Installation Specications
Overcurrent Protection
Input: No internal fuses. UL Listed circuit breakers or fuses rated 3 A to 15 A,
480 V are required to be installed for input protection.
Output: Outputs are capable of providing high currents for short periods of
time for inductive load startup.
Relay
N.O. contact rated 200 mA/50 Vdc.
Connections
An accessible disconnect device shall be installed external to the equipment.
Input: Screw terminals. Connector size range: 16–10 AWG (1.5–6 mm
2
) for
solid or stranded conductors. Screw torque: 4.4-6.5 lb-inch (50-73 N-cm).
Output: Two terminals per output. Connector size range: 16–10 AWG (1.5–6
mm
2
) for solid or stranded conductors. Screw torque: 4.4-6.5 lb-inch (50-73
N-cm).
Use only one copper wire (60/70°C) per terminal.
Non-ratcheting torque driver recommended.
Safety
The power supply should meet the following conditions for safe use when
installed in a Class I, Zone 2, Groups IIC Hazardous Location:
(1) The equipment shall only be used in an area of not more than pollution
degree 2, as dened in IEC 60664-1.
(2) The equipment shall be installed in an enclosure that provides a degree
of protection not less than IP54 in accordance with IEC 60079-0.
(3) The operating temperature class (T-code) of this device was determined
to be T4.
Warning — Explosion Hazard Do not disconnect the equipment
while the circuit is live or unless the area is known to be free of ignitable
concentrations.
Warning — Explosion Hazard Do not open the unit. Do not substitute
components.
Warning — Exposure to some chemicals may degrade the sealing
properties of materials used in the sealed relay device.
The power supplies should meet the following when installed in an ordinary
locations environment: Install in a controlled environment.
DIN Rail Mounting
Simple snap to DIN TS35/7.5 or TS35/15 rail system.
1. Tilt unit as illustrated.
2. Put unit onto the DIN rail.
3. Push unit downward until it stops.
4. Push at the lower front edge to lock.
5. Gently shake the unit to ensure that it is secure.
Especicaciones de Instalación
Protección de Sobreintensidad
Entrada: No contiene fusibles internos. Para protección de entrada se
requiere instalar interruptores de circuito o fusibles certicados por UL con
valoración de 3 A a 15 A a 480 V.
Salida: Las tomas de salida son capaces de entregar corrientes elevadas
durante lapsos breves para el arranque de cargas inductivas.
Relevo
N.O. contacto valoró 200 mA/50 V CC.
Conexiones
Un dispositivo accesible de desconexión debe ser instalado externamente
al equipo.
Entrada: terminales tipo tornillo Rango de tamaños de conectores:
1,5–6 mm
2
para conductores unilares o trenzados. Torque de tornillo:
50-73 N-cm
Salida: dos terminales por salida. Rango de tamaños de conectores:
1,5–6 mm
2
para conductores unilares o trenzados. Torque de tornillo:
50-73 N-cm
Utilizar solo un cable de cobre (60/70 °C) por terminal.
Se recomienda un conductor de torque sin ajuste.
Seguridad
Las siguientes condiciones son requeridas para uso seguro de la fuente de
poder cuando la instalación es en áreas clasicadas como Clase I, Zona 2,
Grupo IIC de Ubicación Peligrosa:
(1) El equipo debe ser usado sólo en un área de no más de un grado 2 de
contaminación, tal como se dene en la norma IEC 60664-1.
(2) El equipo debe instalarse en el interior de un recinto que proporciona
un grado de protección no inferior a IP54 de acuerdo con la norma IEC
60079-0.
(3) El código de temperatura (T-code) de operación de este equipo es de
clase T4.
Advertencia Peligro de Explosión No desconecte el equipo
si el circuito está conectado, exceptuando si se sabe que no existen
concentraciones inamables en el área.
Advertencia Peligro de Explosión No abra la unidad. No substituya
componentes.
Advertencia La exposición a ciertas sustancias químicas podría
degradar las propiedades selladoras de los materiales utilizados en el relé
sellado del equipo.
Las fuentes de alimentación deben cumplir con lo siguiente cuando
se instalen en un entorno de áreas ordinarias: instalar en un entorno
controlado.
Montaje en Riel DIN
Ajuste simple según DIN TS35 / 7.5 o TS35 / 15.
1. Incline la unidad como se ilustra.
2. Póngala sobre el Riel DIN.
3. Empuje hacia abajo hasta que se detenga.
4. Empuje de la parte baja del frente para asegurar.
5. Mueva la unidad ligeramente para vericar está segura.
Technical Specications
Input
Nominal Voltage 380–480 Vac, 3Ph
Inrush Current Negligible
Power Factor (PFC) Active, > 0.92
Nominal Frequency 50/60 Hz
Output
Nominal Voltage 24 V (Adjustable from 24–28 Vdc)
Current 20 A
Power 480 W
Power Boost 1.5 x nominal current for 4 s
Hold-up Time
>20 ms (full load, 380 Vac input @ T
amb
+25°C) to
95% output voltage
Tolerance < ± 2% overall
• Line Regulation <0.5%
• Load Regulation <0.5%
• Time and Temperature Drift <1%
Initial Voltage Setting 24.5 V ± 1%
Ripple <100 mV
pp
Power Back Immunity < 35 V: no damage, auto-recovery
Parallel Operation Switch selectable
Overvoltage Protection >30.5 Vdc; auto-recovery if <33 Vdc
Environmental Data
Ambient Temperature
Storage/Shipment: -40°C to +85°C.
Operating: -40°C to +60°C at full load.
Derate 480 W by 12 W per °C to 360 W from +60°C
to +70°C.
Degree of Protection IP20 (EN60529)
Recommended Minimum
Installation Clearance
1.60 in. (40 mm) above and below; 0.59 in.
(15 mm) left and right. Do not obstruct air ow.
Unit Weight 2.86 lb. (1300 g)
Certications
UL 508/CSA C22.2 No. 107.1
UL 60950-1/CSA C22.2 60950-1
UL 60079-0, UL 60079-15,
CAN/CSA 60079-0, CAN/CSA 60079-15
Class I, Zone 2 AEx nA nC IIC T4 Gc
Class I, Zone 2 Ex nA nC IIC T4 U
IEC60950-1, EN60950-1
II 3 G Ex ec nC IIC T4 Gc, DEMKO 11ATEX1105449X
EN60079-0, EN60079-7, EN60079-15
IECEx Ex ec nC IIC T4 Gc, IECEx UL15.0017X
IEC60079-0, IEC60079-7, IEC60079-15
Emissions/Immunity
EN 61326-1; EN 55032 Class B; EN 55011 Group 1 Class B; EN 61000-3-2, EN 61000-3-3;
EN 55024; EN 61000-6-1; EN 61000-6-2; EN 61000-6-3; EN 61000-6-4; SEMI F47 Sag
Immunity
Datos Técnicos
Entrada
Voltaje Nominal 380–480 V CA, 3Ph
Arranque Despreciable
Factor de Potencia (PFC) Activo, > 0,92
Frecuencia Nominal 50/60 Hz
Salida
Voltaje Nominal 24 V (Ajustable from 24–28 V CC)
Corriente 20 A
Potencia 480 W
Elevación de Potencia 1.5 x la corriente nominal por 4 s
Tiempo de Retención
>20 ms (carga completa, entrada 380 V CA a
temperatura
ambiente
mayor a 25°C) al 95% del voltaje
de salida
Tolerancia <± 2% en conjunto
• Regulación de Línea <0.5%
• Regulación de Carga <0.5%
• Desviación de Tiempo y
Temp
<1%
Ajuste Inicial de Voltaje 24.5 V ± 1%
Rizo <100 mV
pp
Inmunidad de Potencia
Inversa
< 35 V: no implica daño, autorecuperación
Operación Paralela Interruptor seleccionable
Protección de Sobre Voltaje >30.5 V CC; recuperación automática si <33 V CC
Datos Ambientales
Temperatura Ambiente
Almacenamiento/Embarque: -40°C to +85°C
Carga nominal completa: -40°C a +60°C en carga
llena.
Reduzca la capacidad normal de 480 W por 12 W por
el °C a 360 W a partir del +60°C a +70°C.
Grado de Protección IP20 (EN60529)
Espacio Libre Mínimo
recomendado de Instalación
1.60 in. (40 mm) por encima y por debajo; 0.59 in.
(15 mm) izquierda y derecha. No obstruya ujo aéreo.
Unidad de Peso 2.86 lb. (1300 g)
Certicaciones
UL 508/CSA C22.2 No. 107.1
UL 60950-1/CSA C22.2 60950-1
UL 60079-0, UL 60079-15,
CAN/CSA 60079-0, CAN/CSA 60079-15
Clase I, Zona 2 AEx nA nC IIC T4 Gc
Clase I, Zona 2 Ex nA nC IIC T4 U
IEC60950-1, EN60950-1
II 3 G Ex ec nC IIC T4 Gc, DEMKO 11ATEX1105449X
EN60079-0, EN60079-7, EN60079-15
IECEx Ex ec nC IIC T4 Gc, IECEx UL15.0017X
IEC60079-0, IEC60079-7, IEC60079-15
Emisiones/Inmmunidad
EN 61326-1; EN 55032 Class B; EN 55011 Group 1 Class B; EN 61000-3-2,
EN 61000-3-3; EN 55024; EN 61000-6-1; EN 61000-6-2; EN 61000-6-3; EN 61000-6-4;
EMI F47 Inmmunidad a Picos
Fuentes de Poder
SDN 20-24-480CD
Manual de Instrucciones
Dimensiones
3.43 in
[87.0 mm]
5.51 in [140.0 mm]
4.85 in [123.3 mm]
4.98 in [126.6 mm]
5.3 in [134.6 mm]
S
O
L
A
Power Supply
Diagnósticos LED
LED OK
La
Perdida
de CA
CA
Baja
No CC
Alta
Carga
Sobre-
carga
Cali-
ente
Muy
Cali-
ente
Entrada Verde --- Ámbar Verde Verde Verde Verde Verde
Salida Verde --- Verde --- Ámbar Ámbar Verde ---
Alarma --- --- --- Rojo Ámbar Rojo Ámbar Ámbar
Soporte técnico
(800) 377-4384 • (847) 268-6651
www.solahd.com
Aunque se ha tomado toda precaución para asegurar precisión e integridad en
esta información, Appleton Grp LLC d/b/a Appleton Group no asume ninguna
responsabilidad y deniega toda responsabilidad por daños que resulten por el
uso de esta información o por cualquier error u omisión. Las especicaciones
están sujetas a cambios sin previo aviso.
P/N: A272-302 Rev. 1 02/2018
© 2018 Appleton Grp LLC d/b/a
Appleton Group. All rights reserved.
Power Supplies
SDN 20-24-480CD
Instruction Manual
Dimensions
3.43 in
[87.0 mm]
5.51 in [140.0 mm]
4.85 in [123.3 mm]
4.98 in [126.6 mm]
5.3 in [134.6 mm]
S
O
L
A
Power Supply
LED Diagnostics
LED OK
Loss
of AC
Low
AC
No DC
High
Load
Over-
load
Hot
Too
Hot
Input Green --- Amber Green Green Green Green Green
Output Green --- Green --- Amber Amber Green ---
Alarm --- --- --- Red Amber Red Amber Amber
Technical Support
(800) 377-4384 • (847) 268-6651
www.solahd.com
While every precaution has been taken to ensure accuracy and completeness
in this manual, Appleton Grp LLC d/b/a Appleton Group assumes no
responsibility, and disclaims all liability for damages resulting from use of this
information or for any errors or omissions. Specications are subject to change
without notice.
P/N: A272-302 Rev. 1 02/2018
© 2018 Appleton Grp LLC d/b/a
Appleton Group. All rights reserved.

Transcripción de documentos

Power Supplies SDN 20-24-480CD Instruction Manual Dimensions 5.3 in [134.6 mm] 4.85 in [123.3 mm] 5.51 in [140.0 mm] 4.98 in [126.6 mm] SOL A Power Supply Inrush Current Negligible Power Factor (PFC) Active, > 0.92 Nominal Frequency Output Nominal Voltage 50/60 Hz Current 20 A Power 480 W Power Boost 1.5 x nominal current for 4 s Hold-up Time >20 ms (full load, 380 Vac input @ Tamb +25°C) to 95% output voltage Tolerance < ± 2% overall • Line Regulation <0.5% • Load Regulation <0.5% • Time and Temperature Drift <1% Safety Initial Voltage Setting 24.5 V ± 1% Ripple <100 mVpp Power Back Immunity < 35 V: no damage, auto-recovery Parallel Operation Switch selectable Overvoltage Protection Environmental Data >30.5 Vdc; auto-recovery if <33 Vdc LED Diagnostics Degree of Protection Recommended Minimum Installation Clearance 1.60 in. (40 mm) above and below; 0.59 in. (15 mm) left and right. Do not obstruct air flow. Unit Weight Certifications 2.86 lb. (1300 g) LED OK Input Green --- Amber Green Green Green Green Green UL 508/CSA C22.2 No. 107.1 Output Green --- Green --- UL 60950-1/CSA C22.2 60950-1 Alarm --- --- Red No DC High Load Overload Hot Amber Amber Green Amber Red Too Hot 24 V (Adjustable from 24–28 Vdc) Loss of AC --- Low AC 380–480 Vac, 3Ph Storage/Shipment: -40°C to +85°C. Operating: -40°C to +60°C at full load. Derate 480 W by 12 W per °C to 360 W from +60°C to +70°C. IP20 (EN60529) Ambient Temperature 3.43 in [87.0 mm] Technical Specifications Installation Specifications Overcurrent Protection Input: No internal fuses. UL Listed circuit breakers or fuses rated 3 A to 15 A, 480 V are required to be installed for input protection. Output: Outputs are capable of providing high currents for short periods of time for inductive load startup. Relay N.O. contact rated 200 mA/50 Vdc. Connections An accessible disconnect device shall be installed external to the equipment. Input: Screw terminals. Connector size range: 16–10 AWG (1.5–6 mm2) for solid or stranded conductors. Screw torque: 4.4-6.5 lb-inch (50-73 N-cm). Output: Two terminals per output. Connector size range: 16–10 AWG (1.5–6 mm2) for solid or stranded conductors. Screw torque: 4.4-6.5 lb-inch (50-73 N-cm). Use only one copper wire (60/70°C) per terminal. Non-ratcheting torque driver recommended. Input Nominal Voltage --- II 3 G Ex ec nC IIC T4 Gc, DEMKO 11ATEX1105449X EN60079-0, EN60079-7, EN60079-15 While every precaution has been taken to ensure accuracy and completeness in this manual, Appleton Grp LLC d/b/a Appleton Group assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions. Specifications are subject to change without notice. IECEx Ex ec nC IIC T4 Gc, IECEx UL15.0017X IEC60079-0, IEC60079-7, IEC60079-15 Emissions/Immunity EN 61326-1; EN 55032 Class B; EN 55011 Group 1 Class B; EN 61000-3-2, EN 61000-3-3; EN 55024; EN 61000-6-1; EN 61000-6-2; EN 61000-6-3; EN 61000-6-4; SEMI F47 Sag Immunity P/N: A272-302 Rev. 1 02/2018 © 2018 Appleton Grp LLC d/b/a Appleton Group. All rights reserved. Datos Técnicos Entrada Fuentes de Poder Dimensiones 5.3 in [134.6 mm] 4.85 in [123.3 mm] 4.98 in [126.6 mm] 5.51 in [140.0 mm] Voltaje Nominal 380–480 V CA, 3Ph Arranque Despreciable Factor de Potencia (PFC) Activo, > 0,92 Frecuencia Nominal 50/60 Hz Salida SDN 20-24-480CD Manual de Instrucciones SOL A Power Supply 3.43 in [87.0 mm] Voltaje Nominal 24 V (Ajustable from 24–28 V CC) Corriente 20 A Potencia 480 W Elevación de Potencia 1.5 x la corriente nominal por 4 s Tiempo de Retención >20 ms (carga completa, entrada 380 V CA a temperatura ambiente mayor a 25°C) al 95% del voltaje de salida Tolerancia <± 2% en conjunto • Regulación de Línea <0.5% • Regulación de Carga • Desviación de Tiempo y Temp Ajuste Inicial de Voltaje <0.5% Las siguientes condiciones son requeridas para uso seguro de la fuente de poder cuando la instalación es en áreas clasificadas como Clase I, Zona 2, Grupo IIC de Ubicación Peligrosa: (1) El equipo debe ser usado sólo en un área de no más de un grado 2 de contaminación, tal como se define en la norma IEC 60664-1. (2) El equipo debe instalarse en el interior de un recinto que proporciona un grado de protección no inferior a IP54 de acuerdo con la norma IEC 60079-0. (3) El código de temperatura (T-code) de operación de este equipo es de clase T4. Advertencia — Peligro de Explosión — No desconecte el equipo si el circuito está conectado, exceptuando si se sabe que no existen concentraciones inflamables en el área. Advertencia — Peligro de Explosión — No abra la unidad. No substituya componentes. Advertencia — La exposición a ciertas sustancias químicas podría degradar las propiedades selladoras de los materiales utilizados en el relé sellado del equipo. Protección de Sobre Voltaje Datos Ambientales >30.5 V CC; recuperación automática si <33 V CC < 35 V: no implica daño, autorecuperación Interruptor seleccionable Temperatura Ambiente Almacenamiento/Embarque: -40°C to +85°C Carga nominal completa: -40°C a +60°C en carga llena. Reduzca la capacidad normal de 480 W por 12 W por el °C a 360 W a partir del +60°C a +70°C. CA Baja Alta Carga Sobrecarga Caliente Muy Caliente Grado de Protección IP20 (EN60529) No CC Espacio Libre Mínimo recomendado de Instalación 1.60 in. (40 mm) por encima y por debajo; 0.59 in. (15 mm) izquierda y derecha. No obstruya flujo aéreo. Entrada Verde --- Ámbar Verde Verde Verde Verde Verde Unidad de Peso 2.86 lb. (1300 g) Salida Verde --- Verde --- Ámbar Ámbar Verde --- Alarma --- --- --- Rojo Ámbar Ámbar Ámbar Certificaciones UL 508/CSA C22.2 No. 107.1 UL 60950-1/CSA C22.2 60950-1 UL 60079-0, UL 60079-15, CAN/CSA 60079-0, CAN/CSA 60079-15 Clase I, Zona 2 AEx nA nC IIC T4 Gc Clase I, Zona 2 Ex nA nC IIC T4 U (800) 377-4384 • (847) 268-6651 [email protected] www.solahd.com Aunque se ha tomado toda precaución para asegurar precisión e integridad en esta información, Appleton Grp LLC d/b/a Appleton Group no asume ninguna responsabilidad y deniega toda responsabilidad por daños que resulten por el uso de esta información o por cualquier error u omisión. Las especificaciones están sujetas a cambios sin previo aviso. Especificaciones de Instalación Protección de Sobreintensidad Entrada: No contiene fusibles internos. Para protección de entrada se requiere instalar interruptores de circuito o fusibles certificados por UL con valoración de 3 A a 15 A a 480 V. Salida: Las tomas de salida son capaces de entregar corrientes elevadas durante lapsos breves para el arranque de cargas inductivas. Relevo N.O. contacto valoró 200 mA/50 V CC. Conexiones Un dispositivo accesible de desconexión debe ser instalado externamente al equipo. Entrada: terminales tipo tornillo Rango de tamaños de conectores: 1,5–6 mm2 para conductores unifilares o trenzados. Torque de tornillo: 50-73 N-cm Salida: dos terminales por salida. Rango de tamaños de conectores: 1,5–6 mm2 para conductores unifilares o trenzados. Torque de tornillo: 50-73 N-cm Utilizar solo un cable de cobre (60/70 °C) por terminal. Se recomienda un conductor de torque sin ajuste. Seguridad <100 mVpp Soporte técnico Tilt unit as illustrated. Put unit onto the DIN rail. Push unit downward until it stops. Push at the lower front edge to lock. Gently shake the unit to ensure that it is secure. 24.5 V ± 1% La Perdida de CA Rojo 1. 2. 3. 4. 5. <1% Rizo Inmunidad de Potencia Inversa Operación Paralela Diagnósticos LED Las fuentes de alimentación deben cumplir con lo siguiente cuando se instalen en un entorno de áreas ordinarias: instalar en un entorno controlado. Montaje en Riel DIN Ajuste simple según DIN TS35 / 7.5 o TS35 / 15. IEC60950-1, EN60950-1 II 3 G Ex ec nC IIC T4 Gc, DEMKO 11ATEX1105449X EN60079-0, EN60079-7, EN60079-15 IECEx Ex ec nC IIC T4 Gc, IECEx UL15.0017X IEC60079-0, IEC60079-7, IEC60079-15 Emisiones/Inmmunidad EN 61326-1; EN 55032 Class B; EN 55011 Group 1 Class B; EN 61000-3-2, EN 61000-3-3; EN 55024; EN 61000-6-1; EN 61000-6-2; EN 61000-6-3; EN 61000-6-4; EMI F47 Inmmunidad a Picos P/N: A272-302 Rev. 1 02/2018 © 2018 Appleton Grp LLC d/b/a Appleton Group. All rights reserved. DIN Rail Mounting Simple snap to DIN TS35/7.5 or TS35/15 rail system. IEC60950-1, EN60950-1 (800) 377-4384 • (847) 268-6651 [email protected] www.solahd.com OK The power supplies should meet the following when installed in an ordinary locations environment: Install in a controlled environment. UL 60079-0, UL 60079-15, CAN/CSA 60079-0, CAN/CSA 60079-15 Class I, Zone 2 AEx nA nC IIC T4 Gc Class I, Zone 2 Ex nA nC IIC T4 U Amber Amber Technical Support LED The power supply should meet the following conditions for safe use when installed in a Class I, Zone 2, Groups IIC Hazardous Location: (1) The equipment shall only be used in an area of not more than pollution degree 2, as defined in IEC 60664-1. (2) The equipment shall be installed in an enclosure that provides a degree of protection not less than IP54 in accordance with IEC 60079-0. (3) The operating temperature class (T-code) of this device was determined to be T4. Warning — Explosion Hazard — Do not disconnect the equipment while the circuit is live or unless the area is known to be free of ignitable concentrations. Warning — Explosion Hazard — Do not open the unit. Do not substitute components. Warning — Exposure to some chemicals may degrade the sealing properties of materials used in the sealed relay device. 1. 2. 3. 4. 5. Incline la unidad como se ilustra. Póngala sobre el Riel DIN. Empuje hacia abajo hasta que se detenga. Empuje de la parte baja del frente para asegurar. Mueva la unidad ligeramente para verificar está segura.
  • Page 1 1
  • Page 2 2

Emerson SDN 20-24-480CD El manual del propietario

Tipo
El manual del propietario