Square D Company QO-B120 Guía de instalación

Tipo
Guía de instalación

Este manual también es adecuado para

www.se.com
NQ/NQM Panelboards and QONQ Load
Centers
Class 1640
Instruction Bulletin
80043-712-06, Rev. 07
02/2023
Legal Information
The Schneider Electric brand and any trademarks of Schneider Electric SE and its
subsidiaries referred to in this guide are the property of Schneider Electric SE or its
subsidiaries. All other brands may be trademarks of their respective owners.
This guide and its content are protected under applicable copyright laws and furnished
for informational use only. No part of this guide may be reproduced or transmitted in
any form or by any means (electronic, mechanical, photocopying, recording, or
otherwise), for any purpose, without the prior written permission of Schneider Electric.
Schneider Electric does not grant any right or license for commercial use of the guide
or its content, except for a non-exclusive and personal license to consult it on an "as is"
basis. Schneider Electric products and equipment should be installed, operated,
serviced, and maintained only by qualified personnel.
As standards, specifications, and designs change from time to time, information
contained in this guide may be subject to change without notice.
To the extent permitted by applicable law, no responsibility or liability is assumed by
Schneider Electric and its subsidiaries for any errors or omissions in the informational
content of this material or consequences arising out of or resulting from the use of the
information contained herein.
Class 1640
Table of Contents
Safety Information ............................................................................................5
Please Note.....................................................................................................5
Introduction........................................................................................................6
Safety Precautions ...........................................................................................6
Installation .........................................................................................................7
Interior Mounting for Square D Brand Enclosures ...............................................7
Surface Mounting (Enclosure Mounted on Wall)............................................7
Flush Mounting (Enclosure Recessed in Wall) ..............................................8
Neutral Bonding Strap/Cable Installation............................................................9
100 or 250 A Maximum NQ Panelboards....................................................10
400 or 600 A Maximum NQ Panelboards and QONQ Load Centers.............. 11
QO and QOB Circuit Breaker Installation and Removal .....................................13
QO and QOB Circuit Breaker Installation....................................................13
QO and QOB Circuit Breaker Removal.......................................................14
Circuit Breaker Reset Instructions....................................................................15
Deadfront Preparation ....................................................................................16
Appendix 1: Specifications............................................................................18
Typical Wiring ................................................................................................18
Integral Main or Sub-Feed: DJ, FI, KI, H, J, LA, LC, LH, QB, QD, QG, QJ,
QO(B)VH.................................................................................................19
Panelboard Ratings........................................................................................23
CE Marking....................................................................................................32
QO2150VH, QO2175VH and QO2200VH Restrictions ...................................... 33
Appendix 2: Accessory Kits ..........................................................................35
Equipment Ground Bar Kits.............................................................................35
Oversized Neutral Lug Kits for 100–600 A Panelboards ....................................35
Sub-Feed Lug Kits for 100–400 A Panelboards ................................................36
Main Lug Kits.................................................................................................36
Line Side Barrier and Neutral Bonding Strap Kits ..............................................37
80043-712-06 3
Safety Information Class 1640
Safety Information
Read these instructions carefully and look at the equipment to become familiar with
the device before trying to install, operate, service, or maintain it. The following special
messages may appear throughout this user guide or on the equipment to warn of
hazards or to call attention to information that clarifies or simplifies a procedure.
The addition of either symbol to a “Danger” or “Warning” safety
label indicates that an electrical hazard exists which will result
in personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to personal
injury hazards. Obey all safety messages that follow this
symbol to avoid possible injury or death.
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in
death or serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result
in death or serious injury.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result
in minor or moderate injury.
NOTICE
NOTICE is used to address practices not related to physical injury.
NOTE: Provides additional information to clarify or simplify a procedure.
Please Note
Electrical equipment should be installed, operated, serviced, and maintained only by
qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction,
installation, and operation of electrical equipment and has received safety training to
recognize and avoid the hazards involved.
Electrical equipment should be transported, stored, installed, and operated only in the
environment for which it is designed.
80043-712-06 5
Class 1640 Introduction
Introduction
This bulletin contains instructions for installing Square D™ brand NQ circuit breaker
panelboards and QONQ load centers. These panelboards and load centers are
Underwriters Laboratories (cULus) listed and accept QO™ and QOB branch circuit
breakers.
NOTE: For technical support on the installation of this panelboard, contact the
Schneider Electric Customer Information Center at 1-888-778-2733.
NOTE: See the labels on the equipment for rating and safety information.
Additional equipment labels are provided with this document.
Safety Precautions
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Apply appropriate personal protective equipment (PPE) and follow safe electrical
work practices. See NFPA 70E, NOM-029-STPS or CSA Z462 or local
equivalent.
This equipment must only be installed and serviced by qualified electrical
personnel.
Turn off all power supplying this equipment before working on or inside
equipment.
Locking the manual operation or locking the motor cover does not disconnect
the secondary motor circuit.
Always use a properly rated voltage sensing device to confirm power is off.
Read and understand this entire instruction bulletin and the included NEMA PB
1.1 standards publication before installing, operating, or maintaining this
equipment.
Local codes vary, but are adopted and enforced to promote safe electrical
installations. A permit may be needed to do electrical work, and some codes
may require an inspection of the electrical work.
Replace all devices, doors, and covers before turning on power to this
equipment.
Do not allow petroleum based paints, solvents, or sprays to contact the
nonmetallic parts of this product.
Failure to follow these instructions will result in death or serious injury.
WARNING: This product can expose you to chemicals including Nickel compounds, which are
known to the State of California to cause cancer, and Bisphenol A (BPA), which is known to the
State of California to cause birth defects or other reproductive harm. For more information go to
www.P65Warnings.ca.gov.
6 80043-712-06
Installation Class 1640
Installation
This section provides instructions for the following NQ panelboard and QONQ load
center procedures:
Interior Mounting for Square D Brand Enclosures, page 7.
Neutral Bonding Strap/Cable Installation, page 9.
QO and QOB Circuit Breaker Installation and Removal, page 13.
Circuit Breaker Reset Instructions, page 15.
Deadfront Preparation, page 16.
Interior Mounting for Square D Brand Enclosures
A separate standards publication, titled “General Instructions for Proper Installation,
Operation, and Maintenance of Panelboards Rated 600 Volts or Less” (NEMA PB1.1),
has been provided with this equipment. Familiarize yourself with the content of this
document before proceeding with any of the following procedures.
If you did not receive a copy of this document, or if you have any questions regarding
this equipment, contact your local distributor or Schneider Electric representative.
NOTICE
HAZARD OF EQUIPMENT DAMAGE DUE TO LOOSE CONNECTIONS
Ensure all connections are properly tightened.
Refer to the torque information label provided on the panelboard before
tightening the connections.
Failure to follow these instructions can result in equipment damage.
To properly mount and install the NQ panelboard or QONQ load center interior, please
refer to the NEMA PB 1.1 standards publication, and follow the instructions below for
either Surface Mounting (Enclosure Mounted on Wall), page 7 or Flush Mounting
(Enclosure Recessed in Wall), page 8.
Surface Mounting (Enclosure Mounted on Wall)
1. Mount the enclosure as instructed in the NEMA PB 1.1 standards publication.
2. Remove the deadfront from the deadfront brackets.
3. Install the interior as described below:
a. Set the interior on the enclosure studs. An elevating screw is not required
(See Interior Mounting for Square D Brand Enclosures, page 7).
b. Tighten the Keps nuts against the interior side rails until the rails are against
the back of the enclosure.
4. Based on the application and adopted installation code, Neutral Bonding Strap
and Line Side Barrier may be required. See the Neutral Bonding Strap/Cable
Installation, page 9 and Appendix 2: Accessory Kits, page 35.
5. Apply equipment labels (located in the bag assembly) as directed by the
instructions on the back of the equipment label sheet. Please consult local codes
and standards.
80043-712-06 7
Class 1640 Installation
6. Remount the deadfront after wiring.
Flush Mounting (Enclosure Recessed in Wall)
1. Mount the enclosure as instructed in the NEMA PB 1.1 standards publication.
2. Remove the deadfront from the deadfront brackets.
3. Install the interior as described below:
a. Thread the (4) 10-32 x 0.875 in. self-tapping, elevating screws provided with
the flush trim into the side rails.
b. Set the interior on the enclosure studs (see Interior Mounting of Square D
Brand Enclosures, page 9). Place the keps nuts onto the enclosure studs,
but do not tighten.
c. Adjust the screws so that the lip of the deadfront is approximately 0.25
inches (6.35 mm) from the wall line.
d. Tighten the keps nuts against the side rails.
4. Based on the application and adopted installation code, Neutral Bonding Strap
and Line Side Barrier may be required. Please consult local codes and standards.
See the Neutral Bonding Strap/Cable Installation, page 9 and Appendix 2:
Accessory Kits, page 35.
5. Apply equipment labels (located in the bag assembly) as directed by the
instructions on the back of the equipment label sheet.
6. Remount the deadfront after wiring.
8 80043-712-06
Installation Class 1640
Figure 1 - Interior Mounting of Square D Brand Enclosures
Deadfront Bracket
Enclosure Stud
Keps Nut
Enclosure
Deadfront
Wall
Elevating Screw
Side Rail
0.25 in.
(6.35 mm)
Neutral Bonding Strap/Cable Installation
Based on the application and the adopted installation code, a line side barrier and
neutral bonding strap may be required.
To properly bond the neutral to the panelboard, follow the instructions for either 100 or
250 A Maximum NQ Panelboards, or 400 or 600 A Maximum NQ Panelboards and
QONQ Load Centers, page 11.
80043-712-06 9
Class 1640 Installation
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Apply appropriate personal protective equipment (PPE) and follow safe electrical
work practices. See NFPA 70E, NOM-029-STPS or CSA Z462 or local
equivalent.
Turn off all power supplying this equipment before working on or inside
equipment.
Locking the manual operation or locking the motor cover does not disconnect
the secondary motor circuit.
The neutral bonding strap/cable should be used only when the panelboard is
installed as service entrance equipment.
Do not mix the mounting screws with the deadfront screws.
Failure to follow these instructions will result in death or serious injury.
NOTE: Refer to Line Side Barrier and Neutral Bonding Strap Kits, page 38 for
information.
NOTE: The terms “neutral bonding strap” and “neutral bonding cable”, describe
the components which meet the requirements for a “neutral bonding conductor”.
These are equivalent terms.
100 or 250 A Maximum NQ Panelboards
To install a neutral bonding strap on NQ panelboards with mains rated up to 225 A
(with main lugs or main circuit breaker), or up to 250 A with a factory assembled main
circuit breaker, refer to Bonding Strap Installation—100 or 250 A Maximum NQ
Panelboards, page 11, and follow the instructions below.
1. Align the bonding strap on the side rail, as pictured.
NOTE: For some applications, it may be necessary to remove the lug (not
pictured) before installing the bonding strap.
2. Insert the two mounting screws, as pictured. Tighten the 10-32 screw to 10–12
lb.-in. (1.1–1.4 N•m) and the 1/4-20 to 25–30 lb.-in. (2.8–3.4 N•m).
NOTE: Lug mounting screws are provided in the bonding strap bag assembly.
a. If the lug was removed in step 1 above, reinstall it on top of the bonding
strap.
b. Use 1/4-20 x 9/16 in. screw in mounting for 100/225 A interiors with no
options. Refer to note C and D for other options.
c. Use the 1/4-20 screw x 11/16 in. lug mounting screw on applications with
feed-through lug, sub-feed lug, sub-feed circuit breaker, or 200% neutral
applications.
d. Use the 1/4-20 x 7/8 in. lug mounting screw on applications with 200%
neutrals and with feed-through lugs, sub-feed lugs, or sub-feed circuit
breakers.
10 80043-712-06
Installation Class 1640
Figure 2 - Bonding Strap Installation—100 or 250 A Maximum NQ Panelboards
NOTE: For bonding strap lug options, refer to C and D for the correct length of the 1/4-20 screw.
Mounting Screws
Bonding Strap
1/4-20 x 9/16 in.
10/32 x 7/16 in.
Neutral Bus
Side Rail
400 or 600 A Maximum NQ Panelboards and QONQ Load Centers
To install a neutral bonding cable on a 400 or 600 A maximum NQ panelboard and
QONQ load center, refer to Bonding Cable Installation — 400 or 600 A Maximum NQ
Panelboards and QONQ Load Centers, page 12, and follow the instructions below.
1. Align the lug on the side rail mounting hole, as pictured.
2. Tighten the lug mounting screw against the side rail to 10–12 lb.-in. (1.1–1.4
N•m).
3. Align the bonding cable, as pictured, and insert it into the lug and neutral
mounting holes.
4. Tighten both the lug wire binding screw and the neutral wire binding screw to 45–
50 lb.-in. (5.1–5.6 N•m).
80043-712-06 11
Class 1640 Installation
Figure 3 - Bonding Cable Installation — 400 or 600 A Maximum NQ Panelboards and QONQ Load Centers
Neutral
Lug Mounting
Screw
Bonding Cable
Bonding Cable Mounting Hole
Side Rail
Lug
Side Rail
Mounting Hole
Neutral Wire
Binding Screw
Lug
Wire
Binding
Screw
Bonding Cable Mounting Hole
12 80043-712-06
Installation Class 1640
QO and QOB Circuit Breaker Installation and Removal
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Apply appropriate personal protective equipment (PPE) and follow safe electrical
work practices. See NFPA 70E, NOM-029-STPS or CSA Z462 or local
equivalent.
This equipment must only be installed and serviced by qualified electrical
personnel.
Turn off all power supplying this equipment before working on or inside
equipment.
Locking the manual operation or locking the motor cover does not disconnect
the secondary motor circuit.
Always use a properly rated voltage sensing device to confirm power is off.
All unused spaces must be filled with filler plates.
Replace all devices, doors, and covers before turning on power to this
equipment.
Failure to follow these instructions will result in death or serious injury.
WARNING
HAZARD OF PERSONAL INJURY OR EQUIPMENT DAMAGE
This equipment is designed and tested by Schneider Electricto performance
levels which meet Underwriter’s Laboratories®(UL®) standards and Mexican
Official Standards (NOM) listing.
Use only Square Dbrand circuit breakers and accessories.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
QO and QOB Circuit Breaker Installation
Refer to QO and QOB Circuit Breaker Installation and Removal, page 15, for the
following instructions:
1. Turn OFF all power to the panelboard.
2. Turn the circuit breaker OFF.
3. Remove the deadfront.
4. Snap the wire terminal end of the circuit breaker onto the mounting rail.
5. Engage the branch connector.
For QO Circuit Breakers: Push inward until the plug-on jaws fully engage the
branch connector.
For QOB Circuit Breakers: Push inward until the circuit breaker connector is
centered on the branch connector mounting hole. Engage the screw into the
branch connector hole and tighten it to the torque values shown on the interior
wiring and torque diagram.
6. Install the load wire.
7. Reinstall the deadfront.
8. Install a filler plate in all branch circuit breaker spaces not used.
80043-712-06 13
Class 1640 Installation
QO and QOB Circuit Breaker Removal
Refer to QO and QOB Circuit Breaker Installation and Removal, page 15, for the
following instructions:
1. Turn OFF all power to the panelboard.
2. Remove the deadfront.
3. Remove the load wire.
4. Disengage the branch connector.
For QO Circuit Breakers:
Pull outward until the plug-on jaws fully disengage the branch connector.
For QOB Circuit Breakers:
Loosen the screw in the circuit breaker connector and pull the circuit breaker off
of the branch connector.
5. Snap the wire terminal end of the circuit breaker off of the mounting rail.
6. Reinstall the deadfront.
7. Install a filler plate in all branch circuit breaker spaces not used.
14 80043-712-06
Installation Class 1640
Figure 4 - QO and QOB Circuit Breaker Installation and Removal
QO
QOB
Plug-On Jaw
Branch Connector
Branch Connector
Bolt-On
Connector
Screw
Rail
Wire
Terminal
Wire
Terminal
Rail
Circuit Breaker Reset Instructions
If the circuit breaker is tripped, the handle will be at the mid-position between ON and
OFF. To reset the circuit breaker, push the handle to the OFF position, then to the ON
position.
80043-712-06 15
Class 1640 Installation
Figure 5 - Circuit Breaker Handle Positions
ONOFFTripped
Handle
Visi-Trip™ Indicator
NOTE: When the circuit breaker has tripped, the handle assumes a center
position and the red Visi-Trip indicator appears in a window in the circuit breaker
case. The red Visi-Trip indicator is only visible when the circuit breaker has
tripped.
Deadfront Preparation
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Apply appropriate personal protective equipment (PPE) and follow safe electrical
work practices. See NFPA 70E, NOM-029-STPS or CSA Z462 or local
equivalent.
Before energizing the panelboard, all unused spaces must be filled with filler
plates.
Replace all devices, doors, and covers before turning on power to this
equipment.
Failure to follow these instructions will result in death or serious injury.
16 80043-712-06
Installation Class 1640
Figure 6 - Deadfront Diagram
Filler plates
Deadfront
NOTE: The back of the deadfront lists the catalog number for the corresponding
compatible filler plates.
80043-712-06 17
Class 1640 Appendix 1: Specifications
Appendix 1: Specifications
Typical Wiring
Table 1 - Panelboard Typical Wiring1
Voltage AC 1-Phase Panelboards 1-Phase Panelboards
Phase Wires Phase Wires
208Y/120 — — 3 4
120/240 1 3 — —
24021 2 3 4
24031 3 — —
240/1204— — 3 4 Delta
18 80043-712-06
1. Additional information is provided on the panelboard. See the main circuit breaker rating, if used.
2. For this system, the neutral is not used and only circuit breakers rated 240 Vac minimum should be used. Do not use circuit breakers rated
120 V or 120/240 Vac.
3. For a grounded “B” phase system, only circuit breakers rated 240 Vac minimum should be used. Do not use circuit breakers rated 120 V or
120/240 Vac.
4. When wiring for a delta system, phases “A” and “C” must be 120 V to neutral, phase “B” 208 V to neutral. Connect only circuit breakers rated
240 Vac minimum. Do not use circuit breakers rated 120 V or 120/240 V to “B” phase.
Appendix 1: Specifications Class 1640
Integral Main or Sub-Feed: DJ, FI, KI, H, J, LA, LC, LH, QB, QD, QG,
QJ, QO(B)VH
Figure 7 - NQ/NQM 100–225 A Main Lugs or 100–250 A Main Circuit Breaker Diagram
80043-712-06 19
Class 1640 Appendix 1: Specifications
Figure 8 - NQ Panelboard or QONQ Load Center 400–600 A Main Lugs or Main Circuit Breaker with or
without Feed-Through Lugs Diagram
Load
Feed-Through Lugs
(when installed)
Integral Main
Circuit Breaker
(when installed)
Enclosure Bonding
(when required) Neutral
Ground
(when required)
20 80043-712-06
Appendix 1: Specifications Class 1640
Figure 9 - NQ Panelboard or QONQ Load Center 400–600 A Main Circuit Breaker with Feed-Through Lugs
or Sub-Feed Circuit Breakers
Subfeed
Circuit Breaker(s)
Load Load
(when installed)
Load
Enclosure Bonding
(when required) Neutral
Ground
(when required)
Integral Main
Circuit Breaker
(when installed)
Line
80043-712-06 21
Class 1640 Appendix 1: Specifications
Figure 10 - Typical NQ Panelboard with Split Bus Diagram
Integral Main
Circuit Breaker
(when installed)
Enclosure Bonding
(when required) Neutral
Ground
Line
(when required)
22 80043-712-06
Appendix 1: Specifications Class 1640
Panelboard Ratings
Refer to local codes and standards for more information. The series rated system
label is located in the bag assembly.
Series Connected Circuit Breaker Ratings (RMS Symmetrical)
Series Ratings listed at higher system voltages apply to lower system voltages
(Example: 240 3P/3W covers 208Y/120 3P/4W).
Short circuit tests are conducted at 100–105% of the maximum rated voltage of
the panelboard.
“MC” denotes Mission Critical circuit breakers.
Where LG is shown, LJ and LL can be used.
Unless otherwise noted, main circuit breakers can be applied at the maximum
available amperage rating.
Suffixes HID, SWD, and SWN may also be applied to the applicable branch
circuit breakers shown below.
Where QO(B) circuit breakers are shown below, QO(B)H, QO(B)VH, and QH(B)
circuit breakers may also be used.
Two-pole CAFI circuit breakers cannot be used on three-phase systems.
Table 2 - Max. System Voltage AC: 120/240 1P/3W, 208Y/120 3P/4W, 240/120 3P/4W
Max. Short Circuit
Current Rating
Square D Brand Integral or Remote
Main Circuit Breakers and Remote
Main Fuses
Square D Brand Branch Circuit Breaker Catalog Designation and
Allowable Ampere Ranges
Type 1-Pole 2-Pole 3-Pole
18,000 LA/LH MC QO(B) 15–30 A 15–30 A
22,000 QO(B) VH
QOB-VH
QO(B) 15–70 A 15–125 A
QO(B) GFI 15–30 A 15–60 A
QO(B) EPD 15–30 A 15–60 A
QO(B) PL 15–30 A 15–60 A
QO(B) AFI 15–20 A — —
QO(B) CAFI 15–20 A 15–20 A
QO(B) DF 15–20 A — —
80043-712-06 23
Class 1640 Appendix 1: Specifications
Table 2 - Max. System Voltage AC: 120/240 1P/3W, 208Y/120 3P/4W, 240/120 3P/4W (Continued)
Max. Short Circuit
Current Rating
Square D Brand Integral or Remote
Main Circuit Breakers and Remote
Main Fuses
Square D Brand Branch Circuit Breaker Catalog Designation and
Allowable Ampere Ranges
Type 1-Pole 2-Pole 3-Pole
25,000
QD
QO(B) 15–70 A 15–125 A
QOB-VH — 150 A
QO(B) PL 15–30 A 15–60 A
QO(B) GFI 15–30 A 15–60 A
QO(B) EPD 15–30 A 15–60 A
QO(B) AFI 15–20 A — —
QO(B) CAFI 15–20 A 15–20 A
QO(B) DF 15–20 A — —
ED
QO(B) 15–70 A 15–125 A
QO(B) GFI 15–30 A 15–60 A
QO(B) EPD 15–30 A 15–60 A
QO(B) AFI 15–20 A — —
QO(B) CAFI 15–20 A 15–20 A
QO(B) DF 15–20 A — —
BD, HD, JD, LD
QO(B) 15–70 A 15–125 A
QOB-VH — 150 A
QO(B) PL 15–30 A 15–60 A
QO(B) GFI 15–30 A 15–60 A
QO(B) EPD 15–30 A 15–60 A
QO(B) AFI 15–20 A — —
BD, HD, JD, LD
QO(B) CAFI 15–20 A 15–20 A
QO(B) DF 15–20 A — —
42,000 LA, MA QO(B) 15–30 A 15–30 A
24 80043-712-06
Appendix 1: Specifications Class 1640
Table 2 - Max. System Voltage AC: 120/240 1P/3W, 208Y/120 3P/4W, 240/120 3P/4W (Continued)
Max. Short Circuit
Current Rating
Square D Brand Integral or Remote
Main Circuit Breakers and Remote
Main Fuses
Square D Brand Branch Circuit Breaker Catalog Designation and
Allowable Ampere Ranges
Type 1-Pole 2-Pole 3-Pole
65,000
QG
QO(B) 15–70 A 15–125 A
QO(B) VH 15–70 A 15–125 A
QOB-VH — 150 A
QO(B) GFI 15–30 A 15–60 A
QO(B) PL 15–30 A 15–60 A
QO(B) AFI 15–20 A — —
QO(B) CAFI 15–20 A 15–20 A
QO(B) DF 15–20 A — —
EG QO(B) 15–70 A 15–125 A
EG
QO(B) GFI 15–30 A 15–60 A
QO(B) EPD 15–30 A 15–60 A
QO(B) EPE — — —
QO(B) AFI 15–20 A — —
QO(B) CAFI 15–20 A 15–20 A
QO(B) DF 15–20 A — —
BG, HG, JG, LG
QO(B) 15–70 A 15–125 A
QOB-VH — 150 A
QO(B) PL 15–30 A 15–60 A
QO(B) GFI 15–30 A 15–60 A
QO(B) EPD 15–30 A 15–60 A
QO(B) AFI 15–20 A — —
QO(B) CAFI 15–20 A 15–20 A
QO(B) DF 15–20 A — —
80043-712-06 25
Class 1640 Appendix 1: Specifications
Table 2 - Max. System Voltage AC: 120/240 1P/3W, 208Y/120 3P/4W, 240/120 3P/4W (Continued)
Max. Short Circuit
Current Rating
Square D Brand Integral or Remote
Main Circuit Breakers and Remote
Main Fuses
Square D Brand Branch Circuit Breaker Catalog Designation and
Allowable Ampere Ranges
Type 1-Pole 2-Pole 3-Pole
100,000
QJ
QO(B) 15–70 A 15–125 A
QOB-VH — 150 A
QO(B) PL 15–30 A 15–60 A
QO(B) GFI 15–30 A 15–60 A
QO(B) EPD 15–30 A 15–60 A
QO(B) AFI 15–20 A — —
QO(B) CAFI 15–20 A 15–20 A
QO(B) DF 15–20 A — —
EJ
QO(B) 15–70 A 15–125 A
QO(B) GFI 15–30 A 15–60 A
EJ
QO(B) EPD 15–30 A 15–60 A
QO(B) AFI 15–20 A — —
QO(B) CAFI 15–20 A 15–20 A
QO(B) DF 15–20 A — —
BJ, HJ, JJ
QO(B) 15–70 A 15–125 A
QOB-VH — 150 A
QO(B) PL 15–30 A 15–60 A
QO(B) GFI 15–30 A 15–60 A
QO(B) EPD 15–30 A 15–60 A
QO(B) AFI 15–20 A — —
QO(B) CAFI 15–20 A 15–20 A
QO(B) DF 15–20 A — —
LJ
QO(B) 15–70 A 15–125 A
QOB-VH — 150 A
QO(B) GFI 15–60 A
QO(B) EPD 15–60 A
QO(B) AFI 15–20 A — —
QO(B) CAFI 15–20 A 15–20 A
QO(B) DF 15–20 A — —
125,000 HL, JL
QO(B) 15–70 A 15–125 A
QOB-VH — 150 A
QO(B) PL 15–30 A 15–60 A
QO(B) GFI 15–30 A 15–60 A
QO(B) EPD 15–30 A 15–60 A
QO(B) AFI 15–20 A — —
QO(B) CAFI 15–20 A 15–20 A
QO(B) DF 15–20 A — —
200,000
HR, JR
QO(B) 15–70 A 15–125 A
QO(B) GFI 15–30 A 15–60 A
QO(B) EPD 15–30 A 15–60 A
QO(B) AFI 15–20 A — —
HR, JR
QO(B) CAFI 15–20 A 15–20 A
QO(B) DF 15–20 A — —
26 80043-712-06
Appendix 1: Specifications Class 1640
Table 3 - Max. System Voltage AC: 240 1P/2W
Max. Short Circuit
Current Rating
Square D Brand Integral or Remote
Main Circuit Breakers and Remote
Main Fuses
Square D Brand Branch Circuit Breaker Catalog Designation and
Allowable Ampere Ranges
Type 1-Pole 2-Pole 3-Pole
25,000 QD, BD, HD, JD, LD QO(B) H 15–100 A
42,000 LA, MA QDL 70–225 A
65,000 QG, BG, HG, JG, LG QO(B) H 15–100 A
100,000 BJ, HJ, JJ, LJ QO(B) H 15–100 A
125,000 HL, JL QO(B) H 15–100 A
Table 4 - Max. System Voltage AC: 208Y/120 3P/4W
Max. Short Circuit
Current Rating
Square D Brand Integral or Remote
Main Circuit Breakers and Remote
Main Fuses
Square D Brand Branch Circuit Breaker Catalog Designation and
Allowable Ampere Ranges
Type 1-Pole 2-Pole 3-Pole
18,000 LA/LH MC QO(B) 15–30 A
22,000 QO(B) VH, QOB-VH QO(B) GFI 15–50 A
25,000 QD, ED, FD, BD, HD, JD QO(B) GFI 15–50 A
LD QO(B) GFI 15–30 A
65,000 QG, EG, BG, HG, JG QO(B) GFI 15–50 A
LG QO(B) GFI 15–30 A
100,000 QJ
QO(B) 15–30 A
QO(B) VH 15–100 A
QOB-VH 110–150 A
QO(B) PL 15–30 A
QO(B) GFI 15–50 A
QO(B) EPD 15–50 A
QO(B) EPE 15–50 A
EJ, BJ, HJ, JJ QO(B) GFI 15–50 A
80043-712-06 27
Class 1640 Appendix 1: Specifications
Table 5 - Max. System Voltage AC: 240/120 3P/4W, 240 3P/3W
Max. Short Circuit
Current Rating
Square D Brand Integral or Remote
Main Circuit Breakers and Remote
Main Fuses
Square D Brand Branch Circuit Breaker Catalog Designation and
Allowable Ampere Ranges
Type 1-Pole 2-Pole 3-Pole
22,000 QOB VH
QOB-VH
QO(B) 15–100 A
QO(B) EPD 15–50 A
QO(B) EPE 15–50 A
25,000
QD QO(B) 15–30 A
QD
QO(B) VH 15–100 A
QOB-VH 110–150 A
QO(B) PL 15–30 A
QO(B) EPD 15–50 A
QO(B) EPE 15–50 A
ED
QO(B) 15–100 A
QO(B) EPD 15–50 A
QO(B) EPE 15–50 A
BD, HD, JD
QO(B) 15–100 A
QOB-VH 110–150 A
QO(B) PL 15–30 A
QO(B) EPD 15–50 A
QO(B) EPE 15–50 A
LD
QO(B) 15–30 A
QO(B) VH 15–100 A
QOB-VH 110–150 A
QO(B) EPD 15–30 A
QO(B) EPE 15–30 A
42,000 LA, MA QDL 70–225 A
QO(B) VH 15–30 A
MG QOB-VH 110–150 A
65,000
QG
QO(B) 15–30 A
QO(B) VH 15–100 A
QG
QOB-VH 110–150 A
QO(B) PL 15–30 A
EG
QO(B) 15–100 A
QOB-VH 110–125 A
QO(B) EPD 15–50 A
QO(B) EPE 15–50 A
BG, HG, JG
QO(B) 15–100 A
QOB-VH 110–150 A
QO(B) PL 15–30 A
QO(B) EPD 15–50 A
QO(B) EPE 15–50 A
LG
QO(B) 15–30 A
QO(B) VH 15–100 A
QOB-VH 110–150 A
QO(B) EPD 15–30 A
QO(B) EPE 15–30 A
28 80043-712-06
Appendix 1: Specifications Class 1640
Table 5 - Max. System Voltage AC: 240/120 3P/4W, 240 3P/3W (Continued)
Max. Short Circuit
Current Rating
Square D Brand Integral or Remote
Main Circuit Breakers and Remote
Main Fuses
Square D Brand Branch Circuit Breaker Catalog Designation and
Allowable Ampere Ranges
Type 1-Pole 2-Pole 3-Pole
100,000
EJ
QO(B) 15–100 A
QOB-VH 110–125 A
QO(B) EPD 15–50 A
QO(B) EPE 15–50 A
BJ, HJ, JJ
QO(B) 15–100 A
QOB-VH 110–150 A
QO(B) PL 15–30 A
QO(B) EPD 15–50 A
QO(B) EPE 15–50 A
LJ
QO(B) 15–30 A
QO(B) VH 15–100 A
QOB-VH 110–150 A
125,000
HL, JL QO(B) 15–100 A
HL, JL
QOB-VH 110–150 A
QO(B) PL 15–30 A
QO(B) EPD 15–50 A
QO(B) EPE 15–50 A
200,000 HR, JR
QO(B) 15–100 A
QOB-VH 110–150 A
Table 6 - Max. System Voltage AC: 120/240 1P/3W, 208Y/120 3P/4W, 240/120 3P/3W
Max. Short Circuit
Current Rating
Square D Brand Integral or Remote
Main Circuit Breakers and Remote
Main Fuses
Square D Brand Branch Circuit Breaker Catalog Designation and
Allowable Ampere Ranges
Type 1-Pole 2-Pole 3-Pole
42,000 400 A Max.
Class T3 Fuses QO(B) VH 15–70 A 15–125 A
65,000
400 A Max.
Class J Fuses
QO(B) VH 15–70 A 15–125 A
QO(B) AFI 15–20 A — —
QO(B) CAFI 15–20 A 15–20 A
QO(B) DF 15–20 A — —
400 A Max.
Class T6 Fuses
QO(B) VH 15–70 A 15–125 A
QOB-VH — 150 A
QO(B) AFI 15–20 A — —
QO(B) CAFI 15–20 A 15–20 A
QO(B) DF 15–20 A — —
100,000 200 A Max.
Class T3 Fuses
QO(B) 15–70 A 15–125 A
QO(B) GFI 15–30 A 15–60 A
QO(B) EPD 15–30 A 15–60 A
QO(B) AFI 15–20 A — —
QO(B) CAFI 15–20 A 15–20 A
QO(B) DF 15–20 A — —
80043-712-06 29
Class 1640 Appendix 1: Specifications
Table 6 - Max. System Voltage AC: 120/240 1P/3W, 208Y/120 3P/4W, 240/120 3P/3W (Continued)
Max. Short Circuit
Current Rating
Square D Brand Integral or Remote
Main Circuit Breakers and Remote
Main Fuses
Square D Brand Branch Circuit Breaker Catalog Designation and
Allowable Ampere Ranges
Type 1-Pole 2-Pole 3-Pole
200,000
200 A Max.
Class T6 or J Fuses
QO(B) 15–70 A 15–125 A
QO(B) GFI 15–30 A 15–60 A
QO(B) EPD 15–30 A 15–60 A
400 A Max.
Class T3 Fuses
QO(B) 15–70 A 15–125 A
QO(B) GFI 15–30 A 15–60 A
QO(B) EPD 15–30 A 15–60 A
Table 7 - Max. System Voltage AC: 208Y/120 3P/4W
Max. Short Circuit
Current Rating
Square D Brand Integral or Remote
Main Circuit Breakers and Remote
Main Fuses
Square D Brand Branch Circuit Breaker Catalog Designation and
Allowable Ampere Ranges
Type 1-Pole 2-Pole 3-Pole
65,000 400 A Max. Class J QO(B) GFI 15–50 A
100,000 200 A Max. Class T3 QO(B) GFI 15–50 A
200,000
200 A Max.
Class T6 or J Fuses QO(B) GFI 15–50 A
400 A Max. Class T3 Fuses QO(B) GFI 15–50 A
Table 8 - Max. System Voltage AC: 240/120 3P/4W, 240 3P/3W
Max. Short Circuit
Current Rating
Square D Brand Integral or Remote
Main Circuit Breakers and Remote
Main Fuses
Square D Brand Branch Circuit Breaker Catalog Designation and
Allowable Ampere Ranges
Type 1-Pole 2-Pole 3-Pole
50,000 600 A Max. Class T3 Fuses QO(B) VH 15–30 A
65,000
400 A Max. Class J Fuses QO(B) VH 15–100 A
400 A Max. Class T6 Fuses
QO(B) VH 15–100 A
QOB-VH 110–150 A
100,000 200 A Max. Class T3 Fuses
QO(B) 15–100 A
QO(B) EPD 15–50 A
QO(B) EPE 15–50 A
200,000
200 A Max.
Class T6 or J Fuses
QO(B) 15–100 A
QO(B) EPD 15–50 A
QO(B) EPE 15–50 A
400 A Max.
Class T3 Fuses
QO(B) 15–100 A
QO(B) EPD 15–50 A
QO(B) EPE 15–50 A
30 80043-712-06
Appendix 1: Specifications Class 1640
Table 9 - NQ Panel Mission Critical Breaker Selectivity
Maximum SCCR
(RMS Symmetrical)
Integral or Remote Main
Circuit Breakers
Branch Circuit Breakers
Type51-Pole 2-Pole 3-Pole
Fully Rated and Selective to 10 kA
at 208Y/120 Vac or
at 240/120 Vac
J-W, 250 A
L-W, 250 A
QOB
10–70 10–125 10–125
QOB-H
QOB-VH
QH
Series Rated and Selective to 12 kA
at 208Y/120 Vac or
at 240/120 Vac
J-W, 250 A
QOB
10–70 10–125 10–60
QOB-H
QOB-VH
QH
Series Rated and Selective to 15 kA
at 208Y/120 Vac or
at 240/120 Vac
J-W, 250 A
QOB
10–60 10–60 10–30
QOB-H
QOB-VH
QH
Series Rated and Selective to 18 kA
at 208Y/120 Vac or
at 240/120 Vac
J-W, 250 A
QOB
10–30 10–30
QOB-H
QOB-VH
QH
L-W, 250 A
QOB
10–60 10–60 10–60
QOB-H
QOB-VH
QH
Series Rated and Selective to 30 kA
at 208Y/120 Vac or
at 240/120 Vac
L-W, 400 A
L-W, 600 A
QOB
15–70 15–150 15–150
QOB-H
QOB-VH
QH
80043-712-06 31
5. Including AFI, CAFI, EPD and GFI Circuit Breakers.
Class 1640 Appendix 1: Specifications
Table 10 - Short Circuit Current Rating6for Main Lug Interiors with Sub-Feed or Feed-Through Lugs
Maximum System
Voltage AC
Maximum Current
Rating Branch Circuits7Application Adder8
Maximum Short
Circuit Current
Rating9
240
100 18, 30 SFL and FTL
10,000
225
30, 42, 54, 72, 84, 96 SFL 6 in. (152.4 mm)
42
FTL
30, 54, 72, 84, 96 6 in. (152.4 mm)
400
30, 42, 54, 72, 84
SFL
25,000
96 10,000
30, 84
FTL
25,000
96 10,000
42, 54, 72 6 in. (152.4 mm)
25,000
600
30, 42, 54, 72, 84
FTL 12 in. (304.8 mm)
96 10,000
CE Marking
Interiors with the “CE” mark meet the IEC 61439-1 and IEC 61439-2 standards.
Main lug interiors with the “CE” mark have been tested to withstand 10,000 RMS
symmetrical amperes for 30 cycles.
Interiors with the “CE” mark are only approved for use with QOXD or QOBXD
branch circuit breakers which carry the “CE” mark.
32 80043-712-06
6. This rating applies to main lug interiors, equipped with sub-feed or feed-through lugs, where the device feeding the interior is unknown or not
a Square D brand device. Use of a Square D brand main circuit breaker ahead of these lugs will result in a rating equal to the rating of the
circuit breaker. Short circuit tests are conducted at 100–105% of the maximum rated voltage of the panelboard.
7. 96 circuits with SPD has 84 usable branch circuits.
8. The adder is the additional length of the enclosure.
9. RMS symmetrical amperes, for three cycles.
Appendix 1: Specifications Class 1640
QO2150VH, QO2175VH and QO2200VH Restrictions
NOTICE
HAZARD OF EQUIPMENT DAMAGE
Do not install QO2150(VH), QO2175(VH) or QO2200(VH) in seismic
applications.
Do not install QO2150(VH), QO2175(VH) or QO2200(VH) in three phase system
applications.
Do not install more than a total of four QO2175(VH) or QO2200(VH) on NEMA 1
enclosures.
Do not install more than one QO2175(VH) or QO2200(VH) in NEMA 3R Vented
Weatherproof enclosures.
Do not install QO2150(VH), QO2175(VH) or QO2200(VH) adjacent to each
other.
Do not install in un-vented weatherproof enclosures (3R/5/12, 4/4X).
For QO2175(VH) and QO2200(VH) circuit breakers install three-point latch
trims.
Failure to follow these instructions can result in equipment damage.
Leave at least four circuit spaces of blank fillers or circuit breakers of 125 A or lower
before another QO2150(VH), QO2175(VH) or QO2200(VH) is installed.
Place QO2150(VH), QO2175(VH) and QO2200(VH) next to line end, on the right side
for top incoming applications.
Place QO2150(VH), QO2175(VH) and QO2200(VH) next to line end, on the left side
for bottom incoming applications.
QO2150(VH), QO2175(VH) and QO2200(VH) for single phase applications only.
Table 11 - Three-Point Latch Trim Fronts—Catalog Number10
Type Surface Mounted Flush Mounted
Standard
NC50VS3P NC50VF3P
NC56VS3P NC50VF3P
NC62VS3P NC62VF3P
NC68VS3P NC68VF3P
NC74VS3P NC74VF3P
NC80VS3P NC80VF3P
NC86VS3P NC86VF3P
NC92VS3P NC92VF3P
Hinged
NC62VS3PHR NC62VF3PHR
NC68VS3PHR NC68VF3PHR
NC74VS3PHR NC74VF3PHR
NC80VS3PHR NC80VF3PHR
NC86VS3PHR NC86VF3PHR
80043-712-06 33
10. V=Vented, HR=Hinged Right, 3P=Three Point
Class 1640 Appendix 1: Specifications
Table 11 - Three-Point Latch Trim Fronts—Catalog Number11 - (Continued)
Type Surface Mounted Flush Mounted
NC92VS3PHR NC92VF3PHR
Figure 11 - Three-Point Latch Trim Front
Three-Point Latch
Trim Front
34 80043-712-06
Appendix 2: Accessory Kits Class 1640
Appendix 2: Accessory Kits
An assortment of field-installable accessory kits are available for NQ panelboards:
Equipment Ground Bar Kits
Oversized Neutral Lug Kits for 100–600 A Panelboards
Sub-Feed Lug Kits for 100–400 A Panelboards
Main Lug Kits
Mechanical Lug Kits—Aluminum
Mechanical Lug Kits—Copper
Versa-Crimp Compression Lug Kits—Aluminum
Versa-Crimp Compression Lug Kits—Copper
Line Side Barrier and Neutral Bonding Strap Kits
Equipment Ground Bar Kits
Equipment ground bar kits, suitable for copper or aluminum wire, meet the grounding
needs of NQ panelboards and QONQ load centers.
Table 12 - Equipment Ground Bar Kits Specifications
Panelboard Use Ground Bar Kit Catalog Number
Branch Circuit Mains Rating Aluminum11 Copper12
1–42
600 A Maximum
(1) PK27GTA (1) PK27GTACU
54–84 (2) PK27GTA (2) PK27GTACU
Ground bar mounting locations are identified by the ground symbol stamped
into the back wall of the enclosure.
Oversized Neutral Lug Kits for 100–600 A Panelboards
Oversized neutral lug kits are available for applications where termination conductors
of 3 AWG or larger are required for the neutral.
Table 13 - Oversized Neutral Lug Kits for 100–600 A Panelboard Specifications
Circuit Breaker
Rating Kit Catalog Number Wire Size Al/Cu (mm2)
70 A QO70AN
(1) #12–#2 AWG Al ([1] 3.3–33.6)
(1)#14–#4 AWG Cu ([1] 2.1–21.2)
80–100 A NQ100AN (1) #14–2/0 AWG Al/Cu ([1] 2.1–67.4)
80–120 A Q1100AN (1) #4–1/0 AWG Al/Cu ([1] 21.2–53.5)
80043-712-06 35
11. Aluminum bars suitable for 60°C or 75°C Copper or Aluminum conductors.
12. Copper bars suitable for 60°C or 75°C Copper conductors.
Class 1640 Appendix 2: Accessory Kits
Table 13 - Oversized Neutral Lug Kits for 100–600 A Panelboard Specifications
(Continued)
Circuit Breaker
Rating Kit Catalog Number Wire Size Al/Cu (mm2)
110–150 A Q1150AN13 (1) #1–2/0 AWG Al/Cu ([1] 42.4–67.4)
175–200 A NQ200AN (1) #4 AWG–300 kcmil Al/Cu ([1] 21.2–152)
Sub-Feed Lug Kits for 100–400 A Panelboards
Sub-feed main lugs are available for 100, 225, or 400 A applications.
Table 14 - Sub-Feed Lug Kits for 100–400 A Panelboards Specifications
Main Amps Kit Catalog Number Maximum Circuits
100 NQSFL1 18, 30
225 NQSFL2 3014, 4214, 5414, 7214, 8414
400 NQSFL4 30, 42, 54, 72, 84
Main Lug Kits
Table 15 - Mechanical Lug Kits — Aluminum
Panelboard Amps Kit Catalog Number Wire Size Al/Cu (mm2)
100 Standard #6–2/0 AWG
(13.3–67.43 mm2)
225 Standard #6 AWG–350 kcmil
(13.3–177.3 mm2)
400 Standard
(1) 1/0 AWG–750 kcmil
(2) 1/0 AWG–350 kcmil
([1] 53.48–380 mm2)
([2] 53.48–177.3 mm2)
600
Standard (2) 1/0 AWG–750 kcmil
([2] 53.48–380 mm2)
NQALM6A (3) #6 AWG–250 kcmil
([3] 13.3–127 mm2)
Table 16 - Mechanical Lug Kits — Copper
Panelboard Amps Kit Catalog Number Wire Size Al/Cu (mm2)
100 NQCUM1 #6–2/0 AWG
(13.3–67.43 mm2)
225 NQCUM2 #6 AWG–250 kcmil
(13.3–127 mm2)
36 80043-712-06
13. Use Only use 1/0 (53.5 mm2) copper wire for 150 A branch circuit breaker applications.
14. These panels require an additional 6 inches (152.4 mm) for the box and trim, for proper wire bending space.
Appendix 2: Accessory Kits Class 1640
Table 16 - Mechanical Lug Kits — Copper (Continued)
Panelboard Amps Kit Catalog Number Wire Size Al/Cu (mm2)
400 NQCUM4 (1) 1/0 AWG–750 kcmil
(2) 1/0 AWG–350 kcmil
([1] 53.48–380 mm2)
([2] 53.48–177.3 mm2)
600 NQCUM6
Table 17 - Versa-CrimpCompression Lug Kits — Aluminum
Panelboard Amps Kit Catalog Number Wire Size Al/Cu (mm2) Crimp Tool
100 NQALV1 #8–1/0 AWG
(8.36–53.48 mm2)
VC6 (All)
225 NQALV2 #4 AWG–300 kcmil
(21.15–152 mm2)
400 NQALV4 (2) 2/0 AWG–500 kcmil
([2] 67.43–253.4 mm2)VC6–3, VC6–FT
600 NQALV6
Table 18 - Versa-CrimpCompression Lug Kits — Copper
Panelboard Amps Kit Catalog Number Wire Size Al/Cu (mm2) Crimp Tool
100 NQCUV1 #6–1/0 AWG
(13.30–53.48 mm2)VC6 (All), VC7 (All)
225 NQCUV2 2/0 AWG–300 kcmil
(67.43–152 mm2)
VC6-3, VC7, VC6-FT,
VC7–FT
400 NQCUV4 400–750 kcmil
(202.7–380 mm2)VC6-FT, VC7–FT, VC8
600 NQCUV6 (2) 250–500 kcm
([2) 126.7–253.4mm2)
VC6-3, VC7, VC6-FT,
VC7–FT
Line Side Barrier and Neutral Bonding Strap Kits
Based on the application and the adopted installation code, a Line Side Barrier and
Neutral Bonding Strap may be required. Please select the appropriate barrier from the
table below, based upon the main circuit breaker.
80043-712-06 37
Class 1640 Appendix 2: Accessory Kits
Table 19 - Line Side Barrier and Neutral Bonding Strap Kits
Catalog Number
Contents
Description
Line Lug Cover Neutral Bonding Strap
NQLALLC
NQ LA/LH Line Lug
Cover and Neutral
Bonding Strap and
Lug
NQHJQLLC
NQ H/J/Q Line Lug
Cover and Neutral
Bonding Strap
NQPPLLLC
PowerPacTL Line
Lug Cover and
Neutral Bonding Strap
and Lug
38 80043-712-06
Schneider Electric
800 Federal Street
Andover, MA 01810
USA
888-778-2733
www.se.com
As standards, specifications, and design change from time to time,
please ask for confirmation of the information given in this publication.
© 2007 – 2023 Schneider Electric. All rights reserved.
80043-712-06
www.se.com/mx
Tableros NQ/NQM y centros de carga QONQ
Clase 1640
Boletín de instrucciones
80043-712-06, Rev. 07
02/2023
Información legal
La marca Schneider Electric y cualquier marca comercial de Schneider Electric SE y
sus subsidiarias mencionadas en esta guía son propiedad de Schneider Electric SE o
sus subsidiarias. Todas las demás marcas pueden ser marcas comerciales de sus
respectivos propietarios. Esta guía y su contenido están protegidos por las leyes de
derechos de autor aplicables y se proporciona solo para fines informativos. No se
puede reproducir o transmitir ninguna parte de esta guía de ninguna forma ni por
ningún medio (ya sea electrónico, mecánico, por fotocopia, grabación o de otra
manera), con ningún propósito, sin la previa autorización por escrito de Schneider
Electric.
Schneider Electric no concede ningún derecho o licencia para el uso comercial de la
guía o de su contenido, salvo en el caso de una licencia no exclusiva y personal para
consultarla que se suministra "tal cual".
Solo el personal calificado puede instalar, hacer funcionar y prestar servicios de
mantenimiento a los productos y equipos de Schneider Electric.
Ya que las normas, las especificaciones y los diseños cambian cada cierto tiempo, la
información contenida en esta guía puede estar sujeta a cambios sin previo aviso.
En la medida permitida por la ley vigente, Schneider Electric y sus subsidiarias no
asumen responsabilidad alguna por cualquier error u omisión en el contenido
informativo de este material o de las consecuencias derivadas o resultantes del uso
de la información contenida en este documento.
Clase 1640
Contenido
Información de seguridad................................................................................5
Observe que....................................................................................................5
Introducción.......................................................................................................6
Precauciones de seguridad...............................................................................6
Instalación .........................................................................................................7
Montaje interior para gabinetes de la marca Square D ........................................7
Montaje en superficie (gabinete montado en la pared)...................................7
Montaje empotrado (gabinete empotrado en la pared)...................................8
Instalación del cable/correa de conexión neutra .................................................9
Tableros NQ de 100 o 250 A máximo .........................................................10
Tableros NQ y centros de carga QONQ de 400 o 600 A máximo .................. 11
Instalación y extracción de interruptores automáticos QO y QOB.......................13
Instalación de interruptores automáticos QO y QOB....................................13
Extracción de interruptores automáticos QO y QOB ....................................14
Instrucciones de restablecimiento del interruptor automático .............................15
Preparacn del frente muerto .........................................................................16
Anexo 1: Especificaciones ............................................................................18
Cableado habitual ..........................................................................................18
Alimentación integral principal o secundaria: DJ, FI, KI, H, J, LA, LC, LH,
QB, QD, QG, QJ, QO(B)VH.......................................................................19
Clasificación de tableros eléctricos ..................................................................23
Marcado CE ..................................................................................................32
Restricciones QO2150VH, QO2175VH y QO2200VH .......................................33
Anexo 2: Kits de accesorios..........................................................................35
Kits de barra a tierra del equipo ....................................................................... 35
Kits de anclajes de neutro sobredimensionadas para tableros de 100-600
A...................................................................................................................35
Kits de anclajes de alimentación secundaria para tableros de 100-400 A............36
Kits de anclajes principales.............................................................................36
Kits de barrera lateral de línea y correa de conexión neutra ...............................37
80043-712-06 3
Información de seguridad Clase 1640
Información de seguridad
Asegúrese de leer detenidamente estas instrucciones y realice una inspección visual
del equipo para familiarizarse con él antes de instalarlo, hacerlo funcionar o prestarle
servicio de mantenimiento. Los siguientes mensajes especiales pueden aparecer en
esta guía del usuario o en el equipo para advertirle sobre peligros o para llamar su
atención sobre cierta información que clarifica o simplifica un procedimiento.
La adición de cualquiera de los dos símbolos a una etiqueta de
seguridad de “Peligro” o “Advertencia” indica que existe un
peligro eléctrico que causará lesiones si no se siguen las
instrucciones.
Este es el símbolo de alerta de seguridad. Se usa para avisar
sobre peligros de lesiones personales. Respete todos los
mensajes de seguridad con este símbolo para evitar posibles
lesiones o la muerte.
PELIGRO indica una situación de peligro que, si no se evita, podrá causar
la muerte o lesiones serias.
PELIGRO
ADVERTENCIA
ADVERTENCIA indica una situación peligrosa que, si no se evita, puede causar
la muerte o lesiones graves.
PRECAUCIÓN
PRECAUCIÓN indica una situación peligrosa que, si no se evita, puede causar
lesiones menores o moderadas.
AVISO
AVISO se usa para abordar prácticas no relacionadas con lesiones físicas.
NOTA: Proporciona información adicional para clarificar o simplificar un
procedimiento.
Observe que
Solamente el personal calificado con especialización en electricidad deberá instalar,
hacer funcionar y prestar servicios de mantenimiento al equipo eléctrico. Schneider
Electric no asume responsabilidad alguna por las consecuencias que surjan de la
utilización de este material.
Una persona calificada es aquella que tiene destreza y conocimiento técnico
relacionado con la construcción, instalación y funcionamiento del equipo eléctrico;
asimismo, esta persona ha recibido capacitación sobre seguridad con la cual puede
reconocer y evitar los riesgos involucrados.
Los equipos eléctricos deben transportarse, almacenarse, instalarse y operarse
únicamente en el entorno para el que fueron diseñados.
80043-712-06 5
Clase 1640 Introducción
Introducción
Este boletín contiene instrucciones para instalar tableros de interruptores automáticos
y centros de carga QONQ de la marca Square D™. Estos tableros y centros de carga
están homologados por Underwriters Laboratories (cULus) y admiten interruptores
automáticos de derivación QO™ y QOB.
NOTA: Para obtener asistencia técnica sobre la instalación de este tablero,
comuníquese con el Centro de información al cliente de Schneider Electric
llamando al 1 -888-778-2733.
NOTA: Consulte en las etiquetas del equipo los valores nominales y la
información de seguridad. Junto con este documento se facilitan etiquetas
adicionales para los equipos.
Precauciones de seguridad
PELIGRO
PELIGRO DE DESCARGA ELÉCTRICA, EXPLOSIÓN O DESTELLO POR ARCO
ELÉCTRICO
Utilice el equipo de protección personal (EPP) apropiado y siga las prácticas de
seguridad para trabajos eléctricos. Consulte las normas NFPA 70E, NOM-029-
STPS o CSA Z462 o sus equivalentes locales.
Solo el personal capacitado en electricidad deberá instalar y prestar servicio de
mantenimiento a este equipo.
Desenergice todas las fuentes de alimentación del equipo antes de realizar
cualquier trabajo dentro o fuera de él.
El bloqueo de la operación manual o el bloqueo de la cubierta del motor no
desconecta el circuito secundario del motor.
Siempre utilice un dispositivo detector de tensión de valor nominal adecuado
para confirmar que el equipo esté desenergizado.
Lea y comprenda todo este boletín de instrucciones y la publicación de normas
NEMA PB 1.1 incluida antes de instalar, operar o realizar el mantenimiento de
este equipo.
Los códigos locales varían, se aceptan y hacen cumplir para fomentar la
seguridad en instalaciones eléctricas. Es posible que necesite un permiso para
realizar el trabajo eléctrico y, en algunos casos, algunos códigos pueden
requerir una inspección del trabajo eléctrico efectuado.
Vuelva a colocar todos los dispositivos, las puertas y las cubiertas antes de
energizar este equipo.
No permita que superficies no metálicas de este producto entren en contacto
con pintura, solventes o rocíos basados en derivados del petróleo.
El incumplimiento de estas instrucciones tendrá como resultado la muerte o
lesiones graves.
ADVERTENCIA: Este producto puede exponerlo a químicos, incluidos compuestos de níquel,
que son conocidos por el estado de California como causantes de cáncer, y Bisfenol A (BPA),
que es conocido por el estado de California como causante de defectos de nacimiento u otros
daños reproductivos. Para obtener más información, visite www.P65Warnings.ca.gov.
6 80043-712-06
Instalación Clase 1640
Instalación
Esta sección proporciona instrucciones para los siguientes procedimientos del tablero
NQ y del centro de carga QONQ:
Montaje interior para gabinetes de la marca Square D, página 7.
Instalación del cable/correa de conexión neutra, página 9.
Instalación y extracción de interruptores automáticos QO y QOB, página 13.
Instrucciones de restablecimiento del interruptor automático, página 15.
Preparación del frente muerto, página 16.
Montaje interior para gabinetes de la marca Square D
Con este equipo se ha suministrado una publicación de normas separada, titulada
"Instrucciones generales para la correcta instalación, operación y mantenimiento de
tableros de distribución de 600 voltios o menos" (NEMA PB1.1). Familiarícese con el
contenido de este documento antes de proceder con cualquiera de los siguientes
procedimientos.
Si no ha recibido una copia de este documento o si tiene alguna pregunta sobre este
equipo, póngase en contacto con su distribuidor local o representante de Schneider
Electric.
AVISO
PELIGRO DE DAÑO AL EQUIPO DEBIDO A CONEXIONES SUELTAS
Asegúrese de que todas las conexiones estén bien apretadas.
Antes de apretar las conexiones, consulte la etiqueta de información sobre el
par de apriete del tablero.
El incumplimiento de estas instrucciones podría provocar daños en el
equipo.
Para montar e instalar correctamente el interior del tablero NQ o del centro de carga
QONQ, consulte la publicación de normas NEMA PB 1.1 y siga las instrucciones que
se indican a continuación para cualquiera de los dos casos, ya sea Montaje en
superficie (gabinete montado en la pared), página 7 oMontaje empotrado (gabinete
empotrado en la pared), página 8.
Montaje en superficie (gabinete montado en la pared)
1. Monte el gabinete según las instrucciones de la publicación de normas NEMA PB
1.1.
2. Retire el frente muerto de los soportes del frente muerto.
3. Instale el interior como se describe a continuación:
a. Coloque el interior sobre los montantes del gabinete. No es necesario un
tornillo elevador (consulte Montaje interior para gabinetes de la marca
Square D, página 7).
b. Apriete las tuercas Keps contra los rieles laterales interiores hasta que los
rieles queden contra la parte posterior del gabinete.
80043-712-06 7
Clase 1640 Instalación
4. En función de la aplicación y del código de instalación adoptado, pueden ser
necesarias una correa de conexión neutra y una barrera lateral de línea.
Consulte Instalación del cable/correa de conexión neutra, página 9 yAnexo 2:
Kits de accesorios, página 35.
5. Coloque las etiquetas del equipo (situadas en el conjunto de la bolsa) siguiendo
las instrucciones del reverso de la hoja de etiquetas del equipo. Consulte los
códigos y normas locales.
6. Vuelva a montar el frente muerto después del cableado.
Montaje empotrado (gabinete empotrado en la pared)
1. Monte el gabinete según las instrucciones de la publicación de normas NEMA PB
1.1.
2. Retire el frente muerto de los soportes del frente muerto.
3. Instale el interior como se describe a continuación:
a. Enrosque los (4) tornillos elevadores autorroscantes 10-32 x 0.875 in
suministrados con la moldura a ras en los rieles laterales.
b. Coloque el interior sobre los montantes del gabinete (consulte Montaje
interior de gabinetes de la marca Square D, página 9). Coloque las tuercas
Keps en los espárragos del gabinete, pero no las apriete.
c. Ajuste los tornillos de modo que el labio del frente muerto quede
aproximadamente a 6,35 mm (0.25 in) de la línea de la pared.
d. Apriete las tuercas Keps contra las barandillas laterales.
4. En función de la aplicación y del código de instalación adoptado, pueden ser
necesarias una correa de conexión neutra y una barrera lateral de línea.
Consulte los códigos y normas locales. Consulte Instalación del cable/correa de
conexión neutra, página 9 yAnexo 2: Kits de accesorios, página 35.
5. Coloque las etiquetas del equipo (situadas en el conjunto de la bolsa) siguiendo
las instrucciones del reverso de la hoja de etiquetas del equipo.
6. Vuelva a montar el frente muerto después del cableado.
8 80043-712-06
Instalación Clase 1640
Figura 1 - Montaje interior de gabinetes de la marca Square D
Soporte de frente muerto
Espárrago del gabinete
Tuerca Keps
Gabinete
Frente muerto
Pared
Tornillo de elevación
Riel lateral
0.25 pulg.
(6.35 mm)
Instalación del cable/correa de conexión neutra
En función de la aplicación y del código de instalación adoptado, puede ser necesaria
una barrera en el lado de la línea y una correa de conexión neutra.
Para conectar correctamente el neutro al tablero, siga las instrucciones para Tableros
NQ de 100 o 250 A máximo, o Tableros NQ y centros de carga QONQ de 400 o 600 A
máximo, página 11.
80043-712-06 9
Clase 1640 Instalación
PELIGRO
PELIGRO DE DESCARGA ELÉCTRICA, EXPLOSIÓN O DESTELLO POR ARCO
ELÉCTRICO
Utilice el equipo de protección personal (EPP) apropiado y siga las prácticas de
seguridad para trabajos eléctricos. Consulte las normas NFPA 70E, NOM-029-
STPS o CSA Z462 o sus equivalentes locales.
Desenergice todas las fuentes de alimentación del equipo antes de realizar
cualquier trabajo dentro o fuera de él.
El bloqueo de la operación manual o el bloqueo de la cubierta del motor no
desconecta el circuito secundario del motor.
La correa/cable de conexión neutra solo debe utilizarse cuando el tablero se
instala como equipo de entrada de servicio.
No mezcle los tornillos de montaje con los tornillos del frente muerto.
El incumplimiento de estas instrucciones tendrá como resultado la muerte o
lesiones graves.
NOTA: Consulte Kits de barrera lateral de línea y correa de conexión neutra,
página 38 para obtener información.
NOTA: Los términos "correa de conexión neutra" y "cable de conexión neutra"
describen los componentes que cumplen los requisitos de un "conductor de
conexión neutra". Son términos equivalentes.
Tableros NQ de 100 o 250 A máximo
Para instalar una correa de conexión neutra en tableros NQ con redes de hasta 225 A
(con zapatas principales o interruptor automático principal), o hasta 250 A con un
interruptor automático principal montado en fábrica, consulte Instalación de la correa
de conexión: 100 o 250 A máximo en tableros NQ, página 11 y siga las siguientes
instrucciones.
1. Alinee la correa de conexión en el riel lateral, como se muestra en la figura.
NOTA: Para algunas aplicaciones, puede ser necesario retirar la zapata (no
aparece en la imagen) antes de instalar la correa de conexión.
2. Inserte los dos tornillos de montaje, como se muestra en la imagen. Apriete el
tornillo 10-32 a 10-12 lb-in (1.1-1.4 N-m) y el 1/4-20 a 25-30 lb-in (2.8-3.4 N-m).
NOTA: Los tornillos de montaje de la zapata se incluyen en el conjunto de la
bolsa de la correa de conexión.
a. Si la zapata se retiró en el paso 1 anterior, vuelva a instalarla en la parte
superior de la correa de conexión.
b. Utilice un tornillo de 1/4-20 x 9/16 in en el montaje para interiores 100/225 A
sin opciones. Consulte las notas C y D para conocer otras opciones.
c. Utilice el tornillo 1/4-20 x 11/16 in de montaje de la zapata en aplicaciones
con zapata de alimentación de paso, zapata de alimentación secundaria,
interruptor automático de alimentación secundaria o aplicaciones con neutro
al 200%.
d. Utilice el tornillo de montaje de la zapata de 1/4-20 x 7/8 in en aplicaciones
con neutros al 200% y con zapatas de alimentación de paso, zapatas de
alimentación secundaria o interruptores automáticos de alimentación
secundaria.
10 80043-712-06
Instalación Clase 1640
Figura 2 - Instalación de la correa de conexión: tableros NQ de 100 o 250 A máximo
NOTA: Para las opciones de zapatas de correa de conexión, consulte C y D para conocer la longitud correcta
del tornillo 1/4-20.
Tornillos de
montaje
Correa de conexión
1/4-20 x 9/16 pulg.
10/32 x 7/16 pulg.
Barra del neutro
Riel lateral
Tableros NQ y centros de carga QONQ de 400 o 600 A máximo
Para instalar un cable conexión neutra en un tablero NQ de 400 o 600 A máximo y en
un centro de carga QONQ, consulte Instalación del cable de conexión: tableros NQ y
centros de carga QONQ de 400 o 600 A máximo, página 12 y siga las instrucciones
que se indican a continuación.
1. Alinee la zapata en el orificio de montaje del riel lateral, como se muestra en la
imagen.
2. Apriete el tornillo de montaje de la zapata contra el riel lateral a 1,1-1,4 N-m (10-
12 lb-in).
3. Alinee el cable de conexión, tal como se muestra en la imagen, e insértelo en los
orificios de montaje de la zapata y el neutro.
4. Apriete el tornillo de fijación del cable de la zapata y el tornillo de fijación del
cable neutro a 5,1-5,6 N-m (45-50 lb-in).
80043-712-06 11
Clase 1640 Instalación
Figura 3 - Instalación del cable de conexión: tableros NQ y centros de carga QONQ de 400 o 600 A máximo
Neutro
Tornillo de montaje
de la zapata
Cable de conexión
Orificio de montaje del cable de conexión
Riel lateral
Zapata
Orificio de montaje
del riel lateral
Tornillo de fijación
del cable neutro
Tornillo
de fijación
del cable
de la zapata
Orificio de montaje del cable de conexión
12 80043-712-06
Instalación Clase 1640
Instalación y extracción de interruptores automáticos QO y
QOB
PELIGRO
PELIGRO DE DESCARGA ELÉCTRICA, EXPLOSIÓN O DESTELLO POR ARCO
ELÉCTRICO
Utilice el equipo de protección personal (EPP) apropiado y siga las prácticas de
seguridad para trabajos eléctricos. Consulte las normas NFPA 70E, NOM-029-
STPS o CSA Z462 o sus equivalentes locales.
Solo el personal capacitado en electricidad deberá instalar y prestar servicio de
mantenimiento a este equipo.
Desenergice todas las fuentes de alimentación del equipo antes de realizar
cualquier trabajo dentro o fuera de él.
El bloqueo de la operación manual o el bloqueo de la cubierta del motor no
desconecta el circuito secundario del motor.
Siempre utilice un dispositivo detector de tensión de valor nominal adecuado
para confirmar que el equipo esté desenergizado.
Todos los espacios no utilizados deben rellenarse con placas de relleno.
Vuelva a colocar todos los dispositivos, las puertas y las cubiertas antes de
energizar este equipo.
El incumplimiento de estas instrucciones tendrá como resultado la muerte o
lesiones graves.
ADVERTENCIA
PELIGRO DE LESIONES PERSONALES O DAÑOS MATERIALES
Este equipo está diseñado y probado por Schneider Electriccon niveles de
rendimiento que cumplen las normas de Underwriter's Laboratories®(UL®) y el
listado de Normas Oficiales Mexicanas (NOM).
Utilice solamente accesorios e interruptores automáticos de la marca Square
D.
El incumplimiento de estas instrucciones podría tener como resultado la
muerte, lesiones graves o provocar daños en el equipo.
Instalación de interruptores automáticos QO y QOB
Consulte Instalación y extracción de interruptores automáticos QO y QOB, página 15,
para las siguientes instrucciones:
1. Desconecte toda la alimentación del tablero.
2. Desactive el interruptor automático.
3. Quite el frente muerto.
4. Encaje el extremo del terminal del cable del interruptor automático en el riel de
montaje.
80043-712-06 13
Clase 1640 Instalación
5. Enganche el conector de derivación.
Para interruptores automáticos QO: Empuje hacia dentro hasta que las garras
de enchufe encajen completamente en el conector de derivación.
Para interruptores automáticos QO: Empuje hacia dentro hasta que el
conector del interruptor automático quede centrado en el orificio de montaje del
conector de derivación. Enganche el tornillo en el orificio del conector de
derivación y apriételo a los valores de torque indicados en el diagrama interior de
cableado y torque.
6. Instale el cable de carga.
7. Vuelva a instalar el frente muerto.
8. Instale una placa de relleno en todos los espacios de interruptores automáticos
de derivación no utilizados.
Extracción de interruptores automáticos QO y QOB
Consulte Instalación y extracción de interruptores automáticos QO y QOB, página 15,
para las siguientes instrucciones:
1. Desconecte toda la alimentación del tablero.
2. Quite el frente muerto.
3. Extraiga el cable de carga.
4. Desenganche el conector de derivación.
Para interruptores automáticos QO:
Jale hacia afuera hasta que las garras de enchufe desenganchen
completamente el conector de derivación.
Para interruptores automáticos QOB:
Afloje el tornillo del conector del interruptor automático y extraiga el interruptor
automático del conector de derivación.
5. Retire el extremo del terminal del cable del interruptor automático del riel de
montaje.
6. Vuelva a instalar el frente muerto.
7. Instale una placa de relleno en todos los espacios de interruptores automáticos
de derivación no utilizados.
14 80043-712-06
Instalación Clase 1640
Figura 4 - Instalación y extracción de interruptores automáticos QO y QOB
QO
QOB
Mordaza enchufable
Conector de derivación
Conector de derivación
Tornillo
conector
atornillable
Riel
Terminal
del cable
Terminal
del cable
Riel
Instrucciones de restablecimiento del interruptor
automático
Si se dispara el interruptor automático, la palanca estará en la posición intermedia
entre ON y OFF. Para restablecer el interruptor automático, empuje la palanca a la
posición OFF y, a continuación, a la posición ON.
80043-712-06 15
Clase 1640 Instalación
Figura 5 - Posiciones de la palanca del interruptor automático
ONOFFDisparado
Palanca
Indicador Visi-Trip
NOTA: Cuando el interruptor automático se ha disparado, la palanca adopta una
posición central y el indicador rojo Visi-Trip aparece en una ventana de la caja del
interruptor automático. El indicador rojo Visi-Trip solo es visible cuando se dispara
el interruptor automático.
Preparación del frente muerto
PELIGRO
PELIGRO DE DESCARGA ELÉCTRICA, EXPLOSIÓN O DESTELLO POR ARCO
ELÉCTRICO
Utilice el equipo de protección personal (EPP) apropiado y siga las prácticas de
seguridad para trabajos eléctricos. Consulte las normas NFPA 70E, NOM-029-
STPS o CSA Z462 o sus equivalentes locales.
Antes de energizar el tablero, todos los espacios no utilizados deben rellenarse
con placas de relleno.
Vuelva a colocar todos los dispositivos, las puertas y las cubiertas antes de
energizar este equipo.
El incumplimiento de estas instrucciones tendrá como resultado la muerte o
lesiones graves.
16 80043-712-06
Instalación Clase 1640
Figura 6 - Diagrama del frente muerto
Placas de relleno
Frente muerto
NOTA: En la parte posterior del frente muerto figura el número de catálogo de las
placas de relleno compatibles correspondientes.
80043-712-06 17
Clase 1640 Anexo 1: Especificaciones
Anexo 1: Especificaciones
Cableado habitual
Tabla 1 - Cableado habitual de tableros1
Tensión CA Tableros de 1 fase Tableros de 1 fase
Fase Conductores Fase Conductores
208Y/120 — — 3 4
120/240 1 3 — —
24021 2 3 4
24031 3 — —
240/1204— — 3 4 Delta
18 80043-712-06
1. En el tablero hay información adicional. Consulte la capacidad del interruptor automático principal, si se utiliza.
2. Para este sistema, no se utiliza el neutro y solo deben emplearse interruptores automáticos de 240 Vca como mínimo. No utilice interruptores
automáticos de 120 V o 120/240 Vca.
3. Para un sistema de fase "B" conectado a tierra, solo deben utilizarse interruptores automáticos de 240 Vca como mínimo. No utilice
interruptores automáticos de 120 V o 120/240 Vca.
4. Cuando se cablea para un sistema delta, las fases "A" y "C" deben ser de 120 V a neutro, la fase "B" de 208 V a neutro. Conecte solo
interruptores automáticos de 240 Vca como mínimo. No utilice interruptores automáticos de 120 V o 120/240 V para la fase "B".
Anexo 1: Especificaciones Clase 1640
Alimentación integral principal o secundaria: DJ, FI, KI, H, J, LA, LC,
LH, QB, QD, QG, QJ, QO(B)VH
Figura 7 - Zapatas principales NQ/NQM 100-225 A o diagrama del interruptor automático principal 100-250
A
80043-712-06 19
Clase 1640 Anexo 1: Especificaciones
Figura 8 - Tablero NQ o centro de carga QONQ de 400-600 A o interruptor automático principal con o sin
diagrama de zapatas de paso
Carga
Zapatas de paso
(cuando está instalada)
Interruptor automático
principal integral
(cuando está instalada)
Conexión del gabinete
(cuando sea necesario) Neutro
Línea
Línea
Tierra
(cuando sea
necesario)
20 80043-712-06
Anexo 1: Especificaciones Clase 1640
Figura 9 - Tablero NQ o centro de carga QONQ Interruptor automático principal de 400-600 A con zapatas
de alimentación de paso o interruptores automáticos de alimentación secundaria
Interruptor(es)
automático(s)
de alimentación
secundaria
Carga Carga
(cuando está instalada)
Carga
Conexión del gabinete
(cuando sea necesario) Neutro
Tierra
(cuando sea
necesario)
Interruptor automático
principal integral
(cuando está instalada)
Línea
80043-712-06 21
Clase 1640 Anexo 1: Especificaciones
Figura 10 - Tablero NQ habitual con diagrama de barra partida
Interruptor automático
principal integral
(cuando está instalada)
Conexión del gabinete
(cuando sea necesario) Neutro
Tierra
Línea
Línea
(cuando sea
necesario)
22 80043-712-06
Anexo 1: Especificaciones Clase 1640
Clasificación de tableros eléctricos
Consulte los códigos y normas locales para obtener más información. La etiqueta del
sistema nominal de serie se encuentra en el conjunto de la bolsa.
Valores nominales de los interruptores automáticos conectados en serie (RMS
simétrico)
Las clasificaciones de serie que figuran con tensiones de sistema más elevadas
se aplican para tensiones de sistema más bajas (ejemplo: 240 3P/3W abarca
208Y/120 3P/4W).
Las pruebas de cortocircuito se realizan al 100-105% de la tensión nominal
máxima del tablero.
"MC" significa interruptores automáticos de misión crítica.
El tipo LG mostrado puede sustituirse por LJ y LL.
A menos que se indique lo contrario, los interruptores automáticos principales
pueden aplicarse al amperaje máximo disponible.
Los sufijos HID, SWD y SWN pueden aplicarse también a los interruptores
automáticos de derivación correspondientes que se muestran a continuación.
Los interruptores automáticos QO(B) que se muestran a continuación pueden
sustituirse por los interruptores automáticos QO(B)H, QO(B)VH y QH(B).
En los sistemas trifásicos no se pueden usar interruptores automáticos CAFI
bipolares.
Tabla 2 - Máxima tensión CA del sistema: 120/240 1P/3W, 208Y/120 3P/4W, 240/120 3P/4W
Corriente nominal
de cortocircuito
máxima
Interruptores automáticos
principales y fusibles principales
remotos de la marca Square D
Designación del catálogo de interruptores automáticos de derivación de
la marca Square D y rangos de amperaje permitidos
Tipo 1 polo 2 polos 3 polo
18,000 LA/LH MC QO(B) 15-30 A 15-30 A
22,000 QO(B) VH
QOB-VH
QO(B) 15-70 A 15-125 A
QO(B) GFI 15-30 A 15-60 A
QO(B) EPD 15-30 A 15-60 A
QO(B) PL 15-30 A 15-60 A
QO(B) AFI 15-20 A — —
QO(B) CAFI 15-20 A 15-20 A
QO(B) DF 15-20 A — —
80043-712-06 23
Clase 1640 Anexo 1: Especificaciones
Tabla 2 - Máxima tensión CA del sistema: 120/240 1P/3W, 208Y/120 3P/4W, 240/120 3P/4W (Continuación)
Corriente nominal
de cortocircuito
máxima
Interruptores automáticos
principales y fusibles principales
remotos de la marca Square D
Designación del catálogo de interruptores automáticos de derivación de
la marca Square D y rangos de amperaje permitidos
Tipo 1 polo 2 polos 3 polo
25,000
QD
QO(B) 15-70 A 15-125 A
QOB-VH — 150 A
QO(B) PL 15-30 A 15-60 A
QO(B) GFI 15-30 A 15-60 A
QO(B) EPD 15-30 A 15-60 A
QO(B) AFI 15-20 A — —
QO(B) CAFI 15-20 A 15-20 A
QO(B) DF 15-20 A — —
ED
QO(B) 15-70 A 15-125 A
QO(B) GFI 15-30 A 15-60 A
QO(B) EPD 15-30 A 15-60 A
QO(B) AFI 15-20 A — —
QO(B) CAFI 15-20 A 15-20 A
QO(B) DF 15-20 A — —
BD, HD, JD, LD
QO(B) 15-70 A 15-125 A
QOB-VH — 150 A
QO(B) PL 15-30 A 15-60 A
QO(B) GFI 15-30 A 15-60 A
QO(B) EPD 15-30 A 15-60 A
QO(B) AFI 15-20 A — —
BD, HD, JD, LD
QO(B) CAFI 15-20 A 15-20 A
QO(B) DF 15-20 A — —
42,000 LA, MA QO(B) 15-30 A 15-30 A
24 80043-712-06
Anexo 1: Especificaciones Clase 1640
Tabla 2 - Máxima tensión CA del sistema: 120/240 1P/3W, 208Y/120 3P/4W, 240/120 3P/4W (Continuación)
Corriente nominal
de cortocircuito
máxima
Interruptores automáticos
principales y fusibles principales
remotos de la marca Square D
Designación del catálogo de interruptores automáticos de derivación de
la marca Square D y rangos de amperaje permitidos
Tipo 1 polo 2 polos 3 polo
65,000
QG
QO(B) 15-70 A 15-125 A
QO(B) VH 15-70 A 15-125 A
QOB-VH — 150 A
QO(B) GFI 15-30 A 15-60 A
QO(B) PL 15-30 A 15-60 A
QO(B) AFI 15-20 A — —
QO(B) CAFI 15-20 A 15-20 A
QO(B) DF 15-20 A — —
EG QO(B) 15-70 A 15-125 A
EG
QO(B) GFI 15-30 A 15-60 A
QO(B) EPD 15-30 A 15-60 A
QO(B) EPE ———
QO(B) AFI 15-20 A — —
QO(B) CAFI 15-20 A 15-20 A
QO(B) DF 15-20 A — —
BG, HG, JG, LG
QO(B) 15-70 A 15-125 A
QOB-VH — 150 A
QO(B) PL 15-30 A 15-60 A
QO(B) GFI 15-30 A 15-60 A
QO(B) EPD 15-30 A 15-60 A
QO(B) AFI 15-20 A — —
QO(B) CAFI 15-20 A 15-20 A
QO(B) DF 15-20 A — —
80043-712-06 25
Clase 1640 Anexo 1: Especificaciones
Tabla 2 - Máxima tensión CA del sistema: 120/240 1P/3W, 208Y/120 3P/4W, 240/120 3P/4W (Continuación)
Corriente nominal
de cortocircuito
máxima
Interruptores automáticos
principales y fusibles principales
remotos de la marca Square D
Designación del catálogo de interruptores automáticos de derivación de
la marca Square D y rangos de amperaje permitidos
Tipo 1 polo 2 polos 3 polo
100,000
QJ
QO(B) 15-70 A 15-125 A
QOB-VH — 150 A
QO(B) PL 15-30 A 15-60 A
QO(B) GFI 15-30 A 15-60 A
QO(B) EPD 15-30 A 15-60 A
QO(B) AFI 15-20 A — —
QO(B) CAFI 15-20 A 15-20 A
QO(B) DF 15-20 A — —
EJ
QO(B) 15-70 A 15-125 A
QO(B) GFI 15-30 A 15-60 A
EJ
QO(B) EPD 15-30 A 15-60 A
QO(B) AFI 15-20 A — —
QO(B) CAFI 15-20 A 15-20 A
QO(B) DF 15-20 A — —
BJ, HJ, JJ
QO(B) 15-70 A 15-125 A
QOB-VH — 150 A
QO(B) PL 15-30 A 15-60 A
QO(B) GFI 15-30 A 15-60 A
QO(B) EPD 15-30 A 15-60 A
QO(B) AFI 15-20 A — —
QO(B) CAFI 15-20 A 15-20 A
QO(B) DF 15-20 A — —
LJ
QO(B) 15-70 A 15-125 A
QOB-VH — 150 A
QO(B) GFI 15-60 A
QO(B) EPD 15-60 A
QO(B) AFI 15-20 A — —
QO(B) CAFI 15-20 A 15-20 A
QO(B) DF 15-20 A — —
125,000 HL, JL
QO(B) 15-70 A 15-125 A
QOB-VH — 150 A
QO(B) PL 15-30 A 15-60 A
QO(B) GFI 15-30 A 15-60 A
QO(B) EPD 15-30 A 15-60 A
QO(B) AFI 15-20 A — —
QO(B) CAFI 15-20 A 15-20 A
QO(B) DF 15-20 A — —
200,000
HR, JR
QO(B) 15-70 A 15-125 A
QO(B) GFI 15-30 A 15-60 A
QO(B) EPD 15-30 A 15-60 A
QO(B) AFI 15-20 A — —
HR, JR
QO(B) CAFI 15-20 A 15-20 A
QO(B) DF 15-20 A — —
26 80043-712-06
Anexo 1: Especificaciones Clase 1640
Tabla 3 - Máxima tensión CA del sistema: 240 1P/2W
Corriente nominal
de cortocircuito
máxima
Interruptores automáticos
principales y fusibles principales
remotos de la marca Square D
Designación del catálogo de interruptores automáticos de derivación de
la marca Square D y rangos de amperaje permitidos
Tipo 1 polo 2 polos 3 polo
25,000 QD, BD, HD, JD, LD QO(B) H 15-100 A
42,000 LA, MA QDL 70-225 A
65,000 QG, BG, HG, JG, LG QO(B) H 15-100 A
100,000 BJ, HJ, JJ, LJ QO(B) H 15-100 A
125,000 HL, JL QO(B) H 15-100 A
Tabla 4 - Máxima tensión CA del sistema: 208Y/120 3P/4W
Corriente nominal
de cortocircuito
máxima
Interruptores automáticos
principales y fusibles principales
remotos de la marca Square D
Designación del catálogo de interruptores automáticos de derivación de
la marca Square D y rangos de amperaje permitidos
Tipo 1 polo 2 polos 3 polo
18,000 LA/LH MC QO(B) 15-30 A
22,000 QO(B) VH, QOB-VH QO(B) GFI 15-50 A
25,000 QD, ED, FD, BD, HD, JD QO(B) GFI 15-50 A
LD QO(B) GFI 15-30 A
65,000 QG, EG, BG, HG, JG QO(B) GFI 15-50 A
LG QO(B) GFI 15-30 A
100,000 QJ
QO(B) 15-30 A
QO(B) VH 15-100 A
QOB-VH 110-150 A
QO(B) PL 15-30 A
QO(B) GFI 15-50 A
QO(B) EPD 15-50 A
QO(B) EPE 15-50 A
EJ, BJ, HJ, JJ QO(B) GFI 15-50 A
80043-712-06 27
Clase 1640 Anexo 1: Especificaciones
Tabla 5 - Máxima tensión CA del sistema: 240/120 3P/4W, 240 3P/3W
Corriente nominal
de cortocircuito
máxima
Interruptores automáticos
principales y fusibles principales
remotos de la marca Square D
Designación del catálogo de interruptores automáticos de derivación de
la marca Square D y rangos de amperaje permitidos
Tipo 1 polo 2 polos 3 polo
22,000 QOB VH
QOB-VH
QO(B) 15-100 A
QO(B) EPD 15-50 A
QO(B) EPE 15-50 A
25,000
QD QO(B) 15-30 A
QD
QO(B) VH 15-100 A
QOB-VH 110-150 A
QO(B) PL 15-30 A
QO(B) EPD 15-50 A
QO(B) EPE 15-50 A
ED
QO(B) 15-100 A
QO(B) EPD 15-50 A
QO(B) EPE 15-50 A
BD, HD, JD
QO(B) 15-100 A
QOB-VH 110-150 A
QO(B) PL 15-30 A
QO(B) EPD 15-50 A
QO(B) EPE 15-50 A
LD
QO(B) 15-30 A
QO(B) VH 15-100 A
QOB-VH 110-150 A
QO(B) EPD 15-30 A
QO(B) EPE 15-30 A
42,000 LA, MA QDL 70-225 A
QO(B) VH 15-30 A
MG QOB-VH 110-150 A
65,000
QG
QO(B) 15-30 A
QO(B) VH 15-100 A
QG QOB-VH 110-150 A
QO(B) PL 15-30 A
EG
QO(B) 15-100 A
QOB-VH 110-125 A
QO(B) EPD 15-50 A
QO(B) EPE 15-50 A
BG, HG, JG
QO(B) 15-100 A
QOB-VH 110-150 A
QO(B) PL 15-30 A
QO(B) EPD 15-50 A
QO(B) EPE 15-50 A
LG
QO(B) 15-30 A
QO(B) VH 15-100 A
QOB-VH 110-150 A
QO(B) EPD 15-30 A
QO(B) EPE 15-30 A
28 80043-712-06
Anexo 1: Especificaciones Clase 1640
Tabla 5 - Máxima tensión CA del sistema: 240/120 3P/4W, 240 3P/3W (Continuación)
Corriente nominal
de cortocircuito
máxima
Interruptores automáticos
principales y fusibles principales
remotos de la marca Square D
Designación del catálogo de interruptores automáticos de derivación de
la marca Square D y rangos de amperaje permitidos
Tipo 1 polo 2 polos 3 polo
100,000
EJ
QO(B) 15-100 A
QOB-VH 110-125 A
QO(B) EPD 15-50 A
QO(B) EPE 15-50 A
BJ, HJ, JJ
QO(B) 15-100 A
QOB-VH 110-150 A
QO(B) PL 15-30 A
QO(B) EPD 15-50 A
QO(B) EPE 15-50 A
LJ
QO(B) 15-30 A
QO(B) VH 15-100 A
QOB-VH 110-150 A
125,000
HL, JL QO(B) 15-100 A
HL, JL
QOB-VH 110-150 A
QO(B) PL 15-30 A
QO(B) EPD 15-50 A
QO(B) EPE 15-50 A
200,000 HR, JR
QO(B) 15-100 A
QOB-VH 110-150 A
Tabla 6 - Máxima tensión CA del sistema: 120/240 1P/3W, 208Y/120 3P/4W, 240/120 3P/3W
Corriente nominal
de cortocircuito
máxima
Interruptores automáticos
principales y fusibles principales
remotos de la marca Square D
Designación del catálogo de interruptores automáticos de derivación de
la marca Square D y rangos de amperaje permitidos
Tipo 1 polo 2 polos 3 polo
42,000 Fusibles de clase T3
de 400 A máx. QO(B) VH 15-70 A 15-125 A
65,000
Fusibles de clase J
de 400 A máx.
QO(B) VH 15-70 A 15-125 A
QO(B) AFI 15-20 A — —
QO(B) CAFI 15-20 A 15-20 A
QO(B) DF 15-20 A — —
Fusibles de clase T6
de 400 A máx.
QO(B) VH 15-70 A 15-125 A
QOB-VH — 150 A
QO(B) AFI 15-20 A — —
QO(B) CAFI 15-20 A 15-20 A
QO(B) DF 15-20 A — —
100,000 Fusibles de clase T3
de 200 A máx.
QO(B) 15-70 A 15-125 A
QO(B) GFI 15-30 A 15-60 A
QO(B) EPD 15-30 A 15-60 A
QO(B) AFI 15-20 A — —
QO(B) CAFI 15-20 A 15-20 A
QO(B) DF 15-20 A — —
80043-712-06 29
Clase 1640 Anexo 1: Especificaciones
Tabla 6 - Máxima tensión CA del sistema: 120/240 1P/3W, 208Y/120 3P/4W, 240/120 3P/3W (Continuación)
Corriente nominal
de cortocircuito
máxima
Interruptores automáticos
principales y fusibles principales
remotos de la marca Square D
Designación del catálogo de interruptores automáticos de derivación de
la marca Square D y rangos de amperaje permitidos
Tipo 1 polo 2 polos 3 polo
200,000
Fusibles de clase T6 o J
de 200 A máx.
QO(B) 15-70 A 15-125 A
QO(B) GFI 15-30 A 15-60 A
QO(B) EPD 15-30 A 15-60 A
Fusibles de clase T3
de 400 A máx.
QO(B) 15-70 A 15-125 A
QO(B) GFI 15-30 A 15-60 A
QO(B) EPD 15-30 A 15-60 A
Tabla 7 - Máxima tensión CA del sistema: 208Y/120 3P/4W
Corriente nominal
de cortocircuito
máxima
Interruptores automáticos
principales y fusibles principales
remotos de la marca Square D
Designación del catálogo de interruptores automáticos de derivación de
la marca Square D y rangos de amperaje permitidos
Tipo 1 polo 2 polos 3 polo
65,000 de clase J de 400 A máx. QO(B) GFI 15-50 A
100,000 Clase T3 de 200 A máx. QO(B) GFI 15-50 A
200,000
Fusibles de clase T6 o J
de 200 A máx. QO(B) GFI 15-50 A
Fusibles de clase T3 de 400 A máx. QO(B) GFI 15-50 A
Tabla 8 - Máxima tensión CA del sistema: 240/120 3P/4W, 240 3P/3W
Corriente nominal
de cortocircuito
máxima
Interruptores automáticos
principales y fusibles principales
remotos de la marca Square D
Designación del catálogo de interruptores automáticos de derivación de
la marca Square D y rangos de amperaje permitidos
Tipo 1 polo 2 polos 3 polo
50,000 Fusibles de clase T3 de 600 A máx. QO(B) VH 15-30 A
65,000
Fusibles de clase J de 400 A máx. QO(B) VH 15-100 A
Fusibles de clase T6 de 400 A máx.
QO(B) VH 15-100 A
QOB-VH 110-150 A
100,000 Fusibles de clase T3 de 200 A máx.
QO(B) 15-100 A
QO(B) EPD 15-50 A
QO(B) EPE 15-50 A
200,000
Fusibles de clase T6 o J
de 200 A máx.
QO(B) 15-100 A
QO(B) EPD 15-50 A
QO(B) EPE 15-50 A
Fusibles de clase T3
de 400 A máx.
QO(B) 15-100 A
QO(B) EPD 15-50 A
QO(B) EPE 15-50 A
30 80043-712-06
Anexo 1: Especificaciones Clase 1640
Tabla 9 - Selectividad de interruptores de misión crítica del panel NQ
SCCR máxima
(RMS simétrica)
Interruptores automáticos
principales integrales o
remotos
Interruptores automáticos de derivación
Tipo51 polo 2 polos 3 polo
Totalmente nominal y selectivo hasta 10
kA
a 208Y/120 Vca o
a 240/120 Vca
J-W, 250 A
L-W, 250 A
QOB
10-70 10-125 10-125
QOB-H
QOB-VH
QH
Serie nominal y selectiva hasta 12 kA
a 208Y/120 Vca o
a 240/120 Vca
J-W, 250 A
QOB
10-70 10-125 10-60
QOB-H
QOB-VH
QH
Serie nominal y selectiva hasta 15 kA
a 208Y/120 Vca o
a 240/120 Vca
J-W, 250 A
QOB
10-60 10-60 10-30
QOB-H
QOB-VH
QH
Serie nominal y selectiva hasta 18 kA
a 208Y/120 Vca o
a 240/120 Vca
J-W, 250 A
QOB
10-30 10-30
QOB-H
QOB-VH
QH
L-W, 250 A
QOB
10-60 10-60 10-60
QOB-H
QOB-VH
QH
Serie nominal y selectiva hasta 30 kA
a 208Y/120 Vca o
a 240/120 Vca
L-W, 400 A
L-W, 600 A
QOB
15-70 15-150 15-150
QOB-H
QOB-VH
QH
80043-712-06 31
5. Incluye interruptores automáticos AFI, CAFI, EPD y GFI.
Clase 1640 Anexo 1: Especificaciones
Tabla 10 - Corriente nominal de cortocircuito6para interiores de tomas principales con tomas de
alimentación secundaria o de paso
Máxima tensión CA
del sistema Corriente nominal
máxima Circuitos de
derivación7Aplicaciones Sumando8
Corriente nominal
de cortocircuito
máxima9
240
100 18, 30 SFL y FTL
10,000
225
30, 42, 54, 72, 84, 96 SFL 152.4 mm (6 in)
42
FTL
30, 54, 72, 84, 96 152.4 mm (6 in)
400
30, 42, 54, 72, 84
SFL
25,000
96 10,000
30, 84
FTL
25,000
96 10,000
42, 54, 72 152.4 mm (6 in)
25,000
600
30, 42, 54, 72, 84
FTL 304.8 mm (12 in)
96 10,000
Marcado CE
Los interiores con la marca "CE" cumplen las normas IEC 61439-1 e IEC 61439-
2.
Los interiores de las zapatas principales con la marca "CE" han sido probados
para soportar 10,000 amperios simétricos RMS durante 30 ciclos.
Los interiores con la marca "CE" solo están aprobados para su uso con
interruptores automáticos de derivación QOXD o QOBXD que lleven la marca
"CE".
32 80043-712-06
6. Esta clasificación se aplica a los interiores de zapatas principales, equipados con zapatas de alimentación secundaria o de paso, en los que
el dispositivo que alimenta el interior es desconocido o no es un dispositivo de la marca Square D. El uso de un interruptor automático
principal de la marca Square D delante de estas zapatas dará como resultado una clasificación igual a la clasificación del interruptor
automático. Las pruebas de cortocircuito se realizan al 100-105% de la tensión nominal máxima del tablero.
7. 96 circuitos con SPD tienen 84 circuitos de derivación utilizables.
8. El sumando es la longitud adicional del gabinete.
9. Amperios simétricos RMS, durante tres ciclos.
Anexo 1: Especificaciones Clase 1640
Restricciones QO2150VH, QO2175VH y QO2200VH
AVISO
PELIGRO DE DAÑO AL EQUIPO
No instale QO2150(VH), QO2175(VH) o QO2200(VH) en aplicaciones sísmicas.
No instale QO2150(VH), QO2175(VH) o QO2200(VH) en aplicaciones de
sistemas trifásicos.
No instale más de un total de cuatro QO2175(VH) o QO2200(VH) en gabinetes
NEMA 1.
No instale más de un QO2175(VH) o QO2200(VH) en gabinetes NEMA 3R
ventilados resistentes impermeables.
No instale QO2150(VH), QO2175(VH) o QO2200(VH) uno al lado del otro.
No instale en gabinetes impermeables sin ventilación (3R/5/12, 4/4X).
Para los interruptores automáticos QO2175(VH) y QO2200(VH) instale
molduras de cierre de tres puntos.
El incumplimiento de estas instrucciones podría provocar daños en el
equipo.
Deje al menos cuatro espacios de circuito de relleno en blanco o interruptores
automáticos de 125 A o inferiores antes de instalar otro QO2150(VH), QO2175(VH) o
QO2200(VH).
Coloque QO2150(VH), QO2175(VH) y QO2200(VH) junto al final de línea, en el lado
derecho para aplicaciones de entrada superior.
Coloque QO2150(VH), QO2175(VH) y QO2200(VH) junto al final de línea, en el lado
izquierdo para aplicaciones de entrada inferior.
QO2150(VH), QO2175(VH) y QO2200(VH) solo para aplicaciones monofásicas.
Tabla 11 - Frentes de moldura con pestillo de tres puntos; número de catálogo10
Tipo Montaje en superficie Montaje empotrado
Estándar
NC50VS3P NC50VF3P
NC56VS3P NC50VF3P
NC62VS3P NC62VF3P
NC68VS3P NC68VF3P
NC74VS3P NC74VF3P
NC80VS3P NC80VF3P
NC86VS3P NC86VF3P
NC92VS3P NC92VF3P
Con bisagras
NC62VS3PHR NC62VF3PHR
NC68VS3PHR NC68VF3PHR
NC74VS3PHR NC74VF3PHR
NC80VS3PHR NC80VF3PHR
NC86VS3PHR NC86VF3PHR
80043-712-06 33
10. V= Ventilada, HR=Bisagra derecha, 3P=Tres puntos
Clase 1640 Anexo 1: Especificaciones
Tabla 11 - Frentes de moldura con pestillo de tres puntos; número de catálogo11
-(Continuación)
Tipo Montaje en superficie Montaje empotrado
NC92VS3PHR NC92VF3PHR
Figura 11 - Frente de la moldura de cierre de tres puntos
Frente de la moldura
de cierre de tres puntos
34 80043-712-06
Anexo 2: Kits de accesorios Clase 1640
Anexo 2: Kits de accesorios
Los tableros NQ disponen de una amplia gama de kits de accesorios instalables en el
lugar de trabajo:
Kits de barra a tierra del equipo
Kits de anclajes de neutro sobredimensionadas para tableros de 100-600 A
Kits de anclajes de alimentación secundaria para tableros de 100-400 A
Kits de anclajes principales
Kits de anclajes mecánicas: aluminio
Kits de anclajes mecánicas: cobre
Kits de anclajes de compresión Versa-Crimp: aluminio
Kits de anclajes de compresión Versa-Crimp: cobre
Kits de barrera lateral de línea y correa de conexión neutra
Kits de barra a tierra del equipo
Los kits de barras a tierra para equipos, aptos para cable de cobre o aluminio,
satisfacen las necesidades de puesta a tierra de los tableros NQ y los centros de
carga QONQ.
Tabla 12 - Especificaciones de los kits de barra a tierra del equipo
Tablero Utilizar el número de catálogo del kit de barra a
tierra
Circuito de derivación Valor nominal de red Aluminio11 Cobre12
1-42
600 A máximo
(1) PK27GTA (1) PK27GTACU
54-84 (2) PK27GTA (2) PK27GTACU
Las ubicaciones de montaje de la barra a tierra se identifican mediante el
símbolo de tierra estampado en la pared posterior del gabinete.
Kits de anclajes de neutro sobredimensionadas para
tableros de 100-600 A
Los kits de zapatas de neutro sobredimensionadas están disponibles para
aplicaciones en las que se requieren conductores de terminación de 3 AWG o más
para el neutro.
80043-712-06 35
11. Barras de aluminio adecuadas para conductores de cobre o aluminio de 60°C o 75°C.
12. Barras de cobre adecuadas para conductores de cobre o aluminio de 60°C o 75°C.
Clase 1640 Anexo 2: Kits de accesorios
Tabla 13 - Especificaciones de los kits de zapatas de neutro
sobredimensionadas para tableros de 100-600 A
Valor nominal del
interruptor
automático
Número de catálogo del
kit Tamaño del cable Al/Cu (mm2)
70 A QO70AN
(1) #12–#2 AWG Al ([1] 3.3–33.6)
(1)#14–#4 AWG Cu ([1] 2.1–21.2)
80-100 A NQ100AN (1) #14–2/0 AWG Al/Cu ([1] 2.1–67.4)
80-120 A Q1100AN (1) #4-1/0 AWG Al/Cu ([1] 21.2-53.5)
110-150 A Q1150AN13 (1) #1–2/0 AWG Al/Cu ([1] 42.4–67.4)
175-200 A NQ200AN (1) #4 AWG–300 kcmil Al/Cu ([1] 21.2–152)
Kits de anclajes de alimentación secundaria para tableros
de 100-400 A
Las zapatas principales de alimentación secundaria están disponibles para
aplicaciones de 100, 225 ó 400 A.
Tabla 14 - Especificaciones de los kits de zapatas de alimentación secundaria
para tableros de 100-400 A
Amperaje principal Número de catálogo del kit Circuitos máximos
100 NQSFL1 18, 30
225 NQSFL2 3014, 4214, 5414, 7214, 8414
400 NQSFL4 30, 42, 54, 72, 84
Kits de anclajes principales
Tabla 15 - Kits de anclajes mecánicas: aluminio
Amperaje de tablero Número de catálogo del kit Tamaño del cable Al/Cu (mm2)
100 Estándar # 6-2/0 AWG
(13.3-67.43 mm2)
225 Estándar #6 AWG–350 kcmil
(13.3–177.3 mm2)
400 Estándar
(1) 1/0 AWG–750 kcmil
(2) 1/0 AWG–350 kcmil
([1] 53.48–380 mm2)
([2] 53.48–177.3 mm2)
600
Estándar (2) 1/0 AWG–750 kcmil
([2] 53.48–380 mm2)
NQALM6A (3) #6 AWG–250 kcmil
([3] 13.3–127 mm2)
36 80043-712-06
13. Utilice únicamente cable de cobre 1/0 (53,5 mm2) para aplicaciones de interruptores automáticos de derivación de 150 A.
14. Estos paneles requieren un espacio adicional de 6 pulgadas (152.4 mm) para la caja y la moldura, con el fin de disponer de un espacio
adecuado para doblar los cables.
Anexo 2: Kits de accesorios Clase 1640
Tabla 16 - Kits de anclajes mecánicas: cobre
Amperaje de tablero Número de catálogo del kit Tamaño del cable Al/Cu (mm2)
100 NQCUM1 # 6-2/0 AWG
(13.3-67.43 mm2)
225 NQCUM2 #6 AWG-250 kcmil
(13.3-127 mm2)
400 NQCUM4 (1) 1/0 AWG–750 kcmil
(2) 1/0 AWG–350 kcmil
([1] 53.48–380 mm2)
([2] 53.48–177.3 mm2)
600 NQCUM6
Tabla 17 - Kits de anclajes de compresión Versa-Crimp: aluminio
Amperaje de tablero Número de catálogo
del kit
Tamaño del cable Al/
Cu (mm2)Herramienta de
prensado
100 NQALV1 # 8-1/0 AWG
(8.36-53.48 mm2)
VC6 (Todos)
225 NQALV2 #4 AWG-300 kcmil
(21.15-152 mm2)
400 NQALV4 (2) 2/0 AWG-500 kcmil
([2] 67.43-253.4 mm2)VC6–3, VC6–FT
600 NQALV6
Tabla 18 - Kits de anclajes de compresión Versa-Crimp: cobre
Amperaje de tablero Número de catálogo
del kit
Tamaño del cable Al/
Cu (mm2)Herramienta de
prensado
100 NQCUV1 # 6-1/0 AWG
(13.30-53.48 mm2)
VC6 (Todos), VC7
(Todos)
225 NQCUV2 2/0 AWG–300 kcmil
(67.43–152 mm2)
VC6-3, VC7, VC6-FT,
VC7–FT
400 NQCUV4 400–750 kcmil
(202.7–380 mm2)VC6-FT, VC7–FT, VC8
600 NQCUV6 (2) 250–500 kcm
([2) 126.7–253.4mm2)
VC6-3, VC7, VC6-FT,
VC7–FT
Kits de barrera lateral de línea y correa de conexión neutra
En función de la aplicación y del código de instalación adoptado, puede ser necesaria
una barrera lateral de línea y una correa de conexión neutra. Seleccione la barrera
adecuada de la tabla siguiente, en función del interruptor automático principal.
80043-712-06 37
Clase 1640 Anexo 2: Kits de accesorios
Tabla 19 - Kits de barrera lateral de línea y correa de conexión neutra
Número de
catálogo
Contenido Descripción
Cubierta de la zapata de línea Correa de conexión neutra
NQLALLC
Cubierta de la zapata
de línea NQ LA/LH y
correa y zapata de
conexión neutra
NQHJQLLC
Cubierta de la zapata
de línea NQ H/J/Q y
correa de conexión
neutra
NQPPLLLC
Cubierta de la zapata
de línea PowerPacT
Ly correa y zapata
de conexión neutra
38 80043-712-06
Importado en México por: Schneider Electric México, S.A. de C.V.
Av. Ejército Nacional No. 904
Col. Palmas, Polanco 11560
México, D.F.
55-5804-5000
www.se.com/mx
Debido a que las normas, las especificaciones y el diseño cambian de
vez en cuando, solicite confirmación de la información brindada en esta
publicación.
© 2007 – 2023 Schneider Electric. Reservados todos los derechos
80043-712-06
www.se.com/ca
Panneaux de distribution NQ/NQM et centres
de charge QONQ
Classe 1640
Directives d’utilisation
80043-712-06, Rev. 07
02/2023
Information juridique
La marque Schneider Electric et toutes les marques déposées de Schneider Electric
SE et de ses filiales mentionnées dans le présent guide sont la propriété de Schneider
Electric SE et de ses filiales. Toutes les autres marques peuvent être des marques de
commerce de leurs détenteurs respectifs. Le présent guide et son contenu sont
protégés par les lois applicables sur les droits d'auteur et sont fournis à titre
d'information seulement. Aucune partie du présent guide ne peut être reproduite ni
transmise sous aucune forme ni par aucun moyen que ce soit (électronique,
mécanique, photocopie, enregistrement ou autre), à toute fin, sans l'autorisation écrite
préalable de Schneider Electric.
Schneider Electric n'accorde aucun droit ni aucune licence pour l'utilisation
commerciale du présent guide, sauf une licence non exclusive et personnelle pour le
consulter sur une base « tel quel ».
Les produits et l'équipement de Schneider Electric doivent être installés, utilisés et
maintenus par un personnel qualifié uniquement.
Alors que les normes, les spécifications et les designs changent à l'occasion,
l'information contenue dans le présent guide peut être sujette à modification sans
préavis.
Dans la mesure autorisée par les lois applicables, aucune responsabilité n'est
assumée par Schneider Electric et ses filiales pour toute erreur ou omission dans le
contenu informatif de la présente documentation, ni pour toute conséquence découlant
de l'utilisation de l'information contenue ici ou causée par celle-ci.
Classe 1640
Table des matières
Informations relatives à la sécurité ................................................................5
Veuillez noter...................................................................................................5
Introduction........................................................................................................7
Mesures de sécurité .........................................................................................7
Installation .........................................................................................................8
Montage d’intérieur pour armoires Square D ......................................................8
Montage en surface (armoire montée sur un mur) .........................................8
Montage encastré (armoire encastrée dans le mur).......................................9
Installation de la bride ou du câble de liaison du neutre .....................................10
Panneaux de distribution NQ jusqu’à 100 ou 250 A ..................................... 11
Panneaux de distribution NQ jusqu’à 400 ou 600 A et centres de charge
QONQ.....................................................................................................12
Installation et dépose des disjoncteurs QO et QOB...........................................14
Installation des disjoncteurs QO et QOB.....................................................14
Dépose des disjoncteurs QO et QOB .........................................................15
Instructions de réarmement du disjoncteur .......................................................16
Préparation de l’écran isolant..........................................................................17
Annexe 1 : Spécifications..............................................................................19
blage typique.............................................................................................19
Disjoncteur principal intégré ou secondaire : DJ, FI, KI, H, J, LA, LC, LH,
QB, QD, QG, QJ, QO(B)VH.......................................................................20
Valeurs nominales du panneau de distribution ..................................................24
Marquage CE ................................................................................................33
Restrictions QO2150VH, QO2175VH et QO2200VH.........................................34
Annexe 2 : Kits d’accessoires.......................................................................36
Kits de barres de m.à.l.t. .................................................................................36
Kits de cosses de neutre surdimensionnées pour panneaux de 100-
600 A ............................................................................................................36
Kits de cosses secondaires pour panneaux de distribution 100-400 A ................37
Kit de cosses principales ................................................................................37
Kits de barrières côté ligne et de brides de fixation au neutre.............................38
80043-712-06 3
Informations relatives à la sécurité Classe 1640
Informations relatives à la sécurité
Lire attentivement ces directives et examiner l’appareillage pour vous familiariser
avec son fonctionnement avant d’effectuer son installation ou son entretien. Les
messages spéciaux suivants peuvent apparaître dans les présent manuel ou sur
l’appareil pour avertir l’utilisateur de dangers potentiels ou pour attirer l’attention sur
des informations qui clarifient ou simplifient une procédure.
L’ajout d’un de ces deux symboles à une étiquette de sécurité
de « Danger » ou d’« Avertissement » indique qu’un danger
électrique existe et qu’il peut entraîner des blessures
corporelles si les directives ne sont pas respectées.
Ceci est le symbole d’alerte de sécurité. Il est utilisé pour vous
alerter de dangers de blessures corporelles potentielles. Se
conformer à tous les messages de sécurité qui suivent ce
symbole pour éviter une blessure ou la mort.
DANGER
DANGER indique une situation de danger imminent qui, si elle n’est pas
évitée entraînera la mort ou des blessures graves.
AVERTISSEMENT
AVERTISSEMENT indique une situation de danger potentiel qui, si elle
n’est pas évitée, peut entraîner la mort ou des blessures graves.
ATTENTION
ATTENTION indique une situation de danger potentiel qui, si elle n’est
pas évitée, peut entraîner des blessures mineures ou modérées.
AVIS
AVIS est utilisé pour commenter des pratiques sans rapport avec les
blessures physiques.
REMARQUE: Fournit des renseignements complémentaires pour clarifier ou
simplifier une procédure.
Veuillez noter
Seul du personnel qualifié doit effectuer l’installation, l’utilisation, l’entretien et la
maintenance du matériel électrique. Schneider Electric n’assume aucune
responsabilité des conséquences éventuelles découlant de l’utilisation de cette
documentation.
Une personne qualifiée est une personne disposant de compétences et de
connaissances dans le domaine de la construction et du fonctionnement des
équipements électriques et installations et ayant bénéficié d’une formation de sécurité
afin de reconnaître et d’éviter les risques encourus.
80043-712-06 5
Classe 1640 Informations relatives à la sécurité
L’équipement électrique doit être transporté, entreposé, installé et utilisé
exclusivement dans l’environnement pour lequel il a été conçu.
6 80043-712-06
Introduction Classe 1640
Introduction
Ces directives décrivent la procédure d’installation des panneaux de distribution à
disjoncteurs NQ Square D™ et des centres de charge QONQ. Ces panneaux de
distribution et centres de charge sont homologués par Underwriters Laboratories
(cULus) et compatibles avec les disjoncteurs de dérivation QO™ et QOB.
REMARQUE: Pour obtenir une assistance technique sur l’installation de ce
panneau de distribution, contactez le centre d’informations à la clientèle de
Schneider Electric au 1-888-778-2733 (É.-U.).
REMARQUE: Reportez-vous aux étiquettes apposées sur l’appareil pour les
informations de sécurité et les caractéristiques nominales. Des étiquettes
d’équipement supplémentaires sont fournies avec ce document.
Mesures de sécurité
DANGER
RISQUE D’ÉLECTROCUTION, D’EXPLOSION OU D’ÉCLAIR D’ARC
Portez un équipement de protection individuelle (EPI) approprié et observez les
méthodes de travail électrique sécuritaire. Voir NFPA 70E, NOM-029-STPS ou
CSA Z462, ou un équivalent local de la norme.
Seul un personnel qualifié doit effectuer l’installation et l’entretien de cet
appareil.
Coupez toutes les alimentations à cet appareil avant d’y travailler.
Le verrouillage de la commande manuelle ou du capot moteur ne déconnecte
pas le circuit secondaire du moteur.
Utilisez toujours un dispositif de détection de tension à valeur nominale
appropriée pour s’assurer que l’alimentation est coupée.
Il est impératif de lire et de comprendre entièrement ces directives d’utilisation
ainsi que les normes NEMA PB 1.1 incluses avant de procéder à l’installation, à
l’utilisation et à l’entretien de cet équipement.
Les codes locaux varient mais sont adoptés et appliqués pour assurer des
installations électriques sécuritaires. Il peut être nécessaire d’obtenir un permis
pour exécuter des travaux sur des circuits électriques et certains codes peuvent
exiger que le travail électrique accompli soit inspecté.
Replacez tous les dispositifs, les portes et les couvercles avant de mettre
l'appareil sous tension.
Évitez que les peintures, les solvants ou les vaporisateurs à base de pétrole ne
viennent en contact avec les pièces non métalliques de ce produit.
Le fait de ne pas suivre ces instructions entrainera des blessures graves,
voire mortelles.
AVERTISSEMENT : Ce produit peut vous exposer à des produits chimiques, notamment des
composés de nickel, reconnus par l’État de Californie comme pouvant causer le cancer et du
bisphénol A (BPA), reconnu par l’État de Californie comme pouvant causer des anomalies
congénitales ou d’autres troubles de la reproduction. Pour plus d’informations, consulter www.
P65Warnings.ca.gov.
80043-712-06 7
Classe 1640 Installation
Installation
Cette section fournit des instructions pour les procédures suivantes concernant les
panneaux de distribution NQ et les centres de charge QONQ :
Montage d’intérieur pour armoires Square D, page 8.
Installation de la bride ou du câble de liaison du neutre, page 10.
Installation et dépose des disjoncteurs QO et QOB, page 14.
Instructions de réarmement du disjoncteur, page 16.
Préparation de l’écran isolant, page 17.
Montage d’intérieur pour armoires Square D
Une publication de normes séparée, intitulée « General Instructions for Proper
Installation, Operation, and Maintenance of Panelboards Rated 600 Volts or Less »
[Instructions générales pour l’installation, l’utilisation et l’entretien des panneaux de
distribution de tension 600 V ou moins] (NEMA PB1.1), est fournie avec cet
équipement. Familiarisez-vous avec le contenu de ce document avant de suivre l’une
des procédures suivantes.
Si vous n’avez pas reçu une copie de ce document, ou si vous avez des questions
concernant l’équipement, contactez votre distributeur local ou votre représentant
Schneider Electric.
AVIS
RISQUE D’ENDOMMAGER DE L’ÉQUIPEMENT EN RAISON DE
RACCORDEMENTS MAL SERRÉS
Vérifiez que tous les raccordements sont bien serrés.
Consultez l’étiquette indiquant les couples de serrage sur le panneau de
distribution avant de serrer les raccordements.
Le fait de ne pas suivre ces instructions peut endommager l'équipement.
Pour monter et installer correctement l’intérieur de panneau de distribution NF ou de
centre de charge QONQ, reportez-vous à la publication de normes NEMA PB 1.1 et
suivez les instructions ci-dessous pour les procédures Montage en surface (armoire
montée sur un mur), page 8 ou Montage encastré (armoire encastrée dans le mur),
page 9.
Montage en surface (armoire montée sur un mur)
1. Montez l’armoire comme indiqué dans la publication des normes NEMA PB 1.1.
2. Retirez l’écran isolant de ses supports.
3. Installez l’intérieur comme décrit ci-dessous :
a. Placez l’intérieur sur les goujons de l’armoire. La vis de levage n’est pas
nécessaire (voir Montage d’intérieur pour armoires Square D, page 8).
b. Serrez les écrous Keps contre les rails latéraux intérieurs jusqu’à ce que les
rails soient contre le fond de l’armoire.
8 80043-712-06
Installation Classe 1640
4. En fonction de l’application et du code d’installation adopté, une bride de fixation
au neutre et une barrière côté ligne peuvent être nécessaires. Voir les sections
Installation de la bride ou du câble de liaison du neutre, page 10 et Annexe 2 :
Kits d’accessoires, page 36.
5. Appliquez les étiquettes d’équipement (placées dans le sachet) en suivant les
instructions figurant au dos de la feuille d’étiquettes d’équipement. Reportez-vous
aux codes et normes en vigueur localement.
6. Remontez l’écran isolant une fois le câblage réalisé.
Montage encastré (armoire encastrée dans le mur)
1. Montez l’armoire comme indiqué dans la publication des normes NEMA PB 1.1.
2. Retirez l’écran isolant de ses supports.
3. Installez l’intérieur comme décrit ci-dessous :
a. Vissez dans les rails latéraux les (4) vis de levage autotaraudeuses 10-32 ×
0,875 po fournies avec la façade encastrée.
b. Placez l’intérieur sur les goujons de l’armoire (voir Montage d’intérieur pour
armoires Square D, page 10). Placez les écrous Keps sur les goujons de
l’armoire, mais sans les serrer.
c. Ajustez les vis de sorte que la lèvre de l’écran isolant soit à environ 6,35 mm
(0,25 po) de la ligne du mur.
d. Serrez les écrous Keps contre les rails latéraux.
4. En fonction de l’application et du code d’installation adopté, une bride de fixation
au neutre et une barrière côté ligne peuvent être nécessaires. Reportez-vous aux
codes et normes en vigueur localement. Voir les sections Installation de la bride
ou du câble de liaison du neutre, page 10 et Annexe 2 : Kits d’accessoires, page
36.
5. Appliquez les étiquettes d’équipement (placées dans le sachet) en suivant les
instructions figurant au dos de la feuille d’étiquettes d’équipement.
6. Remontez l’écran isolant une fois le câblage réalisé.
80043-712-06 9
Classe 1640 Installation
Figure 1 - Montage d’intérieur pour armoires Square D
Support d’écran isolant
Goujon de l’armoire
Écrou Keps
Armoire
Écran isolant
Mur
Vis de levage
Rail latéral
0,25 po
(6,35 mm)
Installation de la bride ou du câble de liaison du neutre
En fonction de l’application et du code d’installation adopté, une barrière côté ligne et
une bride de fixation au neutre peuvent être nécessaires.
Pour établir correctement la liaison du neutre au panneau de distribution, suivez les
instructions des sections Panneaux de distribution NQ jusqu’à 100 ou 250 A ou
Panneaux de distribution NQ jusqu’à 400 ou 600 A et centres de charge QONQ, page
12.
10 80043-712-06
Installation Classe 1640
DANGER
RISQUE D’ÉLECTROCUTION, D’EXPLOSION OU D’ÉCLAIR D’ARC
Portez un équipement de protection individuelle (EPI) approprié et observez les
méthodes de travail électrique sécuritaire. Voir NFPA 70E, NOM-029-STPS ou
CSA Z462, ou un équivalent local de la norme.
Coupez toutes les alimentations à cet appareil avant d’y travailler.
Le verrouillage de la commande manuelle ou du capot moteur ne déconnecte
pas le circuit secondaire du moteur.
La bride de fixation ou le câble de liaison du neutre ne doivent être utilisés que
lorsque le panneau de distribution est installé comme équipement d’entrée de
service.
Veillez à ne pas mélanger les vis de montage avec les vis de l’écran isolant.
Le fait de ne pas suivre ces instructions entrainera des blessures graves,
voire mortelles.
REMARQUE: Reportez-vous à la section Kits de barrières côté ligne et de brides
de fixation au neutre, page 39 pour plus d’informations.
REMARQUE: Les termes « bride de fixation au neutre » et « câble de liaison du
neutre » décrivent les composants qui répondent aux exigences d’un
« conducteur de liaison du neutre ». Ces termes sont équivalents.
Panneaux de distribution NQ jusqu’à 100 ou 250 A
Pour installer une bride de fixation au neutre sur des panneaux de distribution NQ
avec un courant secteur nominal jusqu’à 225 A (avec cosses principales ou
disjoncteur principal) ou jusqu’à 250 A (avec un disjoncteur principal assemblé en
usine), reportez-vous à la section Installation de la bride de fixation – Panneaux de
distribution NQ jusqu’à 100 ou 250 A, page 12 et suivez les instructions ci-dessous.
1. Alignez la bride de fixation sur le rail latéral, comme illustré.
REMARQUE: Pour certaines applications, il peut être nécessaire de retirer la
cosse (non illustrée) avant d’installer la bride de fixation.
2. Insérez les deux vis de montage, comme illustré. Serrez la vis 10-32 à 1,1-
1,4 N•m (10-12 lb-po) et la vis 1/4-20 à 2,8-3,4 N•m (25-30 lb-po).
REMARQUE: Les vis de montage des cosses sont fournies dans le sachet
de la bride de fixation.
a. Si la cosse a été retirée à l’étape 1 ci-dessus, réinstallez-la par-dessus les
pattes de fixation.
b. Utilisez une vis 1/4-20 × 9/16 po pour le montage des intérieurs 100/225 A
sans options. Voir les notes C et D pour les autres options.
c. Utilisez la vis de montage de cosse 1/4-20 × 11/16 po dans les applications
avec cosse traversante, cosse secondaire, disjoncteur secondaire ou neutre
à 200 %.
d. Utilisez la vis de montage de cosse 1/4-20 × 7/8 po dans les applications
avec neutre à 200 % et cosses traversantes, cosses secondaires ou
disjoncteurs secondaires.
80043-712-06 11
Classe 1640 Installation
Figure 2 - Installation d’une bride de fixation – Panneaux NQ jusqu’à 100 ou 250 A
REMARQUE: Pour les options de cosses de liaison, reportez-vous à C et D pour la longueur correcte de la
vis 1/4-20.
Vis de montage
Bride de fixation
1/4-20 × 9/16 po
10/32 × 7 1/16 po
Barre-bus de neutre
Rail latéral
Panneaux de distribution NQ jusqu’à 400 ou 600 A et centres de
charge QONQ
Pour installer un câble de liaison du neutre sur un panneau de distribution NQ jusqu’à
400 ou 600 A et un centre de charge QONQ, reportez-vous à la section Installation du
câble de liaison – Panneaux de distribution NQ jusqu’à 400 ou 600 A et centres de
charge QONQ, page 13 et suivez les instructions ci-dessous.
1. Alignez la cosse sur le trou de montage du rail latéral, comme illustré.
2. Serrez la vis de montage de la cosse contre le rail latéral à 1,1-1,4 N•m (10-12 lb-
po).
3. Alignez le câble de liaison, comme illustré, et insérez-le dans les trous de
montage de la cosse et du neutre.
4. Serrez la vis de liaison du fil de cosse et la vis de fixation du fil de neutre à 5,1-
5,6 N•m (45-50 lb-po).
12 80043-712-06
Installation Classe 1640
Figure 3 - Installation du câble de liaison – Panneaux de distribution NQ jusqu’à 400 ou 600 A et centres de
charge QONQ
Neutre
Vis de montage
pour cosse
Câble de liaison
Trou de montage du câble de liaison
Rail latéral
Cosse
Trou de montage
du rail latéral
Vis de fixation
du fil de neutre
Vis de
fixation
du fil
de cosse
Trou de montage du câble de liaison
80043-712-06 13
Classe 1640 Installation
Installation et dépose des disjoncteurs QO et QOB
DANGER
RISQUE D’ÉLECTROCUTION, D’EXPLOSION OU D’ÉCLAIR D’ARC
Portez un équipement de protection individuelle (EPI) approprié et observez les
méthodes de travail électrique sécuritaire. Voir NFPA 70E, NOM-029-STPS ou
CSA Z462, ou un équivalent local de la norme.
Seul un personnel qualifié doit effectuer l’installation et l’entretien de cet
appareil.
Coupez toutes les alimentations à cet appareil avant d’y travailler.
Le verrouillage de la commande manuelle ou du capot moteur ne déconnecte
pas le circuit secondaire du moteur.
Utilisez toujours un dispositif de détection de tension à valeur nominale
appropriée pour s’assurer que l’alimentation est coupée.
Comblez tous les espaces inutilisés à l’aide de plaques d’obturation.
Replacez tous les dispositifs, les portes et les couvercles avant de mettre
l'appareil sous tension.
Le fait de ne pas suivre ces instructions entrainera des blessures graves,
voire mortelles.
AVERTISSEMENT
RISQUE DE BLESSURES OU DE DOMMAGES MATÉRIELS
Cet équipement est conçu et testé par Schneider Electricselon des niveaux de
performance qui réponde aux normes Underwriter’s Laboratories®(UL®) et aux
normes officielles mexicaines (NOM).
Utilisez uniquement des disjoncteurs et accessoires Square D.
Le fait de ne pas suivre ces instructions peut entraîner des blessures graves,
voire mortelles, ou endommager l'équipement.
Installation des disjoncteurs QO et QOB
Reportez-vous à la section Installation et dépose des disjoncteurs QO et QOB, page
16 pour les instructions suivantes :
1. Coupez toutes les alimentations du panneau de distribution.
2. Mettez le disjoncteur en position OFF.
3. Retirez l’ensemble de l’écran isolant.
4. Emboîtez l’extrémité de la borne de fil du disjoncteur sur le rail de montage.
5. Engagez le connecteur de dérivation.
Pour les disjoncteurs QO : Poussez vers l’intérieur jusqu’à ce que les
mâchoires enfichables s’engagent complètement dans le connecteur de
dérivation.
Pour les disjoncteurs QOB : Poussez vers l’intérieur jusqu’à ce que le
connecteur du disjoncteur soit centré sur le trou de montage du connecteur de
dérivation. Engagez la vis dans le trou du connecteur de dérivation et serrez au
couple indiqué sur le schéma de câblage et de serrage de l’intérieur.
6. Installez le câble de charge.
14 80043-712-06
Installation Classe 1640
7. Réinstallez l’écran isolant.
8. Installez une plaque d’obturation dans tous les espaces pour disjoncteur de
dérivation non utilisés.
Dépose des disjoncteurs QO et QOB
Reportez-vous à la section Installation et dépose des disjoncteurs QO et QOB, page
16 pour les instructions suivantes :
1. Coupez toutes les alimentations du panneau de distribution.
2. Retirez l’ensemble de l’écran isolant.
3. Retirez le fil de charge.
4. Dégagez le connecteur de dérivation.
Pour les disjoncteurs QO :
Tirez vers l’extérieur jusqu’à ce que les mâchoires enfichables se dégagent
complètement du connecteur de dérivation.
Pour les disjoncteurs QOB :
Desserrez la vis dans le connecteur du disjoncteur et retirez le disjoncteur du
connecteur de dérivation.
5. Emboîtez l’extrémité de la borne de fil du disjoncteur sur le rail de montage.
6. Réinstallez l’écran isolant.
7. Installez une plaque d’obturation dans tous les espaces pour disjoncteur de
dérivation non utilisés.
80043-712-06 15
Classe 1640 Installation
Figure 4 - Installation et dépose des disjoncteurs QO et QOB
QO
QOB
Mâchoire enfichable
Connecteur de dérivation
Connecteur de dérivation
Vis de
connecteur
boulonné
Rail
Borne
à fil
Borne
à fil
Rail
Instructions de réarmement du disjoncteur
Si le disjoncteur est déclenché, la poignée sera en position médiane entre ON et OFF.
Pour réarmer le disjoncteur, poussez la poignée en position OFF, puis en position ON.
16 80043-712-06
Installation Classe 1640
Figure 5 - Positions de la poignée du disjoncteur
ONOFFDéclenché
Manette
Indicateur Visi-Trip™
REMARQUE: Lorsque le disjoncteur s’est déclenché, la poignée prend une
position centrale et l’indicateur rouge Visi-Trip apparaît dans la fenêtre du boîtier
du disjoncteur. L’indicateur rouge Visi-Trip n’est visible que lorsque le disjoncteur
s’est déclenché.
Préparation de l’écran isolant
DANGER
RISQUE D’ÉLECTROCUTION, D’EXPLOSION OU D’ÉCLAIR D’ARC
Portez un équipement de protection individuelle (EPI) approprié et observez les
méthodes de travail électrique sécuritaire. Voir NFPA 70E, NOM-029-STPS ou
CSA Z462, ou un équivalent local de la norme.
Avant de mettre le panneau de distribution sous tension, comblez tous les
espaces inutilisés à l’aide de plaques d’obturation.
Replacez tous les dispositifs, les portes et les couvercles avant de mettre
l'appareil sous tension.
Le fait de ne pas suivre ces instructions entrainera des blessures graves,
voire mortelles.
80043-712-06 17
Classe 1640 Installation
Figure 6 - Diagramme de l’écran isolant
Plaques d’obturation
Écran isolant
REMARQUE: Le dos de l’écran isolant indique le numéro de catalogue des
plaques d’obturation compatibles correspondantes.
18 80043-712-06
Annexe 1 : Spécifications Classe 1640
Annexe 1 : Spécifications
Câblage typique
Tableau 1 - Câblage typique d’un panneau de distribution1
Tension CA
Panneaux de distribution
monophasés Panneaux de distribution
monophasés
Phase Fils Phase Fils
208Y/120 – – 3 4
120/240 1 3 – –
24021 2 3 4
24031 3 – –
240/1204– – 34 Triangle
80043-712-06 19
1. Des informations supplémentaires sont fournies sur le panneau de distribution. Voir la valeur nominale du disjoncteur principal, s’il est utilisé.
2. Pour ce système, le neutre n’est pas utilisé et seuls des disjoncteurs de 240 V minimum doivent être utilisés. N’utilisez pas de disjoncteurs de
120 V ou 120 /240 Vc.a.
3. Pour un système de phase B mis à la terre, seuls des disjoncteurs de 240 V minimum doivent être utilisés. N’utilisez pas de disjoncteurs de
120 V ou 120 / 240 Vc.a.
4. Lors du câblage d’un système en triangle, les phases A et C doivent avoir 120 V au neutre, la phase B 208 V au neutre. Ne connectez que
des disjoncteurs d’une valeur nominale de 240 Vc.a. minimum. N’utilisez pas de disjoncteurs de 120 V ou 120/240 V sur la phase B.
Classe 1640 Annexe 1 : Spécifications
Disjoncteur principal intégré ou secondaire : DJ, FI, KI, H, J, LA, LC,
LH, QB, QD, QG, QJ, QO(B)VH
Figure 7 - Schéma de cosses principales NQ/NQM 100-225 A ou de disjoncteur principal 100-250 A
20 80043-712-06
Annexe 1 : Spécifications Classe 1640
Figure 8 - Schéma de cosses principales ou disjoncteur principal (avec ou sans cosses traversantes) NF
400-600 A pour panneaux de distribution NQ ou centre de charge QONQ
Charge
Cosses traversantes
(si installé)
Disjoncteur
principal
intégré
(si installé)
Liaison des armoires
(si nécessaire) Neutre
Ligne
Ligne
Terre
(si nécessaire)
80043-712-06 21
Classe 1640 Annexe 1 : Spécifications
Figure 9 - Disjoncteurs principaux NF 400-600 A pour panneaux de distribution NQ ou centres de charge
QONQ avec cosses traversantes ou disjoncteurs secondaires
Disjoncteurs
secondaires
Charge Charge
(si installé)
Charge
Liaison des armoires
(si nécessaire) Neutre
Terre
(si nécessaire)
Disjoncteur principal
intégré
(si installé)
Ligne
22 80043-712-06
Annexe 1 : Spécifications Classe 1640
Figure 10 - Schéma typique d’un panneau de distribution NQ avec bus divisé
Disjoncteur principal
intégré
(si installé)
Liaison des armoires
(si nécessaire) Neutre
Terre
Ligne
Ligne
(si nécessaire)
80043-712-06 23
Classe 1640 Annexe 1 : Spécifications
Valeurs nominales du panneau de distribution
Consultez les codes et normes en vigueur localement pour plus d’informations.
L’étiquette pour un système qualifié pour utilisation en série se trouve dans le sachet.
Courant nominal de court-circuit pour des disjoncteurs raccordés en série
(valeurs symétriques efficaces)
Les valeurs nominales des séries indiquées pour des tensions plus élevées
s’appliquent à des tensions plus basses (Exemple : 240 3P/3F couvre 208Y/
120 3P/4F).
Les essais de court-circuit sont effectués à 100-105 % de la tension nominale
max. du panneau de distribution.
« MC » désigne des disjoncteurs critiques.
Lorsque LG est indiqué, LJ et LL peuvent être utilisés.
Sauf indication contraire, les disjoncteurs principaux peuvent s’appliquer à
l’intensité nominale max. disponible.
Les suffixes HID, SWD et SWN peuvent également s’appliquer aux disjoncteurs
de dérivation appropriés figurant ci-dessous.
Lorsque les disjoncteurs QO(B) sont indiqués ci-dessous, les disjoncteurs QO(B)
H, QO(B)VH et QH(B) peuvent également être utilisés.
Les disjoncteur bipolaires CAFI ne peuvent pas être utilisés sur les systèmes
triphasés.
Tableau 2 - Tension max. du système CA : 120/240 1P/3F, 208Y/120 3P/4F, 240/120 3P/4F
Courant nominal
de court-circuit
max.
Disjoncteurs principaux intégrés ou
à distance et fusibles principaux à
distance Square D
Désignation catalogue des disjoncteurs de dérivation Square D et plages
d’intensité admissibles
Type Unipolaire Bipolaire Tripolaire
18 000 LA/LH MC QO(B) 15 à 30 A 15 à 30 A
22 000 QO(B) VH
QOB-VH
QO(B) 15-70 A 15-125 A
QO(B) GFI 15 à 30 A 15-60 A
QO(B) EPD 15 à 30 A 15-60 A
QO(B) PL 15 à 30 A 15-60 A
QO(B) AFI 15-20 A – –
QO(B) CAFI 15-20 A 15-20 A
QO(B) DF 15-20 A – –
24 80043-712-06
Annexe 1 : Spécifications Classe 1640
Tableau 2 - Tension max. du système CA : 120/240 1P/3F, 208Y/120 3P/4F, 240/120 3P/4F (Suite)
Courant nominal
de court-circuit
max.
Disjoncteurs principaux intégrés ou
à distance et fusibles principaux à
distance Square D
Désignation catalogue des disjoncteurs de dérivation Square D et plages
d’intensité admissibles
Type Unipolaire Bipolaire Tripolaire
25 000
QD
QO(B) 15-70 A 15-125 A
QOB-VH – 150 A
QO(B) PL 15 à 30 A 15-60 A
QO(B) GFI 15 à 30 A 15-60 A
QO(B) EPD 15 à 30 A 15-60 A
QO(B) AFI 15-20 A – –
QO(B) CAFI 15-20 A 15-20 A
QO(B) DF 15-20 A – –
ED
QO(B) 15-70 A 15-125 A
QO(B) GFI 15 à 30 A 15-60 A
QO(B) EPD 15 à 30 A 15-60 A
QO(B) AFI 15-20 A – –
QO(B) CAFI 15-20 A 15-20 A
QO(B) DF 15-20 A – –
BD, HD, JD, LD
QO(B) 15-70 A 15-125 A
QOB-VH – 150 A
QO(B) PL 15 à 30 A 15-60 A
QO(B) GFI 15 à 30 A 15-60 A
QO(B) EPD 15 à 30 A 15-60 A
QO(B) AFI 15-20 A – –
BD, HD, JD, LD QO(B) CAFI 15-20 A 15-20 A
QO(B) DF 15-20 A – –
42 000 LA, MA QO(B) 15 à 30 A 15 à 30 A
80043-712-06 25
Classe 1640 Annexe 1 : Spécifications
Tableau 2 - Tension max. du système CA : 120/240 1P/3F, 208Y/120 3P/4F, 240/120 3P/4F (Suite)
Courant nominal
de court-circuit
max.
Disjoncteurs principaux intégrés ou
à distance et fusibles principaux à
distance Square D
Désignation catalogue des disjoncteurs de dérivation Square D et plages
d’intensité admissibles
Type Unipolaire Bipolaire Tripolaire
65 000
QG
QO(B) 15-70 A 15-125 A
QO(B) VH 15-70 A 15-125 A
QOB-VH – 150 A
QO(B) GFI 15 à 30 A 15-60 A
QO(B) PL 15 à 30 A 15-60 A
QO(B) AFI 15-20 A – –
QO(B) CAFI 15-20 A 15-20 A
QO(B) DF 15-20 A – –
EG QO(B) 15-70 A 15-125 A
EG
QO(B) GFI 15 à 30 A 15-60 A
QO(B) EPD 15 à 30 A 15-60 A
QO(B) EPE – – –
QO(B) AFI 15-20 A – –
QO(B) CAFI 15-20 A 15-20 A
QO(B) DF 15-20 A – –
BG, HG, JG, LG
QO(B) 15-70 A 15-125 A
QOB-VH – 150 A
QO(B) PL 15 à 30 A 15-60 A
QO(B) GFI 15 à 30 A 15-60 A
QO(B) EPD 15 à 30 A 15-60 A
QO(B) AFI 15-20 A – –
QO(B) CAFI 15-20 A 15-20 A
QO(B) DF 15-20 A – –
26 80043-712-06
Annexe 1 : Spécifications Classe 1640
Tableau 2 - Tension max. du système CA : 120/240 1P/3F, 208Y/120 3P/4F, 240/120 3P/4F (Suite)
Courant nominal
de court-circuit
max.
Disjoncteurs principaux intégrés ou
à distance et fusibles principaux à
distance Square D
Désignation catalogue des disjoncteurs de dérivation Square D et plages
d’intensité admissibles
Type Unipolaire Bipolaire Tripolaire
100 000
QJ
QO(B) 15-70 A 15-125 A
QOB-VH – 150 A
QO(B) PL 15 à 30 A 15-60 A
QO(B) GFI 15 à 30 A 15-60 A
QO(B) EPD 15 à 30 A 15-60 A
QO(B) AFI 15-20 A – –
QO(B) CAFI 15-20 A 15-20 A
QO(B) DF 15-20 A – –
EJ QO(B) 15-70 A 15-125 A
QO(B) GFI 15 à 30 A 15-60 A
EJ
QO(B) EPD 15 à 30 A 15-60 A
QO(B) AFI 15-20 A – –
QO(B) CAFI 15-20 A 15-20 A
QO(B) DF 15-20 A – –
BJ, HJ, JJ
QO(B) 15-70 A 15-125 A
QOB-VH – 150 A
QO(B) PL 15 à 30 A 15-60 A
QO(B) GFI 15 à 30 A 15-60 A
QO(B) EPD 15 à 30 A 15-60 A
QO(B) AFI 15-20 A – –
QO(B) CAFI 15-20 A 15-20 A
QO(B) DF 15-20 A – –
LJ
QO(B) 15-70 A 15-125 A
QOB-VH – 150 A
QO(B) GFI 15-60 A
QO(B) EPD 15-60 A
QO(B) AFI 15-20 A – –
QO(B) CAFI 15-20 A 15-20 A
QO(B) DF 15-20 A – –
125 000 HL, JL
QO(B) 15-70 A 15-125 A
QOB-VH – 150 A
QO(B) PL 15 à 30 A 15-60 A
QO(B) GFI 15 à 30 A 15-60 A
QO(B) EPD 15 à 30 A 15-60 A
QO(B) AFI 15-20 A – –
QO(B) CAFI 15-20 A 15-20 A
QO(B) DF 15-20 A – –
200 000
HR, JR
QO(B) 15-70 A 15-125 A
QO(B) GFI 15 à 30 A 15-60 A
QO(B) EPD 15 à 30 A 15-60 A
QO(B) AFI 15-20 A – –
HR, JR QO(B) CAFI 15-20 A 15-20 A
QO(B) DF 15-20 A – –
80043-712-06 27
Classe 1640 Annexe 1 : Spécifications
Tableau 3 - Tension du système CA maximale : 240 1P/2F
Courant nominal
de court-circuit
max.
Disjoncteurs principaux intégrés ou
à distance et fusibles principaux à
distance Square D
Désignation catalogue des disjoncteurs de dérivation Square D et plages
d’intensité admissibles
Type Unipolaire Bipolaire Tripolaire
25 000 QD, BD, HD, JD, LD QO(B) H 15-100 A
42 000 LA, MA QDL 70-225 A
65 000 QG, BG, HG, JG, LG QO(B) H 15-100 A
100 000 BJ, HJ, JJ, LJ QO(B) H 15-100 A
125 000 HL, JL QO(B) H 15-100 A
Tableau 4 - Tension du système CA maximale : 208Y/120 3P/4F
Courant nominal
de court-circuit
max.
Disjoncteurs principaux intégrés ou
à distance et fusibles principaux à
distance Square D
Désignation catalogue des disjoncteurs de dérivation Square D et plages
d’intensité admissibles
Type Unipolaire Bipolaire Tripolaire
18 000 LA/LH MC QO(B) 15 à 30 A
22 000 QO(B) VH, QOB-VH QO(B) GFI 15-50 A
25 000 QD, ED, FD, BD, HD, JD QO(B) GFI 15-50 A
LD QO(B) GFI 15 à 30 A
65 000 QG, EG, BG, HG, JG QO(B) GFI 15-50 A
LG QO(B) GFI 15 à 30 A
100 000 QJ
QO(B) 15 à 30 A
QO(B) VH 15-100 A
QOB-VH 110-150 A
QO(B) PL 15 à 30 A
QO(B) GFI 15-50 A
QO(B) EPD 15-50 A
QO(B) EPE 15-50 A
EJ, BJ, HJ, JJ QO(B) GFI 15-50 A
28 80043-712-06
Annexe 1 : Spécifications Classe 1640
Tableau 5 - Tension du système CA maximale : 240/120 3P/4F, 240 3P/3F
Courant nominal
de court-circuit
max.
Disjoncteurs principaux intégrés ou
à distance et fusibles principaux à
distance Square D
Désignation catalogue des disjoncteurs de dérivation Square D et plages
d’intensité admissibles
Type Unipolaire Bipolaire Tripolaire
22 000 QOB VH
QOB-VH
QO(B) 15-100 A
QO(B) EPD 15-50 A
QO(B) EPE 15-50 A
25 000
QD QO(B) 15 à 30 A
QD
QO(B) VH 15-100 A
QOB-VH 110-150 A
QO(B) PL 15 à 30 A
QO(B) EPD 15-50 A
QO(B) EPE 15-50 A
ED
QO(B) 15-100 A
QO(B) EPD 15-50 A
QO(B) EPE 15-50 A
BD, HD, JD
QO(B) 15-100 A
QOB-VH 110-150 A
QO(B) PL 15 à 30 A
QO(B) EPD 15-50 A
QO(B) EPE 15-50 A
LD
QO(B) 15 à 30 A
QO(B) VH 15-100 A
QOB-VH 110-150 A
QO(B) EPD 15 à 30 A
QO(B) EPE 15 à 30 A
42 000 LA, MA QDL 70-225 A
QO(B) VH 15 à 30 A
MG QOB-VH 110-150 A
65 000
QG QO(B) 15 à 30 A
QO(B) VH 15-100 A
QG QOB-VH 110-150 A
QO(B) PL 15 à 30 A
EG
QO(B) 15-100 A
QOB-VH 110-125 A
QO(B) EPD 15-50 A
QO(B) EPE 15-50 A
BG, HG, JG
QO(B) 15-100 A
QOB-VH 110-150 A
QO(B) PL 15 à 30 A
QO(B) EPD 15-50 A
QO(B) EPE 15-50 A
LG
QO(B) 15 à 30 A
QO(B) VH 15-100 A
QOB-VH 110-150 A
QO(B) EPD 15 à 30 A
QO(B) EPE 15 à 30 A
80043-712-06 29
Classe 1640 Annexe 1 : Spécifications
Tableau 5 - Tension du système CA maximale : 240/120 3P/4F, 240 3P/3F (Suite)
Courant nominal
de court-circuit
max.
Disjoncteurs principaux intégrés ou
à distance et fusibles principaux à
distance Square D
Désignation catalogue des disjoncteurs de dérivation Square D et plages
d’intensité admissibles
Type Unipolaire Bipolaire Tripolaire
100 000
EJ
QO(B) 15-100 A
QOB-VH 110-125 A
QO(B) EPD 15-50 A
QO(B) EPE 15-50 A
BJ, HJ, JJ
QO(B) 15-100 A
QOB-VH 110-150 A
QO(B) PL 15 à 30 A
QO(B) EPD 15-50 A
QO(B) EPE 15-50 A
LJ
QO(B) 15 à 30 A
QO(B) VH 15-100 A
QOB-VH 110-150 A
125 000
HL, JL QO(B) 15-100 A
HL, JL
QOB-VH 110-150 A
QO(B) PL 15 à 30 A
QO(B) EPD 15-50 A
QO(B) EPE 15-50 A
200 000 HR, JR QO(B) 15-100 A
QOB-VH 110-150 A
Tableau 6 - Tension du système CA maximale : 120/240 1P/3F, 208Y/120 3P/4F, 240/120 3P/3F
Courant nominal
de court-circuit
max.
Disjoncteurs principaux intégrés ou
à distance et fusibles principaux à
distance Square D
Désignation catalogue des disjoncteurs de dérivation Square D et plages
d’intensité admissibles
Type Unipolaire Bipolaire Tripolaire
42 000 Fusibles de classe T3
400 A max. QO(B) VH 15-70 A 15-125 A
65 000
Fusibles classe J
400 A max.
QO(B) VH 15-70 A 15-125 A
QO(B) AFI 15-20 A – –
QO(B) CAFI 15-20 A 15-20 A
QO(B) DF 15-20 A – –
Fusibles classe T6
400 A max.
QO(B) VH 15-70 A 15-125 A
QOB-VH – 150 A
QO(B) AFI 15-20 A – –
QO(B) CAFI 15-20 A 15-20 A
QO(B) DF 15-20 A – –
100 000 Fusibles de classe T3
200 A max.
QO(B) 15-70 A 15-125 A
QO(B) GFI 15 à 30 A 15-60 A
QO(B) EPD 15 à 30 A 15-60 A
QO(B) AFI 15-20 A – –
QO(B) CAFI 15-20 A 15-20 A
QO(B) DF 15-20 A – –
30 80043-712-06
Annexe 1 : Spécifications Classe 1640
Tableau 6 - Tension du système CA maximale : 120/240 1P/3F, 208Y/120 3P/4F, 240/120 3P/3F (Suite)
Courant nominal
de court-circuit
max.
Disjoncteurs principaux intégrés ou
à distance et fusibles principaux à
distance Square D
Désignation catalogue des disjoncteurs de dérivation Square D et plages
d’intensité admissibles
Type Unipolaire Bipolaire Tripolaire
200 000
Fusibles de classe T6 ou J
200 A max.
QO(B) 15-70 A 15-125 A
QO(B) GFI 15 à 30 A 15-60 A
QO(B) EPD 15 à 30 A 15-60 A
Fusibles de classe T3
400 A max.
QO(B) 15-70 A 15-125 A
QO(B) GFI 15 à 30 A 15-60 A
QO(B) EPD 15 à 30 A 15-60 A
Tableau 7 - Tension du système CA maximale : 208Y/120 3P/4F
Courant nominal
de court-circuit
max.
Disjoncteurs principaux intégrés ou
à distance et fusibles principaux à
distance Square D
Désignation catalogue des disjoncteurs de dérivation Square D et plages
d’intensité admissibles
Type Unipolaire Bipolaire Tripolaire
65 000 400 A max. Classe J QO(B) GFI 15-50 A
100 000 Fusibles classe T3 200 A max. QO(B) GFI 15-50 A
200 000
Fusibles de classe T6 ou J
200 A max. QO(B) GFI 15-50 A
400 A max. Fusibles classe T3 QO(B) GFI 15-50 A
Tableau 8 - Tension du système CA maximale : 240/120 3P/4F, 240 3P/3F
Courant nominal
de court-circuit
max.
Disjoncteurs principaux intégrés ou
à distance et fusibles principaux à
distance Square D
Désignation catalogue des disjoncteurs de dérivation Square D et plages
d’intensité admissibles
Type Unipolaire Bipolaire Tripolaire
50 000 600 A max. Fusibles classe T3 QO(B) VH 15 à 30 A
65 000
400 A max. Fusibles classe J QO(B) VH 15-100 A
400 A max. Fusibles classe T6 QO(B) VH 15-100 A
QOB-VH 110-150 A
100 000 200 A max. Fusibles classe T3
QO(B) 15-100 A
QO(B) EPD 15-50 A
QO(B) EPE 15-50 A
200 000
Fusibles de classe T6 ou J
200 A max.
QO(B) 15-100 A
QO(B) EPD 15-50 A
QO(B) EPE 15-50 A
Fusibles de classe T3
400 A max.
QO(B) 15-100 A
QO(B) EPD 15-50 A
QO(B) EPE 15-50 A
80043-712-06 31
Classe 1640 Annexe 1 : Spécifications
Tableau 9 - Sélectivité des disjoncteurs critiques pour panneaux NQ
Courant nominal de court-circuit
maximum
(symétrique efficace)
Disjoncteurs principaux
intégrés ou à distance
Disjoncteurs de dérivation
Type5Unipolaire Bipolaire Tripolaire
Entièrement calibré et sélectif jusqu’à
10 kA
à 208Y / 120 Vac
ou à 240/120 Vac
J-W, 250 A
L-W, 250 A
QOB
10 à 70 10 à 125 10 à 125
QOB-H
QOB-VH
QH
Convient au raccordement en série et
sélectif jusqu’à 12 kA
à 208Y / 120 Vac ou
à 240/120 Vac
J-W, 250 A
QOB
10 à 70 10 à 125 10 à 60
QOB-H
QOB-VH
QH
Classé et sélectif jusqu’à 15 kA
à 208Y / 120 Vac ou
à 240/120 Vac
J-W, 250 A
QOB
10 à 60 10 à 60 10-30
QOB-H
QOB-VH
QH
Convient au raccordement en série et
sélectif jusqu’à 18 kA
à 208Y / 120 Vac ou
à 240/120 Vac
J-W, 250 A
QOB
10-30 10-30
QOB-H
QOB-VH
QH
L-W, 250 A
QOB
10 à 60 10 à 60 10 à 60
QOB-H
QOB-VH
QH
Convient au raccordement en série et
sélectif jusqu’à 30 kA
à 208Y / 120 Vac ou
à 240/120 Vac
L-W, 400 A
L-W, 600 A
QOB
15 à 70 15 à 150 15 à 150
QOB-H
QOB-VH
QH
32 80043-712-06
5. Y compris disjoncteurs AFI, CAFI, EPD et GFI
Annexe 1 : Spécifications Classe 1640
Tableau 10 - Valeur nominale des courants de court-circuit6pour les cosses principales d’intérieur avec
cosses secondaires ou traversantes
Tension de système
CA maximale Courant nominal
maximal Circuits de
dérivation7Application Additionneur8
Courant nominal de
court-circuit
maximal9
240
100 18, 30 SFL et FTL
10 000
225
30, 42, 54, 72, 84, 96 SFL 152,4 mm (6 po)
42 FTL
30, 54, 72, 84, 96 152,4 mm (6 po)
400
30, 42, 54, 72, 84 SFL 25 000
96 10 000
30, 84
FTL
25 000
96 10 000
42, 54, 72 152,4 mm (6 po)
25 000
600 30, 42, 54, 72, 84 FTL 304,8 mm (12 po)
96 10 000
Marquage CE
Les intérieurs portant la marque « CE » sont conformes aux normes CEI 61439-1
et CEI 61439-2.
L’intérieur à cosses principales portant la marque « CE » a été testé pour résister
à une intensité de 10 000 A RMS symétrique pendant 30 cycles.
Les intérieurs portant la marque « CE » ne sont autorisés que pour une utilisation
avec les disjoncteurs de dérivation QOXD ou QOBXD qui portent la marque
« CE ».
80043-712-06 33
6. Cette classification s’applique aux intérieurs à cosses principales, équipés de cosses secondaires ou traversantes, lorsque le dispositif
alimentant l’intérieur est inconnu ou n’est pas un dispositif Square D. Utilisé en amont de ces cosses, un disjoncteur principal Square D
permet d’obtenir une puissance égale à celle du disjoncteur. Les essais de court-circuit sont effectués à 100-105 % de la tension nominale
max. du panneau de distribution.
7. 96 circuits avec SPD, 84 circuits de dérivation utilisables.
8. L’additionneur est la longueur supplémentaire de l’armoire.
9. Ampères symétriques efficaces, pour trois cycles.
Classe 1640 Annexe 1 : Spécifications
Restrictions QO2150VH, QO2175VH et QO2200VH
AVIS
RISQUE DE DOMMAGES MATÉRIELS
Ne pas installer les unités QO2150(VH), QO2175(VH) ou QO2200(VH) dans
des applications parasismiques.
Ne pas installer les unités QO2150(VH), QO2175(VH) ou QO2200(VH) dans
des applications de réseau triphasé.
Ne pas installer plus de quatre QO2175(VH) ou QO2200(VH) au total sur des
armoires NEMA 1.
Ne pas installer plus d’un QO2175(VH) ou QO2200(VH) dans des armoires
étanches ventilées NEMA 3R.
Ne pas installer les unités QO2150(VH), QO2175(VH) ou QO2200(VH) les unes
à côté des autres.
Ne pas installer dans des armoires étanches non ventilées (3R/5/12, 4/4X).
Pour les disjoncteurs QO2175(VH) et QO2200(VH), installer des façades à
verrouillage en trois points.
Le fait de ne pas suivre ces instructions peut endommager l'équipement.
Laisser au moins quatre espaces vides pour plaques d’obturation vides ou
disjoncteurs de 125 A ou moins avant d’installer un autre QO2150(VH), QO2175(VH)
ou QO2200(VH).
Placer les unités QO2150(VH), QO2175(VH) et QO2200(VH) à côté de l’extrémité de
la ligne, à droite pour les applications à arrivée par le haut.
Placer les unités QO2150(VH), QO2175(VH) et QO2200(VH) à côté de l’extrémité de
la ligne, à gauche pour les applications à arrivée par le bas.
Unités QO2150(VH), QO2175(VH) et QO2200(VH) pour les applications
monophasées uniquement.
Tableau 11 - Façades à verrouillage en trois points – Numéro de catalogue10
Type Montage en surface Montage encastré
Norme
NC50VS3P NC50VF3P
NC56VS3P NC50VF3P
NC62VS3P NC62VF3P
NC68VS3P NC68VF3P
NC74VS3P NC74VF3P
NC80VS3P NC80VF3P
NC86VS3P NC86VF3P
NC92VS3P NC92VF3P
À charnière
NC62VS3PHR NC62VF3PHR
NC68VS3PHR NC68VF3PHR
NC74VS3PHR NC74VF3PHR
NC80VS3PHR NC80VF3PHR
NC86VS3PHR NC86VF3PHR
34 80043-712-06
10. V=Ventilé, HR=Charnière à droite, 3P=Trois points.
Annexe 1 : Spécifications Classe 1640
Tableau 11 - Façades à verrouillage en trois points – Numéro de catalogue11 -
(Suite)
Type Montage en surface Montage encastré
NC92VS3PHR NC92VF3PHR
Figure 11 - Façade à verrou en trois points
Façade à verrou
en trois points
80043-712-06 35
Classe 1640 Annexe 2 : Kits d’accessoires
Annexe 2 : Kits d’accessoires
Un assortiment de kits d’accessoires à installer sur place est disponible pour les
panneaux NQ :
Kits de barres de m.à.l.t.
Kits de cosses de neutre surdimensionnées pour panneaux de 100-600 A
Kits de cosses secondaires pour panneaux de distribution 100-400 A
Kit de cosses principales
Kits de cosses mécaniques en aluminium
Kits de cosses mécaniques en cuivre
Kits de cosses à compression Versa-Crimp en aluminium
Kits de cosses à compression Versa-Crimp en cuivre
Kits de barrières côté ligne et de brides de fixation au neutre
Kits de barres de m.à.l.t.
Les kits de barres de m.à.l.t. de l’équipement, adaptés aux fils de cuivre ou
d’aluminium, répondent aux besoins de mise à la terre des panneaux NQ et des
centres de charge QONQ.
Tableau 12 - Spécifications des kits de barres de m.à.l.t.
Panneau de distribution Utiliser le numéro de catalogue du kit de barres
de m.à.l.t.
Circuit de dérivation Calibre Du Réseau Aluminium11 Cuivre12
1-42 600 A maximum
(1) PK27GTA (1) PK27GTACU
54-84 (2) PK27GTA (2) PK27GTACU
Les emplacements de montage de la barre de m.à.l.t. sont identifiés par le
symbole de terre estampé sur la paroi arrière de l’armoire.
Kits de cosses de neutre surdimensionnées pour panneaux
de 100-600 A
Des kits de cosses de neutre surdimensionnés sont disponibles pour les applications
où des conducteurs de terminaison 3 AWG ou plus sont nécessaires pour le neutre.
Tableau 13 - Spécifications des kits de cosses de neutre surdimensionnées
pour panneaux de 100-600 A
Calibre du
disjoncteur Numéro de catalogue de
kit Calibre de câble Al/Cu (mm2)
70 A QO70AN
(1) 12 – 2 AWG Al ([1] 3,3–33,6)
(1) 14 – 4 AWG Cu ([1] 2,1–21,2)
80-100 A NQ100AN (1) 14 – 2/0 AWG Al/Cu ([1] 2,1–67,4)
36 80043-712-06
11. Barres en aluminium adaptées aux conducteurs en cuivre ou en aluminium à 60 °C ou à 75 °C.
12. Barres en cuivre adaptées aux conducteurs en cuivre à 60 °C ou à 75 °C.
Annexe 2 : Kits d’accessoires Classe 1640
Tableau 13 - Spécifications des kits de cosses de neutre surdimensionnées
pour panneaux de 100-600 A (Suite)
Calibre du
disjoncteur Numéro de catalogue de
kit Calibre de câble Al/Cu (mm2)
80-120 A Q1100AN (1) 4 – 1/0 AWG Al/Cu ([1] 21,2–53,5)
110-150 A Q1150AN13 (1) 1 – 2/0 AWG Al/Cu ([1] 42,4–67,4)
175-200 A NQ200AN (1) 4 AWG – 300 kcmil Al/Cu ([1] 21,2–152)
Kits de cosses secondaires pour panneaux de distribution
100-400 A
Les cosses principales secondaires sont disponibles pour les applications 100, 225
ou 400 A.
Tableau 14 - Spécifications des kits de cosses secondaires pour panneaux de
distribution 100-400 A
Ampères principaux Numéro de catalogue de kit Maximum circuits
100 NQSFL1 18, 30
225 NQSFL2 3014, 4215, 5415, 7215, 8415
400 NQSFL4 30, 42, 54, 72, 84
Kit de cosses principales
Tableau 15 - Kits de cosses mécaniques en aluminium
Ampères pour le panneau
de distribution Numéro de catalogue de
kit Calibre de câble Al/Cu (mm2)
100 Norme #6 – 2/0 AWG
(13,3 – 67,43 mm2)
225 Norme 6 AWG – 350 kcmil
(13,3–177,3 mm2)
400 Norme
(1) 1/0 AWG – 750 kcmil
(2) 1/0 AWG–350 kcmil
([1] 53,48 – 380 mm2)
([2] 53,48 – 177,3 mm2)
600
Norme (2) 1/0 AWG – 750 kcmil
([2] 53,48 – 380 mm2)
NQALM6A (3) 6 AWG – 250 kcmil
([3] 13,3–127 mm2)
80043-712-06 37
13. N’utilisez que du fil de cuivre Nº 0 (26,7 mm2) pour les applications à disjoncteur de dérivation de 150 A.
14. Avec ces panneaux, prévoir un espace supplémentaire de 152,4 mm (6 po) pour le boîtier et la façade afin de pouvoir courber les fils.
15. Avec ces panneaux, réservez un espace supplémentaire de 152,4 mm (6 po) pour le boîtier et la façade afin de pouvoir courber les fils.
Classe 1640 Annexe 2 : Kits d’accessoires
Tableau 16 - Kits de cosses mécaniques en cuivre
Ampères pour le panneau
de distribution Numéro de catalogue de
kit Calibre de câble Al/Cu (mm2)
100 NQCUM1 #6 – 2/0 AWG
(13,3 – 67,43 mm2)
225 NQCUM2 6 AWG – 250 kcmil
(13,3–127 mm2)
400 NQCUM4 (1) 1/0 AWG – 750 kcmil
(2) 1/0 AWG – 350 kcmil
([1] 53,48 – 380 mm2)
([2] 53,48–177,3 mm2)
600 NQCUM6
Tableau 17 - Kits de cosses à compression Versa-Crimpen aluminium
Ampères pour le
panneau de
distribution
Numéro de catalogue
de kit
Calibre de câble Al/Cu
(mm2)Outil de sertissage
100 NQALV1 8 – 1/0 AWG
(8,36–53,48 mm2)VC6 (Tous)
225 NQALV2 #4 AWG – 300 kcmil
(21,15 – 152 mm2)
400 NQALV4 (2) 2/0 AWG –
500 kcmil
([2] 67,43 – 253,4 mm2)VC6–3, VC6–FT
600 NQALV6
Tableau 18 - Kits de cosses à compression Versa-Crimpen cuivre
Ampères pour le
panneau de
distribution
Numéro de catalogue
de kit
Calibre de câble Al/Cu
(mm2)Outil de sertissage
100 NQCUV1 #6 – 1/0 AWG
(13,30 – 53,48 mm2)VC6 (Tous), VC7 (Tous)
225 NQCUV2 2/0 AWG – 300 kcmil
(67,43–152 mm2)VC6-3, VC7, VC6-FT,
VC7–FT
400 NQCUV4 400 – 750 kcmil
(202,7 – 380 mm2)VC6-FT, VC7–FT, VC8
600 NQCUV6 (2) 250 – 500 kcmil
([2) 126,7–253,4 mm2)VC6-3, VC7, VC6-FT,
VC7–FT
Kits de barrières côté ligne et de brides de fixation au neutre
En fonction de l’application et du code d’installation adopté, une barrière côté ligne et
une bride de fixation au neutre peuvent être nécessaires. Sélectionnez la barrière
appropriée dans le tableau ci-dessous, en fonction du disjoncteur principal.
38 80043-712-06
Annexe 2 : Kits d’accessoires Classe 1640
Tableau 19 - Kits de barrières côté ligne et de brides de fixation au neutre
Nº de catalogue Contenu Description
Couvercle de cosses de ligne Bride de fixation au neutre
NQLALLC
Couvercle de cosses
de ligne NQ LA/LH,
bride de fixation au
neutre et cosse
NQHJQLLC
Couvercle de cosses
de ligne NQ H/J/Q et
bride de fixation au
neutre
NQPPLLLC
Couvercle de cosses
de ligne PowerPact
L, bride de fixation au
neutre et cosse
80043-712-06 39
Schneider Electric Canada, Inc.
5985 McLaughlin Road
Mississauga, ON L5R 1B8
Canada
800-565-6699
www.se.com/ca
Puisque les normes, caractéristiques techniques et conceptions
changent à l’occasion, assurez-vous de vérifier si les renseignements
contenus dans la présente publication
© 2007 – 2023 Schneider Electric. Tous droits réservés.
80043-712-06
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120

Square D Company QO-B120 Guía de instalación

Tipo
Guía de instalación
Este manual también es adecuado para

En otros idiomas