1 EN Instruction Manual DC Power Supply
2
DE Bedienungsanleitung DC Stromversorgung
3 FR Manual d'instructions DC Alimentation d'Énergie
4 ES Manual de instrucciones DC Fuente De Alimentación
5 IT Manuale di Istruzione DC Gruppo di alimentazione
6 PT Manual de Instruções DC Fonte De Alimentação
DeviceNet
®
Series
1606-XLEDNET3
1606-XLSDNET4
1606-XLSDNET8
Read this first! English 1
Before operating this unit please read this manual thoroughly and retain this manual for future reference! This device may only be installed and put into operation by qualified personnel. If damage or
malfunction should occur during operation, immediately turn power off and send unit to the factory for inspection. The unit does not contain serviceable parts. The tripping of an internal fuse (if
included) is caused by an internal defect. The information presented in this document is believed to be accurate and reliable and may change without notice. For any clarifications the English
translation will be used.
Intended Use: This power supply is designed for installation in an enclosure and is intended for the general use such as in industrial control, office, communication, and instrumentation equipment.
Do not use this power supply in aircrafts, trains and nuclear equipment where malfunction may cause severe personal injury or threaten human life.
WARNING
CAUTION
Risk of electrical shock, fire, personal injury or death.
1) Do not use the power supply without proper grounding (Protective Earth).
2) Turn power off before working on the device. Protect against inadvertent re-powering.
3) Make sure that the wiring is correct by following all local and national codes.
4) Do not modify or repair the unit.
5) Do not open the unit as high voltages are present inside.
6) Use caution to prevent any foreign objects from entering into the housing.
7) Do not use in wet locations or in areas where moisture or condensation can be expected.
8) Do not touch during power-on, and immediately after power-off. Hot surface may cause burns.
Reduction of output current may be necessary when:
1) Minimum installation clearance can not be met.
2) Altitude is higher than 2000m.
3) Device is used above +60°C ambient.
4) Mounting orientation is other than output and input terminal located at the bottom of the
unit.
5) Airflow for convection cooling is obstructed.
Details for de-rating can be found in this manual and in the datasheet of the unit..
WARNING EXPLOSION HAZARDS (Notes for use in hazardous locations only)
Units which are marked with "Class I Div 2" are suitable for use in non-hazardous or Class I Division 2 Groups A, B, C, D locations.
Substitution of components may impair suitability for Class I Division 2 environment. Do not disconnect equipment unless power has been switched off.
Wiring must be in accordance with Class I, Division 2 wiring methods of the National Electrical Code, NFPA 70, and in accordance with other local or national codes.
Vor Inbetriebnahme lesen! Deutsch 2
Bitte lesen Sie diese Warnungen und Hinweise sorgfältig durch, bevor Sie das Gerät in Betrieb nehmen. Bewahren Sie die Anleitung zum Nachlesen auf. Das Gerät darf nur durch fachkundiges und
qualifiziertes Personal installiert werden. Bei Funktionsstörungen oder Beschädigungen schalten Sie sofort die Versorgungsspannung ab und senden das Gerät zur Überprüfung ins Werk. Das Gerät
beinhaltet keine Servicebauteile. Interne Sicherungen (falls vorhanden) lösen nur bei Gerätedefekt aus. Die angegebenen Daten dienen allein der Produktbeschreibung und sind nicht als
zugesicherte Eigenschaften im Rechtssinne aufzufassen. Im Zweifelsfall gilt der englische Text
Bestimmungsgemäßer Gebrauch: Diese Stromversorgung ist für den Einbau in ein Gehäuse konzipiert und zur Verwendung für allgemeine elektronische Geräte, wie z.B. Industriesteuerungen,
Bürogeräte, Kommunikationsgeräte oder Messgeräte geeignet. Benutzen Sie diese Stromversorgung nicht in Steuerungsanlagen von Flugzeugen, Zügen oder nuklearen Einrichtungen, in denen eine
Funktionsstörung zu schweren Verletzungen führen oder Lebensgefahr bedeuten kann.
WARNUNG
VORSICHT
Missachtung nachfolgender Punkte kann einen elektrischen Schlag, Brände, schwere Unfälle oder Tod
zur Folge haben.
1) Betreiben Sie die Stromversorgung nie ohne Schutzleiter.
2) Schalten Sie die Eingangsspannung vor Installations-, Wartungs- oder Änderungsarbeiten ab und
sichern Sie diese gegen unbeabsichtigtes Wiedereinschalten.
3) Sorgen Sie für eine ordnungsgemäße und fachgerechte Verdrahtung.
4) Führen Sie keine Änderungen oder Reparaturversuche am Gerät durch.
5) Gerät niemals öffnen. Im Inneren befinden sich gefährliche Spannungen.
6) Verhindern Sie das Eindringen von Fremdkörpern, wie z.B. Büroklammern und Metallteilen.
7) Betreiben Sie das Gerät nicht in feuchter Umgebung oder in einer Umgebung, bei der mit Betauung
oder Kondensation zu rechnen ist.
8) Gehäuse nicht während des Betriebes oder kurz nach dem Abschalten berühren. Heiße
Oberflächen können Verletzungen verursachen.
Rücknahme der Ausgangsleistung kann erforderlich sein:
1) wenn die minimalen Einbauabstände nicht eingehalten werden können.
2) bei Aufstellhöhen über 2000m.
3) Betrieb bei Umgebungstemperaturen über +60°C.
4) bei Einbaulagen abweichend von der Standardeinbaulage (Eingang und Ausgang an
der Unterseite des Gerätes).
5) bei behinderter Luftzirkulation.
Details zur Leistungsrücknahme befinden sich in dieser Betriebsanleitung oder im
Datenblatt des Gerätes.
ACHTUNG EXPLOSIONSGEFAHR! (Hinweise für den Betrieb in explosionsgefährdeter Umgebung)
Geräte, die am Leistungsschild mit "Class I Div 2" gekennzeichnet sind, sind für den Einsatz in Klasse I Division 2 Gruppen A,B,C,D oder für nicht explosionsgefährdete Aufstellorte geeignet.
Veränderungen an Bauteilen können die Tauglichkeit für Klasse I Division 2 beeinträchtigen. Anschlüsse nicht trennen, solange Spannung anliegt. Anschluss muss unter Berücksichtigung der
Anforderungen nach Klasse I Division 2 Artikel 501-4(b) des National Electrical Code, NFPA 70, erfolgen.
A lire avant mise sous tension! Français 3
Merci de lire ces instructions de montage et d'entretien avant de mettre l'alimentation sous tension. Conservez ce manuel qui vous sera toujours utile. Cette alimentation doit être installée par du
personnel qualifié et compétent. Le déclenchement du fusible interne traduit très probablement un défaut au niveau de l'appareil. Si un défaut quelconque apparaît en cours de fonctionnement,
débrancher au plus vite l'alimentation. Dans ce deux cas de figure, il convient de faire contrôler l'alimentation en usine! Les données indiquées dans ce document servent uniquement à donner une
description du produit et n'ont aucune valeur juridique. En cas de divergences, le texte anglais fait foi.
Utilisation: Cet appareil est conçu pour être installé dans une armoire et pour tous les équipements électroniques, tel que l'équipement industriel de commande, l'équipement de bureau, le matériel
de communication et les instruments de mesures. N'utilisez pas cet appareil pour l'équipement de commandes dans les avions, les trains et l'équipement atomique où un problème de
fonctionnement de l'alimentation pourrait causer des blessures graves ou menacer la vie humaine.
AVERTISSEMENT
ATTENTION
Prendre en compte les points suivants, afin d'éviter toute détérioration électrique, incendie, dommage
aux personnes ou mort.
1) ne jamais faire fonctionner l'alimentation sans raccordement à la terre !
2) débrancher l'installation avant toute intervention sur l'alimentation (ou démontage) et s'assurer qu'il
n'y a pas risque de redémarrage.
3) s'assurer que le câblage a été fait selon les prescriptions
4) ne pas effectuer de réparations ou modifications sur l'alimentation
5) ne pas ouvrir l'appareil. Des tensions importantes passent à l'intérieur.
6) veiller à ce qu'aucun objet ne rentre en contact avec l'intérieur de l'alimentation (trombones, pièces
métalliques)
7) ne pas faire fonctionner l'appareil dans un environnement humide ou à l'extérieur, non protégé. Ne
pas utiliser l'appareil dans un environnement où il peut y avoir de la condensation.
8) ne pas toucher le carter pendant le fonctionnement ou après la mise sous tension. Surface chaude
risquant d’entraîner des blessures.
Des limitations de puissance de sortie peuvent apparaître si :
1) les distances d'installation mini. ne peuvent être observées
2) installation à une altitude > 2000 m
3) pour des fonctionnements en charge et avec une température ambiante > 60°C
4) pour des positions de montage différentes de la préconisation standard (entrée en sortie
dessous)
5) lorsque la circulation d'air est gênée
D'autres informations sont disponibles dans la documentation de mise en service
ATTENTION RISQUE D’ EXPLOSION (Utilisation Class I Div 2)
Les appareils portant la marque ‘Class I Div 2’ au niveau de la plaque signalétique sont prévus pour fonctionner en Classe I, Division 2, Groupes A,B,C,D ou pour un environnement non explosif et
non dangereux. Le remplacement de composants peut rendre le matériel impropre à une utilisation en Classe 1, Division 2. Ne déconnecter l’équipement qu’ hors tension ou en zone connue comme
non dangereuse. Le raccordement doit obligatoirement tenir compte des exigences de la classe 1, division 2, article 501-4(b) du National Electrical Code, NFPA 70.
Lea primero! Español 4
Conserve este manual como referencia para futuras consultas. La fuente de alimentación solo puede ser instalada y puesta en funcionamiento por personal cualificado. Por favor lea detenidamente
este manual antes de conectar la fuente de alimentación. Cuando se funde un fusible interno, existe gran probabilidad de un fallo interno en el equipo.Si se produce un fallo o mal funcionamiento
durante la operación, desconecte inmediatamente la tensión de alimentación. En ambos casos, el equipo debe ser inspeccionado en fábrica. La información presentada en este documento es
exacta y fiable en cuanto a la descripción del producto y puede cambiar sin aviso. En casa de duda, prevalece el texto inglés.
Uso apropiado: Este equipo ha sido diseñado para su instalación en un ambiente cerrado y ha sido concebido para uso general en instalaciones de control industrial, oficinas, comunicaciones y
equipos de instrumentación. No emplee este equipo en aeronaves, trenes e instalaciones atómicas, donde un mal funcionamiento de la fuente de alimentación puede ocasionar lesiones graves o
riesgo mortal.
ADVERTENCIA
ATENCIÓN
Riesgo de descarga eléctrica, incendio, accidente grave o muerte.
1) No conectar nunca la unidad sin conexión de puesta a tierra.
2) Desconectar la tensión de red antes de trabajar en la fuente de alimentación. Evite una posible
reconexión involuntaria.
3) Asegurarse de que el cableado es correcto de acuerdo a los códigos locales y nacionales.
4) No realizar ninguna modificación o reparación de la unidad.
5) No abrir nunca la unidad. En el interior existe riesgo de altas tensiones.
6) Evitar la introducción en la carcasa de objetos extraños.
7) No usar el equipo en ambientes húmedos. No operar el equipo en ambientes donde se espere la
formación de rocío o condensación.
8) No tocar durante el funcionamiento ni inmediatamente después del apagado. El calor de la
superficie puede causar quemaduras graves
La deriva en la tensión de salida se produce:
1) cuando no pueden mantenerse las distancias mínimas de montaje.
2) en caso de que el montaje se realice en altitudes superiores a los 2000 m.
3) en caso de funcionamiento a plena carga y temperaturas ambientales superiores a
+60ºC.
4) En caso de posiciones de montaje diferentes a la posición de montaje estándar
(terminales abajo).
5) en caso de que la circulación de aire para la refrigeración por conducción esté
obstruida.
Puede encontrar más detalles del caso de deriva en este manual.
ATENCIÓN PELIGRO DE EXPLOSIÓN! (Uso apropiado Class I Div 2)
Los equipos marcados con la expresión "Class I Div 2" son adecuados para su uso en ambientes no peligrosos y en entornos con la Clase I División 2 Grupos A, B, C, D. La sustitución de
componentes puede perjudicar la idoneidad para la Clase I División 2. No desconecte el equipo a menos que la tensión de alimentación esté desconectada.
El conexionado debe cumplir con la Clase I División 2 métodos de conexión del Código Nacional Eléctrico NFPA 70 o con el resto de códigos locales o nacionales.
Leggere prima questa parte! Italiano 5
Prima di collegare il sistema di alimentazione elettrica si prega di leggere attentamente le seguenti avvertenze. Conservare le istruzioni per la consultazione futura. Il sistema di alimentazione elettrica
deve essere installato solo da personale competente e qualificato. In caso di intervento del fusibile interno, molto probabilmente l'apparecchio è guasto. Se durante il funzionamento si verificano
anomalie o guasti, scollegare immediatamente la tensione di alimentazione. In entrambi i casi è necessario far controllare l'apparecchio dal produttore! I dati sono indicati solo a scopo descrittivo del
prodotto e non vanno considerati come caratteristiche garantite dell'apparecchio.In caso di differenze o problemi è valido il testo inglese
Uso previsto: Questo apparecchio è previsto per il montaggio in un rack per moduli elettronici, ad esempio per controllori industriali, apparecchiature per ufficio, unità di comunicazione o apparecchi
di misura. Non utilizzare l'apparecchio in impianti di controllo di aerei, di treni o di impianti nucleari in cui il suo eventuale guasto può comportare gravi lesioni o la morte di persone.
AVVERTENZA
ATTENZIONE
Il mancato rispetto delle seguenti norme può provocare folgorazione elettrica, incendi, gravi incidenti e
perfino la morte.
1) Non far funzionare in nessun caso il sistema di alimentazione elettrica senza conduttore di
protezione!
2) Prima di eseguire interventi di installazione, di manutenzione o di modifica scollegare la tensione di
rete ed adottare tutti i provvedimenti necessari per impedirne il ricollegamento non intenzionale.
3) Assicurare un cablaggio regolare e corretto.
4) Non tentare di modificare o di riparare da soli l'apparecchio.
5) Non aprire l'apparecchio. Al suo interno sono applicate tensioni elettriche pericolose.
6) Impedire la penetrazione di corpi estranei nell'apparecchio, ad esempio fermagli o altri oggetti
metallici.
7) Non far funzionare l'apparecchio in un ambiente umido. Non far funzionare l'apparecchio in un
ambiente soggetto alla formazione di condensa o di rugiada.
8) Non toccare quando acceso e subito dopo lo spegnimento. La superficie calda può causare
scottature.
È necessario ridurre la potenza di uscita se:
1) non è possibile rispettare le distanze minime di montaggio;
2) l'apparecchio viene installato in un luogo di altitudine maggiore di 2000 m;
3) il funzionamento è a pieno carico a temperatura ambiente maggiore di +60°C;
4) la posizione di montaggio differisce da quella standard (ingresso, uscita in basso)
5) è ostacolata la libera circolazione dell'aria.
Ulteriori informazioni sono riportate in questo manuale.
ATTENZIONE: PERICOLO DI ESPLOSIONE! (Uso previsto Class I Div 2)
Gli apparecchi la cui targhetta riporta "Class I Div 2" sono adatti per l'impiego in ambienti di classe I, divisione 2, gruppi A, B, C e D o non soggetti al pericolo di esplosione. La modifica dei
componenti possono influenzare negativamente l'idoneità per ambienti di classe I, divisione 2.Non aprire i morsetti con tensione di alimentazione collegata. Il collegamento deve essere eseguito nel
rispetto dei requisiti previsti dalla classe I, divisione 2, articolo 501-4(b) del National Electrical Code, NFPA 70.
Leia primeiro! Portuguès 6
Recomendamos a leitura cuidadosa das seguintes advertências e observações, antes de colocar em funcionamento a fonte de alimentação. Guarde as Instruções para futura consulta, em casos de
dúvida. A fonte de alimentação deverá ser instalada apenas por profissionais da área, tecnicamente qualificados. Se o fusível interno se fundir, é grande a possibilidade de existir um defeito no
aparelho. Se por acaso, durante a utilização ocorrer algum defeito de funcionamento ou dano, desligue imediatamente a tensão de alimentação. Em ambos os casos, será necessária uma
verificação na Fábrica! Os dados mencionados têm como finalidade somente a descrição do produto, e não devem ser interpretados como propriedades garantidas no sentido jurídico. Em caso de
duvidas aplica-se o texto em inglês.
Utilize: Apenas para o fim pré-estabelecido. Este aparelho foi concebido para ser montado dentro de invólucros, caixas ou armários para aparelhos eletrônicos em geral, como, por exemplo,
comandos de instalações industriais, aparelhos para escritórios, aparelhos de comunicação ou instrumentos de medida e quadros eléctricos. Não utilize este aparelho em sistemas de comando de
aviões, de comboios ou em instalações movidas por energia nuclear, nos quais um defeito de funcionamento poderá causar danos graves ou significar risco de morte.
ATENÇÃO
CUIDADO
A não observância ou o incumprimento dos pontos a seguir mencionados, poderá causar uma
descarga elétrica, incêndios, acidentes graves ou morte.
1) Não use a fonte de alimentação sem o condutor de proteção terra!
2) Antes de trabalhos de instalação, manutenção ou modificação, desligue a tensão de alimentação,
protegendo-a contra uma nova ligação involuntária.
3) As ligações devem ser efectuadas apenas por profissionais competentes.
4) Não efectue nenhuma modificação ou tentativa de reparação no aparelho. Quando necessário
contacte o seu distribuidor.
5) Não abra o aparelho mesmo quando desligado. No seu interior existem condensadores que podem
estar carregados electricamente.
6) Proteger a fonte de alimentação contra a introdução inadvertida de corpos metálicos, como por ex.,
clipes ou outras peças de metal.
7) Não usar o aparelho em ambientes húmidos. Não usar o aparelho em ambientes propensos a
condensações.
8) Não tocar enquanto estiver em funcionamento, nem após a desligar. A superficie poderá estar
quente e provocar lesões.
Será necessário reduzir a potência de saída nos seguintes casos:
1) Quando não forem observadas as distâncias mínimas de montagem.
2) Quando instaladas a altitudes superiores a 2000m.
3) Existencia de temperatura ambiente superior a +60ºC, em plena carga do aparelho.
4) Montagem invertida do aparelho (Entrada, saída em baixo).
5) Montagem em ambiente sem ventilação.
No presente manual de funcionamento encontram-se ainda outras informações.
ATENÇÃO, RISCO DE EXPLOSÃO! (Utilize Class I Div2)
Aparelhos que contêm na sua placa de dados elétricos o texto “Class I Div 2” são apropriados para a aplicação na Classe I, divisão 2, Grupos A, B, C, D ou também para locais de instalação isentos
de riscos de explosão. Modificações efetuadas em componentes podem restringir ou reduzir a adequação para aplicação na Classe I, Divisão 2. As ligações não devem ser separadas enquanto
estiverem ligadas a uma fonte de alimentação elétrica. As ligações devem ser efetuadas levando-se em consideração as exigências normativas da Classe I, Divisão 2.
Rockwell Automation
CH-5001 Aarau, Switzerland
Fax +41 62 837 2202
© 2010 by
Allen-Bradley Company, LCC
Industrial Components Business
1201 South Second Street
Milwaukee, WI 53204-2496 USA
Phone 440 646 5800
1606-XLEDNET3, 1606-XLSDNET4, 1606-XLSDNET8: Power Supply Instruction Manual
1606-XLEDNET3, 1606-XLSDNET4, 1606-XLSDNET8: Bedienungsanleitung für Stromversorgung
Technical Data
1)
Technische Daten
1)
1606-XLEDNET3 1606-XLSDNET4 1606-XLSDNET8
Output Voltage Ausgangsspannung nom. DC 24.1V DC 24.1V DC 24-24.5V
Factory Setting
6)
Werkseinstellung
6)
“Single-Use”, typ. fixed / fest eingestellt fixed / fest eingestellt 24.1V
Output Current Ausgangsstrom nom. 3.3A 3.8A 8A
Output Power Ausgangsleistung PowerBoost
2)
79.5W 91.2W 196W
NEC Power Classifikation Klassifizierung nach NEC
-
NEC Class 2 NEC Class 2 NEC Class 1
Output Ripple & Noise Voltage
3)
Ausgangswelligkeit
3)
max. 50mVpp 50mVpp 50mVpp
Line Regulation
2)
Netzausregelung
2)
max 0.1% 0.1% 0.1%
Load Regulation
5)
Lastausregelung
5)
max 0.3% 0.3% 0.3%
Temperature Coefficient Temperaturgang typ. 0.03% / °C 0.03% / °C 0.03% / °C
Turn-on Time Einschaltzeit typ. 90ms 100ms 85ms
Turn-on Delay Einschaltverzögerung typ. 100ms 200ms 600ms
Turn-on Overshoot Überschwingen beim Einschalten max. 400mV 400mV 400mV
AC Input Voltage AC Eingangsspannung Nom.
AC 100-240V
±15%
AC 100-240V
-15/+10%
AC 100-240V
±15%
Input Frequency Eingangsfrequenz nom.
50-60Hz
±6%
50-60Hz
±6%
50-60Hz
±6%
AC Input Current
7)
AC Eingangsstrom
7)
120 / 230Vac, typ. 1.6A -0.7A 1.1A - 0.5A 2.3A - 1.0A
Power Factor
6)
Leistungsfaktor
6)
120 / 230Vac, typ. 0.61 / 0.56 0.98 / 0.9 0.98 / 0.92
EN 61000-3-2 EN 61000-3-2 PFC-Norm Yes / Ja Yes / Ja Yes / Ja
Input Inrush Current
4)
Einschaltspitzenstrom
4)
typ. 45A peak, 1.7A
2
s 11A peak, 1.1A
2
s 7A peak, 0.6A
2
s
Hold-up Time
6)
Pufferzeit
6)
120 / 230Vac, typ. 30 / 128ms 44 / 85ms 33 / 34ms
Efficiency
6)
Wirkungsgrad
6)
120 / 230Vac, typ. 88.0% / 89.8% 91.4 / 92.0% 92.3 / 92.7%
Power Losses
6)
Verlustleistung
6)
120 / 230Vac, typ. 11.1W / 9.1W 8.6 / 7.9W 16.0 / 15.1W
Operational Temperature Range Betriebstemperaturbereich nom. -25°C - +70°C -25°C - +70°C -25°C - +70°C
Output Derating Leistungsrücknahme 60°C … 70°C 1.8W/°C 2W/°C 5W/°C
Storage Temperature Range Lagertemperaturbereich nom. -40°C - +85°C -40°C - +85°C -40°C - +85°C
Humidity
8)
Feuchte
8)
IEC 60068-2-30 5 - 95% r.H. 5 - 95% r.H. 5 - 95% r.H.
Vibration Schwingen IEC 60068-2-6 2g 2g 2g
Shock Schocken IEC 60068-2-27 30g 6ms, 20g 11ms 30g 6ms, 20g 11ms 30g 6ms, 20g 11ms
Degree of Pollution (not conductive) Verschmutzungsgrad (nicht leitend) EN 50178 / 62103 2 2 2
Degree of Protection Schutzart EN 60529 IP20 IP20 IP20
Class of Protection Schutzklasse IEC 61140 I
9)
I
9)
I
9)
Over-temperature Protection
10)
Übertemperaturschutz
10)
OTP Yes / Ja Yes / Ja Yes / Ja
Output Over-voltage Protection
10)
Überspannungsschutz Ausgang
10)
OVP, max. 39Vdc 29Vdc 29.5Vdc
Touch (Leakage) Current
11)
PE- Ableitstrom
11)
max. 0.32mA / 0.57mA 0.22mA / 0.4mA 0.38mA / 0.74mA
Return Voltages Resistance
12)
Rückspeisefestigkeit
12)
max. 35Vdc 28Vdc 35Vdc
Dimensions
15)
(WxHxD) Abmessungen
15)
(BxHxT) nom. 32x124x102mm 40x124x117mm 60x124x117mm
Weight Gewicht max. 430g; 0.95lb 620g; 1.37lb 900g; 1.98lb
Approvals Zulassungen - Æ 16) Æ 16) Æ 16)
Limited Warranty Gewährleistung Years / Jahre 1 1 1
1) All parameters are specified at 230Vac, nominal output current, 25°C ambient and after a 5 minutes
run-in time unless otherwise noted. Mounting orientation is input terminals on the bottom and
output terminals on top of the unit.
2) Input voltage variation between 85Vac and 264Vac and full loaded output.
3) 50-Ohm measurement, bandwidth 20MHz
4) 1606-XLEDNET3: at 230Vac, 40°C and cold-start, temperature and input voltage dependent.
1606-XLSDNET4 and 1606-XLSDNET8: Input inrush current electronically limited and is
temperature independent.
5) Load deviations from no-load full-load
6) At nominal load and nominal input voltage.
7) At nominal load and the lower end of the input voltage.
8) Do not energize while condensation is present.
9) PE connection required (Ground).
10) Output shut-down with automatic restart attempts.
11) PE Leakage current at 132Vac, 60Hz / 264Vac, 50Hz, TT/TN-mains.
12) Loads such as decelerating motors and inductors can feed voltage back to the output of the
power supply. The figure represents the maximum allowed feed back voltage
13) Including an external 7000µF capacitor
14) Time between turn-on and 23V output voltage
15) Depth without DIN-rail.
16) See datasheet or markings on the unit.
1) Alle Werte gelten bei 230Vac, Nennausgangsstrom, 25°C Umgebung und nach einer
Aufwärmzeit von 5 Minuten, wenn nichts anderes angegeben ist.
Einbaulage: Eingang unten und Ausgang oben.
2) Eingangsspannungsänderungen zwischen 85Vac und 264Vac, Ausgang voll belastet.
3) 50-Ohm Messung, Bandbreite 20MHz
4) 1606-XLEDNET3: bei 230Vac, 40°C und Kaltstart. Abhängig von Temperatur und
Eingangsspannung. 1606-XLSDNET4 and 1606-XLSDNET8: Der Einschaltstromstoß ist
elektronisch begrenzt und temperaturunabhängig.
5) Lastwechsel von Leerlauf bis Volllast
6) Bei Nominallast und Nenneingangsspannung.
7) Bei Nominallast und dem unteren Ende der Eingangsspannung.
8) Nicht betreiben, solange das Gerät Kondensation aufweist.
9) PE Verbindung erforderlich.
10) Ausgang schaltet ab und macht regelmäßig automatische Startversuche.
11) Erd-Ableitstrom bei 132Vac, 60Hz / 264Vac, 50Hz, TT/TN-Netze.
12) Bremsende Motoren oder Induktivitäten können Spannung zum Ausgang des Netzteils
rückspeisen. Der Wert gibt die max. zulässige Rückspeisespannung an.
13) Mit angeschlossenen externen zusätzlichem 7000µF Kondensator
14) Zeit zwischen Einschalten und Erreichen von 23V Ausgangsspannung
15) Tiefe ohne DIN-Schiene.
16) Siehe Datenblatt oder Prüfzeichen auf dem Gerät.
Installation
Use DIN-rails according to EN 60715 or EN 50022 with a height of 7.5 or 15mm. Mounting
orientation must be output terminals on the top and input terminals on the bottom. For other
orientations see datasheet. Do not obstruct air flow as the unit is convection cooled. Ventilation
grid must be kept free of any obstructions. The following installation clearances must be kept
when power supplies are permanently loaded with more than 50% of the nominal current::
Left / right: 5mm (15mm in case the adjacent device is a heat source)
40mm on top, 20mm on the bottom of the unit.
Installation
Geeignet für DIN-Schienen entsprechend EN 60715 oder EN 50022 mit einer Höhe von 7,5 oder
15mm. Der Einbau hat so zu erfolgen, dass der Eingang sich unten und die Ausgang sich oben
befindet. Für andere Einbaulagen siehe Datenblatt. Luftzirkulation nicht behindern! Die Geräte
sind für Konvektionskühlung ausgelegt. Es ist für ungehinderte Luftzirkulation zu sorgen. Folgende
Einbauabstände werden bei dauerhafter Belastung >50% des Nennstromes empfohlen:
Links / rechts: 5mm (15mm bei benachbarten Wärmequellen)
Oben: 40mm, unten 20mm vom Gerät.
Input Fuses
All units have internal input fuses included, which are not user accessible. The units are tested
and approved for branch circuits up to 20A. An external protection is only required if the supplying
branch has an ampacity greater than this, however, in some countries local regulations might
apply. Check local codes and requirements. If external fuses are necessary or utilized, minimum
requirements need to be considered to avoid nuisance tripping of the circuit breaker. The following
minimum values are recommended:
1606-XLEDNET3: 10A B- or 6A C-Characteristic
1606-XLSDNET4: 6A B- or 3A C-Characteristic
1606-XLSDNET8: 6A B- or 4A C-Characteristic
Sicherungen am Eingang
Alle Geräte besitzen interne Eingangssicherungen, die nicht anwenderzugänglich sind. Die Geräte
sind geprüft und zugelassen zum Anschluss an Stromkreisen bis max.32A. Ein zusätzlicher
externer Schutz ist nur erforderlich, wenn der Speisestromkreis mit einem höheren Wert
abgesichert ist oder nationale Richtlinien es vorschreiben. Falls externe Schutzelemente
verwendet werden, sollen diese nicht kleiner als folgende Werte sein, um ein fehlerhaftes
Auslösen zu vermeiden:
1606-XLEDNET3: 10A B- oder 6A C-Charakteristik
1606-XLSDNET4: 6A B- oder 3A C-Charakteristik
1606-XLSDNET8: 6A B- oder 4A C-Charakteristik
EMC Electromagnetic Compatibility
These power supplies are suitable for applications in industrial environment as well as in
residential, commercial and light industry environment without any restrictions. These devices
comply with FCC Part 15 rules.
CE mark is in conformance with EMC guidelines 89/336/EC, 93/68/EC and 2004/108/EC as well
as the low-voltage directives (LVD) 73/23/EC, 93/68/EC, 2006/95/EC.
EMC Immunity: EN 61000-6-1, EN 61000-6-2
EMC Emission EN 61000-6-3, EN 61000-6-4, FCC Part 15 Class B
EMV Elektromagnetische Verträglichkeit
Diese Stromversorgungen erfüllen die Anforderungen für Anwendungen in industrieller Umgebung
und für den Wohn-, Geschäfts- und Gewerbebereich ohne Einschränkungen. Die Geräte erfüllen
auch die Anforderungen der FCC Teil 15. Das CE Zeichen ist angebracht und erklärt die Erfüllung
der EMV Richtlinien 89/336/EG, 93/68/EG und 2004/108/EG wie auch der
Niederspannungsrichtlinien 73/23/EG, 93/68/EG, 2006/95/EG.
Störfestigkeit: EN 61000-6-1, EN 61000-6-2
Störaussendung: EN 61000-6-3, EN 61000-6-4, FCC Part 15 Klasse B
1606-XLEDNET3, 1606-XLSDNET4, 1606-XLSDNET8: Power Supply Instruction Manual
1606-XLEDNET3, 1606-XLSDNET4, 1606-XLSDNET8: Bedienungsanleitung für Stromversorgung
Terminals and Wiring
Use appropriate copper cables that are designed for a minimum operating temperatures of 60°C
(for ambient up to 45°C) and 75°C (for ambient up to 60°C). Follow national installation codes and
regulations! Ensure that all strands of a stranded wire enter the terminal connection! Up to two
stranded wires with the same cross section are permitted in one connection point (except for the
PE wire). Ferrules are allowed, but not required. Unused terminal spaces must be closed.
1606-XLEDNET3: Solid wire / Stranded wire / AWG 0.5-6mm
2
/ 0.5-4mm
2
/ 20-10 AWG
Wire stripping length 7mm / 0.28inch
Tightening torque 0.8Nm / 7lb.inch
1606-XLSDNET4: Input terminals:
Solid wire / Stranded wire / AWG 0.5-6mm
2
/ 0.5-4mm
2
/ 20-10 AWG
Wire stripping length 7mm / 0.28inch
Output and signal terminals:
Solid wire / Stranded wire / AWG 0.3-4mm
2
/ 0.3-2.5mm
2
/ 26-12 AWG
Wire stripping length 6mm / 0.25inch
1606-XLSDNET8: Solid wire / Stranded wire / AWG 0.5-6mm
2
/ 0.5-4mm
2
/ 20-10 AWG
Wire stripping length 7mm / 0.28inch
Anschlussklemmen und Verdrahtung
Verwenden Sie geeignete Kupferkabel, die mindestens für 60°C bei einer Umgebungstemperatur
bis zu 45°C und 75°C bei einer Umgebungstemperatur bis zu 60°C zugelassen sind. Beachten
Sie nationale Bestimmungen und Installationsvorschriften! Stellen Sie sicher, dass keine
einzelnen Drähte von Litzen abstehen. Bis zu zwei Leiter mit gleichem Querschnitt sind in einem
Anschlusspunkt zulässig (außer beim Schutzleiter). Aderendhülsen sind erlaubt, aber nicht
erforderlich. Nichtbenutzte Klemmen immer zudrehen.
1606-XLEDNET3: Starrdraht / Litze / AWG 0,5-6mm
2
/ 0,5-4mm
2
/ 20-10 AWG
Abisolierlänge 7mm / 0,28inch
Empf. Anzugsdrehmoment 0,8Nm / 7lb.inch
1606-XLSDNET4: Eingangsklemmen:
Starrdraht / Litze / AWG 0,5-6mm
2
/ 0,5-4mm
2
/ 20-10 AWG
Abisolierlänge 7mm / 0,28inch
Ausgangs- und Signalklemmen:
Starrdraht / Litze / AWG 0,3-4mm
2
/ 0,3-2,5mm
2
/ 26-12 AWG
Abisolierlänge 6mm / 0,25inch
1606-XLSDNET8: Starrdraht / Litze / AWG 0,5-6mm
2
/ 0,5-4mm
2
/ 20-10 AWG
Abisolierlänge 7mm / 0,28inch
Output- and Overload Characteristic (see Fig. 5)
The units are overload, no-load, short-circuit proof. At overload, the output current flows
continuously. The unit does not switch-off or hiccup at overload.
Ausgangs- und Überlastverhalten (siehe Bild 5)
Die Geräte sind leerlauf-, überlast- und kurzschlussfest. Bei Überlast fließt kontinuierlich Strom.
Die Geräte schalten nicht ab und haben auch keinen „Hiccup“ Modus.
DC-OK Relay Contact except 1606-XLEDNET3 (see Fig. 6)
This feature monitors the output voltage, which is produced by the power supply, and is
independent of a return voltage from a unit which is connected in parallel.
Contact closes when the output voltage reaches 20.5V
Contact opens when the output voltage dips more than 10%. Short dips will be extended to a
length of 250ms. Dips shorter than 1ms will be ignored.
Contact ratings: max.: 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A, Resistive load, min.: 1mA
DC-OK Relais Kontakt außer 1606-XLEDNET3 (siehe Bild 6)
Diese Funktion überwacht die vom Gerät erzeugte Ausgangsspannung und lässt sich von einer
rückwärts eingespeisten Spannung nicht beeinflussen (z.B.: bei Parallelschaltung)
Kontakt schließt sobald die Ausgangsspannung 21,5V erreicht
Kontakt öffnet sobald der Ausgang um mehr als 10% einbricht. Kurze Einbrüche werden auf
250ms verlängert. Einbrüche kürzer 1ms werden ignoriert.
Belastbarkeit: max.: 60Vdc 0,3A; 30Vdc 1A; 30Vac 0,5A; (R-Last); min.: 1mA
Dielectric Strength (see Fig. 4)
The output voltage is floating and separated from the input according to SELV (IEC/EN 60950-1)
and PELV (EN 60204-1, EN 50178; IEC 62103, IEC 60364-4-41) requirements. Type and factory
tests are conducted by the manufacturer. Field tests may be conducted in the field using the
appropriate test equipment which applies the voltage with a slow ramp (2s up and 2s down).
Connect phase and neutral together as well as all output poles before the test is conducted.
A B C D
Type Test (60s) 2500Vac 3000Vac 500Vac 500Vac
Factory Test (5s) 2500Vac 2500Vac 500Vac 500Vac
Field Test (5s) 2000Vac 2000Vac 500Vac 500Vac
Isolationsfestigkeit (siehe Bild 4)
Die Ausgangsspannung hat keinen galvanischen Bezug zur Erde oder Schutzleiter und ist zum
Eingang nach den SELV (IEC/EN 60950-1) und PELV (EN 60204-1, EN 50178, IEC 62103, IEC
60364-4-41) Standards getrennt. Typ- und Stückprüfungen werden beim Hersteller durchgeführt.
Wiederholungsprüfungen dürfen mittels geeigneten Prüfgenerators mit langsam (2s) ansteigenden
und abfallenden Spannungsrampen in der Anwendung erfolgen. Vor den Tests sind Phase und
Neutralleiter wie auch alle Ausgangspole miteinander zu verbinden.
A B C D
Typprüfung (60s) 2500Vac 3000Vac 500Vac 500Vac
Stückprüfung (5s) 2500Vac 2500Vac 500Vac 500Vac
Wiederholungsprüfung (5s) 2000Vac 2000Vac 500Vac 500Vac
Fig. 1 / Bild 1
1606-XLEDNET3: Functional Diagram / Funktionsschaltbild
Fig. 2 / Bild 2
1606-XLSDNET4: Functional Diagram / Funktionsschaltbild
Fig. 3 / Bild 3
1606-XLSDNET8: Functional Diagram / Funktionsschaltbild
+
+
-
-
Input Fuse
&
Input Filter
Output
Voltage
Regulator
Power
Converter
Output
Filter
DC
ok
L
N
Output
Over-
Voltage
Protection
Input
Rectifier
&
NTC Inrush
Limiter
+
+
-
-
DC-ok
contact
Output
Over-
Voltage
Protection
PFC
Converter
Output
Voltage
Regulator
Power
Converter
Output
Filter
DC-ok
Relay
Output
Voltage
Monitor
Output
Power
Manager
Temper-
ature
Shut-
down
Overload
lamp
DC-ok
lamp
Input Fuse
Input Filter
Input Rectifier
Active Transient Filter &
Inrush Current Limiter
L
N
+
+
-
-
DC-ok
contact
Output
Over-
Voltage
Protection
PFC
Converter
Output
Voltage
Regulator
Power
Converter
Output
Filter
DC-ok
Relay
Output
Voltage
Monitor
Output
Power
Manager
Temper-
ature
Shut-
down
Overload
lamp
DC-ok
lamp
Input Fuse
Input Filter
Input Rectifier
Active Transient Filter &
Inrush Current Limiter
V
OUT
L
N
Fig. 4 / Bild 4
Insulation / Isolation
Fig. 5 / Bild 5
Overload Characteristic / Überlastverhalten
Fig. 6 / Bild 6
DC-OK Signal (except / außer 1606-XLEDNET3)
A
D
C
B
B
Input DC-ok
Earth
Output
-
+
N
L
Out put Volt age
0
02 6810A
4
8
12
28V
16
20
24
4
Output Current
a) 1606-XLEDNET3
b) 1606-XLSDNET4
c) 1606-XLSDNET8
a b c
250ms
21.5V
<1ms
open
24V
openclosed closed
>1ms
Fig. 7 / Bild 7 Physical Dimensions / Abmessungen
1606-XLEDNET3 1606-XLSDNET4 1606-XLSDNET8
10000075774 (version 00)
PU-348.011.39-10A

Transcripción de documentos

1 2 3 4 5 6 EN DE FR ES IT PT Instruction Manual Bedienungsanleitung Manual d'instructions Manual de instrucciones Manuale di Istruzione Manual de Instruções DC Power Supply DC Stromversorgung DC Alimentation d'Énergie DC Fuente De Alimentación DC Gruppo di alimentazione DC Fonte De Alimentação DeviceNet® Series 1606-XLEDNET3 1606-XLSDNET4 1606-XLSDNET8 Read this first! English 1 Before operating this unit please read this manual thoroughly and retain this manual for future reference! This device may only be installed and put into operation by qualified personnel. If damage or malfunction should occur during operation, immediately turn power off and send unit to the factory for inspection. The unit does not contain serviceable parts. The tripping of an internal fuse (if included) is caused by an internal defect. The information presented in this document is believed to be accurate and reliable and may change without notice. For any clarifications the English translation will be used. Intended Use: This power supply is designed for installation in an enclosure and is intended for the general use such as in industrial control, office, communication, and instrumentation equipment. Do not use this power supply in aircrafts, trains and nuclear equipment where malfunction may cause severe personal injury or threaten human life. WARNING Risk of electrical shock, fire, personal injury or death. 1) Do not use the power supply without proper grounding (Protective Earth). 2) Turn power off before working on the device. Protect against inadvertent re-powering. 3) Make sure that the wiring is correct by following all local and national codes. 4) Do not modify or repair the unit. 5) Do not open the unit as high voltages are present inside. 6) Use caution to prevent any foreign objects from entering into the housing. 7) Do not use in wet locations or in areas where moisture or condensation can be expected. 8) Do not touch during power-on, and immediately after power-off. Hot surface may cause burns. CAUTION Reduction of output current may be necessary when: 1) Minimum installation clearance can not be met. 2) Altitude is higher than 2000m. 3) Device is used above +60°C ambient. 4) Mounting orientation is other than output and input terminal located at the bottom of the unit. 5) Airflow for convection cooling is obstructed. Details for de-rating can be found in this manual and in the datasheet of the unit.. WARNING EXPLOSION HAZARDS (Notes for use in hazardous locations only) Units which are marked with "Class I Div 2" are suitable for use in non-hazardous or Class I Division 2 Groups A, B, C, D locations. Substitution of components may impair suitability for Class I Division 2 environment. Do not disconnect equipment unless power has been switched off. Wiring must be in accordance with Class I, Division 2 wiring methods of the National Electrical Code, NFPA 70, and in accordance with other local or national codes. Vor Inbetriebnahme lesen! Deutsch 2 Bitte lesen Sie diese Warnungen und Hinweise sorgfältig durch, bevor Sie das Gerät in Betrieb nehmen. Bewahren Sie die Anleitung zum Nachlesen auf. Das Gerät darf nur durch fachkundiges und qualifiziertes Personal installiert werden. Bei Funktionsstörungen oder Beschädigungen schalten Sie sofort die Versorgungsspannung ab und senden das Gerät zur Überprüfung ins Werk. Das Gerät beinhaltet keine Servicebauteile. Interne Sicherungen (falls vorhanden) lösen nur bei Gerätedefekt aus. Die angegebenen Daten dienen allein der Produktbeschreibung und sind nicht als zugesicherte Eigenschaften im Rechtssinne aufzufassen. Im Zweifelsfall gilt der englische Text Bestimmungsgemäßer Gebrauch: Diese Stromversorgung ist für den Einbau in ein Gehäuse konzipiert und zur Verwendung für allgemeine elektronische Geräte, wie z.B. Industriesteuerungen, Bürogeräte, Kommunikationsgeräte oder Messgeräte geeignet. Benutzen Sie diese Stromversorgung nicht in Steuerungsanlagen von Flugzeugen, Zügen oder nuklearen Einrichtungen, in denen eine Funktionsstörung zu schweren Verletzungen führen oder Lebensgefahr bedeuten kann. WARNUNG Missachtung nachfolgender Punkte kann einen elektrischen Schlag, Brände, schwere Unfälle oder Tod zur Folge haben. 1) Betreiben Sie die Stromversorgung nie ohne Schutzleiter. 2) Schalten Sie die Eingangsspannung vor Installations-, Wartungs- oder Änderungsarbeiten ab und sichern Sie diese gegen unbeabsichtigtes Wiedereinschalten. 3) Sorgen Sie für eine ordnungsgemäße und fachgerechte Verdrahtung. 4) Führen Sie keine Änderungen oder Reparaturversuche am Gerät durch. 5) Gerät niemals öffnen. Im Inneren befinden sich gefährliche Spannungen. 6) Verhindern Sie das Eindringen von Fremdkörpern, wie z.B. Büroklammern und Metallteilen. 7) Betreiben Sie das Gerät nicht in feuchter Umgebung oder in einer Umgebung, bei der mit Betauung oder Kondensation zu rechnen ist. 8) Gehäuse nicht während des Betriebes oder kurz nach dem Abschalten berühren. Heiße Oberflächen können Verletzungen verursachen. VORSICHT Rücknahme der Ausgangsleistung kann erforderlich sein: 1) wenn die minimalen Einbauabstände nicht eingehalten werden können. 2) bei Aufstellhöhen über 2000m. 3) Betrieb bei Umgebungstemperaturen über +60°C. 4) bei Einbaulagen abweichend von der Standardeinbaulage (Eingang und Ausgang an der Unterseite des Gerätes). 5) bei behinderter Luftzirkulation. Details zur Leistungsrücknahme befinden sich in dieser Betriebsanleitung oder im Datenblatt des Gerätes. ACHTUNG EXPLOSIONSGEFAHR! (Hinweise für den Betrieb in explosionsgefährdeter Umgebung) Geräte, die am Leistungsschild mit "Class I Div 2" gekennzeichnet sind, sind für den Einsatz in Klasse I Division 2 Gruppen A,B,C,D oder für nicht explosionsgefährdete Aufstellorte geeignet. Veränderungen an Bauteilen können die Tauglichkeit für Klasse I Division 2 beeinträchtigen. Anschlüsse nicht trennen, solange Spannung anliegt. Anschluss muss unter Berücksichtigung der Anforderungen nach Klasse I Division 2 Artikel 501-4(b) des National Electrical Code, NFPA 70, erfolgen. A lire avant mise sous tension! Français 3 Merci de lire ces instructions de montage et d'entretien avant de mettre l'alimentation sous tension. Conservez ce manuel qui vous sera toujours utile. Cette alimentation doit être installée par du personnel qualifié et compétent. Le déclenchement du fusible interne traduit très probablement un défaut au niveau de l'appareil. Si un défaut quelconque apparaît en cours de fonctionnement, débrancher au plus vite l'alimentation. Dans ce deux cas de figure, il convient de faire contrôler l'alimentation en usine! Les données indiquées dans ce document servent uniquement à donner une description du produit et n'ont aucune valeur juridique. En cas de divergences, le texte anglais fait foi. Utilisation: Cet appareil est conçu pour être installé dans une armoire et pour tous les équipements électroniques, tel que l'équipement industriel de commande, l'équipement de bureau, le matériel de communication et les instruments de mesures. N'utilisez pas cet appareil pour l'équipement de commandes dans les avions, les trains et l'équipement atomique où un problème de fonctionnement de l'alimentation pourrait causer des blessures graves ou menacer la vie humaine. AVERTISSEMENT Prendre en compte les points suivants, afin d'éviter toute détérioration électrique, incendie, dommage aux personnes ou mort. 1) ne jamais faire fonctionner l'alimentation sans raccordement à la terre ! 2) débrancher l'installation avant toute intervention sur l'alimentation (ou démontage) et s'assurer qu'il n'y a pas risque de redémarrage. 3) s'assurer que le câblage a été fait selon les prescriptions 4) ne pas effectuer de réparations ou modifications sur l'alimentation 5) ne pas ouvrir l'appareil. Des tensions importantes passent à l'intérieur. 6) veiller à ce qu'aucun objet ne rentre en contact avec l'intérieur de l'alimentation (trombones, pièces métalliques) 7) ne pas faire fonctionner l'appareil dans un environnement humide ou à l'extérieur, non protégé. Ne pas utiliser l'appareil dans un environnement où il peut y avoir de la condensation. 8) ne pas toucher le carter pendant le fonctionnement ou après la mise sous tension. Surface chaude risquant d’entraîner des blessures. ATTENTION Des limitations de puissance de sortie peuvent apparaître si : 1) les distances d'installation mini. ne peuvent être observées 2) installation à une altitude > 2000 m 3) pour des fonctionnements en charge et avec une température ambiante > 60°C 4) pour des positions de montage différentes de la préconisation standard (entrée en sortie dessous) 5) lorsque la circulation d'air est gênée D'autres informations sont disponibles dans la documentation de mise en service ATTENTION RISQUE D’ EXPLOSION (Utilisation Class I Div 2) Les appareils portant la marque ‘Class I Div 2’ au niveau de la plaque signalétique sont prévus pour fonctionner en Classe I, Division 2, Groupes A,B,C,D ou pour un environnement non explosif et non dangereux. Le remplacement de composants peut rendre le matériel impropre à une utilisation en Classe 1, Division 2. Ne déconnecter l’équipement qu’ hors tension ou en zone connue comme non dangereuse. Le raccordement doit obligatoirement tenir compte des exigences de la classe 1, division 2, article 501-4(b) du National Electrical Code, NFPA 70. Lea primero! Español 4 Conserve este manual como referencia para futuras consultas. La fuente de alimentación solo puede ser instalada y puesta en funcionamiento por personal cualificado. Por favor lea detenidamente este manual antes de conectar la fuente de alimentación. Cuando se funde un fusible interno, existe gran probabilidad de un fallo interno en el equipo.Si se produce un fallo o mal funcionamiento durante la operación, desconecte inmediatamente la tensión de alimentación. En ambos casos, el equipo debe ser inspeccionado en fábrica. La información presentada en este documento es exacta y fiable en cuanto a la descripción del producto y puede cambiar sin aviso. En casa de duda, prevalece el texto inglés. Uso apropiado: Este equipo ha sido diseñado para su instalación en un ambiente cerrado y ha sido concebido para uso general en instalaciones de control industrial, oficinas, comunicaciones y equipos de instrumentación. No emplee este equipo en aeronaves, trenes e instalaciones atómicas, donde un mal funcionamiento de la fuente de alimentación puede ocasionar lesiones graves o riesgo mortal. ADVERTENCIA Riesgo de descarga eléctrica, incendio, accidente grave o muerte. 1) No conectar nunca la unidad sin conexión de puesta a tierra. 2) Desconectar la tensión de red antes de trabajar en la fuente de alimentación. Evite una posible reconexión involuntaria. 3) Asegurarse de que el cableado es correcto de acuerdo a los códigos locales y nacionales. 4) No realizar ninguna modificación o reparación de la unidad. 5) No abrir nunca la unidad. En el interior existe riesgo de altas tensiones. 6) Evitar la introducción en la carcasa de objetos extraños. 7) No usar el equipo en ambientes húmedos. No operar el equipo en ambientes donde se espere la formación de rocío o condensación. 8) No tocar durante el funcionamiento ni inmediatamente después del apagado. El calor de la superficie puede causar quemaduras graves ATENCIÓN La deriva en la tensión de salida se produce: 1) cuando no pueden mantenerse las distancias mínimas de montaje. 2) en caso de que el montaje se realice en altitudes superiores a los 2000 m. 3) en caso de funcionamiento a plena carga y temperaturas ambientales superiores a +60ºC. 4) En caso de posiciones de montaje diferentes a la posición de montaje estándar (terminales abajo). 5) en caso de que la circulación de aire para la refrigeración por conducción esté obstruida. Puede encontrar más detalles del caso de deriva en este manual. ATENCIÓN PELIGRO DE EXPLOSIÓN! (Uso apropiado Class I Div 2) Los equipos marcados con la expresión "Class I Div 2" son adecuados para su uso en ambientes no peligrosos y en entornos con la Clase I División 2 Grupos A, B, C, D. La sustitución de componentes puede perjudicar la idoneidad para la Clase I División 2. No desconecte el equipo a menos que la tensión de alimentación esté desconectada. El conexionado debe cumplir con la Clase I División 2 métodos de conexión del Código Nacional Eléctrico NFPA 70 o con el resto de códigos locales o nacionales. Leggere prima questa parte! Italiano 5 Prima di collegare il sistema di alimentazione elettrica si prega di leggere attentamente le seguenti avvertenze. Conservare le istruzioni per la consultazione futura. Il sistema di alimentazione elettrica deve essere installato solo da personale competente e qualificato. In caso di intervento del fusibile interno, molto probabilmente l'apparecchio è guasto. Se durante il funzionamento si verificano anomalie o guasti, scollegare immediatamente la tensione di alimentazione. In entrambi i casi è necessario far controllare l'apparecchio dal produttore! I dati sono indicati solo a scopo descrittivo del prodotto e non vanno considerati come caratteristiche garantite dell'apparecchio.In caso di differenze o problemi è valido il testo inglese Uso previsto: Questo apparecchio è previsto per il montaggio in un rack per moduli elettronici, ad esempio per controllori industriali, apparecchiature per ufficio, unità di comunicazione o apparecchi di misura. Non utilizzare l'apparecchio in impianti di controllo di aerei, di treni o di impianti nucleari in cui il suo eventuale guasto può comportare gravi lesioni o la morte di persone. AVVERTENZA Il mancato rispetto delle seguenti norme può provocare folgorazione elettrica, incendi, gravi incidenti e perfino la morte. 1) Non far funzionare in nessun caso il sistema di alimentazione elettrica senza conduttore di protezione! 2) Prima di eseguire interventi di installazione, di manutenzione o di modifica scollegare la tensione di rete ed adottare tutti i provvedimenti necessari per impedirne il ricollegamento non intenzionale. 3) Assicurare un cablaggio regolare e corretto. 4) Non tentare di modificare o di riparare da soli l'apparecchio. 5) Non aprire l'apparecchio. Al suo interno sono applicate tensioni elettriche pericolose. 6) Impedire la penetrazione di corpi estranei nell'apparecchio, ad esempio fermagli o altri oggetti metallici. 7) Non far funzionare l'apparecchio in un ambiente umido. Non far funzionare l'apparecchio in un ambiente soggetto alla formazione di condensa o di rugiada. 8) Non toccare quando acceso e subito dopo lo spegnimento. La superficie calda può causare scottature. ATTENZIONE È necessario ridurre la potenza di uscita se: 1) non è possibile rispettare le distanze minime di montaggio; 2) l'apparecchio viene installato in un luogo di altitudine maggiore di 2000 m; 3) il funzionamento è a pieno carico a temperatura ambiente maggiore di +60°C; 4) la posizione di montaggio differisce da quella standard (ingresso, uscita in basso) 5) è ostacolata la libera circolazione dell'aria. Ulteriori informazioni sono riportate in questo manuale. ATTENZIONE: PERICOLO DI ESPLOSIONE! (Uso previsto Class I Div 2) Gli apparecchi la cui targhetta riporta "Class I Div 2" sono adatti per l'impiego in ambienti di classe I, divisione 2, gruppi A, B, C e D o non soggetti al pericolo di esplosione. La modifica dei componenti possono influenzare negativamente l'idoneità per ambienti di classe I, divisione 2.Non aprire i morsetti con tensione di alimentazione collegata. Il collegamento deve essere eseguito nel rispetto dei requisiti previsti dalla classe I, divisione 2, articolo 501-4(b) del National Electrical Code, NFPA 70. Leia primeiro! Portuguès 6 Recomendamos a leitura cuidadosa das seguintes advertências e observações, antes de colocar em funcionamento a fonte de alimentação. Guarde as Instruções para futura consulta, em casos de dúvida. A fonte de alimentação deverá ser instalada apenas por profissionais da área, tecnicamente qualificados. Se o fusível interno se fundir, é grande a possibilidade de existir um defeito no aparelho. Se por acaso, durante a utilização ocorrer algum defeito de funcionamento ou dano, desligue imediatamente a tensão de alimentação. Em ambos os casos, será necessária uma verificação na Fábrica! Os dados mencionados têm como finalidade somente a descrição do produto, e não devem ser interpretados como propriedades garantidas no sentido jurídico. Em caso de duvidas aplica-se o texto em inglês. Utilize: Apenas para o fim pré-estabelecido. Este aparelho foi concebido para ser montado dentro de invólucros, caixas ou armários para aparelhos eletrônicos em geral, como, por exemplo, comandos de instalações industriais, aparelhos para escritórios, aparelhos de comunicação ou instrumentos de medida e quadros eléctricos. Não utilize este aparelho em sistemas de comando de aviões, de comboios ou em instalações movidas por energia nuclear, nos quais um defeito de funcionamento poderá causar danos graves ou significar risco de morte. ATENÇÃO A não observância ou o incumprimento dos pontos a seguir mencionados, poderá causar uma descarga elétrica, incêndios, acidentes graves ou morte. 1) Não use a fonte de alimentação sem o condutor de proteção terra! 2) Antes de trabalhos de instalação, manutenção ou modificação, desligue a tensão de alimentação, protegendo-a contra uma nova ligação involuntária. 3) As ligações devem ser efectuadas apenas por profissionais competentes. 4) Não efectue nenhuma modificação ou tentativa de reparação no aparelho. Quando necessário contacte o seu distribuidor. 5) Não abra o aparelho mesmo quando desligado. No seu interior existem condensadores que podem estar carregados electricamente. 6) Proteger a fonte de alimentação contra a introdução inadvertida de corpos metálicos, como por ex., clipes ou outras peças de metal. 7) Não usar o aparelho em ambientes húmidos. Não usar o aparelho em ambientes propensos a condensações. 8) Não tocar enquanto estiver em funcionamento, nem após a desligar. A superficie poderá estar quente e provocar lesões. CUIDADO Será necessário reduzir a potência de saída nos seguintes casos: 1) Quando não forem observadas as distâncias mínimas de montagem. 2) Quando instaladas a altitudes superiores a 2000m. 3) Existencia de temperatura ambiente superior a +60ºC, em plena carga do aparelho. 4) Montagem invertida do aparelho (Entrada, saída em baixo). 5) Montagem em ambiente sem ventilação. No presente manual de funcionamento encontram-se ainda outras informações. ATENÇÃO, RISCO DE EXPLOSÃO! (Utilize Class I Div2) Aparelhos que contêm na sua placa de dados elétricos o texto “Class I Div 2” são apropriados para a aplicação na Classe I, divisão 2, Grupos A, B, C, D ou também para locais de instalação isentos de riscos de explosão. Modificações efetuadas em componentes podem restringir ou reduzir a adequação para aplicação na Classe I, Divisão 2. As ligações não devem ser separadas enquanto estiverem ligadas a uma fonte de alimentação elétrica. As ligações devem ser efetuadas levando-se em consideração as exigências normativas da Classe I, Divisão 2. Rockwell Automation CH-5001 Aarau, Switzerland Fax +41 62 837 2202 © 2010 by Allen-Bradley Company, LCC Industrial Components Business 1201 South Second Street Milwaukee, WI 53204-2496 USA Phone 440 646 5800 1606-XLEDNET3, 1606-XLSDNET4, 1606-XLSDNET8: Power Supply Instruction Manual 1606-XLEDNET3, 1606-XLSDNET4, 1606-XLSDNET8: Bedienungsanleitung für Stromversorgung Technical Data 1) Technische Daten 1) Output Voltage 6) Factory Setting Output Current Output Power NEC Power Classifikation 3) Output Ripple & Noise Voltage 2) Line Regulation Load Regulation 5) Temperature Coefficient Turn-on Time Turn-on Delay Turn-on Overshoot Ausgangsspannung 6) Werkseinstellung Ausgangsstrom Ausgangsleistung Klassifizierung nach NEC 3) Ausgangswelligkeit 2) Netzausregelung 5) Lastausregelung Temperaturgang Einschaltzeit Einschaltverzögerung Überschwingen beim Einschalten AC Input Voltage AC Eingangsspannung Input Frequency 7) AC Input Current 6) Power Factor EN 61000-3-2 Eingangsfrequenz 7) AC Eingangsstrom 6) Leistungsfaktor EN 61000-3-2 Input Inrush Current Hold-up Time 4) 6) 6) Einschaltspitzenstrom Pufferzeit 1606-XLEDNET3 1606-XLSDNET4 1606-XLSDNET8 DC 24.1V fixed / fest eingestellt 3.3A 79.5W NEC Class 2 50mVpp 0.1% 0.3% 0.03% / °C 90ms 100ms 400mV DC 24.1V fixed / fest eingestellt 3.8A 91.2W NEC Class 2 50mVpp 0.1% 0.3% 0.03% / °C 100ms 200ms 400mV DC 24-24.5V 24.1V 8A 196W NEC Class 1 50mVpp 0.1% 0.3% 0.03% / °C 85ms 600ms 400mV nom. 120 / 230Vac, typ. 120 / 230Vac, typ. PFC-Norm AC 100-240V ±15% 50-60Hz ±6% 1.6A -0.7A 0.61 / 0.56 Yes / Ja AC 100-240V -15/+10% 50-60Hz ±6% 1.1A - 0.5A 0.98 / 0.9 Yes / Ja AC 100-240V ±15% 50-60Hz ±6% 2.3A - 1.0A 0.98 / 0.92 Yes / Ja nom. “Single-Use”, typ. nom. PowerBoost - max. max max typ. typ. typ. max. Nom. 4) 6) 6) 2) 2 2 2 typ. 45A peak, 1.7A s 11A peak, 1.1A s 7A peak, 0.6A s 120 / 230Vac, typ. 30 / 128ms 44 / 85ms 33 / 34ms 120 / 230Vac, typ. 120 / 230Vac, typ. 88.0% / 89.8% 11.1W / 9.1W 91.4 / 92.0% 8.6 / 7.9W 92.3 / 92.7% 16.0 / 15.1W nom. 60°C … 70°C nom. -25°C - +70°C 1.8W/°C -40°C - +85°C -25°C - +70°C 2W/°C -40°C - +85°C -25°C - +70°C 5W/°C -40°C - +85°C Efficiency Power Losses 6) Wirkungsgrad Verlustleistung 6) Operational Temperature Range Output Derating Storage Temperature Range Betriebstemperaturbereich Leistungsrücknahme Lagertemperaturbereich Humidity 8) Feuchte 8) IEC 60068-2-30 5 - 95% r.H. 5 - 95% r.H. 5 - 95% r.H. Vibration Shock Schwingen Schocken IEC 60068-2-6 IEC 60068-2-27 2g 30g 6ms, 20g 11ms 2g 30g 6ms, 20g 11ms 2g 30g 6ms, 20g 11ms Degree of Pollution (not conductive) Degree of Protection Class of Protection Over-temperature Protection 10) 10) Output Over-voltage Protection Touch (Leakage) Current 11) Return Voltages Resistance 12) Verschmutzungsgrad (nicht leitend) Schutzart Schutzklasse Übertemperaturschutz 10) Überspannungsschutz Ausgang 10) PE- Ableitstrom 11) Rückspeisefestigkeit 12) EN 50178 / 62103 EN 60529 IEC 61140 OTP OVP, max. max. max. 2 IP20 9) I Yes / Ja 39Vdc 0.32mA / 0.57mA 35Vdc 2 IP20 9) I Yes / Ja 29Vdc 0.22mA / 0.4mA 28Vdc 2 IP20 9) I Yes / Ja 29.5Vdc 0.38mA / 0.74mA 35Vdc Dimensions 15) (WxHxD) Weight Abmessungen 15) (BxHxT) Gewicht nom. max. 32x124x102mm 430g; 0.95lb 40x124x117mm 620g; 1.37lb 60x124x117mm 900g; 1.98lb - Æ 16) Æ 16) Æ 16) Years / Jahre 1 1 1 Approvals Zulassungen Limited Warranty Gewährleistung 1) All parameters are specified at 230Vac, nominal output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. Mounting orientation is input terminals on the bottom and output terminals on top of the unit. 2) Input voltage variation between 85Vac and 264Vac and full loaded output. 3) 50-Ohm measurement, bandwidth 20MHz 4) 1606-XLEDNET3: at 230Vac, 40°C and cold-start, temperature and input voltage dependent. 1606-XLSDNET4 and 1606-XLSDNET8: Input inrush current electronically limited and is temperature independent. 5) Load deviations from no-load full-load 6) At nominal load and nominal input voltage. 7) At nominal load and the lower end of the input voltage. 8) Do not energize while condensation is present. 9) PE connection required (Ground). 10) Output shut-down with automatic restart attempts. 11) PE Leakage current at 132Vac, 60Hz / 264Vac, 50Hz, TT/TN-mains. 12) Loads such as decelerating motors and inductors can feed voltage back to the output of the power supply. The figure represents the maximum allowed feed back voltage 13) Including an external 7000µF capacitor 14) Time between turn-on and 23V output voltage 15) Depth without DIN-rail. 16) See datasheet or markings on the unit. 1) Alle Werte gelten bei 230Vac, Nennausgangsstrom, 25°C Umgebung und nach einer Aufwärmzeit von 5 Minuten, wenn nichts anderes angegeben ist. Einbaulage: Eingang unten und Ausgang oben. 2) Eingangsspannungsänderungen zwischen 85Vac und 264Vac, Ausgang voll belastet. 3) 50-Ohm Messung, Bandbreite 20MHz 4) 1606-XLEDNET3: bei 230Vac, 40°C und Kaltstart. Abhängig von Temperatur und Eingangsspannung. 1606-XLSDNET4 and 1606-XLSDNET8: Der Einschaltstromstoß ist elektronisch begrenzt und temperaturunabhängig. 5) Lastwechsel von Leerlauf bis Volllast 6) Bei Nominallast und Nenneingangsspannung. 7) Bei Nominallast und dem unteren Ende der Eingangsspannung. 8) Nicht betreiben, solange das Gerät Kondensation aufweist. 9) PE Verbindung erforderlich. 10) Ausgang schaltet ab und macht regelmäßig automatische Startversuche. 11) Erd-Ableitstrom bei 132Vac, 60Hz / 264Vac, 50Hz, TT/TN-Netze. 12) Bremsende Motoren oder Induktivitäten können Spannung zum Ausgang des Netzteils rückspeisen. Der Wert gibt die max. zulässige Rückspeisespannung an. 13) Mit angeschlossenen externen zusätzlichem 7000µF Kondensator 14) Zeit zwischen Einschalten und Erreichen von 23V Ausgangsspannung 15) Tiefe ohne DIN-Schiene. 16) Siehe Datenblatt oder Prüfzeichen auf dem Gerät. Installation Installation Use DIN-rails according to EN 60715 or EN 50022 with a height of 7.5 or 15mm. Mounting orientation must be output terminals on the top and input terminals on the bottom. For other orientations see datasheet. Do not obstruct air flow as the unit is convection cooled. Ventilation grid must be kept free of any obstructions. The following installation clearances must be kept when power supplies are permanently loaded with more than 50% of the nominal current:: Left / right: 5mm (15mm in case the adjacent device is a heat source) 40mm on top, 20mm on the bottom of the unit. Geeignet für DIN-Schienen entsprechend EN 60715 oder EN 50022 mit einer Höhe von 7,5 oder 15mm. Der Einbau hat so zu erfolgen, dass der Eingang sich unten und die Ausgang sich oben befindet. Für andere Einbaulagen siehe Datenblatt. Luftzirkulation nicht behindern! Die Geräte sind für Konvektionskühlung ausgelegt. Es ist für ungehinderte Luftzirkulation zu sorgen. Folgende Einbauabstände werden bei dauerhafter Belastung >50% des Nennstromes empfohlen: Links / rechts: 5mm (15mm bei benachbarten Wärmequellen) Oben: 40mm, unten 20mm vom Gerät. Input Fuses Sicherungen am Eingang All units have internal input fuses included, which are not user accessible. The units are tested and approved for branch circuits up to 20A. An external protection is only required if the supplying branch has an ampacity greater than this, however, in some countries local regulations might apply. Check local codes and requirements. If external fuses are necessary or utilized, minimum requirements need to be considered to avoid nuisance tripping of the circuit breaker. The following minimum values are recommended: 1606-XLEDNET3: 10A B- or 6A C-Characteristic 1606-XLSDNET4: 6A B- or 3A C-Characteristic 1606-XLSDNET8: 6A B- or 4A C-Characteristic Alle Geräte besitzen interne Eingangssicherungen, die nicht anwenderzugänglich sind. Die Geräte sind geprüft und zugelassen zum Anschluss an Stromkreisen bis max.32A. Ein zusätzlicher externer Schutz ist nur erforderlich, wenn der Speisestromkreis mit einem höheren Wert abgesichert ist oder nationale Richtlinien es vorschreiben. Falls externe Schutzelemente verwendet werden, sollen diese nicht kleiner als folgende Werte sein, um ein fehlerhaftes Auslösen zu vermeiden: 1606-XLEDNET3: 10A B- oder 6A C-Charakteristik 1606-XLSDNET4: 6A B- oder 3A C-Charakteristik 1606-XLSDNET8: 6A B- oder 4A C-Charakteristik EMC Electromagnetic Compatibility EMV Elektromagnetische Verträglichkeit These power supplies are suitable for applications in industrial environment as well as in residential, commercial and light industry environment without any restrictions. These devices comply with FCC Part 15 rules. CE mark is in conformance with EMC guidelines 89/336/EC, 93/68/EC and 2004/108/EC as well as the low-voltage directives (LVD) 73/23/EC, 93/68/EC, 2006/95/EC. EMC Immunity: EN 61000-6-1, EN 61000-6-2 EMC Emission EN 61000-6-3, EN 61000-6-4, FCC Part 15 Class B Diese Stromversorgungen erfüllen die Anforderungen für Anwendungen in industrieller Umgebung und für den Wohn-, Geschäfts- und Gewerbebereich ohne Einschränkungen. Die Geräte erfüllen auch die Anforderungen der FCC Teil 15. Das CE Zeichen ist angebracht und erklärt die Erfüllung der EMV Richtlinien 89/336/EG, 93/68/EG und 2004/108/EG wie auch der Niederspannungsrichtlinien 73/23/EG, 93/68/EG, 2006/95/EG. Störfestigkeit: EN 61000-6-1, EN 61000-6-2 Störaussendung: EN 61000-6-3, EN 61000-6-4, FCC Part 15 Klasse B 1606-XLEDNET3, 1606-XLSDNET4, 1606-XLSDNET8: Power Supply Instruction Manual 1606-XLEDNET3, 1606-XLSDNET4, 1606-XLSDNET8: Bedienungsanleitung für Stromversorgung Terminals and Wiring Anschlussklemmen und Verdrahtung Use appropriate copper cables that are designed for a minimum operating temperatures of 60°C (for ambient up to 45°C) and 75°C (for ambient up to 60°C). Follow national installation codes and regulations! Ensure that all strands of a stranded wire enter the terminal connection! Up to two stranded wires with the same cross section are permitted in one connection point (except for the PE wire). Ferrules are allowed, but not required. Unused terminal spaces must be closed. 1606-XLEDNET3: Solid wire / Stranded wire / AWG 0.5-6mm2 / 0.5-4mm2 / 20-10 AWG Wire stripping length 7mm / 0.28inch Tightening torque 0.8Nm / 7lb.inch 1606-XLSDNET4: Input terminals: 2 2 Solid wire / Stranded wire / AWG 0.5-6mm / 0.5-4mm / 20-10 AWG Wire stripping length 7mm / 0.28inch Output and signal terminals: 2 2 Solid wire / Stranded wire / AWG 0.3-4mm / 0.3-2.5mm / 26-12 AWG Wire stripping length 6mm / 0.25inch 2 2 1606-XLSDNET8: Solid wire / Stranded wire / AWG 0.5-6mm / 0.5-4mm / 20-10 AWG Wire stripping length 7mm / 0.28inch Verwenden Sie geeignete Kupferkabel, die mindestens für 60°C bei einer Umgebungstemperatur bis zu 45°C und 75°C bei einer Umgebungstemperatur bis zu 60°C zugelassen sind. Beachten Sie nationale Bestimmungen und Installationsvorschriften! Stellen Sie sicher, dass keine einzelnen Drähte von Litzen abstehen. Bis zu zwei Leiter mit gleichem Querschnitt sind in einem Anschlusspunkt zulässig (außer beim Schutzleiter). Aderendhülsen sind erlaubt, aber nicht erforderlich. Nichtbenutzte Klemmen immer zudrehen. 2 2 1606-XLEDNET3: Starrdraht / Litze / AWG 0,5-6mm / 0,5-4mm / 20-10 AWG Abisolierlänge 7mm / 0,28inch Empf. Anzugsdrehmoment 0,8Nm / 7lb.inch 1606-XLSDNET4: Eingangsklemmen: 2 2 Starrdraht / Litze / AWG 0,5-6mm / 0,5-4mm / 20-10 AWG Abisolierlänge 7mm / 0,28inch Ausgangs- und Signalklemmen: Starrdraht / Litze / AWG 0,3-4mm2 / 0,3-2,5mm2 / 26-12 AWG Abisolierlänge 6mm / 0,25inch 2 2 1606-XLSDNET8: Starrdraht / Litze / AWG 0,5-6mm / 0,5-4mm / 20-10 AWG Abisolierlänge 7mm / 0,28inch Output- and Overload Characteristic (see Fig. 5) Ausgangs- und Überlastverhalten (siehe Bild 5) The units are overload, no-load, short-circuit proof. At overload, the output current flows continuously. The unit does not switch-off or hiccup at overload. Die Geräte sind leerlauf-, überlast- und kurzschlussfest. Bei Überlast fließt kontinuierlich Strom. Die Geräte schalten nicht ab und haben auch keinen „Hiccup“ Modus. DC-OK Relay Contact except 1606-XLEDNET3 (see Fig. 6) DC-OK Relais Kontakt außer 1606-XLEDNET3 (siehe Bild 6) This feature monitors the output voltage, which is produced by the power supply, and is independent of a return voltage from a unit which is connected in parallel. Contact closes when the output voltage reaches 20.5V Contact opens when the output voltage dips more than 10%. Short dips will be extended to a length of 250ms. Dips shorter than 1ms will be ignored. Contact ratings: max.: 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A, Resistive load, min.: 1mA Diese Funktion überwacht die vom Gerät erzeugte Ausgangsspannung und lässt sich von einer rückwärts eingespeisten Spannung nicht beeinflussen (z.B.: bei Parallelschaltung) Kontakt schließt sobald die Ausgangsspannung 21,5V erreicht Kontakt öffnet sobald der Ausgang um mehr als 10% einbricht. Kurze Einbrüche werden auf 250ms verlängert. Einbrüche kürzer 1ms werden ignoriert. Belastbarkeit: max.: 60Vdc 0,3A; 30Vdc 1A; 30Vac 0,5A; (R-Last); min.: 1mA Dielectric Strength (see Fig. 4) Isolationsfestigkeit (siehe Bild 4) The output voltage is floating and separated from the input according to SELV (IEC/EN 60950-1) and PELV (EN 60204-1, EN 50178; IEC 62103, IEC 60364-4-41) requirements. Type and factory tests are conducted by the manufacturer. Field tests may be conducted in the field using the appropriate test equipment which applies the voltage with a slow ramp (2s up and 2s down). Connect phase and neutral together as well as all output poles before the test is conducted. Die Ausgangsspannung hat keinen galvanischen Bezug zur Erde oder Schutzleiter und ist zum Eingang nach den SELV (IEC/EN 60950-1) und PELV (EN 60204-1, EN 50178, IEC 62103, IEC 60364-4-41) Standards getrennt. Typ- und Stückprüfungen werden beim Hersteller durchgeführt. Wiederholungsprüfungen dürfen mittels geeigneten Prüfgenerators mit langsam (2s) ansteigenden und abfallenden Spannungsrampen in der Anwendung erfolgen. Vor den Tests sind Phase und Neutralleiter wie auch alle Ausgangspole miteinander zu verbinden. A B C D Typprüfung (60s) 2500Vac 3000Vac 500Vac 500Vac Stückprüfung (5s) 2500Vac 2500Vac 500Vac 500Vac Wiederholungsprüfung (5s) 2000Vac 2000Vac 500Vac 500Vac Type Test (60s) Factory Test (5s) Field Test (5s) A 2500Vac 2500Vac 2000Vac B 3000Vac 2500Vac 2000Vac C 500Vac 500Vac 500Vac D 500Vac 500Vac 500Vac Fig. 1 / Bild 1 1606-XLEDNET3: Functional Diagram / Funktionsschaltbild Fig. 2 / Bild 2 1606-XLSDNET4: Functional Diagram / Funktionsschaltbild Output Voltage Regulator Output Voltage Regulator L N Input Fuse & Input Filter Input Rectifier & NTC Inrush Limiter Power Converter Output OverVoltage Protection Input L N Input Fuse Input Filter Input Rectifier Active Transient Filter & Inrush Current Limiter Temperature Shutdown 24 B D ab 10000075774 (version 00) PU-348.011.39-10A L N Input Fuse Input Filter Input Rectifier Active Transient Filter & Inrush Current Limiter Overload lamp DC-ok lamp DC-ok Relay c Temperature Shutdown DC-ok contact PFC Converter Output OverVoltage Protection Output Power Manager Power Converter Output Voltage Monitor Output Filter DC-ok Relay 21.5V <1ms >1ms 250ms 8 + 4 0 0 2 4 6 8 10A Output Current Fig. 7 / Bild 7 Physical Dimensions / Abmessungen 1606-XLSDNET4 open closed 1606-XLSDNET8 open VOUT + + Overload lamp DC-ok lamp Fig. 6 / Bild 6 DC-OK Signal (except / außer 1606-XLEDNET3) a) 1606-XLEDNET3 b) 1606-XLSDNET4 c) 1606-XLSDNET8 12 - 1606-XLEDNET3 + + - 24V 16 Output C Output Voltage Monitor 28V 20 A Output OverVoltage Protection Output Power Manager Output Filter Output Voltage DC-ok Earth Power Converter PFC Converter Output Voltage Regulator Fig. 5 / Bild 5 Overload Characteristic / Überlastverhalten B L N Output Filter + + DC ok Fig. 4 / Bild 4 Insulation / Isolation Fig. 3 / Bild 3 1606-XLSDNET8: Functional Diagram / Funktionsschaltbild closed DC-ok contact