WEG SSW07 / SSW08 Guía de inicio rápido

Tipo
Guía de inicio rápido
Par. English Español Português
Factory
Setting
P000 Access to parameters
0 to 9999
Acceso a los parámetros
0 a 9999
Acesso aos parâmetros
0 a 9999
0 (5)
READ ONLY PARAMETERS
P001 to P099
PARÁMETROS DE
LECTURA P001 a P099
PARÂMETROS DE LEITURA
P001 a P099
P001 Motor current %In of
SSW-07/SSW-08
0.0 to 999.9 %
Corriente del motor %In del
SSW-07/SSW-08
0.0 a 999.9 %
Corrente do motor %In da
SSW-07/SSW-08
0.0 a 999.9 %
-
P002 Motor current %In of Motor
0.0 to 999.9 %
Corriente del motor %In
del Motor
0.0 a 999.9 %
Corrente do motor %In do
Motor
0.0 a 999.9 %
-
P003 Motor current
0.0 to 6553 A
Corriente del motor
0.0 a 6553 A
Corrente do motor
0.0 a 6553 A
-
P005 Power supply frequency
0.0 to 99.9 Hz
Frecuencia de la red de
alimentación
0.0 a 99.9 Hz
Freqüência da rede de
alimentação
0.0 a 99.9 Hz
-
P006 Soft-Starter Status
0 = rdy - ready
2 = Exx - Error
3 = ruP - Ramp Up
5 = PASS - By-pass
7 = rdo - Ramp Down
8 = br - Braking
9 = rEv - FWD/REV
10 = JoG - Jog
11 = dly - Delay P630
12 = G.di - General Disable
Estado del Arrancador
Suave
0 = rdy - ready
2 = Exx - Error
3 = ruP - Ramp p
5 = PASS - By-pass
7 = rdo - Ramp Down
8 = br - Braking
9 = rEv - FWD/REV
10 = JoG - Jog
11 = dly - Delay P630
12 = G.di - General Disable
Estado da Soft-Starter
0 = rdy - ready
2 = Exx - Error
3 = ruP - Ramp p
5 = PASS - By-pass
7 = rdo - Ramp Down
8 = br - Braking
9 = rEv - FWD/REV
10 = JoG - Jog
11 = dly - Delay P630
12 = G.di - General Disable
-
P007 Voltage imposed by the
Soft-Starter over the load
(%Un)
0 to 100 %
Tensión impueta por el
Arrancador sobre la carga
(%Un)
0 a 100 %
Tensão imposta pela chave
sobre à carga (%Un)
0 a 100 %
-
P011 Apparent output power
0.0 to 999.9 kVA
Potencia aparente de salida
0.0 a 999.9 kVA
Potência aparente de saída
0.0 a 999.9 kVA
-
P012 DI1 to DI3 status
0 = Inactive
1 = Active
Estado DI1 a DI3
0 = Inactiva
1 = Activa
Estado DI1 a DI3
0 = Inativa
1 = Ativa
-
P013 Relay RL1 and RL2 output
status
0 = Inactive
1 = Active
Estado de las salidas a relé
RL1 y RL2
0 = Inactiva
1 = Activa
Estado das saídas a relé
RL1 e RL2
0 = Inativa
1 = Ativa
-
P014 Last fault occurred
E00 to E77
Ultimo error ocurrido
E00 a E77
Último erro ocorrido
E00 a E77
-
P015 Second fault occurred
E00 to E77
Segundo error ocurrido
E00 a E77
Segundo erro ocorrido
E00 a E77
-
P016 Third fault occurred
E00 to E77
Tercero error ocurrido
E00 a E77
Terceiro erro ocorrido
E00 a E77
-
P017 Fourth fault occurred
E00 to E77
Cuarto error ocurrido
E00 a E77
Quarto erro ocorrido
E00 a E77
-
P020 Actual Fault
0...99
Actual Error
0...99
Erro Atual
0...99
-
P023 Software version Versión de software Versão de software -
P030 Phase R current
0.0 to 6553 A
Corriente de la fase R
0.0 a 6553 A
Corrente da fase R
0.0 a 6553 A
-
P031 Phase S current
0.0 to 6553 A
Corriente de la fase S
0.0 a 6553 A
Corrente da fase S
0.0 a 6553 A
-
P032 Phase T current
0.0 to 6553 A
Corriente de la fase T
0.0 a 6553 A
Corrente da fase T
0.0 a 6553 A
-
P050 Motor thermal protection
status
0 to 250 %
Estado de la proteccíon
térmica del motor
0 a 250 %
Estado da proteção térmica
do motor
0 a 250 %
-
P081 Heatsink temperature
10.0 to 110.0 ºC
Temperatura del disipador
10.0 a 110.0 ºC
Temperatura do dissipador
10.0 a 110.0 ºC
-
P090 CAN Controller Status
0 = Inactive
1 = Autobaud
2 = Active CAN Interface
3 = Warning
4 = Error passive
5 = Bus off
6 = No Bus Power
Estado del controlador CAN
0 = Inactivo
1 = Autobaud
2 = CAN ativo
3 = Warning
4 = Error passive
5 = Bus off
6 = No alimentado
Estado controlador CAN
0 = Inativo
1 = Autobaud
2 = CAN ativo
3 = Warning
4 = Error passive
5 = Bus off
6 = Não alimentado
-
P091 DeviceNet Network Status
0 = Offline
1 = Online, Not Connected
2 = Online, Connected
3 = Expire Connection
4 = Connection Failure
5 = Auto-Baud
Estado Rede DeviceNet
0 = Offline
1 = OnLine, No conectado
2 = OnLine, Conectado
3 = Conexión Caduco
4 = Falla Conexión
5 = Auto-Baud
Estado Rede DeviceNet
0 = Offline
1 = OnLine, Não conectado
2 = OnLine, Conectado
3 = Conexão Expirou
4 = Falha Conexão
5 = Auto-Baud
-
P092 DeviceNet Master Status
0 = Run
1 = Idle
Estado Maestro DeviceNet
0 = Run
1 = Idle
Estado Mestre DeviceNet
0 = Run
1 = Idle
-
P093 Received CAN Telegram
Counter
0 to 9999
Telegramas CAN RX
0 a 9999
Telegramas CAN RX
0 a 9999
-
P094 Transmitted CAN Telegram
Counter
0 to 9999
Telegramas CAN TX
0 a 9999
Telegramas CAN TX
0 a 9999
-
P095 Buss Off Error Counter
0 to 9999
Contador de Bus Off
0 a 9999
Contador de Bus Off
0 a 9999
-
P096 Lost CAN Message Counter
0 to 9999
Mensajes CAN perdidas
0 a 9999
Mensagens CAN perdidas
0 a 9999
-
REGULATION
PARAMETERS
P100 to P199
PARÁMETROS DE
REGULACIÓN
P100 a P199
PARÂMETROS DE
REGULAÇÃO
P100 a P199
Ramps Rampas Rampas
P101
(3)
Initial voltage (%Un)
30 to 90 %
Tensión inicial (%Un)
30 a 90 %
Tensão inicial (%Un)
30 a 90 %
50
P102
(3)
Acceleration ramp time
1 to 999 s
Tiempo de la rampa de
aceleración
1 a 999 s
Tempo da rampa de
aceleração
1 a 999 s
20
P103 Deceleration Voltage Step
(% Un)
100 = Inactive
99...60
Escalón de tensión em la
desaceleración (%Un)
100 = Inactiva
99...60
Degrau de tensão na
desaceleração (% Un)
100 = Inativa
99...60
100
P104
(3)
Deceleration ramp time
0=Inactive
1 to 240 s
Tiempo de la rampa de
desaceleración
0 = Inactiva
1 a 240 s
Tempo da rampa de
desaceleração
0 = Inativa
1 a 240 s
0
P105 End Deceleration Voltage
(% Un)
30...55
Tensión Final de
Desaceleración (% Un)
30...55
Tensão Final de
Desaceleração (% Un)
30...55
30
Current Limitation Limitación de Corriente Limitação de Corrente
P110
(3)
Current limitation
(%In of the Soft-Starter)
30 to 500 %
Limitación de corriente
(%In del Arrancador Suave)
30 a 500 %
Limitação de corrente
(%In da Soft-Starter)
30 a 500 %
300
P111 Initial Current for Current
Ramp (%In of the Soft-
Starter)
30...500
Corriente Inicial para
Rampa de Corriente (% In
del Arrancador Suave)
30...500
Corrente Inicial para Rampa
de Corrente (% In da Soft-
Starter)
30...500
150
Par. English Español Português
Factory
Setting
P112 Time for the Current Ramp
(% of P102)
1...99
Tiempo para Rampa de
Corriente (% de P102)
1...99
Tempo para Rampa de
Corrente (% de P102)
1...99
20
CONFIGURATION
PARAMETERS
P200 to P299
PARÁMETROS DE
CONFIGURACIÓN
P200 a P299
PARÂMETROS DE
CONFIGURAÇÃO
P200 a P299
Generic Parameters Parámetros Genéricos Parâmetros Genéricos
P200 The password is
0 = Inactive
1 = Active
La clave esta
0 = Inactiva
1 = Activa
A senha está
0 = Inativa
1 = Ativa
1
P202 Type of Control
0=Voltage Ramp
1=Current Limit
2=Pump Control
3=No Function
4=Current Ramp
5=Direct Online (DOL)
Tipo de Control
0=Rampa de tensión
1=Limitación de corriente
2=Control de bombas
3=Sin Función
4=Rampa de Corriente
5=Arranque Directo
Tipo de Controle
0=Rampa de tensão
1=Limitação de corrente
2=Controle de bombas
3=Sem função
4=Rampa de corrente
5=Partida direta (DOL)
0
P203 Fan Control
0 = Fan is always OFF
1 = Fan is always ON
2 = Fan controlled by software
Control del ventilador
0 = Ventilador siempre apagado
1 = Ventilador siempre
encendido
2 = Ventilador controlado por
el software
Controle do ventilador
0 = Ventilador sempre
desligado
1 = Ventilador sempre ligado
2 = Ventilador controlado por
software
2
P204
(1)
Load parameters with
factory default values
0 = No function
1 = No function
2 = No function
3 = No function
4 = No function
5 = Loads factory default values
Carga parámetros con
valor padrón de fábrica
0 = Sin función
1 = Sin función
2 = Sin función
3 = Sin función
4 = Sin función
5 = Carga padrón de fábrica
Carrega parâmetros com
padrão de fábrica
0 = Sem função
1 = Sem função
2 = Sem função
3 = Sem função
4 = Sem função
5 = Carrega padrão de fábrica
0
P205 Reading parameter
selection
0 to 999
Selección del parámetro
de lectura
0 a 999
Seleção do parâmetro de
leitura
0 a 999
1
P206 Auto-reset time
3 to 1200 s
Tiempo de autoreset
3 a 1200 s
Tempo de Auto-Reset
3 a 1200 s
900
P207
(3)
Auto-reset
0 = Inactive
1 = Active
Autoreset
0 = Inactivo
1 = Activo
Auto-Reset
0 = Inativo
1 = Ativo
0
P215
(1)
Copy function
0 = Inactive
1 = SSW Keypad
2 = Keypad SSW
Función copy
0 = Inactiva
1 = SSW HMI
2 = HMI SSW
Função copy
0 = Inativa
1 = SSW HMI
2 = HMI SSW
0
P219 Parameterization via Keypad
/ (Trimpots and DIP Switch)
0=Trimpots and DIP Switch
1=Keypad
2=P202=2 / Trimpots and DIP
Parametrización vía HMI /
(Trimpots y DIP Switch)
0=Trimpots y DIP Switch
1=HMI
2=P202=2 / Trimpots y DIP
Parametrização via HMI /
(Trimpots e DIP Switch)
0=Trimpots e DIP Switch
1=HMI
2=P202=2 / Trimpots e DIP
0
Local/Remote Definition Definición de Local/Remoto Definição de Local/Remoto
P220
(1)
Local/remote supply
selection
0 = Always local
1 = Always remote
2 = Keypad (local default)
3 = Keypad (remote default)
4 = DI1 to DI3
5 = Serial (local default)
6 = Serial (remote default)
7 = Fieldbus (Default Local)
8 = Fieldbus (Default Remote)
Seleción de la fuente local/
remoto
0 = Siempre local
1 = Siempre remoto
2 = HMI (default local)
3 = HMI (default remoto)
4 = DI1 a DI3
5 = Serial (default local)
6 = Serial (default remoto)
7 = Fieldbus (Default Local)
8 = Fieldbus (Default Remoto)
Seleção da fonte local/
remoto
0 = Sempre local
1 = Sempre remoto
2 = HMI (default local)
3 = HMI (default remoto)
4 = DI1 a DI3
5 = Serial (default local)
6 = Serial (default remoto)
7 = Fieldbus (Default Local)
8 = Fieldbus (Default Remoto)
3
P229
(1)
Command selection – local
situation
0 = Keypad
1 = Digital Input DIx
2 = Serial
3 = Fieldbus
Seleción de los comandos -
situación local
0 = HMI
1 = Bornes
2 = Serial
3 = Fieldbus
Seleção de comandos –
situação local
0 = HMI
1 = Bornes
2 = Serial
3 = Fieldbus
0
P230
(1)
Command selection –
remote situation
0 = Keypad
1 = Digital Input DIx
2 = Serial
3 = Fieldbus
Seleción de los comandos -
situación remoto
0 = HMI
1 = Bornes
2 = Serial
3 = Fieldbus
Seleção de comandos –
situação remoto
0 = HMI
1 = Bornes
2 = Serial
3 = Fieldbus
1
Digital Inputs Entradas Digitales Entradas Digitais
P263 Digital Input DI1 Function
0=No Function
1=Start/Stop (two wires) or
Start (three wires)
2=Local/Remote
3=No External Fault
4=FWD/REV
5=Brake Off
6=Reset
7=No Function
8=Jog
Función entrada DI1
0=Sin función
1=Start/Stop (dos cables) o
Start (tres cables)
2=Local/Remoto
3=Sin error externo
4=Sentido de giro
5=Sin Frenado
6=Reset
7=Sin función
8=Jog
Função entrada DI1
0=Sem função
1=Start/Stop (dois fios) ou Start
(três fios)
2=Local/Remoto
3=Sem erro externo
4=Sentido de giro
5=Sem frenagem
6=Reset
7=Sem função
8=Jog
1
P264 Digital Input DI2 Function
0=No Function
1=Stop (three wires)
2=Local/Remote
3=No External Fault
4=FWD/REV
5=Brake Off
6=Reset
7=Emergency Start
8=Jog
Función entrada DI2
0=Sin función
1=Stop (tres cables)
2=Local/Remoto
3=Sin erro externo
4=Sentido de giro
5=Sin Frenado
6=Reset
7=Arranque de Emergencia
8=Jog
Função entrada DI2
0=Sem função
1=Stop (três fios)
2=Local/Remoto
3=Sem erro externo
4=Sentido de giro
5=Sem frenagem
6=Reset
7=Partida de emergência
8=Jog
6
P265 Digital Input DI3 Function
0=No Function
1=General Enabling
2=Local/Remote
3=No External Fault
4=FWD/REV
5=Brake Off
6=Reset
7=Emergency Start
8=Jog
Función entrada DI3
0=Sin función
1=Habilita general
2=Local/Remoto
3=Sin erro externo
4=Sentido de giro
5=Sin Frenado
6=Reset
7=Arranque de Emergencia
8=Jog
Função entrada DI3
0=Sem função
1=Habilita geral
2=Local/Remoto
3=Sem erro externo
4=Sentido de giro
5=Sem frenagem
6=Reset
7=Partida de emergência
8=Jog
6
Relay Outputs Salidas a Relé Saídas à Relé
P277 RL1 Relay Function
0=No Function
1=Running
2=Full Voltage
3=No Function
4=FWD/REV - K1
5=DC-Brake
6=No Fault
7=Fault
8=No Function
9=Serial
13 = Shunt Trip
Función Relé RL1
0=Sin función
1=En Funcionamiento
2=En Tensión Plena
3=Sin función
4=Sentido de giro K1
5=Frenado CC
6=Sin Error
7=Con Error
8=Sin función
9=Serial
13 = Grupo de Error
Função Relé RL1
0=Sem função
1=Em Funcionamento
2=Em Tensão Plena
3=Sem função
4=Sentido de giro K1
5=Frenagem CC
6=Sem Erro
7=Com Erro
8=Sem função
9=Serial
13 = Grupo de Erros
1
P278 RL2 Relay Function
0=No Function
1=Running
2=Full Voltage
3=No Function
4=FWD/REV - K2
5=DC-Brake
6=No Fault
7=Fault
8=No Function
9=Serial
13 = Shunt Trip
Función Relé RL2
0=Sin función
1=En Funcionamiento
2=En Tensión Plena
3=Sin función
4=Sentido de giro K2
5=Frenado CC
6=Sin Error
7=Con Error
8=Sin función
9=Serial
13 = Grupo de Error
Função Relé RL2
0=Sem função
1=Em Funcionamento
2=Em Tensão Plena
3=Sem função
4=Sentido de giro K2
5=Frenagem CC
6=Sem Erro
7=Com Erro
8=Sem função
9=Serial
13 = Grupo de Erros
2
SSW-07 / SSW-08 Quick Parameter Reference
Referência Rápida de los Parámetros SSW-07 / SSW-08
Referência Rápida dos Parâmetros SSW-07 / SSW-08
10000506541 / 02
Software V1.5X
English Español Português
E03 Phase loss or undercurrent Falta de Fase o Subcorriente Falta de Fase ou Subcorrente
E04 Overtemperature on power Sobretemperatura en la potencia Sobretemperatura na potência
E05 Overload on motor Sobrecarga en el motor Sobrecarga no motor
E06 External fault (DI) Error externo (DI) Erro externo (DI)
E10 Function copy fault Error en la función copy Erro na função copy
E19 SSW short circuit Cortocircuito en la SSW Curto-circuito na SSW
E24 Programming fault Error de programación Erro de programação
E28
Timeout fault at telegram
reception
Error de timeout en la recepción
de los telegramas
Erro de timeout na recepção de
telegramas
E31 Keypad connection failure Fallo en la conexión de la HMI Falha na conexão da HMI
E62 Current limitation start timeout
Exceso de tiempo de limitación
de corriente durante el arranque
Excesso de tempo de limitação
de corrente durante a partida
E63 Stall Rotor bloqueado Rotor bloqueado
E66 Overcurrent Sobrecorriente Sobrecorrente
E67 Inverted phase sequence Secuencia de fase invertida Seqüência de fase invertida
E70
Undervoltage at electronic
supply
Subtensión en la alimentación
de la electrónica
Subtensão na alimentação da
eletrônica
E71 By-pass contact open Contacto del By-pass abierto Contato do By-pass aberto
E72 Overcurrent before By-pass
Sobrecorriente antes del
By-pass
Sobrecorrente antes do By-pass
E74 Current imbalance Desbalanceo de corriente Desbalanceamento de corrente
E75
Power supply frequency out of
allowed range
Frecuencia de la red de
alimentación fuera del rango
permitido
Freqüência da rede de
alimentação fora da faixa
permitida
E76
Overcurrent before closing
By-pass
Subcorriente antes del cierre del
By-pass
Subcorrente antes do
fechamento do By-pass
E77
Closed by-pass contact or
shorted SCR’s
Contactor de By-pass cerrado o
SCRs en cortocircuito
Contato de By-pass fechado ou
SCRs em curto-circuito
Fault Messages / Mensajes de Error / Mensagens de Erro
(1) Changeable parameters only when the motor is disabled.
Solamente se permite modificar el valor del parámetro con el motor parado.
Parâmetros alteráveis somente com motor parado.
(2) Unchanged parameters at factory default settings (P204=5).
No cambia el valor del parámetro cuando se ejecuta el comando cargar valores padrón de fábrica (P204 = 5).
Parâmetros não alterados no padrão de fábrica (P204 = 5).
(3) Changeable parameters only in keypad mode (P219=1). If P219=0 the parameters are read only.
Se permite modificar el parámetro solamente en el modo HMI (P219 = 1). Con P219 = 0 los parámetros son
considerados del tipo lectura.
Parâmetros alteráveis somente em modo HMI (P219 = 1). Com P219 = 0 os parâmetros são considerados do
tipo leitura.
To get the detailed description of the parameters, consult the Programming Manual. This manual is supplied in
electronic format on CD-ROM and at WEG’s web site: www.weg.net
Para obtener la descripción detallada de los parámetros, consulte el Manual de Programación. Este manual es
suministrado en formato electrónico en CD-ROM y en la pagina web de WEG www.weg.net
Para obter a descrição detalhada dos parâmetros, consulte o Manual de Programação. Este manual é fornecido
em formato eletrônico no CD-ROM e no site da WEG www.weg.net
Par. English Español Português
Factory
Setting
Soft-Starter Data
Datos del Arrancador
Suave
Dados da Soft-Starter
P295
(1)(2)
Nominal current
0 = 1.7 A
1 = 17 A
2 = 24 A
3 = 30 A
4 = 45 A
5 = 61 A
6 = 85 A
7 = 130 A
8 = 171 A
9 = 200 A
10 = 255 A
11 = 312 A
12 = 365 A
13 = 412 A
Corriente nominal
0 = 1.7 A
1 = 17 A
2 = 24 A
3 = 30 A
4 = 45 A
5 = 61 A
6 = 85 A
7 = 130 A
8 = 171 A
9 = 200 A
10 = 255 A
11 = 312 A
12 = 365 A
13 = 412 A
Corrente nominal
0 = 1.7 A
1 = 17 A
2 = 24 A
3 = 30 A
4 = 45 A
5 = 61 A
6 = 85 A
7 = 130 A
8 = 171 A
9 = 200 A
10 = 255 A
11 = 312 A
12 = 365 A
13 = 412 A
-
COMMUNICATION
PARAMETERS
P300 to P399
PARÁMETROS DE
COMUNICACIÓN
P300 a P399
PARÂMETROS DE
COMUNICAÇÃO
P300 a P399
Serial Communication Comunicación Serial Comunicação Serial
P308
(1)(2)
Soft-Starter address
1 to 247
Dirección del Arrancador
Suave
1 a 247
Endereço da Soft-Starter
1 a 247
1
P312
(1)(2)
Type of protocol and
serial communication
transmission rate
1 = Modbus 9600 bps no
parity
2 = Modbus 9600 bps odd
3 = Modbus 9600 bps even
4 = Modbus 19200 bps no
parity
5 = Modbus 19200 bps odd
6 = Modbus 19200 bps even
7 = Modbus 38400 bps no
parity
8 = Modbus 38400 bps odd
9 = Modbus 38400 bps even
Tipo de protocolo y tasa de
transmisión de la
comunicación serial
1 = Modbus 9600 bps sin
paridad
2 = Modbus 9600 bps impar
3 = Modbus 9600 bps par
4 = Modbus 19200 bps sin
paridad
5 = Modbus 19200 bps impar
6 = Modbus 19200 bps par
7 = Modbus 38400 bps sin
paridad
8 = Modbus 38400 bps impar
9 = Modbus 38400 bps par
Tipo de protocolo e taxa de
transmissão da
comunicação serial
1 = Modbus 9600 bps sem
paridade
2 = Modbus 9600 bps impar
3 = Modbus 9600 bps par
4 = Modbus 19200 bps sem
paridade
5 = Modbus 19200 bps impar
6 = Modbus 19200 bps par
7 = Modbus 38400 bps sem
paridade
8 = Modbus 38400 bps impar
9 = Modbus 38400 bps par
1
P313 Serial communication error
action (E28)
0 = Inactive
1 = Disable
2 = General disable
3 = Change to local
Acción del error de
comunicación serial (E28)
0 = Inactiva
1 = Deshabilita
2 = Deshabilita General
3 = Se va para local
Ação do erro de
comunicação serial (E28)
0 = Inativa
1 = Desabilita
2 = Desabilita geral
3 = Vai para local
1
P314
(1)
Serial communication
verification time
0 = Inactive
1 to 999 s
Tiempo de verificación de
la comunicación serial
0 = Inactiva
1 a 999 s
Tempo de verificação da
comunicação serial
0 = Inativa
1 a 999 s
0
Fieldbus Communication Comunicación Fieldbus Comunicação Fieldbus
P331 CAN Address
0 to 63
Dirección CAN
0 a 63
Endereço CAN
0 a 63
63
P332 CAN Baud Rate
0 = 125 Kbps
1 = 250 Kbps
2 = 500 Kbps
3 = Autobaud
Tasa Comunicación CAN
0 = 125 Kbps
1 = 250 Kbps
2 = 500 Kbps
3 = Autobaud
Taxa Comunicação CAN
0 = 125 Kbps
1 = 250 Kbps
2 = 500 Kbps
3 = Autobaud
3
P333 Bus Off Reset
0 = Manual
1 = Automatic
Reset de Bus Off
0 = Manual
1 = Automático
Reset de Bus Off
0 = Manual
1 = Automático
0
P335 DeviceNet I/O Instances
0 = ODVA
1 = WEG Specific 1 W
2 = WEG Specific 2 W
3 = WEG Specific 3 W
4 = WEG Specific 4 W
5 = WEG Specific 5 W
6 = WEG Specific 6 W
7 = WEG Specific 7 W
Instancias I/O Dnet
0 = ODVA
1 = Especif. WEG 1 W
2 = Especif. WEG 2 W
3 = Especif. WEG 3 W
4 = Especif. WEG 4 W
5 = Especif. WEG 5 W
6 = Especif. WEG 6 W
7 = Especif. WEG 7 W
Instâncias I/O Dnet
0 = ODVA
1 = Especif. WEG 1 W
2 = Especif. WEG 2 W
3 = Especif. WEG 3 W
4 = Especif. WEG 4 W
5 = Especif. WEG 5 W
6 = Especif. WEG 6 W
7 = Especif. WEG 7 W
0
P336 DeviceNet Reading Word #2
0 to 999
Lectura #2 Dnet
0 a 999
Leitura #2 Dnet
0 a 999
0
P337 DeviceNet Reading Word #3
0 to 999
Lectura #3 Dnet
0 a 999
Leitura #3 Dnet
0 a 999
0
P338 DeviceNet Reading Word #4
0 to 999
Lectura #4 Dnet
0 a 999
Leitura #4 Dnet
0 a 999
0
P339 DeviceNet Reading Word #5
0 to 999
Lectura #5 Dnet
0 a 999
Leitura #5 Dnet
0 a 999
0
P340 DeviceNet Reading Word #6
0 to 999
Lectura #6 Dnet
0 a 999
Leitura #6 Dnet
0 a 999
0
P341 DeviceNet Reading Word #7
0 to 999
Lectura #7 Dnet
0 a 999
Leitura #7 Dnet
0 a 999
0
P342 DeviceNet Writing Word #2
0 to 999
Escrita #2 Dnet
0 a 999
Escrita #2 Dnet
0 a 999
0
P343 DeviceNet Writing Word #3
0 to 999
Escrita #3 Dnet
0 a 999
Escrita #3 Dnet
0 a 999
0
P344 DeviceNet Writing Word #4
0 to 999
Escrita #4 Dnet
0 a 999
Escrita #4 Dnet
0 a 999
0
P345 DeviceNet Writing Word #5
0 to 999
Escrita #5 Dnet
0 a 999
Escrita #5 Dnet
0 a 999
0
P346 DeviceNet Writing Word #6
0 to 999
Escrita #6 Dnet
0 a 999
Escrita #6 Dnet
0 a 999
0
P347 DeviceNet Writing Word #7
0 to 999
Escrita #7 Dnet
0 a 999
Escrita #7 Dnet
0 a 999
0
P348 Fieldbus communication
error action
0 = Inactive
1 = Disable
2 = General Disable
3 = Change to local
Acción del error de
comunicación Fieldbus
0 = Inactiva
1 = Deshabilita
2 = Deshabilita General
3 = Se va para local
Ação do erro de
Comunicação Fieldbus
0 = Inativa
1 = Desabilita
2 = Desabilita Geral
3 = Vai para local
1
MOTOR PARAMETERS
P400 to P499
PARÁMETROS DEL MOTOR
P400 a P499
PARÂMETROS DO
MOTOR P400 a P499
Nominal Parameters Parámetros Nominales Parâmetros Nominais
P400
(1)
Motor nominal voltage
1 to 999 V
Tensión nominal del motor
1 a 999 V
Tensão nominal do motor
1 a 999 V
380
P401
(1)(3)
Motor current setting
30.0 to 100.0 %
Ajuste de la corriente del
motor
30.0 a 100.0 %
Ajuste da corrente do motor
30.0 a 100.0 %
100.0
P406
(1)
Service factor
1.00 to 1.50
Factor de servicio
1.00 a 1.50
Fator de serviço
1.00 a 1.50
1.00
SPECIAL FUNCTIONS
PARAMETERS
P500 to P599
PARÁMETROS DE LAS
FUNCIONES ESPECIALES
P500 a P599
PARÂMETROS DAS
FUNÇÕES ESPECIAIS
P500 a P599
Braking Frenado Frenagem
P501 DC Braking Time
0...299
0=Inactive
Tiempo de Frenado
0...299
0=Inactivo
Tempo de Frenagem
0...299
0=Inativo
0
P502 DC Braking Voltage Level
30...70
Nivel de Frenadol
30...70
Nível da Frenagem
30...70
30
P510 Jog
0=Inactive
1=Active
Jog
0=Inactivo
1=Activo
Jog
0=Inativo
1=Ativo
0
P511 Jog Level
30...70
Nivel do Jog
30...70
Nível do Jog
30...70
30
Kick Start Kick Start Kick Start
P520
(1)(3)
Voltage pulse at start
(Kick Start)
0 = Inactive
1 = Active
Pulso de tensión en el
arranque (Kick Start)
0 = Inactiva
1 = Ativa
Pulso de tensão na partida
(Kick Start)
0 = Inativa
1 = Ativa
0
P521
(3)
Pulse time at start
0.2 to 2.0 s
Tiempo del pulso en el
arranque
0.2 a 2.0 s
Tempo do pulso na partida
0.2 a 2.0 s
0.2
P522 Voltage pulse level at start
(%Un)
70 to 90 %
Nivel del pulso de tensión
en el arranque (%Un)
70 a 90 %
Nível do pulso de tensão na
partida (%Un)
70 a 90 %
80
Par. English Español Português
Factory
Setting
PROTECTION
PARAMETERS
P600 to P699
PARÁMETROS DE
PROTECCIÓN
P600 a P699
PARÂMETROS DE
PROTEÇÃO
P600 a P699
Current Protections Protecciones de Corriente Proteções de Corrente
P610
(1)
Phase Loss or Immediate
Undercurrent
(% In of the Motor)
1 to 80 %
Falta de fase o
Subcorriente Inmediata
(% In del Motor)
1 a 80 %
Falta de Fase ou
Subcorrente
Imediata (% In do Motor)
1 a 80 %
80
P611
(1)(3)
Immediate undercurrent
time or phase loss
0 = Inactive
1 to 99 s
Tiempo de subcorriente
inmediata o falta de fase
0 = Inactiva
1 a 99 s
Tempo de subcorrente
imediata ou falta de fase
0 = Inativa
1 a 99 s
1
P612
(1)
Immediate overcurrent (%In
of motor)
1 to 200 %
Sobrecorriente inmediata
(%In del motor)
1 a 200 %
Sobrecorrente imediata
(%In do motor)
1 a 200 %
100
P613
(1)(3)
Immediate overcurrent time
0 = Inactive
1 to 99 s
Tempo de sobrecorrente
imediata
0 = Inactiva
1 a 99 s
Tempo de sobrecorrente
imediata
0 = Inativa
1 a 99 s
1
P614
(1)
Current imbalance between
phases (%In of motor)
0 to 30 %
Desbalanceo de corriente)
entre fases (%In del motor)
0 a 30 %
Desbalanceamento de
corrente entre fases
(%In do motor)
0 a 30 %
15
P615
(1)
Current imbalance time
between phases
0 = Inactive
1 to 99 s
Tiempo de desbalanceo de
corriente entre fases
0 = Inactiva
1 a 99 s
Tempo de
desbalanceamento de
corrente entre fases
0 = Inativa
1 a 99 s
0
P616
(1)
Undercurrent before
By-Pass closing
0 = Inactive
1 = Active
Subcorriente antes del
cierre del By-pass
0 = Inactiva
1 = Activa
Subcorrente antes do
fechamento do By-pass
0 = Inativa
1 = Ativa
0
P617
(1)(3)
Blocked Rotor
0 = Inactive
1 = Active
Rotor Bloqueado
0 = Inactiva
1 = Activa
Rotor Bloqueado
0 = Inativa
1 = Ativa
1
Phase Sequence Secuencia de Fase Seqüência de Fase
P620
(1)(3)
RST phase sequence
0 = Inactive
1 = Active
Secuencia de fase RST
0 = Inactiva
1 = Activa
Seqüência de fase RST
0 = Inativa
1 = Ativa
1
P621 E77 Enabling
0=Inactive
1=Active
Habilitación E77
0=Inactivo
1=Activo
Habilitação E77
0=Inativo
1=Ativo
1
SSW Short Circuit Detection Detección de Cortocircuito
en la SSW
Detecção de Curto Circuito
na SSW
P622
(1)
SSW short circuit
0 = Inactive
1 = Active
Cortocircuito en la SSW
0 = Inactivo
1 = Activo
Curto-circuito na SSW
0 = Inativo
1 = Ativo
0
Interval Between Starts Intervalo entre Partidas Intervalo entre Partidas
P630 Time interval after stopping
2 to 999 s
Intervalo de tiempo luego
de la parada
2 a 999 s
Intervalo de tempo após
parada
2 a 999 s
2
Motor Thermal Protection
Protección Térmica
del Motor
Proteção Térmica do Motor
P640
(1)(3)
Motor protection thermal
class
0 = Inactive
1 = 5
2 = 10
3 = 15
4 = 20
5 = 25
6 = 30
Clase térmica de
protección del motor
0 = Inactiva
1 = 5
2 = 10
3 = 15
4 = 20
5 = 25
6 = 30
Classe térmica de proteção
do motor
0 = Inativa
1 = 5
2 = 10
3 = 15
4 = 20
5 = 25
6 = 30
6 = 30
P641
(1)
Thermal memory auto-reset
0 = Inactive
1 to 600 s
Autoreset de la memoria
térmica
0 = Inactiva
1 a 600 s
Auto-reset da memória
térmica
0 = Inativa
1 a 600 s
0

Transcripción de documentos

SSW-07 / SSW-08 Quick Parameter Reference Referência Rápida de los Parámetros SSW-07 / SSW-08 Referência Rápida dos Parâmetros SSW-07 / SSW-08 Par. P112 10000506541 / 02 Software V1.5X Par. P000 P001 P002 P003 P005 P006 P007 P011 P012 P013 P014 P015 P016 P017 P020 P023 P030 P031 P032 P050 P081 P090 P091 P092 P093 P094 P095 P096 P101(3) P102(3) P103 P104(3) P105 P110(3) P111 English Access to parameters 0 to 9999 READ ONLY PARAMETERS P001 to P099 Motor current %In of SSW-07/SSW-08 0.0 to 999.9 % Motor current %In of Motor 0.0 to 999.9 % Motor current 0.0 to 6553 A Power supply frequency 0.0 to 99.9 Hz Soft-Starter Status 0 = rdy - ready 2 = Exx - Error 3 = ruP - Ramp Up 5 = PASS - By-pass 7 = rdo - Ramp Down 8 = br - Braking 9 = rEv - FWD/REV 10 = JoG - Jog 11 = dly - Delay P630 12 = G.di - General Disable Voltage imposed by the Soft-Starter over the load (%Un) 0 to 100 % Apparent output power 0.0 to 999.9 kVA DI1 to DI3 status 0 = Inactive 1 = Active Relay RL1 and RL2 output status 0 = Inactive 1 = Active Last fault occurred E00 to E77 Second fault occurred E00 to E77 Third fault occurred E00 to E77 Fourth fault occurred E00 to E77 Actual Fault 0...99 Software version Phase R current 0.0 to 6553 A Phase S current 0.0 to 6553 A Phase T current 0.0 to 6553 A Motor thermal protection status 0 to 250 % Heatsink temperature 10.0 to 110.0 ºC CAN Controller Status 0 = Inactive 1 = Autobaud 2 = Active CAN Interface 3 = Warning 4 = Error passive 5 = Bus off 6 = No Bus Power DeviceNet Network Status 0 = Offline 1 = Online, Not Connected 2 = Online, Connected 3 = Expire Connection 4 = Connection Failure 5 = Auto-Baud DeviceNet Master Status 0 = Run 1 = Idle Received CAN Telegram Counter 0 to 9999 Transmitted CAN Telegram Counter 0 to 9999 Buss Off Error Counter 0 to 9999 Lost CAN Message Counter 0 to 9999 REGULATION PARAMETERS P100 to P199 Ramps Initial voltage (%Un) 30 to 90 % Acceleration ramp time 1 to 999 s Deceleration Voltage Step (% Un) 100 = Inactive 99...60 Deceleration ramp time 0=Inactive 1 to 240 s End Deceleration Voltage (% Un) 30...55 Current Limitation Current limitation (%In of the Soft-Starter) 30 to 500 % Initial Current for Current Ramp (%In of the SoftStarter) 30...500 P200 Español Português Acceso a los parámetros Acesso aos parâmetros 0 a 9999 0 a 9999 PARÁMETROS DE PARÂMETROS DE LEITURA LECTURA P001 a P099 P001 a P099 Corriente del motor %In del Corrente do motor %In da SSW-07/SSW-08 SSW-07/SSW-08 0.0 a 999.9 % 0.0 a 999.9 % Corriente del motor %In Corrente do motor %In do del Motor Motor 0.0 a 999.9 % 0.0 a 999.9 % Corriente del motor Corrente do motor 0.0 a 6553 A 0.0 a 6553 A Frecuencia de la red de Freqüência da rede de alimentación alimentação 0.0 a 99.9 Hz 0.0 a 99.9 Hz Estado del Arrancador Estado da Soft-Starter Suave 0 = rdy - ready 0 = rdy - ready 2 = Exx - Error 2 = Exx - Error 3 = ruP - Ramp p 3 = ruP - Ramp p 5 = PASS - By-pass 5 = PASS - By-pass 7 = rdo - Ramp Down 7 = rdo - Ramp Down 8 = br - Braking 8 = br - Braking 9 = rEv - FWD/REV 9 = rEv - FWD/REV 10 = JoG - Jog 10 = JoG - Jog 11 = dly - Delay P630 11 = dly - Delay P630 12 = G.di - General Disable 12 = G.di - General Disable Tensión impueta por el Tensão imposta pela chave Arrancador sobre la carga sobre à carga (%Un) (%Un) 0 a 100 % 0 a 100 % Potencia aparente de salida Potência aparente de saída 0.0 a 999.9 kVA 0.0 a 999.9 kVA Estado DI1 a DI3 Estado DI1 a DI3 0 = Inactiva 0 = Inativa 1 = Activa 1 = Ativa Estado de las salidas a relé Estado das saídas a relé RL1 y RL2 RL1 e RL2 0 = Inactiva 0 = Inativa 1 = Activa 1 = Ativa Ultimo error ocurrido Último erro ocorrido E00 a E77 E00 a E77 Segundo error ocurrido Segundo erro ocorrido E00 a E77 E00 a E77 Tercero error ocurrido Terceiro erro ocorrido E00 a E77 E00 a E77 Cuarto error ocurrido Quarto erro ocorrido E00 a E77 E00 a E77 Actual Error Erro Atual 0...99 0...99 Versión de software Versão de software Corriente de la fase R Corrente da fase R 0.0 a 6553 A 0.0 a 6553 A Corriente de la fase S Corrente da fase S 0.0 a 6553 A 0.0 a 6553 A Corriente de la fase T Corrente da fase T 0.0 a 6553 A 0.0 a 6553 A Estado de la proteccíon Estado da proteção térmica térmica del motor do motor 0 a 250 % 0 a 250 % Temperatura del disipador Temperatura do dissipador 10.0 a 110.0 ºC 10.0 a 110.0 ºC Estado del controlador CAN Estado controlador CAN 0 = Inactivo 0 = Inativo 1 = Autobaud 1 = Autobaud 2 = CAN ativo 2 = CAN ativo 3 = Warning 3 = Warning 4 = Error passive 4 = Error passive 5 = Bus off 5 = Bus off 6 = No alimentado 6 = Não alimentado Estado Rede DeviceNet Estado Rede DeviceNet 0 = Offline 0 = Offline 1 = OnLine, No conectado 1 = OnLine, Não conectado 2 = OnLine, Conectado 2 = OnLine, Conectado 3 = Conexión Caduco 3 = Conexão Expirou 4 = Falla Conexión 4 = Falha Conexão 5 = Auto-Baud 5 = Auto-Baud Factory Setting P202 0 (5) - P203 - P204(1) - P205 P206 - - - - Estado Maestro DeviceNet 0 = Run 1 = Idle Telegramas CAN RX 0 a 9999 Estado Mestre DeviceNet 0 = Run 1 = Idle Telegramas CAN RX 0 a 9999 - Telegramas CAN TX 0 a 9999 Telegramas CAN TX 0 a 9999 - Contador de Bus Off 0 a 9999 Mensajes CAN perdidas 0 a 9999 PARÁMETROS DE REGULACIÓN P100 a P199 Rampas Tensión inicial (%Un) 30 a 90 % Tiempo de la rampa de aceleración 1 a 999 s Escalón de tensión em la desaceleración (%Un) 100 = Inactiva 99...60 Tiempo de la rampa de desaceleración 0 = Inactiva 1 a 240 s Tensión Final de Desaceleración (% Un) 30...55 Limitación de Corriente Limitación de corriente (%In del Arrancador Suave) 30 a 500 % Corriente Inicial para Rampa de Corriente (% In del Arrancador Suave) 30...500 Contador de Bus Off 0 a 9999 Mensagens CAN perdidas 0 a 9999 PARÂMETROS DE REGULAÇÃO P100 a P199 Rampas Tensão inicial (%Un) 30 a 90 % Tempo da rampa de aceleração 1 a 999 s Degrau de tensão na desaceleração (% Un) 100 = Inativa 99...60 Tempo da rampa de desaceleração 0 = Inativa 1 a 240 s Tensão Final de Desaceleração (% Un) 30...55 Limitação de Corrente Limitação de corrente (%In da Soft-Starter) 30 a 500 % Corrente Inicial para Rampa de Corrente (% In da SoftStarter) 30...500 - - - 50 20 100 0 30 300 150 Português Factory Setting Tiempo para Rampa de Corriente (% de P102) 1...99 PARÁMETROS DE CONFIGURACIÓN P200 a P299 Parámetros Genéricos La clave esta 0 = Inactiva 1 = Activa Tipo de Control 0=Rampa de tensión 1=Limitación de corriente 2=Control de bombas 3=Sin Función 4=Rampa de Corriente 5=Arranque Directo Control del ventilador 0 = Ventilador siempre apagado 1 = Ventilador siempre encendido 2 = Ventilador controlado por el software Load parameters with Carga parámetros con factory default values valor padrón de fábrica 0 = No function 0 = Sin función 1 = No function 1 = Sin función 2 = No function 2 = Sin función 3 = No function 3 = Sin función 4 = No function 4 = Sin función 5 = Loads factory default values 5 = Carga padrón de fábrica Tempo para Rampa de Corrente (% de P102) 1...99 PARÂMETROS DE CONFIGURAÇÃO P200 a P299 Parâmetros Genéricos A senha está 0 = Inativa 1 = Ativa Tipo de Controle 0=Rampa de tensão 1=Limitação de corrente 2=Controle de bombas 3=Sem função 4=Rampa de corrente 5=Partida direta (DOL) Controle do ventilador 0 = Ventilador sempre desligado 1 = Ventilador sempre ligado 2 = Ventilador controlado por software Carrega parâmetros com padrão de fábrica 0 = Sem função 1 = Sem função 2 = Sem função 3 = Sem função 4 = Sem função 5 = Carrega padrão de fábrica 20 Reading parameter selection 0 to 999 Auto-reset time 3 to 1200 s Seleção do parâmetro de leitura 0 a 999 Tempo de Auto-Reset 3 a 1200 s 1 English Español Time for the Current Ramp (% of P102) 1...99 CONFIGURATION PARAMETERS P200 to P299 Generic Parameters The password is 0 = Inactive 1 = Active Type of Control 0=Voltage Ramp 1=Current Limit 2=Pump Control 3=No Function 4=Current Ramp 5=Direct Online (DOL) Fan Control 0 = Fan is always OFF 1 = Fan is always ON 2 = Fan controlled by software Selección del parámetro de lectura 0 a 999 Tiempo de autoreset 3 a 1200 s P207(3) Auto-reset Autoreset Auto-Reset 0 = Inactive 0 = Inactivo 0 = Inativo 1 = Active 1 = Activo 1 = Ativo P215(1) Copy function Función copy Função copy 0 = Inactive 0 = Inactiva 0 = Inativa 1 = SSW → Keypad 1 = SSW → HMI 1 = SSW → HMI 2 = Keypad → SSW 2 = HMI → SSW 2 = HMI → SSW P219 Parameterization via Keypad Parametrización vía HMI / Parametrização via HMI / / (Trimpots and DIP Switch) (Trimpots y DIP Switch) (Trimpots e DIP Switch) 0=Trimpots and DIP Switch 0=Trimpots y DIP Switch 0=Trimpots e DIP Switch 1=Keypad 1=HMI 1=HMI 2=P202=2 / Trimpots and DIP 2=P202=2 / Trimpots y DIP 2=P202=2 / Trimpots e DIP Local/Remote Definition Definición de Local/Remoto Definição de Local/Remoto P220(1) Local/remote supply Seleción de la fuente local/ Seleção da fonte local/ selection remoto remoto 0 = Always local 0 = Siempre local 0 = Sempre local 1 = Always remote 1 = Siempre remoto 1 = Sempre remoto 2 = Keypad (local default) 2 = HMI (default local) 2 = HMI (default local) 3 = Keypad (remote default) 3 = HMI (default remoto) 3 = HMI (default remoto) 4 = DI1 to DI3 4 = DI1 a DI3 4 = DI1 a DI3 5 = Serial (local default) 5 = Serial (default local) 5 = Serial (default local) 6 = Serial (remote default) 6 = Serial (default remoto) 6 = Serial (default remoto) 7 = Fieldbus (Default Local) 7 = Fieldbus (Default Local) 7 = Fieldbus (Default Local) 8 = Fieldbus (Default Remote) 8 = Fieldbus (Default Remoto) 8 = Fieldbus (Default Remoto) P229(1) Command selection – local Seleción de los comandos - Seleção de comandos – situation situación local situação local 0 = Keypad 0 = HMI 0 = HMI 1 = Digital Input DIx 1 = Bornes 1 = Bornes 2 = Serial 2 = Serial 2 = Serial 3 = Fieldbus 3 = Fieldbus 3 = Fieldbus (1) P230 Command selection – Seleción de los comandos - Seleção de comandos – remote situation situación remoto situação remoto 0 = Keypad 0 = HMI 0 = HMI 1 = Digital Input DIx 1 = Bornes 1 = Bornes 2 = Serial 2 = Serial 2 = Serial 3 = Fieldbus 3 = Fieldbus 3 = Fieldbus Digital Inputs Entradas Digitales Entradas Digitais P263 Digital Input DI1 Function Función entrada DI1 Função entrada DI1 0=No Function 0=Sin función 0=Sem função 1=Start/Stop (two wires) or 1=Start/Stop (dos cables) o 1=Start/Stop (dois fios) ou Start Start (three wires) Start (tres cables) (três fios) 2=Local/Remote 2=Local/Remoto 2=Local/Remoto 3=No External Fault 3=Sin error externo 3=Sem erro externo 4=FWD/REV 4=Sentido de giro 4=Sentido de giro 5=Brake Off 5=Sin Frenado 5=Sem frenagem 6=Reset 6=Reset 6=Reset 7=No Function 7=Sin función 7=Sem função 8=Jog 8=Jog 8=Jog P264 Digital Input DI2 Function Función entrada DI2 Função entrada DI2 0=No Function 0=Sin función 0=Sem função 1=Stop (three wires) 1=Stop (tres cables) 1=Stop (três fios) 2=Local/Remote 2=Local/Remoto 2=Local/Remoto 3=No External Fault 3=Sin erro externo 3=Sem erro externo 4=FWD/REV 4=Sentido de giro 4=Sentido de giro 5=Brake Off 5=Sin Frenado 5=Sem frenagem 6=Reset 6=Reset 6=Reset 7=Emergency Start 7=Arranque de Emergencia 7=Partida de emergência 8=Jog 8=Jog 8=Jog P265 Digital Input DI3 Function Función entrada DI3 Função entrada DI3 0=No Function 0=Sin función 0=Sem função 1=General Enabling 1=Habilita general 1=Habilita geral 2=Local/Remote 2=Local/Remoto 2=Local/Remoto 3=No External Fault 3=Sin erro externo 3=Sem erro externo 4=FWD/REV 4=Sentido de giro 4=Sentido de giro 5=Brake Off 5=Sin Frenado 5=Sem frenagem 6=Reset 6=Reset 6=Reset 7=Emergency Start 7=Arranque de Emergencia 7=Partida de emergência 8=Jog 8=Jog 8=Jog Relay Outputs Salidas a Relé Saídas à Relé P277 RL1 Relay Function Función Relé RL1 Função Relé RL1 0=No Function 0=Sin función 0=Sem função 1=Running 1=En Funcionamiento 1=Em Funcionamento 2=Full Voltage 2=En Tensión Plena 2=Em Tensão Plena 3=No Function 3=Sin función 3=Sem função 4=FWD/REV - K1 4=Sentido de giro K1 4=Sentido de giro K1 5=DC-Brake 5=Frenado CC 5=Frenagem CC 6=No Fault 6=Sin Error 6=Sem Erro 7=Fault 7=Con Error 7=Com Erro 8=No Function 8=Sin función 8=Sem função 9=Serial 9=Serial 9=Serial 13 = Shunt Trip 13 = Grupo de Error 13 = Grupo de Erros P278 RL2 Relay Function Función Relé RL2 Função Relé RL2 0=No Function 0=Sin función 0=Sem função 1=Running 1=En Funcionamiento 1=Em Funcionamento 2=Full Voltage 2=En Tensión Plena 2=Em Tensão Plena 3=No Function 3=Sin función 3=Sem função 4=FWD/REV - K2 4=Sentido de giro K2 4=Sentido de giro K2 5=DC-Brake 5=Frenado CC 5=Frenagem CC 6=No Fault 6=Sin Error 6=Sem Erro 7=Fault 7=Con Error 7=Com Erro 8=No Function 8=Sin función 8=Sem função 9=Serial 9=Serial 9=Serial 13 = Shunt Trip 13 = Grupo de Error 13 = Grupo de Erros 1 0 2 0 900 0 0 0 3 0 1 1 6 6 1 2 Par. English Soft-Starter Data P295(1)(2) Nominal current 0 = 1.7 A 1 = 17 A 2 = 24 A 3 = 30 A 4 = 45 A 5 = 61 A 6 = 85 A 7 = 130 A 8 = 171 A 9 = 200 A 10 = 255 A 11 = 312 A 12 = 365 A 13 = 412 A COMMUNICATION PARAMETERS P300 to P399 Serial Communication P308(1)(2) Soft-Starter address 1 to 247 P312(1)(2) Type of protocol and serial communication transmission rate 1 = Modbus 9600 bps no parity 2 = Modbus 9600 bps odd 3 = Modbus 9600 bps even 4 = Modbus 19200 bps no parity 5 = Modbus 19200 bps odd 6 = Modbus 19200 bps even 7 = Modbus 38400 bps no parity 8 = Modbus 38400 bps odd 9 = Modbus 38400 bps even P313 Serial communication error action (E28) 0 = Inactive 1 = Disable 2 = General disable 3 = Change to local P314(1) Serial communication verification time 0 = Inactive 1 to 999 s Fieldbus Communication P331 CAN Address 0 to 63 P332 CAN Baud Rate 0 = 125 Kbps 1 = 250 Kbps 2 = 500 Kbps 3 = Autobaud P333 Bus Off Reset 0 = Manual 1 = Automatic P335 DeviceNet I/O Instances 0 = ODVA 1 = WEG Specific 1 W 2 = WEG Specific 2 W 3 = WEG Specific 3 W 4 = WEG Specific 4 W 5 = WEG Specific 5 W 6 = WEG Specific 6 W 7 = WEG Specific 7 W P336 DeviceNet Reading Word #2 0 to 999 P337 DeviceNet Reading Word #3 0 to 999 P338 DeviceNet Reading Word #4 0 to 999 P339 DeviceNet Reading Word #5 0 to 999 P340 DeviceNet Reading Word #6 0 to 999 P341 DeviceNet Reading Word #7 0 to 999 P342 DeviceNet Writing Word #2 0 to 999 P343 DeviceNet Writing Word #3 0 to 999 P344 DeviceNet Writing Word #4 0 to 999 P345 DeviceNet Writing Word #5 0 to 999 P346 DeviceNet Writing Word #6 0 to 999 P347 DeviceNet Writing Word #7 0 to 999 P348 Fieldbus communication error action 0 = Inactive 1 = Disable 2 = General Disable 3 = Change to local MOTOR PARAMETERS P400 to P499 Nominal Parameters (1) P400 Motor nominal voltage 1 to 999 V P401(1)(3) Motor current setting 30.0 to 100.0 % P406(1) Service factor 1.00 to 1.50 SPECIAL FUNCTIONS PARAMETERS P500 to P599 Braking P501 DC Braking Time 0...299 0=Inactive P502 DC Braking Voltage Level 30...70 P510 Jog 0=Inactive 1=Active P511 Jog Level 30...70 Kick Start (1)(3) P520 Voltage pulse at start (Kick Start) 0 = Inactive 1 = Active P521(3) Pulse time at start 0.2 to 2.0 s P522 Voltage pulse level at start (%Un) 70 to 90 % Español Datos del Arrancador Suave Corriente nominal 0 = 1.7 A 1 = 17 A 2 = 24 A 3 = 30 A 4 = 45 A 5 = 61 A 6 = 85 A 7 = 130 A 8 = 171 A 9 = 200 A 10 = 255 A 11 = 312 A 12 = 365 A 13 = 412 A PARÁMETROS DE COMUNICACIÓN P300 a P399 Comunicación Serial Dirección del Arrancador Suave 1 a 247 Tipo de protocolo y tasa de transmisión de la comunicación serial 1 = Modbus 9600 bps sin paridad 2 = Modbus 9600 bps impar 3 = Modbus 9600 bps par 4 = Modbus 19200 bps sin paridad 5 = Modbus 19200 bps impar 6 = Modbus 19200 bps par 7 = Modbus 38400 bps sin paridad 8 = Modbus 38400 bps impar 9 = Modbus 38400 bps par Português Factory Setting Dados da Soft-Starter Corrente nominal 0 = 1.7 A 1 = 17 A 2 = 24 A 3 = 30 A 4 = 45 A 5 = 61 A 6 = 85 A 7 = 130 A 8 = 171 A 9 = 200 A 10 = 255 A 11 = 312 A 12 = 365 A 13 = 412 A PARÂMETROS DE COMUNICAÇÃO P300 a P399 Comunicação Serial Endereço da Soft-Starter 1 a 247 Tipo de protocolo e taxa de transmissão da comunicação serial 1 = Modbus 9600 bps sem paridade 2 = Modbus 9600 bps impar 3 = Modbus 9600 bps par 4 = Modbus 19200 bps sem paridade 5 = Modbus 19200 bps impar 6 = Modbus 19200 bps par 7 = Modbus 38400 bps sem paridade 8 = Modbus 38400 bps impar 9 = Modbus 38400 bps par - 1 1 Acción del error de Ação do erro de 1 comunicación serial (E28) comunicação serial (E28) 0 = Inactiva 0 = Inativa 1 = Deshabilita 1 = Desabilita 2 = Deshabilita General 2 = Desabilita geral 3 = Se va para local 3 = Vai para local Tiempo de verificación de Tempo de verificação da 0 la comunicación serial comunicação serial 0 = Inactiva 0 = Inativa 1 a 999 s 1 a 999 s Comunicación Fieldbus Comunicação Fieldbus Dirección CAN Endereço CAN 63 0 a 63 0 a 63 Tasa Comunicación CAN Taxa Comunicação CAN 3 0 = 125 Kbps 0 = 125 Kbps 1 = 250 Kbps 1 = 250 Kbps 2 = 500 Kbps 2 = 500 Kbps 3 = Autobaud 3 = Autobaud Reset de Bus Off Reset de Bus Off 0 0 = Manual 0 = Manual 1 = Automático 1 = Automático Instancias I/O Dnet Instâncias I/O Dnet 0 0 = ODVA 0 = ODVA 1 = Especif. WEG 1 W 1 = Especif. WEG 1 W 2 = Especif. WEG 2 W 2 = Especif. WEG 2 W 3 = Especif. WEG 3 W 3 = Especif. WEG 3 W 4 = Especif. WEG 4 W 4 = Especif. WEG 4 W 5 = Especif. WEG 5 W 5 = Especif. WEG 5 W 6 = Especif. WEG 6 W 6 = Especif. WEG 6 W 7 = Especif. WEG 7 W 7 = Especif. WEG 7 W Lectura #2 Dnet Leitura #2 Dnet 0 0 a 999 0 a 999 Lectura #3 Dnet Leitura #3 Dnet 0 0 a 999 0 a 999 Lectura #4 Dnet Leitura #4 Dnet 0 0 a 999 0 a 999 Lectura #5 Dnet Leitura #5 Dnet 0 0 a 999 0 a 999 Lectura #6 Dnet Leitura #6 Dnet 0 0 a 999 0 a 999 Lectura #7 Dnet Leitura #7 Dnet 0 0 a 999 0 a 999 Escrita #2 Dnet Escrita #2 Dnet 0 0 a 999 0 a 999 Escrita #3 Dnet Escrita #3 Dnet 0 0 a 999 0 a 999 Escrita #4 Dnet Escrita #4 Dnet 0 0 a 999 0 a 999 Escrita #5 Dnet Escrita #5 Dnet 0 0 a 999 0 a 999 Escrita #6 Dnet Escrita #6 Dnet 0 0 a 999 0 a 999 Escrita #7 Dnet Escrita #7 Dnet 0 0 a 999 0 a 999 Acción del error de Ação do erro de 1 comunicación Fieldbus Comunicação Fieldbus 0 = Inactiva 0 = Inativa 1 = Deshabilita 1 = Desabilita 2 = Deshabilita General 2 = Desabilita Geral 3 = Se va para local 3 = Vai para local PARÁMETROS DEL MOTOR PARÂMETROS DO P400 a P499 MOTOR P400 a P499 Parámetros Nominales Parâmetros Nominais Tensión nominal del motor Tensão nominal do motor 380 1 a 999 V 1 a 999 V Ajuste de la corriente del Ajuste da corrente do motor 100.0 motor 30.0 a 100.0 % 30.0 a 100.0 % Factor de servicio Fator de serviço 1.00 1.00 a 1.50 1.00 a 1.50 PARÁMETROS DE LAS PARÂMETROS DAS FUNCIONES ESPECIALES FUNÇÕES ESPECIAIS P500 a P599 P500 a P599 Frenado Frenagem Tiempo de Frenado Tempo de Frenagem 0 0...299 0...299 0=Inactivo 0=Inativo Nivel de Frenadol Nível da Frenagem 30 30...70 30...70 Jog Jog 0 0=Inactivo 0=Inativo 1=Activo 1=Ativo Nivel do Jog Nível do Jog 30 30...70 30...70 Kick Start Kick Start Pulso de tensión en el Pulso de tensão na partida 0 arranque (Kick Start) (Kick Start) 0 = Inactiva 0 = Inativa 1 = Ativa 1 = Ativa Tiempo del pulso en el Tempo do pulso na partida 0.2 arranque 0.2 a 2.0 s 0.2 a 2.0 s Nivel del pulso de tensión Nível do pulso de tensão na 80 en el arranque (%Un) partida (%Un) 70 a 90 % 70 a 90 % Par. English Español Português Factory Setting PROTECTION PARAMETERS P600 to P699 Current Protections P610(1) Phase Loss or Immediate Undercurrent (% In of the Motor) 1 to 80 % P611(1)(3) Immediate undercurrent time or phase loss 0 = Inactive 1 to 99 s (1) P612 Immediate overcurrent (%In of motor) 1 to 200 % P613(1)(3) Immediate overcurrent time 0 = Inactive 1 to 99 s PARÁMETROS DE PROTECCIÓN P600 a P699 Protecciones de Corriente Falta de fase o Subcorriente Inmediata (% In del Motor) 1 a 80 % Tiempo de subcorriente inmediata o falta de fase 0 = Inactiva 1 a 99 s Sobrecorriente inmediata (%In del motor) 1 a 200 % Tempo de sobrecorrente imediata 0 = Inactiva 1 a 99 s Current imbalance between Desbalanceo de corriente) phases (%In of motor) entre fases (%In del motor) 0 to 30 % 0 a 30 % PARÂMETROS DE PROTEÇÃO P600 a P699 Proteções de Corrente Falta de Fase ou Subcorrente Imediata (% In do Motor) 1 a 80 % Tempo de subcorrente imediata ou falta de fase 0 = Inativa 1 a 99 s Sobrecorrente imediata (%In do motor) 1 a 200 % Tempo de sobrecorrente imediata 0 = Inativa 1 a 99 s P614(1) Desbalanceamento de corrente entre fases (%In do motor) 0 a 30 % P615(1) Current imbalance time Tiempo de desbalanceo de Tempo de between phases corriente entre fases desbalanceamento de 0 = Inactive 0 = Inactiva corrente entre fases 1 to 99 s 1 a 99 s 0 = Inativa 1 a 99 s (1) P616 Undercurrent before Subcorriente antes del Subcorrente antes do By-Pass closing cierre del By-pass fechamento do By-pass 0 = Inactive 0 = Inactiva 0 = Inativa 1 = Active 1 = Activa 1 = Ativa P617(1)(3) Blocked Rotor Rotor Bloqueado Rotor Bloqueado 0 = Inactive 0 = Inactiva 0 = Inativa 1 = Active 1 = Activa 1 = Ativa Phase Sequence Secuencia de Fase Seqüência de Fase (1)(3) P620 RST phase sequence Secuencia de fase RST Seqüência de fase RST 0 = Inactive 0 = Inactiva 0 = Inativa 1 = Active 1 = Activa 1 = Ativa P621 E77 Enabling Habilitación E77 Habilitação E77 0=Inactive 0=Inactivo 0=Inativo 1=Active 1=Activo 1=Ativo SSW Short Circuit Detection Detección de Cortocircuito Detecção de Curto Circuito en la SSW na SSW P622(1) SSW short circuit 0 = Inactive 1 = Active Interval Between Starts P630 Time interval after stopping 2 to 999 s Cortocircuito en la SSW 0 = Inactivo 1 = Activo Intervalo entre Partidas Intervalo de tiempo luego de la parada 2 a 999 s Protección Térmica Motor Thermal Protection del Motor P640(1)(3) Motor protection thermal Clase térmica de class protección del motor 0 = Inactive 0 = Inactiva 1=5 1=5 2 = 10 2 = 10 3 = 15 3 = 15 4 = 20 4 = 20 5 = 25 5 = 25 6 = 30 6 = 30 P641(1) Thermal memory auto-reset Autoreset de la memoria 0 = Inactive térmica 1 to 600 s 0 = Inactiva 1 a 600 s 80 1 100 1 15 0 0 1 1 1 Curto-circuito na SSW 0 = Inativo 1 = Ativo Intervalo entre Partidas Intervalo de tempo após parada 2 a 999 s 0 2 Proteção Térmica do Motor Classe térmica de proteção do motor 0 = Inativa 1=5 2 = 10 3 = 15 4 = 20 5 = 25 6 = 30 Auto-reset da memória térmica 0 = Inativa 1 a 600 s 6 = 30 0 (1) Changeable parameters only when the motor is disabled. Solamente se permite modificar el valor del parámetro con el motor parado. Parâmetros alteráveis somente com motor parado. (2) Unchanged parameters at factory default settings (P204=5). No cambia el valor del parámetro cuando se ejecuta el comando cargar valores padrón de fábrica (P204 = 5). Parâmetros não alterados no padrão de fábrica (P204 = 5). (3) Changeable parameters only in keypad mode (P219=1). If P219=0 the parameters are read only. Se permite modificar el parámetro solamente en el modo HMI (P219 = 1). Con P219 = 0 los parámetros son considerados del tipo lectura. Parâmetros alteráveis somente em modo HMI (P219 = 1). Com P219 = 0 os parâmetros são considerados do tipo leitura. Fault Messages / Mensajes de Error / Mensagens de Erro E31 English Phase loss or undercurrent Overtemperature on power Overload on motor External fault (DI) Function copy fault SSW short circuit Programming fault Timeout fault at telegram reception Keypad connection failure E62 Current limitation start timeout E63 E66 E67 E71 Stall Overcurrent Inverted phase sequence Undervoltage at electronic supply By-pass contact open E72 Overcurrent before By-pass E74 Current imbalance E75 Power supply frequency out of allowed range E03 E04 E05 E06 E10 E19 E24 E28 E70 E76 E77 Overcurrent before closing By-pass Closed by-pass contact or shorted SCR’s Español Falta de Fase o Subcorriente Sobretemperatura en la potencia Sobrecarga en el motor Error externo (DI) Error en la función copy Cortocircuito en la SSW Error de programación Error de timeout en la recepción de los telegramas Fallo en la conexión de la HMI Exceso de tiempo de limitación de corriente durante el arranque Rotor bloqueado Sobrecorriente Secuencia de fase invertida Subtensión en la alimentación de la electrónica Contacto del By-pass abierto Sobrecorriente antes del By-pass Desbalanceo de corriente Frecuencia de la red de alimentación fuera del rango permitido Subcorriente antes del cierre del By-pass Contactor de By-pass cerrado o SCRs en cortocircuito Português Falta de Fase ou Subcorrente Sobretemperatura na potência Sobrecarga no motor Erro externo (DI) Erro na função copy Curto-circuito na SSW Erro de programação Erro de timeout na recepção de telegramas Falha na conexão da HMI Excesso de tempo de limitação de corrente durante a partida Rotor bloqueado Sobrecorrente Seqüência de fase invertida Subtensão na alimentação da eletrônica Contato do By-pass aberto Sobrecorrente antes do By-pass Desbalanceamento de corrente Freqüência da rede de alimentação fora da faixa permitida Subcorrente antes do fechamento do By-pass Contato de By-pass fechado ou SCRs em curto-circuito To get the detailed description of the parameters, consult the Programming Manual. This manual is supplied in electronic format on CD-ROM and at WEG’s web site: www.weg.net Para obtener la descripción detallada de los parámetros, consulte el Manual de Programación. Este manual es suministrado en formato electrónico en CD-ROM y en la pagina web de WEG www.weg.net Para obter a descrição detalhada dos parâmetros, consulte o Manual de Programação. Este manual é fornecido em formato eletrônico no CD-ROM e no site da WEG www.weg.net
  • Page 1 1
  • Page 2 2

WEG SSW07 / SSW08 Guía de inicio rápido

Tipo
Guía de inicio rápido