Eaton BRN115AF Instruction Leaflet

Tipo
Instruction Leaflet
Effective December 2017
En vigueur en décembre 2017
Vigente a partir de diciembre de 2017
IL003024EN
Notice d’instructions IL003024EN
Folleto de instrucción IL003024EN
Safety instructions
Important safety instructions—
read all instructions before using.
This circuit breaker is designed to detect and
trip when the following conditions occur:
Overcurrent/short-circuit
All DF, AF, and GF circuits will trip when
overcurrent or short-circuit conditions exist
in accordance with UL
489
Ground faults (DF and GF breakers only)
Dual function and ground fault Breakers are
designed for personnel protection and will
trip when leakage current conditions exist
in accordance with UL 943
Arc faults (DF and AF breakers only)
Dual function and arc fault breakers will
detect both low current and high current
arc faults, making it a “Combination type
Arc Fault” circuit interrupter. It will trip
when arcing conditions exist in accordance
with UL 1699
Programmable components
All DF, AF, and GF breakers contain a
programmable integrated circuit and
complies with UL 1998 for safety in
programmable components
Dual function (DF) breakers serve as
universal breakers to fulll all 120 V
arc fault and ground fault requirements
in Eaton panels. Dual function AF/GF
breakers replace/fulll AFCI, GFCI, and
AFGF requirements.
DANGER
FAILURE TO FOLLOW THESE INSTRUCTIONS
COULD RESULT IN DEATH, PERSONAL INJURY, OR
PROPERTY DAMAGE. CIRCUIT BREAKERS MUST
BE INSTALLED AND SERVICED BY A QUALIFIED
ELECTRICIAN. REMOVE ALL POWER SOURCES
TO PANEL BEFORE STARTING INSTALLATION
OR MAINTENANCE. TYPE BR QUICK CONNECT
NEUTRAL™ CIRCUIT BREAKERS ARE ONLY TO BE
INSTALLED IN LISTED TYPE BR QUICK CONNECT
NEUTRAL™ LOADCENTERS.
Instructions de sécurité
Importantes instructions de sécurité - lire
toutes les instructions avant utilisation.
Ces disjoncteurs sont conçus pour détecter
les conditions suivantes et se déclencher
lorsqu’elles se produisent :
Surintensité/court-circuit
Ces disjoncteurs AF, GF et à double fonction
se déclencheront lorsque des conditions de
surintensité ou de court-circuit existent selon
la norme UL 489
Défauts à la terre (disjoncteurs GF
et à double fonction seulement)
Ces disjoncteurs GF et à double fonction
sont conçus pour la protection personnelle
et se déclencheront lorsque des conditions
de courant de fuite existent selon la norme
UL 943
Défauts d’arc électrique (disjoncteurs
AF et à double fonction seulement)
Ces disjoncteurs AF et à double fonction
détecteront aussi bien les
défauts d’arc
électrique de courant élevé que faible. Ils
deviennent ainsi des interrupteurs de circuits
de « défaut d’arc électrique combiné ». Ils se
déclencheront lorsque des conditions d’arc
électrique existent selon la norme UL 1699
Composants programmables
Les disjoncteurs AF, GF et à double
fonction comprennent un circuit intégré
programmable et sont conformes avec
la norme UL 1998 pour la sécurité des
composants programmables
Les disjoncteurs à double fonction sont
utilisés comme disjoncteurs universels
conformes aux exigences en matière de
défauts d’arc électrique et de défauts à la
terre de 120 V dans les panneaux Eaton. Les
disjoncteurs à double fonction remplacent
les interrupteurs de circuit AF, GF et AF/GF
ou sont conformes aux exigences relatives
à ceux-ci.
DANGER
LE NON-RESPECT DE CES INSTRUCTIONS
PEUT ENTRAÎNER LA MORT, DES BLESSURES
PERSONNELLES OU DES DOMMAGES AUX
BIENS. L’INSTALLATION ET LA MAINTENANCE
DES DISJONCTEURS DOIVENT ÊTRE EFFECTUÉES
PAR UN ÉLECTRICIEN QUALIFIÉ. RETIRER TOUTES
LES SOURCES D’ALIMENTATION AU PANNEAU
ÉLECTRIQUE AVANT DE DÉBUTER L’INSTALLATION
OU L’ENTRETIEN. DISJONCTEURS DE TYPE BR
QUICK CONNECT NEUTRAL™ NE DOIVENT ÊTRE
INSTALLÉS SEULEMENT DANS LE RÉPERTORIÉ
“TYPE BR QUICK CONNECT NEUTRAL™”
LOADCENTERS.
Instrucciones de seguridad
Instrucciones de seguridad importantes:
lea todas las instrucciones antes de utilizar
el producto.
Este interruptor de circuito está diseñado para
detectar y desconectarse ante alguna de las
siguientes condiciones:
Sobrecorriente/cortocircuito
Todos los circuitos de DF, AF y GF se
desconectarán cuando existan condiciones
de sobrecorriente o cortocircuito de acuerdo
con la norma ULT 489
Fallas a tierra (Solamente interruptores
de DF y GF)
Los interruptores de doble función y
contra fallas a tierra están diseñados para
protección personal y se desconectarán
cuando existan condiciones de corriente
de fuga de acuerdo con la norma UL 943
Fallas de arco (Solamente interruptores
de DF y AF)
Los interruptores de doble función y contra
fallas de arco detectarán las corrientes bajas
y altas, convirtiéndolos en interruptores
de circuito de “fallas de arco de tipo
combinado. Se desactivarán cuando existan
condiciones de fallas de arco de acuerdo con
la norma UL 1699
Componentes programables
Todos los interruptores de circuito de
DF, AF y GF cuentan con un circuito
integrado programable y cumplen con
la norma UL 1998 referente a seguridad
en componentes programables
Los interruptores de doble función (DF)
sirven como interruptores universales a
n de satisfacer todos los requisitos para
fallas de arco y fallas a tierra de 120 V en los
paneles de Eaton. Los interruptores de doble
función (AF/GF) reemplazan/satisfacen los
requisitos de AFCI, GFCI y AFGF.
PELIGRO
EN CASO DE NO RESPETARSE ESTAS
INSTRUCCIONES, SE PUEDEN PRODUCIR LA
MUERTE, LESIONES PERSONALES O DAÑOS
A LA PROPIEDAD. LA INSTALACIÓN Y EL
MANTENIMIENTO DE LOS INTERRUPTORES
DE CIRCUITO DEBE ESTAR A CARGO DE
UN ELECTRICISTA CALIFICADO. ANTES DE
COMENZAR CON LA INSTALACIÓN O EL
MANTENIMIENTO, DESCONECTE TODOS LOS
SUMINISTROS DE ENERGÍA DEL PANEL. LOS
INTERRUPTORES TIPO BR CON CONEXION
RAPIDA DE NEUTRO PUEDEN INSTALARSE
SOLAMENTE EN CENTROS DE CARGA LISTADOS
TIPO BR “QUICK CONNECT NEUTRAL™”.
BR (1-inch), BR (1-inch) Quick Connect Neutral, and QB (bolt-on)
arc fault (AF), ground fault (GF), dual function AF/GF (DF), and
equipment protection (EP)
Disjoncteurs de type BR (2,5 cm/1 po), type BR Quick Connect Neutral
(2,5 cm/1 po) et type QB (boulonné) de défaut d’arc électrique (AF), de défaut
à la terre (GF) et à double fonction, et protection de l’équipement (EP)
Interruptor de doble función (DF), contra fallas a tierra y fallas de arco (AG/AF)
tipo BR(2.5 cm [1-pulg.]), tipo BR con Quick Connect Neutral (2.5 cm [1-pulg.])
de tipo de conexión QB y protección de equipos (EP)

Transcripción de documentos

IL003024EN Notice d’instructions IL003024EN Folleto de instrucción IL003024EN Effective December 2017 En vigueur en décembre 2017 Vigente a partir de diciembre de 2017 BR (1-inch), BR (1-inch) Quick Connect Neutral, and QB (bolt-on) arc fault (AF), ground fault (GF), dual function AF/GF (DF), and equipment protection (EP) Disjoncteurs de type BR (2,5 cm/1 po), type BR Quick Connect Neutral (2,5 cm/1 po) et type QB (boulonné) de défaut d’arc électrique (AF), de défaut à la terre (GF) et à double fonction, et protection de l’équipement (EP) Interruptor de doble función (DF), contra fallas a tierra y fallas de arco (AG/AF) tipo BR(2.5 cm [1-pulg.]), tipo BR con Quick Connect Neutral (2.5 cm [1-pulg.]) de tipo de conexión QB y protección de equipos (EP) Safety instructions Instructions de sécurité Instrucciones de seguridad Important safety instructions— read all instructions before using. Importantes instructions de sécurité - lire toutes les instructions avant utilisation. This circuit breaker is designed to detect and trip when the following conditions occur: Ces disjoncteurs sont conçus pour détecter les conditions suivantes et se déclencher lorsqu’elles se produisent : Instrucciones de seguridad importantes: lea todas las instrucciones antes de utilizar el producto. • Overcurrent/short-circuit All DF, AF, and GF circuits will trip when overcurrent or short-circuit conditions exist in accordance with UL 489 • Ground faults (DF and GF breakers only) Dual function and ground fault Breakers are designed for personnel protection and will trip when leakage current conditions exist in accordance with UL 943 • Arc faults (DF and AF breakers only) Dual function and arc fault breakers will detect both low current and high current arc faults, making it a “Combination type Arc Fault” circuit interrupter. It will trip when arcing conditions exist in accordance with UL 1699 • Programmable components All DF, AF, and GF breakers contain a programmable integrated circuit and complies with UL 1998 for safety in programmable components Dual function (DF) breakers serve as universal breakers to fulfill all 120 V arc fault and ground fault requirements in Eaton panels. Dual function AF/GF breakers replace/fulfill AFCI, GFCI, and AFGF requirements. DANGER FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN DEATH, PERSONAL INJURY, OR PROPERTY DAMAGE. CIRCUIT BREAKERS MUST BE INSTALLED AND SERVICED BY A QUALIFIED ELECTRICIAN. REMOVE ALL POWER SOURCES TO PANEL BEFORE STARTING INSTALLATION OR MAINTENANCE. TYPE BR QUICK CONNECT NEUTRAL™ CIRCUIT BREAKERS ARE ONLY TO BE INSTALLED IN LISTED TYPE BR QUICK CONNECT NEUTRAL™ LOADCENTERS. • Surintensité/court-circuit Ces disjoncteurs AF, GF et à double fonction se déclencheront lorsque des conditions de surintensité ou de court-circuit existent selon la norme UL 489 • Défauts à la terre (disjoncteurs GF et à double fonction seulement) Ces disjoncteurs GF et à double fonction sont conçus pour la protection personnelle et se déclencheront lorsque des conditions de courant de fuite existent selon la norme UL 943 • Défauts d’arc électrique (disjoncteurs Este interruptor de circuito está diseñado para detectar y desconectarse ante alguna de las siguientes condiciones: • Sobrecorriente/cortocircuito Todos los circuitos de DF, AF y GF se desconectarán cuando existan condiciones de sobrecorriente o cortocircuito de acuerdo con la norma ULT 489 • Fallas a tierra (Solamente interruptores de DF y GF) Los interruptores de doble función y contra fallas a tierra están diseñados para protección personal y se desconectarán cuando existan condiciones de corriente de fuga de acuerdo con la norma UL 943 • Fallas de arco (Solamente interruptores AF et à double fonction seulement) Ces disjoncteurs AF et à double fonction de DF y AF) Los interruptores de doble función y contra détecteront aussi bien les défauts d’arc fallas de arco detectarán las corrientes bajas électrique de courant élevé que faible. Ils y altas, convirtiéndolos en interruptores deviennent ainsi des interrupteurs de circuits de circuito de “fallas de arco de tipo de « défaut d’arc électrique combiné ». Ils se combinado”. Se desactivarán cuando existan déclencheront lorsque des conditions d’arc condiciones de fallas de arco de acuerdo con électrique existent selon la norme UL 1699 la norma UL 1699 • Composants programmables • Componentes programables Les disjoncteurs AF, GF et à double fonction comprennent un circuit intégré Todos los interruptores de circuito de programmable et sont conformes avec DF, AF y GF cuentan con un circuito la norme UL 1998 pour la sécurité des integrado programable y cumplen con composants programmables la norma UL 1998 referente a seguridad en componentes programables Les disjoncteurs à double fonction sont utilisés comme disjoncteurs universels conformes aux exigences en matière de défauts d’arc électrique et de défauts à la terre de 120 V dans les panneaux Eaton. Les disjoncteurs à double fonction remplacent les interrupteurs de circuit AF, GF et AF/GF ou sont conformes aux exigences relatives à ceux-ci. DANGER LE NON-RESPECT DE CES INSTRUCTIONS PEUT ENTRAÎNER LA MORT, DES BLESSURES PERSONNELLES OU DES DOMMAGES AUX BIENS. L’INSTALLATION ET LA MAINTENANCE DES DISJONCTEURS DOIVENT ÊTRE EFFECTUÉES PAR UN ÉLECTRICIEN QUALIFIÉ. RETIRER TOUTES LES SOURCES D’ALIMENTATION AU PANNEAU ÉLECTRIQUE AVANT DE DÉBUTER L’INSTALLATION OU L’ENTRETIEN. DISJONCTEURS DE TYPE BR QUICK CONNECT NEUTRAL™ NE DOIVENT ÊTRE INSTALLÉS SEULEMENT DANS LE RÉPERTORIÉ “TYPE BR QUICK CONNECT NEUTRAL™” LOADCENTERS. Los interruptores de doble función (DF) sirven como interruptores universales a fin de satisfacer todos los requisitos para fallas de arco y fallas a tierra de 120 V en los paneles de Eaton. Los interruptores de doble función (AF/GF) reemplazan/satisfacen los requisitos de AFCI, GFCI y AFGF. PELIGRO EN CASO DE NO RESPETARSE ESTAS INSTRUCCIONES, SE PUEDEN PRODUCIR LA MUERTE, LESIONES PERSONALES O DAÑOS A LA PROPIEDAD. LA INSTALACIÓN Y EL MANTENIMIENTO DE LOS INTERRUPTORES DE CIRCUITO DEBE ESTAR A CARGO DE UN ELECTRICISTA CALIFICADO. ANTES DE COMENZAR CON LA INSTALACIÓN O EL MANTENIMIENTO, DESCONECTE TODOS LOS SUMINISTROS DE ENERGÍA DEL PANEL. LOS INTERRUPTORES TIPO BR CON CONEXION RAPIDA DE NEUTRO PUEDEN INSTALARSE SOLAMENTE EN CENTROS DE CARGA LISTADOS TIPO BR “QUICK CONNECT NEUTRAL™”.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8

Eaton BRN115AF Instruction Leaflet

Tipo
Instruction Leaflet

en otros idiomas