CARLO GAVAZZI RSBT4895CVC Guía de instalación

Tipo
Guía de instalación
ATTENTION
1. To prevent electrical shock, disconnect from power source
before installing or servicing.
2
. The bypass relays in the main circuit may be in an undefined switching state due
t
o handling during shipping. Before first operation of the product, apply the supply
v
oltage to set the bypass relays to a defined state. Unintentional operation of the
c
ompressor may result if this operation is not performed.
3. Unauthorised opening of the product will void warranty.
4. “For use in Pollution Degree 3 Environment”.
5
. The device should be configured as indicated in the connection diagram. Do not
o
perate the product before all connections are completed.
6. The softstarter does not have any integrated short circuit and overload protection.
These must be procured separately.
7. Excessive lengths of cabling should be avoided in view of EMC considerations.
8
. The RSBD and RSBT softstarter series has been designed for Class A equip-
m
ent. Use of the product in domestic environments may cause radio interference.
9. The opening of the branch-circuit protective device may be an indication that a
fault has been interrupted. To reduce the risk of fire or electric shock, current-car-
rying parts and other components of the controller should be examined and re-
placed if damaged. If burnout of the current element of an overload relay occurs, the
complete overload replay must be replaced.
10. For the Canadian application, the control terminals A1, A2 of the RSB. devices
shall be supplied by a secondary circuit where power is limited by a transformer, rec-
t
ifier, voltage divider, or similar device that derives power from a primary circuit, and
w
here the short-circuit limit between conductors of the secondary circuit or between
c
onductors and ground is 1500 VA or less. The short-circuit volt ampere limit is the
p
roduct of the open circuit voltage and the short circuit ampere.
BEMÆRK
1. For at undgå elektrisk stød, frakobl fra strømkilde
før installation og servicering.
2
. By-pass relæerne i hovedafbryderen kan stå i en ikke nærmere defineret ind-
s
tilling grund af håndtering under forsendelse. Før produktet anvendes første
g
ang, skal by-pass relæerne indstilles korrekt til netspændingen. Hvis denne han-
d
ling ikke udføres, kan der opstå utilsigtet drift med kompressoren.
3. Uautoriseret åbning af produktet vil ugyldiggøre garantien.
4
. ”Til brug i miljø med forureningsgrad 3”.
5. Dette udstyr bør konfigureres som angivet i tilslutningsdiagrammet. Sæt ikke pro-
duktet i drift før alle tilslutninger er foretaget.
6. Softstarteren har ingen indbygget beskyttelse mod kortslutning og overbelast-
ning. Disse skal anskaffes separat.
7
. Overdreven længde kabler bør undgås under hensyntagen til EMC (elektro-
m
agnetisk kompatibilitet).
8. RSBD og RSBT softstarterserien er fremstillet som klasse A udstyr. Anvendelse
af produktet i beboelsesmiljøer kan skabe radiointerferens.
9
. Åbningen af et kredsløbet beskyttende enhed kan være et tegn at en fejl er
b
levet afbrudt. For at mindske risikoen for brand eller elektrisk stød, skal strø
f
ørende dele og andre komponenter i enheden undersøges og udskiftes hvis
b
eskadiget. Hvis ”Burnout” af et strøm-element i et overbelastningsrelæet er brændt
o
ver, skal hele overbelastningsrelæet udskiftes
10. "Til brug i Canada skal styreklemmerne A1, A2 i RSB.-enhederne suppleres
m
ed et sekundært kredsløb, hvor strømmen begrænses med en transformer, strøm-
r
etter, spændingsdeler eller lignende enhed, der afleder strømmen fra et primært
k
redsløb, og hvor kortslutningsgrænsen mellem ledere af det sekundære kredsløb
e
ller mellem ledere og jord er 1500 VA eller mindre. Volt-ampere-
k
ortslutningsgrænsen er produktet af den åbne kredsløbsspænding og kort-
s
pændingsampere”
ACHTUNG
1. Trennen Sie das Gerät vor der Installation und vor
W
artungsvorgängen von der Stromversorgung, um das Risiko eines
elektrischen Schlags zu vermeiden.
2. Die Kurzschlussrelais im Hauptstromkreis befinden sich aufgrund der Handhabung
beim Transport glicherweise in einem undefinierten Schaltzustand. Legen Sie daher
vor derersten Inbetriebnahme desProdukts die Versorgungsspannung an, um die Kurz-
s
chlussrelais in einen definierten Zustand zu versetzen. Wenn dieser Schritt nicht
durchgeführt wird, kann dies zu unerwünschtem Einschalten des Kompressors hren.
3. Unerlaubtes Öffnen des Produkts führt zum Verlust der Garantie.
4. „Für die Verwendung in einer Umgebung mit dem Verschmutzungsgrad 3“.
5. Das Gerät muss wie im Anschlussdiagramm angegeben konfiguriert werden.
S
chalten Sie das Produkt nicht ein, bevor alle Verbindungen hergestellt sind.
6. Das Sanftstartgerät besitzt keinen integrierten Kurzschluss- und Überlastschutz.
D
ieser muss gesondert bereitgestellt werden.
7
. Übermäßig gre Kabellängen solltenaus Gründen der Störfestigkeit vermieden werden.
8. Die Produktreihe der RSBD- und RSBT-Sanftstartgeräte wurde für Geräte der
K
lasse A entwickelt. Der Einsatz des Produkts in Wohnumgebungen kann
Funkstörungen hervorrufen.
9
. Das Öffnen der Schutzeinrichtung des Stromzweigs kann ein Hinweis darauf
s
ein, dass ein Fehlerzustand unterbrochen wurde. Um die Brandgefahr und die
G
efahr elektrischer Schläge zu reduzieren, müssen stromführende Bauteile und
a
ndere Komponenten des Controllers überprüft und ersetzt werden, falls sie
b
eschädigt sind. Wenn beim Stromelement des Überstromrelais Abbrand auftritt,
m
uss das gesamte Überstromrelais ausgetauscht werden.
1
0. Bei Anwendungen in Kanada sind die Steuerungsklemmen A1, A2 der RSB.-
G
eräte über einen sekundären Stromkreis zu versorgen, in dem die Leistung durch
e
inen Transformator, Gleichrichter, Spannungstrenner oder ein ähnliches Gerät,
das aus einem Primärkreis mit Strom versorgt wird, begrenzt ist und in dem der
Kurzschlussgrenzwert zwischen Leitern des sekundären Stromkreises oder zwis-
chen Leitern und Erde höchstens 1500 VA beträgt. Der Volt-Ampere-
Kurzschlussgrenzwert ist das Produkt aus der Leerlaufspannung und dem
Kurzschlussstrom
IMPORTANT
Carlo Gavazzi is not to be held responsible for incorrect product operation or dam-
ages resulting from improper use of the product and/or use of the product outside
its specified operating limits. Products, specifications and data in this document
are subject to change without notice. The product is intended to be used by qual-
ified personnel at their own discretion and risk. Should you require information about
installation, operation or maintenance of the product that is not covered in this doc-
ument you should refer the matter to an authorized Carlo Gavazzi representative.
The information in this document is not considered binding on any product war-
ranty.
IMPORTANT
Carlo Gavazzi ne peut être tenu responsable d'une exploitation incorrecte du pro-
duit ou d'avaries résultant d'une utilisation incorrecte du produit et/ou hors des
tolérances de fonctionnement spécifiées.
Les produits, caractéristiques et données décrites dans le présent document peu-
vent changer sans préavis. L'utilisation de ce produit est destinée à un personnel
qualifié qui l'exploite à sa guise et à ses propres risques. Pour plus amples infor-
mations concernant l'installation, le fonctionnement ou la maintenance du produit
et ne figurant pas dans ce document, consulter un concessionnaire agréé Carlo
Gavazzi. Les informations contenues dans ce document ne constituent une obli-
gation de garantie de quelconque nature du produit.
VIGTIGT
Carlo Gavazzi kan ikke holdes ansvarlig for ukorrekt anvendelse af produktet eller
skader opstået ved ukorrekt brug og/eller efter brug af produktet til andet end de
specificerede driftsbestemmelser. Produkter, specifikationer og data i dette doku-
ment kan ændres uden varsel. Produktet er beregnet til anvendelse af uddannet
personale efter eget skøn og risiko. Hvis du har brug for oplysninger om installation,
drift eller vedligeholdelse af produktet, der ikke er dækket af nærværende doku-
ment, bør du rette henvendelse til en autoriseret repræsentant fra Carlo Gavazzi.
Informationen i nærværende dokument anses ikke for bindende for nogen produk-
tgaranti.
IMPORTANTE
Carlo Gavazzi no se responsabiliza del uso incorrecto del producto o de los daños
ocasionados por un uso incorrecto del mismo y /o por el uso del producto sin tener
en cuenta los límites de funcionamiento especificados. Los equipos, especifica-
ciones y datos recogidos en este documento están sujetos a cambios sin previo
aviso. El equipo debe usarse por personal cualificado y bajo su responsabilidad y
riesgo. En caso de necesitar más información sobre la instalación, funcionamiento
o mantenimiento del equipo que no se refleje en este documento, póngase en con-
tacto con un distribuidor autorizado de Carlo Gavazzi. La información detallada en
este documento no se considera vinculante en ninguna garantía del producto.
WICHTIG
Carlo Gavazzi übernimmt keine Haftung r fehlerhafte Bedienung des Produkts sowie r
Scden, die aus unsachgeßer Verwendung des Produkts und/oder dem Einsatz des
Produkts außerhalbderangegebenen Grenzbetriebsdatenresultieren. Die indiesemDoku-
ment beschriebenen Produkte, Spezifikationen und technischen Daten nnen jederzeit
ohne vorherige Anndigung geändert werden. Das Produkt ist nur r die Verwendung
durch qualifiziertes Fachpersonal nach eigenem Ermessen und auf eigenes Risiko vorge-
sehen. WennSie Informationenzur Installation,zum Betrieboderzur Wartungdes Produkts
betigen, die nicht in dieserAnleitung enthalten sind, wenden Sie sich mit Ihrer Frage an
einen autorisierten Vertriebspartnervon CarloGavazzi. DieInformationen indiesem Doku-
ment sind nicht bindend hinsichtlich der Produktgehrleistung.
IMPORTANTE
Carlo Gavazzi non può essere ritenuta responsabile per un malfunzionamento o danni
derivanti da un uso improprio del prodotto e/o utilizzo del prodotto al di fuori dei suoi limiti
operativi specificati. Prodotti, specifiche e dati in questo documento sono soggette a mod-
ifiche senza preavviso.Il prodotto è destinato ad essere utilizzato da personale qualificato
a propria discrezione e rischio. Se avete bisogno di informazioni su installazione, funzion-
amento o manutenzionedelprodotto non riportatein questo documento, dovete fare rifer-
imento al personale autorizzato Carlo Gavazzi. Le informazioni contenute in questo
documento non sono considerate vincolanti per alcuna garanzia sul prodotto.
ATTENTION
1. Avant toute installation ou intervention, déconnecter la source
d'alimentation pour éviter tout risque d'électrocution.
2. La manutention en cours de transport peut positionner les relais de bipasse du
circuit principal dans un état de commutation indéfini.
Avant mise en service initiale, mettre le produit sous tension afin de positionner les
relais de bipasse dans un état de commutation défini.
Effectuer cette opération impérativement sous peine de provoquer un fonction-
nement intempestif du compresseur.
3
. L'ouverture non autorisée du produit annule la garantie.
4. « Pour exploitation en environnement de degré de pollution 3 ».
5. Configurer le dispositif comme indiqué dans le schéma des connexions.Ne pas
utiliser le produit tant que toutes les connexions ne sont pas réalisées.
6
. Le démarreur progressif n'intègre aucune protection contre les courts-circuits/la
s
urcharge.Ces protections doivent être approvisionnées séparément.
7. Éviter les longueurs excessives de câblage afin de respecter les normes de com-
patibilité électromagnétique.
8.Lariedes marreurs progressifs RSBD et RSBT a été cou pour leséquipements
de ClasseA.L'utilisation dece produit dans les environnements sidentiels peutprovoquer
des interférences radio magtiques.
9. L'ouverture du dispositif de protection de la dérivation peut signifier qu'il s'est
produit une défaillance. Pour diminuer le risque d'incendie ou de choc électrique,
vérifier les pièces et les autres composants sous tension du contrôleur et les rem-
placer s'ils sont endommagés. En cas de claquage de l'élément de courant d'un re-
lais de surcharge, remplacer le relais de surcharge au complet
10. « Pour les applications au Canada, les bornes de contrôle A1, A2 des appareils
RSB. seront alimentées par un circuit secondaire dans lequel le courant est limité
par un transformateur, un redresseur, un réducteur de tension, ou un appareil sim-
ilaire dérivant du courant d’un circuit primaire et la limite de court-circuit entre les
conducteurs du circuit secondaire ou entre les conducteurs et la terre est égale ou
inférieure à 1500 VA. La limite en voltampère du court-circuit est le produit de la ten-
sion du circuit ouvert et des ampères du court-circuit. »
ATENCIÓN
1. Antes de instalar o revisar el equipo, desconéctelo para evitar
descargas eléctricas.
2. Los relés de bypass del circuito principal pueden estar en un estado indefinido
de conexión debido al transporte. Antes de conectar el equipo, aplique la ali-
mentación para que los relés de bypass estén en su posición correcta. Si no se
realiza esta operación, puede que el compresor funcione incorrectamente.
3
. La apertura del equipo sin autorización por parte del fabricante anula la garan-
t
ía.
4. “Para uso en entornos con grado de contaminación 3”
5. El equipo debe configurarse como se indica en el diagrama de conexión. El
equipo no debe conectarse hasta que se hayan realizado todas las conexiones.
6
. El arrancador suave no tiene protección contra cortocircuitos ni sobrecarga.
D
eben instalarse independientemente.
7. Hay que evitar una longitud excesiva de los cables, con el fin de cumplir con los
requisitos de compatibilidad electromagnética.
8. Las series RSBD y RSBT de arrancadores suaves se han diseñado como
equipos Clase A. Su uso en instalaciones domésticas puede causar radio
interferencias.
9. La apertura del equipo de protección de uno de los circuitos puede ser una indi-
cación de que el fallo ha sido interrumpido. Para reducir el riesgo de incendio o
descarga eléctrica, las partes conductoras de corriente y otros componentes del
controlador deben ser examinadas y sustituidas, si están dañadas. Si hay un chis-
pazo en el relé de sobrecarga, hay que sustituirlo por completo.
10. "Para aplicaciones en Canadá, los terminales de control A1, A2 del controlador
RSBx deben alimentarse con un circuito secundario donde la potencia está limitada
por un transformador, rectificador, divisor de tensión o similar, que deriva potencia
de un circuito primario y donde el límite de cortocircuito entre conductores del cir-
cuito secundario o entre conductores y tierra es de 1500 VA o menor. El límite VA
de cortocircuito se obtiene multiplicando la tensión de circuito abierto y los ampe-
rios de cortocircuito."
ATTENZIONE
1. Per evitare scosse elettriche, scollegare dalla corrente prima
di installare o la manutenzione.
2. I relè di bypass nel circuito principale può essere in uno stato di commutazione
indefinito a causa di sollecitazioni durante la spedizione. Alla prima operazione del
prodotto, applicare la tensione di alimentazione per impostare i relè di bypass in uno
stato definito. Il compressore può attivarsi in maniera accidentale se questa oper-
azione non viene eseguita.
3
. L'apertura non autorizzata del prodotto renderà nulla la garanzia.
4. "Per l'uso in ambiente grado di inquinamento 3".
5
. Il dispositivo deve essere configurato come indicato nello schema di collega-
m
ento. Non utilizzare il prodotto prima che tutti i collegamenti sono completati.
6. Il soft starter non ha nessuna protezione da cortocircuito e sovraccarico. Questi
devono essere installati a parte.
7. I cavi non devono avere una lunghezza eccessiva per rispettare le richieste EMC.
8
. Le serie RSBD e RSBT sono state progettate per sistemi in Classe A. L'uso del
p
rodotto in ambienti domestici può causare interferenze radio.
9
. L'apertura del circuito di protezione può essere un'indicazione che il guasto è
s
tato interrotto. Per ridurre il rischio di incendi o scosse elettriche, le parti sotto
c
arico e gli altri componenti del regolatore devono essere esaminate e sostituite se
d
anneggiate. Se il relè di sovraccarico si interrompe, il relè deve essere sostituito.
1
0. "Per il mercato canadese, i terminali di controllo A1, A2, dei dispositivi RSB.
d
evono essere alimentati da un circuito secondario in cui la potenza è limitata da
u
no dei seguenti sistemi, trasformatore, raddrizzatore, partitore di tensione, o un
d
ispositivo analogo che deriva l’energia da un circuito primario, e dove i cortocircuiti
s
ono limitati tra i conduttori del circuito secondario o tra i conduttori e la terra per
t
ensioni di 1500 VA o inferiori. Il limite della corrente di corto circuito è dato dal
sistema della tensione a circuito aperto e gli ampere di corto circuito"
ASSEMBLY INSTRUCTIONS - MONTERINGSINSTRUKTIONER - INSTRUC-
TIONS DE MONTAGE - INSTRUCCIONES DE MONTAJE -MONTAGEAN-
WEISUNGEN - ISTRUZIONI DI MONTAGGIO
1
Din Rail
1
2
2
Din Rail
DIN RAIL MOUNTING - DIN-SKINNE MONTERING - MONTAGE SUR RAIL
DIN - MONTAJE EN CARRIL DIN - BEFESTIGUNG AUF DIN-HUTSCHIENE -
MONTAGGIO SU GUIDA DIN
P
anel Mounting - Tavlemontering - Montage en tableau - Montaje en panel - Befestigung auf
Schalttafel - Montaggio a pannello
Mounting: Push the unit in and down onto the upper rail
edge. Ensure that both clips are in place on the rail.Push
the unit inwards in the direction of the rail until the unit
“snaps” into place.
Montage: Appuyer sur le module vers le bas en le re-
poussant sur le rail supérieur.Constater que les deux
agrafes sont en place sur le rail. Appuyer sur le module
vers l'intérieur dans la direction du rail jusqu'à ce qu'à
agrafage en position.
Montering: Tryk enheden ind og ned øverste skin-
nekant. Sørg for, at begge clips står korrekt skinnen.
Skub enheden indad i retning mod skinnen, indtil enheden
“klikker” plads.
Montaje: Presionar el equipo de arriba abajo, fijando
primero la parte superior del carril. Asegúrese de que
ambos clips están bien sujetos. Empuje el equipo en la di-
rección del carril hasta que quede encajado en su sitio.
Einbau: Stecken Sie das Gerät ein, und drücken Sie es
auf die obere Kante der Schiene. Überzeugen Sie sich
davon, dass beide Klammern ordnungsgemäß auf der
Schiene sitzen. Drücken Sie das Gerät in Richtung der
Schiene nach innen, bis es in der Schiene einrastet.
Montaggio: Spingere l'uni verso il basso sul bordo superi-
ore della guida DIN. Assicurarsi che entrambe le clip siano
sulla guida. Spingere verso l'interno unità in direzione del bi-
nario fino a quando l'uni "si blocca" in posizione.
Dismounting: Press the unit down and at the same time,
pull the unit outwards from the bottom side. Slightly lift the
unit up to disengage the clips from the rail edge.
Afmontering: Tryk enheden ned og træk samtidig en-
heden udad fra undersiden. Løft enheden en smule op for
at frakoble clipsene fra skinnekanten.
Démontage: Appuyer sur le module vers le bas tout en le
tirant vers l'extérieur par sa partie inférieure. Soulever
légèrement le module pour dégager les agrafes du bord
du rail.
Desmontaje: Presionar el equipo hacia abajo y al mismo
tiempo, tirar del equipo desde abajo. Levante con cuidado
el equipo para desengancharlo de los clip desde el final
del carril.
Abbau: Drücken Sie das Gerät nach unten, und ziehen
Sie es gleichzeitig an der Unterkante von der Schiene
weg. Heben Sie das Gerät leicht an, um die Klammern von
der Kante der Schiene zu lösen.
Smontaggio: Premere l'unità verso il basso e, allo stesso
tempo, tirare l'unità verso l'esterno dal lato inferiore. Soll-
evare leggermente l'unità fino a sganciare le clip dalla
guida DIN
4 x self-tapping screws 4.2mm (provided), 4 x selvskærende skruer 4,2 mm (medfølger),
4
x vis auto-taraudeuses 4,2mm (fournies),4 tornillos autorroscantes de 4,2mm (incluidos),
4 × Schneidschrauben 4,2 mm (im Lieferumfang enthalten),4 x viti autofilettanti 4,2 millimetri (in dotazione)
1 x M5 screw (provided)
1 x M5 skrue (medfølger)
1 x vis M5 (fournie)
1 tornillo M5 (incluido)
1 × M5-Schraube (im Lieferumfang enthalten)
1 x vite M5 (in dotazione)
4 x M6 screws (not provided)
4 x M6 skruer (medfølger ikke)
4 x vis 6 (non fournies)
4 tornillos M6 (no incluidos)
4 × M6-Schrauben (nicht im Lieferumfang enthalten)
4 x M6 viti (non fornite)
R
SBD & RSBT series
Mounting and Operating Instructions
Monterings- og driftsinstruktioner
M
ontage- und Betriebsanweisungen
Instructions de montage et de fonctionnement
I
nstrucciones de montaje y funcionamiento
I
struzioni operative e di montaggio
INST RSBT_D 251111 7680465
TERMINAL DIAGRAM | KLEMMEDIAGRAM | DIAGRAMA DE TERMINALES |
BELEGUNGSPLAN | IMPLANTATION DES BORNES | DISPOSIZIONE DEI TERMINALI
L
1, L2, L3: Mains supply, Spændings
f
orsyning, Hauptversorgung, Alimen-
tation principale, Alimentación de red,
A
limentazione
T
1, T2, T3: Motor supply, Motor
forsyning, Alimentación del motor,
A
limentation moteur, Motorver-
sorgung, Alimentazione motore,
A
1, A2: Control input, Kontrol input,
Entrada de control, Steuereingang,
E
ntrée de commande, Ingresso di
c
ontrollo
11 / 21: COM
12 / 22: Normally Closed (NC) | Normalt
l
ukket (NC) | Öffner (NC) | Normalement
fermé (NF) | Normalmente cerrado (NC) |
Normalmente Chiuso (NC)
1
4 / 24: Normally Open (NO) | Normalt
åben (NO) | Schlier (NO) | Normale-
m
ent ouvert (NO)| Normalmente abierto
(NA) | Normalmente Aperto (NO)
RSB...
M
3~
M
F
use
Contactor
Overload
I>>
RSB...
M
3~
K
A1
A2
L1 L2 L3
T1
T2 T3
K1
M
3~
A1
A2
L1 L2 L3
T1
T2 T3
M
3~
~
---
14
24
21
22
11
12
Alarm
Bypassed
14
24
21
22
11
12
Alarm
Bypassed
Motor
Protection
Relay
CONNECTION DIAGRAM | TILSLUTNINGSDIAGRAMMER | ANSCHLUSSDIAGRAMME | DIAGRAMME DE RACCORDEMENT | DIAGRAMA DE CONEXIONES | DIAGRAMMA DELLE CONNESSIONI
CONNECTION SPECIFICATIONS - FORBINDELSESSPECIFIKATIONER - TECHNISCHE DATEN DER ANSCHLÜSSE - CARACTÉRISTIQUES DES CONNEXIONS -
ESPECIFICACIONES DE CONEXIÓN - SPECIFICHE CONNESSIONI
*Note: Valid for line voltages up to 400V, *Bemærk: Gælder for driftsspænding op til 400V, *Hinweis: Gültig für Leitungsspannungen von bis zu 400V, *Nota: Applicable aux tensions lignes jusqu'à 400 V, *Nota: Válido para
tensiones de línea hasta 400V, *Nota: Valido per tensioni di linea fino a 400V
*Note / *Bemærk / *Hinweis / *Nota
24VAC/DC
&
110-400VAC
Line Conductors
L1, L2, L3, T1, T2, T3
According to EN60947-1:
Flexible with end sleeve (ferrule) 2 x (10 .... 50mm
2
)
Rigid (stranded) 2 x (10 .... 50mm
2
)
UL/ cUL rated data:
Rigid (stranded) 2 x (AWG 8 ... 1/0)
Stripping length: 16mm
12 Nm Max. M8
Secondary Conductors
A1, A2
According to EN60998
Flexible with end sleeve (ferrule) 0.5 .... 1.5mm
2
Rigid (solid) 0.5 .... 2.5mm
2
UL/ cUL rated data:
Rigid (solid or stranded) AWG 18 ... 10
Stripping length: 6.0mm
0.6Nm Max. M3
Auxiliary Conductors
11, 12, 14, 21, 22, 24
According to EN60998
Flexible with end sleeve (ferrule) 0.05 .... 1.5mm
2
Rigid (solid) 0.05 .... 2.5mm
2
UL/ cUL rated data:
Rigid (solid or stranded) AWG 30 ... 12
Stripping length: 6.0mm
0.8Nm Max. M3
Use 60/ 75˚C copper (CU) conductors
RSBT.D_instr_leaf(200112):RSBT_D_instr 30/01/2012 08:17 Page 1
“Suitable For Use On A Circuit Capable Of Delivering Not More Than
1
0,000 A rms Symmetrical Amperes, 480 Volts Maximum when Pro-
t
ected by Fuses.”
“Tests at 10,000 A were performed with Class J / RK5 fuses.”
“Use Fuses Only”.
“Adecuado para su uso en un circuito capaz de soportar hasta 10000
a
mperios eficaces (rms) simétricos, 480V de tensión máxima cuando
l
a protección sea por fusibles..”
“Se han realizado pruebas a 10000 A con fusibles Classe J / RK5.”
“Usar sólo fusibles.”
”Egnet til brug i kredsløb, der ikke leverer mere end 10000 A rms sym-
m
etriske ampere, maks. 480 volt, når de er beskyttet med sikringer.”
“Tests ved 10000 ampere blev udført med Classe J /RK5-sikringer”
“Benyt kun sikringer”.
« Convient à une utilisation sur un circuit capable d’émettre un maxi-
m
um de 10 000 A symétriques RMS, un maximum de 480 volts en cas
d
e protection par fusibles. »
« Des essais ont été effectués à 10000 A avec des fusibles Class J /
R
K5. »
« Utiliser uniquement des fusibles. »
„Geeignet für den Einsatz in einem Stromkreis, der bei Schutz durch
S
icherungen höchstens einen symmetrischen Strom von 10.000 A ef-
f
ektiv und eine Spannung von maximal 480 Volt liefern kann.“
„Die Prüfungen bei 10.000 A wurden mit Classe J / RK5-Sicherungen..
„Nur Sicherungen verwenden.“
“Utilizzabile in impianti con corrente massima di 10000Arms, e 480V
c
on l’utilizzo di fusibili di protezione”.
"Prove fino a 10000A con fusibili Classe J /RK5"
"Utilizzare solo fusibili".
MODE OF OPERATION - DRIFTSFORM - MODE DE FONCTIONNEMENT - BETRIEBSMODUS - MODO DE FUNCIONAMIENTO - MODALITÀ DI FUNZIONAMENTO
Normal Condi on
Mains Voltage
Green LED
Red LED
Control Voltage
Controller Output
Relay Contact (Bypassed)
R
elay Contact (Alarm)
1min
>= 1min
<
1min
1min
1min
Wrong Phase Sequence
2
L1L
1L2L
3L3L
Green LED
Red LED
Control Voltage
Controller Output
Relay Contact (Bypassed)
R
elay Contact (Alarm)
L
3
L
2
L1
Mains Voltage
Undervoltage Condi on
Green LED
Red LED
Control Voltage
Controller Output
Relay Contact (Bypassed)
Relay Contact (Alarm)
Mains Voltage
<5 =>ces 5sec
5mins recovery
1min
Overcurrent Condi on (during Ramping)
(>4x Ie during ramp-up)
G
reen LED
Red LED
Control Voltage
Controller Output
O
ver Current Condi
o
n
(
>4xIe)
R
elay Contact (Bypassed)
Relay Contact (Alarm)
Two Consecu ve
Alarms
1
min
5
mins
5mins recovery
1
min
5
mins
Alarm does not
self-recover
M
ains Voltage
switching OFF and re-applying power to the so starter
User Interven
on required to reset device by
5mins recovery
L
ED con
n
ues flashing
1
min
s
witching OFF and re-applying power to the so
s
tarter
Two Consecu
ve Alarms
5
mins
5mins recovery
T
wo Consecu
v
e Alarms
Alarm does not
self-recover
L
ED con
n
ues
flashing
1
min
1
min
5
mins
5mins recovery
1
min
Overvoltage Condi on
Green LED
Red LED
Control Voltage
Controller Output
Relay Contact (Bypassed)
Relay Contact (Alarm)
< 5sec
>= 5sec
Mains Voltage
1min
User Interven on required to reset device by
switching OFF and re-applying power to the so
starter
>1sec >1sec
1min
5mins
5mins recovery
1
min
5mins
5mins recovery >1sec
Two Consecu
ve Alarms
LED con
nues flashing
Alarm does not
self-
recover
5mins recovery
5 mins recovery
5mins recovery
Green LED
Red LED
Control Voltage
Controller Output
Relay Contact (Bypassed)
Relay Contact (Alarm)
Mains Voltage
Ramp-Up Time >1sec Alarm
Green LED
Red LED
Control Voltage
Controller Output
Over Current Condi
on
(>Ie + 15%)
Relay Contact (Bypassed)
Relay Contact (Alarm)
M
ains Voltage
Normal Condition
Overcurrent Condition (during ramping)
(>4x le during ramp-up)
W
rong Phase Sequence
Undervoltage condition
Overvoltage condition
Ramp-Up Time > 1 sec. alarm
Overcurrent condition (during bypass)
(
> le +15%)
Current/ Power Ratings - Strøm/ Nominel effekt - Nennstrom/-leistung -Caractéristiques de courant/puissance - Intensidad/Potencia nominal
Valutazioni Corrente / Potenza
Note (3): Motor kW ratings are provided as a reference. User shall al-
ways ensure that compressor operational current and overload current
of the compressor during starting does not exceed the rating of the soft-
starter being used.
N
ota (3): Les valeurs de puissance (kW) du moteur sont fournies à titre de
férence.L'utilisateur doit systématiquement s'assurer que le courant de
fonctionnement et de surcharge au démarrage du compresseur restent in-
rieurs aux caractéristiques de courant du marreur progressif utilisé.
Bemærk (3): Motor kW data er anført som reference. Brugeren skal altid
sikre, at kompressorens driftsstrøm og overbelastningsstrømmen i
kompressoren under start ikke overstiger belastningen for den anvendte
softstarter.
N
ota (3): Los valores en kW del motor son una referencia. El usuario
debe asegurarse siempre de que la intensidad nominal y la intensidad
de sobrecarga del compresor durante el arranque no superen los
valores establecidos del arrancador suave.
Hinweis (3): Die Leistungsangaben für Motoren (kW-Werte) dienen nur
zu Informationszwecken. Der Anwender muss in jedem Fall selbst
sicherstellen, dass der Betriebsstrom des Kompressors und der
Überlaststrom beim Start die Nennleistung des verwendeten
S
anftstartgeräts nicht überschreitet.
N
ota (3): La potenza del motore in kW è fornita come riferimento. L’u-
tente deve assicurarsi che la corrente di funzionamento standard è di
sovraccarico del compressore durante l'avvio non superino il rating del
softstarter in uso.
NOTE: "For use in a circuit where devices or system, including filters or
air gaps, are used to control overvoltages at the maximum rated impulse
withstand voltage peak of 4.0kV. Devices or system shall be evaluated
using the requirements in the standard for Transient Voltage Surge Sup-
pressors, UL 1449 and shall also withstand the available short circuit
current in accordance with UL 1449"
NOTE: "Pour une utilisation dans un circuit les dispositifs ou les sys-
tèmes, y compris les filtres ou les lacunes de l'air, sont utilisés pour con-
trôler les surtensions à l'impulsion nominale maximale supporter les pics
de tension de 4.0kV. Dispositifs ou système est évalué selon les exi-
gences de la norme pour Transitoire Voltage Surge Suppressor, UL 1449
et doit également résister aux courts-circuits disponibles en cours con-
formément à la norme UL 1449"
HINWEIS: "Für den Einsatz in einem Stromkreis oder bei denen Geräte,
einschließlich Filter oder Luftspalte, verwendet werden, um Überspan-
nungen an der maximalen Impulskontrolle Stehwechselspannung Höch-
ststand von 4,0 kV. Devices oder System werden anhand der
Anforderungen der Norm für Transient Spannung Überspan-
nungsableiter, UL 1449 und gilt auch standhalten verfügbar Kurz-
schlussstrom nach UL 1449 "
BERK: "Til brug i et kredsløb, hvor udstyr eller system, herunder fil-
tre eller luft huller, bruges til at kontrollere overspænding ved maksimal
Mærkeimpuls-holdespænding toppen af 4.0kV. Enheder eller system
skal evalueres ved hjælp af kravene i standarden for Transient Voltage
overspændingsbeskyttere, UL 1449 og skal også kunne mods de
tilgængelige kortslutningsstrømmen i overensstemmelse med UL 1449"
NOTA: "Para uso en un circuito donde los equipos o el sistema,
incluyendo filtros o separación física, se utilizan para el control de
sobretensiones con picos ximos de tensión de hasta 4,0 kV. Los
equipos o el sistema deben ser evaluados bajo los requisitos de la
norma para supresores de picos de tensión transitorios, UL 1449 y
deben soportar la intensidad de cortocircuito disponible según UL 1449."
NOTA: "Per l'uso in un circuito in cui i dispositivi o il sistema, compresi
i filtri o vuoti d'aria, vengono utilizzati per controllare l'impulso a sovraten-
sioni nominale massimo sopportare picchi di tensione di 4.0kV. Dispos-
itivi o il sistema deve essere valutato in base ai requisiti della norma per
Transient tensione di sovracorrente, UL 1449 e deve anche sopportare
la corrente di corto circuito disponibili a norma UL 1449 "
RSB.4855CV. RSB.4870CV. RSB.4895CV.
Type of coordination 1 -
UL rated short circuit current
10 kA when protected with
J class fuses up to 60A
10 kA when protected with
J class fuses up to 70A
10 kA when protected with
RK5 class fuses up to 100A
Type of coordination 2 -
Rated short circuit current
10 kA when protected by semiconductor fuses 100A,
class URD.Art. no. 6.900 CPURD 22 x 58 / 100
10 kA when protected by semiconductor fuses 100A,
class URD.Art. no. 6.900 CPURD 22 x 58 / 100
10 kA when protected by semiconductor fuses 160A,
Class URS/URQ, Art. No.
160Ac660VAC 27 x 601/ 6.9xxCP URQ 27 x 60 / 160
Assigned compressor rating @ 40ºC/UL rating @ 40ºC
(3)
IEC Rated operational current Ie (AC-53b)
5
5A
7
0A
9
5A
220 - 240VAC 15kW (20HP) 20kW (25HP) 22kW (30HP)
3
80 - 415VAC
2
2kW (30HP)
3
0kW (40HP)
4
5kW (50HP)
440 - 480VAC 30kW (40HP) 37kW (50HP) 55kW (75HP)
DIN RAIL ADAPTER VERSION SURFACE MOUNT ADAPTER VERSION
120
150
120
80
77
147
170
190
206
170
DIMENSIONS (MM) | MÅL (MM) | DIMENSIONES (MM) | DIMENSIONS (MM) |ABMESSUNGEN (MM) | DIMENSIONI (MM)
DIN RAIL adapter Version, DIN-SKINNE adapter version,
Version mit DIN-Schienenadapter, Version adaptateur pour rail DIN ,
Versión con adaptador a carril DIN, Versione con adattatore per guida DIN
Panel mount Adapter Version, Tavlemonteret adapter version,
Version mit Schalttafeladapter, Version adaptateur pour montage en tableau,
Versión con adaptador para montaje en panel, Versione a pannello
SHORT CIRCUIT PROTECTION (ACCORDING TO EN/IEC 60947-4-2 AND UL508) | PROTECCIÓN CONTRA CORTOCIRCUITOS (SEGÚN EN/IEC 60947-4-2 Y UL508) |
KORTSLUTNINGSBESKYTTELSE (IHT. EN/IEC 60947-4-2 OG UL508) | PROTECTION CONTRE LES COURTS-CIRCUITS (CONFORMENT À EN/IEC 60947-4-2 ET À
UL508) KURZSCHLUSSSCHUTZ (GEMÄSS EN/IEC 60947-4-2 UND UL508) | PROTEZIONE DA CORTO CIRCUITO(SECONDO LE NORME EN / IEC 60947-4-2 E UL508)
LED STATUS INDICATION - LED STATUSINDIKATOR - LED D'INDICATION D'ÉTAT - LED DE INDICACIÓN DE ESTADO - LED-STATUSANZEIGE - LED DI DIAGNOSTICA
State Idle Bypass Alarm Recovery from Alarm Recovery time between starts
Green LED ON ON ON ON Flashing
Red LED OFF OFF Flashing (acc. to alarm) Flashing OFF
RSBT.D_instr_leaf(200112):RSBT_D_instr 30/01/2012 08:17 Page 2

Transcripción de documentos

RSBT.D_instr_leaf(200112):RSBT_D_instr 30/01/2012 08:17 Page 1 ATTENTION BEMÆRK ACHTUNG 1. To prevent electrical shock, disconnect from power source before installing or servicing. 1. For at undgå elektrisk stød, frakobl fra strømkilde før installation og servicering. 2. The bypass relays in the main circuit may be in an undefined switching state due to handling during shipping. Before first operation of the product, apply the supply voltage to set the bypass relays to a defined state. Unintentional operation of the compressor may result if this operation is not performed. 2. By-pass relæerne i hovedafbryderen kan stå i en ikke nærmere defineret indstilling på grund af håndtering under forsendelse. Før produktet anvendes første gang, skal by-pass relæerne indstilles korrekt til netspændingen. Hvis denne handling ikke udføres, kan der opstå utilsigtet drift med kompressoren. 3. Unauthorised opening of the product will void warranty. 3. Uautoriseret åbning af produktet vil ugyldiggøre garantien. 1. Trennen Sie das Gerät vor der Installation und vor Wartungsvorgängen von der Stromversorgung, um das Risiko eines elektrischen Schlags zu vermeiden. 2. Die Kurzschlussrelais im Hauptstromkreis befinden sich aufgrund der Handhabung beim Transport möglicherweise in einem undefinierten Schaltzustand. Legen Sie daher vor der ersten Inbetriebnahme des Produkts die Versorgungsspannung an, um die Kurzschlussrelais in einen definierten Zustand zu versetzen. Wenn dieser Schritt nicht durchgeführt wird, kann dies zu unerwünschtem Einschalten des Kompressors führen. 4. “For use in Pollution Degree 3 Environment”. 4. ”Til brug i miljø med forureningsgrad 3”. 3. Unerlaubtes Öffnen des Produkts führt zum Verlust der Garantie. 5. The device should be configured as indicated in the connection diagram. Do not operate the product before all connections are completed. 5. Dette udstyr bør konfigureres som angivet i tilslutningsdiagrammet. Sæt ikke produktet i drift før alle tilslutninger er foretaget. 6. The softstarter does not have any integrated short circuit and overload protection. These must be procured separately. 6. Softstarteren har ingen indbygget beskyttelse mod kortslutning og overbelastning. Disse skal anskaffes separat. 7. Excessive lengths of cabling should be avoided in view of EMC considerations. 7. Overdreven længde på kabler bør undgås under hensyntagen til EMC (elektromagnetisk kompatibilitet). 8. The RSBD and RSBT softstarter series has been designed for Class A equipment. Use of the product in domestic environments may cause radio interference. 9. The opening of the branch-circuit protective device may be an indication that a fault has been interrupted. To reduce the risk of fire or electric shock, current-carrying parts and other components of the controller should be examined and replaced if damaged. If burnout of the current element of an overload relay occurs, the complete overload replay must be replaced. 10. For the Canadian application, the control terminals A1, A2 of the RSB. devices shall be supplied by a secondary circuit where power is limited by a transformer, rectifier, voltage divider, or similar device that derives power from a primary circuit, and where the short-circuit limit between conductors of the secondary circuit or between conductors and ground is 1500 VA or less. The short-circuit volt ampere limit is the product of the open circuit voltage and the short circuit ampere. 8. RSBD og RSBT softstarterserien er fremstillet som klasse A udstyr. Anvendelse af produktet i beboelsesmiljøer kan skabe radiointerferens. 9. Åbningen af et kredsløbet beskyttende enhed kan være et tegn på at en fejl er blevet afbrudt. For at mindske risikoen for brand eller elektrisk stød, skal strø førende dele og andre komponenter i enheden undersøges og udskiftes hvis beskadiget. Hvis ”Burnout” af et strøm-element i et overbelastningsrelæet er brændt over, skal hele overbelastningsrelæet udskiftes 10. "Til brug i Canada skal styreklemmerne A1, A2 i RSB.-enhederne suppleres med et sekundært kredsløb, hvor strømmen begrænses med en transformer, strømretter, spændingsdeler eller lignende enhed, der afleder strømmen fra et primært kredsløb, og hvor kortslutningsgrænsen mellem ledere af det sekundære kredsløb eller mellem ledere og jord er 1500 VA eller mindre. Volt-amperekortslutningsgrænsen er produktet af den åbne kredsløbsspænding og kortspændingsampere” 5. Das Gerät muss wie im Anschlussdiagramm angegeben konfiguriert werden. Schalten Sie das Produkt nicht ein, bevor alle Verbindungen hergestellt sind. 7. Übermäßig große Kabellängen sollten aus Gründen der Störfestigkeit vermieden werden. 8. Die Produktreihe der RSBD- und RSBT-Sanftstartgeräte wurde für Geräte der Klasse A entwickelt. Der Einsatz des Produkts in Wohnumgebungen kann Funkstörungen hervorrufen. 10. Bei Anwendungen in Kanada sind die Steuerungsklemmen A1, A2 der RSB.Geräte über einen sekundären Stromkreis zu versorgen, in dem die Leistung durch einen Transformator, Gleichrichter, Spannungstrenner oder ein ähnliches Gerät, das aus einem Primärkreis mit Strom versorgt wird, begrenzt ist und in dem der Kurzschlussgrenzwert zwischen Leitern des sekundären Stromkreises oder zwischen Leitern und Erde höchstens 1500 VA beträgt. Der Volt-AmpereKurzschlussgrenzwert ist das Produkt aus der Leerlaufspannung und dem Kurzschlussstrom ATTENZIONE 1. Antes de instalar o revisar el equipo, desconéctelo para evitar descargas eléctricas. 1. Per evitare scosse elettriche, scollegare dalla corrente prima di installare o la manutenzione. 2. La manutention en cours de transport peut positionner les relais de bipasse du circuit principal dans un état de commutation indéfini. Avant mise en service initiale, mettre le produit sous tension afin de positionner les relais de bipasse dans un état de commutation défini. Effectuer cette opération impérativement sous peine de provoquer un fonctionnement intempestif du compresseur. 2. Los relés de bypass del circuito principal pueden estar en un estado indefinido de conexión debido al transporte. Antes de conectar el equipo, aplique la alimentación para que los relés de bypass estén en su posición correcta. Si no se realiza esta operación, puede que el compresor funcione incorrectamente. 2. I relè di bypass nel circuito principale può essere in uno stato di commutazione indefinito a causa di sollecitazioni durante la spedizione. Alla prima operazione del prodotto, applicare la tensione di alimentazione per impostare i relè di bypass in uno stato definito. Il compressore può attivarsi in maniera accidentale se questa operazione non viene eseguita. 6. Le démarreur progressif n'intègre aucune protection contre les courts-circuits/la surcharge.Ces protections doivent être approvisionnées séparément. 7. Éviter les longueurs excessives de câblage afin de respecter les normes de compatibilité électromagnétique. 8. La série des démarreurs progressifs RSBD et RSBT a été conçu pour les équipements de Classe A.L'utilisation de ce produit dans les environnements résidentiels peut provoquer des interférences radio magnétiques. 9. L'ouverture du dispositif de protection de la dérivation peut signifier qu'il s'est produit une défaillance. Pour diminuer le risque d'incendie ou de choc électrique, vérifier les pièces et les autres composants sous tension du contrôleur et les remplacer s'ils sont endommagés. En cas de claquage de l'élément de courant d'un relais de surcharge, remplacer le relais de surcharge au complet 10. « Pour les applications au Canada, les bornes de contrôle A1, A2 des appareils RSB. seront alimentées par un circuit secondaire dans lequel le courant est limité par un transformateur, un redresseur, un réducteur de tension, ou un appareil similaire dérivant du courant d’un circuit primaire et où la limite de court-circuit entre les conducteurs du circuit secondaire ou entre les conducteurs et la terre est égale ou inférieure à 1500 VA. La limite en voltampère du court-circuit est le produit de la tension du circuit ouvert et des ampères du court-circuit. » 3. La apertura del equipo sin autorización por parte del fabricante anula la garantía. 3. L'apertura non autorizzata del prodotto renderà nulla la garanzia. 4. “Para uso en entornos con grado de contaminación 3” 4. "Per l'uso in ambiente grado di inquinamento 3". 5. El equipo debe configurarse como se indica en el diagrama de conexión. El equipo no debe conectarse hasta que se hayan realizado todas las conexiones. 5. Il dispositivo deve essere configurato come indicato nello schema di collegamento. Non utilizzare il prodotto prima che tutti i collegamenti sono completati. 6. El arrancador suave no tiene protección contra cortocircuitos ni sobrecarga. Deben instalarse independientemente. 6. Il soft starter non ha nessuna protezione da cortocircuito e sovraccarico. Questi devono essere installati a parte. 7. Hay que evitar una longitud excesiva de los cables, con el fin de cumplir con los requisitos de compatibilidad electromagnética. 7. I cavi non devono avere una lunghezza eccessiva per rispettare le richieste EMC. 8. Las series RSBD y RSBT de arrancadores suaves se han diseñado como equipos Clase A. Su uso en instalaciones domésticas puede causar radio interferencias. 9. La apertura del equipo de protección de uno de los circuitos puede ser una indicación de que el fallo ha sido interrumpido. Para reducir el riesgo de incendio o descarga eléctrica, las partes conductoras de corriente y otros componentes del controlador deben ser examinadas y sustituidas, si están dañadas. Si hay un chispazo en el relé de sobrecarga, hay que sustituirlo por completo. 10. "Para aplicaciones en Canadá, los terminales de control A1, A2 del controlador RSBx deben alimentarse con un circuito secundario donde la potencia está limitada por un transformador, rectificador, divisor de tensión o similar, que deriva potencia de un circuito primario y donde el límite de cortocircuito entre conductores del circuito secundario o entre conductores y tierra es de 1500 VA o menor. El límite VA de cortocircuito se obtiene multiplicando la tensión de circuito abierto y los amperios de cortocircuito." A1, A2: Control input, Kontrol input, Entrada de control, Steuereingang, Entrée de commande, Ingresso di controllo 9. Das Öffnen der Schutzeinrichtung des Stromzweigs kann ein Hinweis darauf sein, dass ein Fehlerzustand unterbrochen wurde. Um die Brandgefahr und die Gefahr elektrischer Schläge zu reduzieren, müssen stromführende Bauteile und andere Komponenten des Controllers überprüft und ersetzt werden, falls sie beschädigt sind. Wenn beim Stromelement des Überstromrelais Abbrand auftritt, muss das gesamte Überstromrelais ausgetauscht werden. ATENCIÓN 5. Configurer le dispositif comme indiqué dans le schéma des connexions.Ne pas utiliser le produit tant que toutes les connexions ne sont pas réalisées. T1, T2, T3: Motor supply, Motor forsyning, Alimentación del motor, Alimentation moteur, Motorversorgung, Alimentazione motore, 6. Das Sanftstartgerät besitzt keinen integrierten Kurzschluss- und Überlastschutz. Dieser muss gesondert bereitgestellt werden. 1. Avant toute installation ou intervention, déconnecter la source d'alimentation pour éviter tout risque d'électrocution. 4. « Pour exploitation en environnement de degré de pollution 3 ». L1, L2, L3: Mains supply, Spændings forsyning, Hauptversorgung, Alimentation principale, Alimentación de red, Alimentazione 4. „Für die Verwendung in einer Umgebung mit dem Verschmutzungsgrad 3“. ATTENTION 3. L'ouverture non autorisée du produit annule la garantie. TERMINAL DIAGRAM | KLEMMEDIAGRAM | DIAGRAMA DE TERMINALES | BELEGUNGSPLAN | IMPLANTATION DES BORNES | DISPOSIZIONE DEI TERMINALI RSBD & RSBT series 8. Le serie RSBD e RSBT sono state progettate per sistemi in Classe A. L'uso del prodotto in ambienti domestici può causare interferenze radio. 9. L'apertura del circuito di protezione può essere un'indicazione che il guasto è stato interrotto. Per ridurre il rischio di incendi o scosse elettriche, le parti sotto carico e gli altri componenti del regolatore devono essere esaminate e sostituite se danneggiate. Se il relè di sovraccarico si interrompe, il relè deve essere sostituito. 11 / 21: COM INST RSBT_D 251111 12 / 22: Normally Closed (NC) | Normalt lukket (NC) | Öffner (NC) | Normalement fermé (NF) | Normalmente cerrado (NC) | Normalmente Chiuso (NC) 7680465 Mounting and Operating Instructions Monterings- og driftsinstruktioner 14 / 24: Normally Open (NO) | Normalt åben (NO) | Schließer (NO) | Normalement ouvert (NO)| Normalmente abierto (NA) | Normalmente Aperto (NO) Montage- und Betriebsanweisungen Instructions de montage et de fonctionnement Instrucciones de montaje y funcionamiento Istruzioni operative e di montaggio DIN RAIL MOUNTING - DIN-SKINNE MONTERING - MONTAGE SUR RAIL DIN - MONTAJE EN CARRIL DIN - BEFESTIGUNG AUF DIN-HUTSCHIENE MONTAGGIO SU GUIDA DIN ASSEMBLY INSTRUCTIONS - MONTERINGSINSTRUKTIONER - INSTRUCTIONS DE MONTAGE - INSTRUCCIONES DE MONTAJE -MONTAGEANWEISUNGEN - ISTRUZIONI DI MONTAGGIO Panel Mounting - Tavlemontering - Montage en tableau - Montaje en panel - Befestigung auf Schalttafel - Montaggio a pannello 4 x self-tapping screws 4.2mm (provided), 4 x selvskærende skruer 4,2 mm (medfølger), 4 x vis auto-taraudeuses 4,2mm (fournies),4 tornillos autorroscantes de 4,2mm (incluidos), 4 × Schneidschrauben 4,2 mm (im Lieferumfang enthalten),4 x viti autofilettanti 4,2 millimetri (in dotazione) 1 1 10. "Per il mercato canadese, i terminali di controllo A1, A2, dei dispositivi RSB. devono essere alimentati da un circuito secondario in cui la potenza è limitata da uno dei seguenti sistemi, trasformatore, raddrizzatore, partitore di tensione, o un dispositivo analogo che deriva l’energia da un circuito primario, e dove i cortocircuiti sono limitati tra i conduttori del circuito secondario o tra i conduttori e la terra per tensioni di 1500 VA o inferiori. Il limite della corrente di corto circuito è dato dal sistema della tensione a circuito aperto e gli ampere di corto circuito" Din Rail 2 Din Rail 2 Mounting: Push the unit in and down onto the upper rail edge. Ensure that both clips are in place on the rail.Push the unit inwards in the direction of the rail until the unit “snaps” into place. IMPORTANT VIGTIGT WICHTIG Carlo Gavazzi is not to be held responsible for incorrect product operation or damages resulting from improper use of the product and/or use of the product outside its specified operating limits. Products, specifications and data in this document are subject to change without notice. The product is intended to be used by qualified personnel at their own discretion and risk. Should you require information about installation, operation or maintenance of the product that is not covered in this document you should refer the matter to an authorized Carlo Gavazzi representative. The information in this document is not considered binding on any product warranty. Carlo Gavazzi kan ikke holdes ansvarlig for ukorrekt anvendelse af produktet eller skader opstået ved ukorrekt brug og/eller efter brug af produktet til andet end de specificerede driftsbestemmelser. Produkter, specifikationer og data i dette dokument kan ændres uden varsel. Produktet er beregnet til anvendelse af uddannet personale efter eget skøn og risiko. Hvis du har brug for oplysninger om installation, drift eller vedligeholdelse af produktet, der ikke er dækket af nærværende dokument, bør du rette henvendelse til en autoriseret repræsentant fra Carlo Gavazzi. Informationen i nærværende dokument anses ikke for bindende for nogen produktgaranti. Carlo Gavazzi übernimmt keine Haftung für fehlerhafte Bedienung des Produkts sowie für Schäden, die aus unsachgemäßer Verwendung des Produkts und/oder dem Einsatz des Produkts außerhalb der angegebenen Grenzbetriebsdaten resultieren. Die in diesem Dokument beschriebenen Produkte, Spezifikationen und technischen Daten können jederzeit ohne vorherige Ankündigung geändert werden. Das Produkt ist nur für die Verwendung durch qualifiziertes Fachpersonal nach eigenem Ermessen und auf eigenes Risiko vorgesehen. Wenn Sie Informationen zur Installation, zum Betrieb oder zur Wartung des Produkts benötigen, die nicht in dieser Anleitung enthalten sind, wenden Sie sich mit Ihrer Frage an einen autorisierten Vertriebspartner von Carlo Gavazzi. Die Informationen in diesem Dokument sind nicht bindend hinsichtlich der Produktgewährleistung. IMPORTANT IMPORTANTE IMPORTANTE Carlo Gavazzi ne peut être tenu responsable d'une exploitation incorrecte du produit ou d'avaries résultant d'une utilisation incorrecte du produit et/ou hors des tolérances de fonctionnement spécifiées. Les produits, caractéristiques et données décrites dans le présent document peuvent changer sans préavis. L'utilisation de ce produit est destinée à un personnel qualifié qui l'exploite à sa guise et à ses propres risques. Pour plus amples informations concernant l'installation, le fonctionnement ou la maintenance du produit et ne figurant pas dans ce document, consulter un concessionnaire agréé Carlo Gavazzi. Les informations contenues dans ce document ne constituent une obligation de garantie de quelconque nature du produit. Carlo Gavazzi no se responsabiliza del uso incorrecto del producto o de los daños ocasionados por un uso incorrecto del mismo y /o por el uso del producto sin tener en cuenta los límites de funcionamiento especificados. Los equipos, especificaciones y datos recogidos en este documento están sujetos a cambios sin previo aviso. El equipo debe usarse por personal cualificado y bajo su responsabilidad y riesgo. En caso de necesitar más información sobre la instalación, funcionamiento o mantenimiento del equipo que no se refleje en este documento, póngase en contacto con un distribuidor autorizado de Carlo Gavazzi. La información detallada en este documento no se considera vinculante en ninguna garantía del producto. Carlo Gavazzi non può essere ritenuta responsabile per un malfunzionamento o danni derivanti da un uso improprio del prodotto e/o utilizzo del prodotto al di fuori dei suoi limiti operativi specificati. Prodotti, specifiche e dati in questo documento sono soggette a modifiche senza preavviso.Il prodotto è destinato ad essere utilizzato da personale qualificato a propria discrezione e rischio. Se avete bisogno di informazioni su installazione, funzionamento o manutenzione del prodotto non riportate in questo documento, dovete fare riferimento al personale autorizzato Carlo Gavazzi. Le informazioni contenute in questo documento non sono considerate vincolanti per alcuna garanzia sul prodotto. Montage: Appuyer sur le module vers le bas en le repoussant sur le rail supérieur.Constater que les deux agrafes sont en place sur le rail. Appuyer sur le module vers l'intérieur dans la direction du rail jusqu'à ce qu'à agrafage en position. Montering: Tryk enheden ind og ned på øverste skinnekant. Sørg for, at begge clips står korrekt på skinnen. Skub enheden indad i retning mod skinnen, indtil enheden “klikker” på plads. 4 x M6 screws (not provided) 4 x M6 skruer (medfølger ikke) 4 x vis 6 (non fournies) 4 tornillos M6 (no incluidos) 4 × M6-Schrauben (nicht im Lieferumfang enthalten) 4 x M6 viti (non fornite) Montaje: Presionar el equipo de arriba abajo, fijando primero la parte superior del carril. Asegúrese de que ambos clips están bien sujetos. Empuje el equipo en la dirección del carril hasta que quede encajado en su sitio. Einbau: Stecken Sie das Gerät ein, und drücken Sie es auf die obere Kante der Schiene. Überzeugen Sie sich davon, dass beide Klammern ordnungsgemäß auf der Schiene sitzen. Drücken Sie das Gerät in Richtung der Schiene nach innen, bis es in der Schiene einrastet. 1 x M5 screw (provided) 1 x M5 skrue (medfølger) 1 x vis M5 (fournie) 1 tornillo M5 (incluido) 1 × M5-Schraube (im Lieferumfang enthalten) 1 x vite M5 (in dotazione) Montaggio: Spingere l'unità verso il basso sul bordo superiore della guida DIN. Assicurarsi che entrambe le clip siano sulla guida. Spingere verso l'interno unità in direzione del binario fino a quando l'unità "si blocca" in posizione. Dismounting: Press the unit down and at the same time, pull the unit outwards from the bottom side. Slightly lift the unit up to disengage the clips from the rail edge. Afmontering: Tryk enheden ned og træk samtidig enheden udad fra undersiden. Løft enheden en smule op for at frakoble clipsene fra skinnekanten. Démontage: Appuyer sur le module vers le bas tout en le tirant vers l'extérieur par sa partie inférieure. Soulever légèrement le module pour dégager les agrafes du bord du rail. Desmontaje: Presionar el equipo hacia abajo y al mismo tiempo, tirar del equipo desde abajo. Levante con cuidado el equipo para desengancharlo de los clip desde el final del carril. Abbau: Drücken Sie das Gerät nach unten, und ziehen Sie es gleichzeitig an der Unterkante von der Schiene weg. Heben Sie das Gerät leicht an, um die Klammern von der Kante der Schiene zu lösen. Smontaggio: Premere l'unità verso il basso e, allo stesso tempo, tirare l'unità verso l'esterno dal lato inferiore. Sollevare leggermente l'unità fino a sganciare le clip dalla guida DIN CONNECTION DIAGRAM | TILSLUTNINGSDIAGRAMMER | ANSCHLUSSDIAGRAMME | DIAGRAMME DE RACCORDEMENT | DIAGRAMA DE CONEXIONES | DIAGRAMMA DELLE CONNESSIONI *Note / *Bemærk / *Hinweis / *Nota CONNECTION SPECIFICATIONS - FORBINDELSESSPECIFIKATIONER - TECHNISCHE DATEN DER ANSCHLÜSSE - CARACTÉRISTIQUES DES CONNEXIONS ESPECIFICACIONES DE CONEXIÓN - SPECIFICHE CONNESSIONI Line Conductors L1, L2, L3, T1, T2, T3 According to EN60947-1: Flexible with end sleeve (ferrule) Rigid (stranded) UL/ cUL rated data: Rigid (stranded) 2 x (10 .... 50mm2) 2 x (10 .... 50mm2) L1 Stripping length: 16mm L1 L3 L2 L3 24 Fuse 12 Nm Max. L2 Motor 24 Protection 21 Relay M8 2 x (AWG 8 ... 1/0) Bypassed A1 21 A1 Bypassed 22 22 Secondary Conductors A1, A2 Auxiliary Conductors 11, 12, 14, 21, 22, 24 Use 60/ 75˚C copper (CU) conductors According to EN60998 Flexible with end sleeve (ferrule) Rigid (solid) Contactor 0.5 .... 1.5mm2 0.5 .... 2.5mm2 UL/ cUL rated data: Rigid (solid or stranded) AWG 18 ... 10 According to EN60998 Flexible with end sleeve (ferrule) Rigid (solid) 0.05 .... 1.5mm2 0.05 .... 2.5mm2 UL/ cUL rated data: Rigid (solid or stranded) AWG 30 ... 12 K Stripping length: 6.0mm K1 I>> 14 A2 ~ --- 24VAC/DC & 110-400VAC 14 A2 Alarm 11 Alarm 11 12 0.6Nm Max. 12 Overload M3 T1 RSB... Stripping length: 6.0mm 0.8Nm Max. M3 M 3~ T2 T3 T1 T2 T3 RSB... MM 3~ M 3~ M 3~ *Note: Valid for line voltages up to 400V, *Bemærk: Gælder for driftsspænding op til 400V, *Hinweis: Gültig für Leitungsspannungen von bis zu 400V, *Nota: Applicable aux tensions lignes jusqu'à 400 V, *Nota: Válido para tensiones de línea hasta 400V, *Nota: Valido per tensioni di linea fino a 400V RSBT.D_instr_leaf(200112):RSBT_D_instr 30/01/2012 08:17 Page 2 MODE OF OPERATION - DRIFTSFORM - MODE DE FONCTIONNEMENT - BETRIEBSMODUS - MODO DE FUNCIONAMIENTO - MODALITÀ DI FUNZIONAMENTO Normal CondiCondition on Normal Overcurrent Condi on (during Ramping) (during ramping) Overcurrent Condition (>4x Ie during ramp-up) (>4x le during ramp-up) Mains Voltage Mains Voltage Green LED SHORT CIRCUIT PROTECTION (ACCORDING TO EN/IEC 60947-4-2 AND UL508) | PROTECCIÓN CONTRA CORTOCIRCUITOS (SEGÚN EN/IEC 60947-4-2 Y UL508) | KORTSLUTNINGSBESKYTTELSE (IHT. EN/IEC 60947-4-2 OG UL508) | PROTECTION CONTRE LES COURTS-CIRCUITS (CONFORMÉMENT À EN/IEC 60947-4-2 ET À UL508) KURZSCHLUSSSCHUTZ (GEMÄSS EN/IEC 60947-4-2 UND UL508) | PROTEZIONE DA CORTO CIRCUITO(SECONDO LE NORME EN / IEC 60947-4-2 E UL508) User Interven on required to reset device by switching OFF and re-applying power to the so starter Type of coordination 1 UL rated short circuit current RSB.4855CV. RSB.4870CV. RSB.4895CV. 10 kA when protected with J class fuses up to 60A 10 kA when protected with J class fuses up to 70A 10 kA when protected with RK5 class fuses up to 100A Green LED 1min 1min 1 min 1 min Red LED 1min Red LED 5mins 5mins LED con nues flashing 5mins recovery 5mins recovery Alarm does not self-recover Type of coordination 2 Rated short circuit current 10 kA when protected by semiconductor fuses 100A, 10 kA when protected by semiconductor fuses 100A, class URD. Art. no. 6.900 CP URD 22 x 58 / 100 class URD. Art. no. 6.900 CP URD 22 x 58 / 100 Control Voltage Control Voltage Controller Output < 1min >= 1min Controller Output Over Current Condi on (>4xIe) 1 min Relay Contact (Bypassed) Two Consecu ve Alarms • “Suitable For Use On A Circuit Capable Of Delivering Not More Than 10,000 A rms Symmetrical Amperes, 480 Volts Maximum when Protected by Fuses.” • “Tests at 10,000 A were performed with Class J / RK5 fuses.” • “Use Fuses Only”. • ”Egnet til brug i kredsløb, der ikke leverer mere end 10000 A rms symmetriske ampere, maks. 480 volt, når de er beskyttet med sikringer.” • “Tests ved 10000 ampere blev udført med Classe J /RK5-sikringer” • “Benyt kun sikringer”. • “Adecuado para su uso en un circuito capaz de soportar hasta 10000 amperios eficaces (rms) simétricos, 480V de tensión máxima cuando la protección sea por fusibles..” • “Se han realizado pruebas a 10000 A con fusibles Classe J / RK5.” • “Usar sólo fusibles.” • « Convient à une utilisation sur un circuit capable d’émettre un maximum de 10 000 A symétriques RMS, un maximum de 480 volts en cas de protection par fusibles. » • « Des essais ont été effectués à 10000 A avec des fusibles Class J / RK5. » • « Utiliser uniquement des fusibles. » Relay Contact (Bypassed) Relay Contact (Alarm) Relay Contact (Alarm) Wrong Phase Sequence User Interven on required to reset device by switching OFF and re-applying power to the so starter L3 L2 L1 L2 L1 L2 L3 L3 L1 Green LED Red LED Green LED 5mins 5mins LED con nues flashing Two Consecu ve Alarms Controller Output Controller Output Two Consecu ve Alarms Relay Contact (Bypassed) Relay Contact (Alarm) 70A 95A 220 - 240VAC 15kW (20HP) 20kW (25HP) 22kW (30HP) 440 - 480VAC 30kW (40HP) 37kW (50HP) 55kW (75HP) 22kW (30HP) 30kW (40HP) 45kW (50HP) Note (3): Motor kW ratings are provided as a reference. User shall always ensure that compressor operational current and overload current of the compressor during starting does not exceed the rating of the softstarter being used. Bemærk (3): Motor kW data er anført som reference. Brugeren skal altid sikre, at kompressorens driftsstrøm og overbelastningsstrømmen i kompressoren under start ikke overstiger belastningen for den anvendte softstarter. Hinweis (3): Die Leistungsangaben für Motoren (kW-Werte) dienen nur zu Informationszwecken. Der Anwender muss in jedem Fall selbst sicherstellen, dass der Betriebsstrom des Kompressors und der Überlaststrom beim Start die Nennleistung des verwendeten Sanftstartgeräts nicht überschreitet. Nota (3): Les valeurs de puissance (kW) du moteur sont fournies à titre de référence.L'utilisateur doit systématiquement s'assurer que le courant de fonctionnement et de surcharge au démarrage du compresseur restent inférieurs aux caractéristiques de courant du démarreur progressif utilisé. Nota (3): Los valores en kW del motor son una referencia. El usuario debe asegurarse siempre de que la intensidad nominal y la intensidad de sobrecarga del compresor durante el arranque no superen los valores establecidos del arrancador suave. Nota (3): La potenza del motore in kW è fornita come riferimento. L’utente deve assicurarsi che la corrente di funzionamento standard è di sovraccarico del compressore durante l'avvio non superino il rating del softstarter in uso. NOTE: "For use in a circuit where devices or system, including filters or air gaps, are used to control overvoltages at the maximum rated impulse withstand voltage peak of 4.0kV. Devices or system shall be evaluated using the requirements in the standard for Transient Voltage Surge Suppressors, UL 1449 and shall also withstand the available short circuit current in accordance with UL 1449" HINWEIS: "Für den Einsatz in einem Stromkreis oder bei denen Geräte, einschließlich Filter oder Luftspalte, verwendet werden, um Überspannungen an der maximalen Impulskontrolle Stehwechselspannung Höchststand von 4,0 kV. Devices oder System werden anhand der Anforderungen der Norm für Transient Spannung Überspannungsableiter, UL 1449 und gilt auch standhalten verfügbar Kurzschlussstrom nach UL 1449 " NOTA: "Para uso en un circuito donde los equipos o el sistema, incluyendo filtros o separación física, se utilizan para el control de sobretensiones con picos máximos de tensión de hasta 4,0 kV. Los equipos o el sistema deben ser evaluados bajo los requisitos de la norma para supresores de picos de tensión transitorios, UL 1449 y deben soportar la intensidad de cortocircuito disponible según UL 1449." NOTE: "Pour une utilisation dans un circuit où les dispositifs ou les systèmes, y compris les filtres ou les lacunes de l'air, sont utilisés pour contrôler les surtensions à l'impulsion nominale maximale supporter les pics de tension de 4.0kV. Dispositifs ou système est évalué selon les exigences de la norme pour Transitoire Voltage Surge Suppressor, UL 1449 et doit également résister aux courts-circuits disponibles en cours conformément à la norme UL 1449" BEMÆRK: "Til brug i et kredsløb, hvor udstyr eller system, herunder filtre eller luft huller, bruges til at kontrollere overspænding ved maksimal Mærkeimpuls-holdespænding toppen af 4.0kV. Enheder eller system skal evalueres ved hjælp af kravene i standarden for Transient Voltage overspændingsbeskyttere, UL 1449 og skal også kunne modstå de tilgængelige kortslutningsstrømmen i overensstemmelse med UL 1449" NOTA: "Per l'uso in un circuito in cui i dispositivi o il sistema, compresi i filtri o vuoti d'aria, vengono utilizzati per controllare l'impulso a sovratensioni nominale massimo sopportare picchi di tensione di 4.0kV. Dispositivi o il sistema deve essere valutato in base ai requisiti della norma per Transient tensione di sovracorrente, UL 1449 e deve anche sopportare la corrente di corto circuito disponibili a norma UL 1449 " Alarm does not self-recover 5mins recovery 5mins recovery Over Current Condi on (>Ie + 15%) Relay Contact (Bypassed) • “Utilizzabile in impianti con corrente massima di 10000Arms, e 480V con l’utilizzo di fusibili di protezione”. • "Prove fino a 10000A con fusibili Classe J /RK5" • "Utilizzare solo fusibili". IEC Rated operational current Ie (AC-53b) 55A 380 - 415VAC 1min 1min 1min Control Voltage Control Voltage Assigned compressor rating @ 40ºC/UL rating @ 40ºC (3) Mains Voltage Red LED • „Geeignet für den Einsatz in einem Stromkreis, der bei Schutz durch Sicherungen höchstens einen symmetrischen Strom von 10.000 A effektiv und eine Spannung von maximal 480 Volt liefern kann.“ • „Die Prüfungen bei 10.000 A wurden mit Classe J / RK5-Sicherungen..“ • „Nur Sicherungen verwenden.“ Current/ Power Ratings - Strøm/ Nominel effekt - Nennstrom/-leistung -Caractéristiques de courant/puissance - Intensidad/Potencia nominal Valutazioni Corrente / Potenza Overcurrent condition (during bypass) Overcurrent Cond n (during Bypass) (> le +15%) (> Ie +15%) Wrong Phase Sequence Mains Voltage 10 kA when protected by semiconductor fuses 160A, Class URS/URQ, Art. No. 160Ac660VAC 27 x 601/ 6.9xxCP URQ 27 x 60 / 160 Relay Contact (Alarm) Ramp-Up Time > 1 sec. alarm Ramp-Up Time >1sec Alarm Undervoltage condition Undervoltage Condi on < 5sec User Interven on required to reset device by switching OFF and re-applying power to the so starter >= 5sec Mains Voltage Mains Voltage Green LED Green LED 1 min Red LED 1min Red LED 1min 5mins 5mins LED con nues flashing DIMENSIONS (MM) | MÅL (MM) | DIMENSIONES (MM) | DIMENSIONS (MM) |ABMESSUNGEN (MM) | DIMENSIONI (MM) 5 mins recovery Control Voltage Control Voltage Controller Output Controller Output Relay Contact (Bypassed) >1sec 5mins recovery >1sec 5mins recovery >1sec Two Consecu ve Alarms 5 mins recovery Panel mount Adapter Version, Tavlemonteret adapter version, Version mit Schalttafeladapter, Version adaptateur pour montage en tableau, Versión con adaptador para montaje en panel, Versione a pannello DIN RAIL adapter Version, DIN-SKINNE adapter version, Version mit DIN-Schienenadapter, Version adaptateur pour rail DIN , Versión con adaptador a carril DIN, Versione con adattatore per guida DIN Alarm does not selfrecover DIN RAIL ADAPTER VERSION SURFACE MOUNT ADAPTER VERSION 80 Relay Contact (Bypassed) Relay Contact (Alarm) 170 206 190 170 Relay Contact (Alarm) Overvoltage condition Overvoltage Condi on < 5sec >= 5sec Mains Voltage Green LED Red LED Control Voltage 7 Relay Contact (Alarm) 120 7 147 5 mins recovery Controller Output Relay Contact (Bypassed) 150 120 1 min LED STATUS INDICATION - LED STATUSINDIKATOR - LED D'INDICATION D'ÉTAT - LED DE INDICACIÓN DE ESTADO - LED-STATUSANZEIGE - LED DI DIAGNOSTICA 5 mins recovery State Idle Bypass Alarm Recovery from Alarm Recovery time between starts Red LED OFF OFF Flashing (acc. to alarm) Flashing OFF Green LED ON ON ON ON Flashing
  • Page 1 1
  • Page 2 2

CARLO GAVAZZI RSBT4895CVC Guía de instalación

Tipo
Guía de instalación