Pass and Seymour TR20USBAC6W Guía de instalación

Tipo
Guía de instalación

Este manual también es adecuado para

No: 341227 – 09/18
Catalog Number(s) • Numéro(s) de Catalogue • Les Numéros de Catalogue: R26USBAC6, TR15USBAC6, TR20USBAC6,
TR15HUSBAC6 and TR20HUSBAC6
Country of Origin: Made in China • Pays d’origine: Fabriqué en Chine • País de origen: Hecho en China
800.223.4185
1.877.BY.LEGRAND
www.legrand.us
www.legrand.ca
341227 – 09/18
© Copyright 2018 Legrand All Rights Reserved.
© Copyright 2018 Tous droits réservés Legrand.
© Copyright 2018 Legrand Todos los derechos reservados.
radiant® and Pass & Seymour Spec Grade & Hospital Grade Duplex USB-A + USB-C
Charger 6A
Chargeur USB-A + USB-C radiant® Duplex et Qualité de Spécication et por Hôpital 6 A
Cargador USB-A + USB-C dúplex de radiant® y Grado de especicación y para hospitales 6A
Installation Instructions • Notice d’Installation • Instrucciones de Instalación
READ & SAVE THESE INSTRUCTIONS!
CAUTION:
To prevent severe shock or electrocution, always
turn power OFF at the service panel before
working with wiring.
Use this device with copper or copper-clad wire.
Do not use with aluminum wire.
Must be installed in accordance with National and
Local electrical codes.
All cables should be routed away from the outlet
openings.
Outlets are not intended to support devices or
appliances. Do not hang devices by charging cord.
WARNING: IMPROPER WIRING OF ANY
ELECTRICAL DEVICE CAN CAUSE SERIOUS
INJURY OR DEATH. THESE WIRING DEVICES
SHOULD BE INSTALLED BY AN ELECTRICIAN OR
OTHER QUALIFIED PERSON.
LIRE ET CONSERVER CES INSTRUCTIONS.
ATTENTION :
Pour éviter tout choc électrique ou une
électrocution, coupez toujours l’électricité au
niveau du panneau d’alimentation avant de
commencer à câbler.
Utilisez ce dispositif avec des fils en cuivre
ou cuivrés. Ne l’utilisez pas avec des fils en
aluminium.
Doit être installé conformément aux codes locaux
et nationaux de l’électricité.
Tous les câbles doivent être acheminés loin de
l’orifice de sortie.
Les sorties ne sont pas conçues pour le support
de dispositifs ou d’appareils électroménagers.
Ne pas suspendre les appareils par le cordon de
chargement.
AVERTISSEMENT : LE CÂBLAGE INCORRECT DE
TOUT DISPOSITIF ÉLECTRIQUE PEUT CAUSER
DES BLESSURES GRAVES, VOIRE LA MORT.
CES DISPOSITIFS DE CÂBLAGE DOIVENT ÉTRE
INSTALLÉS PAR UN ÉLECTRICIEN OU UNE
PERSONNE QUALIFIÉE.
LEA Y GUARDE ESTAS INSTRUCCIONES.
PRECAUCIÓN:
Para evitar serios electrochoques o electrocución,
siempre APAGUE el suministro eléctrico en el
panel de servicio antes de trabajar con los cables.
Utilice este dispositivo con alambres de cobre
o revestidos de cobre. No usar con cables de
aluminio.
Se debe instalar de acuerdo con los códigos
eléctricos nacionales y locales.
Todos los cables deben ser alejados de la
abertura de la salida.
Las salidas no tienen el objeto de admitir
dispositivos o electrodomésticos. No use el cable
de carga para colgar los dispositivos.
ADVERTENCIA: EL CABLEADO INCORRECTO DE
UN DISPOSITIVO ELÉCTRICO PUEDE CAUSAR
LESIONES GRAVES O AÚN LA MUERTE. UN
ELECTRICISTA U OTRA PERSONA COMPETENTE
DEBE INSTALAR ESTOS DISPOSITIVOS DE
CABLEADO.
DESCRIPTION: This device is a Combination Duplex Receptacle and USB-A + USB-C Charger.
The USB ports provide 6A total DC power at 5 volts for charging USB devices. USB ports are for
charging purposes only and are not intended for data transfer.
DIRECTIONS:
1. Disconnect power to circuit by removing
fuse or turn circuit breakers OFF before
installing. Before wiring verify that power
has been removed by testing with a circuit
tester at the outlet box.
2. To replace existing device, remove wall
plate and pull device from box.
If new installation, skip to step 5.
3. Label wires connected to existing device.
4. Disconnect existing device.
5. Strip wires to length of 12" using stripping
guide on back of device. Use #10 - #14
AWG solid or stranded wire.
6. Install device per corresponding wiring
diagram. See Figure 1.
7. Torque terminal screws to 12-14
inch-pounds.
8. Mount the device to the wall box.
9. Attach wall plate, then restore power
to circuit. Figure 1/Illustration 1/Figura 1
INSTRUCCIONES EN ESPAÑOL
DESCRIPTION : Ce dispositif est un chargeur USB-A + USB-C Duplex.
Les ports USB fournissent un courant total en c.c. de 6 A à 5 V aux
dispositifs de chargement USB. Les ports USB sont destinés aux besoins
de recharge et ne sont pas conçus pour le transfert de données.
INSTRUCTIONS :
1. Coupez l’alimentation du circuit en retirant le fusible ou en ouvrant les
disjoncteurs (OFF/ARRÊT) avant de commencer l’installation. Avant
de commencer le cablage, vérifier que l’alimentation a été coupée en
testant les fils avec un contrôleur au niveau de la boîte murale.
2. Pour remplacer un dispositif existant, retirez la plaque murale, puis
retirez le dispositif de la boîte. S’il s’agit d’une nouvelle installation,
passez à l’étape 5.
3. Étiquetez les fils reliés au dispositif actuel.
4. Déconnectez le dispositif actuel.
5. Dénudez les fils sur 12 mm (0,5 po) en utilisant le guide de
dépouillement dessus en arrière du dispositif. Utilisez un fil plein ou
multibrins avec un AWG n° 10 - 14.
6. Installez le dispositif comme montré au schéma de principe de
l’illustration 1.
7. Les vis des bornes doivent être serrées à un couple de 12 à 14 in-Lb.
8. Montez le dispositif à la boite murale.
9. Remontez la plaque murale, puis remettez le circuit sous tension.
DESCRIPCIÓN: Este dispositivo es un cargador USB-A + USB-C dúplex.
Los puertos USB proveen una fuente de alimentación de corriente
continua total de 6A a 5 voltios para cargar dispositivos USB. Los puertos
USB sirven solamente para cargar y no tienen el objeto de transferir datos.
INSTRUCCIONES:
1. Desconecte el suministro eléctrico al circuito retirando el fusible o
apagando los cortacircuitos antes de instalar. Antes de comenzar con
el cableado, utilice un probador de circuitos en la caja de salida para
verificar que el suministro esté desconectado.
2. Para reemplazar un dispositivo existente, retire la placa de pared y
saque el dispositivo de la caja. Si es una instalación nueva, pase al
paso 5.
3. Marque los cables conectados al dispositivo existente.
4. Desconecte el dispositivo existente.
5. Desforre los cables a una longitud de 1/2 pulg. usando guía de
desmontaje encendido detrás del dispositivo. Utilice cable calibre 10/14
AWG sólido o trenzado.
6. Instale el dispositivo según el diagrama de cableado. Figura 1.
7. Ajuste los tornillos del terminal un par de torsión de 12 a 14 pulg.-lb.
8. Monte el dispositivo en la caja de pared.
9. Instale la placa de pared, luego restaure el suministro eléctrico
al circuito.
INSTRUCTIONS EN FRANÇAIS
  • Page 1 1

Pass and Seymour TR20USBAC6W Guía de instalación

Tipo
Guía de instalación