These notification appliances can be installed in systems using
12 or 24V using DC or full-wave rectified (FWR) power supplies.
The indoor model 914 has an operating temperature range
of 32ºF to 120ºF (0ºC to 49ºC). Model 914W meets NEMA 3R
requirements with an operating temperature of -40ºF to 151ºF
(-40ºC to 66ºC). They are not suitable for ceiling mounting.
Fire Alarm System Considerations
The National Fire Alarm Code, NFPA 72, requires that all horns,
used for building evacuation produce temporal coded signals.
Signals other than those used for evacuation purposes do not
have to produce the Temporal Coded Signal. Temporal coding
is accomplished by interrupting a steady sound in the following
manner:
1/2 sec ON; 1/2 sec OFF; 1/2 sec ON; 1/2 sec OFF, etc. (repeatedly)
Horn Selection
Turn the rotary switch on the back of the product to the desired
setting. The current draw for each setting is listed in Table 1.
The sound output measurement for each horn setting is shown
in Table 2.
WARNING: The horn will not work without power. The horn
may not be heard. The loudness of the horn meets (or exceeds)
current Underwriters Laboratories’ standards. However, the
sounder may not alert a sound sleeper or one who has recently
taken medication/drugs or alcoholic beverages. The sounder may
not be heard if it is located on a different building level from the
person in hazard or if it is placed too far away to be heard over
ambient noise (i.e. traffic, air conditions, machinery or music
appliances). The sounder may also not be heard by persons who
are hearing impaired.
AVERTISSEMENT: L’avertisseur sonore ne fonctionnera pas
sans courant. L’avertisseur sonore pourrait ne pas être entendu.
L’intensité de l’avertisseur sonore rencontre (ou dépasse) les
critères actuels d’Underwriters Laboratories. Cependant, le
bruit pourrait ne pas alerter certaines personnes dormant
profondément ou quelqu’un ayant récemment consommé des
médicaments, de la drogue ou de l’alcool. Le bruit peut ne pas
être entendu s’il provient d‘un autre étage de l’établissement
que celui où se trouve la personne en danger, ou s’il est situé
trop loin pour se distinguer de bruit ambiant (c.-à-d.,circulation,
conditions de l’air, machinerie ou appareils de musique). Le bruit
peut également ne pas être entendu pas les malentendants.
ADVERTENCIA: La bocina no funcionará sin electricidad. Puede
ser que no se escuche. El volumen de la bocina cumple (o
excede) con las normas de Underwriters Laboratories. Sin
embargo, es posible que la sirena no alerte a una persona que
tenga el sueño muy profundo o que haya tomado recientemente
medicamentos/estupefacientes o bebidas alcohólicas. También
es posible que no se escuche la sirena si se localiza en un nivel
del edificio distinto al que se encuentra la persona en peligro o
si se coloca demasiado lejos para ser escuchada por encima del
ruido ambiental (es decir, tráfico, aire acondicionado, maquinaria
o aparatos de música). Asimismo, es posible que las personas
con problemas de audición no la oigan.
Installation Instructions
Table 1 - Horn Current Draw
Pos
Sound
Pattern
Sound
Level
8–17.5
Volts (mA)
16–33
Volts (mA)
1
Temporal
High 57 69
2 Medium 44 58
3 Low 38 44
4
Non-
temporal
High 57 69
5 Medium 42 60
6 Low 41 50
7
Coded
High 57 69
8 Medium 44 56
9 Low 40 52
NOTE: In positions 7, 8 and 9, temporal coding must be
provided by the NAC (Notification Appliance Circuit).
If the NAC voltage is held constant, the horn output will remain
constantly on.
When connected to an BEA 10MAGDE1 Delayed Egress electro-
magnetic lock, set Audio Select Dial to Sound Pattern 7, 8 or 9
only.
914 Sounder Installation Instructions (Continued)
Mounting Indoor Wall Model 914
1. Attach mounting plate to junction box. Compatible with 4”
square, single gang, double gang, and 4” octagon junction
boxes.
2. Connect field wiring to terminals, per mounting bracket
label.
3. Hook tabs on the product housing into the grooves on
mounting plate.
4. Swing product into position to fully engage the pins on the
product with the terminals on the mounting plate.
5. Secure product by tightening the single mounting screw.
For tamper resistance use the enclosed Torx screw.
Model 914W
1. This outdoor sounder must be installed using the proper
weatherproof back box (SA-WBB). Do not attempt to use
boxes other than the ones supplied.
2. The wall mount box internal post must be in the lower left
corner.
3. Two threaded holes are provided in the sides of the box for
3/4 inch conduit adapters. Knockout plugs in the back of the
box can be used for 1/2 or 3/4 inch rear entry. Unused holes
must be sealed. Plugs are provided.
4. It is the responsibility of the installer to make sure that all
openings and connections are sealed properly.
5. Water may pool on the back box due to condensation or
direct exposure to rain or snow. Use watertight fittings for all
wiring connections. With plastic plugs, apply teflon tape and/
or silicone sealant to reduce the chance of leakage.
6. Follow steps 2 – 6 of the indoor mounting
Table 2 - Horn Output (dBA) in UL Reverberant Room:
* Minimum dB rating for Operational Voltage Range as per UL 464.
Figure 9. Wall Mount Weatherproof backbox:
Wall Mount Weatherproof Backbox:
Proper Orientation
Internal Post must be lower left
BEA Inc. RIDC Park West 100 Enterprise Drive Pittsburgh, PA 15275
Phone: 412.249.4100 | Fax: 888.523.2462
Switch Position Sound Pattern Sound Level
8–17.5 Volts*
(dB)
16–33 Volts*
(dB)
24 V Nominal Measurements (dB)
Reverberant Anechoic
1
Temporal
High 78 84 88 99
2 Medium 74 80 86 96
3 Low 71 76 83 94
4
Non-temporal
High 82 88 93 100
5 Medium 78 85 90 98
6 Low 75 81 88 96
7
Coded
High 82 88 93 101
8 Medium 78 85 90 97
9 Low 75 81 88 96
  • Page 1 1
  • Page 2 2

BEA DELAYED EGRESS MAGLOCK KIT Guía del usuario

Tipo
Guía del usuario

en otros idiomas