CARLO GAVAZZI EM23DINAV23XO1PFA Guía de instalación

Tipo
Guía de instalación
Carlo Gavazzi Controls SpA,
Via Safforze, 8 - 32100
Belluno (Italy)
Tel. +39 0437 355811,
Fax +39 0437 355880
CARLO GAVAZZI
Automation Components
EM23DIN MID IM ML CODE 8021682 130117
EM23 DIN Energy Meter
(pulse output)
[6]
VDC
[5]
VDC
ENGLISH
n DESCRIPTION
A- Joystick: move the joystick to direction 1 to display the kWh
meter, to direction 2 to display the currents and to direction 3 to
display the kvarh meter. The instrument will automatically go
back to the kWh meter page, as default, after one minute.
B- Sequence phase alarm: shows if the phase sequence is
wrong. The measurement is independent of the current flow
direction (only X and PFA version).
“EEE” is displayed in case of “OVERFLOW”.
NOTE: the meter is not tested for energy supply networks with
interferences in the frequency range from 2 kHz to 150kHz.
n ELECTRICAL CONNECTIONS
[1]- 3 phases, 4 wires, unbalanced/balanced load.
[2]- 3 phases, 3 wires, unbalanced/balanced load.
[3]- 2 phases, 3 wires, unbalanced/balanced load.
[4]- 1 phase, 2 wires
Note: N is mandatory only in AV9 version.
[5]- Open collector output (GND reference).
[6]- Open collector output (VDC reference).
The value of the load resistance (Rc) must make the close-
contact current be lower than 100 mA; the VDC voltage must be
lower than or equal to 30 V. VDC: (external) power supply volt-
age. Out: positive output contact (transistor type open collector).
GND: output contact connected to ground (transistor type open
collector).
n SAFETY PRECAUTIONS
Read carefully the instruction manual. If the instru-
ment is used in a manner not specified by the pro-
ducer, the protection provided by the instrument may
be impaired. Maintenance: make sure that the connections
are correctly carried out in order to avoid any malfunctioning or
damage to the instrument. To keep the instrument clean, use a
slightly damp cloth; do not use any abrasives or solvents. We
recommend to disconnect the instrument before cleaning it.
n TECHNICAL SPECIFICATIONS
Input specifications: System type: 3. Current: direct input, cur-
rent range 10 (65) A. Accuracy (display): (@25°C ±5°C, R.H.
≤60%, 48-62Hz) Ib: 10A, Imax: 65A; Un: 318 to 480VLL (AV9);
196 to 460VLL (AV2). Current: from 0.2Ib to Imax: ±(0.5% RDG
+1DGT). Active power ±(1%RDG +2DGT). Reactive power
±(2%RDG +2DGT). Energies, Class 1 according to EN62053-
21, class B according to EN50470-3 and Class 2 according to
EN62053-23. Ib: 10A, Imax: 65A; start-up current: 40mA.
Additional errors: influence quantities: according to EN62053-
21, EN62053-23. Temperature drift: ≤200ppm/°C. Sampling
frequency: 1600 samples/s at 50Hz, 1900 samples/s at 60Hz.
Display: 2 rows (1 x 7 DGT; 2 x 3 DGT). Type: LCD, h 9mm.
Instantaneous variables: 3 DGT. Energies: 7 DGT autorange.
Overload status: EEE indications when the measured value
exceeds the “continuous input overload” (max. measuring
capacity). Max. and Min. indication: max. instantaneous vari-
ITALIANO
n DESCRIZIONE
A- Joystick: spingere in direzione 1 per visualizzare il contatore
di kWh. Spingere in direzione 2 per visualizzare le correnti.
Spingere in direzione 3 per visualizzare il contatore di kvarh.
La pagina visualizzata di default è quella del contatore di kWh;
lo strumento si riporterà automaticamente su di essa dopo un
minuto.
B- Allarme sequenza fasi: indica che la sequenza delle fasi non
è corretta (solo versioni X e PFA).
La misura è indipendente dal verso della corrente.
In caso di “OVERFLOW” lo strumento visualizza “EEE”.
Nota: lo strumento non è testato per linee di alimentazione con
interferenze nel range di frequenza da 2 kHz a 150kHz.
n COLLEGAMENTI ELETTRICI
[1]- 3 fasi, 4 fili, carico squilibrato/equilibrato.
[2]- 3 fasi, 3 fili, carico squilibrato/equilibrato.
[3]- 2 fasi, 3 fili, carico squilibrato/equilibrato.
[4]- 1 fase, 2 fili.
Nota: N è obbligatorio solo per la versione AV9.
[5]- Uscita a collettore aperto (riferimento GND).
[6]- Uscita a collettore aperto (riferimento VDC).
La resistenza di carico (Rc) dev’essere dimensionata in modo
che la corrente a contatto chiuso sia inferiore a 100 mA; la ten-
sione VDC dev’essere inferiore o uguale a 30V. VDC: Tensione
di alimentazione (esterna). Out: contatto di uscita positivo (col-
lettore aperto tipo transistor). GND: contatto di uscita collegato a
massa (collettore aperto tipo transistor).
n NORME DI SICUREZZA
Leggere attentamente il manuale istruzioni. Qualora
l’apparecchio venisse adoperato in un modo non spe-
cificato dal costruttore, la protezione prevista dall’ap-
parecchio potrebbe essere compromessa. Manutenzione:
assicurarsi che i collegamenti siano effettuati correttamente al
fine di evitare qualsiasi malfunzionamento o danneggiamento
dello strumento. Per mantenere pulito lo strumento usare un
panno leggermente inumidito; non usare abrasivi o solventi. Si
consiglia di scollegare lo strumento prima di pulirlo.
n CARATTERISTICHE TECNICHE
Ingressi di misura: Sistema trifase. Corrente: Ingresso diretto
portata corrente 10 (65) A. Precisione (display): (@25°C ±5°C,
U.R. ≤60%, 48-62Hz) Ib: 10A, Imax: 65A. Un: da 318 a 480VLL
(AV9); da 196 a 460VLL (AV2). Corrente: da 0,2Ib a Imax:
±(0,5% RDG +1DGT). Potenza attiva ±(1%RDG +2DGT).
Potenza reattiva ±(2%RDG +2DGT). Energie, Classe 1 secon-
do EN62053-21, classe B secondo EN50470-3 e Classe 2
secondo EN62053-23. Ib: 10A, Imax: 65A; corrente di avvia-
mento: 40mA.
Errori addizionali: grandezze di influenza: secondo EN62053-
21, EN62053-23. Deriva termica: ≤200ppm/°C. Frequenza di
campionamento: 1600 campioni/s a 50Hz, 1900 campioni/s
a 60Hz. Display: 2 linee (1 x 7 DGT; 2 x 3 DGT). Tipo: LCD,
DEUTSCH
n BESCHREIBUNG
A- Joystick: um die kWh Zähler anzuzeigen, muß der Joystick in
Richtung 1 gedrückt werden; um die Ströme anzuzeigen, muß der
Joystick in Richtung 2 gedrückt werden; um die kvarh Zähler anzu-
zeigen, muß der Joystick in Richtung 3 gedrückt werden. Die kWh
Zähler werden nach einer Minute automatisch angezeigt.
B- Phasenfolge Alarm: die Phasenfolge ist falsch. Die Messung ist
unabhängig von der Stromrichtung (nur X und PFA Optionen).
Im Falle einer Messbereichsüberschreitung, wird “EEE” ange-
zeigt.
HINWEIS: Das Messgerät ist nicht für Energieversorgungnetze mit
Interferenzen im Frequenzbereich 2kHz-150 kHz getestet.
n ELEKTRISCHE ANSCHLUSS
[1]- 3-Phasen, 4-Adern asymmetrische/symmetriche Last.
[2]- 3-Phasen, 3-Adern, asymmetrische/symmetriche Last.
[3]- 2-Phasen, 3-Adern, asymmetrische/symmetriche Last.
[4]- 1-Phase, 2-Adern.
Hinweis: N ist nur in AV9 Version obligatorisch.
[5]- Open Kollektor Ausgang (GND Bezug).
[6]- Open Kollektor Ausgang (VDC Bezug).
Die Widerstandslast (Rc) muß so bemessen werden, daß
bei geschlossenem Kontakt, der Strom unter 100mA ist, die
Versorgungsspannung “VDC” muß kleiner oder gleich 30VDC sein.
VDC: externe Stromversorgung. Out: posi-
tiver Ausgangskontakt (open Kollektor-Transistorausgang). GND:
Masseanschluss (open Kollektor-Transistorausgang).
n SICHERHEITSBESTIMMUNGEN
Die Betriebsanleitung aufmerksam lesen. Sollte das
Gerät nicht gemäss der Herstellerangaben verwendet
werden, könnte der vom Gerät vorgesehene Schutz beein-
trächtigt werden. Wartung: Beachten Sie den korrekten Anschluss
aller Anschlussterminals um eine Beschädigung des Instruments
zu vermeiden. Das Gerät mit einem feuchten Tuch reinigen; keine
Scheuer- oder Lösemittel verwenden. Das Gerät vor der Reinigung
ausschalten.
n TECHNISCHE DATEN
Messeingänge (Nennwerte): 3 Phasensystem. Strommessung:
Direktmessung: Strombereich 10 (65) A. Genauigkeit (Anzeige):
(@25°C ±5°C, R.F. ≤60%, 48-62Hz) Ib: 10A, Imax: 65A. Un: von
318 bis 480VLL (AV9); von 196 bis 460VLL (AV2). Strom: von
0,2Ib bis Imax: ±(0,5% RDG +1DGT). Wirkleistung ±(1%RDG
+2DGT). Blindleistung ±(2%RDG +2DGT). Energien, Klasse 1
gemäß EN62053-21, Klasse B gemäß EN50470-3 und Klasse 2
gemäß EN62053-23. Ib: 10A, Imax: 65A; Startstrom: 40mA.
Zusätlicher Energiefehler: Bereichsüberschreitungsabhängig:
gemäß EN62053-21, EN62053-23. Temperaturbewegung:
≤200ppm/°C. Abtastrate: 1600 Abtastpunkte/s @ 50Hz, 1900
Abtastpunkte/s @ 60Hz. Anzeige: 2 Linien (1 x 7 DGT; 2 x 3 DGT). Art:
LCD, h 9mm. Momentanmessgrößen: 3 DGT. Energien: 7 DGT mit
automatischer Messbereichsumschaltung. Überlastungsanzeige:
EEE-Anzeige bei dauer hafter überhöhter Eingangsüberlastung
(Überschreitung der Messeingangs-maximalwerte). Max. und Min.
FRANÇAIS
n DESCRIPTION
A- Joystick: actionner le joystick dans la direction 1 pour afficher
le compteur kWh. Actionner le joystick dans la direction 2 pour
afficher les courants. Afficher le joystick dans la direction 3 pour
afficher le compteur kvarh. La page du compteur kWh est affi-
chée implicitement après 1 minute.
B- Alarme séquence phase: la séquence de phase n’est pas
correcte. La mesure est indépendante de la direction du courant
(seulement options X et PFA).
L’appareil affiche “EEE” dans le case de “SURCHARGE”.
REMARQUE: le compteur n’est pas testé pour les réseaux de
fourniture d’énergie avec des interférences dans la gamme de
fréquences de 2 kHz à 150 kHz.
n SCHEMAS ELECTRIQUES
[1]- 3 phases, 4 câbles, charge déséquilibrée/équilibrée.
[2]- 3 phases, 3 câbles, charge déséquilibrée/équilibrée.
[3]- 2 phases, 3 câbles, charge déséquilibrée/équilibrée.
[4]- 1 phase, 2 câbles.
Remarque: N est obligatoire uniquement pour la version AV9.
[5]- Sortie collecteur ouvert (référence GND).
[6]- Sortie collecteur ouvert (référence VDC).
La valeur de la résistance de charge (Rc) doit être telle que le
courant à contact-fermé soit inférieur à 100mA. Tension d’ali-
mentation: la tension VCC doit être inférieure ou égale à 30
VCC. VDC: tension alimentation (extérieure). Out: contact de
sortie positif (transistor collecteur ouvert). GND: contact de sortie
connecté à la terre (transistor à collecteur ouvert).
n MESURES DE SECURITE
Lire attentivement le manuel de l’utilisateur. Si l’ap-
pareil est utilisé dans des conditions différentes de celles
spécifiées par le fabricant, le niveau de protection prévu
par l’instrument peut être compromis. Entretien: s’assurer que
les connexions sont réalisées correctement dans le but d’éviter
toutes fautes ou endommagements de l’appareil. Pour nettoyer
l’instrument, utiliser un chiffon humide; ne pas utiliser d’abrasifs
ou de solvants. Il faut déconnecter le dispositif avant de procéder
au nettoyage.
n CARACTERISTIQUES TECNIQUES
Entrées nominales: système triphasé. Courant: Entrée directe:
plage de courant 10 (65) A. Précision (afficheur): (@25°C
±5°C, H.R. ≤60%, 48-62Hz) Ib: 10A, Imax: 65A; Un: de 318
à 480VLL (AV9); de 196 à 460VLL (AV2). Courant: de 0,2Ib
à Imax: ±(0,5% RDG +1DGT). Puissance active ±(1%RDG
+2DGT). Puissance réactive ±(2%RDG +2DGT). Energies,
Classe 1 selon EN62053-21, classe B selon EN50470-3 et
Classe 2 selon EN62053-23. Ib: 10A, Imax: 65A; courant de
démarrage: 40mA. Erreurs additionnelles énergie: quan-
tités influentes: selon EN62053-21, EN62053-23. Dérive de
température: ≤200ppm/°C. Taux d’échantillonnage: 1600
échantillons/s @ 50Hz, 1900 échantillons/s @ 60Hz. Afficheur:
2 lignes (1 x 7 DGT; 2 x 3 DGT). Type: LCD, h 9mm. Relevé
des variables instantanées: 3 DGT. Energies: 7 DGT auto
étallonage de la gamme. Etat de surcharge: le message “EEE”
ESPAÑOL
n DESCRIPCION
A- Joystick: para visualizar el contador kWh, mover el joystick
en dirección 1. Para visualizar las páginas de intensidad, mover
el joystick en dirección 2. Para visualizar el contador de kvarh,
mover el joystick en dirección 3. La página del contador kWh
es estándar, y el equipo la visualiza automáticamente después
un minuto.
B- Alarma secuencia fases: indica que la secuencia de las
fases no es correcta. La medida es independiente de la direc-
ción de la intensidad (sólo opcións X y PFA).
En caso de “SOBRECARGA” el equipo visualiza “EEE”.
NOTA: el equipo no se ha probado para redes con interferen-
cias en un rango de frecuencia de 2kHz a 150kHz.
n CONEXIONES ELÉCTRICAS
[1]- Trifásico, 4 hilos, carga desequilibrada/equilibrada.
[2]- Trifásico, 3 hilos, carga desequilibrada/equilibrada.
[3]- Bifásico, 3 hilos, carga desequilibrada/equilibrada.
[4]- Monofásico, 2 hilos.
Nota: N es obligatorio sólo en versión AV9.
[5]- Salida colector abierto (referencia a negativo GND).
[6]- Salida colector abierto (referencia a negativo VDC).
El valor de la resistencia de la carga (Rc) debe hacer que la
intensidad a contacto cerrado sea inferior a 100 mA; la tensión
VCC debe ser menor o igual a 30 VCC. VDC: tensión de ali-
mentación (externa). Out: contacto salida positivo (transistor de
tipo colector abierto). GND: salida a negativo (transistor de tipo
colector abierto).
n NORMAS DE SEGURIDAD
Lea atentamente este manual de instrucciones. Si
el instrumento se usa de modo distinto al indicado por
el fabricante, la protección de seguridad ofrecida por el
instrumento podrá resultar dañada. Mantenimiento: asegúre-
se de montar correctamente los módulos extraibles y los cables
correspondientes para evitar un mal funcionamiento y posibles
daños en el equipo. Para limpiar el equipo, utilizar siempre un
trapo ligeramente humedecido, nunca productos abrasivos o
disolventes. Se recomienda desconectar siempre el instru-
mento antes de limpiarlo.
n ESPECIFICACIONES TECNICAS
Entradas de medida: Sistema trifásico. Intensidad: conexión
directa 10 (65) A. Precisión: (display): (@25°C ±5°C, H.R.
≤60%, 48-62Hz) Ib: 10A, Imax: 65A; Vn: de 318 a 480VLL
(AV9); de 196 a 460VLL (AV2). Intensidad: de 0,2Ib a Imax:
±(0,5% lec. +1díg.). Potencia activa ±(1% lec. +2díg.). Potencia
reactiva ±(2%lec. +2díg.). Energías: clase 1 según EN62053-
21, clase B según EN50470-3 y clase 2 según EN62053-23.
Ib: 10A, Imax: 65A; Intensidad de arranque: 40mA. Errores
adicionales: influencia según norma EN62053-21, EN62053-
23. Deriva térmica: ≤200ppm/°C. Frecuencia de muestreo:
1600 lecturas/s @ 50Hz, 1900 lecturas/s @ 60Hz. Display: 2
líneas (1 x 7 DGT; 2 x 3 DGT). Tipo: LCD, h 9mm. Lectura de
variables instantáneas: 3 DGT. Energía: 7 DGT autorrango.
Indicación de sobrecarga: EEE cuando el valor medido excede
[1]
[2]
[3]
[4]
B
A
71,6
90
mm
45
43,6
16,4
66,3
!
!
!
!
!
ables: 999; energies: 9,999,999. Min. instantaneous variables:
0; energies 0,00. LED: red LED (consumed energy),100
pulses/kWh. Max frequency: 16Hz according to EN62052-11.
Measurements: TRMS measurement method of distorted
wave forms. Coupling type: direct. Crest factor: Ib 10A ≤4 (65A
max. peak). Current overload: continuous: 65A at 50Hz. For
10ms: 1920A max at 50Hz. Voltage overload: continuous 1,2
Un. For 500ms 2 Un. Input impedance: 400VL-L see “self-
consumption”: <4VA. Frequency: from 45 to 65 Hz. Joystick:
For the selection of the measuring pages. Pulse output: 1 out-
put 100 pulses per kWh. Type: output connectable to the energy
meter (kWh). Pulse duration: ≥100ms <120msec (ON), ≥120ms
(OFF), according to EN62052-31. Signal: VON 1.2 VDC/ max.
100 mA VOFF 30 VDC max. insulation: by means of optocou-
plers, 4000 VRMS outputs to measuring inputs. Operating
temperature: from -25°C to +55°C (from 13°F to 131°F), (R.H.
90% non condensing @ 40°C) according to EN62053-21 and
EN62053-23. Storage temperature: from -30°C to +70°C (from
22°F to 140°F) (R.H. < 90% non-condensing @ 40°C) according
to EN62053-21 and EN62053-23. Installation category: Cat. III
(IEC60664, EN60664) . Insulation (for 1 minute): 4000VRMS
between measuring inputs and power supply 4000VRMS
between power supply and RS485/digital outputs. Dielectric
strength: 4000 VRMS for 1 minute. Rejection: CMRR 100 dB
from 48 to 62 Hz. EMC: according to EN62052-11. Electrostatic
discharges: 15kV air discharge; Immunity to irradiated test with
current: 10V/m from 80 to 2000MHz; electromagnetic field test
without any current: 30V/m from 80 to 2000MHz; Burst on
current and voltage measuring input circuits: 4kV. Immunity to
conducted disturbances: 10V/m from 150KHz to 80MHz. Surge
on current and voltage measuring input circuits: 4kV. Radio
frequency suppression according to CISPR 22. Standard com-
pliance: safety IEC60664, IEC61010-1 EN60664, EN61010-1
EN62052-11. Metrology EN62053-21, EN62053-23, EN50470-
3. Pulse output: DIN43864, IEC62053-31. Approvals: CE.
Connections: screw-type. Cable cross section area: measur-
ing inputs max. 16 mm
2
; min. 2.5 mm
2
(by cable lug); min/max
screw tightening torque: 1.7 Nm / 3 Nm. Other inputs: 1.5 mm
2
.
Screws tightening torque: 0.5 Nm. DIN Housing: dimensions
71 x 90 x 64.5 mm. Material: nylon PA66; self-extinguishing:
UL 94 V-0. DIN rail mounting. Protection degree: front: IP50.
Connections: IP20. Weight: approx. 400 g (casing included).
Self power supply: -20% +15% 48-62Hz. Self consumption:
≤20VA/1W.
n MID CONFORMITY (only PF version)
Accuracy: 0.9 Un ≤ U ≤ 1.1 Un; 0.98 fn ≤ f ≤ 1,02 fn; fn: 50 or
60Hz; cosj: from 0.5 inductive to 0.8 capacitive. Model AV9,
Class B; I st: 0.04A; I min: 0.5A; I tr: 1A; I max: 65A. Operating
temperature: from -25°C to +55°C (from 13°F to 131°F) (R.H.
from 0 to 90% non condensing at 40°C). EMC conformity: E2.
Mechanical conformity: M2. *Protection degree: in order
to achieve the protection against dust and water required by
the norms harmonized to MID, the meter must be used only
installed in IP51 (or better) cabinets.
n MEASURING MODE (only PF versions)
PFA: energy is calculated both in case of imported and exported
power.
PFB: energy is calculated only in case of imported power.
The interfaces have not any effect on the measurements.
h 9mm. Lettura variabili istantanee: 3 DGT. Energie: 7 DGT
autorange. Stato sovraccarico: indicazione EEE quando il valore
misurato eccede il “sovraccarico continuo d’ingresso” (massima
capacità di misura). Indicazione Max. e Min.: Max. variabili
istantanee: 999; energie: 9.999.999. Min. variabili istantanee:
0; energie 0,00. LED: LED rosso (energia consumata),100
impulsi/kWh. Frequenza max: 16Hz secondo EN62052-11.
Misure: metodo TRMS misura delle forme d’onda distorte.
Tipo di accoppiamento: diretto. Fattore di cresta: Ib 10A ≤4
(65A max. picco). Sovraccarico corrente: continuo: 65A a
50Hz. Per 10ms: 1920A max a 50Hz. Sovraccarico tensione:
continuo 1,2 Un. Per 500ms 2 Un. Impedenza d’ingresso:
400VL-L vedi “autoconsumo”: < 4VA. Frequenza: da 45 a
65 Hz. Joystick: Per la selezione delle pagine di misura.
Uscita impulsi: 1 uscita 100 impulsi per kWh. Tipo: uscita
associata al contatore di energia (kWh). Durata dell’impulso:
≥100ms < 120msec (ON), ≥120ms (OFF), secondo EN62052-
31. Segnale: VON 1.2 VCC/ max. 100 mA VOFF 30 VCC max.
Isolamento: mediante optoisolatori, 4000 VRMS tra le uscite
e gli ingressi di misura. Temperatura di funzionamento: da
-25°C a +55°C (da 13°F a 131°F), (U.R. 90% senza condensa
@ 40°C) secondo EN62053-21 e EN62053-23. Temperatura
di immagazzinamento: da -30°C a +70°C (da 22°F a 140°F)
(U.R. <90% senza condensa @ 40°C) secondo EN62053-21 e
EN62053-23. Categoria di installazione: Cat. III (IEC60664,
EN60664) . Isolamento (per 1 minuto): 4000 VRMS tra
ingressi di misura ed alimentazione. 4000 VRMS tra alimenta-
zione e RS485/uscite digitali. Rigidità dielettrica: 4000 VRMS
per 1 minuto. Reiezione CMRR 100 dB da 48 a 62 Hz. EMC:
secondo EN62052-11. Scariche elettrostatiche: 15kV scarica
in aria; Immunità campi elettromagnetici irradianti: provato con
corrente applicata: 10V/m da 80 a 2000MHz; Provato senza
corrente applicata: da 30V/m da 80 a 2000MHz; Immunità ai
transitori veloci: sui circuiti degli ingressi di misura in corrente
e tensione: 4kV. Immunità ai radiodisturbi condotti: 10V/m
da 150KHz a 80MHz. Immunità ad impulso: sui circuiti degli
ingressi di misura in corrente e tensione: 4kV. Emissioni in
radiofrequenza secondo CISPR 22. Conformità alle norme:
sicurezza IEC60664, IEC61010-1 EN60664, EN61010-1
EN62052-11. Metrologia EN62053-21, EN62053-23, EN50470-
3. Uscita impulsiva: DIN43864, IEC62053-31. Approvazioni CE.
Connessioni: a vite. Sezione del cavo: Ingressi di misura max.
16 mm
2
; min. 2,5 mm
2
(mediante capocorda); coppia serraggio
viti min/max: 1,7 Nm / 3 Nm. Altri ingressi: 1,5 mm
2
. Coppia di
seraggio 0,5Nm. Custodia DIN: Dimensioni 71 x 90 x 64.5 mm.
Materiale: nylon PA66; autoestinguenza: UL 94 V-0. Montaggio
a guida DIN. Grado di protezione: frontale: IP50. Connessioni:
IP20. Peso: circa 400 g (imballo incluso). Autoalimentazione:
-20% +15% 48-62Hz. Autoconsumo: ≤ 20VA/1W.
n CONFORMITA MID (solo versione PF)
Precisione: 0,9 Un U 1,1 Un; 0,98 fn f 1,02 fn; fn:
50 o 60Hz; cosj: da 0,5 induttivo a 0,8 capacitivo. Modello
AV9, Classe B; I st: 0,04A; I min: 0,5A; I tr: 1A; I max: 65A.
Temperatura di funzionamento: da -25°C a +55°C (da 13°F a
131°F) (U.R. da 0 a 90% senza condensa a 40°C). Conformità
EMC: E2. Conformità meccanica: M2. *Grado di protezione:
al fine di conseguire la protezione contro polvere e acqua richie-
ste dalle norme MID, il contatore deve essere utilizzato solo se
installato in armadietti IP51 (o superiore).
n MODO MISURA (solo versione PF)
PFA: La potenza è sempre integrata (sia in caso di potenza
positiva -importata- che negativa - esportata).
PFB: Solamente la potenza positiva è integrata.
Le interfacce non hanno alcun effetto sulle misure
Anzeige: Max. momentanmessgrößen: 999; Energien: 9.999.999.
Min. Momentanmessgrößen: 0; Energien 0,00. LED-Leuchten:
rote LED (Energieverbrauch), 100 Imp./kWh. Max. Frequenz:
16Hz gemäß EN62052-11. Messmethode: TRMS-Messungen
von verzerrten Wellenformen. Direktkopplung. Scheitelwertfaktor:
Ib 10A ≤4 (65A Hochspitze). Überlaststrom: dauer: 65A @
50Hz. Für 10ms: 1920A max @ 50Hz. Überlastspannung:
dauer 1,2 Un. Für 500ms 2 Un. Eingangsimpedanz: 400VL-L
in Abhängigkeit der Leistungsauf-nahme: < 4VA. Frequenz: von
45 bis 65 Hz. Joystick (Frontseitiger): Zur Messgrößenwahl.
Impulsausgang: 1 Ausgang 100 Impulse pro kWh. Typ: mit
dem Energiezähler verknüpfbare Ausgänge (kWh). Impulsdauer:
≥100ms <120msec (ON), ≥120ms (OFF), gemäß EN62052-31.
Signal: VON 1.2 VDC/ max. 100 mA VOFF 30 VDC max. Isolation:
durch Optokoppler, 4000 VRMS Ausgang zur Eingangsmessung.
Betriebstemperatur: von -25°C bis +55°C (von 13°F bis 131°F),
(R.F. 90% nicht-kondensierend @ 40°C) gemäß EN62053-21
und EN62053-23. Lagertemperatur: von-30°C bis +70°C (von
22°F bis 140°F) (R.F. < 90% nicht-kondensierend @ 40°C) gemäß
EN62053-21 und EN62053-23. Installationskatego-rie: Kat.
III (IEC60664, EN60664). Isolationsspannung (für 1 Minute):
4000 VRMS zwischen Eingangsmessung und Stromversorgung.
4000 VRMS zwischen Stromversorgung und RS485/digital
Ausgang. Durchschlagfestigkeit: 4000 VRMS für 1 Minute.
Dämpfungsverhältnis: CMRR 100 dB von 48 bis 62 Hz.
EMC: gemäß EN62052-11. Elektrostatische Entladungen: 15kV
air discharge; Strahlungsimmunität: Test mit angelegten Strom:
10V/m von 80 bis 2000MHz; Test ohne angelegten Strom: von
30V/m bis 80 @ 2000MHz; Überspannungsfestigkeit: am Strom-
und Eingangsspannungsmesskreis: 4kV. Leiterstörungs-immunität:
10V/m von 150KHz bis 80MHz. Störimpulsfestigkeit: am Strom-
und Eingangsspannungsmesskreis: 4kV. Störabstrahlung gemäß
CISPR 22. Standardkonformität: Sicherheit IEC60664, IEC61010-
1 EN60664, EN61010-1 EN62052-11. Metrology: EN62053-
21, EN62053-23, EN50470-3. Impulsausgang: DIN43864,
IEC62053-31. Zulassungen: CE. Anschlusse: Schraubklemmen.
Kabelquerschnitt: Messeingänge max. 16 mm
2
; min. 2,5 mm
2
(mit
Kabelschuh); min./max. Schraubklemme-Drehmoment: 1,7 Nm / 3
Nm. Weitere Eingänge: 1,5 mm
2
. Schraubklemme-Drehmoment:
0,5. Gehäuse DIN: Abmessungen: 71 x 90 x 64.5 mm. Material:
Nylon PA66; selbstlöschend: UL 94 V-0. Montage: DIN Schiene.
Schutzgrad: Front: IP50. Anschlusse: IP20. Gewicht: ca. 400
g (incl. verpackung). Selbststromversorgung: -20% +15%
48-62Hz. Leistungsaufnahme: ≤ 20VA/1W.
n MID KONFORMITÄT (nur PF Option)
Genauigkeit: 0,9 Un ≤ U 1,1 Un; 0,98 fn f ≤ 1,02 fn; fn: 50 o
60Hz; cosj: von 0,5 induktiv bis 0,8 kapazitiv. Modelle AV9, Klasse
B; I st: 0,04A; I min: 0,5A; I tr: 1A; I max: 65A. Betriebstemperatur:
von -25°C bis +55°C (von 13°F bis 131°F) (r.F. von 0 bis 90% nicht-
kondensierend @ 40°C). EMV Konformität: E2. Mechanische
Konformität: M2. *
Schutzgrad: um den Schutz gegen Staub und
Wasser entsprechend der spezifischen Normen gemäß MID zu errei-
chen, muss der Energiezähler in einem Gehäuse oder Schaltschrank
mit Schutzgrad IP51 (oder höher) installiert werden.
n MESSMODUS (nur PF Option)
PFA: Die Leistung ist immer integriert (sowohl im Falle von positive-
naufgenommenen-und negativen-abgegebenen-Strom).
PFB: nur die positive Leistung integriert ist.
Die Schnittstellen haben keine Auswirkungen auf die
Messungen.
signal quand la valeur en cours de mesure excède la “surcharge
d’entrées continues” (capacité de mesure max.). Indication Max.
et Min.: Max. variables instantanées: 999; énergies: 9.999.999.
Min. variables instantanées: 0; énergies 0,00. LED: LED
rouge (consommation d’énergie), 100 imp./kWh. Fréquence
max: 16Hz selon EN62052-11. Mesures: méthode mesures
TRMS des formes d’ondes déformées. Type de serrage: direct.
Facteur de crête: Ib 10A ≤4 (65A pic max.). Surcharges de
courant: continu: 65A @ 50Hz. Pour 10ms: 1920A max @
50Hz. Surcharges de tension: continu 1,2 Un. Pour 500ms 2
Un. Impédance d’entrée: 400VL-L Se référer à “consommation
d’énergie”: < 4VA. Fréquence: de 45 à 65 Hz. Joystick: Pour
la sélection des pages de mesure. Sortie d’impulsion: 1 sortie
100 impulsions par kWh. Type: sortie à connecter au compteur
d’énergie (kWh). Durée d’impulsion: ≥100ms < 120msec (ON),
≥120ms (OFF), selon EN62052-31. Signal: VON 1.2 VCC/
max. 100 mA VOFF 30 VCC max. Isolation: par optocoupleurs,
4000 VRMS entre sorties et entrées de mesure. Température
de fonctionnement: de -25°C à +55°C (de 13°F à 131°F),
(H.R. 90% sans condensation @ 40°C) selon EN62053-21 et
EN62053-23. Température de stockage: de -30°C à +70°C
(de 22°F à 140°F) (H.R. < 90% sans condensation @ 40°C)
selon EN62053-21 et EN62053-23. Catégorie d’installation:
Cat. III (IEC60664, EN60664) . Isolation (pendant 1 minute):
4000 VRMS entre entrées de mesure et alimentation. 4000
VRMS entre alimentation et RS485/sortie logique. Tension
diélectrique: 4000 VRMS pour 1 minute. Emission de bruit:
CMRR 100 dB de 48 à 62Hz. EMC: selon EN62052-11.
Décharges électrostatiques: 15kV décharge atmosphérique;
Immunité aux bruits par conduction: test avec courant: 10V/m
de 80 à 2000MHz; Test sans courant aucun courant: 30V/m de
80 à 2000MHz; Transitoires: sur circuits d’entrées de mesure
courant et tension: 4kV. Immunité aux bruits par conduction:
10V/m de 150KHz à 80MHz. Immunité à l’impulsion: sur circuits
d’entrées de mesure courant et tension: 4kV. Suppression
fréquence radio selon CISPR 22. Conformité aux stan-
dards: sécurité IEC60664, IEC61010-1 EN60664, EN61010-1
EN62052-11. Métrologie EN62053-21, EN62053-23, EN50470-
3. Sortie impulsion: DIN43864, IEC62053-31. Approbations CE.
Connexions: à vis. Section de câble: Entrées de mesure max.
16 mm
2
; min. 2,5 mm
2
(avec raccord de câbles); min. 2,5 mm
2
(entrées de mesure), couple de serrage de vis min./max: 1,7
Nm / 3 Nm. Autres entrées: 1,5 mm
2
. Couple de serrage de vis:
0,5Nm. Boîtier DIN. Dimensions 71 x 90 x 64.5 mm. Matériau:
nylon PA66; auto extinguible: UL 94 V-0. Montage: sur rail DIN.
Indice de protection: face avant: IP50. Terminaisons de vis:
IP20. Poids: environs 400 g (emballage inclus). Version auto-
alimentée: -20% +15% 48-62Hz. Consommation d’énergie:
≤20VA/1W.
n CONFORMITE MID (seulement option PF)
Précision: 0,9 Un ≤ U ≤ 1,1 Un; 0,98 fn ≤ f ≤ 1,02 fn; fn: 50 ou
60Hz; cosj: de 0,5 inductif à 0,8 capacitif. Modèles AV9, Classe
B; I st: 0,04A; I min: 0,5A; I tr: 1A; I max: 65A. Température de
fonctionnement: de -25°C à +55°C (de 13°F à 131°F) (H.R. de
0 à 90% sans condensation @ 40°C). Conformité CEM: E2.
Conformité mécanique: M2. *Indice de protection: afin d’as-
surer la protection contre la poussière et l’eau conformément
aux normes MID, le compteur étant IP51, il est recommandé
pour les applications à environnement sévère d’utiliser un coffret
de protection ayant un IP adapté.
n MODE DE MESURE (seulement option PF)
PFA: La puissance est toujours intégrée la fois en cas
d’alimentation positif-importéeet négatif-exportée).
PFB: seulement la puissance positive est intégré.
Les interfaces ne ont pas d’effet sur les mesures.
la “Sobrecarga de entrada continua” (capacidad máxima de
medida). Indicaciones máx. y mín: variables instantáneas máx.:
999; energías: 9.999.999. Variables instantáneas mín.: 0; ener-
gías 0,00. LED: LED rojo (energía consumida), 100 pulsos/kWh.
Frecuencia máx: 16Hz según EN62052-11. Medidas: medida
TRMS de una onda distorsionada. Tipo de conexión: directo.
Factor de cresta: Ib 10A ≤4 (65A pico máx.). Sobrecargas
intensidad: continua: 65A a 50Hz. Durante 10ms: 1920A
máx @ 50Hz. Sobrecargas de tensión: continua 1,2 Vn.
Durante 500ms 2 Vn. Impedancia de entrada: 400VL-L ver
“autoconsumo”: < 4VA. Frecuencia: de 45 a 65 Hz. Joystick:
para la selección de las páginas de medida. Salida de pulso:
1 salida 100 pulsos para kWh. Tipo: salida correspondiente
al contador de energía (kWh). Duración del pulso: ≥100ms <
120mseg (ON), ≥120ms (OFF), según EN62052-31. Señal:
VON 1.2 VCC/ máx. 100mA VOFF 30 VCC máx. Aislamiento:
por medio de optoacopladores, 4000 VRMS entre salidas y
entradas de medida. Temperatura de funcionamiento: de
-25°C a +55°C (de 13°F a 131°F), (H.R. 90% sin condensación
@ 40°C) según EN62053-21 y EN62053-23. Temperatura
de almacenamiento: de -30°C a +70°C (de 22°F a 140°F)
(H.R. < 90% sin condensación @ 40°C) según EN62053-21
y EN62053-23. Categoría de instalación: Cat. III (IEC60664,
EN60664) . Aislamiento (durante 1 minuto): 4000VRMS
entre entradas de medida y entrada de alimentación. 4000
VRMS entre RS485/salidas digitales. Rigidez dieléctrica:
4000 VRMS durante 1 minuto. Inmunidad al ruido CMRR
100 dB de 48 a 62 Hz. Compatibilidad electromagnética
(EMC): según EN62052-11. Descargas electrostáticas: 15kV
en el aire; Inmunidad a los campos electromagnéticos radiados:
prueba con intensidad aplicada: 10V/m de 80 a 2000MHz;
Prueba sin intensidad aplicada: 30V/m de 80 a 2000MHz;
Ráfagas en el circuito de entradas de medida de intensidad
y tensión: 4kV. Inmunidad a las perturbaciones conducidas:
10V/m de 150KHz a 80MHz. Aislamiento: en los circuitos de las
entradas de medida en intensidad y tensión: 4kV. Emisiones
de radiofrecuencia CISPR 22. Conformidad con las nor-
mas: seguridad IEC60664, IEC61010-1 EN60664, EN61010-1
EN62052-11. Metrología EN62053-21, EN62053-23, EN50470-
3. Salida de pulso: DIN43864, IEC62053-31. Homologaciones
CE. Conexiones: a tornillo. Sección de cable: entradas de
medida máx. 16 mm
2
; mín. 2,5 mm
2
(con terminal de cable;
mín. 2,5 mm
2
(entradas de medida), Mín/Máx. par de apriete:
1,7 Nm / 3 Nm. Otras entradas: 1,5mm
2
. Par de apriete: 0,5
Nm. Caja DIN: Dimensiones 71 x 90 x 64,5 mm. Material: nylon
PA66; autoextinguible: UL 94 V-0. Montaje: carril DIN. Grado
de protección: panel frontal: IP50. Conexiones: IP20. Peso:
aprox. 400 g (embalaje incluido). Autoalimentación: -20%
+15% 48-62Hz. Autoconsumo: ≤ 20VA/1W.
n CONFORMIDAD MID (sólo opción PF)
Precisión: 0,9 Vn V ≤ 1,1 Vn; 0,98 fn ≤ f ≤ 1,02 fn; fn: 50 o
60Hz; cosj: de 0,5 inductiva a 0,8 capacitiva. Modelo AV9, Clase
B; I st: 0,04A; I min: 0,5A; I tr: 1A; I max: 65A. Temperatura de
funcionamiento: de -25°C a +55°C (de 13°F a 131°F) (H.R.
de 0 a 90% sin condensación 40°C). Conformidad EMC: E2.
Compatibilidad EMC: M2. *Grado de protección: Con el fin
de alcanzar la protección contra polvo y agua requerida por las
normas armonizadas según MID, el medidor debe instalarse
sólo en armarios con protección IP51 o superior.
n MODO DE MEDICIÓN (sólo opción PF)
PFA: Integradas potencia positiva y negativa (no importa
polaridad del trafo, siempre mide energía positiva-gene-
rada y consumida).
PFB: solo la potencia positiva es integrada.
Las interfaces no tienen ningún efecto sobre las mediciones.
MID COMPLIANCE
For legal metrology all EM23 models have to be further certified accor-
ding to Annex II modules “D” or “F” of MID directive. PAY ATTENTION:
for legal purpose, the proper metrology mark followed by the ID number
referred to the Annex II module “F” notified body or Annex II module “F”
verification laboratory shall be printed/sticked on the meter.
CONFORMITÀ MID
Per la misura fiscale, tutti i modelli EM23 devono essere ulteriormente
certificati secondo l’Allegato II moduli “D” o “F” della direttiva MID.
ATTENZIONE: per la misura fiscale, la marcatura metrologica seguita
dal numero identificativo dell’ente notificato Allegato II modulo “F”
o del laboratorio Allegato II modulo “F” deve essere presente sullo
strumento.
MID KONFORMITÄT
Lt. gesetzlichen Richtlinen des Messwesen müssen alle EM23 Modelle
nach Anhang D bzw. Anhang II Module “D” oder “F” der MID-Richtlinie
zertifiziert werden. ACHTUNG: aus rechtlichen Gründen muss die
ordnungsgemäße Eichkennzeichnung gefolgt von der ID-Nummer, des
Zertifizierers nach Anhang II Modul “F” oder jener Anhang II Modul “F”
am Zähler aufgedruckt / aufgeklebt werden.
CERTIFICATION
Pour la métrologie légale, tous les modèles EM23 doivent, en com-
plément, être certifiés en accord avec l’Annexe II modules “D” ou “F”
de la Directive MID. ATTENTION: le logo type métrologique suivi du
numéro d’identification se référant à l’Annexe II module “F” ou à l’An-
nexe II module “F” doit être imprimé/collé sur le compteur.
EN CUMPLIMIENTO CON LA DIRECTIVA MID
Para su uso en mediciones legales, todos modelos EM23 deben estar
certificados además según el Anexo II módulos “D” o “F” de la directiva
MID. ¡ATENCIÓN! Por razones legales, la marca indicadora de metrología
seguida del número ID en referencia a la etiqueta del Anexo II módulo “F”
de la entidad notificadora o de verificación del Anexo II módulo “F” debe
estar impresa/adherida en el medidor.

Transcripción de documentos

CARLO GAVAZZI EM23 DIN Energy Meter Automation Components [2] [3] A 45 90 EM23DIN MID IM ML CODE 8021682 130117 (pulse output) [1] Carlo Gavazzi Controls SpA, Via Safforze, 8 - 32100 Belluno (Italy) Tel. +39 0437 355811, Fax +39 0437 355880 B [4] VDC mm 71,6 [5] 16,4 43,6 VDC [6] 66,3 ENGLISH n DESCRIPTION A- Joystick: move the joystick to direction 1 to display the kWh meter, to direction 2 to display the currents and to direction 3 to display the kvarh meter. The instrument will automatically go back to the kWh meter page, as default, after one minute. B- Sequence phase alarm: shows if the phase sequence is wrong. The measurement is independent of the current flow direction (only X and PFA version). ITALIANO n DESCRIZIONE A- Joystick: spingere in direzione 1 per visualizzare il contatore di kWh. Spingere in direzione 2 per visualizzare le correnti. Spingere in direzione 3 per visualizzare il contatore di kvarh. La pagina visualizzata di default è quella del contatore di kWh; lo strumento si riporterà automaticamente su di essa dopo un minuto. B- Allarme sequenza fasi: indica che la sequenza delle fasi non “EEE” is displayed in case of “OVERFLOW”. è corretta (solo versioni X e PFA). NOTE: the meter is not tested for energy supply networks with La misura è indipendente dal verso della corrente. interferences in the frequency range from 2 kHz to 150kHz. In caso di “OVERFLOW” lo strumento visualizza “EEE”. n ELECTRICAL CONNECTIONS Nota: lo strumento non è testato per linee di alimentazione con interferenze nel range di frequenza da 2 kHz a 150kHz. [1]- 3 phases, 4 wires, unbalanced/balanced load. [2]- 3 phases, 3 wires, unbalanced/balanced load. n COLLEGAMENTI ELETTRICI [3]- 2 phases, 3 wires, unbalanced/balanced load. [1]- 3 fasi, 4 fili, carico squilibrato/equilibrato. [4]- 1 phase, 2 wires [2]- 3 fasi, 3 fili, carico squilibrato/equilibrato. Note: N is mandatory only in AV9 version. [3]- 2 fasi, 3 fili, carico squilibrato/equilibrato. [5]- Open collector output (GND reference). [4]- 1 fase, 2 fili. [6]- Open collector output (VDC reference). Nota: N è obbligatorio solo per la versione AV9. The value of the load resistance (Rc) must make the close- [5]- Uscita a collettore aperto (riferimento GND). contact current be lower than 100 mA; the VDC voltage must be [6]- Uscita a collettore aperto (riferimento VDC). lower than or equal to 30 V. VDC: (external) power supply volt- La resistenza di carico (Rc) dev’essere dimensionata in modo age. Out: positive output contact (transistor type open collector). che la corrente a contatto chiuso sia inferiore a 100 mA; la tenGND: output contact connected to ground (transistor type open sione VDC dev’essere inferiore o uguale a 30V. VDC: Tensione di alimentazione (esterna). Out: contatto di uscita positivo (colcollector). lettore aperto tipo transistor). GND: contatto di uscita collegato a n SAFETY PRECAUTIONS massa (collettore aperto tipo transistor). Read carefully the instruction manual. If the instrun NORME DI SICUREZZA ! ment is used in a manner not specified by the proLeggere attentamente il manuale istruzioni. Qualora ducer, the protection provided by the instrument may ! l’apparecchio venisse adoperato in un modo non spebe impaired. Maintenance: make sure that the connections cificato dal costruttore, la protezione prevista dall’apare correctly carried out in order to avoid any malfunctioning or parecchio potrebbe essere compromessa. Manutenzione: damage to the instrument. To keep the instrument clean, use a assicurarsi che i collegamenti siano effettuati correttamente al slightly damp cloth; do not use any abrasives or solvents. We fine di evitare qualsiasi malfunzionamento o danneggiamento recommend to disconnect the instrument before cleaning it. dello strumento. Per mantenere pulito lo strumento usare un panno leggermente inumidito; non usare abrasivi o solventi. Si n TECHNICAL SPECIFICATIONS consiglia di scollegare lo strumento prima di pulirlo. Input specifications: System type: 3. Current: direct input, current range 10 (65) A. Accuracy (display): (@25°C ±5°C, R.H. n CARATTERISTICHE TECNICHE ≤60%, 48-62Hz) Ib: 10A, Imax: 65A; Un: 318 to 480VLL (AV9); Ingressi di misura: Sistema trifase. Corrente: Ingresso diretto 196 to 460VLL (AV2). Current: from 0.2Ib to Imax: ±(0.5% RDG portata corrente 10 (65) A. Precisione (display): (@25°C ±5°C, +1DGT). Active power ±(1%RDG +2DGT). Reactive power U.R. ≤60%, 48-62Hz) Ib: 10A, Imax: 65A. Un: da 318 a 480VLL ±(2%RDG +2DGT). Energies, Class 1 according to EN62053(AV9); da 196 a 460VLL (AV2). Corrente: da 0,2Ib a Imax: 21, class B according to EN50470-3 and Class 2 according to ±(0,5% RDG +1DGT). Potenza attiva ±(1%RDG +2DGT). EN62053-23. Ib: 10A, Imax: 65A; start-up current: 40mA. Potenza reattiva ±(2%RDG +2DGT). Energie, Classe 1 seconAdditional errors: influence quantities: according to EN62053do EN62053-21, classe B secondo EN50470-3 e Classe 2 21, EN62053-23. Temperature drift: ≤200ppm/°C. Sampling secondo EN62053-23. Ib: 10A, Imax: 65A; corrente di avviafrequency: 1600 samples/s at 50Hz, 1900 samples/s at 60Hz. mento: 40mA. Display: 2 rows (1 x 7 DGT; 2 x 3 DGT). Type: LCD, h 9mm. Errori addizionali: grandezze di influenza: secondo EN62053Instantaneous variables: 3 DGT. Energies: 7 DGT autorange. 21, EN62053-23. Deriva termica: ≤200ppm/°C. Frequenza di Overload status: EEE indications when the measured value campionamento: 1600 campioni/s a 50Hz, 1900 campioni/s exceeds the “continuous input overload” (max. measuring a 60Hz. Display: 2 linee (1 x 7 DGT; 2 x 3 DGT). Tipo: LCD, capacity). Max. and Min. indication: max. instantaneous vari- DEUTSCH FRANÇAIS ESPAÑOL n BESCHREIBUNG A- Joystick: um die kWh Zähler anzuzeigen, muß der Joystick in Richtung 1 gedrückt werden; um die Ströme anzuzeigen, muß der Joystick in Richtung 2 gedrückt werden; um die kvarh Zähler anzuzeigen, muß der Joystick in Richtung 3 gedrückt werden. Die kWh Zähler werden nach einer Minute automatisch angezeigt. B- Phasenfolge Alarm: die Phasenfolge ist falsch. Die Messung ist unabhängig von der Stromrichtung (nur X und PFA Optionen). Im Falle einer Messbereichsüberschreitung, wird “EEE” angezeigt. n DESCRIPTION A- Joystick: actionner le joystick dans la direction 1 pour afficher le compteur kWh. Actionner le joystick dans la direction 2 pour afficher les courants. Afficher le joystick dans la direction 3 pour afficher le compteur kvarh. La page du compteur kWh est affichée implicitement après 1 minute. B- Alarme séquence phase: la séquence de phase n’est pas correcte. La mesure est indépendante de la direction du courant (seulement options X et PFA). L’appareil affiche “EEE” dans le case de “SURCHARGE”. REMARQUE: le compteur n’est pas testé pour les réseaux de fourniture d’énergie avec des interférences dans la gamme de fréquences de 2 kHz à 150 kHz. n SCHEMAS ELECTRIQUES [1]- 3 phases, 4 câbles, charge déséquilibrée/équilibrée. [2]- 3 phases, 3 câbles, charge déséquilibrée/équilibrée. [3]- 2 phases, 3 câbles, charge déséquilibrée/équilibrée. [4]- 1 phase, 2 câbles. Remarque: N est obligatoire uniquement pour la version AV9. [5]- Sortie collecteur ouvert (référence GND). [6]- Sortie collecteur ouvert (référence VDC). La valeur de la résistance de charge (Rc) doit être telle que le courant à contact-fermé soit inférieur à 100mA. Tension d’alimentation: la tension VCC doit être inférieure ou égale à 30 VCC. VDC: tension alimentation (extérieure). Out: contact de sortie positif (transistor collecteur ouvert). GND: contact de sortie connecté à la terre (transistor à collecteur ouvert). n MESURES DE SECURITE Lire attentivement le manuel de l’utilisateur. Si l’ap! pareil est utilisé dans des conditions différentes de celles spécifiées par le fabricant, le niveau de protection prévu par l’instrument peut être compromis. Entretien: s’assurer que les connexions sont réalisées correctement dans le but d’éviter toutes fautes ou endommagements de l’appareil. Pour nettoyer l’instrument, utiliser un chiffon humide; ne pas utiliser d’abrasifs ou de solvants. Il faut déconnecter le dispositif avant de procéder au nettoyage. n DESCRIPCION A- Joystick: para visualizar el contador kWh, mover el joystick en dirección 1. Para visualizar las páginas de intensidad, mover el joystick en dirección 2. Para visualizar el contador de kvarh, mover el joystick en dirección 3. La página del contador kWh es estándar, y el equipo la visualiza automáticamente después un minuto. B- Alarma secuencia fases: indica que la secuencia de las fases no es correcta. La medida es independiente de la dirección de la intensidad (sólo opcións X y PFA). En caso de “SOBRECARGA” el equipo visualiza “EEE”. NOTA: el equipo no se ha probado para redes con interferencias en un rango de frecuencia de 2kHz a 150kHz. n CONEXIONES ELÉCTRICAS [1]- Trifásico, 4 hilos, carga desequilibrada/equilibrada. [2]- Trifásico, 3 hilos, carga desequilibrada/equilibrada. [3]- Bifásico, 3 hilos, carga desequilibrada/equilibrada. [4]- Monofásico, 2 hilos. Nota: N es obligatorio sólo en versión AV9. [5]- Salida colector abierto (referencia a negativo GND). [6]- Salida colector abierto (referencia a negativo VDC). El valor de la resistencia de la carga (Rc) debe hacer que la intensidad a contacto cerrado sea inferior a 100 mA; la tensión VCC debe ser menor o igual a 30 VCC. VDC: tensión de alimentación (externa). Out: contacto salida positivo (transistor de tipo colector abierto). GND: salida a negativo (transistor de tipo colector abierto). n NORMAS DE SEGURIDAD Lea atentamente este manual de instrucciones. Si ! el instrumento se usa de modo distinto al indicado por el fabricante, la protección de seguridad ofrecida por el instrumento podrá resultar dañada. Mantenimiento: asegúrese de montar correctamente los módulos extraibles y los cables correspondientes para evitar un mal funcionamiento y posibles daños en el equipo. Para limpiar el equipo, utilizar siempre un trapo ligeramente humedecido, nunca productos abrasivos o disolventes. Se recomienda desconectar siempre el instrumento antes de limpiarlo. HINWEIS: Das Messgerät ist nicht für Energieversorgungnetze mit Interferenzen im Frequenzbereich 2kHz-150 kHz getestet. n ELEKTRISCHE ANSCHLUSS [1]- 3-Phasen, 4-Adern asymmetrische/symmetriche Last. [2]- 3-Phasen, 3-Adern, asymmetrische/symmetriche Last. [3]- 2-Phasen, 3-Adern, asymmetrische/symmetriche Last. [4]- 1-Phase, 2-Adern. Hinweis: N ist nur in AV9 Version obligatorisch. [5]- Open Kollektor Ausgang (GND Bezug). [6]- Open Kollektor Ausgang (VDC Bezug). Die Widerstandslast (Rc) muß so bemessen werden, daß bei geschlossenem Kontakt, der Strom unter 100mA ist, die Versorgungsspannung “VDC” muß kleiner oder gleich 30VDC sein. VDC: externe Stromversorgung. Out: positiver Ausgangskontakt (open Kollektor-Transistorausgang). GND: Masseanschluss (open Kollektor-Transistorausgang). n SICHERHEITSBESTIMMUNGEN Die Betriebsanleitung aufmerksam lesen. Sollte das ! Gerät nicht gemäss der Herstellerangaben verwendet werden, könnte der vom Gerät vorgesehene Schutz beeinträchtigt werden. Wartung: Beachten Sie den korrekten Anschluss aller Anschlussterminals um eine Beschädigung des Instruments zu vermeiden. Das Gerät mit einem feuchten Tuch reinigen; keine Scheuer- oder Lösemittel verwenden. Das Gerät vor der Reinigung ausschalten. n TECHNISCHE DATEN Messeingänge (Nennwerte): 3 Phasensystem. Strommessung: Direktmessung: Strombereich 10 (65) A. Genauigkeit (Anzeige): (@25°C ±5°C, R.F. ≤60%, 48-62Hz) Ib: 10A, Imax: 65A. Un: von 318 bis 480VLL (AV9); von 196 bis 460VLL (AV2). Strom: von 0,2Ib bis Imax: ±(0,5% RDG +1DGT). Wirkleistung ±(1%RDG +2DGT). Blindleistung ±(2%RDG +2DGT). Energien, Klasse 1 gemäß EN62053-21, Klasse B gemäß EN50470-3 und Klasse 2 gemäß EN62053-23. Ib: 10A, Imax: 65A; Startstrom: 40mA. Zusätlicher Energiefehler: Bereichsüberschreitungsabhängig: gemäß EN62053-21, EN62053-23. Temperaturbewegung: ≤200ppm/°C. Abtastrate: 1600 Abtastpunkte/s @ 50Hz, 1900 Abtastpunkte/[email protected]:2Linien(1x7DGT;2x3DGT).Art: LCD, h 9mm. Momentanmessgrößen: 3 DGT. Energien: 7 DGT mit automatischer Messbereichsumschaltung. Überlastungsanzeige: EEE-Anzeige bei dauer hafter überhöhter Eingangsüberlastung (Überschreitung der Messeingangs-maximalwerte). Max. und Min. n CARACTERISTIQUES TECNIQUES Entrées nominales: système triphasé. Courant: Entrée directe: plage de courant 10 (65) A. Précision (afficheur): (@25°C ±5°C, H.R. ≤60%, 48-62Hz) Ib: 10A, Imax: 65A; Un: de 318 à 480VLL (AV9); de 196 à 460VLL (AV2). Courant: de 0,2Ib à Imax: ±(0,5% RDG +1DGT). Puissance active ±(1%RDG +2DGT). Puissance réactive ±(2%RDG +2DGT). Energies, Classe 1 selon EN62053-21, classe B selon EN50470-3 et Classe 2 selon EN62053-23. Ib: 10A, Imax: 65A; courant de démarrage: 40mA. Erreurs additionnelles énergie: quantités influentes: selon EN62053-21, EN62053-23. Dérive de température: ≤200ppm/°C. Taux d’échantillonnage: 1600 échantillons/s @ 50Hz, 1900 échantillons/s @ 60Hz. Afficheur: 2 lignes (1 x 7 DGT; 2 x 3 DGT). Type: LCD, h 9mm. Relevé des variables instantanées: 3 DGT. Energies: 7 DGT auto étallonage de la gamme. Etat de surcharge: le message “EEE” n ESPECIFICACIONES TECNICAS Entradas de medida: Sistema trifásico. Intensidad: conexión directa 10 (65) A. Precisión: (display): (@25°C ±5°C, H.R. ≤60%, 48-62Hz) Ib: 10A, Imax: 65A; Vn: de 318 a 480VLL (AV9); de 196 a 460VLL (AV2). Intensidad: de 0,2Ib a Imax: ±(0,5% lec. +1díg.). Potencia activa ±(1% lec. +2díg.). Potencia reactiva ±(2%lec. +2díg.). Energías: clase 1 según EN6205321, clase B según EN50470-3 y clase 2 según EN62053-23. Ib: 10A, Imax: 65A; Intensidad de arranque: 40mA. Errores adicionales: influencia según norma EN62053-21, EN6205323. Deriva térmica: ≤200ppm/°C. Frecuencia de muestreo: 1600 lecturas/s @ 50Hz, 1900 lecturas/s @ 60Hz. Display: 2 líneas (1 x 7 DGT; 2 x 3 DGT). Tipo: LCD, h 9mm. Lectura de variables instantáneas: 3 DGT. Energía: 7 DGT autorrango. Indicación de sobrecarga: EEE cuando el valor medido excede ables: 999; energies: 9,999,999. Min. instantaneous variables: 0; energies 0,00. LED: red LED (consumed energy),100 pulses/kWh. Max frequency: 16Hz according to EN62052-11. Measurements: TRMS measurement method of distorted wave forms. Coupling type: direct. Crest factor: Ib 10A ≤4 (65A max. peak). Current overload: continuous: 65A at 50Hz. For 10ms: 1920A max at 50Hz. Voltage overload: continuous 1,2 Un. For 500ms 2 Un. Input impedance: 400VL-L see “selfconsumption”: <4VA. Frequency: from 45 to 65 Hz. Joystick: For the selection of the measuring pages. Pulse output: 1 output 100 pulses per kWh. Type: output connectable to the energy meter (kWh). Pulse duration: ≥100ms <120msec (ON), ≥120ms (OFF), according to EN62052-31. Signal: VON 1.2 VDC/ max. 100 mA VOFF 30 VDC max. insulation: by means of optocouplers, 4000 VRMS outputs to measuring inputs. Operating temperature: from -25°C to +55°C (from 13°F to 131°F), (R.H. 90% non condensing @ 40°C) according to EN62053-21 and EN62053-23. Storage temperature: from -30°C to +70°C (from 22°F to 140°F) (R.H. < 90% non-condensing @ 40°C) according to EN62053-21 and EN62053-23. Installation category: Cat. III (IEC60664, EN60664) . Insulation (for 1 minute): 4000VRMS between measuring inputs and power supply 4000VRMS between power supply and RS485/digital outputs. Dielectric strength: 4000 VRMS for 1 minute. Rejection: CMRR 100 dB from 48 to 62 Hz. EMC: according to EN62052-11. Electrostatic discharges: 15kV air discharge; Immunity to irradiated test with current: 10V/m from 80 to 2000MHz; electromagnetic field test without any current: 30V/m from 80 to 2000MHz; Burst on current and voltage measuring input circuits: 4kV. Immunity to conducted disturbances: 10V/m from 150KHz to 80MHz. Surge on current and voltage measuring input circuits: 4kV. Radio frequency suppression according to CISPR 22. Standard compliance: safety IEC60664, IEC61010-1 EN60664, EN61010-1 EN62052-11. Metrology EN62053-21, EN62053-23, EN504703. Pulse output: DIN43864, IEC62053-31. Approvals: CE. Connections: screw-type. Cable cross section area: measuring inputs max. 16 mm2; min. 2.5 mm2 (by cable lug); min/max screw tightening torque: 1.7 Nm / 3 Nm. Other inputs: 1.5 mm2. Screws tightening torque: 0.5 Nm. DIN Housing: dimensions 71 x 90 x 64.5 mm. Material: nylon PA66; self-extinguishing: UL 94 V-0. DIN rail mounting. Protection degree: front: IP50. Connections: IP20. Weight: approx. 400 g (casing included). Self power supply: -20% +15% 48-62Hz. Self consumption: ≤20VA/1W. h 9mm. Lettura variabili istantanee: 3 DGT. Energie: 7 DGT autorange. Stato sovraccarico: indicazione EEE quando il valore misurato eccede il “sovraccarico continuo d’ingresso” (massima capacità di misura). Indicazione Max. e Min.: Max. variabili istantanee: 999; energie: 9.999.999. Min. variabili istantanee: 0; energie 0,00. LED: LED rosso (energia consumata),100 impulsi/kWh. Frequenza max: 16Hz secondo EN62052-11. Misure: metodo TRMS misura delle forme d’onda distorte. Tipo di accoppiamento: diretto. Fattore di cresta: Ib 10A ≤4 (65A max. picco). Sovraccarico corrente: continuo: 65A a 50Hz. Per 10ms: 1920A max a 50Hz. Sovraccarico tensione: continuo 1,2 Un. Per 500ms 2 Un. Impedenza d’ingresso: 400VL-L vedi “autoconsumo”: < 4VA. Frequenza: da 45 a 65 Hz. Joystick: Per la selezione delle pagine di misura. Uscita impulsi: 1 uscita 100 impulsi per kWh. Tipo: uscita associata al contatore di energia (kWh). Durata dell’impulso: ≥100ms < 120msec (ON), ≥120ms (OFF), secondo EN6205231. Segnale: VON 1.2 VCC/ max. 100 mA VOFF 30 VCC max. Isolamento: mediante optoisolatori, 4000 VRMS tra le uscite e gli ingressi di misura. Temperatura di funzionamento: da -25°C a +55°C (da 13°F a 131°F), (U.R. 90% senza condensa @ 40°C) secondo EN62053-21 e EN62053-23. Temperatura di immagazzinamento: da -30°C a +70°C (da 22°F a 140°F) (U.R. <90% senza condensa @ 40°C) secondo EN62053-21 e EN62053-23. Categoria di installazione: Cat. III (IEC60664, EN60664) . Isolamento (per 1 minuto): 4000 VRMS tra ingressi di misura ed alimentazione. 4000 VRMS tra alimentazione e RS485/uscite digitali. Rigidità dielettrica: 4000 VRMS per 1 minuto. Reiezione CMRR 100 dB da 48 a 62 Hz. EMC: secondo EN62052-11. Scariche elettrostatiche: 15kV scarica in aria; Immunità campi elettromagnetici irradianti: provato con corrente applicata: 10V/m da 80 a 2000MHz; Provato senza corrente applicata: da 30V/m da 80 a 2000MHz; Immunità ai transitori veloci: sui circuiti degli ingressi di misura in corrente e tensione: 4kV. Immunità ai radiodisturbi condotti: 10V/m da 150KHz a 80MHz. Immunità ad impulso: sui circuiti degli ingressi di misura in corrente e tensione: 4kV. Emissioni in radiofrequenza secondo CISPR 22. Conformità alle norme: sicurezza IEC60664, IEC61010-1 EN60664, EN61010-1 EN62052-11. Metrologia EN62053-21, EN62053-23, EN504703. Uscita impulsiva: DIN43864, IEC62053-31. Approvazioni CE. Connessioni: a vite. Sezione del cavo: Ingressi di misura max. 16 mm2; min. 2,5 mm2 (mediante capocorda); coppia serraggio viti min/max: 1,7 Nm / 3 Nm. Altri ingressi: 1,5 mm2. Coppia di seraggio 0,5Nm. Custodia DIN: Dimensioni 71 x 90 x 64.5 mm. n MID CONFORMITY (only PF version) Materiale: nylon PA66; autoestinguenza: UL 94 V-0. Montaggio Accuracy: 0.9 Un ≤ U ≤ 1.1 Un; 0.98 fn ≤ f ≤ 1,02 fn; fn: 50 or a guida DIN. Grado di protezione: frontale: IP50. Connessioni: 60Hz; cosj: from 0.5 inductive to 0.8 capacitive. Model AV9, IP20. Peso: circa 400 g (imballo incluso). Autoalimentazione: Class B; I st: 0.04A; I min: 0.5A; I tr: 1A; I max: 65A. Operating -20% +15% 48-62Hz. Autoconsumo: ≤ 20VA/1W. temperature: from -25°C to +55°C (from 13°F to 131°F) (R.H. from 0 to 90% non condensing at 40°C). EMC conformity: E2. n CONFORMITA’ MID (solo versione PF) Mechanical conformity: M2. *Protection degree: in order Precisione: 0,9 Un ≤ U ≤ 1,1 Un; 0,98 fn ≤ f ≤ 1,02 fn; fn: to achieve the protection against dust and water required by 50 o 60Hz; cosj: da 0,5 induttivo a 0,8 capacitivo. Modello the norms harmonized to MID, the meter must be used only AV9, Classe B; I st: 0,04A; I min: 0,5A; I tr: 1A; I max: 65A. installed in IP51 (or better) cabinets. Temperatura di funzionamento: da -25°C a +55°C (da 13°F a 131°F) (U.R. da 0 a 90% senza condensa a 40°C). Conformità n MEASURING MODE (only PF versions) EMC: E2. Conformità meccanica: M2. *Grado di protezione: PFA: energy is calculated both in case of imported and exported al fine di conseguire la protezione contro polvere e acqua richiepower. ste dalle norme MID, il contatore deve essere utilizzato solo se PFB: energy is calculated only in case of imported power. installato in armadietti IP51 (o superiore). The interfaces have not any effect on the measurements. MID COMPLIANCE For legal metrology all EM23 models have to be further certified according to Annex II modules “D” or “F” of MID directive. PAY ATTENTION: for legal purpose, the proper metrology mark followed by the ID number referred to the Annex II module “F” notified body or Annex II module “F” verification laboratory shall be printed/sticked on the meter. Anzeige: Max. momentanmessgrößen: 999; Energien: 9.999.999. Min. Momentanmessgrößen: 0; Energien 0,00. LED-Leuchten: rote LED (Energieverbrauch), 100 Imp./kWh. Max. Frequenz: 16Hz gemäß EN62052-11. Messmethode: TRMS-Messungen von verzerrten Wellenformen. Direktkopplung. Scheitelwertfaktor: Ib 10A ≤4 (65A Hochspitze). Überlaststrom: dauer: 65A @ 50Hz. Für 10ms: 1920A max @ 50Hz. Überlastspannung: dauer 1,2 Un. Für 500ms 2 Un. Eingangsimpedanz: 400VL-L in Abhängigkeit der Leistungsauf-nahme: < 4VA. Frequenz: von 45 bis 65 Hz. Joystick (Frontseitiger): Zur Messgrößenwahl. Impulsausgang: 1 Ausgang 100 Impulse pro kWh. Typ: mit dem Energiezähler verknüpfbare Ausgänge (kWh). Impulsdauer: ≥100ms <120msec (ON), ≥120ms (OFF), gemäß EN62052-31. Signal: VON 1.2 VDC/ max. 100 mA VOFF 30 VDC max. Isolation: durch Optokoppler, 4000 VRMS Ausgang zur Eingangsmessung. Betriebstemperatur: von -25°C bis +55°C (von 13°F bis 131°F), (R.F. 90% nicht-kondensierend @ 40°C) gemäß EN62053-21 und EN62053-23. Lagertemperatur: von-30°C bis +70°C (von 22°F bis 140°F) (R.F. < 90% nicht-kondensierend @ 40°C) gemäß EN62053-21 und EN62053-23. Installationskatego-rie: Kat. III (IEC60664, EN60664). Isolationsspannung (für 1 Minute): 4000 VRMS zwischen Eingangsmessung und Stromversorgung. 4000 VRMS zwischen Stromversorgung und RS485/digital Ausgang. Durchschlagfestigkeit: 4000 VRMS für 1 Minute. Dämpfungsverhältnis: CMRR 100 dB von 48 bis 62 Hz. EMC: gemäß EN62052-11. Elektrostatische Entladungen: 15kV air discharge; Strahlungsimmunität: Test mit angelegten Strom: 10V/m von 80 bis 2000MHz; Test ohne angelegten Strom: von 30V/m bis 80 @ 2000MHz; Überspannungsfestigkeit: am Stromund Eingangsspannungsmesskreis: 4kV. Leiterstörungs-immunität: 10V/m von 150KHz bis 80MHz. Störimpulsfestigkeit: am Stromund Eingangsspannungsmesskreis: 4kV. Störabstrahlung gemäß CISPR 22. Standardkonformität: Sicherheit IEC60664, IEC610101 EN60664, EN61010-1 EN62052-11. Metrology: EN6205321, EN62053-23, EN50470-3. Impulsausgang: DIN43864, IEC62053-31. Zulassungen: CE. Anschlusse: Schraubklemmen. Kabelquerschnitt: Messeingänge max. 16 mm2; min. 2,5 mm2 (mit Kabelschuh); min./max. Schraubklemme-Drehmoment: 1,7 Nm / 3 Nm. Weitere Eingänge: 1,5 mm2. Schraubklemme-Drehmoment: 0,5. Gehäuse DIN: Abmessungen: 71 x 90 x 64.5 mm. Material: Nylon PA66; selbstlöschend: UL 94 V-0. Montage: DIN Schiene. Schutzgrad: Front: IP50. Anschlusse: IP20. Gewicht: ca. 400 g (incl. verpackung). Selbststromversorgung: -20% +15% 48-62Hz. Leistungsaufnahme: ≤ 20VA/1W. signal quand la valeur en cours de mesure excède la “surcharge d’entrées continues” (capacité de mesure max.). Indication Max. et Min.: Max. variables instantanées: 999; énergies: 9.999.999. Min. variables instantanées: 0; énergies 0,00. LED: LED rouge (consommation d’énergie), 100 imp./kWh. Fréquence max: 16Hz selon EN62052-11. Mesures: méthode mesures TRMS des formes d’ondes déformées. Type de serrage: direct. Facteur de crête: Ib 10A ≤4 (65A pic max.). Surcharges de courant: continu: 65A @ 50Hz. Pour 10ms: 1920A max @ 50Hz. Surcharges de tension: continu 1,2 Un. Pour 500ms 2 Un. Impédance d’entrée: 400VL-L Se référer à “consommation d’énergie”: < 4VA. Fréquence: de 45 à 65 Hz. Joystick: Pour la sélection des pages de mesure. Sortie d’impulsion: 1 sortie 100 impulsions par kWh. Type: sortie à connecter au compteur d’énergie (kWh). Durée d’impulsion: ≥100ms < 120msec (ON), ≥120ms (OFF), selon EN62052-31. Signal: VON 1.2 VCC/ max. 100 mA VOFF 30 VCC max. Isolation: par optocoupleurs, 4000 VRMS entre sorties et entrées de mesure. Température de fonctionnement: de -25°C à +55°C (de 13°F à 131°F), (H.R. 90% sans condensation @ 40°C) selon EN62053-21 et EN62053-23. Température de stockage: de -30°C à +70°C (de 22°F à 140°F) (H.R. < 90% sans condensation @ 40°C) selon EN62053-21 et EN62053-23. Catégorie d’installation: Cat. III (IEC60664, EN60664) . Isolation (pendant 1 minute): 4000 VRMS entre entrées de mesure et alimentation. 4000 VRMS entre alimentation et RS485/sortie logique. Tension diélectrique: 4000 VRMS pour 1 minute. Emission de bruit: CMRR 100 dB de 48 à 62Hz. EMC: selon EN62052-11. Décharges électrostatiques: 15kV décharge atmosphérique; Immunité aux bruits par conduction: test avec courant: 10V/m de 80 à 2000MHz; Test sans courant aucun courant: 30V/m de 80 à 2000MHz; Transitoires: sur circuits d’entrées de mesure courant et tension: 4kV. Immunité aux bruits par conduction: 10V/m de 150KHz à 80MHz. Immunité à l’impulsion: sur circuits d’entrées de mesure courant et tension: 4kV. Suppression fréquence radio selon CISPR 22. Conformité aux standards: sécurité IEC60664, IEC61010-1 EN60664, EN61010-1 EN62052-11. Métrologie EN62053-21, EN62053-23, EN504703. Sortie impulsion: DIN43864, IEC62053-31. Approbations CE. Connexions: à vis. Section de câble: Entrées de mesure max. 16 mm2; min. 2,5 mm2 (avec raccord de câbles); min. 2,5 mm2 (entrées de mesure), couple de serrage de vis min./max: 1,7 Nm / 3 Nm. Autres entrées: 1,5 mm2. Couple de serrage de vis: 0,5Nm. Boîtier DIN. Dimensions 71 x 90 x 64.5 mm. Matériau: nylon PA66; auto extinguible: UL 94 V-0. Montage: sur rail DIN. Indice de protection: face avant: IP50. Terminaisons de vis: IP20. Poids: environs 400 g (emballage inclus). Version auton MID KONFORMITÄT (nur PF Option) Genauigkeit: 0,9 Un ≤ U ≤ 1,1 Un; 0,98 fn ≤ f ≤ 1,02 fn; fn: 50 o alimentée: -20% +15% 48-62Hz. Consommation d’énergie: 60Hz; cosj: von 0,5 induktiv bis 0,8 kapazitiv. Modelle AV9, Klasse ≤20VA/1W. B; I st: 0,04A; I min: 0,5A; I tr: 1A; I max: 65A. Betriebstemperatur: von -25°C bis +55°C (von 13°F bis 131°F) (r.F. von 0 bis 90% nicht- n CONFORMITE’ MID (seulement option PF) kondensierend @ 40°C). EMV Konformität: E2. Mechanische Précision: 0,9 Un ≤ U ≤ 1,1 Un; 0,98 fn ≤ f ≤ 1,02 fn; fn: 50 ou 60Hz; cosj: de 0,5 inductif à 0,8 capacitif. Modèles AV9, Classe Konformität: M2. *Schutzgrad: um den Schutz gegen Staub und B; I st: 0,04A; I min: 0,5A; I tr: 1A; I max: 65A. Température de Wasser entsprechend der spezifischen Normen gemäß MID zu erreifonctionnement: de -25°C à +55°C (de 13°F à 131°F) (H.R. de chen, muss der Energiezähler in einem Gehäuse oder Schaltschrank 0 à 90% sans condensation @ 40°C). Conformité CEM: E2. mit Schutzgrad IP51 (oder höher) installiert werden. Conformité mécanique: M2. *Indice de protection: afin d’assurer la protection contre la poussière et l’eau conformément n MESSMODUS (nur PF Option) aux normes MID, le compteur étant IP51, il est recommandé PFA: Die Leistung ist immer integriert (sowohl im Falle von positive- pour les applications à environnement sévère d’utiliser un coffret naufgenommenen-und negativen-abgegebenen-Strom). de protection ayant un IP adapté. PFB: nur die positive Leistung integriert ist. la “Sobrecarga de entrada continua” (capacidad máxima de medida). Indicaciones máx. y mín: variables instantáneas máx.: 999; energías: 9.999.999. Variables instantáneas mín.: 0; energías 0,00. LED: LED rojo (energía consumida), 100 pulsos/kWh. Frecuencia máx: 16Hz según EN62052-11. Medidas: medida TRMS de una onda distorsionada. Tipo de conexión: directo. Factor de cresta: Ib 10A ≤4 (65A pico máx.). Sobrecargas intensidad: continua: 65A a 50Hz. Durante 10ms: 1920A máx @ 50Hz. Sobrecargas de tensión: continua 1,2 Vn. Durante 500ms 2 Vn. Impedancia de entrada: 400VL-L ver “autoconsumo”: < 4VA. Frecuencia: de 45 a 65 Hz. Joystick: para la selección de las páginas de medida. Salida de pulso: 1 salida 100 pulsos para kWh. Tipo: salida correspondiente al contador de energía (kWh). Duración del pulso: ≥100ms < 120mseg (ON), ≥120ms (OFF), según EN62052-31. Señal: VON 1.2 VCC/ máx. 100mA VOFF 30 VCC máx. Aislamiento: por medio de optoacopladores, 4000 VRMS entre salidas y entradas de medida. Temperatura de funcionamiento: de -25°C a +55°C (de 13°F a 131°F), (H.R. 90% sin condensación @ 40°C) según EN62053-21 y EN62053-23. Temperatura de almacenamiento: de -30°C a +70°C (de 22°F a 140°F) (H.R. < 90% sin condensación @ 40°C) según EN62053-21 y EN62053-23. Categoría de instalación: Cat. III (IEC60664, EN60664) . Aislamiento (durante 1 minuto): 4000VRMS entre entradas de medida y entrada de alimentación. 4000 VRMS entre RS485/salidas digitales. Rigidez dieléctrica: 4000 VRMS durante 1 minuto. Inmunidad al ruido CMRR 100 dB de 48 a 62 Hz. Compatibilidad electromagnética (EMC): según EN62052-11. Descargas electrostáticas: 15kV en el aire; Inmunidad a los campos electromagnéticos radiados: prueba con intensidad aplicada: 10V/m de 80 a 2000MHz; Prueba sin intensidad aplicada: 30V/m de 80 a 2000MHz; Ráfagas en el circuito de entradas de medida de intensidad y tensión: 4kV. Inmunidad a las perturbaciones conducidas: 10V/m de 150KHz a 80MHz. Aislamiento: en los circuitos de las entradas de medida en intensidad y tensión: 4kV. Emisiones de radiofrecuencia CISPR 22. Conformidad con las normas: seguridad IEC60664, IEC61010-1 EN60664, EN61010-1 EN62052-11. Metrología EN62053-21, EN62053-23, EN504703. Salida de pulso: DIN43864, IEC62053-31. Homologaciones CE. Conexiones: a tornillo. Sección de cable: entradas de medida máx. 16 mm2; mín. 2,5 mm2 (con terminal de cable; mín. 2,5 mm2 (entradas de medida), Mín/Máx. par de apriete: 1,7 Nm / 3 Nm. Otras entradas: 1,5mm2. Par de apriete: 0,5 Nm. Caja DIN: Dimensiones 71 x 90 x 64,5 mm. Material: nylon PA66; autoextinguible: UL 94 V-0. Montaje: carril DIN. Grado de protección: panel frontal: IP50. Conexiones: IP20. Peso: aprox. 400 g (embalaje incluido). Autoalimentación: -20% +15% 48-62Hz. Autoconsumo: ≤ 20VA/1W. n CONFORMIDAD MID (sólo opción PF) Precisión: 0,9 Vn ≤ V ≤ 1,1 Vn; 0,98 fn ≤ f ≤ 1,02 fn; fn: 50 o 60Hz; cosj: de 0,5 inductiva a 0,8 capacitiva. Modelo AV9, Clase B; I st: 0,04A; I min: 0,5A; I tr: 1A; I max: 65A. Temperatura de funcionamiento: de -25°C a +55°C (de 13°F a 131°F) (H.R. de 0 a 90% sin condensación 40°C). Conformidad EMC: E2. Compatibilidad EMC: M2. *Grado de protección: Con el fin de alcanzar la protección contra polvo y agua requerida por las normas armonizadas según MID, el medidor debe instalarse sólo en armarios con protección IP51 o superior. n MODO DE MEDICIÓN (sólo opción PF) PFA: Integradas potencia positiva y negativa (no importa n MODE DE MESURE (seulement option PF) n MODO MISURA (solo versione PF) Die Schnittstellen haben keine Auswirkungen auf die PFA: La puissance est toujours intégrée (à la fois en cas polaridad del trafo, siempre mide energía positiva-genePFA: La potenza è sempre integrata (sia in caso di potenza Messungen. rada y consumida). d’alimentation positif-importéeet négatif-exportée). positiva -importata- che negativa - esportata). PFB: solo la potencia positiva es integrada. PFB: seulement la puissance positive est intégré. PFB: Solamente la potenza positiva è integrata. Las interfaces no tienen ningún efecto sobre las mediciones. Les interfaces ne ont pas d’effet sur les mesures. Le interfacce non hanno alcun effetto sulle misure CONFORMITÀ MID MID KONFORMITÄT CERTIFICATION EN CUMPLIMIENTO CON LA DIRECTIVA MID Per la misura fiscale, tutti i modelli EM23 devono essere ulteriormente certificati secondo l’Allegato II moduli “D” o “F” della direttiva MID. ATTENZIONE: per la misura fiscale, la marcatura metrologica seguita dal numero identificativo dell’ente notificato Allegato II modulo “F” o del laboratorio Allegato II modulo “F” deve essere presente sullo strumento. Lt. gesetzlichen Richtlinen des Messwesen müssen alle EM23 Modelle nach Anhang D bzw. Anhang II Module “D” oder “F” der MID-Richtlinie zertifiziert werden. ACHTUNG: aus rechtlichen Gründen muss die ordnungsgemäße Eichkennzeichnung gefolgt von der ID-Nummer, des Zertifizierers nach Anhang II Modul “F” oder jener Anhang II Modul “F” am Zähler aufgedruckt / aufgeklebt werden. Pour la métrologie légale, tous les modèles EM23 doivent, en complément, être certifiés en accord avec l’Annexe II modules “D” ou “F” de la Directive MID. ATTENTION: le logo type métrologique suivi du numéro d’identification se référant à l’Annexe II module “F” ou à l’Annexe II module “F” doit être imprimé/collé sur le compteur. Para su uso en mediciones legales, todos modelos EM23 deben estar certificados además según el Anexo II módulos “D” o “F” de la directiva MID. ¡ATENCIÓN! Por razones legales, la marca indicadora de metrología seguida del número ID en referencia a la etiqueta del Anexo II módulo “F” de la entidad notificadora o de verificación del Anexo II módulo “F” debe estar impresa/adherida en el medidor.
  • Page 1 1
  • Page 2 2

CARLO GAVAZZI EM23DINAV23XO1PFA Guía de instalación

Tipo
Guía de instalación