Fantech EPD180CR Installation and Maintenance Manual

Categoría
Deshumidificadores
Tipo
Installation and Maintenance Manual

Este manual también es adecuado para

fantech
Installation and Maintenance Manual
Manual de Instalación y Mantenimiento
Item #: 405037
Rev Date: 2015-06-01
United States
10048 Industrial Blvd., Lenexa, KS, 66215
Tel.: 800.747.1762 • Fax: 800.487.9915
Canada
50 Kanalflakt Way, Bouctouche, NB, E4S 3M5
Tel.: 800.565.3548 • Fax: 877.747.8116
EPD Series
Industrial Dehumidier
Deshumidicador industrial
Industrial Dehumidifier
Déshumidificateur industriel
Deshumidificador industrial
Operating Instructions
Guide d'utilisation
Instrucciones de uso
Read and Save
These
Instructions
Lisez et
conservez ces
instructions
Lea y guarde
estas
instrucciones
1
3
5
405037
Fantech Ltd. 1-800-565-3548
EPD150LR • EPD180CR • EPD190LR • EPD250CR
2
fantech
WARNINGS
Plug into a grounded 3 prong outlet
Do not remove ground prong.
Do not use and adapter.
Do not use an extension cord.
Failure to follow these instructions can result in death, fire, or electrical
shock
WARNING: The dehumidifier uses a high pressure refrigerant system and
high voltage circuitry which could present a health hazard resulting in
death, serious bodily injury, and/or property damage. Only qualified ser-
vice people should service this unit.
CAUTION: Do not operate unit without the front hood secured in place.
The serial data plate is located on the underside of the dehumidifier. For
service information contact 1-800-565-3548.
ADVERTENCIAS
Conecte a un contacto de pared de conexión a tierra de 3 terminales.
No quite la terminal de conexión a tierra.
No use un adaptador.
No use un cable elétrico de extensión.
No seguir estas instrucciones puede ocasional la muerte, incendio o choque
eléctrico.
ADVERTENCIA: El deshumidificador utiliza un sistema de líquido refriger-
ante de alta presión y un circuito eléctrico de alto voltaje que podrían
resultar en daños materiales, peligro para la salud, lesiones corporales
graves, e incluso la muerte. Sólo personal cualificado debe dar servicio a
esta unidad.
PRECAUCIÓN: No utilice la unidad hasta haber asegurado la cubierta fron-
tal en posición cerrada.
La placa serial está situada en el superficie inferior del deshumidificador.
Consulte con el número 1-800-565-3548 para másinformación sobre
servicio.
Note Warning/
Important
note
Information Technical
information
Practical tip
3
fantech
Industrial Dehumidifier
Electrical Requirements
For 115V operation, a common grounded outlet on a 15 amp circuit is required. If used in a wet area, a ground fault interrupter (GFI) is required.
Built in Electrical Safety
For your safety and protection this appliance is manufactured with a grounded plug on its power cord. The power cord must be plugged into a properly
grounded receptacle. If a grounded receptacle does not exist, have one installed by a certified electrician. Do not cut or remove the grounding prong
on the power cord plug if equipped. We recommend that this electrical circuit/receptacle operate under a separate breaker or fuse.
If an extension cord is required, it must have a minimum of 14 gauge conductors if 25 feet long or less and 12 gauge conductors if greater than 25
feet long.
Limitations of Use
Temperature: 4°C to 35°C (40°F to 95°F)
Relative Humidity: 20 to 80%
Water Removal
The dehumidifier is equipped with an internal condensate pump to remove the water that is collected from the air. This allows the water to be pumped
20 feet with the attached hose. If the water needs to be pumped more than 20 feet above the unit, a second pump must be added to relay the water.
The condensate pump automatically purges for 20 seconds every four minutes.
Figure 1
Built in Electrical Safety
For your safety and protection this appliance is manufactured
with a grounded plug on its power cord. The power cord must
be plugged into a properly grounded receptacle. If a ground-
ed receptacle does not exist, have one installed by a certified
electrician. Do not cut or remove the grounding prong on the
power cord plug if equipped. We recommend that this electri-
cal circuit/receptacle operate under a separate breaker or
fuse.
If an extension cord is required, it must have a minimum of
14 gauge conductors if 25 feet long or less and 12 gauge
conductors if greater than 25 feet long.
Electrical Requirements
For 115V operation, a common grounded outlet on a 15 amp
circuit is required. The dehumidifier draws approx. 8 amps at
80°F, 60% RH. If used in a wet area, a ground fault inter-
rupter (GFI) is required.
Power Button (Fig. 1)
The dehumidifier is turned on or off by
pressing the power button. When the
dehumidifier is started, the hour meter will
display the cumulative hours.
Pump Purge Button (Fig. 2)
In normal operation, the pump will automat-
ically empty the reservoir. Pressing this but-
ton allows manual emptying of the reservoir.
Press once, and the pump will operate for
20 seconds. Press and hold the button and
the pump will activate for 30 seconds.
Always manually purge the water reservoir
before transport or storage. Turn off the
power and allow the plugged in dehumidifier
to rest 5 minutes before the final purge.
Electrical Shock Hazard
Plug into a grounded 3 prong outlet.
Do not remove ground prong.
Do not use an adapter.
Do not use an extension cord.
Failure to follow these instructions can result in death,
fire, or electrical shock.
WARNING
Place dehumidifier inside area to be dried. Make sure all win-
dows and doors are closed to the outside and seal off the wet
area from any unaffected areas. Route condensate hose into
a drain, or a very large container. Press the On/Off button
(Fig. 1) to activate the dehumidifier.
OPERATION
Fig. 1
Fig. 2
Digital Hour Counter (Fig. 3)
The counter will accumulate and display the total running hours
of the unit in 1/10 of an hour.
Hour Button (Fig. 4)
Press the HOURS button when the dehu-
midifier cannot be plugged in and the hour
meter needs to be read. The digital hour
meter will display the last saved cumulative
time for ten seconds.
Defrost Indicator (Fig. 5)
The defrost indicator will light to indicate the
dehumidifier is in defrost cycle. During this
period, the compressor is not running.
Defrost Cycle
When ice builds up on the coils, a thermistor activates the elec-
tronic control and defrost light. The compressor is turned off by
the thermistor temperature measurement. The blower will contin-
ue to run, causing air to flow through the evaporator coil and melt
the ice. When the ice is melted, the thermistor will end the defrost
cycle and the compressor will be started.
Disconnect dehumidifier from power supply. The hour meter uses
a battery backup for display when the dehumidifier is unplugged
and the hour button is depressed. To change the battery, it is nec-
essary to remove the four (4) screws from the control panel.
Disconnect the old battery and replace with new battery. Replace
control panel and screws. Do not overtighten screws.
Water Removal
The dehumidifier is equipped with an internal condensate pump
to remove the water that is collected from the air. This allows the
water to be pumped 20 feet with the attached hose. If the water
needs to be pumped more than 20 feet above the unit, a second
pump must be added to relay the water. The condensate pump
automatically purges for 20 seconds every four minutes.
Fig. 3
Fig. 4
Fig. 5
Electrical Shock Hazard
Plug into a grounded 3 prong outlet.
Do not remove ground prong.
Do not use an adapter.
WARNING
Disconnect power supply before replacing battery.
Failure to follow these instructions can result in death,
fire, or electrical shock.
Battery Replacement
(1)
Place dehumidifier inside area to be dried. Make sure all windows and doors are closed to the
outside and seal off the wet area from any unaffected areas. Route condensate hose into a drain, or
a very large container. Press the On/Off button (figure 1) to activate the dehumidifier.
Start-up Mode
The dehumidifier is turned on or off by pressing the power button (figure 1). When the dehumidifier
is started, the hour meter will briefly display the software version #, followed by the cumulative
hours.
Pressing the power button during the first minute, the unit will go into OFF Mode immediately.
Run Mode
During Run Mode the compressor is running causing the evaporator to get cold resulting in
condensate forming on the coil.
The unit will stay in run mode for variable length of time depending on the ambient conditions.
Pressing the power button (figure 1) will send the unit in shut down mode (see below)
Defrost Mode
During the defrost mode, the indicator light will turn on (figure 2), the compressor will be off and the fan
will continue to run. The pump purge will be activated automatically.
The defrost cycle runs every 45 minutes in cool ambient temperature, less often in warm ambient
temperature and the length of time in defrost will vary appropriately.
Heavy frosting on the coil can be expected during low ambient conditions and will not affect the
operation of the unit.
Built in Electrical Safety
For your safety and protection this appliance is manufactured
with a grounded plug on its power cord. The power cord must
be plugged into a properly grounded receptacle. If a ground-
ed receptacle does not exist, have one installed by a certified
electrician. Do not cut or remove the grounding prong on the
power cord plug if equipped. We recommend that this electri-
cal circuit/receptacle operate under a separate breaker or
fuse.
If an extension cord is required, it must have a minimum of
14 gauge conductors if 25 feet long or less and 12 gauge
conductors if greater than 25 feet long.
Electrical Requirements
For 115V operation, a common grounded outlet on a 15 amp
circuit is required. The dehumidifier draws approx. 8 amps at
80°F, 60% RH. If used in a wet area, a ground fault inter-
rupter (GFI) is required.
Power Button (Fig. 1)
The dehumidifier is turned on or off by
pressing the power button. When the
dehumidifier is started, the hour meter will
display the cumulative hours.
Pump Purge Button (Fig. 2)
In normal operation, the pump will automat-
ically empty the reservoir. Pressing this but-
ton allows manual emptying of the reservoir.
Press once, and the pump will operate for
20 seconds. Press and hold the button and
the pump will activate for 30 seconds.
Always manually purge the water reservoir
before transport or storage. Turn off the
power and allow the plugged in dehumidifier
to rest 5 minutes before the final purge.
Electrical Shock Hazard
Plug into a grounded 3 prong outlet.
Do not remove ground prong.
Do not use an adapter.
Do not use an extension cord.
Failure to follow these instructions can result in death,
fire, or electrical shock.
WARNING
Place dehumidifier inside area to be dried. Make sure all win-
dows and doors are closed to the outside and seal off the wet
area from any unaffected areas. Route condensate hose into
a drain, or a very large container. Press the On/Off button
(Fig. 1) to activate the dehumidifier.
OPERATION
Fig. 1
Fig. 2
Digital Hour Counter (Fig. 3)
The counter will accumulate and display the total running hours
of the unit in 1/10 of an hour.
Hour Button (Fig. 4)
Press the HOURS button when the dehu-
midifier cannot be plugged in and the hour
meter needs to be read. The digital hour
meter will display the last saved cumulative
time for ten seconds.
Defrost Indicator (Fig. 5)
The defrost indicator will light to indicate the
dehumidifier is in defrost cycle. During this
period, the compressor is not running.
Defrost Cycle
When ice builds up on the coils, a thermistor activates the elec-
tronic control and defrost light. The compressor is turned off by
the thermistor temperature measurement. The blower will contin-
ue to run, causing air to flow through the evaporator coil and melt
the ice. When the ice is melted, the thermistor will end the defrost
cycle and the compressor will be started.
Disconnect dehumidifier from power supply. The hour meter uses
a battery backup for display when the dehumidifier is unplugged
and the hour button is depressed. To change the battery, it is nec-
essary to remove the four (4) screws from the control panel.
Disconnect the old battery and replace with new battery. Replace
control panel and screws. Do not overtighten screws.
Water Removal
The dehumidifier is equipped with an internal condensate pump
to remove the water that is collected from the air. This allows the
water to be pumped 20 feet with the attached hose. If the water
needs to be pumped more than 20 feet above the unit, a second
pump must be added to relay the water. The condensate pump
automatically purges for 20 seconds every four minutes.
Fig. 3
Fig. 4
Fig. 5
Electrical Shock Hazard
Plug into a grounded 3 prong outlet.
Do not remove ground prong.
Do not use an adapter.
WARNING
Disconnect power supply before replacing battery.
Failure to follow these instructions can result in death,
fire, or electrical shock.
Battery Replacement
(1)
Figure 2
Operation
4
fantech
Shut Down Mode
Pressing the power button after the first minute of operation will initiate a shut-down mode. This mode
will last 15 minutes and will maintain the operation of the fan and purge pump to insure all water is
removed from the unit prior to moving or storing. Pressing the power button at any time during the shut
down mode will immediately shut down the unit and bypass the remainder of the shutdown mode. The
unit must be purged by pressing the purge button if bypassing the shutdown mode to avoid water
overflow.
The display will change during shutdown mode to a countdown timer that will indicate the
time remaining before the unit shuts completely off.
Maintenance
Air Filter (Fig. 7)
The air filter should be checked regularly. Operating the dehu-
midifier with a clogged filter will reduce efficiency. The filter can be
vacuum cleaned to remove dust. To access the filter media, slide
the filter frame up until it clears the dehumidifier cabinet. Remove
the filter media from behind the frame and vacuum. Reverse pro-
cedure to re-install the filter and frame into the dehumidifier.
Storage
Freezing temperatures and biological growth must be considered
before storing the dehumidifier. The dehumidifier should be
flushed with a biofungicide before storing. When storing the unit,
ensure that water has been removed from the reservoir and
hose. This will prevent damage caused by freezing temperatures
and to prevent biological growth. Use the pump purge button to
remove water and biofungicide chemicals from the dehumidifier.
Stacking (Fig.9)
The dehumidifiers can be stacked on top of each other. The
wheels from the upper unit must be resting in the cradle of
the lower unit. DO NOT STACK MORE THAN TWO HIGH.
External Cleaning
Use a non-flammable mild, non-abrasive soap and clean
water solution to clean the dehumidifier. Wipe dry.
Internal Cleaning
Disconnect dehumidifier from power supply.
Light cleaning: Remove the air filter and spray evaporator
coil with water.Remove the two upper screws from the front
hood.
Heavy cleaning: Remove two upper screws from front hood.
Open hood. Spray water at coils. Close hood and replace
screws. (Fig. 8)
Fig. 7
Fig. 8
Electrical Shock Hazard
Plug into a grounded 3 prong outlet.
Do not remove ground prong.
Do not use an adapter.
WARNING
Disconnect power supply before cleaning.
Failure to follow these instructions can result in death,
fire, or electrical shock.
Venting / Ducting (Fig. 6)
Twin rear outlets can accommo-
date two individual 5” ducts or one
10” lay flat duct to be attached.
This allows for warm dry air to be
directed into different areas.
Fig. 6
Cleaning
Fig. 9
Service
A qualified refrigeration technician must service all refriger-
ant leaks.
WARNING: The dehumidifier uses a high pressure refrigerant
system and high voltage circuitry which could present a health
hazard resulting in death, serious bodily injury, and/or property
damage. Only qualified service people should service this unit.
CAUTION: Do not operate unit without the front hood secured in
place.
The serial data plate is located on the underside of the dehumid-
ifier. For service information contact 1-800-565-3548.
(2)
Figure 5
Figure 6
Functions
Loss of Power Recovery Function
In case of a loss of power, the last run state (ON or OFF) will be maintained when the power is
restored.
Pump Purge Function
In normal operation, the pump will automatically empty the reservoir. Pressing the purge button
(figure 3) runs the pump for 1 minute allowing manual emptying of the reservoir. The pump purge
will function in all modes as long as the unit is plugged in.
Hour Meter Display
The cumulative hours will be displayed during normal operation. If the unit is off (even unplugged)
pressing the hour button (figure 4) will also display the accumulative hours briefly.
Venting / Ducting
Twin rear outlets (figure 5) can accommodate two individual 5” ducts or one 10” lay flat duct to be
attached. This allows for warm dry air to be directed into different areas.
Maintenance
Air Filter
The air filter should be checked regularly. Operating the dehumidifier with a clogged filter will reduce
efficiency. To access the filter, slide the filter frame up until it clears the dehumidifier cabinet
(figure 6). Reverse procedure to re-install the filter into the dehumidifier. Metal filters should be
washed with soap and water, and paper filters should be replaced.
Paper filter size is a nominal 12" x 12" x 1"
Operating the unit without the filter in place will cause reduced efficiency due to dirty coils and
increase the frequency of internal coil cleaning.
Stacking
The dehumidifiers can be stacked on top of each other (figure 7). The wheels from the upper unit
must be resting in the cradle of the lower unit. DO NOT STACK MORE THAN TWO HIGH.
Battery Replacement
Disconnect power supply before replacing battery.
Failure to follow these instructions can result in death, fire, or electrical shock
Disconnect dehumidifier from power supply. The hour meter uses a battery backup for display when the
dehumidifier is unplugged and the hour button is depressed. To change the battery, it is necessary to remove
the four (4) screws from the control panel. Disconnect the old battery and replace with new battery.
Replace control panel and screws. Do not overtighten screws.
Built in Electrical Safety
For your safety and protection this appliance is manufactured
with a grounded plug on its power cord. The power cord must
be plugged into a properly grounded receptacle. If a ground-
ed receptacle does not exist, have one installed by a certified
electrician. Do not cut or remove the grounding prong on the
power cord plug if equipped. We recommend that this electri-
cal circuit/receptacle operate under a separate breaker or
fuse.
If an extension cord is required, it must have a minimum of
14 gauge conductors if 25 feet long or less and 12 gauge
conductors if greater than 25 feet long.
Electrical Requirements
For 115V operation, a common grounded outlet on a 15 amp
circuit is required. The dehumidifier draws approx. 8 amps at
80°F, 60% RH. If used in a wet area, a ground fault inter-
rupter (GFI) is required.
Power Button (Fig. 1)
The dehumidifier is turned on or off by
pressing the power button. When the
dehumidifier is started, the hour meter will
display the cumulative hours.
Pump Purge Button (Fig. 2)
In normal operation, the pump will automat-
ically empty the reservoir. Pressing this but-
ton allows manual emptying of the reservoir.
Press once, and the pump will operate for
20 seconds. Press and hold the button and
the pump will activate for 30 seconds.
Always manually purge the water reservoir
before transport or storage. Turn off the
power and allow the plugged in dehumidifier
to rest 5 minutes before the final purge.
Electrical Shock Hazard
Plug into a grounded 3 prong outlet.
Do not remove ground prong.
Do not use an adapter.
Do not use an extension cord.
Failure to follow these instructions can result in death,
fire, or electrical shock.
WARNING
Place dehumidifier inside area to be dried. Make sure all win-
dows and doors are closed to the outside and seal off the wet
area from any unaffected areas. Route condensate hose into
a drain, or a very large container. Press the On/Off button
(Fig. 1) to activate the dehumidifier.
OPERATION
Fig. 1
Fig. 2
Digital Hour Counter (Fig. 3)
The counter will accumulate and display the total running hours
of the unit in 1/10 of an hour.
Hour Button (Fig. 4)
Press the HOURS button when the dehu-
midifier cannot be plugged in and the hour
meter needs to be read. The digital hour
meter will display the last saved cumulative
time for ten seconds.
Defrost Indicator (Fig. 5)
The defrost indicator will light to indicate the
dehumidifier is in defrost cycle. During this
period, the compressor is not running.
Defrost Cycle
When ice builds up on the coils, a thermistor activates the elec-
tronic control and defrost light. The compressor is turned off by
the thermistor temperature measurement. The blower will contin-
ue to run, causing air to flow through the evaporator coil and melt
the ice. When the ice is melted, the thermistor will end the defrost
cycle and the compressor will be started.
Disconnect dehumidifier from power supply. The hour meter uses
a battery backup for display when the dehumidifier is unplugged
and the hour button is depressed. To change the battery, it is nec-
essary to remove the four (4) screws from the control panel.
Disconnect the old battery and replace with new battery. Replace
control panel and screws. Do not overtighten screws.
Water Removal
The dehumidifier is equipped with an internal condensate pump
to remove the water that is collected from the air. This allows the
water to be pumped 20 feet with the attached hose. If the water
needs to be pumped more than 20 feet above the unit, a second
pump must be added to relay the water. The condensate pump
automatically purges for 20 seconds every four minutes.
Fig. 3
Fig. 4
Fig. 5
Electrical Shock Hazard
Plug into a grounded 3 prong outlet.
Do not remove ground prong.
Do not use an adapter.
WARNING
Disconnect power supply before replacing battery.
Failure to follow these instructions can result in death,
fire, or electrical shock.
Battery Replacement
(1)
Figure 3
Figure 4
Maintenance
Air Filter (Fig. 7)
The air filter should be checked regularly. Operating the dehu-
midifier with a clogged filter will reduce efficiency. The filter can be
vacuum cleaned to remove dust. To access the filter media, slide
the filter frame up until it clears the dehumidifier cabinet. Remove
the filter media from behind the frame and vacuum. Reverse pro-
cedure to re-install the filter and frame into the dehumidifier.
Storage
Freezing temperatures and biological growth must be considered
before storing the dehumidifier. The dehumidifier should be
flushed with a biofungicide before storing. When storing the unit,
ensure that water has been removed from the reservoir and
hose. This will prevent damage caused by freezing temperatures
and to prevent biological growth. Use the pump purge button to
remove water and biofungicide chemicals from the dehumidifier.
Stacking (Fig.9)
The dehumidifiers can be stacked on top of each other. The
wheels from the upper unit must be resting in the cradle of
the lower unit. DO NOT STACK MORE THAN TWO HIGH.
External Cleaning
Use a non-flammable mild, non-abrasive soap and clean
water solution to clean the dehumidifier. Wipe dry.
Internal Cleaning
Disconnect dehumidifier from power supply.
Light cleaning: Remove the air filter and spray evaporator
coil with water.Remove the two upper screws from the front
hood.
Heavy cleaning: Remove two upper screws from front hood.
Open hood. Spray water at coils. Close hood and replace
screws. (Fig. 8)
Fig. 7
Fig. 8
Electrical Shock Hazard
Plug into a grounded 3 prong outlet.
Do not remove ground prong.
Do not use an adapter.
WARNING
Disconnect power supply before cleaning.
Failure to follow these instructions can result in death,
fire, or electrical shock.
Venting / Ducting (Fig. 6)
Twin rear outlets can accommo-
date two individual 5” ducts or one
10” lay flat duct to be attached.
This allows for warm dry air to be
directed into different areas.
Fig. 6
Cleaning
Fig. 9
Service
A qualified refrigeration technician must service all refriger-
ant leaks.
WARNING: The dehumidifier uses a high pressure refrigerant
system and high voltage circuitry which could present a health
hazard resulting in death, serious bodily injury, and/or property
damage. Only qualified service people should service this unit.
CAUTION: Do not operate unit without the front hood secured in
place.
The serial data plate is located on the underside of the dehumid-
ifier. For service information contact 1-800-565-3548.
(2)
Figure 7
5
fantech
Maintenance
Air Filter (Fig. 7)
The air filter should be checked regularly. Operating the dehu-
midifier with a clogged filter will reduce efficiency. The filter can be
vacuum cleaned to remove dust. To access the filter media, slide
the filter frame up until it clears the dehumidifier cabinet. Remove
the filter media from behind the frame and vacuum. Reverse pro-
cedure to re-install the filter and frame into the dehumidifier.
Storage
Freezing temperatures and biological growth must be considered
before storing the dehumidifier. The dehumidifier should be
flushed with a biofungicide before storing. When storing the unit,
ensure that water has been removed from the reservoir and
hose. This will prevent damage caused by freezing temperatures
and to prevent biological growth. Use the pump purge button to
remove water and biofungicide chemicals from the dehumidifier.
Stacking (Fig.9)
The dehumidifiers can be stacked on top of each other. The
wheels from the upper unit must be resting in the cradle of
the lower unit. DO NOT STACK MORE THAN TWO HIGH.
External Cleaning
Use a non-flammable mild, non-abrasive soap and clean
water solution to clean the dehumidifier. Wipe dry.
Internal Cleaning
Disconnect dehumidifier from power supply.
Light cleaning: Remove the air filter and spray evaporator
coil with water.Remove the two upper screws from the front
hood.
Heavy cleaning: Remove two upper screws from front hood.
Open hood. Spray water at coils. Close hood and replace
screws. (Fig. 8)
Fig. 7
Fig. 8
Electrical Shock Hazard
Plug into a grounded 3 prong outlet.
Do not remove ground prong.
Do not use an adapter.
WARNING
Disconnect power supply before cleaning.
Failure to follow these instructions can result in death,
fire, or electrical shock.
Venting / Ducting (Fig. 6)
Twin rear outlets can accommo-
date two individual 5” ducts or one
10” lay flat duct to be attached.
This allows for warm dry air to be
directed into different areas.
Fig. 6
Cleaning
Fig. 9
Service
A qualified refrigeration technician must service all refriger-
ant leaks.
WARNING: The dehumidifier uses a high pressure refrigerant
system and high voltage circuitry which could present a health
hazard resulting in death, serious bodily injury, and/or property
damage. Only qualified service people should service this unit.
CAUTION: Do not operate unit without the front hood secured in
place.
The serial data plate is located on the underside of the dehumid-
ifier. For service information contact 1-800-565-3548.
(2)
Figure 8
Troubleshooting
Service
A qualified refrigeration technician must service all refrigerant leaks.
The Unit is NOT working:
Has the breaker tripped? – Reset breaker
If in a wet area, is the unit plugged into a GFI protected circuit? – Excessive
moisture will trip GFI. Remove from area.
Is the unit being run off a generator? - Check output does not fluctuate
as the unit will not operate at low voltage.
If using an extension cord - Is the cord of the correct gauge for the
distance run? (14 AWG up to 25’ and 12 AWG over 25’). Note: Verify
voltage while unit is starting. Start up will cause the highest current draw
and largest voltage drop. Even if plugged directly to outlet there can be
a significant voltage drop. Never assume the voltage is ok without
verifying.
The unit shuts down and displays an error code.
ER 1: Overflow switch remaining closed for >2 minutes.
Plugged or kinked drain hose – Remove obstruction
Bad connection in pump circuit – Check connections
Defective condensate pump – Replace
ER 2: Internal pressure switch indicates refrigerant pressure is too high.
Air filter is dirty or plugged – Clean or replace air filter
The coil is dirty – Clean the coil
Loose or faulty electrical connections to pressure switch – check
connections
Fan is not working – Replace
Defective pressure switch – replace
The unit continually ices up: Note that some ice buildup on the evaporator coil
is normal but airflow should not be blocked.
Is warm air blowing out the back of the unit? - No warm air, ambient
temperature may be too low. Raise temperature with supplementary
source.
Is the air filter clean and airflow unobstructed? – Clean filter. Unit should
have a minimum of 10” clearance all around it.
Dirty evaporator coil? – Clean coil.
Unit moves some water but not as much as expected:
Air filter dirty or airflow obstructed - Unit should have a minimum of 10”
clearance all around it. Clean air filter and ensure adequate airflow/space
around unit.
Evaporator coil dirty – Clean coil.
Restrictive or kinked exhaust ducting (if used) – Straighten out ducting.
Fan does not run. Compressor runs briefly but cycles on/off:
Loose connection in fan circuit – Check connections.
Fan obstructed and not turning – Remove obstruction.
Defective fan – Replace fan.
Defective control board – Replace control board.
Cleaning
Disconnect power supply before cleaning
Failure to follow these instructions can result in death, fire, or electrical shock
External Cleaning
Use a non-flammable mild, non-abrasive soap and water solution. Wipe dry.
Internal Cleaning
Disconnect dehumidifier from power supply.
Light cleaning: Remove the air filter and spray evaporator coil with water.
Heavy cleaning: Remove two upper screws from front hood. Open hood. Spray water at coils. Close
hood and replace screws. (figure 8)
Care must be taken to insure coil fins are not damaged, as damaged fins can restrict airflow
and reduce the unit's ability to produce water.
Storage
Freezing temperatures and biological growth must be considered before storing the dehumidifier. To
prevent the biological growth, spray an evaporator cleaner on the coils and rinse into the drainage
system. You must also purge the excess liquid from the pump using the manual purge function to
prevent issues with freezing storage environments.
6
fantech
Wiring Diagram
GREEN & YELLOW
G
N
L1
ELECTRONIC CONTROL BOARD
E2
E3
E1
E5
E4
J1 J3
COMPRESSOR
O/L
C
R
S
CONDENSATE PUMP
CAPACITOR
BLOWER
14uF
BLOWER
WHITE
THERMISTOR FLOAT
CAPACITOR
COMPRESSOR
60uF
BLUE
BROWN
BLACK
BROWN
WHITE
2-78119-001 REV. 01
WHITE
BLACK
BLUE
BLUE
WHITE
BLACK
WHITE
BROWN
BLACK
RED
WHITE
WHITE
J2
SWITCH
PRESSURE
7
fantech
Deshumidificador industrial
Requisitos eléctricos
Para operar el deshumidificador a 115V, es preciso el uso de un enchufe normal con toma de tierra y circuito de 15 amp. Es preciso utilizar un
interruptor ade escape a tierra si la unidad se va utilizar en un área especialmente húmeda.
Sistema integrado de seguridad eléctrica
Para proporcionarle mayor seguridad, este electrodoméstico está fabricado con una clavija con toma a tierra incluida en el cable de toma de corriente.
El cable debe enchufarse a un receptáculo de corriente adecuado y con toma a tierra. Un electricista acreditado deberá instalar un enchufe con toma
de tierra si no dispone de uno. No corte ni elimine la patilla de toma a tierra de la clavija si ésta viniera incluida en el equipo. Le recomendamos que el
circuito eléctrico o enchufe opere bajo un cortacircuitos o fusible aparte.
En caso de que necesite un cable de extensión, el cable deberá contar con conductores de calibre mínimo de 14 gauge si es de 25 pies o más corto,
y de calibre 12 gauge si es más largo de 25 pies (sección de 3.31 y 2.08 milímetros cuadrados respectivamente).
Limitación de la utilizació
Temperatura: 4°C a 35°C (40°F a 95°F)
Humeda relativa: 20 a 80%
Extracción de agua
El deshumidificador incluye una bomba interna de condensación que elimina el agua sustraída del aire. Este sistema permite evacuar el agua hasta a
20 pies de distancia utilizando la manguera incluida. En caso de que necesite evacuar el agua a una distancia mayor a 20 pies, deberá instalar otra
bomba capaz de evacuar el agua a partir de este punto. La bomba de condensación evacua el agua de manera automática cada cuatro minutos y durante
20 segundos.
Figura 1
Built in Electrical Safety
For your safety and protection this appliance is manufactured
with a grounded plug on its power cord. The power cord must
be plugged into a properly grounded receptacle. If a ground-
ed receptacle does not exist, have one installed by a certified
electrician. Do not cut or remove the grounding prong on the
power cord plug if equipped. We recommend that this electri-
cal circuit/receptacle operate under a separate breaker or
fuse.
If an extension cord is required, it must have a minimum of
14 gauge conductors if 25 feet long or less and 12 gauge
conductors if greater than 25 feet long.
Electrical Requirements
For 115V operation, a common grounded outlet on a 15 amp
circuit is required. The dehumidifier draws approx. 8 amps at
80°F, 60% RH. If used in a wet area, a ground fault inter-
rupter (GFI) is required.
Power Button (Fig. 1)
The dehumidifier is turned on or off by
pressing the power button. When the
dehumidifier is started, the hour meter will
display the cumulative hours.
Pump Purge Button (Fig. 2)
In normal operation, the pump will automat-
ically empty the reservoir. Pressing this but-
ton allows manual emptying of the reservoir.
Press once, and the pump will operate for
20 seconds. Press and hold the button and
the pump will activate for 30 seconds.
Always manually purge the water reservoir
before transport or storage. Turn off the
power and allow the plugged in dehumidifier
to rest 5 minutes before the final purge.
Electrical Shock Hazard
Plug into a grounded 3 prong outlet.
Do not remove ground prong.
Do not use an adapter.
Do not use an extension cord.
Failure to follow these instructions can result in death,
fire, or electrical shock.
WARNING
Place dehumidifier inside area to be dried. Make sure all win-
dows and doors are closed to the outside and seal off the wet
area from any unaffected areas. Route condensate hose into
a drain, or a very large container. Press the On/Off button
(Fig. 1) to activate the dehumidifier.
OPERATION
Fig. 1
Fig. 2
Digital Hour Counter (Fig. 3)
The counter will accumulate and display the total running hours
of the unit in 1/10 of an hour.
Hour Button (Fig. 4)
Press the HOURS button when the dehu-
midifier cannot be plugged in and the hour
meter needs to be read. The digital hour
meter will display the last saved cumulative
time for ten seconds.
Defrost Indicator (Fig. 5)
The defrost indicator will light to indicate the
dehumidifier is in defrost cycle. During this
period, the compressor is not running.
Defrost Cycle
When ice builds up on the coils, a thermistor activates the elec-
tronic control and defrost light. The compressor is turned off by
the thermistor temperature measurement. The blower will contin-
ue to run, causing air to flow through the evaporator coil and melt
the ice. When the ice is melted, the thermistor will end the defrost
cycle and the compressor will be started.
Disconnect dehumidifier from power supply. The hour meter uses
a battery backup for display when the dehumidifier is unplugged
and the hour button is depressed. To change the battery, it is nec-
essary to remove the four (4) screws from the control panel.
Disconnect the old battery and replace with new battery. Replace
control panel and screws. Do not overtighten screws.
Water Removal
The dehumidifier is equipped with an internal condensate pump
to remove the water that is collected from the air. This allows the
water to be pumped 20 feet with the attached hose. If the water
needs to be pumped more than 20 feet above the unit, a second
pump must be added to relay the water. The condensate pump
automatically purges for 20 seconds every four minutes.
Fig. 3
Fig. 4
Fig. 5
Electrical Shock Hazard
Plug into a grounded 3 prong outlet.
Do not remove ground prong.
Do not use an adapter.
WARNING
Disconnect power supply before replacing battery.
Failure to follow these instructions can result in death,
fire, or electrical shock.
Battery Replacement
(1)
Coloque el deshumidificador en el área en la que quiera reducir la humedad. Compruebe que las puertas
y ventanas están cerradas al exterior, y aísle la zona húmeda de cualquier otra zona no afectada.
Introduzca la manguera de condensación en un desagüe o en un contenedor de grandes dimensiones.
Presione el interruptor On/Off para activar el deshumidificador. (figura. 1)
Modo de arranque
Puede prender o apagar el deshumidificador apretando el botón de corriente. (figura 1). Cuando se inicie
el deshumidificador, el contador de horas mostrará brevemente el número de versión de software,
seguido de las horas acumuladas.
Si se pulsa el botón de encendido durante el primer minuto, la unidad entrará en modo apagado
inmediatamente.
Modo de funcionamiento
Durante el modo de funcionamiento el compresor está funcionando, lo que hace que se enfríe el
evaporador dando como resultado la formación de condensación en la bobina.
La unidad permanecerá en modo de funcionamiento durante una cantidad variable de tiempo dependiendo
de las condiciones ambientales.
Si se pulsa el botón de encendido (figura 1) se enviará la unidad a modo de apagado (ver a continuación)
Modo de descongelamiento
Durante el modo descongelamiento, el indicador luminoso se encenderá (figura 2), el compresor estará
apagado y el ventilador seguirá funcionando. La purga de la bomba se activará automáticamente.
El ciclo de descongelamiento se ejecuta cada 45 minutos a temperatura ambiente fría, menos seguido
a temperatura ambiente cálida y la cantidad de tiempo en descongelamiento variará según
corresponda
Debe esperarse un congelamiento intenso en la bobina durante condiciones ambientales bajas pero
esto no afectará el funcionamiento de la unidad.
Built in Electrical Safety
For your safety and protection this appliance is manufactured
with a grounded plug on its power cord. The power cord must
be plugged into a properly grounded receptacle. If a ground-
ed receptacle does not exist, have one installed by a certified
electrician. Do not cut or remove the grounding prong on the
power cord plug if equipped. We recommend that this electri-
cal circuit/receptacle operate under a separate breaker or
fuse.
If an extension cord is required, it must have a minimum of
14 gauge conductors if 25 feet long or less and 12 gauge
conductors if greater than 25 feet long.
Electrical Requirements
For 115V operation, a common grounded outlet on a 15 amp
circuit is required. The dehumidifier draws approx. 8 amps at
80°F, 60% RH. If used in a wet area, a ground fault inter-
rupter (GFI) is required.
Power Button (Fig. 1)
The dehumidifier is turned on or off by
pressing the power button. When the
dehumidifier is started, the hour meter will
display the cumulative hours.
Pump Purge Button (Fig. 2)
In normal operation, the pump will automat-
ically empty the reservoir. Pressing this but-
ton allows manual emptying of the reservoir.
Press once, and the pump will operate for
20 seconds. Press and hold the button and
the pump will activate for 30 seconds.
Always manually purge the water reservoir
before transport or storage. Turn off the
power and allow the plugged in dehumidifier
to rest 5 minutes before the final purge.
Electrical Shock Hazard
Plug into a grounded 3 prong outlet.
Do not remove ground prong.
Do not use an adapter.
Do not use an extension cord.
Failure to follow these instructions can result in death,
fire, or electrical shock.
WARNING
Place dehumidifier inside area to be dried. Make sure all win-
dows and doors are closed to the outside and seal off the wet
area from any unaffected areas. Route condensate hose into
a drain, or a very large container. Press the On/Off button
(Fig. 1) to activate the dehumidifier.
OPERATION
Fig. 1
Fig. 2
Digital Hour Counter (Fig. 3)
The counter will accumulate and display the total running hours
of the unit in 1/10 of an hour.
Hour Button (Fig. 4)
Press the HOURS button when the dehu-
midifier cannot be plugged in and the hour
meter needs to be read. The digital hour
meter will display the last saved cumulative
time for ten seconds.
Defrost Indicator (Fig. 5)
The defrost indicator will light to indicate the
dehumidifier is in defrost cycle. During this
period, the compressor is not running.
Defrost Cycle
When ice builds up on the coils, a thermistor activates the elec-
tronic control and defrost light. The compressor is turned off by
the thermistor temperature measurement. The blower will contin-
ue to run, causing air to flow through the evaporator coil and melt
the ice. When the ice is melted, the thermistor will end the defrost
cycle and the compressor will be started.
Disconnect dehumidifier from power supply. The hour meter uses
a battery backup for display when the dehumidifier is unplugged
and the hour button is depressed. To change the battery, it is nec-
essary to remove the four (4) screws from the control panel.
Disconnect the old battery and replace with new battery. Replace
control panel and screws. Do not overtighten screws.
Water Removal
The dehumidifier is equipped with an internal condensate pump
to remove the water that is collected from the air. This allows the
water to be pumped 20 feet with the attached hose. If the water
needs to be pumped more than 20 feet above the unit, a second
pump must be added to relay the water. The condensate pump
automatically purges for 20 seconds every four minutes.
Fig. 3
Fig. 4
Fig. 5
Electrical Shock Hazard
Plug into a grounded 3 prong outlet.
Do not remove ground prong.
Do not use an adapter.
WARNING
Disconnect power supply before replacing battery.
Failure to follow these instructions can result in death,
fire, or electrical shock.
Battery Replacement
(1)
Figura 2
Funcionamiento
8
fantech
Modo de apagado
Si pulsa el botón de encendido luego del primer minuto de funcionamiento, iniciará el modo de apagado. Este
modo durará 15 minutos y mantendrá el funcionamiento del ventilador y la bomba de purga para asegurar
que se elimine toda el agua de la unidad antes de moverla o almacenarla. Si se pulsa el botón de encendido
en cualquier momento durante el modo de apagado, la unidad se apagará inmediatamente salteando el resto
del modo de apagado. La unidad debe purgarse pulsando el botón de purga si se saltea el modo de apagado
para evitar el desborde de agua.
La pantalla se transformará en una cuenta regresiva durante el modo de apagado que
indicará el tiempo restante antes de que la unidad se apague completamente.
Maintenance
Air Filter (Fig. 7)
The air filter should be checked regularly. Operating the dehu-
midifier with a clogged filter will reduce efficiency. The filter can be
vacuum cleaned to remove dust. To access the filter media, slide
the filter frame up until it clears the dehumidifier cabinet. Remove
the filter media from behind the frame and vacuum. Reverse pro-
cedure to re-install the filter and frame into the dehumidifier.
Storage
Freezing temperatures and biological growth must be considered
before storing the dehumidifier. The dehumidifier should be
flushed with a biofungicide before storing. When storing the unit,
ensure that water has been removed from the reservoir and
hose. This will prevent damage caused by freezing temperatures
and to prevent biological growth. Use the pump purge button to
remove water and biofungicide chemicals from the dehumidifier.
Stacking (Fig.9)
The dehumidifiers can be stacked on top of each other. The
wheels from the upper unit must be resting in the cradle of
the lower unit. DO NOT STACK MORE THAN TWO HIGH.
External Cleaning
Use a non-flammable mild, non-abrasive soap and clean
water solution to clean the dehumidifier. Wipe dry.
Internal Cleaning
Disconnect dehumidifier from power supply.
Light cleaning: Remove the air filter and spray evaporator
coil with water.Remove the two upper screws from the front
hood.
Heavy cleaning: Remove two upper screws from front hood.
Open hood. Spray water at coils. Close hood and replace
screws. (Fig. 8)
Fig. 7
Fig. 8
Electrical Shock Hazard
Plug into a grounded 3 prong outlet.
Do not remove ground prong.
Do not use an adapter.
WARNING
Disconnect power supply before cleaning.
Failure to follow these instructions can result in death,
fire, or electrical shock.
Venting / Ducting (Fig. 6)
Twin rear outlets can accommo-
date two individual 5” ducts or one
10” lay flat duct to be attached.
This allows for warm dry air to be
directed into different areas.
Fig. 6
Cleaning
Fig. 9
Service
A qualified refrigeration technician must service all refriger-
ant leaks.
WARNING: The dehumidifier uses a high pressure refrigerant
system and high voltage circuitry which could present a health
hazard resulting in death, serious bodily injury, and/or property
damage. Only qualified service people should service this unit.
CAUTION: Do not operate unit without the front hood secured in
place.
The serial data plate is located on the underside of the dehumid-
ifier. For service information contact 1-800-565-3548.
(2)
Figura 5
Figura 6
Funciones
Función de recuperación tras un corte de energía
En caso de un corte de energía, se conservará el último estado de funcionamiento (encendido o
apagado) cuando se restaure la energía eléctrica.
Función de purga de la bomba
Durante el funcionamiento normal, la bomba vaciará automáticamente el depósito. Si se pulsa el botón
de purga (figura 3) la bomba funcionará durante 1 minuto permitiendo el vaciado manual del depósito. La
purga de la bomba funcionará en todos los modos siempre que la unidad se encuentre enchufada.
Pantalla del contador de horas
Mostrará las horas acumuladas durante el funcionamiento normal. Si la unidad se encuentra apagada
(incluso desenchufada), al pulsar el botón de hora (figura 4) también se mostrarán brevemente las horas
acumuladas.
Ventilación / tubos de ventilación
El aparato cuenta con dos orificios que permiten la instalación de dos tubos individuales de 5 pulgadas
(12.7 cm.), o de uno solo de 10 pulgadas plano (25.4 cm.). De este modo se puede dirigir el aire
caliente a zonas diferentes.
Mantenimiento
Filtro del aire
Debe comprobar el estado del filtro del aire con frecuencia. Si opera el deshumidificador con un filtro
taponado reducirá su eficiencia. Puede pasar una aspiradora por el filtro para eliminar el polvo. ara acceder
al medio del filtro, deslice el marco del filtro hacia arriba hasta extraerlo por completo del aparato (figura
6). uite el medio del filtro de la parte trasera del marco y pase una aspiradora. Haga el proceso a la inversa
para instalar el filtro y el marco en el deshumidificador. Los filtros metálicos deben lavarse con agua y
jabón, y los filtros de papel deben reemplazarse.
El tamaño nominal del filtro de papel es de 12 x 12 x 1 pulg.
Operar la unidad sin el filtro en su lugar dará como resultado una eficiencia reducida debido a la
suciedad de las bobinas y a un aumento en la frecuencia de limpieza de las bobinas internas.
Colocación en vertical
Puede apilar los deshumidificadores uno encima del otro (figura 7). Las ruedas de la unidad que se
coloque encima deberán apoyarse en los huecos de la unidad colocada abajo. NO APILE MÁS DE DOS
UNIDADES.
Built in Electrical Safety
For your safety and protection this appliance is manufactured
with a grounded plug on its power cord. The power cord must
be plugged into a properly grounded receptacle. If a ground-
ed receptacle does not exist, have one installed by a certified
electrician. Do not cut or remove the grounding prong on the
power cord plug if equipped. We recommend that this electri-
cal circuit/receptacle operate under a separate breaker or
fuse.
If an extension cord is required, it must have a minimum of
14 gauge conductors if 25 feet long or less and 12 gauge
conductors if greater than 25 feet long.
Electrical Requirements
For 115V operation, a common grounded outlet on a 15 amp
circuit is required. The dehumidifier draws approx. 8 amps at
80°F, 60% RH. If used in a wet area, a ground fault inter-
rupter (GFI) is required.
Power Button (Fig. 1)
The dehumidifier is turned on or off by
pressing the power button. When the
dehumidifier is started, the hour meter will
display the cumulative hours.
Pump Purge Button (Fig. 2)
In normal operation, the pump will automat-
ically empty the reservoir. Pressing this but-
ton allows manual emptying of the reservoir.
Press once, and the pump will operate for
20 seconds. Press and hold the button and
the pump will activate for 30 seconds.
Always manually purge the water reservoir
before transport or storage. Turn off the
power and allow the plugged in dehumidifier
to rest 5 minutes before the final purge.
Electrical Shock Hazard
Plug into a grounded 3 prong outlet.
Do not remove ground prong.
Do not use an adapter.
Do not use an extension cord.
Failure to follow these instructions can result in death,
fire, or electrical shock.
WARNING
Place dehumidifier inside area to be dried. Make sure all win-
dows and doors are closed to the outside and seal off the wet
area from any unaffected areas. Route condensate hose into
a drain, or a very large container. Press the On/Off button
(Fig. 1) to activate the dehumidifier.
OPERATION
Fig. 1
Fig. 2
Digital Hour Counter (Fig. 3)
The counter will accumulate and display the total running hours
of the unit in 1/10 of an hour.
Hour Button (Fig. 4)
Press the HOURS button when the dehu-
midifier cannot be plugged in and the hour
meter needs to be read. The digital hour
meter will display the last saved cumulative
time for ten seconds.
Defrost Indicator (Fig. 5)
The defrost indicator will light to indicate the
dehumidifier is in defrost cycle. During this
period, the compressor is not running.
Defrost Cycle
When ice builds up on the coils, a thermistor activates the elec-
tronic control and defrost light. The compressor is turned off by
the thermistor temperature measurement. The blower will contin-
ue to run, causing air to flow through the evaporator coil and melt
the ice. When the ice is melted, the thermistor will end the defrost
cycle and the compressor will be started.
Disconnect dehumidifier from power supply. The hour meter uses
a battery backup for display when the dehumidifier is unplugged
and the hour button is depressed. To change the battery, it is nec-
essary to remove the four (4) screws from the control panel.
Disconnect the old battery and replace with new battery. Replace
control panel and screws. Do not overtighten screws.
Water Removal
The dehumidifier is equipped with an internal condensate pump
to remove the water that is collected from the air. This allows the
water to be pumped 20 feet with the attached hose. If the water
needs to be pumped more than 20 feet above the unit, a second
pump must be added to relay the water. The condensate pump
automatically purges for 20 seconds every four minutes.
Fig. 3
Fig. 4
Fig. 5
Electrical Shock Hazard
Plug into a grounded 3 prong outlet.
Do not remove ground prong.
Do not use an adapter.
WARNING
Disconnect power supply before replacing battery.
Failure to follow these instructions can result in death,
fire, or electrical shock.
Battery Replacement
(1)
Figura 3
Figura 4
Maintenance
Air Filter (Fig. 7)
The air filter should be checked regularly. Operating the dehu-
midifier with a clogged filter will reduce efficiency. The filter can be
vacuum cleaned to remove dust. To access the filter media, slide
the filter frame up until it clears the dehumidifier cabinet. Remove
the filter media from behind the frame and vacuum. Reverse pro-
cedure to re-install the filter and frame into the dehumidifier.
Storage
Freezing temperatures and biological growth must be considered
before storing the dehumidifier. The dehumidifier should be
flushed with a biofungicide before storing. When storing the unit,
ensure that water has been removed from the reservoir and
hose. This will prevent damage caused by freezing temperatures
and to prevent biological growth. Use the pump purge button to
remove water and biofungicide chemicals from the dehumidifier.
Stacking (Fig.9)
The dehumidifiers can be stacked on top of each other. The
wheels from the upper unit must be resting in the cradle of
the lower unit. DO NOT STACK MORE THAN TWO HIGH.
External Cleaning
Use a non-flammable mild, non-abrasive soap and clean
water solution to clean the dehumidifier. Wipe dry.
Internal Cleaning
Disconnect dehumidifier from power supply.
Light cleaning: Remove the air filter and spray evaporator
coil with water.Remove the two upper screws from the front
hood.
Heavy cleaning: Remove two upper screws from front hood.
Open hood. Spray water at coils. Close hood and replace
screws. (Fig. 8)
Fig. 7
Fig. 8
Electrical Shock Hazard
Plug into a grounded 3 prong outlet.
Do not remove ground prong.
Do not use an adapter.
WARNING
Disconnect power supply before cleaning.
Failure to follow these instructions can result in death,
fire, or electrical shock.
Venting / Ducting (Fig. 6)
Twin rear outlets can accommo-
date two individual 5” ducts or one
10” lay flat duct to be attached.
This allows for warm dry air to be
directed into different areas.
Fig. 6
Cleaning
Fig. 9
Service
A qualified refrigeration technician must service all refriger-
ant leaks.
WARNING: The dehumidifier uses a high pressure refrigerant
system and high voltage circuitry which could present a health
hazard resulting in death, serious bodily injury, and/or property
damage. Only qualified service people should service this unit.
CAUTION: Do not operate unit without the front hood secured in
place.
The serial data plate is located on the underside of the dehumid-
ifier. For service information contact 1-800-565-3548.
(2)
Figura 7
9
fantech
Maintenance
Air Filter (Fig. 7)
The air filter should be checked regularly. Operating the dehu-
midifier with a clogged filter will reduce efficiency. The filter can be
vacuum cleaned to remove dust. To access the filter media, slide
the filter frame up until it clears the dehumidifier cabinet. Remove
the filter media from behind the frame and vacuum. Reverse pro-
cedure to re-install the filter and frame into the dehumidifier.
Storage
Freezing temperatures and biological growth must be considered
before storing the dehumidifier. The dehumidifier should be
flushed with a biofungicide before storing. When storing the unit,
ensure that water has been removed from the reservoir and
hose. This will prevent damage caused by freezing temperatures
and to prevent biological growth. Use the pump purge button to
remove water and biofungicide chemicals from the dehumidifier.
Stacking (Fig.9)
The dehumidifiers can be stacked on top of each other. The
wheels from the upper unit must be resting in the cradle of
the lower unit. DO NOT STACK MORE THAN TWO HIGH.
External Cleaning
Use a non-flammable mild, non-abrasive soap and clean
water solution to clean the dehumidifier. Wipe dry.
Internal Cleaning
Disconnect dehumidifier from power supply.
Light cleaning: Remove the air filter and spray evaporator
coil with water.Remove the two upper screws from the front
hood.
Heavy cleaning: Remove two upper screws from front hood.
Open hood. Spray water at coils. Close hood and replace
screws. (Fig. 8)
Fig. 7
Fig. 8
Electrical Shock Hazard
Plug into a grounded 3 prong outlet.
Do not remove ground prong.
Do not use an adapter.
WARNING
Disconnect power supply before cleaning.
Failure to follow these instructions can result in death,
fire, or electrical shock.
Venting / Ducting (Fig. 6)
Twin rear outlets can accommo-
date two individual 5” ducts or one
10” lay flat duct to be attached.
This allows for warm dry air to be
directed into different areas.
Fig. 6
Cleaning
Fig. 9
Service
A qualified refrigeration technician must service all refriger-
ant leaks.
WARNING: The dehumidifier uses a high pressure refrigerant
system and high voltage circuitry which could present a health
hazard resulting in death, serious bodily injury, and/or property
damage. Only qualified service people should service this unit.
CAUTION: Do not operate unit without the front hood secured in
place.
The serial data plate is located on the underside of the dehumid-
ifier. For service information contact 1-800-565-3548.
(2)
Figure 8
Cambio de la batería
Desconecte la toma de corriente antes de limpiar.
No seguir estas instrucciones podría provocar incendios, descargas eléctricas, e incluso la
muerte.
Desconecte el deshumidificador de la toma de corriente. El indicador de horas de operación utiliza una
batería para que pueda ser operativo si el aparato no está enchufado y se presiona el botón de horas. Para
cambiar esta batería, tendrá que desatornillar los cuatro (4) tornillos del panel de instrumentos. Desconecte
la batería agotada y sustitúyala por una nueva. Vuelva a colocar el panel de instrumentos y los tornillos, sin
apretarlos en exceso.Limpieza
Desconecte la toma de corriente antes de limpiar.
No seguir estas instrucciones podría provocar incendios, descargas eléctricas, e incluso la
muerte.
Limpieza del exterior
Utilice una solución de jabón suave, no abrasivo ni inflamable y agua limpia para limpiar el
deshumidificador. Pase un trapo para secarlo.
Limpieza del interior
Desconecte el deshumidificador de la toma de corriente.
Limpieza ligera: Saque el aire del filtro y rocíe el serpentín evaporador con agua.
Limpieza profunda: Desatornille los dos tornillos de la parte superior de la cubierta frontal. Abra la
cubierta. Rocíe los serpentines con agua. Cierre la cubierta y vuelva a colocar los tornillos
(figura 8).
Debe tenerse cuidado de no dañar láminas de la bobina, ya que las láminas dañadas pueden
restringir el flujo del aire y reducir la capacidad de la unidad para producir agua.
Almacenamiento
Las temperaturas bajo cero y el crecimiento biológico deben considerarse antes de almacenar el
deshumidificador. Para evitar el crecimiento biológico, rocíe un limpiador de evaporador sobre las
bobinas y enjuague hacia el sistema de drenaje. También debe purgar el exceso de líquido de la
bomba usando la función de purga manual para evitar problemas en ambientes de almacenamiento
bajo cero.
10
fantech
Solución de problemas
Servicio
Un técnico de refrigeración calificado debe reparar todas las fugas de
refrigerante.
La unidad NO funciona:
¿Se ha disparado el disyuntor? – Restablezca el disyuntor
Si la unidad se encuentra en un área húmeda, ¿está enchufada en un
circuito protegido por un disyuntor diferencial? – La humedad excesiva
disparará el disyuntor diferencial. Aléjela de esa área.
¿Está la unidad conectada a un generador? - Verifique que la tensión de
salida no fluctúe ya que la unidad no funcionará con baja tensión.
Si está conectada mediante un alargador - ¿posee dicho alargador el
grosor adecuado para su longitud? (14 AWG hasta 25 pies y AWG para
más de 25 pies). Nota: Verifique la tensión mientras la unidad está
arrancando. El arranque causará el mayor consumo de corriente y la
mayor caída de tensión. Aun estando conectada directamente al
tomacorriente puede haber una significativa caída de tensión. Nunca
suponga que la tensión es la correcta sin comprobarlo.
La unidad se apaga y muestra un código de error.
ER 1: El interruptor de desborde permanece cerrado por más de 2 minutos.
Manguera de drenaje tapada o retorcida – Elimine la obstrucción
Mala conexión en el circuito de la bomba – Verifique las conexiones
Bomba de condensado defectuosa – Sustitúyala
ER 2: El interruptor de presión interna indica una presión del refrigerante
demasiado alta.
El filtro de aire está sucio u obstruido - Límpielo o sustitúyalo
La bobina está sucia – Límpiela
Conexiones eléctricas flojas o defectuosas hacia el interruptor de presión
– Verifique las conexiones
El ventilador no funciona – Sustitúyalo
Interruptor de presión defectuoso – Sustitúyalo
La unidad se congela continuamente: Tenga en cuenta que es normal la
acumulación de cierta cantidad de hielo en el evaporador, pero no debe
bloquear el flujo del aire.
¿Sale aire caliente por la parte trasera de la unidad? - No hay aire
caliente, puede que la temperatura ambiente sea demasiado baja.
Aumente la temperatura mediante una fuente suplementaria.
¿Está el filtro de aire limpio y el flujo de aire sin obstrucciones? – Limpie
el filtro. La unidad debería tener un espacio libre de 10 pulg. libre de
obstáculos en todas las direcciones.
¿Está sucia la bobina del evaporador? – Limpie la bobina.
La unidad mueve algo de agua pero no tanto como se supone:
El filtro de aire está sucio o el flujo de aire obstruido - La unidad debería
tener un espacio libre de 10 pulg. libre de obstáculos en todas las
direcciones. Limpie el filtro de aire y asegúrese de que exista un flujo de
aire/espacio adecuado alrededor de la unidad.
La bobina del evaporador está sucia – Límpiela.
Tuberías de escape restrictivas o retorcidas – Enderécelas.
El ventilador no funciona. El compresor funciona brevemente pero luego se
enciende y apaga cíclicamente:
Conexión floja en el circuito del ventilador – Verifique las conexiones.
Ventilador obstruido y estático – Elimine la obstrucción
Ventilador defectuoso – Sustitúyalo.
Tablero de control defectuoso – Sustitúyalo.
11
fantech
GREEN & YELLOW
G
N
L1
ELECTRONIC CONTROL BOARD
E2
E3
E1
E5
E4
J1 J3
COMPRESSOR
O/L
C
R
S
CONDENSATE PUMP
CAPACITOR
BLOWER
14uF
BLOWER
WHITE
THERMISTOR FLOAT
CAPACITOR
COMPRESSOR
60uF
BLUE
BROWN
BLACK
BROWN
WHITE
2-78119-001 REV. 01
WHITE
BLACK
BLUE
BLUE
WHITE
BLACK
WHITE
BROWN
BLACK
RED
WHITE
WHITE
J2
SWITCH
PRESSURE
Diagrama de cableado
12
fantech
One (1) Year Warranty
This warranty supersedes all prior warranties
WARRANTY
WARRANTY - ONE YEAR
This product is warranted against defects in material and workmanship for
a period of one year from the date of purchase by the original purchaser.
During this period, all parts and labor will be provided at no cost.
Consumable parts (ie: light bulbs and filters) are not warranted or
guaranteed for any length of time. This warranty is non transferable.
ADDITIONAL SIX YEAR WARRANTY
For a period of six years following the ONE YEAR WARRANTY components
of the sealed system are warranted against defects in material. Parts will
be supplied (freight prepaid) free of charge. Installation labor is not
covered. This warranty is non transferable.
LIFETIME WARRANTY ON ROTOMOLDED HOUSING
The Rotomolded housing of this product carries a lifetime warranty. This
warranty is non transferable.
NOTICE
1. This warranty applies only to the original purchaser and applies only
within the boundaries of CANADA and CONTINENTAL USA.
2. This is the only warranty of the dealer and Fantech Limited. for the
above mentioned product and no other warranty or condition, expressed
or implied shall apply, except where specifically excluded by law.
3. The original purchaser should complete this warranty form and retain it
in the event warranty service is required.
4. Proof of purchase date will be required for warranty claims. Please
retain bills of sale for proof.
5. Some states do not allow the exclusion or limitation of incidental or
consequential damages, so the above limitation or exclusion may not
apply to you. This warranty gives specific legal rights, and the purchaser
may have other rights which vary from state to state. For more
information regarding legal rights the purchaser may contact the local
or state consumer affairs office or the appropriate state Attorney
General.
GENERAL PROVISIONS
No warranty or insurance herein contained or set out shall apply when
damage or repair is caused by any of the following:
1. Power failure.
2. Damage in transit or when moving the appliance.
3. Improper power supply such as low voltage, defective house wiring or
inadequate fuses.
4. Accident, alteration, abuse or misuse of the appliance such as
inadequate air circulation in the room or abnormal operating
conditions, (extremely high or low room temperatures).
5. Fire, water, damage, theft, war, riot, hostility, acts of God such as
hurricanes, floods, etc.
For information concerning your warranty, contact:
In Canada
Fantech
50 Kanalflakt Way,
Bouctouche, NB E4S 3M5
Phone: 800.565.3548; 506.743.9500
Fax: 877.747.8116; 506.743.9600
In Continental USA
Fantech
10048 Industrial Blvd.
Lenexa, KS 66215
Phone: 800.747.1762; 913.752.6000
Fax: 800.487.9915; 913.752.6466
13
fantech
Garantia por un (1) Años
Esta garantia de sin efecto cualquier otra garantia anterior
GARANTÍA DE UN AÑO
Se garantiza este producto contra defectos de fabricación y materiales por
un periodo de un año a contar a partir de la fecha de compra del
comprador original. Todas las partes y la mano de obra estarán cubiertas
sin coste alguno durante este periodo. Las partes de reemplazo habitual
(bombillas y filtros, por ejemplo), no están cubiertas por la garantía ni se
garantizan durante periodo de tiempo alguno. Esta garantía no puede
transferirse.
GARANTÍA ADICIONAL DE SEIS AÑOS
Durante un periodo de seis años a contar desde la finalización de la
GARANTÍA DE UN AÑO, los componentes del sistema precintado están
cubiertos en caso de que las piezas mostraran algún defecto. Se
entregarán las piezas de manera gratuita (tras prepago de costos de
envío). Los costes de mano de obra para la instalación no están cubiertos
por la garantía. Esta garantía no puede transferirse.
GARANTÍA DE POR VIDA EN LA CAJA ROTOMOLDEADO
La caja rotomoldeado de este producto cuenta con una garantía de por
vida. Esta garantía no es transferible.
AVISO
1. Esta garantía es válida solamente para el comprador original y dentro
de las fronteras de Canadá y la parte continental de Estados Unidos.
2. Esta es la única garantía del vendedor y de Fantech Limited para el
producto mencionado arriba. Ningún otro tipo de garantía o condición,
explícita o implícita, será aplicable, excepto en casos específicamente
excluidos por ley.
3. El comprador original deberá completar el formulario de garantía y
conservarlo para poder utilizarlo en caso de que sea preciso dar servicio
al producto.
4. Para cualquier reclamación de garantía será preciso contar con una
prueba de compra con fecha. Recuerde guardar el recibo como
comprobante de venta.
5. En algunos estados no se permite la exclusión o limitación de daños
consecuentes o secundarios; en estos casos, la limitación anterior
podría no aplicar a su caso. Esta garantía ofrece derechos legales
específicos; el comprador puede contar con otros diferentes dependiendo
del estado. Si necesita más información sobre los derechos legales del
comprador, puede consultar con la oficina del consumidor local o
estatal, o con el fiscal de su estado.
PROVISIONES GENERALES
La garantía o seguro contenidos o establecidos aquí no serán aplicables
cuando el daño o la reparación consecuentes sean resultado
de alguno de los siguientes:
1. Fallo del suministro eléctrico.
2. Daños durante el transporte o traslado del electrodoméstico.
3. Suministro eléctrico inadecuado del tipo voltaje bajo, cableado deficiente
en la casa o fusibles no adecuados.
4. Accidente, alteración, abuso o mal uso del electrodoméstico del tipo
circulación de aire inadecuado en el cuarto, o condiciones anormales de
operación (temperaturas demasiado altas o demasiado bajas en el
cuarto).
5. Fuego, agua, daño, robo, guerra, disturbios, hostilidades, casos de
fuerza mayor del tipo huracanes, inundaciones, etc.
Para obtener información relativa a la garantía, comuníquese con:
En CANADA
Fantech
50 Kanalflakt Way,
Bouctouche, NB E4S 3M5
Phone: 800.565.3548; 506.743.9500
Fax: 877.747.8116; 506.743.9600
En Estados Unidos continental
Fantech
10048 Industrial Blvd.
Lenexa, KS 66215
Phone: 800.747.1762; 913.752.6000
Fax: 800.487.9915; 913.752.6466
GARANTIA
14
fantech
NOTES
15
fantech
NOTAS
fantech
Fantech reserves the right to make technical changes.
For updated documentation please refer to www.fantech.net
Fantech®
Fantech se reserva el derecho de hacer modicaciones
técnicas en cualquier momento. Para obtener la documen-
tación actualizada, por favor consulte www.fantech.net
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16

Fantech EPD180CR Installation and Maintenance Manual

Categoría
Deshumidificadores
Tipo
Installation and Maintenance Manual
Este manual también es adecuado para

En otros idiomas