Automation Direct RS485 Guía del usuario

Tipo
Guía del usuario
Motors | Automation | Energy | Transmission & Distribution | Coatings
RS485 Communication Module
Módulo de Comunicación RS485
Módulo de Comunicação RS485
CFW300-CRS485
Installation, Configuration and Operation Guide
Guía de Instalación, Configuración y Operación
Guia de Instalação, Configuração e Operação
WEG Drives & Controls - Automação LTDA.
Jaraguá do Sul - SC - Brazil
Phone 55 (47) 3276-4000 - Fax 55 (47) 3276-4020
São Paulo - SP - Brazil
Phone 55 (11) 5053-2300 - Fax 55 (11) 5052-4212
automacao@weg.net
www.weg.net
1 INFORMAÇÕES DE SEGURANÇA
1.1 AVISOS DE SEGURANÇA
NOTA!
Somente utilizar o módulo RS485 (CFW300-CRS485) nos inversores
WEG série CFW300.
Recomenda-se a leitura do manual do usuário do CFW300 antes
de instalar ou operar esse acessório.
O conteúdo deste guia fornece informações importantes para o
correto entendimento e bom funcionamento deste módulo.
1.2 RECOMENDAÇÕES PRELIMINARES
ATENÇÃO!
Sempre desconecte a alimentação geral antes de conectar ou
desconectar os acessórios do inversor de frequência CFW300.
Aguarde pelo menos 10 minutos para garantir a desenergização
completa do inversor.
2 INFORMAÇÕES GERAIS
Este guia orienta na instalação, configuração e operação do módulo RS485
(CFW300-CRS485).
3 CONTEÚDO DA EMBALAGEM
Ao receber o produto, verificar se a embalagem contém:
Acessório em embalagem anti-estática.
Guia de instalação, configuração e operação.
4 INSTALAÇÃO DO ACESRIO
O CFW300-CRS485 é facilmente conectado ao inversor de frequência CFW300
utilizando o conceito “plug-and-play”. Os procedimentos abaixo devem ser
seguidos para a correta instalação e colocação em funcionamento:
1. Com o inversor desenergizado, retire a tampa de acessórios de comunicação
do inversor Figura A1.
2. Encaixe o acessório a ser instalado conforme indicado na Figura A1.
3. Energize o inversor.
5 CONFIGURAÇÕES
As conexões da interface RS485 devem ser feitas no conector conforme Tabela 1.
Tabela 1: Sinais do conector da interface RS485
Conector Descrição
25 RS485 - A (-) RS485 (Terminal A)
26 RS485 - B (+) RS485 (Terminal B)
27 GND Referência 0 V
28 Shield Blindagem do cabo
29 GND Referência 0 V
A localização da DIP-switch para seleção da terminação da rede RS485 pode
ser melhor visualizada na Figura A2 e deve ser configurada conforme Tabela 2. É
apresentado na Figura A3 um exemplo de conexão do acessório CFW300-CRS485
com uma rede RS485, a ligação está de acordo com as recomendões do manual
do usuário do Modbus RTU para o CFW300.
Tabela 2: Configurações das chaves para configuração da RS485
Comunicação Chave Ajuste das Chaves Opção
RS485
S1
(*)
S1.1 = OFF e S1.2 = OFF Terminação RS485 desligada
S1.1 = ON e S1.2 = ON
Terminação RS485 ligada
(**)
(*) Qualquer outra combinação das chaves não é permitida.
(**) Recomenda-se o uso desta terminação com o uso de cabos maiores de 3 m.
O módulo CFW300-RS485 possui os recursos necessários para realizar
parametrização, comando e monitoração do inversor através do software WPS
- WEG Programming Suite (dispovel em www.weg.net). Para mais detalhes
consulte o catulo 7 do manual do usuário do CFW300.
NOTA!
O conector mini USB (ver Figura A2) é utilizado somente para
comunicação com o kit CFW300-KHMIR.
Não é permitida a utilização do conector mini USB para outras
conexões.
PortuguêsAPPENDIX A - FIGURES
ANEXO A - FIGURAS
(a) Removal of the communication accessory cover
(a) Remoción de la tapa de accesorios de comunicación
(a) Remoção da tampa de acessórios de comunicação
(b) Accessory connection
(b) Conexión del accesorio
(b) Conexão de acessório
Figure A1: (a) to (b): Installation of accessory
Figura A1: (a) a (b): Instalacn de accesorio
Figura A1: (a) a (b): Instalação de acessório
RS485 interface connector
Conector interfaz RS485
Conector da interface RS485
Mini USB
B+ A-
21.2 [0.835]
62.5 [2.461]
29.5 [1.162]
Figure A2: CFW300-CRS485 dimensions in mm [in] and connectors location
Figura A2: Dimensiones del CFW300-CRS485 en mm [in] y localización de los
conectadores
Figura A2: Dimensões do CFW300-CRS485 em mm [in] e localização dos conectores
Ref (0 V) Ref (0 V)
Shield
25 26 27 28 29
Shield
A (-) A (-)
B (+) B (+)
Figure A3: Example of connection of the accessory to the RS485 network
Figura A3: Ejemplo de conexión del accesorio en la red RS485
Figura A3: Exemplo de conexão do acessório na rede RS485
Document: 10003311593 / 01
13123358
DIP
English
Español
1 SAFETY INFORMATION
1.1 SAFETY WARNINGS
NOTE!
Only use the RS485 module (CFW300-CRS485) on WEG CFW300
series inverters.
It is recommended to read the CFW300 user’s manual before
installing or operating this accessory.
The content of this guide provides important information for the full
understanding and proper operation of this module.
1.2 PRELIMINARY RECOMMENDATIONS
ATTENTION!
Always disconnect the general power supply before connecting or
disconnecting the accessories of the CFW300 frequency inverter.
Wait for at least 10 minutes for the full discharge of the inverter.
2 GENERAL INFORMATION
This guide provides directions for the installation, configuration and operation of
the RS485 module (CFW300-CRS485).
3 PACKAGE CONTENT
Upon receiving the product, check if the package contains:
Accessory in anti-static package.
Installation, configuration and operation guide.
4 INSTALLATION OF THE ACCESSORY
The CFW300-CRS485 is easily connected to the CFW300 frequency inverter by
means of the plug-and-play concept. The procedures below must be observed
for the proper installation and start-up:
1. With the inverter de-energized, remove the inverter communication accessory
cover Figure A1.
2. Fit the accessory to be installed as shown in Figure A1.
3. Power up the inverter.
5 CONFIGURATIONS
The RS485 interface connections must be done on the connector as per Table 1.
Table 1: Connector signals of the RS485 interface
Connector Description
25 RS485 - A (-) RS485 (Terminal A)
26 RS485 - B (+) RS485 (Terminal B)
27 GND Reference 0 V
28 Shield Cable shield
29 GND Reference 0 V
The location of the DIP switch to select the RS485 network termination can be
better viewed in Figure A2 and it must be configure as per Table 2. Figure A3
shows a connection example of the CFW300-CRS485 accessory to a RS485
network. The connection complies with the directions of the user's manual of the
Modbus RTU for the CFW300.
Table 2: Configuration of the switches to configure the RS485
Comunication Switch Switch Setting Option
RS485
S1
(*)
S1.1 = OFF and S1.2 = OFF RS485 termination off
S1.1 = ON and S1.2 = ON
RS485 termination on
(**)
(*) Any other combination of the switches is not allowed.
(**) It is recommended to use this termination with cables longer than 3 m.
The CFW300-CRS485 module has the necessary resources to perform setting,
command and monitoring of the inverter by means of the WPS software - WEG
Programming Suite (available on www.weg.net). For further details, refer to chapter
7 of the user's manual of the CFW300.
NOTE!
The mini USB connector (see Figure A2) is used for communication
with the CFW300-KHMIR kit only.
The use of the mini USB connector for other connections is not
permitted.
1 INFORMACIONES DE SEGURIDAD
1.1 AVISOS DE SEGURIDAD
¡NOTA!
Solamente utilice el módulo RS485 (CFW300-CRS485) en los
convertidores WEG serie CFW300.
Se recomienda la lectura del manual del usuario del CFW300 antes
de instalar o operar este accesorio.
El contenido de esta guía provee informaciones importantes para el
correcto entendimiento y el buen funcionamiento de este módulo.
1.2 PRELIMINARY RECOMMENDATIONS
¡ATENCIÓN!
Siempre desconecte la alimentación general antes de conectar o
desconectar los accesorios del convertidor de frecuencia CFW300.
Aguarde por lo menos 10 minutos para garantizar la desenergización
completa del convertidor.
2 INFORMACIONES GENERALES
Esta guía orienta en la instalación, configuración y operación del módulo RS485
(CFW300-CRS485).
3 CONTENIDO DEL EMBALAJE
Al recibir el producto, verificar si el embalaje contiene:
Accesorio en embalaje antiestático.
Guía de instalación, configuración y operación.
4 INSTALACIÓN DEL ACCESORIO
El CFW300-CRS485 es fácilmente conectado al convertidor de frecuencia CFW300
utilizando el concepto “plug-and-play”. Los procedimientos de abajo debe ser
seguidos para la correcta instalación y puesta en funcionamiento:
1. Con el convertidor sin tensión, retire la tapa de los accesorios de comunicación
del convertidor Figura A1.
2. Encaje el accesorio a ser instalado conforme es indicado en la Figura A1.
3. Energice el convertidor.
5 CONFIGURACIONES
Las conexiones de la interfaz RS485 deben ser hechas en el conector, conforme
la Tabla 1.
Tabla 1: Señales del conector de la interfaz RS485
Conector Descripción
25 RS485 - A (-) RS485 (Terminal A)
26 RS485 - B (+) RS485 (Terminal B)
27 GND Referencia 0 V
28 Shield
Blindaje del cable
29 GND Referencia 0 V
La localizacn de las DIP-switches para selección de la terminacn de la red
RS485 pueden ser mejor visualizadas en la Figura A2 e deben ser configurado
conforme la Tabla 2. En la Figura A3 es presentado un ejemplo de conexn del
accesorio CFW300-CRS485 con una red RS485, la conexión está de acuerdo con
las recomendaciones del manual del usuario del Modbus RTU para el CFW300.
Tabla 2: Configuraciones de las llaves para configuración de la RS485
Comunicación Llave Ajuste de las Llaves Opción
RS485
S1
(*)
S1.1 = OFF y S1.2 = OFF Terminación RS485 apagada
S1.1 = ON y S1.2 = ON
Terminación RS485 encendida
(**)
(*) Cualquier otra combinación de las llaves no está permitida.
(**) Se recomienda el uso de esta terminación con el uso de cables mayores de 3 m.
El módulo CFW300-RS485 cuenta con los recursos necesarios para realizar
parametrización, comando y monitoreo del convertidor, a través del software
WPS - WEG Programming Suite (disponible en www.weg.net). Para más detalles
consulte el capítulo 7 del manual del usuario del CFW300.
¡NOTA!
El conector mini USB (ver Figura A2) es utilizado solamente para
comunicación con el kit CFW300-KHMIR.
No está permitida la utilizacn del conector mini USB para otras
conexiones.
  • Page 1 1
  • Page 2 2

Automation Direct RS485 Guía del usuario

Tipo
Guía del usuario