Wiremold 30TC-2V Guía de instalación

Tipo
Guía de instalación
Wiremold
®
Tele-Power
®
Poles
Poteaux Tele-Power
®
Barras Tele-Power
®
30TC-2V, 30TP-2V
Country of Origin: Made in USA • Fabriqué en USA • Hecho en USA

Please read all instructions before
beginning installation
Legrand electrical systems conform to and
should be properly grounded in compliance with
requirements of the current National Electrical
Code or codes administered by local authorities.
All electrical products may present a possible
shock or re hazard if improperly installed or used.
Legrand electrical products may bear the mark of
a Nationally Recognized Testing Laboratory and
should be installed in conformance with current
local and/or the National Electrical Code.

VEUILLEZ LIRE L'ENSEMBLE
DES INSTRUCTIONS AVANT DE
COMMENCER L'INSTALLATION.
Les systèmes électriques Legrand sont
conformes au Code National de l'électricité
(National Electrical Code) ou aux codes
locaux en vigueur et doivent être mis à la terre
conformément à ces codes.
Tous les produits électriques peuvent présenter
un risque d'électrocution ou d'incendie s'ils ne
sont pas installés ou utilisés correctement. Les
produits électriques Legrand peuvent porter la
marque d'un laboratoire reconnu et doivent être
installés conformément au Code national de
l'électricité et/ou aux codes locaux en vigueur.

Lea todas las instrucciones antes
de comenzar la instalación.
Los sistemas eléctricos Legrand cumplen con los
requisitos del Código Eléctrico Nacional (National
Electrical Code, NEC) actual o con los códigos
impuestos por las autoridades locales y deben
conectarse a tierra consecuentemente.
Todos los productos eléctricos pueden presentar
un riesgo de descarga o incendio si se los instala o
utiliza incorrectamente. Los productos eléctricos
Legrand pueden llevar la marca de un laboratorio
de pruebas reconocido a nivel nacional y se deben
instalar conforme al código local en vigencia o al
Código Eléctrico Nacional.

Installation Instructions • Notice d’Installation• Instrucciones de Instalación
30TC-2V*, 30TP-2V
COMMUNICATIONS
COMMUNICATIONS
COMUNICACIONES



30TC-2V* 30TP-2V
30TP-A

30TP-B 30TP-C
30TP-J

30TP-L 30TC-CVR
POWER or COMMUNICATIONS
ALIMENTATION ou COMMUNICATION
ALIMENTACIÓN o COMUNICACIONES



POWER
ALIMENTATION
ALIMENTACIÓN ELÉCTRICA
30TP-2V
30TC-2V*
* 30TC-2V Series not intended for combining power and communications in the same channel.

le même conduit.

en el mismo canal.
2
* 30TC-2V Series not intended for combining power and communications in the same channel.
    
   
     
Unshielded Cat. 5 UTP
0.22 5.59 14 28 18 37
Twisted Pair Cat. 3 UTP
0.19 4.83 19 38 25 50
2 Pair 0.14 3.56 35 70 46 90
Telephone
3 Pair 0.15 3.81 30 61 40 79
4 Pair 0.19 4.83 19 38 25 50
25 Pair 0.41 10.41 4 8 5 11
RG58/U 0.20 4.95 18 36 24 47
Coaxial RG59/U 0.24 6.15 12 23 15 31
RG62/U 0.24 6.15 12 23 15 31
RG6/U 0.27 6.86 9 19 12 25
TwinAxial
100 Ohm 0.33 8.38 6 13 8 16
Shielded
Type 1 STP 0.39 9.91 4 9 6 12
Twisted Pair
Type 2 STP 0.47 11.81 3 6 4 8
Type 3 STP 0.25 6.22 11 23 15 30
Fiber ZipCord
0.11 2.79 56 113 74 14
Fiber Optic
Round Fiber 2 Strand
0.18 4.57 21 42 28 55
Round Fiber 4 Strand
0.19 4.83 19 38 25 50
Round Fiber 6 Strand
0.21 5.33 15 31 20 41

  
30TP-2V 30TC-2V*
     
   
THHN / THWN 10 Awg 0.16 4.17 10 10
12 Awg 0.13 3.30 15 15



de câble
Description de la

du
câble
D.E.
po mm
 

30TP-2V

30TC-2V*
 
THHN / THWN 10 Awg
0.16 4.17
10 10
12 Awg
0.13 3.30 15 15




Description D.E. 30TP-2V 30TC-2V
   
câble du câble
     
Paire torsadée UTP cat. 5
0,22 5,59 14 28 18 37
non blindée UTP cat. 3
0,19 4,83 19 38 25 50
2 paires 0,14 3,56 35 70 46 90
Téléphone
3 paires 0,15 3,81 30 61 40 79
4 paires 0,19 4,83 19 38 25 50
25 paires 0,41 10,41 4 8 5 11
RG58/U 0,20 4,95 18 36 24 47
Coaxial RG59/U 0,24 6,15 12 23 15 31
RG62/U 0,24 6,15 12 23 15 31
RG6/U 0,27 6,86 9 19 12 25
Twinax
100 Ohms 0,33 8,38 6 13 8 16
Paire torsadée
STP type 1 0,39 9,91 4 9 6 12
blindée
STP type 2 0,47 11,81 3 6 4 8
STP type 3 0,25 6,22 11 23 15 30
Fibre ZipCord
0,11 2,79 56 113 74 14
Fibre optique
Fibre ronde à 2 brins
0,18 4,57 21 42 28 55
Fibre ronde à 4 brins
0,19 4,83 19 38 25 50
Fibre ronde à 6 brins
0,21 5,33 15 31 20 41


3

2 3a
3b
Tipo de cable
Descripción cant.



 
PASO PASO
 
Serie AMDTP Serie 

 Comp. grande
PASO

PASO

PASO

PASO

THHN / THWN 10 Awg
0.16 4.17
10 10 34 44
12 Awg
0.13 3.30 15 15 54 69

ALIMENTACIÓN ELÉCTRICA
CUADROS DE CAPACIDAD DE PASO DE CONDUCTORES

Tipo de cable
-



Serie AMDTP
PASO
PASO
COND.
COND.



PASO
PASO
COND.
COND.



PASO
PASO
COND.
COND.


Comp. grande
PASO
PASO
COND.
COND.


Par trenzado
sin blindaje
Cat. 5 UTP
0.22 5.59 10 19 10 19 10 19 13 26
Cat. 3 UTP
0.19 4.83 13 25 13 25 13 25 17 35
Teléfono
2 Pares
0.14 3.56 23 47 23 47 23 47 32 64
3 Pares
0.15 3.81 20 41 20 41 20 41 28 56
4 Pares
0.19 4.83 13 25 13 25 13 25 17 35
25 Pares
0.41 10.41 3 5 3 5 3 5 4 7
RG58/U
0.20 4.95 12 24 12 24 12 24 17 33
Coaxial
RG59/U
0.24 6.15 8 16 8 16 8 16 11 21
RG62/U
0.24 6.15 8 16 8 16 8 16 11 21
RG6/U
0.27 6.86 6 13 6 13 6 13 9 17
Axial retorcido
100 ohmios
0.33 8.38 4 8 4 8 4 8 6 12
Par trenzado
con blindaje
Tipo 1 STP
0.39 9.91 3 6 3 6 3 6 4 8
Tipo 2 STP
0.47 11.81 2 4 2 4 2 4 3 6
Tipo 3 STP
0.25 6.22 8 15 8 15 8 15 10 21
Fibra óptica
ZipCord de fibra óptica
0.11 2.79 38 76 38 76 38 76 52 104
Fibra óptica, 2 hilos, sección circular
0.18 4.57 14 28 14 28 14 28 19 39
Fibra óptica, 4 hilos, sección circular
0.19 4.83 13 25 13 25 13 25 17 35
Fibra óptica, 6 hilos, sección circular
0.21 5.33 10 21 10 21 10 21 14 29




© Copyright 2013 Legrand All Rights Reserved.
© Copyright 2013 Tous droits réservés Legrand.
© Copyright 2013 Legrand Todos los derechos reservados.
860.233.6251
1.877.BY.LEGRAND
www.legrand.us
www.legrand.ca

 
head screw.
 

 


  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Wiremold 30TC-2V Guía de instalación

Tipo
Guía de instalación

en otros idiomas