1. Loosen assembly screws in face and separate device. If needed, back
out cord clamp screws enough to allow cord to fit between the two clamp
halves. Insert cord through cord clamp and housing.
2. Strip cord jacket between 7/8" and 1" from cord's end. Remove insulation
exposing between 3/8" and 1/2" bare copper wire (See diagram 2a). Twist
wire strands tightly together. Trim off cord fillers, if any.
3. Insert bare copper wire into wire clamp and tighten each terminal screw
10-12 in.-lbs. torque. Ensure insulation clears clamp; HOT conductor to
BRASS terminal, NEUTRAL conductor to SILVER terminal and GROUND
conductor to GREEN hex screw.
4. Assemble wired device body with housing. Align keyed housing with key
on device's body. Tighten assembly screws.
5. Alternately tighten cord clamp screws 10-12 in.-lbs. torque. Ensure cord
clamp rests over cord jacket, not over conductors.
Armored Plug; Cat. No. 515PA
Armored Cord Outlet; Cat. No. 515CA
Rated: 15A-125V
Use with Vacuum Cleaner Cord, Jr. Hard Service Cord; 18/3 to 12/3 AWG
0.312"-0.655" dia. max. STRANDED COPPER WIRE ONLY!
To Wire:
WARNING: TO AVOID FIRE, SHOCK, OR DEATH, UNPLUG CORD OR
TURN OFF POWER AT CIRCUIT BREAKER OR FUSE AND TEST THAT
POWER IS OFF BEFORE WIRING!
1. Loosen assembly screws in face to separate device. If needed, back out
cord clamp screws enough to allow cord to fit between the two clamp
halves. Insert cord through cord clamp and housing.
2. Strip cord jacket between 7/8" and 1" from cord's end. Remove insulation
exposing between 3/8" and 1/2" bare copper wire (See diagram 2a). Twist
wire strands tightly together. Trim off cord fillers, if any.
3. Insert bare copper wire into wire clamp and tighten each terminal screw
10-12 in.-lbs. torque. Ensure insulation clears clamp; HOT conductor to
BRASS terminal, NEUTRAL conductor to SILVER terminal and GROUND
conductor to GREEN hex screw.
4. Assemble wired device body with housing. Align keyed housing with key
on device's body. Tighten assembly screws.
5. Alternately tighten cord clamp screws 10-12 in.-lbs. torque. Ensure cord
clamp rests over cord jacket, not over conductors. CORD JACKET MUST
BE CUT TO SPECIFIED LENGTH ONLY. IT MUST ALWAYS REST INSIDE
THE HOUSING AND UNDER CORD CLAMP; OTHERWISE, DANGER
OF AN ELECTRICAL SHORT EXISTS.
TO BE INSTALLED AND/OR USED IN ACCORDANCE
WITH APPROOPIATE ELECTRICAL CODES AND
REGULATIONS / PARA INSTALARSE Y/O USARSE
DE ACUERDO CON LOS CODIGOS ELECTRICOS Y
NORMAS APROPIADOS
Heavy Duty Plug; Cat. No. 115PR
Heavy Duty Cord Outlet; Cat. No. 115CR
Plug; Cat. No. 115PV
Cord Outlet; Cat. No. 115CV
Rated: 15A-125V
Use with Vacuum Cleaner Cord, Jr. Hard Service Cord; 18/3 to 12/3 AWG
0.240"-0.655" dia. max. STRANDED COPPER WIRE ONLY!
To Wire:
WARNING: TO AVOID FIRE, SHOCK, OR DEATH, UNPLUG CORD OR
TURN OFF POWER AT CIRCUIT BREAKER OR FUSE AND TEST THAT
POWER IS OFF BEFORE WIRING!
1. Loosen assembly screws in face and separate device. If needed, back
out cord clamp screws enough to allow cord to fit between the two clamp
halves. Insert cord through cord clamp and housing.
2. Strip cord jacket 7/8" from cord's end. Remove insulation exposing 3/8"
bare copper wire (See diagram 1a). Twist wire strands tightly together.
Trim off cord fillers, if any.
3. Insert bare copper wire into wire clamp and tighten each terminal screw
10-12 in.-lbs. torque. Ensure insulation clears clamp; HOT conductor to
BRASS terminal and NEUTRAL conductor to SILVER terminal.
4. Assemble wired device body with housing. Align keyed housing with key
on device's body. Tighten assembly screws.
5. Alternately tighten cord clamp screws 10-12 in.-lbs. torque. Ensure cord
clamp rests over cord jacket, not over conductors.
Clavija Angular a Tierra; Cat. No. 515AN
Capacidad: 15A-125V
Usar con el Cordón de la Aspiradora, Cordón de Servicio Pesado;
18/3 a 12/3 AWG 0.61 cm-1.66 cm dia. max. SOLO CABLE DE VARIOS
HILOS DE COBRE.
Para Cablear:
ADVERTENCIA: PARA EVITAR DESCARGA ELECTRICA, FUEGO O
MUERTE, DESCONECTE EL CORDON O INTERRUMPA EL PASO DE
ENERGIA MEDIANTE EL INTERRUPTOR DE CIRCUITO O FUSIBLE.
¡ASEGURESE DE QUE EL CIRCUITO NO ESTA ENERGIZADO ANTES
DE INICIAR LA INSTALACION!
1. Afloje los tornillos de montaje de la cara y separe el producto. Afloje los
tornillos de la abrazadera y desensamble la abrazadera.
1. 2.
3.
4.
5.
2. Quitar entre 2.9 cm y 3.2 cm de forro en la punta del cordón. Corte
el conductor A TIERRA a una longitud de 2 cm. Quite el aislante para
exponer entre 1 cm y 1.3 cm de alambre de cobre desnudo en cada uno
de los 3 conductores
(Vea el diagrama 3b). Tuerza los hilos del alambre
fírmemente. Recorte el relleno del cordón si hay.
3. Inserte el alambre de cobre desnudo en la abrazadera y apriete cada
tornillo de las ternimales a un torque 10-12 pulg.-lb. Asegure que el
aislante libra la abrazadera. PRIMERO conecte el conductor A TIERRA
al tornillo hexagonal VERDE. El conductor FASE a la terminal LATON y
el conductor NEUTRO a la terminal PLATEADA.
4. Ensamble el cuerpo del producto ya cableado con su armazon. Alinie la
ranura del armazon con la cuña del cuerpo del aparato. Apriete los tornillos
de montaje.
5. Alternadamente apriete los tornillos de la abrazadera a un torque 10-12
pulg.-lb. Asegúrese de que la abrazadera del cordón presiona sobre el
forro del cordón y no sobre los conductores.
Clavija a Tierra, Uso Rudo; Cat. No. 515PR
Contacto a Tierra para Cordón, Uso Rudo; Cat. No. 515CR
Clavija a Tierra; Cat. No. 515PV
Contacto a Tierra para Cordón; Cat. No. 515CV
Capacidad: 15A-125V
Usar con el Cordón de la Aspiradora, Cordón de Servicio Pesado;
18/3 a 12/3 AWG 0.61 cm-1.66 cm dia. max. SOLO CABLE DE VARIOS
HILOS DE COBRE.
Para Cablear:
ADVERTENCIA: PARA EVITAR DESCARGA ELECTRICA, FUEGO O
MUERTE, DESCONECTE EL CORDON O INTERRUMPA EL PASO DE
ENERGIA MEDIANTE EL INTERRUPTOR DE CIRCUITO O FUSIBLE.
¡ASEGURESE DE QUE EL CIRCUITO NO ESTA ENERGIZADO ANTES
DE INICIAR LA INSTALACION!
1. Afloje los tornillos de montaje de la cara y separe el producto. Si se
necesita afloje los tornillos de la abrazadera lo suficiente para permitir
que el cordón quepa entre las dos mitades de la abrazadera. Inserte el
cordón a través de la abrazadera del cordón y del armazon.
2. Quite entre 2.3 cm y 2.6 cm de forro del cordón. Quite el aislante para
exponer entre 1 cm y 1.3 cm de alambre de cobre desnudo (Vea el
diagrama 2b). Tuerza los hilos del alambre fírmemente. Recorte el relleno
del cordón, si hay.
3. Inserte el alambre de cobre desnudo en la abrazadera y apriete cada
tornillo de las terminales a un torque 10-12 pulg.-lb. Asegure que el aislante
libra la abrazadera; Conecte el conductor FASE a la terminal LATON, el
conductor NEUTRO a la terminal PLATEADA, y el conductor A TIERRA
al tornillo hexagonal VERDE.
4. Ensamble el cuerpo del producto ya cableado con su armazon. Alinie la
ranura del armazon con la cuña del cuerpo del aparato. Apriete los tornillos
de montaje.
5. Alternadamente apriete los tornillos de la abrazadera a un torque 10-12
pulg.-lb. Asegúrese de que la abrazadera del cordón presiona sobre el
forro del cordón y no sobre los conductores.
Clavija Blindada a Tierra; Cat. No. 515PA
Contacto Blindado a Tierra para Cordón; Cat. No. 515CA
Capacidad: 15A-125V
Usar con el Cordón de la Aspiradora, Cordón de Servicio Pesado;
18/3 a 12/3 AWG 0.79 cm-1.66 cm dia. max. SOLO CABLE DE VARIOS
HILOS DE COBRE.
Para Cablear:
ADVERTENCIA: PARA EVITAR DESCARGA ELECTRICA, FUEGO O
MUERTE, DESCONECTE EL CORDON O INTERRUMPA EL PASO DE
ENERGIA MEDIANTE EL INTERRUPTOR DE CIRCUITO O FUSIBLE.
¡ASEGURESE DE QUE EL CIRCUITO NO ESTA ENERGIZADO ANTES
DE INICIAR LA INSTALACION!
1. Afloje los tornillos de montaje de la cara y separe el producto. Si se
necesita afloje los tornillos de la abrazadera lo suficiente para permitir
que el cordón quepa entre las dos mitades de la abrazadera. Inserte el
cordón a través de la abrazadera del cordón y del armazon.
2. Quite entre 2.3 cm y 2.6 cm de forro del cordón. Quite el aislante para
exponer entre 1 cm y 1.3 cm de alambre de cobre desnudo (Vea el
diagrama 2b). Tuerza los hilos del alambre fírmemente. Recorte el relleno
del cordón, si hay.
3. Inserte el alambre de cobre desnudo en la abrazadera y apriete cada
tornillo de las terminales a un torque 10-12 pulg.-lb. Asegure que el
aislante libra la abrazadera; el conductor FASE a la terminal LATON, el
conductor NEUTRO a la terminal PLATEADA, y el conductor A TIERRA
al tornillo hexagonal VERDE.
4. Ensamble el cuerpo del producto ya cableado con su armazon. Alinie la
ranura del armazon con la cuña del cuerpo del aparato. Apriete los tornillos
de montaje.
Grounding Angle Plug; Cat. No. 515AN
Rated: 15A-125V
Use with Vacuum Cleaner Cord, Jr. Hard Service Cord; 18/3 to 12/3 AWG
0.240"-0.655" dia. max. STRANDED COPPER WIRE ONLY!
To Wire:
WARNING: TO AVOID FIRE, SHOCK, OR DEATH, UNPLUG CORD OR
TURN OFF POWER AT CIRCUIT BREAKER OR FUSE AND TEST THAT
POWER IS OFF BEFORE WIRING!
1. Loosen assembly screws in face and separate device. Loosen clamp
screws to disassemble clamp.
2. Strip cord jacket between 1-1/8" and 1-1/4" from cord's end. Cut GROUND
conductor to 3/4" length. Remove insulation exposing between 3/8" and
1/2" bare copper wire on all 3 conductors (See diagram 3a). Twist wire
strands tightly together. Trim off cord fillers, if any.
3. Insert bare copper wire into wire clamp and tighten each terminal screw
10-12 in.-lbs. torque. Ensure insulation clears clamp. FIRST connect
GROUND conductor to GREEN hex screw, HOT conductor to BRASS
terminal and NEUTRAL conductor to SILVER terminal.
4. Assemble wired device body with housing. Align keyed housing with key
on device's body. Tighten assembly screws.
5. Alternately tighten cord clamp screws 10-12 in.-lbs. torque. Ensure cord
clamp rests over cord jacket, not over conductors.
Heavy Duty Grounding Plug; Cat. No. 515PR
Heavy Duty Grounding Cord Outlet; Cat. No. 515CR
Grounding Plug; Cat. No. 515PV
Grounding Cord Outlet; Cat. No. 515CV
Rated: 15A-125V
Use with Vacuum Cleaner Cord, Jr. Hard Service Cord; 18/3 to 12/3 AWG
0.240"-0.655" dia. max. STRANDED COPPER WIRE ONLY!
To Wire:
WARNING: TO AVOID FIRE, SHOCK, OR DEATH, UNPLUG CORD OR
TURN OFF POWER AT CIRCUIT BREAKER OR FUSE AND TEST THAT
POWER IS OFF BEFORE WIRING!