Da 000 a 255 10 Da 000 a 255 255 SUb -.o.-.- Da 000 a 255 255 SUb -.-.o.- Da 000 a 255 255 Da 000 a 255 0 Da 000 a 255 192 GAtE -.o.-.- Da 000 a 255 168 GAtE -.-.o.- Da 000 a 255 1 GAtE -.-.-.o Da 000 a 255 1 USEr 3 IP -.-.-.o SUb SUb o.-.-.- Maschera di sottorete SUb -.-.-.o GAtE GAtE o.-.-.- Gateway di default Port - Porta MODBUS TCP SELECtor SELEC. 1 Pagina visualizzata in base alla posizione del selettore tra le pagine disponibili per ciascuna applicazione (vedere “Selettore frontale” a pagina 31) SELEC. 2 SELEC. 3 SELEC.LoC 502 Da 1 a 28 1 Da 1 a 28 25 Da 1 a 28 28 Da 1 a 28 3 3P.n 3P.1 2P 1P 3P 3P.n SYS - Sistema Ut rAtio - Rapporto del trasformatore di tensione (TV) AV5: da 1 a 6975 AV2: N/D 1 Ct rAtio - Rapporto del trasformatore di corrente (TA) AV5: da 1 a 6975 AV2: N/D 1 P int.ti - Intervallo per il calcolo dei valori medi (min) Da 1 a 30 15 FiLtEr.S - Intervallo di intervento del filtro rispetto al fondo scala (%) Da 0 a 100 2 FiLtEr.Co - Coefficiente del filtro Da 1 a 32 2 End - Esci e salva le modifiche - - Nota: MID (PFA, PFB): solo 3P.n Nota: Ut rAtio è disponibile per compatibilità con altre versioni, anche se la versione AV5 non è destinata ad essere utilizzata con trasformatori di tensione. Dovrebbe essere quindi impostato a 1. 28 EM24 E1 - Manuale utente | CARLO GAVAZZI Controls SpA Cose da sapere Cose da sapere Gestione misure Applicazioni Nota: se l’applicazione selezionata prevede la funzione Easy connection, per il calcolo dell’energia attiva la potenza è sempre integrata, sia nel caso di potenza importata che esportata. La direzione della corrente non influisce sulla misura. Se l’applicazione selezionata non prevede la funzione Easy connection, sono disponibili sia l’energia attiva importata che quella esportata. Applicazione A Misure Sistema: • sequenza fasi • tensione fase-neutro • frequenza • energia attiva importata totale • potenza attiva dmd e dmd max Easy connection SÌ B Sistema: • sequenza fasi • tensione fase-neutro • frequenza • energia attiva importata totale • potenza attiva dmd e dmd max • energia reattiva importata totale • potenza apparente dmd e dmd max SÌ C Sistema: • sequenza fasi • tensione fase-neutro • frequenza • energia attiva importata totale • potenza attiva dmd e dmd max • energia attiva e reattiva importata per tariffa SÌ D Monofase: • energia attiva importata • tensione SÌ E Sistema: • sequenza fasi • tensione fase-neutro • frequenza • energia attiva e reattiva importata totale • potenza attiva dmd e dmd max • contaore • potenza attiva • fattore di potenza NO F Sistema: • sequenza fasi • tensione fase-neutro • frequenza • energia attiva e reattiva importata totale • potenza attiva dmd e dmd max • tensione fase-fase • energia attiva • corrente dmd massima • energia attiva parziale • energia reattiva importata ed esportata totale • potenza apparente, dmd e dmd max • energia reattiva parziale • contaore • potenza attiva • fattore di potenza NO EM24 E1 - Manuale utente | CARLO GAVAZZI Controls SpA 29 Cose da sapere G Sistema: • sequenza fasi • tensione fase-neutro • frequenza • energia attiva importata totale • potenza attiva dmd e dmd max • tensione fase-fase • energia attiva • corrente dmd massima • energia attiva parziale • energia reattiva importata totale • potenza apparente, dmd e dmd max • energia reattiva • contaore • potenza attiva • potenza attiva dmd • potenza reattiva • fattore di potenza • energia attiva e reattiva importata per tariffa Monofase: • potenza reattiva per fase • potenza apparente per fase • fattore di potenza per fase • potenza attiva per fase • corrente per fase • tensioni linea-linea • tensioni linea-neutro SÌ H Sistema: • sequenza fasi • tensione fase-neutro • frequenza • energia attiva e reattiva importata totale • potenza attiva dmd e dmd max • tensione fase-fase • energia attiva • corrente dmd massima • energia attiva parziale • energia reattiva importata ed esportata totale • potenza apparente, dmd e dmd max • energia reattiva • contaore • potenza attiva • potenza attiva dmd • potenza reattiva • fattore di potenza • energia attiva e reattiva importata per tariffa Monofase: • potenza reattiva per fase • potenza apparente per fase • fattore di potenza per fase • potenza attiva per fase • corrente per fase • tensioni linea-linea • tensioni linea-neutro NO Pagine di programmazione La tabella seguente mostra quali pagine di programmazione sono disponibili per ciascuna applicazione Pagina Applicazione A B C D E F G H Modifica password x x x x x x x x Applicazione x x x x x x x x Utente - - - x - - - - Abilitazione DHCP x x x x x x x x Indirizzo IP x x x x x x x x Maschera di sottorete x x x x x x x x Gateway di default x x x x x x x x Porta MODBUS TCP x x x x x x x x 30 EM24 E1 - Manuale utente | CARLO GAVAZZI Controls SpA Cose da sapere Selettore x x x Sistema x x x Rapporto del trasformatore di tensione (TV) x x x x x x x x x x x x x x x x x Rapporto del trasformatore di corrente (TA) x x x x x x x x Intervallo per il calcolo dei valori medi x x x - x x x x Intervallo di intervento del filtro rispetto al fondo scala (%) - - - - - x x x Coefficiente del filtro - - - - - x x x End x x x x x x x x Gestione tariffe Gestire le tariffe tramite comando Modbus Comandare il cambio tariffa scrivendo nel registro 1201Fh il valore corrispondente alla tariffa attuale in accordo alla seguente tabella: Tariffa attuale Valore registro T1 1 T2 2 T3 3 T4 4 Disabilitare la gestione tariffe Impostare la gestione delle tariffe come disabilitata oppure scrivere nel registro 1201Fh il valore 0 (valore di default) LED e selettore frontali LED frontale Il LED rosso frontale lampeggia proporzionalmente al consumo di energia attiva importata se il selettore si trova in posizione energia reattiva induttiva se in posizione kvarh . Ogni tipo di energia negativa (esportata) non è gestita dal LED. - 1 - 2, e al consumo di Selettore frontale • Posizione Lock : il selettore frontale impedisce l’accesso alla modalità di programmazione • Posizione 1, 2, kvarh : accesso rapido alle pagine di misura. Ogni posizione è associata ad una pagina di misura in base alla tabella seguente: Applicazione Posizione del seletore Lock 3 1,2,3 1 B, C, E, F, G, H Lock, 1, 2, kvarh Selezionabile, da 1 a 28 C Lock, 1, 2, kvarh Selezionabile, da 1 a 28 Lock 28 1 15 2 16 3 17 A D Pagina disponibile EM24 E1 - Manuale utente | CARLO GAVAZZI Controls SpA 31 Manutenzione e smaltimento Manutenzione e smaltimento Pulizia Per mantenere pulito il display usare un panno leggermente inumidito. Non usare abrasivi o solventi. Responsabilità di smaltimento Smaltire con raccolta differenziata tramite le strutture di raccolte indicate dal governo o dagli enti pubblici locali. Il corretto smaltimento e il riciclaggio aiuteranno a prevenire conseguenze potenzialmente negative per l’ambiente e per le persone. 32 EM24 E1 - Manuale utente | CARLO GAVAZZI Controls SpA CARLO GAVAZZI Controls SpA via Safforze, 8 32100 Belluno (BL) Italy www.gavazziautomation.com [email protected] info: +39 0437 355811 fax: +39 0437 355880 EM24 E1 - Manuale utente 2018-06 | Copyright © 2018 EM24 E1 Dreiphasen-Energieanalysator BETRIEBSANLEITUNG Inhaltsverzeichnis EM24 E1 37 Einleitung37 Beschreibung37 UCS (Universal Configuration Software) (Konfigurationssoftware) 37 Benutzung des EM24 E1 38 Einleitung38 Anzeige38 Netzwerkparametereinstellungen39 Netzwerkparameter über DHCP einstellen 39 Netzwerkparameter ohne DHCP einstellen 39 Arbeiten mit EM24 E1 40 Arbeiten mit dem Messungs-/Infomenü 40 Arbeiten mit dem Einstellungsmenü 40 Setzt den partiellen Energiezähler zurück 40 Einstellen eines Parameters 41 Beschreibung der Menüs 42 Messungsmenü - Messungsseiten 42 Informationsmenü 43 Einstellungen vom EM24 E1 44 Allgemeine Einstellungen 44 Wichtige Informationen 45 Anwendungen 45 Programmierseiten 46 Tarifverwaltung über Modbus-Befehl 47 Deaktivierung der Tarifverwaltung 47 Front-LED 47 Vorderer Wahlschalter 47 Instandhaltung und Entsorgung 48 EM24 E1 - Bedienungsanleitung | CARLO GAVAZZI Controls SpA 35 Information über Eigentumsrechte Copyright © 2018, CARLO GAVAZZI Controls SpA Alle Rechte vorbehalten in allen Ländern. CARLO GAVAZZI Controls SpA behält sich das Recht vor, ohne vorherige Ankündigung Änderungen oder Verbesserungen in der entsprechenden Dokumentation vorzunehmen. Sicherheitshinweise Der folgende Abschnitt beschreibt die in diesem Dokument enthaltenen Warnungen in Bezug auf Benutzer- und Gerätesicherheit: HINWEIS: Bezeichnet Bedienungsregeln, deren Nichtbeachtung zu Schäden am Gerät führen können. VORSICHT! Bezeichnet eine riskante Situation, die Datenverlust verursachen kann, wenn sie nicht vermieden wird. WICHTIG: Bietet wesentliche Informationen zur Erledigung einer Aufgabe, die nicht vernachlässigt werden sollte. Allgemeine Warnungen Diese Anleitung ist ein integraler Bestandteil des Produkts und verbleibt bei ihm für seine gesamte Lebensdauer. Sie sollte in allen Situationen betreffend Konfiguration, Gebrauch und Instandhaltung zu Rate gezogen werden. Deshalb sollte sie dem Benutzer jederzeit zugänglich sein. HINWEIS: Niemand ist autorisiert, das Analysator zu öffnen. Diese Operation ist ausschließlich dem technischen Kundendienstpersonal von CARLO GAVAZZI vorbehalten. Die Schutzfunktion kann beeinträchtigt werden, wenn das Instrument anders als vom Hersteller vorgesehen benutzt wird. Kundendienst und Garantie Bei Störungen oder Fehlern bzw. wenn Sie Auskünfte benötigen, wenden Sie sich bitte an die Niederlassung von CARLO GAVAZZI oder den zuständigen Vertriebspartner in Ihrem Land. Installation und Gebrauch von Analysatoren abweichend von der Beschreibung in der mitgelieferten Anleitung macht die Garantie ungültig. Download Diese Anleitung www.productselection.net/MANUALS/UK/EM24_im_use.pdf Installationsanleitung - EM24 www.productselection.net/MANUALS/UK/EM24_im_inst.pdf UCS-Software www.productselection.net/Download/UK/ucs.zip 36 EM24 E1 - Bedienungsanleitung | CARLO GAVAZZI Controls SpA EM24 E1 Einleitung EM24 ist ein Drei-Phasen-Energieanalysator für DIN-Schienenmontage mit Konfigurationsjoystick, frontseitigem Wahlschalter und LCDAnzeige. Die Ausführung mit direktem Anschluss (AV2) ermöglicht die Messung bis zu 65 A, während die CT-Anschlussversion (AV5) die Messung bis zu 34875 A mit Stromwandlern (5 A Sekundärausgang) erlaubt. Die DHCP-Funktion kann die Inbetriebnahme beschleunigen, und alle Konfigurationsparameter können über die UCS eingestellt werden. Beschreibung AV2 Teil Beschreibung A LCD-Anzeige B Spannungs-/Stromverbindungen C Joystick D Wahlschalter mit Stift für MID-Dichtung (Programmiersatz) E Eingänge/Ausgänge oder Kommunikationsschnittstelle F Stifte für MID-Dichtung (Schutzabdeckungen inbegriffen) AV5 UCS (Universal Configuration Software) (Konfigurationssoftware) Die Arbeitsoberfläche der UCS ist frei herunterladbar. Sie kann über Ethernet (Modbus TCP/IP) mit EM24 verbunden werden. UCS ermöglicht folgendes: • Konfiguration EM24 (Online oder Offline) • Anzeigen des Systemstatus für Diagnostik und zum Überprüfen der Konfiguration Funktionsüberblick EM24 E1 - Bedienungsanleitung | CARLO GAVAZZI Controls SpA 37 Benutzung des EM24 E1 Einleitung Der EM24 bietet zwei Menüs an: • Messungs- und Informationsmenü: Die Seiten zeigen Messwerteseiten, Informationen über die programmierten Parameter und Firmwarefreigabe an • Einstellungsmenü: Die Seiten stellen die Parametereinstellungen dar Anzeige Die Anzeige ist in 3 Zeilen unterteilt. Symbol Beschreibung Anzeige der Phasen-Nullleiter-Systemspannung Anzeige der Phasen-Phasen-Systemspannung Anzeige der MAX-Werte Benutzer-ID Anzeige der Systemvariablen Anzeige der DMD Variablen EEEE 38 EM24 E1 - Bedienungsanleitung | CARLO GAVAZZI Controls SpA Overflow. Hinweis: Die DMD Berechnungs-, die Stundenzählersowie die Energiezählerfunktionen sind gesperrt, und die Alarmausgänge sind eingeschaltet. Die Angabe „EEEE” in einer Einphasen-Variable deutet automatisch auf den Overflow-Zustand der relevanten Systemvariable hin, und die PF-Angabe wird zu „0.000” gezwungen. Netzwerkparametereinstellungen Netzwerkparameter über DHCP einstellen Schritt Aktion 1 EM24 installieren 2 DHCP aktivieren und mit End verlassen 3 EM24 mit dem LAN-Netzwerk verbinden, an dem der PC angeschlossen ist 4 Zur Ansicht der zugeordneten Netzwerkparameter greifen Sie auf die Info Seiten 5 UCS-Software starten und mit EM24 über Manuelle Verbindung> Modbus TCP verbinden 6 Die auf der Info-Seite (siehe Punkt 4) angezeigte IP-Adresse eingeben 7 Greifen Sie auf die Einstellungen, deaktivieren Sie DHCP und ordnen Sie die notwendigen Netzwerkparameter zu (vom Netzwerkadministrator vergeben) Netzwerkparameter ohne DHCP einstellen Schritt Aktion 1 EM24 installieren 2 DHCP deaktivieren (Standard-Einstellung) 3 Verbinden Sie den PC mit dem EM24 durch ein Ethernetkabel (Punkt-zu-Punkt Verbindung) 4 Die Netzwerkeigenschaften des PCs wie folgt einstellen: • statische IP-Adresse • IP-Adresse der gleichen Art wie EM24, z. Bsp. falls die IP von EM24 192.168.1.10 (Standard) ist, können Sie die PCAdresse auf 192.168.1.20 einstellen • Subnetzmaske: 255.255.255.0 • Gateway: nicht nötig 5 UCS-Software starten und mit EM24 über Manuelle Verbindung> Modbus TCP verbinden, die EM24 IP-Adresse eingeben (192.168.1.10 standardmäßig) 6 Gelangen Sie zu den Einstellungen, und geben Sie die erforderlichen Netzwerkparameter ein 7 Ethernet-Kabel entfernen und EM24 mit dem Netzwerk verbinden, an dem der Modbus-Master angeschlossen ist EM24 E1 - Bedienungsanleitung | CARLO GAVAZZI Controls SpA 39 Benutzung des EM24 E1 Arbeiten mit EM24 E1 Arbeiten mit dem Messungs-/Infomenü zur nächsten Messungsseite zum Einstellungsmenü zur vorherigen Seite zur nächsten Infoseite zur vorherigen Messungsseite Arbeiten mit dem Einstellungsmenü Parameterwert erhöhen Bearbeiten/Bestätigen zur vorherigen Seite zur nächsten Seite Parameterwert verringern Setzt den partiellen Energiezähler zurück Schritt Aktion 1 Die Taste für mindestens 3 Sekunden gedrückt halten 2 Auf der Seite PASS das Passwort 1357 eingeben 3 Operation bestätigen 4 Auf der Seite rESEt YES eingeben 5 Operation bestätigen 40 EM24 E1 - Bedienungsanleitung | CARLO GAVAZZI Controls SpA Taste Benutzung des EM24 E1 Schritt Aktion 6 Auf der Seite EnE PrES YES eingeben 7 Operation bestätigen Taste Einstellen eines Parameters Beispielprozedur: Wie Ct rAtio=20 gesetzt und die Änderung gespeichert wird. Schritt Aktion 1 Energiezähler einschalten 2 Joystick für mindestens 3 Sekunden gedrückt halten 3 Auf der Seite PASS? das richtige Passwort eingeben (Standard 0) 4 Operation bestätigen 5 Seiten scrollen bis Ct rAtio 6 Gelangen Sie in den Bearbeitungsmodus 7 20 auswählen 8 Operation bestätigen 9 Seiten scrollen bis End, um das Menü abzuschließen Taste EM24 E1 - Bedienungsanleitung | CARLO GAVAZZI Controls SpA 41 Benutzung des EM24 E1 Beschreibung der Menüs Messungsmenü - Messungsseiten Die angezeigten Seiten hängen von der eingestellten Anwendung ab. Page Angezeigte Messungen L1-L2-L3 VLNΣ Hz Phasensequenz System Phase-Nullleiter-Spannung Frequenz 2 L1-L2-L3 VLLΣ Hz Phasensequenz System Phase-Phase-Spannung Frequenz 3 Tot kWh (+) WΣ dmd WΣ dmd max Importierte Wirkenergie gesamt System-Wirkleistung DMD System-Wirkleistung DMD max. 4 kWh A dmd max PArt Wirkenergie Maximalstrom DMD Partielle Wirkenergie 5 Tot kvarh (+) VAΣ dmd VAΣ dmd max Importierte Blindenergie gesamt System-Scheinleistung DMD System-Scheinleistung DMD max. 6 kvarh VAΣ PArt Blindenergie System-Scheinleistung Partielle Blindenergie 7 kWh (+) t1 WΣ dmd Importierte Wirkenergie, Tarif 1 System-Wirkleistung DMD 8 kWh (+) t2 WΣ dmd Importierte Wirkenergie, Tarif 2 System-Wirkleistung DMD 9 kWh (+) t3 WΣ dmd Importierte Wirkenergie, Tarif 3 System-Wirkleistung DMD 10 kWh (+) t4 WΣ dmd Importierte Wirkenergie, Tarif 4 System-Wirkleistung DMD 11 kvarh (+) t1 WΣ dmd Importierte Blindenergie, Tarif 1 WΣ DMD 12 kvarh (+) t2 WΣ dmd Importierte Blindenergie, Tarif 2 WΣ DMD 13 kvarh (+) t3 WΣ dmd Importierte Blindenergie, Tarif 3 WΣ DMD 14 kvarh (+) t4 WΣ dmd Importierte Blindenergie, Tarif 4 WΣ DMD 15 kWh (+) X WX User X Importierte Wirkenergie Wirkleistung Benutzer 16 kWh (+) Y WY User Y Importierte Wirkenergie Wirkleistung Benutzer 17 kWh (+) Z WZ User Z Importierte Wirkenergie Wirkleistung Benutzer 18 Total kvarh (-) VAΣ dmd VAΣ dmd max Exportierte Blindenergie gesamt System-Scheinleistung DMD System-Scheinleistung DMD max. 19 Total kWh (-) WΣ dmd WΣ dmd max Exportierte Wirkenergie gesamt System-Wirkleistung DMD System-Wirkleistung DMD max. 1 42 EM24 E1 - Bedienungsanleitung | CARLO GAVAZZI Controls SpA Beschreibung Systemkonfiguration 20 Hours WΣ PFΣ Gesamt-Betriebsstunden unter Last System-Wirkleistung System-Leistungsfaktor 21 Hours VArΣ PFΣ Gesamt-Betriebsstunden unter Last System-Blindleistung System-Leistungsfaktor 22 var L1 var L2 var L3 Blindleistung Phase 1 Blindleistung Phase 2 Blindleistung Phase 3 23 VA L1 VA L2 VA L3 Scheinleistung Phase 1 Scheinleistung Phase 2 Scheinleistung Phase 3 24 PF L1 PF L2 PF L3 Leistungsfaktor Phase 1 Leistungsfaktor Phase 2 Leistungsfaktor Phase 3 25 W L1 W L2 W L3 Wirkleistung Phase 1 Wirkleistung Phase 2 Wirkleistung Phase 3 26 A L1 A L2 A L3 Strom Phase 1 Strom Phase 2 Strom Phase 3 27 V L1-2 V L2-3 V L3-1 Spannung Phase 1-Phase 2 Spannung Phase 2-Phase 3 Spannung Phase 3-Phase 1 28 V L1 V L2 V L3 Spannung Phase 1 Spannung Phase 2 Spannung Phase 3 Hinweis: Die zuletzt angezeigte Seite wird im Programmiermodus gespeichert. Informationsmenü Page Seitentitel Angezeigte Information 1 IP o.o.-.- IP-Adresse (erster Teil) 2 IP -.-.o.o IP-Adresse (zweiter Teil) 3 Sub o.o.-.- Subnetzmaske (erster Teil) 4 Sub -.-.o.o Subnetzmaske (zweiter Teil) 5 Gateo.o.-.- Standard-Gateway (erster Teil) 6 Gate-.-.o.o Standard-Gateway (zweiter Teil) 7 Port Modbus TCP Port 8 DHCP DHCP aktiviert 9 Info Ethernet-Diagnose 10 Ut ratio Spannungswandler-/Stromwandlerverhältnis 11 CT ratio CT-Verhältnis 12 1P/2P/3P/3Pn (2-3-4-wire) dmd (time) System Anschluss (2-3-4-Draht) DMD Integrationszeit (Min.) 13 Pulse LED Impulsgewicht (Anzahl der kWh/kvarh pro Impuls) 14 Year Firmwarefreigabe Herstellungsjahr EM24 E1 - Bedienungsanleitung | CARLO GAVAZZI Controls SpA 43 Systemkonfiguration Einstellungen vom EM24 E1 Allgemeine Einstellungen Die verfügbaren Einstellungen hängen von der eingestellten Anwendung ab. Seitentitel Untermenü Beschreibung Werte Standardwert Cng PASS - Passwort ändern Von 0 bis 9999 0 Anwendung tYP.A tYP.b tYP.C tYP.d tYP.E tYP.F tYP.G tYP.H tYP.H Benutzer Von 0 bis 9999 1 Von 0 bis 9999 2 APPLiCAt User USEr 1 USEr 2 Von 0 bis 9999 3 dHCP - USEr 3 DHCP aktiviert oFF/on oFF IP Addr IP o.-.-.- IP-Adresse Von 000 bis 255 192 IP -.o.-.- Von 000 bis 255 168 IP -.-.o.- Von 000 bis 255 1 Von 000 bis 255 10 Von 000 bis 255 255 SUb -.o.-.- Von 000 bis 255 255 SUb -.-.o.- Von 000 bis 255 255 Von 000 bis 255 0 Von 000 bis 255 192 GAtE -.o.-.- Von 000 bis 255 168 GAtE -.-.o.- Von 000 bis 255 1 GAtE -.-.-.o Von 000 bis 255 1 IP -.-.-.o SUb SUb o.-.-.- Subnetzmaske SUb -.-.-.o GAtE GAtE o.-.-.- Standard-Gateway Port - MODBUS TCP Port SELECtor SELEC. 1 Die Seite wird nach Stellung des Wahlschalters unter den verfügbaren Seiten für jede Anwendung angezeigt (siehe „Vorderer Wahlschalter“ auf Seite 47) SELEC. 2 SELEC. 3 SELEC.LoC 502 Von 1 bis 28 1 Von 1 bis 28 25 Von 1 bis 28 28 Von 1 bis 28 3 3P.n 3P.1 2P 1P 3P 3P.n SYS - System Ut rAtio - Spannungswandlerverhältnis (VT) AV5: von 1 bis 6975 AV2: N/A 1 Ct rAtio - Stromwandlerverhältnis (CT) AV5: von 1 bis 6975 AV2: N/A 1 P int.ti - DMD Integrationszeit (Min) Von 1 bis 30 15 FiLtEr.S - Intervall für die Filteranwendung bezüglich der Vollausschläge (%) Von 0 bis 100 2 FiLtEr.Co - Filterkoeffizient Von 1 bis 32 2 End - Beenden und speichern - - Hinweis: MID (PFA, PFB): nur 3P.n Hinweis: Das Ut rAtio ist zur Kompatibilität mit anderen Versionen verfügbar, obwohl die AV5 Version nicht für die Benutzung mit Spannungswandlern vorgesehen ist. Daher soll es auf 1 eingestellt werden. 44 EM24 E1 - Bedienungsanleitung | CARLO GAVAZZI Controls SpA Wichtige Informationen Wichtige Informationen Verwaltung der Messungen Anwendungen Hinweis: Wenn eine Anwendung mit einfachem Anschluss ausgewählt wird, ist der Strom für die Berechnung der Wirkenergie immer integriert, sowohl bei der importierten als auch exportierten Leistung. Die Stromrichtung beeinträchtigt nicht die Messung. Wenn eine Anwendung ohne einfachen Anschluss ausgewählt wird, ist sowohl die importierte als auch die exportierte Wirkleistung verfügbar. Anwendung Messungen Einfacher Anschluss A System: • Phasensequenz • Phase-Nullleiter-Spannung • Frequenz • importierte Wirkenergie gesamt • Wirkleistung DMD und DMD max JA B System: • Phasensequenz • Phase-Nullleiter-Spannung • Frequenz • importierte Wirkenergie gesamt • Wirkleistung DMD und DMD max • importierte Blindenergie gesamt • Scheinleistung DMD und DMD max JA C System: • Phasensequenz • Phase-Nullleiter-Spannung • Frequenz • importierte Wirkenergie gesamt • Wirkleistung DMD und DMD max • importierte Wirk- und Blindenergie nach Tarif JA D Einphasig: • importierte Wirkenergie • Spannung JA E System: • Phasensequenz • Phase-Nullleiter-Spannung • Frequenz • importierte und exportierte Wirkenergie gesamt • Wirkleistung DMD und DMD max • Betriebsstundenzähler • Wirkleistung • Leistungsfaktor NEIN F System: • Phasensequenz • Phase-Nullleiter-Spannung • Frequenz • importierte und exportierte Wirkenergie gesamt • Wirkleistung DMD und DMD max • Phase-Phase-Spannung • Wirkenergie • Maximalstrom DMD • Partielle Wirkenergie • importierte und exportierte Blindenergie gesamt • Scheinleistung, DMD und DMD max • Partielle Blindenergie • Betriebsstundenzähler • Wirkleistung • Leistungsfaktor NEIN EM24 E1 - Bedienungsanleitung | CARLO GAVAZZI Controls SpA 45 Wichtige Informationen G System: • Phasensequenz • Phase-Nullleiter-Spannung • Frequenz • importierte Wirkenergie gesamt • Wirkleistung DMD und DMD max • Phase-Phase-Spannung • Wirkenergie • Maximalstrom DMD • Partielle Wirkenergie • importierte Blindenergie gesamt • Scheinleistung, DMD und DMD max • Blindenergie • Betriebsstundenzähler • Wirkleistung • Wirkleistung DMD • Blindleistung • Leistungsfaktor • importierte Wirk- und Blindenergie nach Tarif Einphasig: • Blindleistung pro Phase • Scheinleistung pro Phase • Leistungsfaktor pro Phase • Wirkleistung pro Phase • Strom pro Phase • Netznennspannung • Netz-Nullleiter-Spannung H System: • Phasensequenz • Phase-Nullleiter-Spannung • Frequenz • importierte und exportierte Wirkenergie gesamt • Wirkleistung DMD und DMD max • Phase-Phase-Spannung • Wirkenergie • Maximalstrom DMD • Partielle Wirkenergie • importierte und exportierte Blindenergie gesamt • Scheinleistung, DMD und DMD max • Blindenergie • Betriebsstundenzähler • Wirkleistung • Wirkleistung DMD • Blindleistung • Leistungsfaktor • importierte Wirk- und Blindenergie nach Tarif Einphasig: • Blindleistung pro Phase • Scheinleistung pro Phase • Leistungsfaktor pro Phase • Wirkleistung pro Phase • Strom pro Phase • Netznennspannung • Netz-Nullleiter-Spannung JA NEIN Programmierseiten Die folgende Tabelle zeigt welche Programmierseiten für jede Anwendung zur Verfügung stehen Page Anwendung A B C D E F G H Passwort ändern x x x x x x x x Anwendung x x x x x x x x Benutzer - - - x - - - - DHCP aktiviert x x x x x x x x IP-Adresse x x x x x x x x Subnetzmaske x x x x x x x x Standard-Gateway x x x x x x x x MODBUS TCP Port x x x x x x x x 46 EM24 E1 - Bedienungsanleitung | CARLO GAVAZZI Controls SpA Wichtige Informationen Wahlschalter x x x System x x x Spannungswandlerverhältnis x x x x x x x x x x x x x x x x x CT-Verhältnis x x x x x x x x Durchschnittsleistung Integrationszeit x x x - x x x x Filter S - - - - - x x x Filter Co - - - - - x x x End x x x x x x x x Tarifverwaltung Tarifverwaltung über Modbus-Befehl Ändern Sie den Tarif durch Eingabe des Wertes, der gemäß folgender Tabelle dem aktuellen Tarif entspricht, in das Register 1201Fh: Aktueller Tarif Registerwert T1 1 T2 2 T3 3 T4 4 Deaktivierung der Tarifverwaltung Stellen Sie die Tarifverwaltung auf deaktiviert ein oder setzen Sie den Wert im Register 1201Fh auf 0 (Standardwert). Front-LED und Wahlschalter Front-LED Die rote Front-LED blinkt proportional zum importierten Wirkenergieverbrauch falls sich der Wahlschalter in ven Blindleistungsenergieverbrauch in kvarh - 1 - 2 Position befindet sowie zum indukti- Position befindet. Jede Art negativer (exportierter) Energie wird nicht von der Front-LED verwaltet. Vorderer Wahlschalter • Lock Position: Der vordere Wahlschalter verhindert den Zugriff auf den Programmiermodus • 1, 2, kvarh Position: Schnellzugriff auf die Messungsseiten. Jede Position steht in Verbindung mit einer Messungsseite gemäß folgender Tabelle: Anwendung Wahlschalterposition Lock 3 1,2,3 1 B, C, E, F, G, H Lock, 1, 2, kvarh Kann von 1 bis 28 eingestellt werden C Lock, 1, 2, kvarh Kann von 1 bis 28 eingestellt werden Lock 28 1 15 2 16 3 17 A D Verfügbare Seite EM24 E1 - Bedienungsanleitung | CARLO GAVAZZI Controls SpA 47 Instandhaltung und Entsorgung Instandhaltung und Entsorgung Reinigung Benutzen Sie ein leicht angefeuchtetes Tuch zum Reinigen des Displays. Benutzen Sie keine Scheuer- oder Lösungsmittel. Verantwortlichkeit für Entsorgung Dieses Produkt muss bei einem geeigneten von der Regierung oder lokalen öffentlichen Autoritäten anerkannten Recyclingbetrieb entsorgt werden. Ordnungsgemäße Entsorgung und Recycling tragen zur Vermeidung möglicher schädlicher Folgen für Umwelt und Personen bei. 48 EM24 E1 - Bedienungsanleitung | CARLO GAVAZZI Controls SpA CARLO GAVAZZI Controls SpA via Safforze, 8 32100 Belluno (BL) Italien www.gavazziautomation.com [email protected] Tel.: +39 0437 355811 Fax: +39 0437 355880 EM24 E1 - Betriebsanleitung 2018-06 | Copyright © 2018 EM24 E1 Analyseur d’énergie triphasé MANUEL D’EMPLOI Sommaire EM24 E1 53 Introduction53 Description53 UCS (Logiciel de configuration universelle) 53 Utilisation EM24 E1 54 Introduction54 Affichage 54 Configuration des paramètres du réseau 55 Paramétrage du réseau via DHCP 55 Paramétrage du réseau sans DHCP 55 Travailler avec l’EM24 E1 56 Travailler avec le menu mesures/infos 56 Travailler avec le menu paramètres 56 Réinitialiser le compteur d’énergie partiel 56 Configurer un paramètre 57 Description du menu 58 Menu Mesures - pages mesures 58 Menu informations 59 Paramètres d’EM24 E1 60 Paramètres généraux 60 Informations essentielles 61 Applications 61 Pages de programmation 62 Gérer les tarifs via la commande Modbus 63 Désactivation de la gestion tarifaire 63 LED frontale 63 Sélecteur frontal 63 Entretien et élimination 64 EM24 E1 - Manuel d’instructions | CARLO GAVAZZI Controls SpA 51 Propriété des informations Copyright © 2018, CARLO GAVAZZI Controls SpA Tous droits réservés dans tous les pays. CARLO GAVAZZI Controls SpA se réserve le droit d’apporter des modifications ou des améliorations à la documentation relative sans préavis. Messages de sécurité La section suivante décrit les avertissements relatifs à la sécurité de l’utilisateur et du dispositif inclus dans ce document : AVIS : indique les obligations qui, si non observées, peuvent entraîner l’endommagement du dispositif. ATTENTION! Indique une situation de risque qui, si elle n’est pas évitée, peut entraîner la perte de données. IMPORTANT : fournit des informations essentielles pour compléter la tâche qui ne doivent pas être négligées. Avertissements généraux Ce manuel fait partie intégrante du produit et l’accompagne pendant toute sa durée de vie. Il doit être consulté pour toutes les situations liées à la configuration, et à l’entretien. Pour cette raison, il devra toujours être accessible aux opérateurs. AVERTISSEMENT : personne n’est autorisé à ouvrir l’analyseur. Cette opération est réservée exclusivement au personnel du service technique CARLO GAVAZZI. La protection peut être compromise si l’instrument est utilisé d’une manière non spécifiée par le fabricant. Entretien et garantie En cas de dysfonctionnement, de panne ou de besoin d’informations, contactez la filiale ou le distributeur CARLO GAVAZZI de votre pays. L’installation et l’utilisation d’analyseurs autres que ceux indiqués dans les instructions fournies annulent la garantie. Télécharger Ce manuel www.productselection.net/MANUALS/UK/EM24_im_use.pdf Instructions d’installation - EM24 www.productselection.net/MANUALS/UK/EM24_im_inst.pdf logiciel UCS www.productselection.net/Download/UK/ucs.zip 52 EM24 E1 - Manuel d’instructions | CARLO GAVAZZI Controls SpA EM24 E1 Introduction L’EM24 est un analyseur d’énergie triphasé pour montage sur rail DIN avec joystick de configuration, sélecteur frontal et écran à cristaux liquides. La version à connexion directe (AV2) permet de mesurer jusqu’à 65 A, la version à connexion CT (AV5) permet de mesurer jusqu’à 34875 A au moyen de transformateurs de courant (sortie secondaire 5 A). La fonction DHCP est capable d’accélérer la mise en service et tous les paramètres de configuration peuvent être configurés via UCS. Description AV2 Pièce AV5 Description A Affichage LCD B Connexions tension/courants C Joystick D Sélecteur avec broche pour scellé MID (bloc de programmation) E Entrées/sorties ou port de communication F Broches pour scellé MID (couvercles de protection inclus) UCS (Logiciel de configuration universelle) Le bureau UCS est disponible en téléchargement gratuit. Il peut être connecté à l’EM24 via Ethernet (Modbus TCP/IP). Ce qui suit est possible avec UCS : • configurer l’EM24 (en ligne ou hors ligne) • afficher l’état du système pour les diagnostics et les vérifications de configuration vue d’ensemble de la fonction EM24 E1 - Manuel d’instructions | CARLO GAVAZZI Controls SpA 53 Utilisation EM24 E1 Introduction EM24 est organisé en deux menus : • menu de mesure et d’information : pages d’affichage des pages de mesure, des informations relatives aux paramètres programmés et de la version du micrologiciel de l’instrument • menu paramètres : pages utilisées pour définir les paramètres Affichage L’écran est réparti en 3 lignes. Symbole Description Affichage de la tension simple Affichage de la tension système phase à phase Affichage des valeurs maximales Identifiant utilisateur Affichage des variables système Affichage des variables dmd EEEE 54 EM24 E1 - Manuel d’instructions | CARLO GAVAZZI Controls SpA Surcharge. Remarque : les fonctions de calcul DMD, du compteur d’heures et des compteurs d’énergie sont bloquées et les sorties d’alarme sont activées. L’indication « EEEE » dans une variable monophasé implique automatiquement la condition de surcharge de la variable système en question, et l’indication PF est forcée sur « 0,000 ». Configuration des paramètres du réseau Paramétrage du réseau via DHCP Étape Action 1 Installer l’EM24 2 Activer le DHCP et quitter sortir à l’aide de l’option Fin 3 Connecter l’EM24 au réseau LAN auquel le PC est connecté 4 Accéder aux pages Infos pour afficher les paramètres réseau assignés 5 Démarrer le logiciel UCS et se connecter au EM24 via Connexion manuelle > Modbus TCP 6 Saisir l’adresse IP affichée sur la page Infos (voir point 4) 7 Accéder aux paramètres, désactiver DHCP et attribuer les paramètres réseau requis (attribués par l’administrateur réseau) Paramétrage du réseau sans DHCP Étape Action 1 Installer l’EM24 2 Désactiver DHCP (réglage par défaut) 3 Connecter le PC à l’EM24 par le câble Ethernet (connexion point à point) 4 Régler les propriétés de réseau du PC comme suit : • adresse IP statique • Adresse IP de la même classe que l’EM24, par exemple si l’IP de l’EM24 est 192.168.1.10 (par défaut), vous pouvez définir l’adresse du PC sur 192.168.1.20 • Masque de sous-réseau : 255.255.255.0 • Passerelle : pas nécessaire 5 Démarrer le logiciel UCS et se connecter à l’EM24 via Connexion manuelle> Modbus TCP, saisir l’adresse IP de l’EM24 (192.168.1.10 par défaut) 6 Accéder aux paramètres et saisir les paramètres réseau requis 7 Débrancher le câble Ethernet et connecter l’EM24 au réseau auquel le maître Modbus est connecté EM24 E1 - Manuel d’instructions | CARLO GAVAZZI Controls SpA 55 Utilisation EM24 E1 Travailler avec l’EM24 E1 Travailler avec le menu mesures/infos vers la page de mesure suivante vers le menu paramètres vers la page d’infos précédente vers la page d’infos suivante vers la page de mesure précédente Travailler avec le menu paramètres augmenter la valeur d’un paramètre modifier/confirmer vers la page précédente vers la page suivante diminuer la valeur d’un paramètre Réinitialiser le compteur d’énergie partiel Étape Action 1 Appuyer sur le bouton pendant au moins 3 secondes 2 Sur la page PASS, sélectionner le mot de passe 1357 3 Confirmer l’opération 4 Sur la page rESEt, régler sur YES 5 Confirmer l’opération 56 EM24 E1 - Manuel d’instructions | CARLO GAVAZZI Controls SpA Bouton Utilisation EM24 E1 Étape Bouton Action 6 Sur la page EnE PrES, régler sur YES 7 Confirmer l’opération Configurer un paramètre Exemple de procédure : comment configurer Ct rAtio=20 et enregistrer les modifications. Étape Action 1 Mettre l’analyseur d’énergie sous tension 2 Appuyer sur le joystick pendant au moins 3 secondes 3 Sur la page PASS?, sélectionner le bon mot de passe (0 par défaut) 4 Confirmer l’opération 5 Faire défiler les pages jusqu’à Ct rAtio 6 Accéder au mode d’édition 7 Sélectionner 20 8 Confirmer l’opération 9 Faire défiler les pages jusqu’à Fin pour quitter Bouton EM24 E1 - Manuel d’instructions | CARLO GAVAZZI Controls SpA 57 Utilisation EM24 E1 Description du menu Menu Mesures - pages mesures Les pages affichées dépendent de l’ensemble de l’application. Page Mesures affichées L1-L2-L3 VLNΣ Hz Séquence de phase Tension phase-neutre système Fréquence 2 L1-L2-L3 VLLΣ Hz Séquence de phase Tension phase-phase système Fréquence 3 Tot kWh (+) WΣ dmd WΣ dmd max Énergie active importée totale Puissance active système dmd Puissance active système dmd max 4 kWh A dmd max PArt Énergie active Courant dmd maximal Énergie active partielle 5 Tot kvarh (+) VAΣ dmd VAΣ dmd max Énergie réactive importée totale Puissance apparente système dmd Puissance apparente système dmd max 6 kvarh VAΣ PArt Énergie réactive Puissance apparente système Énergie réactive partielle 7 kWh (+) t1 WΣ dmd Énergie active importée, tarif 1 Puissance active système dmd 8 kWh (+) t2 WΣ dmd Énergie active importée, tarif 2 Puissance active système dmd 9 kWh (+) t3 WΣ dmd Énergie active importée, tarif 3 Puissance active système dmd 10 kWh (+) t4 WΣ dmd Énergie active importée, tarif 4 Puissance active système dmd 11 kvarh (+) t1 WΣ dmd Énergie réactive importée, tarif 1 WΣ dmd 12 kvarh (+) t2 WΣ dmd Énergie réactive importée, tarif 2 WΣ dmd 13 kvarh (+) t3 WΣ dmd Énergie réactive importée, tarif 3 WΣ dmd 14 kvarh (+) t4 WΣ dmd Énergie réactive importée, tarif 4 WΣ dmd 15 kWh (+) X WX User X Énergie active importée Puissance active Utilisateur 16 kWh (+) Y WY User Y Énergie active importée Puissance active Utilisateur 17 kWh (+) Z WZ User Z Énergie active importée Puissance active Utilisateur 18 Total kvarh (-) VAΣ dmd VAΣ dmd max Énergie réactive exportée totale Puissance apparente système dmd Puissance apparente système dmd max 19 Total kWh (-) WΣ dmd WΣ dmd max Énergie active exportée totale Puissance active système dmd Puissance active système dmd max 1 58 EM24 E1 - Manuel d’instructions | CARLO GAVAZZI Controls SpA Description Configurer le système 20 Hours WΣ PFΣ Total heures de fonctionnement de la charge Puissance active système Facteur de puissance système 21 Hours VArΣ PFΣ Total heures de fonctionnement de la charge Puissance réactive système Facteur de puissance système 22 var L1 var L2 var L3 Puissance réactive phase 1 Puissance réactive phase 2 Puissance réactive phase 3 23 VA L1 VA L2 VA L3 Puissance apparente phase 1 Puissance apparente phase 2 Puissance apparente phase 3 24 PF L1 PF L2 PF L3 Facteur de puissance phase 1 Facteur de puissance phase 2 Facteur de puissance phase 3 25 W L1 W L2 W L3 Puissance active phase 1 Puissance active phase 2 Puissance active phase 3 26 A L1 A L2 A L3 Courant phase 1 Courant phase 2 Courant phase 3 27 V L1-2 V L2-3 V L3-1 Tension phase 1-phase 2 Tension phase 2-phase 3 Tension phase 3-phase 1 28 V L1 V L2 V L3 Tension de phase 1 Tension de phase 2 Tension de phase 3 Remarque : en mode de programmation, la dernière page affichée est stockée. Menu informations Page Titre page Informations affichées 1 IP o.o.-.- Adresse IP (première partie) 2 IP -.-.o.o Adresse IP (deuxième partie) 3 Sub o.o.-.- Masque de sous-réseau (première partie) 4 Sub -.-.o.o Masque de sous-réseau (deuxième partie) 5 Gateo.o.-.- Passerelle par défaut (première partie) 6 Gate-.-.o.o Passerelle par défaut (deuxième partie) 7 Port Port Modbus TCP 8 DHCP Activation du DHCP 9 Info Diagnostic Ethernet 10 Ut ratio Rapport transformateur de tension (TT)/de puissance (TP) 11 CT ratio Rapport CT 12 1P/2P/3P/3Pn (2-3-4-wire) dmd (time) Système Connexion (à 2-3-4 fils) Temps d’intégration dmd (min.) 13 Pulse Poids d’impulsion LED (Nombre de kWh/kvarh par impulsion) 14 Year Version du micrologiciel Année de production EM24 E1 - Manuel d’instructions | CARLO GAVAZZI Controls SpA 59 Configurer le système Paramètres d’EM24 E1 Paramètres généraux Les paramètres disponibles dépendent de l’ensemble de l’application. Titre page Sous-menu Description Valeur Valeur par défaut Cng PASS - Changer le mot de passe De 0 à 9999 0 Application tYP.A tYP.b tYP.C tYP.d tYP.E tYP.F tYP.G tYP.H tYP.H Utilisateur De 0 à 9999 1 De 0 à 9999 2 APPLiCAt User USEr 1 USEr 2 De 0 à 9999 3 dHCP - USEr 3 Activation du DHCP oFF/on oFF IP Addr IP o.-.-.- Adresse IP SUb GAtE De 000 à 255 192 IP -.o.-.- De 000 à 255 168 IP -.-.o.- De 000 à 255 1 IP -.-.-.o De 000 à 255 10 SUb o.-.-.- De 000 à 255 255 SUb -.o.-.- De 000 à 255 255 SUb -.-.o.- De 000 à 255 255 SUb -.-.-.o De 000 à 255 0 GAtE o.-.-.- Masque de sous-réseau De 000 à 255 192 GAtE -.o.-.- Passerelle par défaut De 000 à 255 168 GAtE -.-.o.- De 000 à 255 1 De 000 à 255 1 GAtE -.-.-.o Port - Port MODBUS TCP SELECtor SELEC. 1 Page affichée selon la position du sélecteur parmi les pages disponibles pour chaque application (voir «Sélecteur frontal» à la page 63) SELEC. 2 SELEC. 3 SELEC.LoC 502 De 1 à 28 1 De 1 à 28 25 De 1 à 28 28 De 1 à 28 3 3P.n 3P.1 2P 1P 3P 3P.n SYS - Système Ut rAtio - Rapport transformateur de tension (TT) AV5 : de 1 à 6975 AV2 : S.O. 1 Ct rAtio - Rapport de transformateur courant (CT) AV5 : de 1 à 6975 AV2 : S.O. 1 P int.ti - Temps d’intégration dmd (min.) De 1 à 30 15 FiLtEr.S - Intervalle d’intervention du filtre par rapport à la pleine échelle (%) De 0 à 100 2 FiLtEr.Co - Coefficient du filtre De 1 à 32 2 End - Quitter et enregistrer - - Remarque : MID (PFA, PFB) : uniquement 3P.n Remarque : la valeur Ut rAtio est disponible pour assurer la compatibilité avec les autres versions même si la version AV5 n’est pas destinée à être utilisée avec des transformateurs de tension. Elle doit donc être réglée sur 1. 60 EM24 E1 - Manuel d’instructions | CARLO GAVAZZI Controls SpA Informations essentielles Informations essentielles Gestion des mesures Applications Remarque : si une application avec une connexion facile est sélectionnée, pour le calcul de l’énergie active, la puissance est toujours intégrée, à la fois dans le cas de l’alimentation importée et exportée. La direction actuelle n’a pas d’incidence sur la mesure. Si une application sans connexion facile est sélectionnée, les alimentations active importée et exportée sont disponibles. Application Mesures Connexion simple A Système : • séquence de phase • tension phase-neutre • fréquence • énergie active importée totale • puissance active dmd et dmd max OUI B Système : • séquence de phase • tension phase-neutre • fréquence • énergie active importée totale • puissance active dmd et dmd max • énergie réactive importée totale • puissance apparente dmd et dmd max OUI C Système : • séquence de phase • tension phase-neutre • fréquence • énergie active importée totale • puissance active dmd et dmd max • énergie importée active et réactive par tarif OUI D Monophasé: • énergie active importée • tension OUI E Système : • séquence de phase • tension phase-neutre • fréquence • énergie active importée et exportée totale • puissance active dmd et dmd max • compte-heures • puissance active • facteur de puissance NO F Système : • séquence de phase • tension phase-neutre • fréquence • énergie active importée et exportée totale • puissance active dmd et dmd max • tension phase-phase • énergie active • courant dmd maximal • énergie active partielle • énergie réactive importée et exportée totale • puissance apparente, dmd et dmd max • énergie réactive partielle • compte-heures • puissance active • facteur de puissance NO EM24 E1 - Manuel d’instructions | CARLO GAVAZZI Controls SpA 61 Informations essentielles G Système : • séquence de phase • tension phase-neutre • fréquence • énergie active importée totale • puissance active dmd et dmd max • tension phase-phase • énergie active • courant dmd maximal • énergie active partielle • énergie réactive importée totale • puissance apparente, dmd et dmd max • énergie réactive • compte-heures • puissance active • puissance active dmd • puissance réactive • facteur de puissance • énergie importée active et réactive par tarif Monophasé: • puissance réactive par phase • puissance apparente par phase • facteur de puissance par phase • puissance active par phase • courant par phase • tensions ligne-ligne • tensions ligne-neutre OUI H Système : • séquence de phase • tension phase-neutre • fréquence • énergie active importée et exportée totale • puissance active dmd et dmd max • tension phase-phase • énergie active • courant dmd maximal • énergie active partielle • énergie réactive importée et exportée totale • puissance apparente, dmd et dmd max • énergie réactive • compte-heures • puissance active • puissance active dmd • puissance réactive • facteur de puissance • énergie importée active et réactive par tarif Monophasé: • puissance réactive par phase • puissance apparente par phase • facteur de puissance par phase • puissance active par phase • courant par phase • tensions ligne-ligne • tensions ligne-neutre NO Pages de programmation Le tableau ci-dessous affiche les pages de programmation disponibles pour chaque application Page Application A B C D E F G H Changer le mot de passe x x x x x x x x Application x x x x x x x x Utilisateur - - - x - - - - Activation du DHCP x x x x x x x x Adresse IP x x x x x x x x Masque de sous-réseau x x x x x x x x Passerelle par défaut x x x x x x x x Port MODBUS TCP x x x x x x x x 62 EM24 E1 - Manuel d’instructions | CARLO GAVAZZI Controls SpA Informations essentielles Sélecteur x x x Système x x x Rapport transformateur de tension x x x x x x x x x x x x x x x x x Rapport CT x x x x x x x x Temps d’intégration de puissance moyenne x x x - x x x x Filtre S - - - - - x x x Filtre Co - - - - - x x x Fin x x x x x x x x Gestion tarifaire Gérer les tarifs via la commande Modbus Modifier le tarif en entrant la valeur correspondant au tarif actuel selon le tableau suivant dans le registre 1201Fh : Tarif actuel Valeur de registre T1 1 T2 2 T3 3 T4 4 Désactivation de la gestion tarifaire Paramétrer la gestion des tarifs comme désactivée ou saisir 0 (valeur par défaut) dans le registre 1201Fh. LED frontale et sélecteur LED frontale La LED rouge frontale clignote proportionnellement à la consommation d’énergie importée active si le sélecteur est en position tion d’énergie réactive à induction en position kvarh . La LED frontale ne gère pas tous les types d’énergie (exporté) négative. 1 - 2 , et à la consomma- Sélecteur frontal • Position Verrouiller • Position 1, 2, kvarh Application A : le sélecteur frontal empêche d’accéder au mode de programmation : accès rapide aux pages de mesure. Chaque position est associée à une seule page de mesure conformément au tableau suivant : Position du sélecteur Verrouiller 3 Page disponible 1,2,3 1 B, C, E, F, G, H Verrouiller, 1, 2, kvarh Peut être réglée de 1 à 28 C Verrouiller, 1, 2, kvarh Peut être réglée de 1 à 28 Verrouiller 28 1 15 2 16 3 17 D EM24 E1 - Manuel d’instructions | CARLO GAVAZZI Controls SpA 63 Entretien et élimination Entretien et élimination Nettoyage Utiliser un chiffon humide pour nettoyer l’afficheur. Ne pas utiliser d’abrasifs ou de solvants. Responsabilité de l’élimination Le produit doit être éliminé dans les déchetteries spécifiés par le gouvernement ou les autorités locales. Une élimination et un recyclage corrects contribueront à prévenir des conséquences potentiellement nuisibles pour l’environnement et les personnes. 64 EM24 E1 - Manuel d’instructions | CARLO GAVAZZI Controls SpA CARLO GAVAZZI Controls SpA via Safforze, 8 32100 Belluno (BL) Italy www.gavazziautomation.com [email protected] info : +39 0437 355811 fax : +86 755 355880 EM24 E1 - Manuel d’emploi 2018-06 | Copyright © 2018 EM24 E1 Analizador de energía trifásico INSTRUCCIONES DE USO Contenido EM24 E1 69 Introducción69 Descripción69 UCS (software de configuración universal) 69 Uso del EM24 E1 70 Introducción70 Display70 Ajuste de los parámetros de la red 71 Ajuste de los parámetros de red a través de DHCP 71 Ajuste de los parámetros de red sin DHCP 71 Operaciones con el EM24 E1 72 Operaciones con el menú de medición/información 72 Operaciones con el menú de configuración 72 Reinicio del medidor de la energía parcial 72 Establecimiento de un parámetro 73 Descripción del menú 74 Menú de medición - páginas de medición 74 Menú de información 75 Ajustes desde EM24 E1 76 Ajustes generales 76 Información esencial 77 Aplicaciones77 Páginas de programación 78 Gestión de tarifas a través de un comando Modbus 79 Inhabilitación de la gestión de tarifas 79 LED frontal 79 Selector frontal 79 Mantenimiento y eliminación 80 EM24 E1 - Manual de instrucciones | CARLO GAVAZZI Controls SpA 67 Información sobre propiedad Copyright © 2018, CARLO GAVAZZI Controls SpA Todos los derechos reservados en todos los países. CARLO GAVAZZI Controls SpA se reserva el derecho a realizar modificaciones o mejoras en la documentación relativa sin obligación de aviso previo. Mensajes de seguridad La siguiente sección describe las advertencias relacionadas con la seguridad de los usuarios y los dispositivos incluidos en este documento: ADVERTENCIA: indica obligaciones que si no se cumplen pueden provocar daños en el dispositivo. ¡CUIDADO! Indica una situación de riesgo que, si no se evita, puede provocar pérdidas de datos. IMPORTANTE: proporciona información esencial sobre la conclusión de una tarea que no debe pasarse por alto. Advertencias generales Este manual forma parte integral del producto y debe acompañarlo a lo largo de toda su vida útil. Debe consultarse para todo lo que tenga que ver con su configuración, uso y mantenimiento. Por este motivo, los operadores deben disponer de acceso a él en todo momento. ADVERTENCIA: nadie está autorizado a abrir el analizador. Esta operación está exclusivamente reservada para el personal de servicio técnico de CARLO GAVAZZI. El uso del instrumento de un modo no especificado por el fabricante podría afectar a la protección. Reparación y garantía Si se producen fallos o anomalías en el funcionamiento o quiere solicitar información, póngase en contacto con la filial o distribuidor de CARLO GAVAZZI de su país. Cualquier instalación o uso de los analizadores que no se ajuste a las instrucciones facilitadas invalidará la garantía. Descargar Este manual www.productselection.net/MANUALS/UK/EM24_im_use.pdf Instrucciones de instalación - EM24 www.productselection.net/MANUALS/UK/EM24_im_inst.pdf Software UCS www.productselection.net/Download/UK/ucs.zip 68 EM24 E1 - Manual de instrucciones | CARLO GAVAZZI Controls SpA EM24 E1 Introducción El EM24 es un analizador de energía trifásico para instalación en carril DIN con configuración de palanca de mando, selector frontal y pantalla LCD. La versión para conexión directa (AV2) permite medir hasta 65 A, la versión para conexión CT (AV5) permite medir hasta 34875 A a través de transformadores de corriente (salida secundaria 5 A). La función DHCP permite acelerar la puesta en servicio y todos los parámetros de configuración se pueden establecer mediante UCS. Descripción AV2 Parte AV5 Descripción A Pantalla LCD B Conexiones de tensión/intensidad C Palanca de mando D Selector con patilla para cierre MID (bloque de programación) E Entradas/salidas o puerto de comunicación F Patillas para cierre MID (cubiertas de protección incluidas) UCS (software de configuración universal) El software UCS de escritorio se encuentra disponible para su descarga de manera gratuita. Se puede conectar al EM24 a través de Ethernet (Modbus TCP/IP) . El UCS permite llevar a cabo estas acciones: • configurar el EM24 (en línea o sin conexión) • ver el estado del sistema con fines de diagnóstico y comprobación de la configuración descripción general de la función EM24 E1 - Manual de instrucciones | CARLO GAVAZZI Controls SpA 69 Uso del EM24 E1 Introducción El EM24 se organiza en dos menús: • menú de información y medición: páginas utilizadas para visualizar las páginas de medición, la información relevante para los parámetros programados y la versión del firmware del instrumento • menú de ajustes: páginas utilizadas para configurar los parámetros Display La pantalla se divide en 3 líneas. Símbolo Descripción Visualización de la tensión del sistema fase-a-neutro Visualización de la tensión del sistema fase-a-fase Visualización de los valores máx. Id. del usuario Visualización de las variables del sistema Visualización de las variables dmd EEEE 70 EM24 E1 - Manual de instrucciones | CARLO GAVAZZI Controls SpA Desbordamiento. Nota: las funciones del cálculo DMD, el contador horario y los medidores de energía se han inhibido y las salidas de alarma se han activado. La indicación “EEEE” en una variable monofásica implica automáticamente la condición de desbordamiento de la variable del sistema en cuestión y la indicación PF se fuerza a “0.000”. Ajuste de los parámetros de la red Ajuste de los parámetros de red a través de DHCP Paso Acción 1 Instale el EM24 2 Habilite la función DHCP y salga con End 3 Conecte el EM24 a la red LAN a la que esté conectado el PC 4 Acceda a las páginas Info para ver los parámetros de red asignados 5 Inicie el software UCS y conéctelo al EM24 a través de Manual connection> Modbus TCP 6 Introduzca la dirección IP que aparece en la página Info (véase el punto 4) 7 Acceda a los ajustes, inhabilite DHCP y asigne los parámetros de red necesarios (asignados por el administrador de la red) Ajuste de los parámetros de red sin DHCP Paso Acción 1 Instale el EM24 2 Inhabilite DHCP (ajuste predeterminado) 3 Conecte el PC al EM24 a través del cable Ethernet (conexión de punto a punto) 4 Configure las propiedades de la red del PC de este modo: • Dirección IP estática • Dirección IP de la misma clase que el EM24; por ejemplo, si la IP del EM24 es 192.168.1.10 (predeterminada), puede configurar la dirección del PC como 192.168.1.20 • Máscara de subred: 255.255.255.0 • Pasarela: no es necesaria 5 Inicie el software UCS y conecte con el EM24 a través de Manual connection> Modbus TCP; introduzca la dirección IP del EM24 (192.168.1.10 por defecto) 6 Acceda a los ajustes e introduzca los parámetros de red necesarios 7 Desconecte el cable Ethernet y conecte el EM24 a la red a la que esté conectado el maestro Modbus EM24 E1 - Manual de instrucciones | CARLO GAVAZZI Controls SpA 71 Uso del EM24 E1 Operaciones con el EM24 E1 Operaciones con el menú de medición/información a la siguiente página de medición al menú de ajustes a la página de información anterior a la siguiente página de información a la página de medición anterior Operaciones con el menú de configuración incrementar un valor del parámetro editar/confirmar a la siguiente página a la página anterior disminuir un valor del parámetro Reinicio del medidor de la energía parcial Paso Acción 1 Pulse el botón durante un mínimo de 3 segundos 2 En la página PASS, configure la contraseña 1357 3 Confirmar operación 4 En la página rESEt, configure YES 5 Confirmar operación 72 EM24 E1 - Manual de instrucciones | CARLO GAVAZZI Controls SpA Botón Uso del EM24 E1 Paso Botón Acción 6 En la página EnE PrES, configure YES 7 Confirmar operación Establecimiento de un parámetro Procedimiento de ejemplo: cómo configurar Ct rAtio=20 y guardar los cambios. Paso Botón Acción 1 Encienda el analizador de energía 2 Pulse la palanca de mando durante un mínimo de 3 segundos 3 En la página PASS?, seleccione la contraseña correcta (valor predeterminado 0) 4 Confirmar operación 5 Recorra las páginas hasta llegar a Ct rAtio 6 Acceda al modo de edición 7 Seleccione 20 8 Confirmar operación 9 Recorra las páginas hasta llegar a End para salir EM24 E1 - Manual de instrucciones | CARLO GAVAZZI Controls SpA 73 Uso del EM24 E1 Descripción del menú Menú de medición - páginas de medición Las páginas mostradas dependerán del conjunto de la aplicación. Page Mediciones mostradas L1-L2-L3 VLNΣ Hz Secuencia de fase Tensión fase-neutro del sistema Frecuencia 2 L1-L2-L3 VLLΣ Hz Secuencia de fase Tensión fase-fase del sistema Frecuencia 3 Tot kWh (+) WΣ dmd WΣ dmd max Energía activa consumida total Potencia activa del sistema dmd Potencia activa del sistema dmd máx. 4 kWh A dmd max PArt Energía activa Intensidad dmd máx. Energía activa parcial 5 Tot kvarh (+) VAΣ dmd VAΣ dmd max Energía reactiva consumida total Potencia aparente del sistema dmd Potencia aparente del sistema dmd máx. 6 kvarh VAΣ PArt Energía reactiva Potencia aparente del sistema Energía reactiva parcial 7 kWh (+) t1 WΣ dmd Energía activa consumida, tarifa 1 Potencia activa del sistema dmd 8 kWh (+) t2 WΣ dmd Energía activa consumida, tarifa 2 Potencia activa del sistema dmd 9 kWh (+) t3 WΣ dmd Energía activa consumida, tarifa 3 Potencia activa del sistema dmd 10 kWh (+) t4 WΣ dmd Energía activa consumida, tarifa 4 Potencia activa del sistema dmd 11 kvarh (+) t1 WΣ dmd Energía reactiva consumida, tarifa 1 WΣ dmd 12 kvarh (+) t2 WΣ dmd Energía reactiva consumida, tarifa 2 WΣ dmd 13 kvarh (+) t3 WΣ dmd Energía reactiva consumida, tarifa 3 WΣ dmd 14 kvarh (+) t4 WΣ dmd Energía reactiva consumida, tarifa 4 WΣ dmd 15 kWh (+) X WX User X Energía activa consumida Potencia activa Usuario 16 kWh (+) Y WY User Y Energía activa consumida Potencia activa Usuario 17 kWh (+) Z WZ User Z Energía activa consumida Potencia activa Usuario 18 Total kvarh (-) VAΣ dmd VAΣ dmd max Energía reactiva generada total Potencia aparente del sistema dmd Potencia aparente del sistema dmd máx. 19 Total kWh (-) WΣ dmd WΣ dmd max Energía activa generada total Potencia activa del sistema dmd Potencia activa del sistema dmd máx. 1 74 EM24 E1 - Manual de instrucciones | CARLO GAVAZZI Controls SpA Descripción Configuración del sistema 20 Hours WΣ PFΣ Horas del funcionamiento de la carga totales Potencia activa del sistema Factor de potencia del sistema 21 Hours VArΣ PFΣ Horas del funcionamiento de la carga totales Potencia reactiva del sistema Factor de potencia del sistema 22 var L1 var L2 var L3 Potencia reactiva fase 1 Potencia reactiva fase 2 Potencia reactiva fase 3 23 VA L1 VA L2 VA L3 Potencia aparente fase 1 Potencia aparente fase 2 Potencia aparente fase 3 24 PF L1 PF L2 PF L3 Factor de potencia fase 1 Factor de potencia fase 2 Factor de potencia fase 3 25 W L1 W L2 W L3 Potencia activa fase 1 Potencia activa fase 2 Potencia activa fase 3 26 A L1 A L2 A L3 Intensidad fase 1 Intensidad fase 2 Intensidad fase 3 27 V L1-2 V L2-3 V L3-1 Tensión fase 1-fase 2 Tensión fase 2-fase 3 Tensión fase 3-fase 1 28 V L1 V L2 V L3 Tensión de fase 1 Tensión de fase 2 Tensión de fase 3 Nota: en el modo de programación, se guarda la última página mostrada. Menú de información Page Título de la página Información mostrada 1 IP o.o.-.- Dirección IP (primera parte) 2 IP -.-.o.o Dirección IP (segunda parte) 3 Sub o.o.-.- Máscara de subred (primera parte) 4 Sub -.-.o.o Máscara de subred (segunda parte) 5 Gateo.o.-.- Pasarela predeterminada (primera parte) 6 Gate-.-.o.o Pasarela predeterminada (segunda parte) 7 Port Puerto modbus TCP 8 DHCP Habilitación de DHCP 9 Info Diagnóstico Ethernet 10 Ut ratio Relación transformador de tensión/potencia 11 CT ratio Ratio CT 12 1P/2P/3P/3Pn (2-3-4-wire) dmd (time) Sistema Conexión (2, 3, 4 alambres) Tiempo de integración dmd (min) 13 Pulse Proporción de pulsos LED (número de kWh/kvarh por pulso) 14 Year Versión del firmware Año de producción EM24 E1 - Manual de instrucciones | CARLO GAVAZZI Controls SpA 75 Configuración del sistema Ajustes desde EM24 E1 Ajustes generales Los ajustes disponibles dependerán del conjunto de la aplicación. Título de la página Submenú Descripción Valores Valor por defecto Cng PASS - Cambie la contraseña Desde 0 hasta 9999 0 Aplicación tYP.A tYP.b tYP.C tYP.d tYP.E tYP.F tYP.G tYP.H tYP.H Usuario Desde 0 hasta 9999 1 Desde 0 hasta 9999 2 APPLiCAt User USEr 1 USEr 2 Desde 0 hasta 9999 3 dHCP - USEr 3 Habilitación de DHCP oFF/on oFF IP Addr IP o.-.-.- Dirección IP SUb GAtE Desde 000 hasta 255 192 IP -.o.-.- Desde 000 hasta 255 168 IP -.-.o.- Desde 000 hasta 255 1 IP -.-.-.o Desde 000 hasta 255 10 SUb o.-.-.- Desde 000 hasta 255 255 SUb -.o.-.- Desde 000 hasta 255 255 SUb -.-.o.- Desde 000 hasta 255 255 SUb -.-.-.o Desde 000 hasta 255 0 GAtE o.-.-.- Máscara de subred Desde 000 hasta 255 192 GAtE -.o.-.- Puerta de enlace predeterminada Desde 000 hasta 255 168 GAtE -.-.o.- Desde 000 hasta 255 1 Desde 000 hasta 255 1 GAtE -.-.-.o Port - Puerto MODBUS TCP SELECtor SELEC. 1 Página mostrada en función de la posición del selector entre las páginas disponibles para cada aplicación (véase “Selector frontal” en página 79) SELEC. 2 SELEC. 3 SELEC.LoC 502 Desde 1 hasta 28 1 Desde 1 hasta 28 25 Desde 1 hasta 28 28 Desde 1 hasta 28 3 3P.n 3P.1 2P 1P 3P 3P.n SYS - Sistema Ut rAtio - Relación del transformador de tensión (VT) AV5: entre 1 y 6975 AV2: N/D 1 Ct rAtio - Relación del transformador de intensidad (CT) AV5: entre 1 y 6975 AV2: N/D 1 P int.ti - Tiempo de integración dmd (min) Desde 1 hasta 30 15 FiLtEr.S - Intervalo de la intervención del filtro con respecto a la escala completa (%) Desde 0 hasta 100 2 FiLtEr.Co - Coeficiente del filtro Desde 1 hasta 32 2 End - Salir y guardar - - Nota: MID (PFA, PFB): solamente 3P.n Nota: la página Ut rAtio se encuentra disponible con fines de compatibilidad con otras versiones, a pesar de que la versión AV5 no se ha ideado para su uso con transformadores de tensión. Por lo tanto, debe configurarse como 1. 76 EM24 E1 - Manual de instrucciones | CARLO GAVAZZI Controls SpA Información esencial Información esencial Gestión de la medición Aplicaciones Nota: cuando se selecciona una aplicación con conexión fácil, para el cálculo de la energía activa siempre se integra la potencia, tanto consumida como generada. La dirección de la intensidad no afecta a la medición. Cuando se selecciona una aplicación sin conexión fácil, se encuentra disponible la activa tanto generada como consumida. Aplicación A Mediciones Sistema: • secuencia de fase • tensión fase-neutro • frecuencia • energía activa consumida total • potencia activa dmd y dmd máx. Conexión fácil SÍ B Sistema: • secuencia de fase • tensión fase-neutro • frecuencia • energía activa consumida total • potencia activa dmd y dmd máx. • energía reactiva consumida total • potencia aparente dmd y dmd máx. SÍ C Sistema: • secuencia de fase • tensión fase-neutro • frecuencia • energía activa consumida total • potencia activa dmd y dmd máx. • energía reactiva y activa consumida por tarifa SÍ D monofase • energía activa consumida • tensión SÍ E Sistema: • secuencia de fase • tensión fase-neutro • frecuencia • energía activa generada y consumida total • potencia activa dmd y dmd máx. • contador de horas • potencia activa • factor de potencia NA F Sistema: • secuencia de fase • tensión fase-neutro • frecuencia • energía activa generada y consumida total • potencia activa dmd y dmd máx. • tensión fase-fase • energía activa • Intensidad dmd máx. • Energía activa parcial • energía reactiva generada y consumida total • potencia aparente, dmd y dmd máx. • Energía reactiva parcial • contador de horas • potencia activa • factor de potencia NA EM24 E1 - Manual de instrucciones | CARLO GAVAZZI Controls SpA 77 Información esencial G Sistema: • secuencia de fase • tensión fase-neutro • frecuencia • energía activa consumida total • potencia activa dmd y dmd máx. • tensión fase-fase • energía activa • Intensidad dmd máx. • Energía activa parcial • energía reactiva consumida total • potencia aparente, dmd y dmd máx. • energía reactiva • contador de horas • potencia activa • potencia activa dmd • potencia reactiva • factor de potencia • energía reactiva y activa consumida por tarifa monofase • potencia reactiva por fase • potencia aparente por fase • factor de potencia por fase • potencia activa por fase • intensidad por fase • tensiones línea-línea • tensiones línea-neutro SÍ H Sistema: • secuencia de fase • tensión fase-neutro • frecuencia • energía activa generada y consumida total • potencia activa dmd y dmd máx. • tensión fase-fase • energía activa • Intensidad dmd máx. • Energía activa parcial • energía reactiva generada y consumida total • potencia aparente, dmd y dmd máx. • energía reactiva • contador de horas • potencia activa • potencia activa dmd • potencia reactiva • factor de potencia • energía reactiva y activa consumida por tarifa monofase • potencia reactiva por fase • potencia aparente por fase • factor de potencia por fase • potencia activa por fase • intensidad por fase • tensiones línea-línea • tensiones línea-neutro NA Páginas de programación La tabla a continuación muestra las páginas de programación disponibles para cada aplicación Page Aplicación A B C D E F G H Cambie la contraseña x x x x x x x x Aplicación x x x x x x x x Usuario - - - x - - - - Habilitación de DHCP x x x x x x x x Dirección IP x x x x x x x x Máscara de subred x x x x x x x x Puerta de enlace predeterminada x x x x x x x x Puerto MODBUS TCP x x x x x x x x 78 EM24 E1 - Manual de instrucciones | CARLO GAVAZZI Controls SpA Información esencial Selector x x x Sistema x x x Relación del transformador de tensión x x x x x x x x x x x x x x x x x Ratio CT x x x x x x x x Tiempo de integración de la potencia media x x x - x x x x Filter S - - - - - x x x Filter Co - - - - - x x x End x x x x x x x x Gestión de tarifas Gestión de tarifas a través de un comando Modbus Modifique la tarifa introduciendo el valor correspondiente en la tarifa actual en función de esta tabla en el registro 1201Fh: Tarifa actual Valor del registro T1 1 T2 2 T3 3 T4 4 Inhabilitación de la gestión de tarifas Configure la gestión de tarifas como inhabilitada o introduzca 0 (valor predeterminado) en el registro 1201Fh. LED frontal y selector LED frontal El LED frontal rojo parpadea de manera proporcional al consumo de energía consumida activa cuando el selector está en la posición de energía inductiva reactiva en la posición kvarh - 1 - 2 y al consumo . El LED frontal no gestionará ningún tipo de energía (generada) negativa. Selector frontal • Posición Lock : el selector frontal impide el acceso al modo de programación • Posición 1, 2, kvarh : acceso rápido a las páginas de medición. Cada posición está asociada a una página de medición según esta tabla: Aplicación Posición del selector Lock 3 1,2,3 1 B, C, E, F, G, H Lock, 1, 2, kvarh Se puede configurar con un valor entre 1 y 28 C Lock, 1, 2, kvarh Se puede configurar con un valor entre 1 y 28 Lock 28 1 15 2 16 3 17 A D Página disponible EM24 E1 - Manual de instrucciones | CARLO GAVAZZI Controls SpA 79 Mantenimiento y eliminación Mantenimiento y eliminación Limpieza Utilice un paño ligeramente humedecido para limpiar la pantalla. No utilice abrasivos ni disolventes. Responsabilidad de la eliminación El producto debe desecharse en los centros de reciclaje correspondientes especificados por el gobierno o las autoridades públicas locales. Una eliminación adecuada y su reciclaje contribuirán a prevenir consecuencias potencialmente dañinas para el medioambiente y las personas. 80 EM24 E1 - Manual de instrucciones | CARLO GAVAZZI Controls SpA CARLO GAVAZZI Controls SpA via Safforze, 8 32100 Belluno (BL) Italia www.gavazziautomation.com [email protected] info: +39 0437 355811 fax: +39 0437 355880 EM24 E1 - Instrucciones de uso 2018-06 | Copyright © 2018 EM24 E1 Trefaset energianalyseapparat BRUGERMANUAL Indhold EM24 E1 85 Introduktion85 Beskrivelse85 UCS (Universel konfigurationssoftware) 85 Brug af EM24 E1 86 Introduktion86 Display86 Indstilling af netværksparametre 87 Indstilling af netværksparametre via DHCP 87 Indstilling af netværksparametre uden DHCP 87 Arbejde med EM24 E1 88 Arbejde med aflæsnings-/infomenuen 88 Arbejde med indstillingsmenuen 88 Nulstilling af partial energimåler 88 Indstilling af en parameter 89 Menubeskrivelse90 Aflæsningsmenuen - aflæsningssider 90 Informationsmenu91 Indstillinger fra EM24 E1 92 Generelle indstillinger 92 Vigtig information 93 Anvendelsesområder93 Programmeringssider94 Tarifstyring via Modbus-kommandoer 95 Deaktivering af tarifstyring 95 Forreste LED 95 Frontvælger95 Vedligeholdelse og bortskaffelse 96 EM24 E1 - Brugervejledning | CARLO GAVAZZI Controls SpA 83 Informationsret Copyright © 2018, CARLO GAVAZZI Controls SpA Alle rettigheder er forbeholdt i alle lande. CARLO GAVAZZI Controls SpA forbeholder sig ret til at udføre ændringer eller forbedringer i den tilhørende dokumentation uden forudgående meddelelse herom. Meddelelser vedr. sikkerhed Det følgende afsnit beskriver advarsler, som har relation til sikkerhedsforhold for brugeren og apparaturet: ADVARSEL: angiver påbud, som, hvis de ikke overholdes, kan medføre skader på apparaturet. PAS PÅ! Angiver en risikobetonet situation, som, hvis den ikke undgås, kan medføre tab af data. VIGTIGT: indeholder vigtig information, som ikke må tilsidesættes vedr. en opgaves udførelse. Generelle advarsler Denne vejledning er en integreret del af produktet og skal være i nærheden i hele produktets levetid. Den skal altid konsulteres i alle situationer, som drejer sig om konfiguration, brug og vedligeholdelse. Af denne grund skal den altid være tilgængelig for brugerne. NOTICE: Ingen er autoriseret til åbning af analysatoren. Denne handling må kun udføres af det tekniske personale hos CARLO GAVAZZI Beskyttelsen kan blive forringet, hvis instrumentet bruges på anden vis end det, der er angivet af fabrikanten. Service og garanti Hvis der opstår fejlfunktioner og defekter eller anmodninger om oplysninger, bedes du kontakte den lokale CARLO GAVAZZIforhandler eller afdeling. Installation og brug af analyseapparater udover dem, der er beskrevet i de medfølgende instruktioner medfører bortfald af garantien. Download Denne manual www.productselection.net/MANUALS/UK/EM24_im_use.pdf Installationsvejledning - EM24 www.productselection.net/MANUALS/UK/EM24_im_inst.pdf UCS-software www.productselection.net/Download/UK/ucs.zip 84 EM24 E1 - Brugervejledning | CARLO GAVAZZI Controls SpA EM24 E1 Introduktion EM24 er en trefaset energianalysator til DIN-skinnemontering med konfigurationsjoystick, frontvælger og LCD-display. Versionen med direkte tilslutning (AV2) gør det muligt at måle op til 65 A, mens versionen med CT-forbindelse (AV5) gør det muligt at måle op til 34875 A ved hjælp af strømtransformere (5 A sekundær udgang). Med DHCP-funktionen bliver ibrugtagningen hurtigere, og alle konfigurationsparametre kan opsættes via UCS. Beskrivelse AV2 Del AV5 Beskrivelse A LCD-display B Spænding-/strømtilslutninger C Joystick D Vælger med pinkode for MID-forsegling (programmeringsblok) E Ind- og udgange eller kommunikationsport F Stifter til MID-forsegling (beskyttelsescovers medfølger) UCS (Universel konfigurationssoftware) UCS-desktop er tilgængelig til gratis download. Den kan tilsluttes EM24 via Ethernet (Modbus TCP/IP) . Følgende er muligt med UCS: • konfigurere EM24 (online eller offline) • vise systemstatus for diagnostik og konfigurationstjek funktionsoversigt EM24 E1 - Brugervejledning | CARLO GAVAZZI Controls SpA 85 Brug af EM24 E1 Introduktion EM24 er opbygget med to menuer: • Aflæsnings- og informationsmenusider: bruges tl at vise aflæsningssiderne, information er relevant for de programmerede parametre og instrumentets firmwareudgivelse • indstillingsmenu: Sider, der anvendes for at indstille parametre Display Displayet er opdelt i tre linjer: Symbol Beskrivelse Visning af fase-til-neutral-systemspænding Visning af fase-til-fase-systemspænding Visning af maks. værdier Bruger-id Visning af systemvariable Visning af dmd-systemvariable EEEE 86 EM24 E1 - Brugervejledning | CARLO GAVAZZI Controls SpA Overløb. Bemærk: Funktionerne for DMD-beregningen, timetælleren og energimålerne undertrykkes, og alarmudgangene aktiveres. Angivelsen “EEEE” i en enkelt fase-variabel medfører automatisk overløbstilstanden i den relevante systemvariabel, og PF-angivelsen tvinges til “0,000”. Indstilling af netværksparametre Indstilling af netværksparametre via DHCP Trin Handling 1 Installér EM24 2 Aktivér DHCP, og afslut med End 3 Forbind EM24 til LAN-netværket, som PC'en er tilsluttet 4 Gå til Info siderne for at få vist de tildelte netværksparametre 5 Start UCS-softwaren, og tilslut til EM24 via Manuel tilslutning > Modbus TCP 6 Indtast den IP-adresse, der vises på Info-siden (se pkt. 4) 7 Gå til indstillingerne, deaktiver DHCP, og tildel de krævede netværksparametre (tildelt af netværksadministrator) Indstilling af netværksparametre uden DHCP Trin Handling 1 Installér EM24 2 Deaktiver DHCP (standardindstilling) 3 Tilslut PC'en til EM24 via Ethernet-kabel (punkt-til-punkt tilslutning) 4 Indstil netværksegenskaberne for PC som følger: • statisk IP-adresse • IP-adressen på samme klasse som EM24, f.eks. hvis IP for EM24 er 192.168.1.10 (standard), kan du indstille PC-adressen til 192.168.1.20 • Undernetmaske: 255.255.255.0 • Gateway: Ikke nødvendig 5 Start UCS-softwaren, og tilslut til EM24 via Manuel tilslutning > Modbus TC, indtast IP-adressen for EM24 (192.168.1.10 som standard) 6 Gå til indstillingerne, og indtast de krævede netværksparametre 7 Tag Ethernet-kablet ud, og tilslut EM24 til netværket, som Modbus master er tilsluttet EM24 E1 - Brugervejledning | CARLO GAVAZZI Controls SpA 87 Brug af EM24 E1 Arbejde med EM24 E1 Arbejde med aflæsnings-/infomenuen til næste aflæsningsside til indstillingsmenu til forrige infoside til næste infoside til forrige aflæsningsside Arbejde med indstillingsmenuen forøg parameterværdien rediger/bekræft til forrige side til næste side formindsk parameterværdien Nulstilling af partial energimåler Trin Handling 1 Tryk på knappen i mindst 3 sekunder 2 På siden PASS indstilles adgangskoden 1357 3 Bekræft handling 4 På siden rESEt indstilles YES 5 Bekræft handling 88 EM24 E1 - Brugervejledning | CARLO GAVAZZI Controls SpA Knap Brug af EM24 E1 Trin Handling 6 På siden EnE PrES indstilles YES 7 Bekræft handling Knap Indstilling af en parameter Eksempelprocedure: indstilling af Ct rAtio=20 hvor ændringer skal gemmes. Trin Handling 1 Tænd energianalysatoren 2 Tryk på joysticket i mindst 3 sekunder 3 På siden PASS? vælges den korrekte adgangskode (standard 0) 4 Bekræft handling 5 Rul igennem siderne til Ct rAtio 6 Aktivér redigeringstilstand 7 Vælg 20 8 Bekræft handling 9 Rul igennem siderne indtil End for at afslutte Knap EM24 E1 - Brugervejledning | CARLO GAVAZZI Controls SpA 89 Brug af EM24 E1 Menubeskrivelse Aflæsningsmenuen - aflæsningssider De viste sider afhænger af den valgte applikation. Side Viste målinger L1-L2-L3 VLNΣ Hz Fasesekvens System, faseneutral spænding Frekvens 2 L1-L2-L3 VLLΣ Hz Fasesekvens System, fase-fase spænding Frekvens 3 Tot kWh (+) WΣ dmd WΣ dmd max Totale importerede aktive energi Aktiv dmd systemeffekt Aktiv maks. dmd systemeffekt 4 kWh A dmd max PArt Aktiv energi Maks. dmd strøm Partial aktiv energi 5 Tot kvarh (+) VAΣ dmd VAΣ dmd max Totale importerede reaktiv energi Tilsyneladende dmd systemeffekt Tilsyneladende maks. dmd systemeffekt 6 kvarh VAΣ PArt Tilsyneladende systemeffekt 7 kWh (+) t1 WΣ dmd Importeret aktiv energi, tarif 1 Aktiv dmd systemeffekt 8 kWh (+) t2 WΣ dmd Importeret aktiv energi, tarif 2 Aktiv dmd systemeffekt 9 kWh (+) t3 WΣ dmd Importeret aktiv energi, tarif 3 Aktiv dmd systemeffekt 10 kWh (+) t4 WΣ dmd Importeret aktiv energi, tarif 4 Aktiv dmd systemeffekt 11 kvarh (+) t1 WΣ dmd Importeret reaktiv energi, tarif 1 WΣ dmd 12 kvarh (+) t2 WΣ dmd Importeret reaktiv energi, tarif 2 WΣ dmd 13 kvarh (+) t3 WΣ dmd Importeret reaktiv energi, tarif 3 WΣ dmd 14 kvarh (+) t4 WΣ dmd Importeret reaktiv energi, tarif 4 WΣ dmd 15 kWh (+) X WX User X Importeret aktiv energi Aktiv effekt Bruger 16 kWh (+) Y WY User Y Importeret aktiv energi Aktiv effekt Bruger 17 kWh (+) Z WZ User Z Importeret aktiv energi Aktiv effekt Bruger 18 Total kvarh (-) VAΣ dmd VAΣ dmd max Totale eksporteret reaktiv energi Tilsyneladende dmd systemeffekt Tilsyneladende maks. dmd systemeffekt 19 Total kWh (-) WΣ dmd WΣ dmd max Totale eksporteret aktiv energi Aktiv dmd systemeffekt Aktiv maks. dmd systemeffekt 1 90 Reaktiv energi Partial reaktiv energi EM24 E1 - Brugervejledning | CARLO GAVAZZI Controls SpA Beskrivelse Konfigurering af systemet 20 Hours WΣ PFΣ Samlede antal driftstimer med belastning Aktiv systemeffekt Systemeffektfaktor 21 Hours VArΣ PFΣ Samlede antal driftstimer med belastning Reaktiv systemeffekt Systemeffektfaktor 22 var L1 var L2 var L3 Reaktiv effekt, fase 1 Reaktiv effekt, fase 2 Reaktiv effekt, fase 3 23 VA L1 VA L2 VA L3 Tilsyneladende effekt, fase 1 Tilsyneladende effekt, fase 2 Tilsyneladende effekt, fase 3 24 PF L1 PF L2 PF L3 Effektfaktor, fase 1 Effektfaktor, fase 2 Effektfaktor, fase 3 25 W L1 W L2 W L3 Aktiv effekt, fase 1 Aktiv effekt, fase 2 Aktiv effekt, fase 3 26 A L1 A L2 A L3 Fase 1 strøm Fase 2 strøm Fase 3 strøm 27 V L1-2 V L2-3 V L3-1 Fase 1-fase 2 spænding Fase 2-fase 3 spænding Fase 3-fase 1 spænding 28 V L1 V L2 V L3 Fase 1 spænding Fase 2 spænding Fase 3 spænding Bemærk: I programmeringstilstand lagres er den sidste side, der vises. Informationsmenu Side Sidenavn Vist information 1 IP o.o.-.- IP-adresse (første del) 2 IP -.-.o.o IP-adresse (anden del) 3 Sub o.o.-.- Undernetmaske (første del) 4 Sub -.-.o.o Undernetmaske (anden del) 5 Gateo.o.-.- Standardgateway (første del) 6 Gate-.-.o.o Standardgateway (anden del) 7 Port Modbus TCP-port 8 DHCP Aktivering af DHCP 9 Info Ethernet-diagnostik 10 Ut ratio VT/PT-koefficient 11 CT ratio CT-koefficient 12 1P/2P/3P/3Pn (2-3-4-wire) dmd (time) System Tilslutning (2-3-4 ledere) Dmd-integrationstid (min.) 13 Pulse LED-impulsvægt (Antal kWh/kvarh pr. impuls) 14 Year Firmware-udgivelse Produktionsår EM24 E1 - Brugervejledning | CARLO GAVAZZI Controls SpA 91 Konfigurering af systemet Indstillinger fra EM24 E1 Generelle indstillinger De tilgængelige indstillinger afhænger af Sidenavn Undermenu Beskrivelse Værdier Standardværdi Cng PASS - Skift adgangskode Fra 0 til 9.999 0 Applikation tYP.A tYP.b tYP.C tYP.d tYP.E tYP.F tYP.G tYP.H tYP.H Bruger Fra 0 til 9.999 1 Fra 0 til 9.999 2 APPLiCAt User USEr 1 USEr 2 Fra 0 til 9.999 3 dHCP - USEr 3 Aktivering af DHCP oFF/on oFF IP Addr IP o.-.-.- IP-adresse SUb GAtE Fra 000 til 255 192 IP -.o.-.- Fra 000 til 255 168 IP -.-.o.- Fra 000 til 255 1 IP -.-.-.o Fra 000 til 255 10 SUb o.-.-.- Fra 000 til 255 255 SUb -.o.-.- Fra 000 til 255 255 SUb -.-.o.- Fra 000 til 255 255 SUb -.-.-.o Fra 000 til 255 0 GAtE o.-.-.- Subnetmaske Fra 000 til 255 192 GAtE -.o.-.- Standardgateway Fra 000 til 255 168 GAtE -.-.o.- Fra 000 til 255 1 Fra 000 til 255 1 GAtE -.-.-.o Port - MODBUS TCP-port SELECtor SELEC. 1 Siden vises i henhold til vælgerposition blandt de tilgængelige side for hver applikation (se ”Frontvælger” på side 95) SELEC. 2 SELEC. 3 SELEC.LoC 502 Fra 1 til 28 1 Fra 1 til 28 25 Fra 1 til 28 28 Fra 1 til 28 3 3P.n 3P.1 2P 1P 3P 3P.n SYS - System Ut rAtio - Transformerkoefficient for spænding (VT) AV5: fra 1 til 6975 AV2: N/A 1 Ct rAtio - Strømtransformerkoefficient (Ct) AV5: fra 1 til 6975 AV2: N/A 1 P int.ti - Dmd-integrationstid (min.) Fra 1 til 30 15 FiLtEr.S - Interval af filterindgreb i forhold til fuld skala (%) Fra 0 til 100 2 FiLtEr.Co - Filterkoefficient Fra 1 til 32 2 End - Afslut og gem - - Bemærk: MID (PFA, PFB): kun 3P.n Bemærk: Ut-koefficientværdien er tilgængelig for kompatibilitet med andre versioner, selv om AV5 versionen ikke skal bruges sammen med spændingstransformere. Den skal derfor indstilles på 1 92 EM24 E1 - Brugervejledning | CARLO GAVAZZI Controls SpA Vigtig information Vigtig information Administration af aflæsninger Anvendelsesområder Bemærk: Hvis en applikation med nem tilslutning vælges, er effekten altid integreret i beregningen af den aktive energi, både ved importeret og eksporteret effekt. Strømretningen påvirker ikke aflæsningen. Hvis en applikation uden nem tilslutning vælges, er både den aktive importerede og eksporterede effekt tilgængelig. Applikation A Målinger System: • fasesekvens • fase-neutral, spænding • frekvens • totale importerede aktive energi • aktiv dmd effekt og maks. dmd Nem tilslutning JA B System: • fasesekvens • fase-neutral, spænding • frekvens • totale importerede aktive energi • aktiv dmd effekt og maks. dmd • totale importerede reaktiv energi • tilsyneladende dmd effekt og maks. dmd JA C System: • fasesekvens • fase-neutral, spænding • frekvens • totale importerede aktive energi • aktiv dmd effekt og maks. dmd • importeret aktiv og reaktiv energi efter tarif JA D Enkeltfase: • importeret aktiv energi. • spænding JA E System: • fasesekvens • fase-neutral, spænding • frekvens • total importeret og eksporteret aktiv energi • aktiv dmd effekt og maks. dmd • driftstimetæller • aktiv effekt • effektfaktor NO F System: • fasesekvens • fase-neutral, spænding • frekvens • total importeret og eksporteret aktive energi • aktiv dmd effekt og maks. dmd • fase-fase, spænding • aktiv energi • maks. dmd strøm • partial aktiv energi • total importeret og eksporteret reaktiv energi • tilsyneladende effekt, dmd og maks. dmd • partial reaktiv energi • driftstimetæller • aktiv effekt • effektfaktor NO EM24 E1 - Brugervejledning | CARLO GAVAZZI Controls SpA 93 Vigtig information G System: • fasesekvens • fase-neutral, spænding • frekvens • totale importerede aktive energi • aktiv dmd effekt og maks. dmd • fase-fase, spænding • aktiv energi • maks. dmd strøm • partial aktiv energi • totale importerede reaktiv energi • tilsyneladende effekt, dmd og maks. dmd • reaktiv energi • driftstimetæller • aktiv effekt • aktiv dmd effekt • reaktiv effekt • effektfaktor • importeret aktiv og reaktiv energi efter tarif Enkeltfase: • reaktiv effekt pr. fase • tilsyneladende effekt pr. fase • effektfaktor pr. fase • aktiv effekt pr. fase • strøm pr. fase • linje-linje spændinger • linj-neutral spændinger JA H System: • fasesekvens • fase-neutral, spænding • frekvens • total importeret og eksporteret aktiv energi • aktiv dmd effekt og maks. dmd • fase-fase, spænding • aktiv energi • maks. dmd strøm • partial aktiv energi • total importeret og eksporteret reaktiv energi • tilsyneladende effekt, dmd og maks. dmd • reaktiv energi • driftstimetæller • aktiv effekt • aktiv dmd effekt • reaktiv effekt • effektfaktor • importeret aktiv og reaktiv energi efter tarif Enkeltfase: • reaktiv effekt pr. fase • tilsyneladende effekt pr. fase • effektfaktor pr. fase • aktiv effekt pr. fase • strøm pr. fase • linje-linje spændinger • linj-neutral spændinger NO Programmeringssider Følgende tabel viser, hvilke programmeringssider der er til rådighed for hver applikation Side Applikation A B C D E F G H Skift adgangskode x x x x x x x x Applikation x x x x x x x x Bruger - - - x - - - - Aktivering af DHCP x x x x x x x x IP-adresse x x x x x x x x Subnetmaske x x x x x x x x Standardgateway x x x x x x x x MODBUS TCP-port x x x x x x x x 94 EM24 E1 - Brugervejledning | CARLO GAVAZZI Controls SpA Vigtig information Vælger x x x System x x x VT-koefficient x x x x x x x x x x x x x x x x x CT-koefficient x x x x x x x x Gns. effektintegrationstid x x x - x x x x Filter S - - - - - x x x Filter Co - - - - - x x x End x x x x x x x x Tarifstyring Tarifstyring via Modbus-kommandoer Skift tariffen ved at ændre værdien svarende til den aktuelle tarif i henhold til flg. tabel i 1201Fh registret: Gældende tarif Registerværdi T1 1 T2 2 T3 3 T4 4 Deaktivering af tarifstyring Sæt tarifstyringen til deaktiveret, eller angiv 0 (standardværdi) i 1201Fh registret. Forreste LED og vælger Forreste LED Den forreste, røde LED blinker proportionalt med det aktive, importerede energiforbrug, hvis vælgeren er i positionen tive energiforbrug i positionen kvarh. Al slags negativ (eksporteret) energi vil ikke blive styret af den forreste LED. - 1 - 2 og med det reaktive, induk- Frontvælger • Lock position: Frontvælgeren forhindrer, at der kan fås adgang til programmeringstilstanden • 1, 2, kvarh position: Giver hurtig adgang til aflæsningssiderne. Hver position er tilknyttet én aflæsningsside i henhold til følgende tabel: Applikation A Vælgerposition Lås 3 Side til rådighed 1,2,3 1 B, C, E, F, G, H Lås, 1, 2, kvarh Kan indstilles fra 1 til 28 C Lås, 1, 2, kvarh Kan indstilles fra 1 til 28 Lås 28 1 15 2 16 3 17 D EM24 E1 - Brugervejledning | CARLO GAVAZZI Controls SpA 95 Vedligeholdelse og bortskaffelse Vedligeholdelse og bortskaffelse Rengøring Brug en let fugtet klud til at rengøre displayet Brug ikke slibende midler eller opløsningsmidler Ansvar for bortskaffelse Produktet skal bortskaffes på en lokal, godkendt genbrugsstation. Korrekt bortskaffelse og genbrug vil bidrage til at mindske eventuelle skadelige konsekvenser for miljøet, mennesker og dyr. 96 EM24 E1 - Brugervejledning | CARLO GAVAZZI Controls SpA CARLO GAVAZZI Controls SpA via Safforze, 8 32100 Belluno (BL) Italien www.gavazziautomation.com [email protected] info: +39 0437 355811 fax: +39 0437 355880 EM24 E1 - Brugermanual 2018-06 | Copyright © 2018
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97