CARLO GAVAZZI RKD2B60D50C Guía de instalación

Tipo
Guía de instalación
RK Series
2 Pole, Solid State Relays
• Operating Instructions • Kom godt i gang
• Bedienungsanleitung • Notice d'utilisation
• Instrucciones • Istruzioni d’uso
Руководство по эксплуатации
操作说明
RK_inst_leaf_ 07_18 7680581-03
C
onnection Diagram | Forbindelsesdiagram | Dia-
grama de conexiones | Anschlussbelegung | Sché-
m
as des connexions | Schema di collegamento |
Схема подключения | 连接图
T
erminations | Termineringer | Terminales | Anschlus-
seigenschaften | Terminations | Terminali | Клеммы |
Connection of ring terminals | Forbindelse af
ringterminaler | Conexn de los terminales de anillo |
Raccordement de cosses rondes|Verbindung mit Ringka-
belschuhen | Collegamento dei terminali | Подключение
кольцевыми кабельными наконечниками | 环形端子连接
CARLO GAVAZZI LTD
BLB042, Bulebel Industrial Estate
Zejtun ZTN 3000, Malta
www.gavazzi-automation.com
info: +356 23601.100
fax: +356 23601.111
FIG. 2
FIG. 3
FIG. 1
1/L1: RKD2, RK2 - Mains Connection, Pole A
2/T1: RKD2, RK2 - Load Connection, Pole A
3/L2: RKD2, RK2 - Mains Connection, Pole B
4/T2: RKD2, RK2 - Load Connection, Pole B
A1(+): RKD2 - Control Signal, Pole A
RK2 - Control Signal, Pole A & B
A2(-): RKD2 - Ground, Pole A
RK2 - Ground, Pole A & B
B1(+): RKD2 - Control Signal, Pole B
B2(-): RKD2 - Ground, Pole B
Removable IP20 Cover
M4 screw with captivated washer
MAX 25mm
2
Cable
with Crimped Ring Terminal
1/
L
1,
2/
T1
3/
L
2,
4/
T2
RK..C
RK..P
R
K..C
R
K..P
Use 75
o
C copper
(Cu) conductors
2 x 2.5 - 6.0 mm
2
1 x 2.5 - 6.0 mm
2
2 x 14 - 10 AWG 1 x 14 - 10 AWG
2 x 1.0 - 2.5 mm
2
2 x 2.5 - 6.0 mm
2
1 x 1.0 - 6.0 mm
2
2 x 18 - 14 AWG 1 x 14 - 10 AWG
2 x 14 - 10 AWG
-
Pozidrive bit 2
UL: 2 .0 Nm (17.7 lb-in)
IEC: 1.5 - 2.0 Nm (13.3 - 17.7 lb-in)
X
A
1,
A
2
B
1,
B
2
Use 60/75
o
C
copper (Cu)
conductors
RK..P
0.5 - 2.5 mm
2
26 - 12 AWG
0.5 - 2.5 mm
2
26 - 12 AWG
X 12 mm 8 - 9 mm
0.5 - 1.5 mm
2
-
F1 Mersen Siba
RK..50
50A, FR22UD69V50T 50A, 50 142 06.50
RK..51
63A, FR22UD69V63T 63A, 50 142 06.63
RK..75
80A, FR22GR69V80T 100A, 50 142 06.100
max. 12.5 mm
-
Do not touch pre-attached thermal interface | Rør ikke ved forudgående termisk grænseflade | No toque la interfaz térmica preinstalada | Berühren Sie nicht
die vormontierte thermische Schnittstelle | Ne touchez pas l'interface thermique pré-attachée | Non toccare l'interfaccia termica preassemblata
Phase
P
hase / Neutral
P
E
F
1F1F1
L
1
L
2
L
3
N
PE
F1 F1 F1
Mounting Instructions
FIG. 1: Remove cover before mount-
ing the SSR on the panel chassis or
heatsink.
FIG. 2: Make sure to select an ade-
quate heat dissipator. Tighten the
SSR, alternating between the 2
screws to max. 2.0 Nm. The RK
should be mounted to the heat dissi-
pator using two M5 screws with flat
and spring washers.
FIG. 3: Mount the heatsink in the cor-
rect orientation so as not to obstruct
airflow through the heatsink.
Installationsvejledning
FIG. 1: Fjern dækslet, før du monterer
SSR'en panelets chassis eller
køler.
FIG. 2: Sørg for at vælge en
passende varmeafleder. Tilspænd
SSR'en, skift mellem de 2 skruer til
maks. 2,0 Nm. RK'en bør monteres
varmelederen ved hjælp af to M5-
skruer med underlags- og fjeder-
skiver.
FIG. 3: Montér kølepladen, så den
vender korrekt og ikke blokerer for
lufstrømmen via kølepladen.
Instructions d'installation
FIG. 1:
Retirez le couvercle avant de
monter le SSR sur le châssis du pan-
neau ou le dissipateur thermique.
FIG. 2: Assurez-vous de choisir un
dissipateur adapté. Serrer le relais
statique au couple maxi de 2.0 Nm en
approche, en alternant d'une vis à
l'autre. Visser le relais statique RK sur
le dissipateur thermique au moyen
des deux vis M5 avec plat et rondelles
élastiques.
FIG. 3: Au montage, orienter cor-
rectement le dissipateur, afin de per-
mettre au flux d'air de le traverser.
Installationsanleitungen
FIG. 1: Entfernen Sie die Abdeckung,
bevor Sie das SSR am Gehäuse oder
Kühlkörper des Panels montieren.
FIG. 2: Stellen Sie sicher, dass ein
geeigneter hlkörper ausgewählt wird.
Befestigen Sie das SSR, indem Sie die
beiden Schrauben abwechselnd bis zu
einem maximalen Anzugsdrehmoment
von 2,0 Nm anziehen. Das RK muss mith-
ilfe zweier M5-Schrauben mit Unter-
legscheiben und Federringen am
Kühlkörper montiert werden.
FIG. 3: Stellen Sie sicher, dass der
Kühlkörper in der passenden Ausrich-
tung montiert wird, damit ein ungehin-
derter Luftstrom durch den Kühlkörper
gewährleistet ist.
Instrucciones de montaje
FIG. 1: Retire la cubierta antes de
montar el SSR en el chasis del panel
o en el disipador de calor.
FIG. 2: Asegurarse de seleccionar el
disipador de calor adecuado. Apretar
el relé estático, alternativamente entre
los 2 tornillos con un par de apriete
máx. de 2.0 Nm. Hay que montar el
relé RK en el disipador usando dos
tornillos M5 con arandelas planas y de
tipo muelle.
FIG. 3: Instalar el disipador con la ori-
entación correcta, de manera que no
se obstruya la circulación de aire a
través del disipador.
Istruzioni per l'Installazione
FIG. 1: Rimuovere la copertura prima di
montare l'SSR sullo chassis del pan-
nello o sul dissipatore di calore.
FIG. 2: Assicurarsi di selezionare il dis-
sipatore di calore adeguato. Stringere,
alternativamente, le viti di fissaggio del
SSR con una coppia massima di 2,0
Nm. I modelli RK devono essere mon-
tati sul dissipatore, utilizando due viti M5
con rondella piana ed elastica.
FIG. 3: Montare il dissipatore di calore
nella posizione corretta, in modo da
consentire il corretto flusso d'aria attra-
verso il componente.
Руководство по монтажу
РИС. 1: Перед установкой ТТР в щит,
в шасси или на радиатор снимите за-
щитный слой.
РИС. 2: Убедитесь, что радиатор по-
добран адекватно. Затяните винты
клемм ТТР постепенно и попере-
менно, макс. до 2.0 Нм. RK должен
монтироваться на радиатор при по-
мощи винтов M5 с плоскими и пру-
жинными шайбами.
РИС. 3: Устанавливайте радиатор в
правильном положении, с беспрепят-
ственным проходом воздуха.
安装说明
图1:在将 SSR 装在面板底盘或散
器上前,请撕掉衬里。
2:
SSR,交替拧紧两颗螺钉至最大扭矩2.0
Nm。应使用两颗M5 螺钉以及平垫圈和
弹簧垫圈将 RK 安装到散热器上。
3:
通过散热器的气流受阻。
Dimensions (mm) | Dimensioner (mm) | Dimensiones
(mm) | Abmessungen (mm) | Dimensions (mm) | Di-
mensioni (mm) | Размеры (мм) | 尺寸(mm)
RK..C
RK..P
Phase
Phase/Neutral
PE
L1
L2
L3
N
PE
F1
F1 F1
F1
F1 F1
E
NGLISH
ATTENTION
Hazardous Voltage can cause death or serious injury. Disconnect power
b
efore proceeding with any work on this equipment. Never touch the terminals of
the solid state relay if voltage is present at its terminals. The output terminals
remain live even in the off-state (leakage current, SSR breakdown). Heatsink may
b
e hot, even after removing the power. The SSR may get damaged in case of a
short circuit condition. Install a protective device such as semiconductor fuses to
protect SSR against short circuits.
IMPORTANT
S
hould you require information about installation, operation or maintenance of the
product that is not covered in this instruction document you should refer the matter
to an authorised Carlo Gavazzi representative. The information in this document
is not considered binding on any product warranty.
- Only authorised and qualified personnel should be allowed to install and
perform maintenance on this equipment
- Always use the SSR within its rated specifications and follow provided
i
nstructions otherwise malfunction, damage or fire may result
- Heat generated by incorrect terminations may result in fire. Ensure the use of
proper cable sizes and allow an adequate radius of curvature for wire bends
- Loose terminals generate abnormal heat. Tighten to the specified torque. Re-
tighten after 48 hours to minimize wire cold flow. Re-torque every 3 - 6 months
-
Ensure proper ventilation in the panel
- For use in Pollution Degree 2 Environment
- For use in a circuit where devices or system, including filters or air gaps, are
used to control overvoltages at the maximum rated impulse withstand voltage
peak of 6 kV on output. Devices or system shall be evaluated using the
requirements in the Standard for Transient Voltage Surge Suppressors, UL
1449 and shall also withstand the available short circuit current in accordance
with UL 1449
- The opening of the branch-circuit protective device may be an indication that a
fault has been interrupted. To reduce the risk of fire or electric shock, current-
carrying parts and other components of the controller should be examined and
replaced if damaged. If burnout of the current element of an overload relay
occurs, the complete overload relay must be replaced
- This product has been designed for Class A equipment (external filtering may
be required). Use of this product in domestic environments may cause radio
interference, in which case the user may be required to employ additional
mitigation methods
D
ANSK
B
EMÆRK
F
arlig spænding kan forsage dsfald eller alvorlig personskade. Afbryd udstyret,
inden du forttter med at udføre arbejde på dette udstyr. Rør aldrig ved terminalerne
p
å halvlederrelæet (SSR), hvis der er spænding til stede terminalerne.
Ydelsesterminalerne forbliver stmrende selv i slukket tilstand (lækagestrøm, SSR-
s
vigt). Varmeaflederen forbliver varm, selv efter at strømmen er blevet afbrudt.
H
alvlederreet kan blive ødelagt i tilfælde af en kortslutning, hvis det ikke beskyttes af
halvledersikringer.
V
IGTIGT
fremt du har behov for oplysninger vedrørende installation, betjening eller
v
edligeholdelse af produktet, der ikke er indeholdt i dette dokument, bedes du rette
henvendelse til en autoriseret Carlo Gavazzi-repsentant. Oplysningerne i dette
dokument er ikke bindende i henhold til nogen produktgaranti.
-
Det er kun autoriseret personale, der må installere og udre vedligeholdelse på
d
ette udstyr
- Anvend altid SSR'en inden for de angivne specifikationer og lg de angivne
i
nstruktioner, da der ellers vil være risiko for fejlfunktion, skader eller brand
- Varme, der opstår som følge af forkerte slutninger, kan forårsage brand. Sørg for at
benytte kabler i den rette størrelse, og sørg for, at der er en passende radius med
plads til ledningerne, de ikke bøjes for meget
- Løse klemmer kan generere unormal varme. Tilspænd til det angivne
drejningsmoment. Spænd igen efter 48 timer for at minimere ledningskrybning.
Genspænd til momentet hver 3. til 6. måned
- Sørg for at sikre tilstkkelig panelventilation
- Til brug i miljøer med forureningsgrad 2
- Til brug et kredsløb, hvor enheder eller systemer, herunder filtre eller luftgab,
anvendes til at kontrollere oversnding ved den maksimalt lte
impulsmodstandsspidsspænding 6 kV på udgange. Enheder eller systemer skal
vurderes ved hjælp af kravene i standarden for transiente
spændingsbølgestøjdæmpningsanordninger, UL1449, og skal ligeledes kunne
modstå den tilgængelige kortslutningsstrøm i henhold til UL1449
-
Åbningen af den linjeforgreningsbeskyttede enhed kan indikere, at en fejl er blevet
afbrudt. For at mindske faren for brand eller elektrisk stødr de strømførende dele
og andre komponenter på halvlederen undersøges og udskiftes, hvis de er
fejlbehæftede. Hvis der forekommer en kortslutning på spændingselementet til et
overbelastningsrelæ, skal hele overbelastningsreet udskiftes
- Dette produkt er blevet udformet til klasse A-udstyr (et udvendigt filter kan være
krævet). Brugen af dette produkt i husholdninger kan forårsage radiointerferens.
Hvis dette sker, kan brugeren blivelagt at anvende yderligere reduceringsmetoder
F
RANCAIS
A
TTENTION DANGER
Tension électrique dangereuse susceptible de provoquer la mort ou de graves
préjudices corporels. Couper l'alimentation secteur du relais avant toute intervention
sur le matériel. Éviter impérativement tout contact avec les bornes du relais statique
lorsqu'il est alimenté. Les bornes de sortie restent sous tensionme à l'état bloqué
(courant de fuite, claquage du relais). Le dissipateur peut être brûlant, même après
mise hors tension. Protéger le relais par des fusibles à semi-conducteurs pour éviter
toute avarie en cas de court-circuit.
IMPORTANT
Pour plus amples détails concernant l'installation, le fonctionnement ou la maintenance du
produit et n'apparaissant pas dans cette fiche technique, consulter un concessionnaire
a
gréé Carlo Gavazzi. Les informations contenues figurant dans ce document ne constituent
aucune obligation de garantie de quelconque nature.
- Seul un personnel autoriet qualifié est habili à installer et à effectuer des opérations
d
e maintenance sur ce produit
- Toujours utiliser le relais statique à l'intérieur des limites spécifiées. Respecter les
i
nstructions fournies sous peine de dysfonctionnement, avarie ou risque d'incendie
- La chaleur générée par des terminaisons incorrectes peut provoquer un incendie.
S'assurer que la section des fils utilisée est correcte et le cas échéant, que le rayon de
c
ourbure des fils est adéquat
- Les connecteurs desserrés génèrent une chaleur anormale. Serrer au couple spécif.
R
esserrer après 48 heures pour minimiser la formation sous charge. Resserrer au
couple indiq tous les 3 à 6 mois
- Veiller à une ventilation aquate du tableau
- Pour exploitation en environnement de deg de pollution 2
- Pour utilisation dans un circuit équipé de dispositifs ou d'un sysme (incluant des filtres
ou des entrefers) contlant les surtensions à la tension maximale d'impulsion supportée
de 6 kV sur la sortie. Les dispositifs ou le système doivent être évalués selon les
exigences de la norme UL1449 intitue Suppresseurs des surtensions transitoires. Ils
doivent également résister au courant de court-circuit disponible, selon la norme UL1449
- L'ouverture du dispositif de protection de la branche du circuit peut indiquer une
interruption du défaut. Pour réduire le risque d'incendie ou dlectrocution, inspecter les
parties porteuses de courant et autre composants du contleur et les remplacer en cas
d'avarie. En cas de carbonisation de l'élément de courant d'un relais de surcharge,
remplacer le relais de surcharge en totali
- Ce produit est cou pour les équipements de Classe A (un filtrage externe peut être
requis). En raison des interférences radio magnétiques que ce produit est susceptible
de nérer en environnement sidentiel, il pourra être demandé à l'utilisateur de mettre
eneuvre des thodes supplémentaires
d'atténuation
D
EUTSCH
A
CHTUNG
Hochspannung kann zum Tod führen oder schwere Verletzungen hervorrufen. Trennen Sie die
S
tromversorgung, bevor Sie Arbeiten jedweder Art an dem Gerät durchführen. Berühren Sie niemals die
A
nschlüsse des Halbleiterrelais (Halbleiterrelais/-schütz), wenn an den Anschlüssen Spannung anliegt. Die
Ausgangsanschlüssehren auch im Aus-Zustand Spannung (Leckstrom, Ausfall des SSR). Der
K
ühlkörper kann auch nach dem Abschalten des Gerätes noch hohe Temperaturen aufweisen. Das
Halbleiterrelais/-schütz kann durch Kurzschlüsse bescdigt werden, wenn es nicht durch
Halbleitersicherungen abgesichert ist.
WICHTIG
W
enn Sie Informationen zur Installation, zum Betrieb oder zur Wartung des Produkts betigen, die nicht
in dieser Anleitung enthalten sind, wenden Sie sich mit Ihrer Frage an einen autorisierten Vertriebspartner
v
on Carlo Gavazzi. Die Informationen in -diesem Dokument sind nicht bindend hinsichtlich der
Produktgewährleistung.
- Die Installation und Wartung dieses Geräts darf nur von qualifiziertem Fachpersonal durchgeführt
w
erden
- Betreiben Sie das SSR stets innerhalb der Spezifikationen und gemäß den beiliegenden Anweisungen,
d
a es andernfalls zu Fehlfunktionen
- Bei fehlerhafter Ausführung der Anschlüsse kann die entstehende Wärme zu Brandgefahr führen.
Stellen Sie sicher, dass die verwendeten Leitungen eine geeignete Größe aufweisen und an
B
iegestellen ausreichend Platz für einen geeigneten Kurvenradius zur Verfügung steht
- Lose Anschlüsse können zu übermäßiger Wärmeentwicklung hren. Befestigen Sie die Anschlüsse
mit dem vorgegebenen Anzugsdrehmoment. Ziehen Sie die Anschlüsse nach 48 Stunden nach, um
den Kaltfluss zu minimieren. Ziehen Sie die Anschlüsse alle 3–6 Monate nach
- Stellen Sie ausreichende Belüftung der Schalttafel sicher
- Stellen Sie die ausreichende Belüftung der Schalttafel sicher. Für die Verwendung in einer Umgebung
mit dem Verschmutzungsgrad 2
- Für die Verwendung in Schaltkreisen, die Vorrichtungen oder ein System wie Filter oder Luftspalten
enthalten, welche sicherstellen, dass der ert der maximal zussigen Nennstoßstehspannung von 6 kV
am Ausgang nicht überschritten wird. Die Einrichtungen oder das System müssen gemäß den
Anforderungen der Norm für Überspannungsableiter, UL1449, überprüft werden und müssen geß
UL1449 dem auftretenden Kurzschlussstrom widerstehen können
- Das Öffnen der Schutzeinrichtung des Stromzweigs kann ein Hinweis darauf sein, dass ein
Fehlerzustand unterbrochen wurde. Um die Brandgefahr und die Gefahr elektrischer Schläge zu
reduzieren, müssen stromführende Bauteile und andere Komponenten des Controllers überprüft und
ersetzt werden, falls sie beschädigt sind. Wenn beim Stromelement des Überstromrelais ein Burnout
auftrat, muss das gesamte Überstromrelais ausgetauscht werden
- Das Produkt wurde für Geräte der Klasse A entwickelt (möglicherweise externe Filter erforderlich). Der
Einsatz des Produkts in Wohnumgebungen kann Funksrungen hervorrufen. Unter diesen
Umständen ist der Anwender möglicherweise verpflichtet, zusätzliche Abhilfemaßnahmen zu ergreifen
ESPAÑOL
ATENCIÓN
Tensiones peligrosas pueden causar la muerte o provocar serios daños.
Desconecte siempre la tensión antes de manipular el equipo. No toque nunca los
terminales del relé estático si hubiera tensión en ellos. Los terminales de salida
permanecen activas incluso si el equipo esdesconectado (corriente de fuga, rotura
del relé estático). El disipador puede incluso estar caliente, aún desconectado el
equipo. El relé estático puede resultar dañado en caso de cortocircuito si no está
protegido con fusibles semiconductores.
IMPORTANTE
En caso de necesitar informacn sobre la instalacn funcionamiento o mantenimiento
del producto que no venga reflejada en este documento de instrucciones, deberá
consultar con su distribuidor o con una oficina de Carlo Gavazzi. La información de
este documento no se considera vinculante con la garantía del producto.
- Solo personal autorizado y cualificado puede instalar y realizar labores de
mantenimiento de este equipo
- Asegúrese de que el relé estático se usa dentro de los valores nominales
especificados y siguiendo las instrucciones, en caso contrario podría producirse un
funcionamiento erróneo, daños o incendio
- El calor generado por terminaciones incorrectas puede provocar un incendio.
Asegurarse de que se usa el tamaño de cable adecuado y que se permite un radio
de curvatura apropiado para poder doblar el cable
- Terminales flojos generan un calor anormal. Apretar usando el par de apriete
especificado y volver a apretar pasadas 48 horas para reducir el flujo de frío en el
cable. Apretar todo cada 3 - 6 meses
- Asegúrese de que el panel está bien ventilado
- Para uso en entornos con grado de contaminación 2
- Para uso en un circuito donde los equipos o el sistema, incluyendo filtros o
separación física, se utilizan para el control de sobretensiones con6picos ximos
de tensión de hasta 4kV en la salida. Los equipos o el sistema deben ser evaluados
bajo los requisitos de la norma para supresores de picos de tensión transitorios,
UL1499 y deben soportar la intensidad de cortocircuito disponible según UL1449
- La apertura de la parte protectora del circuito puede indicar que se ha interrumpido
un fallo. Para reducir el riesgo de incendio o descarga eléctrica, las partes
conductoras y otros componentes del relé deben comprobarse y reemplazarlas si
hubiera daños. Si se quema la parte de intensidad del relé de sobrecarga, hay que
reemplazar dicho relé de sobrecarga
- El reestático RK es un equipo Clase A (se necesita filtro externo). Si se usa con
electrodomésticos puede causar radiointerferencias. Es posible que se precise
añadir métodos adicionales para disminuir las interferencias
ITALIANO
ATTENZIONE
Pericolo alta tensione può causare morte o gravi lesioni. Scollegare
l'alimentazione prima di procedere con qualsiasi intervento su questa apparecchiatura.
Non toccare mai i terminali del relè allo stato solido (SSR) se è presente tensione ai
suoi capi. I morsetti di uscita rimangono in tensione anche in stato OFF (dispersione
di corrente oppure SSR guasto). Il dissipatore di calore può essere caldo, anche dopo
aver tolto l'alimentazione. L’SSR può danneggiarsi in caso di corto circuito, se non è
protetto da fusibili
.
IMPORTANTE
Se avete bisogno di informazioni su installazione, funzionamento o manutenzione del
prodotto non riportate in questo documento è necessario sottoporre la questione ad un
rappresentante autorizzato Carlo Gavazzi. Le informazioni contenute in questo
documento non sono da considerare vincolanti per alcuna garanzia sul prodotto.
- L’installazione e la manutenzione di questo dispositivo devono essere effettuate da
personale autorizzato e qualificato
- Utilizzare sempre lSSR entro i limiti di funzionamento, come da specifiche tecniche. In
caso contrario si potrebbero verificare malfunzionamenti, danneggiamenti o principi di
incendio
-
Il calore generato da una non corretta installazione / terminazione dei cavi di collegamento
può causare rischio di incendio. Assicurarsi di utilizzare la sezione di cavo più adatto alla
specifica applicazione e garantire un adeguato raggio di curvatura dei conduttori
- Un serraggio meccanico dei terminali, non corretto, può generare un surriscaldamento
degli stessi. Assicurarsi che le viti dei morsetti siano strette con la coppia di serraggio
appropriata. Ricontrollare i cablaggi dopo 48 ore dalla prima installazione. Effettuare
ulteriori controlli ogni 3-6 mesi
- Garantire la corretta ventilazione all’interno del quadro
- Per utilizzo in ambiente con grado di inquinamento 2
- Per l'uso in un circuito in cui vengono utilizzati altri dispositivi, tra cui filtri, per il controllo
di sovratensioni con picchi di tensione di 6 kV in uscita. Dispositivi devono essere valutati
sulla base dei requisiti della norma per la soppressione dei transitori di tensione, UL1449
e deve anche sopportare la corrente di corto circuito dis ponibile secondo UL1449
- L'apertura del dispositivo di protezione può essere un'indicazione di guasto. Per ridurre
il rischio di incendi o scosse elettriche, le parti conduttive, gli altri componenti del
dispositivo dovrebbero essere esaminate e sostituite in caso di danneggiamento. Se
viene danneggiato da un sovraccarico di corrente, sarà necessario sostituire tutto
- Questo prodotto è stato progettato per apparecchiature di classe A (può essere richiesto
filtro esterno). L'uso di questo prodotto in ambienti domestici p causare interferenze
radio, nel qual caso l'utente è tenuto a ricorrere a metodi
РУССО
Опасное напряжение может привести к смерти или серьезному увечью. -
Отключите питание перед началом любых работ на оборудовании. Не
прикасайтесь к клеммам ТТР при наличии на них напряжения. На выходных
клеммах даже в отключенном состояние может оставаться напряжение ок
утечки, пробой ТТР). Радиатор может быть горячим, даже после отключения
напряжения. При КЗ ТТР может быть повреждено. Установите защитное
устройство, такое как полупроводниковый предохранитель для защиты ТТР от КЗ.
ВАЖНО
- Если Вам требуется информация по электромонтажу, эксплуатации или
обслуживанию изделия, не содержащаяся в настоящем Руководстве, обратитесь с
Вашим вопросом к местному авторизованному представителю Carlo Gavazzi.
Информация в этом документе не считается связанной с любыми гарантиями на изделие.
- Только авторизованный и квалифицированный персонал имеет право
установки и обслуживания данного оборудования
- Применяйте ТТР в цепях, параметры которых не превышают их номиналов
и строго следуйте указаниям настоящего Руководства, в противном случае
возможны неправильная работа, повреждение устройства или возгорание
- Нагрев при некачественном электромонтаже на клеммах может вызвать пожар. Применяйте
кабели с надлежащим сечением проводников. При слабом затяге клеммы испытывают
нагрев. Затяните клеммы до указанного момента. Подтяните винты через 48 ч во избежание
ослабления при перепаде температуры. Контроль затяга через 3 6 месяцев
- Установите ТТР в предписанной руководством ориентации для
обеспечения беспрепятственного доступа воздуха к радиатору ТТР.
Обеспечьте надлежащую вентиляцию электрощита управления.
- Для применения при Степени Загрязнения 2
- Для цепей с устройствами или системами, включая фильтры или воздушные
зазоры, используемыми для контроля перенапряжения при максимальном
номинальном пиковом напряжении импульса 2.5 кВ на входе, 6 кВ на выходе.
Такие устройства или системы оцениваются в соответствии с требованиями
Стандарта Подавления Переходных Бросков Напряжения, UL 1449 они
должны противостоять имеющимся в цепи токам КЗ в соответствии с UL 1449
- Клеммы управления A1, A2 (RG..A) получают питание с цепи вторичной обмотки,
мощность которых ограничена трансформатором, выпрямителем, делителем
напряжения или аналогичными устройствами, преобразующими мощность от
первичной обмотки, и где ограничение тока КЗ между проводниками вторичной обмотки
иди между проводниками и «землей» составляет 1500 ВА или менее. Граничное
значение мощности в ВА это произведение напряжения незамкнутой цепи и тока КЗ
- Срабатывание локальных защитных устройств электроцепей могут быть
показателем неисправности. Для снижения риска пожара или поражения
электрическим током следует проверить токоведущие части и другие
компоненты устройства и заменить их в случае повреждения. При повреждении
измерительного модуля реле перегрузки замене подлежит реле тока целиком
- Устройство разработано для оборудования Класса A (может потребоваться внешний фильтр).
Применение изделия в жилых помещениях может вызвать радиопомехи, в этом случае
пользователю необходимо использовать дополнительные способы помехоподавления
简体中文
注意事项
危险电压可能导致死亡或严重 伤害。继续对本设备进行任何操作之前,请断
源。如果固态继电器的 端子上有电压,请勿触摸 端子。即使在断电状态(漏电流
,SSR击穿)下,输出端子仍然带电。散热器可能很烫,即使是断电之后。SSR 在
短路情况下可能坏。安装半导体熔断器保护装置以SSR 短
重要事项
- 如果您需要本说明文档未涵盖的产品的安装、操作维护等相关信息,请咨询
Carlo Gavazzi 授权表。本文档中的信息 对任何产品保修均无约束力。
- 只允许经过授权的合格人员装和维本设
- 务必在其额定规格参数范围内使用 SSR,并按照规定说明操作,否则 可能导致故
障、损坏或火灾
- 不正确的端接生的热量能导致火。确保使的电缆规正确。端松动会产
生异常热量。拧紧至规定扭矩。48 小时后再次拧紧,以最大限度降低导线冷变
。每 3 6 个月重新拧
- 按照规定方向安装 SSR,不要阻挡气流流向 SSR 散热器。确保面板通风良好
- 适用于 2污染环
- 适用于使用设备或系统(包括滤波器或气隙)在输出的 最大额定脉冲耐受电压
值为 6 kV时,控制过电压的电路。设备 或系统应按照 瞬态电压浪涌抑制器标准
UL 1449的要求进行评估,还应能耐受符合 UL 1449 标准的可用短路电流
- REC 设备的控制端子 A1、A2(RG..A)应由一个二次回路供电。在此回路中,
率由从一次回路获得功率的一个变压器、整流器、分压器或类似器件加以限制,
二次回路导线之间或导线与地线之间的短路限制是 1500 VA 或以下。短路伏安限
值是开路电压和短路安培数的乘
- 分支电路保护装置开路 可能表示故障已经 中断。为了降低火灾或触电的危险,
制器的载流部件和其他 部件如有损坏,应进行检查 和更换。如果过载继电器的
流元件烧毁,必更换整个过载继电器
- 本产品系为 A 设备设计(可能需要外部滤波)。在庭环境中使用本产品时,
可能会导致无线电干扰,在这种情况下,用可能需要采用其他缓解 方

Transcripción de documentos

F1 F1 F1 F1 L1 L1 L2 L2 L3 L3 N N PE PE F1 F1 F1 F1 F1 F1 RKD2, RK2 - Mains Connection, Pole A RKD2, RK2 - Load Connection, Pole A RKD2, RK2 - Mains Connection, Pole B RKD2, RK2 - Load Connection, Pole B RKD2 - Control Signal, Pole A RK2 - Control Signal, Pole A & B RKD2 - Ground, Pole A RK2 - Ground, Pole A & B RKD2 - Control Signal, Pole B RKD2 - Ground, Pole B F1 Mersen Siba RK..50 50A, FR22UD69V50T 50A, 50 142 06.50 RK..51 63A, FR22UD69V63T 63A, 50 142 06.63 RK..75 80A, FR22GR69V80T 100A, 50 142 06.100 Use 60/75oC copper (Cu) conductors 12 mm X B1(+): B2(-): RK..P F1 F1 X A2(-): 2 Pole, Solid State Relays A1, A2 B1, B2 1/L1, 2/T1 3/L2, 4/T2 RK..C RK..C RK..P RK..P Use 75oC copper (Cu) conductors 1/L1: 2/T1: 3/L2: 4/T2: A1(+): RK Series 7680581-03 Phase Phase Phase/Neutral Phase / Neutral PE PE Terminations | Termineringer | Terminales | Anschlusseigenschaften | Terminations | Terminali | Клеммы | 端接 8 - 9 mm 2 x 2.5 - 6.0 mm2 1 x 2.5 - 6.0 mm2 2 x 14 - 10 AWG 1 x 14 - 10 AWG 0.5 - 2.5 mm2 26 - 12 AWG 2 x 1.0 - 2.5 mm2 2 x 2.5 - 6.0 mm2 1 x 1.0 - 6.0 mm2 2 x 18 - 14 AWG 1 x 14 - 10 AWG 2 x 14 - 10 AWG 0.5 - 2.5 mm2 26 - 12 AWG - 0.5 - 1.5 mm2 max. 12.5 mm - Pozidrive bit 2 UL: 2 .0 Nm (17.7 lb-in) IEC: 1.5 - 2.0 Nm (13.3 - 17.7 lb-in) - Dimensions (mm) | Dimensioner (mm) | Dimensiones (mm) | Abmessungen (mm) | Dimensions (mm) | Dimensioni (mm) | Размеры (мм) | 尺寸(mm) RK..C Connection of ring terminals | Forbindelse af ringterminaler | Conexión de los terminales de anillo | Raccordement de cosses rondes|Verbindung mit Ringkabelschuhen | Collegamento dei terminali | Подключение кольцевыми кабельными наконечниками | 环形端子的连接 • • • • Operating Instructions • Kom godt i gang Bedienungsanleitung • Notice d'utilisation Instrucciones • Istruzioni d’uso Руководство по эксплуатации • 操作说明 FIG. 1 FIG. 2 FIG. 3 Do not touch pre-attached thermal interface | Rør ikke ved forudgående termisk grænseflade | No toque la interfaz térmica preinstalada | Berühren Sie nicht die vormontierte thermische Schnittstelle | Ne touchez pas l'interface thermique pré-attachée | Non toccare l'interfaccia termica preassemblata Mounting Instructions Installationsvejledning Instructions d'installation FIG. 1: Retirez le couvercle avant de monter le SSR sur le châssis du panneau ou le dissipateur thermique. FIG. 1: Remove cover before mounting the SSR on the panel chassis or heatsink. FIG. 1: Fjern dækslet, før du monterer SSR'en på panelets chassis eller køler. FIG. 3: Mount the heatsink in the correct orientation so as not to obstruct airflow through the heatsink. FIG. 3: Montér kølepladen, så den vender korrekt og ikke blokerer for lufstrømmen via kølepladen. FIG. 3: Au montage, orienter correctement le dissipateur, afin de permettre au flux d'air de le traverser. Istruzioni per l'Installazione Руководство по монтажу FIG. 2: Make sure to select an adequate heat dissipator. Tighten the SSR, alternating between the 2 screws to max. 2.0 Nm. The RK should be mounted to the heat dissipator using two M5 screws with flat and spring washers. MAX 25mm2 Cable with Crimped Ring Terminal CARLO GAVAZZI LTD BLB042, Bulebel Industrial Estate Zejtun ZTN 3000, Malta www.gavazzi-automation.com [email protected] info: +356 23601.100 fax: +356 23601.111 RK_inst_leaf_ 07_18 Connection Diagram | Forbindelsesdiagram | Diagrama de conexiones | Anschlussbelegung | Schémas des connexions | Schema di collegamento | Схема подключения | 连接图 FIG. 2: Sørg for at vælge en passende varmeafleder. Tilspænd SSR'en, skift mellem de 2 skruer til maks. 2,0 Nm. RK'en bør monteres på varmelederen ved hjælp af to M5skruer med underlags- og fjederskiver. FIG. 2: Assurez-vous de choisir un dissipateur adapté. Serrer le relais statique au couple maxi de 2.0 Nm en approche, en alternant d'une vis à l'autre. Visser le relais statique RK sur le dissipateur thermique au moyen des deux vis M5 avec plat et rondelles élastiques. M4 screw with captivated washer RK..P Instrucciones de montaje FIG. 1: Retire la cubierta antes de montar el SSR en el chasis del panel o en el disipador de calor. FIG. 2: Asegurarse de seleccionar el disipador de calor adecuado. Apretar el relé estático, alternativamente entre los 2 tornillos con un par de apriete máx. de 2.0 Nm. Hay que montar el relé RK en el disipador usando dos tornillos M5 con arandelas planas y de tipo muelle. Removable IP20 Cover FIG. 3: Instalar el disipador con la orientación correcta, de manera que no se obstruya la circulación de aire a través del disipador. FIG. 1: Rimuovere la copertura prima di montare l'SSR sullo chassis del pannello o sul dissipatore di calore. FIG. 2: Assicurarsi di selezionare il dissipatore di calore adeguato. Stringere, alternativamente, le viti di fissaggio del SSR con una coppia massima di 2,0 Nm. I modelli RK devono essere montati sul dissipatore, utilizando due viti M5 con rondella piana ed elastica. FIG. 3: Montare il dissipatore di calore nella posizione corretta, in modo da consentire il corretto flusso d'aria attraverso il componente. РИС. 1: Перед установкой ТТР в щит, в шасси или на радиатор снимите защитный слой. РИС. 2: Убедитесь, что радиатор подобран адекватно. Затяните винты клемм ТТР постепенно и попеременно, макс. до 2.0 Нм. RK должен монтироваться на радиатор при помощи винтов M5 с плоскими и пружинными шайбами. РИС. 3: Устанавливайте радиатор в правильном положении, с беспрепятственным проходом воздуха. Installationsanleitungen FIG. 1: Entfernen Sie die Abdeckung, bevor Sie das SSR am Gehäuse oder Kühlkörper des Panels montieren. FIG. 2: Stellen Sie sicher, dass ein geeigneter Kühlkörper ausgewählt wird. Befestigen Sie das SSR, indem Sie die beiden Schrauben abwechselnd bis zu einem maximalen Anzugsdrehmoment von 2,0 Nm anziehen. Das RK muss mithilfe zweier M5-Schrauben mit Unterlegscheiben und Federringen am Kühlkörper montiert werden. FIG. 3: Stellen Sie sicher, dass der Kühlkörper in der passenden Ausrichtung montiert wird, damit ein ungehinderter Luftstrom durch den Kühlkörper gewährleistet ist. 安装说明 图1:在将 SSR 安装在面板底盘或散热 器上前,请撕掉衬里。 图 2: 务 必 选 择 适 当 的 散 热 器 。 拧 紧 SSR,交替拧紧两颗螺钉至最大扭矩2.0 Nm。应使用两颗M5 螺钉以及平垫圈和 弹簧垫圈将 RK 安装到散热器上。 图3:按正确的方向安装散热器,以免 通过散热器的气流受阻。 ENGLISH DANSK FRANCAIS DEUTSCH IMPORTANT Should you require information about installation, operation or maintenance of the product that is not covered in this instruction document you should refer the matter to an authorised Carlo Gavazzi representative. The information in this document is not considered binding on any product warranty. - Only authorised and qualified personnel should be allowed to install and perform maintenance on this equipment - Always use the SSR within its rated specifications and follow provided instructions otherwise malfunction, damage or fire may result - Heat generated by incorrect terminations may result in fire. Ensure the use of proper cable sizes and allow an adequate radius of curvature for wire bends - Loose terminals generate abnormal heat. Tighten to the specified torque. Retighten after 48 hours to minimize wire cold flow. Re-torque every 3 - 6 months - Ensure proper ventilation in the panel - For use in Pollution Degree 2 Environment - For use in a circuit where devices or system, including filters or air gaps, are used to control overvoltages at the maximum rated impulse withstand voltage peak of 6 kV on output. Devices or system shall be evaluated using the requirements in the Standard for Transient Voltage Surge Suppressors, UL 1449 and shall also withstand the available short circuit current in accordance with UL 1449 - The opening of the branch-circuit protective device may be an indication that a fault has been interrupted. To reduce the risk of fire or electric shock, currentcarrying parts and other components of the controller should be examined and replaced if damaged. If burnout of the current element of an overload relay occurs, the complete overload relay must be replaced - This product has been designed for Class A equipment (external filtering may be required). Use of this product in domestic environments may cause radio interference, in which case the user may be required to employ additional mitigation methods VIGTIGT Såfremt du har behov for oplysninger vedrørende installation, betjening eller vedligeholdelse af produktet, der ikke er indeholdt i dette dokument, bedes du rette henvendelse til en autoriseret Carlo Gavazzi-repræsentant. Oplysningerne i dette dokument er ikke bindende i henhold til nogen produktgaranti. - Det er kun autoriseret personale, der må installere og udføre vedligeholdelse på dette udstyr - Anvend altid SSR'en inden for de angivne specifikationer og følg de angivne instruktioner, da der ellers vil være risiko for fejlfunktion, skader eller brand - Varme, der opstår som følge af forkerte slutninger, kan forårsage brand. Sørg for at benytte kabler i den rette størrelse, og sørg for, at der er en passende radius med plads til ledningerne, så de ikke bøjes for meget - Løse klemmer kan generere unormal varme. Tilspænd til det angivne drejningsmoment. Spænd igen efter 48 timer for at minimere ledningskrybning. Genspænd til momentet hver 3. til 6. måned - Sørg for at sikre tilstrækkelig panelventilation - Til brug i miljøer med forureningsgrad 2 - Til brug på et kredsløb, hvor enheder eller systemer, herunder filtre eller luftgab, anvendes til at kontrollere overspænding ved den maksimalt målte impulsmodstandsspidsspænding på 6 kV på udgange. Enheder eller systemer skal vurderes ved hjælp af kravene i standarden for transiente spændingsbølgestøjdæmpningsanordninger, UL1449, og skal ligeledes kunne modstå den tilgængelige kortslutningsstrøm i henhold til UL1449 - Åbningen af den linjeforgreningsbeskyttede enhed kan indikere, at en fejl er blevet afbrudt. For at mindske faren for brand eller elektrisk stød bør de strømførende dele og andre komponenter på halvlederen undersøges og udskiftes, hvis de er fejlbehæftede. Hvis der forekommer en kortslutning på spændingselementet til et overbelastningsrelæ, skal hele overbelastningsrelæet udskiftes - Dette produkt er blevet udformet til klasse A-udstyr (et udvendigt filter kan være påkrævet). Brugen af dette produkt i husholdninger kan forårsage radiointerferens. Hvis dette sker, kan brugeren blivepålagt at anvende yderligere reduceringsmetoder IMPORTANT Pour plus amples détails concernant l'installation, le fonctionnement ou la maintenance du produit et n'apparaissant pas dans cette fiche technique, consulter un concessionnaire agréé Carlo Gavazzi. Les informations contenues figurant dans ce document ne constituent aucune obligation de garantie de quelconque nature. - Seul un personnel autorisé et qualifié est habilité à installer et à effectuer des opérations de maintenance sur ce produit - Toujours utiliser le relais statique à l'intérieur des limites spécifiées. Respecter les instructions fournies sous peine de dysfonctionnement, avarie ou risque d'incendie - La chaleur générée par des terminaisons incorrectes peut provoquer un incendie. S'assurer que la section des fils utilisée est correcte et le cas échéant, que le rayon de courbure des fils est adéquat - Les connecteurs desserrés génèrent une chaleur anormale. Serrer au couple spécifié. Resserrer après 48 heures pour minimiser la déformation sous charge. Resserrer au couple indiqué tous les 3 à 6 mois - Veiller à une ventilation adéquate du tableau - Pour exploitation en environnement de degré de pollution 2 - Pour utilisation dans un circuit équipé de dispositifs ou d'un système (incluant des filtres ou des entrefers) contrôlant les surtensions à la tension maximale d'impulsion supportée de 6 kV sur la sortie. Les dispositifs ou le système doivent être évalués selon les exigences de la norme UL1449 intitulée Suppresseurs des surtensions transitoires. Ils doivent également résister au courant de court-circuit disponible, selon la norme UL1449 - L'ouverture du dispositif de protection de la branche du circuit peut indiquer une interruption du défaut. Pour réduire le risque d'incendie ou d'électrocution, inspecter les parties porteuses de courant et autre composants du contrôleur et les remplacer en cas d'avarie. En cas de carbonisation de l'élément de courant d'un relais de surcharge, remplacer le relais de surcharge en totalité - Ce produit est conçu pour les équipements de Classe A (un filtrage externe peut être requis). En raison des interférences radio magnétiques que ce produit est susceptible de générer en environnement résidentiel, il pourra être demandé à l'utilisateur de mettre eneuvre des méthodes supplémentaires d'atténuation WICHTIG Wenn Sie Informationen zur Installation, zum Betrieb oder zur Wartung des Produkts benötigen, die nicht in dieser Anleitung enthalten sind, wenden Sie sich mit Ihrer Frage an einen autorisierten Vertriebspartner von Carlo Gavazzi. Die Informationen in -diesem Dokument sind nicht bindend hinsichtlich der Produktgewährleistung. - Die Installation und Wartung dieses Geräts darf nur von qualifiziertem Fachpersonal durchgeführt werden - Betreiben Sie das SSR stets innerhalb der Spezifikationen und gemäß den beiliegenden Anweisungen, da es andernfalls zu Fehlfunktionen - Bei fehlerhafter Ausführung der Anschlüsse kann die entstehende Wärme zu Brandgefahr führen. Stellen Sie sicher, dass die verwendeten Leitungen eine geeignete Größe aufweisen und an Biegestellen ausreichend Platz für einen geeigneten Kurvenradius zur Verfügung steht - Lose Anschlüsse können zu übermäßiger Wärmeentwicklung führen. Befestigen Sie die Anschlüsse mit dem vorgegebenen Anzugsdrehmoment. Ziehen Sie die Anschlüsse nach 48 Stunden nach, um den Kaltfluss zu minimieren. Ziehen Sie die Anschlüsse alle 3–6 Monate nach - Stellen Sie ausreichende Belüftung der Schalttafel sicher - Stellen Sie die ausreichende Belüftung der Schalttafel sicher. Für die Verwendung in einer Umgebung mit dem Verschmutzungsgrad 2 - Für die Verwendung in Schaltkreisen, die Vorrichtungen oder ein System wie Filter oder Luftspalten enthalten, welche sicherstellen, dass der ert der maximal zulässigen Nennstoßstehspannung von 6 kV am Ausgang nicht überschritten wird. Die Einrichtungen oder das System müssen gemäß den Anforderungen der Norm für Überspannungsableiter, UL1449, überprüft werden und müssen gemäß UL1449 dem auftretenden Kurzschlussstrom widerstehen können - Das Öffnen der Schutzeinrichtung des Stromzweigs kann ein Hinweis darauf sein, dass ein Fehlerzustand unterbrochen wurde. Um die Brandgefahr und die Gefahr elektrischer Schläge zu reduzieren, müssen stromführende Bauteile und andere Komponenten des Controllers überprüft und ersetzt werden, falls sie beschädigt sind. Wenn beim Stromelement des Überstromrelais ein Burnout auftrat, muss das gesamte Überstromrelais ausgetauscht werden - Das Produkt wurde für Geräte der Klasse A entwickelt (möglicherweise externe Filter erforderlich). Der Einsatz des Produkts in Wohnumgebungen kann Funkstörungen hervorrufen. Unter diesen Umständen ist der Anwender möglicherweise verpflichtet, zusätzliche Abhilfemaßnahmen zu ergreifen ESPAÑOL ITALIANO ATTENTION Hazardous Voltage can cause death or serious injury. Disconnect power before proceeding with any work on this equipment. Never touch the terminals of the solid state relay if voltage is present at its terminals. The output terminals remain live even in the off-state (leakage current, SSR breakdown). Heatsink may be hot, even after removing the power. The SSR may get damaged in case of a short circuit condition. Install a protective device such as semiconductor fuses to protect SSR against short circuits. ATENCIÓN Tensiones peligrosas pueden causar la muerte o provocar serios daños. Desconecte siempre la tensión antes de manipular el equipo. No toque nunca los terminales del relé estático si hubiera tensión en ellos. Los terminales de salida permanecen activas incluso si el equipo está desconectado (corriente de fuga, rotura del relé estático). El disipador puede incluso estar caliente, aún desconectado el equipo. El relé estático puede resultar dañado en caso de cortocircuito si no está protegido con fusibles semiconductores. IMPORTANTE En caso de necesitar información sobre la instalación funcionamiento o mantenimiento del producto que no venga reflejada en este documento de instrucciones, deberá consultar con su distribuidor o con una oficina de Carlo Gavazzi. La información de este documento no se considera vinculante con la garantía del producto. - Solo personal autorizado y cualificado puede instalar y realizar labores de mantenimiento de este equipo - Asegúrese de que el relé estático se usa dentro de los valores nominales especificados y siguiendo las instrucciones, en caso contrario podría producirse un funcionamiento erróneo, daños o incendio - El calor generado por terminaciones incorrectas puede provocar un incendio. Asegurarse de que se usa el tamaño de cable adecuado y que se permite un radio de curvatura apropiado para poder doblar el cable - Terminales flojos generan un calor anormal. Apretar usando el par de apriete especificado y volver a apretar pasadas 48 horas para reducir el flujo de frío en el cable. Apretar todo cada 3 - 6 meses - Asegúrese de que el panel está bien ventilado - Para uso en entornos con grado de contaminación 2 - Para uso en un circuito donde los equipos o el sistema, incluyendo filtros o separación física, se utilizan para el control de sobretensiones con6picos máximos de tensión de hasta 4kV en la salida. Los equipos o el sistema deben ser evaluados bajo los requisitos de la norma para supresores de picos de tensión transitorios, UL1499 y deben soportar la intensidad de cortocircuito disponible según UL1449 - La apertura de la parte protectora del circuito puede indicar que se ha interrumpido un fallo. Para reducir el riesgo de incendio o descarga eléctrica, las partes conductoras y otros componentes del relé deben comprobarse y reemplazarlas si hubiera daños. Si se quema la parte de intensidad del relé de sobrecarga, hay que reemplazar dicho relé de sobrecarga - El relé estático RK es un equipo Clase A (se necesita filtro externo). Si se usa con electrodomésticos puede causar radiointerferencias. Es posible que se precise añadir métodos adicionales para disminuir las interferencias BEMÆRK Farlig spænding kan forårsage dødsfald eller alvorlig personskade. Afbryd udstyret, inden du fortsætter med at udføre arbejde på dette udstyr. Rør aldrig ved terminalerne på halvlederrelæet (SSR), hvis der er spænding til stede på terminalerne. Ydelsesterminalerne forbliver strømførende selv i slukket tilstand (lækagestrøm, SSRsvigt). Varmeaflederen forbliver varm, selv efter at strømmen er blevet afbrudt. Halvlederrelæet kan blive ødelagt i tilfælde af en kortslutning, hvis det ikke beskyttes af halvledersikringer. ATTENZIONE Pericolo alta tensione può causare morte o gravi lesioni. Scollegare l'alimentazione prima di procedere con qualsiasi intervento su questa apparecchiatura. Non toccare mai i terminali del relè allo stato solido (SSR) se è presente tensione ai suoi capi. I morsetti di uscita rimangono in tensione anche in stato OFF (dispersione di corrente oppure SSR guasto). Il dissipatore di calore può essere caldo, anche dopo aver tolto l'alimentazione. L’SSR può danneggiarsi in caso di corto circuito, se non è protetto da fusibili. IMPORTANTE Se avete bisogno di informazioni su installazione, funzionamento o manutenzione del prodotto non riportate in questo documento è necessario sottoporre la questione ad un rappresentante autorizzato Carlo Gavazzi. Le informazioni contenute in questo documento non sono da considerare vincolanti per alcuna garanzia sul prodotto. - L’installazione e la manutenzione di questo dispositivo devono essere effettuate da personale autorizzato e qualificato - Utilizzare sempre l’SSR entro i limiti di funzionamento, come da specifiche tecniche. In caso contrario si potrebbero verificare malfunzionamenti, danneggiamenti o principi di incendio - Il calore generato da una non corretta installazione / terminazione dei cavi di collegamento può causare rischio di incendio. Assicurarsi di utilizzare la sezione di cavo più adatto alla specifica applicazione e garantire un adeguato raggio di curvatura dei conduttori - Un serraggio meccanico dei terminali, non corretto, può generare un surriscaldamento degli stessi. Assicurarsi che le viti dei morsetti siano strette con la coppia di serraggio appropriata. Ricontrollare i cablaggi dopo 48 ore dalla prima installazione. Effettuare ulteriori controlli ogni 3-6 mesi - Garantire la corretta ventilazione all’interno del quadro - Per utilizzo in ambiente con grado di inquinamento 2 - Per l'uso in un circuito in cui vengono utilizzati altri dispositivi, tra cui filtri, per il controllo di sovratensioni con picchi di tensione di 6 kV in uscita. Dispositivi devono essere valutati sulla base dei requisiti della norma per la soppressione dei transitori di tensione, UL1449 e deve anche sopportare la corrente di corto circuito dis ponibile secondo UL1449 - L'apertura del dispositivo di protezione può essere un'indicazione di guasto. Per ridurre il rischio di incendi o scosse elettriche, le parti conduttive, gli altri componenti del dispositivo dovrebbero essere esaminate e sostituite in caso di danneggiamento. Se viene danneggiato da un sovraccarico di corrente, sarà necessario sostituire tutto - Questo prodotto è stato progettato per apparecchiature di classe A (può essere richiesto filtro esterno). L'uso di questo prodotto in ambienti domestici può causare interferenze radio, nel qual caso l'utente è tenuto a ricorrere a metodi ATTENTION DANGER Tension électrique dangereuse susceptible de provoquer la mort ou de graves préjudices corporels. Couper l'alimentation secteur du relais avant toute intervention sur le matériel. Éviter impérativement tout contact avec les bornes du relais statique lorsqu'il est alimenté. Les bornes de sortie restent sous tension même à l'état bloqué (courant de fuite, claquage du relais). Le dissipateur peut être brûlant, même après mise hors tension. Protéger le relais par des fusibles à semi-conducteurs pour éviter toute avarie en cas de court-circuit. РУССО Опасное напряжение может привести к смерти или серьезному увечью. Отключите питание перед началом любых работ на оборудовании. Не прикасайтесь к клеммам ТТР при наличии на них напряжения. На выходных клеммах даже в отключенном состояние может оставаться напряжение (ток утечки, пробой ТТР). Радиатор может быть горячим, даже после отключения напряжения. При КЗ ТТР может быть повреждено. Установите защитное устройство, такое как полупроводниковый предохранитель для защиты ТТР от КЗ. ВАЖНО - Если Вам требуется информация по электромонтажу, эксплуатации или обслуживанию изделия, не содержащаяся в настоящем Руководстве, обратитесь с Вашим вопросом к местному авторизованному представителю Carlo Gavazzi. Информация в этом документе не считается связанной с любыми гарантиями на изделие. - Только авторизованный и квалифицированный персонал имеет право установки и обслуживания данного оборудования - Применяйте ТТР в цепях, параметры которых не превышают их номиналов и строго следуйте указаниям настоящего Руководства, в противном случае возможны неправильная работа, повреждение устройства или возгорание - Нагрев при некачественном электромонтаже на клеммах может вызвать пожар. Применяйте кабели с надлежащим сечением проводников. При слабом затяге клеммы испытывают нагрев. Затяните клеммы до указанного момента. Подтяните винты через 48 ч во избежание ослабления при перепаде температуры. Контроль затяга через 3 … 6 месяцев - Установите ТТР в предписанной руководством ориентации для обеспечения беспрепятственного доступа воздуха к радиатору ТТР. Обеспечьте надлежащую вентиляцию электрощита управления. - Для применения при Степени Загрязнения 2 - Для цепей с устройствами или системами, включая фильтры или воздушные зазоры, используемыми для контроля перенапряжения при максимальном номинальном пиковом напряжении импульса 2.5 кВ на входе, 6 кВ на выходе. Такие устройства или системы оцениваются в соответствии с требованиями Стандарта Подавления Переходных Бросков Напряжения, UL 1449 они должны противостоять имеющимся в цепи токам КЗ в соответствии с UL 1449 - Клеммы управления A1, A2 (RG..A) получают питание с цепи вторичной обмотки, мощность которых ограничена трансформатором, выпрямителем, делителем напряжения или аналогичными устройствами, преобразующими мощность от первичной обмотки, и где ограничение тока КЗ между проводниками вторичной обмотки иди между проводниками и «землей» составляет 1500 ВА или менее. Граничное значение мощности в ВА – это произведение напряжения незамкнутой цепи и тока КЗ - Срабатывание локальных защитных устройств электроцепей могут быть показателем неисправности. Для снижения риска пожара или поражения электрическим током следует проверить токоведущие части и другие компоненты устройства и заменить их в случае повреждения. При повреждении измерительного модуля реле перегрузки замене подлежит реле тока целиком -УстройстворазработанодляоборудованияКлассаA(можетпотребоватьсявнешнийфильтр). Применение изделия в жилых помещениях может вызвать радиопомехи, в этом случае пользователю необходимо использовать дополнительные способы помехоподавления ACHTUNG Hochspannung kann zum Tod führen oder schwere Verletzungen hervorrufen. Trennen Sie die Stromversorgung, bevor Sie Arbeiten jedweder Art an dem Gerät durchführen. Berühren Sie niemals die Anschlüsse des Halbleiterrelais (Halbleiterrelais/-schütz), wenn an den Anschlüssen Spannung anliegt. Die Ausgangsanschlüsse führen auch im Aus-Zustand Spannung (Leckstrom, Ausfall des SSR). Der Kühlkörper kann auch nach dem Abschalten des Gerätes noch hohe Temperaturen aufweisen. Das Halbleiterrelais/-schütz kann durch Kurzschlüsse beschädigt werden, wenn es nicht durch Halbleitersicherungen abgesichert ist. 简体中文 注意事项 危险电压可能导致死亡或严重 伤害。继续对本设备进行任何操作之前,请断 源。如果固态继电器的 端子上有电压,请勿触摸 端子。即使在断电状态(漏电流 ,SSR击穿)下,输出端子仍然带电。散热器可能很烫,即使是断电之后。SSR 在 短路情况下可能 损坏。安装半导体熔断器等 保护装置以防 SSR 短 路。 重要事项 - 如果您需要本说明文档中 未涵盖的产品的安装、操作或 维护等相关信息,请咨询 Carlo Gavazzi 授权 代表。本文档中的信息 对任何产品保修均无约束力。 - 只允许经过授权的合格人员 安装和维护 本设备 - 务必在其额定规格参数范围内使用 SSR,并按照规定说明操作,否则 可能导致故 障、损坏或火灾 - 不正确的端接产生的热量可能导致火灾。确保使用的电缆规格正确。端子松动会产 生异常热量。拧紧至规定扭矩。48 小时后再次拧紧,以最大限度降低导线冷变形 。每 3 至 6 个月重新拧紧 - 按照规定方向安装 SSR,不要阻挡气流流向 SSR 散热器。确保面板通风良好 - 适用于 2 度污染环境 - 适用于使用设备或系统(包括滤波器或气隙)在输出的 最大额定脉冲耐受电压峰 值为 6 kV时,控制过电压的电路。设备 或系统应按照 瞬态电压浪涌抑制器标准 UL 1449 中的要求进行评估,还应能耐受符合 UL 1449 标准的可用短路电流 - REC 设备的控制端子 A1、A2(RG..A)应由一个二次回路供电。在此回路中,功 率由从一次回路获得功率的一个变压器、整流器、分压器或类似器件加以限制, 二次回路导线之间或导线与地线之间的短路限制是 1500 VA 或以下。短路伏安限 值是开路电压和短路安培数的乘积 - 分支电路保护装置开路 可能表示故障已经 中断。为了降低火灾或触电的危险,控 制器的载流部件和其他 部件如有损坏,应进行检查 和更换。如果过载继电器的 电 流元件烧毁,必须 更换整个过载继电器 - 本产品系为 A 类 设备设计(可能需要外部滤波)。在 家庭环境中使用本产品时, 可能会导致无线电干扰,在这种情况下,用户 可能需要采用其他缓解 方法