26 Unidad interior
Modo de ajuste del E.S.P
Note :
1. The above table shows the correlation between the air rates and E.S.P.
2. E.S.P. is given after subtracting coil losses motor step factory installed
3. E.S.P. can be higher than the maximum given in the table, but the unit faces the problem of freezing the coil.
ARNU07GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)
ARNU09GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)
ARNU12GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)
ARNU15GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)
ARNU18GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y)
ARNU24GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y)
Presión estática(mmAq(Pa))
Valor de ajuste
0(0) 1(10) 2(20) 3(30) 4(40)
60 6.29 3.03 0.93 - -
65 6.61 4.84 1.52 - -
70 7.69 5.64 2.18 0.79 -
75 8.19 6.28 2.81 0.85 -
80 8.91 7.43 4.96 1.58 -
85 9.51 8.14 5.91 2.75 0.95
90 10.21 8.76 6.79 3.41 1.36
95 10.83 9.62 8.11 5.48 2.61
100 11.31 10.55 9.02 6.12 3.31
105 11.84 11.19 9.99 8.28 5.32
110 12.68 11.88 10.38 9.16 6.92
115 13.19 12.22 11.55 10.21 8.23
Presión estática(mmAq(Pa))
Valor de ajuste
0(0) 1(10) 2(20) 3(30) 4(40)
75 10.32 7.68 3.55 - -
80 11.06 8.77 4.71 1.38 -
85 11.84 10.02 6.95 2.16 -
90 12.73 10.74 8.26 4.73 1.25
95 13.47 12.13 9.93 6.74 2.73
100 14.16 13.25 10.51 8.41 3.65
105 15.29 14.11 12.31 9.83 6.21
110 16.09 14.77 13.49 10.39 8.32
115 16.91 15.88 14.48 12.77 9.92
120 17.81 16.88 15.15 13.98 10.85
125 18.55 17.84 16.12 15.13 12.97
130 19.01 18.55 17.33 16.28 14.59
(Unit: CMM)