Tripp Lite Owner's Manual Extended-Run Battery Cabinet -BP240V65, BP240V65-NIB, BP240V65L, BP240V65L-NIB, BP240V100, BP240V100-NIB, BP240V100L, BP240V100L-NIB El manual del propietario

Tipo
El manual del propietario
1
Owner’s Manual
Extended-Run Battery Cabinet
Models: BP240V65, BP240V65-NIB, BP240V65L, BP240V65L-NIB,
BP240V100, BP240V100-NIB, BP240V100L, BP240V100L-NIB
Not suitable for mobile applications.
1111 W. 35th Street, Chicago, IL 60609 USA • tripplite.com/support
Copyright © 2020 Tripp Lite. All rights reserved.
Español 69 • Français 137
2
Table of Contents
1. Introduction 3
1.1 Features 3
1.2 UPS and Battery Cabinet 4
Compatibility Chart
2. Important Safety Instructions 5
2.1 Installation and Location Warnings 5
2.2 Connection Warnings 5
2.3 Battery Warnings 6
2.4 Standards Compliance 6
3. Battery Cabinet Installation 7
3.1 Preparation 7
3.2 Transportation 7
3.3 Mechanical Check 7
3.4 Package Contents 8
3.5 Internal Wiring (Typical) 8
3.6 Battery Cabinet Placement 9
3.7 Electrical Connection 9
3.8 Final Electrical Check 10
4. Mechanical Data 10
4.1 Physical Measurements 10
4.1.1 Dimensions for BP240V65, 10
BP240V65-NIB, BP240V100,
BP240V100-NIB
4.1.2 Dimensions for BP240V65L, 12
BP240V65L-NIB, BP240V100L,
BP240V100L-NIB
4.2
Physical Requirements (All Models)
14
5. Installation 15
5.1 Unpacking and Inspection 15
5.2 Selecting Installation Position 16
5.3 Power Cables 17
5.3.1 Cable Sizes 17
5.4 Battery Cabinet Connections – 17
Models BP240V65, BP240V65-NIB,
BP240V100, BP240V100-NIB
5.4.1 Remove the Chassis Shell 18
5.4.2 Battery Installation 18
and Connection
5.4.2.1 Battery Installation 22
and Setup: Models
BP240V65-NIB,
BP240V100-NIB
5.5 Battery Cabinet Connections – 32
Models BP240V65L,
BP240V65L-NIB, BP240V100L,
BP240V100L-NIB
5.5.1 Remove the Chassis Shell 32
5.5.2 Battery Installation and 33
Connection
5.5.2.1 Battery Installation 37
and Setup: Models
BP240V65L-NIB,
BP240V100L-NIB
5.6
Multiple Battery Pack Connections
48
6. Operation and Configuration 52
of S3M UPS Models
and Battery Cabinets
6.1 S3M UPS Compatibility with 52
BP240V65 to BP240V100L
Battery Cabinets
6.2 Configuring 10-20K UPS for 53
Specific Battery Cabinets using
the LCD Display
6.2.1 S3M 10-20K UPS Home Display 53
6.2.2 Setting 55
6.2.3 Battery Setup 56
6.2.4 Confiuring the S3M 10-20-NIB 57
and Optimizing Charging of
BP240V65/V65L and
BP240V100/V100L
Battery Cabinets
6.3 Configuring 25-100K UPS for 59
Specific Battery Cabinets
Using the LCD Display
6.3.1 S3M 25-100K UPS Home Display 60
6.3.2 Setting 60
6.3.3 Battery Setup: Click BATT Setup 62
6.3.4 Configuring the S3M25-100K UPS
and Optimizing Charging of the
BP240V65/V65L and
BP240V100/V100L Battery Cabinets
63
6.4 Configuring Reference Tables 66
7. Specifications 67
7.1 Battery Cabinet Specifications 67
8. Storage 67
9. Service and Warranty 68
3
1. Introduction
Tripp Lite’s Extended-Run Battery Cabinets connect to SmartOnline® UPS Systems to provide long-lasting battery backup
for data centers, telecommunications, networks, industrial facilities, security, emergency systems and other mission-critical
applications that require high capacity, high availability and extended runtime.
Battery cabinets are available in seven models, with pre-installed batteries and without: BP240V65, BP240V65-NIB,
BP240V65L, BP240V65L-NIB, BP240V100, BP240V100-NIB, BP240V100L-NIB.
The “-NIB” suffix battery cabinet models BP240V65-NIB, BP240V65L-NIB, BP240V100-NIB and BP240V40L-NIB do not include
pre-installed batteries. However, they include all of the jumper cables, fuses and breakers, enabling the flexibility to purchase
batteries separately for the battery cabinets. The BP240V65-NIB and BP240V65L-NIB battery cabinets are designed for CSB
GP12650i batteries. The BP240V100-NIB and BP240V100L-NIB battery cabinets are designed for CSB GP121000 batteries.
1.1 Features
• The battery cabinets are designed for battery string voltages of ± 120V DC and battery capacities of 65Ah or 100Ah,
@ C20 to 1.67VPC.
• Battery cabinets contain multiple 12V DC AGM batteries connected in series to achieve higher voltages.
• Each battery cabinet contains several shelves to achieve the required battery string voltages:
o BP240V65 / BP240V65-NIB: Holds 20 x 65Ah AGM batteries
o BP240V100 / BP240V100-NIB: Holds 20 x 100Ah AGM batteries
o BP240V65L / BP240V65L-NIB: Holds 40 x 65Ah AGM batteries
o BP240V100L / BP240V100L-NIB: Holds 40 x 100Ah AGM batteries
• A hinged, lockable door facilitates access to batteries for periodic maintenance.
• A minimum of 4 in. (100 mm) clearance is located above the individual batteries for access to terminals.
• The battery cabinet is constructed of heavy-gauge steel for durability.
• A baked powder-coat finish provides corrosion resistance.
• The battery cabinet ships bolted to a pallet with a double layer of protective stretch wrap and integrated corner and top
protection.
• Appropriate ventilation and convection cooling of individual batteries is provided via spacing between batteries. Front and
rear vents allow the free flow of warmer air out of the battery cabinet.
• A molded case circuit breaker is provided for overcurrent protection.
• User-supplied power output cables can be fed into the battery cabinet via built-in conduit knockouts on the bottom of
the cabinet.
• For improved safety, higher power density and minimized maintenance, the cabinet systems use Valve-Regulated Lead-Acid
(VRLA) recombinant batteries. The electrolyte in these batteries is immobilized in either an absorbent mat separator or a
gelling medium, eliminating the spilling hazards and maintenance requirements of free liquid electrolyte. There is no need
to add water or measure specific gravity.
• Because the batteries are recombinant cells that employ an oxygen recombination cycle, minimal gasses are emitted during
normal float charging. Each cell contains an individual valve, which releases the gas products from overcharge and prevents
pressure build-up within the cell.
4
1. Introduction
1.2 UPS and Battery Cabinet Compatibility Chart
Cabinets with
Internal Batteries BP240V65 BP240V65L BP240V100 BP240V100L
Cabinets with NO
Internal Batteries BP240V65-NIB BP240V65L-NIB BP240V100-NIB BP240V100L-NIB
10kVA-20kVA
UPS with Internal
Batteries
• S3M10K1B,
S3M10K2B,
S3M10K3B
• S3M15K2B
S3M15K3B
• S3M20K3B
No No No No
10kVA-20kVA UPS
with NO Internal
Batteries
• S3M10K-NIB
• S3M15K-NIB
• S3M20K-NIB
Yes Yes Yes No
Cabinets with
Internal Batteries BP240V65 BP240V65L BP240V100 BP240V100L
Cabinets with NO
Internal Batteries BP240V65-NIB BP240V65L-NIB BP240V100-NIB BP240V100L-NIB
25kVA-100kVA
UPS with NO
Internal Batteries
• S3M25K
• S3M30K
Yes Yes Yes No
• S3M50K Yes Yes Yes Yes
• S3M60K No Yes Yes Yes
• S3M80K
• S3M100K
No Yes No Yes
5
2. Important Safety Instructions
SAVE THESE INSTRUCTIONS
All sections of this manual contain instructions and warnings that must be followed during the installation and
operation of the battery cabinet described in this manual. Read ALL instructions thoroughly before attempting to
move, install or connect your battery cabinet.
Failure to heed these warnings may affect your warranty and cause serious property damage and/or personal injury.
DANGER! LETHAL HIGH-VOLTAGE HAZARD!
All wiring should be performed by a qualified electrician in accordance with the warnings in this manual
and all applicable electrical and safety codes. Incorrect wiring may cause serious personal injury and
property damage.
2.1 Installation and Location Warnings
• Install the battery cabinet in a controlled indoor environment, away from moisture, temperature extremes, flammable liquids
and gasses, conductive contaminants, dust and direct sunlight.
• Install the battery cabinet in a level, structurally sound location.
• The battery cabinet is extremely heavy. Exercise caution when moving or lifting the unit.
• Operate the battery cabinet at indoor temperatures between 0° C and 40° C only. For best results, maintain an ambient
indoor temperature of 25° C.
• Allow adequate space around the front and rear of the battery cabinet for proper ventilation. Do not block, cover or insert
objects into the battery cabinet’s external ventilation openings.
• Do not place any object on the battery cabinet, especially containers of liquid.
• Do not attempt to stack the battery cabinet. Attempting to stack the battery cabinet may cause permanent damage and
create a potential for serious personal injury.
• Do not attempt to unpack or move the battery cabinet without assistance. Use appropriate handling equipment rated to
bear the weight and bulk of the battery cabinet, such as freight elevators, pallet jacks and forklifts. (Fully extend forks
under load. Spread forks to maximum possible width under load. Lift cabinet from bottom only. Wear safety shoes.)
• For emergency use, install a fire extinguisher rated for energized electrical equipment fires (Class C rating or exact
equivalent, with a non-conductive extinguishing agent) near the battery cabinet.
2.2 Connection Warnings
• The battery cabinet contains hazardous high voltages that have the potential to cause personal injury or death from
electric shock.
• The battery cabinet has its own energy source. The output terminals may be live, even when the battery cabinet is not
connected to a UPS system.
• The battery cabinet must be suitably grounded according to all applicable electrical wiring regulations.
• Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause
the failure of the life support equipment or to significantly affect its safety or effectiveness is not recommended.
• De-energize all input and output power sources before installing cables or making electrical connections.
• Use flexible cable of sufficient length to permit battery cabinet servicing.
• Use ferrule caps to cover termination cables and prevent frayed ends from shorting on terminal blocks. Use cabling rated
VW-1, FT-1 or better. Use cable sleeves and connector clamps.
• Confirm all cables are marked correctly according to their purpose, polarity and diameter.
• Observe proper polarity by following the positive and negative markings on the unit. Failure to observe proper polarity may
damage the batteries and create a serious risk of personal injury and property damage.
6
2. Important Safety Instructions
Wiring and assembly should be performed by trained, qualified electricians only. Refer to the UPS unit’s Owner’s Manual for
wire sizing.
2.3 Battery Warnings
• The battery cabinet requires routine maintenance by qualified, knowledgeable service personnel familiar with its operation.
All required precautions should be taken prior to opening the cabinet for any reason. Keep unauthorized personnel away
from batteries.
• The battery cabinet contains valve-regulated recombinant lead-acid (VRLA) batteries. Do not attempt to add water to these
batteries or sample the electrolyte specific gravity.
• VRLA batteries can contain an explosive mixture of hydrogen gas. DO NOT SMOKE when near batteries. DO NOT cause
flames or sparks near batteries. Discharge static electricity from body before touching batteries. DO NOT open or mutilate
batteries—released electrolyte is harmful to the skin and eyes and may be toxic. DO NOT dispose of batteries in a fire—
they may explode.
• Batteries present a risk of electrical shock and burns from high short-circuit current. Battery connection or replacement
should be performed only by qualified service personnel observing proper precautions. Use tools with insulated handles.
Remove watches, rings or other metal objects. Wear rubber gloves and boots. Do not short or bridge the battery terminals
with any object. Do not lay tools or metal parts on top of batteries.
• Replace batteries with equivalent batteries (same number and type) available from Tripp Lite.
• The batteries are recyclable. Refer to local codes for disposal requirements. Do not dispose of batteries except through
approved channels in accordance with all applicable local, state and national regulations.
• Do not connect or disconnect batteries when the UPS system is operating from the battery supply or when the unit is not
in bypass mode. Disconnect the charging source prior to connection or disconnecting battery terminals.
• If the charging source remains off for an extended period of time, it should be turned on periodically to allow the batteries
to recharge. The charging source should be turned on and the batteries should be recharged at least one uninterrupted
24-hour period every 3 months. Failure to recharge the batteries periodically may cause permanent battery damage.
• Allow batteries to charge uninterrupted for 24 hours after installation.
Note on Labeling
These symbols may appear on the product label:
V : DC Voltage
: Ground
+: Battery Positive
– : Battery Negative
Refer to the product label for model numbers, voltage ratings and other important information.
2.4 Standards Compliance
• UL 1778, CSA-C22.2 No. 107.3-14 (3rd Ed)
• ISTA B (Transport, Vibration, Tilt)
7
3. Battery Cabinet Installation
Read Section 2 – Important Safety
Instructions Before Installation
3.1 Preparation
• At your site, prepare to off-load the battery cabinet from the delivery truck and transport it to the final installation location.
Consider both the packaged weight and dimensions.
• Make sure the floor can support the load of the specific battery cabinet being installed. The battery cabinet must be installed
in a structurally sound area with a level floor that is able to bear the weight of the battery cabinet and other equipment that
will be installed nearby.
• Draw a wiring schematic representing the cables connected between the battery cabinet’s output terminal blocks and any
external disconnect device, junction box and/or load/rectifier.
• If you plan to store the battery cabinet for an extended period before or after installation, follow the instructions in
section 9. Storage and Service.
3.2 Transportation
1. Inspect the shipping container(s) for visible damage (do not remove the stretch wrap around the unit until it has been
transported to the final installation location). Confirm that the model name and rating match the unit you ordered. If
you determine the unit has been damaged during shipping or if anything appears to be missing, contact Tripp Lite for
assistance. Do not attempt to use the unit if it has been damaged or mishandled.
2. Do not attempt to move or unpack the battery cabinet without assistance. Use appropriate handling equipment rated to
bear the weight and bulk of the battery cabinet, such as freight elevators, pallet jacks and forklifts. (Fully extend forks under
load. Spread forks to maximum possible width under load. Lift cabinet from bottom only. Wear safety shoes.) Confirm load
limits for freight elevators, handling equipment and floors along the transport route are not exceeded by the combined
weight of the packaged battery cabinet, handling equipment and personnel. Confirm that the packaged unit will pass
through any doorways along the intended route.
3. The battery cabinet is secured with stretch wrap to protect it during shipping and movement within a facility. Remove the
stretch wrap from the battery cabinet when the unit is in the final installation location—not before.
3.3 Mechanical Check
While the assembled cabinet battery system is still on the shipping pallet, inspect all sides for impact or other damage.
1. Open the front door of the battery cabinet.
2. Confirm none of the internal parts (batteries, terminal blocks, circuit breaker and other parts) have been damaged.
3. Note the individual battery model number and terminal type shown in section 8. Specifications.
4. Use insulated tools to tighten all battery terminal connections to the recommended torque shown in the table in section
6.3 Power Cables.
5. Use insulated tools to tighten the cables from the positive and negative output terminals at the end batteries to the
circuit breaker.
8
3. Battery Cabinet Installation
3.4 Package Contents
Part
Number
Description
BP240V65 BP240V65L BP240V65-
NIB
BP240V65L-
NIB
BP240V100 BP240V100L BP240V100-
NIB
BP240V100L-
NIB
Owners
Manual
933BF8
Yes Yes Yes Yes Yes Yes Yes Yes
Battery
Cables
731891 "Battery cables
to connect to
S3M10-20K
UPS"
2 2 2 2 2 No 2 No
Battery
Insulators
83084A/
83084B
Protective
materials
N/A N/A 4/5 8/8 N/A N/A N/A N/A
"Cabinet
Bottom Side
Metal
Skirts"
1038F7A Cover bottom
area of cabinet
2 N/A 2 N/A 2 N/A 2 N/A
"Cabinet
Bottom Side
Metal
Skirts"
1038F8A Cover bottom
area of cabinet
2 2 2 2 2 2 2 2
"Cabinet
Bottom Side
Metal
Skirts"
1038F8A Cover bottom
area of cabinet
N/A 2 N/A 2 N/A 2 N/A 2
Battery
Cables for
"-NIB"
Models
Several
P/N
For connecting
the battery
strings to the
cabinet
N/A N/A 10 16 N/A N/A 10 16
Copper
Jumper
Bars
1038F3 For intercon-
necting adjacent
batteries
N/A N/A 10 20 N/A N/A N/A N/A
Copper
Jumper
Bars
1038F4 For intercon-
necting adjacent
batteries
N/A N/A 3 8 N/A N/A N/A N/A
Copper
Jumper
Bars
1038F5 For intercon-
necting adjacent
batteries
N/A N/A N/A N/A N/A N/A 3 8
Copper
Jumper
Bars
1038F6 For intercon-
necting adjacent
batteries
N/A N/A N/A N/A N/A N/A 10 20
3.5 Internal Wiring (Typical)
• Battery cabinets use multiple 12V DC batteries connected in series to provide nominal DC voltage of 240V DC (±120V DC).
• Internal cabling is sized for specific application load currents. Do not use any other cable size other than the one provided in
the battery cabinet.
• Each battery cabinet shelf includes a specific wiring diagram. Refer to section 6. Installation for battery installation details.
• All circuit breakers are in the middle tier of the battery cabinet.
• All load connection polarities will be labeled as “+” (battery positive), “-“ (battery negative) and “N” (battery center tap)
for ±120V DC strings.
• All battery cabinets are provided with a branch circuit overcurrent protection device and may be wired directly to the load
or UPS.
9
3. Battery Cabinet Installation
3.6 Battery Cabinet Placement
Place the battery cabinet in a cool location with free airflow and away from direct heat sources. The lifespan and performance
of a battery may be dramatically affected by elevated temperature, decreasing 50% for each 8.25° C above 25° C.
1. Prepare the surface where the cabinet will be placed. The surface must be clean, flat and able to support the battery
cabinet and other equipment installed nearby. See section 8. Specifications for floor loads.
2. Allow adequate clearance around the front and rear of the battery cabinet for ventilation and maintenance. The front door
must be accessible to allow easy access to internal batteries, internal fuses and other overcurrent protection devices.
See section 6.1 Unpacking and Inspection for dimensions and battery cabinet measurements.
3. If the cabinet will be anchored to the floor, install appropriate anchor bolts in the mounting hole located at the bottom of
the cabinet. Use washers to create a level surface between the mounting areas around the anchor bolts.
4. Using extreme caution, remove the bolts securing the battery cabinet to the shipping pallet.
5. Forklift forks should be at maximum width within the cabinet clearance opening and fully inserted to prevent tipping. Lift
cabinet from bottom only. Be careful not to damage the sheet metal floor of the cabinet with the forks.
6. If the battery cabinet will be secured to the floor, carefully align and lower the battery cabinet down on the floor anchor
bolts and secure it in place.
7. If the cabinet will not be secured to the floor, lower it into the designated space and then level it using shims. Leveling
does not affect performance, but does align the battery cabinet with other equipment in the facility.
3.7 Electrical Connection
DANGER! LETHAL HIGH-VOLTAGE HAZARD!
All wiring should be performed by a qualified electrician in accordance with the warnings in this manual
and all applicable electrical and safety codes. Incorrect wiring may cause serious personal injury and
property damage.
• The battery cabinet is connected to the load through a DC circuit breaker. This allows the battery to disconnect from the load
and charger for maintenance and/or repair.
• The DC molded case circuit breakers are CE-approved for branch circuit protection. If replacement is required, CE-approved
components with the same voltage and current rating must be used.
• The size of the load connection cables must consider maximum allowable voltage drop, as well as the cables’ continuous
ampere capacity and anticipated ampere discharge rate of the individual battery cabinet. A maximum voltage drop of 1.5V
DC in the load connection cables is recommended. Refer to the UPS unit’s Owner’s Manual for recommended wire sizes.
• Refer to all applicable local, state and national codes for appropriate cable size and ratings.
• External circuit protection devices (fuses or circuit breakers) must consider the discharge rate of the battery, the wiring to be
protected and the DC short circuit current of the battery.
After performing the installation procedures in section 6. Installation, perform the following:
1. Open the front door of the battery cabinet to access internal components. Use a digital voltmeter when voltage
measurements are required.
2. Determine if the battery has been inadvertently grounded by resetting the circuit breaker to the “On” position and
measuring the voltage between the battery cabinet grounding lug and the positive load connection point within the cabinet.
This voltage should measure 0 (zero) VDC. If the measured voltage is not zero, determine the cause and correct before
proceeding.
3. Return the internal circuit breaker to an open “Off” position as a safety precaution while connecting the output cables.
Doing so prevents damage in the event the cables are accidentally shorted.
4. The top of the battery cabinet includes knockouts for load connection cable entry. Punch out the appropriate knockout
and connect the conduit or cable bushing.
5. The output circuit breaker accommodates cables up to 300 mm
2
.
10
3. Battery Cabinet Installation
6. Connect an appropriate equipment grounding cable to the grounding lug located on the top of the battery cabinet.
7. Feed the positive and negative cables (and “N” center, if equipped) from the open external disconnect switch or the UPS
battery field wiring terminals through the conduit/cable bushing. Connect to the respective output terminals inside the
battery cabinet.
3.8 Final Electrical Check
Before closing any connecting circuit breaker or disconnect switch, complete these verification steps:
1. Verify the battery cabinet output voltage is correct.
2. If battery cabinets will be operated in parallel, verify that the individual system output voltages match within 2V DC.
3. Verify the voltage measured between either output terminal and the battery cabinet ground is zero.
4. If any of the above verification steps show an irregularity, determine and correct the cause before proceeding.
5. Reset the circuit breaker to the “On” position.
4. Mechanical Data
4.1 Physical Measurements
4.1.1 Dimensions for BP240V65, BP240V65-NIB, BP240V100, BP240V100-NIB
31.5 in.
(800 mm)
35.4 in.
(900 mm)
47.2 in.
(1200 mm)
11
Front View Side View Rear View
4. Mechanical Data
1
Battery Breaker
2
Battery Terminal for 10kVA-20kVA UPS
3
Battery Terminal for 25kVA-60kVA UPS
4
Grounding Lugs
5
Battery Cable Knockouts
Rear View (terminal block without cover)
4
3
2
1
5
12
4. Mechanical Data
4.1.2 Dimensions for BP240V65L, BP240V65L-NIB, BP240V100L, BP240V100L-NIB
31.5 in.
(800 mm)
43.4 in.
(1100 mm)
63 in.
(1600 mm)
13
4. Mechanical Data
Front View Side View Rear View
1
Battery Breaker
2
Battery Terminal
for 10kVA-20kVA UPS
3
Battery Terminal
for 25kVA-60kVA UPS
4
Grounding Lugs
5
Battery Cable Knockouts
Rear View (terminal block without cover)
4
3
2
1
5
14
4. Mechanical Data
4.2 Physical Requirements (All Models)
Leave some space around the cabinet for operation and ventilation.
1. Leave at least 31.5 in. (800 mm) space in the front for ventilation.
2. Leave at least 20 in. (500 mm) space at the right and left for operation.
3. Leave at least 20 in. (500 mm) space at the back for ventilation.
>
20 in.
(500 mm)
>
20 in.
(500 mm)
>
20 in.
(500 mm)
>
20 in.
(500 mm)
>
31.5 in.
(800 mm)
15
5. Installation
Note: Before installation, inspect the unit. Ensure nothing inside the package is damaged. Retain the original packing material in a safe
place for future use.
5.1 Unpacking & Inspection
Any damage to packaging should be noted with the delivery carrier at the time of receipt.
Remove the rail kit, battery enclosure, and battery modules from the packaging.
Note: The battery modules are very heavy. Be cautious when unpacking and lifting the unit to avoid injury.
• Don’t tilt the battery pack when removing it from the packaging.
• Inspect the battery cabinet for damage that may have occurred from transport. If damage is found, do not turn on
the unit. Contact the dealer from whom the unit was purchased immediately.
• Check the accessories according to the packing list and contact the dealer in case of missing parts.
3. Remove the packing foam and the beveled pallet. 4. Remove the bolts securing the cabinet to the
shipping pallet.
1. Hold the sliding plate steady.
Cut and remove the binding tapes.
2. Remove the plastic bag and the shipping carton.
16
5. Installation
5. Use a forklift to lift the battery cabinet from the pallet.
5.2 Selecting Installation Position
Select a proper environment to install the unit, in order to minimize the possibility of damage to the battery system and
maximize the life of the batteries.
1. Do not block air flow to the ventilation openings of the unit.
2. Ensure environmental conditions of the installation site are in accordance with the unit specifications to avoid overheat
and excessive moisture. Refer to section 4.2 Physical Requirements.
3. Do not place the unit in a dusty or corrosive environment or near any flammable objects.
4. The unit is not designed for outdoor use.
Notes:
Place the battery cabinet in a clean, stable environment. Avoid vibration, dust, humidity, flammable gases, liquids and corrosives.
To help prevent high temperatures in the room where the UPS is installed, extractor fans and/or cooling systems are recommended.
Batteries should be mounted in an environment where the temperature is within the required specifications. Temperature is a key
factor in determining battery life and capacity. Battery temperature should be maintained between 59°F to 77°F (20°C to 25°C).
Keep batteries away from heat sources, main air ventilation areas, etc.
WARNING!
Typical battery performance data reflects an operating temperature between 59°F to 77°F (20°C to 25°C).
Operating the UPS above this range will reduce the battery life, while operating the UPS below this range will
reduce battery capacity.
If the UPS will not be installed immediately, it must be stored in a room without excessive heat or humidity.
17
5.3 Power Cables
The cable design shall comply with the voltages and currents provided in this section, and in accordance with local electrical codes.
WARNING!
UPON STARTING, PLEASE ENSURE YOU ARE AWARE OF THE LOCATION AND OPERATION OF THE EXTERNAL
ISOLATORS CONNECTED TO THE UPS INPUT/BYPASS SUPPLY OF THE UTILITY DISTRIBUTION PANEL.
CHECK TO SEE IF THESE SUPPLIES ARE ELECTRICALLY ISOLATED AND POST ANY NECESSARY WARNING
SIGNS TO PREVENT ANY INADVERTENT OPERATION
5.3.1 Cable Sizes
5.4 Battery Cabinet Connections:
Models BP240V65, BP240V65-NIB,
BP240V100 and BP240V100-NIB
Each battery cabinet design includes built-in internal battery
connection cables, breaker, fuses and terminals. The standard
cabinet can hold 20 pieces of 12V 65Ah 12V 100Ah batteries.
The DC voltage system for all cabinets is 240VDC with ±120V
internal battery strings.
Figures 6-1 and 6-2 show the overall chassis design
and exploded views for the BP240V65, BP240V65-NIB,
BP240V100 and BP240V100-NIB models. The corresponding
views for the BP240V65L, BP240V65L-NIB, BP240V100L and
BP240V100L-NIB models are shown in section 6.5 Battery
Cabinet Connections: Models BP240V65L, BP240V65L-
NIB, BP240V100L and BP240V100L-NIB.
6. Installation
UPS
MODEL
BP240V65 / BP240V100
BP240V65-NIB / BP240V100-NIB
BP240V65L / BP240V100L
BP240V65L-NIB / BP240V100L-NIB
Recommended
Torque
CABLE SIZES (THHW wiring at 167°F / 75°C)
DC INPUT GROUNDING DC INPUT GROUNDING
10kVA
6 AWG 6 AWG 6 AWG 6 AWG Anderson Connector
(No Torque Parameter)
0kgf.com / 0N•m
15kVA
6 AWG x 2 6 AWG x 2 6 AWG x 2 6 AWG x 2
20kVA
6 AWG x 2 6 AWG x 2 6 AWG x 2 6 AWG x 2
25kVA
1/0 AWG 2 AWG 1/0 AWG 2 AWG 450kgf.cm/
44N•m
30kVA
1/0 AWG 1/0 AWG 1/0 AWG 1/0 AWG
50kVA
2/0 AWG 2/0 AWG 2/0 AWG 2/0 AWG
60kVA
2/0 AWG 2/0 AWG 2/0 AWG 2/0 AWG
80kVA
2/0 AWG x 2 2/0 AWG x 2
100kVA
2/0 AWG x 2 2/0 AWG x 2
Figure 5-1: BP240V65, BP240V65-NIB, BP240V100,
& BP240V100-NIB Battery Cabinet Chassis
* S3M10-30K UPS systems do not support BP240V100L/100L-NIB battery cabinet models.
18
5. Installation
5.4.1 Remove the Chassis Shell
Place the battery cabinet in position. Remove the top, front, left and right panels. Remove the right and left cover plate of the
battery pack and the battery flapper to install the batteries.
5.4.2 Battery Installation and Connection
Each battery group has 20 pieces of batteries in series (BAT+, N and BAT-). Place the batteries in the cabinet from the bottom
to top one-by-one, then connect the battery cables according to the diagrams that follow.
Note: The positive and negative polarity of the battery cannot be reversed or short circuited. Doing so will damage the battery and/or cause
injury. Do not touch the battery’s positive and negative terminals at the same time. Before replacing or removing the batteries, disconnect
the breaker, pull up cell terminals and remove the screws of the copper bus bar. Not following the instructions could result in damage to the
equipment or personal injury. The installation must consist of 40 batteries.
Figure 5-2: Exploded Chassis View, Models BP240V65, BP240V65-NIB, BP240V100, BP240V100-NIB
19
5. Installation
Figure 5-3A: Front View
Figure 5-3B: Rear View
Layer 3
Layer 2
Layer 1
Positive group
10pcs
Negative group
10pcs
Fuses
400A (x2)
Battery
breaker
25-100kVA
connector
10-20kVA
connector
20
5. Installation
Figure 5-4: Wiring Diagram for Model BP240V65
Note: This manual may be downloaded
in color at tripplite.com, which shows
the cables in corresponding colors:
Red = Positive
Blue = Center Tap
Black = Negative
21
5. Installation
Figure 5-5: Wiring Diagram for Model BP240V100
Note: This manual may be downloaded
in color at tripplite.com, which shows
the cables in corresponding colors:
Red = Positive
Blue = Center Tap
Black = Negative
22
5. Installation
Figure 5-6A
Figure 5-6B
5.4.2.1 Battery installation and Setup:
Models BP240V65-NIB, BP240V100-NIB
1. Remove all screws labeled 1 (Figures 5-6A and 5-6B).
23
Figure 5-7
3. Remove all screws of the battery retention brackets and remove the retention brackets (Figure 5-8).
2. Remove the top, right side and left side plates (Figure 5-7).
5. Installation
Figure 5-8
24
5. Installation
Figure 5-9: Model BP240V65-NIB
Figure 5-10: Model BP240V100-NIB
4. Install 8 battery packs in layer 1 (Figure 5-9: Model BP240V65-NIB or Figure 5-10: Model BP240V100-NIB).
25
Figure 5-11: Model BP240V65-NIB
5. Install 6 battery packs in layer 2 (Figure 5-11: Model BP240V65-NIB or Figure 5-12: Model BP240V100-NIB).
5. Installation
Figure 5-12: Model BP240V100-NIB
26
5. Installation
Figure 5-13: Model BP240V65-NIB
Figure 5-14: Model BP240V100-NIB
6. Install 6 battery packs in layer 3 (Figure 5-13: Model BP240V65-NIB or Figure 5-14: ModelBP240V100-NIB).
27
Figure 5-15: Model BP240V65-NIB
7. Reinstall all battery retention brackets and screws (Figure 5-15: Model BP240V65-NIB or
Figure 5-16: Model BP240V100-NIB).
5. Installation
Figure 5-16: Model BP240V100-NIB
28
5. Installation
Figure 5-17A
Figure 5-17B
8. Model BP240V65-NIB: Install copper bus bars (13 pieces) between adjacent batteries and the battery insert bolts/screws
(Figures 5-17A and 5-17B).
29
Figure 5-18A
9. Model BP240V100-NIB: Install copper bus bars (12 pieces) between adjacent batteries and the battery insert bolts/screws
(Figures 5-18A and 5-18B).
5. Installation
Figure 5-18B
30
5. Installation
Figure 5-19: Model BP240V65-NIB
Figure 5-20: Model BP240V100-NIB
10. Connect the cables from battery 1+ to BAT+ bus bar, battery 10- to BATN bus bar, battery 11+ to BATN bus bar, battery
20- to BAT- bus bar and the layer connect cables (Figure 5-19: Model BP240V65-NIB or Figure 5-20:
Model BP240V100-NIB and Figure 5-21).
Notes:
Use the wiring schematics as reference
for the following assemblies:
Use Figure 5-4 for BP240V65-NIB
Use Figure 5-5 for BP240V100-NIB
This manual may be downloaded
in color at tripplite.com, which
shows the cables in corresponding
colors:
Red = Positive
Blue = Center Tap
Black = Negative
31
Figure 5-21
5. Installation
Figure 5-22
11. Reinstall all covers and screws (Figure 5-22).
32
5. Installation
Figure 5-23: BP240V65L, BP240V65L-NIB, BP240V100L,
& BP240V100L-NIB Battery Chassis
Figure 5-24: Exploded View – Models BP240V65L, BP240V65L-NIB, BP240V100l, BP240V100L-NIB
5.5 Battery Cabinet Connections:
Models BP240V65L, BP240V65L-NIB,
BP240V100L and BP240V100L-NIB
Each battery cabinet design includes built-in internal battery
connection cables, breaker, fuses and terminals. The standard
cabinet can hold 20 pieces of 12V 65Ah (12V/100Ah) batteries.
The “L” long-runtime battery cabinets can hold 40 pieces of the 12V
65Ah (12V 100Ah) batteries. The DC voltage system for all cabinets
is 240VDC with ±120V internal battery strings.
Figures 5-23 and 5-24 show the overall chassis design and
exploded views for the BP240V65L, BP240V65L-NIB, BP240V100L
and BP240V100L-NIB models. The corresponding views for the
BP240V65, BP240V65-NIB, BP240V100 and BP240V100-NIB
models are shown in section 5.4 Battery Cabinet Connections:
Models BP240V65, BP240V65-NIB, BP240V100 and
BP240V100-NIB.
5.5.1 Remove the
Chassis Shell
Place the battery box its final location.
Remove the top, front, left and right
panels. Remove the right and left cover
plates of the battery pack and the battery
supports to install the batteries strings.
33
5. Installation
Figure 5-25A: Front view
5.5.2 Battery Installation and Connection
The 40 batteries can be divided into two groups connected in parallel for use. Each group has 20 batteries in series
(BAT+, N and BAT-). Place the batteries in the cabinet from the bottom to top one-by-one, then connect the battery cables
according to the diagrams that follow.
Note: The positive and negative polarity of the battery cannot be reversed or short circuited. Doing so will damage the battery and/or cause
injury. Do not touch the battery’s positive and negative terminals at the same time. Before replacing or removing the batteries, disconnect
the breaker, pull up cell terminals and remove the screws of the copper bus bar. Not following the instructions could result in damage to the
equipment or personal injury. The installation must consist of 40 batteries.
Layer 3
Layer 4
Layer 2
Layer 1
Battery Group 2
Battery Group 1
34
Figure 5-25B: Rear View
5. Installation
Fuses
400A (x2)
Battery
breaker
25-100kVA
connector
10-20kVA
connector
35
5. Installation
Figure 5-26: Wiring diagram for BP240V65L (40 batteries installed)
Note: This manual may be downloaded
in color at tripplite.com, which shows
the cables in corresponding colors:
Red = Positive
Blue = Center Tap
Black = Negative
36
5. Installation
Figure 5-27: Wiring diagram for BP240V100L (40 batteries installed)
When the battery installation and connection is completed, use a multi-meter or other instrument to check if the voltages
between BAT+ and N, N and BAT- are normal. If normal, lock the chassis cover.
Note: This manual may be downloaded
in color at tripplite.com, which shows
the cables in corresponding colors:
Red = Positive
Blue = Center Tap
Black = Negative
37
5. Installation
Figure 5-28A
Figure 5-28B
5.5.2.1 Battery Installation and Setup:
Models BP240V65L-NIB, BP240V100L-NIB
1. Remove all screws labeled 1 (Figures 5-28A and 5-28B).
38
Figure 5-29
3. Remove all screws of the battery retention brackets and remove the retention brackets (Figure 5-30).
2. Remove the top, right side and left side plates (Figure 5-29).
5. Installation
Figure 5-30
39
5. Installation
Figure 5-31: Model BP240V65L-NIB
Figure 5-32: Model BP240V100L-NIB
4. Install 10 battery packs in layer 1 (Figure 5-31: Model BP240V65L-NIB or Figure 5-32: Model BP240V100L-NIB).
40
5. Installation
Figure 5-33: Model BP240V65L-NIB
5. Install 10 battery packs in layer 2 (Figure 5-33: Model BP240V65L-NIB or Figure 5-34: Model BP240V100L-NIB).
Figure 5-34: Model BP240V100L-NIB
41
5. Installation
Figure 5-35: Model BP240V65L-NIB
Figure 5-36: Model BP240V100L-NIB
6. Install 10 battery packs in layer 3 (Figure 5-35: Model BP240V65L-NIB or Figure 5-36: Model BP240V100L-NIB).
42
Figure 5-37: Model BP240V65L-NIB
7. Install 10 battery packs in layer 4 (Figure 5-37: Model BP240V65L-NIB or Figure 5-38: Model BP240V100L-NIB).
5. Installation
Figure5-38: Model BP240V100L-NIB
43
5. Installation
Figure 5-39
Figure 5-40A
8. Reinstall all battery retention brackets and screws (Figure 5-39).
9. Model BP240V65L-NIB: Install copper bus bars (13 pieces) between adjacent batteries and the battery insert bolts/posts
(Figures 5-40A and 5-40B).
44
Figure 5-40B
5. Installation
Figure 6-41A
10. Model BP240V100L-NIB: Install copper bus bars (12 pieces) between adjacent batteries and the battery insert bolts/posts
(Figures 5-41A and 5-41B).
45
5. Installation
Figure 5-41B
Figure 5-42: Model BP240V65L-NIB
11. Connect the cables from battery group 1 battery 1+ to BAT+ bus bar, battery 10- to BATN bus bar, battery 11+ to BATN
bus bar, battery 20- to BAT- bus bar and the layer connect cables. Connect battery group 2 battery 21+ to BAT+ bus bar,
battery 30- to BATN bus bar, battery 31+ to BATN bus bar, battery 40- to BAT- copper bar and the layer connect cables
(Figure 5-42: Model BP240V65L-NIB or Figure 5-43: Model BP240V100L and Figure 5-44).
Notes:
Use the wiring schematics as reference
for the following assemblies:
Use Figure 5-26 for BP240V65L-NIB
Use Figure 5-27 for BP240V100L-NIB
This manual may be downloaded in color
at tripplite.com, which shows the cables
in corresponding colors:
Red = Positive
Blue = Center Tap
Black = Negative
46
Figure 5-43: Model BP240V100L-NIB
Figure 5-44
5. Installation
47
Figure 5-45
12. Reinstall all covers and screws (Figure 5-45).
5. Installation
48
5. Installation
5.6 Multiple Battery Pack Connections
CAUTION!
Ensure correct polarity of the battery string series connection. DO NOT mix batteries with different
capacities, different brands or new and old batteries.
WARNING!
ENSURE CORRECT POLARITY OF STRING END CONNECTIONS TO THE BATTERY CIRCUIT BREAKER, AND
FROM THE BATTERY CIRCUIT BREAKER TO THE UPS TERMINALS (I.E. (+) TO (+) / (-) TO (-) / (N) TO (N)).
DISCONNECT ONE OR MORE BATTERY CELL LINKS IN EACH TIER. DO NOT RECONNECT THESE LINKS
AND DO NOT CLOSE THE BATTERY CIRCUIT BREAKER UNLESS ALL CONNECTIONS ARE PROPERLY
CHECKED AND APPROVED.
UPS Battery Cabinet
Figure 5-46: Connection of BP240V65L and BP240V65L-NIB for 10kVA, 15kVA and 20kVA UPS
49
5. Installation
UPS Battery Cabinet
Figure 5-47: Connection of BP240V65L and BP240V65L-NIB for 25kVA and 30kVA UPS
50
5. Installation
UPS Battery Cabinet
Figure 5-48: Connection of BP240V65L, BP240V65L-NIB, BP240V100L
or BP240V100L-NIB for 50kVA & 60kVA UPS Systems
51
5. Installation
UPS Battery Cabinet
Figure 5-49: Connection of BP240V65L, BP240V65L-NIB, BP240V100L
or BP240V100L-NIB for 80kVA & 100kVA UPS
52
6. Operation and Configuration of
S3M UPS Models and Battery Cabinets
6.1 S3M UPS Compatibility with BP240V65 to
BP240V100L Battery Cabinets
Cabinets with
Internal Batteries BP240V65 BP240V65L BP240V100 BP240V100L
Cabinets with NO
Internal Batteries BP240V65-NIB BP240V65L-NIB BP240V100-NIB BP240V100L-NIB
10kVA-20kVA
UPS with Internal
Batteries
• S3M10K1B,
S3M10K2B,
S3M10K3B
• S3M15K2B
S3M15K3B
• S3M20K3B
No No No No
10kVA-20kVA UPS
with NO Internal
Batteries
• S3M10K-NIB
• S3M15K-NIB
• S3M20K-NIB
Yes Yes Yes No
Cabinets with
Internal Batteries BP240V65 BP240V65L BP240V100 BP240V100L
Cabinets with NO
Internal Batteries BP240V65-NIB BP240V65L-NIB BP240V100-NIB BP240V100L-NIB
25kVA-100kVA
UPS with NO
Internal Batteries
• S3M25K
• S3M30K
Yes Yes Yes No
• S3M50K Yes Yes Yes Yes
• S3M60K No Yes Yes Yes
• S3M80K
• S3M100K
No Yes No Yes
53
6.2 Configuring 10-20K UPS for Specific Battery Cabinets using
the LCD Display
6.2.1 S3M10-20K UPS Home Display
CAUTION !
Settings for most parameters cannot be changed when the UPS
is in inverter mode.
6. Operation and Configuration of
S3M UPS Models and Battery Cabinets
54
6.2.2 Setting
Click on the Settings icon to enter two setting levels. The Basic Setting is for user settings, and the Advanced Setting is for
technical personnel only. Contact your administrator to enter advanced settings.
Advanced Setting: Click Advanced Setting and input the correct password. The user password is “191210”.
6. Operation and Configuration of
S3M UPS Models and Battery Cabinets
55
6.2.3 Battery Setup
Click Battery Setup
6. Operation and Configuration of
S3M UPS Models and Battery Cabinets
56
6.2.4 Configuring the S3M25-100K UPS and Optimizing Charging of
the BP240V65/V65L and BP240V100/V100L Battery Cabinets
Step 1: Setting the Battery Group
The Battery Group is Quantity 1 for every set of 20 batteries that are in and/or connected to the UPS model. For example, UPS
model S3M20K-NIB has no internal batteries and is Battery Group 1 by default for any UPS model. However, to connect a
BP240V65 cabinet with 20 internal batteries to the S3M20K-NIB, the S3M20K-NIB UPS must remain set to Battery Group 1
(one set of 20 batteries). However, to connect a second BP240V65 to the S3M20K-NIB UPS, the UPS Battery Group must be
2 (two sets of 20 batteries). Obtain the Battery Group number based on the specific S3M UPS and Battery Cabinet models
combination from the chart under Section 6.4.
The value can be 1 to 8. The default value is 1 for S3M UPS models without internal batteries.
Step 2: Setting the Battery Number
The battery number must remain at 20 for all S3M10-100K UPS models when connected to Tripp Lite external battery
cabinets designed for the S3M-Series UPS Series.
Step 3: Setting Single Battery (Ah) Capability
Change the Single Battery (Ah) Capability to the individual Ah capacity for one individual battery as follows for the specific
battery cabinet models:
• BP240V09/BP240V09K: the Single Battery (Ah) Capacity is 9
• BP240V40/BP240V40L: the Single Battery (Ah) Capacity is 40
• BP240V65/BP240V65L: the Single Battery (Ah) Capacity is 65
• BP240V100/BP240100L: the Single Battery (Ah) Capacity is 100
The values can be 7~2000.
Scroll to the next display screen by pressing the down arrow.
6. Operation and Configuration of
S3M UPS Models and Battery Cabinets
57
Step 4: Setting Max Charge Current
Max Charge Current is the estimated charge current that the UPS will use to charge the batteries. Obtain the recommended
estimated Max Charge Current based on the specific S3M UPS and battery cabinet model combination from the chart in
Section 6.4.
Float and Boost Voltage: The UPS is factory-set for proper float (2.27V/cell, 13.62V/battery) and boost (2.35V/cell,
14.1V/battery) voltages.
Cell float voltage: The float voltage value can be 2.23~2.30 V/cell. The default value is 2.27 V/cell.
Cell boost voltage: The battery equalized voltage value can be 2.30~2.40 V/cell. The default value is 2.35 V/cell.
Step 5: Setting Aver Changing Duration (min)
Setting the Average Charging Duration in minutes is an estimation of the boost charger time duration to charge new batteries
to 90% capacity at 25°C. Obtain the recommended Average (Aver) Charging Duration (min) number based on the specific
S3M UPS and battery cabinet model combination from the chart in Section 6.4. Note the recommended battery boost charge
durations are estimates only based on new batteries. These numbers may change with the age of the batteries and the battery
ambient temperature. To change the Aver Charging Duration, press directly on the defaulted 240 value in the display.
The Average (Aver) charging duration is the battery boost charge time limit. The value can be 1~999 min. The default is
value 240 (4 hours).
EOD Battery Volt: End of discharge voltage is the low voltage cutoff of the batteries during a battery mode operation. The
value can be 1.60~1.90. The default value is 1.67V/cell, or 10.02Vdc per battery.
Float Temp Compen Coeff: Modifies the voltage of compensation after enabling the switch. The value can be
0.001~0.007V/cell/°C. The default value is 0.003V/cell/°C.
Boost Charge Setting: Boost charge can be set to Disable or Enable. The default value is Enable.
No Battery Warning: Keep this alarm enabled if you want the UPS to provide a warning when no batteries are present. The
default value is Alarm.
6. Operation and Configuration of
S3M UPS Models and Battery Cabinets
58
6.3 Configuring 25-100K UPS for Specific Battery Cabinets
Using the LCD Display
6. Operation and Configuration of
S3M UPS Models and Battery Cabinets
CAUTION !
Settings for most parameters cannot be changed when the UPS
is in inverter mode.
59
6. Operation and Configuration of
S3M UPS Models and Battery Cabinets
6.3.1 S3M25-100K UPS Home Display
6.3.2 Setting
Click on the Settings icon to enter two setting levels. The Basic Setting is for user settings, and the Advanced Setting is for
technical personnel only. Contact your administrator to enter advanced settings.
Advanced Setting: Click Advanced Setting and input the correct password. The user password is “191210”.
60
6. Operation and Configuration of
S3M UPS Models and Battery Cabinets
61
6. Operation and Configuration of
S3M UPS Models and Battery Cabinets
6.3.3 Battery Setup
Click BATT Setup
Float Temp. Compen.: The temperature sensor compensation setting maybe changed to Enable when a battery temperature
sensor is connected to the UPS system’s RJ45 rear port.
Temp Sensor Select: Set the temperature sensor type to NTC for single and short distances. Set the temperature sensor type
to RS485 for multiple and far distances.
62
6. Operation and Configuration of
S3M UPS Models and Battery Cabinets
6.3.4 Configuring the S3M25-100K UPS and Optimizing
Charging of
the BP240V65/V65L and BP240V100/V100L Battery Cabinets
Step 1: Setting the Battery Group
The Battery Group is Quantity 1 for every set of 20 batteries that are in and/or connected to the UPS model. For example,
UPS model S3M100K UPS has no internal batteries and is Battery Group 1 by default. However, to connect a BP240V100L
cabinet with 40 internal batteries to the S3M100K, the S3M100K UPS must be configured to Battery Group 2. To connect
a second BP240V100L cabinet to the S3M100K UPS, the Battery Group must be set to 4 (four sets of 20 batteries). Obtain
the Battery Group number based on the specific S3M UPS and Battery Cabinet models combination from the chart under
Section 6.4.
The value can be 1 to 8. The default value is 1 for S3M UPS models without internal batteries.
Step 2: Setting the Battery Number
The battery number must remain at 20 for all S3M10-100K UPS models when connected to Tripp Lite external battery
cabinets designed for the S3M-Series UPS Series.
Step 3: Setting Single Battery (Ah) Capability
Change the Single Battery (Ah) Capability to the individual Ah capacity for one individual battery as follows for the specific
battery cabinet model:
BP240V40/BP240V40L: the Single Battery (Ah) Capacity is 40
BP240V65/BP240V65L: the Single Battery (Ah) Capacity is 65
BP240V100/BP240V100L: the Single Battery (Ah) Capacity is 100
The Single Battery (Ah) values can be 7~2000.
Scroll to the next display screen by pressing the down arrow.
63
6. Operation and Configuration of
S3M UPS Models and Battery Cabinets
Step 4: Setting Chg. cur. limiting coef (C)
The charging current limit is a multiple of the battery capacity. It is used to set the battery boost charging time limit. The
value can be 0.05~0.25, and is 0.25 by default. Obtain the Charging (Chg) current (cur) limiting coefficient (C) based on the
specific S3M UPS and battery cabinet model combination from the chart in Section 6.4.
Float and Boost Voltage: The UPS is factory-set for proper float (2.27V/cell, 13.62V/battery) and boost (2.35V/cell, 14.1V/
battery) voltages.
Cell float voltage: The float voltage value can be 2.23~2.30 V/cell. The default value is 2.27 V/cell.
Cell boost voltage: The battery equalized voltage value can be 2.30~2.40 V/cell. The default value is 2.35 V/cell.
Step 5: Setting Aver Changing Duration (min)
Setting the Average Charging Duration in minutes is an estimation of the boost charger time duration to charge new batteries
to 90% capacity at 25°C. Obtain the recommended Average (Aver) Charging Duration (min) number based on the specific
S3M UPS and battery cabinet model combination from the chart in Section 6.4. Note the recommended battery boost charge
durations are estimates only based on new batteries. These numbers may change with the age of the batteries and the battery
ambient temperature. To change the Aver Charging Duration, press directly on the defaulted 240 value in the display.
The Average (Aver) charging duration is the battery boost charge time limit. The value can be 1~999 min. The default is
value 240 (4 hours).
64
6. Operation and Configuration of
S3M UPS Models and Battery Cabinets
EOD Battery Volt: End of discharge voltage is the low voltage cutoff of the batteries during a battery mode operation. The
value can be 1.60~1.90. The default value is 1.67V/cell, or 10.02Vdc per battery.
Float Temp Compen Coeff: Modifies the voltage of compensation after enabling the switch. The value can be
0.001~0.007V/cell/°C. The default value is 0.003V/cell/°C.
Boost Charge Setting: Boost charge can be set to Disable or Enable. The default value is Enable.
No Battery Warning: Keep this alarm enabled if you want the UPS to provide a warning when no batteries are present. The
default value is Enable.
65
6.4 Configuration Reference Table for S3M10-100K UPS and
BP240V09K-BP240V100L Battery Cabinet Models
Configurations for S3M10K-NIB, S3M15K-NIB, S3M20K-NIB UPS with no internal batteries
Battery Packs Batteries Qty. of
Battery
Cabinets
Step 1 Step 2 Step 3 Step 4 Step 5
Battery
Group
Battery
Number
Single
Battery
Capability
Max
Charge
Current (A)
Aver Changing Duration (min)
Time (minutes) to Charge
Batteries to 90% at 25°C
BP240V65 20 x 65Ah 1 1 20 65 9.75 500
BP240V65 20 x 65Ah 2 2 20 65 19.5 500
BP240V65 20 x 65Ah 3 3 20 65 20 720
BP240V65L 40 x 65Ah 1 2 20 65 19.5 500
BP240V65L 40 x 65Ah 2 4 20 65 20 960
BP240V100 20 x 100Ah 1 1 20 100 15 500
Configurations for S3M25K and S3M30K
Battery Packs Batteries Qty. of
Battery
Cabinets
Step 1 Step 2 Step 3 Step 4 Step 5
Battery
Group
Battery
Number
Single
Battery
Capability
Chg. Cur.
Limiting
Coef. (C)
Aver Changing Duration (min)
Time (minutes) to Charge
Batteries to 90% at 25°C
BP240V65 20x 65Ah 1 1 20 65 0.15 540
BP240V65 20 x 65Ah 2 2 20 65 0.15 540
BP240V65 20 x 65Ah 3 3 20 65 0.1 900
BP240V65L 40 x 65Ah 1 2 20 65 0.15 540
BP240V65L 40 x 65Ah 2 4 20 65 0.07 999
BP240V100 20 x 100Ah 1 1 20 100 0.15 540
Configurations for S3M50K and S3M60K
Battery Packs Batteries Qty. of
Battery
Cabinets
Step 1 Step 2 Step 3 Step 4 Step 5
Battery
Group
Battery
Number
Single
Battery
Capability
Chg. Cur.
Limiting
Coef. (C)
Aver Changing Duration (min)
Time (minutes) to Charge
Batteries to 90% at 25°C
BP240V65 20 x 65Ah 1 1 20 65 0.15 540
BP240V65 20 x 65Ah 2 2 20 65 0.15 540
BP240V65 20 x 65Ah 3 3 20 65 0.15 540
BP240V65L 40 x 65Ah 1 2 20 65 0.15 540
BP240V65L 40 x 65Ah 2 4 20 65 0.15 540
BP240V65L 40 x 65Ah 3 6 20 65 0.1 840
BP240V100 20 x 100Ah 1 1 20 100 0.15 540
BP240V100 20 x 100Ah 2 2 20 100 0.15 540
BP240V100 20 x 100Ah 3 3 20 100 0.13 540
BP240V100L 40 x 100Ah 1 2 20 100 0.15 540
BP240V100L 40 x 100Ah 2 4 20 100 0.1 840
6. Operation and Configuration of
S3M UPS Models and Battery Cabinets
66
6. Operation and Configuration of
S3M UPS Models and Battery Cabinets
Configurations for S3M80K
Battery Packs Batteries Qty. of
Battery
Cabinets
Step 1 Step 2 Step 3 Step 4 Step 5
Battery
Group
Battery
Number
Single
Battery
Capability
Chg. Cur.
Limiting
Coef. (C)
Aver Changing Duration (min)
Time (minutes) to Charge
Batteries to 90% at 25°C
BP240V65 20 x 65Ah 1 1 20 65 0.15 540
BP240V65 20 x 65Ah 2 2 20 65 0.15 540
BP240V65 20 x 65Ah 3 3 20 65 0.15 540
BP240V65L 40 x 65Ah 1 2 20 65 0.15 540
BP240V65L 40 x 65Ah 2 4 20 65 0.15 540
BP240V65L 40 x 65Ah 3 6 20 65 0.15 540
BP240V100 20 x 100Ah 1 1 20 100 0.15 540
BP240V100 20 x 100Ah 2 2 20 100 0.15 540
BP240V100 20 x 100Ah 3 3 20 100 0.15 540
BP240V100L 40 x 100Ah 1 2 20 100 0.15 540
BP240V100L 40 x 100Ah 2 4 20 100 0.15 540
BP240V100L 40 x 100Ah 3 6 20 100 0.1 840
Configurations for S3M100K
Battery Packs Batteries Qty. of
Battery
Cabinets
Step 1 Step 2 Step 3 Step 4 Step 5
Battery
Group
Battery
Number
Single
Battery
Capability
Chg. Cur.
Limiting
Coef. (C)
Aver Changing Duration (min)
Time (minutes) to Charge
Batteries to 90% at 25°C
BP240V65 20 x 65Ah 1 1 20 65 0.15 540
BP240V65 20 x 65Ah 2 2 20 65 0.15 540
BP240V65 20 x 65Ah 3 3 20 65 0.15 540
BP240V65L 40 x 65Ah 1 2 20 65 0.15 540
BP240V65L 40 x 65Ah 2 4 20 65 0.15 540
BP240V65L 40 x 65Ah 3 6 20 65 0.15 540
BP240V100 20 x 100Ah 1 1 20 100 0.15 540
BP240V100 20 x 100Ah 2 2 20 100 0.15 540
BP240V100 20 x 100Ah 3 3 20 100 0.15 540
BP240V100L 40 x 100Ah 1 2 20 100 0.15 540
BP240V100L 40 x 100Ah 2 4 20 100 0.15 540
BP240V100L 40 x 100Ah 3 6 20 100 0.13 540
67
7.1 Battery Cabinet Specifications
(DC Nominal Voltage: ± 120V DC, 240V DC)
Battery Pack BP240V65 (-NIB) BP240V100 (-NIB) BP240V65L (-NIB) BP240V100L (-NIB)
Dimension
W × D × H
31.5 x 35.4 x 47.2 in.
(800 x 900 x 1200 mm)
31.5 x 43.3 x 63 in.
(800 x 1100 x 1600 mm)
Weight
608 lb. (275.8 kg)* 930 lb. (421.8 kg)* 1083 lb. (491.2 kg)* 1637 lb. (742.5 kg)*
Breaker
1x 250A 1x 600A
Fuse
2x 400A 4x 400A
*Models with the –NIB suffix do not include internal batteries, so their total weight varies based on batteries installed by the end user.
7. Specifications
Storage
The battery cabinet must be stored in a clean, secure environment with a temperature less than 104°F (40°C) and a relative
humidity less than 90% (non-condensing). Store the battery cabinet in its original shipping container if possible. Charge
the batteries for at least 24 hours prior to use. Do not rely on the battery cabinet to provide backup power to connected
equipment until the batteries are fully charged.
Note: If the UPS system remains off for an extended period of time, it should be turned on periodically to allow the batteries
to recharge. The UPS system should be turned on and the batteries should be recharged at least one uninterrupted 24-hour
period every 3 months. Failure to recharge the batteries periodically may cause irreversible battery damage.
8. Storage
Service
Your Tripp Lite product is covered by the warranty described in this manual. A variety of Extended Warranty and On-Site Service Programs are
also available from Tripp Lite. For more information on service, visit tripplite.com/support. Before returning your product for service, follow
these steps:
1. Review the installation and operation procedures in this manual to ensure that the service problem does not originate from a misreading
of the instructions.
2. If the problem continues, do not contact or return the product to the dealer. Instead, visit tripplite.com/support.
3. If the problem requires service, visit tripplite.com/support and click the Product Returns link. From here you can request a Returned
Material Authorization (RMA) number, which is required for service. This simple on-line form will ask for your unit’s model and serial
numbers, along with other general purchaser information. The RMA number, along with shipping instructions will be emailed to you. Any
damages (direct, indirect, special or consequential) to the product incurred during shipment to Tripp Lite or an authorized Tripp Lite service
center are not covered under warranty. Products shipped to Tripp Lite or an authorized Tripp Lite service center must have transportation
charges prepaid. Mark the RMA number on the outside of the package. If the product is within its warranty period, enclose a copy of your
sales receipt. Return the product for service using an insured carrier to the address given to you when you request the RMA.
9. Service and Warranty
68
Limited Warranty
Seller warrants this product, if used in accordance with all applicable instructions, to be free from original defects in material and
workmanship for a period of one (1) year from the date of initial purchase. If the product should prove defective in material or workmanship
within that period, Seller will repair or replace the product, in its sole discretion. Service under this Warranty includes parts and Tripp Lite
service center labor. On-site service plans are available from Tripp Lite through authorized service partners (in most areas). Visit tripplite.com/
support for details. International customers should contact Tripp Lite support at [email protected].
THIS WARRANTY DOES NOT APPLY TO NORMAL WEAR OR TO DAMAGE RESULTING FROM ACCIDENT, MISUSE, ABUSE OR NEGLECT. SELLER
MAKES NO EXPRESS WARRANTIES OTHER THAN THE WARRANTY EXPRESSLY SET FORTH HEREIN. EXCEPT TO THE EXTENT PROHIBITED BY
APPLICABLE LAW, ALL IMPLIED WARRANTIES, INCLUDING ALL WARRANTIES OF MERCHANTABILITY OR FITNESS, ARE LIMITED IN DURATION
TO THE WARRANTY PERIOD SET FORTH ABOVE; AND THIS WARRANTY EXPRESSLY EXCLUDES ALL INCIDENTAL AND CONSEQUENTIAL
DAMAGES. (Some states do not allow limitations on how long an implied warranty lasts, and some states do not allow the exclusion or
limitation of incidental or consequential damages, so the above limitations or exclusions may not apply to you. This Warranty gives you
specific legal rights, and you may have other rights which vary from jurisdiction to jurisdiction.)
Tripp Lite; 1111 W. 35th Street; Chicago IL 60609; USA
WARNING: The individual user should take care to determine prior to use whether this device is suitable, adequate or safe for the use
intended. Since individual applications are subject to great variation, the manufacturer makes no representation or warranty as to the
suitability or fitness of these devices for any specific application.
Regulatory Compliance Identification Numbers
For the purpose of regulatory compliance certifications and identification, your Tripp Lite product has been assigned a unique series
number. The series number can be found on the product nameplate label, along with all required approval markings and information. When
requesting compliance information for this product, always refer to the series number. The series number should not be confused with the
marketing name or model number of the product.
WEEE Compliance Information for Tripp Lite Customers and Recyclers (European Union)
Under the Waste Electrical and Electronic Equipment (WEEE) Directive and implementing regulations, when customers buy new
electrical and electronic equipment from Tripp Lite they are entitled to:
• Send old equipment for recycling on a one-for-one, like-for-like basis (this varies depending on the country)
• Send the new equipment back for recycling when this ultimately becomes waste
Tripp Lite has a policy of continuous improvement. Specifications are subject to change without notice. Photos and illustrations may differ
slightly from actual products.
9. Service and Warranty
1111 W. 35th Street, Chicago, IL 60609 USA • tripplite.com/support
20-11-074 93-3BF8_RevB
69
MÁS DE
AÑOS
Manual del Propietario
Gabinete de Baterías para
Autonomía Extendida
Modelos: BP240V65, BP240V65-NIB, BP240V65L, BP240V65L-NIB,
BP240V100, BP240V100-NIB, BP240V100L, BP240V100L-NIB
No es adecuado para aplicaciones móviles.
1111 W. 35th Street, Chicago, IL 60609 EE UU • tripplite.com/support
Copyright © 2020 Tripp Lite. Todos los derechos reservados.
English 1 • Français 137
70
Índice
1. Introducción 71
1.1 Características 71
1.2 Tabla de Compatibilidad de UPS 72
y Gabinetes de Baterías
2. Instrucciones de Seguridad 73
Importantes
2.1 Advertencias sobre la Instalación y 73
la Ubicación
2.2 Advertencias sobre la Conexión 73
2.3 Advertencias sobre la Batería 74
2.4 Cumplimiento de Estándares 74
3.
Instalación del Gabinete de Baterías
75
3.1 Preparación 75
3.2 Transporte 75
3.3 Comprobación Mecánica 75
3.4 Contenido del Empaque 75
3.5 Cableado Interno (Típico) 76
3.6
Colocación del Gabinete para Baterías
76
3.7 Conexión Eléctrica 77
3.8 Comprobación Eléctrica Final 78
4. Datos Mecánicos 78
4.1 Mediciones Físicas 78
41.1 Dimensiones para BP240V65, 78
BP240V65-NIB,
BP240V100, BP240V100-NIB
4.1.2 Dimensiones para BP240V65L, 80
BP240V65L-NIB, BP240V100L,
BP240V100L-NIB
4.2
Requerimientos Físicos
(Todos los Modelos)
82
5. Instalación 83
5.1
Desempaque e Inspección
83
5.2
Selección de la
84
Posición de Instalación
5.3
Cables de Alimentación
85
5.3.1 Tamaños de Cables
85
5.4
Conexiones del Gabinete de Baterías:
85
Modelos BP240V65, BP240V65-NIB,
BP240V100, BP240V100-NIB
5.4.1 Retire la Cubierta del Bastidor 86
5.4.2 Instalación y Conexión de la Batería
86
5.4.2.1 Instalación y Configuración de 90
la Batería: Modelos BP240V65
NIB, BP240V100-NIB
5.5
Conexiones del Gabinete de
100
Baterías: Modelos BP240V65L,
BP240V65L-NIB, BP240V100L y
BP240V100L-NIB
5.5.1
Retire la Cubierta del Bastidor
100
5.5.2
Instalación y Conexión de la Batería
101
5.5.2.1
Instalación y Configuración
105
de la Batería: Modelos BP240V65L-
NIB, BP240V100L-NIB
5.6
Conexiones de Múltiples de Módulos
116
de Baterías
6. Operación y Configuración de 120
Modelos de UPS S3M y Gabinetes
de Baterías Cabinets
6.1
Compatibilidad de UPS S3M con
120
Gabinetes de Baterías BP240V65
a BP240V100L
6.2
Operación y Configuración de
121
Modelos de UPS S3M y Gabinetes
de Baterías Cabinets
6.2.1
Pantalla de Inicio del UPS S3M10-20K
121
6.2.2
Configuración
122
6.2.3
Configuración de la Batería
123
6.2.4
Configuración del UPS S3M10-20K-NIB
124
y Optimización de la Carga de los
Gabinetes de Baterías BP240V65/V65L
y BP240V100/V100L
6.3
Configuración del UPS de 25K~
126
100K para Gabinetes de Baterías
Específicos Usando la Pantalla LCD
6.3.1
Pantalla de Inicio del UPS S3M25-100K
127
6.3.2
Configuración
127
6.3.3
Configuración de la Batería
129
6.3.4
Configuración del UPS S3M25-100K
130
y Optimización de la Carga de los
Gabinetes de Baterías BP240V65/V65L
y BP240V100/V100L
6.4
Tabla de Referencia de Configuración
133
para Modelos de Sistemas UPS
S3M10-100K y Modelos de Gabinete
de Baterías BP240V09K-BP240V100L
7. Especificaciones 135
7.1
Especificaciones del Gabinete de Baterías
135
8. Almacenamiento 135
9. Servicio y Garantía 135
71
1. Introducción
Los Gabinetes de Baterías para Autonomía Extendida de Tripp Lite se conectan a Sistemas UPS SmartOnline® para
proporcionar respaldo por batería de larga duración para centros de datos, telecomunicaciones, redes, instalaciones
industriales, seguridad, sistemas de emergencia y otras aplicaciones de misión crítica que requieran alta capacidad, alta
disponibilidad y autonomía extendida.
Los gabinetes de baterías están disponibles en siete modelos, con y sin baterías preinstaladas: BP240V65, BP240V65-NIB,
BP240V65L, BP240V65L-NIB, BP240V100, BP240V100-NIB, BP240V100L-NIB.
Los modelos de gabinete de baterías con sufijo “-NIB” BP240V65-NIB, BP240V65L-NIB, BP240V100-NIB y BP240V40L-
NIB no incluyen baterías preinstaladas. Sin embargo, incluyen todos los cables puente, fusibles y breakers, permitiendo la
flexibilidad para comprar baterías por separado para los gabinetes de baterías. Los gabinetes de baterías BP240V65-NIB y
BP240V65L-NIB están diseñados para baterías CSB GP12650i. Los gabinetes de baterías BP240V100-NIB y BP240V100L-
NIB están diseñados para baterías CSB GP121000.
1.1 Características
• Los gabinetes para baterías están diseñados para tensiones de cadenas de baterías de ± 120V CD y capacidades de
batería de 65Ah o 100Ah, @ C20 a 1.67VPC.
• Los gabinetes de baterías contienen múltiples baterías AGM de 12V CD conectadas en serie para obtener voltajes más
altos.
• Cada gabinete de baterías contiene varios estantes para alcanzar los voltajes requeridos de la cadena de baterías:
o BP240V65 / BP240V65-NIB: Soporta 20 x baterías AGM de 65Ah
o BP240V100 y BP240V100-NIB: Soportan 20 x baterías AGM de 100Ah
o BP240V65L y BP240V65L-NIB: Soportan 40 x baterías AGM de 65Ah
o BP240V100L y BP240V100L-NIB: Soportan 40 x baterías AGM de 100Ah
• Una puerta con bisagra y cerradura facilita el acceso a las baterías para el mantenimiento periódico.
• Para acceder a las terminales se ha dejado un espacio libre mínimo de 100 mm [4"] encima de las baterías individuales.
• El gabinete de baterías está construido de acero de grueso calibre para mayor durabilidad.
• Un acabado de pintura en polvo horneada proporciona resistencia a corrosión.
• El gabinete de baterías se embarca atornillado a una tarima con una doble capa de envoltura de protección elástica y
esquineros integrados y protección en la parte superior.
• La ventilación y enfriamiento por convección adecuados de las baterías individuales se proporcionan mediante un espaciado
entre las baterías. Las ventilas delanteras y traseras permiten la libre circulación del aire caliente hacia afuera del gabinete
de baterías.
• Se proporciona un breaker de caja moldeada para protección contra sobrecorriente.
• Los cables de salida de energía suministrados por el usuario pueden introducirse en el gabinete de baterías a través de las
aberturas para conductos ubicadas en la parte inferior del gabinete.
• Para una seguridad mejorada, mayor densidad de potencia y mantenimiento mínimo, los sistemas de gabinete utilizan
baterías recombinantes de Plomo Ácido Reguladas por Válvula (VRLA). El electrolito de estas baterías es inmovilizado en un
separador de estera absorbente o en un medio gelificante, eliminando riesgos de derrame y requisitos de mantenimiento
del electrolito líquido libre. No hay necesidad
de agregar agua o medir la densidad.
• Ya que las baterías tienen celdas recombinantes que emplean un ciclo de recombinación del oxígeno, se emiten gases
mínimos durante la carga de flotación normal. Cada celda contiene una válvula individual, que libera los productos de gas
de la sobrecarga y evita la acumulación de la presión dentro de la celda.
5.5
Conexiones del Gabinete de
100
Baterías: Modelos BP240V65L,
BP240V65L-NIB, BP240V100L y
BP240V100L-NIB
5.5.1
Retire la Cubierta del Bastidor
100
5.5.2
Instalación y Conexión de la Batería
101
5.5.2.1
Instalación y Configuración
105
de la Batería: Modelos BP240V65L-
NIB, BP240V100L-NIB
5.6
Conexiones de Múltiples de Módulos
116
de Baterías
6. Operación y Configuración de 120
Modelos de UPS S3M y Gabinetes
de Baterías Cabinets
6.1
Compatibilidad de UPS S3M con
120
Gabinetes de Baterías BP240V65
a BP240V100L
6.2
Operación y Configuración de
121
Modelos de UPS S3M y Gabinetes
de Baterías Cabinets
6.2.1
Pantalla de Inicio del UPS S3M10-20K
121
6.2.2
Configuración
122
6.2.3
Configuración de la Batería
123
6.2.4
Configuración del UPS S3M10-20K-NIB
124
y Optimización de la Carga de los
Gabinetes de Baterías BP240V65/V65L
y BP240V100/V100L
6.3
Configuración del UPS de 25K~
126
100K para Gabinetes de Baterías
Específicos Usando la Pantalla LCD
6.3.1
Pantalla de Inicio del UPS S3M25-100K
127
6.3.2
Configuración
127
6.3.3
Configuración de la Batería
129
6.3.4
Configuración del UPS S3M25-100K
130
y Optimización de la Carga de los
Gabinetes de Baterías BP240V65/V65L
y BP240V100/V100L
6.4
Tabla de Referencia de Configuración
133
para Modelos de Sistemas UPS
S3M10-100K y Modelos de Gabinete
de Baterías BP240V09K-BP240V100L
7. Especificaciones 135
7.1
Especificaciones del Gabinete de Baterías
135
8. Almacenamiento 135
9. Servicio y Garantía 135
72
1. Introducción
1.2 Tabla de Compatibilidad de UPS y Gabinetes de Baterías
Gabinetes con
Baterías Internas BP240V65 BP240V65L BP240V100 BP240V100L
Gabinetes SIN
Baterías Internas BP240V65-NIB BP240V65L-NIB BP240V100-NIB BP240V100L-NIB
UPS de 10kVA a
20kVA con Baterías
Internas
• S3M10K1B,
S3M10K2B,
S3M10K3B
• S3M15K2B
S3M15K3B
• S3M20K3B
No No No No
UPS de 10kVA a
20kVA SIN Baterías
Internas
• S3M10K-NIB
• S3M15K-NIB
• S3M20K-NIB
No
Gabinetes con
Baterías Internas BP240V65 BP240V65L BP240V100 BP240V100L
Gabinetes SIN
Baterías Internas BP240V65-NIB BP240V65L-NIB BP240V100-NIB BP240V100L-NIB
UPS de 25kVA
~ 100kVA SIN
Baterías Internas
• S3M25K
• S3M30K
No
• S3M50K
• S3M60K No
• S3M80K
• S3M100K
No No
73
2. Instrucciones de Seguridad Importantes
CONSERVE ESTAS INSTRUCCIONES
Todas las secciones de este manual contienen instrucciones y advertencias que deben observarse durante la
instalación y la operación del gabinete de batería aquí descrito. Lea TODAS las instrucciones detenidamente antes de
mover, instalar o conectar el gabinete de batería.
Caso contrario, puede afectar la garantía y causar daños materiales o lesiones físicas graves.
¡PELIGRO! ¡RIESGO LETAL POR ALTO VOLTAJE!
El tendido del cableado debe estar a cargo de un electricista calificado, de conformidad con las
advertencias descritas en este manual y con todos los códigos de seguridad y eléctricos aplicables. Un
cableado incorrecto puede causar lesiones personales graves y daños a la propiedad.
2.1 Advertencias sobre la Instalación y la Ubicación
Instale el gabinete de batería en un ambiente interior controlado, alejado de humedad excesiva, temperaturas extremas, líquidos
y gases inflamables, contaminantes conductores, polvo o luz solar directa.
Instale el gabinete de batería en una ubicación nivelada y con estructura firme.
El gabinete de baterías es extremadamente pesado. Tenga cuidado al mover o levantar la unidad.
Opere el gabinete de baterías únicamente a temperaturas interiores entre 0 °C y 40 °C. Para mejores resultados, mantenga la
temperatura ambiente a 25 °C.
Deje espacio suficiente en la parte delantera y posterior del gabinete para una ventilación adecuada. No bloquee, cubra ni
coloque objetos en las aberturas de ventilación externas del gabinete de baterías.
No coloque objeto alguno sobre el gabinete de batería, especialmente recipientes con líquido.
No intente apilar el gabinete de batería. Si lo hiciera, puede dañarlo de forma definitiva y causar lesiones físicas graves.
No intente desembalar ni mover el gabinete sin asistencia. Use un equipo de manipulación adecuado para
soportar el peso y el volumen del gabinete de baterías, como montacargas y gatos mecánicos para tarimas. (Extienda
totalmente las horquillas del montacargas
debajo de la carga. Abra las horquillas al máximo ancho posible bajo la carga. Levante el gabinete por la base solamente. Use
calzado protector).
Para uso en caso de emergencia, instale un extintor certificado para incendios de equipos eléctricos conectados (clasificación
clase C o uno exactamente equivalente, con agente extintor no conductor) cerca del gabinete.
2.2 Advertencias sobre la Conexión
El gabinete de batería contiene alto voltaje peligroso que puede causar lesiones físicas o la muerte por
descarga eléctrica.
El gabinete tiene su propia fuente de alimentación. Las terminales de salida pueden estar energizadas aún cuando el gabinete
no está conectado a un sistema UPS.
El gabinete se debe conectar a tierra conforme a todas las regulaciones de cableado eléctrico aplicables.
No se recomienda el uso de este equipo en aplicaciones de soporte de vida en donde razonablemente se pueda esperar que la
falla de este equipo provoque la falla del equipo de soporte de vida o afecte significativamente su seguridad o efectividad.
Desconecte todas las fuentes de alimentación de entrada y salida antes de instalar los cables o realizar conexiones eléctricas.
Use un cable flexible de longitud suficiente para permitir las tareas de servicio del gabinete.
Use casquillos para tapar los cables de terminación y evitar que los extremos deshilachados entren en corto en los bloques de
terminales. Use cable con clasificación VW-1, FT-1 o superior. Use manguitos para los cables y abrazaderas para los conectores.
Confirme que todos los cables estén marcados correctamente según su finalidad, polaridad y diámetro.
74
2. Instrucciones de Seguridad Importantes
Tome en cuenta la polaridad correcta siguiendo las marcas de positivo y negativo en la unidad. El hecho de no tomar en cuenta
la polaridad correcta puede dañar las baterías y crear un riesgo grave de lesiones personales y daños a la propiedad.
El tendido del cableado y el ensamble deben estar a cargo solamente de electricistas calificados y capacitados. Consulte el
Manual del Propietario de la unidad UPS para conocer el tamaño de los cables.
2.3 Advertencias sobre la Batería
• El gabinete de baterías requiere mantenimiento de rutina por técnicos calificados que estén familiarizados con en su
operación. Deben tomarse todas las precauciones requeridas antes de abrir el gabinete por cualquier motivo. Mantenga al
personal no autorizado alejado de las baterías.
• El gabinete de batería contiene baterías de plomo ácido recombinantes reguladas con válvula (VRLA). No intente agregar
agua a las baterías ni tomar una muestra del peso específico del electrolito.
• Las baterías VRLA pueden contener una mezcla explosiva de gas de hidrógeno. NO FUME cerca de las baterías. NO
provoque llamas ni chispas cerca de las baterías. Descargue la electricidad estática del cuerpo antes de tocar las baterías.
NO abra ni altere las baterías, la emisión de electrolito es dañina para la piel y los ojos, y puede ser tóxica. NO arroje las
baterías al fuego—pueden explotar.
• Las baterías presentan un riesgo de descarga eléctrica y quemaduras por la alta corriente de cortocircuito. La conexión
y reemplazo de la batería debe llevarse a cabo sólo por personal de servicio calificado que observe las precauciones
apropiadas. Use herramientas con mangos aislados. Retire relojes, anillos u otros objetos metálicos. Use botas y guantes
de hule. No ponga en corto o puentee las terminales de la batería con ningún objeto. No coloque herramientas o partes
metálicas sobre la parte superior de las baterías.
• Reemplace las baterías por otras equivalentes (mismo número y tipo) que puede comprar en Tripp Lite.
• Las baterías son reciclables. Para los requisitos de desecho, consulte los códigos locales. Solo deseche las baterías
mediante los canales autorizados en conformidad con todas las regulaciones locales, estatales y nacionales que
correspondan.
• No conecte ni desconecte las baterías cuando el sistema UPS esté funcionando con suministro de la batería o cuando
la unidad no se encuentre en modo de derivación. Desconecte la fuente de carga antes de conectar o desconectar las
terminales de la batería.
• Si la fuente de carga permanece apagada por un período prolongado, debe encenderse periódicamente para recargar
las baterías. Debe encenderse la unidad de carga y recargarse las baterías durante 24 horas ininterrumpidas como mínimo
cada 3 meses. Si no se recargan las baterías periódicamente, puede causar daños permanentes a la batería.
• Deje que las baterías se carguen durante 24 horas ininterrumpidas después de la instalación.
2.4 Cumplimiento de Estándares
• UL 1778, CSA-C22.2 Nº 107.3-14 (3ª Ed)
• ISTA B (Transporte, Vibración, Inclinación)
Nota sobre el etiquetado
Pueden aparecer estos símbolos en la etiqueta del producto:
V : Voltaje de CD
: Conexión a Tierra
+: Positivo de la Batería
– : Negativo de la Batería
Consulte en la etiqueta del producto los números de modelo, especificación de voltaje y otra infor-
mación importante.
75
3. Instalación del Gabinete de Baterías
Antes de la Instalación Lea la Sección 2 –
Instrucciones de Seguridad Importantes
3.1 Preparación
En su instalación, prepárese para descargar el gabinete de baterías del camión de entrega y transportarlo hasta el lugar de instalación
final. Tenga en cuenta el peso y dimensiones del paquete.
Asegúrese de que el piso pueda soportar la carga del gabinete de baterías específico que se está instalando. El gabinete debe
instalarse en un área estructuralmente firme con un piso nivelado, que pueda soportar el peso del gabinete de baterías y otros
equipos que se instalen cerca.
Dibuje un esquema de cableado que represente los cables conectados entre los bloques de terminales de salida del gabinete de
baterías y cualquier dispositivo exterior de desconexión, caja de conexiones y/o carga y rectificador.
Si planea almacenar el gabinete por un período prolongado antes de la instalación, siga las instrucciones en la
Sección 9. Almacenamiento y Servicio.
3.2 Transporte
1. Inspeccione el o los contenedores de embarque para detectar daños visibles (no retire la envoltura elástica alrededor de la unidad
hasta que haya sido transportada hasta el lugar de instalación final). Confirme que el nombre del modelo y la especificación
coincidan con la unidad que ordenó. Si usted determina que la unidad ha sufrido daños durante el envío o si algo parece faltar,
póngase en contacto con Tripp Lite. No intente utilizar la unidad si ha sido dañada o maltratada.
2. No intente mover o desempacar el gabinete de baterías sin asistencia. Use un equipo de manipulación adecuado para soportar el
peso y el volumen del gabinete de baterías, como montacargas y gatos mecánicos para tarimas. (Extienda totalmente las horquillas
del montacargas debajo de la carga. Abra las horquillas al máximo ancho posible bajo la carga. Levante el gabinete por la base
solamente. Use calzado protector). Confirme que los límites de carga para montacargas, equipos de manejo y pisos a lo largo de
la ruta de transporte no sean excedidos por el peso combinado del gabinete de baterías empacado, equipos de manejo y personal.
Confirme que la unidad empacada pasará a través de cualquier puerta a lo largo de la ruta prevista.
3. El gabinete de baterías está asegurado con envoltura de plástico elástico para protegerlo durante el transporte y movimiento dentro
de una instalación. Retire la envoltura elástica del gabinete de baterías cuando la unidad está en el lugar de instalación final—
no antes.
3.3 Comprobación Mecánica
Mientras que el sistema de gabinete de baterías se encuentre todavía en la tarima, inspeccione todas las partes para detectar golpes
u otros daños.
1. Abra la puerta frontal del gabinete de baterías.
2. Confirme que ninguna de las partes internas (baterías, bloques de terminales, breaker y otras partes) esté dañada.
3.
Tenga en cuenta el número de modelo de batería individual y el tipo de terminal que se muestran en la sección 7. Especificaciones.
4. Utilice herramientas aisladas para apretar todas las conexiones de terminales de la batería al valor recomendado mostrado en la
tabla en la sección 5.3 Cables de Alimentación.
5. Utilice herramientas aisladas para apretar los cables de las terminales de salida positivas y negativas en el extremo de las baterías
al breaker.
76
3. Instalación del Gabinete de Baterías
3.4 Contenido del Empaque
Número
de Parte
Descripción BP240
V65
BP240
V65L
BP240
V65-
NIB
BP240
V65L-
NIB
BP240
V100
BP240
V100L
BP240
V100-
NIB
BP240
V100L-
NIB
Manual del Propi-
etario
933BF8
Cables para Batería
731891 "Cables de batería
para conectar a UPS
S3M10-20K"
2 2 2 2 2 No 2 No
Aisladores de Batería
83084A/
83084B
Materiales protectores N/A N/A 4/5 8/8 N/A N/A N/A N/A
"Lado Inferior
del Gabinete
Faldones Metálicos"
1038F7A Cubrir el área inferior
del gabinete
2 N/A 2 N/A 2 N/A 2 N/A
"Lado Inferior del
Gabinete
Faldones Metálicos"
1038F8A Cubrir el área inferior
del gabinete
2 2 2 2 2 2 2 2
"Lado Inferior del
Gabinete Faldones
Metálicos"
1038F8A Cubrir el área inferior
del gabinete
N/A 2 N/A 2 N/A 2 N/A 2
Cables de Batería
para Modelos "-NIB"
Algunos P/N Para conectar las series
de baterías al gabinete
N/A N/A 10 16 N/A N/A 10 16
Barras para Puentes
de Cobre
1038F3 Para interconexión de
baterías adyacentes
N/A N/A 10 20 N/A N/A N/A N/A
Barras para Puentes
de Cobre
1038F4 Para interconexión de
baterías adyacentes
N/A N/A 3 8 N/A N/A N/A N/A
Barras para Puentes
de Cobre
1038F5 Para interconexión de
baterías adyacentes
N/A N/A N/A N/A N/A N/A 3 8
Barras para Puentes
de Cobre
1038F6 Para interconexión de
baterías adyacentes
N/A N/A N/A N/A N/A N/A 10 20
3.5 Cableado Interno (Típico)
Los gabinetes de baterías utilizan múltiples baterías de 12V CD conectadas en serie para proporcionar el voltaje de CD nominal de
240V CD (±120V CD).
El cableado interno está dimensionando para las corrientes de carga de la aplicación específica. No use otro tamaño de cable que
no sea el proporcionado en el gabinete de baterías.
Cada repisa del gabinete de baterías incluye un diagrama de cableado específico. Refiérase a la sección 6. Instalación para ver
detalles de instalación de la batería.
Todos los breakers están en la capa medio del gabinete de baterías.
Todas las polaridades de conexión de carga serán etiquetadas como “+” (positivo de la batería), “-“ (negativo de la batería) y “N”
(conexión central de la batería) para series de ±120V CD.
Todos los gabinetes de la batería están provistos de un dispositivo de protección de sobrecorriente de circuito de ramal y pueden
conectarse directamente a la carga o al UPS.
3.6 Colocación del Gabinete para Baterías
Coloque el gabinete de baterías en un lugar fresco con flujo de aire libre y lejos de fuentes de calor directo. La vida útil y el rendimiento
de una batería pueden verse considerablemente afectadas por temperaturas elevadas, disminuyendo en un 50% para cada 8.25 °C por
encima de 25 ºC.
1. Prepare la superficie donde se colocará el gabinete. La superficie debe estar limpia, plana y capaz de soportar el gabinete de
baterías y otros equipos instalados cerca. Vea la sección 8. Especificaciones para cargas de piso.
77
3. Instalación del Gabinete de Baterías
2. Deje espacio suficiente en la parte delantera y posterior del gabinete para una correcta ventilación y mantenimiento. La puerta
frontal debe ser accesible para permitir un fácil acceso a las baterías internas, fusibles internos y otros dispositivos de protección
contra sobrecorriente. Para dimensiones y medidas gabinete de baterías, consulte la Sección 6.1 Desempacado e Inspección.
3. Si el gabinete será anclado al suelo, instale tornillos de anclaje adecuados en el orificio situado en la parte inferior del gabinete.
Utilice arandelas para crear una superficie plana entre las áreas de instalación alrededor de los tornillos de anclaje.
4. Con mucho cuidado, retire los tornillos que aseguran el gabinete de baterías a la tarima.
5. Las horquillas del montacargas deben estar a la anchura máxima dentro de la abertura del gabinete y completamente introducidas,
para evitar que se vuelque. Levante el gabinete por la base solamente. Tenga cuidado de no dañar el piso de lámina metálica del
gabinete con las horquillas.
6. Si el gabinete de batería será fijado al suelo, alinee cuidadosamente y baje el gabinete de baterías en los tornillos de anclaje del piso
y fíjelo en su lugar.
7. Si el gabinete no se fijará al piso, bájelo en el espacio designado y luego nivélelo con cuñas. La nivelación no afecta el rendimiento,
pero alinea el gabinete de batería con otros equipos en la instalación.
3.7 Conexión Eléctrica
¡PELIGRO! ¡RIESGO LETAL POR ALTO VOLTAJE!
El tendido del cableado debe estar a cargo de un electricista calificado, de conformidad con las advertencias
descritas en este manual y con todos los códigos de seguridad y eléctricos aplicables. Un cableado incorrecto
puede causar lesiones personales graves y daños a la propiedad.
El gabinete de baterías está conectada a la carga a través de un breaker CD. Esto permite desconectar la batería de la carga y el
cargador para mantenimiento o reparación.
Los breakers de CD en la caja moldeada son aprobados por CE para la protección de circuitos ramales. Si se requiere reemplazarlos,
deben usarse componentes aprobador por CE de la misma especificación de voltaje y corriente.
El tamaño de los cables de conexión de carga debe considerar la caída de voltaje máxima permitida, así como la capacidad de
amperaje continuo y tasa de amperaje de descarga esperada del gabinete de baterías individual. Se recomienda una caída máxima
de 1.5V CD en los cables de conexión de carga. Consulte el Manual del Propietario de la unidad UPS para conocer el tamaño de los
cables recomendados.
Consulte todos los códigos locales, estatales y nacionales para el tamaño y especificaciones de cable apropiadas.
Los dispositivos de protección de circuito externo (fusibles o breakers) deben considerar la tasa de descarga de la batería, el cableado
a proteger y la corriente de cortocircuito de la batería.
Después de ejecutar los procedimientos de instalación en la Sección 6. Instalación, ejecute lo siguiente:
1. Abra la puerta frontal del gabinete de baterías para acceder a los componentes internos. Use un voltímetro digital cuando sea
necesario medir los voltajes.
2. Determine si la batería ha sido inadvertidamente conectada a tierra restableciendo el breaker a la posición "On" y mida el voltaje
entre la terminal de tierra del gabinete de baterías y el punto de conexión de carga positiva dentro del gabinete. Este voltaje debe
medir 0 (cero) VCD. Si el voltaje medido no es cero, determine la causa y corríjala antes de continuar.
3. Regrese el breaker interno a una posición "Off" abierta, como medida de seguridad mientras se conectan los cables de salida. Hacer
esto evita daños en caso de que accidentalmente se pongan en corto los cables.
4. La parte superior del gabinete de baterías incluye recortes ciegos para la entrada del cable de conexión de carga. Despeje el orificio
apropiado y conecte el conducto o el buje del cable.
5. El breaker del circuito de salida permite cables de hasta 300 mm
2
.
6. Conecte un cable adecuado a la oreja de conexión a tierra situada en la parte superior del gabinete de baterías.
7. Introduzca los cables positivo y negativo (y “N” central, si así está equipado) desde el switch de desconexión externo abierto o las
terminales de cableado de campo de la batería del UPS a través del conducto / buje de cable. Conecte a las terminales de salida
respectivas dentro del gabinete de baterías.
78
3. Instalación del Gabinete de Baterías
3.8 Comprobación Eléctrica Final
Antes de cerrar cualquier breaker de conexión o switch de desconexión, siga estos pasos de verificación:
1. Verifique que esté correcto el voltaje de salida del gabinete de baterías.
2. Si los gabinetes de baterías serán operados en paralelo, verifique que los voltajes individuales de salida del sistema coincidan dentro
de 2V CD.
3. Verifique que el voltaje medido entre cualquier terminal de salida y la tierra del gabinete de baterías sea igual a cero.
4. Si alguno de los pasos de verificación anteriores muestra una irregularidad, determine y corrija la causa antes de continuar.
5. Restaure el breaker a la posición “On”.
4. Datos Mecánicos
4.1 Mediciones Físicas
4.1.1 Dimensiones para BP240V65, BP240V65-NIB, BP240V100, BP240V100-NIB
800 mm
[31.5"]
900 mm
[35.4”]
1200 mm
[47.2"]
79
Vista Posterior (bloque de terminales sin tapa)
4
3
2
1
5
Vista Frontal Vista Lateral Vista Posterior
4. Datos Mecánicos
1
Breaker de la Batería
2
Terminal de Batería para UPS de 10kVA ~ 20kVA
3
Terminal de Batería para UPS de 25kVA ~ 60kVA
4
Terminales de Conexión a Tierra
5
Recortes para Cables de la Batería
80
4. Datos Mecánicos
4.1.2 Dimensiones para BP240V65L, BP240V65L-NIB, BP240V100L, BP240V100L-NIB
800 mm
[31.5"]
1100 mm
[43.30"]
1600 mm
[63"]
81
Vista Posterior (bloque de terminales sin tapa)
4
3
2
1
5
4. Datos Mecánicos
Vista Frontal Vista Lateral Vista Posterior
1
Breaker de la Batería
2
Terminal de Batería para
UPS de 10kVA ~ 20kVA
3
Terminal de Batería para
UPS de 25kVA ~ 60kVA
4
Terminales de Conexión
a Tierra
5
Recortes para Cables
de la Batería
82
4. Datos Mecánicos
4.2 Requerimientos Físicos (Todos los Modelos)
Deje algún espacio alrededor del gabinete para operación y ventilación.
1. Deje al menos 800 mm [31.5"] de espacio en el frente para ventilación.
2. Deje al menos 508 mm [20"] de espacio a la derecha e izquierda para su operación.
3. Deje al menos 508 mm [20"] de espacio en la parte posterior para ventilación.
>
508 mm
[20”]
>
508 mm
[20”]
>
508 mm
[20”]
>
508 mm
[20”]
>
800 mm
[31.5"]
83
5. Instalación
Nota: Antes de la instalación, inspeccione la unidad. Cerciórese de que nada se haya dañado dentro del empaque. Conserve el material de
empaque original en un lugar seguro para uso futuro.
5.1 Desempacado e Inspección
Cualquier daño al empaque debe observarse con el transportista en el momento de la recepción.
Retire del empaque el juego de riel, gabinete de baterías y módulos de baterías.
Nota: Los módulos de baterías son muy pesados. Tenga cuidado cuando desempaque y levante la unidad para no causar daños.
No incline el módulo de baterías al retirarlo del empaque.
• Inspeccione el gabinete de baterías para detectar daños que puedan haber ocurrido como resultado del transporte. Si se
encuentran daños, no encienda la unidad. Comuníquese inmediatamente con el distribuidor al que le compró la unidad.
• Compruebe los accesorios de acuerdo con la lista de empaque y póngase en contacto con el distribuidor en caso de que
falten piezas.
3. Retire la espuma de empaque y la tarima biselada. 4. Retire los tornillos que aseguran el gabinete a la
tarima de embarque.
1. Mantenga estable la placa deslizante.
Corte y retire las cintas de sujeción.
2. Retire la bolsa de plástico y la caja de embarque.
84
5. Instalación
5. Use un montacargas para levantar el gabinete de
baterías de la tarima.
5.2 Selección de Posición de Instalación
Seleccione un entorno adecuado para instalar la unidad, a fin de minimizar la posibilidad de daño al sistema de batería y
maximizar la vida útil de las baterías.
1. No bloquee la circulación de aire en las aberturas de ventilación de la unidad.
2. Compruebe que las condiciones ambientales del sitio de instalación coincidan con las especificaciones de la unidad
para evitar recalentamiento o humedad excesiva. Consulte la sección 4.2 Requerimientos Físicos.
3. No coloque la unidad en un ambiente con polvo o corrosivo, ni cerca de objetos inflamables.
4. La unidad no ha sido diseñada para uso en exteriores.
Notas:
Coloque el gabinete de baterías en un entorno limpio y estable. Evite vibraciones, polvo, humedad, gases inflamables, líquidos y
corrosivos.
Para ayudar a evitar altas temperaturas en la sala donde esté instalado el UPS, se recomiendan ventiladores extractores y/o sistemas
de enfriamiento.
Las baterías deben instalarse en un ambiente en donde la temperatura esté dentro de las especificaciones requeridas. La temperatura
es un factor clave para determinar la vida y capacidad de la batería. La temperatura de la batería debe mantenerse entre 20 °C y 25 °C
[59 °F y 77 °F]. Mantenga las baterías alejadas de fuentes de calor, áreas de ventilación del aire principal, etc.
¡ADVERTENCIA!
Los datos típicos de rendimiento de la batería reflejan una temperatura de operación entre 20 °C y 25 °C [59 °F y 77 °F].
Operar el UPS por encima de este rango reducirá la vida de la batería, mientras que operar el UPS por debajo de
este rango reducirá la capacidad de la batería.
Si el UPS no se instalará de inmediato, debe almacenarse en un cuarto sin calor o humedad excesivos.
85
5.3 Cables de Alimentación
El diseño del cable debe cumplir con los voltajes y corrientes proporcionados en esta sección y de acuerdo con los códigos
eléctricos locales.
¡ADVERTENCIA!
AL ARRANCAR, ASEGÚRESE DE ESTAR ATENTO A LA UBICACIÓN Y OPERACIÓN DE LOS AISLADORES
EXTERNOS CONECTADOS AL SUMINISTRO DE ENTRADA Y DERIVACIÓN DEL UPS DEL PANEL DE
DISTRIBUCIÓN DE LA ENERGÍA DE LA RED PÚBLICA.
REVISE PARA VER SI ESTAS ALIMENTACIONES ESTÁN AISLADAS ELÉCTRICAMENTE Y COLOQUE CUALQUIER
SEÑAL DE ADVERTENCIA NECESARIA PARA EVITAR CUALQUIER OPERACIÓN INADVERTIDA
5.3.1 Tamaños de Cables
5.4 Conexiones del Gabinete de Baterías:
Modelos BP240V65, BP240V65-NIB,
BP240V100 y BP240V100-NIB
El diseño de cada gabinete de baterías incluye cables de conexión
de la batería interna, breaker, fusibles y terminales. El gabinete
estándar puede contener 20 piezas de baterías de 12V 65Ah
12V 65Ah 12V 100Ah. El sistema de voltaje de CD para todos
los gabinetes es de 240VCD con series de baterías internas de
±120V.
Las Figuras 5-1 y 5-2 muestran el diseño general del bastidor y
vistas de despiece para los modelos BP240V65, BP240V65-NIB,
BP240V100 y BP240V100-NIB. Las vistas correspondientes
para los modelos BP240V65L, BP240V65L-NIB, BP240V100L y
BP240V100L-NIB se muestran en la sección 5.5 Conexiones del
Gabinete de Baterías: Modelos BP240V65L, BP240V65L-NIB,
BP240V100L y BP240V100L-NIB.
5. Instalación
Figura 5-1: Bastidor del Gabinete de Baterías BP240V65,
BP240V65-NIB, BP240V100
y BP240V100-NIB
UPS
MODEL
BP240V65 / BP240V100
BP240V65-NIB / BP240V100-NIB
BP240V65L / BP240V100L
BP240V65L-NIB / BP240V100L-NIB
Recomendado
Fuerza de Torsión
(Apriete)
Tamaños de Cable (Cableado THHW a 75 °C)
Entrada de CD Conexión a Tierra Entrada de CD Conexión a Tierra
10kVA*
6 AWG 6 AWG 6 AWG 6 AWG Anderson Connector
(No Torque Parameter)
0kgf.com / 0N•m
15kVA*
2 x 6 AWG 2 x 6 AWG 2 x 6 AWG 2 x 6 AWG
20kVA*
2 x 6 AWG 2 x 6 AWG 2 x 6 AWG 2 x 6 AWG
25kVA*
1/0 AWG 2 AWG 1/0 AWG 2 AWG 450kgf.cm/
44N•m
30kVA*
1/0 AWG 1/0 AWG 1/0 AWG 1/0 AWG
50kVA
2/0 AWG 2/0 AWG 2/0 AWG 2/0 AWG
60kVA
2/0 AWG 2/0 AWG 2/0 AWG 2/0 AWG
80kVA
2/0 AWG*2 2/0 AWG*2
100kVA
2/0 AWG*2 2/0 AWG*2
* Los sistemas UPS S3M10-30K no soportan los modelos de gabinete de baterías BP240V100L/100L-NIB.
86
5. Instalación
5.4.1 Retire la Cubierta del Bastidor
Coloque el gabinete de baterías en posición. Retire los paneles superior, frontal, izquierdo y derecho. Retire la placa de la
cubierta derecha e izquierda de la batería y la aleta de la batería para instalar las baterías.
5.4.2 Instalación y Conexión de la Batería
Cada grupo de baterías tiene 20 baterías en serie (BAT+, N y BAT-). Coloque las baterías en el gabinete de abajo haca arriba
una por una, entonces conecte los cables de batería de acuerdo con los diagramas que siguen.
Nota: La polaridad positiva y negativa de la batería no pueden invertirse ni estar en corto circuito. Hacerlo dañará la batería y/o causará
lesiones. No toque las terminales positiva y negativa de la batería al mismo tiempo. Antes de reemplazar o retirar las baterías, desconecte el
breaker, jale las terminales de la celda y retire los tornillos de la barra del bus de cobre. No seguir las instrucciones podría causar daños al
equipo o lesiones personales. La instalación debe consistir en 40 baterías.
Figura 5-2: Vista de Despiece del Bastidor, Modelos BP240V65, BP240V65-NIB, BP240V100, BP240V100-NIB
87
5. Instalación
Figura 5-3A: Vista Frontal
Figura 5-3B: Vista Posterior
Capa 3
Capa 2
Capa 1
Grupo positivo
10 piezas
Grupo negativo 10
piezas
Fusibles
400A (x2)
Breaker
de la batería
Conector
de 25kVA ~
100kVA
Conector
de 10kVA ~
20kVA
88
5. Instalación
Figura 5-4: Diagrama de Cableado para el Modelo BP240V65
La Parte Posterior
La Parte Posterior
La Parte Posterior
Capa 3
Capa 2
Capa 1
El Frente
El Frente
El Frente
Nota: Este manual puede descargarse
en color en tripplite.com, que
muestra los cables con los colores
correspondientes:
Rojo = Positivo
Azul = Borne Central
Negro = Negativo
89
Nota: Este manual puede descargarse
en color en tripplite.com, que
muestra los cables con los colores
correspondientes:
Rojo = Positivo
Azul = Borne Central
Negro = Negativo
5. Instalación
Figura 5-5: Diagrama de Cableado para el Modelo BP240V100
La Parte Posterior
La Parte Posterior
La Parte Posterior
Capa 3
Capa 2
Capa 1
El Frente
El Frente
El Frente
90
5. Instalación
Figura 5-6A
Figura 5-6B
5.4.2.1 Instalación y configuración de la batería:
Modelos BP240V65-NIB, BP240V100-NIB
1. Retire todos los tornillos etiquetados 1 (Figuras 5-6A y 5-6B).
91
Figura 5-7
3. Retire todos los tornillos de los soportes de retención de la batería y retire los soportes de retención (Figura 5-8).
2. Retire las placas superior, lado derecho y lado izquierdo (Figura 5-7).
5. Instalación
Figura 5-8
92
5. Instalación
Figura 5-9: Modelo BP240V65-NIB
Figura 5-10: Modelo BP240V100-NIB
4. Instale 8 módulos de baterías en la capa 1 (Figura 5-9: Modelo BP240V65-NIB o Figura 5-10: Modelo BP240V100-NIB).
93
Figura 5-11: Modelo BP240V65-NIB
5. Instale 6 módulos de baterías en la capa 2 (Figura 5-11: Modelo BP240V65-NIB o Figura 5-12: Modelo BP240V100-NIB).
5. Instalación
Figura 5-12: Modelo BP240V100-NIB
94
5. Instalación
Figura 5-13: Modelo BP240V65-NIB
Figura 5-14: Modelo BP240V100-NIB
6. Instale 6 módulos de baterías en la capa 3 (Figura 5-13: Modelo BP240V65-NIB o Figura 5-14: Modelo BP240V100-NIB).
95
Figura 5-15: Modelo BP240V65-NIB
7. Reinstale todos los soportes y tornillos de retención de la batería (Figura 5-15: Modelo BP240V65-NIB o
Figura 5-16: Modelo BP240V100-NIB).
5. Instalación
Figura 5-16: Modelo BP240V100-NIB
96
5. Instalación
Figura 5-17A
Figura 5-17B
8. Modelo BP240V65-NIB: Instale barras de bus de cobre (13 piezas) entre baterías adyacentes y los tornillos y postes de
inserción de la batería (Figuras 5-17A y 5-17B).
97
Figura 5-18A
9. Modelo BP240V100-NIB: Instale barras de bus de cobre (12 piezas) entre baterías adyacentes y los tornillos y postes de
inserción de la batería (Figuras 5-18A y 5-18B).
5. Instalación
Figura 5-18B
98
5. Instalación
Figura 5-19: Modelo BP240V65-NIB
Figura 5-20: Modelo BP240V100-NIB
10. Conecte los cables de la batería 1+ a la barra de bus BAT+ B, Batería 10- a Barra de bus BATN, Batería 11+ a Barra
de bus BATN, batería 20- a Barra de bus BAT - y los cables de conexión de capa (Figura 5-19: Modelo BP240V65-NIB o
Figura 5-20: Modelo BP240V100-NIB y Figura 5-21).
Notas:
Use los esquemas de cableado como
referencia para los siguientes conjuntos:
Use la Figura 5-4 para BP240V65-NIB
Use la Figura 5-5 para BP240V100-NIB
Este manual puede descargarse en
color en tripplite.com, que muestra
los cables con los colores
correspondientes:
Rojo = Positivo
Azul = Borne Central
Negro = Negativo
99
Figura 5-21
5. Instalación
Figura 5-22
11. Vuelva a instalar todas las cubiertas y tornillos (Figura 5-22).
100
5. Instalación
Figura 5-23: Bastidor de Baterías BP240V65L, BP240V65L-NIB,
BP240V100L y BP240V100L-NIB
Figura 5-24: Vista de Despiece – Modelos BP240V65L, BP240V65L-NIB, BP240V100l, BP240V100L-NIB
5.5 Conexiones del Gabinete de
Baterías: Modelos BP240V65L,
BP240V65L-NIB, BP240V100L y
BP240V100L-NIB
El diseño de cada gabinete de baterías incluye cables de conexión
de la batería interna, breaker, fusibles y terminales. El gabinete
estándar puede contener 20 piezas de baterías de 12V 65Ah (12V
/ 100Ah). Los gabinetes de baterías de larga duración “L” pueden
contener 40 piezas de las baterías de 12V 65Ah (12V 100Ah). El
sistema de voltaje de CD para todos los gabinetes es de 240VCD
con series de baterías internas de ±120V.
Las Figuras 5-23 y 5-24 muestran el diseño general del bastidor
y vistas de despiece para los modelos BP240V65L, BP240V65L-
NIB, BP240V100L y BP240V100L-NIB. Las vistas correspondientes
para los modelos BP240V65, BP240V65-NIB, BP240V100 y
BP240V100-NIB se muestran en la sección 5.4 Conexiones del
Gabinete de Baterías: Modelos BP240V65, BP240V65-NIB,
BP240V100 y BP240V100-NIB.
5.5.1 Retire la
Cubierta del Bastidor
Coloque la caja de baterías en su
ubicación final. Retire los paneles
superior, frontal, izquierdo y derecho.
Retire las Placas de la cubierta derecha
e izquierda del módulo de baterías y los
soportes de batería para instalar las series
de baterías.
101
5. Instalación
Figura 5-25A: Vista Frontal
5.5.2 Instalación y Conexión de la Batería
Las 40 baterías pueden dividirse en dos grupos conectados en paralelo para su uso. Cada grupo tiene 20 baterías en serie
(BAT+, N y BAT-). Coloque las baterías en el gabinete de abajo haca arriba una por una, entonces conecte los cables de
batería de acuerdo con los diagramas que siguen.
Nota: La polaridad positiva y negativa de la batería no pueden invertirse ni estar en corto circuito. Hacerlo dañará la batería y/o causará
lesiones. No toque las terminales positiva y negativa de la batería al mismo tiempo. Antes de reemplazar o retirar las baterías, desconecte
el breaker, jale las terminales de la celda y retire los tornillos de la barra del bus de cobre. No seguir las instrucciones podría causar daños
al equipo o lesiones personales. La instalación debe consistir en 40 baterías.
Capa 3
Capa 4
Capa 2
Capa 1
Grupo de
Baterías 2
Grupo de Baterías
1
102
Figura 5-25B: Vista Posterior
5. Instalación
Fusibles
400A (x2)
Breaker de la
batería
Conector
de 25kVA ~
100kVA
Conector
de 10kVA ~
20kVA
103
5. Instalación
Figura 5-26: Diagrama de Cableado para BP240V65L (40 baterías instaladas)
Capa 2
Capa 4
Capa 1
Capa 3
La Parte Posterior
El Frente
La Parte Posterior
El Frente
La Parte Posterior
El Frente
La Parte Posterior
El Frente
Nota: Este manual puede descargarse
en color en tripplite.com, que
muestra los cables con los colores
correspondientes:
Rojo = Positivo
Azul = Borne Central
Negro = Negativo
104
5. Instalación
Figura 5-27: Diagrama de Cableado para BP240V100L (40 baterías instaladas)
Cuando se complete la instalación y conexión de la batería, use un multímetro u otro instrumento para comprobar si los
voltajes entre BAT+ y N, N y BAT- son normales. Si es normal, bloquee la cubierta del bastidor.
Capa 2
Capa 4
Capa 1
Capa 3
La Parte Posterior
El Frente
La Parte Posterior
El Frente
La Parte Posterior
El Frente
La Parte Posterior
El Frente
Nota: Este manual puede descargarse
en color en tripplite.com, que
muestra los cables con los colores
correspondientes:
Rojo = Positivo
Azul = Borne Central
Negro = Negativo
105
5. Instalación
Figura 5-28A
Figura 5-28B
5.5.2.1 Instalación y Configuración de la Batería:
Modelos BP240V65L-NIB, BP240V100L-NIB
1. Retire todos los tornillos etiquetados 1 (Figuras 5-28A y 5-28B).
106
Figura 5-29
3. Retire todos los tornillos de los soportes de retención de la batería y retire los soportes de retención (Figura 5-30).
2. Retire las placas superior, derecha e izquierda (Figura 5-29).
5. Instalación
Figura 5-30
107
5. Instalación
Figura 5-31: Modelo BP240V65L-NIB
Figura 5-32: Modelo BP240V100L-NIB
4. Instale 10 módulos de baterías en la capa 1 (Figura 5-31: Modelo BP240V65L-NIB o Figura 5-32: Modelo BP240V100L-NIB).
108
5. Instalación
Figura 5-33: Modelo BP240V65L-NIB
5. Instale 10 módulos de baterías en la capa 2 (Figura 5-33: Modelo BP240V65L-NIB o Figura 5-34: Modelo BP240V100L-NIB).
Figura 5-34: Modelo BP240V100L-NIB
109
5. Instalación
Figura 5-35: Modelo BP240V65L-NIB
Figura 5-36: Modelo BP240V100L-NIB
6. Instale 10 módulos de baterías en la capa 3 (Figura 5-35: Modelo BP240V65L-NIB o Figura 5-36: Modelo BP240V100L-NIB).
110
Figura 5-37: Modelo BP240V65L-NIB
7. Instale 10 módulos de baterías en la capa 4 (Figura 5-37: Modelo BP240V65L-NIB o Figura 5-38: Modelo BP240V100L-NIB).
5. Instalación
Figura 5-38: Modelo BP240V100L-NIB
111
5. Instalación
Figura 5-39
Figura 5-40A
8. Reinstale todos los soportes y tornillos de retención de la batería (Figura 5-39).
9. Modelo BP240V65L-NIB: Instale barras de bus de cobre (13 piezas) entre baterías adyacentes y los tornillos y postes de
inserción de la batería (Figuras 5-40A y 5-40B).
112
Figura 5-40B
5. Instalación
Figura 5-41A
10. Modelo BP240V100L-NIB: Instale barras de bus de cobre (12 piezas) entre baterías adyacentes y los tornillos y postes de
inserción de la batería (Figuras 5-41A y 5-41B).
113
5. Instalación
Figura 5-41B
Figura 5-42: Modelo BP240V65L-NIB
11. Conecte los cables del grupo de baterías 1 batería 1+ a barra de bus BAT+, Batería 10- a barra de bus BATN, Batería 11+ a
barra de bus BATN, batería 20- a barra de bus BAT- bus y los cables de conexión de nivel. Conecte la batería del grupo de baterías
2 21+ a la barra de bus BAT+, Batería 30- a barra de bus BATN, Batería 31+ a barra de bus BATN, batería 40- a barra de cobre
BAT y los cables de conexión de nivel (Figura 5-42: Modelo BP240V65L-NIB o Figura 5-43: Modelo BP240V100L y Figura 5-44).
Notas:
Use los esquemas de cableado como
referencia para los siguientes conjuntos:
Use la Figura 5-26 para BP240V65L-NIB
Use la Figura 5-27 para BP240V100L-NIB
Este manual puede descargarse en color
en tripplite.com, que muestra los cables
con los colores correspondientes:
Rojo = Positivo
Azul = Borne Central
Negro = Negativo
114
Figura 5-43: Modelo BP240V100L-NIB
Figura 5-44
5. Instalación
115
Figura 5-45
12. Vuelva a instalar todas las cubiertas y tornillos (Figura 5-45).
5. Instalación
116
5. Instalación
5.6 Conexiones de Múltiples de Módulos de Baterías
¡PRECAUCIÓN!
Asegure la polaridad correcta de la conexión de la serie de baterías. No mezcle baterías con capacidades
diferentes o marcas diferentes o baterías nuevas y viejas.
¡ADVERTENCIA!
ASEGURE LA POLARIDAD CORRECTA DE LAS CONEXIONES DEL EXTREMO DE LA CADENA AL BREAKER DE
LA BATERÍA Y DEL BREAKER DE LA BATERÍA A LAS TERMINALES DEL UPS (ES DECIR (+) A (+) / (-) A (-)
/ (N) A (N)). DESCONECTE UNO O MÁS ENLACES DE CELDA DE LA BATERÍA EN CADA NIVEL. NO VUELVA
A CONECTAR ESTOS ENLACES Y NO CIERRE EL BREAKER DE LA BATERÍA A MENOS QUE TODAS LAS
CONEXIONES ESTÉN CORRECTAMENTE REVISADAS Y APROBADAS.
UPS Gabinete de Baterías
Figura 5-46: Conexión de BP240V65L y BP240V65L-NIB para UPS de 10kVA, 15kVA y 20kVA
117
5. Instalación
UPS Gabinete de Baterías
Figura 5-47: Conexión de BP240V65L y BP240V65L-NIB para UPS de 25kVA y 30kVA
118
5. Instalación
UPS Gabinete de Baterías
Figura 5-48: Conexión de BP240V65L, BP240V65L-NIB, BP240V100L
o BP240V100L-NIB para sistemas UPS de 50kVA y 60kVA
119
5. Instalación
UPS Gabinete de Baterías
Figura 5-49: Conexión de BP240V65L, BP240V65L-NIB, BP240V100L
o BP240V100L-NIB para UPS de 80kVA y 100kVA
120
6. Operación y Configuración de Modelos de
UPS S3M y Gabinetes de Baterías
6.1 Compatibilidad de UPS S3M con Gabinetes de Baterías
BP240V65 a BP240V100L
Gabinetes con
Baterías Internas BP240V65 BP240V65L BP240V100 BP240V100L
Gabinetes SIN
Baterías Internas BP240V65-NIB BP240V65L-NIB BP240V100-NIB BP240V100L-NIB
UPS de 10kVA a
20kVA con Baterías
Internas
• S3M10K1B,
S3M10K2B,
S3M10K3B
• S3M15K2B
S3M15K3B
• S3M20K3B
No No No No
UPS de 10kVA a
20kVA SIN Baterías
Internas
• S3M10K-NIB
• S3M15K-NIB
• S3M20K-NIB
No
Gabinetes con
Baterías Internas BP240V65 BP240V65L BP240V100 BP240V100L
Gabinetes SIN
Baterías Internas BP240V65-NIB BP240V65L-NIB BP240V100-NIB BP240V100L-NIB
UPS de 25kVA
~ 100kVA SIN
Baterías Internas
• S3M25K
• S3M30K
No
• S3M50K
• S3M60K No
• S3M80K
• S3M100K
No No
121
6.2 Configuración del UPS de 10K ~ 20K para Gabinetes
de Baterías Específicos Usando la Pantalla LCD
6.2.1 Pantalla de Inicio del UPS S3M10-20K
¡PRECAUCIÓN!
La configuración para la mayoría de los parámetros no puede
cambiarse cuando el UPS está en modo de inversor.
6. Operación y Configuración de Modelos de
UPS S3M y Gabinetes de Baterías
122
6.2.2 Configuración
Haga click en el ícono de Configuración para ingresar dos niveles de configuración. La configuración básica es para
la configuración del usuario y la configuración avanzada es sólo para el personal técnico. Póngase en contacto con su
administrador para ingresar a la configuración avanzada.
Configuración Avanzada: Haga click en Configuración Avanzada e ingrese la contraseña correcta. La contraseña de
usuario es “191210”.
6. Operación y Configuración de Modelos de
UPS S3M y Gabinetes de Baterías
123
6.2.3 Configuración de la Batería
Haga click en Configuración de la Batería
6. Operación y Configuración de Modelos de
UPS S3M y Gabinetes de Baterías
124
6.2.4 Configuración del UPS S3M10-20K-NIB y Optimización de
la Carga de los Gabinetes de Baterías BP240V65/V65L y
BP240V100/V100L
Paso 1: Configuración del Grupo de Baterías
La Cantidad del Grupo de Baterías es 1 para cada juego de 20 baterías que estén en el modelo del UPS o conectadas al
modelo del UPS. Por ejemplo, el UPS modelo S3M20K-NIB no tiene baterías internas y es el Grupo de Baterías 1 de forma
predeterminada para cualquier modelo de UPS. Sin embargo, para conectar un gabinete BP240V65 con 20 baterías internas
al S3M20K-NIB, el UPS S3M20K-NIB debe permanecer configurado para el Grupo de Baterías 1 (un juego de 20 baterías).
Sin embargo, para conectar un segundo BP240V65 al UPS S3M20K-NIB, el Grupo de Baterías del UPS debe ser 2 (dos
juegos de 20 baterías). Obtenga el número de Grupo de Baterías basado en la combinación de modelos de UPS S3M y
Gabinete de Baterías específicos de la tabla debajo de la Sección 6.4.
El valor puede ser de 1 a 8. El valor predeterminado es 1 para modelos de UPS S3M sin baterías internas.
Paso 2: Configuración del Número de Baterías
El número de baterías debe permanecer en 20 para todos los UPS modelo S3M10-100K cuando se conecten con gabinetes
de baterías externas de Tripp Lite diseñados para la serie de UPS de la Serie S3M.
Paso 3: Configuración de la Capacidad de Una Sola Batería (Ah)
Cambie la capacidad de una sola batería (Ah) a la capacidad de Ah individual para una batería individual, como sigue, para los
modelos específicos de gabinete de baterías:
• BP240V09 y BP240V09K: La Capacidad de Una Sola Batería (Ah) es 9
• BP240V40 y BP240V40L: La Capacidad de Una Sola Batería (Ah) es 40
• BP240V65 y BP240V65L: la La Capacidad de Una Sola Batería (Ah) es 65
• BP240V100 y BP240100L: la La Capacidad de Una Sola Batería (Ah) es 100
Los valores pueden ser de 7 ~ 2000.
Desplácese a la siguiente pantalla presionando la flecha hacia abajo.
6. Operación y Configuración de Modelos de
UPS S3M y Gabinetes de Baterías
125
Paso 4: Configuración de la Corriente Máxima de Carga
La Corriente Máxima de Carga es la corriente de carga estimada que utilizará el UPS para cargar las baterías. Obtenga la
corriente máxima de carga estimada recomendada en base a la combinación específica de UPS S3M y modelo de gabinete
de baterías de la tabla en la Sección 6.4.
Voltaje en Flotación y Elevación: El UPS está configurado de fábrica para voltajes adecuados en flotación (2.27V/celda,
13.62V/batería) y elevación (2.35V/celda, 14.1V/batería).
Voltaje en flotación de celda: l valor del voltaje en flotación puede ser de 2.23 ~ 2.30 V/celda. El valor predeterminado es
2.27 V/celda.
Voltaje en elevación de celda: El valor de voltaje ecualizado de la batería puede ser de 2.30 ~ 2.40 V/celda. El valor
predeterminado es 2.35 V/celda.
Paso 5: Configuración de la Duración Promedio de Carga (min)
La configuración de la duración promedio de carga en minutos es una estimación de la duración del cargador de elevación
para cargar baterías nuevas a una capacidad del 90% a 25 °C. Obtenga el número de Duración de Carga Promedio
recomendado (Prom) (min) basado en la combinación específica de UPS S3M y gabinete de baterías de la tabla en la
sección 6.4. Tenga en cuenta que las duraciones recomendadas de carga de elevación de la batería son estimaciones
basadas solamente en baterías nuevas. Estos números pueden cambiar con la edad de las baterías y la temperatura
ambiente de la batería. Para cambiar la Duración Promedio de Carga, presione directamente en el valor de 240
predeterminado en la pantalla.
La duración promedio de carga (Prom) es el límite de tiempo de carga de elevación de la batería. El valor puede ser de 1 ~
999 min. El valor predeterminado es de 240 (4 horas).
Voltaje de la Batería EOD: El fin del voltaje de descarga es el corte de bajo voltaje de las baterías durante una operación en
modo de respaldo por batería. El valor puede ser de 1.60 ~ 1.90. El valor predeterminado es 1.67V/celda o 10.02VCD por batería.
Coeficiente de Compensación de Temperatura en Flotación: Modifica el voltaje de compensación después de activar el
switch. El valor puede ser de 0.001 ~ 0.007v/celda/°C. El valor predeterminado es de 0.003v/celda/°C.
Configuración de Carga de Elevación: La carga de elevación puede configurarse como Inactiva o Activa. El valor
predeterminado es Activa.
Advertencia de Sin Batería: Mantenga activa esta alarma si desea que el UPS proporcione una advertencia cuando No haya
baterías presentes. El valor predeterminado es Alarma.
6. Operación y Configuración de Modelos de
UPS S3M y Gabinetes de Baterías
126
6.3 Configuración del UPS de 25K ~ 100K para Gabinetes de
Baterías Específicos Usando la Pantalla LCD
¡PRECAUCIÓN!
La configuración para la mayoría de los parámetros no puede
cambiarse cuando el UPS está en modo de inversor.
6. Operación y Configuración de Modelos de
UPS S3M y Gabinetes de Baterías
127
6.3.1 Pantalla de Inicio del UPS S3M25-100K
6.3.2 Configuración
Haga click en el ícono de Configuración para ingresar dos niveles de configuración. La configuración básica es para la
configuración del usuario y la configuración avanzada es sólo para el personal técnico. Póngase en contacto con su
administrador para ingresar a la configuración avanzada.
Configuración Avanzada: Haga click en Configuración Avanzada e ingrese la contraseña correcta. La contraseña de
usuario es “191210”.
6. Operación y Configuración de Modelos de
UPS S3M y Gabinetes de Baterías
128
6. Operación y Configuración de Modelos de
UPS S3M y Gabinetes de Baterías
129
6.3.3 Configuración de la Batería
Haga click en BATT Setup [Configuración de Batería]
Temperatura de Flotación. Compen.: La configuración de compensación del sensor de temperatura puede cambiarse para
activar cuando se conecte un sensor de temperatura de la batería al puerto posterior RJ45 del sistema UPS.
Selección del Sensor de Temperatura: Configure el tipo de sensor de temperatura en NTC para uno solo y distancias
cortas. Configure el tipo de sensor de temperatura en RS485 para varios y distancias grandes.
6. Operación y Configuración de Modelos de
UPS S3M y Gabinetes de Baterías
130
6.3.4 Configuración del UPS S3M25-100K y Optimización de la Carga
de los Gabinetes de Baterías BP240V65/V65L y BP240V100/V100L
Paso 1: Configuración del Grupo de Baterías
La Cantidad del Grupo de Baterías es 1 para cada juego de 20 baterías que estén en el modelo del UPS o conectadas al
modelo del UPS. Por ejemplo, el UPS modelo S3M100K no tiene baterías internas y es el Grupo de Baterías 1 de forma
predeterminada. Sin embargo, para conectar un gabinete BP240V100L con 40 baterías internas al S3M100K, el UPS
S3M100K debe configurarse a Grupo de Baterías 2. Para conectar un segundo gabinete BP240V100L al UPS S3M100K, el
Grupo de Baterías debe configurarse en 4 (cuatro juegos de 20 baterías). Obtenga el número de Grupo de Baterías basado en
la combinación de modelos de UPS S3M y Gabinete de Baterías específicos de la tabla debajo de la Sección 6.4.
El valor puede ser de 1 a 8. El valor predeterminado es 1 para modelos de UPS S3M sin baterías internas.
Paso 2: Configuración del Número de Baterías
El número de baterías debe permanecer en 20 para todos los UPS modelo S3M10-100K cuando se conecten con gabinetes
de baterías externas de Tripp Lite diseñados para la serie de UPS de la Serie S3M.
Paso 3: Configuración de la Capacidad de Una Sola Batería (Ah)
Cambie la Capacidad de Una Sola Batería (Ah) a la capacidad de Ah individual para una batería individual, como sigue, para el
modelo específico de gabinete de baterías:
• BP240V40 y BP240V40L: La Capacidad de Una Sola Batería (Ah) es 40
• BP240V65 y BP240V65L: La Capacidad de Una Sola Batería (Ah) es 65
• BP240V100 y BP240V100L: La Capacidad de Una Sola Batería (Ah) es 100
Los Valores de Una Sola Batería (Ah) pueden ser de 7 ~ 2000.
Desplácese a la siguiente pantalla presionando la flecha hacia abajo.
6. Operación y Configuración de Modelos de
UPS S3M y Gabinetes de Baterías
131
Paso 4: Configuración de coeficiente de limitación de corriente de carga (C)
El límite de corriente de carga es un múltiplo de la capacidad de la batería. Se usa para establecer el límite de tiempo de
carga de elevación de la batería. El valor puede ser 0.05 ~ 0.25 y es 0.25 de forma predeterminada. Obtenga el coeficiente
de limitación (C) de corriente (cur) de carga (Chg) basado en la combinación de UPS S3M y gabinete de baterías
específicos de la tabla en la Sección 6.4.
Voltaje en Flotación y Elevación: El UPS está configurado de fábrica para voltajes adecuados en flotación (2.27V/celda,
13.62V/batería) y elevación (2.35V/celda, 14.1V/batería).
Voltaje en flotación de celda: l valor del voltaje en flotación puede ser de 2.23 ~ 2.30 V/celda. El valor predeterminado es
2.27 V/celda.
Voltaje en elevación de celda: El valor de voltaje ecualizado de la batería puede ser de 2.30 ~ 2.40 V/celda. El valor
predeterminado es 2.35 V/celda.
Paso 5: Configuración de la Duración Promedio de Carga (min)
La configuración de la duración promedio de carga en minutos es una estimación de la duración del cargador de elevación
para cargar baterías nuevas a una capacidad del 90% a 25 °C. Obtenga el número de Duración de Carga Promedio
recomendado (Prom) (min) basado en la combinación específica de UPS S3M y gabinete de baterías de la tabla en la sección
6.4. Tenga en cuenta que las duraciones recomendadas de carga de elevación de la batería son estimaciones basadas
solamente en baterías nuevas. Estos números pueden cambiar con la edad de las baterías y la temperatura ambiente de
la
batería. Para cambiar la Duración Promedio de Carga, presione directamente en el valor de 240 predeterminado en la pantalla.
La duración promedio de carga (Prom) es el límite de tiempo de carga de elevación de la batería. El valor puede ser
de 1 ~ 999 min. El valor predeterminado es de 240 (4 horas).
6. Operación y Configuración de Modelos de
UPS S3M y Gabinetes de Baterías
132
Voltaje de la Batería EOD: El fin del voltaje de descarga es el corte de bajo voltaje de las baterías durante una operación en
modo de respaldo por batería. El valor puede ser de 1.60 ~ 1.90. El valor predeterminado es 1.67V/celda o 10.02VCD por
batería.
Coeficiente de Compensación de Temperatura en Flotación: Modifica el voltaje de compensación después de activar el
switch. El valor puede ser de 0.001 ~ 0.007v/celda/°C. El valor predeterminado es de 0.003v/celda/°C.
Configuración de Carga de Elevación: La carga de elevación puede configurarse como Inactiva o Activa. El valor
predeterminado es Activa.
Advertencia de Sin Batería: Mantenga activa esta alarma si desea que el UPS proporcione una advertencia cuando No haya
baterías presentes. El valor predeterminado es Activa.
6. Operación y Configuración de Modelos de
UPS S3M y Gabinetes de Baterías
133
6.4 Tabla de Referencia de Configuración para Modelos de
Sistemas UPS S3M10-100K y Modelos de Gabinete de
Baterías BP240V09K-BP240V100L
Configuraciones para UPS S3M10K-NIB, S3M15K-NIB, S3M20K-NIB sin baterías internas
Módulos
de Baterías
Baterías Cantidad de
Gabinetes
de Baterías
Paso 1 Paso 2 Paso 3 Paso 4 Paso 5
Grupo de
Baterías
Número
de Baterías
Capacidad
de Una
Sola Batería
Máxima
Corriente
de Carga (A)
Duración Promedio de Carga
(min) Tiempo (minutos) para
Cargar Baterías al 90% a 25 °C
BP240V65 20 x 65Ah 1 1 20 65 9.75 500
BP240V65 20 x 65Ah 2 2 20 65 19.5 500
BP240V65 20 x 65Ah 3 3 20 65 20 720
BP240V65L 40 x 65Ah 1 2 20 65 19.5 500
BP240V65L 40 x 65Ah 2 4 20 65 20 960
BP240V100 20 x 100Ah 1 1 20 100 15 500
Configuraciones para S3M25K y S3M30K
Módulos
de Baterías
Baterías Cantidad de
Gabinetes
de Baterías
Paso 1 Paso 2 Paso 3 Paso 4 Paso 5
Grupo de
Baterías
Número
de Baterías
Capacidad
de Una
Sola Batería
Coeficiente de
Limitación de
Corriente de
Carga (C)
Duración Promedio de Carga
(min) Tiempo (minutos) para
Cargar Baterías al 90% a 25 °C
BP240V65 20x 65Ah 1 1 20 65 0.15 540
BP240V65 20 x 65Ah 2 2 20 65 0.15 540
BP240V65 20 x 65Ah 3 3 20 65 0.1 900
BP240V65L 40 x 65Ah 1 2 20 65 0.15 540
BP240V65L 40 x 65Ah 2 4 20 65 0.07 999
BP240V100 20 x 100Ah 1 1 20 100 0.15 540
Configuraciones para S3M50K y S3M60K
Módulos
de Baterías
Baterías Cantidad de
Gabinetes
de Baterías
Paso 1 Paso 2 Paso 3 Paso 4 Paso 5
Grupo de
Baterías
Número
de Baterías
Capacidad
de Una
Sola Batería
Coeficiente de
Limitación de
Corriente de
Carga (C)
Duración Promedio de Carga
(min) Tiempo (minutos) para
Cargar Baterías al 90% a 25 °C
BP240V65 20 x 65Ah 1 1 20 65 0.15 540
BP240V65 20 x 65Ah 2 2 20 65 0.15 540
BP240V65 20 x 65Ah 3 3 20 65 0.15 540
BP240V65L 40 x 65Ah 1 2 20 65 0.15 540
BP240V65L 40 x 65Ah 2 4 20 65 0.15 540
BP240V65L 40 x 65Ah 3 6 20 65 0.1 840
BP240V100 20 x 100Ah 1 1 20 100 0.15 540
BP240V100 20 x 100Ah 2 2 20 100 0.15 540
BP240V100 20 x 100Ah 3 3 20 100 0.13 540
BP240V100L 40 x 100Ah 1 2 20 100 0.15 540
BP240V100L 40 x 100Ah 2 4 20 100 0.1 840
6. Operación y Configuración de Modelos de
UPS S3M y Gabinetes de Baterías
134
Configuraciones para S3M80K
Módulos
de Baterías
Baterías Cantidad de
Gabinetes
de Baterías
Paso 1 Paso 2 Paso 3 Paso 4 Paso 5
Grupo de
Baterías
Número
de Baterías
Capacidad
de Una
Sola Batería
Coeficiente
de Limitación
de Corriente
de Carga (C)
Duración Promedio de Carga
(min) Tiempo (minutos) para
Cargar Baterías al 90% a 25 °C
BP240V65 20 x 65Ah 1 1 20 65 0.15 540
BP240V65 20 x 65Ah 2 2 20 65 0.15 540
BP240V65 20 x 65Ah 3 3 20 65 0.15 540
BP240V65L 40 x 65Ah 1 2 20 65 0.15 540
BP240V65L 40 x 65Ah 2 4 20 65 0.15 540
BP240V65L 40 x 65Ah 3 6 20 65 0.15 540
BP240V100 20 x 100Ah 1 1 20 100 0.15 540
BP240V100 20 x 100Ah 2 2 20 100 0.15 540
BP240V100 20 x 100Ah 3 3 20 100 0.15 540
BP240V100L 40 x 100Ah 1 2 20 100 0.15 540
BP240V100L 40 x 100Ah 2 4 20 100 0.15 540
BP240V100L 40 x 100Ah 3 6 20 100 0.1 840
Configuraciones para S3M100K
Módulos
de Baterías
Baterías Cantidad de
Gabinetes
de Baterías
Paso 1 Paso 2 Paso 3 Paso 4 Paso 5
Grupo de
Baterías
Número
de Baterías
Capacidad
de Una
Sola Batería
Coeficiente
de Limitación
de Corriente
de Carga (C)
Duración Promedio de Carga
(min) Tiempo (minutos) para
Cargar Baterías al 90% a 25 °C
BP240V65 20 x 65Ah 1 1 20 65 0.15 540
BP240V65 20 x 65Ah 2 2 20 65 0.15 540
BP240V65 20 x 65Ah 3 3 20 65 0.15 540
BP240V65L 40 x 65Ah 1 2 20 65 0.15 540
BP240V65L 40 x 65Ah 2 4 20 65 0.15 540
BP240V65L 40 x 65Ah 3 6 20 65 0.15 540
BP240V100 20 x 100Ah 1 1 20 100 0.15 540
BP240V100 20 x 100Ah 2 2 20 100 0.15 540
BP240V100 20 x 100Ah 3 3 20 100 0.15 540
BP240V100L 40 x 100Ah 1 2 20 100 0.15 540
BP240V100L 40 x 100Ah 2 4 20 100 0.15 540
BP240V100L 40 x 100Ah 3 6 20 100 0.13 540
6. Operación y Configuración de Modelos de
UPS S3M y Gabinetes de Baterías
135
7.1 Especificaciones del Gabinete de Baterías
Voltaje Nominal de CD: ± 120V CD, 240V CD
Módulo de baterías BP240V65 (-NIB) BP240V100 (-NIB) BP240V65L (-NIB) BP240V100L (-NIB)
Dimensión
An x Pr x Al
[31.5" x 35.4" x 47.2"]
800 x 900 x 1200 mm
[31.5" x 43.3" x 63"]
800 x 1100 x 1600 mm
Peso
275.8 kg [608 lb]* 421.8 kg [930 lb]* 491.2 kg [1083 lb]* 742.5 kg [1637 lb]*
Breaker
1x 250A 1x 600A
Fusible
2x 400A 4x 400A
*Los modelos con sufijo -NIB no incluyen baterías internas, de modo que su peso total varía en función de las baterías
instaladas por el usuario final.
El gabinete de batería debe almacenarse en un ambiente limpio y seguro con una temperatura inferior a 40 °C [104 °F] y una
humedad relativa inferior al 90% (sin condensación). De ser posible, almacene el gabinete de baterías en su contenedor de
embarque original. Cargue las baterías por lo menos 24 horas antes de usarlas. No confíe en el el gabinete de baterías para
proporcionar energía de respaldo hasta que las baterías estén completamente cargadas.
Nota: Si el sistema UPS permanece apagado por un período prolongado, deberá encenderse periódicamente para permitir
recargar las baterías. Debe encenderse el UPS y recargarse las baterías por un período de al menos 24 horas ininterrumpidas
cada 3 meses. El no cargar las baterías periódicamente puede causar un daño irreversible a la batería.
8. Almacenamiento
Servicio
Su producto Tripp Lite está cubierto por la garantía descrita en este manual. También están disponibles una gran variedad
de Programas de Garantía Extendida y Servicio En Sitio por parte de Tripp Lite. Para más información sobre el servicio, visite
tripplite.com/support. Antes de devolver su producto para servicio, siga estos pasos:
1. Revise los procedimientos de instalación y operación en este manual para cerciorarse de que el problema de servicio no se
debe a una mala lectura de las instrucciones.
2. Si el problema persiste, no se ponga en contacto con el distribuidor ni le devuelva el producto. En su lugar, visite
tripplite.com/support.
3. Si el problema requiere de servicio, visite tripplite.com/support y haga click en el enlace Devolución de productos. Desde
aquí usted puede solicitar un número de Autorización de Devolución de Mercancía [RMA] que se requiere para el servicio.
Esta sencilla forma en línea solicitará los números de modelo y serie de su unidad junto con otra información general del
comprador. El número de RMA junto con las instrucciones de embarque le serán enviadas por correo electrónico. Cualquier
daño (directo, indirecto, especial o consecuencial) al producto incurrido durante el embarque a Tripp Lite o un Centro
de Servicio Autorizado de Tripp Lite no está cubierto bajo la garantía. Los productos embarcados a Tripp Lite o un Centro
de Servicio Autorizado de Tripp Lite deben tener los cargos del transporte prepagados. Marque el número de RMA en el
exterior del empaque. Si el producto está dentro del período de garantía, adjunte una copia de su recibo de venta. Regrese
el producto para servicio usando un transportista asegurado a la dirección que se le proporcionó cuando solicitó la RMA.
9. Servicio y Garantía
7. Especificaciones
136
MÁS DE
AÑOS
1111 W. 35th Street, Chicago, IL 60609 EE UU • tripplite.com/support
Garantía Limitada
El vendedor garantiza este producto, si se usa de acuerdo con todas las instrucciones aplicables, de que está libre de defectos en material y mano de
obra por un período de un (1) año a partir de la fecha de compra inicial. Si el producto resultara defectuoso en material o mano de obra dentro de ese
período, el vendedor reparará o reemplazará el producto a su entera discreción. El servicio cubierto por esta garantía incluye partes y mano de obra en
un centro de servicio de Tripp Lite. En Tripp Lite están disponibles planes de servicio en sitio a través de socios de servicio autorizados (en la mayoría de
las áreas). Para detalles, visite tripplite.com/support. Los clientes internacionales deben ponerse en contacto con el soporte de Tripp Lite en
ESTA GARANTÍA NO SE APLICA AL DESGASTE NORMAL O A LOS DAÑOS QUE RESULTEN DE ACCIDENTES, USO INCORRECTO, USO INDEBIDO O
NEGLIGENCIA. EL VENDEDOR NO OTORGA GARANTÍAS EXPRESAS DISTINTAS A LA ESTIPULADA EN EL PRESENTE. SALVO EN LA MEDIDA EN QUE LO
PROHÍBAN LAS LEYES APLICABLES, TODAS LAS GARANTÍAS IMPLÍCITAS, INCLUIDAS TODAS LAS GARANTÍAS DE COMERCIALIZACIÓN O IDONEIDAD,
ESTÁN LIMITADAS EN CUANTO A DURACIÓN AL PERÍODO DE GARANTÍA ESTABLECIDO; ASIMISMO, ESTA GARANTÍA EXCLUYE EXPRESAMENTE TODOS
LOS DAÑOS INCIDENTALES E INDIRECTOS. (Algunos estados no permiten limitaciones en cuanto dura una garantía y algunos estados no permiten la
exclusión de limitación de daños incidentales o indirectos, de modo que las limitaciones anteriores pueden no aplicar para usted. Esta Garantía le
otorga derechos legales específicos y es posible que usted goce de otros derechos que pueden variar de una jurisdicción a otra).
Tripp Lite; 1111 W. 35th Street; Chicago IL 60609; EE UU
ADVERTENCIA: antes de usarlo, cada usuario debe tener cuidado al determinar si este dispositivo es adecuado o seguro para el uso previsto. Ya que las
aplicaciones individuales están sujetas a gran variación, el fabricante no garantiza la adecuación de estos dispositivos para alguna aplicación específica.
Números de Identificación de Conformidad Regulatoria
Para el propósito de certificaciones e identificación de cumplimiento normativo, su producto Tripp Lite ha recibido un número de serie exclusivo. El
número de serie se puede encontrar en la etiqueta de placa de identificación, junto con todas las marcas e información requeridas de aprobación.
Al solicitar información de conformidad para este producto, refiérase siempre al número de serie. El número de serie no debe confundirse con el
nombre de la marca o el número de comercialización del producto.
Información de Cumplimiento con WEEE para Clientes y Recicladores de Tripp Lite (Unión Europea)
Conforme a la Directiva de Residuos de Equipos Eléctricos y Electrónicos [WEEE] y regulaciones aplicables, cuando los clientes adquieren un
equipo eléctrico y electrónico nuevo de Tripp Lite están obligados a:
• Enviar el equipo viejo para fines de reciclaje bajo la modalidad de uno por uno, semejante por semejante (esto varía de un país a otro)
• Enviar el equipo nuevo para reciclaje una vez que finalmente sea un desecho
Tripp Lite tiene una política de mejora continua. Las especificaciones están sujetas a cambio sin previo aviso. Las fotografías e ilustraciones pueden
diferir ligeramente de los productos reales.
20-11-074 93-3BF8_RevB
9. Servicio y Garantía
137
Manuel de l'utilisateur
Armoire de batteries pour un
fonctionnement prolongé
Modèles : BP240V65, BP240V65-NIB, BP240V65L, BP240V65L-NIB,
BP240V100, BP240V100-NIB, BP240V100L, BP240V100L-NIB
Ne convient pas aux applications mobiles.
1111 W. 35th Street, Chicago, IL 60609 USA • tripplite.com/support
Droits d'auteur © 2020 Tripp Lite. Tous droits réservés.
English 1 • Español 69
138
Table des matières
1. Introduction 139
1.1
Caractéristiques
139
1.2
Tableau de compatibilité de
140
l’onduleur et de l’armoire de batteries
2.
Consignes de sécurité importantes
141
2.1
Avertissements concernant l’installation
141
2.2
et l’emplacement
141
2.3
Avertissements concernant les connexions
142
2.4
Conformité aux normes
142
3.
Installation de l’armoire de batteries
143
3.1
Préparation
143
3.2
Transport
143
3.3
Vérification mécanique
143
3.4
Contenu de l’emballage
144
3.5
Câblage interne (typique)
145
3.6
Placement de l’armoire de batteries
145
3.7
Connexion électrique
145
3.8
Vérification électrique finale
145
4.
Données mécaniques
147
4.1 Mesures physiques 147
4.1.1
Dimensions pour BP240V65,
147
BP240V65-NIB, BP240V100,
BP240V100-NIB
4.1.2
Dimensions pour BP240V65L,
149
BP240V65L-NIB, BP240V100L,
BP240V100L-NIB
4.2
Exigences physiques
(tous les modèles)
151
5. Installation 152
5.1
Déballage et inspection
152
5.2
Sélection de la position d’installation
153
5.3
Câbles d’alimentation
154
5.3.1 Tailles des câbles
154
5.4
Connexions de l’armoire de batteries
154
Modèles BP240V65, BP240V65-NIB,
BP240V100, BP240V100-NIB
5.4.1
Retirer la coque du châssis
155
5.4.2
Installation des batteries et Connexion
155
5.4.2.1
Installation et configuration
159
des batteries : modèles
BP240V65-NIB,
BP240V100-NIB
5.5
Connexions de l’armoire de batteries
169
Modèles BP240V65L, BP240V65L-NIB,
BP240V100L, BP240V100L-NIB
5.5.1
Retirer la coque du châssis
169
5.5.2
Installation des batteries et Connexion
170
5.5.2.1
Installation et configuration
174
des batteries : modèles
BP240V65L-NIB,
BP240V100L-NIB
5.6
Connexions de plusieurs modules
185
de batteries
6.
Fonctionnement et configuration
189
des modèles d’onduleur S3M et
des armoires de batteries
6.1
Compatibilité des onduleurs S3M
189
avec les armoires de batteries de
BP240V65 à BP240V100L
6.2
Configuration des onduleurs de
10 à
190
20K pour des armoires de batteries
spécifiques en utilisant l’écran ACL
6.2.1
Écran d’accueil de l’onduleur S3M10-20K
190
6.2.2
Réglages
191
6.2.3
Réglage des batteries
192
6.2.4
Configuration de l’onduleur
193
S3M10-20K-NIB et optimisation du
chargement des armoires de batteries
BP240V65/V65L et BP240V100/V100L
6.3
Configuration des onduleurs de 25
196
à 100K pour des armoires de batteries
spécifiques en utilisant l’écan ACL
6.3.1
Écran d’accueil de l’onduleur S3M25-100K
196
6.3.2
Réglages
197
6.3.3
Configuration des batteries
199
6.3.4
Configuration de l’onduleur S3M25-
200
100K et l’optimisation du chargement
des armoires de batteries BP240V65/
V65L et BP240V100/V100L
6.4
Tabla de Referencia de Configuración
203
para Modelos de Sistemas UPS
S3M10-100K y Modelos de Gabinete
de Baterías BP240V09K-BP240V100L
7. Caractéristiques techniques 205
7.1
Caracteristiques techniques des
203
armoires de batteries
8. Entreposage 205
9. Service et garantie 206
139
1. Introduction
Les armoires de batteries pour fonctionnement prolongé de Tripp Lite se connectent aux onduleurs SmartOnline® pour fournir
une alimentation de secours de longue durée à partir des batteries pour les centres de données, les télécommunications,
les réseaux, les installations industrielles, la sécurité, les systèmes d'urgence et autres applications critiques qui exigent une
haute capacité, une haute disponibilité et un fonctionnement prolongé.
Les armoires de batteries sont offertes en sept modèles, avec ou sans batteries préinstallées : BP240V65, BP240V65-NIB,
BP240V65L, BP240V65L-NIB, BP240V100, BP240V100-NIB, BP240V100L-NIB.
Les modèles d'armoires de batteries avec le suffixe « -NIB » BP240V65-NIB, BP240V65L-NIB, BP240V100-NIB et
BP240V40L-NIB n'incluent pas de batteries préinstallées. Cependant, ils incluent tous les câbles de raccordement, les fusibles
et les disjoncteurs, offrant la flexibilité d'acheter des batteries séparément pour les armoires de batteries. Les armoires de
batteries BP240V65-NIB et BP240V65L-NIB sont conçues pour des batteries CSB GP12650i. Les armoires de batteries
BP240V100-NIB et BP240V100L-NIB sont conçues pour des batteries CSB GP121000.
1.1 Caractéristiques
• Les armoires de batteries sont conçues pour un ensemble de batteries avec un tension de ± 120 V CC et des batteries
avec une capacité de 65 Ah ou 100 Ah, @ C20 jusqu'à 1,67 VPC.
• Les armoires de batteries contiennent plusieurs batteries AGM de 12 V CC connectées en série pour atteindre des tensions
plus élevées.
• Chaque armoire de batteries contient plusieurs étagères pour atteindre les tensions d'ensemble de batteries requises :
o BP240V65/BP240V65-NIB : peut accueillir 20 x batteries AGM de 65 Ah
o BP240V100/BP240V100-NIB : peut accueillir 20 x batteries AGM de 100 Ah
o BP240V65L/BP240V65L-NIB : peut accueillir 40 x batteries AGM de 65 Ah
o BP240V100L/BP240V100L-NIB : peut accueillir 40 x batteries AGM de 100 Ah
• Une porte à charnières verrouillable facilite l'accès aux batteries pour l'entretien périodique.
• Un espace libre d'au moins 100 mm (4 po) est présent au-dessus des batteries individuelles pour permettre l'accès aux
bornes.
• L'armoire de batteries est fabriquée en acier épais pour une bonne durabilité.
• Le fini en poudre cuite offre une résistance à la corrosion.
• L'armoire de batteries est expédiée boulonnée à une palette avec une double couche de film de protection étirable et une
protection des coins et du dessus intégrée.
• Une ventilation appropriée et un refroidissement par convection des batteries individuelles sont fournis par de l'espace entre
les batteries. Les évents avant et arrière permettent la libre circulation de l'air chaud hors de l'armoire de batteries.
• Un disjoncteur à boîtier moulé est fourni pour une protection contre les surcharges.
• Les câbles de sortie de puissance fournis par l’utilisateur peuvent être introduits dans l’armoire de batterie par des entrées
défonçables intégrées au bas de l’armoire.
• Pour une meilleure sécurité, une densité de puissance supérieure et un entretien minimum, les systèmes d'armoire utilisent
des batteries recombinantes au plomb-acide à valves. L'électrolyte dans ces batteries est immobilisé dans un séparateur
composé d'un paillasson absorbant ou d'un produit gélifiant, éliminant les risques de déversement et les exigences en
matière d'entretien de l'électrolyte sous forme de liquide libre. Il n'est pas nécessaire d'ajouter de l'eau ou de mesurer une
gravité spécifique.
• Parce que les batteries sont des éléments recombinants qui utilisent un cycle de recombinaison d'oxygène, une quantité
minimale de gaz est émise pendant le chargement normal de maintien. Chaque élément contient une soupape individuelle
qui libère les produits du gaz des surcharges et prévient l'accumulation de pression dans l'élément.
140
1. Introduction
1.2 Tableau de compatibilité de l'onduleur et de l'armoire de batteries
Armoires avec
batteries internes BP240V65 BP240V65L BP240V100 BP240V100L
Armoires SANS
batteries internes BP240V65-NIB BP240V65L-NIB BP240V100-NIB BP240V100L-NIB
Onduleurs 10
kVA-20 kVA avec
batteries internes
• S3M10K1B,
S3M10K2B,
S3M10K3B
• S3M15K2B,
S3M15K3B
• S3M20K3B
Non Non Non Non
Onduleurs 10
kVA-20 kVA sans
batterie interne
• S3M10K-NIB
• S3M15K-NIB
• S3M20K-NIB
Oui Oui Oui Non
Armoires avec
batteries internes BP240V65 BP240V65L BP240V100 BP240V100L
Armoires SANS
batteries internes BP240V65-NIB BP240V65L-NIB BP240V100-NIB BP240V100L-NIB
Onduleurs de 25
kVA à 100 kVA
SANS batteries
internes
• S3M25K
• S3M30K
Oui Oui Oui Non
• S3M50K Oui Oui Oui Oui
• S3M60K Non Oui Oui Oui
• S3M80K
• S3M100K
Non Oui Non Oui
141
2. Consignes de sécurité importantes
CONSERVER CES INSTRUCTIONS.
Toutes les sections de ce manuel contiennent des instructions et des avertissements qui doivent être respectés lors
de l'installation et du fonctionnement de l'armoire de batteries décrite dans ce manuel. Lire attentivement TOUTES les
instructions avant de tenter de déplacer, d'installer ou de connecter l'armoire de batteries.
Le non-respect de ces avertissements peut avoir une incidence sur la garantie et causer des dommages graves à la
propriété ou des blessures.
DANGER! DANGER MORTEL, HAUTE TENSION!
Tout le câblage doit être effectué par un électricien qualifié en conformité avec les avertissements se trouvant
dans ce manuel, avec tous les codes de sécurité et de l'électricité applicables. Un câblage incorrect risque de
causer des dommages graves à la propriété ou des blessures.
2.1 Avertissements concernant l'installation et l'emplacement
Installer l'armoire de batteries dans un environnement intérieur contrôlé, à l'écart de l'humidité, des températures extrêmes, des
liquides et des gaz inflammables, des contaminants conducteurs, de la poussière et de la lumière directe du soleil.
Installer l'armoire de batteries dans un endroit au niveau, solidement construit.
L'armoire de batteries est extrêmement lourde. Faire preuve de prudence au moment de déplacer ou de soulever l'appareil.
Utiliser l'armoire de batteries à des températures intérieures entre 0 °C et 40 °C seulement. Pour de meilleurs résultats, maintenir une
température ambiante interne de 25 °C.
Laisser un espace adéquat autour de l'avant et l'arrière de l'armoire de batteries pour permettre une ventilation appropriée. Ne pas
bloquer, couvrir ou insérer des objets dans les ouvertures de ventilation externes de l'armoire de batteries.
Ne placer aucun objet sur l'armoire de batteries, en particulier des récipients contenant un liquide.
Ne pas essayer d'empiler l'armoire de batteries. Tenter d'empiler l'armoire de batteries pourrait causer des dommages permanents et
créer un potentiel de sévices graves à la personne.
Ne pas tenter de déballer ou de déplacer l'armoire de batteries sans aide. Utiliser de l'équipement de manutention approprié pouvant
supporter le poids et l'encombrement de l'armoire de batteries, comme un monte-charge, un transpalette et un chariot élévateur à
fourche. (Déplier complètement les fourches sous la charge. Écarter les fourches le plus possible sous la charge. Soulever l'armoire à
partir du bas seulement. Porter des chaussures de sécurité.)
Pour des situations d'urgence, installer un extincteur conçu pour les incendies d'équipement électrique alimenté (de classe C ou
l'équivalent exact, avec un agent d'extinction non conducteur) à proximité de l'armoire de batteries.
2.2 Avertissements concernant les connexions
L'armoire de batteries contient des hautes tensions dangereuses qui ont le potentiel de causer des blessures ou la mort par
électrocution.
L'armoire de batteries contient sa propre source d'énergie. Les bornes de sortie peuvent être sous tension même lorsque l'armoire de
batteries n'est pas connectée à un onduleur.
L'armoire de batteries doit être correctement mise à la terre conformément à toutes les réglementations sur le câblage électrique.
Il n'est pas recommandé d'utiliser cet équipement pour des appareils de survie où une défaillance de cet équipement peut, selon
toute vraisemblance, entraîner la défaillance de l’appareil de maintien de la vie ou nuire de façon majeure à sa sécurité ou à son
efficacité.
Désactiver toutes les sources d'alimentation d'entrée et de sortie avant d'installer les câbles ou de faire les connexions électriques.
Utiliser un câble flexible de longueur suffisante pour permettre l'entretien de l'armoire de batteries.
Utiliser des capuchons à ferrules pour couvrir l'extrémité des câbles et d'empêcher les extrémités effilochées de court-circuiter les
blocs de jonction. Utiliser du câblage coté VW-1, FT-1 ou supérieur. Utiliser des manchons de câble et des coquilles d'accouplement.
142
2. Consignes de sécurité importantes
Confirmer que tous les câbles sont marqués correctement en fonction de leurs fins, leur polarité et leur diamètre.
Respecter une polarité appropriée en observant les indications des bornes positive et négative sur l’appareil. Le non-respect d’une
bonne polarité pourrait endommager les batteries et créer un risque sérieux de dommages à la propriété et de blessures.
Le câblage et l'assemblage doivent être confiés uniquement à un électricien formé et qualifié. Consulter le manuel de
l'utilisateur de l'onduleur pour le dimensionnement des câbles.
2.3 Avertissements concernant les batteries
L'armoire de batteries nécessite un entretien de routine par du personnel d'entretien qualifié et compétent connaissant bien son
fonctionnement. Prendre toutes les précautions requises avant d'ouvrir l'armoire pour quelque raison que ce soit. Garder le personnel
non autorisé à l'écart des batteries.
L'armoire de batteries contient des batteries au plomb-acide à régulation par soupape (VRLA). Ne pas tenter d'ajouter de l'eau à ces
batteries ou d'effectuer un échantillonnage de la gravité spécifique de l'électrolyte.
Les batteries VRLA peuvent contenir un mélange explosif de gaz hydrogène. NE PAS FUMER à proximité des batteries. NE PAS
provoquer de flammes ou d'étincelles à proximité des batteries. Décharger l'électricité statique du corps avant de toucher les
batteries. NE PAS ouvrir ou endommager les batteries — les électrolytes dégagés sont dangereux pour la peau et les yeux et peuvent
être toxiques. NE PAS jeter de batteries dans le feu — elles risqueraient d'exploser.
Les batteries peuvent présenter un risque de décharge électrique et de brûlures par des courants de court-circuit élevés. La connexion
ou le remplacement des batteries ne devrait être effectué que par du personnel d'entretien qualifié tenant compte des mesures de
sécurité appropriées. Utiliser des outils ayant des poignées isolées. Enlever les montres, les bagues ou tout autre objet métallique.
Porter des gants et des bottes en caoutchouc. Ne pas créer de court-circuit ou de pont entre les bornes de la batterie avec un objet
quelconque. Ne pas déposer d'outils ou de pièces métalliques sur les batteries.
Remplacer les batteries avec des batteries équivalentes (de même type et de même numéro) disponibles chez Tripp Lite.
Les batteries sont recyclables. Se reporter aux codes locaux pour les exigences en ce qui a trait à l'élimination. Ne pas éliminer les
batteries sauf au moyen d'un canal approuvé conformément à toutes les réglementations locales, de l'État et nationales applicables.
Ne pas connecter ou déconnecter les batteries lorsque l'onduleur est alimenté par batteries ou lorsque l'appareil ne se trouve pas en
mode de dérivation. Débrancher la source de chargement avant de brancher ou débrancher les bornes des batteries.
Si la source de chargement demeure hors tension pendant une période prolongée, il est recommandé de la mettre périodiquement
sous tension pour permettre aux batteries de se recharger. La source de chargement doit être mise sous tension et les batteries
doivent être rechargées pendant une période ininterrompue d'au moins 24 heures tous les 3 mois. Si les batteries ne sont pas
rechargées périodiquement, cela risque de causer des dommages permanents aux batteries.
Permettre le chargement des batteries sans interruption pendant 24 heures suivant l'installation.
2.4 Conformité aux normes
UL 1778, CSA-C22.2 No. 107.3-14 (3e édition)
ISTA B (transport, vibration, inclinaison)
Remarque concernant l'étiquetage
Ces symboles peuvent figurer sur l'étiquette du produit :
V : tension CC
: Masse
+ : positif de la batterie
: négatif de la batterie
Consulter l'étiquette du produit pour les numéros de modèles, les valeurs nominales de tension et
autres informations importantes.
143
3. Installation de l'armoire de batteries
Lire la Section 2 – Consignes de sécurité
importantes avant l'installation
3.1 Préparation
Sur le site, se préparer à décharger l'armoire de batteries du camion de livraison et à la transporter vers l'emplacement d'installation
final. Prendre en considération le poids et les dimensions de l'emballage.
S'assurer que le plancher peut supporter la charge de l'armoire de batteries spécifique étant installée. L'armoire de batteries doit être
installée dans un endroit solidement construit dont le plancher est au niveau qui est capable de supporter le poids de l'armoire de
batteries et tout autre équipement qui sera installé à proximité.
Dessiner un schéma de câblage représentant les câbles connectés entre les blocs de jonction de sortie de l'armoire de batteries et
tout dispositif de déconnexion externe, boîte de connexion et/ou charge/redresseur.
S'il est prévu que l'armoire de batteries soit entreposée pendant une période prolongée avant ou après l'installation, suivre les
instructions de la section 9. Entreposage et entretien
3.2 Transport
1. Inspecter le ou les conteneurs d'expédition pour la présence de dommages visibles (ne pas retirer le film étirable autour de l'appareil
avant son transport vers l'emplacement d'installation final). Confirmer que le nom du modèle et les valeurs nominales correspondent
à l'appareil commandé. S'il est déterminé que l'appareil a été endommagé durant l'expédition ou si quelque chose semble manquer,
contacter Tripp Lite pour obtenir de l'aide. Ne pas tenter d'utiliser l'appareil s'il a été endommagé ou manipulé de façon inappropriée.
2. Ne pas tenter de déballer ou de déplacer l'armoire de batteries sans aide. Utiliser de l'équipement de manutention approprié pouvant
supporter le poids et l'encombrement de l'armoire de batteries, comme un monte-charge, un transpalette et un chariot élévateur à
fourche. (Déplier complètement les fourches sous la charge. Écarter les fourches le plus possible sous la charge. Soulever l'armoire à
partir du bas seulement. Porter des chaussures de sécurité.) Confirmer que les limites de charge pour le monte-charge, l'équipement
de manutention et les planchers le long de l'itinéraire de transport n'excèdent pas le poids combiné de l'armoire de batteries
emballée, de l'équipement de manutention et du personnel. Confirmer que l'appareil emballé passera à travers les portes le long de
l'itinéraire prévu.
3. L'armoire de batteries est retenue avec du film étirable pour la protéger pendant l'expédition et le déplacement à l'intérieur de
l'installation. Enlever le film étirable de l'armoire de batteries une fois que l'appareil se trouve dans son emplacement d'installation
final — et non pas avant.
3.3 Vérification mécanique
Pendant que le système de batteries de l'armoire assemblée se trouve toujours sur la palette d'expédition, inspecter tous les côtés à la
recherche d'impact ou de tout autre dommage.
1. Ouvrir la porte avant de l'armoire de batteries.
2. Confirmer qu'aucune pièce interne (batteries, bloc de jonction, disjoncteur et autres pièces) n'est endommagée.
3. Prendre en note le numéro de modèle individuel des batteries et le type de borne illustrés dans la section 7. Caractéristiques
techniques.
4. Utiliser des outils ayant des poignées isolées pour serrer toutes les connexions des bornes des batteries au couple recommandé
illustré dans le tableau de la section 5.3 Câbles d'alimentation.
5. Utiliser des outils ayant des poignées isolées pour serrer les câbles des bornes de sortie positives et négatives des batteries de la fin
au disjoncteur.
144
3. Installation de l'armoire de batteries
3.4 Contenu de l’emballage
Numéro
de pièce
Description
BP240
V65
BP240
V65L
BP240
V65-NIB
BP240
V65L-NIB
BP240
V100
BP240
V100L
BP240
V100-NIB
BP240
V100L-NIB
Manuel de
l'utilisateur
933BF8
Oui Oui Oui Oui Oui Oui Oui Oui
Câbles des
batteries
731891 Câbles des
batteries à
connecter
à S3M10-20K
UPS
2 2 2 2 2 Non 2 Non
Isolateurs
des
batteries
83084A/
83084B
Matériel de
protection
S.O. S.O. 4/5 8/8 S.O. S.O. S.O. S.O.
Côté
inférieur
de l'armoire
Jupes en
métal
1038F7A Couvrent la
partie inférieure
de l'armoire
2 S.O. 2 S.O. 2 S.O. 2 S.O.
Côté
inférieur
de l'armoire
Jupes en
métal
1038F8A Couvrent la
partie inférieure
de l'armoire
2 2 2 2 2 2 2 2
Côté
inférieur
de l'armoire
Jupes en
métal
1038F8A Couvrent la
partie inférieure
de l'armoire
S.O. 2 S.O. 2 S.O. 2 S.O. 2
Câbles des
batteries
pour les
modèles
«-NIB»
Plusieurs
N/P
Pour connecter
les ensembles
de batteries à
l'armoire
S.O. S.O. 10 16 S.O. S.O. 10 16
Barres de
raccordement
en cuivre
1038F3 Pour
l’interconneion
de batteries
adjacentes
S.O. S.O. 10 20 S.O. S.O. S.O. S.O.
Barres de
raccordement
en cuivre
1038F4 Pour
l’interconneion
de batteries
adjacentes
S.O. S.O. 3 8 S.O. S.O. S.O. S.O.
Barres de
raccordement
en cuivre
1038F5 Pour
l'interconneion
de batteries
adjacentes
S.O. S.O. S.O. S.O. S.O. S.O. 3 8
Barres de
raccordement
en cuivre
1038F6 Pour
l’interconneion
de batteries
adjacentes
S.O. S.O. S.O. S.O. S.O. S.O. 10 20
145
3. Installation de l'armoire de batteries
3.5 Câblage interne (typique)
Les armoires de batteries utilisent plusieurs batteries de 12 V CC connectées en série pour fournir une tension nominale CC de 240 V
CC (±120 V CC).
Le câblage interne est dimensionné pour des courants de charge spécifiques à l'application. Ne pas utiliser un câble de toute autre
taille que celui fourni dans l'armoire de batteries.
Chaque étagère de l'armoire de batteries inclut un schéma de câblage spécifique. Consulter la section 6. Installation pour des
détails sur l'installation des batteries.
Tous les disjoncteurs se trouvent dans la section intermédiaire de l'armoire de batteries.
Les polarités de toutes les connexions de la charge seront étiquetées « + » (positif de la batterie), « - » (négatif de la batterie) et « N »
(partie centrale de la batterie) pour des chaînes CC de ±120 V.
Toutes les armoires de batteries sont fournies avec un dispositif de protection contre les surcharges du circuit de dérivation et peuvent
être câblées directement à la charge ou à l'onduleur.
3.6 Placement de l'armoire de batteries
Placer l'armoire de batteries dans un endroit frais où l'air circule librement et à l'écart des sources de chaleur directes. La durée de vie
utile et le rendement d'une batterie peuvent être fortement touchées par une température élevée, réduits de 50 % pour chaque 8,25 °C
au-dessus de 25 °C.
1. Préparer la surface de l'endroit où l'armoire sera placée. La surface doit être propre, plane et capable de supporter l'armoire de
batteries et le reste de l'équipement installé à proximité. Consulter la section 8. Spécifications pour les charges au plancher.
2. Laisser un espace libre adéquat autour de l'avant et l'arrière de l'armoire de batteries pour la ventilation et l'entretien. La porte avant
doit être accessible pour permettre un accès facile aux batteries internes, aux fusibles internes et aux dispositifs de protection contre
les surcharges. Consulter la section 6.1 Déballage et inspection pour les dimensions et les mesures de l'armoire de batteries.
3. Si l'armoire est ancrée au sol, installer des boulons d'ancrage appropriés dans le trou de montage qui se trouve dans la partie
inférieure de l'armoire. Utiliser des rondelles pour créer une surface au niveau entre les zones de montage et les boulons d'ancrage.
4. En procédant avec soin, retirer les boulons retenant l'armoire de batteries à la palette d'expédition.
5. Les fourches du chariot élévateur à fourche doivent être écartées le plus possible dans l'ouverture de dégagement de l'armoire
et complètement insérées pour prévenir le renversement. Soulever l'armoire à partir du bas seulement. Prendre soin de ne pas
endommager le plancher en tôle de l'armoire avec les fourches.
6. Si l'armoire de batteries est fixée au sol, aligner soigneusement l'armoire de batteries et l'abaisser sur les boulons d'ancrage du sol,
puis la fixer en place.
7. Si l'armoire n'est pas fixée au sol, l'abaisser dans l'espace désigné, puis la mettre au niveau en utilisant les cales. La mise à niveau
ne nuit pas au rendement, mais permet d'aligner l'armoire de batteries avec le reste de l'équipement dans l'installation.
3.7 Connexion électrique
DANGER! DANGER MORTEL, HAUTE TENSION!
Tout le câblage doit être effectué par un électricien qualifié en conformité avec les avertissements se trouvant
dans ce manuel, avec tous les codes de sécurité et de l'électricité applicables. Un câblage incorrect risque de
causer des dommages graves à la propriété ou des blessures.
L'armoire de batteries est connectée à la charge au moyen d'un disjoncteur CC. Cela permet de déconnecter la batterie depuis la
charge et le chargeur pour l'entretien et/ou la réparation.
Les disjoncteurs à boîtier moulé CC sont homologués CE pour la protection du circuit de dérivation. Si un remplacement est requis,
utiliser des composants homologués CE avec la même tension et intensité nominale.
Le dimensionnement des câbles de connexion doit prendre en considération la chute de tension maximale permise de même que la
capacité continue en ampères des câbles et le taux de décharge anticipé en ampères de l'armoire de batteries individuelle. Une chute
de tension maximale de 1,5 V CC dans les câbles de connexion de la charge est recommandée. Consulter le manuel de l'utilisateur
de l'onduleur pour le dimensionnement des câbles recommandé.
146
3. Installation de l'armoire de batteries
Se référer à tous les codes locaux, nationaux et de l'État applicables pour le dimensionnement et les valeurs nominales appropriés
pour les câbles.
Les dispositifs de protection du circuit externe (fusibles ou disjoncteurs) doivent prendre en considération le taux de décharge de la
batterie, le câblage à protéger et le courant du court-circuit CC de la batterie.
Après avoir effectué les procédures d'installation de la section 5. Installation, effectuer ce qui suit :
1. Ouvrir la porte avant de l'armoire de batteries pour accéder aux composants internes. Utiliser un voltmètre numérique lorsque des
mesures de la tension doivent être prises.
2. Déterminer si la batterie a été mise à la masse par inadvertance en réinitialisant le disjoncteur en position « On » (marche) et en
mesurant la tension entre la patte de mise à la masse de l'armoire de batteries et le point de connexion de charge positive dans
l'armoire. Cette tension devrait mesurer 0 (zéro) V CC. Si la tension mesurée n'est pas zéro, déterminer la cause et apporter une
correction avant de continuer.
3. Remettre le disjoncteur interne en position « Off » (arrêt) comme mesure de précaution pendant la connexion des câbles de sortie.
Une telle mesure permet d'empêcher les dommages si les câbles sont accidentellement court-circuités.
4. Le dessus de l'armoire de batteries inclut des entrées défonçables pour l'entrée du câble de connexion de la charge. Défoncer
l'entrée défonçable appropriée, puis raccorder le conduit ou la bague du câble.
5. Le disjoncteur de sortie accueille des câbles jusqu'à 300 mm
2
.
6. Raccorder un câble de mise à la masse de l'équipement approprié à la patte de mise à la masse qui se trouve sur le dessus de
l'armoire de batteries.
7. Acheminer les câbles positif et négatif (et le centre « N », le cas échéant) de l'interrupteur général externe ouvert ou les bornes du
câblage de champ de la batterie de l'onduleur à travers la bague du conduit/câble. Raccorder les bornes de sorties respectives à
l'intérieur de l'armoire de batteries.
3.8 Vérification électrique finale
Avant de fermer un disjoncteur de connexion ou un interrupteur général, effectuer les étapes de vérification suivantes :
1. Vérifier que la tension de sortie de l'armoire de batteries est correcte.
2. Si les armoires de batteries fonctionnent en parallèle, vérifier que les tensions de sorties individuelles du système correspondent à
2 V CC.
3. Vérifier que la tension mesurée entre la borne de sortie et la masse de l'armoire de batterie est zéro.
4. Si l'une ou l'autre des vérifications ci-dessus révèle une irrégularité, déterminer et corriger la cause avant de continuer.
5. Remettre le disjoncteur à la position « On » (marche).
147
4. Données mécaniques
4.1 Mesures physiques
4.1.1 Dimensions pour BP240V65, BP240V65-NIB, BP240V100, BP240V100-NIB
800 mm
(31,5 po)
900 mm
(35,4 po)
1 200 mm
(47,2 po)
148
Vue arrière (bloc de jonction sans couvercle)
4
3
2
1
5
vue avant vue latérale vue arrière
4. Données mécaniques
1
Disjoncteur de batterie
2
Borne de batterie pour onduleur de 10 kVA à 20 kVA
3
Borne de batterie pour onduleur de 25 kVA à 60 kVA
4
Pattes de mise à la masse
5
Entrées défonçables du câble des batteries
149
4. Données mécaniques
4.1.2 Dimensions pour BP240V65L, BP240V65L-NIB, BP240V100L, BP240V100L-NIB
800 mm
(31,5 po)
1 100 mm
(43,4 po)
1 600 mm
(63 po)
Vue arrière (bloc de jonction sans couvercle)
150
Vue arrière (bloc de jonction sans couvercle)
4
3
2
1
5
4. Données mécaniques
vue avant vue latérale vue arrière
1
Disjoncteur de batterie
2
Borne de batterie pour
onduleur de 10 kVA à 20 kVA
3
Borne de batterie pour
onduleur de 25 kVA à 60 kVA
4
Pattes de mise à la masse
5
Entrées défonçables du
câble des batteries
151
4. Données mécaniques
4.2 Exigences physiques (tous les modèles)
Laisser de l'espace autour de l'armoire pour le fonctionnement et la ventilation.
1. Laisser au moins 800 mm (31,5 po) d'espace à l'avant pour la ventilation.
2. Laisser au moins 500 mm (20 po) d'espace à droite et à gauche pour le fonctionnement.
3. Laisser au moins 500 mm (20 po) d'espace à l'arrière pour la ventilation.
>
500 mm
(20 po)
>
500 mm
(20 po)
>
500 mm
(20 po)
>
500 mm
(20 po)
>
800 mm
(31,5 po)
152
5. Installation
Remarque : Avant l'installation, inspecter l'appareil. S'assurer que rien à l'intérieur de l'emballage n'est endommagé. Conserver le matériel d'emballage original
dans un lieu sûr pour utilisation future.
5.1 Déballage et inspection
Tout dommage à l'emballage doit être pris en note avec le transporteur chargé de la livraison au moment de la réception.
Retirer l'ensemble de rail, le boîtier des batteries et les modules de batteries de l'emballage.
Remarque : Les modules de batteries sont très lourds. Faire preuve de prudence au moment de déballer et de soulever l'appareil pour éviter les blessures.
Ne pas incliner le module de batteries en le retirant de l'emballage.
Inspecter l'armoire de batteries pour la présence de dommages qui auraient pu survenir pendant le transport. Si des
dommages sont présents, ne pas mettre l'appareil sous tension. Contacter immédiatement le fournisseur chez qui
l'appareil a été acheté.
Vérifier les accessoires par rapport au bordereau d'expédition, puis contacter le fournisseur si des pièces sont manquantes.
3. Retirer la mousse d'emballage et la palette biseautée. 4. Retirer les boulons retenant l'armoire à la
palette d'expédition.
1. Tenir fermement la plaque coulissante.
Couper, puis retirer les rubans de ligature.
2. Retirer le sac en plastique et la boîte d'expédition.
153
5. Installation
5. Utiliser un chariot élévateur pour soulever l'armoire de
batteries de la palette.
5.2 Sélection de la position d'installation
Sélectionner un environnement approprié où installer l'appareil afin de minimiser la possibilité de dommages au système de
batteries et maximiser la durée de vie des batteries.
1. Ne pas bloquer le débit d'air vers les ouvertures de ventilation de l'appareil.
2. S'assurer que les conditions environnementales du lieu d'installation sont conformes aux caractéristiques techniques de
l'appareil afin d'éviter la surchauffe et l'excès d'humidité. Consulter la section 4.2 Exigences physiques.
3. Ne pas placer l'appareil dans un environnement poussiéreux ou corrosif ou à proximité d'objets inflammables.
4. L'appareil n'est pas conçu pour être utilisé à l'extérieur.
Remarques :
Placer l'armoire de batteries dans un endroit propre et stable. Éviter les vibrations, la poussière, l'humidité, les gaz inflammables, les
liquides et les matières corrosives.
Pour aider à prévenir les températures élevées dans la pièce où l'onduleur est installé, il est recommandé d'utiliser des ventilateurs
d'évacuation et/ou des systèmes de refroidissement.
Les batteries doivent être montées dans un endroit où la température se situe à l'intérieur des spécifications requises. La température est
un facteur clé pour déterminer la durée de vie et la capacité des batteries. La température des batteries doit être maintenue entre 20 et
25 °C (59 et 77 °F). Garder les batteries à l'écart des sources de chaleur, des principales zones de ventilation d'air, etc.
AVERTISSEMENT!
Les données sur la performance typique des batteries indiquent une température de fonctionnement entre
20 et 25 °C (59 et 77 °F). L'utilisation de l'onduleur au-dessus de cette plage réduira la durée de vie des batteries,
tandis que l'utilisation de l'onduleur en deçà de cette plage réduira la capacité des batteries.
Si l'onduleur n'est pas installé immédiatement, il doit être entreposé dans une pièce exempte de chaleur ou d'humidité excessive.
154
5.3 Câbles d'alimentation
La conception des câbles doit être conforme aux tensions et aux courants fournis dans cette section et en conformité avec les
codes locaux de l'électricité.
AVERTISSEMENT!
S'ASSURER DE PRENDRE CONNAISSANCE DE L'EMPLACEMENT ET DU FONCTIONNEMENT DES ISOLATEURS
EXTERNES QUI SONT CONNECTÉS À LA SOURCE D'ENTRÉE/DE DÉRIVATION DE L'ONDULEUR DANS LE
PANNEAU DE DISTRIBUTION DU SECTEUR.
VÉRIFIER SI CES SOURCES SONT ISOLÉES ÉLECTRIQUEMENT, PUIS AFFICHER TOUT SIGNE
D'AVERTISSEMENT NÉCESSAIRE POUR PRÉVENIR TOUT FONCTIONNEMENT ACCIDENTEL.
5.3.1 Tailles des câbles
5.4 Connexions de l'armoire de
batteries : modèles BP240V65,
BP240V65-NIB, BP240V100 et
BP240V100-NIB
La conception de chaque armoire de batteries inclut des câbles
de connexion de batteries internes intégrés, de disjoncteur,
des fusibles et des bornes. L'armoire standard peut accueillir
20 batteries de 12V 65Ah 12V 100Ah. Le système de tension
CC pour toutes les armoires est 240 V CC avec des ensembles
de batteries internes de ±120 V.
Les Figures 5-1 et 5-2 illustrent la conception générale du
châssis et des vues éclatées pour les modèles BP240V65,
BP240V65-NIB, BP240V100 et BP240V100-NIB. Les vues
correspondantes pour les modèles BP240V65L, BP240V65L-
NIB, BP240V100L et BP240V100L-NIB sont illustrées dans
la section 5.5 Connexions de l'armoire de batteries :
modèles BP240V65L, BP240V65L-NIB, BP240V100L
et BP240V100L-NIB.
5. Installation
Modèle du
système ASC
BP240V65 / BP240V100
BP240V65-NIB / BP240V100-NIB
BP240V65L / BP240V100L*
BP240V65L-NIB / BP240V100L-NIB*
Recommandé
Couple
Tailles des câbles (câblage THHW à 75 °C)
Entrée CC Mise à la terre Entrée CC Mise à la terre
10kVA*
6 AWG 6 AWG 6 AWG 6 AWG Connecteur Anderson
(aucun paramètre
de couple)
0kgf.com / 0N m
15kVA*
2 x 6 AWG 2 x 6 AWG 2 x 6 AWG 2 x 6 AWG
20kVA*
2 x 6 AWG 2 x 6 AWG 2 x 6 AWG 2 x 6 AWG
25kVA*
1/0 AWG 2 AWG 1/0 AWG 2 AWG
450kgf.cm/
44N•m
30kVA*
1/0 AWG 1/0 AWG 1/0 AWG 1/0 AWG
50kVA
2/0 AWG 2/0 AWG 2/0 AWG 2/0 AWG
60kVA
2/0 AWG 2/0 AWG 2/0 AWG 2/0 AWG
80kVA
2/0 AWG*2 2/0 AWG*2
100kVA
2/0 AWG*2 2/0 AWG*2
* Les onduleurs S3M10-30K ne prennent pas en charge les modèles d’armoires de batteries BP240V100L/100L-NIB.
Figure 5-1 : Châssis d'armoire de batteries BP240V65,
BP240V65-NIB, BP240V100 et BP240V100-NIB
155
5. Installation
5.4.1 Retirer la coque du châssis
Mettre l'armoire de batteries en place. Retirer les panneaux supérieurs, avant, de gauche et de droite. Retirer la plaque du
couvercle de droite et de gauche du module de batteries, puis le clapet des batteries pour installer les batteries.
5.4.2 Installation et connexion des batteries
Chaque groupe de batteries consiste de 20 batteries en série (BAT+, N et BAT-). Placer les batteries dans l'armoire à partir du
bas en montant, une à la fois, puis raccorder les câbles de batterie conformément aux schémas qui suivent.
Remarque : La polarité positive et négative de la batterie ne peut pas être inversée ou court-circuitée. Cela endommagerait la batterie et/ou
causerait des blessures. Ne pas toucher aux bornes positive et négative de la batterie en même temps. Avant de remplacer ou de retirer les
batteries, déconnecter le disjoncteur, tirer sur les bornes des éléments, puis retirer les vis de la barre du bus de cuivre. Le non-respect de
ces instructions pourrait causer des dommages à l'équipement ou des blessures. L'installation doit consister de 40 batteries.
Figure 5-2 : Vue éclatée du châssis, modèles BP240V65, BP240V65-NIB, BP240V100, BP240V100-NIB
156
5. Installation
Figure 5-3A : Vue avant
Figure 5-3B : Vue arrière
Couche 3
Couche 2
Couche 1
Groupe positif,
10 pièces
Groupe négatif, 10
pièces
Fusibles
400 A (x2)
Disjoncteur
de batterie
Connecteur de
25 à 100 kVA
Connecteur de
10 à 20 kVA
157
Remarque: Ce manuel peut être
téléchargé en couleur en visitant
tripplite.com, le manuel affiche
les câbles dans les couleurs
correspondantes :
rouge = positif
bleu = prise centrale
noir = négatif
5. Installation
Figure 5-4 : Schéma de câblage pour le modèle BP240V65
L’arrière
L’arrière
L’arrière
Couche 3
Couche 2
Couche 1
L’avant
L’avant
L’avant
158
Remarque: Ce manuel peut être
téléchargé en couleur en visitant
tripplite.com, le manuel affiche
les câbles dans les couleurs
correspondantes :
rouge = positif
bleu = prise centrale
noir = négatif
5. Installation
Figure 5-5 : Schéma de câblage pour le modèle BP240V100
L’arrière
L’arrière
L’arrière
Couche 3
Couche 2
Couche 1
L’avant
L’avant
L’avant
159
5. Installation
Figure 5-6A
Figure 5-6B
5.4.2.1 Installation et configuration des batteries :
modèles BP240V65-NIB, BP240V100-NIB
1. Retirer toutes les vis étiquetées 1 (Figures 5-6A et 5-6B).
160
Figure 5-7
3. Retirer toutes les vis du support de rétention des batteries, puis retirer les supports de rétention (Figure 6-8).
2. Retirer les plaques du haut, de droite et de gauche (Figure 5-7).
5. Installation
Figure 5-8
161
5. Installation
Figure 5-9 : modèle BP240V65-NIB
Figure 5-10 : modèle BP240V100-NIB
4. Installer 8 modules de batteries dans la couche 1 (Figure 5-9 : modèle BP240V65-NIB ou Figure 5-10 : modèle
BP240V100-NIB).
162
Figure 5-11 : modèle BP240V65-NIB
5. Installer 6 modules de batteries dans la couche 2 (Figure 5-11 : modèle BP240V65-NIB ou Figure 5-12 : modèle
BP240V100-NIB).
5. Installation
Figure 5-12 : modèle BP240V100-NIB
163
5. Installation
Figure 5-13 : modèle BP240V65-NIB
Figure 5-14 : modèle BP240V100-NIB
6. Installer 6 modules de batteries dans la couche 3 (Figure 5-13 : modèle BP240V65-NIB ou Figure 5-14 : modèle
BP240V100-NIB).
164
Figure 5-15 : modèle BP240V65-NIB
7. Réinstaller tous les supports de rétention des batteries et toutes les vis (Figure 5-15 : modèle BP240V65-NIB ou
Figure 5-16 : modèle BP240V100-NIB).
5. Installation
Figure 5-16 : modèle BP240V100-NIB
165
5. Installation
Figure 5-17A
Figure 5-17B
8. Modèle BP240V65-NIB : Installer les barres du bus en cuivre (13 pièces) entre les batteries adjacentes et les boulons/
montants d’insertion des batteries
166
Figure 5-18A
9. Modèle BP240V100-NIB : Installer les barres du bus en cuivre (12 pièces) entre les batteries adjacentes et les boulons/
montants d’insertion des batteries (Figures 5-18A et 5-18B).
5. Installation
Figure 5-18B
167
5. Installation
Figure 5-19 : modèle BP240V65-NIB
Figure 5-20 : modèle BP240V100-NIB
10. Connecter les câbles de la batterie 1+ à la barre du bus de BAT+, de la batterie 10- à la barre du bus de BATN, de la
batterie 11+ à la barre du bus de BATN, de la batterie 20- à la barre du bus de BAT- et les câble de connexion de la
couche (Figure 5-19 : modèle BP240V65-NIB ou Figure 5-20 : modèle BP240V100-NIB et Figure 5-21).
Remarques :
• Utiliser les schémas de câblage en
guise de référence pour les
assemblages suivants :
Utiliser la Figure 5-4
pour BP240V65-NIB.
Utiliser la Figure 5-5
pour BP240V100-NIB.
Ce manuel peut être téléchargé
en couleur en visitant tripplite.com,
le manuel affiche les câbles dans
les couleurs correspondantes :
rouge = positif
bleu = prise centrale
noir = négatif
168
Figure 5-21
5. Installation
Figure 5-22
11. Réinstaller tous les couvercles et toutes les vis (Figure 5-22).
169
5. Installation
Figure 5-23 : châssis de batterie BP240V65L, BP240V65L-NIB,
BP240V100L et BP240V100L-NIB
Figure 5-24 : Vue éclatée – modèles BP240V65L, BP240V65L-NIB, BP240V100l, BP240V100L-NIB
5.5 Connexions de l'armoire de
batteries : modèles BP240V65L,
BP240V65L-NIB, BP240V100L et
BP240V100L-NIB
La conception de chaque armoire de batteries inclut des câbles de
connexion de batteries internes intégrés, de disjoncteur, des fusibles
et des bornes. L'armoire standard peut accueillir 20 batteries de 12
V 65 Ah (12 V/100 Ah). Les armoires de batteries de longue durée «
L » peuvent accueillir 40 batteries de 12 V 65 Ah (12 V 100 Ah). Le
système de tension CC pour toutes les armoires est 240 V CC avec
des ensembles de batteries internes de ±120 V.
Les Figures 5-23 et 5-24 illustrent la conception générale du
châssis et des vues éclatées pour les modèles BP240V65L,
BP240V65L-NIB, BP240V100L et BP240V100L-NIB. Les vues
correspondantes pour les modèles BP240V65, BP240V65-NIB,
BP240V100 et BP240V100-NIB sont illustrées dans la section
5.4 Connexions de l'armoire des batteries : modèles
BP240V65, BP240V65-NIB, BP240V100 et BP240V100-NIB.
5.5.1 Retirer lacoque du châssis
Placer la boîte de batteries à son
emplacement final. Retirer les panneaux
supérieurs, avant, de gauche et de droite.
Retirer les plaques du couvercle de droite
et de gauche du module de batteries, puis
les supports des batteries pour installer les
ensembles de batteries.
170
5. Installation
Figure 5-25A : Vue avant
5.5.2 Installation et connexion des batteries
Les 40 batteries peuvent être divisées en deux groupes connectés pour fonctionner en parallèle. Chaque groupe consiste de
20 batteries en série (BAT+, N et BAT-). Placer les batteries dans l'armoire à partir du bas en montant, une à la fois, puis
raccorder les câbles de batterie conformément aux schémas qui suivent.
Remarque : La polarité positive et négative de la batterie ne peut pas être inversée ou court-circuitée. Cela endommagerait la batterie et/ou
causerait des blessures. Ne pas toucher aux bornes positive et négative de la batterie en même temps. Avant de remplacer ou de retirer les
batteries, déconnecter le disjoncteur, tirer sur les bornes des éléments, puis retirer les vis de la barre du bus de cuivre. Le non-respect de
ces instructions pourrait causer des dommages à l'équipement ou des blessures. L'installation doit consister de 40 batteries.
Couche 3
Couche 4
Couche 2
Couche 1
Groupe de
batteries 2
Groupe de
batteries 1
171
Figure 5-25B : Vue arrière
5. Installation
Fusibles
400 A (x2)
Disjoncteur de
batterie
Connecteur de
25 à 100 kVA
Connecteur de
10 à 20 kVA
172
Remarque : Ce manuel peut
être téléchargé en couleur en
visitant tripplite.com, le manuel
affiche les câbles dans les couleurs
correspondantes :
rouge = positif
bleu = prise centrale
noir = négatif
6. Installation
Figure 5-26 : Schéma de câblage pour BP240V65L (40 batteries installées)
Couche
2
Couche
4
Couche
1
Couche
3
L’arrière
L’avant
L’arrière
L’avant
L’arrière
L’avant
L’arrière
L’avant
173
Remarque : Ce manuel peut
être téléchargé en couleur en
visitant tripplite.com, le manuel
affiche les câbles dans les couleurs
correspondantes :
rouge = positif
bleu = prise centrale
noir = négatif
5. Installation
Figure 5-27 : Schéma de câblage pour BP240V100L (40 batteries installées)
Une fois l'installation et la connexion des batteries terminées, utiliser un multimètre ou un autre instrument pour vérifier si les
tensions entre BAT+ et N, N et BAT- sont normales. Si les tensions sont normales, verrouiller le couvercle du châssis.
Couche
2
Couche
4
Couche
1
Couche
3
L’arrière
L’avant
L’arrière
L’avant
L’arrière
L’avant
L’arrière
L’avant
174
5. Installation
Figure 5-28A
Figure 5-28B
5.5.2.1 Installation et configuration des batteries :
modèles BP240V65L-NIB, BP240V100L-NIB
1. Retirer toutes les vis étiquetées 1 (Figures 5-28A et 5-28B).
175
Figure 5-29
3. Retirer toutes les vis du support de rétention des batteries, puis retirer les supports de rétention (Figure 5-30).
2. Retirer les plaques du haut, de droite et de gauche (Figure 5-29).
5. Installation
Figure 5-30
176
5. Installation
Figure 5-31 : modèle BP240V65L-NIB
Figure 5-32 : modèle BP240V100L-NIB
4. Installer 10 modules de batteries dans la couche 1 (Figure 5-31 : modèle BP240V65L-NIB ou Figure 5-32 : modèle
BP240V100L-NIB).
177
5. Installation
Figure 5-33 : modèle BP240V65L-NIB
5. Installer 10 modules de batteries dans la couche 2 (Figure 5-33 : modèle BP240V65L-NIB ou Figure 5-34 : modèle
BP240V100L-NIB).
Figure 5-34 : modèle BP240V100L-NIB
178
5. Installation
Figure 5-35 : modèle BP240V65L-NIB
Figure 5-36 : modèle BP240V100L-NIB
6. Installer 10 modules de batteries dans la couche 3 (Figure 5-35 : modèle BP240V65L-NIB ou Figure 5-36 : modèle
BP240V100L-NIB).
179
Figure 5-37 : modèle BP240V65L-NIB
7. Installer 10 modules de batteries dans la couche 4 (Figure 5-37 : modèle BP240V65L-NIB ou Figure 5-38 : modèle
BP240V100L-NIB).
5. Installation
Figure 5-38 : modèle BP240V100L-NIB
180
5. Installation
Figure 5-39
Figure 5-40A
8. Réinstaller tous les supports de rétention et les vis des batteries (Figure 5-39).
9. Modèle BP240V65L-NIB : Installer les barres du bus en cuivre (13 pièces) entre les batteries adjacentes et les boulons/
montants d’insertion des batteries (Figures 5-40A et 5-40B).
181
Figure 5-40B
5. Installation
Figure 5-41A
10. Modèle BP240V100L-NIB : Installer les barres du bus en cuivre (12 pièces) entre les batteries adjacentes et les boulons/
montants d’insertion des batteries (Figures 5-41A et 5-41B).
182
5. Installation
Figure 5-41B
Figure 5-42 : modèle BP240V65L-NIB
11. Connecter les câbles de la batterie 1+ du groupe de batteries 1 à la barre du bus de BAT+, de la batterie 10- à la barre du bus
de BATN, de la batterie 11+ à la barre du bus de BATN, de la batterie 20- à la barre du bus de BAT- et les câbles de connexion
de la couche. Connecter la batterie 21+ du groupe de batteries 2 à la barre du bus de BAT+, de la batterie 30- à la barre
du bus de BATN, de la batterie 31+ à la barre du bus de BATN, de la batterie 40- à la barre du bus de BAT- et les câbles de
connexion de la couche (Figure 5-42 : modèle BP240V65L-NIB ou Figure 5-43 : modèle BP240V100L et Figure 5-44).
Remarques :
• Utiliser les schémas de câblage
en guise de référence pour les
assemblages suivants :
Utiliser la Figure 5-26 pour
BP240V65L-NIB.
Utiliser la Figure 5-27 pour
BP240V100L-NIB.
• Ce manuel peut être téléchargé
en couleur en visitant tripplite.com,
le manuel affiche les câbles dans
les couleurs correspondantes :
rouge = positif
bleu = prise centrale
noir = négatif
183
Figure 5-43 : modèle BP240V100L-NIB
Figure 5-44
5. Installation
Figure 5-42 : modèle BP240V65L-NIB
184
Figure 5-45
12. Réinstaller tous les couvercles et toutes les vis (Figure 5-45).
5. Installation
185
5. Installation
5.6 Connexions de plusieurs modules de batteries
DANGER!
S'assurer que la polarité de la connexion en série de l'ensemble de batteries est correcte. NE PAS combiner des
batteries de différentes capacités de différentes marques ou des batteries vieilles et neuves.
AVERTISSEMENT!
S'ASSURER QUE LA POLARITÉ DES CONNEXIONS D'EXTRÉMITÉ DES ENSEMBLES VERS LE DISJONCTEUR DES
BATTERIES ET DU DISJONCTEUR DES BATTERIES VERS LES BORNES DE L'ONDULEUR EST CORRECTE, C.-À-D. (+)
À (+)/(-) À (-)/(N) À (N). DÉCONNECTER UN OU PLUSIEURS LIENS DES ÉLÉMENTS DE BATTERIES DANS CHAQUE
NIVEAU. NE PAS RECONNECTER CES LIENS ET NE PAS FERMER LE DISJONCTEUR DES BATTERIES À MOINS QUE
TOUTES LES CONNEXIONS AIENT ÉTÉ CORRECTEMENT VÉRIFIÉES ET APPROUVÉES.
onduleur armoire de batteries
Figure 6-46 : Connexion de BP240V65L et BP240V65L-NIB pour un onduleur de 10 kVA, 15 kVA et 20 kVA
186
5. Installation
onduleur armoire de batteries
Figure 6-47 : Connexion de BP240V65L et BP240V65L-NIB pour un onduleur de 25 kVA et 30 kVA
187
5. Installation
onduleur armoire de batteries
Figure 5-48 : Connexion de BP240V65L, BP240V65L-NIB, BP240V100L
ou BP240V100L-NIB pour des onduleurs de 50 kVA et 60 kVA
188
5. Installation
onduleur armoire de batteries
Figure 5-49 : Connexion de BP240V65L, BP240V65L-NIB, BP240V100L
ou BP240V100L-NIB pour un onduleur de 80 kVA et 100 kVA
189
6. Fonctionnement et configuration des modèles d’onduleur
S3M et des armoires de batteries
6.1 Compatibilité des onduleurs S3M avec les armoires
de batteries de BP240V65 à BP240V100L
Armoires avec
batteries internes BP240V65 BP240V65L BP240V100 BP240V100L
Armoires SANS
batteries internes BP240V65-NIB BP240V65L-NIB BP240V100-NIB BP240V100L-NIB
Onduleurs 10
kVA-20 kVA avec
batteries internes
• S3M10K1B,
S3M10K2B,
S3M10K3B
• S3M15K2B,
S3M15K3B
• S3M20K3B
Non Non Non Non
Onduleurs 10
kVA-20 kVA sans
batterie interne
• S3M10K-NIB
• S3M15K-NIB
• S3M20K-NIB
Oui Oui Oui Non
Armoires avec
batteries internes BP240V65 BP240V65L BP240V100 BP240V100L
Armoires SANS
batteries internes BP240V65-NIB BP240V65L-NIB BP240V100-NIB BP240V100L-NIB
Onduleurs de 25
kVA à 100 kVA
SANS batteries
internes
• S3M25K
• S3M30K
Oui Oui Oui Non
• S3M50K Oui Oui Oui Oui
• S3M60K Non Oui Oui Oui
• S3M80K
• S3M100K
Non Oui Non Oui
190
6.2 Configuration des onduleurs de 10 à 20K pour des armoires de
batteries spécifiques en utilisant l’écran ACL
6.2.1 Écran d’accueil de l’onduleur S3M10-20K
6. Fonctionnement et configuration des modèles d’onduleur
S3M et des armoires de batteries
Danger!
Les réglages pour la plupart des paramètres ne peuvent pas être c
hangés lorsque l’onduleur se trouve en mode inverseur.
191
6.2.2 Réglages
Cliquer sur l’icône Settings (réglages) pour saisir deux niveaux de réglage. Le Basic Setting (réglage de base) est pour les
réglages par l’utilisateur et le Advanced Setting (réglages avancés) est pour le personnel technique uniquement. Contacter
l’administrateur pour accéder aux réglages avancés.
Réglages avancés : cliquer sur Advanced Setting (réglages avancés), puis saisir le bon mot de passe. Le mot de passe
de l’utilisateur est « 191210 ».
6. Fonctionnement et configuration des modèles d’onduleur
S3M et des armoires de batteries
192
6.2.3 Réglage des batteries
Cliquer sur Battery Setup (configuration des batteries)
6. Fonctionnement et configuration des modèles d’onduleur
S3M et des armoires de batteries
193
6.2.4 Configuration de l’onduleur S3M10-20K-NIB et optimisation
du chargement des armoires de batteries BP240V65/V65L
et BP240V100/V100L.
Étape 1 : Réglage du groupe de batteries
Le groupe de batteries doit être configuré à quantité 1 pour chaque ensemble de 20 batteries qui se trouve dans le modèle
de l’onduleur et/ou qui y est connecté. Par exemple, le modèle d’onduleur S3M20K-NIB n’a aucune batterie interne et est
configuré à Battery Group 1 (groupe de batteries 1) par défaut pour tous les modèles d’onduleur. Toutefois, pour connecter
une armoire BP240V65 avec 20 batteries internes au S3M20K-NIB, l’onduleur S3M20K-NIB doit rester configuré à Battery
Group 1 (un ensemble de 20 batteries). Toutefois, pour connecter une seconde armoire BP240V65 à l’onduleur S3M20K-NIB
UPS, le groupe de batteries de l’onduleur doit être configuré à 2 (deux ensembles de 20 batteries). Obtenir le numéro pour le
Battery Group (groupe de batteries) en fonction de la combinaison particulière du modèle de l’onduleur S3M et du modèle
de l’armoire de batteries depuis le tableau dans la Section 6.4.
La valeur peut être 1 à 8. La valeur par défaut est 1 pour les modèles d’onduleur S3M sans batteries internes.
Étape 2 : Réglage du nombre de batteries
Le nombre de batteries doit rester à 20 pour tous les modèles d’onduleur S3M10-100K lorsqu’ils sont connectés à des
armoires de batteries externes Tripp Lite conçues pour les onduleurs de la série S3M.
Étape 3 : Réglage de la capacité d’une seule batterie (Ah)
Changer la capacité d’une seule batterie (Ah) pour la capacité individuelle Ah pour une batterie individuelle comme suit pour
les modèles d’armoires de batteries spécifiques :
• BP240V09/BP240V09K : la capacité d’une seule batterie (Ah) est 9
• BP240V40/BP240V40L : la capacité d’une seule batterie (Ah) est 40
• BP240V65/BP240V65L : la capacité d’une seule batterie (Ah) est 65
• BP240V100/BP240100L : la capacité d’une seule batterie (Ah) est 100 Les valeurs peuvent varier entre 7 et 2 000.
Faire défiler jusqu’à l’écran suivant en appuyant sur la flèche pointant vers le bas.
6. Fonctionnement et configuration des modèles d’onduleur
S3M et des armoires de batteries
194
Étape 4 : Réglage du courant de charge maximum
Le courant de charge maximum est le courant de charge estimé que l’onduleur utilisera pour charger les batteries. Configurer
le courant de charge maximum estimé recommandé en fonction de la combinaison particulière du modèle d’onduleur S3M et
du modèle d’armoire de batteries depuis le tableau dans la Section 6.4.
Tension de maintien et tension d’amplification : l’onduleur est configuré en usine pour les tensions de maintien (2,27 V/
élément, 13,62 V/batterie) et d’amplification (2,35 V/élément, 14,1 V/batterie) appropriées.
Tension d’augmentation des éléments : la valeur de la tension d’entretien peut se situer entre 2,23 et 2,30 V/élément. La
valeur par défaut est 2,27 V/élément.
Cell boost voltage: la valeur de la tension uniformisée des batteries peut se situer entre 2,30 et 2,40 V/élément. La valeur
par défaut est 2,35 V/élément.
Étape 5 : Réglage de la durée moyenne de chargement (min.)
Le réglage de la durée moyenne de chargement en minutes est une estimation de la durée de la charge d’augmentation
pour charger les batteries neuves à une capacité de 90 % à 25 °C. Configurer la durée moyenne (Aver) de chargement (min.)
recommandée en fonction de la combinaison particulière du modèle de l’onduleur S3M et du modèle de l’armoire de batteries
depuis le tableau dans la Section 6.4. Il convient de noter que les durées de charge d’augmentation recommandées ne sont
que des estimations basées sur des batteries neuves. Ces valeurs peuvent changer avec l’âge des batteries et la température
ambiante. Pour changer la durée moyenne de chargement, appuyer directement sur la valeur 240 par défaut à l’écran.
La durée moyenne (Aver) de chargement est la limite de temps de charge d’augmentation des batteries. La valeur peut se
situer entre 1 et 999 min. La valeur par défaut est 240 (4 heures).
6. Fonctionnement et configuration des modèles d’onduleur
S3M et des armoires de batteries
195
EOD Battery Volt : la tension de fin de décharge est le seuil de sectionnement bas de la tension des batteries pendant un
fonctionnement en mode batterie. La valeur peut se situer entre 1,60 et 1,90. La valeur par défaut est 1,67 V/élément ou
10,02 V CC par batterie.
Float Temp Compen Coeff : permet de modifier la tension de compensation après l’activation du commutateur. La valeur
peut varier entre 0,001 et 0,007 V/élément/°C. La valeur par défaut est 0,003 V/élément/°C.
Boost Charge Setting : la charge d’augmentation peut être configurée à Disable (désactivé) ou Enable (activé). La valeur par
défaut est Enable (activé).
No Battery Warning : garder cette alarme activée pour que l’onduleur émette un avertissement lorsqu’aucune batterie n’est
présente. La valeur par défaut est Alarm (alarme).
6. Fonctionnement et configuration des modèles d’onduleur
S3M et des armoires de batteries
196
6.3 Configuration des onduleurs de 25 à 100K pour des armoires
de batteries spécifiques en utilisant l’écan ACL
6.3.1 Écran d’accueil de l’onduleur S3M25-100K
6. Fonctionnement et configuration des modèles d’onduleur
S3M et des armoires de batteries
DANGER!
Les réglages pour la plupart des paramètres ne peuvent pas être
changés lorsque l’onduleur se trouve en mode inverseur.
197
6.3.2 Réglages
Cliquer sur l’icône Setting (réglage) pour saisir deux niveaux de réglage. Le Basic Setting (réglage de base) est pour les
réglages par l’utilisateur et le Advanced Setting (réglages avancés) est pour le personnel technique uniquement. Contacter
l’administrateur pour accéder aux réglages avancés.
Réglages avancés : cliquer sur Advanced Setting (réglages avancés), puis saisir le bon mot de passe. Le mot de passe de
l’utilisateur est « 191210 ».
6. Fonctionnement et configuration des modèles d’onduleur
S3M et des armoires de batteries
198
6. Fonctionnement et configuration des modèles d’onduleur
S3M et des armoires de batteries
199
6.3.3 Configuration des batteries
Cliquer sur BATT Setup
Float Temp. Compen. : le réglage de la compensation de la sonde de température peut être changé à Enable (activé)
lorsqu’une sonde de température des batteries est connectée au port arrière RJ45 de l’onduleur.
Temp Sensor Select : permet de configurer le type de sonde de température à NTC pour les distances simples et courtes.
Configurer le type de sonde de température à RS485 pour les distances multiples et grandes.
6. Fonctionnement et configuration des modèles d’onduleur
S3M et des armoires de batteries
200
6.3.4 Configuration de l’onduleur S3M25-100K et l’optimisation
du chargement des armoires de batteries BP240V65/V65L
et BP240V100/V100L
Étape 1 : Réglage du groupe de batteries
Le groupe de batteries doit être configuré à quantité 1 pour chaque ensemble de 20 batteries qui se trouve dans le modèle de
l’onduleur et/ou qui y est connecté. Par exemple, le modèle d’onduleur S3M100K n’a aucune batterie interne et est configuré
à Battery Group 1 (groupe de batteries 1) par défaut. Toutefois, pour connecter une armoire BP240V100L avec 40 batteries
internes au S3M100K, l’onduleur S3M100K doit être configuré à Battery Group 2 (groupe de batteries 2) Pour connecter une
seconde armoire BP240V100L à l’onduleur S3M100K, le Battery Group (groupe de batteries) doit être configuré à 4 (quatre
ensembles de 20 batteries). Obtenir le numéro pour le Battery Group (groupe de batteries) en fonction de la combinaison
particulière du modèle de l’onduleur S3M et du modèle de l’armoire de batteries depuis le tableau dans la Section 6.4.
La valeur peut être 1 à 8. La valeur par défaut est pour les modèles d’onduleur S3M sans batteries internes.
Étape 2 : Réglage du nombre de batteries
Le nombre de batteries doit rester à 20 pour tous les modèles d’onduleur S3M10-100K lorsqu’ils sont connectés à des
armoires de batteries externes Tripp Lite conçues pour les onduleurs de la série S3M.
Étape 3 : Réglage de la capacité d’une seule batterie (Ah)
Changer la capacité d’une seule batterie (Ah) pour la capacité individuelle Ah pour une batterie individuelle comme suit pour
les modèles d’armoires de batteries spécifiques :
• BP240V40/BP240V40L : la capacité d’une seule batterie (Ah) est 40
• BP240V65/BP240V65L : la capacité d’une seule batterie (Ah) est 65
• BP240V100/BP240V100L : la capacité d’une seule batterie (Ah) est 100
Les valeurs pour une batterie simple (Ah) peuvent varier entre 7 et 2 000.
Faire défiler jusqu’à l’écran suivant en appuyant sur la flèche pointant vers le bas.
6. Fonctionnement et configuration des modèles d’onduleur
S3M et des armoires de batteries
201
Étape 4 : Configurer le coefficient de limite du courant de chargement (C)
La limite de l’intensité de charge est un multiple de la capacité des batteries. Elle est utilisée pour configurer la limite de
temps de charge d’augmentation des batteries. La valeur peut se situer entre 0,05 et 0,25, et est configurée à 0,25 par
défaut. Configurer le coefficient (C) de limite de courant (cur) de chargement en fonction de la combinaison particulière
du modèle de l’onduleur S3M et du modèle d’armoire de batteries depuis le tableau dans la Section 6.4.
Tension de maintien et tension d’amplification : l’onduleur est configuré en usine pour les tensions de maintien
(2,27 V/élément, 13,62 V/batterie) et d’amplification (2,35 V/élément, 14,1 V/batterie) appropriées.
Tension d’entretien des éléments : la valeur de la tension d’entretien peut se situer entre 2,23 et 2,30 V/élément. La
valeur par défaut est 2,27 V/élément.
Tension d’augmentation des éléments : la valeur de la tension uniformisée des batteries peut se situer entre 2,30 et
2,40 V/élément. La valeur par défaut est 2,35 V/élément.
Étape 5 : Réglage de la durée moyenne de chargement (min.)
Le réglage de la durée moyenne de chargement en minutes est une estimation de la durée de la charge d’augmentation
pour charger les batteries neuves à une capacité de 90 % à 25 °C. Configurer la durée moyenne (Aver) de chargement (min.)
recommandée en fonction de la combinaison particulière du modèle de l’onduleur S3M et du modèle de l’armoire de batteries
depuis le tableau dans la Section 6.4. Il convient de noter que les durées de charge d’augmentation recommandées ne sont
que des estimations basées sur des batteries neuves. Ces valeurs peuvent changer avec l’âge des batteries et la température
ambiante. Pour changer la durée moyenne de chargement, appuyer directement sur la valeur 240 par défaut à l’écran.
La durée moyenne (Aver) de chargement est la limite de temps de charge d’augmentation des batteries. La valeur peut se
situer entre 1 et 999 min. La valeur par défaut est 240 (4 heures).
6. Fonctionnement et configuration des modèles d’onduleur
S3M et des armoires de batteries
202
EOD Battery Volt : la tension de fin de décharge est le seuil de sectionnement bas de la tension des batteries pendant un
fonctionnement en mode batterie. La valeur peut se situer entre 1,60 et 1,90. La valeur par défaut est 1,67 V/élément ou
10,02 V CC par batterie.
Float Temp Compen Coeff : permet de modifier la tension de compensation après l’activation du commutateur. La valeur
peut varier entre 0,001 et 0,007 V/élément/°C. La valeur par défaut est 0,003 V/élément/°C.
Boost Charge Setting : la charge d’augmentation peut être configurée à Disable (désactivé) ou Enable (activé). La valeur par
défaut est Enable (activé).
No Battery Warning : garder cette alarme activée pour que l’onduleur émette un avertissement lorsqu’aucune batterie n’est
présente. La valeur par défaut est Enable (activé).
6. Fonctionnement et configuration des modèles d’onduleur
S3M et des armoires de batteries
203
6. Fonctionnement et configuration des modèles d’onduleur
S3M et des armoires de batteries
6.4 Tableau de référence pour la configuration des modèles
d’onduleur S3M10-100K UPS et des modèles d’armoires
de batteries BP240V09-BP240V100L
Configurations pour les onduleurs S3M10K-NIB, S3M15K-NIB, S3M20K-NIB
sans aucune batterie interne
Modules
de batteries
Batteries Nombre de
Armoires
de batteries
Étape 1 Étape 2 Étape 3 Étape 4 Étape 5
Groupe de
batteries
Nombre
de
batteries
Capacité d'une
seule batterie
Courant de
charge max. (A)
Durée moyenne de chargement
(
min) Temps (minutes) pour charger
les batteries à 90 % à 25 °C
BP240V65 20 x 65Ah 1 1 20 65 9.75 500
BP240V65 20 x 65Ah 2 2 20 65 19.5 500
BP240V65 20 x 65Ah 3 3 20 65 20 720
BP240V65L 40 x 65Ah 1 2 20 65 19.5 500
BP240V65L 40 x 65Ah 2 4 20 65 20 960
BP240V100
20 x 100Ah
1 1 20 100 15 500
Configurations pour S3M25K et S3M30K
Modules
de batteries
Batteries Nombre de
Armoires
de batteries
Étape 1 Étape 2 Étape 3 Étape 4 Étape 5
Groupe de
batteries
Nombre
de
batteries
Capacité d'une
seule batterie
Coefficient de
limite du courant
de chargement (C)
Durée moyenne de chargement
(min) Temps (minutes) pour charger
les batteries à 90 % à 25 °C
BP240V65 20x 65Ah 1 1 20 65 0.15 540
BP240V65 20 x 65Ah 2 2 20 65 0.15 540
BP240V65 20 x 65Ah 3 3 20 65 0.1 900
BP240V65L 40 x 65Ah 1 2 20 65 0.15 540
BP240V65L 40 x 65Ah 2 4 20 65 0.07 999
BP240V100 20 x 100Ah 1 1 20 100 0.15 540
Configurations pour S3M50K et S3M60K
Modules
de batteries
Batteries Nombre de
Armoires
de batteries
Étape 1 Étape 2 Étape 3 Étape 4 Étape 5
Groupe de
batteries
Nombre
de
batteries
Capacité d'une
seule batterie
Coefficient de
limite du courant
de chargement (C)
Durée moyenne de chargement
(min) Temps (minutes) pour charger
les batteries à 90 % à 25 °C
BP240V65 20 x 65Ah 1 1 20 65 0.15 540
BP240V65 20 x 65Ah 2 2 20 65 0.15 540
BP240V65 20 x 65Ah 3 3 20 65 0.15 540
BP240V65L 40 x 65Ah 1 2 20 65 0.15 540
BP240V65L 40 x 65Ah 2 4 20 65 0.15 540
BP240V65L 40 x 65Ah 3 6 20 65 0.1 840
BP240V100 20 x 100Ah 1 1 20 100 0.15 540
BP240V100 20 x 100Ah 2 2 20 100 0.15 540
BP240V100 20 x 100Ah 3 3 20 100 0.13 540
BP240V100L
40 x 100Ah 1 2 20 100 0.15 540
BP240V100L
40 x 100Ah 2 4 20 100 0.1 840
204
6. Fonctionnement et configuration des modèles d’onduleur
S3M et des armoires de batteries
Configurations pour S3M80K
Modules
de batteries
Batteries Nombre de
Armoires de
batteries
Étape 1 Étape 2 Étape 3 Étape 4 Étape 5
Groupe de
batteries
Nombre
de
batteries
Capacité
d'une seule
batterie
Coefficient de
limite du courant
de chargement (C)
Durée moyenne de
chargement (min) Temps
(minutes) pour charger les
batteries à 90 % à 25 °C
BP240V65 20 x 65 Ah 1 1 20 65 0.15 540
BP240V65 20 x 65 Ah 2 2 20 65 0.15 540
BP240V65 20 x 65 Ah 3 3 20 65 0.15 540
BP240V65L 40 x 65 Ah 1 2 20 65 0.15 540
BP240V65L 40 x 65 Ah 2 4 20 65 0.15 540
BP240V65L 40 x 65 Ah 3 6 20 65 0.15 540
BP240V100 20 x 100 Ah 1 1 20 100 0.15 540
BP240V100 20 x 100 Ah 2 2 20 100 0.15 540
BP240V100 20 x 100 Ah 3 3 20 100 0.15 540
BP240V100L 40 x 100 Ah 1 2 20 100 0.15 540
BP240V100L 40 x 100 Ah 2 4 20 100 0.15 540
BP240V100L 40 x 100 Ah 3 6 20 100 0.1 840
Configurations pour S3M100K
Modules
de batteries
Batteries Nombre de
Armoires de
batteries
Étape 1 Étape 2 Étape 3 Étape 4 Étape 5
Groupe de
batteries
Nombre
de
batteries
Capacité
d'une seule
batterie
Coefficient de
limite du courant
de chargement (C)
Durée moyenne de
chargement (min) Temps
(minutes) pour charger les
batteries à 90 % à 25 °C
BP240V65 20 x 65 Ah 1 1 20 65 0.15 540
BP240V65 20 x 65 Ah 2 2 20 65 0.15 540
BP240V65 20 x 65 Ah 3 3 20 65 0.15 540
BP240V65L 40 x 65 Ah 1 2 20 65 0.15 540
BP240V65L 40 x 65 Ah 2 4 20 65 0.15 540
BP240V65L 40 x 65 Ah 3 6 20 65 0.15 540
BP240V100 20 x 100 Ah 1 1 20 100 0.15 540
BP240V100 20 x 100 Ah 2 2 20 100 0.15 540
BP240V100 20 x 100 Ah 3 3 20 100 0.15 540
BP240V100L 40 x 100 Ah 1 2 20 100 0.15 540
BP240V100L 40 x 100 Ah 2 4 20 100 0.15 540
BP240V100L 40 x 100 Ah 3 6 20 100 0.13 540
205
Module de batteries BP240V65 (-NIB) BP240V100 (-NIB) BP240V65L (-NIB) BP240V100L (-NIB)
Dimension
l × P × H
800 x 900 x 1 200 mm
(31,5 x 35,4 x 47,2 po)
800 x 1 100 x 1 600 mm
(31,5 x 43,3 x 63 po)
Poids
275, 8 kg (608 lb)* 421,8 kg (930 lb)* 491,2 kg (1 083 lb)* 742,5 kg (1 637 lb)*
Disjoncteur
1x 250 A 1x 600 A
Fusible
2x 400 A 4x 400 A
*Les modèles avec le suffixe –NIB n'incluent aucune batterie interne, leur poids total varie donc en fonction des batteries
installées par l'utilisateur final.
7. Caractéristiques techniques
Entreposage
L'armoire de batteries doit être entreposée dans un environnement propre et sûr et où la température est inférieure à 40 °C
(104 °F) et l'humidité relative est inférieure à 90 % (sans condensation). Entreposer l'armoire de batteries dans son conteneur
d'expédition original si possible. Charger les batteries pendant au moins 24 heures avant l'utilisation. Ne pas se fier à l'armoire
de batteries pour fournir une alimentation de secours à l'équipement connecté jusqu'à ce que les batteries soient entièrement
chargées.
Remarque : Si l'onduleur demeure hors tension pendant une période prolongée, il est recommandé de le mettre
périodiquement sous tension pour permettre aux batteries de se recharger. L'onduleur doit être mis sous tension et les
batteries doivent être rechargées pendant une période ininterrompue d'au moins 24 heures tous les 3 mois. Si les batteries
ne sont pas rechargées périodiquement, cela risque de causer des dommages irréversibles aux batteries.
8. Entreposage
7.1 Caracteristiques techniques des armoires de batteries
(tension nominale cc :
+
120 V CC, 240 V CC)
206
Garantie limitée
Le vendeur garantit que ce produit, s'il est utilisé conformément à toutes les instructions applicables, est exempt de tous défauts de matériaux et
de fabrication pour une période de un (1) an à partir de la date d'achat initiale. Si le produit s'avère défectueux en raison d'un vice de matière ou de
fabrication au cours de cette période, le vendeur s'engage à réparer ou remplacer le produit, à sa seule discrétion. Le service sous cette garantie inclut
les pièces et la main-d’œuvre du centre de service de Tripp Lite. Tripp Lite offre des plans de services sur place par le biais de partenaires de service
autorisés (dans la plupart des régions). Pour plus de détails, visiter tripplite.com/support. Les clients internationaux doivent contacter l'assistance de
Tripp Lite à [email protected].
CETTE GARANTIE NE S'APPLIQUE PAS À L'USURE NORMALE OU AUX DOMMAGES RÉSULTANT D'UNE MAUVAISE UTILISATION, D'UN ABUS OU D'UNE
NÉGLIGENCE. LE VENDEUR N'ACCORDE AUCUNE GARANTIE EXPRESSE AUTRE QUE LA GARANTIE EXPRESSÉMENT DÉCRITE DANS LE PRÉSENT
DOCUMENT. SAUF DANS LA MESURE OÙ CELA EST INTERDIT PAR LA LOI EN VIGUEUR, TOUTE GARANTIE IMPLICITE, Y COMPRIS TOUTES LES
GARANTIES DE QUALITÉ MARCHANDE OU D'ADAPTATION, SONT LIMITÉES À LA PÉRIODE DE GARANTIE CI-DESSUS ET CETTE GARANTIE EXCLUT
EXPRESSÉMENT TOUS DOMMAGES DIRECTS ET INDIRECTS. (Certains États ne permettent pas de limitations sur la durée d'une garantie implicite,
et certains États ne permettent pas l'exclusion ou la limitation des dommages fortuits ou consécutifs, de sorte que les limitations ou exclusions
susmentionnées peuvent ne pas s'appliquer à vous. Cette garantie vous donne des droits légaux spécifiques, et vous pouvez avoir d'autres droits qui
varient selon le territoire.)
Tripp Lite; 1111 W. 35th Street; Chicago IL 60609; USA
AVERTISSEMENT : L'utilisateur individuel doit prendre soin de déterminer avant l'utilisation si cet appareil est approprié, adéquat et sûr pour l'usage
prévu. Puisque les utilisations individuelles sont sujettes à des variations importantes, le fabricant ne fait aucune déclaration ou garantie quant à
l'aptitude ou l'adaptation de ces dispositifs pour une application spécifique.
Numéros d'identification à la conformité réglementaire
À des fins de certification de conformité réglementaire et d'identification, un numéro de série unique a été attribué au produit Tripp Lite. Le numéro de
série, ainsi que toutes les marques d'homologation et les renseignements requis, se trouvent sur la plaque signalétique du produit. Lors d'une demande
de renseignements concernant la conformité de ce produit, toujours se reporter au numéro de série. Le numéro de série ne doit pas être confondu avec
le nom de la marque ou le numéro de modèle du produit.
Renseignements sur la conformité à la directive DEEE pour les clients de Tripp Lite et les recycleurs (Union européenne)
En vertu de la directive et des règlements d'application relatifs aux déchets d'équipements électriques et électroniques (DEEE), lorsque des clients
achètent de l'équipement électrique et électronique neuf de Tripp Lite, ils ont droit :
D'envoyer l'équipement usagé au recyclage pourvu qu'il soit remplacé par un équipement équivalent (cela varie selon les pays)
D'envoyer le vieil équipement au recyclage en autant qu'il remplace un équipement équivalent (cela varie selon les pays)
La politique de Tripp Lite en est une d'amélioration continue. Les caractéristiques techniques sont modifiables sans préavis. Les produits réels peuvent
différer légèrement des photos et des illustrations.
Entretien
Le produit Tripp Lite est couvert par la garantie décrite dans ce manuel. Une variété de programmes de garantie prolongée et de service d'entretien sont
également offerts par Tripp Lite. Pour obtenir plus de renseignements sur le service, visiter tripplite.com/support. Avant de retourner le produit pour la
réparation, procéder comme suit :
1. Passer en revue les procédures d'installation et de fonctionnement dans ce manuel afin de s'assurer que le problème ne provient pas d'une mauvaise
interprétation des instructions.
2. Si le problème persiste, ne pas communiquer avec le fournisseur et ne pas lui renvoyer le produit. Visiter plutôt tripplite.com/support.
3. Si le problème nécessite une réparation, visiter tripplite.com/support et cliquer sur le lien de retours de produit. À partir de ce point, il est possible de
demander une autorisation de retour de matériel (RMA) qui est requise pour le service. Ce simple formulaire en ligne demandera le modèle de l'appareil
et le numéro de série, ainsi que d'autres informations générales. Le numéro RMA ainsi que des instructions d'expédition seront envoyés par courriel. Les
dommages (directs, indirects, particuliers ou consécutifs) encourus par le produit lors du transport vers Tripp Lite ou vers un centre de réparation agréé
Tripp Lite ne sont pas couverts par la garantie. Les frais liés au transport des produits expédiés à Tripp Lite ou à un centre de service autorisé Tripp Lite
doivent être entièrement payés d'avance. Inscrire le numéro de RMA à l'extérieur de l'emballage. Si le produit est dans sa période de garantie, joindre
une copie du reçu de caisse. Retourner le produit pour réparation par un transporteur assuré à l'adresse fournie lors de la demande de « RMA ».
9. Service et garantie
207
208
1111 W. 35th Street, Chicago, IL 60609 USA • tripplite.com/support
20-11-074 93-3BF8_RevB

Transcripción de documentos

Owner’s Manual Extended-Run Battery Cabinet Models: BP240V65, BP240V65-NIB, BP240V65L, BP240V65L-NIB, BP240V100, BP240V100-NIB, BP240V100L, BP240V100L-NIB Not suitable for mobile applications. Español 69 • Français 137 1111 W. 35th Street, Chicago, IL 60609 USA • tripplite.com/support Copyright © 2020 Tripp Lite. All rights reserved. 1 Table of Contents 1. Introduction 3 1.1 Features 1.2 UPS and Battery Cabinet Compatibility Chart 3 4 2. Important Safety Instructions 5 2.1 2.2 2.3 2.4 Installation and Location Warnings Connection Warnings Battery Warnings Standards Compliance 3. Battery Cabinet Installation 3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 Preparation Transportation Mechanical Check Package Contents Internal Wiring (Typical) Battery Cabinet Placement Electrical Connection Final Electrical Check 4. Mechanical Data 4.1 Physical Measurements 4.1.1 4.1.2 Dimensions for BP240V65, BP240V65-NIB, BP240V100, BP240V100-NIB Dimensions for BP240V65L, BP240V65L-NIB, BP240V100L, BP240V100L-NIB 5.5 Battery Cabinet Connections – Models BP240V65L, BP240V65L-NIB, BP240V100L, BP240V100L-NIB 32 32 5.5.2 Battery Installation and Connection 5.5.2.1 Battery Installation and Setup: Models BP240V65L-NIB, BP240V100L-NIB 5 5 6 6 5.1 Unpacking and Inspection 5.2 Selecting Installation Position 5.3 Power Cables 5.3.1 Cable Sizes 6. Operation and Configuration of S3M UPS Models and Battery Cabinets 7 7 7 8 8 9 9 10 6.1 6.2 37 10 6.2.1 6.2.2 6.2.3 10 6.2.4 12 10 6.3 15 15 16 17 52 S3M UPS Compatibility with 52 BP240V65 to BP240V100L Battery Cabinets Configuring 10-20K UPS for 53 Specific Battery Cabinets using the LCD Display S3M 10-20K UPS Home Display Setting Battery Setup Confiuring the S3M 10-20-NIB and Optimizing Charging of BP240V65/V65L and BP240V100/V100L Battery Cabinets 53 55 56 57 Configuring 25-100K UPS for 59 Specific Battery Cabinets Using the LCD Display 6.3.1 6.3.2 6.3.3 6.3.4 17 17 S3M 25-100K UPS Home Display Setting Battery Setup: Click BATT Setup Configuring the S3M25-100K UPS and Optimizing Charging of the BP240V65/V65L and BP240V100/V100L Battery Cabinets 5.4 Battery Cabinet Connections – Models BP240V65, BP240V65-NIB, 6.4 Configuring Reference Tables BP240V100, BP240V100-NIB 5.4.1 Remove the Chassis Shell 5.4.2 Battery Installation and Connection 5.4.2.1 Battery Installation and Setup: Models BP240V65-NIB, BP240V100-NIB 33 5.6 Multiple Battery Pack Connections 48 7 4.2 Physical Requirements (All Models) 14 5. Installation 5.5.1 Remove the Chassis Shell 60 60 62 63 66 18 7. Specifications 18 67 22 8. 67 7.1 Battery Cabinet Specifications Storage 9. Service and Warranty 2 67 68 1. Introduction Tripp Lite’s Extended-Run Battery Cabinets connect to SmartOnline® UPS Systems to provide long-lasting battery backup for data centers, telecommunications, networks, industrial facilities, security, emergency systems and other mission-critical applications that require high capacity, high availability and extended runtime. Battery cabinets are available in seven models, with pre-installed batteries and without: BP240V65, BP240V65-NIB, BP240V65L, BP240V65L-NIB, BP240V100, BP240V100-NIB, BP240V100L-NIB. The “-NIB” suffix battery cabinet models BP240V65-NIB, BP240V65L-NIB, BP240V100-NIB and BP240V40L-NIB do not include pre-installed batteries. However, they include all of the jumper cables, fuses and breakers, enabling the flexibility to purchase batteries separately for the battery cabinets. The BP240V65-NIB and BP240V65L-NIB battery cabinets are designed for CSB GP12650i batteries. The BP240V100-NIB and BP240V100L-NIB battery cabinets are designed for CSB GP121000 batteries. 1.1 Features • The battery cabinets are designed for battery string voltages of ± 120V DC and battery capacities of 65Ah or 100Ah, @ C20 to 1.67VPC. • Battery cabinets contain multiple 12V DC AGM batteries connected in series to achieve higher voltages. • Each battery cabinet contains several shelves to achieve the required battery string voltages: o BP240V65 / BP240V65-NIB: Holds 20 x 65Ah AGM batteries o BP240V100 / BP240V100-NIB: Holds 20 x 100Ah AGM batteries o BP240V65L / BP240V65L-NIB: Holds 40 x 65Ah AGM batteries o BP240V100L / BP240V100L-NIB: Holds 40 x 100Ah AGM batteries • A hinged, lockable door facilitates access to batteries for periodic maintenance. • A minimum of 4 in. (100 mm) clearance is located above the individual batteries for access to terminals. • The battery cabinet is constructed of heavy-gauge steel for durability. • A baked powder-coat finish provides corrosion resistance. • The battery cabinet ships bolted to a pallet with a double layer of protective stretch wrap and integrated corner and top protection. • Appropriate ventilation and convection cooling of individual batteries is provided via spacing between batteries. Front and rear vents allow the free flow of warmer air out of the battery cabinet. • A molded case circuit breaker is provided for overcurrent protection. • User-supplied power output cables can be fed into the battery cabinet via built-in conduit knockouts on the bottom of the cabinet. • For improved safety, higher power density and minimized maintenance, the cabinet systems use Valve-Regulated Lead-Acid (VRLA) recombinant batteries. The electrolyte in these batteries is immobilized in either an absorbent mat separator or a gelling medium, eliminating the spilling hazards and maintenance requirements of free liquid electrolyte. There is no need to add water or measure specific gravity. • Because the batteries are recombinant cells that employ an oxygen recombination cycle, minimal gasses are emitted during normal float charging. Each cell contains an individual valve, which releases the gas products from overcharge and prevents pressure build-up within the cell. 3 1. Introduction 1.2 UPS and Battery Cabinet Compatibility Chart Cabinets with Internal Batteries BP240V65 BP240V65L BP240V100 BP240V100L Cabinets with NO Internal Batteries BP240V65-NIB BP240V65L-NIB BP240V100-NIB BP240V100L-NIB 10kVA-20kVA UPS with Internal Batteries • S3M10K1B, S3M10K2B, S3M10K3B • S3M15K2B S3M15K3B • S3M20K3B No No No No 10kVA-20kVA UPS with NO Internal Batteries • S3M10K-NIB • S3M15K-NIB • S3M20K-NIB Yes Yes Yes No Cabinets with Internal Batteries BP240V65 BP240V65L BP240V100 BP240V100L Cabinets with NO Internal Batteries BP240V65-NIB BP240V65L-NIB BP240V100-NIB BP240V100L-NIB • S3M25K • S3M30K Yes Yes Yes No • S3M50K Yes Yes Yes Yes • S3M60K No Yes Yes Yes • S3M80K • S3M100K No Yes No Yes 25kVA-100kVA UPS with NO Internal Batteries 4 2. Important Safety Instructions SAVE THESE INSTRUCTIONS All sections of this manual contain instructions and warnings that must be followed during the installation and operation of the battery cabinet described in this manual. Read ALL instructions thoroughly before attempting to move, install or connect your battery cabinet. Failure to heed these warnings may affect your warranty and cause serious property damage and/or personal injury. DANGER! LETHAL HIGH-VOLTAGE HAZARD! All wiring should be performed by a qualified electrician in accordance with the warnings in this manual and all applicable electrical and safety codes. Incorrect wiring may cause serious personal injury and property damage. 2.1 Installation and Location Warnings • Install the battery cabinet in a controlled indoor environment, away from moisture, temperature extremes, flammable liquids and gasses, conductive contaminants, dust and direct sunlight. • Install the battery cabinet in a level, structurally sound location. • The battery cabinet is extremely heavy. Exercise caution when moving or lifting the unit. • Operate the battery cabinet at indoor temperatures between 0° C and 40° C only. For best results, maintain an ambient indoor temperature of 25° C. • Allow adequate space around the front and rear of the battery cabinet for proper ventilation. Do not block, cover or insert objects into the battery cabinet’s external ventilation openings. • Do not place any object on the battery cabinet, especially containers of liquid. • Do not attempt to stack the battery cabinet. Attempting to stack the battery cabinet may cause permanent damage and create a potential for serious personal injury. • Do not attempt to unpack or move the battery cabinet without assistance. Use appropriate handling equipment rated to bear the weight and bulk of the battery cabinet, such as freight elevators, pallet jacks and forklifts. (Fully extend forks under load. Spread forks to maximum possible width under load. Lift cabinet from bottom only. Wear safety shoes.) • For emergency use, install a fire extinguisher rated for energized electrical equipment fires (Class C rating or exact equivalent, with a non-conductive extinguishing agent) near the battery cabinet. 2.2 Connection Warnings • The battery cabinet contains hazardous high voltages that have the potential to cause personal injury or death from electric shock. • The battery cabinet has its own energy source. The output terminals may be live, even when the battery cabinet is not connected to a UPS system. • The battery cabinet must be suitably grounded according to all applicable electrical wiring regulations. • Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of the life support equipment or to significantly affect its safety or effectiveness is not recommended. • De-energize all input and output power sources before installing cables or making electrical connections. • Use flexible cable of sufficient length to permit battery cabinet servicing. • Use ferrule caps to cover termination cables and prevent frayed ends from shorting on terminal blocks. Use cabling rated VW-1, FT-1 or better. Use cable sleeves and connector clamps. • Confirm all cables are marked correctly according to their purpose, polarity and diameter. • Observe proper polarity by following the positive and negative markings on the unit. Failure to observe proper polarity may damage the batteries and create a serious risk of personal injury and property damage. 5 2. Important Safety Instructions • Wiring and assembly should be performed by trained, qualified electricians only. Refer to the UPS unit’s Owner’s Manual for wire sizing. 2.3 Battery Warnings • The battery cabinet requires routine maintenance by qualified, knowledgeable service personnel familiar with its operation. All required precautions should be taken prior to opening the cabinet for any reason. Keep unauthorized personnel away from batteries. • The battery cabinet contains valve-regulated recombinant lead-acid (VRLA) batteries. Do not attempt to add water to these batteries or sample the electrolyte specific gravity. • VRLA batteries can contain an explosive mixture of hydrogen gas. DO NOT SMOKE when near batteries. DO NOT cause flames or sparks near batteries. Discharge static electricity from body before touching batteries. DO NOT open or mutilate batteries—released electrolyte is harmful to the skin and eyes and may be toxic. DO NOT dispose of batteries in a fire— they may explode. • Batteries present a risk of electrical shock and burns from high short-circuit current. Battery connection or replacement should be performed only by qualified service personnel observing proper precautions. Use tools with insulated handles. Remove watches, rings or other metal objects. Wear rubber gloves and boots. Do not short or bridge the battery terminals with any object. Do not lay tools or metal parts on top of batteries. • Replace batteries with equivalent batteries (same number and type) available from Tripp Lite. • The batteries are recyclable. Refer to local codes for disposal requirements. Do not dispose of batteries except through approved channels in accordance with all applicable local, state and national regulations. • Do not connect or disconnect batteries when the UPS system is operating from the battery supply or when the unit is not in bypass mode. Disconnect the charging source prior to connection or disconnecting battery terminals. • If the charging source remains off for an extended period of time, it should be turned on periodically to allow the batteries to recharge. The charging source should be turned on and the batteries should be recharged at least one uninterrupted 24-hour period every 3 months. Failure to recharge the batteries periodically may cause permanent battery damage. • Allow batteries to charge uninterrupted for 24 hours after installation. Note on Labeling These symbols may appear on the product label: V : DC Voltage : Ground +: Battery Positive – : Battery Negative Refer to the product label for model numbers, voltage ratings and other important information. 2.4 Standards Compliance • UL 1778, CSA-C22.2 No. 107.3-14 (3rd Ed) • ISTA B (Transport, Vibration, Tilt) 6 3. Battery Cabinet Installation Read Section 2 – Important Safety Instructions Before Installation 3.1 Preparation • At your site, prepare to off-load the battery cabinet from the delivery truck and transport it to the final installation location. Consider both the packaged weight and dimensions. • Make sure the floor can support the load of the specific battery cabinet being installed. The battery cabinet must be installed in a structurally sound area with a level floor that is able to bear the weight of the battery cabinet and other equipment that will be installed nearby. • Draw a wiring schematic representing the cables connected between the battery cabinet’s output terminal blocks and any external disconnect device, junction box and/or load/rectifier. • If you plan to store the battery cabinet for an extended period before or after installation, follow the instructions in section 9. Storage and Service. 3.2 Transportation 1. Inspect the shipping container(s) for visible damage (do not remove the stretch wrap around the unit until it has been transported to the final installation location). Confirm that the model name and rating match the unit you ordered. If you determine the unit has been damaged during shipping or if anything appears to be missing, contact Tripp Lite for assistance. Do not attempt to use the unit if it has been damaged or mishandled. 2. Do not attempt to move or unpack the battery cabinet without assistance. Use appropriate handling equipment rated to bear the weight and bulk of the battery cabinet, such as freight elevators, pallet jacks and forklifts. (Fully extend forks under load. Spread forks to maximum possible width under load. Lift cabinet from bottom only. Wear safety shoes.) Confirm load limits for freight elevators, handling equipment and floors along the transport route are not exceeded by the combined weight of the packaged battery cabinet, handling equipment and personnel. Confirm that the packaged unit will pass through any doorways along the intended route. 3. The battery cabinet is secured with stretch wrap to protect it during shipping and movement within a facility. Remove the stretch wrap from the battery cabinet when the unit is in the final installation location—not before. 3.3 Mechanical Check While the assembled cabinet battery system is still on the shipping pallet, inspect all sides for impact or other damage. 1. Open the front door of the battery cabinet. 2. Confirm none of the internal parts (batteries, terminal blocks, circuit breaker and other parts) have been damaged. 3. Note the individual battery model number and terminal type shown in section 8. Specifications. 4. Use insulated tools to tighten all battery terminal connections to the recommended torque shown in the table in section 6.3 Power Cables. 5. Use insulated tools to tighten the cables from the positive and negative output terminals at the end batteries to the circuit breaker. 7 3. Battery Cabinet Installation 3.4 Package Contents Part Number Description BP240V65 BP240V65L BP240V65NIB BP240V65LNIB BP240V100 BP240V100L BP240V100NIB BP240V100LNIB Yes Yes Yes Yes Yes Yes Yes Yes 2 2 2 2 2 No 2 No N/A N/A 4/5 8/8 N/A N/A N/A N/A Owners Manual 933BF8 Battery Cables 731891 Battery Insulators 83084A/ 83084B "Cabinet Bottom Side Metal Skirts" 1038F7A Cover bottom area of cabinet 2 N/A 2 N/A 2 N/A 2 N/A "Cabinet Bottom Side Metal Skirts" 1038F8A Cover bottom area of cabinet 2 2 2 2 2 2 2 2 "Cabinet Bottom Side Metal Skirts" 1038F8A Cover bottom area of cabinet N/A 2 N/A 2 N/A 2 N/A 2 Battery Cables for "-NIB" Models Several P/N For connecting the battery strings to the cabinet N/A N/A 10 16 N/A N/A 10 16 Copper Jumper Bars 1038F3 For interconnecting adjacent batteries N/A N/A 10 20 N/A N/A N/A N/A Copper Jumper Bars 1038F4 For interconnecting adjacent batteries N/A N/A 3 8 N/A N/A N/A N/A Copper Jumper Bars 1038F5 For interconnecting adjacent batteries N/A N/A N/A N/A N/A N/A 3 8 Copper Jumper Bars 1038F6 For interconnecting adjacent batteries N/A N/A N/A N/A N/A N/A 10 20 "Battery cables to connect to S3M10-20K UPS" Protective materials 3.5 Internal Wiring (Typical) • Battery cabinets use multiple 12V DC batteries connected in series to provide nominal DC voltage of 240V DC (±120V DC). • Internal cabling is sized for specific application load currents. Do not use any other cable size other than the one provided in the battery cabinet. • Each battery cabinet shelf includes a specific wiring diagram. Refer to section 6. Installation for battery installation details. • All circuit breakers are in the middle tier of the battery cabinet. • All load connection polarities will be labeled as “+” (battery positive), “-“ (battery negative) and “N” (battery center tap) for ±120V DC strings. • All battery cabinets are provided with a branch circuit overcurrent protection device and may be wired directly to the load or UPS. 8 3. Battery Cabinet Installation 3.6 Battery Cabinet Placement Place the battery cabinet in a cool location with free airflow and away from direct heat sources. The lifespan and performance of a battery may be dramatically affected by elevated temperature, decreasing 50% for each 8.25° C above 25° C. 1. Prepare the surface where the cabinet will be placed. The surface must be clean, flat and able to support the battery cabinet and other equipment installed nearby. See section 8. Specifications for floor loads. 2. Allow adequate clearance around the front and rear of the battery cabinet for ventilation and maintenance. The front door must be accessible to allow easy access to internal batteries, internal fuses and other overcurrent protection devices. See section 6.1 Unpacking and Inspection for dimensions and battery cabinet measurements. 3. If the cabinet will be anchored to the floor, install appropriate anchor bolts in the mounting hole located at the bottom of the cabinet. Use washers to create a level surface between the mounting areas around the anchor bolts. 4. Using extreme caution, remove the bolts securing the battery cabinet to the shipping pallet. 5. Forklift forks should be at maximum width within the cabinet clearance opening and fully inserted to prevent tipping. Lift cabinet from bottom only. Be careful not to damage the sheet metal floor of the cabinet with the forks. 6. If the battery cabinet will be secured to the floor, carefully align and lower the battery cabinet down on the floor anchor bolts and secure it in place. 7. If the cabinet will not be secured to the floor, lower it into the designated space and then level it using shims. Leveling does not affect performance, but does align the battery cabinet with other equipment in the facility. 3.7 Electrical Connection DANGER! LETHAL HIGH-VOLTAGE HAZARD! All wiring should be performed by a qualified electrician in accordance with the warnings in this manual and all applicable electrical and safety codes. Incorrect wiring may cause serious personal injury and property damage. • The battery cabinet is connected to the load through a DC circuit breaker. This allows the battery to disconnect from the load and charger for maintenance and/or repair. • The DC molded case circuit breakers are CE-approved for branch circuit protection. If replacement is required, CE-approved components with the same voltage and current rating must be used. • The size of the load connection cables must consider maximum allowable voltage drop, as well as the cables’ continuous ampere capacity and anticipated ampere discharge rate of the individual battery cabinet. A maximum voltage drop of 1.5V DC in the load connection cables is recommended. Refer to the UPS unit’s Owner’s Manual for recommended wire sizes. • Refer to all applicable local, state and national codes for appropriate cable size and ratings. • External circuit protection devices (fuses or circuit breakers) must consider the discharge rate of the battery, the wiring to be protected and the DC short circuit current of the battery. After performing the installation procedures in section 6. Installation, perform the following: 1. Open the front door of the battery cabinet to access internal components. Use a digital voltmeter when voltage measurements are required. 2. Determine if the battery has been inadvertently grounded by resetting the circuit breaker to the “On” position and measuring the voltage between the battery cabinet grounding lug and the positive load connection point within the cabinet. This voltage should measure 0 (zero) VDC. If the measured voltage is not zero, determine the cause and correct before proceeding. 3. Return the internal circuit breaker to an open “Off” position as a safety precaution while connecting the output cables. Doing so prevents damage in the event the cables are accidentally shorted. 4. The top of the battery cabinet includes knockouts for load connection cable entry. Punch out the appropriate knockout and connect the conduit or cable bushing. 5. The output circuit breaker accommodates cables up to 300 mm2. 9 3. Battery Cabinet Installation 6. Connect an appropriate equipment grounding cable to the grounding lug located on the top of the battery cabinet. 7. Feed the positive and negative cables (and “N” center, if equipped) from the open external disconnect switch or the UPS battery field wiring terminals through the conduit/cable bushing. Connect to the respective output terminals inside the battery cabinet. 3.8 Final Electrical Check Before closing any connecting circuit breaker or disconnect switch, complete these verification steps: 1. Verify the battery cabinet output voltage is correct. 2. If battery cabinets will be operated in parallel, verify that the individual system output voltages match within 2V DC. 3. Verify the voltage measured between either output terminal and the battery cabinet ground is zero. 4. If any of the above verification steps show an irregularity, determine and correct the cause before proceeding. 5. Reset the circuit breaker to the “On” position. 4. Mechanical Data 4.1 Physical Measurements 4.1.1 Dimensions for BP240V65, BP240V65-NIB, BP240V100, BP240V100-NIB 47.2 in. (1200 mm) 31.5 in. (800 mm) 35.4 in. (900 mm) 10 4. Mechanical Data Front View Side View 1 4 2 3 5 1 2 3 4 5 Rear View (terminal block without cover) Battery Breaker Battery Terminal for 10kVA-20kVA UPS Battery Terminal for 25kVA-60kVA UPS Grounding Lugs Battery Cable Knockouts 11 Rear View 4. Mechanical Data 4.1.2 Dimensions for BP240V65L, BP240V65L-NIB, BP240V100L, BP240V100L-NIB 63 in. (1600 mm) 31.5 in. (800 mm) 43.4 in. (1100 mm) 12 4. Mechanical Data Front View Side View Rear View 1 2 4 3 1 Battery Breaker 2 Battery Terminal for 10kVA-20kVA UPS 3 Battery Terminal Rear View (terminal block without cover) for 25kVA-60kVA UPS 4 Grounding Lugs 5 Battery Cable Knockouts 5 13 4. Mechanical Data 4.2 Physical Requirements (All Models) Leave some space around the cabinet for operation and ventilation. 1. Leave at least 31.5 in. (800 mm) space in the front for ventilation. 2. Leave at least 20 in. (500 mm) space at the right and left for operation. 3. Leave at least 20 in. (500 mm) space at the back for ventilation. >20 in. (500 mm) >20 in. (500 mm) >20 in. (500 mm) >20 in. (500 mm) >31.5 in. (800 mm) 14 5. Installation Note: Before installation, inspect the unit. Ensure nothing inside the package is damaged. Retain the original packing material in a safe place for future use. 5.1 Unpacking & Inspection Any damage to packaging should be noted with the delivery carrier at the time of receipt. Remove the rail kit, battery enclosure, and battery modules from the packaging. Note: The battery modules are very heavy. Be cautious when unpacking and lifting the unit to avoid injury. • Don’t tilt the battery pack when removing it from the packaging. • Inspect the battery cabinet for damage that may have occurred from transport. If damage is found, do not turn on the unit. Contact the dealer from whom the unit was purchased immediately. • Check the accessories according to the packing list and contact the dealer in case of missing parts. 1. Hold the sliding plate steady. Cut and remove the binding tapes. 3. Remove the packing foam and the beveled pallet. 2. Remove the plastic bag and the shipping carton. 4. Remove the bolts securing the cabinet to the shipping pallet. 15 5. Installation 5. Use a forklift to lift the battery cabinet from the pallet. 5.2 Selecting Installation Position Select a proper environment to install the unit, in order to minimize the possibility of damage to the battery system and maximize the life of the batteries. 1. Do not block air flow to the ventilation openings of the unit. 2. Ensure environmental conditions of the installation site are in accordance with the unit specifications to avoid overheat and excessive moisture. Refer to section 4.2 Physical Requirements. 3. Do not place the unit in a dusty or corrosive environment or near any flammable objects. 4. The unit is not designed for outdoor use. Notes: • Place the battery cabinet in a clean, stable environment. Avoid vibration, dust, humidity, flammable gases, liquids and corrosives. • To help prevent high temperatures in the room where the UPS is installed, extractor fans and/or cooling systems are recommended. • Batteries should be mounted in an environment where the temperature is within the required specifications. Temperature is a key factor in determining battery life and capacity. Battery temperature should be maintained between 59°F to 77°F (20°C to 25°C). Keep batteries away from heat sources, main air ventilation areas, etc. WARNING! Typical battery performance data reflects an operating temperature between 59°F to 77°F (20°C to 25°C). Operating the UPS above this range will reduce the battery life, while operating the UPS below this range will reduce battery capacity. • If the UPS will not be installed immediately, it must be stored in a room without excessive heat or humidity. 16 6. Installation 5.3 Power Cables The cable design shall comply with the voltages and currents provided in this section, and in accordance with local electrical codes. WARNING! UPON STARTING, PLEASE ENSURE YOU ARE AWARE OF THE LOCATION AND OPERATION OF THE EXTERNAL ISOLATORS CONNECTED TO THE UPS INPUT/BYPASS SUPPLY OF THE UTILITY DISTRIBUTION PANEL. CHECK TO SEE IF THESE SUPPLIES ARE ELECTRICALLY ISOLATED AND POST ANY NECESSARY WARNING SIGNS TO PREVENT ANY INADVERTENT OPERATION 5.3.1 Cable Sizes UPS MODEL BP240V65 / BP240V100 BP240V65-NIB / BP240V100-NIB BP240V65L / BP240V100L BP240V65L-NIB / BP240V100L-NIB Recommended Torque CABLE SIZES (THHW wiring at 167°F / 75°C) DC INPUT GROUNDING DC INPUT GROUNDING 10kVA 6 AWG 6 AWG 6 AWG 6 AWG 15kVA 6 AWG x 2 6 AWG x 2 6 AWG x 2 6 AWG x 2 20kVA 6 AWG x 2 6 AWG x 2 6 AWG x 2 6 AWG x 2 25kVA 1/0 AWG 2 AWG 1/0 AWG 2 AWG 30kVA 1/0 AWG 1/0 AWG 1/0 AWG 1/0 AWG 50kVA 2/0 AWG 2/0 AWG 2/0 AWG 2/0 AWG 60kVA 2/0 AWG 2/0 AWG 2/0 AWG 2/0 AWG 80kVA 2/0 AWG x 2 2/0 AWG x 2 100kVA 2/0 AWG x 2 2/0 AWG x 2 Anderson Connector (No Torque Parameter) 0kgf.com / 0N•m 450kgf.cm/ 44N•m * S3M10-30K UPS systems do not support BP240V100L/100L-NIB battery cabinet models. 5.4 Battery Cabinet Connections: Models BP240V65, BP240V65-NIB, BP240V100 and BP240V100-NIB Each battery cabinet design includes built-in internal battery connection cables, breaker, fuses and terminals. The standard cabinet can hold 20 pieces of 12V 65Ah 12V 100Ah batteries. The DC voltage system for all cabinets is 240VDC with ±120V internal battery strings. Figures 6-1 and 6-2 show the overall chassis design and exploded views for the BP240V65, BP240V65-NIB, BP240V100 and BP240V100-NIB models. The corresponding views for the BP240V65L, BP240V65L-NIB, BP240V100L and BP240V100L-NIB models are shown in section 6.5 Battery Cabinet Connections: Models BP240V65L, BP240V65LNIB, BP240V100L and BP240V100L-NIB. Figure 5-1: BP240V65, BP240V65-NIB, BP240V100, & BP240V100-NIB Battery Cabinet Chassis 17 5. Installation Figure 5-2: Exploded Chassis View, Models BP240V65, BP240V65-NIB, BP240V100, BP240V100-NIB 5.4.1 Remove the Chassis Shell Place the battery cabinet in position. Remove the top, front, left and right panels. Remove the right and left cover plate of the battery pack and the battery flapper to install the batteries. 5.4.2 Battery Installation and Connection Each battery group has 20 pieces of batteries in series (BAT+, N and BAT-). Place the batteries in the cabinet from the bottom to top one-by-one, then connect the battery cables according to the diagrams that follow. Note: The positive and negative polarity of the battery cannot be reversed or short circuited. Doing so will damage the battery and/or cause injury. Do not touch the battery’s positive and negative terminals at the same time. Before replacing or removing the batteries, disconnect the breaker, pull up cell terminals and remove the screws of the copper bus bar. Not following the instructions could result in damage to the equipment or personal injury. The installation must consist of 40 batteries. 18 5. Installation Layer 3 Positive group 10pcs Layer 2 Negative group 10pcs Layer 1 Figure 5-3A: Front View Fuses 400A (x2) Battery breaker 25-100kVA connector 10-20kVA connector Figure 5-3B: Rear View 19 5. Installation Note: This manual may be downloaded in color at tripplite.com, which shows the cables in corresponding colors: Red = Positive Blue = Center Tap Black = Negative Figure 5-4: Wiring Diagram for Model BP240V65 20 5. Installation Note: This manual may be downloaded in color at tripplite.com, which shows the cables in corresponding colors: Red = Positive Blue = Center Tap Black = Negative Figure 5-5: Wiring Diagram for Model BP240V100 21 5. Installation 5.4.2.1 Battery installation and Setup: Models BP240V65-NIB, BP240V100-NIB 1. Remove all screws labeled 1 (Figures 5-6A and 5-6B). Figure 5-6A Figure 5-6B 22 5. Installation 2. Remove the top, right side and left side plates (Figure 5-7). Figure 5-7 3. Remove all screws of the battery retention brackets and remove the retention brackets (Figure 5-8). Figure 5-8 23 5. Installation 4. Install 8 battery packs in layer 1 (Figure 5-9: Model BP240V65-NIB or Figure 5-10: Model BP240V100-NIB). Figure 5-9: Model BP240V65-NIB Figure 5-10: Model BP240V100-NIB 24 5. Installation 5. Install 6 battery packs in layer 2 (Figure 5-11: Model BP240V65-NIB or Figure 5-12: Model BP240V100-NIB). Figure 5-11: Model BP240V65-NIB Figure 5-12: Model BP240V100-NIB 25 5. Installation 6. Install 6 battery packs in layer 3 (Figure 5-13: Model BP240V65-NIB or Figure 5-14: ModelBP240V100-NIB). Figure 5-13: Model BP240V65-NIB Figure 5-14: Model BP240V100-NIB 26 5. Installation 7. Reinstall all battery retention brackets and screws (Figure 5-15: Model BP240V65-NIB or Figure 5-16: Model BP240V100-NIB). Figure 5-15: Model BP240V65-NIB Figure 5-16: Model BP240V100-NIB 27 5. Installation 8. Model BP240V65-NIB: Install copper bus bars (13 pieces) between adjacent batteries and the battery insert bolts/screws (Figures 5-17A and 5-17B). Figure 5-17A Figure 5-17B 28 5. Installation 9. Model BP240V100-NIB: Install copper bus bars (12 pieces) between adjacent batteries and the battery insert bolts/screws (Figures 5-18A and 5-18B). Figure 5-18A Figure 5-18B 29 5. Installation 10. Connect the cables from battery 1+ to BAT+ bus bar, battery 10- to BATN bus bar, battery 11+ to BATN bus bar, battery 20- to BAT- bus bar and the layer connect cables (Figure 5-19: Model BP240V65-NIB or Figure 5-20: Model BP240V100-NIB and Figure 5-21). Notes: • Use the wiring schematics as reference for the following assemblies: Use Figure 5-4 for BP240V65-NIB Use Figure 5-5 for BP240V100-NIB • This manual may be downloaded in color at tripplite.com, which shows the cables in corresponding colors: Red = Positive Blue = Center Tap Black = Negative Figure 5-19: Model BP240V65-NIB Figure 5-20: Model BP240V100-NIB 30 5. Installation Figure 5-21 11. Reinstall all covers and screws (Figure 5-22). Figure 5-22 31 5. Installation 5.5 Battery Cabinet Connections: Models BP240V65L, BP240V65L-NIB, BP240V100L and BP240V100L-NIB Each battery cabinet design includes built-in internal battery connection cables, breaker, fuses and terminals. The standard cabinet can hold 20 pieces of 12V 65Ah (12V/100Ah) batteries. The “L” long-runtime battery cabinets can hold 40 pieces of the 12V 65Ah (12V 100Ah) batteries. The DC voltage system for all cabinets is 240VDC with ±120V internal battery strings. Figures 5-23 and 5-24 show the overall chassis design and exploded views for the BP240V65L, BP240V65L-NIB, BP240V100L and BP240V100L-NIB models. The corresponding views for the BP240V65, BP240V65-NIB, BP240V100 and BP240V100-NIB models are shown in section 5.4 Battery Cabinet Connections: Models BP240V65, BP240V65-NIB, BP240V100 and BP240V100-NIB. Figure 5-23: BP240V65L, BP240V65L-NIB, BP240V100L, & BP240V100L-NIB Battery Chassis 5.5.1 Remove the Chassis Shell Place the battery box its final location. Remove the top, front, left and right panels. Remove the right and left cover plates of the battery pack and the battery supports to install the batteries strings. Figure 5-24: Exploded View – Models BP240V65L, BP240V65L-NIB, BP240V100l, BP240V100L-NIB 32 5. Installation 5.5.2 Battery Installation and Connection The 40 batteries can be divided into two groups connected in parallel for use. Each group has 20 batteries in series (BAT+, N and BAT-). Place the batteries in the cabinet from the bottom to top one-by-one, then connect the battery cables according to the diagrams that follow. Note: The positive and negative polarity of the battery cannot be reversed or short circuited. Doing so will damage the battery and/or cause injury. Do not touch the battery’s positive and negative terminals at the same time. Before replacing or removing the batteries, disconnect the breaker, pull up cell terminals and remove the screws of the copper bus bar. Not following the instructions could result in damage to the equipment or personal injury. The installation must consist of 40 batteries. Battery Group 2 Layer 4 Layer 3 Battery Group 1 Layer 2 Layer 1 Figure 5-25A: Front view 33 5. Installation Fuses 400A (x2) Battery breaker 25-100kVA connector 10-20kVA connector Figure 5-25B: Rear View 34 5. Installation Figure 5-26: Wiring diagram for BP240V65L (40 batteries installed) Note: This manual may be downloaded in color at tripplite.com, which shows the cables in corresponding colors: Red = Positive Blue = Center Tap Black = Negative 35 5. Installation Figure 5-27: Wiring diagram for BP240V100L (40 batteries installed) When the battery installation and connection is completed, use a multi-meter or other instrument to check if the voltages between BAT+ and N, N and BAT- are normal. If normal, lock the chassis cover. Note: This manual may be downloaded in color at tripplite.com, which shows the cables in corresponding colors: Red = Positive Blue = Center Tap Black = Negative 36 5. Installation 5.5.2.1 Battery Installation and Setup: Models BP240V65L-NIB, BP240V100L-NIB 1. Remove all screws labeled 1 (Figures 5-28A and 5-28B). Figure 5-28A Figure 5-28B 37 5. Installation 2. Remove the top, right side and left side plates (Figure 5-29). Figure 5-29 3. Remove all screws of the battery retention brackets and remove the retention brackets (Figure 5-30). Figure 5-30 38 5. Installation 4. Install 10 battery packs in layer 1 (Figure 5-31: Model BP240V65L-NIB or Figure 5-32: Model BP240V100L-NIB). Figure 5-31: Model BP240V65L-NIB Figure 5-32: Model BP240V100L-NIB 39 5. Installation 5. Install 10 battery packs in layer 2 (Figure 5-33: Model BP240V65L-NIB or Figure 5-34: Model BP240V100L-NIB). Figure 5-33: Model BP240V65L-NIB Figure 5-34: Model BP240V100L-NIB 40 5. Installation 6. Install 10 battery packs in layer 3 (Figure 5-35: Model BP240V65L-NIB or Figure 5-36: Model BP240V100L-NIB). Figure 5-35: Model BP240V65L-NIB Figure 5-36: Model BP240V100L-NIB 41 5. Installation 7. Install 10 battery packs in layer 4 (Figure 5-37: Model BP240V65L-NIB or Figure 5-38: Model BP240V100L-NIB). Figure 5-37: Model BP240V65L-NIB Figure5-38: Model BP240V100L-NIB 42 5. Installation 8. Reinstall all battery retention brackets and screws (Figure 5-39). Figure 5-39 9. Model BP240V65L-NIB: Install copper bus bars (13 pieces) between adjacent batteries and the battery insert bolts/posts (Figures 5-40A and 5-40B). Figure 5-40A 43 5. Installation Figure 5-40B 10. Model BP240V100L-NIB: Install copper bus bars (12 pieces) between adjacent batteries and the battery insert bolts/posts (Figures 5-41A and 5-41B). Figure 6-41A 44 5. Installation Figure 5-41B 11. Connect the cables from battery group 1 battery 1+ to BAT+ bus bar, battery 10- to BATN bus bar, battery 11+ to BATN bus bar, battery 20- to BAT- bus bar and the layer connect cables. Connect battery group 2 battery 21+ to BAT+ bus bar, battery 30- to BATN bus bar, battery 31+ to BATN bus bar, battery 40- to BAT- copper bar and the layer connect cables (Figure 5-42: Model BP240V65L-NIB or Figure 5-43: Model BP240V100L and Figure 5-44). Notes: • Use the wiring schematics as reference for the following assemblies: Use Figure 5-26 for BP240V65L-NIB Use Figure 5-27 for BP240V100L-NIB • This manual may be downloaded in color at tripplite.com, which shows the cables in corresponding colors: Red = Positive Blue = Center Tap Black = Negative Figure 5-42: Model BP240V65L-NIB 45 5. Installation Figure 5-43: Model BP240V100L-NIB Figure 5-44 46 5. Installation 12. Reinstall all covers and screws (Figure 5-45). Figure 5-45 47 5. Installation 5.6 Multiple Battery Pack Connections CAUTION! Ensure correct polarity of the battery string series connection. DO NOT mix batteries with different capacities, different brands or new and old batteries. WARNING! ENSURE CORRECT POLARITY OF STRING END CONNECTIONS TO THE BATTERY CIRCUIT BREAKER, AND FROM THE BATTERY CIRCUIT BREAKER TO THE UPS TERMINALS (I.E. (+) TO (+) / (-) TO (-) / (N) TO (N)). DISCONNECT ONE OR MORE BATTERY CELL LINKS IN EACH TIER. DO NOT RECONNECT THESE LINKS AND DO NOT CLOSE THE BATTERY CIRCUIT BREAKER UNLESS ALL CONNECTIONS ARE PROPERLY CHECKED AND APPROVED. UPS Battery Cabinet Figure 5-46: Connection of BP240V65L and BP240V65L-NIB for 10kVA, 15kVA and 20kVA UPS 48 5. Installation UPS Battery Cabinet Figure 5-47: Connection of BP240V65L and BP240V65L-NIB for 25kVA and 30kVA UPS 49 5. Installation UPS Battery Cabinet Figure 5-48: Connection of BP240V65L, BP240V65L-NIB, BP240V100L or BP240V100L-NIB for 50kVA & 60kVA UPS Systems 50 5. Installation UPS Battery Cabinet Figure 5-49: Connection of BP240V65L, BP240V65L-NIB, BP240V100L or BP240V100L-NIB for 80kVA & 100kVA UPS 51 6. O  peration and Configuration of S3M UPS Models and Battery Cabinets 6.1 S  3M UPS Compatibility with BP240V65 to BP240V100L Battery Cabinets Cabinets with Internal Batteries BP240V65 BP240V65L BP240V100 BP240V100L Cabinets with NO Internal Batteries BP240V65-NIB BP240V65L-NIB BP240V100-NIB BP240V100L-NIB 10kVA-20kVA UPS with Internal Batteries • S3M10K1B, S3M10K2B, S3M10K3B • S3M15K2B S3M15K3B • S3M20K3B No No No No 10kVA-20kVA UPS with NO Internal Batteries • S3M10K-NIB • S3M15K-NIB • S3M20K-NIB Yes Yes Yes No Cabinets with Internal Batteries BP240V65 BP240V65L BP240V100 BP240V100L Cabinets with NO Internal Batteries BP240V65-NIB BP240V65L-NIB BP240V100-NIB BP240V100L-NIB • S3M25K • S3M30K Yes Yes Yes No • S3M50K Yes Yes Yes Yes • S3M60K No Yes Yes Yes • S3M80K • S3M100K No Yes No Yes 25kVA-100kVA UPS with NO Internal Batteries 52 6. O  peration and Configuration of S3M UPS Models and Battery Cabinets 6.2 C  onfiguring 10-20K UPS for Specific Battery Cabinets using the LCD Display CAUTION ! Settings for most parameters cannot be changed when the UPS is in inverter mode. 6.2.1 S3M10-20K UPS Home Display 53 6. O  peration and Configuration of S3M UPS Models and Battery Cabinets 6.2.2 Setting Click on the Settings icon to enter two setting levels. The Basic Setting is for user settings, and the Advanced Setting is for technical personnel only. Contact your administrator to enter advanced settings. Advanced Setting: Click Advanced Setting and input the correct password. The user password is “191210”. 54 6. O  peration and Configuration of S3M UPS Models and Battery Cabinets 6.2.3 Battery Setup Click Battery Setup 55 6. O  peration and Configuration of S3M UPS Models and Battery Cabinets 6.2.4 Configuring the S3M25-100K UPS and Optimizing Charging of the BP240V65/V65L and BP240V100/V100L Battery Cabinets Step 1: Setting the Battery Group The Battery Group is Quantity 1 for every set of 20 batteries that are in and/or connected to the UPS model. For example, UPS model S3M20K-NIB has no internal batteries and is Battery Group 1 by default for any UPS model. However, to connect a BP240V65 cabinet with 20 internal batteries to the S3M20K-NIB, the S3M20K-NIB UPS must remain set to Battery Group 1 (one set of 20 batteries). However, to connect a second BP240V65 to the S3M20K-NIB UPS, the UPS Battery Group must be 2 (two sets of 20 batteries). Obtain the Battery Group number based on the specific S3M UPS and Battery Cabinet models combination from the chart under Section 6.4. The value can be 1 to 8. The default value is 1 for S3M UPS models without internal batteries. Step 2: Setting the Battery Number The battery number must remain at 20 for all S3M10-100K UPS models when connected to Tripp Lite external battery cabinets designed for the S3M-Series UPS Series. Step 3: Setting Single Battery (Ah) Capability Change the Single Battery (Ah) Capability to the individual Ah capacity for one individual battery as follows for the specific battery cabinet models: • BP240V09/BP240V09K: the Single Battery (Ah) Capacity is 9 • BP240V40/BP240V40L: the Single Battery (Ah) Capacity is 40 • BP240V65/BP240V65L: the Single Battery (Ah) Capacity is 65 • BP240V100/BP240100L: the Single Battery (Ah) Capacity is 100 The values can be 7~2000. Scroll to the next display screen by pressing the down arrow. 56 6. O  peration and Configuration of S3M UPS Models and Battery Cabinets Step 4: Setting Max Charge Current Max Charge Current is the estimated charge current that the UPS will use to charge the batteries. Obtain the recommended estimated Max Charge Current based on the specific S3M UPS and battery cabinet model combination from the chart in Section 6.4. Float and Boost Voltage: The UPS is factory-set for proper float (2.27V/cell, 13.62V/battery) and boost (2.35V/cell, 14.1V/battery) voltages. Cell float voltage: The float voltage value can be 2.23~2.30 V/cell. The default value is 2.27 V/cell. Cell boost voltage: The battery equalized voltage value can be 2.30~2.40 V/cell. The default value is 2.35 V/cell. Step 5: Setting Aver Changing Duration (min) Setting the Average Charging Duration in minutes is an estimation of the boost charger time duration to charge new batteries to 90% capacity at 25°C. Obtain the recommended Average (Aver) Charging Duration (min) number based on the specific S3M UPS and battery cabinet model combination from the chart in Section 6.4. Note the recommended battery boost charge durations are estimates only based on new batteries. These numbers may change with the age of the batteries and the battery ambient temperature. To change the Aver Charging Duration, press directly on the defaulted 240 value in the display. • The Average (Aver) charging duration is the battery boost charge time limit. The value can be 1~999 min. The default is value 240 (4 hours). EOD Battery Volt: End of discharge voltage is the low voltage cutoff of the batteries during a battery mode operation. The value can be 1.60~1.90. The default value is 1.67V/cell, or 10.02Vdc per battery. Float Temp Compen Coeff: Modifies the voltage of compensation after enabling the switch. The value can be 0.001~0.007V/cell/°C. The default value is 0.003V/cell/°C. Boost Charge Setting: Boost charge can be set to Disable or Enable. The default value is Enable. No Battery Warning: Keep this alarm enabled if you want the UPS to provide a warning when no batteries are present. The default value is Alarm. 57 6. O  peration and Configuration of S3M UPS Models and Battery Cabinets 6.3 C  onfiguring 25-100K UPS for Specific Battery Cabinets Using the LCD Display CAUTION ! Settings for most parameters cannot be changed when the UPS is in inverter mode. 58 6. O  peration and Configuration of S3M UPS Models and Battery Cabinets 6.3.1 S3M25-100K UPS Home Display 6.3.2 Setting Click on the Settings icon to enter two setting levels. The Basic Setting is for user settings, and the Advanced Setting is for technical personnel only. Contact your administrator to enter advanced settings. Advanced Setting: Click Advanced Setting and input the correct password. The user password is “191210”. 59 6. O  peration and Configuration of S3M UPS Models and Battery Cabinets 60 6. O  peration and Configuration of S3M UPS Models and Battery Cabinets 6.3.3 Battery Setup Click BATT Setup Float Temp. Compen.: The temperature sensor compensation setting maybe changed to Enable when a battery temperature sensor is connected to the UPS system’s RJ45 rear port. Temp Sensor Select: Set the temperature sensor type to NTC for single and short distances. Set the temperature sensor type to RS485 for multiple and far distances. 61 6. O  peration and Configuration of S3M UPS Models and Battery Cabinets 6.3.4 Configuring the S3M25-100K UPS and Optimizing Charging of the BP240V65/V65L and BP240V100/V100L Battery Cabinets Step 1: Setting the Battery Group The Battery Group is Quantity 1 for every set of 20 batteries that are in and/or connected to the UPS model. For example, UPS model S3M100K UPS has no internal batteries and is Battery Group 1 by default. However, to connect a BP240V100L cabinet with 40 internal batteries to the S3M100K, the S3M100K UPS must be configured to Battery Group 2. To connect a second BP240V100L cabinet to the S3M100K UPS, the Battery Group must be set to 4 (four sets of 20 batteries). Obtain the Battery Group number based on the specific S3M UPS and Battery Cabinet models combination from the chart under Section 6.4. The value can be 1 to 8. The default value is 1 for S3M UPS models without internal batteries. Step 2: Setting the Battery Number The battery number must remain at 20 for all S3M10-100K UPS models when connected to Tripp Lite external battery cabinets designed for the S3M-Series UPS Series. Step 3: Setting Single Battery (Ah) Capability Change the Single Battery (Ah) Capability to the individual Ah capacity for one individual battery as follows for the specific battery cabinet model: • BP240V40/BP240V40L: the Single Battery (Ah) Capacity is 40 • BP240V65/BP240V65L: the Single Battery (Ah) Capacity is 65 • BP240V100/BP240V100L: the Single Battery (Ah) Capacity is 100 The Single Battery (Ah) values can be 7~2000. Scroll to the next display screen by pressing the down arrow. 62 6. O  peration and Configuration of S3M UPS Models and Battery Cabinets Step 4: Setting Chg. cur. limiting coef (C) The charging current limit is a multiple of the battery capacity. It is used to set the battery boost charging time limit. The value can be 0.05~0.25, and is 0.25 by default. Obtain the Charging (Chg) current (cur) limiting coefficient (C) based on the specific S3M UPS and battery cabinet model combination from the chart in Section 6.4. Float and Boost Voltage: The UPS is factory-set for proper float (2.27V/cell, 13.62V/battery) and boost (2.35V/cell, 14.1V/ battery) voltages. Cell float voltage: The float voltage value can be 2.23~2.30 V/cell. The default value is 2.27 V/cell. Cell boost voltage: The battery equalized voltage value can be 2.30~2.40 V/cell. The default value is 2.35 V/cell. Step 5: Setting Aver Changing Duration (min) Setting the Average Charging Duration in minutes is an estimation of the boost charger time duration to charge new batteries to 90% capacity at 25°C. Obtain the recommended Average (Aver) Charging Duration (min) number based on the specific S3M UPS and battery cabinet model combination from the chart in Section 6.4. Note the recommended battery boost charge durations are estimates only based on new batteries. These numbers may change with the age of the batteries and the battery ambient temperature. To change the Aver Charging Duration, press directly on the defaulted 240 value in the display. • The Average (Aver) charging duration is the battery boost charge time limit. The value can be 1~999 min. The default is value 240 (4 hours). 63 6. O  peration and Configuration of S3M UPS Models and Battery Cabinets EOD Battery Volt: End of discharge voltage is the low voltage cutoff of the batteries during a battery mode operation. The value can be 1.60~1.90. The default value is 1.67V/cell, or 10.02Vdc per battery. Float Temp Compen Coeff: Modifies the voltage of compensation after enabling the switch. The value can be 0.001~0.007V/cell/°C. The default value is 0.003V/cell/°C. Boost Charge Setting: Boost charge can be set to Disable or Enable. The default value is Enable. No Battery Warning: Keep this alarm enabled if you want the UPS to provide a warning when no batteries are present. The default value is Enable. 64 6. O  peration and Configuration of S3M UPS Models and Battery Cabinets 6.4 Configuration Reference Table for S3M10-100K UPS and BP240V09K-BP240V100L Battery Cabinet Models Configurations for S3M10K-NIB, S3M15K-NIB, S3M20K-NIB UPS with no internal batteries Battery Packs Batteries Qty. of Battery Cabinets Step 1 Step 2 Step 3 Step 4 Step 5 Battery Group Battery Number Single Battery Capability Max Charge Current (A) Aver Changing Duration (min) Time (minutes) to Charge Batteries to 90% at 25°C BP240V65 20 x 65Ah 1 1 20 65 9.75 500 BP240V65 20 x 65Ah 2 2 20 65 19.5 500 BP240V65 20 x 65Ah 3 3 20 65 20 720 BP240V65L 40 x 65Ah 1 2 20 65 19.5 500 BP240V65L 40 x 65Ah 2 4 20 65 20 960 BP240V100 20 x 100Ah 1 1 20 100 15 500 Configurations for S3M25K and S3M30K Battery Packs Batteries Qty. of Battery Cabinets Step 1 Step 2 Step 3 Step 4 Step 5 Battery Group Battery Number Single Battery Capability Chg. Cur. Limiting Coef. (C) Aver Changing Duration (min) Time (minutes) to Charge Batteries to 90% at 25°C BP240V65 20x 65Ah 1 1 20 65 0.15 540 BP240V65 20 x 65Ah 2 2 20 65 0.15 540 BP240V65 20 x 65Ah 3 3 20 65 0.1 900 BP240V65L 40 x 65Ah 1 2 20 65 0.15 540 BP240V65L 40 x 65Ah 2 4 20 65 0.07 999 BP240V100 20 x 100Ah 1 1 20 100 0.15 540 Configurations for S3M50K and S3M60K Battery Packs Batteries Qty. of Battery Cabinets Step 1 Step 2 Step 3 Step 4 Step 5 Battery Group Battery Number Single Battery Capability Chg. Cur. Limiting Coef. (C) Aver Changing Duration (min) Time (minutes) to Charge Batteries to 90% at 25°C BP240V65 20 x 65Ah 1 1 20 65 0.15 540 BP240V65 20 x 65Ah 2 2 20 65 0.15 540 BP240V65 20 x 65Ah 3 3 20 65 0.15 540 BP240V65L 40 x 65Ah 1 2 20 65 0.15 540 BP240V65L 40 x 65Ah 2 4 20 65 0.15 540 BP240V65L 40 x 65Ah 3 6 20 65 0.1 840 BP240V100 20 x 100Ah 1 1 20 100 0.15 540 BP240V100 20 x 100Ah 2 2 20 100 0.15 540 BP240V100 20 x 100Ah 3 3 20 100 0.13 540 BP240V100L 40 x 100Ah 1 2 20 100 0.15 540 BP240V100L 40 x 100Ah 2 4 20 100 0.1 840 65 6. O  peration and Configuration of S3M UPS Models and Battery Cabinets Configurations for S3M80K Battery Packs Batteries Qty. of Battery Cabinets Step 1 Step 2 Step 3 Step 4 Step 5 Battery Group Battery Number Single Battery Capability Chg. Cur. Limiting Coef. (C) Aver Changing Duration (min) Time (minutes) to Charge Batteries to 90% at 25°C BP240V65 20 x 65Ah 1 1 20 65 0.15 540 BP240V65 20 x 65Ah 2 2 20 65 0.15 540 BP240V65 20 x 65Ah 3 3 20 65 0.15 540 BP240V65L 40 x 65Ah 1 2 20 65 0.15 540 BP240V65L 40 x 65Ah 2 4 20 65 0.15 540 BP240V65L 40 x 65Ah 3 6 20 65 0.15 540 BP240V100 20 x 100Ah 1 1 20 100 0.15 540 BP240V100 20 x 100Ah 2 2 20 100 0.15 540 BP240V100 20 x 100Ah 3 3 20 100 0.15 540 BP240V100L 40 x 100Ah 1 2 20 100 0.15 540 BP240V100L 40 x 100Ah 2 4 20 100 0.15 540 BP240V100L 40 x 100Ah 3 6 20 100 0.1 840 Step 1 Step 2 Step 3 Step 4 Step 5 Battery Group Battery Number Single Battery Capability Chg. Cur. Limiting Coef. (C) Aver Changing Duration (min) Time (minutes) to Charge Batteries to 90% at 25°C Configurations for S3M100K Battery Packs Batteries Qty. of Battery Cabinets BP240V65 20 x 65Ah 1 1 20 65 0.15 540 BP240V65 20 x 65Ah 2 2 20 65 0.15 540 BP240V65 20 x 65Ah 3 3 20 65 0.15 540 BP240V65L 40 x 65Ah 1 2 20 65 0.15 540 BP240V65L 40 x 65Ah 2 4 20 65 0.15 540 BP240V65L 40 x 65Ah 3 6 20 65 0.15 540 BP240V100 20 x 100Ah 1 1 20 100 0.15 540 BP240V100 20 x 100Ah 2 2 20 100 0.15 540 BP240V100 20 x 100Ah 3 3 20 100 0.15 540 BP240V100L 40 x 100Ah 1 2 20 100 0.15 540 BP240V100L 40 x 100Ah 2 4 20 100 0.15 540 BP240V100L 40 x 100Ah 3 6 20 100 0.13 540 66 7. Specifications 7.1 B  attery Cabinet Specifications (DC Nominal Voltage: ± 120V DC, 240V DC) Battery Pack Dimension W×D×H Weight BP240V65 (-NIB) BP240V100 (-NIB) 31.5 x 35.4 x 47.2 in. (800 x 900 x 1200 mm) 608 lb. (275.8 kg)* 930 lb. (421.8 kg)* BP240V65L (-NIB) BP240V100L (-NIB) 31.5 x 43.3 x 63 in. (800 x 1100 x 1600 mm) 1083 lb. (491.2 kg)* 1637 lb. (742.5 kg)* Breaker 1x 250A 1x 600A Fuse 2x 400A 4x 400A *Models with the –NIB suffix do not include internal batteries, so their total weight varies based on batteries installed by the end user. 8. Storage Storage The battery cabinet must be stored in a clean, secure environment with a temperature less than 104°F (40°C) and a relative humidity less than 90% (non-condensing). Store the battery cabinet in its original shipping container if possible. Charge the batteries for at least 24 hours prior to use. Do not rely on the battery cabinet to provide backup power to connected equipment until the batteries are fully charged. Note: If the UPS system remains off for an extended period of time, it should be turned on periodically to allow the batteries to recharge. The UPS system should be turned on and the batteries should be recharged at least one uninterrupted 24-hour period every 3 months. Failure to recharge the batteries periodically may cause irreversible battery damage. 9. Service and Warranty Service Your Tripp Lite product is covered by the warranty described in this manual. A variety of Extended Warranty and On-Site Service Programs are also available from Tripp Lite. For more information on service, visit tripplite.com/support. Before returning your product for service, follow these steps: 1. Review the installation and operation procedures in this manual to ensure that the service problem does not originate from a misreading of the instructions. 2. If the problem continues, do not contact or return the product to the dealer. Instead, visit tripplite.com/support. 3. If the problem requires service, visit tripplite.com/support and click the Product Returns link. From here you can request a Returned Material Authorization (RMA) number, which is required for service. This simple on-line form will ask for your unit’s model and serial numbers, along with other general purchaser information. The RMA number, along with shipping instructions will be emailed to you. Any damages (direct, indirect, special or consequential) to the product incurred during shipment to Tripp Lite or an authorized Tripp Lite service center are not covered under warranty. Products shipped to Tripp Lite or an authorized Tripp Lite service center must have transportation charges prepaid. Mark the RMA number on the outside of the package. If the product is within its warranty period, enclose a copy of your sales receipt. Return the product for service using an insured carrier to the address given to you when you request the RMA. 67 9. Service and Warranty Limited Warranty Seller warrants this product, if used in accordance with all applicable instructions, to be free from original defects in material and workmanship for a period of one (1) year from the date of initial purchase. If the product should prove defective in material or workmanship within that period, Seller will repair or replace the product, in its sole discretion. Service under this Warranty includes parts and Tripp Lite service center labor. On-site service plans are available from Tripp Lite through authorized service partners (in most areas). Visit tripplite.com/ support for details. International customers should contact Tripp Lite support at [email protected]. THIS WARRANTY DOES NOT APPLY TO NORMAL WEAR OR TO DAMAGE RESULTING FROM ACCIDENT, MISUSE, ABUSE OR NEGLECT. SELLER MAKES NO EXPRESS WARRANTIES OTHER THAN THE WARRANTY EXPRESSLY SET FORTH HEREIN. EXCEPT TO THE EXTENT PROHIBITED BY APPLICABLE LAW, ALL IMPLIED WARRANTIES, INCLUDING ALL WARRANTIES OF MERCHANTABILITY OR FITNESS, ARE LIMITED IN DURATION TO THE WARRANTY PERIOD SET FORTH ABOVE; AND THIS WARRANTY EXPRESSLY EXCLUDES ALL INCIDENTAL AND CONSEQUENTIAL DAMAGES. (Some states do not allow limitations on how long an implied warranty lasts, and some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitations or exclusions may not apply to you. This Warranty gives you specific legal rights, and you may have other rights which vary from jurisdiction to jurisdiction.) Tripp Lite; 1111 W. 35th Street; Chicago IL 60609; USA WARNING: The individual user should take care to determine prior to use whether this device is suitable, adequate or safe for the use intended. Since individual applications are subject to great variation, the manufacturer makes no representation or warranty as to the suitability or fitness of these devices for any specific application. Regulatory Compliance Identification Numbers For the purpose of regulatory compliance certifications and identification, your Tripp Lite product has been assigned a unique series number. The series number can be found on the product nameplate label, along with all required approval markings and information. When requesting compliance information for this product, always refer to the series number. The series number should not be confused with the marketing name or model number of the product. WEEE Compliance Information for Tripp Lite Customers and Recyclers (European Union) Under the Waste Electrical and Electronic Equipment (WEEE) Directive and implementing regulations, when customers buy new electrical and electronic equipment from Tripp Lite they are entitled to: • Send old equipment for recycling on a one-for-one, like-for-like basis (this varies depending on the country) • Send the new equipment back for recycling when this ultimately becomes waste Tripp Lite has a policy of continuous improvement. Specifications are subject to change without notice. Photos and illustrations may differ slightly from actual products. 1111 W. 35th Street, Chicago, IL 60609 USA • tripplite.com/support 68 20-11-074 93-3BF8_RevB Manual del Propietario Gabinete de Baterías para Autonomía Extendida Modelos: BP240V65, BP240V65-NIB, BP240V65L, BP240V65L-NIB, BP240V100, BP240V100-NIB, BP240V100L, BP240V100L-NIB No es adecuado para aplicaciones móviles. English 1 • Français 137 MÁS DE AÑOS 1111 W. 35th Street, Chicago, IL 60609 EE UU • tripplite.com/support Copyright © 2020 Tripp Lite. Todos los derechos reservados. 69 Índice 1. Introducción 71 1.1 Características 1.2 Tabla de Compatibilidad de UPS y Gabinetes de Baterías 71 72 2. Instrucciones de Seguridad Importantes 73 2.1 2.2 2.3 2.4 73 Advertencias sobre la Instalación y la Ubicación Advertencias sobre la Conexión Advertencias sobre la Batería Cumplimiento de Estándares 5.5 Conexiones del Gabinete de Baterías: Modelos BP240V65L, BP240V65L-NIB, BP240V100L y BP240V100L-NIB 5.5.1 5.5.2 Preparación Transporte Comprobación Mecánica Contenido del Empaque Cableado Interno (Típico) Colocación del Gabinete para Baterías Conexión Eléctrica Comprobación Eléctrica Final 4. Datos Mecánicos 4.1 Mediciones Físicas 41.1 4.1.2 Dimensiones para BP240V65, BP240V65-NIB, BP240V100, BP240V100-NIB Dimensiones para BP240V65L, BP240V65L-NIB, BP240V100L, BP240V100L-NIB 6. Operación y Configuración de 120 Modelos de UPS S3M y Gabinetes de Baterías Cabinets 75 75 75 75 76 76 77 78 6.1 6.2 5.1 Desempaque e Inspección 78 78 78 6.3.1 6.3.2 6.3.3 6.3.4 83 83 84 5.3.1 Tamaños de Cables 85 Pantalla de Inicio del UPS S3M10-20K Configuración Configuración de la Batería Configuración del UPS S3M10-20K-NIB y Optimización de la Carga de los Gabinetes de Baterías BP240V65/V65L y BP240V100/V100L 121 122 123 124 6.3 Configuración del UPS de 25K~ 126 100K para Gabinetes de Baterías Específicos Usando la Pantalla LCD 80 5.2 Selección de la Posición de Instalación 5.3 Cables de Alimentación Compatibilidad de UPS S3M con 120 Gabinetes de Baterías BP240V65 a BP240V100L Operación y Configuración de 121 Modelos de UPS S3M y Gabinetes de Baterías Cabinets 6.2.1 6.2.2 6.2.3 6.2.4 4.2 Requerimientos Físicos (Todos los Modelos) 82 5. Instalación Retire la Cubierta del Bastidor 100 Instalación y Conexión de la Batería 101 5.5.2.1 Instalación y Configuración 105 de la Batería: Modelos BP240V65LNIB, BP240V100L-NIB 5.6 Conexiones de Múltiples de Módulos 116 de Baterías 73 74 74 3. Instalación del Gabinete de Baterías 75 3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 100 6.4 85 Pantalla de Inicio del UPS S3M25-100K Configuración Configuración de la Batería Configuración del UPS S3M25-100K y Optimización de la Carga de los Gabinetes de Baterías BP240V65/V65L y BP240V100/V100L Tabla de Referencia de Configuración 133 para Modelos de Sistemas UPS S3M10-100K y Modelos de Gabinete de Baterías BP240V09K-BP240V100L 5.4 Conexiones del Gabinete de Baterías: 85 Modelos BP240V65, BP240V65-NIB, BP240V100, BP240V100-NIB 7. Especificaciones 5.4.1 Retire la Cubierta del Bastidor 86 5.4.2 Instalación y Conexión de la Batería 86 5.4.2.1 Instalación y Configuración de 90 la Batería: Modelos BP240V65 NIB, BP240V100-NIB 127 127 129 130 135 7.1 Especificaciones del Gabinete de Baterías 135 70 8. Almacenamiento 135 9. Servicio y Garantía 135 1. Introducción Los Gabinetes de Baterías para Autonomía Extendida de Tripp Lite se conectan a Sistemas UPS SmartOnline® para proporcionar respaldo por batería de larga duración para centros de datos, telecomunicaciones, redes, instalaciones industriales, seguridad, sistemas de emergencia y otras aplicaciones de misión crítica que requieran alta capacidad, alta disponibilidad y autonomía extendida. Los gabinetes de baterías están disponibles en siete modelos, con y sin baterías preinstaladas: BP240V65, BP240V65-NIB, BP240V65L, BP240V65L-NIB, BP240V100, BP240V100-NIB, BP240V100L-NIB. Los modelos de gabinete de baterías con sufijo “-NIB” BP240V65-NIB, BP240V65L-NIB, BP240V100-NIB y BP240V40LNIB no incluyen baterías preinstaladas. Sin embargo, incluyen todos los cables puente, fusibles y breakers, permitiendo la flexibilidad para comprar baterías por separado para los gabinetes de baterías. Los gabinetes de baterías BP240V65-NIB y BP240V65L-NIB están diseñados para baterías CSB GP12650i. Los gabinetes de baterías BP240V100-NIB y BP240V100LNIB están diseñados para baterías CSB GP121000. 1.1 Características • Los gabinetes para baterías están diseñados para tensiones de cadenas de baterías de ± 120V CD y capacidades de batería de 65Ah o 100Ah, @ C20 a 1.67VPC. • Los gabinetes de baterías contienen múltiples baterías AGM de 12V CD conectadas en serie para obtener voltajes más altos. • Cada gabinete de baterías contiene varios estantes para alcanzar los voltajes requeridos de la cadena de baterías: o BP240V65 / BP240V65-NIB: Soporta 20 x baterías AGM de 65Ah o BP240V100 y BP240V100-NIB: Soportan 20 x baterías AGM de 100Ah o BP240V65L y BP240V65L-NIB: Soportan 40 x baterías AGM de 65Ah o BP240V100L y BP240V100L-NIB: Soportan 40 x baterías AGM de 100Ah • Una puerta con bisagra y cerradura facilita el acceso a las baterías para el mantenimiento periódico. • Para acceder a las terminales se ha dejado un espacio libre mínimo de 100 mm [4"] encima de las baterías individuales. • El gabinete de baterías está construido de acero de grueso calibre para mayor durabilidad. • Un acabado de pintura en polvo horneada proporciona resistencia a corrosión. • El gabinete de baterías se embarca atornillado a una tarima con una doble capa de envoltura de protección elástica y esquineros integrados y protección en la parte superior. • La ventilación y enfriamiento por convección adecuados de las baterías individuales se proporcionan mediante un espaciado entre las baterías. Las ventilas delanteras y traseras permiten la libre circulación del aire caliente hacia afuera del gabinete de baterías. • Se proporciona un breaker de caja moldeada para protección contra sobrecorriente. • Los cables de salida de energía suministrados por el usuario pueden introducirse en el gabinete de baterías a través de las aberturas para conductos ubicadas en la parte inferior del gabinete. • Para una seguridad mejorada, mayor densidad de potencia y mantenimiento mínimo, los sistemas de gabinete utilizan baterías recombinantes de Plomo Ácido Reguladas por Válvula (VRLA). El electrolito de estas baterías es inmovilizado en un separador de estera absorbente o en un medio gelificante, eliminando riesgos de derrame y requisitos de mantenimiento del electrolito líquido libre. No hay necesidad de agregar agua o medir la densidad. • Ya que las baterías tienen celdas recombinantes que emplean un ciclo de recombinación del oxígeno, se emiten gases mínimos durante la carga de flotación normal. Cada celda contiene una válvula individual, que libera los productos de gas de la sobrecarga y evita la acumulación de la presión dentro de la celda. 71 1. Introducción 1.2 Tabla de Compatibilidad de UPS y Gabinetes de Baterías Gabinetes con Baterías Internas BP240V65 BP240V65L BP240V100 BP240V100L Gabinetes SIN Baterías Internas BP240V65-NIB BP240V65L-NIB BP240V100-NIB BP240V100L-NIB UPS de 10kVA a • S3M10K1B, 20kVA con Baterías S3M10K2B, Internas S3M10K3B • S3M15K2B S3M15K3B • S3M20K3B No No No No UPS de 10kVA a • S3M10K-NIB 20kVA SIN Baterías • S3M15K-NIB Internas • S3M20K-NIB Sí Sí Sí No Gabinetes con Baterías Internas BP240V65 BP240V65L BP240V100 BP240V100L Gabinetes SIN Baterías Internas BP240V65-NIB BP240V65L-NIB BP240V100-NIB BP240V100L-NIB • S3M25K • S3M30K Sí Sí Sí No • S3M50K Sí Sí Sí Sí • S3M60K No Sí Sí Sí • S3M80K • S3M100K No Sí No Sí UPS de 25kVA ~ 100kVA SIN Baterías Internas 72 2. Instrucciones de Seguridad Importantes CONSERVE ESTAS INSTRUCCIONES Todas las secciones de este manual contienen instrucciones y advertencias que deben observarse durante la instalación y la operación del gabinete de batería aquí descrito. Lea TODAS las instrucciones detenidamente antes de mover, instalar o conectar el gabinete de batería. Caso contrario, puede afectar la garantía y causar daños materiales o lesiones físicas graves. ¡PELIGRO! ¡RIESGO LETAL POR ALTO VOLTAJE! El tendido del cableado debe estar a cargo de un electricista calificado, de conformidad con las advertencias descritas en este manual y con todos los códigos de seguridad y eléctricos aplicables. Un cableado incorrecto puede causar lesiones personales graves y daños a la propiedad. 2.1 Advertencias sobre la Instalación y la Ubicación • Instale el gabinete de batería en un ambiente interior controlado, alejado de humedad excesiva, temperaturas extremas, líquidos y gases inflamables, contaminantes conductores, polvo o luz solar directa. • Instale el gabinete de batería en una ubicación nivelada y con estructura firme. • El gabinete de baterías es extremadamente pesado. Tenga cuidado al mover o levantar la unidad. • Opere el gabinete de baterías únicamente a temperaturas interiores entre 0 °C y 40 °C. Para mejores resultados, mantenga la temperatura ambiente a 25 °C. • Deje espacio suficiente en la parte delantera y posterior del gabinete para una ventilación adecuada. No bloquee, cubra ni coloque objetos en las aberturas de ventilación externas del gabinete de baterías. • No coloque objeto alguno sobre el gabinete de batería, especialmente recipientes con líquido. • No intente apilar el gabinete de batería. Si lo hiciera, puede dañarlo de forma definitiva y causar lesiones físicas graves. • No intente desembalar ni mover el gabinete sin asistencia. Use un equipo de manipulación adecuado para soportar el peso y el volumen del gabinete de baterías, como montacargas y gatos mecánicos para tarimas. (Extienda totalmente las horquillas del montacargas debajo de la carga. Abra las horquillas al máximo ancho posible bajo la carga. Levante el gabinete por la base solamente. Use calzado protector). • Para uso en caso de emergencia, instale un extintor certificado para incendios de equipos eléctricos conectados (clasificación clase C o uno exactamente equivalente, con agente extintor no conductor) cerca del gabinete. 2.2 Advertencias sobre la Conexión • El gabinete de batería contiene alto voltaje peligroso que puede causar lesiones físicas o la muerte por descarga eléctrica. • El gabinete tiene su propia fuente de alimentación. Las terminales de salida pueden estar energizadas aún cuando el gabinete no está conectado a un sistema UPS. • El gabinete se debe conectar a tierra conforme a todas las regulaciones de cableado eléctrico aplicables. • No se recomienda el uso de este equipo en aplicaciones de soporte de vida en donde razonablemente se pueda esperar que la falla de este equipo provoque la falla del equipo de soporte de vida o afecte significativamente su seguridad o efectividad. • Desconecte todas las fuentes de alimentación de entrada y salida antes de instalar los cables o realizar conexiones eléctricas. • Use un cable flexible de longitud suficiente para permitir las tareas de servicio del gabinete. • Use casquillos para tapar los cables de terminación y evitar que los extremos deshilachados entren en corto en los bloques de terminales. Use cable con clasificación VW-1, FT-1 o superior. Use manguitos para los cables y abrazaderas para los conectores. • Confirme que todos los cables estén marcados correctamente según su finalidad, polaridad y diámetro. 73 2. Instrucciones de Seguridad Importantes • Tome en cuenta la polaridad correcta siguiendo las marcas de positivo y negativo en la unidad. El hecho de no tomar en cuenta la polaridad correcta puede dañar las baterías y crear un riesgo grave de lesiones personales y daños a la propiedad. • El tendido del cableado y el ensamble deben estar a cargo solamente de electricistas calificados y capacitados. Consulte el Manual del Propietario de la unidad UPS para conocer el tamaño de los cables. 2.3 Advertencias sobre la Batería • El gabinete de baterías requiere mantenimiento de rutina por técnicos calificados que estén familiarizados con en su operación. Deben tomarse todas las precauciones requeridas antes de abrir el gabinete por cualquier motivo. Mantenga al personal no autorizado alejado de las baterías. • El gabinete de batería contiene baterías de plomo ácido recombinantes reguladas con válvula (VRLA). No intente agregar agua a las baterías ni tomar una muestra del peso específico del electrolito. • Las baterías VRLA pueden contener una mezcla explosiva de gas de hidrógeno. NO FUME cerca de las baterías. NO provoque llamas ni chispas cerca de las baterías. Descargue la electricidad estática del cuerpo antes de tocar las baterías. NO abra ni altere las baterías, la emisión de electrolito es dañina para la piel y los ojos, y puede ser tóxica. NO arroje las baterías al fuego—pueden explotar. • Las baterías presentan un riesgo de descarga eléctrica y quemaduras por la alta corriente de cortocircuito. La conexión y reemplazo de la batería debe llevarse a cabo sólo por personal de servicio calificado que observe las precauciones apropiadas. Use herramientas con mangos aislados. Retire relojes, anillos u otros objetos metálicos. Use botas y guantes de hule. No ponga en corto o puentee las terminales de la batería con ningún objeto. No coloque herramientas o partes metálicas sobre la parte superior de las baterías. • Reemplace las baterías por otras equivalentes (mismo número y tipo) que puede comprar en Tripp Lite. • Las baterías son reciclables. Para los requisitos de desecho, consulte los códigos locales. Solo deseche las baterías mediante los canales autorizados en conformidad con todas las regulaciones locales, estatales y nacionales que correspondan. • No conecte ni desconecte las baterías cuando el sistema UPS esté funcionando con suministro de la batería o cuando la unidad no se encuentre en modo de derivación. Desconecte la fuente de carga antes de conectar o desconectar las terminales de la batería. • Si la fuente de carga permanece apagada por un período prolongado, debe encenderse periódicamente para recargar las baterías. Debe encenderse la unidad de carga y recargarse las baterías durante 24 horas ininterrumpidas como mínimo cada 3 meses. Si no se recargan las baterías periódicamente, puede causar daños permanentes a la batería. • Deje que las baterías se carguen durante 24 horas ininterrumpidas después de la instalación. Nota sobre el etiquetado Pueden aparecer estos símbolos en la etiqueta del producto: V : Voltaje de CD : Conexión a Tierra +: Positivo de la Batería – : Negativo de la Batería Consulte en la etiqueta del producto los números de modelo, especificación de voltaje y otra información importante. 2.4 Cumplimiento de Estándares • UL 1778, CSA-C22.2 Nº 107.3-14 (3ª Ed) • ISTA B (Transporte, Vibración, Inclinación) 74 3. Instalación del Gabinete de Baterías Antes de la Instalación Lea la Sección 2 – Instrucciones de Seguridad Importantes 3.1 Preparación • En su instalación, prepárese para descargar el gabinete de baterías del camión de entrega y transportarlo hasta el lugar de instalación final. Tenga en cuenta el peso y dimensiones del paquete. • Asegúrese de que el piso pueda soportar la carga del gabinete de baterías específico que se está instalando. El gabinete debe instalarse en un área estructuralmente firme con un piso nivelado, que pueda soportar el peso del gabinete de baterías y otros equipos que se instalen cerca. • Dibuje un esquema de cableado que represente los cables conectados entre los bloques de terminales de salida del gabinete de baterías y cualquier dispositivo exterior de desconexión, caja de conexiones y/o carga y rectificador. • Si planea almacenar el gabinete por un período prolongado antes de la instalación, siga las instrucciones en la Sección 9. Almacenamiento y Servicio. 3.2 Transporte 1. Inspeccione el o los contenedores de embarque para detectar daños visibles (no retire la envoltura elástica alrededor de la unidad hasta que haya sido transportada hasta el lugar de instalación final). Confirme que el nombre del modelo y la especificación coincidan con la unidad que ordenó. Si usted determina que la unidad ha sufrido daños durante el envío o si algo parece faltar, póngase en contacto con Tripp Lite. No intente utilizar la unidad si ha sido dañada o maltratada. 2. No intente mover o desempacar el gabinete de baterías sin asistencia. Use un equipo de manipulación adecuado para soportar el peso y el volumen del gabinete de baterías, como montacargas y gatos mecánicos para tarimas. (Extienda totalmente las horquillas del montacargas debajo de la carga. Abra las horquillas al máximo ancho posible bajo la carga. Levante el gabinete por la base solamente. Use calzado protector). Confirme que los límites de carga para montacargas, equipos de manejo y pisos a lo largo de la ruta de transporte no sean excedidos por el peso combinado del gabinete de baterías empacado, equipos de manejo y personal. Confirme que la unidad empacada pasará a través de cualquier puerta a lo largo de la ruta prevista. 3. El gabinete de baterías está asegurado con envoltura de plástico elástico para protegerlo durante el transporte y movimiento dentro de una instalación. Retire la envoltura elástica del gabinete de baterías cuando la unidad está en el lugar de instalación final— no antes. 3.3 Comprobación Mecánica Mientras que el sistema de gabinete de baterías se encuentre todavía en la tarima, inspeccione todas las partes para detectar golpes u otros daños. 1. Abra la puerta frontal del gabinete de baterías. 2. Confirme que ninguna de las partes internas (baterías, bloques de terminales, breaker y otras partes) esté dañada. 3. Tenga en cuenta el número de modelo de batería individual y el tipo de terminal que se muestran en la sección 7. Especificaciones. 4. Utilice herramientas aisladas para apretar todas las conexiones de terminales de la batería al valor recomendado mostrado en la tabla en la sección 5.3 Cables de Alimentación. 5. Utilice herramientas aisladas para apretar los cables de las terminales de salida positivas y negativas en el extremo de las baterías al breaker. 75 3. Instalación del Gabinete de Baterías 3.4 Contenido del Empaque Número de Parte Descripción BP240 V65 BP240 V65L BP240 V65NIB BP240 V65LNIB BP240 V100 BP240 V100L BP240 V100NIB BP240 V100LNIB Sí Sí Sí Sí Sí Sí Sí Sí Manual del Propietario 933BF8 Cables para Batería 731891 "Cables de batería para conectar a UPS S3M10-20K" 2 2 2 2 2 No 2 No Aisladores de Batería 83084A/ 83084B Materiales protectores N/A N/A 4/5 8/8 N/A N/A N/A N/A "Lado Inferior del Gabinete Faldones Metálicos" 1038F7A Cubrir el área inferior del gabinete 2 N/A 2 N/A 2 N/A 2 N/A "Lado Inferior del Gabinete Faldones Metálicos" 1038F8A Cubrir el área inferior del gabinete 2 2 2 2 2 2 2 2 "Lado Inferior del Gabinete Faldones Metálicos" 1038F8A Cubrir el área inferior del gabinete N/A 2 N/A 2 N/A 2 N/A 2 Cables de Batería para Modelos "-NIB" Algunos P/N Para conectar las series de baterías al gabinete N/A N/A 10 16 N/A N/A 10 16 Barras para Puentes de Cobre 1038F3 Para interconexión de baterías adyacentes N/A N/A 10 20 N/A N/A N/A N/A Barras para Puentes de Cobre 1038F4 Para interconexión de baterías adyacentes N/A N/A 3 8 N/A N/A N/A N/A Barras para Puentes de Cobre 1038F5 Para interconexión de baterías adyacentes N/A N/A N/A N/A N/A N/A 3 8 Barras para Puentes de Cobre 1038F6 Para interconexión de baterías adyacentes N/A N/A N/A N/A N/A N/A 10 20 3.5 Cableado Interno (Típico) • Los gabinetes de baterías utilizan múltiples baterías de 12V CD conectadas en serie para proporcionar el voltaje de CD nominal de 240V CD (±120V CD). • El cableado interno está dimensionando para las corrientes de carga de la aplicación específica. No use otro tamaño de cable que no sea el proporcionado en el gabinete de baterías. • Cada repisa del gabinete de baterías incluye un diagrama de cableado específico. Refiérase a la sección 6. Instalación para ver detalles de instalación de la batería. • Todos los breakers están en la capa medio del gabinete de baterías. • Todas las polaridades de conexión de carga serán etiquetadas como “+” (positivo de la batería), “-“ (negativo de la batería) y “N” (conexión central de la batería) para series de ±120V CD. • Todos los gabinetes de la batería están provistos de un dispositivo de protección de sobrecorriente de circuito de ramal y pueden conectarse directamente a la carga o al UPS. 3.6 Colocación del Gabinete para Baterías Coloque el gabinete de baterías en un lugar fresco con flujo de aire libre y lejos de fuentes de calor directo. La vida útil y el rendimiento de una batería pueden verse considerablemente afectadas por temperaturas elevadas, disminuyendo en un 50% para cada 8.25 °C por encima de 25 ºC. 1. Prepare la superficie donde se colocará el gabinete. La superficie debe estar limpia, plana y capaz de soportar el gabinete de baterías y otros equipos instalados cerca. Vea la sección 8. Especificaciones para cargas de piso. 76 3. Instalación del Gabinete de Baterías 2. Deje espacio suficiente en la parte delantera y posterior del gabinete para una correcta ventilación y mantenimiento. La puerta frontal debe ser accesible para permitir un fácil acceso a las baterías internas, fusibles internos y otros dispositivos de protección contra sobrecorriente. Para dimensiones y medidas gabinete de baterías, consulte la Sección 6.1 Desempacado e Inspección. 3. Si el gabinete será anclado al suelo, instale tornillos de anclaje adecuados en el orificio situado en la parte inferior del gabinete. Utilice arandelas para crear una superficie plana entre las áreas de instalación alrededor de los tornillos de anclaje. 4. Con mucho cuidado, retire los tornillos que aseguran el gabinete de baterías a la tarima. 5. Las horquillas del montacargas deben estar a la anchura máxima dentro de la abertura del gabinete y completamente introducidas, para evitar que se vuelque. Levante el gabinete por la base solamente. Tenga cuidado de no dañar el piso de lámina metálica del gabinete con las horquillas. 6. Si el gabinete de batería será fijado al suelo, alinee cuidadosamente y baje el gabinete de baterías en los tornillos de anclaje del piso y fíjelo en su lugar. 7. Si el gabinete no se fijará al piso, bájelo en el espacio designado y luego nivélelo con cuñas. La nivelación no afecta el rendimiento, pero alinea el gabinete de batería con otros equipos en la instalación. 3.7 Conexión Eléctrica ¡PELIGRO! ¡RIESGO LETAL POR ALTO VOLTAJE! El tendido del cableado debe estar a cargo de un electricista calificado, de conformidad con las advertencias descritas en este manual y con todos los códigos de seguridad y eléctricos aplicables. Un cableado incorrecto puede causar lesiones personales graves y daños a la propiedad. • El gabinete de baterías está conectada a la carga a través de un breaker CD. Esto permite desconectar la batería de la carga y el cargador para mantenimiento o reparación. • Los breakers de CD en la caja moldeada son aprobados por CE para la protección de circuitos ramales. Si se requiere reemplazarlos, deben usarse componentes aprobador por CE de la misma especificación de voltaje y corriente. • El tamaño de los cables de conexión de carga debe considerar la caída de voltaje máxima permitida, así como la capacidad de amperaje continuo y tasa de amperaje de descarga esperada del gabinete de baterías individual. Se recomienda una caída máxima de 1.5V CD en los cables de conexión de carga. Consulte el Manual del Propietario de la unidad UPS para conocer el tamaño de los cables recomendados. • Consulte todos los códigos locales, estatales y nacionales para el tamaño y especificaciones de cable apropiadas. • Los dispositivos de protección de circuito externo (fusibles o breakers) deben considerar la tasa de descarga de la batería, el cableado a proteger y la corriente de cortocircuito de la batería. Después de ejecutar los procedimientos de instalación en la Sección 6. Instalación, ejecute lo siguiente: 1. Abra la puerta frontal del gabinete de baterías para acceder a los componentes internos. Use un voltímetro digital cuando sea necesario medir los voltajes. 2. Determine si la batería ha sido inadvertidamente conectada a tierra restableciendo el breaker a la posición "On" y mida el voltaje entre la terminal de tierra del gabinete de baterías y el punto de conexión de carga positiva dentro del gabinete. Este voltaje debe medir 0 (cero) VCD. Si el voltaje medido no es cero, determine la causa y corríjala antes de continuar. 3. Regrese el breaker interno a una posición "Off" abierta, como medida de seguridad mientras se conectan los cables de salida. Hacer esto evita daños en caso de que accidentalmente se pongan en corto los cables. 4. La parte superior del gabinete de baterías incluye recortes ciegos para la entrada del cable de conexión de carga. Despeje el orificio apropiado y conecte el conducto o el buje del cable. 5. El breaker del circuito de salida permite cables de hasta 300 mm2. 6. Conecte un cable adecuado a la oreja de conexión a tierra situada en la parte superior del gabinete de baterías. 7. Introduzca los cables positivo y negativo (y “N” central, si así está equipado) desde el switch de desconexión externo abierto o las terminales de cableado de campo de la batería del UPS a través del conducto / buje de cable. Conecte a las terminales de salida respectivas dentro del gabinete de baterías. 77 3. Instalación del Gabinete de Baterías 3.8 Comprobación Eléctrica Final Antes de cerrar cualquier breaker de conexión o switch de desconexión, siga estos pasos de verificación: 1. Verifique que esté correcto el voltaje de salida del gabinete de baterías. 2. Si los gabinetes de baterías serán operados en paralelo, verifique que los voltajes individuales de salida del sistema coincidan dentro de 2V CD. 3. Verifique que el voltaje medido entre cualquier terminal de salida y la tierra del gabinete de baterías sea igual a cero. 4. Si alguno de los pasos de verificación anteriores muestra una irregularidad, determine y corrija la causa antes de continuar. 5. Restaure el breaker a la posición “On”. 4. Datos Mecánicos 4.1 Mediciones Físicas 4.1.1 Dimensiones para BP240V65, BP240V65-NIB, BP240V100, BP240V100-NIB 1200 mm [47.2"] 800 mm [31.5"] 900 mm [35.4”] 78 4. Datos Mecánicos Vista Frontal Vista Lateral 1 4 2 3 5 1 2 3 4 5 Vista Posterior (bloque de terminales sin tapa) Breaker de la Batería Terminal de Batería para UPS de 10kVA ~ 20kVA Terminal de Batería para UPS de 25kVA ~ 60kVA Terminales de Conexión a Tierra Recortes para Cables de la Batería 79 Vista Posterior 4. Datos Mecánicos 4.1.2 Dimensiones para BP240V65L, BP240V65L-NIB, BP240V100L, BP240V100L-NIB 1600 mm [63"] 800 mm [31.5"] 1100 mm [43.30"] 80 4. Datos Mecánicos Vista Frontal Vista Lateral Vista Posterior 1 2 4 3 1 Breaker de la Batería 2 Terminal de Batería para UPS de 10kVA ~ 20kVA 3 Terminal de Batería para UPS de 25kVA ~ 60kVA 4 Terminales de Conexión Vista Posterior (bloque de terminales sin tapa) a Tierra 5 Recortes para Cables de la Batería 5 81 4. Datos Mecánicos 4.2 Requerimientos Físicos (Todos los Modelos) Deje algún espacio alrededor del gabinete para operación y ventilación. 1. Deje al menos 800 mm [31.5"] de espacio en el frente para ventilación. 2. Deje al menos 508 mm [20"] de espacio a la derecha e izquierda para su operación. 3. Deje al menos 508 mm [20"] de espacio en la parte posterior para ventilación. >508 mm [20”] >508 mm [20”] >508 mm [20”] >508 mm [20”] >800 mm [31.5"] 82 5. Instalación Nota: Antes de la instalación, inspeccione la unidad. Cerciórese de que nada se haya dañado dentro del empaque. Conserve el material de empaque original en un lugar seguro para uso futuro. 5.1 Desempacado e Inspección Cualquier daño al empaque debe observarse con el transportista en el momento de la recepción. Retire del empaque el juego de riel, gabinete de baterías y módulos de baterías. Nota: Los módulos de baterías son muy pesados. Tenga cuidado cuando desempaque y levante la unidad para no causar daños. • No incline el módulo de baterías al retirarlo del empaque. • Inspeccione el gabinete de baterías para detectar daños que puedan haber ocurrido como resultado del transporte. Si se encuentran daños, no encienda la unidad. Comuníquese inmediatamente con el distribuidor al que le compró la unidad. • Compruebe los accesorios de acuerdo con la lista de empaque y póngase en contacto con el distribuidor en caso de que falten piezas. 1. Mantenga estable la placa deslizante. Corte y retire las cintas de sujeción. 3. Retire la espuma de empaque y la tarima biselada. 2. Retire la bolsa de plástico y la caja de embarque. 4. Retire los tornillos que aseguran el gabinete a la tarima de embarque. 83 5. Instalación 5. Use un montacargas para levantar el gabinete de baterías de la tarima. 5.2 Selección de Posición de Instalación Seleccione un entorno adecuado para instalar la unidad, a fin de minimizar la posibilidad de daño al sistema de batería y maximizar la vida útil de las baterías. 1. No bloquee la circulación de aire en las aberturas de ventilación de la unidad. 2. Compruebe que las condiciones ambientales del sitio de instalación coincidan con las especificaciones de la unidad para evitar recalentamiento o humedad excesiva. Consulte la sección 4.2 Requerimientos Físicos. 3. No coloque la unidad en un ambiente con polvo o corrosivo, ni cerca de objetos inflamables. 4. La unidad no ha sido diseñada para uso en exteriores. Notas: • Coloque el gabinete de baterías en un entorno limpio y estable. Evite vibraciones, polvo, humedad, gases inflamables, líquidos y corrosivos. • Para ayudar a evitar altas temperaturas en la sala donde esté instalado el UPS, se recomiendan ventiladores extractores y/o sistemas de enfriamiento. • Las baterías deben instalarse en un ambiente en donde la temperatura esté dentro de las especificaciones requeridas. La temperatura es un factor clave para determinar la vida y capacidad de la batería. La temperatura de la batería debe mantenerse entre 20 °C y 25 °C [59 °F y 77 °F]. Mantenga las baterías alejadas de fuentes de calor, áreas de ventilación del aire principal, etc. ¡ADVERTENCIA! Los datos típicos de rendimiento de la batería reflejan una temperatura de operación entre 20 °C y 25 °C [59 °F y 77 °F]. Operar el UPS por encima de este rango reducirá la vida de la batería, mientras que operar el UPS por debajo de este rango reducirá la capacidad de la batería. • Si el UPS no se instalará de inmediato, debe almacenarse en un cuarto sin calor o humedad excesivos. 84 5. Instalación 5.3 Cables de Alimentación El diseño del cable debe cumplir con los voltajes y corrientes proporcionados en esta sección y de acuerdo con los códigos eléctricos locales. ¡ADVERTENCIA! AL ARRANCAR, ASEGÚRESE DE ESTAR ATENTO A LA UBICACIÓN Y OPERACIÓN DE LOS AISLADORES EXTERNOS CONECTADOS AL SUMINISTRO DE ENTRADA Y DERIVACIÓN DEL UPS DEL PANEL DE DISTRIBUCIÓN DE LA ENERGÍA DE LA RED PÚBLICA. REVISE PARA VER SI ESTAS ALIMENTACIONES ESTÁN AISLADAS ELÉCTRICAMENTE Y COLOQUE CUALQUIER SEÑAL DE ADVERTENCIA NECESARIA PARA EVITAR CUALQUIER OPERACIÓN INADVERTIDA 5.3.1 Tamaños de Cables UPS MODEL BP240V65 / BP240V100 BP240V65-NIB / BP240V100-NIB BP240V65L / BP240V100L BP240V65L-NIB / BP240V100L-NIB Tamaños de Cable (Cableado THHW a 75 °C) Entrada de CD Conexión a Tierra Entrada de CD Conexión a Tierra 10kVA* 6 AWG 6 AWG 6 AWG 6 AWG 15kVA* 2 x 6 AWG 2 x 6 AWG 2 x 6 AWG 2 x 6 AWG 20kVA* 2 x 6 AWG 2 x 6 AWG 2 x 6 AWG 2 x 6 AWG 25kVA* 1/0 AWG 2 AWG 1/0 AWG 2 AWG 30kVA* 1/0 AWG 1/0 AWG 1/0 AWG 1/0 AWG 50kVA 2/0 AWG 2/0 AWG 2/0 AWG 2/0 AWG 60kVA 2/0 AWG 2/0 AWG 2/0 AWG 2/0 AWG 80kVA 2/0 AWG*2 2/0 AWG*2 100kVA 2/0 AWG*2 2/0 AWG*2 Recomendado Fuerza de Torsión (Apriete) Anderson Connector (No Torque Parameter) 0kgf.com / 0N•m 450kgf.cm/ 44N•m * Los sistemas UPS S3M10-30K no soportan los modelos de gabinete de baterías BP240V100L/100L-NIB. 5.4 Conexiones del Gabinete de Baterías: Modelos BP240V65, BP240V65-NIB, BP240V100 y BP240V100-NIB El diseño de cada gabinete de baterías incluye cables de conexión de la batería interna, breaker, fusibles y terminales. El gabinete estándar puede contener 20 piezas de baterías de 12V 65Ah 12V 65Ah 12V 100Ah. El sistema de voltaje de CD para todos los gabinetes es de 240VCD con series de baterías internas de ±120V. Las Figuras 5-1 y 5-2 muestran el diseño general del bastidor y vistas de despiece para los modelos BP240V65, BP240V65-NIB, BP240V100 y BP240V100-NIB. Las vistas correspondientes para los modelos BP240V65L, BP240V65L-NIB, BP240V100L y BP240V100L-NIB se muestran en la sección 5.5 Conexiones del Gabinete de Baterías: Modelos BP240V65L, BP240V65L-NIB, BP240V100L y BP240V100L-NIB. Figura 5-1: Bastidor del Gabinete de Baterías BP240V65, BP240V65-NIB, BP240V100 y BP240V100-NIB 85 5. Instalación Figura 5-2: Vista de Despiece del Bastidor, Modelos BP240V65, BP240V65-NIB, BP240V100, BP240V100-NIB 5.4.1 Retire la Cubierta del Bastidor Coloque el gabinete de baterías en posición. Retire los paneles superior, frontal, izquierdo y derecho. Retire la placa de la cubierta derecha e izquierda de la batería y la aleta de la batería para instalar las baterías. 5.4.2 Instalación y Conexión de la Batería Cada grupo de baterías tiene 20 baterías en serie (BAT+, N y BAT-). Coloque las baterías en el gabinete de abajo haca arriba una por una, entonces conecte los cables de batería de acuerdo con los diagramas que siguen. Nota: La polaridad positiva y negativa de la batería no pueden invertirse ni estar en corto circuito. Hacerlo dañará la batería y/o causará lesiones. No toque las terminales positiva y negativa de la batería al mismo tiempo. Antes de reemplazar o retirar las baterías, desconecte el breaker, jale las terminales de la celda y retire los tornillos de la barra del bus de cobre. No seguir las instrucciones podría causar daños al equipo o lesiones personales. La instalación debe consistir en 40 baterías. 86 5. Instalación Capa 3 Grupo positivo 10 piezas Capa 2 Grupo negativo 10 piezas Capa 1 Figura 5-3A: Vista Frontal Fusibles 400A (x2) Breaker de la batería Conector de 25kVA ~ 100kVA Conector de 10kVA ~ 20kVA Figura 5-3B: Vista Posterior 87 5. Instalación La Parte Posterior Capa 3 El Frente La Parte Posterior Capa 2 El Frente La Parte Posterior Capa 1 Nota: Este manual puede descargarse en color en tripplite.com, que muestra los cables con los colores correspondientes: Rojo = Positivo Azul = Borne Central El Frente Negro = Negativo Figura 5-4: Diagrama de Cableado para el Modelo BP240V65 88 5. Instalación La Parte Posterior Capa 3 El Frente La Parte Posterior Capa 2 El Frente La Parte Posterior Capa 1 Nota: Este manual puede descargarse en color en tripplite.com, que muestra los cables con los colores correspondientes: Rojo = Positivo Azul = Borne Central Negro = Negativo El Frente Figura 5-5: Diagrama de Cableado para el Modelo BP240V100 89 5. Instalación 5.4.2.1 Instalación y configuración de la batería: Modelos BP240V65-NIB, BP240V100-NIB 1. Retire todos los tornillos etiquetados 1 (Figuras 5-6A y 5-6B). Figura 5-6A Figura 5-6B 90 5. Instalación 2. Retire las placas superior, lado derecho y lado izquierdo (Figura 5-7). Figura 5-7 3. Retire todos los tornillos de los soportes de retención de la batería y retire los soportes de retención (Figura 5-8). Figura 5-8 91 5. Instalación 4. Instale 8 módulos de baterías en la capa 1 (Figura 5-9: Modelo BP240V65-NIB o Figura 5-10: Modelo BP240V100-NIB). Figura 5-9: Modelo BP240V65-NIB Figura 5-10: Modelo BP240V100-NIB 92 5. Instalación 5. Instale 6 módulos de baterías en la capa 2 (Figura 5-11: Modelo BP240V65-NIB o Figura 5-12: Modelo BP240V100-NIB). Figura 5-11: Modelo BP240V65-NIB Figura 5-12: Modelo BP240V100-NIB 93 5. Instalación 6. Instale 6 módulos de baterías en la capa 3 (Figura 5-13: Modelo BP240V65-NIB o Figura 5-14: Modelo BP240V100-NIB). Figura 5-13: Modelo BP240V65-NIB Figura 5-14: Modelo BP240V100-NIB 94 5. Instalación 7. Reinstale todos los soportes y tornillos de retención de la batería (Figura 5-15: Modelo BP240V65-NIB o Figura 5-16: Modelo BP240V100-NIB). Figura 5-15: Modelo BP240V65-NIB Figura 5-16: Modelo BP240V100-NIB 95 5. Instalación 8. Modelo BP240V65-NIB: Instale barras de bus de cobre (13 piezas) entre baterías adyacentes y los tornillos y postes de inserción de la batería (Figuras 5-17A y 5-17B). Figura 5-17A Figura 5-17B 96 5. Instalación 9. Modelo BP240V100-NIB: Instale barras de bus de cobre (12 piezas) entre baterías adyacentes y los tornillos y postes de inserción de la batería (Figuras 5-18A y 5-18B). Figura 5-18A Figura 5-18B 97 5. Instalación 10. Conecte los cables de la batería 1+ a la barra de bus BAT+ B, Batería 10- a Barra de bus BATN, Batería 11+ a Barra de bus BATN, batería 20- a Barra de bus BAT - y los cables de conexión de capa (Figura 5-19: Modelo BP240V65-NIB o Figura 5-20: Modelo BP240V100-NIB y Figura 5-21). Notas: • Use los esquemas de cableado como referencia para los siguientes conjuntos: Use la Figura 5-4 para BP240V65-NIB Use la Figura 5-5 para BP240V100-NIB • Este manual puede descargarse en color en tripplite.com, que muestra los cables con los colores correspondientes: Rojo = Positivo Azul = Borne Central Negro = Negativo Figura 5-19: Modelo BP240V65-NIB Figura 5-20: Modelo BP240V100-NIB 98 5. Instalación Figura 5-21 11. Vuelva a instalar todas las cubiertas y tornillos (Figura 5-22). Figura 5-22 99 5. Instalación 5.5 Conexiones del Gabinete de Baterías: Modelos BP240V65L, BP240V65L-NIB, BP240V100L y BP240V100L-NIB El diseño de cada gabinete de baterías incluye cables de conexión de la batería interna, breaker, fusibles y terminales. El gabinete estándar puede contener 20 piezas de baterías de 12V 65Ah (12V / 100Ah). Los gabinetes de baterías de larga duración “L” pueden contener 40 piezas de las baterías de 12V 65Ah (12V 100Ah). El sistema de voltaje de CD para todos los gabinetes es de 240VCD con series de baterías internas de ±120V. Las Figuras 5-23 y 5-24 muestran el diseño general del bastidor y vistas de despiece para los modelos BP240V65L, BP240V65LNIB, BP240V100L y BP240V100L-NIB. Las vistas correspondientes para los modelos BP240V65, BP240V65-NIB, BP240V100 y BP240V100-NIB se muestran en la sección 5.4 Conexiones del Gabinete de Baterías: Modelos BP240V65, BP240V65-NIB, BP240V100 y BP240V100-NIB. Figura 5-23: Bastidor de Baterías BP240V65L, BP240V65L-NIB, BP240V100L y BP240V100L-NIB 5.5.1 Retire la Cubierta del Bastidor Coloque la caja de baterías en su ubicación final. Retire los paneles superior, frontal, izquierdo y derecho. Retire las Placas de la cubierta derecha e izquierda del módulo de baterías y los soportes de batería para instalar las series de baterías. Figura 5-24: Vista de Despiece – Modelos BP240V65L, BP240V65L-NIB, BP240V100l, BP240V100L-NIB 100 5. Instalación 5.5.2 Instalación y Conexión de la Batería Las 40 baterías pueden dividirse en dos grupos conectados en paralelo para su uso. Cada grupo tiene 20 baterías en serie (BAT+, N y BAT-). Coloque las baterías en el gabinete de abajo haca arriba una por una, entonces conecte los cables de batería de acuerdo con los diagramas que siguen. Nota: La polaridad positiva y negativa de la batería no pueden invertirse ni estar en corto circuito. Hacerlo dañará la batería y/o causará lesiones. No toque las terminales positiva y negativa de la batería al mismo tiempo. Antes de reemplazar o retirar las baterías, desconecte el breaker, jale las terminales de la celda y retire los tornillos de la barra del bus de cobre. No seguir las instrucciones podría causar daños al equipo o lesiones personales. La instalación debe consistir en 40 baterías. Grupo de Baterías 2 Capa 4 Capa 3 Grupo de Baterías 1 Capa 2 Capa 1 Figura 5-25A: Vista Frontal 101 5. Instalación Fusibles 400A (x2) Breaker de la batería Conector de 25kVA ~ 100kVA Conector de 10kVA ~ 20kVA Figura 5-25B: Vista Posterior 102 5. Instalación La Parte Posterior La Parte Posterior Capa 4 Capa 2 El Frente El Frente La Parte Posterior La Parte Posterior Capa 3 Capa 1 El Frente El Frente Figura 5-26: Diagrama de Cableado para BP240V65L (40 baterías instaladas) Nota: Este manual puede descargarse en color en tripplite.com, que muestra los cables con los colores correspondientes: Rojo = Positivo Azul = Borne Central Negro = Negativo 103 5. Instalación La Parte Posterior La Parte Posterior Capa 4 Capa 2 El Frente El Frente La Parte Posterior La Parte Posterior Capa 3 Capa 1 El Frente El Frente Figura 5-27: Diagrama de Cableado para BP240V100L (40 baterías instaladas) Cuando se complete la instalación y conexión de la batería, use un multímetro u otro instrumento para comprobar si los voltajes entre BAT+ y N, N y BAT- son normales. Si es normal, bloquee la cubierta del bastidor. Nota: Este manual puede descargarse en color en tripplite.com, que muestra los cables con los colores correspondientes: Rojo = Positivo Azul = Borne Central Negro = Negativo 104 5. Instalación 5.5.2.1 Instalación y Configuración de la Batería: Modelos BP240V65L-NIB, BP240V100L-NIB 1. Retire todos los tornillos etiquetados 1 (Figuras 5-28A y 5-28B). Figura 5-28A Figura 5-28B 105 5. Instalación 2. Retire las placas superior, derecha e izquierda (Figura 5-29). Figura 5-29 3. Retire todos los tornillos de los soportes de retención de la batería y retire los soportes de retención (Figura 5-30). Figura 5-30 106 5. Instalación 4. Instale 10 módulos de baterías en la capa 1 (Figura 5-31: Modelo BP240V65L-NIB o Figura 5-32: Modelo BP240V100L-NIB). Figura 5-31: Modelo BP240V65L-NIB Figura 5-32: Modelo BP240V100L-NIB 107 5. Instalación 5. Instale 10 módulos de baterías en la capa 2 (Figura 5-33: Modelo BP240V65L-NIB o Figura 5-34: Modelo BP240V100L-NIB). Figura 5-33: Modelo BP240V65L-NIB Figura 5-34: Modelo BP240V100L-NIB 108 5. Instalación 6. Instale 10 módulos de baterías en la capa 3 (Figura 5-35: Modelo BP240V65L-NIB o Figura 5-36: Modelo BP240V100L-NIB). Figura 5-35: Modelo BP240V65L-NIB Figura 5-36: Modelo BP240V100L-NIB 109 5. Instalación 7. Instale 10 módulos de baterías en la capa 4 (Figura 5-37: Modelo BP240V65L-NIB o Figura 5-38: Modelo BP240V100L-NIB). Figura 5-37: Modelo BP240V65L-NIB Figura 5-38: Modelo BP240V100L-NIB 110 5. Instalación 8. Reinstale todos los soportes y tornillos de retención de la batería (Figura 5-39). Figura 5-39 9. Modelo BP240V65L-NIB: Instale barras de bus de cobre (13 piezas) entre baterías adyacentes y los tornillos y postes de inserción de la batería (Figuras 5-40A y 5-40B). Figura 5-40A 111 5. Instalación Figura 5-40B 10. Modelo BP240V100L-NIB: Instale barras de bus de cobre (12 piezas) entre baterías adyacentes y los tornillos y postes de inserción de la batería (Figuras 5-41A y 5-41B). Figura 5-41A 112 5. Instalación Figura 5-41B 11. Conecte los cables del grupo de baterías 1 batería 1+ a barra de bus BAT+, Batería 10- a barra de bus BATN, Batería 11+ a barra de bus BATN, batería 20- a barra de bus BAT- bus y los cables de conexión de nivel. Conecte la batería del grupo de baterías 2 21+ a la barra de bus BAT+, Batería 30- a barra de bus BATN, Batería 31+ a barra de bus BATN, batería 40- a barra de cobre BAT y los cables de conexión de nivel (Figura 5-42: Modelo BP240V65L-NIB o Figura 5-43: Modelo BP240V100L y Figura 5-44). Notas: • Use los esquemas de cableado como referencia para los siguientes conjuntos: Use la Figura 5-26 para BP240V65L-NIB Use la Figura 5-27 para BP240V100L-NIB • Este manual puede descargarse en color en tripplite.com, que muestra los cables con los colores correspondientes: Rojo = Positivo Azul = Borne Central Negro = Negativo Figura 5-42: Modelo BP240V65L-NIB 113 5. Instalación Figura 5-43: Modelo BP240V100L-NIB Figura 5-44 114 5. Instalación 12. Vuelva a instalar todas las cubiertas y tornillos (Figura 5-45). Figura 5-45 115 5. Instalación 5.6 Conexiones de Múltiples de Módulos de Baterías ¡PRECAUCIÓN! Asegure la polaridad correcta de la conexión de la serie de baterías. No mezcle baterías con capacidades diferentes o marcas diferentes o baterías nuevas y viejas. ¡ADVERTENCIA! ASEGURE LA POLARIDAD CORRECTA DE LAS CONEXIONES DEL EXTREMO DE LA CADENA AL BREAKER DE LA BATERÍA Y DEL BREAKER DE LA BATERÍA A LAS TERMINALES DEL UPS (ES DECIR (+) A (+) / (-) A (-) / (N) A (N)). DESCONECTE UNO O MÁS ENLACES DE CELDA DE LA BATERÍA EN CADA NIVEL. NO VUELVA A CONECTAR ESTOS ENLACES Y NO CIERRE EL BREAKER DE LA BATERÍA A MENOS QUE TODAS LAS CONEXIONES ESTÉN CORRECTAMENTE REVISADAS Y APROBADAS. UPS Gabinete de Baterías Figura 5-46: Conexión de BP240V65L y BP240V65L-NIB para UPS de 10kVA, 15kVA y 20kVA 116 5. Instalación UPS Gabinete de Baterías Figura 5-47: Conexión de BP240V65L y BP240V65L-NIB para UPS de 25kVA y 30kVA 117 5. Instalación UPS Gabinete de Baterías Figura 5-48: Conexión de BP240V65L, BP240V65L-NIB, BP240V100L o BP240V100L-NIB para sistemas UPS de 50kVA y 60kVA 118 5. Instalación UPS Gabinete de Baterías Figura 5-49: Conexión de BP240V65L, BP240V65L-NIB, BP240V100L o BP240V100L-NIB para UPS de 80kVA y 100kVA 119 6. O  peración y Configuración de Modelos de UPS S3M y Gabinetes de Baterías 6.1 C  ompatibilidad de UPS S3M con Gabinetes de Baterías BP240V65 a BP240V100L Gabinetes con Baterías Internas BP240V65 BP240V65L BP240V100 BP240V100L Gabinetes SIN Baterías Internas BP240V65-NIB BP240V65L-NIB BP240V100-NIB BP240V100L-NIB UPS de 10kVA a • S3M10K1B, 20kVA con Baterías S3M10K2B, Internas S3M10K3B • S3M15K2B S3M15K3B • S3M20K3B No No No No UPS de 10kVA a • S3M10K-NIB 20kVA SIN Baterías • S3M15K-NIB Internas • S3M20K-NIB Sí Sí Sí No Gabinetes con Baterías Internas BP240V65 BP240V65L BP240V100 BP240V100L Gabinetes SIN Baterías Internas BP240V65-NIB BP240V65L-NIB BP240V100-NIB BP240V100L-NIB • S3M25K • S3M30K Sí Sí Sí No • S3M50K Sí Sí Sí Sí • S3M60K No Sí Sí Sí • S3M80K • S3M100K No Sí No Sí UPS de 25kVA ~ 100kVA SIN Baterías Internas 120 6. O  peración y Configuración de Modelos de UPS S3M y Gabinetes de Baterías 6.2 C  onfiguración del UPS de 10K ~ 20K para Gabinetes de Baterías Específicos Usando la Pantalla LCD ¡PRECAUCIÓN! La configuración para la mayoría de los parámetros no puede cambiarse cuando el UPS está en modo de inversor. 6.2.1 Pantalla de Inicio del UPS S3M10-20K 121 6. O  peración y Configuración de Modelos de UPS S3M y Gabinetes de Baterías 6.2.2 Configuración Haga click en el ícono de Configuración para ingresar dos niveles de configuración. La configuración básica es para la configuración del usuario y la configuración avanzada es sólo para el personal técnico. Póngase en contacto con su administrador para ingresar a la configuración avanzada. Configuración Avanzada: Haga click en Configuración Avanzada e ingrese la contraseña correcta. La contraseña de usuario es “191210”. 122 6. O  peración y Configuración de Modelos de UPS S3M y Gabinetes de Baterías 6.2.3 Configuración de la Batería Haga click en Configuración de la Batería 123 6. O  peración y Configuración de Modelos de UPS S3M y Gabinetes de Baterías 6.2.4 Configuración del UPS S3M10-20K-NIB y Optimización de la Carga de los Gabinetes de Baterías BP240V65/V65L y BP240V100/V100L Paso 1: Configuración del Grupo de Baterías La Cantidad del Grupo de Baterías es 1 para cada juego de 20 baterías que estén en el modelo del UPS o conectadas al modelo del UPS. Por ejemplo, el UPS modelo S3M20K-NIB no tiene baterías internas y es el Grupo de Baterías 1 de forma predeterminada para cualquier modelo de UPS. Sin embargo, para conectar un gabinete BP240V65 con 20 baterías internas al S3M20K-NIB, el UPS S3M20K-NIB debe permanecer configurado para el Grupo de Baterías 1 (un juego de 20 baterías). Sin embargo, para conectar un segundo BP240V65 al UPS S3M20K-NIB, el Grupo de Baterías del UPS debe ser 2 (dos juegos de 20 baterías). Obtenga el número de Grupo de Baterías basado en la combinación de modelos de UPS S3M y Gabinete de Baterías específicos de la tabla debajo de la Sección 6.4. El valor puede ser de 1 a 8. El valor predeterminado es 1 para modelos de UPS S3M sin baterías internas. Paso 2: Configuración del Número de Baterías El número de baterías debe permanecer en 20 para todos los UPS modelo S3M10-100K cuando se conecten con gabinetes de baterías externas de Tripp Lite diseñados para la serie de UPS de la Serie S3M. Paso 3: Configuración de la Capacidad de Una Sola Batería (Ah) Cambie la capacidad de una sola batería (Ah) a la capacidad de Ah individual para una batería individual, como sigue, para los modelos específicos de gabinete de baterías: • BP240V09 y BP240V09K: La Capacidad de Una Sola Batería (Ah) es 9 • BP240V40 y BP240V40L: La Capacidad de Una Sola Batería (Ah) es 40 • BP240V65 y BP240V65L: la La Capacidad de Una Sola Batería (Ah) es 65 • BP240V100 y BP240100L: la La Capacidad de Una Sola Batería (Ah) es 100 Los valores pueden ser de 7 ~ 2000. Desplácese a la siguiente pantalla presionando la flecha hacia abajo. 124 6. O  peración y Configuración de Modelos de UPS S3M y Gabinetes de Baterías Paso 4: Configuración de la Corriente Máxima de Carga La Corriente Máxima de Carga es la corriente de carga estimada que utilizará el UPS para cargar las baterías. Obtenga la corriente máxima de carga estimada recomendada en base a la combinación específica de UPS S3M y modelo de gabinete de baterías de la tabla en la Sección 6.4. Voltaje en Flotación y Elevación: El UPS está configurado de fábrica para voltajes adecuados en flotación (2.27V/celda, 13.62V/batería) y elevación (2.35V/celda, 14.1V/batería). Voltaje en flotación de celda: l valor del voltaje en flotación puede ser de 2.23 ~ 2.30 V/celda. El valor predeterminado es 2.27 V/celda. Voltaje en elevación de celda: El valor de voltaje ecualizado de la batería puede ser de 2.30 ~ 2.40 V/celda. El valor predeterminado es 2.35 V/celda. Paso 5: Configuración de la Duración Promedio de Carga (min) La configuración de la duración promedio de carga en minutos es una estimación de la duración del cargador de elevación para cargar baterías nuevas a una capacidad del 90% a 25 °C. Obtenga el número de Duración de Carga Promedio recomendado (Prom) (min) basado en la combinación específica de UPS S3M y gabinete de baterías de la tabla en la sección 6.4. Tenga en cuenta que las duraciones recomendadas de carga de elevación de la batería son estimaciones basadas solamente en baterías nuevas. Estos números pueden cambiar con la edad de las baterías y la temperatura ambiente de la batería. Para cambiar la Duración Promedio de Carga, presione directamente en el valor de 240 predeterminado en la pantalla. •La duración promedio de carga (Prom) es el límite de tiempo de carga de elevación de la batería. El valor puede ser de 1 ~ 999 min. El valor predeterminado es de 240 (4 horas). Voltaje de la Batería EOD: El fin del voltaje de descarga es el corte de bajo voltaje de las baterías durante una operación en modo de respaldo por batería. El valor puede ser de 1.60 ~ 1.90. El valor predeterminado es 1.67V/celda o 10.02VCD por batería. Coeficiente de Compensación de Temperatura en Flotación: Modifica el voltaje de compensación después de activar el switch. El valor puede ser de 0.001 ~ 0.007v/celda/°C. El valor predeterminado es de 0.003v/celda/°C. Configuración de Carga de Elevación: La carga de elevación puede configurarse como Inactiva o Activa. El valor predeterminado es Activa. Advertencia de Sin Batería: Mantenga activa esta alarma si desea que el UPS proporcione una advertencia cuando No haya baterías presentes. El valor predeterminado es Alarma. 125 6. O  peración y Configuración de Modelos de UPS S3M y Gabinetes de Baterías 6.3 C  onfiguración del UPS de 25K ~ 100K para Gabinetes de Baterías Específicos Usando la Pantalla LCD ¡PRECAUCIÓN! La configuración para la mayoría de los parámetros no puede cambiarse cuando el UPS está en modo de inversor. 126 6. O  peración y Configuración de Modelos de UPS S3M y Gabinetes de Baterías 6.3.1 Pantalla de Inicio del UPS S3M25-100K 6.3.2 Configuración Haga click en el ícono de Configuración para ingresar dos niveles de configuración. La configuración básica es para la configuración del usuario y la configuración avanzada es sólo para el personal técnico. Póngase en contacto con su administrador para ingresar a la configuración avanzada. Configuración Avanzada: Haga click en Configuración Avanzada e ingrese la contraseña correcta. La contraseña de usuario es “191210”. 127 6. O  peración y Configuración de Modelos de UPS S3M y Gabinetes de Baterías 128 6. O  peración y Configuración de Modelos de UPS S3M y Gabinetes de Baterías 6.3.3 Configuración de la Batería Haga click en BATT Setup [Configuración de Batería] Temperatura de Flotación. Compen.: La configuración de compensación del sensor de temperatura puede cambiarse para activar cuando se conecte un sensor de temperatura de la batería al puerto posterior RJ45 del sistema UPS. Selección del Sensor de Temperatura: Configure el tipo de sensor de temperatura en NTC para uno solo y distancias cortas. Configure el tipo de sensor de temperatura en RS485 para varios y distancias grandes. 129 6. O  peración y Configuración de Modelos de UPS S3M y Gabinetes de Baterías 6.3.4 Configuración del UPS S3M25-100K y Optimización de la Carga de los Gabinetes de Baterías BP240V65/V65L y BP240V100/V100L Paso 1: Configuración del Grupo de Baterías La Cantidad del Grupo de Baterías es 1 para cada juego de 20 baterías que estén en el modelo del UPS o conectadas al modelo del UPS. Por ejemplo, el UPS modelo S3M100K no tiene baterías internas y es el Grupo de Baterías 1 de forma predeterminada. Sin embargo, para conectar un gabinete BP240V100L con 40 baterías internas al S3M100K, el UPS S3M100K debe configurarse a Grupo de Baterías 2. Para conectar un segundo gabinete BP240V100L al UPS S3M100K, el Grupo de Baterías debe configurarse en 4 (cuatro juegos de 20 baterías). Obtenga el número de Grupo de Baterías basado en la combinación de modelos de UPS S3M y Gabinete de Baterías específicos de la tabla debajo de la Sección 6.4. El valor puede ser de 1 a 8. El valor predeterminado es 1 para modelos de UPS S3M sin baterías internas. Paso 2: Configuración del Número de Baterías El número de baterías debe permanecer en 20 para todos los UPS modelo S3M10-100K cuando se conecten con gabinetes de baterías externas de Tripp Lite diseñados para la serie de UPS de la Serie S3M. Paso 3: Configuración de la Capacidad de Una Sola Batería (Ah) Cambie la Capacidad de Una Sola Batería (Ah) a la capacidad de Ah individual para una batería individual, como sigue, para el modelo específico de gabinete de baterías: • BP240V40 y BP240V40L: La Capacidad de Una Sola Batería (Ah) es 40 • BP240V65 y BP240V65L: La Capacidad de Una Sola Batería (Ah) es 65 • BP240V100 y BP240V100L: La Capacidad de Una Sola Batería (Ah) es 100 Los Valores de Una Sola Batería (Ah) pueden ser de 7 ~ 2000. Desplácese a la siguiente pantalla presionando la flecha hacia abajo. 130 6. O  peración y Configuración de Modelos de UPS S3M y Gabinetes de Baterías Paso 4: Configuración de coeficiente de limitación de corriente de carga (C) El límite de corriente de carga es un múltiplo de la capacidad de la batería. Se usa para establecer el límite de tiempo de carga de elevación de la batería. El valor puede ser 0.05 ~ 0.25 y es 0.25 de forma predeterminada. Obtenga el coeficiente de limitación (C) de corriente (cur) de carga (Chg) basado en la combinación de UPS S3M y gabinete de baterías específicos de la tabla en la Sección 6.4. Voltaje en Flotación y Elevación: El UPS está configurado de fábrica para voltajes adecuados en flotación (2.27V/celda, 13.62V/batería) y elevación (2.35V/celda, 14.1V/batería). Voltaje en flotación de celda: l valor del voltaje en flotación puede ser de 2.23 ~ 2.30 V/celda. El valor predeterminado es 2.27 V/celda. Voltaje en elevación de celda: El valor de voltaje ecualizado de la batería puede ser de 2.30 ~ 2.40 V/celda. El valor predeterminado es 2.35 V/celda. Paso 5: Configuración de la Duración Promedio de Carga (min) La configuración de la duración promedio de carga en minutos es una estimación de la duración del cargador de elevación para cargar baterías nuevas a una capacidad del 90% a 25 °C. Obtenga el número de Duración de Carga Promedio recomendado (Prom) (min) basado en la combinación específica de UPS S3M y gabinete de baterías de la tabla en la sección 6.4. Tenga en cuenta que las duraciones recomendadas de carga de elevación de la batería son estimaciones basadas solamente en baterías nuevas. Estos números pueden cambiar con la edad de las baterías y la temperatura ambiente de la batería. Para cambiar la Duración Promedio de Carga, presione directamente en el valor de 240 predeterminado en la pantalla. • La duración promedio de carga (Prom) es el límite de tiempo de carga de elevación de la batería. El valor puede ser de 1 ~ 999 min. El valor predeterminado es de 240 (4 horas). 131 6. O  peración y Configuración de Modelos de UPS S3M y Gabinetes de Baterías Voltaje de la Batería EOD: El fin del voltaje de descarga es el corte de bajo voltaje de las baterías durante una operación en modo de respaldo por batería. El valor puede ser de 1.60 ~ 1.90. El valor predeterminado es 1.67V/celda o 10.02VCD por batería. Coeficiente de Compensación de Temperatura en Flotación: Modifica el voltaje de compensación después de activar el switch. El valor puede ser de 0.001 ~ 0.007v/celda/°C. El valor predeterminado es de 0.003v/celda/°C. Configuración de Carga de Elevación: La carga de elevación puede configurarse como Inactiva o Activa. El valor predeterminado es Activa. Advertencia de Sin Batería: Mantenga activa esta alarma si desea que el UPS proporcione una advertencia cuando No haya baterías presentes. El valor predeterminado es Activa. 132 6. O  peración y Configuración de Modelos de UPS S3M y Gabinetes de Baterías 6.4 Tabla de Referencia de Configuración para Modelos de Sistemas UPS S3M10-100K y Modelos de Gabinete de Baterías BP240V09K-BP240V100L Configuraciones para UPS S3M10K-NIB, S3M15K-NIB, S3M20K-NIB sin baterías internas Módulos de Baterías Baterías Cantidad de Paso 1 Paso 2 Paso 3 Gabinetes Grupo de Número Capacidad de Baterías Baterías de Baterías de Una Sola Batería Paso 4 Paso 5 Máxima Corriente de Carga (A) Duración Promedio de Carga (min) Tiempo (minutos) para Cargar Baterías al 90% a 25 °C BP240V65 20 x 65Ah 1 1 20 65 9.75 500 BP240V65 20 x 65Ah 2 2 20 65 19.5 500 BP240V65 20 x 65Ah 3 3 20 65 20 720 BP240V65L 40 x 65Ah 1 2 20 65 19.5 500 BP240V65L 40 x 65Ah 2 4 20 65 20 960 BP240V100 20 x 100Ah 1 1 20 100 15 500 Configuraciones para S3M25K y S3M30K Módulos de Baterías Baterías Cantidad de Gabinetes de Baterías Paso 1 BP240V65 20x 65Ah BP240V65 BP240V65 Paso 2 Paso 3 Paso 4 Paso 5 Grupo de Número Capacidad Baterías de Baterías de Una Sola Batería Coeficiente de Limitación de Corriente de Carga (C) Duración Promedio de Carga (min) Tiempo (minutos) para Cargar Baterías al 90% a 25 °C 1 1 20 65 0.15 540 20 x 65Ah 2 2 20 65 0.15 540 20 x 65Ah 3 3 20 65 0.1 900 BP240V65L 40 x 65Ah 1 2 20 65 0.15 540 BP240V65L 40 x 65Ah 2 4 20 65 0.07 999 BP240V100 20 x 100Ah 1 1 20 100 0.15 540 Configuraciones para S3M50K y S3M60K Módulos de Baterías Baterías Cantidad de Gabinetes de Baterías Paso 1 Paso 4 Paso 5 Grupo de Número Capacidad Baterías de Baterías de Una Sola Batería BP240V65 Paso 2 Paso 3 Coeficiente de Limitación de Corriente de Carga (C) Duración Promedio de Carga (min) Tiempo (minutos) para Cargar Baterías al 90% a 25 °C 20 x 65Ah 1 1 20 65 0.15 540 BP240V65 20 x 65Ah 2 2 20 65 0.15 540 BP240V65 20 x 65Ah 3 3 20 65 0.15 540 BP240V65L 40 x 65Ah 1 2 20 65 0.15 540 BP240V65L 40 x 65Ah 2 4 20 65 0.15 540 BP240V65L 40 x 65Ah 3 6 20 65 0.1 840 BP240V100 20 x 100Ah 1 1 20 100 0.15 540 BP240V100 20 x 100Ah 2 2 20 100 0.15 540 BP240V100 20 x 100Ah 3 3 20 100 0.13 540 BP240V100L 40 x 100Ah 1 2 20 100 0.15 540 BP240V100L 40 x 100Ah 2 4 20 100 0.1 840 133 6. O  peración y Configuración de Modelos de UPS S3M y Gabinetes de Baterías Configuraciones para S3M80K Módulos de Baterías Baterías Cantidad de Paso 1 Gabinetes de Baterías Paso 2 Paso 3 Paso 4 Paso 5 Grupo de Número Baterías de Baterías Capacidad de Una Sola Batería Coeficiente Duración Promedio de Carga de Limitación (min) Tiempo (minutos) para de Corriente Cargar Baterías al 90% a 25 °C de Carga (C) BP240V65 20 x 65Ah 1 1 20 65 0.15 540 BP240V65 20 x 65Ah 2 2 20 65 0.15 540 BP240V65 20 x 65Ah 3 3 20 65 0.15 540 BP240V65L 40 x 65Ah 1 2 20 65 0.15 540 BP240V65L 40 x 65Ah 2 4 20 65 0.15 540 BP240V65L 40 x 65Ah 3 6 20 65 0.15 540 BP240V100 20 x 100Ah 1 1 20 100 0.15 540 BP240V100 20 x 100Ah 2 2 20 100 0.15 540 BP240V100 20 x 100Ah 3 3 20 100 0.15 540 BP240V100L 40 x 100Ah 1 2 20 100 0.15 540 BP240V100L 40 x 100Ah 2 4 20 100 0.15 540 BP240V100L 40 x 100Ah 3 6 20 100 0.1 840 Paso 1 Paso 2 Paso 3 Paso 4 Paso 5 Grupo de Número Baterías de Baterías Capacidad de Una Sola Batería Coeficiente Duración Promedio de Carga de Limitación (min) Tiempo (minutos) para de Corriente Cargar Baterías al 90% a 25 °C de Carga (C) Configuraciones para S3M100K Módulos de Baterías Baterías Cantidad de Gabinetes de Baterías BP240V65 20 x 65Ah 1 1 20 65 0.15 540 BP240V65 20 x 65Ah 2 2 20 65 0.15 540 BP240V65 20 x 65Ah 3 3 20 65 0.15 540 BP240V65L 40 x 65Ah 1 2 20 65 0.15 540 BP240V65L 40 x 65Ah 2 4 20 65 0.15 540 BP240V65L 40 x 65Ah 3 6 20 65 0.15 540 BP240V100 20 x 100Ah 1 1 20 100 0.15 540 BP240V100 20 x 100Ah 2 2 20 100 0.15 540 BP240V100 20 x 100Ah 3 3 20 100 0.15 540 BP240V100L 40 x 100Ah 1 2 20 100 0.15 540 BP240V100L 40 x 100Ah 2 4 20 100 0.15 540 BP240V100L 40 x 100Ah 3 6 20 100 0.13 540 134 7. Especificaciones 7.1 Especificaciones del Gabinete de Baterías Voltaje Nominal de CD: ± 120V CD, 240V CD Módulo de baterías Dimensión An x Pr x Al Peso BP240V65 (-NIB) BP240V100 (-NIB) [31.5" x 35.4" x 47.2"] 800 x 900 x 1200 mm 275.8 kg [608 lb]* 421.8 kg [930 lb]* BP240V65L (-NIB) BP240V100L (-NIB) [31.5" x 43.3" x 63"] 800 x 1100 x 1600 mm 491.2 kg [1083 lb]* 742.5 kg [1637 lb]* Breaker 1x 250A 1x 600A Fusible 2x 400A 4x 400A *Los modelos con sufijo -NIB no incluyen baterías internas, de modo que su peso total varía en función de las baterías instaladas por el usuario final. 8. Almacenamiento El gabinete de batería debe almacenarse en un ambiente limpio y seguro con una temperatura inferior a 40 °C [104 °F] y una humedad relativa inferior al 90% (sin condensación). De ser posible, almacene el gabinete de baterías en su contenedor de embarque original. Cargue las baterías por lo menos 24 horas antes de usarlas. No confíe en el el gabinete de baterías para proporcionar energía de respaldo hasta que las baterías estén completamente cargadas. Nota: Si el sistema UPS permanece apagado por un período prolongado, deberá encenderse periódicamente para permitir recargar las baterías. Debe encenderse el UPS y recargarse las baterías por un período de al menos 24 horas ininterrumpidas cada 3 meses. El no cargar las baterías periódicamente puede causar un daño irreversible a la batería. 9. Servicio y Garantía Servicio Su producto Tripp Lite está cubierto por la garantía descrita en este manual. También están disponibles una gran variedad de Programas de Garantía Extendida y Servicio En Sitio por parte de Tripp Lite. Para más información sobre el servicio, visite tripplite.com/support. Antes de devolver su producto para servicio, siga estos pasos: 1.  Revise los procedimientos de instalación y operación en este manual para cerciorarse de que el problema de servicio no se debe a una mala lectura de las instrucciones. 2. Si el problema persiste, no se ponga en contacto con el distribuidor ni le devuelva el producto. En su lugar, visite tripplite.com/support. 3.  Si el problema requiere de servicio, visite tripplite.com/support y haga click en el enlace Devolución de productos. Desde aquí usted puede solicitar un número de Autorización de Devolución de Mercancía [RMA] que se requiere para el servicio. Esta sencilla forma en línea solicitará los números de modelo y serie de su unidad junto con otra información general del comprador. El número de RMA junto con las instrucciones de embarque le serán enviadas por correo electrónico. Cualquier daño (directo, indirecto, especial o consecuencial) al producto incurrido durante el embarque a Tripp Lite o un Centro de Servicio Autorizado de Tripp Lite no está cubierto bajo la garantía. Los productos embarcados a Tripp Lite o un Centro de Servicio Autorizado de Tripp Lite deben tener los cargos del transporte prepagados. Marque el número de RMA en el exterior del empaque. Si el producto está dentro del período de garantía, adjunte una copia de su recibo de venta. Regrese el producto para servicio usando un transportista asegurado a la dirección que se le proporcionó cuando solicitó la RMA. 135 9. Servicio y Garantía Garantía Limitada El vendedor garantiza este producto, si se usa de acuerdo con todas las instrucciones aplicables, de que está libre de defectos en material y mano de obra por un período de un (1) año a partir de la fecha de compra inicial. Si el producto resultara defectuoso en material o mano de obra dentro de ese período, el vendedor reparará o reemplazará el producto a su entera discreción. El servicio cubierto por esta garantía incluye partes y mano de obra en un centro de servicio de Tripp Lite. En Tripp Lite están disponibles planes de servicio en sitio a través de socios de servicio autorizados (en la mayoría de las áreas). Para detalles, visite tripplite.com/support. Los clientes internacionales deben ponerse en contacto con el soporte de Tripp Lite en [email protected]. ESTA GARANTÍA NO SE APLICA AL DESGASTE NORMAL O A LOS DAÑOS QUE RESULTEN DE ACCIDENTES, USO INCORRECTO, USO INDEBIDO O NEGLIGENCIA. EL VENDEDOR NO OTORGA GARANTÍAS EXPRESAS DISTINTAS A LA ESTIPULADA EN EL PRESENTE. SALVO EN LA MEDIDA EN QUE LO PROHÍBAN LAS LEYES APLICABLES, TODAS LAS GARANTÍAS IMPLÍCITAS, INCLUIDAS TODAS LAS GARANTÍAS DE COMERCIALIZACIÓN O IDONEIDAD, ESTÁN LIMITADAS EN CUANTO A DURACIÓN AL PERÍODO DE GARANTÍA ESTABLECIDO; ASIMISMO, ESTA GARANTÍA EXCLUYE EXPRESAMENTE TODOS LOS DAÑOS INCIDENTALES E INDIRECTOS. (Algunos estados no permiten limitaciones en cuanto dura una garantía y algunos estados no permiten la exclusión de limitación de daños incidentales o indirectos, de modo que las limitaciones anteriores pueden no aplicar para usted. Esta Garantía le otorga derechos legales específicos y es posible que usted goce de otros derechos que pueden variar de una jurisdicción a otra). Tripp Lite; 1111 W. 35th Street; Chicago IL 60609; EE UU ADVERTENCIA: antes de usarlo, cada usuario debe tener cuidado al determinar si este dispositivo es adecuado o seguro para el uso previsto. Ya que las aplicaciones individuales están sujetas a gran variación, el fabricante no garantiza la adecuación de estos dispositivos para alguna aplicación específica. Números de Identificación de Conformidad Regulatoria Para el propósito de certificaciones e identificación de cumplimiento normativo, su producto Tripp Lite ha recibido un número de serie exclusivo. El número de serie se puede encontrar en la etiqueta de placa de identificación, junto con todas las marcas e información requeridas de aprobación. Al solicitar información de conformidad para este producto, refiérase siempre al número de serie. El número de serie no debe confundirse con el nombre de la marca o el número de comercialización del producto. Información de Cumplimiento con WEEE para Clientes y Recicladores de Tripp Lite (Unión Europea) Conforme a la Directiva de Residuos de Equipos Eléctricos y Electrónicos [WEEE] y regulaciones aplicables, cuando los clientes adquieren un equipo eléctrico y electrónico nuevo de Tripp Lite están obligados a: • Enviar el equipo viejo para fines de reciclaje bajo la modalidad de uno por uno, semejante por semejante (esto varía de un país a otro) • Enviar el equipo nuevo para reciclaje una vez que finalmente sea un desecho Tripp Lite tiene una política de mejora continua. Las especificaciones están sujetas a cambio sin previo aviso. Las fotografías e ilustraciones pueden diferir ligeramente de los productos reales. MÁS DE AÑOS 1111 W. 35th Street, Chicago, IL 60609 EE UU • tripplite.com/support 136 20-11-074 93-3BF8_RevB Manuel de l'utilisateur Armoire de batteries pour un fonctionnement prolongé Modèles : BP240V65, BP240V65-NIB, BP240V65L, BP240V65L-NIB, BP240V100, BP240V100-NIB, BP240V100L, BP240V100L-NIB Ne convient pas aux applications mobiles. English 1 • Español 69 1111 W. 35th Street, Chicago, IL 60609 USA • tripplite.com/support Droits d'auteur © 2020 Tripp Lite. Tous droits réservés. 137 Table des matières 1. Introduction 139 1.1 Caractéristiques 139 1.2 Tableau de compatibilité de 140 l’onduleur et de l’armoire de batteries 2. Consignes de sécurité importantes 141 2.1 2.2 2.3 2.4 Avertissements concernant l’installation et l’emplacement Avertissements concernant les connexions Conformité aux normes 141 141 142 142 3. Installation de l’armoire de batteries 143 3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 Préparation Transport Vérification mécanique Contenu de l’emballage Câblage interne (typique) Placement de l’armoire de batteries Connexion électrique Vérification électrique finale 4. Données mécaniques 4.1 Mesures physiques 4.1.1 4.1.2 Dimensions pour BP240V65, BP240V65-NIB, BP240V100, BP240V100-NIB Dimensions pour BP240V65L, BP240V65L-NIB, BP240V100L, BP240V100L-NIB 143 143 143 144 145 145 145 145 147 147 147 149 4.2 Exigences physiques (tous les modèles) 151 5. Installation 5.1 Déballage et inspection 5.2 Sélection de la position d’installation 5.3 Câbles d’alimentation 5.3.1 Tailles des câbles 5.5 Connexions de l’armoire de batteries Modèles BP240V65L, BP240V65L-NIB, BP240V100L, BP240V100L-NIB 169 5.5.1 Retirer la coque du châssis 5.5.2 Installation des batteries et Connexion 5.5.2.1 Installation et configuration des batteries : modèles BP240V65L-NIB, BP240V100L-NIB 169 170 174 5.6 Connexions de plusieurs modules de batteries 6. Fonctionnement et configuration 189 des modèles d’onduleur S3M et des armoires de batteries 6.1 6.2 Compatibilité des onduleurs S3M 189 avec les armoires de batteries de BP240V65 à BP240V100L Configuration des onduleurs de 10 à 190 20K pour des armoires de batteries spécifiques en utilisant l’écran ACL 6.2.1 6.2.2 6.2.3 6.2.4 Écran d’accueil de l’onduleur S3M10-20K Réglages Réglage des batteries Configuration de l’onduleur S3M10-20K-NIB et optimisation du chargement des armoires de batteries BP240V65/V65L et BP240V100/V100L 190 191 192 193 6.3 Configuration des onduleurs de 25 196 à 100K pour des armoires de batteries spécifiques en utilisant l’écan ACL 6.3.1 6.3.2 152 6.3.3 152 6.3.4 153 154 154 Écran d’accueil de l’onduleur S3M25-100K196 Réglages 197 Configuration des batteries 199 Configuration de l’onduleur S3M25200 100K et l’optimisation du chargement des armoires de batteries BP240V65/ V65L et BP240V100/V100L 6.4 Tabla de Referencia de Configuración 5.4 Connexions de l’armoire de batteries 154 para Modelos de Sistemas UPS Modèles BP240V65, BP240V65-NIB, S3M10-100K y Modelos de Gabinete BP240V100, BP240V100-NIB de Baterías BP240V09K-BP240V100L 5.4.1 Retirer la coque du châssis 5.4.2 Installation des batteries et Connexion 5.4.2.1 Installation et configuration des batteries : modèles BP240V65-NIB, BP240V100-NIB 185 155 155 7. Caractéristiques 159 techniques 7.1 Caracteristiques techniques des armoires de batteries 203 205 203 8. Entreposage 205 9. Service et garantie 206 138 1. Introduction Les armoires de batteries pour fonctionnement prolongé de Tripp Lite se connectent aux onduleurs SmartOnline® pour fournir une alimentation de secours de longue durée à partir des batteries pour les centres de données, les télécommunications, les réseaux, les installations industrielles, la sécurité, les systèmes d'urgence et autres applications critiques qui exigent une haute capacité, une haute disponibilité et un fonctionnement prolongé. Les armoires de batteries sont offertes en sept modèles, avec ou sans batteries préinstallées : BP240V65, BP240V65-NIB, BP240V65L, BP240V65L-NIB, BP240V100, BP240V100-NIB, BP240V100L-NIB. Les modèles d'armoires de batteries avec le suffixe « -NIB » BP240V65-NIB, BP240V65L-NIB, BP240V100-NIB et BP240V40L-NIB n'incluent pas de batteries préinstallées. Cependant, ils incluent tous les câbles de raccordement, les fusibles et les disjoncteurs, offrant la flexibilité d'acheter des batteries séparément pour les armoires de batteries. Les armoires de batteries BP240V65-NIB et BP240V65L-NIB sont conçues pour des batteries CSB GP12650i. Les armoires de batteries BP240V100-NIB et BP240V100L-NIB sont conçues pour des batteries CSB GP121000. 1.1 Caractéristiques • Les armoires de batteries sont conçues pour un ensemble de batteries avec un tension de ± 120 V CC et des batteries avec une capacité de 65 Ah ou 100 Ah, @ C20 jusqu'à 1,67 VPC. • Les armoires de batteries contiennent plusieurs batteries AGM de 12 V CC connectées en série pour atteindre des tensions plus élevées. • Chaque armoire de batteries contient plusieurs étagères pour atteindre les tensions d'ensemble de batteries requises : o BP240V65/BP240V65-NIB : peut accueillir 20 x batteries AGM de 65 Ah o BP240V100/BP240V100-NIB : peut accueillir 20 x batteries AGM de 100 Ah o BP240V65L/BP240V65L-NIB : peut accueillir 40 x batteries AGM de 65 Ah o BP240V100L/BP240V100L-NIB : peut accueillir 40 x batteries AGM de 100 Ah • Une porte à charnières verrouillable facilite l'accès aux batteries pour l'entretien périodique. • Un espace libre d'au moins 100 mm (4 po) est présent au-dessus des batteries individuelles pour permettre l'accès aux bornes. • L'armoire de batteries est fabriquée en acier épais pour une bonne durabilité. • Le fini en poudre cuite offre une résistance à la corrosion. • L'armoire de batteries est expédiée boulonnée à une palette avec une double couche de film de protection étirable et une protection des coins et du dessus intégrée. • Une ventilation appropriée et un refroidissement par convection des batteries individuelles sont fournis par de l'espace entre les batteries. Les évents avant et arrière permettent la libre circulation de l'air chaud hors de l'armoire de batteries. • Un disjoncteur à boîtier moulé est fourni pour une protection contre les surcharges. • Les câbles de sortie de puissance fournis par l’utilisateur peuvent être introduits dans l’armoire de batterie par des entrées défonçables intégrées au bas de l’armoire. • Pour une meilleure sécurité, une densité de puissance supérieure et un entretien minimum, les systèmes d'armoire utilisent des batteries recombinantes au plomb-acide à valves. L'électrolyte dans ces batteries est immobilisé dans un séparateur composé d'un paillasson absorbant ou d'un produit gélifiant, éliminant les risques de déversement et les exigences en matière d'entretien de l'électrolyte sous forme de liquide libre. Il n'est pas nécessaire d'ajouter de l'eau ou de mesurer une gravité spécifique. • Parce que les batteries sont des éléments recombinants qui utilisent un cycle de recombinaison d'oxygène, une quantité minimale de gaz est émise pendant le chargement normal de maintien. Chaque élément contient une soupape individuelle qui libère les produits du gaz des surcharges et prévient l'accumulation de pression dans l'élément. 139 1. Introduction 1.2 Tableau de compatibilité de l'onduleur et de l'armoire de batteries Armoires avec batteries internes BP240V65 BP240V65L BP240V100 BP240V100L Armoires SANS batteries internes BP240V65-NIB BP240V65L-NIB BP240V100-NIB BP240V100L-NIB Onduleurs 10 kVA-20 kVA avec batteries internes • S3M10K1B, S3M10K2B, S3M10K3B • S3M15K2B, S3M15K3B • S3M20K3B Non Non Non Non Onduleurs 10 kVA-20 kVA sans batterie interne • S3M10K-NIB • S3M15K-NIB • S3M20K-NIB Oui Oui Oui Non Armoires avec batteries internes BP240V65 BP240V65L BP240V100 BP240V100L Armoires SANS batteries internes BP240V65-NIB BP240V65L-NIB BP240V100-NIB BP240V100L-NIB • S3M25K • S3M30K Oui Oui Oui Non • S3M50K Oui Oui Oui Oui • S3M60K Non Oui Oui Oui • S3M80K • S3M100K Non Oui Non Oui Onduleurs de 25 kVA à 100 kVA SANS batteries internes 140 2. Consignes de sécurité importantes CONSERVER CES INSTRUCTIONS. Toutes les sections de ce manuel contiennent des instructions et des avertissements qui doivent être respectés lors de l'installation et du fonctionnement de l'armoire de batteries décrite dans ce manuel. Lire attentivement TOUTES les instructions avant de tenter de déplacer, d'installer ou de connecter l'armoire de batteries. Le non-respect de ces avertissements peut avoir une incidence sur la garantie et causer des dommages graves à la propriété ou des blessures. DANGER! DANGER MORTEL, HAUTE TENSION! Tout le câblage doit être effectué par un électricien qualifié en conformité avec les avertissements se trouvant dans ce manuel, avec tous les codes de sécurité et de l'électricité applicables. Un câblage incorrect risque de causer des dommages graves à la propriété ou des blessures. 2.1 Avertissements concernant l'installation et l'emplacement • Installer l'armoire de batteries dans un environnement intérieur contrôlé, à l'écart de l'humidité, des températures extrêmes, des liquides et des gaz inflammables, des contaminants conducteurs, de la poussière et de la lumière directe du soleil. • Installer l'armoire de batteries dans un endroit au niveau, solidement construit. • L'armoire de batteries est extrêmement lourde. Faire preuve de prudence au moment de déplacer ou de soulever l'appareil. • Utiliser l'armoire de batteries à des températures intérieures entre 0 °C et 40 °C seulement. Pour de meilleurs résultats, maintenir une température ambiante interne de 25 °C. • Laisser un espace adéquat autour de l'avant et l'arrière de l'armoire de batteries pour permettre une ventilation appropriée. Ne pas bloquer, couvrir ou insérer des objets dans les ouvertures de ventilation externes de l'armoire de batteries. • Ne placer aucun objet sur l'armoire de batteries, en particulier des récipients contenant un liquide. • Ne pas essayer d'empiler l'armoire de batteries. Tenter d'empiler l'armoire de batteries pourrait causer des dommages permanents et créer un potentiel de sévices graves à la personne. • Ne pas tenter de déballer ou de déplacer l'armoire de batteries sans aide. Utiliser de l'équipement de manutention approprié pouvant supporter le poids et l'encombrement de l'armoire de batteries, comme un monte-charge, un transpalette et un chariot élévateur à fourche. (Déplier complètement les fourches sous la charge. Écarter les fourches le plus possible sous la charge. Soulever l'armoire à partir du bas seulement. Porter des chaussures de sécurité.) • Pour des situations d'urgence, installer un extincteur conçu pour les incendies d'équipement électrique alimenté (de classe C ou l'équivalent exact, avec un agent d'extinction non conducteur) à proximité de l'armoire de batteries. 2.2 Avertissements concernant les connexions • L'armoire de batteries contient des hautes tensions dangereuses qui ont le potentiel de causer des blessures ou la mort par électrocution. • L'armoire de batteries contient sa propre source d'énergie. Les bornes de sortie peuvent être sous tension même lorsque l'armoire de batteries n'est pas connectée à un onduleur. • L'armoire de batteries doit être correctement mise à la terre conformément à toutes les réglementations sur le câblage électrique. • Il n'est pas recommandé d'utiliser cet équipement pour des appareils de survie où une défaillance de cet équipement peut, selon toute vraisemblance, entraîner la défaillance de l’appareil de maintien de la vie ou nuire de façon majeure à sa sécurité ou à son efficacité. • Désactiver toutes les sources d'alimentation d'entrée et de sortie avant d'installer les câbles ou de faire les connexions électriques. • Utiliser un câble flexible de longueur suffisante pour permettre l'entretien de l'armoire de batteries. • Utiliser des capuchons à ferrules pour couvrir l'extrémité des câbles et d'empêcher les extrémités effilochées de court-circuiter les blocs de jonction. Utiliser du câblage coté VW-1, FT-1 ou supérieur. Utiliser des manchons de câble et des coquilles d'accouplement. 141 2. Consignes de sécurité importantes • Confirmer que tous les câbles sont marqués correctement en fonction de leurs fins, leur polarité et leur diamètre. • Respecter une polarité appropriée en observant les indications des bornes positive et négative sur l’appareil. Le non-respect d’une bonne polarité pourrait endommager les batteries et créer un risque sérieux de dommages à la propriété et de blessures. • Le câblage et l'assemblage doivent être confiés uniquement à un électricien formé et qualifié. Consulter le manuel de l'utilisateur de l'onduleur pour le dimensionnement des câbles. 2.3 Avertissements concernant les batteries • L'armoire de batteries nécessite un entretien de routine par du personnel d'entretien qualifié et compétent connaissant bien son fonctionnement. Prendre toutes les précautions requises avant d'ouvrir l'armoire pour quelque raison que ce soit. Garder le personnel non autorisé à l'écart des batteries. • L'armoire de batteries contient des batteries au plomb-acide à régulation par soupape (VRLA). Ne pas tenter d'ajouter de l'eau à ces batteries ou d'effectuer un échantillonnage de la gravité spécifique de l'électrolyte. • Les batteries VRLA peuvent contenir un mélange explosif de gaz hydrogène. NE PAS FUMER à proximité des batteries. NE PAS provoquer de flammes ou d'étincelles à proximité des batteries. Décharger l'électricité statique du corps avant de toucher les batteries. NE PAS ouvrir ou endommager les batteries — les électrolytes dégagés sont dangereux pour la peau et les yeux et peuvent être toxiques. NE PAS jeter de batteries dans le feu — elles risqueraient d'exploser. • Les batteries peuvent présenter un risque de décharge électrique et de brûlures par des courants de court-circuit élevés. La connexion ou le remplacement des batteries ne devrait être effectué que par du personnel d'entretien qualifié tenant compte des mesures de sécurité appropriées. Utiliser des outils ayant des poignées isolées. Enlever les montres, les bagues ou tout autre objet métallique. Porter des gants et des bottes en caoutchouc. Ne pas créer de court-circuit ou de pont entre les bornes de la batterie avec un objet quelconque. Ne pas déposer d'outils ou de pièces métalliques sur les batteries. • Remplacer les batteries avec des batteries équivalentes (de même type et de même numéro) disponibles chez Tripp Lite. • Les batteries sont recyclables. Se reporter aux codes locaux pour les exigences en ce qui a trait à l'élimination. Ne pas éliminer les batteries sauf au moyen d'un canal approuvé conformément à toutes les réglementations locales, de l'État et nationales applicables. • Ne pas connecter ou déconnecter les batteries lorsque l'onduleur est alimenté par batteries ou lorsque l'appareil ne se trouve pas en mode de dérivation. Débrancher la source de chargement avant de brancher ou débrancher les bornes des batteries. • Si la source de chargement demeure hors tension pendant une période prolongée, il est recommandé de la mettre périodiquement sous tension pour permettre aux batteries de se recharger. La source de chargement doit être mise sous tension et les batteries doivent être rechargées pendant une période ininterrompue d'au moins 24 heures tous les 3 mois. Si les batteries ne sont pas rechargées périodiquement, cela risque de causer des dommages permanents aux batteries. • Permettre le chargement des batteries sans interruption pendant 24 heures suivant l'installation. Remarque concernant l'étiquetage Ces symboles peuvent figurer sur l'étiquette du produit : V : tension CC : Masse + : positif de la batterie – : négatif de la batterie Consulter l'étiquette du produit pour les numéros de modèles, les valeurs nominales de tension et autres informations importantes. 2.4 Conformité aux normes UL 1778, CSA-C22.2 No. 107.3-14 (3e édition) ISTA B (transport, vibration, inclinaison) 142 3. Installation de l'armoire de batteries Lire la Section 2 – Consignes de sécurité importantes avant l'installation 3.1 Préparation • Sur le site, se préparer à décharger l'armoire de batteries du camion de livraison et à la transporter vers l'emplacement d'installation final. Prendre en considération le poids et les dimensions de l'emballage. • S'assurer que le plancher peut supporter la charge de l'armoire de batteries spécifique étant installée. L'armoire de batteries doit être installée dans un endroit solidement construit dont le plancher est au niveau qui est capable de supporter le poids de l'armoire de batteries et tout autre équipement qui sera installé à proximité. • Dessiner un schéma de câblage représentant les câbles connectés entre les blocs de jonction de sortie de l'armoire de batteries et tout dispositif de déconnexion externe, boîte de connexion et/ou charge/redresseur. • S'il est prévu que l'armoire de batteries soit entreposée pendant une période prolongée avant ou après l'installation, suivre les instructions de la section 9. Entreposage et entretien 3.2 Transport 1. Inspecter le ou les conteneurs d'expédition pour la présence de dommages visibles (ne pas retirer le film étirable autour de l'appareil avant son transport vers l'emplacement d'installation final). Confirmer que le nom du modèle et les valeurs nominales correspondent à l'appareil commandé. S'il est déterminé que l'appareil a été endommagé durant l'expédition ou si quelque chose semble manquer, contacter Tripp Lite pour obtenir de l'aide. Ne pas tenter d'utiliser l'appareil s'il a été endommagé ou manipulé de façon inappropriée. 2. Ne pas tenter de déballer ou de déplacer l'armoire de batteries sans aide. Utiliser de l'équipement de manutention approprié pouvant supporter le poids et l'encombrement de l'armoire de batteries, comme un monte-charge, un transpalette et un chariot élévateur à fourche. (Déplier complètement les fourches sous la charge. Écarter les fourches le plus possible sous la charge. Soulever l'armoire à partir du bas seulement. Porter des chaussures de sécurité.) Confirmer que les limites de charge pour le monte-charge, l'équipement de manutention et les planchers le long de l'itinéraire de transport n'excèdent pas le poids combiné de l'armoire de batteries emballée, de l'équipement de manutention et du personnel. Confirmer que l'appareil emballé passera à travers les portes le long de l'itinéraire prévu. 3. L'armoire de batteries est retenue avec du film étirable pour la protéger pendant l'expédition et le déplacement à l'intérieur de l'installation. Enlever le film étirable de l'armoire de batteries une fois que l'appareil se trouve dans son emplacement d'installation final — et non pas avant. 3.3 Vérification mécanique Pendant que le système de batteries de l'armoire assemblée se trouve toujours sur la palette d'expédition, inspecter tous les côtés à la recherche d'impact ou de tout autre dommage. 1. Ouvrir la porte avant de l'armoire de batteries. 2. Confirmer qu'aucune pièce interne (batteries, bloc de jonction, disjoncteur et autres pièces) n'est endommagée. 3. Prendre en note le numéro de modèle individuel des batteries et le type de borne illustrés dans la section 7. Caractéristiques techniques. 4. Utiliser des outils ayant des poignées isolées pour serrer toutes les connexions des bornes des batteries au couple recommandé illustré dans le tableau de la section 5.3 Câbles d'alimentation. 5. Utiliser des outils ayant des poignées isolées pour serrer les câbles des bornes de sortie positives et négatives des batteries de la fin au disjoncteur. 143 3. Installation de l'armoire de batteries 3.4 Contenu de l’emballage Numéro de pièce Description BP240 V65 BP240 V65L BP240 V65-NIB BP240 V65L-NIB BP240 V100 BP240 V100L BP240 V100-NIB BP240 V100L-NIB Manuel de l'utilisateur 933BF8 Oui Oui Oui Oui Oui Oui Oui Oui Câbles des batteries 731891 2 2 2 2 2 Non 2 Non S.O. S.O. 4/5 8/8 S.O. S.O. S.O. S.O. Isolateurs des batteries Câbles des batteries à connecter à S3M10-20K UPS 83084A/ Matériel de 83084B protection Côté inférieur de l'armoire Jupes en métal 1038F7A Couvrent la partie inférieure de l'armoire 2 S.O. 2 S.O. 2 S.O. 2 S.O. Côté inférieur de l'armoire Jupes en métal 1038F8A Couvrent la partie inférieure de l'armoire 2 2 2 2 2 2 2 2 Côté inférieur de l'armoire Jupes en métal 1038F8A Couvrent la partie inférieure de l'armoire S.O. 2 S.O. 2 S.O. 2 S.O. 2 Câbles des batteries pour les modèles «-NIB» Plusieurs Pour connecter N/P les ensembles de batteries à l'armoire S.O. S.O. 10 16 S.O. S.O. 10 16 Barres de raccordement en cuivre 1038F3 S.O. S.O. 10 20 S.O. S.O. S.O. S.O. Barres de raccordement en cuivre 1038F4 S.O. S.O. 3 8 S.O. S.O. S.O. S.O. Barres de raccordement en cuivre 1038F5 S.O. S.O. S.O. S.O. S.O. S.O. 3 8 Barres de raccordement en cuivre 1038F6 S.O. S.O. S.O. S.O. S.O. S.O. 10 20 Pour l’interconneion de batteries adjacentes Pour l’interconneion de batteries adjacentes Pour l'interconneion de batteries adjacentes Pour l’interconneion de batteries adjacentes 144 3. Installation de l'armoire de batteries 3.5 Câblage interne (typique) • Les armoires de batteries utilisent plusieurs batteries de 12 V CC connectées en série pour fournir une tension nominale CC de 240 V CC (±120 V CC). • Le câblage interne est dimensionné pour des courants de charge spécifiques à l'application. Ne pas utiliser un câble de toute autre taille que celui fourni dans l'armoire de batteries. • Chaque étagère de l'armoire de batteries inclut un schéma de câblage spécifique. Consulter la section 6. Installation pour des détails sur l'installation des batteries. • Tous les disjoncteurs se trouvent dans la section intermédiaire de l'armoire de batteries. • Les polarités de toutes les connexions de la charge seront étiquetées « + » (positif de la batterie), « - » (négatif de la batterie) et « N » (partie centrale de la batterie) pour des chaînes CC de ±120 V. • Toutes les armoires de batteries sont fournies avec un dispositif de protection contre les surcharges du circuit de dérivation et peuvent être câblées directement à la charge ou à l'onduleur. 3.6 Placement de l'armoire de batteries Placer l'armoire de batteries dans un endroit frais où l'air circule librement et à l'écart des sources de chaleur directes. La durée de vie utile et le rendement d'une batterie peuvent être fortement touchées par une température élevée, réduits de 50 % pour chaque 8,25 °C au-dessus de 25 °C. 1. Préparer la surface de l'endroit où l'armoire sera placée. La surface doit être propre, plane et capable de supporter l'armoire de batteries et le reste de l'équipement installé à proximité. Consulter la section 8. Spécifications pour les charges au plancher. 2. Laisser un espace libre adéquat autour de l'avant et l'arrière de l'armoire de batteries pour la ventilation et l'entretien. La porte avant doit être accessible pour permettre un accès facile aux batteries internes, aux fusibles internes et aux dispositifs de protection contre les surcharges. Consulter la section 6.1 Déballage et inspection pour les dimensions et les mesures de l'armoire de batteries. 3. Si l'armoire est ancrée au sol, installer des boulons d'ancrage appropriés dans le trou de montage qui se trouve dans la partie inférieure de l'armoire. Utiliser des rondelles pour créer une surface au niveau entre les zones de montage et les boulons d'ancrage. 4. En procédant avec soin, retirer les boulons retenant l'armoire de batteries à la palette d'expédition. 5. Les fourches du chariot élévateur à fourche doivent être écartées le plus possible dans l'ouverture de dégagement de l'armoire et complètement insérées pour prévenir le renversement. Soulever l'armoire à partir du bas seulement. Prendre soin de ne pas endommager le plancher en tôle de l'armoire avec les fourches. 6. Si l'armoire de batteries est fixée au sol, aligner soigneusement l'armoire de batteries et l'abaisser sur les boulons d'ancrage du sol, puis la fixer en place. 7. Si l'armoire n'est pas fixée au sol, l'abaisser dans l'espace désigné, puis la mettre au niveau en utilisant les cales. La mise à niveau ne nuit pas au rendement, mais permet d'aligner l'armoire de batteries avec le reste de l'équipement dans l'installation. 3.7 Connexion électrique DANGER! DANGER MORTEL, HAUTE TENSION! Tout le câblage doit être effectué par un électricien qualifié en conformité avec les avertissements se trouvant dans ce manuel, avec tous les codes de sécurité et de l'électricité applicables. Un câblage incorrect risque de causer des dommages graves à la propriété ou des blessures. • L'armoire de batteries est connectée à la charge au moyen d'un disjoncteur CC. Cela permet de déconnecter la batterie depuis la charge et le chargeur pour l'entretien et/ou la réparation. • Les disjoncteurs à boîtier moulé CC sont homologués CE pour la protection du circuit de dérivation. Si un remplacement est requis, utiliser des composants homologués CE avec la même tension et intensité nominale. • Le dimensionnement des câbles de connexion doit prendre en considération la chute de tension maximale permise de même que la capacité continue en ampères des câbles et le taux de décharge anticipé en ampères de l'armoire de batteries individuelle. Une chute de tension maximale de 1,5 V CC dans les câbles de connexion de la charge est recommandée. Consulter le manuel de l'utilisateur de l'onduleur pour le dimensionnement des câbles recommandé. 145 3. Installation de l'armoire de batteries • Se référer à tous les codes locaux, nationaux et de l'État applicables pour le dimensionnement et les valeurs nominales appropriés pour les câbles. • Les dispositifs de protection du circuit externe (fusibles ou disjoncteurs) doivent prendre en considération le taux de décharge de la batterie, le câblage à protéger et le courant du court-circuit CC de la batterie. Après avoir effectué les procédures d'installation de la section 5. Installation, effectuer ce qui suit : 1. Ouvrir la porte avant de l'armoire de batteries pour accéder aux composants internes. Utiliser un voltmètre numérique lorsque des mesures de la tension doivent être prises. 2. Déterminer si la batterie a été mise à la masse par inadvertance en réinitialisant le disjoncteur en position « On » (marche) et en mesurant la tension entre la patte de mise à la masse de l'armoire de batteries et le point de connexion de charge positive dans l'armoire. Cette tension devrait mesurer 0 (zéro) V CC. Si la tension mesurée n'est pas zéro, déterminer la cause et apporter une correction avant de continuer. 3. Remettre le disjoncteur interne en position « Off » (arrêt) comme mesure de précaution pendant la connexion des câbles de sortie. Une telle mesure permet d'empêcher les dommages si les câbles sont accidentellement court-circuités. 4. Le dessus de l'armoire de batteries inclut des entrées défonçables pour l'entrée du câble de connexion de la charge. Défoncer l'entrée défonçable appropriée, puis raccorder le conduit ou la bague du câble. 5. Le disjoncteur de sortie accueille des câbles jusqu'à 300 mm2. 6. Raccorder un câble de mise à la masse de l'équipement approprié à la patte de mise à la masse qui se trouve sur le dessus de l'armoire de batteries. 7. Acheminer les câbles positif et négatif (et le centre « N », le cas échéant) de l'interrupteur général externe ouvert ou les bornes du câblage de champ de la batterie de l'onduleur à travers la bague du conduit/câble. Raccorder les bornes de sorties respectives à l'intérieur de l'armoire de batteries. 3.8 Vérification électrique finale Avant de fermer un disjoncteur de connexion ou un interrupteur général, effectuer les étapes de vérification suivantes : 1. Vérifier que la tension de sortie de l'armoire de batteries est correcte. 2. Si les armoires de batteries fonctionnent en parallèle, vérifier que les tensions de sorties individuelles du système correspondent à 2 V CC. 3. Vérifier que la tension mesurée entre la borne de sortie et la masse de l'armoire de batterie est zéro. 4. Si l'une ou l'autre des vérifications ci-dessus révèle une irrégularité, déterminer et corriger la cause avant de continuer. 5. Remettre le disjoncteur à la position « On » (marche). 146 4. Données mécaniques 4.1 Mesures physiques 4.1.1 Dimensions pour BP240V65, BP240V65-NIB, BP240V100, BP240V100-NIB 1 200 mm (47,2 po) 800 mm (31,5 po) 900 mm (35,4 po) 147 4. Données mécaniques vue avant vue latérale vue arrière 1 4 2 3 5 1 2 3 4 5 Vue arrière (bloc de jonction sans couvercle) Disjoncteur de batterie Borne de batterie pour onduleur de 10 kVA à 20 kVA Borne de batterie pour onduleur de 25 kVA à 60 kVA Pattes de mise à la masse Entrées défonçables du câble des batteries 148 4. Données mécaniques 4.1.2 Dimensions pour BP240V65L, BP240V65L-NIB, BP240V100L, BP240V100L-NIB 1 600 mm (63 po) 800 mm (31,5 po) 1 100 mm (43,4 po) 149 4. Données mécaniques vue avant vue latérale vue arrière 1 2 4 3 1 Disjoncteur de batterie 2 Borne de batterie pour onduleur de 10 kVA à 20 kVA 3 Borne de batterie pour onduleur de 25 kVA à 60 kVA 4 Pattes de mise à la masse 5 Entrées défonçables du câble des batteries Vue arrière (bloc de jonction sans couvercle) 5 150 4. Données mécaniques 4.2 Exigences physiques (tous les modèles) Laisser de l'espace autour de l'armoire pour le fonctionnement et la ventilation. 1. Laisser au moins 800 mm (31,5 po) d'espace à l'avant pour la ventilation. 2. Laisser au moins 500 mm (20 po) d'espace à droite et à gauche pour le fonctionnement. 3. Laisser au moins 500 mm (20 po) d'espace à l'arrière pour la ventilation. >500 mm (20 po) >500 mm (20 po) >500 mm (20 po) >500 mm (20 po) >800 mm (31,5 po) 151 5. Installation Remarque : Avant l'installation, inspecter l'appareil. S'assurer que rien à l'intérieur de l'emballage n'est endommagé. Conserver le matériel d'emballage original dans un lieu sûr pour utilisation future. 5.1 Déballage et inspection Tout dommage à l'emballage doit être pris en note avec le transporteur chargé de la livraison au moment de la réception. Retirer l'ensemble de rail, le boîtier des batteries et les modules de batteries de l'emballage. Remarque : Les modules de batteries sont très lourds. Faire preuve de prudence au moment de déballer et de soulever l'appareil pour éviter les blessures. • Ne pas incliner le module de batteries en le retirant de l'emballage. • Inspecter l'armoire de batteries pour la présence de dommages qui auraient pu survenir pendant le transport. Si des dommages sont présents, ne pas mettre l'appareil sous tension. Contacter immédiatement le fournisseur chez qui l'appareil a été acheté. • Vérifier les accessoires par rapport au bordereau d'expédition, puis contacter le fournisseur si des pièces sont manquantes. 1. Tenir fermement la plaque coulissante. Couper, puis retirer les rubans de ligature. 3. Retirer la mousse d'emballage et la palette biseautée. 2. Retirer le sac en plastique et la boîte d'expédition. 4. Retirer les boulons retenant l'armoire à la palette d'expédition. 152 5. Installation 5. Utiliser un chariot élévateur pour soulever l'armoire de batteries de la palette. 5.2 Sélection de la position d'installation Sélectionner un environnement approprié où installer l'appareil afin de minimiser la possibilité de dommages au système de batteries et maximiser la durée de vie des batteries. 1. Ne pas bloquer le débit d'air vers les ouvertures de ventilation de l'appareil. 2. S'assurer que les conditions environnementales du lieu d'installation sont conformes aux caractéristiques techniques de l'appareil afin d'éviter la surchauffe et l'excès d'humidité. Consulter la section 4.2 Exigences physiques. 3. Ne pas placer l'appareil dans un environnement poussiéreux ou corrosif ou à proximité d'objets inflammables. 4. L'appareil n'est pas conçu pour être utilisé à l'extérieur. Remarques : • Placer l'armoire de batteries dans un endroit propre et stable. Éviter les vibrations, la poussière, l'humidité, les gaz inflammables, les liquides et les matières corrosives. • Pour aider à prévenir les températures élevées dans la pièce où l'onduleur est installé, il est recommandé d'utiliser des ventilateurs d'évacuation et/ou des systèmes de refroidissement. • Les batteries doivent être montées dans un endroit où la température se situe à l'intérieur des spécifications requises. La température est un facteur clé pour déterminer la durée de vie et la capacité des batteries. La température des batteries doit être maintenue entre 20 et 25 °C (59 et 77 °F). Garder les batteries à l'écart des sources de chaleur, des principales zones de ventilation d'air, etc. AVERTISSEMENT! Les données sur la performance typique des batteries indiquent une température de fonctionnement entre 20 et 25 °C (59 et 77 °F). L'utilisation de l'onduleur au-dessus de cette plage réduira la durée de vie des batteries, tandis que l'utilisation de l'onduleur en deçà de cette plage réduira la capacité des batteries. • Si l'onduleur n'est pas installé immédiatement, il doit être entreposé dans une pièce exempte de chaleur ou d'humidité excessive. 153 5. Installation 5.3 Câbles d'alimentation La conception des câbles doit être conforme aux tensions et aux courants fournis dans cette section et en conformité avec les codes locaux de l'électricité. AVERTISSEMENT! S'ASSURER DE PRENDRE CONNAISSANCE DE L'EMPLACEMENT ET DU FONCTIONNEMENT DES ISOLATEURS EXTERNES QUI SONT CONNECTÉS À LA SOURCE D'ENTRÉE/DE DÉRIVATION DE L'ONDULEUR DANS LE PANNEAU DE DISTRIBUTION DU SECTEUR. VÉRIFIER SI CES SOURCES SONT ISOLÉES ÉLECTRIQUEMENT, PUIS AFFICHER TOUT SIGNE D'AVERTISSEMENT NÉCESSAIRE POUR PRÉVENIR TOUT FONCTIONNEMENT ACCIDENTEL. 5.3.1 Tailles des câbles Modèle du système ASC BP240V65 / BP240V100 BP240V65-NIB / BP240V100-NIB BP240V65L / BP240V100L* BP240V65L-NIB / BP240V100L-NIB* Tailles des câbles (câblage THHW à 75 °C) Entrée CC Mise à la terre Entrée CC Mise à la terre 10kVA* 6 AWG 6 AWG 6 AWG 6 AWG 15kVA* 2 x 6 AWG 2 x 6 AWG 2 x 6 AWG 2 x 6 AWG 20kVA* 2 x 6 AWG 2 x 6 AWG 2 x 6 AWG 2 x 6 AWG 25kVA* 1/0 AWG 2 AWG 1/0 AWG 2 AWG 30kVA* 1/0 AWG 1/0 AWG 1/0 AWG 1/0 AWG 50kVA 2/0 AWG 2/0 AWG 2/0 AWG 2/0 AWG 60kVA 2/0 AWG 2/0 AWG 2/0 AWG 2/0 AWG 80kVA 2/0 AWG*2 2/0 AWG*2 100kVA 2/0 AWG*2 2/0 AWG*2 Recommandé Couple Connecteur Anderson (aucun paramètre de couple) 0kgf.com / 0N m 450kgf.cm/ 44N•m * Les onduleurs S3M10-30K ne prennent pas en charge les modèles d’armoires de batteries BP240V100L/100L-NIB. 5.4 C  onnexions de l'armoire de batteries : modèles BP240V65, BP240V65-NIB, BP240V100 et BP240V100-NIB La conception de chaque armoire de batteries inclut des câbles de connexion de batteries internes intégrés, de disjoncteur, des fusibles et des bornes. L'armoire standard peut accueillir 20 batteries de 12V 65Ah 12V 100Ah. Le système de tension CC pour toutes les armoires est 240 V CC avec des ensembles de batteries internes de ±120 V. Les Figures 5-1 et 5-2 illustrent la conception générale du châssis et des vues éclatées pour les modèles BP240V65, BP240V65-NIB, BP240V100 et BP240V100-NIB. Les vues correspondantes pour les modèles BP240V65L, BP240V65LNIB, BP240V100L et BP240V100L-NIB sont illustrées dans la section 5.5 Connexions de l'armoire de batteries : modèles BP240V65L, BP240V65L-NIB, BP240V100L et BP240V100L-NIB. 154 Figure 5-1 : Châssis d'armoire de batteries BP240V65, BP240V65-NIB, BP240V100 et BP240V100-NIB 5. Installation Figure 5-2 : Vue éclatée du châssis, modèles BP240V65, BP240V65-NIB, BP240V100, BP240V100-NIB 5.4.1 Retirer la coque du châssis Mettre l'armoire de batteries en place. Retirer les panneaux supérieurs, avant, de gauche et de droite. Retirer la plaque du couvercle de droite et de gauche du module de batteries, puis le clapet des batteries pour installer les batteries. 5.4.2 Installation et connexion des batteries Chaque groupe de batteries consiste de 20 batteries en série (BAT+, N et BAT-). Placer les batteries dans l'armoire à partir du bas en montant, une à la fois, puis raccorder les câbles de batterie conformément aux schémas qui suivent. Remarque : La polarité positive et négative de la batterie ne peut pas être inversée ou court-circuitée. Cela endommagerait la batterie et/ou causerait des blessures. Ne pas toucher aux bornes positive et négative de la batterie en même temps. Avant de remplacer ou de retirer les batteries, déconnecter le disjoncteur, tirer sur les bornes des éléments, puis retirer les vis de la barre du bus de cuivre. Le non-respect de ces instructions pourrait causer des dommages à l'équipement ou des blessures. L'installation doit consister de 40 batteries. 155 5. Installation Couche 3 Groupe positif, 10 pièces Couche 2 Groupe négatif, 10 pièces Couche 1 Figure 5-3A : Vue avant Fusibles 400 A (x2) Disjoncteur de batterie Connecteur de 25 à 100 kVA Connecteur de 10 à 20 kVA Figure 5-3B : Vue arrière 156 5. Installation L’arrière Couche 3 L’avant L’arrière Couche 2 L’avant L’arrière Couche 1 Remarque: Ce manuel peut être téléchargé en couleur en visitant tripplite.com, le manuel affiche les câbles dans les couleurs correspondantes : rouge = positif bleu = prise centrale L’avant noir = négatif Figure 5-4 : Schéma de câblage pour le modèle BP240V65 157 5. Installation L’arrière Couche 3 L’avant L’arrière Couche 2 L’avant L’arrière Couche 1 Remarque: Ce manuel peut être téléchargé en couleur en visitant tripplite.com, le manuel affiche les câbles dans les couleurs correspondantes : rouge = positif bleu = prise centrale L’avant noir = négatif Figure 5-5 : Schéma de câblage pour le modèle BP240V100 158 5. Installation 5.4.2.1 Installation et configuration des batteries : modèles BP240V65-NIB, BP240V100-NIB 1. Retirer toutes les vis étiquetées 1 (Figures 5-6A et 5-6B). Figure 5-6A Figure 5-6B 159 5. Installation 2. Retirer les plaques du haut, de droite et de gauche (Figure 5-7). Figure 5-7 3. Retirer toutes les vis du support de rétention des batteries, puis retirer les supports de rétention (Figure 6-8). Figure 5-8 160 5. Installation 4. Installer 8 modules de batteries dans la couche 1 (Figure 5-9 : modèle BP240V65-NIB ou Figure 5-10 : modèle BP240V100-NIB). Figure 5-9 : modèle BP240V65-NIB Figure 5-10 : modèle BP240V100-NIB 161 5. Installation 5. Installer 6 modules de batteries dans la couche 2 (Figure 5-11 : modèle BP240V65-NIB ou Figure 5-12 : modèle BP240V100-NIB). Figure 5-11 : modèle BP240V65-NIB Figure 5-12 : modèle BP240V100-NIB 162 5. Installation 6. Installer 6 modules de batteries dans la couche 3 (Figure 5-13 : modèle BP240V65-NIB ou Figure 5-14 : modèle BP240V100-NIB). Figure 5-13 : modèle BP240V65-NIB Figure 5-14 : modèle BP240V100-NIB 163 5. Installation 7. Réinstaller tous les supports de rétention des batteries et toutes les vis (Figure 5-15 : modèle BP240V65-NIB ou Figure 5-16 : modèle BP240V100-NIB). Figure 5-15 : modèle BP240V65-NIB Figure 5-16 : modèle BP240V100-NIB 164 5. Installation 8. Modèle BP240V65-NIB : Installer les barres du bus en cuivre (13 pièces) entre les batteries adjacentes et les boulons/ montants d’insertion des batteries Figure 5-17A Figure 5-17B 165 5. Installation 9. Modèle BP240V100-NIB : Installer les barres du bus en cuivre (12 pièces) entre les batteries adjacentes et les boulons/ montants d’insertion des batteries (Figures 5-18A et 5-18B). Figure 5-18A Figure 5-18B 166 5. Installation 10. Connecter les câbles de la batterie 1+ à la barre du bus de BAT+, de la batterie 10- à la barre du bus de BATN, de la batterie 11+ à la barre du bus de BATN, de la batterie 20- à la barre du bus de BAT- et les câble de connexion de la couche (Figure 5-19 : modèle BP240V65-NIB ou Figure 5-20 : modèle BP240V100-NIB et Figure 5-21). Remarques : • Utiliser les schémas de câblage en guise de référence pour les assemblages suivants : Utiliser la Figure 5-4 pour BP240V65-NIB. Utiliser la Figure 5-5 pour BP240V100-NIB. • Ce manuel peut être téléchargé en couleur en visitant tripplite.com, le manuel affiche les câbles dans les couleurs correspondantes : rouge = positif bleu = prise centrale noir = négatif Figure 5-19 : modèle BP240V65-NIB Figure 5-20 : modèle BP240V100-NIB 167 5. Installation Figure 5-21 11. Réinstaller tous les couvercles et toutes les vis (Figure 5-22). Figure 5-22 168 5. Installation 5.5 C  onnexions de l'armoire de batteries : modèles BP240V65L, BP240V65L-NIB, BP240V100L et BP240V100L-NIB La conception de chaque armoire de batteries inclut des câbles de connexion de batteries internes intégrés, de disjoncteur, des fusibles et des bornes. L'armoire standard peut accueillir 20 batteries de 12 V 65 Ah (12 V/100 Ah). Les armoires de batteries de longue durée « L » peuvent accueillir 40 batteries de 12 V 65 Ah (12 V 100 Ah). Le système de tension CC pour toutes les armoires est 240 V CC avec des ensembles de batteries internes de ±120 V. Les Figures 5-23 et 5-24 illustrent la conception générale du châssis et des vues éclatées pour les modèles BP240V65L, BP240V65L-NIB, BP240V100L et BP240V100L-NIB. Les vues correspondantes pour les modèles BP240V65, BP240V65-NIB, BP240V100 et BP240V100-NIB sont illustrées dans la section 5.4 Connexions de l'armoire des batteries : modèles BP240V65, BP240V65-NIB, BP240V100 et BP240V100-NIB. Figure 5-23 : châssis de batterie BP240V65L, BP240V65L-NIB, BP240V100L et BP240V100L-NIB 5.5.1 Retirer lacoque du châssis Placer la boîte de batteries à son emplacement final. Retirer les panneaux supérieurs, avant, de gauche et de droite. Retirer les plaques du couvercle de droite et de gauche du module de batteries, puis les supports des batteries pour installer les ensembles de batteries. Figure 5-24 : Vue éclatée – modèles BP240V65L, BP240V65L-NIB, BP240V100l, BP240V100L-NIB 169 5. Installation 5.5.2 Installation et connexion des batteries Les 40 batteries peuvent être divisées en deux groupes connectés pour fonctionner en parallèle. Chaque groupe consiste de 20 batteries en série (BAT+, N et BAT-). Placer les batteries dans l'armoire à partir du bas en montant, une à la fois, puis raccorder les câbles de batterie conformément aux schémas qui suivent. Remarque : La polarité positive et négative de la batterie ne peut pas être inversée ou court-circuitée. Cela endommagerait la batterie et/ou causerait des blessures. Ne pas toucher aux bornes positive et négative de la batterie en même temps. Avant de remplacer ou de retirer les batteries, déconnecter le disjoncteur, tirer sur les bornes des éléments, puis retirer les vis de la barre du bus de cuivre. Le non-respect de ces instructions pourrait causer des dommages à l'équipement ou des blessures. L'installation doit consister de 40 batteries. Groupe de batteries 2 Couche 4 Couche 3 Groupe de batteries 1 Couche 2 Couche 1 Figure 5-25A : Vue avant 170 5. Installation Fusibles 400 A (x2) Disjoncteur de batterie Connecteur de 25 à 100 kVA Connecteur de 10 à 20 kVA Figure 5-25B : Vue arrière 171 6. Installation L’arrière L’arrière Couche 4 Couche 2 L’avant L’avant L’arrière L’arrière Couche 1 Couche 3 L’avant L’avant Figure 5-26 : Schéma de câblage pour BP240V65L (40 batteries installées) Remarque : Ce manuel peut être téléchargé en couleur en visitant tripplite.com, le manuel affiche les câbles dans les couleurs correspondantes : rouge = positif bleu = prise centrale noir = négatif 172 5. Installation L’arrière L’arrière Couche 4 Couche 2 L’avant L’avant L’arrière L’arrière Couche 3 Couche 1 L’avant L’avant Figure 5-27 : Schéma de câblage pour BP240V100L (40 batteries installées) Une fois l'installation et la connexion des batteries terminées, utiliser un multimètre ou un autre instrument pour vérifier si les tensions entre BAT+ et N, N et BAT- sont normales. Si les tensions sont normales, verrouiller le couvercle du châssis. Remarque : Ce manuel peut être téléchargé en couleur en visitant tripplite.com, le manuel affiche les câbles dans les couleurs correspondantes : rouge = positif bleu = prise centrale noir = négatif 173 5. Installation 5.5.2.1 Installation et configuration des batteries : modèles BP240V65L-NIB, BP240V100L-NIB 1. Retirer toutes les vis étiquetées 1 (Figures 5-28A et 5-28B). Figure 5-28A Figure 5-28B 174 5. Installation 2. Retirer les plaques du haut, de droite et de gauche (Figure 5-29). Figure 5-29 3. Retirer toutes les vis du support de rétention des batteries, puis retirer les supports de rétention (Figure 5-30). Figure 5-30 175 5. Installation 4. Installer 10 modules de batteries dans la couche 1 (Figure 5-31 : modèle BP240V65L-NIB ou Figure 5-32 : modèle BP240V100L-NIB). Figure 5-31 : modèle BP240V65L-NIB Figure 5-32 : modèle BP240V100L-NIB 176 5. Installation 5. Installer 10 modules de batteries dans la couche 2 (Figure 5-33 : modèle BP240V65L-NIB ou Figure 5-34 : modèle BP240V100L-NIB). Figure 5-33 : modèle BP240V65L-NIB Figure 5-34 : modèle BP240V100L-NIB 177 5. Installation 6. Installer 10 modules de batteries dans la couche 3 (Figure 5-35 : modèle BP240V65L-NIB ou Figure 5-36 : modèle BP240V100L-NIB). Figure 5-35 : modèle BP240V65L-NIB Figure 5-36 : modèle BP240V100L-NIB 178 5. Installation 7. Installer 10 modules de batteries dans la couche 4 (Figure 5-37 : modèle BP240V65L-NIB ou Figure 5-38 : modèle BP240V100L-NIB). Figure 5-37 : modèle BP240V65L-NIB Figure 5-38 : modèle BP240V100L-NIB 179 5. Installation 8. Réinstaller tous les supports de rétention et les vis des batteries (Figure 5-39). Figure 5-39 9. Modèle BP240V65L-NIB : Installer les barres du bus en cuivre (13 pièces) entre les batteries adjacentes et les boulons/ montants d’insertion des batteries (Figures 5-40A et 5-40B). Figure 5-40A 180 5. Installation Figure 5-40B 10. Modèle BP240V100L-NIB : Installer les barres du bus en cuivre (12 pièces) entre les batteries adjacentes et les boulons/ montants d’insertion des batteries (Figures 5-41A et 5-41B). Figure 5-41A 181 5. Installation Figure 5-41B 11. Connecter les câbles de la batterie 1+ du groupe de batteries 1 à la barre du bus de BAT+, de la batterie 10- à la barre du bus de BATN, de la batterie 11+ à la barre du bus de BATN, de la batterie 20- à la barre du bus de BAT- et les câbles de connexion de la couche. Connecter la batterie 21+ du groupe de batteries 2 à la barre du bus de BAT+, de la batterie 30- à la barre du bus de BATN, de la batterie 31+ à la barre du bus de BATN, de la batterie 40- à la barre du bus de BAT- et les câbles de connexion de la couche (Figure 5-42 : modèle BP240V65L-NIB ou Figure 5-43 : modèle BP240V100L et Figure 5-44). Remarques : • Utiliser les schémas de câblage en guise de référence pour les assemblages suivants : Utiliser la Figure 5-26 pour BP240V65L-NIB. Utiliser la Figure 5-27 pour BP240V100L-NIB. • Ce manuel peut être téléchargé en couleur en visitant tripplite.com, le manuel affiche les câbles dans les couleurs correspondantes : rouge = positif bleu = prise centrale noir = négatif Figure 5-42 : modèle BP240V65L-NIB 182 5. Installation Figure 5-43 : modèle BP240V100L-NIB Figure 5-44 183 5. Installation 12. Réinstaller tous les couvercles et toutes les vis (Figure 5-45). Figure 5-45 184 5. Installation 5.6 Connexions de plusieurs modules de batteries DANGER! S'assurer que la polarité de la connexion en série de l'ensemble de batteries est correcte. NE PAS combiner des batteries de différentes capacités de différentes marques ou des batteries vieilles et neuves. AVERTISSEMENT! S'ASSURER QUE LA POLARITÉ DES CONNEXIONS D'EXTRÉMITÉ DES ENSEMBLES VERS LE DISJONCTEUR DES BATTERIES ET DU DISJONCTEUR DES BATTERIES VERS LES BORNES DE L'ONDULEUR EST CORRECTE, C.-À-D. (+) À (+)/(-) À (-)/(N) À (N). DÉCONNECTER UN OU PLUSIEURS LIENS DES ÉLÉMENTS DE BATTERIES DANS CHAQUE NIVEAU. NE PAS RECONNECTER CES LIENS ET NE PAS FERMER LE DISJONCTEUR DES BATTERIES À MOINS QUE TOUTES LES CONNEXIONS AIENT ÉTÉ CORRECTEMENT VÉRIFIÉES ET APPROUVÉES. onduleur armoire de batteries Figure 6-46 : Connexion de BP240V65L et BP240V65L-NIB pour un onduleur de 10 kVA, 15 kVA et 20 kVA 185 5. Installation onduleur armoire de batteries Figure 6-47 : Connexion de BP240V65L et BP240V65L-NIB pour un onduleur de 25 kVA et 30 kVA 186 5. Installation onduleur armoire de batteries Figure 5-48 : Connexion de BP240V65L, BP240V65L-NIB, BP240V100L ou BP240V100L-NIB pour des onduleurs de 50 kVA et 60 kVA 187 5. Installation onduleur armoire de batteries Figure 5-49 : Connexion de BP240V65L, BP240V65L-NIB, BP240V100L ou BP240V100L-NIB pour un onduleur de 80 kVA et 100 kVA 188 6. Fonctionnement et configuration des modèles d’onduleur S3M et des armoires de batteries 6.1 C  ompatibilité des onduleurs S3M avec les armoires de batteries de BP240V65 à BP240V100L Armoires avec batteries internes BP240V65 BP240V65L BP240V100 BP240V100L Armoires SANS batteries internes BP240V65-NIB BP240V65L-NIB BP240V100-NIB BP240V100L-NIB Onduleurs 10 kVA-20 kVA avec batteries internes • S3M10K1B, S3M10K2B, S3M10K3B • S3M15K2B, S3M15K3B • S3M20K3B Non Non Non Non Onduleurs 10 kVA-20 kVA sans batterie interne • S3M10K-NIB • S3M15K-NIB • S3M20K-NIB Oui Oui Oui Non Armoires avec batteries internes BP240V65 BP240V65L BP240V100 BP240V100L Armoires SANS batteries internes BP240V65-NIB BP240V65L-NIB BP240V100-NIB BP240V100L-NIB • S3M25K • S3M30K Oui Oui Oui Non • S3M50K Oui Oui Oui Oui • S3M60K Non Oui Oui Oui • S3M80K • S3M100K Non Oui Non Oui Onduleurs de 25 kVA à 100 kVA SANS batteries internes 189 6. Fonctionnement et configuration des modèles d’onduleur S3M et des armoires de batteries 6.2 C  onfiguration des onduleurs de 10 à 20K pour des armoires de batteries spécifiques en utilisant l’écran ACL Danger! Les réglages pour la plupart des paramètres ne peuvent pas être c hangés lorsque l’onduleur se trouve en mode inverseur. 6.2.1 Écran d’accueil de l’onduleur S3M10-20K 190 6. Fonctionnement et configuration des modèles d’onduleur S3M et des armoires de batteries 6.2.2 Réglages Cliquer sur l’icône Settings (réglages) pour saisir deux niveaux de réglage. Le Basic Setting (réglage de base) est pour les réglages par l’utilisateur et le Advanced Setting (réglages avancés) est pour le personnel technique uniquement. Contacter l’administrateur pour accéder aux réglages avancés. Réglages avancés : cliquer sur Advanced Setting (réglages avancés), puis saisir le bon mot de passe. Le mot de passe de l’utilisateur est « 191210 ». 191 6. Fonctionnement et configuration des modèles d’onduleur S3M et des armoires de batteries 6.2.3 Réglage des batteries Cliquer sur Battery Setup (configuration des batteries) 192 6. Fonctionnement et configuration des modèles d’onduleur S3M et des armoires de batteries 6.2.4 Configuration de l’onduleur S3M10-20K-NIB et optimisation du chargement des armoires de batteries BP240V65/V65L et BP240V100/V100L. Étape 1 : Réglage du groupe de batteries Le groupe de batteries doit être configuré à quantité 1 pour chaque ensemble de 20 batteries qui se trouve dans le modèle de l’onduleur et/ou qui y est connecté. Par exemple, le modèle d’onduleur S3M20K-NIB n’a aucune batterie interne et est configuré à Battery Group 1 (groupe de batteries 1) par défaut pour tous les modèles d’onduleur. Toutefois, pour connecter une armoire BP240V65 avec 20 batteries internes au S3M20K-NIB, l’onduleur S3M20K-NIB doit rester configuré à Battery Group 1 (un ensemble de 20 batteries). Toutefois, pour connecter une seconde armoire BP240V65 à l’onduleur S3M20K-NIB UPS, le groupe de batteries de l’onduleur doit être configuré à 2 (deux ensembles de 20 batteries). Obtenir le numéro pour le Battery Group (groupe de batteries) en fonction de la combinaison particulière du modèle de l’onduleur S3M et du modèle de l’armoire de batteries depuis le tableau dans la Section 6.4. La valeur peut être 1 à 8. La valeur par défaut est 1 pour les modèles d’onduleur S3M sans batteries internes. Étape 2 : Réglage du nombre de batteries Le nombre de batteries doit rester à 20 pour tous les modèles d’onduleur S3M10-100K lorsqu’ils sont connectés à des armoires de batteries externes Tripp Lite conçues pour les onduleurs de la série S3M. Étape 3 : Réglage de la capacité d’une seule batterie (Ah) Changer la capacité d’une seule batterie (Ah) pour la capacité individuelle Ah pour une batterie individuelle comme suit pour les modèles d’armoires de batteries spécifiques : • BP240V09/BP240V09K : la capacité d’une seule batterie (Ah) est 9 • BP240V40/BP240V40L : la capacité d’une seule batterie (Ah) est 40 • BP240V65/BP240V65L : la capacité d’une seule batterie (Ah) est 65 • BP240V100/BP240100L : la capacité d’une seule batterie (Ah) est 100 Les valeurs peuvent varier entre 7 et 2 000. Faire défiler jusqu’à l’écran suivant en appuyant sur la flèche pointant vers le bas. 193 6. Fonctionnement et configuration des modèles d’onduleur S3M et des armoires de batteries Étape 4 : Réglage du courant de charge maximum Le courant de charge maximum est le courant de charge estimé que l’onduleur utilisera pour charger les batteries. Configurer le courant de charge maximum estimé recommandé en fonction de la combinaison particulière du modèle d’onduleur S3M et du modèle d’armoire de batteries depuis le tableau dans la Section 6.4. Tension de maintien et tension d’amplification : l’onduleur est configuré en usine pour les tensions de maintien (2,27 V/ élément, 13,62 V/batterie) et d’amplification (2,35 V/élément, 14,1 V/batterie) appropriées. Tension d’augmentation des éléments : la valeur de la tension d’entretien peut se situer entre 2,23 et 2,30 V/élément. La valeur par défaut est 2,27 V/élément. Cell boost voltage: la valeur de la tension uniformisée des batteries peut se situer entre 2,30 et 2,40 V/élément. La valeur par défaut est 2,35 V/élément. Étape 5 : Réglage de la durée moyenne de chargement (min.) Le réglage de la durée moyenne de chargement en minutes est une estimation de la durée de la charge d’augmentation pour charger les batteries neuves à une capacité de 90 % à 25 °C. Configurer la durée moyenne (Aver) de chargement (min.) recommandée en fonction de la combinaison particulière du modèle de l’onduleur S3M et du modèle de l’armoire de batteries depuis le tableau dans la Section 6.4. Il convient de noter que les durées de charge d’augmentation recommandées ne sont que des estimations basées sur des batteries neuves. Ces valeurs peuvent changer avec l’âge des batteries et la température ambiante. Pour changer la durée moyenne de chargement, appuyer directement sur la valeur 240 par défaut à l’écran. • La durée moyenne (Aver) de chargement est la limite de temps de charge d’augmentation des batteries. La valeur peut se situer entre 1 et 999 min. La valeur par défaut est 240 (4 heures). 194 6. Fonctionnement et configuration des modèles d’onduleur S3M et des armoires de batteries EOD Battery Volt : la tension de fin de décharge est le seuil de sectionnement bas de la tension des batteries pendant un fonctionnement en mode batterie. La valeur peut se situer entre 1,60 et 1,90. La valeur par défaut est 1,67 V/élément ou 10,02 V CC par batterie. Float Temp Compen Coeff : permet de modifier la tension de compensation après l’activation du commutateur. La valeur peut varier entre 0,001 et 0,007 V/élément/°C. La valeur par défaut est 0,003 V/élément/°C. Boost Charge Setting : la charge d’augmentation peut être configurée à Disable (désactivé) ou Enable (activé). La valeur par défaut est Enable (activé). No Battery Warning : garder cette alarme activée pour que l’onduleur émette un avertissement lorsqu’aucune batterie n’est présente. La valeur par défaut est Alarm (alarme). 195 6. Fonctionnement et configuration des modèles d’onduleur S3M et des armoires de batteries 6.3 C  onfiguration des onduleurs de 25 à 100K pour des armoires de batteries spécifiques en utilisant l’écan ACL DANGER! Les réglages pour la plupart des paramètres ne peuvent pas être changés lorsque l’onduleur se trouve en mode inverseur. 6.3.1 Écran d’accueil de l’onduleur S3M25-100K 196 6. Fonctionnement et configuration des modèles d’onduleur S3M et des armoires de batteries 6.3.2 Réglages Cliquer sur l’icône Setting (réglage) pour saisir deux niveaux de réglage. Le Basic Setting (réglage de base) est pour les réglages par l’utilisateur et le Advanced Setting (réglages avancés) est pour le personnel technique uniquement. Contacter l’administrateur pour accéder aux réglages avancés. Réglages avancés : cliquer sur Advanced Setting (réglages avancés), puis saisir le bon mot de passe. Le mot de passe de l’utilisateur est « 191210 ». 197 6. Fonctionnement et configuration des modèles d’onduleur S3M et des armoires de batteries 198 6. Fonctionnement et configuration des modèles d’onduleur S3M et des armoires de batteries 6.3.3 Configuration des batteries Cliquer sur BATT Setup Float Temp. Compen. : le réglage de la compensation de la sonde de température peut être changé à Enable (activé) lorsqu’une sonde de température des batteries est connectée au port arrière RJ45 de l’onduleur. Temp Sensor Select : permet de configurer le type de sonde de température à NTC pour les distances simples et courtes. Configurer le type de sonde de température à RS485 pour les distances multiples et grandes. 199 6. Fonctionnement et configuration des modèles d’onduleur S3M et des armoires de batteries 6.3.4 C  onfiguration de l’onduleur S3M25-100K et l’optimisation du chargement des armoires de batteries BP240V65/V65L et BP240V100/V100L Étape 1 : Réglage du groupe de batteries Le groupe de batteries doit être configuré à quantité 1 pour chaque ensemble de 20 batteries qui se trouve dans le modèle de l’onduleur et/ou qui y est connecté. Par exemple, le modèle d’onduleur S3M100K n’a aucune batterie interne et est configuré à Battery Group 1 (groupe de batteries 1) par défaut. Toutefois, pour connecter une armoire BP240V100L avec 40 batteries internes au S3M100K, l’onduleur S3M100K doit être configuré à Battery Group 2 (groupe de batteries 2) Pour connecter une seconde armoire BP240V100L à l’onduleur S3M100K, le Battery Group (groupe de batteries) doit être configuré à 4 (quatre ensembles de 20 batteries). Obtenir le numéro pour le Battery Group (groupe de batteries) en fonction de la combinaison particulière du modèle de l’onduleur S3M et du modèle de l’armoire de batteries depuis le tableau dans la Section 6.4. La valeur peut être 1 à 8. La valeur par défaut est pour les modèles d’onduleur S3M sans batteries internes. Étape 2 : Réglage du nombre de batteries Le nombre de batteries doit rester à 20 pour tous les modèles d’onduleur S3M10-100K lorsqu’ils sont connectés à des armoires de batteries externes Tripp Lite conçues pour les onduleurs de la série S3M. Étape 3 : Réglage de la capacité d’une seule batterie (Ah) Changer la capacité d’une seule batterie (Ah) pour la capacité individuelle Ah pour une batterie individuelle comme suit pour les modèles d’armoires de batteries spécifiques : • BP240V40/BP240V40L : la capacité d’une seule batterie (Ah) est 40 • BP240V65/BP240V65L : la capacité d’une seule batterie (Ah) est 65 • BP240V100/BP240V100L : la capacité d’une seule batterie (Ah) est 100 Les valeurs pour une batterie simple (Ah) peuvent varier entre 7 et 2 000. Faire défiler jusqu’à l’écran suivant en appuyant sur la flèche pointant vers le bas. 200 6. Fonctionnement et configuration des modèles d’onduleur S3M et des armoires de batteries Étape 4 : Configurer le coefficient de limite du courant de chargement (C) La limite de l’intensité de charge est un multiple de la capacité des batteries. Elle est utilisée pour configurer la limite de temps de charge d’augmentation des batteries. La valeur peut se situer entre 0,05 et 0,25, et est configurée à 0,25 par défaut. Configurer le coefficient (C) de limite de courant (cur) de chargement en fonction de la combinaison particulière du modèle de l’onduleur S3M et du modèle d’armoire de batteries depuis le tableau dans la Section 6.4. Tension de maintien et tension d’amplification : l’onduleur est configuré en usine pour les tensions de maintien (2,27 V/élément, 13,62 V/batterie) et d’amplification (2,35 V/élément, 14,1 V/batterie) appropriées. Tension d’entretien des éléments : la valeur de la tension d’entretien peut se situer entre 2,23 et 2,30 V/élément. La valeur par défaut est 2,27 V/élément. Tension d’augmentation des éléments : la valeur de la tension uniformisée des batteries peut se situer entre 2,30 et 2,40 V/élément. La valeur par défaut est 2,35 V/élément. Étape 5 : Réglage de la durée moyenne de chargement (min.) Le réglage de la durée moyenne de chargement en minutes est une estimation de la durée de la charge d’augmentation pour charger les batteries neuves à une capacité de 90 % à 25 °C. Configurer la durée moyenne (Aver) de chargement (min.) recommandée en fonction de la combinaison particulière du modèle de l’onduleur S3M et du modèle de l’armoire de batteries depuis le tableau dans la Section 6.4. Il convient de noter que les durées de charge d’augmentation recommandées ne sont que des estimations basées sur des batteries neuves. Ces valeurs peuvent changer avec l’âge des batteries et la température ambiante. Pour changer la durée moyenne de chargement, appuyer directement sur la valeur 240 par défaut à l’écran. • La durée moyenne (Aver) de chargement est la limite de temps de charge d’augmentation des batteries. La valeur peut se situer entre 1 et 999 min. La valeur par défaut est 240 (4 heures). 201 6. Fonctionnement et configuration des modèles d’onduleur S3M et des armoires de batteries EOD Battery Volt : la tension de fin de décharge est le seuil de sectionnement bas de la tension des batteries pendant un fonctionnement en mode batterie. La valeur peut se situer entre 1,60 et 1,90. La valeur par défaut est 1,67 V/élément ou 10,02 V CC par batterie. Float Temp Compen Coeff : permet de modifier la tension de compensation après l’activation du commutateur. La valeur peut varier entre 0,001 et 0,007 V/élément/°C. La valeur par défaut est 0,003 V/élément/°C. Boost Charge Setting : la charge d’augmentation peut être configurée à Disable (désactivé) ou Enable (activé). La valeur par défaut est Enable (activé). No Battery Warning : garder cette alarme activée pour que l’onduleur émette un avertissement lorsqu’aucune batterie n’est présente. La valeur par défaut est Enable (activé). 202 6. Fonctionnement et configuration des modèles d’onduleur S3M et des armoires de batteries 6.4 T ableau de référence pour la configuration des modèles d’onduleur S3M10-100K UPS et des modèles d’armoires de batteries BP240V09-BP240V100L Configurations pour les onduleurs S3M10K-NIB, S3M15K-NIB, S3M20K-NIB sans aucune batterie interne Modules de batteries Batteries Nombre de Étape 1 Étape 2 Étape 3 Armoires Groupe de Nombre Capacité d'une de batteries batteries de seule batterie batteries Étape 4 Étape 5 Courant de charge max. (A) Durée moyenne de chargement (min) Temps (minutes) pour charger les batteries à 90 % à 25 °C BP240V65 20 x 65Ah 1 1 20 65 9.75 500 BP240V65 20 x 65Ah 2 2 20 65 19.5 500 BP240V65 20 x 65Ah 3 3 20 65 20 720 BP240V65L 40 x 65Ah 1 2 20 65 19.5 500 BP240V65L 40 x 65Ah 2 4 20 65 20 960 BP240V100 20 x 100Ah 1 1 20 100 15 500 Étape 3 Étape 4 Étape 5 Configurations pour S3M25K et S3M30K Modules de batteries Batteries Nombre de Armoires de batteries Étape 1 Groupe de Nombre batteries de batteries BP240V65 BP240V65 Étape 2 Capacité d'une Coefficient de Durée moyenne de chargement seule batterie limite du courant (min) Temps (minutes) pour charger de chargement (C) les batteries à 90 % à 25 °C 20x 65Ah 1 1 20 65 0.15 540 20 x 65Ah 2 2 20 65 0.15 540 BP240V65 20 x 65Ah 3 3 20 65 0.1 900 BP240V65L 40 x 65Ah 1 2 20 65 0.15 540 BP240V65L 40 x 65Ah 2 4 20 65 0.07 999 BP240V100 20 x 100Ah 1 1 20 100 0.15 540 Étape 3 Étape 4 Étape 5 Configurations pour S3M50K et S3M60K Modules de batteries Batteries Nombre de Armoires de batteries Étape 1 BP240V65 Étape 2 Groupe de Nombre Capacité d'une batteries de seule batterie batteries Coefficient de Durée moyenne de chargement limite du courant (min) Temps (minutes) pour charger de chargement (C) les batteries à 90 % à 25 °C 20 x 65Ah 1 1 20 65 0.15 540 BP240V65 20 x 65Ah 2 2 20 65 0.15 540 BP240V65 20 x 65Ah 3 3 20 65 0.15 540 BP240V65L 40 x 65Ah 1 2 20 65 0.15 540 BP240V65L 40 x 65Ah 2 4 20 65 0.15 540 BP240V65L 40 x 65Ah 3 6 20 65 0.1 840 BP240V100 20 x 100Ah 1 1 20 100 0.15 540 BP240V100 20 x 100Ah 2 2 20 100 0.15 540 BP240V100 20 x 100Ah 3 3 20 100 0.13 540 BP240V100L 40 x 100Ah 1 2 20 100 0.15 540 BP240V100L 40 x 100Ah 2 4 20 100 0.1 840 203 6. Fonctionnement et configuration des modèles d’onduleur S3M et des armoires de batteries Configurations pour S3M80K Modules de batteries Batteries Nombre de Armoires de batteries Étape 1 Étape 2 Étape 3 Étape 4 Étape 5 Groupe de batteries Nombre de batteries Capacité d'une seule batterie Coefficient de limite du courant de chargement (C) Durée moyenne de chargement (min) Temps (minutes) pour charger les batteries à 90 % à 25 °C BP240V65 BP240V65 20 x 65 Ah 1 1 20 65 0.15 540 20 x 65 Ah 2 2 20 65 0.15 540 BP240V65 20 x 65 Ah 3 3 20 65 0.15 540 BP240V65L 40 x 65 Ah 1 2 20 65 0.15 540 BP240V65L 40 x 65 Ah 2 4 20 65 0.15 540 BP240V65L 40 x 65 Ah 3 6 20 65 0.15 540 BP240V100 20 x 100 Ah 1 1 20 100 0.15 540 BP240V100 20 x 100 Ah 2 2 20 100 0.15 540 BP240V100 20 x 100 Ah 3 3 20 100 0.15 540 BP240V100L 40 x 100 Ah 1 2 20 100 0.15 540 BP240V100L 40 x 100 Ah 2 4 20 100 0.15 540 BP240V100L 40 x 100 Ah 3 6 20 100 0.1 840 Nombre de Armoires de batteries Étape 1 Étape 2 Étape 3 Étape 4 Étape 5 Groupe de batteries Nombre de batteries Capacité d'une seule batterie Coefficient de limite du courant de chargement (C) Durée moyenne de chargement (min) Temps (minutes) pour charger les batteries à 90 % à 25 °C Configurations pour S3M100K Modules de batteries Batteries BP240V65 20 x 65 Ah 1 1 20 65 0.15 540 BP240V65 20 x 65 Ah 2 2 20 65 0.15 540 BP240V65 20 x 65 Ah 3 3 20 65 0.15 540 BP240V65L 40 x 65 Ah 1 2 20 65 0.15 540 BP240V65L 40 x 65 Ah 2 4 20 65 0.15 540 BP240V65L 40 x 65 Ah 3 6 20 65 0.15 540 BP240V100 20 x 100 Ah 1 1 20 100 0.15 540 BP240V100 20 x 100 Ah 2 2 20 100 0.15 540 BP240V100 20 x 100 Ah 3 3 20 100 0.15 540 BP240V100L 40 x 100 Ah 1 2 20 100 0.15 540 BP240V100L 40 x 100 Ah 2 4 20 100 0.15 540 BP240V100L 40 x 100 Ah 3 6 20 100 0.13 540 204 7. Caractéristiques techniques 7.1 C  aracteristiques techniques des armoires de batteries (tension nominale cc : +– 120 V CC, 240 V CC) Module de batteries BP240V65 (-NIB) 800 x 900 x 1 200 mm (31,5 x 35,4 x 47,2 po) Dimension l×P×H Poids BP240V100 (-NIB) 275, 8 kg (608 lb)* 421,8 kg (930 lb)* BP240V65L (-NIB) BP240V100L (-NIB) 800 x 1 100 x 1 600 mm (31,5 x 43,3 x 63 po) 491,2 kg (1 083 lb)* 742,5 kg (1 637 lb)* Disjoncteur 1x 250 A 1x 600 A Fusible 2x 400 A 4x 400 A *Les modèles avec le suffixe –NIB n'incluent aucune batterie interne, leur poids total varie donc en fonction des batteries installées par l'utilisateur final. 8. Entreposage Entreposage L'armoire de batteries doit être entreposée dans un environnement propre et sûr et où la température est inférieure à 40 °C (104 °F) et l'humidité relative est inférieure à 90 % (sans condensation). Entreposer l'armoire de batteries dans son conteneur d'expédition original si possible. Charger les batteries pendant au moins 24 heures avant l'utilisation. Ne pas se fier à l'armoire de batteries pour fournir une alimentation de secours à l'équipement connecté jusqu'à ce que les batteries soient entièrement chargées. Remarque : Si l'onduleur demeure hors tension pendant une période prolongée, il est recommandé de le mettre périodiquement sous tension pour permettre aux batteries de se recharger. L'onduleur doit être mis sous tension et les batteries doivent être rechargées pendant une période ininterrompue d'au moins 24 heures tous les 3 mois. Si les batteries ne sont pas rechargées périodiquement, cela risque de causer des dommages irréversibles aux batteries. 205 9. Service et garantie Entretien Le produit Tripp Lite est couvert par la garantie décrite dans ce manuel. Une variété de programmes de garantie prolongée et de service d'entretien sont également offerts par Tripp Lite. Pour obtenir plus de renseignements sur le service, visiter tripplite.com/support. Avant de retourner le produit pour la réparation, procéder comme suit : 1. Passer en revue les procédures d'installation et de fonctionnement dans ce manuel afin de s'assurer que le problème ne provient pas d'une mauvaise interprétation des instructions. 2. Si le problème persiste, ne pas communiquer avec le fournisseur et ne pas lui renvoyer le produit. Visiter plutôt tripplite.com/support. 3. S  i le problème nécessite une réparation, visiter tripplite.com/support et cliquer sur le lien de retours de produit. À partir de ce point, il est possible de demander une autorisation de retour de matériel (RMA) qui est requise pour le service. Ce simple formulaire en ligne demandera le modèle de l'appareil et le numéro de série, ainsi que d'autres informations générales. Le numéro RMA ainsi que des instructions d'expédition seront envoyés par courriel. Les dommages (directs, indirects, particuliers ou consécutifs) encourus par le produit lors du transport vers Tripp Lite ou vers un centre de réparation agréé Tripp Lite ne sont pas couverts par la garantie. Les frais liés au transport des produits expédiés à Tripp Lite ou à un centre de service autorisé Tripp Lite doivent être entièrement payés d'avance. Inscrire le numéro de RMA à l'extérieur de l'emballage. Si le produit est dans sa période de garantie, joindre une copie du reçu de caisse. Retourner le produit pour réparation par un transporteur assuré à l'adresse fournie lors de la demande de « RMA ». Garantie limitée Le vendeur garantit que ce produit, s'il est utilisé conformément à toutes les instructions applicables, est exempt de tous défauts de matériaux et de fabrication pour une période de un (1) an à partir de la date d'achat initiale. Si le produit s'avère défectueux en raison d'un vice de matière ou de fabrication au cours de cette période, le vendeur s'engage à réparer ou remplacer le produit, à sa seule discrétion. Le service sous cette garantie inclut les pièces et la main-d’œuvre du centre de service de Tripp Lite. Tripp Lite offre des plans de services sur place par le biais de partenaires de service autorisés (dans la plupart des régions). Pour plus de détails, visiter tripplite.com/support. Les clients internationaux doivent contacter l'assistance de Tripp Lite à [email protected]. CETTE GARANTIE NE S'APPLIQUE PAS À L'USURE NORMALE OU AUX DOMMAGES RÉSULTANT D'UNE MAUVAISE UTILISATION, D'UN ABUS OU D'UNE NÉGLIGENCE. LE VENDEUR N'ACCORDE AUCUNE GARANTIE EXPRESSE AUTRE QUE LA GARANTIE EXPRESSÉMENT DÉCRITE DANS LE PRÉSENT DOCUMENT. SAUF DANS LA MESURE OÙ CELA EST INTERDIT PAR LA LOI EN VIGUEUR, TOUTE GARANTIE IMPLICITE, Y COMPRIS TOUTES LES GARANTIES DE QUALITÉ MARCHANDE OU D'ADAPTATION, SONT LIMITÉES À LA PÉRIODE DE GARANTIE CI-DESSUS ET CETTE GARANTIE EXCLUT EXPRESSÉMENT TOUS DOMMAGES DIRECTS ET INDIRECTS. (Certains États ne permettent pas de limitations sur la durée d'une garantie implicite, et certains États ne permettent pas l'exclusion ou la limitation des dommages fortuits ou consécutifs, de sorte que les limitations ou exclusions susmentionnées peuvent ne pas s'appliquer à vous. Cette garantie vous donne des droits légaux spécifiques, et vous pouvez avoir d'autres droits qui varient selon le territoire.) Tripp Lite; 1111 W. 35th Street; Chicago IL 60609; USA AVERTISSEMENT : L'utilisateur individuel doit prendre soin de déterminer avant l'utilisation si cet appareil est approprié, adéquat et sûr pour l'usage prévu. Puisque les utilisations individuelles sont sujettes à des variations importantes, le fabricant ne fait aucune déclaration ou garantie quant à l'aptitude ou l'adaptation de ces dispositifs pour une application spécifique. Numéros d'identification à la conformité réglementaire À des fins de certification de conformité réglementaire et d'identification, un numéro de série unique a été attribué au produit Tripp Lite. Le numéro de série, ainsi que toutes les marques d'homologation et les renseignements requis, se trouvent sur la plaque signalétique du produit. Lors d'une demande de renseignements concernant la conformité de ce produit, toujours se reporter au numéro de série. Le numéro de série ne doit pas être confondu avec le nom de la marque ou le numéro de modèle du produit. Renseignements sur la conformité à la directive DEEE pour les clients de Tripp Lite et les recycleurs (Union européenne) En vertu de la directive et des règlements d'application relatifs aux déchets d'équipements électriques et électroniques (DEEE), lorsque des clients achètent de l'équipement électrique et électronique neuf de Tripp Lite, ils ont droit : • D'envoyer l'équipement usagé au recyclage pourvu qu'il soit remplacé par un équipement équivalent (cela varie selon les pays) • D'envoyer le vieil équipement au recyclage en autant qu'il remplace un équipement équivalent (cela varie selon les pays) La politique de Tripp Lite en est une d'amélioration continue. Les caractéristiques techniques sont modifiables sans préavis. Les produits réels peuvent différer légèrement des photos et des illustrations. 206 207 1111 W. 35th Street, Chicago, IL 60609 USA • tripplite.com/support 208 20-11-074 93-3BF8_RevB
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163
  • Page 164 164
  • Page 165 165
  • Page 166 166
  • Page 167 167
  • Page 168 168
  • Page 169 169
  • Page 170 170
  • Page 171 171
  • Page 172 172
  • Page 173 173
  • Page 174 174
  • Page 175 175
  • Page 176 176
  • Page 177 177
  • Page 178 178
  • Page 179 179
  • Page 180 180
  • Page 181 181
  • Page 182 182
  • Page 183 183
  • Page 184 184
  • Page 185 185
  • Page 186 186
  • Page 187 187
  • Page 188 188
  • Page 189 189
  • Page 190 190
  • Page 191 191
  • Page 192 192
  • Page 193 193
  • Page 194 194
  • Page 195 195
  • Page 196 196
  • Page 197 197
  • Page 198 198
  • Page 199 199
  • Page 200 200
  • Page 201 201
  • Page 202 202
  • Page 203 203
  • Page 204 204
  • Page 205 205
  • Page 206 206
  • Page 207 207
  • Page 208 208

Tripp Lite Owner's Manual Extended-Run Battery Cabinet -BP240V65, BP240V65-NIB, BP240V65L, BP240V65L-NIB, BP240V100, BP240V100-NIB, BP240V100L, BP240V100L-NIB El manual del propietario

Tipo
El manual del propietario