NSi Industries, LLC
TORK INSTRUCTION MANUAL
p/n 1104 (LI-564(E))
ENGLISH
3.5” x 7.5”
1/0 (BLACK)
We recommend that installation be made by a licensed electrician.
Disconnect power at main panel prior to installing or servicing this time
switch or the equipment connected to it.
Connect in accordance with national and local electrical codes.
Supply Connections: Use gauge specified (AWG # 8-14) suitable for 75˚C (167˚F).
Replace insulator before turning on electricity to unit.
1104 208-277VAC/60Hz
INSTALLATION AND OPERATING INSTRUCTIONS
TO SET ON AND OFF TIMES:
Light trippers turn ON. Dark trippers turn OFF. Place
tripper on dial edge as shown in figure and set point
of each tripper to desired operating time. Note if
selected time is AM or PM. Hold tripper against dial
edge and firmly tighten knurled screw.
1104• 24 HOUR TIME SWITCH
SWITCH: DPST
CONTACT RATINGS: 40 AMP 120-277VAC
40 AMP TUNGSTEN 120VAC
20 AMP INDUCTIVE
TIMING MOTOR: 208-277VAC 60Hz
POWER CONSUMPTION: 3 WATTS MAX
1000VA (120-277) PILOT DUTY
120-277VAC SINGLE PHASE
2HP 120VAC; 5HP 240VAC
LR21743
INSTALLATION AND OPERATING INSTRUCTIONS
TO SET DIAL TO TIME:
Turn dial counter-clockwise until correct time is indicated by arrow on nameplate.
FOR TEMPORARY MANUAL OVERRIDE:
Press down lever on right of nameplate to turn ON. Press down lever on left of nameplate to turn
OFF. CAUTION: Do not rotate dial for manual override.
TO REMOVE MECHANISM FROM CASE:
Press lever near case latch to release mainplate and swing the movement out. To replace, insert
mainplate projections in slots opposite latch and swing movement in until it latches.
LI-564(E)
TORK, INC • 888.500.4598 • www.nsiindustries.com
A DIVISION OF NSi INDUSTRIES, LLC
1104 • MINUTERIE SUR 24 HEURES
INTERRUPTEUR : I.B.
CAPACITÉ DES CONTACTS :
40 A 120-277 V CA
40 A TUNGSTÈNE 120 V CA
20 A INDUCTIF
MOTEUR DE MINUTAGE : 208-277 V CA 60 Hz
CONSOMMATION : 3 WATTS MAX
1000 VA (120-277)
RÉGIME DE
FONCTIONNEMENT ASSERVI
120-277 V CA MONOPHASÉ
2 HP 120 V CA; 5 HP 240 V CA
INSTRUCTIONS POUR L’INSTALLATION ET L’UTILISATION
RÉGLAGE DU CADRAN :
Tournez le cadran dans le sens antihoraire jusqu’à ce que l’aiguille de la plaque
signalétique pointe la bonne heure.
INTERRUPTION MANUELLE :
Abaissez le levier situé à droite de la plaque signalétique pour mettre la minuterie en marche (ON).
Abaissez le levier situé à gauche de la plaque signalétique pour arrêter la minuterie (OFF).
MISE EN GARDE : Ne tournez pas le cadran pour interrompre manuellement la minuterie.
RETRAIT DU MÉCANISME :
Appuyez sur le levier situé prêt du loquet du boîtier pour détacher le platine et retirez le mouvement
en le tournant. Pour replacer le mécanisme, insérez les supports de platine dans les fentes situées en
face du loquet et faites pivoter le mouvement pour l’enclencher.
INSTRUCCIONES DE INSTALACIÓN Y FUNCIONAMIENTO
PARA AJUSTAR LA PERILLA AL TIEMPO:
Gire la perilla en dirección contraria a las manecillas del reloj hasta que la flecha
indique la hora correcta en la placa de datos.
PARA ANULAR TEMPORALMENTE EL PROGRAMA:
Presione la palanca hacia abajo en la parte derecha de la placa de datos para ENCENDERLA.
Presione la palanca hacia abajo en la parte izquierda de la placa de datos para APAGARLA.
PRECAUCIÓN: No gire la perilla para una anulación manual.
PARA RETIRAR EL MECANISMO DEL ESTUCHE:
Presione la palanca cerca del pestillo del estuche para liberar la placa principal y haga que
oscile hacia fuera. Para reemplazarlo, inserte las proyecciones de la placa principal en el pestillo
opuesto de las ranuras y haga que oscile hacia adentro hasta que se enganche.
1104• INTERRUPTOR DE TIEMPO DE 24 HRS
INTERRUPTOR: TIPO UNIPOLAR Y BIDIRECCIONAL (DPST)
CLASIFICACIONES DEL CONTACTO:
40 A 120-277 V CA
40 A TUNGSTENO 120 V CA
20 A INDUCTIVO
MOTOR DEL TEMPORIZADOR:
208-277 V CA 60 Hz
CONSUMO DE ENERGÍA: 3 VATIOS MÁX.
1000 VA (120-277)
CAPACIDAD
DETERMINADA EXPERIMENTALMENTE
120-277 V CA FASE ÚNICA
2 HP 120 V CA; 5 HP 240 V CA
1104 208-277 V CA 60 Hz
INSTRUCTIONS POUR L’INSTALLATION ET L’UTILISATION
Nous recommandons de confier l’installation à un électricien qualifié. Coupez le courant
à partir du tableau de distribution principal avant d’installer ou de réparer cette
minuterie ou tout équipement y étant branché. Effectuez les branchements conformé-
ment aux codes de l’électricité en vigueur dans votre pays et votre région. Connecteurs
d’alimentation: Utilisez des fils correspondant au calibre indiqué (8 à 14 AWG) et pouvant
résister à une température de 75 °C. Replacez l’isolant avant d’alimenter l’appareil.
RÉGLAGE DES HEURES DE MARCHE ET D’ARRÊT :
Les déclencheurs de MARCHE sont pâles. Les déclench-
eurs d’ARRÊT sont foncés. Placez les déclencheurs sur le
bord du cadran, tel qu’il est illustré, pour qu’ils pointent
vers l’heure voulue. Assurez-vous de bien choisir AM ou
PM. Maintenez le déclencheur contre le bord du cadran
et serrez fermement la vis à tête moletée.
Heure d’arrêt
(Onglet foncé)
Levier manuel
ARRÊT
Vis moletée
Calibrage de cadran
Heure de mise
en marche
(déclencheur pâle)
Levier manuel
EN MARCHE
1104 208-277 V CA y 60 Hz
INSTRUCCIONES DE INSTALACIÓN Y FUNCIONAMIENTO
Se recomienda que la instalación sea realizada por un electricista calificado. Desconecte la
alimentación en el panel principal antes de instalar este interruptor de tiempo o el
equipo conectado a éste o para realizarle mantenimiento.
Conecte de acuerdo con los
códigos eléctricos locales y nacionales. Conexiones de suministro: Use el calibre especificado
(AWG # 8-14) adecuado para 75 grados C (167 grados F). Reemplace el aislador antes de
encender la unidad.
PARA AJUSTAR LAS HORAS DE ENCENDIDO Y APAGADO:
Los interruptores claros son de ENCENDIDO. Los interrup-
tores oscuros son de APAGADO. Ubique el interruptor en el
borde de la perilla como se muestra en la figura y ajuste
la punta de cada interruptor en la hora de funcionamiento
deseada. Verifique si la hora seleccionada es AM o PM.
Sostenga el interruptor contra el borde de la perilla y
ajuste firmemente el tornillo de cabeza moleteada.
APAGAR
(Disparador
Negro)
Palanca Manual
APAGAR
Tornillo
Calibracion de disco
ENCENDER
(Disparador
Blanco)
Palanca Manual
ENCENDER
NSi Industries, LLC
TORK INSTRUCTION MANUAL
p/n 1104 (LI-564(E))
FRENCH
3.5” x 6.0”
1/0 (BLACK)
NSi Industries, LLC
TORK INSTRUCTION MANUAL
p/n 1104 (LI-564(E))
SPANISH
3.5” x 6.0”
1/0 (BLACK)
NSi Industries, LLC
TORK INSTRUCTION MANUAL
p/n 1104 (LI-564(E))
1/0 (BLACK)
CHARGE CHARGE
CHARGE
TYPIQUE POUR ALIMENTATION DE 240V
TYPIQUE POUR ALIMENTATION
DE 240V
DOÎT ÊTRE
MONOPHASE
Typique pour systeme bipolar–
interruption du fil du motor en 1
Conexion tipica para 240V~ Conexion tipica para 220V~
Debe ser la
misma fase
L
M
L
1
X
2
L
CARGA
CARGA CARGA
L
M
L
1
X
2
L
N
N
H
H
H
H

Transcripción de documentos

LR21743 1104• 24 HOUR TIME SWITCH SWITCH: CONTACT RATINGS: DPST 40 AMP 120-277VAC 1000VA (120-277) PILOT DUTY 40 AMP TUNGSTEN 120VAC 120-277VAC SINGLE PHASE 20 AMP INDUCTIVE 2HP 120VAC; 5HP 240VAC TIMING MOTOR: 208-277VAC 60Hz POWER CONSUMPTION: 3 WATTS MAX MUST BE SAME PHASE LOAD 1104 • MINUTERIE SUR 24 HEURES 1104• INTERRUPTOR DE TIEMPO DE 24 HRS INTERRUPTEUR : I.B. CAPACITÉ DES CONTACTS : 40 A 120-277 V CA 1000 VA (120-277) RÉGIME DE 40 A TUNGSTÈNE 120 V CA FONCTIONNEMENT ASSERVI 120-277 V CA MONOPHASÉ 20 A INDUCTIF 2 HP 120 V CA; 5 HP 240 V CA MOTEUR DE MINUTAGE : 208-277 V CA 60 Hz CONSOMMATION : 3 WATTS MAX INTERRUPTOR: TIPO UNIPOLAR Y BIDIRECCIONAL (DPST) CLASIFICACIONES DEL CONTACTO: 1000 VA (120-277) CAPACIDAD 40 A 120-277 V CA 40 A TUNGSTENO 120 V CA DETERMINADA EXPERIMENTALMENTE 120-277 V CA FASE ÚNICA 20 A INDUCTIVO 2 HP 120 V CA; 5 HP 240 V CA MOTOR DEL TEMPORIZADOR: 208-277 V CA 60 Hz CONSUMO DE ENERGÍA: 3 VATIOS MÁX. LOAD DOÎT ÊTRE MONOPHASE TYPICAL FOR 277V SUPPLY Typical for double pole Cut motor lead at 1 LOAD CHARGE TYPICAL FOR 240V SUPPLY 1104 CHARGE 208-277VAC/60Hz INSTALLATION AND OPERATING INSTRUCTIONS TO SET ON AND OFF TIMES: Light trippers turn ON. Dark trippers turn OFF. Place tripper on dial edge as shown in figure and set point of each tripper to desired operating time. Note if selected time is AM or PM. Hold tripper against dial edge and firmly tighten knurled screw. TYPIQUE POUR ALIMENTATION Typique pour systeme bipolar– DE 240V interruption du fil du motor en 1 1104 208-277 V CA 60 Hz Nous recommandons de confier l’installation à un électricien qualifié. Coupez le courant à partir du tableau de distribution principal avant d’installer ou de réparer cette minuterie ou tout équipement y étant branché. Effectuez les branchements conformément aux codes de l’électricité en vigueur dans votre pays et votre région. Connecteurs d’alimentation: Utilisez des fils correspondant au calibre indiqué (8 à 14 AWG) et pouvant résister à une température de 75 °C. Replacez l’isolant avant d’alimenter l’appareil. INSTRUCTIONS POUR L’INSTALLATION ET L’UTILISATION INSTALLATION AND OPERATING INSTRUCTIONS TO SET DIAL TO TIME: Turn dial counter-clockwise until correct time is indicated by arrow on nameplate. FOR TEMPORARY MANUAL OVERRIDE: Press down lever on right of nameplate to turn ON. Press down lever on left of nameplate to turn OFF. CAUTION: Do not rotate dial for manual override. TO REMOVE MECHANISM FROM CASE: Press lever near case latch to release mainplate and swing the movement out. To replace, insert mainplate projections in slots opposite latch and swing movement in until it latches. LI-564(E) CHARGE TYPIQUE POUR ALIMENTATION DE 240V We recommend that installation be made by a licensed electrician. Disconnect power at main panel prior to installing or servicing this time switch or the equipment connected to it. Connect in accordance with national and local electrical codes. Supply Connections: Use gauge specified (AWG # 8-14) suitable for 75˚C (167˚F). Replace insulator before turning on electricity to unit. A DIVISION OF NSi INDUSTRIES, LLC TORK, INC • 888.500.4598 • www.nsiindustries.com RÉGLAGE DES HEURES DE MARCHE ET D’ARRÊT : Les déclencheurs de MARCHE sont pâles. Les déclencheurs d’ARRÊT sont foncés. Placez les déclencheurs sur le bord du cadran, tel qu’il est illustré, pour qu’ils pointent vers l’heure voulue. Assurez-vous de bien choisir AM ou PM. Maintenez le déclencheur contre le bord du cadran et serrez fermement la vis à tête moletée. Calibrage de cadran Heure d’arrêt (Onglet foncé) M M Vis moletée Levier manuel ARRÊT Heure de mise en marche (déclencheur pâle) Levier manuel EN MARCHE L 1 HL HL 1104 Debe ser la misma fase HL 2 X CARGA Conexion tipica para 240V~ L 1 HL X 2 CARGA CARGA NN Conexion tipica para 220V~ 208-277 V CA y 60 Hz Se recomienda que la instalación sea realizada por un electricista calificado. Desconecte la alimentación en el panel principal antes de instalar este interruptor de tiempo o el equipo conectado a éste o para realizarle mantenimiento. Conecte de acuerdo con los códigos eléctricos locales y nacionales. Conexiones de suministro: Use el calibre especificado (AWG # 8-14) adecuado para 75 grados C (167 grados F). Reemplace el aislador antes de encender la unidad. INSTRUCCIONES DE INSTALACIÓN Y FUNCIONAMIENTO PARA AJUSTAR LAS HORAS DE ENCENDIDO Y APAGADO: Los interruptores claros son de ENCENDIDO. Los interruptores oscuros son de APAGADO. Ubique el interruptor en el borde de la perilla como se muestra en la figura y ajuste la punta de cada interruptor en la hora de funcionamiento deseada. Verifique si la hora seleccionada es AM o PM. Sostenga el interruptor contra el borde de la perilla y ajuste firmemente el tornillo de cabeza moleteada. Calibracion de disco Tornillo APAGAR (Disparador Negro) Palanca Manual APAGAR ENCENDER (Disparador Blanco) Palanca Manual ENCENDER INSTRUCTIONS POUR L’INSTALLATION ET L’UTILISATION INSTRUCCIONES DE INSTALACIÓN Y FUNCIONAMIENTO RÉGLAGE DU CADRAN : Tournez le cadran dans le sens antihoraire jusqu’à ce que l’aiguille de la plaque signalétique pointe la bonne heure. INTERRUPTION MANUELLE : Abaissez le levier situé à droite de la plaque signalétique pour mettre la minuterie en marche (ON). Abaissez le levier situé à gauche de la plaque signalétique pour arrêter la minuterie (OFF). MISE EN GARDE : Ne tournez pas le cadran pour interrompre manuellement la minuterie. RETRAIT DU MÉCANISME : Appuyez sur le levier situé prêt du loquet du boîtier pour détacher le platine et retirez le mouvement en le tournant. Pour replacer le mécanisme, insérez les supports de platine dans les fentes situées en face du loquet et faites pivoter le mouvement pour l’enclencher. PARA AJUSTAR LA PERILLA AL TIEMPO: Gire la perilla en dirección contraria a las manecillas del reloj hasta que la flecha indique la hora correcta en la placa de datos. PARA ANULAR TEMPORALMENTE EL PROGRAMA: Presione la palanca hacia abajo en la parte derecha de la placa de datos para ENCENDERLA. Presione la palanca hacia abajo en la parte izquierda de la placa de datos para APAGARLA. PRECAUCIÓN: No gire la perilla para una anulación manual. PARA RETIRAR EL MECANISMO DEL ESTUCHE: Presione la palanca cerca del pestillo del estuche para liberar la placa principal y haga que oscile hacia fuera. Para reemplazarlo, inserte las proyecciones de la placa principal en el pestillo opuesto de las ranuras y haga que oscile hacia adentro hasta que se enganche. NSi Industries, LLC TORK INSTRUCTION MANUAL p/n 1104 (LI-564(E)) FRENCH 3.5” x 6.0” 1/0 (BLACK) NSi Industries, LLC TORK INSTRUCTION MANUAL p/n 1104 (LI-564(E)) SPANISH 3.5” x 6.0” 1/0 (BLACK) NSi Industries, LLC TORK INSTRUCTION MANUAL p/n 1104 (LI-564(E)) ENGLISH 3.5” x 7.5” 1/0 (BLACK) NSi Industries, LLC TORK INSTRUCTION MANUAL p/n 1104 (LI-564(E)) 1/0 (BLACK)
  • Page 1 1