Inductor DB204C Guía de instalación

Tipo
Guía de instalación
INSTALLATION INSTRUCTIONS FOR IN-LINE DUCT FANS™
READ AND SAVE THESE INSTRUCTIONS
GENERAL SAFETY INSTRUCTIONS
WARNING – RISK OF ELECTRIC SHOCK. CAN CAUSE INJURY OR DEATH: DISCONNECT AND/OR LOCKOUT ALL REMOTE ELECTRIC POWER SUPPLIES BEFORE SERVICING OR INSTALLING.
WHEN THE SERVICE DISCONNECTING MEANS CANNNOT BE LOCKED, SECURELY FASTEN A PROMINENT WARNING DEVICE, SUCH AS A TAG TO THE SERVICE PANEL.
WARNING – USE COPPER SUPPLY WIRES ONLY.
WARNING – FOR GENERAL VENTILATING USE ONLY. DO NOT USE TO EXHAUST HAZARDOUS OR EXPLOSIVE MATERIALS AND VAPORS. DO NOT USE TO EXHAUST AIR LADEN WITH LINT,
GREASE, OR OIL.
WARNING – PRODUCT INTENDED INSTALLATION IS AN INLINE DUCT FAN WITH BOTH ENDS CONNECTED TO DUCTWORK (SEE INSTALLATION INSTRUCTIONS SECTION). FOR ANY OTHER
INSTALLATION, GUARDS MUST BE INSTALLED TO PREVENT UNINTENTIONAL CONTACT WITH MOVING FAN BLADE UNLESS THE UNIT IS MOUNTED WITH THE LOWEST MOVING PARTS AT
LEAST 2.4M (8FT) ABOVE FLOOR OR GRADE LEVEL.
WARNING – FAN IS SUITABLE FOR ONLY CONNECTION TO A DUCT SUPPLYING SINGLE-ROOM DISCHARGE (MODELS: DB100C, DB200C, DB204C, DB205C, DB206C, DB208C, DB306E, DB308E)
Use this unit only in the manner intended by the manufacturer. If you have any questions, contact the manufacturer. You may phone the manufacturer during normal business hours at 1-800-999-3267 or submit
your questions from our website: www.suncourt.com.
In-Line Duct Fans
TM
are designed to boost dry conditioned (heated or cooled) indoor airflow in ducts of forced air systems with temperatures between 40°F (4°C) and 140°F (60°C). Suncourt accepts no
responsibility for use of this product in other applications.
EXPOSURE TO AIRFLOW TEMPERATURES EXCEEDING 140°F (60°C) WILL PERMANENTLY DAMAGE THE FAN AND VOID THE WARRANTY.
ELECTRICAL SAFETY INSTRUCTIONS
WARNING – To Reduce the Risk Of Fire, Electrical Shock, or Injury to Persons, Observe the Following:
Installation work and electrical wiring must be done by a qualified person(s) in accordance with all applicable codes and standards, including fire-rated construction and accessibility.
Your In-Line Duct Fan
TM
must be connected to a 110/120 Volt AC, 60Hz fuse or circuit breaker protected power source only in a manner approved by all applicable codes. Never connect your In-Line Duct Fan
TM
to
a 240 Volt AC blower motor or other 240 Volt AC system. Never connect your In-Line Duct Fan
TM
to a variable-speed (ECM) furnace blower. For a two-speed In-Line Duct Fan
TM
, never connect directly to multiple
taps on the furnace blower; always use isolation relays.
The power source must be protected by a fuse or circuit breaker rated at a minimum of 15 amperes.
You may also supply power to your In-Line Duct Fan
TM
using the Suncourt DuctStat
®
Temperature Sensitive Switch
TM
or a standard on/off switch (Purchased Separately).
For In-Line Duct Fans
TM
without power cord attached, all connections to the power supply must be made inside the electrical box provided with the unit. Use power supply conductors and wire nuts of appropriate
size and type. Attach a wire nut to any unused lead in a 2-speed In-Line Duct Fan
TM
. The power supply wiring must always include a ground wire properly terminated at the fan (green wire).
For In-Line Duct Fans
TM
with power cord attached, the cord can be plugged in to any standard (NEMA 5-15) 3-prong outlet. The outlet supplying power to the cord must include a ground terminal properly
connected to a ground source. The power cord should be secured to a location where it is not subject to damage, abrasion, or temperatures exceeding 140°F (60°C).
For maximum performance and minimum noise, the best location to install your In-Line Duct Fan
TM
is 6–10 feet from the register that needs the boosted air.
To prevent air leaks, use a good quality aluminum foil duct tape to seal the seams in the ductwork after installing the In-Line Duct Fan
TM
.
By utilizing tapered reducers, you may install larger diameter duct fans in smaller diameter ducts to achieve greater boosted airflow.
Always leave your In-Line Duct Fan
TM
accessible for maintenance, cleaning, or repair.
ACCESSORY INFO
Ductstat
®
Temperature Sensitive Switch
TM
, model DS100
The In-Line Duct Fan
TM
can be controlled by our Ductstat
®
to operate the fan. This is the easiest way to interlock your In-Line Duct Fan
TM
to your furnace. Simply plug your fan into the Ductstat
®
and set the controls
to operate the fan only when conditioned air is sensed inside the boosted duct. Please visit www.suncourt.com for more info on the Ductstat
®
Temperature Sensitive Switch
TM
.
Standard Variable Speed Control, model VS100
The speed of your non-corded In-Line Duct Fan
TM
(models DB412E, DB414E, DB416E) can be controlled with our model VS100 Variable Speed Control. This speed control utilizes solid-state circuitry to safely
adjust the fan speed without damaging the motor. The speed control mounts inside a standard 2x4 electrical box and includes a cover plate and mounting hardware.
GENERAL INSTALLATION NOTES
WARNING – NEVER USE A RHEOSTAT OR LIGHT DIMMER SWITCH TO CONROL YOUR FAN SPEED. A SOLID-STATE SPEED CONTROLLER MUST BE USED TO AVOID DAMAGE TO THE MOTOR.
Please visit www.suncourt.com for more info on these or other accessories.
In-Line Duct Fans
TM
with power cord attached have the model number extension DBxxxC
In-Line Duct Fans
TM
with electrical box attached have the model number extension DBxxxE
INSTALLATION INSTRUCTIONS
1. Locate the place in the duct where you wish to install the In-Line Duct Fan™.
2. Tape the enclosed template to the duct with the arrow pointing in the direction of the airflow. Cut out the required opening by first drilling a pilot hole and cutting along the dashed
line using a jig saw or tin snips.
3. Place the Inductor® In-Line Duct Fan™ in the opening, making sure that the fan blade can turn freely. Align the arrow on the unit in the direction of airflow.
4a. Connect the spring through the middle hole provided in the base plate, stretch the spring over the duct and through the middle hole on the other side of the loose plate. Bend the
ends of the spring over to secure, providing a snug installation.
4b. Secure the In-Line Duct Fan™ in position with the supplied #6 sheet metal screws using the provided holes in the base plate of the unit.
5. Finish the installation by covering the seams in the duct with a good quality aluminum foil duct tape.
MODEL: DB100C
MODELS: DB200C, DB204C
1. Locate the place in the duct where you wish to install the In-Line Duct Fan™. Align arrow label on unit in direction of airflow.
FLEXIBLE DUCT
2a. Simply cut the flexible duct and slide the In-Line Duct Fan™ in place by slipping the cut flexible duct ends over the crimped ends on the In-Line Duct Fan™,
making sure the unit is well supported.
Complete the installation by securing the In-Line Duct Fan™ to the flexible duct with a good quality aluminum foil duct tape or nylon cable ties.
METAL DUCT
2b. Remove a section of the existing ductwork and slide the In-Line Duct Fan™ in place by slipping the duct ends over the crimped ends of the unit. Complete the
installation by securing the In-Line Duct Fan™ to the metal duct with the supplied #6 sheet metal screws spaced evenly around the circumference on each end of
the unit.
3. Finish the installation by covering the seams in the duct with a good quality aluminum foil duct tape.
LEA Y CONSERVE ESTAS INSTRUCCIONES
INSTRUCCIONES DE SEGURIDAD IMPORTANTES
INSTUCCIONES DE FUNCIONAMIENTO IN-LINE DUCT FANS™
1. Locate the place in the duct where you wish to install the In-Line Duct Fan™. Align arrow label on unit in the direction of the airflow.
FLEXIBLE DUCT
2a. Install connectors onto any uncrimped ends of the unit. Then simply cut the flexible duct and slide the In-Line Duct Fan™ in place by slipping the cut flexible duct ends
over the connectors or crimped ends on the In-Line Duct Fan™, making sure the unit is well supported. Complete the installation by securing the In-Line Duct Fan™ to the
flexible duct with a good quality aluminum foil duct tape or nylon cable ties.
METAL DUCT
2b. Install connectors onto any uncrimped ends of the unit, or crimp your existing ductwork. Then simply place the existing duct over the crimped ends of the unit, or the
existing crimped ductwork into the unit. Secure the In-Line Duct Fan™ to the metal duct with the supplied #6 sheet metal screws spaced evenly around the circumference
on each end of the unit.
3. Finish the installation by covering the seams in the duct with a good quality aluminum foil duct tape.
MODELS: DB205C, 206C, 208C, 210C, 212C, 306E, 308E, 310E, 412E, 414E, 416E, 6GTC
WIRING INSTRUCTIONS FOR IN-LINE DUCT FANS™ WITHOUT POWER CORDS ATTACHED:
DB306E, DB308E and DB310E:
Never connect red and black wires together!
IMPORTANT NOTICE - In-Line Dut Fans
TM
without power cord attached.
Single Speed - DB4xxE
The motor of your In-Line Duct Fan™ may have 1 White and 1 Black wire or 2 Black wires. If you have a motor with a White and Black wire, connect the White motor wire
to the White supply wire and the Black motor wire to the Black supply wire. If you have a motor with 2 black wires, connect either of the Black wires to the White supply
wire and the other Black wire to the Black supply wire.
Two Speed - DB3xxE
Make sure you connect the colored wire as shown in the table below. Failure to connect correctly will destroy the motor. Make sure to attach a wire nut to any unused wire
lead. No warranty claim for an incorrectly wired motor will be accepted by Suncourt.
Airflow
Existing
flexible duct
Secure with duct tape or
nylon cable ties
Airflow
Secure with
sheet metal screws
Existing
metal duct
DB306E, DB308E, and DB310E: Never connect LOW and HIGH wires together. For single speed operation, select the LOW
or HIGH speed wire for your application and attach a wire nut to the unused wire lead. When either the LOW or HIGH speed
wire is energized there will be voltage present in the other wire.
For two-speed operation you must never supply power to both LOW and HIGH speed leads simultaneously. You must
isolate the power to LOW and HIGH speeds using a relay or switch. If connecting to a HVAC blower please consult with
the system manufacturer or qualified HVAC contractor. Never connect to a DC blower system.
Green wire from
Suncourt
motor.
Green wire from
Suncourt
motor.
DB412E
DB414E DB416E
Black wire or White wire
(see note above) from
Suncourt motor.
White (neutral or common)
wire from power source
Black (hot or line)
from power source
Green (ground) wire
from power source
Black wire from
Suncourt
motor.
MODELS
DB306E, DB308E,
DB310E
White wire from
Suncourt
motor.
LOW fan speed: Red
wire from
Suncourt
motor.
HIGH fan speed: Black
wire from
Suncourt
motor.
Suncourt Inc. recommends that you clean your In-Line Duct Fan™ at regular intervals, similar to what is recommended for the fan of your furnace, no less than twice a year. Keep your In-Line Duct Fan™ free of
lint, dust, and debris. The In-Line Duct Fan™ must never be exposed to temperatures over 140°F (60°C).
CLEANING AND MAINTENANCE
ONE YEAR LIMITED WARRANTY
Subject to the following limitations, Suncourt Inc. (manufacturer) warrants that the In-Line Duct Fan™ will, for 1 (one) year from date of original retail purchase, but not exceeding 2 (two) years from date of
manufacture, remain free from appearance of defects in workmanship or materials.
This warranty is subject to the following limitations: (a) manufacturer’s liability is limited to the replacement or repair of the unit, as decided by the manufacturer; (b) a defective unit must be returned, prepaid, with
proof of purchase, well packaged to avoid damage in transit; and (c) this warranty does not apply to defects resulting from the alteration, abuse, accidental damage, unauthorized repair, or misuse of the unit. This
warranty is given in lieu of all other warranties, guarantees, and conditions on manufacturer’s part, and the manufacturer shall have no tortious or other liability in respect to this In-Line Duct Fan™. Ship unit to
Suncourt Inc. only after obtaining a Return Goods Authorization (RGA) number. Returns without this RGA number will not be accepted.
Actual product appearance may differ from illustrations. Suncourt reserves the right to modify any or all of its products' features, designs, components and specifications without notice.
Airflow
Secure with
sheet metal screws
Existing
metal duct
Airflow
Existing
flexible duct
Secure with duct tape or
nylon cable ties
ADVERTENCIA: RIESGO DE DESCARGA ELÉCTRICA. PUEDEN CAUSAR LESIONES GRAVES O LA MUERTE: DESCONECTAR Y/O REMOTO BLOQUEAR TODOS SUMINISTROS DE ENERGÍA
ELÉCTRICA ANTES DE REALIZAR CUALQUIER TRABAJO DE MANTENIMIENTO O INSTALACIÓN. CUANDO EL DISPOSITIVO PARA DESCONECTAR EL SEVVICIO ELECTRICO NO PUEDE SER
CERRADO CON ALGUN TIPO DE TRABA, SUJETE FUERTEMENTE AL PANEL DE SERVICIO, UNA ETIQUETA DE ADVERTENCIA PROMINENTE.
ADVERTENCIA: UTILICE ÚNICAMENTE CABLES DE ALIMENTACIÓN COBRE.
ADVERTENCIA - PARA USO EN VENTILACIÓN GENERAL. NO UTILIZAR PARA ELIMINAR MATERIALES Y VAPORES PELIGROSOS O EXPLOSIVOS. NO UTILICE PARA ESCAPE EL AIRE CARGADO
CON PELUSA, GRASA, O ACEITE.
ADVERTENCIA - PRODUCTO DESTINADO PARA LA INSTALACIÓN DE UN CONDUCTO EN LÍNEA CON LOS DOS EXTREMOS DEL VENTILADOR CONECTADO AL CONDUCTO DE TRABAJO (VER
INSTRUCCIONES DE INSTALACIÓN SECCIÓN). POR CUALQUIER OTRA INSTALACIÓN, GUARDIAS SE DEBEN INSTALAR PARA PREVENIR ACCIDENTAL CONTACTO CON LA HOJA DEL VENTILADOR
EN MOVIMIENTO A MENOS QUE LA UNIDAD SE MONTA CON LOS PRECIOS MÁS BAJOS PARTES MÓVILES POR LO MENOS 2,4 M (8 PIES) ARRIBA PISO DE O GRADO.
ADVERTENCIA - FAN ESTÁ FABRICADO SOLO CONEXIÓN A UN CONDUCTO DE SUMINISTRO DE UN SOLO SALA DE LOS GASES DE ESCAPE (MODELOS: DB100C, DB200C, DB204C, DB205C,
DB206C, DB208C, DB306E, DB308E)
Utilice esta unidad sólo de la manera indicada por el fabricante. Si tiene alguna pregunta, póngase en contacto con el fabricante. Usted puede llamar al fabricante durante el horario normal en 1-800-999-3267 o
enviar sus preguntas desde nuestro sitio web: www.suncourt.com.
In-Line Duct Fans
TM
están diseñados para aumentar seco acondicionado (caliente o frío) flujo interior de los conductos de aire forzado los sistemas con temperaturas entre 40 °F (4 °C) y 140 °F (60 °C).
Suncourt no acepta responsabilidad alguna para su uso de este producto en otras aplicaciones.
EXPOSICIÓN A TEMPERATURAS SUPERIORES A FLUJO 140° F (60° C) FORMA PERMANENTE DAÑAR EL VENTILADOR Y ANULAR LA GARANTÍA.
INSTRUCCIONES DE SEGURIDAD ELÉCTRICA
ADVERTENCIA - Para reducir el riesgo de incendio, choque eléctrico, o lesiones a personas, observe lo siguiente:
El trabajo de instalación y cableado eléctrico debe ser realizado por una persona calificada (s) de acuerdo con todos los códigos y normas aplicables, incluyendo la construcción y la accesibilidad a prueba de
fuego.
El In-Line Duct Fan
TM
debe estar conectado a un fusible de 60 Hz o disyuntor protegido fuente de alimentación de 110/120 voltios AC sólo en una forma aprobada por todos los códigos aplicables. Nunca conecte
su In-Line Duct Fan
TM
a un motor de ventilador Volt AC 240 u otro sistema de 240 voltios de corriente alterna. Nunca conecte su In-Line Duct Fan
TM
con el velocidad variable (ECM) horno. Para las dos velocidades
In Line Duct Fan
TM
, nunca conecte directamente con las conexiones eléctricas en el Ventilador de HVAC; siempre use aislamiento relés.
La fuente de alimentación debe estar protegido por un fusible o interruptor de circuito con un mínimo de 15 amperios.
También puede suministrar energía al In-Line Duct Fan
TM
por medio de un interruptor estándar de Encendido o apagado mediante un termostato DuctStat® Temperature Sensitive Switch
TM
(Vendido Por Separado).
Para In-Line Duct Fans
TM
sin cable de alimentación conectado, todas las conexiones a la fuente de alimentación se deben hacer dentro de la caja eléctrica suministrado con la unidad. Utilice conductores de
alimentación y tuercas de cable de tamaño y tipo apropiado. Coloque una tuerca para cable a cualquier plomo sin utilizar en un 2 velocidades en línea Conducto Fan
TM
. El cableado de alimentación debe incluir
siempre un cable a tierra adecuadamente terminado en el ventilador (cable verde) .
Para In-Line Duct Fans
TM
con cable de alimentación conectado, el cable se puede conectar a cualquier estándar (NEMA 5-15) de 3 clavijas. La salida de suministrar alimentación al cable debe incluir una terminal
de tierra correctamente conectado a una fuente de tierra. El cable de alimentación debe ser fijado a una ubicación en la que no está sujeto a daños, a la abrasión, o temperaturas superiores a 140° F (60° C).
Con el máximo rendimiento y el mínimo ruido, la mejor ubicación para instalar el conducto In-Line Duct Fan
TM
es de 6 - 10 pies de distancia de los gases de escape.
Para evitar fugas de aire, utilizar una buena calidad de aluminio cinta adhesiva de aluminio para sellar las juntas de los conductos después de instalar el In-Line Duct Fan
TM
.
Siempre deje su In-Line Duct Fan
TM
accesible para el mantenimiento, limpieza o reparación.
INFORMACIÓN DE ACCESORIOS
Temperatura Ductstat® Switch
TM
Sensible, modelo DS100
El In-Line Duct Fan
TM
puede ser controlado por nuestro Ductstat®. Esta es la forma más fácil de cierre patronal su In-Line Duct Fan
TM
desde su sistema de calefacción. Enchufar el ventilador en el Ductstat® los y
siga las instrucciones para operar el ventilador Cuando sólo aire caliente o frío se detecta Dentro del conducto. Por favor, visite www.suncourt.com para obtener más información sobre la Ductstat® Temperatura
Switch
TM
sensible.
Standard control de velocidad variable, modelo VS100
La velocidad de su no-cable In-Line Duct Fan
TM
(modelos DB412E, DB414E, DB416E) se puede controlar con nuestro modelo VS100 de control de velocidad variable. Este control de velocidad utiliza circuitos de
estado sólido para ajustar la velocidad del ventilador de manera segura sin dañar el motor ELECTRICO. El control de velocidad se monta dentro de un estándar de 2x4 cuadro eléctrico e incluye una placa de
cubierta y el hardware de montaje.
NOTAS GENERALES PARA LA INSTALACIÓN
ADVERTENCIA - NUNCA UTILICE UN REÓSTATO O LUZ DIMMER PARA CONROL LA VELOCIDAD DEL VENTILADOR. UN ESTADO SÓLIDO CONTROLADOR DE VELOCIDAD DEBER UTILIZARSE
PARA EVITAR DAÑOS EN EL MOTOR
Por favor, visite www.suncourt.com para obtener más información sobre estos u otros accesorios.
In-Line Duct Fans
TM
con la caja eléctrica con tenga el sufijo Dbxxx-E
In-Line Duct Fans
TM
con un cable electrico atado tenga el sufijo DBxxxC
INSTRUCCIONES DE INSTALACIÓN
MODELO DB100C
1. Ubique el lugar del conducto donde desea instalar el In-Line Duct Fan™.
2. Adhiera la plantilla suministrada al conducto con la flecha señalando en la dirección del flujo de aire. Corte la abertura requerida, taladrando primero un orificio de control y cortando a lo largo
de la línea punteada con una sierra de vaivén o una tijereta para cortar estaño.
3. Coloque el Inductor® In-Line Duct Fan™ en la abertura, verificando que la hélice del ventilador pueda rotar libremente. Alinee la flecha en la unidad señalando la dirección del flujo de aire.
4a. Conecte el resorte a través del orificio central en la placa base, estire el resorte y doble el extremo para una instalación ajustada.
4b. Fije el In-line Duct Fan™ en posición con los tornillos para chapa metálica #6 suministrados, utilizando los orificios en la placa base de la unidad. Puede finalizar la instalación cubriendo las
costuras del conducto con cinta adhesiva de buena calidad especial para conductos.
5. Acabe la instalación cubriendo las conexión en el conducto con cinta adhesiva de buena calidad especial para conductos.
MODEL0S: DB200C, DB204C
TUBO FLEXIBLE
2a. Simplemente corte el conducto flexible y coloque el In-Line Duct Fan™ en su lugar deslizando el conducto flexible cortado sobre los extremos con reborde del In-Line
Duct Fan™, y asegúrese de que la unidad tenga suficiente apoyo. Complete la instalación asegurando el In-Line Duct Fan™, al conducto flexible, con cinta adhesiva de
buena calidad especial para conductos o con un cable de nylon.
1. Localice en el conducto el lugar donde desea instalar el In-Line Duct Fan™, alinear en la unidad la etiqueta con la flecha en la dirección del flujo de aire.
Flujo
de aire
Conducto
flexible existente
Conecte al conducto flexible, con cinta
adhesiva de buena calidad especial para
conductos o con un cable de nylon
CONDUCTO DE METAL
2b. Retire una sección de la canalización existente y deslizar el In-Line Duct Fan™ en su lugar deslizando los extremos del conducto sobre los extremos con reborde de
la unidad. Complete la instalación asegurando el In-Line Duct Fan™ al conducto de metal con los tornillos #6 (proporcionados) para chapa metálica, colocándolos de
manera uniforme alrededor de la circunferencia en cada uno de los extremos de la unidad.
3. Acabe la instalación cubriendo las conexión en el conducto con cinta adhesiva de buena calidad especial para conductos.
Flujo
de aire
Asegurar con tornillos
para chapa metálica
Conducto de
metal existente
LIMPIEZA Y MANTENIMIENTO
UN AÑO DE GARANTÍA
Dos velocidades - DB3xxE
Asegúrese de conectar los cables de colores según las instrucciones a continuación. La conexión incorrecta
de los cables destruirá el motor. Asegúrese de colocar una tuerca para cable a cualquier sin utilizar cable.
Suncourt Inc. no aceptará reclamaciones de garantía por un motor cableado incorrectamente.
Instrucciones de cableado para ventiladores en línea sin los cables de electricidad adjunto.
DB306E: ¡Nunca conecte los alambres amarillos y rojos juntos!
DB308E y DB310E: ¡Nunca conecte los alambres rojos y negros juntos!
DB306E, DB308E y DB310E: Nunca conecte los alambres BAJA y ALTA juntos. Para la operación de velocidad unica, seleccione la cable BAJA o ALTA velocidad para su aplicación y coloque una tuerca para
cable a cualquier sin utilizar cable. Cuando se energiza el cable BAJA o ALTA velocidad habrá tensión presente en el otro cable. Para la operación de dos velocidades nunca debe alimentar a ambos BAJA y
ALTA velocidad conduce simultáneamente. Se debe aislar el poder de BAJA y ALTA velocidad utilizando un relé o interruptor.
Si está conectado a un soplador de la HVAC consulte con el fabricante o el contratista HVAC. Nunca conecte a un sistema de ventilador de DC.
Suncourt Inc. recomienda limpiar el In-Line Duct Fan™ a intervalos regulares, en forma similar a la recomendada para el ventilador del calefactor, pero dos veces por año como mínimo. Conserve el In-Line
Duct Fan™ libre de pelusas, polvo y desechos. El In-Line Duct Fan™ no debe exponerse nunca a temperaturas que excedan los 140°F (60°C).
Con sujeción a las siguientes limitaciones, la empresa fabricante, Suncourt Inc., garantiza que durante un (1) año a partir de la fecha original de compra minorista, pero sin exceder un plazo de dos (2) años a
partir de la fecha de fabricación, el Inductor® In-Line Duct Fan™ no presentará defectos de fabricación, o de materiales. Esta garantía está sujeta a las siguientes limitaciones: (a) la responsabilidad del fabricante
se limita a reemplazar o reparar la unidad, a criterio del fabricante; (b) la unidad defectuosa se deberá devolver, empaquetado bien para evitar daño en el tránsito, pagado por adelantado con la prueba de la
compra, y (c) esta garantía no cubre defectos resultantes de alteración, uso inadecuado, daño accidental o reparación por personal no autorizado de la unidad. Esta garantía sustituye todas las otras
certificaciones, garantías y condiciones otorgadas por los fabricantes de partes, y el fabricante no tendrá responsabilidad extracontractual o de otro tipo respecto del Inductor® In-Line Duct Fan™. Envíe la unidad
a Suncourt Inc. sólo después de obtener una autorización de productos devueltos (RGA). Las devoluciones sin este número RGA no serán aceptados. El aspecto real del producto puede variar de ilustraciones.
Suncourt reserva la derecha de modificarse las características del producto, de los diseños, de los componentes y de las características sin aviso.
Cable verde del
Suncourt motor
Cable verde del
Suncourt motor
Cable verde del
Suncourt motor
DB412E
DB414E DB416E
Cable negro o cable
blanco (ver nota anterior)
del Suncourt motor
Cable blanco (neutro o
común) de la fuente de
alimentación
Cable negro (vivo o línea)
de la fuente de alimentación
Cable verde (tierra) de la
fuente de alimentación
Cable negro del
Suncourt motor
DB306E
MODELOS
Cable negro del
Suncourt motor
Velocidad del ventilador BAJA:
Cable amarillo del Suncourt motor
Velocidad del motor ALTA:
Cable rojo del Suncourt motor
DB308E, DB310E
Cable blanco del
Suncourt motor
Velocidad del ventilador BAJA:
Cable rojo del Suncourt motor
Velocidad del motor ALTA:
Cable negro del Suncourt motor
MODEL0S: DB205C, 206C, 208C, 210C, 212C, 306E, 308E, 310E, 412E, 414E, 416E, 6GTC
1. Localice en el conducto el lugar donde desea instalar el In-Line Duct Fan™, alinear en la unidad la etiqueta con la flecha en la dirección del flujo de aire.
TUBO FLEXIBLE
2a. Simplemente corte el conducto flexible y coloque el In-Line Duct Fan™ en su lugar deslizando el conducto flexible cortado sobre los extremos con reborde del In-Line
Duct Fan™, y asegúrese deque la unidad tenga suficiente apoyo. Complete la instalación asegurando el In-Line Duct Fan™, al conducto flexible, con cinta adhesiva de
buena calidad especial para conductos o con un cable de nylon.
CONDUCTO DE METAL
2b. Retire una sección de la canalización existente y deslizar el In-Line Duct Fan™ en su lugar deslizando los extremos del conducto sobre los extremos con reborde de la
unidad. Completela instalación asegurando el In-Line Duct Fan™ al conducto de metal con los tornillos #6 (proporcionados) para chapa metálica, colocándolos de manera
uniforme alrededor de la circunferencia en cada uno de los extremos de la unidad.
3. Acabe la instalación cubriendo las conexión en el conducto con cinta adhesiva de buena calidad especial para conductos.
AVISO IMPORTANTE - In-Line Dut Fans
TM
sin cable de alimentación conectado.
Velocidad única - DB4xxE
El motor del In-Line Duct Fan™ puede tener 1 cable blanco y 1 cable negro o dos cables negros. Si tiene un
motor con un cable blanco y un cable negro, conecte el cable blanco del motor al cable blanco de la fuente
de alimentación, y el cable negro del motor al cable negro de la fuente de alimentación. Si tiene un motor con
dos cables negros, conecte cualquiera de los cables negros al cable blanco de la fuente de alimentación y el
otro cable negro al cable negro de la fuente de alimentación.
Flujo
de aire
Conducto
flexible existente
Asegure con las ataduras de cables
de la cinta o del nilón del conducto
Flujo
de aire
Asegurar con tornillos
para chapa metálica
Conducto de
metal existente
AVERTISSEMENT - FAN EST SEULEMENT CONVENABLE POUR CONNEXION À UN CONDUIT ALIMENTATION AVEC CHAMBRE SIMPLE DÉCHARGE (MODÈLES: DB100C, DB200C, DB204C, DB205C, DB206C,
DB208C, DB306E, DB308E)
Utilisez cet appareil uniquement de la manière prévue par le fabricant. Si vous avez des questions, contactez le fabricant.
Vous pouvez téléphoner au fabricant pendant les heures normales de bureau au 1-800-999-3267 ou soumettre vos questions sur notre site web: www.suncourt.com.
In-Line Duct Fans
TM
sont conçus pour augmenter sèche climatise (chauffé ou refroidi) intérieur débit d'air dans les conduits forceé de systèmes à air avec des températures entre 40° F (4° C) et 140° F (60° C).
Suncourt accepte aucune responsabilité pour l'utilisation de ce produit dans d'autres applications.
EXPOSITION À DES TEMPÉRATURES DE DÉBIT D'AIR SUPÉRIEURE À 140° F (60° C) ENDOMMAGER EN PERMANENCE LE FAN ET ANNULER LA GARANTIE.
CONSIGNES DE SÉCURITÉ ÉLECTRIQUE
AVERTISSEMENT - Pour ramener le risque du feu ou de choc électrique ou de dommages aux personnes, observez ce qui suit:
Le travail d'installation et le câblage électrique doivent étre faits par la personne qualifiée(s) selon tous les codes et normes applicables, y compris la construction feu-évaluée.
Votre ventilateur In-Line Duct Fan
TM
doit être branché sur une alimentation à courant alternatif de 110/120 volts, 60Hz protégée par une fusible ou un disjoncteur seulement d'une maniére approuvée par tous les
codes en vigueur. Ne jamais brancher votre In-Line Duct Fan
TM
à un moteur de soufflante avec courant alternatif de 240 volts ou à d'autres systèmes fonctionnant sur 240 volts. Ne jamais brancher votre In-Line
Duct Fan
TM
à une vitesse variable (ECM) de soufflante de chauffage. Pour un deux-vitesse In-Line Duct Fan
TM
, ne jamais brancher directement sur plusieurs robinets sur le four de soufflante; utilisez toujours
l'isolement relais.
La source d'énergie doit être protégée par un fusible ou un disjoncteur évalué à 15 ampères au minimum.
Vous pouvez également puissance votre In-Line Duct Fan
TM
utilisant le Suncourt DuctStat® Temperature Sensitive Switch
TM
ou une norme interrupteur marche / arrêt (vendu séparément).
Pour In-Line Duct Fans
TM
sans cordon d'alimentation fixé, toutes les connexions à l'alimentation doivent être faites à l'intérieur de la boîte électrique fourni avec l'appareil. Utilisez conducteurs d'alimentation et des
écrous de fil de approprié taille et type. Fixer un écrou de fil à n'importe quel plomb inutilisé dans un 2 vitesses In-Line Duct Fan
TM
. Le câblage d'alimentation doit toujours comporter un fil de terre correctement
terminé au le ventilateur (fil vert).
Pour In-Line Duct Fans
TM
avec cordon d'alimentation fixé, le cordon peut être branché en n'importe quel standard (NEMA 5-15) de prise avec mise à la terre. La prise fournissé alimenter à le cordon doit inclure
une terminal de terre ce qui est correctement connecté à une sol source. Le cordon d'alimentation doit être fixé à un endroit où il ne est pas soumis à des dégâts, à l'abrasion, ou à des températures dépassant
140° F (60° C).
NOTES D'INSTALLATION GÉNÉRALES
Pour performance maximale et un minimum de bruit, le meilleur endroit pour installer votre In-Line Duct Fan
TM
est de 6 à 10 pieds par la grille d'aération qui besoins l'air d'être augmenteé.
Pour éviter les fuites d'air, utiliser un bon aluminium de qualité conduit de ruban métallique pour sceller les joints dans les conduits après l'installation du In-Line Duct Fan
TM
.
En utilisant réducteurs coniques, vous pouvez installer grands ventilateurs pour gaines de diamètre dans les conduits de diamètre plus petit pour atteindre une plus grande augmenter de circulation de l'air.
Toujours laisser votre In-Line Duct Fan
TM
accessibles pour l'entretien, le nettoyage, ou la réparation.
INFO ACCESSOIRE
Ductstat
®
Temperature Sensitive Switch
TM
, modèles DS100
L'In-Line Duct Fan
TM
peut être contrôlé par notre Ductstat® à faire fonctionner le ventilateur. Ce est la aisément façon de verrouiller votre In-Line Duct Fan
TM
à votre fournaise. Il suffit de brancher votre ventilateur à
le Ductstat® et réglez les commandes à fonctionner le ventilateur seulement lorsque conditionné air est détecté à l'intérieur du conduit avec augmenteé air. Plaît visitez www.suncourt.com pour plus d'infos sur le
Ductstat® Temperature Sensitive Switch
TM
Norme de contrôle de vitesse variable, modèle VS100
La vitesse de votre non-filaires conduit In-Line Duct FanTM (modèles DB412E, DB414E, DB416E) peuvent être contrôlés avec modèle Suncourt VS100 Contrôle de vitesse variable. Cette régulation de vitesse
utilise solid state circuits en toute sécurité pour régler la vitesse du ventilateur sans endommager le moteur. Le contrôle de la vitesse montures standard de l'intérieur 2x4 boîtier électrique et comprend une plaque
de couvercle et la boulonnerie de montage.
AVERTISSEMENT - NE JAMAIS UTILISER UN RHÉOSTAT OU ATTÉNUATEUR POUR CONTRÔLER VOTRE VITESSE DE VENTILATEUR. UN ÉTAT SOLIDE CONTRÔLEUR DE VITESSE DOIT ÊTRE
UTILISÉ POUR ÉVITER D'ENDOMMAGER LE MOTEUR.
Veuillez visiter www.suncourt.com pour plus d'infos sur ces ou autres accessoires.
INSTALLATION INSTRUCTIÓNS
In-Line Duct Fans
TM
avec la boîte électrique joint ayez suffixe DbxxxE
In-Line Duct Fans
TM
avec le cordon attaché ayez suffix DBxxxC
CONDUIT MÉTALLIQUE
2b. Enlevez une partie des conduits existants et placez le ventilateur In-Line Duct Fan™ en glissant les extrémités du conduit sur les extrémités ondulées de l'appareil.
Terminez l'installation en attachant bien le ventilateur In-Line Duct Fan™ au conduit métallique avec les vis à tôle No.6 fournies espacées à égale distance autour de la
circonférence sur chaque extrémité de l'appareil.
3. Couvrez les coutures dans le conduit avec ruban adhésif aluminium.
Circulation
d’air
Bien attacher avec des vis á tôle
Conduit
métallique existant
1. Trouvez l'endroit dans le conduit où vous voulez installer le ventilateur In-Line Duct Fan™. Aligner la flèche sur l'appareil dans la direction de circulation d'air.
CONDUIT FLEXIBLE
2a. Installez les raccords sur n'importe quelle des extrémités pas ondulées de l'appareil. Puis coupez simplement le conduit
flexible et placez le ventilateur In-Line Duct Fan™ en glissant les extrémités du conduit flexible coupé sur les raccords ou extrémités ondulées sur le ventilateur In-Line Duct
Fan™, en s'assurant que l'appareil est bien supporté. Terminez l'installation en attachant bien le ventilateur In-Line Duct Fan™ au conduit flexible avec du ruban adhésif pour
conduits ou des attache-câbles en nylon.
CONDUIT MÉTALLIQUE
2b. Installer les raccords sur n'importe quelle des extrémités pas ondulées de l'appareil, ou sertir vos conduits existants. Puis placez simplement le conduit existant sur les
extrémités ondulées de l'appareil, ou les conduits ondulés existants dans l'appareil. Bien attacher le ventilateur In-Line Duct Fan™ au conduit métallique avec les vis à tôle
No.6 fournies espacées à égale distance autour de la circonférence sur chaque extrémité de l'appareil.
3. Couvrez les coutures dans le conduit avec ruban adhésif aluminium.
MODÈLES: DB205C, 206C, 208C, 210C, 212C, 306E, 308E, 310E, 412E, 414E, 416E, 6GTC
NOTIFICATION IMPORTANTE - In-Line Dut Fans
TM
sans cordon d'alimentation est branché.
Vitesse Simple - DB4xxE
Le moteur de votre In-Line Duct Fan™ peut avoir 1 fil Blanc et 1 Noir ou 2 fils Noirs. Si vous avez un moteur avec un fil Blanc et Noir, reliez le fil Blanc de moteur au fil Blanc d'approvisionnement et le fil Noir de
moteur au fil Noir d'approvisionnement. Si vous avez un moteur avec 2 fils Noirs, reliez l'un ou l'autre des fils Noirs au fil Blanc d'approvisionnement et à l'autre fil Noir au fil Noir d'approvisionnement.
À Deux Vitesses -DB3xxE
Veillez-vous pour relier le fil coloré comme montré ci-dessous. Le manque de se relier correctement détruira le moteur. Assurez-vous d'attacher un serre-fils à n'importe quel fil inutilisé. Aucune réclamation de
garantie pour un moteur inexactement de câble ne sera acceptée par Suncourt.
Circulation
d’air
Conduit flexible
existant
Fixez avec du ruban adhésif pour
conduits de bonne qualité ou des
attache-câbles en nylon
Circulation
d’air
Bien attacher avec des vis á tôle
Conduit
métallique existant
DB306E, DB308E et DB310E: Ne reliez ensemble jamais les fils LENTE et RAPIDE. Pour un fonctionnement à
vitesse seul, sélectionnez la vitesse de fils LENTE ou RAPIDE pour votre application et attacher un serre-fils
quel fil inutilisé. Lorsque le fils de vitesse LENTE ou RAPIDE est alimenté sous tension l'autre fil aura lieu. Pour
fonctionnement de deux vitesses ne reliez approvisionner jamais alimenter les deux vitesse de fils LENTE et
RAPIDE simultanément. Vous moût isoler le alimentation de vitesses LENTE et RAPIDE à l'aide d'un relais ou un
commutator électrique.
Si la connexion à un ventilateur de CVC veuillez consulter le fabricant du système ou un installateur HVAC. Ne
jamais raccorder à un système de ventilateur DC.
Instructions de câblage pour In-Line Duct Fans™ sans les cordons de secteur ont attaché:
DB306E: Ne reliez ensemble jamais les fils jaunes et rouges!
DB308E et DB310E: Ne reliez ensemble jamais les fils rouges et noirs!
Suncourt Inc. recommande que vous nettoyez votre ventilateur In-Line Duct Fan™ à des intervalles réguliers, semblable à ce qui est recommandé pour le ventilateur de votre chaudière, mais au moins deux fois
par an. Garder votre ventilateur In-Line Duct Fan™ propre sans peluches, sans poussière ni débris. Le ventilateur In-Line Duct Fan™ ne doit jamais être exposé à des températures au-dessus de 60°C (140°F).
GARANTIE D’UN AN
NETTOYAGE ET ENTRETIEN
Sous réserve des limitations suivantes, Suncourt Inc. (le fabricant) garantie le ventilateur In-Line Duct Fan™ contre tout défaut de pièce et de main d'oeuvre pour une période d'un (1) an à partir de la date d'achat
original, mais n'excédant pas deux ans à partir de la date de fabrication. Cette garantie est sous réserve des limitations suivantes: (a) la responsabilité du fabricant est limitée au remplacement ou à la réparation
de l'appareil, suivant la décision par le fabricant; (b) un appareil défectueux doit être renvoyé, bien emballé pour éviter des dommages en transit, les frais de transport payés à l'avance et avec preuve d'achat; et
(c) cette garantie ne s'applique pas aux dommages causés par des modifications, l'abus, des dommages accidentels, des réparations pas autorisées, ou la mauvaise utilisation de l'appareil. Cette garantie est
donnée à la place de toutes autres garanties et conditions de la part du fabricant, et le fabricant n'aura aucune autre responsabilité en ce qui concerne ce ventilateur In-Line Duct Fan™. Expédiez l'unité à
Suncourt Inc seulement après l'obtention d'une autorisation de retour de marchandise (RGA). Les retours sans ce numéro de RGA ne seront pas acceptées. L’apperance de produit peut différer des illustrations.
Suncourt se réserve le droit de modifier partiellement ou entierement les caractéristiques du produit, de conceptions, de composants et de caractéristiques sans préavis.
Vert câblage du
Suncourt moteur.
Vert câblage du
Suncourt moteur.
Vert câblage du
Suncourt moteur.
DB412E
DB414E DB416E
Noir ou blanc câblage
du moteur. Le Suncourt
moteur n‘est pas polarise.
Blanc (neutre ou commun)
câblage de la source
d‘alimentation.
Noir (tension/conductrice de
courant) câblage de la source
d ‘ alimentation.
Vert (Terre/Masse) câblage
de la source d ‘ alimentation.
Noir câblage du moteur.
Remarques: Le Suncourt
moteur n‘est pas polarise.
DB306E
MODÈLES
Noir câblage du
Suncourt moteur.
Vitesse Lente: Jaune câblage
du Suncourt moteur.
Vitesse Rapide: Rouge câblage
du Suncourt moteur.
DB308E, DB310E
Blanc câblage du
Suncourt moteur.
Vitesse Lente: Rouge câblage
du Suncourt moteur.
Vitesse Rapide: Noir câblage
du Suncourt moteur.
WNT600-1015-A05-HD
MODÈLES: DB100C
1. Trouvez l'endroit dans le conduit où vous voulez installer le ventilateur In-Line Duct Fan™.
2. Collez le gabarit ci-joint au conduit avec la flèche orientée dans la direction du courant d'air. Découpez l'ouverture requise en perçant premièrement un trou pilote et en coupant le long des
lignes pointillées avec une scie sauteuse ou des cisailles.
3. Placez le ventilateur Inductor® In-Line Duct Fan™ dans l'ouverture, en s'assurant que l'hélice du ventilateur puisse tourner librement. Alignez la flèche sur l'appareil dans la direction de
circulation d'air.
4a. Accrochez le ressort à travers le trou du milieu prévu dans la plaque de base, tirez sur le ressort et replier l'extrémité pour obtenir une installation bien ajustée.
4b. Bien serrer en place le ventilateur In-Line Duct Fan™ avec les vis à tôle No. 6 fournies en utilisant les trous prévus dans la plaque de base de l'appareil. Vous pouvez terminer l'installation en
recouvrant les joints dans le conduit avec du ruban adhésif pour conduits de bonne qualité.
5. Couvrez les coutures dans le conduit avec ruban adhésif aluminium.
CONSIGNES GÉNÉRALES DE SÉCURITÉ
LIRE ET CONSERVER CES DIRECTIVES
DIRECTIVES POUR L’INSTALLATION DE VENTILATEURS IN-LINE DUCT FANS™
AVERTISSEMENT - RISQUE DE CHOC ÉLECTRIQUE. PEUT PROVOQUER DES BLESSURES OU LA MORT: DÉCONNECTEZ ET / OU VERROU TOUS ÉLECTRIQUE À DISTANCE ALIMENTATIONS AVANT DE
RÉPARER OU INSTALLATION. QUAND LES MOYENS
DÉBRANCHANT DE SERVICE NE PEUVENT PAS ÊTRE VERROUILLES, ATTACHEZ SOLIDEMENT UN PROÉMINENT DISPOSITIF D'AVERTISSEMENT, TEL QU'UNE ETIQUETTE AU PANNEAU DE SERVICE.
AVERTISSEMENT - EMPLOI FIL DE CUIVRE SEULEMENT.
ADVERTISSEMENT - POUR GÉNÉRAL AÉRATION SEULEMENT. N'UTILISEZ PAS POUR ÉPUISER MATÉRIAUX DANGEREUX OU EXPLOSIFS ET VAPEURS. N'UTILISEZ PAS À D'ÉCHAPPEMENT D'AIR CONTENANT
LINT, DE LA GRAISSE OU DE L'HUILE.
AVERTISSEMENT - INTENTIONNÉ PRODUIT INSTALLATION EST POUR INLINE CONDUIT FAN AVEC LES DEUX EXTRÉMITÉS
RACCORDÉS À CONDUIT (VOIR NOTICE D'INSTALLATION SECTION). POUR TOUTE AUTRE INSTALLATION, DES PROTECTEURS DOIVENT ÊTRE INSTALLÉS POUR EMPÊCHER TOUT CONTACT INVOLONTAIRE
AVEC LE DÉPLACEMENT FAN BLADE EXCEPTÉ SI L'UNITÉ EST MONTÉ AVEC LE PLUS BAS PIÈCES AU MOINS 2,4 M (8FT) AU-DESSUS PLANCHER OU TERRE NIVEAU.
1. Trouvez l'endroit dans le conduit où vous voulez installer le ventilateur In-Line Duct Fan™. Aligner la flèche sur l'appareil dans la direction de circulation d'air.
CONDUIT FLEXIBLE
2a. Coupez simplement le conduit flexible et placez le ventilateur In-Line Duct Fan™ en glissant les extrémités du conduit flexible coupé sur les extrémités ondulées sur le
ventilateur In-Line Duct Fan™, en s'assurant que l'appareil soit bien supporté. Terminez l'installation en attachant bien le ventilateur In-Line Duct Fan™ au conduit flexible
avec du ruban adhésif pour conduits de bonne qualité ou des attache-câbles en nylon.
MODÈLES: DB200C, DB204C
Circulation
d’air
Conduit flexible
existant
Fixez avec du ruban adhésif pour
conduits de bonne qualité ou des
attache-câbles en nylon
SUNCOURT INC.
500 W. SECOND AVENUE • P.O. BOX 40
DURANT, IOWA 52747-0040
1-800-999-FANS (3267)
www.suncourt.com
INSTALLATION INSTRUCTIONS FOR IN-LINE DUCT FANS™
READ AND SAVE THESE INSTRUCTIONS
GENERAL SAFETY INSTRUCTIONS
WARNING – RISK OF ELECTRIC SHOCK. CAN CAUSE INJURY OR DEATH: DISCONNECT AND/OR LOCKOUT ALL REMOTE ELECTRIC POWER SUPPLIES BEFORE SERVICING OR INSTALLING.
WHEN THE SERVICE DISCONNECTING MEANS CANNNOT BE LOCKED, SECURELY FASTEN A PROMINENT WARNING DEVICE, SUCH AS A TAG TO THE SERVICE PANEL.
WARNING – USE COPPER SUPPLY WIRES ONLY.
WARNING – FOR GENERAL VENTILATING USE ONLY. DO NOT USE TO EXHAUST HAZARDOUS OR EXPLOSIVE MATERIALS AND VAPORS. DO NOT USE TO EXHAUST AIR LADEN WITH LINT,
GREASE, OR OIL.
WARNING – PRODUCT INTENDED INSTALLATION IS AN INLINE DUCT FAN WITH BOTH ENDS CONNECTED TO DUCTWORK (SEE INSTALLATION INSTRUCTIONS SECTION). FOR ANY OTHER
INSTALLATION, GUARDS MUST BE INSTALLED TO PREVENT UNINTENTIONAL CONTACT WITH MOVING FAN BLADE UNLESS THE UNIT IS MOUNTED WITH THE LOWEST MOVING PARTS AT
LEAST 2.4M (8FT) ABOVE FLOOR OR GRADE LEVEL.
WARNING – FAN IS SUITABLE FOR ONLY CONNECTION TO A DUCT SUPPLYING SINGLE-ROOM DISCHARGE (MODELS: DB100C, DB200C, DB204C, DB205C, DB206C, DB208C, DB306E, DB308E)
Use this unit only in the manner intended by the manufacturer. If you have any questions, contact the manufacturer. You may phone the manufacturer during normal business hours at 1-800-999-3267 or submit
your questions from our website: www.suncourt.com.
In-Line Duct Fans
TM
are designed to boost dry conditioned (heated or cooled) indoor airflow in ducts of forced air systems with temperatures between 40°F (4°C) and 140°F (60°C). Suncourt accepts no
responsibility for use of this product in other applications.
EXPOSURE TO AIRFLOW TEMPERATURES EXCEEDING 140°F (60°C) WILL PERMANENTLY DAMAGE THE FAN AND VOID THE WARRANTY.
ELECTRICAL SAFETY INSTRUCTIONS
WARNING – To Reduce the Risk Of Fire, Electrical Shock, or Injury to Persons, Observe the Following:
Installation work and electrical wiring must be done by a qualified person(s) in accordance with all applicable codes and standards, including fire-rated construction and accessibility.
Your In-Line Duct Fan
TM
must be connected to a 110/120 Volt AC, 60Hz fuse or circuit breaker protected power source only in a manner approved by all applicable codes. Never connect your In-Line Duct Fan
TM
to
a 240 Volt AC blower motor or other 240 Volt AC system. Never connect your In-Line Duct Fan
TM
to a variable-speed (ECM) furnace blower. For a two-speed In-Line Duct Fan
TM
, never connect directly to multiple
taps on the furnace blower; always use isolation relays.
The power source must be protected by a fuse or circuit breaker rated at a minimum of 15 amperes.
You may also supply power to your In-Line Duct Fan
TM
using the Suncourt DuctStat
®
Temperature Sensitive Switch
TM
or a standard on/off switch (Purchased Separately).
For In-Line Duct Fans
TM
without power cord attached, all connections to the power supply must be made inside the electrical box provided with the unit. Use power supply conductors and wire nuts of appropriate
size and type. Attach a wire nut to any unused lead in a 2-speed In-Line Duct Fan
TM
. The power supply wiring must always include a ground wire properly terminated at the fan (green wire).
For In-Line Duct Fans
TM
with power cord attached, the cord can be plugged in to any standard (NEMA 5-15) 3-prong outlet. The outlet supplying power to the cord must include a ground terminal properly
connected to a ground source. The power cord should be secured to a location where it is not subject to damage, abrasion, or temperatures exceeding 140°F (60°C).
For maximum performance and minimum noise, the best location to install your In-Line Duct Fan
TM
is 6–10 feet from the register that needs the boosted air.
To prevent air leaks, use a good quality aluminum foil duct tape to seal the seams in the ductwork after installing the In-Line Duct Fan
TM
.
By utilizing tapered reducers, you may install larger diameter duct fans in smaller diameter ducts to achieve greater boosted airflow.
Always leave your In-Line Duct Fan
TM
accessible for maintenance, cleaning, or repair.
ACCESSORY INFO
Ductstat
®
Temperature Sensitive Switch
TM
, model DS100
The In-Line Duct Fan
TM
can be controlled by our Ductstat
®
to operate the fan. This is the easiest way to interlock your In-Line Duct Fan
TM
to your furnace. Simply plug your fan into the Ductstat
®
and set the controls
to operate the fan only when conditioned air is sensed inside the boosted duct. Please visit www.suncourt.com for more info on the Ductstat
®
Temperature Sensitive Switch
TM
.
Standard Variable Speed Control, model VS100
The speed of your non-corded In-Line Duct Fan
TM
(models DB412E, DB414E, DB416E) can be controlled with our model VS100 Variable Speed Control. This speed control utilizes solid-state circuitry to safely
adjust the fan speed without damaging the motor. The speed control mounts inside a standard 2x4 electrical box and includes a cover plate and mounting hardware.
GENERAL INSTALLATION NOTES
WARNING – NEVER USE A RHEOSTAT OR LIGHT DIMMER SWITCH TO CONROL YOUR FAN SPEED. A SOLID-STATE SPEED CONTROLLER MUST BE USED TO AVOID DAMAGE TO THE MOTOR.
Please visit www.suncourt.com for more info on these or other accessories.
In-Line Duct Fans
TM
with power cord attached have the model number extension DBxxxC
In-Line Duct Fans
TM
with electrical box attached have the model number extension DBxxxE
INSTALLATION INSTRUCTIONS
1. Locate the place in the duct where you wish to install the In-Line Duct Fan™.
2. Tape the enclosed template to the duct with the arrow pointing in the direction of the airflow. Cut out the required opening by first drilling a pilot hole and cutting along the dashed
line using a jig saw or tin snips.
3. Place the Inductor® In-Line Duct Fan™ in the opening, making sure that the fan blade can turn freely. Align the arrow on the unit in the direction of airflow.
4a. Connect the spring through the middle hole provided in the base plate, stretch the spring over the duct and through the middle hole on the other side of the loose plate. Bend the
ends of the spring over to secure, providing a snug installation.
4b. Secure the In-Line Duct Fan™ in position with the supplied #6 sheet metal screws using the provided holes in the base plate of the unit.
5. Finish the installation by covering the seams in the duct with a good quality aluminum foil duct tape.
MODEL: DB100C
MODELS: DB200C, DB204C
1. Locate the place in the duct where you wish to install the In-Line Duct Fan™. Align arrow label on unit in direction of airflow.
FLEXIBLE DUCT
2a. Simply cut the flexible duct and slide the In-Line Duct Fan™ in place by slipping the cut flexible duct ends over the crimped ends on the In-Line Duct Fan™,
making sure the unit is well supported.
Complete the installation by securing the In-Line Duct Fan™ to the flexible duct with a good quality aluminum foil duct tape or nylon cable ties.
METAL DUCT
2b. Remove a section of the existing ductwork and slide the In-Line Duct Fan™ in place by slipping the duct ends over the crimped ends of the unit. Complete the
installation by securing the In-Line Duct Fan™ to the metal duct with the supplied #6 sheet metal screws spaced evenly around the circumference on each end of
the unit.
3. Finish the installation by covering the seams in the duct with a good quality aluminum foil duct tape.
LEA Y CONSERVE ESTAS INSTRUCCIONES
INSTRUCCIONES DE SEGURIDAD IMPORTANTES
INSTUCCIONES DE FUNCIONAMIENTO IN-LINE DUCT FANS™
1. Locate the place in the duct where you wish to install the In-Line Duct Fan™. Align arrow label on unit in the direction of the airflow.
FLEXIBLE DUCT
2a. Install connectors onto any uncrimped ends of the unit. Then simply cut the flexible duct and slide the In-Line Duct Fan™ in place by slipping the cut flexible duct ends
over the connectors or crimped ends on the In-Line Duct Fan™, making sure the unit is well supported. Complete the installation by securing the In-Line Duct Fan™ to the
flexible duct with a good quality aluminum foil duct tape or nylon cable ties.
METAL DUCT
2b. Install connectors onto any uncrimped ends of the unit, or crimp your existing ductwork. Then simply place the existing duct over the crimped ends of the unit, or the
existing crimped ductwork into the unit. Secure the In-Line Duct Fan™ to the metal duct with the supplied #6 sheet metal screws spaced evenly around the circumference
on each end of the unit.
3. Finish the installation by covering the seams in the duct with a good quality aluminum foil duct tape.
MODELS: DB205C, 206C, 208C, 210C, 212C, 306E, 308E, 310E, 412E, 414E, 416E, 6GTC
WIRING INSTRUCTIONS FOR IN-LINE DUCT FANS™ WITHOUT POWER CORDS ATTACHED:
DB306E, DB308E and DB310E:
Never connect red and black wires together!
IMPORTANT NOTICE - In-Line Dut Fans
TM
without power cord attached.
Single Speed - DB4xxE
The motor of your In-Line Duct Fan™ may have 1 White and 1 Black wire or 2 Black wires. If you have a motor with a White and Black wire, connect the White motor wire
to the White supply wire and the Black motor wire to the Black supply wire. If you have a motor with 2 black wires, connect either of the Black wires to the White supply
wire and the other Black wire to the Black supply wire.
Two Speed - DB3xxE
Make sure you connect the colored wire as shown in the table below. Failure to connect correctly will destroy the motor. Make sure to attach a wire nut to any unused wire
lead. No warranty claim for an incorrectly wired motor will be accepted by Suncourt.
Airflow
Existing
flexible duct
Secure with duct tape or
nylon cable ties
Airflow
Secure with
sheet metal screws
Existing
metal duct
DB306E, DB308E, and DB310E: Never connect LOW and HIGH wires together. For single speed operation, select the LOW
or HIGH speed wire for your application and attach a wire nut to the unused wire lead. When either the LOW or HIGH speed
wire is energized there will be voltage present in the other wire.
For two-speed operation you must never supply power to both LOW and HIGH speed leads simultaneously. You must
isolate the power to LOW and HIGH speeds using a relay or switch. If connecting to a HVAC blower please consult with
the system manufacturer or qualified HVAC contractor. Never connect to a DC blower system.
Green wire from
Suncourt
motor.
Green wire from
Suncourt
motor.
DB412E
DB414E DB416E
Black wire or White wire
(see note above) from
Suncourt motor.
White (neutral or common)
wire from power source
Black (hot or line)
from power source
Green (ground) wire
from power source
Black wire from
Suncourt
motor.
MODELS
DB306E, DB308E,
DB310E
White wire from
Suncourt
motor.
LOW fan speed: Red
wire from
Suncourt
motor.
HIGH fan speed: Black
wire from
Suncourt
motor.
Suncourt Inc. recommends that you clean your In-Line Duct Fan™ at regular intervals, similar to what is recommended for the fan of your furnace, no less than twice a year. Keep your In-Line Duct Fan™ free of
lint, dust, and debris. The In-Line Duct Fan™ must never be exposed to temperatures over 140°F (60°C).
CLEANING AND MAINTENANCE
ONE YEAR LIMITED WARRANTY
Subject to the following limitations, Suncourt Inc. (manufacturer) warrants that the In-Line Duct Fan™ will, for 1 (one) year from date of original retail purchase, but not exceeding 2 (two) years from date of
manufacture, remain free from appearance of defects in workmanship or materials.
This warranty is subject to the following limitations: (a) manufacturer’s liability is limited to the replacement or repair of the unit, as decided by the manufacturer; (b) a defective unit must be returned, prepaid, with
proof of purchase, well packaged to avoid damage in transit; and (c) this warranty does not apply to defects resulting from the alteration, abuse, accidental damage, unauthorized repair, or misuse of the unit. This
warranty is given in lieu of all other warranties, guarantees, and conditions on manufacturer’s part, and the manufacturer shall have no tortious or other liability in respect to this In-Line Duct Fan™. Ship unit to
Suncourt Inc. only after obtaining a Return Goods Authorization (RGA) number. Returns without this RGA number will not be accepted.
Actual product appearance may differ from illustrations. Suncourt reserves the right to modify any or all of its products' features, designs, components and specifications without notice.
Airflow
Secure with
sheet metal screws
Existing
metal duct
Airflow
Existing
flexible duct
Secure with duct tape or
nylon cable ties
ADVERTENCIA: RIESGO DE DESCARGA ELÉCTRICA. PUEDEN CAUSAR LESIONES GRAVES O LA MUERTE: DESCONECTAR Y/O REMOTO BLOQUEAR TODOS SUMINISTROS DE ENERGÍA
ELÉCTRICA ANTES DE REALIZAR CUALQUIER TRABAJO DE MANTENIMIENTO O INSTALACIÓN. CUANDO EL DISPOSITIVO PARA DESCONECTAR EL SEVVICIO ELECTRICO NO PUEDE SER
CERRADO CON ALGUN TIPO DE TRABA, SUJETE FUERTEMENTE AL PANEL DE SERVICIO, UNA ETIQUETA DE ADVERTENCIA PROMINENTE.
ADVERTENCIA: UTILICE ÚNICAMENTE CABLES DE ALIMENTACIÓN COBRE.
ADVERTENCIA - PARA USO EN VENTILACIÓN GENERAL. NO UTILIZAR PARA ELIMINAR MATERIALES Y VAPORES PELIGROSOS O EXPLOSIVOS. NO UTILICE PARA ESCAPE EL AIRE CARGADO
CON PELUSA, GRASA, O ACEITE.
ADVERTENCIA - PRODUCTO DESTINADO PARA LA INSTALACIÓN DE UN CONDUCTO EN LÍNEA CON LOS DOS EXTREMOS DEL VENTILADOR CONECTADO AL CONDUCTO DE TRABAJO (VER
INSTRUCCIONES DE INSTALACIÓN SECCIÓN). POR CUALQUIER OTRA INSTALACIÓN, GUARDIAS SE DEBEN INSTALAR PARA PREVENIR ACCIDENTAL CONTACTO CON LA HOJA DEL VENTILADOR
EN MOVIMIENTO A MENOS QUE LA UNIDAD SE MONTA CON LOS PRECIOS MÁS BAJOS PARTES MÓVILES POR LO MENOS 2,4 M (8 PIES) ARRIBA PISO DE O GRADO.
ADVERTENCIA - FAN ESTÁ FABRICADO SOLO CONEXIÓN A UN CONDUCTO DE SUMINISTRO DE UN SOLO SALA DE LOS GASES DE ESCAPE (MODELOS: DB100C, DB200C, DB204C, DB205C,
DB206C, DB208C, DB306E, DB308E)
Utilice esta unidad sólo de la manera indicada por el fabricante. Si tiene alguna pregunta, póngase en contacto con el fabricante. Usted puede llamar al fabricante durante el horario normal en 1-800-999-3267 o
enviar sus preguntas desde nuestro sitio web: www.suncourt.com.
In-Line Duct Fans
TM
están diseñados para aumentar seco acondicionado (caliente o frío) flujo interior de los conductos de aire forzado los sistemas con temperaturas entre 40 °F (4 °C) y 140 °F (60 °C).
Suncourt no acepta responsabilidad alguna para su uso de este producto en otras aplicaciones.
EXPOSICIÓN A TEMPERATURAS SUPERIORES A FLUJO 140° F (60° C) FORMA PERMANENTE DAÑAR EL VENTILADOR Y ANULAR LA GARANTÍA.
INSTRUCCIONES DE SEGURIDAD ELÉCTRICA
ADVERTENCIA - Para reducir el riesgo de incendio, choque eléctrico, o lesiones a personas, observe lo siguiente:
El trabajo de instalación y cableado eléctrico debe ser realizado por una persona calificada (s) de acuerdo con todos los códigos y normas aplicables, incluyendo la construcción y la accesibilidad a prueba de
fuego.
El In-Line Duct Fan
TM
debe estar conectado a un fusible de 60 Hz o disyuntor protegido fuente de alimentación de 110/120 voltios AC sólo en una forma aprobada por todos los códigos aplicables. Nunca conecte
su In-Line Duct Fan
TM
a un motor de ventilador Volt AC 240 u otro sistema de 240 voltios de corriente alterna. Nunca conecte su In-Line Duct Fan
TM
con el velocidad variable (ECM) horno. Para las dos velocidades
In Line Duct Fan
TM
, nunca conecte directamente con las conexiones eléctricas en el Ventilador de HVAC; siempre use aislamiento relés.
La fuente de alimentación debe estar protegido por un fusible o interruptor de circuito con un mínimo de 15 amperios.
También puede suministrar energía al In-Line Duct Fan
TM
por medio de un interruptor estándar de Encendido o apagado mediante un termostato DuctStat® Temperature Sensitive Switch
TM
(Vendido Por Separado).
Para In-Line Duct Fans
TM
sin cable de alimentación conectado, todas las conexiones a la fuente de alimentación se deben hacer dentro de la caja eléctrica suministrado con la unidad. Utilice conductores de
alimentación y tuercas de cable de tamaño y tipo apropiado. Coloque una tuerca para cable a cualquier plomo sin utilizar en un 2 velocidades en línea Conducto Fan
TM
. El cableado de alimentación debe incluir
siempre un cable a tierra adecuadamente terminado en el ventilador (cable verde) .
Para In-Line Duct Fans
TM
con cable de alimentación conectado, el cable se puede conectar a cualquier estándar (NEMA 5-15) de 3 clavijas. La salida de suministrar alimentación al cable debe incluir una terminal
de tierra correctamente conectado a una fuente de tierra. El cable de alimentación debe ser fijado a una ubicación en la que no está sujeto a daños, a la abrasión, o temperaturas superiores a 140° F (60° C).
Con el máximo rendimiento y el mínimo ruido, la mejor ubicación para instalar el conducto In-Line Duct Fan
TM
es de 6 - 10 pies de distancia de los gases de escape.
Para evitar fugas de aire, utilizar una buena calidad de aluminio cinta adhesiva de aluminio para sellar las juntas de los conductos después de instalar el In-Line Duct Fan
TM
.
Siempre deje su In-Line Duct Fan
TM
accesible para el mantenimiento, limpieza o reparación.
INFORMACIÓN DE ACCESORIOS
Temperatura Ductstat® Switch
TM
Sensible, modelo DS100
El In-Line Duct Fan
TM
puede ser controlado por nuestro Ductstat®. Esta es la forma más fácil de cierre patronal su In-Line Duct Fan
TM
desde su sistema de calefacción. Enchufar el ventilador en el Ductstat® los y
siga las instrucciones para operar el ventilador Cuando sólo aire caliente o frío se detecta Dentro del conducto. Por favor, visite www.suncourt.com para obtener más información sobre la Ductstat® Temperatura
Switch
TM
sensible.
Standard control de velocidad variable, modelo VS100
La velocidad de su no-cable In-Line Duct Fan
TM
(modelos DB412E, DB414E, DB416E) se puede controlar con nuestro modelo VS100 de control de velocidad variable. Este control de velocidad utiliza circuitos de
estado sólido para ajustar la velocidad del ventilador de manera segura sin dañar el motor ELECTRICO. El control de velocidad se monta dentro de un estándar de 2x4 cuadro eléctrico e incluye una placa de
cubierta y el hardware de montaje.
NOTAS GENERALES PARA LA INSTALACIÓN
ADVERTENCIA - NUNCA UTILICE UN REÓSTATO O LUZ DIMMER PARA CONROL LA VELOCIDAD DEL VENTILADOR. UN ESTADO SÓLIDO CONTROLADOR DE VELOCIDAD DEBER UTILIZARSE
PARA EVITAR DAÑOS EN EL MOTOR
Por favor, visite www.suncourt.com para obtener más información sobre estos u otros accesorios.
In-Line Duct Fans
TM
con la caja eléctrica con tenga el sufijo Dbxxx-E
In-Line Duct Fans
TM
con un cable electrico atado tenga el sufijo DBxxxC
INSTRUCCIONES DE INSTALACIÓN
MODELO DB100C
1. Ubique el lugar del conducto donde desea instalar el In-Line Duct Fan™.
2. Adhiera la plantilla suministrada al conducto con la flecha señalando en la dirección del flujo de aire. Corte la abertura requerida, taladrando primero un orificio de control y cortando a lo largo
de la línea punteada con una sierra de vaivén o una tijereta para cortar estaño.
3. Coloque el Inductor® In-Line Duct Fan™ en la abertura, verificando que la hélice del ventilador pueda rotar libremente. Alinee la flecha en la unidad señalando la dirección del flujo de aire.
4a. Conecte el resorte a través del orificio central en la placa base, estire el resorte y doble el extremo para una instalación ajustada.
4b. Fije el In-line Duct Fan™ en posición con los tornillos para chapa metálica #6 suministrados, utilizando los orificios en la placa base de la unidad. Puede finalizar la instalación cubriendo las
costuras del conducto con cinta adhesiva de buena calidad especial para conductos.
5. Acabe la instalación cubriendo las conexión en el conducto con cinta adhesiva de buena calidad especial para conductos.
MODEL0S: DB200C, DB204C
TUBO FLEXIBLE
2a. Simplemente corte el conducto flexible y coloque el In-Line Duct Fan™ en su lugar deslizando el conducto flexible cortado sobre los extremos con reborde del In-Line
Duct Fan™, y asegúrese de que la unidad tenga suficiente apoyo. Complete la instalación asegurando el In-Line Duct Fan™, al conducto flexible, con cinta adhesiva de
buena calidad especial para conductos o con un cable de nylon.
1. Localice en el conducto el lugar donde desea instalar el In-Line Duct Fan™, alinear en la unidad la etiqueta con la flecha en la dirección del flujo de aire.
Flujo
de aire
Conducto
flexible existente
Conecte al conducto flexible, con cinta
adhesiva de buena calidad especial para
conductos o con un cable de nylon
CONDUCTO DE METAL
2b. Retire una sección de la canalización existente y deslizar el In-Line Duct Fan™ en su lugar deslizando los extremos del conducto sobre los extremos con reborde de
la unidad. Complete la instalación asegurando el In-Line Duct Fan™ al conducto de metal con los tornillos #6 (proporcionados) para chapa metálica, colocándolos de
manera uniforme alrededor de la circunferencia en cada uno de los extremos de la unidad.
3. Acabe la instalación cubriendo las conexión en el conducto con cinta adhesiva de buena calidad especial para conductos.
Flujo
de aire
Asegurar con tornillos
para chapa metálica
Conducto de
metal existente
LIMPIEZA Y MANTENIMIENTO
UN AÑO DE GARANTÍA
Dos velocidades - DB3xxE
Asegúrese de conectar los cables de colores según las instrucciones a continuación. La conexión incorrecta
de los cables destruirá el motor. Asegúrese de colocar una tuerca para cable a cualquier sin utilizar cable.
Suncourt Inc. no aceptará reclamaciones de garantía por un motor cableado incorrectamente.
Instrucciones de cableado para ventiladores en línea sin los cables de electricidad adjunto.
DB306E: ¡Nunca conecte los alambres amarillos y rojos juntos!
DB308E y DB310E: ¡Nunca conecte los alambres rojos y negros juntos!
DB306E, DB308E y DB310E: Nunca conecte los alambres BAJA y ALTA juntos. Para la operación de velocidad unica, seleccione la cable BAJA o ALTA velocidad para su aplicación y coloque una tuerca para
cable a cualquier sin utilizar cable. Cuando se energiza el cable BAJA o ALTA velocidad habrá tensión presente en el otro cable. Para la operación de dos velocidades nunca debe alimentar a ambos BAJA y
ALTA velocidad conduce simultáneamente. Se debe aislar el poder de BAJA y ALTA velocidad utilizando un relé o interruptor.
Si está conectado a un soplador de la HVAC consulte con el fabricante o el contratista HVAC. Nunca conecte a un sistema de ventilador de DC.
Suncourt Inc. recomienda limpiar el In-Line Duct Fan™ a intervalos regulares, en forma similar a la recomendada para el ventilador del calefactor, pero dos veces por año como mínimo. Conserve el In-Line
Duct Fan™ libre de pelusas, polvo y desechos. El In-Line Duct Fan™ no debe exponerse nunca a temperaturas que excedan los 140°F (60°C).
Con sujeción a las siguientes limitaciones, la empresa fabricante, Suncourt Inc., garantiza que durante un (1) año a partir de la fecha original de compra minorista, pero sin exceder un plazo de dos (2) años a
partir de la fecha de fabricación, el Inductor® In-Line Duct Fan™ no presentará defectos de fabricación, o de materiales. Esta garantía está sujeta a las siguientes limitaciones: (a) la responsabilidad del fabricante
se limita a reemplazar o reparar la unidad, a criterio del fabricante; (b) la unidad defectuosa se deberá devolver, empaquetado bien para evitar daño en el tránsito, pagado por adelantado con la prueba de la
compra, y (c) esta garantía no cubre defectos resultantes de alteración, uso inadecuado, daño accidental o reparación por personal no autorizado de la unidad. Esta garantía sustituye todas las otras
certificaciones, garantías y condiciones otorgadas por los fabricantes de partes, y el fabricante no tendrá responsabilidad extracontractual o de otro tipo respecto del Inductor® In-Line Duct Fan™. Envíe la unidad
a Suncourt Inc. sólo después de obtener una autorización de productos devueltos (RGA). Las devoluciones sin este número RGA no serán aceptados. El aspecto real del producto puede variar de ilustraciones.
Suncourt reserva la derecha de modificarse las características del producto, de los diseños, de los componentes y de las características sin aviso.
Cable verde del
Suncourt motor
Cable verde del
Suncourt motor
Cable verde del
Suncourt motor
DB412E
DB414E DB416E
Cable negro o cable
blanco (ver nota anterior)
del Suncourt motor
Cable blanco (neutro o
común) de la fuente de
alimentación
Cable negro (vivo o línea)
de la fuente de alimentación
Cable verde (tierra) de la
fuente de alimentación
Cable negro del
Suncourt motor
DB306E
MODELOS
Cable negro del
Suncourt motor
Velocidad del ventilador BAJA:
Cable amarillo del Suncourt motor
Velocidad del motor ALTA:
Cable rojo del Suncourt motor
DB308E, DB310E
Cable blanco del
Suncourt motor
Velocidad del ventilador BAJA:
Cable rojo del Suncourt motor
Velocidad del motor ALTA:
Cable negro del Suncourt motor
MODEL0S: DB205C, 206C, 208C, 210C, 212C, 306E, 308E, 310E, 412E, 414E, 416E, 6GTC
1. Localice en el conducto el lugar donde desea instalar el In-Line Duct Fan™, alinear en la unidad la etiqueta con la flecha en la dirección del flujo de aire.
TUBO FLEXIBLE
2a. Simplemente corte el conducto flexible y coloque el In-Line Duct Fan™ en su lugar deslizando el conducto flexible cortado sobre los extremos con reborde del In-Line
Duct Fan™, y asegúrese deque la unidad tenga suficiente apoyo. Complete la instalación asegurando el In-Line Duct Fan™, al conducto flexible, con cinta adhesiva de
buena calidad especial para conductos o con un cable de nylon.
CONDUCTO DE METAL
2b. Retire una sección de la canalización existente y deslizar el In-Line Duct Fan™ en su lugar deslizando los extremos del conducto sobre los extremos con reborde de la
unidad. Completela instalación asegurando el In-Line Duct Fan™ al conducto de metal con los tornillos #6 (proporcionados) para chapa metálica, colocándolos de manera
uniforme alrededor de la circunferencia en cada uno de los extremos de la unidad.
3. Acabe la instalación cubriendo las conexión en el conducto con cinta adhesiva de buena calidad especial para conductos.
AVISO IMPORTANTE - In-Line Dut Fans
TM
sin cable de alimentación conectado.
Velocidad única - DB4xxE
El motor del In-Line Duct Fan™ puede tener 1 cable blanco y 1 cable negro o dos cables negros. Si tiene un
motor con un cable blanco y un cable negro, conecte el cable blanco del motor al cable blanco de la fuente
de alimentación, y el cable negro del motor al cable negro de la fuente de alimentación. Si tiene un motor con
dos cables negros, conecte cualquiera de los cables negros al cable blanco de la fuente de alimentación y el
otro cable negro al cable negro de la fuente de alimentación.
Flujo
de aire
Conducto
flexible existente
Asegure con las ataduras de cables
de la cinta o del nilón del conducto
Flujo
de aire
Asegurar con tornillos
para chapa metálica
Conducto de
metal existente
AVERTISSEMENT - FAN EST SEULEMENT CONVENABLE POUR CONNEXION À UN CONDUIT ALIMENTATION AVEC CHAMBRE SIMPLE DÉCHARGE (MODÈLES: DB100C, DB200C, DB204C, DB205C, DB206C,
DB208C, DB306E, DB308E)
Utilisez cet appareil uniquement de la manière prévue par le fabricant. Si vous avez des questions, contactez le fabricant.
Vous pouvez téléphoner au fabricant pendant les heures normales de bureau au 1-800-999-3267 ou soumettre vos questions sur notre site web: www.suncourt.com.
In-Line Duct Fans
TM
sont conçus pour augmenter sèche climatise (chauffé ou refroidi) intérieur débit d'air dans les conduits forceé de systèmes à air avec des températures entre 40° F (4° C) et 140° F (60° C).
Suncourt accepte aucune responsabilité pour l'utilisation de ce produit dans d'autres applications.
EXPOSITION À DES TEMPÉRATURES DE DÉBIT D'AIR SUPÉRIEURE À 140° F (60° C) ENDOMMAGER EN PERMANENCE LE FAN ET ANNULER LA GARANTIE.
CONSIGNES DE SÉCURITÉ ÉLECTRIQUE
AVERTISSEMENT - Pour ramener le risque du feu ou de choc électrique ou de dommages aux personnes, observez ce qui suit:
Le travail d'installation et le câblage électrique doivent étre faits par la personne qualifiée(s) selon tous les codes et normes applicables, y compris la construction feu-évaluée.
Votre ventilateur In-Line Duct Fan
TM
doit être branché sur une alimentation à courant alternatif de 110/120 volts, 60Hz protégée par une fusible ou un disjoncteur seulement d'une maniére approuvée par tous les
codes en vigueur. Ne jamais brancher votre In-Line Duct Fan
TM
à un moteur de soufflante avec courant alternatif de 240 volts ou à d'autres systèmes fonctionnant sur 240 volts. Ne jamais brancher votre In-Line
Duct Fan
TM
à une vitesse variable (ECM) de soufflante de chauffage. Pour un deux-vitesse In-Line Duct Fan
TM
, ne jamais brancher directement sur plusieurs robinets sur le four de soufflante; utilisez toujours
l'isolement relais.
La source d'énergie doit être protégée par un fusible ou un disjoncteur évalué à 15 ampères au minimum.
Vous pouvez également puissance votre In-Line Duct Fan
TM
utilisant le Suncourt DuctStat® Temperature Sensitive Switch
TM
ou une norme interrupteur marche / arrêt (vendu séparément).
Pour In-Line Duct Fans
TM
sans cordon d'alimentation fixé, toutes les connexions à l'alimentation doivent être faites à l'intérieur de la boîte électrique fourni avec l'appareil. Utilisez conducteurs d'alimentation et des
écrous de fil de approprié taille et type. Fixer un écrou de fil à n'importe quel plomb inutilisé dans un 2 vitesses In-Line Duct Fan
TM
. Le câblage d'alimentation doit toujours comporter un fil de terre correctement
terminé au le ventilateur (fil vert).
Pour In-Line Duct Fans
TM
avec cordon d'alimentation fixé, le cordon peut être branché en n'importe quel standard (NEMA 5-15) de prise avec mise à la terre. La prise fournissé alimenter à le cordon doit inclure
une terminal de terre ce qui est correctement connecté à une sol source. Le cordon d'alimentation doit être fixé à un endroit où il ne est pas soumis à des dégâts, à l'abrasion, ou à des températures dépassant
140° F (60° C).
NOTES D'INSTALLATION GÉNÉRALES
Pour performance maximale et un minimum de bruit, le meilleur endroit pour installer votre In-Line Duct Fan
TM
est de 6 à 10 pieds par la grille d'aération qui besoins l'air d'être augmenteé.
Pour éviter les fuites d'air, utiliser un bon aluminium de qualité conduit de ruban métallique pour sceller les joints dans les conduits après l'installation du In-Line Duct Fan
TM
.
En utilisant réducteurs coniques, vous pouvez installer grands ventilateurs pour gaines de diamètre dans les conduits de diamètre plus petit pour atteindre une plus grande augmenter de circulation de l'air.
Toujours laisser votre In-Line Duct Fan
TM
accessibles pour l'entretien, le nettoyage, ou la réparation.
INFO ACCESSOIRE
Ductstat
®
Temperature Sensitive Switch
TM
, modèles DS100
L'In-Line Duct Fan
TM
peut être contrôlé par notre Ductstat® à faire fonctionner le ventilateur. Ce est la aisément façon de verrouiller votre In-Line Duct Fan
TM
à votre fournaise. Il suffit de brancher votre ventilateur à
le Ductstat® et réglez les commandes à fonctionner le ventilateur seulement lorsque conditionné air est détecté à l'intérieur du conduit avec augmenteé air. Plaît visitez www.suncourt.com pour plus d'infos sur le
Ductstat® Temperature Sensitive Switch
TM
Norme de contrôle de vitesse variable, modèle VS100
La vitesse de votre non-filaires conduit In-Line Duct FanTM (modèles DB412E, DB414E, DB416E) peuvent être contrôlés avec modèle Suncourt VS100 Contrôle de vitesse variable. Cette régulation de vitesse
utilise solid state circuits en toute sécurité pour régler la vitesse du ventilateur sans endommager le moteur. Le contrôle de la vitesse montures standard de l'intérieur 2x4 boîtier électrique et comprend une plaque
de couvercle et la boulonnerie de montage.
AVERTISSEMENT - NE JAMAIS UTILISER UN RHÉOSTAT OU ATTÉNUATEUR POUR CONTRÔLER VOTRE VITESSE DE VENTILATEUR. UN ÉTAT SOLIDE CONTRÔLEUR DE VITESSE DOIT ÊTRE
UTILISÉ POUR ÉVITER D'ENDOMMAGER LE MOTEUR.
Veuillez visiter www.suncourt.com pour plus d'infos sur ces ou autres accessoires.
INSTALLATION INSTRUCTIÓNS
In-Line Duct Fans
TM
avec la boîte électrique joint ayez suffixe DbxxxE
In-Line Duct Fans
TM
avec le cordon attaché ayez suffix DBxxxC
CONDUIT MÉTALLIQUE
2b. Enlevez une partie des conduits existants et placez le ventilateur In-Line Duct Fan™ en glissant les extrémités du conduit sur les extrémités ondulées de l'appareil.
Terminez l'installation en attachant bien le ventilateur In-Line Duct Fan™ au conduit métallique avec les vis à tôle No.6 fournies espacées à égale distance autour de la
circonférence sur chaque extrémité de l'appareil.
3. Couvrez les coutures dans le conduit avec ruban adhésif aluminium.
Circulation
d’air
Bien attacher avec des vis á tôle
Conduit
métallique existant
1. Trouvez l'endroit dans le conduit où vous voulez installer le ventilateur In-Line Duct Fan™. Aligner la flèche sur l'appareil dans la direction de circulation d'air.
CONDUIT FLEXIBLE
2a. Installez les raccords sur n'importe quelle des extrémités pas ondulées de l'appareil. Puis coupez simplement le conduit
flexible et placez le ventilateur In-Line Duct Fan™ en glissant les extrémités du conduit flexible coupé sur les raccords ou extrémités ondulées sur le ventilateur In-Line Duct
Fan™, en s'assurant que l'appareil est bien supporté. Terminez l'installation en attachant bien le ventilateur In-Line Duct Fan™ au conduit flexible avec du ruban adhésif pour
conduits ou des attache-câbles en nylon.
CONDUIT MÉTALLIQUE
2b. Installer les raccords sur n'importe quelle des extrémités pas ondulées de l'appareil, ou sertir vos conduits existants. Puis placez simplement le conduit existant sur les
extrémités ondulées de l'appareil, ou les conduits ondulés existants dans l'appareil. Bien attacher le ventilateur In-Line Duct Fan™ au conduit métallique avec les vis à tôle
No.6 fournies espacées à égale distance autour de la circonférence sur chaque extrémité de l'appareil.
3. Couvrez les coutures dans le conduit avec ruban adhésif aluminium.
MODÈLES: DB205C, 206C, 208C, 210C, 212C, 306E, 308E, 310E, 412E, 414E, 416E, 6GTC
NOTIFICATION IMPORTANTE - In-Line Dut Fans
TM
sans cordon d'alimentation est branché.
Vitesse Simple - DB4xxE
Le moteur de votre In-Line Duct Fan™ peut avoir 1 fil Blanc et 1 Noir ou 2 fils Noirs. Si vous avez un moteur avec un fil Blanc et Noir, reliez le fil Blanc de moteur au fil Blanc d'approvisionnement et le fil Noir de
moteur au fil Noir d'approvisionnement. Si vous avez un moteur avec 2 fils Noirs, reliez l'un ou l'autre des fils Noirs au fil Blanc d'approvisionnement et à l'autre fil Noir au fil Noir d'approvisionnement.
À Deux Vitesses -DB3xxE
Veillez-vous pour relier le fil coloré comme montré ci-dessous. Le manque de se relier correctement détruira le moteur. Assurez-vous d'attacher un serre-fils à n'importe quel fil inutilisé. Aucune réclamation de
garantie pour un moteur inexactement de câble ne sera acceptée par Suncourt.
Circulation
d’air
Conduit flexible
existant
Fixez avec du ruban adhésif pour
conduits de bonne qualité ou des
attache-câbles en nylon
Circulation
d’air
Bien attacher avec des vis á tôle
Conduit
métallique existant
DB306E, DB308E et DB310E: Ne reliez ensemble jamais les fils LENTE et RAPIDE. Pour un fonctionnement à
vitesse seul, sélectionnez la vitesse de fils LENTE ou RAPIDE pour votre application et attacher un serre-fils
quel fil inutilisé. Lorsque le fils de vitesse LENTE ou RAPIDE est alimenté sous tension l'autre fil aura lieu. Pour
fonctionnement de deux vitesses ne reliez approvisionner jamais alimenter les deux vitesse de fils LENTE et
RAPIDE simultanément. Vous moût isoler le alimentation de vitesses LENTE et RAPIDE à l'aide d'un relais ou un
commutator électrique.
Si la connexion à un ventilateur de CVC veuillez consulter le fabricant du système ou un installateur HVAC. Ne
jamais raccorder à un système de ventilateur DC.
Instructions de câblage pour In-Line Duct Fans™ sans les cordons de secteur ont attaché:
DB306E: Ne reliez ensemble jamais les fils jaunes et rouges!
DB308E et DB310E: Ne reliez ensemble jamais les fils rouges et noirs!
Suncourt Inc. recommande que vous nettoyez votre ventilateur In-Line Duct Fan™ à des intervalles réguliers, semblable à ce qui est recommandé pour le ventilateur de votre chaudière, mais au moins deux fois
par an. Garder votre ventilateur In-Line Duct Fan™ propre sans peluches, sans poussière ni débris. Le ventilateur In-Line Duct Fan™ ne doit jamais être exposé à des températures au-dessus de 60°C (140°F).
GARANTIE D’UN AN
NETTOYAGE ET ENTRETIEN
Sous réserve des limitations suivantes, Suncourt Inc. (le fabricant) garantie le ventilateur In-Line Duct Fan™ contre tout défaut de pièce et de main d'oeuvre pour une période d'un (1) an à partir de la date d'achat
original, mais n'excédant pas deux ans à partir de la date de fabrication. Cette garantie est sous réserve des limitations suivantes: (a) la responsabilité du fabricant est limitée au remplacement ou à la réparation
de l'appareil, suivant la décision par le fabricant; (b) un appareil défectueux doit être renvoyé, bien emballé pour éviter des dommages en transit, les frais de transport payés à l'avance et avec preuve d'achat; et
(c) cette garantie ne s'applique pas aux dommages causés par des modifications, l'abus, des dommages accidentels, des réparations pas autorisées, ou la mauvaise utilisation de l'appareil. Cette garantie est
donnée à la place de toutes autres garanties et conditions de la part du fabricant, et le fabricant n'aura aucune autre responsabilité en ce qui concerne ce ventilateur In-Line Duct Fan™. Expédiez l'unité à
Suncourt Inc seulement après l'obtention d'une autorisation de retour de marchandise (RGA). Les retours sans ce numéro de RGA ne seront pas acceptées. L’apperance de produit peut différer des illustrations.
Suncourt se réserve le droit de modifier partiellement ou entierement les caractéristiques du produit, de conceptions, de composants et de caractéristiques sans préavis.
Vert câblage du
Suncourt moteur.
Vert câblage du
Suncourt moteur.
Vert câblage du
Suncourt moteur.
DB412E
DB414E DB416E
Noir ou blanc câblage
du moteur. Le Suncourt
moteur n‘est pas polarise.
Blanc (neutre ou commun)
câblage de la source
d‘alimentation.
Noir (tension/conductrice de
courant) câblage de la source
d ‘ alimentation.
Vert (Terre/Masse) câblage
de la source d ‘ alimentation.
Noir câblage du moteur.
Remarques: Le Suncourt
moteur n‘est pas polarise.
DB306E
MODÈLES
Noir câblage du
Suncourt moteur.
Vitesse Lente: Jaune câblage
du Suncourt moteur.
Vitesse Rapide: Rouge câblage
du Suncourt moteur.
DB308E, DB310E
Blanc câblage du
Suncourt moteur.
Vitesse Lente: Rouge câblage
du Suncourt moteur.
Vitesse Rapide: Noir câblage
du Suncourt moteur.
WNT600-1015-A05-HD
MODÈLES: DB100C
1. Trouvez l'endroit dans le conduit où vous voulez installer le ventilateur In-Line Duct Fan™.
2. Collez le gabarit ci-joint au conduit avec la flèche orientée dans la direction du courant d'air. Découpez l'ouverture requise en perçant premièrement un trou pilote et en coupant le long des
lignes pointillées avec une scie sauteuse ou des cisailles.
3. Placez le ventilateur Inductor® In-Line Duct Fan™ dans l'ouverture, en s'assurant que l'hélice du ventilateur puisse tourner librement. Alignez la flèche sur l'appareil dans la direction de
circulation d'air.
4a. Accrochez le ressort à travers le trou du milieu prévu dans la plaque de base, tirez sur le ressort et replier l'extrémité pour obtenir une installation bien ajustée.
4b. Bien serrer en place le ventilateur In-Line Duct Fan™ avec les vis à tôle No. 6 fournies en utilisant les trous prévus dans la plaque de base de l'appareil. Vous pouvez terminer l'installation en
recouvrant les joints dans le conduit avec du ruban adhésif pour conduits de bonne qualité.
5. Couvrez les coutures dans le conduit avec ruban adhésif aluminium.
CONSIGNES GÉNÉRALES DE SÉCURITÉ
LIRE ET CONSERVER CES DIRECTIVES
DIRECTIVES POUR L’INSTALLATION DE VENTILATEURS IN-LINE DUCT FANS™
AVERTISSEMENT - RISQUE DE CHOC ÉLECTRIQUE. PEUT PROVOQUER DES BLESSURES OU LA MORT: DÉCONNECTEZ ET / OU VERROU TOUS ÉLECTRIQUE À DISTANCE ALIMENTATIONS AVANT DE
RÉPARER OU INSTALLATION. QUAND LES MOYENS
DÉBRANCHANT DE SERVICE NE PEUVENT PAS ÊTRE VERROUILLES, ATTACHEZ SOLIDEMENT UN PROÉMINENT DISPOSITIF D'AVERTISSEMENT, TEL QU'UNE ETIQUETTE AU PANNEAU DE SERVICE.
AVERTISSEMENT - EMPLOI FIL DE CUIVRE SEULEMENT.
ADVERTISSEMENT - POUR GÉNÉRAL AÉRATION SEULEMENT. N'UTILISEZ PAS POUR ÉPUISER MATÉRIAUX DANGEREUX OU EXPLOSIFS ET VAPEURS. N'UTILISEZ PAS À D'ÉCHAPPEMENT D'AIR CONTENANT
LINT, DE LA GRAISSE OU DE L'HUILE.
AVERTISSEMENT - INTENTIONNÉ PRODUIT INSTALLATION EST POUR INLINE CONDUIT FAN AVEC LES DEUX EXTRÉMITÉS
RACCORDÉS À CONDUIT (VOIR NOTICE D'INSTALLATION SECTION). POUR TOUTE AUTRE INSTALLATION, DES PROTECTEURS DOIVENT ÊTRE INSTALLÉS POUR EMPÊCHER TOUT CONTACT INVOLONTAIRE
AVEC LE DÉPLACEMENT FAN BLADE EXCEPTÉ SI L'UNITÉ EST MONTÉ AVEC LE PLUS BAS PIÈCES AU MOINS 2,4 M (8FT) AU-DESSUS PLANCHER OU TERRE NIVEAU.
1. Trouvez l'endroit dans le conduit où vous voulez installer le ventilateur In-Line Duct Fan™. Aligner la flèche sur l'appareil dans la direction de circulation d'air.
CONDUIT FLEXIBLE
2a. Coupez simplement le conduit flexible et placez le ventilateur In-Line Duct Fan™ en glissant les extrémités du conduit flexible coupé sur les extrémités ondulées sur le
ventilateur In-Line Duct Fan™, en s'assurant que l'appareil soit bien supporté. Terminez l'installation en attachant bien le ventilateur In-Line Duct Fan™ au conduit flexible
avec du ruban adhésif pour conduits de bonne qualité ou des attache-câbles en nylon.
MODÈLES: DB200C, DB204C
Circulation
d’air
Conduit flexible
existant
Fixez avec du ruban adhésif pour
conduits de bonne qualité ou des
attache-câbles en nylon
SUNCOURT INC.
500 W. SECOND AVENUE • P.O. BOX 40
DURANT, IOWA 52747-0040
1-800-999-FANS (3267)
www.suncourt.com

Transcripción de documentos

INSTALLATION INSTRUCTIONS FOR IN-LINE DUCT FANS™ READ AND SAVE THESE INSTRUCTIONS GENERAL SAFETY INSTRUCTIONS WARNING – RISK OF ELECTRIC SHOCK. CAN CAUSE INJURY OR DEATH: DISCONNECT AND/OR LOCKOUT ALL REMOTE ELECTRIC POWER SUPPLIES BEFORE SERVICING OR INSTALLING. WHEN THE SERVICE DISCONNECTING MEANS CANNNOT BE LOCKED, SECURELY FASTEN A PROMINENT WARNING DEVICE, SUCH AS A TAG TO THE SERVICE PANEL. WARNING – USE COPPER SUPPLY WIRES ONLY. WARNING – FOR GENERAL VENTILATING USE ONLY. DO NOT USE TO EXHAUST HAZARDOUS OR EXPLOSIVE MATERIALS AND VAPORS. DO NOT USE TO EXHAUST AIR LADEN WITH LINT, GREASE, OR OIL. WARNING – PRODUCT INTENDED INSTALLATION IS AN INLINE DUCT FAN WITH BOTH ENDS CONNECTED TO DUCTWORK (SEE INSTALLATION INSTRUCTIONS SECTION). FOR ANY OTHER INSTALLATION, GUARDS MUST BE INSTALLED TO PREVENT UNINTENTIONAL CONTACT WITH MOVING FAN BLADE UNLESS THE UNIT IS MOUNTED WITH THE LOWEST MOVING PARTS AT LEAST 2.4M (8FT) ABOVE FLOOR OR GRADE LEVEL. WARNING – FAN IS SUITABLE FOR ONLY CONNECTION TO A DUCT SUPPLYING SINGLE-ROOM DISCHARGE (MODELS: DB100C, DB200C, DB204C, DB205C, DB206C, DB208C, DB306E, DB308E) Use this unit only in the manner intended by the manufacturer. If you have any questions, contact the manufacturer. You may phone the manufacturer during normal business hours at 1-800-999-3267 or submit your questions from our website: www.suncourt.com. In-Line Duct FansTM are designed to boost dry conditioned (heated or cooled) indoor airflow in ducts of forced air systems with temperatures between 40°F (4°C) and 140°F (60°C). Suncourt accepts no responsibility for use of this product in other applications. EXPOSURE TO AIRFLOW TEMPERATURES EXCEEDING 140°F (60°C) WILL PERMANENTLY DAMAGE THE FAN AND VOID THE WARRANTY. ELECTRICAL SAFETY INSTRUCTIONS WARNING – To Reduce the Risk Of Fire, Electrical Shock, or Injury to Persons, Observe the Following: Installation work and electrical wiring must be done by a qualified person(s) in accordance with all applicable codes and standards, including fire-rated construction and accessibility. Your In-Line Duct FanTM must be connected to a 110/120 Volt AC, 60Hz fuse or circuit breaker protected power source only in a manner approved by all applicable codes. Never connect your In-Line Duct FanTM to a 240 Volt AC blower motor or other 240 Volt AC system. Never connect your In-Line Duct FanTM to a variable-speed (ECM) furnace blower. For a two-speed In-Line Duct FanTM, never connect directly to multiple taps on the furnace blower; always use isolation relays. The power source must be protected by a fuse or circuit breaker rated at a minimum of 15 amperes. You may also supply power to your In-Line Duct FanTM using the Suncourt DuctStat® Temperature Sensitive SwitchTM or a standard on/off switch (Purchased Separately). For In-Line Duct FansTM without power cord attached, all connections to the power supply must be made inside the electrical box provided with the unit. Use power supply conductors and wire nuts of appropriate size and type. Attach a wire nut to any unused lead in a 2-speed In-Line Duct FanTM. The power supply wiring must always include a ground wire properly terminated at the fan (green wire). For In-Line Duct FansTM with power cord attached, the cord can be plugged in to any standard (NEMA 5-15) 3-prong outlet. The outlet supplying power to the cord must include a ground terminal properly connected to a ground source. The power cord should be secured to a location where it is not subject to damage, abrasion, or temperatures exceeding 140°F (60°C). GENERAL INSTALLATION NOTES For maximum performance and minimum noise, the best location to install your In-Line Duct FanTM is 6–10 feet from the register that needs the boosted air. To prevent air leaks, use a good quality aluminum foil duct tape to seal the seams in the ductwork after installing the In-Line Duct FanTM. By utilizing tapered reducers, you may install larger diameter duct fans in smaller diameter ducts to achieve greater boosted airflow. Always leave your In-Line Duct FanTM accessible for maintenance, cleaning, or repair. ACCESSORY INFO Ductstat® Temperature Sensitive SwitchTM, model DS100 The In-Line Duct FanTM can be controlled by our Ductstat® to operate the fan. This is the easiest way to interlock your In-Line Duct FanTM to your furnace. Simply plug your fan into the Ductstat® and set the controls to operate the fan only when conditioned air is sensed inside the boosted duct. Please visit www.suncourt.com for more info on the Ductstat® Temperature Sensitive SwitchTM. Standard Variable Speed Control, model VS100 The speed of your non-corded In-Line Duct FanTM (models DB412E, DB414E, DB416E) can be controlled with our model VS100 Variable Speed Control. This speed control utilizes solid-state circuitry to safely adjust the fan speed without damaging the motor. The speed control mounts inside a standard 2x4 electrical box and includes a cover plate and mounting hardware. WARNING – NEVER USE A RHEOSTAT OR LIGHT DIMMER SWITCH TO CONROL YOUR FAN SPEED. A SOLID-STATE SPEED CONTROLLER MUST BE USED TO AVOID DAMAGE TO THE MOTOR. Please visit www.suncourt.com for more info on these or other accessories. INSTALLATION INSTRUCTIONS In-Line Duct FansTM with power cord attached have the model number extension DBxxxC In-Line Duct FansTM with electrical box attached have the model number extension DBxxxE MODEL: DB100C 1. Locate the place in the duct where you wish to install the In-Line Duct Fan™. 2. Tape the enclosed template to the duct with the arrow pointing in the direction of the airflow. Cut out the required opening by first drilling a pilot hole and cutting along the dashed line using a jig saw or tin snips. 3. Place the Inductor® In-Line Duct Fan™ in the opening, making sure that the fan blade can turn freely. Align the arrow on the unit in the direction of airflow. 4a. Connect the spring through the middle hole provided in the base plate, stretch the spring over the duct and through the middle hole on the other side of the loose plate. Bend the ends of the spring over to secure, providing a snug installation. 4b. Secure the In-Line Duct Fan™ in position with the supplied #6 sheet metal screws using the provided holes in the base plate of the unit. 5. Finish the installation by covering the seams in the duct with a good quality aluminum foil duct tape. MODELS: DB200C, DB204C 1. Locate the place in the duct where you wish to install the In-Line Duct Fan™. Align arrow label on unit in direction of airflow. FLEXIBLE DUCT 2a. Simply cut the flexible duct and slide the In-Line Duct Fan™ in place by slipping the cut flexible duct ends over the crimped ends on the In-Line Duct Fan™, making sure the unit is well supported. Complete the installation by securing the In-Line Duct Fan™ to the flexible duct with a good quality aluminum foil duct tape or nylon cable ties. METAL DUCT 2b. Remove a section of the existing ductwork and slide the In-Line Duct Fan™ in place by slipping the duct ends over the crimped ends of the unit. Complete the installation by securing the In-Line Duct Fan™ to the metal duct with the supplied #6 sheet metal screws spaced evenly around the circumference on each end of the unit. 3. Finish the installation by covering the seams in the duct with a good quality aluminum foil duct tape. Airflow Existing Secure with duct tape or flexible duct nylon cable ties Airflow Existing metal duct Secure with sheet metal screws MODÈLES: DB100C 1. Trouvez l'endroit dans le conduit où vous voulez installer le ventilateur In-Line Duct Fan™. 2. Collez le gabarit ci-joint au conduit avec la flèche orientée dans la direction du courant d'air. Découpez l'ouverture requise en perçant premièrement un trou pilote et en coupant le long des lignes pointillées avec une scie sauteuse ou des cisailles. 3. Placez le ventilateur Inductor® In-Line Duct Fan™ dans l'ouverture, en s'assurant que l'hélice du ventilateur puisse tourner librement. Alignez la flèche sur l'appareil dans la direction de circulation d'air. 4a. Accrochez le ressort à travers le trou du milieu prévu dans la plaque de base, tirez sur le ressort et replier l'extrémité pour obtenir une installation bien ajustée. 4b. Bien serrer en place le ventilateur In-Line Duct Fan™ avec les vis à tôle No. 6 fournies en utilisant les trous prévus dans la plaque de base de l'appareil. Vous pouvez terminer l'installation en recouvrant les joints dans le conduit avec du ruban adhésif pour conduits de bonne qualité. 5. Couvrez les coutures dans le conduit avec ruban adhésif aluminium. MODÈLES: DB200C, DB204C 1. Trouvez l'endroit dans le conduit où vous voulez installer le ventilateur In-Line Duct Fan™. Aligner la flèche sur l'appareil dans la direction de circulation d'air. CONDUIT FLEXIBLE 2a. Coupez simplement le conduit flexible et placez le ventilateur In-Line Duct Fan™ en glissant les extrémités du conduit flexible coupé sur les extrémités ondulées sur le ventilateur In-Line Duct Fan™, en s'assurant que l'appareil soit bien supporté. Terminez l'installation en attachant bien le ventilateur In-Line Duct Fan™ au conduit flexible avec du ruban adhésif pour conduits de bonne qualité ou des attache-câbles en nylon. CONDUIT MÉTALLIQUE 2b. Enlevez une partie des conduits existants et placez le ventilateur In-Line Duct Fan™ en glissant les extrémités du conduit sur les extrémités ondulées de l'appareil. Terminez l'installation en attachant bien le ventilateur In-Line Duct Fan™ au conduit métallique avec les vis à tôle No.6 fournies espacées à égale distance autour de la circonférence sur chaque extrémité de l'appareil. 3. Couvrez les coutures dans le conduit avec ruban adhésif aluminium. Circulation d’air Conduit flexible existant Fixez avec du ruban adhésif pour conduits de bonne qualité ou des attache-câbles en nylon Circulation d’air Conduit métallique existant Bien attacher avec des vis á tôle MODÈLES: DB205C, 206C, 208C, 210C, 212C, 306E, 308E, 310E, 412E, 414E, 416E, 6GTC 1. Trouvez l'endroit dans le conduit où vous voulez installer le ventilateur In-Line Duct Fan™. Aligner la flèche sur l'appareil dans la direction de circulation d'air. CONDUIT FLEXIBLE Circulation d’air 2a. Installez les raccords sur n'importe quelle des extrémités pas ondulées de l'appareil. Puis coupez simplement le conduit flexible et placez le ventilateur In-Line Duct Fan™ en glissant les extrémités du conduit flexible coupé sur les raccords ou extrémités ondulées sur le ventilateur In-Line Duct Conduit flexible Fixez avec du ruban adhésif pour conduits de bonne qualité ou des Fan™, en s'assurant que l'appareil est bien supporté. Terminez l'installation en attachant bien le ventilateur In-Line Duct Fan™ au conduit flexible avec du ruban adhésif pour existant attache-câbles en nylon conduits ou des attache-câbles en nylon. CONDUIT MÉTALLIQUE Circulation 2b. Installer les raccords sur n'importe quelle des extrémités pas ondulées de l'appareil, ou sertir vos conduits existants. Puis placez simplement le conduit existant sur les d’air extrémités ondulées de l'appareil, ou les conduits ondulés existants dans l'appareil. Bien attacher le ventilateur In-Line Duct Fan™ au conduit métallique avec les vis à tôle Conduit Bien attacher avec des vis á tôle No.6 fournies espacées à égale distance autour de la circonférence sur chaque extrémité de l'appareil. métallique existant 3. Couvrez les coutures dans le conduit avec ruban adhésif aluminium. NOTIFICATION IMPORTANTE - In-Line Dut FansTM sans cordon d'alimentation est branché. Vitesse Simple - DB4xxE Le moteur de votre In-Line Duct Fan™ peut avoir 1 fil Blanc et 1 Noir ou 2 fils Noirs. Si vous avez un moteur avec un fil Blanc et Noir, reliez le fil Blanc de moteur au fil Blanc d'approvisionnement et le fil Noir de moteur au fil Noir d'approvisionnement. Si vous avez un moteur avec 2 fils Noirs, reliez l'un ou l'autre des fils Noirs au fil Blanc d'approvisionnement et à l'autre fil Noir au fil Noir d'approvisionnement. À Deux Vitesses -DB3xxE Veillez-vous pour relier le fil coloré comme montré ci-dessous. Le manque de se relier correctement détruira le moteur. Assurez-vous d'attacher un serre-fils à n'importe quel fil inutilisé. Aucune réclamation de garantie pour un moteur inexactement de câble ne sera acceptée par Suncourt. Instructions de câblage pour In-Line Duct Fans™ sans les cordons de secteur ont attaché: DB306E: Ne reliez ensemble jamais les fils jaunes et rouges! DB308E et DB310E: Ne reliez ensemble jamais les fils rouges et noirs! DB306E, DB308E et DB310E: Ne reliez ensemble jamais les fils LENTE et RAPIDE. Pour un fonctionnement à vitesse seul, sélectionnez la vitesse de fils LENTE ou RAPIDE pour votre application et attacher un serre-fils quel fil inutilisé. Lorsque le fils de vitesse LENTE ou RAPIDE est alimenté sous tension l'autre fil aura lieu. Pour fonctionnement de deux vitesses ne reliez approvisionner jamais alimenter les deux vitesse de fils LENTE et RAPIDE simultanément. Vous moût isoler le alimentation de vitesses LENTE et RAPIDE à l'aide d'un relais ou un commutator électrique. Si la connexion à un ventilateur de CVC veuillez consulter le fabricant du système ou un installateur HVAC. Ne jamais raccorder à un système de ventilateur DC. MODÈLES Blanc (neutre ou commun) câblage de la source d‘alimentation. Noir (tension/conductrice de courant) câblage de la source d ‘ alimentation. Vert (Terre/Masse) câblage de la source d ‘ alimentation. DB412E DB414E DB416E Noir ou blanc câblage du moteur. Le Suncourt moteur n‘est pas polarise. Noir câblage du moteur. Remarques: Le Suncourt moteur n‘est pas polarise. Vert câblage du Suncourt moteur. DB306E Noir câblage du Suncourt moteur. Vitesse Lente: Jaune câblage du Suncourt moteur. Vitesse Rapide: Rouge câblage du Suncourt moteur. Vert câblage du Suncourt moteur. DB308E, DB310E Blanc câblage du Suncourt moteur. Vitesse Lente: Rouge câblage du Suncourt moteur. Vitesse Rapide: Noir câblage du Suncourt moteur. Vert câblage du Suncourt moteur. NETTOYAGE ET ENTRETIEN Suncourt Inc. recommande que vous nettoyez votre ventilateur In-Line Duct Fan™ à des intervalles réguliers, semblable à ce qui est recommandé pour le ventilateur de votre chaudière, mais au moins deux fois par an. Garder votre ventilateur In-Line Duct Fan™ propre sans peluches, sans poussière ni débris. Le ventilateur In-Line Duct Fan™ ne doit jamais être exposé à des températures au-dessus de 60°C (140°F). GARANTIE D’UN AN Sous réserve des limitations suivantes, Suncourt Inc. (le fabricant) garantie le ventilateur In-Line Duct Fan™ contre tout défaut de pièce et de main d'oeuvre pour une période d'un (1) an à partir de la date d'achat original, mais n'excédant pas deux ans à partir de la date de fabrication. Cette garantie est sous réserve des limitations suivantes: (a) la responsabilité du fabricant est limitée au remplacement ou à la réparation de l'appareil, suivant la décision par le fabricant; (b) un appareil défectueux doit être renvoyé, bien emballé pour éviter des dommages en transit, les frais de transport payés à l'avance et avec preuve d'achat; et (c) cette garantie ne s'applique pas aux dommages causés par des modifications, l'abus, des dommages accidentels, des réparations pas autorisées, ou la mauvaise utilisation de l'appareil. Cette garantie est donnée à la place de toutes autres garanties et conditions de la part du fabricant, et le fabricant n'aura aucune autre responsabilité en ce qui concerne ce ventilateur In-Line Duct Fan™. Expédiez l'unité à Suncourt Inc seulement après l'obtention d'une autorisation de retour de marchandise (RGA). Les retours sans ce numéro de RGA ne seront pas acceptées. L’apperance de produit peut différer des illustrations. Suncourt se réserve le droit de modifier partiellement ou entierement les caractéristiques du produit, de conceptions, de composants et de caractéristiques sans préavis. SUNCOURT INC. 500 W. SECOND AVENUE • P.O. BOX 40 DURANT, IOWA 52747-0040 1-800-999-FANS (3267) www.suncourt.com WNT600-1015-A05-HD
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5

Inductor DB204C Guía de instalación

Tipo
Guía de instalación