Troubleshooting EN
Carlo Gavazzi RSBT Troubleshooting Guide Rev 1.0 2
LED Status Indications
State
Supply
(green LED)
Alarm
(red LED)
Idle
ON
OFF
Ramping
ON
OFF
Bypass
ON
OFF
Alarm
ON
Flashing
Relay status indication
Supply
(green LED)
Relay contact position
RSBT 45mm
(V21..)
RSBT 120 mm
(CV0, CVC)
Alarm
(11, 12, 14)
Alarm
(11, 12, 14)
Bypass
(21, 22, 24)
ON
11, 14
11, 12
21, 22
ON
11, 14
11, 12
21, 22
ON
11, 14
11, 12
21, 24
ON
11, 12
11, 14
21, 22
Alarms
The RSBT includes a number of diagnostics and protection features each of which is signalled through a flashing
sequence on the red LED. After each flashing cycle, there is a delay (OFF time) on the red LED of 1.5 sec before
the next cycle starts. During the alarm recovery period, the red LED will flash at twice the frequency to indicate that
the RSBT is in recovery mode.
Troubleshooting EN
Carlo Gavazzi RSBT Troubleshooting Guide Rev 1.0 3
Number of flashes
2
Alarm
Wrong phase sequence
Alarm description
If the connection to the soft starter is not done in the correct
sequence (L1, L2, L3), the RSBT will trigger the wrong phase
sequence alarm and the motor will not be started.
Alarm recovery period
N/A
Consecutive alarms for hard reset
1
Action to recover alarm
User intervention is required to change the wiring sequence to
recover alarm.
Troubleshooting
Check that wiring on L1, L2, L3 is in the correct
sequence
Number of flashes
3
Alarm
Line voltage out of range
Alarm description
RSBT 48 models have fixed over-voltage and under voltage alarm
limits. When the mains voltage is out of these limits for more than
5 seconds the line voltage out of range alarm will be triggered.
RSBT40 models have auto-adjustable over-voltage and under-
voltage alarm limits, that can be modified by user as well. Unless
they are modified, they will automatically adjust according to the
supply voltage. Once any or both are modified, the change/s will
be retained until the user changes again any or both limits. When
the mains voltage is out of these limits for more than 5 seconds
the line voltage out of range alarm will be triggered.
Model
Under-voltage limit
Over-voltage limit
RSBT40
187/330 VAC
250/470 VAC
RSBT48
175 VAC
560 VAC
Alarm recovery period
5 minutes
Consecutive alarms for hard reset
N/A
Action to recover alarm
The alarm will self-recover after 5 minutes from when the supply
voltage is within limits.
Troubleshooting
Check supply voltage level across L1, L2, L3 terminals
Troubleshooting EN
Carlo Gavazzi RSBT Troubleshooting Guide Rev 1.0 4
Number of flashes
4
Alarm
Frequency out of range
Alarm description
If the frequency measured by the RSBT is > 66.5 Hz and < 44.5
Hz for at least 1 second, this alarm will trigger.
Alarm recovery period
5 minutes
Consecutive alarms for hard reset
N/A
Action to recover alarm
Check for any disturbance on the voltage network. The voltage
waveform may be disrupted when unfiltered variable frequency
drives are used.
Troubleshooting
In the case where variable frequency drives are present,
ensure that proper EMI filters are installed
Number of flashes
5
Alarm
Locked rotor condition (during ramp)
Alarm description
If a current ≥ 4 x Ie for 100 msec is detected, the RSBT will issue
the locked rotor alarm.
Alarm recovery period
5 minutes
Consecutive alarms for hard reset
2
Action to recover alarm
The alarm will self-recover after 5 minutes. If the soft starter
remains in alarm for more than 5 minutes (due to consecutive
alarms) then a power reset (reset of L1, L2, L3 is required.
Troubleshooting
Check that the RSBT model is suitably rated for the
motor
Check motor windings resistance to check if motor is
damaged
Number of flashes
6
Alarm
Ramp-up time (> 1 sec)
Alarm description
The RSBT will trigger this alarm if the compressor does not reach
full speed within 1 second. The alarm protects the bypass relays
from switching a high current.
Alarm recovery period
5 minutes
Consecutive alarms for hard reset
2
Action to recover alarm
The alarm will self-recover after 5 minutes. If the alrm is triggered
twice consecutively, then the user must switch OFF and then ON
the mains (L1, L2, L3) to perform a hard reset. This will reset the
alarm.
Troubleshooting
Check that the correct model of RSBT is being used
Chec that the connections to the compressor are correct
Check for any mechanical blockage of the compressor
Troubleshooting EN
Carlo Gavazzi RSBT Troubleshooting Guide Rev 1.0 5
Number of flashes
7
Alarm
Over-temperature
Alarm description
The RSBT constantly measures the heatsink and thyristors
(SCRs) temperature. If the maximum internal temperature is
exceeded (for a minimum of 0.5 sec) an over-temperature alarm
is triggered. This condition can be triggered by too many starts
per hour, an over-load condition during starting and/or stopping or
a high surrounding temperature.
Alarm recovery period
Depends on the cooling period.
The RSBT will only recover if the internal temperature is within
safe limits.
Consecutive alarms for hard reset
N/A
Action to recover alarm
The alarm will self-recover - the recovery period will depend on
the cooling time required by RSBT. The higher the surrounding
temperature, the longer the cooling period.
Troubleshooting
Check that the specified number of starts/hr is not
exceeded.
Check that the surrounding temperature around the soft
starter is within limits.
Number of flashes
8
Alarm
Current not normal (during bypass)
Alarm description
The RSBT measures the current during bypass state. If the current
is > 1.15 * Ie for at least 1 second, the RSBT will trigger this alarm
and switch OFF the output. This condition can result in case of an
overload condition or because the RSBT moel is under-rated for
the load it is controlling.
Alarm recovery period
5 minutes
Consecutive alarms for hard reset
2
Action to recover alarm
The alarm will self-recover after a period of 5 minutes. If the alarm
is triggered twice consecutively, then the user must switch OFF
and then ON the mains (L1, L2, L3) to prform a hard reset. This
will reset the alarm.
Troubleshooting
Check that the correct model of RSBT is being used
Check that the connections to the compressor are
correct
Measure the current with a clamp meter on any of L1,
L2, L3 phases and check if the current is within the
expected levels. If the current is higher than the RSBT
rated current, change the RSBT to a larger model.
Number of flashes
9
Alarm
Supply voltage unbalance
Alarm description
The RSBT measures the voltages on all the three phases and if
there is a difference of more than 10% for ≥ 5 sec between any of
the phases, the RSBT will trigger the voltage unbalance alarm.
Alarm recovery period
5 minutes
Consecutive alarms for hard reset
N/A
Action to recover alarm
The alarm will start a self-recovery of 5 minutes from the moment
the voltage on L1, L2, L3 are within 10% of each other. If the
voltage unbalance remains > 10%, the RSBT will reman in alarm
state.
Troubleshooting
Check for any loose connections on the mains and load-
side terminals
Check supply voltage level across L1, L2, L3 terminals
and see if there is any unbalance
Check resistance on motor windings to see if any of the
coils is damaged
Problembehebung DE
Status-LED-Anzeigen
Zustand
Spannungs-
versorgung
(Grüne LED)
Alarm
(Rote LED)
Leerlaufzustand
Ein
AUS
Anlaufzustand
Ein
AUS
Überbrückungszustand
Ein
AUS
Alarmrücksetzung
Ein
Blinken
Relais Zustandsanzeigen
Zustand
Spannungs-
versorgung
(Grüne LED)
Position der Relaiskontakte
RSBT 45 mm
(V21..)
RSBT 120 mm
(CV0, CVC)
Alarm
(11, 12, 14)
Alarm
(11, 12, 14)
Überbrückung
(21, 22, 24)
Leerlaufzustand
Ein
11, 14
11, 12
21, 22
Anlaufzustand
Ein
11, 14
11, 12
21, 22
Überbrückungszustand
Ein
11, 14
11, 12
21, 24
Alarmrücksetzung
Ein
11, 12
11, 14
21, 22
Alarme
Das RSGD ist mit verschiedenen Diagnose- und Schutzfunktionen ausgestattet. Alle diese Funktionen werden
mithilfe einer Blinksequenz der roten LED signalisiert.
Problembehebung DE
Carlo Gavazzi RSBT Troubleshooting Guide Rev 1.0 7
Anzahl der Blinksignale
2
Alarm
Falsche Phasenreihenfolge
Alarmbeschreibung
Wenn der Netzanschluss am Sanftstartgerät nicht in der richtigen
Reihenfolge (L1, L2, L3) vorgenommen wurde, löst das RSBT den
Alarm für falsche Phasenreihenfolge aus, und der Motor wird nicht
gestartet.
Alarmerholungsphase
n.v.
Aufeinanderfolgende Alarme für
hartes RÜCKSETZEN
1
Aktion zur Beseitigung des Alarms
In diesem Fall ist ein Eingriff durch den Anwender erforderlich, um
die Beschaltung zu korrigieren und den Alarm zu beseitigen.
Problembehebung
Überprüfen
Anzahl der Blinksignale
3
Alarm
Netzspannung außerhalb des Bereichs
Alarmbeschreibung
Der RSBT 48 hat fest eingestellte Überspannungs- und
Unterspannungsalarmschwellen. Überschreitet bzw.
unterschreitet die Netzspannung 5s lang diese Grenzen, so wird
ein Netzspannungsalarm ausgelöst. RSBT40-Modelle verfügen
über automatisch einstellbare Über- und Unterspannungsala-
rmgrenzen, die auch vom Benutzer geändert werden können.
Sofern sie nicht geändert werden, werden sie automatisch an die
Versorgungsspannung angepasst. Sobald eine oder beide
Änderungen vorgenommen wurden, bleiben die Änderungen
erhalten, bis der Benutzer eine oder beide Grenzwerte erneut
ändert. Wenn die Netzspannung länger als 5 Sekunden
außerhalb dieser Grenzen liegt, wird der Alarm für die
Netzspannung außerhalb des Bereichs ausgelöst.
Modell
Unterspannungs-
schwellen
Überspannungs-
schwellen
RSBT40
187/330
250/470
RSBT48
175
560
Alarmerholungsphase
5 Minuten
Aufeinanderfolgende Alarme für
hartes RÜCKSETZEN
4
Aktion zur Beseitigung des Alarms
Im automatischen Erholungsmodus wird der Alarm 5 Minuten,
nachdem die Versorgungsspannung wieder innerhalb der
Grenzwerte liegt, automatisch deaktiviert.
Problembehebung
Überprüfen Sie die Versorgungsspannung zwischen den
Anschlüssen L1, L2 und L3.
Stellen Sie sicher, dass Sie kein RSBT40-Modell bei
einer Versorgungsspannung von > 440 V AC betreiben.
Problembehebung DE
Carlo Gavazzi RSBT Troubleshooting Guide Rev 1.0 8
Anzahl der Blinksignale
4
Alarm
Frequenz nicht vorschriftsmäßig
Alarmbeschreibung
Dieser Alarm wird ausgelöst, wenn die vom RSBT gemessene
Frequenz mindestens 1 Sekunde lang >66.5 Hz oder <44.5 Hz ist.
Alarmerholungsphase
5 Minuten
Aufeinanderfolgende Alarme für
hartes RÜCKSETZEN
n.v.
Aktion zur Beseitigung des Alarms
Überprüfen Sie das Stromnetz auf Störungen. Die Wellenform der
Spannung kann unterbrochen werden, wenn ungefilterte
Wechselstromantriebe verwendet werden.
Problembehebung
Stellen Sie sicher, dass geeignete EMI-Filter installiert
sind, wenn Wechselstromantriebe mit dem Netz verbunden sind.
Anzahl der Blinksignale
5
Alarm
Blockierter Rotorzustand (während der Rampe)
Alarmbeschreibung
Der RSBT löst diesen Alarm aus, wenn der Kompressor nicht
innerhalb einer Sekunde seine Nenndrehzahl erreicht. Dies
bewahrt das Bypassrelais davor sehr hohe Ströme zu schalten.
Alarmerholungsphase
OK
Aufeinanderfolgende Alarme für
hartes RÜCKSETZEN
2
Aktion zur Beseitigung des Alarms
Im automatischen Erholungsmodus wird der Alarm nach 5
Minuten automatisch deaktiviert. Wenn der Softstarter (aufgrund
aufeinanderfolgender Alarme) länger als 5 Minuten in Alarm
bleibt, ist ein Power-Reset (Reset von L1, L2, L3 für RSBT40 und
Reset von A1, A2 für RSBT60-Modelle) erforderlich.
Problembehebung
Überprüfen Sie, ob das RSBT-Modell leistungsfähig
genug für den Motor ist.
Überprüfen Sie den Widerstand der Motorwicklungen,
um eventuelle Motorbeschädigungen festzustellen.
Anzahl der Blinksignale
6
Alarm
Hochlaufzeit (> 1sec)
Alarmbeschreibung
Das RSBT misst den Strom im Überbrückungszustand. Wenn der
Strom mindestens eine Sekunde lang > 1,05 × Ie ist, löst das
RSBT diesen Alarm aus und schaltet den Ausgang AUS. Dieser
Zustand kann bei Überlastung oder bei einem RSBT auftreten,
das für die geregelte Last unterdimensioniert ist.
Alarmerholungsphase
5 Minuten
Aufeinanderfolgende Alarme für
hartes RÜCKSETZEN
2
Aktion zur Beseitigung des Alarms
Der Alarm wird nach einem Zeitraum von 5 Minuten automatisch
deaktiviert.
Wenn der Alarm zweimal in Folge ausgelöst wird, muss der
Anwender die Hauptspeisung AUS- und wieder ANschalten (L1,
L2, L3 oder A1, A2 bei den RSBT60-Modellen), um ein hartes
Rücksetzen auszuführen. Dadurch wird der Alarm zurückgesetzt.
Problembehebung
Stellen Sie sicher, dass das richtige RSBT-Modell
verwendet wird.
Stellen Sie sicher, dass die Anschlüsse des
Kompressors ordnungsgemäß verbunden sind.
Überprüfen Sie den Kompressor auf mechanische
Blockierungen.
Anzahl der Blinksignale
7
Problembehebung DE
Carlo Gavazzi RSBT Troubleshooting Guide Rev 1.0 9
Alarm
Überhitzung
Alarmbeschreibung
Das RSBT misst kontinuierlich die Temperatur des Kühlkörpers
und der Thyristoren. Wenn die maximale Innentemperatur
überschritten wird (für einen Zeitraum von mindestens 0,5 s), wird
ein Überhitzungsalarm ausgelöst. Dieser Zustand kann durch eine
zu hohe Anzahl von Startvorgängen pro Stunde, eine
Überlastungssituation beim Starten und/oder Stoppen oder durch
hohe Umgebungstemperaturen ausgelöst werden.
Alarmerholungsphase
Hängt vom Abkühlzeitraum ab.
Das RSBT deaktiviert den Alarm erst dann, wenn die
Innentemperatur innerhalb sicherer Grenzen liegt.
Aufeinanderfolgende Alarme für
hartes RÜCKSETZEN
4
Aktion zur Beseitigung des Alarms
Im automatischen Erholungsmodus wird der Alarm automatisch
deaktiviert. Die Erholungsdauer hängt von dem Zeitraum ab, den
das RSBT zum Abkühlen benötigt. Die Kühlzeitdauer fällt umso
länger aus, je höher die Umgebungstemperatur liegt.
Problembehebung
Stellen Sie sicher, dass die angegebene Anzahl von
Startvorgängen pro Stunde nicht überschritten wird.
Stellen Sie sicher, dass die Umgebungstemperatur um
das Sanftstartgerät herum innerhalb der zulässigen Grenzwerte
liegt.
Anzahl der Blinksignale
8
Alarm
Strom anormal (bei Überbrückung)
Alarmbeschreibung
Das RSBT misst den Strom im Überbrückungszustand. Wenn der
Strom mindestens eine Sekunde lang > 1,15 × Ie ist, löst das
RSBT diesen Alarm aus und schaltet den Ausgang AUS. Dieser
Zustand kann bei Überlastung oder bei einem RSBT auftreten,
das für die geregelte Last unterdimensioniert ist.
Alarmerholungsphase
5 Minuten
Aufeinanderfolgende Alarme für
hartes RÜCKSETZEN
2
Aktion zur Beseitigung des Alarms
Der Alarm wird nach einem Zeitraum von 5 Minuten automatisch
deaktiviert.
Wenn der Alarm zweimal in Folge ausgelöst wird, muss der
Anwender die Hauptspeisung AUS- und wieder ANschalten (L1,
L2, L3), um ein hartes Rücksetzen auszuführen. Dadurch wird der
Alarm zurückgesetzt.
Problembehebung
Stellen Sie sicher, dass das richtige RSBT-Modell
verwendet wird.
Stellen Sie sicher, dass die Anschlüsse des
Kompressors ordnungsgemäß verbunden sind.
Messen Sie auf allen Phasen L1, L2 und L3 mit einer
Strommesszange den Strom, und überprüfen Sie, ob die Ströme
dem erwarteten Wert entsprechen. Wenn der Betriebsstrom über
dem Nennstrom des RSBT liegt, ersetzen Sie das RSBT durch
ein leistungsfähigeres Modell.
Anzahl der Blinksignale
9
Problembehebung DE
Carlo Gavazzi RSBT Troubleshooting Guide Rev 1.0 10
Alarm
Unsymmetrische Versorgungsspannung
Alarmbeschreibung
Das RSBT misst die Spannung aller drei Phasen. Wenn bei einer
beliebigen Phase ≥ 5 s lang eine Abweichung von mehr als 20 %
auftritt, löst das RSGD den Alarm für unsymmetrische Spannung
aus.
Alarmerholungsphase
5 Minuten (ab dem Zeitpunkt, an dem das
Spannungsungleichgewicht zwischen allen Phasen <10% ist)
Aufeinanderfolgende Alarme für
hartes RÜCKSETZEN
n.v.
Aktion zur Beseitigung des Alarms
Sobald die Spannungen an L1, L2 und L3 innerhalb einer
Toleranz von 10 % liegen, beginnt eine Erholungsphase von 5
Minuten, nach der der Alarm zurückgesetzt wird. Wenn die
Spannungsunsymmetrie > 10 % bleibt, verbleibt das RSBT im
Alarmzustand.
Problembehebung
Überprüfen Sie, ob die Verbindungen an der Netz- oder
Lastseite lose sind.
Überprüfen Sie die Spannung zwischen L1 L2, L2
L3, L1 L3, und überprüfen Sie, ob eine Unsymmetrie
vorliegt.
Überprüfen Sie den Widerstand der Motorwicklungen,
um festzustellen, ob die Spulen beschädigt sind.
Ricerca guasti ITA
Indicazioni LED di stato
Stato
Alimentazione
(LED verde)
Allarme
(LED rosso)
Inattivo
ON
OFF
Rampa
ON
OFF
Bypass
ON
OFF
Allarme
ON
Lampeggiante
Indicazioni dello stato dei relè
Stato
Alimentazione
(LED verde)
Posizione contatti relè
RSBT 45 mm
(V21..)
RSBT 120 mm
(CV0/CVC)
Allarme
(11, 12, 14)
Allarme
(11, 12, 14)
Bypass
(21, 22, 24)
Inattivo
ON
11, 14
11, 12
21, 22
Rampa
ON
11, 14
11, 12
21, 22
Bypass
ON
11, 14
11, 12
21, 24
Allarme
ON
11, 12
11, 14
21, 22
Allarmi
L’ RSBT dispone di una serie di funzioni di diagnostica e protezione, ciascuna delle quali è segnalata attraverso
una sequenza di lampeggi del LED rosso.
Ricerca guasti ITA
Numero di lampeggi
2
Allarme
Errata sequenza fase
Descrizione allarme
Se la connessione al soft starter non è fatta nella corretta
sequenza (L1, L2, L3), l' RSBT attiverà l'allarme errata sequenza
fasi e il motore non sarà avviato.
Tempo di ripristino allarme
N/A
Allarmi consecutivi che richiedono un
RESET completo
1
Azione per disattivare l'allarme
E’ richiesto l’intervento dell’utente per modificare la sequenza di
cablaggio e disattivare così, l’allarme.
Riparazione guasto
Controllare che il cablaggio di L1, L2, L3 sia stato
effettuato in modo corretto.
Numero di lampeggi
3
Allarme
Tensione di linea fuori range
Descrizione allarme
I modelli RSBT 48 hanno limiti di allarme fissi per sovratensione e
sottotensione. Quando la tensione di rete è fuori da questi limiti
per più di 5 secondi, verrà attivato l'allarme di tensione fuori linea.
I modelli RSBT40 hanno limiti di allarme di sovratensione e
sottotensione regolabili automaticamente, che possono essere
modificati anche dall'utente. A meno che non vengano modificati,
si regoleranno automaticamente in base alla tensione di
alimentazione. Una volta che una o entrambe le modifiche sono
state modificate, le modifiche verranno conservate fino a quando
l'utente non modificherà nuovamente uno o entrambi i limiti.
Quando la tensione di rete è fuori da questi limiti per più di 5
secondi, scatta l'allarme di tensione di linea fuori range.
Modello
Sottotensione
Sovratensione
RSBT40
187/330
250/470
RSBT48
175
560
Tempo di ripristino allarme
5 minuti
Allarmi consecutivi che richiedono un
RESET completo
4
Azione per disattivare l'allarme
L'allarme si disattiva ( in modalità AUTO ) trascorsi 5 minuti da
quando il livello di tensione è rientrato nei limiti previsti.
Riparazione guasto
Controllare la tensione di linea sui terminali L1,L2,L3.
Assicurarsi di non aver utilizzato un modello
RSBT40 su una linea di alimentazione con tensione >
440VCA.
Ricerca guasti ITA
Numero di lampeggi
4
Allarme
Frequenza fuori portata
Descrizione allarme
Se la frequenza misurata dal RSBT è >66.5 Hz e <44.5 Hz per
almeno 1 secondo, questo allarme si attiva.
Tempo di ripristino allarme
5 minuti
Allarmi consecutivi che richiedono un
RESET completo
N/A
Azione per disattivare l'allarme
Controllare eventuali disturbi sulla rete di tensione. La forma
d’onda della tensione può essere disturbata quando vengono
utilizzati azionamenti a frequenza variabile non filtrati.
Riparazione guasto
Nel caso in cui siano presenti azionamenti a frequenza
variabile, assicurarsi che siano installati i filtri EMI appropriati.
Numero di lampeggi
5
Allarme
Condizione del rotore bloccato (durante la rampa)
Descrizione allarme
Se la corrente di carico è ≥ 4 * Ie volte il valore di FLC
programmato per 100ms, l' RSBT attiverà l'allarme rotore
bloccato.
Tempo di ripristino allarme
5 minuti
Allarmi consecutivi che richiedono un
RESET completo
2
Azione per disattivare l'allarme
L’allarme si disattiva trascorsi 5 minuti. Se l’avviatore statico
rimane in allarme per più di 5 minuti (a causa di allarmi
consecutivi), è necessario un ripristino dell’alimentazione
(ripristino di L1, L2, L3).
Riparazione guasto
Verificare che il modello di RSBT scelto sia adatto
all’applicazione.
Verificare che gli avvolgimenti del motore non siano
danneggiati.
Numero di lampeggi
6
Allarme
Tempo di accelerazione (> 1 sec)
Descrizione allarme
L'RSBT attiverà questo allarme se il compressore non raggiunge
la velocità massima entro 1 secondo. Questo allarme protegge i
relè di bypass dalla commutazione di una corrente elevata.
Tempo di ripristino allarme
5 minuti
Allarmi consecutivi che richiedono un
RESET completo
2
Azione per disattivare l'allarme
L’allarme si ripristinerà automaticamente dopo un periodo di 5
minuti.
Se l’allarme viene attivato due volte consecutivamente, l’utente
deve spegnere (OFF) e poi ON (L1, L2, L3) per eseguire un reset
hardware. Questo resetterà l’allarme.
Riparazione guasto
Verificare che venga utilizzato il modello corretto di
RSBT
Verificare che i collegamenti al compressore siano
corretti
Controllare eventuali blocchi meccanici sul compressore
Ricerca guasti ITA
Numero di lampeggi
7
Allarme
Sovra temperatura
Descrizione allarme
L' RSBT misura costantemente la temperatura del dissipatore e
degli SCR. Se la temperatura interna massima ammessa viene
superata ( per un minimo di 0,5s ) l'allarme per sovra temperatura
viene attivato. Questa condizione può essere causata da un
eccessivo numero di partenze per ora, da una condizione di
sovraccarico durante la rampa di avvio e/o durante la rampa di
arresto o da una eccessiva temperatura ambiente.
Tempo di ripristino allarme
In funzione del tempo di raffreddamento.
L' RSBT si riattiva solo se la temperatura è rientrata nei limiti
massimi ammessi.
Allarmi consecutivi che richiedono un
RESET completo
4
Azione per disattivare l'allarme
L'allarme si disattiva (in modalità AUTO) autonomamente - il
periodo di ripristino dipende dal tempo di raffreddamento
necessario al RSBT. Maggiore è la temperatura ambiente,
maggiore sarà il tempo necessario per la disattivazione
dell'allarme.
Riparazione guasto
Verificare che non sia stato superato il numero massimo
di partenze/h consentito.
Verificare che la temperatura ambiente dove è installato
il componente sia entro i limiti ammessi.
Numero di lampeggi
8
Allarme
Corrente non normale (durante il bypass)
Descrizione allarme
Il RSBT misura la corrente durante lo stato di bypass. Se la
corrente è> 1,15 * Ie per almeno 1 secondo, l’RSBT attiverà
questo allarme e spegnerà l’uscita. Questa condizione può essere
causata da un sovraccarico condizione o perché il modello RSBT
sotto dimensionato per il carico che sta controllando.
Tempo di ripristino allarme
5 minuti
Allarmi consecutivi che richiedono un
RESET completo
2
Azione per disattivare l'allarme
L’allarme si ripristinerà automaticamente dopo un periodo di 5
minuti.
Se l’allarme viene attivato due volte consecutivamente, l’utente
deve spegnere (OFF) e poi ON (L1, L2, L3) per eseguire un reset
hardware. Questo resetterà l’allarme.
Riparazione guasto
Verificare che venga utilizzato il modello corretto di
RSBT.
Verificare che i collegamenti al compressore siano
corretti.
Misurare la corrente con una pinza
amperometrica su una qualsiasi delle fasi L1, L2, L3 e
verificare se la corrente rientra nei livelli previsti. Se la
corrente è superiore alla corrente nominale RSBT,
cambiare il RSBT in un modello più grande.
Ricerca guasti ITA
Numero di lampeggi
9
Allarme
Tensione di linea squilibrata
Descrizione allarme
L' RSBT effettua la misurazione della tensione di linea e se
verifica che esiste una differenza superiore al 10% per un tempo
≥ 5s fra due qualsiasi delle tre fasi di ingresso, attiva la
segnalazione di allarme.
Tempo di ripristino allarme
5 minuti (dal momento in cui lo squilibrio di tensione % tra tutte le
fasi è <10%)
Allarmi consecutivi che richiedono un
RESET completo
N/A
Azione per disattivare l'allarme
L’allarme inizierà un auto-recupero di 5 minuti dal momento in cui
le tensioni su L1, L2, L3 si trovano entro il 10% l’una dall’altra. Se
lo squilibrio di tensione rimane> 10%, il RSBT rimarrà in stato di
allarme.
Riparazione guasto
Controllare eventuali collegamenti allentati sulla rete e
sul lato di carico.
Controllare la tensione su L1 - L2, L2 - L3, L1 - L3 e
vedere se ci sono sbilanciamenti.
Controllare la resistenza sugli avvolgimenti del motore
per vedere se una qualsiasi delle bobine è danneggiata.
Défauts FR
Carlo Gavazzi RSBT Troubleshooting Guide Rev 1.0 16
LED d'indication d'état
Etat
Alimentation
(LED verte)
Alarme
(LED rouge)
Marche à vide
ALLUMÉE
OFF
État accélération
ALLUMÉE
OFF
Bipasse
ALLUMÉE
OFF
Alarme
ALLUMÉE
Clignotement
Indication d’état relais
Etat
Alimentation
(LED verte)
Position des contacts de relais
RSBT 45 mm
(V21..)
RSBT 120 mm
(CV0/CVC)
Alarme
(11, 12, 14)
Alarme
(11, 12, 14)
Bipasse
(21, 22, 24)
Marche à vide
ALLUMÉE
11, 14
11, 12
21, 22
État accélération
ALLUMÉE
11, 14
11, 12
21, 22
Bipasse
ALLUMÉE
11, 14
11, 12
21, 24
Alarme
ALLUMÉE
11, 12
11, 14
21, 22
Alarmes
Le RSBT intègre un certain nombre de fonctions de diagnostic et de protection, chaque fonction étend signalée
par une diode rouge qui clignote en séquence.
Défauts FR
Carlo Gavazzi RSBT Troubleshooting Guide Rev 1.0 17
Nombre de clignotements
2
Alarme
Erreur de séquence de phases
Description de l'alarme
Si la connexion au démarreur progressif est mal séquencée
(différente de la séquence L1, L2, L3), le RSBT déclenche une
alarme Erreur de Séquence de Phase et interdit le démarrage du
moteur.
Période d'acquittement d'une alarme
N/A
Alarmes consécutives pour
REDÉMARRAGE À FROID
1
Intervention d'acquittement d'une alarme
Une intervention de l’utilisateur est requise pour modifier l’ordre
de câblage et acquitter une alarme.
Localisation de défauts
Constater que la séquence de câblage L1, L2, L3 est
correcte.
Nombre de clignotements
3
Alarme
Tension de ligne hors limites
Description de l'alarme
Les modèles RSBT 48 ont des limites d'alarme fixes de
surtension et de sous-tension. Lorsque la tension du secteur est
hors de ces limites pendant plus de 5 secondes, l'alarme de
tension de ligne hors plage se déclenche. Les modèles RSBT40
ont des limites d'alarme de surtension et de sous-tension auto-
réglables, qui peuvent également être modifiées par l'utilisateur. À
moins qu'ils ne soient modifiés, ils s'ajusteront automatiquement
en fonction de la tension d'alimentation. Une fois que l'un ou les
deux sont modifiés, le ou les changements seront conservés
jusqu'à ce que l'utilisateur modifie à nouveau l'une ou les deux
limites. Lorsque la tension secteur est en dehors de ces limites
pendant plus de 5 secondes, l'alarme de tension secteur hors
plage est déclenchée.
Modèle
Limites de sous-
tension
Limites de
surtension
RSBT40
187/330
250/470
RSBT48
175
560
Période d'acquittement d'une alarme
5 minutes
Alarmes consécutives pour
REDÉMARRAGE À FROID
4
Intervention d'acquittement d'une alarme
En mode Acquittement Auto, l'alarme est automatiquement
acquittée 5 minutes après rétablissement de la tension
d'alimentation dans ses limites.
Localisation de défauts
Mesurer la tension d'alimentation aux bornes L1, L2, L3.
Le cas échéant, ne jamais utiliser un RSBT40 à une
tension d'alimentation > 440 VCA.
Défauts FR
Carlo Gavazzi RSBT Troubleshooting Guide Rev 1.0 18
Nombre de clignotements
4
Alarme
Fréquence hors gamme
Description de l'alarme
Si la fréquence mesurée par le RSBT est supérieure à 66,5Hz Hz
et inférieure à 44,5Hz Hz pendant 1 seconde minimum, cette
alarme sera activée.
Période d'acquittement d'une alarme
5 minutes
Alarmes consécutives pour
REDÉMARRAGE À FROID
N/A
Intervention d'acquittement d'une alarme
Constater l’absence de perturbations sur le réseau de tension.
Les entraînements à fréquence variable non filtrés sont
susceptibles de perturber la forme d’onde.
Localisation de défauts
En cas d’utilisation d’entraînements à fréquence variable,
vérifier la présence de filtres EMI adéquats.
Nombre de clignotements
5
Alarme
Condition du rotor bloqué (pendant la rampe)
Description de l'alarme
Si un courant est ≥ à 4 fois le courant de pleine charge défini,
pendant 100 ms, le RSBT va déclencher une alarme rotor bloqué.
Période d'acquittement d'une alarme
5 minutes
Alarmes consécutives pour REDÉ-
MARRAGE À FROID
2
Intervention d'acquittement d'une alarme
L’alarme est automatiquement acquittée 5 minutes plus tard. Si le
démarreur progressif reste en alarme pendant plus de 5 minutes
(suite à des alarmes consécutives), une réinitialisation de
l’alimentation (réinitialisation de L1, L2, L3) est requise.
Localisation de défauts
S’assurer que la version du RSBT est conforme aux
caractéristiques du moteur.
Nombre de clignotements
6
Alarme
Temps d’accélération (> 1sec)
Description de l'alarme
Le RSBT déclenchera cette alarme si le compresseur n'atteint
pas sa vitesse maximale en moins d'une seconde. Cette alarme
empêche les relais de bypass de commuter un courant élevé.
Période d'acquittement d'une alarme
5 minutes
Alarmes consécutives pour
REDÉMARRAGE À FROID
2
Intervention d'acquittement d'une alarme
Le rétablissement post alarme est automatique au bout de 5
minutes.
En cas de deux déclenchements consécutifs de l’alarme, mettre
le secteur Sous Tension puis Hors Tension (L1, L2, L3) afin de
réinitialiser le démarreur progressif (impératif). Cette opération
réinitialise l’alarme.
Localisation de défauts
Constater l’adéquation de la version du RSBT utilisé.
Constater la qualité des connexions du compresseur.
Constater l’absence de tout blocage mécanique du
compresseur.
Défauts FR
Carlo Gavazzi RSBT Troubleshooting Guide Rev 1.0 19
Nombre de clignotements
7
Alarme
Surchauffe
Description de l'alarme
Le démarreur progressif RSBT mesure constamment la
température du dissipateur thermique et des thyristors (SCR).
Une alarme de surchauffe déclenche sur dépassement de la
température maximale interne pendant 0,5 s minimum. Un
déclenchement par surchauffe peut-être dû à un nombre de dé-
marrages horaires trop important, une condition de surcharge au
démarrage/à l'arrêt ou une haute température ambiante.
Période d'acquittement d'une alarme
Dépend de la période de refroidissement.
L'acquittement de l'alarme de surchauffe a lieu seulement si la
température interne se situe à l'intérieur des limites sécuritaires.
Alarmes consécutives pour
REDÉMARRAGE À FROID
4
Intervention d'acquittement d'une alarme
En mode acquittement auto, l'acquittement automatique de
l'alarme dépend de la période de refroidissement requise par le
RSBT. Plus la température ambiante est élevée plus la période de
refroidissement est longue.
Localisation de défauts
Constater l'absence de dépassement du nombre de
démarrages horaires.
Constater l'absence de dépassement de la température
ambiante aux abords du démarreur progressif.
Nombre de clignotements
8
Alarme
Courant anormal (en cours de bypasse)
Description de l'alarme
Le RSBT mesure le courant à l’état bipassé. Si le courant est
supérieur à 1,15* x Ie pendant 1 seconde minimum, le RSBT
déclenche cette alarme et désactive la sortie. Cette condition peut
se produire en cas de surcharge ou de déclassement de la
version du RSBT par rapport à la charge qu’il contrôle.
Période d'acquittement d'une alarme
5 minutes
Alarmes consécutives pour
REDÉMARRAGE À FROID
2
Intervention d'acquittement d'une alarme
Le rétablissement post alarme est automatique au bout de 5
minutes. En cas de deux déclenchements consécutifs de l’alarme,
mettre le secteur Hors puis Sous Tension (L1, L2, L3) afin de
réinitialiser le démarreur progressif (impératif). Cette opération
réinitialise l’alarme.
Localisation de défauts
Constater l’adéquation de la version du RSBT utilisé.
Constater la qualité des connexions du compresseur.
Muni d’un ampèremètre à pinces, mesurer le courant sur
l’une des phases L1, L2, L3 et constater que la valeur indiquée se
situe à l’intérieur des limites prévues. Si le courant est supérieur
au courant nominal du RSBT, remplacer le RSBT par une version
supérieure.
Nombre de clignotements
9
Alarme
Déséquilibre de la tension d'alimentation
Description de l'alarme
Le RSBT mesure les tensions sur les trois phases. Si le delta
entre phases quelconques est supérieur à 20% pendant 5
secondes ou plus, le RSBT déclenche une alarme de déséquilibre
de tension.
Période d'acquittement d'une alarme
5 minutes (à partir du moment où le % de déséquilibre de tension
entre toutes les phases est <10%)
Alarmes consécutives pour
REDÉMARRAGE À FROID
N/A
Intervention d'acquittement d'une alarme
L’alarme démarre un rétablissement automatique de 5 minutes
dès que les tensions L1, L2, L3 se situent dans les limites de 10%
les unes par rapport aux autres.
Défauts FR
Carlo Gavazzi RSBT Troubleshooting Guide Rev 1.0 20
Localisation de défauts
Constater le bon serrage des connexions, côté secteur
et côté charge.
Vérifier la tension aux bornes L1 - L2, L2 - L3, L1 - L3 et
constater la présence d’un éventuel déséquilibre.
Vérifier la résistance des enroulements du moteur afin
de détecter une avarie éventuelle des bobines.
Soluciones ES
Indicaciones LED de los estados
Estado
Alimentación (LED verde)
Alarma
(LED rojo)
Reposo
ON
OFF
Rampa
ON
OFF
Bypass
ON
OFF
Alarma
ON
PARPADEANDO
Indicación del estado del relé
Estado
Alimentación
(LED verde)
Posición de contacto del relé
RSBT 45 mm
(V21..)
RSBT 120 mm
(CV0, CVC)
Alarma
(11, 12, 14)
Alarma
(11, 12, 14)
Bypass
(21, 22, 24)
Reposo
ON
11, 14
11, 12
21, 22
Rampa
ON
11, 14
11, 12
21, 22
Bypass
ON
11, 14
11, 12
21, 24
Alarma
ON
11, 12
11, 14
21, 22
Alarmas
RSBT incluye diagnósticos y protecciones que se indican mediante la secuencia de parpadeos del LED rojo.
Soluciones ES
Carlo Gavazzi RSBT Troubleshooting Guide Rev 1.0 22
Número de parpadeos
2
Alarma
Secuencia incorrecta de fases
Descripción de la alarma
Si la conexión al arrancador suave no se realiza en la secuencia
correcta
(L1, L2, L3), RSBT disparará la alarma de secuencia incorrecta de
fases y el
motor no arrancará.
Periodo de recuperación de la alarma
No se aplica
Máximo n.º de reset consecutivos
1
Acción para auto-recuperar la alarma
Se necesita la intervención del usuario para cambiar la secuencia
de las conexiones, ya que la alarma no se auto-recupera.
Resolución del problema
Comprobar que L1, L2 y L3 están conectadas en la
secuencia correcta.
Número de parpadeos
3
Alarma
Tensión de línea fuera de rango
Descripción de la alarma
RSBT 48 tiene establecidos límites de alarma por nivel alto o bajo
de la tensión de alimentación. Si el nivel está fuera de estos
límites durante más de 5 segundos, se disparará la alarma por
tensión de alimentación fuera de rango. Los modelos RSBT40
tienen límites de alarma de sobrevoltaje y bajo voltaje
autoajustables, que el usuario también puede modificar. A menos
que se modifiquen, se ajustarán automáticamente de acuerdo con
la tensión de alimentación. Una vez que se modifique alguno o
ambos, los cambios se conservarán hasta que el usuario cambie
de nuevo alguno o ambos límites. Cuando el voltaje de la red está
fuera de estos límites durante más de 5 segundos, se activará la
alarma de voltaje de línea fuera de rango.
Modelo
Límite baja
tensión
Límite alta
tensión
RSBT40
187/330
250/470
RSBT48
175
560
Periodo de recuperación de la alarma
5 minutos
Máximo n.º de reset consecutivos
4
Acción para auto-recuperar la alarma
La alarma se recuperará automáticamente transcurridos 5
minutos desde que la tensión de alimentación esté dentro de los
límites.
Resolución del problema
Comprobar el nivel de tensión de alimentación a través
de los terminales L1, L2 y L3.
Asegurarse de que no se está usando un modelo
RSBT40 con tensión de alimentación > 440VCA.
Soluciones ES
Carlo Gavazzi RSBT Troubleshooting Guide Rev 1.0 23
Número de parpadeos
4
Alarma
Frecuencia fuera de rango
Descripción de la alarma
Si la frecuencia medida por RSBT es >66.5 Hz y <44.5 Hz
durante más de 1 segundo, esta alarma se activará.
Periodo de recuperación de la alarma
5 minutos
Máximo n.º de reset consecutivos
No se aplica
Acción para auto-recuperar la alarma
Comprobar cualquier anomalía en la tensión de red. El uso de
variadores de frecuencia sin filtro puede afectar a la forma de
onda de tensión.
Resolución del problema
En caso de existir variadores de frecuencia, asgurar que
están instalados los filtros EMI adecuados.
Número de parpadeos
5
Alarma
Condición del rotor bloqueado (durante la rampa)
Descripción de la alarma
Si se detecta una intensidad de ≥ 4xIe durante 100 msegundos,
RSBT activará la alarma de rotor bloqueado.
Periodo de recuperación de la alarma
5 minutos
Máximo n.º de reset consecutivos
2
Acción para auto-recuperar la alarma
La alarma se recuperará automáticamente después de 5 minutos.
Si el arrancador suave permanece en alarma durante más de 5
minutos (debido a alarmas consecutivas), hay que reiniciar la
alimentación (reset de L1, L2, L3).
Resolución del problema
Comprobar que el modelo RSBT elegido es adecuado
para el motor.
Comprobar la resistencia del bobinado del motor para
saber si el motor está dañado.
Número de parpadeos
6
Alarma
Tiempo de rampa ascendente (> 1 segundo)
Descripción de la alarma
RSBT disparará esta alarma si el compresor no alcanza la
velocidad nominal en 1 segundo. Esta alarma protege los relés de
bypass de una conmutación a alta intensidad.
Periodo de recuperación de la alarma
5 minutos
Máximo n.º de reset consecutivos
2
Acción para auto-recuperar la alarma
La alarma se autorecuperará después de un periodo de 5 minutos.
Si la alarma se activa dos veces consecutivas, el usuario debe
desconectar y conectar de nuevo la tensión (L1,L2,L3) para hacer
un reset. Esto reiniciará la alarma.
Resolución del problema
Comprobar que se está utilizando el modelo correcto de
RSBT
Comprobar que las conexiones al compresor son
correctas
Comprobar si hay bloqueo mecánico en el compresor
Soluciones ES
Carlo Gavazzi RSBT Troubleshooting Guide Rev 1.0 24
Número de parpadeos
7
Alarma
Sobretemperatura
Descripción de la alarma
RSBT mide constantemente la temperatura del disipador y de los
tiristores (SCR). Si se supera la máxima temperatura interna
(durante un mínimo de 0,5 segundos) se dispara la alarma de
sobretemperatura. Esta condición puede generarse debido a:
demasiados arranques por hora, condición de sobrecarga durante
el arranque y/o parada o alta temperatura ambiente.
Periodo de recuperación de la alarma
Depende del periodo de enfriamiento.
RSBT se recuperará si la temperatura interna está dentro de los
límites de seguridad.
Máximo n.º de reset consecutivos
4
Acción para auto-recuperar la alarma
La alarma se recuperará automáticamente (en modo de
recuperación automática) el periodo de recuperación depende
del tiempo de enfriamiento requerido por RSBT. Cuanto mayor es
la temperatura ambiente, más se prolongará el tiempo de
enfriamiento.
Resolución del problema
Comprobar que no se supera el número especificado de
arranques/hora.
Comprobar que la temperatura ambiente del entorno del
arrancador está dentro de los límites.
Número de parpadeos
8
Alarma
Corriente anómala (durante el bypass)
Descripción de la alarma
RSBT mide la corriente durante el estado de bypass. Si la
corriente es >1.15 x Ie más de 1 segundo, RSBT activará esta
alarma y desconectará la salida. Esta condición puede ocurrir en
caso de sobrecarga o porque el modelo de RSBT es pequeño
para la carga que controla.
Periodo de recuperación de la alarma
5 minutos
Máximo n.º de reset consecutivos
2
Acción para auto-recuperar la alarma
La alarma se autorecuperará después de un periodo de 5 minutos.
Si la alarma se activa dos veces consecutivas, el usuario debe
desconectar y conectar de nuevo la tensión (L1,L2,L3) para hacer
un reset. Esto reiniciará la alarma.
Resolución del problema
Comprobar que se está utilizando el modelo correcto de
RSBT.
Comprobar que las conexiones al compresor son
correctas.
Medir la corriente con una pinza amperimétrica en
cualquiera de las fases L1,L2,L3 y comprobar que la corriente
esté dentro de los niveles estimados. Si la corriente es superior a
la nominal de RSBT, cambiar el arrancador RSBT por otro
modelo superior.
Soluciones ES
Carlo Gavazzi RSBT Troubleshooting Guide Rev 1.0 25
Número de parpadeos
9
Alarma
Tensión de alimentación desequilibrada
Descripción de la alarma
RSBT mide los niveles de tensión en las 3 fases y si hay una
diferencia de al menos un 10% entre cualquiera de ellas durante
5 segundos, RSBT disparará la alarma de tensión desequilibrada
y desconectará la salida.
Periodo de recuperación de la alarma
5 minutos
Máximo n.º de reset consecutivos
N/A
Acción para auto-recuperar la alarma
La alarma comenzará un periodo de autorecuperación de 5
minutos desde el momento que la diferencia de tensión entre
fases sea inferior a un 10%. Si el desequilibrio de tensión
permanece > 10%, RSBT permenecerá en estado de alarma.
Resolución del problema
Comprobar si hay alguna pérdida de conexión en la red
y en el lado de la carga.
Comprobar la tensión entre L1-L2, L2-L3, L1-L3 y ver si
hay algún desequilibrio.
Comprobar la resistencia en los devanados del motor
para ver si están dañados.
Fejlfinding DAN
LED-statusindikationer
Forsyning
(grøn LED)
Rampe/Bypass
(gul LED)
Alarm
(rød LED)
Idle
TIL
FRA
Rampe
TIL
Blinker
Bypass
TIL
FRA
Alarmtilstand
TIL
FRA
Relæ statusindikering
Tilstand
Forsyning
(grøn LED)
Position for relækontakt
RSBT 45 mm
(V21..)
RSBT 120 mm
(CV0, CVC)
Alarm
(11, 12, 14)
Alarm
(11, 12, 14)
Bypass
(21, 22, 24)
Idle
TIL
11, 14
11, 12
21, 22
Rampe
TIL
11, 14
11, 12
21, 22
Bypass
TIL
11, 14
11, 12
21, 24
Alarmtilstand
TIL
11, 12
11, 14
21, 22
Alarmer
RSBT'en indeholder en række funktioner til diagnosticering og beskyttelse. Disse varsles med en sekvens af
røde LED-blink.
Fejlfinding DAN
Carlo Gavazzi RSBT Troubleshooting Guide Rev 1.0 27
Antal blink
2
Alarm
Forkert fasefølge
Alarmbeskrivelse
Hvis tilslutning til softstarteren ikke sker i den korrekte sekvens
(L1, L2, L3), vil RSBT’en udløse alarmen for forkert fasefølge, og
motoren vil ikke blive startet.
Alarmgenoprettelsesperiode
N/A
Fortløbende alarmer til hoved-
NULSTILLING
1
Handling til alarmgenoprettelse
Brugeren skal aktivt ændre forbindelsessekvensen for at
genoprette alarmen.
Fejlfinding
Kontrollér, at forbindelserne i L1, L2, L3 er i korrekt
sekvens.
Antal blink
3
Alarm
Linjespænding uden for normalområde
Alarmbeskrivelse
RSBT-48 modeller har faste overspændinger og under
spændingsalarmgrænser. Når netspændingen er uden for disse
grænser i mere end 5 sekunder, udløses ”netspænding” uden for
område alarmen. RSBT40-modeller har automatisk justerbare
over- og underspændingsalarmgrænser, som også kan ændres af
brugeren. Medmindre de ændres, justeres de automatisk i
henhold til forsyningsspændingen. Når en eller begge er ændret,
bevares ændringerne, indtil brugeren igen ændrer en eller begge
grænser. Når netspændingen er uden for disse grænser i mere
end 5 sekunder, udløses alarmen for netspænding uden for
området.
Model
Under
spændings-
grænser
Overspændings-
grænser
RSBT40
187/330
250/470
RSBT48
175
560
Alarmgenoprettelsesperiode
5 minutter
Fortløbende alarmer til hoved-
NULSTILLING
4
Handling til alarmgenoprettelse
Alarmen vil genoprettes af sig selv 5 minutter efter at
forsyningsspændingen igen er inden for grænserne.
Fejlfinding
Kontrollér forsyningsspændingsniveauet på tværs af L1,
L2, L3 klemmerne.
Vær opmærksom på, at du ikke anvender en RSBT40
model på en forsyningsspænding > 440 VAC.
Fejlfinding DAN
Carlo Gavazzi RSBT Troubleshooting Guide Rev 1.0 28
Antal blink
4
Alarm
Frekvens uden for området
Alarmbeskrivelse
Hvis frekvensen målt af RSBT er >66.5Hz og <44.5Hz i mindst 1
sekund, vil denne alarm blive udløst.
Alarmgenoprettelsesperiode
5 minutter
Fortløbende alarmer til hoved-
NULSTILLING
N/A
Handling til alarmgenoprettelse
Kontroller om der er forstyrrelser på spændingsnetværket.
Spændingsbølgeformen kan blive forstyrret, når der anvendes
ufiltrerede variable frekvensdrev.
Fejlfinding
I tilfælde af, at frekvensomformere er til stede, skal du
sørge for, at de korrekte EMI-filtre er installeret.
Antal blink
6
Alarm
Rampe-op-tid (> 1sec)
Alarmbeskrivelse
RSBT udløser denne alarm, hvis kompressoren ikke når fuld
hastighed inden for 1 sekund. Denne alarm beskytter bypass-
relæerne mod at indkoble ved for høj strøm.
Alarmgenoprettelsesperiode
5 minutter
Fortløbende alarmer til hoved-
NULSTILLING
2
Handling til alarmgenoprettelse
Alarmen genopretter sig selv efter en periode på 5 minutter.
Hvis alarmen udløses to gange i træk, skal brugeren SLUKKE og
derefter TÆNDE for lysnettet (L1, L2, L3) for at udføre en fuld
nulstilling. Derved bliver alarmen nulstillet.
Fejlfinding
Kontroller at den rigtige model af RSBT anvendes
Kontroller om tilslutningerne til kompressoren er korrekte
Kontroller om der findes nogen mekanisk blokering på
kompressoren
Antal blink
7
Alarm
Overtemperatur
Alarmbeskrivelse
RSBT'en måler konstant temperaturen for køleplade og tyristorer
(SCR'er). Hvis den maksimale interne temperatur overstiges (i
mindst 0,5 sek.), udløses en alarm for overtemperatur. Denne
situation kan opstå pga. for mange opstarter i timen, et
overbelastningsforhold under start og/eller stop eller en høj
omgivende temperatur.
Alarmgenoprettelsesperiode
Afhænger af afkølingsperioden.
RSBT'en vil kun genoprettes, hvis den interne temperatur ligger
inden for sikre grænser.
Fortløbende alarmer til hoved-
NULSTILLING
4
Handling til alarmgenoprettelse
Alarmen vil genoprettes af sig selv (i tilstanden Automatisk
genoprettelse) genoprettelsesperioden afhænger af den
afkølingsperiode, der er påkrævet for RSBT'en. Jo højere den
omgivende temperatur er, desto længere er afkølingsperioden.
Fejlfinding
Kontrollér, at det angivne antal starter i timen ikke er
overskredet.
Kontrollér, at den omgivende temperatur omkring
softstarteren ligger inden for grænserne.
Fejlfinding DAN
Carlo Gavazzi RSBT Troubleshooting Guide Rev 1.0 29
Antal blink
8
Alarm
Strømmen er ikke normal (under overgang)
Alarmbeskrivelse
RSBT måler strømmen under overgangs-tilstand. Hvis strømmen
er >1,15 * Ie i mindst 1 sekund, udløser RSBT denne alarm og
SLUKKER for udgangen. Denne tilstand kan resultere i en
overbelastning eller fordi RSBT-modellen er undervurderet for den
belastning, den styrer.
Alarmgenoprettelsesperiode
5 minutter
Fortløbende alarmer til hoved-
NULSTILLING
2
Handling til alarmgenoprettelse
Alarmen genopretter sig selv efter en periode på 5 minutter.
Hvis alarmen udløses to gange i træk, skal brugeren SLUKKE og
derefter TÆNDE for lysnettet (L1, L2, L3) for at udføre en fuld
nulstilling. Dette vil nulstille alarmen.
Fejlfinding
Kontrollér at den korrekte model af RSBT bruges.
Kontroller om tilslutningerne til kompressoren er
korrekte.
Mål strømmen med en klemmåler i en hvilken som helst
af L1, L2, L3- faserne og kontroller om strømmen er inden for de
forventede niveauer. Hvis strømmen er højere end RSBT-nominel
strøm, skal du ændre RSBT til en større model.
Antal blink
9
Alarm
Ubalance i forsyningsspænding
Alarmbeskrivelse
RSBT måler spændingen i alle tre faser, og hvis der er en forskel
mere end 10% mellem nogen af L1, L2, L3 i mindst 5
sekunder, vil RSBT’en udløse alarmen 9. Når alarmen udløses
RSBT vil slukke for udgangen.
Alarmgenoprettelsesperiode
5 minutter (fra det øjeblik, hvor % spændingsbalancen mellem alle
faser er <10%)
Fortløbende alarmer til hoved-NUL-
STILLING
N/A
Handling til alarmgenoprettelse
Alarmen genstarter 5 minutter fra det øjeblik, spændingerne på
L1, L2, L3 ligger inden for 10% fra hinanden. Hvis spændings-
ubalancen forbliver >10%, forbliver RSBT i alarmtilstand.
Fejlfinding
Kontroller, om der er løse forbindelser på net- og
belastningssiden.
Kontroller spændingen over L1 - L2, L2 - L3, L1 - L3 og
se om der er nogen ubalance.
Kontroller modstanden på motorviklingerne for at se om
nogen af spolerne er beskadiget.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29