ION8650 switchboard meter installation guide Installation
ENGLISH
COM3 Setup
(Front optical)
Protocol Specifies the protocol used on this port None, ION, Modbus RTU, Modbus Master1,
DNP v3.00, DLMS, GPS: Truetime/Datum,
GPS: Arbiter, GPS: Arbiter-Vorne,Factory
ION
Baud Rate Specifies baud rate during serial communications 300 to 115200 9600
Transmit Delay Specifies the port’s transmit delay setting 0 to 1.00 0.01
Unit ID Identifies the meter during communications 1 to 9999 102
Serial Port Data, parity and stop bits for the port 8O1, 8O2, 8N1, 8N2, 8E1, 8E2 8N1
COM4 Setup
(RS-485)
Protocol Specifies the protocol used on this port None, ION, Modbus RTU, Modbus Master1,
DNP v3.00, DLMS, ModemGate,
GPS: Truetime/Datum, GPS: Arbiter,
GPS: Arbiter-Vorne,Factory, EtherGate
ION
Baud Rate Specifies baud rate during serial communications 300 to 115200 9600
Transmit Delay Specifies the port’s transmit delay setting 0 to 1.00 0.01
Unit ID Identifies the meter during communications 1 to 9999 103
Serial Port Data, parity and stop bits for the port 8O1, 8O2, 8N1, 8N2, 8E1, 8E2 8N1
RS485 Bias Specifies whether or not RS-485 is applied to port ON or OFF OFF
Network
Setup
IP Address Specifies TCP/IP Ethernet address 0.0.0.0 to 255.255.255.2553None4
Mask Specifies Subnet Mask 0.0.0.0 to 255.255.255.255 None
Gateway Specifies Ethernet gateway (if used) 0.0.0.0 to 255.255.255.255 None
SMTP Address Specifies location of SMTP Server 0.0.0.0 to 255.255.255.255 None
MAC Address Machine Access Control address hexadecimal5N/A
Port Enable Specifies if the port is enabled or disabled Webserver, FTP, DNP over TCP, ION over
TCP, Modbus over TCP, Modbus TCP, Telnet TBD
Enabled
Com Ports6
COM1 Specifies whether COM1 (RS-232/RS-485) is enabled or not Enabled
COM2 Specifies whether COM2 (Modem) is enabled or not Enabled, Disabled
COM3 COM3 (Front optical port) is always enabled Enabled Enabled
COM4 Specifies whether COM4 (RS485) is enabled or not Enabled, Disabled
Ethernet Specifies whether the Ethernet port is enabled or not Enabled, Disabled
Undo & Return Select this to cancel the changes made and return to the previous menu
Reboot Select this to reboot the meter
Format Setup
Phase Labels Specifies how phases are labeled 123, ABC, RST, XYZ, RYB, RWB ABC
PF Symbol Specifies what symbol pair is used to indicate power factor CAP/IND (capacitive/inductive),
LD/LG (lead/lag), +/- LD/LG
Digit Group Specifies symbols used to delimit thousands & decimal place
holder 1000.0 or 1,000.0 or 1 000,0 1000.0
Date Format Specifies how dates are displayed YYYY/MM/DD, MM/DD/YYYY, DD/MM/
YYYY MM/DD/YYYY
Show DST Specifies whether or not DST is displayed Do not display DST, Display DST Display DST
Volts Decimal Number of decimal places displayed for voltages 1. to 123456789.XXX 1.XX
Current Decimal Number of decimal places displayed for currents 1. to 123456789.XXX 1.XX
Power Decimal Number of decimal places displayed for power values 1. to 123456789.XXX 1.XX
Display Setup
Update Rate Sets how often the display is updated, in seconds 1s to 6s 1s
Contrast Sets the contrast of the display (higher numbers are sharper) 0 to 9 6
Backlight TO How long the front panel display backlight stays on after the last
button is pressed 0 to 7200 (seconds)7300
DMD Lock TO Minimum time allowed between consecutive demand resets 0 to 5184000 (seconds) 2160000 s (25 days)
Test Mode TO How long the device remains in test mode before reverting to
normal 60 to 21600 (seconds) 1800
Display Scale Scale applied to values before they are displayed 1.00 to 999999.0 1000
Scaling Mode Specifies if values are divided or multiplied by the Display Scale
before being displayed Multiply or Divide Divide
Delta Vectors Specifies how vector diagrams are displayed when in Delta mode System or Instrument Instrument
Security
Modify Passwd Changes the password in basic security80 - 99999999 0
Disable Security Removed password requirement for USER0 (front panel) when
Advanced Security has not be enabled. Enabled, Disabled9Password Enabled
Web Config Allows configuration through web server interface Enabled, Disabled Enabled
1ION8650C (Feature set C) does not support Modbus Master protocol.
2The factory set Unit ID is based on the serial number of the meter. For example: Serial number: XXXX-1009X263-XX is factory set to unit ID 9263.
3After it has been entered, the address 0.0.0.0 is displayed as ‘None’ on the front panel.
4To modify the NONE setting, press and hold the up arrow to enter edit mode.
5MAC address is hard-coded at the factory and is for reference use only.
6Applies only to ION8650C (Feature Set C). See “Switching the active communications ports for ION8650C” on page 31.
7Setting the backlight timeout to 0 results in the backlight always being on.
8This option is only available in basic security. When advanced security is enabled, the NOT AVAILABLE message is displayed on the front panel.
9To disable or enable basic meter security, see “Meter security” on page 30.
Menu Setting Description Range (Values) Default