ABB CLMD03 Installation, Operation & Maintenance Instructions Manual

Tipo
Installation, Operation & Maintenance Instructions Manual
Power LV Capacitor CLMD03
Installation, Operation &
Maintenance Instructions
Condensadores de potencia
de baja tensión CLMD03
Instrucciones de Instalación,
Utilización y Mantenimiento
Capacitor de Potência
Baixa Tensão CLMD03
Instruções para instalação,
Utilização e manutenção
Niederspannungs-
Leistungskondensator CLMD03
Installations-, Inbetriebnahme-
und Wartungsanleitung
Condensatori di potenza
Bassa tensione CLMD03
Istruzioni per l'installazione,
l'uso e la manutenzione
Condensateurs de puissance
basse tension CLMD03
Instructions d’installation,
d’utilisation et d’entretien
AG Güç Kondansatörü CLMD03
Montaj, İşletme &
Bakımıklamaları
低壓電力電容器 TYPE CLMD03
安裝,操作,維護手冊
en
es
de
pt
it
fr
tr
zht
2
Before installation, read this notice carefully and keep it at
disposal of people in charge of installation, maintenance
and operation.
READ THIS FIRST
Safety
WARNING!
Wait 5 min. after isolating supply before
handling. After the 5 min. wait and as an additional
precaution before commencing work, carefully proceed
with DC voltage measurement on the terminals and make
sure of the capacitor discharge.
For a safe use of CLMD03 capacitor units, please ensure:
1. Installation and maintenance are undertaken only by
authorized and qualified personnel, in accordance with
current local regulations;
2. Isolate the equipment from the supply before
attempting to gain access.
Inspection on reception
Unpack the CLMD03 and check that:
- data on the label correspond to those of your purchase
order and local regulations;
- the CLMD03 is not damaged.
Any loss or damage should be notified immediately to
your closest ABB agent.
Storage
Indoor, in dry, dust free and non-corrosive environments,
protected from vibrations or shocks.
Storage temperature: minimum: -40°C/-40°F, maximum:
75°C/167°F.
Transportation and handling
In case severe conditions of transportation are expected,
make sure the fixation points are strong enough to
withstand weight of the CLMD03 and vibrations that may
occur.
WARNING!
Failure to respect the installation rules may
lead to premature failure, other material damage to
installations or bodily injury.
INSTALLATION
Applicable standards
IEC 60831 Parts 1 and 2. Current local regulations.
Protection
IP00 by default and IP20 with optional top cover.
Installation and use
Indoor installation on firm foundation or fixed on a rigid
plate/frame in well-ventilated situations where the air
temperature around the capacitor does not exceed
35°C/95°F over one year, 45°C/113°F over 24 hours and
55°C/131°F (according to IEC 60831 Parts 1 and 2 for a -
25/D temperature category product).
Always refer to the nameplate for exact specifications.
WARNING!
The ambient temperature for capacitors
inside a cubicle is the temperature around the capacitors
and not around the cubicle.
WARNING!
Like other standard capacitor units, CLMD03
discharge devices are not suitable for use with rapid
switching rates like thyristor switched banks (minimum off
time: 40 sec). Additional external resistors are not a
solution for such cases. Only specially designed
capacitors must be used in such applications.
Vertical and horizontal mounting
The CLMD03 capacitors must be fixed in such a way as
to ensure a natural airflow from bottom to top.
Several CLMD03 units can be installed side by side,
provided that they are in line (Fig. #1). Triangle and
square configuration are not allowed. The minimum free
space between groups of in-line adjacent units is 25 mm
(Fig. #2 & 3).
In case of vertical mounting, use a punched mounting
plate or support bars to allow free airflow around
capacitors units (Fig. #4 & 5). Do not mount upside down.
(Fig. #6)
In case of horizontal mounting, install so that the natural
airflow goes through the units without major constraints
(Fig. #7). Do not mount so that the natural airflow is
blocked (Fig. #8).
Installation in a cubicle
WARNING! Guidelines only apply if the following limits
are respected:
- Maximum room temperature: 40°C (1 hour).
- Average maximum room temperature over 24 hours:
35°C.
- Average maximum room temperature over 1 year:
25°C.
When the capacitors are installed in a cubicle the
components should be placed in such a way as to
optimize the cooling. Do preferably place devices with
high heat dissipation above the capacitors to avoid
overheating them. When reactors are used they should be
placed in such a way that they do not radiate heat directly
on the capacitors. A thermal barrier is recommended.
Reactors do in general dissipate much more heat, so their
thermal impact through convection must also be taken
into account.
1. Natural air circulation
The difference in height between air inlet and air outlet
should be large enough to improve the air circulation.
The airflow should be channeled in such a way as to
well cool the hottest spots in the cubicle. Air should flow
from the bottom to the top of the cubicle. The cross-
section of the top air outlet should be at least equal to
1.2 times the cross-section of the bottom air inlet.
2. Forced ventilation
Forced cooling using a fan is sometimes required
(Fig. #8).
Please refer to the following recommendations:
- Consider the maximum ambient temperature of the
installation site including the heating effect of the
capacitor installation itself.
- Consider the heat dissipated from all the components
and apparatus in the cubicle: reactors, capacitors,
contactors, fuses, etc.
en
en
3
- Consider the maximum permissible temperatures for
all the components and apparatus.
- Consider how to direct the airflow with respect to the
position of the capacitors (Fig. #9).
3. The use of an overtemperature protection is
recommended in order to switch the bank off in case of
fan failure or overtemperature due to other cause.
4. Regular maintenance and cleaning of any filters is
necessary. Without regular cleaning the cooling system
may become inefficient.
CLMD03 fixation (Fig. #10)
Four fixation holes are provided for M6 screws (not
included). At least two of the fixation holes must be used
in a symmetrical way (Fig. #11).
Make sure that the rigidity of the support and the screws
are sufficient to bear the weight of the CLMD03 capacitor
unit(s).
Electrical connection
Power supply
CLMD03 is available as a unit that houses either a single
capacitor or two individual capacitors in the same case.
Consequently one (Fig. #12) or two (Fig. #13) sets of 3-
phase terminals are provided.
Cables should be rated at minimum 1.5 times the nominal
capacitor current.
Appropriate cable shoes must be used in accordance with
good common practice of electrical installation.
While tightening the bolt, a torque of 6Nm must be applied
for proper electrical connection (according to DIN46-200).
Ensure that all connections are tight. If there is an
optional top cover, ensure that it is properly fixed (see
section ‘Optional accessories’ below).
Earthing
Earthing is achieved through fixation points of the
CLMD03 enclosure. Remark: this implies that an extra
cable between the CLMD03 enclosure and the earthing
contact of the installation is required in case the CLMD03
unit is fixed on an isolating material.
Harmonics
Installation of capacitors on networks disturbed by
harmonics may require special precautions especially
when there is a risk of resonance phenomena.
COMMISSIONING
With the equipment isolated from the supply, check:
- Cabling is properly connected (earthing may be
considered)
- Ambient ventilation is adequate
- Correct tightness of the connections.
- IP20 top cover is well fixed, if any (see section
“Optional accessories”)
OPTIONAL ACCESSORIES
Top cover
The optional top cover allows the CLMD03 unit to get
IP20 protected as per the IEC 60529 provided that
appropriate glands or grummets are used. Fix it properly
with the 4 push-screws (delivered with the top cover)
(Fig. #14.1 & 14.2). This protection cover prevents people
from touching live part of the CLMD03 unit especially
when exposed in open areas.
We recommend to drill hole(s) in the top cover with a hole
saw at the appropriate side. Three bosses are provided in
the top cover for the use of cable glands up to the
standard size PG29 (two small bosses for dual capacitor
units) or PG36 (one large boss for single capacitor units).
Cable grummets are also allowed.
Discharge resistor
The CLMD03 capacitor unit is delivered with factory-
installed discharge resistors to comply with IEC 60831
and allow a decrease of the residual voltage to less than
50V after 1 min. disconnection from supply. Make sure the
delay before the CLMD03 is re-energized is not shorter
than 40 sec. Failure to follow this rule may cause
damage and reduce the lifetime of the capacitor.
MAINTENANCE
1. Ensure safety procedures are completed (see
paragraph “Safety”);
2. Yearly maintenance should include:
- Removal of dust deposits, cleaning of all parts;
- Check of tightness of all electrical connections;
- Check of ambient temperature;
- Check condition of discharge resistors.
While every care is taken to ensure that the information contained
in this publication is correct, no legal responsibility can be accepted
for any inaccuracy. We do not accept responsibility for any misuse
of the product. The company reserves the right to alter or modify the
information contained herein at any time in the light of technical or
other developments.
4
Prima dell'installazione, leggere queste note con
attenzione e tenerle a disposizione del personale addetto
all'installazione, alla manutenzione ed al funzionamento.
LEGGERE PRIMA
Salute e sicurezza
ATTENZIONE!
aspettare 5 min. dopo aver tolto
l’alimentazione prima di maneggiare. Dopo aver atteso 5
min, come precauzione aggiuntiva prima di iniziare ad
utilizzare il prodotto, procedere con cautela alle
misurazioni in cc sui terminali e accertarsi che il
condensatore sia scarico.
Per un uso sicuro dei condensatori CLMD03, assicurarsi:
1. Che l'installazione e la manutenzione siano effettuate
da personale autorizzato e qualificato, in accordo con i
vigenti regolamenti locali;
2. Di isolare l'equipaggiamento dall’ alimentazione prima
di intervenire.
Ispezione al ricevimento
Disimballare i CLMD03 e verificare che:
- I dati sull'etichetta corrispondano al vostro ordine di
acquisto ed ai regolamenti locali;
- che i CLMD03 non sia danneggiato.
Qualunque danno deve essere immediatamente notificato
all'ufficio ABB più vicino.
Immagazzinamento
In ambiente coperto, secco, senza polvere e non
corrosivo, protetto da colpi e vibrazioni.
Temperatura di immagazzinamento :T° min.: -40°C/-40°F
T° max.: 75°C/167°F
Trasporto & maneggiamento
In caso di condizioni di trasporto severe, verificare che i
punti di aggancio sia sufficientemente robusti da
sopportare il peso del CLMD03 e le eventuali vibrazioni
che possono presentarsi. ATTENZIONE! Il non rispetto
delle regole d’installazione puo’ portare a un prematuro
guasto, a danni materiali alle installazioni o a rottura
dell’involucro.
ATTENZIONE
! Il non rispetto delle regole di installazione
puo’ portare ad un premature guasto, a danni materiali
alle installazioni o a rottura dell’involucro.
INSTALLAZIONE
Norme applicabili
IEC 60831 Parti 1 e 2. Regolamenti vigenti locali.
Protezione
IP00 standard e IP20 con calotta opzionale.
Posizionamento
Installazione al coperto su fondazioni stabili o fissato ad
una piastra/telaio rigidi in condizione di buona
ventilazione dove la temperatura dell’aria intorno al
condensatore non ecceda i 35°C/95°F nell'arco dell'anno
e i 45°C/113°F nell'arco delle 24 ore e 55°C/131°F
(secondo la IEC 60831 Parti 1 e 2 per prodotti di categoria
-25/D).
Far sempre riferimento ai dati di targa per le esatte
specifiche tecniche
ATTENZIONE!
La temperatura ambiente del
condensatore all’interno di un quadro e’ la temperatura
attorno al condensatore e non attorno al quadro.
ATTENZIONE!
Come per gli altri condensatori standard, i
dispositivi di scarica degli CLMD03 non sono adatti
all'utilizzo con commutazione rapida come per es.
inserimento attraverso tiristori (tempo minimo di
spegnimento: 40 sec). Aggiungere resistori esterni
aggiuntivi non risolve il problema, solo condensatori
opportunamente studiati possono essere utilizzati in
queste applicazioni.
Montaggio verticale e orizzontale
I CLMD03 devono essere fissato in modo da assicurare il
naturale flusso d'aria, dal basso verso l'alto. I CLMD03
possono essere installati affiancati tenendo conto che
siano in linea (Fig. #1)., altre configurazioni per es. a
triangolo non sono consentite. Lo spazio minimo tra i vari
gruppi in linea adiacenti è di 25mm (Fig. #2 & 3).
Nel caso di montaggio verticale usare un piatto di
montaggio punzonato o barre di supporto per permettere
la libera circolazione dell’aria intorno ai condensatori (Fig.
#4 & 5). Non montare sottosopra. (Fig. #6) Nel caso di
montaggio orizzontale, installare in modo tale da
permettere la naturale circolazione dell’aria attraverso le
unita’ senza ulteriori impedimenti (Fig. #7). Non montare
bloccando la naturale circolazione dell’aria (Fig. #8).
Installazione in un quadro
ATTENZIONE! Linea guida applicabile solo se Ie
seguenti limitazioni sono rispettate:
- Temperatura massima del locale 40°C (1 ora).
- Media della temperatura massima del locale oltre le 24
ore: 35°C.
- Media della temperatura massima del locale oltre 1
anno: 25°C. .
Quando i condensatori sono installati in un quadro i
componenti devono essere disposti in modo tale da
ottimizzare il raffreddamento. Preferibilmente sistemare i
dispositivi con alta dissipazione di calore al di sopra dei
condensatori per evitare il loro surriscaldamento. Quando
vengono usati i reattori, essi devono essere collocati in
modo tale che non irradino il calore direttamente sui
condensatori. Viene raccomandata una barriera termica.
I reattori generalmente dissipano molto più calore e anche
il loro impatto termico per convezione deve essere tenuto
in considerazione.
1. Naturale circolazione dell’aria
La differenza in altezza tra l’aria in entrata e quella in
uscita dovrebbe essere maggiore per migliorare la
circolazione dell’aria. Il flusso dell’aria dovrebbe essere
canalizzato per ben raffreddare i punti piu’ caldi del
quadro. L’aria dovrebbe fluire dal basso verso l’alto del
quadro. L’intersezione dell’aria in uscita dall’alto
dovrebbe essere almeno uguale a 1.2 volte dell’aria in
entrata dal basso.
2. Ventilazione forzata
A volte e’ richiesto il raffreddamento forzato usando un
it
5
it
ventilatore (Fig. #8). Prego fare riferimento alle
seguenti raccomandazioni:
- Considerare la temperatura piu’ alta del luogo di
installazione includendo l’effetto della dissipazione dei
condensatori stessi.
- Considerare il calore disperso da tutti i componenti
e
dall’apparato all’interno del quadro: reattori, contattori,
condensatori , fusibili ecc.
- Considerare la temperatura massima permessa per
tutti i componenti e apparati.
- Considerare come convogliare il flusso dell’aria
rispetto alla posizione dei condensatori (Fig. #9).
3. E’ raccomandato l’uso di una protezione da
sovratemperatura in modo da ottenere lo
spegnimento del banco in caso di guasto della
ventola dovuto ad altre cause.
4. E’ necessaria la regolare pulizia e manutenzione dei
filtri. Senza una regolare pulizia il sistema di
raffreddamento potrebbe essere inefficiente.
Fissaggio del CLMD (Fig. #10)
Il prodotto ha quattro fori di fissaggio per viti M6 (non
incluse). Almeno due fori di fissaggio in posizione
simmetrica devono essere utilizzati (Fig. #11). Assicurarsi
che la rigidità del supporto e delle viti sia sufficiente a
sostenere il peso del(i) condensatori CLMD03.
Collegamenti elettrici
Alimentazione di potenza
I CLMD03 sono disponibili in unità che includono sia uno
sia due singoli condensatori nello stesso case. Di
conseguenza vengono forniti uno (Fig. #12) o due (Fig.
#13) set di terminali trifasi. I cavi devono essere
dimensionati al minimo per 1.5 volte la corrente nominale
del condensatore. Appropriati terminali vanno utilizzate in
accordo con l’installazione elettrica a regola d’arte.
Mentre, per stringere il bullone, deve essere applicata una
coppia di 6Nm per raggiungere una corretta connessione
elettrica (in accordo alla DIN46-200)
Assicurarsi che tutte le connessioni siano ben avvitate.
Se è presente anche una calotta protettiva aggiuntiva
assicurarsi che sia fissata correttamente (vedi
sezione”Accessori opzionali” sotto)
Messa a terra
La messa a terra è raggiunta attraverso i punti di fissaggio
del CLMD03. Attenzione: questo implica che un cavo
extra tra il condensatore e la messa a terra
dell’installazione è richiesto nel caso in cui il CLMD03 sia
fissato su un materiale isolante.
Armoniche
L'installazione di condensatori in reti disturbate da
armoniche richiede speciali precauzioni specialmente
quando ci sono rischi di fenomeni di risonanza.
MESSA IN SERVIZIO
Con l'equipaggiamento isolato dalla rete, verificare:
- Che la cablatura sia corretta (la messa a terra potrebbe
essere considerata);
- Che la ventilazione ambientale sia adeguata;
- Il corretto serraggio delle connessioni.
- La calotta IP20 è ben fissata, se presente (vedi
sezione”Accessori opzionali” sotto)
ACCESSORI OPZIONALI
Calotta IP20
La calotta opzionale consente al CLMD03 di raggiungere
un grado di protezione IP20 in base alla IEC60529
considerando che flange e guarnizioni adatte siano
utilizzate. Fissarla correttamente con le 4 viti fornite con la
calotta (Fig. #14.1 & 14.2). Questa calotta protettiva
protegge le persone da contatti accidentali con le parti in
tensione del CLMD03 specialmente quando gli stessi
sono in spazi aperti.
Noi raccomandiamo di forare (con uno o più buchi) il
coperchio superiore con una punta circolare sul lato
appropriato. Tre flange sono fornite nel coperchio
superiore per l'utilizzo dei pressacavi fino alla grandezza
standard PG29 (due piccole flange per unità doppie di
condensatori) o PG36 (una flangia grande per unità di
condensatore singola). Guarnizioni per i cavi sono altresì
permesse.
Resistenze di scarica
I CLMD03 sono forniti con all’interno una resistenza di
scarica per essere conformi alla IEC60831 e permette
una riduzione della tensione residua a meno di 50V dopo
1 ms di sconnessione dall’alimentazione. Prestare
attenzione al fatto che il ritardo prima che il CLMD03 sia
ricaricato non sia inferiore ai 40 sec. Non seguire questa
regola potrebbe causare danni e ridurre la vita del
condensatore.
MANUTENZIONE
1. Assicurarsi che la procedura di sicurezza sia
completata (vedere Salute & Sicurezza);
2. La manutenzione annuale include:
- La rimozione dei depositi di polvere, pulire tutte le parti;
- La verifica del serraggio delle connessioni elettriche;
- Il controllo della temperatura ambiente.;
- Il controllo dello stato delle resistenze di scarico.
Mentre viene presa ogni precauzione per assicurare che le
informazioni contenute in questa pubblicazione siano corrette, non
può essere accettata alcuna responsabilità legale per alcuna
inesattezza. Non ci assumiamo nessuna responsabilità per l'uso
improprio del prodotto. La Società si riserva il diritto di alterare o
modificare le informazioni qui contenute in qualunque momento alla
luce di sviluppi tecnici o altro.
6
es
Antes de proceder a la instalación lea atentamente este
documento y manténgalo al alcance del personal
responsable de la instalación, mantenimiento y
utilización.
LEA ESTO PRIMERO
Seguridad
¡ATENCIÓN!: espere 5 minutos tras la desconexión antes
de proceder a la manipulación. Después de esperar 5 min
y como precaución adicional antes de empezar a trabajar,
comprobar la tensión cc entre terminales y asegurarse
que el condensador está descargado.
Para una utilización segura de los condensadores
CLMD03, por favor asegúrese que:
1. La instalación y el mantenimiento lo realicen
únicamente personal cualificado y autorizado, de
acuerdo con la normativa local vigente;
2. El equipo esté desconectado de la red antes de
acceder al mismo.
Inspección a la recepción
Desembale el CLMD03 y compruebe que:
- los datos en la placa corresponden con los indicados
en su pedido y con la normativa local;
- el CLMD03 no esté dañado.
Cualquier pérdida o daño debe ser notificada de
inmediato a la oficina de ABB más cercana.
Almacenamiento
Interior, en ambientes secos, libres de polvo y no
corrosivos, protegido contra vibraciones y golpes.
Temperatura de almacenamiento:Tª mín.: -40°C/-40°F
Tª máx.: 75°C/167°F
Transporte y manipulación
En caso que se prevean unas condiciones de transporte
duras, asegurarse que los puntos de fijación sean lo
suficientemente fuertes de acuerdo al peso del CLMD03
y de las vibraciones que pudieran ocurrir.
¡ATENCIÓN!
No seguir las normas de instalación puede
desembocar en fallos prematuros, otros daños materiales
a la instalación o daños personales.
INSTALACIÓN
Normas aplicables
IEC 60831 Partes 1 y 2. Normativa local vigente.
Protección
P00 por defecto y IP20 con tapa superior opcional
Instalación y utilización
Instalación interior sobre una base sólida o fijado sobre
un armazón/placa en espacios bien ventilados donde la
temperatura media alrededor del condensador no exceda
de 35°C/95°F a lo largo de un año ni de 45°C/113°F
durante 24 horas ni de 55ºC/131ºF (de acuerdo con IEC
60831 Partes 1 y 2 para un producto de la categoría -
25/D).
Ver siempre la placa de características para las
especificaciones exactas.
¡ATENCIÓN!
La temperatura ambiente de un
condensador instalado en un armario eléctrico es la
temperatura alrededor del condensador no alrededor del
armario.
PRECAUCION: Como otras unidades de condensadores
estándares, los dispositivos de descarga de los CLMD03
no son adecuados para su uso en conmutaciones rápidas
como las baterías activadas por tiristores (tiempo mínimo
de desconexión: 40 seg). Las resistencias externas
adicionales no son una solución para tales casos, sólo
condensadores especialmente diseñados para ello se
deben utilizar en tales aplicaciones.
Montaje horizontal y vertical
El CLMD se debe fijar de tal forma que se asegure una
ventilación natural desde la parte inferior a la superior.
Algunas unidades CLMD03 pueden ser montadas lado a
lado si están alineadas (Fig. #1). No está permitida la
configuración en triángulo ni en cuadrado. El espacio libre
mínimo entre grupos en línea adyacentes es de 25 mm
(Fig. #2 & 3).
En caso de montaje vertical utilice una placa base
agujereada o barras de soporte de modo que se habilite
la libre circulación de aire alrededor de las unidades de
condensadores (Fig. #4 & 5). No montar boca abajo (Fig.
#6). En caso de montaje horizontal, se debe instalar de
forma que el flujo natural de aire circule a través de las
unidades sin mayor constricción (Fig. #7). No montar de
forma que el flujo natural de aire quede bloqueado (Fig.
#8).
Instalación en un armario eléctrico
¡ATENCIÓN! Las directrices sólo se aplican si se
respetan los límites siguientes:
- Temperatura máxima del recinto: 40°C (1 hora).
- Temperatura media máxima del recinto durante 24
horas: 35°C.
- Temperatura máxima del recinto durante 1 año: 25°C.
Cuando los condensadores se instalan en un armario los
componentes se deben disponer de tal forma que se
optimice la refrigeración. Los componentes que disipen
gran cantidad de calor se deberán situar preferiblemente
por encima de los condensadores de forma que estos no
se sobrecalienten. Cuando se utilicen reactancias, éstas
deben situarse de tal forma que no irradien calor
directamente sobre los condensadores. Se recomienda
una barrera térmica. Generalmente las reactancias
disipan mucho más calor, por lo que su impacto térmico
mediante convección también debe tenerse en cuenta.
1. Ventilación natural.
La diferencia de altura entre la entrada y la salida de
aire debe ser grande de modo que se mejore la
circulación de aire. El flujo de aire debe ser canalizado
de forma que refrigere los puntos más calientes en el
armario. El aire debe fluir en el armario de abajo a
arriba. La superficie de la salida de aire debe ser al
menos 1,2 veces la de la entrada de aire.
2. Ventilación forzada.
A veces se requiere una refrigeración forzada
mediante ventilador (Fig. #8). Para ello tener en cuenta
las siguientes recomendaciones:
- Considere la máxima temperatura ambiente de la
7
estancia incluyendo el efecto calefactor de la
instalación de condensadores.
- Considere el calor disipado por todos los componentes
y aparatos del armario: reactancias, condensadores,
contactores, fusibles, etc.
- Considere las temperaturas máximas admisibles de
todos los componentes y aparatos.
- Considere como dirigir la corriente de aire de acuerdo
con la posición de los condensadoes (Fig. #9).
3. Se recomienda el uso de una protección para la
sobretemperatura que desconecte la batería en caso
de fallo del ventilador o por sobretemperatura debida a
otra causa.
4. Es necesaria una limpieza y mantenimiento regular de
los filtros que puedan haber. Sin una limpieza regular
el sistema de refrigeración puede resultar ineficiente.
Fijación del CLMD03 (Fig. #10)
Están provistos de cuatro taladros de fijación para
tornillos de M6 (no incluidos). Como mínimo deben
emplearse dos de los taladros en forma simétrica (Fig.
#11).
Asegurarse que la rigidez del soporte y de los tornillos es
suficiente para soportar el peso de los condensadores
CLMD03.
Conexión eléctrica
Alimentación
El CLMD03 está disponible como una unidad que alberga
tanto un solo condensador como dos condensadores
individuales en la misma unidad. Para ello están provistos
de uno (Fig. #12) o dos (Fig. #13) juegos de terminales
para tres fases .
Los cables deben dimensionarse para 1,5 veces la
intensidad nominal del condensador. Deben utilizarse los
conectores adecuados para su correcto empleo en
instalaciones eléctricas.
Para el ajuste de los tornillos, debe aplicarse un par de
6Nm para una correcta conexión eléctrica (según norma
DIN 46-200).
Asegurarse que todas las conexiones están apretadas. Si
hay la tapa superior opcional, asegurarse que está
debidamente fijada (ver abajo en la sección de
“Accesorios opcionales).
Tierra
La tierra viene mediante los puntos de fijación de la
envolvente del CLMD03. A tener en cuenta: ello implica
que se necesita un cable extra entre la envolvente de
CLMD03 y el contacto de tierra de la instalación en el
caso de que la unidad CLMD03 esté fijada sobre un
material aislante.
Armónicos
La instalación de condensadores en redes distorsionadas
por armónicos puede requerir precauciones especiales,
particularmente cuando existe riesgo de fenómenos
resonantes.
PUESTA EN MARCHA
Con el equipo desconectado de la red, comprobar que:
- El cableado está conectado correctamente (debiendo
ser considerada la tierra);
- La ventilación ambiente es adecuada;
- Las conexiones tienen el apriete correcto.
- La tapa superior para IP20 esté correctamente fijada,
en caso de existir (ver sección “Accesorios
opcionales”)
ACCESORIOS OPCIONALES
Tapa superior
La tapa superior del CLMD03 para conseguir la
protección IP20 de acuerdo a IEC 60529 ya viene
provista de los prensaestopas o pasacables que se vayan
a emplear. La fijación es mediante 4 tornillos
autorroscantes (incluidos en la tapa) (Fig. #14.1 y 14.2).
Esta tapa de protección sirve para impedir el contacto
accidental con alguna parte viva de la unidad CLMD03
especialmente cuando están ubicados en áreas abiertas.
Recomendamos taladrar los agujeros con una broca de
sierra en la tapa en el lado adecuado. La tapa está
provista de tres pretalaros para colocar prensaestopas
hasta el tamaño estándar PG29 (dos pequeños
pretaladros para unidades duales) o PG36 (un pretaladro
grande para una unidad de un solo condensador).
También admiten los pasataladros.
Resistencias de descarga
El condensador CLMD03 se suministra desde fábrica con
el juego de resistencias de descarga ya instalado para
cumplir con la IEC 60831que permite una descarga hasta
la tensión residual por debajo de los 50V después de
1min una vez se desconecta de la red. Tener en cuenta
retrasar en no menos de 40 seg la reconexión del
CLMD03. No seguir esta recomendación podría causar
daños y reducir la vida del condensador.
MANTENIMIENTO
1. Asegurarse que se han seguido los procedimientos de
seguridad (ver Seguridad);
2. El mantenimiento anual debe incluir:
- Eliminación de los depósitos de suciedad, limpieza de
todas las partes;
- Comprobación del apriete de todas las conexiones
eléctricas;
- Comprobación de la temperatura ambiente;
- La verificación del estado de las resistencias de
descarga.
Si bien se han tomado todas las medidas para garantizar que la
información contenida en esta publicación sea correcta, no nos
hacemos responsables de posibles errores. No nos hacemos
responsables de la mala utilización del producto ni de daños
directos o indirectos. La compañía se reserva el derecho a
modificar la información aquí contenida en función de mejoras
técnicas o de cualquier otro tipo.
es
8
Avant l'installation, lisez attentivement cette notice et
laissez-la à la disposition des gens en charge de
l'installation, de l'utilisation et de l'entretien des
condensateurs.
A LIRE EN PREMIER
Sécurité
ATTENTION! Avant de manipuler les condensateurs,
attendez 5 min après les avoir déconnectés du réseau.
Comme précaution supplémentaire, passées ces 5 min,
attendez avant de commencer le travail, procédez
prudemment à la mesure de la tension DC sur les bornes
et assurez-vous que le condensateur est déchargé.
Pour une utilisation sans danger :
1. L'installation et l'entretien ne peuvent être effectués
que par du personnel autorisé et qualifié,
conformément aux réglementations locales en vigueur
;
2. Isolez le matériel de l’alimentation avant d'y accéder.
Inspection à la réception du matériel
Déballez le CLMD03 et vérifiez que:
- les informations reprises sur les étiquettes
signalétiques correspondent à celles commandées et
respectent la réglementation en vigueur ;
- le CLMD03 n'est pas endommagé.
Tout dégât ou perte doit être signalé immédiatement à
votre plus proche revendeur ABB.
Entreposage
A l'intérieur, dans un milieu sec, non poussiéreux et non
corrosif, exempt de vibration et protégé des chocs.
Température d'entreposage : de -40°C/-40°F à
75°C/167°F
Manipulation et transport
Pour des conditions de transport difficiles, assurez-vous
que les points de fixation sont suffisamment solides pour
supporter le poids du CLMD03 ainsi que les vibrations qui
pourraient survenir.
ATTENTION
! Le non-respect des instructions
d’installation peut engendrer une défaillance prématurée,
d’autres dégâts matériels de l’installation ou des
dommages corporels.
INSTALLATION
Normes applicables
IEC 60831 §1 & §2 et normes locales en vigueur.
Protection
IP00 par défaut et IP20 avec le capot en option.
Installation et utilisation
Installation à l’intérieur sur une surface solide ou sur un
support rigide dans un endroit bien ventilé où la
température de l’air autour du condensateur n'excède pas
35°C/95°F sur un an, 45°C/113°F sur 24h et 55°C/131°F
(selon la norme IEC 60831 §1 & §2 pour une catégorie -
25°C/D).
Référez-vous toujours à l’étiquette pour les spécifications
exactes.
ATTENTION
! La température ambiante pour les
condensateurs à l’intérieur d’une armoire est la
température autour des condensateurs et non autour de
l’armoire.
ATTENTION
! Comme pour les autres condensateurs
standards, les dispositifs de décharge du CLMD03
n’acceptent pas des commutations trop fréquentes
comme les batteries à commutation thyristor (temps
d’arrêt minimum: 40 sec). Des résistances externes
supplémentaires ne sont pas une solution pour ces cas.
Seuls des condensateurs spécialement conçus pour ces
applications peuvent être utilisés.
Montage vertical et horizontal
Les condensateurs CLMD03 doivent être fixés de telle
sorte qu’une convection naturelle de l’air (de bas en haut)
soit possible.
Plusieurs CLMD03 peuvent être installés côte à côte
pourvu qu’ils soient alignés (Fig. #1). Les configurations
en triangle et en carré ne sont pas autorisées. L’espace
libre minimal entre les groupes d’unités alignées
adjacentes est de 25 mm (Fig. #2 & 3).
En cas d’installation verticale, veuillez utiliser une plaque
de montage perforée ou des barres de support pour
permettre une ventilation libre autour des condensateurs
(Fig. #4 & 5). N’installez pas les CLMD03 à l’envers (tête
en bas). (Fig. #6)
En cas d’installation horizontale, veuillez monter les
CLMD03 de sorte que la ventilation naturelle passe
autour des unités sans contraintes importantes (Fig. #7).
N’installez pas les CLMD03 de manière à ce que la
ventilation naturelle soit bloquée (Fig. #8).
Installation dans une armoire
ATTENTION! Ces règles s’appliquent uniquement si les
limites suivantes sont respectées:
- Température maximale du local: 40°C (1 heure).
- Température moyenne maximale du local sur 24 heures
: 35°C.
- Température moyenne maximale du local sur 1 an:
25°C.
Quand les condensateurs sont installés dans une
armoire, les composants devraient être placés de façon à
optimiser le refroidissement. Placez de préférence les
appareils à dissipation thermique élevée au-dessus des
condensateurs pour éviter de les surchauffer. Quand il y a
des selfs, elles devraient être placées de façon à ce
qu’elles ne rayonnent pas de chaleur directement sur les
condensateurs. Une séparation thermique est
recommandée. Les selfs génèrent en général beaucoup
plus de chaleur, leur impact thermique sur la convection
doit également être pris en considération.
1. Ventilation par convection naturelle
La différence en hauteur entre l’entrée et la sortie d’air
devrait être grande afin d’améliorer la circulation de
l’air. Le flux d’air devrait être canalisé pour refroidir au
mieux les points les plus chauds dans l’armoire. L’air
devrait circuler du bas vers le haut de l’armoire. La
dimension de l’évent supérieur doit au moins être égale
à 1,2 fois celle de l’évent inférieur.
fr
9
fr
2. Ventilation forcée
Le refroidissement forcé utilisant un ventilateur est
parfois nécessaire (Fig. #8). Veuillez vous référer aux
recommandations suivantes :
- Prenez en considération la température maximum
ambiante de l’emplacement de l’installation ainsi que
l’effet thermique de l’installation de condensateurs elle-
même.
- Prenez en considération la chaleur émise par les
composants et appareils dans l’armoire : bornes,
condensateurs, contacteurs, fusibles, etc.
- Prenez en considération les températures maximum
admissibles pour tous les composants et appareils.
- Prenez en considération la circulation de l’air tout en
respectant la position des condensateurs (Fig. #9).
3. L’utilisation d’une protection de surchauffe est
recommandée afin d’éteindre la batterie en cas de
défaillance du ventilateur ou de température excessive
due à une autre cause.
4. L’entretien et le nettoyage réguliers de tous les filtres
sont nécessaires. Sans nettoyage régulier, le système
de refroidissement peut devenir inefficace.
Fixation du CLMD03 (Fig. #10)
Quatre trous de fixations sont fournis pour des vis M6
(non fournies). Deux de ces trous de fixations doivent au
moins être utilisés de façon symétrique (Fig. #11).
Assurez-vous que le support et les vis sont appropriés
pour supporter le poids des CLMD03.
Connexions électriques
Alimentation électrique
Le CLMD03 est disponible en tant qu’une unité constituée
soit d’un seul condensateur soit de deux condensateurs
individuels dans le même boîtier. Par conséquence, un
(Fig. #12) ou deux (Fig. #13) jeux de bornes triphasées
sont fournis.
Les câbles doivent être dimensionnés pour supporter au
minimum 1,5 fois le courant nominal des condensateurs.
Les souliers de câble appropriés doivent être utilisés
selon les bonnes pratiques habituelles d’une installation
électrique.
En serrant l’écrou, un couple de serrage de 6Nm doit être
appliqué pour assurer une connexion électrique correcte
(selon la DIN 46-200).
Assurez-vous que toutes les connexions sont serrées.
S’il y a un capot optionnel, assurez-vous qu’il est
correctement fixé (voir la section “accessoires en option”
ci-dessous).
Mise à la terre
La mise à la terre se fait au moyen des points de fixations
du boîtier du CLMD03. Remarque : cela implique qu’un
câble supplémentaire entre le boîtier du CLMD03 et la
mise à la terre de l’installation est nécessaire si le
CLMD03 est fixé sur un matériau isolant.
Harmoniques
L'installation de condensateurs sur des réseaux pollués
par des harmoniques demande une attention toute
particulière lorsqu'il y a un risque de phénomène de
résonance.
MISE EN SERVICE
L'équipement étant isolé du réseau, vérifiez que :
- le câblage est correct (la mise à la terre doit être
considérée);
- la ventilation est adéquate ;
- les câbles sont solidement connectés.
ACCESSOIRES EN OPTION
Capot
Le capot en option permet au CLMD03 d’avoir une
protection IP20 selon la norme IEC 60529 pourvu que les
presse-étoupes et passe-fils appropriés soient utilisés.
Fixez le capot correctement avec les quatre clous à visser
(fournis avec le capot) (Fig. #14.1 & 14.2). Ce capot de
protection empêche quiconque de toucher les parties
actives du CLMD03 particulièrement quand le
condensateur est facilement accessible.
Nous recommandons de forer le(s) trou(s) dans le capot
avec une scie-cloche sur la face appropriée. Trois
bossages sont formés dans le capot pour le placement
des presse-étoupes jusque la taille normalisée PG29 (2
bossages pour les boîtiers à double condensateurs) ou
PG36 (un bossage pour un condensateur simple). Les
passe-fils sont également autorisés.
Résistance de décharge
Le condensateur CLMD03 est livré avec des résistances
de décharge pré-installées pour être conforme à la norme
IEC 60831 et permettre une diminution de la tension
résiduelle jusqu’à moins de 50V une minute après la
déconnexion de l’alimentation. Assurez-vous que le délai
avant que le CLMD03 ne soit réalimenté n’est pas plus
court que 40 sec. Le non-respect de cette règle pourrait
endommager le condensateur et réduire sa durée de vie.
ENTRETIEN
1. Assurez-vous que les procédures de sécurité sont
respectées (voir le paragraphe " Sécurité ") ;
2. L'entretien annuel doit inclure :
- le dépoussiérage et le nettoyage de toutes les parties ;
- la vérification de la fermeté des connexions électriques
- la vérification de la température ambiante;
- la vérification de l’état des résistances de décharge.
Bien que tout soit mis en oeuvre pour garantir l'exactitude des
informations contenues dans cette publication, nous n'acceptons
aucune responsabilité légale pour toute information incorrecte.
Nous déclinons toute responsabilité en cas de mauvaise utilisation
du produit ainsi que pour les éventuels dommages en résultant,
qu'ils soient directs ou indirects. Nous nous réservons le droit de
changer ou de modifier à tout moment les informations contenues
dans cette publication à la lumière des développements techniques
ou autres. Les spécifications techniques sont valables uniquement
sous conditions de fonctionnement normales.
10
pt
Antes da instalação, leia cuidadosamente este manual e
o mantenha sempre disponível para os responsáveis da
instalação, manutenção e operação.
LEIA ISTO PRIMEIRO
Segurança
CUIDADO!
aguarde 5 minutos após a desenergização
antes de tocar nos terminais do capacitor. Depois de
esperar 5 min. e, como medida de precaução adicional,
antes de começar o trabalho, medir cuidadosamente a
tensão DC nos terminais e certifique-se que o capacitor
está descarregado.
Para o seguro uso das unidades do CLMD03, por favor
certifique-se de que:
1. A instalação e manutenção dos capacitores seja de
inteira e exclusiva responsabilidade de pessoas
autorizadas e qualificadas, e de acordo com as normas
e regulamentações locais;
2. O equipamento esteja isolado de sua fonte de
alimentação antes de se obter acesso aos terminais.
Inspeção e Recepção
Desembale o CLMD03 e verifique se:
- os dados correspondentes na etiqueta correspondem
aos mesmos descritos na ordem de compra e
regulamentaçõe locais.
- o CLMD03 não está danificado.
Qualquer problema deverá ser notificado imediatamente
ao seu agente ABB mais próximo.
Armazenagem
Abrigada, local seco, livre de poeira, em ambientes não
corrosivos, protegido de vibrações ou impactos.
Temperatura de armazenagem: T° mín.: -40°C/-40°F
T° máx.: 75°C/167°F
Transporte e Manuseio
No caso de severas condições de transporte, certifique-
se que os pontos de fixação são fortes o suficiente para
suportar o peso do CLMD03 e as vibrações que podem
ocorrer.
CUIDADO
! O desrespeito às normas de instalação,
podem levar a falhas prematuras, danos em outros mate-
riais da instalação ou acidentes pessoais.
INSTALAÇÃO
Aplicações Básicas
IEC 60831 Parte 1 & 2. Atual regulamentação local.
Proteção
IP00 como padrão e IP20 com tampa superior opcional.
Instalação e Utilização
Instalação abrigada sobre uma plataforma firme ou fixado
sobre uma rígida placa/caixa com boa ventilação onde a
temperatura do ar em torno do condensador não exceda
35ºC/95ºF por mais de um ano e 45ºC/113ºF por mais de
24 horas e 55ºC/131ºF (de acordo com a IEC 60831
Parte 1 & 2 para produtos com categoria -25/D.)
Consulte sempre a etiqueta de identificação para obtenir
as especificações exatas do produto.
CUIDADO
! A temperatura ambiente para capacitores
dentro de cubículos, é a temperatura ao redor do
capacitor, e não ao redor do cubículo.
CUIDADO! Assim como outros capacitores padrões, os
dispositivos de descarregamento do CLMD03, não são
convenientes para uso com faixas rápidas de
chaveamento como bancos chaveados à tiristores (tempo
mínimo para o desligamento 40 seg).
Resitores adicionais externos, não são uma solução para
estes casos, somente capacitores com projeto especial
devem ser usados para esta aplicação.
Montagem Vertical e horizontal
O CLMD03 deve ser afixado de forma a permitir o fluxo
natural de ventilação CLMD03 de baixa para cima.
Várias unidades do CLMD03 podem ser instaladas lado a
lado, considerando-se que elas sejam alinhadas (Figura
#1). Configurações triângulo e quadrado não são
permitidas. O espaço livre mínimo entre grupos de
unidades adjacentes é de 25mm (Figura #2 & 3).
No caso de montagem em plano horizontal, use suportes
de chapa perfurada, ou que permitam livre fluxo de ar ao
redor das unidades dos capacitores(Figura #4 & 5). Não
monte o capacitor em posição invertida (Topo para baixo)
(Figura #6). No caso de montagem em plano vertical,
instale de forma tal que haja ventilação natural através
das unidades sem grandes obstruções (Figura #7). Não
monte de forma que a ventilação natural fique bloqueada
(Figura #8).
Instalação em cubículo
CUIDADO! As regras a seguir somente se aplicam se os
seguintes limites forem respeitados:
- Temperatura máxima ambiente: 40°C (1 hora).
- Temperatura média ambiente máxima durante 24 horas:
35°C.
- Temperatura média ambiente máxima durante 1 ano:
25°C.
Quando capacitores são instalados em cubículos, os
componentes devem ser montados de forma a otimizar o
resfriamento. Instale dispositivos com elevada dissipação
térmica acima dos capacitors, evitando sobreaquecê-los.
Quando reatores estiverem sendo utilizados eles devem
ser alocados, de forma a não irradiar aquecimento
diretamente nos capacitores. É recomendada a utilização
de uma barreira térmica. Reatores em geral dissipam
muito mais calor, portanto o impacto térmico através da
convecção também deve ser considerado.
1. Circulação natural de ar
A diferença em peso entre o ar que entra e o ar que sai
deveria ser grande de forma a aumentar a circulação
de ar. O fluxo de ar deve ser canalizado de tal forma a
refrigerar melhor os pontos mais quentes do cubículo.
O ar deve fluir de baixo para cima no cubículo. A área
de abertura da saída de ar superior, deve ser igual a
1.2 vezes a área de abertura para entrada de ar
inferior.
11
2. Ventilação forçada
Refrigeração forçada utilizando-se de ventiladores são
algumas vezes requeridas (Figura #8). Por favor
considere as seguintes recomendações:
- Considere a máxima temperature ambiente da
instalação, incluindo o efeito do aquecimento da
própria instalação do capacitor.
- Considere a dissipação térmica de todos os
componentes e aparelhos no cubículo: Reatores,
Capacitores, Contatores, fusíveis, etc.
- Considere a temperatura máxima permissível para
todos os componentes e aparelhos.
- Considere como direcionar o fluxo de ar com respeito
as posições dos capacitores (Figura #9).
3. O uso de proteção por sobretemperatura é
recomendado de forma a desligar o banco em caso de
falha, ou sobretemperatura devido a outras causas.
4. Manutenção regular e limpeza de filtro são
necessárias. Sem uma limpeza regular o sistema de
refrigeração pode se tornar ineficiente.
Fixação do CLMD (Figura #10)
Existem quatro furos de fixação para parafusos do tipo
M6 (não incluídos). Ao menos dois dos furos de fixação
devem ser utilizados de forma simétrica (Figura #11).
Certifique-se de que a rigidez do suporte e dos parafusos
são suficientes para resistir ao peso das unidades dos
condensadores CLMD03.
Conexão Elétrica
Alimentação
O CLMD03 é disponível como uma unidade que contém
um capacitor único ou dois capacitors individuais na
mesma caixa. Consequentemente um (Figura #12) ou
dois (Figura #13) conjuntos de terminais trifásicos são
fornecidos. Os condutores devem ser dimensionados no
mínimo para 1,5 vezes a corrente nominal do
condensador. Devem ser utilizados terminais de cabos
apropriados de acordo com a boa prática de instalações
eléctricas. Enquanto aperta o parafuso, um torque de
6Nm deve ser aplicado para obtenir uma conexão elétrica
correta. (de acorde com DIN46-200).
Certifique-se de que todas as ligações estão apertadas.
No caso da existência da tampa opcional, certifique-se
que ela é devidamente fixada (veja seção ‘Acessórios
opcionais’).
Ligação de terra
A ligação a terra é executada através dos pontos de
fixação do invólucro do CLMD03. Observação: isto
emplica que um cabo extra, entre o invólucro do CLMD03
e o contato do terra da instalação, é necessário no caso
em que o CLMD03 é fixado sobre um material isolante.
Harmônicas
A instalação de capacitores em sistemas com distorções
harmônicas pode requerer precauções especiais,
especialmente em locais que possuem riscos com
fenômenos de ressonância.
COMISSIONAMENTO
Com o equipamento isolado da fonte de alimentação,
verificar:
- Os condutores estão apropriadamente conectados (a
ligação à terra deve ser considerada);
- A ventilação ambiente é adequada;
- O devido aperto das conexões.
- A tampa IP20 é bem fixada, si existente (veja seção
“Acessórios opcionais”)
ACESSÓRIOS OPCIONAIS
Tampa
A tampa opcional permite ao CLMD03 a obtenção do grau
de proteção IP20 de acordo com a IEC 60529,
considerando-se que bucins adequados sejam utilizados.
Fixá-la apropriadamente com quatro parafusos
(fornecidos com a tampa) (Figura #14.1 & 14.2). Esta
tampa de protecção impede as pessoas de tocar as
partes energizadas da unidade CLMD03 especialmente
quando expostos em áreas abertas. Recomenda-se a
perfuração de buraco(s) na tampa com uma serra-copo
do lado apropriado. Existem três bossas na tampa para a
utilização de bucins até o tamanho padrão PG36 (duas
pequenas bossas para unidades de capacitor duplo) ou
PG36 (uma grande bossa para unidades de capacitor
único). Passa-cabos também são permitidos.
Resistor de descarga
A unidade do capacitor CLMD03 é fornecidada com
resistores de descarga, instalados de fábrica, em acordo
com IEC 60831, permitindo a diminuação da tensão
residual à valor inferior à 50V após 1min. da desconexão
da alimentação. Certifique-se que o intervalo antes que o
CLMD03 seja re-energizado não é inferior à 40 seg. Não
seguir esta regra pode causar danos e reduzir a vida útil
do capacitor.
MANUTENÇÃO
1. Assegure-se de que os procedimentos foram
corretamente seguidos (veja o parágrafo Segurança);
2. Uma manutenção anual deverá incluir:
- Remova o depósito de poeira, limpe todas as partes;
- Verifique o aperto de todas as conexões elétricas;
- Verifique a temperatura ambiente;
- A verificação do estado das resistências de descarga.
Enquanto cada cuidado seja necessário para garantir que a
informação contida na publicação seja correta, nenhuma
responsabilidade legal pode ser aceita por qualquer imprecisão.
Não aceitamos responsabilidade por qualquer desuso do produto.
A companhia reserva o direito de alterar ou modificar as
informações aqui contidas em qualquer momento, tanto no quesito
técnico quanto em outros desenvolvimentos.
pt
12
Montaj yapılmadan önce ilgili personelin açıklamaları
dikkatlice okuması ve uygulanması gereklidir.
ÖNCE OKUYUNUZ
Güvenlik
UYARI!
Enerji kesildikten sonra 5 dk beklemeden
müdahale yapılamamalıdır. 5 dk beklendikten sonra ek
önlem olarak ölçü aletiyle DC gerilim ölçümleri yapılıp
kondansatörün deşarj olduğundan emin olunmalıdır.
CLMD03 kondansatörü güvenli şekilde kullanmak için
aşağıdakiler yerine getirilmelidir:
1. Montaj ve bakım işlemleri, işletmelerde sadece yetkili
kişiler tarafından yapılmalıdır.
2. Kondansatöre müdahale etmeden önce bağlantıları
sökülmelidir.
Kontrol ve Onay
- Etiketinde yazan bilgiler ile siparişinizin aynı olduğu
- CLMD03’ün hasar görmediği.
Herhangi bir yanlýþlýk veya hasar durumunda derhal en
yakýn ABB ofisi veya yetkili satýcýsý ile irtibata geçiniz.
Depolama
Dahili, kuru, temiz, korozif olmayan ortamda titreşim ve
darbelere karşı korunmalıdır.
Depolama sıcaklığı: en az -40°C/-40°F, en yüksek
75°C/167°F.
Nakliye
Tüm nakliye ve taşıma durumlarında, CLMD03’ün
sabitleme noktalarından ağırlığının taşınabilecek güçte
olması gereklidir.
UYARI!
Kurulumuyla ilgili belirtilen kurallara uyulmaması
kullanım süresinin azalması, diğer ekipmanlarda hasar
veya can tehlikesine neden olabilir.
KURULUM
Uygulama standartları
IEC 60831’in 1. ve 2. Bölümleri ile yürürlükteki
düzenlemeler.
Koruma
Standart IP00 ve opsiyonel olarak IP20 üst kapama
Kurulum ve kullanım
Dahili olarak katı yada sertleştirilmiş plakaya, sıcaklığın
bir yıl içerisinde (IEC 60831’de 1. Ve 2. Bölümdeki 25/D
ürün sıcaklığı ile ilgili belirtilen) 45°C/113°F, 24 saatte
55°C/131°F’i aşmayacak şekilde sabitlenmesi yapılabilir.
Tüm özellikler için etiketinden yararlanılmalıdır.
UYARI!
Pano içerisindeki kondansatör için ortam sıcaklığı
pano iç sıcaklığıdır, oda sıcaklığı değildir.
UYARI!
Diğer standart kondansatörlerde olduğu gibi,
CLMD03’lerin deşarj dirençleri, tristör anahtarlamalı
sistemlerdeki hızlı anahtarlamalar (en düşük 40sn) için
uygun değildir. Harici dirençler bunun yanında
kullanılmalıdır. Bu tür uygulamalarda sadece özel
tasarımlı kondansatörler kullanılmalıdır.
Yatay ve dikey montaj
CLMD03 kondansatörlerinde havalandırma alttan üste
gelecek şekilde yapılmalıdır.
Birden fazla CLMD03 yan yana (Şek. #1) sıralı olarak
monte edilebilir. Her bir grubun arasındaki mesafe en az
25mm olmalıdır (Şek. #2 & 3).
Düşey montajlar için taşıyıcı sabitlemeleri ve destek
plakaları kullanılarak hava akışı sağlanmalıdır (Şekil #4 &
5). Ters montaj yapılmamalıdır (Şek. #6)
Yatay montaj doğal hava akışı engellenmeyecek şekilde
yapılmalıdır (Şek. #7). Hava akışını engelleyecek
montajlar yapılmamalıdır (Şek. #8).
Pano içi montajı
UYARI!
Uyarılar sadece aşağıdaki sınırlar içerisinde
geçerlidir:
- En yüksek oda sıcaklığı: 40°C (1 saat).
- 24 saatin üzerinde ortalama oda sıcaklığı: 35°C.
- 1 yılın üzerinde ortalama oda sıcaklığı: 25°C.
Kondansatörler pano içerisine yerleştirildiğinde, hava
akımının uygun bir şekilde oluşmasına izin verilecek
şekilde pano tasarımı yapılmalıdır. Kondansatörlerin
ısınmasının önlenmesi için üzerlerinde hava değişimini
sağlayan havalandırma sistemleri yerleştirilmelidir.
Reaktörler ile birlikte kullanıldığında, ısılarının doğrudan
kondansatörlere gelmeyecek şekilde konulmalıdır. Isıl
engellerin kullanılması önerilir. Reaktörlerde genellikle ısı
dağılımı çok yüksek olduğu için, pano tasarımda dikkate
alınmalıdır.
1. Doğal hava dolaşımı
Hava girişi ile çıkışı arasındaki fark, hava dolaşımının
yeterli olması için yeteri kadar büyük olmalıdır. Pano
içerisinde hava kanalları oluşturularak sıcak bölümlerin
soğutulması sağlanabilir. Üst havalandırmanın kesiti,
alt kesitin en az 1,2 katı olmalıdır.
2. Zorlanmış hava dolaşımı
Havalandırma fanı kullanılarak zorlanmış hava
dolaşımı yapılaması bazen gerekli olabilir (Şek. #8).
Aşağıdaki hususlar dikkate alınmalıdır:
- En yüksek ortam için sıcaklığı kondansatörün kendi
sıcaklık etkisi de göz önüne alınmalıdır.
- Panel içerisinde kullanılan reaktör, kondansatör,
kontaktör ve sigortaların sıcaklıkları göz önüne
alınmalıdır.
- Her bir malzemenin izin verilen çalışma sıcaklıkları göz
önüne alınmalıdır.
- Kondansatörlerin konumlarına göre hava dolaşımının
nasıl olacağı göz önüne alınmalıdır.
- Kondansatörlerin yerleşimine göre hava dolaşımı göz
önüne alınmalıdır (Şek. #9).
3. Fan arızası yada başka sebeplerden oluşabilecek aşırı
sıcaklık artışları durumlarında kademelerin devreye
girmesini önlemek için aşırı sıcaklık algılayıcıları
kullanılmalıdır.
4. Filtrelerin ve fanların düzenli temizlenmesi gereklidir.
tr
13
tr
CLMD03 sabitleme (Şek. #10)
M6 ölçüsünde dört sabitleme deliği bulunmaktadır.
Simetrik olarak en az iki vida ile tutturulması gereklidir
(Şek. #11).
CLMD03 kondansatörlerinin güçlü bir şekilde durması için
tamamen sıkılı olduğuna emin olunmalıdır.
Elektriksel Bağlantı
Güç bağlantıları
CLMD03 aynı kasada tek bir kondansatör yada iki ayrı
kondansatör olarak yerleştirilebilir. Buna göre, tek set
(Şek. #12) ve iki set (Şek. #13) olarak 3-fazlı kondansatör
mümkündür.
Kablolar nominal akımın en az 1,5 katı taşıma kapasiteli
olarak seçilmelidir.
Kablolar bağlantı kolaylığı sağlayacak şekilde olmalıdır.
Bağlantı vidalarını sıkarken iyi bir elektriksel geçirgenlik
için 6NM tork uygulanmalıdır (DIN46-200’e göre).
Tüm bağlantıların sıkı bir şekilde yapıldığından emin
olunmalıdır. Üst kapatma kullanılıyorsa, tamamen
kapattığından emin olunmalıdır (Bkn. Opsiyonel
aksesuarlar)
Topraklama
CLMD03 tutturma noktaları, topraklama bağlantısı için
kullanılabilir. Dikkat: bu tasarmda CLMD03 kasası
yalıtkan bir yüzeye monte edilmişse, topraklama noktası
arasında ek bir kablo gereklidir.
Harmonikler
Harmonik bozulması olan sistemlerde kondansatörlerin
kullanımı şebekede rezonans riski oluşturur ve önlem
alınması gerekebilir.
DEVREYE ALMA
Şebeke gerilimi uygulanmadan önce şu hususlar kontrol
edilmelidir:
- Kablolamanın doğru yapılıp yapılmadığı (topraklama
kablosu ile birlikte)
- Ortam havalandırmasının yeterli olup olmadığı,
- Bağlantıların sıkı bir şekilde yapılıp yapılmadığı,
- Eğer varsa, IP20 için üst kapağının takılıp takılmadığı
(Bkn. Opsiyonel aksesuarlar)
EK AKSESUARLAR
Üst kapak
IEC 60529’a uygun olarak IP20 korumasının sağlanması
için üst kapak kullanılabilir. Üst kapak ile birlikte
gönderilen 4 vida ile üste sabitlenebilir (Şek. #14.1 &
14.2). Bu koruma ile CLMD03’ün enerjili bölümlerine
doğrudan temas engellenmiş olur.
Üst kapakta bir matkapla kablo girişleri için delik açılması
önerilir. Üst kapaktan kablo girişi için çiftli kapasitör
üniteleri için PG29 boyutunda iki adet, tek kapasitör
ünitesi için PG36 boyutunda bir adet delik açılıp kroşe ile
kablo girişi yapılabilir.
Deşarj dirençleri
CLMD03 kondansatörler, IEC 60831’e göre enerjisi
kesildikten sonra 1dk. içerisinde kondansatör üzerinde
kalan gerilimi 50V’un altına düşürülmesi için deşarj
dirençleri ile birlikte üretilmektedir. Tekrar enerji
verilmeden önce geçen sürenin 40 sn. den uzun
olduğundan emin olunmalıdır. Bunun dışındaki bir
çalışma, hasara neden olacak ve kondansatör ömrünü
kısaltacaktır.
BAKIM
1. Güvenlik uyarılarının sağlanmalıdır (Bkn. “Güvenlik”
bölümü);
2. Yıllık bakım için:
- Tüm tozlu bölümler temizlenmelidir;
- Elektriksel bağlantılar kontrol edilmelidir;
- Ortam sıcaklığı kontrol edilmelidir;
- Deşarj dirençlerinin durumu kontrol edilmelidir.
Bu belgede yazılı tüm bilgilerin doğrudur ve güvenli bir çalışma için
uyulması gereklidir. Ürünün yanlış kullanımı sonucu oluşan
sorumluluk kabul edilmemektedir. Üretici, teknik veya diğer
gelişmelerden dolayı bilgilerin güncellenmesi hakkını saklı tutar.
14
Dieses Dokument vor der Installation sorgfältig lesen und
für Personen, die mit der Installation, Wartung oder mit
dem Betrieb beauftragt sind, stets zur Verfügung halten.
LESEN SIE DIES ZUERST
Gesundheit & Sicherheit
ACHTUNG!
Vor Arbeiten an CLMD03 Kondensatoren
nach dem Freischalten erst 5 Minuten Entladezeit
abwarten, danach seine Spannungsfreiheit
(Gleichspannung!) prüfen.
Für den sicheren Gebrauch der Kondensatoreinheiten
folgendes sicherstellen:
1. Installationen und Wartung sind nur von autorisiertem,
qualifiziertem Personal in Übereinstimmung mit den
örtlichen Vorschriften vorzunehmen;
2. Das Gerät ist von der Spannungsversorgung
freizuschalten, bevor sich Zugang verschafft wird.
Wareneingangskontrolle
Die CLMD03 Kondensatoreinheiten auspacken und
überprüfen, dass
- die Daten auf dem Typenschild mit der Bestellung und
den örtlichen Vorschriften übereinstimmen,
- die CLMD03 Kondensatoreinheiten nicht beschädigt
sind.
Jeglicher Verlust oder Beschädigung sollte unverzüglich
der nächsten ABB Vertretung gemeldet werden.
Lagerung
Innenraum, in trockener, staubfreier und nicht
korrodierender Umgebung, geschützt vor Vibration und
Stößen.
Lagertemperatur: T° min.: -40°C/-40°F, T° max.:
75°C/167°F
Transport und Handhabung)
Bei schwierigen Transportbedingungen (der Anlage) ist
sicherzustellen, dass die Montagepunkte an denen der
CLMD03 befestigt ist stark genug sind um evtl,
Erschütterungen oder Vibrationen auszuhalten.
ACHTUNG!
Nichtbeachtung dieser Anleitung kann zu
vorzeitiger Alterung der Kondensatoren, Schäden an den
Anlagen und Verletzungen von Personen führen.
INSTALLATION
Anzuwendende Normen
IEC 60831 Teil 1 und 2 bzw. EN 60831 Teil1 und 2. Gültige
lokale Vorschriften.
Schutz
Standardmäßig IP 00. IP 20 bei der Verwendung des
optionalen Deckels.
Einbau- und Umgebungsbedingungen
Innenraum-Installation auf festem Untergrund oder
montiert auf fester Platte oder Rahmen in gut belüfteter
Umgebung, wo die Umgebungstemperatur 35°C/95°F im
Jahresmittel, 45°C/113°F im 24 Stunden-Mittel und
55°C/131°F nicht überschritten wird (entsprechend IEC
60831 Teil 1 und 2 für die Kategorie -25/D). Beachten Sie
immer auch das Typenschild um die genauen
Spezifikationen zu prüfen.
ACHTUNG!
Die Umgebungstemperatur für
Kondensatoren in einem Schaltschrank ist die Temperatur
an den Kondensatoren und nicht die Raumtemperatur
außerhalb des Schrankes.
ACHTUNG!
Wie bei anderen marktüblichen
Kondensatoren sind die Entladevorrichtungen bei
CLMDO03-Kondensatoren nicht für den Einsatz mit
kurzen Schaltzeiten geeignet, wie sie bei Verwendung von
Thyristoren auftreten (kleinste zulässige
Wiederzuschaltzeit: 40 sec.). Zusätzliche externe
Entladevorrichtungen sind keine Lösung des Problems, in
solchen Fällen müssen speziell ausgelegte
Kondensatoren eingesetzt werden.
Senkrechte und waagerechte Montage
Die CLMD03 Einheiten sind so zu montieren, dass eine
natürliche Luftbewegung zwischen den Einheiten von
unten nach oben statt finden kann. Mehrere CLMD03
Kondensatoren können direkt nebeneinander montiert
werden, wenn sie sich in einer Reihe befinden (Fig. #1).
Dreieckige und quadratische Anordnungen sind nicht
zulässig.
Der minimale Gehäuseabstand zwischen
Kondensatorgruppen beträgt 25mm (Fig. #2 & 3).
Bei senkrechter Montage sind gelochte Montageplatten
oder Traversen zu benutzen, um den Kühlluftdurchgang
zwischen den Kondensatoren zu gewährleisten (Fig. #4 &
5). Der Überkopf-Einbau ist nicht zulässig (Fig. #6). Bei
waagerechter Montage muss der Kühlluftweg ohne
größere Behinderungen zwischen den Kondensatoren
hindurch führen (Fig. #7). Blockieren der Kühlluftführung
ist nicht zulässig (Fig. #8).
Einbau in Schaltschränke
WARNUNG! Die Richtlinien gelten nur, wenn folgende
Grenzen sichergestellt sind:
- Kurzzeitige Raumtemperatur maximal : 40°C (1
Stunde).
- 24-Stunden-Mittelwert der Raumtemperatur maximal:
35°C.
- Jahresmittelwert der Raumtemperatur maximal: 25°C.
Beim Einbau in Schaltschränke sollten die Kondensatoren
so angeordnet werden, dass eine optimale Kühlung
gewährleistet ist. Komponenten mit großer Verlustleistung
sollten oberhalb der Kondensatoren angeordnet werden.
Filterdrosseln sollten so angeordnet werden, dass die
Kondensatoren keiner direkten Strahlungswärme
ausgesetzt sind. Eine thermische Barriere ist notwendig.
Filterdrosseln erzeugen üblicherweise soviel
Verlustleistung, dass der thermische Einfluss durch
Konvektion ebenfalls berücksichtigt werden muss.
1. Natürliche Belüftung (Eigenkonvektion)
Der Höhenabstand zwischen Luftein- und –austritt sollte
möglichst groß sein. Die Luft sollte so geführt werden,
dass die heißesten Bereiche im Schrank besonders gut
gekühlt werden. Die Luft sollte den Schrank von unten
nach oben durchströmen.
de
15
de
Der Querschnitt der Luftaustrittsöffnung soll mindestens
dass 1,2fache der Lufteintrittsöffnung betragen.
2. Zwangsbelüftung In einigen Fällen ist eine
Zwangsbelüftung erforderlich (Fig. #8). Bitte
berücksichtigen Sie die Empfehlungen:
- Beachten Sie maximale Umgebungstemperatur am
Aufstellungsort unter Berücksichtigung der
Verlustleistung der Kondensatoranlage
- Beachten Sie Verlustleistung aller Komponenten und
Geräte im Schrank: Drosseln, Kondensatoren, Schütze,
Sicherungen etc.
- Beachten Sie die maximal zulässigen Temperaturen für
alle Komponenten und Geräte
- Beachten Sie die Führung der Kühlluft insbesondere in
Hinblick auf die Anordnung der Kondensatoren (Fig.
#9).
3. Der Einsatz einer Übertemperaturüberwachung wird
empfohlen, um die Kondensatorbank bei Ausfall des
Ventilators oder Übertemperatur aus anderen Gründen
abzuschalten.
4. Eine regelmäßige Wartung und Reinigung der
Lufteintritts- und Luftaustrittsgitter (bzw. –filter) ist
erforderlich, anderenfalls kann die Kühlung schnell
unwirksam werden.
CLMD03 Befestigung (Fig.#10)
Jeder CLMD03 Kondensator ist mit Löchern für die
Fixierung mit M6-Schrauben ausgestattet (M6-Schrauben
nicht im Lieferumfang). Für eine ordentliche Befestigung
müssen mindestens 2 diagonal angeordnete
Montagelöcher verwendet werden (Fig. #11). Es ist
sicherzustellen, dass die Belastbarkeit der Montageplatte
und deren Befestigung ausreichend sind, um das Gewicht
der CLMD03 Einheiten zu tragen.
Elektrischer Anschluss
Leistungsanschlus
Der CLMD03 ist entweder mit einem oder zwei internen
Kondensatoren in einem Gehäuse bestückt. Demzufolge
sind ein (Fig. #12) oder zwei (Fig. #13) 3-phasige
Anschlüsse vorhanden.
Anschlussleitungen sollen mindestens für den 1,5-fachen
Kondensatornennstrom bemessen sein. Die
Anschlussleitungen müssen mit Kabelschuhen
ordnungsgemäß versehen werden.
Für eine gute elektrische Verbindung ist ein
Anzugsmoment von 6 Nm zu verwenden (DIN 46200).
Abschließend kontrollieren, dass alle Verbindungen
festgezogen sind. Sollte der optionale Deckel mitgeliefert
sein, ist sicherzustellen, dass dieser ebenfalls fest sitzt
(siehe Abschnitt: Optionales Zubehör -unten).
Erdung
Die Erdung wird erreicht durch die Montagepunkte am
Gehäuse des CLMD03. Anmerkung: Dies bedeutet
natürlich, dass im Falle einer isolierten Montage des
CLMD03 eine seperate leitfähige Verbindung zwischen
CLMD03 und der Erde erforderlich ist (PE-Leiter).
Oberschwingungen
IDie Installation von Kondensatoren in
oberschwingungsbelasteten Netzen kann besondere
Vorsichtsmaßnahmen erfordern, insbesondere wenn das
Risiko von Resonanzerscheinungen besteht.
INBETRIEBNAHME
Vor dem Anschluss an die Versorgungsspannung ist zu
prüfen, dass
- die CLMD03 Einheiten korrekt montiert und sicher
befestigt sind,
- korrekte Leitungen richtig und fest angeschlossen und
sicher befestigt sind (gegebenenfalls ist die Erdung zu
prüfen),
- die Belüftung der Umgebung ausreichend ist,
- der optionale Deckel fest montiert ist (siehe Abschnitt:
Optionales Zubehör unten).
OPTIONALES ZUBEHÖR
Deckel
Der optionale Deckel macht den CLMD03 zu einem IP 20
geschützten Bauelement entsprechend der IEC 60529,
wenn die geeigneten Verschraubungen, Würgenippel oder
Kabeltüllen benutzt werden. Montieren Sie den Deckel mit
den mitgelieferten Druckschrauben (Fig. #14.1 & 14.2).
Dieser Schutzdeckel verhindert die Berührung unter
Spannung stehender Teile des CLMD03.
Falls Löcher benötigt werden, empfehlen wir, diese mit
einer geeigneten Lochsäge am passenden Ort
anzubringen. Drei vorgeprägte Löcher sind vorgesehen für
die Verwendung von Kabelverschraubungen bis zur
Standardgröße PG29 (2 kleine vorgeprägte Löcher für
Doppelkondensator-Einheiten) oder PG36 (1 großes
vorgeprägtes Loch für Einzelkondensator-Einheiten).
Kabeltüllen sind auch erlaubt.
Entladewiderstand
Der CLMD03 Kondensator wird mit einem angebauten
Entladewiderstand ausgeliefert entsprechend IEC 60831
und entlädt sich innerhalb einer Minute auf eine
Restspannung von unter 50 V nach Unterbrechung der
Versorgungsspannung.
Stellen Sie sicher, dass der Kondensator nicht schneller
wiedereingeschaltet wird, als nach mindestens 40
Sekunden.
Eine Missachtung dieser Anweisung kann zu Ausfällen
führen und reduziert die Lebenserwartung des
Kondensators.
WARTUNG
1. Sicherstellen, dass die Sicherheitsvorschriften
eingehalten werden (siehe Abschnitt „Gesundheit &
Sicherheit“);
2. Die jährliche Wartung sollte umfassen:
- Entfernen von Staubablagerung, Reinigen aller Teile;
- Überprüfen der Festigkeit aller elektrischen
Verbindungen;
- Überprüfen der Umgebungstemperatur.
- Überprüfen des Entladewiderstandes
Obwohl höchste Sorgfalt aufgewendet wurde um sicherzustellen,
dass die Informationen in diesem Dokument korrekt sind, wird keine
gesetzliche Haftung für eventuelle Unkorrektheiten übernommen.
Wir übernehmen keine Verantwortung für jegliche nicht
bestimmungsgemäße Verwendung dieses Produkts. Die Firma
behält sich das Recht vor, die hier gegebenen Informationen zu
jeder Zeit aufgrund von technischen oder anderen Entwicklungen
zu ändern oder zu modifizieren.
16
zht
安裝之前情詳細讀本手冊,並將此手冊交由負責安裝、
維護和操作的專業人員保管。
請先
安全
注意
!斷電後須待五分鐘方可進行操作。五分鐘後,先小心
進行DC電壓量測,並請確認電容器已由放電電阻完全放電
!!
為維護CLMD03電容器單體之使用安全,
在安裝前請確保:
1.安裝及維護必須由當地現行法例許可之合格人員操作。
2.設備必須確定已完全切離電源。
驗收檢
CLMD03 開箱後請依下列驟檢查﹔
- 請確認銘牌規格是否符合您採購之項目及當地法規。
- 確認CLMD03本體外觀無損壞。
如有任何損壞,請立即與您最近之ABB或經銷代理商連繫
儲存方式
請置放在室,乾燥,無塵及無腐蝕性之環境,並避免受到
震動及衝擊。
置放度: 最低度:
- 40°C/ - 40°F,最高度:75°C/ 167°F
運輸及搬運
運輸途中請避免劇烈的震動,且務必確認CLMD03能妥善固
定後,方可運送。
注意
!錯誤的安裝方式可能導致電容器提早損壞,其他材料
破損或本體損傷。
安裝
使用標準
依照IEC60831-1&-2
的規範和建議,以及當地現行的法規。
保護等級
CLMD03單體之保護等級為IP00,選配單體(含上蓋)保護
等級為IP20
安裝及使用
電容器應安裝在屋平穩的基礎座或牢固的平台,且注意
通風良好的地方。周圍環境度:年均應低於35°C/ 95
°F,單日24小時最高度應低於45°C/ 113°F及低於55
°C/ 131°F之短時間使用(依據IEC60831 Part 1 2 中針對
- 25/ D 類型品的規定)
必須依照銘牌實際之規格為基準。
注意
!環境度之定義為電容器裝置於盤體,圍繞電容器的
度,非為圍繞外部盤體之度。
注意
!如同其他電容器之規範標準,CLMD03其放電設計並
不適用於快速補償閘流體開關之系統(切離後最時間為
40)外部熔絲也並不可以理等同之
設計的電容器可以使用在閘流體開關的系統中.
垂直平安裝
CLMD03電容器必須安裝在自然通風對流由下上的地方
數個CLMD03電容器可許安裝於同一排列上(Fig. #1)
三角或是方列方式是不被允許的,而鄰近的電容
器之間必須25mm以上之空隙(Fig. #2 & 3)
倘若垂直安裝時,必須裝置於已鑽孔之固定支撐架
上,讓空氣對流環繞電容器單(Fig. #4 & 5)
CLMD03電容器不可置裝設(Fig. #6)
倘若平安裝時,安裝時須注意空氣對流動(Fig.
#7)。避免安裝在自然通風不良之(Fig. #8)
安裝
注意
!安裝準則僅適用於以下限制規定
- 小時最高環境40°C
- 超過24小時之最高環境平均35°C
- 超過一年之最高環境平均 25°C
當電容器安裝於盤體,須置放於最佳散熱位置。請
能將電容器裝置於容易散熱,並避免電容器過熱
當有安裝電器時,須注意電是否會直
接影響到電容器一般而言,電生較多
對流影響需被考量,以避免造成電容器受到傷
1. 空氣對流
排氣孔之不同高度設計,
應以最大空氣對流量設計,由
抽入冷空氣,並由排出熱氣
上方的排氣孔
設計最應為部進氣孔之1.2
2. 強制通風
強制性的通風風有時是必須的(Fig. #8).
參考以下建議:
- 考慮安裝之最環境,包含電容器本發熱量。
- 考慮在盤體各元件散熱,如:器,電容器,
接觸器,保險絲等等..
- 同時考慮所有設備及元件之最大允度。
- 考慮設計電容器安裝置之空氣的流通 (Fig. #9)
3. 當風無法作動,或其他原因導致高時,
應使用保護裝置切離電容器盤。
4. 清洗濾網過髒濾網將使
得排效果降
17
CLMD03
安裝固定
(Fig. # 10)
CLMD03固定M6螺絲釘(CLMD03附螺絲釘),最
須固定兩孔且為對之方式(Fig. #11).
請確認有的固定及螺絲釘是能支撐CLMD03電容器本
()量。
電力連
電源
CLMD03電容器將依容量提不同的單體規格,可能
一至二組電容器在同一組。單之電容器單體(Fig.
#12) 二組之電容器單體組成(Fig.
#13)將提供三相之連接端子
纜線定電流最小應為體電容器組正常電流的1.5
並應確保有的連牢固及選用適當的電纜末端套管。
鎖緊電力連螺絲釘,建議使用的力6Nm (牛頓-
)(依據DIN46-200標準)
確認有連接皆鎖緊
有選購上蓋,請確認其完全定。(照以下選用配’)
地方式是透過CLMD03固定孔來
外電纜線CLMD03地裝置
,以CLMD03固定在絕緣物件上。
諧波
電容器安裝於受諧波干擾的電上時,需要一些特別
預防措施其是在有可能發生諧波共振時。
試車
在設備送電之前,請檢以下項:
- 接線已完(請務必)
- 環境通風良好
- 鎖緊相關連
- IP20 之上蓋已確實安裝,如有需要
(參照以下選用配件’)
選用配
上蓋
選配 外的上蓋可使CLMD03 IEC
60529規範之IP20保護等級。
本上蓋將提供四個螺絲組供鎖(與上蓋一起)(Fig.
#14.1 & 14.2)
此上蓋將可提保護,以避免人員於維及操作時可能
觸活電部分。
我們建議使用開(鑽孔機)將上蓋合適之側邊
上蓋將提供三個凸起面讓纜接頭使用,標準尺寸PG2
9(二個較小的凸起面供給二個電容器單 )
PG36(一個較大凸起面供給一個電容器單)。電纜鎖
可以適用。
放電電阻
CLMD03原廠 建有放電電阻以符合IEC
60831之規範,在電源切離後,殘留電壓將於分鐘
50V以下。請確認再投入時間至少須間40以上,
短的再投入時間,會造成電容器之使用壽命減短。
維護保
1. 確保安全程序已完(參考”Safety章節)
2. 年度維護保含:
- 塵,清潔所有的零組件
- 有電器連是否牢固
- 環境
- 放電電阻之
份資料業經本公司細心準備以確保容無誤,然若有不確之
。本公司不負任何法責任。無何時其他技術上的發展
公司得留變更修改文件所容的權利.
zht
Fig. #4 / Şek.#4
18
Fig. #1 / Şek.#1 Fig. #2 / Şek.#2
Fig. #3 / Şek.#3
Fig. #5 / Şek.#5
19
Fig. #8 / Şek.#8
Fig. #7 / Şek.#7
Fig. #6 / Şek.#6
Fig. #9 / Şek.#9
20
Fig. #11 / Şek.#11
Fig. #10 / Şek.#10
21
Fig. #14.2 / Şek.#14.2
Fig. #14.1 / Şek.#14.1
Fig. #13 / Şek.#13Fig. #12 / Şek.#12
2GCS202081A0030 2009-11-12
ABB n.v.
Power Quality Products
Avenue Centrale, 10
Zoning Industriel de Jumet
B-6040 Charleroi (Jumet), Belgium
Phone: +32 71 250 811
Fax: +32 71 344 007

Transcripción de documentos

en it Power LV Capacitor CLMD03 Istruzioni per l'installazione, l'uso e la manutenzione fr es Installation, Operation & Maintenance Instructions Condensatori di potenza Bassa tensione CLMD03 Condensadores de potencia de baja tensión CLMD03 Instructions d’installation, d’utilisation et d’entretien tr pt Instrucciones de Instalación, Utilización y Mantenimiento Condensateurs de puissance basse tension CLMD03 Capacitor de Potência Baixa Tensão CLMD03 AG Güç Kondansatörü CLMD03 Instruções para instalação, Utilização e manutenção Montaj, İşletme & Bakım Açıklamaları t de zh Niederspannungs低壓電力電容器 TYPE CLMD03 Leistungskondensator CLMD03 Installations-, Inbetriebnahmeund Wartungsanleitung 安裝,操作,維護手冊 en and not around the cubicle. Before installation, read this notice carefully and keep it at disposal of people in charge of installation, maintenance and operation. WARNING! Like other standard capacitor units, CLMD03 discharge devices are not suitable for use with rapid switching rates like thyristor switched banks (minimum off time: 40 sec). Additional external resistors are not a solution for such cases. Only specially designed capacitors must be used in such applications. READ THIS FIRST Safety WARNING! Wait 5 min. after isolating supply before handling. After the 5 min. wait and as an additional precaution before commencing work, carefully proceed with DC voltage measurement on the terminals and make sure of the capacitor discharge. Vertical and horizontal mounting The CLMD03 capacitors must be fixed in such a way as to ensure a natural airflow from bottom to top. Several CLMD03 units can be installed side by side, provided that they are in line (Fig. #1). Triangle and square configuration are not allowed. The minimum free space between groups of in-line adjacent units is 25 mm (Fig. #2 & 3). In case of vertical mounting, use a punched mounting plate or support bars to allow free airflow around capacitors units (Fig. #4 & 5). Do not mount upside down. (Fig. #6) In case of horizontal mounting, install so that the natural airflow goes through the units without major constraints (Fig. #7). Do not mount so that the natural airflow is blocked (Fig. #8). For a safe use of CLMD03 capacitor units, please ensure: 1. Installation and maintenance are undertaken only by authorized and qualified personnel, in accordance with current local regulations; 2. Isolate the equipment from the supply before attempting to gain access. Inspection on reception Unpack the CLMD03 and check that: - data on the label correspond to those of your purchase order and local regulations; - the CLMD03 is not damaged. Any loss or damage should be notified immediately to your closest ABB agent. Installation in a cubicle WARNING! Guidelines only apply if the following limits are respected: - Maximum room temperature: 40°C (1 hour). - Average maximum room temperature over 24 hours: 35°C. - Average maximum room temperature over 1 year: 25°C. Storage Indoor, in dry, dust free and non-corrosive environments, protected from vibrations or shocks. Storage temperature: minimum: -40°C/-40°F, maximum: 75°C/167°F. Transportation and handling In case severe conditions of transportation are expected, make sure the fixation points are strong enough to withstand weight of the CLMD03 and vibrations that may occur. When the capacitors are installed in a cubicle the components should be placed in such a way as to optimize the cooling. Do preferably place devices with high heat dissipation above the capacitors to avoid overheating them. When reactors are used they should be placed in such a way that they do not radiate heat directly on the capacitors. A thermal barrier is recommended. Reactors do in general dissipate much more heat, so their thermal impact through convection must also be taken into account. 1. Natural air circulation The difference in height between air inlet and air outlet should be large enough to improve the air circulation. The airflow should be channeled in such a way as to well cool the hottest spots in the cubicle. Air should flow from the bottom to the top of the cubicle. The crosssection of the top air outlet should be at least equal to 1.2 times the cross-section of the bottom air inlet. 2. Forced ventilation Forced cooling using a fan is sometimes required (Fig. #8). Please refer to the following recommendations: - Consider the maximum ambient temperature of the installation site including the heating effect of the capacitor installation itself. - Consider the heat dissipated from all the components and apparatus in the cubicle: reactors, capacitors, contactors, fuses, etc. WARNING! Failure to respect the installation rules may lead to premature failure, other material damage to installations or bodily injury. INSTALLATION Applicable standards IEC 60831 Parts 1 and 2. Current local regulations. Protection IP00 by default and IP20 with optional top cover. Installation and use Indoor installation on firm foundation or fixed on a rigid plate/frame in well-ventilated situations where the air temperature around the capacitor does not exceed 35°C/95°F over one year, 45°C/113°F over 24 hours and 55°C/131°F (according to IEC 60831 Parts 1 and 2 for a 25/D temperature category product). Always refer to the nameplate for exact specifications. WARNING! The ambient temperature for capacitors inside a cubicle is the temperature around the capacitors 2 en - Consider the maximum permissible temperatures for all the components and apparatus. - Consider how to direct the airflow with respect to the position of the capacitors (Fig. #9). 3. The use of an overtemperature protection is recommended in order to switch the bank off in case of fan failure or overtemperature due to other cause. 4. Regular maintenance and cleaning of any filters is necessary. Without regular cleaning the cooling system may become inefficient. with the 4 push-screws (delivered with the top cover) (Fig. #14.1 & 14.2). This protection cover prevents people from touching live part of the CLMD03 unit especially when exposed in open areas. We recommend to drill hole(s) in the top cover with a hole saw at the appropriate side. Three bosses are provided in the top cover for the use of cable glands up to the standard size PG29 (two small bosses for dual capacitor units) or PG36 (one large boss for single capacitor units). Cable grummets are also allowed. CLMD03 fixation (Fig. #10) Four fixation holes are provided for M6 screws (not included). At least two of the fixation holes must be used in a symmetrical way (Fig. #11). Make sure that the rigidity of the support and the screws are sufficient to bear the weight of the CLMD03 capacitor unit(s). Discharge resistor The CLMD03 capacitor unit is delivered with factoryinstalled discharge resistors to comply with IEC 60831 and allow a decrease of the residual voltage to less than 50V after 1 min. disconnection from supply. Make sure the delay before the CLMD03 is re-energized is not shorter than 40 sec. Failure to follow this rule may cause damage and reduce the lifetime of the capacitor. Electrical connection Power supply CLMD03 is available as a unit that houses either a single capacitor or two individual capacitors in the same case. Consequently one (Fig. #12) or two (Fig. #13) sets of 3phase terminals are provided. Cables should be rated at minimum 1.5 times the nominal capacitor current. Appropriate cable shoes must be used in accordance with good common practice of electrical installation. While tightening the bolt, a torque of 6Nm must be applied for proper electrical connection (according to DIN46-200). MAINTENANCE 1. Ensure safety procedures are completed (see paragraph “Safety”); 2. Yearly maintenance should include: - Removal of dust deposits, cleaning of all parts; - Check of tightness of all electrical connections; - Check of ambient temperature; - Check condition of discharge resistors. Ensure that all connections are tight. If there is an optional top cover, ensure that it is properly fixed (see section ‘Optional accessories’ below). Earthing Earthing is achieved through fixation points of the CLMD03 enclosure. Remark: this implies that an extra cable between the CLMD03 enclosure and the earthing contact of the installation is required in case the CLMD03 unit is fixed on an isolating material. Harmonics Installation of capacitors on networks disturbed by harmonics may require special precautions especially when there is a risk of resonance phenomena. COMMISSIONING With the equipment isolated from the supply, check: - Cabling is properly connected (earthing may be considered) - Ambient ventilation is adequate - Correct tightness of the connections. - IP20 top cover is well fixed, if any (see section “Optional accessories”) OPTIONAL ACCESSORIES While every care is taken to ensure that the information contained in this publication is correct, no legal responsibility can be accepted for any inaccuracy. We do not accept responsibility for any misuse of the product. The company reserves the right to alter or modify the information contained herein at any time in the light of technical or other developments. Top cover The optional top cover allows the CLMD03 unit to get IP20 protected as per the IEC 60529 provided that appropriate glands or grummets are used. Fix it properly 3 it Prima dell'installazione, leggere queste note con attenzione e tenerle a disposizione del personale addetto all'installazione, alla manutenzione ed al funzionamento. Far sempre riferimento ai dati di targa per le esatte specifiche tecniche La temperatura ambiente del ATTENZIONE! condensatore all’interno di un quadro e’ la temperatura attorno al condensatore e non attorno al quadro. LEGGERE PRIMA Salute e sicurezza ATTENZIONE! aspettare 5 min. dopo aver tolto l’alimentazione prima di maneggiare. Dopo aver atteso 5 min, come precauzione aggiuntiva prima di iniziare ad utilizzare il prodotto, procedere con cautela alle misurazioni in cc sui terminali e accertarsi che il condensatore sia scarico. ATTENZIONE! Come per gli altri condensatori standard, i dispositivi di scarica degli CLMD03 non sono adatti all'utilizzo con commutazione rapida come per es. inserimento attraverso tiristori (tempo minimo di spegnimento: 40 sec). Aggiungere resistori esterni aggiuntivi non risolve il problema, solo condensatori opportunamente studiati possono essere utilizzati in queste applicazioni. Per un uso sicuro dei condensatori CLMD03, assicurarsi: 1. Che l'installazione e la manutenzione siano effettuate da personale autorizzato e qualificato, in accordo con i vigenti regolamenti locali; 2. Di isolare l'equipaggiamento dall’ alimentazione prima di intervenire. Montaggio verticale e orizzontale I CLMD03 devono essere fissato in modo da assicurare il naturale flusso d'aria, dal basso verso l'alto. I CLMD03 possono essere installati affiancati tenendo conto che siano in linea (Fig. #1)., altre configurazioni per es. a triangolo non sono consentite. Lo spazio minimo tra i vari gruppi in linea adiacenti è di 25mm (Fig. #2 & 3). Nel caso di montaggio verticale usare un piatto di montaggio punzonato o barre di supporto per permettere la libera circolazione dell’aria intorno ai condensatori (Fig. #4 & 5). Non montare sottosopra. (Fig. #6) Nel caso di montaggio orizzontale, installare in modo tale da permettere la naturale circolazione dell’aria attraverso le unita’ senza ulteriori impedimenti (Fig. #7). Non montare bloccando la naturale circolazione dell’aria (Fig. #8). Ispezione al ricevimento Disimballare i CLMD03 e verificare che: - I dati sull'etichetta corrispondano al vostro ordine di acquisto ed ai regolamenti locali; - che i CLMD03 non sia danneggiato. Qualunque danno deve essere immediatamente notificato all'ufficio ABB più vicino. Immagazzinamento In ambiente coperto, secco, senza polvere e non corrosivo, protetto da colpi e vibrazioni. Temperatura di immagazzinamento :T° min.: -40°C/-40°F T° max.: 75°C/167°F Installazione in un quadro ATTENZIONE! Linea guida applicabile solo se Ie seguenti limitazioni sono rispettate: - Temperatura massima del locale 40°C (1 ora). - Media della temperatura massima del locale oltre le 24 ore: 35°C. - Media della temperatura massima del locale oltre 1 anno: 25°C. . Trasporto & maneggiamento In caso di condizioni di trasporto severe, verificare che i punti di aggancio sia sufficientemente robusti da sopportare il peso del CLMD03 e le eventuali vibrazioni che possono presentarsi. ATTENZIONE! Il non rispetto delle regole d’installazione puo’ portare a un prematuro guasto, a danni materiali alle installazioni o a rottura dell’involucro. Quando i condensatori sono installati in un quadro i componenti devono essere disposti in modo tale da ottimizzare il raffreddamento. Preferibilmente sistemare i dispositivi con alta dissipazione di calore al di sopra dei condensatori per evitare il loro surriscaldamento. Quando vengono usati i reattori, essi devono essere collocati in modo tale che non irradino il calore direttamente sui condensatori. Viene raccomandata una barriera termica. I reattori generalmente dissipano molto più calore e anche il loro impatto termico per convezione deve essere tenuto in considerazione. 1. Naturale circolazione dell’aria La differenza in altezza tra l’aria in entrata e quella in uscita dovrebbe essere maggiore per migliorare la circolazione dell’aria. Il flusso dell’aria dovrebbe essere canalizzato per ben raffreddare i punti piu’ caldi del quadro. L’aria dovrebbe fluire dal basso verso l’alto del quadro. L’intersezione dell’aria in uscita dall’alto dovrebbe essere almeno uguale a 1.2 volte dell’aria in entrata dal basso. 2. Ventilazione forzata A volte e’ richiesto il raffreddamento forzato usando un ATTENZIONE! Il non rispetto delle regole di installazione puo’ portare ad un premature guasto, a danni materiali alle installazioni o a rottura dell’involucro. INSTALLAZIONE Norme applicabili IEC 60831 Parti 1 e 2. Regolamenti vigenti locali. Protezione IP00 standard e IP20 con calotta opzionale. Posizionamento Installazione al coperto su fondazioni stabili o fissato ad una piastra/telaio rigidi in condizione di buona ventilazione dove la temperatura dell’aria intorno al condensatore non ecceda i 35°C/95°F nell'arco dell'anno e i 45°C/113°F nell'arco delle 24 ore e 55°C/131°F (secondo la IEC 60831 Parti 1 e 2 per prodotti di categoria -25/D). 4 it - - 3. 4. - La calotta IP20 è ben fissata, se presente (vedi sezione”Accessori opzionali” sotto) ventilatore (Fig. #8). Prego fare riferimento alle seguenti raccomandazioni: Considerare la temperatura piu’ alta del luogo di installazione includendo l’effetto della dissipazione dei condensatori stessi. Considerare il calore disperso da tutti i componenti e dall’apparato all’interno del quadro: reattori, contattori, condensatori , fusibili ecc. Considerare la temperatura massima permessa per tutti i componenti e apparati. Considerare come convogliare il flusso dell’aria rispetto alla posizione dei condensatori (Fig. #9). E’ raccomandato l’uso di una protezione da sovratemperatura in modo da ottenere lo spegnimento del banco in caso di guasto della ventola dovuto ad altre cause. E’ necessaria la regolare pulizia e manutenzione dei filtri. Senza una regolare pulizia il sistema di raffreddamento potrebbe essere inefficiente. ACCESSORI OPZIONALI Calotta IP20 La calotta opzionale consente al CLMD03 di raggiungere un grado di protezione IP20 in base alla IEC60529 considerando che flange e guarnizioni adatte siano utilizzate. Fissarla correttamente con le 4 viti fornite con la calotta (Fig. #14.1 & 14.2). Questa calotta protettiva protegge le persone da contatti accidentali con le parti in tensione del CLMD03 specialmente quando gli stessi sono in spazi aperti. Noi raccomandiamo di forare (con uno o più buchi) il coperchio superiore con una punta circolare sul lato appropriato. Tre flange sono fornite nel coperchio superiore per l'utilizzo dei pressacavi fino alla grandezza standard PG29 (due piccole flange per unità doppie di condensatori) o PG36 (una flangia grande per unità di condensatore singola). Guarnizioni per i cavi sono altresì permesse. Fissaggio del CLMD (Fig. #10) Il prodotto ha quattro fori di fissaggio per viti M6 (non incluse). Almeno due fori di fissaggio in posizione simmetrica devono essere utilizzati (Fig. #11). Assicurarsi che la rigidità del supporto e delle viti sia sufficiente a sostenere il peso del(i) condensatori CLMD03. Resistenze di scarica I CLMD03 sono forniti con all’interno una resistenza di scarica per essere conformi alla IEC60831 e permette una riduzione della tensione residua a meno di 50V dopo 1 ms di sconnessione dall’alimentazione. Prestare attenzione al fatto che il ritardo prima che il CLMD03 sia ricaricato non sia inferiore ai 40 sec. Non seguire questa regola potrebbe causare danni e ridurre la vita del condensatore. Collegamenti elettrici Alimentazione di potenza I CLMD03 sono disponibili in unità che includono sia uno sia due singoli condensatori nello stesso case. Di conseguenza vengono forniti uno (Fig. #12) o due (Fig. #13) set di terminali trifasi. I cavi devono essere dimensionati al minimo per 1.5 volte la corrente nominale del condensatore. Appropriati terminali vanno utilizzate in accordo con l’installazione elettrica a regola d’arte. Mentre, per stringere il bullone, deve essere applicata una coppia di 6Nm per raggiungere una corretta connessione elettrica (in accordo alla DIN46-200) Assicurarsi che tutte le connessioni siano ben avvitate. Se è presente anche una calotta protettiva aggiuntiva assicurarsi che sia fissata correttamente (vedi sezione”Accessori opzionali” sotto) MANUTENZIONE 1. Assicurarsi che la procedura di sicurezza sia completata (vedere Salute & Sicurezza); 2. La manutenzione annuale include: - La rimozione dei depositi di polvere, pulire tutte le parti; - La verifica del serraggio delle connessioni elettriche; - Il controllo della temperatura ambiente.; - Il controllo dello stato delle resistenze di scarico. Messa a terra La messa a terra è raggiunta attraverso i punti di fissaggio del CLMD03. Attenzione: questo implica che un cavo extra tra il condensatore e la messa a terra dell’installazione è richiesto nel caso in cui il CLMD03 sia fissato su un materiale isolante. Armoniche L'installazione di condensatori in reti disturbate da armoniche richiede speciali precauzioni specialmente quando ci sono rischi di fenomeni di risonanza. MESSA IN SERVIZIO Mentre viene presa ogni precauzione per assicurare che le informazioni contenute in questa pubblicazione siano corrette, non può essere accettata alcuna responsabilità legale per alcuna inesattezza. Non ci assumiamo nessuna responsabilità per l'uso improprio del prodotto. La Società si riserva il diritto di alterare o modificare le informazioni qui contenute in qualunque momento alla luce di sviluppi tecnici o altro. Con l'equipaggiamento isolato dalla rete, verificare: - Che la cablatura sia corretta (la messa a terra potrebbe essere considerata); - Che la ventilazione ambientale sia adeguata; - Il corretto serraggio delle connessioni. 5 es Antes de proceder a la instalación lea atentamente este documento y manténgalo al alcance del personal responsable de la instalación, mantenimiento y utilización. ¡ATENCIÓN! La temperatura ambiente de un condensador instalado en un armario eléctrico es la temperatura alrededor del condensador no alrededor del armario. PRECAUCION: Como otras unidades de condensadores estándares, los dispositivos de descarga de los CLMD03 no son adecuados para su uso en conmutaciones rápidas como las baterías activadas por tiristores (tiempo mínimo de desconexión: 40 seg). Las resistencias externas adicionales no son una solución para tales casos, sólo condensadores especialmente diseñados para ello se deben utilizar en tales aplicaciones. LEA ESTO PRIMERO Seguridad ¡ATENCIÓN!: espere 5 minutos tras la desconexión antes de proceder a la manipulación. Después de esperar 5 min y como precaución adicional antes de empezar a trabajar, comprobar la tensión cc entre terminales y asegurarse que el condensador está descargado. Montaje horizontal y vertical El CLMD se debe fijar de tal forma que se asegure una ventilación natural desde la parte inferior a la superior. Algunas unidades CLMD03 pueden ser montadas lado a lado si están alineadas (Fig. #1). No está permitida la configuración en triángulo ni en cuadrado. El espacio libre mínimo entre grupos en línea adyacentes es de 25 mm (Fig. #2 & 3). En caso de montaje vertical utilice una placa base agujereada o barras de soporte de modo que se habilite la libre circulación de aire alrededor de las unidades de condensadores (Fig. #4 & 5). No montar boca abajo (Fig. #6). En caso de montaje horizontal, se debe instalar de forma que el flujo natural de aire circule a través de las unidades sin mayor constricción (Fig. #7). No montar de forma que el flujo natural de aire quede bloqueado (Fig. #8). Para una utilización segura de los condensadores CLMD03, por favor asegúrese que: 1. La instalación y el mantenimiento lo realicen únicamente personal cualificado y autorizado, de acuerdo con la normativa local vigente; 2. El equipo esté desconectado de la red antes de acceder al mismo. Inspección a la recepción Desembale el CLMD03 y compruebe que: - los datos en la placa corresponden con los indicados en su pedido y con la normativa local; - el CLMD03 no esté dañado. Cualquier pérdida o daño debe ser notificada de inmediato a la oficina de ABB más cercana. Almacenamiento Interior, en ambientes secos, libres de polvo y no corrosivos, protegido contra vibraciones y golpes. Temperatura de almacenamiento:Tª mín.: -40°C/-40°F Tª máx.: 75°C/167°F Instalación en un armario eléctrico ¡ATENCIÓN! Las directrices sólo se aplican si se respetan los límites siguientes: - Temperatura máxima del recinto: 40°C (1 hora). - Temperatura media máxima del recinto durante 24 horas: 35°C. - Temperatura máxima del recinto durante 1 año: 25°C. Cuando los condensadores se instalan en un armario los componentes se deben disponer de tal forma que se optimice la refrigeración. Los componentes que disipen gran cantidad de calor se deberán situar preferiblemente por encima de los condensadores de forma que estos no se sobrecalienten. Cuando se utilicen reactancias, éstas deben situarse de tal forma que no irradien calor directamente sobre los condensadores. Se recomienda una barrera térmica. Generalmente las reactancias disipan mucho más calor, por lo que su impacto térmico mediante convección también debe tenerse en cuenta. 1. Ventilación natural. La diferencia de altura entre la entrada y la salida de aire debe ser grande de modo que se mejore la circulación de aire. El flujo de aire debe ser canalizado de forma que refrigere los puntos más calientes en el armario. El aire debe fluir en el armario de abajo a arriba. La superficie de la salida de aire debe ser al menos 1,2 veces la de la entrada de aire. 2. Ventilación forzada. A veces se requiere una refrigeración forzada mediante ventilador (Fig. #8). Para ello tener en cuenta las siguientes recomendaciones: - Considere la máxima temperatura ambiente de la Transporte y manipulación En caso que se prevean unas condiciones de transporte duras, asegurarse que los puntos de fijación sean lo suficientemente fuertes de acuerdo al peso del CLMD03 y de las vibraciones que pudieran ocurrir. ¡ATENCIÓN! No seguir las normas de instalación puede desembocar en fallos prematuros, otros daños materiales a la instalación o daños personales. INSTALACIÓN Normas aplicables IEC 60831 Partes 1 y 2. Normativa local vigente. Protección P00 por defecto y IP20 con tapa superior opcional Instalación y utilización Instalación interior sobre una base sólida o fijado sobre un armazón/placa en espacios bien ventilados donde la temperatura media alrededor del condensador no exceda de 35°C/95°F a lo largo de un año ni de 45°C/113°F durante 24 horas ni de 55ºC/131ºF (de acuerdo con IEC 60831 Partes 1 y 2 para un producto de la categoría 25/D). Ver siempre la placa de características para las especificaciones exactas. 6 es - 3. 4. estancia incluyendo el efecto calefactor de la instalación de condensadores. Considere el calor disipado por todos los componentes y aparatos del armario: reactancias, condensadores, contactores, fusibles, etc. Considere las temperaturas máximas admisibles de todos los componentes y aparatos. Considere como dirigir la corriente de aire de acuerdo con la posición de los condensadoes (Fig. #9). Se recomienda el uso de una protección para la sobretemperatura que desconecte la batería en caso de fallo del ventilador o por sobretemperatura debida a otra causa. Es necesaria una limpieza y mantenimiento regular de los filtros que puedan haber. Sin una limpieza regular el sistema de refrigeración puede resultar ineficiente. - La ventilación ambiente es adecuada; - Las conexiones tienen el apriete correcto. - La tapa superior para IP20 esté correctamente fijada, en caso de existir (ver sección “Accesorios opcionales”) ACCESORIOS OPCIONALES Tapa superior La tapa superior del CLMD03 para conseguir la protección IP20 de acuerdo a IEC 60529 ya viene provista de los prensaestopas o pasacables que se vayan a emplear. La fijación es mediante 4 tornillos autorroscantes (incluidos en la tapa) (Fig. #14.1 y 14.2). Esta tapa de protección sirve para impedir el contacto accidental con alguna parte viva de la unidad CLMD03 especialmente cuando están ubicados en áreas abiertas. Recomendamos taladrar los agujeros con una broca de sierra en la tapa en el lado adecuado. La tapa está provista de tres pretalaros para colocar prensaestopas hasta el tamaño estándar PG29 (dos pequeños pretaladros para unidades duales) o PG36 (un pretaladro grande para una unidad de un solo condensador). También admiten los pasataladros. Fijación del CLMD03 (Fig. #10) Están provistos de cuatro taladros de fijación para tornillos de M6 (no incluidos). Como mínimo deben emplearse dos de los taladros en forma simétrica (Fig. #11). Asegurarse que la rigidez del soporte y de los tornillos es suficiente para soportar el peso de los condensadores CLMD03. Resistencias de descarga El condensador CLMD03 se suministra desde fábrica con el juego de resistencias de descarga ya instalado para cumplir con la IEC 60831que permite una descarga hasta la tensión residual por debajo de los 50V después de 1min una vez se desconecta de la red. Tener en cuenta retrasar en no menos de 40 seg la reconexión del CLMD03. No seguir esta recomendación podría causar daños y reducir la vida del condensador. Conexión eléctrica Alimentación El CLMD03 está disponible como una unidad que alberga tanto un solo condensador como dos condensadores individuales en la misma unidad. Para ello están provistos de uno (Fig. #12) o dos (Fig. #13) juegos de terminales para tres fases . Los cables deben dimensionarse para 1,5 veces la intensidad nominal del condensador. Deben utilizarse los conectores adecuados para su correcto empleo en instalaciones eléctricas. Para el ajuste de los tornillos, debe aplicarse un par de 6Nm para una correcta conexión eléctrica (según norma DIN 46-200). Asegurarse que todas las conexiones están apretadas. Si hay la tapa superior opcional, asegurarse que está debidamente fijada (ver abajo en la sección de “Accesorios opcionales). MANTENIMIENTO 1. Asegurarse que se han seguido los procedimientos de seguridad (ver Seguridad); 2. El mantenimiento anual debe incluir: - Eliminación de los depósitos de suciedad, limpieza de todas las partes; - Comprobación del apriete de todas las conexiones eléctricas; - Comprobación de la temperatura ambiente; - La verificación del estado de las resistencias de descarga. Tierra La tierra viene mediante los puntos de fijación de la envolvente del CLMD03. A tener en cuenta: ello implica que se necesita un cable extra entre la envolvente de CLMD03 y el contacto de tierra de la instalación en el caso de que la unidad CLMD03 esté fijada sobre un material aislante. Armónicos La instalación de condensadores en redes distorsionadas por armónicos puede requerir precauciones especiales, particularmente cuando existe riesgo de fenómenos resonantes. Si bien se han tomado todas las medidas para garantizar que la información contenida en esta publicación sea correcta, no nos hacemos responsables de posibles errores. No nos hacemos responsables de la mala utilización del producto ni de daños directos o indirectos. La compañía se reserva el derecho a modificar la información aquí contenida en función de mejoras técnicas o de cualquier otro tipo. PUESTA EN MARCHA Con el equipo desconectado de la red, comprobar que: - El cableado está conectado correctamente (debiendo ser considerada la tierra); 7 fr Avant l'installation, lisez attentivement cette notice et laissez-la à la disposition des gens en charge de l'installation, de l'utilisation et de l'entretien des condensateurs. ATTENTION! La température ambiante pour les condensateurs à l’intérieur d’une armoire est la température autour des condensateurs et non autour de l’armoire. A LIRE EN PREMIER ATTENTION! Comme pour les autres condensateurs standards, les dispositifs de décharge du CLMD03 n’acceptent pas des commutations trop fréquentes comme les batteries à commutation thyristor (temps d’arrêt minimum: 40 sec). Des résistances externes supplémentaires ne sont pas une solution pour ces cas. Seuls des condensateurs spécialement conçus pour ces applications peuvent être utilisés. Sécurité ATTENTION! Avant de manipuler les condensateurs, attendez 5 min après les avoir déconnectés du réseau. Comme précaution supplémentaire, passées ces 5 min, attendez avant de commencer le travail, procédez prudemment à la mesure de la tension DC sur les bornes et assurez-vous que le condensateur est déchargé. Pour une utilisation sans danger : 1. L'installation et l'entretien ne peuvent être effectués que par du personnel autorisé et qualifié, conformément aux réglementations locales en vigueur ; 2. Isolez le matériel de l’alimentation avant d'y accéder. Montage vertical et horizontal Les condensateurs CLMD03 doivent être fixés de telle sorte qu’une convection naturelle de l’air (de bas en haut) soit possible. Plusieurs CLMD03 peuvent être installés côte à côte pourvu qu’ils soient alignés (Fig. #1). Les configurations en triangle et en carré ne sont pas autorisées. L’espace libre minimal entre les groupes d’unités alignées adjacentes est de 25 mm (Fig. #2 & 3). En cas d’installation verticale, veuillez utiliser une plaque de montage perforée ou des barres de support pour permettre une ventilation libre autour des condensateurs (Fig. #4 & 5). N’installez pas les CLMD03 à l’envers (tête en bas). (Fig. #6) En cas d’installation horizontale, veuillez monter les CLMD03 de sorte que la ventilation naturelle passe autour des unités sans contraintes importantes (Fig. #7). N’installez pas les CLMD03 de manière à ce que la ventilation naturelle soit bloquée (Fig. #8). Inspection à la réception du matériel Déballez le CLMD03 et vérifiez que: - les informations reprises sur les étiquettes signalétiques correspondent à celles commandées et respectent la réglementation en vigueur ; - le CLMD03 n'est pas endommagé. Tout dégât ou perte doit être signalé immédiatement à votre plus proche revendeur ABB. Entreposage A l'intérieur, dans un milieu sec, non poussiéreux et non corrosif, exempt de vibration et protégé des chocs. Température d'entreposage : de -40°C/-40°F à 75°C/167°F Installation dans une armoire ATTENTION! Ces règles s’appliquent uniquement si les limites suivantes sont respectées: - Température maximale du local: 40°C (1 heure). - Température moyenne maximale du local sur 24 heures : 35°C. - Température moyenne maximale du local sur 1 an: 25°C. Manipulation et transport Pour des conditions de transport difficiles, assurez-vous que les points de fixation sont suffisamment solides pour supporter le poids du CLMD03 ainsi que les vibrations qui pourraient survenir. ATTENTION! Le non-respect des instructions d’installation peut engendrer une défaillance prématurée, d’autres dégâts matériels de l’installation ou des dommages corporels. Quand les condensateurs sont installés dans une armoire, les composants devraient être placés de façon à optimiser le refroidissement. Placez de préférence les appareils à dissipation thermique élevée au-dessus des condensateurs pour éviter de les surchauffer. Quand il y a des selfs, elles devraient être placées de façon à ce qu’elles ne rayonnent pas de chaleur directement sur les condensateurs. Une séparation thermique est recommandée. Les selfs génèrent en général beaucoup plus de chaleur, leur impact thermique sur la convection doit également être pris en considération. 1. Ventilation par convection naturelle La différence en hauteur entre l’entrée et la sortie d’air devrait être grande afin d’améliorer la circulation de l’air. Le flux d’air devrait être canalisé pour refroidir au mieux les points les plus chauds dans l’armoire. L’air devrait circuler du bas vers le haut de l’armoire. La dimension de l’évent supérieur doit au moins être égale à 1,2 fois celle de l’évent inférieur. INSTALLATION Normes applicables IEC 60831 §1 & §2 et normes locales en vigueur. Protection IP00 par défaut et IP20 avec le capot en option. Installation et utilisation Installation à l’intérieur sur une surface solide ou sur un support rigide dans un endroit bien ventilé où la température de l’air autour du condensateur n'excède pas 35°C/95°F sur un an, 45°C/113°F sur 24h et 55°C/131°F (selon la norme IEC 60831 §1 & §2 pour une catégorie 25°C/D). Référez-vous toujours à l’étiquette pour les spécifications exactes. 8 fr 2. Ventilation forcée Le refroidissement forcé utilisant un ventilateur est parfois nécessaire (Fig. #8). Veuillez vous référer aux recommandations suivantes : - Prenez en considération la température maximum ambiante de l’emplacement de l’installation ainsi que l’effet thermique de l’installation de condensateurs ellemême. - Prenez en considération la chaleur émise par les composants et appareils dans l’armoire : bornes, condensateurs, contacteurs, fusibles, etc. - Prenez en considération les températures maximum admissibles pour tous les composants et appareils. - Prenez en considération la circulation de l’air tout en respectant la position des condensateurs (Fig. #9). 3. L’utilisation d’une protection de surchauffe est recommandée afin d’éteindre la batterie en cas de défaillance du ventilateur ou de température excessive due à une autre cause. 4. L’entretien et le nettoyage réguliers de tous les filtres sont nécessaires. Sans nettoyage régulier, le système de refroidissement peut devenir inefficace. MISE EN SERVICE L'équipement étant isolé du réseau, vérifiez que : - le câblage est correct (la mise à la terre doit être considérée); - la ventilation est adéquate ; - les câbles sont solidement connectés. ACCESSOIRES EN OPTION Capot Le capot en option permet au CLMD03 d’avoir une protection IP20 selon la norme IEC 60529 pourvu que les presse-étoupes et passe-fils appropriés soient utilisés. Fixez le capot correctement avec les quatre clous à visser (fournis avec le capot) (Fig. #14.1 & 14.2). Ce capot de protection empêche quiconque de toucher les parties actives du CLMD03 particulièrement quand le condensateur est facilement accessible. Nous recommandons de forer le(s) trou(s) dans le capot avec une scie-cloche sur la face appropriée. Trois bossages sont formés dans le capot pour le placement des presse-étoupes jusque la taille normalisée PG29 (2 bossages pour les boîtiers à double condensateurs) ou PG36 (un bossage pour un condensateur simple). Les passe-fils sont également autorisés. Fixation du CLMD03 (Fig. #10) Quatre trous de fixations sont fournis pour des vis M6 (non fournies). Deux de ces trous de fixations doivent au moins être utilisés de façon symétrique (Fig. #11). Assurez-vous que le support et les vis sont appropriés pour supporter le poids des CLMD03. Résistance de décharge Le condensateur CLMD03 est livré avec des résistances de décharge pré-installées pour être conforme à la norme IEC 60831 et permettre une diminution de la tension résiduelle jusqu’à moins de 50V une minute après la déconnexion de l’alimentation. Assurez-vous que le délai avant que le CLMD03 ne soit réalimenté n’est pas plus court que 40 sec. Le non-respect de cette règle pourrait endommager le condensateur et réduire sa durée de vie. Connexions électriques Alimentation électrique Le CLMD03 est disponible en tant qu’une unité constituée soit d’un seul condensateur soit de deux condensateurs individuels dans le même boîtier. Par conséquence, un (Fig. #12) ou deux (Fig. #13) jeux de bornes triphasées sont fournis. Les câbles doivent être dimensionnés pour supporter au minimum 1,5 fois le courant nominal des condensateurs. Les souliers de câble appropriés doivent être utilisés selon les bonnes pratiques habituelles d’une installation électrique. En serrant l’écrou, un couple de serrage de 6Nm doit être appliqué pour assurer une connexion électrique correcte (selon la DIN 46-200). Assurez-vous que toutes les connexions sont serrées. S’il y a un capot optionnel, assurez-vous qu’il est correctement fixé (voir la section “accessoires en option” ci-dessous). ENTRETIEN 1. Assurez-vous que les procédures de sécurité sont respectées (voir le paragraphe " Sécurité ") ; 2. L'entretien annuel doit inclure : - le dépoussiérage et le nettoyage de toutes les parties ; - la vérification de la fermeté des connexions électriques - la vérification de la température ambiante; - la vérification de l’état des résistances de décharge. Mise à la terre La mise à la terre se fait au moyen des points de fixations du boîtier du CLMD03. Remarque : cela implique qu’un câble supplémentaire entre le boîtier du CLMD03 et la mise à la terre de l’installation est nécessaire si le CLMD03 est fixé sur un matériau isolant. Bien que tout soit mis en oeuvre pour garantir l'exactitude des informations contenues dans cette publication, nous n'acceptons aucune responsabilité légale pour toute information incorrecte. Nous déclinons toute responsabilité en cas de mauvaise utilisation du produit ainsi que pour les éventuels dommages en résultant, qu'ils soient directs ou indirects. Nous nous réservons le droit de changer ou de modifier à tout moment les informations contenues dans cette publication à la lumière des développements techniques ou autres. Les spécifications techniques sont valables uniquement sous conditions de fonctionnement normales. Harmoniques L'installation de condensateurs sur des réseaux pollués par des harmoniques demande une attention toute particulière lorsqu'il y a un risque de phénomène de résonance. 9 pt Antes da instalação, leia cuidadosamente este manual e o mantenha sempre disponível para os responsáveis da instalação, manutenção e operação. CUIDADO! A temperatura ambiente para capacitores dentro de cubículos, é a temperatura ao redor do capacitor, e não ao redor do cubículo. CUIDADO! Assim como outros capacitores padrões, os dispositivos de descarregamento do CLMD03, não são convenientes para uso com faixas rápidas de chaveamento como bancos chaveados à tiristores (tempo mínimo para o desligamento 40 seg). Resitores adicionais externos, não são uma solução para estes casos, somente capacitores com projeto especial devem ser usados para esta aplicação. LEIA ISTO PRIMEIRO Segurança CUIDADO! aguarde 5 minutos após a desenergização antes de tocar nos terminais do capacitor. Depois de esperar 5 min. e, como medida de precaução adicional, antes de começar o trabalho, medir cuidadosamente a tensão DC nos terminais e certifique-se que o capacitor está descarregado. Para o seguro uso das unidades do CLMD03, por favor certifique-se de que: 1. A instalação e manutenção dos capacitores seja de inteira e exclusiva responsabilidade de pessoas autorizadas e qualificadas, e de acordo com as normas e regulamentações locais; 2. O equipamento esteja isolado de sua fonte de alimentação antes de se obter acesso aos terminais. Montagem Vertical e horizontal O CLMD03 deve ser afixado de forma a permitir o fluxo natural de ventilação CLMD03 de baixa para cima. Várias unidades do CLMD03 podem ser instaladas lado a lado, considerando-se que elas sejam alinhadas (Figura #1). Configurações triângulo e quadrado não são permitidas. O espaço livre mínimo entre grupos de unidades adjacentes é de 25mm (Figura #2 & 3). No caso de montagem em plano horizontal, use suportes de chapa perfurada, ou que permitam livre fluxo de ar ao redor das unidades dos capacitores(Figura #4 & 5). Não monte o capacitor em posição invertida (Topo para baixo) (Figura #6). No caso de montagem em plano vertical, instale de forma tal que haja ventilação natural através das unidades sem grandes obstruções (Figura #7). Não monte de forma que a ventilação natural fique bloqueada (Figura #8). Inspeção e Recepção Desembale o CLMD03 e verifique se: - os dados correspondentes na etiqueta correspondem aos mesmos descritos na ordem de compra e regulamentaçõe locais. - o CLMD03 não está danificado. Qualquer problema deverá ser notificado imediatamente ao seu agente ABB mais próximo. Instalação em cubículo Armazenagem Abrigada, local seco, livre de poeira, em ambientes não corrosivos, protegido de vibrações ou impactos. Temperatura de armazenagem: T° mín.: -40°C/-40°F T° máx.: 75°C/167°F CUIDADO! As regras a seguir somente se aplicam se os seguintes limites forem respeitados: - Temperatura máxima ambiente: 40°C (1 hora). - Temperatura média ambiente máxima durante 24 horas: 35°C. - Temperatura média ambiente máxima durante 1 ano: 25°C. Quando capacitores são instalados em cubículos, os componentes devem ser montados de forma a otimizar o resfriamento. Instale dispositivos com elevada dissipação térmica acima dos capacitors, evitando sobreaquecê-los. Quando reatores estiverem sendo utilizados eles devem ser alocados, de forma a não irradiar aquecimento diretamente nos capacitores. É recomendada a utilização de uma barreira térmica. Reatores em geral dissipam muito mais calor, portanto o impacto térmico através da convecção também deve ser considerado. 1. Circulação natural de ar A diferença em peso entre o ar que entra e o ar que sai deveria ser grande de forma a aumentar a circulação de ar. O fluxo de ar deve ser canalizado de tal forma a refrigerar melhor os pontos mais quentes do cubículo. O ar deve fluir de baixo para cima no cubículo. A área de abertura da saída de ar superior, deve ser igual a 1.2 vezes a área de abertura para entrada de ar inferior. Transporte e Manuseio No caso de severas condições de transporte, certifiquese que os pontos de fixação são fortes o suficiente para suportar o peso do CLMD03 e as vibrações que podem ocorrer. CUIDADO! O desrespeito às normas de instalação, podem levar a falhas prematuras, danos em outros materiais da instalação ou acidentes pessoais. INSTALAÇÃO Aplicações Básicas IEC 60831 Parte 1 & 2. Atual regulamentação local. Proteção IP00 como padrão e IP20 com tampa superior opcional. Instalação e Utilização Instalação abrigada sobre uma plataforma firme ou fixado sobre uma rígida placa/caixa com boa ventilação onde a temperatura do ar em torno do condensador não exceda 35ºC/95ºF por mais de um ano e 45ºC/113ºF por mais de 24 horas e 55ºC/131ºF (de acordo com a IEC 60831 Parte 1 & 2 para produtos com categoria -25/D.) Consulte sempre a etiqueta de identificação para obtenir as especificações exatas do produto. 10 pt 2. Ventilação forçada Refrigeração forçada utilizando-se de ventiladores são algumas vezes requeridas (Figura #8). Por favor considere as seguintes recomendações: - Considere a máxima temperature ambiente da instalação, incluindo o efeito do aquecimento da própria instalação do capacitor. - Considere a dissipação térmica de todos os componentes e aparelhos no cubículo: Reatores, Capacitores, Contatores, fusíveis, etc. - Considere a temperatura máxima permissível para todos os componentes e aparelhos. - Considere como direcionar o fluxo de ar com respeito as posições dos capacitores (Figura #9). 3. O uso de proteção por sobretemperatura é recomendado de forma a desligar o banco em caso de falha, ou sobretemperatura devido a outras causas. 4. Manutenção regular e limpeza de filtro são necessárias. Sem uma limpeza regular o sistema de refrigeração pode se tornar ineficiente. - Os condutores estão apropriadamente conectados (a ligação à terra deve ser considerada); - A ventilação ambiente é adequada; - O devido aperto das conexões. - A tampa IP20 é bem fixada, si existente (veja seção “Acessórios opcionais”) ACESSÓRIOS OPCIONAIS Tampa A tampa opcional permite ao CLMD03 a obtenção do grau de proteção IP20 de acordo com a IEC 60529, considerando-se que bucins adequados sejam utilizados. Fixá-la apropriadamente com quatro parafusos (fornecidos com a tampa) (Figura #14.1 & 14.2). Esta tampa de protecção impede as pessoas de tocar as partes energizadas da unidade CLMD03 especialmente quando expostos em áreas abertas. Recomenda-se a perfuração de buraco(s) na tampa com uma serra-copo do lado apropriado. Existem três bossas na tampa para a utilização de bucins até o tamanho padrão PG36 (duas pequenas bossas para unidades de capacitor duplo) ou PG36 (uma grande bossa para unidades de capacitor único). Passa-cabos também são permitidos. Fixação do CLMD (Figura #10) Existem quatro furos de fixação para parafusos do tipo M6 (não incluídos). Ao menos dois dos furos de fixação devem ser utilizados de forma simétrica (Figura #11). Certifique-se de que a rigidez do suporte e dos parafusos são suficientes para resistir ao peso das unidades dos condensadores CLMD03. Resistor de descarga A unidade do capacitor CLMD03 é fornecidada com resistores de descarga, instalados de fábrica, em acordo com IEC 60831, permitindo a diminuação da tensão residual à valor inferior à 50V após 1min. da desconexão da alimentação. Certifique-se que o intervalo antes que o CLMD03 seja re-energizado não é inferior à 40 seg. Não seguir esta regra pode causar danos e reduzir a vida útil do capacitor. Conexão Elétrica Alimentação O CLMD03 é disponível como uma unidade que contém um capacitor único ou dois capacitors individuais na mesma caixa. Consequentemente um (Figura #12) ou dois (Figura #13) conjuntos de terminais trifásicos são fornecidos. Os condutores devem ser dimensionados no mínimo para 1,5 vezes a corrente nominal do condensador. Devem ser utilizados terminais de cabos apropriados de acordo com a boa prática de instalações eléctricas. Enquanto aperta o parafuso, um torque de 6Nm deve ser aplicado para obtenir uma conexão elétrica correta. (de acorde com DIN46-200). Certifique-se de que todas as ligações estão apertadas. No caso da existência da tampa opcional, certifique-se que ela é devidamente fixada (veja seção ‘Acessórios opcionais’). MANUTENÇÃO 1. Assegure-se de que os procedimentos foram corretamente seguidos (veja o parágrafo Segurança); 2. Uma manutenção anual deverá incluir: - Remova o depósito de poeira, limpe todas as partes; - Verifique o aperto de todas as conexões elétricas; - Verifique a temperatura ambiente; - A verificação do estado das resistências de descarga. Ligação de terra A ligação a terra é executada através dos pontos de fixação do invólucro do CLMD03. Observação: isto emplica que um cabo extra, entre o invólucro do CLMD03 e o contato do terra da instalação, é necessário no caso em que o CLMD03 é fixado sobre um material isolante. Harmônicas A instalação de capacitores em sistemas com distorções harmônicas pode requerer precauções especiais, especialmente em locais que possuem riscos com fenômenos de ressonância. Enquanto cada cuidado seja necessário para garantir que a informação contida na publicação seja correta, nenhuma responsabilidade legal pode ser aceita por qualquer imprecisão. Não aceitamos responsabilidade por qualquer desuso do produto. A companhia reserva o direito de alterar ou modificar as informações aqui contidas em qualquer momento, tanto no quesito técnico quanto em outros desenvolvimentos. COMISSIONAMENTO Com o equipamento isolado da fonte de alimentação, verificar: 11 tr Yatay ve dikey montaj CLMD03 kondansatörlerinde havalandırma alttan üste gelecek şekilde yapılmalıdır. Birden fazla CLMD03 yan yana (Şek. #1) sıralı olarak monte edilebilir. Her bir grubun arasındaki mesafe en az 25mm olmalıdır (Şek. #2 & 3). Düşey montajlar için taşıyıcı sabitlemeleri ve destek plakaları kullanılarak hava akışı sağlanmalıdır (Şekil #4 & 5). Ters montaj yapılmamalıdır (Şek. #6) Yatay montaj doğal hava akışı engellenmeyecek şekilde yapılmalıdır (Şek. #7). Hava akışını engelleyecek montajlar yapılmamalıdır (Şek. #8). Montaj yapılmadan önce ilgili personelin açıklamaları dikkatlice okuması ve uygulanması gereklidir. ÖNCE OKUYUNUZ Güvenlik UYARI! Enerji kesildikten sonra 5 dk beklemeden müdahale yapılamamalıdır. 5 dk beklendikten sonra ek önlem olarak ölçü aletiyle DC gerilim ölçümleri yapılıp kondansatörün deşarj olduğundan emin olunmalıdır. CLMD03 kondansatörü güvenli şekilde kullanmak için aşağıdakiler yerine getirilmelidir: 1. Montaj ve bakım işlemleri, işletmelerde sadece yetkili kişiler tarafından yapılmalıdır. 2. Kondansatöre müdahale etmeden önce bağlantıları sökülmelidir. Pano içi montajı UYARI! Uyarılar sadece aşağıdaki sınırlar içerisinde geçerlidir: - En yüksek oda sıcaklığı: 40°C (1 saat). - 24 saatin üzerinde ortalama oda sıcaklığı: 35°C. - 1 yılın üzerinde ortalama oda sıcaklığı: 25°C. Kontrol ve Onay - Etiketinde yazan bilgiler ile siparişinizin aynı olduğu - CLMD03’ün hasar görmediği. Herhangi bir yanlýþlýk veya hasar durumunda derhal en yakýn ABB ofisi veya yetkili satýcýsý ile irtibata geçiniz. Kondansatörler pano içerisine yerleştirildiğinde, hava akımının uygun bir şekilde oluşmasına izin verilecek şekilde pano tasarımı yapılmalıdır. Kondansatörlerin ısınmasının önlenmesi için üzerlerinde hava değişimini sağlayan havalandırma sistemleri yerleştirilmelidir. Reaktörler ile birlikte kullanıldığında, ısılarının doğrudan kondansatörlere gelmeyecek şekilde konulmalıdır. Isıl engellerin kullanılması önerilir. Reaktörlerde genellikle ısı dağılımı çok yüksek olduğu için, pano tasarımda dikkate alınmalıdır. Depolama Dahili, kuru, temiz, korozif olmayan ortamda titreşim ve darbelere karşı korunmalıdır. Depolama sıcaklığı: en az -40°C/-40°F, en yüksek 75°C/167°F. Nakliye Tüm nakliye ve taşıma durumlarında, CLMD03’ün sabitleme noktalarından ağırlığının taşınabilecek güçte olması gereklidir. 1. Doğal hava dolaşımı Hava girişi ile çıkışı arasındaki fark, hava dolaşımının yeterli olması için yeteri kadar büyük olmalıdır. Pano içerisinde hava kanalları oluşturularak sıcak bölümlerin soğutulması sağlanabilir. Üst havalandırmanın kesiti, alt kesitin en az 1,2 katı olmalıdır. 2. Zorlanmış hava dolaşımı Havalandırma fanı kullanılarak zorlanmış hava dolaşımı yapılaması bazen gerekli olabilir (Şek. #8). Aşağıdaki hususlar dikkate alınmalıdır: - En yüksek ortam için sıcaklığı kondansatörün kendi sıcaklık etkisi de göz önüne alınmalıdır. - Panel içerisinde kullanılan reaktör, kondansatör, kontaktör ve sigortaların sıcaklıkları göz önüne alınmalıdır. - Her bir malzemenin izin verilen çalışma sıcaklıkları göz önüne alınmalıdır. - Kondansatörlerin konumlarına göre hava dolaşımının nasıl olacağı göz önüne alınmalıdır. - Kondansatörlerin yerleşimine göre hava dolaşımı göz önüne alınmalıdır (Şek. #9). 3. Fan arızası yada başka sebeplerden oluşabilecek aşırı sıcaklık artışları durumlarında kademelerin devreye girmesini önlemek için aşırı sıcaklık algılayıcıları kullanılmalıdır. 4. Filtrelerin ve fanların düzenli temizlenmesi gereklidir. UYARI! Kurulumuyla ilgili belirtilen kurallara uyulmaması kullanım süresinin azalması, diğer ekipmanlarda hasar veya can tehlikesine neden olabilir. KURULUM Uygulama standartları IEC 60831’in 1. ve 2. Bölümleri ile yürürlükteki düzenlemeler. Koruma Standart IP00 ve opsiyonel olarak IP20 üst kapama Kurulum ve kullanım Dahili olarak katı yada sertleştirilmiş plakaya, sıcaklığın bir yıl içerisinde (IEC 60831’de 1. Ve 2. Bölümdeki 25/D ürün sıcaklığı ile ilgili belirtilen) 45°C/113°F, 24 saatte 55°C/131°F’i aşmayacak şekilde sabitlenmesi yapılabilir. Tüm özellikler için etiketinden yararlanılmalıdır. UYARI! Pano içerisindeki kondansatör için ortam sıcaklığı pano iç sıcaklığıdır, oda sıcaklığı değildir. UYARI! Diğer standart kondansatörlerde olduğu gibi, CLMD03’lerin deşarj dirençleri, tristör anahtarlamalı sistemlerdeki hızlı anahtarlamalar (en düşük 40sn) için uygun değildir. Harici dirençler bunun yanında kullanılmalıdır. Bu tür uygulamalarda sadece özel tasarımlı kondansatörler kullanılmalıdır. 12 tr CLMD03 sabitleme (Şek. #10) M6 ölçüsünde dört sabitleme deliği bulunmaktadır. Simetrik olarak en az iki vida ile tutturulması gereklidir (Şek. #11). CLMD03 kondansatörlerinin güçlü bir şekilde durması için tamamen sıkılı olduğuna emin olunmalıdır. kalan gerilimi 50V’un altına düşürülmesi için deşarj dirençleri ile birlikte üretilmektedir. Tekrar enerji verilmeden önce geçen sürenin 40 sn. den uzun olduğundan emin olunmalıdır. Bunun dışındaki bir çalışma, hasara neden olacak ve kondansatör ömrünü kısaltacaktır. Elektriksel Bağlantı Güç bağlantıları CLMD03 aynı kasada tek bir kondansatör yada iki ayrı kondansatör olarak yerleştirilebilir. Buna göre, tek set (Şek. #12) ve iki set (Şek. #13) olarak 3-fazlı kondansatör mümkündür. Kablolar nominal akımın en az 1,5 katı taşıma kapasiteli olarak seçilmelidir. Kablolar bağlantı kolaylığı sağlayacak şekilde olmalıdır. Bağlantı vidalarını sıkarken iyi bir elektriksel geçirgenlik için 6NM tork uygulanmalıdır (DIN46-200’e göre). BAKIM 1. Güvenlik uyarılarının sağlanmalıdır (Bkn. “Güvenlik” bölümü); 2. Yıllık bakım için: - Tüm tozlu bölümler temizlenmelidir; - Elektriksel bağlantılar kontrol edilmelidir; - Ortam sıcaklığı kontrol edilmelidir; - Deşarj dirençlerinin durumu kontrol edilmelidir. Tüm bağlantıların sıkı bir şekilde yapıldığından emin olunmalıdır. Üst kapatma kullanılıyorsa, tamamen kapattığından emin olunmalıdır (Bkn. Opsiyonel aksesuarlar) Topraklama CLMD03 tutturma noktaları, topraklama bağlantısı için kullanılabilir. Dikkat: bu tasarmda CLMD03 kasası yalıtkan bir yüzeye monte edilmişse, topraklama noktası arasında ek bir kablo gereklidir. Harmonikler Harmonik bozulması olan sistemlerde kondansatörlerin kullanımı şebekede rezonans riski oluşturur ve önlem alınması gerekebilir. DEVREYE ALMA Şebeke gerilimi uygulanmadan önce şu hususlar kontrol edilmelidir: - Kablolamanın doğru yapılıp yapılmadığı (topraklama kablosu ile birlikte) - Ortam havalandırmasının yeterli olup olmadığı, - Bağlantıların sıkı bir şekilde yapılıp yapılmadığı, - Eğer varsa, IP20 için üst kapağının takılıp takılmadığı (Bkn. Opsiyonel aksesuarlar) EK AKSESUARLAR Üst kapak IEC 60529’a uygun olarak IP20 korumasının sağlanması için üst kapak kullanılabilir. Üst kapak ile birlikte gönderilen 4 vida ile üste sabitlenebilir (Şek. #14.1 & 14.2). Bu koruma ile CLMD03’ün enerjili bölümlerine doğrudan temas engellenmiş olur. Üst kapakta bir matkapla kablo girişleri için delik açılması önerilir. Üst kapaktan kablo girişi için çiftli kapasitör üniteleri için PG29 boyutunda iki adet, tek kapasitör ünitesi için PG36 boyutunda bir adet delik açılıp kroşe ile kablo girişi yapılabilir. Bu belgede yazılı tüm bilgilerin doğrudur ve güvenli bir çalışma için uyulması gereklidir. Ürünün yanlış kullanımı sonucu oluşan sorumluluk kabul edilmemektedir. Üretici, teknik veya diğer gelişmelerden dolayı bilgilerin güncellenmesi hakkını saklı tutar. Deşarj dirençleri CLMD03 kondansatörler, IEC 60831’e göre enerjisi kesildikten sonra 1dk. içerisinde kondansatör üzerinde 13 de Dieses Dokument vor der Installation sorgfältig lesen und für Personen, die mit der Installation, Wartung oder mit dem Betrieb beauftragt sind, stets zur Verfügung halten. immer auch das Typenschild Spezifikationen zu prüfen. um die genauen Die Umgebungstemperatur für ACHTUNG! Kondensatoren in einem Schaltschrank ist die Temperatur an den Kondensatoren und nicht die Raumtemperatur außerhalb des Schrankes. LESEN SIE DIES ZUERST Gesundheit & Sicherheit ACHTUNG! Vor Arbeiten an CLMD03 Kondensatoren nach dem Freischalten erst 5 Minuten Entladezeit abwarten, danach seine Spannungsfreiheit (Gleichspannung!) prüfen. Wie bei anderen marktüblichen ACHTUNG! Kondensatoren sind die Entladevorrichtungen bei CLMDO03-Kondensatoren nicht für den Einsatz mit kurzen Schaltzeiten geeignet, wie sie bei Verwendung von Thyristoren auftreten (kleinste zulässige Wiederzuschaltzeit: 40 sec.). Zusätzliche externe Entladevorrichtungen sind keine Lösung des Problems, in solchen Fällen müssen speziell ausgelegte Kondensatoren eingesetzt werden. Für den sicheren Gebrauch der Kondensatoreinheiten folgendes sicherstellen: 1. Installationen und Wartung sind nur von autorisiertem, qualifiziertem Personal in Übereinstimmung mit den örtlichen Vorschriften vorzunehmen; 2. Das Gerät ist von der Spannungsversorgung freizuschalten, bevor sich Zugang verschafft wird. Senkrechte und waagerechte Montage Die CLMD03 Einheiten sind so zu montieren, dass eine natürliche Luftbewegung zwischen den Einheiten von unten nach oben statt finden kann. Mehrere CLMD03 Kondensatoren können direkt nebeneinander montiert werden, wenn sie sich in einer Reihe befinden (Fig. #1). Dreieckige und quadratische Anordnungen sind nicht zulässig. Der minimale Gehäuseabstand zwischen Kondensatorgruppen beträgt 25mm (Fig. #2 & 3). Bei senkrechter Montage sind gelochte Montageplatten oder Traversen zu benutzen, um den Kühlluftdurchgang zwischen den Kondensatoren zu gewährleisten (Fig. #4 & 5). Der Überkopf-Einbau ist nicht zulässig (Fig. #6). Bei waagerechter Montage muss der Kühlluftweg ohne größere Behinderungen zwischen den Kondensatoren hindurch führen (Fig. #7). Blockieren der Kühlluftführung ist nicht zulässig (Fig. #8). Wareneingangskontrolle Die CLMD03 Kondensatoreinheiten auspacken und überprüfen, dass - die Daten auf dem Typenschild mit der Bestellung und den örtlichen Vorschriften übereinstimmen, - die CLMD03 Kondensatoreinheiten nicht beschädigt sind. Jeglicher Verlust oder Beschädigung sollte unverzüglich der nächsten ABB Vertretung gemeldet werden. Lagerung Innenraum, in trockener, staubfreier und nicht korrodierender Umgebung, geschützt vor Vibration und Stößen. Lagertemperatur: T° min.: -40°C/-40°F, T° max.: 75°C/167°F Einbau in Schaltschränke Transport und Handhabung) Bei schwierigen Transportbedingungen (der Anlage) ist sicherzustellen, dass die Montagepunkte an denen der CLMD03 befestigt ist stark genug sind um evtl, Erschütterungen oder Vibrationen auszuhalten. WARNUNG! Die Richtlinien gelten nur, wenn folgende Grenzen sichergestellt sind: - Kurzzeitige Raumtemperatur maximal : 40°C (1 Stunde). - 24-Stunden-Mittelwert der Raumtemperatur maximal: 35°C. - Jahresmittelwert der Raumtemperatur maximal: 25°C. Beim Einbau in Schaltschränke sollten die Kondensatoren so angeordnet werden, dass eine optimale Kühlung gewährleistet ist. Komponenten mit großer Verlustleistung sollten oberhalb der Kondensatoren angeordnet werden. Filterdrosseln sollten so angeordnet werden, dass die Kondensatoren keiner direkten Strahlungswärme ausgesetzt sind. Eine thermische Barriere ist notwendig. Filterdrosseln erzeugen üblicherweise soviel Verlustleistung, dass der thermische Einfluss durch Konvektion ebenfalls berücksichtigt werden muss. ACHTUNG! Nichtbeachtung dieser Anleitung kann zu vorzeitiger Alterung der Kondensatoren, Schäden an den Anlagen und Verletzungen von Personen führen. INSTALLATION Anzuwendende Normen IEC 60831 Teil 1 und 2 bzw. EN 60831 Teil1 und 2. Gültige lokale Vorschriften. Schutz Standardmäßig IP 00. IP 20 bei der Verwendung des optionalen Deckels. 1. Natürliche Belüftung (Eigenkonvektion) Der Höhenabstand zwischen Luftein- und –austritt sollte möglichst groß sein. Die Luft sollte so geführt werden, dass die heißesten Bereiche im Schrank besonders gut gekühlt werden. Die Luft sollte den Schrank von unten nach oben durchströmen. Einbau- und Umgebungsbedingungen Innenraum-Installation auf festem Untergrund oder montiert auf fester Platte oder Rahmen in gut belüfteter Umgebung, wo die Umgebungstemperatur 35°C/95°F im Jahresmittel, 45°C/113°F im 24 Stunden-Mittel und 55°C/131°F nicht überschritten wird (entsprechend IEC 60831 Teil 1 und 2 für die Kategorie -25/D). Beachten Sie 14 de 2. - - - 3. 4. Der Querschnitt der Luftaustrittsöffnung soll mindestens dass 1,2fache der Lufteintrittsöffnung betragen. Zwangsbelüftung In einigen Fällen ist eine Zwangsbelüftung erforderlich (Fig. #8). Bitte berücksichtigen Sie die Empfehlungen: Beachten Sie maximale Umgebungstemperatur am Aufstellungsort unter Berücksichtigung der Verlustleistung der Kondensatoranlage Beachten Sie Verlustleistung aller Komponenten und Geräte im Schrank: Drosseln, Kondensatoren, Schütze, Sicherungen etc. Beachten Sie die maximal zulässigen Temperaturen für alle Komponenten und Geräte Beachten Sie die Führung der Kühlluft insbesondere in Hinblick auf die Anordnung der Kondensatoren (Fig. #9). Der Einsatz einer Übertemperaturüberwachung wird empfohlen, um die Kondensatorbank bei Ausfall des Ventilators oder Übertemperatur aus anderen Gründen abzuschalten. Eine regelmäßige Wartung und Reinigung der Lufteintritts- und Luftaustrittsgitter (bzw. –filter) ist erforderlich, anderenfalls kann die Kühlung schnell unwirksam werden. INBETRIEBNAHME Vor dem Anschluss an die Versorgungsspannung ist zu prüfen, dass - die CLMD03 Einheiten korrekt montiert und sicher befestigt sind, - korrekte Leitungen richtig und fest angeschlossen und sicher befestigt sind (gegebenenfalls ist die Erdung zu prüfen), - die Belüftung der Umgebung ausreichend ist, - der optionale Deckel fest montiert ist (siehe Abschnitt: Optionales Zubehör unten). OPTIONALES ZUBEHÖR Deckel Der optionale Deckel macht den CLMD03 zu einem IP 20 geschützten Bauelement entsprechend der IEC 60529, wenn die geeigneten Verschraubungen, Würgenippel oder Kabeltüllen benutzt werden. Montieren Sie den Deckel mit den mitgelieferten Druckschrauben (Fig. #14.1 & 14.2). Dieser Schutzdeckel verhindert die Berührung unter Spannung stehender Teile des CLMD03. Falls Löcher benötigt werden, empfehlen wir, diese mit einer geeigneten Lochsäge am passenden Ort anzubringen. Drei vorgeprägte Löcher sind vorgesehen für die Verwendung von Kabelverschraubungen bis zur Standardgröße PG29 (2 kleine vorgeprägte Löcher für Doppelkondensator-Einheiten) oder PG36 (1 großes vorgeprägtes Loch für Einzelkondensator-Einheiten). Kabeltüllen sind auch erlaubt. CLMD03 Befestigung (Fig.#10) Jeder CLMD03 Kondensator ist mit Löchern für die Fixierung mit M6-Schrauben ausgestattet (M6-Schrauben nicht im Lieferumfang). Für eine ordentliche Befestigung müssen mindestens 2 diagonal angeordnete Montagelöcher verwendet werden (Fig. #11). Es ist sicherzustellen, dass die Belastbarkeit der Montageplatte und deren Befestigung ausreichend sind, um das Gewicht der CLMD03 Einheiten zu tragen. Entladewiderstand Der CLMD03 Kondensator wird mit einem angebauten Entladewiderstand ausgeliefert entsprechend IEC 60831 und entlädt sich innerhalb einer Minute auf eine Restspannung von unter 50 V nach Unterbrechung der Versorgungsspannung. Stellen Sie sicher, dass der Kondensator nicht schneller wiedereingeschaltet wird, als nach mindestens 40 Sekunden. Eine Missachtung dieser Anweisung kann zu Ausfällen führen und reduziert die Lebenserwartung des Kondensators. Elektrischer Anschluss Leistungsanschlus Der CLMD03 ist entweder mit einem oder zwei internen Kondensatoren in einem Gehäuse bestückt. Demzufolge sind ein (Fig. #12) oder zwei (Fig. #13) 3-phasige Anschlüsse vorhanden. Anschlussleitungen sollen mindestens für den 1,5-fachen Kondensatornennstrom bemessen sein. Die Anschlussleitungen müssen mit Kabelschuhen ordnungsgemäß versehen werden. Für eine gute elektrische Verbindung ist ein Anzugsmoment von 6 Nm zu verwenden (DIN 46200). Abschließend kontrollieren, dass alle Verbindungen festgezogen sind. Sollte der optionale Deckel mitgeliefert sein, ist sicherzustellen, dass dieser ebenfalls fest sitzt (siehe Abschnitt: Optionales Zubehör -unten). WARTUNG 1. Sicherstellen, dass die Sicherheitsvorschriften eingehalten werden (siehe Abschnitt „Gesundheit & Sicherheit“); 2. Die jährliche Wartung sollte umfassen: - Entfernen von Staubablagerung, Reinigen aller Teile; - Überprüfen der Festigkeit aller elektrischen Verbindungen; - Überprüfen der Umgebungstemperatur. - Überprüfen des Entladewiderstandes Erdung Die Erdung wird erreicht durch die Montagepunkte am Gehäuse des CLMD03. Anmerkung: Dies bedeutet natürlich, dass im Falle einer isolierten Montage des CLMD03 eine seperate leitfähige Verbindung zwischen CLMD03 und der Erde erforderlich ist (PE-Leiter). Obwohl höchste Sorgfalt aufgewendet wurde um sicherzustellen, dass die Informationen in diesem Dokument korrekt sind, wird keine gesetzliche Haftung für eventuelle Unkorrektheiten übernommen. Wir übernehmen keine Verantwortung für jegliche nicht bestimmungsgemäße Verwendung dieses Produkts. Die Firma behält sich das Recht vor, die hier gegebenen Informationen zu jeder Zeit aufgrund von technischen oder anderen Entwicklungen zu ändern oder zu modifizieren. Oberschwingungen IDie Installation von Kondensatoren in oberschwingungsbelasteten Netzen kann besondere Vorsichtsmaßnahmen erfordern, insbesondere wenn das Risiko von Resonanzerscheinungen besteht. 15 zh t 請先閱讀 注意!如同其他電容器之規範標準,CLMD03其放電設計並 不適用於快速補償閘流體開關之系統(切離後最少時間為 4 0 秒),而外部熔絲也並不可以處理等同之狀況,只有特 別設計的電容器可以使用在閘流體開關的系統中. 安全 垂直與水平安裝 注意!斷電後須待五分鐘方可進行操作。五分鐘後,先小心 進行DC電壓量測,並請確認電容器已由放電電阻完全放電 !! 為 維 護 C L M D 0 3 電 容 器 單 體 之 使 用 安 全 , 在安裝前請確保: 1.安裝及維護必須由當地現行法例許可之合格人員操作。 2.設備必須確定已完全切離電源。 CLMD03電容器必須安裝在自然通風對流由下往上的地方 數個CLMD03電容器可允許安裝於同一排列上(Fig. #1) 。三角或是方形的排列方式是不被允許的,而鄰近的電容 器之間必須要保留25m m 以上之空隙(Fig. #2 & 3)。 倘若在垂直安裝時,必須裝置於已鑽孔之固定板或支撐架 上,讓空氣產生對流環繞各電容器單元(Fig. #4 & 5)。 另CLMD03電容器不可倒置裝設(Fig. #6)。 倘若在水平安裝時,安裝時須注意空氣對流動向( Fi g . #7)。避免安裝在自然通風不良之處(Fig. #8)。 安裝之前情詳細閱讀本手冊,並將此手冊交由負責安裝、 維護和操作的專業人員保管。 驗收檢查 CLMD03 開箱後請依下列步驟檢查﹔ - 請確認銘牌規格是否符合您採購之項目及當地法規。 - 確認CLMD03本體外觀無損壞。 如有任何損壞,請立即與您最近之ABB或經銷代理商連繫 盤內安裝 注意!安裝準則僅適用於以下限制規定 - 一小時內最高環境溫度40°C - 超過24小時之最高環境平均溫度35°C - 超過一年之最高環境平均溫度 25°C 當電容器安裝於盤體內,須置放於最佳散熱位置。請儘可 能將電容器裝置於容易散熱之處,並避免電容器過熱。 儲存方式 請置放在室內,乾燥,無塵及無腐蝕性之環境,並避免受到 震動及衝擊。 置放溫度: 最低溫度: - 40°C/ - 40°F,最高溫度:75°C/ 167°F 當有安裝電抗器時,也須注意電抗器所產生的熱是否會直 接影響到電容器組。一般而言,電抗器會產生較多的熱能 ,熱對流影響必需被考量,以避免造成電容器受到傷害。 運輸及搬運 運輸途中請避免劇烈的震動,且務必確認CLMD03能妥善固 定後,方可運送。 1. 空氣對流循環 進 氣 及 排 氣 孔 之 不 同 高 度 設 計 , 應 以 最 大 空 氣 對 流 量 設 計 , 由 底部抽入冷空氣,並由頂部排出熱氣。而上方的排氣孔 橫切面設計最少應為底部進氣孔之1.2倍 注意!錯誤的安裝方式可能導致電容器提早損壞,其他材料 破損或本體損傷。 安裝 使用標準 依 照 I E C 6 0 8 3 1 的規範和建議,以及當地現行的法規。 - 1 & - 2. 強制通風 強制性的通風風扇有時是必須的(Fig. #8). 請參考以下建議: - 考慮安裝之最大環境溫度,包含電容器本身之發熱量。 - 考慮在盤體內各元件之散熱,如:電抗器,電容器, 接觸器,保險絲等等.. - 同時考慮所有設備及元件之最大允許溫度。 - 考慮設計電容器安裝位置之空氣的流通 (Fig. #9)。 2 保護等級 CLMD03單體之保護等級為IP00,選配單體(含上蓋)保護 等級為IP20。 安裝及使用 電容器應安裝在屋內平穩的基礎座或牢固的平台,且注意 通風良好的地方。周圍環境溫度:年均溫應低於35°C/ 95 °F,單日24小時內最高溫度應低於45°C/ 113°F及低於55 °C/ 131°F之短時間使用(依據IEC60831 Part 1 及2 中針對 - 25/ D 類型產品的規定)。 必須依照銘牌實際之規格為基準。 3. 當風扇無法作動,或其他原因導致溫度過高時, 應使用過溫保護裝置來切離電容器盤。 4. 定期保養及清洗濾網,過髒的濾網將使得排風效果降低 注意!環境溫度之定義為電容器裝置於盤體,圍繞電容器的 溫度,非為圍繞外部盤體之溫度。 16 t zh CLMD03安裝固定( Fig. # 10) CLMD03固定孔為M6之螺絲釘(CLMD03不附螺絲釘),最 少須固定兩孔且為對稱之方式(Fig. #11)。. 請確認所有的固定及螺絲釘是能夠支撐CLMD03電容器本 體(組)之重量。 維護保養 1. 2. - 電力連結 電源供應 CLMD03電容器將依容量提供不同的單體規格,可能會有 一至二組電容器在同一組內 。單一之電容器單體( Fi g . # 1 2 ) 或 二 組 之 電 容 器 單 體 組 成 ( F i g . #13)將提供三相之連接端子。 電纜線之額定電流最小應為整體電容器組正常電流的1 .5 倍。 並應確保所有的連接牢固及選用適當的電纜末端套管。 鎖緊電力連接之螺絲釘,建議使用的力矩為6 Nm (牛頓米)。(依據DIN46-200標準)。 確認所有連接皆已鎖緊。 若有選購上蓋,請確認其完全鎖定。(參照以下’選用配件’) 確保安全程序已完成(請參考”Safety” 章節) 年度維護保養應包含: 除塵,清潔所有的零組件 檢查所有電器連結是否牢固 檢查環境溫度 檢查放電電阻之狀態 接地 接地方式是透過CLMD03外殼固定孔來連接。 備註:包含需有另外電纜線連接CLMD03外殼與接地裝置 ,以防CLMD03被固定在絕緣的物件上。 諧波 若電容器安裝於受諧波干擾的電路上時,需要一些特別的 預防措施,尤其是在有可能發生諧波共振現象時。 試車運轉 在設備未送電之前,請檢查以下事項: - 接線已完整連接(請務必接上接地線) - 環境通風良好 - 正確鎖緊相關連結 - IP20 之上蓋已確實安裝,如有需要 (參照以下’選用配件’) 選用配件 上蓋 選 配 額 外 的 上 蓋 可 使 C L M D 0 3 具 有 I E C 60529規範之IP20保護等級。 本上蓋將提供四個螺絲組以供鎖定(與上蓋一起交付)(Fig. #14.1 & 14.2)。 此上蓋將可提供保護,以避免人員於維修及操作時可能接 觸活電部分。 我們建議使用開孔器(或鑽孔機)將上蓋合適之側邊開孔, 上蓋將提供三個凸起面讓電纜接頭使用,標準尺寸之PG2 9 ( 二個較小的凸起面供給二個電容器單元) 或PG36(一個較大的凸起面供給一個電容器單元)。電纜鎖 環亦可以適用。 放電電阻 C L M D 0 3 原廠內 建有放電電阻以符合I E C 60831之規範,在電源切離後,殘留電壓將於一分鐘內降 至50V以下。請確認再投入時間至少須間隔40秒以上,過 短的再投入時間,會造成電容器之使用壽命減短。 本份資料業經本公司細心準備以確保內容無誤,然若有不正確之處 。本公司不負任何法律責任。無論何時因其他技術上的發展之故, 本公司得保留變更或修改此文件所含內容的權利。. 17 Fig. #1 / Şek.#1 Fig. #2 / Şek.#2 Fig. #3 / Şek.#3 Fig. #4 / Şek.#4 Fig. #5 / Şek.#5 18 Fig. #6 / Şek.#6 Fig. #7 / Şek.#7 Fig. #8 / Şek.#8 Fig. #9 / Şek.#9 19 Fig. #10 / Şek.#10 Fig. #11 / Şek.#11 20 Fig. #12 / Şek.#12 Fig. #13 / Şek.#13 Fig. #14.1 / Şek.#14.1 Fig. #14.2 / Şek.#14.2 21 2009-11-12 2GCS202081A0030 ABB n.v. Power Quality Products Avenue Centrale, 10 Zoning Industriel de Jumet B-6040 Charleroi (Jumet), Belgium Phone: +32 71 250 811 Fax: +32 71 344 007
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22

ABB CLMD03 Installation, Operation & Maintenance Instructions Manual

Tipo
Installation, Operation & Maintenance Instructions Manual

En otros idiomas