Simplicity 076155-01 Manual de usuario

Categoría
Generadores de poder
Tipo
Manual de usuario
16 BRIGGSandSTRATTON.COM
Fuel Consumption (50Hz)
Shown below are the estimated fuel supply requirements.
Fuel Consumption (60Hz)
Shown below are the estimated fuel supply requirements.
Series 29000 (3.0L) LP Vapor Fuel Consumption
Full Load 1/2 Load Exercise
BTU/hr 365000 230000 70000
ft³/hr 146 92 28
m³/hr 4.2 2.6 0.8
Gal/hr (liquid) 4.0 2.6 0.8
Series 35000 (3.0L) LP Vapor Fuel Consumption
Full Load 1/2 Load Exercise
BTU/hr 371000 241000 130000
ft³/hr 149 97 52
m³/hr 4.2 2.8 1.5
Gal/hr (liquid) 4.1 2.7 1.5
Series 29000 (3.0L) NG Fuel Consumption
Full Load 1/2 Load Exercise
BTU/hr 286000 179000 89000
ft³/hr 286 179 89
m³/hr 8.1 5.1 2.6
Series 35000 (3.0L) NG Fuel Consumption
Full Load 1/2 Load Exercise
BTU/hr 336000 215000 108000
ft³/hr 336 215 108
m³/hr 9.5 6.1 3.1
Series 29000 (4.3L) LP Vapor Fuel Consumption
Full Load 1/2 Load Exercise
BTU/hr 349000 225000 106000
ft³/hr 140 90 43
m³/hr 4.0 2.6 1.2
Gal/hr (liquid) 3.9 2.5 1.2
Series 35000 (4.3L) LP Vapor Fuel Consumption
Full Load 1/2 Load Exercise
BTU/hr 409000 262000 137000
ft³/hr 164 105 55
m³/hr 4.7 3.0 1.6
Gal/hr (liquid) 4.5 2.9 1.5
Series 29000 (4.3L) NG Fuel Consumption
Full Load 1/2 Load Exercise
BTU/hr 356000 222000 120000
ft³/hr 356 222 120
m³/hr 10.1 6.3 3.4
Series 35000 (4.3L) NG Fuel Consumption
Full Load 1/2 Load Exercise
BTU/hr 405000 258000 146000
ft³/hr 405 258 146
m³/hr 11.5 7.3 4.2
Series 40000 (4.3L) NG Fuel Consumption
Full Load 1/2 Load Exercise
BTU/hr 428000 256000 118000
ft³/hr 428 256 118
m³/hr 12.2 7.3 3.4
Series 48000 (4.3L) NG Fuel Consumption
Full Load 1/2 Load Exercise
BTU/hr 511000 328000 181000
ft³/hr 511 328 181
m³/hr 14.5 9.3 5.2
Series 40000 (4.3L) LP Vapor Fuel Consumption
Full Load 1/2 Load Exercise
BTU/hr 682500 470000 183750
ft³/hr 273 188 74
m³/hr 7.7 5.3 2.1
Gal/hr (liquid) 7.5 5.1 2.0
Series 48000 (4.3L) LP Vapor Fuel Consumption
Full Load 1/2 Load Exercise
BTU/hr 533000 337000 165000
ft³/hr 214 135 66
m³/hr 6.1 3.9 1.9
Gal/hr (liquid) 5.9 3.7 1.9
Series 50000 (5.7L) LP Vapor Fuel Consumption
Full Load 1/2 Load Exercise
BTU/hr 729000 500000 198000
ft³/hr 292 200 80
m³/hr 8.3 5.7 2.3
Gal/hr (liquid) 8.0 5.5 2.2
Series 60000 (5.7L) LP Vapor Fuel Consumption
Full Load 1/2 Load Exercise
BTU/hr 875000 644000 264000
ft³/hr 350 258 106
m³/hr 10.0 7.3 3.0
Gal/hr (liquid) 9.6 7.1 2.9
Series 50000 (5.7L) NG Fuel Consumption
Full Load 1/2 Load Exercise
BTU/hr 669000 462000 213000
ft³/hr 669 462 213
m³/hr 19.0 13.1 6.1
Series 60000 (5.7L) NG Fuel Consumption
Full Load 1/2 Load Exercise
BTU/hr 753000 561000 264000
ft³/hr 753 561 264
m³/hr 21.4 15.9 7.5
Manual de instalación y operación
29 kW 40 kW 50 kW (50 Hz)
35 kW 48 kW 60 kW (60 Hz)
Generador de reserva monofásico y trifásico
Sistema de generador de energía de emergencia enfriado por líquido
Este generador está clasificado conforme a la norma UL (Underwriters Laboratories) 2200 (grupos
generadores de motor fijo) y a la norma CSA (Canadian Standards Association) C22.2 n.º 100-14 (motores
y generadores).
© Briggs & Stratton, LLC.
Todos los derechos reservados.
80022439USCN
Revisión F
2 BRIGGSandSTRATTON.COM
Gracias por comprar este generador Briggs & Stratton® de alta calidad. Nos complace que haya depositado su confianza
en la marca Briggs & Stratton. Si se utiliza y mantiene de acuerdo con las instrucciones de este manual, el generador le
proporcionará muchos años de funcionamiento fiable.
Este manual contiene información de seguridad para alertarlo sobre los peligros y riesgos asociados con los generadores de
energía de emergencia, y para indicarle cómo evitarlos.
Guarde estas instrucciones para futuras consultas.
Este generador requiere una instalación profesional antes de su uso. El instalador debe seguir completamente las
instrucciones.
Dónde puede encontrarnos
Nunca deberá buscar demasiado para encontrar asistencia y servicio para su generador. Consulte las Páginas Amarillas.
Existen muchos distribuidores de servicio autorizados en todo el mundo, que ofrecen asistencia de calidad. También puede
comunicarse con Servicio Técnico por teléfono al
800-732-2989 entre las 8:00 a. m. y las 5:00 p. m. hora del Centro, o bien, puede hacer clic en Dealer Locator en www.
briggsandstrattom.com, donde obtendrá una lista de distribuidores autorizados.
Para futuras consultas
Complete la siguiente información y manténgala con su recibo. Tenga esta información a mano, en caso que deba
comunicarse con su instalador o distribuidor autorizado con respecto al mantenimiento o a reparaciones de la unidad.
FECHA DE COMPRA
GENERADOR
Número de modelo
Número de serie
Número de modelo
Modificación del modelo
Número de serie
MOTOR
ADVERTENCIA
Este producto puede exponerlo a sustancias
químicas entre las que se incluyen aceite de motor,
reconocidas por el Estado de California como causantes de
cáncer; y monóxido de carbono, reconocido por el Estado de
California como causante de defectos de nacimiento u otros
problemas reproductivos. Para obtener más información,
visite www.P65Warnings.ca.gov.
3
Table Of Contents
Instrucciones de seguridad importantes ............4
Información general .............................7
Descripción del equipo .................................... 7
Antes de la instalación .................................... 7
Responsabilidades del instalador ........................... 7
Responsabilidades del propietario........................... 7
Factores de instalación que se deben considerar .............. 8
Inspección de entrega..................................... 8
Consideraciones para la ubicación del generador .............. 8
La ubicación física real del generador tiene un efecto directo en lo siguiente:
8
Instalación . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
PARA REDUCIR EL RIESGO DE ENVENENAMIENTO POR MONÓXIDO
DE CARBONO .......................................... 9
Generador de energía de emergencia....................... 10
PARA REDUCIR EL RIESGO DE INCENDIO ................ 11
Otros requisitos de ubicación.............................. 12
Ubicaciones de las entradas eléctrica y de combustible ........ 12
Losa de hormigón ....................................... 12
Elevación del generador .................................. 13
Planificación de la instalación de combustible......14
Tamaño de las tuberías de combustible ..................... 14
Tipo de combustible que se debe usar ...................... 15
Conversión de combustible ............................... 15
Presión de combustible................................... 15
Pérdida de potencia ..................................... 15
Consumo de combustible (50 Hz) .......................... 16
Consumo de combustible (60 Hz) .......................... 16
Conexiones de energía................................... 17
Conexiones del cliente - Interconexión/control......18
Aplicaciones del controlador Briggs & Stratton - Monofásica y trifásica 18
Aplicaciones del controlador Intelinano – Trifásica............. 19
Aplicaciones del controlador Intelilite - Monofásica y trifásica ... 20
Batería ................................................ 21
Consideraciones finales de la instalación .................... 21
Sistema de suministro de combustible ...................... 21
Arranque inicial (sin carga) ................................ 22
Características y controles ......................23
Paneles de acceso ...................................... 23
Ubicaciones de los componentes .......................... 24
Mantenimiento .................................25
Limpieza del generador .................................. 25
Mantenimiento del sistema eléctrico ........................ 26
Mantenimiento del sistema de escape ...................... 26
Solución de problemas ..........................27
Especificaciones del generador (60 Hz y 50 Hz).....28
Diagramas de cableado .........................29
35 kW a 60 kW - Monofásica, 60 Hz . . . . . . . . . . . . . . . . . . . . . . . . 30
29 kW a 50 kW - Monofásica, 50 Hz . . . . . . . . . . . . . . . . . . . . . . . . 32
29 kW a 60 kW - Trifásica, Intelinano, 50/60 Hz............... 34
35 kW a 60 kW - Monofásica, Intelilite, 60 Hz................. 36
35 kW a 60 kW - Trifásica, Intelilite, 60 Hz ................... 38
35 kW a 60 kW - 600 V, Intelilite, 60 Hz ..................... 40
Esquemas del cableado .........................42
Motor - 3,0 l ............................................ 42
Motor - 4,3 l ............................................ 44
Motor - 5,7 l ............................................ 46
4 BRIGGSandSTRATTON.COM
Instrucciones de seguridad
importantes
CONSERVE ESTAS INSTRUCCIONES: Este manual
contiene instrucciones importantes que se deben seguir
durante la instalación y el mantenimiento del generador y las
baterías.
Símbolos de seguridad y significados
El símbolo de alerta de seguridad indica un posible
riesgo para su integridad física. Se usa una palabra de
señalización (PELIGRO, ADVERTENCIA o PRECAUCIÓN)
junto con el símbolo de alerta para designar un grado o un
nivel de gravedad de riesgo. Se puede utilizar un símbolo
de seguridad para representar el tipo de peligro. La palabra
de señalización AVISO se usa para designar prácticas no
relacionadas con lesiones corporales.
PELIGRO
indica un riesgo que, si no se evita, ocasionará
la muerte o lesiones graves.
ADVERTENCIA
indica un riesgo que, si no se evita,
podría ocasionar la muerte o lesiones graves.
PRECAUCIÓN
indica un riesgo que, si no se evita, podría
ocasionar lesiones menores o moderadas.
AVISO
hace referencia a una práctica no relacionada con
una lesión física.
El fabricante no puede anticipar cada circunstancia que
involucre potencialmente un peligro. Por lo tanto, las
advertencias incluidas en este manual, así como también
las etiquetas y las calcomanías fijadas en la unidad, no
son exhaustivas. Si emplea un procedimiento, un método
de trabajo o una técnica de operación que el fabricante no
recomienda específicamente, debe cerciorarse de que sea
seguro para usted y el resto del personal. También debe
asegurarse de que el procedimiento, el método de trabajo
o la técnica de operación que elija no pongan en riesgo la
seguridad del sistema generador.
ADVERTENCIA
El motor en funcionamiento emite
monóxido de carbono, un gas venenoso que carece
de olor y de color.
La inhalación de monóxido de carbono podría
ocasionar la muerte, lesiones graves, dolor de
cabeza, fatiga, mareos, vómitos, confusión,
convulsiones, náuseas o desmayos.
Haga funcionar este producto SOLO en el exterior, en
un área donde no se acumulen los gases de escape
mortales.
Mantenga los gases de escape lejos de ventanas,
puertas, tomas de ventilación, ventilaciones de sofitos,
espacios de subsuelo, puertas de garajes abiertas
u otras aberturas que puedan permitir que estos
gases ingresen o se vean atraídos hacia estructuras o
edificios posiblemente habitados.
La instalación y el mantenimiento de detectores de
monóxido de carbono en interiores se DEBE realizar
conforme a las recomendaciones e instrucciones del
fabricante. Las alarmas de humo no pueden detectar
el monóxido de carbono.
ADVERTENCIA
Las baterías almacenadas producen
hidrógeno explosivo mientras se recargan.
Las chispas más pequeñas encenderán el
hidrógeno y causarán una explosión, que tendrá
como resultado la muerte o lesiones graves.
El líquido de electrolito de la batería contiene
ácido y es extremadamente cáustico.
El contacto con el contenido de la batería puede
provocar quemaduras químicas graves.
Una batería presenta un riesgo de descarga
eléctrica y alta corriente de cortocircuito.
NO elimine una batería en el fuego. Recicle las baterías.
NO permita que existan llamas abiertas, chispas,
fuentes de calor, ni que se enciendan cigarrillos durante
y varios minutos después de cargar una batería.
NO abra ni destroce la batería.
Use anteojos protectores de seguridad, delantal de
goma, botas de goma y guantes de goma.
Quítese el reloj, los anillos u otros objetos metálicos.
Use herramientas con mangos aislados.
Explosión
Incendio
Descarga eléctrica
Piezas giratorias
Superficie caliente
Gases tóxicos
Quemadura
química
Presión explosiva
Arranque
automático
Peligro de
aplastamiento y
cortes
Piezas móviles
Lea el manual
ADVERTENCIA
Antes de utilizar este producto, lea este
manual y siga todas las reglas de seguridad
e instrucciones de funcionamiento.
5
ADVERTENCIA
El combustible y sus vapores son
extremadamente inflamables y explosivos,
lo que podría causar quemaduras, incendios
o explosiones que conlleven la muerte o
lesiones graves.
Instale el suministro de combustible conforme a la
norma NFPA 37 y otros códigos de gas combustible
pertinentes.
Antes de poner en servicio el generador, las
tuberías del sistema de combustible se deben
purgar y someter a pruebas de detección de fugas
adecuadamente.
Una vez instalado el generador, debe inspeccionar el
sistema de combustible en forma periódica.
NO se deben permitir fugas.
NO opere el motor si detecta olor a combustible u
otras condiciones explosivas.
NO fume cerca del generador. Limpie inmediatamente
los derrames de aceite con un trapo. Asegúrese
de que no haya materiales combustibles en el
compartimiento del generador. Mantenga el área
alrededor del generador limpia y sin residuos.
ADVERTENCIA
Los gases y el calor de escape pueden
inflamar los materiales combustibles y las
estructuras, lo que podría provocar la muerte
o lesiones graves.
El contacto con el área del mofle podría provocar
quemaduras y causar lesiones graves.
NO toque las piezas calientes y EVITE los gases de
escape calientes.
Deje que el equipo se enfríe antes de tocarlo.
El lado de la salida de escape de la caja impermeable
debe tener un espacio libre de al menos 5 pies (1,5 m)
desde cualquier estructura, arbustos, árboles o
cualquier tipo de vegetación.
La caja impermeable del generador de energía de
emergencia debe estar a una distancia mínima de
5 pies (1,5 m) desde ventanas, puertas, aberturas
en paredes, arbustos o vegetación de más de
12 pulgadas (30,5 cm) de altura.
La caja impermeable del generador de energía de
emergencia debe tener un espacio libre superior
a 5 pies (1,5 m) como mínimo desde cualquier
estructura, elemento colgante o árboles.
NO coloque la caja impermeable debajo de una
cubierta u otro tipo de estructura que pueda encerrar
el flujo de aire.
La instalación y el mantenimiento de detectores de
humo en interiores se DEBE realizar conforme a las
recomendaciones e instrucciones del fabricante. Las
alarmas de monóxido de carbono no pueden detectar
el humo.
Mantenga por lo menos las distancias mínimas que se
muestran en las Pautas generales de ubicación para
garantizar la refrigeración del generador y el espacio
libre para mantenimiento adecuados.
Las piezas de repuesto deben ser iguales y se
deben instalar en la misma posición que las piezas
originales.
ADVERTENCIA
Voltaje peligroso: el contacto con los
cables eléctricos podría provocar electrocución y
quemaduras que pueden provocar lesiones graves o
la muerte.
Si se utilizan equipos de elevación o izado con
polipasto, NO toque las líneas de alta tensión.
NO levante ni mueva el generador sin ayuda.
NO levante la unidad por el techo, ya que ocurrirán
daños en el generador.
ADVERTENCIA
Los generadores producen un voltaje
peligrosa.
Una conexión a tierra defectuosa del generador puede
provocar electrocución.
No aislar el generador de la energía de la red de servicio
público podría provocar la muerte o lesiones graves a los
trabajadores de la red de servicio público eléctrico, debido
a la alimentación inversa de la energía.
NO toque cables ni receptáculos sin aislamiento.
NO use el generador con cables eléctricos que estén
desgastados, raídos, sin aislamiento o dañados de
cualquier otro modo.
NO manipule el generador ni los cables eléctricos si
está en contacto con agua, descalzo o si sus manos o
pies están mojados.
Si debe trabajar cerca de una unidad mientras está
funcionando, párese en una superficie seca y aislada
para reducir el peligro de descarga.
NO permita que personas no calificadas o niños
operen o realicen mantenimiento al generador.
En caso de un accidente por descarga eléctrica,
corte inmediatamente la fuente de energía eléctrica
y comuníquese con las autoridades locales.Evite el
contacto directo con la víctima.
A pesar del diseño seguro del generador, si lo opera
de manera imprudente, no realiza el mantenimiento
o si es descuidado, se pueden producir lesiones o la
muerte.
Permanezca alerta en todo momento mientras trabaja
en el equipo. Nunca trabaje en los equipos cuando
esté mental o físicamente fatigado.
Antes de realizar cualquier mantenimiento en el
generador, detenga el generador y desconecte el
cable negativo (-) de la batería.
Después de instalar el sistema, el generador puede
arrancar sin advertencia cada vez que se produzca un
corte de energía.
6 BRIGGSandSTRATTON.COM
PRECAUCIÓN
Las velocidades operativas
extremadamente altas pueden provocar lesiones leves o
dañar el generador.
Las velocidades excesivamente bajas imponen una
pesada carga en el generador.
NO manipule la velocidad de régimen. El generador
suministra la frecuencia y el voltaje nominales
correctos cuando funciona a la velocidad de régimen.
NO modifique el generador de ninguna forma.
AVISO
El tratamiento inadecuado del generador podría
estropearlo y acortar su vida útil.
Utilice el generador solo para sus usos previstos.
Si tiene dudas acerca de los usos previstos,
comuníquese con un distribuidor autorizado.
Haga funcionar el generador solamente sobre
superficies niveladas.
Para el funcionamiento correcto del generador,
es fundamental contar con una circulación de
aire de ventilación y refrigeración adecuada y sin
obstrucciones.
Las puertas y los paneles de acceso deben
estar instalados siempre que la unidad esté en
funcionamiento.
NO exponga el generador a un ambiente con exceso
de humedad, polvo, suciedad o vapores corrosivos.
Permanezca alerta en todo momento mientras trabaja
en el equipo. Nunca trabaje en los equipos cuando
esté mental o físicamente fatigado.
NO arranque el motor si se quitó el filtro de aire o la
cubierta de este.
NO inserte ningún objeto por las ranuras de
refrigeración.
NO use el generador ni ninguna de sus piezas como
un peldaño. Pararse sobre la unidad podría provocar
tensión y romper las piezas. Esto puede generar
condiciones de funcionamiento peligrosas, como
por ejemplo, fuga de gases de escape, fugas de
combustible, fugas de aceite, etc.
Si los dispositivos conectados se sobrecalientan,
apáguelos y desconéctelos del generador.
Apague el generador en los siguientes casos:
-si pierde potencia eléctrica;
-si el equipo produce chispas o humo, o emite llamas;
-si la unidad vibra en exceso.
AVISO
Exceder la capacidad de vatios o amperios del
generador podría dañar el generador o los dispositivos
eléctricos conectados a este.Arranque el generador y
permita que el motor se estabilice antes de conectar las
cargas eléctricas.
ADVERTENCIA
Las partes móviles podrían aplastar y
cortar.
El arrancador y otras piezas giratorias
podrían apretar las manos, el cabello, la
ropa o los accesorios y causar lesiones graves.
NUNCA opere el generador sin carcasas de
protección, cubiertas o protecciones en su lugar.
NO use ropa suelta, joyas o cualquier cosa que se
pueda quedar atrapada en el arrancador o en otras
piezas giratorias.
Recoja el cabello largo y quítese cualquier joya.
Antes de realizar el mantenimiento, detenga siempre
el generador y desconecte el cable negativo (-) de la
batería.
7
Información general
En el caso de la mayoría de las aplicaciones, el Manual
de instalación y operación incluye toda la información
necesaria para instalar, operar el generador y realizarle el
mantenimiento de manera adecuada.
Se ha hecho todo lo posible para garantizar que la
información contenida en este manual sea precisa y actual.
Sin embargo, nos reservamos el derecho de realizar
cambios, alterar o mejorar el producto y este documento, en
cualquier momento sin previo aviso.
Asegúrese de que este manual se le haya proporcionado al
propietario después de completar la instalación.
Descripción del equipo
Este producto solo se debe usar como un sistema
generador opcional, para proporcionar una fuente alternativa
de energía eléctrica y abastecer cargas como por ejemplo
de sistemas de calefacción, refrigeración y de comunicación
que, cuando se detienen durante un corte de energía,
pueden generar incomodidades o inconvenientes.
AVISO Solo los modelos equipados con el controlador
DSE7310 o ComAp Intelilite pueden calificar para un
sistema de emergencia legalmente exigido, conforme a lo
definido en la norma NFPA 70 (NEC). Para ver la información
completa acerca de estos tipos de instalaciones, consulte
NFPA 70 y NFPA 110.
Los sistemas de generador de energía de emergencia
legalmente exigidos están diseñados para suministrar
automáticamente energía para cargas seleccionadas,
en el caso de falla de la fuente normal, que podría
generar peligros u obstaculizar operaciones de
rescate o combate de incendios.
Antes de la instalación
Solo electricistas y plomeros profesionales con licencia
actualizada deben realizar las instalaciones del generador.
Las instalaciones deben cumplir estrictamente todos los
reglamentos, las leyes, los estándares industriales y los
códigos pertinentes.
En algunas áreas, es posible que deba conseguir permisos
eléctricos para instalar el generador, permisos de
construcción para instalar tuberías de gas y permisos para
tolerancias de ruidos. El instalador debe revisar los códigos
locales y obtener los permisos antes de instalar el sistema.
La garantía del generador se ANULARÁ salvo que
profesionales de plomería y electricidad con licencia instalen
el sistema.
Responsabilidades del instalador
Lea y respete las instrucciones de seguridad.
Instale solo un interruptor de transferencia aprobado
por UL que sea compatible con el generador.
Lea y siga las instrucciones que se entregan en el
Manual de instalación y operación.
Las instalaciones deben cumplir estrictamente todos
los reglamentos, las leyes, los estándares industriales
y los códigos pertinentes.
Deje suficiente espacio en todos los lados del
generador para realizar mantenimiento.
Responsabilidades del propietario
Lea y siga las instrucciones que se entregan en el
Manual de instalación y operación.
Siga un programa regular para el mantenimiento y uso
del generador, según se especifica en este manual.
La instalación y el mantenimiento de detectores de
monóxido de carbono en interiores se DEBE realizar
conforme a las recomendaciones e instrucciones del
fabricante. Las alarmas de humo no pueden detectar
el monóxido de carbono.
La instalación y el mantenimiento de detectores de
humo en interiores se DEBE realizar conforme a las
recomendaciones e instrucciones del fabricante. Las
alarmas de monóxido de carbono no pueden detectar
el humo.
8 BRIGGSandSTRATTON.COM
Factores de instalación que se deben
considerar
Las ilustraciones que se muestran en este manual son
para circunstancias típicas. Tienen la intención de que se
familiarice con las opciones de instalación disponibles para
el generador.
Los códigos locales y federales, la apariencia, los niveles
de ruido, los tipos de combustible y las distancias son
factores de instalación que se deben considerar. Recuerde
que a medida que aumenta la distancia desde el servicio
eléctrico y el suministro de combustible gaseoso existente,
y que aumenta la cantidad de curvas en el suministro de
combustible, se deben realizar compensaciones en los
materiales de cableado y tuberías. Lo anterior es necesario
para cumplir los códigos locales y superar las caídas de
voltaje eléctrico y las caídas de presión del combustible
gaseoso.
Los factores antes mencionados tienen un efecto directo en
el precio general de la instalación del generador.
Inspección de entrega
Evite los daños por caídas, golpes o colisiones con la caja
de envío. Inspeccione cuidadosamente si el generador
presenta daños que puedan haber ocurrido durante el envío.
Si se detectan daños o pérdidas al momento de la entrega,
pida a la persona encargada de la entrega que tome nota
de todos los daños en la factura de flete y ponga su firma en
el memorándum de pérdidas y daños del expedidor. Si se
detectan daños o pérdidas después de la entrega, separe
los materiales dañados y comuníquese con la empresa de
transporte para realizar los procedimientos de reclamación.
Las piezas dañadas o faltantes no tienen garantía.
El sistema de generador de energía de emergencia se
proporciona con:
Sistema de enfriamiento con mantenimiento completo
Sistema de aceite o lubricación con mantenimiento
completo
Manguera de conexión flexible para combustible
Manual de instalación y operación
Llaves de repuesto de la puerta de acceso
Pintura de retoque
No se proporciona lo siguiente:
Detectores de monóxido de carbono
Detectores de humo
Batería de arranque
Losa de hormigón reforzado
Conducto y cable de conexión
Tuberías y válvulas de suministro de combustible
Grúa, cables, cadenas o correas de levantamiento,
barra separadora
Medidor de voltaje y frecuencia
Diversas herramientas o equipos especiales
Consideraciones para la ubicación del
generador
La ubicación física real del generador tiene un efecto directo
en lo siguiente:
1. La cantidad de plomería que se requiere para
abastecer de combustible el generador.
2. La cantidad de cableado que se requiere para
controlar y conectar el generador.
3. La seguridad de la instalación con respecto a los
peligros del monóxido de carbono y el gas de escape,
los peligros de incendio, la proximidad a otros servicios
públicos y la exposición a los elementos del clima.
Las pautas específicas de ubicación se analizan en la
siguiente sección. El propietario y el instalador se deben
consultar entre sí para determinar cómo el lugar puede
afectar los costos de instalación y el cumplimiento con los
códigos y normas locales.
9
C
B
B
Instalación
Antes de decidir acerca de la ubicación final del generador, el propietario e instalador deben analizar y comprender las
distintas pautas de ubicación. Hay dos inquietudes de seguridad fundamentales que se deben tratar: el envenenamiento
por monóxido de carbono y el riesgo de incendio, de la siguiente manera:
ADVERTENCIA El motor en funcionamiento emite monóxido
de carbono, un gas venenoso que carece de olor y de
color.
La inhalación de monóxido de carbono podría ocasionar la
muerte, lesiones graves, dolor de cabeza, fatiga, mareos,
vómitos, confusión, convulsiones, náuseas o desmayos.
Haga funcionar este producto SOLO en el exterior, en un área
donde no se acumulen los gases de escape mortales.
Mantenga los gases de escape lejos de ventanas, puertas,
tomas de ventilación, ventilaciones de sofitos, espacios de
subsuelo, puertas de garajes abiertas u otras aberturas que
puedan permitir que estos gases ingresen o se vean atraídos
hacia estructuras o edificios posiblemente habitados.
La instalación y el mantenimiento de detectores de monóxido
de carbono en interiores se DEBEN realizar conforme las
recomendaciones e instrucciones del fabricante. Las alarmas
de humo no pueden detectar el
monóxido de carbono.
ADVERTENCIA
Los gases y el calor de escape
pueden inflamar los materiales combustibles y las
estructuras, lo que podría provocar la muerte o
lesiones graves.
El lado de la salida de escape de la caja de
emergencia debe estar al menos a 5 pies (1,5 m) de
cualquier estructura, arbustos, árboles o cualquier tipo
de vegetación.
La caja de emergencia debe estar, al menos, a
5 pies (1,5 m) de ventanas, puertas, aberturas en
paredes, arbustos o vegetación sobre 12 pulgadas
(30,5 cm) de altura.
La caja de emergencia debe tener un mínimo de
distancia libre hacia arriba de 5 pies (1,5 m) con
respecto a cualquier estructura, saliente o árboles.
NO coloque la caja de emergencia debajo de una
cubierta u otro tipo de estructura que pueda encerrar
el flujo de aire.
La instalación y el mantenimiento de detectores de
humo en interiores se DEBE realizar conforme las
recomendaciones e instrucciones del fabricante. Las
alarmas de monóxido de carbono no pueden detectar
el humo.
PARA REDUCIR EL RIESGO DE ENVENENAMIENTO POR MONÓXIDO DE CARBONO
Siga los requisitos de instalación que se indican a continuación. Las cifras a continuación indican puntos potenciales de
ingreso de gas de monóxido de carbono.
Asegúrese de que el gas de escape del generador se
mantenga alejado de:
Puertas elevadas (B, se muestra arriba)
Puertas de entrada (C, se muestra arriba)
Ventanas (no se muestra)
Otras aberturas que pueden permitir que los gases de
escape ingresen o se vean atraídos hacia estructuras
o edificios posiblemente habitados.
10 BRIGGSandSTRATTON.COM
Todos los equipos que queman combustibles fósiles,
como los generadores de energía de emergencia,
contienen gas de monóxido de carbono (CO) en el
escape del motor. El gas de CO es inodoro, incoloro y no
tiene sabor, y es muy poco probable que una persona
lo detecte hasta que se sienta debilitado. El gas de CO
puede matarlo. Se necesita que lo siguiente se incluya
como parte de la instalación:
Instale el generador en el exterior, en un área donde
no se acumulen los gases de escape mortales.
NO instale el generador donde los gases de escape
se puedan acumular e ingresar o ser atraídos hacia
estructuras o edificios posiblemente habitados.
Las estructuras cercanas pueden estar expuestas
al escape del motor de la unidad; esto se debe
considerar cuando instale el generador de energía
de emergencia.
Se deben considerar las corrientes de aire y el viento
cuando se determina la ubicación del generador.
Coloque el generador en un área donde el viento
aleje el gas de escape de cualquier edificio o
estructura posiblemente habitada.
NO coloque el generador de energía de emergencia
en un área donde normalmente se acumulen hojas o
residuos.
Por ley, muchos estados exigen un detector de
monóxido de carbono (CO) completamente operativo
en hogares y en otras estructuras con presencia
de personas. La instalación y el mantenimiento de
detectores de monóxido de carbono en interiores se
DEBEN realizar conforme las recomendaciones e
instrucciones del fabricante. Un monitor de CO es un
dispositivo electrónico que detecta niveles peligrosos
de CO. Cuando existe acumulación de CO, el monitor
alerta a los ocupantes mediante el parpadeo de una
luz indicadora visual y una alarma. Las alarmas de
humo no pueden detectar el gas de CO.
Dirija el escape del generador de energía de
emergencia (A, se muestra abajo) lejos de o
paralelo al edificio o la estructura. NO dirija el
escape del generador hacia edificios o estructuras
posiblemente habitados, ventanas, puertas, tomas
de ventilación, ventilaciones de sofitos, espacios
de subsuelo, puertas de garajes abiertas u otras
aberturas que puedan permitir que estos gases
ingresen o se vean atraídos hacia estructuras o
edificios posiblemente habitados.
El escape del motor sale de la parte superior de la
carcasa (A).
A
Generador de
energía
11
A
A
B
C
PARA REDUCIR EL RIESGO DE INCENDIO
Siga los requisitos de instalación que se indican a continuación. Las figuras a continuación muestran las distancias
mínimas desde las estructuras y la vegetación para reducir el riesgo de incendio.
La norma NFPA 37 de la Asociación Nacional de Protección contra Incendios (NFPA) establece los criterios para minimizar
el peligro de incendio durante la instalación y el funcionamiento de motores de combustión fijos. La norma NFPA 37 limita
el espacio de un generador cerrado con respecto a paredes, estructuras y materiales combustibles fuera de la caja. Los
siguientes requisitos de ubicación del generador se basan en el cumplimiento de la norma NFPA 37.
5 pies (1,5 m) mín.
Emergencia
5 pies (1,5 m) mín.
Escape
B
A
5 pies (1,5 m) mín.
Emergencia
5 pies (1,5 m) mín.
Escape
A
A
B
5 pies (1,5 m) mín.
Emergencia
5 pies (1,5 m) mín.
Escape
B
A
A
A La caja de emergencia debe estar, al menos, a
5 pies (1,5 m) de ventanas, puertas, aberturas
en paredes, arbustos o vegetación sobre
12 pulgadas (30,5 cm) de altura.
B El lado de la salida de escape de la caja de
emergencia debe tener un espacio libre de al
menos 5 pies (1,5 m) desde cualquier estructura,
arbustos, árboles o cualquier tipo de vegetación.
C La caja de emergencia debe tener un mínimo
de distancia libre hacia arriba de 5 pies (1,5 m)
con respecto a cualquier estructura, saliente o
árboles.
NO coloque la caja de emergencia bajo una plataforma
u otro tipo de estructura cubierta que pueda restringir
el flujo de aire.
5 pies (1,5 m) mín.
5 pies (1,5 m) mín.
Emergencia
5 pies (1,5 m) mín.
Escape
B
A
A
12 BRIGGSandSTRATTON.COM
Otros requisitos de ubicación
Coloque el generador de energía de emergencia en
una ubicación preparada que esté nivelada y tenga
disposiciones para el drenaje de agua.
Instale el generador de energía de emergencia en
una ubicación donde la descarga de la bomba de
sumidero, los tubos de bajada de canaletas para
lluvia, el desagüe de techos, el riego de jardines
o los rociadores de agua no inunden la unidad ni
pulvericen la caja, ni que ingresen por las aberturas
de entrada y salida de aire.
Instale el generador de energía de emergencia
donde no afecte ni obstruya ningún de la red
de servicio público (ya sea cubierto, cerrado
o subterráneo), como teléfono, electricidad,
combustible (gas natural o vapor de GLP), riego,
aire acondicionado, cables, instalaciones sépticas,
alcantarillas, pozos, etc.
Instale el generador de energía de emergencia
donde las hojas, el césped, la nieve, etc. no
obstruyan las aberturas de entrada y salida de aire.
Si los vientos predominantes hacen volar las hojas
o producen amontonamiento, puede necesitar un
cortaviento para proteger la unidad.
Ubicaciones de las entradas eléctrica y de
combustible
Se prefiere el uso de un pasamuros para el cable de
alimentación a través de la losa. El conector de entrada de
combustible (A) se muestra como referencia.
Losa de hormigón
El generador debe estar instalado en una losa de hormigón
reforzado, construida de la siguiente manera:
Resistencia de compresión a 28 días de 3000 psi
(200 MPa)
Mínimo 5 pulgadas (13 cm) de grosor
Mínimo 6 pulg (15 cm) más ancha que la caja del
generador en todos los lados
Refuerce la losa con barras de refuerzo n.° 6 en centros
de 12 pulgadas (30,5 cm) o con tela metálica de acero
calibre 8 en centros de 6 pulgadas (15 cm).
Evite colocar refuerzos en el área de pasamuros de
entrada.
Se necesitarán las siguientes dimensiones para ajustar el
tamaño y configurar correctamente la losa. Consulte la figura
a la derecha:
A - Dimensiones del contenedor
29/35 kW (3,0 l) = 82 pulg (208 cm) de largo x 37 pulg
(94 cm) de ancho
29/35 kW (4,3 l) = 88 pulg (224 cm) de largo x 37 pulg
(94 cm) de ancho
40/48 kW = 88 pulg (224 cm) de largo x 37 pulg (94 cm)
de ancho
50/60 kW = 96 pulg (244 cm) de largo x 37 pulg (94 cm)
de ancho
B - Orificios de montaje del generador
29/35 kW (3,0 l) = 75,5 pulg (192 cm) de largo x
34,25 pulg (87 cm) de ancho
29/35 kW (4,3 l) = 85 pulg (216 cm) de largo x
34,25 pulg (87 cm) de ancho
40/48 kW = 85 pulg (216 cm) de largo x 34,25 pulg
(87 cm) de ancho
50/60 kW = 94 pulg (239 cm) de largo x 34,25 pulg
(87 cm) de ancho
C - Ubicación de la entrada de combustible
29/35 kW (3,0 l) = 40,75 pulg (104 cm)
29/35 kW (4,3 l) = 45,5 pulg (116 cm)
40/48 kW = 45,5 pulg (116 cm)
50/60 kW = 52 pulg (132 cm)
D - Área de la entrada del pasamuros
29/35 kW (3,0 l) = 9,25 pulg (23 cm) de largo x
5,25 pulg (13 cm) de ancho
29/35 kW (4,3 l) = 10,5 pulg (27 cm) de largo x
6,75 pulg (17 cm) de ancho
40/48 kW = 10,5 pulg (27 cm) de largo x 6,75 pulg
(17 cm) de ancho
50/60 kW = 6,0 pulg (15 cm) de largo x 5,25 pulg
(13 cm) de ancho
D1 x D2 - Ubicación de la entrada del pasamuros
29/35 kW (3,0 l) = 6,0 pulg (15 cm) x 7,75 pulg (20 cm)
29/35 kW (4,3 l) = 8,5 pulg (22 cm) x 7,75 pulg (20 cm)
40/48 kW = 8,5 pulg (22 cm) x 7,75 pulg (20 cm)
50/60 kW = 16,0 pulg (41 cm) x 7,0 pulg (18 cm)
A
13
A - Contenedor del generador de energía de
emergencia
B - Orificios de montaje en la base del generador
C - Ubicación de la entrada de combustible
D - Área de la entrada del pasamuros
D1 x D2 - Ubicación de la entrada del pasamuros
E - Referencia del área de salida del escape
F - Referencia de la losa de concreto
ADVERTENCIA
Tensión peligrosa: El contacto con los
cables eléctricos podría provocar electrocución y
quemaduras que pueden provocar lesiones graves
o la muerte.
Si se utilizan equipos de elevación o izado con
polipasto, NO toque las líneas de alta tensión.
NO levante ni mueva el generador sin ayuda.
NO levante la unidad por el techo, ya que ocurrirán
daños en el generador.
Elevación del generador
Adjunte el generador a la losa en las cuatro ubicaciones
de las esquinas (B) con anclas de mampostería según lo
requiera el código local.
B
D
C
F
E
A
B
D2
D
D1
D
C
B
En todas las etapas de manipulación y traslado del
generador, se deben utilizar las herramientas y los equipos
adecuados y debe intervenir personal capacitado. El peso
aproximado del generador se indica en la Sección de
especificaciones del generador.
Use los orificios de elevación (G) en la base del generador
para levantar el generador sobre la plataforma de hormigón.
Levante el generador de acuerdo con OSHA o la normativa
local de elevación. Retoque la pintura descascarada con la
pintura de retoque que se proporciona.
G
14 BRIGGSandSTRATTON.COM
Planificación de la instalación
de combustible
La siguiente información se proporciona para ayudar a los
técnicos en sistemas de combustible gaseoso para planificar
las instalaciones. Los códigos estatales y locales pueden anular
algunas de estas recomendaciones. Consulte con el proveedor
de combustible local o con el jefe de Bomberos si necesita
aclaración.
ADVERTENCIA
El propano
y el gas natural son
extremadamente inflamables y explosivos,
lo que podría causar quemaduras, incendios
o explosiones que conlleven la muerte o
lesiones graves.
El gas licuado de petróleo es más pesado que el aire
y se asentará en áreas bajas.
El gas natural es más liviano que el aire y se
acumulará en áreas altas.
La chispa más leve podría encender estos
combustibles y provocar una explosión.
NO encienda un cigarrillo ni fume.
Se deberá instalar una válvula de cierre manual,
aprobada y accesible (F), como mínimo en la tubería
de suministro de combustible, a una distancia de 6 pies
(180 cm) del generador.
Donde las condiciones locales incluyan terremotos,
tornados, terrenos inestables o peligros de inundación,
se deberá considerar especialmente el aumento de la
resistencia y la flexibilidad de los soportes y conexiones
de las tuberías.
Las tuberías deben ser del tamaño correcto para
mantener las presiones de suministro y el flujo de
volumen necesarios en condiciones variables de carga
del generador, con todos los artefactos a gas conectados
al sistema de combustible que esté encendido y
en funcionamiento.
Use un sellador de tuberías o un compuesto para
juntas aprobado para su uso con GN o PL en todos
los conectores roscados, para reducir la posibilidad de
fugas.
Las tuberías instaladas se deben purgar y probar
contra fugas, de acuerdo con los códigos y las normas
pertinentes.
El propietario y el instalador deberán consultarse mutuamente
para revisar cualquier cambio en el plan de instalación que
pueda surgir al aplicar las siguientes pautas para la tubería de
combustible.
• Las tuberías deben ser de un material que cumpla con los
códigos locales y federales, deben montarse rígidamente
y deben estar protegidas contra la vibración.
• Las tuberías deben estar protegidas de los daños físicos
cuando pasen a través de canteros de flores, canteros
de arbustos y otras áreas cultivadas donde se podrían
producir daños.
Instale la tubería flexible de (B, a la derecha) entre el
puerto de entrada de combustible del generador (A) y
la tubería rígida para evitar que la expansión térmica y
la contracción térmica produzcan tensión excesiva en el
material de la tubería.
AVISO
La tubería flexible de combustible no se debe instalar
de manera subterránea ni en contacto con el suelo.Toda
la tubería flexible debe estar visible para inspeccionarla
periódicamente.
Se debe proporcionar una unión (C) o conexión bridada
corriente abajo para permitir el retiro de los controles.
Se debe instalar un puerto de prueba para el manómetro
(D) para combustibles de vapor. El puerto permite la
instalación temporal de un manómetro para garantizar
que el motor reciba la presión de combustible
correcta para funcionar de manera correcta en todo
su rango operativo. Hay un manómetro digital (P/N
19495) disponible en su centro de servicio solo para
combustibles de vapor. Para propano líquido, se puede
utilizar cualquier instrumento de medición de presión
apto para propano líquido y 350 psi. Cuando se terminan
las pruebas iniciales, se retira el manómetro y se tapa el
puerto.
Solo para combustibles de vapor: Cuando se sabe
que se forman hidratos o hielo, se deben proteger las
tuberías contra la congelación. El extremo de la tubería
dura debe incluir un colector de sedimentos (E) donde
no sea posible que se congele el condensado.
A
B
C
D
E
F
A - - Entrada de combustible del
generador
B - Manguera de combustible flexible
C - Conector de unión
D - Puerto de prueba del manómetro
E - Colector de sedimentos (solo
combustibles de vapor)
F - Válvula de cierre manual
Tamaño de las tuberías de combustible
Las normas NFPA 54 y 58 son recursos comunes. El instalador
debe considerar la gravedad específica del gas, compensar
la cantidad nominal de restricción producida por curvas y
conectores, y consultar los códigos locales y federales para
obtener orientación.
15
Conversión de combustible
El motor está diseñado de fábrica para funcionar con gas
natural (GN). Para convertir el motor para que funcione con
propano líquido (vapor de GLP) o para cambiarlo de vuelta a
GN posteriormente, siga estos pasos:
1. Abra la puerta del controlador.
2. Ubique el interruptor selector de combustible en el
lado de la caja del disyuntor.
3. Mueva la llave (A, a continuación) a GLP o GN.
4. Cierre la puerta del controlador.
A
ADVERTENCIA
El combustible es extremadamente
inflamable y explosivo, lo que podría causar quemaduras,
incendios o explosiones que conlleven la muerte o lesiones
graves.
El generador está equipado con válvulas “de cierre
de gas combustible” automáticas de seguridad.
NO opere el equipo si faltan las válvulas “de cierre de
combustible” o si no están en funcionamiento.
Tipo de combustible que se debe usar
Una consideración importante que afecta toda la
instalación es el tipo de combustible que se usa. Para
garantizar el funcionamiento correcto, use combustible
limpio, seco, libre de humedad o cualquier partícula
especial. El uso de combustibles que estén fuera de
los siguientes valores recomendados puede provocar
problemas de rendimiento.
Presión de combustible
La presión de suministro de combustible en el puerto
de entrada de combustible del generador (o puerto de
prueba del vaporizador) debe ser de 7 a 11 pulgadas
CA (17 a 28 mBar) a carga completa con todos los
artefactos a gas encendidos y en funcionamiento. La caída
máxima de presión de estático (con el motor apagado)
a carga completa es de 0.5 pulgadas CA (1,3 mBar). La
presión máxima con el motor APAGADO sin carga es de
13,85 pulgadas CA (34,5 mBar). La presión del combustible
de propano líquido en la entrada del generador debe ser de
100 a 250 psi (690 a 1725 kPa).
Pérdida de potencia
La potencia del motor disminuirá:
• 1,5 % por cada 10 °F (5,6 °C) sobre la temperatura de
77 °F (25 °C).
• 2,5 % por cada 1000 pies (305 m) sobre la altitud de
1200 pies (366 m) sobre el nivel del mar.
Propiedades físicas Vapor de
PL
Gas natural
Estado atmosférico normal Gas Gas
Punto de ebullición en °F: -44 -259
Valor de calentamiento:
BTU por galón (LHV neto
*)
BTU por galón (bruto **)
BTU por pies cúbicos
(gas)
83,340
91,547
2500
63,310
1000
Densidad *** 36,39 57,75
Peso † 4,24 2,65
*LHV (valor inferior de calentamiento) es la calificación
más realista.
**El valor de calentamiento bruto no considera la pérdida
de calor en forma de agua durante la combustión.
***La densidad se presenta en “pies cúbicos por galón de
líquido”.
†El peso se presenta en “libras por galón de líquido”.
16 BRIGGSandSTRATTON.COM
Consumo de combustible (50 Hz)
A continuación se muestran los requisitos estimados de
suministro de combustible.
Consumo de combustible (60 Hz)
A continuación se muestran los requisitos estimados de suministro de
combustible.
Consumo de combustible de vapor de GLP (3,0 l) de la serie
29000
Carga completa 1/2 carga Ejercicio
BTU/h 365000 230000 70000
pies cúbicos/h 146 92 28
m³/h 4,2 2,6 0,8
Gal/h (líquido) 4,0 2,6 0,8
Consumo de combustible de vapor de
GLP (3,0 l) de la serie 35000
Carga completa 1/2 carga Ejercicio
BTU/h 371000 241000 130000
pies cúbicos/h 149 97 52
m³/h 4,2 2,8 1,5
Gal/h (líquido) 4,1 2,7 1,5
Consumo de combustible de GN (3,0 l) de la serie 29000
Carga completa 1/2 carga Ejercicio
BTU/h 286000 179000 89000
pies cúbicos/h 286 179 89
m³/h 8,1 5,1 2,6
Consumo de combustible de GN (3,0 l) de la serie 35000
Carga completa 1/2 carga Ejercicio
BTU/h 336000 215000 108000
pies cúbicos/h 336 215 108
m³/h 9,5 6,1 3,1
Consumo de combustible de vapor de
GLP (4,3 l) de la serie 29000
Carga completa 1/2 carga Ejercicio
BTU/h 349000 225000 106000
pies cúbicos/h 140 90 43
m³/h 4,0 2,6 1,2
Gal/h (líquido) 3,9 2,5 1,2
Consumo de combustible de vapor de
GLP (4,3 l) de la serie 35000
Carga completa 1/2 carga Ejercicio
BTU/h 409000 262000 137000
pies cúbicos/h 164 105 55
m³/h 4,7 3,0 1,6
Gal/h (líquido) 4,5 2,9 1,5
Consumo de combustible de GN (4,3 l) de la serie 29000
Carga completa 1/2 carga Ejercicio
BTU/h 356000 222000 120000
pies cúbicos/h 356 222 120
m³/h 10,1 6,3 3,4
Consumo de combustible de GN (4,3 l) de la serie 35000
Carga completa 1/2 carga Ejercicio
BTU/h 405000 258000 146000
pies cúbicos/h 405 258 146
m³/h 11,5 7,3 4,2
Consumo de combustible de GN (4,3 l) de la serie 40000
Carga completa 1/2 carga Ejercicio
BTU/h 428000 256000 118000
pies cúbicos/h 428 256 118
m³/h 12,2 7,3 3,4
Consumo de combustible de GN (4,3 l) de la serie 48000
Carga completa 1/2 carga Ejercicio
BTU/h 511000 328000 181000
pies cúbicos/h 511 328 181
m³/h 14,5 9,3 5,2
Consumo de combustible de vapor de GLP (4,3 l) de la serie
40000
Carga completa 1/2 carga Ejercicio
BTU/h 682500 470000 183750
pies cúbicos/h 273 188 74
m³/h 7,7 5,3 2,1
Gal/h (líquido) 7,5 5,1 2,0
Consumo de combustible de vapor de
GLP (4,3 l) de la serie 48000
Carga completa 1/2 carga Ejercicio
BTU/h 533000 337000 165000
pies cúbicos/h 214 135 66
m³/h 6,1 3,9 1,9
Gal/h (líquido) 5,9 3,7 1,9
Consumo de combustible de vapor de GLP (5,7 l) de la serie
50000
Carga completa 1/2 carga Ejercicio
BTU/h 729000 500000 198000
pies cúbicos/h 292 200 80
m³/h 8,3 5,7 2,3
Gal/h (líquido) 8,0 5,5 2,2
Consumo de combustible de vapor de
GLP (5,7 l) de la serie 60000
Carga completa 1/2 carga Ejercicio
BTU/h 875000 644000 264000
pies cúbicos/h 350 258 106
m³/h 10,0 7,3 3,0
Gal/h (líquido) 9,6 7,1 2,9
Consumo de combustible de GN (5,7 l) de la serie 50000
Carga completa 1/2 carga Ejercicio
BTU/h 669000 462000 213000
pies cúbicos/h 669 462 213
m³/h 19,0 13,1 6,1
Consumo de combustible de GN (5,7 l) de la serie 60000
Carga completa 1/2 carga Ejercicio
BTU/h 753000 561000 264000
pies cúbicos/h 753 561 264
m³/h 21,4 15,9 7,5
17
Conexiones de energía
Compare esta ilustración con su generador para familiarizarse con la ubicación de estas conexiones.
B
C
A A
A - Conexión de energía - Conexión de energía hacia el switch de
transferencia.
B - Conexión Neutra - Conectar al neutro del switch de
transferencia.
C - Conexión a tierra - Conectar a tierra del switch de
transferencia.
Conecte el generador a tierra conforme a los códigos, las normas
y los reglamentos pertinentes. Hay dos ubicaciones de orejetas de
conexión a tierra (GND) en el generador. La ubicación mostrada (C,
arriba) deberá ser suficiente para la mayoría de las aplicaciones. La
segunda orejeta GND del generador está ubicada en el bastidor.
Esta SOLO se debe usar para una varilla de conexión a tierra
ubicada en el generador si lo exigen los códigos locales.
Para obtener información sobre las conexiones del sistema, como
el arranque remoto, las paradas de emergencia y las entradas y
salidas del controlador, consulte los diagramas de conexión en las
siguientes páginas.
Para la conexión de salida de potencia, utilice un cable
de 167 °F (75 °C) clasificado para temperatura ambiente
de 104 °F (40 °C) según las Tablas NEC 310.15(B)(16) y
310.15(B)(2)(a).
Para las conexiones del circuito de la red de servicio público,
use un cable n.° 14 AWG para 600 voltios mínimo, 167 a
194 °F (75 °C a 90 °C).
Para la comunicación del switch de transferencia, use un
cable con conductores de par trenzado n.º 18 AWG, de una
longitud inferior a 200 pies (60 m) para 600 voltios y para 167
a 194 °F (75 °C a 90 °C).
18 BRIGGSandSTRATTON.COM
Disyuntor del generador
Voltaje
- Fase -
Frecuencia
230 V - Monofásica - 50 Hz 120/240 V - Monofásica - 60 Hz 120/208 V - Estrella trifásica - 60 Hz 120/240 V - Delta trifásica - 60 Hz
Nodo de
potencia
Corriente
máxima del
disyuntor
Rango de cable con
lengüeta
Corriente
máxima del
disyuntor
Rango de cable con
lengüeta
Corriente
máxima del
disyuntor
Rango de cable con
lengüeta
Corriente
máxima del
disyuntor
Rango de cable con
lengüeta
20/25 kW 90 A 125 A Cu/Al: n.º 2 - 300 kcmil 90 A Cu: n.º 6 - 2/0 Al: n.º 4 - 2/0 80 A Cu/Al: n.º 3 - 500 kcmil
25/30 kW 125 A Cu/Al: n.º 2 - 300 kcmil 150 A Cu/Al: n.º 2 - 300 kcmil 110 A Cu: n.º 3 - 3/0 Al: n.º 1 - 3/0 90 A Cu: n.º 6 - 2/0 Al: n.º 4 - 2/0
29/35 kW 150 A Cu/Al: n.º 2 - 300 kcmil 150 A Cu/Al: n.º 2 - 300 kcmil
40/48 kW 175 A Cu/Al: n.º 2 - 300 kcmil 200 A Cu/Al: n.º 2 - 300 kcmil
50/60 kW 225 A Cu/Al: n.º 2 - 300 kcmil 300 A Cu/Al: n.º 6 - 600 kcmil
Aplicaciones del controlador Briggs & Stratton - Monofásica y trifásica
Conexiones del cliente - Interconexión/control
19
Disyuntor del generador
Voltaje
- Fase -
Frecuencia
120/208 V - Estrella trifásica - 60 Hz 120/240 V - Delta trifásica - 60 Hz 220/380 V - Estrella trifásica - 50 Hz 240/416 V - Estrella trifásica - 60 Hz 277/480 V - Estrella trifásica - 60 Hz
Nodo de
potencia
Corriente
máxima del
disyuntor
Rango de cable con
lengüeta
Corriente
máxima del
disyuntor
Rango de cable con
lengüeta
Corriente
máxima del
disyuntor
Rango de cable con lengüeta
Corriente
máxima del
disyuntor
Rango de cable con lengüeta
Corriente
máxima del
disyuntor
Rango de cable con lengüeta
20/25 kW 40 A Cu: n.º 14 a n.º 3 Al: n.º 12 a n.º 1 40 A Cu: n.º 14 a n.º 3 Al: n.º 12 a n.º 1 40 A Cu: n.º 14 a n.º 3 Al: n.º 12 a n.º 1
25/30 kW 50 A Cu: n.º 14 a n.º 3 Al: n.º 12 a n.º 1 50 A Cu: n.º 14 a n.º 3 Al: n.º 12 a n.º 1 50 A Cu: n.º 14 a n.º 3 Al: n.º 12 a n.º 1
29/35 kW 125 A Cu/Al: n.º 4 - 300 kcmil 110 A Cu/Al: n.º 4 - 300 kcmil 60 A Cu: n.º 14 a n.º 3 Al: n.º 12 a n.º 1 70 A Cu: n.º 6 - 2/0 Al: n.º 4 - 2/0 60 A Cu: n.º 14 a n.º 3 Al: n.º 12 a n.º 1
40/48 kW 200 A Cu/Al: n.º 4 - 300 kcmil 175 A Cu/Al: n.º 4 - 300 kcmil 100 A Cu: n.º 3 - 3/0 Al: n.º 1 - 3/0 100 A Cu: n.º 3 - 3/0 Al: n.º 1 - 3/0 90 A Cu: n.º 6 - 2/0 Al: n.º 4 - 2/0
50/60 kW 225 A Cu/Al: n.º 4 - 300 kcmil 200 A Cu/Al: n.º 4 - 300 kcmil 100 A Cu/Al: n.º 4 - 300 kcmil 125 A Cu/Al: n.º 4 - 300 kcmil 100 A Cu: n.º 3 - 3/0 Al: n.º 1 - 3/0
Aplicaciones del controlador Intelinano – Trifásica
20 BRIGGSandSTRATTON.COM
Disyuntor del generador
Voltaje - Fase
- Frecuencia
230 V - Monofásica - 50 Hz 120/240 V - Monofásica - 60 Hz 120/208 V - Estrella trifásica - 60 Hz 120/240 V - Delta trifásica - 60 Hz
Nodo de
potencia
Corriente
máxima del
disyuntor
Rango de cable con
lengüeta
Corriente
máxima del
disyuntor
Rango de cable con
lengüeta
Corriente
máxima del
disyuntor
Rango de cable con
lengüeta
Corriente
máxima del
disyuntor
Rango de cable con
lengüeta
20/25 kW 90 A 125 A Cu/Al: n.º 2 -
300 kcmil
90 A Cu: n.º 6 - 2/0 Al: n.º 4
- 2/0
80 A Cu/Al: n.º 3 - 500 kcmil
25/30 kW 125 A Cu/Al: n.º 2 -
300 kcmil
150 A Cu/Al: n.º 2 -
300 kcmil
110 A Cu: n.º 3 - 3/0 Al: n.º 1
- 3/0
90 A Cu: n.º 6 - 2/0 Al: n.º 4
- 2/0
29/35 kW 150 A Cu/Al: n.º 2 -
300 kcmil
150 A Cu/Al: n.º 2 -
300 kcmil
40/48 kW 175 A Cu/Al: n.º 2 -
300 kcmil
200 A Cu/Al: n.º 2 -
300 kcmil
50/60 kW 225 A Cu/Al: n.º 2 -
300 kcmil
300 A Cu/Al: n.º 6 -
600 kcmil
Aplicaciones del controlador Intelilite - Monofásica y trifásica
Disyuntor del generador
Voltaje
- Fase -
Frecuencia
120/240V - 1Ø - 60Hz 120/208V - 3Ø Wye - 60Hz 120/240V - 3Ø Delta - 60Hz 220/380V - 3Ø Wye - 50Hz
Nodo de
potencia
Corriente
máxima del
disyuntor
Rango de cable con
lengüeta
Corriente
máxima del
disyuntor
Rango de cable con
lengüeta
Corriente
máxima del
disyuntor
Rango de cable con
lengüeta
Corriente
máxima del
disyuntor
Rango de cable con
lengüeta
20/25kW 150A Cu/Al: #2 - 300kcmil 125A Cu/Al: #4 - 300kcmil 110A Cu/Al: #4 - 300kcmil 60A Cu: #6 - 2/0 Al: #4 - 2/0
25/30kW 225A Cu/Al: #2 - 300kcmil 200A Cu/Al: #4 - 300kcmil 175A Cu/Al: #4 - 300kcmil 100A Cu: #3 - 3/0 Al: #1 - 3/0
29/35kW 300A Cu/Al: #6 - 600kcmil 225A Cu/Al: #4 - 300kcmil 200A Cu/Al: #4 - 300kcmil 125A Cu/Al: #4 - 300kcmil
Generator Circuit Breaker
Voltaje
- Fase -
Frecuencia
240/416V - 3Ø Wye - 60Hz 277/480V - 3Ø Wye - 60Hz 347/600V - 3Ø Wye - 60Hz
Nodo de
potencia
Corriente máxima
del disyuntor
Rango de cable con
lengüeta
Corriente máxima
del disyuntor
Rango de cable con
lengüeta
Corriente
máxima del
disyuntor
Rango de cable con lengüeta
20/25kW 70A Cu: #6 - 2/0 Al: #4 - 2/0 60A Cu: #14 - #3 Al: #12 - #1 45A Cu: #14 - #3 Al: #12 - #1
25/30kW 100A Cu: #3 - 3/0 Al: #1 - 3/0 90A Cu: #6 - 2/0 Al: #4 - 2/0 70A Cu: #6 - 2/0 Al: #4 - 2/0
29/35kW 125A Cu/Al: #4 - 300kcmil 100A Cu: #3 - 3/0 Al: #1 - 3/0 90A Cu: #6 - 2/0 Al: #4 - 2/0
21
Consideraciones finales de la instalación
Inspección de la instalación
Antes de poner el generador en funcionamiento, revise las
instrucciones mientras inspecciona cuidadosamente toda
la instalación, para asegurarse de que esté completa y sea
correcta.
Sistema de suministro de combustible
Asegúrese de que todas las conexiones de tuberías de
combustible estén ajustadas, fijas y que no tengan fugas.
Asegúrese de que todas las válvulas de cierre de la línea de
combustible estén ABIERTAS y de que se disponga de la
presión de combustible adecuada.
Batería
El instalador debe suministrar e instalar una batería de
arranque que cumpla con las especificaciones indicadas a
continuación.
Especificaciones de la batería
Voltios 12 V CC
Amperios (MÍN.) 775 CCA (corriente de arranque
en frío)
Tipo AGM (separador de fibra de
vidrio absorbente)
Tamaño del
Grupo BCI
34
Instale la batería como se describe en Mantenimiento de la
batería en la sección Mantenimiento. Asegúrese de conectar
el cable NEGATIVO siempre en último lugar.
ADVERTENCIA
Las baterías almacenadas producen
hidrógeno explosivo mientras se
recargan.
Aun la menor chispa puede encender el hidrógeno y
ocasionar una explosión, que tendrá como resultado
la muerte, lesiones graves o daños en la propiedad. El
líquido de electrolito de la batería contiene ácido y es
extremadamente cáustico. El contacto con el contenido de
la batería puede provocar quemaduras químicas graves.
Las baterías presentan el riesgo de descarga eléctrica y de
corriente de cortocircuito elevada.
NO elimine una batería en el fuego. Recicle las
baterías.
NO permita que existan llamas abiertas, chispas,
fuentes de calor, ni que se enciendan cigarrillos
durante y varios minutos después de cargar una
batería.
NO abra ni destroce la batería.
Use anteojos protectores de seguridad, delantal de
goma, botas de goma y guantes de goma.
Quítese el reloj, los anillos u otros objetos metálicos.
Use herramientas con mangos aislados.
22 BRIGGSandSTRATTON.COM
Voltaje
Tabla de voltaje sin carga (60 Hz)
Fase a fase Fase a neutro
Mínimo Máximo Mínimo Máximo
Monofásico 120/240 238 242 119 121
Estrella
trifásica
120/208 206 210 119 121
Delta trifásica 120/240 238 242 119 121
Estrella
trifásica
277/480 475 485 275 279
Estrella
trifásica
347/600 594 606 344 350
Voltaje
Tabla de voltaje sin carga (50 Hz)
Fase a fase Fase a neutro
Mínimo Máximo Mínimo Máximo
Monofásico 230 228 232 N/C N/C
Estrella
trifásica
220/380 377 383 218 222
Arranque inicial (sin carga)
Antes de hacer funcionar el generador o de prepararlo
para su funcionamiento, inspeccione cuidadosamente
toda la instalación. Familiarícese con la ubicación de los
componentes y la ubicación y función del controlador del
generador. Luego, comience a probar el sistema sin cargas
eléctricas conectadas, como se indica a continuación:
1. Revise el aceite del motor. Añada aceite si es
necesario. Consulte el tipo de aceite requerido en el
manual del motor.
2. Coloque el disyuntor principal del generador en la
posición APAGADO (abierta).
3. Encienda el generador. Cuando se enciende el
generador por primera vez, se purgará el aire de
las tuberías de combustible gaseoso. Esto puede
provocar que el motor funcione bruscamente durante
unos minutos.
4. Esté atento por si escucha ruidos, vibración u otros
indicadores de funcionamiento anormal. Revise en
busca de fugas de aceite o de refrigerante mientras
funciona el motor.
5. Deje que el motor se caliente durante 5 minutos.
6. Revise la salida del generador en el lado de línea
del disyuntor. El voltaje sin carga debe ser como se
muestra en la siguiente tabla.
La frecuencia debe ser de 59,8 a 60,2 Hz para las
aplicaciones de 60 Hz.
La frecuencia debe ser de 49,8 a 50,2 Hz para las
aplicaciones de 50 Hz.
NOTA
Si el voltaje sin carga está fuera del rango
especificado, realice el ajuste automático del
regulador de voltaje (AVR) en el Paso 8. No continúe
hasta que el voltaje de CA esté dentro de los
márgenes especificados.
7. Controle la salida del voltaje entre cada una de las
orejetas de conexión del disyuntor y la orejeta neutra.
El voltaje sin carga debe ser como se muestra en la
siguiente tabla.
8. Si es necesario, ajuste el control de voltaje AVR (A)
para obtener el rango especificado. NO ajuste ningún
otro control del alternador.
9. Asegúrese de que el switch de transferencia esté en la
posición “SERVICIO”
y de que no haya carga presente en el
generador.
10. Coloque el disyuntor principal del generador en la
posición ENCENDIDO (cerrada).
11. Detenga el generador.
A
23
Características y controles
Paneles de acceso
A - Puerto de entrada de combustible
B - Puertas del controlador
C - Abertura de escape
D - Puerta de llenado de refrigerante
E - Puerta de la batería
F - Puerta del silenciador
Cada generador se envía con un juego de llaves idénticas.
Estas llaves pertenecen a las cerraduras que cierran las
puertas de acceso.
Todas las puertas deben cerrarse siempre que la unidad
esté funcionando para asegurar un funcionamiento correcto
y seguro.
B
A
C
D
E
F
24 BRIGGSandSTRATTON.COM
Ubicaciones de los componentes
Compare las ilustraciones siguientes con su generador para familiarizarse con las ubicaciones de los diversos componentes
de la unidad.
D - Entrada de combustible: el suministro de combustible
se conecta aquí.
E - Etiqueta de datos del generador: identifica el modelo
y el número de serie del generador.
F - Caja del disyuntor: equipada con una parte inferior
desmontable para ayudar en la conexión de conductos.
G - Controlador: se utiliza para distintas funciones de
prueba, funcionamiento y mantenimiento.
E
Con fines de claridad, el generador se muestra sin el techo y
las puertas de acceso.
A - Filtro de aire: protege el motor filtrando el polvo y los
desechos del aire de admisión.
B - Protección de malla: evita que los dedos toquen
el ventilador del radiador y alberga la botella de
recuperación de refrigerante. Debe estar cerrada
mientras el generador está en uso.
C - Botella de recuperación de refrigerante: se ubica en
la parte interna de la protección de malla. Proporciona
un indicador visual del nivel de refrigerante del motor.
A
B
C
A
D
F
G
25
Filtro de aire del motor
1. Detenga el generador.
2. Desconecte el cable negativo ( - ) de la batería.
3. Retire el cartucho del filtro.
4. Limpie el tubo de salida y revise la válvula del
descargador de polvo (si está equipada): use un paño
limpio para limpiar la superficie de sellado del filtro
y las superficies del tubo de salida. Asegúrese de
eliminar todos los contaminantes antes de insertar un
filtro nuevo. Tenga cuidado de no dañar el área de
sellado del tubo.
Revise y apriete la válvula del descargador de polvo,
unida a la tapa de servicio, para asegurarse de que es
flexible y que no está invertida, dañada u obstruida.
5. Limpie el filtro: use un cepillo de cerdas suaves para
aflojar la suciedad y una aspiradora para quitar la
suciedad y los residuos. Cambie los cartuchos del filtro
si se detectan orificios en el medio de filtración.
6. Instale el filtro limpio correctamente: inserte el filtro con
cuidado. Coloque el filtro con la mano y asegúrese de
que esté completamente dentro de la carcasa del filtro
de aire antes de fijar la cubierta en su lugar.
7. Vuelva a instalar la tapa del panel de servicio.
Asegúrese de que todas las bandas de montaje, las
abrazaderas, los pernos y las conexiones de todo el
sistema de filtro de aire estén ajustadas y controle
que las tuberías no tengan orificios. Repare de ser
necesario.
8. Conecte el cable negativo ( - ) de la batería.
9. Ajuste el modo del generador en AUTOMÁTICO.
Limpieza del generador
Limpie la unidad si advierte la presencia de polvo, suciedad,
aceite, humedad u otras sustancias extrañas en las
superficies interiores y exteriores. Las entradas y salidas
de aire de la caja no deben obstruirse con nieve, hojas
o cualquier otro material extraño. Para evitar daños en el
generador causados por el sobrecalentamiento, mantenga
siempre limpias y sin obstrucciones las entradas y salidas
de aire de la caja.
AVISO NO rocíe directamente con una manguera de jardín
para limpiar el generador. El agua puede ingresar en el
motor y en el generador y ocasionar problemas.
1. Detenga el generador.
2. Desconecte el cable negativo ( - ) de la batería.
3. Limpie el generador de la siguiente manera:
Use un paño húmedo para limpiar las superficies
exteriores.
Use un cepillo de cerda suave y una aspiradora para
aflojar y recoger la suciedad y los residuos.
Use aire a baja presión (no más de 25 psi) para soplar
la suciedad.
Limpie las entradas y salidas de aire que tengan
presencia de nieve, hojas o desechos.Para evitar
daños generados por el sobrecalentamiento, estas
aberturas deben mantenerse sin obstrucciones.
4. Conecte el cable negativo ( - ) de la batería.
5. Ajuste el modo del generador en AUTOMÁTICO.
Mantenimiento
26 BRIGGSandSTRATTON.COM
Mantenimiento del sistema eléctrico
Cableado y conexiones
El sistema eléctrico del generador incorpora computadoras
para controlar diversos componentes relacionados. Las
conexiones del sistema eléctrico y los circuitos de conexión
a tierra necesitan buenas conexiones. Cuando inspeccione
el sistema eléctrico, revise lo siguiente:
Revise si los cables positivo (+) y negativo (-) de la
batería tienen daños por corrosión, fricción, desgaste,
quemaduras y asegúrese de que las conexiones estén
ajustadas en ambos extremos.
Revise si hay grietas o daños en la caja de la batería.
Reemplace según sea necesario.
Inspeccione el cableado del motor para ver si tiene
daños por fricción, desgaste, pinzado, quemaduras y
grietas o cortes.
Verifique que los conectores del cableado del motor
estén correctamente fijados.
Inspeccione el cable de la bobina de ignición para ver
si tiene endurecimiento, grietas, desgaste por fricción,
quemaduras, separación y fundas divididas.
Inspeccione el cable de la bujía para ver si tiene
endurecimiento, grietas, desgaste por fricción,
quemaduras, separación y fundas divididas.
Cambie las bujías según los intervalos que se indican
en la tabla de mantenimiento.
Verifique que todos los componentes eléctricos estén
firmemente montados en el motor o en el chasis.
Verifique que todos los servicios eléctricos adicionales
instalados por el propietario, estén correctamente
instalados en el sistema.
Reemplazo de la batería
1. Detenga el generador.
2. Desconecte el cable negativo ( - ) de la batería.
3. Desconecte el cable positivo ( + ) de la batería.
4. Retire la batería e instale la batería de repuesto.
5. Conecte el cable positivo ( + ) de la batería.
6. Conecte el cable negativo ( - ) de la batería.
7. Asegúrese de que las piezas metálicas de los
terminales positivo y negativo de la batería estén fijas.
8. Ajuste el modo del generador en AUTOMÁTICO.
Carga de la batería
1. Detenga el generador.
2. Desconecte el cable negativo ( - ) de la batería.
3. Desconecte el cable positivo ( + ) de la batería.
4. Conecte el cargador en la batería. Cargue la batería a
2 amperios, hasta que la batería contenga 12 voltios.
NO exceda los 13,7 voltios durante la carga de la
batería.
5. Conecte el cable positivo ( + ) de la batería.
6. Conecte el cable negativo ( - ) de la batería.
7. Asegúrese de que las piezas metálicas de los
terminales positivo y negativo de la batería estén fijas.
8. Ajuste el modo del generador en AUTOMÁTICO.
Mantenimiento del sistema de escape
Cuando inspeccione el sistema de escape, revise lo
siguiente:
Inspeccione si hay fugas en el colector de escape en el
cabezal del cilindro.
Compruebe que todos los pernos de retención y
protecciones (si se usan) estén en su lugar.
Inspeccione los sujetadores entre el colector y la
tubería de escape para garantizar que estén ajustados
y que no haya fugas en el escape. Repare según sea
necesario.
Inspeccione el conector eléctrico del sensor de
oxígeno para garantizar que esté asentado y
bloqueado. Revise los cables para garantizar que
no tengan grietas, fisuras, desgaste por fricción
ni quemaduras. Reemplace o repare según sea
necesario.
Inspeccione si hay fugas en la conexión del tubo de
escape. Repare según sea necesario.
NO CONTAMINE. CONSERVE LOS RECURSOS.
DEVUELVA LAS BATERÍAS USADAS A UN
CENTRO DE RECOLECCIÓN Y RECICLAJE.
27
Solución de problemas
Problema Causa Corrección
El motor funciona, pero no hay salida
de CA disponible.
1. El disyuntor está abierto o
defectuoso.
2. El control del generador presenta
fallas.
3. Conexiones de cableado deficientes
o switch de transferencia defectuoso.
1. Restablezca o reemplace el disyuntor.
2. Comuníquese con el establecimiento
de servicio local.
3. Revise y repare.
El motor funciona bien sin carga,
pero se atasca cuando se conectan
las cargas.
1. Existe un cortocircuito en una carga
conectada.
2. El generador está sobrecargado.
3. El circuito del generador tiene un
cortocircuito.
4. La presión o mezcla del combustible
es incorrecta.
1. Desconecte la carga eléctrica
cortocircuitada.
2. Apague una o más cargas.
3. Comuníquese con el establecimiento
de servicio local.
4. Consulte la sección Planificación de la
instalación de combustible.
El motor no arranca.
El motor arranca, pero tiene un
funcionamiento forzado.
1. Se apagó o se acabó el suministro
de combustible.
2. La batería tiene fallas.
3. La presión de combustible es
incorrecta.
1. Revise las válvulas de combustible.
Revise el suministro de combustible
2. Cambie la batería.
3. Consulte la sección Planificación de la
instalación de combustible.
El motor se apaga durante el
funcionamiento.
1. Se apagó o se acabó el suministro
de combustible.
1. Revise las válvulas de combustible;
revise el suministro de combustible.
Pérdida de energía en los circuitos.
1. El disyuntor del generador está
abierto.
2. El interruptor de transferencia tiene
problemas.
1. Restablezca el disyuntor.
2. Consulte el manual de la llave de
transferencia.
28 BRIGGSandSTRATTON.COM
Especificaciones del generador (60 Hz y 50 Hz)
Este generador está clasificado conforme a la norma UL (Underwriters Laboratories) 2200 (grupos generadores de motor fijo)
y a la norma CSA (Canadian Standards Association) C22.2 n.º 100-14 (motores y generadores).
Serie 29000 Voltaje
Amperios
nominales *
Frecuencia
Intervalo de
funcionamiento ambiental
Nivel de sonido
de salida ^
Peso con embalaje
Monofásico 230 126
50 Hz
-20 °F (-28 °C)
a 104 °F (40 °C)
60 dB (3,0 l)
66 dB (4,3 l)
1831 lb
(831 kg) (3,0 l)
2033 lb
(922 kg) (4,3 l)
Monofásico 120/240 120
Estrella trifásica 115/200 104
Estrella trifásica 220/380 55
Estrella trifásica 230/400 52
Estrella trifásica 240/416 50
Serie 35000 Voltaje
Amperios
nominales *
Frecuencia
Intervalo de
funcionamiento ambiental
Nivel de sonido
de salida ^
Peso con embalaje
Monofásico 120/240 145
60 Hz
-20 °F (-28 °C)
a 104 °F (40 °C)
61 dB (3,0 l)
68 dB (4,3 l)
1831 lb
(831 kg) (3,0 l)
2033 lb
(922 kg) (4,3 l)
Estrella trifásica 120/208 121
Delta trifásica 120/240 105
Estrella trifásica 240/416 61
Estrella trifásica 277/480 53
Estrella trifásica 347/600 42
Serie 40000 Voltaje
Amperios
nominales *
Frecuencia
Intervalo de
funcionamiento ambiental
Nivel de sonido
de salida ^
Peso con embalaje
Monofásico 230 174
50 Hz
-20 °F (-28 °C)
a 104 °F (40 °C)
66 dB
2033 lb
(922 kg)
Monofásico 120/240 166
Estrella trifásica 115/200 144
Estrella trifásica 220/380 76
Estrella trifásica 230/400 72
Estrella trifásica 240/416 69
Serie 48000 Voltaje
Amperios
nominales *
Frecuencia
Intervalo de
funcionamiento ambiental
Nivel de sonido
de salida ^
Peso con embalaje
Monofásico 120/240 200
60 Hz
-20 °F (-28 °C)
a 104 °F (40 °C)
68 dB
2033 lb
(922 kg)
Estrella trifásica 120/208 167
Delta trifásica 120/240 144
Estrella trifásica 240/416 83
Estrella trifásica 277/480 72
Estrella trifásica 347/600 58
Serie 50000 Voltaje
Amperios
nominales *
Frecuencia
Intervalo de
funcionamiento ambiental
Nivel de sonido
de salida ^
Peso con embalaje
Monofásico 230 217
50 Hz
-20 °F (-28 °C)
a 104 °F (40 °C)
67 dB
2419 lb
(1097 kg)
Monofásico 120/240 208
Estrella trifásica 220/380 95
Estrella trifásica 230/400 90
Estrella trifásica 240/416 87
Serie 60000 Voltaje
Amperios
nominales *
Frecuencia
Intervalo de
funcionamiento ambiental
Nivel de sonido
de salida ^
Peso con embalaje
Monofásico 120/240 250
60 Hz
-20 °F (-28 °C)
a 104 °F (40 °C)
70 dB
2419 lb
(1097 kg)
Estrella trifásica 120/208 215
Delta trifásica 120/240 186
Estrella trifásica 240/416 108
Estrella trifásica 277/480 93
Estrella trifásica 347/600 75
* La clasificación del gas natural dependerá del combustible específico, sin embargo, la reducción típica está entre un 10 y un 20 %
menos que el propano.
^ Según ISO 3744. Micrófono más bajo a 23 pies (7 m) sin carga.
29
Diagramas de cableado
Los diagramas del cableado empiezan en la siguiente página.
48 BRIGGSandSTRATTON.COM
Esta página se dejó intencionalmente en blanco.

Transcripción de documentos

Fuel Consumption (50Hz) Shown below are the estimated fuel supply requirements. Fuel Consumption (60Hz) Shown below are the estimated fuel supply requirements. Series 29000 (3.0L) LP Vapor Fuel Consumption Full Load 365000 BTU/hr 146 ft³/hr m³/hr Gal/hr (liquid) 4.2 4.0 1/2 Load 230000 Exercise 70000 92 28 2.6 0.8 2.6 0.8 Series 35000 (3.0L) LP Vapor Fuel Consumption Full Load 1/2 Load Exercise 286 179 89 286000 ft³/hr 8.1 m³/hr 179000 89000 5.1 2.6 Full Load 1/2 Load Exercise 140 90 43 349000 ft³/hr m³/hr Gal/hr (liquid) 4.0 3.9 225000 106000 2.6 1.2 2.5 1.2 Gal/hr (liquid) 1/2 Load Exercise 356 222 120 356000 BTU/hr ft³/hr 10.1 m³/hr 222000 120000 6.3 3.4 1/2 Load Exercise 273 188 74 682500 BTU/hr ft³/hr m³/hr Gal/hr (liquid) 7.7 7.5 470000 183750 5.3 2.1 5.1 2.0 ft³/hr 1/2 Load Exercise 428 256 118 428000 BTU/hr ft³/hr 12.2 m³/hr 256000 118000 7.3 3.4 Exercise 292 200 80 729000 BTU/hr ft³/hr m³/hr 1/2 Load Gal/hr (liquid) 8.3 8.0 500000 198000 5.7 2.3 5.5 2.2 BTU/hr ft³/hr m³/hr 16 1/2 Load Exercise 669 462 213 669000 19.0 462000 13.1 213000 6.1 130000 97 52 2.8 1.5 2.7 1.5 1/2 Load Exercise 336 215 108 215000 108000 6.1 Full Load 1/2 Load 164 105 409000 BTU/hr ft³/hr m³/hr Gal/hr (liquid) 3.1 4.7 4.5 262000 Exercise 137000 55 3.0 1.6 2.9 1.5 Series 35000 (4.3L) NG Fuel Consumption Full Load 1/2 Load Exercise 405 258 146 405000 BTU/hr ft³/hr 11.5 m³/hr 258000 146000 7.3 4.2 Series 48000 (4.3L) LP Vapor Fuel Consumption Full Load 1/2 Load 214 135 533000 BTU/hr ft³/hr m³/hr Gal/hr (liquid) 6.1 5.9 337000 Exercise 165000 66 3.9 1.9 3.7 1.9 Series 48000 (4.3L) NG Fuel Consumption Full Load 1/2 Load Exercise 511 328 181 511000 BTU/hr ft³/hr 14.5 m³/hr 328000 181000 9.3 5.2 Series 60000 (5.7L) LP Vapor Fuel Consumption ft³/hr m³/hr Full Load 1/2 Load Exercise 350 258 106 875000 BTU/hr Gal/hr (liquid) Series 50000 (5.7L) NG Fuel Consumption Full Load Exercise Series 35000 (4.3L) LP Vapor Fuel Consumption Series 50000 (5.7L) LP Vapor Fuel Consumption Full Load 241000 Full Load 9.5 m³/hr Series 40000 (4.3L) NG Fuel Consumption Full Load 4.1 336000 BTU/hr Series 40000 (4.3L) LP Vapor Fuel Consumption Full Load 4.2 1/2 Load Series 35000 (3.0L) NG Fuel Consumption Series 29000 (4.3L) NG Fuel Consumption Full Load 149 m³/hr Series 29000 (4.3L) LP Vapor Fuel Consumption BTU/hr 371000 ft³/hr Series 29000 (3.0L) NG Fuel Consumption BTU/hr Full Load BTU/hr 10.0 9.6 644000 264000 7.3 3.0 7.1 2.9 Series 60000 (5.7L) NG Fuel Consumption BTU/hr ft³/hr m³/hr Full Load 1/2 Load Exercise 753 561 264 753000 21.4 561000 15.9 264000 7.5 BRIGGSandSTRATTON.COM Manual de instalación y operación 29 kW 40 kW 50 kW (50 Hz) 35 kW 48 kW 60 kW (60 Hz) Generador de reserva monofásico y trifásico Sistema de generador de energía de emergencia enfriado por líquido Este generador está clasificado conforme a la norma UL (Underwriters Laboratories) 2200 (grupos generadores de motor fijo) y a la norma CSA (Canadian Standards Association) C22.2 n.º 100-14 (motores y generadores). © Briggs & Stratton, LLC. Todos los derechos reservados. 80022439USCN Revisión F Gracias por comprar este generador Briggs & Stratton® de alta calidad. Nos complace que haya depositado su confianza en la marca Briggs & Stratton. Si se utiliza y mantiene de acuerdo con las instrucciones de este manual, el generador le proporcionará muchos años de funcionamiento fiable. Este manual contiene información de seguridad para alertarlo sobre los peligros y riesgos asociados con los generadores de energía de emergencia, y para indicarle cómo evitarlos. Guarde estas instrucciones para futuras consultas. Este generador requiere una instalación profesional antes de su uso. El instalador debe seguir completamente las instrucciones. Dónde puede encontrarnos Nunca deberá buscar demasiado para encontrar asistencia y servicio para su generador. Consulte las Páginas Amarillas. Existen muchos distribuidores de servicio autorizados en todo el mundo, que ofrecen asistencia de calidad. También puede comunicarse con Servicio Técnico por teléfono al 800-732-2989 entre las 8:00 a. m. y las 5:00 p. m. hora del Centro, o bien, puede hacer clic en Dealer Locator en www. briggsandstrattom.com, donde obtendrá una lista de distribuidores autorizados. Para futuras consultas Complete la siguiente información y manténgala con su recibo. Tenga esta información a mano, en caso que deba comunicarse con su instalador o distribuidor autorizado con respecto al mantenimiento o a reparaciones de la unidad. FECHA DE COMPRA GENERADOR Número de modelo Modificación del modelo Número de serie MOTOR Número de modelo Número de serie ADVERTENCIA Este producto puede exponerlo a sustancias 2 químicas entre las que se incluyen aceite de motor, reconocidas por el Estado de California como causantes de cáncer; y monóxido de carbono, reconocido por el Estado de California como causante de defectos de nacimiento u otros problemas reproductivos. Para obtener más información, visite www.P65Warnings.ca.gov. BRIGGSandSTRATTON.COM Table Of Contents Instrucciones de seguridad importantes . . . . . . . . . . . 4 Información general . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Descripción del equipo . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Antes de la instalación . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Responsabilidades del instalador . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Responsabilidades del propietario . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Factores de instalación que se deben considerar . . . . . . . . . . . . . . . 8 Inspección de entrega . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Consideraciones para la ubicación del generador . . . . . . . . . . . . . . 8 La ubicación física real del generador tiene un efecto directo en lo siguiente: 8 Instalación . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 PARA REDUCIR EL RIESGO DE ENVENENAMIENTO POR MONÓXIDO DE CARBONO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Generador de energía de emergencia . . . . . . . . . . . . . . . . . . . . . . . 10 PARA REDUCIR EL RIESGO DE INCENDIO . . . . . . . . . . . . . . . . . 11 Otros requisitos de ubicación . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Ubicaciones de las entradas eléctrica y de combustible . . . . . . . . 12 Losa de hormigón . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Elevación del generador . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Planificación de la instalación de combustible . . . . . 14 Tamaño de las tuberías de combustible . . . . . . . . . . . . . . . . . . . . . . Tipo de combustible que se debe usar . . . . . . . . . . . . . . . . . . . . . . . Conversión de combustible . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Presión de combustible . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pérdida de potencia . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Consumo de combustible (50 Hz) . . . . . . . . . . . . . . . . . . . . . . . . . . . Consumo de combustible (60 Hz) . . . . . . . . . . . . . . . . . . . . . . . . . . . Conexiones de energía . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 15 15 15 15 16 16 17 Conexiones del cliente - Interconexión/control . . . . . 18 Aplicaciones del controlador Briggs & Stratton - Monofásica y trifásica18 Aplicaciones del controlador Intelinano – Trifásica . . . . . . . . . . . . . 19 Aplicaciones del controlador Intelilite - Monofásica y trifásica . . . . 20 Batería . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Consideraciones finales de la instalación . . . . . . . . . . . . . . . . . . . . 21 Sistema de suministro de combustible . . . . . . . . . . . . . . . . . . . . . . . 21 Arranque inicial (sin carga) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Características y controles . . . . . . . . . . . . . . . . . . . . . . 23 Paneles de acceso . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Ubicaciones de los componentes . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Mantenimiento . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Limpieza del generador . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Mantenimiento del sistema eléctrico . . . . . . . . . . . . . . . . . . . . . . . . . 26 Mantenimiento del sistema de escape . . . . . . . . . . . . . . . . . . . . . . . 26 Solución de problemas . . . . . . . . . . . . . . . . . . . . . . . . . 27 Especificaciones del generador (60 Hz y 50 Hz) . . . . 28 Diagramas de cableado . . . . . . . . . . . . . . . . . . . . . . . . . 29 35 kW a 60 kW - Monofásica, 60 Hz . . . . . . . . . . . . . . . . . . . . . . . . 29 kW a 50 kW - Monofásica, 50 Hz . . . . . . . . . . . . . . . . . . . . . . . . 29 kW a 60 kW - Trifásica, Intelinano, 50/60 Hz . . . . . . . . . . . . . . . 35 kW a 60 kW - Monofásica, Intelilite, 60 Hz . . . . . . . . . . . . . . . . . 35 kW a 60 kW - Trifásica, Intelilite, 60 Hz . . . . . . . . . . . . . . . . . . . . 35 kW a 60 kW - 600 V, Intelilite, 60 Hz . . . . . . . . . . . . . . . . . . . . . . 30 32 34 36 38 40 Esquemas del cableado . . . . . . . . . . . . . . . . . . . . . . . . . 42 Motor - 3,0 l . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 Motor - 4,3 l . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 Motor - 5,7 l . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 3 Instrucciones de seguridad importantes ADVERTENCIA Antes de utilizar este producto, lea este manual y siga todas las reglas de seguridad e instrucciones de funcionamiento. CONSERVE ESTAS INSTRUCCIONES: Este manual contiene instrucciones importantes que se deben seguir durante la instalación y el mantenimiento del generador y las baterías. Símbolos de seguridad y significados ADVERTENCIA El motor en funcionamiento emite Explosión Incendio Descarga eléctrica Gases tóxicos Piezas giratorias Superficie caliente monóxido de carbono, un gas venenoso que carece de olor y de color. La inhalación de monóxido de carbono podría ocasionar la muerte, lesiones graves, dolor de cabeza, fatiga, mareos, vómitos, confusión, convulsiones, náuseas o desmayos. • Haga funcionar este producto SOLO en el exterior, en un área donde no se acumulen los gases de escape mortales. • Arranque automático Presión explosiva Quemadura química • Piezas móviles Peligro de aplastamiento y cortes Lea el manual El símbolo de alerta de seguridad indica un posible riesgo para su integridad física. Se usa una palabra de señalización (PELIGRO, ADVERTENCIA o PRECAUCIÓN) junto con el símbolo de alerta para designar un grado o un nivel de gravedad de riesgo. Se puede utilizar un símbolo de seguridad para representar el tipo de peligro. La palabra de señalización AVISO se usa para designar prácticas no relacionadas con lesiones corporales. PELIGRO indica un riesgo que, si no se evita, ocasionará la muerte o lesiones graves. ADVERTENCIA indica un riesgo que, si no se evita, podría ocasionar la muerte o lesiones graves. PRECAUCIÓN indica un riesgo que, si no se evita, podría ocasionar lesiones menores o moderadas. AVISO hace referencia a una práctica no relacionada con una lesión física. El fabricante no puede anticipar cada circunstancia que involucre potencialmente un peligro. Por lo tanto, las advertencias incluidas en este manual, así como también las etiquetas y las calcomanías fijadas en la unidad, no son exhaustivas. Si emplea un procedimiento, un método de trabajo o una técnica de operación que el fabricante no recomienda específicamente, debe cerciorarse de que sea seguro para usted y el resto del personal. También debe asegurarse de que el procedimiento, el método de trabajo o la técnica de operación que elija no pongan en riesgo la seguridad del sistema generador. 4 Mantenga los gases de escape lejos de ventanas, puertas, tomas de ventilación, ventilaciones de sofitos, espacios de subsuelo, puertas de garajes abiertas u otras aberturas que puedan permitir que estos gases ingresen o se vean atraídos hacia estructuras o edificios posiblemente habitados. La instalación y el mantenimiento de detectores de monóxido de carbono en interiores se DEBE realizar conforme a las recomendaciones e instrucciones del fabricante. Las alarmas de humo no pueden detectar el monóxido de carbono. ADVERTENCIA Las baterías almacenadas producen hidrógeno explosivo mientras se recargan. Las chispas más pequeñas encenderán el hidrógeno y causarán una explosión, que tendrá como resultado la muerte o lesiones graves. El líquido de electrolito de la batería contiene ácido y es extremadamente cáustico. El contacto con el contenido de la batería puede provocar quemaduras químicas graves. Una batería presenta un riesgo de descarga eléctrica y alta corriente de cortocircuito. • NO elimine una batería en el fuego. Recicle las baterías. • NO permita que existan llamas abiertas, chispas, fuentes de calor, ni que se enciendan cigarrillos durante y varios minutos después de cargar una batería. • NO abra ni destroce la batería. • Use anteojos protectores de seguridad, delantal de goma, botas de goma y guantes de goma. • Quítese el reloj, los anillos u otros objetos metálicos. • Use herramientas con mangos aislados. BRIGGSandSTRATTON.COM ADVERTENCIA Los generadores producen un voltaje peligrosa. Una conexión a tierra defectuosa del generador puede provocar electrocución. No aislar el generador de la energía de la red de servicio público podría provocar la muerte o lesiones graves a los trabajadores de la red de servicio público eléctrico, debido a la alimentación inversa de la energía. • NO toque cables ni receptáculos sin aislamiento. • • • • • • • • • NO use el generador con cables eléctricos que estén desgastados, raídos, sin aislamiento o dañados de cualquier otro modo. NO manipule el generador ni los cables eléctricos si está en contacto con agua, descalzo o si sus manos o pies están mojados. Si debe trabajar cerca de una unidad mientras está funcionando, párese en una superficie seca y aislada para reducir el peligro de descarga. NO permita que personas no calificadas o niños operen o realicen mantenimiento al generador. En caso de un accidente por descarga eléctrica, corte inmediatamente la fuente de energía eléctrica y comuníquese con las autoridades locales.Evite el contacto directo con la víctima. A pesar del diseño seguro del generador, si lo opera de manera imprudente, no realiza el mantenimiento o si es descuidado, se pueden producir lesiones o la muerte. Permanezca alerta en todo momento mientras trabaja en el equipo. Nunca trabaje en los equipos cuando esté mental o físicamente fatigado. Antes de realizar cualquier mantenimiento en el generador, detenga el generador y desconecte el cable negativo (-) de la batería. Después de instalar el sistema, el generador puede arrancar sin advertencia cada vez que se produzca un corte de energía. ADVERTENCIA Voltaje peligroso: el contacto con los cables eléctricos podría provocar electrocución y quemaduras que pueden provocar lesiones graves o la muerte. • • • Si se utilizan equipos de elevación o izado con polipasto, NO toque las líneas de alta tensión. NO levante ni mueva el generador sin ayuda. NO levante la unidad por el techo, ya que ocurrirán daños en el generador. ADVERTENCIA El combustible y sus vapores son • • • • • • extremadamente inflamables y explosivos, lo que podría causar quemaduras, incendios o explosiones que conlleven la muerte o lesiones graves. Instale el suministro de combustible conforme a la norma NFPA 37 y otros códigos de gas combustible pertinentes. Antes de poner en servicio el generador, las tuberías del sistema de combustible se deben purgar y someter a pruebas de detección de fugas adecuadamente. Una vez instalado el generador, debe inspeccionar el sistema de combustible en forma periódica. NO se deben permitir fugas. NO opere el motor si detecta olor a combustible u otras condiciones explosivas. NO fume cerca del generador. Limpie inmediatamente los derrames de aceite con un trapo. Asegúrese de que no haya materiales combustibles en el compartimiento del generador. Mantenga el área alrededor del generador limpia y sin residuos. ADVERTENCIA Los gases y el calor de escape pueden inflamar los materiales combustibles y las estructuras, lo que podría provocar la muerte o lesiones graves. El contacto con el área del mofle podría provocar quemaduras y causar lesiones graves. • NO toque las piezas calientes y EVITE los gases de escape calientes. • Deje que el equipo se enfríe antes de tocarlo. • El lado de la salida de escape de la caja impermeable debe tener un espacio libre de al menos 5 pies (1,5 m) desde cualquier estructura, arbustos, árboles o cualquier tipo de vegetación. • La caja impermeable del generador de energía de emergencia debe estar a una distancia mínima de 5 pies (1,5 m) desde ventanas, puertas, aberturas en paredes, arbustos o vegetación de más de 12 pulgadas (30,5 cm) de altura. • La caja impermeable del generador de energía de emergencia debe tener un espacio libre superior a 5 pies (1,5 m) como mínimo desde cualquier estructura, elemento colgante o árboles. • NO coloque la caja impermeable debajo de una cubierta u otro tipo de estructura que pueda encerrar el flujo de aire. • La instalación y el mantenimiento de detectores de humo en interiores se DEBE realizar conforme a las recomendaciones e instrucciones del fabricante. Las alarmas de monóxido de carbono no pueden detectar el humo. • Mantenga por lo menos las distancias mínimas que se muestran en las Pautas generales de ubicación para garantizar la refrigeración del generador y el espacio libre para mantenimiento adecuados. • Las piezas de repuesto deben ser iguales y se deben instalar en la misma posición que las piezas originales. 5 ADVERTENCIA Las partes móviles podrían aplastar y cortar. El arrancador y otras piezas giratorias podrían apretar las manos, el cabello, la ropa o los accesorios y causar lesiones graves. • • • • NUNCA opere el generador sin carcasas de protección, cubiertas o protecciones en su lugar. NO use ropa suelta, joyas o cualquier cosa que se pueda quedar atrapada en el arrancador o en otras piezas giratorias. Recoja el cabello largo y quítese cualquier joya. Antes de realizar el mantenimiento, detenga siempre el generador y desconecte el cable negativo (-) de la batería. PRECAUCIÓN Las velocidades operativas extremadamente altas pueden provocar lesiones leves o dañar el generador. Las velocidades excesivamente bajas imponen una pesada carga en el generador. • NO manipule la velocidad de régimen. El generador suministra la frecuencia y el voltaje nominales correctos cuando funciona a la velocidad de régimen. • NO modifique el generador de ninguna forma. AVISO Exceder la capacidad de vatios o amperios del generador podría dañar el generador o los dispositivos eléctricos conectados a este.Arranque el generador y permita que el motor se estabilice antes de conectar las cargas eléctricas. AVISO El tratamiento inadecuado del generador podría estropearlo y acortar su vida útil. • Utilice el generador solo para sus usos previstos. • • • • • • • • • • • 6 Si tiene dudas acerca de los usos previstos, comuníquese con un distribuidor autorizado. Haga funcionar el generador solamente sobre superficies niveladas. Para el funcionamiento correcto del generador, es fundamental contar con una circulación de aire de ventilación y refrigeración adecuada y sin obstrucciones. Las puertas y los paneles de acceso deben estar instalados siempre que la unidad esté en funcionamiento. NO exponga el generador a un ambiente con exceso de humedad, polvo, suciedad o vapores corrosivos. Permanezca alerta en todo momento mientras trabaja en el equipo. Nunca trabaje en los equipos cuando esté mental o físicamente fatigado. NO arranque el motor si se quitó el filtro de aire o la cubierta de este. NO inserte ningún objeto por las ranuras de refrigeración. NO use el generador ni ninguna de sus piezas como un peldaño. Pararse sobre la unidad podría provocar tensión y romper las piezas. Esto puede generar condiciones de funcionamiento peligrosas, como por ejemplo, fuga de gases de escape, fugas de combustible, fugas de aceite, etc. Si los dispositivos conectados se sobrecalientan, apáguelos y desconéctelos del generador. Apague el generador en los siguientes casos: -si pierde potencia eléctrica; -si el equipo produce chispas o humo, o emite llamas; -si la unidad vibra en exceso. BRIGGSandSTRATTON.COM Información general En el caso de la mayoría de las aplicaciones, el Manual de instalación y operación incluye toda la información necesaria para instalar, operar el generador y realizarle el mantenimiento de manera adecuada. Se ha hecho todo lo posible para garantizar que la información contenida en este manual sea precisa y actual. Sin embargo, nos reservamos el derecho de realizar cambios, alterar o mejorar el producto y este documento, en cualquier momento sin previo aviso. Asegúrese de que este manual se le haya proporcionado al propietario después de completar la instalación. Descripción del equipo Este producto solo se debe usar como un sistema generador opcional, para proporcionar una fuente alternativa de energía eléctrica y abastecer cargas como por ejemplo de sistemas de calefacción, refrigeración y de comunicación que, cuando se detienen durante un corte de energía, pueden generar incomodidades o inconvenientes. AVISO Solo los modelos equipados con el controlador DSE7310 o ComAp Intelilite pueden calificar para un sistema de emergencia legalmente exigido, conforme a lo definido en la norma NFPA 70 (NEC). Para ver la información completa acerca de estos tipos de instalaciones, consulte NFPA 70 y NFPA 110. • Los sistemas de generador de energía de emergencia legalmente exigidos están diseñados para suministrar automáticamente energía para cargas seleccionadas, en el caso de falla de la fuente normal, que podría generar peligros u obstaculizar operaciones de rescate o combate de incendios. Responsabilidades del instalador • Lea y respete las instrucciones de seguridad. • Lea y siga las instrucciones que se entregan en el Manual de instalación y operación. • • • Instale solo un interruptor de transferencia aprobado por UL que sea compatible con el generador. Las instalaciones deben cumplir estrictamente todos los reglamentos, las leyes, los estándares industriales y los códigos pertinentes. Deje suficiente espacio en todos los lados del generador para realizar mantenimiento. Responsabilidades del propietario • • • • Lea y siga las instrucciones que se entregan en el Manual de instalación y operación. Siga un programa regular para el mantenimiento y uso del generador, según se especifica en este manual. La instalación y el mantenimiento de detectores de monóxido de carbono en interiores se DEBE realizar conforme a las recomendaciones e instrucciones del fabricante. Las alarmas de humo no pueden detectar el monóxido de carbono. La instalación y el mantenimiento de detectores de humo en interiores se DEBE realizar conforme a las recomendaciones e instrucciones del fabricante. Las alarmas de monóxido de carbono no pueden detectar el humo. Antes de la instalación Solo electricistas y plomeros profesionales con licencia actualizada deben realizar las instalaciones del generador. Las instalaciones deben cumplir estrictamente todos los reglamentos, las leyes, los estándares industriales y los códigos pertinentes. En algunas áreas, es posible que deba conseguir permisos eléctricos para instalar el generador, permisos de construcción para instalar tuberías de gas y permisos para tolerancias de ruidos. El instalador debe revisar los códigos locales y obtener los permisos antes de instalar el sistema. La garantía del generador se ANULARÁ salvo que profesionales de plomería y electricidad con licencia instalen el sistema. 7 Factores de instalación que se deben considerar Las ilustraciones que se muestran en este manual son para circunstancias típicas. Tienen la intención de que se familiarice con las opciones de instalación disponibles para el generador. Los códigos locales y federales, la apariencia, los niveles de ruido, los tipos de combustible y las distancias son factores de instalación que se deben considerar. Recuerde que a medida que aumenta la distancia desde el servicio eléctrico y el suministro de combustible gaseoso existente, y que aumenta la cantidad de curvas en el suministro de combustible, se deben realizar compensaciones en los materiales de cableado y tuberías. Lo anterior es necesario para cumplir los códigos locales y superar las caídas de voltaje eléctrico y las caídas de presión del combustible gaseoso. Los factores antes mencionados tienen un efecto directo en el precio general de la instalación del generador. Consideraciones para la ubicación del generador La ubicación física real del generador tiene un efecto directo en lo siguiente: 1. La cantidad de plomería que se requiere para abastecer de combustible el generador. 2. La cantidad de cableado que se requiere para controlar y conectar el generador. 3. La seguridad de la instalación con respecto a los peligros del monóxido de carbono y el gas de escape, los peligros de incendio, la proximidad a otros servicios públicos y la exposición a los elementos del clima. Las pautas específicas de ubicación se analizan en la siguiente sección. El propietario y el instalador se deben consultar entre sí para determinar cómo el lugar puede afectar los costos de instalación y el cumplimiento con los códigos y normas locales. Inspección de entrega Evite los daños por caídas, golpes o colisiones con la caja de envío. Inspeccione cuidadosamente si el generador presenta daños que puedan haber ocurrido durante el envío. Si se detectan daños o pérdidas al momento de la entrega, pida a la persona encargada de la entrega que tome nota de todos los daños en la factura de flete y ponga su firma en el memorándum de pérdidas y daños del expedidor. Si se detectan daños o pérdidas después de la entrega, separe los materiales dañados y comuníquese con la empresa de transporte para realizar los procedimientos de reclamación. Las piezas dañadas o faltantes no tienen garantía. El sistema de generador de energía de emergencia se proporciona con: • Sistema de enfriamiento con mantenimiento completo • • • • • Sistema de aceite o lubricación con mantenimiento completo Manguera de conexión flexible para combustible Manual de instalación y operación Llaves de repuesto de la puerta de acceso Pintura de retoque No se proporciona lo siguiente: • Detectores de monóxido de carbono • Detectores de humo • Losa de hormigón reforzado • • • • • • 8 Batería de arranque Conducto y cable de conexión Tuberías y válvulas de suministro de combustible Grúa, cables, cadenas o correas de levantamiento, barra separadora Medidor de voltaje y frecuencia Diversas herramientas o equipos especiales BRIGGSandSTRATTON.COM Instalación Antes de decidir acerca de la ubicación final del generador, el propietario e instalador deben analizar y comprender las distintas pautas de ubicación. Hay dos inquietudes de seguridad fundamentales que se deben tratar: el envenenamiento por monóxido de carbono y el riesgo de incendio, de la siguiente manera: ADVERTENCIA El motor en funcionamiento emite monóxido de carbono, un gas venenoso que carece de olor y de color. La inhalación de monóxido de carbono podría ocasionar la muerte, lesiones graves, dolor de cabeza, fatiga, mareos, vómitos, confusión, convulsiones, náuseas o desmayos. • Haga funcionar este producto SOLO en el exterior, en un área donde no se acumulen los gases de escape mortales. • Mantenga los gases de escape lejos de ventanas, puertas, tomas de ventilación, ventilaciones de sofitos, espacios de subsuelo, puertas de garajes abiertas u otras aberturas que puedan permitir que estos gases ingresen o se vean atraídos hacia estructuras o edificios posiblemente habitados. • La instalación y el mantenimiento de detectores de monóxido de carbono en interiores se DEBEN realizar conforme las recomendaciones e instrucciones del fabricante. Las alarmas de humo no pueden detectar el monóxido de carbono. ADVERTENCIA Los gases y el calor de escape pueden inflamar los materiales combustibles y las estructuras, lo que podría provocar la muerte o lesiones graves. • • • • • El lado de la salida de escape de la caja de emergencia debe estar al menos a 5 pies (1,5 m) de cualquier estructura, arbustos, árboles o cualquier tipo de vegetación. La caja de emergencia debe estar, al menos, a 5 pies (1,5 m) de ventanas, puertas, aberturas en paredes, arbustos o vegetación sobre 12 pulgadas (30,5 cm) de altura. La caja de emergencia debe tener un mínimo de distancia libre hacia arriba de 5 pies (1,5 m) con respecto a cualquier estructura, saliente o árboles. NO coloque la caja de emergencia debajo de una cubierta u otro tipo de estructura que pueda encerrar el flujo de aire. La instalación y el mantenimiento de detectores de humo en interiores se DEBE realizar conforme las recomendaciones e instrucciones del fabricante. Las alarmas de monóxido de carbono no pueden detectar el humo. PARA REDUCIR EL RIESGO DE ENVENENAMIENTO POR MONÓXIDO DE CARBONO Siga los requisitos de instalación que se indican a continuación. Las cifras a continuación indican puntos potenciales de ingreso de gas de monóxido de carbono. B B C Asegúrese de que el gas de escape del generador se mantenga alejado de: • Puertas elevadas (B, se muestra arriba) • Puertas de entrada (C, se muestra arriba) • • Ventanas (no se muestra) Otras aberturas que pueden permitir que los gases de escape ingresen o se vean atraídos hacia estructuras o edificios posiblemente habitados. 9 Todos los equipos que queman combustibles fósiles, como los generadores de energía de emergencia, contienen gas de monóxido de carbono (CO) en el escape del motor. El gas de CO es inodoro, incoloro y no tiene sabor, y es muy poco probable que una persona lo detecte hasta que se sienta debilitado. El gas de CO puede matarlo. Se necesita que lo siguiente se incluya como parte de la instalación: • Instale el generador en el exterior, en un área donde no se acumulen los gases de escape mortales. • • NO instale el generador donde los gases de escape se puedan acumular e ingresar o ser atraídos hacia estructuras o edificios posiblemente habitados. Dirija el escape del generador de energía de emergencia (A, se muestra abajo) lejos de o paralelo al edificio o la estructura. NO dirija el escape del generador hacia edificios o estructuras posiblemente habitados, ventanas, puertas, tomas de ventilación, ventilaciones de sofitos, espacios de subsuelo, puertas de garajes abiertas u otras aberturas que puedan permitir que estos gases ingresen o se vean atraídos hacia estructuras o edificios posiblemente habitados. A Generador de energía El escape del motor sale de la parte superior de la carcasa (A). • • • • 10 Las estructuras cercanas pueden estar expuestas al escape del motor de la unidad; esto se debe considerar cuando instale el generador de energía de emergencia. Por ley, muchos estados exigen un detector de monóxido de carbono (CO) completamente operativo en hogares y en otras estructuras con presencia de personas. La instalación y el mantenimiento de detectores de monóxido de carbono en interiores se DEBEN realizar conforme las recomendaciones e instrucciones del fabricante. Un monitor de CO es un dispositivo electrónico que detecta niveles peligrosos de CO. Cuando existe acumulación de CO, el monitor alerta a los ocupantes mediante el parpadeo de una luz indicadora visual y una alarma. Las alarmas de humo no pueden detectar el gas de CO. Se deben considerar las corrientes de aire y el viento cuando se determina la ubicación del generador. Coloque el generador en un área donde el viento aleje el gas de escape de cualquier edificio o estructura posiblemente habitada. NO coloque el generador de energía de emergencia en un área donde normalmente se acumulen hojas o residuos. BRIGGSandSTRATTON.COM PARA REDUCIR EL RIESGO DE INCENDIO Siga los requisitos de instalación que se indican a continuación. Las figuras a continuación muestran las distancias mínimas desde las estructuras y la vegetación para reducir el riesgo de incendio. La norma NFPA 37 de la Asociación Nacional de Protección contra Incendios (NFPA) establece los criterios para minimizar el peligro de incendio durante la instalación y el funcionamiento de motores de combustión fijos. La norma NFPA 37 limita el espacio de un generador cerrado con respecto a paredes, estructuras y materiales combustibles fuera de la caja. Los siguientes requisitos de ubicación del generador se basan en el cumplimiento de la norma NFPA 37. A A A 5 pies (1,5 m) mín. 5 pies (1,5 m) mín. Emergencia B Emergencia 5 pies (1,5 m) mín. Escape Escape 5 pies (1,5 m) mín. A B 5 pies (1,5 m) mín. A 5 pies (1,5 m) mín. Emergencia 5 pies (1,5 m) mín. A Escape Emergencia ) ,5 m s (1 ie 5p B . mín Escape 5 pies (1,5 m) mín. A B A La caja de emergencia debe estar, al menos, a 5 pies (1,5 m) de ventanas, puertas, aberturas en paredes, arbustos o vegetación sobre 12 pulgadas (30,5 cm) de altura. B El lado de la salida de escape de la caja de emergencia debe tener un espacio libre de al menos 5 pies (1,5 m) desde cualquier estructura, arbustos, árboles o cualquier tipo de vegetación. C La caja de emergencia debe tener un mínimo de distancia libre hacia arriba de 5 pies (1,5 m) con respecto a cualquier estructura, saliente o árboles. C A B A NO coloque la caja de emergencia bajo una plataforma u otro tipo de estructura cubierta que pueda restringir el flujo de aire. 11 Otros requisitos de ubicación • Coloque el generador de energía de emergencia en una ubicación preparada que esté nivelada y tenga disposiciones para el drenaje de agua. • Instale el generador de energía de emergencia en una ubicación donde la descarga de la bomba de sumidero, los tubos de bajada de canaletas para lluvia, el desagüe de techos, el riego de jardines o los rociadores de agua no inunden la unidad ni pulvericen la caja, ni que ingresen por las aberturas de entrada y salida de aire. • Instale el generador de energía de emergencia donde no afecte ni obstruya ningún de la red de servicio público (ya sea cubierto, cerrado o subterráneo), como teléfono, electricidad, combustible (gas natural o vapor de GLP), riego, aire acondicionado, cables, instalaciones sépticas, alcantarillas, pozos, etc. • Instale el generador de energía de emergencia donde las hojas, el césped, la nieve, etc. no obstruyan las aberturas de entrada y salida de aire. Si los vientos predominantes hacen volar las hojas o producen amontonamiento, puede necesitar un cortaviento para proteger la unidad. Ubicaciones de las entradas eléctrica y de combustible Se prefiere el uso de un pasamuros para el cable de alimentación a través de la losa. El conector de entrada de combustible (A) se muestra como referencia. A Losa de hormigón El generador debe estar instalado en una losa de hormigón reforzado, construida de la siguiente manera: • Resistencia de compresión a 28 días de 3000 psi (200 MPa) • Mínimo 5 pulgadas (13 cm) de grosor • Mínimo 6 pulg (15 cm) más ancha que la caja del generador en todos los lados • Refuerce la losa con barras de refuerzo n.° 6 en centros de 12 pulgadas (30,5 cm) o con tela metálica de acero calibre 8 en centros de 6 pulgadas (15 cm). • Evite colocar refuerzos en el área de pasamuros de entrada. Se necesitarán las siguientes dimensiones para ajustar el tamaño y configurar correctamente la losa. Consulte la figura a la derecha: A - Dimensiones del contenedor • 29/35 kW (3,0 l) = 82 pulg (208 cm) de largo x 37 pulg (94 cm) de ancho • 29/35 kW (4,3 l) = 88 pulg (224 cm) de largo x 37 pulg (94 cm) de ancho • 40/48 kW = 88 pulg (224 cm) de largo x 37 pulg (94 cm) de ancho • 50/60 kW = 96 pulg (244 cm) de largo x 37 pulg (94 cm) de ancho B - Orificios de montaje del generador • 29/35 kW (3,0 l) = 75,5 pulg (192 cm) de largo x 34,25 pulg (87 cm) de ancho • 29/35 kW (4,3 l) = 85 pulg (216 cm) de largo x 34,25 pulg (87 cm) de ancho • 40/48 kW = 85 pulg (216 cm) de largo x 34,25 pulg (87 cm) de ancho • 50/60 kW = 94 pulg (239 cm) de largo x 34,25 pulg (87 cm) de ancho C - Ubicación de la entrada de combustible • 29/35 kW (3,0 l) = 40,75 pulg (104 cm) • 29/35 kW (4,3 l) = 45,5 pulg (116 cm) • 40/48 kW = 45,5 pulg (116 cm) • 50/60 kW = 52 pulg (132 cm) D - Área de la entrada del pasamuros • 29/35 kW (3,0 l) = 9,25 pulg (23 cm) de largo x 5,25 pulg (13 cm) de ancho • 29/35 kW (4,3 l) = 10,5 pulg (27 cm) de largo x 6,75 pulg (17 cm) de ancho • 40/48 kW = 10,5 pulg (27 cm) de largo x 6,75 pulg (17 cm) de ancho • 50/60 kW = 6,0 pulg (15 cm) de largo x 5,25 pulg (13 cm) de ancho 12 D1 x D2 - Ubicación de la entrada del pasamuros • 29/35 kW (3,0 l) = 6,0 pulg (15 cm) x 7,75 pulg (20 cm) • 29/35 kW (4,3 l) = 8,5 pulg (22 cm) x 7,75 pulg (20 cm) • 40/48 kW = 8,5 pulg (22 cm) x 7,75 pulg (20 cm) • 50/60 kW = 16,0 pulg (41 cm) x 7,0 pulg (18 cm) BRIGGSandSTRATTON.COM Adjunte el generador a la losa en las cuatro ubicaciones de las esquinas (B) con anclas de mampostería según lo requiera el código local. D2 B Elevación del generador ADVERTENCIA Tensión peligrosa: El contacto con los cables eléctricos podría provocar electrocución y quemaduras que pueden provocar lesiones graves o la muerte. • D • • D1 NO levante ni mueva el generador sin ayuda. NO levante la unidad por el techo, ya que ocurrirán daños en el generador. B D D En todas las etapas de manipulación y traslado del generador, se deben utilizar las herramientas y los equipos adecuados y debe intervenir personal capacitado. El peso aproximado del generador se indica en la Sección de especificaciones del generador. C C B Si se utilizan equipos de elevación o izado con polipasto, NO toque las líneas de alta tensión. A E F Use los orificios de elevación (G) en la base del generador para levantar el generador sobre la plataforma de hormigón. Levante el generador de acuerdo con OSHA o la normativa local de elevación. Retoque la pintura descascarada con la pintura de retoque que se proporciona. A - Contenedor del generador de energía de emergencia B - Orificios de montaje en la base del generador C - Ubicación de la entrada de combustible D - Área de la entrada del pasamuros D1 x D2 - Ubicación de la entrada del pasamuros E - Referencia del área de salida del escape F - Referencia de la losa de concreto G 13 Planificación de la instalación de combustible La siguiente información se proporciona para ayudar a los técnicos en sistemas de combustible gaseoso para planificar las instalaciones. Los códigos estatales y locales pueden anular algunas de estas recomendaciones. Consulte con el proveedor de combustible local o con el jefe de Bomberos si necesita aclaración. • • • ADVERTENCIA El propano y el gas natural son extremadamente inflamables y explosivos, lo que podría causar quemaduras, incendios o explosiones que conlleven la muerte o lesiones graves. • • • • El gas licuado de petróleo es más pesado que el aire y se asentará en áreas bajas. El gas natural es más liviano que el aire y se acumulará en áreas altas. La chispa más leve podría encender estos combustibles y provocar una explosión. • NO encienda un cigarrillo ni fume. El propietario y el instalador deberán consultarse mutuamente para revisar cualquier cambio en el plan de instalación que pueda surgir al aplicar las siguientes pautas para la tubería de combustible. • Las tuberías deben ser de un material que cumpla con los códigos locales y federales, deben montarse rígidamente y deben estar protegidas contra la vibración. • Las tuberías deben estar protegidas de los daños físicos cuando pasen a través de canteros de flores, canteros de arbustos y otras áreas cultivadas donde se podrían producir daños. •Instale la tubería flexible de (B, a la derecha) entre el puerto de entrada de combustible del generador (A) y la tubería rígida para evitar que la expansión térmica y la contracción térmica produzcan tensión excesiva en el material de la tubería. AVISO La tubería flexible de combustible no se debe instalar de manera subterránea ni en contacto con el suelo.Toda la tubería flexible debe estar visible para inspeccionarla periódicamente. • Se debe proporcionar una unión (C) o conexión bridada corriente abajo para permitir el retiro de los controles. • Se debe instalar un puerto de prueba para el manómetro (D) para combustibles de vapor. El puerto permite la instalación temporal de un manómetro para garantizar que el motor reciba la presión de combustible correcta para funcionar de manera correcta en todo su rango operativo. Hay un manómetro digital (P/N 19495) disponible en su centro de servicio solo para combustibles de vapor. Para propano líquido, se puede utilizar cualquier instrumento de medición de presión apto para propano líquido y 350 psi. Cuando se terminan las pruebas iniciales, se retira el manómetro y se tapa el puerto. • Solo para combustibles de vapor: Cuando se sabe que se forman hidratos o hielo, se deben proteger las tuberías contra la congelación. El extremo de la tubería dura debe incluir un colector de sedimentos (E) donde no sea posible que se congele el condensado. 14 • Se deberá instalar una válvula de cierre manual, aprobada y accesible (F), como mínimo en la tubería de suministro de combustible, a una distancia de 6 pies (180 cm) del generador. Donde las condiciones locales incluyan terremotos, tornados, terrenos inestables o peligros de inundación, se deberá considerar especialmente el aumento de la resistencia y la flexibilidad de los soportes y conexiones de las tuberías. Las tuberías deben ser del tamaño correcto para mantener las presiones de suministro y el flujo de volumen necesarios en condiciones variables de carga del generador, con todos los artefactos a gas conectados al sistema de combustible que esté encendido y en funcionamiento. Use un sellador de tuberías o un compuesto para juntas aprobado para su uso con GN o PL en todos los conectores roscados, para reducir la posibilidad de fugas. Las tuberías instaladas se deben purgar y probar contra fugas, de acuerdo con los códigos y las normas pertinentes. D C B F E A A - - Entrada de combustible del generador B - Manguera de combustible flexible C - Conector de unión D - Puerto de prueba del manómetro E - Colector de sedimentos (solo combustibles de vapor) F - Válvula de cierre manual Tamaño de las tuberías de combustible Las normas NFPA 54 y 58 son recursos comunes. El instalador debe considerar la gravedad específica del gas, compensar la cantidad nominal de restricción producida por curvas y conectores, y consultar los códigos locales y federales para obtener orientación. BRIGGSandSTRATTON.COM Tipo de combustible que se debe usar Presión de combustible ADVERTENCIA El combustible es extremadamente inflamable y explosivo, lo que podría causar quemaduras, incendios o explosiones que conlleven la muerte o lesiones graves. Pérdida de potencia Una consideración importante que afecta toda la instalación es el tipo de combustible que se usa. Para garantizar el funcionamiento correcto, use combustible limpio, seco, libre de humedad o cualquier partícula especial. El uso de combustibles que estén fuera de los siguientes valores recomendados puede provocar problemas de rendimiento. • • El generador está equipado con válvulas “de cierre de gas combustible” automáticas de seguridad. NO opere el equipo si faltan las válvulas “de cierre de combustible” o si no están en funcionamiento. La presión de suministro de combustible en el puerto de entrada de combustible del generador (o puerto de prueba del vaporizador) debe ser de 7 a 11 pulgadas CA (17 a 28 mBar) a carga completa con todos los artefactos a gas encendidos y en funcionamiento. La caída máxima de presión de estático (con el motor apagado) a carga completa es de 0.5 pulgadas CA (1,3 mBar). La presión máxima con el motor APAGADO sin carga es de 13,85 pulgadas CA (34,5 mBar). La presión del combustible de propano líquido en la entrada del generador debe ser de 100 a 250 psi (690 a 1725 kPa). La potencia del motor disminuirá: • 1,5 % por cada 10 °F (5,6 °C) sobre la temperatura de 77 °F (25 °C). • 2,5 % por cada 1000 pies (305 m) sobre la altitud de 1200 pies (366 m) sobre el nivel del mar. Propiedades físicas Estado atmosférico normal Punto de ebullición en °F: Valor de calentamiento: BTU por galón (LHV neto *) BTU por galón (bruto **) BTU por pies cúbicos (gas) Conversión de combustible El motor está diseñado de fábrica para funcionar con gas natural (GN). Para convertir el motor para que funcione con propano líquido (vapor de GLP) o para cambiarlo de vuelta a GN posteriormente, siga estos pasos: 1. Abra la puerta del controlador. 2. Ubique el interruptor selector de combustible en el lado de la caja del disyuntor. 3. Mueva la llave (A, a continuación) a GLP o GN. 4. Cierre la puerta del controlador. Densidad *** Peso † Vapor de PL Gas natural -44 -259 83,340 91,547 2500 63,310 36,39 57,75 Gas 4,24 Gas 1000 2,65 *LHV (valor inferior de calentamiento) es la calificación más realista. **El valor de calentamiento bruto no considera la pérdida de calor en forma de agua durante la combustión. ***La densidad se presenta en “pies cúbicos por galón de líquido”. †El peso se presenta en “libras por galón de líquido”. A 15 Consumo de combustible (50 Hz) Consumo de combustible (60 Hz) A continuación se muestran los requisitos estimados de suministro de combustible. A continuación se muestran los requisitos estimados de suministro de combustible. Consumo de combustible de vapor de GLP (3,0 l) de la serie 29000 Carga completa BTU/h pies cúbicos/h m³/h Gal/h (líquido) 365000 146 4,2 4,0 1/2 carga 230000 92 2,6 2,6 Ejercicio 70000 28 0,8 0,8 Consumo de combustible de GN (3,0 l) de la serie 29000 BTU/h pies cúbicos/h m³/h Carga completa 1/2 carga Ejercicio 286 179 89 286000 8,1 179000 5,1 Consumo de combustible de vapor de GLP (4,3 l) de la serie 29000 BTU/h pies cúbicos/h m³/h Gal/h (líquido) Carga completa 349000 140 4,0 3,9 1/2 carga 225000 90 2,6 2,5 89000 2,6 43 1,2 1,2 Consumo de combustible de GN (4,3 l) de la serie 29000 BTU/h pies cúbicos/h m³/h Carga completa 1/2 carga Ejercicio 356 222 120 356000 10,1 222000 6,3 120000 3,4 pies cúbicos/h m³/h Gal/h (líquido) BTU/h pies cúbicos/h m³/h Gal/h (líquido) 1/2 carga Ejercicio 273 188 74 682500 7,7 7,5 470000 5,3 5,1 183750 2,1 2,0 Consumo de combustible de GN (4,3 l) de la serie 40000 BTU/h pies cúbicos/h m³/h Carga completa 428000 428 12,2 1/2 carga 256000 256 7,3 Ejercicio 118000 118 3,4 BTU/h pies cúbicos/h m³/h BTU/h pies cúbicos/h m³/h Gal/h (líquido) 1/2 carga Ejercicio 292 200 80 729000 8,3 8,0 500000 5,7 5,5 198000 2,3 2,2 Consumo de combustible de GN (5,7 l) de la serie 50000 BTU/h pies cúbicos/h m³/h 16 Carga completa 669000 669 19,0 1/2 carga Ejercicio 462 213 462000 13,1 213000 6,1 149 1/2 carga 241000 97 4,2 2,8 4,1 2,7 Ejercicio 130000 52 1,5 1,5 Carga completa 1/2 carga Ejercicio 336000 215000 108000 9,5 6,1 3,1 336 215 Consumo de combustible de vapor de GLP (4,3 l) de la serie 35000 BTU/h pies cúbicos/h m³/h Gal/h (líquido) 108 Carga completa 1/2 carga Ejercicio 164 105 55 409000 4,7 262000 3,0 4,5 2,9 137000 1,6 1,5 Consumo de combustible de GN (4,3 l) de la serie 35000 BTU/h pies cúbicos/h m³/h Carga completa 1/2 carga Ejercicio 405 258 146 405000 11,5 258000 7,3 Consumo de combustible de vapor de GLP (4,3 l) de la serie 48000 BTU/h pies cúbicos/h m³/h Gal/h (líquido) Carga completa 1/2 carga 214 135 533000 6,1 337000 3,9 5,9 3,7 146000 4,2 Ejercicio 165000 66 1,9 1,9 Consumo de combustible de GN (4,3 l) de la serie 48000 BTU/h pies cúbicos/h m³/h Consumo de combustible de vapor de GLP (5,7 l) de la serie 50000 Carga completa 371000 Consumo de combustible de GN (3,0 l) de la serie 35000 Consumo de combustible de vapor de GLP (4,3 l) de la serie 40000 Carga completa Carga completa BTU/h Ejercicio 106000 Consumo de combustible de vapor de GLP (3,0 l) de la serie 35000 Carga completa 1/2 carga Ejercicio 511 328 181 511000 14,5 328000 9,3 Consumo de combustible de vapor de GLP (5,7 l) de la serie 60000 BTU/h pies cúbicos/h m³/h Gal/h (líquido) 181000 5,2 Carga completa 1/2 carga Ejercicio 350 258 106 875000 10,0 644000 7,3 9,6 7,1 264000 3,0 2,9 Consumo de combustible de GN (5,7 l) de la serie 60000 BTU/h pies cúbicos/h m³/h Carga completa 753000 753 21,4 1/2 carga Ejercicio 561 264 561000 15,9 264000 7,5 BRIGGSandSTRATTON.COM Conexiones de energía Compare esta ilustración con su generador para familiarizarse con la ubicación de estas conexiones. C B A A A-C  onexión de energía - Conexión de energía hacia el switch de transferencia. B-C  onexión Neutra - Conectar al neutro del switch de transferencia. C-C  onexión a tierra - Conectar a tierra del switch de transferencia. Conecte el generador a tierra conforme a los códigos, las normas y los reglamentos pertinentes. Hay dos ubicaciones de orejetas de conexión a tierra (GND) en el generador. La ubicación mostrada (C, arriba) deberá ser suficiente para la mayoría de las aplicaciones. La segunda orejeta GND del generador está ubicada en el bastidor. Esta SOLO se debe usar para una varilla de conexión a tierra ubicada en el generador si lo exigen los códigos locales. Para obtener información sobre las conexiones del sistema, como el arranque remoto, las paradas de emergencia y las entradas y salidas del controlador, consulte los diagramas de conexión en las siguientes páginas. • Para la conexión de salida de potencia, utilice un cable de 167 °F (75 °C) clasificado para temperatura ambiente de 104 °F (40 °C) según las Tablas NEC 310.15(B)(16) y 310.15(B)(2)(a). • Para las conexiones del circuito de la red de servicio público, use un cable n.° 14 AWG para 600 voltios mínimo, 167 a 194 °F (75 °C a 90 °C). • Para la comunicación del switch de transferencia, use un cable con conductores de par trenzado n.º 18 AWG, de una longitud inferior a 200 pies (60 m) para 600 voltios y para 167 a 194 °F (75 °C a 90 °C). 17 Conexiones del cliente - Interconexión/control Aplicaciones del controlador Briggs & Stratton - Monofásica y trifásica Disyuntor del generador Voltaje - Fase Frecuencia Nodo de potencia 20/25 kW 230 V - Monofásica - 50 Hz Corriente máxima del disyuntor Rango de cable con lengüeta 90 A 120/240 V - Monofásica - 60 Hz Corriente máxima del disyuntor 125 A Rango de cable con lengüeta Cu/Al: n.º 2 - 300 kcmil 25/30 kW 125 A Cu/Al: n.º 2 - 300 kcmil 150 A Cu/Al: n.º 2 - 300 kcmil 29/35 kW 150 A Cu/Al: n.º 2 - 300 kcmil 150 A Cu/Al: n.º 2 - 300 kcmil 50/60 kW 225 A Cu/Al: n.º 2 - 300 kcmil 300 A Cu/Al: n.º 6 - 600 kcmil 40/48 kW 18 175 A Cu/Al: n.º 2 - 300 kcmil 200 A 120/208 V - Estrella trifásica - 60 Hz Corriente máxima del disyuntor Rango de cable con lengüeta 90 A Cu: n.º 6 - 2/0 Al: n.º 4 - 2/0 110 A Cu: n.º 3 - 3/0 Al: n.º 1 - 3/0 120/240 V - Delta trifásica - 60 Hz Corriente máxima del disyuntor Rango de cable con lengüeta 80 A Cu/Al: n.º 3 - 500 kcmil 90 A Cu: n.º 6 - 2/0 Al: n.º 4 - 2/0 Cu/Al: n.º 2 - 300 kcmil BRIGGSandSTRATTON.COM Aplicaciones del controlador Intelinano – Trifásica Voltaje - Fase Frecuencia Nodo de potencia 20/25 kW 25/30 kW Disyuntor del generador 120/208 V - Estrella trifásica - 60 Hz Corriente máxima del disyuntor Rango de cable con lengüeta 120/240 V - Delta trifásica - 60 Hz Corriente máxima del disyuntor Rango de cable con lengüeta 29/35 kW 125 A Cu/Al: n.º 4 - 300 kcmil 110 A Cu/Al: n.º 4 - 300 kcmil 50/60 kW 225 A Cu/Al: n.º 4 - 300 kcmil 200 A Cu/Al: n.º 4 - 300 kcmil 40/48 kW 200 A Cu/Al: n.º 4 - 300 kcmil 175 A Cu/Al: n.º 4 - 300 kcmil 220/380 V - Estrella trifásica - 50 Hz Corriente máxima del disyuntor Rango de cable con lengüeta 40 A Cu: n.º 14 a n.º 3 Al: n.º 12 a n.º 1 60 A Cu: n.º 14 a n.º 3 Al: n.º 12 a n.º 1 100 A Cu/Al: n.º 4 - 300 kcmil 50 A 100 A Cu: n.º 14 a n.º 3 Al: n.º 12 a n.º 1 Cu: n.º 3 - 3/0 Al: n.º 1 - 3/0 240/416 V - Estrella trifásica - 60 Hz Corriente máxima del disyuntor 40 A Rango de cable con lengüeta Cu: n.º 14 a n.º 3 Al: n.º 12 a n.º 1 277/480 V - Estrella trifásica - 60 Hz Corriente máxima del disyuntor 40 A 50 A Cu: n.º 14 a n.º 3 Al: n.º 12 a n.º 1 50 A 100 A Cu: n.º 3 - 3/0 Al: n.º 1 - 3/0 90 A 70 A 125 A Cu: n.º 6 - 2/0 Al: n.º 4 - 2/0 Cu/Al: n.º 4 - 300 kcmil 60 A 100 A Rango de cable con lengüeta Cu: n.º 14 a n.º 3 Al: n.º 12 a n.º 1 Cu: n.º 14 a n.º 3 Al: n.º 12 a n.º 1 Cu: n.º 14 a n.º 3 Al: n.º 12 a n.º 1 Cu: n.º 6 - 2/0 Al: n.º 4 - 2/0 Cu: n.º 3 - 3/0 Al: n.º 1 - 3/0 19 Aplicaciones del controlador Intelilite - Monofásica y trifásica Nodo de potencia 20/25kW Corriente máxima del disyuntor 150A 25/30kW 225A 29/35kW 300A Voltaje - Fase Frecuencia Nodo de potencia 20/25kW 25/30kW 29/35kW 20 Disyuntor del generador 120/240V - 1Ø - 60Hz Voltaje - Fase Frecuencia 120/208V - 3Ø Wye - 60Hz Rango de cable con lengüeta Cu/Al: #2 - 300kcmil Cu/Al: #2 - 300kcmil Cu/Al: #6 - 600kcmil Corriente máxima del disyuntor 125A 200A 225A Rango de cable con lengüeta Cu/Al: #4 - 300kcmil 70A 100A 125A Corriente máxima del disyuntor Cu/Al: #4 - 300kcmil Cu/Al: #4 - 300kcmil 240/416V - 3Ø Wye - 60Hz Corriente máxima del disyuntor 120/240V - 3Ø Delta - 60Hz Rango de cable con lengüeta Cu: #6 - 2/0 Al: #4 - 2/0 Cu: #3 - 3/0 Al: #1 - 3/0 Cu/Al: #4 - 300kcmil 110A 175A 200A Rango de cable con lengüeta Cu/Al: #4 - 300kcmil Corriente máxima del disyuntor 60A Cu/Al: #4 - 300kcmil 100A Cu/Al: #4 - 300kcmil Generator Circuit Breaker 277/480V - 3Ø Wye - 60Hz Corriente máxima del disyuntor Rango de cable con lengüeta 60A Cu: #14 - #3 Al: #12 - #1 100A Cu: #3 - 3/0 Al: #1 - 3/0 90A 220/380V - 3Ø Wye - 50Hz Cu: #6 - 2/0 Al: #4 - 2/0 125A Rango de cable con lengüeta Cu: #6 - 2/0 Al: #4 - 2/0 Cu: #3 - 3/0 Al: #1 - 3/0 Cu/Al: #4 - 300kcmil 347/600V - 3Ø Wye - 60Hz Corriente máxima del disyuntor Rango de cable con lengüeta 70A Cu: #6 - 2/0 Al: #4 - 2/0 45A Cu: #14 - #3 Al: #12 - #1 90A Cu: #6 - 2/0 Al: #4 - 2/0 BRIGGSandSTRATTON.COM Batería El instalador debe suministrar e instalar una batería de arranque que cumpla con las especificaciones indicadas a continuación. Voltios Especificaciones de la batería Amperios (MÍN.) Tipo Tamaño del Grupo BCI 12 V CC 775 CCA (corriente de arranque en frío) AGM (separador de fibra de vidrio absorbente) 34 Consideraciones finales de la instalación Inspección de la instalación Antes de poner el generador en funcionamiento, revise las instrucciones mientras inspecciona cuidadosamente toda la instalación, para asegurarse de que esté completa y sea correcta. Sistema de suministro de combustible Asegúrese de que todas las conexiones de tuberías de combustible estén ajustadas, fijas y que no tengan fugas. Asegúrese de que todas las válvulas de cierre de la línea de combustible estén ABIERTAS y de que se disponga de la presión de combustible adecuada. Instale la batería como se describe en Mantenimiento de la batería en la sección Mantenimiento. Asegúrese de conectar el cable NEGATIVO siempre en último lugar. ADVERTENCIA Las baterías almacenadas producen hidrógeno explosivo mientras se recargan. Aun la menor chispa puede encender el hidrógeno y ocasionar una explosión, que tendrá como resultado la muerte, lesiones graves o daños en la propiedad. El líquido de electrolito de la batería contiene ácido y es extremadamente cáustico. El contacto con el contenido de la batería puede provocar quemaduras químicas graves. Las baterías presentan el riesgo de descarga eléctrica y de corriente de cortocircuito elevada. • NO elimine una batería en el fuego. Recicle las baterías. • • • • • NO permita que existan llamas abiertas, chispas, fuentes de calor, ni que se enciendan cigarrillos durante y varios minutos después de cargar una batería. NO abra ni destroce la batería. Use anteojos protectores de seguridad, delantal de goma, botas de goma y guantes de goma. Quítese el reloj, los anillos u otros objetos metálicos. Use herramientas con mangos aislados. 21 Arranque inicial (sin carga) 7. Controle la salida del voltaje entre cada una de las orejetas de conexión del disyuntor y la orejeta neutra. El voltaje sin carga debe ser como se muestra en la siguiente tabla. Antes de hacer funcionar el generador o de prepararlo para su funcionamiento, inspeccione cuidadosamente toda la instalación. Familiarícese con la ubicación de los componentes y la ubicación y función del controlador del generador. Luego, comience a probar el sistema sin cargas eléctricas conectadas, como se indica a continuación: 1. Revise el aceite del motor. Añada aceite si es necesario. Consulte el tipo de aceite requerido en el manual del motor. 8. Si es necesario, ajuste el control de voltaje AVR (A) para obtener el rango especificado. NO ajuste ningún otro control del alternador. 2. Coloque el disyuntor principal del generador en la posición APAGADO (abierta). A 3. Encienda el generador. Cuando se enciende el generador por primera vez, se purgará el aire de las tuberías de combustible gaseoso. Esto puede provocar que el motor funcione bruscamente durante unos minutos. 4. Esté atento por si escucha ruidos, vibración u otros indicadores de funcionamiento anormal. Revise en busca de fugas de aceite o de refrigerante mientras funciona el motor. 9. Asegúrese de que el switch de transferencia esté en la posición “SERVICIO” y de que no haya carga presente en el generador. 5. Deje que el motor se caliente durante 5 minutos. 6. Revise la salida del generador en el lado de línea del disyuntor. El voltaje sin carga debe ser como se muestra en la siguiente tabla. La frecuencia debe ser de 59,8 a 60,2 Hz para las aplicaciones de 60 Hz. La frecuencia debe ser de 49,8 a 50,2 Hz para las aplicaciones de 50 Hz. 10. 11. Coloque el disyuntor principal del generador en la posición ENCENDIDO (cerrada). Detenga el generador. NOTA Si el voltaje sin carga está fuera del rango especificado, realice el ajuste automático del regulador de voltaje (AVR) en el Paso 8. No continúe hasta que el voltaje de CA esté dentro de los márgenes especificados. Tabla de voltaje sin carga (50 Hz) Monofásico Estrella trifásica Fase a fase Fase a neutro Voltaje Mínimo Máximo Mínimo Máximo 220/380 377 383 218 222 230 228 232 N/C N/C Tabla de voltaje sin carga (60 Hz) Monofásico Estrella trifásica Delta trifásica Estrella trifásica 22 Estrella trifásica Fase a fase Fase a neutro Voltaje Mínimo Máximo Mínimo Máximo 120/208 206 210 119 121 120/240 238 242 119 121 120/240 238 242 119 121 277/480 475 485 275 279 347/600 594 606 344 350 BRIGGSandSTRATTON.COM Características y controles D C B A E F Paneles de acceso A -Puerto de entrada de combustible B -Puertas del controlador C -Abertura de escape D -Puerta de llenado de refrigerante E -Puerta de la batería F -Puerta del silenciador Cada generador se envía con un juego de llaves idénticas. Estas llaves pertenecen a las cerraduras que cierran las puertas de acceso. Todas las puertas deben cerrarse siempre que la unidad esté funcionando para asegurar un funcionamiento correcto y seguro. 23 Ubicaciones de los componentes Compare las ilustraciones siguientes con su generador para familiarizarse con las ubicaciones de los diversos componentes de la unidad. A C B G A F D E Con fines de claridad, el generador se muestra sin el techo y las puertas de acceso. A-F  iltro de aire: protege el motor filtrando el polvo y los desechos del aire de admisión. B-P  rotección de malla: evita que los dedos toquen el ventilador del radiador y alberga la botella de recuperación de refrigerante. Debe estar cerrada mientras el generador está en uso. C-B  otella de recuperación de refrigerante: se ubica en la parte interna de la protección de malla. Proporciona un indicador visual del nivel de refrigerante del motor. 24 D-E  ntrada de combustible: el suministro de combustible se conecta aquí. E-E  tiqueta de datos del generador: identifica el modelo y el número de serie del generador. F-C  aja del disyuntor: equipada con una parte inferior desmontable para ayudar en la conexión de conductos. G-C  ontrolador: se utiliza para distintas funciones de prueba, funcionamiento y mantenimiento. BRIGGSandSTRATTON.COM Mantenimiento Limpieza del generador Limpie la unidad si advierte la presencia de polvo, suciedad, aceite, humedad u otras sustancias extrañas en las superficies interiores y exteriores. Las entradas y salidas de aire de la caja no deben obstruirse con nieve, hojas o cualquier otro material extraño. Para evitar daños en el generador causados por el sobrecalentamiento, mantenga siempre limpias y sin obstrucciones las entradas y salidas de aire de la caja. AVISO NO rocíe directamente con una manguera de jardín para limpiar el generador. El agua puede ingresar en el motor y en el generador y ocasionar problemas. 1. Detenga el generador. 2. Desconecte el cable negativo ( - ) de la batería. 3. Limpie el generador de la siguiente manera: • Use un paño húmedo para limpiar las superficies exteriores. • Use un cepillo de cerda suave y una aspiradora para aflojar y recoger la suciedad y los residuos. • Use aire a baja presión (no más de 25 psi) para soplar la suciedad. • Limpie las entradas y salidas de aire que tengan presencia de nieve, hojas o desechos.Para evitar daños generados por el sobrecalentamiento, estas aberturas deben mantenerse sin obstrucciones. 4. Conecte el cable negativo ( - ) de la batería. 5. Ajuste el modo del generador en AUTOMÁTICO. Filtro de aire del motor 1. Detenga el generador. 2. Desconecte el cable negativo ( - ) de la batería. 3. Retire el cartucho del filtro. 4. Limpie el tubo de salida y revise la válvula del descargador de polvo (si está equipada): use un paño limpio para limpiar la superficie de sellado del filtro y las superficies del tubo de salida. Asegúrese de eliminar todos los contaminantes antes de insertar un filtro nuevo. Tenga cuidado de no dañar el área de sellado del tubo. Revise y apriete la válvula del descargador de polvo, unida a la tapa de servicio, para asegurarse de que es flexible y que no está invertida, dañada u obstruida. 5. Limpie el filtro: use un cepillo de cerdas suaves para aflojar la suciedad y una aspiradora para quitar la suciedad y los residuos. Cambie los cartuchos del filtro si se detectan orificios en el medio de filtración. 6. Instale el filtro limpio correctamente: inserte el filtro con cuidado. Coloque el filtro con la mano y asegúrese de que esté completamente dentro de la carcasa del filtro de aire antes de fijar la cubierta en su lugar. 7. Vuelva a instalar la tapa del panel de servicio. Asegúrese de que todas las bandas de montaje, las abrazaderas, los pernos y las conexiones de todo el sistema de filtro de aire estén ajustadas y controle que las tuberías no tengan orificios. Repare de ser necesario. 8. Conecte el cable negativo ( - ) de la batería. 9. Ajuste el modo del generador en AUTOMÁTICO. 25 Mantenimiento del sistema eléctrico Cableado y conexiones El sistema eléctrico del generador incorpora computadoras para controlar diversos componentes relacionados. Las conexiones del sistema eléctrico y los circuitos de conexión a tierra necesitan buenas conexiones. Cuando inspeccione el sistema eléctrico, revise lo siguiente: • Revise si los cables positivo (+) y negativo (-) de la batería tienen daños por corrosión, fricción, desgaste, quemaduras y asegúrese de que las conexiones estén ajustadas en ambos extremos. • Revise si hay grietas o daños en la caja de la batería. Reemplace según sea necesario. • Inspeccione el cableado del motor para ver si tiene daños por fricción, desgaste, pinzado, quemaduras y grietas o cortes. • Verifique que los conectores del cableado del motor estén correctamente fijados. • Inspeccione el cable de la bobina de ignición para ver si tiene endurecimiento, grietas, desgaste por fricción, quemaduras, separación y fundas divididas. • Inspeccione el cable de la bujía para ver si tiene endurecimiento, grietas, desgaste por fricción, quemaduras, separación y fundas divididas. • Cambie las bujías según los intervalos que se indican en la tabla de mantenimiento. • Verifique que todos los componentes eléctricos estén firmemente montados en el motor o en el chasis. • Verifique que todos los servicios eléctricos adicionales instalados por el propietario, estén correctamente instalados en el sistema. NO CONTAMINE. CONSERVE LOS RECURSOS. DEVUELVA LAS BATERÍAS USADAS A UN CENTRO DE RECOLECCIÓN Y RECICLAJE. Carga de la batería 1. Detenga el generador. 2. Desconecte el cable negativo ( - ) de la batería. 3. Desconecte el cable positivo ( + ) de la batería. 4. Conecte el cargador en la batería. Cargue la batería a 2 amperios, hasta que la batería contenga 12 voltios. NO exceda los 13,7 voltios durante la carga de la batería. 5. Conecte el cable positivo ( + ) de la batería. 6. Conecte el cable negativo ( - ) de la batería. 7. Asegúrese de que las piezas metálicas de los terminales positivo y negativo de la batería estén fijas. 8. Ajuste el modo del generador en AUTOMÁTICO. Mantenimiento del sistema de escape Cuando inspeccione el sistema de escape, revise lo siguiente: • Inspeccione si hay fugas en el colector de escape en el cabezal del cilindro. • Compruebe que todos los pernos de retención y protecciones (si se usan) estén en su lugar. • Inspeccione los sujetadores entre el colector y la tubería de escape para garantizar que estén ajustados y que no haya fugas en el escape. Repare según sea necesario. • Inspeccione el conector eléctrico del sensor de oxígeno para garantizar que esté asentado y bloqueado. Revise los cables para garantizar que no tengan grietas, fisuras, desgaste por fricción ni quemaduras. Reemplace o repare según sea necesario. • Inspeccione si hay fugas en la conexión del tubo de escape. Repare según sea necesario. Reemplazo de la batería 1. Detenga el generador. 2. Desconecte el cable negativo ( - ) de la batería. 3. Desconecte el cable positivo ( + ) de la batería. 4. Retire la batería e instale la batería de repuesto. 5.Conecte el cable positivo ( + ) de la batería. 6. Conecte el cable negativo ( - ) de la batería. 7. Asegúrese de que las piezas metálicas de los terminales positivo y negativo de la batería estén fijas. 8.Ajuste el modo del generador en AUTOMÁTICO. 26 BRIGGSandSTRATTON.COM Solución de problemas Problema Causa 1. El disyuntor está abierto o defectuoso. El motor funciona, pero no hay salida 2. El control del generador presenta de CA disponible. fallas. 3.Conexiones de cableado deficientes o switch de transferencia defectuoso. 1. Existe un cortocircuito en una carga conectada. El motor funciona bien sin carga, 2. El generador está sobrecargado. pero se atasca cuando se conectan 3. El circuito del generador tiene un las cargas. cortocircuito. 4.La presión o mezcla del combustible es incorrecta. Corrección 1. Restablezca o reemplace el disyuntor. 2. Comuníquese con el establecimiento de servicio local. 3. Revise y repare. 1. Desconecte la carga eléctrica cortocircuitada. 2. Apague una o más cargas. 3. Comuníquese con el establecimiento de servicio local. 4.Consulte la sección Planificación de la instalación de combustible. El motor no arranca. El motor arranca, pero tiene un funcionamiento forzado. 1. Se apagó o se acabó el suministro de combustible. 2. La batería tiene fallas. 3. La presión de combustible es incorrecta. 1. Revise las válvulas de combustible. Revise el suministro de combustible 2. Cambie la batería. 3. Consulte la sección Planificación de la instalación de combustible. El motor se apaga durante el funcionamiento. 1. Se apagó o se acabó el suministro de combustible. 1. Revise las válvulas de combustible; revise el suministro de combustible. Pérdida de energía en los circuitos. 1. El disyuntor del generador está 1. Restablezca el disyuntor. abierto. 2. Consulte el manual de la llave de 2. El interruptor de transferencia tiene transferencia. problemas. 27 Especificaciones del generador (60 Hz y 50 Hz) Serie 29000 Monofásico Voltaje 230 Monofásico 120/240 Estrella trifásica 220/380 Estrella trifásica Estrella trifásica 115/200 230/400 Amperios nominales * 126 104 55 50 Serie 35000 Voltaje Amperios nominales * 120/240 Delta trifásica 120/240 Estrella trifásica 120/208 240/416 105 61 53 Serie 40000 Voltaje Amperios nominales * Monofásico 230 Monofásico 120/240 Estrella trifásica 220/380 Estrella trifásica Estrella trifásica Estrella trifásica Serie 48000 115/200 230/400 240/416 Voltaje Monofásico 120/240 Delta trifásica 120/240 Estrella trifásica Estrella trifásica Estrella trifásica 120/208 240/416 144 76 144 83 Voltaje Estrella trifásica Estrella trifásica 230/400 240/416 90 Serie 60000 Voltaje Amperios nominales * Delta trifásica 120/240 Estrella trifásica Estrella trifásica Estrella trifásica 240/416 277/480 347/600 61 dB (3,0 l) 1831 lb (831 kg) (3,0 l) 68 dB (4,3 l) 2033 lb (922 kg) (4,3 l) Nivel de sonido de salida ^ Peso con embalaje 50 Hz -20 °F (-28 °C) a 104 °F (40 °C) 66 dB 2033 lb (922 kg) Frecuencia Intervalo de funcionamiento ambiental Nivel de sonido de salida ^ Peso con embalaje 60 Hz -20 °F (-28 °C) a 104 °F (40 °C) 68 dB 2033 lb (922 kg) Frecuencia Intervalo de funcionamiento ambiental Nivel de sonido de salida ^ Peso con embalaje 50 Hz -20 °F (-28 °C) a 104 °F (40 °C) 67 dB 2419 lb (1097 kg) Frecuencia Intervalo de funcionamiento ambiental Nivel de sonido de salida ^ Peso con embalaje 60 Hz -20 °F (-28 °C) a 104 °F (40 °C) 70 dB 2419 lb (1097 kg) 217 120/240 120/208 Peso con embalaje Intervalo de funcionamiento ambiental 58 Monofásico 120/240 Nivel de sonido de salida ^ 167 Serie 50000 Estrella trifásica 2033 lb (922 kg) (4,3 l) Frecuencia 200 Amperios nominales * Monofásico 66 dB (4,3 l) -20 °F (-28 °C) a 104 °F (40 °C) 69 72 220/380 1831 lb (831 kg) (3,0 l) 72 Amperios nominales * Peso con embalaje 60 dB (3,0 l) 166 277/480 Estrella trifásica Nivel de sonido de salida ^ 60 Hz 174 347/600 230 Intervalo de funcionamiento ambiental 42 Estrella trifásica Monofásico Frecuencia 121 277/480 347/600 -20 °F (-28 °C) a 104 °F (40 °C) 145 Estrella trifásica Estrella trifásica 50 Hz 52 240/416 Estrella trifásica Intervalo de funcionamiento ambiental 120 Estrella trifásica Monofásico Frecuencia 208 95 87 250 215 186 108 93 75 * La clasificación del gas natural dependerá del combustible específico, sin embargo, la reducción típica está entre un 10 y un 20 % menos que el propano. ^ Según ISO 3744. Micrófono más bajo a 23 pies (7 m) sin carga. Este generador está clasificado conforme a la norma UL (Underwriters Laboratories) 2200 (grupos generadores de motor fijo) y a la norma CSA (Canadian Standards Association) C22.2 n.º 100-14 (motores y generadores). 28 BRIGGSandSTRATTON.COM Diagramas de cableado Los diagramas del cableado empiezan en la siguiente página. 29 Esta página se dejó intencionalmente en blanco. 48 BRIGGSandSTRATTON.COM
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144

Simplicity 076155-01 Manual de usuario

Categoría
Generadores de poder
Tipo
Manual de usuario