Installing pressure
switch
➔Mounting position arbitrary, but
preferably with horizontal or verti-
cal diaphragm – with clear view to
scale disk – please make sure that
dirt or humidity does not get into the
connections open for aeration.
Fasten the bottom part of the pressure
switches DL 3 AT, 3 KT by means of
– 4 holes ø 0.106’’ x 0.315’’ (2,8 mm x
8 mm) or ø 0.138’’ x 0.315’’ (3.5 mm
x 8 mm) for self-tapping screws #6
(ø 3.5 mm) or #8 (ø 4.0 mm).
DL 5 KT, 10 KT, 50 KT by means of
– 4 holes ø 0.106’’ x 0.63’’ (2.8 mm x
16 mm) for self-tapping screws #6
(ø 3.5 mm).
DL 5 AT, 10 AT, 50 AT by means of
– 4 holes ø 0.106’’ x 0.315’’ (2.8 mm x
8 mm) or ø 0.138’’ x 0.315’’ (3.5 mm
x 8 mm) for self-tapping screws #6
(ø 3.5 mm) or #8 (ø 4.0 mm).
Installation using a set of tubes
➔The set includes connecting flanges
for the tube connection – 5/32"
(4 x 1 mm) – to the pressure test
points.
Heat up tube ends in hot water be-
fore inserting flange.
➔Put on cable connector for traction
relief – the cable connector cannot
be undone.
Type of gas: air, fumes
➔Connection 2 is sealed with a rub-
ber cap when delivered (DL 3 AT,
DL 5 AT, DL 10 AT, DL 50 AT).
Excess pressure test
Connect excess pressure to con-
nection 1, 1/4 NPT (DL 3 AT, DL 5
AT, DL 10 AT, DL 50 AT) or connec-
tion 2, hose 5/32" (4 x 1 mm) –
➔max. pressure: see label –
➔connection 3 must stay open.
Negative pressure test
Connect negative pressure to con-
nection 3, hose 5/32" (4 x 1 mm) –
➔max. negative pressure: see label –
➔connection 1 (only DL 3 AT, DL 5 AT,
DL 10 AT, DL 50 AT) or 2 must stay
open.
Montage du pressostat
➔La position de montage est quel
-
conque mais, de préférence avec
la membrane horizontale ou ver-
ticale – le disque gradué doit être
bien visible – vérifier qu’il ne pénètre
pas de corps étrangers ni d’humi-
dité dans les raccords qui ont été
ouverts pour l’aération.
Fixation de la partie inférieure des pres-
sostats DL 3 AT, 3 KT à l’aide de
– 4 trous dia 0,106 pouce x
0,315 pouce (2,8 mm x 8 mm) ou
dia 0,138 pouce x 0,315 pouce
(3,5 mm x 8 mm) pour vis autota-
raudeuses #6 (dia 3,5 mm) ou #8
(dia 4,0 mm).
DL 5 KT, 10 KT, 50 KT, à l’aide de
– 4 trous dia 0,106 pouce x 0,63 pouce
(2,8 mm x 16 mm) pour vis autota-
raudeuses #6 (dia 3,5 mm).
DL 5 AT, 10 AT, 50 AT, à l’aide de
– 4 trous dia 0,106 pouce x
0,315 pouce (2,8 mm x 8 mm) ou
dia 0,138 pouce x 0,315 pouce
(3,5 mm x 8 mm) pour vis autota-
raudeuses #6 (dia 3,5 mm) ou #8
(dia 4,0 mm).
Installation à l’aide d’un jeu de
tubes
➔Le jeu comprend des brides de rac-
cordement pour le raccordement du
tuyau – 5/32 pouces (4 x 1 mm) –
sur les prises de pression.
Chauffer les extrémités du tuyau
dans l’eau chaude avant d’insérer
la bride.
➔Mettre en place le connecteur de
câble pour le soulagement de la
traction – le connecteur de câble
ne peut pas être défait.
Type de gaz: air, fumées
➔À la livraison, le raccord 2 est fermé
par un capuchon en caoutchouc
(pour DL 3 AT, DL 5 AT, DL 10 AT,
DL 50 AT).
Test de surpression
Raccorder la surpression au raccord
1, 1/4 NPT (pour DL 3 AT, DL 5 AT,
DL 10 AT, DL 50 AT) ou au raccord
2, tuyau 5/32 pouces (4 x 1 mm) –
➔pression maxi.: voir étiquette –
➔le raccord 3 doit rester ouvert.
Test de pression négative
Raccorder la pression négative au
raccord 3, tuyau 5/32 pouces (4 x
1 mm) –
➔pression négative maxi.: voir éti-
quette –
➔le raccord 1 (seulement pour
DL 3 AT, DL 5 AT, DL 10 AT,
DL 50 AT) ou 2 doit rester ouvert.
Instalación del
presostato
➔Posición de montaje arbitraria, aun-
que preferentemente con diafragma
horizontal o vertical (con el disco de
la escala bien visible). Asegurarse de
que no penetre suciedad o hume-
dad en las conexiones abiertas de
ventilación.
Fijar la parte inferior de los presostatos
DL 3 AT, 3 KT por medio de
– 4 orificios D 2,8 mm x 8 mm (0,106’’
x 0,315’’) o D 3,5 mm x 8 mm
(0,138’’ x 0,315’’) con tornillos au-
torroscantes n° 6 (D 3,5 mm) o n° 8
(D 4,0 mm).
DL 5 KT, 10 KT, 50 KT por medio de
– 4 orificios D 2,8 mm x 16 mm
(0,106’’ x 0,63’’) para tornillos au-
torroscantes n° 6 (D 3,5 mm).
DL 5 AT, 10 AT, 50 AT por medio de
– 4 orificios D 2,8 mm x 8 mm (0,106’’
x 0,315’’) o D 3,5 mm x 8 mm
(0,138’’ x 0,315’’) para tornillos
autorroscantes n° 6 (D 3,5 mm) o
n° 8 (D 4,0 mm).
Instalación de un juego de tubos
➔El juego incluye unas bridas de co-
nexión para los manguitos de cone-
xión de 4 x 1 mm (5/32"), para las
boquillas de medición.
Calentar los extremos del tubo en
un baño María antes de insertar la
brida.
➔Colocar el conector del cable para
descargar la tensión – no se debe
deshacer el conector para cables.
Tipo de gas: aire, humos
➔La conexión 2, al salir de fábrica,
está sellada con una tapa de goma
(para DL 3 AT, DL 5 AT, DL 10 AT,
DL 50 AT).
Ensayo del exceso de presión
➔Conectar la presión excesiva a la co-
nexión 1, 1/4 NPT (DL 3 AT, DL 5 AT,
DL 10 AT, DL 50 AT), o a la conexión
2, manguito 4 x 1 mm (5/32") –
➔presión máx.: ver la etiqueta –
➔la conexión 3 debe permanecer
abierta.
Ensayo de la presión negativa
Conectar la presión negativa a la
conexión 3, manguito 4 x 1 mm
(5/32") –
➔presión negativa máx.: ver la etique-
ta –
➔la conexión 1 (sólo DL 3 AT, DL 5 AT,
DL 10 AT, DL 50 AT) o la 2 debe
quedar abierta.
+
ø 0.106x0.315"
(2.7x8)
ø 0.138x0.315"
(3.5x8)
1.95" (49.5)
1.75" (44.5)
ø 0.217"
(5.5)
ø 0.165"
(4,2)
ø 0.106x0.63
(2,7x16) 2.52" (64)
1.77"
(45)
2.42" (61,5)
2.11" (53,7)
ø 0.217"
(5.5)
1.75"
(44.5)
∅ 0.217"
(5.5)
1,95" (49.5)
∅ 0.138x0.315
(3.5x8)
∅ 0.106x0.315
(2.8x8)
+
-
3
2
DL 3 KT
DL 3 AT, DL 3 KT
DL 5 KT, 10 KT, 50 KT
DL 5 AT, 10 AT, 50 AT