USER GUIDE
10k / 15k / 20k / 30k / 40k / 60k S / 80k S HV (380 / 400 / 415V)
10k / 15k (S) / 20k (S) / 30k S / 40k S LV (208 / 220V)
Version française……………………………………………………………………………….2
English version…………………………………………………………………………………..57
Version española…………………………………………………….…………………….107
ربية
النسخة الع
…………………………...……………………………………..……….…….160
Version Française
1
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Table des matières
1. CONSIGNES DE SECURITE ET DE CEM........................................................................................................ 3
1-1. TRANSPORT ET ENTREPOSAGE ..................................................................................................................... 3
1-2. PREPARATION .............................................................................................................................................. 3
1-3. INSTALLATION............................................................................................................................................... 3
1-4. AVERTISSEMENTS RELATIFS AU RACCORDEMENT ............................................................................................ 4
1-5. OPERATION.................................................................................................................................................. 4
1-6. ENTRETIEN, REPARATION ET PANNES ............................................................................................................. 4
1-7. ENTRETIEN, REPARATION ET PANNES ............................................................................................................. 5
1-8. À PROPOS DES BATTERIES : .......................................................................................................................... 5
1-9. CONFORMITE CE : ....................................................................................................................................... 7
2. INSTALLATION ET FONCTIONNEMENT......................................................................................................... 8
2-1. DEBALLAGE ET INSPECTION .......................................................................................................................... 8
2-2. VUE DU PANNEAU ARRIERE ........................................................................................................................... 9
2-3. INSTALLATION A UPS UNIQUE ...................................................................................................................... 16
2-4. INSTALLATION DE L’UPS POUR LE SYSTEME PARALLELE ................................................................................ 20
2-5. INSTALLATION DU LOGICIEL ......................................................................................................................... 23
3. OPERATIONS .................................................................................................................................................. 24
3-1. FONCTIONNEMENT DU BOUTON ................................................................................................................... 24
3-2. INDICATEURS LED ET ECRAN LCD .............................................................................................................. 25
3-3. ALARME SONORE ....................................................................................................................................... 27
3-4. FONCTIONNEMENT UNIQUE DE L’UPS .......................................................................................................... 27
3-5. FONCTIONNEMENT EN PARALLELE ............................................................................................................... 31
3-6. SIGNIFICATION DES ABREVIATIONS SUR L’ECRAN LCD .................................................................................. 33
3-7. REGLAGE DE L’ECRAN LCD ........................................................................................................................ 33
3-8. MODE DE FONCTIONNEMENT/DESCRIPTION DES ETATS ................................................................................. 41
3-9. CODE DE DEFAUT ....................................................................................................................................... 47
3-10. VOYANT D’AVERTISSEMENT : L’ICONE CLIGNOTE........................................................................................... 48
3-11. CODE D’AVERTISSEMENT ............................................................................................................................ 48
4. DEPANNAGE................................................................................................................................................... 50
5. STOCKAGE ET ENTRETIEN .......................................................................................................................... 51
5-1. ENTREPOSAGE .......................................................................................................................................... 51
5-2. ENTRETIEN ................................................................................................................................................ 52
6. SPECIFICATIONS TECHNIQUES................................................................................................................... 53
2
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
1. Consignes de sécurité et de CEM
Veuillez respecter strictement toutes les consignes d’utilisation de ce manuel.
Conservez ce manuel dans un endroit sûr et lisez attentivement les instructions
suivantes avant d’installer l’appareil. N’utilisez pas l’appareil avant d’avoir lu
attentivement tous les avertissements et toutes les consignes d’utilisation.
IMPORTANT !
L’installation et le raccordement des onduleurs d’une manière non conforme dégage Infosec
Communication de toute responsabilité.
1-1. Transport et entreposage
Transportez l’onduleur uniquement dans son emballage d’origine pour le protéger contre les chocs et
les impacts.
l’onduleur doit être entreposé dans une salle ventilée et sans humidité.
1-2. Préparation
De la condensation peut se produire si l’onduleur est déplacé directement d’un environnement froid à
un environnement chaud. L’onduleur doit être parfaitement sec avant d’être installé. Veuillez laisser
l’onduleur reposer pendant au moins deux heures pour s’acclimater à l’environnement.
N’installez pas l’onduleur près de l’eau ou dans un environnement humide.
N’installez pas l’onduleur dans un endroit où il pourrait être exposé à la lumière directe du soleil ou
près d’un radiateur.
N’obstruez pas les orifices de ventilation de l’onduleur.
N’obstruez pas les orifices de ventilation du boîtier de l’UPS. L’onduleur doit être
installé dans un endroit bien aéré ou doté de la climatisation. Assurez-vous qu’il y a
suffisamment d’espace de chaque côté pour la ventilation. En principe, la température
ambiante ne doit pas dépasser 20 °C, avec une humidité relative sans condensation
comprise entre 0 et 90 %.
1-3. Installation
3
Ne branchez aucun appareil ou dispositif susceptible de surcharger l’onduleur
Ne branchez aucun appareil électroménager tel que les séchoirs en sortie de l’onduleur.
Disposez les câbles de telle sorte que personne ne puisse marcher ou trébucher dessus.
L’onduleur ne peut être installé que par un personnel de maintenance qualifié.
Un dispositif de déconnexion approprié doit être installé pour protéger le câblage du bâtiment contre
les courts-circuits.
L’installation et le câblage doivent être réalisés conformément aux réglementations et normes locales
en vigueur.
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
1-4. Avertissements relatifs au raccordement
Il n’y a pas protection « anti-retour » à l’intérieur. Veuillez isoler l’onduleur avant d’effectuer tout travail
sur ce circuit électrique. Un dispositif d’isolement type contacteur doit être installé en amont de
l’onduleur.
Input Rly
Main
Input
Input Rly
Main
Input
L1
L1
L2
L3
N
Input Rly
L2
UPS
L3
Bypass
Input
N
L1
UPS
L2
L3
N
Schéma contacteur d’entrée
Schéma contacteur d’entrée
E4 Evolution II + 10/15/20k TT HV
E4 Evolution II + 10/15/20k TT HV
E4 Evolution II + 10k TT LV
E4 Evolution II + 10k TT LV
(double alimentation en option)
E4 Evolution II + 30/40/60/80k TT HV
E4 Evolution II + 15/20/30/40k TT LV
•
L’alimentation de cet appareil doit être triphasée neutre et conforme aux indications de la
plaque signalétique de l’équipement. Il doit aussi être correctement relié à la terre.
•
Il n’est poas recommandé d’utiliser de cet équipement dans les applications de maintien des fonctions
vitales où un dysfonctionnement de celui-ci peut provoquer une panne de l’équipement de maintien des
fonctions vitales ou encore altérer notablement sa sécurité ou son efficacité. N’utilisez pas cet
équipement en présence de mélange anesthésique inflammable à l’air, à l’oxygène ou à l’oxyde nitreux.
•
Ce produit est destiné à une application commerciale et industrielle dans le environnement de type
secondaire. Des contraintes d’installation ou des mesures supplémentaires seront éventuellement
nécessaires pour minimiser les perturbations.
•
Des étiquettes d’avertissement doivent être apposées sur tous les interrupteurs d’alimentation primaires
installés loin de l’appareil pour avertir le personnel de maintenance électrique de la présence de
l’onduleur dans le circuit. L’étiquette doit mentionner le texte suivant ou un texte équivalent :
Avant d’intervenir sur ce circuit
- Isolez l’onduleur.
- Ensuite, vérifiez l’absence de tension dangereuse entre
toutes les bornes y compris la protection de mise à la terre.
Risque de retour de tension
1-5. Opération
4
Ne jamais débrancher le câble conducteur de mise à la terre, car cela stopperait la liaison à la mise à
la terre de l’onduleur et de toutes les charges connectées.
l’onduleur dispose de sa propre alimentation en courant interne (des batteries). Les bornes de sortie
de l’onduleur peuvent être sous tension, même si l’onduleur n’est pas branché sur le secteur.
Pour débrancher complètement l’onduleur, appuyez d’abord sur le bouton « ARRÊT », puis
débranchez l’alimentation secteur.
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Assurez-vous qu’aucun liquide ou corps étranger ne peut pénétrer à l’intérieur de l’onduleur.
1-6. Normes
* Sécurité
IEC/EN 62040-1
* Emission électromagnétique
Émission par conduction................................................... : CEI/EN 62040-2
Catégorie C3
Émission par rayonnement... ............. ............. ............... : CEI/EN 62040-2
Catégorie C3
* Susceptibilité électromagnétique
DES............................................................................... : CEI/EN 61000-4-2
Niveau 4
RS................................................................................... : CEI/EN 61000-4-
Niveau 3
EFT................................................................................ : CEI/EN 61000-4-4
Niveau 4
SURTENSION.................................... ........... .......... ... : CEI/EN 61000-4-5
Niveau 4
CS................................... ................... ..................... ... : CEI/EN 61000-4-6
Niveau 3
Champ magnétique de fréquence industrielle................ : CEI/EN 61000-4-8
Niveau 4
Signaux basse fréquence.............................................. : CEI/EN 61000-2-2
Mise en garde : Ce produit est destiné à une application commerciale et industrielle dans le
second environnement. Des contraintes d’installation ou des mesures supplémentaires
seront éventuellement nécessaires pour minimiser les perturbations.
1-7. Entretien, réparation et pannes
l’onduleur fonctionne avec des tensions dangereuses. Les réparations ne doivent être effectuées que
par un personnel qualifié.
Avertissement : risque de choc électrique. Même lorsque l’alimentation électrique de
l’appareil est coupée, les composants internes de l’onduleur sont toujours connectés à la
batterie, et sont donc sous tension et dangereux.
Avant d’effectuer tout entretien ou toute réparation, déconnectez les batteries et vérifiez qu’il n’y a
aucun courant dangereux ni aucune tension dangereuse aux bornes des condensateurs de grande
capacité tels que les condensateurs BUS DC.
Seules les personnes compétentes ou les personnes qualifiées aux opérations liées aux batteries
peuvent remplacer ces dernières et superviser les opérations en prenant les mesures de sécurité
requises. Les personnes non autorisées doivent être tenues à l’écart des batteries.
Avertissement - risque de choc électrique. Le circuit de la batterie n’est pas isolé de la tension
d’entrée. Des tensions dangereuses peuvent survenir entre les bornes de la batterie et le sol. Avant
de toucher, veuillez vérifier que la tension est nulle !
Ne remplacez les fusibles que par des fusibles de type et d’intensité identiques afin d’éviter les
risques d’incendie.
Ne démontez pas l’onduleur.
1-8. À propos des batteries :
5
Il est recommandé de faire remplacer la batterie par un technicien qualifié.
Ne pas ouvrir ou endommager la batterie ! L’électrolyte, principalement de l’acide sulfurique, peut
être toxique et néfaste pour la peau et les yeux. Si l’électrolyte entre en contact avec votre corps,
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
lavez soigneusement les parties touchées avec de l’eau et nettoyez les vêtements contaminés.
Ne jetez pas la batterie au feu. Elle peut exploser. Elle doit être mise recyclée séparément à la fin de
sa durée de vie utile. Référez-vous aux réglementations et à la législation locales.
l’onduleur contient des batteries de grande capacité. Pour éviter tout risque de choc électrique, ne
l’ouvrez pas. Si une batterie nécessite d’être entretenue ou remplacée, veuillez contacter votre
distributeur.
L’entretien doit être effectué ou supervisé par un personnel compétent avec les précautions
nécessaires. Gardez le personnel non autorisé à distance des batteries.
Une batterie peut entraîner un risque de choc électrique et de provoquer des courts-circuits. Les
précautions suivantes doivent être prises par le technicien qualifié :
Retirez montres, bagues ou autres objets métalliques de vos mains.
Utilisez des outils munis de poignées isolées.
Déconnectez la source de rechargement avant de connecter ou de déconnecter les bornes
de la batterie.
Lors du remplacement des batteries, utilisez le même type et le même nombre de batteries
acide-plomb étanches.
1-9. SERVICE APRES-VENTE
IMPORTANT !
Lors d’un l’appel au Service Après-Vente, nous vous recommandons de transmettre les informations
suivantes qui vous seront dans tous les cas demandées : le modèle de l’onduleur, le numéro de série,
la date d’achat et le type de matériel alimenté par l’onduleur, ainsi qu’une description précise du
problème comprenant : état des voyants, état de l’alarme, conditions d’installations et
d’environnement.
Ces renseignements sont notés sur la facture ou inscrits sur la plaque signalétique à l’arrière de
l’appareil.
Vous pouvez également les reporter dans le cadre ci-dessous.
Modèle
Numéro de série
Date d’achat
E4 Evolution II + TT…
! Veuillez conserver l’emballage d’origine, il sera indispensable pour un éventuel retour de votre onduleur en
nos locaux.
6
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
1-10. Conformité CE :
Ce logo signifie que le produit répond aux normes relatives à la CEM et à la DBT (en ce qui
concerne la réglementation relative aux directives basses tensions et à la compatibilité
électromagnétique). Il s’agit ici d’un onduleur de catégorie C3.
Dans un environnement résidentiel, ce produit peut causer des interférences radio, auquel
cas l’utilisateur peut être amené à prendre des mesures supplémentaires.
Important
Un onduleur appartient à la catégorie des équipements électriques et électroniques. À la
fin de sa durée de vie utile, il doit être recyclé séparément dans un lieu adapté.
Ce symbole est également apposé sur les batteries fournies avec l’appareil, car elles
aussi doivent être éliminées dans un lieu adapté à la fin de leur durée de vie utile.
Contactez votre centre local de recyclage ou de traitement des déchets pour plus d’informations sur la mise
au rebut des batteries usagées.
7
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
2. Installation et fonctionnement
REMARQUE : Avant l’installation, veuillez examiner l’appareil. Veillez à ce que rien à l’intérieur de
l’emballage ne soit endommagé. Veuillez conserver l’emballage d’origine dans un endroit sûr pour une
utilisation future.
En cas de détérioration ou de pièce manquante, n’allumez pas l’appareil et informez immédiatement le
transporteur et le revendeur. Il est recommandé de conserver chaque équipement et ensemble de batteries
dans son emballage d’origine parce qu’ils ont été conçus pour assurer une protection maximale durant le
transport et l’entreposage.
REMARQUE : Il existe différents types d’onduleurs E4 Evolution II + TT : les modèles standard et les
modèles longues autonomies (versions S), tous deux disponibles en HV et LV. Veuillez consulter le tableau
suivant.
REMARQUE : La fonction Double Alimentation (dual input) est en option pour les modèles E4 Evolution II +
10/15/20k TT HV et E4 Evolution II + 7.5/10k TT LV et est inclue en standard pour les modèles E4 Evolution
II + 30/40/60/80 TT HV et E4 Evolution II + 15/20/30/40 TT LV.
Puissances
Modèle
Version
10 kVA
E4 Evolution II + 10k TT HV
E4 Evolution II + 10k TT S HV
15 kVA
E4 Evolution II + 15k TT HV
E4 Evolution II + 15k TT S HV
20 kVA
E4 Evolution II + 20k TT HV
30 kVA
E4 Evolution II + 30k TT HV
40 kVA
E4 Evolution II + 40k TT HV
60 kVA
-
Modèle
standard
HV
Modèle
E4 Evolution II + 20k TT S HV
E4 Evolution II + 30k TT S HV
E4 Evolution II + 40k TT S HV
Version
Modèle
longue
autonomie
HV
E4 Evolution II + 60k TT S HV
80 kVA
E4 Evolution II + 80k TT S HV
10 kVA
E4 Evolution II + 10k TT LV
15 kVA
E4 Evolution II + 15k TT LV
20 kVA
E4 Evolution II + 20k TT LV
30 kVA
-
40 kVA
E4 Evolution II + 10k TT S LV
Modèle
standard
LV
E4 Evolution II + 15k TT S LV
E4 Evolution II + 20k TT S LV
E4 Evolution II + 30k TT S LV
Modèle
longue
autonomie
LV
E4 Evolution II + 40k TT S LV
HV implique une tension nominale triphasée de 380/400/415 VAC
LV implique une tension nominale triphasée de 208/220 VAC
2-1. Déballage et inspection
Déballez le colis et vérifiez le contenu du paquet. L’emballage contient :
Un onduleur
Un manuel de l’utilisateur
Un câble RS-232
Un câble USB
Un câble parallèle (en option pour les modèles 10/15/20k VA HV et 10kVA LV)
Un câble à courant de partage (en option pour les modèles 10/15/20k VA HV et 7.5/10kVA LV)
8
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
2-2. Vue du panneau arrière
Modèles HV
Face arrière
Face arrière
E4 Evolution II + 10/15/20k TT (S) HV (standard)
E4 Evolution II + 10/15/20k TT (S) HV
(option double alimentation)
9
Bornier d'entrée / sortie
Bornier d'entrée / sortie
E4 Evolution II + 10/15/20k TT (S) HV
E4 Evolution II + 10/15/20k TT HV (S)
(standard)
(option double alimentation)
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Face arrière
Face arrière
E4 Evolution II + 30k TT (S) HV E4 Evolution II + 40k TT (S) HV
Bornier d'entrée / sortie
E4 Evolution II + 30/40k TT (S) HV
10
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Face avant porte ouverte
Face avant porte ouverte
E4 Evolution II + 60k TT S HV
E4 Evolution II + 80k TT S HV
13
11
Bornier d'entrée / sortie
E4 Evolution II + 60/80k TT (S) HV
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Modèles LV
Face arrière
Face arrière
E4 Evolution II + 10k TT LV (S) (standard)
E4 Evolution II + 10k TT (S) LV
(option double alimentation)
Bornier d'entrée / sortie
Bornier d'entrée / sortie
E4 Evolution II + 10k TT (S) LV (standard)
E4 Evolution II + 10k TT (S) LV
12
(option double alimentation)
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Face arrière
Face arrière
E4 Evolution II + 15k TT (S) LV
E4 Evolution II + 20k TT (S) LV
Bornier d’entrée / sortie
E4 Evolution II + 15/20k TT (S) LV
13
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Face avant porte ouverte
Face avant porte ouverte
E4 Evolution II + 30k TT S LV
E4 Evolution II + 40k TT S LV
Bornier d'entrée / sortie
E4 Evolution II + 30/40k TT (S) LV
14
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Légendes :
1. Port de communication RS-232
2. Port de communication USB
3. Connecteur de la fonction d’arrêt d’urgence (connecteur EPO)
4. Port de partage de courant (pour le mode parallèle)
5. Port parallèle
6. Slot intelligent SNMP
7. Connecteur de batterie externe
8. Disjoncteur ou commutateur d’entrée
9. Commutateur de bypass maintenance
10. Bornier entrée / sortie avec couvercle de protection
11. Borne d'entrée
12. Borne de sortie
13. Borne de mise à la terre d'entrée
14. Borne de mise à la terre de sortie
15. Disjoncteur ou commutateur de circuit d’entrée de bypass
16. Borne d'entrée de bypass
17. Borne de terre
18. Commutateur de sortie
15
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
2-3. Installation de l’onduleur seul
L’installation et le câblage doivent être effectués conformément aux lois et réglementations en vigueur et
relatifs aux installations électriques. Les instructions suivantes doivent être respectées par des
professionnels ayants leurs habilitations électriques.
1)
Assurez-vous que le câble secteur et les disjoncteurs installés sont compatibles avec la tension
nominale de l’onduleur pour éviter tout risque de choc électrique ou d’incendie.
REMARQUE : N’utilisez pas la prise murale comme source d’alimentation de l’onduleur, car son courant
nominal est inférieur au courant d’entrée maximal de l’onduleur. Autrement, la prise peut brûler et être
détruite.
2)
Ouvrir le disjoncteur d’alimentation avant de procéder à l’installation.
3)
Mettez hors tension tous les dispositifs connectés avant de les brancher sur l’onduleur.
4)
Préparer les câbles en suivant les indications du tableau suivant (utilisez des câbles flexibles) :
Modèles HV
Spécifications de câblage (mm²/AWG)
Entrée (Ph)
Sortie (Ph)
Neutre
E4 Evolution II + 10k TT HV
6 / 14
6 / 14
6 / 14
E4 Evolution II + 15k TT HV
6 / 12
6 / 12
6 / 12
E4 Evolution II + 20k TT HV
10 / 10
10 / 10
10 / 10
E4 Evolution II + 30k TT HV
16 / 8
16 / 8
16 / 8
E4 Evolution II + 40k TT HV
16 / 6
16 / 6
16 / 6
E4 Evolution II + 60k TT S HV
25 / 4
25 / 4
25 / 4
E4 Evolution II + 80k TT S HV
35 / 2
35 / 2
35 / 2
Modèles LV
Spécifications de câblage (mm²/AWG)
Entrée (Ph)
Sortie (Ph)
Neutre
E4 Evolution II + 10k TT LV
10 / 10
10 / 10
10 / 10
E4 Evolution II + 15k TT LV
16 / 8
16 / 8
16 / 8
E4 Evolution II + 20k TT LV
16 / 6
16 / 6
16 / 6
E4 Evolution II + 30k TT S LV
25 / 4
25 / 4
25 / 4
E4 Evolution II + 40k TT S LV
35 / 2
35 / 2
35 / 2
REMARQUE 1 : Le câble du modèle E4 Evolution II + 10k TT (S) HV doit être capable de supporter
un courant d’intensité supérieure à 20 A. Il est recommandé d’utiliser un câble de section
6mm²/14 AWG ou une section plus importante.
REMARQUE 2 : Le câble des modèles E4 Evolution II + 15k TT (S) HV doit être capable de supporter
un courant d’intensité supérieure à 30 A. Il est recommandé d’utiliser un câble de section
6mm²/12 AWG ou une section plus importante.
REMARQUE 3 : Le câble des modèles E4 Evolution II + 20k TT (S) HV et E4 Evolution II + 10k TT
(S) LV doit être capable de supporter un courant d’intensité supérieure à 40 A. Il est recommandé
d’utiliser un câble de 10mm²/10 AWG ou une section plus importante.
REMARQUE 3 : Le câble des modèles E4 Evolution II + 30k TT (S) HV et E4 Evolution II + 15k TT
(S) LV doit être capable de supporter un courant d’intensité supérieure à 60 A. Il est recommandé
16
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
d’utiliser un câble de 16mm²/8 AWG ou ou une section plus importante.
REMARQUE 4 : Le câble des modèles E4 Evolution II 40k TT (S) HV et E4 Evolution II + 20k TT (S)
LV doit être capable de supporter un courant d’intensité supérieure à 80 A. Il est recommandé
d’utiliser un câble de 16mm²/6 AWG ou ou une section plus importante.
REMARQUE 5 : Le câble des modèles E4 Evolution II + 60k TT S HV et E4 Evolution II + 30k TT S
LV doit être capable de supporter un courant d’intensité supérieure à 120 A. Il est recommandé
d’utiliser un câble de 25mm²/4 AWG pour le neutre pour plus de sécurité et d’efficacité.
REMARQUE 6 : Le câble des modèles E4 Evolution II + 80k TT (S) HV et E4 Evolution II + 40k TT
(S) LV doit être capable de supporter un courant d’intensité supérieure à 160 A. Il est recommandé
d’utiliser un câble de 35mm²/2 AWG ou un câble plus épais pour la phase et un câble de 1/0 AWG ou
un ou une section plus importante.
REMARQUE 7 : Utiliser des câbles souples et à raccorder avec des cosses tubulaires à sertir.
5)
Retirez le couvercle du bornier situé sur le panneau arrière de l’onduleur. Connectez ensuite les câbles
selon les schémas de bornier suivants : (Connectez le câble de mise à la terre en premier lors du
câblage. Déconnectez le câble de mise à la terre en dernier lors du débranchement des câbles !)
Sortie
Entrée
Schéma de bornier du modèle E4 Evolution II + 10/15/20k TT (S) HV (standard)
E4 Evolution II + 10k (S) LV (standard)
17
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Sortie
Entrée
Entrée de le bypass
Schéma de bornier du modèle E4 Evolution II + 10/15/20k TT (S) HV (double alimentation)
E4 Evolution II + 10k TT (S) LV (double alimentation)
Terre
Sortie
Entrée
Entrée de le bypass
Schéma de bornier du modèle E4 Evolution II + 30/40k TT (S) HV
E4 Evolution II + 15/20k TT (S) LV
18
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Entrée
Sortie
Entrée bypass
Schéma de bornier du modèle E4 Evolution II + 60/80k TT S HV
E4 Evolution II + 30/40k TT S LV
VERS BAT+ l’onduleur
TO UPS BAT+
PBAT
PBAT
TO UPS BAT N
VERS NBAT l’onduleur
NBAT
NBAT
VERS BAT- l’onduleur
TO
UPS BAT-
Schéma de câblage de la batterie
19
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
REMARQUE 1 : Assurez-vous que les câbles sont fermement serrés aux bornes.
REMARQUE 2 : Veuillez installer un disjoncteur de sortie entre la sortie et la charge. Le disjoncteur doit
être approprié et, si nécessaire, doté de la fonction de protection contre le courant de fuite (différentiel).
6)
Remettez en place le couvercle de protection des bornes de raccordement.
Avertissement : (Pour le modèle standard uniquement)
Assurez-vous que l’onduleur n’est pas en marche avant de l’installer. Il doit être éteint pendant le
câblage.
N’essayez pas de changer le modèle standard en modèle longue autonomie. Tout particulièrement,
n’essayez pas de relier la batterie interne standard à la batterie externe. Le type de batterie, la tension
et le nombre peuvent être différents. Si vous les reliez ensemble, cela peut constituer un risque de choc
électrique ou d’incendie !
Avertissement : (Pour les modèles de longue autonomie uniquement)
Assurez-vous qu’un disjoncteur CC ou tout autre dispositif de protection est installé entre l’onduleur et
le module d’autonomie. Sinon, veuillez l’installer soigneusement. Coupez le disjoncteur de la batterie
avant l’installation.
REMARQUE : Réglez le disjoncteur du module d’autonomie en position « ARRÊT », puis installez ce
dernier.
Prêtez une grande attention à la tension nominale de la batterie indiquée sur le panneau arrière. Si
vous souhaitez modifier le nombre de module d’autonomie, veuillez modifier par la même occasion la
configuration. Le branchement avec une tension de batterie inappropriée peut causer des dommages
permanents à l’onduleur. Assurez-vous que la tension du bloc-batterie est correcte.
Prêtez une attention particulière à l’indication de polarité sur le bornier de la batterie externe et
assurez-vous que la batterie est bien connectée suivant cette polarité. Un mauvais raccordement peut
causer des dommages permanents à l’onduleur.
2-4. Installation des onduleurs dans un système parallèle
Si l’onduleur est prévu que pour un raccordement seul, vous pouvez ignorer cette section et passer à la
suivante section.
1)
Installez et câblez les onduleurs conformément aux indications de la section 2-3.
2)
Branchez le câble de sortie de chaque l’onduleur à un disjoncteur de sortie.
3)
Connectez tous les disjoncteurs de sortie à un disjoncteur de sortie principal. Ce disjoncteur de sortie
principal sera ensuite directement connecté aux charges.
4)
Il est possible d’utiliser des modules d’autonomie communs ou des modules d’autonomie
indépendants pour chaque onduleur.
5)
Référez-vous au schéma de câblage ci-après :
20
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Onduleur 2
Onduleur 1
Sortie
Entrée
Schéma de câblage du système parallèle pour le modèle E4 Evolution II + 10/15/20k TT (S)
HV (standard)
E4 Evolution II + 10k TT (S) LV (standard)
Onduleur 2
Onduleur 1
Sortie
Entrée
Entrée de le bypass
Schéma de câblage du système parallèle pour le modèle E4 Evolution II + 15/20k TT (S) HV
(double alimentation en option)
E4 Evolution II + 10k TT (S) LV (double alimentation en option)
Onduleur 1
Onduleur 2
Terre
Terre
Sortie
Entrée
Entrée de le bypass
Schéma de câblage du système parallèle pour le modèle E4 Evolution II + 30/40k TT (S) HV
E4 Evolution II + 15/20k TT (S) LV
21
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Onduleur 1
Onduleur 2
Entrée
Onduleur 2
Sortie
Onduleur 1
Entrée de le bypass
Schéma de câblage du système parallèle pour le modèle E4 Evolution II + 60/80k TT S HV
E4 Evolution II + 30/40k TT S LV
22
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
2-5. Installation du logiciel
Pour une protection optimale du système informatique, installez le logiciel de surveillance de l’onduleur
pour configurer entièrement l’arrêt de l’onduleur.
Ports de communication :
Port USB
Port RS-232
Logement intelligent
Pour la mise en marche ou l’arrêt sans surveillance de l’onduleur et la surveillance du mode de
fonctionnement, connectez une extrémité du câble de communication au port RS-232/USB et l’autre au
port de communication de votre PC. À l’aide du logiciel de surveillance installé, vous pouvez programmer
l’arrêt ou le démarrage de l’onduleur et surveiller les états de ce dernier sur votre PC.
L’onduleur est équipé d’un slot intelligent, prévu pour l’installation des cartes SNMP ou AS400. Lorsqu’une
carte SNMP ou AS400 est installée dans l’onduleur, elle fournit des options de communication et de
surveillance avancées.
Remarque : Le port USB et le port RS-232 ne peuvent pas fonctionner simultanément.
23
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
3. Opérations
Ecran LCD
Indicateurs
Boutons
Schéma 11 : Indicateurs et écran LCD
3-1. Fonctionnement du bouton
Bouton
Fonction
Bouton MARCHE/Entrée
(ON/ENTER)
Mise en marche de l’onduleur : Maintenez ce bouton enfoncé (plus d’une
seconde) pour mettre l’onduleur en marche.
Touche Entrée : Appuyez sur ce bouton pour confirmer la sélection dans
le menu de réglage.
Bouton ARRÊT/ÉCHAP
(OFF/ESC)
Arrêt de l’onduleur : Maintenez ce bouton enfoncé (plus de 2 s) pour
éteindre l’onduleur.
Touche ÉCHAP : Appuyez sur ce bouton pour retourner au menu
précédent dans le menu de réglage.
Bouton Test/Haut
(TEST/UP)
Test de la batterie : Maintenez ce bouton enfoncé plus d’une seconde
pour tester la batterie en mode AC ou CVCF.
Touche HAUT : Appuyez sur ce bouton pour afficher la sélection suivante
dans le menu de réglage.
Bouton Silence/Bas
(MUTE/DOWN)
Coupe l’alarme : Maintenez ce bouton enfoncé (plus d’une seconde) pour
couper l’avertisseur. Veuillez-vous référer à la section 3-4-9 pour plus
d’informations.
Touche Bas : Appuyez sur ce bouton pour afficher la sélection précédente
dans le menu de réglage.
Touches Test/Haut +
Silence/Bas (TEST/UP &
MUTE/DOWN)
Appuyez simultanément sur ces deux boutons pendant plus d’une
seconde pour accéder au menu de réglage ou le quitter.
* Le mode CA indique le mode normal et le mode CVCF celui de convertisseur de fréquence.
24
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
3-2. Indicateurs LED et écran LCD
Voyants lumineux :
Il y a 4 voyants sur le panneau avant pour indiquer l’état de fonctionnement de l’onduleur :
Voyant
Bypass
Line
Battery
Fault
Mode
Démarrage de
●
l’onduleur
●
○
Mode bypass
○
Mode normal
●
Mode batterie
○
Mode CVCF
●
Test de batterie
●
Mode ÉCO
●
Défaut
○
Remarque : ● signifie que le voyant est allumé et ○ qu’il est éteint.
Pas de mode de sortie
Informations
relatives à la tension
de la batterie et à la
tension d’entrée
○
●
○
○
○
●
●
○
Informations relatives à la durée
d’autonomie
●
●
○
○
○
●
○
●
○
○
○
○
○
○
○
○
○
●
Informations relatives au défaut
Fonctionnement silencieux
Informations relatives à
la batterie
Informations
relatives à tension de
la batterie et à la
tension de sortie
Informations
relatives à la charge
Informations relatives au mode de fonctionnement
Schéma 12 : Ecran LCD
25
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Affichage
Fonction
Informations relatives à la durée d’autonomie
Indique la durée d’autonomie lorsque l’onduleur est en mode batterie
H : heures, M : minutes, S : secondes
Informations relatives à la panne
Indique qu’un avertissement a été émis ou qu’une panne s’est produite.
Indique les codes de panne (mentionnés en détail dans la section 3-9).
Fonctionnement silencieux
Indique que l’alarme de l’onduleur est désactivée.
Informations relatives à la tension de la batterie et à la batterie de sortie
Indique la tension de sortie, la fréquence ou la tension de la batterie.
VAC : tension de sortie ; VDC : tension de la batterie ; Hz : fréquence
Informations relatives à la charge
Indique le niveau de charge : 0-25 %, 26-50 %, 51-75 % et 76-100 %.
Indique une surcharge.
Indique que la charge ou la sortie est court-circuitée.
Informations relatives au mode de fonctionnement
Indique que l’onduleur est branché sur le secteur.
Indique que la batterie fonctionne.
Indique que le circuit de bypass fonctionne.
Indique que le mode ECO est activé.
Indique que le circuit onduleur fonctionne.
Indique que la sortie fonctionne.
Informations relatives à la batterie
Indique la capacité de la batterie : 0-25 %, 26-50 %, 51-75 % et 76-100 %.
Indique une défaillance de la batterie.
Indique un niveau de batterie faible.
Informations relatives à la tension d’entrée et à la tension de la batterie
Indique la tension ou la fréquence d’entrée, ou la tension de la batterie.
VAC : tension d’entrée, VDC : tension de la batterie, Hz : fréquence d’entrée
26
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
3-3. Alarme sonore
Description
État de l’onduleur
Mode bypass
Mode batterie
Mode défaut
Avertissement
Surcharge
Autres
Défaut
Tous défauts
État de l’avertisseur
Arrêt bip possible
Un bip toutes les 2 minutes
Un bip toutes les 4 secondes
Bips continus
Oui
Deux bips par seconde
Un bip toutes les secondes
Non
Bips continus
Oui
3-4. Fonctionnement de l’onduleur seul
1.
Mise en marche de l’onduleur avec l’alimentation secteur (en mode normal)
Une fois l’alimentation électrique correctement raccordée, mettre le disjoncteur du bloc-batterie en position
« MARCHE » (ON) (phase disponible pour le modèle longue autonomie uniquement). Actionner ensuite le
disjoncteur d’entrée sur la position « MARCHE » (ON), mettre le disjoncteur de bypass (15) en position
« MARCHE » (ON) pour tous les modèles à double alimentation. Le ventilateur tourne maintenant et
l’onduleur alimente les charges via le bypass. L’onduleur fonctionne en mode Bypass, mettre le disjoncteur
de sortie (18) en position « MARCHE » (ON).
REMARQUE 1 : Lorsque l’onduleur est en mode Bypass, la tension de sortie sera directement
fournie par le secteur après la fermeture du disjoncteur d’entrée. En mode Bypass, la charge n’est
pas protégée par l’onduleur. Pour protéger vos précieux appareils, vous devez mettre l’onduleur
en marche. Référez-vous à l’étape suivante.
Maintenez enfoncé pendant au moins 0,5 s le bouton « MARCHE » (ON) pour mettre l’onduleur en marche.
L’avertisseur émettra alors un bip.
Quelques secondes plus tard, l’onduleur passera en mode secteur (voyant LINE allumé). Si l’alimentation
secteur est anormale, l’onduleur fonctionnera sans interruption en mode Batterie.
REMARQUE 2 : Lorsque la batterie de l’onduleur est faible, il s’éteint automatiquement en mode
Batterie. Une fois l’alimentation secteur rétablie, l’onduleur redémarre automatiquement en mode
secteur.
2. Mise en marche de l’onduleur sans l’alimentation secteur (en mode Batterie)
1)
Assurez-vous que les batteries soient correctement connectées aux bornes « +, terre, - » et dans
cet ordre, et que le disjoncteur du bloc-batterie est en position « MARCHE » (pour les modèles
longues autonomies uniquement).
Appuyez brièvement sur le bouton « MARCHE » (ON) pour configurer l’alimentation de l’onduleur qui
passera alors en mode TEST. Une fois l’initialisation terminée, l’onduleur entrera en mode « Pas de
sortie ». Maintenez enfoncé pendant au moins 0,5 s le bouton « ON » pour mettre l’onduleur en marche.
L’avertisseur émettra alors un bip.
Quelques secondes plus tard, l’onduleur passera en mode Batterie (voyant BATTERY allumé).
3. Connection de la charge de l’onduleur
Une fois l’onduleur en marche, vous pouvez y connecter la charge sur les sorties.
1)
Allumez l’onduleur en premier, puis allumez les appareils les uns après les autres. Le niveau de
charge total sera affiché sur l’écran LCD.
S’il est nécessaire de connecter des charges inductives, par exemple une imprimante, le courant de
démarrage devra être soigneusement calculé pour vérifier s’il est conforme à la capacité de surcharge de
27
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
l’onduleur. Pour toute charge supérieure à 150 % de la capacité nominale, la durée d’exécution sera
inférieure à 60 ms.
Si l’onduleur est en surcharge, l’avertisseur émettra deux bips toutes les secondes.
Si l’onduleur est en surcharge, veuillez retirer immédiatement certaines charges. Il est recommandé que
les charges totales connectées à l’onduleur soient inférieures à 70 % de sa puissance nominale pour éviter
toute surcharge du système pour des raisons de sécurité.
Si la durée de la surcharge dépasse la durée acceptable en mode secteur indiquée dans les
caractéristiques, l’onduleur bascule automatiquement en mode Bypass. Une fois la surcharge éliminée, il
bascule de nouveau en mode secteur. Si la durée de la surcharge dépasse la durée acceptable en mode
Batterie indiquée dans les caractéristiques, l’onduleur affiche le statut d’erreur. Si le mode Bypass est
activé, l’onduleur alimentera la charge via la bypass. Si la fonction de bypass est désactivée ou si
l’alimentation électrique n’est pas dans la plage de bypass acceptable, la sortie sera directement coupée.
4. Recharger des batteries
1)
Une fois l’onduleur connecté à l’alimentation secteur, le chargeur batterie recharge
automatiquement les batteries, sauf en mode Batterie, pendant l’auto-test de la batterie, en cas de
surcharge ou lorsque la tension de la batterie est élevée.
Il est recommandé de charger les batteries pendant au moins 10 heures avant de les utiliser. Sinon, la
durée d’autonomie peut être plus courte que prévue.
Assurez-vous que le réglage du nombre de batteries paramétré (veuillez-vous référer à la section 3-4-14
pour le réglage détaillé) est conforme à la connexion réelle.
5. Fonctionnement en mode Batterie
1)
Lorsque l’onduleur est en mode Batterie, l’avertisseur émet un bip en fonction des différentes
capacités de la batterie. Si la batterie a une capacité supérieure à 25 %, l’avertisseur émet un bip
toutes les 4 secondes ; si la tension de la batterie descend jusqu’au niveau d’alarme, l’avertisseur
émet des bips rapides (un bip par seconde) pour rappeler aux utilisateurs que la batterie est faible
et que l’onduleur est sur le point de s’éteindre automatiquement. Les utilisateurs peuvent retirer
certaines charges non essentielles pour désactiver l’alarme d’arrêt et prolonger la durée
d’autonomie. Si cela n’est pas possible, vous devez éteindre toutes les charges le plus tôt
possible afin de protéger les appareils contre les ruptures de charge ou les pertes de données.
En mode Batterie, les utilisateurs peuvent appuyer sur le bouton Silence pour couper le son de
l’avertisseur.
La durée d’autonomie du modèle longue autonomie dépend de la capacité des batteries externes.
La durée d’autonomie peut varier selon les températures ambiantes et les types de charges.
Lors du réglage de la durée d’autonomie sur 16,5 heures (valeur par défaut sur l’écran LCD : 999 min), au
bout de 16,5 heures de décharge, l’onduleur s’arrête automatiquement pour protéger la batterie. Cette
protection contre la décharge de la batterie peut être activée ou désactivée à l’aide du panneau de
commande LCD. (Référez-vous à la section 3-7 relative au réglage de l’écran) (cette fonction est
désactivée par défaut).
6. Test de batterie
1)
Si vous êtes appelé à vérifier l’état de la batterie alors que l’onduleur est en mode AC /CVCF, vous
pouvez appuyer sur le bouton « Test » pour amener l’onduleur à procéder à l’auto-test de la
batterie.
Les utilisateurs peuvent également configurer l’autotest de la batterie grâce au logiciel de surveillance.
28
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
7.
Arrêt de l’onduleur avec l’alimentation secteur en mode normal
1)
Éteignez l’onduleur en appuyant sur le bouton « ARRÊT » (OFF) pendant au moins 0,5 s.
L’avertisseur émettra un bip et l’onduleur basculera en mode Bypass.
REMARQUE : Après avoir éteint l’onduleur, sachez qu’il fonctionne en mode Bypass et qu’il y a
un risque de perte d’alimentation pour les appareils connectés.
En mode Bypass, la tension de sortie de l’onduleur est toujours présente. Pour couper la sortie, ouvrir le
disjoncteur d’entrée. Quelques secondes plus tard, plus rien ne s’affiche sur le panneau d’affichage et
l’onduleur est totalement éteint.
8. Arrêt de l’onduleur sans l’alimentation secteur en mode Batterie
1)
Éteignez l’onduleur en appuyant sur le bouton « ARRÊT » (OFF) pendant au moins 0,5 s.
L’avertisseur émettra un bip.
L’onduleur coupe ensuite l’alimentation à la sortie et plus rien ne s’affiche sur le panneau d’affichage.
9. Couper le son de l’avertisseur
1)
Pour couper le son de l’avertisseur, appuyez sur la touche « Silence » (MUTE) pendant au moins
0,5 seconde. Si vous appuyez à nouveau sur ce bouton après avoir coupé le son de l’avertisseur,
vous entendrez à nouveau les bips.
Certaines alarmes d’avertissement ne peuvent pas être coupées tant que l’erreur n’est pas corrigée.
10. Fonctionnement en mode avertissement
1)
Lorsque le voyant d’indication de panne clignote et que l’avertisseur émet un bip toutes les
secondes, cela indique un dysfonctionnement de l’onduleur. Les utilisateurs peuvent voir le code
d’erreur sur l’écran LCD (voir section 3-10). Veuillez consulter le tableau de dépannage du
chapitre 4 pour plus d’informations.
Certaines alarmes d’avertissement ne peuvent pas être coupées tant que l’erreur n’est pas corrigée.
Veuillez-vous référer à la section 3-3 pour plus d’informations.
11. Fonctionnement en mode Défaut
1) Lorsque l’indicateur « FAULT » s’allume et que l’alarme sonne en continue, cela signifie que
l’onduleur rencontre un défaut critique. L’utilisateur peut obtenir le code de défaut en consultant
l’écran LCD (voir section 3-9). Veuillez vous référer à la section 4 pour plus d’informations.
2)
Lorsqu’un défaut survient, veuillez vérifier les charges, le câblage, la ventilation, l’alimentation
secteur, la batterie, etc. N’essayez pas de rallumer l’onduleur avant d’avoir résolu le problème. Si le
problème persiste, contactez immédiatement le distributeur ou le réparateur.
3)
En cas d’urgence, débranchez immédiatement l’alimentation secteur, la batterie externe et la sortie
afin d’éviter tout dommage sur l’onduleur ou l’équipement.
12. Fonctionnement en mode Maintenance
Ce mode de fonctionnement doit exclusivement être mis en œuvre par le personnel de maintenance ou un
technicien qualifié.
Si une opération de réparation ou d’entretien doit être effectuée sur l’onduleur et que la charge ne peut pas
être coupée, l’onduleur doit être basculé en mode Maintenance.
1)
Tout d’abord, éteignez l’onduleur (bouton OFF).
2)
Ensuite, retirez le capot du commutateur de bypass d’entretien (9) installé sur le panneau arrière.
3)
Tournez le commutateur de maintenance en position « BPS ». Ensuite, coupez le disjoncteur
d’alimentation et bypass statique si présent (15)
4) Débranchez la batterie, s’il s’agit d’une batterie externe
29
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
5) L’onduleur s’éteint alors complètement et la tension d’entrée va directement vers la borne de sortie.
6) Pour redémarrer, suivez la procédure dédiée.
13. Réglage du courant de charge
1)
Cette opération est réservée exclusivement aux techniciens professionnels ou qualifiés.
2)
Connectez le câble de communication sur l’onduleur et l’ordinateur. Assurez-vous d’avoir d’abord
installé l’outil de communication dédié. Pour plus d’informations sur cet outil logiciel, veuillez
contactez votre revendeur. Utilisez le logiciel pour paramétrer le courant de charge de manière
appropriée.
Une fois les paramètres mis à jour avec succès, le courant de charge mis à jour sera immédiatement
appliqué.
Afin d’appliquer le même réglage de courant de charge la prochaine fois, éteignez l’onduleur alors
que la batterie est connectée pour enregistrer la modification.
14. Réglage du chargeur et nombre de batteries
1)
Cette opération est réservée exclusivement aux techniciens professionnels ou qualifiés.
Éteignez l’onduleur. Si la charge ne peut pas être coupée, retirez le capot de l’interrupteur de bypass
d’entretien installé sur le panneau arrière et tournez d’abord le commutateur de maintenance en position
« BPS ».
Coupez le disjoncteur d’entrée de ligne pour que l’onduleur entre en mode « Pas de sortie ».
Connectez le câble de communication de l’onduleur à l’ordinateur. Lancez le logiciel pour configurer avec
soin le nombre de batteries.
Une fois les paramètres mis à jour avec succès, arrêtez l’onduleur alors que les batteries sont connectées
pour enregistrer la modification. Modifiez ensuite le nombre de chargeurs branchés.
Mettre le disjoncteur d’entrée et le disjoncteur de bypass externe en position de marche. l’onduleur entrera
alors en mode Bypass. Si l’onduleur est en mode de bypass d’entretien, réglez le commutateur d’entretien
en position « onduleur», puis mettez l’onduleur en marche.
REMARQUE : Le nombre de batteries défini doit être identique à celui défini dans l’onduleur. Si le nombre
défini est différent du nombre réel, le courant de charge ne peut pas répondre aux spécifications.
30
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
3-5. Fonctionnement en parallèle
1.
Démarrage initial du système parallèle
Tout d’abord, assurez-vous que tous les onduleurs ont la même configuration.
1)
Allumez respectivement chaque onduleur en mode AC [référez-vous à la section 3-4(1)]. Mesurez
ensuite la tension de sortie d’onduleur de la phase de chaque onduleur à l’aide d’un multimètre.
Veuillez calibrer la tension de sortie de l’onduleur en configurant le réglage de la tension de
l’onduleur (référez-vous aux Programmes 15, 16 et 17, section 3 à 7) dans les paramètres de
l’écran LCD jusqu’à ce que la différence de tension de sortie de chaque onduleur soit inférieure
à 1 V. Si la différence de tension est inférieure à 1 V, le fonctionnement en parallèle peut être
effectué sans aucun problème.
2)
Calibrez la mesure de la tension de sortie en configurant le calibrage de la tension de sortie
(référez-vous aux Programme 18, 19 et 20, sections 3 à 7) sur l’écran LCD afin d’être sûr que la
différence entre la tension de sortie réelle et la valeur mesurée par l’onduleur est inférieure à 1 V.
3)
Éteignez chaque onduleur [référez-vous à la section 3-4(7)]. Ensuite, respectez la procédure de
câblage indiquée à la section 2-4.
4)
Retirez le capot du port du câble de partage de courant en parallèle de l’onduleur, connectez
chaque onduleur un à un avec le câble parallèle et le câble de partage de courant, puis remettez
le couvercle en place.
5)
Mettez le système parallèle en mode CA :
a. Fermer le disjoncteur d’entrée d’alimentation de chaque onduleur. En cas d’utilisation d’une
unité à entrées doubles, veuillez fermer également le disjoncteur d’entrée de bypass. Une fois
tous les onduleurs en mode de bypass, mesurez la tension de sortie entre deux onduleurs
pour la même phase pour vous assurer que la séquence de phase est correcte. Si ces deux
différences de tension sont proches de zéro, cela signifie que toutes les connexions sont
correctes. Sinon, veuillez vérifier si les câblages sont correctement effectués.
b. Fermer le disjoncteur de sortie de chaque onduleur.
c. Allumez ensuite chaque onduleur (bouton ON). Au bout d’un moment, les onduleurs entreront
de manière synchrone en mode AC, achevant ainsi le système parallèle.
6)
Mettez le système parallèle en mode Batterie :
a. Fermer le disjoncteur de batterie (disponible uniquement si batteries externes) et le
disjoncteur externe de sortie de chaque onduleur.
b. Allumez n’importe quel onduleur. Quelques secondes plus tard, l’onduleur passera en mode
Batterie.
c. Allumez ensuite chaque onduleur. Au bout d’un moment, les onduleurs entreront de manière
synchrone en mode AC, achevant ainsi le système parallèle.
d. Suivez la procédure indiquée au point c si vous disposez d’une troisième ONDULEUR. Le
système parallèle sera alors complet.
Pour plus d’informations, veuillez contacter la hotline pour obtenir des instructions de
fonctionnement en parallèle.
7) Ajouter une nouvelle unité au système parallèle
a. Il est impossible d’ajouter une nouvelle unité au système parallèle lorsque l’ensemble du
système est en marche. Vous devez couper la charge et arrêter le système.
b. Assurez-vous que tous les onduleurs sont du modèle parallèle, et respectez le câblage.
Référez-vous à la section 2-4.
31
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
c. Installez le nouveau système parallèle en vous référant à la section précédente.
8)
Retirer une unité du système parallèle
Il existe deux méthodes de retrait d’une unité du système parallèle :
Première méthode :
1) Appuyez à deux reprises sur la touche « ARRÊT », chaque appui étant d’une durée supérieure
à 0,5 s. l’onduleur entrera alors en mode de bypass ou en mode « Pas de sortie » sans sortie.
2) Ouvrir le disjoncteur de sortie externe de cette unité, puis le disjoncteur d’entrée de cet appareil.
3) Une fois celui-ci à l’arrêt, vous pouvez ouvrir le disjoncteur de la batterie (pour le modèle avec
batteries externes) et retirer les câbles parallèles et de partage de courant. Retirez ensuite l’unité
du système parallèle.
Deuxième méthode :
1) Si le bypass est anormal, vous ne pourrez pas retirer l’onduleur sans interruption. Vous devez
couper la charge et arrêter le système d’abord.
2) Assurez-vous que le réglage de bypass est activé dans chaque onduleur, puis éteignez le système
en marche. Tous les onduleurs basculeront en mode Bypass. Retirez tous les capots de bypass
d’entretien et réglez les commutateurs d’entretien de la position « ONDULEUR » à la position
« BPS ». Coupez tous les disjoncteurs d’entrée et les disjoncteurs de batterie du système
parallèle.
3) Coupez le disjoncteur de sortie et retirez le câble parallèle et le câble de partage de courant de
l’onduleur que vous souhaitez retirer. Retirez-la ensuite du système parallèle.
4) Allumez le disjoncteur d’entrée de l’onduleur restant pour que le système bascule en mode Bypass.
Réglez les commutateurs d’entretien de la position « BPS » à la position « ONDULEUR » et
remettez les capots de bypass d’entretien en place.
5) Allumez l’onduleur restant conformément aux indications de la section précédente.
Avertissement : (Uniquement pour le système parallèle)
32
●
Avant d’allumer le système parallèle pour activer l’onduleur, vérifiez que tous les commutateurs
d’entretien de l’ensemble sont à la même position.
●
Lorsque le système parallèle est activé de manière à fonctionner en mode onduleur, veuillez
n’actionner le commutateur d’entretien d’aucune unité.
●
Le mode ÉCO n’est pas pris en charge par le système parallèle. Par conséquent, veuillez « ne pas
activer » le mode ÉCO d’aucune unité.
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
3-6. Signification des abréviations sur l’écran LCD
Abréviation
ENA
DIS
ATO
BAT
NCF
Affichage
Définition
Activer
Désactiver
Auto
Batterie
Mode normal (pas le mode
CVCF)
CF
Mode CVCF (mode
Convertisseur de fréquence)
SUB
ADD
ON
OFF
FBD
OPN
RES
N.L
CHE
33
Soustraire
Ajouter
Marche
Arrêt
Non autorisé
Autoriser
Réservé.
Perte de la ligne neutre
Vérifier
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
OP.V
Tension de sortie
Parallèle, 001 fait référence à
PAR
au premier onduleur
AN
Phase 1 - Neutre
BN
Phase 2- Neutre
CN
Phase 3- Neutre
AB
Phases 1 et 2
BC
Phases 2 et 3
CA
Phases 3 et 1
HS.H
Secours immédiat
3-7. Réglage de l’écran LCD
Il existe trois paramètres pour configurer l’onduleur. Se référer au schéma 13.
Paramètre 1
Le Paramètre 1 est réservé aux différents
programmes. Il y a 20 programmes à
configurer. Voir le tableau ci-dessous.
Les paramètres 2 et 3 sont les options de
configuration ou les valeurs possibles pour
chaque programme.
REMARQUE : Utilisez les boutons « Haut » et
« Bas » pour modifier les programmes ou les
paramètres.
Paramètre 2
Paramètre 3
Schéma 13 : Réglage de l’écran LCD
Liste des 20 programmes disponibles pour le paramètre 1 :
Code
Description
01
Tension de sortie
34
Bypass
FA
Éco
CVCF
Batterie
Test de
batterie
O*
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Code
Description
02
Fréquence de sortie
O
03
Plage de tension de bypass
O
04
Plage de fréquence de bypass
O
05
Activer/désactiver le mode ÉCO
O
06
Plage de tension du mode ÉCO
O
07
Plage de fréquence du mode ÉCO
O
08
Réglage du mode Bypass
O
O
O
O
09
10
11
Bypass
Réglage du temps de décharge maximal
de la batterie
Réservé.
FA
Éco
CVCF
Batterie
O
O
O
Test de
batterie
O
Réservé aux futures options
Réglage de la fonction de secours
immédiat
O
12
Détection de perte de neutre
O
O
O
O
O
O
13
Étalonnage de tension de batterie
O
O
O
O
O
O
14
Réglage de la tension du chargeur
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
15
16
17
18
19
Réglage de la tension de l’onduleur A
phase A
Réglage de la tension de l’onduleur B
phase B
Réglage de la tension de l’onduleur C
phase C
Étalonnage de la tension de la sortie A
phase A
Étalonnage de la tension de la sortie B
phase B
Étalonnage de la tension de la sortie C
O
phase C
* O (oui) signifie que ce programme peut être configuré dans ce mode.
20
REMARQUE : Tous les réglages ne sont sauvegardés que lorsque l’onduleur s’éteint normalement alors
qu’une batterie interne ou externe est connectée. (L’arrêt normal de l’onduleur implique l’arrêt du
disjoncteur d’entrée en mode Bypass/Pas de sortie).
01 : Tension de sortie
Interface
Paramétrage
Paramètre 3 : Tension de sortie
Pour les modèles HV de 208/220/230/240 VAC, choisissez la
tension de sortie suivante :
208 : La tension de sortie est de 208 VAC
220 : La tension de sortie est de 220 VAC
230 : La tension de sortie est de 230 VAC (par défaut)
240 : La tension de sortie est de 240 VAC
Pour les modèles LV de 120/127 VAC, choisissez la tension de
sortie suivante :
120 : La tension de sortie est de 120 VAC (par défaut)
127 : La tension de sortie est de 127 VAC
35
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
02 : Fréquence de sortie
Interface
60 Hz, mode CVCF
50 Hz, mode normal
ATO
Paramétrage
Paramètre 2 : Fréquence de sortie
Réglage de la fréquence de sortie. Choisissez l’une des trois
options du paramètre 2 :
50,0 Hz : La fréquence de sortie définie est de 50,0 Hz.
60,0Hz : La fréquence de sortie définie est de 60,0 Hz.
ATO : Si cette option est sélectionnée, la fréquence de sortie sera
déterminée en fonction de la dernière fréquence normale. Si elle
est comprise entre 46 Hz et 54 Hz, la fréquence de sortie sera
de 50,0 Hz. Si elle est comprise entre 56 Hz et 64 Hz, la fréquence
de sortie sera de 60,0 Hz. ATO est le réglage par défaut.
Paramètre 3 : Mode de fréquence
Réglage de la fréquence de sortie en mode CVCF ou non CVCF.
Vous pouvez choisir les deux options suivantes du paramètre 3 :
CF : Configuration de l’onduleur en mode CVCF. Si cette option
est sélectionnée, la fréquence de sortie sera fixée à 50 Hz
ou 60 Hz en fonction du réglage du paramètre 2. La fréquence
d’entrée pourrait être comprise entre 46 Hz et 64 Hz.
NCF : Réglage de l’onduleur en mode normal (pas en mode
CVCF).
Si cette option est sélectionnée, la fréquence de sortie sera
synchronisée avec la fréquence d’entrée dans la plage comprise
entre 46 Hz et environ 54 Hz à 50 Hz ou entre 56 Hz et
environ 64 Hz à 60 Hz, en fonction du réglage du paramètre 2.
Si 50 Hz est sélectionné dans le paramètre 2, l’onduleur bascule
en mode Batterie lorsque la fréquence d’entrée n’est pas comprise
entre 46 Hz et environ 54 Hz. Si 60 Hz est sélectionné dans le
paramètre 2, l’onduleur bascule en mode Batterie lorsque la
fréquence d’entrée n’est pas comprise entre 56 Hz et
environ 64 Hz.
* Si le paramètre 2 est ATO, le paramètre 3 affiche la fréquence
actuelle.
03 : Plage de tension de bypass
Interface
Paramétrage
Paramètre 2 : Définit la tension minimum acceptable pour le
bypass.
Pour les modèles 208/220/230/240 VAC, la plage de réglage
s’étend de 176 V à 209 V et la valeur par défaut est 176 V.
Pour les modèles 120/127 VAC, la plage de réglage s’étend de
96 V à 88 V et la valeur par défaut est 96 V.
Paramètre 3 : Définit la tension maximum acceptable pour le
bypass.
Pour les modèles 208/220/230/240 VAC, la plage de réglage
s’étend de 231 V à 276 V et la valeur par défaut est 264 V.
Pour les modèles 120/127 VAC, la plage de réglage s’étend de
146 V à 156 V et la valeur par défaut est 146 V.
36
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
04 : Plage de fréquence de bypass
Interface
Paramétrage
Paramètre 2 : Définit la fréquence minimum acceptable pour le
bypass.
Système de 50 Hz : La plage de réglage est comprise
entre 46,0 Hz et 49,0 Hz.
Système de 60 Hz : La plage de réglage est comprise
entre 56,0 Hz et 59,0 Hz.
La valeur par défaut est de 46,0 Hz/56,0 Hz.
Paramètre 3 : Définit la fréquence maximum acceptable pour le
bypass.
50 Hz : La plage de réglage est comprise entre 51,0 Hz et 54,0 Hz.
60 Hz : La plage de réglage est comprise entre 61,0 Hz et 64,0 Hz.
La valeur par défaut est de 54,0 Hz/64,0 Hz.
05 : Activer/désactiver le mode ÉCO
Interface
Paramétrage
Paramètre 3 : Activer ou désactiver la fonction ÉCO. Vous
pouvez choisir les deux options suivantes :
DÉSACT : Désactiver la fonction ÉCO (par défaut)
ACT : Activer la fonction ÉCO
Si la fonction ÉCO est désactivée, la plage de tension et la plage
de fréquence du mode ÉCO peuvent encore être définies, mais
cela n’a de sens que si la fonction ÉCO est activée.
* Si le système fonctionne en parallèle, veillez à le régler sur
« DIS » uniquement.
06 : Plage de tension du mode ÉCO
Interface
Paramétrage
Paramètre 2 : Point de tension basse en mode ÉCO. La plage de
réglage est comprise entre -5 % et 10 % de la tension nominale.
Paramètre 3 : Point de tension haute en mode ÉCO. La plage de
réglage est comprise entre +5 % et +10 % de la tension
nominale.
07 : Plage de fréquence du mode ÉCO
Interface
Paramétrage
Paramètre 2 : Définir le point de fréquence minimum du mode
ÉCO.
Système de 50 Hz : La plage de réglage est comprise
entre 46,0 Hz et 48,0 Hz.
Système de 60 Hz : La plage de réglage est comprise
entre 56,0 Hz et 58,0 Hz.
La valeur par défaut est de 48,0 Hz/58,0 Hz.
Paramètre 3 : Définir le point de fréquence maximum du mode
ÉCO.
50 Hz : La plage de réglage est comprise entre 52,0 Hz
et 54,0 Hz.
60 Hz : La plage de réglage est comprise entre 62,0 Hz
et 64,0 Hz.
La valeur par défaut est de 52,0 Hz/62,0 Hz.
37
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
08 : Réglage du mode Bypass
Interface
09 : Réglage du temps de décharge maximal de la batterie
Interface
Paramétrage
Réservé aux futures options.
11 : Réglage de la fonction de secours immédiat
Interface
38
Paramétrage
Paramètre 3 :
000~999 : Définit le temps de décharge maximal entre 0 min
et 999 min. l’onduleur s’arrête pour protéger la batterie si le temps
de décharge s’écoule avant que la batterie soit sous tension. La
valeur par défaut est de 990 min.
DÉSACT : Désactive la protection de la batterie contre la
décharge. La durée d’autonomie dépend de la capacité de la
batterie.
10 : Réservé.
Interface
Paramétrage
Paramètre 2 :
OPN : Bypass autorisé. Lorsque cette option est sélectionnée,
l’onduleur fonctionne en mode Bypass selon qu’il est activé ou
désactivé (par défaut)
FBD : Bypass non autorisé. Lorsque cette option est
sélectionnée, le fonctionnement en mode Bypass n’est pas
autorisé, quelle que soit la situation.
Paramètre 3 :
ACT : Bypass activé. Lorsque cette option est sélectionnée, le
mode Bypass est activé (par défaut).
DÉSACT : Bypass désactivé. Lorsque cette option est
sélectionnée, la bypass automatique est acceptable, mais le
bypass manuel n’est pas autorisé. Le bypass manuel permet aux
utilisateurs d’activer manuellement le mode Bypass de l’onduleur.
Par exemple, lorsqu’on appuie sur le bouton ARRÊT en mode
AC, on bascule en mode Bypass.
Paramétrage
Paramètre 2 :
HS.H : Indique la fonction de secours immédiat.
Paramètre 3 : Active ou désactive la fonction de secours
immédiat.
OUI : La fonction de secours immédiat est activée. Cela signifie
que l’onduleur actuel est définie comme hôte de la fonction de
secours immédiat, et qu’elle redémarre une fois le courant
alternatif rétabli, même lorsqu’aucune batterie n’est connectée.
NON : La fonction de secours immédiat est désactivée. l’onduleur
fonctionne en mode Normal et ne peut pas redémarrer sans
batterie.
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
12 : Détection de perte de neutre
Interface
13 : Étalonnage de tension de batterie
Interface
Paramétrage
Paramètre 2 : Sélectionnez la fonction « Ajouter » ou
« Soustr. » pour ajuster la tension de la batterie au chiffre réel.
Paramètre 3 : La plage de tension est comprise entre
0 V et 9,9 V et la valeur par défaut est 0 V.
14 : Réglage de la tension du chargeur
Interface
39
Paramétrage
Paramètre 2 :
N.L : Indique la fonction de détection de perte de neutre.
Paramètre 3 :
DÉSACT : Désactive la fonction de détection de perte de neutre.
L’ONDULEUR ne détectera pas la perte de neutre ni la présence
de celui-ci.
ATO : l’onduleur détectera automatiquement la perte du neutre ou
la présence de celui-ci. En cas de détection de perte de neutre,
une alarme est générée. Si l’onduleur est allumé, elle basculera
en mode Batterie. Une fois le neutre restauré et détecté, l’alarme
se coupe automatiquement et l’onduleur repasse également
automatiquement en mode normal.
CHE : l’onduleur détecte automatiquement la perte du neutre. En
cas de détection de perte de neutre, une alarme est générée. Si
l’onduleur est allumé, elle basculera en mode Batterie. Une fois le
neutre restauré, l’alarme NE se coupe PAS automatiquement et
l’onduleur NE repasse également PAS automatiquement en mode
normal.
Ici, vous devez couper l’alarme et faire passer manuellement
l’onduleur en mode normal. L’opération est la suivante : Tout
d’abord, accédez à ce menu et appuyez sur la touche « Entrée »
pour faire clignoter l’indication « CHE ». Ensuite, appuyez à
nouveau sur la touche « Entrée » pour activer la détection du
neutre (vérifier). En cas de détection du neutre, l’alarme se coupe
automatiquement et l’onduleur repasse en mode normal. En cas
de non-détection du neutre, l’onduleur continuera à émettre une
alarme et demeurera sur le dernier statut jusqu’à la bonne
détection du neutre lors de l’opération de vérification manuelle
suivante.
CHE est le réglage par défaut.
Paramétrage
Paramètre 2 : Vous pouvez choisir Ajouter ou Soustr. Pour
ajuster la tension du chargeur
Paramètre 3 : La plage de tension est comprise entre 0 V
et 9,9 V et la valeur par défaut est 0 V.
REMARQUE :
* Avant de procéder au réglage de la tension, assurez-vous de
débrancher toutes les batteries afin d’obtenir une tension de
chargeur précise.
* Toute modification doit être conforme aux spécifications de la
batterie.
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
15 : Réglage de la tension de l’onduleur A Phase A
Interface
Paramétrage
Paramètre 2 : Vous pouvez choisir Ajouter ou Soustr. Pour
ajuster la tension de l’onduleur A.
Paramètre 3 : La plage de tension est comprise entre 0 V
et 9,9 V et la valeur par défaut est 0 V.
* Les fonctions Ajouter ou Soustr. dépendent de la tension de
sortie que vous définissez.
16 : Réglage de la tension de l’onduleur B Phase B
Interface
Paramétrage
Paramètre 2 : Vous pouvez choisir Ajouter ou Soustr. Pour
ajuster la tension de l’onduleur B*.
Paramètre 3 : La plage de tension est comprise entre
0 V et 9,9 V et la valeur par défaut est 0 V.
* Il affichera le numéro 1 sous
ou
représenter la tension de l’onduleur B.
17 : Réglage de la tension de l’onduleur C Phase C
Interface
Paramétrage
Paramètre 2 : Vous pouvez choisir Ajouter ou Soustr. Pour
ajuster la tension de l’onduleur C*.
Paramètre 3 : La plage de tension est comprise entre
0 V et 9,9 V et la valeur par défaut est 0 V.
* Il affichera le numéro 2 sous
ou
représenter la tension de l’onduleur C.
Paramétrage
Paramètre 2 : il affiche toujours OP.V comme tension de sortie.
Paramètre 3 : il indique la valeur de mesure interne de la tension
de la sortie A que vous pouvez calibrer en appuyant sur Haut ou
Bas selon que la mesure est faite depuis un multimètre interne ou
externe. Le résultat du calibrage sera appliqué après l’appui sur le
bouton Entrée. La plage d’étalonnage est limitée à +/-9 V. Cette
fonction est normalement utilisée pour le fonctionnement en
parallèle.
19 : Étalonnage de la tension de la sortie B Phase B
Interface
Paramétrage
Paramètre 2 : il affiche toujours OP.V comme tension de sortie*.
Paramètre 3 : il indique la valeur de mesure interne de la tension
de la sortie B que vous pouvez calibrer en appuyant sur Haut ou
Bas selon que la mesure est faite depuis un multimètre interne ou
externe. Le résultat du calibrage sera appliqué après l’appui sur le
bouton Entrée. La plage d’étalonnage est limitée à +/-9 V. Cette
fonction est normalement utilisée pour le fonctionnement en
parallèle.
* Il affichera le numéro 1 sous
tension de la sortie B.
40
pour
18 : Étalonnage de la tension de la sortie A Phase A
Interface
pour
pour représenter la
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
20 : Étalonnage de la tension de la sortie C Phase C
Interface
Paramétrage
Paramètre 2 : il affiche toujours OP.V comme tension de sortie.
Paramètre 3 : il indique la valeur de mesure interne de la tension
de la sortie C que vous pouvez calibrer en appuyant sur Haut ou
Bas selon que la mesure est faite depuis un multimètre interne ou
externe. Le résultat du calibrage sera appliqué après l’appui sur le
bouton Entrée. La plage d’étalonnage est limitée à +/-9 V. Cette
fonction est normalement utilisée pour le fonctionnement en
parallèle.
* Il affichera le numéro 2 sous
tension de la sortie C.
pour représenter la
3-8. Mode de fonctionnement/description des états
Le tableau suivant indique l’affichage de l’écran LCD pour les modes de fonctionnement et les états.
(1) Si l’onduleur est en mode de fonctionnement normal, elle affiche sept écrans l’un après l’autre,
représentant tour à tour les tensions d’entrée triphasées neutre (An, bn, Cn), 3 tensions d’entrée entre
phase (Ab, bC, CA) et la fréquence.
(2) Si des onduleurs parallèles sont mis en place avec succès, il affiche un écran supplémentaire avec
« PAR » comme paramètre 2 et le numéro assigné au paramètre 3 comme l’indique le schéma de
l’écran parallèle ci-dessous. L’onduleur principal recevra par défaut le numéro « 001 » et les onduleurs
esclaves le numéro « 002 » ou « 003 ». Les numéros attribués peuvent être modifiés de manière
dynamique en cours de fonctionnement ;
Écran parallèle
Mode de fonctionnement/état
Mise en
Description
marche de
secondes pendant l’initialisation du système et de l’UC.
l’onduleur
Écran LCD
Mode « Pas de
Description
sortie »
À l’allumage de l’onduleur, celle-ci entrera dans ce mode pendant quelques
Lorsque la tension/fréquence de bypass est hors de la plage acceptable ou
lorsque la bypass est désactivée (ou interdite), l’onduleur entrera en mode
« Pas de sortie » à l’allumage ou lors de sa mise hors tension. Cela signifie
que l’onduleur n’a pas de sortie. Des bips d’alarme retentissent toutes les
2 minutes.
41
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Écran LCD
Mode AC
Description
Lorsque la tension d’entrée est dans la plage acceptable, l’onduleur délivre
un courant alternatif pur et stable à la sortie. l’onduleur charge également la
batterie en mode CA.
Écran LCD
42
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Mode ÉCO
Description
Lorsque la tension d’entrée est dans la plage de régulation de tension et
que le mode ÉCO est activé, l’onduleur est alimenté directement par le
secteur sans passer par le circuit ondulé pour économiser l’énergie.
Écran LCD
Mode CVCF
Description
Lorsque la fréquence de sortie est réglée sur « CF », l’onduleur délivre une
fréquence constante (50 Hz ou 60 Hz). Dans ce mode, le bypass est
désactivé mais l’onduleur charge néanmoins la batterie.
Écran LCD
43
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Mode batterie
Description
Lorsque la tension/fréquence d’entrée est hors de la plage acceptable ou
en cas de panne d’alimentation, l’onduleur bascule sur la batterie et émet
un bip d’alarme toutes les 4 secondes.
Écran LCD
Mode bypass
Description
Lorsque la tension d’entrée est dans la plage acceptable et que la bypass
est activée, arrêter l’onduleur pour qu’il passe en mode Bypass. Des bips
d’alarme retentissent toutes les 2 minutes.
Écran LCD
44
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Test de batterie
Description
Lorsque l’onduleur est en mode AC ou CVCF, appuyez sur la touche
« Test » pendant plus de 0,5 s. l’onduleur émettra alors un bip et
commencera le « Test de la batterie ». La flèche située entre les icônes I/P
et l'onduleur clignotera à titre de rappel pour les utilisateurs. Cette
opération permet de vérifier l’état de la batterie.
Écran LCD
45
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
État
Description
d’avertissement
Si des erreurs se produisent dans l’onduleur (mais qu’il fonctionne toujours
normalement), un écran supplémentaire apparaîtra pour représenter la
situation d’avertissement. L’icône
clignote sur cet écran d’alerte qui
peut afficher jusqu’à 3 codes d’erreur indiquant chacun une erreur. La
signification des codes est fournie dans le tableau des codes
d’avertissement.
Écran LCD
État de défaut
Description
Lorsqu’une panne s’est produite dans l’onduleur, l’onduleur est bloqué. Le
code d’erreur est affiché à l’écran et l’icône
s’allume. La signification
des codes est fournie dans le tableau des codes d’erreurs.
Écran LCD
46
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
3-9. Code de défaut (icone
fixe)
Panne
Code de défaut
Icône
Panne
Code de défaut
Icône
01
Défaut de démarrage du bus
Aucune
42
Défaut de communication DSP
Aucune
DC
02
Surtension BUS DC
Aucune
43
Surcharge
03
Soustension BUS DC
Aucune
46
Réglage de l’onduleur incorrect
Aucune
04
Déséquilibre de bus DC
Aucune
47
Défaut de communication MCU
Aucune
06
Surintensité du convertisseur
Aucune
48
Deux versions de firmware DSP
Aucune
sont incompatibles dans le
DC
système parallèle.
11
Échec de démarrage progressif
Aucune
60
Phase du circuit en court-circuit
Aucune
61
SCR de bypass en court-circuit
Aucune
62
SCR de bypass en circuit ouvert
Aucune
63
Forme d’onde de tension
Aucune
de l’onduleur
12
Tension élevée du circuit
onduleur
15
Court-circuit sur circuit
onduleur entre phase B et
neutre
16
Court-circuit sur circuit
onduleur entre phase C et
anormale en phase R
neutre
17
Court-circuit sur circuit
64
onduleur entre phase A et B
18
Aucune
anormale en phase S
Court-circuit sur circuit
65
onduleur entre phase B et C
19
Forme d’onde de tension
Forme d’onde de tension
Aucune
anormale en phase T
Court-circuit sur circuit
66
Courant d’onduleur anormal
Aucune
67
Sortie de bypass en court-circuit
Aucune
68
O/P de bypass phase/phase en
Aucune
onduleur entre phase C et A
1A
Défaut de puissance négative
sur circuit onduleur A
1B
Défaut de puissance négative
sur circuit onduleur B
47
court-circuit
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
1C
Défaut de puissance négative
Aucune
69
sur circuit onduleur C
21
SCR de la batterie en
Aucune
6C
Chute de tension du BUS trop
Aucune
rapide
Relais de l’onduleur en circuit
Aucune
6D
ouvert
24
Aucune
court-circuit
court-circuit
23
SCR du circuit de l’onduleur en
Valeur de l’erreur
Aucune
d’échantillonnage de courant
Relais de l’onduleur en
Aucune
6E
Erreur d’alimentation SPS
Aucune
court-circuit
25
Défaut de câblage alimentation
Aucune
6F
Polarité inversé de la batterie
Aucune
31
Défaut de communication
Aucune
71
Surintensité de l’IGBT PFC en
Aucune
parallèle
32
phase R
Défaillance du signal de l’hôte
Aucune
72
Surintensité de l’IGBT PFC en
Aucune
phase S
33
Défaut de synchronisation
Aucune
73
Surintensité de l’IGBT PFC en
Aucune
phase T
34
Défaillance du seuil de
Aucune
74
déclenchement de
Surintensité de l’IGBT INV en
Aucune
phase R
synchronisation
35
Perte de communication
Aucune
75
parallèle
36
Déséquilibre de courant de
Aucune
76
Surintensité de l’IGBT INV en
Aucune
3-10. Voyant d’avertissement : L’icône
Icône
(clignotante)
clignote
Alarme
Batterie faible
Un bip toutes les secondes
Surcharge
Deux bips par seconde
Batterie non connectée
Un bip toutes les secondes
48
Aucune
phase T
Surchauffe
Mise en garde
Aucune
phase S
sortie parallèle
41
Surintensité de l’IGBT INV en
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Surcharge faible
Un bip toutes les secondes
Activation de l’EPO
Un bip toutes les secondes
Panne de
ventilateur/surchauffe
Un bip toutes les secondes
Panne de chargeur
Un bip toutes les secondes
Fusible I/P grillé
Un bip toutes les secondes
Autres avertissements (se
référer à la section 3-11)
49
Un bip toutes les secondes
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Code d’avertissement
Code
d’avertissement
Événement
d’avertissement
Code
d’avertissement
01
Batterie non connectée
21
02
Perte de neutre d’entrée
22
04
Rotation phase entrée
anormale
33
05
07
Rotation phase de bypass
anormale
Surcharge de la limite de
tolérence
34
3A
Condition d’alimentation
Les situations de la ligne sont
différentes dans le système parallèle
Conditions de bypass sont
différentes dans le système parallèle
Verrouillé en bypass après trois
surcharges en l’espace
de 30 minutes
Déséquilibre de courant du
convertisseur
Le capot du commutateur du bypass
manuel est ouvert
Alimentation secteur
08
Batterie faible
3C
09
Surcharge
3D
La bypass est instable
0A
Panne de ventilateur
3E
Tension de batterie trop élevée
0B
Activation de l’EPO
3F
Tension de batterie déséquilibrée
0D
Surchauffe
40
Chargeur en court-circuit
0E
Panne de chargeur
particulièrement déséquilibrée
4. Dépannage
Si l’onduleur ne fonctionne pas correctement, veuillez résoudre le problème en vous servant du tableau
ci-dessous.
Symptôme
Aucune indication et aucune alarme
sur le panneau d’affichage avant,
même si l’alimentation secteur est
normale.
L’icône
et le code d’alarme
clignotent sur l’écran LCD et un bip
d’alarme retentit toutes les secondes.
Les icônes
et
clignotent sur l’écran LCD et un bip
d’alarme retentit toutes les secondes.
Les icônes
et
clignotent sur l’écran LCD et un bip
d’alarme retentit deux fois par
seconde.
50
Cause possible
Remède
L’alimentation CA d’entrée
n’est pas bien connectée.
Vérifier si le câble d’entrée est
correctement branché sur le
secteur.
La fonction EPO est activée. À
ce stade, le bouton d’arrêt
d’urgence EPO est en position
« ARRÊT » ou le cavalier est
ouvert.
Définir le circuit en position
fermée pour désactiver la
fonction EPO.
La batterie interne ou externe
n’est pas correctement
connectée.
Vérifier si toutes les batteries
sont correctement connectées.
l’onduleur est en surcharge.
Retirer l’excédent de charges
de la sortie de l’onduleur.
l’onduleur est en surcharge.
Les appareils connectés à
l’onduleur sont directement
alimentés par le réseau
électrique via la bypass.
Retirer l’excédent de charges
de la sortie de l’onduleur.
Après des surcharges répétées,
l’onduleur est verrouillée en
mode Bypass. Les appareils
connectés sont directement
alimentés par le secteur.
Retirer d’abord l’excédent de
charges de la sortie de
l’onduleur. Ensuite, arrêter
l’onduleur et la redémarrer.
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Le code d’erreur affiché est 43.
L’icône
s’allume sur l’écran
LCD et des bips d’alarme retentissent
de manière continue.
Le code d’erreur affiché est
le 14, 15, 16, 17, 18 ou 19 ; l’icône
s’allume sur l’écran LCD et
des bips d’alarme retentissent de
manière continue.
D’autres codes d’erreur sont affichés
sur l’écran LCD et des bips d’alarme
retentissent de manière continue.
La durée d’autonomie de la batterie
est inférieure à la valeur nominale
La trop longue surcharge de
l’onduleur s’est changée en
panne. l’onduleur s’éteint alors
automatiquement.
Retirer l’excédent de charges
de la sortie de l’onduleur et la
redémarrer.
l’onduleur s’éteint
automatiquement parce qu’un
court-circuit s’est produit à la
sortie de l’onduleur.
Vérifier le câblage de sortie et
si les appareils connectés sont
en court-circuit.
Une panne interne de
l’onduleur s’est produite.
Contacter son distributeur.
Les batteries ne sont pas
complètement chargées
Défaut des batteries
Les icônes
et
clignotent
sur l’écran LCD et un bip d’alarme
retentit toutes les secondes.
Le code d’alarme 02 et l’icône
clignotent sur l’écran LCD. Des bips
d’alarme retentissent toutes les
secondes.
Le ventilateur est bloqué ou ne
fonctionne pas ; ou la
température de l’onduleur est
trop élevée.
Le fil de neutre d’entrée est
déconnecté.
Le fusible d’entrée de L2
ou L3 est grillé.
Charger les batteries pendant
au moins 7 heures, puis
vérifier leurs capacités. Si le
problème persiste, consulter
son revendeur.
Contacter le revendeur pour
remplacer la batterie.
Inspecter les ventilateurs et
aviser le revendeur.
Vérifier et corriger la
connexion du neutre d’entrée.
Si la connexion est correcte et
que l’alarme s’affiche toujours,
veuillez vous référez-vous à la
section relative au réglage de
l’écran LCD pour accéder au
menu de vérification de perte
de neutre afin de vérifier si la
valeur du paramètre 3 est
« CHE ». Si tel est le cas,
veuillez appuyer d’abord sur la
touche « Entrée » pour faire
clignoter l’indication « CHE »,
puis appuyer à nouveau sur la
touche « Entrée » pour
amener l’onduleur à effacer
l’alarme. Si l’avertissement
persiste, veuillez vérifier les
fusibles d’entrée de L2 et L3.
Remplacer le fusible.
5. Stockage et entretien
5-1. Entreposage
Avant l’entreposage, chargez l’onduleur pendant au moins 7 heures. Couvrez l’onduleur avant de la
ranger en position verticale dans un endroit sec et frais. Au cours de l’entreposage, rechargez la
batterie conformément aux indications du tableau suivant :
51
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Température de stockage
Fréquence de la recharge
Durée de la charge
De -25 °C à 40 °C
Tous les 3 mois
1 à 2 heures
De 40 °C à 45 °C
Tous les 2 mois
1 à 2 heures
5-2. Entretien
l’onduleur fonctionne avec des tensions dangereuses. Les réparations ne doivent être effectuées
que par le personnel de maintenance.
Même lorsque l’alimentation secteur de l’appareil est coupée, les composants internes de
l’onduleur sont toujours connectés aux blocs-batterie qui sous potentiellement dangereux.
Avant d’effectuer tout entretien ou toute réparation, déconnectez les batteries et vérifiez qu’il n’y a
aucun courant présent ni aucune tension dangereuse aux bornes des condensateurs de grande capacité
tels que les condensateurs BUS.
Seules les personnes compétentes ou les personnes suffisamment formées aux opérations liées
aux batteries peuvent remplacer ces dernières et superviser les opérations en prenant les mesures de
sécurité requises. Les personnes non autorisées doivent être tenues à l’écart des batteries.
Vérifiez qu’aucune tension n’est présente entre les bornes de la batterie et le sol avant tout
entretien ou toute réparation. Le circuit de la batterie de ce produit n’est pas isolé de la tension d’entrée.
Des tensions dangereuses peuvent survenir entre les bornes de la batterie et le sol.
Les batteries peuvent occasionner des chocs électriques et présenter un courant de court-circuit
élevé. Veuillez retirer vos montres-bracelets, bagues et autres objets personnels métalliques avant tout
entretien ou toute réparation, et utilisez uniquement des outils aux poignées isolées pour vos travaux
d’entretien et de réparation.
Lors du remplacement des batteries, installez le même nombre de batteries et des batteries de
même type.
N’essayez pas de mettre les batteries au rebut en les brûlant. Cela pourrait provoquer une
explosion. Les batteries doivent être recyclées comme il se doit et dans le strict respect des
réglementations locales.
N’ouvrez pas ou ne détruisez pas les batteries. L’électrolyte qui s’en déverse peut causer des
dommages à la peau et aux yeux. Il peut être nocif.
Veuillez ne remplacer le fusible que par un fusible de type et d’intensité identiques afin d’éviter les
risques d’incendie.
Ne démontez pas l’onduleur.
52
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
6. Spécifications techniques
Modèles HV (400 V)
CAPACITÉ*
ENTRÉE
Plage de
tension
Perte de ligne
basse
Retour de
ligne basse
Perte de ligne
haute
Retour de
ligne haute
Plage de fréquence
E4
Evolution
II + 10 k
TT (S)
E4
Evolution
II + 15 k
TT (S)
E4
Evolution
II + 20 k
TT (S)
E4
Evolution
II + 30 k
TT (S)
E4
Evolution
II + 40 k
TT (S)
E4
Evolution
II + 60 k TT
S
E4
Evolution
II + 80 k
TT S
10 KVA
10 KW
15 KVA
15 KW
20 KVA
20 KW
30 KVA
30 KW
40 KVA
40 KW
60 KVA
60 KW
80 KVA
80 KW
110 VAC (Ph-N) ± 3 % à 50 % de charge ; 176 VAC (Ph-N) ± 3 % et 100 % de charge
Perte de ligne basse tension + 10 V
300 VAC(L-N) ± 3 % à 50 % de charge ; 276 VAC (L-N) ± 3 % à 100 % de charge
Perte de ligne haute tension - 10 V
46 Hz ~ 54 Hz pour système 50 Hz
56 Hz ~ 64 Hz pour système 60 Hz
3 ph + Neutre
≧0,99 à 100 % de charge
Phase
Facteur de puissance
SORTIE
Phase
3 Ph + Neutre
Tension de sortie
360/380/400/415 VAC (Ph-Ph)
208*/220/230/240 VAC (Ph-N)
±1%
Régulation de tension
Plage de fréquence (plage
synchronisée)
Plage de fréquence (mode
batterie)
Saturation
Mode CA
Mode batterie
Facteur de crête
Distorsion harmonique
Temps de
Secteur
transfert
Batterie
Onduleur
46 Hz ~ 54 Hz pour système 50 Hz ;
56 Hz ~ 64 Hz pour système 60 Hz
50 Hz ± 0,1 Hz ou 60 Hz ± 0,1 Hz
100 % ~ 110 % : 60 min ; 110 %~125 % : 10 min ; 125 %~150 % : 1 min ;
>150 % : immédiatement
100 % ~ 110 % : 60 min ; 110 %~125 % : 10 min ; 125 %~150 % : 1 min ;
>150 % : immédiatement
3:1 max
≦ 2 % pour 100 % de charge linéaire ; ≦ 5 % pour 100 % de charge non linéaire
0 ms
0 ms (En cas d’échec de la phase de Verrouillage,
une interruption < 4 ms survient de l’onduleur au bypass)
Bypass
Onduleur
ECO
RENDEMENT
Mode normal
Mode batterie
BATTERIE
Modèle
Type
standard
Quantité
Temps de
recharge
Courant de
charge (max)
Tension de
charge
Modèle
longue
autonomie
53
Type
Quantité
Courant de
charge (max)
Tension de
charge
< 10 ms
95,5 %
94,5 %
12 V/ 7 A
12 V/ 9 A
12 V/ 9 A
12 V/ 7 A
12 V/ 9 A
20 (10 +
32 (16 +
32 (16 +
32 (16+16) pcs x 2
10)
+16)
+16)
rangées
9 heures pour récupérer 90 % de la capacité de la batterie
+/
-136,5 Vcc
±1%
20
+/
-136,5 Vcc
±1%
N/A
2,0 A ± 10 % (recommandé)
1,0~12,0 A (réglable)
+ / -218 Vcc ± 1 %
En fonction des applications
32 ~ 40 (réglable)
1,0~12,0 A ± 10 % (réglable)
2,0~24,0 A ± 10 %
(réglable)
+/- 13,65 Vcc * N ± 1 % (N = 16~20)
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
CARACTÉRISTIQUES PHYSIQUES
Modèle
Dimensions,
standard
L x l x H (mm)
Poids net (kg)
129
Modèle
Dimensions,
longue
L x l x H mm
autonomie
Poids net (kg)
33
ENVIRONNEMENT
Température de
fonctionnement
Humidité relative
Altitude de fonctionnement **
Niveau sonore
GESTION
Smart RS-232 ou USB
SNMP en option
Moins de
55 dB à
1m
627 x 250 x 826
144
627 x 250 x 826
144
48
48
815 x 300 x 1000
N/A
225
250
815 x 300 x 1000
790 x 360 x 1010
60
61
108 (sans
batt)
113 (sans
batt)
0 ~ 40 °C (la durée de Vie de la batterie est réduite
lorsque la température est supérieure à 25 °C)
< 95 % sans condensation
< 1000 m **
Moins de 58 dB à 1 m
Moins de
Moins de
Moins de
65 dB à
70 dB à
70 dB à
1m
1m
1m
Moins de
75 dB à
1m
Prend en charge Windows® 2000/2003/XP/Vista/2008/7/8/10, Linux, Unix et Mac
Gestion de l’alimentation sur le protocole SNMP (compatible avec VMWare© )
et le navigateur web
* La capacité passe à 90 % lorsque la tension de sortie est réglée sur 208 VAC.
** Si l’onduleur est installé ou utilisé à une altitude supérieure à 1 000 mètres, la puissance de sortie doit être déclassée de 1 % tous les
100 mètres au-delà de 1 000 mètres.
***Les spécifications du produit sont sujettes à modifications sans préavis.
54
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Modèles LV (208V)
CAPACITÉ*
ENTRÉE
Plage de
tension
Perte de ligne
basse
Retour de ligne
basse
Perte de ligne
haute
Retour de ligne
haute
Plage de fréquence
Phase
Facteur de puissance
SORTIE
Phase
E4 Evolution
II + 15k TT
(S)
15 KVA
15 KW
E4 Evolution
II + 20k TT
(S)
20 KVA
20 KW
E4 Evolution
II + 30k TT
S
30 KVA
30 KW
E4 Evolution
II + 40k TT
S
40 KVA
40 KW
70 VAC (Ph-N) ± 3 % à 50 % de charge
88 VAC (Ph-N) ± 3 % à 100 % de charge
Perte de ligne basse tension + 5 V
156 VAC(L-N) ± 3 % à 50 % de charge
146 VAC(L-N) ± 3 % à 100 % de charge
Perte de ligne haute tension – 5 V
46 Hz ~ 54 Hz pour système 50 Hz
56 Hz ~ 64 Hz pour système 60 Hz
3 Ph + Neutre
≧0,99 à 100 % de charge
3 Ph + Neutre
Tension de sortie
Régulation de tension
Plage de fréquence
(plage synchronisée)
Plage de fréquence
(mode batterie)
Saturation
Mode CA
Mode batterie
Facteur de crête
Distorsion harmonique
Temps de
transfert
E4 Evolution
II + 10k TT
(S)
10 KVA
10 KW
208/220 VAC (Ph-Ph)
120/127 VAC (Ph-N)
±1%
46 Hz ~ 54 Hz pour système 50 Hz
56 Hz ~ 64 Hz pour système 60 Hz
50 Hz ± 0,1 Hz ou 60 Hz ± 0,1 Hz
100 % ~ 110 % : 60 min ; 110 %~125 % : 10 min ; 125 %~150 % : 1 min ;
>150 % : immédiatement
100 % ~ 110 % : 60 min ; 110 %~125 % : 10 min ; 125 %~150 % : 1 min ;
>150 % : immédiatement
3:1 max
≦ 2 % pour 100 % de charge linéaire ;
≦ 4 % pour 100 % de charge non linéaire (PF ≥ 0,8)
0 ms
Secteur
Batterie
0 ms (En cas d’échec de la phase de Verrouillage,
Onduleur
une interruption < 4 ms survient de l’onduleur au bypass)
Bypass
< 10 ms
Onduleur
ECO
EFFICACITÉ ÉNERGÉTIQUE
Mode CA
93,5 %
Mode batterie
92,5 %
BATTERIE
Modèle
Type
12 V/ 9 A
12 V/ 7 A
12 V/ 9 A
N/A
standard
Quantité
(8 + 8) pcs
(8 + 8) pcs x 2 rangées
Temps de
9 heures pour récupérer 90 %
recharge
de la capacité de la batterie
Courant de charge
1,0~12,0 A ± 10 % (réglable)
(max)
Tension de charge
+ / -109 Vcc ± 1 %
Modèle
Type
En fonction des applications
longue
Quantité
16 ~ 20 (réglable)
autonomie Courant de charge
1,0~12,0 A ± 10 % (réglable)
2,0~24,0 A ± 10 % (réglable)
(max)
Tension de charge
+/- 13,65 Vcc * N ± 1 % (N = 8~10)
CARACTÉRISTIQUES PHYSIQUES
Modèle
Dimensions,
627 x 250 x
815 x 300 x
815 x 300 x
N/A
standard
L x l x H mm
826
1000
1000
Poids net (kg)
144
225
250
Modèle
Dimensions,
627 x 250 x
815 x 300 x
815 x 300 x
790 x 360 x 10 790 x 360 x 10
longue
L x l x H mm
826
1000
1000
10
10
autonomie Poids net (kg)
48
60
61
108 (sans batt) 113 (sans batt)
ENVIRONNEMENT
Température de fonctionnement
0 ~ 40 °C (la durée de Vie de la batterie est réduite lorsque la température est
55
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Humidité relative
Altitude de fonctionnement **
Niveau sonore
GESTION
Smart RS-232 ou USB
SNMP en option
Moins de 58 dB
à1m
supérieure à 25 °C)
< 95 % sans condensation
< 1000 m **
Moins de 65 dB Moins de 70 dB Moins de 70 dB
à1m
à1m
à1m
Moins de 75 dB
à1m
Prend en charge Windows® 2000/2003/XP/Vista/2008/7/8/10, Linux, Unix et Mac
Gestion de l’alimentation sur le protocole SNMP (compatible avec VMWare© )
et le navigateur web
* Si l’onduleur est installé ou utilisé à une altitude supérieure à 1 000 mètres, la puissance de sortie doit être déclassée de 1 % tous les 100
mètres au-delà de 1 000 mètres.
**Les spécifications du produit sont sujettes à modifications sans préavis.
56
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
English version
57
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Table of Contents
1. SAFETY AND EMC INSTRUCTIONS .............................................................................................................. 59
1.1. TRANSPORTATION AND STORAGE .................................................................................................................. 59
1-2. PREPARATION .............................................................................................................................................. 59
1-3. INSTALLATION .............................................................................................................................................. 59
1-4. CONNECTION WARNINGS .............................................................................................................................. 60
1-5. OPERATION ................................................................................................................................................. 61
1-6. MAINTENANCE, SERVICING AND FAULTS ......................................................................................................... 61
1-7. MAINTENANCE, SERVICING AND FAULTS ......................................................................................................... 61
1-8. ABOUT BATTERIES: ....................................................................................................................................... 62
1-9. CE CONFORMITY: ........................................................................................................................................ 62
2. INSTALLATION AND OPERATION ................................................................................................................. 63
2-1. UNPACKING AND INSPECTION........................................................................................................................ 64
2-2. WIRING TERMINAL VIEW ............................................................................................................................... 65
2-3. SINGLE UPS INSTALLATION .......................................................................................................................... 72
2-4. UPS INSTALLATION FOR PARALLEL SYSTEM .................................................................................................. 75
2-5. SOFTWARE INSTALLATION ............................................................................................................................. 77
3. OPERATIONS .................................................................................................................................................. 78
3-1. BUTTON OPERATION .................................................................................................................................... 78
3-2. LED INDICATORS AND LCD PANEL................................................................................................................ 79
3-3. AUDIBLE ALARM ........................................................................................................................................... 81
3-4. SINGLE UPS OPERATION ............................................................................................................................. 81
3-5. PARALLEL OPERATION .................................................................................................................................. 84
3-6. MEANING OF THE ABBREVIATIONS ON THE LCD DISPLAY ................................................................................ 85
3-7. LCD SETTING.............................................................................................................................................. 87
3-8. OPERATING MODE/STATUS DESCRIPTION ..................................................................................................... 92
6-1. 3-9. FAULT CODE ....................................................................................................................................... 97
3-10. WARNING INDICATOR: ICON FLASHING
................................................................................................ 98
3-11.WARNING CODE ......................................................................................................................................... 98
4. TROUBLE SHOOTING .................................................................................................................................... 99
5. STORAGE AND MAINTENANCE.................................................................................................................. 100
5-1. STORAGE .................................................................................................................................................. 100
5-2. MAINTENANCE ........................................................................................................................................... 100
6. TECHNICAL SPECIFICATIONS .................................................................................................................... 102
58
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
1. Safety and EMC instructions
Please strictly comply with all operating instructions in this manual. Keep this manual
in a safe place and read the following instructions carefully before installing the unit.
Do not operate this unit before carefully reading all warnings and operating
instructions.
IMPORTANT!
Installing and connecting UPSs in a way that does not comply with accepted practices releases Infosec
Communication from any liability.
1.1. Transportation and Storage
Only transport the UPS system in the original package to protect it against shocks and impacts.
The UPS must be stored in a room that is ventilated and dry.
1-2. Preparation
Condensation may occur if the UPS system is moved directly from a cold to a warm environment. The
UPS system must be absolutely dry before being installed. Please allow at least two hours for the UPS
system to acclimatize to the environment.
Do not install the UPS system near water or in a damp environment.
Do not install the UPS system where it could be exposed to direct sunlight or near a heater.
Do not block ventilation holes in the UPS housing.
Do not block the air ventilation holes in the UPS housing. The UPS must be installed in a
location with good ventilation or with air-conditioning. Make sure there is enough space
on each side for ventilation. Ideally, the room temperature must not exceed 20°C and
0-90% non-condensing humidity.
1-3. Installation
59
Do not connect appliances or devices which would overload the UPS (e.g. large motor-type
equipment) to its output sockets or terminal.
Do not connect domestic appliances such as hair dryers to UPS outlets.
Place cables in such a way that no one can step on or trip over them.
The UPS provides a grounded terminal, in the final installed system configuration and equipotential
ground bonding to the external UPS battery cabinets.
The UPS may only be installed by qualified maintenance personnel.
An appropriate disconnection device for short-circuit backup protection should be provided in the
building wiring installation.
An integral single emergency switching device to prevent further supply to the load by the UPS
regardless of the mode of operation should be provided in the building wiring installation.
Connect the ground before connecting to the building wiring terminal.
Installation and wiring must be performed in accordance with local electrical laws and regulations.
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
1-4. Connection warnings
There is no standard backfeed protection inside, please isolate the UPS before working according to
this circuit. The isolation device must be able to carry the UPS input current.
Input Rly
Input Rly
Main
Input
L1
Main
Input
L2
L1
L3
N
Input Rly
L2
UPS
L3
N
Bypass
Input
L1
UPS
L2
L3
N
Input relay diagram
Input relay diagram
E4 Evolution II + 10/15/20k TT HV
E4 Evolution II + 10/15/20k TT HV
E4 Evolution II + 10k TT LV
E4 Evolution II + 10k TT LV
(optional dual input)
E4 Evolution II + 30/40/60/80k TT HV
E4 Evolution II + 15/20/30/40k TT LV
•
This UPS should be connected with TN grounding/earthing system.
In accordance with safety standard EN-IEC 62040-1, installation has to be provided with a《Backfeed
Protection》system, as for example a contactor, which will prevent the appearance of
voltage or dangerous energy in the input mains during a mains fault (see figure 24 and
respect the wiring diagram of «Backfeed Protection»depending if the equipment is with
single or three phase input).
•
The power supply for this unit must be three-phase rated in accordance with the equipment nameplate.
It also must be suitably grounded.
•
Use of this equipment in life support applications where failure of this equipment can reasonably be
expected to cause the failure of the life support equipment or to significantly affect its safety or
effectiveness is not recommended. Do not use this equipment in the presence of a flammable
anesthetic mixture with air, oxygen or nitrous oxide.
•
Connect your UPS power module’s grounding terminal to a grounding electrode conductor.
•
This is a product for commercial and industrial application in the second environment –installation
restriction or additional measures may be needed to prevent disturbances.
•
Warning labels should be placed on all primary power switches installed in places away from the device
to alert the electrical maintenance personnel of the presence of a UPS in the circuit. The label will bear
the following or an equivalent text:
-
60
-
Before working on this circuit
Isolate Uninterruptible Power System (UPS)
Then check for Hazardous Voltage between all
terminals including the protective earth.
Risk of Voltage Backfeed
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
1-5. Operation
Never disconnect the ground conductor cable as this would cancel the protective ground of the UPS
system and to all connected loads.
The UPS system features its own, internal current supply (batteries). The UPS output sockets may be
electrically live even if the UPS system is not connected to the mains.
In order to fully disconnect the UPS system, first press the “OFF” button and then disconnect the
mains.
Ensure that no liquid or other foreign objects can enter the UPS system.
1-6. Maintenance, servicing and faults
* Safety
IEC/EN 62040-1
* EMI
Conducted Emission...............................:IEC/EN 62040-2
Category C3
Radiated Emission..................................:IEC/EN 62040-2
Category C3
*EMS
ESD.........................................................:IEC/EN 61000-4-2
Level 4
RS........................................................ ...:IEC/EN 61000-4-3
Level 3
EFT......................................................... :IEC/EN 61000-4-4
Level 4
SURGE................................................... :IEC/EN 61000-4-5
Level 4
CS........................................................... :IEC/EN 61000-4-6
Level 3
Power-frequency Magnetic field.............. :IEC/EN 61000-4-8
Level 4
Low Frequency Signals............................:IEC/EN 61000-2-2
Warning: This is a product for commercial and industrial application in the
second environment-installation restrictions or additional measures may be
needed to prevent disturbances.
1-7. Maintenance, servicing and faults
The UPS system operates with hazardous voltages. Repairs may only be carried out by qualified
maintenance personnel.
Caution - Risk of electric shock. Even after the unit is disconnected from the power supply,
components inside the UPS system are still connected to the battery and electrically live and
dangerous.
Before carrying out any servicing and/or maintenance disconnect the batteries and check that there is
no current or hazardous voltage in the high capability capacitor terminals such as BUS-capacitors.
Only people knowledgeable or who are familiar with batteries and with the required precautionary
measures may replace the batteries and supervise operations. Unauthorized persons must be kept
well away from the batteries.
Caution - Risk of electric shock. The battery circuit is not isolated from the input voltage. Hazardous
voltages may occur between the battery terminals and the ground. Before touching, please check that
no voltage is present!
61
Only replace the fuse with the same type and amperage in order to avoid fire hazards.
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Do not dismantle the UPS system.
1-8. About batteries:
It is recommended that a qualified technician changes the battery.
Do not open or damage the battery! The electrolyte, fundamentally sulphuric acid, can be toxic and
harmful to the skin and eyes. If you come into contact with it, wash the affected body parts thoroughly
with water and clean the soiled clothes.
Do not throw the battery into a fire. It may explode. It has to be disposed of separately at the end of its
useful life. Refer to the local legislation and regulations.
The UPS contains large-capacity batteries. To avoid any danger of electric shock do not open it. If a
battery needs servicing or has to be replaced, please contact the distributor.
Servicing should be performed or supervised by able personnel who will take the necessary
precautions. Keep unauthorized personnel away from batteries.
A battery can lead to a risk of electric shock and cause short circuits. The following precautions should
be followed the qualified technician:
Remove watches, rings or other metal objects from your hands.
Use tools with insulated handles.
Disconnect the charging source prior to connecting or disconnecting battery terminals.
When replacing batteries, use the same type and number of sealed lead-acid batteries.
1-9. CE conformity:
This logo means that the product answers to the EMC and LVD standards (regarding to the
regulation associated with the electric equipment voltage and the electromagnetic fields).
This is a category C3 UPS product. In a residential environment, this product may cause
radio interference, in which case the user may be required to take additional measures.
Important
A UPS device belongs to the electronic and electrical equipment category. At the end of
its useful life it must be disposed of separately and in an appropriate manner.
This symbol is also affixed to the batteries supplied with this device, which means they
too have to be taken to the appropriate place at the end of their useful life.
Contact your local recycling or waste center for information on proper disposal of the used battery.
62
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
2. Installation and Operation
NOTE: Before installation, please inspect the unit. Make sure that nothing inside the package is damaged.
Please keep the original package in a safe place for future use.
NOTE: There are different types of E4 Evolution II TT UPS: standard and long-run models both in High
Voltage and Low Voltage. Please refer to the following table.
NOTE: The Dual Input function is optional for the models E4 Evolution II + 10/15/20k TT HV and E4
Evolution II + 10k TT LV and as standard for the models E4 Evolution II + 30/40/60/80 TT HV and E4
Evolution II + 15/20/30/40 TT LV.
Model
Version
Model
E4 Evolution II + 10k TT HV
E4 Evolution II + 10k TT S HV
E4 Evolution II + 15k TT HV
E4 Evolution II + 15k TT S HV
E4 Evolution II + 20k TT HV
E4 Evolution II + 20k TT S HV
E4 Evolution II + 30k TT HV
E4 Evolution II + 40k TT HV
Standard model
High Voltage
-
E4 Evolution II + 30k TT S HV
E4 Evolution II + 40k TT S HV
Version
Long-run model
High Voltage
E4 Evolution II + 60k TT S HV
E4 Evolution II + 80k TT S HV
E4 Evolution II + 10k TT LV
E4 Evolution II + 10k TT LV
E4 Evolution II + 15k TT LV
E4 Evolution II + 15k TT S LV
E4 Evolution II + 20k TT LV
-
Standard model
Low Voltage
E4 Evolution II + 20k TT S LV
E4 Evolution II + 30k TT S LV
Long-run model
Low Voltage
E4 Evolution II + 40k TT S LV
High Voltage (HV) means rated voltage 380 / 400 / 415 VAC
Low Voltage (LV) means rated voltage 190 / 198 / 208 VAC
63
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
2-1. Unpacking and Inspection
Unpack the package and check the package contents. The shipping package contains:
One UPS
One user manual
One monitoring software CD
One RS-232 cable
One USB cable
One parallel cable (optional for models 10/15/20k VA HV and 10kVA LV)
One Share Current cable (optional for models 10/15/20k VA HV and 10kVA LV)
Before installation, please inspect the unit. Be sure that nothing inside the package is damaged during
transportation. Do not turn on the unit and notify the carrier and dealer immediately if there is any damage
or lacking of some parts. Please keep the original packages in a safe place for future use. It is recommended
to keep each equipment and battery set in their original packages because they have been designed to
assure the maximum protection during transportation and storage.
64
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
2-2. Wiring Terminal View
HV models
Rear Panel
Rear Panel
E4 Evolution II + 10/15/20k (S) TT HV (standard)
E4 Evolution II + 10/15/20k TT (S) HV
(optional dual input)
Input/Output Terminal
Input/Output Terminal
E4 Evolution II + 10/15/20k TT (S) HV (standard)
E4 Evolution II + 10/15/20k TT (S) HV (optional dual input)
65
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Rear Panel
Rear Panel
E4 Evolution II + 30k TT (S) HV
E4 Evolution II + 40k TT (S) HV
Input/Output Terminal
E4 Evolution II + 30/40k TT (S) HV
66
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Front Panel Open door
Front Panel Open door
E4 Evolution II + 60k TT S HV
E4 Evolution II + 80k TT S HV
Input/Output Terminal
E4 Evolution II + 60/80k TT (S) HV
67
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
LV models
Rear Panel
Rear Panel
E4 Evolution II + 10k TT LV (S) (standard)
E4 Evolution II + 10k TT (S) LV
(optional dual input)
Input/Output Terminal
Input/Output Terminal
E4 Evolution II + 10k TT (S) LV (standard)
E4 Evolution II + 10k TT (S) LV (optional dual input)
68
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Rear Panel
Rear Panel
E4 Evolution II + 15k TT (S) LV
E4 Evolution II + 20k TT (S) LV
Rear Panel
E4 Evolution II + 15/20k TT (S) LV
69
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Front Panel Open door
Front Panel Open door
E4 Evolution II + 30k TT S LV
E4 Evolution II + 40k TT S LV
Input/Output Terminal
E4 Evolution II + 30/40k TT (S) LV
70
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
1. RS-232 communication port
2. USB communication port
3. Emergency power off function connector (EPO connector)
4. Share current port (only available for parallel model)
5. Parallel port (only available for parallel model)
6. Intelligent slot
7. External battery connector/terminal (Only available for long-run model)
8. Line input circuit breaker/switch
9. Maintenance bypass switch
10. Input/Output terminal with protection
11. Line input terminal
12. Output terminal
13. Input grounding terminal
14. Output grounding terminal
15. Bypass input circuit breaker/switch
16. Bypass input terminal
17. Grounding terminal
18. Output switch
71
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
2-3. Single UPS Installation
Installation and wiring must be performed in accordance with the local electric laws/regulations and the
following instructions executed by qualified personnel.
1) Make sure the mains wire and breakers in the building are in compliance with the standard of rated
capacity of the UPS to avoid hazard of electric shock or fire.
NOTE: Do not use the wall receptacle as the input power source for the UPS, as its rated current is less
than the UPS’s maximum input current. Otherwise the receptacle may be burned and destroyed.
2)
Switch off the mains switch in the building before installation.
3)
Turn off all the connected devices before connecting to the UPS.
4)
Prepare wires based on the following table (use flexible cables):
HV Model
Wiring spec (mm² / AWG)
Input(Ph)
Input(Ph)
Input(Ph)
E4 Evolution II + 10k TT HV
6 / 14
6 / 14
6 / 14
E4 Evolution II + 15k TT HV
6 / 12
6 / 12
6 / 12
E4 Evolution II + 20k TT HV
10 / 10
10 / 10
10 / 10
E4 Evolution II + 30k TT HV
16 / 8
16 / 8
16 / 8
E4 Evolution II + 40k TT HV
16 / 6
16 / 6
16 / 6
E4 Evolution II + 60k TT S HV
25 / 4
25 / 4
25 / 4
E4 Evolution II + 80k TT S HV
35 / 2
35 / 2
35 / 2
LV Model
Wiring spec (mm² / AWG)
Input(Ph)
Input(Ph)
Input(Ph)
E4 Evolution II + 10k TT LV
10 / 10
10 / 10
10 / 10
E4 Evolution II + 15k TT LV
16 / 8
16 / 8
16 / 8
E4 Evolution II + 20k TT LV
16 / 6
16 / 6
16 / 6
E4 Evolution II + 30k TT S LV
25 / 4
25 / 4
25 / 4
E4 Evolution II + 40k TT S LV
35 / 2
35 / 2
35 / 2
NOTE 1: The cable for E4 Evolution II + 10k TT (S) HV should be able to withstand over 20A current.
It is recommended to use AWG 14 or thicker wire for Phase and AWG10 or thicker wire for Neutral for
safety and efficiency.
NOTE 2: The cable for E4 Evolution II + 15k TT (S) HV should be able to withstand over 30A current.
It is recommended to use AWG 12 or thicker wire for Phase and AWG10 or thicker wire for Neutral for
safety and efficiency.
NOTE 3: The cable for E4 Evolution II + 20k TT (S) HV et E4 Evolution II + 10k TT (S) LV should be
able to withstand over 40A current. It is recommended to use AWG10 or thicker wire for Phase and
AWG 6 or thicker wire for Neutral for safety and efficiency.
NOTE 3: The cable for E4 Evolution II + 30k TT (S) HV or E4 Evolution II 15k TT (S) LV should be
able to withstand over 60A current. It is recommended to use AWG 8 or thicker wire for Phase and
AWG 4 or thicker wire for Neutral for safety and efficiency.
NOTE 4: The cable for for E4 Evolution II + 40k TT (S) HV or E4 Evolution II 20k TT (S) LV should be
able to withstand over 80A current. It is recommended to use 16mm²/AWG 6 for safety and efficiency.
72
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
NOTE 5: The cable for for E4 Evolution II + 60k TT S HV or E4 Evolution II 30k TT (S) LV should be
able to withstand over 120A current. It is recommended to use 25mm²/AWG 4 for safety and
efficiency.
NOTE 6: The cable for E4 Evolution II + 80k TT S HV or E4 Evolution II 40k TT (S) LV should be able
to withstand over 160A current. It is recommended to use 35mm²/AWG 2 for safety and efficiency.
5) Remove the terminal block cover on the rear panel of UPS. Then connect the wires according to the
following terminal block diagrams: (Connect the earth wire first when making wire connection. Disconnect
the earth wire last when making wire disconnection!)
Terminal block wiring diagram for E4 Evolution II + 10/15/20k TT (S) HV (standard)
E4 Evolution II + 10k LV (S) HV (standard)
Entrée
Entrée de le
bypass
Terminal block wiring diagram for E4 Evolution II + 10/15/20k TT (S) HV (optional dual input)
E4 Evolution II + 10k TT (S) LV (optional dual input)
73
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Terminal block wiring diagram for E4 Evolution II + 30/40k TT (S) HV
E4 Evolution II + 15/20k TT (S) LV
Terminal block wiring diagram for E4 Evolution II + 60/80k TT S HV
E4 Evolution II + 30/40k TT S LV
74
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
TO UPS BAT+
PBAT
TO UPS BAT N
NBAT
TO UPS BATBattery wires connection schematic
NOTE 1: Make sure that the wires are connected tightly with the terminals.
NOTE 2: Please install the output breaker between the output terminal and the load, and the breaker
should be qualified with leakage current protective function if necessary.
6)
Put the terminal block cover back to the rear panel of the UPS.
Warning: (Only for standard model)
Make sure the UPS is not turned on before installation. The UPS should not be turned on during wiring
connection.
Do not try to modify the standard model to the long-run model. Particularly, do not try to connect the
standard internal battery to the external battery. The battery type, voltage and numbers may be
different. If you connect them together, it maybe causes the hazard of electric shock or fire!
Warning: (Only for long-run model)
Make sure a DC breaker or other protection device between UPS and external battery pack is installed.
If not, please install it carefully. Switch off the battery breaker before installation.
NOTE: Set the battery pack breaker in “OFF” position and then install the battery pack.
Pay highly attention to the rated battery voltage marked on the rear panel. If you want to change the
numbers of the battery pack, please make sure you modify the setting simultaneously. The connection
with wrong battery voltage may cause permanent damage of the UPS. Make sure the voltage of the
battery pack is correct.
Pay highly attention to the polarity marking on external battery terminal block, and make sure the
correct battery polarity is connected. Wrong connection may cause permanent damage of the UPS.
Make sure the protective earth ground wiring is correct. The current spec, color, position, connection
and conductance reliability of wire should be checked carefully.
2-4. UPS Installation for Parallel System
If the UPS is only available for single operation, you may skip this section to the next.
1)
Install and wire the UPSs according to the section 2-3.
2)
Connect the output wires of each UPS to an output breaker.
75
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
3) Connect all output breakers to a major output breaker. Then this major output breaker will directly
connect to the loads.
4)
Either common battery packs or independent battery packs for each UPS are allowed.
5)
Refer to the following wiring diagram:
Wiring diagram of parallel system for E4 Evolution II + 10/15/20k TT (S) HV (standard)
E4 Evolution II + 10k TT (S) LV (standard)
Wiring diagram of parallel system for E4 Evolution II + 10/15/20k TT (S) HV (optional dual
input)
E4 Evolution II + 10k TT (S) LV (optional dual input)
76
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Wiring diagram of parallel system for E4 Evolution II + 30/40k TT (S) HV
E4 Evolution II + 15/20k TT (S) LV
Wiring diagram of parallel system for E4 Evolution II + 60/80k TT S HV
E4 Evolution II + 30/40k TT LV
2-5. Software Installation
For optimal computer system protection, install the UPS monitoring software to fully configure UPS
shutdown.
77
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Communication ports:
USB port
RS-232 port
Intelligent slot
To allow for unattended UPS shutdown/start-up and status monitoring, connect one end of the
communication cable to the USB/RS-232 port and the other to the communication port of your PC. With the
monitoring software installed, you can schedule UPS shutdown/start-up and monitor UPS status on your
PC.
The UPS is equipped with an intelligent slot, ideal for either an SNMP or AS400 card. When installing either
an SNMP or AS400 card in the UPS, it will provide advanced communication and monitoring options.
Note: A USB port and RS-232 port cannot work at the same time.
3. Operations
LCD Panel
Indicators
Buttons
Diagram 11: Indicators and LCD Panel
3-1. Button Operation
Button
Function
ON/Enter Button
Switch on the UPS: Press and hold the button more than 1s to switch on the
UPS.
Enter Key: Press this button to confirm the selection in the setting menu.
OFF/ESC Button
Turn off the UPS: Press and hold the button more than 2s to turn off the UPS.
Esc key: Press this button to return to last menu in the setting menu.
Test/Up Button
Battery test: Press and hold the button more than 1s to test the battery while in
AC mode, or CVCF mode.
UP key: Press this button to display next selection in the setting menu.
Mute/Down Button
Mute the alarm: Press and hold the button more than 1s to mute the buzzer.
Please refer to section 3-4-8 for details.
Down key: Press this button to display previous selection in the setting menu.
78
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Test/Up +
Mute/Down Button
Press and hold the two buttons simultaneously more than 1s to enter/exit the
setting menu.
* AC mode means normal mode, CVCF mode means frequency converter mode.
3-2. LED Indicators and LCD Panel
LED Indicators:
There are 4 LEDs on the front panel to show the UPS working status:
Mode
LED
Bypass
Line
Battery
Fault
●
○
○
○
●
○
●
○
○
●
○
○
○
○
○
○
○
●
●
●
No Output mode
○
○
Bypass mode
○
●
AC mode
○
●
Battery mode
○
○
CVCF mode
○
●
Battery Test
●
●
ECO mode
●
●
Fault
○
○
Note: ● means LED is ON, and ○ means LED is OFF.
UPS On
Diagram 12 : LCD Panel
Display
Function
Backup time information
Indicates backup time in numbers when the UPS is in battery mode
H: hours, M: minutes, S: seconds
Fault information
Indicates that the warning and fault occurs.
Indicates fault codes (listed in details in section 3-8).
Mute operation
79
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Indicates that the UPS alarm is disabled.
Output & Battery voltage information
Indicates output voltage, frequency or battery voltage.
VAC: output voltage, VDC: battery voltage, Hz: frequency
Load information
Indicates the load level: 0-25%, 26-50%, 51-75%, and 76-100%.
Indicates overload.
Indicates that the load or output is short.
Operation mode information
Indicates that the UPS is connected to the mains.
Indicates that the battery is working.
Indicates that the bypass circuit is working.
Indicates the ECO mode is enabled.
Indicates that the Inverter circuit is working.
Indicates that the output is working.
Battery information
Indicates Battery capacity: 0-25%, 26-50%, 51-75%, and 76-100%.
Indicates a battery fault.
Indicates low battery level and low battery voltage.
Input & Battery voltage information
Indicates the input voltage or frequency or battery voltage.
VAC: Input voltage, VDC: battery voltage, Hz: input frequency
80
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
3-3. Audible Alarm
Description
UPS status
Bypass mode
Battery mode
Fault mode
Warning
Overload
Others
Fault
All
Buzzer status
Muted
Beeping once every 2 minutes
Beeping once every 4 seconds
Beeping continuously
Yes
Beeping twice every second
Beeping once every second
No
Beeping continuously
Yes
3-4. Single UPS Operation
1. Switch on the UPS with utility power supply (in AC mode)
1)
Once the power supply has been correctly connected, set the breaker of the battery pack to the
“ON” position (step only available for long-run model). Then set the input breaker to the “ON”
position. The fan is now running and the UPS supplies power to the loads via the bypass. The
UPS is operating in Bypass mode.
NOTE 1: When the UPS is in Bypass mode, the output voltage will be directly supplied by the
utility power after you switch on the input breaker. In Bypass mode, the load is not protected by the
UPS. To protect your valuable devices, you should switch on the UPS. Refer to next step.
2)
Press and hold the “ON” button for 0.5s to switch on the UPS and the buzzer will beep once.
3)
A few seconds later, the UPS will switch to AC mode. If the utility power is unusual, the UPS will
operate in Battery mode without interruption.
NOTE 2: When the UPS is running out battery, it will shut down automatically at Battery mode. When
the utility power is restored, the UPS will auto restart in AC mode.
2. Switch on the UPS without the utility power supply (in Battery mode)
1)
Make sure that the two strings of batteries are connected correctly in order of ”+,GND,-” terminals
and the breaker of the battery pack is at “ON” position (only for long-run model).
2)
Press the “ON” button to set up the power supply for the UPS, UPS will enter to power on mode.
After initialization UPS will enter to No Output mode, then Press and hold the “ON” button for 0.5s
to turn on the UPS, and the buzzer will beep once.
3)
A few seconds later, the UPS will run in Battery mode.
3. Connect devices to UPS
After the UPS is switched on, you can connect devices to the UPS.
81
1)
Switch on the UPS first and then switch on the devices one by one, the LCD panel will display the
total load level.
2)
If it is necessary to connect the inductive loads such as a printer, the in-rush current of the load
should be calculated carefully to see if it meets the overload capability of the UPS. Any load more
than 150% over designed capacity the runtime will be less than 60ms
3)
If the UPS is in overload, the buzzer will beep twice every second.
4)
If the UPS is in overload, please remove some loads immediately. It is recommended to have the
total loads connected to the UPS totaling less than 80% of its nominal power capacity to prevent
overloads for system safety.
5)
If the overload time is over the acceptable time listed in the specs in AC mode, the UPS will
automatically switch to Bypass mode. After the overload is removed, it will return to AC mode. If
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
the overload time is over the acceptable time listed in spec in Battery mode, the UPS will display
the fault status. Then if the Bypass is enabled, the UPS will supply power to the load through
bypass. If the bypass function is disabled or the input power is not within the acceptable bypass
range, the output will be cut off directly.
4. Charge the batteries
1)
Once the UPS has been connected to the utility power, the charger will charge the batteries
automatically except in Battery mode or during the battery self-test, overload or when the battery
voltage is high.
2)
Charging batteries for at least 10 hours before use is recommended. Otherwise, the backup time
may be shorter than expected.
3)
Make sure the battery numbers setting on the control board (Please refer to the section 3-4-13 for
detailed setting) is consistent with the actual connection.
5. Battery mode operation
1)
When the UPS is in Battery mode, the buzzer will beep according to different battery capacities. If
the battery capacity is more than 25%, the buzzer will beep once every 4 seconds; If the battery
voltage drops to the alarm level, the buzzer will beep quickly (once every sec) to remind users that
the battery is at a low level and that the UPS is about to automatically shut down. Users can switch
off some non-critical loads to disable the shutdown alarm and prolong the backup time. If there is
no more load to be switched off, you have to shut down all loads as soon as possible to protect the
devices from load failure and/or data loss.
2)
In Battery mode, users can press the Mute button to disable the buzzing sound.
3)
The backup time of the long-run model depends on the external batteries’ capacity.
4)
The backup time may vary with different environment temperatures and load types.
5)
When setting backup time for 16.5 hours (default value from LCD panel: 999min), after
discharging 16.5 hours, UPS will shut down automatically to protect the battery. This battery
discharge protection can be enabled or disabled using the LCD panel control. (Refer to 3-7 LCD
setting section)
6. Battery test
1) If you need to check the battery status when the UPS is running in AC mode/CVCF mode, you
could press the “Test” button to let the UPS do battery self-test.
2) Users also can set battery self-test through monitoring software.
7. Turn off the UPS with the utility power supply in AC mode
1) Turn off the UPS inverter by pressing the “OFF” button for at least 0.5s. The buzzer will beep once
and the UPS will switch to Bypass mode.
NOTE 1: If the UPS has been set to enable the bypass output, it will bypass voltage from the utility
power to the output sockets and terminal even though the UPS is switched off (inverter).
NOTE 2: After turning off the UPS, please be aware that the UPS is working in Bypass mode and
that there is risk of power loss for connected devices.
2)
82
In Bypass mode, output voltage from the UPS is still present. In order to cut off the output, switch
off the input breaker. A few seconds later, there is no display shown on the display panel and UPS
is completely off.
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
8. Turn off the UPS without the utility power supply in Battery mode
1)
Turn off the UPS by pressing the “OFF” button for at least 0.5s. The buzzer will beep once.
2)
Then the UPS cuts off the power to the output and there is no display shown on the display panel.
9. Mute the buzzer
1)
To mute the buzzer, please press the “Mute” button for at least 0.5s. If you press it again after the
buzzer is muted, the buzzer will beep again.
2)
Some warning alarms cannot be muted unless the error is fixed.
10. Operation in warning status
1)
When the Fault LED flashes and the buzzer beeps once every second, there are some problems
in the UPS operation. Users can see the fault code on the LCD panel. Please check the trouble
shooting table in chapter 4 for details.
2)
Some warning alarms cannot be muted unless the error is fixed. Please refer to section 3-3 for
details.
11. Operation in Fault mode
1)
When Fault LED illuminates and the buzzer beeps continuously, it means that there is a fatal error
with the UPS. Users can get the fault code from LCD menu. Please refer to the Chapter 4 for
details.
2)
Please check the loads, wiring, ventilation, mains, battery and so on after the fault occurs. Don’t try
to turn on the UPS again before solving the issues. If the problems persist, contact the distributor
or service personnel immediately.
3)
In case of an emergency, shut off connections from mains, external battery, and output
immediately to avoid possible damage to the UPS or equipment.
12. Operation in maintenance mode
This operation should only be performed by maintenance personnel or qualified technicians.
When the UPS needs to repair or service and the load could not be shut off, the UPS needs to be put into
maintenance mode.
1) First, switch off the UPS.
2) Then, remove the cover of maintenance bypass switch on the panel.
3) Turn the maintenance switch to “BPS” position. Then, turn off the UPS input breaker and output
breaker.
4) Disconnect battery if external
5) UPS will totally off and input voltage will go directly to output terminal.
6) To restart, follow the reserved procedure
13. Operation of setting charging current
1) This operation is only for professional or qualified technicians.
2) Connect communication cable to the UPS and a computer. Be sure to install communication tool first.
For this software tool, please check your local dealer for the details. Use the software to set up charging
current accordingly.
1) After the settings are updated successfully, the updated charging current will be effective
immediately.
In order to apply the same setting charging current the next time, turn off the UPS with battery
connected to save the change.
83
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
14. Operation of setting the charger numbers
1) This operation is only for professional or qualified technicians.
2) Turn off the UPS. If the load cannot be cut, remove the cover of maintenance bypass switch on the
rear panel and turn the maintenance switch to the “BPS” position first.
3) Switch off the line input breaker and the UPS will enter in “No Output mode”.
4) Connect the communication cable from the UPS to the computer. Enter the software to set the
charger numbers carefully.
5) After the settings are updated successfully, shut the UPS down with the batteries connected to save
the change. Then, modify the connected charger numbers.
6) Switch on the line input breaker and the external bypass input breaker. Then, the UPS will enter
in bypass mode. If the UPS is in maintenance bypass mode, turn the maintenance switch to the “UPS”
position and then switch the UPS on.
NOTE: The charger number setting must be the same as the actual number in the UPS. If the setting
number is different than the actual number, the charging current cannot meet the specification.
3-5. Parallel Operation
1. Parallel system initial startup
First of all, make sure all of UPSs have the same configuration.
1)
Turn on each UPS to AC mode respectively (Refer to section 3-4(1)). Then, measure the inverter
output voltage of each phase for each UPS with a multimeter. Please calibrate the inverter output
voltage by configuring inverter voltage adjustment (Refer to Program 15, 16 and 17, section 3-7) in
LCD setting until the output voltage difference of each UPS is within 1V. If voltage difference is
less than 1V, it’s ok to start parallel operation.
2)
Calibrate the output voltage measurement by configuring output voltage calibration(Refer to
Program 18,19, and 20, section 3-7) in LCD setting to make sure the difference between real
output voltage and detected value of UPS is less than 1V.
3)
Turn off each UPS (Refer to section 3-4(7.)). Then, follow the wiring procedure in section 2-4.
4)
Remove the cover of parallel share current cable port on the UPS, connect each UPS one by one
with the parallel cable and share current cable, and then screw the cover back.
5)
Turn on the parallel system in AC mode:
6)
a)
Turn on the line input breaker of each UPS. If using dual-input unit, please also turn on the
external bypass input breaker. After all UPSs enter to bypass mode, measure the output
voltage between two UPSs for the same phase to make sure the phase sequence is correct. If
these two voltage differences are near to zero, that means all connections are correct.
Otherwise, please check if the wirings are connected correctly.
b)
Turn on the output breaker of each UPS.
c)
Turn on each UPS in turns. After a while, the UPSs will enter to AC mode synchronously and
then, the parallel system is completed.
Turn on the parallel system in Battery mode:
a)
Turn on the battery breaker (only available in long-run model) and external output breaker of
each UPS.
b)
Turn on any UPS. A few seconds later, the UPS will enter to battery mode.
c)
Then, turn on another UPS. A few seconds later, the UPS will enter to battery mode and add
to the parallel system.
d)
If you have the third UPS, follow the same procedure of c). Then, the parallel system is
complete.
If more detailed information is needed, please contact supplier or service center for parallel
operation instruction.
84
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
2. Add one new unit into the parallel system
1)
You cannot add one new unit into the parallel system when whole system is running. You must cut
off the load and shutdown the system.
2)
Make sure all of the UPS are the parallel models, and follow the wiring refer to section 2-4.
3)
Install the new parallel system refers to the previous section.
3. Remove one unit from the parallel system
There are two methods to remove one unit from the parallel system:
First method:
4) Press the “OFF” key twice and each time should be lasted for more than 0.5s. Then, the UPS will
enter into bypass mode or no output mode without output.
5) Turn off the external output breaker of this unit, and then turn off the input breaker of this unit.
6) After it shuts down, you can turn off the battery breaker (for long-run model) and remove the
parallel and share current cables. And then remove the unit from the parallel system.
Second method:
6) If the bypass is abnormal, you can not remove the UPS without interruption. You must cut off the
load and shut down the system first.
7) Make sure the bypass setting is enabled in each UPS and then turn off the running system. All
UPSs will transfer to Bypass mode. Remove all the maintenance bypass covers and set the
maintenance switches from “UPS” to “BPS”. Turn off all the input breakers and battery breakers in
parallel system.
8) Turn off the output breaker and remove the parallel cable and share current cable of the UPS which
you want to remove. Then, remove it from parallel system.
9) Turn on the input breaker of the remaining UPS and the system will transfer to Bypass mode. Set
the maintenance switches from “BPS” to “UPS and put the maintenance bypass covers back.
10) Turn on the remaining UPS according to the previous section.
Warning: (Only for the parallel system)
●
Before turning on the parallel system to activate inverter, make sure that all unit’s maintenance
switch at the same position.
●
When parallel system is turned on to work through inverter, please do not operate the maintenance
switch of any unit.
●
If applying for parallel system, ECO mode is not supported. Therefore, please DO NOT “enable”
ECO mode in any unit.
3-6. Meaning of the abbreviations on the LCD Display
Abbreviation
Display content
Meaning
ENA
Enable
DIS
Disable
ATO
Auto
BAT
Battery
NCF
Normal mode (not CVCF mode)
CF
CVCF mode (frequency converter mode)
SUB
Subtract
ADD
Add
ON
On
85
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
OFF
Off
FBD
Not allowed
OPN
Allow
RES
Reserved
N.L
Neutral line loss
CHE
Check
OP.V
Output voltage
PAR
Parallel, 001 means the first UPS
AN
The first phase
BN
The second phase
CN
The third phase
AB
The first line
BC
The second line
CA
The third line
HS.H
Hot Standby
86
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
3-7. LCD Setting
There are three parameters to set up the UPS. Refer to diagram 13.
Parameter 1
Parameter 1 is for program alternatives. There
are 20 programs to set up. Refer to the table
below.
Parameter 2 and parameter 3 are the setting
options or values for each program.
NOTE: Select “Up” or “Down” buttons to
change the programs or parameters.
Parameter 2
Parameter 3
Diagram 13 : LCD Settings
List of 20 programs available for parameter 1:
Bypass
AC
Eco
CVCF
Battery
Y
Y
Y
Battery
Code
Description
01
Output voltage
Y*
02
Output frequency
Y
03
Voltage range for bypass
Y
04
Frequency range for bypass
Y
05
ECO mode enable/disable
Y
06
Voltage range for ECO mode
Y
07
Frequency range for ECO mode
Y
08
Bypass mode setting
Y
Y
09
Maximum battery discharge time setting
Y
Y
10
Reserved
11
Hot standby function Setting
Y
12
Neutral loss detection
Y
Y
Y
Y
Y
Y
13
Battery voltage calibration
Y
Y
Y
Y
Y
Y
14
Charger voltage adjustment
Y
Y
Y
Y
Y
Y
15
Inverter A voltage adjustment
Y
Y
Y
16
Inverter B voltage adjustment
Y
Y
Y
17
Inverter C voltage adjustment
Y
Y
Y
18
Output A voltage calibration
Y
Y
Y
19
Output B voltage calibration
Y
Y
Y
Y
Y
Y
Test
Y
Reserved for future options
20
Output C voltage calibration
*Y (YES) means that this program can be set in this mode.
NOTE: All parameter settings will be saved only when UPS shuts down normally with internal or external
battery connection. (Normal UPS shutdown means turning off input breaker in bypass/no output mode).
87
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
01: Output voltage
Interface
02: Output frequency
Interface
60 Hz, CVCF mode
50 Hz, Normal mode
ATO
03: Voltage range for bypass
Interface
Setting
Parameter 3: Output voltage
For 208/220/230/240 VAC models, choose the following output
voltage:
208: output voltage is 208Vac
220: output voltage is 220Vac
230: output voltage is 230Vac
240: output voltage is 240Vac
For 120/127 VAC models, choose the following output voltage:
120: output voltage is 120Vac
127: output voltage is 127Vac
Setting
Parameter 2: Output Frequency
Setting the output frequency. Choose between three options in
parameter 2:
50.0Hz: The output frequency is set for 50.0Hz.
60.0Hz: The output frequency is set for 60.0Hz.
ATO: If selected, the output frequency will be decided according
to the latest normal utility frequency. If it is from 46Hz to 54Hz, the
output frequency will be 50.0Hz. If it is from 56Hz to 64Hz, the
output frequency will be 60.0Hz. ATO is the default setting.
Parameter 3: Frequency mode
Setting output frequency at CVCF mode or not CVCF mode. You
may choose following two options in parameter 3:
CF: Setting UPS to CVCF mode. If selected, the output frequency
will be fixed at 50Hz or 60Hz according to setting in parameter 2.
The input frequency could be from 46Hz to 64Hz.
NCF: Setting UPS to normal mode (not CVCF mode). If selected,
the output frequency will synchronize with the input frequency
within 46~54 Hz at 50Hz or within 56~64 Hz at 60Hz according to
setting in parameter 2. If 50 Hz selected in parameter 2, UPS will
transfer to battery mode when input frequency is not within 46~54
Hz. If 60Hz selected in parameter 2, UPS will transfer to battery
mode when input frequency is not within 56~64 Hz.
*If Parameter 2 is ATO, the Parameter 3 will show the current
frequency.
Setting
Parameter 2: Set the acceptable low voltage for bypass.
For 208/220/230/240 VAC models, setting range is from 176V to
209V and the default value is 176V.
For 120/127 VAC models, setting range is from 96V to 88V and the
default value is 96V.
Parameter 3: Set the acceptable high voltage for bypass.
For 208/220/230/240 VAC models, setting range is from 231V to
276V and the default value is 264V.
For 120/127 VAC models, setting range is from 146V to 156V and
the default value is 146V.
04: Frequency range for bypass
Interface
Setting
88
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Parameter 2: Set the acceptable low frequency for bypass.
50 Hz system: Setting range is from 46.0Hz to 49.0Hz.
60 Hz system: Setting range is from 56.0Hz to 59.0Hz.
The default value is 46.0Hz/56.0Hz.
Parameter 3: Set the acceptable high frequency for bypass.
50 Hz: Setting range is from 51.0Hz to 54.0 Hz.
60 Hz: Setting range is from 61.0Hz to 64.0Hz.
The default value is 54.0Hz/64.0Hz.
05: ECO mode enable/disable
Interface
Setting
Parameter 3: Enable or disable ECO function. You may choose
following two options:
DIS: disable ECO function
ENA: enable ECO function
If ECO function is disabled, voltage range and frequency range
for ECO mode still can be set, but it is meaningless unless the
ECO function is enabled.
*If the system is running in parallel, be sure to set “DIS” only.
06: Voltage range for ECO mode
Interface
Setting
Parameter 2: Low voltage point in ECO mode. The setting range
is from -5% to -10% of the nominal voltage.
Parameter 3: High voltage point in ECO mode. The setting range
is from +5% to +10% of the nominal voltage.
07: Frequency range for ECO mode
Interface
Setting
Parameter 2: Set low voltage point for ECO mode.
50 Hz system: Setting range is from 46.0Hz to 48.0Hz.
60 Hz system: Setting range is from 56.0Hz to 58.0Hz.
The default value is 48.0Hz/58.0Hz.
Parameter 3: Set high voltage point for ECO mode.
50 Hz: Setting range is from 52.0Hz to 54.0 Hz.
60 Hz: Setting range is from 62.0Hz to 64.0Hz.
The default value is 52.0Hz/62.0Hz.
08: Bypass mode setting
Interface
09: Maximum battery discharge time setting
Interface
89
Setting
Parameter 2:
OPN: Bypass allowed. When selected, UPS will run at Bypass
mode depending on bypass enabled/disabled setting.
FBD: Bypass not allowed. When selected, it’s not allowed for
running in Bypass mode under any situations.
Parameter 3:
ENA: Bypass enabled. When selected, Bypass mode is activated.
DIS: Bypass disabled. When selected, automatic bypass is
acceptable, but manual bypass is not allowed. Manual bypass
means users manually operate UPS for Bypass mode. For
example, pressing OFF button in AC mode to turn into Bypass
mode.
Setting
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Parameter 3:
000~999: Set the maximum discharge time from 0 min to 999
min. UPS will shut down to protect battery if the discharge time
arrives before the battery is under voltage. The default value is
990 min.
DIS: Disable battery discharge protection and backup time will
depend on battery capacity.
10: Reserved
Interface
11: Hot standby function Setting
Interface
Setting
Parameter 2:
N.L: Indicates neutral loss detection function.
Parameter 3:
DIS: Disable the neutral loss detection function. The UPS will not
detect the neutral loss or not.
ATO: The UPS will automatically detect the neutral is lost or not. If
neutral loss is detected, an alarm will be generated. If the UPS is
turned on, it will transfer to battery mode. When neutral is
restored and detected, the alarm will be muted automatically and
the UPS will go back to normal mode automatically.
CHE: The UPS will automatically detect the neutral loss. If neutral
loss is detected, an alarm will be generated. If the UPS is turned
on, it will transfer to battery mode. When neutral is restored, the
alarm will NOT be muted automatically and the UPS will NOT go
back to normal mode automatically.
Here, you must mute the alarm and make the UPS go back to
normal mode manually. The operation is: Firstly, enter this menu
and press the “Enter” key to make the “CHE” flash. Secondly,
press the “Enter” key again to activate the neutral detection
(check). If neutral is detected, the alarm will be muted and the
UPS will go back to normal mode. If neutral is not detected, the
UPS will continue alarming and stay on the latest status until the
neutral is detected well at next manual checking operation.
CHE is default setting.
13: Battery voltage calibration
Interface
90
Setting
Parameter 2:
HS.H: Indicates Hot standby function.
Parameter 3: Enable or disable hot standby function.
YES: Hot standby function is enabled. It means that the current
UPS is set to host of the hot standby function, and it will restart
After AC recovery even without battery connected.
NO: Hot standby function is disabled. The UPS is running at
Normal mode and can’t restart without battery.
12: Neutral loss detection
Interface
Setting
Reserve for future options.
Setting
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Parameter 2: Select “Add” or “Sub” function to adjust battery
voltage to real figure.
Parameter 3: the voltage range is from 0V to 9.9V and the default
value is 0V.
14: Charger voltage adjustment
Interface
15: Inverter A voltage adjustment
Interface
Setting
Parameter 2: you may choose Add or Sub to adjust charger
voltage
Parameter 3: the voltage range is from 0V to 9.9V and the default
value is 0V.
NOTE:
*Before making voltage adjustment, be sure to disconnect all
batteries first to get the accurate charger voltage.
* Any modification should be suitable to battery specifications.
Setting
Parameter 2: you may choose Add or Sub to adjust inverter A
voltage.
Parameter 3: the voltage range is from 0V to 9.9V and the default
value is 0V.
* Add or Sub is according to the output voltage what you set.
16: Inverter B voltage adjustment
Interface
Setting
Parameter 2: you may choose Add or Sub to adjust inverter B
voltage*.
Parameter 3: the voltage range is from 0V to 9.9V and the default
value is 0V.
*It will display number 1 under
inverter B voltage.
Setting
Parameter 2: you may choose Add or Sub to adjust inverter C
voltage*.
Parameter 3: the voltage range is from 0V to 9.9V, the default
value is 0V.
*It will display number 2 under
inverter C voltage.
or
to represent
18: Output A voltage calibration
Interface
91
to represent
17: Inverter C voltage adjustment
Interface
or
Setting
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Parameter 2: it always shows OP.V as output voltage.
Parameter 3: it shows the internal measurement value of the
output A voltage, and you can calibrate it by pressing Up or Down
according to the measurement from an external voltage meter.
The calibration result will be effective by pressing Enter. The
calibration range is limited within +/-9V. This function is normally
used for parallel operation.
19: Output B voltage calibration
Interface
Setting
Parameter 2: it always shows OP.V as output voltage*.
Parameter 3: it shows the internal measurement value of the
output B voltage, and you can calibrate it by pressing Up or Down
according to the measurement from an external voltage meter.
The calibration result will be effective by pressing Enter. The
calibration range is limited within +/-9V. This function is normally
used for parallel operation.
*It will display number 1 under
voltage.
to represent the output B
20: Output C voltage calibration
Interface
Setting
Parameter 2: it always shows OP.V as output voltage.
Parameter 3: it shows the internal measurement value of the
output C voltage, and you can calibrate it by pressing Up or Down
according to the measurement from an external voltage meter.
The calibration result will be effective by pressing Enter. The
calibration range is limited within +/-9V. This function is normally
used for parallel operation.
*It will display number 2 under
voltage.
to represent the output C
3-8. Operating Mode/Status Description
Following table shows LCD display for operating modes and status.
(1) If the UPS is in normal operation, it will show seven screens one by one, which represents 3 phase input
voltages (An, bn, Cn), 3 line input voltages (Ab, bC, CA) and frequency in turns.
(2) If parallel UPS systems are successfully set up, it will show one more screen with “PAR” in parameter 2
and assigned number in parameter 3 as below parallel screen diagram. The master UPS will be default
assigned as “001” and slave UPSs will be assigned as either “002” or “003”. The assigned numbers may be
changed dynamically in the operation;
Parallel screen
Operating mode/status
UPS
On
92
Power
Description
When UPS is powered on, it will enter into this mode for a few seconds as
initializing the CPU and system.
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
LCD display
No-output
description
mode
When bypass voltage/frequency is out of acceptable range or bypass is
disabled (or forbidden), UPS will enter into no-output mode if powering on
or turning off the UPS. It means the UPS has no output. Alarm beeps every
two minutes.
LCD display
AC mode
Description
When the input voltage is within acceptable range, UPS will provide pure
and stable AC power to output. The UPS will also charge the battery at AC
mode.
LCD display
93
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
ECO mode
Description
When the input voltage is within voltage regulation range and ECO mode is
enabled, UPS will bypass voltage to output for energy saving.
LCD display
CVCF mode
Description
When the output frequency is set to “CF”, the inverter will output constant
frequency (50 Hz or 60 Hz). At this mode, the UPS will have no bypass
output but still charge battery.
LCD display
94
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Battery mode
Description
When the input voltage/frequency is beyond the acceptable range or power
failure, UPS will backup power from battery and alarm will beep every 4
seconds.
LCD display
Bypass mode
Description
When input voltage is within acceptable range and bypass is enabled, turn
off the UPS and it will enter Bypass mode. Alarm beeps every two minutes.
95
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
LCD display
Battery Test
Description
When UPS is in AC mode or CVCF mode, press “Test” key for more than
0.5s. Then, the UPS will beep once and start “Battery Test”. The line
between I/P and inverter icons will blink to remind users. This operation is
used to check the battery status.
LCD display
96
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Warning
Description
status
If some errors occur in the UPS (but it is still running normally), it will show
one more screen to represent the warning situation. In the warning screen,
the icon
will be flashing, and it can show up to 3 error codes and each
code indicates one error. You can find the code meaning in the warning
code table.
LCD display
Fault status
Description
When UPS has fault happened, the inverter will be blocked. It will display
fault code in screen, and the icon
will light up. You can find the code
meaning in the fault code table.
LCD display
6-1. 3-9. Fault Code
Fault
Icon
Fault
Fault code
Icon
01
Bus start failure
None
42
DSP communication failure
02
Bus over
None
43
Overload
03
Bus under
None
46
Incorrect UPS setting
None
04
Bus unbalance
None
47
MCU communication failure
None
06
Converter over current
None
48
None
11
Inverter soft start failure
None
60
Two DSP firmware versions are
incompatible in parallel system.
Bypass phase short circuited
12
High inverter voltage
None
61
Bypass SCR short circuited
None
15
Inverter B output(line to
neutral) short circuited
Inverter C output(line to
neutral) short circuited
62
Bypass SCR open circuited
None
63
Voltage waveform abnormal in R
phase
None
16
97
Fault code
None
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
17
1A
Inverter A-B output (line to
line) short circuited
Inverter B-C output (line to
line) short circuited
Inverter C-A output (line to
line) short circuited
Inverter A negative power fault
66
Voltage waveform abnormal in S
phase
Voltage waveform abnormal in T
phase
Inverter current sample abnormal
None
67
Bypass O/P short circuited
1B
Inverter B negative power fault
None
68
1C
Inverter C negative power fault
None
69
Bypass O/P line to line short
circuited
Inverter SCR short circuited
None
21
Battery SCR short circuited
None
6C
BUS voltage drops too fast
None
Inverter relay open circuited
None
6D
Current sampling error value
None
24
Inverter relay short circuited
None
6E
SPS power error
None
25
Line wiring fault
None
6F
Battery polarity reverse
None
31
Parallel communication failure
None
71
PFC IGBT over-current in R phase
None
32
The host signal failure
None
72
PFC IGBT over-current in S phase
None
33
Synchronous signal failure
None
73
PFC IGBT over-current in T phase
None
34
Synchronous trigger signal
failure
Parallel communication loss
None
74
INV IGBT over-current in R phase
None
None
75
INV IGBT over-current in S phase
None
Parallel output current
unbalance
Over temperature
None
76
INV IGBT over-current in T phase
None
18
19
23
35
36
41
64
65
None
None
None
None
3-10. Warning Indicator: Icon flashing
Warning
Icon (flashing)
Alarm
Warning Code
Battery low
Beeping every second
Battery low
Overload
Beeping twice every second
Overload
Battery unconnected
Beeping every second
Battery disconnected
Over charge
Beeping every second
Over charge
EPO enable
Beeping every second
EPO enable
Fan failure / Overheating
Beeping every second
Fan failure / Overheating
Charger failure
Beeping every second
Charger failure
I/P fuse broken
Beeping every second
I/P fuse broken
Other warnings (refer to
3-11)
Beeping every second
Other warnings (refer to
3-11)
3-11.Warning Code
Warning code
98
Warning event
Warning code
01
Battery unconnected
21
02
IP Neutral loss
22
Warning event
Line situations are different in
parallel system
Bypass situations are different in
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
parallel system
04
IP phase abnormal
33
05
Bypass phase abnormal
34
Locked in bypass after overload 3
times in 30 minutes
Converter current unbalanced
07
Over charge
3A
Cover of maintain switch is open
08
Low battery
3C
Utility extremely unbalanced
09
Overload
3D
Bypass is unstable
0A
Fan failure
3E
Battery voltage too high
0B
EPO enable
3F
Battery voltage unbalanced
0D
Over temperature
40
Charger short circuited
0E
Charger failure
4. Trouble Shooting
If the UPS system does not operate correctly, please solve the problem by using the table below.
Symptom
Possible cause
Remedy
No indication and alarm in the front
display panel even though the mains is
normal.
The AC input power is not
connected well.
Check if input cable firmly
connected to the mains.
flash on LCD display and alarm
beeps every second.
EPO function is activated. At
this time, the EPO switch is in
“OFF” status or the jumper is
open.
Set the circuit in closed
position to disable the EPO
function.
The icon
and
flash on
LCD display and alarm beeps every
second.
The external
battery
is
connected.
Check if all batteries
connected well.
The icon
and the warning code
The icon
and
flash on
LCD display and alarm beeps twice
every second.
Fault code is shown as 43. The icon
lights on LCD display and
alarm beeps continuously.
Fault code is shown as 14, 15, 16, 17,
18 or 19, the icon
LCD display, and
continuously.
lights on
alarm beeps
Other fault codes are shown on LCD
display and alarm beeps continuously.
99
or
internal
incorrectly
are
UPS is overload.
Remove excess loads from UPS
output.
UPS is overloaded. Devices
connected to the UPS are fed
directly by the electrical
network via the Bypass.
Remove excess loads from UPS
output.
After repetitive overloads, the
UPS is locked in the Bypass
mode. Connected devices are
fed directly by the mains.
Remove excess loads from UPS
output first. Then shut down
the UPS and restart it.
UPS is overload too long and
becomes fault. Then UPS shut
down automatically.
Remove excess loads from UPS
output and restart it.
The
UPS
shut
down
automatically because short
circuit occurs on the UPS
output.
Check output wiring and if
connected devices are in short
circuit status.
A UPS internal
occurred.
Contact your dealer
fault
has
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Battery backup time is shorter than
nominal value
The icon
and
flash on LCD
display and alarm beeps every second.
The warning code 02 and the icon
flash on LCD display. The alarm
beeps every second.
Batteries are not fully charged
Charge the batteries for at
least 7 hours and then check
capacity. If the problem still
persists, consult your dealer.
Batteries defect
Contact your dealer to replace
the battery.
Fan is locked or not working;
or the UPS temperature is too
high.
Check fans and notify dealer.
The input neutral wire is
disconnected.
Check and correct the input
neutral connection. If the
connection is ok and the alarm
is still displaying, please refer
to the LCD setting section, to
enter the neutral loss check
menu, to see if the parameter3
is “CHE”, if it is, please press
the “Enter” key firstly to make
the “CHE” flash and press the
“Enter” key secondly to make
the UPS clear the alarm. If the
warning still exists, please
check input fuses of L2 and L3.
The L2 or L3 input fuse is
broken.
Replace the fuse.
5. Storage and Maintenance
5-1. Storage
Before storing, charge the UPS for at least 7 hours. Store the UPS covered and upright in a cool, dry
location. During storage, recharge the battery in accordance with the following table:
Storage Temperature
Recharge Frequency
Charging Duration
From -25°C to 40°C
Every 3 months
1-2 hours
From 40°C to 45°C
Every 2 months
1-2 hours
5-2. Maintenance
The UPS system operates with hazardous voltages. Repairs may only be carried out by qualified
maintenance personnel.
Even after the unit is disconnected from the mains, components inside the UPS system are still
connected to the battery packs which are potentially dangerous.
Before carrying out any kind of service and/or maintenance, disconnect the batteries and check
that no current is present and no hazardous voltage exists in the high capability capacitor terminals such
as BUS-capacitors.
Only persons who are sufficiently familiar with batteries and with the required precautionary
measures may replace batteries and supervise operations. Unauthorized persons must be kept well away
from the batteries.
100
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Check that no voltage between the battery terminals and the ground is present before
maintenance or repair. The battery circuit of this product is not isolated from the input voltage. Hazardous
voltages may occur between the battery terminals and the ground.
Batteries may cause electric shock and have a high short-circuit current. Please remove all
wristwatches, rings and other metal personal objects before maintenance or repair, and only use tools
with insulated grips and handles for maintenance and repair work.
When replacing the batteries, install the same number and same type of batteries.
Do not attempt to dispose of batteries by burning them. This could cause an explosion. The
batteries must be deposed of correctly according to local regulations.
Do not open or destroy batteries. Escaping electrolyte can cause injury to the skin and eyes. It
may be toxic.
Please replace the fuse only with the same type and amperage in order to avoid fire hazards.
Do not disassemble the UPS system.
101
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
6. Technical specifications
HV MODEL (400V)
E4
Evolution
II + 10 k
TT (S)
10KVA /
10KW
CAPACITY*
INPUT
Voltage
Range
Low Line Loss
E4
Evolution
II + 15 k
TT (S)
15KVA /
15KW
E4
Evolution
II + 60 k
TT S
60KVA /
60KW
E4
Evolution
II + 80 k TT
S
80KVA /
80KW
300 VAC(L-N) ± 3 % at 50% Load; 276 VAC(L-N) ± 3 % at 100% Load
High Line Loss Voltage - 10V
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
3 Phase with Neutral
≧ 0.99 at 100% Load
3 Phase with Neutral
Output voltage
360/380/400/415VAC (Ph-Ph)
208*/220/230/240VAC (Ph-N)
± 1%
AC Voltage Regulation
Frequency Range
(Synchronized Range)
Frequency Range (Batt. Mode)
Over
AC mode
load
Battery mode
Current Crest Ratio
Harmonic Distortion
Transfer
Line
Battery
Time
Inverter
Bypass
Inverter
ECO
EFFICIENCY
AC mode
Battery Mode
BATTERY
Standard Type
Model
Numbers
Recharge Time
Charging Current
(max)
Charging Voltage
102
E4
Evolution
II + 40 k
TT (S)
40KVA /
40KW
Low Line Loss Voltage + 10V
Phase
Power Factor
OUTPUT
Phase
Type
Numbers
Charging
Current(max.)
Charging Voltage
PHYSICAL
Standard Dimension,
Model
X H (mm)
Net Weight
Long-run Dimension,
Model
X H mm
Net Weight
ENVIRONMENT
Operation Temperature
Operation Humidity
Operation Altitude**
E4
Evolution
II + 30 k
TT (S)
30KVA /
30KW
110 VAC(Ph-N) ± 3 % at 50% Load; 176 VAC(Ph-N) ± 3 % at 100% Load
Low Line
Comeback
High Line Loss
High Line
Comeback
Frequency Range
Long-run
Model
E4
Evolution
II + 20 k
TT (S)
20KVA /
20KW
46Hz ~ 54 Hz @ 50Hz system;
56Hz ~ 64 Hz @ 60Hz system
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
100%~110%: 60min; 110%~125%: 10min; 125%~150%:1min;>150% : immediately
100%~110%: 60min; 110%~125%: 10min; 125%~150%:1min;>150% : immediately
3:1 max
≦ 2 % @ 100% Linear Load; ≦ 5 % @ 100% Non-linear Load
0 ms
0 ms (When phase lock fails, <4ms interruption occurs from inverter to bypass)
<10 ms
95.5%
94.5%
12 V / 7 Ah
20 (10+10)
+/-136.5
VDC ± 1%
20
12 V / 9 Ah 12 V / 9 Ah 12 V / 7 Ah 12 V / 9 Ah
32 (16+16) 32 (16+16)
(16+16)pcs x 2 strings
9 hours recover to 90% capacity
2.0 A ± 10% (Recommended)
1.0~12.0A (Adjustable)
+/-218 VDC ± 1%
Depending on applications
32 ~ 40 (adjustable)
1.0~12.0A ±10% (Adjustable)
+/-136.5
VDC ± 1%
DXW
124/126
(kgs)
28/30
2.0~24.0A ±10%
(Adjustable)
+/- 13.65 VDC * N ± 1% (N = 16~20)
626 x 250 x 750
(kgs)
DXW
N/A
139/141
139/141
626 x 250 x 750
43/45
43/45
815 x 300 x 1000
N/A
225/230
250/260
815 x 300 x 1000
790 x 360 x 1010
60/65
61/71
108/112
113/117
0 ~ 40°C (the battery life will down when > 25°C)
<95 % and non-condensing
<1000m**
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Acoustic Noise Level
MANAGEMENT
Smart RS-232 or USB
Optional SNMP
Less than
55dB @ 1
Meter
Less than 58dB @ 1 Meter
Less than
65dB @1
Meter
Less than
70dB @ 1
Meter
Less than
70dB @ 1
Meter
Less than
75dB @ 1
Meter
Supports Windows® 2000/2003/XP/Vista/2008/7/8/10, Linux, Unix, and MAC
Power management from SNMP (VMWare© compatible) manager and web browser
* Derate capacity to to 90% when the output voltage is adjusted to 208VAC.
**If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated 1% per 100m.
***Product specifications are subject to change without further notice.
103
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
LV MODEL (208V)
CAPACITY*
INPUT
Voltage
Range
E4
Evolution II +
10k TT
(S)
10KVA
10KW
Low Line Loss
E4
Evolution II
+ 15k TT
(S)
15KVA
15KW
E4
Evolution
II + 30k TT
S
30KVA
30KW
E4
Evolution II
+ 40k TT
S
40KVA
40KW
70 VAC(Ph-N) ± 3 % at 50% Load
88 VAC(Ph-N) ± 3 % at 100% Load
Low Line Loss Voltage + 5V
156 VAC(L-N) ± 3 % at 50% Load
146 VAC(L-N) ± 3 % at 100% Load
High Line Loss Voltage - 5V
Low Line Comeback
High Line Loss
High Line
Comeback
Frequency Range
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
3 Phase with Neutral
≧ 0.99 at 100% Load
Phase
Power Factor
OUTPUT
Phase
3 Phase with Neutral
Output voltage
208/220VAC (Ph-Ph)
120/127VAC (Ph-N)
± 1%
AC Voltage Regulation
Frequency Range
(Synchronized Range)
Frequency Range (Batt. Mode)
Overload
AC mode
Battery mode
Current Crest Ratio
Harmonic Distortion
Transfer
Line
Battery
Time
Inverter
Bypass
Inverter
ECO
EFFICIENCY
AC mode
Battery Mode
BATTERY
Standard
Type
Model
Numbers
Recharge Time
Charging
Current(max.)
Charging Voltage
Long-run
Type
Model
Numbers
Charging
Current(max.)
Charging Voltage
PHYSICAL
Standard
Dimension,
Model
DXWXH
mm
Net Weight (kgs)
Long-run
Dimension,
Model
DXWXH
mm
Net Weight (kgs)
ENVIRONMENT
Operation Temperature
Operation Humidity
Operation Altitude**
104
E4
Evolution II
+ 20k TT
(S)
20KVA
20KW
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
100%~110%: 60min; 110%~125%: 10min; 125%~150%:1min;>150% : immediately
100%~110%: 60min; 110%~125%: 10min; 125%~150%:1min;>150% : immediately
3:1 max
≦ 2 % @ 100% Linear Load; ≦ 4 % @ 100% Non-linear Load (PF≥0.8)
0 ms
0 ms (When phase lock fails, <4ms interruption occurs from inverter to bypass)
<10 ms
93.5%
92.5%
12 V / 9 Ah
12 V / 7 Ah
12 V / 9 Ah
(8+8)pcs
(8+8)pcs x 2 strings
9 hours recover to 90% capacity
1.0~12.0A±10% (Adjustable)
N/A
+/-109 VDC ± 1%
Depending on applications
16 ~ 20 (adjustable)
1.0~12.0A±10% (Adjustable)
2.0~24.0A±10% (Adjustable)
+/- 13.65 VDC * N ± 1% (N = 8~10)
626 x 250 x 750
815 x 300 x
1000
815 x 300 x
1000
139/141
626 x 250 x 750
152
815 x 300 x
1000
117
815 x 300 x
1000
790 x 360 x
1010
790 x 360 x
1010
43/45
60/65
61/71
108/112
113/117
N/A
0 ~ 40°C (the battery life will down when > 25°C)
<95 % and non-condensing
<1000m**
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Acoustic Noise Level
MANAGEMENT
Smart RS-232 or USB
Optional SNMP
Less than 58dB
@ 1 Meter
Less than 65dB
@ 1 Meter
Less than 70dB
@ 1 Meter
Less than
70dB @ 1
Meter
Less than 75dB
@ 1 Meter
Supports Windows® 2000/2003/XP/Vista/2008/7/8/10, Linux, Unix, and MAC
Power management from SNMP (VMWare© compatible) manager and web browser
* If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated 1% per 100m.
**Product specifications are subject to change without further notice.
105
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Versión española
106
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Índice de contenidos
1. INSTRUCCIONES DE SEGURIDAD Y EMC ................................................................................................ 108
1-1. TRANSPORTE Y ALMACENAMIENTO ............................................................................................................ 108
1-2. PREPARACION.......................................................................................................................................... 108
1-3. INSTALACION ............................................................................................................................................ 108
1-4. ADVERTENCIAS ACERCA DE LA CONEXION .................................................................................................. 109
1-5. OPERACION ..............................................................................................................................................110
1-6. MANTENIMIENTO, SERVICIO Y FALLAS .........................................................................................................110
1-7. MANTENIMIENTO, SERVICIO Y FALLAS .........................................................................................................110
1-8. ACERCA DE LAS BATERIAS: ........................................................................................................................ 111
1-9. MARCA DE CONFORMIDAD CE: ................................................................................................................... 111
2. INSTALACION Y OPERACION ..................................................................................................................... 112
2-1. DESEMBALAJE E INSPECCION .....................................................................................................................113
2-2. VISTA DE TERMINAL DE CABLEADO ..............................................................................................................114
2-3. INSTALACION DE UPS SENCILLO ............................................................................................................... 121
2-4. INSTALACION DEL UPS PARA UN SISTEMA PARALELO .................................................................................. 125
2-5. INSTALACION DE SOFTWARE ...................................................................................................................... 128
3. OPERACIONES ............................................................................................................................................. 129
3-1. OPERACION DE LOS BOTONES ................................................................................................................... 129
3-2. INDICADORES LED Y PANEL LCD .............................................................................................................. 130
3-3. ALARMA AUDIBLE ...................................................................................................................................... 132
3-4. OPERACION DEL UPS SENCILLA................................................................................................................ 132
3-5. OPERACION PARALELA ............................................................................................................................. 136
3-6. SIGNIFICADO DE LAS ABREVIATURAS EN LA PANTALLA LCD.......................................................................... 137
3-7. CONFIGURACION DE LCD ......................................................................................................................... 139
3-8. MODO DE FUNCIONAMIENTO/DESCRIPCION DE ESTADO ............................................................................. 145
3-9. CODIGO DE FALLA .................................................................................................................................... 150
3-10. INDICADOR DE ADVERTENCIA: ÍCONO INTERMITENTE
.......................................................................... 151
3-11. CODIGO DE ADVERTENCIA ........................................................................................................................ 152
4. SOLUCION DE PROBLEMAS ...................................................................................................................... 152
5. ALMACENAMIENTO Y MANTENIMIENTO .................................................................................................. 153
5-1. ALMACENAMIENTO ................................................................................................................................... 153
5-2. MANTENIMIENTO ...................................................................................................................................... 154
6. ESPECIFICACIONES TECNICAS ................................................................................................................ 155
107
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
1. Instrucciones de seguridad y EMC
Por favor, siga todas las instrucciones de operación de este manual. Mantenga este
manual en un lugar seguro y lea cuidadosamente las instrucciones antes de instalar la
unidad. Evite operar esta unidad sin haber leído cuidadosamente todas las
advertencias e instrucciones de operación.
¡IMPORTANTE!
Instalar y conectar el sistema UPS sin seguir las prácticas comunes, libera a Infosec Communication de
toda responsabilidad.
1-1. Transporte y almacenamiento
El sistema UPS solo se deberá transportar en su embalaje original, de modo que estará protegido de
golpes e impactos.
Almacene el UPS en una habitación ventilada y seca.
1-2. Preparación
Se puede producir condensación si desplaza al UPS directamente de un entorno frío a uno caliente.
El UPS deberá estar completamente seco antes de su instalación. De modo que el sistema UPS se
aclimatice a su entorno, deje reposar al menos dos horas.
No instale el sistema UPS cerca de agua o en entornos húmedos.
No instale el UPS en u lugar donde esté expuesto a la luz solar directa o cerca de la calefacción.
No bloquee los orificios de ventilación de la carcasa del sistema UPS.
No bloquee los orificios de ventilación de aire de la carcasa del sistema UPS. El sistema
UPS debe instalarse en una ubicación con buena ventilación o con aire acondicionado.
Asegúrese de que exista suficiente espacio en cada lado para contar con una buena
ventilación. En condiciones óptimas, la temperatura de la habitación no deberá exceder
20 °C y un 0 a 90% de humedad sin condensación.
1-3. Instalación
108
No conecte aparatos o dispositivos que pudieran sobrecargar el sistema UPS (por ejemplo: equipos
con motores de gran tamaño) a sus contactos o terminales.
No conecte aparatos domésticos, tales como secadores de cabello, a los contactos del UPS.
Coloque los cables de manera que nadie los pise o se tropiece con ellos.
El sistema UPS le proporciona una terminal con tierra, en la configuración final del sistema con
conexión de tierra de compensación de potencial a los gabinetes de baterías exteriores de sistema
UPS.
Solo personal de mantenimiento calificado deberá realizar la instalación del sistema UPS.
Se deberá dotar a la instalación de cableado del edificio con un dispositivo adecuado de desconexión
para protegerlo contra cortos circuitos.
Se deberá dotar a la instalación de cableado del edificio con un dispositivo interruptor de emergencia
sencillo integral para interrumpir la alimentación de voltaje al sistema UPS, sin importar su modo de
operación.
Antes conectar a la terminal del cableado del edificio conecte la tierra.
La instalación y la conexión del cableado se deberán llevar a cabo de acuerdo con las leyes y normas
eléctricas locales.
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
1-4. Advertencias acerca de la conexión
No existe un estándar de protección contra la retroalimentación en el interior, por favor, aísle el UPS
antes de trabajar de acuerdo con este circuito. El dispositivo de aislamiento deberá ser capaz de
soportar la corriente de entrada del UPS.
Input Rly
Input Rly
Main
Input
L1
Main
Input
L2
UPS
L3
L1
L2
L3
N
Input Rly
N
Bypass
Input
L1
UPS
L2
L3
N
Diagrama de relé de entrada
Diagrama de relé de entrada
E4 Evolution II + 10/15/20k TT HV
E4 Evolution II + 10/15/20k TT HV
E4 Evolution II + 10k TT LV
E4 Evolution II + 10k TT LV
(Entrada doble opcional)
E4 Evolution II + 30/40/60/80k TT HV
E4 Evolution II + 15/20/30/40k TT LV
•
Este UPS debe conectarse con un sistema de conexión de tierra/cable a tierra TN.
•
De acuerdo con la norma de seguridad EN-IEC 62040-1, la instalación se debe proveer con un
sistema de “protección de retroalimentación”, por ejemplo un contactor, el cual, evitará la
presencia de voltaje o energía peligrosa en los suministros de entrada durante una falla
de la red eléctrica (ver figura 24 y siga el diagrama de cableado de “protección de
retroalimentación”, dependiendo si el equipo es de fase simple o trifásica).
•
La fuente de alimentación para esta unidad deberá de ser de clasificación trifásica de acuerdo con el
nombre de la placa del equipo. Además deberá estar conectada a tierra de manera adecuada.
•
No se recomienda el uso de este equipamiento en aplicaciones de soporte vital en las que en caso de
mal funcionamiento puedan causar la falla del equipamiento de soporte vital o afectar
significativamente la seguridad o eficiencia. No utilice este equipamiento en presencia de mezclas de
oxígeno, aire, óxido nitroso y anestésicos inflamables.
•
Conecte la terminal de tierra del módulo de su UPS a una terminal de electrodo conductor.
•
Este es un producto para aplicación comercial e industrial en un entorno secundario. Son necesarias
restricciones de instalación o medidas adicionales para evitar contratiempos.
•
Se deben colocar etiquetas de advertencia en todos los interruptores principales de energía que se
instalen en lugares apartados del dispositivo, para alertar al personal de mantenimiento de la presencia
de un UPS en el circuito. La etiqueta deberá mostrar la siguiente leyenda o su equivalente:
-
109
-
Antes de trabajar en el circuito
Aísle el sistema de alimentación ininterrumpida (UPS)
Luego compruebe que no exista voltaje peligroso entre todas
sus terminales, incluyendo la conexión a tierra de
protección.
Riesgo de retroalimentación de voltaje
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
1-5. Operación
Jamás desconecte el cable conductor de tierra, ya que al hacerlo se anularía la tierra de protección
del sistema UPS y hacia todas las cargas conectadas.
El sistema UPS cuenta con su propio suministro de voltaje interno (baterías). Los contactos de salida
del UPS podrían estar energizados, incluso si el sistema UPS no está conectado a la red eléctrica.
Para desconectar el sistema UPS por completo, presione primero el botón “OFF” (APAGAR) y
después desconéctelo de la red eléctrica.
Asegúrese de evitar que líquidos u objetos extraños entren en el sistema UPS.
1-6. Mantenimiento, servicio y fallas
* Seguridad
IEC/EN 62040-1
* EMI
Emisiones conducidas...............................:IEC/EN 62040-2
Categoría C3
Emisiones radiadas..................................:IEC/EN 62040-2
Categoría C3
*EMS
ESD.........................................................:IEC/EN 61000-4-2
Nivel 4
RS........................................................ ...:IEC/EN 61000-4-3
Nivel 3
EFT.........................................................:IEC/EN 61000-4-4
Nivel 4
SOBRETENSIÓN...................................................:IEC/EN 61000-4-5
Nivel 4
CS...........................................................:IEC/EN 61000-4-6
Nivel 3
Campo magnético de frecuencia de alimentación..............:IEC/EN 61000-4-8
Nivel 4
Señales de frecuencia baja............................:IEC/EN 61000-2-2
Advertencia: Este es un producto para aplicación comercial e industrial en un entorno
secundario. Son necesarias restricciones de instalación o medidas adicionales para evitar
contratiempos.
1-7. Mantenimiento, servicio y fallas
El UPS opera con voltajes peligrosos. La reparaciones solo deben ser llevadas a cabo por personal
de mantenimiento calificado.
Cuidado: Riesgo de descarga eléctrica. Aún si la unidad se encuentra desconectada del
suministro de energía, los componentes en el interior del sistema UPS siguen conectados a
la batería, de modo que están energizados y son peligrosos.
Antes de llevar a cabo cualquier tipo de mantenimiento o servicio, desconecte las baterías y verifique
que no exista corriente ni voltaje a niveles peligrosos en las terminales del condensador de
capacidad, tales como el condensador del bus.
Solo personas con conocimientos o que estén familiarizados con las baterías y que tomen las
medidas precautorias necesarias deberán remplazar las baterías y supervisar las operaciones. El
personal no autorizado deberá mantenerse alejado de las baterías.
Cuidado: Riesgo de descarga eléctrica. El circuito de la batería no se encuentra aislado del voltaje de
entrada. Pueden presentarse voltajes peligrosos entre las terminales de la batería y la tierra. ¡Antes
de entrar en contacto, verifique que no existe voltaje presente!
110
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Al remplazar el fusible, solo hágalo con otro del mismo tipo y amperaje, para evitar riesgos de
incendio.
No desmantele el sistema UPS.
1-8. Acerca de las baterías:
Se recomienda que el cambio de la batería se lleve a cabo por un técnico calificado.
¡No abra o dañe la batería! El electrolito, principalmente ácido sulfúrico, puede ser tóxico y dañino a
la piel y ojos. Si entra en contacto con él, lave las partes del cuerpo efusivamente con agua y limpie
las vestimentas contaminadas.
No lance la batería al fuego. Podría explotar. Debe ser desechada por separado al final de su ciclo de
vida. Consulte la legislación y reglamentos locales.
El UPS cuenta con baterías de gran capacidad. No lo abra para evitar todo riesgo de descarga
eléctrica. Si necesita dar servicio a la batería, o debe remplazarla, por favor póngase en contacto con
el distribuidor.
Todo servicio deberá ser llevado a cabo y supervisado por personal capaz y que tomará las
precauciones necesarias. Mantenga al personal no autorizado lejos de las baterías.
Una batería representa un riesgo de descarga eléctrica y puede causar cortos circuitos. El técnico
calificado deberá seguir las siguientes precauciones:
Quítese los relojes, anillos y demás objetos metálicos de sus manos.
Utilice herramientas con mangos aislados.
Antes de conectar o desconectar las terminales de la batería desconecte la fuente de
carga.
Al remplazar las baterías, use el mismo tipo y número de baterías de plomo-ácido selladas.
1-9. Marca de conformidad CE:
Este logotipo significa que este producto responde a las normativas EMC y LVD (respecto
a la regulación asociada al voltaje de equipo eléctrico y los campos electromagnéticos).
Este es un producto UPS de categoría C3. Este producto podría causar interferencia de
radio en un entorno residencial, situación en la cual el usuario podría necesitar de medidas
adicionales.
Importante
Un dispositivo UPS pertenece a la categoría de equipo electrónico y eléctrico. Al llegar al
final de su ciclo de vida útil, debe ser desechado por separado y de la manera adecuada.
Este símbolo está también presente en las baterías que son provistas con este
dispositivo, lo que significa que también deben ser desechadas en un lugar adecuado al
final de su vida útil.
Póngase en contacto con el centro de residuos peligrosos y reciclaje local para obtener más información
acerca de la forma adecuada de desechar la batería usada.
111
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
2.
Instalación y operación
NOTA: Antes de la instalación, realice una inspección. Asegúrese de que nada en el interior del paquete se
encuentra dañado. Conserve el embalaje original en un lugar seguro para su uso en el futuro.
NOTA: Existen distintos tipos de UPS E4 Evolution II TT: modelos estándar y de uso prolongado, tanto de
alto como de bajo voltaje. Consulte la tabla a continuación.
NOTA: La función de doble entrada es opcional para los modelos E4 Evolution II + 10/15/20k TT HV y E4
Evolution II + 10k TT LV y como estándar para los modelos E4 Evolution II + 30/40/60/80 TT HV y E4
Evolution II + 15/20/30/40 TT LV.
Modelo
Versión
Modelo
E4 Evolution II + 10k TT HV
E4 Evolution II + 10k TT S HV
E4 Evolution II + 15k TT HV
E4 Evolution II + 15k TT S HV
E4 Evolution II + 20k TT HV
E4 Evolution II + 20k TT S HV
E4 Evolution II + 30k TT HV
E4 Evolution II + 40k TT HV
Modelo estándar
de alto voltaje
-
E4 Evolution II + 30k TT S HV
E4 Evolution II + 40k TT S HV
Versión
Modelo de alto
voltaje de uso
prolongado
E4 Evolution II + 60k TT S HV
E4 Evolution II + 80k TT S HV
E4 Evolution II + 10k TT LV
E4 Evolution II + 10k TT LV
E4 Evolution II + 15k TT LV
E4 Evolution II + 15k TT S LV
E4 Evolution II + 20k TT LV
-
Modelo estándar
de bajo voltaje
E4 Evolution II + 20k TT S LV
E4 Evolution II + 30k TT S LV
Modelo de bajo
voltaje de uso
prolongado
E4 Evolution II + 40k TT S LV
Se entiende por alto voltaje (HV) la tensión nominal de 380/400/415 V/AC
Se entiende por bajo voltaje (LV) la tensión nominal de 190/198/208 V/AC
112
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
2-1. Desembalaje e inspección
Desempaque el paquete y verifique su contenido El paquete enviado contiene:
Un UPS
Un manual del usuario
Un CD de programa de monitoreo
Un cable RS-232
Un cable USB
Un cable paralelo (opcional para los modelos 10/15/20k VA HV y 7.5/10kVA LV)
Un cable de corriente compartida (opcional para los modelos 10/15/20k VA HV y 7.5/10kVA LV)
Antes de la instalación, realice una inspección. Asegúrese de que nada en el interior del paquete se
encuentra dañado. No encienda la unidad y avise al transportista y al distribuidor de inmediato si existe
algún daño o hay piezas faltantes. Conserve el embalaje original en un lugar seguro para su uso en el futuro.
Se recomienda conservar cada juego de equipo y batería en sus embalajes originales ya que están
diseñados para proveer el máximo nivel de protección durante su transporte y almacenamiento.
113
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
2-2. Vista de terminal de cableado
Modelos de alto voltaje
Panel trasero
E4 Evolution II + 10/15/20k (S) TT HV (estándar)
Terminal de entrada/salida
E4 Evolution II + 10/15/20k TT (S) HV (estándar)
114
Panel trasero
E4 Evolution II + 10/15/20k TT (S) HV
(Entrada doble opcional)
Terminal de entrada/salida
E4 Evolution II + 10/15/20k TT (S) HV (entrada doble
opcional)
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Panel trasero
Panel trasero
E4 Evolution II + 30k TT (S) HV
E4 Evolution II + 40k TT (S) HV
Terminal de entrada/salida
E4 Evolution II + 30/40k TT (S) HV
115
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Apertura de puerta por panel
Apertura de puerta por panel
delantero
delantero
E4 Evolution II + 60k TT S HV
E4 Evolution II + 80k TT S HV
Terminal de entrada/salida
E4 Evolution II + 60/80k TT (S) HV
116
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Modelos de bajo voltaje
Panel trasero
E4 Evolution II + 10k TT LV (S) (estándar)
Panel trasero
E4 Evolution II + 10k TT (S) LV
(Entrada doble opcional)
Terminal de entrada/salida
Terminal de entrada/salida
E4 Evolution II + 10k TT (S) LV (estándar)
E4 Evolution II + 10k TT (S) LV (entrada doble
opcional)
117
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Panel trasero
Panel trasero
E4 Evolution II + 15k TT (S) LV
E4 Evolution II + 20k TT (S) LV
Panel trasero
E4 Evolution II + 15/20k TT (S) LV
118
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Apertura de puerta por panel
Apertura de puerta por panel
delantero
delantero
E4 Evolution II + 30k TT S LV
E4 Evolution II + 40k TT S LV
Terminal de entrada/salida
E4 Evolution II + 30/40k TT (S) LV
119
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
1.
Puerto de comunicación RS-232
2.
Puerto de comunicación USB
3.
Conector de función de apagado de emergencia (conector EPO)
4.
Puerto de corriente compartida (solo está disponible para el modelo paralelo)
5.
Puerto paralelo (solo está disponible para el modelo paralelo)
6.
Espacio inteligente
7.
Conector/terminal de batería externa (solo está disponible para el modelo de uso prolongado)
8.
Disyuntor/interruptor de circuito de entrada de línea
9.
Interruptor de derivación de mantenimiento
10. Terminal de entrada/salida con protección
11. Terminal de entrada de línea
12. Terminal de salida
13. Terminal de conexión a tierra de entrada
14. Terminal de conexión a tierra de salida
15. Disyuntor/interruptor de circuito de entrada de derivación
16. Terminal de entrada de derivación
17. Terminal de conexión a tierra
18. Interruptor de salida
120
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
2-3. Instalación de UPS sencillo
La instalación y el cableado deberá ser llevado a cabo de acuerdo a las leyes/regulaciones locales,
además, las instrucciones a continuación deberán ser ejecutadas por personal calificado.
1)
Asegúrese de que el cableado e interruptores en el edificio acatan los estándares de capacidad
nominal del UPS para así evitar el riesgo de descarga eléctrica o de incendio.
NOTA: No use un receptáculo de pared como entrada de fuente de energía para el UPS, ya que su
corriente nominal es menor a la entrada de corriente máxima del UPS. De otro manera, el contacto podría
quemarse y ser destruido.
2)
Desactive el interruptor de la red eléctrica del edificio antes de la instalación.
3)
Apague todos los dispositivos conectados antes de conectar al UPS.
4)
Prepare el cableado según la siguiente tabla (use cables flexibles):
Modelos de alto voltaje
Especificaciones del cableado (mm²/AWG)
Entrada (Ph)
Entrada (Ph)
Entrada (Ph)
E4 Evolution II + 10k TT HV
6/14
6/14
6/14
E4 Evolution II + 15k TT HV
6/12
6/12
6/12
E4 Evolution II + 20k TT HV
10/10
10/10
10/10
E4 Evolution II + 30k TT HV
16/8
16/8
16/8
E4 Evolution II + 40k TT HV
16/6
16/6
16/6
E4 Evolution II + 60k TT S HV
25/4
25/4
25/4
E4 Evolution II + 80k TT S HV
35/2
35/2
35/2
Modelos de bajo voltaje
Especificaciones del cableado (mm²/AWG)
Entrada (Ph)
Entrada (Ph)
Entrada (Ph)
E4 Evolution II + 10k TT LV
10/10
10/10
10/10
E4 Evolution II + 15k TT LV
16/8
16/8
16/8
E4 Evolution II + 20k TT LV
16/6
16/6
16/6
E4 Evolution II + 30k TT S LV
25/4
25/4
25/4
E4 Evolution II + 40k TT S LV
35/2
35/2
35/2
NOTA 1: El cable para el E4 Evolution II + 10k TT (S) HV deberá ser capaz de soportar una corriente
superior a 20A. Se recomienda usar cable AWG 14 o más grueso para la fase y AWG10 o más grueso
para la neutral, como medida de seguridad y eficiencia.
NOTA 2: El cable para el E4 Evolution II + 15k TT (S) HV deberá ser capaz de soportar una corriente
superior a 30A. Se recomienda usar cable AWG 12 o más grueso para la fase y AWG10 o más grueso
para la neutral, como medida de seguridad y eficiencia.
NOTA 3: El cable para el E4 Evolution II + 20k TT (S) HV y E4 Evolution II + 10k TT (S) LV deberá ser
capaz de soportar una corriente superior a 40A. Se recomienda usar cable AWG10 o más grueso para la
fase y AWG 6 o más grueso para la neutral, como medida de seguridad y eficiencia.
NOTA 3: El cable para el E4 Evolution II + 30k TT (S) HV y E4 Evolution II + 15k TT (S) LV deberá ser
capaz de soportar una corriente superior a 60A. Se recomienda usar cable AWG 8 o más grueso para la
fase y AWG 4 o más grueso para la neutral, como medida de seguridad y eficiencia.
NOTA 4: El cable para el E4 Evolution II + 40k TT (S) HV y E4 Evolution II + 20k TT (S) LV deberá ser
121
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
capaz de soportar una corriente superior a 80A. Se recomienda usar 16mm²/AWG 6 como medida de
seguridad y eficiencia.
NOTA 5: El cable para el E4 Evolution II + 60k TT S HV o el E4 Evolution II 30k TT (S) LV deberá ser
capaz de soportar una corriente superior a 120A. Se recomienda usar 25mm²/AWG 4 como medida de
seguridad y eficiencia.
NOTA 6: El cable para el E4 Evolution II + 80k TT (S) HV y E4 Evolution II + 40k TT (S) LV deberá ser
capaz de soportar una corriente superior a 160A. Se recomienda usar 35mm²/AWG 2 como medida de
seguridad y eficiencia.
5)
Retire la cubierta del bloque de la terminal en el panel trasero del UPS. Después conecte los cables
de acuerdo a los siguientes diagramas de bloques de la terminal: (Primero conecte el cable de tierra
al realizar la conexión del cableado. ¡Al realizar la desconexión del cableado, el cable de conexión a
tierra deberá desconectarse al final!)
EN
ES
Output
Salida
Input
Entrada
Diagrama del cableado del bloque de terminal para el E4 Evolution II + 10/15/20k TT (S) HV
(estándar)
E4 Evolution II + 10k LV (S) HV (estándar)
Entrée
122
Entrée de le bypass
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
EN
ES
Output
Salida
Input
Entrada
Bypass Input
Entrada de derivación
Diagrama del cableado del bloque de terminal para el E4 Evolution II + 10/15/20k TT (S) HV
(entrada doble opcional)
E4 Evolution II + 10k TT (S) LV (entrada doble opcional)
EN
ES
Output
Salida
Input
Entrada
Bypass Input
Entrada de derivación
Diagrama del cableado del bloque de terminal para el E4 Evolution II + 30/40k TT (S) HV
E4 Evolution II + 15/20k TT (S) LV
123
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Diagrama del cableado del bloque de terminal para el E4 Evolution II + 60/80k TT S HV
E4 Evolution II + 30/40k TT S LV
TO UPS BAT+
PBAT
TO UPS BAT N
NBAT
TO UPS BATEsquemas de conexión de cableado de batería
NOTA 1: Asegúrese de que los cables están firmemente conectados a las terminales.
NOTA 2: Instale el disyuntor de salida entre la terminal de salida y la carga, de ser necesario, el disyuntor
deberá estar dotado con una función de protección de fugas de corriente.
6)
124
Coloque de nuevo la cubierta del bloque de la terminal en el panel trasero del UPS.
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Advertencia: (Solo para el modelo estándar)
Antes de la instalación, asegúrese de que el UPS no está encendido. Durante la conexión del
cableado, el UPS no deberá estar encendido.
No intente modificar el modelo estándar del modelo de uso prolongado. Especialmente, no intente
conectar la batería interna estándar a la batería externa. El tipo, voltaje y número podrían ser
distintos. ¡Realizar una conexión entre ellas podría dar como resultado un riesgo de descarga
eléctrica o de incendio!
Advertencia: (Solo para el modelo de uso prolongado)
Asegúrese de que un disyuntor de CC u otro dispositivo de protección está instalado entre el UPS y la
batería externa. De no ser así, instálelo con cuidado. Antes de la instalación, apague el disyuntor de
la batería.
NOTA: Coloque el disyuntor del paquete de la batería en la posición de “OFF” (APAGADO) y después
instale el paquete de batería.
Ponga especial atención al voltaje nominal de la batería, el cual se encuentra descrito en el panel
trasero. Si desea cambiar los números del paquete de batería, asegúrese de cambiar también la
configuración. Realizar una conexión con el voltaje incorrecto podría causar daños permanentes al
UPS. Asegúrese de que el voltaje del paquete de batería es el correcto.
Ponga mucha atención a las marcas de la polaridad del bloque de la batería externa, para asegurarse
de que conecta las polaridades de la batería correctamente. Una conexión incorrecta podrá causar
daños permanentes al UPS.
Asegúrese de que el cableado de conexión a tierra de protección se realiza correctamente. Las
especificaciones, color, posición, conexión y la confiabilidad de la conductancia deben ser verificados
con sumo cuidado.
2-4. Instalación del UPS para un sistema paralelo
Si el UPS solo está disponible para una operación simple, puede omitir esta sección y pasar a la siguiente.
1)
Instale y conecte el cableado del UPS de acuerdo a la sección 2-3.
2)
Conecte los cables de salida del UPS a un disyuntor de salida.
3)
Conecte todos los disyuntores de salida a un disyuntor de salida principal. Posteriormente, este
disyuntor de salida principal se conectará directamente a las cargas.
4)
Están permitidos tanto, paquetes de baterías comunes o paquetes de baterías independiente para
cada uno de los UPS.
5)
Consulte los siguientes diagramas de cableado:
125
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
EN
ES
UPS1
UPS 1
UPS2
UPS 2
Output
Salida
Input
Entrada
Diagrama de cableado para sistema paralelo del E4 Evolution II + 10/15/20k TT (S) HV
(estándar)
E4 Evolution II + 10k TT (S) LV (estándar)
EN
ES
UPS1
UPS 1
UPS2
UPS 2
Output
Salida
Input
Entrada
Bypass Input
Entrada de derivación
Diagrama de cableado para sistema paralelo del E4 Evolution II + 10/15/20k TT (S) HV (salida
doble opcional)
E4 Evolution II + 10k TT (S) LV (entrada doble opcional)
126
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
EN
ES
UPS1
UPS 1
UPS2
UPS 2
Output
Salida
Input
Entrada
Bypass Input
Entrada de derivación
Diagrama de cableado para sistema paralelo del E4 Evolution II + 30/40k TT (S) HV
E4 Evolution II + 15/20k TT (S) LV
127
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
EN
ES
UPS1
UPS 1
UPS2
UPS 2
Output
Salida
Input
Entrada
Bypass Input
Entrada de derivación
Diagrama de cableado para sistema paralelo del E4 Evolution II + 60/80k TT S HV
E4 Evolution II + 30/40k TT LV
2-5. Instalación de software
Para una protección de sistema computacional óptima, instale el software de monitoreo de UPS para
configurar el apagado completo de UPS.
Puertos de comunicación:
Puerto USB
128
Puerto RS-232
Espacio inteligente
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Para lograr un apagado/encendido y el monitoreo del estado sin supervisión del UPS, conecte un extremo
del cable de comunicación al puerto USB/RS-232 y el otro al puerto de comunicación de su PC. Cuando
tenga el software de monitoreo instalado, podrá programar el apagado/encendido y monitoreo del UPS
desde su PC.
El UPS está equipado con un espacio inteligente, óptimo ya sea para una tarjeta SNMP o AS400. Cuando
instale ya sea una tarjeta SNMP o AS400 en el UPS, le proporcionará opciones de monitoreo y de
comunicación avanzadas.
Nota: No es posible que un puerto USB y un puerto RS-232 trabajen simultáneamente.
3.
Operaciones
Panel LCD
Indicadores
Botones
Diagrama 11: Indicadores y panel LCD
3-1. Operación de los botones
Botón
Botón ON/Enter
(ENCENDIDO/Entrar)
Botón OFF/ESC
(APAGADO/SALIR)
Botón Test/Up
(Probar/Subir)
Botón Mute/Down
(Silenciar/Bajar)
Botón Test/Up +
Mute/Down
(Probar/Arriba +
Silenciar/Abajo)
Función
Enciende el UPS: Presione y mantenga presionado el botón más de 1 s
para encender el UPS.
Tecla Enter (Entrar): Presione esta tecla para confirmar la selección del
menú de configuración.
Apaga el UPS: Presione y mantenga presionado el botón más de 2 s para
apagar el UPS.
Tecla Esc (Salir): Presione este botón para regresar al último menú en el
menú de configuración.
Prueba de la batería: Presione y mantenga presionado el botón más de 1 s
para probar la batería en el modo CA, o en el modo CVCF.
Tecla UP (SUBIR): Presione este botón para mostrar la selección siguiente
en el menú de configuración.
Silenciar la alarma: Presione y mantenga presionado el botón más de 1 s
para silenciar la alarma. Consulte la sección 3-4-8 para más detalles.
Tecla Down (Abajo): Presione este botón para mostrar la selección anterior
en el menú de configuración.
Presione y mantenga presionado simultáneamente por más de 1 s para
entrar/salir del menú de configuración.
* Modo AC significa modo normal, modo CVCF significa modo de convertidor de frecuencia.
129
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
3-2. Indicadores LED y panel LCD
Indicadores LED:
Existen 4 testigos LED en el panel frontal del UPS para mostrar que está en funcionamiento:
LED
Derivación
Línea
Batería
Falla
●
○
●
○
○
○
●
●
○
●
○
○
●
○
●
●
●
○
●
○
○
○
●
○
●
○
○
●
○
○
○
○
○
○
○
●
Modo
UPS encendido
Sin modo de salida
Modo de derivación
Modo CA
Modo batería
Modo CVCF
Prueba de la batería
Modo ECO
Falla
Nota: ● significa que el LED está ENCENDIDO, y ○ significa que el LED está APAGADO.
En
Es
BackupTime lnfo
BackupTime lnfo (Respaldo la información de
tiempo)
Fault Info
Información de la falla
Input & Battery Voltage Info
Información del voltaje de la batería y de entrada
Mute Operation
Silenciar operación
Output & Battery Voltage Info
Información del voltaje de la batería y de salida
Battery Info
Información de la batería
Load Info
Información de la carga
ModeOperation Info
ModeOperation Info (Información Operación de
modo)
Diagrama 12: Panel LCD
130
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Pantalla
Función
Información del tiempo de respaldo
Indica el tiempo de respaldo en números cuando el UPS está en el modo
batería
H: horas, M: minutos, S: segundos
Información de falla
Indica que una advertencia y una falla han ocurrido.
Indica códigos de falla (enumerados en la sección 3-8).
Silenciar operación
Indica que la alarma del UPS esta inhabilitada.
Información de voltaje de salida y de batería
Indica el voltaje de salida, frecuencia o el voltaje de la batería.
V/AC: voltaje de salida, V/DC: voltaje de batería, Hz: frecuencia
Información de carga
Indica el nivel de carga: 0 - 25%, 26 - 50%, 51 - 75% y 76 - 100%.
Indica la sobrecarga.
Indica que la carga o la salida está baja.
Información de modo de operación
Indica que el UPS está conectado a la red eléctrica.
Indica que la batería está en operación.
Indica que el circuito de derivación está en operación.
Indica si el modo ECO se encuentra habilitado.
Indica que el circuito inversor está en operación.
Indica que la salida está en operación.
Información de la batería
Indica la capacidad de la batería: 0 - 25%, 26 - 50%, 51 - 75% y 76 - 100%.
Indica una falla en la batería.
Indica el nivel de batería bajo y el nivel de voltaje bajo.
131
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Información del voltaje de entrada y batería
Indica el voltaje de entrada o frecuencia o voltaje de la batería.
V/AC: Voltaje de entrada, VCD: voltaje de la batería, Hz: frecuencia de
entrada
3-3. Alarma audible
Descripción
Estado del UPS
Modo de derivación
Modo batería
Modo de falla
Advertencia
Sobrecarga
Otros
Falla
Todo
Estado de la alarma
Silenciado
Señal sonora cada 2 minutos
Señal sonora cada 4 segundos
Señal sonora continua
Sí
Señal sonora cada dos segundos
Señal sonora cada segundo
No
Señal sonora continua
Sí
3-4. Operación del UPS sencilla
1.
Encienda el UPS conectado a la red eléctrica (en el modo AC)
1)
Después de conectar correctamente el suministro de energía, coloque el disyuntor del paquete
de batería en la posición “ON” (ENCENDIDO) (paso disponible solo para el modelo de uso
prolongado). Después coloque el disyuntor de entrada en la posición “ON” (ENCENDIDO). En
este momento, el ventilador debería estar funcionando y el UPS suministrará energía a las
cargas a través de la derivación. El UPS está operando en el modo Derivación.
NOTA 1: Cuando el UPS se encuentra en el modo Derivación, el voltaje de salida se
suministrará directamente por la red eléctrica después de encender el disyuntor de entrada. En
el modo Derivación, la carga no es protegida por el UPS. Para proteger sus valiosos
dispositivos, debe encender el UPS. Consulte la siguiente etapa.
2)
Presione y mantenga presionado el botón “ON” (ENCENDIDO) por 0.5 s para encender el UPS y
la señal sonora se escuchará una vez.
3)
Algunos segundos después, el UPS cambiará al modo AC. Si el voltaje de la red eléctrica es
anormal, el UPS operará en el modo batería ininterrumpidamente.
NOTA 2: Cuando la batería del UPS esté baja, se apagará automáticamente en el modo Batería.
Cuando el suministro de la red eléctrica se restaure, el UPS reiniciará automáticamente en el modo
AC.
2.
132
Encienda el UPS sin el suministro de la red eléctrica (en el modo batería)
1)
Asegúrese de que las dos líneas de baterías están conectadas en el orden correcto de
terminales “+,TIERRA,-” y que el disyuntor del paquete de baterías está en la posición “ON”
(ENCENDIDO)(solo para el modelo de uso prolongado).
2)
Presione el botón “ON” (ENCENDIDO) para establecer el suministro de energía para el UPS y
que este ingrese al modo encendido. Después de la inicialización el UPS entrará al modo Sin
salida, luego presione y mantenga presionado el botón “ON” (ENCENDIDO) por 0.5 s para
encender el UPS y la señal sonora se escuchará una vez.
3)
Algunos segundos más tarde, el UPS operará en el modo Batería.
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
3.
Conectar dispositivos al UPS
Una vez que le UPS esté encendido puede conectar dispositivos a él.
4.
5.
133
1)
Primero encienda el UPS, después encienda los dispositivos uno por uno y el panel LCD
mostrará la carga total.
2)
De ser necesario conectar las cargas inductivas, tales como una impresora, los picos de corriente
de la carga deberán ser calculadas minuciosamente para verificar que son compatibles con la
capacidad de sobrecarga del UPS. Toda carga superior al 150% de la capacidad del diseño deberá
ser de menos de 60 ms.
3)
Si el UPS está sobrecargado, la señal sonora se escuchará dos veces por segundo.
4)
Si el UPS está sobrecargado, retire las cargas de inmediato. Se recomienda que todas las
cargas que estén conectadas al UPS acumulen un total del 80% de su capacidad de potencia
nominal para evitar sobrecargas del sistema de seguridad.
5)
Si el tiempo de sobrecarga sobrepasa el tiempo aceptable listado en las especificaciones en el
modo AC, el UPS cambiará automáticamente al modo Derivación. Después de eliminar la
sobrecarga, regresará al modo AC. Si el tiempo de sobrecarga sobrepasa el tiempo aceptable
listado en las especificaciones en el modo Batería, el UPS mostrará el estado de falla. Luego, si
se habilita la derivación, el UPS suministrará la potencia a la carga a través de la derivación. Si
la función de derivación se inhabilita o el voltaje de entrada no se encuentra dentro del rango de
derivación aceptable, la salida se cortará directamente.
Carga de las baterías
1)
Una vez que el UPS ha sido conectado a la red eléctrica, el cargador de baterías entrará en
operación automáticamente, a excepción del modo Batería o durante la autoprueba de batería,
sobrecarga o cuando el voltaje de la batería es alto.
2)
Se recomienda cargar las baterías por al menos 10 horas antes de su uso. De no ser así, el
tiempo de respaldo podría ser menor al esperado.
3)
Asegúrese de que las configuraciones de los números en el panel del control (por favor consulte
la sección 3-4-13 para una configuración detallada) coincide con la conexión actual.
Operación de modo de batería
1)
Cuando el UPS está en el modo Batería, la alarma sonora se escuchará de acuerdo con las
diferentes capacidades de la batería. Si la capacidad de la batería es mayor al 25%, la alarma
sonora se escuchará una vez cada 4 segundos; si el voltaje de la batería cae al nivel de la
alarma, la alarma sonora será más rápida (una vez por segundo) para recordar a los usuarios
que la batería está a un nivel bajo y que el UPS está a punto de efectuar el apagado automático.
Los usuarios pueden apagar algunas de las cargas que no son críticas para inhabilitar la alarma
de apagado y alargar así, el tiempo de respaldo. Si ya no hay más cargas que apagar, deberá
apagar todas las cargas tan pronto como sea posible, para proteger los dispositivos de la falla de
carga y/o pérdida de datos.
2)
En el modo Batería, los usuarios pueden presionar el botón Silenciar para inhabilitar la alarma
sonora.
3)
El tiempo de respaldo del modelo de uso prolongado depende la capacidad de las baterías
exteriores.
4)
El tiempo de respaldo puede variar en distintos entornos y tipos de cargas.
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
5)
6.
7.
Al ajustar el tiempo de respaldo a 16.5 horas (valor predeterminado del panel de LCD: 999 min),
después de la descarga de 16.5 horas, el UPS se apagará automáticamente para proteger la
batería. Esta protección de descarga de batería puede habilitarse o inhabilitarse a través del
panel de control LCD. (Consulte la sección de ajustes de LCD 3-7)
Prueba de la batería
1)
Si se ve en la necesidad de verificar el estado de la batería mientras el UPS está en operación
en el modo AC/modo CVCF, puede presionar el botón “Test” (Prueba) para que el UPS realice
una autoevaluación de la batería.
2)
Los usuarios también pueden realizar la autoevaluación de la batería, a través del software de
monitoreo.
Apague el UPS con el suministro de la red eléctrica en el modo AC
1)
Presione el botón “OFF” (APAGAR) por al menos 0.5 s para apagar el inversor del UPS. La
alarma sonora se escuchará una vez y el UPS cambiará al modo Derivación.
NOTA 1: Si el UPS está configurado para habilitar al salida de derivación, el voltaje se derivará
de la red eléctrica a los contactos de salida y a la terminal, incluso si el UPS está apagado
(inversor).
NOTA 2: Después de apagar el UPS, tome en consideración que el UPS se encuentra operando
en el modo Derivación y que existe el riesgo de pérdida de potencia en los dispositivos
conectados.
2)
8.
9.
En el modo Derivación, el voltaje de salida del UPS seguirá estando presente. Para poder cortar
la salida, apague el disyuntor de entrada. Después de algunos segundos, nada se visualizará en
el panel de visualización y el UPS se encontrará apagado por completo.
Apague el UPS sin el suministro de la red eléctrica en el modo Batería
1)
Presione el botón “OFF” (APAGAR) por al menos 0.5 s para apagar el UPS. La alarma sonora se
escuchará una vez.
2)
Entonces el UPS corta la energía hacia la salida y nada se visualizará en el panel de
visualización.
Silenciar la alarma sonora
1)
Para silenciar la alarma sonora, presione el botón “Mute” (silenciar) al menos 0.5 s. Si después
de silenciar la alarma sonora presiona el botón de nuevo, la alarma sonora se escuchará otra
vez.
2)
Algunas de las alarmas no pueden ser silenciadas a menos que el error se corrija.
10. Operación en estado de advertencia
134
1)
Cuando el LED de falla se ilumina y la alarma sonora se escucha cada segundo, es porque
existe algún problema la operación del UPS. Los usuarios pueden verificar el código de la falla
en el panel LCD. Consulte la tabla de solución de problemas en el capítulo 4 para más
información.
2)
Algunas de las alarmas no pueden ser silenciadas a menos que el error se corrija. Consulte la
sección 3-3 para más información.
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
11. Operación en el modo Falla
1)
Cuando el LED de falla se ilumina y la alarma sonora se escucha continuamente, es señal de que
existe un error crítico en el UPS. Los usuarios pueden obtener el código de la falla en el menú LCD.
Consulte el capítulo 4 para más información.
2)
Verifique las cargas, el cableado, la ventilación, la red eléctrica, la batería etc., después de que
ocurra una falla. No intente encender de nuevo el UPS sin haber resuelto el problema antes. Si el
problema persiste, póngase en contacto con su distribuidor o el personal de asistencia al cliente.
3)
En caso de una emergencia, desconecte la unidad de la red eléctrica, la batería externa y la salida
de inmediato para evitar daños potenciales al UPS o al equipo.
12. Modo de operación y de mantenimiento
Solo personal de mantenimiento o técnicos calificados deberá llevar a cabo esta operación.
Si el UPS requiere de servicio o reparaciones y la carga no puede ser desconectada, el UPS debe estar
en el modo de mantenimiento.
1)
Primero, apague el UPS.
2)
Después, retire la cubierta del interruptor de la derivación de mantenimiento en el panel.
3)
Cambie el interruptor de mantenimiento a la posición “BPS”. Después, apague el disyuntor de
entrada y el de salida del UPS.
4)
En el caso de contar con una batería externa, también desconéctela.
5)
El UPS se apagará por completo y el voltaje de entrada irá directamente a la terminal de salida.
6)
Para reiniciar, siga el procedimiento reservado.
13. Operación de configuración de corriente de carga
1)
Esta es una operación reservada para técnicos calificados o profesionales.
2)
Conecte el cable de comunicación al UPS y a una computadora. Asegúrese de haber instalado
antes la herramienta de comunicación. Para obtener información acerca de esta herramienta de
software, consulte a su distribuidor local para más información. Use el software para configurar la
corriente de carga correctamente.
3)
Después de actualizar la configuración con éxito, la corriente de carga se aplicará de inmediato.
De manera que la misma configuración de voltaje de carga se aplique la próxima vez, apague el
UPS con la batería conectada para guardar los cambios.
14. Operación de configuración de los números de carga
1)
Esta es una operación reservada para técnicos calificados o profesionales.
2)
Apagar el UPS. Si la carga no puede desconectarse, antes que nada, retire la cubierta del
interruptor de derivación de mantenimiento del panel posterior y coloque el interruptor de
mantenimiento en “BPS”.
3)
Apague el interruptor de entrada de línea y el UPS entrará en “No Output mode” (Modo sin
salida).
4)
Conecte el cable de comunicación del UPS a la computadora. Ingrese el software para
configurar los números del cargador cuidadosamente.
5)
Después que la configuración se actualice exitosamente, apague el UPS con las baterías
conectadas para guardar el cambio. Luego, modifique los números del cargador conectado.
135
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
6) Encienda el interruptor de entrada de línea y el interruptor de entrada de bypass (derivación)
externo. Luego, el UPS entrará en modo bypass (derivación). Si el UPS está en modo bypass
(derivación) de mantenimiento, gire el interruptor de mantenimiento a la posición "UPS" y luego
encienda el UPS.
NOTA: La configuración del número de cargador debe ser la misma que la del número real en el UPS. Si el
número de configuración es diferente al número real, la corriente de carga no puede cumplir con la
especificación.
3-5. Operación Paralela
1.
Arranque inicial del sistema paralelo
En primer lugar, asegúrese que todos los UPS tengan la misma configuración.
1)
Encienda cada UPS en modo AC (modo normal) respectivamente (Consulte la sección 3-4 (1)).
Luego, mida el voltaje de salida del inversor de cada fase para cada UPS con un multímetro.
Calibre el voltaje de salida del inversor configurando el ajuste de voltaje del inversor (consulte
los Programas 15, 16 y 17, sección 3-7) en la configuración de LCD hasta que la diferencia de
voltaje de salida de cada UPS esté dentro de 1V. Si la diferencia de voltaje es menor a 1V, puede
proceder a comenzar la operación paralela.
2)
Calibre la medición del voltaje de salida configurando la calibración el voltaje de salida (consulte el
Programa 18,19 y 20, sección 3-7) en la configuración de LCD para asegurarse de que la
diferencia entre el voltaje de salida real y el valor detectado del UPS sea inferior a 1V.
3)
Apague cada UPS (Consulte la sección 3-4 (7.)). Luego, siga el procedimiento de cableado en la
sección 2-4.
4)
Retire la cubierta del puerto del cable paralelo de corriente compartida en el UPS, conecte cada
UPS uno por uno con el cable paralelo y comparta el cable de corriente. Luego, atornille de
nuevo la cubierta.
5)
Encienda el sistema paralelo en modo AC (modo normal):
6)
a)
Encienda el interruptor de entrada de línea de cada UPS. Si usa una unidad de doble
entrada, encienda también el bypass (derivación) externo del interruptor de entrada.
Después de que todos los UPS ingresen al modo bypass (derivación), mida el voltaje de
salida entre dos UPS en la misma fase para asegurarse de que la secuencia de fases sea
correcta. Si estas dos diferencias de voltaje están cerca de cero, eso significa que todas las
conexiones son correctas. De lo contrario, compruebe si los cableados están conectados
correctamente.
b)
Encienda el interruptor de salida de cada UPS.
c)
Encienda cada UPS por turnos. Después de un tiempo, los UPS ingresarán al modo de AC
(modo normal) de forma síncrona y luego, se completará el sistema paralelo.
Encienda el sistema paralelo en modo Batería:
a)
Encienda el interruptor de la batería (solo disponible en el modelo de largo alcance) y el
interruptor de salida externo de cada UPS.
b)
Encienda cualquier UPS. Unos segundos más tarde, el UPS entrará en modo battery
(batería).
c)
Luego, enciende otro UPS. Unos segundos más tarde, el UPS ingresará en modo battery
(batería) y se agregará al sistema paralelo.
d)
Si tiene el tercer UPS, siga el mismo procedimiento de c). Entonces, el sistema paralelo
está completo.
Si necesita información más detallada, comuníquese con el proveedor o centro de servicio para
obtener instrucciones de operación en paralelo.
2.
Añadir una nueva unidad en el sistema paralelo
1)
136
No puede agregar una nueva unidad al sistema paralelo cuando todo el sistema se está
ejecutando. Debe cortar la carga y apagar el sistema.
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
3.
2)
Asegúrese de que todos los UPS sean los modelos paralelos y siga el cableado, consulte la
sección 2-4.
3)
Instalar el nuevo sistema paralelo referirse a la sección anterior.
Retire una unidad del sistema paralelo
Hay dos métodos para eliminar una unidad del sistema paralelo:
Primer método:
1)
Presione la tecla "OFF" (APAGADO) dos veces y cada vez debe durar más de 0,5 seg. Luego, el
UPS entrará en modo bypass (derivación) o modo sin salida sin salida de poder.
2)
Apague el interruptor de salida externa de esta unidad y luego apague el interruptor de entrada
de esta unidad.
3)
Después de apagado, puede apagar el interruptor de la batería (para el modelo de largo
alcance), quitar el paralelo y compartir los cables de corriente. Y luego retire la unidad del
sistema paralelo.
Segundo método:
1)
Si el bypass (derivación) es anormal, no puede retirar el UPS sin interrupción. Debe cortar la
carga y apagar el sistema primero.
2)
Asegúrese de que la configuración de bypass (derivación) esté habilitada en cada UPS y luego
apague el sistema en operación. Todos los UPS se transferirán al modo Bypass (derivación).
Retire todas las cubiertas de bypass (derivación) de mantenimiento y configure los interruptores
de mantenimiento de "UPS" a "BPS". Apague todos los interruptores de entrada e interruptores
de batería en el sistema paralelo.
3)
Apague el interruptor de salida, retire el cable paralelo y comparta el cable de corriente del UPS
que desea extraer. Luego, retírelo del sistema paralelo.
4)
Encienda el interruptor de entrada del UPS restante y el sistema se transferirá al modo Bypass
(derivación). Ajuste los interruptores de mantenimiento de "BPS" a "UPS" y vuelva a colocar las
cubiertas de bypass (derivación) de mantenimiento.
5)
Encienda el UPS restante de acuerdo con la sección anterior.
Advertencia: (Solo para el sistema paralelo)
●
Antes de encender el sistema paralelo para activar el inversor, asegúrese de que todas las
unidades de mantenimiento cambien a la misma posición.
●
Cuando el sistema paralelo es encendido para funcionar a través del inversor, por favor no opere
el interruptor de mantenimiento de ninguna unidad.
●
Si aplica al sistema paralelo, el modo ECO no es compatible. Por lo tanto, NO "active" el modo
ECO en ninguna unidad.
3-6. Significado de las abreviaturas en la pantalla LCD
Abreviatura
Contenido en pantalla
Significado
HAB
Habilitado
INH
Inhabilitado
ATO (auto)
Automático
BAT
Batería
NCF (modo
Modo normal (sin modo CVCF)
normal)
CF (modo CVCF)
Modo CVCF (modo convertidor de
SUB (sustraer)
frecuencia)
Sustraer
AGREGAR
Agregar
ENCENDIDO
Encendido
137
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
OFF (apagado)
Apagado
FBD (no
No permitido
permitido)
OPN (permitido)
Permitir
RES (reservado)
Reservado
N.L (pérdida de
Pérdida de línea neutra
línea (verificar)
neutra)
CHE
Verificar
OP.V (voltaje de
Voltaje de salida
salida)
PAR
(paralela)
Paralela, 001 se refiere al primer UPS.
AN (primera fase)
La primera fase
BN (segunda fase)
La segunda fase
CN (tercera fase)
La tercera fase
AB (primera línea)
La primera línea
BC (segunda
La segunda línea
línea)
CA
(tercera línea)
La tercera línea
HS.H (espera
Espera Activa
activa)
138
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
3-7. Configuración de LCD
Existen tres parámetros para ajustar el UPS. Consulte el diagrama 13.
Parámetro 1
Parámetro 1 es para las alternativas del
programa. Hay 20 programas para configurar.
Consulte la tabla debajo.
Parámetro 2 y parámetro 3 son las opciones
o valores de configuración para cada
programa.
NOTA: Seleccione los botones "Up” (Arriba) o
"Down” (Abajo) para cambiar los programas o
parámetros.
Parámetro 2
Parámetro 3
Diagrama 13: Configuraciones LCD
Lista de 20 programas disponibles para el parámetro 1:
CVCF
(modo
Código
Descripción
Derivación
CA
Eco
convertidor
Prueba
Batería
de
de la
batería
frecuencia)
01
Voltaje de salida
Y*
02
Frecuencia de salida
Y
03
04
05
06
07
08
09
10
11
Rango de voltaje para bypass
(derivación)
Rango de frecuencia para bypass
(derivación)
Modo ECO habilitar/inhabilitar
Rango de voltaje para el modo
ECO
Rango de frecuencia para el modo
ECO
Configuración de modo bypass
(derivación)
Configuración del tiempo máximo
de descarga de batería
Y
Y
Y
Y
Y
Y
Y
Y
Y
Reservado
Configuración de la función de
Espera activa
Y
Y
Y
Y
Reservado para futuras opciones
Y
12
Detección de pérdida neutra
Y
Y
Y
Y
Y
Y
13
Calibración de voltaje de batería
Y
Y
Y
Y
Y
Y
14
Ajuste de voltaje del cargador
Y
Y
Y
Y
Y
Y
139
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
15
Ajuste del voltaje del inversor A
Y
Y
Y
16
Ajuste del voltaje del inversor B
Y
Y
Y
17
Ajuste del voltaje del inversor C
Y
Y
Y
18
Calibración de voltaje de salida A
Y
Y
Y
19
Calibración de voltaje de salida B
Y
Y
Y
Y
Y
20
Calibración de voltaje de salida C
Y
*Y (SÍ) significa que este programa se puede configurar en este modo.
NOTA: Todos los ajustes de parámetros se guardarán solo cuando el UPS se apague normalmente con la
conexión de la batería interna o externa. (El apagado normal del UPS significa apagar el interruptor de
entrada en modo bypass (derivación)/sin salida).
01: Voltaje de salida
Interfaz
02: Frecuencia de salida
Interfaz
60 Hz, modo CVCF
50 Hz, Modo normal
ATO (auto)
140
Configuración
Parámetro 3: Voltaje de salida
Para los modelos 208/220/230/240 VAC, elija el siguiente voltaje
de salida:
208: voltaje de salida es de 208Vac
220: voltaje de salida es de 220Vac
230: voltaje de salida es de 230Vac
240: voltaje de salida es de 240Vac
Para los modelos de 120/127 VCA, elija el siguiente voltaje de
salida:
120: voltaje de salida es de 120Vac
127: voltaje de salida es de 127Vac
Configuración
Parámetro 2: Frecuencia de Salida
Configurando la frecuencia de salida. Elija entre tres opciones en
el parámetro 2:
50.0 Hz: La frecuencia de salida está ajustada para 50.0 Hz.
60.0 Hz: La frecuencia de salida está ajustada para 60.0 Hz.
ATO (Automático): De ser seleccionada, la frecuencia de salida
se decidirá según la última frecuencia normal del servicio
eléctrico. Si es de 46 Hz a 54 Hz, la frecuencia de salida será de
50.0 Hz. Si es de 56 Hz a 64 Hz, la frecuencia de salida será de
60.0 Hz. ATO (automático) es la configuración predeterminada.
Parámetro 3: Modo de frecuencia
Configuración de la frecuencia de salida en modo CVCF o en
modo distinto a CVCF. Puede elegir las siguientes dos opciones
en el parámetro 3:
CF (modo convertidor de frecuencia): Ajuste de UPS al modo
CVCF. De ser seleccionada, la frecuencia de salida se fijará en
50 Hz o 60 Hz de acuerdo con la configuración en el parámetro 2.
La frecuencia de entrada podría ser de 46 Hz a 64 Hz.
NCF (modo normal): Ajuste de UPS al modo normal (no al modo
CVCF). De ser seleccionada, la frecuencia de salida se
sincronizará a 50 Hz si la frecuencia de entrada está entre 46 ~
54 Hz o, a 60 Hz si está entre 56 ~ 64 Hz según la configuración
del parámetro 2. Si se selecciona 50 Hz en el parámetro 2, el
UPS transferirá a modo de batería cuando la frecuencia de
entrada no esté dentro de los 46 ~ 54 Hz. Si se selecciona 60 Hz
en el parámetro 2, el UPS transferirá a modo de batería cuando la
frecuencia de entrada no esté dentro de 56 ~ 64 Hz.
*Si el Parámetro 2 es ATO, el Parámetro 3 mostrará la frecuencia
actual.
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
03: Rango de voltaje para bypass (derivación)
Interfaz
Configuración
Parámetro 2: Ajuste el bajo voltaje aceptable para el bypass
(derivación).
Para los modelos 208/220/230/240 VAC, el rango de configuración
es de 176V a 209V y el valor predeterminado es 176V.
Para los modelos de 120/127 VCA, el rango de configuración es de
96 V a 88 V y el valor predeterminado es 96 V.
Parámetro 3: Ajuste el alto voltaje aceptable para el bypass
(derivación).
Para los modelos 208/220/230/240 VAC, el rango de configuración
es de 231V a 276V y el valor predeterminado es 264V.
Para los modelos de 120/127 VCA, el rango de configuración es de
146V a 156V y el valor predeterminado es 146V.
04: Rango de frecuencia para bypass (derivación)
Interfaz
Configuración
Parámetro 2: Ajuste la baja frecuencia aceptable para el bypass
(derivación).
Sistema de 50 Hz: El rango de configuración es de 46.0 Hz a
49.0 Hz.
Sistema de 60 Hz: El rango de configuración es de 56.0 Hz a
59.0 Hz.
El valor predeterminado es 46.0 Hz/56.0 Hz.
Parámetro 3: Ajuste la alta frecuencia aceptable para el bypass
(derivación).
50 Hz: El rango de configuración es de 51.0 Hz a 54.0 Hz.
60 Hz: El rango de configuración es de 61.0 Hz a 64.0 Hz.
El valor predeterminado es 54.0 Hz / 64.0 Hz.
05: Modo ECO habilitar/inhabilitar
Interfaz
Configuración
Parámetro 3: Habilitar o inhabilitar la función ECO. Puedes elegir
las siguientes dos opciones:
INH: inhabilitar la función ECO
HAB: Habilitar la función ECO
Si la función ECO está inhabilitada, el rango de voltaje y el rango
de frecuencia para el modo ECO aún se pueden configurar, pero
no tiene sentido a menos que la función ECO esté habilitada.
*Si el sistema se ejecuta en paralelo, asegúrese de configurar
"DIS" (inhabilitar) solamente.
06: Rango de voltaje para el modo ECO
Interfaz
141
Configuración
Parámetro 2: Punto de bajo voltaje en modo ECO. El rango de
configuración es de -5% a -10% del voltaje nominal.
Parámetro 3: Punto de alta voltaje en modo ECO. El rango de
configuración es de + 5% a + 10% del voltaje nominal.
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
07: Rango de frecuencia para el modo ECO
Interfaz
Configuración
Parámetro 2: Ajuste el punto de bajo voltaje para el modo ECO.
Sistema de 50 Hz: El rango de configuración es de 46.0 Hz a
48.0 Hz.
Sistema de 60 Hz: El rango de configuración es de 56.0 Hz a
58.0 Hz.
El valor predeterminado es 48.0 Hz/58.0 Hz.
Parámetro 3: Establecer el punto de alto voltaje para el modo
ECO.
50 Hz: El rango de configuración es de 52.0 Hz a 54.0 Hz.
60 Hz: El rango de configuración es de 62.0 Hz a 64.0 Hz.
El valor predeterminado es 52.0 Hz/62.0 Hz.
08: Configuración de modo bypass (derivación)
Interfaz
09: Configuración del tiempo máximo de descarga de batería
Interfaz
Configuración
Parámetro 3:
000 ~ 999: Ajuste el tiempo máximo de descarga de 0 min a
999 min. El UPS se apagará para proteger la batería si el tiempo
de descarga llega antes de que la batería esté en bajo voltaje. El
valor predeterminado es 990 min.
INH: Inhabilite la protección de descarga de la batería y el tiempo
de respaldo dependerá de la capacidad de la batería.
10: Reservado
Interfaz
142
Configuración
Parámetro 2:
OPN (permitido): Bypass (derivación) permitido. Una vez
seleccionado, el UPS funcionará en modo Bypass (derivación)
dependiendo de la configuración de bypass (derivación)
habilitado/inhabilitado.
FBD (no permitido): Bypass (derivación) no permitido. Una vez
seleccionado, no se permite el funcionamiento en modo Bypass
(derivación) bajo ninguna situación.
Parámetro 3:
HAB: Bypass (derivación) habilitado. Una vez seleccionado, se
activa el modo Bypass (derivación).
INH: Bypass (derivación) inhabilitado. Una vez seleccionado, se
acepta el bypass (derivación) automático, pero no se permite el
bypass (derivación) manual. El bypass (derivación) manual
significa que los usuarios operan manualmente el UPS para
modo Bypass (Derivación). Por ejemplo, al presionar el botón
OFF (APAGADO) en modo AC (MODO NORMAL) para cambiar
al modo Bypass (derivación).
Configuración
Reserva para opciones futuras.
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
11: Configuración de la función de Espera activa
Interfaz
12: Detección de pérdida neutra
Interfaz
Configuración
Parámetro 2:
N.L (pérdida neutra): Indica la función de detección de pérdida
neutra.
Parámetro 3:
INH: Deshabilite la función de detección de pérdida neutra. El
UPS no detectará la pérdida neutra o no.
ATO (Automático): El UPS detectará automáticamente si el
neutro se pierde o no. Si se detecta una pérdida neutra, se
generará una alarma. Si el UPS está encendido, se transferirá al
modo de batería. Cuando se recupera y detecta el neutro, la
alarma se silenciará automáticamente y el UPS volverá
automáticamente al modo normal.
CHE (verificar): El UPS detectará automáticamente la pérdida
neutra. Si se detecta una pérdida neutra, se generará una
alarma. Si el UPS está encendido, se transferirá al modo de
batería. Cuando se restaura el neutro, la alarma NO se silenciará
automáticamente y el UPS NO volverá automáticamente al modo
normal.
Aquí, debe silenciar la alarma y hacer que el UPS vuelva al modo
normal de forma manual. La operación es: En primer lugar,
ingrese a este menú y presione la tecla “Enter” (Ingresar) para
hacer que “CHE” (verificar) parpadee. En segundo lugar, vuelva a
presionar la tecla "Enter" (Ingresar) para activar la detección
neutral (verificar). Si se detecta un neutro, la alarma se silenciará
y el UPS volverá al modo normal. Si no se detecta el neutro, el
UPS continuará la alarma y permanecerá en el estado más
reciente hasta que el neutro se detecte correctamente en la
próxima operación de verificación manual.
CHE (verificar) es el ajuste predeterminado.
13: Calibración de voltaje de batería
Interfaz
143
Configuración
Parámetro 2:
HS.H (espera activa): Indica la función Espera activa.
Parámetro 3: Habilitar o inhabilitar la función espera activa
SÍ: La función de espera activa está habilitada. Significa que la
corriente.
El UPS está configurado para albergar la función de espera
activa, y se reiniciará
Después de la recuperación de AC (modo normal) incluso sin
batería conectada.
NO: La función de espera activa está inhabilitada. El UPS se
está ejecutando en
Modo normal y no se puede reiniciar sin batería.
Configuración
Parámetro 2: Seleccione “Add (Agregar)” o “ Sub (Sustraer)” la
función para ajustar el voltaje de la batería a la figura real.
Parámetro 3: el rango de voltaje es de 0V a 9.9V y el valor
predeterminado es 0V.
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
14: Ajuste de voltaje del cargador
Interfaz
15: Ajuste del voltaje del inversor A
Interfaz
Configuración
Parámetro 2: puede elegir Add (Agregar)o Sub (Sustraer)para
ajustar el voltaje del cargador
Parámetro 3: el rango de voltaje es de 0V a 9.9V y el valor
predeterminado es 0V.
NOTA:
*Antes de realizar el ajuste de voltaje, asegúrese de desconectar
todas las baterías primero para obtener el voltaje exacto del
cargador.
* Cualquier modificación debe ser adecuada a las
especificaciones de la batería.
Configuración
Parámetro 2: puede elegirAdd (Agregar) o Sub (Sustraer)
para ajustar el voltaje A del inversor.
Parámetro 3: el rango de voltaje es de 0V a 9.9V y el valor
predeterminado es 0V.
* Add (Agregar) o Sub (Sustraer) se ajusta al voltaje de salida
que haya configurado.
16: Ajuste del voltaje del inversor B
Interfaz
Configuración
Parámetro 2: puede elegir Add (Agregar) o Sub (Sustraer)para
ajustar el voltaje del inversor B*.
Parámetro 3: el rango de voltaje es de 0V a 9.9V y el valor
predeterminado es 0V.
*Mostrará el número 1 debajo de
representar el voltaje del inversor B.
Configuración
Parámetro 2: puede elegir Add (Agregar) o Sub (Sustraer)para
ajustar el voltaje del inversor C*.
Parámetro 3: el rango de voltaje es de 0V a 9.9V, el valor
predeterminado es 0V.
*Mostrará el número 2 debajo de
representar el voltaje C del inversor.
o
para
18: Calibración de voltaje de salida A
Interfaz
144
para
17: Ajuste del voltaje del inversor C
Interfaz
o
Configuración
Parámetro 2: siempre muestra OP.V (Voltaje de salida) como
voltaje de salida.
Parámetro 3: muestra el valor de medición interno del voltaje de
salida A y puede calibrarlo presionando Up (Arriba)o Down
(Abajo) según la medición de un voltímetro externo. El resultado
de la calibración será efectivo presionando Enter (Ingresar) El
rango de calibración está limitado dentro de +/- 9V. Esta función
se utiliza normalmente para la operación en paralelo.
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
19: Calibración de voltaje de salida B
Interfaz
Configuración
Parámetro 2: siempre muestra OP.V (Voltaje de salida) como
voltaje de salida*.
Parámetro 3: muestra el valor de medición interno del voltaje de
salida B, y puede calibrarlo presionando Up (Arriba) o Down
(Abajo) según la medición de un voltímetro externo. El resultado
de la calibración será efectivo presionando Enter (Ingresar) El
rango de calibración está limitado dentro de +/- 9V. Esta función
se utiliza normalmente para la operación en paralelo.
*Mostrará el número 1 debajo de
voltaje de salida B.
para representar el
20: Calibración de voltaje de salida C
Interfaz
Configuración
Parámetro 2: siempre muestra OP.V (Voltaje de salida) como
voltaje de salida.
Parámetro 3: muestra el valor de medición interno del voltaje de
salida C, y puede calibrarlo presionando Up (Arriba)o Down
(Abajo) según la medición de un voltímetro externo. El resultado
de la calibración será efectivo presionando Enter (Ingresar) El
rango de calibración está limitado dentro de +/- 9V. Esta función
se utiliza normalmente para la operación en paralelo.
*Mostrará el número 2 debajo de
voltaje de salida C.
para representar el
3-8. Modo de Funcionamiento/Descripción de Estado
La siguiente tabla muestra la pantalla LCD para los modos de operación y estados.
(1) Si el UPS está en funcionamiento normal, mostrará siete pantallas una por una, lo que representa
voltajes de entrada trifásicos (An, bn, Cn), voltajes de entrada de 3 líneas (Ab, bC, CA) y su
frecuencia respectiva.
(2) Si los sistemas de UPS paralelos se configuran con éxito, mostrará una pantalla más con "PAR
(Paralelo)" en el parámetro 2 y el número asignado en el parámetro 3 como se muestra a
continuación en el diagrama de pantalla paralela. El UPS maestro se asignará por defecto como "001"
y los UPS subalternos se asignarán como "002" o "003". Los números asignados pueden ser
cambiados dinámicamente en la operación;
Pantalla paralela
Modo de funcionamiento/estado
UPS
Descripción
Encendido
Cuando el UPS esté encendido, entrará en este modo durante unos
segundos como inicialización del CPU y el sistema.
Pantalla
LCD
145
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Modo sin
descripción
salida
Cuando el voltaje/frecuencia de bypass (derivación) esté fuera del rango
aceptable o el bypass (derivación) esté inhabilitado (o prohibido), el UPS
entrará en modo sin salida si se enciende o apaga el UPS. Significa que el
UPS no tiene salida. La alarma suena cada dos minutos.
Pantalla
LCD
Modo CA
Descripción
Cuando el voltaje de entrada esté dentro del rango aceptable, el UPS
proporcionará energía de AC (corriente alterna) pura y estable para la
salida. El UPS también cargará la batería en modo AC (modo normal)
Pantalla
LCD
146
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Modo ECO
Descripción
Cuando el voltaje de entrada esté dentro del rango de regulación de voltaje
y el modo ECO esté habilitado, el UPS pasará el voltaje a la salida para
ahorrar energía.
Pantalla
LCD
Modo CVCF
Descripción
Cuando la frecuencia de salida se establece en "CF", el inversor emitirá
una frecuencia constante (50 Hz o 60 Hz). En este modo, el UPS no tendrá
salida de bypass (derivación) pero seguirá cargando la batería.
Pantalla
LCD
147
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Modo batería
Descripción
Cuando el voltaje/frecuencia de entrada esté fuera del rango aceptable o
exista falla de alimentación, el UPS respaldará energía de la batería y la
alarma sonará cada 4 segundos.
Pantalla
LCD
Modo de
Descripción
derivación
Cuando el voltaje de entrada esté dentro de un rango aceptable y el bypass
(derivación) esté habilitado, apague el UPS y entrará en el modo Bypass.
La alarma suena cada dos minutos.
Pantalla
LCD
148
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Prueba de la
Descripción
batería
Cuando el UPS esté en modo AC o modo CVCF, presione la tecla "Test”
(Prueba) durante más de 0,5 seg. Luego, el UPS emitirá un pitido y
comenzará la “Battery Test” (Prueba de Batería). La línea entre I/P y los
íconos del inversor parpadearán para recordarle a los usuarios. Esta
operación se utiliza para comprobar el estado de la batería.
Pantalla
LCD
149
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Estado de
Descripción
Advertencia
Si se producen algunos errores en el UPS (pero sigue funcionando
normalmente), se mostrará una pantalla más para representar la situación
de advertencia. En la pantalla de advertencia, el ícono
estará
parpadeando y puede mostrar hasta 3 códigos de error con cada código
indicando error. Puede encontrar el significado del código en la tabla de
códigos de advertencia.
Pantalla
LCD
Estado de
Descripción
falla
Cuando el UPS haya fallado, se bloqueará el inversor. Mostrará el código
de falla en la pantalla y se encenderá el ícono
. Puede encontrar el
significado del código en la tabla de códigos de falla.
Pantalla
LCD
3-9. Código de Falla
Falla
Ícono
Falla
Código de falla
Ícono
01
Falla de arranque del Bus
Ninguno
42
Falla de comunicación DSP
02
Sobre Bus
Ninguno
43
Sobrecarga
03
Bajo Bus
Ninguno
46
Configuración incorrecta de UPS
Ninguno
04
Desequilibrio de Bus
Ninguno
47
Falla de comunicación MCU
Ninguno
06
Convertidor sobre corriente
Ninguno
48
Ninguno
11
Falla de arranque suave del
inversor
Alto voltaje del inversor
Ninguno
60
Ninguno
61
Dos versiones de firmware DSP
son incompatibles en el sistema
paralelo.
Fase de bypass (derivación) en
cortocircuito
Bypass (derivación) SCR
cortocircuitado
Bypass (derivación) SCR abierto
en circulación
Forma de onda de voltaje
anormal en fase R
Forma de onda de voltaje
anormal en fase S
Forma de onda de voltaje
anormal en fase T
12
15
16
17
18
150
Código de falla
Salida del inversor B (línea a
neutro) cortocircuitado
Salida del inversor C (línea a
neutro) cortocircuitado
Salida del inversor A-B (línea a
línea) cortocircuitada
Inversor B-C salida (línea a
línea) cortocircuitado
62
63
64
65
Ninguno
Ninguno
Ninguno
Ninguno
Ninguno
Ninguno
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
19
1A
Inversor C-A salida (línea a
línea) cortocircuitado
Inversor A falla de energía
negativa
Falla de alimentación negativa
del inversor B
Fallo de alimentación negativa
del inversor C
Batería SCR cortocircuitada
66
Muestra de corriente del inversor
anormal
Bypass (derivación) O/P
cortocircuitado
Bypass (derivación) O/P
cortocircuitado
Inversor SCR cortocircuitado
Ninguno
Ninguno
Ninguno
67
Ninguno
68
Ninguno
69
Ninguno
6C
Ninguno
6D
24
Relé inversor abierto en
circulación
Relé inversor cortocircuitado
Ninguno
6E
Voltaje de BUS cae demasiado
rápido
Valor de error de muestreo de
corriente
Error de alimentación SPS
25
Fallo en el cableado de línea
Ninguno
6F
Polaridad de batería revertida
Ninguno
31
Falla de comunicación paralela
Ninguno
71
PFC IGBT en fase
Ninguno
32
La falla de señal del host.
Ninguno
72
PFC IGBT en fase
Ninguno
33
Fallo de señal síncrona
Ninguno
73
PFC IGBT en fase
Ninguno
34
Falla de señal de disparador
síncrono
Pérdida de comunicación
paralela
Desequilibrio de corriente de
salida paralela
Sobretemperatura
Ninguno
74
INV IGBT en fase
Ninguno
Ninguno
75
INV IGBT en fase
Ninguno
Ninguno
76
Sobrecorriente
R
Sobrecorriente
S
Sobrecorriente
T
Sobrecorriente
R
Sobrecorriente
S
Sobrecorriente
T
INV IGBT en fase
Ninguno
1B
1C
21
23
35
36
41
3-10.
Ninguno
Ninguno
Ninguno
Ninguno
Indicador de Advertencia: Ícono intermitente
Ícono
Advertencia
Alarma
(intermitente)
Batería baja
Código de Advertencia
Sonando cada segundo
Señal
Sobrecarga
sonora
cada
segundos
Batería baja
dos
Sobrecarga
Batería sin conectar
Sonando cada segundo
Batería desconectada
Sobrecarga
Sonando cada segundo
Sobrecarga
EPO habilitar
Sonando cada segundo
EPO habilitar
Falla
del
ventilador/Sobrecalentami
Falla
Sonando cada segundo
ento
ventilador/Sobrecalenta
miento
Falla en el cargador
Sonando cada segundo
Falla en el cargador
Fusible I/P dañado
Sonando cada segundo
Fusible I/P dañado
Otras advertencias (ver
3-11)
151
del
Sonando cada segundo
Otras advertencias (ver
3-11)
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
3-11.
Código de Advertencia
Código de
advertencia
4.
Evento de advertencia
Código de
advertencia
Evento de advertencia
Las situaciones de línea son
diferentes en el sistema paralelo.
Las situaciones de bypass
(derivación) son diferentes en el
sistema paralelo.
Bloqueo en bypass (derivación)
después de sobrecarga 3 veces en
30 minutos
Convertidor de corriente
desequilibrado
La cubierta de interruptor de
mantenimiento está abierta
Servicio eléctrico extremadamente
01
Batería sin conectar
21
02
Pérdida de IP Neutro
22
04
Fase IP anormal
33
05
Fase de bypass (derivación)
anormal
34
07
Sobrecarga
3A
08
Batería baja
3C
09
Sobrecarga
3D
Bypass (derivación) está inestable
0A
Falla del ventilador
3E
Voltaje de batería demasiado alto
0B
EPO habilitar
3F
Voltaje de batería desequilibrado
0D
Sobretemperatura
40
Cargador cortocircuitado
0E
Falla en el cargador
desequilibrado
Solución de Problemas
Si el sistema UPS no funciona correctamente, resuelva el problema utilizando la tabla a continuación.
Síntoma
No hay indicación ni alarma en el panel
de la pantalla frontal, aunque la red
eléctrica esté normal.
Solución
Compruebe si el cable de
entrada está firmemente
conectado a la red.
advertencia
parpadean en la
pantalla LCD y la alarma suena cada
segundo.
Posible causa
La alimentación de entrada de
AC (corriente alterna) no está
bien conectada.
La función EPO está activada.
En este momento, el
interruptor EPO está en estado
"OFF" (apagado) o el puente
está abierto.
El ícono
y
parpadean
en la pantalla LCD y la alarma suena
cada segundo.
La batería externa o interna
está conectada
incorrectamente.
Compruebe si todas las
baterías están bien
conectadas.
UPS está sobrecargado.
Elimine el exceso de cargas de
la salida del UPS.
El ícono
y el código de
El ícono
y
parpadean
en la pantalla LCD y la alarma suena
dos veces por segundo.
152
UPS está sobrecargado. Los
dispositivos conectados al UPS
son alimentados directamente
por la red eléctrica a través del
Bypass (derivación).
Después de repetidas
sobrecargas, el UPS se
bloquea en el modo Bypass
(derivación). Los dispositivos
conectados son alimentados
directamente por la red
eléctrica.
Coloque el circuito en posición
cerrada para deshabilitar la
función EPO.
Elimine el exceso de cargas de
la salida del UPS.
Elimine primero el exceso de
carga de la salida del UPS.
Luego apague el UPS y
reinícielo.
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
El código de falla se muestra como 43.
El ícono
se enciende en la
pantalla LCD y la alarma suena
continuamente.
El código de falla se muestra como 14,
15, 16, 17, 18 o 19, el ícono
se ilumina en la pantalla LCD y la
alarma suena continuamente.
Otros códigos de falla se muestran en
la pantalla LCD y la alarma suena
continuamente.
El tiempo de respaldo de la batería es
más corto que el valor nominal
El UPS sobrecargado
demasiado tiempo y se
convierte en falla. Entonces el
UPS se apaga
automáticamente.
Retire el exceso de carga de la
salida del UPS y reinícielo.
El UPS se apaga
automáticamente porque se
produce un cortocircuito en la
salida del UPS.
Compruebe el cableado de
salida y si los dispositivos
conectados están en estado de
cortocircuito.
Se ha producido una falla
interna de UPS.
Póngase en contacto con su
distribuidor
Cargue las baterías durante al
menos 7 horas y luego
verifique la capacidad. Si el
problema persiste, consulte a
su distribuidor.
Póngase en contacto con su
distribuidor para reemplazar la
batería.
Las baterías no están
completamente cargadas
Defecto de baterías
El ícono
y
parpadean en
la pantalla LCD y la alarma suena cada
segundo.
El código de advertencia 02 y el ícono
parpadean en la pantalla LCD. La
alarma suena cada segundo.
5.
El ventilador está bloqueado o
no funciona; o la temperatura
del UPS es demasiado alta.
Revise los ventiladores y
notifique al distribuidor.
El cable neutro de entrada está
desconectado.
Verifique y corrija la conexión
neutra de entrada Si la
conexión es correcta y la
alarma sigue apareciendo
consulte la sección de
configuración del LCD para
ingresar al menú de
comprobación de pérdida
neutral y ver si el parámetro 3
es "CHE"; si es así, presione
primero la tecla "Enter"
(Ingresar) para hacer que
“CHE” parpadee y presione la
tecla “Enter” (Ingresar) en
segundo lugar para que el UPS
desactive la alarma. Si la
advertencia persiste, verifique
los fusibles de entrada de L2 y
L3.
El fusible de entrada L2 o L3
está dañado.
Reemplace el fusible.
Almacenamiento y Mantenimiento
5-1. Almacenamiento
Antes de guardarlo, cargue el UPS durante al menos 7 horas. Guarde el UPS cubierto y en posición
vertical en un lugar fresco y seco. Durante el almacenamiento, recargue la batería de acuerdo con la
siguiente tabla:
Temperatura de
Frecuencia de Recarga
Duración de Carga
De -25°C a 40°C
Cada 3 meses
1-2 horas
De 40°C a 45°C.
Cada 2 meses
1-2 horas
Almacenamiento
153
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
5-2. Mantenimiento
El UPS opera con voltajes peligrosos. La reparaciones solo deben ser llevadas a cabo por
personal de mantenimiento calificado.
Incluso después de desconectar la unidad de la red eléctrica, los componentes dentro del
sistema UPS todavía están conectados a los paquetes de baterías que son potencialmente
peligrosos.
Antes de realizar cualquier tipo de servicio y/o mantenimiento, desconecte las baterías y
verifique que no haya corriente y que no exista voltaje peligroso en los terminales de alta capacidad
del capacitor como los condensadores BUS.
Sólo las personas que están lo suficientemente familiarizadas con las baterías y con las
medidas de precaución necesarias pueden reemplazar las baterías y supervisar las operaciones. El
personal no autorizado deberá mantenerse alejado de las baterías.
Verifique que no haya voltaje entre los terminales de la batería y la tierra antes del
mantenimiento o la reparación. El circuito de la batería de este producto no está aislado del voltaje de
entrada. Pueden presentarse voltajes peligrosos entre las terminales de la batería y la tierra.
Las baterías pueden causar descarga eléctrica y tener una alta corriente de cortocircuito. Retire
todos los relojes de pulsera, anillos y otros objetos personales metálicos antes del mantenimiento o la
reparación, y sólo use herramientas con empuñaduras y mangos aislados para trabajos de
mantenimiento y reparación.
Al reemplazar las baterías, instale el mismo número y el mismo tipo de baterías.
No intente desechar las baterías quemándolas. Esto podría causar una explosión. Las
baterías deben ser descartadas correctamente de acuerdo con las regulaciones locales.
No abra ni destruya las baterías. El derrame de electrolitos puede causar lesiones en la piel y
los ojos. Podría ser tóxico.
Por favor, solo remplace el fusible con el mismo tipo y amperaje para evitar el riesgo de
incendio.
No desmonte el sistema UPS.
154
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
6.
Especificaciones técnicas
MODELO HV (400V)
CAPACIDAD*
E4
Evolution
II + 10 k
TT (S)
10KVA/10K
W
ENTRADA
Rango de
voltaje
Pérdida de
Línea de Baja
Regreso de
Línea de Baja
Pérdida de
Línea de Alta
Retorno de
línea alta
Rango de frecuencia
E4
Evolution
II + 15 k
TT (S)
15KVA/15K
W
E4
Evolution
II + 40 k
TT (S)
40KVA/40K
W
E4
Evolution
II + 60 k
TT S
60KVA/60K
W
E4
Evolution
II + 80 k TT
S
80KVA/80KW
Pérdida de Voltaje de Línea de Baja + 10V
300 VAC(L-N) ± 3% a una Carga del 50%; 276 VAC(L-N) ± 3% a 100% de Carga
Pérdida de Voltaje de Línea de Baja - 10V
Sistema de 46 Hz ~ 54 Hz @ 50 Hz
Sistema de 56 Hz ~ 64 Hz @ 60 Hz
Trifásico con Neutro
≧ 0,99 al 100% de la carga
Trifásico con Neutro
Voltaje de salida
360/380/400/415VAC (Ph-Ph)
208*/220/230/240VAC (Ph-N)
± 1%
Regulación de voltaje de CA
155
E4
Evolution
II + 30 k
TT (S)
30KVA/30K
W
110 VAC(Ph-N) ± 3% a 50% de Carga; 176 VAC(Ph-N) ± 3% a 100% de Carga
Fase
Factor de potencia
SALIDA
Fase
Rango de frecuencia
(Rango Sincronizado)
Rango de frecuencia (modo
bat. )
Sobrecarga
Modo CA
Modo batería
Proporción de cresta de
corriente
Distorsión armónica
Tiempo de
Batería
transferencia
de
línea
Derivación
de
inversor
ECO
inversor
EFICIENCIA
Modo CA
Modo batería
BATERÍA
Modelo
Tipo
estándar
Números
Tiempo de
recarga
Corriente de
carga (máx.)
Voltaje de
carga
Modelo de
Tipo
Largo
Números
Alcance
Corriente de
Carga (máx.)
Voltaje de
carga
FÍSICO
Modelo
Dimensiones,
estándar
Largo x Ancho
x Alto (mm)
Peso neto
(kg.)
E4
Evolution
II + 20 k
TT (S)
20KVA/20K
W
46 Hz ~ 54 Hz @ sistema de 50 Hz;
Sistema de 56 Hz ~ 64 Hz @ 60 Hz
50 Hz ± 0.1 Hz o, 60Hz ± 0.1 Hz
100%~110%: 60 min; 110%~125%: 10 min; 125%~150%: 1 min; >150%: inmediatamente
100%~110%: 60 min; 110%~125%: 10 min; 125%~150%: 1 min; >150%: inmediatamente
3:1 max
≦ 2 % @ 100% Carga Lineal; ≦ 5 % @ 100% Carga No-Lineal
0 ms
0 ms (Cuando falla el bloqueo de fase, se produce una interrupción <4 ms desde el inversor hasta el
bypass (derivación))
<10 ms
95.5%
94.5%
12 V/7 Ah
12 V/9 Ah
12 V/9 Ah
12 V/7 Ah
12 V/9 Ah
20 (10+10) 32 (16+16) 32 (16+16) (16+16)pzas x 2 cuerdas
9 horas de recuperación hasta el 90% de su capacidad
+/- 136.5
VDC ± 1%
20
2.0 A ± 10% (Recomendado)
1.0 ~ 12.0A (Ajustable)
+/- 218 VDC ± 1%
Dependiendo de las aplicaciones
32 ~ 40 (ajustable)
1.0~12.0A ±10% (Ajustable)
2.0~24.0A ±10%
(Ajustable)
+/- 13.65 VDC * N ± 1% (N = 16 ~ 20)
+/- 136.5
VDC ± 1%
626 x 250 x 750
124/126
N/A
139/141
815 x 300 x 1000
139/141
225/230
N/A
250/260
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Modelo de
Largo
Alcance
Dimensiones,
Largo x Ancho
x Alto (mm)
Peso neto
(kg.)
AMBIENTE
Temperatura de operación
Humedad de operación
Altitud de operación**
Nivel de ruido acústico
ADMINISTRACIÓN
Smart RS-232 o USB
SNMP opcional
626 x 250 x 750
28/30
Menos de
55dB @ 1
Metro
43/45
815 x 300 x 1000
43/45
60/65
61/71
790 x 360 x 1010
108/112
0 ~ 40 °C (la vida de la batería disminuirá al estar a > 25 °C)
<95 % y sin condensación
<1000 mts**
Menos de 58dB @ 1 Metro
Menos de
Menos de
Menos de
65dB @ 1
70dB @ 1
70dB @ 1
Metro
Metro
Metro
113/117
Menos de
75dB @ 1
Metro
Compatible con Windows® 2000/2003/XP/Vista/2008/7/8/10, Linux, Unix, y MAC
Gestión de la energía del administrador y navegador de web SNMP (compatible con VMWare©)
* Reducir la capacidad a 90% cuando el voltaje de salida se ajusta a 208VAC.
**Si el UPS se instala o se usa en un lugar donde la altitud es superior a 1000 mts, la potencia de salida debe reducirse en un 1% cada 100
mts.
***Las especificaciones del producto están sujetas a cambios sin previo aviso.
156
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
MODELO LV (208V)
CAPACIDAD*
E4
Evolution II
+ 10k TT (S)
E4
Evolution II
+ 15k TT (S)
10KVA
10KW
15KVA
15KW
ENTRADA
Rango de
voltaje
Pérdida de Línea
de Baja
Regreso de
Línea de Baja
Pérdida de Línea
de Alta
Retorno de línea
alta
Rango de frecuencia
Sistema de 46 Hz ~ 54 Hz @ 50 Hz
Sistema de 56 Hz ~ 64 Hz @ 60 Hz
Trifásico con Neutro
≧ 0,99 al 100% de la carga
Trifásico con Neutro
208/220VAC (Ph-Ph)
120/127VAC (Ph-N)
± 1%
Regulación de voltaje de CA
Proporción de cresta de
corriente
Distorsión armónica
Tiempo de
Batería
transferencia de línea
Derivación
de
inversor
ECO
inversor
EFICIENCIA
Modo CA
Modo batería
BATERÍA
Modelo
Tipo
estándar
Números
Tiempo de
recarga
Corriente de
Carga (máx.)
Voltaje de carga
Modelo de
Tipo
Largo
Números
Alcance
Corriente de
Carga (máx.)
Voltaje de carga
FÍSICO
Modelo
Dimensiones,
estándar
Largo x Ancho x
Alto (mm)
Peso neto (kg.)
Modelo de
Dimensiones,
Largo
Largo x Ancho x
Alcance
Alto (mm)
157
E4
Evolution II +
40k TT
S
40KVA
40KW
156 VAC(L-N) ± 3% a 50% de Carga
146 VAC(L-N) ± 3% a 100% de Carga
Pérdida de Voltaje de Línea de Alta - 5V
Voltaje de salida
Modo batería
E4
Evolution II
+ 30k TT
S
30KVA
30KW
70 VAC(Ph-N) ± 3% a 50% de Carga
88 VAC(Ph-N) ± 3% a 100% de Carga
Pérdida de Voltaje de Línea de Baja + 5V
Fase
Factor de potencia
SALIDA
Fase
Rango de frecuencia
(Rango Sincronizado)
Rango de frecuencia (modo bat.
)
Sobrecarga
Modo CA
E4
Evolution
II + 20k TT
(S)
20KVA
20KW
Sistema de 46 Hz ~ 54 Hz @ 50 Hz
Sistema de 56 Hz ~ 64 Hz @ 60 Hz
50 Hz ± 0.1 Hz o, 60Hz ± 0.1 Hz
100%~110%: 60 min; 110%~125%: 10min; 125%~150%: 1min; > 150%:
inmediatamente
100%~110%: 60 min; 110%~125%: 10min; 125%~150%: 1min; > 150%:
inmediatamente
3:1 max
≦ 2% @ 100% de Carga Lineal; ≦ 4% a 100% de Carga No Lineal (PF≥0.8)
0 ms
0 ms (Cuando falla el bloqueo de fase, se produce una interrupción <4 ms desde el
inversor hasta el bypass (derivación))
<10 ms
93.5%
92.5%
12 V/9 Ah
12 V/7 Ah
12 V/9 Ah
(8 + 8)pzas
(8 + 8)pzas x 2 cuerdas
9 horas de recuperación hasta el 90% de su
capacidad
1.0~12.0A±10% (Ajustable)
N/A
+/- 109 VDC ± 1%
Dependiendo de las aplicaciones
16~20 (ajustable)
1.0~12.0A±10% (Ajustable)
2.0~24.0A±10% (Ajustable)
+/- 13.65 VDC * N ± 1% (N = 8~10)
626 x 250 x
750
815 x 300 x
1000
815 x 300 x
1000
139/141
626 x 250 x
750
152
815 x 300 x
1000
117
815 x 300 x
1000
N/A
790 x 360 x
1010
790 x 360 x 1010
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
Peso neto (kg.)
AMBIENTE
Temperatura de operación
Humedad de operación
Altitud de operación**
Nivel de ruido acústico
ADMINISTRACIÓN
Smart RS-232 o USB
SNMP opcional
43/45
60/65
61/71
108/112
113/117
0 ~ 40 °C (la vida de la batería disminuirá al estar a > 25 °C)
<95 % y sin condensación
<1000 mts**
Menos de 58dB Menos de 65dB
Menos de
Menos de 70dB
Menos de 75dB
@ 1 Metro
@ 1 Metro
70dB @ 1
@ 1 Metro
@ 1 Metro
Metro
Compatible con Windows® 2000/2003/XP/Vista/2008/7/8/10, Linux, Unix, y MAC
Gestión de la energía del administrador y navegador de web SNMP (compatible con
VMWare©)
* Si el UPS se instala o utiliza en un lugar donde la altitud es superior a 1000 mts, la potencia de salida debe reducirse un 1% cada 100 mts.
**Las especificaciones del producto están sujetas a cambios sin previo aviso.
158
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
ةبرعاا ةخسنلا
159
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
.1
ا
�KتاداشراCEM
�������
اامرلا
تلىىيري
يل
تل ات د
تبىيرا
تلى عام
ت ال ي ااتلا ي
تلىلايتلى اميتإ يش
حت .م ل
لللمتاإ اي
تف يت
ت كاي
تلىىيرت لا
يل
لةياتد
تلىلة ا
تلمكيا
تلإر
لىلاىيح
لىلا ي اات
تلا ي اات .
تل يش
لىلةييملا
تإ يشت
لىلا ح
تلى املحت
تلإر
تلىلة ا
تلملل يتديم
.ل ملل لي
!تري
لتإي اتلمإ إتل لاتلىإ
بيت
ت للللاحتيل ا
ياحتبيم
تتإ إم
الحتلىق اإاح
لىيحتInfosec Communicationت
ت ؤت مي
.ي
ميحت لتل ي يح
لىيم
تملاافشتلى ملحت
لى ا ل
ت يت
.ى ي
لى ايام
ىللللاتشت
CEتل
لىلل ي راا
لى يملرحت يت
تلى ل إ إ اات
تش
يللللا
تلى لبت
لىعا امت ي
يلت
لى لا احتإلا ي ا( DBTتلتCEMتيا اتد
ات
لى كرمل ة إيم ا
ىللللات
ىتإار تلى لي متلل
الحتلىقاإاحت يتلتح ).لىمقحتلىلا ح
يلا اتلا متتإ ل تلىإ
C3ت
تلى ملليت
تي ي
تل
ىةاىح
تل
تلل اتديم
تلىقم كاف
ىلللر
تلى لبت تمل
يل
تيكليتد
تل
لىمك اف
قملل ليت
تإيتح تلاتحى
لا
اليح
للايتل لإيمتبر
.
!تري
ي ل ات لتلىإ
تللنىكلمل يح
إاتيح
لىكرم
تىيتحتلى ا لات
تل ليمت ديمت .الحتلىق اإاح
تي اتبها ا
ل لاترايحتل لراف
إعكرت ي رتلات كايت ام الى ل اا
.
ةيستي اتلىلل فت راتي طراتل ات كايت ا م اتت،يليتلتإي ات ديلتلى م تي طرات ه لتلىإ إا ميا اتلى ل اتشتلى را
ايحته مدا
.لات ر
مك تب ها
لى ملل حلل رتإ
ميحت
لى إإا
بها اتلليمت
يت
ى ة لرت ه لت ا ل اات امإحته
لىياياات
ت مك ت ىاا حت
لى ة ات ل
لى ليمت
.اتل
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
160
اوتشتااا اوت متاا
.2
��K
لتإي ا :شن
لى
تلى را ت،لإرت
تل ةف
لىا إح .يم ل
تل شت ؤتعاتتللرت
لبكت يته ي
تفيت .
تل ات كاي
للىلة يش تلا ا
تإاىلاإتحت
لةليا
لاتل
.ى ملاإر ملل ل ات
ت لتتت يال
تل ش
تةاىحتة لس
لىيل مت،ل ا
لىلكيرته لت
تل
لى الر
تإغإقإت
للي
لى را ت
يتإلعةيرت
حت .تلا
يل لتإا ةليااتإكرت راتل إإامي
للىلل يي
لىارت
يحت ات اتت
ليمت ل لتة
ىلل
لاته إلراتلا يحتا را ت حت
.
��K
تلىإالحتلىق اإاح :شن
لل لل يحت يت ل لا
تللات Evolution II + TT E4 :د اقت ت
لى ايلتيلا
يحتل
لى ايللتىايام
متل اتS)،ت لن لملا(تلةلياإاتإلير
كقد ات للل
تHVتن سخة
لىلاى ا LV.تل
لتتبىلتلى لرت
يم ل
لىم
.
��
الحتلى ل ح :ةظ
تلىإ
لاييح
ميحتى ايل )(dual inputت
لليا
لتE4 Evolution II + 10/15 / 20k TT HVتل
ى ايلتE4 Evolution II + 7.5 / 10k TT LVت
ميحت
ليا
تلتE4 Evolution II + 30/40 / 60/80 TT HVتلدات لللمات
Evolution II + 15/20/30/40 TT LV E4.
لىإالح
لى ليل
لى ملح
لى ليل
10 kVA
E4 Evolution II + 10k TT
HV
E4 Evolution II + 10k TT S
HV
15 kVA
E4 Evolution II + 15k TT
HV
E4 Evolution II + 20k TT
HV
30 kVA
E4 Evolution II + 30k TT
HV
TT E4 Evolution II + 40k
HV
E4 Evolution II + 15k TT S
HV
E4 Evolution II + 20k TT S
HV
E4 Evolution II + 30k TT S
HV
E4 Evolution II + 40k TT S
HV
E4 Evolution II + 60k TT S
HV
E4 Evolution II + 80k TT S
HV
E4 Evolution II + 10k TT S
LV
E4 Evolution II + 15k TT S
LV
E4 Evolution II + 20k TT S
LV
E4 Evolution II + 30k TT S
LV
E4 Evolution II + 40k TT S
LV
20 kVA
40 kVA
60 kVA
ليلت
ليام ا
HV
-
80 kVA
10 kVA
E4 Evolution II + 10k TT
LV
15k TT + E4 Evolution II
LV
E4 Evolution II + 20k TT
LV
30 kVA
-
15 kVA
20 kVA
40 kVA
ليلت
ليام ا
LV
لى ملح
يلات
ليلت
للات
لةليا إات
إلير
HV
يلات
ليلت
للات
لةليا إات
إلير
LV
لى ااىا( HV
لى ر ت
تقتات لاإللمي إلؤت هلت ر تلم ا )
ت ل ال ات380/400/415تل ـت
للىات إي م
تتقتاتلا إللم )لىر تلى لي م( LV
لت ر تل م ات
ت ل ال ات208/220تل ـتي إلؤت ه
للىات إي م
���
�����K
.1-2ةتقاا
الحتلىق اإاح
لة ات لتلىإ
لى ملل ي
ىيرت
لىا إح
تللبك يت ةللياات
ت
ىإم
لقتل
لىا إح .
يتللر يت
:ي ات
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
161
232-RS تتكاإر
USB تكاإر
)7.5/10kVA LVتلت10/15/20k VA HV تللل ؤكاإرت
(ى ايل
ليامؤت
تتلل
)7.5/10kVA LVتلت10/15/20k VA HVليام
كاإرتىلااميتى
ل
ى ايل(ت
ليامؤت
تلل
162
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
�اشكل
�������
.2-2
���
�����K
���
�����K
E4 Evolution II + 10/15/20k TT (S) HV E4 Evolution II + 10/15/20k TT (S) HV ()حار ق
(�
����ش ل خ
)شا دااو
وشلح ا
������K
ش/اوشحاا
)S( E4 Evolution II + 10/15/20k TT HV
وشلح ا
������K
ش/اوشحاا
E4 Evolution II + 10/15/20k TT (S) HV ()حار ق
(�
����ش ل خ
)شا دااو
163
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
���
�����K
���
�����K
E4 Evolution II + 30k TT (S) HVE4 Evolution II + 40k TT (S) HV
وشلح ا
������K
ش/اوشحاا
E4 Evolution II + 30/40k TT (S) HV
164
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
��� ااو
���
�����K
E4 Evolution II + 60k TT S HV
��� ا
���
�������
E4 Evolution II + 80k TT S HV
وشلح ا
������K
ش/اوشحاا
13
E4 Evolution II + 60/80k TT (S) HV
165
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
شلرتاقااوشح ادحر ا
:
232-RSتييتلل ار 1.
USBتييتلل ار 2.
لىإلل مر 3.
شته ت
تلىللل
)EPOت م لإإ(تملإإتل ح
ليامتلىكرمإات ا 4.
لى
يشت
لى للل ؤ(تكاإرتلل
ى) ليلت
ت للل ؤ 5.
تيي
لةحتيكيح 6.
SNMPتل
يحتلام يح 7.
م لإإ تإإام
لا إشت ل مات لت إةرتلى لر 8.
ت إةرتلى م قتلى ا إ اتى يا ح 9.
لى لر 10.
شتبإاتتلىة /تةإحتإمليحت
ايحلى لملت
لى لر 11.
لإات
لى لمل 12.
لإات
لإاتلىلبمي متى لر 13.
لإاتلىلبميمتى لمل 14.
لا إشت ل مات لت إةرتى لت مات لرتلى م قتلى ا إ ا 15.
ى م قتلى ا إا 16.
لإاتلرتل
لإات لامرا 17.
إةرتلى ل مل 18.
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
166
��Kاوحلت
�������Kنش
تشت ااا
.3-2
كيإا اتل
تلىلم
لت
طاتى اللييتللى للت اتلى ا لرتإراتللى ل ا احتإاىل مكيإا اتلىكر مإاتيحلت وصيل ياتب م
لى ر اات .ىكاإق اتلل ا
يييت
تل
ي إ ةا
للىييتلاتارتلىكرمإات ا
لى
يتيي
شت
لىلاىيحت يتإم ر
.
)7
تىل
تلىق اإاح
لى رتل م اتى لتلىإالح
ت شت
ت للللا
تإلح
لى
تلى لمات
تللللإش
لىك رمإاتا
تكاإرلتىليامت
لبكت يت ي
ؤتلإمت ات
حت لتةميا
إاتي
ست حتكرم
.ةل
لى
تلملل يت
)8
��K
لى ا ل ت :شن
لي حلتىليامت
تا لرت يت
تلنم يحتد
لي حلتىليام
تلىق اإاحت ايت
تى لتلىإالح
لى ل مؤ تك متإالح
اإت
لىإالحتلىق اإاح
لىاإ تليل ش .لات لرت ل ت
تيةلم ت
فتل
.لب
لإرتلىعملتل
حت
إاتي
لىكرم
لى لمات
لاإشت
للات
لىلتإيال
.ات
ىإالحتلىق اإاح
تلإرتلل ي راتإال تل
يشتلااتلى ل ح
ر
تلعةير
غيااش ت
ليتإ
. )9
لىكاإقاتلى م ح(تليتإغ ه لتلىكاإق ات ة م اتلىل اي ا اتلى إية حتل اتلى لرتلىلاى ا
): )10لملليت
HVت ايل
لىك اإقات وصيلت لل ياا
)² / AWGت ي(ت
لى لر
)لىإل م(ت
)لىإل م(تلى لمل
يلى ةا
E4 Evolution II + 10k TT HV
6 / 14
6 / 14
6 / 14
E4 Evolution II + 15k TT HV
6 / 12
6 / 12
6 / 12
E4 Evolution II + 20k TT HV
10 / 10
10 / 10
10 / 10
E4 Evolution II + 30k TT HV
16 / 8
16 / 8
16 / 8
E4 Evolution II + 40k TT HV
16 / 6
16 / 6
16 / 6
E4 Evolution II + 60k TT S HV
25 / 4
25 / 4
25 / 4
E4 Evolution II + 80k TT S HV
35 / 2
35 / 2
35 / 2
LVت ايل
لىك اإقاتت وصيل لل ياا
)² / AWGت ي(ت
لى لر
)لىإل م(ت
)لىإل م(تلى لمل
E4 Evolution II + 10k TT LV
10 / 10
10 / 10
10 / 10
Evolution II + 15k TT LV E4
16 / 8
16 / 8
16 / 8
E4 Evolution II + 20k TT LV
16 / 6
16 / 6
16 / 6
E4 Evolution II + 30k TT S LV
25 / 4
35 / 2
25 / 4
35 / 2
25 / 4
35 / 2
E4 Evolution II + 40k TT S LV
لى ةاي
��Kااحم
نأ بجي 1:تشن
لبا نوكي
ي20ينن يلي ار ايت كيتنلي ا ري اقي10k TT (S) HV + E4 Evolution IIي ذويناي ي
نيب أ
نوكيجبييصوي .
ين لبر
بيي أويي6ي بقايو
ويين بأي/ 14 AWGيي
نبييص
.
��Kااحم
لبا نوكيأن نجي 2:تشن
ييE4 Evolution II + 15k TT (S) HVي ذويناي ي
ي30ينن يلي ار ايت كيتنلي ا ري اق
نيب أ
نوكيجبييصوي .
ين لبر
بيي أويي6ي بقايو
ويين بأي/ 12 AWGيي
نبييص
.
��Kااحم
لبا نوكيأن نجي 3:تشن
E4 Evolution II + 10k TTيبيE4 Evolution II + 20k TT (S) HVي ذويناي ي
يي(S) LV
نيب أي40ينن يلي ار ايت كيتنلي ا ري اق
نوكيجبييصوي .
ايونلبر
بييأويي10ي بق ي
نبييصويين بأي/ 10 AWGيي
.
��Kااحم
ين 3:تشن
لبا نوكيأن نجي ذو
E4 Evolution II + 15k TTيبيE4 Evolution II + 30k TT (S) HVي اي ي
يي(S) LV
نيب أي60ينن يلي ار ايت كيتنلي ا ري اق
نوكيجبييصوي .
ايونلبر
بييأويي16ي بق ي
نبييصويين بأي/ 8 AWGيي
.
��Kااحم
لبا نوكيأن نجي 4:تشن
E4 Evolution II + 20k TTيبيE4 Evolution II + 40k TT (S) HVي ذويناي ي
يي(S) LV
نيب أي80ينن يلي ار ايت كيتنلي ا ري اق
نوكيجبييصوي .
ايونلبر
بييأويي16ي بق ي
نبييصويين بأي/ 6 AWGيي
.
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
167
��Kااحم
لى ايل 5:تشن
يكليتكاإرت
ت ات يت
E4 Evolution II + 30k TTتلتE4 Evolution II + 20k TT (S) HVي
تت(S) LV
تي يتهيتلا طملت ه لتل ة ر
ليا م
تيؤت اإش .إي مت120ت
تكاإر
إاملل لي
شتت/ 10 AWGت يت مإشت25ت يل لت
لت ا إ
.كإم
��Kااحم
لبا نوكيأن نجي 6:تشن
E4 Evolution II + 40k TTيبيE4 Evolution II + 80k TT (S) HVي ذويناي ي
يي(S) LV
يب أي160ينن يلي ار ايت كيتنلي ا ري اق
ييص .ن
يجب
يون لبري نوك
يبييأوي35يوي بقا
نبي/ 2 AWGي
كاب لي
جبييصوي أول لطورب ال نسبة سمكا أك ثر
نوكي
.اإشت كإ م أو / 1ي0ي
��Kااحم
ىلل 7:تشن
لىم حتلل
صيل يتلىكاإقات
ت ل ايت لملل
إيح ى
ااات يحت إل
.إة ا
تلىق اإاح
تى لتلىإالح
ت ييح
لىل
ىلل رح
تل
تلى ل ل ته ل
مليح
تلىإ
لى ةإح
تإلل ي .لمةات بإاتت
يتلي
تلىكاإقاتكات
)11دلت لراتتر
مليح
تلىإ
لىلاىيح تى ةإاا
ليتإي ( ).ليتإلل يرتكاإرتلىلب مي مت لطت ه تلل يرتلىكاإق ا( :لات لى لإإاات
تلىلبمي متلات
تكاإر
ر
لىك اإقا
!).لاليمتهتل رت
اوشلحا
اوشحاا
اود ش خ ا
���K
��ا
)حار ق( E4 Evolution II + 10/15/20k TT (S) HVشحااااوشح
)حار ق( 10k (S) LV/+ E4 Evolution II
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
168
ج رخملا
اوشلحا
خر تق
وش دسااو
ش لحااا
اود ش خ ا
���K
��ا
تشحااااوشحE4 Evolution II + 10/15/20k TT (S) HV (�
����ل خ
)او ار
E4 Evolution II + /10k (S) LV (�
����ل خ
)او ار
��اة
اوشحاا
اوشلحا
خر تق
وش دسااو
ش لحااا
اود ش خ ا
���K
��ا
شحااااوشحE4 Evolution II + 30/40k TT (S) HV
E4 Evolution II + 15/20k TT (S) LV
169
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
اوشلحا
اوشحاا
خر تق
وش دسااو
ش لحااا
اود ش خ ا
���K
��ا
شحااااوشحE4 Evolution II + 60/80k TT S HV
E4 Evolution II + 30/40k TT S LV
ا ح+BAT ��K
����
اوش لااوارح
TO
UPS
BAT+
PBAT
PBAT
ا حNBAT�ا
ونش د اا
��ااK
وش لااو
TO
UPS
BAT
N
NBAT
NBAT
ا ح- BAT�ا
ونش د اا
��ااK
وش لااو
TO
UPS
BAT-
شح ااات حاا
���ا
ةرتناااوت
170
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
��Kااحم
يت هلت لالإاا 1:تشن
لىكاإق ات عل اتإغةكا
لبكيت يت
.ت
��Kااحم
لىعة ح 2:تشن
تلى لملتتل
تإيي
تلى لمل
تلاإشت لما
تلتإيا
بيلتى يتل ا مفت لطلت .ي م ل
طافتل
ي ات يتيكليتلا إشتلى ل مات ا م إ
تليامتلىلمما
ايحت ر
).ليار ا(ت إة
ىللل
اتتل
كا اتلىةإ
بىلت
لىلل ير ه ت
لىلافتإبلإاات
. )12ات
يلتلىاياماتلا إ( ر :خا ا
)ى ل
تإيل ا
احتلإرتل
لحتلىق اإ
يتلعةيرتل تلىإا
ت يت ه
لبك
تيكلي .
لىكاإتعن موق فاتي ات ي
تتلل يرت
يرت ت ا
لىلعة
.قا
تل لاتلة لياإاتإلير
تيؤ
ت ليل
تبىل
تلىا ياما
لى ليل
تلةييمت
تلىإإ .تلةالر
تلل ير
لىل لففتتلةالر
حت ه لتل ات
تلىللي
اميح
لىلام يح
يحت
اياميحتإاىإإام
لى
تللىا لل ييي .
لى ر ت
يكليت لتلىإإاميحتل
طا .لت
بيلتل اتإلل ي رات ا
تيكليت،
يىقتل إطملتى حتتلا
حت لت علاتةمي ا
إاتي
!كرم
اتلةلياإاتإليرتلا إ( ر :خا ا
يلاتلل
ى) ايلت
تل ةلياإ ات لت ؤت را تةايحت
تلىل لا
تلىإالحتلىق اإاحتللة ا
تإييت ل
ف لم
يك .
تىيت
يل
ب
يت
تلاإشت لماCC
تلتإي ا
تلي
تل
لبكت يت ا
ت
يىق
يلاتإا ايحت،ك
تلتإ
لتإي ا .يم ل
لى
اميحتلإرت
لماتلىإإ
تلاإشت
.با
��K
لىللاتل ةلياإات هلتلرش :شن
لاإشتلمات لةات
تيتليتإلتإياتديلتل لي مت"ARRÊT"،ت لرإإت
.
تل
تى إإام ياا
لى رتل م يح
تىاي حت
ت يل
تلى .ى إية حت ه لتلىلل رحتلىلييحل لإا
ةييمته ت لة لا
يلت ك ات لمبات لاتل
ت،ل لاتل ةلياإ اب
ىل لا
تلنه لت لات يتل
تلا ير
تلىق اإاحي كيت يتي مإ اتلىلل يرتإ رتإ إا ميحتبي مت ةي ات ر مطملت لتطاتى لتلى إا .ي م ل
.لح
يحت ةي ا
ت يت يت ر ت لهحتلىإإام
لبك
.
لى
تلىاإإيحت
ت ي لتى يعم
تإعكر تل لإا
تلل يرتلىإإاميح
بكت ي
تلل
لىلام يح
مليحتى إإاميحت
تلىإ
تل ى ةإح
طاتىريمت ل ل ته ل
ةي اتلل ا
رممت لتيتى ل ت
تيل مإاتلات
تإعكرتبيمت ةياتل
.لل ير
لىاإإيح
لىإالحتلىق اإاح ك ل .
ماشت ا ت
�K
�����Kا
�������K
تشت ااا
.4-2
�����
���لا
�����شر الاااخاااو
د
���Kوش ا
.اة
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
171
تشتااااوتا رشت
.5-2
���K
���� اة
���لا
�����شر الاااخاااو
د
.اوش ا
.3تشدار ا
��
LCDا م
تاوششمااا
اوشلرتاق( ا اة ااا
)
LCDتيعملاتلعاعح 11:تاوش حااااحم
.1-3تمتااااو ا
او ا
����K
تلىق اإاح
تلىإالح
لعةيرت ل
تلى ملر :
يل
تإ شتل مل ملمته لتد
تتايح(ت ة
) للة اتكتمت ي
MARCHE/Entréeت م
ىإالحتلىق اإاح
ىلعةيرتل تل
.
()ON/ENTER
تحتلنه ل لا :
تلا
ليامتل ا
بكي تل ل
يلااتتىل
لى
لت
ت م.Entréeلرةإته لتدي
ىإالحتلىق اإاح
تلعةيرتل تل
بيااش
يلتلى م :
لرةإشتل مل ملمته لتد
تكتمت ي(ت ت
ARRÊT/ÉCHAPت م
يلييتا
الحتلىق اإاح )
لعةيرتل تلىإ
نيااشت
.
()OFF/ESC
اإاحتلاتلاتحتلنه ل لا :
تبىلتلىاحتلىم
ى ال ا ات
لىمت
لرةإته لتديلت
تيلا ا. ÉCHAP
إامتلىإإاميح
للل
يحتللة ات للإ :
يتت
اكتمت ا
لىمت
لتديت
ل
شتل مل ملمته
امت لرةإت
Test/Hautت م
تلاتلرشACت لت.CVCF
تلىإإاميح
)(TEST/UP
ليامتلىلاىاتلاتلاتحتلنه ل لا :
يلتلى ي لااتنارامتل ل
ت اايل .HAUTلرةإت ه لتد
لإشتل يلم
يلتلى م :
يحتللة ا(تلرةإت شتل مل ملمت ه لتد
اكت يتتا
اشتلع )مت
ةيرتنيا
Silence/Basت م
لىامي .ليل م.9-4-3ى تييتلى ا ل اات
بىلت
تيم لتلىم ل ت
)(MUTE/DOWN
اتلات حتلن ه ل لا لرةإت ه :
لىماإاتل
يلتلى ي لااتنارامتللليامت
تيلا ا.BASلتد
Test/Haut +تياليا
لات
بىلت
يحتللةاتى للرت
تتميتتا
مييتتاك
لى
لتديييت
لىللات ه
لات ي ت
Silence/Basحت لرةإت
تلىلمللت را
.لنه ل لات ل
( & TEST/UP
)MUTE/DOWN
يعيمتلرش *
رشتل ؤتليعيمتلرشتACت
ىل ىاا
بىلتل
لىلم تCVCFت
ىلتلرشت ةلرت
ب
.
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
172
�KاLCD
.2-3اششمااا LEDا مر
���K
:ششمااا اا
تلعةيرت4ت د اق
لتةاىح
بى
يحتىلعامات
لةحتلا
ا
لى
تيحته لت
تت رل
لىإالحتلىق اإاحت يعملا
:لت
يعمت رلتا
Fault
Battery
Line
Bypass
لرش
لحت
ةيرت ل تلىإا
تتلع
إ
●
●
●
●
تلىق اإاح
ىي تد اقتلرشتلى لمل
○
○
○
○
ى م قتلى ا إا
لرشتتل
●
○
○
○
○
لرشتلىإإاميح
○
●
○
○
○
CVCFتلرش
○
●
●
○
○
إامتلىإإاميح
للل
●
●
ÉCOتلرش
●
○
●
○
تلىاا ؤ
لىلرش
لر
ا ل ااتهيت ر ت
اميحتل ر ت
لىإإ
لى لمل
رت ا
●
○
○
○
○
○
●
نشبمليينل كنيبي● :قةاح
تبيتق دي○ ألينايين وضأ
.ﺗﺸﻐﯿلﮫيفﯾﻘا
ا لااتهيتلىل ر
اتﺸﻐﯿ
لىللاتل ةلياإ
ا ا لااتهيت ات
ا ل ااتهيت ر ت
اميحتل ر ت
لىإإ
لى لر
يت
ا ل ا اته
لىإإاميح
لىعة ح
ا ل ااتهيت
لىلعةير
ييحت
تهيتكي
ا ل اا
اوش حااااحم
LCDتحعاع 12:ت
���K
���� اة
���لا
�����شر الاااخاااو
د
.اوش ا
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
173
.3-3ر خاااح تق
���K
���� اة
���لا
�����شر الاااخاااو
د
.اوش ا
��Kاوحلت
�������Kنش
تشت ااا
.4-3
شق 1-
�����اااوةلاتر
������ر تحلام اا
��K
تمتاااش لااوا
�����Kوارلت( ا
)
تبىلتلرشت إا
تلىإإاميح
لىكرمإات اتإعكرت ةيافت متلاإشت لما تة ح
ىليامت
تل
ىلل ير تإ متإالح
")MARCHE" (ONتل
تلةلياإ ات إليرت لاإ(
تيلات للا
ت ليل
ت لللماى
تبىلتلرش ).لى مة ح
تلى لر
تيت متلاإشت لما
شتتMARCHE" (ON)"،ت
للر إإتلاإ
تلى ا إا
تلى م ق
لى ل ح ")MARCHE" (ONت ه لتلرش )(15ت لما
تلىإالحت
لةارتى .يشت ايل
ملإتلى ملةحتل يت لاتل ع
تلىق اإاحل
تلى ا إاتميةيؤت لتلىإالح
تلى م ق
.لىعةيتهإم
يعلةر
تلىق ا إاحت
لى ا إافتت مت لتلىإالح
لاتلرشتلى م قت
لاإشتلى لما
لتلىلرش )(18ت
بى
MARCHE" (ON)".ت
��Kااحم
نندي 1:تشن
يابأنلنلياأريين لب اييابي نو
ييبنضأو ي
رخ نذنهبلن ي ابيبنرين بأي
ريأصو ديبليبريين جي
ن
ينن يي لوين رلك
تق رق
نندنريأصو دي نن ق .نلنأونمليو ري
ذنهبلني د ي لييابي نوي
ن ندي .بليبريين جرخين
صه د
نونندي نريأصو دي،نبناتخين
ذويار خيتنق كييياب ي
لىي رجى .
ىلتلى مة حت
لىم ل تب
لاىيح
.
تلى م
لىق اإاحت0.5تى ا ")MARCHE" (ONت لرةإتإامل ملمته ل
تىلعةيرت لتلىإالحت
تلى إات ا.تيحته لتلالر
تليي
يالي
م
تم يي
.إا لم
ت
لي
تبىلتلرشلتىليامت
لى ق اإاح
تيلةلرت لتلىإالحت
لى رلتا(تملش
حت ).علارتLINEتلى يعمت
تك ا اتإال
يل
ب
لىك رمإاتات،إ اتإ رشتتل ع
لى
لىليامت
إيايح
لرشتلىإإاميحت،ل الاتبيمتإ
تإعكرت ملمتلات
لىإالحتلىق اإاح
تيعلةرت ل ت
.لملش
�ا احم
طاتل اتل رشتلىإ إا ميحت،إإاميحت لتلىإالحتلىق اإاحتمستوىي نخفضت ه ا 2:تشنح�
بيااشتلعةي اتل ااتي
.يليت
الحتلىق ا
تلعةيرتل تلىإ
افتلليتبها ا
ليامتلى ل ال
لى
لحت
طاتل اتل رشتلىليا متلى ل ال ها تلملاا اتإا
.إ احتل ااتي
2- ��K
�����
���� لااوا
ت حااااو
حتإاى لامل
فتيك قتلل يرتلىعة
الحتلىق اإاح
ةيرت ل تلىإ
.إ م تلع
ط
تل لتلال مت،ليتإلعةيرت لتلى إالحتلىق ا إ احت لت
لعةيرتلا ر اتللة ا
تليتإ
تي
يليته م مت مللتلىع .
تلىك ات هلت م
)1ةي
تعاعح.LCD
تلىةتيح
تلىعةي
تلل ير
تلىرمل مؤ
تكايت ي
يل
تلىإ اإاحت،ب
لىعةحتت،تر
ت شتماحت
تيللللا
تلىإ تتإاايحتى لةاات يت ا
تليام
لي ا تةماا
ىإالحتلىق اإاح
ىتل اتى لتل
ؤتعة حتلي تهي .ل
يتلىماحتل م يحت150٪ت ا
يييتلرت يت،
لى
ميكليتللات
ل
تا يحت60ت
.ات
�������وارلتاادروات متاااش لااو 3-
����اااوةلاتر
اتر تحلاماارح
��K
اونش
��K
ا
تل الرت
تا يحته ل
تل ىرةإته لت م)ARRÊT" (OFFتى ا ". 0.5
تلىق اإاحتهيت إميا
تلعةيرت لتلىإالح
تإغيااش
لي
)2ت
قتلى ا إ ا
تلرشتلى م
حتلىق اإاحتبىل
لىإال
إاتم ي اتلميلةلرت ل ت
ملشتي متلى
.
��K
تبياا :شن
يت إا
تلال
تلى ا إاتلد اق تلإم
لى م ق
ته يتإباتيا رتلاتلرشت
تكيته ل
لىق اإاحف
تلعةيرت لتلىإالحت
ش
الحتىة ر اتلى ل ح
.لىإ
ت لللمل
تلىق اإاح
تي تارلت ات ر ت لتلىإالح
تلى ا إاف
تلى لمل .ل اتلرشتلى م ق
لى لرت،ىاإش
لللاتلاإشت لمات
لي .
ت
تت،إ اتإ رشتتل ع
يليته م مت ؤتعاتته ل
لى ق اإاحت
لحت
لىعاعحتليكليتل تلىإا
حت
.ليات هيتلىلعةيرتل اط امتوتىلة
���Kوحدا 4-
اوتمتاااةق
تل ىق اإاحتلإبتلا ةا "
تيلل ات لتلىإالح
تإعكرت مل مف
لى إات للا
يتي ك .لي مت
" )6ت ه اتيريت يعمFAULT
لىا مي 4).ت
بىلت
تل( 9-3تيم لتلىم ل ت
يتلقرتل تبىلتعاعحLCDتىامي ل ام
ىلإب لىم
ى تملل يتلىة لرت هلتم تل ت
لى ا ل ا ا
ت يت
.ى ي
لىك اإقات ،ه تة لستل ر
ىعةيفت
تل
لىلةا ات ي
لىلرليحت،يم لت
تلىإإاميحت،
لى لالاف
تلىليا مت
بى إت ،إالح
تل .
)7عةيرت لت تلةالر
ة
فتلال رتإاى ل تلتلى اته .لى إالحتلىق ا إ احت مات ل م ت ةللتل ةرتلى عكح
ماتل عك ح
يلتلمل ى
ب
لىيلم
.لت
)8
تلىق
تلىإالح
تل شت ل
تىل ا
لى لمل
تل
تلىلام يح
تلىإالحتللىإإاميح
لىيلم ت م
رتتلل رته لت
تلىإلل م
تةاىح
اإاحلت لا
ت
.لى را
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
174
.5-3اوتمتاااتروت ا ت
���K
���� اة
���لا
�����شر الاااخاااو
د
.اوش ا
LCD��K
���Kتحرااااو
حرش
.6-3ا
����� واا ا
او
اةحتحرا
ENA
DIS
ATO
BAT
NCF
CF
د�ل ةال
ياير
ل
ياير
تتل
بىةا
ت لقائ ي
لىإإاميح
لىلرشتلىاا ؤ
)CVCFتلىيتلرش(ت
لرشت ةلرت( CVCFتلرايح
لىلم
)
SUB
ADD
ON
OFF
FBD
OPN
RES
اق تطاع
لرالح
ال تش ﻐيلق يد
ال تش ﻐيل عنتلإااش
ممنوع
ب ه مسموح
ةل
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
175
N.L
CHE
OP.V
PAR
لى ةاي
لىلإت
ليت
لا
لىلةاا
لى لمل
رت
فتيعيم متو
بىلت لتت001تل ؤ
الحتلىق اإاحتلالر
.لىإ
AN
BN
CN
AB
BC
CA
HS.H
لى ةاي 1 -تلىإلم
لى ةاي 2 -تلىإلم
لى ةاي 3 -تلىإلم
2تلت1ت لاإللم
3تلت2ت لاإللم
1تلت3ت لاإللم
تللميح ما
ه ا
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
176
�LCD
����
.7-3ا
لىإالحتلىق اإاح
ست ا ا اتنهل ت ل ت
اقتتق
ىعكري رجى .د
تبىلتل
لىم
13.تل
لى ا ح
1ت
جرخعمخم
بلرحدي1ي
نربأ يبين
بخوي
إ م ابتت20ت د اق .ي ذ
ل .امتلى لرت ام .ىله ل
ش ادشتر�
تلي
ىله ل ت ل
لايت
حتىكرت دات ي
يتت ك 3تلت2تاوم
.إ م ا ب
��K
لىإملبت "لامير"تل " لاه ل"تلملل يت مؤ :شن
ةييمت
ىل
لتلى ا ا ا
.
لى ا ح
2ت
لى ا ح
3ت
اوش حااااحم
LCDت رإإتعاعح 13:ت
���K
���� اة
���لا
�����شر الاااخاااو
د
.اوش ا
(���Kااش ااوحدا
ا
�Kاا
شرت
) .8-3
تاا
اش ااوحدا
01
تتلعةير
تلاتإ
DC BUSتل ر
تعي
02
تتBUC DC
إ ر تلت
تعي
43
03
تتBUC DC
إ ر ت ال ف
تعي
46
لحتلىق اإاحتبيمت ةي ا
رإإتل تلىإا
04
تل ا
لللقرت
BUS DCت
تعي
47
MCUتلرتلل ار
تعي
لييتإمل ب
تاإلحتبيمتتDSPتب لمت
لى
48
تعي
06
ياد�
يامتلى ةلر تعي
تلاتل
DCت يا ا
ياد�
تاا
اش ااوحدا
42
DSPتلرتلل ار
حت لت ا
عة
تعي
تعي
لىلل ؤ
يت
لى اا
اييتلات
.لللل
لحت
11لعرتلاتإ تتلعةيرتل تلىإا
تعي
60
لتماتلات لماتل يما
لى
إلمت
لىق اإاح
12
لحت
ر تهاىاتىلتماتل تلىإا
تعي
61
لىم قتلى اإاتلات لماتل يماتSCR
تعي
لىق اإاح
15
حت
لى إال
يماتلات لتمات ل ت
تللما
62
إاتل لتمات يللةحتSCR
لىم قتلى ا ات
تعي
لى إلم
إييت
لى ةايتBتلىق اإاحت
ل
16
حت
لى إال
يماتلات لتمات ل ت
تللما
لى إلم
تبيمتإإيا اتلات
لى ر
R 63تعكرت ل حت
تعي
لى إلم
إييت
لى ةايتCتلىق اإاحت
ل
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
177
17
ت يماتلاتلتمات ل
حتتلما ل
لى إال
لى إلم
حتر تبيمتإإيااتلات
عكرت للى
S 64ت
تعي
لى إلم
إييت
تتAتلىق اإاحت
Bتل
18
حت
لى إال
يماتلات لتمات ل ت
تللما
لى إلم
عكرت ل حتلىر تبيمتإإيااتلات
T 65ت
تعي
لى إلم
إييت
CتلتBتلىق اإاحت
19
حت
لى إال
يماتلات لتمات ل ت
تللما
66
لىق اإاحتبيمتإإيا ا
لحت
ليامت ل تلىإا
تعي
لى إلم
إييت
AتلتCتلىق اإاحت
1A
حت
لىإال
تمات ل ت
لحت مإاتلات ل
هإرتإا
تعي
67
ى م قتلى اإاتلات لماتل يما
لملتل
Aتلىق اإاح
1B
حت
لىإال
تمات ل ت
لحت مإاتلات ل
هإرتإا
تعي
68
لى ا إات إل متO/P
إلمتلاتلمات /ى م قت
Bتلىق اإاح
1C
حت
لىإال
تمات ل ت
لحت مإاتلات ل
هإرتإا
ل يما
تعي
69
Cتلىق اإاح
21
ميحتلات لماتل يماتSCR
لىإإا
23
ي مطةرت لتلى إالحتلىق ا إ احتل ات
لى م قتSCR
لتمات
حتل مزت
ل تلىاإل
تعي
تلات لماتل يما
لىق اإاح
تعي
تعي
6C
مميشت لتBUSتللي امت ر
تعي
6D
لي ح
ىليامتال خطأت
ليتىاي اات
ل
تعي
لتماتيللةح
ت
24
ي مطةرت لتلى إالحتلىق ا إ احتتل ات
تعي
6E
لىكرمإاتا
لحتلىليامت
SPSتلإبتلاتإا
تعي
لماتل يما
يامت
لىل
لحت
25لإبتلل يرتلىكاإقاتىإا
تعي
6F
حت اكلمح
لإإيحتلىإإامي
ت
تعي
لىكرمإات ا
ي تع
71
ليا لت تىا
Rتلاتت إلمتIGBT PFCتمت
تعي
31
تلل ارت للل ؤ
لر
72
ليا لت تىا
Sتلاتت إلمتIGBT PFCتمت
تعي
32
بعاماتلى ريش
لعرت
تعي
ليا لت تىا
Tتلاتت إلمتIGBT PFCتمت
تعي
33
لىل ل ي
تلات
لر
تعي
73
تعي
34
لىل ل ي
لإحتل إق ت
تلعرته
تعي
74
ليا لت تىا
تت إلمتIGBT INVتمت
Rت لا
35
ليتللارتللل ؤ
لا
تعي
75
ليا لت تىا
تت إلمتIGBT INVتمت
Sت لا
تعي
36
لملتلى للل ؤ
لى
تليامت
لللقر
تعي
76
ليا لت تىا
تت إلمتIGBT INVتمت
Tت لا
تعي
41
ةملما لت ا
ت
تعي
����ا:ششمااا خ اا
.9-3ا ت شاا ا
تحخا ا
اييح
لىإإاميحتر
خاار
���K
) شاا( ا
تا يح
تت
بيلمت للاتكر
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
178
حت لت ا
عة
تا يح
تكرت
يلمليتللياي
ب
ميحتبيمت للىح
لىإإا
تا يح
تت
بيلمت للاتكر
اييح
حت لت اتر
عة
تا يح
تت
بيلمت للاتكر
لياير
EPOت
تا يح
تت
بيلمت للاتكر
تلاتلى ملةح
مليا ت /ت ه إر
ل
م حتلىةمل ما
تا يح
تت
بيلمت للاتكر
لاتلىعاةي
هإرت
بيلمت للاتكر
تت
تا يح
رم
تا يح
تت
بيلمت للاتكر
ة لمتI/Pت
لةييملات لم
لىامي(ت
مل شت
ت
)3-11
تا يح
تت
بيلمت للاتكر
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
179
اش اا خ اا
اش اا خا ا
01
02
لى لر
لي ةاي ت
لا ت
22
04
تإلمتلى لرتبيمتإإياا
لملي
33
إاتبيمت
قتلى ا
لمليتإلمتلى م
إإيا ا
حت لت ا
ىليالاتب اتال خاصل لحدت عة
ب هتلى م لا
اييح
لىإإاميحتر
34
يامتلى ةلر
لللقرتل
3A
ب إاتتلى إةرتلىي ل ؤتى م قتلى ا إ اتيلل ا
3C
ت لللحتإعكرتلا ف
لحتبيم
ل ل لاتلىإا
09
0A
0B
0D
حت لت ا
عة
تلاتلى ملةح
ت ه إر
لياير
EPOت
ةملما لت ا
ت
3D
3E
3F
40
تبيمت ملا م
ى م قتلى ا إا
ل
ر تلىإإاميحتهاى ات ل
ت للل
يحتبيم
ير تلىإإام
لىعاةيتلات لماتل يما
0E
لاتلىعاةي
هإرت
05
07
08
.4
حل ذاا خا ا
ميحتبيمت للىح
لىإإا
اش اا خا ا
21
��K
�ب ا ادادما� ا
وارح
لى
يحتلات
لىلإتلل
لىلل ؤ ةا ات
يت
اا
حتلاتل اايت
قتلى ا تإالل ي ى
ةا اتلى م
لى لل ؤ
لت ات
قتحتعةيت
إات تت
لى ا إا
لى مقت
رتلات
اي
لياحت30تلقر
ا حنا
رتإعك رت ةيا
تيعلة
ىإالحتلىق اإاحت
تكايتل تل
يل
لى لرت امت،ب
يت
تةرتل عك حتإاملل ل
.يم ل ى
اةتااا
لىعاعحت
لتىلةحت
بعاماتلبتيلمته
تلل ت ؤت
لى ل الات أن من غمب ال رت ،لاا يح
لحتلىليامت
إا
يايح
.إإ
������
اة تر
اوحد ا
لى ل الا
إاىليامت
لةييحت
لى
لاتتACت
.لى لرتبي مت ل لىحت يطل
لبكت يتكاإرتلى لرت ل لرت يطلت
لىكرمإاتا
.إاىاإا ت
حتلىالايي
لاتديمت .ي اةحتEPOت
لىإلل مرت،لى مة ح
يحت
يكليتمتلاي
لىلةييمت تلايال ح ت
يل رايتت تلم ت
شت ""OFFتلات لرشتEPO
يتلىااإ
ت لتعاعح لت
تا يحتLCDه
تكرت
تيمي
.للنيلم
لىملإإتيللا
.لت
لىة ات
ايحت
اتلات لر
تإرإإتللتم
ى
لي
ييحتلىا
ايرت لا
يااشتلي
EPO.تن
يحتبيمت
لى ل
لت
اتلىلام يحت ل
تل تلايال لاي لىإإاميا
لل رايته لتت
ل .لىحتإعكرت ي
تكرتتيحتLCDتعاعح
تيمي ا
.للنيلم
ال بطاري ات جميع أن منت أك د
..صحيحب شكل موصول ة
ب ي وي نن يق ن
مروييقييبأيييا
يأصو ديين باين وأي ا
نندين ر
يابي نو
نريأصو د
نندي
.نو
.يني ذ و
يأصو ديين باين وأي
نندين ر
يابي نو
بنديو ابي .يني ذ و
وين ب ق
دبنا
بي
مروييقييبأيييا
وينن قي نا
وييقي
يبنضأ
تلققني
نريأصو دي
نندي
نو
نريأصو د
نندي
.نو
نلنأو ديابأين جرخي
ننبلدي نم
تل تلايال لاي
لل رايته لتت
.نذنهبل
تا يحتLCDتعاعح
تكرت
يي
تيميت مل
.للنيلم
يلركينن أدينا م
ريتذ
لبي ر
روني و
بي
مروييقييبأيييا
وينن قي نا
نريأصو ديبلي
نندي
تقرقيياب ي نو
نريأصو د
نندي
ب ي .نو
جرخنذنهبل بينبنفييا
بر دي ن ي
للةي ت .
اريتنق ر ا
بن
نريأصو دي
نندي
.نو
ل ا ر اتلى ل لىحت إاع مات يتلىعإكحت
.لىكر مإاتيح
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
180
لىل ر
تت ارلمتم ت
تتلايال حت43
ت
تته لتعاعح
لميتتLCDت لرا
للن يلملات
.إامل مل م
لىل ر
تف14ت ارلمتم ت
تف15
تف17ت16،
تف18
ت19
تت
تتلايال ح
تته لتعاعحت
تLCDتلر ا
تلميتإامل مل م
.للن يلملا
نندي
نن أدي نا مروياراييابي نو
ييب رلكيي ابي
ص و دي برديبر
ن ريأ
بليلرك
نريأصو دي
نندي
ريجنخي .نو
و
يأصو دياقي
فييا نونندي نر
لبن ب ي
صنمين
.نلنق كيتر
بي
مروييقييبأيييا
وينن قي نا
اريتنق ر
نريأصو بين
نندي دي
.ا نو
فييا نونندي نر
لبن ب ي
للبك تيت
تلاتلى لملت
لةفتلىكاإق ا
يأصو دياقي ل
نلنقليتر
تلات لما
لى للىحتىيما
صنمينيوجب وي لوين ت أويبلي تيتلا ر ات
.يبأب ا
.ل يما
تعاعح
تLCDتم ل ت مل تى ل رتلارمته ل
تلميتإامل مل م
.للن يلملا
نندي
ي لرليو ابي نو
ربايلرك
نريأصو د
.
لىلافتإق
لل رتإاى ل ت
.
يتىايحت
ةلياإيحتى إإامياات ل تم ل
لى اتل
.ل م يح
اتبيمعةل حتإعكرتكا ر
.لىإإاميا ت
لعةيتلىإإاميااتى ا
ماهااته لتت7ت
لالرتلل
لمت .يةفتل ملرا
ه تلمل م
عك حفتلل رتإاى ل
لى .
تلاتلىإإامياا
.ل ر
نبي
ن أب دييلبنحدينبيديتنلقكني
ضد
بيشنايارايضن
يت
صو دي
نندينريأ
يب ديصبهلنا لبدي أ لويياب ي نو
ي أاي كينه ديLCD
.ب نهق ل
ي
.يأتح ديبر
لىل ر
تتت تللايال حت02،ت ارلمتم ت
كرت LCD .تلل مته لتعاعح
للن يلملاتل ميت
تا يح
.
لرتلىإإام ياا
لل رتإاى ل ت ملإ
.
يةفتلى ملةااتللل رتإاى ل
.ل
تلى ةاي
تلل يرت لر
.لية فت ل ةا
بيلتكايتل ل ارت ةيطةاتل تي لرت
تلاىم اتتلىم ل
يمتاادملف
لىلةي
بىلتت
تعاعح
تل ا
لميتل ىرإإ
ى للرتتLCDت
تت
ليتلى ةاي
لىلةات ايتلا
لاتحت
بىلت
لى ا ح
تليحت
بيلتك ا ا
ت3تلبك ت ات
تدلى
يمت
تإاى ةاي تب
لىل اف
لى لرت
كاإرت
يي "CHE".
تجي ن اي قنخني رقنينب د
.لر
ليتبيل » « Enterي ارا
«ينل
بيرقنييأوينلأنيارا » CHE
ي
نندي » « Enter
نل ل لقييابي نو
لي
نريأصو دييقيي بينل ق أ
يلتل .
ب
مل مت
لى لر
تتلنيلمفتللةفت ادمت
تL2
L3.تل
لملإ رتلى ر م
.
لى لر
L3.ت لتL2تلةلمل ت رمت
�����
����
.5
.1-5
�K
اااوتح
تلىلل يي
تى ات،لإر
تلىق اإاح
تل الرت7تلعةيت لتلىإالح
تلإر .م اهااته ل
تلىق اإاح
تإلةإيحت لتلىإالح
تي
رااته لياتول
لى .لاتكايتإام تل اش
طاتى لرتلىلاى القرت
:لل ييفت هتع ةيتلىإ إا ميا اتلل ا
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
181
���
��� حا اادااو
ت اتاااو��
شلدااومح�
بىلت - 25ي
ت حتليحت+ 40ت
م
عرمت3تكر
لتماهليي
بى
تماهحت
ي
بىلت40ت ي
حت تليحت45ت
م
كرتعر م
ي ن
لتماهليي
بى
تماهحت
ي
.2-5اوحار�
���لا��ي ااة خ
�����شر الاااخاااو
د
���وش ا
.ا
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
182
��K
.6اوش احلراااوت
HV (400
لى ر
ارت
ت اخان ماال
)V
E4
Evolutio
n II + 10
)k TT (S
E4
Evolutio
n II + 15
)k TT (S
��K
*ا
10 KVA
10 KW
15 VA /
KW 15
E4
Evoluti
on II +
k 20
)TT (S
20 VA /
KW 20
E4
Evolution
II + 30 k
)TT (S
E4
Evolutio
n II + 40
)k TT (S
30 VA /
KW 30
40 VA /
KW 40
E4
Evoluti
on II +
k 60
)TT (S
60 VA /
KW 60
E4
Evolutio
n II + 80
)k TT (S
80 VA /
KW 80
اوشلحا
يتلىعةي 50 %تعند 3 %ت) ±محاي د-طور( VAC 110
تلىلإت يتلىعةي 100 %تعند ) ± 3 %محاي د-طور( 176ت/ VACت
لالي
لى لي م
لىلإت
هلات
لى ل
يم
لإتلىااى ا
تلى
لالي
لإتلىااى ا
تلى
لالي
رتلىلم
ا
لى ر
لى لي مت
لىلإت
ليت
للىإت+ 10تلا
يتلىعةي 50 %تعند 3 %ت) ±محاي د-خ( VAC 300
يتلىعةي 100 %تعند ) ± 3 %محاي د-خ( 276ت/ VACت
تلى ر
إتلىااىا
تلىل
تللىإت- 10تلالي
) دمل ت50ت ااي(ت دملت~ 54ت دملت46
) دمل ت60ت ااي(ت دملت~ 64ت دملت56
ةاي +ت إللمت3
بىلت0.99ت≧
يتلىع ةي 100 %ت
لىإلم
ها رتلىإالح
اوش حا ا
ةاي +ت إللمت3
) إل م -إل م( VAC 360/380/400/415
) ةاي -إل م( VAC 220/230/240/*208
± 1%
) دمل ت50ت ااي(ت مل دت~ 54ت دملت46
) دمل ت60ت ااي(ت دملت~ 64ت دملت56
دمل ت± 0.1ت دمل ت60ت دملت لت± 0.1ت دملت50
، 110 %~125 %:لياحت100 %~110 %: 60
ياحتلل ة ا ، 125 %~150 %:لاتات10
;ل
لل مل >150 % :
ياحتلل ة ا ، 125 %~150 %:لاتات، 110 %~125 %: 10لياحت100 %~110 %: 60
;ل
لل مل >150 % :
ة ت ل لت3 :1
تبيمتلإيح 100 %تىا 5 %ت≦ ; يتع ة حتلإيح 100 %تىا 2 %ت≦
يتع ة ح
ي اتتايحت0
لىإل م
رتلى لمل
لى ر
ت رإإت
رتلىلم
) ارت ل ل ي(ت ا
رتلىلم
شتلىإإاميا ا(ت ا
) لر
لىيامت
شتل
لر
لىلعإش
لى ل الا
CAت
شتلىإإاميح
لر
تلىيملا
ت ها ر
ف
ط
طللتاتللللايح
ىل
ل
نلي نلنأونمل
يين
اتل لاار ل
نبونل د
نندي
با ي نو
ي
ريأص و د
يين
ن جرخي
هبل
نذن
لتلىإالحت
لىق اإ اح
ىحتلعرت مة حتلىاير(ت اتتايحت0
لتلىم قتل ى ا إات<4تة لستل اإات،لات ةا
تبى
تلىق اإاح
تتا ايحت يت لتلىإالح
)
تا يحت10
ي ات
ECO
95.5 %
94.5 %
شتلىاا ؤ
لىلر
شتلىإإاميح
لر
يلتليام ا
ل
لى ل
لىك يح
بهاتلىع ةي
ات ا
تلىعةي
تليام
اوش ال ل
+
12 V/
A7
20 (10
)10
+
12 V/
12 V/
A9
A9
32 (16 + 32 (16
)+16
)+16
12 A V/ 7
×ت لإاح )16
ييي
+
12 V/
A9
32 (16
N/A
اوت ارا
�K
يحت٪ت90ت ماه اات ملم لت9
تلى إإام
ت يتماح
) إات ل ل ( ± 10 %ت إيمت2.0
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
183
) لال ل(
لىعةي
ت رت
لى ل
لىك يح
تلىعةي
تليام
) لال ل(
تيلاتللات
ليل
تإلير
لي اإا
لة
ر تلىع ةي
�
اوححرشيااولاارشا
ليلتليام ا
يلات
ليلت
للاتلةليا إات
إلير
يxيل طول :ي دو ن
أا
يxين
يرب(يدلتحنا
)
لتىل يتلى الا
)كك(
تxيل طول :تا لاإا
لى امم
تxت
) ي(تل مليا
لتىل يتلى الا
)كك(
تةملماتلىلعةير
مح
لى مإيح
لىمإلإحت
ىلعةير
ليا تل
**لم
لى ملل تلىلل ا
USB :أو 232-Smart RS
للليامؤ SNMP
تت إيمت1,0~12,0
تىلا ير(
)لاإر
218 ± 1 %
+/
-
136,5Vc
c 1± %
20
+ / -Vcc
ىلإإياا ا
ةماتل
تىلا ير(ت32~40
)لاإر
لاإرت( إي مت2,0~24,0
)لاإرتىلا ير(ت إيمت1,0~12,0
13,65 )N = 16~20( % Vcc * N ± 1
+/
-136,5
)ىلا ير
+/-
Vcc ±
1%
826 x 250 x 627
129
144
1000 815 x 300 x
144
826 x 250 x 627
33
48
225
250
1000 815 x 300 x
48
60
N/A
61
1010 790 x 360 x
إليت(ت108
) إإاميح
إليت(ت113
) إإاميح
�
اوتاش
تليح 0 ~ 40
محت
يحتهاتلكليت محتلىةملما(
تلىإإا م
)م حت تليحت25ته لت يتملشتل افت لماته م
ليتلكاتشت٪ت<95
**ت لمت<1000
ت70تلرت ي ت70تلرت ي ت75تلرت ي
ت55تلرت ي تيميإرت هلت مالحت58تلرت ي ت65تلرت ي
يميإرته لت تيميإرته ل يميإرته لت
يميإرته لت
ل مت1
يميإرته لت
ل مت1ت مالح
ل مت1ت مالح لمت1ت مالح
ل مت1ت مالح
ل مت1ت مالح
ا لا اد
Macو Windows® 2000/2003/XP/Vista/2008/7/8/10, Linux, Unixي هي
ندياقي
وي لن رري نون
ييييوأهنيب( SNMPيت ل
لب به
لتح ينب و)© VMWareيي
بي
وأبتب بإ
أ هي
حتبى *
للييمتلىما
تلى لملته ل 90%تل
VAC 208.ت ه ترإإت ر
تيي ل **
اتلاتلمليا
تلىق احتإا لتلملل ل
تلىإالح
حتلى لملتإات1000ت هتلتإيات ل
لمفتلغاتياتللييمتإال
تتلمتاتللت100تهيتكر 1 %ت
.لمت1000
ب هقيت مإ ا***
.ي كيت يتللةيد متل ات فتلى ل ا اتإ ليت
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 –
[email protected] – 07 19 AA 59 205 03
184