Koblenz 5016 USB/R Operation & Instruction Manual

Categoría
Fuentes de alimentación ininterrumpida (UPS)
Tipo
Operation & Instruction Manual

Este manual también es adecuado para

CONGRATULATIONS!
You have just acquired a Koblenz Electronic UPS Battery Back Up. Please read this
manual carefully, before operating your new UPS. Keep manual for further references.
¡FELICIDADES!
Acaba usted de adquirir un Sistema de respaldo de energía No Break. Antes de operar
su No Break, por favor lea este manual cuidadosamente. Conserve este manual a la
mano para futuras referencias.
X. WARRANTY
This warranty gives you legal rights, and you may also have other rights which vary from state to state. This product
is warranted against malfunctions and defects in material and workmanship for a period of 3 years (2 in battery) on
model 7016 USB/R and 2 years (2 in battery) on model 5016 USB/R.
THIS WARRANTY SHALL NOT APPLY to any products or parts there-of which have damaged by tampering,
misuse or abuse or which have been altered or repaired by an unauthorized person or service center.
FOR REPAIR, the inoperative “UPS” must be delivered with shipping and delivery charges prepaid, together with
satisfactory evidence of the purchase date to the dealer from whom it was purchased. Koblenz will either repair or
replace, at its election, all defective “UPS” during the warranty period.
THE FOREGOING OBLIGATIONS ARE IN LIEU OF ALL OTHERS OBLIGATIONS AND LIABILITIES INCLUDING
NEGLIGENCE AND STATE KOBLENZ’S ENTIRE AND EXCLUSIVE LIABILITY AND PURCHASER’S EXCLUSIVE
REMEDY. KOBLENZ WILL IN NO EVENT, BE LIABLE FOR ANY DIRECT, INDIRECT, SPECIAL, INCIDENTAL, OR
CONSEQUENTIAL DAMAGES OR LOSSES WHATSOEVER, AND KOBLENZ LIABILITY UNDER NO
CIRCUMSTANCES WILL EXCEED THE CONTRACT PRICE FOR THE GOODS OR PARTS FOR WHICH
LIABILITY IS CLAIMED.
Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation
or exclusion may not apply to you.
T H O R N E ELECTRIC, CO.
P. O. BOX 18363
SAN ANTONIO. TX.
78218-0363 U.S.A.
TEL: (210) 590 12 26
FAX: (210) 590 12 58
MADE IN CHINA.
X. GARANTÍA
Koblenz Eléctrica, S. A. de C. V. garantiza el modelo 7016 USB/R por un término de 3 años, 2 en batería, y el modelo
5016 USB/R por un término de 2 años, 2 en batería, incluyendo todas sus partes y mano de obra contra cualquier
defecto de fabricación a partir de la fecha de entrega. Tratándose de productos que requieran de enseñanza o
adiestramiento en su manejo o instalación de aditamentos, accesorios, implementos o dispositivos, a partir de la fecha
en que se hubiera quedado operando normalmente después de su instalación en el domicilio que señale el consumidor
bajo las siguientes
CONDICIONES:
1. Para hacer efectiva esta garantía, no podrá exigirse mayores requisitos que la presentación de esta póliza junto con
el producto en el lugar donde fue adquirido o en cualquiera de los Centros de Servicio Autorizados.
2. La empresa se compromete a reparar o cambiar el producto, así como las piezas y componentes defectuosos del
mismo, sin ningún cargo para el consumidor; los costos del transporte que se deriven de su cumplimiento serán
cubiertos por el fabricante o por el importador.
3. El tiempo de reparación en ningún caso será mayor de 30 días contados a partir de la recepción del producto en
cualquiera de los sitios en donde pueda hacerse efectiva.
4. En cualquiera de los Centros de Servicio Autorizados podrá adquirir las refacciones y partes.
5. La reposición del fusible queda fuera de garantía.
ESTA GARANTÍA NO ES VÁLIDA EN LOS SIGUIENTES CASOS:
A. Cuando el producto ha sido utilizado en condiciones distintas a las normales.
B. Cuando el producto no ha sido operado de acuerdo con el manual de uso proporcionado.
C. Cuando el producto ha sido alterado o reparado por personas no autorizadas por la empresa.
El consumidor podrá solicitar que se haga efectiva la garantía ante la propia casa comercial donde adquirió el producto.
NOTA: En caso de que la presente garantía se extraviara, el consumidor puede recurrir a su proveedor para que le
expida otra póliza con previa presentación de la nota o factura de compra.
Producto:
Marca:
Modelo:
Número de Serie:
Nombre del Distribuidor:
Calle y Número:
Colonia o Poblado:
Ciudad / C. P. :
Fecha de Entrega:
Sello y Firma:
Importado por:
Koblenz Eléctrica, S.A. de C.V.
Av. Ciencia #28, Fraccionamiento Industrial Cuamatla
Cuautitlán Izcalli, Edo. de México
C.P. 54730 Tel: 5864-0300
19-0858-00-1 B
Modelos: 5016 USB/R 00-4205-1
7016 USB/R 00-4206-9
Descripción: SISTEMA DE RESPALDO DE ENERGÍA NO BREAK
HECHO EN CHINA
Models / Modelos: 5016 USB/R
7016 USB/R
Operation instruction manual
Manual de operación
UPS BATTERY BACK UP
SISTEMA DE RESPALDO DE ENERGÍA
NO BREAK
www.koblenz-energia.com.mx
CENTROS DE SERVICIO, REFACCIONES Y CONSUMIBLES
Para mayores informes sobre un centro de servicio autorizado cercano a su
domicilio visite nuestro sitio de internet: www.koblenz-energia.com.mx o llame sin
costo al: 01 800 849 4711 o contáctenos: [email protected]
SERVICIO Y REFACCIONES EN TODA LA REPÚBLICA
GUADALAJARA, JAL.
CINCINNATI No. 125
SECTOR REFORMA
01 800 711 8046
01 800 711 8047
MONTERREY, N.L.
PLATÓN SÁNCHEZ No. 1860
NORTE, COL. 1 DE MAYO
01 800 711 8114
01 800 712 7714
EDO. DE MÉXICO
AV. CIENCIA No. 28
FRACCIONAMIENTO INDUSTRIAL
CUAMATLA, CUAUTITLÁN IZCALLI
01 800 840 4711
(55) 5864 0300
2
Please read carefully before opetaring your new UPS.
IMPORTANT SAFETY INSTRUCTION
SAVE THIS INSTRUCTIONS
CAUTION
SAFETY
• This manual contains important safety instructions that should be followed.
• Hazardous live parts inside can be energized by the battery when the AC input power is disconnected. If you need to
de-energize this equipment, turn it off first and unplug the unit.
• Risk of electric shock, do not remove the cover. No users serviceable parts inside.
Refer servicing to qualified service personal.
• Plug this unit into an AC power outlet with fuse or circuit breaker protection do not plug into an outlet that is not grounded.
• This unit is intended for installation in a temperature controlled, indoor area free of conductive contaminants.
• Keep your Koblenz UPS away from moisture and liquids.
• Do not expose the UPS to direct sunlight.
• Do not remove the UPS cover. RISK OF ELECTRIC SHOCK: IF YOUR UPS
REQUIRES SERVICE TAKE IT TO AN AUTHORIZED SERVICE CENTER.
Call in MEXICO 01-800-849-4711 and 1-800-548-5741 in the USA
• Plugging any domestic appliance (i.e. blender, iron, refrigerator, etc.) into the UPS will void the warranty.
• Black outlets should not be used to plug in laser printers.
I. Introduction
This uninterrumptible power supply (UPS) is a high quality product designed to protect your computer system against informa-
tion loss and damages in case of a blackout. It is also designed to protect computer peripherals like monitors and modems
against voltage fluctuations. In the event of a power interruption this Koblenz UPS will instantly draw power from its internal
battery allowing you to finish your work, save open files and shut down your computer. You can also keep watching a movie or
TV show in the event of a power outage. All Koblenz UPS models feature RJ11 telephone jacks to protect your computer
against voltage spikes and surges coming through your telephone line (cable not included).
This model (see Table 1) also includes an integerated USB port that with the Koblenz Protek Sotfware gives you screen
warnings in case of power failuere (cable included). If the blackout continues and your computer is unattended, the Koblenz
Protek Software will save and close your open files and safely shutdown your computer.
II.Inspection
The following items are inside the box:
User’s manual UPS Power cord
Remove the UPS from its package and inspect it for damage that may have occurred during shipping. If any damage is
discovered, re-pack the unit and return it to the place of purchase.
III. Place the UPS
Install this UPS in a protected area that is free of excessive
dust and provide 7.8-inch (20-cm) clearance on sides for
adequate airflow around the unit.
Avoid direct sunlight
Avoid excessive heat
Avoid excessive humidity or liquids
Avoid excessive dust
IV. Connect UPS to Utility
Use the power cord that came with your UPS to connect the UPS
directly to the wall outlet.
Do not power the UPS using a surge suppressor or power strip.
Battery Charging:
The UPS battery charges whenever the UPS is connected to utility power and typically requires
less than 6 hours to charge fully. Operating runtime is reduced until the battery is fully charged.
V. Connecting Equipment to UPS
Connect the equipment to Battery Power Supplied outlets.
Battery Power Supplied Outlets (4) Connect computer, monitor, and external drive to the "Battery Power
Supplied" outlets. These outlets provide battery backup, EMI filtering, line conditioning, and surge protection.
Battery power is automatically provided in case of power failure.
6 hours
SIGA ESTAS INSTRUCCIONES
Este manual contiene instrucciones importantes para los modelos que deberán
ser seguidas durante la instalación y mantenimiento del No Break y las baterías.
El No Break utiliza voltaje que puede ser peligroso. No intente
desarmar la unidad. Esta unidad contiene partes que no son
reemplazables. Solamente.
El Voltaje interno de la batería es 12Vdc. Sellada con acido y
plomo, 6 baterías de células.
• Conectando cualquier otro tipo de receptáculo que tenga dos
polos, tres alambres de tierra, podría resultar en descarga eléctrica
peligrosa, como también a una violación a los códigos locales
eléctricos.
En el evento de una emergencia apague y desconecte el cordón de
la electricidad AC, abastecedor de energía, para propiamente
incapacitar el No Break.
No permita líquidos o cualquier otro objeto que entren en No Break,
no ponga bebidas líquidas o vasos que tengan líquido cerca de la
unidad.
Esta unidad esta diseñada para instalarse en medio ambiente
controlado (Temperatura con control dentro de áreas. Libres de
contaminantes conductivos) evitar instalar el No Break en lugares
donde hay corriente de agua o humedad excesiva.
• No enchufe el No Break dentro de su propio suministro eléctrico.
No adherir un cordón eléctrico o supresor de corrientes al el No
Break.
• No adhiera ningún otro artículo que no sea parte de la computado-
ra al No Break,como equipo medico, equipo de soporte médico, el
horno de ondas o la aspiradora.
Para reducir el riesgo de calentamiento del No Break, no lo tape,
evite la ventilación fría y exposición de la luz directa del sol o
instalación de la unidad cerca de aparatos como calentones y
hornos.
• Desenchufe el No Break antes de limpiarlo y no use liquido,
aerosol o detergente.
No abra ni mutile la batería o baterías. Liberan electrólitos que
podrían dañar la piel, los ojos y podrían ser tóxicos.
Las batería puede presentar un riesgo de sacudida eléctrica,
corriente de circuito alto y bajo, las siguientes precauciones
deberán de observarse cuando se trabaja con baterías:
1) Remover relojes, anillos y otros objetos de metal de las manos.
2) Use herramientas cubiertas con insolación.
3) Use guates de plástico y botas.
4) No ponga herramientas o partes que tenga metal en la parte de
arriba de las baterías.
5) Desconecte el cargador antes de conectar y desconectar la
terminal de las baterías.
• El servicio de las baterías deberá ser supervisado y hacerse por
personal con conocimiento de baterías, requiere cuidado.
Mantenga personal no autorizado alejado.
• Cuando reemplace las baterías, reemplácelas con el mismo tipo
de batería sellada con acido y plomo. La máxima temperatura de
ambiente es 40 grados Celsius.
Este equipo tipo A esta listo para enchufarse con la batería
instalada de suministro y puede ser operado por cualquiera.
El enchufe principal que suministra el No Break deberá ser
instalado cerca del No Break y ser de fácil acceso.
Este aparato no se destina para utilizarse por personas
(incluyendo niños) cuyas capacidades físicas, sensoriales o
mentales sean diferentes o estén reducidas, o carezcan de
experiencia o conocimiento, a menos que dichas personas reciban
una supervisión o capacitación para el funcionamiento del aparato
por una persona responsable de su seguridad.
Los niños deben supervisarse para asegurar que ellos no empleen
los aparatos como juguete.
Posible causa
Batería baja.
Batería defectuosa.
El No Break no esta prendido.
El No Break esta sobrecargado.
El No Break esta sobrecargado.
El voltaje de la batería es muy bajo.
Batería defectuosa.
El programa no se instalo debidamente.
El cordón no esa conectado
correctamente.
El interruptor se activo.
El cordón esta flojo.
Solución
Cargar la batería por 8 horas.
Reemplace la batería por otra del mismo tipo.
Presione le botón para prenderlo
Verificar si la carga del No Break es la misma
capacidad recomendada en las especificaciones.
Remover alguna carga no critica.
Cargar la batería por 8 horas o mas.
Reemplácela con el mismo tipo de batería.
Revisar las configuraciones del programa
Revise si el cordón del USB esta conectado a la
computadora y revise las configuraciones.
Ajuste el interruptor.
Conecte el cordón correctamente.
Problema
No muestra LCD enfrente
del panel.
La alarma suena
continuamente cuando el
suministro AC es normal.
Cuando le energía falla,
el tiempo de regreso es
muy corto.
La comunicación entre la
computadora y el No
Break se perdió
La red es normal pero el
SAI esta en baterías.
MODELO
CAPACIDAD
SUMINISTRO
RENDIMIENTO
BATERIA
TIEMPO DE TRANSFERENCIA
PROTECCION
FISICO
MEDIO
AMBIENTE
COMUNICACIÓN
VA/W
Voltaje
Rango de Voltaje
Frecuencia
Regulación de Frecuencia
Tipo de Onda
Tipo de Batería
Tiempo de recarga
Protección de Corriente
Protección de Corriente para Tel./Fax/DSL
Filtro EMI/RFI
Suministro AC
Dimensiones
Peso Neto
Operación en el Medio Ambiente
Nivel de Ruido
USB
5016 USB/R 7016 USB/R
500 VA/240W 700 VA/360W
120 VAC
90-145 VAC
60Hz
60Hz +/-1Hz
Ondas cuasisenoidal
12V/4.5Ah x 1 12V/7Ah x 1
4-6 Horas 90%
4-6ms (típico)
Tiempo completo, 316 joules
RJ11
Tiempo Completo
Cortocircuito
287 x 100 x 142mm
3.55 kg 4.25 kg
0-40 C, 0-90% Humedad relativa
Menos de 45dB
Windows® 2000/2003/XP/Vista/2008, Windows® 7,
Linux, Unix, y MAC
*Especificaciones pueden cambiar sin previo aviso.
7
Beware of the Power Switch it must be kept in the "ON" position,
otherwise, the UPS will be disabled and your equipment will not be
protected during a power failure.
Full Time Surge Protection Outlets (2)
Connect a printer fax machine, or scanner to the “Full Time
Surge Protected Outlets”. Both outlets do not provide
power during power failure.
CAUTION: DO NOT connect a printer to any Battery Power
Supplied outlet.
VI. Connect Modem/Phoneline
This UPS protects a single line (1 in/1out) phone, modem, or fax machine from surges when connected through the UPS.
Plug in conning Internet line into the “IN” socket.
Use one more Internet line cable in the “OUT” socket and plug one other end to the modem input socket.
VII. Connect UPS to Computer
Connect one end of the USB cable to PC and the other to the
USB port at the rear of the UPS. Insert ViewPower software
CD or download the latest version of ViewPower software from
http://www.power-software-download.com to your hard drive.
Follow on-screen instructions to complete the software installation.
Once PC is restarted, ViewPower is geared and presents as an
orange plug icon located in the system tray at the right-bottom corner.
VIII. Turn On/Off
To turn on the UPS unit, press the power On/Off Switch once.
To turn off the UPS unit, press the Power On/Off Switch again.
IX. Storage
To store the UPS for an extended period, cover it and store
with battery fully charged. While in storage, recharge the
battery every 3 months to secure battery life.
MonitorComputer
Printer
Scanner
Impresora
Scanner
UPS Status Indicator
Fault: Red lighting
Battery mode: Yellow flashing
AC mode: Green lighting
Power switch on/off
Power Switch: Press and release the button to supply
power to the Battery Power Supplied Outlets. Press and
release the button again to switch off power to the Battery
Power Supplied Outlets.
AC Mode Indicator: This green LED is lit when the UPS
transfers utility power to both Battery Power Supplied
Outlets and Full Time Surge Protection Outlets.
Battery Mode Indicator: This yellow LED flashes when
the utility power is outside acceptable limits and the battery
supplies power only through the Battery Power Supplied
Outlets.
Botón para Prender: Presione y libere el botón que
abastece la batería de energía. Presione y libere otra vez el
botón para apagar la energía de la batería.
Modo Indicador AC: La luz verde del LED indica que el
UPS esta pasando energía de corriente a los enchufes
suministrados con energía de batería y a los enchufes
protegidos.
Indicador Modo de la Batería: La luz amarilla del LED
enciende cuando la corriente de energía de afuera es
limitada y la batería suministra la energía los enchufes
solamente a través de la batería.
PRECAUCIÓN: Nunca conecte la impresora o productos motorizados a los enchufes abastecidos por energía de batería.
VI. Conectar Línea de Teléfono/Modem
El No Break protege una sola línea (1 entrada/ 1 salida) teléfono, modem o fax, contra corriente cuando es conectado a través del
No Break. Enchufe La Red en la conexión "IN" esta se encuentra en la parte de atrás del No Break. Use el enchufe "Out" para
conectar el Modem.
VII. Comunicar No Break con la Computadora
Conecte uno de los cables USB a la computadora personal y
otro al puerto USB en la parte de atrás del No Break.
Inserte el Programa CD o descargue la versión mas reciente en:
<http://www.power-software-download.com>
en su manejador y siga las instrucciones de la pantalla para que
complete la instalación del programa.
Una vez que el que la Computadora Personal prende, se puede ver en
color naranja un signo en la esquina del lado derecho de la parte de abajo.
VIII. Prender/ APAGAR
Para prender la unidad No Break, presione el botón.
Para apagar la unidad No Break, presione el botón otra vez.
IX. Almacenar
Para almacenar el No Break por un periodo prolongado, cubra y almacénelo
con la batería completamente cargada, mientras este almacenado
cargue la batería cada 3 meses para garantizar la vida de la batería.
Indicadores y Controles No Break
UPS Indicador de la Condición
Falla: Luz roja prendida
Modo de batería: Luz amarilla
AC modo de corriente alternada: Luz verde
Botón para Prender
Contactos con Protección de Corriente todo el Tiempo (2)
Conectar la impresora, fax, escáner al enchufe con corriente protegida.
Ambos enchufes no proporcionan energía durante una falla eléctrica.
Contactos
SIN Respaldo
(blancos)
Modo de la Batería: Sonando cada 10 segundos
Batería Baja: Sonando cada segundo
Reemplazar la Batería: Sonando cada 2 segundos.
Falla/Batería Baja/Indicador Reemplazo de Batería:
Esta luz roja del LED es encendida siempre que el No
Break falla la batería esta baja o la vida de la batería
esta llegando a su final. La batería deberá ser
reemplazada cuando el botón del No Break esta
pagado.
Sobrecarga: Sonando cada 0.5 segundos
Falla: Continuamente sonando
36
Battery Mode: sounding every 10 seconds
Low Battery: sounding every seconds
Battery Replacement: sounding every 2 second.
Fault/Low Battery/Battery Replacement Indicator:
This red LED is lit whenever the UPS fails, low battery
occurs, or battery is close to the end of its useful life.
The battery should be replaced with UPS switched off.
Overload: sounding every 0.5 seconds
Fault: continuously sounding
Por favor lea este manual cuidadosamente
antes de operar su No Break
I. Introducción
El sistema de respaldo de energía (No Break) es un equipo de alta calidad diseñado especialmente para proteger a las
computadoras contra la pérdida de información y daños a los componentes periféricos como monitores y módems, durante
fluctuaciones de corriente o CUANDO SE VA LA LUZ; el sistema de respaldo de energía Koblenz transferirá la carga o una
fuente alterna derivada de una batería integrada al No Break. La batería proveerá energía al tiempo sificiente para salvar
achivos y concluir trabajos en la computadora. Así mismo, permite disfrutar de programas de televisión y películas en video
por un tiempo limitado, dependiendo de la carga de la batería.
Estos modelos incluyen puerto de comunicación USB (ver cuadro 1), el cual conectado a su computadora y con la instalación
del Koblenz Protek Software, le dará mensajes de advertencia en la pantalla de su computadora en caso de fallas en el
suministro eléctrico. Durante un apagón de larga duración, las baterías del No Break comienzan a descargarse, el Koblenz
Protek Software permite el cierre automático del sistema operativo y de sus archivos.
SAVE THESE INSTRUCTIONS
This manual contains important instructions for this UPS that should be followed
during installation and maintenance of the UPS and batteries.
This UPS utilizes voltage that may be hazardous. Do not attempt
to disassemble the unit. The unit contains no user replaceable
parts. Only factory service personnel may perform repairs.
Internal battery voltage is 12Vdc. Sealed, lead-acid, 6 cells
battery.
Connection to any other type of receptacle other than a two-pole,
three-wire grounded receptacle may result in shock hazard as well
as violate local electrical codes.
In the event of an emergency, press the "OFF" button and
disconnect the power cord from the AC power supply to properly
disable the UPS.
Do not allow any liquids or any foreign object to enter the UPS.
Do not place beverages or any other liquid-containing vessels on or
near the unit.
This unit is intended installation in a controlled environment
(temperature controlled, indoor area free of conductive
contaminants). Avoid installing the UPS in locations where there is
standing or running water, or excessive humidity.
Do not plug the UPS input into its own output.
Do not attach a power strip or surge suppressor to the UPS.
Do not attach non-computer-related items, such as medical
equipment, life-support equipment, microwave ovens, or vacuum
cleaners to UPS.
To reduce the risk of overheating the UPS, do not cover the UPS'
cooling vents and avoid exposing the unit to direct sunlight or
installing the unit near heat emitting appliances such as space
heater or furnaces.
Unplug the UPS prior to cleaning and do not use liquid or spray
detergent.
Do not open or mutilate the battery or batteries. Release
electrolyte is harmful to the skin and eyes. It may be toxic.
A battery can present a risk of electrical shock and high short
circuit current. The following precautions should be observed
when working on batteries:
1) Remove watches, rings, or other metal objects from the
hands.
2) Use tools with insulated handles.
3) Wear rubber gloves and boots.
4) Do not lay tools or metal parts on top of batteries.
5) Disconnect charging source prior to connecting or
disconnecting batteries terminal.
Servicing of batteries should be performed or supervised by
personnel knowledgeable of batteries and the required
precautions. Keep unauthorized personnel away from batteries.
When replacing batteries, replace with the same number and
type of sealed lead-acid battery. The maximum ambient
temperature rating is 40°C.
During the installation of this equipment it should be assured
that the sum of the leakage currents of the UPS and the
connected loads does not exceed 3.5mA.
This pluggable type A equipment with battery already installed
by the supplier is operator installable and may be operated by
laymen.
Attention, hazardous through electric shock. Also with
disconnection of this unit from the mains, hazardous voltage still
may be accessible through supply from battery. The battery
supply should be therefore disconnected in the plus and minus
pole of the battery when maintenance or service work inside the
UPS is necessary.
The mains socket outlet that supplies the UPS shall be installed
near the UPS and shall be easily accessible.
Monitor
Computadora
Probable Cause
Low battery.
Battery fault.
The UPS is not turned on.
The UPS is overloaded.
The UPS is overloaded.
Battery voltage is too low.
Battery defect. It might be due to high
temperature operation environment, or
improper operation to battery.
Power cord is loose.
Solution
Charge the battery at least 8 hours.
Replace the battery with the same type of battery.
Press the power switch again to turn on the UPS.
Remove some loads first. Before reconnecting
equipment, please verify that the load matches
the UPS capability specified in the specs.
Remove some critical load.
Charge the battery at least 8 hours.
Replace the battery with the same type of battery.
Reconnect the power cord properly.
Problem
No LED display on
the front panel.
Alarm continuously sounds
when the mains is normal.
When power fails, backup
time is shorten.
The mains is normal but
LED is flashing.
II. Inspección
Los siguientes artículos están dentro de la caja:
Manual del Usuario Cable USB • No Break Programa CD
Al sacar el No Break de la caja, es necesario inspeccionar si algún daño fue causado en el envío de la mercancía, si la unidad esta
dañada póngala en la caja y devuélvala a la tienda donde la compro.
III. Lugar del No Break
Permita 7.8 pulgadas (20-cm) de espacio a los lados para la
circulación de aire alrededor de la unidad cuando la unidad
es instalada al lado del monitor.
Evitar la luz directa del sol.
Evitar calor excesivo.
Evitar excesiva humedad y líquidos.
Evitar polvo excesivo.
IV. Enchufe el No Break a la Corriente
• Conecte el cable de línea del No break directamente al enchufe de la pared.
• No conecte al No Break otro cable, supresor o extensión de corriente.
Cargando la Batería:
El No Break se carga siempre que este conectado a la corriente eléctrica
y típicamente necesita 6 horas para carga completa.
V. Conecte el Equipo al No Break
Conecte los equipos que desea reapaldar en los contactos del No Break con respaldo de energía (negros).
Modelo 5016 USB/R 2 contactos respaldados.
Modelo 7016 USB/R 4 contactos respaldados.
Estos contactos proporcionan batería de reserva, EMI esta filtrando condicionando la línea de protección de corriente.
La energía de la batería es activada automáticamente en caso de una falla eléctrica. Asegúrese de que el No Break este prendido de
otra manera el No Break se deshabilitará y su equipo no será protegido en caso de una falla eléctrica.
6 horas
2 Contactos
CON Respaldo
(negros)
Monitor
Computadora
4 Contactos
CON Respaldo
(negros)
4 5
Modelo: 5016 USB/R Modelo: 7016 USB/R

Transcripción de documentos

X. WARRANTY This warranty gives you legal rights, and you may also have other rights which vary from state to state. This product is warranted against malfunctions and defects in material and workmanship for a period of 3 years (2 in battery) on model 7016 USB/R and 2 years (2 in battery) on model 5016 USB/R. THIS WARRANTY SHALL NOT APPLY to any products or parts there-of which have damaged by tampering, misuse or abuse or which have been altered or repaired by an unauthorized person or service center. FOR REPAIR, the inoperative “UPS” must be delivered with shipping and delivery charges prepaid, together with satisfactory evidence of the purchase date to the dealer from whom it was purchased. Koblenz will either repair or replace, at its election, all defective “UPS” during the warranty period. THE FOREGOING OBLIGATIONS ARE IN LIEU OF ALL OTHERS OBLIGATIONS AND LIABILITIES INCLUDING NEGLIGENCE AND STATE KOBLENZ’S ENTIRE AND EXCLUSIVE LIABILITY AND PURCHASER’S EXCLUSIVE REMEDY. KOBLENZ WILL IN NO EVENT, BE LIABLE FOR ANY DIRECT, INDIRECT, SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES OR LOSSES WHATSOEVER, AND KOBLENZ LIABILITY UNDER NO CIRCUMSTANCES WILL EXCEED THE CONTRACT PRICE FOR THE GOODS OR PARTS FOR WHICH LIABILITY IS CLAIMED. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. T H O R N E ELECTRIC, CO. P. O. BOX 18363 SAN ANTONIO. TX. 78218-0363 U.S.A. TEL: (210) 590 12 26 FAX: (210) 590 12 58 MADE IN CHINA. Operation instruction manual Manual de operación UPS BATTERY BACK UP SISTEMA DE RESPALDO DE ENERGÍA NO BREAK X. GARANTÍA Koblenz Eléctrica, S. A. de C. V. garantiza el modelo 7016 USB/R por un término de 3 años, 2 en batería, y el modelo 5016 USB/R por un término de 2 años, 2 en batería, incluyendo todas sus partes y mano de obra contra cualquier defecto de fabricación a partir de la fecha de entrega. Tratándose de productos que requieran de enseñanza o adiestramiento en su manejo o instalación de aditamentos, accesorios, implementos o dispositivos, a partir de la fecha en que se hubiera quedado operando normalmente después de su instalación en el domicilio que señale el consumidor bajo las siguientes CONDICIONES: 1. Para hacer efectiva esta garantía, no podrá exigirse mayores requisitos que la presentación de esta póliza junto con el producto en el lugar donde fue adquirido o en cualquiera de los Centros de Servicio Autorizados. 2. La empresa se compromete a reparar o cambiar el producto, así como las piezas y componentes defectuosos del mismo, sin ningún cargo para el consumidor; los costos del transporte que se deriven de su cumplimiento serán cubiertos por el fabricante o por el importador. 3. El tiempo de reparación en ningún caso será mayor de 30 días contados a partir de la recepción del producto en cualquiera de los sitios en donde pueda hacerse efectiva. 4. En cualquiera de los Centros de Servicio Autorizados podrá adquirir las refacciones y partes. 5. La reposición del fusible queda fuera de garantía. ESTA GARANTÍA NO ES VÁLIDA EN LOS SIGUIENTES CASOS: A. Cuando el producto ha sido utilizado en condiciones distintas a las normales. B. Cuando el producto no ha sido operado de acuerdo con el manual de uso proporcionado. C. Cuando el producto ha sido alterado o reparado por personas no autorizadas por la empresa. El consumidor podrá solicitar que se haga efectiva la garantía ante la propia casa comercial donde adquirió el producto. NOTA: En caso de que la presente garantía se extraviara, el consumidor puede recurrir a su proveedor para que le expida otra póliza con previa presentación de la nota o factura de compra. Producto: Marca: Modelo: Número de Serie: Nombre del Distribuidor: Calle y Número: Colonia o Poblado: Ciudad / C. P. : Fecha de Entrega: Sello y Firma: Importado por: Koblenz Eléctrica, S.A. de C.V. Av. Ciencia #28, Fraccionamiento Industrial Cuamatla Cuautitlán Izcalli, Edo. de México C.P. 54730 Tel: 5864-0300 19-0858-00-1 B Modelos: 5016 USB/R 00-4205-1 7016 USB/R 00-4206-9 Descripción: SISTEMA DE RESPALDO DE ENERGÍA NO BREAK CENTROS DE SERVICIO, REFACCIONES Y CONSUMIBLES Para mayores informes sobre un centro de servicio autorizado cercano a su domicilio visite nuestro sitio de internet: www.koblenz-energia.com.mx o llame sin costo al: 01 800 849 4711 o contáctenos: [email protected] GUADALAJARA, JAL. MONTERREY, N.L. 01 800 711 8046 01 800 711 8047 01 800 711 8114 01 800 712 7714 CINCINNATI No. 125 SECTOR REFORMA PLATÓN SÁNCHEZ No. 1860 NORTE, COL. 1 DE MAYO EDO. DE MÉXICO AV. CIENCIA No. 28 FRACCIONAMIENTO INDUSTRIAL CUAMATLA, CUAUTITLÁN IZCALLI 01 800 840 4711 (55) 5864 0300 SERVICIO Y REFACCIONES EN TODA LA REPÚBLICA HECHO EN CHINA Models / Modelos: 5016 USB/R 7016 USB/R CONGRATULATIONS! You have just acquired a Koblenz Electronic UPS Battery Back Up. Please read this manual carefully, before operating your new UPS. Keep manual for further references. ¡FELICIDADES! Acaba usted de adquirir un Sistema de respaldo de energía No Break. Antes de operar su No Break, por favor lea este manual cuidadosamente. Conserve este manual a la mano para futuras referencias. www.koblenz-energia.com.mx Please read carefully before opetaring your new UPS. SIGA ESTAS INSTRUCCIONES Este manual contiene instrucciones importantes para los modelos que deberán ser seguidas durante la instalación y mantenimiento del No Break y las baterías. IMPORTANT SAFETY INSTRUCTION SAVE THIS INSTRUCTIONS • This manual contains important safety instructions that should be followed. CAUTION • Hazardous live parts inside can be energized by the battery when the AC input power is disconnected. If you need to de-energize this equipment, turn it off first and unplug the unit. • Risk of electric shock, do not remove the cover. No users serviceable parts inside. Refer servicing to qualified service personal. • Plug this unit into an AC power outlet with fuse or circuit breaker protection do not plug into an outlet that is not grounded. • This unit is intended for installation in a temperature controlled, indoor area free of conductive contaminants. SAFETY • Keep your Koblenz UPS away from moisture and liquids. • Do not expose the UPS to direct sunlight. • Do not remove the UPS cover. RISK OF ELECTRIC SHOCK: IF YOUR UPS REQUIRES SERVICE TAKE IT TO AN AUTHORIZED SERVICE CENTER. Call in MEXICO 01-800-849-4711 and 1-800-548-5741 in the USA • Plugging any domestic appliance (i.e. blender, iron, refrigerator, etc.) into the UPS will void the warranty. • Black outlets should not be used to plug in laser printers. I. Introduction This uninterrumptible power supply (UPS) is a high quality product designed to protect your computer system against information loss and damages in case of a blackout. It is also designed to protect computer peripherals like monitors and modems against voltage fluctuations. In the event of a power interruption this Koblenz UPS will instantly draw power from its internal battery allowing you to finish your work, save open files and shut down your computer. You can also keep watching a movie or TV show in the event of a power outage. All Koblenz UPS models feature RJ11 telephone jacks to protect your computer against voltage spikes and surges coming through your telephone line (cable not included). This model (see Table 1) also includes an integerated USB port that with the Koblenz Protek Sotfware gives you screen warnings in case of power failuere (cable included). If the blackout continues and your computer is unattended, the Koblenz Protek Software will save and close your open files and safely shutdown your computer. II.Inspection The following items are inside the box: • User’s manual • UPS • Power cord Remove the UPS from its package and inspect it for damage that may have occurred during shipping. If any damage is discovered, re-pack the unit and return it to the place of purchase. III. Place the UPS Install this UPS in a protected area that is free of excessive dust and provide 7.8-inch (20-cm) clearance on sides for adequate airflow around the unit. • Avoid direct sunlight • Avoid excessive heat • Avoid excessive humidity or liquids • Avoid excessive dust • El No Break utiliza voltaje que puede ser peligroso. No intente desarmar la unidad. Esta unidad contiene partes que no son reemplazables. Solamente. • El Voltaje interno de la batería es 12Vdc. Sellada con acido y plomo, 6 baterías de células. • Conectando cualquier otro tipo de receptáculo que tenga dos polos, tres alambres de tierra, podría resultar en descarga eléctrica peligrosa, como también a una violación a los códigos locales eléctricos. • En el evento de una emergencia apague y desconecte el cordón de la electricidad AC, abastecedor de energía, para propiamente incapacitar el No Break. • No permita líquidos o cualquier otro objeto que entren en No Break, no ponga bebidas líquidas o vasos que tengan líquido cerca de la unidad. • Esta unidad esta diseñada para instalarse en medio ambiente controlado (Temperatura con control dentro de áreas. Libres de contaminantes conductivos) evitar instalar el No Break en lugares donde hay corriente de agua o humedad excesiva. • No enchufe el No Break dentro de su propio suministro eléctrico. • No adherir un cordón eléctrico o supresor de corrientes al el No Break. • No adhiera ningún otro artículo que no sea parte de la computadora al No Break,como equipo medico, equipo de soporte médico, el horno de ondas o la aspiradora. • Para reducir el riesgo de calentamiento del No Break, no lo tape, evite la ventilación fría y exposición de la luz directa del sol o instalación de la unidad cerca de aparatos como calentones y hornos. • Desenchufe el No Break antes de limpiarlo y no use liquido, aerosol o detergente. • No abra ni mutile la batería o baterías. Liberan electrólitos que podrían dañar la piel, los ojos y podrían ser tóxicos. Posible causa Batería baja. Batería defectuosa. El No Break no esta prendido. El No Break esta sobrecargado. Solución Cargar la batería por 8 horas. Reemplace la batería por otra del mismo tipo. Presione le botón para prenderlo Cuando le energía falla, el tiempo de regreso es muy corto. El No Break esta sobrecargado. El voltaje de la batería es muy bajo. Batería defectuosa. Remover alguna carga no critica. Cargar la batería por 8 horas o mas. Reemplácela con el mismo tipo de batería. La comunicación entre la computadora y el No Break se perdió La red es normal pero el SAI esta en baterías. El programa no se instalo debidamente. El cordón no esa conectado correctamente. Revisar las configuraciones del programa Revise si el cordón del USB esta conectado a la computadora y revise las configuraciones. Problema No muestra LCD enfrente del panel. La alarma suena continuamente cuando el suministro AC es normal. MODELO CAPACIDAD El interruptor se activo. El cordón esta flojo. IV. Connect UPS to Utility VA/W Voltaje Rango de Voltaje SUMINISTRO Frecuencia Regulación de Frecuencia RENDIMIENTO Tipo de Onda Tipo de Batería BATERIA Tiempo de recarga TIEMPO DE TRANSFERENCIA Protección de Corriente Battery Charging: PROTECCION Use the power cord that came with your UPS to connect the UPS directly to the wall outlet. Do not power the UPS using a surge suppressor or power strip. The UPS battery charges whenever the UPS is connected to utility power and typically requires less than 6 hours to charge fully. Operating runtime is reduced until the battery is fully charged. V. Connecting Equipment to UPS 6 hours Connect the equipment to Battery Power Supplied outlets. Battery Power Supplied Outlets (4) Connect computer, monitor, and external drive to the "Battery Power Supplied" outlets. These outlets provide battery backup, EMI filtering, line conditioning, and surge protection. Battery power is automatically provided in case of power failure. 2 • Las batería puede presentar un riesgo de sacudida eléctrica, corriente de circuito alto y bajo, las siguientes precauciones deberán de observarse cuando se trabaja con baterías: 1) Remover relojes, anillos y otros objetos de metal de las manos. 2) Use herramientas cubiertas con insolación. 3) Use guates de plástico y botas. 4) No ponga herramientas o partes que tenga metal en la parte de arriba de las baterías. 5) Desconecte el cargador antes de conectar y desconectar la terminal de las baterías. • El servicio de las baterías deberá ser supervisado y hacerse por personal con conocimiento de baterías, requiere cuidado. Mantenga personal no autorizado alejado. • Cuando reemplace las baterías, reemplácelas con el mismo tipo de batería sellada con acido y plomo. La máxima temperatura de ambiente es 40 grados Celsius. • Este equipo tipo A esta listo para enchufarse con la batería instalada de suministro y puede ser operado por cualquiera. • El enchufe principal que suministra el No Break deberá ser instalado cerca del No Break y ser de fácil acceso. • Este aparato no se destina para utilizarse por personas (incluyendo niños) cuyas capacidades físicas, sensoriales o mentales sean diferentes o estén reducidas, o carezcan de experiencia o conocimiento, a menos que dichas personas reciban una supervisión o capacitación para el funcionamiento del aparato por una persona responsable de su seguridad. • Los niños deben supervisarse para asegurar que ellos no empleen los aparatos como juguete. FISICO MEDIO AMBIENTE COMUNICACIÓN Verificar si la carga del No Break es la misma capacidad recomendada en las especificaciones. Ajuste el interruptor. Conecte el cordón correctamente. 5016 USB/R 500 VA/240W 7016 USB/R 700 VA/360W 120 VAC 90-145 VAC 60Hz 60Hz +/-1Hz Ondas cuasisenoidal 12V/4.5Ah x 1 12V/7Ah x 1 4-6 Horas 90% 4-6ms (típico) Tiempo completo, 316 joules Protección de Corriente para Tel./Fax/DSL RJ11 Filtro EMI/RFI Tiempo Completo Suministro AC Cortocircuito Dimensiones 287 x 100 x 142mm Peso Neto 3.55 kg 4.25 kg Operación en el Medio Ambiente 0-40 C, 0-90% Humedad relativa Nivel de Ruido Menos de 45dB USB Windows® 2000/2003/XP/Vista/2008, Windows® 7, Linux, Unix, y MAC *Especificaciones pueden cambiar sin previo aviso. 7 Contactos con Protección de Corriente todo el Tiempo (2) Beware of the Power Switch it must be kept in the "ON" position, otherwise, the UPS will be disabled and your equipment will not be protected during a power failure. Conectar la impresora, fax, escáner al enchufe con corriente protegida. Ambos enchufes no proporcionan energía durante una falla eléctrica. Contactos SIN Respaldo (blancos) Impresora Full Time Surge Protection Outlets (2) Computer Monitor Printer Scanner Scanner PRECAUCIÓN: Nunca conecte la impresora o productos motorizados a los enchufes abastecidos por energía de batería. VI. Conectar Línea de Teléfono/Modem El No Break protege una sola línea (1 entrada/ 1 salida) teléfono, modem o fax, contra corriente cuando es conectado a través del No Break. Enchufe La Red en la conexión "IN" esta se encuentra en la parte de atrás del No Break. Use el enchufe "Out" para conectar el Modem. Connect a printer fax machine, or scanner to the “Full Time Surge Protected Outlets”. Both outlets do not provide power during power failure. CAUTION: DO NOT connect a printer to any Battery Power Supplied outlet. VI. Connect Modem/Phoneline This UPS protects a single line (1 in/1out) phone, modem, or fax machine from surges when connected through the UPS. Plug in conning Internet line into the “IN” socket. Use one more Internet line cable in the “OUT” socket and plug one other end to the modem input socket. VII. Comunicar No Break con la Computadora Conecte uno de los cables USB a la computadora personal y otro al puerto USB en la parte de atrás del No Break. Inserte el Programa CD o descargue la versión mas reciente en: <http://www.power-software-download.com> en su manejador y siga las instrucciones de la pantalla para que complete la instalación del programa. VII. Connect UPS to Computer Connect one end of the USB cable to PC and the other to the USB port at the rear of the UPS. Insert ViewPower software CD or download the latest version of ViewPower software from http://www.power-software-download.com to your hard drive. Follow on-screen instructions to complete the software installation. Una vez que el que la Computadora Personal prende, se puede ver en color naranja un signo en la esquina del lado derecho de la parte de abajo. Once PC is restarted, ViewPower is geared and presents as an orange plug icon located in the system tray at the right-bottom corner. VIII. Prender/ APAGAR VIII. Turn On/Off Para prender la unidad No Break, presione el botón. Para apagar la unidad No Break, presione el botón otra vez. To turn on the UPS unit, press the power On/Off Switch once. To turn off the UPS unit, press the Power On/Off Switch again. IX. Almacenar Para almacenar el No Break por un periodo prolongado, cubra y almacénelo con la batería completamente cargada, mientras este almacenado cargue la batería cada 3 meses para garantizar la vida de la batería. Indicadores y Controles No Break IX. Storage To store the UPS for an extended period, cover it and store with battery fully charged. While in storage, recharge the battery every 3 months to secure battery life. UPS Indicador de la Condición UPS Status Indicator Falla: Luz roja prendida Fault: Red lighting Modo de batería: Luz amarilla AC modo de corriente alternada: Luz verde Botón para Prender 6 AC mode: Green lighting Power switch on/off Botón para Prender: Presione y libere el botón que abastece la batería de energía. Presione y libere otra vez el botón para apagar la energía de la batería. Modo de la Batería: Sonando cada 10 segundos Batería Baja: Sonando cada segundo Reemplazar la Batería: Sonando cada 2 segundos. Modo Indicador AC: La luz verde del LED indica que el UPS esta pasando energía de corriente a los enchufes suministrados con energía de batería y a los enchufes protegidos. Falla/Batería Baja/Indicador Reemplazo de Batería: Esta luz roja del LED es encendida siempre que el No Break falla la batería esta baja o la vida de la batería esta llegando a su final. La batería deberá ser reemplazada cuando el botón del No Break esta pagado. Indicador Modo de la Batería: La luz amarilla del LED enciende cuando la corriente de energía de afuera es limitada y la batería suministra la energía los enchufes solamente a través de la batería. Battery mode: Yellow flashing Sobrecarga: Sonando cada 0.5 segundos Falla: Continuamente sonando Power Switch: Press and release the button to supply power to the Battery Power Supplied Outlets. Press and release the button again to switch off power to the Battery Power Supplied Outlets. AC Mode Indicator: This green LED is lit when the UPS transfers utility power to both Battery Power Supplied Outlets and Full Time Surge Protection Outlets. Battery Mode Indicator: This yellow LED flashes when the utility power is outside acceptable limits and the battery supplies power only through the Battery Power Supplied Outlets. Battery Mode: sounding every 10 seconds Low Battery: sounding every seconds Battery Replacement: sounding every 2 second. Fault/Low Battery/Battery Replacement Indicator: This red LED is lit whenever the UPS fails, low battery occurs, or battery is close to the end of its useful life. The battery should be replaced with UPS switched off. Overload: sounding every 0.5 seconds Fault: continuously sounding 3 SAVE THESE INSTRUCTIONS This manual contains important instructions for this UPS that should be followed during installation and maintenance of the UPS and batteries. • This UPS utilizes voltage that may be hazardous. Do not attempt to disassemble the unit. The unit contains no user replaceable parts. Only factory service personnel may perform repairs. • Internal battery voltage is 12Vdc. Sealed, lead-acid, 6 cells battery. • Connection to any other type of receptacle other than a two-pole, three-wire grounded receptacle may result in shock hazard as well as violate local electrical codes. • In the event of an emergency, press the "OFF" button and disconnect the power cord from the AC power supply to properly disable the UPS. • Do not allow any liquids or any foreign object to enter the UPS. Do not place beverages or any other liquid-containing vessels on or near the unit. • This unit is intended installation in a controlled environment (temperature controlled, indoor area free of conductive contaminants). Avoid installing the UPS in locations where there is standing or running water, or excessive humidity. • Do not plug the UPS input into its own output. • Do not attach a power strip or surge suppressor to the UPS. • Do not attach non-computer-related items, such as medical equipment, life-support equipment, microwave ovens, or vacuum cleaners to UPS. • To reduce the risk of overheating the UPS, do not cover the UPS' cooling vents and avoid exposing the unit to direct sunlight or installing the unit near heat emitting appliances such as space heater or furnaces. • Unplug the UPS prior to cleaning and do not use liquid or spray detergent. • Do not open or mutilate the battery or batteries. Release electrolyte is harmful to the skin and eyes. It may be toxic. • A battery can present a risk of electrical shock and high short circuit current. The following precautions should be observed when working on batteries: 1) Remove watches, rings, or other metal objects from the hands. 2) Use tools with insulated handles. 3) Wear rubber gloves and boots. 4) Do not lay tools or metal parts on top of batteries. 5) Disconnect charging source prior to connecting or disconnecting batteries terminal. • Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries. • When replacing batteries, replace with the same number and type of sealed lead-acid battery. The maximum ambient temperature rating is 40°C. • During the installation of this equipment it should be assured that the sum of the leakage currents of the UPS and the connected loads does not exceed 3.5mA. • This pluggable type A equipment with battery already installed by the supplier is operator installable and may be operated by laymen. • Attention, hazardous through electric shock. Also with disconnection of this unit from the mains, hazardous voltage still may be accessible through supply from battery. The battery supply should be therefore disconnected in the plus and minus pole of the battery when maintenance or service work inside the UPS is necessary. • The mains socket outlet that supplies the UPS shall be installed near the UPS and shall be easily accessible. Probable Cause Low battery. Battery fault. The UPS is not turned on. Alarm continuously sounds The UPS is overloaded. when the mains is normal. Problem No LED display on the front panel. When power fails, backup time is shorten. The mains is normal but LED is flashing. The UPS is overloaded. Battery voltage is too low. Battery defect. It might be due to high temperature operation environment, or improper operation to battery. Power cord is loose. Solution Charge the battery at least 8 hours. Replace the battery with the same type of battery. Press the power switch again to turn on the UPS. Remove some loads first. Before reconnecting equipment, please verify that the load matches the UPS capability specified in the specs. Remove some critical load. Charge the battery at least 8 hours. Replace the battery with the same type of battery. Reconnect the power cord properly. Por favor lea este manual cuidadosamente antes de operar su No Break I. Introducción El sistema de respaldo de energía (No Break) es un equipo de alta calidad diseñado especialmente para proteger a las computadoras contra la pérdida de información y daños a los componentes periféricos como monitores y módems, durante fluctuaciones de corriente o CUANDO SE VA LA LUZ; el sistema de respaldo de energía Koblenz transferirá la carga o una fuente alterna derivada de una batería integrada al No Break. La batería proveerá energía al tiempo sificiente para salvar achivos y concluir trabajos en la computadora. Así mismo, permite disfrutar de programas de televisión y películas en video por un tiempo limitado, dependiendo de la carga de la batería. Estos modelos incluyen puerto de comunicación USB (ver cuadro 1), el cual conectado a su computadora y con la instalación del Koblenz Protek Software, le dará mensajes de advertencia en la pantalla de su computadora en caso de fallas en el suministro eléctrico. Durante un apagón de larga duración, las baterías del No Break comienzan a descargarse, el Koblenz Protek Software permite el cierre automático del sistema operativo y de sus archivos. II. Inspección Los siguientes artículos están dentro de la caja: • Manual del Usuario • Cable USB • No Break • Programa CD Al sacar el No Break de la caja, es necesario inspeccionar si algún daño fue causado en el envío de la mercancía, si la unidad esta dañada póngala en la caja y devuélvala a la tienda donde la compro. III. Lugar del No Break Permita 7.8 pulgadas (20-cm) de espacio a los lados para la circulación de aire alrededor de la unidad cuando la unidad es instalada al lado del monitor. • Evitar la luz directa del sol. • Evitar calor excesivo. • Evitar excesiva humedad y líquidos. • Evitar polvo excesivo. IV. Enchufe el No Break a la Corriente • Conecte el cable de línea del No break directamente al enchufe de la pared. • No conecte al No Break otro cable, supresor o extensión de corriente. Cargando la Batería: El No Break se carga siempre que este conectado a la corriente eléctrica y típicamente necesita 6 horas para carga completa. 6 horas V. Conecte el Equipo al No Break Conecte los equipos que desea reapaldar en los contactos del No Break con respaldo de energía (negros). Modelo 5016 USB/R 2 contactos respaldados. Modelo 7016 USB/R 4 contactos respaldados. Estos contactos proporcionan batería de reserva, EMI esta filtrando condicionando la línea de protección de corriente. La energía de la batería es activada automáticamente en caso de una falla eléctrica. Asegúrese de que el No Break este prendido de otra manera el No Break se deshabilitará y su equipo no será protegido en caso de una falla eléctrica. Computadora 2 Contactos CON Respaldo (negros) 4 Modelo: 5016 USB/R Monitor Computadora Monitor 4 Contactos CON Respaldo (negros) Modelo: 7016 USB/R 5
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Koblenz 5016 USB/R Operation & Instruction Manual

Categoría
Fuentes de alimentación ininterrumpida (UPS)
Tipo
Operation & Instruction Manual
Este manual también es adecuado para

En otros idiomas